Empire Comfort Systems DVP36DP31N-2 Installation Instructions And Owner's Manual


Add to my manuals
76 Pages

advertisement

Empire Comfort Systems DVP36DP31N-2 Installation Instructions And Owner's Manual | Manualzz

EMPIRE

INSTALLATION INSTRUCTIONS

AND

Comfort Systems

OWNER’S MANUAL

DIRECT VENT GAS FIREPLACE

HEATER

Direct Vent Zero Clearance Gas

Fireplace Heater

MILLIVOLT STANDING PILOT

DVP36DP31(N,P)-2

DIRECT IGNITION

DVP36DP51N-1

INTERMITTENT PILOT

DVP36DP71(N,P)-3

REMOTE RF

DVP36DP91(N,P)-3

UL FILE NO. MH30033

GAS-FIRED

Installer: Leave this manual with the appliance.

Consumer: Retain this manual for future reference.

WARNING: If not installed, operated and maintained in accordance with the manufacturer’s instructions, this product could expose you to substances in fuel or from fuel combustion which can cause death or serious illness.

This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by state or local codes.

This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.

WARNING: If the information in these instruc tions are not followed exactly, a fire or explosion may result causing property damage, personal in jury or loss of life.

— Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

— WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.

• Do not touch any electrical switch; do not use any phone in your building.

• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.

• If you cannot reach your gas supplier, call the fire department.

— Installation and service must be performed by a qualified installer, service agency or the gas sup plier.

Page 1

TABLE OF CONTENTS

Section Page

IMPORTANT SAFETY INFORMATION ..................................................................................................................................... 3

SAFETY INFORMATION FOR USERS OF LP GAS ................................................................................................................. 4

REQUIREMENTS FOR MASSACHUSETTS ............................................................................................................................ 5

INTRODUCTION ....................................................................................................................................................................... 6

SPECIFICATIONS ..................................................................................................................................................................... 7

VENT SYSTEM IDENTIFICATION ............................................................................................................................................ 8

SPECIAL VENT SYSTEMS ....................................................................................................................................................... 8

FIREPLACE DIMENSIONS ....................................................................................................................................................... 9

CLEARANCES ........................................................................................................................................................................ 10

LOCATING FIREPLACE ..........................................................................................................................................................11

GAS SUPPLY .......................................................................................................................................................................... 12

INSTALLATION ..................................................................................................................................................................13-16

VENTING FIREPLACE - TOP ............................................................................................................................................ 17-20

EXAMPLES - TOP VENT RUN ............................................................................................................................................... 21

REAR VENT CONVERSION ................................................................................................................................................... 22

VENTING FIREPLACE - REAR .............................................................................................................................................. 23

EXAMPLES - REAR VENT RUN ............................................................................................................................................. 24

VENT CLEARANCES .............................................................................................................................................................. 25

FRAMING AND FINISHING ............................................................................................................................................... 26-27

TERMINATION CLEARANCES ............................................................................................................................................... 28

HORIZONTAL TERMINATION ................................................................................................................................................ 29

VERTICAL TERMINATION .................................................................................................................................................30-31

DVVK-4FV DIRECT VENT TERMINATION KIT ................................................................................................................. 32-38

DVVK-4F FLEX VENT INSTRUCTIONS - TOP VENT ONLY ................................................................................................. 39

DVVK-4RE VENT KIT INSTALLATION INSTRUCTIONS .................................................................................................. 40-42

PROPANE/LP GAS CONVERSION ........................................................................................................................................ 43

LOG PLACEMENT (4 LOG SET) ............................................................................................................................................ 44

MILLIVOLT SYSTEM OPERATING INSTRUCTIONS ........................................................................................................ 45-46

MILLIVOLT SYSTEM STANDING PILOT WIRING DIAGRAM ................................................................................................ 47

MILLIVOLT SYSTEM STANDING PILOT LIGHTING INSTRUCTIONS .................................................................................. 48

MILLIVOLT SYSTEM STANDING PILOT TROUBLESHOOTING ........................................................................................... 49

DIRECT IGNITION LIGHTING INSTRUCTIONS .................................................................................................................... 50

DIRECT IGNITION WIRING DIAGRAM .................................................................................................................................. 51

OPTIONAL REMOTE CONTROL ............................................................................................................................................ 51

INITIAL START UP GAS LINE PURGE ................................................................................................................................... 52

DIRECT IGNITION TROUBLESHOOTING ............................................................................................................................. 52

PROPANE/LP GAS CONVERSION ........................................................................................................................................ 53

IPI ELECTRONIC SYSTEM OPERATING INSTRUCTIONS .................................................................................................. 54

IPI ELECTRONIC SYSTEM WIRING DIAGRAM .................................................................................................................... 55

INTERMITTENT PILOT LIGHTING INSTRUCTIONS ............................................................................................................. 56

INTERMITTENT PILOT CONTROL SYSTEM TROUBLESHOOTING .............................................................................. 57-59

RF OPERATING INSTRUCTIONS .......................................................................................................................................... 60

RF MAINTENANCE INSTRUCTIONS ..................................................................................................................................... 61

RF WIRING DIAGRAM ............................................................................................................................................................ 62

RF STANDING PILOT LIGHTING INSTRUCTIONS ............................................................................................................... 63

MAINTENANCE AND SERVICE ........................................................................................................................................ 64-65

PARTS VIEW ........................................................................................................................................................................... 66

PARTS LIST .......................................................................................................................................................................67-68

MASTER PARTS DISTRIBUTOR LIST ................................................................................................................................... 69

HOW TO ORDER REPAIR PARTS ......................................................................................................................................... 69

FBB4 VARIABLE SPEED BLOWER INSTALLATION ........................................................................................................ 70-71

JUNCTION BOX WIRING INSTALLATION INSTRUCTIONS ................................................................................................. 72

BRICK LINER INSTALLATION INSTRUCTIONS .................................................................................................................... 72

ACCESSORIES....................................................................................................................................................................... 73

QUICK REFERENCE GUIDE ............................................................................................................................................. 74-75

WARRANTY ............................................................................................................................................................................ 76

Page 2 31451-2-1013

IMPORTANT SAFETY INFORMATION

Before enclosing the vent pipe assembly, operate the appliance to ensure it is venting properly.

DO NOT OPERATE THIS APPLIANCE WITHOUT GLASS FRONT PANEL INSTALLED

DANGER : Indicates a hazardous situation which, if not avoided, will result in death or serious injury.

WARNING : Indicates a hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION : Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.

NOTICE : Addresses practices not related to personal injury.

• If this appliance is installed directly on carpeting, tile or other combustible material other than wood flooring the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance.

The base referred to above does not mean the fireproof base as used on wood stoves. The protection is for rugs that are extremely thick and light colored tile.

• Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition.

• Young children should be carefully supervised when they are in the same room as the appliance.

• Clothing or other flammable material should not be placed on or near the appliance.

• Adequate accessibility clearances for servicing and proper operation.

• This appliance must not share or be connected to a flue serving a separate solid-fuel burning appliance.

• Keep the area around your appliance clear of combustible materials, gasoline and other flammable vapor and liquids.

• Under no circumstances should any solid fuels (wood, coal, paper or cardboard etc.) be used in this appliance.

• The flow of combustion and ventilation air must not be obstructed in any way.

• Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies.

• The glass front or any part removed for servicing the appliance must be replaced prior to operating the appliance. Work should be done by a qualified service person.

• Keep burner and control compartment clean.

• Vent cap is hot while fireplace is in operation.

• Installation and repair should be done by a QUALIFIED

SERVICE PERSON. The appliance should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding materials, etc. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.

• DO NOT put anything around the fireplace that will obstruct the flow of ventilation air.

• Clearance in accordance with local installation codes and the requirements of the gas supplier.

31451-2-1013

• DO keep the appliance area clear and free from combustible material, gasoline and other flammable vapors and liquids.

• DO examine venting system periodically and replace damaged parts.

make a periodic visual check of pilot and burners.

Clean and replace damaged parts.

• CAUTION: The glass used in your fireplace is tempered glass. If the glass is cracked or damaged in any way, it should be replaced only with a complete glass frame assembly from Empire. See parts list on Pages 67 and 68 for ordering.

• DO NOT use this fireplace if any part has been under water. Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water.

• Any safety screen or guard removed for servicing an appliance must be replaced prior to operating the appliance.

Page 3

SAFETY INFORMATION FOR USERS OF LP GAS

Propane (LP-Gas) is a flammable gas which can cause fires and explosions. In its natural state, propane is odorless and colorless. You may not know all the following safety precau tions which can protect both you and your family from an accident. Read them carefully now, then review them point by point with the members of your household. Someday when there may not be a minute to lose, everyone’s safety will depend on knowing exactly what to do. If, after read ing the following information, you feel you still need more information, please contact your gas supplier.

LP-GAS WARNING ODOR

If a gas leak happens, you should be able to smell the gas because of the odorant put in the LP-Gas.

That’s your signal to go into immediate action!

• Do not operate electric switches, light matches, use your phone.

Do not do anything that could ignite the gas.

• Get everyone out of the building, vehicle, trailer, or area. Do that IMMEDIATELY.

• Close all gas tank or cylinder supply valves.

• LP-Gas is heavier than air and may settle in low areas such as basements. When you have reason to suspect a gas leak, keep out of basements and other low areas. Stay out until firefighters declare them to be safe.

• Use your neighbor’s phone and call a trained LP-Gas service person and the fire department. Even though you may not continue to smell gas, do not turn on the gas again. Do not re-enter the building, vehicle, trailer, or area.

• Finally , let the service man and firefighters check for escaped gas. Have them air out the area before you return. Properly trained LP-Gas service people should repair the leak, then check and relight the gas appliance for you.

NO ODOR DETECTED - ODOR FADE

Some people cannot smell well. Some people cannot smell the odor of the chemical put into the gas. You must find out if you can smell the odorant in propane.

Smoking can decrease your ability to smell. Being around an odor for a time can affect your sensitivity or ability to detect that odor. Sometimes other odors in the area mask the gas odor. People may not smell the gas odor or their minds are on something else. Thinking about smelling a gas odor can make it easier to smell.

The odorant in LP-Gas is colorless, and it can fade under some circumstances.

For example, if there is an underground leak, the movement of the gas through soil can filter the odorant.

Odorants in LP-Gas also are subject to oxidation. This fading can occur if there is rust inside the storage tank or in iron gas pipes.

The odorant in escaped gas can adsorb or absorb onto or into walls, masonry and other materials and fabrics in a room. That will take some of the odorant out of the gas, reducing its odor intensity.

LP-Gas may stratify in a closed area, and the odor intensity could vary at different levels. Since it is heavier than air, there may be more odor at lower levels. Always be sensitive to the slightest gas odor. If you detect any odor, treat it as a serious leak. Immediately go into action as instructed earlier.

SOME POINTS TO REMEMBER

• Learn to recognize the odor of LP-Gas.

Your local LP-Gas

Dealer can give you a “Scratch and Sniff” pamphlet. Use it to find out what the propane odor smells like. If you suspect that your LP-Gas has a weak or abnormal odor, call your LP-Gas

Dealer.

odor fade. If such conditions are suspected to exist, a periodic sniff test of the gas is advisable. If you have any question about the gas odor, call your LP-Gas dealer. A periodic sniff test of the LP -Gas is a good safety measure under any condition.

• If you are not qualified, do not light pilot lights, perform service, or make adjustments to appliances on the LP-Gas system. If you are qualified, consciously think about the odor of LP-Gas prior to and while lighting pilot lights or performing service or making adjustments.

• If, at any time, you do not smell the LP-Gas odorant and you think you should, assume you have a leak. Then take the same immediate action recommended above for the occasion when you do detect the odorized LP-Gas.

• Sometimes a basement or a closed-up house has a musty smell that can cover up the LP-Gas odor. Do not try to light pilot lights, perform service, or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP-Gas.

• Odor fade, due to oxidation by rust or adsorption on walls of new cylinders and tanks, is possible. Therefore, people should be particularly alert and careful when new tanks or cylinders are placed in service. Odor fade can occur in new tanks, or reinstalled old tanks, if they are filled and allowed to set too long before refilling. Cylinders and tanks which have been out of service for a time may develop internal rust which will cause

• If you experience a complete “gas out,” (the container is under no vapor pressure), turn the tank valve off immediately. If the container valve is left on, the container may draw in some air through openings such as pilot light orifices. If this occurs, some new internal rusting could occur. If the valve is left open, then treat the container as a new tank. Always be sure your container is under vapor pressure by turning it off at the container before it goes completely empty or having it refilled before it is completely empty.

Page 4 31451-2-1013

REQUIREMENTS FOR MASSACHUSETTS

For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the

Commonwealth and where the side wall exhaust vent termination is less than seven feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than 1/2 inch in size,

INSTALLATION OF CARBON MONOXIDE

DETECTORS.

At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty days to comply with the above requirements; provided, however, that during said thirty day period, a battery operated carbon monoxide detector with an alarm shall be installed.

2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/

UL 2034 listed and IAS certified.

4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.

(b) EXEMPTIONS: The following equipment is exempt from

248 CMR 5.08(2)(a)1 through 4:

1. The equipment listed in Chapter 10 entitled

“Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS - GAS

EQUIPMENT VENTING SYSTEM NOT PROVIDED.

When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies

“special venting systems”, the following requirements shall be satisfied by the manufacturer:

1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and

2. The “special venting systems” shall be Product

Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instruction.

(e) A copy of all installation instructions for all Product

Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

31451-2-1013 Page 5

INTRODUCTION

Instructions to Installer

1. Installer must leave instruction manual with owner after installation.

2. Installer must have owner fill out and mail warranty card supplied with the fireplace.

3. Installer should show owner how to start and operate the fireplace.

This direct vent gas fireplace heater is designed to operate with all combustion air being siphoned from the outside of the building and all exhaust gases expelled to the outside of the building. The information contained in this manual pertains to all models and gas control systems unless otherwise noted.

WARNING

This unit is not for use with solid fuels.

Appliance Certification

This fireplace is design certified in accordance with American

National Standard/CSA Standard ANSI Z21.88/CSA 2.33 and by

Underwriters Laboratories as a Direct Vent Gas Fireplace Heater and shall be installed according to these instructions.

Consult your local building code agency, prior to installation, to ensure compliance with local codes-including permits and inspections.

The fireplace, when installed, must be electrically grounded in accordance with local codes or, in absence of local codes, with the

National Electric Code ANSI/NFPA 70 or Canadian Electric code,

CSA C22.1, if an external electrical source is utilized.

These models may be installed in a bedroom or bed-sitting room in the U.S.A. and Canada.

Qualified Installing Agency

Installation and replacement of gas piping, gas utilization equipment or accessories and repair and servicing of equipment shall be performed only by a qualified agency. The term “qualified agency” means any individual, firm, corporation or company which either in person or through a representative is engaged in and is responsible for

(a) the installation or replacement of gas piping or (b) the connection, installation, repair or servicing of equipment, who is experienced in such work, familiar with all precautions required and has complied with all the requirements of the authority having jurisdiction.

State of Massachusetts: The installation must be made by a licensed plumber or gas fitter in the Commonwealth of

Massachusetts.

The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1/NFPA

54* Natural Gas and Propane Installation Code, or CSA B149.1 in

Canada. *Available from the American National Standards Institute,

Inc. 11 West 42nd St., New York, N.Y. 10036.

WARNING

ANY CHANGE TO THIS FIREPLACE OR ITS CONTROLS

CAN BE DANGEROUS.

Improper installation or use of the fireplace can cause serious injury or death from fire, burns, explosions, or carbon monoxide poisoning.

Any alteration of the original design, installed other than as shown in these instructions or use with a type of gas not shown on the rating plate is the responsibility of the person and company making the change.

Important

All correspondence should refer to complete Model Number, Serial

Number and type of gas.

High Altitude

When installing this unit at an elevation above 2000 feet (in the

United States) it may be necessary to decrease the input rating by changing the existing burner orifice to a smaller size. Generally, input should be reduced 4 percent for each 1000 feet above sea level. However, if the heating value of the gas has been reduced, this general rule may not apply. Check with local gas utility for proper orifice size identification.

Canadian High Altitude

Altitude: 0-4500 feet (0-1370 m)

When installing this unit at an elevation above 4500 feet (in Canada), check with local authorities.

Consult your local gas utility for assistance in determining the proper orifice for location.

Preparation

This direct vent gas fireplace and its components are tested and safe when installed in accordance with this Installation Manual.

Report to your dealer any parts damaged in shipment, specifically check glass condition. Do not install unit with damaged, incomplete, or substitute parts. Read all instructions before starting installation and follow these instructions carefully during installation to insure maximum benefit and safety. Failure to follow them will void your warranty and may present a fire hazard.

The warranty will be voided by, and the warranter disclaims any responsibility for the following actions:

• Installation of any damaged fireplace or vent system component.

• Modification of the fireplace or direct vent system.

• Installation other than as instructed by Empire Comfort Systems,

Inc.

• Improper positioning of the logs, glass door or decorative rock.

• Installation and/or use of any component part not manufactured or approved by manufacturer.

Page 6 31451-2-1013

SPECIFICATIONS

DVP36 Nat Models

Input Btu/hr Maximum

Btu/hr Minimum (millivolt only)

KWH (Maximum)

(Minimum)

Orifice

Air Shutter Opening

25,000

18,000

7.3

5.2

#41 (P-256)

1/8" (DVP36DP(3,7,9))

1/4" (DVP36DP5)

DVP36 LP Models

Input Btu/hr Maximum

Btu/hr Minimum (millivolt only)

KWH (Maximum)

(Minimum)

Orifice

Air Shutter Opening

DVP36 Nat and LP Models

Height without standoff

Width

Depth

Gas Inlet Shutoff Valve (pipe)

27,000

21,000

7.9

5.2

1.55mm (P-258)

FULL OPEN

34 3/4"

39"

19 7/8"

1/2" NPT

NOTICE : Air shutter settings are factory minimum settings. Some venting configurations may require minor air shutter adjustments for optimum performance.

Remote Control Options

& Accessories

FRBC

FRBTC

TRW

TMV

FWS-1

FREC

Description

Millivolt/IP Battery Remote ON/OFF

Millivolt/IP Battery Remote Thermostat

Millivolt/IP Wireless Wall Thermostat

Millivolt/IP Reed Switch Wall Thermostat

Direct Ignition/Millivolt/IP Wall Switch

Electric Remote

Venting

Options

DVVK-4TSP

(DVVK-4TS)

DVVK-4TP

(DVVK-4T)

DVVK-4RP

(DVVK-4R)

Description

Top Vent Kit (Horizontal) - 5" to 7" wall thickness

Top Vent Kit (Horizontal) - 8" to 11" wall thickness

Rear Vent Kit (Horizontal) - 5" to 7" wall thickness

DVVK-4VP

(DVVK-4V)

Vertical Vent Kit

DVVK-4F Horizontal Flex Vent Kit (4' Flex)

DVVK-4RE Horizontal Round Termination wall thickness (up to 13 3/4")

DV822 Vinyl Siding Kit for DVVK-4RE

DVVK-4FV Vertical Flex Vent Kit

DVEK-10

DVEK-25

10' Vent Extension Kit

25' Vent Extension Kit

NOTICE : Rear vent installation can only be vented on natural gas.

31451-2-1013 Page 7

VENT SYSTEM IDENTIFICATION

Begin the vent system installation by selecting the type of venting to be installed and the path that it will take. Verify that clearances are met throughout the path of the venting system. Determine if the fireplace is to be vented out the top or out the rear.

NOTICE: Some fireplaces cannot be vented out the rear of the fireplace.

Determine how the vent system will be terminated out the side of the house or through the roof. Verify clearances for the termination.

When selecting a vent system for use with the fireplace, refer to the “Special Vent Systems” section in this manual to determine what systems are acceptable. Check all clearances and venting components. Identify if any problems existing in the vent system.

Use Figure 21 on page 17 for top venting, or Figure 33 on page

23 for rear venting to eliminate issues after installation. Check pipe diameter on vent system and fireplace to verify the size is the same.

NOTICE : All outer connection joints must be sealed with aluminum tape, screws or silicone sealant rated above

300°F/149°C. The inner flue joints do not require any sealant.

*Note: If using three 90° elbows during horizontal termination, see Figure 31.

Figure 1

Special Venting Components (Simpson Duravent)

See Empire Comfort Systems Retail Price List for Simpson Duravent part numbers and pricing.

DVVK-4VP

(DVVK-4V)

Special DV Vent Kits

Available from Empire Comfort Systems, Inc. dealers.

Direct-Vent Fireplace Vent Kit - Vertical, Includes 46DVA-VCH,

46DVA-SC and 46DVA-F6

DVVK-4TP

(DVVK-4T)

Direct-Vent Fireplace Vent Kit for Top Vent, Thru-the-wall,

8 to 11 inch wall thickness, Includes 46DVA-09, 46DVA-08A,

46DVA-HC, 46DVA-E90 and 46DVA-WT

DVVK-4TSP

(DVVK-4TS)

Direct-Vent Fireplace Vent Kit for Top Vent, Thru-the-wall,

5 to 7 inch wall thickness, Includes 46DVA-06, 46DVA-HC,

46DVA-E90 and 46DVA-WT

DVVK-4FV Direct-Vent Fireplace Vertical Flex Vent Kit

DVVK-4RE

Direct-Vent Fireplace Vent Kit, Thru-the-wall, 5 to 13 3/4 inch wall thickness

Notice: Rear vent installation can only be vented on natural gas.

SPECIAL VENT SYSTEMS

The following vent systems are acceptable for use with the DVP36 series fireplaces:

Simpson Duravent® GS 4" - 6 ⅝"

American Metal Products 4" - 6 ⅝"

Selkirk Direct-Temp® 4" - 6 ⅝"

Security Secure Vent® 4" - 6 ⅝"

Excel DV Venting 4” - 6 ⅝”

Empire Horizontal Round Termination Kit DVVK-4RE

Empire Flexvent Kit DVVK-4F

Empire Flexvent Kit DVVK-4FV Vertical Flex Vent Kit

Page 8 31451-2-1013

31451-2-1013

LEFT SIDE VIEW

FIREPLACE DIMENSIONS

FRONT VIEW

RIGHT SIDE VIEW

C

D

H

A

GAS LINE ACCESS

VENT COLLAR

STANDOFFS

NAILING

FLANGES

GLASS

FRAME

ASSEMBLY

GAS LINE

ACCESS

RATING PLATE

AND LABELS

E

B

J

I

G

C

D

E

A

B

I

J

G

H

GAS CONTROLS

AND SWITCHES

Dimension

34 3/4" (882.7 mm)

39" (990.6 mm)

19 7/8" (505 mm)

25" (635 mm)

36" (914.4 mm)

26 1/2" (673.1 mm)

37 3/4" (958.9 mm)

13 1/4" (336.6 mm)

7 1/8" (181 mm)

Figure 2

TOP VIEW

GAS LINE

ACCESS

ELECTRICAL

ACCESS

VENT COLLAR

Page 9

Clearance to Combustibles

Back

Side

0" (0 mm)

0" (0 mm)

Floor

Top Stand-off

0" (0 mm)

0" (0 mm)

Top Framing Edge 3" (76 mm)

CLEARANCES

Figure 4

Note A: See Figure 5 for maximum mantle depth.

Note B: See Figure 5 for minimum height above unit.

Figure 3

Combustible Material

No greeting cards, stockings or ornamentation of any type should be placed on or attached to the fireplace. The flow of heat can ignite combustibles.

NOTICE : Empire “Standard Mantels” are not approved for use with the DVP36DP(31,71,91)(N,P) Series fireplaces.

Mantel Chart

Figure 5

Clearances

Clearance from top of fireplace to ceiling is 36”

Clearance from side of fireplace to adjacent sidewall is 6”. See

Figure 6.

Figure 6

Page 10 31451-2-1013

LOCATING FIREPLACE

NOTICE : Island and Room Divider installation is possible as long as the horizontal portion of the vent system does not exceed 20 feet with a minimum vertical run of 8 feet. See details in Venting Section.

When you install your Direct Vent Fireplace in Room divider or Flat on wall corner positions, a minimum of 6 inches clearance must be maintained from the perpendicular wall and the front edge of the appliance.

Figure 7

31451-2-1013 Page 11

GAS SUPPLY

The gas pipeline can be brought in through the right or left side of the appliance. Consult the current National Fuel Gas Code, ANSI

Z223.1 CAN/CGA-B149 (.1 or .2) installation code.

Recommended Gas Pipe Diameter

Pipe Length Schedule 40 Pipe

Inside Diameter

Nat.

L.P.

Tubing, Type L

Outside Diameter

Nat.

L.P.

0-10ft

0-3m

11-40ft

4-12m

41-100ft

13-30m

101-150ft

31-46m

1/2"

12.7mm

1/2"

12.7mm

1/2"

12.7mm

3/4"

19mm

3/8"

9.5mm

1/2"

12.7mm

1/2"

12.7mm

1/2"

12.7mm

1/2"

12.7mm

5/8"

15.9mm

3/4"

19mm

7/8"

22.2mm

3/8"

9.5mm

1/2"

12.7mm

1/2"

12.7mm

3/4"

1.9 mm

NOTICE : Never use plastic pipe. Check to confirm whether your local codes allow copper tubing or galvanized.

NOTICE : Since some municipalities have additional local codes, it is always best to consult your local authority and installation code.

The use of the following gas connectors is recommended:

— ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing and Fittings.

— ANS Z21.45 Assembled Flexible Appliance Connectors of Other

Than All-Metal Construction

The above connectors may be used if acceptable by the authority having jurisdiction. The state of Massachusetts requires that a flexible appliance connector cannot exceed three feet in length.

Installing a New Main Gas Cock

Each appliance should have its own manual gas cock.

A manual main gas cock should be located in the vicinity of the unit.

Where none exists, or where its size or location is not adequate, contact your local authorized installer for installation or relocation.

Compounds used on threaded joints of gas piping shall be resistant to the action of liquefied petroleum gases. The gas lines must be checked for leaks by the installer. This should be done with a soap solution watching for bubbles on all exposed connections, and if unexposed, a pressure test should be made.

Never use an exposed flame to check for leaks. Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test. Never pressure test with appliance connected; control valve will sustain damage!

NOTICE : The millivolt gas controls are equipped with a captured screw type pressure test point, therefore it is not necessary to provide a 1/8” test point up stream of the control.

On direct ignition valves, hex plugs may be replaced with hose fittings for pressure checks, then reinstalled before operating fireplace.

When using copper or flex connector use only approved fittings.

The appliance and it’s individual shut off valve must be disconnected from supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5kPa).

The appliance must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5kPa).

CAUTION

If one of the procedures results in pressures in excess of 1/2 psig (14” w.c.) (3.5 kPa) on the fireplace gas valve, it will result in a hazardous condition.

Figure 8

Checking Manifold Pressures

Both Propane and Natural gas valves have a built-in pressure regulator in the gas valve. Natural gas models will have a manifold pressure of approximately 3.5” w.c. (.871kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 4.5” w.c.

(1.120kPa) for the purpose of input adjustment to a maximum of

14.0” w.c. (3.484kPa). Propane gas models will have a manifold pressure approximately 10.0” w.c. (2.49kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 10.8” w.c.

(2.68kPa) for the purpose of input adjustment to a maximum of

14.0” w.c. (3.484kPa).

Gas Supply Pressure (inches w.c.)

Minimum Normal Maximum

Natural Gas

LP (Propane)

4.5"

10.8"

7.0"

11.0"

*14.0"

*14.0"

Manifold Pressure (inches w.c.)

Normal (HI)

Natural Gas

LP (Propane)

3.5"

10.0"

* NOTICE : Remote "RF" Models - 10.5" w.c. maximum

Page 12

Figure 9

31451-2-1013

INSTALLATION

Framing and Finishing

1. Choose unit location.

2. Frame in fireplace with a header across the top. It is important to allow for finished face when setting the depth of the frame.

See Figure 10B.

3. Attach fireplace to frame using adjustable nailing flange. Preset depth to suit facing material (adjustable to 3/8”, 1/2” or 3/4” depths).

NOTICE : Fireplace must mount flush to facing material. If facing material requires more depth than 3/4”, mark and drill two 1/8” holes into fireplace side at appropriate depth. Bend standoff tabs as needed to move fireplace flush with facing material.

See Figure 10A.

4. Use eight 1/2” hex-head screws supplied in hardware package, to screw through slotted holes in nailing flange and then screw into pre-drilled holes on fireplace side. Measure from face of fireplace to face of nailing flange to determine final depth.

Vent Pipe Clearance

NOTICE : Maintain one inch of clearance around top vent pipe.

See Figure 11B.

For rear vent, maintain a minimum 1” clearance to the bottom and sides of the vent, and 3” clearance to combustibles above the vent pipe. See Figure 11A.

Figure 11A - Rear Vent

Figure 10A

Figure 11B - Top Vent

31451-2-1013

Figure 10B

Page 13

INSTALLATION

Flush Mount Mantel Installation

The fireplace must extend 3/4” beyond finished wall surface when using a flush mount mantel. Refer to Figure 12 to locate nailing flanges on fireplace sides. Mark and drill two 1/8” holes into fireplace side to mount each nailing flange. Use eight 1/2” hex-head screws supplied in hardware package to attach nailing flanges to fireplace sides.

Figure 12

Attention: When fireplace is installed in optional full cabinet mantel or corner mantel the four nailing flanges shown in Figure 12 will not be installed on the side of outer casing. The fireplace will be attached to the full cabinet mantel or corner mantel with the two nailing flanges located on the top of the outer casing assembly.

Framing

Fireplace framing can be built before or after the fireplace is set in place. Framing should be positioned to accommodate wall covering and fireplace facing material. The fireplace framing should be constructed of 2 x 4 lumber or heavier. The framing headers may rest on the fireplace standoffs. Refer to Figure 13 for minimum framing dimensions.

CAUTION

MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING

METHODS, AND WALL COVERING DETAILS BEFORE

FRAMING CONSTRUCTION BEGINS.

Framing dimension "A" includes a three inch clearance for standoffs on fireplace. After installing fireplace into framing, the finished non-combustible wall surface must cover the three inch opening above the fireplace.

NOTICE : For finishing to top of fireplace, refer to Figure 13.

"A"

"B"

"C"

Dimension

37 7/8" (962 mm)

40 3/8" (1025.5 mm)

19 7/8" (505 mm)

Figure 13

Attention: Add 3-3/4” to “A” dimensions when using a flush mantel base.

WARNING

If a base or mantel is not used and the appliance is installed directly on carpeting, tile or other combustible material other than wood flooring, it shall be installed on a metal or wood panel extending the full width and depth of the appliance. The vertical dimension in Figure 13 must be adjusted when a metal or wood panel is placed beneath the appliance.

Finishing

Finish the walls with the material of your choice. Figure 4 on page 10 shows the minimum vertical and corresponding maximum horizontal dimensions of mantels or other combustible projections above the top front edge of the fireplace.

Only non-combustible materials may be used to cover the black fireplace front.

WARNING

When finishing the fireplace never obstruct or modify the air inlet/outlet louvers in any manner. Provide adequate clearances around air openings into the combustion chamber.

CAUTION

If the joints between the finished wall and the fireplace surround

(top and sides) are sealed, a 300°F minimum sealant material must be used. These joints are not required to be sealed. Only non-combustible material (using 300°F minimum adhesive if needed), can be applied as facing to the fireplace surround.

Page 14 31451-2-1013

Flush Wall Installation

Figure 14

Combustible Surround Installation

INSTALLATION

Attention: Cold climate installation recommendation:

When installing this unit against a non-insulated exterior wall, it is recommended that the outer walls be insulated to conform to applicable insulation codes.

Vent Runs

In planning the installation for the fireplace, it is necessary to install certain components before the appliance is completely positioned and installed. These include the direct vent system, gas piping for the appliance and the electrical wiring. (If the fan option is used.)

The appliance can be mounted on any of the following surfaces:

1. A flat, hard combustible (burnable) surface.

2. A raised wooden platform.

3. Four corner supports. (Example: Four concrete masonry blocks.)

These supports must be positioned so they contact all four perimeter edges on the bottom of the unit (if allowed by local codes.

NOTICE : Fireplace must be mounted above floor surfaces. Doors will not operate properly if fireplace rests below room flooring.

NOTICE: Discard insulation and retainer when venting from the top of the fireplace. See page 22.

TOP, 90° ELBOW WITH HORIZONTAL TERMINATION

31451-2-1013

Figure 15

LP and Nat models

Figure 16

Page 15

INSTALLATION

REAR ONLY, STRAIGHT OUT THE BACK CORNER INSTALLATION TOP, 90° ELBOW TO HORIZONTAL

OUT THE WALL

Nat models only

"A"

6"

(152.4mm)

9"

(228.6mm)

12"

(304.8mm)

"B"

5 1/8" to 6 1/2"

(130mm to 165mm)

8 1/8" to 9 1/2"

(206.4mm to 241mm)

11 1/8" to 12 1/2"

(282.6mm to 317.5mm)

Figure 17

TOP, 90° ELBOW TO HORIZONTAL OUT THE WALL

A

LP and Nat models

44 7/8"

(1140mm)

B

C

D

31 3/4"

(806.5mm)

13 7/16"

(341.3mm)

63 7/16"

(1611.3mm)

Figure 19

CORNER INSTALLATION REAR, 45° ELBOW TO

HORIZONTAL OUT THE WALL

"A"

6"

(152.4mm)

9"

(228.6mm)

12"

(304.8mm)

LP and Nat models

"B"

11 1/4" to 12 3/4"

(285.8mm to 324mm)

"C"

4 3/4" to 6 1/4"

(121mm to 159mm)

14 1/4" to 15 3/4"

(362mm to 400mm)

17 1/4" to 18 3/4"

(438mm to 476mm)

7 3/4" to 9 1/4"

(197mm to 235mm)

10 3/4" to 12 1/4"

(273mm to 311mm)

Figure 18

Page 16

"A"

6"

(152.4mm)

Nat models only

"B"

4" to 5 1/2"

(101.6mm to 140mm)

9"

(228.6mm)

12"

(304.8mm)

6" to 7 1/2"

(152.4mm to 190.5mm)

9" to 10 1/2"

(229mm to 267mm)

Figure 20

31451-2-1013

VENTING FIREPLACE - TOP (LP & NAT MODELS)

Venting Graph (Dimensions in Feet)

To Use the Vent Graph

1. Determine the height of the center of the horizontal vent pipe. Using this dimension on the Sidewall Vent

Graph, locate the point it intersects with the slanted graph line.

2. From the point of this intersection, draw a vertical line to the bottom of the graph.

3. Select the indicated dimension, and position the unit in accordance with same.

EXAMPLE A:

If the vertical dimension from the floor of the unit is 35 feet, the horizontal run to the outer wall flange must not exceed 6.5 feet.

EXAMPLE B:

If the vertical dimension from the floor of the unit is 6.5 feet, the horizontal run to the outer wall flange must not exceed 14.5 feet.

SPECIAL NOTICE : For each 45 degree elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18" (45cm). This does not apply if the 45 degree elbows are installed on the vertical part of the vent system. Reduce 3' for every 90° elbow.

Example: According to the chart the maximum horizontal vent length is 20' and if two 45 degree elbows are required in the horizontal vent it must be reduced to 17'.

The maximum number of 45 degree elbows permitted per side wall installation is two. These elbows can be installed in either the vertical or horizontal run.

NOTICE : On vertical venting the first elbow does not get counted.

NOTICE : LP and Nat gas models can be top vented.

NOTICE : Flue heat shield must be installed for venting applications with less than two feet of vertical pipe off the top of the fireplace.

31451-2-1013

Figure 21

Acceptable vertical and horizontal vent run.

(40' maximum vertical and 20' maximum horizontal)

Unacceptable vertical and horizontal vent run.

Page 17

VENTING FIREPLACE - TOP (continued)

Installation of Flue Heat Shield

1. Remove flue insulation.

2. Remove two screws on outside of inlet vent adapter.

See Figure 22.

3. Lift top shield placing flue heat shield around flue.

4. Replace two screws on outside of inlet vent adapter.

See Figure 23.

5. Bend tab at top front of flue heat shield if necessary to maintain air gap between flue pipe and flue heat shield.

6. Replace flue insulation.

Figure 22 Figure 23

Page 18 31451-2-1013

VENTING FIREPLACE - TOP (continued)

Below Grade Installation

When it is not possible to meet the required vent terminal clearances of 12" (305mm) above grade level, a snorkel kit is recommended.

It allows installation depth down to 7" (178mm) below grade level.

The 7" (178mm) is measured from the center of the horizontal vent pipe as it penetrates through the wall.

Ensure the sidewall venting clearances are observed. If venting system is installed below ground, we recommend a window well with adequate and proper drainage to be installed around the termination area.

TYPICAL BASEMENT INSTALLATION

Figure 24

Examples of possible venting systems using one 90° elbow. Eight feet is listed as minimum vertical vent run with 20 feet of maximum horizontal vent run. Vertical dimensions are based on centerline to centerline of pipe. Horizontal dimensions are based on centerline of pipe to end of termination.

Figure 25

Examples of possible venting systems using two 90° elbows.

V is listed as minimum vertical dimensions and H1 + H2 is listed as total of maximum horizontal dimensions. The maximum vertical and horizontal distances for two 90° elbows as shown in Figure

26 is 20 feet.

Attention: Refer to Figure 21 for additional venting requirements.

31451-2-1013

Figure 26

Page 19

VENTING FIREPLACE - TOP (continued)

Figure 28

Figure 27

MINIMUM HOLE LOCATION DIMENSIONS FOR THROUGH

THE WALL HORIZONTAL INSTALLATIONS WITH 90 DEGREE

ELBOW OFF TOP OF FIREPLACE

Positioning the Fireplace

FIREPLACE

SERIES

DVP36DP

HARD ELBOW DIMENSIONS

"A"

43-1/2"

(1105mm)

"B"

4-1/2"

(114mm)

"C"

6-1/2"

(165mm)

FIREPLACE

SERIES

DVP36DP

FLEX PIPE 90 DEGREE BEND

"A"

45"

(1143mm)

"B"

4-1/2"

(114mm)

"C"

6-1/2"

(165mm)

Determine the exact position of the appliance so the direct vent termination will be centered (if possible) between two studs. This will avoid any extra framing. All vent kit pipes should be assembled on the unit after the unit is moved into the final position.

Cutting the Hole

After the fireplace has been positioned in its permanent location, the hole through the exterior wall of the house can be cut. This hole must be

11" (280mm) high x 10" (254mm) wide with its center line determined by the amount of vertical rise and horizontal run of the termination.

See Figure 27.

When locating the hole it must be noted that the bottom of the cap must be 12" (305mm) above the ground level, and top of the cap must be no less than 18" (457mm) below a combustible projection, and no closer than 9" (229mm) to any wall running parallel to vent termination. See Figure 28.

Page 20

Figure 29

31451-2-1013

31451-2-1013

Figure 30

EXAMPLES - TOP VENT RUN

Figure 31

Figure 32

Page 21

REAR VENT CONVERSION

Converting flue take-off to rear venting

When switching out the flue and inlet vent collars to run horizontally off the rear vent, the following steps must be taken.

1. Remove the inlet vent collar (8 screws) and flue collar (4 screws) from the top of the fireplace, and set to the side.

2. Remove the inlet cover plate and flue cover plate located on the back of the fireplace. These will be used to close the top flue and inlet openings.

3. Insert the insulation retainer bracket and insulation into the top flue pipe before reinstalling the flue cover plate over the top flue with 4 screws.

4. Reinstall the inlet cover plate over the top inlet opening with 4 screws. See illustration above..

5. Install the flue collar assembly to the rear flue with 4 screws.

6. Install the inlet vent collar to the rear of the fireplace with 8 screws.

7. This completes the conversion for a rear vent application.

WARNING

For top vented installations, the insulation and retainer are to be removed from the flue pipe and discarded.

Page 22 31451-2-1013

VENTING FIREPLACE - REAR (NAT GAS MODELS ONLY)

Venting Graph (Dimensions in Feet)

To Use the Vent Graph

1. Determine the height of the center of the horizontal vent pipe. Using this dimension on the Sidewall

Vent Graph, locate the point it intersects with the slanted graph line.

2. From the point of this intersection, draw a vertical line to the bottom of the graph.

3. Select the indicated dimension, and position the unit in accordance with same.

EXAMPLE A:

If the vertical dimension from the floor of the unit is

12 feet, 4 inches the horizontal run to the outer wall flange must not exceed 12 feet, 3 inches.

EXAMPLE B:

If the vertical dimension from the floor of the unit is

6 feet, 9 inches, the horizontal run to the outer wall flange must not exceed 6 feet, 6 inches.

SPECIAL NOTICE : For each 45 degree elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18" (45cm). This does not apply if the 45 degree elbows are installed on the vertical part of the vent system. Reduce 3' for every 90° elbow.

Example: According to the chart the maximum horizontal vent length is 20' and if two 45 degree elbows are required in the horizontal vent it must be reduced to 17'.

The maximum number of 45 degree elbows permitted per side wall installation is two. These elbows can be installed in either the vertical or horizontal run.

NOTICE : Only natural gas models can be rear vented.

31451-2-1013

Acceptable vertical and horizontal vent run.

Unacceptable vertical and horizontal vent run.

Figure 33

Page 23

EXAMPLES - REAR VENT RUN

Model

DVP36

Nat models only

Figure 36

Maximum Pipe

Length H1

24"

Nat models only

Figure 34

Model

DVP36

Maximum Pipe

Length H1

24"

Page 24

Nat models only

Figure 35

Nat models only

Figure 37

31451-2-1013

VENT CLEARANCES

Figure 38

A = *Clearance above grade, veranda, porch, deck or balcony

[*12 inches (30cm) minimum]

B = clearance to window or door that may be opened [*12 inches

(30cm) minimum for appliances < 100,000 Btuh (30kW)

J = clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance [*12 inches

(30cm) minimum for appliances ≤ 100,000 Btuh (30 kW)

C = clearance to permanently closed window [minimum 12 inches (30cm) recommended to prevent condensation on window]

36 inches (90cm) minimum for appliances > 100,000 Btuh

(30kW)]

K = clearance to a mechanical air supply inlet [* 6 feet (1.8m) minimum]

D = vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 24 inches (60 cm) from the center of the terminal [18 Inches (46 cm) minimum

L = †clearance above paved sidewalk or a paved driveway located on public property [*7 feet (2.1m) minimum]

M = clearance under veranda, porch, deck, or balcony [*12 inches (30cm) minimum ¥] E = clearance to unventilated soffit [12 inches 30cm) minimum]

F = clearance to outside corner.

G = clearance to inside corner.

See Page 27.

See Page 27.

† a vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings*

H = *not to be installed above a meter/regulator assembly within 3 feet (90cm) horizontally from the center-line of the regulator

¥ only permitted if veranda, porch, deck, or balcony, is fully open on a minimum of 2 sides beneath the floor*

I = clearance to service regulator vent outlet [*6 feet (1.8m) minimum]

* as specified in CGA B149 Installations Codes or ANSI

Z223.1. Note: Local Codes or Regulations may require different clearances.

Distances are to non-combustible surfaces unless otherwise indicated.

31451-2-1013 Page 25

6-5/8” VENTING FRAMING AND FINISHING

Installing Support Brackets

A horizontal pipe support MUST BE used for each 3 feet of horizontal run. The pipe supports should be placed around the pipe and nailed in place to framing members. There MUST BE a 3 inch clearance to combustibles above 6 5/8 inch diameter pipe and elbows and

1 inch clearance on both sides and bottom of 6 5/8 inch pipe to combustibles on all horizontal pipe sections and elbows.

Vertical runs of this vent systems must be supported every 4 feet above the appliance flue outlet by wall brackets attached to the 6

5/8 inch vent pipe and secured with nails or screws to structural framing members.

Figure 39

Installing Firestops

Firestops are required for safety whenever the vent system passes through an interior wall, an exterior wall, or a ceiling. These firestops act as a firebreak heat shield and as a means to insure that minimum clearances are maintained to the vent system.

Horizontal runs in the vent system which pass through either interior or exterior walls, require the use of wall firestops on both sides of the wall through which the vent passes.

Position the firestops on both sides of the 10 inch x 11 inch hole, previously cut. Secure with nails or screws. The heat shields of the firestops MUST BE placed towards the top of the hole. Continue the vent run through the firestops. See Figure 40.

Figure 40

Vertical runs of this system which pass through ceilings require the use of ONE ceiling firestop at the hole in each ceiling through which the vent passes.

Position a plumb bob directly over the center of the vertical vent component and mark the ceiling to establish the center point of the vent. Drill a hole or drive a nail through this center point and check the floor above for any obstructions such as wiring or plumbing runs. Reposition the appliance and vent system, if necessary, to accommodate ceiling joists and/or obstructions.

Cut a 10 inch x 10 inch hole through the ceiling, using the center point previously marked. Frame the hole with framing lumber the same size as the ceiling joists. See Figure 41.

If the area above the ceiling is NOT an attic, position and secure the ceiling firestop on the ceiling side of the previously cut and framed hole.

See Figure 42.

If the area above the ceiling is an attic, position and secure the firestop on top of the previously framed hole. See

Figure 43.

NOTICE : Remove insulation from the framed area in the attic before installing the firestop and/or vent pipes.

Page 26 31451-2-1013

31451-2-1013

6-5/8” VENTING FRAMING AND FINISHING

Figure 41

Figure 43

See Horizontal Termination Page 29 and Vertical Termination

Page 30-31.

Figure 42

Page 27

TERMINATION CLEARANCES

Termination clearance for buildings with combustible and noncombustible exteriors.

Figure 44

Vertical Sidewall Installations

Important! Minimum clearance between vent pipes and combustible materials is three 3" (76mm) on top, and 1" (25mm) on bottom and sides.

Important!

When vent termination exits through foundation less than 20" below siding outcrop, the vent pipe must extend outward so that the horizontal vent terminal is located flush to, or beyond the outcrop siding.

Information on Various Venting Routes and Components

Important: It is always best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length.

Since it is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust, certain limitations as to vent configurations apply and must be strictly adhered to.

The graph showing the relationship between vertical and horizontal side wall venting will help to determine the various vent lengths allowable.

The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace to the face of the outer wall.

The maximum horizontal vent run is 20 feet (457 cm) when the vertical vent rise is 8 feet (244 cm). See Figures 21 and 33.

Venting terminals shall not be recessed into wall or siding.

Page 28 31451-2-1013

HORIZONTAL TERMINATION

NOTICE : Termination cap should pass through the wall firestop from the exterior of the building. Adjust the termination cap to its final exterior position on the building.

WARNING

Termination cap must be positioned so that arrow is pointing up.

Attach the termination cap with the four wood screws provided.

Before attachment of the termination, run a bead of silicone sealant rated above 250°F on its outside edge too, so as to make a seal to the exterior wall.

NOTICE : Wood screws can and should be replaced with appropriate fasteners for use on stucco, brick, concrete or other types of siding.

CAUTION

If exterior walls are finished with vinyl siding (or materials that could become discolored or warp), it is necessary to install a vinyl siding standoff.

The vinyl siding standoff will be installed between the vent termination and the exterior wall. See Figure 45. This horizontal vent termination bolts onto the flat portion of the vinyl siding standoff, so an air space will exist between the wall and the termination cap.

Nat models only

Figure 46A

Figure 45

For installations requiring a vertical rise on the exterior of the building,

14-inch and 36-inch tall Snorkel Terminations, as shown in Figure

46A are available. Follow the same installation procedures as used for standard Horizontal Terminations. If the Snorkel Termination must be installed below grade (i.e. basement applications, proper drainage must be provided to prevent water from entering the

Snorkel Termination. See Figure 46B.

Do not attempt to enclose the Snorkel within the wall or any other type of enclosure.

31451-2-1013

Nat models only

Figure 46B

Page 29

VERTICAL TERMINATION

Locate and mark the center point of the venting pipe. Using a nail on the underside of the roof and drive this nail through this center point. Make the outline of the roof hole around this center point.

NOTICE : Size of the roof hole dimensions depend on the pitch of the roof. There must be a 1 inch clearance (25mm) to the vertical pipe sections. This clearance is to all combustible material.

Cover the opening of the vent pipe and cut and frame the roof hole.

Use framing lumber the same size as the roof rafters and install the frame securely. Flashing anchored to frame must withstand high winds. The storm collar is placed over this joint to make a water-tight seal. Non-hardening sealant should be used to completely seal this flashing installation.

Determining Minimum Vent Height Above the Roof.

WARNING

Major U.S. building codes specify minimum chimney and/ or vent height above the roof top. These minimum heights are necessary in the interest of safety. These specifications are summarized in Figure 47.

When terminating the vent cap near an exterior wall or overhang, maintain minimum clearances as shown in Figure 48 .

General Maintenance

Conduct an inspection of the venting system semi-annually.

Recommended areas to inspect are as follows:

1. Check areas of the venting system which are exposed to the elements for corrosion. These will appear as rust spots or streaks and, in extreme cases, holes. These components should immediately be replaced.

2. Remove the cap and shine a flashlight down the vent. Remove any bird nests or other foreign material.

3. Check for evidence of excessive condensate, such as water droplets forming in the inner liner and subsequently dripping out at joints. Condensate can cause corrosion of caps, pipe and fittings. It may be caused by having excessive lateral runs, too many elbows and exterior portions of the system being exposed to cold weather.

4. Inspect joints to verify that no pipe sections or fittings have been disturbed and, consequently, loosened. Also, check mechanical supports, such as wall straps or plumbers’ tape for rigidity.

Venting terminal shall not be recessed into a wall or siding.

A removable panel or other means must be provided in the enclosure for visual inspection of the flue connection.

NOTICE : This also pertains to vertical vent systems installed on the outside of the building.

Slide the vertical vent cap over the ends of the vent pipe and secure.

See Figure 49.

Installing the Vent System in a Chase

A chase is a vertical box-like structure built to enclose the gas appliance and/or it’s vent system. Vertical vent runs on the outside of a building may be, but are not required to be installed inside a chase.

ROOF PITCH

Flat to 6/12

H (Min.)

12" (305 mm)

6/12 to 7/12 15" (381 mm)

Over 7/12 to 8/12 18" (457 mm)

Over 8/12 to 16/12 24" (610 mm)

Over 16/12 to 21/12 36" (914 mm)

Figure 47

Note that for steep roof pitches, the vent height must be increased.

In high wind conditions, nearby trees, adjoining roof lines, steep pitched roofs, and other similar factors can result in poor draft, or down-drafting. In these cases, increasing the vent height may solve this problem.

Figure 49

CAUTION

Treatment of firestop spacers and construction of the chase may vary with the type of building. These instructions are not substitutes for the requirements of local building codes.

Therefore, your local building codes must be checked to determine the requirements for these steps.

Page 30

Figure 48

31451-2-1013

VERTICAL TERMINATION (continued)

NOTICE : When installing this vent system in a chase, it is always good building practice to insulate the chase as you would the outside walls of your home. This is especially important for cold climate installations. Upon completion of building your chase framing, install the vent system by following the instructions in this manual.

Remember to build the chase large enough so that minimum clearance of combustible materials (including insulation) to the vent system are maintained.

Installation of Vertical Inlet Baffle

The vertical inlet baffle is to be used only in a completely vertical vent installation. The vertical inlet baffle can be used when the vertical vent rise is between 10 feet and 40 feet. To maintain the yellow flame in the main burner, purchase Vertical Inlet baffle, VIB6A for use with 6 5/8" diameter vent systems, or the VIB7A for use with

7" diameter vent systems. These are available from your Empire

Comfort Systems, Inc. distributor or dealer.

In a vertical vent rise the rear (yellow) flame on the main burner can be reduced due to the drawing action from the flue exhaust pipe and the air inlet pipe. A decrease in the height or the appearance of the yellow flame may occur when the vertical vent rise is between 10 feet and 40 feet. To enhance the yellow flame on the main burner, the vertical inlet baffle can be attached to the direct vent high wind vertical top.

Please refer to the instructions included with the Air Inlet Baffle Kit for proper installation.

Reassembly and Resealing Vent Pipe System

Attach vent pipe to inlet and outlet vent adaptor on fireplace in either the vertical or horizontal position, replace horizontal and vertical pipe lengths, elbows and horizontal or vertical termination kit.

All vent system components lock into place by sliding the concentric pipe section with four equally spaced interior beads onto the appliance collar or previously installed component end with four equally spaced indented sections. When the internal beads of each starting outer pipe line up, rotate pipe section clockwise 90° (approximately 3 inches). The vent pipe is now locked together.

Continue replacing components per the vent system configuration.

Be certain that each succeeding vent component is securely fitted and locked into the preceding component in the vent system.

Figure 50

Vertical Through the Roof Applications

Your Gas Fireplace has been approved for: a) Vertical installations up to 40 feet in height.

b) Two sets of 45 degree elbow offsets within these vertical installations. From 0 to a maximum of 8 ft. a vent pipe can be used between elbows.

c) Wall straps must be used to support offset pipe every 4'.

This application will require that you first determine the roof pitch and use the appropriate venting components.

31451-2-1013 Page 31

DVVK-4FV DIRECT VENT TERMINATION KIT

This termination kit can only be used with Empire Comfort Systems direct vent fireplaces listed for use with DVVK-4FV Vertical Flex Vent Kit. Please review the instructions packaged with your fireplace and verify the fireplace model number. Check that this flex vent system is listed for use with your fireplace model prior to starting the installation.

This vent kit may be installed as an OEM installation in a manufactured home (USA only) or mobile home and must be installed in accordance with the manufacturer’s instruc tions and the manufactured home construction and safety standard, Title 24 CFR, Part 3280 or Standard for Installation in Mobile Homes, CAN/CSA Z240 MH.

WARNING

Failure to follow these instructions may create a possible fire hazard and will void the warranty.

WARNING

Always maintain minimum clearances around vent systems.

The minimum clearance to combustibles for horizontal runs of vent pipe is 3 inches from the top, and 1 inch from the sides and bottom of the vent system. Do not pack the open air spaces around the fireplace or flue with insulation or other materials. Any horizontal run must have a 1/4” rise for every one foot of run towards the vent termination. The vent above the roof must terminate vertically.

CAUTION

All Fireplaces listed for use with the DVVK-4FV will operate safely when installed in accordance with this instruction manual. Read all instructions before starting installation, then follow these instructions carefully to maximize fireplace performance and safety. Report damaged parts to your dealer.

WARNING

Contact your Local Building and Fire Officials about re strictions and installation inspections in your area.

WARNING

Any common venting of the gas appliance using the DV vent kit with other gas appliances is not allowed. Do not connect this appliance to a chimney flue servicing a separate solid fuelburning appliance.

IMPORTANT SAFETY INFORMATION

• The vertical termination cap MUST be vented directly to the outside. The termination kit MUST NEVER be connected to a chimney flue(s) servicing a separate solid-fuel burning appliance or any other appliances.

• Termination cap MUST NOT be mounted horizontally.

• The flexible vent pipe cannot be intermingled with any of the rigid vent pipe section(s). DO NOT connect two sections of flexible vent pipe together to achieve a longer length without the use of approved connectors.

• The installation must conform with local codes or in the absence of local codes, with the National Fuel Gas Code, ANSI

Z223.1 (in the United States) or with the current installation code CAN/CGA B149 (in Canada).

• Only Direct Vent fireplaces approved for use with Empire

Comfort Systems, Inc. DVVK-4FV termination kit shall be used. See PARTS LIST/ILLUSTRATIONS section for vent component identification.

• Horizontal vent runs must be supported every 2 feet using wall straps. Vertical runs must be supported every 3 feet using wall straps. Slip wall straps loosely on to pipe. Attach installer provided straps to framing members using nails or screws.

• The fireplace and venting system should be inspected before initial use and at least annually by a qualified field service person. Inspect the external vent cap on a regular basis to make sure that no debris is interfering with the airflow. Inspect entire venting system to ensure proper function.

• Please refer to the fireplace instructions for information on

Termination Cap clearances.

Page 32 31451-2-1013

DVVK-4FV DIRECT VENT TERMINATION KIT

PRE-INSTALLATION INFORMATION:

Items Required For Installation:

Tools

Phillips Screwdriver

Hammer

Saw and/or saber saw

Level

Measuring Tape

Electric Drill and Bits

Pliers

Square

Tin Snips

Building Supplies

Framing Materials

Wall Finishing Materials

Caulking Material (Noncombustible)

Support Strap supplies

CAUTION

This flex vent kit can be installed either vertically or horizontally off of Direct Vent Series fireplaces but must only terminate vertically.

WARNING

Because of sharp edges, always use gloves when handling the flex vent components.

CAUTION

Vent connections should overlap a minimum of 1” for proper sealing.

Before You Start:

Plan your installation. Read these instructions and the fireplace installation manual before installing unit and vent system. Set unit in place and survey how best to vent the unit. After the vent configuration has been decided, stretch the flex pipe components out, then trim off what will not be needed.

Refer to the fireplace installation manual for information on vertical venting requirements. The maximum length of vent when using flex venting is 35 feet total. Contact your dealer or distributor for information on flex vent extension kits that may be added to the

DVVK-4FV kit, in order to terminate up to 35 feet. Available extension kits include the DVEK-10 (10’ Flex) or the DVEK-25 (25’ Flex) extension kits. The extension kits include connection hardware.

CAUTION

Always stretch and secure venting with metal strapping secured with nails (nails and strapping not supplied) to ensure that the flex vent runs remain true.

INSTALLATION NOTE:

If space permits, it is generally easier to attach venting in the top vent configuration.

Installation of the Vertical Flex Termination Kit

WARNING

Ensure that the venting system exits the structure through the roof and does not terminate less than 12 inches (305mm) above the roof.

WARNING

Refer to your fireplace homeowner’s manual for the minimum and maximum venting requirement of your fireplace prior to installation. Failure to do so may cause a fire hazard.

WARNING

This flexible pipe termination kit is ONLY for vertical terminations.

WARNING

Any horizontal run section must have a 1/4” rise for every one foot of run towards the vent termination. Never allow the vent pipe to run downward. This could cause high temperatures and may present a fire hazard. This vertical kit may incorporate two

90 degree bends, but must terminate vertically.

31451-2-1013 Page 33

DVVK-4FV DIRECT VENT TERMINATION KIT

Step-By-Step Installation:

1. Unpack vent components and check all items for shipping damage.

2. For this venting system to operate as designed it is dependent on the use of all parts and procedures detailed in these instructions. Failure to follow these instructions may potentially affect the performance of this vent system and the attached appliance.

3. As per the fireplace manufacturer’s instructions, replace the existing 6 5/8” diameter fireplace vent adapter with the 7” diameter flex vent fireplace adapter included in the vent kit.

Install the adapter collar with the screws removed from the standard fireplace collar. Refer to the fireplace manual for additional information on the vent collar removal and installation.

4. Once the fireplace location has been determined, mark the ceiling where the flex vent will pass through. Cut an opening for installation of the firestop thimble assembly. The opening must measure a minimum of 9-1/2” x 9-1/2” square. See Figure 51.

5. Next, determine the location for the cutout in the roof opening.

This opening must be large enough to provide a minimum 1” air space clearance from the vertical vent pipe to any combustible framing.

6. Install the Firestop/Thimble assembly to the framed opening in the ceiling using common nails or screws.

NOTICE : The thimble assembly is adjustable up or down as needed within the firestop. It is also designed with a pivoting firestop for use with 0 - 3/12 pitch cathedral ceilings.

7. To begin vent system assembly, first layout all the vent components on the floor in the order in which they will be assembled.

8. Stretch the 4” diameter inner flex flue and 7” diameter outer flex vent to the maximum length of 6 feet.

9. Install the spring spacers provided around the 4” diameter flex flue at 1 foot intervals, then slide the flue pipe with spacers into the 7” diameter outer flex vent pipe. Make sure the springs are spaced evenly starting at 12 inches from the fireplace collar. See Figure 52.

Figure 52

Figure 51

Page 34 31451-2-1013

DVVK-4FV DIRECT VENT TERMINATION KIT

10. With the flex vent assembly and the 48” long hard pipe components laid out on the floor, begin securing these parts together. First, apply a generous bead of silicone sealant to the inside of the 4” diameter flex flue (not the end with the pre-installed connector), then slide the flex flue over the 4” diameter hard pipe flue. Be sure to overlap at least 1-1/4”. Secure this connection with a 4” diameter band clamp provided. Be careful not to damage or tear the flex flue when tightening clamp.

11. Repeat the connection process for the outer 7” diameter flex vent to hard pipe connection. Use silicone sealant at this joint also, overlap at least 1-1/4”, then secure the joint with the 7” diameter band clamp provided. Be careful not to damage or tear the flex vent pipe when tightening the clamp.

12. While the venting is still on the floor, assemble the roof jack components as shown in Figure 53 and pre-install the roof jack assembly to the hard pipe approximately 18” from the top end of the hard pipe.

13. Now the pre-assembled vent system may be carried to the roof, then lowered through the roof cutout opening (see step

5). Feed the flex vent end down through the roof opening and firestop/thimble assembly installed in steps 4 through 6.

14. Secure the roof support assembly to the roof sheathing with at least four nails/screws through each support bracket. Check that the combustible clearances through the roof framing will maintain at least a 1” clearance from the vent pipe.

15. Determine how high the vent terminal should be located above the roof line based on the roof pitch information shown in Figure 54 . Adjust the vent system height by loosening the pre-installed roof support pipe clamp and sliding the vent pipe up or down as pre-determined, then re-tighten the pipe clamp.

Install a couple of sheet metal screws through the pipe clamp into the outer hard vent pipe to lock in place.

16. Check to make sure that the bottom end of the flex vent is long enough to reach the fireplace adapter collars. If too long, trim off the extra flex vent not needed.

Figure 53

ROOF PITCH

Flat to 6/12

6/12 to 7/12

Over 7/12 to 8/12

Over 8/12 to 16/12

Over 16/12 to 21/12

H (Min.)

12” (305mm)

15” (381mm)

18” (457mm)

24” (610mm)

36” (914mm)

Figure 54

31451-2-1013 Page 35

DVVK-4FV DIRECT VENT TERMINATION KIT

17. To attach the vent connections at the fireplace, be sure the 7” diameter adapter collar has been installed per step 3. Apply a bead of silicone sealant to the 4” diameter flex connector, then slide the flex pipe adapter collar into the fireplace flue collar and secure by installing a minimum of two screws through the flue collar and into the adapter. See Figure 55.

18. Apply sealant to the 7” diameter adapter collar, slide outer flex vent over the collar, then secure with a 7” diameter band clamp. See Figure 55.

19. Once the lower connections are made and the flex pipe is secured with support bands as required (3 feet minimum between supports) then the roof flashing can be installed. See

Figure 56.

LP and Nat models

Figure 55

Figure 56

20. Install the roof flashing, and seal using common constructions practices.

21. An additional storm collar band is provided in kit that may be used as an attic insulation shield. The collar can be installed around the flex pipe (or hard pipe) just above the firestop thimble. This collar will act as a shield to prevent blown insulation from entering the thimble.

22. To complete the vent installation, install the vent termination cap to the top of the hard vent pipe assembly. Mate up the flue and outer telescopes with the hard pipe assembly, then secure by installing a minimum of two sheet metal screws into the overlapped flanges of the cap and pipe.

23. Figure 57 shows a completed installation with components identified and other installation information such as heights and clearance to combustibles.

Page 36 31451-2-1013

DVVK-4FV DIRECT VENT TERMINATION KIT

31451-2-1013

Figure 57

Page 37

DVVK-4FV DIRECT VENT TERMINATION KIT

Vertical Flex Termination Kit

Page 38

Item

Number

1

2

3

6

7

8

9

4

5

10

N/S

N/S

N/S

N/S

N/S

Item Description

4”/7” Vertical Termination Cap

Roof Support Kit

2 Ply Alum Flex 4” Diameter by 6 ft.

2 Ply Alum Flex 7” Diameter by 6 ft.

4”/7” x 48” Rigid Pipe Assembly

Firestop Thimble Assembly

Roof Flashing (0/12 to 6/12)

7” Flex Adapter Collar with Gasket

7” Storm Collar

Spring Spacers

Clamp 4” Diameter

Clamp 7” Diameter

#8 x 1/2” Self Drilling Screws

HT Silicone

#8 x 5/8” Self Drilling Screws

Repair Part No.

MF100038

MF100503

MF04ALA2F006

MF07ALA2F006

MF100554

MF100124

MF100091

MF100524

MF100147

MF100548

MF100330

MF100534

N/A

N/A

N/A

2

20

5

2

1

10

Quantity

Supplied

1

1

1

1

1

1

2

1

1

31451-2-1013

DVVK-4F FLEX VENT INSTRUCTIONS - TOP VENT ONLY

The DVVK-4F FLEX VENT KIT includes the following components:

• Horizontal Termination Cap

• 4-foot section of Flex vent with spacers (4” flue/7” outer pipe)

• 4” diameter Flue adapter collar

• 7” diameter Outer Vent adapter collar

• Wall Firestop/Thimble Assembly

• Hardware pack that includes band clamps and screws

Flex venting can be installed either vertically or horizontally off of the DVP36 Series fireplaces. When installing a horizontal vent run from top connections, maintain at least ½” rise for every 12” of vent run. When venting horizontal off the rear vent connections, allow a minimum rise of 2”. Refer to Figure

57 when mounting termination near vinyl siding.

3. Remove the 6-⅝” diameter Vent collar from the fireplace.

Replace this collar with the 7” diameter Flex Vent adapter collar provided with the vent kit.

4. Slide the Flex Vent flue pipe into the Outer Flex Vent pipe.

5. Install the Wall Firestop/Thimble assembly as required through the wall. Refer to the venting charts in the fireplace manual to determine the proper height and size of the vent opening. The minimum opening should be 9” wide by 11” high.

The minimum combustible clearance from the horizontal vent is 1” from sides and bottom, and 3” above the vent pipe. See

Figure C.

CAUTION: Always stretch and secure venting with wire or metal strapping to ensure that the horizontal runs do not sag.

If space permits, it is generally easier to attach venting in the top vent configuration.

Because of sharp edges, always use gloves when handling the flex vent components.

Vent connections should overlap a minimum of 1” for proper sealing.

Always follow the general venting requirements for vent terminal location, vent lengths, and clearance to combustible materials.

STEP-BY-STEP INSTALLATION

1. Unpack vent components and check that all items are included.

2. Check to see that the vent spacer springs are located around the flue vent at 8” and 12” intervals along its length. See

Figure A.

If not, stretch the spacer springs to about 15” long and wrap them around the flue, then interlock the ends of each spring about 2”. See Figure B.

Maintain equal distance between spring spacers.

Figure C

6. In most cases, after determining the length of the vent that is needed, it may be easier to install the flue and outer vent pipes to the Termination Cap first, then from the outside, feed the venting through the wall to the fireplace.

7. If the venting is to long, trim off any excess vent before attaching the vent end connectors.

8. Attach the Termination Cap to the outside of the house.

9. Prior to making the vent connections, apply high temperature sealant (1000 degree F min.) to the vent connections before securing with the band clamps provided. NOTICE : the flue pipe end without the adapter is to be installed to the

Termination Cap.

10. Apply sealant to the outside of the flue pipe adapter and connect to the flex flue pipe. Then insert the adapter into the fireplace flue. Secure flue adapter to the fireplace flue with a minimum of two screws provided. See Figure D.

Figure A

31451-2-1013

Figure B

Figure D

11. Attach the Outer Vent pipe to the 7” diameter Collar on the fireplace with a large band clamp provided. Sealant may also be used on the outer vent connections.

12. Check all vent connections for tightness. Make sure horizontal venting has the proper rise and combustible clearances required. Refer to venting charts in fireplace instruction manual.

Page 39

DVVK-4RE VENT KIT INSTALLATION INSTRUCTIONS

CAUTION

Sharp edges, use protective gloves when installing.

Tools Needed for Installation:

Sheet metal snips

5/16” nut driver

Phillips head screwdriver - #2

High temperature sealant or furnace cement rated for continuous use at 1,000 o F minimum

Measuring tape

Parts Verification

See parts list on page 42 to verify components included in this vent kit prior to installation.

Installing Wall Thimble/Firestop Assembly

1. Fix fireplace to permanent location. If using rigid venting system, install up to the location where it will exit the building.

2. Cut hole in wall for wall thimble/firestop assembly ( Figure 59 ) into your combustible wall. NOTICE : On brick or block exterior wall a 7” (178mm) diameter hole needs to be cut.

Measure the total wall thickness to determine whether or not the extension thimble is to be used. If the combustible wall depth is over 5 3/8” (137mm), then the extension thimble should be used (Figure 59).

3. Install the wall thimble assembly through the framed opening so the firestop plate is on the interior wall ( Figure 59 ). Telescope section should extend all the way through the exterior wall. Attach with four 10 x 1” screws.

4. When placing the vent cap on an exterior wall covered with combustibles such as wood, lap, or vinyl siding, install the vinyl siding kit to the exterior wall sheathing.

NOTICE : If installing onto wood, lap, or vinyl siding, the vinyl siding kit should be used (sold separately, part number DV-822).

The vinyl siding vent kit, DV-822, is available from Empire Comfort

Systems, Inc. The depth is 3” (76mm), which enables the vent cap to be extended away from vinyl siding or projections. The wall depth plus the additional 3” (76mm) depth of the vinyl siding vent cap extension should not exceed a total depth of 13 3/4” (349mm).

If wall depth exceeds 13 3/4” (349mm), extend system using

6 5/8” (168mm) x 4” (102mm) rigid venting (See Fireplace Instructions for approved lengths) See Figure 58.

Figure 59

Nat models only

Figure 58

Page 40 31451-2-1013

DVVK-4RE VENT KIT INSTALLATION INSTRUCTIONS

Cutting Vent Tubes

This is the most important part of the installation.

With the fireplace (and the rigid venting system if used) fixed to its permanent location, the 6 5/8” (168mm) diameter air inlet tube and the 4” (102mm) diameter flue outlet tube are to be marked and cut using the following procedure.

5. Attach the inlet tube to the outside mounting plate. Align tinnerman clips on the tabs of the air inlet tube to the holes on outside mounting plate, and fix with two #10 x 1/2” screws.

6. With the vinyl siding kit installed to wall (if necessary), insert the 6 5/8” (168mm) diameter tube with outside mounting plate attached through hole in wall. Connect to collar on fireplace or rigid vent system. Measure between wall or vent cap extension and outside mounting plate. See Figures 60 and 61 .

CAUTION

Sharp edges, use protective gloves when installing.

7. Remove outside mounting plate with tube attached from wall.

Mark and cut the extra length of the 6 5/8” (168mm) diameter tube from the opposite end. Do not crimp or enlarge tube.

8. Attach the 4” (102mm) diameter flue outlet tube onto the rigid venting system or directly to fireplace. Ensure the 4” (102mm) diameter flue outlet tube is placed as far as possible onto the rigid venting system. Mark the 4” (102mm) diameter flue outlet tube 2 1/2” (64mm) beyond the vinyl siding kit or wall. S ee

Figure 61.

Remove the 4” (102mm) diameter flue outlet tube from rigid venting system. When installing directly to fireplace, tape gasket needs to be used.

9. Mark or wrap tape completely around the tubes at the marked points to help in making a true cut. Do not crimp or enlarge tubes.

10. From outside: Push the 6 5/8” (168mm) diameter inlet tube/ mounting plate onto end of rigid venting system to correct position. Fasten the outside mounting plate to the vinyl siding kit or wall with four 10 x 1 1/2” screws. (Ensure upward slope).

11. From inside: Attach the inlet tube to the collar on the back of the fireplace (or the rigid venting system) using three self tapping screws.

12. Seal the 4” (102mm) diameter flue outlet tube. Follow instructions and diagram. See Figure 62.

13. Fasten 4” (102mm) diameter flue outlet tube in place. Do not

“twist” the flue outlet tube into the fireplace collar (or rigid venting system). Hold the tube by the seam and push in using a perpendicular “rocking” motion. This ensures the seam on the tube stay intact.

14. Fasten vent cap end using three 10 x 1/2” screws to mounting plate.

Figure 60

Sealing 4” (102mm) Diameter Flue Outlet Tube

Figure 62

NOTICE : Tape gasket to be applied prior to installing to fireplace flue outlet tube only. Tape gasket should not be used when mating the flue outlet tube to a rigid venting system.

Figure 61

31451-2-1013 Page 41

DVVK-4RE VENT KIT INSTALLATION INSTRUCTIONS

Follow correct option according to venting method.

Connecting Directly to Fireplace

If the air inlet and flue outlet tubes are to be connected directly to the unit (no rigid venting system is being used), then the gasket provided must be used to seal the 4” (102mm) flue outlet tube.

Peel the paper off the self-adhesive gasket and then wrap it around the end of the tube (if tube was cut, it is recommended to use cut end) as shown in Figure 62.

Pull the gasket tight at all times while wrapping it around tube. The gasket ends should align, to form a complete seal. The overlapped section should NOT come in contact with the seam in the tube. Apply high temperature sealant to the opposite end of the tube (on the inside of the tube). The end with the gasket will attach to the back of the unit. Continue with

Step 13.

Connecting to Rigid Vent System

If the air inlet and flue outlet tubes are to be connected to a rigid venting system (and not directly to the back of the unit), then do not use the gasket provided. High temperature sealant should be applied to the outside of the 4” diameter (102mm) flue outlet tube

(if tube was cut, it is recommended to use cut end) and to the inside of the tube on the end that connects to the vent cap. Continue with step 13.

INDEX

NUMBER

1

2

3

4

5

6

PART

NUMBER

DV769

19193

19194

DV524

19196

20527

PARTS LIST

DESCRIPTION

Vent Cap Assembly

Outside Mounting Plate

Air Inlet Tube

Flue Outlet Tube

Firestop/Thimble Assembly

Gasket

Page 42 31451-2-1013

PROPANE/LP GAS CONVERSION

A

Air Shutter Setting Burner Orifice

Opening "A" Propane/LP Orifice

FULL OPEN 1.55 mm

Figure 63

Maxitrol Valve Conversion - Direct Ignition Only

Figure 64

31451-2-1013 Page 43

LOG PLACEMENT (4 LOG SET)

Before you begin: This fireplace is supplied with a set of four ceramic fiber logs. Do not handle these logs with your bare hands.

Always wear gloves to prevent skin irritation from ceramic fibers.

After handling logs, wash your hands gently with soap and water to remove any traces of fiber.

The positioning of logs is critical to safe and clean operation of this fireplace. Sooting and other problems may result if the logs are not properly and firmly positioned in the fireplace. Please refer to Figure

65, Figure 66, and Figure 67 and corresponding WARNING , when completing the following log placement steps.

1. Remove Decorative Doors (where applicable) by opening and lifting straight up.

2. Remove Decorative Front.

3. Release two glass frame spring clamps at bottom of firebox

4. Place rear (#1) log onto two pins on rear log support.

5. Place left, front (#2) log onto two left, front pins on burner pan.

6. Place right, front (#3) log onto two right, front pins on burner pan.

7. Place Branch (#4) onto one pin on rear log and one pin on front left log.

8. Place decorative rock in front of grates and sides of main burner.

9. After all logs are properly positioned, place small “dime” size pieces of Rockwool lightly across the front round “blueflame” ports. Place the ember material (Rockwool pieces) side by side.

Do not stack more than one layer of embers across the burner ports. See Figure 65.

Figure 66

WARNING

Failure to position the parts in accordance with this diagram or failure to use only parts specifically approved with this appliance may result in property damage or personal injury.

ATTENTION: Do not place decorative rock on logs or on burner. The decorative rock should only be placed on the fireplace floor.

10. Replace glass door onto firebox.

11. Secure the two glass frame spring clamps at bottom of firebox.

12. Replace Decorative Front.

13. Replace Decorative Doors (where applicable) by aligning hinges over posts.

Index No.

1

2

3

4

Figure 67

Log Set Parts List

Part No.

R10349

R10350

R10351

R10352

Description

Rear Log

Front Left Log

Front Right Log

Top Branch

Figure 65

WARNING

If flame lifts off burner and goes out, verify insulation and retainer were removed. See page 22.

Page 44 31451-2-1013

MILLIVOLT SYSTEM OPERATING INSTRUCTIONS

750 Millivolt System

The standing pilot (750 millivolt system) is a continuous burning pilot. The pilot remains ON even when the main burner is OFF.

When you ignite the pilot, the thermopile produces millivolts (electrical current) which energizes the magnet in the gas valve. After 30 seconds to 1 minute time period you can release the gas control knob and the pilot will stay ON. Allow your pilot flame to operate an additional one to two minutes before you turn the gas control knob from the PILOT position to the ON position. This time period allows the millivolts (electrical current) to build-up to a sufficient level allowing the gas control to operate properly.

1. Follow the SAFETY and LIGHTING INSTRUCTIONS for standing pilot controls found in this manual and on labels found in control compartment behind the door assembly.

Initial Lighting

Upon completing the gas line or turning the gas valve on after it has been in the “OFF” position, a small amount of air will be in the lines.

When first lighting the fireplace, it will take a few minutes for the lines to purge themselves of this air. Once the purging is complete, the fireplace will light and operate satisfactorily.

Subsequent lightings of the appliance will not require such purging if the gas valve is not turned to “OFF.”

Pilot Flame

The thermopile/thermocouple (standing pilot) tips should be covered with flame.

CAUTION

During the initial purging and subsequent lightings, never allow the gas valve control knob to remain depressed in the “pilot” position without pushing the piezo ignitor button at least once every second.

2. During the operating season, leave the control valve knob in the

“ON” position. This will allow the pilot flame to remain lit. Turn the burner flame on or off with the fireplace REMOTE/OFF/ON switch, wall switch or remote controls.

NOTICE : The gas control valve allows you to increase or decrease the height of the main burner flame. The control valve has a pressure regulator with a knob as shown in Figure 68 . Rotate the knob clockwise to “HI” to increase the flame height and counterclockwise to “LO” to decrease the flame height.

3. When the operating season is over, turn the REMOTE/OFF/ON switch to “OFF” and the control valve to “OFF”. The system, including the pilot light, will be shut down.

Figure 69

Figure 68

The OWNER should carefully read and follow these operating instructions at all times. Lower the door assembly to view the gas controls for the fireplace.

31451-2-1013 Page 45

MILLIVOLT SYSTEM OPERATING INSTRUCTIONS

STANDING PILOT OPERATING INSTRUCTIONS

REMOTE/OFF/ON Switch

The fireplace is equipped with a REMOTE/OFF/ON switch. A wire harness is attached to the REMOTE/OFF/ON switch. The red, black and green (wires) female push-ons attach to the

REMOTE/OFF/ON switch. At the opposite end of the wire harness, the black and green (wires) female push-ons attach to the gas valve.

An additional green wire and the red wire, which are stripped and bare, will attach to one of the accessories that can be purchased for use with your fireplace.

Operation of REMOTE/OFF/ON Switch with no Accessories

To ignite main burner, turn the control knob on the gas valve from the PILOT position to the ON position. Turn the REMOTE/OFF/ON switch from the OFF position to the ON position. The additional green wire and red wire, which are stripped and bare are not used.

Wall Switch, FWS-1

Connect the green and red, stripped and bare, wires on the REMOTE/

OFF/ON switch wire harness to the wall switch using wire nuts. Turn the REMOTE/OFF/ON switch to the REMOTE position. Pivot the rocker switch on the FWS-1 to the ON position.

Wall Thermostats (optional)

TRW - Wireless for Millivolt models

TMV - Reed switch for Millivolt models

Battery Operated Remote Controls, FRBC, FBRTC, and TRW

Connect the green and red, stripped and bare, wires on the

REMOTE/OFF/ON switch wire harness to the remote receiver that is a component in the remote kit using wire nuts. Turn the REMOTE/

OFF/ON switch to the REMOTE position. Follow instructions included with the remote to complete installation.

NOTICE : If batteries fail in the remote, and immediate heat is desired, turn the REMOTE/OFF/ON switch from the REMOTE position to the ON position.

Electric (120 volt) Operated Remote Control, FREC

Connect the green and red, stripped and bare, wires on the REMOTE/

OFF/ON switch wire harness to the wires on remote receiver that is a component in the FREC using wire nuts. Turn the REMOTE/

OFF/ON switch to the REMOTE position. Follow instructions in the

FREC to complete installation.

NOTICE : If electric (120 volt) fails in FREC, and immediate heat is desired, turn the REMOTE/OFF/ON switch from the REMOTE position to the ON position.

Installation of Remote Receiver

Place remote receiver on the floor of fireplace behind the louver as far forward as possible.

Attention: The Velcro loop and hook are not necessary in this installation but can be used to secure remote receiver.

Refer to remote control installation and operating instructions for more details on remote control.

Millivolt Control

The valve regulator controls the burner pressure which should be checked at the pressure test point. Turn captured screw counter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point (Use test point “A” closest to control knob). After taking pressure reading, be sure and turn captured screw clockwise firmly to re-seal. Do not over torque. Check for gas leaks.

Millivolt thermopile is self generating. Gas valve does not require

24 volts or 110 volts.

Check System Operation

Millivolt system and all individual components may be checked with a millivolt meter 0-1000 MV range.

It is important to use wire of a gauge proper for the length of the wire:

Recommended Wire Gauges

Maximum Length

1' to 10'

Wire Gauge

18

10' to 25'

25' to 35'

16

14

Page 46 31451-2-1013

MILLIVOLT SYSTEM STANDING PILOT WIRING DIAGRAM

31451-2-1013

Figure 70

Page 47

MILLIVOLT SYSTEM STANDING PILOT LIGHTING INSTRUCTIONS

FOR YOUR SAFETY READ BEFORE LIGHTING

WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

A. This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly.

B. Before lighting smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

What To Do If You Smell Gas

• Do not try to light any appliance.

• Do not touch any electrical switch;

• Do not use any phone in your building.

• Immediately call your gas supplier from a neighbor's phone.

Follow the gas supplier's instructions.

• If you cannot reach your gas supplier, call the fire department.

C. Use only your hand to push in or turn the gas control knob.

Never use tools. If the knob will not push in or turn by hand, don't try to repair it; call a qualified service technician. Force or attempted repair may result in a fire or explosion.

D. Do not use this appliance if any part has been under water.

Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

LIGHTING INSTRUCTIONS

1. Stop! Read the safety information above.

2. Set REMOTE/OFF/ON switch to OFF.

3. Turn off all electric power to the appliance (if applicable).

4. Lower bottom louver assembly.

5. Push in gas control knob slightly and turn clockwise to "OFF."

Note: Knob cannot be turned from "PILOT" to "OFF" unless knob is pushed in slightly. Do not force.

6. Wait ten (10) minutes to clear out any gas. Then smell for gas, including near the floor. If you then smell gas, STOP! Follow

"B" in the safety information above. If you do not smell gas, go to the next step.

7. Find pilot - Follow metal tube from gas control. The pilot is behind the burner on the right side.

8. Turn gas control knob counterclockwise

to "PILOT."

9. Push in control knob all the way and hold in. Repeatedly push the piezo ignitor button until the pilot is lit. Continue to hold the control knob in the for about one minute after the pilot is lit.

Release knob, and it will pop back up. Pilot should remain lit.

If it goes out, repeat steps 5 through 9.

• If the control knob does not pop up when released,

STOP and IMMEDIATELY call a qualified service technician or gas supplier.

• If the pilot will not stay lit after several tries, turn the gas control knob to "OFF" and call your service technician or gas supplier.

10. Turn gas control knob counterclockwise to "ON."

11. Close bottom louver assembly.

12. Turn on all electric power to the appliance (if applicable).

13. Set REMOTE/OFF/ON switch to desired setting.

TO TURN OFF GAS TO FIREPLACE

1. Set REMOTE/OFF/ON switch to OFF.

2. Turn off all electric power to the appliance if service is to be performed (if applicable).

3. Lower bottom louver assembly.

4. Push in gas control knob slightly and turn clockwise to "OFF." Do not force.

5. Close bottom louver assembly.

Page 48 31451-2-1013

MILLIVOLT SYSTEM STANDING PILOT TROUBLESHOOTING

With proper installation and maintenance, your new Direct Vent Gas Fireplace will provide years of trouble-free service. If you do experience a problem, refer to the Trouble Shooting Guide below. This guide will assist a qualified service person in the diagnosis of problems and the corrective action to be taken.

1. Spark ignitor will not light pilot after repeated triggering of piezo ignitor button.

a. Defective ignitor (no spark electrode)

—Check for spark at electrode and pilot; if no spark and electrode wire is properly connected, replace ignitor.

b. No gas or low gas pressure.

—Check remote shut off valves from fireplace. Usually there is a valve near the main. There can be more than one valve between the fireplace and main.

—Low pressure can be caused by a variety of situations such as a bent line, too narrow diameter of pipe, or low line pressure. Consult with plumber or gas supplier.

c. No LP in tank.

—Check LP (propane) tank. Refill tank.

2. Pilot will not stay lit after carefully following lighting instructions.

a. Defective thermocouple.

—Check that pilot flame impinges on thermocouple. Clean and/or adjust pilot for maximum flame impingement.

—Ensure the thermocouple connection at the gas valve is fully inserted and tight (hand tight plus 1/4 turn). Faulty thermocouple if reading is below specified minimum of 15 millivolts.

—Disconnect the thermocouple from the valve, place one millivolt meter lead wire on the end of the thermocouple and the other millivolt meter lead wire on the thermocouple copper wire. Start the pilot and hold the valve knob in. If the millivolt reading is less than 15 millivolt, replace the thermocouple.

b. Defective valve.

—If thermocouple is producing more than 15 millivolts, replace faulty valve.

3. Pilot burning, no gas to burner, valve knob “ON”, REMOTE/

OFF/ON switch “ON.” a. REMOTE/OFF/ON switch, wall switch, remote control or wires defective.

—Check REMOTE/OFF/ON switch and wires for proper connections. Place jumper wires across terminal at switch.

If burner comes on, replace defective switch. If OK, place jumper wires across switch wires at gas valve-if burner comes on, wires are faulty or connections are bad.

b. Thermopile may not be generating sufficient millivolts.

—If the pilot flame is not close enough physically to the thermopile, adjust the pilot flame.

—Be sure the wire connections from the thermopile at the gas valve terminals are tight and the thermopile is fully inserted into the pilot bracket.

—Check the thermopile with a millivolt meter. Take the reading at TH-TP & TP terminals of the gas valve. The meter should read 350 millivolts minimum, while holding the valve knob depressed in the PILOT position, with the pilot lit, and the REMOTE/OFF/ON switch in the OFF position. Replace the faulty thermopile if the reading is below the specified minimum.

—With the pilot in the ON position, disconnect the thermopile leads from the valve. Take a reading at the thermopile leads.

The reading should be 350 millivolts minimum. Replace the thermopile if the reading is below the minimum.

c. Defective valve.

—Turn valve knob to ON. Place REMOTE/OFF/ON switch to ON. Check with millivolt meter at thermopile terminals.

Millivolt meter should read greater than 200 millivolts. If the reading is okay and the main burner does not ignite, replace the gas valve.

d. Plugged main burner orifice.

—Check main burner orifice for blockage and remove.

4. Frequent pilot outage problem.

a. Pilot flame may be too high or too low, or blowing (high), causing pilot safety to drop out.

—Clean and adjust flame for maximum flame impingement on the thermocouple. Follow lighting instructions carefully.

5. The pilot and main burner extinguish while in operation.

a. No LP (Propane) in tank.

Check LP (Propane) tank. Refill fuel tank.

b. Inner vent pipe leaking exhaust gases back into system

—Check for leaks.

c. Glass too loose, gasket leaks in corners after usage.

—Be certain glass assembly is installed correctly.

d. Horizontal vent improperly pitched.

—The horizontal vent cap should slope down only enough to prevent any water from entering the unit. The maximum downwards slope is 1/4 inch.

e. Bad thermopile or thermocouple.

—Replace if necessary.

f. Improper vent cap installation.

—Check for proper installation and freedom from debris or blockage.

6. Glass soots.

a. Flame impingement on logs.

—Check and adjust log position. Contact Empire Comfort

Systems, Inc.

b. Debris around throat of main burner.

—Inspect the opening at the base of the main burner. It is imperative that NO material be placed in this opening.

7. Flame burns blue and lifts off main burner.

a. Insufficient oxygen being supplied.

—Check to make sure vent cap is installed properly and free of debris. Make sure that vent system joints are tight and have no leaks.

—Check to make sure that no material has been placed at the main burner base.

31451-2-1013 Page 49

DIRECT IGNITION LIGHTING INSTRUCTIONS

FOR YOUR SAFETY READ BEFORE LIGHTING

WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION

MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE.

A. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance

• Do not touch any electrical switch

• Do not use any phone in your building.

• Immediately call your gas supplier from a neighbor's phone.

• Follow the gas supplier's instructions.

• If you can not reach your gas supplier, call the fire department.

B. Use only the wall switch or remote control switch to turn the gas control on/off. Any attempted repairs or adjustments should be performed by a qualified service technician. Applying force or attempted repair may result in a fire or explosion.

C. Do not use this appliance if any part has been under water.

Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

LIGHTING INSTRUCTIONS

1. STOP! Read the safety information above.

2. Set the thermostat, if used, to the lowest setting.

3. Turn off all electric power to the appliance.

4. This appliance is equipped with an ignition device that automatically lights the burner. Do not try to light the burner by hand.

5. Open bottom louver assembly.

6. Turn gas line valve to “ON.”

7. Wait five minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “A” in the safety information above. If you do not smell gas, go to the next step.

8. Close bottom louver assembly.

9. Turn on all electric power to the appliance.

10. Set thermostat to desired setting (if available).

11. If the appliance will not operate, follow the instructions “TO

TURN OFF GAS TO APPLIANCE,” and call your service technician or gas supplier.

TO TURN OFF GAS TO APPLIANCE

5. Close bottom louver assembly, or close valve access door.

1. STOP! Read the safety information above.

2. Turn off all electric power to the appliance.

3. Open bottom louver assembly, or open the valve access door.

4. Turn gas line valve to "OFF."

Page 50 31451-2-1013

DIRECT IGNITION WIRING DIAGRAM

Steady ON

2 Flashes

3 Flashes

LED CODES

Normal operation, power ON to control

3 unsuccessful ignition trials

Main burner flame failed 4 times during a single heating cycle

4 Flashes Interrupt power for 5 seconds to reset control

Steady Flash Flame detected out of sequence

Figure 71

OPTIONAL REMOTE CONTROL

Electric (120 volt) Operated Remote Control (FREC)

1. Disconnect 3-prong power cord from receptacle.

2. Remove wire from 120 VAC hot terminal on control module.

3. Connect female terminal from receiver onto 120 VAC hot terminal on control module.

4. Connect remaining wire from remote control (male terminal) to (female terminal) on power cord removed from control module (step 2).

5. Insert electric remote control power cord plug into the junction box on the right side of fireplace.

6. Connect 3-prong plug into receptacle.

31451-2-1013 Page 51

INITIAL START UP GAS LINE PURGE

NOTICE : UNIT MUST BE PROPERLY GROUNDED FOR ELECTRONIC IGNITION TO FUNCTION.

On initial installation, or after extended periods where the fireplace has not been used, gas lines may require purging.

The installer or qualified service person may use the following purge procedures to prevent the delays that would be caused by waiting for the lockout periods between tries for ignition.

PURGE PROCEDURE

1. Remove glass door and place away from the fireplace.

2. Turn on gas shut off valve. Follow ignition procedure.

3. If burner does not light after spark sequence has ended, use an insulated jumper wire (see page 51) between terminal locations

12 and 13 for fast reset function.

4. Interrupt power for 5 seconds. The green indicator light will blink 4 times repetitively. Then retry for ignition.

5. Allow time for any raw gas to dissipate and repeat steps 3 and

4 until ignition is achieved.

6. Turn burner off and install glass door frame assembly.

7. Test ignition of burner with glass door in place.

INSULATED

JUMPER WIRE

DIRECT IGNITION TROUBLESHOOTING

With proper installation and maintenance, your new Direct Vent Gas Fireplace will provide years of trouble-free service. If you do experience a problem, refer to the troubleshooting guide below. This guide will assist a qualified service person in the diagnosis of problems and the corrective action to be taken.

SYMPTOM

No spark when system is turned to “ON” and reset cycle* has been completed

Main burner will light, but igniter continues to spark for several seconds and then locks out (module will show two blinks on indicator light).

Spark for six seconds at ignitor, but no ignition of burner. purged

CHECK

Check for 120V between black “hot” line at control module and “white” return at module

Disconnect power to fireplace junction box and check that the "Hot-Black" wire is connected to the gold receptacle screw side, and that the "Neutral - White" wire is connected to the silver screw side. The green ground must also be secured for proper operation.

a. Check that gas is turned on and system b. Check that tips of ignitor are directly above ports on main burner. Spark is between electrodes and not from one electrode to burner.

light codes.

ACTION

If 120V not present, check fuse or circuit breaker or repair wiring leading to fireplace.

Prior to rewiring the fireplace junction box, check operation of the control system by running a grounded extension cord from another standard wall receptacle outlet to the fireplace control system. Follow purge reset procedure above in order to clear the

Turn gas on and/or purge system

Position electrodes so tips are directly above burner port ports and about ¼" to

If 120V present, but gas valve does not click, replace gas valve.

Spark for six seconds, main burner lights, but goes out when spark stops.

Main burner lights normally and then goes out.

c. Check for 120V at each coil on the gas valve and listen for click, indicating gas valve is opening.

Check for clean ground path between electrode bracket and fireplace chassis.

Check wiring to wiring diagram label. Check for broken electrode on high-tension lead attachment to module.

a. Check thermostat if applicable.

Clean, position according to wiring diagram, and repair defective electric connections.

If all electrical connections are clean and correct, replace module.

Turn thermostat up to call for heat or replace

Replace spark electrode assembly b. Check high-tension lead and connector for shorts. c. Refer to installation instructions troubleshooting guide for issues such as venting.

Repair as required.

Page 52 31451-2-1013

PROPANE/LP GAS CONVERSION

The conversion shall be carried out in accordance with the requirements of the provincial authorities having jurisdiction and in accordance with the requirements of the CSA B149.2 installation code (Canada) and with the requirements of the

National Fuel Gas Code Z223.1/NFPA 54 (United States).

WARNING

This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer's instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in this instruction is not followed exactly, a fire, explosion, or production of carbon monoxide may result causing property damage, personal injury, or loss of life. The qualified service agency is responsible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer's instructions supplied with the kit.

Installer notice: Using an ink pen, fill out the required information on the conversion label. Remove the backing from label and stick label in a visible position on bottom of fireplace close to gas valve.

Installer notice: These instructions must be left with the appliance.

Instructions for converting your direct ignition fireplace from natural gas to propane/LP gas.

All direct ignition fireplaces are shipped from the factory equipped to operate on natural gas. To convert the direct ignition fireplace to operate on propane/LP gas, follow the instructions on this page.

Please see the appropriate parts list for your model for parts included with the direct ignition fireplace.

Check the items in the kit with the parts list. Notify the supplier of any items that are missing before installing the conversion kit.

1. Turn off the gas supply.

2. Turn off the electrical supply to the appliance if so equipped.

3. Remove top louver and lower bottom louver.

4. Remove glass frame assembly.

5. Remove logs from burner assembly.

VALVE CONVERSION - See Page 43

6. Remove plastic cap from regulator fitting. Unscrew fitting using a 11/16" wrench. Turn fitting over so end of fitting marked "LPG"

(red) screws into valve. Tighten fitting (snug only). Replace plastic cap.

7. Remove 1/4" screw from air shutter.

8. Located to the right of electrodes is a burner hold-down tab.

Using needle-nose pliers, bend burner hold-down tab off the main burner.

9. Remove main burner by pivoting main burner forward as you slide main burner from left to right. Be careful as you remove main burner in order to protect the electrodes from being damaged.

10. Remove air shutter from orifice fitting.

11. Remove natural gas main burner orifice from orifice fitting.

12. Install propane/LP main burner orifice marked 1.55 mm.

Important: Failure to install the correct orifice will result in unit over-firing that could overheat the appliance and result in a fire.

13. Replace air shutter onto orifice fitting. Air shutter must be threaded and bottomed-out onto orifice fitting.

14. Replace main burner onto burner assembly. Place main burner beneath electrodes, slide main burner from right to left into burner location, and pivot main burner away from you and into air shutter.

15. Set air shutter opening at 1/4" FULL OPEN. Tighten air shutter in place with 1/4" screw from step 7.

16. Using needle-nose pliers, bend burner hold-down tab over main burner.

17. Refer to log placement, page 44 to place logs onto burner assembly.

18. Loosen screw and attach a manometer or pressure gauge to the outlet pressure tap of the control valve.

19. Turn on the gas supply. Turn on the electrical supply to the appliance. Check for gas leaks using soap and water solution or leak detection solution. Bubbles indicate a leak that MUST be corrected. Do not use an open flame to test for gas leaks.

20. Check the air shutter opening. See chart and illustration below.

21. Relight the main burners and verify proper burner ignition and operation.

22. With the main burner burning, read the pressure on the manometer or pressure gauge. The pressure on the gauge should read between 9.8" and 10.2" w.c.

23. Turn off the gas supply. Turn off the electrical supply to the appliance.

24. Remove the manometer or pressure gauge. Tighten the screw in the pressure tap.

25. Turn on the gas supply. Turn on the electrical supply to the appliance.

26. Immediately test all gas line connections and the control valve for gas leaks using a soap and water solution or other gas detection solution. Bubbles indicate a leak that MUST be corrected. Do not use an open flame to test for gas leaks.

27. Using a ball point pen, fill out the conversion label that is supplied with the conversion kit. Place the conversion label adjacent to the rating plate.

28. Replace glass frame assembly.

29. Reinstall top and bottom louvers.

30. Test operation of fireplace once again. Allow the fireplace to operate for at least 10 minutes and check flame coloration.

Flames on rear of burner should be yellow without any orange-colored tip. Minor adjustment of the air shutter may be necessary to "tune in" the proper flame color.

31451-2-1013 Page 53

IPI ELECTRONIC SYSTEM OPERATING INSTRUCTIONS

5.25 VDC ELECTRONIC CONTROL VALVE

The electronic control valve system includes the ability to switch the pilot from a standing pilot mode to an intermittent pilot mode.

• IPI Mode - In the Intermittent Pilot mode, when the unit is turned ON, it will cause spark to the pilot, light the pilot, then allow the burner to light. When the unit is turned to

OFF, both the burner and pilot will be OFF.

• CPI Mode - In the Continuess Pilot mode, the pilot remains ON continuously even when the burner is turned

OFF.

Note: A small toggle switch is located on the front of the module tray that is used to switch from IPI (left) to the CPI (right). See

Figure 72.

When the unit is turned to ON, the electrical current will energize a spark to the pilot igniter. Once the pilot sensor heats up (after a few seconds), the valve will be energized, allowing gas to flow to the burner.

OPTIONAL REMOTE CONTROLS

Optional remote controls are available for use with this appliance.

It is recommended that the remote receiver be placed either in a wall outlet box with extended wiring, on the fireplace hearth, behind the left side surround panel, or in the control compartment area as far forward in the insert as possible.

The placement options for the remote receiver are given to allow flexibility, however battery life will be extended when the receiver is placed in cooler areas.

To connect the remote receiver to the appliance, first disconnect the ON/OFF switch wires from the white and green wire connectors and connect the wires from the remote receiver to the green and white wire connectors. See Figure 72.

Follow the instructions included with the remote control for programming and other operational information.

1. Follow the SAFETY and LIGHTING INSTRUCTIONS for Intermittent Pilot controls found in this manual, and on labels found in the control compartment located in the lower cavity of the appliance.

2. During the operating season (or in power outage periods), it is recommended that the pilot remain in the CPI (standing pilot mode) to reduce cold start issues, and/or conserve battery backup power during a power outage.

3. The gas valve has inlet and outlet pressure taps as shown in

Figure 72. Refer to page 10 for gas pressure requirements.

Note: The gas control has a manual HI/LO flame adjustment knob (regulator) that allows you to increase or decrease the height of the burner flame. See Figure 72. Rotate the HI/LO knob counterclockwise to “HI” to increase the flame height, and clockwise to “LO” to decrease the flame height.

Page 54

Figure 72

31451-2-1013

IPI ELECTRONIC SYSTEM WIRING DIAGRAM

If any of the original wire as supplied with this unit must be replaced, it must be replaced with equivalent gauge and temperature rated wire.

This appliance is only for use with the type of gas indicated on the rating plate and may be installed in an aftermarket, permanently located, manufactured (mobile) home where not prohibited by local codes. This appliance is not convertible for use with other gases, unless a certified kit is used.

CAUTION: Do not operate the appliance with lliner(s) removed, cracked or broken. Replacement of the liner(s) should be done by a licensed or qualified service person.

WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer, service agency or the gas supplier.

31451-2-1013 Page 55

INTERMITTENT PILOT LIGHTING INSTRUCTIONS

FOR YOUR SAFETY READ BEFORE LIGHTING

WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

A. This appliance has a pilot which can be lighted with the manual on/off switch, a remote control, or by switching the receiver switch to the “ON” position. When lighting the pilot, follow these instructions exactly.

B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance. Do not touch any electrical switch. Do not use any phone in your building. Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you can not reach your gas supplier, call the fire department.

C. Use only the remote control or manual remote receiver switch to operate the gas valve. Never use tools. If valve does not operate, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.

D. Do not use this appliance if any part has been under water.

Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

LIGHTING INSTRUCTIONS

1. STOP! Read the safety information above.

2. Turn OFF electric power to the appliance.

3. Remove front surround panel assembly or bottom louver if included.

4. Turn gas cock counterclockwise to “On” position.

5. Wait ten minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety information above on this page. If you do not smell gas, go to the next step.

6. Turn ON electric power to the appliance.

7. Find pilot - Follow metal tube from gas control. The pilot is behind the burner on the right side.

8. Turn main flame to on. If the pilot does not light within 60 seconds, stop and go to Step 5.

9. Refer to remote control instructions for detailed information, control features, and operation. Note: There is a CPI/IPI switch that allows for a continuous standing pilot mode or an intermittent pilot mode. See appliance manual for location of this switch. If the pilot or burner does not stay lit (in the standing pilot mode), stop and immediately call a qualified service technician or gas supplier.

10. If the burner or pilot does not operate properly after several

to “OFF” and call tries, turn the gas cock clockwise your service technician or gas supplier.

11. Replace the front surround assembly or close bottom louver assembly.

12. Operation of the gas valve is controlled by a manual on/ off switch or a hand held remote control. Refer to remote instructions for detailed operation information.

GAS COCK

TO TURN OFF GAS TO FIREPLACE

1. Turn off all electric power to the appliance if service is to be performed (if applicable).

2. Gain access to control compart. Remove surround panel assembly if necessary.

3. Locate On/Off gas cock and turn clockwise to

“OFF”. Do not force.

4. Close bottom louver assembly, if included.

Page 56 31451-2-1013

INTERMITTENT PILOT CONTROL SYSTEM TROUBLESHOOTING

Brief Description of the Components

The gas valve is fitted with a manual HI/LO knob to allow for manual modulation of the gas outlet pressure to the appliance burner.

The controls are designed to be used with either LPG or Natural

Gas and can be converted by use of an OEM supplied conversion kit.

The Digital Fireplace Control (DFC) is an automatic gas ignition system based on a single microcontroller core. This control manages all functions related to ignition, flame sensing and supervision for atmospheric applications.

The DFC can be set to provide continuous or intermittent ignition control sequences and flame monitoring with safety shutdown in case of failure.

The DFC is set up as a stand alone (AC powered system with battery back up. See Lighting Instructions on page 56 and Wiring

Diagram on page 55.

Troubleshooting

Before proceeding with the procedures in the following troubleshooting table, verify that the power supply (AC/DC adapter) is present and that the batteries inside the receiver and/or optional battery pack are fresh and installed with correct polarity.

Make sure all the connections between the wire harnesses and system components are proper and positive.

Verify that the static inlet pressure meets the manufacturer’s recommended inlet pressure. If necessary adjust the line pressure regulator.

If the recommended actions for the following troubleshooting chart do not help to address the problem consider replacing wiring harnesses.

WARNING:

Any actions performed on the gas valve must be performed in accordance with this instruction manual. Likewise, any actions performed on the DFC or other system components must be done in accordance with the individual component instructions.

Replacement of components must be performed in accor dance with this instructions manual.

31451-2-1013 Page 57

INTERMITTENT PILOT CONTROL SYSTEM TROUBLESHOOTING

1

If the DFC giving signal lock out:

The board should be unlocked to reinitiate a pilot flame ignition (for the correct unlock sequence refer to the DFC Use and Installation

Instructions).

NO

YES

Is the DFC board in lock out?

NO

1.

Verify the electrical connections’ integrity and make sure they are in accordance with the relevant system wiring diagram. If necessary replace the wire harness.

2.

Replace the DFC board.

YES

Was observed spark at the Pilot Hood before the DFC board locked out?

NO

1.

Check the spark electrode positioning - adjust as necessary.

2.

Replace the pilot assembly.

3.

Verify the electrical connections’ integrity and make sure they are in accordance with the relevant system wiring diagram. If necessary replace the wire harness.

4.

Replace the DFC board.

YES

1.

Verify the electrical connections’ integrity and make sure they are in accordance with the relevant system wiring diagram. If necessary replace the wire harness.

2.

If pilot flow adjuster screw is not sealed:

Check if pilot flow adjust screw is set correctly in accordance with the appliance manufacturer instructions. If necessary correct it.

3.

Replace pilot tube or complete pilot assembly.

4.

Replace the pilot orifice with a new orifice of correct size, and type, or replace the pilot assembly. Under all circumstances follow the appliance manufacturer’s service instructions.

5.

Remove the provided wiring harnesses from

Ev1 of gas valve (red base), and verify voltage at ignition between the Ev1 terminal and the ground connection on teh valve body. If the voltage is greater than 0 then Replace Valve. Otherwise

Replace DFC.

YES

1.

Replace the pilot assembly.

2.

Replace the DFC board.

Spark continues while the pilot is ON.

NO

2

Page 58 31451-2-1013

INTERMITTENT PILOT CONTROL SYSTEM TROUBLESHOOTING

31451-2-1013 Page 59

RF OPERATING INSTRUCTIONS

RF VALVE OPERATION (AF-4040 Electronic Gas Valve system only)

Please refer to the separate instructions for detailed operation and programming of the Multi-function Remote Control.

The AF-4040 Electronic Gas Control Valve features a Remote controlled High/Low Variable - 6 Volt DC Motor Drive. This gas control uses a spark to pilot burner assembly. For use with Propane or natural gas (pre-set at the factory).

This gas control system includes the items identified in Figure 73.

SPECIAL FEATURES ON THE CONTROL MODULE

The Control Module has two special pilot mode features built into the system.

wires on the Control Module.

3. When the remote/off switch is in the REMOTE position the appliance will operate from the Remote Control transmitter.

The Control Module must be programmed to the Remote Control.

1. To program, located the learn button on the left side of the

Control Module. NOTICE : Press and release the learn button.

There will be a beep sound from the Control Module, then press any key on the remote transmitter. Once the internal receiver accepts the transmitter code there will be a series of confirming beeps.

2. To switch between the NG and LP step motor settings, press and hold the learn button for 20 seconds. The module should emit a short beep (less than 1 second) to indicate that the control was switched from NG (default setting) to LP. When switching back from LP to NG, the control should emit a long beep (3 seconds).

CONTINUOUS PILOT FEATURE: This allows the user to change from a spark to pilot system to a standing pilot system.

1. There is a switch located on the right side of the Control

Module (#4) that reads CONTINUOUS PILOT ON/OFF. This switch will allow the user to select the pilot mode of operation.

2. When the continuous pilot switch is in the OFF position and the appliance turned ON, the pilot will spark and light, then the main burner will light as well. When the appliance is turned

OFF, the pilot and main burner will shut OFF.

3. When the continuous pilot switch is in the ON position and the appliance is turned ON, the pilot will spark and light. Then when the appliance is turned OFF the pilot will remain ON, but the main burner will shut OFF.

NOTICE : The Continuous pilot mode setting is generally recommended on Direct Vent appliances during cold climate seasons to help keep the firebox warm.

POWER SUPPLY SYSTEM

The Gas Control system is powered by a standard 110 volt AC through a 6.0 volt DC adaptor. The AC adaptor is connected to the

Control Module with two 1/4” female terminals.

This control system also includes a Battery Back-up pack that allows the Gas Control system only to operate in the event of a power outage.

NOTICE : The Accent Light and/or Blower features will not operate during a power outage.

NOTICE : All Batteries should be replaced at least once each year, preferably at the beginning of the heating season.

REMOTE CONTROL FEATURE: The Control Module has a built in remote control receiver which allows the user to program the hand held remote transmitter.

1. There is a switch located on the right side of the Control Module that reads REMOTE/OFF.

2. When the remote/off switch is in the OFF position the appliance will operate from an appliance mounted rocker switch

(#3) or optional wall switch connected to the two BROWN

WARNING

Fire or explosion hazard. Can cause property damage, sever injury or death.

Do not attempt to take apart the gas control or to clean it. Improper assembly and cleaning can cause unreliable operation.

7

3

6

Page 60

1

Index No.

1

2

3

4

5

6

7

Not Shown

2

4

Part No.

R10418

R10415

R2522

R11007

R10416

R10419

R10423

R10424

R11006

Figure 73

Description

Battery Back-up

AF Valve, RF

Off/On Switch

AF Control Module

AF Extension Module

AC Adapter

Pilot Assembly - Nat

Pilot Assembly - LP

Remote Control, RF

5

31451-2-1013

RF MAINTENANCE INSTRUCTIONS

MAINTENANCE

Maintenance frequency must be determined individually for each application. Some considerations are:

• Exposure to water, dirt, chemicals and heat can damage the gas control and shut down the control system.

• Cycling frequency. Appliances that may cycle 20,000 times annually should be checked monthly.

• Intermittent use. Appliances that are used seasonally should be checked before shutdown and again before the next use.

• Dusty, wet or corrosive environment. Because these environments can cause the gas control to deteriorate more rapidly, the system should be checked more often.

• Any control should be replaced if it does not perform properly on checkout or service. In addition, replace any module if it is wet or looks like it has been wet.

TROUBLESHOOTING

IMPORTANT: All service and trouble-shooting procedures should be performed by an experienced qualified service technician.

If the pilot will not stay lit:

1. Confirm that the “S” wire and the “I” wire are properly connected to the Control Module “S” and “I” terminals.

2. Confirm that the Spark to Pilot burner is properly grounded to the Gas Control Valve and the Control Module.

3. Check the power source from the 6-volt power adaptor or the

Battery Back-up pack connection and condition of batteries.

4. Check the position of the CONTINUOUS PILOT switch on the

Control Module. If main burner does not come ON when the manual switch and remote control is turned ON: a. Confirm that the pilot sparks and lights.

b. Check the two pin plastic connectors that plug into the face of the Gas Control valve.

c. Confirm that the Gas Control valve is properly grounded to the Control Module.

SERVICE

Do not disassemble the gas control; it contains non-replaceable components. Attempted disassembly or repair can damage the control.

Exactly follow the warnings and the lighting instructions.

1. Before lighting, smell around the appliance area for gas. If the appliance uses LP (bottled) gas, be sure to smell next to the floor because LP gas is heavier than air. If you smell gas, immediately shut off the manual valve in the gas piping to the appliance or on LP at the tank. Do not try to light any appliance. Do not touch any electrical switch or use the phone.

Leave the building and call your gas supplier. If your gas supplier cannot be reached, call the fire department.

2. The gas control must be replaced if it has been flooded with water. Call a qualified service technician.

3. The gas control is a safety device. It must be replaced in case of any physical damage such as bent terminals, missing parts, stripped threads, or evidence of exposure to excessive heat.

OPTIONAL GAS CONVERSION KITS

Please contact your dealer or distributor for the proper Conversion kit for these fireplace models. Conversion kits will include complete instructions, minimum rate screw, plus the pilot and main burner orifice for the gas type required. The AF-4040 Electronic

Gas Control Valve is convertible to use either natural or propane gas by simply turning a small Rotary knob located at the front of the gas valve. This rotary knob is located under a small rubber cap and should only be adjusted when converting gas type.

CAUTION

The gas type has been pre-set at the factory and must not be changed unless a complete conversion is made which includes changing of the gas pilot injector, minimum rate screw and main burner orifice.

Follow the operating instructions provided by the manufacturer of your heating appliance.

31451-2-1013 Page 61

RF WIRING DIAGRAM

NOTICE : For "RF" Fireplace models with Premium Multi-Function Remote Control, Refer to the separate instructions for operation of the remote control system.

Figure 74

Page 62 31451-2-1013

RF STANDING PILOT LIGHTING INSTRUCTIONS

FOR YOUR SAFETY READ BEFORE LIGHTING

WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR

EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF

LIFE.

A. This appliance has a pilot which must be lighted with the remote control. When lighting the pilot, follow these instructions exactly.

B. BEFORE LIGHTING, smell around the appliance area for gas. Be sure to smell next to the floor because some gas in heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.

• Do not touch any electrical switch.

• Do not use any phone in your building.

• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions. If you can not reach your gas supplier, call the fire department.

C. Use only the remote control to operate the gas control knob. Never use tools. If valve does not operate, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.

D. Do not use this appliance if any part has been under water.

Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

LIGHTING INSTRUCTIONS

1. STOP! Read the safety information above.

2. Turn OFF electric power to the appliance.

3. Open bottom louver assembly.

4. Turn gas cock counterclockwise to "ON" position.

5. Wait ten minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow

"B" in the safety information above on this label. If you do not smell gas, go to the next step.

6. Turn ON electric power to the appliance.

7. Find pilot - Follow metal tube from gas control. The pilot is behind the burner on the right side.

8. Using the remote control, turn main flame to "ON." If the pilot does not light within 60 seconds, stop and go to Step

5.

9. Refer to remote control instructions for detailed information, control features, and operation. Note: There is a switch on the side of the Electronic Control Module that allows for a continuous standing pilot mode or an intermittent pilot mode. See appliance manual for location of this switch.

If the pilot or burner does not stay lit (in the standing pilot mode), stop and immediately call a qualified service technician or gas supplier.

10. If the burner or pilot does not operate properly after several tries, turn the gas control knob clockwise

to "OFF" and call your service technician or gas supplier.

11. Close bottom louver assembly.

12. Operation of the gas valve, blower, and/or optional light must be controlled by using the hand held remote control.

Refer to remote instructions for detailed operation information.

TO TURN OFF GAS TO APPLIANCE

1. Turn off all electric power to the appliance if service is to be performed (if applicable).

2. Open bottom louver assembly.

3. Locate On/Off gas cock and turn clockwise to

"OFF." Do not force.

4. Close bottom louver assembly.

31451-2-1013 Page 63

MAINTENANCE AND SERVICE

NOTICE

It is normal for appliances fabricated of steel to give off some expansion and/or contraction noise during the start up or cool down cycle. Similar noises are found with your furnace heat exchanger or car engine.

It is not unusual for your gas fireplace to give off some odor the first time it is burned. This is due to the curing of the paint and any undetected oil from the manufacturing process.

Please ensure that your room is well ventilated - open all windows.

It is recommended that you burn your fireplace for at least six hours the first time you use it. If optional fan kit has been installed, place fan in the “OFF” position during this time.

IMPORTANT: Turn off gas before servicing appliance. It is recommended that a qualified service person perform these checkups at the beginning of each heating season.

• Clean Burner and Control Compartment

Keep the control compartment, logs, and burner areas surrounding the logs clean by vacuuming or brushing at least twice a year.

Cleaning Procedure

1. Turn off pilot light at gas valve.

2. Remove glass front. (See Glass Removal)

3. Vacuum burner compartment.

4. Reinstall glass front.

5. Ignite pilot. (See Lighting Instructions)

6. Operate the pilot burner. If it appears abnormal call a service person.

• Check Vent System

The appliance and venting system should be inspected before initial use and at least annually by a qualified service person.

Inspect the external vent cap on a regular basis to make sure that no debris is interfering with the air flow.

Glass Cleaning

It will be necessary to clean the glass periodically. During start-up condensation, which is normal, forms on the inside of the glass and causes lint, dust and other airborne particles to cling to the glass surface. Also initial paint curing may deposit a slight film on the glass. It is therefore recommended that the glass be cleaned two or three times with a non-abrasive household cleaner and warm water

(we recommend gas fireplace glass cleaner). After that the glass should be cleaned two or three times during each heating season depending on the circumstances present.

General Glass Information

Only glass approved for use by the manufacturer in fireplace may be used for replacement. The glass replacement should be done by a licensed or qualified service person.

CAUTION :

1. The use of substitute glass will void all product warranties.

2. Care must be taken to avoid breakage of the glass.

3. Under no circumstances should this appliance be operated without the glass front or with a broken glass front. Replacement of the glass (with gasket) as supplied by the manufacturer should be done by a qualified service person.

4. Do not abuse the glass by striking or hitting the glass.

CAUTION

Do not use abrasive cleaners on glass. Do not attempt to clean glass when glass is hot.

WARNING

Do not operate appliance with the glass front removed, cracked or broken. Replacement of the glass should be done by a licensed or qualified service person.

Page 64 31451-2-1013

MAINTENANCE AND SERVICE

Reassembly and Resealing Gas Accumulation Relief System

Glass Frame Assembly and Combustion Chamber

Whenever the glass frame assembly is pivoted open by a delayed ignition in the main burner, the glass frame assembly gaskets and combustion chamber must be examined by a qualified service person for damage. All damaged gaskets on the glass frame assembly and combustion chamber must be replaced by a qualified service person. If damage occurs to the combustion chamber, it must be replaced by a qualified service person. Contact Empire Comfort

Systems, Inc. for replacement parts.

Glass Removal and Replacement

1. Remove decorative front doors (where applicable) by opening and lifting straight up.

2. Remove decorative front by tilting lower portion forward to release ball catch and lifting front off mounting bracket. See

Figure 75.

3. Release two glass frame clamps at bottom of firebox.

4. Remove glass frame.

5. Place glass frame onto firebox.

6. Attach two glass frame clamps at bottom of firebox.

7. Replace decorative front by hooking front mounting brackets.

Be sure to lower front with slight angle to keep ball clasp from scratching the front of appliance. Push in lower portion to lock ball clasp. See Figure 76.

8. Replace decorative front doors by aligning hinges over posts.

Figure 76

31451-2-1013

Figure 75

Page 65

Index

No.

36

36

37

38

39

40

41

30

31

32

33

34

35

25

26

27

27

28

29

18

20

22

22

23

24

12

13

14

15

16

17

10

11

8

9

6

7

3

4

5

1

2

R7649

P200

P258

P256

R5676

11499

11377

17370

21533

18801

R2423

-

R7578

R7577

17161

29057

R10947

R2708

R3436

25604

17162

R3492

17357

26070

25495

23343

18809

R7611

R7612

R7617

11269

DVP36DP31(N,P)

R7654

17425

R7566

R7573

17155

M163

17142

R7575

17141

R7574

25812

R7649

P200

P258

P256

R5676

11499

11377

17370

26632

17369

R2423

-

R7733

R7733

2020

29057

R8147

-

-

25604

17162

R3492

17357

26070

25495

23343

18809

-

-

R7617

11269

Part Number

DVP36DP51N DVP36DP71(N,P)

R7654 R7654

17425

R7566

R7573

17155

17425

R7566

R7573

17155

M163

17142

R7575

17141

R7574

25812

M163

17142

R7575

17141

R7574

25812

25604

17162

R3492

17357

26070

25495

23343

18809

R10424

R10423

R9189

11269

R7649

P200

P258

P256

R5676

11499

11377

17370

21533

31458

R2423

R1109

R11126

R11125

29400

29057

R11034

-

R2522

PARTS LIST

Description

DVP36DP91(N,P)

R7654

17425

R7566

R7573

17155

M163

17142

R7575

17141

R7574

25812

25604

17162

R3492

17357

26070

25495

23343

18809

R10424

R10423

R9189

11269

-

P200

P258

P256

R5676

11499

11377

17370

21533

18801

R2423

-

Insulation, Flue

Retainer, 4” Flue

Vent Adapter

Inlet Vent Gasket

Flue Outlet Assembly

Gasket, Flue Outlet

Cover Plate, Vent

Vent Cover Plate Gasket

Cover Plate, Flue

Gasket, Flue Outlet

Top Standoff (Qty. 2)

Nailing Flange (Qty. 4)

Junction Box

3-Prong Receptacle

Heat Shield (Junction Box)

Top Shield

Top Inner Heat Shield

Baffle, Flue Vent

Glass Door Assembly

Pilot Assembly (LPG)

Pilot Assembly (Nat)

Pilot Gasket

Gas Line Fitting

Fan Control Switch

Orifice Fitting

Orifice (LPG)

Orifice (Nat)

Air Shutter

Burner Support - Left

Burner Support - Right

Burner Assembly

Burner Base Plate Assembly

Tubing Assembly

5/16" Male Connector

Bushing, Flush

R10415 & R10428 Gas Valve (LPG)

R10415 & R10430 Gas Valve (Nat)

2630

29057

-

-

-

Gas Valve Bracket

Spring Retainer Assembly

Wire Assembly

Piezo Ignitor

Remote/On/Off Switch

Page 66

USE ONLY MANUFACTURER’S REPLACEMENT PARTS. USE OF ANY OTHER PARTS COULD CAUSE INJURY OR DEATH.

31451-2-1013

PARTS LIST

Index

No.

68

69

70

71

74

75

62

63

64

65

66

67

55

56

57

58

59

60

52

53

54

76

77

N/S

N/S

N/S

N/S

N/S

N/S

N/S

47

48

49

50

51

43

44

45

46

-

-

-

-

R9645

R5668

-

-

-

-

-

-

25520

25129

R8598

R8602

R8598

R8606

-

-

-

-

-

-

-

18704

18704

DVP36DP31(N,P)

-

-

-

-

-

FBB4

-

R10352

R10350

R10351

R10349

-

N/S = Not Shown

See page 44 for log part numbers.

R7613

R7590

R7589

19545

-

-

-

-

-

-

R9645

-

R7616

-

-

-

-

-

25520

25129

R8598

R8602

R8598

R8606

-

18704

18704

Part Number

DVP36DP51N

R7615

DVP36DP71(N,P)

-

R8144

-

-

R11123

-

-

FBB4

-

-

FBB4

-

-

R10352

R10350

R10351

R10349

-

R10352

R10350

R10351

R10349

R11122

-

-

-

-

29382

R2667

R11334

31500

-

-

R9645

-

R11128

-

R11127

-

-

-

25520

25129

R8598

R8602

R8598

R8606

-

18704

18704

DVP36DP91(N,P)

-

-

-

18880

18858

R7731

R7831

R10352

R10350

R10351

R10349

R10418

-

-

-

-

-

-

-

-

R10428 (# 52)

R10430 (# 37)

R9645

-

R10419

R10416

R11007

R10499

R10497

R10498

25520

25129

R8598

R8602

R8598

R8606

R11006

18704

18704

Description

Cord Set

Wire Harness (DI)

Wire Harness (IP)

Blower Shield

Blower Base

Blower Assembly

Blower Wire Assembly

Twig, Top Branch

Log, Front Left

Log, Front Right

Log, Rear

Battery Back-up

AC Adapter

120V Extension Module

Control Module

Extension Wire Harness (5 pin)

Wire Harness (4 Pin )

Wire Harness (8 Pin)

Heat Shield, (Flue)

Mounting Brace

Optional Brick Panel, Side (Left)

Optional Brick Panel, Back

Optional Brick Panel, Side (Right)

Optional Brick Panel, Top

Spark Plug Wire

Spark Ignitor, PSE

Gasket, PSE Ignitor

Spark Ignitor Shield

Module Tray

Wire Assembly

Sensor Wire

Pilot Shield

Minimum Rate Screw - #52 (LPG)

Minimum Rate Screw - #37 (NAT)

Replacement Halogen Bulb

Ignitor Wire, Piezo

Remote Control, RF

Decorative Rock (1 lb)

Rockwool (0.1 oz)

USE ONLY MANUFACTURER’S REPLACEMENT PARTS. USE OF ANY OTHER PARTS COULD CAUSE INJURY OR DEATH.

31451-2-1013 Page 67

PARTS VIEW

Page 68 31451-2-1013

MASTER PARTS DISTRIBUTOR LIST

To Order Parts Under Warranty, please contact your local Empire dealer. See the dealer locator at www.empirecomfort.

com. To provide warranty service, your dealer will need your name and address, purchase date and serial number, and the nature of the problem with the unit.

To Order Parts After the Warranty Period, please contact your dealer or one of the Master Parts Distributors listed below.

This list changes from time to time. For the current list, please click on the Master Parts button at www.empirecomfort.com.

Please note: Master Parts Distributors are independent businesses that stock the most commonly ordered Original

Equipment repair parts for Heaters, Grills, and Fireplaces manufactured by Empire Comfort Systems Inc.

Dey Distributing

1401 Willow Lake Boulevard

Vadnais Heights, MN 55101

Phone: 651-490-9191

Toll Free: 800-397-1339

Website: www.deydistributing.com

Parts: Heater & Hearth

Victor Division of F. W. Webb Company

200 Locust Street

Hartford, CT 06114

Phone: 860-722-2433

Toll Free: 800-243-9360

Fax: 860-293-0479

Toll Free Fax: 800-274-2004

Websites: www.fwwebb.com & www.victormfg.com

Parts: Heater & Hearth and Grills

East Coast Energy Products

10 East Route 36

West Long Branch, NJ 07764

Phone: 732-870-8809

Toll Free: 800-755-8809

Fax: 732-870-8811

Website: www.eastcoastenergy.com

Parts: Heater & Hearth and Grills

HOW TO ORDER REPAIR PARTS

Parts Not Under Warranty

Parts can be ordered through your Service Person, Dealer, or a Master Parts Distributor. See this page for the Master Parts Distributors list. For best results, the service person or dealer should order parts through the distributor. Parts can be shipped directly to the service person/dealer .

Warranty Parts

Warranty parts will need a proof of purchase and can be ordered by your Service Person or Dealer. Proof of purchase is required for warranty parts.

All parts listed in the Parts List have a Part Number. When ordering parts, first obtain the Model Number and Serial Number from the name plate on your equipment. Then determine the Part Number ( not the Index Number) and the Description of each part from the following illustration and part list. Be sure to give all this information . . .

Appliance Model Number

Appliance Serial Number

Part Description

Part Number

Type of Gas (Propane or Natural)

Do not order bolts, screws, washers or nuts. They are standard hardware items and can be purchased at any local hardware store.

Shipments contingent upon strikes, fires and all causes beyond our control.

31451-2-1013 Page 69

FBB4 VARIABLE SPEED BLOWER INSTALLATION

Attention: Install blower assembly before connecting gas inlet supply line

NOTICE : Junction box on right side of fireplace must be prewired at time of fireplace installation for use with blower assembly. It is recommended that an ON/OFF wall switch be installed that will activate the power supply to the furnace by a qualified electrician.

1. If installed, turn OFF gas supply to fireplace.

2. If applicable, turn OFF electric supply to fireplace.

3. Lower bottom louver on fireplace.

4. Refer to page 72, "Junction Box Wiring Installation Instructions" to complete wiring of junction box.

Attention: If installed, do not damage gas inlet supply line when blower assembly is inserted into fireplace. If necessary, remove gas inlet supply line.

5. Insert blower assembly into interior, bottom of fireplace.

Position blower assembly behind gas valve, align notch on back of blower assembly with center screw on fireplace back and push blower assembly against fireplace back. The magnets on the back and bottom of blower assembly will sufficiently hold blower assembly in place.

6. Position speed control box to the right of gas valve. Attach speed control box to bottom of fireplace. The magnets on bottom of speed control box will sufficiently hold speed control box in place.

7. With base (flush face) of fan control switch facing upward, insert base of fan control switch under the mounting tabs on valve bracket. The base (flush face) of fan control switch must be in contact with bottom of firebox.

8. Insert power cord plug into junction box.

9. Close bottom louver on fireplace.

10. Installation of FBB4 optional variable speed blower assembly is completed.

Wiring

The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70 , if an external electrical source is utilized. This appliance is equipped with a three-prong [grounding] plug for your protection against shock hazard and should be plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug.

For an ungrounded receptacle, an adapter, which has two prongs and a wire for grounding, can be purchased, plugged into the ungrounded receptacle and its wire connected to the receptacle mounting screw. With this wire completing the ground, the appliance cord plug can be plugged into the adapter and be electrically grounded.

CAUTION

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

Blower Motor

The blower motor does not have oiling holes. Do not attempt to oil the blower motor.

Blower Wheels

The blower wheels will collect lint and could require periodic cleaning. If the air output decreases or the noise level increases, it indicates a dirty blower wheel. Remove fan and clean blower wheels.

WARNING

Unplugging of blower accessory will not stop the heater from cycling. To turn off gas to the heater (millivolt model): push in gas control knob slightly and turn clockwise to "OFF." Do not force. To turn off gas on direct ignition model, turn gas line valve to "OFF."

FAN SWITCH

* NOTICE

FAN KIT

SEE NOTE*

JUNCTION BOX

SPEED CONTROL

VALVE BRACKET

SWITCH HOLDER

(TOP OF VALVE BRACKET)

: Refer to Junction Box wiring instructions on page 72 for proper operation.

Page 70 31451-2-1013

FBB4 VARIABLE SPEED BLOWER INSTALLATION

1

2

3

4

R7731 BLOWER MOTOR

31920 SWITCH ASSEMBLY

R4192 SPEED CONTROL KNOB

R4186 SPEED CONTROL

31451-2-1013 Page 71

JUNCTION BOX WIRING INSTALLATION INSTRUCTIONS

CAUTION: ALL WIRING SHOULD BE DONE BY A QUALIFIED ELECTRICIAN AND SHALL BE IN COMPLIANCE WITH ALL

LOCAL, CITY AND STATE BUILDING CODES. BEFORE MAKING THE ELECTRICAL CONNECTION, MAKE SURE THAT MAIN

POWER SUPPLY IS DISCONNECTED. THE APPLIANCE, WHEN INSTALLED, MUST BE ELECTRICALLY GROUNDED IN ACCOR-

DANCE WITH LOCAL CODES OR, IN THE ABSENCE OF LOCAL CODES, WITH THE NATIONAL ELECTRICAL CODE ANSI/NFPA

70 (LATEST EDITION).

*

A factory installed junction box is located on the lower right side of the fireplace. Wiring must be fed to the junction box and attached to the receptacle that is provided. Leave approximately

6" of wire in the junction box for connection.

Attach black wire to one side of the receptacle and white wire to opposite side of receptacle. The ground wire should be attached to the green (ground) screw.

Install the receptacle into the junction box. Attach cover plate.

Attention: A Junction box is located on the lower left side of the fireplace for direct ignition connections on direct ignition fireplace models only.

* NOTICE : For intermittent pilot models, refer to wiring instructions on page 55.

BRICK LINER INSTALLATION INSTRUCTIONS

1. Using gloves, unpack liner components and check for damaged or missing components.

2. Lower bottom louver and remove upper louver on fireplace.

3. Remove glass frame assembly from fireplace.

4. Remove rear logs from burner assembly.

5. Place brick panel (rear) against rear wall in fireplace.

NOTICE : The top edge will have a half-moon cutout relief to match up with the rear flue vent hole.

6. While holding finished edge on brick panel (side), place brick panel (sides) against side walls in fireplace. Move side panels rearward until the back edge meets the rear brick panel. Slide side brick panels down so they rest on firebox bottom.

7. Align grout lines on top brick panel with the grout lines on the side brick panels. Place the top brick panel into brick panel holder. With needle-nose pliers, carefully bend hold-down tabs on brick panel holder over the edges of the top brick panel. The hold-down tabs will securely hold the top brick panel in place.

8. Replace rear logs onto burner assembly. (Refer to log placement, page 44.)

9. Attach glass frame assembly onto fireplace.

10. Raise bottom louver and replace top louver onto fireplace.

11. Installation of optional brick liner is complete.

Page 72 31451-2-1013

ACCESSORIES

The following accessory parts can be obtained from your Empire Comfort Systems dealer. If you need additional information beyond what your dealer can furnish, contact Empire Comfort Systems Inc., Nine Eighteen Freeburg Ave., Belleville, Illinois 62220-2623.

Accessory

Simulated Brick Panels

TOP

Description

The simulated brick panels were designed to enhance the appearance of your fireplace, imitating the look of authentic masonry.

Model Number

DVP36DG

STACKED STONE

BACK

LEFT

Simulated Brick Liners

RIGHT

The simulated brick panels were designed to enhance the appearance of your fireplace, imitating the look of authentic masonry.

DVP36D2H

HERRINGBONE

Simulated Brick Liners The simulated brick panels were designed to enhance the appearance of your fireplace, imitating the look of authentic masonry.

DVP36D2A

AGED BRICK

DECORATIVE ACCESSORIES

BRAIDED ARCH FRONT TIFFANY ARCH FRONT ARTS & CRAFTS FRONT

31451-2-1013

MARQUIS ARCH

DOORS

ARTS & CRAFTS

DOORS

Page 73

Page 74

Empire Comfort Systems

918 Freeburg Avenue

Belleville, Illinois 62220-2623

Web Site www.empirecomfort.com

GAS-FIRED

The Studio Series Direct Vent Zero Clearance

Gas Fireplace Heater

MILLIVOLT STANDING PILOT: DVP36DP31(N,P)-2

DIRECT IGNITION PILOT: DVP36DP51N-1

INTERMITTENT PILOT: DVP36DP71(N,P)-3

REMOTE RF: DVP36DP91(N,P)-3

Fireplace requires one of the following fronts:

Arched: DCF36B(FB,CM,HP), DCF(36,42)T(FB,CM,HP)

Rectangular: DCF36A(FB,CM,HP)

Fireplace requires one of the following ceramic liners:

DVP36D2A, DVP36D2H, DVP36DG

All Brick Liners are made from Ceramic Fiber for rich detail and lasting beauty. Aged Brick

Liners have brown bricks with charcoal mortar in running bond courses, plus smoked accents.

Herringbone Liners have burnt umber bricks in a herringbone pattern with light mortar, plus smoked accents. Stacked Limestone Liners have stones of varying depth and color for a rustic cabin look.

CLEARANCES TO COMBUSTIBLES

Clearance to Combustibles

Back

Side

Floor

Top Stand-off

0" (0 mm)

0" (0 mm)

0" (0 mm)

0" (0 mm)

Top Framing Edge 3" (76 mm)

36”

(914mm)

6” (152mm)

31451-2-1013

31451-2-1013

LEFT SIDE VIEW

GAS LINE ACCESS

Empire Comfort Systems

918 Freeburg Avenue

Belleville, Illinois 62220-2623

Web Site www.empirecomfort.com

GAS-FIRED

The Studio Series Direct Vent Zero Clearance

Gas Fireplace Heater

MILLIVOLT STANDING PILOT: DVP36DP31(N,P)-2

DIRECT IGNITION PILOT: DVP36DP51N-1

INTERMITTENT PILOT: DVP36DP71(N,P)-3

REMOTE RF: DVP36DP91(N,P)-3

Fireplace requires one of the following fronts:

Arched: DCF36B(FB,CM,HP), DCF(36,42)T(FB,CM,HP)

Rectangular: DCF36A(FB,CM,HP)

Fireplace requires one of the following ceramic liners:

DVP36D2A, DVP36D2H, DVP36DG

All Brick Liners are made from Ceramic Fiber for rich detail and lasting beauty. Aged Brick Liners have brown bricks with charcoal mortar in running bond courses, plus smoked accents. Herringbone

Liners have burnt umber bricks in a herringbone pattern with light mortar, plus smoked accents.

Stacked Limestone Liners have stones of varying depth and color for a rustic cabin look.

FIREBOX DIMENSIONS

RIGHT SIDE VIEW

C

FRONT VIEW

A

GAS LINE

ACCESS

A

VENT COLLAR

STANDOFFS

NAILING

FLANGES

GLASS

FRAME

ASSEMBLY

E

B

J

I

D

H

G

TOP VIEW

GAS LINE

ACCESS

ELECTRICAL

ACCESS

VENT COLLAR

B

C

D

E

G

H

I

J

34 3/4"

(882.7 mm)

39"

(990.6 mm)

19 7/8"

(505 mm)

25"

(635 mm)

36"

(914 mm)

26 1/2"

(673.1 mm)

37 3/4"

(959 mm)

13 1/4"

(336.6 mm)

7 1/8"

(181 mm)

RATING PLATE

AND LABELS

GAS CONTROLS

AND SWITCHES

FRAMING DIMENSIONS

"A"

"B"

"C"

37 7/8"

40 3/8"

19 7/8"

Page 75

WARRANTY

Empire Comfort Systems Inc. warranties this hearth product to be free from defects at the time of purchase and for the periods specified below. Hearth products must be installed by a qualified technician and must be maintained and operated safely, in accordance with the instructions in the owner’s manual. This warranty applies to the original purchaser only and is not transferable. All warranty repairs must be accomplished by a qualified gas appliance technician.

Limited Lifetime Parts Warranty – Combustion Chamber, Heat Exchanger, and Factory-Installed Glass

If the combustion chamber, heat exchanger (see parts list) or factory-installed glass fails because of defective workmanship or material, Empire will repair or replace at Empire’s option.

Limited Three-Year Parts Warranty – All Other Components

(Except Remote Controls, Thermostats, Accessories and Replacement Parts)

Should any part fail because of defective workmanship or material within three years from the date of purchase, Empire will repair or replace at Empire’s option..

Limited One-Year Parts Warranty – Remote Controls, Thermostats, Accessories, and Parts

Should any remote control, thermostat, accessory, or other part fail because of defective workmanship within one year from the date of purchase, Empire will repair or replace at Empire’s option.

Duties Of The Owner

The appliance must be installed by a qualified installer and operated in accordance with the instructions furnished with the appliance.

A bill of sale, cancelled check, or payment record should be kept to verify purchase date and establish warranty period.

Ready access to the appliance for service.

What Is Not Covered

Damages that might result from the use, misuse, or improper installation of this appliance.

Travel, diagnostic costs and freight charges on warranted parts to and from the factory.

Claims that do not involve defective workmanship or materials.

Unauthorized service or parts replacements.

Removal and reinstallation cost.

Inoperable due to improper or lack of maintenance.

How To Get Service

To make a claim under this warranty, please have your receipt available and contact your installing dealer. Provide the dealer with the model number, serial number, type of gas, and purchase verification. The installing dealer is responsible for providing service and will contact the factory to initiate any warranted parts replacements. Empire will make replacement parts available at the factory. Shipping expenses are not covered.

If, after contacting your Empire dealer, service received has not been satisfactory, contact: Consumer Relations Department,

Empire Comfort Systems Inc., PO Box 529, Belleville, Illinois 62222, or send an e-mail to [email protected] with “Consumer Relations” in the subject line.

Your Rights Under State Law

This warranty gives your specific legal rights, and you may also have other rights, which vary from state to state.

Page 76

EMPIRE

Comfort Systems

Empire Comfort Systems Inc.

918 Freeburg Ave. Belleville, IL 62220

If you have a general question about our products, please e-mail us at [email protected].

If you have a service or repair question, please contact your dealer.

www.empirecomfort.com

31451-2-1013