INSTALLATION GUIDE
GUIDA ALL’INSTALLAZIONE
INSTALLATIONSANLEITUNG
NOTICE D’INSTALLATION
GUÍA PARA LA INSTALACIÓN
GUIA DE INSTALAÇÃO
D812M
• 230 Vac control unit with inverter
• 230 Vac for three-phase motors with
delta connections
Vers. firmware 2049
1
3
4
5
6 7
D812M
24 25 26
27
12 13 14
15 16 17
18 19 20
8 9 10
11
88:88
1 2
D-MNL0D812M 21-09-2021 - Rev.05
2
21 22 23
28 29 30
IT - Istruzioni originali
2002/95/EC
Signal light 230 Vac
For the connection of
a 12 Vac lamp with or
without flashing card:
See the Page n° 12
230 Vac
automatic switch
10/16A
1
F1 10 A
2
3
4
5
6 7
D812M
TEST
TEST
AUXILIARY
12 ÷ 14 Vac
OUTPUT
N.U.
LED WARNING
N.U.
PEDESTRIAN
COMUN
LED POWER ON
F2
1,6 A
8 9 10 11
24 25 26 27
88:88
S. TEMP.
MF1
N.A.
1 2
Radio Connector
CHIUDE
AP/CH
SICUREZZA
STOP
FOTO
FCC
FCA
MF3
APRE
MF2
MF1
MF2
MF3
Three-phase output for
three-phase motors and
“delta“ connections
N.C.
P3
28 29 30
-
N.C.
*
TX
N.A.
+
N.A.
Connect this point to terminal no. 8 for
the photo-test. Otherwise connect it to the
terminal board no. 10
Photocells
working
in closing
-
N.A.
+
*
P2
FCA
FCC
STOP
PHOTO
SAFETY
OPRN
CLOSE
OP/CL
SAFETY EDGE
COMUN
COMUN
AERIAL
12 13 14 15 16 17 18 19 20 21 22 23
P1
RX
OUT
2
Foreword
This manual provides all the specific information you need to familiarize yourself with
and correctly operate your unit. Read it very
carefully when you purchase the instrument
and consult it whenever you have doubts regarding use and before performing any maintenance operations. Nologo has the right to
modify the product without previous notice.
Environmental protection
measures
Information regarding the environment for
customers within the European Union. European Directive EC 2002/96 requires that units
bearing this symbol on the unit and/or on the
packaging be disposed of separately from undifferentiated urban wastes.
The symbol indicates that the product must
not be disposed of with the normal household
wastes. The owner is responsible for disposing of this product and other electrical and
electronic equipment through specific waste
collection facilities indicated by the government or local public agencies. Correct disposal and recycling help prevent any potentially
negative impact on the environment and human health. To receive more detailed information regarding disposal of your unit, we
recommend that you contact the competent
public agencies, the waste collection.
Piccola legenda
LSO or FCA
Open limit switch
LSC or FCC
Close limit switch
OP/CL
Control to drive the gate
INDEX
Par.
Desricption
1
Scheme of the control unit
Pag.
6
1.1
Description of the electrical connections
8
2
Use and functions of the control panel
9
2.1
State of the control unit
9
2.2
Settings and parameters
9
2.3
Example how to use the MENU and information
2.4
Set up a password for programming
10
2.5
Display the number of cycles and the speed of
the motor
11
2.6
Desactivation of the cycle when the control panel
wil be turned on
11
9
3
Installation of the control unit
12
3.1
Connection of the TENSION and MOTOR
12
3.2
Connection of the lamp 230 Vac or 12 Vac
12
3.3
Pre-flashing time
12
3.4
Connection of the Aerial
13
3.5
STOP connection
13
3.6
Connection of the 8k2 safety edge or N.C.
13
3.7
Connection of the Open and Close limit switch
13
3.8
The connection of PEDESTRIAN or OP/CL
14
3.9
Connection of the PHOTOCELL (only when
closing)
14
3.10
Connection of the PHOTOCELL (activated when
closing) with TEST
15
15
4
ACTIVATE the single OUTPUTS
5
Operating modes and adjustements
16
5.1
Logic of functions
16
5.2
Working time
17
5.3
Set SPEED and ACCELERATION
18
5.4
SCHEME relation between SPEED and FRQUENCY
of the motor
19
in sliding units: control
partial opening
(alternate current)
alternating voltage
(discrete current) direct
voltage
6
RESET of the control unit and restore of factory default settings
20
6.1
Restore factory settings
20
6.2
SAVE SET UP and CHECK of the parameters
20
7
LIST of the FUNCTIONS
21
NC
normally closed
8
Problems
25
NA o NO
normally open
9
Note
26
Isolated
contact
10
Declaration of CE conformity
27
isolated from power supply
PEDESTRIAN
Vac
Vdc
3
Safety precautions
We remind that the installations of gates and automatic doors must be executed from qualified personnels according to the norms. Before installing check the strength and mechanic part of the gate or door,
check that the mechanical stops are suitable to stop immediatelly the cycle of the gate or door even
in case of faulty limit switches or during the manual cycle. For your security we recommend to install
a STOP switch when activated it stops immediatelly the gate. The switch has a N.C. opening in case is
activated (as shown in par. no. 3.5)
Symbols and warning
Dangerous
Damage
This is a warning and if it is
not respec it can provoque
material damage
For safety reasons, protect your
face during the connection
Device under tension
Read carefully the operating
manual
The installation should be
done only from professional
installer
Read carefully this manul before
installation and keep it for the
future
Dangerous for overheated
surface
Network filter for CE norms
FILTER-S12
Option for CE Norms
4
Type of installation
The control board D812M can be used for Industrial rapid doors and for sliding automation with
threephase motors (delta connection) up to 2 Hp with ventilation systems.
Sliding automation
Check the software version and compatibility with the operating manual
When the control unit is turn on, you can see 4 numbers in the display. This is the software number. We
suggest to check this number with the version on the manual. (see pic).
CODE
2049
GUIDA ALL’INSTALLAZIONE
INSTALLATION GUIDE
INSTALLATIONSANLEITUNG
NOTICE D’INSTALLATION
GUÍA PARA LA INSTALACIÓN
GUIA DE INSTALAÇÃO
D812M
Vers. firmware 2049
1
Vers. firmware 1850
Check that the number
on the display correspond
to the firmware
on the operating manual
24 25 26
12 13 14
15 16 17
18 19 20
3
4
5
6 7
27
8 9 10
11
88:88
21 22 23
28 29 30
IT - Istruzioni originali
1
5
2
D812M
1 2
D-MNL0D812M 02-03-2020 - Rev.04
!
• Centrale Inverter 230Vac
• Per motori trifase 230Vac
2002/95/EC
1. Scheme of the control unit
LED POWER ON
Indicates the
network power
WARNING!
We remind you that the safety devices, accessories should be
installed when the control unit is not powered.
1
F1 10 A
2
3
4
5
6 7
LED WARNING
LED POWER ON
F2
1,6 A
D812M
8 9 10 11
24 25 26 27
88:88
S. TEMP.
MF1
1 2
12 13 14 15 16 17 18 19 20 21 22 23
P1 P2 P3 Set the control unit
DIP not used
JP1 Connector for temperature sensor
F1 Fuses protection motor and power: 10A
F2 Fused protection terminal boards (4, 5):
1.6A
Radio Connector
CHIUDE
AP/CH
SICUREZZA
STOP
FOTO
FCC
FCA
MF3
APRE
MF2
P1
P2
P3
28 29 30
MF1-2-3 Three-phases output for 230Vac motors delta
connection
LED WARNING Indicates that the capacitors are still charged, before removing the control unit wait for the LED to
go off.
The red led in the input LSO-LSC-STOP-PHOTO-SAFETY are always lit on
The green led in the inputs OPEN-CLOSE-OP/CL are normally lit off
LSO
LSC
STOP PHOTO
SAFETY OPEN CLOSE OP/CL
WARNING: If the inputs are desactivated from display with S13, S14, S15, S16, S17 red leds are
6
switched off
NETWORK FILTER
1
F1 10 A
2
3
4
5
6 7
F2
1,6 A
LED WARNING
LED POWER ON
Recommended
wiring
diagram
D812M
8 9 10 11
24 25 26 27
88:88
S. TEMP.
MF1
1 2
12 13 14 15 16 17 18 19 20 21 22 23
Radio Connector
CHIUDE
AP/CH
SICUREZZA
STOP
FOTO
FCC
FCA
MF3
APRE
MF2
P1
P2
P3
28 29 30
fILTER RINg
CABLE MOTOR
OUTPUT
1 TURN
ELECTRICAL
gROUND BAR
shielded
CABLE
ENgINE
MOTOR
TERMINAL
BOARD
MOTOR
7
1.1 Description of the electrical connections
In case of long sections of cables (> 20 m) for N.O./N.C. controls (ex. OPEN/CLOSE,
STOP, PEDESTRIAN, etc.), in order to avoid gate malfunctions, it will be necessary
to uncouple the various controls using RELAYS or using our 750T-RELE device.
Earth
230 Vac (N)
1
2
Earth
230 Vac 50Hz, power supply, neutral
230 Vac (L)
3
230 Vac 50Hz, power supply, phase
Signal light
4
Signal light
5
230 Vac Signal light
Max power 40 W
6
For the connection of a 12 Vac lamp or 230Vac signal ligth:
See the par 3.2, page number 12
7
Test 8
Test 9
Out 12 Vac 10
Clean contact for PHOTOCELL TEST
Clean contact for TEST
800mA auxiliary 12÷14 Vac output
Out 12 Vac 11
800mA auxiliary 12÷14 Vac output
LSO
LSC
Stop
Photo A
Safety edge
Open
Close
OP/CL
Costa Common
Common
12
13
14
15
16
17
18
19
20
21
22
Open limit switch
Closing limit switch
STOP
Photo-A closing
N.C. contact (see S17 setting)
OPEN
CLOSE
OPEN / CLOSE input
SAFETY edge - NC / 8k2 contact
Common Services Safeties
Antenna Socks / Common-Services-Safeties
+ Antenna 23
+ Antenna
N.U. 24
N.U. 25
Pedestrian 26
NOT USED
NOT USED
Partial opening / Interlock input
Common 27
Out + 12 Vdc 28
Out - 12 Vdc 29
N.U. 30
Common Services Safeties
Output + 12Vdc 60mA
Output - 12Vdc 60mA
NOT USED
8
2. Use and functions of the control panel
D812M has a display for a simple and fast programming. The menu has been designed for a clear and
fast set up of the working time and the logic of the control unit. You can set up the control unit only
when the door is closed.
2.1 State of the control unit
If no button is pressed, the display shows the position of the automation and the temperature value of
the IGBT heat sink.
P.Fcc
t23c
In this case the door is with closing limit switch
and that the heat temperature is 23°C.
2.2. Settings and parameters
P1
P2 - UP
ACCESS TO ThE fUNCTIONS
Press P1 when the gate is closed
- t- L- E-
P3 - DOWN
P1 - OK
SELECTION Of ThE LETTER ADJUSTMENT
Press button P2 and P3 to select the group and press P1
to confirm.
Set up T
Set up of the Time
programming
Set up L
Set up of the programm
(Speed, power...)
- S- r-
Set up S
Logic of the control unit
Set up R
Activation of the outputs Displays information about the
control unit
Set up E
Back to the standard functions
+
P2 - UP
P3 - DOWN
P2
P1 - OK
SELECTION OF NUMBER SET UP
Press P2 and P3 to select the set up
Press P1 to confirm
P3
gO BACk
To go back to the previous
group press P2 and P3
SELf-RESET
If the control unit is not used for more than one minute, the control unit go out
from the programming saving programs and all changes.
2.3. Example how to use the MENU and information
You can read the information through a display: you can read if it is working properly, the manoeuvre counter
and the sink temperature. Some information can be shown only on the R function (see Chapter no.4)
9
- t-
SYmBOlS
P1
Access to the MENU
Press and
release
P2
DOWN
- L- S- r-
Keep pressed
Release
1st Press
2nd Press
3rd Press
P1 confirm
In the function R if you press P1, you can choose the group function: first select P2 and P3 and then
confirm with P1. Now you can go to the function R07, R08, R09 and R10.
DOWN
r 07
r 08
P2
r 09
P3
UP
r 10
Show the tension
in the capacitors
P1
P1
Show temperature
of the IgBT
P1
P1
P1
P1
Show the resistive
value in the
Safety edge input
(terminal board no.20)
Show the
cycle counters
(point indicated the
thousands)
P1
P1
2.4. Set up a password for programming
To save all changes it is possible to select a password of 4 numbers. To activate this function make as
follow:
•
Password activation:
Press P1, P2 and P3 in the function S32 and then confirm with P1.
10
- t-
P1
Access to the menu
- S-
P2
2nd press
P1 confirm
In the function S if you press P1, you can choose the group function: first select P2, now you can go to
the function S32 and then confirm with P1.
S 01
•
INSERT PASSWORD
Choose the first number with the buttons P2 and
P3 then confirm with P1. The same procedure
applies to the other digits.
0--P2
finished entering the 4 digit. Press P1 to confirm.
To cancel press P1, within 10 seconds. Otherwise, the next access will be required the security
code.
S 32
Pay attention in case you forget
the password it is not possible to
enter in control board as well.
P1 - OK
•
Deactivation of the password
S 33
If you select the fucntion no. S33 you can cancel the password.
Wait 10 seconds to confi rm the operation.
P1 - OK
2.5. Display the number of cycles and the speed of the motor
•
Cycle counter
•
Motor speed
Press P1 when the door is open,
the display shows the SPEED of
the MOTOR
It is possible to show the number of
cycles even pressing P3 (expressed in ten
cycles)
P1
P3
The counter counts up to 999’999 openings. The display shows the first 4 most significant digits.
344.2
If you read these number, it
means that the installation has
made 344200 cycles.
2.6. Desactivation of the cycle when the control panel wil be turned on
When the tension has been interrupted and you turn on the control board again it will make a new
cycle. To exclude this operation make as follow:
P1
DESACTIVATE THE COMPLETE CYCLE Of ThE CYCLE fUNCTION
WhEN ThE TENSION hAS BEEN INTERRUPTED:
keep pressed P1 when turns on.
11
3. Installation of the control unit
3.1. Connection of the TENSION and MOTOR POWER SUPPLY
1
2
3
• The control unit is
equipped with a network
filter
three-phase motor
connection
(no single-phase motor)
We recommend:
N
230 Vac
L
• Install an automatic
switch 10/16A
• Check the network power: 230 Vac: -5% +10%
3.2. Connection of the lamp 230 Vac or 12 Vac
It is shown the connection of a 230V lamp with
or without flashing card.
4
5
6
7
flashing light
230 Vac
It is shown the connection of a 12 Vac lamp with
or without flashing card.
10 11
6
7
flashing light
12 Vac
• Set up of the lighting
In case the lamp has no flashing card, set S12 in 1:
S12
FLASHING
1 - Activated (standard)
0 - Deactivated
• Lamp in pause time
To activate the function lamp in pause TIME, set S05 as shown:
S 05
LAMP IN PAUSE
1 - Activated
0 - Deactivated (standard)
3.3. Pre-flashing time
It is possible to increase or reduce the time of pre-flashing when the door is closed or open, make as
follow with T07 and T08:
t 07
t 08
Pre-flashing time on opening
From 0 to 10 s
Standard value 0.5 s
Pre-flashing time ON CLOSING
From 0 to 10 s
Standard value 2 s
12
3.4. Connection of the Aerial
20 21 22 23
In case the antenna is only a cable of 17cm for
433.92Mhz, connect it to the terminal board no.
23.
3.5. STOP connection
Button: Stop until a new command
Switch: it keep the automation stopped until a
new command
S 15
12 13 14 15 16 17 18 19 20 21 22 23
STOP
1 - Activated (Default)
0 - Deactivated
The connection of the safety devices is prevued
with a button or a normally closed contact
More devices should be connected in parallel.
3.6. Connection of the 8k2 safety edge or N.C. contact
Connect the safety edge at terminal board no. 20
and 21
S 22
S 38
12 13 14 15 16 17 18 19 20 21 22 23
SAFETY EDGE
0 - Deactivated
1 - Activated (Default)
SAFETY EDGE contact
0 - NC contact (normally
closed) (Default)
1 - 8K2 contact
3.7. Connection of the Open and Close limit switch
12 13 14 15 16 17 18 19 20 21 22 23
OPEN
N.C.
S 13
S 14
CLOSE
N.C.
LSO
1 - Activated (Default)
0 - Deactivated
LSC
1 - Activated (Default)
0 - Deactivated
If the input LSO & LSC
is not used, set S13 & S14 in 0
limit switch
13
3.8. The connection of Pedestrian or OP/CL
12 13 14 15 16 17 18 19 20 21 22 23
OP/CL
The connection of a OP/CL command can be
done with a button or with a N.O. contact. When
more devices are available, connect them in parallel.
24 25 26 27
PEDESTRIAN
control
The connection of Pedestrian can be done with
a button or a normally open contact.
It is possible to connect a timer in the terminal board no. 19 and 21 to program the opening time of
the gates.The contact of the timer should be normally open (N.O.) and it should be closed for all the
time the gate is open. If the conncection of opening command is available in the terminal board no 19,
connect it in parallel.
3.9. Connection of the PHOTOCELL (only when closing)
8
9 10 11
12 13 14 15 16 17 18 19 20 21 22 23
The contact of the receiver should be:
- Isolated (isolated from tensions)
- Normally closed
0 Vac
TX
RX
If the PHOTOCELL input is
not used, S16 must be set
to 0
12 Vac
NC
Contact
14
3.10. Connection of the PHOTOCELL (activated when closing) with TEST
8
9 10 11
12 13 14 15 16 17 18 19 20 21 22 23
0 Vac
12Vac
TEST
TX
The TEST of the photo-beam works only
if the photo-beams are installed properly.
The control unit will check all connections
before opening!
RX
In case the photo-beam are not working properlym the control unit will lit on for 5 seconds and the gate is not moving.
If you go back to function without TEST, do
the connection as in Par. 3.9 and put in 0
the S06 and S09 (deactivate the latter only if
there are no other inputs connected to TEST)
12 Vac
NC Contact
To activate the TEST set 1 in the PHOTO-A:
S 09
TEST in PHOTO OUTPUT
1 - Activated
0 - Deactivated (default)
S 06
TEST in the INPUT
safeties
1 - Activated
0 - Deactivated (default)
4. ACTIVATE the single OUTPUTS
D812M can open and close separately and the outputs for lamps and test. This is useful in case you
want to check the single outputs.
- tP2
P1
Access to the functions
SYmBOlS
Press and
release
Keep pressed
Release
In the function R if you press P1, you can choose the subfunction group
function: first select P2 and P3 and then confirm with P1. Now you can go
to the function R01, R02, R03 ...
15
- L- S- r-
P2 - 1° press
P2 - 2° press
P2 - 3° press
P1 confirm
r 01
DOWN
r 02
P2
r 03
r 04
P3
r 05
UP
r 06
r 11
P1
OPEN
with set up
acceleration
P1
P1
CLOSE
with set up
acceleration
P1
OPENINg
with slow down
P1
P1
CLOSINg
with slow down
P1
P1
Activate the LIghT
P1
P1
P1
P1
ACTIVATE
the TEST output
ACTIVATE
the BRAkE output
P1
P1
5. Operating modes and adjustments
5.1. Logic of functions
Imp. N°
S 01
Functions
Description
1
Signal Reverse
By each START command inverts: OPEN-CLOSE
It recloses automatically
2
Automatic
The START command can open or recharge the
pause
time. It recloses automatically
3
Bistable function
4
Stable function with
automatic reclosing
after pause time
5
Signal reverse
Same as function S01 - 1
+ Dead-man function OPEN and CLOSE with “Dead-man function“ function
6
Collective use
Same as function S01 - 2
+ Dead-man function OPEN and CLOSE with “Dead-man function“ function
By each START command it follows: open-stop-closestop-open... It doesn’t recloses automatically
By each START command it opens-stops-closesstops-opens... It recloses automatically after pause
time
16
7
Bistable function
Same as function S01 - 3
+ Dead-man function OPEN and CLOSE with “Dead-man function“ function
S 02
1
Bistable function
with
automatic reclosing
after pause time
+ Dead-man function
Reclosing when
turning on
(Standard value 0)
S 04
1
Photocell contact
(Default 0)
8
S 07
T 18
1
Same as function S01 - 4
OPEN and CLOSE with “Dead-man function“ function
Complete open and close. ONLY when the tension has
been interrupted when the gate is open.
Al passaggio rilevato dalle fotocellule, in apre se S07 è
0 imposta tempo di pausa a 2 s.
Put S04 in 1. When the following function is active on
Close after photocell the passage detected by the photocells on opening,
(Default 0)
the control unit reverses the motor motion and closes.
It is possible to activate the automation opening
Automatic opening
after the set time, from 1 to 99 minutes. (00 If the
after the time set
function is deactivated). Attention, choose a mode of
(Default 00)
operation with automatic reclosing.
5.2. Working time
You can see how to program the control unit with T function:
0 s.
20 s.
T01=20 s.
Total opening time of the automation
Opening
0s.
T04=5s.
5s.
Start of the deceleration in the closing manoeuvre
15s.
20s.
T03=15s.
Start of the deceleration in the opening manoeuvre
SET
DESCRIPTION
UP
Setting the total working time of the opening
From the FCC closing limit switch to the FCA opening limit switch the time increases from 0s ÷ 20s.
Vice versa, from the FCA opening limit switch to
T 01
the FCC closing limit switch, the time decreases
from 20s ÷ 0s (countdown).
it is recommended to set the time T01 with a few extra
seconds of work
17
Values
accepted
step da front 0,1 to
0,1 s
990 s
STANDARD
- seconds -
20,0
T 02
Setting the pedestrian opening time
Setting the starting slowdown position on opening
If we want the gate to slow down the last 5s, just
set 15s on T03 and the gate will start to slow down
from 15s to 20s.
Ex.: T01 = 20s
assumed slowdown time = 5s
T 03
step da front 0,1 to
0,1 s
990 s
3,0
step da front 0,1 to
0,1 s
990 s
15,0
Setting the starting slowdown position on closing
To set the slowdown on closing, the work time
works as a countdown, so if we want the gate to
step da front 0,1 to
slow down the last 5s, just set 5s on T04 and the
0,1 s
990 s
gate will start to slow down from 5s to 0s.
Ex.: T04 = 5s When T01 reaches 5s from 20s, the slowdown
starts.
T 04
5,0
Extra time for limit switch search
T 10
In order to avoid that, due to errors in counting the
operating time, the motor cannot open or close
completely, an extra limit switch search time can
be set. We recommend setting at least 5 s as per
DEFAULT
step da
0,1s
da 0,1
a 990s
5,0 ???
5.3. Set SPEED and ACCELERATION
Are now given the parameters that allow you to set SPEED, ACCELERATION and ABSORPTION:
Set up
Description
Values accepted
Default
L 01
Minimum speed OPENING
from 1 to 50
30
L 02
Minimum speed CLOSING
from 1 to 50
30
L 03
Maximum speed OPENING
from 1 to 120
80
L 04
Maximum speed CLOSING
from 1 to 120
80
L 05
OPENING acceleration
from 1 to 10
5
L 06
CLOSING acceleration
from 1 to 10
5
L 07
OPENING deceleration
from 0 to 10
5
L 08
CLOSING deceleration
from 0 to 10
5
L 09
Motor absorption in case of STOP
Ampere
9,0
L 10
Motor absorption in case of problems
Ampere
12,0
L 11
Not used
from 1 to 70
50
18
5.4. SCHEME relation between SPEED and FREQUENCY of the motor
Here is the relation between speed and frequency of the motor:
Speed
setting
FREQUENCY
[Hz]
1
12
5
14.50
10
17.00
15
19.50
20
22.00
25
24.50
30
27.00
35
29.50
40
32.00
45
34.50
50
37.00
55
39.50
60
42.00
65
44.50
70
47.50
75
49.50
80
52.00
85
54.50
90
57.00
95
59.50
100
62.00
105
64.50
110
67.00
115
69.50
120
72.00
19
6. RESET of the control unit and restore of factory default settings
The control unit allows the parameters to be reset to their DEFAULT value (see par. 6.1), and also allows
you to recall parameters stored specifically for the operation of the sliding gates.
6.1. Restore factory settings
Checking those paramenter of the parameters (Chapter no.7), yuo can look the set up during the RESET
of the control unit. Select the paragraph S18 as shown:
- t-
- S-
P2
2nd press
P1
Access to the
functions
P1 confirm
S 18
WARNINg:
This operation
cancel all settings
P1 - OK
Operation will be cancelled.
Wait 10 seconds, otherwise, if you press
P1 in 10 seconds, this operation will be
cancelled.
For standard values see table at pag no. 20 and following.
6.2. SAVE SET UP and CHECK of the PARAMETERS
D812M has 2 memory slots saving all manually set up and you can check it again. See how to check
the set up with functions S23, S24, S25, S26. Once all parameters are set up, it is possible to change.
Thanks of the 2 memory slots, it is possible to save and check 2 differents set up.
•
MEMORIA 1 (slot 1)
S 23
S 25
Press P1
Save all set up
MEMORY 1
Press P1
Charge set up of
MEMORY 1
•
MEMORIA 2 (slot 2)
S 24
S 26
20
Press P1
Save all set up
MEMORY 2
Press P1
Charge set up of
MEMORY 2
7. LIST of the FUNCTIONS D812M
Group functions “T”
SET
DESCRIPTION
UP
step from
0,1 s
step from
0,1 s
step from
0,1 s
step from
0,1 s
step from
0,5 s
step from
0,5 s
step from
0,5 s
step from
0,5 s
VALUES STANDARD
MEMO
ACCEPTED - seconds from 0,1 to
20,0 s 990 s
from 0,1 to
3,0 s
990 s
from 0,1 to
15,0 s
990 s
from 0,1 to
5,0 s
990 s
from 2 to
2,0 s
127.5 s
from 2 to
5,0 s
127.5 s
from 2 to
0,5 s
127 s
from 2 to
2,0 s
127 s
step from
0,1 s
from 0,1 to
990 s
5,0 s
Stop the detection of input of the photo-beam.
Not considered if S03 is set 1
step from
0,1 s
from 0,1 to
990 s
0,5 s
Time to stp to detecte the SAFETY EDEGE INPUT
(terminal board. 16)
step from
0,5 s
from 0,1 to
2s
1,0 s
step from
0,1 s
from 0 to
2s
0,2 s
step from
0,1 s
step from
0,1 s
step from
0,1 s
from 0 to
2s
from 0 to
3s
from 0 to
3s
T 01 Complete opening cycle time
T 02 Partial opening time
Setting the starting slowdown position on
opening
Setting the starting slowdown position on
T 04
closing
T 03
T 05 Automatic closing time
T 06 Pause time for PARTIAL OPENING
T 07 PRE-LIGHTING time by opening
T 08 PRE-LIGHTING time by closing
T 09 (Not used)
T 10 Extra time for limit switch search
T 11
T 12
Time block the check of the absorption of the
T 13 motor
when the gate is opening or closing
Pause time of reverse of the direction of the
T 14
motor
T 15 STOP of the motor after detecting the LSO
Time of delay of the motor when detecting the
T 16
LSC
Lead time on the release of the brake before
T 17 starting
the engine (in tenths of seconds)
T 18
Automatic opening after the time set (00 If the function is deactivated)
step from 1
min
21
0,1 s
0s
0s
from 0 to 20
12
from 00 to
99 min
00
Group functions “L”
SET
UP
VALUES
ACCEPTED
DESCRIPTION
STANDARD
- seconds -
L 01
Minimum opening speed
from 1 to 50
30
L 02
Minimum closing speed
from 1 to 50
30
L 03
Maximum opening speed
from 1 to 120
80
L 04
Maximum closing speed
from 1 to 120
80
L 05
Opening acceleration
from 1 a 10
5
L 06
Closing acceleration
from 1 a 10
5
L 07
Opening deceleration
from 0 to 10
5
L 08
Closing deceleration
from 0 to 10
5
L 09
Maximum absorption of the motor to STOP the door in Ampere from 0,5 to 13
9,0
L 10
Maximum absorption of the motor in case of trouble in Ampere from 0,5 to 13
12,0
L 11
Power of the output BRAKE
from 0 to 70
50
Group functions “S”
SET
DESCRIPTION
UP
VALUES ACCEPTED
S 01 Logic of the motor:
STANDARD MEMO
from 1 to 8
4
Opening-closing cycle when the door is
not closed
0 Off - 1 On
0
Deactivate the input PHOTO A
S 03 after intervention of the slow down LSC
0 Deactivated - 1 Activated
0
0 Off - 1 On
0
1 - Fast reverse
2 - Collective use
3 - Bistable function
4 - Bistable function with automatic
reclosing
5 - Fast reversing and “Dead’s man“
function
6 - Collective use and “Dead’s man
function
7 - Bistable funciton and “Dead’s man“
function
8 - Bistable function with automatic
reclosing
and “Dead’s man“ function
S 02
S 04 Photocell contact activation
22
S 05 Signal light in pause time
0 Off - 1 On
0
S 06 Activation TEST in the safeties inputs
0 Off - 1 On
0
S 07 Close after photocell
0 Off - 1 On
0
S 08 NOT USED
Activate the TEST in the input
S 09
PHOTOCELL
Activate the Test in the SAFETY EDGE
S 10
input
leave on 2
2
0 Off - 1 On
0
0 Off - 1 On
0
S 11 Activate the TEST in the input STOP
0 Off - 1 On
0
0 Off - 1 On
1
S 13 Activate the input LSO
0 Off - 1 On
1
S 14 Activate the input LSC
0 Off - 1 On
1
S 15 Activate STOP input
0 Off - 1 On
1
S 16 Activate the PHOTOCELL by closing
0 Off - 1 On
1
S 17 Security
0 Off - 1 On
0
S 12
S 18
Activate the flashing in the signal light
input
Reset of the control unit at factory’s
settings
S 19 NOT USED
S 20
Activated the input SWITCH for
opening slowing down
0 Off - 1 On
0
S 21
Activate the input swicht for CLOSING slowing down
0 Off - 1 On
0
S 22
Activate the input for SAFETY EDGE
(terminal 20-21)
0 Deactivated - 1 Activated
1
S 23 Copy set up of memory 1
S 24 Copy set up of memory 2
S 25 Charge the set up of memory 1
S 26 Charge the set up of memory 2
23
S 27 Charge the standard set up 1
S 28 Charge the standard set up 2
S 29 Charge the standard set up 3
S 30 Charge the standard set up 4
S 31 Charge the standard set up 5
Activate of a password to set up with a
S 32 code of 4 numbers. Put the new code
and let the time goes.
You can deactive the access of the set
S 33 up
with a password
Activation of the security closing
S 34
after intervention of the edge (20-21)
0 deactivated - 1 activated
0
leave on 0
0
S 35 NOT USED
S 36 NOT USED
leave on 0
0
Integrated electric brake
S 37 (activated for 2 seconds after motor
stopping)
1= light acceleration
4 = heavy acceleration
5=neither acceleration nor
braking
6= light braking
9= heavy braking
4
Safety edge - contact terminal board
no.20-21
0: N.C. contact - 1: 8K2 contact
0
0 deactivated - 1 activated
0
S 38
S 39 Opening / Closing in case of emergency
Group functions “R”
SET UP DESCRIPTION
R 01
Activate Opening until P1 has been released with acceleration set up
R 02
Activate CLOSING until P1 has been released with acceleration set up
R 03
Activate the OPENING until P1 has been released with slow down acceleration
R 04
Activate CLOSING until P1 has been released with slow down set up
R 05
Activate LIGHT/SIGNAL LIGHTH until P1 has been released
R 06
Activate TEST output until P1 has been released
R 07
Display the tension of the capacitors until P1 has been released
R 08
Display temperature of the IGBT until P1 has been released
R 09
R 10
Display the resistive value in the SAFETY EDGE input (terminal board no.20) until P1 has
been released
Display the number of cycles number of cycles until P1 has been released (point indicated
the thousands)
24
R 11
Activate the brake output
8. Problems
Here are listed some functions issue indicated in the display. You can see the causes and the procedure
to solve the issue..
PROBLEM
Er01
Er02
Er03
Er04
DESCRIPTION
SOLUTION
OVERVOLT on bus
There is a tension of 240 Vac in the capacitors. Check the network tension.
OVERCURRENT in the MOTOR
The overcurrent level of programm L10
has been exceeded. If necessary increase the
value.
Tension in the capacitors too
low
The tension in the capacitors is too
low. Check the network tension.
Absorption at 1.5 A
when the motor is not working
The control unit has an absorption of
more than 1,5A even if the motor is not
working. Check the accessories and
the motor.
Er05
Er06
Security code not correct
Code not correct.
Try a new code.
Exceeded temperature
of the spendthrift IGBT
Wait until the temperature in the
spendthrift is reduced.
Er07 Er17
Er27 Er67
Er77
Signal error of the encoder
Check the encoder connections
N.C. contact - Safety edge open
Check terminals 20-21
(see paragraph 3.6)
CO S.2
25
09
Note
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
.................................................................................................
26
10
Declaration of CE conformity
(according to EC Directive 2006/42, Attachment II, part 1, ses. A)
The undersigned Loris Virgilio Danieli,
Administrator
DECLARES THAT:
Company:TAU S.r.l.
Via Enrico Fermi, 43 Address:
36066 Sandrigo (VI) Italia
Product’s name:
D812M
Centrale Inverter 230Vac
THE PRODUCT COMPLIES
with what is outlined in the European Community directive:
2006/42/CE
EC DIRECTIVE 2006/42 ISSUED BY THE EUROPEAN PARLIAMENT AND
COUNCIL on may 17, 2006 harmonizing the legislation of the member countries
regarding machinery.
Reference: Attachment II, part 1, ses. A (EC Declaration of Conformity issued by the manufacturer).
THE PRODUCT COMPLIES
with what is outlined in the European Community directives:
2014/35/CE
DIRECTIVE 2014/35/EU OF THE EUROPEAN PARLIAMENT AND OF THE
COUNCIL of 26 February 2014 on the harmonisation of the laws of the Member
States relating to the making available on the market of electrical equipment
designed for use within certain voltage limits.
Reference to harmonized standards: EN 60335-1
2014/30/CE
Reference to harmonized standards: EN 61000-6-2
DIRECTIVE 2014/30/EU OF THE EUROPEAN PARLIAMENT AND OF THE
COUNCIL of 26 February 2014 on the harmonisation of the laws of the Member
States relating to electromagnetic compatibility.
EN 61000-6-3
with the essential requirements of article 3 of the following
European Community Directive, for the use for which the
product is designede
IL PRODOTTO E’ CONFORME
2014/53/CE (RED)
DIRECTIVE 2014/53/EU OF THE EUROPEAN PARLIAMENT AND OF THE
COUNCIL of 16 April 2014 on the harmonisation of the laws of the Member
States relating to the making available on the market of radio equipment
Reference to harmonized standards: ETSI EN 300 220-3
ETSI EN 301 489-1
ETSI EN 301 489-3
The directive 2006/42/CE remind that it is not allowed the function of the product until the machine, for which
the product is included, is not indentify and declared conformed to the 2006/42/CE directive.
Sandrigo, 01/06/2017
The Administrator
Loris Virgilio Danieli
TAU S.r.l.
Via Enrico Fermi, 43
36066 Sandrigo (VI) Italia
Tel +39 0444 750190
Fax +39 0444 750376
[email protected]
www.tauitalia.com
27
Via Enrico Fermi, 43 - 36066 Sandrigo (VI) - Italy
Tel +39 0444 750190 - Fax +39 0444 750376
[email protected] - www.tauitalia.com