TouchSecure Connectivity MUL access control reader User Manual
Below you will find brief information for access control reader Connectivity MUL. The Connectivity MUL is a physical access control reader that can read HF and LF contactless credentials. The reader can interface with an access control system equipped with a Wiegand or RS485 serial interface Control Panel. It can also be interfaced with a Host Sever / Control Panel that supports Ethernet interface. User interfaces include RGB LED’s and Buzzer.
Advertisement
Advertisement
TouchSecure® Connectivity User Manual
Ver2.0
TouchSecure® Connectivity User Manual
Version History
Date
16-May-13
11-Jul-13
Version
1.0
2.0
Description of Changes
Initial version
1. ICES-003 Statement removed.
2. French translation added for RSS-GEN
3. Added FCC statement
Author
Sixtus
Sixtus
IDT.QM.P2.T1.DT
Printed copies of this document are uncontrolled
Ver1.0 Page 2 of 11
Internal Use Only
TouchSecure® Connectivity User Manual
Contents
IDT.QM.P2.T1.DT
Printed copies of this document are uncontrolled
Ver1.0 Page 3 of 11
Internal Use Only
TouchSecure® Connectivity User Manual
1.0 Introduction
This document details the Physical Access Control Reader TouchSecure® and its basic operational and installation procedures. It covers the details of the Mullion form-factor reader
Model: Connectivity MUL
The reader comes in two variants for interfacing with the control panel
•
Pigtail
•
Phoenix connectors
2.0 Reader
2.1 Functionality
TouchSecure® is a physical access reader that can read HF and LF contactless credentials .The reader can interface with an access control system equipped with a Wiegand or RS485 serial interface Control Panel. It can also be interfaced with a Host Sever / Control Panel that supports
Ethernet interface. User interfaces include RGB LED’s and Buzzer.
The reader consists of the following main parts.
2.2 Top Casing
IDT.QM.P2.T1.DT
Printed copies of this document are uncontrolled
Ver1.0 Page 4 of 11
Internal Use Only
TouchSecure® Connectivity User Manual
2.3 TouchSecure® reader with Bottom Casing
3.0 Product details
Model Name
Device Type
: Connectivity MUL
: RFID reader, 13.56MHz (HF) / 125 KHz (LF)
Physical Access control Reader (accessory equipment)
Type of equipment
Interface Type
Voltage Rating
: Potted reader. Suitable for Indoor / Controlled Outdoor use
: Pigtail Cable (11 Core + Drain) or Phoenix connectors and RJ45
Current Rating @12V
: 5-16V DC or 48VDC on RJ45 Connector
: Pk Current – 180mA , Average Current 120mA
: Wiegand, RS485 (2wire - Half Duplex) , 10BaseT ETH Communication protocol
IDT.QM.P2.T1.DT
Printed copies of this document are uncontrolled
Ver1.0 Page 5 of 11
Internal Use Only
TouchSecure® Connectivity User Manual
4.0 Specifications
Model
Connectivity MUL
Op Voltage Current @ 12V
5-16 VDC or
POE@ 48VDC
Av -120mA
Pk -180mA
Op temp
-35 to +65 Deg C
Cable Length
RS485 - 4000ft (24AWG)
Wiegand -500ft (22AWG)/
300ft (24AWG)
Table 1
5.0 Installation details
5.1 Parts List
•
TouchSecure®reader -1
•
Screws (A #6-18X1.5" SS ) - 2Nos – Mounting screws for Wall
•
Snake Eye Screw (SMF #6-32X5/16" SS) – 1 No- Top casing mounting security screw
•
Screws (SMF #6-32x3/8" SS) - 3 No’s - 1 Top casing mounting screw and 2 Junction Box mounting screws
•
Nylon anchor plug -2 Nos
•
6 pin phoenix plug (Phoenix connector version only) – 2 Nos
5.2 Recommended Infrastructure
•
Cable Wiegand - 22AWG for 500Ft / 24AWG for 300Ft with Foil Shield
•
Cable RS485 - RS485 for 1000m** (4000ft) 24AWG STP
•
Cable RJ45 - Cat5e / Cat6
•
Linear DC PS - 5-16 V, 1A min.
•
POE Adaptor Kit - TL-POE200A
** Tested in lab conditions upto 115Kbaud
5.3 Wiring Information
5.3.1 Cable Color codes for Pig Tail Reader
Red
&
White
Orange
Yellow
Blue
Brown
+ VDC 12V (nominal)
Black & White Ground
Green Wiegand Data 0
Wiegand Data 1
LED Green
Buzzer
Hold
LED Red
Grey
Pink
Violet
RS485 -
RS 485 +
Tamper Output
Black / Drain Shield Ground
Table 2
& -
Do not connect when reader is powered by Power over Ethernet
IDT.QM.P2.T1.DT
Printed copies of this document are uncontrolled
Ver1.0 Page 6 of 11
Internal Use Only
TouchSecure® Connectivity User Manual
5.3.2 Pin out for Phoenix Connector Reader
Pin Cable colour
P1.1 Orange
P1.2
P1.3
White
Green
P1.4 Black
P1.5 Black + White
P1.6
P2.1
Red
Blue
P2.2
P2.3
P2.4
P2.5
P2.6
Violet
Gray
Pink
Yellow
Brown
Description
LED Green
Data 1
Data 0
Drain
Gnd
Power
Hold
Tamper
RS485-
RS485+
Buzzer
LED Red
Comment
Do not connect when reader is powered by PoE
Table 3
Caution:
During Wiring make sure that the +VDC lines does not make contact with any other cables, as it might affect reader functionality/ cause damage to the reader.
IDT.QM.P2.T1.DT
Printed copies of this document are uncontrolled
Ver1.0 Page 7 of 11
Internal Use Only
TouchSecure® Connectivity User Manual
5.4 Mounting the Reader
5.4.1 Location of mounting holes on wall
Phoenix connector Reader – 2 Holes and 1 Slot
5.4.2 Reader Installation Steps
a. Make two holes on the wall as per the image above. b. Insert the nylon screw plugs into the wall. c. Connect the wires as per the Table 2 or Table 3. d. TouchSecure® reader with Bottom Casing is to be now secured onto the wall using the
Screws (A #6-18X1.5" SS ) e. The top casing can be inserted onto the bottom casing f. Secure the Top and bottom casing by the Snake Eye Screw (SMF #6-32X5/16" SS)
IDT.QM.P2.T1.DT
Printed copies of this document are uncontrolled
Ver1.0 Page 8 of 11
Internal Use Only
TouchSecure® Connectivity User Manual
Reader Installation Steps - Phoenix Connector Version
Reader Installation Steps - Pig Tail Version
IDT.QM.P2.T1.DT
Printed copies of this document are uncontrolled
Ver1.0 Page 9 of 11
Internal Use Only
TouchSecure® Connectivity User Manual
5.5 Power up and Testing
1 Turn power on
The LED blinks 3 times green with a long beep, then turns red
2 Present a card
The LED blinks green, and a short Beep is emitted
This is the default reader behavior.
6.0 Certifications
6.1 FCC
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) this device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may cause undesired operation
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
—Reorient or relocate the receiving antenna.
—Increase the separation between the equipment and receiver.
—Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
—Consult the dealer or an experienced radio/TV technician for help.
Information to user
Changes or modifications not expressly approved by Identive could void the user's authority to operate the equipment.
6.2
IC
This device complies with Industry Canada license-exempt RSS standard(s).
Operation is subject to the following two conditions:
(1) This device may not cause interference
(2) This device must accept any interference, including interference that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes :
(1) l'appareil ne doit pas produire de brouillage, et
(2) l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre le fonctionnement
IDT.QM.P2.T1.DT
Printed copies of this document are uncontrolled
Ver1.0 Page 10 of 11
Internal Use Only
TouchSecure® Connectivity User Manual
6.3 CE
Identive hereby declares that the TouchSecure® Model: Connectivity MUL device mentioned herein is in compliance with the essential requirements and other relevant portions of the Directive R&TTE
1999/5/EC.
IDT.QM.P2.T1.DT
Printed copies of this document are uncontrolled
Ver1.0 Page 11 of 11
Internal Use Only
Download
Advertisement
Key features
HF and LF contactless credentials reading
Wiegand or RS485 serial interface
Ethernet interface support
RGB LED’s and Buzzer user interface
Pigtail Cable or Phoenix connectors and RJ45
5-16V DC or 48VDC on RJ45 Connector
Power over Ethernet support
Indoor/Controlled Outdoor use
Frequently asked questions
The Connectivity MUL can read both HF and LF contactless credentials.
The Connectivity MUL supports Wiegand, RS485, and Ethernet communication protocols.
The Connectivity MUL can be powered by 5-16V DC or 48VDC on the RJ45 Connector, or by Power over Ethernet.