- Industrial & lab equipment
- Electrical equipment & supplies
- Power generators
- Guardian
- 5241
- User manual
advertisement
![Guardian 5241, 5243, 5244, 5281, 5282 Installation And Owner's Manual | Manualzz Guardian 5241, 5243, 5244, 5281, 5282 Installation And Owner's Manual | Manualzz](http://s2.manualzz.com/store/data/062001872_1-f6d2c70ae4be993ab53237661ca0af00-360x466.png)
C
LISTED
US
Installation and
Owner’s Manual
7, 10, 13 and 16kW Air-cooled,
Automatic Standby Generators
Models: 005240, 005280 (6 kW NG, 7 kW LP)
005241, 005281 (9 kW NG, 10 kW LP)
005242, 005282 (13 kW NG, 13 kW LP)
005243, 005244, (15 kW NG, 16 kW LP)
Not intended for use as Primary Power in place of utility or in life-support applications.
DANGER
DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!
INTRODUCTION
Thank you for purchasing this model of the Guardian product line by Generac Power Systems Inc. This model is a compact, high performance, air-cooled, engine-driven generator designed to automatically supply electrical power to operate critical loads during a utility power failure.
This unit is factory installed in an all-weather, metal enclosure that is intended exclusively for outdoor installation.
This generator will operate using either vapor withdrawn liquid propane (LP) or natural gas
(NG).
READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, contact the nearest Authorized Dealer for starting, operating and servicing procedures.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING,
CAUTION and NOTE blocks are used to alert personnel to special instructions about a particular operation that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their definitions are as follows:
DANGER
After this heading, read instructions that, if not strictly complied with, will result in serious personal injury, including death, in addition to property damage.
After this heading, read instructions that, if not strictly complied with, may result in serious personal injury or property damage.
After this heading, read instructions that, if not strictly complied with, could result in damage to equipment and/or property.
NOTE:
After this heading, read explanatory statements that require special emphasis.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compliance with the special instructions while performing the service are essential to preventing accidents.
Four commonly used safety symbols accompany the
DANGER, WARNING and CAUTION blocks. The type of information each indicates follows:
This symbol points out important safety information that, if not followed, could endanger personal safety and/or property of others.
This symbol points out potential explosion hazard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock hazard.
The operator is responsible for proper and safe use of the equipment. The manufacturer strongly recommends that the operator read this Owner's Manual and thoroughly understand all instructions before using this equipment. The manufacturer also strongly recommends instructing other users to properly start and operate the unit. This prepares them if they need to operate the equipment in an emergency.
CONTENTS
This manual contains pertinent owner’s information, including warranty, electrical diagrams, exploded views and lists of repair parts, for these different models:
• 05240 & 05280 – 6 kW NG, 7 kW LP, single-cylinder GH-410 Engine
•
•
05241 & 05281 – 9.0 kW NG, 10 kW LP, V-twin
GT-530 Engine
05242 & 05282 – 13 kW NG, 13 kW LP, V-twin GT-
990 Engine
• 05243, 05244, 05283 & 05284 – 15 kW NG, 16 kW
LP, V-twin GT-990 Engine
OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safety checks, to make sure that all maintenance for safe operation is performed promptly, and to have the equipment checked periodically by an Authorized
Dealer. Normal maintenance service and replacement of parts are the responsibility of the owner/operator and, as such, are not considered defects in materials or workmanship within the terms of the warranty.
Individual operating habits and usage contribute to the need for maintenance service.
Proper maintenance and care of the generator ensures a minimum number of problems and keep operating expenses at a minimum. See an Authorized Dealer for service aids and accessories.
HOW TO OBTAIN SERVICE
When the generator requires servicing or repairs, contact an Authorized Dealer for assistance. Service technicians are factory-trained and are capable of handling all service needs.
When contacting an Authorized Dealer about parts and service, always supply the complete model number and serial number of the unit as given on its data decal, which is located on the generator. See section
"The Generator" for decal location.
Model No. ____________ Serial No. ______________
AUTHORIZED
DEALER LOCATION
To locate the nearest AUTHORIZED
DEALER, please call this number:
1-800-333-1322
DEALER LOCATION INFORMATION
CAN BE OBTAINED AT THIS NUMBER or visit www.guardiangenerators.com.
Table of Contents
Air-cooled Generators
Introduction ........................Inside Front Cover
Read This Manual Thoroughly ........................ IFC
Operation and Maintenance ............................ IFC
How to Obtain Service ..................................... IFC
Authorized Dealer Locator Number ................... IFC
Safety Rules ........................................................2
Section 1 – General Information ...................4
Interruption Breaker for Bedrooms .............. 4
Section 3 – Operation ....................................16
3.1 Using the AUTO/OFF/MANUAL Switch ........ 16
3.2 Automatic Transfer Operation ..................... 16
3.3 Sequence of Automatic Operation ............... 17
3.5 Setting the Exercise Timer .......................... 18
Section 4 – Maintenance .............................. 20
4.2 Checking the Engine Oil Level ..................... 20
4.3 Changing the Engine Oil .............................. 21
4.4 Changing the Engine Air Cleaner ................. 21
1.7 Fuel Requirements and Recommendations ... 7
1.9 Reconfiguring the Fuel System ...................... 8
1.10 Location ........................................................ 9
1.12 Battery Installation ...................................... 10
1.13 The Battery ................................................. 11
Section 2 – Post Installation Start-up and Adjustments .......................12
2.2 Check Transfer Switch Operation ............... 12
2.4 Generator Tests Under Load ....................... 13
7kW (Natural Gas Only) ............................... 14
2.8 Voltage Regulator Adjustment ...................... 15
Valve Clearance ............................................ 23
4.10 Corrosion Protection ................................... 25
4.11 Out of Service Procedure ............................. 25
4.12 Service Schedule ......................................... 26
Section 5 – Troubleshooting .........................27
Section 6 – Notes ........................................... 28
Section 7 – Electrical Data ........................... 29
Section 8 – Exploded Views and
Parts Lists ................................... 40
Section 9 – Mounting Dimensions ............. 66
Section 10 – Warranty ................................... 68
1
IMPORTANT SAFETY INSTRUCTIONS
Air-cooled Generators
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted near the unit’s installation site. Safety should be stressed to all operators and potential operators of this equipment.
•
• WARNING:
The engine exhaust from this product contains chemicals known to the state of California to cause cancer, birth defects or other reproductive harm.
• WARNING:
• This product contains or emits chemicals known to the state of California to cause cancer, birth defects or other reproductive harm.
Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The generator can operate safely, efficiently and reliably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive. If using a procedure, work method or operating technique the manufacturer does not specifically recommend, ensure that it is safe for others. Also make sure the procedure, work method or operating technique utilized does not render the generator unsafe.
DANGER
Despite the safe design of this generator, operating this equipment imprudently, neglecting its maintenance or being careless can cause possible injury or death. Permit only responsible and capable persons to operate or maintain this equipment.
Potentially lethal voltages are generated by these machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator.
Parts of the generator are rotating and/or hot during operation. Exercise care near running generators.
GENERAL HAZARDS
•
•
•
•
•
•
•
•
For safety reasons, the manufacturer recommends that the installation, initial start-up and maintenance of this equipment is carried out by an
Authorized Dealer.
The engine exhaust fumes contain carbon monoxide, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. This exhaust system must be installed properly, in strict compliance with applicable codes and standards.
Following installation, do nothing that might render the system unsafe or in noncompliance with such codes and standards.
Keep hands, feet, clothing, etc., away from drive belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
Adequate, unobstructed flow of cooling and ventilating air is critical to correct generator operation.
Do not alter the installation or permit even partial blockage of ventilation provisions, as this can seriously affect safe operation of the generator. The generator MUST be installed outdoors.
When working on this equipment, remain alert at all times. Never work on the equipment when physically or mentally fatigued.
Inspect the generator regularly, and contact the nearest Authorized Dealer for parts needing repair or replacement.
Before performing any maintenance on the generator, disconnect its battery cables to prevent accidental start up. Disconnect the cable from the battery post indicated by a NEGATIVE, NEG or
(–) first, then remove the POSITIVE, POS or (+) cable. When reconnecting the cables, connect the
POSITIVE cable first, the NEGATIVE cable last.
Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
2
IMPORTANT SAFETY INSTRUCTIONS
Air-cooled Generators
•
•
•
•
•
•
•
ELECTRICAL HAZARDS
All generators covered by this manual produce dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as does the standby generator when it is in operation. Avoid contact with bare wires, terminals, connections, etc., while the unit is running. Ensure all appropriate covers, guards and barriers are in place, secured and/or locked before operating the generator. If work must be done around an operating unit, stand on an insulated, dry surface to reduce shock hazard.
Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK
MAY RESULT.
The National Electrical Code (NEC) requires the frame and external electrically conductive parts of the generator to be connected to an approved earth ground. Local electrical codes also may require proper grounding of the generator electrical system.
After installing this home standby electrical system, the generator may crank and start at any time without warning. When this occurs, load circuits are transferred to the STANDBY (generator) power source. To prevent possible injury if such a start and transfer occur, always set the generator’s
AUTO/OFF/MANUAL switch to its OFF position before working on equipment and remove the 15A fuse from the generator control panel.
In case of accident caused by electric shock, immediately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH
THE VICTIM. Use a nonconducting implement, such as a dry rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.
Never wear jewelry when working on this equipment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving components causing injury.
FIRE HAZARDS
For fire safety, the generator must be installed and maintained properly. Installation must always comply with applicable codes, standards, laws and regulations.
Adhere strictly to local, state and national electrical and building codes. Comply with regulations the Occupational Safety and
Health Administration (OSHA) has established.
Also, ensure that the generator is installed in accordance with the manufacturer’s instructions and recommendations. Following proper installation, do nothing that might alter a safe installation and render the unit in noncompliance with the aforementioned codes, standards, laws and regulations.
• Keep a fire extinguisher near the generator at all times. Extinguishers rated “ABC” by the National
Fire Protection Association are appropriate for use on the standby electric system. Keep the extinguisher properly charged and be familiar with its use. Consult the local fire department with any questions pertaining to fire extinguishers.
EXPLOSION HAZARDS
•
•
Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no combustible materials are left in the generator compartment, or on or near the generator, as FIRE or
EXPLOSION may result. Keep the area surrounding the generator clean and free from debris.
Gaseous fluids such as natural gas and liquid propane (LP) gas are extremely EXPLOSIVE. Install the fuel supply system according to applicable fuel-gas codes. Before placing the home standby electric system into service, fuel system lines must be properly purged and leak tested according to applicable code. After installation, inspect the fuel system periodically for leaks. No leakage is permitted.
STANDARDS INDEX
In the absence of pertinent standards, codes, regulations and laws, the published information listed below may be used as installation guide for this equipment.
1. NFPA No. 37, STATIONARY COMBUSTION
ENGINES AND GAS TURBINES, available from the National Fire Protection Association, 470
Atlantic Avenue, Boston, MA 02210.
2. NFPA No. 76A, ESSENTIAL ELECTRICAL
SYSTEMS FOR HEALTH CARE FACILITIES, available same as Item 1.
3. NFPA No. 54, NATIONAL FUEL GAS CODE, available same as Item 1.
4. NFPA No. 58, AMERICAN NATIONAL STANDARD
FOR STORAGE AND HANDLING OF LIQUEFIED
PETROLEUM GAS, available same as Item 1.
5. NFPA No. 70, NFPA HANDBOOK OF NATIONAL
ELECTRIC CODE, available same as Item 1.
6. Article X, NATIONAL BUILDING CODE, available from the American Insurance Association, 85
John Street, New York, N.Y. 10038.
7. AGRICULTURAL WIRING HANDBOOK, available from the Food and Energy Council, 909
University Avenue, Columbia, MO 65201.
MAINTENANCE OF FARM STANDBY ELECTRICAL
SYSTEMS, available from the American Society of Agricultural Engineers, 2950 Niles Road, St.
Joseph, MI 49085.
9. NFPA No. 30, FLAMMABLE AND COMBUSTIBLE
LIQUIDS CODE, available same as Item 1.
3
Section 1 — General Information
Air-cooled Generators
DANGER
Only qualified electricians or contractors should attempt such installations, which must comply strictly with applicable codes, standards and regulations.
1.1 UNPACKING/INSPECTION
After unpacking, carefully inspect the contents for damage.
•
•
•
This standby generator set is ready for installation with a factory supplied and pre-mounted base pad and has a weather protective enclosure that is intended for outdoor installation only.
This UL listed standby generator set is packaged with an automatic transfer switch with built in load center. The combination transfer switch and load center is pre-wired with a two foot and 30 foot conduit. Circuit breakers for emergency circuit connections are included (if equipped).
This UL listed, 2-pole switch is rated at 100 AC amperes at 250 volts maximum. This transfer switch is for indoor use only (if equipped).
If this generator is used to power electrical load circuits normally powered by a utility power source, it is required by code to install a transfer switch. The transfer switch must effectively isolate the electrical system from the utility distribution system when the generator is operating (NEC 700,
701 & 702). Failure to isolate an electrical system by such means will result in damage to the generator and also may result in injury or death to utility power workers due to backfeed of electrical energy.
If any loss or damage is noted at time of delivery, have the person(s) making the delivery note all damage on the freight bill or affix their signature under the consignor's memo of loss or damage.
If a loss or damage is noted after delivery, separate the damaged materials and contact the carrier for claim procedures.
“Concealed damage” is understood to mean damage to the contents of a package that is not in evidence at the time of delivery, but is discovered later.
SYSTEMS
Unlike an automobile engine, the generator may have to run for long periods of time with no operator present to monitor engine conditions. For that reason, the engine is equipped with the following systems that protect it against potentially damaging conditions:
1. Low Oil Pressure Sensor 4. Overspeed
2. High Temperature Sensor 5. RPM Sensor
3. Overcrank 6. Low Battery
4
There are LED readouts on the control panel to notify personnel that one of these faults has occurred.
There is also a System Set LED that is lit when all of the conditions described in section "System Set
LED" are true. (See the "Protection Systems" section for details.)
NEC REQUIREMENT FOR ARC
FAULT CIRCUIT INTERRUPTION
BREAKER FOR BEDROOMS
In 2001, the National Electric Code (NEC) introduced a requirement for new construction. This new requirement indicates the need for Arc Fault Circuit
Interrupters to be used to protect the complete branch circuit that feeds a dwelling bedroom. The actual NEC requirement is indicated below.
INTERRUPTER PROTECTION
1. Definition: An arc fault circuit interrupter is a device intended to provide protection from the effects of arc faults by recognizing characteristics unique to arcing and by functioning to de-energize the circuit when an arc fault is detected.
2. Dwelling Unit Bedrooms: All branch circuits that supply 125 volt, single-phase, 15 and 20 ampere outlets installed in dwelling unit bedrooms shall be protected by an arc fault circuit interrupter listed to provide protection of the entire branch circuit.
Section 210.12 requires that AFCI protection be provided on branch circuits that supply outlets
(receptacle, lighting, etc.) in dwelling bedrooms. The requirement is limited to 15 and 20 ampere, 125 volt circuits. There is no prohibition against providing AFCI protection on other circuits or in locations other than bedrooms. Because circuits are often shared between a bedroom and other areas such as closets and hallways, providing AFCI protection on the complete circuit would comply with 210.12.
If during the installation of the home standby system the decision is made to provide back up power to a bedroom branch circuit, then the circuit breaker in the transfer switch should be replaced with an Arc
Fault Circuit Interrupter.
It is most important that breakers only be switched like for like. For instance, if replacing a 15A breaker, it MUST be replaced with a 15A AFCI breaker.
Likewise, a 20A breaker MUST be replaced with a
20A AFCI.
These AFCI breakers are available at the nearest hardware store.
Siemens Item #
Q115AF
Q120AF
Description
15A Single Pole AFCI
20A Single Pole AFCI
Section 1 — General Information
Air-cooled Generators
1.4 THE GENERATOR
Figure 1.1 – 7kW, Single Cylinder GH-410 Engine Figure 1.2 – 10kW, V-twin GT-530 Engine
Oil
Dipstick
Data
Decal
Air Filter
Cover
Control
Panel
Oil
Dipstick
Data
Decal
Control
Panel
Exhaust
Enclosure
Exhaust
Enclosure
Fuel
Inlet
(Back)
Fuel
Regulator
Composite Base Oil Filter Battery Compartment
Figure 1.3 – 13kW and 16kW, V-twin GT-990 Engine
Composite Base Oil Filter Battery Compartment
Air Filter
Fuel
Inlet
(Back)
Fuel
Regulator
Oil
Dipstick
Air Filter
Cover
Data
Decal
Control
Panel
Exhaust
Enclosure
Composite Base Oil Filter Battery Compartment
Fuel
Inlet
(Back)
Fuel
Regulator
5
Section 1 — General Information
Air-cooled Generators
1.5 SPECIFICATIONS
1.5.1 GENERATOR
Model
Rated Max. Continuous
Power Capacity (Watts*)
Rated Voltage
Rated Max. Continuous
Load Current (Amps)
120 Volts**
05240 & 05280
6,000 NG/7,000 LP
120/240
05241 & 05281
9,000 NG/10,000 LP 13,000 NG/13,000 LP 15,000 NG/16,000 LP
120/240
05242 & 05282
120/240
05243 & 05244
120/240
240 Volts
Main Line Circuit Breaker
Circuits***
50A, 240V
40A, 240V
30A, 240V
Phase
Number of Rotor Poles
Rated AC Frequency
50.0 NG/58.3 LP
25.0 NG/29.2 LP
30 Amp
-
-
1
2
60 Hz
75.0 NG/83.3 LP
37.5 NG/41.7 LP
45 Amp
-
-
1
2
60 Hz
108.3 NG/108.3 LP
54.1 NG/54.1 LP
55 Amp
-
1
1
125 NG/133.3 LP
62.5 NG/66.6 LP
65 Amp
- 1 - 1
1 3 3 5
5 3 5 5
1 1 1 1
2
60 Hz
1
1
-
2
60 Hz
Power Factor
Recommended Air Filter
Battery Requirement
Battery Warming Blanket
Weight (Unit Only)
Enclosure
1
Part # 0C8127
Group 26
12 Volts and
350 Cold-cranking
Amperes Minimum
336 Pounds
1
Part # 0E9581
Group 26
12 Volts and
525 Cold-cranking
Amperes Minimum
375 Pounds
0F6148DSRV
1
Part # 0C8127
Group 26
12 Volts and
525 Cold-cranking
Amperes Minimum
425.5 Pounds
1
Part # 0C8127
Group 26
12 Volts and
525 Cold-cranking
Amperes Minimum
445 & 414 Pounds
Steel/Aluminum
Normal Operating Range -20°F (-28.8°C) to 104°F (40°C)
* Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum power decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6° C (10° F) above 16° C (60° F) ambient temperature.
** Load current values shown for 120 volts are maximum TOTAL values for two separate circuits. The maximum current in each circuit must not exceed the value stated for 240 volts.
*** Circuits to be moved must be protected by same size breaker. For example, a 15 amp circuit in main panel must be a 15 amp circuit in transfer switch.
1.5.2 ENGINE
Model
Type of Engine
Number of Cylinders
Rated Horsepower
Displacement
Cylinder Block
Valve Arrangement
Ignition System
Recommended Spark Plug
Spark Plug Gap
Compression Ratio
Starter
Oil Capacity Including Filter
Recommended Oil Filter
Recommended Air Filter
Operating RPM
6
05240 & 05280 05241 & 05281 05242 & 05282 05243 & 05244
05283 & 05284
GH-410
1
14.5 @ 3,600 rpm
410cc
Aluminum w/Cast
Iron Sleeve
GT-530
2
18 @ 3,600 rpm
530cc
Aluminum w/Cast
Iron Sleeve
GT-990
2
30 @ 3,600 rpm
992cc
Aluminum w/Cast
Iron Sleeve
GT-990
2
30 @ 3,600 rpm
992cc
Aluminum w/Cast
Iron Sleeve
Overhead Valves Overhead Valves Overhead Valves Overhead Valves
Solid-state w/Magneto Solid-state w/Magneto Solid-state w/Magneto Solid-state w/Magneto
RC14YC BPR6HS RC14YC RC14YC
0.76 mm (0.030 inch) 0.76 mm (0.030 inch) 1.02 mm (0.040 inch) 1.02 mm (0.040 inch)
8.6:1
12 Vdc
9.5:1
12 Vdc
9.5:1
12 Vdc
9.5:1
12 Vdc
Approx. 1.5 Qts
Part # 070185F
Part # 0C8127
3,600
Approx. 1.7 Qts
Part # 070185F
Approx. 1.7 Qts
Part # 070185F
Part # 0E9581 Part # 0C8127
3,600 3,600
Approx. 1.7 Qts
Part # 070185F
Part # 0C8127
3,600
Section 1 — General Information
Air-cooled Generators
1.6 SYSTEM SET LED
The “System Set” LED is lit when all of the following conditions are true:
1. The AUTO/OFF/MANUAL switch is set to the
AUTO position.
2. The utility voltage being supplied to the unit is being sensed by the PCB. If the utility sense voltage is not connected to the unit or if it is below approximately 150-160 volts AC, then the system set light will flash rapidly. This indicates that if the AUTO/OFF/ MANUAL switch is placed in the
Auto position, the generator will start.
3. No alarms are present, for example, low oil pressure, high temperature, etc.
AND RECOMMENDATIONS
With LP gas, use only the vapor withdrawal system.
This type of system uses the vapors formed above the liquid fuel in the storage tank.
The engine has been fitted with a fuel carburetion system that meets the specifications of the 1997
California Air Resources Board for tamper-proof dual fuel systems. The unit will run on natural gas or LP gas, but it has been factory set to run on natural gas.
Should the primary fuel need to be changed to LP gas, the fuel system needs to be reconfigured. See the
Reconfiguring the Fuel System section for instructions on reconfiguration of the fuel system.
Recommended fuels should have a Btu content of at least 1,000 Btus per cubic foot for natural gas; or at least 2,520 Btus per cubic foot for LP gas. Ask the fuel supplier for the Btu content of the fuel.
Required fuel pressure for natural gas is 5 inches to 7 inches water column (0.18 to 0.25 psi); and for liquid propane, 10 inches to 12 inches of water column (0.36 to 0.43 psi).
NOTE:
All pipe sizing, construction and layout must comply with NFPA 54 for natural gas applications and
NFPA 58 for liquid propane applications. Once the generator is installed, verify that the fuel pressure
NEVER drops below four (4) inches water column for natural gas or 10 inches water column for liquid propane.
Prior to installation of the generator, the installer should consult local fuel suppliers or the fire marshall to check codes and regulations for proper installation. Local codes will mandate correct routing of gaseous fuel line piping around gardens, shrubs and other landscaping to prevent any damage.
Special considerations should be given when installing the unit where local conditions include flooding, tornados, hurricanes, earthquakes and unstable ground for the flexibility and strength of piping and their connections.
Use an approved pipe sealant or joint compound on all threaded fitting.
All installed gaseous fuel piping must be purged and leak tested prior to initial start-up in accordance with local codes, standards and regulations.
Unit Nat. Gas (*)
Full
LP Vapor (**)
1/2 Load Full Load
6/7 kW 66
9/10 kW 102
119
156
0.82/30
1.25/46
1.47/54
1.93/70
13/13 kW 156
15/16 kW 173
220
245
1.55/57
1.59/59
2.18/80
2.51/92
*Natural gas is in cubic feet per hour.
**LP is in gallons per hour/cubic feet per hour.
*** Values given are approximate.
NATURAL GAS
BTU flow required for each unit based on 1000 BTU per cubic foot.
•
•
•
•
6kW — 119,000 BTU/Hour
9kW — 156,000 BTU/Hour
13kW — 220,000 BTU/Hour
15kW — 245,000 BTU/Hour
DANGER
Gaseous fuels such as natural gas and liquid propane (LP) gas are highly explosive. Even the slightest spark can ignite such fuels and cause an explosion. No leakage of fuel is permitted.
Natural gas, which is lighter than air, tends to collect in high areas. LP gas is heavier than air and tends to settle in low areas.
NOTE:
A minimum of one approved manual shut-off valve must be installed in the gaseous fuel supply line.
The valve must be easily accessible. Local codes determine the proper location.
7
Section 1 — General Information
Air-cooled Generators
FUEL SYSTEM
1.9.1 7 KW, 410CC ENGINE
To reconfigure the fuel system from NG to LP, follow these steps (Figure 1.4):
NOTE:
The primary regulator for the propane supply is
NOT INCLUDED with the generator. A fuel pressure of 10 to 12 inches of water column (0.36 to
0.43 psi) to the fuel inlet of the generator MUST
BE SUPPLIED.
1. Turn off the main gas supply (if connected).
2. Open the roof and remove the door.
3. Remove the battery (if installed).
4. Disconnect wire #0 and wire #14 from the gas solenoid on top of the demand regulator.
5. Remove the carburetor fuel hose from the outlet port of the demand regulator.
6. Remove the demand regulator by removing the fastener that retains the regulator mounting bracket.
7. Remove the square headed steel pipe plug from outlet port #1 and the brass hose barb fitting from outlet port #2.
8. Refit the brass hose barb fitting to outlet port #1 and the square headed steel pipe plug to outlet port #2.
Figure 1.4 – Demand Regulator
HOSE & PLUG
SWITCHED SIDES
FUEL HOSE
BRASS HOSE
FITTING
ADJUSTMENT
SCREW
PIPE
PLUG
FUEL HOSE
BRASS HOSE
FITTING
OUTLET
PORT
FUEL JET
NOTE:
Use an approved pipe sealant or joint compound on all threaded fittings to reduce the possibility of leakage.
9. Reverse procedure steps 1-6 to reinstall demand regulator.
10. Take the plastic plug supplied in the poly-bag with the generator and press it into the 3/4” hole on the bottom of the air cleaner base (Figure
4.6).
11. Reverse the procedure to convert back to natural gas.
12. Check for gas leakage at the pipe plug, hose connection and fittings.
1.9.2 10, 13 AND 16KW, V-TWIN ENGINES
To reconfigure the fuel system from NG to LP, follow these steps:
NOTE:
The primary regulator for the propane supply is
NOT INCLUDED with the generator. A fuel pressure of 10 to 12 inches of water column (0.36 to
0.43 psi) to the fuel inlet of the generator MUST
BE SUPPLIED.
2. For 10kW units: Loosen clamp and slide back the air inlet hose.
• Slide fuel selector on carburetor out towards the back of the enclosure (Figures 1.5 and 1.6).
• Return the inlet hose and tighten clamp securely.
For 13 and 16kW units: remove the air cleaner cover.
• Slide the selector lever out towards the back of the enclosure (Figures 1.7 and 1.8).
• Return the air cleaner cover and tighten the two thumb screws.
4. Reverse the procedure to convert back to natural gas.
8
NG FUEL SYSTEM
RUNNING
PRESSURE
TAP
LP FUEL SYSTEM
STATIC
PRESSURE
TAP
Figure 1.5 - 10kW, GT-530 (Inlet Hose Slid Back)
Section 1 — General Information
Air-cooled Generators
Figure 1.8 - 13/16kW, GT-990 (Airbox Cover
Removed)
Fuel Selection Lever - "Out" Position for Liquid Propane
(Vapor) Fuel
Fuel Selection
Lever - "In"
Position for
Natural Gas
Fuel
Figure 1.6 - 10kW, GT-530 (Inlet Hose Slid Back)
Fuel Selection
Lever - "Out"
Position for
Liquid Propane
(Vapor) Fuel
Figure 1.7 - 13/16kW, GT-990 (Airbox Cover
Removed)
Fuel Selection Lever - "In" Position for Natural Gas Fuel
1.10 LOCATION
1.10.1 GENERATOR
Install the generator set, in its protective enclosure, outdoors , where adequate cooling and ventilating air is always available (Figure 1.9). Consider these factors:
•
•
•
•
•
•
•
The installation of the generator must comply strictly with NFPA 37, NFPA 54, NFPA 58, and
NFPA 70 standards.
Install the unit where air inlet and outlet openings will not become obstructed by leaves, grass, snow, etc.. If prevailing winds will cause blowing or drifting, consider using a windbreak to protect the unit.
Install the generator on high ground where water levels will not rise and endanger it.
Allow sufficient room on all sides of the generator for maintenance and servicing. This unit must be installed in accordance with current applicable
NFPA 37 and NFPA 70 standards; as well as any other federal, state and local codes for minimum distances from other structures. DO NOT install under wooden decks or structures.
Install the unit where rain gutter down spouts, roof fun-off, landscape irrigation, water sprinklers or sump pump discharge does not flood the unit or spray the enclosure, including any air inlet or outlet openings.
Install the unit where services will not be affected or obstructed, including concealed, underground or covered services such as electrical, fuel, phone, air conditioning or irrigation.
Where strong prevailing winds blow from one direction, face the generator air inlet openings to the prevailing winds.
9
Section 1 — General Information
Air-cooled Generators
•
•
•
•
Install the generator as close as possible to the fuel supply, to reduce the length of piping.
Install the generator as close as possible to the transfer switch. REMEMBER THAT LAWS OR
CODES MAY REGULATE THE DISTANCE AND
LOCATION.
The genset must be installed on a level surface.
The base frame must be level within two (2) inches all around.
The generator is typically placed on pea gravel or crushed stone. Check local codes if a concrete slab is required. If a concrete base slab is required, all federal, state and local codes should be followed.
Special attention should be given to the concrete base slab which should exceed the length and width of the generator by a minimum of six (6) inches (0.152 meters) on all sides.
Figure 1.9 – Generator Clearances
The engine exhaust fumes contain carbon monoxide, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. This exhaust system must be installed properly, in strict compliance with applicable codes and standards. Following installation, do nothing that might render the system unsafe or in noncompliance with such codes and standards.
• Operate the generator outdoors ONLY.
• Keep exhaust gases from entering a confined area through windows, doors, ventilation or other openings (Figure 1.9).
1.10.2 TRANSFER SWITCH
1.10.2.1 7, 10, 13, and 16 kW Units (if equipped)
The transfer switch shipped with this generator is enclosed in a NEMA 1 enclosure. This type of enclosure is intended for indoor use only . Follow these rules:
10
•
•
•
•
Install the transfer switch indoors on a firm, sturdy supporting structure.
To prevent switch distortion, level the switch if necessary. This can be done by placing washers between the switch enclosure and mounting surface.
Never install the switch where water or any corrosive substance might drip onto the enclosure.
Protect the switch at all times against excessive moisture, dust, dirt, lint, construction grit and corrosive vapors.
If the AUTO/OFF/MANUAL switch is not set to its
OFF position, the generator can crank and start as soon as the battery cables are connected. If the utility power supply is not turned off, sparking can occur at the battery posts and cause an explosion.
1.11 BATTERY REQUIREMENTS
See the Specifications section for correct battery size and rating.
1.12 BATTERY INSTALLATION
Fill the battery with the proper electrolyte fluid if necessary and have the battery fully charged before installing it.
Before installing and connecting the battery, complete the following steps:
1. Set the generator's AUTO/OFF/MANUAL switch to
OFF.
2. Turn off utility power supply to the transfer switch.
3. Remove the 15A fuse from the generator control panel.
Battery cables were factory connected at the generator (Figure 1.10). Connect cables to battery posts as follows:
4. Connect the red battery cable (from starter contactor) to the battery post indicated by a positive,
POS or (+).
5. Connect the black battery cable (from frame ground) to the battery post indicated by a negative, NEG or (—).
NOTE:
Dielectric grease should be used on battery posts to aid in the prevention of corrosion.
NOTE:
Damage will result if battery connections are made in reverse.
Section 1 — General Information
Air-cooled Generators
Figure 1.10 – Battery Cable Connections
NOTE:
In areas where temperatures regularly fall below
10° F (-12° C) it is recommended that a pad type battery heater be installed to aid in cold climate starting (see Specifications).
NOTE:
The generator is equipped with a battery trickle charger that is active when the unit is set up for automatic operation. With the battery installed and utility power source voltage available to the transfer switch, the battery receives a trickle charge while the engine is not running, to prevent self-discharge. The trickle charger is designed to help extend the life of the battery by maintaining the battery when the unit is not running. The trickle charge feature cannot be used to recharge a discharged battery.
1.13 THE BATTERY
DANGER
Do not dispose of the battery in a fire. The battery is capable of exploding.
A battery presents a risk of electrical shock and high short circuit current. The following precautions are to be observed when working on batteries:
• Remove the 15A fuse from the generator control panel.
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the battery; and
• Disconnect charging source prior to connecting or disconnecting battery terminals.
Do not open or mutilate the battery. Released electrolyte has been known to be harmful to the skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive.
The following procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off immediately with water;
• Where electrolyte contacts the eyes, flush thoroughly and immediately with water and seek medical attention; and
• Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of 1 pound (500 grams) bicarbonate of soda to 1 gallon (4 liters) of water. The bicarbonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.
Lead-acid batteries present a risk of fire because they generate hydrogen gas. The following procedures are to be followed:
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from body before touching the battery by first touching a grounded metal surface.
Be sure the AUTO/OFF/MANUAL switch is set to the OFF position before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.
Be sure the utility power supply is turned off and the 15A fuse is removed from the generator control panel, or sparking may occur at the battery posts as the cables are attached and cause an explosion.
Servicing of the battery is to be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
See the Specifications section for the correct size and rating when replacing the battery. When using a maintenance-free battery, it is not necessary to check the specific gravity or electrolyte level. Have these procedures performed at the intervals specified in the “Service Schedule.” A negative ground system is used. Battery connections are shown on the wiring diagrams. Make sure the battery is correctly connected and terminals are tight. Observe battery polarity when connecting the battery to the generator set.
11
Section 2 — Post Installation Start-up and Adjustments
Air-cooled Generators
INITIAL
NOTE:
START-UP
These units have been run and tested at the factory prior to being shipped and do not require any type of break-in.
Before starting, complete the following:
1. Set the generator’s main circuit breaker to its
OFF (or OPEN) position.
2. Set the generator's AUTO/OFF/MANUAL switch to the OFF position.
3. Turn OFF all breakers on the load center of the transfer box (T1 and T2).
4. Turn OFF all loads connected to the transfer switch terminals T1 and T2.
5. Check the engine crankcase oil level and, if necessary, fill to the dipstick FULL mark with the recommended oil. Do not fill above the FULL mark.
6. Check the fuel supply. Gaseous fuel lines must have been properly purged and leak tested in accordance with applicable fuel-gas codes. All fuel shutoff valves in the fuel supply lines must be open.
During initial start up, after installation, it is normal for the generator to exceed the normal number of start attempts and experience an “over crank” fault.
This is due to accumulated air in the fuel system during shipment.
To reduce or eliminate this problem on initial start up, remove the air filter cover and partially cover the fuel mixer inlet while the engine is cranking (Figures
2.1 and 2.2). This will cause an abnormal vacuum in the system and purge the air from the system.
Once fuel reaches the engine, it will begin to run.
Remove the blockage from the mixer inlet as soon as the engine begins to fire. The unit should then be run several minutes to insure that all air is removed from the fuel system. Once the engine is running, this procedure is not required as long as the fuel supply to the generator is not interrupted. This procedure will only be required if the generator becomes disconnected from the fuel system for whatever reason.
NOTE:
This procedure applies to 13kW and 16kW units only and should be performed by trained personnel.
Never operate the engine with the oil level below the “Add” mark on the dipstick. Doing this could damage the engine.
Figure 2.1 – Remove Air Filter Cover
Figure 2.2 – Restrict Air Flow During
Inital Start Up
OPERATION
Refer to the "Manual Transfer Operation" section, of the owner’s manual for procedures.
DANGER
Do not attempt manual transfer switch operation until all power voltage supplies to the transfer switch have been positively turned off.
Failure to turn off all power voltage supplies will result in extremely hazardous and possibly fatal electrical shock.
12
Section 2 — Post Installation Start-up and Adjustments
Air-cooled Generators
CHECKS
Complete electrical checks as follows:
1. Set the generator's main circuit breaker to its
OFF (or OPEN) position.
2. Set the generator's AUTO/OFF/MANUAL switch to the OFF position.
3. Turn OFF all breakers on the load center of the transfer box (T1 and T2).
4. Turn on the utility power supply to the transfer switch using the means provided (such as a utility main line circuit breaker).
DANGER
The transfer switch is now electrically “hot.”
Contact with “hot” parts will result in extremely hazardous and possibly fatal electrical shock.
Proceed with caution.
5. Use an accurate AC voltmeter to check utility power source voltage across transfer switch terminals N1 and N2. Nominal line-to-line voltage should be 240 volts AC.
6. Check utility power source voltage across terminals N1 and the transfer switch neutral lug; then across terminal N2 and neutral. Nominal line-toneutral voltage should be 120 volts AC.
7. When certain that utility supply voltage is compatible with transfer switch and load circuit ratings, turn OFF the utility power supply to the transfer switch.
8. On the generator panel, set the AUTO/OFF/
MANUAL switch to MANUAL. The engine should crank and start.
9. Let the engine warm up for about five minutes to allow internal temperatures to stabilize. Then, set the generator’s main circuit breaker to its ON (or
CLOSED) position.
DANGER
Proceed with caution! Generator power voltage is now supplied to the transfer switch. Contact with live transfer switch parts will result in dangerous and possibly fatal electrical shock.
10. Connect an accurate AC voltmeter and a frequency meter across transfer switch terminal lugs E1 and E2. 7kW voltage should be 242-252 volts at a frequency of 61-63 Hertz. 10, 13, and 16kW voltage should be 247-249 volts at a frequency of
57.5-59.5 Hertz.
11. Connect the AC voltmeter test leads across terminal lugs E1 and neutral; then across E2 and neutral. In both cases, voltage reading should be
121-126 volts AC (7kW), and 125-126 volts AC
(10, 13 and 16kW).
12. Set the generator’s main circuit breaker to its
OFF (or OPEN) position. Let the engine run at noload for a few minutes to stabilize internal engine generator temperatures.
13. Set the generator's AUTO/OFF/MANUAL switch to
OFF. The engine should shut down.
NOTE:
It is important not to proceed until certain that generator AC voltage and frequency are correct and within the stated limits. Generally, if both AC frequency and voltage are high or low, the engine governor requires adjustment* (*GH410 only). If frequency is correct, but voltage is high or low, the generator’s voltage regulator requires adjustment.
2.4 GENERATOR TESTS UNDER LOAD
To test the generator set with electrical loads applied, proceed as follows:
1. Set generator’s main circuit breaker to its OFF
(or OPEN) position.
2. Turn OFF all breakers on the load center of the transfer box (T1 and T2).
3. Set the generator's AUTO/OFF/MANUAL switch to
OFF.
4. Turn OFF the utility power supply to the transfer switch, using the means provided (such as a utility main line circuit breaker).
Do not attempt manual transfer switch operation until all power voltage supplies to the transfer switch have been positively turned off.
Failure to turn off all power voltage supplies will result in extremely hazardous and possibly fatal electrical shock.
5. Manually set the transfer switch to the STANDBY position, i.e., load terminals connected to the generator's E1/E2 terminals. The transfer switch operating lever should be down.
6. Set the generator's AUTO/OFF/MANUAL switch to MANUAL. The engine should crank and start immediately.
7. Let the engine stabilize and warm up for a few minutes.
8. Set the generator’s main circuit breaker to its ON
(or closed) position. Loads are now powered by the standby generator.
9. Turn ON the load center of the transfer switch
(T1 and T2).
10. Connect an accurate AC voltmeter and a frequency meter across terminal lugs E1 and E2.
• 7kW voltage should be greater than 230 volts and frequency should be greater than 58 Hz.
13
Section 2 — Post Installation Start-up and Adjustments
Air-cooled Generators
• 10, 13 & 16kW voltage should be greater than
240 volts and frequency should be greater than
60 Hz.
11. Let the generator run at full rated load for 20-30 minutes. Listen for unusual noises, vibration or other indications of abnormal operation. Check for oil leaks, evidence of overheating, etc.
12. When testing under load is complete, turn OFF electrical loads.
13. Set the generator's main circuit breaker to its
OFF (or OPEN) position.
14. Let the engine run at no-load for a few minutes.
15. Set the AUTO/OFF/MANUAL switch to OFF. The engine should shut down.
OPERATION
To check the system for proper automatic operation, proceed as follows:
1. Set generator’s main circuit breaker to its OFF
(or OPEN) position.
2. Check that the AUTO/OFF/MANUAL switch is set to OFF.
3. Turn OFF the utility power supply to the transfer switch, using means provided (such as a utility main line circuit breaker).
4. Manually set the transfer switch to the UTILITY position, i.e., load terminals connected to the utility power source side.
5. Turn ON the utility power supply to the transfer switch, using the means provided (such as a utility main line circuit breaker).
6. Set the generator's main circuit breaker to its ON
(or CLOSED)) position.
7. Set the AUTO/OFF/MANUAL switch to AUTO. The system is now ready for automatic operation.
8. Turn OFF the utility power supply to the transfer switch.
With the AUTO/OFF/MANUAL switch at AUTO, the engine should crank and start when the utility source power is turned OFF after a 10 second delay. After starting, the transfer switch should connect load circuits to the standby side after a 15 second delay. Let the system go through its entire automatic sequence of operation.
With the generator running and loads powered by generator AC output, turn ON the utility power supply to the transfer switch. The following should occur:
•
•
After about 15 seconds, the switch should transfer loads back to the utility power source.
About one minute after retransfer, the engine should shut down.
- 7KW (NATURAL GAS ONLY)
NOTE:
All V-twin engine units DO NOT require a fuel regulator adjustment due to the fuel system design.
Although the generator has been factory set to provide maximum power, it may be necessary in some areas to adjust this setting. If experiencing engine problems at high or full load conditions, follow these steps. It will require a frequency meter to perform this procedure.
1. Turn off utility power to the main distribution panel in the house. This can be done by switching the service main breaker to the off or open position.
2. Allow the generator to start. Before loading the generator, confirm that the No Load Frequency, with the roof open and door off, is set to 63-63.5
Hz. Transfer load to emergency circuits.
3. Turn on appliances, lights, pumps, etc., that are on the emergency circuits in an attempt to fully load the generator. Be cautious not to overload the generator. Use the following chart as a guide:
Unit
7 kW 50.0 amps 25.0 amps
4. When 3/4 load has been achieved. Connect a frequency meter to the output lugs of the generator’s main line circuit breaker.
5. The fuel regulator is fitted with one adjustment screw. While watching the frequency meter, slowly turn the adjustment screw clockwise or counterclockwise until the highest frequency is read on the meter. Only limited adjustment is available because of the set pin. Under no circumstances should any of the pins be removed (Figure 2.3).
Figure 2.3 — 7kW Fuel Regulator
ngine 410cc Engine
Adjustment
Screw
(One Side
Only)
Set
Pin
14
Section 2 — Post Installation Start-up and Adjustments
Air-cooled Generators
6. When the highest frequency is reached maximum power has been set. From this point turn the adjustment screw 1/4 turn counterclockwise. The regulator is now set.
7. Turn utility power to the main distribution panel back on. This can be done by switching the service main breaker to the on or closed position.
Allow the generator to shut down.
Do not make any unnecessary adjustments.
Factory settings are correct for most applications. However, when making adjustments, be careful to avoid overspeeding the engine.
If this procedure or the test equipment is not available, locate the nearest Dealer and they can perform the adjustments.
NOTE:
A service fee may be charged for this adjustment.
2.7 ENGINE GOVERNOR ADJUSTMENT
If both AC frequency and voltage are correspondingly high or low, adjust the engine governor as follows:
2.7.1 7 KW UNITS
The engine must be OFF to perform steps 1 and
2.
1. Loosen the governor clamp bolt (Figure 2.4).
Figure 2.4 — Engine Governor Adjustment
Single Cylinder Engines
SECONDARY
ADJUST SCREW
GOVERNOR
SHAFT
GOVERNOR
CLAMP
BOLT
PRIMARY
ADJUST
SCREW
2. Hold the governor lever at its wide open throttle position (clockwise), and rotate the governor shaft clockwise as far as it will go. Then, tighten the governor lever clamp bolt to 70 inch-pounds
(8 N-m).
3. Start the generator; let it stabilize and warm up at no-load.
4. Connect a frequency meter across the generators
AC output leads.
5. Turn the primary adjust screw to obtain a frequency reading of 61.5 Hertz. Turn the secondary adjust screw to obtain a frequency of 62.5 Hz.
6. When frequency is correct at no load, check the
AC voltage reading. If voltage is incorrect, the voltage regulator may require adjustment (See the
Voltage Regulator Adjustment section).
2.7.2 13 KW AND 16 KW UNITS
NOTE:
All V-twin units DO NOT require an engine governor adjustment due to their design.
PROTECTION
Periodically spray all engine linkage parts and brackets with corrosion inhibiting spray such as WD-40 or a comparable product.
ADJUSTMENT
With the frequency between 62-63 Hertz at no-load, slowly turn the slotted potentiometer (Figure 2.5) until line voltage reads 248-252 volts.
2.8.2 10, 13, AND 16KW UNITS
With the frequency between 58-59 Hertz at no-load, slowly turn the slotted potentiometer (Figure 2.3) until line voltage reads 247-249 volts.
NOTE:
The access panel on top of the control panel must be removed to adjust the voltage regulator.
NOTE:
The voltage regulator is housed above the generator's control panel. The regulator maintains a voltage in direct proportion to frequency at a 2-to-
1 ratio. For example, at 62 Hertz, line-to-neutral voltage will be 124 volts.
15
Section 3 — Operation
Air-cooled Generators
Figure 2.5 – Voltage Adjustment Potentiometer
Turn to adjust voltage.
Set the switch to MANUAL to crank and start the engine. Transfer to standby power will not occur unless there is a utility failure.
With the switch set to AUTO, the engine may crank and start at any time without warning.
Such automatic starting normally occurs when utility power source voltage drops below a preset level or during the normal exercise cycle. To prevent possible injury that might be caused by such sudden starts, always set the switch to
OFF and remove the fuses before working on or around the generator or transfer switch. Then, place a “DO NOT OPERATE” tag on the generator panel and on the transfer switch.
1. 990 engines have an electric choke in the air box that is automatically controlled by the electronic control board.
2. 530 engines have an electric choke on the divider panel air inlet hose that is automatically controlled by the electronic control board.
3. 410 engines do not have a choke.
SWITCH (FIGURE 3.1)
Selecting this switch position activates fully automatic system operation. It also allows the unit to automatically start and exercise the engine every seven days with the setting of the exercise timer (see the Setting the Exercise Timer section).
This switch position shuts down the engine. This position also prevents automatic operation.
Figure 3.1 – Generator Control Panel
AUTO.
SYSTEM FUSE
OFF MAN.
15A
ASSY: 0F8418/0F8419
SET
EXERCISE
TIME
CONTROL AND INFORMATION CENTER
SYSTEM SET
LOW BATTERY
LOW OIL
HIGH TEMP
OVER SPEED
NO RPM SENSE IF FLASHING
OVER CRANK
FLASHING GREEN LED=
NO UTILITY SENSE
5 FLASHING RED LEDS=
EXERCISER NOT SET
OPERATION
To select automatic operation, do the following:
1. Make sure the transfer switch main contacts are set to their UTILITY position, i.e., loads connected to the utility power source (Figure 3.2).
2. Be sure that normal UTILITY power source voltage is available to transfer switch terminal lugs
N1 and N2 (Refer to the Electrical Data section).
3. Set the generator’s AUTO/OFF/MANUAL switch to
AUTO.
4. Set the generator’s main circuit breaker to its ON
(or CLOSED) position.
With the preceding steps complete, the generator will start automatically when utility source voltage drops below a preset level. After the unit starts, loads are transferred to the standby power source. Refer to the
Sequence of Automatic Operation section.
16
Section 3 — Operation
Air-cooled Generators
OPERATION
The generator’s control panel houses a control logic circuit board. This board constantly monitors utility power source voltage. Should that voltage drop below a preset level, circuit board action will signal the engine to crank and start. After the engine starts, the circuit board signals the transfer switch to activate and connect load circuits to the standby power supply (load terminal lugs T1/T2 connect to terminal lugs E1/E2). Refer to the Electrical Data section.
The generator must run at 50 Hz or greater for the transfer output to be activated. Once activated, it will remain active even if the frequency dips below 50
Hz.
Upon restoration of utility source voltage above a preset level, generator circuit board action signals the transfer switch to transfer loads back to that power supply. After retransfer, the engine is signalled to shut down.
The actual sequence of operation is controlled by sensors and timers on a control logic circuit board, as follows:
A. Utility Voltage Dropout Sensor
• This sensor monitors utility source voltage.
• If utility source voltage drops below about 65 percent of the nominal supply voltage, the sensor energizes a 10 second timer.
• Once the timer has expired, the engine will crank and start if utility is still low.
B. Engine Warm-up Time Delay
• This mechanism lets the engine warm up for about five (5) seconds before the load is transferred to the standby source.
C. Standby Voltage Sensor
• This sensor monitors generator AC output voltage. When the voltage has reached 50 percent of the nominal rated voltage, transfer to standby can occur.
D. Utility Voltage Pickup Sensor
• This sensor monitors utility power supply voltage. When that voltage is restored above 75 percent of the nominal source voltage, a retransfer time delay starts timing.
E. Retransfer Time Delay
• This timer runs for about 15 seconds.
• At end of a 15-second delay, circuit board action de-energizes transfer relay in the transfer switch if utility is still present.
• Retransfer to utility power source then occurs.
F. Engine Cool-down Timer
• When the load is transferred back to utility power source, the engine cool-down timer starts timing.
• The timer will run for about one minute, and the generator will then shut down.
POWER SOURCE
To start the generator and activate the transfer switch manually, proceed as follows:
1. Set the generator’s AUTO/OFF/MANUAL switch to
OFF.
2. Set the generator’s main circuit breaker to its
OFF (or OPEN) position.
3. Turn OFF the utility power supply to the transfer switch using the means provided (such as a utility main line circuit breaker).
DANGER
Do not attempt to activate the transfer switch manually until all power voltage supplies to the switch have been positively turned off. Failure to turn off all power voltage supplies may result in extremely hazardous and possibly fatal electrical shock.
4. Use the manual transfer handle inside the transfer switch to move the main contacts to their
STANDBY position, i.e., loads connected to the standby power source (Figure 3.2).
5. To crank and start the engine, set the AUTO/OFF/
MANUAL switch to MANUAL.
6. Let the engine stabilize and warm up for a few minutes.
7. Set the generator’s main circuit breaker to its ON
(or CLOSED) position. The standby power source now powers the loads.
Figure 3.2 – Manual Transfer Switch Operation
17
Section 3 — Operation
Air-cooled Generators
SOURCE
When utility power has been restored, transfer back to that source and shut down the generator. This can be accomplished as follows:
1. Set the generator’s main circuit breaker to its
OFF (or OPEN) position.
2. Let the engine run for a minute or two at no-load to stabilize the internal temperatures.
3. Set the generator’s AUTO/OFF/MANUAL switch to its OFF (or OPEN) position. The engine should shut down.
4. Check that utility power supply to the transfer switch is turned OFF.
DANGER
Do not attempt to activate the transfer switch manually until all power voltage supplies to the switch have been positively turned off.
Failure to turn off all power voltage supplies may result in extremely hazardous and possibly fatal electrical shock.
5. Use the manual transfer handle inside the transfer switch to move the main contacts back to their
UTILITY position, i.e., loads connected to the utility power source (Figure 3.2).
6. Turn ON the utility power supply to the transfer switch using the means provided.
7. Set the system to automatic operation as outlined in Automatic Transfer Operation section.
3.5 SETTING THE EXERCISE TIMER
This generator is equipped with an exercise timer.
Once it is set, the generator will start and exercise once every seven days, on the day of the week and at the time of day the following sequence is completed.
During this exercise period, the unit runs for approximately 12 minutes and then shuts down. Transfer of loads to the generator output does not occur during the exercise cycle unless utility power is lost.
A switch on the control panel (see Figure 3.1) permits selection of the day and time for the system to exercise. At the chosen time, perform the following sequence to select the desired day and time of day the system will exercise. Remember seasonal time changes affect the exercise time settings.
1. Verify that the AUTO/OFF/MANUAL switch is set to AUTO.
2. Press and hold the "Set Exercise Time" switch for several seconds, then release. All the red LED's will flash for approximately 10 seconds and then stop.
18
3. Once the red LED's stop flashing, the generator will start and run for approximately 12 minutes and then shut down. The exerciser is now set to run at this time of day each week.
Example: If the "Set Exercise Time" switch is pressed on Saturday afternoon at 2:00 p.m., the generator will start and exercise for approximately 12 minutes every Saturday at 2:00 p.m..
NOTE:
The exerciser will only work in the AUTO mode and will not work unless this procedure is performed. The exerciser will need to be reset every time the 12-volt battery is disconnected and then reconnected, and when the 15A fuse is removed.
The 16kW unit has a low speed exercise option. Dip switch 1 on the control board is factory set to OFF.
This allows the engine to run at a slower speed during weekly exercise periods for quieter operation. If this Dip switch is set to ON, the generator will exercise at it's normal speed.
This DIP switch position is only read at board power up. If the DIP switch position is changed, power to the board must be cycled for the micro controller to recognize the new DIP switch position.
Low speed exercise will be handled as follows:
1. The standard start sequence will be initiated.
2. The unit will run at 2,400 RPM.
3. If utility is lost during exercise, the controller will do the following:
• Wait 10 seconds for utility to return.
• If utility returns within 10 seconds, continue to exercise at 2,400 RPM.
• If utility is still lost after 10 seconds, run the engine up to 3600 RPM and transfer the load.
At this time the controller will exit the exercise routine and assume full automatic operation.
3.6.1 LOW OIL PRESSURE SWITCH
This switch (Figure 3.3) has normally closed contacts that are held open by engine oil pressure during cranking and operating. Should oil pressure drop below the 8 psi range, switch contacts close, and the engine shuts down. The unit should not be restarted until oil is added. The AUTO/OFF/MANUAL switch must then be turned to OFF and then back to
AUTO.
Section 3 — Operation
Air-cooled Generators
3.6.2 HIGH TEMPERATURE SWITCH
This switch’s contacts (Figure 3.3) close if the temperature should exceed approximately 144º C (293º
F), initiating an engine shutdown. The generator will automatically restart and the LED on the generator control panel will reset once the temperature has returned to a safe operating level.
Figure 3.3 – Low Oil Pressure and
High Temperature Switches
Low Oil Switch High Temp Switch
Loose n
Oil Filter
Oil
Drain
Hose
3.6.3 OVERCRANK
This feature prevents the generator from damaging itself when it continually attempts to start and another problem, such as no fuel supply, prevents it from starting. The unit will crank and rest for a preset time limit. Then, it will stop cranking, and the LED on the generator control panel will light indicating an overcrank failure. The AUTO/OFF/MANUAL switch will need to be set to OFF and then back to AUTO to reset the generator control board.
NOTE:
If the fault is not repaired, the overcrank feature will continue to activate.
3.7.3.1 Approximate Crank Cycle Times
7kW Units:
•
•
•
•
•
15 seconds ON
7 seconds OFF
7 seconds ON
7 seconds OFF
7 seconds ON
•
•
•
•
7 seconds OFF
7 seconds ON
7 seconds OFF
7 seconds ON
•
•
7 seconds OFF
7 seconds ON
If the unit fails to start, the overcrank alarm LED will be illuminated.
10kW, 13kW and 16kW Units:
•
•
•
•
•
•
•
16 seconds ON
7 seconds OFF
16 seconds ON
7 seconds OFF
7 seconds ON
7 seconds OFF
7 seconds ON
•
•
7 seconds OFF
7 seconds ON
• 7 seconds OFF
If the unit fails to start, the overcrank alarm LED will be illuminated.
3.6.4 OVERSPEED
This feature protects the generator from damage by shutting it down if it happens to run faster than the preset limit. This protection also prevents the generator from supplying an output that could potentially damage appliances connected to the generator circuit. Contact the nearest Authorized Dealer if this failure occurs.
3.6.5 RPM SENSOR FAILURE
During cranking, if the board does not see a valid
RPM signal within three (3) seconds, it will shut down and latch out on RPM sensor loss.
During running, if the RPM signal is lost for one full second the board will shut down the engine, wait 15 seconds, then re-crank the engine.
•
•
If an RPM signal is not detected within the first three (3) seconds of cranking, the control board will shut the engine down and latch out on RPM sensor loss.
If the RPM signal is detected the engine will start and run normally. If the RPM signal is subsequently lost again, the control board will try one more re-crank attempt before latching out and flashing the overspeed LED.
The microprocessor will continually monitor the battery voltage and turn on the Low Battery LED if the battery voltage falls below 11.0 volts for one (1) minute. No other action is taken on a low battery condition. Low battery voltage is a non-latching alarm which will automatically clear if the battery voltage rises above 11.0 volts. Battery voltage is NOT monitored during the crank cycle.
19
Section 4 — Maintenance
Air-cooled Generators
4.1 FUSES
The 15-amp fuse on the generator panel protects the
DC control circuit against overload (Figure 4.1). This fuse is wired in series with the battery output lead to the panel. If this fuse element has melted open, the engine will not be able to crank or start. Replace this fuse using only an identical 15-amp replacement fuse. To replace the fuse, push the fuse holder cap down and rotate it counterclockwise. Whenever the fuse is removed or replaced, the exercise timer needs to be reset.
Figure 4.1 – Generator Control Panel
AUTO.
SYSTEM FUSE
OFF MAN.
15A
ASSY: 0F8418/0F8419
SET
EXERCISE
TIME
CONTROL AND INFORMATION CENTER
SYSTEM SET
LOW BATTERY
LOW OIL
HIGH TEMP
OVER SPEED
NO RPM SENSE IF FLASHING
OVER CRANK
FLASHING GREEN LED=
NO UTILITY SENSE
5 FLASHING RED LEDS=
EXERCISER NOT SET
OIL LEVEL
For oil capacities, see the Specifications section.
For engine oil recommendations, see the Engine Oil
Recommendations section. To check the engine oil level, proceed as follows (Figures 4.2, 4.3 and 4.4):
1. Move the AUTO/OFF/ MANUAL switch to the OFF position.
2. Remove the dipstick and wipe it dry with a clean cloth.
3. Completely insert the dipstick; then, remove it again. The oil level should be at the dipstick “Full” mark. If necessary, add oil to the “Full” mark only. DO NOT FILL ABOVE THE “FULL” MARK.
Never operate the engine with the oil level below the “Add” mark on the dipstick. Doing this could damage the engine.
5. Reset the AUTO/OFF/MANUAL switch to its original position.
Figure 4.2 — Oil Dipstick and Fill, 7kW
Oil Dipstick and Fill
Figure 4.3 — Oil Dipstick and Fill, 10kW
Oil Dipstick
Oil Fill
Figure 4.4 — Oil Dipstick and Fill,
13kW and 16kW
Oil Dipstick
Oil Fill
20
Section 4 — Maintenance
Air-cooled Generators
4.3 CHANGING THE ENGINE OIL
4.3.1 OIL CHANGE INTERVALS
See the "Service Schedule" section.
4.3.2 ENGINE OIL RECOMMENDATIONS
All oil should meet minimum American Petroleum
Institute (API) Service Class SJ, SL or better. Use no special additives. Select the oil's viscosity grade according to the expected operating temperature.
Any attempt to crank or start the engine before it has been properly serviced with the recommended oil may result in an engine failure.
Figure 4.5 – Oil Drain Hose and Filter
Low Oil Switch High Temp Switch
Loose n
Oil Filter
Oil
Drain
Hose
4. Refill with the proper recommended oil (see the
Engine Oil Recommendations section). See the
Specifications section for oil capacities.
5. Start the engine, run for one (1) minute, and check for leaks.
6. Shutdown and recheck oil level, add as needed.
DO NOT OVER FILL.
7. Reset the AUTO/OFF/MANUAL switch to the
AUTO position.
4.3.3 OIL & OIL FILTER CHANGE PROCEDURE
To change the oil, proceed as follows:
1. Start the engine by moving the AUTO/OFF/
MANUAL switch to MANUAL and run until it is thoroughly warmed up. Then shut OFF the engine by moving the switch to the OFF position.
2. Immediately after the engine shuts OFF, pull the oil drain hose (Figure 4.5) free of its retaining clip. Remove the cap from the hose and drain the oil into a suitable container.
3. After the oil has drained, replace the cap onto the end of the oil drain hose. Retain the hose in the clip.
Change the engine oil filter as follows:
1. With the oil drained, remove the old oil filter by turning it counterclockwise.
2. Apply a light coating of clean engine oil to the gasket of the new filter. See the Specifications section for recommended filter.
3. Screw the new filter on by hand until its gasket lightly contacts the oil filter adapter. Then, tighten the filter an additional 3/4 to one turn (Figure
4.4).
AIR CLEANER
4.4.1 7, 13, AND 16KW GENERATORS
See Figures 1.1 and 1.2, for the location of the air cleaner. Use the following procedures (Figure 4.6,
7kW; Figure 4.8, 13/16kW):
1. Lift the roof and remove the door.
2. Turn the two screws counterclockwise to loosen.
3. Remove the cover and air filter.
4. Wipe away dust or debris from inside of the air box and around edges.
5. Install the new air cleaner into the air box.
6. Install the cover. Turn the two cover screws clockwise to tighten.
See the Service Schedule section for air cleaner maintenance. See the Specifications section for air filter replacement part number.
21
Section 4 — Maintenance
Air-cooled Generators
Figure 4.6 — 7 kW, Engine Air Cleaner Location Figure 4.8 — 13 kW and 16 kW Engine
Air Cleaner
Screw
Air
Cleaner
Cover
Filter
3/4”
Hole
See Figure 1.2 for the location of the air cleaner. Use the following procedure (Figure 4.7):
1. Lift the roof and remove the door.
2. Turn the worm gear clamp screw counterclockwise to loosen.
3. Pull the old filter off the divider panel hub.
4. Wipe away dust or debris from the panel hub.
5. Install the new air cleaner onto the hub.
6. Turn the worm gear clamp screw clockwise to tighten.
7. Replace door and roof.
Figure 4.7 — 10kW Engine Air Cleaner
Control
Panel
Air Filter
PLUG(S)
Reset the spark plug(s) gap or replace the spark plug(s) as necessary. See the Service Schedule section for maintenance requirements.
1. Clean the area around the base of the spark plug(s) to keep dirt and debris out of the engine.
2. Remove the spark plug(s) and check the condition. Replace the spark plug(s) if worn or if reuse is questionable. See the Service Schedule section for recommended inspection. Clean by scraping or washing using a wire brush and commercial solvent. Do not blast the spark plug(s) to clean.
3. Check the spark plug gap using a wire feeler gauge. Adjust the gap to 0.76 mm (0.030 inch) for
7 and 10kW; and 1.02 mm (0.040 inch) for 13/16 kW by carefully bending the ground electrode
(Figure 4.9).
Figure 4.9 – Setting the Spark Plug Gap
SET PLUG GAP AT 0.76 mm (.030 inch) - 7 & 10kW;
1.02 mm (.040 inch) - 13 & 16kW
22
Section 4 — Maintenance
Air-cooled Generators
MAINTENANCE
The battery should be inspected per the "Service
Schedule" section. The following procedure should be followed for inspection:
1. Inspect the battery posts and cables for tightness and corrosion. Tighten and clean as necessary.
2. Check the battery fluid level of unsealed batteries and, if necessary, fill with Distilled Water Only. Do not use tap water in batteries.
3. Have the state of charge and condition checked.
This should be done with an automotive-type battery hydrometer.
DANGER
Do not dispose of the battery in a fire. The battery is capable of exploding.
A battery presents a risk of electrical shock and high short circuit current. The following precautions are to be observed when working on batteries:
• Remove the 15A fuse from the generator control panel.
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the battery; and
• Disconnect charging source prior to connecting or disconnecting battery terminals.
Do not open or mutilate the battery. Released electrolyte has been known to be harmful to the skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off immediately with water;
• Where electrolyte contacts the eyes, flush thoroughly and immediately with water and seek medical attention; and
• Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of 1 pound (500 grams) bicarbonate of soda to 1 gallon (4 liters) of water. The bicarbonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.
Lead-acid batteries present a risk of fire because they generate hydrogen gas. The following procedures are to be followed:
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from body before touching the battery by first touching a grounded metal surface.
Be sure the AUTO/OFF/MANUAL switch is set to the OFF position before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.
Be sure the utility power supply is turned off and the 15A fuse is removed from the generator control panel, or sparking may occur at the battery posts as the cables are attached and cause an explosion.
VALVE CLEARANCE
After the first six (6) months of operation, check the valve clearance in the engine, adjust if necessary.
Important: If feeling uncomfortable about doing this procedure or the proper tools are not available, please contact the Authorized Dealer for service assistance. This is a very important step to insure longest life for the engine.
To check valve clearance:
•
•
•
•
The engine should be cool before checking. If valve clearance is 0.002" - 0.004" (0.05 - 0.1mm), adjustment is not needed.
Remove spark plug wires and position wires away from plugs.
Remove spark plugs.
Make sure the piston is at Top Dead Center (TDC) of its compression stroke (both valves closed). To get the piston at TDC, remove the intake screen at the front of the engine to gain access to the flywheel nut. Use a large socket and socket wrench to rotate the nut and hence the engine in a clockwise direction. While watching the piston through the spark plug hole. The piston should move up and down.
The piston is at TDC when it is at its highest point of travel.
•
23
Section 4 — Maintenance
Air-cooled Generators
To adjust valve clearance (if necessary):
•
•
•
•
Make sure the engine is at 60° to 80° F.
Make sure that the spark plug wire is removed from the spark plug and out of the way.
Remove the four screws attaching the valve cover with a #2 or #3 Phillips screwdriver.
Loosen the rocker jam nut. Use an 10mm allen wrench to turn the pivot ball stud while checking clearance between the rocker arm and the valve stem with a feeler gauge. Correct clearance is
0.002-0.004 inch (0.05-0.1 mm).
Figure 4.10 - Valve Clearance Adjustment
Jam Nut
Pivot Ball
S tud
Rocker
Arm
Valve
S tem
SYSTEM
Air inlet and outlet openings in the generator compartment must be open and unobstructed for continued proper operation. This includes such obstructions as high grass, weeds, brush, leaves and snow.
Without sufficient cooling and ventilating air flow, the engine/generator quickly overheats, which causes it to quickly shut down. (See Figure 4.11 for vent locations.)
Make sure the doors and roof are in place during operation as running the generator with them removed can effect cooling air movement.
Figure 4.11 – Cooling Vent Locations
NOTE:
Hold the rocker arm jam nut in place as the pivot ball stud is turned.
When valve clearance is correct, hold the pivot ball stud in place with the allen wrench and tighten the rocker arm jam nut. Tighten the jam nut to 174 in/lbs. torque. After tightening the jam nut, recheck valve clearance to make sure it did not change.
•
•
Install new valve cover gasket.
Re-attach the valve cover.
NOTE:
Start all four screws before tightening or it will not be possible to get all the screws in place. Make sure the valve cover gasket is in place.
•
•
•
Install spark plugs.
Re-attach the spark plug wire to the spark plug.
On the GT-530 and GT-990, repeat the process for the other cylinder.
The exhaust from this product gets extremely hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.
The maximum ambient temperature for the generator is 40° C (104° F).
4.9 ATTENTION AFTER SUBMERSION
If the generator has been submerged in water, it must not be started and operated. Following any submersion in water, have an Authorized Dealer thoroughly clean, dry and inspect the generator. If the structure
(ex. home) has been flooded, it should be inspected by a certified electrician to ensure there won't be any electrical problems during generator operation or when utility is returned.
24
Section 4 — Maintenance
Air-cooled Generators
4.10 CORROSION PROTECTION
Periodically wash and wax the enclosure using automotive type products. Frequent washing is recommended in salt water/coastal areas. Spray engine linkages with a light oil such as WD-40.
4.11 OUT OF SERVICE PROCEDURE
4.11.1 REMOVAL FROM SERVICE
If the generator cannot be exercised every seven days, and will be out of service longer than 90 days, prepare the generator for storage as follows:
1. Start the engine and let it warm up.
2. Close the fuel shutoff valve in the fuel supply line and allow the unit to shut down.
3. Once the unit has shut down, it will signal a low oil fault.
4. Set the generator’s main circuit breaker to its
OFF (or OPEN) position.
5. Set the AUTO/OFF/MANUAL switch to OFF and turn off the utility power to the transfer switch.
Remove the 15A fuse from the generator control panel. Disconnect the battery cables as outlined in “General Hazards”.
6. While the engine is still warm from running, drain the oil completely. Refill the crankcase with oil. See ”Engine Oil Recommendations".
7. Attach a tag to the engine indicating the viscosity and classification of the oil in the crankcase.
8. Remove the spark plug(s) and spray fogging agent into the spark plug(s) threaded openings.
Reinstall and tighten the spark plug(s).
9. Remove the battery and store it in a cool, dry room on a wooden board. Never store the battery on any concrete or earthen floor.
10. Clean and wipe the entire generator.
4.11.2 RETURN TO SERVICE
To return the unit to service after storage, proceed as follows:
1. Verify that utility power is turned off and that the
AUTO/OFF/MANUAL switch is set to OFF.
2. Check the tag on the engine for oil viscosity and classification. Verify that the correct recommended oil is used in the engine (see the Engine Oil
Recommendations section). If necessary, drain and refill with the proper oil.
3. Check the state of the battery. Fill all cells of unsealed batteries to the proper level with distilled water. DO NOT USE TAP WATER IN THE
BATTERY. Recharge the battery to 100 percent state of charge, or, if defective, replace the battery.
See “Specifications,” for type and size.
4. Clean and wipe the entire generator.
5. Make sure the 15A fuse is removed from the generator control panel. Reconnect the battery.
Observe battery polarity. Damage may occur if the battery is connected incorrectly.
6. Open the fuel shutoff valve.
7. Insert the 15A fuse into the generator control panel. Start the unit by moving the AUTO/OFF/
MANUAL switch to MANUAL. Allow the unit to warm up thoroughly.
8. Stop the unit by setting the AUTO/OFF/MANUAL switch to OFF.
9. Turn on the utility power to the transfer switch.
10. Set the AUTO/OFF/MANUAL switch to AUTO.
11. The generator is now ready for service.
NOTE:
If the battery was dead or disconnected, the exercise timer must be reset.
Section 4 — Maintenance
Air-cooled Generators
4.12 SERVICE SCHEDULE
ATTENTION: It is recommended that all service work be performed by the nearest Dealer.
SYSTEM/COMPONENT PROCEDURE FREQUENCY
X = Action
R = Replace as Necessary
* = Notify Dealer if Repair is Needed.
FUEL
Inspect Change Clean W = Weekly
M = Monthly
Y = Yearly
Fuel lines and connections* X
LUBRICATION
M
Oil level X
Oil X
M
Every 200 hours**, or 24
hours of continuous use,
Oil filter
COOLING
X Every 200 hours**, or 24
hours of continuous use,
X W Enclosure louvers X
BATTERY
Remove corrosion, X ensure dryness
Clean and tighten X battery terminals
Check charge state
Electrolyte level
(unsealed batteries only)*
ENGINE AND MOUNTING
X
X
R
R
X
X
M
M
EVERY 6 M
EVERY 6 M
Air cleaner
Spark plug(s)
GENERAL CONDITION
X
X
R
R
Vibration, Noise, Leakage, X
Temperature*
COMPLETE TUNE-UP* TO BE COMPLETED BY
2Y or 200 hours
2Y or 200 hours
M
2Y or 200 hours
* Contact the nearest dealer for assistance if necessary.
** Change oil and fi lter after fi rst eight (8) hours of operation and then every 200 hours thereafter, or 2 years, whichever occurs fi rst. Change sooner when operating under a heavy load or in a dusty or dirty environment or in high ambient temperatures.
Section 5 — Troubleshooting
Air-cooled Generators
5.1 TROUBLESHOOTING GUIDE
Problem Cause
The engine will not crank. 1. Fuse blown.
The engine cranks but will not start.
2. Loose, corroded or defective
3. Defective starter contactor. (7 kW) 3. *
4. Defective starter motor.
5. Dead Battery.
4. *
5. Charge or replace battery.
1. Out of fuel.
2. Defective fuel solenoid (FS).
Correction
1. Correct short circuit condition, replace 15A fuse in generator control panel.
2. Tighten, clean or replace
1. Replenish fuel/Turn on fuel valve.
2. *
3. *
The engine starts hard and runs rough. engine control board.
4. Defective spark plug(s).
5. Valve lash out of adjustment.
6. Choke not operating.
1. Air cleaner plugged or damaged.
2. Defective spark plug(s).
3. Fuel regulator not set.
4. Fuel pressure incorrect.
5. Fuel selector in wrong position.
6. Choke remains closed.
4. Clean, re-gap or replace plug(s).
5. Reset valve lash.
6. Verify choke plate moves freely.
1. Check, replace air cleaner.
2. Clean, re-gap or replace plug(s).
3. Set Fuel Regulator.
4. Confirm fuel pressure to regulator is 10-12” water column (0.36-0.43 psi) for LP, and 5-7” water column
(0.18-0.25 psi) for natural gas.
5. Move selector to correct position.
6. Verify choke plate moves freely.
The AUTO/OFF/MANUAL switch 1. Defective switch. is set to OFF, but the engine continues to run.
2. AUTO/OFF/MANUAL switch wired incorrectly.
3. Defective control board.
There is no AC output from 1. Main line circuit breaker is in the generator. the OFF (or OPEN) position.
2. Generator internal failure.
There is no transfer to standby after utility source failure.
Unit consumes large amounts of oil.
1. Defective transfer switch coil.
2. Defective transfer relay.
3. Transfer relay circuit open.
4. Defective control logic board.
1. Engine over filled with oil.
2. Engine breather defective.
4. Damaged gasket, seal or hose.
1. *
2. *
3. *
1. Reset circuit breaker to ON (or CLOSED).
2. *
1. *
2. *
3. *
4. *
1. Adjust oil to proper level.
2. *
4. Check for oil leaks.
*Contact the nearest Authorized Dealer for assistance.
27
28
Section 6 — Notes
Air-cooled Generators
Section 7 — Electrical Data
Air-cooled Generators
Electrical Schematic – 8, 10, 12 and 16 Circuit Load Center – Drawing No. 0F9775
E1
N1A
N1A
E1
7
1
7 9
4
9
3 6
194
A
TR
23
B
126 205
N1A
N1A
N2A
194
23
E1
N1A
F2
F1
E1
E2
B
B
N2A
A
NO
126
B
205
N2A
N1A
N2A
NC NC NO
COM
XB XA
COM
VR1
C1
ATS
VR2
C2
T1 T2
E1
E2
N2A
B E2
E2
NEUTRAL
CONNECTION
INSIDE SWITCH
B
LEGEND
E2
ATS-AUTOMATIC TRANSFER SWITCH
C1-UTILITY COIL & RECTIFIER
C2-GENERATOR COIL & RECTIFIER
F1,F2-5A, 600V FUSE
LC-CIRCUIT BREAKER (LOADS)
TR-TRANSFER RELAY
TS-TERMINAL STRIP
XA,XB-LIMIT SWITCHES
T1
T2
CIRCUIT 4
CIRCUIT 7
CIRCUIT 8
CIRCUIT 11
CIRCUIT 12
CIRCUIT 15
CIRCUIT 16
CIRCUIT 14
CIRCUIT 13
CIRCUIT 10
CIRCUIT 9
CIRCUIT 6
CIRCUIT 5
CIRCUIT 2
CIRCUIT 1
CIRCUIT 3
194
23
OPEN
E1
E2
N2
N1
LC
194
23
12Vdc TRANSER
COIL
N2
N1
240VAC
OUTPUT
BLACK
RED
NEUTRAL (WHITE)
NEUTRAL (WHITE)
RED (MAIN 2)
BLACK (MAIN 1)
TS TO
GENERATOR
CONTROL PANEL
TO GENERATOR
OUTPUT
CIRCUIT BREAKER
240VAC TO
MAIN DISTRIBUTION
PANEL
29
30
Section 7 — Electrical Data
Air-cooled Generators
Wiring Diagram – 10, 13 & 16kW, V-Twin – Drawing No. 0F7822-A
Section 7 — Electrical Data
Air-cooled Generators
Wiring Diagram – 10, 13 & 16kW, V-Twin – Drawing No. 0F7822-A
31
32
Section 7 — Electrical Data
Air-cooled Generators
Electrical Schematic – 10, 13 & 16kW, V-Twin – Drawing No. 0F7823-A
Section 7 — Electrical Data
Air-cooled Generators
Electrical Schematic – 10, 13 & 16kW, V-Twin – Drawing No. 0F7823-A
33
34
Section 7 — Electrical Data
Air-cooled Generators
Wiring Diagram – 7kW, Single Cylinder – Drawing No. 0F7820-A
Section 7 — Electrical Data
Air-cooled Generators
Wiring Diagram – 7kW, Single Cylinder – Drawing No. 0F7820-A
35
36
Section 7 — Electrical Data
Air-cooled Generators
Electrical Schematic – 7kW, Single Cylinder – Drawing No. 0F7821-A
Section 7 — Electrical Data
Air-cooled Generators
Electrical Schematic – 7kW, Single Cylinder – Drawing No. 0F7821-A
37
38
Section 7 — Electrical Data
Air-cooled Generators
Wiring Diagram – 8, 10, 12 and 16 Circuit Load Center – Drawing No. 0F9070-A
Section 7 — Electrical Data
Air-cooled Generators
Wiring Diagram – 8, 10, 12 and 16 Circuit Load Center – Drawing No. 0F9070-A
39
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
Enclosure – Drawing No. 0F9431-D
SHEET METAL PAINT/MATERIAL CODE LEGEND
The following exploded views contain part numbers of various sheet metal components. Only the base part number is listed. When ordering sheet metal, the correct color and material information must be included as a suffi x at the end of the part number as shown below.
Material Color Example: Desc. Part No. Material Color Order As"
S = Steel
A = Aluminum
N = Tan
G = Gray
B = Black
Roof
Door
Divider
0F6522
0F6555
0F6558
S = Steel
A = Aluminum
S = Steel
N = Tan
G = Gray
B = Black
0F6522SN
0F6555AG
0F6558SB
40
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
Enclosure – Drawing No. 0F9431-D
ITEM PART NO. QTY. DESCRIPTION
24
25
26
27
28
29
30
31
0F6570
0F6571
0D2979B
0D2979C
022097
022097
022473
0F7826
0F0165A
32
33
34
35
0F6550
0F0164A
0E1330A
021267A
36 0E5968
37
38
40
41
0F0165
0F0164
0A8475
0G0400
42 0F6552
43 0F9379
44 0D1839
45 0F8210
0F8209
0F9078
46 0F5458
16
17
18
19
20
21
22
23
10
11
12
13
14
15
1
2
3
4
5
6
0F9653
045771
022129
022129
022145
043107
090388
7 0D3700
0D3700*
022097*
022473*
8
9
049813*
0D4662
0D4662
0F8871
0F8080
0F8246
0F8915
0F6558
092120
0F7825
0F7824
0F6549
0F7824A
0D1840
047411
047411
0F0710
0A2115
0C6735
0D2979D
0D7176
0F7827
1 PAD, 24 X 48” WITH MOUNTING HOLES
4 NUT HEX M8-1.25
4 WASHER LOCK 5/16
5 WASHER LOCK 5/16 (7KW)
8 WASHER FLAT 5/16
4 SCREW HHC M8-1.25 X 25
15 SCREW TAPTITE M6-1.0 X 12
24 NUT, LOCKING FLANGE M6-1.0
14 NUT, LOCKING FLANGE M6-1.0
10 WASHER LOCK M6-1/4
10 WASHER FLAT 1/4-M6 ZINC
10 NUT HEX M6 X 1.0
14 SCREW HHTR 5/16-18 X 3/4" (7KW)
13 SCREW HHTR 5/16-18 X 3/4"
1 SCROLL, FAN (7KW, 10KW)
1 PANEL, ALTERNATOR DIVIDER (7KW)
1 PANEL, ALTERNATOR DIVIDER (10KW)
1 PANEL, ALTERNATOR DIVIDER
4 NUT LOCK TRIC M6 X 1.0
1 FOAM, MUFFLER BOX FRONT
1 FOAM, MUFFLER BOX END
1 ENCLOSURE, EXHAUST SIDE
1 FOAM, MUFFLER BOX END
2 BRACKET, BOTTOM SUPPORT
6 SCREW HHC M6-1.0 X 16 G8.8 (7KW)
8 SCREW HHC M6-1.0 X 16 G8.8
12 RIVET POP 0.125” X 0.337”
4 WASHER NYLON M6-1/4”
2 SUPPORT, ROOF FOLDING
2 CLOTH HARDWARE 266.7mm X 387.4mm
34 WASHER, SELF LOCKING
2 FOAM, EXHAUST ENCLOSURE COVER
1 COVER, BACK EXHAUST ENCLOSURE
1 COVER, FRONT EXHAUST ENCLOSURE
1 CLOTH, HARDWARE 266.7mm X 146mm
1 CLOTH, HARDWARE 543mm X 146mm
4 WASHER LOCK M6-1/4 (7KW)
3 WASHER LOCK M6-1/4
2 WASHER FLAT M6-1/4
1 FOAM, MUFFLER BOX BACK
1 HINGE TYPE B WITH STUDS, SOCKET
1 ENCLOSURE, SIDE & BACK
1 HINGE TYPE A WITH STUDS, SOCKET
1 GROMMET, 38.1 CROSS SLIT WITH HOLE
2 PLUG PLASTIC 1.5 BLIND GROMMET
11 GASKET, EXTRUDED TRIM
1 HINGE TYPE B WITH STUDS, PIN
1 HINGE TYPE A WITH STUDS, PIN
1 L/WASH SPECIAL #10
1 WIRE ASSEMBLY, GROUND
1 ENCLOSURE, ROOF
1 FOAM, ROOF ENCLOSURE
2 BRACKET, TOP SUPPORT
1 REGULATOR ASSEMBLY (7KW)
1 REGULATOR ASSEMBLY (10KW)
4 SCREW PLASTITE HI-LOW #10 X 3/8
ITEM PART NO. QTY. DESCRIPTION
47
48
49
50
0F5438
0F5434
0F8263
0F7886
0F7885
023484H
0D3058A
0E4245
51 0D3058C
52 0D1605A
0F7798
53
54
55
56
57
0F8380
0D3472
0C8285
0D3167
0E1330
64
65
66
67
68
69
70
71
58 043116
043116
59 086729
60 0F8039
61
62
022127
0388040AJ0
63 0F8847
0F8434
0F9968
0C2937
049813
0A1658
0G0617
092079
055414
0F8234
0F7711
72 0F8257
73 0C3906
74 0F6555
75 0F8555
76 0D3037
77 0D3037A
78 0F9143
79 0F8261
80 0F5440
0F9328
0F5478
81
82
83
84
051713
022152
036937
022158
85 0C8911
86 026850
89
90
0G3540
0G3539
1 HARNESS, ENGINE (7KW)
1 HARNESS ENG V-T HSB
1 PANEL, ENGINE DIVIDER (7KW)
1 PANEL, ENGINE DIVIDER (10KW)
1 PANEL, ENGINE DIVIDER
1 BUSHING SNAP SB-1500-18
1 FOAM, FRONT INTAKE BAFFLE (7KW)
1 FOAM, BACK INTAKE BAFFLE (7KW)
1 BAFFLE, INTAKE (7KW)
1 FOAM, TOP INTAKE BAFFLE
1 GROMMET OVAL 31.75 X 50.8
1 BRACKET, BATTERY SUPPORT
1 GASKET, BATTERY SUPPORT BRACKET
1 GROMMET, 38.1 DIA. CROSS SLIT
3 SCREW HHC, M6-1.0 X 12 G8.8(7KW)
1 SCREW HHC M6-1.0 X 12 G8.8
1 CONTACTOR, STARTER (7KW)
1 MOUNTING CLIP
1 NUT HEX 1/4-20 (7KW)
1 CABLE, #6 RED BATTERY 38.5”
1 GASKET, FRONT DIVIDER
1 GASKET, FRONT DIVIDER (10KW)
1 FUEL LINE, 1/2” OUTDOOR (NOT SHOWN)
1 BRACKET, BATTERY HOLD DOWN (7KW)
1 NUT HEX M6-1.0 G8
1 LOCK WASHER SPECIAL 1/4
1 EXTERNAL CONNECTION BOX
1 SCREW TAPTITE M6-1.0 X 25 BP
1 LUG SLDLSS #2-#8 X 17/64 CU
1 ASSEMBLY, ENCLOSURE BASE (7KW)
1 ASSEMBLY, ENCLOSURE BASE
1 FOAM, FRONT ENCLOSURE
2 SELF-ALIGN SCREW M6 HH
1 ENCLOSURE, FRONT
1 GASKET, DOOR SEAL
1 LATCH, QUARTER TURN LOCKING
1 LATCH, QUARTER TURN NON-LOCKING
2 PAWL, DOOR
1 FOAM, BACK ENCLOSURE
1 HARNESS GENERATOR TO EXTERNAL
CONNECTION BOX (7KW)
1 HARNESS GENERATOR TO EXTERNAL
CONNECTION BOX (10KW)
1 HARNESS GENERATOR TO EXTERNAL
CONNECTION BOX
2 WASHER FLAT M5
5 WASHER LOCK #10
2 SCREW PPHM#10-32 X 1
5 NUT HEX #10-32
1 POWER BLOCK
1 WASHER SHAKEPROOF EXT 1/4 STEEL
1 WASHER FLAT .125ID X .375OD
1 RIVET POP .122 X 0.465 STEEL
*ITEM 7 FOR MODELS WITH ALUMINUM ENCLOSURE
41
42
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
Control Panel – Drawing No. 0F9695-F
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
Control Panel – Drawing No. 0F9695-F
1 0E7886A
0E7886D
0E7886K
0E7886J
0E7886L
2
3
0A1801
0F9719
4 0C2174
5 075210A
7 0F8992
0F1504
0G5715
8 032300
9 022676
10
11
0E4494
0E7890
12 023484E
13
14
075476
043182
15 0E6480
16 0D4804A
0D4804A
17
18
0C1085
0C1085
058000H
19 023897
20 0F8040
21
0F9282
075235
22 0E3928
23 0D9784
0D9784
1 CIRCUIT BREAKER 30A X 2P 240V (7KW)
1 CIRCUIT BREAKER 45A X 2P 240V
(10KW)
1 CIRCUIT BREAKER 55A X 2P 240V
(13KW)
1 CIRCUIT BREAKER 65A X 2P 240V
(16KW)
1 CIRCUIT BREAKER 80A X 2P 240V
(18KW)
1 ASSEMBLY, BATTERY CHARGER ENGINE
1 ASSEMBLY, POTTED REGULATOR
1 RELAY, 12V 25A SPST (NON 7KW)
1 BLOCK
1 ASSEMBLY, HOME STANDBY
CONTROLLER
1 ASSEMBLY, HOME STANDBY
CONTROLLER (7KW)
1 ASSEMBLY, HOME STANDBY
CONTROLLER (18KW)
1 HOLDER,
1 FUSE, 15 AMP X AGC15
1 SWITCH, ROCKER DPDT ON-OFF-ON
1 CIRCUIT BREAKER MOUNTING BRACKET
1 SNAP BUSHING
4 SCREW PPHM M4-0.7 x 16mm
2 M3 LOCK WASHER (NON 7KW)
6 NUT HEX LOCK M4-0.7 NYLON INSERT
CURRENT TRANSFORMER, IDLE
CONTROL (NON 7KW)
24 0D8502
25 031879
26
031879
0F5433
27
28
29
30
31
32
33
34
35
36
37
0F5437
38 045770
39 0E7866
40
0E7867
0D3700
41
43
022097*
022473*
049813*
0G0400
0A1658
44
45
022473
0E3969
46 0G5454
47 0G5449A
CONTROL (18KW)
12 SCREW PPHM M3-0.5 x 8mm
8 SCREW PPHM M3-0.5 x 8mm (7KW)
2 M3-0.5 TRIC NUT (NON 7KW)
2 WASHER FLAT #10
1 CONTROL, PANEL BOTTOM
1 CONTROL, PANEL BOTTOM (7KW)
4 SCREW HHC M5-0.8 x 30mm
1 SWITCH, SPST
4 NUT HEX LOCK M3-0.5 NYLON INSERT
2 NUT HEX LOCK M3-0.5 NYLON INSERT
(7KW)
48
49
50
074908
049813
082025
0G0627
022507
022097
046689
063617
075475
043180
0F8041
0F9283
0G5449B
0D5303
0G6131
*ITEM 40 FOR MODELS WITH ALUMINUM ENCLOSURE
1 NEUTRAL BLOCK
4 WASHER FLAT #4
2 WASHER FLAT #4 (7KW)
1 HARNESS, CONTROL PANEL WIRE (NOT
SHOWN)
1 HARNESS, CONTROL PANEL WIRE (NOT
SHOWN) (7KW)
4 SCREW HHTT, M5-0.8 x 10 BP
4 NUT HEX M6-1.0
6 NUT HEX LOCK M5-0.8 NYLON INSERT
1 XFMR 240/16V 1VA&56VA W/PTC
2 SCREW HHC 1/4”-20 x 1/2”
4 WASHER LOCK M6-1/4”
1 TERMINAL STRIP 4 POSITION
1 RELAY PANEL 12VDC DPDT 10A 240VAC
2 SCREW PPHM M4-0.7 x 10mm
2 WASHER FLAT M4
1 COVER, CONTROL PANEL COMPONENT
1 COVER, CONTROL PANEL COMPONENT
(7KW)
2 SCREW HHC M5-0.8 x10mm
1 COVER, CONTROL PANEL
1 COVER, CONTROL PANEL (7KW)
8 NUT FLANGE M6-1.0 NYLOK
8 WASHER LOCK M6-1/4
8 WASHER FLAT 1/4-M6
8 NUT HEX M6 X 1.0
1 WIRE ASSEMBLY, GROUND
2 WASHER LOCK SPECIAL 1/4”
6 WASHER FLAT 1/4”-M6
2 SCREW PPH M3-0.5 X 30mm (18KW)
2 SPACER (18KW)
1 JUMPER WIRE, RED (18KW, NOT
SHOWN)
1 JUMPER WIRE, BLACK (18KW, NOT
SHOWN)
2 WASHER FLAT .25” ID X 1"OD ZINC
2 SCREW HHC M6-1.0 x 30mm
43
44
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
Transfer Switch Assembly – Drawing No. 0F9774-C
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
Transfer Switch Assembly – Drawing No. 0F9774-C
1 0F8278
2 0D4800
0F5211
0D3092
3
0F8312
0C2237
3A 077220
3B 077220A
3C
3D
082574
084464
4
5
074908
024912
6 0A1658
7 063617
8 0E7889A
0E7889
9
10
11
12
0F9213
0A1495
0A1661
022473
081108
13 0D4684
0D4684A
14 0F8279
15 0F4790
16 022152
17
18
064526
0E6155
19 063378
20 0G0979
0G0980
0G0981
0G0982
1 BOX CENTER
1 COVER, 8 CIRCUIT LOAD CENTER
1 COVER, 10 CIRCUIT LOAD CENTER
1 COVER, 12 CIRCUIT LOAD CENTER
1 COVER, 16 CIRCUIT LOAD CENTER
1 TRANSFER SWITCH HOME STANDBY
100A 2P 250V
1 COIL UTILITY
1 COIL STANDBY
1 INSULATOR-SIDEWALL (NOT SHOWN)
1 LIMIT SWITCH OPERATION (NOT
SHOWN)
6 SCREW HHTT M5-0.8 X 10
1 SCREW HHTT 1/4-20 X 5/8
1 LOCK SPECIAL-1/4”
1 RELAY PANEL 12VDC DPDT 10A@240VAC
1 8 CIRCUIT LOAD CENTER
1 12 CIRCUIT LOAD CENTER (ALSO USED
FOR 10 CIRCUIT)
1 16 CIRCUIT LOAD CENTER
4 SCREW HHTT M4-0.7 X 10
2 RIVET POP .156” X .675”
1 WASHER FLAT 1/4-M6 ZINC
1 PLUG PLASTIC
1 HARNESS ADAPTER PLATE
1 8 CIRCUIT HARNESS ADAPTER PLATE
1 SUBPLATE, LOAD CENTER
10.5” U-CHANNEL
6 WASHER LOCK #10
2 SCREW HWHS #6-25 X 3/8”
1 ARM EXTENDER PIN
4 HOLDER CABLE TIE
1 HARNESS, 8 CIRCUIT LOAD CENTER TO
MAIN PANEL
1 HARNESS, 10 CIRCUIT LOAD CENTER
TO MAIN PANEL
1 HARNESS, 12 CIRCUIT LOAD CENTER
TO MAIN PANEL
1 HARNESS, 16 CIRCUIT LOAD CENTER
TO MAIN PANEL
21
22
23
24
25
26
27
28
036933
077033
048850
028739
0A2110
0D3191
0D3088
29 073591
30 073590A
31 040213B
32
33
34
35
36
0E7888
0E7888A
0E7888B
0E7888C
0E7888D
37
38
39
0E7888E
0D3320
0F5439
40
41
42
074138
0F9327
0F6720
0F6720
074908
066849
0A7215
0E6193
2 LUG QUICK DISCONNECT NI-S 10X45
DEG BRASS / TIN
6 SCREW PPHM #10-32 X 3/8”
6 LUG SLDLSS 1/0-#14X9/16 AL/CU
1 BLOCK TERMINAL 20A 5 X 6 X 1100V
4 TIE WRAP 3.9" X .10"
4 SCREW SWAGE 1/4-20 X 1/2" ZINC
1 COVER, RELAY & TERMINAL BLOCK
1 WIRE HARNESS, LOAD CENTER (NOT
SHOWN)
2 FUSE HOLDER
2 FUSE 5A
4 SUPPORT SNAP-IN 1-3/8"
8 10 12 16 CIR.
A/R CIR BRK 20A 2P 1 1
A/R CIR BRK 30A 2P 1 1 1
A/R CIR BRK 15A 1P 5 3 5 5
A/R CIR BRK 20A 1P 1 3 3 5
A/R CIR BRK 40A 2P 1 1
A/R CIR BRK 50A 2P 1
1 COVER - HARNESS ENTRY
1 HARNESS, 8 CIRCUIT LOAD CENTER TO
EXT CONN BOX
1 HARNESS, 10 CIRCUIT LOAD CENTER
TO EXT CONN BOX
1 HARNESS, 12 CIRCUIT LOAD CENTER
TO EXT CONN BOX
1 HARNESS, 16 CIRCUIT LOAD CENTER
TO EXT CONN BOX
2 SCREW HHTT M5-0.8 X 10 (8 CIRCUIT)
2 SCREW HHTT M5-0.8 X 16 (10, 12, 16
CIRCUIT)
4 SCREW SW 1/4"-20 X 5/8” WITH WASHER
1 BRACKET, ARM EXTENDER
45
46
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
13 & 16kW, GT-990 Engine – Drawing No. 0G3071-J - Part 1
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
13 & 16kW, GT-990 Engine – Drawing No. 0G3071-J - Part 1
1
2
0C5729
0E9843A
3 0G0919
4 0C5372
5
6
7
8
9
0C3005
0E3372B
0D8067A
071983
0C2981F
11
12
0G2751
0G2565
13 0E1466
14 0D4041
15 0C2977
16
17
0C5943
0E3791E
18
19
20
21
22
23
24
0E3223
0D2157
0E6098
0D4123B
0E8152
0C3011
0C3009
25
26
27
28
0C3010
093873
0F5458
0C3027
29 0C5998
31 0F2664C
32 0C5305
33 0D6147
1 ASSY, CRANKCASE WITH SLEEVE
1 SEAL, 38 I.D. CRANKSHAFT GREEN
5 SCREW, HHFCS M6-1.0 X 12 G8.8
1 ASSEMBLY,
1 GASKET, BREATHER COVER
1 SEPARATOR, OIL BREATHER
1 ASSEMBLY, HEAD #1 G&S
4 RETAINER, PISTON PIN 20
1 ROCKER, COVER NO OIL FILL
2 PISTON, FLAT TOP DIA 90 COATED
2 RING SET, PISTON DIA 90
2 PIN PISTON
1 ASSEMBLY, CAMSHAFT & GEAR
1 GASKET, CRANK CASE
1 SEAL, OIL PASSAGE
1 ASSY, CRANKSHAFT GTH-990 DIRECT
DRIVE
2 ASSEMBLY, CONNECTING ROD
2 SCREW SHC M6-1.0 X 50 G8.8
1 SCREEN, OIL PICKUP
1 ASSEMBLY, OIL PUMP W/O O-RING
1 O-RING .49 ID X .07 THICK
2 COVER, OIL RELIEF
2 SPRING, OIL RELIEF
2 BALL, 1/2D OIL RELIEF
2 WASHER, LOCK RIB M6
1 SCREW, PLASTITE HI-LOW #10
1 O-RING, 3/8” X 1/2”
1 CLAMP, OIL TUBE
1 ASSEMBLY, DIPSTICK WITH HANDLE
1 TUBE, DIPSTICK
5 SCREW HHFC M6-1.0 X 10mm
34
35
36
37
043790A
0E9842A
0F8054
0C3006
38
39
40
41
080318
093064
0G1839
0D2723D
42 0C2979
43 086515
44 0D2274
45 0D3867
46 078672
47 0C5371
48 072694
49 0D5313
50
51
52
0D3998
0D6024
0C2976
53 086516
54 0C2229
55 083897
56 0D8067B
57 0D9853D
58 0C2978
59 0D4010
60
61
62
0D4012
0D8675A
0D8675B
63
64
65
0D4015
078699C
078699B
1 BARBED ELBOW 90 3/8NPT X 3/8 VS
1 SEAL, 42 I.D. CRANKSHAFT GREEN
1 GEARCOVER / ADAPTOR GTH-990
10 SCREW, HHFC M10-1.5 X 55
8 SCREW HHFC M6-1.0 X 25
1 ASSEMBLY, OIL FILL CAP
2 LIFT HOOK GT990/760
1 ROCKER, COVER WITH OIL FILL
2 GASKET, VALVE COVER
8 KEEPER, VALVE SPRING
4 RETAINER, VALVE SPRING
4 SPRING, VALVE
2 SEAL, VALVE STEM D7
4 WASHER, VALVE SPRING
4 STUD, ROCKER ARM PIVOT
4 ROCKER ARM
4 NUT HEX M8-1.0 G8 YEL CHR
2 PLATE, PUSH ROD GUIDE
12 SCREW HHFC M8-1.25 X 65
2 VALVE, EXHAUST
2 VALVE, INTAKE
4 TAPPET, SOLID
1 ASSEMBLY, HEAD #2 G&S
4 PUSHROD, 147
2 GASKET, HEAD
1 KIT GASKET
1 KIT BREATHER ASSEMBLY
1 KIT HEAD ASSEMBLY CYLINDER 1
1 KIT HEAD ASSEMBLY CYLINDER 2
1 KIT OIL RELIEF
2 SLEEVE DOWEL PIN 14 DIA.
4 SLEEVE DOWEL PIN 12 DIA.
47
48
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
13 & 16kW, GT-990 Engine – Drawing No. 0G3071-J - Part 2
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
13 & 16kW, GT-990 Engine – Drawing No. 0G3071-J - Part 2
64
65
022145
0C5136A
66 0C3024
67 0C3040
68
69
70
71
72
0C8127
0F9255
0E9582
0D4417
0E7585A
73
74
75
76
77
0E6043
0D1142A
0C3025
0G0290
070185F
78
79
0D3083
0F2094
80 094090
81 035461
82 0G3662
104
105
106
107
108
109
83 0G0286
84 0E9506
85
86
0C9764
0C3043
87
88
89
90
91
0C7694A
045756
082025
0G3730
090388
92 0E4997
93 0C3033
94
95
0C3034
0C9763
96 0D1131
97
98
99
100
101
102
103
0F1169K
051754
0A5992
0C3032
0C3031
0C3725B
0G4928A
0C7693A
0C3041A
082774
0C3036A
0C3019
0C3018
1 WASHER FLAT M8 – 5/16
2 KNOB, AIR CLEANER
1 COVER, AIRBOX NG/LP
1 PRE-CLEANER,
1 ELEMENT, AIR CLEANER
1 ASSEMBLY, MIXER/AIRBOX 990
4 SCREW SHLDR(8MM) M6-1.0 X 21
4 WASHER,RUBBER 1/4" X 1/8" THICK
2 SPARKPLUG, RCY14 GAP: 0.040”
2 SCREW TAPTITE M5 – 0.8 X 8
1 WRAPPER, LOWER CYLINDER 2
1 SWITCH, OIL PRESS
1 HOSE, 3/8” ID X 6-1/2”LG SAE J30R9
1 OIL FILTER, 90mm w/LOGO
1 ASSY, OIL DRAIN HOSE
2 SCREW M3 – 0.5 X 6 SEMS
1 SWITCH, THERMAL 293F
2 BARBED STRAIGHT 1/4NPT X 3/8
5 CLAMP, HOSE OETIKER STEPLESS
17mm
1 HOSE, 3/8” I.D. X 6”LG SAE J30R9
1 COOLER, OIL
4 SCREW PLASTITE 1/4-15 X 3/4
2 GASKET, MANIFOLD / PORT
1 MANIFOLD CYLINDER 2
4 SCREW, HHTT M6-1 x 10 LONG
1 NUT, HEX LOCK M5-0.8 ZINC
4 SCREW SHC M8 – 1.25 X 20 SEMS
13 SCREW TAPTITE M6–1X12 CLEAR ZINC
1 ASSY,GROUND WIRE CONNECTOR
1 WASHER, 25MM I.D.
1 NUT, HEX M24
4 NUT, GROMMET 1/4 PLUG
1 GUARD, FAN
1 HOUSING, BLOWER NG COOLER
2 SCREW HHC M8 – 1.25 X 12 G8.8
2 WASHER SHAKEPROOF INT M8 SS
1 PLATE, FAN
1 FAN, NYLON
1
2
1 FLYWHEEL ASSEMBLY
1 PLATE, BACKING WITH OIL COOLER
ZINC
MANIFOLD CYLINDER 1
SLEEVE, RUBBER
1 KEY, WOODRUFF 4 X 19D
1 HOSE BREATHER
1 WRAPPER, LOWER CYLINDER 1
1 WRAPPER, UPPER CYLINDER 1
0E9348
0E9599
0E9595
090987
0E9403
0E9571
0E9380
0A6345
0E9598
0E9593
0E5108
0D6342
0E9570
0E9577
0E5846
0E9419
0C4760
0F9253
0E9553
0E9554
0E9564
0E9575
0E9357
0A7094
0E9574
0F9273
0F5467
0E9557
0E1644
0E9568
0E9565
074027
0C3044
0C4756
075477
043116
0E1644
0E9572
0D9784
0D1143
0E9323
061906
022129
0F1177
022097
0G3110
0G3224A
0G3224B
139
140
141
142
143
144
145
146
147
148
129
130
131
132
133
134
135
136
137
138
149
150
151
152
153
154
155
156
157
119
120
121
122
123
124
125
126
127
128
110
111
112
113
114
115
116
117
118
1 WRAPPER, UPPER CYLINDER 2
1 STARTER MOTOR HEAR REDUCED 1KW
2 SCREW HHC M8 – 1.25 X 85 G8.8
3 WASHER LOCK M8 – 5/16
1 ASSEMBLY, GROUND WIRE
2 WASHER LOCK M6 – 1/4
4 SCREW TAPTITE M6 – 1.0 X 20 ZINC
1 ASSY, IGN COIL W/DIODE, CYLINDER 1
1 ASSY, IGN COIL W/DIODE, CYLINDER 2
1
2
ASSY, THROTTLE SHAFT
THROTTLE VALVE
4 SCREW PPHM M3 – 0.5 X 5
1 COVER, DUST, MIX/AIRBOX
1 SPRING, IDLE ADJUST
1 SCREW PPHM M5 – 0.58 X 20
2 SCREW HHC M6 – 1.0 X 12
1 SCREW BHSC M6-1.0 X 12 SS
1 BRACKET, STEPPER MOTOR
1 NUT HEX LOCK M3 – 0.5 NYLON INSERT
1
1
1
1
1
ASSY, CONTROLLER
BALL STUD, 10MM
ASSY, THROTTLE ROD
BELLOWS, INTAKE
EXPANSION PLUG
3
1
#10 O-RING
PLUG, MANIFOLD
1 ASSY, AIR BOX BASE
1 PIN, FUEL SELECTOR
1 PIN, FUEL SEL STOP
1
1
SOLENOID COVER
LINKAGE, CHOKE
4 SCREW PPPH HI-LO #6 X 1/2
1 SCREW PHTT M3 – 0.5 X 8
1 RETAINER, CHOKE RETURN SPRING
1 SPRING, CHOKE RETURN
1 WASHER, BELLEVILLE SPRING
1 SCREW PPHM M2 – 0.4 X 8
1 CHOKE ARM
1 SCREW SHOULDER M3 – 0.5 X 6
1
1
VALVE, CHOKE
SHAFT, CHOKE
1 SEAL, GOVERNOR ARM
2 SCREW PHM #4 – 40 X 1/4
1 BRACKET, SOLENOID
1 SOLENOID, 6VDC
1 NUT HEX M8 – 1.25 YELLOW ZINC
1 SPRING, CHOKE VALVE ADJUST
1 SCREW, BHSC M6-1.0 x 12
49
50
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
10kW, GT-530 Engine – Drawing No. 0F9429-N - Part 1
0C3592
0C3733
0C4390
088156
084186
0E9368
077168
0E9305
0C3590
0E9351
0A5776
0C5315A
0C5314A
0E9473
073144
0C3027
0E9358
093064
0E9334A
0E9352
0E9428B
0E3812
0C8566
0E9367A
0E9366
0E9304
0E9334C
076390
076389
088057
088411
0E9322A
0E9407A
0E9350
0E9318E
043116
093873
0G0272
0E9482
0C3591
083235
0E9455E
0E9353A
076307
077160
077161
0G0273
0G0274
0G0275
0G0276
0E9502
080318
0E3372C
078699B
0C5943
043790
30
31
32
33
34
35
36
37
38
39
20
21
22
23
24
25
26
27
28
29
10
11
12
13
14
15
16
17
18
19
1
2
3
4
5
6
7
8
9
50
51
52
53
54
55
56
40
41
42
43
44
45
46
47
48
49
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
10kW, GT-530 Engine – Drawing No. 0F9429-N - Part 1
2
12
1
2
2
8
4
4
2
4
2
1
1
1
2
1
1
1
1
9
1
3
3
1
1
2
2
2
1
1
1
2
2
1
1
1
1
4
2
1
1
12
1
6
1
1
4
4
1
1
1
2
4
4
2
4
CRANKCASE
SEAL D 35 X 48.2
SCREW HHFC M6 – 1.0 X 20
GASKET BREATHER ASSY
CYLINDER HEAD 1
COVER, ROCKER PLAIN
PISTON PIN RETAINER RING
PISTON
PISTON RING SET
ASSY CONNECTING ROD
ASSY, CAM & GEAR
GASKET CRANKCASE
ASSY CRANKSHAFT W/PLUG
SCREW HHC M6 – 1.0 X 12
WASHER LOCK M6 RIBBED
ASSY GEROTOR
SPRING OIL PRESSURE RELIEF
BALL 11/32 DIA PRESSURE RELIEF
GEROTOR OUTER 9MM THICK
GEROTOR INNER 9MM THICK
GEAR COVER
SCREW HHFC M8 – 1.25 X 45
O-RING 3/8 X 1/2
SCREEN OIL PICK-UP
ASSY, OIL FILL CAP
COVER, ROCKER, W/ FILL
GASKET, VALVE COVER
KEEPER, VALVE SPRING
VALVE RETAINER
SPRING VALVE
SEAL, VALVE STEM
WASHER, VALVE SPRING
SPARKPLUG
SCREW HHC M8 – 1.25 X 56
CYLINDER HEAD 2
VALVE EXHAUST
GASKET CYLINDER HEAD
VALVE INTAKE
TAPPET, SOLID
PUSHROD, ALUMINUM
PLATE, PUSH ROD GUIDE
NUT JAM (ROCKER ARM)
ROCKER ARM
STUD ROCKER ARM PIVOT
GASKET KIT
BREATHER KIT
KIT HEAD ASSY CYLINDER #1
KIT HEAD ASSEMBLY CYLINDER #2
SEPERATOR, OIL, GT530
SCREW HHFC M6 – 1.0 X 25
SEPARATOR, OIL BREATHER GT530
SLEEVE DOWEL PIN 12 DIA.
SEAL, OIL PASSAGE
BARBED EL 90 3/8 NPT X 3/8
51
52
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
10kW, GT-530 Engine – Drawing No. 0F9429-N - Part 2
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
10kW, GT-530 Engine – Drawing No. 0F9429-N - Part 2
58 022097
59 0E9561
60 0E9472
61 0E9471
62
63
078643B
0D9784
64 0E9584
65 0D6342
66 0E9587
67 0C9997
68 0E9319
69 0E9597
70
71
040976
022129
72 061906
73 0E9323
74 0E9507
75 0E9362
76 0E9337
77
78
0E9339
0G3378
79 0F2664H
80 0E9336F
81 0D6147
82
83
84
0E5139
0E9432
0E9338
85
86
87
88
0E9370
0E9505A
0F5458
045757
89 070185B
3 WASHER LOCK M6-1/4
1 INTAKE ADAPTER
1 GASKET, AIRBOX TO CARB/MIXER
1 GASKET, MANIFOLD TO CARB/MIXER
4 BOLT, CARB MOUNT M6 – 1.0 X 85
1 NUT HEX LOCK M3 – 0.5
1 ASSY, CONTROLLER
1 BALL STUD, 10 MM
1 ASSY, THROTTLE ROD
1 GUARD, FAN
2 GASKET INTAKE
1 BREATHER HOSE
4 SCREW SHC M8 – 1.25 X 20 G12.9
2 WASHER LOCK M8 – 5/16
2 SCREW HHC M8 – 1.25 X 85
1 STARTER MOTOR
6 SCREW HHFC M8 – 1.25 X 14
2 LIFTING HOOK
1 WRAPPER OUTER CYLINDER 1
1 WRAPPER INNER CYLINDER 1
1 TUBE, DIPSTICK GTH 530
1 ASSY, DIPSTICK /TEXT
1 BLOWER HOUSING
6 SCREW HHFC M6-1.0 X 10 G8.8
3 SCREW HHFC M6-1.0 X 8 G8.8
1 WRAPPER INNER CYLINDER 2
1 WRAPPER OUTER CYLINDER 2
1 GASKET, OIL FILTER ADAPTER
1 ASSY, DIRECT OIL COOLER ADAPTER
2 SCREW PLASTITE HI-LOW #10X3/8
3 SCREW HHC M6 – 1.0 X 25
1 OIL FILTER
110
111
112
113
114
115
116
117
118
100
101
102
103
104
105
106
107
108
109
90 094090
91 0F2094
92
93
0G4403
0D9235
94 082774
95 0F1177
96 0G3251A
97
98
99
0G3251B
026850
0E9443
0G3662
0G0286
0G0479
0G4985
0E9525C
0E9486
0A5992
051754
067890
067198N
0C3032
0E4997
0E9406
0G1705
0E9450
0E9376
0E9550
028916
0C8563
0G0919
1 THERMAL SWITCH
2 SCREW PPHM M3-0.5 X 6 SEMS
1 ASSY OIL DRAIN HOSE
1 OIL PRESSURE SWITCH HOBBS 5PSI
1 KEY, WOODRUFF 4 X 19D
1 ASSY, GROUNDING WIRE
1 ASSY IGNITION COIL CYLINDER 1
1 ASSY IGNITION COIL CYLINDER 2
4 WASHER SHAKEPROOF EXT 1/4
1 ASSY, MIXER DUAL FUEL
4 CLAMP, HOSE OETIKER STEPLESS
17mm
1 HOSE 3/8”ID X 6” SAE J30R9
1 HOSE 3/8”ID X 7.25 SAE J30R9
1 BACKING PLATE, GT-530 ZINC
1 ASSY, FLYWHEEL & RING GEAR
1 FAN, FLYWHEEL, 20 FIN, 218.8 OD
2 WASHER LOCK INT M8
2 SCREW HHC M8 – 1.25 X 12
1 NUT HEX M20 – 1.5
1 WASHER BELV – 20 X 2.2
1 PLATE, FAN
1
1
ASSY, GROUND WIRE CONNECTOR
OIL COOLER
13 SCREW HHFC M6 – 1.0 X 14
1 CENTER BAFFLE
1 INTAKE MANIFOLD
1 FRONT COVER
1 ELBOW - 1/8” NPT
2 SCREW, HHFC M6-1.0 x 12
4 SCREW, HHFCS M6-1 x 12 CLEAR ZINC
53
54
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
7kW, GN-410 Engine – Drawing No. 0F9428-D - Part 1
083897
077158
0C3150
072694
083907
0D3998
078694
021742
0D6094
076329
076361
0A8898D
0D2274
0C4391
086025
0E3341
021714
086516
086517
0D9853B
0E3221
0E1466
021533
0E2985
071983
0E8440
0A7628
078658
078659
088261E
0E3812
0E6519
078645
0A7811
0G3358
076701
021713B
078691
0A5771
0A5776
0E0057
0D4788
074908
086515
078606
0A1442
078672
089673
0B2104
078699C
0A7627
043790A
078699B
31
32
33
34
35
36
37
38
39
40
21
22
23
24
25
26
27
28
29
30
11
12
13
14
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
41
42
43
44
45
46
47
48
49
50
51
52
53
54
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
7kW, GN-410 Engine – Drawing No. 0F9428-D - Part 1
2
1
4
1
1
2
1
1
2
2
1
1
1
1
2
1
1
2
2
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
2
8
1
2
1
2
1
1
1
4
4
1
1
2
ASSEMBLY, CONNECTING ROD
PIN, PISTON D20
SET, PISTON RING 90MM
RETAINER, PISTON PIN 20
ASSEMBLY, CRANKSHAFT GH410 SMALL TAPER
ARM, GOVERNOR RC45
PIN, “R” GOVERNOR ARM
WASHER, GOVERNOR ARM THRUST
CRANKCASE, SUBASSEMBLY WITH PLUGS GH410
SEAL, 35 I.D. CRANKSHAFT
ASSEMBLY, GOVERNOR GEAR
C-RING, GOVERNOR GEAR RETAINER
SPOOL, GOVERNOR- MACHINE
ASSEMBLY, CAMSHAFT & GEAR 410HSB
GASKET , CRANKCASE
GASKET, HEAD 410
COVER, OIL PRESSURE RELIEF
SPRING, OIL RELIEF 360
BALL, DIA 11/32 PRESSURE RELIEF
WASHER, THRUST GOVERNOR GEAR
ASSEMBLY, COVER, GEAR TOP CHECK / FILL
RETAINER, VALVE SPRING
VALVE SPRING LF
SET,GEROTOR 12 THK
BALANCER
ASSEMBLY,CYLINDER HEAD SEATS & GUIDES
VALVE, EXHAUST
VALVE, INTAKE
PUSH ROD 174.9
TAPPET
ASSEMBLY, SCREEN OIL PICK-UP
GASKET, ROCKER COVER 410
STUD, D20 PIVOT BALL
ROCKER ARM
NUT, JAM (ROCKER ARM)
PLATE, PUSH ROD GUIDE
SCREW, HHFL M10-1.5 X 105
ASSEMBLY, ROCKER COVER BREATHER
PLUG, OIL FILL PLASTIC
O-RING 17.8 I.D. x 2.4
PLUG, STANDARD PIPE 3/8 STEEL SQUARE HEAD
SCREW, TAPTITE M5-0.8 X 10 BP
KEEPER, VALVE SPRING
SCREW & LOCKWASHER M6-1 X 12
SCREW, HHFC M8-1.25 X 42
SEAL, VALVE STEM D7
WASHER, VALVE SPRING
WASHER, LARGE SPRING
DOWEL, SEAMED SLEEVE
SHAFT, GOVERNOR RC55
BARBED ELBOW 90 3/8NPT X 3/8 LOCKTITE
DOWEL, SLEEVE SEAMED 12 DIA.
55
56
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
7kW, GN-410 Engine – Drawing No. 0F9428-D - Part 2
049821
099236
070185B
082774
091222E
067198N
067890
0E7585
072734
072735
0C3978
0C6040
0D9760
0G3111
0F3800
083502
082025
0G4403
0E7887C
090072
094090
022145
0F2094
0C4373
022717B
0F3865
0F3855
039253
0D3751
0F3921
0C8493
0D8758
0C1069
0D2922
0F8426
0C9997
088434
045756
0C4176A
0D9004A
059985
022129
0C2458A
083512
0D1401A
091039
0C9619
049811
022097
040945
086999
0D5667A
31
32
33
34
35
36
37
38
39
40
21
22
23
24
25
26
27
28
29
30
41
42
43
44
45
46
47
48
49
50
51
52
11
12
13
14
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
7kW, GN-410 Engine – Drawing No. 0F9428-D - Part 2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
2
4
2
1
1
1
1
1
1
1
11
1
1
2
3
5
1
1
1
1
SCREW, TAPTITE M6-1X10 YELLOW CHROME
SCREW, SHC M8-1.25 X 45 G12.9
WASHER, LOCK M8-5/16
BACKPLATE, L/F D/F
SCREW, TAPTITE M8-1.25 X 16 BP
BREATHER TUBE
GASKET, INTAKE ADAPTER
ASSEMBLY, PLASTIC CARB
WASHER, FLAT M6
WASHER, LOCK M6-1/4
SCREW, SHC M6-1.0 X 20 G12.9
GASKET,OIL FILTR ADAPTER
ADAPTER, OIL FILTER
SCREW, SHC M8-1.25 X 30 G12.9
SWITCH, OIL 8.0 PSI
OIL FILTER
KEY, WOODRFF 4 X 19D
FLYWHEEL WITH RING GEAR 32DEG.
WASHER,BELV-20 X 2.2
NUT, HEX - FLYWHEEL
SPARKPLUG
ASSEMBLY,GOVERNOR LEVER 12 HP
ROD,GOVERNOR CONTROL.
SPRING, ANTI-LASH
ASSEMBLY, WIRE
ASSEMBLY, IGNITION COIL
SCREW, TAPTITE M6-1.0 X 25 ZINC
SPRING GOVERNOR
BOLT, GOVERNOR ADJUST M5
NUT HEX LOCK M5-0.8 NYINS ZINC
ASSY OIL DRAIN HOSE
ASSEMBLY, CAP & DIPSTICK
O-RING 9/16 X 3/4 X 3/32
SWITCH, THERMAL 293F
WASHER FLAT 5/16 - M8
SCREW, M3-0.5 X 6 SEMS
SPACER ENDFRAME
GOMMET
SPRING SECONDARY
BRACKET SECONDARY GOVERNOR SPRING
SCREW HHC M8-1.25 x 20
SPRING, IDLE RETURNING
BARREL GOVERNOR ADJUSTMENT
SCREW SHC M5-0.8 x 30
ENGINE LIFT HOOK
57
58
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
7kW, GN-410 Engine – Drawing No. 0F9422-C
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
7kW, GN-410 Engine – Drawing No. 0F9422-C
029451
049451
022237
022511
022131
039287
022145
049820
090388
022129
022259
059637
048031K
0C9592
048031M
040976
0G0414
0D5823
090239
0C6989
0F8186
0F5540H
0C9934H
0F7774A
0C8096
0F6591
0F8078
056482
0C3168
056147
0D1847
0C7038C
0F9445
0F9497
0C7038B
0C7758
0388050AE0
0C2417A
0F6528
066386
0D1214
0C8127
0C3024
0D2273
055934N
0F7065
0C5136A
039253
022473
066849
0F6551
0F8079
0F0710
0F8256
045771
0G0676
074906
32
33
34
35
36
37
38
39
40
41
22
23
24
25
26
27
28
29
30
31
12
13
14
15
16
17
18
19
20
21
1
2
3
4
5
6
7
9
10
11
53
54
55
56
57
58
59
42
43
44
45
46
47
48
49
50
52
2
1
3
1
1
8
2
3
1
2
1.8 FT
1
4
4
4
4
18
4
8
17
4
1
1
1
1
4
1
1
1
1
1
1
1
3
1
1
1
1
1
1
1
1
2
1
4
2
4
1
1
1
1
1
1.25 FT
2
2
4
2
STATOR
ROTOR
CARRIER, REAR BEARING
FAN, 8” CURVED BLADE
MUFFLER
TAIL PIPE, MUFFLER
BEARING
5/16 SPECIAL L/WASH
BOLT ROTOR HHCS 5/16”-24 X 13-1/2” G5
BOLT STATOR IHHCS M8-1.25 x 305mm
BRACKET, ALTERNATOR MOUNTING
DUCT, ALTERNATOR AIR
GASKET, ALTERNATOR AIR DUCT
BRACKET, ENGINE MOUNTING
RUBBER MOUNT
CABLE, #6 40” BLACK BATTERY
EARTH STRAP 3/8X 3/8
EXHAUST FLEX
ASSEMBLY BRUSH HOLDER
TAPE ELEC UL FOAM 1/8 X 1/2
WASHER FLAT .406ID X 1.62OD
WASHER LOCK 3/8
BOLT HHC 3/8-16 X 1-1/4 G5
WASHER FLAT 3/8
SCREW HHC M8-1.25 X 45 G8.8
WASHER FLAT 5/16
NUT LOCK HEX M8-1.25 NYL INSRT
SCREW TAP M6-1.0X12
WASHER LOCK M8-5/16
NUT HEX 5/16-18
SCREW TAPTITE 3/8-16X 3/4”
BAND, HOSE CLAMP 35.05 DIA.
BELLOWS
HOSE CLAMP 3/4"
SCREW SHC M8-1.25 X 20 G12.9
PLATE “HOT”
U-BOLT 5/16”-18 X 1.62” W/ SADDLE
GASKET, EXHAUST
STINGER, ENGINE AIR IN
BASE, AIR CLEANER
ELEMENT, AIR CLEANER
COVER, AIR CLEANER NG/LP
TUBE, 1.25"O.D. x 20Ga. x 12.125" LONG
CLAMP VINYL 1.31 X .281 Z
HOSE LP 1/2" I.D.
KNOB, AIR CLEANER
SCREW HHC M8-1.25 X 20 G8.8
WASHER FLAT 1/4
SCREW HHTT M5-0.8 X 16
FLEX COVER
BRACKET MUFFLER ACCESS
RIVET POP 0.125” X 0.337”
EXHAUST MANIFOLD
NUT HEX M8-1.25 NY INS
SCREW THTT M6-1.0 X 10
SCREW HHTT M6-1.0 X 20
59
60
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
10, 13, and 16kW, V-twin Generators – Drawing No. 0G4392-A
ITEM PART NO. QTY. DESCRIPTION
1 040976
2 0F6694
0F5538
0F7548
3 0F9795
0F5539
0F7549
4
5
0F7774
0E9579
0F8998
6 0F6591
7
8
0F8078
099502
9 056482
10 0C3168
11 0D1838
12
13
14
15
0D1846
0C7038
0F9396
0D2559
16 0C7038A
0F4179
17 0C7758
18 0388050AD0
19 0C2417A
20 0F6528
21 066386
22 029451
23 049451
24
25
26
27
022237
035685
0E9549
051731
28
29
30
022145
049820
0G0676
4
1
1
SCREW SHC M8-1.25 X 20mm
STATOR
ROTOR
1 CARRIER, REAR BEARING
1 FAN, 12” CURVED BLADE
1 FAN, 12” CURVED BLADE (10KW)
1 MUFFLER
1 TAIL PIPE, MUFFLER
2 CLAMP HOSE #24 B1.06-2.00 (10KW)
1 BEARING
3 5/16 SPECIAL LOCK WASHER
1 BOLT, IHHCS 3/8”-24 X 15.50”
4 BOLT, IHHCS M8-1.25 X 345mm
1 BRACKET, ALTERNATOR MOUNTING
1 DUCT, ALTERNATOR AIR
1 GASKET, ALTERNATOR AIR DUCT
1 BRACKET, ENGINE MOUNTING
1 PLATE, MOUNTING ENG 530HSB
4 RUBBER MOUNT
1 CABLE, #6 48” BLACK BATTERY
1 EARTH STRAP 3/8 X 3/8
1 EXHAUST FLEX
1 ASSEMBLY BRUSH HOLDER
2.6 FT TAPE ELEC UL FOAM 1/8 X 1/2
1 WASHER FLAT .406ID X 1.62OD
1 WASHER LOCK 3/8
1 CLAMP HOSE #28 1.32-2.25 (10KW)
1 HOSE, INTAKE GTH530 HSB (10KW)
4 SCREW HHC M8-1.25 X 50
18 WASHER FLAT 5/16 ZINC
4 NUT LOCK HEX M8-1.25 NYL INSERT
2 SCREW THTT M6-1.0 X 10
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
10, 13, and 16kW, V-twin Generators – Drawing No. 0G4392-A
ITEM PART NO. QTY. DESCRIPTION
31
32
33
34
35
36
37
022129
022259
059637
0E9591
0F7065
048031M
0E9589
18 WASHER LOCK M8-5/16
8 NUT LOCK HEX 5/16-18
2 SCREW TAPTITE 3/8-16 X ¾
1 SPRING-CHOKE RETURN (10KW)
3 FT HOSE RES ½ LP GAS
4 HOSE CLAMP ¾” I.D.
1 CHOKE HSG (10KW)
38 0G0414
39 0D5823
40 0E9369
0C4138
41
42
43
44
040173
074995
066849
0F7799
0F8115
1
3
2
PLATE, “HOT”
U-BOLT 5/16”-18 X 1.62” WITH SADDLE
GASKET, EXHAUST PORT (10KW)
2 CLAMP HOSE #5.5 0.62”-0.62” (10KW)
1.44 FT HOSE ¼ ID LPG 350PSI UL21 (10KW)
2 SCREW HHTT M5-0.8 X 16
1 EXHAUST MANIFOLD
1 EXHAUST MANIFOLD (10KW)
45 0G30430GS0R 1 FLEX COVER
0G30440GS0R 1 FLEX COVER (10KW)
46 0E9595 2 SCREW PPPH HI-LO #6/1/2 W/ #5HD
(10KW)
56
57
58
59
60
61
47
48
49
50
090388
045771
039253
0F0710
51
52
0F8079
0F9273
53 0E9592
54 0E9588
55 077091
0E9581
0E9594
0E9590
0E9542
0D1683
077075
7
4
2
2
1
1
2
1
1
1
SCREW TAPTITE M6-1.0 X 12
NUT HEX M8-1.25
SCREW HHC M8-1.25 X 20
RIVET POP 0.125” X 0.337”
BRACKET MUFFLER ACCESS
SOLENOID, 6 VOLTS DC (10KW)
SCREW PPHM $4-40 X 3/8 SEMS (10KW)
LINKAGE, CHOKE (10KW)
COTTER PIN (10KW)
1 AIR CLEANER GTH530 HSB (10KW)
3 SCREW PPPH HI-LO #14-15 X ½ (10KW)
1 ASSEMBLY, CHOKE SHAFT (10KW)
1 VALVE, CHOKE (10KW)
2 SCREW PFHM M3-0.5 X 5 (10KW)
BOOT, CHOKE SOLENOID (10KW)
61
62
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
7 & 10kW, GN-410/GT-530 Regulator – Drawing No. 0F9425-B
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
7 & 10kW, GN-410/GT-530 Regulator – Drawing No. 0F9425-B
070728
0C6069
0C5762
0F9189
045764
0C6731
0C6067
0C4706
0C6068
0C4643A
072683
072683
0A4032
0D3308
024310
0D3973
042907
028414A
035483
0G0247
0F9773B
0F9773A
0D5694
0F9285
0F5022
0C4647
0D4166
0F8822
022145
022129
0F4795
0C5760P
0C6606
0C6606
097934
0C4645
0C5761
0C5968
0C6066
0C5759
0C5764A
0C5764
27
28
29
30
31
32
33
34
35
36
37
18
19
20
21
22
23
24
25
26
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
1
2
1
1
1
2
1
1
4
1
1
1
4
2
2
2
16
2
2
2
2
2
1
2
1
1
2
2
2
2
2
2
1
1
1
1
1
1
2
2
4
1
CASTING, TWIN REGULATOR HOUSING (7KW)
SOLENOID COIL, 12VDC
GASKET , SOLENOID
PLUNGER, LP REGULATOR ASSEMBLY
WASHER FLAT 5/16-M8
WASHER LOCK 5/16-M8
SCREW PPHM SEMS M4-0.7 X 10
FUEL JET GASEOUS REGULATOR (7KW)
BARBED STRAIGHT ½ NPT x ½ (7KW)
BARBED STRAIGHT ½ NPT x ½
ADJUSTER SCREW, TWIN REGULATOR (7KW)
SUPPORT, INLET SEAL
PIN, PIVOT ARM
SPRING, REGULATOR (7KW)
SCREW, PFHMS M3-0.5 x 5
COVER, TWIN REGULATOR (7KW)
SCREW, TAPTITE M4X8 BP
RIVET, POP .118 X .125
CAP, DIAPHRAGM SUPPORT
INLET, TWIN REGULATOR 11.11 DIA.
PLUG STD PIPE 1/8 SOCKET HEAD (7KW)
PLUG STD PIPE 1/8 SOCKET HEAD
PIN, LIMITED ADJUSTMENT (7KW)
WASHER, FLAT M3 X 10mm O.D.
PLUG, STANDARD PIPE 1/2” STEEL SQUARE HEAD (7KW)
PLUG, EXPANSION 16mm (7KW)
SCREW HHC M8-1.25 X 16
BARBED STRAIGHT 1/8”NPT X ¼” (10KW)
NIPPLE PIPE 1/8” NPT X 1-1/2” (10KW)
SOLENOID, LP/NG DC12V (10KW)
63
64
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
13 & 16kW, GT-990 Regulator – Drawing No. 0F9426-A
045764
0C6731
0C6067
0C4706
0C6068
0C4643A
072683
049226
0D3308
051713
0F8979
051716
0E9533
0E9534
0E9535
0F9285
0F5022
0C4647
0D4166
0F8096
022145
022129
0F4795
045771
0C6606
042907
026915A
0C5761
0C5968
0C6066
0C5759
0C5764
070728
0C6069
0F9189
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
11
12
13
14
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
Section 8 — Exploded Views and Parts Lists
Air-cooled Generators
13 & 16kW, GT-990 Regulator – Drawing No. 0F9426-A
2
3
4
4
4
16
2
2
2
2
1
4
1
1
1
2
2
4
2
2
2
1
2
2
2
4
4
8
2
2
1
1
2
1
1
SOLENOID COIL, 12VDC
GASKET , SOLENOID
PLUNGER, LP REGULATOR ASSEMBLY
BRKT REGULATOR MOUNTING 990
WASHER FLAT 5/16-M8
WASHER LOCK 5/16-M8
SCREW PPHM SEMS M4-0.7 X 10
NUT HEX M8-1.25
BARBED STRAIGHT ½ NPT x ½
SCREW HHC M8-1.25 X 16
NIPPLE CLOSE ¾ X 1.375 WITH VIBRA SEAL
SUPPORT, INLET SEAL
PIN, PIVOT ARM
SCREW, PFHMS M3-0.5 x 5
SCREW, TAPTITE M4X8 BP
RIVET, POP .118 X .125
CAP, DIAPHRAGM SUPPORT
INLET, TWIN REGULATOR 11.11 DIA.
PLUG STD PIPE 1/8 SOCKET HEAD
WASHER, LOCK, M5
WASHER, FLAT M3 X 10mm O.D.
WASHER, FLAT, M5
SOLENOID COVER PLATE
NUT HEX M5-0.8
ASSY, FUEL SYSTEM PLENUM
65
66
Section 9 — Mounting Dimensions
Air-cooled Generators
Drawing No. 0F9424-D
Section 9 — Mounting Dimensions
Air-cooled Generators
Drawing No. 0F9424-D
67
Section 10 – Warranty
Air-cooled Generators
NOTE: This Emission Control Warranty Statement pertains to this product only IF the generator size is 15 kW or below.
CALIFORNIA EMISSION CONTROL WARRANTY STATEMENT
YOUR WARRANTY RIGHTS AND OBLIGATIONS
The California Air Resources Board (CARB) and Generac Power Systems, Inc. (Generac) are pleased to explain the Emission
Control System Warranty on your new engine.
* In California, new utility, and lawn and garden equipment engines must be designed, built and equipped to meet the state’s stringent anti-smog standards. Generac will warrant the emission control system on your engine for the periods of time listed below provided there has been no abuse, neglect, unapproved modification or improper maintenance of your engine.
Your emission control system may include parts such as the carburetor, ignition system and exhaust system. Generac will repair your engine at no cost to you for diagnosis, replacement parts and labor, should a warrantable condition occur.
MANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE:
Emissions control systems on 1995 and later model year engines are warranted for two years as hereinafter noted. If, during such warranty period, any emission-related component or system on your engine is found to be defective in materials or workmanship, repairs or replacement will be performed by a Generac Authorized Warranty Service Facility.
PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES:
As the engine purchaser/owner, you are responsible for the completion of all required maintenance as listed in your factory supplied Owner’s Manual.
For warranty purposes, Generac recommends that you retain all receipts covering maintenance on your engine. However, Generac cannot deny warranty solely due to the lack of receipts or for your failure to ensure the completion of all scheduled maintenance.
As the engine purchaser/owner, you should, however, be aware that Generac may deny any and/or all warranty coverage or responsibility if your engine, or a part/component thereof, has failed due to abuse, neglect , improper maintenance or unapproved modifications, or the use of counterfeit and/or “grey market” parts not made, supplied or approved by Generac.
You are responsible for contacting a Generac Authorized Warranty Service Facility as soon as a problem occurs.
The warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days.
Warranty service can be arranged by contacting either your selling dealer or a Generac Authorized Warranty Service Facility.
To locate the Generac Authorized Warranty Service Facility nearest you, call our toll-free number:
1-800-333-1322
IMPORTANT NOTE: This warranty statement explains your rights and obligations under the Emission Control System
Warranty (ECS Warranty), which is provided to you by Generac pursuant to California law. See also the “Generac Limited
Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by
Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where the Generac Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac Warranty describe important rights and obligations with respect to your new engine.
Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty service, evidence must be presented showing the date of the sale to the original purchaser/owner.
If you have any questions regarding your warranty rights and responsibilities, you should contact Generac at one of the following addresses:
For Air-cooled Product ...
ATTENTION WARRANTY DEPARTMENT
GENERAC POWER SYSTEMS, INC.
P.O. BOX 297
WHITEWATER, WI 53190
Part 1
For Liquid-cooled Product ...
ATTENTION WARRANTY DEPARTMENT
GENERAC POWER SYSTEMS, INC.
211 MURPHY DRIVE
EAGLE, WI 53119
68
Section 10 – Warranty
Air-cooled Generators
EMISSION CONTROL SYSTEM WARRANTY
Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines:
(a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall continue for 24 consecutive months thereafter.
(b) General Emissions Warranty Coverage: Generac warrants to the original, end-use purchaser/owner of the new engine or equipment and to each subsequent purchaser/owner that each of its engines is ...
(1) Designed, built and equipped so as to conform with all applicable regulations adopted by the CARB pursuant to its authority, and
(2) Free from defects in materials and workmanship which, at any time during the ECS Warranty Period, may cause a warranted emissions-related part to fail to be identical in all material respects to the part as described in the engine manufacturer’s application for certification.
(c) The ECS Warranty only pertains to emissions-related parts on your engine, as follows:
(1) Any warranted, emissions-related parts that are not scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the ECS Warranty Period. If any such part fails during the ECS Warranty Period, it shall be repaired or replaced by Generac according to Subsection (4) below. Any such part repaired or replaced under the
ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.
(2) Any warranted, emissions-related part that is scheduled only for regular inspection as specified in the Owner’s Manual shall be warranted for the ECS Warranty Period. A statement in such written instructions to the effect of “repair or replace as necessary” shall not reduce the ECS Warranty Period. Any such part repaired or replaced under the ECS
Warranty shall be warranted for the remainder of the ECS Warranty Period.
(3) Any warranted, emissions-related part that is scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the period of time prior to the first scheduled replacement point for that part. If the part fails prior to the first scheduled replacement, the part shall be repaired or replaced by Generac according to Subsection
(4) below. Any such emissions-related part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions-related part.
(4) Repair or replacement of any warranted, emissions-related part under this ECS Warranty shall be performed at no charge to the owner at a Generac Authorized Warranty Service Facility.
(5) When the engine is inspected by a Generac Authorized Warranty Service Facility, the owner shall not be held responsible for diagnostic costs if the repair is deemed warrantable.
(6) Generac shall be liable for damages to other original engine components or approved modifications proximately caused by a failure under warranty of any emission-related part covered by the ECS Warranty.
(7) Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted emission-related parts sufficient to meet the expected demand for such emission-related parts.
(8) Any Generac authorized and approved emission-related replacement part may be used in the performance of any ECS
Warranty maintenance or repairs and will be provided without charge to the owner. Such use shall not reduce Generac
ECS Warranty obligations.
(9) Unapproved, add-on, modified, counterfeit and/or “grey market” parts may not be used to modify or repair a Generac engine. Such use voids this ECS Warranty and shall be sufficient grounds for disallowing an ECS Warranty claim.
Generac shall not be held liable hereunder for failures of any warranted parts of a Generac engine caused by the use of such an unapproved, add-on, modified, counterfeit and/or “grey market” part.
EMISSION RELATED PARTS INCLUDE THE FOLLOWING:
1) Fuel Metering System:
1.2) LPG/Natural Gas carburetion assembly and its internal components.
a) Fuel controller (if so equipped) b) Mixer and its gaskets (if so equipped) c) Carburetor and its gaskets (if so equipped) d) Primary gas regulator (if so equipped) e) LP liquid vaporizer (if so equipped)
2) Air Induction System including: a) Intake pipe/manifold b) Air cleaner
3) Ignition System including: a) Spark plug b) Ignition module
4) Catalytic Muffler Assembly (if so equipped) including: a) Muffler gasket b) Exhaust manifold
5) Crankcase Breather Assembly including: a) Breather connection tube
* Generac engine types covered by this warranty statement include the following:
1) Prepackaged Standby Generator
2) Auxiliary Power Unit (APU) Generator
3) Standby Generator
Part 2
69
Section 10 – Warranty
Air-cooled Generators
GENERAC POWER SYSTEMS "TWO YEAR" LIMITED WARRANTY FOR GUARDIAN
®
"PREPACKAGED EMERGENCY AUTOMATIC STANDBY GENERATORS"
For a period of two years from the date of original sale, Generac Power S ystems, Inc. (Generac) warrants that its Guardian generator will be free from defects in material and workmanship for the items and period set forth below. Generac will, at its option, repair or replace any part which, upon examination, inspection and testing by Generac or a Guardian Authorized Warranty S ervice Dealer, is found to be defective. Any equipment that the purchaser/owner claims to be defective must be examined by the nearest Guardian Authorized
Warranty S ervice Dealer. All transportation costs under the warranty, including return to the factory, are to be borne and prepaid by the purchaser/owner. This warranty applies only to Generac Guardian prepackaged emergency automatic standby generators sold and rated for use in " S tandby" applications.
WARRANTY SCHEDULE
YEAR S ONE and TWO - 100% (one hundred percent) transferable coverage on Labor and Part(s) listed (proof of purchase and maintenance is required):
Engine - All Components
Alternator - All Components
Transfer S ystem - All Components
S teel enclosures are warranted against rusting for the first year of ownership only. Damage caused after receipt of generator is the responsibility of the owner and is not covered by this warranty. Nicks, scrapes, dents or scratches to the painted enclosure should be repaired promptly by the owner.
All warranty expense allowances are subject to the conditions defined in Guardian's Warranty Policies, Procedures and Flat Rate
Manual.
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:
• Guardian generators that utilize non-Guardian/Generac replacement parts.
• Guardian generators utilizing non-Guardian/Generac automatic transfer switches.
S ystems.
• Any Guardian generators used as rental or trailer mounted applications.
• Damage to generator system (including transfer switch) caused by improper installation or costs necessary to correct installation.
not normally exist.
• Costs of normal maintenance, adjustments, installation and start-up.
• teel enclosures that are rusting due to the improper installation, location in a harsh or saltwater environment or scratched where integrity of paint applied is compromised.
• Failures caused by any contaminated fuels, oils, coolants or lack of proper fluid amounts.
Generac engines need periodic part(s) service and replacement to perform well. This warranty will not cover repair when normal use has exhausted the life of a part(s) or engine. quake, windstorm, hail, volcanic eruption, water or flood, tornado or hurricane.
• Damage related to rodent and/or insect infestation.
• Products that are modified or altered in a manner not authorized by Generac in writing. tive part(s).
• Failure due to misapplication.
• Telephone, cellular phone, facsimile, internet access or other communication expenses.
• Expenses related to "customer instruction" or troubleshooting where no manufacturing defect is found.
• Rental equipment used while warranty repairs are being performed.
• Costs incurred for equipment used for removal and/or reinstallation of generator, (i.e.; cranes, hoists, lifts, etc.)
• Overnight freight costs for replacement part(s).
• S tarting batteries, fuses, light bulbs and engine fluids.
THI S WARRANTY I S IN PLACE OF ALL OTHER WARRANTIE S , EXPRE SS ED OR IMPLIED. S PECIFICALLY, GENERAC MAKE S
NO OTHER WARRANTIE S A S TO THE MERCHANTABILITY OR FITNE SS FOR A PARTICULAR PURPO S E. S ome states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
GENERAC' S ONLY LIABILITY S HALL BE THE REPAIR OR REPLACEMENT OF PART( S ) A S S TATED ABOVE. IN NO EVENT
S HALL GENERAC BE LIABLE FOR ANY INCIDENTAL OR CON S EQUENTIAL DAMAGE S , EVEN IF S UCH DAMAGE S ARE A
DIRECT RE S ULT OF GENERAC' S NEGLIGENCE. S ome states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation may not apply to you.
This warranty gives you specific legal rights. You also have other rights from state to state.
GENERAC ® POWER SYSTEMS, INC.
P.O. BOX 297 • WHITEWATER, WI 53190
Part No. 0F9421 Revision L (08/14/07)
Revision (09/01/06)
Printed in U.S.A.
advertisement