MONITOR HEATING SYSTEMS
Service Manual
MONITOR 22 MONITOR 41
The information contained herein is proprietary to Monitor Products, Inc. shall not be disclosed, duplicated, nor otherwise copied in whole or part for any other purpose without express written permission of the Legal
Department of Monitor Products, Inc. This data is issued to authorized Monitor Servicing Personnel for guidance in the installation and maintenance of the subject product and is intended for use by authorized Monitor service personnel only. Further. Monitor Products, Inc. reserves the right to make improvements and corrections and to alter apecifications of products described herein, at any time without prior notice.
P.O.BOX3408
PRINCETON, NEW JERSEY 08543
MONITOR HEATING SYSTEMS
Table of Contents
Section 1: Description Page 1-7
1-1 Introduction; 1-2 Physical Specifications; 1-3 Functional Description; 1-4 Description; 1-5 Spill Tray; 1-6 Heater Cabinet; 1-7 Combustion System; 1-8 Combustion Ghamber; 1-9 Burner Pot; 1-10 Combustion Ring Assembly; 1-11 Burner Cap; 1-12 FlameSensor; 1-13 Igniter;
1-14 Combustion Air System; 1-15 Flue Pipe; 1-16 Combustion Blower;
1-17 Heat Exchanger; 1-18 Air Circulation Fan; 1-19 Air Pressure
Switch; 1-20 Fuel Delivery System; 1-21 External Fuel Tank; 1-22
Fusible Link Valve; 1-23 Fuel Constant Level Valve; 1-24 Solenoid
Pump; 1-25 Electrical System; 1-26 Microprocessor; 1-27 Temperature Sensor; 1-28 Safety Mechanism; 1-29 Cloth Covered Exhaust
Pipe; 1-30 Air Circulation Fan Guard; 1-31 Fuse; 1-32 Overheat
Protector Switches ; 1-33 Slide Selector For the Reset Temp.
Section 2: Installation Page 9—21
2-1 Introduction; 2-2 Physical Placement of Heater; 2-3 Drilling
Requirements; 2-4 Power Requirements; 2-5 Fuel Tank Requirements; 2-6 Temperature Sensor Wiring Requirements; 2-7 Building
Codes: 2-8 Un-packing; 2-9 Heater Installation; 2-10 Installing an
Extension Kit; 2-11 Typical Monitor Lifter Pump Installations; 2-12
Uses for the Elbow Adapter Kit; 2-13 Fuel Tank Installation; 2-14
Heater Installation
Section 3: Operation Page 22—33
3-1 Introduction; 3-2 Operating Specifications; 3-3 Operating Controls and Indicators; 3-4 Pre-operation Check List; 3-5 Operation; 3-6
Manual Heater Operation; 3-7 Automatic Heater Operation; 3-8
Reprogramming the Monitor Heater; 3-9 Heat Sensor; 3-10 Monitor
Shutdown; 3-11 Out of Fuel; 3-12 Recovery from a Power Failure; 3-13
Recovery from Overheat Condition; 3-14 Recovery from Blown Fuse
3-15 Operation Control system
Section 4: Maintenance Page 34-37
4-1 Introduction; 4-2 Periodic Maintenance; 4-3 Inspect Exhaust Air
Lines; 4-4 Verify Igniter Operation: 4-5 Clean Fuel Constant Level
Valve Filter; 4-6 Cleaning Fusible Link Valve Intake Fitting onM-22;
4-7 Corrective Maintenance; 4-8 Replacement of Fuses; 4-9 Fuel
Contamination
MONITOR HEATING SYSTEMS
Table of Contents
Section 5: Servicing Page 38-40
5-1 Introduction; 5-2 Measurerment of Fuel Flow rate; 5-3 Removal of
Water Deposits and Contaminants from Fuel Constant Level Valve and Fuel Lines; 5-4 Cleaning the Burn Chamber & Burner Pot: 5-5
Cleaning the Fuel Inlet
Section 6: Troubleshooting Page 41—54
Resistance Values component Voltage Readings
Test Point Voltage
Troubleshooting Diagrams (Mechanical)
Troubleshooting Diagrams (Electrical)
Indication of Failure mode
Section 7: Electrical System Page 55-57
Schematic
Monitor 41 Printed Circuit Board Wiring Diagram
Monitor 22 Printed Circuit Board Wiring Diagram
MONITOR HEATING SYSTEMS
Table of Contents
Section 1: Description Page 1-7
1-1 Introduction; 1-2 Physical Specifications; 1-3 Functional Description; 1-4 Description; 1-5 Spill Tray; 1-6 Heater Cabinet; 1-7 Combustion System; 1-8 Combustion Chamber; 1-9 Burner Pot; 1-10 Combustion Ring Assembly; 1-11 Burner Cap; 1-12 FlameSensor; 1-13 Igniter;
1-14 Combustion Air System; 1-15 Flue Pipe; 1-16 Combustion Blower;
1-17 Heat Exchanger; 1-18 Air Circulation Fan; 1-19 Air Pressure
Switch; 1-20 Fuel Delivery System; 1-21 External Fuel Tank; 1-22
Fusible Link Valve; 1-23 Fuel Constant Level Valve; 1-24 Solenoid
Pump; 1-25 Electrical System; 1-26 Microprocessor; 1-27 Temperature Sensor; 1-28 Safety Mechanism; 1-29 Cloth Covered Exhaust
Pipe; 1-30 Air Circulation Fan Guard; 1-31 Fuse; 1-32 Overheat
Protector Switches : 1-33 Slide Selector For the Reset Temp.
Section 2: Installation Page 9—21
2-1 Introduction; 2-2 Physical Placement of Heater; 2-3 Drilling
Requirements; 2-4 Power Requirements; 2-5 Fuel Tank Requirements; 2-6 Temperature Sensor Wiring Requirements; 2-7 Building
Codes; 2-8 Un-packing; 2-9 Heater Installation; 2-10 Installing an
Extension Kit; 2-11 Typical Monitor Lifter Pump Installations; 2-12
Uses for the Elbow Adapter Kit; 2-13 Fuel Tank Installation; 2-14
Heater Installation
Section 3: Operation Page 22~33
3-1 Introduction; 3-2 Operating Specifications; 3-3 Operating Controls and Indicators; 3-4 Pre-operation Check List; 3-5 Operation; 3-6
Manual Heater Operation; 3-7 Automatic Heater Operation; 3-8
Reprogramming the Monitor Heater; 3-9 Heat Sensor; 3-10 Monitor
Shutdown; 3-11 Out of Fuel; 3-12 Recovery from a Power Failure; 3-13
Recovery from Overheat Condition; 3-14 Recovery from Blown Fuse
3-15 Operation Control system
Section 4: Maintenance Page 34-37
4-1 Introduction; 4-2 Periodic Maintenance; 4-3 Inspect Exhaust Air
Lines; 4-4 Verify Igniter Operation; 4-5 Clean Fuel Constant Level
Valve Filter; 4-6 Cleaning Fusible Link Valve Intake Fitting on M-22;
4-7 Corrective Maintenance; 4-8 Replacement of Fuses; 4-9 Fuel
Contamination
MONITOR HEATING SYSTEMS
Section 1: Description
1-1 INTRODUCTION
The Monitor Heating System represents "state of the art" technology and, although the heater is sophisticated, it is simple to operate, takes little time to maintain and requires minimum servicing.
The Monitor is a totally integrated heater consisting of a housing(cabinet),a combustion system, an air circulation system, a fuel delivery system and micro-computer system.
Redundant safety devices are included in the heater's design to protect the user from injury and the heater from damage.
This section describes the heaters and their components.
Since a number of components have multiple functions, a component may be described more than once.
1-2 PHYSICAL SPECIFICATIONS
Listed below, are the physical specifications that apply to the Monitors:
Monitor 41:
Height:26.6' (67.5cm)
Width:28.7" (73cm)
Depth:13.8" (35cm)
Weight:82 Ibs (37kg)
Flue Pipe Hole:2' j "(65mm)diameter
Monitor 22:
Height:25.6" (65cm)
Width:20.9" (53cm
Depth:12.4" (31.5cm)
Weight:55 Ibs (25kg)Empty
Flue Pipe Hole:2'
2
(65mm)diameter
1-3 FUNCTIONAL DESCRIPTION
An overview of the functional operation of the
Monitors is diagrammed by Fiqure 1-1 and is described as follows:
Monitor operation always begins with a pre-purge and a pre-heat, which must be completed before operation can- begin to expel kerosene vapors from the Combustion Chamber.
At conclusion of the pre-heat, the Fuel Pump begins to work, the fuel is delivered into the preheated burner, and then an air fuel mixture is ignited, combustion takes place, and the heater keeps pre-burning. When the pre-buring is finished, the igniter turns off, the circulation fan turns on (at the appropriate speed) and the heater will automatically maintain the necessary burn rate.
The user is able to monitor the heater s performance by visually examining a series of indicators on the
Control Panel.
A Temperature Selector Control permits the user to set the temperature to the level desired in the room.
Upon commencing heater shutdown, a post-purge is run.
All heating operations cease-except for the air circulation fan and the combustion fan which continue. The post-purge continues for three minutes after a flame goes out.At this point, heater operation stops completely.
Auromatic operation of the Monitor 41 and Monitor
22 is controlled by a microprocessor with four sets of
Time Temperature programming per day.
PRE-PURGE
PRE-HEAT
IGNITION
COMBUSTION
HEATING
SHUTDOWN
POST-PURGE
Figure 1-1
SIMPLIFIED OPERATIVE CYCLE
1-4 DESCRIPTION
The Monitor heaters are composed of the following: a spill tray, a cabinet, a combustion system, an air circulation system, a fuel delivery system, electrical and electronics systems and a variery of safety
MONITOR HEATING SYSTEMS
Section 1: Description
mechanisms.
1-5 SPILL TRAY
The Spill Tray:
— Protects the floor from damage resulting from fuel spillage.
- Provides a secure, tip-resistant heater base.
Metal retainers (2) secure the heater to the Spill
Tray.
The legs are positioned with in the circular indentations.
1-6 HEATER CABINET
A steel Cabinet holds and protects all internal components.
A number of primary parts are assembled to form this housing.
1-7 COMBUSTION SYSTEM
The Combustion System is responsible for the production of heat which is circulated into the room.
In the Combustion Systems a mixture of fuel and air is burned to produce heat. Air is drawn from outside the dwelling into the Combustion Chamber. At the same time, fuel is metered from a storage cavity into this same Combustion Chamber.Within the chamber.the air fuel mixture is ignited to produce heat.
The Monitor combustion systems are safeguarded by a pair of overheat protector switches; They will shut down the heater (to protect it from damage) in the event of excessive heat build-up. The overheat protector switches reset automatically after cooling down.
1-8 COMBUSTION CHAMBER
This tall cylinder is positioned on the Heater Base.
It is secured to the base by Phillips head screws.
Connected to the Combustion Chamber are the igniter, (located within the chamber) a fuel line, the
Heat Exchanger, and a Flame Sensor.
Within the Combustion Chamber are the Burner Pot, the Combustion Ring Assembly and the Burner
Cap(M-22). Access to those internally-located parts is facilitated by a removable Service panel.A Window on the panel lets the technician visually examine the combustion process(i.e. glowing igniter or proper flame color).
An airway, in the Cabinet Base, extends from the intake fan of the Combustion Blower to the hollow base of the Combustion Chamber. This airway channels air to the Combustion Chamber.
The Flame Sensor is mounted with two (2) phillips head screws onto the wall of the Combustion
Chamber.
1-9 BURNER POT
Designed specifically to support combustion, the
Burner Pot (refer to Figure 1-2) contains a series of air holes, an igniter tube (to accommodate the
Igniter), and a fuel inlet fitting (interconnects the fuel line). It is secured to a mounting plate near the bottom of the Combustion Chamber.
The Combustion Ring Assembly is seated on three
(3) screws or pins in the Burner Pot.
1-10 COMBUSTION RING ASSEMBLY
This assembly is a speciai structure, designed to promote efficient combustion.
1-11 BURNER CAP
Secured by tabs and a screw on the Burner Pot, the
Burner Cap "shapes" the flame into its comfiguration and height. (M-22 only)
1-12 FLAME SENSOR
Mounted on the outside wall of Combustion Chamber, the Flame Sensor always supervises the flame.
1-13 IGNITER
Located within the igniter tube of the Burner Pot, the
Igniter is designed to pre-heat the Burner Pot and to vaporize and ignite the air/fuel mixture to start the combustion process.
The Igniter is secured by a bracket and screw to the igniter tube. The cover plate is secured to the combustion chamber by three (3) phillips head screws.
1-14 COMBUSTION AIR SYSTEM
The Combustion Air System channels air to and from the heater.
Outside air is drawn into the heater by the Combustion Blower through an airway to the Combustion
Chamber.
A Combustion Blower draws the intake air into the through a Flue Pipe. This air enters the Combustion
Chamber at the Burner Pot and mixes with the fuel to support combustion, Remaining air is heated and is drawn into the Heat Exchanger.
As the heated air passes through the Heat Exchanger, an Air Circulation Fan blows room air past the
Heat Exchanger and out again into the room, heating passing air by convection. Exhaust vapors exiting from the Hear Exchanger are vented through the
Flue Pipe.
A deterioration of air pressure at the Air Pressure
Switch is an abnormal condition; the heater is shut down by the malfunction.
MONITOR HEATING SYSTEMS
Section 1: Description
1-15 FLUE PIPE
Flue Pipes are available in three (3) sizes. This provides the flexibility to meet the installation requirements for dwelling of various wall thicknesses.
One side of the Flue Pipe contains a '"T-shaped fitting consisting of four ports. This side is mounted on the interior wall of the dwelling. The pipe side of the Flue Pipe is vented outside the dwelling.
The Flue Pipe Assembly consists of two concentric tubes. Outside air is drawn through the cylindrical space between the tubes.
Combustion by-products are vented through the inner tube.
As the cool air enters, it is heated by the hot air that is exiting the system.
A large-bore, flexible hose connects the air inlet port on the Flue Pipe with the Combustion Blower; a cloth-covered metal pipe connects the Combustion
Blower with the exhaust outlet on the Flue Pipe.
IMPORTANT: If extension kits are utilized, use the correct damper as follows:
Extension kit
Up to 3 elbows with
Extra Short Extensior kit
Length: 11' ,"-7' ,"
M-41
"STANDARD" damper
M-22
"STANDARD" damper
Up to 3 elbows with
Short Extension Kit
Length: II
1
,"-20' ,'
Up to 3 elbows with
Medium Extension Kit
Length: 20' ,"-38"
Up to 3 elbows with
Long Extension Kit
Length: 38"-73"
"STANDARD" damper
"EXTENSION" damper
"EXTENSION" damper
"STANDARD" damper
unused unused
1-16 COMBUSTION BLOWER
The combustion blower on the Monitor 22 is a dual function fan.
The intake fan draws in outside air thru the flue pipe for internal combustion. The cooling fan which runs on a common shaft with the intake fan circulates air inside the heater cabinet to keep internal components cool.
The Monitor 41 combustion blower has a two stage intake fan.
Burner modes control fan speeds and the solenoid damper in the blower casing. Those functions are as follows:
Table 1-1 COMBUSTION AIR CONTROL
Burn Mode
High
Medium-High
Fan Speed
High
Solenoid Damper
C Open)
Off (Open)
Medium-Low
Low
Low
Low
Low
On (Close)
On (Close)
1-17 HEAT EXCHANGER
An inlet at the top of the Heat Exchanger permits the heated air to travel from the Combustion Chamber into the exchanger.
An outlet, at the bottom of the exchanger, permits combustion by-products to be vented to the Flue
Pipe.
While moving through the Heat Exchanger, the hot air within the exchanger heats the outside metal walls. The hot metal walls, in turn, heat air that is pushed past the exchanger and is circulated into the room. An air baffle, directly in front of the exchanger, deflects the heated air upwards, and out, through the louver assembly.
A pair of Over-Heat Protector Switches protect the heater from damage due to excessive heat built-up.
1-18 AIR CIRCULATION FAN
Both Monitor circulation fans are driven by twospeed motors and are designed to circulate the heated room air.
If the heater is running in low and medium-low burn modes, the fan also runs at low-speed; in mediumhigh or high burn modes, the fan advances to high-speed.
Operation of the fan is controlled by the microprocessor and fan thermostat switch (52°C 126T--on,
35'C 95'F
-Off)
Physically assembled with a protective wire cage for the Monitor 41 and metal mesh cage for Monitor 22, the entire fan assembly is secured to a bracket on the rear of the Heater Cabinet.
A metal conduit, at the rear of the heater, protects the fan wiring from damage.
1-19 AIR PRESSURE SWITCH
This switch consists of a rubber diaphragm which senses changes in air pressure(it is connected to the Combustion Blower) and normally-open, micro switch.
Should an abnormal pressure differential exist, the switch opens to disable the circuitry that controls
MONITOR HEATING SYSTEMS
Section 1: Description
the supply of fuel. Since the flow of fuel to the Burner
Pot is cut off.the flame extinguishes (after all fuel currently in the line has been consumed), and the
Burner Status Indicators blink.
This safety mechanism can be triggered by several conditions:
— Leak or loose connection in air line
— Leak, loose, or broken tubing which connects the Air Pressure Switch with the Combustion
Blower
- Clogged or blocked Air Line
— Blocked or clogged Flue Pipe
— Intake port of Combustion Blower is blocked.
- Combustion Blower is inoperable
1-20 FUEL DELIVERY SYSTEM
Fuel Delivery is a very important aspect of the
Monitor's operation.
The fuel flow must be maintained at a level corresponding to the burn mode, so that combustion can be conducted efficiently.
Fuel moves by gravity-flow from the external fuel storage tank or the capsule fuel tank to the Fuel
Constant Level Valve.
The Solenoid Pump meters the flow of fuel from the
Fuel Constant Level Valve to the Burner Pot.
The metered flow of fuel is carried to the Burner Pot by a copper fuel line.
1-21 EXTERNAL FUEL TANK
The Monitor 22 gives the user the option of either using the internal capsule tank or hooking up to an external fuel tank.
Fuel for the Monitors can be stored in, and fed from an external storage tank. The tank, which generally is dealer installed, should contain a shutoff valve, a fuel filter and a vent. Installation of the tank should conform to local regulations and to the specifications and guidelines documented in this Service
Manual.
1-22 FUSIBLE LINK VALVE
Basically, the Fusible Link Valve is a safety mechanism that cuts-off fuel to the heater in the event of an overheat condition at the valve.
The fusible link valve is mounted as a standard item on the Monitor 22. Located outside the rear of the
Heater Cabinet, the Fusible Link Valve is a springloaded device that cuts off the supply of fuel to the heater when the temperature level (at the valve) exceeds a predefined maximum limit.
An inlet on the bottom of the valve allows fuel to pass into the heater. The handle-which can also manually be opened or closed-sits on a springloaded stem which contains a low-melting point alloy.
The fusible link valve can be externally mounted on the Monitor 41 if required.
1-23 FUEL CONSTANT LEVEL VALVE
This valve has an automatic shutoff safety mechanism and a Fuel Set Lever. The safety mechanism prevents fuel from flooding or overflowing from the fuel reservoir. The Fuel Set Lever resets the float so the Fuel Constant Level Valve can resume operation.
The fuel reservoir is a tank which contains a float assembly, a safety mechanism, and a priming lever.
Both the Monitor 22 and 41 fuel control valves are basically the same, however they are of different size and material and can not be interchanged.
Fuel enters the Fuel Constant Level Valve through an inlet at the bottom of the reservoir. As the level of fuel rises, it passes through a filter (which removes most particles and foreign matter from the fuel), flows up through an open inlet valve and enters the tank.
IMPORTANT: The Fuel Constant Level Valve filter should be cleaned or replaced periodically. Time intervals will depend on purity and quality of fuel.
Within the Valve, a float mechanism controls the level of fuel that will be permitted to the reservoir. As the fuel level drops, the float drops down to increase the inlet valve opening to admit more fuel into the valve. When the fuel level reaches its muximum volume, the float rises to shut the inlet valve.
In the event that fuel within the reservoir rises to an abnormally high level, a float within the reservoir rises to trip a safety lever. This safety lever drops to prevent fuel from entering into the reservoir.
Should a foreign substance cause the inlet valve to stick (or prevent it from opening), the Fuel Set Lever is utilized to free the valve and to admit fuel to the reservoir.
CAUTION: Care must be taken to prevent dust, dirt, or other debris from clogging or blocking the inlet valve. If debris collects on the seat of the inlet valve it may cause tripping of the safety lever and will require cleaning.
MONITOR HEATING SYSTEMS
Section 1: Description
1-24 SOLENOID PUMP
The Solenoid Pump is mounted on the Fuel Constant Level Valve, controlled by a microcessor.and
four modes(High, Medium-High, Medium-Low, Low) fuel flow is delivered to the Burner Pot.
1-25 ELECTRICAL SYSTEM
Electrical power is supplied to the Monitor to run the
Microprocessor and the other electrically-energized component.
Electrical operation of the Monitor can be thought of as having the following eight(8) distinct phasesiplug in; turn-on; pre-purge pre-heat; ignition: precombustion; heating; Shutdown and post-purge.
All electronic diagrams, Such as wiring diagram, circuit board layout and electrical schematic can be found in Section 7 of this Service Manual.
1-26 MICROPROCESSOR
Principally consisting of a 64-pin Integrated Circuit, the Microprocessor provides safety timings, controls relays and provides clock and thermostat functions for the Monitor heater. A component layout of the
Printed Circuit Board is found in Section 7 of this
Service Manual.
1-27 TEMPERATURE SENSOR
The sensor which is capable of sensing room temperature within a range of 42T to 96 F. can be left mounted on the back of the heater cabinet or be wall mounted.
Approximately 6' ,' (about 200 cm) of No. 20 AWG
Wire is supplied with the sensor to facilitate wall mounting the sensor in a favorable location.
1-28 SAFETY MECHANISMS
Several safety mechanisms have been built into the
Monitor Heating System. These devices protect the user against personal injury, protect the heater against damage, and shutdown the heater if a malfunction occurs.
1-29 CLOTH COVERED EXHAUST PIPE
Insulating cloth covers are to be placed over all metal surfaces of the Exhaust Line during installation.
Since combustion by-products are vented at elevated temperatures, the Exhaust Pipe will become hot during operation. The insulating cloth covers protect the user from burn hazards associated with accidental contact with these heated metal surfaces.
During installation make sure that all Exhaust Lines are tight. Do not operate the heater without the insulating covers.
1-30 AIR CIRCULATION FAN GUARD
This guard is an integral part of the fan assembly.
The guard protects the user against physical injury which could occur from accidental contact with revolving metal fan blade.
1-31 FUSE
2-amp. and 10-amp.. 125VAC, fuses protect the heater from damage resulting from power overloads.
In the event of a power surge or internal wiring hazards, the fuse opens and power to the heater is cut
off.
The electrical outlet into which the heater is connected should be protected by at least a 15-amp.
fuse or circuit breaker.
1-32 OVERHEAT PROTECTOR SWITCHES
Connected in series, two (2) normally-closed Overheat Protector Switches safeguard the heaters against damage due to overheating.
The Monitor 22 switches are rated 110"C (230'F).
The Monitor 41 switches are rated 115'C (239'K).
Should a Monitor overheat (internal temperatures rise beyond 110"C (230'F) on the Monitor 22, 115t
(239'F) on the Monitor 41) either or both switches will open to shut down the heater. After extinguishing the flame, the Burner Status indicators continue to blink. The Overheat Protector Switches will automatically reset after cooling down.
Once the heater has cooled to 80'C (176'F), the system can be restarted. To restart the Monitor, proceed as follows:
A. Press ON OFF Switch to OFF.
B. Allow heater to cool.
C. Troubleshoot the cause of the overheat.
D. Press ON OFF switch to ON
E. Proceed with normal operation.
V33 SLIDE SELECTOR FOR THE RESET TEMP.
Once power is restored after power interruption by power failure or by disconnecting heater plug from wall outlet, heater will resume operation in the
MANUAL mode and maintain room temperature according to the setting temperature selected by using the selector for the reset temperature at the lower right hand side of the cabinet.
MONITOR HEATING SYSTEMS
Section 1: Description
COMBUSTION CHAMBER
FLAME SENSOR
COMBUSTION RING
BURNER POT
AIR CIRCULATION FAN
FLUE PIPE
INTAKE OUTDOOR AIR
Figure 1-3 ELEMENTS OF COMBUSTION SYSTEM (MONITOR 41)
SOLENOID DAMPER
AIR PRESSURE SWITCH
MONITOR HEATING SYSTEMS
Section 2: Installation
2-1 INTRODUCTION
Installing the Monitor System at the user's location can be performed quickly and economically. The
Monitor 22can be used as either an internally fueled
(capsule tank) or remotely fueled System. The
Monitor 41 model is strictly a remotely fueled system and both are externally vented. As such both need the installation of an externally vented intake exhaust system and if remotely fueled, will need the installation of a remote fuel storage tank.
By completing each step of the easy-to-follow installation instructions (each step should be completed in the exact order specified), the Technician is directed through the installation process.
This section contains all relevant installation information including:
— Installation specifications
— List of installation tools
— Alternative types of venting systems (and installation procedures for each)
— Basic requirements for fuel tank installation
— Instructions to install the Monitor System
IMPORTANT: Before beginning installation of the
Monitor vented heating system (including any electrical wiring and fuel supply equipment), check local building,electrical, mechanical and fire codes. The requirements of these codes must be followed to insure lawful installation and use.
The heater can be located almost anywhere within the dwelling provided that electrical, fuel, and exhaust specifications are met.
2-2 PHYSICAL PLACEMENT OF HEATER
In addition to the space taken up by the heater, interior space must also be reserved for free air circulation. Remove all combustibles from the heating area.
Unless building or fire codes dictate otherwise, the
Monitor system can be placed on any floor surface
(including carpeting or other combustible material) and provide safe operation.
2-3 DRILLING REQUIREMENTS
Through-the-wall Flue Pipe installation requires that a 2 ' .," (65mm) hole be drilled through the dwelling wall (interior to exterior). The hole must be pitched downward toward the outside at an approximate angle of 2 (about
L
/' per foot). The appropriate wall area (in which hole will be drilled) must contain no internal obstacles such as piping, wiring, air ducts, or studs.
RECOMMENDED TOOL KIT FOR MONITOR
HEATER SERVICE TECHNICIANS
1) =2 Phillips Head Screwdriver
2) Steel Tape Measure
3) Felt Tip Pen or Pencil
4) Caulking Material (exterior grade)
5) Electrical Drill
(reverse capability recommended)
6) Hole Saw, Saber (Jig) Saw, or other appropriate tool for cutting a 2.5" diameter hole for flue pipe
7) Rubber Clipping Tool
8) Long Drill Bit—'
t
"
9) -2 Standard Screwdriver
10) Adjustable Wrenches (various sizes)
11) Copper Tubing Cutter
12) Copper Tubing Flaring Tool
13) V.O.M.(Volt, OHM. Meter with shielded probes)
14) Level
15) Plumber's Pipe Thread Tape
16) Small assortment of Self-Tappeng Screws
17) Assorted Pliers (Slip Joint, Needlenose, Cutting,
Lock Joint)
18) Phenolic Probe or Insulated Screwdriver
19) Supply of 125V, 2 and 10 Amp fuses
20) Floor mat to cover carpeting
21) Quart size pan for draining fuel
2-4 POWER REQUIREMENTS
WARNING
THE MONITOR POWER CORD MUST BE PLUGGED
INTO A DIRECTLY ACCESSIBLE WALL OUTLET.
DO NOT USE AN EXTENSION CORD TO MAKE
THIS ELECTRICAL CONNECTION.
Line current to the system should be 120 VAC at 60
Hz. The electrical system should be protected against current overload by means of at least a
15-ampere fuse or circuit breaker.
NOTE: The wall outlet should supply electricity for the Monitor system only. Do not connect any other electrical appliance to it.
CAUTION: In some installations, it may be best to hard-wire the heater to the house circuits. A competent, licensed electrician should do this.
MONITOR HEATING SYSTEMS
Section 2: Installation
2-5 FUEL TANK REQUIREMENTS
INSTALLATION OF ANY REMOTELY LOCATED
FUEL TANKS MUST COMPLY WITH ALL LOCAL
STANDARDS AND OR BUILDING CODES.
Heater fuel (crystal clear kerosene only) can be stored in remotely located storage tanks ranging from 55 gallon drums to 275 gallon tanks. When using large tanks a pressure regulator with a max. of
2.5 PSI should be installed near heater inlet.
CAUTION: In some installations, it may be better to install permanent fuel tank plumbing. A licensed
Plumber should do this.
2-6 TEMPERATURE SENSOR WIRING REQUIRE-
MENTS
A wall-mounted temperature Sensor gauges room temperature and automatically regulates the heating cycles of the Monitor System.
The standard sensor wire is 6
J
,' long and can be left mounted on the back of the cabinet as shipped.
If this is not practical the sensor can be mounted on a wall.
NOTE: The Dealer should complete the Registration Card at time of customer purchase and return it to Monitor Products, Inc. as soon as possible.
D. Remove the spill tray from shipping carton, and remove the plastic bag.
E. Remove the plastic bag covering the hearer.
F. Remove the plastic bag containing the heater parts.and set it aside.
G. Remove the Flue Pipe from the rear of the heater. When ready to install, separate Flue
Pipe from cardboard packing materials.
H. Firmly grasp cabiet handles (one on each side of heater cabinet) and lift heater off the cardboard shipping base.
I. Check for parts as listed in Monitor Owners
Guide.
IMPORTANT: Only the standard-size Flue Pipe is shipped with the heater. The Monitor dealer will also stock Medium
Rue Pipes, Window Kits, Extension
Kits, and other accessories that may be required for non-standard installations.
CAUTION: II sensor is to be mounted remotely be careful not to place it in direct sunlight, on uninsulated exterior walls in drafty areas etc., as this will create an inaccurate temperature reading.
2-7 BUILDING CODES
Fire regulations, electrical and other local building codes may govern the installation and use of a vented heater and related fueling systems. Prior to installation, check and comply with all codes.
2-8 UNPACKING
Save all shipping materials until the Monitor has been completely installed and is working properly.
A. Cut the two plastic ribbons that hold the shipping carton together.
B. Remove the top.
C. Remove from the shipping carton the Cardboard
(drilling) Template and the Owner s Guide.
10
MONITOR HEATING SYSTEMS
Section 2: Installation
2-9 HEATER INSTALLATION
In choosing a location for your heater, the following guidelines must be considered:
•The heater MAY be installed on combustible floors.
• The area around the heater should be free of obstacles that might interfere with the free flow of air.
Allow the clearances shown in Figure 2-1.
• The heater must not be installed in a combustible fireplace.
• An AC wall outlet must be within reach of the heater's power cord. Extension cords must not be used.
• The area outside where the flue pipe will emerge should be free of foliage, fuel storage tanks and flammable objects. Air should circulate freely in the area. Allow the clearances shown on following page.
• The wall where flue pipe hole will be cut should be free of plumbing pipes, electrical wires, studs.
air ducts and other obstacles.
NOTE: After using the installation template as a guide for drilling the flue pipe hole, the
Monitor Flue Pipe can be normally installed according to the Illustration procedure in the Monitor Manual.
Just in case the template was misplaced, the approximate flue pipe hole location measurements are as follows:
Tha center of The Joint Pipe opening, which connects to the Flue Pipe.
M41
Back of Heater
15cm, 6in
100cm, 39in
25cm, 10in
The center of The Joint Pipe Back of Heater
M22
100cm, 39in
Figure 2-1
11
Figure 2-2
MONITOR HEATING SYSTEMS
Section 2: Installation
FLUE PIPE CLEARANCES
Flue pipe installations should provide for venting to an unconfined space through which there is a free flow of outdoor air. Clearances to adjacent walls or obstacles must comply with the requirements shown below.
Frontal Clearance
ACAUTION: 24 (60cm)
Do not attach anything onto the outlet or more of the flue pipe.
(13.5cm) j
4
Clamp 1 II
<- Wall !
Any construction E above Flue Pipe
S
1
^' must not come _ i
(14 within 24' (60cm) I cm) of front obstacle
-or+ 24" (60cm) .
more or more j Front Obstacle
^..-Flue Pipe !
'-.
J j
Heater
8" (20cm) or more
Ground or slab surface
Overhead Clearance
r h (
.
h|
Non-combustible
~
Wal!
Combustible
24' (60cm) or more
Body -r^i
Clamp . I
45'
fjr 24' (60cm)
<£jr or more
"7
T
-;•/ 12' (30cm)
/ or more
Heater -I :*<- •
f" ' — Flue Pipe
Ground or slab surface
Side Clearance Body
Clamp
\
-H
^j1
Side obstacle
" " ~
18' (45cm) or more t^ -V
Flue Pipe
•
IMPORTANT:
In open area with strong wind, a wind break may be necessary.
a t
'
>
^
Figure 2-3
12
&
MONITOR HEATING SYSTEMS
Section 2: Installation
HOW TO PREVENT FREEZING IN COLD CLIMATE.
Exhaust Elbow
Front Obstacle
In areas of heavy snow falls, ground surface clearance must be increased according to average snow falls, to prevent flue pipe from being buried.
SNOW SURFACE or GROUND
Long — .
N
Extension \
^
=5: c
*"i
Must be higher.
J
'•"..'•.!'••" Snow t
Figure 2-4 FLUE PIPE CLEARANCES
INSTALLATION OF FLUE PIPE WINDOW KIT
A window kit makes it possible to vent the heater from dwellings in which through-the-wall venting is neither practical nor possible.
The Window Kit is available in two sizes. The Short
Window Kit accommodates windows from 20 to 32" wide; the Long Window Kit accommodates windows from 31 to 50" wide.
NOTE: The procedure below describes how a
Window Kit is installed in a double-hung window. The Window Kit can also be installed in a vertical, sliding type window.
Install the Window Kit in the manner outlined below:
STEP 1: Install Flue Pipe in Window Kit
A. Push the rubber seal into the Flue Pipe hole on the window kit frame. The hole on the seal should be positioned at the exterior side of the frame.
B. Using the four (4) Phillips head screws, fasten the spacer to the frame.
C. With the arrow on the Flue Pipe pointing UP, align the screw holes on the Flue Pipe with those on the Spacer. Secure with three (3)
Phillips head screws.
13
MONITOR HEATING SYSTEMS
Section 2: Installation
STEP 2: Install Window Kit in the Window
IMPORTANT: Prior to installation, clean the window frame of all dust, dirt, and debris.
A. Raise the lower window
B. Place the window kit frame into the innermost track of the window.
C. Expand the frame until it fits loosely within the width of the window; it may be necessary to loosen the large set screw on the frame in order to do so.
D. Slightly lift window kit frame. Slide the L-
Adapter under the frame and position it at the point where the inner and outer frame meet.
Expand the frame to fit the window tightly.
Adjust the position of the L-Adapter. if necessary. Tighten the set screw to secure the frame.
Secure the L-Adapter to the window sill with two (2) wood screws.
Lower the window firmly down upon the top of the Window Kit frame.
Measure the width of the upper (outer) window
(which is located in the outer track). Cut a length of the Rubber Packing to this size.
Remove the protective backing and firmly mount it onto the underside of the outer window.
MONITOR HEATING SYSTEMS
Section 2: Installation
STEP 3: Install Window Lock
A special window lock replaces the usual clamshell lock.
To install the window lock, proceed as follows:
A. Turn locking lever to left and disengage lock from lock bracket.
B. Attach lock bracket to left-hand side of upper window frame. Use the two wood screws provided.
NOTE: If the lock bracket prevents the lower window from sliding upward, notch the bracket into the upper window frame.
C. Slip lock into lock bracket.
IMPORTANT: Window can be locked by turning locking lever to right; to open, turn locking lever to left and remove lock from bracket.
D. Two adjustable-position stops are supplied to accommodate various window sash thicknesses. If short stop is too small, remove two retaining screws and brackets which hold the short stop to the underside of the lock. Remove the short stop and substitute the long stop.
Adjust to proper position, and secure with screws and washers previously removed.
(Before securing the stop to the window, remove the protective backing and firmly stick the stop packing onto the underside of the stop,)
NOTE: Windows with deep sills may require the use of an extra intake and exhaust elbow to provide clearance for flue pipe hook up,
A piece of the air intake line can be cut to join the two intake elbows together.
Deep Window Sill
One Exhaust Elbow
Figure 2-6
Two Intake Elbows
15
MONITOR HEATING SYSTEMS
Section 2: Installation
2-10 INSTALLING AN EXTENSION KIT
Installing an Extension Kit requires the construction of an air line and the exhaust line. The air line is connected between the Air Supply Elbow at the rear of the heater and the air inlet port on the Fiue Pipe.
Similarly, the exhaust line is connected between the joint pipe at the rear of the heater, and the exhaust port on the Flue Pipe.
IMPORTANT: The PVC air line is longer than the exhaust line and may need to be cut to size. Be sure, however, to thoroughly deburr all rough edges.
ITEM=
1
2
3
4
5
Figure 2-7 COMPONENTS OF EXTENSION KIT
DESCRIPTION
PIPE. Air supply
JOINT, Air line
ELBOW 90 Air line
LEG. Wall-standoff
PIPE CLAMP. Top
ITEM:
6
7
8
9
DESCRIPTION
PIPE CLAMP, Bottom
SCREW, Legs, mounting
SCREW, Pipe Clamp
BOND, Adhesive
16
MONITOR HEATING SYSTEMS
Section 2: Installation
Max lengths and bends allowable using extension kits.
Extension kits are available in four diffirent lengths.
For exact dimensions refer to the accessories catalog.
3-90 Bends
10 R.Max
Figure 2-8 MAX LENGTHS AND BENDS ALLOWABLE USING EXTENSION KITS
17
MONITOR HEATING SYSTEMS
Section 2: Installation
2-TI TYPICAL MONITOR UFTER PUMP INSTALLA- For more detailed information look under Kerosene
TIONS
Lifter manual.
NOTE: The same minimum and maximum pump heights must be maintain as is with other fuel tanks. Figure 2-12
MONITOR"' KEROSENE UFTER
MONITOR
1
" KEROSENE UFTER
(CAN BE POSITIONED BEHIND UNIT)
MONITOR"
1
KEROSENE LIFTER
Figures 2-9
MONITOR
1M
KEROSENE LIFTER GRAVITY
MONITOR HEATING SYSTEMS
Section 2: Installation
2-12 USES FOR THE ELBOW ADAPTER KIT
Convert from Monitor 20 30 to 22 41 using an elbow adapter Kit (part=8213) and utilizing existing flue pipe installation.
PARTS LIST EXPLODED
Name No
Rel.
of in
No. Part Unit
1 Exhaust Pipe Clamp
2 Exhaust Elbow 1
3 Exhaust Joint 1
4 Joint Supporter 1
5 Heat Insulation Cover 1
6 Self-Tapping Screws 2
7 Hose Clamp (this part comes with your
Monitor
1
*
1
Heater)
8 Air Damper {this part comes with your
Monitor™ Heater)
9 Flue Pipe (this part comes with your
Monitor"
1
Heater)
A. Remove Monitor 20 30 heater and flue pipe.
B. Install Monitor 22 41 flue pipe into sleeve.
C. Slide the exhaust elbow onto the exhaust port opening on the rear of the heater. (To locate exhaust port opening, see your Monitor Owner' s Guide.)
D. Secure the exhaust elbow by attaching the exhaust pipe clamp to the heater cabinet with two self-tapping screws.
E. Cover the adjustable exhaust pipe with heat insulation cover.
F. Remove metal cap on side mounted exhaust port of flue pipe and replace into the port (the
Monitor 22 41 is now ready to be positioned into place.)
NOTE: Be sure the exhaust elbow is firmly fixed on the flue pipe with a joint supporter.
G. Insert air supply elbow opening over flue pipe air intake flange and secure with hose clamp.
NOTE: The Standard Air Damper is installed over the flue pipe "air intaka flange." (To locate flue pipe "air intaka flange", see your
Monitor™ Owner's Guide.)
Elbow adapter kits may also be used to raise a flue pipe high enough to clear certain base board heating systems.
2-13 FUEL TANK INSTALLATION
Pictorial views of alternative types of storage facilities and delivery systems are illustrated (Figure
2-12).
Since fuel storage tank installation techniques vary from place-to-place (often dependent upon applicable codes), a particular installation procedure cannot be specifed. However, certain criteria govern the fuel hook-up of the Monitor Use the following check list as a guide to the fuel storage facilities:
Figure 2-10
USE ONLY CRYSTAL CLEAR KEROSENE. NEVER
USE GASOLINE, WHITE GAS, CAMP FUEL OR
OTHER FLAMMABLE LIQUIDS. USE OF SUCH
FUELS CAN RESULT IN AN EXPLOSIVE RRE AND
CAUSE SEVERE INJURY.
Fueling Options Available
Fueling of the Monitor Heating Systems can be accomplished in one of 3 ways:
1. Capsule Tank (on the Monitor 22).
2. Gravity Fed Large Capacity External Tank:
Practical for large heating needs where bulk delivery of kerosene is available. This system should be installed by a qualified plumber or fuel supply technician.
*3. Large Capacity External Tank with Pump: For large heating needs where a gravity fed system is not practical. An electric pump, the
Monitor™ Kerosene Lifter, especially designed for use with Monitor heating systems.
"if a pumping system is used is used to supply fuel, the inlet pressure to the heater must not exceed 2.
5
psi.
19
MONITOR HEATING SYSTEMS
Section 2: Installation
To install a large capacity, gravity fed external tank, follow the instructions below. Use of a qualified installer is recommended.
• Installation height of the bottom of the fuel tank should be 16 inches or more above the floor surface on which the heater stands. This insures that inlet fuel pressure will be sufficient.
The top of the fuel tank should be no higher than 8' > feet above the floor under the heater.
This insures that inlet fuel pressure will not be excessive.
• The horizontal length of piping should not exceed 100 feet and should be free of sharp bends or obstructions.
• Piping should include no inverse U-type bends
(to avoid air locks, which could block the fuel supply).
• Only
J
, inch OD copper tubing should be used.
The tubing should be bent carefully to avoid crimping.
• A fuel filter is recommended for use on the fuel line near tank, and a shut-off valve should be installed at the tank.
• Flare connections should be used at the fusible link valve connection on the heater and at the fuel filter to be installed at the tank.
• The fuel tank should be located no closer than
6 feet to a source of heat.
• The fuel tank should have an opening for filling on the top and a vent with a weather-proof cap on the side. On some tanks the vent and fill spout use the same opening.
55,100, and 250 gallon tanks must contain:
• Shut-off valve at tank outlet
• Disposable fuel filter (protects heater against condensation and other impurities)
• Fueling inlet (protected by weather-proof cap)
• Ventilation outlet
• Clearance of at least 6' from any source of heat
Allowable Height Dimensions:
• Bottom of tank-at least 16" above floor holding heater (maintains sufficient pressure)
• Top of tank-maximum of 8' / above floor holding heater (prevents excessive line pressure)
• Position of Lifter-more than 8' above fuel inlet of heater requires pressure reduction valve.
RECOMMENDATION
Pipe fittings in the fuel supply to the Monitor heating systems should be sealed with pipe thread tape.
The supply line from the tank to the Monitor
1
'
1
Kerosene Lifter must be absolutely air tight. 275 gallons and bigger tanks should have a 2.5 P.S.I, max pressure reducer to avoid excessive pressure at heater inlet.
2-14 HEATER INSTALLATION
The Monitor heaters can be physically situated on carpeting or other combustible flooring with complete safety. The selected heater site must be accessible to an electrical outlet, must support free air ciculation (both internal and external), and must not contain combustible materials in the heater's immediate vicinity.
Litter
Interior or exterior gravityfed 55.
100,
or
275gallon tank
Lifter circulates fuel from remote storage tank
Figure 2-11 ALTERNATIVE SOURCES OF FUEL STORAGE
MONITOR HEATING SYSTEMS
Section 2: Installation
Shut-off Valve
. Flare Connection
- - - -.1
Outdoor Fuel Tank
:
, OD Copper Tubing
Outdoor Fuel Tank
Shut-off Valve
." Flare Connection ff
Fuel Filter
16"
Flare Connection (°-
4m
)
OD Copper Tubing
Figure 2-12 TYPICAL FUEL LINE CONNECTIONS
21
MONITOR HEATING SYSTEMS
Section 3: Operation
3-1 INTRODUCTION
Monitor is an easy-to-operate vented kerosene heater. Routine operation features high BTU output, automatic adjustment of room temperature, low fuel and power consumption, and choice of automatic or manual heater operation.
This section provides all information necessary to operate the Monitor Heating System. All operation procedures specified should be performed in the order in which they are described.
3-2 OPERATING SPECIFICATIONS
The following specifications apply to the operation of the Monitor 41 and the Monitor 22:
Monitor 41
— Rated Efficiency (as applied to kerosene heaters): 93%"
— Rated Efficiency (as applied to central heating systems): 87%
— Power Consumption : as follows
HIGH MEDIUM-HIGH MEDIUM-LOW LOW
IGNITION E W BURN BURN BURN
340watts 65watts 62*atts 58watts SSwatts
— Circulation Fan Output : 388 cubic feet min.
— Fuel source : Remote, separate tank
— Potential heating area : 900-3200 sq. feet
"The energy from the combustion process is released in the form of heat and vaporized water.
Normally, heating systems discharge water from combustion to the atmosphere without condensing it. This 93% efficiency rating means that, assuming the water cannot be condensed, 93% of the heat produced by the combustion process is recovered.
Assuming the water can be condensed, the efficiency is 87%.
NOTE: Actual effective heating area depends upon numerous factors such as type and severity of climate, type of dwelling construction, condition of dwelling, and thickness and effectiveness of dwelling insulation.
Table 3-1 lists Monitor 41 performance specifications at various user-selected heat output settings.
Rating
Heater Output hr.
Table 3-1 HEATER PERFORMANCE SPECIFICATIONS
Specification
Fuel Consumption (gal hr)
8-hrs day burntime (5-gal. tank)
Continuous-use burntime (5-gal.tank)
8-hrs day burntime (55-gal.tank)
Continuous-use burntime (55-gal.tank)
8-hrs day burntime (275-gal.tank)
Continuous-use burntime (275-gal.tank)
Low
16,200
15,000
0.12
5.2days
41.7hrs.
57.3days
19.1days
286.5days
95.5days
Medium
Low
Setting
Medium
High
21.000
33,900
19,500 31,500
0.16
3.9days
31.3hrs.
43days
14.3days
214.8days
71.6days
0.25
2.5days
20hrs.
27.5days
9.2days
137.5days
45.8days
High
43,000
40,000
0.319
2.0days
15.7hrs.
21.6days
7.2days
107.8days
35.9days
22
MONITOR HEATING SYSTEMS
Section 3: Operation
Monitor 22
Rated Efficiency (as applied to kerosene heater): 93%"
— Rated Efficiency (as applied to central heating systems): 87 %
— Power Consumption : as follows
HIGH MEDIUM-HIGH MEDIUM-LOW LOW
IGNITION BURN BURN BURN BURN
250watts 52watts Slwatts SOwatts SOwatts
— Circulation Fan Output : 176 cubic feet min
— Fuel source : 1.32 U.S. gal., separate tank optional
— Potentional heating area : 600-2000 sq. feet
Table 3-2 lists Monitor 22 performance specifications at various user-selected heat output setting.
Rating
Table 3-2 HEATER PERFORMANCE SPECIFICATIONS
Specification
Low
9,600
Medium
Low
Setting
Medium
High
11,700 17,400
Heater Output hr.
8,900 10,900 16,200
Fuel Consumption (gal hr)
0.07
0.09
0.13
8-hrs day burntime (1.32-gal. tank)
Continuous-use burntime (1.32-gal. tank)
2.4days
13.9hrs.
LSdays
14.7hrs.
1.3days
10.2hrs.
8-hrs day brntime (55-gal.tank)
Continuous-use burntime (55-gal.tank)
98.2days
32.7days
76.4days
25.5days
52.9days
17.6days
High
22,000
20,400
0.164
LOdays
S.Ohrs.
41.9days
14.0days
23
3-3 OPERATING CONTROLS AND INDICATORS
Several controls and indicators are used to operate the heater and to monitor its performance as follows:
MONITOR HEATING SYSTEMS
Section 3: Operation
RUN AUTO EMPTY
BURNER STATUS
aBSSi.
LOW
HIGH
TEMP
AM
/PM
SET
ROOM
4 6
Figure 3-1, INDICATORS
10 11 12 13 14
!
OPERATION I TIMER SELECTOR
CLOCK CLOCK I I I
ON OFF AUTO
TEMP SET 1st 2nd 3rd 4th
[D=
TEMP
20
Figure 3-2, CONTROLS
TIME TEMP SET
HOUR MINUTE SET CLEAR
16 17
FIGURE AND ITEM NO CONTROL OR INDICATOR. FUNCTION
Figure 3-1, Iteml RUN Indicator Light Light to indicate that power has been apllied to heater.
Illuminates when operation ON OFF pushbutton switch is pressed to position ON
Figure 3-1, Item2 AUTO Indicator Light Lights when heater runs in automatic mode.
AUTO, RUN, and appropriate BURNER STA-
TUS Indicators are illuminated simultaneously if heater is burning.
Figure 3-1, Item3 Empty Indicator Light
Figure 3-1, Item4
BURNER STATUS
Indicator Lights
In case of using the cartridge tank, when the fuel is empty, EMPTY Indicator Light blinks.
This Light is not provided with Monitor 41.
Light in accordance with heat output as follows:
Heat Output Light Pattern
High 8indicators-ON
Medium High 6indicators-ON
Medium Low 4indicators-ON
Low 2indicators-ON
24
MONITOR HEATING SYSTEMS
Section 3: Operation
FIGURE AND ITEM NO
Figure 3-1, ItemS
CONTROL OR INDICATOR. FUNCTION
TEMP Indicator Light Lights when heater is running and Digital
Window is showing the temperature.
Figure 3-1, Item6 AM Indicator Light
PM Indicator Light
Figure 3-1, Item?
Figure 3-1, Items
Figure 3-2, ItemlO
Digital Display Indicates SET and ROOM temperature when heater is running, and indicates time when heater is Off.
Indicates time and temperature for automatic operation setting.
Figure 3-2, Item9 TIMER SELECTOR Displays set and current room temperature
CLOCK TEMP when heater is ON.
position Displays current time (after time has been programmed) when heater is OFF. Prior to programming, 88:88 is displayed on clock.
NOTE: During routine heater operation, the selector switch is normally set to this position.
CLOCK SET position
Programs current time on Clock by use of
HOUR and MINUTE push-button switches.
NOTE: Prior to programming current time.
Digital Display shows 88:88.
IMPORTANT: Once current time has been programmed, press the SET pushbutton switch with in 60 seconds.Otherwise clock display will revert to previously programmed time, if any.
Figure 3-2, Item11 1ST Position
Programs first automatic heater operation.
When programmed, heater automatically operates at specified time and temperature (i.e. 6:
00 a.m., 70T), if set for AUTO, providing that heater has been set for automatic mode of operation.
TIME, TEMP, HOUR(UP), MINUTE(DOWN) and
SET push-button switches are used to program first operated time and temperature.
IMPORTANT: Once time and temperature have been programmed, the
SET push-button switch must be pressed with in ISseconds.
Otherwise, time and temperature will revert to previously programmed time, If any.
When selector switch is set to this position, 1st presently programmed time and temperature are displayed.
Figure 3-2, Item12 2ND Position
Programs second automatic heater operation as same as 1st position.
25
MONITOR HEATING SYSTEMS
Section 3: Operation
FIGURE AND ITEM NO
Figure 3-2, Item13
Figure 3-2, ItemH
Figure 3-2, Item15
Figure 3-2, Itemie
Figure 3-2, Item! 7
Figure 3-2, Item18
Figure 3-2, Item19
Figure 3-2, Item20
CONTROL OR INDICATOR. FUNCTION
3RD Position Programs third automatic heater operation as same as 1st position.
4TH Position Programs fourth automatic heater operation as same as 1st position.
TIME push-button This switch is used to set time and change switch display over.
TEMP push-button This switch is used set temperature and switch change display over.
HOUR UP, Programs time or temperature.
MINUTE DOWN NOTE: Each time push-button switch is repetitive-action pressed, the digit advances in increpush-button switch ments of one digit, If push-button is pressed and held, the degits are advanced repetitively.
SET push-button switch "Sets" time and or temperature.
If this control is not pressed after time and or temperature have been programmed, the time and or temperature programmed (as indicated by display window) will not be accepted, and will revert to previously programmed time and/ or temperature.
CLEAR push-button switch Erases programmed time and temperature.
When cleared, time and/or temperature previously programmed and displayed disappears) from window.
IMPORTANT: Both current time and automatically programmed timers), temperature(s) will have to be reprogrammed If electrical operation Is interrupted by power failure or by disconnecting heater plug from wall outlet. If this occurs, the heater will go into MAN-
UAL mode of operation and maintain room temperature according to the setting temperature you've selected by using the slide silector for the reset temperature at the lower right hand side of the cabinet.
ON OFF push-button
ON posi ti
0n
(push-button is "in")applies power switch to the unit. When this occurs, the RUN indicator lights to indicate that heater operation has begun.
OFF position (push-button is "out") remove power from the heater. All circuits-except for
Clock and Air Flow — are shut down.
26
MONITOR HEATING SYSTEMS
Section 3: Operation
FIGURE AND ITEM NO
Figure 3-2, Item21
CONTROL OR INDICATOR. FUNCTION
AUTO push-button switch
Places heater in automatic mode of operation.
AUTO indicator lights to confirm automatic operation.
Assuming that the heater has been properly programmed and heater is in ON position.
heater will operate automatically.
When pressed again, AUTO indicator goes out and then heater will operate in MANUAL mode. During manual operation, the user turns heater ON and OFF, at will.
3-4 PRE-OPERATION CHECK LIST
After heater installation, but prior to Monitor heater start-up, inspect the system for operational readiness. The following check list specifies those items that should be inspected on a routine basis:
, Check that the Monitor heater is plugged into wall outlet
(120 Vac,
60 Hz)
Verify that adequate supply of kerosene is available in fuel tank
Confirm that fuel is free of water or other contaminants
Check fuel tank for good operating condition; it must be free of rust, corrosion, and or leaks
Inspect Fuel Line for signs of leaks, loose connections, cracks, air pockets or blockages
Confirm that Fuel Valves on Fuel Tank and
Fusible Link Valve are open so fuel can flow freely
Outside dwelling, check area immediately around Flue Pipe for combustibles or obstructions to free air circulation
Inspect Air Line for cracks, loose connections or blockage
Check Exhaust Line for cracks, loose connections or blockage
At rear of heater, verify that air flow to the Air
Circulation Fan is not blocked
Inspect dwelling interior and confirm that immediate area near heater is free of combustible and objects that might interfere with free air flow.
Make certain that Heat Sensor is not exposed to drafts, direct sunlight, nor direct heat from the Monitor.
Confirm that heater is level
If this inspection reveals any system deficiencies, correct the problems before operating the heater.
3-5 OPERATION
Operation of Monitor heater can be controlled manually by the user, or run automatically by the microprocessor.
Paragraphs 3-6 through 3-10 provide the details of heater start-up, operation, and shutdown. The controls and indicators illustrated by Figure 3-1 and
3-2 are used to operate the system and to monitor the heater's performance.
3-6 MANUAL HEATER OPERATION
Operation of the heater is under the direct control of the user (heater will not operate automatically). The heater will, however, automatically respond to changes in room temperature signaled by the Heat
Sensor to maintain the temperature of the room at a comfortable level.
NOTE: Resetting the Fuel Constant Level Valve is necessary only if the heater is being started for the first time, hasn t been used for an extended period of time, or if tank has run empty. If priming is unnecessary skip to step 2.
STEM: Prime the Heater
Gently press and release the Fuel Constant Level
Valve Reset Lever four or five times.
STEP2: Select Manual Operation
If heater operation is in AUTO mode, press the
AUTO push-button switch and change Auto to
Manual mode.
STEPS: Select Temperature Setting
Press the TEMP push-button switch and press either the UP or DOWN push-button switch to set the digital set room temperature indicator to the desired temperature, and then press the SET pushbutton switch.
27
MONITOR HEATING SYSTEMS
Section 3: Operation
IMPORTANT: In case no temperature is set, temperature will automatically be set at the setting temperature selected by using the slide selector for the reset temperature.
STEP4: Turn Monitor On
Press the ON OFF push button switch to position
ON. The RUN indicator light illuminates to indicate that power has been applied to the instrument and the heater is cycled for manual mode of operation.
3-7 AUTOMATIC HEATER OPERATION
Automatic operation is established by programming the time temperature settings for specific times. On a daily basis, a maximum of four time temperature settings can be programmed.
If, subsequently, it should be desired to switch to manual mode of operation, the changeover can be made at any time.
Proceed with automatic mode of operation in the following manner:
STEP1: Program Clock for Current Time
A. Position TIMER SELECTOR slide switch at position CLOCK SET.
B. Press HOUR push-button switch to program current hour on the Clock.
IMPORTANT: Be sure to set clock for AM or PM, as appropriate.
NOTE: Both hour and minute digits on Display
Window are advanced in i-crements of one by pressing the appropr ate push-button switch one time for each digit: digits can also be advanced repetitively by pressing and holding the appropriate push-button switch.
C. Press MINUTE push-button switch to program the current minute(s) on Clock.
D. Immediately after programming current time in terms of hours and minutes, press the SET push-button switch.
E. Place TIMER SELECTOR slide switch in position CLOCK TEMP and verify that time displayed on Clock is the current time.
STEP2: Program the 1st Time Temperature
A. Slide TIMER SELECTOR slide switch to position 1st.
B. Press TIME push-button switch.
C. Press HOUR and MINUTE push-button switches to program 1st desired time.
IMPORTANT: Be sure to set the clock AM or PM, as appropriate.
D. Immediately after programming the 1st desired time, press the SET push-button switch. This step must be completed within fifteen seconds after programming the time.
E. Press TEMP push-button switch.
F. Press UP and or DOWN push-button switch(es) to program 1st desired temperature.
G. Immediately after programming the 1st desired temperature, Press the SET push-button switch.
This step must be completed within fifteen seconds after programming the temperature.
STEPS: Program the Remaining Times
With the TIMER SELECTOR slide switch in the appropriate positions, program the 2nd, 3rd, 4th times as described above.
Be sure to press the SET push-button switch after each time is programmed.
IMPORTANT: Should heater power be interrupted by a power failure or by disconnection of the power cord, heater reverts to MANUAL operation, and all AUTO programming Is erased.
STEP4: Select Automatic Operation
Press AUTO push-button switch. The AUTO indicator light will illuminate.
STEPS: Turn Monitor ON
Press ON OFF push-button switch to position ON.
The RUN indicator light will illuminate to indicate that power has been applied to the heater.
From this point, heater operation is as follow example:
76 F
6:OOAM 9:OOAM 5:OOPM 10:OOPM
1 SffFl
68 F
64 F
Example
3-8 REPROGRAMMING THE MONITOR HEATER
On occasion, it may be necessary to reprogram the
Monitor.
Reprogramming is performed as specified below:
28
MONITOR HEATING SYSTEMS
Section 3: Operation
STEP1: Reprogramming Current Time
(if necessary)
A. Set the TIMER SELECTOR slide switch to position CLOCK SET.
B. Press HOUR and MINUTE push-button switches to program new current time. Set applicable time by watching Clock display.
C. Press SET push-button switch.
IMPORTANT: If SET push-button switch is not pressed, current time will revert to previously programmed time.
STEP2: Reprogramming Automatic Operation
A. Set TIMER SELECTOR switch to appropriate position (1st, 2nd, 3rd or 4th)
B. Press TIME push-button switch.
C. Press CLEAR push-button switch. Time displayed on window will disappear.
D. Using HOUR and MINUTE push-button switches program new desired time by watching the Display Window.
E. Press SET push-button switch.
F. Press TEMP push-button switch.
G. Press CLEAR push-button switch. Set Temperature displayed on Window will disappear.
H. Using UP and DOWN push-button switches program new desired temperature by watching the Display Window.
I. Press SET push-button switch.
3-9 HEAT SENSOR
Heat Sensor is located on the rear of the cabinet. It is recommended to leave the sensor in its original mounted position. However should relocation be necessary, choose a location for the sensor that is not in the path of direct sunlight, drafts or the flow of warm air from the heater. Loosen the screw and release the sensor from the rear of the cabinet.
Fasten the sensor to the wall with the screw.
3-10 MONITOR SHUTDOWN
A simple one-step procedure is utilized to shutdown the Monitor:
Press ON OFF push-button switch to position OFF; the RUN indicator will extinguish.
IMPORTANT: Once heater has shut down, it cannot be restarted until post-purge cycle has been completed. If ON/OFF switch is left in position ON, Monitor operation will automatically restart upon completion of post-purge.
3-11 OUT OF FUEL
During either manual or automatic operation of heater, fuel in the tank may be depleted.
The Monitor (in case of using external fuel tank) is known to be out of fuel when all of the following symptoms are present:
— Burner Status indicator lights blink.
— Absence of flame (visually verified through view plate on wall of Combustion Chamber).
STEP1: Turn Heater OFF
Press ON OFF switch to OFF.
STEP2: Fill Fuel Tank
A. Close shut-off valve at outlet of Fuel Tank.
B. Drain Fuel Tank (from bottom, if possible) to remove all condensation, debris, and old fuel.
C. Fill Fuel Tank with fresh, crystal clear kerosene.
D. Upon completion of stepC, open shut-off valve which was closed in stepA above.
STEPS: Turn Heater ON
Press ON OFF switch to ON. Proceed with normal heater operation.
The Monitor 22 (in case of using capsule fuel tank) is known to be out of fuel as follows:
When the EMPTY indicator light illuminates and flashes, a buzzer will sound for twenty seconds. The burner mode is changed to "Low" automatically, and then, the heater will shut off after 30 minutes.
The remaining burning time is indicated at the
Display Window.
Refueling:
STEP1: Turn Heater OFF
Press ON OFF switch and wait 15 minutes for the heater to cool.
STEP2: Lin Out the Capsule Fuel Tank
Open the tank cover and lift out the capsule fuel tank.
Turn the tank upside down, and remove the fuel cap.
STEP3: Fill the Capsule Fuel Tank
Fill the capsule fuel tank with fresh, crystal clear kerosene by using a siphon.
STEP4: Reinstall the Capsule Fuel Tank
Replace and tighten the fuel cap. To insure proper fuel flow, be sure the cap is secured correctly.
29
MONITOR HEATING SYSTEMS
Section 3: Operation
Install the tank with the arrow pointing forward, and close the tank cover.
STEPS: Turn Heater ON
Press ON OFF switch to ON. Proceed with normal heater operation.
3-12 RECOVERY FROM A POWER FAILURE
The Monitor is equipped with an automatic reset feature which restores (the manual mode of) operation following interruption of power to the heater.
Note, however, that a power-failure automatically triggers a cooling and purge cycle: routine operation will automatically be resumed following purge cycle.
A switch to manual mode is automatic because the absence of power to the microprocessor wipes-out the programmed memory.
To recover from a power failure (automatic mode of operation), proceed as listed below:
STEP1: Program Current Time
STEP2: Program Automatic Time Temperature operation cycles.
STEPS: Return to Automatic operation.
3-13 RECOVERY FROM OVERHEAT CONDITION
The Monitor is protected against damage resulting from an overheat condition by two 110"C (Monitor
22), 115
;
C (Monitor 41) automatic reset thermostats.
In the event of an overheat the thermostats are triggered to cut off the flow of kerosene to the
Burner Pot, the flame is extinguished automatically, and user is alerted to the overheat condition by blinking of the Burner Status indicators.
To recover from an overheat condition, proceed as outlined below:
STEP1: Turn OFF Heater
STEP2: Allow Monitor Heater to cool
NOTE: Be sure that heater is cool to touch.
A period of 30 to 45-minutes should be sufficient to permit heater to cool completely.
STEP3: Unplug Heater
Disconnect heater power cord from wall outlet.
STEP4: Check for Cause of Overheating
NOTE: Overheating is usually caused by objects that impede free air circulation.
Look for debris and other obstructions at front of heater, at Circulation Fan at rear of the heater, and at Flue Pipe tip outside dwelling.
STEPS: Remove Louver Assembly
STEPS: Clean Heater Interior
BEFORE PROCEEDING TO CLEAN HEATER, BE
SURE THAT HEATER INTERIOR IS COOL ENOUGH
TO TOUCH.
With a clean, lint-free, damp rag or other appropriate cleaning material, wipe up all dust, dirt and debris from exterior of cabinet, including exterior of Combustion Chamber and Heat Exchanger.
STEP7: Replace Louver Assembly
STEPS: Reconnect Monitor Heater Power Plug to the Wall Outlet.
STEP9: Turn Heater ON
STEP10: Reprogram Heater Microprocessor
STEP11: Select Mode of Operation
30
CAUTION: If after the completion of recovery procedure, the heater overheats again, something is wrong '
Do not operate heater until problem has been diagnosed and cor reeled.
3-14 RECOVERY FROM BLOWN FUSE
All electrical components of the Monitor heater are protected against power overloads and electrical malfunctions by two 2-amp fuses and a 10-amp fuse. Should fuse blow, the recovery procedure is outlined below:
STEP1: Turn Monitor OFF
STEP2: Unplug heater
STEPS: Remove louver assembly
STEP4: Remove front cover
MONITOR HEATING SYSTEMS
Section 3: O eration
NOTE: As the Frc jver of the Monitor 41 is connected :ie Printed Circuit Board by
Lead Wires, pull the Front Cover to the front side slightly and remove the Connector of the Lead Wires from the Printed Circuit
Board, and then, remove the Front Cover.
STEPS: Locate and replace fuse(s)
STEP6: Reattach front cover
(In case of the Monitor 41, be sure that the connector is connected to the printed circuit board.)
STEP7: Reattach louver assembly
STEPS: Plug heater power cord into wall outlet
STEP9: Turn Monitor ON
STEP10: Reprogram heater
STEP11: Program Automatic operation cycles (if applicable)
STEP12: Select Automatic operation (if applicable)
31
MONITOR HEATING SYSTEMS
Section 3: Operation
32
3-15 OPERATION CONTROL SYSTEM
I/O
M-41 OPERATION TIMING CHART
s
5?
1
1 i i i
OPERATION SW AUTO
SENSOR SW
1
ROOM TEMP
QVERHEAT
| AIR PRESSURE SW
+4T
T ,
+ 2 F
+ 1 F
SET TEMP
1 F
2 F
3 F
4 F
1 i i
1 i
J
i
1
1 i i
1
/
/
/
^
/
___^
\
—
/
^*"
^_^ s
/— '
X
^^
^
/
/
/
L^ -^1
\ s
\
"s^
V^
"*"" _— •*
^^
~i
• — • s^
TIMER
SELECTOR
CLOCK SET
AUTO
RL 7 ( FM
RL 2 ( FM-H
RELAY
COUPLER
RL 5 ( SL
1C 9 ( HIGH
1C 10 ( H-MED
CLOCK
LED INDICATOR
.
BURNER STATUS
HIGH
H-MED
MONITOR LED
•
LOW
AUTO
•
BUZZER fs
»'.°y
Sr
*"*
F^ f"
-7-^H
1=
^r: f"-
°"
!
•
=
iH
— 1
1
—
—
~S
«"Sc
z=;
|
Sfi
g
"* c
—
—
~±
MONITOR HEATING SYSTEMS
Section 3: Operation
33
M-22 OPERATION TIMING CHART i/0
OPERATION SW AUTO
1
ROOM TEMP
AJR Pressure sw
+4F
-t-3F
+ 2 F
+ 1 F
SET TEMP
1 F
2 F
3 F
1
TIMER
SELECTOR
CLOCK SET
RELAY
COUPLER
LED INDICATOR
BURNER STATUS
MONITOR LED
HIGH
H-MED
LOW
AUTO
BUZZER
RL HEATER)
RL 2 FM-H ) '
RL 4 BM )
RL 5 SL !
RL 6 PUMP !
1C 9 HIGH )
1C 10 H-MED )
1C 11 L-MED )
CLOCK
IKr
1
1
I
1
1
i
i
1
i
\
i
?
/
/
/ f>
S
/
s^
^^
\
/
j x'
^ ^
\
/
/
/
^
*^
\
\i
"\_
\
^
1
1
I
—
-
^f.
^
»^
»^
H
—
— 1
-i
^=
—
—
—
—
—
—
—
—
•
—
H-
—
«=
~
—
' tax
r
—
—
MONITOR HEATING SYSTEMS
Section 4: Maintenance
4-1 INTRODUCTION
Heater maintenance is divided into two classifications; periodic maintenance is required to maintain the heater in good operating condition; corrective maintenance is necessary to repair a malfunction.
4-2 PERIODIC MAINTENANCE
The Maintenance Schedule provided in Table 4-1 describes the tasks that must be performed periodically in order to sustain the efficiency of the Monitor
Heating Systems.
At the time of the demonstration or installation, heater maintenance should be discussed with the user; emphasize that a clean heater and proper fuel are the keys to optimum heater operation and performance.
Table 4-1 SUGGESTED MAINTENANCE ACTIVITIES
Activity Material Remarks
Check all fuel lines for leaks and 3 8" OD copper tubing loose connections
Fuel lines must be secure and free of leaks, Replace tubing when necessary.
All exhaust lines must be covered by a cloth insulation cover.
Inspect exhaust lines for leaks or loose connections
Check fuel for water and or other contamination.
If the capsule tank is used on the
Monitor 22 the capsule tank filter should be checked, cleaned or replaced.
Inspect Fuel Pipe for obstruction
Inspect electrical wiring for cracks, signs of deterioration, bare wires and or loose connectors
Fuel color should be crystal clear, if fuel is contaminated, see Corrective Maintenance procedure, paragraph 4-9,
Clean heater
^| WARNING: ^^^^
UNPLUG HEATER BEFORE PRO-
CEEDING. HEATER MUST ALSO
BE COOL BEFORE STARTING.
Clean, lint-free cloth and a mild non-abrasive household cleaning agent. USE ONLY NON-
PETROLEUM DISTILLATE
CLEANERS.
Wipe down exterior of heater cabinet. Vacuum heater interior (if necessary).
Clean Air Circulation Fan (Monthly) Vacuum blades.
fan cage. Wipe fan
Look for cracks, wear, or signs of deterioration; replace if necessary.
Inspect air lines for leaks or loose connections.
Inspect rubber Air Hose at rear of heater.
Clean fuel constant level Valve filter. Inspect fusible link Valve input fitting.
Clean only if necessary, Varify that heater is level.
Clean Kerosene Refer to paragraph 4-5. Procedure is described in paragraph 4-6.
Check Leveling Guide.
34
MONITOR HEATING SYSTEMS
Section 4: Maintenance
Activity
Inspect Combustion Ring, Flame
Sensor Rod and Baffle.
(Suggested frequency every 3 years).
Clean Combustion Chamber (every
3 years)
Inspect air holes in Burner Pot
Clean Igniter
Check air line that interconnect
Combustion Blower and Air Pressure Switch.
Check for carbon build up in fuel inlet going into burn chamber (every year)
CAUTION: If any obstruction is felt remove igniter before proceeding.
Material Remarks
Clean all carbon deposits. Replace if excessively worn or cracked.
NOTE: If any gaskets are torn when Components are removed, the gasket must be replaced.
Vacuum all carbon deposits from interior of chamber.
Use a small, stiff brush or a short length of soft copper wire to clean any blocked holes.
Scrape any carbon deposits from igniter.
Replace air line that is worn, broken or brittle.
Disconnect copper fuel line from burn chamber and clear fuel inlet line by reaming with a solid piece of wire(such as copper,bailing wire.or
coat hanger) which should be able to go in approximately 3" without obstruction.
NOTE: Removing and retightening burner fuel connection must be done when the burner cools down completely. If it is done when the burner is hot, the welding on the fuel joint may break. Fixing torgue for n u t ; 3 0 ^ - 4 0 k g - c m ( 2 6
-35lb-in)
4-3 INSPECT EXHAUST AIR LINES
Verify that all exhaust and air lines are free of leaks and loose connections, as specified below:
STEP1: Remove Protective Cloth
Remove cloth insulation cover(s) from all exhaust lines.
STEP2: Inspection of Exhaust Air Lines
A. Visually inspect both air and exhaust lines for obvious cracks, leaks or loose connections.
Black carbon deposits may be evidence of these leaks.
B. Be sure that all lines are installed tightly and
35
securely, especially at joints.
C. Turn heater ON.
D, Carefully apply a small amount of soapy water
(with a paint brush) to the surface areas of the air exhaust lines.
Any leaks that may exist will be readily identified by the appearance of bubbles.
STEPS: Return to Operating Condition
A. Turn heater OFF.
B. Dry all lines with paper towels.
C. Repair any leaks that have been found (if necessary, replace the tubing).
D. Replace cloth insulation covers.
MONITOR HEATING SYSTEMS
Section 4: Maintenance
4-4 VERIFY IGNITER OPERATION
Visually inspect Igniter Operation
WARNING:
HEATER IS OPERATIONAL DURING THIS INSPEC-
TION. AVOID DIRECT CONTACT WITH ANY
HEATED OR ELECTRICAL COMPONENT.
STEP1: Prepare (or Inspection
Remove Louver Assembly.
STEP2: Visual Inspection
A. Turn heater ON.
B. Look (downward) through window on the Combustion Chamber. Verity that igniter is glowing,
If igniter does not glow, something is wrong.
Refer to the Troubleshooting Chart in Section 6 of this Service Manual to diagnose the problem.
CAUTION: If igniter is broken,do not operate the
"ON OFF" switch button repeatedly.
STEPS: Reassembly of Heater
Turn the heater OFF and replace the Louver Assembly.
4-5 CLEAN FUEL CONSTANT LEVEL VALVE FIL-
TER
Contaminants are trapped by the filter to prevent them from clogging the Fuel Constant Level Valve.
The filter, itself has a great number of small pores.
Whenever a filter is torn or disfigured (enlarged pores), it should immediately be replaced.
Inspect and clean the filter as indicated by the procedure below:
CLOSE FUSIBLE LINK VALVE ON M-22 OR CLOSE
SHUT-OFF VALVE OF THE EXTERNAL FUEL TANK
ON M-41 TO AVOID DRAINING ALL FUEL FROM
TANKS.
NOTE: Power should be OFF during the performance of this procedure.
STEP1: Disassembly
A. Using a phillips head screwdriver, unscrew the screws holding the rounded diamond-shaped cover plate at the bottom of the Fuel Constant
Level Valve. Remove the cover plate.
NOTE: Position a six inch U shaped piece of metal or cardboard under strainer cover to drain fuel into a pan.
B Carefully remove the rubber gasket which is located behind the cover plate.
STEP2: Inspection and Cleaning
A. Pull the filter straight out of the fuel reservoir.
B. If the filter is dirty (but undamaged), rinse the filter in fresh, clean kerosene to remove all particles. Replace damaged filters.
C. To drain off upper portion of fuel constant level valve, back out Phillips head screw which is located slightly above and to the left of filter cover plate. (See Fig4-1)
STEP3: Reassembly
A. Push the (new or cleaned) filter back into the bottom of the fuel reservoir.
B. Replace both the rubber gasket and the cover plate. (Take care to properly align the screw holes in the gasket and cover plate).
C. Wipe up any spilled fuel.
M-41 M-22
Figure 4-1 CLEAN FUEL CONSTANT LEVEL VALVE
36
MONITOR HEATING SYSTEMS
Section 4: Maintenance
4-6 CLEANING FUSIBLE LINK VALVE INTAKE FIT-
TING ON M-22
At periodic intervals, the fitting on the Fusible Link
Valve should be cleaned to prevent any accumulation of foreign materials from clogging the inlet. This is accomplished as follows:
UNPLUG THE HEATER. POWER TO THE HEATER
SHOULD BE OFF DURING THE PERFORMANCE OF
THIS PROCEDURE.
STEM: Close off Fuel Supply
A. Shut off fuel at the Storage Tank or remove fuel from the fuel sump tank with siphon and syringe if using the capsule fuel tank.
B. Manually turn handle to close Fusible Link
Valve.
NOTE: Place paper towels underneath the Fusible
Link Valve to catch any spilled fuel.
STEP2: Clean Valve
A. Loosen hex nut on Fusible Link Valve inlet fitting at rean of the heater. Disconnect the copper tubing which delivers the fuel from the storage or the fuel sump tank.
B. Using a small, straight piece of wire carefully and slowly ream-out the inlet fitting on the
Fusible Link Valve.
Avoid scratching the inside wall of the fitting.
With a cotton swab, wipe the interior area of the inlet fitting.
STEP3: Reconnect Fuel Line
A. Reconnect the copper tubing to the intake fitting and tighten the hex nut.
B. Turn ON fuel at Fusible Link Valve and at storage tank or fuel sump tank.
C. Check for leaks.
4-7 CORRECTIVE MAINTENANCE
The two procedures below are remedies for very generalized types of operating difficulties.
4-8 REPLACEMENT OF FUSES
A short circuit or similar electrical malfunction could cause the fuse to blow. Troubleshoot the cause of the blown fuse.
Replace the fuse as follows:
DO NOT REPLACE FUSE WHILE POWER IS ON.
STEP1: Removal of Fuse
A. Unplug heater. Remove Louver Assembly and
Front Cover.
B. Remove the fuse from fuseholder on the Printed
Circuit Board.
STEP2: Installation of New Fuse
A. Install a new fuse into the fuseholder. The fuse must be a 250-V, 2 amp or a 250-V, 10 amp type as marked on the printed circuit board.
B. Replace the Front Cover and the Louver
Assembly and plug the heater into the wall outlet.
IMPORTRNT: Whenever the heater is unplugged, the Microprocessor must be reprogrammed when power is restored.
4-9 FUEL CONTAMINATION
Fuel contamination is often difficult to diagnose, even though it will adversely affect heater operation and performance. The best course of action to take when fuel contamination is suspected is to examine all of the system's fuel filters, beginning with the fuel storage tank. If a Monitor Kerosene Lifter is part of the fueling system, examine and clean that unit s filter, as well as the filter located in the Fuel Constant Level Valve. When it has been determined that water or some other contaminants have infiltrated the fuel, the following action must be taken:
WARNING
37
BEFORE PROCEEDING FURTHER, UNPLUG THE
HEATER.
STEP1: Remove Contamination
A. Shut OFF the fuel supply at the storage tank or at the Fusible Link Valve.
B. Drain off the contaminants from the fuel storage tank or the fuel sump tank (M-22). Fill with fresh, clean fuel.
STEP2: Clean the Heater
A. Clean fuel constant level valve filter and filter compartment.
B. Remove the Louver Assembly and Solenoid
Pump on the constant level valve. Clean the
Solenoid Pump filter.
STEPS: Reinstall Cleaned Components
A. Replace the components correctly and install new gasket.
B. Turn on the fuel at the storage tank and at the fusible link valve, and apply power to the heater.
If problem still exists and contaminated fuel is suspected it can be checked by
A, Shutting off the fuel supply at the storage tank and at the fusible link valve.
B, Drain off fuel at constant level valve.
C. Disconnect fuel line at back of heater and hook up a 5 gallon quick tank with proven good fuel.
D. Test run heater to see if problem clears up with use of new fuel.
MONITOR HEATING SYSTEMS
Section 5: Servicing
5-1 INTRODUCTION
Servicing is required when the Monitor Heater is not running at proper efficiency. This section covers possible causes and corrective procedures for efficiency loses.
Signs of improper heater efficiency and performance would be:
— Yellowish lazy flame
— Smoke from flue pipe exhaust
— Heavy soot and carbon build up in combustion chamber
— Lowered heat output.
5-2 MEASUREMENT OF FUEL FLOW RATE
Fuel flow rates are preset and sealed. These rates should not and we recommend they do not be readjusted.
5-3 REMOVAL OF WATER DEPOSITS AND
CONTAMINANTS FROM FUEL CONSTANT
LEVEL VALVE AND FUEL LINES
NOTE: Disconnect the Monitor from power supply
(unplug) before proceeding.
1. Use a syphon pump and a syringe to drain off any fuel in the fuel sump (in case of capsule tank use on the Monitor 22).
2. If using separate tank on the Monitor 22, shut off fusible link valve. On the Monitor 41 shut off valve of separate tank.
3. Bend a piece of sheet metal or cardboard into a
U shape and place it under the fuel constant level valve strainer cover to drain bad fuel into a 1-2 liter pan. (Figure 4-1)
A. Remove strainer cover and drain.
B. With strainer cover removed, inspect, clean and or replace strainer if damaged.
C. Remove drain port screw and drain.
D. Replace strainer, cover and screw.
E. Open fusible link valve or shut-off valve to refill system with fresh crystal clear kerosene.
F. Repeat steps 1-3 until all contaminated fuel is drained off.
4. Remove fuel feed pipe from burner pot and solenoid pump, and drain fuel into pan.
5. Once lines are clear, reconnect fuel feed pipe, turn operation switch ON and start a test run.
NOTE: Removing and retightening burner fuel connection must be done when a burner cools down completely. If it is done when a burner is hot. the welding on the fuel joint may break. Fixing Torgue for nut:30
--40kg • cm(26~35ls.in).
5-4 CLEANING THE BURN CHAMBER & BURNER
POT
Under normal running conditions, soot will not deposit in great quantities in side the burner, and a light covering of soot will not affect the performance of the unit thus it need not be cleaned. However, if heavy soot built up does occur the unit should be opened and cleaned.
The burner is assembled using gaskets to maintain its air tightness. If these gaskets leak, the extra air can cause a serious soot problem and or exhaust gases to escape into the area being heated.
NOTE: If any gaskets are torn when components are removed.
If cleaning is necessary, use the following method:
1. On the Monitor 22
A. Remove louver assembly.
B. Remove front cover.
C. Remove top cover and lead wire connectors.
D. Remove front bracket and top bracket to cover combustion chamber.
E. Remove combustion chamber cap.
F. Remove service panel.
G. Remove baffle from within combustion chamber.
H. Remove flame detector rod.
I. Remove burner cap.
2. On the Monitor 41
A. Remove louver assembly.
B. Remove front cover and lead wire connectors.
C. Remove top cover.
D. Remove front bracket to cover combustion chamber.
E. Remove service panel and chamber cap.
F. Remove Flame detector rod.
3. Turn counter-clockwise to remove combustion ring.
4. Use wire brush to clean inside of combustion chamber.
Vacuum and wipe clean with a waste cloth.
5. If tar is present on the burner bottom, remove the tar by using a flat-bladed screw driver or wire brush,then clean the area by using a vacuum cleaner etc.
NOTE: Make sure all air inlet openings are clear.
MONITOR HEATING SYSTEMS
Section 5: Servicing
When cleaning the inside of the burner pot, remove the igniter and change the burner cloth by the following procebure.
On the Monitor 22
A. Apply glue(P Na8217) on the burner bottom as shown in Figure5-1.
Figure 5-3 Figure 5-4
C. Apply glue at all 4 corners of Burner Cloth as Shown in Figure 5-5.
Figure 5-1
B. Put the burner cloth on the burner bottom, afterwards press and straighten out the burner cloth so that it is glued flat and even on the burner bottom.
On the Monitor 41
A. Apply glue arround the burner cloth as shown in Figure 5-2.
Figure 5-5
Figure 5-2
B. As shown in Figure 5-3 and 5-4, insert the
Burner Cloth narrow between the Nozzle
Collar and the Igniter Shield, then push the
Burner Cioth, using your fingers or a screw driver, so that it slips in under the Nozzle
Collar. Afrerwards press and straighten out the Burner cloth so that it is glued flat and even on the Burner bottom.
NOTE: In some cases, pulling out the Fuel Nozzle and Collar may make this procedure easier.
NOTE: The Burner Cloth is not symmetrical in shape, therefore make sure to place it in the correct position so that the wider side of the cloth is at left side of the Igniter
Shield as shown in Figure 5-5.
9. Combustion ring may deform and deteriorate after several years use and should be cleaned and inspected before reinstallation. If combustion ring is warped, has cracked or is deteriorating excessively it should be replaced.
10. When reassembling the unit check that combustion ring is positioned whit the correct side up and is sitting squarely on all three support screws(M-22) or pins(M-41) inside the burner pot.
11. Reassemble by reversing the procedure followed during disassembly.
39
MONITOR HEATING SYSTEMS
Section 5: Servicing
NOTE Make sure the position of flame detector rod is centered between combustion ring and burner pot before reassembling chamber cap.(See Figure 5-6)
Flame Detector Rod
Combustion Ring Assy
_Combustion
Chamber
M-41: 4mm (0.16") or more
M-22: 3mm (0.12") or more
Burner
Pot -
Figure 5-6
5-5 CLEANING THE FUEL INLET
When cleaning the combustion chamber and the burner pot, the fuel inlet nozzle should also be cleaned. This can be done as follows:
1. Disconnect copper fuel line at burn chamber.
Push a piece of wire (about the same size as the I.D. of fuel inlet pipe) into the fuel inlet nozzle.
If obstruction is felt twist wire back and forth (to brake up soot and carbon) so that wire ultimately penetrates igniter shield.
40
MONITOR HEATING SYSTEMS
Section 6: Troubleshooting
Monitor 22/41 Resistance values
COMPONENT
Igniter {connector B B)
Power Transformer — Primary (connector H H)
Power Transformer -Secondary (connector L L)
Power Transformer - Secondary (connector M M)
Damper Solenoid (connector I I)
Resistor (connector G G)
Circulation Fan (M-41:WH & BK, M-22:RD & BK)
Circulation Fan (M-41:WH & GR, M-22:RD & YL)
Circulation Fan (M-41:BL & BK, M-22:GR & BK)
Circulation Fan (M-41:BL & GR, M-22:GR & YL)
Combustion Blower (M-41:WH & GR, M-22:BK & BK)
Combustion Blower (M-41:GR & OR)
Thermistor (connector Q Q, at 77 F)
Fuse 2A (read with fuse out)
Fuse 10A (read with fuse out)
Solenoid Pump (coil)
APPROX.
M-22
16.8
97
824
1.3
4,600
68
310
365
270
210
22
-
10,000
0.1
0.01
688
OHMS
M-41
12.7
97
824
1.3
4,600
91
120
190
260
200
78
92
10,000
0.1
0.01
695
DISCONNECT HEATER FROM POWER SOURCE
BEFORE MAKING ANY RESISTANCE TESTS.
41
MONITOR HEATING SYSTEMS
Section 6: Troubleshooting
Igniter
Power Transformer
(primary side)
Power Transformer
(secondary side)
Combustion Blower
High Speed
Combustion Blower
Low Speed
Resistor
Monitor 22/41 Component Voltage Readings
COMPONENT
Thermistor
Thermistor
Air Pressure Switch
Overheat Protector Closed
Air Pressure Switch
Overheat Protector Open
Damper Solenoid
Solenoid Pump
Circulation Fan High Speed
Circulation Fan Low Speed
READING TAKEN AT
Q on PCB Sensor disconnected
Q on PCB Sensor connected
Connector J
Connector J
I on PCB
K on PCB
GR to BK BK to RD (M-21)
BL to BK BK to WH (M-40)
YL to RD GR to YL (M-21)
GR to WH BL to GR (M-40)
B on PCB
H on PCB
Connector L
Connector M
f on PCB
F on PCB
(RL3
is
OFF)
G on PCB
120
110
92(M-22)
88(M-41)
18(lv1-22)
22(M-41)
110
110
110
110
110
110
AC DC
5
1.6-3.3
110
0
105
105
11
42
MONITOR HEATING SYSTEMS
Section 6: Troubleshooting
8 1
§
8
S
|a
II
3 f
43
MONITOR HEATING SYSTEMS
Section 6: Troubleshooting
GENERAL CHECKS
la BOWM available in waJI outl»t?
la Dower Plug MaorMd in wall outlet?
Has there been a power interruption? [Display
Hot Circulation Fan Moppetf?
la fuel in tank? Tank vahw opwi?
Has Fuel ComUnl Lavel Valve Set Lever raiMd and loweredT
Is Opention Switch on?
SYMPTOM | | CHECK1 | I RESULT I I CHECK2 | | RESULT I I CHECK3 I I RESULT | | CHECK* I I RESULT.)
| REASON | | CORRECTIVE ME
I
Extinguished I—I It Fual constant LJ Ho. tsoon aftor I | Lavet Value I I I -J
*-I Flame doe. LJ ^ fuel lira length
uFWi i '»'«•(. cf unit placed
5. JpooHlame^ouna^t^afri^^^^^l
| ri» not a faiture, but ie apJ to occuri \—
•I Failure ot ulenoiQ pi
J [sSS.."
H
| FMNltak.
It Unplug net
2 Ftemove at or determii
3. Replaca ci
Failure at circuit board.
Cl Wiring.
|—^ Replace solenoid pump.
J-l-
I SYMPTOM 1 [ CHECK1 I j RESULT [ f CHECK2 J [ RESULT j | CHECKS [ [ RESULTJ [ CHECK4 [ [ RESULTj [ CHECKSj | RESULT [ |
CORRECTIVE MEASURE
Combustion
•noise i; mmif soonaner
Igniting la Igniting ionn?
( Usually 0.5-t
SYMPTOM
CHECK1
The Ovetheat
Thermostat is activated
Is window curtain too !
close to the fear of unit?
Is Circulation
-Fan Guard dusty?
REASON
Curtain or other obstruction covers circulation air inlet.
Obstacle covers circulating air outlet.
CORRECTIVE MEASURE I
Clean guard.
Keep curtain from unit.
Remove obstacle.
Failure of RGB
H
-\
Circulation fan failed.
Incorrect wiring.
H
H
H
Replace or check P.C.B
Replace Fan Motor.
Repair or replace wiring.
I
I
I
| SYMPTOM | | CHECK1
'*| No operation. |^ 3oe
3
^^_^^^_^^J 1 in the disp lay
1 window?
1
1 Plug m AC cord. 1
| RESULT | CHECK2 |
1 1 TP3? 1
1 If problem is found to be in PCB, do not attempt to repair, replace and send PCB thru your distributor to MPI for repair.
(On W-22) i
YBSi
rTl
ls there fuel?
h
1 1
Press the operation button switch to
ON pos tion.
1
I
1
|
CHECKS CHECK4 | | RESULT | | CHECKS "| | RESULT | REASON
1 [
CORRECTIVE MEASURE
M m
J Failure of Trans- 1 I Replace franslormer.
J Failure of Diode i •— J Replace Diode.
1 nA.r»7 ^^^^^
Failure of Capacitor |-- -_ ] Replace capacitor
H
R I
. '" 1
^^^^
L
1 Failure of Capacitor L^^J Replace capacitor n ca i __
J 1
1
1 1
1 1 does output of Tps 1 1 1 turn tnto High f*om 1
Failure of comparatadClS' 1 1 Replace comparata.
^
Failure of zener 1 1 diode iZDlL | |
1 ai ure o Capacitor L^J Replace capacitor.
J Faikire o t r a n s i s t o , 1 1
neD
, ace translslot
(On M-22)
Remove the connector of operation ctf- \
1
T2 pin and T7 pin on PCB. |_
Failure of capacitor ^.J
ReDlace caoac
, tOf iri7i 1
J^
No
L— . |
S
temperature -pi No. I-M Does heater —-J Yes. 1— -J Failure of operation 1 Replace operation circuit board.
1 Circuit boafd. ^^^^.
U No 1— •4 Failure of resonator L^^J Replace resonator.
Move the Timer Sele-
1 r 't 1
" '"' \
H
Failure of resistor *"H
R
«P
|ac e 'esiBtor
J Failure of micro- 1 1
R
REASON
CHECK2 SYMPTOM | CHECK1 | RESULT on preheat?
H
Nn
NO.
at coil of relay
[ RESULT |
CHECKS
| RESULT J | CHECK4
| RESULT | | CHECKS ] | RESULT | orocsrasor IC1
Failure of IC3.
I
y
1
1 r*
RL1 .
Fuse F2 open.
L tgniter open.
Does combustion during prepurge and igniting?
(3 there l2Vdc
RL4' during prepurge and
CORRECTIVE MEASURE
R 1 ce 1C
~
Replace fuse.
—
Replace igniter epiace crop ocessor.
— i i i '
Jij
i
switch, worfc noc-
J I i — 1 — r ~
(
S i
_ processor IC1 .
Failure of IC5.
RL4 .
blower
Incoirect wiring of comtMistion blower.
Failure of resistor
In correct wiring of resistor pressure switch.
Rubber hose is blokad on discorrected.
L
Incorrect wiring.
Dlower
—
correct wiring.
U
Replace resistor.
~
correct winng.
.
1
Replace air pressure switch.
—
Clear and or correct rubber hose.
~
Correct wiring.
CORRECTIVE MEASURE
I SYMPTOM I I CHECK1 I | RESULT | | CHECK2 | [ RESULT | | CHECK3 | [ RESULT | | CHECK4 [ | RESULT | | CHECKS | [RESULT ]
REASON is there 12Vdc at coil of relay flL6 during igniting.
•
A Yas r™
Does solenoid dunn, «„,„„,?
•1 No r
m
Failure of relay
RL6 .
-
Failure of diode
02
L
Failure of solenoid pump.
•4 Yes p-
Failure of fuel supply parts.
H I* |-
Is transistor
Qt ON during
1
-
-
Failure of microprocessor ICl .
Failure of iCB i
No
i
-
Failure of IC7
Failure of 1C
IC6.
IC3
Failure of resistor iR69l
-
1
Failure of transistor
0,
Failure of diode
(D13I.
^^^ Reoiace relay
• • J Replace diode.
— ^ Replace solenoid pump
^^ Check fuel auoply parts.
^••J Replace microprocessor.
-^-J Replace 1C.
1
— 1 Replace 1C.
i| Replace 1C.
M
Replace resistor
_~^J Replace transistor
^~J Replace diode.
SYMPTOM
^^^ ^^^^ ^^ r~ j
IC2 $ pin.?
For testing purposes - A flame detector rod bypass circuit can be made up. consisting of 2 insulated alligator ci ps. 2-6" pieces of nsulaied
These components are to be soldered together in sequence as shown in
Once the bypass circuit is made the unit is comes on. the O and N pins are disconnected off the PCS and replaced with the Bypass crcuit, The unit should then continue functioning as thougn it had a good flame inside tne burn chamber and sen/ice
(Note - warning after all tests are completed.
replace original flame rod wires as it is a vital safety feature. ;
C^] H
A y
A v
A v (^]
^\
CLIPS
^-^
1 1 1 i 1
CHECK4 [ | RESULT | [ CHECKS | | RESULT | | REASON ]
CORRECTIVE MEASURE
,R5 6 . 7 8,. 1 —-.,„. 1
H
Fuse F3 open. | ' 1 ^Wace fuse.
Fmlure of capacitor _J
R (ace capacitor
.
^~1
1
Failure of resistor II
Re(}|ace fas|3[or
;Rl.n.)2.l3.24.25i. \ 1
M
— — — _l___Zi! * l
Fail.ira flf rB^olnf 1 1 nrDlOCO r(?5l3tOr
_
Failure of diode | 1 Replace diode.
(D17) 1
Failure ol capacitcx 1 1 Replace cauacitw
-
Failuta of IC5 1 1 Beolace 1C.
Failure of mK.oproces.or. | | Replace microprocessor.
—
-
1
Failure of wiring for I J Correct wiring, flama sensor and around. 1 1
Incorrect installation — ^J Correct installation.
ConnectlOKfl r tor at g pins, and men. set temperature from Low to High.
Is circulation fan motor able to change 3peed?
I RESULT | { CHECKS | | RESULT | | REASON | | CORRECTIVE MEASURE
1 lC9.10.il .
_J Failure of resistor
1 R63. 31 32.63.34
H
Failure of solenoid pump.
Failure of relay
RL2 .
M
Reolace 1C.
M
Replace resistor
K
Replace solenoid pump.
-L
Replace relay
Failure of circulation fan motor
Failure of relay
RL3.4.5 .
Failure of combustioi blower.
Failure of damper solenoid.
Failure of resistor
'R2,3).
Failure of capacitor
IC9.IO).
(
Failure of res iR41
-
LJ Failure of cai
| 'C11.C12-.
Failure of microprocessor.
H
Replace circulal fan motor.
J-C
J-C
,^_J Replace c
I blower.
H
Replace c
3
°'°"°' d
-
Replace resistor
Replace capacitor.
-L
Replace resistor.
Replace capacitor.
M
Replace microproce-
_^
MONITOR HEATING SYSTEMS
Section 6: Troubleshooting
Digital Display
c n i
I- U I c n c
L U J n r u u
/ _/
/ L
INDICATION OF FAILURE MODE
The Reason of Indication
Trouble Point
At pre-purge, Flame rod is sensing flame Flame sensing circuit, grounded when there should be none. flame rod or pinched wire.
After power on, power supply to the microprocesser timing circuit is incorrect.
Timer clock circuit bad or power source to unit above or below acceptable levels.
At starting of operation, the circuit to drive Solenoid Pump control circuit
Relay RL6 of Solenoid Pump is malhas a malfunction.
functioning.
When unit is shut off either manually or automatically, flame rod does not detect
Driving circuit of RL6 or excess fuel in burner pot flame out within 300 seconds.
54
55
MONITOR HEATING SYSTEM
Section 7: Electrical System
Schematics
TTT? si
MONITOR HEATING SYSTEM
Section 7: Electrical System
Printed Circuit Wiring Diagram
CONNECTION OF LEAD WIRES
OPERATION
an
TIMER
SELECTOR
TIME!
TEMPI
Panel Printed Wiring Board
TIME/TEMP SET
CD a a
RUN AUTO EMPTY BURNER STATUS TEMP
i 1 i 1 i 1 / / / / / AM
I I I I I
Blower for
Combustion
Resistor
Blower for
Circulation
Fan
Thermostat
figure 7-1 Monitor 41
Junction Box
Power
Cord
56
MONITOR HEATING SYSTEMS
Section 7: Electrical System
Printed Circuit Wiring Diagram
DC12V
CONNECTION OF LEAD WIRES
HT)
T8
T9
OPERATION SELECTOR
T
|
MFa
TIME
i i r i i i i i i
1
— " — ' IbMPCD
/TEMP SET
=D a c
ID
Panel Printed Wiring Board
S
T1
T?
T3
T4
T5
Tfi
1
2
3
4
5
6
R
RUM Airrn FMPTY BURNER STATUS TEMP
= = «= / / / / /
AP
"
SET ROOM
Lamp Printed Wiring Board
J~
_r~
=Ta b r, d g f e
, 1 Short
' ' Terminal
cO
K lo o ol
J
fol
Main Printed
Wiring Board
Empty Lamp Switch
(Float Switch)
n
Power Transformer
Blower for
Combustion
B
Resistor toj
F fo] E fo] [oj
L°J G
Blower for
Circulation
c D
D B H
M
A fo]
|o|
Fan
Thermostat
B
L
1
\
L
>
' ^
Heater
4-
"ol t
^
-»•
E
Junction Box
Power
Cord
figure 7-2 Monitor 22
57
MONITOR 41
SERVICE PARTS LIST
DESCRIPTION
SPILL TRAY
LEG
AIR SUPPLY HOSE (A)
AIR SUPPLY HOSE (B)
CONSTANT LEVEL VALVE
C.LV.STRAINER
STRAINER GASKET
FUEL PIPE
SOLENOID PUMP
GASKET (1)
BURNER
BURNER CLOTH
ROPE GASKET
HEATER
GASKET (3)
IGNITER BRACKET
HEATER COVER PACKING
IGNITER COVER
FLAME DETECTIVE PLUG
PLUG PACKING
FL PLUG BRACKET
GASKET (4)
HEAT EXCHANGER ASSY
GASKET (6)
EXHAUST DUCT
O-RING (P39)
OIL SUMP PIPE
JOINT SEAL PACKING
FUEL NOZZLE
FUEL NOZZLE COVER
BASE TRAY RETAINER
WINDOW GASKET
WINDOW FRAME GASKET
WINDOW GLASS
WINDOW BASE GASKET
CHAMBER GASKET
COMBUSTION CHAMBER
COMBUSTION RING ASSY
CHAMBER GAP
CONDENSER (2.5 ^FD)
BLOWER ASSY
DAMPER SOLENOID ASSY
SUCTION CASE A ASSY
SEAL PACKING
MOTOR FOR COMBUSTION
PWB ASSY
PWB SPACER CLIP (A)
PWB SPACER CLIP (B)
MICROPROCESSOR
RELAY (A)
RELAY (B)
BUZZER
FUSE (250V 10A)
FUSE (250V 2A)
6352
6353
6404
6124
6125
6405
6350
6317
6349
6356
6321
6322
6323
6406
6324
6144
6348
6362
6134
6135
6202
6168
6169
6203
6172
6173
6119
6196
6313
6314
6122
6123
6176
6315
6164
6363
6358
6311
6115
6402
6354
6403
6355
PART
NO.
6400
5019
6301
6302
6303
6304
6344
6305
6306
6357
6401
ITEM
NO.
1
23
24
25
26
27
19
20
21
22
15
16
17
18
12
13
14
8
9
10
11
4
5
2
3
6
7
28
29
30
31
32
33
34
49
50
51
52
45
46
47
48
53
54
39
40
41
42
35
36
37
38
43
44
MONITOR 41 SERVICE PARTS LIST
68
69
70
71
72
73
74
ITEM
NO.
55
56
57
58
59
60
61
62
63
64
65
66
67
80
81
82
83
84
75
76
77
78
79
85
86
87
95
96
97
98
99
100
101
102
103
104
105
106
107
108
88
89
90
91
92
93
94
DESCRIPTION
CAPACITOR (1.8 //FD)
TR ARRAY (M54563P)IC3
PHOTO COUPLER(IC9~~11)
POWER TRANSFOPMER
AIR LINE
AIR PRESSURE SW
RUBBER BUSH
OVER HEAT THERMOSTAT
FAN THERMOSTAT
CORD CONNECTOR
JUNCTION BOX COVER
POWER SUPPLY CORD
CORD BUSHING
LEVEL GUIDE
CARRYING HANDLE
SENSOR ASSY
SLIDE SWITCH ASSY
SLIDE SWITCH COVER
SLIDE SWITCH PANEL
SLIDE SWITCH KNOB
JOINT PIPE
AIR DAMPER (E)
AIR DAMPER (S)
AIR SUPPLY HOSE ASSY
EXHAUST OUTLET CAP
AIR PORT 0 RING
PIPE HOLDER
HOSE BAND
AIR OUTLET CAP
FLUE PIPE ASSY
SLEEVE FLANGE SET
FAN
CIRCULATION MOTOR
BLOWER GUARD
WIRING GUARD
UNDER COVER
LOUVER
CONTROL COVER
FRONT COVER
LAMP PANEL
SWITCH ASSY
LAMP ASSY
TOP COVER
RESISTOR
CABINET ASSY
UNION NUT
WALL CLAMPS
SCREW SET FOR FLUE PIPE
CARTON BOX
CUSHION SET
OWNERS GUIDE
TOUCH-UP PAINT(WHITE)
GLUE
TOUCH-UP PAINT (GREY)
6208
4004
6407
6408
6145
4014
4016
4006
4008
4805
6147
6148
6075
6330
6331
6347
6332
6409
6410
6411
6412
6154
6155
6337
6338
6413
6345
6194
6197
6414
6342
1148
8216
8217
8219
6152
6137
6032
6139
4833
6037
6138
6186
6205
6206
6207
PART
NO.
6340
6187
6204
6132
6326
6343
6136
6327
58
MONITOR HEATING SYSTEM
EXPLODED VIEWS AND PARTS LIST
59
MONITOR 41 EXPLODED VIEW
,1U2) Screw Set for Flue Pipe
Carton Box
Cushion Set
Owners Guide
Touch-up Paint (White)
Glue
Touch-up Paint (Grey)
MONITOR 22
SERVICE PARTS LIST
ITEM
NO.
13
14
15
16
17
18
19
7
8
9
10
11
12
1
2
3
4
5
6
39
40
41
42
43
44
35
36
37
38
29
30
31
32
33
34
25
26
27
28
49
50
51
52
45
46
47
48
20
21
22
23
24
53
54
55
56
57
58
PART
NO.
6126
6127
6181
6128
6129
6130
6131
6132
6201
6134
6135
6202
6168
6169
6203
6172
6173
6170
6187
6204
6137
6107
6184
6109
6110
6164
6111
6112
6182
6113
6114
6200
5019
6101
6102
6103
6104
6105
6106
6189
6108
6122
6123
6176
6124
6125
6068
6069
6115
6116
6195
6117
6191
6118
6119
6196
6120
6121
DESCRIPTION
SPILL TRAY
LEG
AIR SUPPLY HOSE (A)
AIR SUPPLY HOSE (B)
FUEL PIPE
FUSIBLE VALVE
CONSTANT LEVEL VALVE
C.LV.STRAINER
STRAINER GASKET
SOLENOID PUMP PACKING
SOLENOID PUMP
OIL SUMP PIPE
JOINT SEAL PACKING
FUEL SUMP
GASKET (1)
BURNER
BURNER CLOTH
GASKET (2)
GASKET (3)
HEATER
IGNITER BRACKET
HEATER COVER PACKING
IGNITER COVER
FLAME DETECTIVE PLUG
PLUG PACKING
FL PLUG BRACKET
GASKET (4)
HEAT EXCHANGER ASSY
GASKET (6)
EXHAUST DUCT
O-RING (P39)
WINDOW GASKET
WINDOW FRAME GASKET
WINDOW PLATE
WINDOW GLASS
WINDOW BASE GASKET
COMBUSTION CHAMBER
COMBUSTION RING ASSY
BURNER CAP
BAFFLE ASSY
CHAMBER GASKET
CHAMBER CAP
POWER TRANSFORMER
PWB ASSY
PWB SPACER CLIP (A)
PWB SPACER CLIP (B)
MICROPROCESSOR
RELAY (A)
RELAY (B)
BUZZER
FUSE (250V 10A)
FUSE (250V 2A)
CAPACITOR (1.5^FD)
TR ARRAY (M54563P)IC3
PHOTO COUPLER(IC9~11)
CORD CONNERCTOR
AIR LINE
AIR PRESSURE SWITCH
MONITOR 22 SERVICE PARTS LIST
ITEM
NO.
70
71
72
73
74
66
67
68
69
75
76
77
59
60
61
62
63
64
65
78
79
80
81
82
83
84
95
96
97
98
99
100
101
102
103
89
90
91
92
93
94
85
86
87
88
104
105
106
107
108
109
110
111
112
113
114
115
116
6197
6215
6175
1148
8216
8217
8219
6160
6161
6180
6192
6193
4004
6209
6145
4014
4016
4006
4008
4805
6147
6148
6149
6210
6211
6154
6155
6156
6212
6158
6159
6179
6165
6178
6177
6162
6213
6345
6194
6214
PART
NO.
6136
6151
6152
6163
6139
4833
6037
6138
6186
6205
6206
6207
6208
6140
6141
6142
6143
6144
DESCRIPTION
RUBBER BUSH
OVER HEAT THERMOSTAT
FAN THERMOSTAT
AIR PACKING SET
POWER SUPPLY CORD
CORD BUSHING
LEVEL GUIDE
CARRYING HANDLE
SENSOR ASSY
SLIDE SWITCH ASSY
SLIDE SWITCH COVER
SLIDE SWITCH PANEL
SLIDE SWITCH KNOB
BLOWER ASSY
BLOWER MOUTH PACKING
DAMPER SOLENOID ASSY
SUCTION CASE
SEAL PACKING
BLOWER GUARD
CIRCULATION MOTOR
FAN BLADE
WIRING GUARD
WIRING HARNESS(FAN MOTOR)
JOINT PIPE
AIR DAMPER (S)
AIR SUPPLY HOSE ASSY
EXHAUST OUTLET CAP
AIR PORT O RING
PIPE HOLDER
HOSE BAND
AIR OUTLET CAP
FLUE PIPE ASSY
SLEEVE FLANGE SET
UNDER COVER
LOUVER
FRONT COVER
SWITCH ASSY
LAMP ASSY
TOP COVER
LAMP PANEL
FUEL TANK COVER
FUEL TANK ASSY
FUEL TANK CAP
FLOAT SWITCH
FLOAT SWITCH PACKING
OIL FILTER
RESISTOR
CABINET ASSY
UNION NUT
WALL CLAMPS
BASE TRAY RETAINER
SCREW SET FOR FLUE PIPE
CARTON BOX
CUSHION SET
OWNERS GUIDE
TOUCH-UP PAINT(WHITE)
GLUE
TOUCH-UP PAINT(GREY)
60
MONITOR HEATING SYSTEM
EXPLODED VIEWS AND PARTS LIST
92
61
MONITOR 22 EXPLODED VIEW
Screw Set for Flue Pipe
Touch-up Paint
(White)
Glue
Touch-up Paint
(Grey)