Omron V7 Datasheet
Reklama
Reklama
Y203-EN2-02-Katalog.book Seite 329 Mittwoch, 24. Mai 2006 2:22 14
CIMR-V7AZ
Varispeed V7
Sensorless vector in pocket size
• Nominal torque at 0.5 Hz
• Autotuning
• High carrier up to 14 khz
• Stop accuracy function.
• Integrated PID controller and bidirectional PID-out put
• Motor protection with PTC input
• Pulse input
• Standard digital operator with copy function
• Fieldbus: Modbus, DeviceNet, PROFIBUS, CANopen
• High speed motion bus: ML- II
• Plug-in PLC option unit. Total inverter access.
• CE, UL, and cUL marked
V7 IP65
• Compact size
• Easy wiring
• Built-in filter (Class B)
Customized software*
• The inverter software can be customized to meet specific application. Examples:
• Traverse sofware S-9381.
*For detailed information please refer to case software section.
Ratings
• 200 V Class single-phase 0.1 to 4 kW
• 200 V Class three-phase 0.1 to 7.5 kW
• 400 V Class three-phase 0.2 to 7.5 kW
System configuration
3G3IV-PCN329-E
Inverter to PC cable
CX-Drive 3G3IV-PEZZ8122_
DIN attachment
JVOP-144
Remote digital oper.
with potentiometer
JVOP-146
Remote digital oper.
with potentiometer
3G3IV-PCN126/326
Digital operator extension cable
*See note
Line filter Braking accessories
* V7 IP65 types are built-in filter inverters.
Varispeed
V7
Communication unit
*See note
PLC option unit
*See note
LKEB_ CDBR_B ERF150WJ_
* Option frames are needed for V7 IP65 type.
Varispeed V7 329
Y203-EN2-02-Katalog.book Seite 330 Mittwoch, 24. Mai 2006 2:22 14
Specifications
Type designation
C I M R — V 7 A Z B 0 P 1 0
Inverter
V7 series
A: With digital operator (with potentiometer)
T: V7 IP65 type with digital operator
( without potentiometer )
Z: European standard specifications
Protective enclosure:
0: IP20
1: NEMA1
05: IP65
Max. applicable motor output
0P1: 0.1 kW
7P5: 7.5 kW
Voltage
B: Single-phase 200 VAC
2: Three-phase 200 VAC
4: Three-phase 400 VAC
point
200 V class
IP20 single-phase: CIMR-V7AZ
IP65 single-phase: CIMR-V7TZ
IP20 three-phase: CIMR-V7AZ
Maximum permissible motor output kW
1
Inverter capacity kVA
Rated output current A
Max. output voltage
B0P1
---
20P1
0.12
0.3
0.8
B0P2
---
20P2
0.25
0.6
1.6
B0P4
B0P405
20P4
0.55
1.1
B0P7
B0P705
20P7
1.1
1.9
B1P5
B1P505
21P5
1.5
3.0
3.0
5.0
8.0
Proportional to input voltage: 0..240 V
B2P2
B2P205
22P2
2.2
4.2
11.0
Max. output frequency 400 Hz
Rated input voltage and frequency
Allowable voltage fluctuation
Allowable frequency fluctuation
Single-phase 200..240 V 50/60 Hz
3-phase 200..230 V 50/60 Hz
-15%..+10%
+5%
1.
Based on a standard 4-pole motor for maximum applicable motor output. Select the inverter model within the allowable motor rated current
400 V class
IP20 three-phase: CIMR-V7AZ
IP65 three-phase: CIMR-V7TZ
Maximum permissible motor output kW
1
Inverter capacity kVA
Rated output current A
Max. output voltage
Max. output frequency
40P2
0.37
0.9
1.2
40P4
0.55
1.4
1.8
40P7
40P405 40P705 41P505 42P205 43P005 44P005
1.1
2.6
3.4
41P5 42P2
400 Hz
43P0
1.5
3.7
2.2
4.2
3.0
5.5
4.8
5.5
7.2
Proportional to input voltage: 0..400 V
44P0
4.0
7.0
9.2
45P5
5.5
11.0
14.8
Rated input voltage and frequency
Allowable voltage fluctuation
Allowable frequency fluctuation
3-phase 380..460 VAC, 50/60 Hz
-15%..+10%
+5%
1.
Based on a standard 4-pole motor for maximum applicable motor output. Select the inverter model within the allowable motor rated current
B4P0
---
24P0
4.0
6.7
17.5
47P5
7.5
14.0
18.0
330 Frequency inverters
Y203-EN2-02-Katalog.book Seite 331 Mittwoch, 24. Mai 2006 2:22 14
Commom specifications
Model number
CIMR-V7AZ@
CIMR-V7TZ@
Control methods
Output frequency range
Frequency tolerance
Resolution of frequency set value
Resolution of output frequency
Overload capability
Frequency set value
Braking torque
(short term peak torque)
Binary inputs
Binary outputs
Analogue output
Analogue inputs
Braking/acceleration times
Display
Motor overload protection
Instantaneous overcurrent
Overload
Overvoltage
Undervoltage
Momentary power loss
Cooling fin overheat
Stall prevention level
Cooling fan fault
Ground fault
Power charge indication
Degree of protection
Cooling
Ambient temperature
Ambient humidity
Storage temperature
Installation
Installation height
Vibration
Specifications
Sine wave PWM (V/f control, sensorless vector control)
0.1..400 Hz
Digital set value: ±0.01% (-10..+50 ºC)
Analogue set value: ±0.5% (25 ±10 ºC)
Digital set value: 0.01 Hz (<100 Hz), 0.1 Hz (>100 Hz)
Analogue set value: 1/1000 of maximum frequency
0.01 Hz
150%/60 s
0..10 V (20 k
Ω
), 4..20 mA (250
Ω
), 0..20 mA (250
Ω
)
Pulse train input, frequency setting value (selectable)
Up to 200 W 150% or more
550 W to 1.1 kW 100% or more
1.5 kW 50% or more
>1.5 kW 20% or more
Continuous braking torque approx. 20% without, 150% with external braking resistor
7 freely programmable inputs
1 relay output, 2 freely programmable open collector outputs
1 programmable analogue output (0..10 V)/pulse output
2 analogue inputs, 0..10 V, 4..20 mA, 0..20 mA
0.01..6000 s
Optionally frequency, current or set value
Error and status LED
Electronic thermal overload relay
Motor coasts to a stop at approx. 250% of inverter rated current
Motor coasts to a stop after 1 minute at 150% of inverter rated output current
Motor coasts to a stop if DC bus voltage exceed 410 V (double for 400 V class)
Stops when DC bus voltage is approx. 200 V or less (double for 400 V class)
(approx. 160 V or less for single-phase series)
Following items are selectable: not provided (stop if power loss is 15 ms or longer), continuous operation if power loss is approx. 0.5 s or shorter, continuous operation
Protected by electronic circuit
Individual levels during accel/constant speed. Decel ON/OFF available. During decel enable/disable selectable.
Detected by electronic circuit (fan lock detection)
Protected by electronic circuit (operation level is approx. 250% of rated output current)
RUN lamp stays ON or digital operator LED stays ON until the DC bus voltage becomes 50 V or less.
(Charge LED is provided for 400 V)
IP20, NEMA1, IP65
Self cooling for 200 V 0.1..0.4 kW (3 or single phase) and for 400 V 0.2..0.75 kW
Cooling fan for 200 V 0.75 to 7.5 kW and for 400 V 1.5 to 7.5 kW
Open air mounting: -10 ºC..50 ºC
Wall mounting: -10 ºC..40 ºC
95% (without condensation)
-20 ºC..+60 ºC (short-term temperature during transportation)
Indoor (no corrosive gas, dust, etc.)
Max. 1000 m
10 to 20 Hz, 9.8 m/s
2
max; 20 to 50 Hz, 2 m/s
2
max
Varispeed V7 331
Y203-EN2-02-Katalog.book Seite 332 Mittwoch, 24. Mai 2006 2:22 14
Digital operator
Data display
Indicators
(setting/monitor item indicators)
Operation keys
FREQUENCY adjuster
Appearance
Data display
Name
Frequency adjuster
Function
Displays relevant data items, such as frequency reference, output frequency, and parameter set values.
Sets the frequency reference within a range between 0 Hz and the maximum frequency.
1
Frequency reference indicator
Output frequency indicator
Output current indicator
Multi-function monitor indicator
Forward/reverse selection indicator
Local/remote selection indicator
Parameter setting indicator
Mode key
Increment key
Decrement key
Enter key
RUN key
The frequency reference can be monitored or set while this indicator is lit.
The output frequency of the inverter can be monitored while this indicator is lit.
The output current of the inverter can be monitored while this indicator is lit.
The values set in U01 through U10 are monitored while this indicator is lit.
The direction of rotation can be selected while this indicator is lit when operating the inverter with the RUN key.
The operation of the inverter through the digital operator or according to the set parameters is selectable while this indicator is lit.
2
The parameters in n001 through n179 can be set or monitored while this indicator is lit.
3
Switches the simplified-LED (setting and monitor) item indicators in sequence.
Parameter being set will be canceled if this key is pressed before entering the setting.
Increases multi-function monitor numbers, parameter numbers, and parameter set values.
Decreases multi-function monitor numbers, parameter numbers, and parameter set values.
Enters multi-function monitor numbers, parameter numbers, and internal data values after they are set or changed.
Starts the inverter running when the 3G3MV is in operation with the digital operator
STOP/RESET key Stops the inverter unless parameter n007 is set to disable the STOP key.
Used to reset the inverter when an error occurs.
4
1.
V7 IP65 types have digital operator without frequency adjuster.
2.
The status of the local/remote selection indicator can be only monitored while the inverter is in operation. Any RUN comand input is ignored while this indicator is lit.
3.
While inverter is in operation, the parameters can be only monitored and only some parameters can be changed. Any RUN command is ignored while the parameter setting indicator is lit.
4.
For safety reasons, the reset function cannot be used while an operation instruction (forward/reverse) is being input. Turn the operation instruction OFF before using this function.
332 Frequency inverters
Y203-EN2-02-Katalog.book Seite 333 Mittwoch, 24. Mai 2006 2:22 14
Dimensions
IP 20 type 0.1 to 4 Kw
2 M4
4 M4
W 1
W
8.5
(0.34)
Figure 1
D
D1
W 1
W
8.5
(0.34)
Figure 2
D
D1
Voltage class
Three-phase
200 V
Single-phase
200 V
Three-phase
400 V
Max. applicable motor output kW
0.12
0.25
0.55
1.1
1.5
2.2
4.0
0.12
0.25
0.55
1.1
1.5
2.2
4.0
0.37
0.55
1.1
1.5
2.2
3.0
4.0
Inverter model
CIMR V7AZ
20P1
20P2
20P4
20P7
21P5
22P2
24P0
B0P1
B0P2
B0P4
B0P7
B1P5
B2P2
B4P0
40P2
40P4
40P7
41P5
42P2
43P0
44P0
Figure
1
2
1
2
2
IP20 / NEMA1 type 5.5/7.5 Kw
W
68
108
140
170
108
140
108
140
68
H
128
128
128
Dimensions in mm
D W1 H1 H2 D1
Weight kg
Cooling method
0.6
76 10
56 5
0.6 Self cooled
0.9
131 1.4
96
5
64 Fan cooled
140 1.5
143 128
76
71
10
2.1
0.6
118 5 Self cooled
140 96
156 96
163 128
180 158
92
96 140
156
143 128
118
118
5
5
64
71
16
64
71
1.5
1.5
2.2
2.9
1.0
1.5
1.5
1.5
2.1
2.1
Fan cooled
Fan cooled
Voltage class
Three-phase
200 V
Three-phase
400 V
Max. applicable motor output kW
5.5
7.5
5.5
7.5
Inverter model
CIMR - V7AZ
25P5
27P5
45P5
47P5
Figure
3
W
180
180
Figure 3
H
260
Dimensions in mm (inches)
D W1 H1 H2
170 164 244 8
260 170 164 244 8
D1
65
65
Weight kg
4.6
4.8
4.8
4.8
Cooling method
Fan cooled
Varispeed V7 333
Y203-EN2-02-Katalog.book Seite 334 Mittwoch, 24. Mai 2006 2:22 14
IIP65 type 0.55 to 4 Kw
W 2
D
D1
W
W 1
6 . 4
H
H 1
3x PG25
Figure 4
Voltage class
Single-phase
200 V
Three-phase
400 V
Max. applicable motor output kW
0.55
1.1
1.5
2.2
0.55
1.1
1.5
2.2
3.0
4.0
Inverter model
CIMR V7TZ
B0P405
B0P705
B1P505
B2P205
40P405
40P705
41P505
42P205
43P005
44P005
Figure
4
W
280
280
H
240 142
240
D
142
Dimensions in mm
W1 W2 H1
260 228 165 38 275
260 228
H2 H3
165 38 275
D1
Weight kg
Cooling method
44
4.3
3.7
4.2
4.3
44
3.7
3.7
4.1
4.1
Fan cooled
Fan cooled
334 Frequency inverters
Y203-EN2-02-Katalog.book Seite 335 Mittwoch, 24. Mai 2006 2:22 14
IP65 type 0.55 to 4Kw (with option frame accessory attached)
W 2
D2
D
D1
W
W 1
6 . 4
H
H 1
2x PG12 3x PG25 Figure 5
Voltage class
Singlephase 200 V
Three-phase
400 V
Max. applicable motor output kW
0.55
1.1
1.5
2.2
0.55
1.1
1.5
2.2
3.0
4.0
Inverter model
CIMR V7TZ
Figure
B0P405
B0P705
B1P505
B2P205
40P405
40P705
41P505
42P205
43P005
44P005
5
W
280
280
H
240 180
240
D
180
W1
260 228 165 38 275
260
Dimensions in mm
W2 H1
228
H2 H3
165 38 275
D1 D2
44 38
44 38
Weight kg
Cooling method
4.5
3.9
4.4
4.5
3.9
3.9
4.3
4.3
Fan cooled
Fan cooled
Varispeed V7 335
Y203-EN2-02-Katalog.book Seite 336 Mittwoch, 24. Mai 2006 2:22 14
Filters *
Schaffner model
A
3x200 V 3G3MV-PFI2010-SE 194
3G3MV-PFI2020-SE 169
3G3MV-PFI2030-SE 174
1x200 V 3G3MV-PFI1010-SE 169
3G3MV-PFI1020-SE 169
3G3MV-PFI1030-SE 174
3G3MV-PFI1040-SE 174
3x400 V 3G3MV-PFI3005-SE 169
3G3MV-PFI3010-SE 169
3G3MV-PFI3020-SE 174
3G3MV-PFI3030-SE 304
B
82
111
144
71
111
144
144
111
111
144
184
45
50
50
50
C
50
50
50
45
45
50
56
Dimensions
D
160
E
181
135
135
135
135
135
135
156
161
156
156
161
161
135
135
135
264
156
156
161
288
F
62
91
120
51
91
120
150
91
91
120
150
M5
M5
M5
M5
H
M5
M5
M5
M5
M5
M5
M5
5.3
5.3
5.3
5
G
5.3
5.5
5.3
5.3
5.3
5
6
22
25
25
25
I
25
25
25
22
22
25
28
K
118
118
118
118
118
118
118
118
118
118
244
J
56
96
128
56
96
128
158
96
96
128
164
M4
M4
M4
M4
L
M4
M4
M4
M4
M4
M4
M5
Drive mounts
Output flexes
Rasmi model
3x200 V 3G3MV-PFI2010-E
3G3MV-PF2020-E
3G3MV-PFI2030-E
3G3MV-PFI2050-E
1x200 V 3G3MV-PFI1010-E
3G3MV-PFI1020-E
3G3MV-PFI1030-E
3G3MV-PFI1040-E
3x400 V 3G3MV-PFI3005-E
3G3MV-PFI3010-E
3G3MV-PFI3020-E
3G3MV-PFI3030-E
W
82
111
144
184
71
111
144
174
111
111
144
184
* V7 IP65 types are built-in filter inverters.
56
45
50
50
H
50
50
50
50
50
50
50
56
174
169
169
174
304
L
194
Dimensions
X
181
Y
62
169
174
304
169
169
174
156
161
288
156
156
161
91
120
150
51
91
120
161
156
156
161
288
150
91
91
120
150
Inverter fixing
M5
M5
M5
M5
M5
M5
M5
M5
M5
M5
M5
M5
336 Frequency inverters
Y203-EN2-02-Katalog.book Seite 337 Mittwoch, 24. Mai 2006 2:22 14
DIN rail mounting bracket
3G3IV-PZZ08122A 3G3IV-PZZ08122B
(35.1)
DIN r ail
3G3IV-PZZ08122C
Four, M4 tap
Side view
(common to all the units)
3G3IV-PZZ08122D
Four, M4 tap
3-phase 200 VAC
Single-phase 200 VAC
3-phase 400 VAC
Four, M4 tap
Inverter
CIMR-V7AZ - 20P1/ 20P4/ 20P7
CIMR-V7AZ - 21P5/ 22P2
CIMR-V7AZ - 24P0
CIMR-V7AZ - B0P1/ B0P2/ B0P4
CIMR-V7AZ - B0P7/ B1P5
CIMR-V7AZ - B2P2
CIMR-V7AZ - B4P0
CIMR-V7AZ - 40P2/ 40P4/ 40P7/ 41P5/ 42P2
CIMR-V7AZ - 44P0
Four, M4 tap
DIN rail mounting bracket
3G3IV-PEZZ08122A
3G3IV-PEZZ08122B
3G3IV-PEZZ08122C
3G3IV-PEZZ08122A
3G3IV-PEZZ08122B
3G3IV-PEZZ08122C
3G3IV-PEZZ08122D
3G3IV-PEZZ08122B
3G3IV-PEZZ08122C
Varispeed V7 337
Y203-EN2-02-Katalog.book Seite 338 Mittwoch, 24. Mai 2006 2:22 14
Attachments
Heatsink external mounting attachment
When mounting an external cooling-fan to the V7AZ, this attachment is required.
338
CIMR-V7AZ
V7AZ-20P1
V7AZ-20P2
V7AZ-20P4
V7AZ-20P7
V7AZ-21P5
V7AZ-22P2
V7AZ-24P0
V7AZ-25P5
V7AZ-27P5
V7AZ-B0P1
V7AZ-B0P2
V7AZ-B0P4
V7AZ-B0P7
V7AZ-B1P5
V7AZ-B2P2
V7AZ-B4P0
V7AZ-40P2
V7AZ-40P4
V7AZ-40P7
V7AZ-41P5
V7AZ-42P2
V7AZ-43P0
V7AZ-44P0
V7AZ-45P5
V7AZ-47P5
Attachment order code
EZZ08136A
EZZ08136B
EZZ08136C
EZZ08136D
-EZZ08136F
EZZ08136H
EZZ08136A
EZZ08136B
EZZ08136D
EZZ08136F
EZZ08136G
EZZ08136E
EZZ08136D
EZZ08136F
EZZ08136H
69.2
92.2
82
98
98.6
115.6
82
82
82
98
D1
69.2
69.2
69.2
73
98
78.6
113.8
Dimensions in mm
D2
12
42
62
58
58
64.4
56.2
12
42
58
58
64.4
64.4
13.2
28
58
58
78.6
113.8
64.4
56.2
D3
30
50
70
70
70
70
60
30
70
30
40
70
50
70
70
70
70
70
60
Frequency inverters
Y203-EN2-02-Katalog.book Seite 339 Mittwoch, 24. Mai 2006 2:22 14
Braking resistor unit ERF-150WJ
Note: Prepare mounting screws
(2-M4x8 tapped screws).
Screws 8mm or more and general
metric screws cannot be used.
Braking resistors unit
MTG screw
30 or more
C
A 30 or more
150
Voltage
200 V class
400 V class
Model LKEB#
20P7
21P5
22P2
40P7
25P5
27P5
40P7
41P5
42P2
43P0
43P7
45P5
47P5
A B
Dimensions in mm
C D
350 350 200 335
105 275 50 260
130 350 75)
130 350 75)
350 350 200 335
MTG.screw
M6x4
M5x3
M6x4
Approx.
weight kg
3.0
4.5
4.5
5.0
7.5
8.5
3.0)
4.5
4.5
5.0
7.5
8.5
Varispeed V7 339
Y203-EN2-02-Katalog.book Seite 340 Mittwoch, 24. Mai 2006 2:22 14
Installation
Standard connections
MCCB
R
S
T
Multifunction input
Forward run/stop
Reverse run/stop
External fault
(no contact)
Fault reset
Multi-step speed reference 1
Multi-step speed reference 2
JOG command
Frequency reference
Pulse train input
2k
Ω
Frequency setter
P
P
MEMOBUS communication
RS-485/422 max 19.2kBPS
Line filter
1*
S1
S2
S3
S4
S5
S6
S7
SC
DC reactor (option)
U
Short bar
X
+2
R/L1
S/L2
T/L3
+1 –
Thermal overload relay (option)
B1
Braking resistor
(option)
B2
U/T1
V/T2
W/T3
NPN
PHC
PHC
PHC
PHC
PHC
PHC
PHC
PNP
24 V
MA
MB
MC
P1
Fault
Running
Grounding
Multi-function output
250 VAC 1 A or less
30 VDC 1 A or less
IM
R+
R–
S+
S–
Shield connection terminal
RP
Speed reference pulse train
(33 kHz max.)
FS
Frequency setting power supply
(+12 V 20 mA)
FR
FC
Speed frequency reference
0 to +10 V (20 k
4 to 20 mA (250
Ω ) OR
)
0 V
Digital operator frequency setting potentiometer min
P2
PC max
CN2
VIN
IIN
GND
Speed agree
Multi-function photocoupler output
+48 VDC 50 mA or less
Housing (type : ZHR-3)
0 to 10 V
P 4 to 20 mA
0V
Multi-function analog input 2*
Terminal resistance
(1/2 W. 120
Ω
)
AM
AC
Frequency meter adjusting potentiometer
P
FM
Analog monitor output
0 TO +10 VDC (2 mA)
Output frequency
Pulse monitor output
(12 VDC
20 mA max. 30 - 70% duty)
1* V7 IP65 types are built-in filter.
2* A housing is required when using the CN2 terminal on the back side of the digital operator.
1m analog input cable (code no. 3G3MV-PCN-CN2) is available for housing on request
: shielded wire P : twisted pair shielded wire
Shows the following two kinds of connections (factory setting) :
· Input signals (S1 to S7) are non-voltage contacts
· Sequence connection by NPN transistor (0V common)
A +24 V power supply is required for sequence connection by PNP transistor (+24 V common) .
340 Frequency inverters
Y203-EN2-02-Katalog.book Seite 341 Mittwoch, 24. Mai 2006 2:22 14
Main circuit
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
B1, B2
+2, +1
+1, –
Name
AC power supply input
Inverter output
Braking resistor connection
DC reactor connection
DC power supply input
Grounding
Function (signal level)
Main circuit power supply input (use R/L1 and S/L2 for single-phase power supply inverter.
Do not use T/L3 of the models less than 0.75 kW for other usage, such as a junction terminal.)
For inverter output
For braking resistor connection
Remove the short bar between +2 and +1 when connecting DC reactor (option)
For power supply input (+1: positive electrode; – : negative electrode)*
For grounding (grounding should conform to the local grounding code.)
Control Circuit
Type
S4
S5
S6
S7
No.
S1
S2
S3
SC
RP
FS
FR
FC
1 (CN2)
2 (CN2)
3 (CN2
MA
NC
MC
P1
P2
PC
AM
AC
R+
R–
S+
S–
Signal name
Multi-function input selection 1
Multi-function input selection 2
Multi-function input selection 3
Function
Factory setting: runs when CLOSED, stops when OPEN.
Factory setting: runs when CLOSED, stops when OPEN.
Factory setting: "fault reset"
Signal level
Multi-function input selection 4
Multi-function input selection 5
Factory setting: "external fault (NO contact)"
Factory setting: "multi-step speed reference 1"
24VDC, 8mA photocoupler insulation
Multi-function input selection 6 Factory setting: "multi-step speed reference 2"
Multi-function input selection 7
Multi-function input selection
Common
Speed reference pulse train input
Power supply terminal for frequency setting
Speed frequency reference
Factory setting: "JOG command"
Common for control signal
33 kHz max.
+12V (allowable current: 20 mA max.)
0 to +10 VDC (20 k
Ω
) or 4 to 20 mA (250
Ω
), 0 to 20 mA (250
Ω
) (resolution 1/1000)
Frequency reference common 0 V
Multi-function analog voltage input Voltage input (between terminals 1 and 3): 0 to 10 VDC (input impedance: 20 k
Ω
)
Multi-function analog current input
Current input (between terminals 2 and 3): 4 to 20 mA (input impedance: 250 Ω )
Multi-function analog input common
NO contact output
Contact output
Contact output common
Factory setting: "fault"
Photocoupler output 1
Photocoupler output 2
Photocoupler output common
Analog monitor output
Factory setting: "running"
Factory setting: "at frequency"
0 V
Factory setting: "output frequency" 0 to +10 V output
(pulse monitor output available by setting constants. Duty: 30 to 70%)
0 V Analog monitor common
Communication input (+)
Communication input (–)
Communication output (+)
Communication output (–)
For MEMOBUS communication operation by RS-485 or RS-422 communication is available.
Contact capacity
250 VAC,
1 A or less
30 VDC, 1 A or less
Photocoupler output:
+48 VDC, 50 mA or less
0 to 10 V 2 mA or less
Resolution: 8 bits
RS-485/422
MEMOBUS protocol
19.2 kBPS max.
Varispeed V7 341
Y203-EN2-02-Katalog.book Seite 342 Mittwoch, 24. Mai 2006 2:22 14
W = 30 mm min. (0.1 to 4.0 KW)
50 mm min. (5.5 and 7.5 KW)
Inverter Inverter Inverter
100 mm min.
Air
Side
100 mm min.
Air
Inverter heat loss
Three-phase 200 V class
Model CIMR-V7AZ
Inverter capacity kVA
Rated current A
Fin
Inside unit
Total heat loss
Single-phase 200 V class
Model CIMR-V7AZ
Inverter capacity kVA
Rated current A
Fin
Inside unit
Total heat loss
Three-phase 400 V class
Model CIMR-V7AZ
Inverter capacity kVA
Rated current A
Fin
Inside unit
Total heat loss
20P1
0.3
0.8
3.7
9.3
13.0
B0P1
0.3
0.8
3.7
10.4
14.1
40P2
1.4
1.8
15.1
15.0
30.1
20P2
0.6
1.6
7.7
10.3
18.0
B0P2
0.6
1.6
7.7
12.3
20.0
40P4
2.6
3.4
30.3
24.6
54.9
20P4
1.1
3
15.8
12.3
28.1
B0P4
1.1
3
15.8
16.1
31.9
40P7
3.7
4.8
45.8
29.9
75.7
20P7
1.9
5
28.4
16.7
45.1
B0P7
1.9
5
28.4
23.0
51.4
41P5
4.2
5.5
50.5
32.5
83.0
21P5
3.0
8
53.7
19.1
72.8
B1P5
3.0
8
53.7
29.1
82.8
42P2
5.5
7.2
58.2
37.6
95.8
22P2
4.2
11
60.4
34.4
94.8
B2P2
4.2
11
64.5
49.1
113.6
44P0
7.0
8.6
73.4
44.5
117.9
Installation conditions for IP65
Install the inverter vertically in order to ensure proper cooling. When installing the inverter, always provide the following minimum installation space to allow normal heat dissipation.
24P0
6.7
17.5
96.7
52.4
149.1
B4P0
6.7
17.5
98.2
78.2
176.4
45P5
11
14.8
168.8
87.7
256.5
50 mm or more
120 mm or more
Air
25P5
9.5
25
170.4
79.4
249.8
27P5
13
33
219.2
98.9
318.1
47P5
14
18
209.6
99.3
308.9
342
40 mm or more
50 mm or more
40 mm or more
120 mm or more
Air
Side spaces Top and bottom spaces
1. Always provide enough space for the main circuit or control lines including cable gland.
2. If installing inverters next to one another, provide a minimum spacing of 60mm .
Frequency inverters
Y203-EN2-02-Katalog.book Seite 343 Mittwoch, 24. Mai 2006 2:22 14
Connections for braking resistor
3-phase power supply
Braking resistor
Motor
Connections for braking resistor unit
Power supply
3-phase
Braking resistor unit overheat contact
Use sequencer to break power supply side on overload relay trip contact
Overload relay trip contact
Braking resistor unit
AC reactor
Faulr contact
AC reactor
Motor
Be sure to connect
AC reactor on inverter input side [L
1
L
2
(S), L
3
(R),
(T)].
Max. applicable
motor output kW
0.12
0.25
0.55
1.1
1.5
2.2
4.0
5.5
7.5
200 V class
Current value
A
2.0
2.0
2.5
5
10
15
20
30
40
Inductance mH
2.0
2.0
4.2
2.1
1.1
0.71
0.53
0.35
0.265
Max. applicable motor output kW
0.2
0.4
0.75
1.5
2.2
4.0
5.5
7.5
400 V class
Current value
A
------
1.3
2.5
5
7.5
10
15
20
Inductance mH
18.0
8.4
4.2
3.6
2.2
1.42
1.06
Varispeed V7 343
Y203-EN2-02-Katalog.book Seite 344 Mittwoch, 24. Mai 2006 2:22 14
DC reactor
DC reactor
Motor
Max. applicable motor output kW
0.12
0.25
0.55
1.1
1.5
2.2
4.0
5.5
7.5
200 V class
Current value
A
5.4
18
36
Inductance mH
8
3
1
Max. applicable
motor output kW
0.2
0.4
0.75
1.5
2.2
4.0
5.5
7.5
400 V class
Current value
A
--------
3.2
5.7
12
23
Inductance mH
28
11
6.3
3.6
344 Frequency inverters
Y203-EN2-02-Katalog.book Seite 345 Mittwoch, 24. Mai 2006 2:22 14
Ordering information
3G3IV-PCN329-E
Inverter to PC cable
CX-Drive
D
Line filter
D
*See note
3G3IV-PEZZ8122_
DIN attachment
JVOP-144
Remote digital oper.
with potentiometer
JVOP-146
Remote digital oper.
with potentiometer
3G3IV-PCN126/326
Digital operator extension cable
D D D D
Braking accessories
A
* V7 IP65 types are built-in filter inverters.
Varispeed
V7
Communication unit
*See note
PLC option unit
*See note
B C
* Option frames are needed for V7 IP65 type.
E
LKEB_ CDBR_B ERF150WJ_
Varispeed V7
200 V
1x200 V
3x200 V
Specifications
0.12 Kw
0.25 Kw
0.55 Kw
1.1 Kw
1.5 Kw
2.2 Kw
4.0 Kw
0.12 Kw
0.25 Kw
0.55 Kw
1.1 Kw
1.5 Kw
2.2 Kw
4.0 Kw
5.5 Kw
7.5 Kw
0.8 A
1.6 A
3.0 A
5.0 A
8.0 A
11.0 A
17.5 A
0.8 A
1.6 A
3.0 A
5.0 A
8.0 A
11.0 A
17.5 A
25.0 A
33.0 A
Varispeed V7
Model
CIMR-V7AZB0P10
CIMR-V7AZB0P20
CIMR-V7AZB0P40
CIMR-V7AZB0P70
CIMR-V7AZB1P50
CIMR-V7AZB2P20
CIMR-V7AZB4P00
CIMR-V7AZ20P10
CIMR-V7AZ20P20
CIMR-V7AZ20P40
CIMR-V7AZ20P70
CIMR-V7AZ21P50
CIMR-V7AZ22P20
CIMR-V7AZ24P00
CIMR-V7AZ25P51
CIMR-V7AZ27P51
400 V
3x400 V
Specifications
0.37 Kw
0.55 Kw
1.1 Kw
1.5 Kw
2.2 Kw
3.0 Kw
4.0 Kw
5.5 Kw
7.5 Kw
1.2 A
1.8 A
3.4 A
4.8 A
5.5 A
7.2 A
9.2 A
14.8 A
18.0 A
Model
CIMR-V7AZ40P20
CIMR-V7AZ40P40
CIMR-V7AZ40P70
CIMR-V7AZ41P50
CIMR-V7AZ42P20
CIMR-V7AZ43P00
CIMR-V7AZ44P00
CIMR-V7AZ45P51
CIMR-V7AZ47P51
345
Y203-EN2-02-Katalog.book Seite 346 Mittwoch, 24. Mai 2006 2:22 14
Varispeed V7 IP65
200 V
1x200 V
Specifications
0.55 Kw
1.1 Kw
1.5 Kw
2.2 Kw
3.0 A
5.0 A
8.0 A
11.0 A
A
Line filters *
Model
CIMR-V7TZB0P405
CIMR-V7TZB0P705
CIMR-V7TZB1P505
CIMR-V7TZB2P205
400 V
3x400 V
Specifications
0.55 Kw
1.1 Kw
1.5 Kw
2.2 Kw
3.0 Kw
4.0 Kw
1.8 A
3.4 A
4.8 A
5.5 A
7.2 A
9.2 A
Model
CIMR-V7TZ40P405
CIMR-V7TZ40P705
CIMR-V7TZ41P505
CIMR-V7TZ42P205
CIMR-V7TZ43P005
CIMR-V7TZ44P005
Voltage
3-Phase 200 VAC
Single-Phase 200 VAC
3-Phase 400 VAC
Inverter
Model CIMR-V7AZ
20P1 / 20P2 / 20P4 / 20P7
21P5 / 22P2
24P0
25P5 / 27P5
B0P1 / B0P2 / B0P4
B0P7 / B1P5
B2P2
B4P0
40P2 / 40P4
40P7 / 41P5 / 42P2
43P0 / 44P0
45P5 / 47P5
* V7 IP65 types are built-in filter inverters.
Schaffner
3G3MV-PFI2010-SE
3G3MV-PFI2020-SE
3G3MV-PFI2030-SE
-
3G3MV-PFI1010-SE
3G3MV-PFI1020-SE
3G3MV-PFI1030-SE
3G3MV-PFI1040-SE
3G3MV-PFI3005-SE
3G3MV-PFI3010-SE
3G3MV-PFI3020-SE
3G3MV-PFI3030-SE
Line filter
Rasmi
3G3MV-PFI2010-E
3G3MV-PFI2020-E
3G3MV-PFI2030-E
3G3MV-PFI2050-E
3G3MV-PFI1010-E
3G3MV-PFI1020-E
3G3MV-PFI1030-E
3G3MV-PFI1040-E
3G3MV-PFI3005-E
3G3MV-PFI3010-E
3G3MV-PFI3020-E
3G3MV-PFI3030-E
Rated current (A)
10
20
30
50
10
20
30
40
5
10
15
30
Weight (kg)
0.8
1.0
1.1
2.3
0.6
1.0
1.1
1.2
1.0
1.0
1.1
2.3
346 Frequency inverters
Y203-EN2-02-Katalog.book Seite 347 Mittwoch, 24. Mai 2006 2:22 14
B
Communication cards
Type Model
1
3G3MV-PDRT2
Description
DeviceNet option card
2
Function
• Used for running or stopping the inverter, setting or referencing parameters, and monitoring output frequency, output current, or similar items through DeviceNet communication with the host controller.
SI-P1/V7
PROFIBUS-DP option card
• Used for running or stopping the inverter, setting or referencing parameters, and monitoring output frequency, output current, or similar items through PROFIBUS-DP communication with the host controller.
SI-S1/V7
Can open option card
• Used for running or stopping the inverter, setting or referencing parameters, and monitoring output frequency, output current, or similar items through CANopen communication with the host controller.
3G3MV-PCORT21
Can open gateway
• Used for running or stopping the inverter, setting or referencing parameters, and monitoring output frequency, output current, or similar items through CANopen communication with the host controller.
SI-T1/V7
MECHATROLINK-II option card
• Used for running or stopping the inverter, setting or referencing parameters, and monitoring output frequency, output current, or similar items through MECHATROLINK-II communication with the host controller.
• High speed motion bus.
• Host controller: TrajeXia, MCH or MP series.
3
1.
Option frame accessory is needed for V7 IP65 types when communications option units are used.
2.
For V7 IP65 types with DeviceNet communication, SI-N1/V7 should be used.
3.
Please refer to TrajeXia, MCH or MP series section for host controller technical information.
C
PLC option card
Type Model
1
3G3MV-P10CDT-E
Description
PLC option
Function
• Full PLC featrues, wireless installation and seamless access to the inverter parameters and analogue/digital inputs and outputs.
• Standard OMRON tools can be used for programming
• Calendar / clock
• Same features as standard models with RS 422/485 support.
PLC option with
RS 422/485
3G3MV-P10CDT3-E
1.
Option frame accessory is needed on V7 IP65 types when PLC option unit is used.
D
Option frame accessory for V7 IP65
Type Model Description
V7TZ-FR1
Function
• Frame accessory is needed when communication option unit or PLC option unit are used with Varispeed V7 IP65.
Option frame
Varispeed V7 347
Y203-EN2-02-Katalog.book Seite 348 Mittwoch, 24. Mai 2006 2:22 14
E
Accessories
Types Model
JVOP-146
Description
JVOP-144
72606-CVS31060
3G3IV-PEZZ0838BA
3G3IV-PCN126
3G3IV-PCN326
3G3IV-PCN329-E
E
Computer software
Types Model
CX-drive
CX-One
Remote digital operator without potentiometer
DATA (15.5)
STOP
78 (3.07)
88 (3.46)
5
(0.2)
1.7
(0.07)
12.2
(0.48)
10.5
(0.41)
30.4
(1.20)
18.2
(0.72)
15.5 (0.61)
70 (2.76)
56 (2.20)
4-M4 SPOT FACING
DEEP 3.5 (0.14)
Remote digital operator with potentiometer
Blank cover
Digital operator case
Digital operator extension cable
1 meter
3 meters
PC configuration cable
OPERATOR
JVOP-140
DSPL
DATA
ENTER
RUN
STOP
RESET
MIN MAX
78 (3.07)
88 (3.46)
5
(0.2)
23.1 (0.91)
15.5 (0.61)
70 (2.76) same as JVOP-144 without operator
10.5
(0.41)
30.4
(1.20)
18.2
(0.72)
-----
-----
-----
56 (2.20)
4-M4 SPOT FACING
DEEP 3.5 (0.14) deep 3.5 (0.14)
Description
Computer software
Computer software
Functions
Installation
Configuration and monitoring software tool
Configuration and monitoring software tool
348 Frequency inverters
Y203-EN2-02-Katalog.book Seite 349 Mittwoch, 24. Mai 2006 2:22 14
F
Braking unit, braking resistor unit
Voltage
Inverter
Max. applicable motor output kW
Inverter model
CIMR-V7AZ
Inverter-mounted type
(3 %ED, 10 sec max)
Braking resistor unit
Separately-installed type
(10 %ED, 10 sec. max.)
200 V
(single-/ three-phase)
400 V
(threephase)
0.37
0.55
1.1
1.5
2.2
3.0
4.0
5.5
7.5
0.12
0.25
0.55
1.1
1.5
2.2
4.0
5.5
7.5
Singlephase
–
–
–
–
–
–
–
–
–
B0P1
B0P2
B0P4
B0P7
B1P5
B2P2
B4P0
–
–
Threephase
40P2
40P4
40P7
41P5
42P2
43P0
44P0
45P5
47P5
20P1
20P2
20P4
20P7
21P5
22P2
24P0
25P5
27P5
700
620
–
–
751
751
751
401
301
Model
ERF-
150WJ_
401
401
201
201
101
401
–
–
Resistance
Ω
400
400
200
200
100
70
62
–
–
750
750
750
400
300
No. of used
Braking torque %
1
1
–
–
1
1
1
1
1
1
1
1
1
1
220
220
220
125
125
120
100
–
–
230
230
130
125
115
400
–
–
2
–
–
105
–
–
22P2
23P7
25P5
27P5
–
40P7
40P7
41P5
42P2
Model
LKEB-
#
–
–
20P7
20P7
21P5
Resistor spec.
(per one unit)
W
Ω
–
–
70 200
70 200
260 100
260 70
390 40
520 30
780 20
–
70 750
70 750
260 400
260 250
No. of used
Braking torque %
1
1
1
1
1
1
–
–
1
1
1
1
–
1
–
–
220
125
125
120
125
115
125
–
230
130
125
135
43P7
45P5
47P5
390 150
520 100
780 75
1
1
1
135
135
130
Connectable min. resistance
Ω
300
300
200
120
60
60
32
9.6
9.6
750
750
510
240
200
100
32
32
Varispeed V7 349
Y203-EN2-02-Katalog.book Seite 350 Mittwoch, 24. Mai 2006 2:22 14
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. I20E-EN-02 In the interest of product improvement, specifications are subject to change without notice.
350 Frequency inverters