advertisement
JDF-2S, JDF-4S
Silver Series
®
JDF-2S & JDF-4S PH or PC with Non LIT or LIT Graphic Door
JDF-2S & JDF-4S PH or PC with LIT Segment Door
SERVICE & REPAIR MANUAL
Bunn-O-Matic Corporation
Post Office Box 3227, Springfield, Illinois 62708-3227
Phone (217) 529-6601 | Fax (217) 529-6644
49179.0000 G 10/19 © 2013 Bunn-O-Matic Corporation
BUNN-O-MATIC COMMERCIAL PRODUCT WARRANTY
Bunn-O-Matic Corp. (“BUNN”) warrants equipment manufactured by it as follows:
1) Airpots, thermal carafes, decanters, GPR servers, iced tea/coffee dispensers, MCR/MCP/MCA single cup brewers, thermal servers and ThermoFresh® servers (mechanical and digital) 1 year parts and 1 year labor.
2) All other equipment - 2 years parts and 1 year labor plus added warranties as specified below: a) Electronic circuit and/or control boards - parts and labor for 3 years.
b) Compressors on refrigeration equipment - 5 years parts and 1 year labor.
c) Grinding burrs on coffee grinding equipment to grind coffee to meet original factory screen sieve analysis - parts and labor for 4 years or 40,000 pounds of coffee, whichever comes first.
These warranty periods run from the date of installation BUNN warrants that the equipment manufactured by it will be commercially free of defects in material and workmanship existing at the time of manufacture and appearing within the applicable warranty period. This warranty does not apply to any equipment, component or part that was not manufactured by BUNN or that, in BUNN’s judgment, has been affected by misuse, neglect, alteration, improper installation or operation, improper maintenance or repair, non periodic cleaning and descaling, equipment failures related to poor water quality, damage or casualty. In addition, the warranty does not apply to replacement of items subject to normal use including but not limited to user replaceable parts such as seals and gaskets. This warranty is conditioned on the Buyer 1) giving BUNN prompt notice of any claim to be made under this warranty by telephone at (217) 529-6601 or by writing to Post Office Box
3227, Springfield, Illinois 62708-3227; 2) if requested by BUNN, shipping the defective equipment prepaid to an authorized
BUNN service location; and 3) receiving prior authorization from BUNN that the defective equipment is under warranty.
THE FOREGOING WARRANTY IS EXCLUSIVE AND IS IN LIEU OF ANY OTHER WARRANTY, WRITTEN OR ORAL, EX-
PRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF EITHER MERCHANTABILITY OR
FITNESS FOR A PARTICULAR PURPOSE.
The agents, dealers or employees of BUNN are not authorized to make modifications to this warranty or to make additional warranties that are binding on BUNN. Accordingly, statements by such individuals, whether oral or written, do not constitute warranties and should not be relied upon.
If BUNN determines in its sole discretion that the equipment does not conform to the warranty, BUNN, at its exclusive option while the equipment is under warranty, shall either 1) provide at no charge replacement parts and/or labor (during the applicable parts and labor warranty periods specified above) to repair the defective components, provided that this repair is done by a BUNN Authorized Service Representative; or 2) shall replace the equipment or refund the purchase price for the equipment.
THE BUYER’S REMEDY AGAINST BUNN FOR THE BREACH OF ANY OBLIGATION ARISING OUT OF THE SALE OF THIS
EQUIPMENT, WHETHER DERIVED FROM WARRANTY OR OTHERWISE, SHALL BE LIMITED, AT BUNN’S SOLE OPTION
AS SPECIFIED HEREIN, TO REPAIR, REPLACEMENT OR REFUND.
In no event shall BUNN be liable for any other damage or loss, including, but not limited to, lost profits, lost sales, loss of use of equipment, claims of Buyer’s customers, cost of capital, cost of down time, cost of substitute equipment, facilities or services, or any other special, incidental or consequential damages.
392, A Partner You Can Count On, Air Infusion, AutoPOD, AXIOM, BrewLOGIC, BrewMETER, Brew Better Not Bitter, Brew-
WISE, BrewWIZARD, BUNN Espress, BUNN Family Gourmet, BUNN Gourmet, BUNN Pour-O-Matic, BUNN, BUNN with the stylized red line, BUNNlink, Bunn-OMatic, Bunn-O-Matic, BUNNserve, BUNNSERVE with the stylized wrench design,
Cool Froth, DBC, Dr. Brew stylized Dr. design, Dual, Easy Pour, EasyClear, EasyGard, FlavorGard, Gourmet Ice, Gourmet
Juice, High Intensity, iMIX, Infusion Series, Intellisteam, My Café, Phase Brew, PowerLogic, Quality Beverage Equipment
Worldwide, Respect Earth, Respect Earth with the stylized leaf and coffee cherry design, Safety-Fresh, savemycoffee.com,
Scale-Pro, Silver Series, Single, Smart Funnel, Smart Hopper, SmartWAVE, Soft Heat, SplashGard, The Mark of Quality in
Beverage Equipment Worldwide, ThermoFresh, Titan, trifecta, TRIFECTA (sylized logo), Velocity Brew, Air Brew, Beverage
Bar Creator, Beverage Profit Calculator, Brew better, not bitter., Build-A-Drink, BUNNSource, Coffee At Its Best, Cyclonic
Heating System, Daypart, Digital Brewer Control, Element, Milk Texturing Fusion, Nothing Brews Like a BUNN, Picture
Prompted Cleaning, Pouring Profits, Signature Series, Sure Tamp, Tea At Its Best, The Horizontal Red Line, Ultra are either trademarks or registered trademarks of Bunn-O-Matic Corporation. The commercial trifecta® brewer housing configuration is a trademark of Bunn-O-Matic Corporation.
2 49179 031314
INTRODUCTION
Safety first!
To avoid electrical shock, unplug dispenser from power source before servicing inside.
Basic Maintenance
In order to maintain proper machine operation, a Preventative Maintenance schedule must be performed on a regular basis.
The following procedures pretain to all versions in the JDF family of machines unless otherwise noted.
CONTENTS
Warranty ...................................................................................................................................2
User Notices .............................................................................................................................3
Site Preparation .......................................................................................................................3
Preventive Maintenance
Recommended Daily Cleaning ...........................................................................................4
Preventive Maintenance Schedule .......................................................................................5
Troubleshooting ........................................................................................................................6
Service ....................................................................................................................................12
Electrical Schematics ..............................................................................................................50
USER NOTICES
All notices on this equipment are written for your protection. All notices are to be kept in good condition.
Replace any unreadable or damaged labels.
SITE PREPARATION
A minimal clearance is required between the dispenser sides and the wall or another appliances.For optimum performance, do not allow warm air from surrounding machines blow on the JDF dispenser. Leave some space so the dispenser can be moved for cleaning.
3 49179 110613
Recommended Daily Cleaning Instructions
The use of a damp cloth rinsed in any mild, non-abrasive, liquid detergent is recommended for cleaning all surfaces on Bunn-O-Matic equipment. Do NOT clean this equipment with a water jet device.
1. Open dispenser door. Lift up on product containers to disconnect them from the machine inlet.
2. Close door, place an empty container under the dispense nozzles.
3. Dispense from each station until clear water flows from the dispense nozzle.
4. Open dispenser door and reconnect all product containers.
5. Remove dispense nozzles and drip tray. Wash all parts in warm soapy water.
6. With a warm/soapy cloth, wipe down interior of cabinet and splash panel area behind dispensing nozzles.
7. Replace drip tray and dispense nozzles.
8. Dispense from each station until finished product flows from the dispense nozzles.
4 49179 110613
REQUIRED REGULAR MAINTENANCE:
When performing Daily-Weekly Cleaning procedures, inspect o-rings, seals, and bushings for signs of wear or damage and replace immediately.
Check and/or replace every 6 months or as required:
39690.0000
28755.1011
Pump Tube Replacement Kit (Includes items indented below)
Tube, Norprene .25" ID x 17.0" lg
32732.0000 Clamp
32656.0000
.39"/.48"
21275.0003 Clamp
34325.0032
Fitting, Elbow .25" Barb x .38" Barb
.57"/.70"
Hose, Flex .38" ID x 5.25" lg
5 49179 110613
TROUBLESHOOTING
A troubleshooting guide is provided to suggest probable causes and remedies for the most likely problems encountered. If the problem remains after exhausting the troubleshooting steps, contact the Bunn-O-Matic
Technical Service Department.
• Inspection, testing, and repair of electrical equipment should be performed only by qualified service personnel.
• All electronic components have high voltage ac and low voltage dc potential on their terminals. Shorting of terminals or the application of external voltages may result in board failure.
• Intermittent operation of electronic circuit boards is unlikely. Board failure will normally be permanent. If an intermittent condition is encountered, the cause will likely be a switch contact or a loose connection at a terminal or crimp.
• Solenoid removal requires interrupting the water supply to the valve. Damage may result if solenoids are energized for more than ten minutes without a supply of water.
• The use of two wrenches is recommended whenever plumbing fittings are tightened or loosened. This will help to avoid twists and kinks in the tubing.
• Make certain that all plumbing connections are sealed and electrical connections tight and isolated.
• This unit is heated at all times. Keep away from combustibles.
WARNING – • Exercise extreme caution when servicing electrical equipment.
• Unplug the dispenser when servicing, except when electrical tests are specified.
• Follow recommended service procedures
• Replace all protective shields or safety notices
PROBLEM
Cold Water Circulation
Dispense stations not working.
Note: Cooling failure or excessive cabinet temperatures for more than 4 hours will result in dispense lockout or no dispense.
Note: Reset fault/timer by unplugging unit.
PROBABLE CAUSE
1. Cabinet cooling fan.
2. Bath recirculation pump.
REMEDY
Replace fan (24vdc).
Note: Fan receives power when the dispenser is powered.
A) If not running, check refrigeration switch and wiring for proper continuity.
B) Check for 120V or 230V AC at pump. Replace pump.
3. Restricted water flow to cabinet water coil and bath.
Check for kinked hose.
6 49179 110613
TROUBLESHOOTING (Continued)
PROBLEM
Dispenser Locked Out
Dispense stations not working.
Cooling system failure.
PROBABLE CAUSE
Refrigeration
Dispense stations not working.
Note: Cooling failure or excessive bath and cabinet temperatures for more than 4 hours will result in dispense lockout or no dispense.
1. Compressor ON/OFF switch.
2. Dirty condenser filter or fins.
REMEDY
Check for "ON" position or no continuity - replace switch.
Clean filter and fins or replace condenser filter. (Filter not supplied on some machines).
3. Condenser fan not running.
A) Check for 120V or 230V AC. Replace fan motor or check fan blades for obstructions.
B) Check compressor LED on circuit board. If ON, relay coil should have power (120 or 230 VAC).
4. Compressor relay not activating.
Check compressor relay coil for 120 or 230vac.
NOTE: Always check power with coil attached. If compressor LED is ON and no 120 or 230vac - replace board.
If yes, 120 or 230vac - replace relay.
Note: Relay contacts are normally open.
5. Compressor not running.
Check compressor thermal overload
(N/C). If open check for dirty condenser filter or adequate ventilation and space around machine.
6. Compressor running and not cooling.
Check refrigeration system for leaks and proper charge.
1. Check Dispense Lockout switch.
(A) Set switch to ON position.
(B) Check switch and harness for proper continuity.
1. Refrigeration or cold water recirculation system.
Check all previous items that pretain to refrigeration or cold water recirculation
7 49179 110613
TROUBLESHOOTING (Continued)
PROBLEM
Dispense station not working
PROBABLE CAUSE REMEDY
1. Dispense Lockout switch set to
OFF position.
Place switch in ON position.
2. Dispense switch failed
All stations dispense concentrate only Main water supply
Check switch and harness for proper continuity.
Check for ON position.
Frozen bath
Inlet water valve failed
A) Compressor relay/contacts shorted - replace relay.
B) Recirculating pump - replace or check for kinked flex line.
A) Check for 120V or 230V power when dispensing. If yes, replace valve. If no, check harness for proper continuity. Then replace circuit board if needed.
8 49179 110613
TROUBLESHOOTING (Continued)
PROBLEM PROBABLE CAUSE
Dispense station concentrate only
Water solenoid
Dispense station water only
Concentrate out
Product pump not pumping
Pump not turning
REMEDY
Replace solenoid (24vdc) or check wire connection between water valve and main control board.
Replace refill concentrate container or BIB
Check for proper counterclockwise rotation of pump rollers. If counterclockwise, replace pump tubing. If clockwise, wire connection to pump is reversed. Switch wires on terminals.
A) Check speed setting on circuit board and increase speed (turn clockwise)
B) Check for d.c. power to pump motor. If yes, replace motor assy. If no, check harness for proper continuity.
Then replace circuit board if needed.
9 49179 110613
TROUBLESHOOTING (Continued)
PROBLEM
Water leaking beneath machine
Erratic spray during dispense
PROBABLE CAUSE
Water leak filling drip tray or around dispense deck area
1. Initial fill/setup
2. Dispense deck
REMEDY
Some expansion normal. May fill drip tray during initial ice block formation
Inspect or replace fittings clamps, o-rings, solenoids and quick disconnect fittings.
NOTE: Dispense deck area slopes to drain tube that leads to the drip tray.
3. Water pressure greater than 100psi
Install water pressure regulator and reduce to 50 psi.
1. Bath tank overflow.
A) Check all internal water connections.
B) Check internal plumbing connections.
2. Condensation from cabinet cooling coil.
Check for routing of condensation tube to water bath.
Dispense nozzle mixer missing or broken
Replace mixer.
Replace dispense deck solenoid.
Dispense solenoid.
Dispense nozzle dripping water
10 49179 110613
TROUBLESHOOTING (Continued)
PROBLEM
Unit is not working
Difficulty brixing and/or weak beverage
PROBABLE CAUSE
1. Step-down transformer.
2. Main control board.
1. Product viscosity or too cold.
2. Low water pressure.
3. High water pressure.
REMEDY
Check for 120/24 or 230/24 vac. If no 24vac reading, replace step-down transformer.
If 24 vac present and no LED’s lit, replace control board..
Thorough thaw of product before use
(35° - 40°)
Maintain 20 psi or higher and a minimum flow rate of 1 fl oz/sec.
Over 100 psi, install a pressure regulator and set to 50 psi.
Difficulty brixing and/or weak beverage
4. Dispense valve adjustment setting.
A) Perform 3 second water dispense test. Factory setting is 1.0 oz/sec.
Acceptable water flow rate is .-0.8 to 1.5 oz/sec depending on the mix ratio (4+1).
B) Adjust water to proper mix ratio.
Once water is set, adjust motor speed to achieve brix %.
5. Brix ratio.
1. Pump tubing.
2. Use of portable water pump.
Check for proper brix ratio per product using Total Dispense method and or refractometer method.
Inspect, clean, or replace tubing and pump rotor/rollers for ease of rotation.
A) Follow plumbing requirements for pressure and flow rate.
B) Source another portable pump or water supply that meets requirements.
Vacuum leak
Difficulty brixing bag-in-box Inspect all lines and connections from bag-in-box connector to bottle adapter assembly.
11 49179 110613
SERVICE
This section provides procedures for testing and replacing various major components used in this dispenser should service become necessary. Refer to Troubleshooting for assistance in determining the cause of any problem.
WARNING - Inspection, testing, and repair of electrical equipment should be performed only by qualified service personnel. The dispenser should be disconnected from the power source when servicing, except when electrical tests are required and the test procedure specifically states to connect the dispenser to the power source.
COMPONENT ACCESS
WARNING - Disconnect the dispenser from the power source before the removal of any panel or the replacement of any component.
All components are accessible by opening the door, removal of the door panels, dispenser top covers, hopper(s), hopper support plate, splash guard, splash panel w/drip tray, lower front access panel and rear access cover.
Refer to the contents listing for component location.
INDEX
Access Panels ..................................................................................................................................13
Dispense Platform Removal .............................................................................................................14
Ballast ..............................................................................................................................................15
Cabinet Fan ......................................................................................................................................16
Compressor .....................................................................................................................................17
Compressor Switch ..........................................................................................................................23
Condenser Fan .................................................................................................................................24
Control Board (Main) .......................................................................................................................25
Control Board (Portion Control Models) ..........................................................................................26
Circulation Pump .............................................................................................................................29
Dispense Platform Switch ................................................................................................................30
Dispense Pump ................................................................................................................................31
Dispense Motor ................................................................................................................................32
Dispense Valve .................................................................................................................................33
Dispense Switches ...........................................................................................................................34
Cold Water Dispense Switch ............................................................................................................35
Dispense Membrane Switches .........................................................................................................36
Cold Water Membrane Switch ..........................................................................................................37
EMI Filter ..........................................................................................................................................38
Lamp ................................................................................................................................................39
Lamp Holder ....................................................................................................................................39
LED Lamp ........................................................................................................................................40
Rectifier ...........................................................................................................................................41
Relay ................................................................................................................................................42
Resistor ...........................................................................................................................................43
Solenoid (Cold Water) ......................................................................................................................44
Solenoid (Inlet) ................................................................................................................................45
Temperature Probe (Water Bath Thermistor) ...................................................................................46
Temperature Sensor .........................................................................................................................48
Transformer .....................................................................................................................................49
Transformer-Lited Doors ..................................................................................................................50
Circuit Board Triac Map ....................................................................................................................51
Schematic Wiring Diagrams .............................................................................................................52
12 49179 051914
SERVICE(CONT.)
ACCESS PANELS
Location:
All access panels are similar through the whole JDF family (JDF-4S shown). Before removing panels, make sure power is OFF to the machine and water is disconnected accept where indicated in testing procedures. Retain all screws and other attaching hardware for re-assembly.
JDF-4S shown
FIG. 1 ACCESS PANELS
13 49179 110613
SERVICE(CONT.)
DISPENSE PLATFORM REMOVAL
1. Remove concentrate dispense tips by turning 1/4 turn to the left, then pull straight down.
2. Lift and remove product shelf to access dispense platform(s).
3. Remove front thumb screw holding dispense platform(s).
4. Disconnect 12 pin connector above dispense platform in rear.
5. Disconnect 3/8” water line at quick disconnect.
6. Remove dispense platform(s) by pulling forward.
JDF-2S shown
The JDF-4S uses 2 of the two head dispense platforms.
FIG. 2 DISPENSE PLATFORM REMOVAL
14 49179 110613
SERVICE (CONT.)
Ballast (JDF-2S,4S)
FIG. 3 BALLAST
JDF-2S shown
P1684.40
Location:
The door lamp ballast is located inside the dispenser door mounted in the center of the door rear cover.
Test Procedure:
1. Disconnect the dispenser from the power source.
2. Disconnect a black and blue wire from one set of lamp sockets.
3. Connect an ohmmeter to the end of each wire.
4. Check for continuity between the two wires.
If continuity is present as described, the ballast is operating properly.
If continuity is not present as described, replace the ballast.
5. Check for continuity between the other pair of black and blue wires.
5. Remove the wire to the ballast from the back of each bracket.
6. To disengage the ballast wire from the bracket, push a 1/16” allen wrench (or equivalent tool) into the front hole that lines up with the wire in the back.
Pull the wire out.
7. Repeat for each bracket.
8. White jumper must remain in place on the back of the light socket.
9. Remove screws from each ballast. Remove the green ground wire from the ballast bracket by removing the bracket’s bottom screw.
10. Install the single ballast (wires on the bottom) onto the ballast bracket using 2 of the screws previously removed.
11. Attach ballast wires to the back of bulb sockets by pushing wires into holes in back of socket.
Note: Attach black wires to the top sockets, and blue wires to the bottom sockets. Reference electrical schematic if needed.
12. Snap all 4 bulb sockets back onto light panel. Reinstall fluorescent bulbs.
13. Attach green ground wire to the bottom hole of the ballast bracket using 1 screw.
14. Plug in 3-pin connector into the door harness.
15. To replace door cover, re-connect the dispense switch harness to door harness. Fasten with 5 screws.
16. Reconnect power to the unit. Test operation.
Removal and Replacement:
1. Disconnect the dispenser from the power source.
2. Remove door cover by taking out the 5 screws and unplug the dispense switch harness from the door harness. Set door cover and screws aside.
3. Disconnect the 3-pin connector from the ballasts to the door harness.
4. Remove fluorescent bulbs from the brackets. Pull off the four snap-in light sockets from the light panel.
15
FIG. 4 BALLAST TERMINALS
P1219
49179 110613
SERVICE (CONT.)
Cabinet Fan (all Models)
JDF-2S shown
1. Disconnect the dispenser from the power source.
2. Remove the four screws attaching the fan and cover assembly.
3. Gently pull the cover forward and disconnect the
2-pin connector from the main wiring harness.
4. Remove the fan from the cover assembly and discard the old fan.
5. Install the new fan to the cover assembly using screws previously removed.
6. Reconnect the fan to the 2-pin connector on the main wiring harness.
7. Install the fan and cover assembly to the cabinet using screws previously removed.
8. Reconnect power to the dispenser.
P1684.40
FIG. 5 CABINET FAN
Location:
The cabinet fan is located inside the dispenser cabinet mounted in the center behind the fan guard cover.
Test Procedure:
1. Disconnect the dispenser from the power source.
2. Remove the four screws attaching the fan and cover assembly.
3. Gently pull the cover forward and disconnect the
2-pin connector from the main wiring harness.
4. Check for continuity between the two wires on the fan.
If continuity is present as described, the fan is operating properly.
If continuity is not present as described, replace the fan.
Removal and Replacement:
RED
2
1
BLK
FIG. 6 CABINET FAN TERMINALS
P1219
16 49179 110613
SERVICE (CONT.)
LG Compressor (JDF-2S,4S,4D)
P1684.40
FIG. 7 COMPRESSOR
Location:
The compressor is located at the top of the dispenser frame.
1 2 3
GRN Wire
JDF-4S shown
FIG. 8 COMPRESSOR THERMAL
OVERLOAD PROTECTOR LOCATION
1. Compressor Terminal Cover
2. Compressor Relay
3. Thermal Overload Protector
P4298.20
Test Procedures:
Compressor Relay: Refer to FIG. 8
1. Disconnect the dispenser from the power source.
2. Remove compressor terminal cover retainer (1).
3. Connect a voltmeter across the white wire and the blue/black wire. Connect the dispenser to the power source.
The indication must be:
(a) 120 volts ac for two wire 120 volt models or
(b) 230 volts ac for two wire 230 volt models.
5. Disconnect the dispenser from the power source.
If voltage is present as described, proceed to the following test procedures.
If voltage is not present as described, refer to the
Contactor and check the contactor.
6. Disconnect the white wire from the compressor relay.
7. Remove relay from the compressor.
8. Check for continuity across the terminal and the pin socket on the rear of the relay.
If continuity is present as described, the compressor start relay is operating properly.
If continuity is not present as described, replace relay.
Compressor:
1. Remove relay and yhermal overload protector.
2. Check for continuity across the bottom pin on the compressor and the left top pin on the compressor.
If continuity is present as described, the electrical part of the compressor is operating properly.
If continuity is not present as described, replace the compressor.
Thermal Overload Protector:
1. Check for continuity across the terminals on the thermal overload protector (3).
If continuity is present as described, the thermal overload protector is operating properly.
If continuity is not present as described, replace the thermal overload protector.
17 49179 110613
SERVICE (CONT.)
Compressor (Cont.)
Removal and Replacement:
Compressor Relay: Refer to FIG. 8
1. Remove the terminal cover (1)
2. Disconnect the white wire from the compressor relay.
3. Pull relay (2) off of the compressor pins and discard.
4. Push new relay onto the compressor pins.
5. Refer to Fig. 9 and reconnect the wires.
6. Reinstall terminal cover (1).
Compressor Thermal Overload Protector: Refer to
FIG. 8
1. Remove terminal cover (1).
2. Disconnect the BLU/BLK wire of the harness from the thermal overload protector.
3. Remove relay (2).
4. Remove overload protector (3) and discard overload protector.
5. Install new overload protector (3) on to the compressor.
6. Install relay (2).
7. Refer to Fig. 10 and reconnect the thermal overload protector wires.
8. Reinstall terminal cover (1).
Compressor Assy:
NOTE: the refrigerant in the system must be reclaimed by a licensed refrigeration repair person.
NOTE:
Before removal of any refrigeration component
When replacing the compressor it is recommended that the dryer also be replaced.
WHI Wire
FIG. 9 RELAY TERMINALS
Plugs into Relay
BLU/BLK Wire
FIG. 10 THERMAL OVERLOAD PROTECTOR
TERMINALS
6. Install new compressor over the four studs in the dispenser chassis with the fill valve to the right side of the dispenser.
7. Secure compressor to the dispenser chassis using four .25-20 keps nuts and washers.
8. Reconnect tubes from the condenser and the accumulator to the compressor.
9. Reinstall transformer.
10. Evacuate the system.
11. Recharge 120V and 230V system with:
1. Disconnect the tubes from the condenser and the accumulator.
2. Disconnect the compressor wiring harness from the dispenser main wiring harness.
3. Remove the four .25-20 keps nuts and washers securing the compressor to the chassis. Set nuts and washers aside for reassembly.
4. Disconnect and remove the transformer.
5. From the right side of the dispenser lift the compressor assembly over the four studs in the chassis and remove compressor.
JDF-2S - 9 oz. Type R134A refrigerant.
NOTE:
Design Pressures: High 255 - Low 36 psi
JDF-4S & 4D - 10 oz. Type R134A refrigerant.
Design Pressures: High 335 - Low 88 psi
The charging of the system must be done by a licensed refrigeration repair person.
NOTE: Refer to Wiring Diagrams when reconnecting wires to Compressor, Thermal Overload Protector and
Start Relay.
18 49179 110613
SERVICE (CONT.)
GD Compressor (JDF-2S,4S,4D)
JDF-4S shown
P1684.40
FIG. 11 COMPRESSOR
Location:
The compressor is located at the top of the dispenser frame.
1 3
Test Procedures:
Compressor Start Relay: Refer to FIG. 12
WARNING: The compressor capacitor must be properly discharged before proceeding. This is most commonly done on low voltage capacitors by shorting across the terminals with a screwdriver.
1. Disconnect the dispenser from the power source.
2. Remove compressor terminal cover retainer (4).
3. Connect a voltmeter across the white wire and the blue/black wire. Connect the dispenser to the power source.
The indication must be:
(a) 120 volts ac for two wire 120 volt models or
(b) 230 volts ac for two wire 230 volt models.
5. Disconnect the dispenser from the power source.
If voltage is present as described, proceed to the following test procedures.
If voltage is not present as described, refer to the
Contactor and check the contactor.
6. Disconnect the two black wires from the compressor start relay.
7. Remove relay from the compressor.
8. Check for continuity across the upper left terminal and the right pin socket on the rear of the relay.
If continuity is present as described, the compressor start relay is operating properly.
If continuity is not present as described, replace relay.
2 4
FIG.12 COMPRESSOR THERMAL
OVERLOAD PROTECTOR LOCATION
1. Compressor Start Relay
2. Wiring Harness Strain Relief
3. Thermal Overload Protector
4. Compressor Terminal Cover
P4040.40
Compressor:
1. With the compressor start relay (1) removed, disconnect the black wire from the compressor.
2. Check for continuity across the terminal on the compressor and the left pin on the compressor.
If continuity is present as described, the electrical part of the compressor is operating properly.
If continuity is not present as described, replace the compressor.
Thermal Overload Protector:
1. Check for continuity across the terminals on the thermal overload protector (3).
If continuity is present as described, the thermal overload protector is operating properly.
If continuity is not present as described, replace the thermal overload protector.
19 49179 110613
SERVICE (CONT.)
Compressor (Cont.)
Removal and Replacement:
Compressor Start Relay: Refer to FIG. 12
1. Remove the terminal cover (4)
2. Disconnect the wires from the compressor start relay.
3. Pull relay (1) off of the compressor pins and discard.
4. Push new relay onto the compressor pins.
5. Refer to Fig. 26 and reconnect the wires.
6. Reinstall terminal cover (4).
BLU/BLK
GRN
WHI
Compressor Thermal Overload Protector: Refer to
FIG. 12
1. Remove terminal cover (4).
2. Disconnect the BLU/BLK wire of the harness from the thermal overload protector.
3. Disconnect the BLK wire from the Compressor’s upper terminal.
4. Remove overload protector (3) and start relay as an assembly.
5. Remove overload protector (3) and discard overload protector.
6. Install new overload protector (3) on to the relay
(1).
7. Install relay (1) and overload protector (2) on the compressor terminal bracket.
8. Refer to Fig. 27 and reconnect the thermal overload protector wires.
9. Reinstall terminal cover (4).
Compressor Assy:
NOTE: Before removal of any refrigeration component the refrigerant in the system must be reclaimed by a licensed refrigeration repair person.
NOTE: When replacing the compressor it is recommended that the dryer also be replaced.
FIG. 13 RELAY TERMINALS
Plugs into Relay
FIG. 14 THERMAL OVERLOAD PROTECTOR
TERMINALS pressor assembly over the four studs in the chassis and remove compressor.
6. Install new compressor over the four studs in the dispenser chassis with the fill valve to the right side of the dispenser.
7. Secure compressor to the dispenser chassis using four .25-20 keps nuts and washers.
8. Reconnect tubes from the condenser and the accumulator to the compressor.
9. Reinstall transformer.
10. Evacuate the system.
11. Recharge 120V and 230V system with:
1. Disconnect the tubes from the condenser and the accumulator.
2. Disconnect the compressor wiring harness from the dispenser main wiring harness.
3. Remove the four .25-20 keps nuts and washers securing the compressor to the chassis. Set nuts and washers aside for reassembly.
4. Disconnect and remove the transformer.
5. From the right side of the dispenser lift the com-
JDF-2S - 9 oz. Type R134A refrigerant.
Design Pressures: High 255 - Low 36 psi
JDF-4S & 4D - 10 oz. Type R134A refrigerant.
Design Pressures: High 335 - Low 88 psi
NOTE: The charging of the system must be done by a licensed refrigeration repair person.
NOTE: Refer to Wiring Diagrams when reconnecting wires to Compressor, Thermal Overload Protector and
Start Relay.
20 49179 110613
SERVICE (CONT.)
Compressor (JDF-4SB)
P1684.40
FIG. 15 COMPRESSOR
Location:
The compressor is located at the top of the dispenser frame.
1 3 2 4
230V shown
Test Procedures:
Compressor Start Relay: Refer to FIG. 16
WARNING: The compressor capacitor must be properly discharged before proceeding. This is most commonly done on low voltage capacitors by shorting across the terminals with a screwdriver.
1. Disconnect the dispenser from the power source.
2. Remove compressor terminal cover retainer (4).
3. Connect a voltmeter across the white wire and the blue/black wire. Connect the dispenser to the power source.
The indication must be:
(a) 120 volts ac for two wire 120 volt models or
(b) 230 volts ac for two wire 230 volt models.
5. Disconnect the dispenser from the power source.
If voltage is present as described, proceed to the following test procedures.
If voltage is not present as described, refer to the
Contactor and check the contactor.
6. Disconnect the two black wires from the compressor start relay.
7. Remove relay from the compressor.
8. Check for continuity across the upper left terminal and the right pin socket on the rear of the relay.
If continuity is present as described, the compressor start relay is operating properly.
If continuity is not present as described, replace relay.
5 6
FIG. 16 COMPRESSOR THERMAL
OVERLOAD PROTECTOR LOCATION
1. Compressor Start Relay
2. Wiring Harness Strain Relief
3. Thermal Overload Protector
4. Compressor Terminal Cover
5. Cable 230V only
6. Capcitor 230V only
7. Cover, Capacitor 230V only
7
P4068
Compressor:
1. With the compressor start relay (1) removed, disconnect the black wire from the compressor.
2. Check for continuity across the terminal on the compressor and the left pin on the compressor.
If continuity is present as described, the electrical part of the compressor is operating properly.
If continuity is not present as described, replace the compressor.
Thermal Overload Protector:
1. Check for continuity across the terminals on the thermal overload protector (3).
If continuity is present as described, the thermal overload protector is operating properly.
If continuity is not present as described, replace the thermal overload protector.
21 49179 110613
SERVICE (CONT.)
Compressor (Cont.)
Removal and Replacement:
Compressor Start Relay: Refer to FIG. 16
1. Remove the terminal cover (4)
2. Disconnect the wires from the compressor start relay.
3. Pull relay (1) off of the compressor pins and discard.
4. Push new relay onto the compressor pins.
5. Refer to Fig. 16 and reconnect the wires.
6. Reinstall terminal cover (4).
BLU/BLK
GRN
WHI
1. Disconnect the tubes from the condenser and the accumulator.
2. Disconnect the compressor wiring harness from the dispenser main wiring harness.
3. Remove the four .25-20 keps nuts and washers securing the compressor to the chassis. Set nuts and washers aside for reassembly.
4. Disconnect and remove the transformer.
BLU from Capacitor
BRN from Capacitor
FIG. 17 RELAY TERMINALS
Compressor Thermal Overload Protector: Refer to
FIG. 16
1. Remove terminal cover (4).
2. Disconnect the WHI/ORN wire of the harness from the thermal overload protector.
3. Disconnect the BLK wire from the Compressor’s upper terminal.
4. Remove overload protector (3) and start relay as an assembly.
5. Remove overload protector (3) and discard overload protector.
6. Install new overload protector (3) on to the relay
(1).
7. Install relay (1) and overload protector (2) on the compressor terminal bracket.
8. Refer to Fig. 17 and reconnect the thermal overload protector wires.
9. Reinstall terminal cover (4).
Compressor Assy:
NOTE: Before removal of any refrigeration component the refrigerant in the system must be reclaimed by a licensed refrigeration repair person.
NOTE: When replacing the compressor it is recommended that the dryer also be replaced.
Plugs into Relay
FIG. 18 THERMAL OVERLOAD PROTECTOR
TERMINALS
5. From the right side of the dispenser lift the compressor assembly over the four studs in the chassis and remove compressor.
6. Install new compressor over the four studs in the dispenser chassis with the fill valve to the right side of the dispenser.
7. Secure compressor to the dispenser chassis using four .25-20 keps nuts and washers.
8. Reconnect tubes from the condenser and the accumulator to the compressor.
9. Reinstall transformer.
10. Evacuate the system.
11. Recharge 120V and 230V system with:
JDF-4SB - 10 oz. Type R134A refrigerant.
Design Pressures: High 335 - Low 88 psi
NOTE: The charging of the system must be done by a licensed refrigeration repair person.
NOTE: Refer to Wiring Diagrams when reconnecting wires to Compressor, Thermal Overload Protector and
Start Relay.
22 49179 110613
SERVICE (CONT.)
Compressor Switch (all Models)
JDF-4S shown
Removal and Replacement:
1. Disconnect the dispenser from the power source.
2. Remove the cover or splash panel to gain access to the switch.
3. Gently disconnect the wiring harness from the switch.
4. Remove the switch from the mounting bracket and discard.
5. Install the new into the mounting bracket.
6. Reconnect the wiring harness to the new switch.
7. Install covers or panels previously removed.
8. Reconnect power to the dispenser.
P1684.40
FIG. 19 COMPRESSOR SWITCH
Location:
On models JDF-2S and 4S, early models had the switch located on the back of the dispenser next to the water inlet. On later models JDF-2S, 4S, 4D and 4SB, the switch is located on the front left of the dispenser behind the splash panel.
Test Procedure:
1. Disconnect the dispenser from the power source.
2. Remove the two wires from the switch terminals.
3. Check for continuity across the switch terminals with the switch in the “ON” position. Continuity must not be present when the switch is in the “OFF” position.
If continuity is present as described, reconnect the wires to the switch terminals.
If continuity is not present as described, replace the switch.
RED/BLK
BLK
P1219
FIG. 20 COMPRESSOR SWITCH TERMINALS
23 49179 110613
SERVICE (CONT.)
Condenser Fan (all Models)
JDF-4S shown
1. Disconnect the dispenser from the power source.
2. Remove the four screws attaching the fan and cover assembly to the refrigeration cabinet.
3. Gently pull the cover assembly forward and disconnect the 2-pin connector from the fan to the main harness.
4. Remove the fan from the cover assembly and discard.
5. Install the new fan onto the cover assembly.
6. Reconnect the wiring harness to the new fan.
7. Install fan and cover assembly using four screws previously removed.
8. Reconnect power to the dispenser.
P1684.40
FIG. 21 CONDENSER FAN
Location:
The condenser fan is located inside the main frame below the compressor assembly.
Test Procedure:
1. Disconnect the dispenser from the power source.
2. Disconnect the 2-pin from the fan to the main wiring harness.
3. Check for continuity across the fan terminals.
If continuity is present as described, reconnect the wires to the fan terminals.
If continuity is not present as described, replace the fan.
Removal and Replacement:
BLU/BLK
WHI
FIG. 22 CONDENSER FAN TERMINALS
P1219
24 49179 110613
SERVICE (CONT.)
Control Board, Main (all Models)
JDF-4S shown
P3250.25
FIG. 23 CONTROL BOARD
Location:
The Main Control Board is located on the electrical component enclosure behind the splash panel.
Test Procedure:
Power Supply Circuitry:
1. Disconnect the dispenser from the power source.
2. With a voltmeter, back probe check the voltage across pins 1 & 3 of the J6 connector on the wiring harness. Connect the dispenser to the power source. The indication must be 24 volts ac.
3. Disconnect the dispenser from the power source.
If voltage is present as described, proceed to step 4.
If voltage is not present as described, refer to the Wiring
Diagrams and check the dispenser wiring harness back to the transformer (See TRANSFORMER).
4. Disconnect the dispenser from the power source.
5. With a voltmeter, back probe check the voltage across pins 1 & 3 of the J12 connector on the wiring harness. Connect the dispenser to the power source. The indication must be 24 volts ac.
6. Disconnect the dispenser from the power source.
If voltage is not present as described, refer to the Wiring
Diagrams and check the dispenser wiring harness back to the transformer (See TRANSFORMER).
Removal and Replacement:
1. Remove the four #6-32 screws securing the control board to the component bracket.
2. Disconnect all the plugs on the main wiring harness from the connectors on the control board.
3. Remove the spacers from the control board and discard.
4. Install the spacers on to the new control board
5. Reconnect all plugs on the main harness to the connectors on the control board.
6. Install new control board on the component bracket using four #6-32 screws.
NOTE: Verify all ground wires are connected to the grounding stud and secured with nuts.
NOTE: If the main circuit board is being replaced, the technician should also calibrate the water bath thermistor after the new board is installed.
JDF-4S
JDF-2S
FIG. 24 CONTROL BOARD CONNECTORS
25 49179 051914
SERVICE (CONT.)
Portion Control Board (JDF-2S,4S)
FIG. 25 PORTION CONTROL BOARD
P4034.25
Location:
The Portion Control Board is located inside the door cover mounted on the bracket.
Test Procedure:
1. Disconnect the dispenser from the power source.
2. With a voltmeter, back probe check the voltage across pins 1 & 5 of the J6 connector on the wiring harness. Connect the dispenser to the power source. The indication must be 24 volts ac.
3. Disconnect the dispenser from the power source.
If voltage is not present as described, refer to the Wiring
Diagrams and check the dispenser wiring harness back to the transformer (See TRANSFORMER).
Removal and Replacement:
1. Remove the five screws securing the door cover to the door frame.
2. Carefully pull the cover forward and disconnect all switch harnesses from the connectors on the control board.
3. Remove the four #6-20 screws securing the control board to the light panel.
4. Remove the spacers from the control board and discard the old board.
5. Install the spacers on to the new control board.
6. Install new control board on the light panel using four #6-20 screws.
7. Position the door cover to the door frame and reconnect all switch harnesses to the connectors on the control board.
8. Secure the door cover to the frame with the five screws previously removed.
J-8
J-7
J-9
J-6
J-1
J-2
J-3
J-4
Cold Water Switch
Left Left Dispense Switch
Left Middle Dispense Switch
Right Middle Dispense Switch
J-5
J-6
Right Right Dispense Switch
Main Harness
J-7 N/A
J-8 N/A
J-9 N/A
J-2
J-3
J-4
J-1
J-5
FIG. 26 CONTROL BOARD CONNECTORS
26 49179 110613
SERVICE (CONT.)
Push Button Control Board (JDF-4D)
PO W
ER
CO
O
LI NG
P4081.25
FIG. 27 PUSH BUTTON CONTROL BOARD
Location:
The Push Button Control Board is located inside the door cover mounted on the bracket.
Removal and Replacement:
1. Remove the five screws securing the door cover to the door frame.
2. Carefully pull the cover forward and disconnect all switch harnesses from the connectors on the control board.
3. Remove the four #6-20 screws securing the control board to the light panel.
4. Remove the spacers from the control board and discard the old board.
5. Install the spacers on to the new control board.
6. Install new control board on the light panel using four #6-20 screws.
7. Position the door cover to the door frame and reconnect all switch harnesses to the connectors on the control board.
8. Secure the door cover to the frame with the five screws previously removed.
Test Procedure:
1. Disconnect the dispenser from the power source.
2. With a voltmeter, back probe check the voltage across pins 1 & 5 of the J6 connector on the wiring harness. Connect the dispenser to the power source. The indication must be 24 volts ac.
3. Disconnect the dispenser from the power source.
If voltage is not present as described, refer to the Wiring
Diagrams and check the dispenser wiring harness back to the transformer (See TRANSFORMER).
J-9
J-7
J-11
J-10
J-1 N/A
J-6 Main Harness
J-7 N/A
J-9
J-10
J-11
Rinse Switch
Dispense Nozzles (Disable)
Dispense Switches
J-6
FIG. 28 CONTROL BOARD CONNECTORS
27 49179 110613
SERVICE (CONT.)
Portion Control Board (JDF-4D)
PO
W
ER
LI
NG
CO
FIG. 29 PORTION CONTROL BOARD
P4081.25
Location:
The Portion Control Board is located inside the door cover mounted on the bracket.
Test Procedure:
1. Disconnect the dispenser from the power source.
2. With a voltmeter, back probe check the voltage across pins 1 & 5 of the J6 connector on the wiring harness. Connect the dispenser to the power source. The indication must be 24 volts ac.
3. Disconnect the dispenser from the power source.
If voltage is not present as described, refer to the Wiring
Diagrams and check the dispenser wiring harness back to the transformer (See TRANSFORMER).
Removal and Replacement:
1. Remove the five screws securing the door cover to the door frame.
2. Carefully pull the cover forward and disconnect all switch harnesses from the connectors on the control board.
3. Remove the four #6-20 screws securing the control board to the light panel.
4. Remove the spacers from the control board and discard the old board.
5. Install the spacers on to the new control board.
6. Install new control board on the light panel using four #6-20 screws.
7. Position the door cover to the door frame and reconnect all switch harnesses to the connectors on the control board.
8. Secure the door cover to the frame with the five screws previously removed.
J-8
J-7
J-6
J-1
J-2
J-3
J-4
Cold Water Switch
Left Left Dispense Switch
Left Middle Dispense Switch
Right Middle Dispense Switch
J-5
J-6
Right Right Dispense Switch
Main Harness
J-7 N/A
J-8 N/A
J-9 N/A
J-2
J-3
J-4
J-1
J-5
J-9
FIG. 30 CONTROL BOARD CONNECTORS
28 49179 110613
SERVICE (CONT.)
Circulation Pump (all Models)
FIG. 31 CIRCULATION PUMP
Location:
The Circulation Pump is located on top of the water bath tank cover.
Test Procedure:
1. Disconnect the dispenser from the power source.
2. Disconnect both spade terminals at the recirculating pump. Place meter leads across the harness side that connected to the pump. Connect the dispenser to the power source. Ensure refrigeration switch is turned On, the voltage reading should be applicable to the main power source 120VAC or 230VAC.
No voltage reading, go to refrigeration switch.
3. Install amp clamp around red/black wire going to the recirculating pump. Meter should display around
.30 to .55 amps during operation.
Visually ensure the pump is moving or circulating the water by slightly lifting the silicone tube along side the pump.
No water circulation - replace recircu;lation pump.
Note: Water bath may be completely frozen. Symptom will be no water coming out of any dispense nozzle.
Removal and Replacement:
Note: The dispenser will require to be unplugged from power for 48 hours to allow a completely frozen water bath to thaw before recirculation pump can be replaced
1. Remove dispense platform(s) for ease of taking out recirculating pump.
2. Remove left and right side panels.
3. Remove silicone condensation hose out of bath tank along side recirculating pump.
4. Disconnect pump motor and condenser fan wires
(1/4” spade terminals).
5. Remove 2 screws left and right side of the condenser mounting bracket. Remove condenser fan assembly out the right side of the machine.
6. Release recirculating pump holding bracket right side (2 nuts).
7. Lift up on recirculating pump and maneuver out the right side of the machine
RED/BLK to
Compressor Switch
WHI to Transformer
RED/BLK
WHT
Later Style
120/230VAC
50/60 Hz
Early Style
FIG. 32 CIRCULATION PUMP
P3250.25
29 49179 110613
SERVICE (CONT.)
Dispense Platform Switch (all Models)
JDF-2S shown
Removal and Replacement:
1. Disconnect the dispenser from the power source.
2. Loosen the two #8-32 screws securing the component mounting bracket to the dispenser base.
3. Disconnect the two black wires from the switch.
4. Press the locking tabs of the old switch and remove from the component mounting bracket.
5. Press the new switch into the component mounting bracket.
6. Connect the two black wires to the switch terminals as shown below.
7. Position the component mounting bracket in the dispenser base and secure with two #8-32 screws.
8. Return power to the dispenser.
FIG. 33 DISPENSE PLATFORM SWITCH
Location:
The Dispense Platform Switch is located below the dispenser in the front center and is mounted on the component mounting bracket.
Test Procedure:
1. Disconnect the dispenser from the power source.
2. With a voltmeter, back probe check across the two black wires on the switch.
3. Return power to the dispenser. The indication must be 24 volts ac.
4. Disconnect the dispenser from the power source.
If voltage is present as described, proceed to step 5.
If voltage is not present as described, refer to the Wiring Diagrams and check back to the control board, J5.
5. With an ohmmeter, chech for continuity between the terminals shown in Fig. 34.
Continuity must be present when the switch is in the
ON position.
If continuity is not present, replace the switch.
BLK to J5-4 to Main Circuit Board
!st Type
BLK to Dispense Switch Harness
ORN to J11-5 to Main Circuit Board
2nd Type
ORN to J6-5 Auxillary CB
BLU to J11-4 to Main Circuit Board
3rd Type
BLU to J6-4 Auxillary CB
FIG. 34 SWITCH TERMINALS
P1640
30 49179 031416
SERVICE (CONT.)
Dispense Pump (all Models except JDF-4D)
5. Install the new pump tube around the rotor and position into the rear housing with the clamp resting on the top edge.
6. Install the front housing to be flush with the rear housing.
7. Position the pump assembly back on the platform and secure with four #8-32 x 2.45 screws previously removed.
8. Repeat for remaining pumps.
FIG. 35 DISPENSE PUMP
Location:
The Dispense Pumps are located on the platform assembly.
Removal, Inspection, and Replacement:
1. Loosen the four #8-32 x 2.45 screws securing the pump assembly to the platform.
2. Pry the two halves of the pump housing apart to reveal the pump tube and the rotor.
3. Inspect the pump tubing for signs of wear and replace every six months or as needed.
4. Inspect the pump rotor for signs of wear and replace if necessary.
FIG. 36 DISPENSE PUMP COMPONENTS
P1640
31 49179 110613
SERVICE (CONT.)
Dispense Motor (all Models)
Removal and Replacement:
1. Disconnect the two wires from the dispense motor.
2. Loosen the four #8-32 screws securing the motor to the platform assembly and remove the motor.
3. Inspect the gasket and rubber bushings for signs of wear and replace if necessary.
4. Position the new motor into place with the gasket and bushings onto the platform. Secure with four
#8-32 screws previously removed.
5. Reconnect the two wires to the motor as shown in
Fig. 38.
FIG. 37 DISPENSE MOTOR
Location:
The Dispense Motors are located on the rear of the platform assembly.
Test Procedure:
1. Disconnect the dispenser from the power source.
2. With a voltmeter, check the voltage across the two wire terminals of the motor assembly. Connect the dispenser to the power source. The indication must be 24 volts ac.
3. Disconnect the dispenser from the power source.
If voltage is present as described, replace the motor.
If voltage is not present as described, refer to the Wiring
Diagrams and check the dispenser wiring harness back to the transformer (See TRANSFORMER).
FIG. 38 DISPENSE MOTOR CONNECTORS
32 49179 110613
SERVICE (CONT.)
Dispense Valve (all Models)
Removal and Replacement:
1. Disconnect the two wires from the dispense valve.
2. Remove the #6-32 screw and plate securing the water manifold tube to the valve.
3. Loosen the two #6-32 screws securing the valve to the platform assembly and remove the valve.
4. Install the new valve onto the platform and secure with two #6-32 screws previously removed.
5. Inspect the o-ring on the manifold tube connector for signs of wear and replace if necessary.
6. Connect the water manifold tube to the valve and secure in place with the plate and #6-32 screw previously removed.
7. Reconnect the two wires to the valve as shown in
Fig. 40.
FIG. 39 DISPENSE VALVE
Location:
The Dispense Valves are located at the front of the platform assembly.
Test Procedure:
1. Disconnect the dispenser from the power source.
2. With a voltmeter, check the voltage across the two wire terminals of the valve solenoid. Connect the dispenser to the power source. The indication must be 24 volts ac.
3. Disconnect the dispenser from the power source.
If voltage is present as described, replace the valve.
If voltage is not present as described, refer to the Wiring
Diagrams and check the dispenser wiring harness back to the transformer (See TRANSFORMER).
YEL to Control Board
Dispense Station
#1 WHI/VIO
Dispense Station
#2 WHI/ORN
Dispense Station
#3 WHI/VIO
Dispense Station
#4 WHI/ORN
FIG. 40 DISPENSE VALVE CONNECTORS
P3503
33 49179 110613
SERVICE (CONT.)
Dispense Switches (JDF-2S, JDF-4S)
FIG. 41 DISPENSE SWITCHES
Location:
The dispense switches are located on the lower outside of the dispenser door.
1. Disconnect the dispenser from the power source.
2. Remove the five screws attaching the dispenser door cover to the door and move the door cover to gain access to the switches.
3. Disconnect the wires on the dispense switch to be removed from the door wiring harness.
4. Compress the clips inside the door on the dispense switch and gently push the switch through the opening.
5. Push new switch into the opening and spread the clips to hold the switch in the door.
6. Reconnect the wires to the dispense switch from door wiring harness.
7. Reinstall the door cover and secure with the five screws previously removed.
8. Refer to Fig. 42 when reinstalling wires.
BLK
RED
Test Procedure:
1. Disconnect the dispenser from the power source.
2. Remove the five screws attaching the dispenser door cover to the door and move the door cover to gain access to the switches.
3. With a voltmeter, check the voltage across the two wires for each dispense switch. Connect the dispenser to the power source. The indication must be +5 volts dc.
BLK
GRN
Station #2
BLK
ORN
If voltage is present as described, proceed to #4.
If voltage is not present as described, refer to the Wiring Diagrams and check the dispenser wiring harness.
Station #1
BLK
YEL
Station #4
4. Check for continuity across the terminals (top right to top left) of the dispense switch with the switch in the “ON” position. Continuity must not be present when the switch is in the “OFF” (released) position.
Station #3
FIG. 42 DISPENSE SWITCH TERMINALS
P1449
If continuity is present as described, reconnect the door wiring harness, the switch is operating properly.
If continuity is not present as described, replace the switch.
Removal and Replacement:
34 49179 110613
SERVICE (CONT.)
Cold Water Dispense Switch (JDF-4S only)
FIG. 43 COLD WATER DISPENSE SWITCH
Location:
The cold water dispense switch is located on the lower outside of the dispenser door.
Test Procedure:
1. Disconnect the dispenser from the power source.
2. Remove the five screws attaching the dispenser door cover to the door and move the door cover to gain access to the switch.
3. With a voltmeter, check the voltage across the two wires for the dispense switch. Connect the dispenser to the power source. The indication must be +5 volts dc.
1. Disconnect the dispenser from the power source.
2. Remove the five screws attaching the dispenser door cover to the door and move the door cover to gain access to the switches.
3. Disconnect the wires on the dispense switch from the door wiring harness.
4. Compress the clips inside the door on the dispense switch and gently push the switch through the opening.
5. Push new switch into the opening and spread the clips to hold the switch in the door.
6. Reconnect the wires to the dispense switch from door wiring harness.
7. Reinstall the door cover and secure with the five screws previously removed.
8. Refer to Fig. 44 when reinstalling wires.
BLK
BLU If voltage is present as described, proceed to #4.
If voltage is not present as described, refer to the Wiring Diagrams and check the dispenser wiring harness.
4. Check for continuity across the terminals (top right to top left) of the dispense switch with the switch in the “ON” position. Continuity must not be present when the switch is in the “OFF” (released) position.
If continuity is present as described, reconnect the door wiring harness, the switch is operating properly.
If continuity is not present as described, replace the switch.
Removal and Replacement:
35
FIG. 44 COLD WATER SWITCH TERMINALS
P1449
49179 110613
SERVICE (CONT.)
Dispense Membrane Switch (all Models)
COLD W
ATER
FIG.45 MEMBRANE SWITCHES
Location:
The dispense buttons are located on the lower outside of the dispenser door and actuate switches on the dispense switch board located on the inside of the door.
1. Disconnect the dispenser from the power source.
2. Open the dispenser door.
3. Remove the four #8-32 screws securing the lower door panel and remove the panel.
4. Disconnect the six pin harness from the switch board.
5. Carefully peel the membrane switch from the front of the switch bezel.
6. Remove any excess adhesive from the bezel surface.
7. Remove the backing from the new membrane switch.
8. Feed the membrane switch harness through the openning and apply the new membrane switch to the switch bezel.
9. Connect the switch harness to the control board.
Test Procedures:
NOTE : Before continuing, check that the ribbon cable is properly connected to the control board and not a pin off in either direction.
1. Disconnect the dispenser from the power source.
2. Remove the rear panel and disconnect ribbon cable.
3. Check for continuity of the switches using pin #1as common.
If continuity is not present when the appropriate switch
#1 Common
#2 ON/STOP
#3 Large
#4 Medium
#5 Small is pressed, the Membrane Switch must be replaced.
If continuity is present, chech the short harness going to J6 on the Control Board.
Removal and Replacement:
PORTION CONTROL
FIG. 46 MEMBRANE SWITCH
36 49179 110613
SERVICE (CONT.)
Cold Water Dispense Membrane Switch (all Models)
COLD W
ATER
FIG.47 MEMBRANE SWITCHES
Location:
The dispense buttons are located on the lower outside of the dispenser door and actuate switches on the dispense switch board located on the inside of the door.
1. Disconnect the dispenser from the power source.
2. Open the dispenser door.
3. Remove the four #8-32 screws securing the lower door panel and remove the panel.
4. Disconnect the three pin harness from the switch board.
5. Carefully peel the membrane switch from the front of the switch bezel.
6. Remove any excess adhesive from the bezel surface.
7. Remove the backing from the new membrane switch.
8. Feed the membrane switch harness through the openning and apply the new membrane switch to the switch bezel.
9. Connect the switch harness to the control board.
Test Procedures:
NOTE : Before continuing, check that the ribbon cable is properly connected to the control board and not a pin off in either direction.
1. Disconnect the dispenser from the power source.
2. Remove the rear panel and disconnect ribbon cable.
3. Check for continuity of the switches using pin #1as common.
If continuity is not present when the appropriate switch
#1 Common
#2 Cold Water is pressed, the Membrane Switch must be replaced.
If continuity is present, chech the short harness going to J6 on the Control Board.
Removal and Replacement:
COLD WATER DISPENSE
FIG. 48 MEMBRANE SWITCH
COLD W
ATER
37 49179 110613
SERVICE (CONT.)
PH or PC Membrane Switches (without Bezel)
FIG.45 MEMBRANE SWITCHES
Location:
The membrane switches are located on the lower outside of a standard, 4 lens or graphic door cover.
Each membrane switch connects to a PH or PC switch board (CBA) located on the inner door panel. Switches are connected in logical order from left to right on the switch board (CBA).
Removal and Replacement:
1. Disconnect the dispenser from the power source.
2. Remove the 5 outter screws securing the door cover.
4. Disconnect the membrane switch connector from the switch board.
5. Carefully peel the membrane switch from the front of the door cover.
6. Remove any excess adhesive from the surface.
7. Remove the backing from the new membrane switch.
8. Feed the membrane switch ribbon through the openning and apply the new membrane switch to the door surface.
9. Connect the switch ribbon connector to the switch board. Note: Ensure that you are not a pin off in either direction.
1
Test Procedures: Continuity Check
1. Disconnect the dispenser from the power source.
2. Remove the 5 outter screws securing the door cover.
3. Carefully remove door cover and disconnect all membrane switches from switch board (CBA).
4. Locate ribbon connector (membrane switch) being checked. Install red meter lead on the input or station terminal being checked and install black meter lead on common terminal number 1.
Depress the station button, meter should show continuity 0.00 on display or here audible tone and return back to an open connection when depression
is released from switch.
No continuity as described, replace membrane switch.
#1 Common
#2 ON/STOP
#3 Large
#4 Medium
#5 Small
1
PUSH/HOLD
PORTION CONTROL
FIG. 46 MEMBRANE SWITCH
38 49179 110613
SERVICE (CONT.)
Cold Water Membrane Switch (without Bezel)
FIG.47 MEMBRANE SWITCHES
Location:
The membrane switches are located on the lower outside of a standard, 4 lens or graphic door cover.
Each membrane switch connects to a PH or PC switch board (CBA) located on the inner door panel. Switches are connected in logical order from left to right on the switch board (CBA).
Removal and Replacement:
1. Disconnect the dispenser from the power source.
2. Remove the 5 outter screws securing the door cover.
4. Disconnect the membrane switch connector from the switch board.
5. Carefully peel the membrane switch from the front of the door cover.
6. Remove any excess adhesive from the surface.
7. Remove the backing from the new membrane switch.
8. Feed the membrane switch ribbon through the openning and apply the new membrane switch to the door surface.
9. Connect the switch ribbon connector to the switch board. Note: Ensure that you are not a pin off in either direction.
Test Procedures: Continuity Check
1. Disconnect the dispenser from the power source.
2. Remove the 5 outter screws securing the door cover.
3. Carefully remove door cover and disconnect all membrane switches from switch board (CBA).
4. Locate ribbon connector (membrane switch) being checked. Install red meter lead on the input or station terminal being checked and install black meter lead on common terminal number 1.
Depress the station button, meter should show continuity 0.00 on display or here audible tone and return back to an open connection when depression
is released from switch.
No continuity as described, replace membrane switch.
#1 Common
#2 Cold Water
1
WATER
COLD WATER DISPENSE
FIG. 48 MEMBRANE SWITCH
39 49179 110613
SERVICE (CONT.)
EMI Filter (all Models)
JDF-4S shown
Removal and Replacement:
1. Disconnect the wires from the EMI Filter.
2. Remove the two #8-32 screws and nuts securing the EMI Filter.
3. Remove and discard EMI Filter.
4. Install new EMI Filter using two #8-32 screws and nuts to secure EMI Filter to its former location.
5. Refer to Fig. 50 when reconnecting the wires.
FIG. 49 EMI FILTER
Location:
The EMI Filter is located on the electrical component mounting bracket on the lower front of the dispenser behind the splash panel.
Test Procedure:
1. Disconnect the dispenser from the power source.
2. Disconnect the two black wires and two white wires on the EMI Filter from the power cord and the main wiring harness.
3. Check for resistance between the two black leads on the EMI Filter.
If resistance is present as described the EMI Filter is operating properly.
If resistance is not present as described, replace the
EMI Filter.
118.0 kΩ - 118.5 kΩ
Across either pair
FIG. 50 EMI FILTER CONNECTORS
40 49179 110613
SERVICE (CONT.)
Lamps, Holders and Ballast(s) (Early Models)
1. Disconnect the dispenser from the power source.
2. Remove the five #10-32 screws securing the door cover to the door and move the cover aside to gain access to the light panel.
3. Rotate the lamp to remove from the lamp holders.
4. Pry the lamp holder from light panel.
5. Cut the two wires from the ballast as close the lamp holder as possible and remove the lamp holder.
6. Strip the ends of the wires from the ballast and install the into the new lamp holder.
7. Snap the new lamp holder into the holes on the light panel.
8. Replace the lamps and install the door cover using the five screws previously removed.
FIG. 51 LAMPS & HOLDERS
Location:
The lamps and lamp holders are located on the door light panel behind the door cover.
Test Procedure:
1. Disconnect the dispenser from the power source.
2. Remove the five #10-32 screws securing the door cover to the door and move the cover aside to gain access to the light panel.
3. Rotate the lamp to remove from the lamp holders.
4. Check for continuity across terminals on each end of the lamp.
If continuity is present as described, continue to step 5.
If continuity is not present as described replace the lamp.
5. Check for 24VDC supplied to ballast (dual ballast black to red, single ballast white to red).
If voltage is present as described, replace ballast. If voltage is not present as described, refer to the Wiring
Diagrams and check the wiring harness back to the transfomer/rectifier.
Removal and Replacement:
41
FIG. 52 LAMP HOLDERS
49179 110613
SERVICE (CONT.)
LED Lamps (JDF-2S, JDF-4S)
LED regulator board
FIG. 53 LED DOOR LIGHTS
Location:
The LED door lights are located inside the dispenser door.
Test Procedures:
No illumination at all: First verify that the dispense lockout switch has not been turned off!
1. Disconnect power from the dispenser.
2. Check the voltage across the black and red leads ofJ2 or J3 at the LED regulator board with a voltmeter.
Reconnect power to the dispenser. The indication must be 24 volts dc.
3. Disconnect power from the dispenser.
If voltage is present as described, the LED regulator board is working correctly.
If voltage is not present as described, go to step 4.
4. Check for supply voltage (unregulated +30VDC) across brown wire and white wire at J1 of the regulator board. (FIG 54).
If voltge is present as described, replace LED regulator board.
If voltage is not present as described, check the wiring back to the main CBA.
42
Removal and Replacement:
1. Disconnect power from the dispenser.
2. Remove the five #6-32 screws securing the door cover to the door.
3. Carefully lower the door cover and disconnect the lamp terminals from the LED regulator board.
4. Remove and discard the faulty LED board.
5. Install a new LED regulator board exposing the adhesive backing.
6. Refer to Fig. 54 and reconnect wires to the LED regulator board.
7. Replace the door cover and secure with the five
#6-32 screws.
8. Return power to the dispenser.
J3
J2
J1
White to brown unregulated +30VDC
FIG. 54 LED DOOR LIGHT WIRING
49179 110613
SERVICE (CONT.)
Rectifier (JDF-2S, JDF-4S)
Removal and Replacement:
1. Disconnect the wires from the rectifier.
2. Remove the #10-32 screw securing the rectifier.
3. Remove the rectifier and discard.
4. Secure new rectifier with #10-32 screw.
5. Refer to Fig. 56 and reconnect the wires.
BLU from Door Harness (+)
WHI/GRN to Transformer (~ AC)
WHI/BLK to Transformer (~ AC)
WHI from Door Harness (-)
FIG. 55 RECTIFIER
Location:
The rectifier is located on the electrical component mounting bracket on the lower front of the dispenser behind the splash panel.
Test Procedures:
1. Disconnect the dispenser from the power source.
2. Remove the blue wire and the white wire from the rectifier.
3. Check the voltage across the (+) and (-) terminals on the rectifier with a voltmeter. Connect the dispenser to the power source. The indication must be approximately 24 volts dc.
4. Disconnect the dispenser from the power source.
If voltage is present as described, the rectifier is operating properly.
If voltage is not present as described, refer to the dispenser wiring diagram and check the wiring back to the transformer.
43
FIG. 56 RECTIFIER TERMINALS
49179 110613
SERVICE (CONT.)
Relay (all Models)
FIG. 57 RELAY
Location:
The relay (or contactor) is located inside the dispenser chassis on the lower outside of the component bracket.
Test Procedures:
1. Disconnect the dispenser from the power source.
2. With a voltmeter, check the voltage across the white wire and the white/black wire. Connect the dispenser to the power source. The indication must be: a) 120 volts ac for 120 volt models.
b) 230 volts ac for 230 volt models.
3. Disconnect the dispenser from the power source.
If voltage is present as described, proceed to #4.
If voltage is not present as described, refer to the Wiring Diagram and check the dispenser wiring harness.
If harness has continuity, replace Control Board.
4. Disconnect the blue/black wire and the red/black wires from relay terminals #4 and #6.
5. Connect the dispenser to the power source.
6. Turn on power and check for continuity across terminals on relay.
If continuity is present as described, disconnect the dispenser from power source and reconnect wires to terminals #4 and #6, the relay is working.
If continuity is not present as described, do the same continuity test across terminals #2 and #8. If continuity is present between terminals #2 and #8, reconnect wires to terminals #4 and #6 instead of #2 and #8.
If continuity is not present as described, replace the relay.
Removal and Replacement:
1. Disconnect the wires from the relay.
2. Remove the two #8-32 locking screws securing the relay and mounting bracket to the chassis. Remove and discard relay.
3. Install the new relay to the mounting bracket and then on the chassis using two #8-32 locking screws.
4. Refer to Fig. 58 to reconnect the wires.
Terminal #0
WHI from
Main Harness
Terminal #2
Terminal #4
Terminal #1
BLK from
Main Harness
Terminal #8
BLK from
Main Harness
Terminal #6
WHI/ORN from
Main Harness
FIG. 58 RELAY TERMINALS
44 49179 110613
SERVICE (CONT.)
Resistor (all 230V Models)
Removal and Replacement:
1. Disconnect the dispenser from the power source.
2. Disconnect the resistor from the relay and discard.
3. Install new resistor to the relay as shown below.
4. Return power to the dispenser.
FIG. 59 RESISTOR
Location:
The resistor is located on the relay at the electrical component mounting bracket on the lower front of the dispenser behind the splash panel.
Test Procedures:
1. Disconnect the dispenser from the power source.
2. Remove the resistor from the relay.
3. Check the resistance across the terminals of the resistor with a ohmmeter. The indication must be approximately 36k ± 5%.
4. Disconnect the dispenser from the power source.
If resistance is present as described, the resistor is operating properly.
If resistance is not present as described, replace the resistor.
FIG. 60 RESISTOR TERMINALS
P3864
45 49179 110613
SERVICE (CONT.)
Solenoid - Cold Water (JDF-4S only)
FIG. 61 COLD WATER DISPENSE SOLENOID
Location:
The Cold Water dispense solenoid is located at the inside rear of the chassis frame.
6. Check the solenoid valve for coil action. Connect the dispenser to the power source. Press the Cold
Water dispense switch and listen carefully in the vicinity of the solenoid valve for a “clicking” sound as the coil magnet attracts.
7. Disconnect the dispenser from the power source.
If the sound is heard as described and water will not pass through the solenoid valve, there may be a blockage in the tank water outlet before the solenoid valve or, the solenoid valve may require inspection for wear, and removal of waterborne particles.
If the sound is not heard as described, replace the solenoid valve.
Removal and Replacement:
1. Disconnect the dispenser from the power source.
2. Turn off the water supply to the dispenser.
3. Remove the two wires from the solenoid valve.
4. Disconnect the water line from the solenoid valve.
5. Remove the #10-32 screws securing the solenoid valve to the chassis frame. Remove solenoid valve.
6. Using the #10-32 screws install new solenoid valve to the chassis frame.
7. Reconnect the water lines to solenoid valve.
8. Refer to schematic wiring diagrams when reconnecting the wires.
Test Procedures:
1. Disconnect the dispenser from the power source.
2. Disconnect the two wires from the solenoid valve.
Press the Cold Water dispense switch on front of the door.
3. With a voltmeter, check the voltage across the two wires. Connect the dispenser to the power source.
The indication must be: a) 120 volts ac for two wire 120 volt models, three wire 120/208 volt, and 120/240 volt models.
b) 240 volts ac for two wire 240 volt models.
c) 230 volts ac for two wire 230 volt models.
4. Disconnect the dispenser from the power source.
If voltage is present as described, proceed to #5
If voltage is not present as described, refer to Wiring
Diagrams and check dispenser wiring harness.
WHI/VIO to Control Board
5. Check for continuity across the solenoid valve coil terminals.
If continuity is present as described, reconnect the two wires to the solenoid.
If continuity is not present as described, replace the solenoid valve.
46
WHI to Control Board
FIG. 62 COLD WATER SOLENOID
TERMINALS
49179 110613
SERVICE (CONT.)
Solenoid - Inlet (all Models)
P1445.40
FIG. 63 INLET SOLENOID VALVE
Location:
The inlet solenoid is located inside on the rear of the dispenser base.
Test Procedures:
1. Disconnect the dispenser from the power source.
2. Disconnect the two wires from the solenoid valve.
3. Check for continuity across the solenoid valve coil terminals.
age in the water line before the solenoid valve or, the solenoid valve may require inspection for wear, and removal of waterborne particles.
If the sound is not heard as described, replace the solenoid valve.
Removal and Replacement:
1. Remove the two wires from the solenoid valve.
2. Turn off the water supply to the dispenser.
3. Disconnect the water lines to and from the solenoid valve.
4. Remove the two #8-32 screws securing the solenoid to the dispenser base. Remove solenoid.
5. Install new solenoid valve on the dispenser base and secure with the two #8-32 screws.
6. Securely fasten the water lines to and from the solenoid valve.
7. Refer to Schematic Wiring Diagrams when reconnecting the wires.
BRN to Control Board WHI to Control Board
120V 1.2 kΩ
230V 3.84 kΩ
If continuity is present as described, reconnect the two wires to the solenoid.
If continuity is not present as described, replace the solenoid valve.
4. Check the solenoid valve for coil action. Connect the dispenser to the power source. Listen carefully in the vicinity of the solenoid valve for a “clicking” sound as the coil magnet attracts.
5. Disconnect the dispenser from the power source.
If the sound is heard as described and water will not pass through the solenoid valve, there may be a block-
P1217
FIG. 64 INLET SOLENOID VALVE TERMINALS
47 49179 110613
SERVICE (CONT.)
Temperature Probe (all Models)
(Also known as Water Bath Thermistor)
JDF S Bath Thermistor Calibration:
Recalibration of the bath thermistor should be conducted anytime the main circuit board or the bath thermistor is being replaced.
Recalibration procedure:
Step 1: Remove the front splash panel so you can see the LED’s on the main circuit board.
FIG. 65 TEMPERATURE PROBE
Step 2: Place the “Program” switch in the “On” position. (For early models without the program switch, place the dispense on/off switch in the “off” position).
Step 3: Remove the thermistor from the bath tank and place the thermistor in a known 32º F bath or ice water. It is very critical that the water must be 32º F, in order to calibrate the thermistor properly.
Location:
The temperature probe is located on the top of the tank assembly.
Test Procedure:
1. Disconnect the dispenser from the power source.
2. Remove the top rear cover.
3. With a voltmeter, back probe the connector from the temperature probe.
4. Connect the dispenser to the power source.
5. See the chart for voltage readings.
6. For continuity check, disconnect the dispenser from the power source.
7. Disconnect the two pin connector from the dispenser main wiring harness.
8. With an ohmmeter, check for continuity across the pins for the black or orange and white wires.
9. See the chart for resistance/voltage readings. Alternate check: Leave two pin connector plugged in, place dc voltmeter across two pin connector in parallel, check voltage with dispenser running.
10. Verify wiring to probe.
11. If readings are not present as described, replace the temperature probe.
NOTE: Some meters have difficulty measuring a sensor either rapidly rising or falling in temperature.
Step 4: Push and hold the two left dispense switches
(or both switches on a 2S model). After a few seconds, the green water bath, < 34 LED on the board will flash slowly.
Step 5: While still holding the dispense switches, toggle the “Program” switch from the “on” position, to the “off” position, then back to the “on” position. (For early models without the program switch, toggle the dispense on/off switch from “off”, to “on” and then back “off” again).
Step 6: The green water bath, < 34 LED on the board will flash rapidly for a few seconds. When the green water bath, < 34 LED starts flashing slowly again, release the dispense buttons. The calibration is now complete.
Step 7: Place Program switch back in the “off” position for normal operation. (or place the dispense on/ off switch back in the “on” position for normal operation).
48 49179 060914
SERVICE (CONT.)
Removal and Replacement:
1. Disconnect the dispenser from the power source.
2. Remove the top rear cover.
3. Disconnect the two pin connector from the dispenser main wiring harness.
4. Remove the temperature probe by firmly pullingup on the tube at the tank lid. This will disengage the grommet from the tank lid.
5. Slide a new grommet on to the new temperature probe.
6. Insert the temperature probe through the hole in the tank lid and press the grommet firmly and evenly so that the groove in the grommet fits into the tank lid.
7. Reconnect the two pin connector to the dispenser main wiring harness.
BLKor ORN pin 1
WHI pin 2
FIG. 66 TEMPERATURE PROBE
TEMP RESISTANCE VOLTAGE
SHORTED 0 Ω 0VDC
31.2k - 34k Ω 3.0VDC
32° F
0.0° C
77° F
25.0° C
9.8k - 10.2k Ω 1.5VDC
OPEN INFINITE 5.0VDC
NOTE: ALL FIGURES LISTED ABOVE ARE APPROXIMATE.
49 49179 051914
SERVICE (CONT.)
Temperature Sensor (all Models)
FIG. 67 TEMPERATURE SENSOR
Location:
The Temperature Sensor is located inside the cabinet between the fan and the water coil.
Removal and Replacement:
1. Remove the left side housing panel.
2. Disconnect the plug on the temperature sensor leads from the connector on the dispenser main harness.
3. Open the cabinet door and remove the product containers.
4. Remove the cabinet fan and fan guard assembly.
5. Clip off the connector and pull the temperature sensor from the top left rear of the cabinet and discard.
6. Push new temperature sensor wires into the grommet at the top left rear of the cabinet and secure to sensor mounting clip.
7. Refer to Fig. 68 and connect the wires to the new plug.
8. Connect the sensor plug to the connector from the main harness.
9. Reinstall the cabinet fan and guard assembly.
10. Reinstall the left side housing panel.
Test Procedures:
1. Remove the left side housing panel.
2. Connect a voltmeter across the two leads of the temperature sensor (leave plug connected);
The indication must be: a) Approx. 1.4 vdc @ 71° F b) Approx. 2.6 vdc @ 32° F
1. RED to GRY J7-1
(Control Board) Positive
2. BLK to WHI/BLK J7-2
(Control Board) Negative
If voltage reading is 0v, the Control Board is not supplying the necessary 5v and should be replaced. If the reading stays at 5vdc, replace sensor.
Alternate Test:
2. Disconnect the plug on sensor leads and check resistance as indicated in chart.
If resistance reading is not within the range listed in chart, replace sensor.
2 1
FIG. 68 TEMPERATURE SENSOR
TEMP RESISTANCE VOLTAGE
SHORTED 0 Ω 0VDC
32° F
0° C
77° F
25.0° C
5645k Ω
2k Ω
2.5VDC
1.1VDC
OPEN INFINITE 5.0VDC
NOTE: ALL FIGURES LISTED ABOVE ARE APPROXIMATE.
50 49179 031416
SERVICE (CONT.)
Transformer (all Models)
C
C
P3864
FIG. 69 TRANSFORMER
Location:
The transformer is located on the electrical component mounting bracket on the lower front of the dispenser behind the splash panel.
Removal and Replacement:
1. Loosen the two #8-32 screws securing the component bracket to the dispenser housing base.
2. Pull component bracket out the front of the dispenser far enough so the transformer can be disconnected from the main wiring harness.
3 Remove the two #6-32 keps nuts securing the transformer to the component bracket.
5. Remove and discard the transformer.
6. Install new transformer on the component bracket and secure with two #6-32 keps nuts.
7. Refer to Fig. 70 and connect the transformer to the main wiring harness.
8. Place the component bracket into position and tighten the two #8-32 screws.
Test Procedure:
1. Disconnect the dispenser from the power source.
2. Check the voltage across black wire and the white wire from the main harness. Connect the dispenser to power source. The indication must be: a) 120 volts ac for two wire 120 volt models, three wire 120/208 volt and three wire 120/240 volt models.
b) 240 volts ac for two wire 240 volt models.
c) 230 volts ac for two wire 230 volt models.
4. Disconnect the dispenser from the power source.
WHI/BLU to Control
Board J6-1,J12-1
WHI from
Power Cord
BLK from
Power Cord
If voltage is present as described, proceed to #5.
If voltage is not present as described, refer to the Wiring Diagrams and check the main wiring harness.
5. Check the voltage between J6-1 and J6-3 at the control board. Connect the dispenser to the power source. The indication must be 24 volts ac.
If voltage is present as described the transformer is operating properly.
If voltage is not present as described, replace the transformer.
BLU to Control
Board J6-3,J12-3
FIG. 70 TRANSFORMER TERMINALS
P1647
51 49179 110613
SERVICE (CONT.)
Transformer - Lited Doors (JDF-2S, JDF-4S)
C
C
P3864
FIG. 71 TRANSFORMER
Location:
The transformer is located on the electrical component mounting bracket on the lower front of the dispenser behind the splash panel.
Test Procedure:
1. Disconnect the dispenser from the power source.
2. Disconnect the four pin plug from the main harness from the four pin connector on the transformer.
3 Check the voltage across black wire pin 1 and the white wire pin 2 on the plug from the main harness. Connect the dispenser to power source. The indication must be: a) 120 volts ac for two wire 120 volt models, three wire 120/208 volt and three wire 120/240 volt models.
b) 240 volts ac for two wire 240 volt models.
c) 230 volts ac for two wire 230 volt models.
4. Disconnect the dispenser from the power source.
Removal and Replacement:
1. Loosen the two #8-32 screws securing the component bracket to the dispenser housing base.
2. Pull component bracket out the front of the dispenser far enough so the transformer connector can be disconnected from the main wiring harness.
3 Disconnect the transformer four pin connector from the four pin plug on the main wiring harness.
4. Remove the two #6-32 keps nuts securing the transformer to the component bracket.
5. Remove and discard the transformer.
6. Install new transformer on the component bracket and secure with two #6-32 keps nuts.
7. Connect the four pin connector on the transformer to four pin plug on the main wiring harness.
8. Place the component bracket into position and tighten the two #8-32 screws.
WHI/GRN - T8
WHI/BLK - T12
If voltage is present as described reconnect the plug and the connector and proceed to #5.
If voltage is not present as described, refer to the Wiring Diagrams and check the main wiring harness.
WHI - 120V T2, 240V T6
BLK - TI
FIG. 72 TRANSFORMER TERMINALS
P1647
5. Check the voltage between J3-5 and J3-6 on the six pin connector at the control board. Connect the dispenser to the power source. The indication must be 24 volts ac.
If voltage is present as described the transformer is operating properly.
If voltage is not present as described, replace the transformer.
52 49179 110613
1. Compressor Relay Q25
2. Station 2 Water Q27
3. Station 1 Water Q28
4. Station 1 Concentrate Q23
5. Station 2 Concentrate Q18
6. Station 3 Concentrate Q17
7. Station 4 Concentrate Q13
8. Station 3 Water Q7
9. Cold Water Valve Q11
10. Inlet Water Valve Q10
11. Station 4 Water Q8
Triac Map
2
1 10
9
6 7
8
3
4 5
11
53 49179 012214
ELECTRICAL SCHEMATIC DIAGRAM for JDF-2S
(Models with LED Lited Doors)
SCHEMATIC WIRING DIAGRAM JDF-2S
120V
MODELS
L1 N
220-230V
MODELS
GND L1 N
Models with Dual Dispense Option
BLU
TRANSFORMER
WHI/BLU
O
L
D
A N
E
I
L
BLK
WHI
GRN
A B
A B
EMI
FILTER
A B
A B
BLU
TRANSFORMER
WHI/BLU A
D
L
O
N
E
I
L
BLK
WHI
BLU/BLK
COMPRESSOR ASSY
COMPRESSOR
MOTOR
LIMIT
THERM.
WHI
K1
WHI/BLK
3
6 5
2
N
4
PTC
ASSY 1
WHI
CONDENSOR FAN
BLU/BLK
MOTOR
WHI
BLU/BLK
K1
RED/BLK
RED
LEFT
DISPENSE
PUMP
VIO RED
RIGHT
DISPENSE
PUMP
ORN
WHI RECIR.
PUMP
GRN
WHI/VIO
1
WHI/VIO
RED/BLK
RED/BLK BLK
REFRIGERATION
SWITCH
WHI BLK
WHI/VIO
LEFT
DISPENSE
SOL
YEL YEL
RIGHT
DISPENSE
SOL
WHI/ORN
VIO
WHI/ORN
YEL
VIO
WHI/ORN
YEL
RED
ORN
12
RED
ORN
RED
ORN
VIO
YEL
WHI/ORN
WHI/VIO
J2-1
J2-6
WHI/BLU
BLU
WHI/BLU
BLU
J6-1
J6-3
J12-1
J12-3
C
P
BOARD
BRN
J3-1
J3-2
J7-1
J7-2
J9-1
J9-2
RED
WHI/RED
GRY
WHI/BLK
BLK or ORN
WHI
WATER INLET
VALVE
SOL
WHI
RED
BLK
Models with Membrane Switches
AUXILLARY
CONTROL BOARD
J6-1
J6-5
BLK
RED
BLU
YEL
ORN
J11-1
J11-5 J5-1
J8-1 J8-2
J5-4
WHI
FAN
1 t
WATER BATH
THERMISTOR
Models with Mechanical Switches t
CABINET
THERMISTOR
BLK
RIGHT
DISPENSE
SWITCH
RED
1
GRN or YEL
RED
BLK
BLK
BLK
LEFT
DISPENSE
SWITCH
GRN
STATIC
SHIELD
STATIC
SHIELD
BLK
DISPENSE
STATION
#1
PUSH BUTTON OPTION
DISPENSE
STATION
#2
ORN
ORN
BRN YEL
BLK
BRN
STATIC
SHIELD
STATIC
SHIELD
BLK
PROGRAM
SWITCH
DISPENSE
STATION
#1
DISPENSE
STATION
#2
DISPENSE
LOCKOUT
SWITCH
EARLY MODELS
DISPENSE
LOCKOUT
SWITCH
Chassis
Ground
Chassis
Ground
WHI
BRN
GRN
Models with Lited Doors
+
_
BLK
RED
WHI
BRN
GRN
Door
Ground
RED
BLK
J2-1
Regulator
Board
J3-1
RED
BLK
J1-1
J6-1
J6-5
BLK
RED
YEL
BLU
ORN
J11-1
J11-5
RED
BLK
+
_
120 VOLTS AC or
220-230 VOLTS AC
2 WIRE
SINGLE PHASE
BLU
BLU
BRN
DISPENSE
LOCKOUT
SWITCH
LATE MODELS
54 49179 031416
ELECTRICAL SCHEMATIC DIAGRAM for JDF-2S
(Models with Flourescent Lited Doors)
WHI
GRN
BRN
BRN
WHI
WHI
WHI
RED
BLK
WHI
WHI
RED
BLK
WHI
BLK
DISPENSE LOCKOUT SWITC
WHI
BLK
GRN
BLU or BRN
WHI/BLK
WHI/GRN
GRN
WHI
BLU or BRN RED
WHI
GRN
BLU
BLU
BLK
BLK
BLU
BRN
GRN/YEL
L I N E
L O A D
BRN/WHI
WHI/GRN
BLK
WHI
L I N E
L O A D
T STAR
RUN
GRN/YEL-16
TER INLET VA
BLK
BLK
1
WHI
BLK
BLK WH
WHI/BLK
BRN
BLK
WHI
J1-5
J1-1
C O N T R O L P C B O A R D
DISPENSE SWITC DISPENSE SWITC
GRN or YEL RE BLK BLK
BLK RE
RECIR. PUMP
J2-5
J3-1
J2-1
J5-1
J1-3
J1-1
J4-5
J5-5
J3-5
J4-1
SMALL
MEDIUM
LARGE
STOP/PLUS
MEDIUM
LARGE
SMALL
STOP/PLUS
DISPENSE
DISPENSE
LOCKOUT SWITCH
55 49179 110613
SCHEMATIC WIRING DIAGRAM JDF-2S PUSH/HOLD
(OVAL SWITCH MEMBRANE)
120V
MODELS
L1 N
220-230V
MODELS
GND L1 N
Models with Dual Dispense Option
BLU
TRANSFORMER
WHI/BLU A
D
L
O
N
E
I
L
BLK
WHI
GRN
A B
A B
EMI
FILTER
A B
A B
BLU
TRANSFORMER
WHI/BLU A
D
L
O
N
E
I
L
BLK
WHI
COMPRESSOR ASSY
C
A P
Protector
RELAY
1
BRN/WHT
2
BLK
BRN
BLUE
Start Capacitor
WHT
CONDENSOR FAN
BLU/BLK
MOTOR
WHI
BLU/BLK
K1
RED/BLK
RED
LEFT
DISPENSE
PUMP
VIO RED
RIGHT
DISPENSE
PUMP
ORN
WHI RECIR.
PUMP
GRN
WHI/VIO
1
WHI/VIO
RED/BLK
WHI
K1
WHI/BLK
RED/BLK BLK
REFRIGERATION
SWITCH
WHI BLK
J3-1
J3-2
COLD WATER
VALVE
WHI/VIO
SOL
BRN
RED
WHI/RED
WHI
WATER INLET
VALVE
SOL
WHI
RED
BLK
WHI/VIO
LEFT
DISPENSE
SOL
YEL YEL
RIGHT
DISPENSE
SOL
WHI/ORN
VIO
WHI/ORN
YEL
VIO
WHI/ORN
YEL
RED
ORN
12
RED
ORN
RED
ORN
VIO
YEL
WHI/ORN
WHI/VIO
J2-1
J2-6
J7-1
J7-2
J9-1
J9-2
GRY
WHI/BLK
BLK or ORN
WHI
WHI
FAN
1 t
WATER BATH
THERMISTOR t
CABINET
THERMISTOR
Models with P/H Membrane Switches
J13-1
Models with Lit Doors
AUXILLARY
CONTROL BOARD
Push & Hold
Connector J13-6
STATIC
SHIELD
STATIC
SHIELD
DISPENSE
STATION
#1
DISPENSE
STATION
#2
WHI/BLU
BLU
WHI/BLU
BLU
J6-1
J6-3
J12-1
J12-3
J11-1
J11-5 J8-1
J15-1
YEL
ORN
BLU
J15-4
J5-1
J5-4
GRY
RED
BLK
BLK
Regulator
Board
J2-1 J3-1
J1-1
+ + -
RED
BLK
120 VOLTS AC or
220-230 VOLTS AC
2 WIRE
SINGLE PHASE
44745.0002 A 11/18 © 2011 BUNN-O-MATIC CORPORATION
1
BLK
BRN
DISPENSE
LOCKOUT
SWITCH
BLK
Chassis
Ground
PROGRAM
SWITCH
Chassis
Ground
WHI
BRN
GRN
WHI
BRN
GRN
Door
Ground
56 49179 011619
SCHEMATIC WIRING DIAGRAM JDF-2S PORTION CONTROL
(OVAL SWITCH MEMBRANE) GRN
120V
MODELS
L1 N
220-230V
MODELS
GND L1 N
BLU
TRANSFORMER
WHI/BLU A
D
L
O
N
E
I
L
BLK
WHI
A B
A B
COMPRESSOR ASSY
C
A P
Protector
RELAY
1
BRN/WHT
2
BLK
BRN BLUE
Start Capacitor
WHT
WHI
K1
RED
BLU/BLK
STATION 1
DISPENSE
PUMP
VIO
K1
RED/BLK
RED
STATION 2
DISPENSE
PUMP
BLU/BLK
MOTOR
WHI
CONDENSOR FAN
WHI RECIR.
PUMP
GRN
RED/BLK
RED/BLK BLK
REFRIGERATION
SWITCH
ORN
WHI/BLK
WHI BLK
WHI/VIO
1
WHI/VIO
WHI/VIO
STATION 1
DISPENSE
SOL
YEL YEL
STATION 2
DISPENSE
SOL
WHI/ORN
VIO
WHI/ORN
YEL
RED
ORN
12
VIO
WHI/ORN
YEL
RED
ORN
RED
ORN
VIO
YEL
WHI/ORN
WHI/VIO
J2-1
J2-6
BLU
TRANSFORMER
WHI/BLU A
D
L
O
N
E
I
L BLK
WHI
COLD WATER
WHI/VIO
BRN
J3-1
J3-2
J7-1
J7-2
J9-1
J9-2
VALVE
SOL
WATER INLET
VALVE
SOL
RED
WHI/RED
GRY
WHI/BLK
WHI
WHI
BLK or ORN
WHI t
WATER BATH
THERMISTOR
1
RED
BLK FAN t
CABINET
THERMISTOR
EMI
FILTER
A B
A B
120 VOLTS AC or
220-230 VOLTS AC
2 WIRE
SINGLE PHASE
44745.0001 A 11/18 © 2011 BUNN-O-MATIC CORPORATION
Models with Lit Doors
J13-1
J13-6
WHI/BLU
BLU
WHI/BLU
BLU
J6-1
J6-3
J12-1
J12-3
BLK
RED
YEL
BLU
ORN
J11-1
J11-5
BRN
J8-1 J8-2
WHI
J15-1
J15-4
J5-1
J5-4
BLK
BLK
BRN
BLU
1
DISPENSE
LOCKOUT
SWITCH
Portion Control
Connector
Models with P/C Membrane Switches
AUXILLARY
CONTROL BOARD
Chassis
Ground
WHI
BRN
GRN
BLK
Chassis
Ground
PROGRAM
SWITCH
WHI
BRN
GRN
Door
Ground
STATIC
SHIELD
DISPENSE
STATION
#1
STATIC
SHIELD
DISPENSE
STATION
#2
Regulator
Board
J2-1 J3-1
J1-1
+ + -
RED
BLK
57 49179 011619
ELECTRICAL SCHEMATIC DIAGRAM for JDF-4S
(Models with LED Lited Doors)
SCHEMATIC WIRING DIAGRAM JDF-4S
GRN
120V
MODELS
L1 N
220-230V
MODELS
GND L1 N
VIO
WHI/ORN
YEL
VIO
WHI/ORN
YEL
RED
ORN
12
RED
ORN
BLU
TRANSFORMER
WHI/BLU A
D
O
L
N
E
L
I
BLK
WHI
BLU
TRANSFORMER
WHI/BLU A
D
O
L
N
E
L
I
BLK
WHI
COMPRESSOR ASSY
BLU/BLK
LIMIT
THERM.
3
6
4
5
2
N
1
BLU/BLK
RED
STATION 1
DISPENSE
PUMP
VIO
K1
RED/BLK
RED
STATION 2
DISPENSE
PUMP
BLU/BLK
MOTOR
WHI
CONDENSOR FAN
ORN
WHI RECIR.
PUMP
RED/BLK
GRN
REFRIGERATION
SWITCH
RED/BLK BLK
WHI BLK
WHI/VIO
1
WHI/VIO
WHI/VIO
STATION 1
DISPENSE
SOL
YEL YEL
STATION 2
DISPENSE
SOL
WHI/ORN
WHI
K1
WHI/BLK
WHI/VIO
COLD WATER
VALVE
SOL
WHI
RED
ORN
VIO
YEL
WHI/ORN
WHI/VIO
J2-1
J2-6
BRN
WATER INLET
VALVE
SOL
J3-1
J3-2
J7-1
J7-2
J9-1
J9-2
RED
WHI/RED
GRY
WHI/BLK
BLK or ORN
WHI
WHI t
WATER BATH
THERMISTOR
RED
STATION 3
DISPENSE
PUMP
VIO RED
STATION 4
DISPENSE
PUMP
ORN
WHI/VIO
1
TAN
1
A B
A B
RED
BLK FAN t
CABINET
THERMISTOR
Models with Mechanical Switches
EMI
FILTER
A B
A B
WHI/VIO
STATION 3
DISPENSE
SOL
YEL
Models with Membrane Switches
YEL
STATION 4
DISPENSE
SOL
WHI/ORN
AUXILLARY
CONTROL BOARD
VIO
WHI/ORN
YEL
PNK
BLU
GRY
RED
ORN
12
WHI/GRN
GRN
J6-1
J6-5
BLK
RED
BLU
YEL
ORN
WHI/GRN
GRN
PNK
GRY
BLU
TAN
J13-1
J13-6
WHI/BLU
BLU
WHI/BLU
BLU
BLK
RED
BLU
YEL
ORN
J6-1
J6-3
J12-1
J12-3
J11-1
J11-5 J8-1 J8-2
J15-1
YEL
ORN
BLU
J15-4
J5-1
J5-4
GRN or GRY
RED
BLK
BLK
8
1
BLU
COLD WATER
DISPENSE
SWITCH
BLK
BLK
STATION 4
DISPENSE
SWITCH
ORN
BLK
STATION 3
DISPENSE
SWITCH
YEL
BLK
STATION 2
DISPENSE
SWITCH
RED
BLK
STATION 1
DISPENSE
SWITCH
GRN
STATIC
SHIELD
STATIC
SHIELD
STATIC
SHIELD
STATIC
SHIELD
STATIC
SHIELD
YEL
BLK
DISPENSE
STATION
#1
PUSH BUTTON OPTION
DISPENSE
STATION
#2
DISPENSE
STATION
#3
COLD
WATER
SWITCH
DISPENSE
STATION
#4
DISPENSE
STATION
#1
STATIC
SHIELD
DISPENSE
STATION
#2
STATIC
SHIELD
DISPENSE
STATION
#3
STATIC
SHIELD
STATIC
SHIELD
COLD
WATER
SWITCH
DISPENSE
STATION
#4
STATIC
SHIELD
ORN
BRN
DISPENSE
LOCKOUT
SWITCH
EARLY MODELS
BLK
BRN
DISPENSE
LOCKOUT
SWITCH
BLK
Chassis
Ground
PROGRAM
SWITCH
Chassis
Ground
WHI
BRN
GRN
Models with Lited Doors
WHI
BRN
GRN
Door
Ground
+
_
BLK
RED
+
_
RED
BLK
Regulator
Board
J2-1 J3-1
RED
BLK
J1-1
RED
BLK
_
+
RED
BLK
_
+
J6-1
J6-5
BLK
RED
YEL
BLU
ORN
J11-1
J11-5
120 VOLTS AC or
220-230 VOLTS AC
2 WIRE
SINGLE PHASE
BLU
BRN
DISPENSE
LOCKOUT
SWITCH
LATE MODELS
58 49179 031416
ELECTRICAL SCHEMATIC DIAGRAM for JDF-4S
(Models with Flourescent Lited Doors)
WHI
GRN
BRN
BRN
WHI
WHI
WHI
RED
BLK
WHI
WHI
RED
BLK
WHI
BLK
DISPENSE LOCKOU
WHI
BLK
GRN
VIO or BRN
WHI/BLK
WHI/GRN
GRN
WHI
VIO or BRN
WHI
GRN
RED
BLU
BLU
BLK
BLK
BLU
BRN
GRN/YEL
BLK
WHI
BLK
WHI
L I N E
L O A D
L I N E
L O A D
T STAR
RUN
GRN/YEL-16
1
TER INLET VA
BLK
WHI
BRN
WHI/BLK
WHI/VIO
J1-1
J1-5
WHI
BLK
BLK
BLK
C O N T R O L P C B O A R D
RECIR. PUMP
K BL
J2-5
J3-1
J2-1
J3-5
J4-1
J5-1
J1-3
J1-1
J4-5
J5-5
DISPENSE
MEDIUM
LARGE
SMALL
STOP/PLUS
DISPENSE ST
COLD WA
SMALL
MEDIUM
LARGE
STOP/PLUS
MEDIUM
LARGE
SMALL
STOP/PLUS
MEDIUM
LARGE
SMALL
STOP/PLUS
DISPENSE ST
DISPENSE ST
DISPENSE ST
DISPENSE
DISPENSE
DISPENSE
DISPENSE
DISPENSE
DISPENSE ST
COLD WA
DISPENSE ST
DISPENSE ST
DISPENSE ST
59 49179 110613
SCHEMATIC WIRING DIAGRAM JDF-4S PUSH/HOLD
(OVAL SWITCH MEMBRANE) GRN
120V
MODELS
L1 N
220-230V
MODELS
GND L1 N
BLU/BLK
2
3
1
OVERLOAD
PROTECTOR
COMPRESSOR ASSY
C
COMPRESSOR
MOTOR
S
4
3 1
2
M
WHT
WHI
RED
BLU/BLK
STATION 1
DISPENSE
PUMP
VIO
K1
START RELAY
RED/BLK
RED
STATION 2
DISPENSE
PUMP
BLU/BLK
MOTOR
WHI
CONDENSOR FAN
WHI RECIR.
PUMP
GRN
RED/BLK
RED/BLK BLK
REFRIGERATION
SWITCH
ORN
WHI/VIO
1
WHI/VIO
WHI BLK
BLU
TRANSFORMER
WHI/BLU A
D
L
O
N
E
I
L
BLK
WHI
BLU
TRANSFORMER
WHI/BLU A
D
L
O
N
E
I
L BLK
WHI
K1
WHI/BLK
WHI/VIO
STATION 1
DISPENSE
SOL
YEL YEL
STATION 2
DISPENSE
SOL
WHI/ORN
VIO
WHI/ORN
YEL
RED
ORN
12
VIO
WHI/ORN
YEL
RED
ORN
RED
ORN
VIO
YEL
WHI/ORN
WHI/VIO
J2-1
J2-6
J3-1
J3-2
J7-1
J7-2
J9-1
J9-2
RED
WHI/RED
GRY
WHI/BLK
BLK or ORN
WHI t
WATER BATH
THERMISTOR
RED
STATION 3
DISPENSE
PUMP
VIO RED
STATION 4
DISPENSE
PUMP
ORN
COLD WATER
VALVE
WHI/VIO
SOL
WHI
BRN
WATER INLET
VALVE
SOL
WHI
WHI/VIO
1
TAN
1
RED
BLK
A B
A B
FAN t
CABINET
THERMISTOR
EMI
FILTER
A B
A B
Models with P/H Membrane Switches
AUXILLARY
CONTROL BOARD
Models with Lit Doors
+ -
RED
BLK
WHI/VIO
STATION 3
DISPENSE
SOL
YEL YEL
STATION 4
DISPENSE
SOL
WHI/ORN
VIO
WHI/ORN
YEL
PNK
BLU
GRY
RED
ORN
12
WHI/GRN
GRN
WHI/GRN
GRN
PNK
GRY
BLU
TAN
J13-1
J13-6
STATIC
SHIELD
DISPENSE
STATION
#1
STATIC
SHIELD
DISPENSE
STATION
#2
Push & Hold
Connector
STATIC
SHIELD
DISPENSE
STATION
#3
STATIC
SHIELD
COLD
WATER
SWITCH
STATIC
SHIELD
WHI/BLU
BLU
WHI/BLU
BLU
J6-1
J6-3
J12-1
J12-3
J11-1
J15-1
J15-4
J5-1
J5-4
YEL
ORN
BLU
GRY
RED
BLK
BLK
DISPENSE
STATION
#4
+ + -
Regulator
Board
J2-1 J3-1
J1-1
J11-5 J8-1
WHI
BRN
1
+ -
RED
BLK
BLK
BRN
DISPENSE
LOCKOUT
SWITCH
BLK
Chassis
Ground
PROGRAM
SWITCH
Chassis
Ground
WHI
BRN
GRN
WHI
BRN
GRN
Door
Ground
120 VOLTS AC or
220-230 VOLTS AC
2 WIRE
SINGLE PHASE
44746.0002 A 11/18 © 2011 BUNN-O-MATIC CORPORATION
60 49179 011619
SCHEMATIC WIRING DIAGRAM JDF-4S PORTION CONTROL
(OVAL SWITCH MEMBRANE) GRN
120V
MODELS
L1 N
220-230V
MODELS
GND L1 N
BLU/BLK
2
3
1
OVERLOAD
PROTECTOR
COMPRESSOR ASSY
C
COMPRESSOR
MOTOR
S
4
3 1
2
M
WHT
WHI
RED
BLU/BLK
STATION 1
DISPENSE
PUMP
VIO
K1
START RELAY
RED/BLK
RED
STATION 2
DISPENSE
PUMP
BLU/BLK
MOTOR
WHI
CONDENSOR FAN
WHI RECIR.
PUMP
GRN
RED/BLK
RED/BLK BLK
REFRIGERATION
SWITCH
ORN
WHI/VIO
1
WHI/VIO
WHI BLK
BLU
TRANSFORMER
WHI/BLU A
D
L
O
N
E
I
L
BLK
WHI
BLU
TRANSFORMER
WHI/BLU A
D
L
O
N
E
I
L BLK
WHI
K1
WHI/BLK
WHI/VIO
STATION 1
DISPENSE
SOL
YEL YEL
STATION 2
DISPENSE
SOL
WHI/ORN
VIO
WHI/ORN
YEL
RED
ORN
12
VIO
WHI/ORN
YEL
RED
ORN
RED
ORN
VIO
YEL
WHI/ORN
WHI/VIO
J2-1
J2-6
J3-1
J3-2
J7-1
J7-2
J9-1
J9-2
RED
WHI/RED
GRY
WHI/BLK
BLK or ORN
WHI t
WATER BATH
THERMISTOR
RED
STATION 3
DISPENSE
PUMP
VIO RED
STATION 4
DISPENSE
PUMP
ORN
COLD WATER
VALVE
WHI/VIO
SOL
WHI
BRN
WATER INLET
VALVE
SOL
WHI
WHI/VIO
1
TAN
1
RED
BLK
A B
A B
FAN t
CABINET
THERMISTOR
EMI
FILTER
A B
A B
WHI/VIO
STATION 3
DISPENSE
SOL
YEL YEL
STATION 4
DISPENSE
SOL
WHI/ORN
VIO
WHI/ORN
YEL
PNK
BLU
GRY
RED
ORN
12
WHI/GRN
GRN
WHI/GRN
GRN
PNK
GRY
BLU
TAN
J13-1
J13-6
WHI/BLU
BLU
WHI/BLU
BLU
BLK
RED
YEL
BLU
ORN
J11-5
J6-1
J6-3
J12-1
J12-3
J11-1
J15-1
J15-4
J5-1
BRN
J8-1 J8-2
WHI
J5-4
BLK
BLK
BRN
BLU
1
DISPENSE
LOCKOUT
SWITCH
Chassis
Ground
BLK
WHI
BRN
GRN
Chassis
Ground
PROGRAM
SWITCH
Models with Lit Doors
WHI
BRN
GRN
Door
Ground
+ -
RED
BLK
Portion Control
Connector
Models with P/C Membrane Switches
AUXILLARY
CONTROL BOARD
+ + -
Regulator
Board
J2-1 J3-1
J1-1
+ -
RED
BLK
120 VOLTS AC or
220-230 VOLTS AC
2 WIRE
SINGLE PHASE
44746.0003 A 11/18 © 2011 BUNN-O-MATIC CORPORATION
STATIC
SHIELD
DISPENSE
STATION
#1
STATIC
SHIELD
DISPENSE
STATION
#2
STATIC
SHIELD
DISPENSE
STATION
#3
STATIC
SHIELD
STATIC
SHIELD
COLD
WATER
SWITCH
DISPENSE
STATION
#4
61 49179 011619
ELECTRICAL SCHEMATIC DIAGRAM for JDF-4D
(Press & Release Models)
SCHEMATIC WIRING DIAGRAM JDF-4D
GRN
120V
MODELS
L1 N
230V
MODELS
GND L1 N
BLU/BLK
COMPRESSOR ASSY
COMPRESSOR
MOTOR
LIMIT
THERM.
WHI/GRN
BLU
TAN
WHI/ORN
WHI/VIO
STATION 1
DISPENSE
3
6
4
5
2
N
1
WHI
CONDENSOR FAN
BLU/BLK
MOTOR
WHI
BLU/BLK
K1
RED/BLK
PUMP
WHI RECIR.
PUMP
RED/BLK
GRN
WHI
K1
WHI/BLK
REFRIGERATION
SWITCH
RED/BLK BLK
WHI BLK
STATION 2
DISPENSE PUMP
STATION 3
DISPENSE PUMP
VIO
ORN
RED
PNK
ORN
WHI/GRN
1
6
VIO
ORN
RED
PNK
ORN
WHI/GRN
J2-1
J2-6
STATION 4
DISPENSE PUMP
STATION 1
DISPENSE
STATION 2
DISPENSE
SOL
SOL
J13-1
O
A
C
B
R
D
L
P
R
O
N
T
C
O
STATION 3
DISPENSE
STATION 4
DISPENSE
SOL
SOL
WHI/VIO
WHI/ORN
YEL
TAN
BLU
GRY
1
WHI/VIO
WHI/ORN
YEL
TAN
BLU
GRY
6
J13-6
Models with Membrane Switches
J10-1
J10-7
AUXILLARY
CONTROL BOARD
J6-1
J6-5
J8-1
BLK
RED
BLU
YEL
ORN
WHI/BLU
BLU
WHI/BLU
BLU
J6-1
J6-3
J12-1
J12-3
BLK
RED
BLU
YEL
ORN
J11-1
J11-5
BLU
TRANSFORMER
O
L L
I
WHI/BLU
BLK
WHI
BLU
TRANSFORMER
O
L L
I
WHI/BLU
BLK
WHI
COLD WATER
WHI/VIO
VALVE
SOL
WHI
A B
A B
BRN
WATER INLET
VALVE
SOL
WHI
J3-1
J3-2
RED
WHI/RED
J7-1
J7-2
J9-1
J9-2
GRY
WHI/BLK
BLK
WHI
1
J8-1 t
WATER BATH
THERMISTOR
WHI-22
BLK-22 t
CABINET
THERMISTOR
RED
BLK
RED
BLK
FAN
FAN
J15-1
J15-4
J5-1
J5-4
BLK
BLK
EMI
FILTER
A B
A B
1 22
J8-6
J9-1
J9-4
RINSE
SWITCH
DISPENSE
LOCKOUT
SWITCH
BLK
BLK
DISPENSE
SWITCH
#1
DISPENSE
NOZZLE
#1
DISPENSE
SWITCH
#2
DISPENSE
NOZZLE
#2
DISPENSE
SWITCH
#3
POWER
LED
DISPENSE
SWITCH
#4
DISPENSE
NOZZLE
#3
COOLING
LED
STATIC
SHIELD
DISPENSE
NOZZLE
#4
WHI/VIO
WHI/ORN
TAN
120 VOLTS AC or
230 VOLTS AC
2 WIRE
SINGLE PHASE 41649.0000B 03/09 © 2009 BUNN-O-MATIC CORPORATION
BLU
WHI/GRN
62 49179 110613
ELECTRICAL SCHEMATIC DIAGRAM for JDF-4D
(Portion Control Models)
SCHEMATIC WIRING DIAGRAM JDF-4D
GRN
120V
MODELS
L1 N
220-230V
MODELS
GND L1 N
BLU
TRANSFORMER
WHI/BLU A
D
L
O
N
E
I
L
BLK
WHI
BLU
TRANSFORMER
WHI/BLU A
D
L
O
N
E
I
L BLK
WHI
A B
A B
EMI
FILTER
A B
A B
BLU/BLK
COMPRESSOR ASSY
STATION 1
DISPENSE
3
6
4
5
2
N
PTC
ASSY 1
WHI
CONDENSOR FAN
BLU/BLK
MOTOR
WHI
BLU/BLK
K1
RED/BLK
PUMP
WHI RECIR.
PUMP
RED/BLK
GRN
WHI
K1
WHI/BLK
REFRIGERATION
SWITCH
RED/BLK BLK
WHI BLK
STATION 2
DISPENSE PUMP
STATION 3
DISPENSE PUMP
STATION 4
DISPENSE PUMP
VIO
ORN
RED
PNK
ORN
WHI/GRN
1
6
VIO
ORN
RED
PNK
ORN
WHI/GRN
J2-1
J2-6
STATION 1
DISPENSE
SOL
STATION 2
DISPENSE
SOL
STATION 3
DISPENSE
SOL
STATION 4
DISPENSE
SOL
WHI/VIO
WHI/ORN
YEL
TAN
BLU
GRY
1
6
WHI/VIO
WHI/ORN
YEL
TAN
BLU
GRY
J13-1
J13-6
COLD WATER
VALVE
WHI/VIO
SOL
WHI
C
P
BOARD
BRN
WATER INLET
VALVE
SOL
WHI
J3-1
J3-2
RED
WHI/RED
J7-1
J7-2
J9-1
J9-2
GRY
WHI/BLK
BLK
WHI
J8-1
1 t
WATER BATH
THERMISTOR
WHI-22
BLK-22
1
CLOCK t
CABINET
THERMISTOR
RED
BLK
RED
BLK
FAN
FAN
WHI/GRN
BLU
TAN
WHI/ORN
WHI/VIO
Models with Membrane Switches
J10-1
POWER LED
J10-7
COOLING LED
J8-1
J8-6
J6-1
J6-5
BLK
RED
BLU
YEL
ORN
WHI/BLU
BLU
WHI/BLU
BLU
J6-1
J6-3
J12-1
J12-3
BLK
RED
BLU
YEL
ORN
J11-1
J11-5
J15-1
J15-4
J5-1
J5-4
BLK
BLK
AUXILLARY
CONTROL BOARD
J9-1
J9-4
RINSE
SWITCH
BLK
BLK DISPENSE
LOCKOUT
SWITCH
STATIC
SHIELD
STATIC
SHIELD
STATIC
SHIELD
STATIC
SHIELD
STATIC
SHIELD
DISPENSE
STATION
#1
DISPENSE
NOZZLE
#1
DISPENSE
STATION
#2
DISPENSE
NOZZLE
#2
DISPENSE
STATION
#3
DISPENSE
NOZZLE
#3
COLD
WATER
SWITCH
DISPENSE
STATION
#4
DISPENSE
NOZZLE
#4
WHI/VIO
WHI/ORN
TAN
120 VOLTS AC or
220-230 VOLTS AC
2 WIRE
SINGLE PHASE 41649.0001A 02/13 © 2013 BUNN-O-MATIC CORPORATION
BLU
WHI/GRN
63 49179 110613
ELECTRICAL SCHEMATIC DIAGRAM for JDF-4S-SB
SCHEMATIC WIRING DIAGRAM JDF-4S-SB
GRN
120V
MODELS
L1 N
230V
MODELS
GND L1 N
BLU
TRANSFORMER
L
O I
L
WHI/BLU
BLK
WHI
BLU
TRANSFORMER
WHI/BLU
A
D
L
O
N
E
I
L BLK
WHI
BLU/BLK
COMPRESSOR ASSY
COMPRESSOR
MOTOR
LIMIT
THERM.
WHI
K1
WHI/BLK
COLD WATER
VALVE
WHI/VIO
SOL
WHI
3
6
4
5
2
N
1
BLU/BLK
K1
RED/BLK
RED
STATION 1
DISPENSE
PUMP
VIO RED
STATION 2
DISPENSE
PUMP
ORN
CONDENSOR FAN
BLU/BLK
MOTOR
WHI
WHI
RECIR.
PUMP
GRN
WHI/VIO
1
WHI/VIO
RED/BLK
RED/BLK BLK
REFRIGERATION
SWITCH
WHI BLK
WHI/VIO
STATION 1
DISPENSE
SOL
YEL YEL
STATION 2
DISPENSE
SOL
WHI/ORN
VIO
WHI/ORN
YEL
RED
ORN
12
VIO
WHI/ORN
YEL
RED
ORN
RED
ORN
VIO
YEL
WHI/ORN
WHI/VIO
J2-1
J2-6
RED
STATION 3
DISPENSE
PUMP
VIO RED
STATION 4
DISPENSE
PUMP
ORN
WHI/VIO
1
TAN
WHI/VIO
STATION 3
DISPENSE
SOL
YEL YEL
STATION 4
DISPENSE
SOL
WHI/ORN
VIO
WHI/ORN
YEL
PNK
BLU
GRY
RED
ORN
12
WHI/GRN
GRN
WHI/GRN
GRN
PNK
GRY
BLU
TAN
J13-1
J13-6
WHI/BLU
BLU
WHI/BLU
BLU
J6-1
J6-3
J12-1
J12-3
J11-1
120 VOLTS AC or
230 VOLTS AC
2 WIRE
SINGLE PHASE 44746.0001A 06/11 © 2011 BUNN-O-MATIC CORPORATION
J11-5
BRN
WATER INLET
VALVE
SOL
WHI
J3-1
J3-2
J7-1
J7-2
J9-1
J9-2
RED
WHI/RED
GRY
WHI/BLK
BLK or ORN
WHI
J15-1
YEL
ORN
BLU
J15-4
J5-1
J5-4
GRN
RED
BLK
BLK
DISPENSE
LOCKOUT
SWITCH t
WATER BATH
THERMISTOR
BLK
1
BLK
BLK
MAIN POWER
ON/OFF
SWITCH
BLK
WHI WHI
RED
BLK FAN t
CABINET
THERMISTOR
8
1
ORN
YEL
RED
GRN
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
A B
A B
RED
BLK
1
BLK
6
GRN
BLK
1
BLK
6
ORN
BLK
1
BLK
6
YEL
BLK
1
BLK
6
EMI
FILTER
A B
A B
STATIC
SHIELD
DISPENSE
DISPENSE
STATION
#4
STATIC
SHIELD
DISPENSE
DISPENSE
STATION
#3
STATIC
SHIELD
DISPENSE
DISPENSE
STATION
#2
STATIC
SHIELD
DISPENSE
DISPENSE
STATION
#1
64 49179 110613
SCHEMATIC WIRING DIAGRAM JDF-4S-SB PUSH/HOLD
(OVAL SWITCH MEMBRANE)
GRN
120V
MODELS
L1 N
220-230V
MODELS
GND L1 N
A B
A B
EMI
FILTER
BLK
WHI
A B
A B
MAIN ON/OFF SWITCH
BLU/BLK
2
3
1
OVERLOAD
PROTECTOR
COMPRESSOR ASSY
COMPRESSOR
MOTOR
S
4
3
C
1
2
M
WHT
START RELAY
BLU/BLK
MOTOR
WHI
CONDENSOR FAN
BLU/BLK
K1
RED/BLK
RED
STATION 1
DISPENSE
PUMP
VIO RED
STATION 2
DISPENSE
PUMP
ORN
WHI RECIR.
PUMP
GRN
RED/BLK
WHI/VIO
1
WHI
1
WHI/VIO
WHI/VIO
STATION 1
DISPENSE
SOL
YEL
RED
STATION 3
DISPENSE
PUMP
VIO
YEL
STATION 2
DISPENSE
SOL
WHI/ORN
RED
STATION 4
DISPENSE
PUMP
ORN
VIO
WHI/ORN
YEL
RED
ORN
12
WHI
WHI
WHI
WHI
WHI
VIO
WHI/ORN
YEL
12
RED
ORN
WHI/VIO
1
WHI
1
TAN
WHI/VIO
STATION 3
DISPENSE
SOL
YEL YEL
STATION 4
DISPENSE
SOL
WHI/ORN
VIO
WHI/ORN
YEL
RED
ORN
12
WHI
WHI
WHI
WHI
WHI
PNK
BLU
GRY
12
WHI/GRN
GRN
BLU
TRANSFORMER
WHI/BLU A
D
L
O
N
E
L
I
BLK
WHI
BLU
TRANSFORMER
WHI/BLU A
D
L
O
N
E
L
I
BLK
WHI
WHI
K1
WHI/BLK
WHI/VIO
COLD WATER
VALVE
SOL
WHI
RED/BLK BLK
REFRIGERATION
SWITCH
RED
ORN
VIO
YEL
WHI/ORN
WHI/VIO
J2-1
J2-6
WHI/GRN
GRN
PNK
GRY
BLU
TAN
J13-1
J13-6
WHI BLK
WHI/BLU
BLU
WHI/BLU
BLU
J6-1
J6-3
J12-1
J12-3
J11-1
J11-5 J8-1
WHI
BRN
J15-1
YEL
ORN
BLU
J15-4
J5-1
J5-4
GRY
RED
BLK
BLK
BRN
WATER INLET
VALVE
SOL
WHI
J3-1
J3-2
J7-1
J7-2
J9-1
J9-2
RED
WHI/RED
GRY
WHI/BLK
BLK or ORN
WHI
1
RED
BLK FAN t
WATER BATH
THERMISTOR t
CABINET
THERMISTOR
Models with P/H Membrane Switches
AUXILLARY
CONTROL BOARD
Push & Hold
Connector
STATIC
SHIELD
DISPENSE
STATION
#1
STATIC
SHIELD
DISPENSE
STATION
#2
STATIC
SHIELD
DISPENSE
STATION
#3
STATIC
SHIELD
STATIC
SHIELD
COLD
WATER
SWITCH
DISPENSE
STATION
#4
1
120 VOLTS AC or
220-230 VOLTS AC
2 WIRE
SINGLE PHASE
44746.0004 A 11/18 © 2011 BUNN-O-MATIC CORPORATION
BLK
BRN
DISPENSE
LOCKOUT
SWITCH
BLK
Chassis
Ground
PROGRAM
SWITCH
Chassis
Ground
WHI
BRN
GRN
Door
Ground
65 49179 011619
advertisement
Related manuals
advertisement
Table of contents
- 2 Warranty
- 3 User Notices
- 3 Site Preparation
- 4 Recommended Daily Cleaning
- 5 Preventive Maintenance Schedule
- 6 Troubleshooting
- 12 Service
- 50 Electrical Schematics
- 13 Access Panels
- 14 Dispense Platform Removal
- 15 Ballast
- 16 Cabinet Fan
- 17 Compressor
- 23 Compressor Switch
- 25 Control Board (Main)
- 26 Control Board (Portion Control Models)
- 29 Circulation Pump
- 30 Dispense Platform Switch
- 31 Dispense Pump
- 32 Dispense Motor
- 33 Dispense Valve
- 34 Dispense Switches
- 35 Cold Water Dispense Switch
- 36 Dispense Membrane Switches
- 37 Cold Water Membrane Switch
- 38 EMI Filter
- 39 Lamp Holder
- 40 LED Lamp
- 41 Rectifier
- 42 Relay
- 43 Resistor
- 44 Solenoid (Cold Water)
- 45 Solenoid (Inlet)
- 46 Temperature Probe (Water Bath Thermistor)
- 48 Temperature Sensor
- 49 Transformer
- 50 Transformer-Lited Doors
- 51 Circuit Board Triac Map
- 52 Schematic Wiring Diagrams