Eaton Simple Electrical ground and test device lower terminals Owner's Manual
Advertisement
Advertisement
IB131018EN
Effective January 2017
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
Contents
Description Page
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2. Description . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3. Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Appendix A - Front view . . . . . . . . . . . . . . . . . . . . 8
Appendix B - Side view . . . . . . . . . . . . . . . . . . . . 9
Appendix C - Control scheme . . . . . . . . . . . . . . 10
Appendix D - Outline drawing . . . . . . . . . . . . . . 11
Appendix E - Breaker code plate reference . . . . 12
Appendix F - How to make breaker plates . . . . . 16
Appendix G - How to make cell plates . . . . . . . . 17
SEG&TD
For use in type VCP-W switchgear rated up to 15 kV, 40 kA bottom terminal set version
IB131018EN
Effective January 2017
CAUTION
BECAUSE OF THE UNIQUE APPLICATION AND VAST VARIETY OF SYSTEM/
USER REQUIREMENTS, SPECIFIC SAFE OPERATING PROCEDURES FOR THE
USE OF THIS DEVICE MUST BE DEVELOPED BY THE USER.
1. Introduction
Type Vac Clad-W switchgear assemblies are designed with all the bus work completely insulated for safety. Since the current carrying parts are not readily accessible, the type VCP-W Simple Ectrical
Ground & Test Device (SEG&TD) is designed for insertion into the breaker compartment to gain access to the primary stationary contacts. It provides a convenient means to ground the circuit for maintenance work.
Non roll-on-floor option available
There is an equivalent style number available to order this SEG&TD as a non roll-on-floor device. Please contact your Eaton representative for information.
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
2. Description
The SEG&TD is a drawout element that can be inserted into a lower circuit breaker compartment in the same manner as a VCP-W circuit breaker. This device is equipped with a set of three bottom terminals (see Figures 1, 2, and 3). In the lower compartment, the terminals of the SEG&TD typically connect to switchgear terminals connected to cables. It is important that the user review the switchgear compartment configuration, to confirm the circuit that he/she intends to ground, prior to using this device.
Figure 1. SEG&TD (front view).
2 EATON www.eaton.com
Figure 2. Bottom stabs of the SEG&TD (as provided).
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
IB131018EN
Effective January 2017
WARNING
IMPROPER USE CAN RESULT IN DEATH, SERIOUS PERSONAL INJURY, OR
PROPERTY DAMAGE.
2.3 Basic elements description
Selector Switch - The selector switch has the “OPEN”, “OFF” and
“CLOSE” positions and operates in association with the remote operating station's “OPEN”/”CLOSE” pushbuttons (see Figure 4).
Figure 3. Bottom stabs of the SEG&TD (rear view).
This device is deeper than the standard VCP-W breaker. The stored energy closing mechanism for the SEG&TD is the same as used in type VCP-W breakers. It is capable of applying the ground against a “Live” circuit if operational errors have not cleared the circuit.
However, in such a case, the relaying at the source of power is expected to cause the source interrupter to clear the circuit.
WARNING
THIS MANUAL DESCRIBES A SPECIFIC SEG&TD FOR USE AT A SPECIFIC
LOCATION. IT SHOULD NOT BE REFERENCED FOR ANY OTHER PURPOSE
OR INSTALLATION.
2.1 VCP-W interlocks and safety features
The SEG&TD is designed to provide as many interlocks and safety features as practical for the personnel performing any of the operations described earlier.
The device cannot be levered into or out of the “Connected” position unless the SEG&TD is open.
•
•
When working with a "Closed" SEG&TD, the cam on the floor of the compartment will trip the breaker when the device is levered into or out of the “Test” position.
In the “Connected” position, engaging the levering crank will trip the SEG&TD open.
•
•
•
•
•
An indicator on the front panel shows the status of the SEG&TD contacts, “Open-Ungrounded” or “Closed-Grounded” (see
Appendix A).
The SEG&TD cannot be manually closed. The spring charging socket and manual close button are both covered by the device front panel (see Appendix A).
The SEG&TD can be closed only electrically by a remote operating station at the end of a 50 ft. (15.2 m) cable supplied with the device.
The power to operate the SEG&TD in this device is obtained through the secondary disconnect in the breaker compartment.
The control switch cable is connected to the device with a twist lock connector.
Figure 4. Selector switch.
N otee: In this design, the selector switch functions as described below. In the “OFF” position, the SEG&TD is electrically disabled. The selector switch is padlockable in the “OFF” position. This provides the padlockable function. The selector switch in the “CLOSE” position allows the execution of a remote “CLOSE” command. The “OPEN” function is disabled. Conversely, the selector switch in the “OPEN” position allows the execution of a remote
“OPEN” command. The “CLOSE” function is disabled.
EATON www.eaton.com
3
IB131018EN
Effective January 2017
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
2. Move the test probe shutter handles to the left then insert the test probes into the test ports for all three phases.
3.0 Operation
3.1 Safe practices
The SEG&TD is a safety-related device. It must be recognized that improper use can result in death, serious personal injury, or property damage. That is why it is important that the user develop specific and safe operating procedures for its use.
The following general safe practices are recommended.
CAUTION
THE DEVICE CANNOT BE STORED IN VAC CLAD-W BREAKER COMPART-
MENT. IT CAN ONLY BE STORED IN ITS STORAGE COMPARTMENT.
Test probes
1. Store the device in a clean, dry area free from dust, dirt, moisture, etc.
2. Keep all insulating surfaces, which include primary support insulation and insulation barriers, clean and dry.
3. Check all primary circuit connections to make certain that they are clean and tight.
4. Permit only authorized trained personnel to use this device.
5. Take extreme care while using this device to avoid contacting
“Live” or “Hot” (energized) terminals.
6. Do not remove the device's front panel while using this device.
7. Always “CLOSE” the SEG&TD electrically from the farthest distance with the remote control switch.
9. Check for dielectric integrity at 15 kV AC across the terminals to ground with the SEG&TD “OPEN”.
10. Always install the "test probes" when the SEG&TD is in the
"DISCONNECT" position in the breaker cubicle.
DANGER
IT IS NOT RECOMMENDED THAT YOU INSTALL THE "TEST PROBES"
WHEN THE SEG&TD IS IN THE "CONNECTED" POSITION. THE VOLTAGES
IN ENERGIZED EQUIPMENT CAN CAUSE DEATH OR SEVERE PERSONAL
INJURY. IF ATTEMPTING TO INSERT TEST PROBES WHILE THE SEG&TD IS
IN THE "CONNECTED" POSITION USE 20 KV GLOVES.
Test probe shutter handles
Figure 6. Test probes inserted into the test ports.
3. Once the three test probes are fully inserted, slide the test probe shutter handles to the right to lock the test probes in place. The test port shutter is fully closed when the hole in the left test probe shutter handle aligns with the hole in the test probe shutter locking plate.
N otee: The test probe shutter can be locked in place by inserting a padlock through the holes in the left test probe shutter handle and the hole in the test probe shutter locking plate.
Left shutter handle
3.2 Ground and test device operation sequence
1. With the SEG&TD control switch in the "OFF" position, insert the SEG&TD into the breaker cubicle in the "DISCONNECT" position.
Figure 5. SEG&TD inserted into the breaker cubicle.
4 EATON www.eaton.com
Locking plate
Figure 7. Test port shutter locking the test probes in the test ports.
4. Lift up on the release tabs on the retaining straps and remove the 6 ft. (1.8 m) extension cord from its storage location.
Align then insert the male plug of the extension cord into the
SEG&TD's remote control female twist-lock receptacle. Turn the male plug clockwise to lock it in place.
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
IB131018EN
Effective January 2017
5. Insert the levering mechanism and rack the SEG&TD into the
"CONNECTED" position. Reference the switchgear manufacturer's instruction book for instructions on bypassing the mechanical interlock to permit open door racking so that the SEG&TD can be racked in while the door remains open.
Release tab
Figure 8. Location of the release tabs on the retaining straps.
Figure 9. Male plug of the 6 ft. extension cord.
Figure 11. Levering mechanism used to move the SEG&TD into the "CONNECTED" position.
.
6. Check for the presence of voltage on all three phases using a hot stick mounted test instrument.
Figure 10. Male twist-lock plug locked into the twist-lock receptacle on the SEG&TD.
EATON www.eaton.com
5
IB131018EN
Effective January 2017
7. If no voltage is detected, insert the remote operating station male twist-lock plug into the 6 ft. twist lock extension cord's female receptacle. Turn the plug and receptacle to lock them together.
N otee: The male plug and female receptacle are fully locked when the square tabs are aligned.
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
Alignment tabs
Figure 12. Correct orientation of the alignment tabs on the twist-lock plug and receptacle.
8. Turn the SEG&TD's control switch to the "CLOSE" position.
Figure 14. Buttons on the remote operating station.
11. Disconnect the remote station cord from the 6 ft. twist-lock extension and turn the SEG&TD control switch to the "OFF" position. Roll the remote station cord up for storage outside of the cubicle.
Figure 13. Control switch in the "CLOSE" position.
9. Unroll the remote operating station cord and step outside the switchgear enclosure.
10. Push and hold the "CLOSE" button on the remote operating station to charge the motor circuit which in turn charges the closing springs and grounds the circuit. Once the SEG&TD is closed, release the "CLOSE" button.
Figure 15. Control switch in the "OFF" position.
12. Remove the male twist-lock plug from the SEG&TD's female receptacle. Store the 6 ft. twist-lock extension in its storage location on the SEG&TD and secure it using the retaining straps. Close the switchgear cubicle door.
Figure 16. Twist-lock extension stored and secured in its storage location.
6 EATON www.eaton.com
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
13. Upon completion of the work, open the switchgear cubicle door and locate the 6 ft. twist-lock extension cord. Release it from its storage location.
14. Insert the 6 ft. extension cord's male twist-lock plug into the
SEG&TD's remote control twist-lock receptacle and turn the
SEG&TD control switch to the "Open" position.
IB131018EN
Effective January 2017
Figure 17. Control switch in the "OPEN" position.
15. Remove the remote operating station cord from storage and connect it to the 6 ft. twist-lock extension cord.
16. Unroll the remote operating station cord and step outside the switchgear enclosure.
17. Push the "OPEN" button on the remote operating station to unground the circuit.
Figure 18. "OPEN" button on the remote operating station.
18. Insert the levering mechanism and rack the SEG&TD to the
"DISCONNECT" position.
Figure 19. Levering mechanism used to move the SEG&TD into the "DISCONNECT" position.
19. Disconnect the remote operating station cord from the 6 ft. extension cord.
20. Remove the 6 ft. extension cord, with twist-lock connectors, from the SEG&TD. Secure the 6 ft. extension cord in its storage location usSEing the retaining straps.
21. Move the test port shutter to the left to unlock the probes in the test ports.
22. Remove the test probes from the test ports for all three phases.
Move the test port shutter to the right to close the test post shutter.
23. Remove the SEG&TD from the cubicle.
EATON www.eaton.com
7
IB131018EN
Effective January 2017
Appendix A - Front view
1 10
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
11
12
5
3
8
2
4
7
13
1. Probe inserted in the test port
2. Test port padlock (probes inserted)
3. Manual trip button
4. Operations counter
5. Grounding switch position indicator
6. Remote operating station with 50 foot cord
7 Ground Contact
8. Remote operating station receptacle
9. Floor tripper
10. Test port shutter handles
11. Selector switch
12. Selector switch padlock
13. 6 ft. extension cord
9
6
8 EATON www.eaton.com
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
Appendix B - Side view
1
2
3
IB131018EN
Effective January 2017
4
1. Selector switch padlock
2. Selector switch
3. Levering latch handle
4. Lower terminal primary contacts
EATON www.eaton.com
9
IB131018EN
Effective January 2017
Appendix C - Control scheme
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
10 EATON www.eaton.com
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
Appendix D - Outline drawing
IB131018EN
Effective January 2017
Outline drawing applies to 40 kA rated version only.
EATON www.eaton.com
11
IB131018EN
Effective January 2017
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
Appendix E - Breaker code plate reference
The chart below shows a summary of the code plates that are on our Eaton breakers. In order to avoid an interference issue on this particular ground and test device you may need to change the code plates. We apologize for any inconvenience when you encounter code plate interference. The best solution for resolving the interference is to obtain code plates that match the breakers being used. Cross reference this list to find the correct code plates to use. See appendices F & G for information on making code plates.
Breaker model
150VCP-W 40 C
150VCP-W 40 C
150VCP-W 50
150VCP-W 50
150VCP-W 50
150VCP-W 50
150VCP-W 50
150VCP-W 50
150VCP-W 50 C
150VCP-W 50 C
150VCP-W 50 C
150VCP-W 63
150VCP-W 63
150VCP-W 63
150VCP-W 63
150VCP-W 25
150VCP-W 25
150VCP-W 25
150VCP-W 25
150VCP-W 25
150VCP-W 25
150VCP-W 25 C
150VCP-W 25 C
150VCP-W 25 C
150VCP-W 40
150VCP-W 40
150VCP-W 40
150VCP-W 40
150VCP-W 40
150VCP-W 40
150VCP-W 40 C
150VCP-W 63
150VCP-W 63
150VCP-W 63
150VCP-W 63
150VCP-W 63
150VCP-W 63
150VCP-W 63
150VCP-W 63
150VCP-W 63 C
150VCP-W 63 C
150VCP-W 63 C
150VCP-W1000
150VCP-W1000
150VCP-W1000
Current rating
1200
2000
3000
1200
1200
1200
1200
2000
2000
3000
3000
2000
3000
1200
1200
2000
3000
3000
1200
3000
1200
1200
2000
3000
3000
1200
2000
1200
1200
2000
2000
1200
2000
3000
1200
1200
2000
3000
3000
3000
3000
2000
2000
2000
2000
Cycle
3
5
5
C
3
C
C
3
5
3
5
3
5
C
C
5
C
5
3
5
3
C
3
C
C
3
5
3
5
3
5
C
3
C
C
5
3
5
5
3
3
5
5
3
3
Class
C
C
C
K=1
K=1
K=1
K=1
K=1
K=1
K=1
K=1
C
C
K=1
K=1
K=1
K=1
K=1
C
C
K=1
K=1
K=1
C
C
K=1
K=1
K=1
K=1
K=1
K=1
C
C
C
K>1
K>1
K>1
K=1
K=1
K=1
K=1
K=1
K=1
K=1
K=1
Breaker LH code
00010
00010
00010
10010
10010
10020
10020
00010
00010
12000
12000
11000
11000
20000
20000
21010
12000
12000
11000
11000
20000
20000
00010
12000
12000
11000
11000
20000
20000
21010
21010
10000
10000
10000
10010
10020
10010
10010
10010
10020
10020
10010
10010
10020
10020
Breaker LH style code plate
8061A39H04
8061A39H04
8061A47H06
8061A47H06
8061A38H06
8061A38H06
8061A40H06
8061A40H06
8061A39H04
8061A39H04
8061A39H04
8061A39H01
8061A39H01
8061A33H01
8061A33H01
8061A47H06
8061A47H06
8061A38H06
8061A38H06
8061A40H06
8061A40H06
8061A38H01
8061A38H01
8061A38H01
8061A47H06
8061A47H06
8061A38H06
8061A38H06
8061A40H06
8061A40H06
8061A39H04
8061A39H01
8061A39H01
8061A33H01
8061A33H01
8061A39H01
8061A39H01
8061A33H01
8061A33H01
8061A50H03
8061A50H03
8061A50H03
8061A39H01
8061A33H01
8061A39H01
Breaker RH code Breaker RH style code plate
00102
00101
00110
00002
00002
00002
00002
10101
10110
10011
10012
10011
10012
10011
10012
21110
11011
11012
11011
11012
11011
11012
10102
21011
21012
21011
21012
21011
21012
21102
21101
00002
00001
00010
10002
10002
10001
00001
00001
00001
00001
00010
00010
00010
00010
8061A39H03
8061A39H03
8061A39H03
8061A39H03
8061A39H04
8061A39H04
8061A39H04
8061A39H04
8061A39H02
8061A39H03
8061A39H04
8061A46H01
8061A46H01
8061A50H01
8061A50H02
8061A39H05
8061A40H02
8061A42H01
8061A40H02
8061A42H01
8061A40H02
8061A42H01
8061A39H06
8061A39H07
8061A39H08
8061A39H02
8061A39H02
8061A39H02
8061A39H02
8061A40H07
8061A41H01
8061A40H07
8061A41H01
8061A40H07
8061A41H01
8061A44H02
8061A48H03
8061A38H03
8061A38H05
8061A38H04
8061A38H05
8061A38H04
8061A38H05
8061A38H04
8061A46H02
12 EATON www.eaton.com
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
Breaker model
150VCP-W750
150VCP-W750
150VCP-W750
150VCP-W750
150VCP-W750
150VCP-W750 H
150VCP-W750 H
150VCP-W750 H
150VCP-W750 H
150VCP-W750 H
150VCP-W750 H
150VCP-WG 50
150VCP-WG 50
150VCP-WG 50
150VCP-WG 63
150VCP-WG 63
150VCP-W1000
150VCP-W1000
150VCP-W1000
150VCP-W500
150VCP-W500
150VCP-W500
150VCP-W500
150VCP-W500
150VCP-W500
150VCP-W500 H
150VCP-W500 H
150VCP-W500 H
150VCP-W500 H
150VCP-W500 H
150VCP-W500 H
150VCP-W750
150VCP-WG 63
50VCP-W 25
50VCP-W 25
50VCP-W 25
50VCP-W 25
50VCP-W 25
50VCP-W 25
50VCP-W 25 C
50VCP-W 25 C
50VCP-W 25 C
50VCP-W 40
50VCP-W 40
50VCP-W 40
50VCP-W 40
50VCP-W 40
50VCP-W 40
50VCP-W 40 C
50VCP-W 40 C
Cycle
3
3
3
3
5
3
5
3
5
3
5
3
5
3
5
3
5
3
5
3
5
3
5
3
5
3
5
3
5
3
5
3
3
5
3
5
C
C
3
5
C
C
5
C
5
3
5
3
3
3
Current rating
2000
3000
1200
2000
2000
3000
3000
1200
3000
1200
1200
2000
1200
2000
2000
3000
2000
3000
3000
1200
3000
1200
1200
2000
1200
2000
2000
3000
2000
3000
3000
1200
2000
2000
3000
3000
2000
3000
1200
1200
1200
2000
2000
3000
3000
1200
3000
1200
1200
2000
IB131018EN
Effective January 2017
Class
K=1
K=1
K=1
K=1
K>1
K>1
K>1
K=1
K>1
K>1
K>1
K>1
K>1
K>1
K>1
K>1
K>1
K>1
K>1
K>1
K>1
K>1
K>1
K>1
K>1
K>1
K>1
K>1
K>1
K>1
K>1
K>1
C
C
K=1
K=1
K=1
K=1
C
C
K=1
K=1
K=1
K=1
K=1
C
K=1
K=1
K=1
K=1
Breaker LH code
21020
21010
21020
10020
10020
10020
10020
10020
21020
21010
21020
21010
21020
21010
21020
21010
22020
22010
22020
22010
22020
22010
22020
21010
10020
10010
10020
22010
22020
22010
22020
22010
21012
21012
12002
12002
11002
11002
20002
20002
00012
00012
10020
12002
12002
11002
11002
20002
20002
21012
Breaker LH style code plate Breaker RH code Breaker RH style code plate
8061A32H01
8061A38H01
8061A32H01
8061A38H01
8061A32H01
8061A38H01
8061A32H01
8061A38H01
8061A32H01
8061A38H01
8061A32H01
8061A33H01
8061A33H01
8061A33H01
8061A33H01
8061A33H01
8061A33H01
8061A39H01
8061A33H01
8061A37H01
8061A31H01
8061A37H01
8061A31H01
8061A37H01
8061A31H01
8061A37H01
8061A31H01
8061A37H01
8061A31H01
8061A37H01
8061A31H01
8061A38H01
8061A33H01
8061A47H05
8061A47H05
3A74923H01
3A74923H01
8061A45H01
8061A45H01
8061A41H01
8061A41H01
8061A41H01
8061A47H05
8061A47H05
3A74923H01
3A74923H01
8061A45H01
8061A45H01
8061A42H02
8061A42H02
10001
10010
10010
00002
00001
00010
00002
00001
21002
21001
21001
21010
21010
10002
10002
10001
22010
21002
21002
21001
21001
21010
21010
21002
10001
10010
10010
22002
22002
22001
22001
22010
21101
21110
11011
11012
11011
11012
11011
11012
10102
10101
00010
21011
21012
21011
21012
21011
21012
21102
8061A44H01
8061A48H01
8061A48H01
8061A38H01
8061A38H01
8061A46H01
8061A46H01
8061A50H01
8061A50H01
8061A39H01
8061A39H01
8061A39H02
8061A39H03
8061A39H04
8061A39H02
8061A39H03
8061A50H01
8061A39H01
8061A39H01
8061A43H01
8061A43H01
8061A47H01
8061A47H01
8061A37H01
8061A37H01
8061A44H01
8061A44H01
8061A48H01
8061A48H01
8061A38H01
8061A38H01
8061A44H01
8061A39H04
8061A40H07
8061A41H01
8061A40H07
8061A41H01
8061A40H07
8061A41H01
8061A44H02
8061A48H03
8061A38H03
8061A38H05
8061A38H04
8061A38H05
8061A38H04
8061A38H05
8061A38H04
8061A46H02
8061A50H02
EATON www.eaton.com
13
IB131018EN
Effective January 2017
Cycle
5
3
5
3
5
3
C
3
C
C
5
5
3
3
5
5
3
3
5
5
3
3
C
C
5
C
5
3
5
3
C
3
3
3
5
3
3
3
5
3
5
3
5
3
5
3
5
3
5
3
Breaker model Current rating
50VCP-W250
50VCP-W250 H
50VCP-W250 H
50VCP-W250 H
50VCP-W250 H
50VCP-W250 H
50VCP-W250 H
50VCP-W350
50VCP-W350
50VCP-W350
50VCP-W350
50VCP-W350
50VCP-W350
50VCP-WG 50
50VCP-WG 50
50VCP-WG 50
50VCP-WG 63
50VCP-WG 63
50VCP-W 40 C
50VCP-W 50
50VCP-W 50
50VCP-W 50
50VCP-W 50
50VCP-W 50
50VCP-W 50
50VCP-W 50 C
50VCP-W 50 C
50VCP-W 50 C
50VCP-W 63
50VCP-W 63
50VCP-W 63
50VCP-W 63
50VCP-W 63
50VCP-W 63
50VCP-W 63
50VCP-W 63
50VCP-W 63
50VCP-W 63
50VCP-W 63
50VCP-W 63
50VCP-W 63 C
50VCP-W 63 C
50VCP-W 63 C 3000
50VCP-W ND 250 1200
50VCP-W ND 250 1200
50VCP-W250 1200
50VCP-W250
50VCP-W250
50VCP-W250
50VCP-W250
1200
2000
2000
3000
3000
3000
1200
2000
2000
2000
3000
3000
1200
1200
2000
2000
2000
3000
1200
1200
2000
3000
3000
1200
3000
1200
1200
2000
3000
1200
2000
3000
1200
2000
2000
3000
1200
2000
2000
3000
3000
1200
3000
1200
1200
2000
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
Class
K>1
K>1
K>1
K>1
C
K>1
K>1
K>1
C
C
K=1
K=1
K=1
K=1
K=1
K=1
K=1
K=1
K=1
K=1
C
C
K=1
K=1
K=1
K=1
K=1
C
C
K=1
K=1
K=1
K>1
K=1
K=1
K=1
K>1
K>1
K>1
K>1
K=1
K=1
K>1
K>1
K>1
K>1
K>1
K>1
K>1
K>1
Breaker LH code
00012
21212
21222
21012
21022
21012
21022
21012
10022
10022
10012
10012
10022
10022
00012
00012
00012
00012
10012
10012
10022
10022
10012
10012
00012
12002
12002
11002
11002
20002
20002
00012
10022
10012
10022
10012
10022
10022
10022
10022
10022
10022
21022
21012
21022
21012
21022
21012
21022
10012
Breaker LH style code plate
8061A36H01
8061A36H01
8061A42H01
8061A42H01
8061A36H01
8061A36H01
8061A42H02
8061A42H02
8061A42H02
8061A61H01
8061A60H01
8061A41H01
8061A35H01
8061A41H01
8061A35H01
8061A41H01
8061A42H02
8061A47H05
8061A47H05
3A74923H01
3A74923H01
8061A45H01
8061A45H01
8061A42H02
8061A42H02
8061A42H02
8061A42H01
8061A42H01
8061A36H01
8061A36H01
8061A42H01
8061A42H01
8061A35H01
8061A41H01
8061A35H01
8061A41H01
8061A35H01
8061A41H01
8061A35H01
8061A42H01
8061A36H01
8061A42H01
8061A36H01
8061A42H01
8061A36H01
8061A36H01
8061A36H01
8061A36H01
8061A36H01
8061A36H01
Breaker RH code Breaker RH style code plate
00010
None
None
21002
21002
21001
21001
21010
00001
00001
00010
00010
00010
00010
00002
00001
00101
00110
00002
00002
00002
00002
00001
00001
10110
10011
10012
10011
10012
10011
10012
00102
10002
10001
10001
10010
10010
00002
00001
00010
00002
00001
21010
10002
10002
10001
10001
10010
10010
10002
8061A39H03
8061A39H03
8061A39H04
8061A39H04
8061A39H04
8061A39H04
8061A39H02
8061A39H01
8061A39H04
None
None
8061A44H01
8061A44H01
8061A48H01
8061A48H01
8061A38H01
8061A39H05
8061A40H02
8061A42H01
8061A40H02
8061A42H01
8061A40H02
8061A42H01
8061A39H06
8061A39H07
8061A39H08
8061A39H02
8061A39H02
8061A39H02
8061A39H02
8061A39H03
8061A39H03
8061A38H01
8061A46H01
8061A46H01
8061A50H01
8061A50H01
8061A39H01
8061A39H01
8061A46H01
8061A46H01
8061A50H01
8061A50H01
8061A39H01
8061A39H01
8061A39H02
8061A39H03
8061A39H04
8061A39H02
8061A39H03
14 EATON www.eaton.com
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
Breaker model
50VCP-WG 63
75VCP-W 40
75VCP-W 40
75VCP-W 40
75VCP-W 40
75VCP-W 40
75VCP-W 40
75VCP-W 50
75VCP-W 50
75VCP-W 50
75VCP-W 50
75VCP-W 50
75VCP-W 50
75VCP-W 50 C
75VCP-W 50 C
75VCP-W 50 C
75VCP-W500
75VCP-W500
75VCP-W500
75VCP-W500
75VCP-W500
75VCP-W500
Cycle
C
C
5
C
5
3
5
3
5
3
5
3
5
3
3
3
3
5
3
5
3
5
Current rating
3000
1200
2000
3000
1200
2000
2000
3000
2000
3000
3000
1200
3000
1200
1200
2000
1200
1200
2000
2000
3000
3000
IB131018EN
Effective January 2017
Class
C
C
K=1
C
K=1
K=1
K=1
K=1
K=1
K=1
K=1
K=1
K=1
K=1
K=1
K=1
K>1
K>1
K>1
K>1
K>1
K>1
Breaker LH code
12001
11001
11001
20001
20001
10011
10011
10011
10022
12001
12001
11001
11001
20001
20001
12001
20011
20021
20011
20021
20011
20021
Breaker LH style code plate
8061A36H01
8061A47H02
8061A47H02
8061A48H02
8061A48H02
8061A49H01
8061A49H01
8061A47H02
8061A47H02
8061A48H02
8061A48H02
8061A49H01
8061A49H01
8061A40H02
8061A40H02
8061A40H02
8061A40H01
8061A34H01
8061A40H01
8061A34H01
8061A40H01
8061A34H01
Breaker RH code Breaker RH style code plate
10012
10011
10012
10011
10012
00102
00101
00110
00010
11011
11012
11011
11012
11011
11012
10011
20002
20002
20001
20001
20010
20010
8061A39H04
8061A38H05
8061A38H04
8061A38H05
8061A38H04
8061A38H05
8061A38H04
8061A40H02
8061A42H01
8061A40H02
8061A42H01
8061A40H02
8061A42H01
8061A46H02
8061A50H02
8061A39H05
8061A45H01
8061A45H01
8061A49H01
8061A49H01
8061A51H01
8061A51H01
EATON www.eaton.com
15
IB131018EN
Effective January 2017
Appendix F - How to make breaker plates
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
16 EATON www.eaton.com
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
Appendix G - How to make cell plates
IB131018EN
Effective January 2017
EATON www.eaton.com
17
IB131018EN
Effective January 2017
Appendix G - How to make cell plates (cont.)
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
18 EATON www.eaton.com
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
Appendix G - How to make cell plates (cont.)
IB131018EN
Effective January 2017
EATON www.eaton.com
19
IB131018EN
Effective January 2017
Appendix G - How to make cell plates (cont.)
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
20 EATON www.eaton.com
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
Appendix G - How to make cell plates (cont.)
IB131018EN
Effective January 2017
EATON www.eaton.com
21
IB131018EN
Effective January 2017
Appendix G - How to make cell plates (cont.)
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
22 EATON www.eaton.com
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
Appendix G - How to make cell plates (cont.)
IB131018EN
Effective January 2017
EATON www.eaton.com
23
IB131018EN
Effective January 2017
The instructions for installation, testing, maintenance, or repair herein are provided for the use of the product in general commercial applications and may not be appropriate for use in nuclear applications. Additional instructions may be available upon specific request to replace, amend, or supplement these instructions to qualify them for use with the product in safety-related applications in a nuclear facility.
The information, recommendations, descriptions, and safety notations in this document are based on Eaton’s experience and judgment with respect to Retrofitting of Power Breakers. This instructional literature is published solely for information purposes and should not be considered all-inclusive. If further information is required, you should consult an authorized Eaton sales representative.
The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between the parties. This literature is not intended to and does not enlarge or add to any such contract.
The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton.
NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING
WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR
MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE
OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING
THE INFORMATION, RECOMMENDATIONS, AND DESCRIPTIONS
CONTAINED HEREIN.
In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and description contained herein.
Instructions for VCP-W Simple Electrical Ground
& Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
Eaton
Electrical Sector
1000 Eaton Boulevard
Cleveland, OH 44122
United States
877-ETN-CARE (877-386-2273)
Eaton.com
© 2017 Eaton
All Rights Reserved
Printed in USA
Publication No. IL131018EN / TBG1265
January 2017
Eaton is a registered trademark.
All other trademarks are property of their respective owners.