advertisement
http://biz.lgservice.com
Ceiling Cassette Air Conditioner
SVC MANUAL(Exploded View)
MODEL : LT-H488DLE1
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual.
Only for authorized service personnel.
1. Specification
Indoor
Indoor Unit Type
Models
Decorative Panel Model
Power Supply
Cooling Capacity
Heating Capacity
Ø / V / Hz kW
Btu/h kW
Btu/h
A Current
Fan
Nominal Running Current
Motor Type
Fan Type
Motor Output(W) x No. of Unit
Air Flow Rate
(H / M / L)
External Static Pressure
Capacitor
Coil
Drive
Row x Column x FPI
Dimensions (W x H x D) Body
Net Weight
Decorative Panel
Body
Decorative Panel
Air Filter
Sound Level (H / M / L / SL)
Piping
Connections
Liquid
Gas
Drain(OD/ID)
Dehumidification Rate
Safety Devices
Temperature Sensor
Referigerant
Referigerant Control
Connectable Outdoor Unit
Power and Transmission Interunit Cable
CMM cfm mmAq
µF / Vac mm(inch) mm(inch) kg (lbs) kg (lbs) dB(A)+3 mm (inch) mm (inch) mm l/h
No. x mm 2
Ceiling Cassette
LTNH488DLE1
PT-HDA1
3/380~415/50
14
47,770
15.2
51,865
0.4
BLDC
Turbo
124*1
31/29/27
1094/1024/953
-
680/400
Direct
2R*12C*19FPI
840*840*288(33.1*33.1*11.3)
950*950*30(37.4*37.4*1.2)
31/68.3)
5(11)
Long Life Filter
45/44/42/41
9.52(3/8)
19.05(3/4)
32/25
2.4
Fuse, Thermal Protector
Thermistor
R22
Capillary Tube
LTUH488DLE1
5* 3.5 ( 5* 0.75)
Note:
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27°C(80.6°F) DB/19°C(66.2°F) WB
- Outdoor Temperature 35°C(95°F) DB/24°C(75.2°F) WB
Heating: - Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB
- Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
Conversion Formula kW = Btu/h x 0.0002931
cfm = CMM x 35.3
2 Ceiling Cassette Air Conditioner
Outdoor
Nominal Capacity
(Min~Rating~Max)
Nominal Input
(Min~Rating~Max)
Cooling
Heating
Testing Combination
Running Current(Rating) Cooling
Starting Current
Heating
Cooling/Heating
Power Supply
Power Supply Cable(Outdoor)
Power and Transmission Cable
(Outdoor to Indoor or Outdoor to BD)
Power and Transmission Cable(BD to Indoor)
Dimensions W x H x D
Net Weight
Max. Number of Connectable Indoor Units
Compressor (#1) Type
Qty x Model
Compressor (#2)
Compressor (#3)
Refrigerant
Motor type
Oil charge volume
Oil type
Cycle A Charge (at 7.5m)
Cycle B Charge (at 7.5m)
Type
Control
Additional Refrigerant Charge
Heat Exchanger (Rows x Column x FPI) x No.
Defrosting Method
Fan
Motor type
Oil charge volume
Oil Type
Type
Qty x Model
Motor type
Oil charge volume
Oil type
Type
Qty x Model
Sound Level(H/L)
Piping Connections
Capacitor
Drive
Discharge Direction(Side/Top)
Air Flow RatexNo. of Fan
Sound Pressure
Liquid(Cycle A)
Gas(Cycle A)
Liquid(Cycle B)
Gas(Cycle B)
High Pressure Gas
Max. Interunit
Piping Length
Max. Elevation
Difference
Operation Range
(Outdoor)
Outdoor Unit
Cooling
Heating
Total Piping
Main Piping
Total Branch Piping
Each Branch Piping
Outdoor Unit~Indoor Unit
Indoor Unit~Indoor Unit
Cooling
Heating kW
Btu/h kW
Btu/h kW kW
A
A
A
Ø / V / Hz
No. x mm
No. x mm
No. x mm mm(inch) kg(lbs) cc cc cc g(oz) g(oz) g/m(oz/ft)
µF/Vac
CMM(cfm) dB(A)+3 mm(inch) mm(inch) mm(inch) mm(inch) mm(inch) m m m m m m
°C(°F)
°C(°F)
2
2
2
Note:
1. Capacities are based on the following conditions:
Cooling:
Heating:
- Indoor Temperature 27°C(80.6°F) DB/19°C(66.2°F) WB
- Outdoor Temperature 35°C(95°F) DB/24°C(75.2°F) WB
- Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB
- Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without notic for purpose of improvement.
LTUH488DLE1
14
47,770
15.2
51,865
4.9
4.9
-
8.5
8.7
-
3/380-415/50
5*3.5(Including Earth)
5*0.75(Including Earth)
-
1130*900*370 (44.5 *35.4*14.5)
105(231)
1
SCROLL
1 * SB061YAA
Induction
1,650
SUNISO 4GSI
-
-
-
-
-
-
-
-
-
-
3,700(130.5)
-
R22
Capillary Tube
45(0.48)
(2R*22C*18FPI)*2
Reversing Cycle
6/370-400
Direct
Side
110(3885)
59
9.52(3/8)
19.05(3/4)
-
-
-
50
-
-
-
30
-
21~54
-7~24
Conversion Formula kW = Btu/h x 0.0002931
cfm = CMM x 35.3
Service Manual 3
2. List of Functions
Indoor
Category Function
Air flow
Air Purifier
Installation
Reliability
Convenience
Individual
Control
CAC
Network
Function
Special
Function
Kit
Others
Air Supply Outlet
Airflow Direction Control (left & right)
Airflow Direction Control (up & down)
Auto Swing (left & right)
Auto Swing (up & down)
Airflow Steps(Fan / Cool / Heat)
CHAOS Swing
CHAOS Wind (Auto wind)
Jet Cool (Power Wind)
Swirl Wind
Deodorizing Filter
Plasma Air Purifier
Prefilter(Washable / Anti-Fungus)
Drain Pump
E.S.P. Control
Electric Heater(Operation)
High Ceiling Operation
Hot Start
Self Diagnosis
Soft Dry Operation
Auto Changeover
Auto Cleaning
Auto Operation (Artificial Intelligence)
Auto Restart Operation
Child Lock
Forced Operation
Group Control
Sleep Mode
Timer (On/Off)
Timer (weekly)
Two Thermistor Control
Standard Wired Remote Controller
Deluxe Wired Remote Controller
Simple Wired Remote Controller
Wired Remote Controller(for hotel use)
Wireless Remote Controller(simple)
Wireless LCD Remote Controller
General Central Controller(Non LGAP)
Dry Contact
Network Soluation(LGAP)
PDI(Power Distribution Indicator)
PI485
Zone Control
CTIE
Electro Thermostat
Thermistor
LTNH488DLE1
O
O
O
O
O
O
O
O
O
O
O
-
-
O
O
X
4
-
Auto
X
O
4/5/4
X
O
O
O
X
OPTION
O
O
X
X
X
O
O
X
ACCESSORY(PQWRHSF0)
X
OPTION
O
X
ACCESSORY(PMNFP14A0)
X
X
X
-
Note :
O : Applied, X : Not applied, – : No relation
Option: Model name & price are different according to options, and assembled in factory with main unit.
Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Skip over evaporator sensing means that the function of knock-off to prevent freezing is skipped, when IDU start cooling mode.
4 Ceiling Cassette Air Conditioner
Outdoor
Category
Reliability
Convenience
CAC Network
Function
Special Function Kit
Others
Function
Defrost / Deicing
High Pressure Switch
Low Pressure Switch
Phase protection
Restart Delay (3-minutes)
Self Diagnosis
Soft Start
Test Function
Auto Changeover
Auto Restart Operation
Central control(LGAP)
PDI(Power Distribution Indicator)
PI485
Low Ambient Kit
Thermistor
LTNH488DLE1
O
O
X
O
O
O
X
O
O
O
O
X
X
ACCESSORY
-
Note :
O : Applied, X : Not applied, – : No relation
Option: Model name & price are different according to options, and assembled in factory with main unit.
Accessory: Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Service Manual 5
3. Piping Diagrams
Indoor Unit
Th1
Th2
Capillary Tube Liquid Side
3-Way Valve
Heat
Exchanger
(Evaporator)
Outdoor Unit
Capillary Tube
Gas Side
3-Way Valve
LOC.
Th1
Th2
Th3
Description
Thermistor for indoor air temperature
Thermistor for evaporating temperature
Thermistor for condensing temperature
Heat
Exchanger
(Condenser)
Th3
Compressor
Reversing Valve
High Pressure S/W
Cooling
Heating
PCB Connector
CN_ROOM
CN_PIPE1
Deice PCB
6 Ceiling Cassette Air Conditioner
4. Wiring Diagrams
Indoor Unit
0.7
CN-POWER CN-DPUMP CN-MOTOR2 CN-FLOAT
CN-ROOM
CN-PIPE1
CN-REMO
CN-VANE2 CN-VANE1 CN-DISP
Service Manual 7
Outdoor Unit
Magnetic
Contactor
Fuse
Fan
Capacitor
8 Ceiling Cassette Air Conditioner
Anti phase
PCB
Deice PCB
Connecting wire Terminal block
Main Power
Terminal Block
5. Exploded View
Indoor Unit
130400
W6640
268711
249951
ROOM
W49810
354211
263230-1
PIPE
349480
552111
352118
330870
330860
158591
Note) * Please ensure GCSC since the replacement parts may be changed depending upon the buyer's request.
Please check the correct parts in View RPL(Replacement Part List) on GCSC.
(GCSC Website http://biz.Lgservice.com,)
Service Manual - 9 -
Please check the service part of front panel by model name(PT-HDA1)
130412
130911-4
352150
267110
130911-1
249310
Note) * Please ensure GCSC since the replacement parts may be changed depending upon the buyer's request.
Please check the correct parts in View RPL(Replacement Part List) on GCSC.
(GCSC Website http://biz.Lgservice.com,)
- 10 - Ceiling Cassette Air Conditioner
346810
359012
130911-2
130911-3
Outdoor Unit
Note) * Please ensure GCSC since the replacement parts may be changed depending upon the buyer's request.
Please check the correct parts in View RPL(Replacement Part List) on GCSC.
(GCSC Website http://biz.Lgservice.com,)
Service Manual - 11 -