ST900 Direct Vent Gas Fireplace

Installation Manual

NEW ZEALAND EDITION

Important:

The appliance shall be installed in accordance with;

• This installation instruction booklet

• Local gas fitting regulations

• Municipal building codes

• Electrical wiring regulations

• NZS 5261, Gas installations

• Any other relevant statutory regulations.

• Must be installed by a qualified person

Manufactured by: Escea Ltd, PO Box 5277 Dunedin NZ, Ph: 03 479 0302, e: [email protected]

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

Note:

THERE ARE A FEW THINGS TO CONSIDER BEFORE INSTALLATION

• Cavity Dimensions and Clearances

• MUST be installed a 100mm minimum off the floor or nearest horizontal surface.

• Coupling of flue to fire

• Coupling of gas lines to fire

• Fixing the fire to cavity

• Electrical mains socket at rear left corner of the cavity, to accommodate the power

transformer

• Isolation switch for electrical transformer.

• Gas pipe placement to the front left of the cavity.

• The ST900 electronic control system is designed to work within the temperature range of

0°C to 60°C, with a humidity level that is non condensing. This is to ensure safe

operation of the electronic and gas control system.

If the fireplace is subjected to an environment with temperatures very close to or

exceeding these temperature limits (irrespective of if the fireplace is on or off at the time)

the fireplace may not start up until the temperature returns back to within the operating

range.

To remedy this the environmental temperature should be addressed and the fireplace

control system given time to adjust accordingly. The fireplace should then function

correctly.

It would be prudent to consider these operational limits during the installation planning

stage. Protecting the installed fireplace from low external ambient temperatures and cold

drafts through the use of approved modern building methods and materials will help

ensure that the required operating environment is maintained.

WARNING:

Failure to follow these instructions could cause a malfunction of the fire, which, could result in death, serious bodily injury, and/or property damage. Failure to follow these instructions may also void insurance cover and/or product warranty.

Installation:

Installation must be carried out by a registered installer who, on completion of the installation, must issue a certificate of compliance, in accordance with national and/or local codes. If a certificate of compliance is not issued then the Escea warranty may be void.

Warranty Repair and Annual Servicing:

Warranty repair work must be carried out by a recognised Escea gas fire technician. It is recommended that recognised Escea Gas fire technicians are also used to carry out annual servicing requirements (particularly during the warranty period). For contact details of authorised Escea technicians in your area, please contact the retailer from whom the appliance was purchased.

This product must be installed according to these instructions and in compliance with all relevant building, gas fitting, electrical and other statutory regulations (eg. NZS 5261). Any shortcomings in the appliance and flue installation will be the responsibility of the installer, and Escea will not be accountable for any such failings or their consequences.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

Recommended Installation Process:

The following diagram illustrates the steps required to install your gas fire, and the trades required at each stage.

The sequence in which you choose to do these tasks will vary depending on your individual scenario. Please read these instructions fully before proceeding with the installation. Leave the installation of the fascia panels until the very end of the installation and commissioning to avoid damage to the fascia panels.

Builder

1.

Construct Frame (Section 1.0 to 6.0)

Electrician

2.

Install Electrical connection (Section 15.0)

Gasfitter

3.

Install Gas Pipe (Section 7.0 to 8.0)

4.

Install Fire (Section 9.0 to 12.0)

Ensure that you leave a gap between the studwork and fire chassis to accept the wall lining if applicable.

Gasfitter

5. Install Flue + Flue Restrictor if required (Section 13.0)

6.

Test fire and verify flame pattern is acceptable

7.

Cover-up fire using packaging (Section 16.0)

Builder

8.

Gib / line chimney breast

Gasfitter

9.

Commission the Gas Fire (Section 17.0)

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

Contents:

1.0

2.0

3.0

4.0

5.0

6.0

7.0

8.0

9.0

10.0

11.0

12.0

13.0

14.0

15.0

16.0

17.0

18.0

19.0

20.0

21.0

22.0

23.0

Product Description

Creating the Cavity

Hearth and Floor Clearances

Wall Linings

Vertical Clearances

Corner Installations

Laying Gas Pipe

Connecting Gas Pipe

Power Supply

Fixing Fire to Wall

Removing the Firebox Glass

Installing the Flue system

Fitting the Flue Restrictor

Converting to Natural Gas

Placing the Fuel Bed

Checking Operating Pressure

Covering up the Fire

Commissioning the Fire (fitting the fascia)

Operating Instructions

Sounds and Smells

Annual Service Check

Installation Check List

Warranty Terms and Conditions

1.0 Product Description:

The Escea ST900 decorative gas fire is designed to be built into a cavity.

The appliance is flued via Simpson

Duravent Direct Vent Pro 5”x8” Flue, available from your Escea distributor or retailer. The user will control their fire with the Radio Frequency (RF) remote.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

2.0 Creating the Cavity:

The cavity specifications vary depending on fascia type. The dimensioned drawings below show the size of opening that must be created to fit the ST900. The wall directly above the fire should be finished / gibbed / lined after the fire has been installed, unless there is an access hatch or the chase is open to the ceiling cavity, which allows the flue to be installed after the wall has been lined.

The wall and framework in front of the flue must not exceed 100mm in thickness, this includes plaster board or any wall linings. This is to ensure there is at least 25mm gap between all fluing components and any combustible material.

FERRO / MOLARIS

Go to section 2.1

VELO

Go to section 2.2

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

2.1 Cavity for Ferro / Molaris Fascias

Note: It is not necessary to line the cavity, and it may be constructed with timber.

Continue on to section 2.4

2.2 Cavity for Velo Fascias

Note: It is not necessary to line the cavity, and it may be constructed with timber.

For Velo fascias, the fireplace should be recessed 12mm into the cavity.

Continue on to section 2.4

2.4 Considerations for creating the cavity:

If installing the ST900 into a purpose built chimney breast or chase which is not open to the roof space of the building, it may be appropriate during the planning stage to consider the installation of additional vents.

Heat otherwise lost through the outer skin of the fireplace and flue system into the cavity of the chimney breast or chase may be recovered into the room by placing two air vents in the cavity or chase. By placing one vent at or just above floor level and the other near the ceiling of the room will induce natural convection and prevent heat build up in the cavity and subsequently recover some of the heat into the room.

3.0

Hearth and Floor Clearances:

There should be at least 100mm between the bottom of the ST900 fire and any horizontal surface below, for example hearths and floors.

3.1

Wall and Cabinet Clearances:

There must be a minimum of 100mm from the sides of the fascia to any protruding side walls or cabinetry.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

4.0

Wall Linings:

The wall board that lines the outside of this opening can be normal dry wall

(Plaster Board) and does not need to be non-combustible providing that it does not come any closer to the fire than the dimensions shown in section 2.0. Note: The temperature of the wall lining directly above the fire does get warm and hence may discolour paint finishes that are susceptible to temperature damage or distort vinyl wall coverings.

5.0

Television Positioning Considerations:

It is becoming common practice for consumers to mount flat screen TV‟s above their gas fireplace.

Most TV manufacturers have specified in their instructions that the TV should not be installed on, near or above a heat source. For this reason TV location decisions rest solely with the householder and Escea will not be held liable for any adverse affects on a TV located near to an Escea fireplace that may be caused by heat.

The drawings below are suggestions that may be used as a GUIDE for those consumers who do decide to locate their TV above an ST900 gas fire. These drawings show ways to reduce the amount of warm air rising off the fireplace and onto the TV.

Recessed TV

Flush TV with small mantle Mantle above fire Protruding fire

50 min

50 min

50 min

50 min

50 min

100 min

50 min

50 min

Mantle

100 min

Mantle

500 min

500 min

500 min 500 min

The material that the wall and mantle are made from will also affect the operating temperature of the TV so it is the customers responsibility to satisfy themselves that their

TV mounting and mantle design will not exceed the listed maximum operating temperature of their electronic goods.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

5.1 Combustible Mantle Clearances:

The diagram to the right shows the minimum and maximum allowable size for mantles or protruding surfaces mounted above the ST900.

Note: Escea does not recommend placement of items on the mantles shown in the diagram to the right. This is because of the potential for items placed on or above the mantle to be affected by the heat rising from the appliance.

5.2 Non-Combustible Mantle Clearances:

If the entire installation (mantle, wall and cavity) is constructed from non-combustible materials, the clearances to mantles may be as shown in the shaded area.

6.0

Corner Installations:

If a cavity is to be created in a corner, the following table gives the minimum sizes in millimetres.

Fascia Type

Ferro

Velo

A

7.0

Laying Gas Pipe:

B C D

380 910 835 1670

392 940 862 1724

Gas pipe should be sized as per the requirements of NZS5261. The pipe sizing must be sufficient to deliver the following volume of gas to the fire with all other gas appliances in the home running at the same time;

ST900 = 20Mj/hr

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

8.0

Connecting the Gas Pipe:

Soft copper should be run directly to fire and connected onto the regulator with flare nut

( 3/8” BSP thread). The regulator that is supplied with the fire MUST NOT BE REMOVED.

Removal of the regulator, or replacing it with one not intended for use with an Escea fire, will void the limited appliance warranty.

9.0

Power Supply:

Depending on market, your ST900 has been supplied with either a battery pack or power transformer. Both are also available from Escea if you wish to change the power supply type from what your fire was supplied with.

9.1

If you are using a power transformer:

Whilst the cavity is being created consideration should be given to appropriate location of a standard 3 pin, 240V power outlet to accommodate the power transformer. This must be within 1.5

m of the lower left hand side of the appliance.

Locating this plug within the cavity makes the installation very neat but the provision must be made to be able to switch the power supply off and on (electrical isolation switch) and must be accessible after the fire has been installed. This is normally done by means of a separate switch located outside of the cavity and wired to the plug. This will allow service technicians to isolate the power supply before performing service work on the appliance.

The power transformer cord should be run, as shown below left, through the small hole in the rear of the fire and connected to the panel mounted plug pictured below right.

This appliance will draw a maximum of 2A (fused) from a 240V supply.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

9.1

If you are using a battery pack:

Using a battery pack will allow your ST900 to operate without mains power, allowing the fire to run in the event of a power cut. This battery pack uses 3x C cell batteries.

To install the battery pack simply place the pack in the bottom right of the fire as pictured below and connect it to the plug which should be near the brass

Copreci valve.

To access the battery pack, remove the fascia (described in section 18) and the battery pack will be on the lower right hand side.

As the ST900 draws a small current when not in use, it is recommended to remove the batteries if the fire will not be in use for long periods of time.

10.0

Fixing the Fire to the base and wall:

It is a requirement that this fire be securely fastened to the wall and base. Once the fire has been pushed back into the correct position, use wood screws (or other suitable fasteners) to fix the fire to the cavity through each of the four holes in the corners, as shown in the diagram to the right. Note: It may be necessary to use washers on the fasteners to securely fasten the fire to the wall.

When fixing the fireplace in position ensure that you leave a gap between the fireplace flange and the framing timber for the wall lining, which will be added at a later stage.

11.0

Removing the Firebox Glass:

Pull the four hooks shown below towards you and then away from the glass to release the glass frame underneath the hook.

Do not operate the appliance if the glass has been broken, damaged, or the glass is not properly positioned/hooked onto the appliance.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

12.0

Installing the Flue System:

Ensure all flue components are Simpson Duravent Direct Vent Pro 5” x 8,” no other flue types may be used.

Note: Consult section 12.13 to ensure correct length of flue is calculated.

There are two basic types of Balanced Flue System installations:

• Horizontal Termination

• Vertical Termination

Use the diagrams in sections 12.5, 12.6 & 12.7 to check if your proposed flue system is acceptable. Section 12.9 will also need to be used to determine whether the flue terminal location meets the requirements of NZS 5261. Then use Appendix A to work out the quantities of the flue components that are required.

12.1

Any offsets in your flue configuration should be 45 ° where possible .

12.2

If your flue configuration has a horizontal run, there must be a minimum 1 ° inclination

(20mm vertical rise per 1m horizontal run) leading upwards towards the termination.

Do not install the flue with horizontal sections sloping down towards the termination.

This could cause the fire to operate incorrectly and possibly create an unsafe condition.

12.3

The flue must maintain the following clearances to combustible materials;

25mm from all sides and bottom of the flue, and

50mm from the top of the flue.

12.4 If your flue configuration falls on or near a restriction zone boundary line in diagrams 12.5,

12.6 & 12.7, it may require the restriction value from either side of the boundary line to achieve the correct flame aesthetic, this may vary from installation to installation.

12.5 Vertical Only Flue Diagram:

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

Use this diagram to determine what percentage of flue restriction in required to ensure safe and correct operation of the ST900 decorative gas fireplace.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

12.6 Horizontally Terminating Flue Diagram:

Use this diagram to determine what percentage of flue restriction in required to ensure safe and correct operation of the ST900 decorative gas fireplace.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

12.7 Vertically Terminating flue with a Horizontal Offset:

Use this diagram to determine what percentage of flue restriction in required to ensure safe and correct operation of the ST900 decorative gas fireplace.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

12.8

Standard Flueing Configurations:

The following flue components are available from escea in kitset form.

DVF-H

DVF-V

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

12.9 Locating the Flue Terminal:

The flue terminal must be located using the information given in the following diagram and table based on NZS 5261

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

Table 16 – Minimum clearances required for flue terminals shown in figure 3

Ref. Item Minimum Clearances (mm) a Below eaves, balconies and other projections:

Gas appliances up to 50 MJ/h input

Gas appliances over 50 MJ/h input b From the ground, above a balcony or other surface (see note 6) c From a return wall or external corner (see note 6) d From a gas meter (M) (see 2.5.4.9 for vent terminal location of

Regulator) e From an electricity meter or fuse box (P) f From a drain pipe or soil pipe g Horizontally from any building structure (see note 6) or obstruction

Facing a terminal h From any other flue terminal, cowl, or combustion air intake

(see note 6)

Natural draught

300

500

300

500

1000

500

150

500

500 j Horizontally from an openable window, door, non-mechanical air

Inlet, or any other opening into a building with the exception of

Sub-floor ventilation:

Gas appliances up to 150 MJ/h input

Gas appliances over 150 MJ/h input up to 200 MJ/h input

Gas appliances over 200 MJ/h input

All fan-assisted flue gas appliances, in the direction of

discharge k From a mechanical air inlet, including a spa blower

500

1500

1500

1500

300

300

500

1500

1000 n Vertically below an openable window, non-mechanical air inlet, or

Any other opening into a building with the exception of sub-floor

Ventilation:

Space heaters up to 50 MJ/h input

Other gas appliances up to 50 MJ/h input

Gas appliances over 50 MJ/h input and up to 150 MJ/h input

Gas appliances over 150 MJ/h input

150

500

1000

1500

150

500

1000

1500

NOTE-

(1) All distances are measured to the nearest part of the flue terminal

(2) Prohibited area below electricity meter or fuse box extends to ground level

(3) See 2.6.13.3 for restrictions on a flue terminal under a covered area

(4) See appendix G LPG Cylinder Locations, figure G2 and figure G3, for clearances required from a flue terminal to

An LPG cylinder. A flue terminal is considered to be a source of ignition.

(5) For gas appliances not addressed above, the design shall be certified by a suitably qualified engineer.

(6) Some gas appliances may be suitable for closer installation; refer to the manufacturer‟s instructions.

Fan assisted

200

300

300

300

1000

500

75

500

300

12.10 Supporting the flue system:

Wall straps are required to fix the flue system in place for each installation. This will ensure that no undue strain is placed on flue components once installed.

For a flue offset or horizontal run, it is recommended that wall straps be used to the flue system with a spacing of 900mm between straps. Plumbers strapping / tape can be used to connect the wall straps to the building structure where there are large distances between the support point and the anchor point.

For vertical flue runs it is recommended that wall straps be used to anchor the flue system with a spacing of 1200mm between straps.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

12.11 Sealing ‘through roof’ and ‘through wall’ penetrations:

For „through roof‟ penetrations, use a Deck-tite flashing or equivalent to create a weathertight seal between the flue and the roof cladding.

For „through wall‟ penetrations, this will require the use of a Wall Thimble. The Wall Thimble will ensure you have suitable clearance from combustibles as well as sealing the penetration. The section of the wall thimble installed on the external surface of the wall should be sealed to the wall using a high temperature sealant such as a High Temperature

RTV Silicone or equivalent. Additional sealant is required to seal the Terminal Cap to the external wall. A bead should be run along the edge of the Terminal that will be in contact with the wall once installed.

12.12

Twist locking procedure:

Before connecting flue components, to ensure an airtight seal run a single 7-8mm bead of

High Temperature RTV Silicone or equivalent, on the „male‟ end of the flue as shown in the diagram below.

The four indentations located on the female end of the flue are designed to slide straight onto the male ends of the adjacent flue length, by orienting the four flue indentations so they match and slide into the four entry slots on the male ends.

Push the pipe sections completely together, then twist-lock one section clockwise approximately one-quarter turn, until the two sections are fully locked.

Wipe off any excess sealant from the exterior of the flue joint.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

12.13

Points to note when planning the Installation of the Escea DV flue:

- This flue system cannot be cut to length. Correct lengths must be selected for each installation. For a full list of available flue lengths, contact your Escea retailer.

- The listed length of the flue pipe is not the installed length. 1 ½” (38mm) needs to be subtracted for each join to determine the installed length of each piece of flue pipe.

E.g. 48” length has installed length of 45”.

- All vertical measurements should be measured from the top surface of the fireplace casing itself (not the fascia).

- When using horizontal flue runs, vertical measurements should be measured to the centre line of the horizontal flue pipes.

- When using 90° elbows in the installation, use the diagram below to help calculate installations horizontal and vertical distances. 1½” (38mm) will still need to be subtracted from each join.

- If using a 45° offset in your installation, consult the chart below to select the required flue length to give the desired offset. 1½” (38mm) will still need to be subtracted from each of the 45° bends to allow for the joins.

Straight

Flue Length:

0”

6”

9”

12”

24”

36”

48”

Offset:

5

8

10

13”

21

29

5

7

7

3

7

38

1

/

8

/

8

/

/

/

8

/

8

8

4

Rise:

15

18

20

22

31

3

3

5

5

1

/

8

/

8

/

8

/

8

39

3

/

8

47

7

/

/

8

8

- Adjustable lengths are available depending on stock levels. Contact escea for more information.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

13.0

Fitting the Flue Restrictor:

If your flueing configuration requires that you fit a flue restrictor

( see graph in section 12.5, 12.6 & 12.7 of this manual to find out if your configuration requires a flue restrictor ), follow the instructions below.

First, prepare the Flue Restrictor by removing and discarding the two inner rings to achieve 60%, 70% or 80% restriction and hand bending the five tabs 90°.

Remove the firebox glass (if fitted), and using a Phillips /

Pozi Drive screwdriver remove the two screws located inside the firebox as shown.

Once the two screws are removed the baffle will be free to slide down and out as pictured.

Ensure the firebox paint is not scratched and that the baffle is not damaged.

Fit the flue restrictor by pushing it up into the flue with the tabs facing downwards as shown. Push it up into the flue until the tabs no longer protrude into the firebox and it is securely placed. If the restrictor is loose or will not stay in position manipulate the five tabs to suit.

Once the restrictor is in place, replace the baffle taking care not to damage or scrap paint, and replace the two screws.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

14.0 Converting to Natural Gas:

Where a conversion to natural gas is needed, the following steps should be followed

14.1

First you need to remove the burner by removing the screw holding it in place on the left hand side of the firebox (Fig. 1).

Then remove the 1.3mm burner jet (Fig. 2) and replace it with the 1.9mm jet supplied in the kit.

Now remove the gas pipe fitting under the pilot (Fig. 3) and remove the No.46 pilot Jet

(Fig. 4) and replace it with the No.48 pilot jet supplied in the kit.

Replace the pilot line.

Adjust the Primary Aeration Collar on the burner to the Natural Gas position as shown in the diagram by removing the screw in the side and then replacing it when the collar is in the correct position. Place the burner into position and screw it in place.

The gas regulator needs to be converted from the LPG setting to the Natural Gas setting.

The regulator is located on the left hand side of the control tray, at the base of the fire. To change the regulator between Natural Gas and Propane, unscrew the top cap off the regulator and pull the plunger from it. Re-insert the plunger on the opposite side (as shown in the diagram to the right) and screw the assembly back in the stack

Finally, put the sticker supplied in the conversion kit in onto the dataplate of the ST900 in the position shown.

The sticker must be signed and dated by the installer who has converted the fire.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

15.0

Placing the Fuel Bed Media:

Your ST900 Gas fire will be supplied with a Fuel Bed kit. Follow the instructions below for the Fuel Bed kit that applies to you.

15.1 Driftwood Fuel Bed:

First scatter one layer of the supplied white stones evenly across the base of the firebox, ensuring there are no stones or driftwood pieces inside the pilot flame surround guard.

Arrange the supplied driftwood pieces exactly as shown in the diagram and photo below.

Underneath each piece of driftwood is a written number which will help in correctly positioning it within the firebox.

15.2 Coal or Glass Fuel Bed:

Scatter the supplied fuel bed media evenly across the base of the firebox, ensuring there are no coals, glass or media inside the pilot flame surround guard which may obstruct or impair the pilot assembly.

Ensure no coals, driftwood, glass, or other material are inside the pilot flame surround guard, and the pilot flame is clearly visible. If any loose material is inside

16.0

Checking Operating Pressure:

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

WARNING: The regulator that is supplied with the fire MUST NOT BE REMOVED.

Removal of the regulator, or replacing it with one not intended for use with an Escea fire, will void the limited appliance warranty.

The regulator is factory set (not adjustable) to supply the correct operating pressures based on the minimum and maximum inlet pressure in the table below for the relevant gas type.

This is done at the regulator located at the front LH corner of the appliance.

This is best done before the fascia panels have been fitted to avoid fascia damage.

Pressure test points are available for both inlet and operating test pressure (as shown below).

1) Remove inlet pressure test point screw and attach manometer tube.

2) Run the fire on full and measure inlet pressure with all the other gas appliances running. If pressure does not fall within the maximum or minimum pressures listed on the table below then reassess installation pipe size or upstream regulator settings.

3) Remove the manometer and replace inlet test point screw.

4) Remove the operating pressure test point screw. Connect manometer tube and measure pressure with fire running on full and with all the other gas appliances running.

5) Replace operating test point screw and leak test inlet and operating pressure test points and inlet gas connection union.

ST900 Pressure Table

A = ½” BSPT Female Inlet Connection

B = Gas Conversion Cap

C = Operating Pressure test point

Minimum Inlet Pressure

Maximum Inlet Pressure

Operating Pressure

LPG

2.5 kPa

5.0 kPa

2.30 kPa

Gas Type

Natural

1.2 kPa

5.0 kPa

1.0 kPa

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

17.0

Covering up the fire:

Before the wall surrounding the ST900 is lined, the fire must be covered up and sealed to prevent Gib dust from getting into the fire. It is recommended that the packaging supplied with the fire is used to achieve this.

18.0

Commissioning the Fire:

After the cladding and finishing processes are completed, the gasfitter must return to the site to run the fire for a minimum of 20 minutes and finally assemble and fit the fascia and associated accessories.

→ If you are installing a FERRO or MOLARIS fascia: SEE SECTION 18.1

→ If you are installing a VELO fascia: SEE SECTION 18.2

1.

18.1

Assembling the Ferro or Molaris fascia:

(Skip this step if using Molaris (Natural Stone) fascia)

The ST900 Ferro fascia has two brackets supplied in the fascia box which have not been fully assembled. To assemble them use the 4x screws supplied to fasten the brackets to the fascia as shown below. Position the brackets with the flange facing outwards, and the hooks facing the bottom of the fascia [Identify the bottom of the fascia by the large cut-out shown below].

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

3.

2.

Fitting the Grill Trim:

(Skip this step if using Molaris (Natural Stone) fascia)

Packed in with the fascia kit is the Grill Trim.

Attach this to the fire using the 3 supplied screws in the positions shown to the right.

The perforated surface (grill) should be on top.

The ST900 fascia uses these four hooks for attaching to the fire. Do this by lining up the fascia hooks with the receptacles on the sides of the fire. Lift the fascia so that the hooks are above the receptacles, and let it drop down into position until it is secure and free from movement.

Remove all protective plastic and packaging material before operating the fire. Care should be taken when handling the fascia.

To remove the Fascia, lift it upwards briefly, and then pull towards you. Ensure the fascia is allowed to cool before attempting to remove it.

→ Continue on to section 19.0

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

18.2

Assembling the Velo fascia:

Preparation:

1.

The supplied upper baffle must be removed and discarded before continuing with the install. To do so, undo the 4x screws shown right and remove the baffle by lifting it upwards and outwards as shown.

2. Install the Heat Deflector to the top of the fireplace using the 3x supplied screws with the Heat Deflector facing outwards as shown.

3. Install the supplied Upper Baffle (the part with grill fitted) into the fireplace with grills facing downwards. Fix in place using the 4x supplied screws in the position shown.

4. Install the lower fascia magnet brackets using the 4x supplied screws in the two positions shown below. (Do not affix the magnets at this stage)

Installation:

5. The ST900 fascia uses the hooks on the rear

for attaching to the fire. Line up the hooks with the receptacles on the sides of the fireplace, and lift the fascia so that the hooks are above the receptacles. Let it drop down into position until it is secure and free from movement. The Heat Deflector (2) should sit slightly inside the fascia so that the fascia can sit tight against the wall.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

6. Attach the supplied Magnets to brackets installed in step 4 above, using the supplied nuts and bolts

7. Place lower trim by securing it to the magnet brackets attached in step 3.

18.4 Cleaning the ST900 Fascia:

The fascia must be cold before starting any form of maintenance or cleaning.

If your Stainless Steel fascia requires cleaning, 3M Stainless Steel cleaner (or equivalent) is recommended.

If your Powder Coated (Painted) fascia requires cleaning, you must only use a damp nonabrasive cloth to give it a gentle wipe. Never ever rub the fascia.

18.5 To clean the glass, remove it as described in section 11.0 and clean inside and out using standard window cleaner. Do not allow glass to become excessively dirty as this will be difficult to remove.

DO NOT ATTEMPT TO CLEAN THE GLASS WHILE IT IS HOT. NEVER OPERATE THE UNIT

WITH THE GLASS REMOVED.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

19.0

Operating Instructions:

The escea ST900 remote control allows you to turn ON and OFF the fire, control the flame height in the Manual mode, or control the room temperature in the Thermostat mode. The remote has a maximum range of approximately 10 meters, and because the remote works by radio frequency, it does not need to be aimed at the ST900 for it to operate. The remote control runs off 2x AA batteries which are supplied in the same packaging as the remote.

The remote control is supplied with a wall-mount cradle; the installer should mount this at a location determined by the customer.

19.3

Switching on the ST900:

Note: If this is the first time running the ST900 the air will need to be purged from the gas lines. To do this, follow the instructions below to switch the fire on and then switch it off. Repeat this up to 10 times until the pilot flame successfully sparks and ignites.

When first powered the remote starts at the OFF screen (it is possible that the remote is locked in the OFF screen: to unlock it just press the button below Unlock, and then OK).

Switching on: Once the remote is unlocked, press On (left button) and OK (middle button).

A beep from the control unit will be heard, and the ignition process starts (the pilot will start sparking and gas will start flowing to the pilot, which should then be lit within a few seconds). Note that while in operation the RF signal strength indicator disappears.

Wait until the current flame status displays pilot .

If the pilot flame fails to ignite, you must turn OFF the fire from the remote and start the process of turning it ON again.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

19.4

Switching off the ST900:

To turn off the fire, push the OFF button, to shut down the gas flow to the fire and switch it off. The OFF display will now appear in the display.

19.5

Setting the control mode for the fireplace:

There are three different modes for controlling the appliance:

> Manual

> Automatic

> Program

Automatic mode allows you to set a temperature, while in manual mode the flame level may be set to HIGH, MEDIUM, LOW & PILOT. Program mode offers automatic temperature control for specific times of the day.

In the initial screen when the remote is turned on, three options are available: AUTO,

MANUAL and MENU.

Auto and Manual are two of the three different modes for controlling the appliance with the remote.

> Manual mode:

If Manual is pressed, Pilot appears as the selected setting. In the bottom ro w, ↓ and ↑ appear, indicating that the flame level can by changed by just pressing the left or middle button. There are four possible flame positions:

Pilot flame, Low flame, Medium flame and High flame.

Pressing Back (right button), returns to the initial screen.

Note that a Safety temperature can be previously set in the configuration menu. This specifies the maximum permitted room temperature. This temperature can never be set higher than 40ºC (104 ºF).

> Automatic mode:

If Auto is pressed in the initial screen, 25ºC (77 º F) appears as the desired temperature in the selected setting. In the bot tom row, ↓ and ↑appear, indicating that we can change the desired temperature value by just pressing the left or middle button. In auto mode the appliance heats until this temperature is reached. Limits are 0-37ºC (32-99ºF).

Pressing Back (right button), returns to the initial screen.

The Auto mode feature is optional and can be enabled or disabled in the configuration menu (see specific chapter).

In this mode the main burner can be switched on and off.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

> Program mode:

By default the program mode is not enabled. To enable program mode, enter configuration mode by pressing and holding the OFF button for 40 seconds, selecting “Programming” and selecting “yes” (For more information on configuration mode see section 19.9).

There are two types of program mode: a Daily mode and a Weekly mode. In the daily mode, every day uses the same program. In the weekly mode, every day has its own program, so it is possible have a different program for each day of the week.

In this mode the main burner can be switched on and off (pilot still burning).

Day programming menu: (Menu → Adjust Menu → Change Program)

There are 8 menus like this. One for Daily, and the others for each separate day (Monday,

Tuesday, Wednesday, Thursday, Friday, Saturday and Sunday). This day programming screen consists of:

Daily program:

A: Selec ted (including “Daily”). The selected day can be changed by pressing

Change (middle button).

B: Day schedule graphic. This bar displays the program for the whole day by showing the temperature setting for each hour of the day. Each bar on the screen represents an hour (0 to 24). To access the day schedule graphic, press ↓ (left button). To change the desired temperature, go to the hour you want to change by pressing → (left button) and then press change (middle button).

There are 3 temperature settings (bars):

Off [Small bar] No temperature control (the appliance is in pilot mode).

Night Temp [Medium bar] The night temperature is set as the desired temperature and the appliance will heat until this temperature is reached. To adjust the night temperature pres s Menu → Adjust menu → Night and set the desired temperature.

Comfort Temp [Large bar] The comfort temperature is set as the desired temperature and the appliance will heat until this temperature is reached. (High bar).

To adjust the comfort temperature pres Menu → Adjust menu →

Comfort and set the desired temperature.

Finally, to launch the program mode, in the main menu, set Program to On, and select the desired Program Type (Daily or weekly). When activated, the screen will show which of the above temperature settings is currently active, Off, Night, or Comfort. The pilot must remain lit in order for the program to remain running

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

19.6

Changing the display from Celsius to Fahrenheit:

Go into Menu → Adjust menu → Unit. Press middle button and then left button for changing units.

19.7

To Lock / Unlock the remote control buttons:

Go into Menu → Lock. Press middle button and then left button for locking the remote.

To unlock press left button and then middle button.

19.8

Replacing batteries:

When batteries are replaced in either the Battery box (inside the fireplace) or in the handset, then the unit will require 1 minute afterwards to regain connection.

19.9

Operation from the Touch Pad:

The touch pad is intended to be used for service/diagnostic purposes and to operate the fire in the event that the remote handset becomes lost or inoperative.

If you remove the fascia you will find an electronic touch pad in the lower centre of the fire.

The touch pad features the basic operations of the fire: On, off, and manual adjustment of the flame height.

To turn on the ST900, push the ON/OFF button on the touch pad. The system will emit a beep and begin the ignition process, which can take about 20 seconds. Once the start up process is complete, the pilot flame is lit. The ST900 is now in the „Manual‟ mode and ready to be used.

While the pilot is lit, press the „Flame Up‟ or „Flame Down‟ button to alter the flame height.

The LED will flash once and the unit will beep to confirm the flame height has been adjusted. The ST900 has 4 flame positions: Pilot only, Low, Medium, and High flame height.

If the „Flame Up‟ button is pressed while the unit is in the „high‟ flame position, nothing will happen. Similarly, if „Flame Down‟ is pressed while the unit is in the „pilot‟ flame position, nothing will happen.

To shut down the gas flow to the ST900, press the On/Off button and the LED will begin to blink and the unit will emit a beep.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

19.10

Pairing the Remote to the Control Unit:

Install batteries to the battery pack and after a while the valve motor will start moving (if not wait one minute from the time of installing batteries). Once the valve has finished moving, press the OFF button on the remote control for 40 seconds. During this time the screen may go blank, this is normal. After 40 seconds, the configuration menu appears:

All the operation must be done on channel A (go to the last option in the setup menu by pressing ↓ and select channel A).

After that, go to pairing option again and press the select button (middle button) and when off is highlighted, press the change button (left button) off becomes on.

Once the pairing is on, there are 20 seconds to push

(press and release) the button S1 (yellow) in the control unit.

Once this operation is done, you hear a beep in the control unit and on the remote control will appear:

The indication on the pairing menu option will now become off and the pairing is over. To return to the home screen press the back button until you get to main screen.

PS: If the pairing has been attempted previously and has not been achieved, do the following:

- Prepare the command by pressing the key OFF for 40 seconds.

- Set the channel on channel A.

- Select On in the pairing setting.

- Remove the batteries from the control unit (wait 10 seconds) and put the batteries back.

- Once the valve has finished moving, repeatedly push (press and release) the S1 button

(yellow button on the control unit), until you hear the beep that confirms that learning has taken place.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

19.11

Initial configuration:

To enter the configuration menu, press the OFF button on the remote control for 40 seconds.

During this time the screen may go blank, this is normal. After 40 seconds, the configuration menu appears.

It is possible to configure the appliance with the following options:

Thermostat : This option enables or disables the auto thermostat mode. To enable it, select

Yes. To disable it select No.

Gap Temp : This option refers to the tolerance between the desired temperature and the current one. If the difference is greater than this gab temperature setting, the flame level increases.

For example: the desired temperature is set at 20°C and the current temperature is 18°

 If the Gap Temp is 0•5°C: Flame level will go to maximum level because the difference is 2°C.

If the Gap Temp is 1°C: Flame level will go to medium level as difference of 2°C is two times the gap setting. (The flame level increases two levels: Pilot → Low → Medium.)

If the Gap Temp is 2°C: Flame level will go to minimum level as the difference of 2°C is equal to the gap setting. (The flame level inc reases one level: Pilot → Low.)

Programming : this option enables or disables the program mode. To enable it, select Yes .

To disable it, select No .

Fan System : This option enables or disables the fan system. To enable it, select Yes . To disable it, select No .

Soft start : this option causes the thermostat mode to work incrementally. When the change of flame level required by the thermostat involves more than one level, this option makes the change step by step, with a delay of 10 seconds between each change of flame level.

To enable this option, select Yes . To disable it, select No .

Ember bed : this option enables or disables the ember bed output. To enable it, select Yes .

To disable it, select No .

Sounder : This option enables or disables the sounder option. To enable it, select Yes . To disable it, select No .

Safety temp : This temperature is the maximum permitted room temperature. If the remote detects that the temperature is higher than the Safety temp, the appliance is switched off.

This temperature can never be set higher than 40°C (104°F). The possible range of values is 25-40°C (77-104°F).

Channel : There are three different channels available: A, B and C. A change of channel should be done if communication is no good, and only after pairing has been done. Never try to do channel change and a pairing at the same time. To change the channel just press

Select , choose one of the channels and then reset the control unit by disconnection the power supply for a short period. Afterwards the connection between the remote and the control unit will be re-established. This process can take 10 seconds.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

20.0

Sounds And Smells:

Note: Each time the fire is lit from cold the glass will fog up with condensation. This is normal and the condensation will disappear within a few minutes once the glass heats up.

20.1

Sounds:

It is possible that you will hear some sounds from your gas appliance. This is perfectly normal due to the fact that there are various types of materials used within your appliance.

Listed below are some examples. These are all normal operating sounds and should not be considered as defects in your appliance.

Gas Control Valve:

As the gas control valves turn ON and OFF, a dull clicking sound may be audible, this is normal operation of a valve. When the fire is switched off after being run for a while, there may be popping and fluttering noises as the residual gas in the burner burns away. These are normal and should be no cause for concern.

Unit Body/Firebox:

Different types and thickn ess‟ of steel will expand and contract at different rates resulting in some “dull drumming” and “ticking” sounds being heard throughout the cycling process.

20.2

Smells:

The first few times the unit is operated, the unit may release an odour and the flames may appear orange caused by the curing of the paint, the burning off of the starch in the gas coals and the oils in the metal and finishes. This is a temporary curing process which will disappear with use.

A deposit on the inside of the glass, caused by the starch in the coals may appear as a build up after several uses. If this film is not removed, it may bake on and may become difficult to remove. When the glass is cold, remove it (see section 11.0) and clean the inside with a non-abrasive cleaner.

DO NOT ATTEMPT TO CLEAN THE GLASS WHILE IT IS HOT. NEVER OPERATE THE UNIT

WITH THE GLASS REMOVED.

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

21.0 Annual Service Check:

The ST900 Fireplace should be serviced annually to ensure it continues to operate in a safe manner. This annual service check should involve the following

Replace thermocouple

Check glass assembly gasket

Clean pilot and main burner jets

Paint firebox [if required]

Inspect flue system [if possible]

General clean and inspection

22.0

Installation Check List:

1

2

Fuel Bed Media correctly installed as per manual

Operating pressure checked with fire running on full (high flame setting) and all other gas appliances in the house switched on.

3 Flue restrictor fitted if required, flame picture verified 15 minutes after start-up.

4 Ensure the pilot frame is clearly visible and free from loose material (coals).

5 After Gib installation, fire run on high for 60 minutes with house doors and windows open to clear smell of paint and oils initial burn.

6

7

8

Fire and flue clearances comply with these instructions.

Fire securely fixed to wall.

Leak test all joints and pressure test points. Soapy water and drop test done on pipe work.

9

10

11

12

13

Remote cradle screwed to wall.

House holder has been shown how to operate fire.

User manual has been left out for house holder, installer has filled in their own details and fire serial number into warranty card.

Inform the customer that the fire may continue smelling for a while after installation depending on frequency & duration of use

Given house holder Plumbing Industry Commission Compliance

Certificate.

23.0

WARRANTY TERMS & CONDITIONS:

630156_5_Manual_Installation-Service_ST900_NZ_R-emotion

Provided that the Product is installed as per ESCEA’s Installation Manual and the step by step warranty procedure has been followed as per instructions issued by ESCEA, (documented in the Agent Manual), and the product is operated and maintained in accordance with ESCEA operating and maintenance instructions, then for the first period of twelve (12) months from the date of purchase ESCEA will pay the cost of repairing or replacing any part of the

Product that is deemed by ESCEA to be faulty.

For the second period of twelve (12) months from the date of purchase ESCEA will supply replacement parts only, without charge.

Parts and Labour for the first twelve (12) months: a) b)

ESCEA, at its sole discretion, may modify, adjust, repair, or replace the faulty products. The warranty period on parts and labour shall be for twelve (12) months from the date of purchase.

Labour costs will only be reimbursed when ESCEA specified procedure has been followed, and ESCEA has authorised service work before it was carried out.

Parts Only for the second twelve (12) months: a) ESCEA, at its sole discretion, will provide replacement parts to the Distributor, retailer or repair service.

Faulty parts MUST be returned to ESCEA. The parts only warranty period shall be for twelve (12) months and will commence twelve (12) months after the acceptance date of the Products by the ESCEA retailer.

General Terms and Exclusions:

1. All repairs made within the Limited Warranty period shall be covered by this Limited Warranty for a period of three (3) months from the date of completion of the repair, or for the remainder of the overall Limited

Warranty period, whichever is the longer.

2.

3.

4.

5.

6.

7.

If the buyer or any other party modifies any part of the Product within the Limited Warranty period without the prior written consent of ESCEA then the Limited Warranty shall be void. ESCEA may, at its sole discretion, decide that the Limited Warranty is void in relation to any part of the product, which has been modified.

ESCEA must be notified of all claims under this Limited Warranty as soon as possible, but in any event not later than two (2) weeks of the claimant becoming aware of the circumstance giving rise to the claims.

No ESCEA Distributor, retailer, employee or other third party is authorized to make any modification, extension, or addition to this Limited Warranty, whether verbal or written.

ESCEA reserves the right to discontinue products or make substitutions, in such event, the buyer may receive a substitute product or a cash refund at ESCEA’S sole discretion, if a replacement for the product covered by this Limited Warranty is no longer available.

ESCEA is not responsible for damage arising from failure to follow instructions for the product’s installation, maintenance and permitted and proper use. The Limited Warranty does not cover damage caused by use with non-ESCEA products or damage caused by accident, abuse, misuse, weather, fire, flood, earthquake or other external causes. Products where an ESCEA serial number has been removed or defaced, cosmetic damage, including but not limited to scratches, and normal fair wear and tear are not covered as well.

This warranty does not cover installation of the fire into wet areas such as bathrooms or areas of very high humidity.

  emotion   NZ   R ‐ ST900   Service al   Manu   630156

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

  emotion   NZ   R ‐ ST900   Service al   Manu   630156

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

  emotion   NZ   R ‐ ST900   Service al   Manu   630156

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

  nce  

  ical temperature es  

    start soft   Active

  valve   to   e     cabl cable ly  

  spark

  supp

Connect

Connect n   atio y  

 

  ectl handset igur

  manual) is   corr conf

  a   shorter te  

 

  from cable

  remo again  

  in   the lation

  l  

  signal

  tro

  ol

  in   the

  con instal   contr   g   the   channel

  the   pairing touch touch

  (see

  the  

 

 

  of   n ptio batteries

 

 

  rece ance making changin Try  

Try  

Change

Check dist menu

Ensure connected

Change

  to   valve     box   m battery   fro   cable   earth

    unit ol   in   contr batteries

    unit ol   contr

  new  

Place change

Connect

Solution

  issu al on ‐ find   operati fault   and  

  emotion   NZ   R ‐ ST900   Service al   Manu   630156 diagnose  

 

 

the  

  secure   it   is  

  so   that   the  

  up    lining until facia

 

  by   ion   into   posit   down

  of   the   fire.

  Lift   the  

  to   the   fire.

  Do   this is   set   too  

 

  flame drop attaching

  and   let   it  

  on   the   sides

  for   receptacles, receptacles hooks

 

  four  

 

  the  

  the

  these movement.

  with above uses from

  hooks

  and   free  

  are  

 

The   fascia

Facia

 

Re

fit

 

the

  facia hooks

 

  device failure

  that   the   pilot

  flame

 

  on   the   indicates thermocouple).

impinges

  red,   as   this  

  correctly

  the   life   of   the   glow

  d   not  

  flame joins/unions.

  system

   screw.

  point

 

  the   test  

  and   gas  

  and   replace points reduce pilot

  and   will  

  shoul

  that   the   Check

(thermocouples high

  emotion

 

    the

  manometer.

media, reversing the   gas    

  NZ   R ‐ again

ST900

 

 

  a   d using

 

  Fuel   bed

  by  

Service

 

Burner, point al   Manu assembled

  assemble re   test   pressu   at  

  fire   fully

.

  

  and   the

  replaced

  

  plate data     re   to   specifications.

against batteries completed pressure

 

  be   re ‐

  Cover, should

Connections

 

Pilot

  removed).

 

 

  the

  the   fire

Tray   (if   replacing s,  

  complete,

  step

  is  

Control work

  and  

  in   previous

 

Power

  service

 

630156  

  done

  the  

  assembly,

establish assemble Re

Once actions

Glass

  

  

  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14.0

 

 

 

 

 

 

13.0

12.0

  emotion

  clean s.

  mm

25 mm

25 mm

50 mm

25

  of  

 

  adjacent blockages

25mm

  as  

  within

  l  

 

  into   the components, material potentia

  any   flue  

  or  

‐ locked

  or   twist damage above

  is  

 

  objects

 

  it   for

 

  may  

  Do

 

 

  all port

 

  to

 

 

  uple.

  black

  you

  and

  air.

dusting d jet

 

 

  matt order burner in   or   the   firebox

 

 

  thermoco

  tools mpresse down blocking co

  the

 

  or

  Remove

Flue wiping temperature

  clean

  drill   cleaning

 

  e by

  to

  mm 25 combustible component

50mm undertaken inspect

    be mm

25 d

 

   

  of   the   fire   shoul

 

  or  

  you  

  a   rag

  the   surface.

with  

 

Inspection:

,

  removed surfaces.

  and   mm

25

 

 

  Cover it   ng

 

  areas

  of   the   inside

  is   a   risk   of  

  high  

  on   the   there suitable paint

  as   burner,   on   the  

  To   do   this,   use   a  

  to   the     or   damage paint paint.

  Do   not   put   any  

  the    

  are   any   scrapes touch up   to   riat approp access micro accessible.

a  

 

 

  now

  using is     now   have other as  

  jet

 

  down removed riate

  any   soot   from

Pilot this   by   wipi

  the   there accessible clean

and

    general

Clean

 

ral

mm

50

  or  

  below: e   components

  diagram below   flu

    in   the

  side   or  

  flue     system,

  are   no   each there  

  Ensure  

  to   the   flue   cowl).

access

  and   that

  the  

  If   you   have

(including components, either shown

 

 

:

possible]

such burner

Jets:

 

  : the  

[if

  method

 

 

 

required] [if

   

Flue

 

System

 

Gene

Inspect

paint.

Firebox

wish

 

Paint

remove

Thermocouple:

Burner

  approp burner

Main and

   

 

Pilot

  an  

  the   it   using

With

 

With

Clean

Clean

If  

A  

  

  

7.0

  

8.0

  

9.0

  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11.0

 

 

 

 

  NZ   R ‐   ST900 al   Service 630156   Manu

  emotion   NZ   R ‐ ST900   Service al   Manu   630156

 

  emotion

 

 

  care   firebox)

  taking

  the   two t   of   the   remove below,     as   shown

  To   do   this,  

  fron   grill   at   the

  upwards, thermocouple.

  long (The

  below.

  and   lift   shown

 

  and  

  Cover

  as  

Pilot

Cover pilot firebox

 

 

  the  

  the  

  the remove clean

  side   of   the   Pilot

  to  

  and   damage   or   need either access not   to   scrape

  on  

  to  

You   will   also   order in   screws

  

  off   the   jet   on   

  

  the   left   side holding  

!

 

extreme

 

care

screw burner

  lifting then

  the  

  the  

,   and  

 

 

Use

 

fragile

sliding

 

very

  and  

  to   the   right

  by   removing

  burner upwards shown side.

 

 

  the  

  as   hand   burner place remove the   right of   the   it   in  

  Next

 

are

   

logs The

 

driftwood

  

   somewhere stones

  

  white completely part.

   

  down

  side  

  and  

 

 

  any

  to   the cooled

(Driftwood   remove

 

  or  

  have carefully touch

 

 

  bed   media them   damaged.

place

  not   be  

  all   fuel

  and  

  to  

  contents ng attempti

  the   firebox

  remove they   will

First   or   Coals)

Ensure before

 

Firebox

 

Contents:

 

Remove

  NZ   R ‐   ST900 al   Service 630156   Manu

4.0

  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

  emotion cylinders,

 

 

  be  

  to  

  of  

  you

  to  

  it.

  towards

 

  lift    it   when   sheet to   remove glass

    a

 

  the  

 

  or taken simply  

  be   from  

  away newspaper it.

  facia, assembly always

  attempting re   glass

 

 

  some     upon

  Lift   the

  you   and   then

  hook.

 

  it   flat

  the towards coverings place eath w  

  floor

  and  

 

  belo undern your supports

 

 

  shown

 

  frame protect

  befo   completely   has   cooled   assembly

  the   ld   to   remove remove

  shou

  To  

Care

 

 

  must supply

  by   removing isolated   can   be  

  the   gas   off   at   the   the   gas     ing

  on   the   fire, er   turn

  Power valve.

 

  is   done

  by   eith work  

   hooks.

attempting isolation isolated

  you.

pack.

nance towards pull       and

  to   the   fire   by   four  

  re     befo

  cooled   hooks locating facia   has facia.

Assembly:

  glass glass

 

  to  

  the  

  the  

  four Pull   the

  the  

 

  15 ‐

 

  the

  the  

  facia The cardboard

Glass

20mm,

  attaches clear release

Ensure

Remove

handling upwards

Ensure

 

   

Facia:

 

the

 

  battery  

  or   at   the   from   the   appliance

  or   shut   off.

  Gas   can   be  

  and   mainte service   any   meter batteries the   at   the  

Before isolated

 

Remove

 

Supply:

 

and

 

Gas

   

Power Isolate 1.0

  

2.0

  

3.0

  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

  NZ   R ‐   ST900 al   Service 630156   Manu

  emotion

 

15.0

5.0

 

4.0

 

3.0

 

2.0

 

1.0

 

 

 

9.0

 

8

.0

 

7.0

 

6.0

 

10.0

11.0

14.0

 

13.0

 

12.0

 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

     

 

 

 

 

 

 

  electrical

 

 

  gas   and  

  

   

  facia   assemble establish Re ‐

Re ‐ connections

Replace

 

  

   

 

   

  jet   

   

 

possible]

inspection burner

required]

 

 

 

[if

  main assembly ermocouple

  and   system

 

[if

  er   th

  and  

 

  clean  

  flue glass pilot

  burn

 

  firebox  

Check

Clean

Clean

Paint

Inspect

General

‐ 

‐ 

‐ 

‐ 

‐ 

 

required]

 

 

 

    supply

 

   

   

Tray  

[if

 

 

  and   gas  

  assembly

  contents

 

  firebox glass facia

 

 

  Control

 

  power

       

Remove

Remove

Remove

Remove

Isolate

TROUBLESHOOTING

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐   

 

 

 

 

 

‐ 

‐ 

‐ 

 

 

 

 

ASSEMBLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SERVICE

 

 

 

 

 

RE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ASSEMBLY DIS

 

 

 

 

Contents:

  NZ   R ‐ ST900   Service al   Manu   630156

z ea.co.nz

info@esc scea.co.n

w.e

ail: ww se visit ealer plea r or d

NZ, Ph: +64 3 479 0302, em ea distributo sc d, PO Box 5277 Dunedin t details of your local e

is carried out on this d trained person ce operation d every 12 months

Gas and electricity supply MUST be isolated before any servi ce be service

Any service operation should be carried out only by a suitably qualified an

It is recommended that this applian

For contac tured by: Escea Lt appliance.

Manufac

Important

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NZ EDITION

 

ST900 Direct Vent Gas Fireplace

Service Guide

  emotion   NZ   R ‐ ST900   Service al   Manu   630156