NETAFIM NMC Junior irrigation controller Installation & Service Manual
जाहिरात
जाहिरात
NMC-Junior Irrigation
Installation & Service Manual
Doc. Name: NMC Junior Installation Manual
Revision: 1.0
Page 2 of 109 pages
Written By:
Checked By:
Checked By:
Approved By:
Name
Alissa Levy
Rami Bar
Gideon Maestro
Idan Marko
Signature Date
30-Jan-2008
30-Jan-2008
30-Jan-2008
30-Jan-2008
PROPRIETARY INFORMATION
This document discloses data in which NETAFIM Ltd. has proprietary rights. Neither the furnishing, receipt, or possession thereof confers or transfers any right to reproduce or disclose the document, any part thereof, or any information therein except by written permission form, or written agreement with NETAFIM Ltd.
Doc. Name: NMC Junior Installation Manual
Revision: 1.0
Page 3 of 109 pages
Rev
1.0
Change Description
Updates
Change No. Date
30-Jan-2008
Authorizer’s
Name
Idan Marko
Doc. Name: NMC Junior Installation Manual
Table of Contents
2. Basic Requirements for On-Site Preparation
6.4 PC and Inter-Controller Communication
6.4.2 Wiring and Controller Setup
Revision: 1.0
Page 4 of 109 pages
7
8
9
10
10
11
11
16
17
17
21
24
24
25
25
26
27
27
28
32
32
33
Doc. Name: NMC Junior Installation Manual
Table of Contents Con’t…
8. System Configuration Procedure
9.1 Device Delay Configuration
9.2 Pump Station Configuration
9.6 Dosing Channel Configuration
9.10 System Nutrigation™ Check
Revision: 1.0
Page 5 of 109 pages
41
41
42
43
36
36
37
38
39
40
44
53
54
55
57
48
49
50
51
52
44
45
46
46
47
Doc. Name: NMC Junior Installation Manual
Table of Contents Con’t…
10. Controller Advanced Settings
10.1 Pump Station Configuration
10.3 Various Dosing Configurations
11. Hot Keys and Status Screens
Appendix A- NMC-Junior Parts List
Appendix C-Replacement and Additional Installations
Appendix D-Sensor Installation and Definition
Appendix E- Technical Specifications
Revision: 1.0
Page 6 of 109 pages
67
70
76
82
95
105
109
58
58
59
60
60
61
61
62
62
62
63
66
Doc. Name: NMC Junior Installation Manual
Chapter: General Instructions Revision: 1.0
•
•
•
•
•
1. General Instructions
Installation should be performed by authorized technicians only.
Verify that field components are working properly.
All safety regulations are to be applied.
Do not apply force or pressure on components during the installation procedure.
Refer to your supervisor if problems occur during installation procedure.
Page 7 of 109 pages
Doc. Name: NMC Junior Installation Manual
Chapter: Basic Requirements Revision: 1.0
•
•
•
•
2. Basic Requirements for On-Site Preparation
Verify power source between 115-220 VAC±10% or 12VDC (Australia & New Zealand
240VAC±5%).
Verify grounding connection <10Ω
Environment temperature between (-10 o c/14°F)-(+60 o c/140°F).
Verify protection from damaging climate conditions.
Page 8 of 109 pages
Doc. Name: NMC Junior Installation Manual
Chapter: General Dimensions
3. General Dimensions
22.5 cm
8.9 in
Revision: 1.0
Page 9 of 109 pages
30.5 cm
12 in
12.5 cm
4.9 in
30.5 cm
12 in
Type A
18 cm
7.1 in
25.5 cm
10 in
Type B
Doc. Name: NMC Junior Installation Manual
Chapter: Unpacking & Installation Revision: 1.0
4. Unpacking and Installation
4.1 Unpacking
Package carefully
User manual
Page 10 of 109 pages
3
Junior case Type A
Type A
Or
Junior case Type B
Type B
Doc. Name: NMC Junior Installation Manual
Chapter: Unpacking & Installation Revision: 1.0
4.2 Box Installation
4.2.1 Option A
1
Cover by opening screws x4
Flat, wide headed screwdriver
2
Junior case Type A
Page 11 of 109 pages
Doc. Name: NMC Junior Installation Manual
Chapter: Unpacking & Installation Revision: 1.0
3
Grounding
4
Flat cable
Rock slightly
Spanner
Page 12 of 109 pages
Doc. Name: NMC Junior Installation Manual
Chapter: Unpacking & Installation Revision: 1.0
5
Bracket from slots
Door wing
Page 13 of 109 pages
6
Door from base
Doc. Name: NMC Junior Installation Manual
Chapter: Unpacking & Installation Revision: 1.0
7
Holes x4 according to markings on back side
9
Exact location of four holes
Holes
ø6mm according to markings on the wall
Anchors
8
Level
Box on the wall at intended location
10
Screws 4.5X4
Flat washer x4
Screwdriver
Screw covers x4
Page 14 of 109 pages
Doc. Name: NMC Junior Installation Manual
Chapter: Unpacking & Installation Revision: 1.0
11
Pin into socket
Door to base
Page 15 of 109 pages
12
Flat cable
13
Grounding
Doc. Name: NMC Junior Installation Manual
Chapter: Unpacking & Installation Revision: 1.0
4.2.2 Box Option B
1
Bracket
X4
2
Page 16 of 109 pages
Box on the wall at intended location
Philips tip screwdriver
Level
3 4
Exact holes location
Drill holes
Anchor
X4
Screwdriver
Screws 4.5X4
Flat washer x4
Doc. Name: NMC Junior Installation Manual
Chapter: Power Supply Wiring
5. Power Supply Wiring
5.1 Main Power Wiring
1
Main power
Verify grounding connection <10Ω
Revision: 1.0
CAUTION! SHOCK HAZARD! The electrical installation should be performed by a qualified electrician only!
2
Gland screw
3
Feeding cable into
Gland cover
USA:
Green =GND
White = Common
Black = Phase
Tri-wires feeding cable
3*1.5 mm
2 or
3*16 AWG
Page 17 of 109 pages
NOTE: Ensure source voltage matches sticker
(USA/MEX: 115VAC)
Doc. Name: NMC Junior Installation Manual
Chapter: Power Supply Wiring
4
Cable into gland screw
Cable length to reach the terminal connector location
Revision: 1.0
Page 18 of 109 pages
5
Gland cover
Doc. Name: NMC Junior Installation Manual
Chapter: Power Supply Wiring
6 7
Terminal Connector
Screws x3
Revision: 1.0
Page 19 of 109 pages
8
Wire accordingly:
~- Phase
N- Neutral
G- Ground
Screws x3
Doc. Name: NMC Junior Installation Manual
Chapter: Power Supply Wiring
9
Connector terminal
Revision: 1.0
10
Feeding cable to interior box wall using a tie wrap
11
Main power
Page 20 of 109 pages
Doc. Name: NMC Junior Installation Manual
Chapter: Power Supply Wiring Revision: 1.0
5.2 Electrical Test
1
Electrical test with Multimeter
2
Ö Phase to ground
Ö Phase to neutral
Phase to ground results:
Option 1- 220VAC± 10 % (EUR, AFR)
Option 2- 115VAC±10% (USA, MEX)
Option 3- 240VAC±5% (AUS, NZ)
Phase to neutral results:
Option 1- 220VAC± 10 % (EUR, AFR)
Option 2- 115VAC±10% (USA, MEX)
Option 3- 240VAC±5% (AUS, NZ)
CAUTION! SHOCK HAZARD! The electrical installation should be performed by a qualified electrician only!
Page 21 of 109 pages
Doc. Name: NMC Junior Installation Manual
Chapter: Power Supply Wiring
3
Display is OK
4
Revision: 1.0
CPU led is blinking
Page 22 of 109 pages
Doc. Name: NMC Junior Installation Manual
Chapter: Power Supply Wiring
5
Final high and low terminals of output card
Electrical test with Multimeter
Revision: 1.0
6
Result:
24VAC± 10%
Page 23 of 109 pages
Doc. Name: NMC Junior Installation Manual
Chapter: Electrical Installation
6. Electrical Installation
6.1 Input/Output Layout
Display card
Revision: 1.0
CPU &
Keyboard card
Page 24 of 109 pages
Power Supply
Card
RS232 or RS485
Communication
Card Connector
Data Plug
Digital & Analog
Input
RS232 or RS485
Communication Terminal
Terminals 1-15: Digital Output
Terminal 16: 24VAC
Doc. Name: NMC Junior Installation Manual
Chapter: Electrical Installation
6.2 Output Terminals
6.2.1 Wiring
24 VAC as shown
Revision: 1.0
Page 25 of 109 pages
1
2
3
Relevant screws
-Common wires on top row
-Command wires on lower row
Common
Until wires are secure
Command
Doc. Name: NMC Junior Installation Manual
Chapter: Electrical Installation
6.2.2 Output Wiring Example
Black – Common
C o l o r s
- Command
Revision: 1.0
Page 26 of 109 pages
Pump switch gear
Irrigation
Valves
NOTE: Before switching the controller on, the technician should verify that there is no short circuit on each output. (Resistance test)
Doc. Name: NMC Junior Installation Manual
Chapter: Electrical Installation
6.3 Input Terminals
6.3.1 Wiring
Input terminals
Common
Digital input #1 to #6
EC sensor input
PH sensor input
Temperature sensors input
Humidity sensors input
+12 VDC
NOTE: Before switching the controller on, the technician should verify that there is no short circuit on each input.
(Resistance test)
Revision: 1.0
Page 27 of 109 pages
Doc. Name: NMC Junior Installation Manual
Chapter: Electrical Installation
6.3.2 Digital Input Examples
Example A-
Digital input 1: Water meter, Fertilizer meter
Digital input 2: Float switch, Pressure switch
Revision: 1.0
Page 28 of 109 pages
Water meter, Fertilizer meter
Float switch, Pressure switch, etc.
Doc. Name: NMC Junior Installation Manual
Chapter: Electrical Installation Revision: 1.0
Example B-
Digital input 3: Water Meter with Photo-Diode Output
Page 29 of 109 pages
Water Meter with Photo- Diode Output
500Ω Resistor
Doc. Name: NMC Junior Installation Manual
Chapter: Electrical Installation
Example B-
EC / pH sensors
Revision: 1.0
Transmitter
Terminals
24VAC±25%,
50-60Hz, 5Watt
COM
EC pH
NOTE: Can wire EC/pH main power source to 24VAC on the output terminals.
Page 30 of 109 pages
Doc. Name: NMC Junior Installation Manual
Chapter: Electrical Installation
Example C-
Temp/ Humidity sensors
Temp./Hum.
Sensor
Revision: 1.0
Page 31 of 109 pages
NOTE: Can wire 24VAC source in same way as on previous page.
Measuring Box
Terminals
24VAC
Doc. Name: NMC Junior Installation Manual
Chapter: Electrical Installation
6.4 PC and Inter-Controller Communication
6.4.1 Card Installation
Insert RS-232 card
Option A: RS-232
Revision: 1.0
Insert RS-485 card
Option B: RS-485
Page 32 of 109 pages
Doc. Name: NMC Junior Installation Manual
Chapter: Electrical Installation
6.4.2 Wiring and Controller Setup
Option A: RS-232
NOTE: Use 3 wire shielded communication cable.
Com
Rx
Tx
Ground (shield)
NOTE: Do not connect the end of the cable’s shield to the ground.
Revision: 1.0
DB9 connector
MUX RS-232
Refer to table on page 35
Junior 1
Page 33 of 109 pages
Junior 2
Doc. Name: NMC Junior Installation Manual
Chapter: Electrical Installation
Option B: RS-485
NOTE: Use 2 wire shielded communication cable.
A
Ground (shield)
B
Revision: 1.0
NOTE: Do not connect the end of the cable’s shield to the ground.
DB9 connector
MUX RS 458
Refer to table on page 35
Junior 1
Page 34 of 109 pages
Junior 2
Doc. Name: NMC Junior Installation Manual
Chapter: Electrical Installation Revision: 1.0
Baud Rate
9600 BPS
4800 BPS
2400 BPS
Communication Distance and Baud Rate
1 Controller
2000 meter
1.25 mile
2500 meter
1.55 mile
3000 meter
1.86 mile
10 Controllers
1200 meter
0.75 mile
1800 meter
1.12 mile
2400 meter
1.49 mile
Page 35 of 109 pages
NOTE: Baud rate is dependent on cable length and number of controllers.
Doc. Name: NMC Junior Installation Manual
Chapter: Controller Set-Up
7. Controller Set Up
7.1 Start-up
1
Irrigation system and controller set-up and definition
2
Main power
Controller
“MENU” on touch pad
Revision: 1.0
Page 36 of 109 pages
Doc. Name: NMC Junior Installation Manual
Chapter: Controller Set-Up
7.2 Language, Time and Date
Ö Select desired language
Ö Select Temp. and Vol. unit (USA: Temp.=°F,
Vol.=Gallon)
Ö “1. Time & Date” in Setup menu and set
3
5 6
Revision: 1.0
4
Page 37 of 109 pages
7
NOTE: In any given menu, you may use arrow and ENTER keys on touch pad to make a selection or press the corresponding number and ENTER on touch pad as a short cut.
Doc. Name: NMC Junior Installation Manual
Chapter: Controller Set-Up Revision: 1.0
7.3 Output Definition
Ö “8. Install” in main menu and press ENTER
Ö “1. Device Layout” and press ENTER
1
2
Technician writes an I/O list
Page 38 of 109 pages
3
Define devices:
Ex: Valves 1 and 2,
Relays 3 and 4 as Output 3 and 4
4
5
“2. Device List” is read-only overview list of definitions for verification
These step for every Output
Doc. Name: NMC Junior Installation Manual
Chapter: Controller Set-Up
7.4 Digital Input Definition
Ö “3. Digital Input” in
Installation menu
Ö Input 1 set definition
Step 2 for all Input definitions- according to
technician and equipment in field
1
2
Revision: 1.0
Page 39 of 109 pages
Doc. Name: NMC Junior Installation Manual
Chapter: Controller Set-Up
7.5 Analog Input Definition
5. Analog Input in Installation menu
1 2
Revision: 1.0
Page 40 of 109 pages
Channel and enter “YES” for sensors according to terminal
Previous step for all other analog input sensors
Doc. Name: NMC Junior Installation Manual
Chapter: Controller Test Procedure Revision: 1.0
8. Controller Test Procedure
8.1 Test Relays
1 2
Page 41 of 109 pages
“5. Test” in Main Menu
Ö “1. Relays” to test output devices in the field (dry test)
Ö Highlight status, press ENTER,
“MAN” appears
Ö To end process press ENTER again
For Irrigation valve test, send someone out in field with Walky-Talky to verify status
3 4
Doc. Name: NMC Junior Installation Manual
Chapter: Controller Test Procedure Revision: 1.0
8.2 Digital Input Test
1 2
Ö “2. Digital Input” in Test menu
Dry test- Get a pulse using magnet; attach magnet to get a pulse from the “read” of the cable
Ö
Water, fertilizer and any auxiliary meters: Count up 1-256
Ö
Delta pressure: 1= ON, 0= OFF
Page 42 of 109 pages
Doc. Name: NMC Junior Installation Manual
Chapter: Controller Test Procedure Revision: 1.0
8.3 Analog Input Test
“3. Analog Input” in Test menu
See table below
“4. Temperature” or “5. Humidity”values will be displayed
1 2
pH sensor
Sensor type
EC sensor
Humidity sensor
Temp sensor
Page 43 of 109 pages
Description
pH = 0 – A/D = 205 pH = 7.0 – A/D = 615 pH = 14.0 – A/D = 1023
EC = 0 – A/D = 205
EC = 2.0 – A/D = 370
EC = 10.0 – A/D = 1024
RH% = 0 – A/D = 0
RH% = 50 – A/D = 308
RH% = 100 – A/D = 620
T°C = 0 – A/D = 768
T°C = 25 – A/D = 489
T°C = 50 – A/D = 250
Doc. Name: NMC Junior Installation Manual
Chapter: System Configuration Procedure Revision: 1.0
9. System Configuration Procedure
9.1 Device Delay Configuration
1
Irrigation system and controller configuration
Ö “7. Config” in Main Menu
Ö “1. Device Delay Configuration”
Ö Enter delay values. See table below.
3
2
NOTE: Settings in the graph below are for example only.
Page 44 of 109 pages
NMC Device delay
Valve
ON
Main valve
Pump
Irrigation
Start
5 10 Sec
ON
ON
ON
End
5 10 Sec
Doc. Name: NMC Junior Installation Manual
Chapter: System Configuration Procedure Revision: 1.0
9.2 Pump Station Configuration
Ö “2. Pump Station Configuration”
Ö Define capacity of main pump (USA: Gallon/min.)
1 2
Page 45 of 109 pages
If there is more than 1 is being used, refer to Controller Advanced
Settings
chapter p.58
Doc. Name: NMC Junior Installation Manual
Chapter: System Configuration Procedure Revision: 1.0
9.3 Valve Configuration
Ö “3. Valve Configuration”
Ö Allocate pump, main valve and water meter
(Note: If there is more than 1 pump, refer to
NMC-Junior Advanced Settings chapter)
1
9.4 Valve Flow Rate
Ö “4. Valve Flow Rate” (USA: Gallon/min.)
Ö Define exact flow consumption of every valve:
Technician must calculate formula:
[Drippers/lateral x dripper capacity (liters/hr) x # of laterals/valve] ÷ 1000 = nominal flow of valve (m³/hr)
Ö Set Min./Max. flow rate limits per valve for alarm
(already defined as 25% by default)
3
2
Drippers /
Lateral
Number of laterals
Dripper capacity
Irrigation valve
Page 46 of 109 pages
Doc. Name: NMC Junior Installation Manual
Chapter: System Configuration Procedure Revision: 1.0
9.5 Water Meter
Ö “5. Water Meter”
Ö Define resolution of water meter-
See label on water meter as shown in
Step 2 (USA: Gallon/min.)
1 2
Page 47 of 109 pages
If there is no label, check data sheet supplied with the meter.
NOTE: If there is more than 1 water meter, refer to Controller Advanced
Settings
chapter on page 59.
3
Doc. Name: NMC Junior Installation Manual
Chapter: System Configuration Procedure Revision: 1.0
9.6 Dosing Channel Configuration
1
Ö “6. Dosing Channel Configuration”
Ö Define flow rate of every Venturi (USA: Gallon/hr.)
Ö Define channels 1-2=EC
Ö Define channel 3=Acid
2
Page 48 of 109 pages
3
NOTE: In case that different dosing pump (electric) or setting (fertilizer meter), please refer to Controller
Advanced Settings
chapter on pages 60-61.
Doc. Name: NMC Junior Installation Manual
Chapter: System Configuration Procedure Revision: 1.0
9.7 Dosing Configuration
1
Ö “7. Dosing Configuration”
Ö EC and PH Control and Alarms to “Yes”
Ö Set Min. On Time to 0.8≤2.0 seconds
Ö Set Min. Off Time to 0.8≤2.0 seconds
Ö To set Control Cycle, run system and measure time in seconds it takes to see reaction of EC/PH meter
Ö Set dosing Booster Off Delay to 10 seconds (Time booster continues running after dosing process)
2 3
Page 49 of 109 pages
NOTE: For different dosing settings, please refer to
Controller Advanced Settings
chapter on page 62.
Doc. Name: NMC Junior Installation Manual
Chapter: System Configuration Procedure Revision: 1.0
9.8 EC/PH Sensor Range
Ö “12. EC/PH Sensor Range”
Ö Leave as is
1 2
Page 50 of 109 pages
Doc. Name: NMC Junior Installation Manual
Chapter: System Configuration Procedure Revision: 1.0
9.9 History Resolution
Ö
Program how often computer should collect sensor data (keep in mind that lower resolution fill the memory in short period and will overwrite the old data)
1 2
Page 51 of 109 pages
Controller number (in case of multiple controllers in the network, name each controller with a different number)
3
Communication baud rate between controllers and
PC
NOTE: For more details on system setup, please refer to
Controller Advanced Settings
chapter on page 63-65.
4
Doc. Name: NMC Junior Installation Manual
Chapter: System Configuration Procedure Revision: 1.0
9.10 System Nutrigation™ Check
EC/PH is on target
1
Page 52 of 109 pages
Know limits of irrigation system. Calculate max. allowed injection: (Dosing channel suction flow ÷ average flow rate from field) X 0.8 = Max. injection quantity (lit/m³, USA: Gallon/1000 gallon.)
2
3
Enter desired amount of fertilizer to inject per dosing channel in l/m³ (USA: Gallon/1000 gallon)
4
Enter desired target EC/PH levels
Doc. Name: NMC Junior Installation Manual
Chapter: System Configuration Procedure Revision: 1.0
9.10.1 Simulation
Ö 10 liters of water in bucket
Ö Inject 50 ml of fertilizer from each tank
Ö Inject 30 ml of acid
Ö Mix until acid and fertilizer is dissolved
Ö EC and pH levels.
Ö Results should be relatively close to desired target.
Ö Deviation of ≤ 0.5 from target is allowed.
Use protective equipment, gloves and goggles when handling fertilizers, acid and other chemicals!
10 liters of Source Water
50 ml of Fertilizer from each Tank
30 ml ACID
Page 53 of 109 pages
Doc. Name: NMC Junior Installation Manual
Chapter: System Configuration Procedure Revision: 1.0
9.10.2 Water Run Time
1 2
Page 54 of 109 pages
3
Enter water run time or quantity
Doc. Name: NMC Junior Installation Manual
Chapter: System Configuration Procedure Revision: 1.0
9.10.3 Start/Stop Valve
1 2
Page 55 of 109 pages
3
Run Time Program (1)
Dosing Program (1)
Doc. Name: NMC Junior Installation Manual
Chapter: System Configuration Procedure Revision: 1.0
4 5
Page 56 of 109 pages
MENU
6
Active Irrigation Screen
7
Ö Difference between nominal and actual flow rate is ≤10%
Ö Difference between target and actual EC\pH ≤0.2
Doc. Name: NMC Junior Installation Manual
Chapter: System Configuration Procedure Revision: 1.0
9.11 Data Plug
1 2
Data plug into terminal
Page 57 of 109 pages
System is idle and not in process before
“Write to Data Plug”
3 4 5
Data Plug from terminal at end of process
Doc. Name: NMC Junior Installation Manual
Chapter:
Controller Advanced Settings
Revision: 1.0
10. Controller Advanced Settings
10.1 Pump Station Configuration
1 2
Pump 1
Pump 2
Pump 3
3
Page 58 of 109 pages
Valve 1
Valve 2
Valve 3
Stability: Time between each pump start
Off Delay: Time delay between switching each pump Off
4 5
Valves 1, 2 & 3 allocated to
Pumps 1, 2 & 3 (Pump station)
Pump station will be operated according to the valve/s nominal flow
Doc. Name: NMC Junior Installation Manual
Chapter:
Controller Advanced Settings
Revision: 1.0
10.2 Multiple Water Meters
1
2 3
Page 59 of 109 pages
Enter capacity and type for additional water meters
4
5
Configure meters to valves
Ex: Valves 1, 2 & 3 are allocated to water meters 1, 2 & 3 consecutively
Only 1 water meter can be measured at a time.
Doc. Name: NMC Junior Installation Manual
Chapter:
Controller Advanced Settings
Revision: 1.0
10.3 Various Dosing Configurations
10.3.1 Method 1- Dosing Pump control = Fert. Meter
Dosing pump measurement= Fert. Meter
Dosing pump type= Venturi or Electric
Inject fertilizer according to nominal capacity of pump/measure from fertilizer meter for verification purposes
Page 60 of 109 pages
Set nominal pump capacity
Doc. Name: NMC Junior Installation Manual
Chapter:
Controller Advanced Settings
Revision: 1.0
10.3.2 Method 2- Dosing Pump control =Nominal Flow Rate
Dosing pump measurement= Calculate dosing pump flow rate
Dosing pump type= Venturi or Electric
Page 61 of 109 pages
10.3.3 Method 3- Dosing Pump control =According Fert. meter pulses
Dosing pump measurement= Fert. Meter
Dosing pump type= Hydraulic
(For quantitative injection only)
Doc. Name: NMC Junior Installation Manual
Chapter:
Controller Advanced Settings
Revision: 1.0
10.4 Dosing Configuration
Type of each channel configured by technician during installation process
EC- channel influenced by EC levels
ACID- channel to inject acid to reduce pH levels
PASSIVE- no EC/pH influence
ALKALI- channel to increase pH levels
10.4.1 EC/pH Control- System will inject +/- depending on EC levels, auto-adjust to meet target levels.
Set limits for controller adjustments when levels are too high/low
Page 62 of 109 pages
Ex: If dosing channel 1 is set by the grower to inject 10 liter/m
3
, the controller auto adjust range is 5 to 15 liter/m
3 in order to meet the EC level.
10.4.2 EC/pH Control
EC/pH coarse tuning- when way off target, faster/stronger correction
EC/pH fine tuning- off target is low, slow/light correction
Control cycle- Delay time from fertilizer/Acid injection point to EC/pH sensors reading
EC/pH averaging- balanced reading from EC/pH sensors
Dose boost off delay- time clear water circulated through system after fertigation stops and venturi closes
Doc. Name: NMC Junior Installation Manual
Chapter:
Controller Advanced Settings
Revision: 1.0
10.5 Advanced System Setup
End day time
Stop time for measuring water and dosing accumulating information from irrigation valves and dosing channels
Page 63 of 109 pages
Max. cooling parallel
Max. misting parallel
Define cooling/misting valve/pump
Set max. cooling/misting programs working together
NOTE: Use only when the system has a limited capacity to operate max # cooling/misting programs simultaneously.
Doc. Name: NMC Junior Installation Manual
Chapter:
Controller Advanced Settings
Revision: 1.0
Stop irrigation?
Stop Dosing?
Page 64 of 109 pages
Set to pause irrigation during cooling/misting process, then resume irrigation
Valve transition
Set to pause irrigation during filter flushing process, then resume irrigation
Set delay between valves or set to overlap valves in order to create pressure before opening them by pressing +/- key
5 second overlap
Valve 1
5 sec. delay
Valve 2
5 second delay
Set to pause dosing during filter flushing process, then resume irrigation
Valve 1
5 sec. overlap
Valve 2
Doc. Name: NMC Junior Installation Manual
Chapter:
Controller Advanced Settings
Revision: 1.0
Default hot key/ History resolution
Page 65 of 109 pages
Change setting of default hot key that will be present for the grower as a default.
Set history resolution-how often system saves information
Baud rate
Select baud rate of communication
Doc. Name: NMC Junior Installation Manual
Chapter:
Hot Keys and Status Screens
Revision: 1.0
Page 66 of 109 pages
11. Hot Keys and Status Screens
In the Active Irrigation screen, can view status of the system by pressing number keys corresponding to each hot screen.
Hot Screen 1- Active Irrigation Hot Screen 2- Irrigation Process Status Hot Screen 3- Program Status
Hot Screen 4- Water Flow & EC/pH Status
Hot Screen 5- Filter Flushing Status Hot Screen 6- Temp. & Hum. Status
Doc. Name: NMC Junior Installation Manual
Appx. A- Parts List Revision: 1.0
Page 67 of 109 pages
APPENDIX A
NMC-JUNIOR Parts List
Doc. Name: NMC Junior Installation Manual
Appx. A- Parts List
NMC-JUNIOR Parts List
8
7
6
5 4
Revision: 1.0
Page 68 of 109 pages
1
2
3
Doc. Name: NMC Junior Installation Manual
Appx. A- Parts List Revision: 1.0
Page 69 of 109 pages
NMC Junior Parts List Con’t…
Item # Description
1
2
NMC-JUNIOR power supply card 115VAC
NMC-JUNIOR power supply card 230VAC
NMC-JUNIOR power supply card 115VAC external 24VAC *
NMC-JUNIOR power supply card 230VAC external 24VAC *
NMC-JUNIOR power supply card 12VDC
NMC-JUNIOR Communication card RS-232
NMC-JUNIOR Communication card RS-485
5
6
3
4
7
8
NMC-JUNIOR input/output card
NMC-JUNIOR flat cable for input/output card
NMC-JUNIOR memory backup key - Data Plug
NMC-JUNIOR CPU+Keyboard card for fluorescent display (old type)
NMC-JUNIOR CPU+Keyboard card for LED backlit display (new type)
NMC-JUNIOR flat cable for display card
NMC-JUNIOR display card with fluorescent (old type)
NMC-JUNIOR display card with LED backlit (new type)
* Special request
Assembled
When ordering a new controller
Part of the controller
74340-001000
74340-001100
Part of the controller
Part of the controller
Part of the controller
Part of the controller
Part of the controller
Part of the controller
Additional
Spare part
74340-004995
74340-009400
74340-
74340-
74340-004997
74340-006600
74340-006700
74340-009490
74340-004972
74340-009000
74340-009480
74340-009485
74340-004973
74340-009470
74340-004920
Doc. Name: NMC Junior Installation Manual
Appx. B- Troubleshooting Revision: 1.0
Page 70 of 109 pages
APPENDIX B
Troubleshooting
Doc. Name: NMC Junior Installation Manual
Appx. B- Troubleshooting
Troubleshooting
1. Display Malfunction-
Controller display is off
1 2
Main power source is O.K
CPU led is blinking
Revision: 1.0
Page 71 of 109 pages
Yes No
Continue to next page
Main power
Flat cable connection is OK
Doc. Name: NMC Junior Installation Manual
Appx. B- Troubleshooting
3
Electrical test with Multimeter
Ö Phase to ground
Ö Phase to neutral
Phase to ground results:
Option 1- 230VAC± 10 % (EUR, AFR, AUS)
Option 2- 115VAC±10% (USA, MEX)
Phase to neutral results:
Option 1- 230VAC± 10 % (EUR, AFR, AUS)
Option 2- 115VAC±10% (USA, MEX)
Revision: 1.0
CAUTION! SHOCK HAZARD! The electrical installation should be performed by a qualified electrician only!
Voltage is OK
Continue to next page
No
Voltage
Cable connection is OK
Page 72 of 109 pages
Doc. Name: NMC Junior Installation Manual
Appx. B- Troubleshooting
4
Main power
If fuses 1 and 2 are burnt
Revision: 1.0
Page 73 of 109 pages
Burnt
Not burnt
Fuse from casing
Contact CMT technical support
with extra fuses provided
NOTE: Make sure that the same current load is written on the new fuse.
Main power
24VAC is available
F2
F1
Doc. Name: NMC Junior Installation Manual
Appx. B- Troubleshooting Revision: 1.0
2. Output Malfunction-
Outputs (valves, pumps etc.) are not working although controller show “ON”
1
Final high and low terminals of output card
Electrical test with Multimeter of final high and low terminals of output card
Result:
24VAC± 10%
Page 74 of 109 pages
Voltage is OK
No
Voltage
Continue to next page
Output wire connections and cable
Doc. Name: NMC Junior Installation Manual
Appx. B- Troubleshooting
2
Main power
If fuses 5 and 7 are burnt
Revision: 1.0
Page 75 of 109 pages
Burnt Not burnt
Fuse from casing
With extra fuses provided
NOTE: Make sure that the same current load is written on the new fuse.
Contact CMT technical support
Main power
24VAC is available
F5
F7
Doc. Name: NMC Junior Installation Manual
Appx. C- Replacements & Add. Installations Revision: 1.0
Page 76 of 109 pages
APPENDIX C
Replacement and Additional Installations
Doc. Name: NMC Junior Installation Manual
Appx. C- Replacements & Add. Installations Revision: 1.0
Replacement and Additional Installations
1. Card Replacement
1.1 Power Supply Card
1
Main power
2
Power Cable
3
Screws x2
4
Old Card
Page 77 of 109 pages
Doc. Name: NMC Junior Installation Manual
Appx. C- Replacements & Add. Installations Revision: 1.0
1.2 Relay Card
1
Main power
2
Screws x4
Page 78 of 109 pages
3
Grounding Cable and Flat Cable
4
Old Card
Doc. Name: NMC Junior Installation Manual
Appx. C- Replacements & Add. Installations Revision: 1.0
Page 79 of 109 pages
2. NMC-Junior LCD & Keyboard
If LCD or keyboard are no longer in working condition first recognize if your LCD or keyboard is an OLD or NEW version.
High Voltage No High Voltage
OLD NEW
Jumper on CCFL
Fluorescent Lamp
Fluorescent LCD SAP# : 74340-007600
Fluorescent CPU+Keyboard SAP#: 74340-009480
Refer to next page if you have a Fluorescent version.
Jumper on LED
No Fluorescent Lamp
LED LCD SAP# : 74340-004920
LED Keyboard SAP#: 74340-009485
CHINESE/KOREAN LED LCD SAP# : 74340-004930 (Not Standard)
Refer to page 81 if you have a LED version.
Doc. Name: NMC Junior Installation Manual
Appx. C- Replacements & Add. Installations Revision: 1.0
2.1 NMC-Junior Fluorescent LCD & Keyboard Replacement
Disconnect wires
Disconnect cable
Page 80 of 109 pages
Remove Screws (x4)
Jumper set to
CCFL
Fluorescent LCD SAP# : 74340-007600
Fluorescent CPU+Keyboard SAP#: 74340-009480
Disconnect cable Fluorescent Lamp
Remove Screws (x4)
Doc. Name: NMC Junior Installation Manual
Appx. C- Replacements & Add. Installations Revision: 1.0
2.2 NMC-Junior LED LCD & Keyboard Replacement
Page 81 of 109 pages
Remove Screws (x4)
LED LCD SAP# : 74340-004920
LED Keyboard SAP#: 74340-009485
Jumper set to LED
CHINESE/KOREAN LED LCD SAP# : 74340-004930 (Not Standard)
No Fluorescent Lamp
Remove Screws (x4)
Disconnect wires
Doc. Name: NMC Junior Installation Manual
Appx. D- Sensor Installation & Definition Revision: 1.0
Page 82 of 109 pages
APPENDIX D
Sensor Installation and Definition
Doc. Name: NMC Junior Installation Manual
Appx. D- Sensor Installation & Definition Revision: 1.0
Sensor Installation and Definition
1. EC / pH Sensor Connection
Transmitter
Terminals
24VAC±25%,
50-60Hz, 5Watt
COM
EC pH
NOTE: Can wire EC/pH main power source to 24VAC on the output terminals.
Page 83 of 109 pages
Cable type
COM/EC/pH- 3x0.5mm
2
(20AWG) Shielded
24VAC- 2x0.5mm
2
(20AWG)
Doc. Name: NMC Junior Installation Manual
Appx. D- Sensor Installation & Definition Revision: 1.0
1.1 EC Sensor Calibration
1
SM Pump switch is in OFF position
2
Page 84 of 109 pages
Ö On EC/pH screen, press
MENU
Ö Scroll down to EC Calibration by pressing SELECT
Ö ENTER
3
4
ESC to Main Menu
Doc. Name: NMC Junior Installation Manual
Appx. D- Sensor Installation & Definition Revision: 1.0
Page 85 of 109 pages
5
MENU
6 7
8
EC sensor into Calibration
Buffer and immerse for 30 seconds
ENTER
9
Doc. Name: NMC Junior Installation Manual
Appx. D- Sensor Installation & Definition Revision: 1.0
10 11 12
Page 86 of 109 pages
Sensor from buffer
ENTER
13
Calibration in process
14
Calibration in process
If display says “Buffer Fault”, please see Troubleshooting Appendix B
Doc. Name: NMC Junior Installation Manual
Appx. D- Sensor Installation & Definition Revision: 1.0
1.2 pH Sensor Calibration
1 2
Ö On EC/pH screen, press MENU
Ö Scroll down to pH Calibration by pressing SELECT
3
Page 87 of 109 pages
4 5
ESC to Main Menu
Doc. Name: NMC Junior Installation Manual
Appx. D- Sensor Installation & Definition Revision: 1.0
1.2.1 pH 7.01 Sensor Calibration
1 2 3
MENU
4
Sensor from plastic bottle
5
pH sensor into pH 7.0
Calibration Buffer and immerse for 30 seconds
ENTER
Calibration in process
Page 88 of 109 pages
If display says “Buffer Fault”, please see Troubleshooting Appendix B
Doc. Name: NMC Junior Installation Manual
Appx. D- Sensor Installation & Definition Revision: 1.0
1.2.2 pH 4.01 Sensor Calibration
1 2
pH sensor into water and immerse for 30 seconds
3
Page 89 of 109 pages pH sensor into pH 4.0
Calibration Buffer and immerse for 30 seconds
ENTER
4 5
Calibration in process
ESC If display says “Buffer Fault”, please see Troubleshooting Appendix B
Doc. Name: NMC Junior Installation Manual
Appx. D- Sensor Installation & Definition Revision: 1.0
Page 90 of 109 pages
1
2
In Setup menu, select EC/pH Calibration
If EC and PH numbers match on both screens. If not:
Use arrows to increase/decrease value so numbers match
Ö ENTER when values match
Ö Press MENU
3
Doc. Name: NMC Junior Installation Manual
Appx. D- Sensor Installation & Definition Revision: 1.0
2. Temperature / Humidity Sensor Connection
Temp./Hum.
Sensor
Page 91 of 109 pages
NOTE: Can wire 24VAC terminals of measuring box to 24VAC on the output terminals.
Cable type
6x0.5mm
2
(20AWG)
Measuring Box
Terminals
24VAC
Doc. Name: NMC Junior Installation Manual
Appx. D- Sensor Installation & Definition Revision: 1.0
2.1 Sensor Definition
Temp./Hum.
Sensor
1
Fan
Measuring Box
2 3
Channel 3- Temp. Sensor
Page 92 of 109 pages
Doc. Name: NMC Junior Installation Manual
Appx. D- Sensor Installation & Definition Revision: 1.0
Page 93 of 109 pages
4
Channel 4- Hum. Sensor
Doc. Name: NMC Junior Installation Manual
Appx. D- Sensor Installation & Definition Revision: 1.0
3. Sensor and Cable Specifications
Page 94 of 109 pages
Sensor Type
Temperature –
RTS-s
RH – RHS-10
EC pH
Measured Values
-20°C to 50°C/ -4°F to 122°F
Accuracy
0.3°C/ 0.54°F
0 – 100%
±2% (10%-90%RH)
±3.5% (90%-100%RH)
0 to 10mS (old transmitters used
20mS)
0 - 14
0.05-0.1mS
0.1
Input Range
30kΩ (kOhm)
0 – 3 VDC
4 – 20mA
4 – 20mA
Maximum Cable Length
500 meters (1640 feet)
Cable Type
2x0.5mm
2 (20AWG)
300 meters (985 feet) 3x0.5mm
2 (20AWG)
---
3x0.5mm
2 (20AWG)
Shielded
Doc. Name: NMC Junior Installation Manual
Appx. E- Technical Specifications Revision: 1.0
Page 95 of 109 pages
APPENDIX E
Technical Specifications
Doc. Name: NMC Junior Installation Manual
Appx. E- Technical Specifications Revision: 1.0
Page 96 of 109 pages
1. Technical Specifications
Small Plastic box
(Indoor installation)
IP 65 Housing Plastic housing with a screw on lid
Dimensions (LxWxH)
Weight
Ambient Conditions Operating temperature range
22.5x31x13 cm
(8.86x12.2x5.12 inch)
4.5 kg
9.9 lbs
-10 to +60
0
Fahrenheit)
Celsius (14 to 140
0
Approvals
Storage temperature range
EMC approval
CE
-10 to +70
0
Fahrenheit)
Celsius (14 to 158
0
The 115/230VAC has Safety
CE approval
EN61010-1
EN55011 Class A
EN55011 Class B
EN61000-4-2,3,4,5,6,8,11;
Sealed Plastic box
(Outdoor installation)
IP 65
32.5x29.0x18.0 cm
(12.79x11.41x7.08 inch)
5.5Kg
12.12 lbs
-10 to +60
0
Fahrenheit)
Celsius (14 to 140
0
-10 to +70
0
Fahrenheit)
Celsius (14 to 158
0
EN61010-1
EN55011 Class A
EN55011 Class B
EN61000-4-2,3,4,5,6,8,11;
Doc. Name: NMC Junior Installation Manual
Appx. E- Technical Specifications Revision: 1.0
Page 97 of 109 pages
LCD Display
Power Supply
Card
CPU &
Keyboard Card
Input/Output
Card
Doc. Name: NMC Junior Installation Manual
Appx. E- Technical Specifications
2. Hardware Layout
24 VAC Output
Transformer
System transformer
Revision: 1.0
Main power line filter
Main power terminal
Surge
Suppression
Input
Communication card (can be either
RS232 or RS485)
Inputs’ terminal
Communications’ terminal
Page 98 of 109 pages
Output relays
Output fuse protection
Surge
Suppression
Outputs
Output/24 VAC connection terminal
Doc. Name: NMC Junior Installation Manual
Appx. E- Technical Specifications Revision: 1.0
Page 99 of 109 pages
Lithium battery for
SRAM & clock
CPU status LED
Firmware
EPROM
Data plug socket
Doc. Name: NMC Junior Installation Manual
Appx. E- Technical Specifications
3. Power Supply Card
Power supply transformers:
•12VDC to the CPU and relays.
•5VDC to digital inputs, 3VDC to analog inputs, etc’.
•24VAC to 24VAC output card.
Revision: 1.0
Page 100 of 109 pages
Doc. Name: NMC Junior Installation Manual
Appx. E- Technical Specifications
Option A: 115 or 230 VAC Power Supply Card
Specifications
Main voltage
Main frequency
Single phase
230 VAC,
0.5 Amp
50/60
Single phase
110 VAC,
0.5 Amp
50/60
Max voltage
Min voltage
Main fuse
250 VAC 200 VAC 0.5 Amp
130 VAC 90 VAC 0.5 Amp
Revision: 1.0
Page 101 of 109 pages
230/115
Mains Supply
LINE
GND
Neutral
NOTE: 24 VAC- available power for peripheral equipment: 50Watt/2A
F1
Filter
F7
T2
T1
F2
18V
25VA
24VAC
To Valves
F5
50VA
5V
5V DC
To CPU
12-18V DC
To I/O Circuit
Doc. Name: NMC Junior Installation Manual
Appx. E- Technical Specifications Revision: 1.0
Option B: 115VAC or 230VAC power supply card with external 24VAC power for output devices
Specifications
Main voltage
Main frequency
50/60 Single phase
230 VAC,
0.5 Amp
Single phase
110 VAC,
0.5 Amp
50/60
Max voltage
Min voltage
Main fuse
250 VAC 200 VAC 0.5 Amp
130 VAC 90 VAC 0.5 Amp
Page 102 of 109 pages
230/115
Mains Supply
LINE
GND
Neutral
NOTE: System uses 24VAC External transformer with limit of 6.3Amp (F5).
F1
Filter
T1
F2
18V
25VA
24VAC
External
P2
24VAC
To Valves
5V
5V DC
To CPU
12-18V DC
To I/O Circuit
Doc. Name: NMC Junior Installation Manual
Appx. E- Technical Specifications
Option C: 12VDC Power Supply Card
Revision: 1.0
Page 103 of 109 pages
Specifications
Main voltage
12 – 48 VDC/VAC
System fuse
2 Amp
P2
F2
P3
F5
12V
12V DC
To Valves
5V
5V DC
To CPU
12V DC
To I/O Circuit
Doc. Name: NMC Junior Installation Manual
Appx. E- Technical Specifications Revision: 1.0
4. Input and Output Card
The Input & Output card consists of the following
Analog inputs
Digital inputs
Relays outputs
1x EC input
1x pH input
1x humidity sensor input
2x temperature sensor input
6x digital input
15x N.O output
Communication 1x RS232/RS485 port
4 - 20 mA
4 - 20 mA
0 - 3 VDC
30KΩ THERMISTOR
5V/2mA, max pulse rate 50
Pulse/Sec
24VAC low power relay, 5
Amps, maximum output changing rate 0.4 Sec
RS232 or RS485 communication port, function depends on type of connection and type of
MUX used.
Page 104 of 109 pages
Doc. Name: NMC Junior Installation Manual
Appx. F- Main Menu Tree Revision: 1.0
Page 105 of 109 pages
APPENDIX F
Main Menu Tree
Doc. Name: NMC Junior Installation Manual
Appx. F- Main Menu Tree Revision: 1.0
Page 106 of 109 pages
1. Program
1.1
Irrigation
1.2
Water Run
Time
1.3
Dosing
1.4
External
Condition
1.5
Agitator
1.6
Selector
1.7
Filter Flushing
1.8
Cooling
1.9
Misting
1.10
Water
Heating
2.1
Irrigation Pause
2.2
Start/Stop Program
2. Manual
2.3
Start/Stop Valve
2.4
Filter Flushing
3. Alarm
3.1
Alarm Reset
3.2
History
3.3
Alarm Definition
3.4
Alarm Setting
Doc. Name: NMC Junior Installation Manual
Appx. F- Main Menu Tree Revision: 1.0
Page 107 of 109 pages
4. History
4.1
Irrigation
Log
4.2
Uncompleted
Irrigation
4.3
Uncompleted
Programs
4.4
Daily
Irrigation
4.5
Irrigation
Accumultation
4.6
Auxillary Meter
Accumultation
4.7
Accumulation
Reset
4.8
Filters
4.9
Cooling
4.10
Sensor
Log
4.11
Event
Log
4.12
System
Log
5.1
Relays
5.2
Digital Input
5. Test
5.3
Analog Input
5.4
Temperature
5.5
Humidity
6.1
Time &
Date
6.2
System
Setup
6.3
Temp.
Calibration
6.4
Hum.
Calibration
6. Setup
6.5
EC/pH.
Calibration
6.6
Sensor
Logging
6.7
Write to
Data Plug
6.8
Read from
Data Plug
Doc. Name: NMC Junior Installation Manual
Appx. F- Main Menu Tree Revision: 1.0
Page 108 of 109 pages
7. Configuration
7.1
Device Delay
Configuration
7.2
Pump Station
Configuration
7.3
Valve
Configuration
7.4
Valve Flow
Rate
7.5
Water
Meter
7.6
Dosing
Channel
Configuration
7.7
Dosing
Configuration
7.8
E/pH Sensor
Range
7.9
Cooling
Configuration
7.10
Misting
Configuration
8.1
Device Layout
8.2
Device List
8. Installation
8.3
Digital Input
8.4
Analog Input
Doc. Name: NMC Junior Installation Manual
Controller Warranty Revision: 1.0
Page 109 of 109 pages
Controller Warranty
Controller:
Netafim warrants the electronic components of the NMC-Junior Controller on to be free of defects in materials or workmanship for 2 (two) years from the date of purchase by end user. If a defect is discovered during the applicable warranty period, Netafim will repair or replace, at its option, the product or the defective part.
Note: Lightning and surge damages are not covered by warranty.
Date of commissioning:
Customer’s representative:
Name:
Signature:
Netafim’s representative:
Name:
Signature:
डाउनलोड
जाहिरात