TCNet Boiler Controller

User and Service Manual

Safety Instructions

Caution! Schock Hazard!

Risk of electrical schock which may cause serious injuries or death. Please disconnect the mains before servicing this equipment.

Caution! Hot Surfaces!

The boiler assembly and/or the temperature sensors may be extremely hot!

Caution! Moving Parts!

Watch your hands while servicing the moving parts such as auger and grate cleaning assembly which may cause serious injuries.

Caution!

This device is intended to be professionally installed. Incorrect installation and/or operating parameters may cause dangerous conditions.

Please do not expose the control panel directly to sunlight.

Please avoid any liquid contacts to control panel and/or cable assemblies.

2

TCNet Boiler Controller

(This page is intentionally left blank)

User and Service Manual

3

TCNet Boiler Controller

User and Service Manual

Table of Contents

Safety Instructions ................................................................................................................................... 2

Overview to Control Panel ...................................................................................................................... 5

Quick Reference ...................................................................................................................................... 6

Starting and Stopping Your Boiler ....................................................................................................... 6

Setting up The Temperature of Boiler or Utility Water ....................................................................... 6

Operation Menu ...................................................................................................................................... 7

Menu Structure ....................................................................................................................................... 9

User Preferences Menu ........................................................................................................................... 9

Operation Mode ................................................................................................................................ 10

Weather Compensation .................................................................................................................... 10

Day-Night Compensation .................................................................................................................. 11

Date-Time .......................................................................................................................................... 12

Week Timer ....................................................................................................................................... 12

Internet Connectivity ............................................................................................................................. 13

The Status Page ................................................................................................................................. 14

Adjust the Temperatures and Operation Mode From Internet ........................................................ 15

Setting up The Week Timer from Internet ........................................................................................ 16

Changing the Network Settings ......................................................................................................... 17

Turning On and Turning Off your Boiler From Internet .................................................................... 18

Clearing Errors From Internet ........................................................................................................... 18

Service Menu ......................................................................................................................................... 19

Boiler Setup ....................................................................................................................................... 20

Combustion Data ............................................................................................................................... 20

Ignition Data ...................................................................................................................................... 23

Circulation Data ................................................................................................................................. 23

Network Status .................................................................................................................................. 24

Pellet Refill ......................................................................................................................................... 24

Digital Inputs ..................................................................................................................................... 25

Analog Inputs ..................................................................................................................................... 25

Test Devices ....................................................................................................................................... 25

Factory Defaults ................................................................................................................................ 25

Error Log ............................................................................................................................................ 25

4

TCNet Boiler Controller

Overview to Control Panel

User and Service Manual

1. Power key.

2. Input key.

3. Menu navigation key.

4. Menu navigation key.

5. Decrease parameter key.

6. Increase parameter key.

5

TCNet Boiler Controller

User and Service Manual

Quick Reference

Starting and Stopping Your Boiler

Please hold the power key to either run or stop your boiler.

The power state will be highlighted when you press the power key.

Setting up The Temperature of Boiler or Utility Water

Press the Input key to enter the Temperature Setup menu.

Press navigation keys to highlight boiler temperature or utility water temperature.

Press adjust keys to change the temperature.

To return operation menu, navigate to “<Return” with navigation keys and press Input key.

To jump User Preferences Menu, navigate to Next> and pres input key.

6

TCNet Boiler Controller

Operation Menu

User and Service Manual

The operation menu indicates current process values of your boiler. Large LCD display allows the control panel to show almos all temperatures measured by sensors and the calculated output power.

1. Power state: Indicates the current power state of your boiler. When it set to RUN, boiler will opeate if any heat demand. When it set to STOP, boiler will complete the current cycle of process and jump to deflating and cleaning sequences immediately.

2. Flue Temperature: Indicates the flue gas temperature.

3. Output Power: Indicates the calculated output power of the boiler.

4. Status display: Indicates the current process of your boiler

- Ready/Idle: No operation or the boiler reached the set point temperature

- Flame check: In this state, boiler checks the sensor if any flame exists on the grate.

- Ignition: Boiler is performing ignition cycle.

- Heating: Boiler is in normal burning cycle.

- Cleaning: Boiler is either deflating the flame or cleaning the grate and internal flue gas pipes.

5. Grate Display: In this are of screen, control panel shows the curent state of your boiler.

Idle/No operation

Flame check

Ignition Cycle

Boiler is operating at 20% or less of its rated power.

Boiler is operating at 20%-40% of its rated power.

Boiler is operating at 40%-60% of its rated power.

Boiler is operating at 60%-80% of its rated power.

7

TCNet Boiler Controller

User and Service Manual

Boiler is operating at 80%-100% of its rated power.

Boiler is either performing the deflating sequence or grate cleaning sequence.

6. Device Icons:

Auger is operating.

Blower is operating.

External fuel refilling system is operating.

I Ignition heater is operating.

C Cleaning mechanism is operating.

7. Utility water circuit status display:

This section indicates the measured temperature of the utility water circuit. icon indicates that the circulation pump of the utility water circuit is operating.

8. Building heating circuit status display:

This section indicates the building heating circuit’s data as same as utility water circuit.

9. System clock in 24-hour format.

10. Measured weather temperature.

8

TCNet Boiler Controller

User and Service Manual

Menu Structure

TCNet controller has three menu schemes for quick setup, user preferences and the service settings.

The most common settings are grouped together.

1. Temperature

Setup: Basic temperature adjust of your boiler

2. User Preferences:

Operation mode, timer and temperature compensation options

3. Service Settings:

Advanced settings of your boiler. This settings are intended to be adjusted by a service engineer.

User Preferences Menu

To enter the User Preferences menu, Press the Input key and navigate to

“Next>” with navigation keys than press the input key again.

User Preferences menu has five settings.

9

TCNet Boiler Controller

User and Service Manual

Operation Mode

To change the operation mode press

adjust keys. Navigate to

<Return with navigation keys and press Input key to return the

User Preferences menu.

There are three operation modes of your boiler.

Mode Building Heating

1 ON

Utility Water

ON

2

3

OFF

ON

ON

OFF

Both circulation pumps will operate according to heat demand.

Only the utility water circuit’s circulation pump will operate. (Summer mode)

Only the building heating circuit’s circulation pump will operate. (Utility water is not necessary or not available in the boiler system)

Weather Compensation

Your boiler is able to adjust the temperature setpoint according to the weather temperature.

To setup the weather compensation, first navigate to temperature range with navigation keys and select the temperature range with

adjust keys. After selecting the temperature range, navigate to

Correction value and set the offset temperature of your boiler for this temperature range. To adjust another temperature range, navigate back to temperature range with

navigation keys and select the range that you want. After all settings have been completed, navigate to <Return and press Input key to return to the User Preferences Menu.

There are eleven temperature ranges for adjusting.

Range

-20 … -17:C

-16 … -13:C

-12 … -9:C

Adjust

-/+ 10:C

-/+ 10:C

-/+ 10:C

10

TCNet Boiler Controller

User and Service Manual

-8 … -5:C

-4 … -1:C

0 … 3:C

4 … 7:C

8 … 11:C

12 … 15:C

16 … 19:C

>20 :C

-/+ 10:C

-/+ 10:C

-/+ 10:C

-/+ 10:C

-/+ 10:C

-/+ 10:C

-/+ 10:C

-/+ 10:C

If the compensated temperature setpoint exceeds the temperature limits of the boiler, controller will increase or decrease the setpoint in between minimum and maximum temperature limits.

Day-Night Compensation

Your boiler is olso able to adjust the temperature setpoint according to different time slices in a day.

To setup the day-night compensation, first navigate to time slice with

navigation keys and select the time slice with adjust keys.

After selecting the time slice, navigate to Correction value and set the offset temperature of your boiler for this time slice. To adjust another time slice, navigate back to time slice with navigation keys and select the time slice that you want. After all settings have been completed, navigate to <Return and press Input key to return to the User Preferences Menu.

There are eight time slices to adjust.

00:00 – 02:59

03:00 – 05:59

06:00 – 08:59

09:00 – 11:59

12:00 – 14:59

15:00 – 17:59

18:00 – 20:59

21:00 – 23:59

If the compensated temperature setpoint exceeds the temperature limits of the boiler, controller will increase or decrease the setpoint in between minimum and maximum temperature limits.

11

TCNet Boiler Controller

User and Service Manual

Date-Time

The controller panel has a realtime clock calendar.

To adjust the system time and date, navigate to hour, minute, date, month, year or day of week with

navigation keys. Press adjust keys to change. Controller accepts 24-hour hh:mm time format and dd/mm/yyyy date format.

Incorrect date setting may halt the clock (i.e. 30/02/2011).

The realtime clock has a backup battery at the back side of the control panel. If your boiler resets the date-time settings after AC mains power loss, replace the backup battery. The backup battery is

CR2032 type lithium battery. Please insert the battery with correct polarity. The overal life of backup battery is about two years.

The chemistry of the battery may be harmful to the environment. Please dispose the old battery properly according to the instructions on the battery’s package.

Week Timer

The week timer allows you to set three programs for each day of the week to turn on or turn off your boiler.

To set up the week timer, first select the desired day with adjust keys than navigate to ON/OFF with navigation keys. If you select

OFF, all of three programs will be ignored by the controller for that day.

Select the start-up and stop times adjust the hour and minute with

<Return with

Menu. with navigation keys and

adjust keys. After all programs are completed, navigate to

navigation keys and press Input key to return to the User Preferences

12

TCNet Boiler Controller

User and Service Manual

Internet Connectivity

The controller has an onboard Ethernet port to directly connect to the Internet or your local area network.

The LAN connector of the boiler is depends on the boiler model. Please refer to the instruction manual of your boiler fort he location of the LAN connector.

Use a straight patched network cable for connecting your boiler to your DSL modem, router or computer.

The default IP address of your boiler is 192.168.1.127. If you have changed the IP address or enabled the DHCP service, you may learn the controllers IP address from Service>Network Status menu.

To connect the control panel, your computer or device which has internet connectivity must be in the same subnet.

Open your Internet browser software and type the IP address of your boiler.

If the network connection is OK, you should see the login window. The username of the boiler is

admin” and the password is “boiler”

13

TCNet Boiler Controller

After login, you should see the status page of the boiler

User and Service Manual

The Status Page

All measured temperatures and the device status are shown on this page. CPU load indicates the current utilization of the control panel’s processor.

14

TCNet Boiler Controller

User and Service Manual

Adjust the Temperatures and Operation Mode From Internet

Click the “Temperature Setup” on the menu box.

Adjust the temperatures and click “Submit” button.

If you don’t want to make any adjustments, click “Administration” from the menu and click the “Save

Settings to FLASH” button to make adjustmens permanent.

15

TCNet Boiler Controller

Setting up The Week Timer from Internet

Click the “Week Timer” on menu box.

User and Service Manual

Set up your desired start up and shut down times for each day.

If you don’t want to make any adjustments, click “Administration” from the menu and click the “Save

Settings to FLASH” button to make adjustmens permanent.

16

TCNet Boiler Controller

Changing the Network Settings

Click the “Network Configuration” on menu box.

User and Service Manual

Make all required changes on network configuration and click “Save Config” button.

Please note that the controller should reboot after changing the network settings and perform the

AC Power loss sequences at startup.

17

TCNet Boiler Controller

Turning On and Turning Off your Boiler From Internet

User and Service Manual

Click “Administration” on menu box.

Click “Turn On Boiler” button to turn on your boiler.

Click “Turn Off Boiler” button to turn of your boiler.

Clearing Errors From Internet

If you see any error messages on the status page, you may clear the error by clicking the “Clear

Errors” button on the Administration page.

18

TCNet Boiler Controller

User and Service Manual

Service Menu

Caution! This settings are intended to be adjusted by a well trained service technician or a service engineer. Incorrect settings may cause dangerous conditions.

Service Menu Structure

To enter the Service menu, navigate to Service> with and press Input key.

navigation keys

19

TCNet Boiler Controller

Boiler Setup

Max. Power kW

Min. Power kW

Feed rate gr/min

Efficiency %

Max auger Curr. A

Curr. Detect latency sec

Grate Open T s

Combustion Data

Fuel Energy kW/kg

Modulator

91

0.5

2

190

25

5

380

4.88

PID

Mod. Delta :C 10

Hysteresis :C 2

Feed Period :C 15

User and Service Manual

The maximum power of the boiler

The minimum power of the boiler

The pellet feed amount for a minute of the auger or other fuel feeding system.

The total efficiency of the boiler

The maximum allowable current drawn by the auger excitation motor.

The time delay for the auger current limit alarm

The run time of the grate open/close actuator.

The energy of a kilogram of used pellet. (Please refer to the information on your pellet package)

The power regulation metod of the boiler. There are three modes for power regulation.

(PID [Graph1], 5STEP [Graph2] or fixed power [Graph3])

The power regulation to reduce the power of the boiler.

Eg. : The boiler temp. 50 C

Mod.Delta : 10 C

Boiler begins to slow down when it is reached to 40 C.

The temperature overlimit.

E.g :

The temp.of the boiler is : 50 C

If the hysteresis is set 2 C. the boiler operates between

50-51 C. If it exceeds the 51 C

,it deflates the flame.

The fuel consumption to reach the capacity :

E.g : If the feed period is set 15 it feeds 5 gr in every 15 sec.

If the feed period is set 20 it feeds 7 gr.

If the feed period is set 25.

It feeds 9 gr.fuel in every 25 sec

20

TCNet Boiler Controller

User and Service Manual

Power and Fan speed settings for 5STEP modulation or Fixed power.

Mod1

Mod2

Mod3

Mod4

Mod5

Exh. Limit :C

5kW

10kW

15kW

20kW

25kW

150

Fan:

Fan:

Fan:

Fan:

Fan:

33

37

40

43

46

Maximum allowable flue temperature. In case of flue gases exceed the limit, controller will reduce the power to regulate the flue gas temperature.

Graph 1 PID Modulation

21

TCNet Boiler Controller

User and Service Manual

Graph 2 5 Step Modulation

Graph 3 Fixed Power Regulation

Tuning the PID modulation:

- If your boiler never reaches the setpoint, Increase the Mod1 Power level.

- If your boiler exceeds the setpoint more than the hysteresis value, Decrease the Mod1

Power Level.

- If your heating circuit(s) power demand is too low for the boiler (for example only utility water heating in summer) you may decrease the Mod5 Power level to avoid overshoot the temperature setpoint.

22

TCNet Boiler Controller

User and Service Manual

Ignition Data

Feed Time sec

Timeout min

Retries

Burn. Detect Temp :C

Burn. Detect Delta :C

Auger Filling min

First run

Fan Speed

7

3

0

50

60

10

3

100

Graph 4 Feed Period

[Graph5]

Circulation Data

Heating Circuit

Threshold

Graph 5 Burning Detection and Deflating Cycle

35

23

TCNet Boiler Controller

Hysteresis

Util. Water Circuit

Threshold

Hysteresis

Network Status

IP Address

192.168.1.127

Subnet Mask

255.255.255.0

Default Gateway

192.168.1.1

Pellet Refill

Machine Type

Run duration (minutes)

2

35

2

User and Service Manual

The IP address of the controller

The subnet mask of the controller

The default gateway address (DSL modem router etc.)

None-> Auger -> Suction

10

The type of the refill system.

The run time of the refill system in case of detection of low pellet level from the bunker.

24

TCNet Boiler Controller

User and Service Manual

Digital Inputs

IN0: OFF

IN1: OFF

IN2: OFF

IN3: OFF

IN4:OFF

IN5: OFF

IN6: OFF

IN7: OFF

The input signals of the controller.

OFF : No signal / Open

ON: Signal / Close

Analog Inputs

T3 (boiler temp. Sensor) LM (Lambda sensor)*

T1 (Util. Water temp. Sensor) PC (Photocell)*

T2 (Weather temp. Sensor)

TC (Flue temp. Sensor)

The measured values of the

Analog-to-digital converter of the controller

(*) Lambda sensor and photocell may not be implemented on your system.

Test Devices

Warning! This menu is only for testing the outputs of the boiler for a short time. Leaving the boiler in Test Devices menu may cause dangerous conditions.

IGN

PUMPH

PUMPU

AUGER

CLEAN

REFILL

FAN1

FAN2

FAN3

Factory Defaults

Restores all parameters to the Factory defaults.

Error Log

Controller stores the last five errors.

Select the device with navigation keys to test.

+ adjust key: RUN

_ adjust key: STOP

Record format is DD/MM/YYYY HH:MM – Error code

25