PowerMaster rsw Installation And Owner's Manual

Add to My manuals
28 Pages

advertisement

PowerMaster rsw Installation And Owner's Manual | Manualzz

INSTALLATION AND OWNER’S MANUAL

MODEL RSW

Swing Gate Operator

UL 325 and UL 991 Listed

21 1/2"

19 1/ 4'' LENGTH X 10 1/ 2'' WIDTH

14 5/ 8''

12 1/ 8''

16 1/ 4''

2'' O.D. PIPE

( BY OTHERS )

Serial #:

Date Installed:

Your Dealer:

READ THIS MANUAL CAREFULLY

BEFORE INSTALLATION OR USE.

SAVE THESE INSTRUCTIONS.

Table of Contents

Model RSW Residential Swing Gate Operator

Important Safety Information ..................................................................................3

Important Notice for Gate Operators Manufactured after 1/11/16 ..........................4

UL Installation and Safety Considerations ..............................................................5

System Designer Safety Instructions......................................................................6

Installer Safety Instructions ................................................................................ 7-8

End User Safety Warnings ............................................................................... 9-10

Manual Operation .................................................................................................11

Installation & Setup Procedure

Before Installing Operator .................................................................................11

Installation Layout .............................................................................................12

Installation of Operator ............................................................................... 13-14

Electrical Connections ......................................................................................15

Left Hand/Right Hand Conversion ....................................................................16

Connection of a 3-Button Station ......................................................................16

Limit Adjustment ...............................................................................................17

Master/Slave Installation ...................................................................................18

Timer to Close ...................................................................................................18

Accessory Connections

Connection of a Radio ......................................................................................18

Loop Detector Systems .............................................................................. 18-21

Loop Installation (Standard Layout Chart) ........................................................19

Cutting the Required Groove ............................................................................19

Loop Connections ....................................................................................... 20-21

Safety Device Connections

Inherent Obstruction Sensing Device ...............................................................21

Secondary Obstruction Sensing Devices ................................................... 22-24

Contact - Sensing Edge ...............................................................................22

Non-contact - Photo Eyes ............................................................................23

Warranty ..............................................................................................................27

IMPORTANT!

FOR SWING GATE OPERATING SYSTEMS,

SAFETY IS EVERYONE’S BUSINESS.

Automatic gate operators provide convenience and security to users. However, because these machines can produce high levels of force, it is important that all gate operator system designers, installers, and end users be aware of the potential hazards associated with improperly designed, installed, or maintained systems. Keep in mind that the gate operator is a component part of a total gate operating system.

The following information contains various safety precautions and warnings for the system designer, installer and end user. These instructions provide an overview of the importance of safe design, installation, and use.

Warnings are identified with the ▲ symbol. This symbol will identify some of the conditions that can result in serious injury or death. Take time to carefully read and follow these precautions and other important information provided to help ensure safe system design, installation and use.

WARNING:

Gate operators are only one part of a total gate operating system. It is the responsibility of purchaser, designer, and installer to ensure that the total system is safe for its intended use. All secondary entrapment safety devices must be RECOGNIZED by UL to ensure the safety of the complete operating system.

3

4

IMPORTANT NOTICE FOR GATE OPERATORS

MANUFACTURED AFTER JANUARY 11TH, 2016

All gate operators manufactured after January 11th, 2016 must have a monitored input for each direction. In order to satisfy this requirement, all PowerMaster gate operators with the universal board will have one monitored input for each direction. The close photo (11) terminal will function for the close direction and the open photo (10) will function for the open direction. These terminals will look for, or “monitor”, the presence of a 10k in-line resistor. If either terminal does not detect the presence of the monitored device, the unit will function in constant contact for this direction.

Note: The first time a monitored device is added to the unit, the board must “learn” what the monitored device is. To have the board learn the monitored device, perform the following steps:

1. With the power off, hold both the open and close limit simultaneously.

2. Power up the unit and release your fingers from the limits. The unit has now learned the monitored device.

E.g. The operator detects there is a monitored device on the 11 terminal but not the 10 terminal. The operator will function in momentary contact to close and constant pressure to open.

Following are the monitored devices acceptable for use with the

GSMCB02:

Device

Prime-Guard

Reflecti-Guard

IRB-MON

IRB-RET

The Solution

Manufacturer

Miller Edge

Miller Edge

EMX

EMX

Miller Edge

Description

Monitored Photoeye

Retroreflective Monitored Photoeye

Monitored Photoeye

Retroreflective Monitored Photoeye

Multiple Safety Devices

Any actions taken to circumvent this monitoring are in violation of the

UL325, building code, and local laws.

UL INSTALLATION AND SAFETY CONSIDERATIONS

INSTALLATION CLASSES

CLASS I - RESIDENTIAL VEHICULAR GATE

OPERATOR

A vehicular gate operator (or system) intended for use in a home of one to four single-family dwellings, or a garage or parking area associated therewith.

CLASS II – COMMERCIAL/GENERAL ACCESS VEHICULAR GATE OPERATOR

A vehicular gate operator (or system) intended for use in a commercial location or building such as a multifamily housing unit

(five or more single family units), hotel, garages, retail store or other building servicing the general public.

CLASS III - INDUSTRIAL/LIMITED ACCESS

VEHICULAR GATE OPERATOR

A vehicular gate operator (or system) intended for use in an industrial location or building such as a factory or loading dock area or other locations not intended to service the general public.

CLASS IV - RESTRICTED ACCESS VEHICULAR GATE OPERATOR

A vehicular gate operator (or system) intended for use in a guarded industrial location or building such as an airport area or other restricted access locations not servicing the general public, in which unauthorized access is prevented via supervision by security personnel.

5

SYSTEM DESIGNER SAFETY INSTRUCTIONS

▲ 1. Familiarize yourself with the precautions and warnings for the installer. Users are relying on your design to provide a safe installation.

▲ 2. The operator is supplied with a primary obstruction sensing entrapment protection system. The installation must also have a secondary entrapment protection system installed, such as photoelectric sensors or an electric edge system.

3. When designing a system that will be entered from a highway or main thoroughfare, be sure the system is placed far enough away from the road to eliminate traffic backup. Distance from the road, size of the gate, usage levels, and gate cycle/speed must be considered to eliminate potential traffic hazards.

4. Swing gates have two potential entrapment zones you must avoid. Make sure they are protected as shown in the following diagram (Figure 1).

ELECTRIC EDGE, ON VERTICAL OUTSIDE

EDGE OF GATE. WIRED TO REVERSE

WHILE CLOSING (RECOMMENDED).

1 ENTRAPMENT ZONE

HORIZONTAL ELECTRIC EDGE, ON BOTTOM

OUTSIDE EDGE OF GATE. WIRED TO REVERSE

WHILE CLOSING (REQUIRED).

2 ENTRAPMENT ZONE

HORIZONTAL ELECTRIC EDGE, ON INSIDE

BOTTOM OF GATE. WIRED TO REVERSE WHILE

OPENING (RECOMMENDED).

• Pedestrians should keep clear of path of gate, particularly in the area before fully closed.

• The area of the gate arm and linkage must be avoided as it can create an entrapment.

FIGURE 1

WARNING

THIS GATE SYSTEM IS FOR VEHICULAR TRAFFIC ONLY. A

SEPARATE PEDESTRIAN ENTRANCE MUST BE PROVIDED.

The illustrations and descriptive captions provide precautions to help eliminate injuries or fatalities. Familiarize yourself with them when designing the total system.

5. Design the gate system so a person cannot reach over, under, around, or through the gate to operate any controls. Never place controls on the gate operator itself.

6

INSTALLER SAFETY INSTRUCTIONS

BEFORE INSTALLATION

1. Check to see that the operator is proper for this type and size of gate and its frequency of use. If you are not sure, consult factory.

2. Check to see that there are no structures adjacent to the area, which may pose a risk of entrapment when gate is opening or closing.

3. You must ensure that the gate has been properly installed and works freely in both directions. Replace or service any worn or damaged gate hardware prior to installation. A freely moving gate will require less force to operate and enhance the performance of the operator as well as the safety devices used within the system.

4. Install the gate operator on the inside of the property and/or fence line. DO NOT install an operator on the public side of the gate.

5. Severe injury or death can result from entrapment by a gate. The operator is supplied with an obstruction sensing primary entrapment protection system. Additional safety equipment such as electric edges or photocell sensors must be installed to provide the required secondary entrapment protection system. For assistance in selecting the correct type of safety equipment, consult the factory.

6. Review the operation of the unit and become familiar with the manual operation procedure and safety features of the system.

7. You must install a pushbutton control or key switch to allow for normal operation of the gate if the automatic controls do not work. Locate the push button or key switch and small warning placard within sight of the gate in a secured area at least 10 feet or more from any moving parts of the gate or operator.

8. Outdoor or easily accessed gate controls should be of the security type to prohibit unauthorized use. Please consult your local distributor concerning the types and specifications of available controls.

DURING INSTALLATION

1. Be aware of all moving parts and avoid close proximity to any pinch points.

2. Disconnect power at the control panel before making any electric service connections.

Connection location for controls and safety equipment can be found on the wiring diagram, and in this manual.

3. Know the procedure for disengaging and manually operating the unit.

4. Adjust the open and close force adjustment on the control board, in each direction, to the minimum force required to operate the gate smoothly. DO NOT increase the force adjustment setting to make up for rough spots in gate travel - FIX THE GATE

INSTEAD!

7

Moving Gate Can Cause

Serious Injury or Death.

KEEP CLEAR! Gate May Move at Any Time. Children

Should Not Operate Gate.

Operate Gate Only When

Area is in Sight and Free of

People and Obstructions.

10 feet

Control

Station

▲ 5. Locate the controls at least 10 feet from the moving gate so that the user can observe the gate operation, but is not able to come in contact with the gate while operating the controls.

6. Attach large warning signs provided to each side of the gate or fence in the most conspicuous place.

Mount control station and smaller warning placard together within sight of the gate opening.

8

AFTER INSTALLATION

You are responsible for ensuring that the end user understands the basic operations and safety systems of the unit, INCLUDING THE MANUAL OPERATION PROCEDURE.

Point out that the safety instructions in brochure are the responsibility of the end user, and then LEAVE THIS MANUAL WITH THE END USER.

END USER SAFETY WARNINGS

The manufacturer of the gate operator does not know what type of gate you have, or what type of automatic system is installed on your gate. Be sure you’ve been fully instructed on the sequence of operation for your specific gate system(s). Keep the gate properly maintained and have a qualified service person make repairs.

1. Be sure the following safety instructions are distributed to all persons authorized to use your gate.

2. KEEP GATEWAY CLEAR (Front and

Back) AT ALL TIMES. Your automatic gate is not for pedestrian use. No one should ever cross the path of the moving gate.

3. DO NOT allow children to play near your gate, or to operate the gate.

4. DO NOT operate your gate system unless you can see it when the gate moves.

5. Be sure a pushbutton or key switch has been installed for manual electric operation in the event your radio or card key does not work. Any mounted control station should be located a minimum of 10 feet from the gate so the gate cannot be reached through or touched. Any pushbutton located in a building should be installed within sight of the gate.

6. DO NOT operate any controls without watching the movement of the gate.

7. Your gate system is required to have a primary and a secondary entrapment safety system installed and maintained.

8. If your gate closes automatically, loop detectors should be installed to detect the presence of a vehicle.

9

▲ 9. DO NOT increase force adjustment to compensate for a damaged gate. The gate should always be maintained to operate manually as easily as possible to provide maximum protection.

10. Check all safety systems at least once per month for the correct force, speed and sensitivity. Gate must reverse when hitting a rigid object, or when a non-contact sensor is activated. If these functions are observed to operate improperly, discontinue use and have it serviced immediately!

11. You are responsible for ensuring that warning signs are installed and maintained on both sides of your gate.

12. To ensure safe operation of this equipment, you must read this safety manual and keep it for reference.

13. Swing gates have two potential entrapment zones you must avoid. Make sure they are protected as shown in Figure 1.

10

4’

MINIMUM

MANUAL OPERATION

Your operator is equipped with an emergency disconnect for manual operation.

Be sure you know how to properly use this feature. To disengage operator, follow the procedure in Figure 2.

NOTE: TO DISCONNECT OPERATOR FOR

MANUAL OPERATION, REMOVE HAND

KNOBS AND SEPARATE CONTROL ARM

EXTENSION FROM CONTROL ARM

CONTROL ARM

EXTENSION

CONTROL ARM

DRIVE SHAFT

HAND KNOBS FOR MANUAL DISCONNECT

(USE HOLES SHOWN AS STARTING

POSITION)

3/8” BOLT

3/8” LOCK WASHER

3/8” WASHER

1/4” DRIVE KEY

OPERATOR

FIGURE 2

INSTALLATION INSTRUCTIONS & SET-UP PROCEDURE

WARNING

DO NOT APPLY POWER UNTIL TOLD TO DO SO! RISK

OF ELECTRICAL SHOCK OR INJURY MAY RESULT!

BEFORE INSTALLING OPERATOR

IMPORTANT: Operator should always be mounted inside the gate. Determine whether the installation is Left hand or Right hand by the direction the gate moves in order to open, when viewed from inside the fence.

FENCE

LEFT HAND INSTALLATION

HINGE GATE

OPERATOR

RIGHT HAND INSTALLATION

GATE HINGE FENCE

OPERATOR

FIGURE 3

1. Gate must swing freely to fully opened and fully closed position.

2. The operator will be located as shown above, for left and right hand installation.

11

INSTALLATION LAYOUT

1. Layout mounting post and electrical conduit locations as shown in figures below.

Excavate required area for conduit installation and cementing of mounting posts

(Minimum of 2 feet deep. Check local codes.)

2. Set mounting post and electrical conduit in place.

3. Pour cement to secure mounting posts and let cure for two days prior to operator installation.

Note: Distance between mounting posts and relative location to gate is very important! Operator must be installed perpendicular to the fence.

GATE HINGE

ELECTRICAL

CONTUIT

18”

APPROX. 16”

24” MIN.

FIGURE 4

CENTER LINE OF FENCE

17-3/8”

28”

21-1/2”

ELECTRICAL ACCESS

SIDE COVER

4” MIN.

2” O.D. (MOUNTING POST) BY OTHERS

GROUND LEVEL

ELECTRICAL CONDUIT

PER LOCAL CODE

FIGURE 5

21-1/2”

SWING GATE OPERATOR

TOP MOUNTING ANGLE

2” U-BOLTS

2” O.D. (MOUNTING POST)

BY OTHERS

LOWER

MOUNTING

PLATE

APPROX. 16”

4” MIN.

24” MIN.

ELECTRIAL CONDUIT PER

LOCAL CODE

12

OPERATOR INSTALLATION

1. Mount operator on posts with mounting angles and mounting plates. Secure position with 2” U-bolts and hardware provided. See Figure 5.

2. Set control arm on output shaft of operator without drive key, and install control arm extension using hand knobs to secure position. See Figure 6.

NOTE: TO DISCONNECT OPERATOR FOR

MANUAL OPERATION, REMOVE

HANDKNOBS AND SEPARATE CONTROL

ARM EXTENSION FROM CONTROL ARM.

CONTROL ARM

EXTENSION

CONTROL ARM

DRIVE SHAFT

HAND KNOBS FOR MANUAL DISCONNECT

(USE HOLES SHOWN AS STARTING

POSITION FOR INITIAL SETUP)

3/8” BOLT

3/8” LOCK WASHER

3/8” WASHER

1/4” DRIVE KEY

OPERATOR

MOUNTING ANGLE

MOUNTING PLATE

FIGURE 6

3. Install end fittings on connecting rod assembly and attach one end of assembly to end of control arm extension.

See Figure 7.

FIGURE 7

SET SCREWS

CONNECTING

ROD (2PCS)

SPLICE BAR

3/8” PIVOT BOLT

FLAT WASHER

SPACER BUSHING

END FITTING

FLAT WASHER

GATE BRACKET

3/8” HEX NUT LOCK WASHER TUBE

PIN (4)

SPACER

ROLL

SET SCREWS

3/8” HEX NUT

3/8” PIVOT BOLT

FLAT WASHER

SPACER BUSHING

END FITTING

FLAT WASHER

GATE ARM

FLAT WASHER

LOCK WASHER

4. Install gate bracket on remaining end of connecting rod (See Figures 7 & 8)

5. Locate gate bracket in position on gate, as shown in Figure 8 and clamp in position.

6. Move control arm to its maximum close position.

See Figure 8. Control arm and connecting rod must be straight in line.

36”

GATE HINGE

CL

OF GATE

GATE

BRACKET

GATE ANGLE

(BY OTHERS)

GATE BRACKET

PIVOT BOLT

CONTROL ARM

PIVOT BOLT

CONNECTING ROD ASSEMBLY

CONTROL ARM

ELECTRICAL

ACCESS

OPERATOR

FIGURE 8

13

Note: Adjustment can be made in (4) locations to get desired closed position, as described below. Always start with Option “a”.

a. Move the gate bracket to left or right of the 36 inch starting position.

b. Change length of connecting rod assembly.

c. Relocate control arm extension on control arm to a different hole pattern then start position. See Figure 6.

d. Move connecting rod bolt in gate bracket to a different hole. See Figure 8.

7. Move control arm to its open position as shown in Figure 9.

Note: Arm and connecting rod should almost double over each other. This is important for smooth operation and longevity of the operator.

Note: Open position of gate may be adjusted slightly with limit switch adjustment, but when finished, open position of control arm assembly should be as close as possible to that shown in

Figure 9. If mechanical adjustments are made to achieve desired open position of gate, repeat Steps 6 & 7 , since this will affect the closed position.

GATE

OPERATOR

CONTROL ARM

ASSEMBLY

CONNECTING

ROD ASSEMBLY

FIGURE 9

8. When the desired open and closed g ate position have been achieved, place gate in the fully closed position a nd remove control arm extension from control arm. See Figure 6.

9. Remove control arm from operator drive shaft and insert drive key. See Figure 6.

10. Replace control arm on operator drive shaft with drive key and secure with 3/8 inch bolt.

See Figure 6.

11. Replace control arm extension on control arm and secure with hand knobs as shown in

Figure 6.

Note: If operator was ordered as a right or left hand unit from the factory, the control arm position will be somewhere in its normal travel segment and the limit switches will be set at an approximate open and close position. Final adjustments will be made later after power is connected.

If the hand of the operator is to be changed in the field as described in the following section than before the control arm extension is replaced as in Step #11 , proceed to

Step #12 .

12. By turning the internal drive pulley by hand, move the control arm to somewhere in its normal drive segment.

13. Control arm extension may now be attached to control arm as in Figure 6.

ELECTRICAL SET-UP AND CONNECTIONS

WARNING

DO NOT APPLY POWER UNTIL TOLD TO DO SO! RISK

OF ELECTRICAL SHOCK OR INJURY MAY RESULT!

NOTE: Before connecting the operator, use a voltmeter to determine that the electrical service is 115V. THIS OPERATOR CANNOT BE CONNECTED AT 230 VOLTS. Damage will result which is not covered under warranty.

NOTE: Wiring to operator must use watertight materials in accordance with local electric code. See the following wire gauge/distance charts for proper sizing. Master/Slave installations should have SEPARATE power supply wiring or length of wire runs should be figured at half that shown on the chart. This unit must be grounded in accordance with N.E.C. and local codes.

LINE

VOLTAGE

115VAC

HP

1/2

14 AWG

150’

12 AWG

250’

WIRE GAUGE

10 AWG

400’

8 AWG

500’

6 AWG

650’

LOW VOLTAGE WIRE GAUGE/ DISTANCE CHART

24 AWG: UP TO 150’

20 AWG: 150’ - 200’

18 AWG: 250’ - 1,500’

Control wiring should be run as twisted pairs. DO NOT run control wires in the same conduit as power wires. telephone wires, or loop detector leads.

1. Be sure the power switches at source, and at the operator are OFF.

2. Connect incoming power lines and ground wire as shown below.

Hot leg (Black) to Black; Neutral (White) to White; Ground to Ground Screw.

Power

Switch

Power Box

Operator

BLK

WHT

BLK

WHT

GND

GND

Incoming Power

115V - 1PH

Inside Power Box,

Connect As Shown

NOTE: In order to properly run and check the operator at various stages during the setup procedure, it is suggested that a three button control station be connected at this time.

15

LEFT/RIGHT HAND CONVERSION:

Refer to Figure 3 to determine hand of operator required for this installation. This unit is factory setup for right hand operation.

To convert operator to left hand operation, make certain the power switch is off, and locate the motor capacitor (See Figure 10). Switch the red and blue wires on the capacitor that goes to the motor. The operator is now setup for left hand installation.

TO MOTOR

TO CONTROL

BOARD

SWITCH THE RED AND

BLUE WIRES GOING TO

THE MOTOR TO

CHANGE OPERATOR

TO LEFT HAND

OPERATION

FIGURE 10

CONNECTION OF A 3-BUTTON STATION

WARNING

READ ENTIRE PROCEDURE BEFORE

STARTING. TURN OFF MAIN POWER

BEFORE MAKING ANY ADJUSTMENTS!

WARNING

STAY CLEAR OF ALL MOVING PARTS

AND ELECTRICAL COMPONENTS OF

THE OPERATOR WHILE TESTING!

A CONTROL STATION SUCH

AS A THREE BUTTON STATION

(OPEN, CLOSE, STOP) WITH ALL

NORMALLY OPEN CONTACTS IS

REQUIRED FOR THIS PROCEDURE.

SEE INSTRUCTIONS BELOW.

OPEN

CLOSE

STOP

COMMON

4 5 6 7

1. Connect a wire from the COMMON connection of the control station to Terminal #5.

2. Connect a second wire from the OPEN button of the control station to Terminal #6.

3. Connect a third wire from the CLOSE button of the control station to Terminal #7.

4. Connect a fourth wire from the STOP button of the control station to Terminal #4.

16

LIMIT ADJUSTMENT PROCEDURE

NOTE: Operator should be completely installed, mechanically and electrically, before attempting to set limit switch cams (See Figure 11).

NOTE: For Master/Slave installation, travel time for the Master operator must be set longer than the Slave operator.

OPEN LIMIT SWITCH ADJUSTMENT

Drive Shaft

Open Limit

Switch

Close Limit

Switch

Open

Limit Cam

Close

Limit Cam

Actuating

Screw

FIGURE 11

Limit Switch

Limit Cam

Adjustment

Set Screw

1. Turn on power. Press OPEN button on control station. Gate should stop before full open position is reached. If gate does not stop when open position is reached, PRESS STOP

BUTTON!

2. To adjust gate for more open travel, loosen open limit cam set screw and rotate limit cam in the opposite direction drive shaft rotates to open gate. Re-tighten set screw after adjustment (See Figure 11).

3. If it was necessary to stop gate, adjust open limit switch cam for less open travel by rotating the cam in the same direction that the drive shaft rotates to open the gate.

4. Press CLOSE button and stop gate in mid travel with STOP button.

5. Repeat procedure until desired open setting is obtained.

CLOSE LIMIT SWITCH ADJUSTMENT

1. Press CLOSE button on control station. Gate should stop before full closed position is reached. If gate does not stop when close position is reached, PRESS STOP BUTTON!

2. To adjust gate for more close travel, loosen close limit cam set screw and rotate limit cam in the opposite direction drive shaft rotates to close gate (See Figure 11).

3. If it is necessary to stop gate, adjust close limit switch cam for less close travel by rotating the cam in the same direction that the drive shaft rotates to close the gate.

4. Press OPEN button and stop gate in mid travel with STOP button. Repeat procedure until desired close setting is obtained.

NOTE: After both OPEN and CLOSE limit adjustments are complete, check that both limit cam set screws are tight.

17

MASTER-SLAVE INSTALLATION

NOTE: A single unit is considered a

Master. In a Master/Slave installation, one unit must be converted to LEFT

HAND operation.

1. Place jumper on the Master operator’s control board in the

OFF position.

2. Place jumper on the Slave operator’s control board in the ON position.

3. Connect Terminal #15 of Master unit to Terminal #5 of Slave unit.

4. Connect Terminal #16 from the

Master unit to Terminal #6 on the

Slave unit.

JUMPER

ON

SLAVE

MASTER POSITION

(OFF)

ON

SLAVE

SLAVE POSITION

(ON)

5. Connect Terminal #17 from the Master unit to Terminal #7 on the Slave unit.

JUMPER

MASTER

1 2 3 4 5 6 7 8 9 10 11 12 13 14

1 2 3 4 5 6 7 8 9 10 11 12 13 14

15 16 17 18

15 16 17 18

SLAVE

TIMER TO CLOSE OPTION

The operator is equipped with a timer to close option for use with control devices, such as a radio control or card key control. The AUTO RE-CLOSE TIMER adjustment screw is located on the printed circuit board. The operator is shipped from the factory with this timer preset to the OFF position, fully counter-clockwise. As the timer adjustment screw is rotated clockwise, the closing of the gate can be delayed from 2 seconds to 60 seconds.

FIGURE 12

18

LOCATION OF AUTO CLOSE

TIMER ADJUSTMENT

2 SEC

OFF 60 SEC

AUTO

CLOSE

TIMER

ACCESSORY CONNECTIONS

RADIO CONTROL INSTALLATION

A three or four wire radio control receiver can be installed on this operator. This radio control receiver can only be used to open the gate, therefore the TIMER TO CLOSE option must be activated for closing.

N.O.

CONTACT

4 WIRE

RADIO

24 VAC

GREY

GREY

BLACK

RED

SINGLE BUTTON

COMMON

TERMINAL A

TERMINAL B

FIGURE 13

NOTE: If your radio’s connecting wires are not color coded as shown, see the radio’s installation manual to determine which wires are for the normally open contacts and which require the 24VAC Power Supply.

LOOP DETECTOR SYSTEMS AND INSTALLATION

The diagram on the right depicts the typical loop options for a Swing Gate installation.

1. The Exit Loop provides a signal to open the gate when a vehicle enters the loop zone.

2. The Reversing Loop protects a vehicle in the loop zone from being contacted with the gate by overriding any close signal while the gate is open, and by reversing the gate if closing.

3. The Shadow Loop protects a vehicle in the loop zone from being contacted with the gate by overriding any close signal while the gate is in the full open position.

4'

4'

4'

4'

4'

3/16” to 1/4”

Saw Slot

Road Surface

Sealant

Loop Wires

Min 1”

4'

Approx.

10’

4'

LOOP INSTALLATION

1. Lay out the desired loop locations per the diagram. The standard size chart on the following page will give an approximate length of wire required for various loop dimensions and number of turns required.

19

STANDARD LOOP LAYOUTS

FOR APPROX. 36” HEIGHT DETECTION

LOOP SIZE

4’ X 4’

4’ X 6’

4’ X 8’

4’ X 10’

4’ X 12’

4’ X 14’

4’ X 16’

4’ X 18’

4’ X 20’

4’ X 22’

4’ X 24’

4’ X 26’

4’ X 28’

4’ X 30’

4’ X 32’

4’ X 34’

4’ X 36’

4’ X 38’

4’ X 40’

# OF TURNS

2

2

3

2

3

3

3

3

2

2

2

3

3

3

3

3

3

4

4

LOOP WIRE

LENGTH (FT)

64’

80’

72’

84’

96’

108’

120’

132’

144’

156’

168’

180’

192’

136’

144’

152’

160’

168’

176’

CAUTION: The loop wires and lead-in wires must be a continuous piece of wire without splices. The amount of lead-in wire required must be added to these lengths for total wire required. Only use wire intended for this type of application

(Type XHHW insulation

16 AWG).

NOTE: Buried steel from drains or other systems may affect functioning of the loop system. Check with the factory for advice on any special installations.

Call 1-800-243-4476.

2. Cut the required groove at the locations laid out in Step#1 according to the diagram below (Figure 14).

Loop Wire

(See Chart)

Lead In Wire

(Twisted at 6 turns per foot)

1/2” Conduit

Conduit Cut

3/16” to 1/4”

1” to 2”

1” to 2”

20

FIGURE 14

3. Leaving enough wire for the lead-in, insert the specified number of turns of wire in the cut grooves (See chart).

CAUTION: Be careful not to damage the wire insulation during installation.

4. After completing the required number of loop turns, twist the ends together at the rate of 6 turns per foot to form the lead-in.

5. Seal the lead-in wire in the conduit to prevent moisture seepage into the conduit.

6. Fill over the loop wires in the groove with a recommended loop sealant. Contact your distributor for available sealants.

7. Mount the loop detector in the operator and connect the wire loop.

8. Connect loop detector to the control board as shown in the following diagrams:

EXIT LOOP CONNECTION

A B

BK

WH

2 3 4 5

BL Y

V

OR

R

P

Not Used

GR

BR

GY

TO

DRIVEWAY

LOOP

NOTE: TWIST LEADS APPROX.

6 TURNS PER FOOT

REVERSING LOOP CONNECTION

A B

BK

WH

7 8 9 10

Y BL

V

OR

R

P

Not Used

GR

BR

GY

TO

DRIVEWAY

LOOP

NOTE: TWIST LEADS APPROX.

6 TURNS PER FOOT

21

SHADOW LOOP CONNECTION

A B

BK

WH

7 8 9 10

Y BL

Red Wire From Aux.

Open Limit

V

OR

R

P

Not Used

GR

BR

GY

TO

DRIVEWAY

LOOP

NOTE: TWIST LEADS APPROX.

6 TURNS PER FOOT

SAFETY DEVICE CONNECTIONS

INHERENT OBSTRUCTION SENSING DEVICE

NOTE: The gate MUST move smoothly and easily in manual operation before attempting this adjustment.

WARNING

This unit is supplied with a current sensing system, which will stop the gate when it

TURN OFF POWER TO OPERATOR

WHEN MAKING ANY ADJUSTMENTS!

encounters an obstruction, and then backs the gate off approximately 2 inches. If the gate is started again and a second encounter occurs before hitting a limit switch, the gate will stop and sound a warning signal. A constant pressure control will then be needed to start the gate.

This sensing system has sensitivity adjustments located on the printed circuit board. The force required to activate the system may be adjusted in both OPEN and CLOSE directions separately. Start at minimum and increase force setting until it is just over what is required to move the gate smoothly without any nuisance tripping.

WARNING

NEVER INCREASE FORCE SETTING TO

MAKE UP FOR A GATE THAT IS NOT

MAINTAINED PROPERLY. THIS WILL

DESENSITIZE THE OPERATION OF THE

SAFETY SYSTEM.

LOCATION OF OVERLOAD

FORCE ADJUSTMENT

R35 R36

CLOSE OPEN

OVERLOAD FORCE

MINIMUM MAXIMUM

22

SECONDARY OBSTRUCTION SENSING DEVICES

Two sensing devices (either a contact or a non-contact system) must be installed and connected to this unit to increase protection against entrapment per UL requirements; one for each respective direction.

NOTE: Safety device contacts must be 10k monitored or NORMALLY OPEN.

24 VAC power is available at marked terminals for devices that may require it (e.g. photo eyes, wireless edges, etc.).

CONTACT SENSOR INSTALLATION

NOTE: Wireless sensors must be installed so there is no signal interference.

NOTE: All hard wiring to safety edges must be installed so there is no threat of mechanical damage to wiring between components when the gate is moving.

Horizontal Electric Edge

Mounted On Outside

Bottom of Gate

1. Install electric edge sensors in locations shown on the right.

NOTE: A separate pedestrian gate must be installed if there is no other entry access but the vehicular gate.

Electric Edge

Mounted On Vertical

Outside Edge of Gate

Horizontal Electric Edge

Mounted On Inside

Bottom of Gate

2. Connect contact sensor edges to the control board as shown in Figure 15.

Outside Edge

11 12 13 14

Inside Edge

Vertical Edge

FIGURE 15

3. After sensors are mounted and electrically connected, turn ON the power.

4. Test the CLOSE OBSTRUCTION SENSING SYSTEM for proper operation by depressing the vertical edge sensing strip while the operator is running closed.

NOTE: The operator should STOP AND REVERSE a short distance and then STOP.

23

5. Run the operator to the OPEN limit and repeat Step #3 for the outside horizontal edge.

6. Test the OPEN OBSTRUCTION SENSING SYSTEM by depressing the inside horizontal edge sensor while the gate is opening.

NOTE: The operator should repeat the STOP AND REVERSE procedure.

NOTE: If an edge is activated twice, or a second edge is activated before a limit is hit

(full open or close), operator will stop and sound a warning horn. To reactivate system,

turn operator power switch OFF then ON.

NON-CONTACT SENSOR INSTALLATION

1. Install photoelectric cell as close to FULL OPEN and FULL

CLOSED position of gate as possible.

2. Photocells should be installed across the gate opening and behind the gate at least 10 inches above ground (see image on right).

NOTE: A separate pedestrian gate must be installed if there is no other entry access but the vehicular gate.

Photo Electric Cell

(For Close Direction)

Photo Electric Cell

(For Open Direction)

24

3. Connect NON-CONTACT sensors to the control board as shown in Figure 16.

NON CONTACT SENSOR CONNECTION

10 11 12 13 14

Close Photocell

Sensor

Open Photocell

Sensor

FIGURE 16

NOTE: Close photocell is connected to Terminal #11 and Terminal #14. Open photocell is connected to Terminal #10 and Terminal #14.

AFTER SENSORS ARE CONNECTED

1. Turn power OFF.

2. Make sure the photo-beams are properly aligned per the manufacturer’s specifications.

3. Hold both limits.

4. Turn ON power.

5. Release limits after the beep turns off.

6. Test the CLOSE OBSTRUCTION SENSING SYSTEM for proper operation by blocking the beam across the gate opening while the gate is running closed.

NOTE: The gate should STOP AND REVERSE a short distance and then STOP.

7. Test the OPEN OBSTRUCTION SENSING SYSTEM by blocking the beam mounted at the back area of the gate while the gate is running open.

NOTE: The operator should repeat the STOP AND REVERSE procedure.

MAINTENANCE SUGGESTIONS

Periodically check all hardware (nuts, bolts, screws, etc) for tightness.

25

Notes

PowerMaster

Limited 5-Year Warranty

PowerMaster warrants all GATE OPERATORS (Swing, Slide, Barrier categories) to be free of defects in materials and workmanship for a period of five (5) years from date of manufacture, provided that product has been registered. A one year warranty applies if product has not been registered.

ELECTRICAL PARTS (including boards, switches, relays, etc):

PowerMaster warrants electrical parts for a two (2) year period, provided that product has been registered. A one year warranty applies if product has not been registered.

If any part is found to be defective during this period, new parts will be furnished free of charge.

Failure of this product due to misuse, improper installation, alterations, vandalism, acts of God, or lack of maintenance is not covered under this warranty, and voids any other implied warranties herein.

PowerMaster is not responsible for any labor charges incurred in connection with the installation of warranted parts.

In order to activate this warranty, the registration form found with your operator MUST BE

COMPLETED AND RETURNED WITHIN THIRTY CALENDAR DAYS FROM DATE OF PURCHASE.

Visit our website at www.VEpower.net and click on the Register your Product link.

You can also register via email to [email protected].

If registration is not activated, a ONE YEAR warranty from date of manufacture will apply for all claims.

REGISTRATION INFORMATION

Operator Information

Model RSW

Serial #

Date Installed

Location Installed

Address

Address

Address

Installer’s Information

Company Name

Address

Address 2

City, State, Zip

Telephone #

Contact Name

The end user should retain this information for their records and to obtain warranty service.

27

Need Technical Support?

Visit: www.vepower.net/faqs

Call us toll free @ 1-800-243-4476

Email us: [email protected]

www.facebook.com/PowerMasterOperators

Scan QR Code with your Smart phone to find us on the web!

WWW.VEPOWER.NET

MANUFACTURED BY V.E. POWER DOOR CO,INC.

REV 2017-1024

advertisement

Key Features

  • Compact design suitable for narrow spaces
  • Handles gates up to 1,500 lbs and 18 feet long
  • Adjustable speed and force settings for smooth and safe operation
  • Built-in obstruction sensing device for improved safety
  • Supports various accessories for added convenience
  • UL 325 and UL 991 Listed for safety and reliability

Related manuals

Frequently Answers and Questions

What is the purpose of the 'Timer to Close' feature?
The 'Timer to Close' feature allows you to set a specific time after which the gate will automatically close after it has been opened.
What type of obstruction sensing device does the Powermaster RSW come with?
The Powermaster RSW comes with a primary inherent obstruction sensing entrapment protection system.
What is the difference between Class I, Class II, Class III, and Class IV gate operators?
The classification of gate operators is based on the intended use and location of the gate system. Class I is for residential vehicular gates, Class II is for commercial/general access vehicular gates, Class III is for industrial/limited access vehicular gates, and Class IV is for restricted access vehicular gates.
What is the required secondary entrapment protection system for the Powermaster RSW?
The Powermaster RSW requires a secondary entrapment protection system such as photoelectric sensors or an electric edge system to be installed.
How do I put the unit into constant contact for a specific direction?
To put the unit into constant contact for a specific direction, you need to add a 10k in-line resistor to the corresponding monitored input terminal (10 for open and 11 for close).