Generac 45kW RG04524ANAX Standby Generator Manual

Add to My manuals
2 Pages

advertisement

Generac 45kW RG04524ANAX Standby Generator Manual | Manualzz

B

4

RADIATOR/EXHAUST

DISCHARGE AIR

(BOTH SIDES)

443

[17.5]

187

[7.4]

EXHAUST MUFFLER

ENCLOSED WITHIN

GENERATOR ENCLOSURE

REMOVE COVER

FOR ACCESS TO

RADIATOR FILL CAP

AIR INTAKE

(BOTH SIDES)

BATTERY 12V

GROUP 26

NEGATIVE GROUND

P/N: 077483

TOP VIEW

749.3 [29.5]

CENTER OF GRAVITY

(SEE NOTE 5)

3

SERVICE ITEM

OIL FILL CAP

OIL DIP STICK

OIL FILTER

2.4L

EITHER SIDE

RIGHT SIDE

RIGHT SIDE

OIL DRAIN HOSE

RADIATOR DRAIN HOSE

RIGHT SIDE

LEFT SIDE

COOLANT RECOVERY BOTTLE LEFT SIDE

RADIATOR FILL CAP ROOF TOP

AIR CLEANER ELEMENT

SPARK PLUGS

MUFFLER

DRIVE BELT

FAN BELT

BATTERY

LUBE OIL MAINTAINER

SUPPLY TANK FILL CAP

LEFT SIDE

LEFT SIDE

SEE NOTE 11

EITHER SIDE

SEE NOTE 11

LEFT SIDE

ROOF TOP

REFERENCE OWNERS MANUAL

FOR PERIODIC REPLACEMENT

PART LISTINGS.

SH

REMOVE COVER FOR

ACCESS TO LUBE OIL

MAINTAINER SUPPLY TANK

REFERENCE OWNERS MANUAL

CIRCUIT BREAKER

SEE NOTE 3

1/2

REV

D

WINDCHILL VERSION

D.1

1

NOTES:

1. MINIMUM RECOMMENDED CONCRETE PAD SIZE IS 6" OFFSET OF OVERALL LENGTH

AND WIDTH OF GENERATOR. {1193.8 (47") WIDE X 2255.5 (88.8") LONG}. REFERENCE

INSTALLATION GUIDE SUPPLIED WITH THE UNIT FOR CONCRETE PAD GUIDELINES.

REFERENCE MANUFACTURER'S SPECIFICATIONS IF USING ENGINEERED, PREFABRICATED SLABS.

2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE

AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT

APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,

STATE, AND LOCAL CODES.

3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:

- SEE SPECIFICATION SHEET OR OWNERS MANUAL

- ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR.

4. REMOVE THE REAR ENCLOSURE COVER PANEL TO ACCESS

THE STUB-UP AREAS AS FOLLOWS:

- HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION

NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.

- LOW VOLTAGE CONNECTION INCLUDING TRANSFER SWITCH CONTROL WIRES.

5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.

6. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND

RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.

7. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.

8. MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5

(USE STANDARD SAE TORQUE SPECS)

9. MUST ALLOW FREE FLOW OF INTAKE AIR, DISCHARGE AIR AND EXHAUST. SEE SPEC

SHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS.

10. GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE

AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED.

11. EXHAUST MUFFLER AND FAN BELT ENCLOSED WITHIN GENERATOR ENCLOSURE,

REMOVE FRONT PANEL TO ACCESS.

759 [29.9]

DOOR TYP

VICE ACTION LATCH,

ONE PER DOOR,

ONE LIFT OFF

DOOR PER SIDE

OF GENERATOR

B

A

RADIATOR/EXHAUST

DISCHARGE AIR

DRAWING CREATED FROM PRO/ENGINEER

3D FILE. ECO MODIFICATION TO BE

APPLIED TO SOLID MODEL ONLY.

4

REAR ENCLOSURE

COVER PANEL

SEE NOTE 4

1171

[46.1]

OVERALL

HEIGHT

50

[2.0]

LEFT SIDE VIEW

1000 [39.4]

FUEL LINE CONNECTION

3/4" NPT FEMALE COUPLING

888 [35.0]

OVERALL WIDTH

REAR VIEW

ENGINE/KW

2.4L 36KW

2.4L 36KW

2.4L 45KW

2.4L 45KW

ENCLOSURE

MATERIAL

ST

AL

ST

AL

WEIGHT DATA

WEIGHT

GENSET ONLY

KG [LBS]

WEIGHT

SHIPPING SKID

KG [LBS]

569 [1255]

545 [1202]

596 [1313]

572 [1260]

44 [98]

44 [98]

44 [98]

44 [98]

3

58

[2.3]

TYP

CUSTOMER ACCESS

ASSEMBLY, CONTROL

PANEL ACCESS,

BATTERY CHARGER

LOCATED WITHIN

SEE NOTE 4

47

[1.8]

1857 [73.1] TYP

1950 [76.8]

OVERALL LENGTH

RIGHT SIDE VIEW

SHIPPING WEIGHT

KG [LBS]

613 [1353]

590 [1300]

640 [1411]

616 [1358]

DIMENSIONS: MM [INCH]

GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING

WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR

ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT

THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.

c GENERAC POWER SYSTEMS 2013

2

ELECTRONICALLY APPROVED

INSIDE WINDCHILL

TITLE

INSTALL CPL PROT G2.4L C2

36/45KW

ISSUE DATE:

SIZE

B

SCALE

CAGE NO DWG NO

N/A

0.050 WT-KG

0K8636

SEE ABOVE SHEET

1

REV

D

1 of 2

A

B

4

50 [2.0]

TYP

A

DRAWING CREATED FROM PRO/ENGINEER

3D FILE. ECO MODIFICATION TO BE

APPLIED TO SOLID MODEL ONLY.

4

13.5 X 29.5

MOUNTING SLOTS

4X

TOP VIEW

1708

[67.2]

3

1750 [68.9] TYP

MOUNTING SLOT CENTERS

1950 [76.8]

LEFT SIDE VIEW

3

SH

2/2

REV

D

WINDCHILL VERSION

D.1

1

* NOTE: STUB-UP AREA FOR HIGH AND LOW

VOLTAGE CONNECTIONS, CIRCUIT BREAKER,

NEUTRAL AND CUSTOMER CONNECTION OPENING.

37

[1.5]

B

HIGH AND LOW

VOLTAGE

STUB-UP AREA

162

[6.4]

* STUB-UP

AREA

786

[30.9]

233

[9.2]

9

[.4]

162 [6.4]

* STUB-UP

AREA

51

[2.0]

REMOVABLE

STUB-UP COVER

850 [33.5]

116 [4.6]

25 [1.0]

TYP

838 [33.0] TYP

MOUNTING SLOT CENTERS

888 [35.0]

REAR VIEW

TITLE

DIMENSIONS: MM [INCH]

GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING

WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR

ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT

THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.

c GENERAC POWER SYSTEMS 2013

2

ELECTRONICALLY APPROVED

INSIDE WINDCHILL

INSTALL CPL PROT G2.4L C2

36/45KW

ISSUE DATE:

SIZE

B

SCALE

CAGE NO

N/A

DWG NO

0K8636

0.100 WT-KG SEE SHEET 1 SHEET

1

REV

2 of 2

D