- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Mitsubishi Electric
- Mr. Slim MUZ-GE15NA-1
- Service manual
advertisement
Revision G:
• The descriptions of the expansion valve coil have been corrected. (10-4.)
• Some descriptions have been modified.
Please void OBH549 REVISED EDITION-F.
OUTDOOR UNIT
SERVICE MANUAL
HFC
utilized
R410A
No. OBH549
REVISED EDITION-G
Models
MUZ-GE09NA
MUZ-GE09NA2
MUZ-GE12NA
MUZ-GE12NA2
MUZ-GE15NA,
MUZ-GE15NA2
-
1
-
1
MUZ-GE18NA,
MUZ-GE24NA
MUY-GE09NA
MUY-GE09NA2
MUY-GE12NA
MUY-GE12NA2
MUY-GE15NA,
MUY-GE15NA2
-
1
MUZ-GE09NAH
MUZ-GE09NAH2
MUZ-GE12NAH
MUZ-GE12NAH2
MUZ-GE15NAH
MUZ-GE15NAH2
MUZ-GE18NAH
MUY-GE18NA,
MUY-GE24NA
-
1
Indoor unit service manual
MSZ-GE•NA MSY-GE•NA Series (OBH548)
MUZ-GE09NA/NA2
MUZ-GE12NA/NA2
MUZ-GE15NA,
-
1
/NA2
MUY-GE09NA/NA2
MUY-GE12NA/NA2
MUY-GE15NA,
-
1
/NA2
MUZ-GE09NAH/NAH2
MUZ-GE12NAH/NAH2
MUZ-GE15NAH/NAH2
CONTENTS
1. TECHNICAL CHANGES ··································· 3
2. PART NAMES AND FUNCTIONS ····················· 4
3. SPECIFICATION ················································ 6
4. OUTLINES AND DIMENSIONS ······················ 10
5. WIRING DIAGRAM ·········································· 13
6. REFRIGERANT SYSTEM DIAGRAM ············· 25
7. DATA ································································ 28
8. ACTUATOR CONTROL ··································· 42
9. SERVICE FUNCTIONS ··································· 43
10. TROUBLESHOOTING ····································· 44
11. DISASSEMBLY INSTRUCTIONS ···················· 64
PARTS CATALOG (OBB549)
TM
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
Use the speci
fi
ed refrigerant only
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of.
Correct refrigerant is specified in the manuals and on the spec labels provided with our products.
We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
Revision A:
•
MUZ-GE24NA and MUY-GE24NA have been added.
Revision B:
•
Descriptions regarding the outdoor fan motor has been corrected.
Revision C:
•
MUZ-GE15NA-
1
, MUZ-GE18NA-
1
, MUY-GE15NA-
1
, and MUY-GE18NA-
1
have been added.
Revision D:
• Specification has been corrected. [Capacity Capacity Rated (Maximum), Power consumption Power consumption Rated (Maximum)]
Revision E:
• MUZ-GE09NAH, MUZ-GE12NAH, MUZ-GE15NAH and MUZ-GE18NAH have been added.
Revision F:
• MUZ-GE09/12/15NA2, MUZ-GE09/12/15NAH2 and MUY-GE09/12/15NA2 have been added.
Revision G:
• The descriptions of the expansion valve coil have been corrected. (10-4.)
• Some descriptions have been modified.
OBH549G
2
1
TECHNICAL CHANGES
MUZ-GE09NA MUY-GE09NA
MUZ-GE12NA MUY-GE12NA
MUZ-GE15NA MUY-GE15NA
MUZ-GE18NA MUY-GE18NA
MUZ-GE24NA MUY-GE24NA
1. New model
MUZ-GE15NA MUZ-GE15NA -
1
MUZ-GE18NA MUZ-GE18NA -
1
1. Compressor has been changed.
2. Inverter P.C. board has been changed.
MUY-GE15NA MUY-GE15NA -
1
MUY-GE18NA MUY-GE18NA -
1
1. Compressor has been changed.
2. Inverter P.C. board has been changed.
MUZ-GE09NA MUZ-GE09NAH
1. Defrost heater has been added.
2. Reactor has been changed.
3. Inverter P.C. board has been changed.
MUZ-GE12NA MUZ-GE12NAH
MUZ-GE15NA -
1
MUZ-GE15NAH
MUZ-GE18NA -
1
MUZ-GE18NAH
1. Defrost heater has been added.
2. Inverter P.C. board has been changed.
MUZ-GE09NA
MUZ-GE12NA
MUZ-GE09NA2
MUZ-GE12NA2
MUZ-GE15NA -
1
MUZ-GE15NA2
MUZ-GE09NAH MUZ-GE09NAH2
MUZ-GE12NAH
MUZ-GE15NAH
MUY-GE09NA
MUY-GE12NA
MUZ-GE12NAH2
MUZ-GE15NAH2
MUY-GE09NA2
MUY-GE12NA2
MUY-GE15NA -
1
MUY-GE15NA2
1. SEER and HSPF have been added.
OBH549G
3
2
PART NAMES AND FUNCTIONS
MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA
MUZ-GE09NA2 MUZ-GE12NA2 MUZ-GE15NA2
MUZ-GE09NAH MUZ-GE12NAH MUZ-GE15NAH
MUZ-GE09NAH2 MUZ-GE12NAH2 MUZ-GE15NAH2
MUY-GE09NA MUY-GE12NA MUY-GE15NA
MUY-GE09NA2 MUY-GE12NA2 MUY-GE15NA2
Air inlet
(back and side)
Piping
Drain hose
Air outlet
Drain outlet
MUZ-GE18NA
MUZ-GE18NAH
MUY-GE18NA
Air inlet
(back and side)
Piping
Drain hose
Air outlet
Drain outlet
OBH549G
4
MUZ-GE24NA
MUY-GE24NA
Air inlet
(back and side)
Piping
Drain hose
Air outlet
Drain outlet
OBH549G
5
3
SPECIFICATION
Outdoor unit model
Capacity
Rated (Minimum~Maximum)
Cooling 1
Heating 47 1
Btu/h
Btu/h
MUZ-GE09NA
MUZ-GE09NA2
MUZ-GE09NAH
MUZ-GE09NAH2
9,000
( 3,800 ~ 12,200 )
10,900
( 4,500 ~ 14,100 )
MUY-GE09NA
MUY-GE09NA2
9,000
( 3,800 ~ 12,200 )
—
MUZ-GE12NA
MUZ-GE12NA2
MUZ-GE12NAH
MUZ-GE12NAH2
12,000
( 3,800 ~ 13,600 )
14,400
( 5,500 ~ 18,100 )
MUY-GE12NA
MUY-GE12NA2
12,000
( 3,800 ~ 13,600 )
—
Capacity
Rated (Maximum)
Heating 17 2
Power consumption
Rated (Minimum~Maximum)
Cooling 1
Heating 47 1
Btu/h
W
W
6,600 (8,700) — 8,800 (11,200) —
660 (205~1,200) 660 (205~1,200) 960 (205~1,300) 960 (205~1,300)
760 (255~1,200) — 1,170 (340~1,660) —
Power consumption
Rated (Maximum)
Heating 17 2 W 700 (950) — 900 (1,200) —
EER 1 [SEER]
Compressor
3 Cooling
HSPF IV 4 Heating
09NA/H
: 13.6 [ 21.0 ]
09NA
: 13.6 [ 21.0 ]
09NA2/H2
: 13.6 [23.2]
09NA2
: 13.6 [23.2]
09NA/H
: 10.0
09NA2
: 11.0
—
09NAH2
: 10.1
COP Heating 1 4.20
Power supply
Max. fuse size (time delay)
V , phase , Hz
A
Min. circuit ampacity
Fan motor
A
F.L.A
Model KNB073FQDHC
—
R.L.A 6.6
L.R.A 8.2
4.9
6.1
12NA/H
: 12.5 [ 20.5 ]
12NA/H
: 12.5 [ 20.5 ]
12NA2/H2
: 12.5 [22.7]
12NA2/H2
: 12.5 [22.7]
12NA/H
: 10.0
12NA2
: 11.4
—
12NAH2
: 10.8
3.61
208/230 , 1 , 60
15
12
0.50
KNB092FQAHC
—
6.6
8.2
4.9
6.1
Refrigeration oil
(Model)
L 0.32 (NEO22)
Refrigerant control Linear expansion valve
Sound level 1
Cooling dB(A)
Heating dB(A) 50
46
— 51
49
—
Defrost method
Dimensions
W
D
H in.
in.
in.
Reverse cycle
31-1/2
11-1/4
21-5/8
77
External fi nish Munsell 3Y 7.8/1.1
Remote controller
Control voltage (by built-in transformer)
Refrigerant piping
VDC
Wireless type
12 - 24
Not supplied
Refrigerant pipe size
(Min. wall thickness)
Connection method
Liquid in.
Gas in.
Indoor Flared
Outdoor Flared ft.
40
Between the indoor & outdoor units
Height difference
Piping length
Refrigerant charge (R410A) ft.
1 lb. 12 oz.
65
NOTE
: Test conditions are based on AHRI 210/240.
1: Rating conditions (Cooling) — Indoor: 80 ˚ FDB, 67 ˚ FWB, Outdoor: 95 ˚ FDB, (75 ˚ FWB)
(Heating) — Indoor: 70 ˚ FDB, 60 ˚ FWB, Outdoor: 47 ˚ FDB, 43 ˚ FWB
2: (Heating) ˚ FWB, Outdoor: 17 ˚ FDB, 15 ˚ FWB
2 lb. 9 oz.
OBH549G
6
Outdoor unit model
Capacity
Rated (Minimum~Maximum)
Cooling 1
Heating 47 1
Btu/h
Btu/h
MUZ-GE15NA
MUZ-GE15NA-
1
MUZ-GE15NA2
MUZ-GE15NAH
MUZ-GE15NAH2
14,000
( 3,100 ~ 18,200 )
18,000
( 4,800 ~ 20,900 )
MUY-GE15NA
MUY-GE15NA-
MUY-GE15NA2
14,000
1
( 3,100 ~ 18,200 )
—
MUZ-GE18NA
MUZ-GE18NA-
MUZ-GE18NAH
1
17,200
( 3,700 ~ 18,700 )
21,600
( 3,500 ~ 25,200 )
MUY-GE18NA
MUY-GE18NA-
17,200
( 3,700 ~ 18,700 )
—
1
Capacity
Rated (Maximum)
Heating 17 2
Power consumption
Rated (Minimum~Maximum)
Cooling 1
Heating 47 1
Power consumption
Rated (Maximum)
Heating 17 2
Btu/h
W
W
W
11,300 (15,900) — 13,400 (17,200) —
1,080 (160 ~ 2,000) 1,080 (160 ~ 2,000) 1,640 (240 ~ 2,070) 1,640 (240 ~ 2,070)
1,600 (270 ~ 2,010)
1,150 (1,950)
—
—
EER
1
[SEER] 3 Cooling
15NA/H
: 13.0 [ 21.0]
15NA/H
: 13.0 [ 21.0]
15NA2/H2
: 13.6 [ 21.6]
15NA2/H2
: 13.6 [ 21.6]
15NA/H
: 10.0
15NA2
: 11.2
— HSPF IV 4 Heating
15NA2/H2
: 10.8
COP Heating 1 3.30
—
1,900 (230 ~ 2,680)
1,450 (2,080)
10.5 [19.2]
10.0
3.33
—
—
10.5 [19.2]
—
—
208/230 , 1 , 60
15
14
0.93
SNB130FQBH
Power supply
Max. fuse size (time delay)
Min. circuit ampacity
Fan motor
Compressor
Model
(Model)
V , phase , Hz
A
A
F.L.A
12
0.50
MUZ/MUY-GE NA
MUZ/MUY-GE NA2
MUZ/MUY-GE NA-
1
MUZ-GE NAH, NAH2
R.L.A 7.4
L.R.A 9.3
Refrigeration oil
L
Refrigerant control
Sound level 1
Cooling dB(A)
Heating dB(A) 51
49
Defrost method
Dimensions
W
D
H in.
in.
in.
31-1/2
11-1/4
21-5/8
6.8
8.5
SNB130FQBHT
Linear expansion valve
—
0.45 (NEO22)
Reverse cycle
56
10.0
12.5
54
33-1/16
13
33-7/16
119
—
External fi nish
Remote controller
Control voltage (by built-in transformer)
Refrigerant piping
VDC
Munsell 3Y 7.8/1.1
Wireless type
12 - 24
Not supplied
Refrigerant pipe size
(Min. wall thickness)
Liquid in.
Gas in.
Connection method
Between the indoor & outdoor units
Indoor Flared
Outdoor Flared
Height difference
Piping length
Refrigerant charge (R410A) ft.
ft.
40
65
2 lb. 9 oz.
50
100
3 lb. 7 oz.
NOTE
: Test conditions are based on AHRI 210/240.
1: Rating conditions (Cooling) — Indoor: 80 ˚ FDB, 67 ˚ FWB, Outdoor: 95 ˚ FDB, (75 ˚ FWB)
(Heating) — Indoor: 70 ˚ FDB, 60 ˚ FWB, Outdoor: 47 ˚ FDB, 43 ˚ FWB
2: (Heating) ˚ FWB, Outdoor: 17 ˚ FDB, 15 ˚ FWB
OBH549G
7
Outdoor unit model
Compressor
MUZ-GE24NA MUY-GE24NA
Capacity
Rated (Minimum~Maximum)
Cooling 1
Heating 47 1
Btu/h
Btu/h
22,500
(8,200 ~ 31,400)
27,600
(7,500 ~ 36,900)
22,500
(8,200 ~ 31,400)
—
Capacity
Rated (Maximum)
Heating 17 2
Power consumption
Rated (Minimum~Maximum)
Cooling 1
Heating 47 1
Power consumption
Rated (Maximum)
Heating 17 2
Min. circuit ampacity
Fan motor
Btu/h
W
W
W
A
F.L.A
16,000 (24,600)
1,800 (570 ~ 3,580) 1,800 (570 ~ 3,580)
2,340 (520 ~ 3,650)
1,770 (3,290)
EER 1 [SEER] 3 Cooling
HSPF IV 4 Heating 10.0
COP Heating 1 3.46
Power supply
Max. fuse size (time delay)
V , phase , Hz
A
208/230 , 1 , 60
20
17.1
0.93
—
—
—
—
—
Model SNB172FQKMT
R.L.A 12.9
L.R.A 16.1
Refrigeration oil
(Model)
L 0.40 (FV50S)
Refrigerant control
Sound level
Dimensions
1
Defrost method
Cooling dB(A)
Heating dB(A)
W
D
H in.
in.
in.
Linear expansion valve
55
55 —
Reverse cycle
33-1/16
13
34-5/8
External fi nish
Remote controller
Control voltage (by built-in transformer)
Refrigerant piping
VDC
Munsell 3Y 7.8/1.1
Wireless type
12-24
Not supplied
Refrigerant pipe size
(Min. wall thickness)
Connection method
Between the indoor & outdoor units
Liquid in.
Gas in.
Indoor Flared
Outdoor Flared
Height difference
Piping length
Refrigerant charge (R410A) ft.
ft.
50
100
4 lb. 3 oz.
NOTE
: Test conditions are based on AHRI 210/240.
1: Rating conditions (Cooling) — Indoor: 80 ˚ FDB, 67 ˚ FWB, Outdoor: 95 ˚ FDB, (75 ˚ FWB)
(Heating) — Indoor: 70 ˚ FDB, 60 ˚ FWB, Outdoor: 47 ˚ FDB, 43 ˚ FWB
2: (Heating) ˚ FWB, Outdoor: 17 ˚ FDB, 15 ˚ FWB
OBH549G
8
Test condition
3, 4
ARI
Mode Test
Indoor air condition (°F)
Dry bulb Wet bulb
Outdoor air condition (°F)
Dry bulb Wet bulb
"A-2" Cooling Steady State at rated compressor Speed
"B-2" Cooling Steady State at rated compressor Speed
SEER
(Cooling)
"B-1" Cooling Steady State at minimum compressor Speed
"F-1" Cooling Steady State at minimum compressor Speed
"E-V" Cooling Steady State at Intermediate compressor Speed 5
"H1-2" Heating Steady State at rated compressor Speed
80
80
80
80
80
70
67
67
67
67
67
60
95
82
82
67
87
47
HSPF
(Heating)
(MUZ)
"H3-2" Heating at rated compressor Speed
"H0-1" Heating Steady State at minimum compressor Speed
"H1-1" Heating Steady State at minimum compressor Speed
"H2-V" Heating at Intermediate compressor Speed 5
70
70
70
70
60
60
60
60
17
62
47
35
5 : At Intermediate compressor Speed
= ("Cooling rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed".
(75)
(65)
(65)
(53.5)
(69)
43
15
56.5
43
33
3-1. OPERATING RANGE
(1) POWER SUPPLY
Rated voltage
Outdoor unit
208/230 V
1 phase
60 Hz
Guaranteed voltage (V)
Min. 187 208 230 Max. 253
(2) OPERATION
Mode Condition
Cooling
Heating
(MUZ)
Standard temperature
Maximum temperature
Minimum temperature
Maximum humidity
Standard temperature
Maximum temperature
Minimum temperature
DB
80
90
67
70
80
70
Indoor
78 %
Intake air temperature (°F)
WB
67
73
57
60
67
60
DB
95
115
14
47
75
-4
Outdoor
—
WB
—
—
—
43
65
-5
OBH549G
9
4
OUTLINES AND DIMENSIONS
MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA
MUZ-GE09NA2 MUZ-GE12NA2 MUZ-GE15NA2
MUZ-GE09NAH MUZ-GE12NAH MUZ-GE15NAH
MUZ-GE09NAH2 MUZ-GE12NAH2 MUZ-GE15NAH2
MUY-GE09NA MUY-GE12NA MUY-GE15NA
MUY-GE09NA2 MUY-GE12NA2 MUY-GE15NA2
15-3/4
Air in
Drain hole ø1-5/8
(GE09/12/15NA/NA2)
Drain hole ø1-5/16
(GE09/12/15NAH/NAH2)
REQUIRED SPACE
*1
4 in.
or more when front and sides of the unit are clear
Air in
4 in.
or more
4 in.
or more
Unit: inch
8 in.
or more *2
*2 When any 2 sides of left, right and rear of the unit are clear
14 in.
or more
7/8 handle
Air out
1-9/16
2- 3/8 13/16 Oval hole
29/32 11-1/4 17/32
6-23/32
Liquid pipe :1/4 (flared)
Gas pipe :3/8 (flared)
(GE09/12)
1/2 (flared)
(GE15)
5-15/16
11-29/32
19-11/16
31-1/2 2-23/32
OBH549G
10
MUZ-GE18NA
MUZ-GE18NAH
MUY-GE18NA
Drain 3 holes
ø1-5/16
(GE18NA)
20-9/32
11-25/32
2-19/32
Air in
Air in
Drain hole
ø1-5/16
(GE18NAH)
Air out
19-11/16
33-1/16
4-25/32
Unit: inch
1-9/16
4-3/8 × 13/16 slot
3-3/16
REQUIRED SPACE
*1
20 in.
more when front
and sides of the unit are clear
4 in.
or more
4 in
. or more
14 in
. or more
20 in.
or more *2
*2 When any 2 sides of left, right
and rear of the unit are clear
35°
30°
8-11/32
Liquid:1/4(flared)
Gas :1/2(flared)
OBH549G
11
MUZ-GE24NA
MUY-GE24NA
16-7/16
Air in
Drain hole
1-9/16
1-5/8
REQUIRED SPACE
*1
20 in.
or more when front and sides of the unit are clear
4 in.
or more
4 in.
or more
6-7/8
Air out
19-11/16
33-1/16
4-5/16
2-holes 13/32 13/16
3-3/16
14 in.
or more
20 in.
or more *2
*2 When any 2 sides of left, right and rear of the unit are clear
Service panel
Liquid refrigerant pipe joint
Refrigerant pipe (flared)
Ø
3/8
7-11/16
44
35
Gas refrigerant pipe joint
Refrigerant pipe (flared)
Ø
5/8
Unit: inch
OBH549G
12
5
WIRING DIAGRAM
MUZ-GE09NA MUZ-GE12NA
MUZ-GE09NA2 MUZ-GE12NA2
OBH549G
13
MUZ-GE09NAH MUZ-GE12NAH
MUZ-GE09NAH2 MUZ-GE12NAH2
OBH549G
14
MUY-GE09NA MUY-GE12NA
MUY-GE09NA2 MUY-GE12NA2
OBH549G
15
MUZ-GE15NA
MUZ-GE15NA-
1
OBH549G
16
MUZ-GE15NA2
MUZ-GE15NAH
OBH549G
17
MUZ-GE15NAH2
MUY-GE15NA
OBH549G
18
MUY-GE15NA-
1
MUY-GE15NA2
OBH549G
19
MUZ-GE18NA
MUZ-GE18NA-
1
OBH549G
20
MUZ-GE18NAH
MUY-GE18NA
OBH549G
21
MUY-GE18NA-
1
OBH549G
22
MUZ-GE24NA
OBH549G
23
MUY-GE24NA
OBH549G
24
6
REFRIGERANT SYSTEM DIAGRAM
MUZ-GE09NA MUZ-GE09NA2
MUZ-GE09NAH MUZ-GE09NAH2
MUY-GE09NA MUY-GE09NA2
Refrigerant pipe ø3/8
(with heat insulator)
Muffler
Flared connection
4-way valve
Stop valve
(with service port)
Service port
Discharge temperature thermistor
RT62
Muffler
Service port
Compressor
Defrost thermistor
RT61
(
MUZ
)
Outdoor heat exchanger
Outdoor heat exchanger temperature thermistor
RT68
Ambient temperature thermistor
RT65
Unit: inch
Flared connection
Capillary tube
O.D. 0.118 × I.D. 0.079
× 9-7/16
(ø3.0 × ø2.0 × 240)
LEV
Strainer
#100
R.V. coil (
MUZ
) heating ON cooling OFF
Refrigerant pipe ø1/4
(with heat insulator)
Stop valve
(with strainar)
Refrigerant flow in cooling
Refrigerant flow in heating (
MUZ
)
MUZ-GE12NA MUZ-GE12NA2 MUZ-GE15NA MUZ-GE15NA2
MUZ-GE12NAH MUZ-GE12NAH2 MUZ-GE15NAH MUZ-GE15NAH2
MUY-GE12NA MUY-GE12NA2 MUY-GE15NA MUY-GE15NA2
Refrigerant pipe ø3/8
(GE12NA)
Refrigerant pipe ø1/2
(GE15NA)
(with heat insulator)
Muffler
4-way valve
Flared connection
Stop valve
(with service port)
Discharge temperature thermistor
RT62
Service port
Muffler
Service port
Compressor
Defrost thermistor
RT61
(
MUZ
)
Outdoor heat exchanger
Outdoor heat exchanger temperature thermistor
RT68
Ambient temperature thermistor
RT65
Flared connection
Capillary tube
O.D. 0.118 × I.D. 0.079
× 9-7/16
(ø3.0 × ø2.0 × 240)
LEV
Capillary tube
O.D. 0.118 × I.D. 0.071
× 23-5/8
(ø3.0 × ø1.8 × 600) (×2)
Strainer
#100
R.V. coil (
MUZ
) heating ON cooling OFF
Refrigerant pipe ø1/4
(with heat insulator)
Stop valve
(with strainar)
OBH549G
25
Refrigerant flow in cooling
Refrigerant flow in heating (
MUZ
)
MUZ-GE18NA
MUZ-GE18NAH
MUY-GE18NA
Refrigerant pipe ø1/2
(with heat insulator)
4-way valve
Muffler
#100
Flared connection
Stop valve
(with service port)
Service port
Discharge temperature thermistor
RT62
Service port
Defrost thermistor
RT61
(
MUZ
)
Outdoor heat exchanger
Ambient temperature thermistor
RT65
Unit: inch
Flared connection
Receiver
Refrigerant pipe ø1/4
(with heat insulator)
Stop valve
(with strainar)
Compressor
Outdoor heat exchanger temperature thermistor
RT68
LEV
Strainer
#100
Capillary tube
O.D. 0.142 × I.D. 0.094
× 1-31/32
(ø 3.6×ø2.4×50)
R.V. coil
(
MUZ
heating ON cooling OFF
)
Refrigerant flow in cooling
Refrigerant flow in heating
(
MUZ
)
MUZ-GE24NA
MUY-GE24NA
Refrigerant pipe ø5/8
(with heat insulator)
4-way valve
Muffler
#100
Service port
Flared connection
Stop valve
(with service port)
Service port
Discharge temperature thermistor
RT62
Defrost thermistor
RT61
(
MUZ
)
Outdoor heat exchanger
Ambient temperature thermistor
RT65
Flared connection
Strainer
#100
Stop valve
Refrigerant pipe ø3/8
(with heat insulator)
Compressor
Outdoor heat exchanger temperature thermistor
RT68
LEV
Strainer
#100
Capillary tube
O.D.0.157 × I.D.0.094
× 3-15/16
(ø 4.0×ø2.4×100)
R.V. coil (
MUZ
heating ON cooling OFF
)
Refrigerant flow in cooling
Refrigerant flow in heating (
MUZ
)
OBH549G
26
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
Refrigerant piping: ft.
Max. Length
A
Max. Height difference
B
Gas
Piping size O.D: in.
Liquid
MUZ-GE09/12/15NA/NA2
MUZ-GE09/12/15NAH/NAH2
MUY-GE09/12/15NA/NA2
MUZ-GE18NA
MUZ-GE18NAH
MUY-GE18NA
MUZ-GE24NA
MUY-GE24NA
65 40
100 50
100 50
3/8
(GE09/12)
1/2
(GE15)
1/2
5/8
1/4
3/8
Indoor unit
Max. Height difference
B
Max. Length
A
Outdoor unit
ADDITIONAL REFRIGERANT CHARGE (R410A: oz.)
NOTE
: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model
Outdoor unit precharged
25 30
Refrigerant piping length (one way): ft.
40 50 60
MUZ-GE09NA/NA2
MUZ-GE09NAH/NAH2
MUY-GE09NA/NA2
MUZ-GE12NA/NA2
MUZ-GE12NAH/NAH2
MUY-GE12NA/NA2
MUZ-GE15NA/NA2
MUZ-GE15NAH/NAH2
MUY-GE15NA/NA2
1 lb. 12 oz.
2 lb. 9 oz.
0 1.62
4.86
8.10
11.34
Model
Outdoor unit precharged
25 30
65
12.96
Calculation: X oz. = 1.62/5 oz. / ft. × (Refrigerant piping length (ft.) - 25)
40
Refrigerant piping length (one way): ft.
50 60 70 80 90 100
MUZ-GE18NA
MUZ-GE18NAH
MUY-GE18NA
3 lb. 7 oz.
0 1.08 3.24 5.40 7.56 9.72 11.88 14.04 16.20
Calculation: X oz. = 1.08/5 oz. / ft. × (Refrigerant piping length (ft.) - 25)
NOTE
: Refrigerant piping exceeding 33 ft. requires additional refrigerant charge according to the calculation.
Model
Outdoor unit precharged
33 40
Refrigerant piping length (one way): ft.
50 60 70 80 90
MUZ-GE24NA
MUY-GE24NA
4 lb. 3 oz.
0 4.14
10.06
15.98
21.90
27.82
33.74
100
39.66
Calculation: X oz. = 2.96/5 oz. / ft. × (Refrigerant piping length (ft.) - 33)
OBH549G
27
7 DATA
7-1. PERFORMANCE DATA
1) COOLING CAPACITY
MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA
MUZ-GE09NA2 MUZ-GE12NA2 MUZ-GE15NA2
MUZ-GE09NAH MUZ-GE12NAH MUZ-GE15NAH MUZ-GE18NAH
MUZ-GE09NAH2 MUZ-GE12NAH2 MUZ-GE15NAH2
MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA
MUY-GE09NA2 MUY-GE12NA2 MUY-GE15NA2
MUZ-GE24NA
MUY-GE24NA
Model
MUZ-GE09NA/NA2
MUZ-GE09NAH/NAH2
MUY-GE09NA/NA2
MUZ-GE12NA/NA2
MUZ-GE12NAH/NAH2
MUY-GE12NA/NA2
MUZ-GE15NA/NA2
MUZ-GE15NAH/NAH2
MUY-GE15NA/NA2
MUZ-GE18NA
MUZ-GE18NAH
MUY-GE18NA
MUZ-GE24NA
MUY-GE24NA
Indoor air
IWB (
71
67
63
63
71
67
63
67
63
71
67
71
67
63
71
˚ F)
Outdoor intake air DB temperature ( ˚ F)
75 85 95 105 115
TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC
11.0
7.6 0.59 10.3 7.1 0.64 9.7
6.6 0.69 9.0
6.2 0.73 8.3
5.7 0.76
10.4 8.6 0.55 9.7
8.0 0.61 9.0
7.4 0.66 8.4
6.9 0.70 7.7
6.3 0.73
9.8
9.4 0.53 9.1
8.7 0.58 8.5
8.1 0.63 7.7
7.3 0.67 7.0
6.7 0.70
14.7 8.9 0.85 13.7 8.3 0.94 12.9 7.8 1.01 12.0 7.3 1.06 11.0
6.7 1.10
13.9 10.3 0.81 13.0 9.6 0.89 12.0 8.9 0.96 11.2
8.3 1.02 10.3 7.6 1.07
13.1 11.4 0.77 12.1 10.6 0.85 11.3
9.9 0.92 10.3 9.0 0.98 9.4
8.2 1.02
17.2 11.4 0.96 16.0 10.7 1.05 15.1 10.0 1.13 14.0 9.3 1.19 12.9 8.6 1.24
16.2 13.0 0.91 15.1 12.1 1.00 14.0 11.2 1.08 13.0 10.4 1.14 12.0 9.6 1.20
15.3 14.2 0.86 14.1 13.2 0.96 13.2 12.3 1.03 12.0 11.2 1.10 10.9 10.2 1.14
21.1 12.2 1.46 19.7 11.4 1.60 18.5 10.7 1.72 17.2 9.9 1.81 15.8 9.1 1.89
20.0 14.2 1.38 18.6 13.2 1.52 17.2 12.2 1.64 16.0 11.4 1.74 14.7 10.4 1.82
18.7 15.8 1.31 17.4 14.7 1.45 16.2 13.6 1.57 14.7 12.4 1.67 13.4 11.3 1.74
27.6 17.0 1.60 25.8 15.9 1.76 24.2 14.9 1.89 22.5 13.9 1.99 20.7 12.8 2.07
26.1 19.6 1.51 24.3 18.2 1.67 22.5 16.9 1.80 20.9 15.7 1.91 19.2 14.4 2.00
24.5 21.7 1.44 22.7 20.1 1.59 21.2 18.7 1.72 19.2 17.0 1.84 17.6 15.5 1.91
NOTE
: 1. IWB: Intake air wet-bulb temperature
TC: Total Capacity (×10
3
Btu/h)
SHC: Sensible Heat Capacity (×10 3 Btu/h)
TPC: Total Power Consumption (kW)
2. SHC is based on 80 ˚ F of indoor Intake air DB temperature.
2) COOLING CAPACITY CORRECTIONS
Refrigerant piping length (one way: ft.)
25 (std.) 40 65 100
MUZ-GE09NA/NA2
MUZ-GE09NAH/NAH2
MUY-GE09NA/NA2
MUZ-GE12NA/NA2
MUZ-GE12NAH/NAH2
MUY-GE12NA/NA2
MUZ-GE15NA/NA2
MUZ-GE15NAH/NAH2
MUY-GE15NA/NA2
MUZ-GE18NA
MUZ-GE18NAH
MUY-GE18NA
1.0
0.954
0.878
—
MUZ-GE24NA
MUY-GE24NA
1.0
0.954
0.878
0.771
OBH549G
28
3) HEATING CAPACITY (MUZ)
Model
MUZ-GE09NA
MUZ-GE09NA2
MUZ-GE09NAH
MUZ-GE09NAH2
MUZ-GE12NA
MUZ-GE12NA2
MUZ-GE12NAH
MUZ-GE12NAH2
MUZ-GE15NA
MUZ-GE15NA2
MUZ-GE15NAH
MUZ-GE15NAH2
MUZ-GE18NA
MUZ-GE18NAH
MUZ-GE24NA
Indoor air
IDB (
70
65
75
70
75
70
65
75
65
75
70
65
65
75
70
65
70
65
75
70
75
70
65
75
75
70
65
˚ F)
5 15
Outdoor intake air WB temperature ( ˚ F)
25 35 43 45 55
TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC
4.8
0.45
6.3
0.57
7.9
0.67
9.4
0.74 10.6 0.78 11.0 0.79 12.4 0.82
5.2
0.43
6.7
0.55
8.2
0.65
9.6
0.72 10.9 0.76 11.2 0.78 12.7 0.81
5.5
0.41
6.9
0.52
8.6
0.63 10.0 0.70 11.2 0.74 11.6 0.75 13.0 0.79
4.8
0.58
6.3
0.70
7.9
0.80
9.4
0.74 10.6 0.78 11.0 0.79 12.4 0.82
5.2
0.56
6.7
0.68
8.2
0.78
9.6
0.72 10.9 0.76 11.2 0.78 12.7 0.81
5.5
0.54
6.9
0.65
8.6
0.76 10.0 0.70 11.2 0.74 11.6 0.75 13.0 0.79
6.3
0.69
8.4
0.87 10.4 1.02 12.5 1.14 14.0 1.20 14.5 1.22 16.4 1.26
6.8
0.66
8.9
0.84 10.8 1.00 12.7 1.11 14.4 1.17 14.8 1.19 16.8 1.24
7.2
0.63
9.1
0.81 11.3 0.97 13.2 1.08 14.8 1.14 15.3 1.16 17.1 1.22
6.3
0.82
8.4
1.00 10.4 1.15 12.5 1.14 14.0 1.20 14.5 1.22 16.4 1.26
6.8
0.79
8.9
0.97 10.8 1.13 12.7 1.11 14.4 1.17 14.8 1.19 16.8 1.24
7.2
0.76
9.1
0.94 11.3 1.10 13.2 1.08 14.8 1.14 15.3 1.16 17.1 1.22
7.9
0.63 10.4 0.79 13.1 0.93 1.56 1.03 17.6 1.09 18.1 1.10 20.5 1.14
8.6
0.60 11.1 0.76 13.5 0.91 15.9 1.01 18.0 1.06 18.5 1.08 21.0 1.12
9.0
0.57 11.3 0.73 14.1 0.87 16.5 0.98 18.5 1.03 19.1 1.05 21.4 1.10
7.9
0.76 10.4 0.92 13.1 1.06 15.6 1.03 17.6 1.09 18.1 1.10 20.5 1.14
8.6
0.73 11.1 0.89 13.5 1.04 15.9 1.01 18.0 1.06 18.5 1.08 21.0 1.12
9.0
0.70 11.3 0.86 14.1 1.00 16.5 0.98 18.5 1.03 19.1 1.05 21.4 1.10
9.1
0.64 11.9 0.81 14.9 0.95 17.8 1.06 20.1 1.12 20.7 1.13 23.5 1.18
9.8
0.62 12.7 0.78 15.5 0.93 18.2 1.04 20.6 1.09 21.2 1.11 24.0 1.16
10.3 0.59 13.0 0.75 16.2 0.90 18.8 1.01 21.2 1.06 21.8 1.08 24.5 1.13
9.1
0.77 11.9 0.94 14.9 1.08 17.8 1.06 20.1 1.12 20.7 1.13 23.5 1.18
9.8
0.75 12.7 0.91 15.5 1.06 18.2 1.04 20.6 1.09 21.2 1.11 24.0 1.16
10.3 0.72 13.0 0.88 16.2 1.03 18.8 1.01 21.2 1.06 21.8 1.08 24.5 1.13
12.1 1.38 16.0 1.74 20.0 2.05 23.9 2.28 26.9 2.40 27.7 2.43 31.5 2.53
13.1 1.32 17.0 1.68 20.7 2.00 24.4 2.22 27.6 2.34 28.4 2.39 32.2 2.48
13.8 1.26 17.4 1.61 21.7 1.93 25.3 2.16 28.4 2.28 29.3 2.32 32.8 2.43
NOTE
: 1. IDB: Intake air dry-bulb temperature
TC: Total Capacity (x10 3 Btu/h)
TPC: Total Power Consumption (kW)
2. Above data is for heating operation without any frost.
How to operate with fixed operational frequency of the compressor.
1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL mode or EMERGENCY HEAT mode before starting to operate the air conditioner.
2. The compressor starts with operational frequency.
3. The fan speed of the indoor unit is High.
4. This operation continues for 30 minutes.
5. In order to release this operation, press the EMERGENCY OPERATION switch twice or once, or press any button on the remote controller.
OBH549G
29
7-2. PERFORMANCE CURVE
Cooling
Cooling capacity
(at Rated frequency)
1.5
1.4
Indoor intake air WB temperature( F)
1.3
1.2
79
1.1
75
1.0
0.5
65
0.9
104 113
72
68
64
14 23 32 41 50 59 68 77 86
Outdoor intake air DB temperature(°F)
MUZ-GE09NA
MUZ-GE09NAH
MUY-GE09NA
SHF at rating condition = 0.76
Airflow = 307 CFM
0.8
MUZ-GE09NA2
MUZ-GE09NAH2
MUY-GE09NA2
0.7
0.6
Indoor intake air WB temperature (°F)
75 85 95 105
Outdoor intake air DB temperature (°F)
71
67
63
115
95
MUZ-GE12NA
MUZ-GE12NAH
MUY-GE12NA
1.3
1.2
1.1
1.0
0.9
0.8
0.7
65
MUZ-GE12NA2
MUZ-GE12NAH2
MUY-GE12NA2
SHF at rating condition = 0.73
Airflow = 350 CFM
Indoor intake air WB temperature (°F)
75 85 95 105
Outdoor intake air DB temperature (°F)
71
67
63
115
MUZ-GE15NA
MUZ-GE15NAH
MUY-GE15NA
MUZ-GE15NA2
MUZ-GE15NAH2
MUY-GE15NA2
SHF at rating condition = 0.80
Airflow
= 498 CFM
1.4
1.3
1.2
1.1
1.0
0.9
0.8
Indoor intake air WB temperature (°F)
71
67
63
65 75 85 95 105
Outdoor intake air DB temperature (°F)
115
MUZ-GE18NA
MUZ-GE18NAH
MUY-GE18NA
SHF at rating condition = 0.71
Airflow
= 498 CFM
2.0
1.9
1.8
1.7
1.6
1.5
1.4
1.3
Indoor intake air WB temperature (°F)
65 75 85 95 105
Outdoor intake air DB temperature (°F)
115
71
67
63
MUZ-GE24NA
MUY-GE24NA
SHF at rating condition = 0.75
Airflow
= 634 CFM
2.2
2.1
2.0
1.9
1.8
1.7
1.6
1.5
1.4
1.3
65
Indoor intake air WB temperature (°F)
75 85 95 105
Outdoor intake air DB temperature (°F)
115
71
67
63
OBH549G
30
Heating (MUZ)
Heating capacity
(at Rated frequency)
0.9
0.8
0.7
0.6
0.5
0.4
1.3
1.2
1.1
1.0
-4
Indoor intake air DB temperature ( F)
5 14 23 32 41
Outdoor intake air WB temperature (°F)
50
MUZ-GE09NA MUZ-GE09NA2
Airflow = 413 CFM
1.2
1.0
0.8
0.6
0.4
0.2
0
Indoor intake air DB temperature (°F)
10 20 30 40 50
Outdoor intake air WB temperature (°F)
60
MUZ-GE12NA MUZ-GE12NA2
70
75
70
65
1.4
1.2
1.0
0.8
0.6
0.4
0
Indoor intake air DB temperature (°F)
Airflow = 413 CFM
75
70
65
10 20 30 40 50
Outdoor intake air WB temperature (°F)
60
MUZ-GE15NA MUZ-GE15NA2
70
Airflow = 463 CFM
2.0
1.7
1.4
1.1
0.8
0.5
0
Indoor intake air DB temperature (°F)
10 20 30 40 50
Outdoor intake air WB temperature (°F)
60
75
70
65
70
59
68
79
59
MUZ-GE09NAH MUZ-GE09NAH2
Airflow = 413 CFM
1.2
1.0
0.8
0.6
0.4
0.2
0
Indoor intake air DB temperature (°F)
10 20 30 40 50
Outdoor intake air WB temperature (°F)
60
MUZ-GE12NAH MUZ-GE12NAH2
70
75
70
65
1.4
1.2
1.0
0.8
0.6
0.4
0
Indoor intake air DB temperature (°F)
Airflow = 413 CFM
75
70
65
10 20 30 40 50
Outdoor intake air WB temperature (°F)
60
MUZ-GE15NAH MUZ-GE15NAH2
70
Airflow = 463 CFM
2.0
1.7
1.4
1.1
0.8
0.5
0
Indoor intake air DB temperature (°F)
10 20 30 40 50
Outdoor intake air WB temperature (°F)
60
75
70
65
70
This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships between frequency and capacity.
OBH549G
31
MUZ-GE18NA MUZ-GE18NAH
2.2
2.0
1.8
1.6
1.4
1.2
1.0
0.8
0.6
0
Indoor intake air DB temperature (°F)
Airflow = 512 CFM
75
70
65
10 20 30 40 50
Outdoor intake air WB temperature (°F)
60
MUZ-GE24NA
70
2.2
2.0
1.8
1.6
1.4
1.2
1.0
0.8
0.6
0
Indoor intake air DB temperature (°F)
Airflow = 512 CFM
70
65
10 20 30 40 50
Outdoor intake air WB temperature (°F)
60
Airflow = 738 CFM
3.0
2.6
2.2
1.8
1.4
1.0
0
Indoor intake air DB temperature (°F)
75
70
65
10 20 30 40 50
Outdoor intake air WB temperature (°F)
60 70
This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships between frequency and capacity.
70
7-3. CONDENSING PRESSURE
Cooling
Data is based on the condition of indoor humidity 50 %.
Air flow should be set to High speed.
MUZ-GE09NA
MUZ-GE09NAH
MUY-GE09NA
MUZ-GE09NA2
MUZ-GE09NAH2
MUY-GE09NA2
(PSIG)
440
(PSIG)
200
86
Indoor DB temperature (°F)
400
360
180
160
80
75
70
320
Indoor DB temperature (°F)
280
6870 75 80 85 90 95 100 105
(°F)
Outdoor ambient temperature
140
120
68 70 75 80 85 90 95 100 105
(°F)
Outdoor ambient temperature
OBH549G
32
MUZ-GE12NA
MUZ-GE12NAH
MUY-GE12NA
MUZ-GE12NA2
MUZ-GE12NAH2
MUY-GE12NA2
(PSIG)
420
(PSIG)
190
380
340
170
150
Indoor DB temperature (°F)
86
80
75
70
300
Indoor DB temperature (°F)
260
6870 75 80 85 90
95
100 105
(°F)
Outdoor ambient temperature
MUZ-GE15NA
MUZ-GE15NAH
MUY-GE15NA
(PSIG)
440
MUZ-GE15NA2
MUZ-GE15NAH2
MUY-GE15NA2
400
86
80
75
70
130
110
6870 75 80 85 90
95
100 105
(°F)
Outdoor ambient temperature
(PSIG)
200
180
360
160
Indoor DB temperature (°F)
86
80
75
70
320
Indoor DB temperature (°F)
280
6870 75 80 85 90
95
100 105
(°F)
Outdoor ambient temperature
MUZ-GE18NA
MUZ-GE18NAH
MUY-GE18NA
(PSIG)
430
86
80
75
70
390
140
120
68 70 75 80 85 90 95 100 105(°F)
Outdoor ambient temperature
(PSIG)
160
145
86
80
75
70
350 130
Indoor DB temperature (°F)
310
270
6870 75 80 85 90 95 100 105(°F)
Outdoor ambient temperature
115
Indoor DB temperature (°F)
100
6870 75 80 85 90 95 100 105(°F)
Outdoor ambient temperature
OBH549G
33
MUZ-GE24NA
MUY-GE24NA
(PSIG)
480
450
420
390
360
Indoor DB temperature (°F)
86
80
75
70
330
300
270
6870 75 80 85 90
95
100 105
(°F)
Outdoor ambient temperature
(PSIG)
180
170
160
150
140
86
80
75
70
130
120
Indoor DB temperature (°F)
110
6870 75 80 85 90
95
100 105
(°F)
Outdoor ambient temperature
Heating (MUZ)
Data is based on the condition of outdoor humidity 75%.
Air flow should be set to High speed.
Data is for heating operation without any frost.
MUZ-GE09NA
MUZ-GE09NAH
(PSIG)
370
345
MUZ-GE09NA2
MUZ-GE09NAH2
75
70
65
(PSIG)
210
185
320
Indoor DB temperature (°F)
295
270
245
58Hz
220
5 15 25 35 45 55
Outdoor ambient temperature
65 75 (°F)
75
70
65
160
135
110
Indoor DB temperature (°F)
58Hz
85
60
5 15 25 35 45 55
Outdoor ambient temperature
65 75 (°F)
OBH549G
34
MUZ-GE12NA
MUZ-GE12NAH
(PSIG)
460
MUZ-GE12NA2
MUZ-GE12NAH2
420
380
340
300
Indoor DB temperature (°F)
58Hz
260
5 15 25 35 45 55
Outdoor ambient temperature
65 75 (°F)
MUZ-GE15NA
MUZ-GE15NAH
(PSIG)
440
MUZ-GE15NA2
MUZ-GE15NAH2
75
70
65
404
368
332
296
Indoor DB temperature (°F)
54Hz
260
5 15 25 35 45 55
Outdoor ambient temperature
65 75 (°F)
75
70
65
(PSIG)
210
185
75
70
65
160
135
Indoor DB temperature (°F)
110
85
58Hz
60
5 15 25 35 45 55
Outdoor ambient temperature
65 75 (°F)
(PSIG)
210
185
75
65
160
135
Indoor DB temperature (°F)
110
85
54Hz
60
5 15 25 35 45 55
Outdoor ambient temperature
65 75 (°F)
OBH549G
35
MUZ-GE18NA
MUZ-GE18NAH
(PSIG)
500
475
450
425
400
375
350
325
300
5
Indoor DB temperature (°F)
58Hz
75
70
65
15 25 35 45 55
Outdoor ambient temperature
65 75(°F)
MUZ-GE24NA
(PSIG)
450
425
400
375
350
325
300
275
250
5
Indoor DB temperature (°F)
58Hz
75
70
65
15 25 35 45 55
Outdoor ambient temperature
65 75 (°F)
(PSIG)
210
185
75
70
65
160
135
Indoor DB temperature (°F)
110
85
58Hz
60
5 15 25 35 45 55
Outdoor ambient temperature
65 75 (°F)
(PSIG)
210
190
170
150
130
110
90
70
50
5
Indoor DB temperature (°F)
58Hz
75
70
65
15 25 35 45 55
Outdoor ambient temperature
65 75 (°F)
OBH549G
36
7-4. STANDARD OPERATION DATA
Model
Item
Capacity
SHF
Input
Rated frequency
Indoor unit
Power supply (V, Phase, Hz)
Input
Fan motor current
Unit
Btu/h
kW
Hz kW
A
Outdoor unit
Power supply (V, phase, Hz)
Input
Comp. current
Fan motor current
Condensing pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Comp. shell bottom temp
Ref. pipe length
Refrigerant charge (R410A)
Intake air temperature
Discharge air temperature
Fan speed (High)
Air fl ow (High)
Intake air temperature
Fan speed
Air fl ow kW
A
A
PSIG
DB
WB °F
DB °F
WB °F rpm
°F ft.
-
°F
PSIG
°F
°F
°F
DB
CFM
°F
WB °F rpm
CFM
MSZ-GE09NA
MSY-GE09NA
Cooling
9,000
0.82
0.660
MSZ-GE09NA
Heating
10,900
—
0.760
MSZ-GE12NA
MSY-GE12NA
Cooling
12,000
0.74
0.960
MSZ-GE12NA
Heating
14,400
—
1.170
59.5
77.5
MSZ-GE09NA, MSY-GE09NA
0.022
69.0
77.0
MSZ-GE12NA, MSY-GE12NA
0.023
208/230, 1, 60
0.022
0.023
0.25/0.23
0.25/0.23
0.24/0.22
MUZ-GE09NA
MUZ-GE09NA2
MUZ-GE09NAH
MUZ-GE09NAH2
MUY-GE09NA
MUY-GE09NA2
MUZ-GE09NA
MUZ-GE09NA2
MUZ-GE09NAH
MUZ-GE09NAH2
0.24/0.22
MUZ-GE12NA
MUZ-GE12NA2
MUZ-GE12NAH
MUZ-GE12NAH2
MUY-GE12NA
MUY-GE12NA2
MUZ-GE12NA
MUZ-GE12NA2
MUZ-GE12NAH
MUZ-GE12NAH2
0.638
3.32/3.00
0.27/0.24
389
0.737
208/230, 1, 60
0.938
3.66/3.31
0.30/0.27
331
4.39/3.97
0.34/0.31
389
1.147
5.41/4.89
0.31/0.28
397
151
154
115
59
151
103
152
103
39
149
133
163
115
56
158
104
162
116
35
158
25
80
67
60
58
1,020
367 (Wet)
95
—
800
1151
1 lb. 12 oz.
70
60
97
—
1,040
413
47
43
850
1225
80
67
56
55
1,020
367 (Wet)
95
—
900
1229
2 lb. 9 oz.
70
60
108
—
1,040
413
47
43
860
1172
OBH549G
37
Model
Item
Capacity
SHF
Input
Rated frequency
Indoor unit
Power supply (V, Phase, Hz)
Input
Fan motor current
Outdoor unit
Power supply (V, phase, Hz)
Input
Comp. current
Fan motor current
Condensing pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Comp. shell bottom temp
Ref. pipe length
Refrigerant charge (R410A)
Intake air temperature
Discharge air temperature
Fan speed (High)
Air fl ow (High)
Intake air temperature
Fan speed
Air fl ow
DB
WB
DB
WB
DB
WB kW
A
A
PSIG
°F ft.
-
°F
PSIG
°F
°F
°F
CFM
°F
°F rpm
°F
°F
°F rpm
CFM
Unit
Btu/h
kW
Hz kW
A
MSZ-GE15NA
MSY-GE15NA
Cooling
14,000
0.80
1.080
MSZ-GE15NA
Heating
18,000
—
1.600
MSZ-GE18NA
MSY-GE18NA
Cooling
17,200
0.71
1.640
MSZ-GE18NA
Heating
21,600
—
1.900
55.5
74.0
MSZ-GE15NA, MSY-GE15NA
0.045
83.0
84.0
MSZ-GE18NA, MSY-GE18NA
0.031
208/230, 1, 60
0.043
0.037
0.35/0.32
0.43/0.39
0.40/0.36
0.50/0.45
MUZ-GE15NA, -
1
MUZ-GE15NA2
MUZ-GE15NAH
MUZ-GE15NAH2
MUY-GE15NA, -
1
MUY-GE15NA2
MUZ-GE15NA, -
MUZ-GE15NA2
MUZ-GE15NAH
MUZ-GE15NAH2
1
MUZ-GE18NA, -
MUZ-GE18NAH
MUY-GE18NA, -
1
1
MUZ-GE18NA, -
MUZ-GE18NAH
1
1,035
4.86/4.40
0.33/0.30
400
1,569
208/230, 1, 60
1,595
7.38/6.67
0.34/0.31
431
6.97/6.29
0.80/0.72
376
1,860
8.36/7.55
0.64/0.59
458
139
164
117
57
148
99
179
122
31
165
117
177
112
59
164
102
184
127
33
170
25
2 lb. 9 oz.
3 lb. 7 oz.
80
67
60
57
1,280
498 (Wet)
95
—
910
1,243
70
60
114
—
1,140
463
47
43
900
1,229
80
67
56
54
1,280
498 (Wet)
95
—
780
1,730
70
60
117
—
1,240
512
47
43
740
1,659
OBH549G
38
Model
Item
Capacity
SHF
Input
Rated frequency
Indoor unit
Power supply (V, Phase, Hz)
Input
Fan motor current
Outdoor unit kW
A
Power supply (V, phase, Hz)
Input
Comp. current
Fan motor current
Condensing pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Comp. shell bottom temp
Ref. pipe length
Refrigerant charge (R410A)
Intake air temperature
Discharge air temperature
Fan speed (High)
Air fl ow (High)
Intake air temperature
Fan speed
Air fl ow
DB
-
°F
WB °F
DB °F
°F
°F
°F ft.
kW
A
A
PSIG
PSIG
°F
WB °F rpm
DB
CFM
°F
WB °F rpm
CFM
Unit
Btu/h
kW
Hz
MSZ-GE24NA
MSY-GE24NA
Cooling
22,500
0.75
1.800
66.5
MSZ-GE24NA
Heating
27,600
—
2.340
82.0
MSZ-GE24NA, MSY-GE24NA
208/230, 1, 60
0.058
0.56/0.51
MUZ-GE24NA
MUY-GE24NA
MUZ-GE24NA
208/230, 1, 60
1.742
7.01/6.34
2.282
9.59/8.67
1.61/1.05
395
141
158
1.13/1.02
405
102
171
115
52
140
33
148
25
4 lb. 3 oz.
80
67
56
53
70
60
111
—
1,300
634 (Wet)
95
—
840
1,769
738
47
43
810
1,701
OBH549G
39
7-5. CAPACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY
MUZ-GE09NA
MUZ-GE09NAH
MUY-GE09NA
MUZ-GE09NA2
MUZ-GE09NAH2
MUY-GE09NA2
Correction of Cooling capacity
Correction of Cooling total input
1.5
2.0
2.0
MUZ-GE09NA
MUZ-GE09NAH
MUZ-GE09NA2
MUZ-GE09NAH2
Correction of Heating capacity
2.0
Correction of Heating total input
1.5
1.5
1.5
1.0
0.5
1.0
0.5
1.0
0.5
1.0
0.5
(Hz)
The operational frequency of compressor
0 50 100 150
(Hz)
The operational frequency of compressor
0 50 100 150 (Hz)
The operational frequency of compressor
0 50 100 150 (Hz)
The operational frequency of compressor
MUZ-GE12NA
MUZ-GE12NAH
MUY-GE12NA
MUZ-GE12NA2
MUZ-GE12NAH2
MUY-GE12NA2
Correction of Cooling capacity
Correction of Cooling total input
1.5
1.5
1.5
MUZ-GE12NA
MUZ-GE12NAH
MUZ-GE12NA2
MUZ-GE12NAH2
Correction of Heating capacity
1.5
Correction of Heating total input
1.0
0.5
1.0
0.5
1.0
0.5
1.0
0.5
1.0
0.5
(Hz)
The operational frequency of compressor
0 50 100 150 (Hz)
The operational frequency of compressor
0 50 100 150 (Hz)
The operational frequency of compressor
MUZ-GE15NA
MUZ-GE15NAH
MUY-GE15NA
2.0
MUZ-GE15NA2
MUZ-GE15NAH2
MUY-GE15NA2
Correction of Cooling capacity
2.0
Correction of Cooling total input
1.5
MUZ-GE15NA
MUZ-GE15NAH
0 50 100 150
(Hz)
The operational frequency of compressor
MUZ-GE15NA2
MUZ-GE15NAH2
Correction of Heating capacity
1.5
Correction of Heating total input
1.5
1.5
1.0
1.0
1.0
0.5
1.0
0.5
0.5
0.5
0 50 100 150 (Hz)
The operational frequency of compressor
0 50 100 150 (Hz)
The operational frequency of compressor
0 50 100 150
(Hz)
The operational frequency of compressor
0 50 100 150 (Hz)
The operational frequency of compressor
MUZ-GE18NA
MUZ-GE18NAH
MUY-GE18NA
Correction of Cooling capacity
1.5
1.5
Correction of Cooling total input
1.5
MUZ-GE18NA
MUZ-GE18NAH
Correction of Heating capacity
1.5
Correction of Heating total input
1.0
0.5
1.0
0.5
1.0
0.5
(Hz)
The operational frequency of compressor
0 50 100 150 (Hz)
The operational frequency of compressor
0 50 100 150 (Hz)
The operational frequency of compressor
0 50 100 150 (Hz)
The operational frequency of compressor
OBH549G
40
MUZ-GE24NA
MUY-GE24NA
Correction of Cooling capacity
1.5
1.0
0.5
1.5
1.0
0.5
2.5
Correction of Cooling total input
2.0
1.5
1.0
0.5
MUZ-GE24NA
Correction of Heating capacity
2.0
Correction of Heating total input
1.5
1.0
0.5
0 50 100 150(Hz)
The operational frequency of compressor
0 50 100 150(Hz)
The operational frequency of compressor
0 50 100 150(Hz)
The operational frequency of compressor
0 50 100 150(Hz)
The operational frequency of compressor
7-6. HOW TO OPERATE FIXED-FREQUENCY OPERATION (Test run operation)
1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor varies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on remote controller.
OBH549G
41
8
ACTUATOR CONTROL
MUZ-GE09NA2 MUZ-GE12NA2 MUZ-GE15NA2
MUZ-GE09NAH MUZ-GE12NAH MUZ-GE15NAH MUZ-GE18NAH
MUZ-GE09NAH2 MUZ-GE12NAH2 MUZ-GE15NAH2
MUY-GE09NA2 MUY-GE12NA2 MUY-GE15NA2
8-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
5 seconds 15 seconds
ON
Compressor
OFF
ON
Outdoor fan motor
OFF
8-2. R.V. COIL CONTROL (MUZ)
Heating . . . . . . . . . . . . . . . . . ON
Cooling . . . . . . . . . . . . . . . . . OFF
Dry . . . . . . . . . . . . . . . . . . . . OFF
NOTE
: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
<COOL> <HEAT>
5 seconds 5 seconds
Compressor
ON
OFF
R.V.coil
ON
OFF
Outdoor fan
ON motor
OFF
8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
Sensor
Discharge temperature thermistor
Indoor coil temperature thermistor
Defrost thermistor
(MUZ)
Fin temperature thermistor
Ambient temperature thermistor
Outdoor heat exchanger temperature thermistor
OBH549G
Protection
Purpose
Cooling: Coil frost prevention
Heating: High pressure protection
Heating: Defrosting
Protection
Cooling: Low ambient temperature operation
Cooling: Low ambient temperature operation
Cooling: High pressure protection
Compressor LEV
Outdoor fan motor
R.V.coil
(MUZ)
Indoor fan motor
○ ○
○
○ ○
○ ○ ○ ○ ○
○ ○
○ ○ ○
○ ○ ○
○ ○ ○
42
Actuator
9
SERVICE FUNCTIONS
MUZ-GE09NA2 MUZ-GE12NA2 MUZ-GE15NA2
MUZ-GE09NAH MUZ-GE12NAH MUZ-GE15NAH MUZ-GE18NAH
MUZ-GE09NAH2 MUZ-GE12NAH2 MUZ-GE15NAH2
MUY-GE09NA2 MUY-GE12NA2 MUY-GE15NA2
9-1. CHANGE IN DEFROST SETTING (MUZ)
Changing defrost finish temperature
<JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board. (Refer to 10-6.1.)
Jumper
MUZ-GE09
Defrost fi nish temperature
MUZ-GE12 MUZ-GE15 MUZ-GE18 MUZ-GE18/24
JS
Soldered
(Initial setting)
None
(Cut)
41°F (5°C)
46°F (8°C)
50°F (10°C)
55°F (13°C)
41°F (5°C)
50°F (10°C)
48°F (9°C)
64°F (18°C)
50°F (10°C)
64°F (18°C)
9-2. PRE-HEAT CONTROL SETTING
PRE-HEAT CONTROL
When moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low outside temperature.
The pre-heat control prevents this interference. The pre-heat control turns ON when the discharge temperature thermistor is 68°F (20°C) or below. When pre-heat control turns ON, compressor is energized. (About 50 W)
Pre-heat control setting
<JK> ON: To activate the pre-heat control, cut the JK wire of the inverter P.C. board. (Refer to 10-6.1.)
OFF: To deactivate the pre-heat control, solder JK wire of the inverter P.C. board. (Refer to 10-6.1.)
NOTE:
When the inverter P.C. board is replaced, check the Jumper wires, and cut/solder them if necessary.
OBH549G
43
10
TROUBLESHOOTING
MUZ-GE09NA2 MUZ-GE12NA2 MUZ-GE15NA2
MUZ-GE09NAH MUZ-GE12NAH MUZ-GE15NAH MUZ-GE18NAH
MUZ-GE09NAH2 MUZ-GE12NAH2 MUZ-GE15NAH2
MUY-GE09NA2 MUY-GE12NA2 MUY-GE15NA2
10-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, then after confirming the horizontal vane is closed, turn off the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
5) When connecting or disconnecting the connectors, hold the connector housing. DO NOT pull the lead wires.
<Incorrect> <Correct>
Lead wiring
Connector housing
3. Troubleshooting procedure
1) Check if the OPERATION INDICATOR lamp on the indoor unit is flashing ON and OFF to indicate an abnormality.
To make sure, check how many times the OPERATION INDICATOR lamp is flashing ON and OFF before starting service work.
2) Before servicing, check that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration.
4) Refer to 10-2. and 10-3.
OBH549G
44
10-2. FAILURE MODE RECALL FUNCTION
Outline of the function
This air conditioner can memorize the abnormal condition which has occurred once.
Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details can be recalled.
1. Flow chart of failure mode recall function for the indoor/outdoor unit
MSZ-GE06/09/12/15/18NA
MSZ-GE24NA
MSY-GE09/12/15/18NA
MSY-GE24NA
Operational procedure
The cause of abnormality cannot be found because the abnormality does not recur.
Setting up the failure mode recall function
Turn ON the power supply.
<Preparation of the remote controller>
While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button.
First, release RESET button.
Hold down the other two buttons for another 3 seconds. Make sure that the indicators on the LCD screen shown in the right fi gure are all displayed. Then release the buttons.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1
Does the upper lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds?
Blinks: Either indoor or outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of the upper lamp of OPERATION INDICATOR lamp. 2
Judgment of indoor/outdoor abnormality
Yes
(Blinks)
Before blinking, does the upper lamp of OPERATION INDICA-
TOR lamp stay ON for 3 seconds?
When it stays ON for 3 seconds (without beep):
The outdoor unit is abnormal.
No
No
(OFF)
Yes
The indoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring to indoor unit failure mode table. (Refer to indoor unit service manual.)
Make sure to check at least two consecutive blinking cycles. 2
1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
Indoor unit is normal.
But the outdoor unit might be abnormal because there are some abnormalities that cannot be recalled with this way.
Check if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function. (Refer to 10-2.2)
The outdoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring to outdoor unit failure mode table. (Refer to 10-2.3)
Make sure to check at least two consecutive blinking cycles. 3
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
Repair the failure parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above.
NOTE:
1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
2. Blinking pattern when the indoor unit is abnormal:
2.5-second OFF
Blinking at 0.5second interval 2.5-second OFF
Blinking at 0.5second interval
ON
OFF
Beeps
Repeated cycle
Beeps
Repeated cycle
Beeps
Repeated cycle
3.Blinking pattern when the outdoor unit is abnormal:
Blinking at 0.5-
2.5-second OFF 3-second ON second interval
ON
OFF
No beep
Repeated cycle
Beeps
OBH549G
2.5-second OFF
45
3-second ON
No beep
Repeated cycle
Blinking at 0.5second interval
Beeps
Repeated cycle
2. Flow chart of the detailed outdoor unit failure mode recall function
Operational procedure
The outdoor unit might be abnormal.
Check if outdoor unit is abnormal according to the following procedures.
Make sure that the remote controller is set to the failure mode recall function.
With the remote controller headed towards the indoor unit, press TOO
COOL or TOO WARM button to adjust the set temperature to 77°F (25°C).
1
Does the upper lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds?
Blinks: The outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of the upper lamp of OPERATION INDICATOR lamp. 2
Yes
(Blinks
)
No
(OFF)
The outdoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring to outdoor unit failure mode table (10-2.3.).
Make sure to check at least two consecutive blinking cycles. 2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
1. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received.
The outdoor unit is normal.
Release the failure mode recall function according to the left mentioned procedure.
Repair the failure parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" (10-2.1.).
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above.
NOTE
: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
2.Blinking pattern when outdoor unit is abnormal:
2.5-second OFF 3-second ON
ON
OFF
No beep
Repeated cycle
Blinking at 0.5second interval
Beeps
2.5-second OFF 3-second ON
No beep
Repeated cycle
Blinking at 0.5second interval
Beeps
Repeated cycle
OBH549G
46
3. Outdoor unit failure mode table
OPERATION
INDICATOR upper lamp
(Indoor unit)
Abnormal point
(Failure mode / protection)
LED indication
(Outdoor P.C. board)
2-time
2.5 seconds
OFF
3-time
OFF fl fl
ash
ash
2.5 seconds
Outdoor power system
Discharge temperature thermistor
Defrost thermistor
(MUZ)
Fin temperature thermistor
1-time fl
—
—
ash every
2.5 seconds
—
Overcurrent protection cut-out operates
3 consecutive times within 1 minute after the compressor gets started.
Thermistor shorts or opens during compressor running.
—
• Reconnect connectors.
• Refer to 10-5. "How to check inverter/ compressor".
• Check stop valve.
• Refer to 10-5. "Check of outdoor thermistors".
Defective outdoor thermistors can be identi fi ed by checking the blinking pattern of
LED. P.C. board temperature thermistor
Ambient temperature thermistor
Outdoor heat exchanger temperature thermistor
(MUZ-GE24, MUY-GE24)
3-time fl ash
2.5 seconds OFF
4-time
2-time fl
2.5 seconds OFF fl
ash
ash
2.5 seconds OFF
4-time
5-time
6-time
7-time
8-time
9-time fl ash
2.5 seconds
OFF fl ash
2.5 seconds
OFF fl ash
2.5 seconds
OFF fl ash
2.5 seconds
OFF fl ash
2.5 seconds
OFF fl ash
2.5 seconds
OFF
10-time fl ash
2.5 seconds
OFF
Compressor synchronous abnormality (Compressor startup failure protection)
Discharge temperature
High pressure
Fin temperature/ P.C. board temperature
Outdoor fan motor
Nonvolatile memory data
Power module
(MUZ-GE24, MUY-GE24)
Discharge temperature
2.5 seconds OFF
12-time fl fl
ash
ash
2.5 seconds OFF
7-time
2.5 seconds OFF
5-time fl fl
—
—
ash
—
ash
2.5 seconds OFF
6-time fl ash
2.5 seconds OFF
—
Large current fl ows into intelligent power module/ power module 1.
Waveform of compressor current is distorted.
Temperature of discharge temperature thermistor exceeds 241°F (116°C), compressor stops.
Compressor can restart if discharge temperature thermistor reads 212°F
(100°C) or less 3 minutes later.
Temperature of indoor coil thermistor exceeds 158°F (70°C) in HEAT mode
(MUZ only).
Temperature of outdoor heat exchanger temperature thermistor exceeds 158°F (70°C) in COOL mode.
Temperature of fi n temperature thermistor on the inverter P.C. board exceeds 167 ~ 176°F (75 ~ 80°C), or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 158 ~ 167°F (70 ~ 75°C).
Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up.
Nonvolatile memory data cannot be read properly.
The interphase short circuit occurs in the output of the intelligent power module (IPM)/power module (IPM) 1.
The compressor winding shorts circuit.
Temperature of discharge temperature thermistor has been 122°F (50°C) or less for 20 minutes.
• Reconnect compressor connector.
• Refer to 10-5. "How to check inverter/ compressor".
• Check stop valve.
• Reconnect compressor connector.
• Refer to 10-5. "How to check inverter/ compressor".
• Check refrigerant circuit and refrigerant amount.
• Refer to 10-5. "Check of LEV".
• Check refrigerant circuit and refrigerant amount.
• Check stop valve.
• Check around outdoor unit.
• Check outdoor unit air passage.
• Refer to 10-5. "Check of outdoor fan motor".
• Refer to 10-5. "Check of outdoor fan motor".
Refer to 10-5. "Check of inverter P.C. board".
• Replace the inverter
P.C. board.
• Refer to 10-5. "How to check inverter/ compressor".
• Refer to 10-5. "Check of LEV".
• Check refrigerant circuit and refrigerant amount.
Indoor/
Outdoor unit failure mode failure mode recall function recall function
— —
○
○
—
—
—
—
—
—
○
—
○
○
○
○
○
○
○
○
○
○
NOTE
: Blinking patterns of this mode differ from the ones of Troubleshooting check table (10-3.).
1
Intelligent power module:
MUZ-GE09/12/15/18/24NA
,
MUY-GE09/12/15/18/24NA
Power module:
Other models
OBH549G
47
3. Outdoor unit failure mode table
OPERATION
INDICATOR upper lamp
(Indoor unit)
11-time fl ash
2.5 seconds
OFF
Abnormal point
(Failure mode / protection)
DC voltage
12-time
OFF fl ash
2.5 seconds
Each phase current of compressor
Overcurrent Compressor openphase
LED indication
(Outdoor P.C. board)
8-time fl ash
2.5 seconds OFF
9-time fl ash
2.5 seconds OFF
10-time fl ash
2.5 seconds OFF
DC voltage of inverter cannot be detected normally.
Each phase current of compressor cannot be detected normally.
Large current fl ows into intelligent power module (IPM)/power module
(IPM) 1.
The open-phase operation of compressor is detected.
The interphase short circuit occurs in the output of the intelligent power module (IPM)/power module (IPM) 1.
The compressor winding shorts circuit.
14-time fl ash
2.5 seconds
OFF
Stop valve (Closed valve) 14-time fl ash
2.5 seconds OFF
• Refer to 10-5. "How to check inverter/ compressor".
• Reconnect compressor connector.
• Refer to 10-5. "How to check inverter/ compressor".
Closed valve is detected by compressor current.
• Check stop valve
Indoor/
Outdoor unit failure mode failure mode recall function recall function
—
—
○
○
4-way valve/
Pipe temperature
16-time fl ash
2.5 seconds OFF
The 4-way valve does not work properly.
The indoor coil thermistor detects an abnormal temperature.
• Check the 4-way valve.
• Replace the inverter
P.C. board.
○ ○
NOTE
: Blinking patterns of this mode differ from the ones of Troubleshooting check table (10-3.).
1
Intelligent power module:
MUZ-GE09/12/15/18/24NA
,
MUY-GE09/12/15/18/24NA
Power module:
Other models
OBH549G
48
10-3. TROUBLESHOOTING CHECK TABLE
No. Symptom LED indication
1
Outdoor unit does not operate.
1-time fl ash every
2.5 seconds
Abnormal point/
Condition
Outdoor power system
2
3
Condition Remedy
Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started, or failure of restart of compressor has repeated 24 times.
Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor, defrost thermistor, outdoor heat exchanger temperature thermistor,
P.C. board temperature thermistor or ambient temperature thermistor shorts or opens during compressor running.
Outdoor control system
Nonvolatile memory data cannot be read properly.
(The upper lamp of OPERATION INDICATOR of the indoor unit lights up or fl ashes 7 times.)
• Reconnect connector of compressor.
• Refer to 10-5. "How to check inverter/ compressor".
• Check stop valve.
• Refer to 10-5. "Check of outdoor thermistors".
• Replace inverter P.C. board.
4
5
6
6-time fl ash
2.5 seconds OFF
11-time fl ash
2.5 seconds OFF
14-time fl ash
2.5 seconds OFF
Serial signal
Stop valve/
Closed valve
Outdoor unit
(Other abnormality)
The communication fails between the indoor and outdoor unit for
3 minutes.
Closed valve is detected by compressor current.
Outdoor unit is defective.
• Refer to 10-5. "How to check miswiring and serial signal error.
• Check stop valve.
• Refer to 10-2.2. "Flow chart of the detailed outdoor unit failure mode recall function".
7
16-time fl ash
2.5 seconds OFF
4-way valve/
Pipe temperature
The 4-way valve does not work properly.
The indoor coil thermistor detects an abnormal temperature.
• Refer to 10-5. "Check of R.V. coil".
• Replace the inverter P.C. board.
8
9
10
11
12
13
14
15
16
17
18
'Outdoor unit stops and restarts 3 minutes later' is repeated.
2-time fl ash
2.5 seconds OFF
Overcurrent protection
Outdoor unit operates.
Large current
1.
fl ows into intelligent power module/power module
When overcurrent protection occurs within 10 seconds after compressor starts, compressor restarts after 15 seconds
(MUZ-GE09/12/15/18, MUY-GE09/12/15/18)
.
• Reconnect connector of compressor.
• Refer to 10-5. "How to check inverter/ compressor".
• Check stop valve.
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
5-time fl ash
2.5 seconds OFF
8-time fl ash
2.5 seconds OFF
Discharge temperature overheat protection
Fin temperature /P.C. board temperature thermistor overheat protection
Temperature of fi n temperature thermistor on the heat sink exceeds 167 ~ 176°F (75 ~ 80°C) or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 158 ~ 167°F
(70 ~ 75°C).
High pressure protection
Temperature of discharge temperature thermistor exceeds 241°F
(116°C), compressor stops. Compressor can restart if discharge temperature thermistor reads 212°F (100°C) or less 3 minutes later.
Temperature of indoor coil thermistor exceeds 158°F (70°C) in
HEAT mode
(MUZ only)
. Temperature of outdoor heat exchanger temperature thermistor exceeds 158°F (70°C) in COOL mode.
• Check refrigerant circuit and refrigerant amount.
• Refer to 10-5. "Check of LEV".
• Check around outdoor unit.
• Check outdoor unit air passage.
• Refer to 10-5. "Check of outdoor fan motor".
• Check refrigerant circuit and refrigerant amount.
• Check stop valve.
Compressor synchronous abnormality
The waveform of compressor current is distorted.
• Reconnect connector of compressor.
• Refer to 10-5. "How to check inverter/ compressor".
10-time fl ash
2.5 seconds OFF
12-time
2.5 seconds OFF
13-time
2.5 seconds OFF
1-time
2.5 seconds OFF
3-time
2.5 seconds OFF
4-time fl fl fl fl fl
ash
ash
ash
ash
ash
2.5 seconds OFF
Outdoor fan motor
Each phase current of compressor
DC voltage
Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up.
• Refer to 10-5. "Check of outdoor fan motor.
• Refer to 10-5. "Check of inverter P.C. board.
Each phase current of compressor cannot be detected normally. • Refer to 10-5. "How to check inverter/ compressor".
DC voltage of inverter cannot be detected normally.
• Refer to 10-5. "How to check inverter/ compressor".
Frequency drop by current protection
Frequency drop by high pressure protection
Frequency drop by defrosting in COOL mode
Current from power outlet is nearing Max. fuse size.
Temperature of indoor coil thermistor exceeds 131°F (55°C) in
HEAT mode, compressor frequency lowers.
Indoor coil thermistor reads 46°F (8°C) or less in COOL mode, compressor frequency lowers.
The unit is normal, but check the following.
• Check if indoor fi lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short cycled.
Frequency drop by discharge temperature protection
Temperature of discharge temperature thermistor exceeds 232°F
(111°C), compressor frequency lowers.
• Check refrigerant circuit and refrigerant amount.
• Refer to 10-5. "Check of LEV".
• Refer to 10-5. "Check of outdoor thermistors".
NOTE
: 1. The location of LED is illustrated at the right fi gure. Refer to 10-6.1.
2. LED is lighted during normal operation. fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF. Flashing
(Example) When the fl ashing frequency is “2”.
Inverter
P.C. board
(Parts side)
LED
MUZ-GE24NA
MUY-GE24NA
0.5-second ON
0.5-second ON
ON
OFF
2.5-second OFF
2.5-second OFF
1
Intelligent power module:
MUZ-GE09/12/15/18/24NA
,
MUY-GE09/12/15/18/24NA
Power module:
Other models
Flashing →
LED
MUZ-GE09/12/15
NA/NA2/NAH/
NAH2
MUY-GE09/12/15
NA/NA2
MUZ-18NA/NAH
MUY-18NA
OBH549G
49
10-3. TROUBLESHOOTING CHECK TABLE
No. Symptom LED indication
19
Outdoor unit operates.
7-time fl ash
2.5 seconds OFF
Abnormal point/
Condition
Low discharge temperature protection
20
21
8-time fl ash
2.5 seconds OFF
PAM protection PAM:
Pulse Amplitude
Modulation
The overcurrent fl ows into IGBT (Insulated Gate Bipolar transistor: TR821) or the bus-bar voltage reaches 320 V or more, PAM stops and restarts.
9-time fl ash
2.5 seconds OFF
Zero cross detecting circuit
Condition Remedy
Temperature of discharge temperature thermistor has been
122°F (50°C) or less for 20 minutes.
Zero cross signal for PAM control cannot be detected.
Inverter check mode The connector of compressor is disconnected, inverter check mode starts.
• Refer to 10-5. "Check of LEV".
• Check refrigerant circuit and refrigerant amount.
This is not malfunction. PAM protection will be activated in the following cases:
1 Instantaneous power voltage drop
(Short time power failure)
2 When the power supply voltage is high.
• Check if the connector of the compressor is correctly connected. Refer to
10-5. "How to check inverter/compressor".
NOTE
: 1. The location of LED is illustrated at the right fi gure. Refer to 10-6.1.
2. LED is lighted during normal operation. fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF. Flashing
(Example) When the fl ashing frequency is “2”.
0.5-second ON
0.5-second ON
Inverter
P.C. board
(Parts side)
LED
MUZ-GE24NA
MUY-GE24NA
ON
OFF
2.5-second OFF
2.5-second OFF
Flashing →
LED
MUZ-GE09/12/15
NA/NA2/NAH/
NAH2
MUY-GE09/12/15
NA/NA2
MUZ-18NA/NAH
MUY-18NA
10-4. TROUBLE CRITERION OF MAIN PARTS
MUZ-GE24NA
MUZ-GE09NA2 MUZ-GE12NA2 MUZ-GE15NA2
MUZ-GE09NAH MUZ-GE12NAH MUZ-GE15NAH MUZ-GE18NAH
MUZ-GE09NAH2 MUZ-GE12NAH2 MUZ-GE15NAH2
MUY-GE24NA
MUY-GE09NA2 MUY-GE12NA2 MUY-GE15NA2
Figure Part name Check method and criterion
Defrost thermistor (RT61)
(MUZ)
Fin temperature thermistor (RT64)
Measure the resistance with a tester.
Ambient temperature thermistor (RT65)
Refer to 10-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, for the chart of thermistor.
Outdoor heat exchanger temperature thermistor
(RT68)
Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up.
Discharge temperature thermistor (RT62)
Refer to 10-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, for the chart of thermistor.
Compressor
Measure the resistance between terminals using a tester.
(Temperature: -4 ~ 104°F (-20 ~ 40°C))
GE09
Normal ( Ω )
GE12 GE15/18
U-V
U-W
V-W
1.36 ~ 1.93
1.52 ~ 2.17
0.78 ~ 1.11
GE24
0.83 ~ 1.18
WHT
V
RED BLK
W
U
OBH549G
50
Part name
Outdoor fan motor
R. V. coil (21S4)
(MUZ)
Expansion valve coil
(LEV)
Defrost heater
MUZ-GE•NAH
Check method and criterion
Measure the resistance between lead wires using a tester.
(Temperature: -4 ~ 104°F (-20 ~ 40°C))
Color of lead wire
GE09/12
Normal ( Ω )
GE15 GE18/24
RED – BLK
BLK – WHT
WHT – RED
28 ~ 40 11 ~ 16
Measure the resistance using a tester.
(Temperature: 14 ~ 104°F (-10 ~ 40°C))
Normal (k Ω )
0.97 ~ 1.38
Measure the resistance using a tester.
(Temperature: 14 ~ 104°F (-10 ~ 40°C))
MUZ-GE09/12/15/18NA
MUZ-GE09/12/15NA2
MUZ-GE09/12/15/18NAH
MUZ-GE09/12/15NAH2
MUY-GE09/12/15/18NA
MUY-GE09/12/15NA2
Normal ( Ω ) Color of lead wire
WHT – RED
RED – ORN
YLW – BRN
BRN – BLU
37 ~ 54
Measure the resistance using a tester.
(Temperature: 14 ~ 104°F (-10 ~ 40°C))
MUZ-GE24NA, MUY-GE24NA
Normal ( Ω ) Color of lead wire
RED – ORN
RED – WHT
RED – BLU
RED – YLW
37 ~ 54
Measure the resistance using a tester.
(Temperature: 14 ~ 104°F (-10 ~ 40°C))
Normal ( Ω )
349 ~ 428
Figure
WHT
RED BLK
W
V
U
WHT
RED
ORN
LEV
WHT
ORN
RED
(+12V)
LEV
OBH549G
51
10-5. TROUBLESHOOTING FLOW
A How to check inverter/compressor
Disconnect the connector between compressor and the intelligent power module (IPM)/power module (IPM) 1.
Check the voltage between terminals.
See 10-5. “Check of open phase”.
Are the voltages balanced?
Yes
Check the compressor.
No
Replace the inverter P.C. board.
See 10-5. “Check of compressor”.
B Check of open phase
● With the connector between the compressor and intelligent power module/power module 1 disconnected, activate the inverter and check if the inverter is normal by measuring the voltage balance between the terminals.
Output voltage is 50 - 130 V. (The voltage may differ according to the tester.)
<< Operation method>>
Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERA-
TION: Refer to 7-6.)
<<Measurement point>>
at 3 points
BLK (U) - WHT (V)
BLK (U) - RED (W)
WHT(V) - RED (W)
Measure AC voltage between the lead wires at 3 points.
NOTE
: 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of the inverter P.C. board fl ashes 9 times. (Refer to 10-6.1.)
C Check of compressor
Refer to 10-5. “Check of compressor winding”.
Is the compressor normal?
Yes
No
Replace the compressor.
Refer to 10-5. “Check of compressor operation time”.
Does the compressor operate continuously?
Yes
OK
No
Refer to 10-5. “Check of compressor start failure”.
1
Intelligent power module:
MUZ-GE09/12/15/18/24NA
,
MUY-GE09/12/15/18/24NA
Power module:
Other models
OBH549G
52
D Check of compressor winding
● Disconnect the connector between the compressor and intelligent power module/power module 1, and measure the resistance between the compressor terminals.
<<Measurement point>>
At 3 points
BLK - WHT
BLK - RED
WHT - RED
<<Judgement>>
Measure the resistance between the lead wires at 3 points.
1
Refer to 10-4.
0[ Ω ] ················· Abnormal [short]
Intelligent power module:
Power module:
Infinite [ Ω ] ········ Abnormal [open]
NOTE
: Be sure to zero the ohmmeter before measurement.
MUZ-GE09/12/15/18/24NA
Other models
,
MUY-GE09/12/15/18/24NA
E Check of compressor operation time
● Connect the compressor and activate the inverter. Then measure the time until the inverter stops due to over current.
<<Operation method>>
Start heating or cooling operation by pressing EMERGENCY
OPERATION switch on the indoor unit.
(TEST RUN OPERATION: Refer to 7-6.)
<<Measurement>>
Measure the time from the start of compressor to the stop of compressor due to overcurrent.
<<Judgement>>
0 second
1 second
2 seconds
10 seconds
Compressor starts
Abnormal
(IPM failure)
(Compressor winding short)
Abnormal
(Compressor lock out)
(Starting defect)
Abnormal
(Poor contact,)
(Inverter P.C. board defect)
(Disconnected connector)
Abnormal
(Refrigerant circuit defect)
(Closed valve)
Normal
10 minutes
F Check of compressor start failure
Con fi rm that 1~4 is normal.
• Electrical circuit check
1. Contact of the compressor connector
2. Output voltage of inverter P.C. board and balance of them (See 10-5. )
3. Direct current voltage between DB61(+) and (-) (
MUZ-GE09/12/1518,
MUY-GE09/12/1518)
/ JP715(+) and JP30(-) (
MUZ-GE24, MUY-GE24)
on the inverter P.C. board
4. Voltage between outdoor terminal block S1-S2
Does the compressor run for 10 seconds or more after it starts?
No
Yes
After the compressor is heated with a drier, does the compressor start? 1
Yes
Compressor start failure. Activate pre-heat control.
(Refer to 9-2. "PRE-HEAT CONTROL SETTING")
No
Check the refrigerant circuit.
Check the stop valve.
Replace the compressor.
1
Heat the compressor with a drier for about 20 minutes.
Do not recover refrigerant gas while heating.
Heating part
OBH549G
53
G Check of outdoor thermistors
Disconnect the connector of thermistor in the inverter P.C. board (see below table), and measure the resistance of thermistor.
Is the resistance of thermistor normal? (Refer to 10-6.1.)
Yes
No
Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P.C. board.
Reconnect the connector of thermistor.
Turn ON the power supply and press EMERGENCY OPERATION switch.
Does the unit operate for 10 minutes or more without showing thermistor abnormality?
Yes
OK (Cause is poor contact.)
No
Replace the inverter P.C. board.
MUZ-GE09/12/15NA/NA2/NAH/NAH2, MUZ-GE18NA/NAH, MUY-GE09/12/15NA/NA2, MUY-GE18NA
Thermistor
Defrost
(MUZ)
Discharge temperature
Symbol Connector, Pin No.
RT61 Between CN641 pin1 and pin2
RT62 Between CN641 pin3 and pin4
Fin temperature
Ambient temperature
RT64
RT65
Between CN642 pin1 and pin2
Between CN643 pin1 and pin2
Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3
Board
Inverter P.C. board
MUZ-GE24NA, MUY-GE24NA
Thermistor
Defrost
(MUZ)
Discharge temperature
Symbol Connector, Pin No.
RT61 Between CN671 pin1 and pin2
RT62 Between CN671 pin3 and pin4
Fin temperature
Ambient temperature
RT64
RT65
Between CN673 pin1 and pin2
Between CN672 pin1 and pin2
Outdoor heat exchanger temperature RT68 Between CN671 pin5 and pin6
Board
Inverter P.C. board
H Check of R.V. coil
MUZ-GE09/12/15NA/NA2/NAH/NAH2, MUZ-GE18NA/NAH, MUZ-GE24NA
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 10-4.
In case CN721 (
MUZ-GE09/12/15/18
)/CN602 (
MUZ-GE24
) is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector although no signal is being transmitted to R.V. coil. Check if CN721 (
MUZ-
GE09/12/15/18
)/CN602 (
MUZ-GE24
) is connected.
Unit operates COOL mode even if it is set to HEAT mode.
Disconnect connector between the compressor and intelligent power module/ power module 1.
Turn ON the power supply and press
EMERGENCY OPERATION switch twice
(HEAT mode).
Is there 208/230 VAC between CN721 (
MUZ-
GE09/12/15/18
)/CN602 (
MUZ-GE24
) and on the inverter P.C. board 3 minutes after the power supply is turned ON?
Yes
Replace the 4-way valve.
No
Replace the inverter
P.C. board.
1
Intelligent power module:
MUZ-GE09/12/15/18/24NA
,
MUY-GE09/12/15/18/24NA
Power module:
Other models
OBH549G
54
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector between the compressor and intelligent power module/ power module 1.
Turn ON the power supply and press
EMERGENCY OPERATION switch once (COOL mode).
Is there 230 VAC between CN721 (
MUZ-
GE09/12/15/18
)/CN602 (
MUZ-GE24
) and
on the inverter P.C. board 3 minutes after the power supply is turned ON?
No
Yes
Replace the inverter
P.C. board.
Replace the 4-way valve.
1
Intelligent power module:
MUZ-GE09/12/15/18/24NA
,
MUY-GE09/12/15/18/24NA
Power module:
Other models
I Check of outdoor fan motor
Disconnect the connectors CN931 and CN932 from the inverter P.C. board.Check the connection between the connector CN931 and CN932.
Is the resistance between each terminal of outdoor fan motor normal?
(Refer to 10-4.)
No
Yes
Disconnect CN932 from the inverter P.C. board, and turn on the power supply.
Rotate the outdoor fan motor manually and measure the voltage of CN931.
Between 1(+) and 5(-)
Between 2(+) and 5(-)
Between 3(+) and 5(-)
(Fixed to either 5 or 0 VDC)
No
Replace the outdoor fan motor.
No
Does the voltage between each terminal become 5 and 0
VDC repeatedly?
Yes
Does the outdoor fan motor rotate smoothly?
Yes
Replace the inverter P.C. board.
OBH549G
55
J Check of power supply
MUZ-GE09/12/15NA/NA2/NAH/NAH2 MUZ-GE18NA/NAH
MUY-GE09/12/15NA/NA2 MUY-GE18NA
1
Intelligent power module:
MUZ-GE09/12/15/18/24NA
,
MUY-GE09/12/15/18/24NA
Power module:
Other models
Disconnect the connector (CN61) between compressor and intelligent power module/ power module 1.
Turn ON power supply and press
EMERGENCY OPERATION switch.
Does The upper lamp of
OPERATION INDICATOR lamp on the indoor unit light up?
Yes
No
Is there bus-bar voltage 260-325
VDC between DB61 (+) and DB61 (–) on the inverter P.C. board?
(Refer to 10-6.1.)
No
Yes
Check the electric parts in main circuit.
Rectify indoor/outdoor connecting wire.
Yes
Is there voltage 208/230 VAC between the indoor terminal block S1 and S2?
Does LED on the inverter P.C. board light up or fl ash? (Refer to 10-6.1.)
Yes
No
Replace the inverter
P.C. board.
If LED lights up, it is OK.
If LED fl ashes, refer to 10-3.
No
Replace the indoor electronic control P.C. board.
260-325 VDC
DB61
MUZ-GE24NA
MUY-GE24NA
Inverter P.C. board
(Solder side) Disconnect the connector between compressor and intelligent power module/ power module 1.
Turn ON power supply and press
EMERGENCY OPERATION switch.
Does the upper lamp of
OPERATION INDICATOR on the indoor unit light up?
Yes
No
Is there bus-bar voltage 294 - 370
VDC between JP715 (+) and JP30 (–) on the inverter P.C. board?
(Refer to 10-6.1.)
No
Yes
Rectify indoor/outdoor connecting wire.
Yes
Is there voltage 208/230 VAC between the indoor terminal block S1 and S2?
No
Replace the indoor electronic control P.C. board.
Does LED on the inverter P.C. board light up or fl ash? (Refer to 10-6.1.)
Yes
No
Replace the inverter
P.C. board.
Check the electric parts in main circuit.
If LED lights up, it is OK.
If LED fl ashes, refer to 10-3.
JP30 JP715
OBH549G
294 -370 VDC
56
K Check of LEV (Expansion valve)
Turn ON the power supply.
<Preparation of the remote controller>
While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button.
First, release RESET button.
Hold down the other two buttons for another 3 seconds. Make sure that the indicators on the LCD screen shown in the right fi gure are all displayed.
Then release the buttons.
MSZ-GE06/09/12/15/18NA
MSY-GE09/12/15/18NA
MSZ-GE24NA
MSY-GE24NA
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1
Expansion valve operates in full-opening direction.
1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
Do you hear the expansion valve "click, click·······"?
Do you feel the expansion valve vibrate on touching it ?
No
Is LEV coil properly fi xed to the expansion valve?
Yes
No
Yes
Properly fi
OK
x the LEV coil to the expansion valve.
Does the resistance of LEV coil have the characteristics?
(Refer to 10-4.)
No
Replace the LEV coil.
Yes
Measure each voltage between connector pins of CN724 on the inverter P.C. board.
1. Pin (-) — Pin (+)
2. Pin (-) — Pin (+)
3. Pin (-) — Pin (+)
4. Pin (-) — Pin (+)
Is there about 3 ~ 5 VAC between each?
NOTE
: Measure the voltage by an analog tester.
Yes
Replace the expansion valve.
No
Replace the inverter P.C. board.
NOTE
: After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn ON it again.
2. Press RESET button on the remote controller.
OBH549G
57
L Check of inverter P.C. board
Check the outdoor fan motor.
(Refer to 10-5. .)
Is the fuse (F901) blown on the inverter P.C. board?
No
Yes
Check the connection of the connectors
(CN931 , CN932) of the outdoor fan motor.
If the connection is poor, make it correct.
Only for
MUZ-GE24NA MUY-GE24NA
Operate the outdoor unit by starting
EMERGENCY OPERATION.
Check the LED indication on the inverter P.C. board.
Does the LED fl ash 10 times?
Yes
(10-time fl ash)
No
Check the remedy following LED indication.
(Refer to 10-3.)
Replace the inverter P.C. board.
OBH549G
58
M How to check miswiring and serial signal error
Turn OFF the power supply.
Is there rated voltage in the power supply?
Yes
Turn ON the power supply.
No
Check the power supply.
Is there rated voltage between outdoor terminal block S1 and S2?
Yes
Press EMERGENCY OPERATION switch once.
No
Check the wiring.
Does the OPERATION INDICATOR lamp light up? <Con fi rmation of the power to the indoor unit>
Yes
Is serial signal error indicated 6 minutes later?
Yes
No
No
Is there any miswiring, poor contact, or wire disconnection of the indoor/outdoor connecting wire?
No
Yes
Correct them.
A
B
Turn OFF the power supply.
Check once more if the indoor/outdoor connecting wire is not miswiring.
Bridge the outdoor terminal block S2 and
S3. 1
1. Miswiring may damage indoor electronic control P.C. board during the operation.
Be sure to con fi rm the wiring is correct before the operation starts.
3. Be sure to check this within 3 minutes after turning ON.
After 3 minutes, LED blinks 6 times. Even when the inverter P.C. board or the outdoor electronic control P.C. board is normal, LED blinks 6 times after 3 minutes.
Turn ON the power supply.
Is the bus-bar voltage of the inverter P.C. board normal? (Refer to "TEST POINT DIAGRAM AND
VOLTAGE" in this manual.)
Yes
Does the LED on the inverter P.C. board repeat "3.6-second-OFF and 0.8-second-ON quick blinking"? 3
Yes
Turn OFF the power supply.
Remove the bridge between outdoor terminal block S2 and S3.
No
(Lighted or not lighted)
No
Check of power supply.
(Refer to 10-5. .)
Replace the inverter P.C. board . 2
2. Be careful of the residual voltage of smoothing capacitor.
Replace the indoor electronic control P.C. board.
A
• Turn OFF inverter-controlled lighting equipment.
• Turn OFF the power supply and then turn ON again.
• Press EMERGENCY OPERATION switch.
Is serial signal error indicated 6 minutes later?
Yes
No
B
• Reinstall either the unit or the light away from each other.
• Attach a fi lter on remote control receiving section of the indoor unit.
OBH549G
59
N Electromagnetic noise enters into TV sets or radios
Is the unit grounded?
Yes
No
Ground the unit.
Is the distance between the antennas and the indoor unit within 9.91 ft., or is the distance between the antennas and the outdoor unit within 9.91 ft.?
No
Yes
Is the distance between the TV sets or radios and the indoor unit within 3.28 ft., or is the distance between the TV sets or radios and the outdoor unit within 9.91 ft.?
No
Yes
Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.
Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Are the antennas damaged?
Is the coaxial cable damaged?
Is there any poor contact in the antenna wiring?
No
Yes
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?
No
Yes
Replace or repair the antenna.
Replace or repair the coaxial cable.
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas.
Even if all of the above conditions are ful fi lled, the electromagnetic noise may enter, depending on the electric fi eld strength or the installation condition (combination of speci fi c conditions such as antennas or wiring).
Check the followings before asking for service.
1. Devices affected by the electromagnetic noise
TV sets, radios (FM/AM broadcast, shortwave)
2. Channel, frequency, broadcast station affected by the electromagnetic noise
3. Channel, frequency, broadcast station unaffected by the electromagnetic noise
4. Layout of:
indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring from antennas, receiver
5. Electric fi eld intensity of the broadcast station affected by the electromagnetic noise
6. Presence or absence of ampli fi er such as booster
7. Operation condition of air conditioner when the electromagnetic noise enters in
1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise.
2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise.
3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.
4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
OBH549G
60
10-6. TEST POINT DIAGRAM AND VOLTAGE
1. Inverter P.C. board
MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA
MUZ-GE09NA2 MUZ-GE12NA2 MUZ-GE15NA2
MUZ-GE09NAH MUZ-GE12NAH MUZ-GE15NAH
MUZ-GE09NAH2 MUZ-GE12NAH2 MUZ-GE15NAH2
MUY-GE09NA MUY-GE12NA MUY-GE15NA
MUY-GE09NA2 MUY-GE12NA2 MUY-GE15NA2
Back side of unit
Bus-bar voltage
DB61
260-325 VDC
Smoothing capacitor
(C63)
Smoothing capacitor
(C62)
208/230 VAC
(-)
(+)
Fuse (F801)
T3.15AL250V
Fuse (F901)
T3.15AL250V
Output to drive compressor
(LDU,
LDV,
LDW)
Smoothing capacitor
(C61)
Fuse (F701)
T3.15AL250V
Heater connector
(CN722)
MUZ-GE•NAH/NAH2
R.V.coil
(CN721)
208/230
VAC
(MUZ)
Signal of outdoor fan motor
(CN931)
208/230
VAC
Front side of unit
Output to drive outdoor fan motor (CN932)
Fin temperature thermistor/RT64 (CN642)
Outdoor heat exchanger temperature thermistor
/RT68 (CN644)
LED
Discharge temperature thermistor/RT62
(CN641)
Defrost thermistor
/RT61(CN641)
(MUZ)
Ambient temperature thermistor/RT65 (CN643)
LEV connector
(CN724)
100
Defrost thermistor(RT61)
Ambient temperature thermistor(RT65)
Outdoor heat exchanger temperature thermistor(RT68)
Jumper wire for changing defrost setting (JS)
(MUZ)
Jumper wire for pre-heat control setting
(JK)
200
Fin temperature thermistor(RT64)
90
180
80
160
70
60
50
40
30
20
10
0
-4 14 32 50 68 86 104
Temperature(°F)
OBH549G
400
300
200
100
800
Discharge temperature thermistor (RT62)
700
600
500
0
32 60 68 86 104 122 140 158 176 194 212 230 248
Temperature (°F)
61
140
120
100
80
60
40
20
0
32 50 68 86 104 122 140 158 176
Temperature(°F)
MUZ-GE18NA
MUZ-GE18NAH
MUY-GE18NA
Back side of unit
208/230 VAC
Bus-bar voltage
DB61
260-325 VDC
(-)
(+)
Smoothing capacitor
(C63)
Smoothing capacitor
(C62)
Fuse (F801)
T3.15AL250V
Smoothing capacitor
(C61)
Fuse (F701)
T3.15AL250V
R.V.coil
(CN721)
208/230
VAC
(MUZ)
Heater connector
(CN722)
MUZ-GE•
NAH
Fuse (F901)
T3.15AL250V
Output to drive compressor
(LDU,
LDV,
LDW)
208/230
VAC
Front side of unit
Fin temperature thermistor /R
Outdoor heat exchanger temperature thermistor /R
Ambient temperature thermistor /R Defrost thermistor /R
Discharge temperature thermistor /R
Output to drive outdoor fan motor (CN932)
Signal of outdoor fan motor (CN931)
80
70
60
50
40
30
20
10
100
Defrost thermistor(RT61)
Ambient temperature thermistor(RT65)
Outdoor heat exchanger temperature thermistor(RT68)
90
0
-4 14 32 50 68 86 104
Temperature(°F)
OBH549G
800
700
600
500
400
300
200
100
Discharge temperature thermistor (RT62)
0
32 60 68 86 104 122 140 158 176 194 212 230 248
Temperature (°F)
62
200
Fin temperature thermistor(RT64)
180
160
140
120
100
80
60
40
20
0
32 50 68 86 104 122 140 158 176
Temperature(°F)
MUZ-GE24NA
MUY-GE24NA
Fuse (F62)
T2.0AL250V
Fuse (F601)
T3.15AL250V (
MUZ
)
R.V. coil (CN602)
208/230 VAC (
MUZ
)
Signal of outdoor fan motor
(CN931)
LED
Output to drive outdoor fan motor
(CN932)
Fuse (F901)
T3.15AL250V
Fuse (F880)
T3.15AL250V
Jumper wire for changing defrost setting (JS) (
MUZ
)
Jumper wire for pre-heat control setting (JK)
Defrost thermistor
/RT61 (CN671) (
MUZ
)
Discharge temperature thermistor/RT62
(CN671)
Outdoor heat exchanger temperature thermistor
/RT68 (CN671)
Ambient temperature thermistor/RT65
(CN672)
Fin temperature thermistor/RT64
(CN673)
LEV connector (CN724)
80
70
60
50
40
30
20
10
100
Defrost thermistor(RT61)
Ambient temperature thermistor(RT65)
Outdoor heat exchanger temperature thermistor(RT68)
90
0
-4 14 32 50 68 86 104
Temperature(°F)
OBH549G
800
700
600
500
400
300
200
100
63
JP715 (+)
Bus-bar voltage
294 - 370 VDC
JP30 (-)
Discharge temperature thermistor (RT62)
0
32 60 68 86 104 122 140 158 176 194 212 230 248
Temperature (°F)
200
180
160
140
120
100
80
60
Fin temperature thermistor(RT64)
40
20
0
32 50 68 86 104 122 140 158 176
Temperature(°F)
11
DISASSEMBLY INSTRUCTIONS
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below.
There are two types (refer to (1) and (2)) of the terminal with locking mechanism.
The terminal without locking mechanism can be detached by pulling it out.
Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not.
(2) The terminal with this connector has the
locking mechanism.
Sleeve
Locking lever
Slide the sleeve.
Pull the terminal while pushing the locking lever.
Connector
11-1. MUZ-GE09NA MUZ-GE12NA
MUZ-GE09NA2
MUZ-GE15NA
MUZ-GE12NA2
MUZ-GE09NAH
MUZ-GE09NAH2
MUZ-GE15NA2
MUZ-GE15NAH
MUZ-GE15NAH2
MUY-GE09NA MUY-GE12NA MUY-GE15NA
Hold the sleeve, and pull out the terminal slowly.
OPERATING PROCEDURE
1. Removing the cabinet
(1) Remove the screw fixing the service panel.
(2) Pull down the service panel and remove it.
(3) Remove the screws fixing the conduit cover.
(4) Remove the conduit cover.
(5) Disconnect the power supply wire and indoor/outdoor connecting wire.
(6) Remove the screws fixing the top panel.
(7) Remove the top panel.
(8) Remove the screws fixing the cabinet.
(9) Remove the cabinet.
(10) Remove the screws fixing the back panel.
(11) Remove the back panel.
NOTE
: Turn OFF power supply before disassembly.
PHOTOS
Photo 1
Screws of the top panel
Screws of the top panel
Back panel
Screws of the back panel
Photo 2
Screw of the cabinet
Screws of the terminal block support and the back panel
Screws of the cabinet
Photo 3
Service panel
Screw of the service panel
Screws of the conduit cover
Direction to remove
Conduit cover
Conduit plate
Screws of the cabinet
OBH549G
Hooks
64
OPERATING PROCEDURE
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following connectors:
<Inverter P.C. board>
CN641 (Defrost thermistor
(MUZ)
and discharge temperature thermistor)
CN643 (Ambient temperature thermistor)
CN644 (Outdoor heat exchanger temperature thermistor)
CN721 (R.V. coil)
(MUZ)
CN724 (LEV)
CN931, CN932 (Fan motor)
(3) Remove the compressor connector (CN61).
(4) Remove the screws fixing the heat sink support and the separator.
(5) Remove the fixing screws of the terminal block support and the back panel.
(6) Remove the inverter assembly.
(7) Remove the screw of the ground wire and screw of the terminal block support.
(8) Remove the heat sink support from the P.C. board support.
(9) Remove the screw of the inverter P.C. board and remove the inverter P.C. board from the P.C. board support.
Photo 4
PHOTOS
Screw of the heat sink support and the separator
Photo 5 (Inverter assembly)
Heat sink
Inverter P.C. board
Hook of the
P.C. board support
P.C. board support
Screws of the terminal block support and the back panel
Screw of the terminal block support
3. Removing R.V. coil
(MUZ)
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil.
Terminal block support
Heat sink support
Hook of the P.C. board support
Screw of the P.C. board fixture
Screw of the ground wire
Photo 6
R.V. coil
(MUZ)
OBH549G
65
Discharge temperature thermistor
OPERATING PROCEDURE
4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following connectors:
<Inverter P.C. board>
CN641 (Defrost thermistor
(MUZ)
and discharge temperature thermistor)
CN643 (Ambient temperature thermistor)
CN644 (Outdoor heat exchanger temperature thermistor)
(3) Pull out the discharge temperature thermistor from its holder.
(Photo 6)
(4) Pull out the defrost thermistor from its holder.
(5) Pull out the outdoor heat exchanger temperature thermistor from its holder.
(6) Pull out the ambient temperature thermistor from its holder.
Photo 7
PHOTOS
Outdoor heat exchanger temperature thermistor
Defrost thermistor
(MUZ)
Photo 8
Screws of the outdoor fan motor
5. Removing outdoor fan motor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN931, CN932 (Fan motor)
(3) Remove the propeller nut.
(4) Remove the propeller.
(5) Remove the screws fixing the fan motor.
(6) Remove the fan motor.
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Remove the inverter assembly. (Refer to 2.)
(3) Recover gas from the refrigerant circuit.
NOTE:
Recover gas from the pipes until the pressure gauge shows 0 PSIG.
(4) Detach the brazed part of the suction and the discharge pipes connected with compressor.
(5) Remove the compressor nuts.
(6) Remove the compressor.
(7) Detach the brazed part of the pipes connected with 4-way valve.
Propeller
Photo 9
Propeller nut
Brazed parts of 4-way valve
OBH549G
66
11-2. MUZ-GE18NA
MUZ-GE18NAH
MUY-GE18NA
OPERATING PROCEDURE
1. Removing the cabinet
(1) Remove the screws of the service panel.
(2) Remove the screws of the top panel.
(3) Remove the screw of the valve cover.
(4) Remove the service panel.
(5) Remove the top panel.
(6) Remove the valve cover.
(7) Disconnect the power supply and indoor/outdoor connecting wire.
(8) Remove the screws of the cabinet.
(9) Remove the cabinet.
(10) Remove the screws of the back panel.
(11) Remove the back panel.
NOTE:
Turn OFF power supply before disassembly.
PHOTOS
Photo 1
Screw of the top panel Screws of the cabinet
Screws of the back panel
Screws of the cabinet
Photo 2
Screws of the top panel
OBH549G
67
Screws of the cabinet
Screw of the service panel
Screw of the valve cover
Screws of the back panel
OPERATING PROCEDURE PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following connectors:
<Inverter P.C. board>
CN641 (Defrost thermistor
(MUZ)
and discharge temperature thermistor)
CN643 (Ambient temperature thermistor)
CN644 (Outdoor heat exchanger temperature thermistor)
CN721 (R.V.coil)
(MUZ)
CN724 (LEV)
CN931, CN932 (Fan motor)
(3) Remove the compressor connector (CN61).
(4) Remove the screws fixing the heat sink support and the separator.
(5) Remove the fixing screws of the terminal block support and the back panel.
(6) Remove the inverter assembly.
(7) Remove the screw of the ground wire and screw of the terminal block support.
(8) Remove the heat sink support from the P.C. board support.
(9) Remove the screw of the inverter P.C. board and remove the inverter P.C. board from the P.C. board support.
Photo 3
Screw of the heat sink support and the separator
Photo 4 (Inverter assembly)
Screws of the terminal block support and the back panel
Screws of the reactor
Heat sink
Inverter P.C. board
Hook of the P.C. board support
P.C. board support
Screw of the terminal block support
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN721 (R.V. coil)
(MUZ)
(3) Remove the R.V. coil.
Heat sink support
Hook of the P.C. board support
Screw of the ground wire
Screw of the P.C. board fixture
Terminal block support
Photo 5
R.V. coil
(MUZ)
OBH549G
68
Brazed parts of 4-way valve
OPERATING PROCEDURE
4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following connectors:
<Inverter P.C. board>
CN641 (Defrost thermistor
(MUZ)
and discharge temperature thermistor)
CN643 (Ambient temperature thermistor)
CN644 (Outdoor heat exchanger temperature thermistor)
(3) Pull out the discharge temperature thermistor from its holder.
(4) Pull out the defrost thermistor from its holder.
(5) Pull out the outdoor heat exchanger temperature thermistor from its holder.
(6) Pull out the ambient temperature thermistor from its holder.
PHOTOS
Photo 6
Outdoor heat exchanger temperature thermistor
Ambient temperature thermistor
5. Removing outdoor fan motor
(1) Remove the top panel, cabinet and service panel. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN931 and CN932 (Fan motor)
(3) Remove the propeller.
(4) Remove the screws fixing the fan motor.
(5) Remove the fan motor.
Photo 7
Screws of the outdoor fan motor
Defrost thermistor
(MUZ)
6. Removing the compressor and 4-way valve
(1) Remove the top panel, cabinet and service panel. (Refer to 1.)
(2) Remove the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Recover gas from the refrigerant circuit.
NOTE:
Recover gas from the pipes until the pressure gauge shows 0 PSIG.
(5) Detach the brazed part of the suction and the discharge pipes connected with compressor.
(6) Remove the compressor nuts.
(7) Remove the compressor.
(8) Detach the brazed parts of 4-way valve and pipes. (Photo 5)
Photo 8
Brazed part of the discharge pipe
Discharge temperature thermistor
Brazed part of the suction pipe
OBH549G
69
11-3. MUZ-GE24NA
MUY-GE24NA
OPERATING PROCEDURE
1. Removing the cabinet
(1) Remove the screws of the service panel.
(2) Remove the screws of the top panel.
(3) Remove the screw of the valve cover.
(4) Remove the service panel.
(5) Remove the screws fixing the conduit cover.
(6) Remove the conduit cover.
(7) Remove the top panel.
(8) Remove the valve cover.
(9) Disconnect the power supply and indoor/outdoor connecting wire.
(10) Remove the screws of the cabinet.
(11) Remove the cabinet.
(12) Remove the screws of the back panel.
(13) Remove the back panel.
Photo 2
Screws of the back panel
Screws of the top panel
Screws of the back panel
NOTE
: Turn OFF power supply before disassembly.
PHOTOS
Photo 1
Screws of the top panel
Screws of the cabinet
Screws of the cabinet
Screws of the back panel
Photo 3
Screws of the conduit cover
Conduit plate
Screws of the cabinet
Screws of the back panel
Screws of the back panel
Screws of the service panel
Screw of the valve cover
OBH549G
70
OPERATING PROCEDURE
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following connectors:
<Inverter P.C. board>
CN602 (R.V. coil)
(MUZ)
CN671 (Defrost thermistor
(MUZ)
, discharge temperature thermistor and outdoor heat exchanger temperature thermistor)
CN672 (Ambient temperature thermistor)
CN724 (LEV)
CN931, CN932 (Fan motor)
(3) Remove the compressor connector.
(4) Remove the screws fixing the relay panel.
(5) Remove the relay panel.
(6) Remove the ground wires and the lead wires of the inverter
P.C. board.
(7) Remove the screw of the PB support.
(8) Remove the inverter P.C. board from the relay panel.
Photo 4
Inverter P.C. board
Screws of the PB support
PHOTOS
Screw of the relay panel
Ground wires
Screws of the
PB support
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the following connector:
<Inverter P.C. board>
CN602 (R.V. coil)
(MUZ)
(3) Remove the R.V. coil.
Photo 5
Screws of the relay panel
Screw of the
R.V. coil
(MUZ)
Brazed parts of
4-way valve
OBH549G
71
OPERATING PROCEDURE
4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.)
(2) Disconnect the lead wire to the reactor and the following connectors:
<Inverter P.C. board>
CN671 (Defrost thermistor
(MUZ)
, discharge temperature thermistor and outdoor heart exchanger temperature thermistor)
CN672 (Ambient temperature thermistor)
(3) Pull out the discharge temperature thermistor from its holder.
(4) Pull out the defrost thermistor from its holder.
(5) Pull out the outdoor heat exchanger temperature thermistor from its holder.
(6) Pull out the ambient temperature thermistor from its holder.
PHOTOS
Photo 6
Outdoor heat exchanger temperature thermistor
Ambient temperature thermistor
5. Removing outdoor fan motor
(1) Remove the top panel, cabinet and service panel. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN931 and CN932 (Fan motor)
(3) Remove the propeller.
(4) Remove the screws fixing the fan motor.
(5) Remove the fan motor.
Photo 7
Defrost thermistor
(MUZ)
6. Removing the compressor and 4-way valve
(1) Remove the top panel, cabinet and service panel. (Refer to 1.)
(2) Remove the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Recover gas from the refrigerant circuit.
NOTE:
Recover gas from the pipes until the pressure gauge shows 0 PSIG.
(5) Detach the brazed part of the suction and the discharge pipes connected with compressor.
(6) Remove the compressor nuts.
(7) Remove the compressor.
(8) Detach the brazed parts of 4-way valve and pipes. (Photo 5)
Screws of the outdoor fan motor
Photo 8
Brazed part of the discharge pipe
Discharge temperature thermistor
Brazed part of the suction pipe
OBH549G
72
OBH549G
73
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
© Copyright 2009 MITSUBISHI ELECTRIC CORPORATION
Distributed in Jan. 2015. No. OBH 549 REVISED EDITION-G
Distributed in Dec. 2013. No. OBH 549 REVISED EDITION-F
Distributed in Apr. 2012. No. OBH 549 REVISED EDITION-E
Distributed in Apr. 2011. No. OBH 549 REVISED EDITION-D
Distributed in Apr. 2011. No. OBH 549 REVISED EDITION-C
Distributed in Dec. 2010. No. OBH 549 REVISED EDITION-B
Distributed in Sep. 2010. No. OBH 549 REVISED EDITION-A 5
Distributed in Jul. 2009. No. OBH 549 5
Made in Japan
New publication, effective Jan. 2015
Specifications are subject to change without notice.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project