YASKAWA AC Drive-L1000A
AC Drive for Elevator Applications
Quick Start Guide
Type: CIMR-LU A
Models: 200 V Class: 1.5 to 110 kW (2 to 150 HP)
400 V Class: 1.5 to 315 kW (2 to 500 HP)
600 V Class: 1.5 to 160 kW (2 to 250 HP)
To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance. Ensure the end user receives this manual.
MANUAL NO. TOEP C710616 38H
Receiving
1
Mechanical Installation
2
Electrical Installation
3
Start-Up Programming &
Operation
4
Troubleshooting
5
Periodic Inspection &
Maintenance
6
Option Card Installation
Specifications
7
A
Parameter Table
Standards Compliance
B
C
TOEP_C710616_38H_7_0.book 2 ページ 2015年11月11日 水曜日 午後7時40分
Copyright © 2010 YASKAWA ELECTRIC CORPORATION.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of Yaskawa. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, Yaskawa assumes no responsibility for errors or omissions.
Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
2 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
Yaskawa AC Drive L1000A
Supplement to L1000A Manuals
Introduction
This supplement to L1000A Manuals describes features or functions that are changed with a L1000A software upgrade, and should be read to ensure proper usage. Read this supplement together with the
L1000A Quick Start Guide No. TOEPC71061638 or Technical Manual No. SIEPC71061638. Observe all safety messages and precautions to prevent injury to personnel and to ensure correct application of the product.
Applicable Software Version
Applicable to L1000A software version PRG: 7205 and later.
See the product nameplate or parameter U1-25 to confirm the L1000A software version.
< Added items >
◆ Addition: PM Tuning Setup
PM Tuning Setup for simplified elevator system setup.
Control
Mode
A1-02=7
Input parameters during tuning
T2-04:
Motor Rated Power
T2-05:
Motor Rated Voltage
T2-06:
Motor Rated Current
T2-08:
Number of Motor
Poles
T2-09:
Motor Base Speed
T2-16:
Encoder Resolution
Tuning process
Step 1 :
Stationary Auto-Tuning
(Same as T2-01=1)
Step 2 :
Initial magnet pole search parameters
Auto-Tuning
(Same as T2-01=3)
Step 3 :
Encoder offset stationary Auto-Tuning
(Same as T2-01=4)
Step 1 :
E5-09=0
Parameters set after
Auto Tuning
F1-01= Users T2-16 input value
A1-02=Users input value
E5-02=UsersT 2-04 input value
E5-03=Users T2-06 input value
E5-04=Users T2-08 input value
E5-05=Tuning result
E5-06=Tuning result
E5-07=Tuning result
E5-24=Tuning result
E1-06=Users T2-09 input value
E1-04=E1-06
E1-09=0
E1-05=Users T2-05 input value
Step 2 : n8-36=Tuning result n8-37=Tuning result n8-81=Tuning result n8-82=Tuning result
Step 3 :
E5-11=Tuning result
Note : If tuning is interrupted, the tuning results for completed steps are preserved.
Page 1 of 2
Document No. EZZ023447
Prepared: December, 2016
Revised by Yaskawa America: April, 2017
◆ Addition: Brake Torque Check Function
The brake torque check function checks for holding torque of the motor brake.
■ Add aram ters
No.
( Addr.
)
Name Description
S5-15
(6D8H)
The allowable amount of cargo movement during a brake torque check
CLV CLV/PM
Sets the allowable amount of cargo movement during a brake torque check.
parameter o1
Setting
Default :
Range : o1-12=0:
0 to 100 mm o1-12=1:
0 to 3.93 in
The brake torque
CLV CLV/PM
S5-16
(6D9H)
The amount of torque applied during a brake torque check. Set as a percentage of motor rated torque. if torque limit amount of the drive.
Default :
Range :
100 %
50 to 200 %
Brake torque rise time
S5-17
(6DCH)
CLV CLV/PM eter sets the rise time to achieve the brake torque value set in parameter S
Default :
Range :
0.5 sec
0.0 to 3.0 sec
Brake torque check fall time
CLV CLV/PM
S5-18
(6DDH)
Default :
Range :
0.5 sec
0.0 to 3.0 sec
Brake torque check operating time
CLV CLV/PM
S5-19
(6DEH) which the brake torque is maintained at the
Default :
Range :
3.0sec
0.0 to10.0sec
(*1) The factory default value of o2-12 is 0. This causes the units for parameter S5-15 to be mm.
■ Addition: Multi-Function Digital Input
H1□□
Setting
Name Description
CLV CLV/PM
5DH ctivate brake torque check
■ Addition: Multi-Function Digital Outputs
H2□□
Setting
Name
To activate the brake torque check
CLV CLV/PM
Description
5DH active
Closed : During brake torque check
CLV CLV/PM
5EH completion
■ Addition: Fault
Digital Operator Display
brA
Fault Name
Brake torque degradation
The allowable amount of cargo movement set in parameter
S5-15 was exceeded during a brake torque check.
TOEP_C710616_38H_7_0.book 3 ページ 2015年11月11日 水曜日 午後7時40分
■
Quick Reference
Drive a Synchronous PM Motor
L1000A can operate synchronous PM motors.
Refer to Flowchart C: Auto-Tuning for PM Motors on page 71
.
Perform Auto-Tuning
Automatic tuning sets motor parameters. Refer to Types of Auto-Tuning on page 73 .
Maintenance Check Using Drive Monitors
Fault Display and Troubleshooting
Refer to Troubleshooting on page 132
.
Standards Compliance
Refer to European Standards on page 216 and
UL and CSA Standards on page 224 .
CSA B44.1 /
ASME A17.5
Y E A
_ c o m m o n
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 3
TOEP_C710616_38H_7_0.book 4 ページ 2015年11月11日 水曜日 午後7時40分
4 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 5 ページ 2015年11月11日 水曜日 午後7時40分
Table of Contents
Preface & General Safety ................................................................................................. 7
Receiving......................................................................................................................... 15
Mechanical Installation .................................................................................................. 17
Electrical Installation...................................................................................................... 25
Start-Up Programming & Operation ............................................................................. 58
Troubleshooting ........................................................................................................... 132
Periodic Inspection & Maintenance ........................................................................... 143
Option Card Installation ............................................................................................... 150
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 5
TOEP_C710616_38H_7_0.book 6 ページ 2015年11月11日 水曜日 午後7時40分
Table of Contents
Specifications................................................................................................................ 161
Parameter Table ............................................................................................................ 166
Defaults and Setting Ranges by Display Unit Selection (o1-03) . . . . . . . . . . . . . . . . .215
Standards Compliance ................................................................................................. 216
Revision History............................................................................................................. 244
6 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 7 ページ 2015年11月11日 水曜日 午後7時40分 i Preface & General Safety
i Preface & General Safety
◆
Preface
Yaskawa manufactures products used as components in a wide variety of industrial systems and equipment. The selection and application of Yaskawa products remain the responsibility of the equipment manufacturer or end user. Yaskawa accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances should any Yaskawa product be incorporated into any product or design as the exclusive or sole safety control. Without exception, all controls should be designed to detect faults dynamically and fail safely under all circumstances. All systems or equipment designed to incorporate a product manufactured by Yaskawa must be supplied to the end user with appropriate warnings and instructions as to the safe use and operation of that part. Any warnings provided by Yaskawa must be promptly provided to the end user. Yaskawa offers an express warranty only as to the quality of its products in conforming to standards and specifications published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR
IMPLIED, IS OFFERED. Yaskawa assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its products.
This manual is designed to ensure correct and suitable application of L1000A-Series Drives. Read this manual before attempting to install, operate, maintain, or inspect a drive and keep it in a safe, convenient location for future reference.
Be sure you understand all precautions and safety information before attempting application.
■
Applicable Documentation
The following manuals are available for L1000A series drives:
DIGITAL OPERATOR JVOP-180
ALM
F1
ESC
RESET
RUN
F2
LO
RE
ENTER
STOP
S/N:
WARNING
Risk of electric shock.
Read manual before installing.
Wait 5 minutes for capacitor discharge after disconnecting power supply.
To conform to requirements, make sure to ground the supply neutral for 400V class.
After opening the manual switch between the drive and motor, please wait 5 minutes before inspecting, performing maintenance or wiring the drive.
Hot surfaces
Top and Side surfaces may become hot. Do not touch.
AVERTISSMENT NPJT31470-1
Risque de décharge électrique.
Lire le manuel avant l'installation.
Attendre 5 minutes après la coupure de l'alimentation, pour permettre la décharge des condensateurs.
Pour répondre aux exigences , s assurer que le neutre soit relié
à la terre, pour la série 400V.
Après avoir déconnécte la protection entre le driver et le moteur, veuillez patienter 5 minutes avain d’effectuer une opération de montage ou de câblage du variateur.
Surfaces Chaudes
Dessus et cotés du boitier Peuvent devenir chaud. Ne Pas toucher.
危 険
けが.感電のおそれがあります。
据え付け、運転の前には必ず取扱説明書を読むこと。
通電中および電源遮断後 5 分以内はフロントカバー
を外さない事。
400V 級インバータの場合は、電源の中性点が接地
されていることを確認すること。( 対応)
保守・点検、配線を行う場合は、出力側開閉器を
遮断後
高温注意
インバータ上部、両側面は高温になります。
触らないでください。
YEA_ common
L1000A Series AC Drive Quick Start Guide (this book)
Read this manual first. This guide is packaged together with the product. It contains basic information required to install and wire the drive, in addition to an overview of fault diagnostics, maintenance, and parameter settings. Use the information in this book to prepare the drive for a trial run with the application and for basic operation.
L1000A Series AC Drive Technical Manual
This manual provides detailed information on parameter settings, drive functions, and MEMOBUS/
Modbus specifications. Use this manual to expand drive functionality and to take advantage of higher performance features.
◆
General Safety
■
Supplemental Safety Information
General Precautions
• The diagrams in this manual may be indicated without covers or safety shields to show details. Replace the covers or shields before operating the drive and run the drive according to the instructions described in this manual.
• Any illustrations, photographs, or examples used in this manual are provided as examples only and may not apply to all products to which this manual is applicable.
• The products and specifications described in this manual or the content and presentation of the manual may be changed without notice to improve the product and/or the manual.
• When ordering a new copy of the manual due to damage or loss, contact your Yaskawa representative or the nearest Yaskawa sales office and provide the manual number shown on the front cover.
• If nameplate becomes worn or damaged, order a replacement from your Yaskawa representative or the nearest Yaskawa sales office.
W ARNING
Read and understand this manual before installing, operating or servicing this drive. The drive must be installed according to this manual and local codes.
The following conventions are used to indicate safety messages in this manual. Failure to heed these messages could result in serious or fatal injury or damage to the products or to related equipment and systems.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 7
TOEP_C710616_38H_7_0.book 8 ページ 2015年11月11日 水曜日 午後7時40分 i Preface & General Safety
DANGER
Indicates a hazardous situation, which, if not avoided, will result in death or serious injury.
W ARNING
Indicates a hazardous situation, which, if not avoided, could result in death or serious injury.
WARNING!
may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
CAUTION
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury.
CAUTION!
may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
NOTICE
Indicates a property damage message.
NOTICE: may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
■
Safety Messages
DANGER
Heed the safety messages in this manual.
Failure to comply will result in death or serious injury.
The operating company is responsible for any injuries or equipment damage resulting from failure to heed the warnings in this manual.
Electrical Shock Hazard
Do not connect or disconnect wiring or service the drive while the power is on.
Failure to comply will result in death or serious injury.
Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. After shutting off the power, wait for at least the amount of time specified on the drive before touching any components.
W ARNING
Sudden Movement Hazard
The drive system or elevator may start unexpectedly upon application of power, resulting in death or serious injury.
• Clear all personnel from the drive, motor, and machine area before applying power.
• Secure covers, couplings, shaft keys, and machine loads before applying power to the drive.
Ensure there are no short circuits between the main circuit terminals (R/L1, S/L2, and T/L3) or between the ground and main circuit terminals before restarting the drive.
Failure to comply may result in serious injury or death and will cause damage to equipment.
8 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 9 ページ 2015年11月11日 水曜日 午後7時40分 i Preface & General Safety
W ARNING
System may start unexpectedly upon application of power when the Auto-restart function is enabled resulting in death or serious injury.
Use care when enabling Auto-restart as this function may cause unintended start of the elevator.
Use parameter S1-12 to enable/disable automatic switching of the Motor Contactor Control output signal during Auto-Tuning.
When using setting S1-12 = 1 or 2, ensure that the multi-function output terminals are properly wired and in the correct state before setting parameter S1-12.
Failure to comply could result in damage to the drive, serious injury or death.
Electrical Shock Hazard
Do not attempt to modify or alter the drive in any way not explained in this manual.
Yaskawa is not responsible for damage caused by modification of the product made by the user. Failure to comply could result in death or serious injury from operation of damaged equipment.
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall covers or shields before operating the drives and run the drives according to the instructions described in this manual.
When a drive is running a PM motor, voltage continues to be generated at the motor terminals after the drive is shut off while the motor coasts to stop. Take the precautions described below to prevent shock and injury:
• In applications where the machine can still rotate even though the drive has fully stopped a load, install a switch to the drive output side to disconnect the motor and the drive.
• Do not allow an external force to rotate the motor beyond the maximum allowable speed or to rotate the motor when the drive has been shut off.
• Wait for at least the time specified on the warning label after opening the load switch on the output side before inspecting the drive or performing any maintenance.
• Do not open and close the load switch while the motor is running, as this can damage the drive.
If the motor is coasting, make sure the power to the drive is turned on and the drive output has completely stopped before closing the load switch.
Do not connect or disconnect wiring to the drive or motor while the power is on.
Failure to comply will result in death or serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are
OFF and measure the DC bus voltage level to confirm safe level.
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall covers or shields before operating the drives and run the drives according to the instructions described in this manual.
Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection.
Failure to comply could result in death or serious injury.
Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning work on the drive.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 9
TOEP_C710616_38H_7_0.book 10 ページ 2015年11月11日 水曜日 午後7時40分 i Preface & General Safety
W ARNING
Do not change wiring, remove covers, connectors or options cards, or attempt to service the drive with power applied to the drive.
Failure to comply could result in death or serious injury. Disconnect all power to the drive and check for unsafe voltages before servicing.
Do not allow unqualified personnel to use the equipment.
Failure to comply could result in death or serious injury.
Maintenance, inspection, and replacement of parts must be performed only by authorized personnel familiar with installation, adjustment and maintenance of AC drives.
Fire Hazard
Drive Short-Circuit Current Rating
Install adequate branch circuit protection according to applicable local codes and this Installation Manual.
Failure to comply could result in fire and damage to the drive or injury to personnel.
The device is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes, 240
Vac maximum (200 V class) and 480 Vac maximum (400 V class), and 600 Vac maximum (600 V class) when protected by branch circuit protection devices specified in this manual.
Applications using a braking option should wire a thermal relay so that the output contactor opens when the thermal relay trips.
Inadequate braking circuit protection could result in death or serious injury by fire from overheating resistors.
Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire.
Attach the drive to metal or other noncombustible material.
NOTICE
Equipment Hazard
Do not modify the drive circuitry.
Failure to comply could result in damage to the drive and will void warranty.
Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified.
Failure to comply could result in damage to the drive or braking circuit.
Observe proper electrostatic discharge procedures (ESD) when handling the drive, circuit boards, and option cards.
Failure to comply may result in ESD damage to the drive circuitry.
If a fuse is blown or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of the peripheral devices.
Check for short circuits or ground faults on the secondary side of fuses and Ground Fault Circuit Interrupters (GFCI), and check the wiring and the selection of peripheral devices. Remove the cause of the problem and then turn the power supply on again. If the cause cannot be identified, do not turn on the power supply or attempt to operate the equipment.
Do not restart the drive immediately operate the peripheral devices if a fuse is blown or a GFCI is tripped.
Check the wiring and the selection of peripheral devices to identify the cause. Contact your supplier before restarting the drive or the peripheral devices if the cause cannot be identified.
10 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 11 ページ 2015年11月11日 水曜日 午後7時40分 i Preface & General Safety
NOTICE
Do not operate damaged equipment.
Failure to comply could result in further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
Do not lift the drive up while the cover is removed.
This can damage the terminal board and other components.
Do not expose the drive to halogen group disinfectants.
Failure to comply may cause damage to the electrical components in the drive.
Do not pack the drive in wooden materials that have been fumigated or sterilized.
Do not sterilize the entire package after the product is packed.
■
General Application Precautions
Motor Selection
Drive Capacity
The output current should not exceed 150% of the drive rated current. Select a drive that can output enough current when accelerating a load at 100%.
For specialized motors, make sure that the motor rated current is less than the rated output current for the drive.
Starting Torque
The startup and acceleration characteristics of the motor are restricted to the drive's overload current rating (150% rated current for 60 s).
The overload rating for the drive determines the starting and accelerating characteristics of the motor. Expect lower torque than when running from line power. To get more starting torque, use a larger drive or increase both the motor and drive capacity.
Stopping
Fast Stop
When the drive faults out, a protective circuit is activated and drive output is shut off. This, however, does not stop the motor immediately. A mechanical brake may be required to stop the motor if Fast Stop deceleration is insufficient.
Mechanical Brake
A mechanical brake is required to prevent the elevator from free falling during a drive fault condition.
Repetitive Starting/Stopping
Elevators and other applications with frequent starts and stops often approach 150% of their rated current values. Heat stress generated from repetitive high current will shorten the life span of the IGBTs. The expected lifetime for the IGBTs is about 3 million start and stop cycles with a default carrier frequency of 2 kHz (CIMR-LU2 0346, 2 0415), 5 kHz
(CIMR-LU4 0112 to 4 0216), or 8 kHz (CIMR-LU2 0008 to 2 0115, 4 0005 to 4 0091) and a 150% peak current.
Yaskawa recommends lowering the carrier frequency, particularly when audible noise is not a concern. It is beneficial to reduce the load, increase the acceleration and deceleration times, or switch to a larger drive to help keep peak current levels under 150%. Be sure to check the peak current levels when starting and stopping repeatedly during the initial test run, and make adjustments accordingly.
Installation
Enclosure Panels
Keep the drive in a clean environment by installing the drive in an enclosure panel or selecting an installation area free of airborne dust, lint, and oil mist. Be sure to leave the required space between drives to provide for cooling, and take proper measures so the ambient temperature remains within allowable limits and keep flammable materials away from the drive.
Yaskawa offers protective designs for drives that must be used in areas subjected to oil mist and excessive vibration.
Contact Yaskawa or your Yaskawa agent for details.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 11
TOEP_C710616_38H_7_0.book 12 ページ 2015年11月11日 水曜日 午後7時40分 i Preface & General Safety
Installation Direction
NOTICE: Install the drive upright as specified in the manual.
Refer to Mechanical Installation on page 17
installation. Failure to comply may damage the drive due to improper cooling.
for more information on
Settings
DC Injection Braking
NOTICE: Excessive current during DC Injection Braking and excessive duration of DC Injection Braking can cause motor overheating.
Adjust DC Injection parameters to prevent motor overheating.
Acceleration/Deceleration Ramp
Acceleration and deceleration times are affected by the amount of torque generated by the motor, the load torque, and the inertia moment. Set a longer accel/decel time when Stall Prevention is enabled. The accel/decel times are lengthened for as long as the Stall Prevention function is in operation. Install one of the available braking options or increase the capacity of the drive for faster acceleration and deceleration.
General Handling
Selecting a Molded Case Circuit Breaker or Ground Fault Circuit Interrupter (GFCI)
Select an appropriate GFCI. This drive can cause a residual current with a DC component in the protective earthing conductor. Where a residual current operated protective or monitoring device is used for protection in case of direct or indirect contact, always use an GFCI of type B according to IEC/EN 60755.
Select a MCCB (Molded Case Circuit Breaker) with a rated current that is 1.5 to 2 times higher than the rated current of the drive in order to avoid nuisance trips caused by harmonics in the drive input current.
WARNING!
Sudden Movement Hazard. Install a properly controlled contactor on the input-side of the drive for applications where power should be removed from the drive during a fault condition. Improper equipment sequencing could result in death or serious injury.
WARNING!
Fire Hazard. Shut off the drive with a magnetic contactor (MC) when a fault occurs in any external equipment such as braking resistors. Failure to comply may cause resistor overheating, fire, and injury to personnel.
NOTICE: To get the full performance life out of the electrolytic capacitors and circuit relays, refrain from switching the drive power supply off and on more than once every 30 minutes. Frequent use can damage the drive. Use the drive to stop and start the motor.
Inspection and Maintenance
WARNING!
Electrical Shock Hazard. Capacitors in the drive do not immediately discharge after shutting off the power. Wait for at least the amount of time specified on the drive before touching any components after shutting off the power. Failure to comply may cause injury to personnel from electrical shock.
CAUTION!
Burn Hazard. Because the heatsink can get very hot during operation, take proper precautions to prevent burns. When replacing the cooling fan, shut off the power and wait at least 15 minutes to be sure that the heatsink has cooled down. Failure to comply may cause burn injury to personnel.
WARNING!
Electrical Shock Hazard. When a drive is running a PM motor, voltage continues to be generated at the motor terminals after the drive is shut off while the motor coasts to stop. Take the precautions described below to prevent shock and injury:
• In applications where the machine can still rotate after the drive has fully stopped a load, install a load disconnect switch on the drive output side to disconnect the motor and the drive.
• Do not allow an external force to rotate the motor beyond the maximum allowable speed or to rotate the motor when the drive is powered off.
• Wait for at least the time specified on the warning label after opening the load switch on the output side before inspecting the drive or performing any maintenance.
• Do not open and close the load switch while the motor is running.
• If the motor is coasting, make sure the power to the drive is turned on and the drive output has completely stopped before closing the load switch to reconnect the drive to the motor.
Wiring
Yaskawa recommends using ring terminals on all drive models for UL/cUL compliance. Use only the tools recommended by the terminal manufacturer for crimping.
12 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 13 ページ 2015年11月11日 水曜日 午後7時40分 i Preface & General Safety
Transporting the Drive
NOTICE: Never steam clean the drive. During transport, keep the drive from coming into contact with salts, fluorine, bromine, phthalate ester, and other such harmful chemicals. Failure to comply may damage the drive.
■
Motor Application Precautions
Standard Induction Motors
Insulation Tolerance
NOTICE: Consider motor voltage tolerance levels and motor insulation in applications with an input voltage of over 440 V or particularly long wiring distances.
NOTICE: Ensure that the motor is suitable for inverter duty and/or the motor service factor is adequate to accommodate the additional heating with the intended operating conditions. A motor connected to a PWM drive may operate at a higher temperature than a utility-fed motor and the operating speed range may reduce motor cooling capacity.
High-Speed Operation
NOTICE: Mechanical damage may occur with the motor bearings and dynamic balance of the machine when operating a motor beyond its rated speed. Operate the motor within specifications to prevent motor damage.
Low-Speed Range
The cooling fan of a standard motor should sufficiently cool the motor at the rated speed. As the self-cooling capability of such a motor reduces with the speed, applying full torque at low speed will possibly damage the motor. Reduce the load torque as the motor slows to prevent motor damage from overheat. Use a motor designed specifically for operation with a drive when 100% continuous torque is needed at low speeds.
Torque Characteristics
Torque characteristics differ compared to operating the motor directly from line power. The user should have a full understanding of the load torque characteristics for the application.
Vibration and Shock
The drive allows selection of high carrier PWM control and low carrier PWM control. Selecting high carrier PWM can help reduce motor oscillation.
If resonance occurs, install shock-absorbing rubber mounts around the base of the motor and utilize the Jump frequency selection to prevent continuous operation in the resonant frequency ranges.
Audible Noise
Noise created during run varies by the carrier frequency setting. When using a high carrier frequency, audible noise from the motor is comparable to the motor noise generated when running from line power. Operating above the rated r/min, however, can create unpleasant motor noise.
Precautions for PM Motors
NOTICE: Damage to Equipment. Improper sequencing of output motor circuits could result in damage to the drive. Do not connect electromagnetic switches or magnetic contactors to the output motor circuits without proper sequencing. Do not open the main circuit between the drive and the motor while the PM motor is rotating.
• Contact Yaskawa or your Yaskawa agent if you plan to use any PM motor not endorsed by Yaskawa.
• When using a holding brake, release the brake prior to starting the motor. Failure to set the proper timing can result in speed loss.
WARNING!
Sudden Movement Hazard. Use the Initial Pole Search Status Signal (H2 = 61) to interlock the brake to ensure the brake is not released before the Initial Magnetic Pole Search is completed. Failure to comply may cause inadvertent elevator movement resulting in serious injury.
This safety message is applicable under these conditions:
• When applying a PM motor, with an external brake sequence, and the PG-F3 option is not being used.
WARNING!
Electrical Shock Hazard. The motor must be at a complete stop before performing any maintenance, inspection, or wiring.
• With a PM motor, drive output must be fully interrupted when the power is shut off and the motor is still rotating.
Failure to comply can result in personal injury from electrical shock.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 13
TOEP_C710616_38H_7_0.book 14 ページ 2015年11月11日 水曜日 午後7時40分 i Preface & General Safety
■
Drive Label Warnings
Always heed the warning information listed in Figure 1
in the position shown in
Figure 1
WARNING
●
●
●
●
●
Risk of electric shock.
Read manual before installing.
Wait 5 minutes for capacitor discharge after disconnecting power supply.
To conform to requirements, make sure to ground the supply neutral for 400V class.
After opening the manual switch between the drive and motor, please wait 5 minutes before inspecting, performing maintenance or wiring the drive.
Hot surfaces
Top and Side surfaces may become hot. Do not touch.
Figure 1 Warning Information
Figure 2
DIGITAL OPERATOR JVOP-180 ALM
F1
ESC
RESET
RUN
F2
LO
RE
ENTER
STOP
CIMR
200V 3Phase 5.5kW/3.7kW
S/N:
WARNING
Risk of electric shock.
●
●
Read manual before installing.
Wait 5 minutes for capacitor
● discharge after disconnecting power supply.
●
To conform to requirements, make sure to ground the supply neutral for 400V class.
After opening the manual switch between the drive and motor, please wait 5 minutes before inspecting, performing maintenance or wiring the drive.
Hot surfaces
● Top and Side surfaces may become hot. Do not touch.
●
●
●
●
AVERTISSMENT NPJT31470-1
Risque de décharge électrique.
●
●
Lire le manuel avant l'installation.
Attendre 5 minutes après la coupure
● de l'alimentation, pour permettre la décharge des condensateurs.
● assurer que le neutre soit relié
à la terre, pour la série 400V.
Après avoir déconnécte la protection entre le driver et le moteur, veuillez patienter 5 minutes avain d’effectuer une opération de montage ou de câblage du variateur.
Surfaces Chaudes
● Dessus et cotés du boitier Peuvent devenir chaud. Ne Pas toucher.
危 険
●
けが.感電のおそれがあります。
●
据え付け、運転の前には必ず取扱説明書を読むこと。
通電中および電源遮断後 5 分以内はフロントカバー
●
●
を外さない事。
級インバータの場合は、電源の中性点が接地
されていることを確認すること。( 対応)
保守・点検、配線を行う場合は、出力側開閉器を
遮断後 5 分待って実施してください。
●
高温注意
インバータ上部、両側面は高温になります。
触らないでください。
YEA_comm on
Warning Label
Figure 2 Warning Information Position
■
Warranty Information
Restrictions
The drive is not designed or manufactured for use in devices or systems that may directly affect or threaten human lives or health.
Customers who intend to use the product described in this manual for devices or systems relating to transportation, health care, space aviation, atomic power, electric power, or in underwater applications must first contact their Yaskawa representatives or the nearest Yaskawa sales office.
WARNING!
Injury to Personnel. This product has been manufactured under strict quality-control guidelines. However, if this product is to be installed in any location where failure of this product could involve or result in a life-and-death situation or loss of human life or in a facility where failure may cause a serious accident or physical injury, safety devices must be installed to minimize the likelihood of any accident.
14 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 15 ページ 2015年11月11日 水曜日 午後7時40分
1 Receiving
1 Receiving
◆
Model Number and Nameplate Check
Please perform the following tasks after receiving the drive:
• Inspect the drive for damage.
If the drive appears damaged upon receipt, contact the shipper immediately.
• Verify receipt of the correct model by checking the information on the nameplate.
• If you have received the wrong model or the drive does not function properly, contact your supplier.
Description Drive
Controller Power Supply Cable for Rescue Operation
Quick Start Guide
–
YEA_co mmon
Quick Start Guide
Quantity
■
Figure 1
Nameplate
1 1 1
YEA_common
AC drive model
Input specifications
Output specifications
Lot number
Serial number
200/400 V Class
MODEL
C / C
: CIMR-LU2A0018DAA
REV: A
: CIMR-LU2A0018DAA
INPUT
S / N
: AC3PH 200-240V 50/60Hz 18.9A
OUTPUT
MASS
O / N
: AC3PH 0-240V 0-200Hz 17.5A
: 3.5 kg PRG : 7010
:
:
IND.CONT.EQ.
7J48 B
Design revision order
Software version
AC drive model
Input specifications
Output specifications
Lot number
Serial number
FILE NO : E131457 IP00 PASS
YASKAWA ELECTRIC CORPORATION MADE IN JAPAN
2-1 Kurosaki-shiroishi, Yahatanishi-Ku, Kitakyushu 806-0004 Japan <1>
Enclosure type
Normal Duty Amps / Heavy Duty
Amps 600 V Class
MODEL : CIMR-LU5A0006DAA REV : A
C/C CIMR-LU5A0006DAA
INPUT
OUTPUT : AC3PH 0-600V 0-200Hz 6.3A
MASS
O / N
S / N
: AC3PH 500-600V 50/60Hz 8.3A
: 3.5 kg
:
:
PRG : 7010
IND.CONT.EQ.
7J48 B
Software version
<1>
FILE NO : E131457 IP00
PASS
YASKAWA ELECTRIC CORPORATION MADE IN JAPAN
2-1 Kurosaki-shiroishi, Yahatanishi-Ku, Kitakyushu 806-0004 Japan
Enclosure type
<1> The address of the head office of Yaskawa Electric Corporation (responsible for product liability) is shown on the nameplate.
Figure 1 Nameplate Information
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 15
1
TOEP_C710616_38H_7_0.book 16 ページ 2015年11月11日 水曜日 午後7時40分
1 Receiving
■
Model Number
CIMR - L U 2
Drive
No.
U
L1000A
Series
Region
Code
U.S.A.
A
No.
Customized
Specifications
A Standard model
F
Models in compliance with
IEC/EN 61508
SIL3 Safety
Integrity Level 3
0018 D
No. Enclosure Type
A
D
IP00
IP00 with top protective cover
A
No.
A
Environmental
Specification <1>
Standard
A
Design
Revision
Order
YEA_common
No.
2
4
5
Voltage Class
3-phase, 200-240 Vac
3-phase, 380-480 Vac
3-phase, 500-600 Vac
.
<1> Drives with these specifications do not guarantee complete protection for the environmental conditions indicated.
Table 1 Model Number and Specifications
2
2
2
2
2
2
Three-Phase 200 V Class
Drive
Model
Max. Motor
Capacity
(HP)
Rated
Output
Current
(A)
2 0008
2 0011
2 0014
2 0018
2 0025
2 0033
0047
0060
2 0075
2 0085
0115
0145
2 0180
2 0215
0283
0346
2 0415
–
–
–
–
–
2
3
3
5
7.5
10
25
30
60
75
100
125
150
–
–
–
15
20
40
50
–
–
8
11
14
17.5
25
33
47
60
75
85
115
145
180
215
283
346
415
–
–
–
–
–
Three-Phase 400 V Class
Drive
Model
Max. Motor
Capacity
(HP)
Rated
Output
Current
(A)
4 0005
4 0006
4 0007
4 0009
4 0015
4 0018
4
4
0024
0031
4 0039
4 0045
4
4
0060
0075
3
3
5
5
7.5
10
15
20
25-30
25-30
40
50-60
4.8
5.5
7.2
9.2
14.8
18
24
31
39
45
60
75
4 0091
4 0112
4 0150
4 0180
4 0216
4 0260
4 0304
4 0370
50-60
75
100
125-150
150
200
250
300
4 0450 350
4 0605 400-450-500
216
260
304
370
91
112
150
180
450
605
5 0077
5 0099
5 0130
5 0172
5 0200
–
–
–
–
–
Three-Phase 600 V Class
Drive
Model
Max. Motor
Capacity
(HP)
Rated
Output
Current
(A)
5 0003
5 0004
5 0006
5 0010
5 0013
5 0017
5
5
0022
0027
5 0032
5 0041
5
5
0052
0062
2
3
5
7.5
10
15
20
25
25-30
40
50-60
50-60
3.5
4.1
6.3
9.8
12.5
17
22
27
32
41
52
62
75
100
125
150
200
–
–
–
–
–
200
–
–
–
77
99
130
172
–
–
Figure 2
16 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 17 ページ 2015年11月11日 水曜日 午後7時40分
2 Mechanical Installation
2 Mechanical Installation
◆
Mechanical Installation
This section outlines specifications, procedures, and the environment for proper mechanical installation of the drive.
CAUTION!
Crush Hazard. Carrying the drive by the front cover may cause the main body of the drive to fall, resulting in minor or moderate injury. Always hold the case when carrying the drive.
■
Installation Environment
Install the drive in an environment matching the specifications below to help prolong the optimum performance life of the drive.
Table 2 Installation Environment
Environment
Installation Area
Ambient Temperature
Humidity
Storage Temperature
Surrounding Area
Altitude
Vibration
Orientation
Conditions
Indoors
IP00 enclosure with top protective cover: -10 to +40 ° C (14 to 104 ° F)
IP00 enclosure: -10 to +50 ° C (14 to 122 ° F)
Drive reliability improves in environments without wide temperature fluctuations.
When using the drive in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the drive.
95% RH or less and free of condensation
-20 to 60 ° C (-4 to 140 ° F)
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
1000 m or lower, up to 3000 m with derating 1000 m (3280 ft.) or lower, up to 3000 m (9842 ft.) with derating
(Refer to
Altitude Derating on page 165 .)
10 to 20 Hz at 9.8 m/s 2
20 to 55 Hz at 5.9 m/s 2 (CIMR-LU2 0008 to 2 0180, 4 0005 to 4 0150, and 5 0003 to 5 0077)
2.0 m/s 2 (CIMR-LU2 0215 to 2 0415, CIMR-LU4 0180 to 4 0605, and 5 0099 to 5 0200)
Install the drive vertically to maintain maximum cooling effects.
NOTICE: Avoid placing drive peripheral devices, transformers, or other electronics near the drive as the noise created can lead to erroneous operation. If such devices must be used in close proximity to the drive, take proper steps to shield the drive from noise.
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the drive during installation. Failure to comply could result in damage to the drive. Place a temporary cover over the top of the drive during installation. Remove the temporary cover before startup, as the cover will reduce ventilation and cause the drive to overheat.
2
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 17
TOEP_C710616_38H_7_0.book 18 ページ 2015年11月11日 水曜日 午後7時40分
2 Mechanical Installation
■
Installation Orientation and Spacing
WARNING!
Fire Hazard. Provide sufficient cooling when installing the drive inside an enclosed panel or cabinet. Failure to comply could result in overheating and fire. When drives are placed inside the same enclosure panel, install proper cooling to ensure air entering the enclosure does not exceed 40 ° C (104 ° F).
Installation Orientation
Install the drive upright as illustrated in Figure 2
to maintain proper cooling. Refer to
Mechanical Installation on page 17 for details on installing the drive.
Figure 3
OK Not OK Not OK
Figure 2 Correct Installation Orientation
Installation Spacing
shows the installation distance required to maintain sufficient space for airflow and wiring.
Figure 4
Side Clearance Top/Bottom Clearance
A
C
YEA_common
A
B B
C
D
D
A – 50 mm (1.97 in.) minimum
B – 30 mm (1.18 in.) minimum
C – 120 mm (4.72 in.) minimum
D – Airflow direction
Figure 3 Correct Installation Spacing
18 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 19 ページ 2015年11月11日 水曜日 午後7時40分
2 Mechanical Installation
■
Instructions on Installation
Eye bolts are used to install the drive or to temporarily lift the drive when replacing it. The drive can be installed in an enclosure panel or on a wall. Do not leave the drive suspended by the wires in a horizontal or vertical position for long periods of time. Do not transport the drive over long distances. Read the following precautions and instructions before installing the drives.
WARNING!
Be sure to observe the following instructions and precautions. Failure to comply could result in minor or moderate injury and damage to the drive from falling equipment.
• Before using wires to suspend the drive vertically and horizontally, make sure that the drive front cover, terminal blocks and other drive components are securely fixed with screws.
• Do not subject the drive to vibration or impact greater than 1.96 m/s 2 (0.2 G) while it is suspended by the wires.
• Do not overturn the drive while it is suspended by the wires.
• Do not leave the drive suspended by the wires for long periods of time.
Horizontal Suspension of the Drive (CIMR-LU2 0346, 2 0415, 4 0216 to 4 0605, and 5 0172 to 5 0200)
To make a wire hanger or frame for use when lifting the drive with a crane, lay the drive in a horizontal position and pass a wire through the holes of the four eye bolts.
When lifting the drive, confirm that the spring washer is fully closed. If not, the drive may become deformed or damaged when lifted.
Figure 5
A B C D
A – No space between drive and washer
B – Spring washer: Fully closed
C – Space between drive and washer
D – Spring washer: Open
Figure 4 Details of Spring Washers
Vertical Suspension of the Drive (CIMR-LU2 0346, 2 0415, 4 0216 to 4 0605, and 5 0172 to 5 0200)
When vertical suspension of the drive is required in an enclosure panel, the orientation of the eye bolts for these drive models can be easily changed by turning the eye bolts counterclockwise 90 degrees.
Figure 6
2
Figure 5 Adjusting Angle of Eye Bolts (CIMR-LU2 0346, 2 0415, 4 0216 to 4 0605, and 5 0172 to 5 0200)
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 19
TOEP_C710616_38H_7_0.book 20 ページ 2015年11月11日 水曜日 午後7時40分
2 Mechanical Installation
■
Exterior and Mounting Dimensions
IP00 Enclosure Drive with Top Protective Cover
4-d
W1
W1
4-d t2
20
W
0060
0075
0085
0115
0145
0180
Drive Model
CIMR-LU2
0008
0011
0014
0018
0025
0033
0047
Figure 1
Figure
1
2
W
140
(5.51)
140
(5.51)
180
(7.09)
220
(8.66)
140
(5.51)
140
(5.51)
140
(5.51)
140
(5.51)
220
(8.66)
250
(9.84)
275
(10.83)
325
(12.80)
325
(12.80)
D
D1 t1
Max 8
(0.31)
W
YEA_common
H
260
(10.24)
260
(10.24)
300
(11.81)
350
(13.78)
260
(10.24)
260
(10.24)
260
(10.24)
260
(10.24)
365
(14.37)
400
(15.75)
450
(17.72)
550
(21.65)
550
(21.65)
D
167
(6.57)
167
(6.57)
187
(7.36)
197
(7.76)
147
(5.79)
147
(5.79)
164
(6.46)
164
(6.46)
197
(7.76)
258
(10.16)
258
(10.16)
283
(11.14)
283
(11.14)
Table 3 Dimensions: 200 V Class
W1
122
(4.80)
122
(4.80)
160
(6.30)
192
(7.56)
122
(4.80)
122
(4.80)
122
(4.80)
122
(4.80)
192
(7.56)
195
(7.68)
220
(8.66)
260
(10.24)
260
(10.24)
Dimensions mm (in)
H1 H2
248
(9.76)
248
(9.76)
284
(11.18)
335
(13.19)
248
(9.76)
248
(9.76)
248
(9.76)
248
(9.76)
335
(13.19)
385
(15.16)
435
(17.13)
535
(21.06)
535
(21.06)
6
(0.24)
6
(0.24)
8
(0.31)
8
(0.31)
6
(0.24)
6
(0.24)
6
(0.24)
6
(0.24)
8
(0.31)
7.5
(0.30)
7.5
(0.30)
7.5
(0.30)
7.5
(0.30)
D1
55
(2.17)
55
(2.17)
75
(2.95)
78
(3.07)
38
(1.50)
38
(1.50)
55
(2.17)
55
(2.17)
78
(3.07)
100
(3.94)
100
(3.94)
110
(4.33)
110
(4.33)
Max 8
(0.31)
Figure 2 t1
5
(0.20)
5
(0.20)
5
(0.20)
5
(0.20)
5
(0.20)
5
(0.20)
5
(0.20)
5
(0.20)
5
(0.20)
2.3
(0.09)
2.3
(0.09)
2.3
(0.09)
2.3
(0.09) t2
–
–
–
–
–
–
–
–
–
2.3
(0.09)
2.3
(0.09)
2.3
(0.09)
2.3
(0.09)
D
D1 t1
M6
M6
M6
M6
M6
M6
M5
M5
M5
M5 d
M5
M5
M5
Wt. kg
(lb)
4
(8.8)
4
(8.8)
5.6
(12.3)
8.7
(19.2)
3.2
(7.1)
3.2
(7.1)
3.5
(7.7)
3.5
(7.7)
9.7
(21.4)
21
(46.3)
25
(55.1)
37
(81.6)
38
(83.8)
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 21 ページ 2015年11月11日 水曜日 午後7時40分
Drive Model
CIMR-LU4
0005
0006
0024
0031
0039
0045
0007
0009
0015
0018
0060
0075
0091
0112
0150
2 Mechanical Installation
Figure
1
2
325
(12.80)
325
(12.80)
325
(12.80)
325
(12.80)
180
(7.09)
220
(8.66)
250
(9.84)
275
(10.83)
140
(5.51)
140
(5.51)
140
(5.51)
180
(7.09)
W
140
(5.51)
140
(5.51)
140
(5.51)
510
(20.08)
510
(20.08)
550
(21.65)
550
(21.65)
300
(11.81)
350
(13.78)
400
(15.75)
450
(17.72)
H
260
(10.24)
260
(10.24)
260
(10.24)
260
(10.24)
260
(10.24)
260
(10.24)
300
(11.81)
258
(10.16)
258
(10.16)
283
(11.14)
283
(11.14)
187
(7.36)
197
(7.76)
258
(10.16)
258
(10.16)
164
(6.46)
167
(6.57)
167
(6.57)
167
(6.57)
D
147
(5.79)
164
(6.46)
164
(6.46)
Table 4 Dimensions: 400 V Class
260
(10.24)
260
(10.24)
260
(10.24)
260
(10.24)
160
(6.30)
192
(7.56)
195
(7.68)
220
(8.66)
122
(4.80)
122
(4.80)
122
(4.80)
160
(6.30)
W1
122
(4.80)
122
(4.80)
122
(4.80)
Dimensions mm (in)
495
(19.49)
495
(19.49)
535
(21.06)
535
(21.06)
284
(11.18)
335
(13.19)
385
(15.16)
435
(17.13)
248
(9.76)
248
(9.76)
248
(9.76)
284
(11.18)
H1
248
(9.76)
248
(9.76)
248
(9.76)
7.5
(0.30)
7.5
(0.30)
7.5
(0.30)
7.5
(0.30)
8
(0.31)
8
(0.31)
7.5
(0.30)
7.5
(0.30)
6
(0.24)
6
(0.24)
6
(0.24)
8
(0.31)
H2
6
(0.24)
6
(0.24)
6
(0.24)
105
(4.13)
105
(4.13)
110
(4.33)
110
(4.33)
75
(2.95)
78
(3.07)
100
(3.94)
100
(3.94)
55
(2.17)
55
(2.17)
55
(2.17)
55
(2.17)
D1
38
(1.50)
55
(2.17)
55
(2.17)
2.3
(0.09)
2.3
(0.09)
2.3
(0.09)
2.3
(0.09)
5
(0.20)
5
(0.20)
2.3
(0.09)
2.3
(0.09)
5
(0.20)
5
(0.20)
5
(0.20)
5
(0.20) t1
5
(0.20)
5
(0.20)
5
(0.20)
Wt. kg
(lb)
8.3
(18.3)
21
(46.3)
25
(55.1)
36
(79.4)
36
(79.4)
41
(90.4)
42
(92.6)
3.9
(8.6)
3.9
(8.6)
5.4
(11.9)
5.7
(12.6)
3.2
(7.1)
3.4
(7.5)
3.5
(7.7)
3.5
(7.7)
–
–
–
–
–
–
2.3
(0.09)
2.3
(0.09)
3.2
(0.13)
3.2
(0.13)
2.3
(0.09)
2.3
(0.09)
–
– t2
–
M6
M6
M6
M6
M5
M6
M6
M6
M5
M5
M5
M5 d
M5
M5
M5
2
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 21
TOEP_C710616_38H_7_0.book 22 ページ 2015年11月11日 水曜日 午後7時40分
2 Mechanical Installation
Drive Model
CIMR-LU5
0003
0004
0006
0010
0013
0017
0022
0027
0032
0041
0052
0062
0077
0099
Figure
1
2
220
(8.66)
275
(10.83)
275
(10.83)
325
(12.80)
325
(12.80)
325
(12.80)
450
(17.72)
140
(5.51)
180
(7.09)
180
(7.09)
220
(8.66)
W
140
(5.51)
140
(5.51)
140
(5.51)
350
(13.78)
450
(17.72)
450
(17.72)
550
(21.65)
550
(21.65)
550
(21.65)
705
(27.76)
H
260
(10.24)
260
(10.24)
260
(10.24)
260
(10.24)
300
(11.81)
300
(11.81)
350
(13.78)
197
(7.76)
258
(10.16)
258
(10.16)
283
(11.14)
283
(11.14)
283
(11.14)
330
(12.99)
167
(6.57)
187
(7.36)
187
(7.36)
197
(7.76)
D
147
(5.79)
164
(6.46)
164
(6.46)
Table 5 Dimensions: 600 V Class
192
(7.56)
220
(8.66)
220
(8.66)
260
(10.24)
260
(10.24)
260
(10.24)
325
(12.80)
122
(4.80)
160
(6.30)
160
(6.30)
192
(7.56)
W1
122
(4.80)
122
(4.80)
122
(4.80)
Dimensions mm (in)
335
(13.19)
435
(17.13)
435
(17.13)
535
(21.06)
535
(21.06)
535
(21.06)
680
(26.77)
248
(9.76)
284
(11.18)
284
(11.18)
335
(13.19)
H1
248
(9.76)
248
(9.76)
248
(9.76)
8
(0.31)
7.5
(0.30)
7.5
(0.30)
7.5
(0.30)
7.5
(0.30)
7.5
(0.30)
12.5
(0.49)
6
(0.24)
8
(0.31)
8
(0.31)
8
(0.31)
H2
6
(0.24)
6
(0.24)
6
(0.24)
78
(3.07)
100
(3.94)
100
(3.94)
110
(4.33)
110
(4.33)
110
(4.33)
130
(5.12)
55
(2.17)
75
(2.95)
75
(2.95)
78
(3.07)
D1
38
(1.50)
55
(2.17)
55
(2.17)
–
–
–
–
–
2.3
(0.09)
2.3
(0.09)
2.3
(0.09)
2.3
(0.09)
2.3
(0.09)
3.2
(0.13)
–
– t2
–
5
(0.20)
2.3
(0.09)
2.3
(0.09)
2.3
(0.09)
2.3
(0.09)
2.3
(0.09)
3.2
(0.13)
5
(0.20)
5
(0.20)
5
(0.20)
5
(0.20) t1
5
(0.20)
5
(0.20)
5
(0.20)
M6
M6
M10
M6
M6
M6
M6
M5
M5
M5
M6 d
M5
M5
M5
Wt. kg
(lb)
25
(55.1)
25
(55.1)
41
(90.4)
41
(90.4)
41
(90.4)
80.5
(177.5)
5.7
(12.6)
5.7
(12.6)
8.3
(18.3)
8.3
(18.3)
3.2
(7.1)
3.5
(7.7)
3.5
(7.7)
3.9
(8.6)
22 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 23 ページ 2015年11月11日 水曜日 午後7時40分
IP00 Enclosure Drive
W1
4-d t2
W1
2 Mechanical Installation
4-d t2
Max W2 W
W3
W1
W3
Max W2
Figure 1
6-d
D
D1 t1
Max W2 t2
W Max W2
Figure 2
D
D1 t1
YEA_common
Max W2 W Max W2
Figure 3
D
D1 t1
2
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 23
TOEP_C710616_38H_7_0.book 24 ページ 2015年11月11日 水曜日 午後7時40分
2 Mechanical Installation
Drive Model
CIMR-LU2
Figure
0215
0283
0346
0415
1
W
450
(17.72)
450
(17.72)
500
(19.69)
500
(19.69)
H
705
(27.76)
705
(27.76)
800
(31.50)
800
(31.50)
D
330
(12.99)
330
(12.99)
350
(13.78)
350
(13.78)
W1
325
(12.80)
325
(12.80)
370
(14.57)
370
(14.57)
Table 6 Dimensions: 200 V Class
Dimensions mm (in)
W2
10
(0.39)
10
(0.39)
10
(0.39)
10
(0.39)
W3
–
–
–
–
H1
680
(26.77)
680
(26.77)
773
(30.43)
773
(30.43)
H2
12.5
(0.49)
12.5
(0.49)
13
(0.51)
13
(0.51)
Drive Model
CIMR-LU4
Figure
0180
0216
0260
0304
0370
0450
0605
1
2
3
W
450
(17.72)
500
(19.69)
500
(19.69)
500
(19.69)
500
(19.69)
670
(26.38)
670
(26.38)
H
705
(27.76)
800
(31.50)
800
(31.50)
800
(31.50)
950
(37.40)
1140
(44.88)
1140
(44.88)
D
330
(12.99)
350
(13.78)
350
(13.78)
350
(13.78)
370
(14.57)
370
(14.57)
370
(14.57)
W1
325
(12.80)
370
(14.57)
370
(14.57)
370
(14.57)
370
(14.57)
440
(17.32)
440
(17.32)
Table 7 Dimensions: 400 V Class
Dimensions mm (in)
W2
10
(0.39)
10
(0.39)
10
(0.39)
W3
–
–
–
H1
680
(26.77)
773
(30.43)
773
(30.43)
H2
12.5
(0.49)
13
(0.51)
13
(0.51)
10
(0.39)
8
(0.31)
–
–
773
(30.43)
923
(36.34)
13
(0.51)
13
(0.51)
6
(0.24)
6
(0.24)
220
(8.66)
220
(8.66)
1110
(43.70)
1110
(43.70)
15
(0.59)
15
(0.59)
Table 8 Dimensions: 600 V Class
Drive Model
CIMR-LU5
Figure
0130
0172
0200
1
W
450
(17.72)
500
(19.69)
500
(19.69)
H
705
(27.76)
800
(31.50)
800
(31.50)
D
330
(12.99)
350
(13.78)
350
(13.78)
W1
325
(12.80)
370
(14.57)
370
(14.57)
Dimensions mm (in)
W2
10
(0.39)
10
(0.39)
10
(0.39)
W3
–
–
–
H1
680
(26.77)
773
(30.43)
773
(30.43)
H2
12.5
(0.49)
13
(0.51)
13
(0.51)
D1
130
(5.12)
130
(5.12)
130
(5.12)
130
(5.12) t1
3.2
(0.13)
3.2
(0.13)
4.5
(0.18)
4.5
(0.18) t2
3.2
(0.13)
3.2
(0.13)
4.5
(0.18)
4.5
(0.18)
D1
130
(5.12)
130
(5.12)
130
(5.12)
130
(5.12)
135
(5.31)
150
(5.91)
150
(5.91) t1
3.2
(0.13)
4.5
(0.18)
4.5
(0.18)
4.5
(0.18)
4.5
(0.18)
4.5
(0.18)
4.5
(0.18) t2
3.2
(0.13)
4.5
(0.18)
4.5
(0.18)
4.5
(0.18)
4.5
(0.18)
4.5
(0.18)
4.5
(0.18)
D1
130
(5.12)
130
(5.12)
130
(5.12) t1
3.2
(0.13)
4.5
(0.18)
4.5
(0.18) t2
3.2
(0.13)
4.5
(0.18)
4.5
(0.18) d
M10
M10
M12
M12
Wt. kg
(lb)
76
(167.6)
80
(176.4)
98
(216.1)
99
(218.3) d
M10
M12
M12
M12
M12
M12
M12
Wt. kg
(lb)
79
(174.2)
96
(211.6)
102
(224.9)
107
(235.9)
125
(275.6)
216
(476.2)
221
(487.2) d
M10
M12
M12
Wt. kg
(lb)
79
(174.2)
107
(235.9)
107
(235.9)
24 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 25 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
3 Electrical Installation
◆
Standard Connection Diagram
operator without connecting digital I/O wiring. This section does not discuss drive operation;
Programming & Operation on page 58
for instructions on operating the drive.
WARNING!
Sudden Movement Hazard. Ensure holding brake circuits are properly configured, load equipment may fall or drop during power loss or drive fault, which could result in death or serious injury.
・ Provide a separate holding brake if necessary.
・ Always construct the external sequence to confirm that the holding brake is activated in the event of an emergency, a power failure, or an abnormality in the drive.
・ When using the drive with an elevator, provide safety measures on the elevator to prevent the elevator from dropping.
NOTICE: Equipment Hazard. Separate motor and/or braking circuit wiring (terminals, U/T1, V/T2, W/T3, +3, +2, +1,(-), B1, B2, from all other wiring. Place motor wiring within its own conduit or cable tray with appropriate divider, and use shielded motor cable where appropriate. Improper wiring practices could result in malfunction of drive due to electrical interference.
NOTICE: Inadequate wiring could result in damage to the drive. Install adequate branch circuit short circuit protection per applicable codes. The drive is suitable for circuits capable of delivering not more than 100,000 RMS symmetrical amperes, 240 Vac maximum
(200 V class), 480 Vac maximum (400 V class), and 600 Vac maximum (600 V class).
NOTICE: When the input voltage is 440 V or higher or the wiring distance is greater than 100 meters (328 ft.), pay special attention to the motor insulation voltage or use a drive rated motor. Failure to comply could lead to motor insulation breakdown.
Note: Do not connect AC control circuit ground to drive enclosure. Improper drive grounding can cause control circuit malfunction.
NOTICE: The minimum load for the multi-function relay output MA-MB-MC is 10 mA. If a circuit requires less than 10 mA (reference value), connect it to a photocoupler output (P1-C1, P2-C2). Improper application of peripheral devices could result in damage to the photocoupler output of the drive.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 25
3
TOEP_C710616_38H_7_0.book 26 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
Figure 7
Wiring sequence should shut off power to the drive when a fault output is triggered.
<14>
Terminals -, +1, +2, B1, B2 are for connecting options. Never connect power supply lines to these terminals
DC link choke
(option)
<1>
Jumper
Thermal relay
(option)
<2><3>
Braking resistor
(option)
2 1
Main Circuit
− B 1 B 2
U/T 1
V/T 2
W/T 3
<2> r1 s1 t1
<4>
FU
FV
FW
U/T1
V/T2
W/T3
M
Cooling fan
M
YEA_common
Three-phase
ELCB (MCCB)
R power supply S
200 to 240 V
T
50 / 60 Hz
MC MB 2MCCB THRX OFF
Braking resistor unit
MC
Thermal relay trip contact
1 2
SA
TRX
2MCCB r1 s1 t1
ON
MC MA
TRX
MC
SA
THRX
SA
Multi-function analog inputs
MC
Fault relay contact
Multi-function digtial inputs
(default setting)
Up command / Stop
Down command / Stop
External Fault
Fault Reset
Multi-step Speed 1
Multi-step Speed 2
Multi-step Speed 3
Not Used
Sink / Source mode selection wire jumper
(default: Sink) <7>
2 k
Ω
MEMOBUS/Modbus comm. RS485/422 max. 115.2 kBps
Fuse
If running from a 400 V power supply or 600 V power supply, a step-down transformer is needed to reduce the voltage to 200 V.
R/L1
S/L2
T/L3
Ground
S 1
S 2
S 3
S 4
S 5
S 6
S 7
S 8
SN
SC
SP
+ 24 V
Drive
Control Circuit <5>
PG X3
<6>
Option card connector
CN5-C
IP12
IP5
IG
NC
SD
FE
CN3
TB2
IP
IG
SG a+ ab+ bz+ z-
CN5-B
CN5-A
MA
MB
MC
TB1
A+
A
B+
B
Z+
Z
M 1
M 2
Shield ground terminal
<8>
+ V Power supply +10.5 Vdc, max. 20 mA
A 1 Analog Input 1 (Speed Bias)
-10 to +10 Vdc (20 k Ω )
R
+
R
S
S
IG
A 2 Analog Input 2 (Not used)
-10 to +10 Vdc (20 k
Ω
)
AC
0 V
− V Power supply, -10.5 Vdc, max. 20 mA
<8>
Termination resistor
(120
Ω
, 1/2 W)
DIP
Switch S2
<9>
M 3
M 4
M 5
M 6
FM
AM
AC
PG
A pulse monitor signal
Fault relay output
250 Vac, max. 1 A
<13> <14>
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
Multi-function relay output (Brake Release Command)
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
Multi-function relay output (Motor Contactor Close Command)
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
Multi-function relay output (Drive Ready)
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
<15>
P1
C1
P2
Photo Coupler 1
(During Frequency Output)
C2
Photo Coupler 2
(not used)
Digital output
5 to 48 Vdc
2 to 50 mA
(default setting)
−
FM
+
Multi-function analog output 1
(Output Speed)
-10 to +10 Vdc (2mA) <12>
−
AM
+
Multi-function analog output 2
(Output Current)
-10 to +10 Vdc (2mA)
H 1
H 2
<10>
0 V
B pulse monitor signal
Z pulse monitor signal
E (G)
Safe Disable inputs
<11>
HC
DM
+
DM
EDM (Safety Electronic Device Monitor) shielded line twisted-pair shielded line control circuit terminal main circuit terminal
Figure 6 Drive Standard Connection Diagram (example: CIMR-LU2 0033)
<1> Remove the jumper when installing a DC link choke. Models CIMR-LU2 0085 through 2 0415, 4 0045 through 4 0605, and 5 0032 through 5 0200 come with a built-in DC link choke.
<2> Set L8-55 to 0 to disable the protection function of the built-in braking transistor of the drive when using an optional regenerative converter or dynamic braking option.
<3> Set up a thermal relay sequence to disconnect drive main power in the event of an overheat condition on the dynamic braking option.
<4> Self-cooling motors do not require the same wiring necessary for motors with separate cooling fans.
26 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 27 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
<5> Supplying power to the control circuit separately from the main circuit requires a 24 V power supply (option).
<6> For control modes that do not use a motor speed feedback signal, PG option card wiring is not necessary.
<7> This figure illustrates an example of a sequence input to S1 through S8 using a non-powered relay or an NPN transistor. Install the wire link between terminals SC-SP for Sink mode, between SC-SN for Source mode, or leave the link out for external power supply. Never short terminals SP and SN, as it will damage the drive.
<8> The maximum output current capacity for the +V and -V terminals on the control circuit is 20 mA. Never short terminals +V, -V, and AC, as it can cause erroneous operation or damage the drive.
<9> Set DIP switch S2 to the ON position to enable the termination resistor in the last drive in a MEMOBUS/
Modbus network.
<10>The sink/source setting for the Safe Disable input is the same as with the sequence input. Jumper S3 has the drive set for an external power supply. When not using the Safe Disable input feature, remove the jumper
Disable Inputs on page 55 for instructions.
<11> Disconnect the wire jumper between H1 - HC and H2 - HC when utilizing the Safe Disable input. Terminals
H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/
EN 61800-5-2, ISO/EN 13849 Cat.3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
<12>Monitor outputs work with devices such as analog frequency meters, ammeters, voltmeters, and wattmeters.
They are not intended for use as a feedback-type of signal.
<13>When the drive is set to trigger a fault output upon activation of the fault reset function (L5-02 = 1), a sequence to interrupt power when a fault occurs will shut off the power to the drive when the drive attempts a reset. The default setting for L5-02 is 0 (fault output not active during reset attempt).
<14>Wire fault contact outputs MA, MB, and MC. Wire so that a fault will open the safety circuit and interrupt drive output.
<15>When using the Programming Mode to edit parameter settings, L1000A will not accept an Up/Down command. If the drive still will not run when an Up/Down command has been entered and no fault is present, then use the "Drive ready" signal (the default setting for terminal M5-M6) to interlock components.
WARNING!
Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the correct state before energizing the drive. Failure to comply could result in death or serious injury from moving equipment.
NOTICE: When using the automatic fault reset function with wiring designed to shut off the power supply upon drive fault, make sure the drive does not trigger a fault output during fault reset (L5-02 = 0, default). Failure to comply will prevent the automatic fault reset function from working properly.
3
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 27
TOEP_C710616_38H_7_0.book 28 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
◆
Main Circuit Connection Diagram
when wiring the main circuit of the drive. Connections may vary based on drive capacity. The DC power supply for the main circuit also provides power to the control circuit.
NOTICE: Do not use the negative DC bus terminal “-” as a ground terminal. This terminal is at high DC voltage potential. Improper wiring connections could damage the drive.
NOTICE: Equipment Hazard. Separate motor and/or braking circuit wiring (terminals, U/T1, V/T2, W/T3, +3, +2, +1,(-), B1, B2, from all other wiring. Place motor wiring within its own conduit or cable tray with appropriate divider, and use shielded motor cable where appropriate. Improper wiring practices could result in malfunction of drive due to electrical interference.
CIMR-LU2 0008 to 2 0075
CIMR-LU4 0005 to 4 0039
CIMR-LU5 0003 to 5 0027
B1 B2
CIMR-LU2 0085, 2 0115
CIMR-LU4 0045, 4 0060
CIMR-LU5 0032, 5 0041
B1 B2
+1
+2
R/L1
S/L2
T/L3
–
Relay
+
Current sensor
U/T1
V/T2
W/T3
+1
DC link choke
Relay
R/L1
S/L2
T/L3
+
–
Current sensor
U/T1
V/T2
W/T3
YEA_co mmon
Gate board
Control board
Operator Gate board
Control board
Operator
CIMR-LU2 0145 to 2 0180
CIMR-LU4 0075 to 4 0112
CIMR-LU5 0052 to 5 0077
+3
+1
R/L1
S/L2
T/L3
DC link choke
Relay
–
+
Current sensor
U/T1
V/T2
W/T3
YEA_co mmon
Gate board
Control board
Operator
CIMR-LU2 0215 to 2 0415
CIMR-LU4 0150 to 4 0605
CIMR-LU5 0003 to 5 0200
CIMR-LU5 0099 to 5 0200
+3
+1
DC link choke
Relay
R/L1
S/L2
T/L3
–
+
Current sensor
24 V
Power
Supply
Gate board
Control board
Operator
U/T1
V/T2
W/T3
YEA_co mmon
Figure 7 Drive main circuit configurations
28 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 29 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
◆
Terminal Cover
Follow the procedure below to remove the terminal cover for wiring and to reattach the terminal cover after wiring is complete.
■
Removing/Reattaching the Terminal Cover
Removing the Terminal Cover
Models CIMR-LU2 0008 to 2 0075, 4 0005 to 4 0039, and 5 0003 to 5 0027
1.
Loosen the terminal cover screw using a #2 Phillips screwdriver. Screw sizes vary by drive model.
Figure 8
YEA_common
Figure 9
Figure 8 Removing the Terminal Cover
2.
Push in on the tab located on the bottom of the terminal cover and gently pull forward to remove the terminal cover.
YEA_common
Figure 9 Removing the Terminal Cover
Models CIMR- LU2 0085 to 2 0415, 4 0045 to 4 0605, and 5 0003 to 5 0027
1.
Loosen the screws on the terminal cover, then pull down on the cover.
CAUTION!
Do not completely remove the cover screws, just loosen them. If the cover screws are removed completely, the terminal cover may fall off causing an injury.
Figure 10
Note: The shape of the terminal covers and the numbers of screws differ depending on the drive models.
3
YEA_common
Figure 10 Removing the Terminal Cover
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 29
TOEP_C710616_38H_7_0.book 30 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
Figure 11
2.
Pull forward on the terminal cover to free it from the drive.
YEA_common
Figure 11 Removing the Terminal Cover
Reattaching the Terminal Cover
Models CIMR-LU2 0008 to 2 0075, 4 0005 to 4 0039, and 5 0003 to 5 0027
Power lines and signal wiring should pass through the opening provided.
Refer to Wiring the Main Circuit Terminal on page 46 and
Wiring the Control Circuit Terminal on page 51
for details on wiring.
NOTICE: Equipment Hazard. Separate motor and/or braking circuit wiring (terminals, U/T1, V/T2, W/T3, +3, +2, +1,(-), B1, B2, from all other wiring. Place motor wiring within its own conduit or cable tray with appropriate divider, and use shielded motor cable where appropriate. Improper wiring practices could result in malfunction of drive due to electrical interference.
Reattach the terminal cover after completing the wiring to the drive and other devices.
Figure 12
Connect ground wiring first, followed by the main circuit, and then wire the control circuit.
Power lines and signal wiring exit through the opening provided.
YEA_common
Figure 12 Reattaching the Terminal Cover
Models CIMR- LU2 0085 to 2 0415, 4 0045 to 4 0605, and 5 0003 to 5 0027
After wiring the terminal board and other devices, double-check connections and reattach the terminal cover.
Wiring the Main Circuit Terminal on page 46
and Wiring the Control Circuit Terminal on page 51
for details on wiring.
Figure 13
30
Connect ground wiring first, followed by the main circuit, and then wire the control circuit.
Figure 13 Reattaching the Terminal Cover
YEA_common
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 31 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
◆
Digital Operator and Front Cover
Detach the digital operator from the drive for remote operation or when opening the front cover to install an option card.
Note: Be sure to remove the digital operator prior to opening or reattaching the front cover. Leaving the digital operator plugged into the drive when removing the front cover can result in erroneous operation caused by a poor connection. Firmly fasten the front cover back into place before reattaching the digital operator.
■
Removing/Reattaching the Digital Operator
Removing the Digital Operator
While pressing on the tab located on the right side of the digital operator, pull the digital operator forward to remove it from the drive.
Figure 14
YEA_common
Figure 14 Removing the Digital Operator
Reattaching the Digital Operator
Insert the digital operator into the opening in the top cover while aligning it with the notches on the left side of the opening.
Next, press gently on the right side of the operator until it clicks into place.
Figure 15
YEA_common
Figure 15 Reattaching the Digital Operator
■
Removing/Reattaching the Front Cover
Removing the Front Cover
Models CIMR- LU2 0008 to 2 0075, 4 0005 to 4 0039, and 5 0003 to 5 0027
After removing the terminal cover and the digital operator, loosen the screw that affixes the front cover (model
CIMR-LU2 0047, 4 0024, 4 0031, 5 0017, and 5 0022 does not use a screw to affix the front cover). Pinch inwards on the tabs found on each side of the front cover, then pull forward to remove it from the drive.
Figure 16
3
YEA_common
Figure 16 Remove the Front Cover (Models CIMR-LU2 0008 to 2 0075, 4 0005 to 4 0039, and 5 0003 to 5 0027)
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 31
TOEP_C710616_38H_7_0.book 32 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
Models CIMR-LU2 0085 to 2 0415, 4 0045 to 4 0605, and 5 0032 to 5 0200
1.
Remove the terminal cover and the digital operator.
2.
Loosen the installation screw on the front cover.
3.
Use a straight-edge screwdriver to loosen the hooks on each side of the cover that hold it in place.
Figure 17
Hook
Front cover installation screw
Hook
Free hooks on both sides of the cover
Figure 18
Figure 17 Remove the Front Cover
(Models CIMR-LU2 0085 to 2 0415, 4 0045 to 4 0605, and 5 0032 to 5 0200)
4.
Unhook the left side of the front cover then swing the left side towards you as shown in
until the cover comes off.
Figure 18 Remove the Front Cover
(Models CIMR-LU2 0085 to 2 0415, 4 0045 to 4 0605, and 5 0032 to 5 0200)
Reattaching the Front Cover
Models CIMR-LU2 0008 to 2 0075, 4 0005 to 4 0039, and 5 0003 to 5 0027
front cover while guiding it back into the drive. Make sure it clicks firmly into place.
32 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 33 ページ 2015年11月11日 水曜日 午後7時40分
Models CIMR-LU2 0085 to 2 0415, 4 0045 to 4 0605, and 5 0032 to 5 0200
1.
Slide the front cover so the hooks on the top connect to the drive.
Figure 19
3 Electrical Installation
Figure 19 Reattach the Front Cover
(Models CIMR- LU2 0085 to 2 0415, 4 0045 to 4 0605, and 5 0032 to 5 0200)
2.
After connecting the hooks to the drive, press firmly on the cover to lock it into place.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 33
3
TOEP_C710616_38H_7_0.book 34 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
◆
Main Circuit Wiring
This section describes the functions, specifications, and procedures required to safely and properly wire the main circuit in the drive.
NOTICE: Only connect recommended devices to the drives braking transistor terminals. Failure to comply could result in damage to the drive or braking circuit. Carefully review instruction manual TOBP C720600 0 when connecting a braking option to the drive.
NOTICE: Do not use the negative DC bus terminal “-” as a ground terminal. This terminal is at high DC voltage potential.
Improper wiring connections could damage the drive.
NOTICE: Equipment Hazard. Separate motor and/or braking circuit wiring (terminals, U/T1, V/T2, W/T3, +3, +2, +1,(-), B1, B2, from all other wiring. Place motor wiring within its own conduit or cable tray with appropriate divider, and use shielded motor cable where appropriate. Improper wiring practices could result in malfunction of drive due to electrical interference.
NOTICE: Equipment Hazard. Comply with proper wiring practices. The motor may run in reverse if the phase order is backward, causing incorrect elevator direction movement. Connect motor input terminals U, V and W to drive output terminals U/T1,V/T2, and W/
T3. The phase order for the drive and motor should match.
NOTICE: Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen over time. Improper wiring practices could result in drive malfunction due to loose terminal connections.
NOTICE: Do not switch the drive input to start or stop the motor. Frequently switching the drive on and off shortens the life of the DC bus charge circuit and the DC bus capacitors, and can cause premature drive failures. For the full performance life, refrain from switching the drive on and off more than once every 30 minutes.
■
Main Circuit Terminal Functions
Table 9 Main Circuit Terminal Functions
Terminal
200 V
Class
400 V
Class
Model
CIMR-L
U
600 V
Class
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
B1
B2
+2
+1
–
+3
2
4
5
0008 to 2
0005 to 4
0003 to 5
0075
0039
0027
2
4
5
0085, 2
0045, 4
0032, 5
Main circuit power supply input
Drive output
Braking resistor
Type
0115
0060
0041
2
4
5
0145 to 2
0075 to 4
0052 to 5
0415
0605
0200
Not available
• DC reactor connection
(+1, +2) (remove the shorting bar between
+1 and +2)
• DC power supply input
(+1, –)
(+1, –)
Not available
For 200 V class: 100 Ω or less
For 400 V class: 10 Ω or less
For 600 V class: 10 Ω or less
Not available
DC power supply input
• DC power supply input (+1, –)
• Braking unit connection (+3, –)
Function
Connects line power to the drive
Connects to the motor
Available for connecting a braking resistor or a braking resistor unit option
For connection
• of the drive to a DC power supply
(terminals +1 and – are not UL approved)
• of dynamic braking options
Grounding terminal
Note: Use terminal B1 and - terminals when installing the braking unit (CDBR type) to the drives with built-in braking transistor
(2 0008 to 2 0115, 4 0005 to 4 0060, and 5 0003 to 5 0041).
Page
–
–
34 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 35 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
■
Protecting Main Circuit Terminals
Insulation Cap or Sleeves
Use insulation caps or sleeves when wiring the drive with crimp terminals. Take particular care to ensure that the wiring does not touch nearby terminals or the surrounding case.
Insulation Barrier
Insulation barriers are packaged with drive models CIMR-LU4A0370 through 4A0605 to provide added protection between terminals. Yaskawa recommends using the provided insulation barriers to ensure proper wiring. Refer to
for instructions on placement of the insulation barriers.
Figure 20
YEA_common
Insulation Barrier
Figure 20 Installing Insulation Barriers
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 35
3
TOEP_C710616_38H_7_0.book 36 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
■
Wire Gauges and Tightening Torque
Use the tables in this section to select the appropriate wires and crimp terminals.
Gauges listed in the tables are for use in the United States.
Note: 1.
Wire gauge recommendations based on drive continuous current ratings using 75°C (167°F) 600 Vac vinyl-sheathed wire assuming ambient temperature within 40°C (104°F) and wiring distance less than 100 m (328 ft.).
2.
Terminals B1, B2, -, +1, +2, and +3, are for connecting a DC link choke, braking resistor or DC power supply. Do not connect other nonspecific devices to these terminals.
• Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is greater than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following formula to calculate the amount of voltage drop:
Line drop voltage (V) = 3 × wire resistance ( Ω /km) × wire length (m) × current (A) × 10 -3
• Refer to instruction manual TOBP C720600 0 for braking transistor option or braking resistor option wire gauges.
• Use terminal +1 and the negative terminal when connecting a regenerative converter or a regen unit.
• Use terminal B1 and - terminals when installing the braking unit to the drives with built-in braking transistor (2 0008 to 2 0115, 4 0005 to 4 0060, and 5 0003 to 5 0041).
•
Refer to UL Standards Compliance on page 224
for information on UL compliance.
Yaskawa recommends using closed-loop crimp terminals on all drive models. UL/cUL approval requires the use of closed-loop crimp terminals when wiring the drive main circuit terminals on models CIMR-LU2 0085 to 2 0415 and
4 0045 to 4
0260. Use only the tools recommended by the terminal manufacturer for crimping. Refer to Closed-Loop
Crimp Terminal Size on page 231
for closed-loop crimp terminal recommendations.
The wire gauges listed in the following tables are Yaskawa recommendations. Refer to local codes for proper wire gauge selections.
36 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 37 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
Three-Phase 200 V Class
Table 10 Wire Gauge and Torque Specifications (Three-Phase 200 V Class)
Model
CIMR-LU
2 0008
2 0011
2 0014
2 0018
2 0025
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
Recomm. Gauge
AWG, kcmil
14
14
–
–
10
–
–
12
14
10
–
–
10
10
10
10
8
8
–
–
–
–
10
10
Wire Range
AWG, kcmil
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
12 to 10
14 to 10
14 to 10
14 to 10
14 to 10
18 to 10
18 to 10
12 to 10
14 to 10
12 to 10
12 to 6
12 to 6
10 to 6
12 to 10
Screw
Size
M4
M4
M4
M4
M4
Tightening Torque
N m (lb.in.)
1.2 to 1.5
(10.6 to 13.3)
1.2 to 1.5
(10.6 to 13.3)
1.2 to 1.5
(10.6 to 13.3)
1.2 to 1.5
(10.6 to 13.3)
2.1 to 2.3
(18.6 to 20.4)
10 to 8 M5
2.0 to 2.5
(17.7 to 22.1)
2 0033
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
6
8
–
–
12 to 6
12 to 6
6
12 to 10
M4
2.1 to 2.3
(18.6 to 20.4)
8 10 to 8 M5
2.0 to 2.5
(17.7 to 22.1)
2 0047
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
4
4
–
–
6
6 to 4
6 to 4
6 to 4
10 to 6
8 to 6
M6
M5
M6
5.4 to 6.0
(47.8 to 53.1)
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
(47.8 to 53.1)
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
3
3
–
10 to 2
10 to 2
4 to 3
M8
9.9 to 11.0
(87.6 to 97.4)
2 0060
B1, B2 –
6
8 to 6
6 to 4
M5
M6
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
(47.8 to 53.1)
3
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 37
TOEP_C710616_38H_7_0.book 38 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
Model
CIMR-LU
2 0075
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
2 0085
2 0115
2 0145
2 0180
2 0215
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
2 0283
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
2 0346
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
Wire Range
AWG, kcmil
10 to 2
10 to 2
3 to 2
6
4
1/0 to 4/0
1/0 to 4/0
1 to 4/0
1/0 to 4/0
4 to 2
1/0 to 4/0
1/0 to 4/0
1 to 4/0
1/0 to 4/0
4 to 1/0
6 to 4
10 to 1/0
10 to 1/0
2 to 1/0
6 to 1/0
6 to 4
10 to 3/0
10 to 3/0
1/0 to 3/0
4 to 2/0
3/0 to 300
3/0 to 300
3/0 to 300
2 to 300
3 to 300
3/0 to 300
3/0 to 300
3/0 to 300
3/0 to 300
2 to 300
4/0 to 600
4/0 to 600
250 to 600
3/0 to 600
1 to 350
Recomm. Gauge
AWG, kcmil
2
2
–
–
4
4/0
4/0
–
–
4
1/0 × 2P
1/0 × 2P
–
–
6
1/0
1/0
–
–
6
2/0
2/0
–
–
4
2/0 × 2P
2/0 × 2P
–
–
3
3/0 × 2P
3/0 × 2P
–
–
2
250 × 2P
4/0 × 2P
–
–
1
Screw
Size
M8
M5
M6
Tightening Torque
N m (lb.in.)
9.9 to 11.0
(87.6 to 97.4)
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
(47.8 to 53.1)
M8
9 to 11
(79.7 to 97.4)
M10
M8
M10
M10
M12
M10
M12
M12
M10
M12
M12
M10
M12
18 to 23
(159 to 204)
9 to 11
(79.7 to 97.4)
18 to 23
(159 to 204)
9 to 11
(79.7 to 97.4)
18 to 23
(159 to 204)
9 to 11
(79.7 to 97.4)
32 to 40
(283 to 354)
18 to 23
(159 to 204)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
18 to 23
(159 to 204)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
18 to 23
(159 to 204)
32 to 40
(283 to 354)
38 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 39 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
Model
CIMR-LU
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
Recomm. Gauge
AWG, kcmil
350 × 2P
300 × 2P
–
–
Wire Range
AWG, kcmil
250 to 600
300 to 600
300 to 600
3/0 to 600
Screw
Size
M12
Tightening Torque
N m (lb.in.)
32 to 40
(283 to 354)
2 0415
1 1 to 350
M10
M12
18 to 23
(159 to 204)
32 to 40
(283 to 354)
<1> When using the wire of this gauge in accordance with IEC/EN 61800-5-1, install an ELCB.
<2> When using the wire of this gauge in accordance with IEC/EN 61800-5-1, install an ELCB, or use copper wire of 10 mm 2 (AWG 8).
Note: When connecting peripheral devices and options to the terminals –, +1, +3, B1, and B2, refer to the instruction manuals for each device. For more information, contact Yaskawa or your nearest sales representative.
Three-Phase 400 V Class
Table 11 Wire Gauge and Torque Specifications (Three-Phase 400 V Class)
Model
CIMR-LU
Screw
Size
Tightening Torque
N m (lb.in.)
4 0005
4 0006
4 0007
4 0009
4 0015
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
Recomm. Gauge
AWG, kcmil
14
14
–
–
10
12
14
–
–
10
10
10
–
–
10
Wire Range
AWG, kcmil
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
18 to 10
18 to 10
14 to 10
14 to 10
14 to 10
12 to 6
12 to 6
12 to 6
12 to 10
14 to 10
M4
M4
M4
M5
1.2 to 1.5
(10.6 to 13.3)
1.2 to 1.5
(10.6 to 13.3)
2.1 to 2.3
(18.6 to 20.4)
2.0 to 2.5
(17.7 to 22.1)
4 0018
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
10
10
–
–
10
12 to 6
12 to 6
12 to 6
12 to 10
12 to 10
M4
M5
2.1 to 2.3
(18.6 to 20.4)
2.0 to 2.5
(17.7 to 22.1)
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
8
8
–
10 to 6
10 to 6
10 to 6
M5
3.6 to 4.0
(31.8 to 35.4)
4 0024
B1, B2 –
10 to 8
10 to 8
M5
M6
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
(47.8 to 53.1)
4 0031
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
6
8
–
–
6
10 to 6
10 to 6
6
10 to 8
10 to 6
M5
M5
M6
3.6 to 4.0
(31.8 to 35.4)
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
(47.8 to 53.1)
3
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 39
TOEP_C710616_38H_7_0.book 40 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
Model
CIMR-LU
4 0039
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
4 0045
4 0060
4 0075
4 0091
4 0112
4 0150
4 0180
4 0216
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
Wire Range
AWG, kcmil
6 to 4
6 to 4
6 to 4
10 to 8
8 to 6
6 to 250
6 to 250
3 to 1/0
4 to 1/0
6 to 4
1/0 to 4/0
1/0 to 4/0
1/0 to 4/0
3 to 4/0
4
1/0 to 4/0
1/0 to 4/0
1 to 4/0
1/0 to 4/0
4 to 2
2 to 300
2 to 300
1 to 250
10 to 1/0
10 to 1/0
6 to 1
8 to 4
8 to 6
10 to 3/0
10 to 3/0
4 to 1
6 to 3
6
6 to 250
6 to 250
3 to 1/0
6 to 1/0
6 to 4
3 to 3/0
4 to 300
1 to 600
1/0 to 600
3/0 to 600
1 to 325
2 to 350
Recomm. Gauge
AWG, kcmil
6
6
–
–
6
4
4/0
4/0
–
–
4
1 × 2P
1 × 2P
–
–
4
2/0 × 2P
2/0 × 2P
–
–
2
4
3/0
2/0
–
–
1/0
1
–
–
–
–
2
2
4
–
–
6
3
3
–
6
4
4
–
Screw
Size
M6
M5
M6
Tightening Torque
N m (lb.in.)
5.4 to 6.0
(47.8 to 53.1)
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
(47.8 to 53.1)
M8
9 to 11
(79.7 to 97.4)
M8
M8
M8
M10
M10
M10
M10
9 to 11
(79.7 to 97.4)
9 to 11
(79.7 to 97.4)
9 to 11
(79.7 to 97.4)
18 to 23
(159 to 204)
18 to 23
(159 to 204)
18 to 23
(159 to 204)
18 to 23
(159 to 204)
40 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 41 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
Model
CIMR-LU
4 0260
4 0304
4 0370
4 0450
4 0605
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
Recomm. Gauge
AWG, kcmil
3/0 × 2P
3/0 × 2P
–
–
2
4/0 × 2P
4/0 × 2P
–
–
1
300 × 2P
300 × 2P
–
–
1
3/0 × 4P
3/0 × 4P
–
–
1/0
300 × 4P
300 × 4P
–
–
2/0
Wire Range
AWG, kcmil
2/0 to 600
2/0 to 600
3/0 to 600
1 to 325
2 to 350
3/0 to 600
3/0 to 600
4/0 to 600
3/0 to 600
1 to 350
4/0 to 300
4/0 to 300
3/0 to 300
3/0 to 300
1 to 3/0
3/0 to 300
3/0 to 300
1/0 to 300
1/0 to 300
1/0 to 300
4/0 to 300
4/0 to 300
1/0 to 300
1/0 to 300
2/0 to 300
Screw
Size
M12
M10
M12
M12
M10
M12
M12
M12
M12
Tightening Torque
N m (lb.in.)
32 to 40
(283 to 354)
18 to 23
(159 to 204)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
18 to 23
(159 to 204)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
<1> When using the wire of this gauge in accordance with IEC/EN 61800-5-1, install an ELCB.
<2> When using the wire of this gauge in accordance with IEC/EN 61800-5-1, install an ELCB, or use copper wire of 10 mm 2 (AWG 8).
Note: When connecting peripheral devices and options to the terminals –, +1, +3, B1, and B2, refer to the instruction manuals for each device. For more information, contact Yaskawa or your nearest sales representative.
Table 12 Wire Gauge and Torque Specifications (Three-Phase 600 V Class)
Model
CIMR-LU
5 0003
5 0004
5 0006
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
Recomm. Gauge
AWG, kcmil
14
14
10
14
–
–
14
–
–
10
Wire Range
AWG, kcmil
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
12 to 10
Screw
Size
M4
M4
Tightening Torque
N m (lb.in.)
1.2 to 1.5
(10.6 to 13.3)
1.2 to 1.5
(10.6 to 13.3)
3
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 41
TOEP_C710616_38H_7_0.book 42 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
Model
CIMR-LU
5 00010
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
5 0013
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
5 0017
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
5 0022
5 0027
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
5 0032
5 0041
5 0052
5 0062
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
12 to 8
10 to 6
10 to 6
10 to 6
10 to 8
10 to 8
6 to 4
6 to 4
6 to 4
10 to 8
10 to 6
10 to 4/0
10 to 4/0
4 to 4/0
6 to 4/0
4
10 to 4/0
10 to 4/0
3 to 4/0
6 to 4/0
4
10 to 3
10 to 3
6 to 1
12 to 3
6
10 to 3
10 to 3
6 to 1
8 to 3
6
Wire Range
AWG, kcmil
14 to 6
14 to 6
14 to 6
14 to 10
12 to 8
10 to 6
10 to 6
10 to 6
10 to 8
8
8
10
–
–
8
6
6
–
–
6
–
–
3
3
4
–
–
4
4
4
–
–
4
6
6
–
–
6
6
6
Recomm. Gauge
AWG, kcmil
10
14
–
–
8
10
10
–
–
M6
M6
M5
M6
Screw
Size
M4
M5
M5
M6
M5
Tightening Torque
N m (lb.in.)
2.1 to 2.3
(18.6 to 20.4)
2.0 to 2.5
(17.7 to 22.1)
3.6 to 4.0
(31.8 to 35.4)
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
(47.8 to 53.1)
3.6 to 4.0
(31.8 to 35.4)
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
(47.8 to 53.1)
5.4 to 6.0
(47.8 to 53.1)
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
(47.8 to 53.1)
M8
9 to 11
(79.7 to 97.4)
M8
M10
M10
9 to 11
(79.7 to 97.4)
18 to 23
(159 to 204)
18 to 23
(159 to 204)
42 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 43 ページ 2015年11月11日 水曜日 午後7時40分
Model
CIMR-LU
5
5
5
5
0077
0099
0130
0172
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
5 0200
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
Recomm. Gauge
AWG, kcmil
1/0
1
–
–
3
3/0
3/0
–
4
2/0
2/0
–
–
–
3
300
250
–
–
1
400
350
–
–
1
Wire Range
AWG, kcmil
10 to 4/0
10 to 4/0
2 to 4/0
4 to 4/0
4
1 to 300
1 to 300
2/0 to 3/0
1 to 1/0
4 to 300
2/0 to 300
2/0 to 300
3/0 to 4/0
1/0 to 2/0
4 to 300
2/0 to 600
2/0 to 600
2/0 to 400
2/0 to 250
1 to 350
2/0 to 600
2/0 to 600
2/0 to 500
250 to 300
1 to 350
M10
M10
M12
M10
M12
M12
M10
M12
3 Electrical Installation
Screw
Size
Tightening Torque
N m (lb.in.)
M10
18 to 23
(159 to 204)
18 to 23
(159 to 204)
18 to 23
(159 to 204)
32 to 40
(283 to 354)
18 to 23
(159 to 204)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
18 to 23
(159 to 204)
32 to 40
(283 to 354)
3
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 43
TOEP_C710616_38H_7_0.book 44 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
■
Main Circuit Terminal and Motor Wiring
This section outlines the various steps, precautions, and checkpoints for wiring the main circuit terminals and motor terminals.
WARNING!
Electrical Shock Hazard. Before servicing, disconnect all power to the equipment and lock out the power source. Failure to comply may result in injury from electrical shock. Wait at least five minutes after all indicators are OFF and measure the DC bus voltage level and main circuit terminals to confirm the circuit is safe before wiring.
WARNING!
Electrical Shock Hazard. Verify motor wiring bare wire ends do not contact the drive chassis or enclosure when wiring drive terminals U/T1, V/T2, W/T3. Failure to comply may result in serious injury or death due to electrical shock.
WARNING!
Electrical Shock Hazard. Improper equipment grounding could result in death or serious injury by contacting the motor case. Always properly ground the motor-side grounding terminal.
WARNING!
Fire Hazard. Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections. Improperly tightened terminal screws can also cause erroneous equipment operation.
WARNING!
Fire Hazard. Do not use an improper voltage source. Failure to comply could result in death or serious injury by fire. Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.
WARNING!
Do not connect the AC power line to the output motor terminals of the drive. Failure to comply could result in death or serious injury by fire as a result of drive damage from line voltage application to output terminals.
NOTICE: Equipment Hazard. Separate motor and/or braking circuit wiring (terminals, U/T1, V/T2, W/T3, +3, +2, +1,(-), B1, B2, from all other wiring. Place motor wiring within its own conduit or cable tray with appropriate divider, and use shielded motor cable where appropriate. Improper wiring practices could result in malfunction of drive due to electrical interference.
NOTICE: Equipment Hazard. Comply with proper wiring practices. The motor may run in reverse if the phase order is backward, causing incorrect elevator direction movement and injury to personnel. Connect motor input terminals U/T1, V/T2, and W/T3 to drive output terminals U/T1,V/T2, and W/T3. The phase order for the drive and motor should match.
NOTICE: Equipment Hazard. Improper equipment sequencing could shorten useful life of the electrolytic capacitors and circuit relays of the drive. Refrain from switching an input contactor more often than once every 30 minutes. Normally the drive I/O should be used to stop and start the motor.
NOTICE: Equipment Hazard. Standard motors used with PWM drives may experience winding failures due to surge voltages, when input line voltage is greater than 480 V or motor wire distance is greater than 100 meters. Select a motor design with insulation tolerant of surge voltages and drive-rated motor for use with PWM drives. Failure to comply could lead to motor winding failure.
NOTICE: Do not use the negative DC bus terminal "-" as a ground terminal. This terminal is at high DC voltage potential. Improper wiring connections could damage the drive.
NOTICE: Improper application of devices on drive output circuits can damage the drive. Do not connect unapproved LC or RC interference suppression filters, capacitors, ground fault circuits, or overvoltage protection devices to the output of the drive.
NOTICE: Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Failure to comply could result in damage to the drive, phase-advancing capacitors, LC/RC noise filters or ground fault circuit interrupters.
NOTICE: Properly integrate auxiliary contacts into the control logic circuit to avoid unnecessary fault displays caused by contactors or output switches placed between drive and motor. Improper installation of input and output contactors could result in damage to the drive.
NOTICE: Before applying power to the drive, use power-off resistance checks to check for short-circuits between (R/L1, S/L2, and
T/L3) or between main circuit terminals and ground. Failure to comply may result in damage to the drive.
44 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 45 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
Cable Length Between Drive and Motor
Voltage drop along the motor cable may cause reduced motor torque when the wiring between the drive and the motor is too long, especially at low frequency output. This can also be a problem when motors are connected in parallel with a fairly long motor cable. Drive output current will increase as the leakage current from the cable increases. An increase in leakage current may trigger an overcurrent situation and weaken the accuracy of the current detection.
Adjust the drive carrier frequency according to
. If the motor wiring distance exceeds 100 m (328 ft.) because of
the system configuration, reduce the ground currents. Refer to C6: Carrier Frequency on page 172
.
NOTICE: Equipment Hazard. Separate motor and/or braking circuit wiring (terminals, U/T1, V/T2, W/T3, +3, +2, +1,(-), B1, B2, from all other wiring. Place motor wiring within its own conduit or cable tray with appropriate divider, and use shielded motor cable where appropriate. Improper wiring practices could result in malfunction of drive due to electrical interference.
Table 13 Cable Length Between Drive and Motor
Cable Length
Carrier Frequency
50 m (164 ft.) or less
15 kHz or less
100 m (328 ft.) or less
5 kHz or less
Greater than 100 m (328 ft.)
2 kHz or less
Note: When setting carrier frequency for drives running multiple motors, calculate cable length as the total wiring distance to all connected motors.
Ground Wiring
Follow the precautions to wire the ground for one drive or a series of drives.
WARNING!
When using an EMC filter, the leakage current exceeds 3.5 mA. Therefore, according to IEC/EN 61800-5-1, at least one of the conditions below must be satisfied: a) The cross-section of the protective earthing conductor must be at least 10 mm 2 (Cu) or 16 mm 2 (Al).
b) The power supply must be disconnected automatically in case of discontinuity of the protective earthing conductor.
WARNING!
Electrical Shock Hazard. Always use a ground wire that complies with technical standards on electrical equipment and local installation regulations. Minimize the length of the ground wire. Improper equipment grounding may cause dangerous electrical potentials on equipment chassis, which could result in death or serious injury.
WARNING!
Electrical Shock Hazard. Be sure to ground the drive ground terminal (200 V class: Ground to 100
Ground to 10 Ω or less, and 600 V class: ground to 10 Ω
Ω or less, 400 V class:
or less). Improper equipment grounding may cause dangerous electrical potentials on equipment chassis, which could result in death or serious injury.
NOTICE: Do not share the ground wire with other devices such as welding machines or large-current electrical equipment. Improper equipment grounding could result in drive or equipment malfunction due to electrical interference.
NOTICE: When using more than one drive, ground multiple drives according to instructions. Improper equipment grounding could result in abnormal operation of drive or equipment.
Refer to Figure 21 when using multiple drives. Do not loop the ground wire.
Figure 21
OK OK Not OK
3
Figure 21 Multiple Drive Wiring
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 45
TOEP_C710616_38H_7_0.book 46 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
Wiring the Main Circuit Terminal
WARNING!
Electrical Shock Hazard. Shut off the power supply to the drive before wiring the main circuit terminals. Failure to comply may result in death or serious injury.
Wire the main circuit terminals after the terminal board has been properly grounded.
Models CIMR-LU2 0008 to 2 0075, 4 0005 to 4 0039, and 5 0003 to 5 0027 have a cover placed over the DC bus and braking circuit terminals prior to shipment to help prevent miswiring. Use wire cutters to cut away covers as needed for terminals.
Figure 22
A
A – Protecting Cover
Figure 22 Protecting Cover to Prevent Miswiring (CIMR-LU2 0047)
Main Circuit Connection Diagram
WARNING!
Fire Hazard. The braking resistor connection terminals are B1 and B2. Do not connect braking resistors to any other terminals. Improper wiring connections could cause the braking resistor to overheat and cause death or serious injury by fire. Failure to comply may result in damage to the braking circuit or drive.
Refer to Standard Connection Diagram on page 25 when wiring the drive control circuit terminals.
■
Control Circuit Terminal Block Functions
Drive parameters determine which functions apply to the multi-function digital inputs (S3 to S8), multi-function digital outputs (M1 to M6), multi-function photocoupler outputs (P1-C1, P2-C2), multi-function analog inputs (A1, A2), and
NOTICE: Equipment Hazard. Improper equipment sequencing could shorten useful life of the electrolytic capacitors and circuit relays of the drive. Refrain from switching an input contactor more often than once every 30 minutes. Normally the drive I/O should be used to stop and start the motor.
WARNING!
Sudden Movement Hazard. Always check the operation and wiring of control circuits after being wired. Operating a drive with untested control circuits could result in death or serious injury.
WARNING!
Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before starting test run. Failure to comply may result in death or serious injury.
NOTICE: Frequently switching the drive power supply to stop and start the motor can damage the drive.
NOTICE: To get the full performance life out of the electrolytic capacitors and circuit relays, refrain from switching the drive power supply off and on more than once every 30 minutes. Frequent use can damage the drive. Use the drive to stop and start the motor.
Note: Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen over time. Improper wiring practices could result in drive malfunction due to loose terminal connections.
46 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 47 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
Input Terminals
lists the input terminals on the drive. Text in parenthesis indicates the default setting for each multi-function input.
Table 14 Control Circuit Input Terminals
Type
Digital Inputs
Digital Input
Power Supply
Safe Disable
Analog Inputs
No.
Terminal Name (Function)
S1 Up Command (Closed: Up, Open: Stop)
S2 Down Command (Closed: Down, Open: Stop)
S3 Multi-function input 1 (External Fault)
S4 Multi-function input 2 (Fault Reset)
S5
Multi-function input 3 (Multi-Step Speed
Reference 1)
S6
S7
Multi-function input 4 (Multi-Step Speed
Reference 2)
Multi-function input 5 (Multi-Step Speed
Reference 3)
S8 Multi-function input 6 (Not used)
SC Multi-function input common
SN 0 V
SP +24 Vdc
H1
H2
HC
+V
Safe Disable function common
Power supply for analog inputs
-V Power supply for analog inputs
A1
Multi-function analog input 1 (Speed reference bias)
A2 Multi-function analog input 2 (Not used)
AC Analog input common
E (G) Ground for shielded lines and option cards
Function (Signal Level) Default Setting
Photocoupler
24 Vdc, 8 mA
Use the wire link between terminals SC and SN or between SC and SP to select sinking or sourcing, and to select the power supply.
24 Vdc, 150 mA (only when DI-A3 is not used)
Use the wire jumper between terminals SC and SN or between SC and SP to select sinking or sourcing, and to select the power supply.
24 Vdc, 8 mA
One or both open: Drive output disabled
Both closed: Normal operation
Internal impedance: 3.3 k Ω
Off time of at least 1 ms
Set the S3 jumper to select sinking or sourcing, and to select the power supply.
Common for the Safe Disable function
10.5 Vdc (max allowable current 20 mA)
-10.5 Vdc (max allowable current 20 mA)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 k
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 k
0 V
–
Ω
Ω )
)
Page
–
–
–
–
–
<1> Setting jumper S3 for an external power supply makes the wire jumper between terminals H1, H2, and HC ineffective. Remove the wire jumper and connect an external power supply that can supply terminals H1, H2, and HC continuously.
<2> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN 61800-5-2, ISO/EN
13849 Cat.3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
3
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 47
TOEP_C710616_38H_7_0.book 48 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
Output Terminals
WARNING!
Sudden Movement Hazard. The logic of terminals DM+/DM- is inverted between drive models CIMR-L A and
CIMR-L F . Check all wiring to ensure that the sequence is correct after installing the drive and connecting any other devices.
Improper wiring connections could result in death or serious injury.
output.
Note: Multi-function relay output terminals are rated at a minimum of 10 mA. If less than 10 mA is required, use the photocoupler outputs (P1-C1, P2-C2). Using the wrong current output level may cause the output to malfunction when the terminal is activated.
Table 15 Control Circuit Output Terminals
Type Function (Signal Level) Default Setting
Fault Relay
Multi-Functio n Relay
Output
Multi-Functio n
Photocoupler
Output
Monitor
Output
Safety
Monitor
Output
No.
Terminal Name (Function)
MA N.O.
MB N.C. output
MC Fault output common
M1
M2
Multi-function relay output 1 (Brake release command)
M3 Multi-function relay output 2 (Output contactor close
M4 command)
M5
M6
Multi-function relay output 3 (Drive ready)
P1
Photocoupler output 1 (During Frequency output)
C1
P2
Photocoupler output 2 (Not Used/Through Mode)
C2
FM Analog monitor output 1 (Output speed)
AM Analog monitor output 2 (Output current)
AC Monitor common
DM+ Safety monitor output
DM- Safety monitor output common
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
Contact relay output
30 Vdc, 10 mA to 1 A
250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
-10 to +10 Vdc or 0 to +10 Vdc
0 V
Outputs status of Safe Disable function. Up to +48 Vdc 50 mA
<1> Refrain from assigning functions to terminals M1 thru M6 that involve frequent switching, as doing so may shorten relay performance life.
Switching life is estimated at 200,000 times (assumes 1 A, resistive load).
<2> Connect a suppression diode as shown in
the circuit voltage.
<3> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN 61800-5-2, ISO/EN
13849 Cat.3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
Figure 23
B
A
C
D
YEA_common
A – External power, 48 V max.
B – Suppression diode
C – Coil
D – 50 mA or less
Figure 23 Connecting a Suppression Diode
48 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 49 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
Serial Communication Terminals
Table 16 Control Circuit Terminals: Serial Communications
Type
MEMOBUS/Modbus
Communication
No.
R+
R-
S+
S-
IG
Signal Name
Communications input (+)
Communications input (-)
Communications output (+)
Communications output (-)
Shield ground
MEMOBUS/Modbus communication: Use an RS-485 or RS-422 cable to connect the drive.
Function (Signal Level)
RS-485/422
MEMOBUS/Modbus communication protocol
115.2 kbps (max.)
0 V
<1> Enable the termination resistor in the last drive in a MEMOBUS network by setting DIP switch S2 to the ON position.
■
Terminal Configuration
Control circuit terminals are arranged as shown in Figure 24
.
Figure 24
YEA_common
E
E(G) HC H1 H2 DM+ DM- IG R+ RS+ S-
D
V+ AC VA1 A2 FM AM AC P1 C1 P2 C2
C
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
A
M3 M4 M6
M1 M2 M5
MA MB MC
B
A – Terminal Block (TB 2)
B – Terminal Block (TB 5)
C – Terminal Block (TB 1)
D – Terminal Block (TB 3)
E – Terminal Block (TB 4)
Figure 24 Control Circuit Terminal Arrangement
3
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 49
TOEP_C710616_38H_7_0.book 50 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
Wire Size and Torque Specifications
WARNING!
Fire hazard. Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections. Improperly tightened terminal screws can also cause erroneous equipment operation.
Select appropriate wire type and gauges from
. For simpler and more reliable wiring, use crimp ferrules on the wire ends. Refer to
for ferrule terminal types and sizes.
Terminal
Block
Terminal
TB1, TB2
TB3, TB4
FM, AC, AM, P1,
P2, PC, SC, A1,
A2, A3, +V, -V, S1 to S8, MA, MB,
MC, M1, M2, HC,
H1, H2, DM+,
DM-, IG,
R+, R-, S+, S-,
RP, MP
E (G)
Table 17 Wire Gauges and Torque Specifications
Screw
Size
Tightening
Torque
N m
(lb.in.)
Bare Wire Terminal
Applicable
Wire
Size mm 2 (AWG)
Recomm.
mm 2 (AWG)
Ferrule-Type Terminal
Applicable
Wire
Size mm 2 (AWG)
Recomm.
mm 2 (AWG)
M3
0.5 to 0.6
(4.4 to 5.3)
Stranded wire:
0.2 to 1.0
(24 to 17)
Solid wire:
0.2 to 1.5
(24 to 16)
0.75
(18)
0.25 to 0.5
(24 to 20)
0.5
(20)
TB5 E (G) M3.5
0.5 to 1.0
(4.4 to 8.9)
0.5 to 2
(20 to 14)
1.0 (16)
1.25
(12)
– –
Wire Type
Shielded wire, etc.
Ferrule-Type Wire Terminals
Yaskawa recommends using CRIMPFOX 6, a crimping tool manufactured by PHOENIX CONTACT, to prepare wire
ends with insulated sleeves before connecting to the drive. Refer to Table 18 for dimensions.
Figure 25 d1
YEA_common
Size mm 2 (AWG)
0.25 (24)
0.34 (22)
0.5 (20) d2
Type
AI 0.25-8YE
AI 0.34-8TQ
AI 0.5-8WH
AI 0.5-8OG
Figure 25 Ferrule Dimensions
Table 18 Ferrule Terminal Types and Sizes
L mm (in) d1 mm (in)
12.5 (0.49)
12.5 (0.49)
0.8 (0.03)
0.8 (0.03)
14 (0.55) 1.1 (0.04) d2 mm (in)
2 (0.08)
2 (0.08)
2.5 (0.10)
Manufacturer
PHOENIX CONTACT
50 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 51 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
■
Wiring the Control Circuit Terminal
This section describes the proper procedures and preparations for wiring the control terminals.
WARNING!
Sudden Movement Hazard. Operating a drive with untested emergency circuits could result in death or serious injury.
Verify all drive fast stop circuit wiring and any additional emergency circuits before operating the drive.
WARNING!
Fire hazard. Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
WARNING!
Electrical Shock Hazard. Do not remove covers or touch the circuit boards while the power is on. Failure to comply could result in death or serious injury.
WARNING!
Electrical Shock Hazard. Before servicing, disconnect all power to the equipment and lock out the power source. Failure to comply may result in injury from electrical shock. Wait at least five minutes after all indicators are OFF and measure the DC bus voltage level and main circuit terminals to confirm the circuit is safe before wiring.
WARNING!
Sudden Movement and Hazard. Install additional emergency circuits separately from the drive fast stop circuits. Failure to comply may result in personal injury.
NOTICE: Equipment Hazard. Do not connect control circuit ground terminals to the drive enclosure. Improper drive grounding can cause control circuit malfunction.
NOTICE: Equipment Hazard. Insulate shields with heat shrink tubing or tape to prevent contact with other signal lines and equipment.
Improper wiring practices could result in drive or equipment malfunction due to short circuit.
NOTICE: Equipment Hazard. Use twisted-pair or shielded twisted-pair cables for control circuits. Improper wiring practices could result in drive or equipment malfunction or nuisance trips.
NOTICE: Connect the shield of shielded cable to the appropriate ground terminal. Improper equipment grounding could result in drive or equipment malfunction or nuisance trips.
NOTICE: Separate wiring for output terminals MA, MB, MC, M1 and M2 from wiring to other control circuit lines. Improper wiring practices could result in drive or equipment malfunction or nuisance trips.
NOTICE: Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1, V/T2, W/T3, -, +1, +2) and other high-power lines. Improper wiring practices could result in drive malfunction due to electrical interference.
NOTICE: Use a class 2 power supply (UL standard) when connecting to the control terminals. Improper application of peripheral devices could result in drive performance degradation due to improper power supply.
NOTICE: Do not exceed 50 meters (164 ft.) for the control line between the drive and the operator when using an analog signal from a remote source to supply the frequency reference. Failure to comply could result in poor system performance.
NOTICE: Do not use unshielded cable for control wiring. Failure to comply may cause electrical interference resulting in poor system performance. Use shielded, twisted-pair wires, and ground the shield to the ground terminal of the drive.
NOTICE: Insulate shields with tape or shrink tubing to prevent contact with other signal lines and equipment. Improper wiring practices could result in drive or equipment malfunction due to short circuit.
Wire the control circuit only after terminals have been properly grounded and main circuit wiring is complete. Refer to
for details. Prepare the ends of the control circuit wiring as shown in
. Refer to Wire Size and Torque
.
WARNING!
Do not tighten screws beyond the specified tightening torque. Failure to comply may result in erroneous operation, damage the terminal block, or cause injury due to fire from overheating of loose electrical connections.
NOTICE: Use shielded twisted-pair cables as indicated to prevent operating faults. Improper wiring practices could result in drive or equipment malfunction due to electrical interference.
3
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 51
TOEP_C710616_38H_7_0.book 52 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
Connect control wires as shown in
.
Figure 26
A
YEA_common
B
Preparing wire terminal ends
C
D
A – Loosen screw to insert wire
B – Single wire or stranded wire
C – Avoid fraying wire strands when stripping insulation from wire. Strip length 5.5 mm (0.22 in.)
D – Blade depth of 0.4 mm (0.02 in.) or less
Blade width of 2.5 mm (0.10 in.) or less
Figure 26 Terminal Board Wiring Guide
When connecting control wires to the terminals, use shielded twisted-pair wires (treating wire ends as shown in
and connect the shield to the ground terminal (E [G]) of the drive.
Figure 27
E B
A C
D
A – Drive side
B – Insulation
C – Control device side
D – Shield sheath (insulate with tape or heat-shrink tubing)
E – Shield
Figure 27 Preparing the Ends of Shielded Cables
NOTICE: Do not exceed 50 meters (164 ft.) for the control line between the drive and the operator when using an analog signal from a remote source to supply the frequency reference. Failure to comply could result in poor system performance.
52 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 53 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
■
Switches and Jumpers on the Terminal Board
The terminal board is equipped with several switches used to adapt the drive I/Os to the external control signals.
shows the location of these switches. Refer to
Control I/O Configuration on page 54
for setting instructions.
Figure 28
YEA_c ommon
Jumper S3
Terminal H1/H2
Sink/Source Sel.
DIP Switch S2
RS-422/485 Termination
Resistor
Off On
Figure 28 Locations of Jumpers and Switches on the Terminal Board
3
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 53
TOEP_C710616_38H_7_0.book 54 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
◆
Control I/O Configuration
■
Setting Sink/Source with Input Terminals SN and SP
Note: Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN
61800-5-2, ISO/EN 13849 Cat.3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
Use the wire jumper between terminals SC and SP or SC and SN to select between Sink mode, Source mode or external power supply for the digital inputs S1 to S8 as shown in
(Default: Sink mode, internal power supply).
NOTICE: Damage to Equipment. Do not short terminals SP and SN. Failure to comply will damage the drive.
Table 19 Digital Input Sink / Source / External Power Supply Selection
Drive Internal Power Supply (Terminal SN and
SP)
External 24 Vdc Power Supply
S7 S7
Sinking Mode (NPN)
Sourcing Mode (PNP)
S8
SN
SC
SP
S7
S8
SN
SC
SP
24 Vdc
24 Vdc
S8
SN
SC
External
24 Vdc
±
10%
SP
S7
S8
SN
SC
External
24 Vdc
±
10%
SP
24 Vdc
24 Vdc
54 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 55 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
■
Sinking/Sourcing Mode Selection for Safe Disable Inputs
Use jumper S3 on the terminal board to select between Sink mode, Source mode or external power supply for the Safe
Disable inputs H1 and H2 as shown in Table 20 (Default: Sink mode, internal power supply).
Table 20 Safe Disable Input Sink / Source / External Power Supply Selection
Drive Internal Power Supply External 24 Vdc Power Supply
Jumper S3 Jumper S3
24 Vdc 24 Vdc
HC HC
External
24 Vdc
Sinking Mode
H1 H1
Sourcing Mode
H2
HC
Jumper S3
24 Vdc
H1
H2
H2
HC
External
24 Vdc
H1
Jumper S3
24 Vdc
H2
◆
Connect to a PC
This drive is equipped with a USB port (type-B).
The drive can connect to a USB port on a PC using a USB 2.0, AB-type cable (sold separately). After connecting the drive to a PC, Yaskawa DriveWizard Plus software can be used to monitor drive performance and manage parameter settings. Contact Yaskawa for more information on DriveWizard Plus.
Download and install the USB driver before connecting L1000A to a PC with the USB cable.
To obtain the driver and software of USB Copy Unit, CopyUnitManager and DriveWizardPlus, access these sites:
U.S.A: http://www.yaskawa.com
Other areas: contact a Yaskawa representative.
Figure 29
3
USB Cable
(Type-AB)
(Type-B) (Type-A)
Figure 29 Connecting to a PC (USB)
PC
Y E A
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 55
TOEP_C710616_38H_7_0.book 56 ページ 2015年11月11日 水曜日 午後7時40分
3 Electrical Installation
◆
Wiring Checklist
1
2
3
No.
4
5
6
Item
Drive, peripherals, option cards
Check drive model number to ensure receipt of correct model.
Make sure you have the correct braking resistors, DC link choke, noise filters, and other peripheral devices installed.
Check the option card model number.
Installation area and physical setup
Ensure that the area surrounding the drive complies with specifications.
Power supply voltage, output voltage
The voltage from the power supply should be within the input voltage specification range of the drive.
The voltage rating for the motor should match the drive output specifications.
7 Verify that the drive is properly sized to run the motor.
8
Main circuit wiring
Confirm proper branch circuit protection as specified by national and local codes.
9
10
Properly wire the power supply to drive terminals R/L1, S/L2, and T/L3.
Properly wire the drive and motor together.
The motor lines and drive output terminals R/T1, V/T2, and W/T3 should match in order to produce the desired phase order. If the phase order is incorrect, the drive will rotate in the opposite direction.
11 Use 600 Vac vinyl-sheathed wire for the power supply and motor lines.
12
Use the correct wire gauges for the main circuit.
Refer to Wire Gauges and Tightening Torque on page 36 .
• Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is greater than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following formula to calculate the amount of voltage drop:
Line drop voltage (V) = 3 × wire resistance ( Ω /km) × wire length (m) × current (A) × 10 -3
• If the cable between the drive and motor exceeds 50 m (164 ft.), adjust the carrier frequency set to C6-02 accordingly.
13
Properly ground the drive. Review page 45 .
14
15
16
Tightly fasten all terminal screws (control circuit terminals, grounding terminals).
Refer to Wire Gauges and Tightening Torque on page 36
.
Install a magnetic contactor when using a dynamic braking option. Properly install the resistor and ensure that overload protection shuts off the power supply using the magnetic contactor.
Verify phase advancing capacitors, input noise filters, or ground fault circuit interrupters are NOT installed on the output side of the drive.
Control circuit wiring
17 Use twisted-pair line for all drive control circuit wiring.
18 Connect the shields of shielded wiring to the ground terminal (E [G] ).
19 Properly wire any option cards.
20
21
Check for any other wiring mistakes.
Only use a multimeter to check wiring.
Properly fasten the control circuit terminal screws in the drive.
Refer to Wire Gauges and Tightening Torque on page 36
.
22 Pick up all wire clippings.
23 Ensure that no frayed wires on the terminal block are touching other terminals or connections.
24 Properly separate control circuit wiring and main circuit wiring.
Page
–
–
–
–
–
–
–
–
–
–
56 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 57 ページ 2015年11月11日 水曜日 午後7時40分
No.
Item
25 Analog signal line wiring should not exceed 50 m (164 ft.).
26 Safe Disable input wiring should not exceed 30 m (98 ft.).
27 Check the logic of the Safe Disable monitor output signals (terminals DM+ and DM-).
3 Electrical Installation
Page
–
–
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 57
3
TOEP_C710616_38H_7_0.book 58 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
4 Start-Up Programming & Operation
◆
Using the Digital Operator
Use the digital operator to enter Run and Stop commands, edit parameters, and display data including fault and alarm information.
■
Figure 30
Keys and Displays
DIGITAL OPERATOR JVOP-180
ALM
12
2
3
5
6
7
8
9
10
No.
1
4
Display
F1
F2
ESC
RESET
RUN
STOP
ENTER
LO
RE
RUN
1
2
3
10
F1
ESC
RESET
RUN
F2
LO
RE
ENTER
STOP
11 YEA_common
9
8
4 5 6 7
Figure 30 Keys and Displays on the Digital Operator
Name Function
Function Key
(F1, F2)
ESC Key
RESET Key
RUN Key
Up Arrow Key
Down Arrow Key
ENTER Key
LO/RE Selection Key
RUN Light
The functions assigned to F1 and F2 vary depending on the currently displayed menu.
The name of each function appears in the lower half of the display window.
• Returns to the previous display.
• Moves the cursor one space to the left.
• Pressing and holding this button will return to the Speed Reference display.
• Moves the cursor to the right.
• Resets the drive to clear a fault situation.
Starts the drive in the LOCAL mode.
The Run LED
• is on, when the drive is operating the motor.
• flashes during deceleration to stop or when the speed reference is 0.
• flashes quickly, the drive is disabled by a DI, the drive was stopped using a fast stop
DI, or an Up/Down command was active during power up.
Scrolls up to display the next item, select parameter numbers, and increment setting values.
Scrolls down to display the previous item, select parameter numbers, and decrements setting values.
Stops drive operation.
• Enters parameter values and settings.
• Selects a menu item to move between displays.
Switches drive control between the operator (LOCAL) and the control circuit terminals (REMOTE) for the Run command and speed reference. The LED is on when the drive is in the LOCAL mode (operation from keypad).
Lit while the drive is operating the motor. Refer to page
for details.
58 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 59 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
No.
11
Display
LO
RE
Name
LO/RE Light
Function
Lit while the operator is selected to run the drive (LOCAL mode). Refer to page 61
for details.
Refer to ALARM (ALM) LED Displays on page 61 .
12 ALM LED Light
<1> The STOP key has highest priority. Pressing the STOP key will always cause the drive to stop the motor, even if an Up/Down command is active at any external Up/Down command source. To disable the STOP key priority, set parameter o2-02 to 0.
<2> The LO/RE key can only switch between LOCAL and REMOTE when the drive is stopped. By default settings the LO/RE key function is disabled. To allow using the LO/RE key for switching between LOCAL and REMOTE, set parameter o2-01 to 1.
■
Figure 31
LCD Display
1 2 3
- MODE DRV Rdy
Speed Ref (OPR)
U1-01= 0.00%
U1-02= 0.00%
U1-03= 0.00A
RSEQ
LREF
FWD
FWD/REV
4
5
6
YEA_common
2
3
4
No.
1
5
6
7
Name
Operation Mode Menus
Mode Display Area
Ready
Data Display
Speed Reference Source
LO/RE
Display
Function Key 1
(F1)
9 8 7
Figure 31 LCD Display
Table 21 Display and Contents
Display
MODE Displayed when in Mode Selection.
MONITR Displayed when in Monitor Mode.
VERIFY Indicates the Verify Menu.
Content
PRMSET Displayed when in Parameter Setting Mode.
A.TUNE
Displayed during Auto-Tuning.
SETUP
DRV
Displayed when in Setup Mode.
Displayed when in Drive Mode.
PRG
Rdy
–
OPR
COM
OP
RSEQ
LSEQ
RREF
LREF
Displayed when in Programming Mode.
Indicates the drive is ready to run.
Displays specific data and operation data.
Displayed when the speed reference source is assigned to the LCD Operator.
Displayed when the speed reference source is assigned to MEMOBUS/Modbus
Communication.
Displayed when the speed reference is assigned to an option card.
Displayed when the Up/Down command is supplied from a remote source.
Displayed when the Up/Down command is supplied from the operator keypad.
Displayed when the speed reference is supplied from a remote source.
Displayed when the speed reference is supplied from the operator keypad.
HELP Pressing
F1 displays the Help menu.
←
HOME Pressing
F1
returns to the top menu (Speed Reference).
ESC Pressing
F1
returns to the previous display.
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 59
TOEP_C710616_38H_7_0.book 60 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
No.
8
Name
FWD/REV
Display
FWD
REV
FWD/REV
Content
During Up command
During Down command
Pressing
F1 the digital operator.
switches between Up and Down when the Up/Down command is set from
Pressing
F1
scrolls to the next display.
9
Function Key 2
(F2)
DATA
→ Pressing
F1
scrolls the cursor to the right.
RESET Pressing resets the existing drive fault or error.
F1
<1> Displayed when in Drive Mode.
<2> Displayed when in Drive Mode and Monitor Mode.
■
The Drive and Operation Status Display
Powering Up the Drive
Perform the following power-off checks before applying main power to the drive.
WARNING!
Electrical Shock Hazard. Do not contact live electrical parts. Failure to comply could result in death or serious injury. Never touch the output terminals directly with your hands or allow the output lines to come into contact with the drive case.
WARNING!
Sudden Movement Hazard. Operating a drive with untested emergency circuits could result in death or serious injury.
Always check the operation of drive fast stop circuits and any additional emergency circuits after they are wired. Fast stop circuits are required to provide safe and quick shutdown of the drive.
WARNING!
Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the correct state before energizing the drive. Failure to comply could result in death or serious injury from moving equipment.
Power-off Checks
Power supply voltage
Description
Ensure the power supply voltage is correct on the supply side of the disconnect, before applying power to the drive.
200 V class: 3-phase 200 to 240 Vac 50/60 Hz
400 V class: 3-phase 380 to 480 Vac 50/60 Hz
600 V class: 3-phase 500 to 600 Vac 50/60 Hz
Properly wire the power supply input terminals (R/L1, S/L2, T/L3). Check for correct wiring, terminals are tightened, and there are no loose wire strands.
Drive output terminals and motor terminals
Check for proper grounding of drive and motor.
Properly wire drive output terminals U/T1, V/T2, and W/T3 with motor terminals U/T1, V/T2, and W/T3.
Check for correct wiring, terminals are tightened, and there are no loose wire strands.
Control circuit terminals
Check control circuit terminal connections. Check that control circuit terminals are correctly wired, terminals are tightened, and there are no loose wire strands.
Drive control terminal status Open all control circuits to the drive I/O terminal block.
Status Display
When the power supply to the drive is turned on, the digital operator lights will appear as follows:
No.
Normal
Operation
Name
DIGITAL OPERATOR JVOP-180
ALM
- MODE -
Speed Ref (OPR)
U1-01= 0.00%
DRV Rdy
U1-02= 0.00%
U1-03= 0.00A
RSEQ
LREF
FWD FWD/REV
YEA_ common
Description
The data display area in the upper half of the display, displays the speed reference.
DRV is displayed.
Fault
DIGITAL OPERATOR JVOP-180 ALM
- MODE DRV
EF3
Ext Fault S3
FWD RESET
YEA_ common
External fault (example)
Data displayed varies by the type of fault. Refer to Fault Displays, Causes, and
Possible Solutions on page 132
for more information and possible solutions. ALM
LED is lit and DRV displayed.
60 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 61 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
ALARM (ALM) LED Displays
Table 22 ALARM (ALM) LED Status and Contents
State Content
Illuminated
Flashing
When the drive detects an alarm or error.
• When an alarm occurs.
• When oPE is detected.
• When a fault or error occurs during Auto-Tuning.
Off Normal operation (no fault or alarm).
Display
■
LO/RE LED and RUN LED Indications
Table 23 LO/RE LED and RUN LED Indications
LED Lit
When source of the Up/
Down command is assigned to the digital operator
(LOCAL).
During run
Flashing
–
Flashing Quickly
–
Off
Up/Down command to be given from a device other than the digital operator (REMOTE).
• During deceleration to stop.
• When an Up/Down command is input and speed reference is
0%.
• While the drive is set for
LOCAL, an Up/Down command was entered to the input terminals after which the drive was then switched to REMOTE.
• An Up/Down command was entered via the input terminals while not in the
Drive Mode.
• During deceleration when a
Fast Stop command was entered.
• The drive output is shut off by the Safe Disable function.
• While the drive was running in the REMOTE mode, the
STOP key was pushed.
During stop
Examples
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 61
TOEP_C710616_38H_7_0.book 62 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
Figure 32
Menu Structure for Digital Operator
- MODE DRV Rdy
Speed Ref (OPR)
U1-01= 0.00%
U1-02= 0.00%
U1-03= 0.00A
RSEQ
LREF
FWD FWD/REV
- MODE DRV
Monitor Menu
U1-01= 0.00%
Rdy
U1-02= 0.00%
U1-03= 0.00A
RSEQ
LREF
FWD FWD/REV
-MONITRDRV
Speed Ref 1
Rdy
U1-01= 0 00.00%
←
㧔 0.00
㨪 50.00
㧕
̌ 0.00% ̍
FWD
→
-MONITRDRV
Monitor
U 1 -01= 0.00%
Rdy
U1-02= 0.00%
U1-03= 0.00A
RSEQ
LREF
FWD FWD/REV
-MONITRDRV
Fault Trace
U 2 -01= oC
Rdy
U2-02= oPr
U2-03= 0.00Hz
RSEQ
LREF
FWD FWD/REV
<3>
- MODE PRG
Modified Consts
Modified
X Parameters
HELP FWD DATA
<4>
- MODE PRG
Quick Setting
HELP FWD DATA
Initial Display
<5>
-MONITRDRV Rdy
Speed Reference
U1- 01 = 0.00%
U1-02= 0.00%
U1-03= 0.00A
RSEQ
LREF
FWD FWD/REV
-MONITRDRV
Output Speed
U1- 02 = 0.00%
Rdy
U1-03= 0.00A
U1-04= 0
RSEQ
LREF
FWD FWD/REV
L1000A
YASKAWA
L1000A
XXXV X.X/X.XkW
XX.XX/XX.XXA
<XXXXXXXXX>
<6>
- MODE PRG
Programming
HELP FWD DATA
- MODE PRG Rdy
Auto-Tuning
AUTO
HELP FWD DATA
YEA_common
Figure 32 Digital Operator Menu and Screen Structure
<1> Pressing
RUN will start the motor.
<2> Drive cannot operate the motor.
<4> An "X" character is used as a placeholder for illustration purposes in this manual. The LCD Operator will display the actual setting values.
<5> The Speed Reference appears after the initial display which shows the product name.
<6> The information that appears on the display will vary depending on the drive.
62 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 63 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
◆
The Drive and Programming Modes
The drive has a Drive Mode to operate the motor and a Programming Mode to edit parameter settings.
Drive Mode: In Drive Mode the user can operate the motor and observe U Monitor parameters. Parameter settings cannot be edited or changed when in Drive Mode.
Programming Mode: In Programming Mode the user can edit and verify parameter settings and perform Auto-Tuning.
The drive will not accept an Up/down command when the digital operator is in the Programming Mode unless parameter b1-08 is set to 1 to allow an Up/down command.
■
Changing Parameter Settings or Values
This example explains changing C1-02 (Deceleration Ramp 1) from 1.50 seconds (default) to 2.50 seconds.
Step
1.
Turn on the power to the drive. The initial display appears.
Display/Result
- MODE DRV Rdy
Speed Ref (OPR)
U1-01= 0.00%
U1-02= 0.00%
U1-03= 0.00A
RSEQ
LREF
FWD FWD/REV
- MODE PRG
Programming
2.
Press or until the Parameter Setting Mode screen appears.
3.
Press
4.
Press
5.
6.
Press
7.
Press
to enter the parameter menu tree.
or
or
to select the C parameter group.
to select the parameter C1-02.
to view the current setting value (1.5 s). The left most digit flashes.
8.
Press
F1 left
,
F2 right
or until the desired number is selected. “1” flashes.
HELP FWD DATA
-PRMSETPRG
Initialization
A 1-00= 0
Select Language
←
FWD
→
-PRMSETPRG
Accel/Decel
C 1 -01= 1.50 sec
←
Accel Ramp 1
FWD
→
-PRMSETPRG
Basic Setup
C 1-01 = 1.50 sec
Accel Ramp 1
←
FWD
→
-PRMSETPRG
Accel Ramp 1
C101 = 1.50 sec
(0.0~600.00)
“1.50 sec”
←
FWD
→
-PRMSETPRG
Decel Ramp 1
C102 = 1.50 sec
(0.0~600.00)
“1.50 sec”
φ
FWD
ψ
-PRMSETPRG
Decel Ramp 1
C1-02= 0 01.50 sec
(0.0~600.00)
←
“1.50 sec”
FWD
→
-PRMSETPRG
Decel Ramp 1
C1-02=00 1 .50 sec
←
(0.0~600.00)
“1.50 sec”
FWD
→
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 63
TOEP_C710616_38H_7_0.book 64 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Step
9.
Press and enter 0020.0.
10.
Press to confirm the change.
11.
The display automatically returns to the screen shown in Step 4.
12.
Press as many times as necessary to return to the initial display.
Display/Result
-PRMSETPRG
Decel Ramp 1
C1-02=00 2 .50 sec
(0.0~600.00)
←
“1.50 sec”
FWD
→
Entry Accepted
-PRMSETPRG
Decel Ramp 1
C102 = 2.50 sec
(0.0~600.00)
“1.50 sec”
φ
FWD
ψ
- MODE DRV Rdy
Speed Ref (OPR)
U1-01= 0.00%
U1-02= 0.00%
U1-03= 0.00A
RSEQ
LREF
FWD FWD/REV
64 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 65 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
mplified SiSetup Using the Setup Group
In the Setup Group, the drive lists the basic parameters needed to set up the drive for an elevator application. This group expedites the startup process for an elevator application by showing only the most important parameters for the application.
Using the Setup Group
illustrates how to enter and how to change parameters in the Setup Group.
The first display shown when entering the Setup Group is the Control Method menu. Skipping this display will keep the current Setup Group parameter selection. The default setting for the Setup Group is a group of parameters most commonly use in control methods.
In this example, the Setup Group is accessed to change b1-01 from 0 to 1. This changes the source of the speed reference from the digital operator to the control circuit terminals.
- MODE DRV Rdy
Speed Ref (OPR)
U1-01= 0.00%
U1-02= 0.00%
U1-03= 0.00A
RSEQ
LREF
FWD FWD/REV
Speed reference appears when powered up
- MODE PRG
Quick Setting
HELP FWD DATA
YEA_common
<1>
- SETUP PRG
Control Method
Rdy
A1-02 = 2 ∗ 2 ∗
Open Loop Vector
Home FWD DATA
- SETUP PRG
Speed Ref Sel
Rdy b1-01 = 0 ∗ 0 ∗
Operator
Home FWD DATA
- SETUP PRG Rdy
Up/Dn Command Sel b1-02 = 1 ∗ 1 ∗
Digital Inputs
Home FWD DATA
- SETUP PRG Rdy
StallP Accel Sel
L3-01 = 1 ∗ 1 ∗
General Purpose
Home FWD DATA
Entry Accepted
- SETUP PRG
Speed Ref Sel
Rdy b1-01= 0 ∗
0
∗
Operator
←
“1”
FWD
→
Control Circuit
Terminal
<2>
- SETUP PRG
Speed Ref Sel
Rdy b1-01= 0 ∗ 0 ∗
←
Analog Input
“1”
FWD
Operator
→
<2>
<1> Use the up and down arrow keys to scroll through the Setup Group. Press the ENTER key to view or change parameter settings.
<2> To return to the previous menu without saving changes, press the ESC key.
Figure 33 Setup Group Example 4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 65
TOEP_C710616_38H_7_0.book 66 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
Switching Between LOCAL and REMOTE
LOCAL mode is when the drive is set to accept the Up/Down command from the digital operator keypad. REMOTE mode is when the drive is set to accept the Up/Down command from an external device (via the input terminals or serial communications, etc.).
Switch the operation between LOCAL and REMOTE using the LO/RE key on the digital operator or via a digital input.
This key is disabled with default settings, but can be enabled by setting parameter o2-01 to 1.
Note: 1.
After selecting LOCAL, the LO/RE light will remain lit.
2.
The drive will not allow the user to switch between LOCAL and REMOTE during run.
Using the LO/RE Key on the Digital Operator
Step Display/Result
1.
Turn on the power to the drive. The initial display appears.
2.
Press . The LO/RE light will light up. The drive is now in LOCAL.
To set the drive for REMOTE operation, press again.
YEA_c ommon
- MODE DRV Rdy
Speed Ref(A1/A2)
U1-01= 0.00%
U1-02= 0.00%
U1-03= 0.00A
RSEQ
RREF
FWD FWD/REV
YEA_ com mon
DIGITAL OPERATOR JVOP-180
ALM
- MODE DRV Rdy
Speed Ref (OPR)
U1-01= 0.00%
U1-02= 0.00%
U1-03= 0.00A
FWD
LSEQ
LREF
F1
ESC
F2
LO
RE
RESET
RUN
ENTER
STOP
◆
Start-Up Flowcharts
This section covers basic setup for the drive, including Auto-Tuning procedures and corresponding flowcharts. Follow the flowchart that matches the motor used in your application. Refer to
Types of Auto-Tuning on page 73
for details on the types of Auto-Tuning.
Flowchart
A
B
C
D
Purpose
Installation, wiring, and basic steps required to setup the motor and elevator for operation
Auto-Tuning for induction motors
Auto-Tuning for PM motors
Encoder Offset Auto-Tuning
Page
66 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 67 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
Flowchart A: Installation, Wiring, Basic Setup for Motor and Elevator
The flowchart below covers the basic procedure required to install the drive, motor, and elevator.
Figure 33
START
Install the drive as explained in
Mechanical Installation on page 17
.
Wire the drive as explained in
Main Circuit Wiring on page 34 .
Check the PG encoder power supply selection.
(Closed Loop Vector Control only -CLV)
Apply main power to the drive.
Adhere to safety messages concerning application of power.
Check the motor rotation direction.
Select the control mode in parameter A1-02.
Set up the PG encoder feedback in F1 parameters when using a
Closed Loop Vector Control and check the PG encoder rotation direction.
Set the Unit Length in parameter o1-12.
Set up o1-20 to o1-22 and then select the display units for speed, acceleration and deceleration ramp and jerk settings in o1-03.
Perform Auto-Tuning for motor parameters and the PG encoder offset.
For control modes below, refer to
Flowchart B: Auto-Tuning for Induction Motors on page 70 .
• V/f Control
• Open Loop Vector Control
• Closed Loop Vector Control
For Closed Loop Vector for PM, refer to
Flowchart C: Auto-Tuning for PM Motors on page 71 .
Digital operator (b1-01 = 0)
(Speed selection by digital inputs)
Determine the source of the speed reference.
Analog Input
Assign functions to the analog/digital I/O terminals using parameters H1, H2, H3, and H4.
Set the Speed Reference Selection mode parameter d1-18.
Assign functions to the digital I/O terminals using parameters H1 and H2.
Set up:
• Acceleration/deceleration ramp (C1-
• Jerk settings (C2)
)
Set up:
• Preset speed references (d1)
• Acceleration/deceleration ramp (C1-
• Jerk settings (C2)
)
Set up the Inspection Operation sequence.
Perform a test run.
Fine-tuning
• Adjust settings for the brake sequence (S1-
• Adjust speed control loop (C5) etc.
) .
FINISH
Figure 34 Installation, Wiring, Basic Setup for Motor and Elevator
Note: Set parameter H5-11 to 1 when setting parameters using MEMOBUS/Modbus communications.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 67
4
TOEP_C710616_38H_7_0.book 68 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
Power On
Take the following precautions before applying main power to the drive:
WARNING!
Sudden Movement Hazard. Ensure start/stop, I/O and safety circuits are wired properly and in the correct state before energizing or running the drive. Failure to comply could result in death or serious injury from moving equipment.
WARNING!
Fire Hazard. Do not use an improper voltage source. Failure to comply could result in death or serious injury by fire. Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.
WARNING!
Fire Hazard. Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections. Tighten all terminal screws to the specified tightening torque.
WARNING!
Fire Hazard. Do not connect the AC power line to the output motor terminals of the drive. Failure to comply could result in death or serious injury by fire as a result of drive damage from line voltage application to output terminals.
• Do not connect AC line power to output terminals U/T1, V/T2, and W/T3.
• Make sure that the power supply lines are connected to main circuit input terminals R/L1, S/L2, and T/L3
(or R/L1 and S/L2 for single-phase power).
WARNING!
Sudden Movement Hazard. Clear personnel, secure equipment and check sequence and safety circuitry before starting the drive. Failure to comply could result in death or serious injury from moving equipment.
• Clear all personnel from the drive, motor, and machine area.
• Secure covers, couplings, shaft keys, and machine loads.
• Ensure start/stop and safety circuits are wired properly and in the correct state.
WARNING!
Sudden Movement Hazard. Operating a drive with untested emergency circuits could result in death or serious injury.
Always check the operation of drive fast stop circuits and any additional emergency circuits after they are wired. Fast stop circuits are required to provide safe and quick shutdown of the drive.
NOTICE: Equipment Hazard. Comply with proper wiring practices. The motor may run in reverse if the phase order is backward.
Connect motor input terminals U/T1, V/T2, and W/T3 to drive output terminals U/T1,V/T2, and W/T3. The phase order for the drive and motor should match.
NOTICE: Equipment Hazard. Check all the wiring including the PG encoder wiring and PG option jumper settings, to ensure that all connections are correct after installing the drive and connecting any other devices. Failure to comply could result in damage to the drive.
After applying the power, the drive mode display should appear and no fault or alarm should be displayed. In the event of a drive fault or error code, refer to
.
■
Control Mode Selection
Select one of the four motor control modes after applying power to the drive. Note that Closed Loop Vector modes require
PG encoder feedback cards. The table below indicates possible control modes depending on the motor type and shows the required encoder feedback card.
Machine Type
Induction motor without encoder
Induction motor with incremental encoder
Permanent magnet motor with EnDat 2.1/01,
EnDat 2.2/01, or EnDat 2.2/22 encoder
Permanent magnet motor with ERN1387 or
ERN487 encoder
Yaskawa IPM motor with incremental encoder
Control Mode
V/f Control
Open Loop Vector Control
Closed Loop Vector Control
Closed Loop Vector Control for PM motors
A1-02 setting Encoder Option Card
0
2
3
No card required
No card required
PG-B3 / PG-X3
7 PG-F3
Closed Loop Vector Control for PM motors
Closed Loop Vector Control for PM motors
7
7
PG-E3
PG-X3
68 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 69 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
Motor Rotation Direction Setup
Check the direction of motor rotation to verify the Up command causes the elevator to move in the upward direction.
Perform the following checks to confirm proper motor and load direction:
• The drive outputs motor voltage in U/T1-V/T2-W/T3 phase sequence when an Up command is issued. Check the motor rotation with this phase sequence (for most motors clockwise is seen from the shaft side).
• If the motor drives the elevator in the up direction with a U/T1-V/T2-W/T3 sequence, make sure parameter b1-14 is set to 0.
• If the motor drives the elevator in the down direction with a U/T1-V/T2-W/T3 sequence, make sure parameter b1-14 is set to 1. Motor direction may also be changed by reversing two motor leads connected to U/T1, V/T2, W/T3 on the drive terminal block.
DANGER!
Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are OFF and measure the DC bus voltage level to confirm safe level.
Note: Always perform motor rotation direction setup prior to setting the encoder rotation direction.
■
PG Encoder Setup
PG Encoder Resolution Setup
Set the encoder resolution (incremental signal in the case of absolute encoders with Sin/Cos channels) in parameter
F1-01.
PG Encoder Rotation Direction Setup
Perform the following steps to make sure the PG encoder rotation direction is set up correctly in the drive.
If information about the signal sequence of the PG encoder is available:
1.
Check the sequence of PG encoder phases A and B when the motor drives the elevator in the up direction.
2.
If the PG encoder A phase leads phase B, make sure F1-05 is set to 0.
3.
If the PG encoder B phase leads phase A, make sure F1-05 is set to 1.
If no information about the signal sequence of the PG encoder is available:
1.
Turn the motor manually in elevator up direction while checking the value of monitor U1-05.
2.
If the value in U1-05 is positive, the set PG encoder direction is correct.
3.
If the value in U1-05 is negative, alter the setting of parameter F1-05.
Note: Always set the motor rotation direction prior to the encoder rotation direction. Refer to
Motor Rotation Direction Setup on page 69
.
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 69
TOEP_C710616_38H_7_0.book 70 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
Flowchart B: Auto-Tuning for Induction Motors
The flowchart below covers Auto-Tuning for induction motors operating with V/f Control, Open Loop Vector Control, or
Closed Loop Vector Control.
START
YEA_common
Set terminals H1 and H2 if the Safe Disable function is used.
Set the Baseblock input (H1 = 8/9) if used.
Refer to
Auto-Tuning Fault Detection on page 140
.
Remove the source of Fault/Alarm and repeat Auto Tuning.
Is the Control Mode
V/f Control ?
No
A1-02 = 2 or 3
Yes
A1-02 = 0
Select Stationary Auto-Tuning for Terminal Resistance only,
T1-01 = 2.
Can the motor rotate freely?
No
Select Stationary
Auto-Tuning 1 or 2
T1-01 = 1 or 4.
Yes
(Ropes removed)
Select Rotational
Auto-Tuning
T1-01 = 0.
Enter the data in to T1 parameters as indicated on the display.
Press the Up key until “Tuning Ready” is displayed.
<1>
Enter the data in to T1displayed.
parameters as indicated on the display.
Press the Up key until “Tuning Ready” is
<1>
Release the Brake.
Close the motor contactor.
Press the Run key on the digital operator and wait until Auto-Tuning is finished.
Tuning
Successful?
No
(Alarm or Fault code displayed Yes
(“Entry Accepted” displayed) <2>
Apply the brake if it was released during Auto-tuning.
Open the motor contactor.
Open terminals H1-HC and H2-HC if used during the normal sequence.
Open the Baseblock input (H1 = 8/9) if used.
FINISH
<1> If an LED operator is used, the display shows “
<2> If an LED operator is used, the display shows “
”.
”.
Figure 35 Auto-Tuning for Induction Motors
70 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 71 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
Flowchart C: Auto-Tuning for PM Motors
The flowchart below covers Auto-Tuning for permanent magnetic (PM) motors operating with Closed Loop Vector
Control for PM motors.
START
Set terminals H1-HC and H2-HC if Safe Disable function is used.
Set the Baseblock input (H1 = 8/9) if used.
YEA_common
No
Is the motor data sheet available?
Yes
Select Motor Data Input
T2-01 = 0.
Enter the data in to T2 parameters as indicated on the display.
Press the Up key until “Tuning Ready” is displayed.
<1>
Select Stationary Auto-Tuning
T2-01 = 1.
Enter the data in to T2 parameters as indicated on the display.
Press the Up key until “Tuning Ready” is displayed.
<1>
Close the motor contactor.
Refer to
Auto-Tuning Fault Detection on page 140
.
Remove the Fault/Alarm source and repeat Auto Tuning.
Press the Run key on the digital operator and wait until Auto-Tuning is finished.
Tuning
Successful?
Yes
(“Entry Accepted” displayed <2>
Continue with encoder offset tuning.
Refer to
Flowchart D: PG Encoder Offset Auto-Tuning on page 72 .
Can the motor rotate freely?
No
Yes (Ropes removed)
・ Select Rotational Back EMF Constant Auto-Tuning T2-01=11.
・ Press the Up key.
Press the Run key on the digital operator and wait until Auto-Tuning is finished.
Open the motor contactor.
Open terminals H1-HC and H2-HC if used during the normal sequence.
Open the Baseblock input (H1 = 8/9) if used.
FINISH
<1> If an LED operator is used, the display shows “
<2> If an LED operator is used, the display shows “
”.
”.
Figure 36 Auto-Tuning for PM Motors
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 71
4
TOEP_C710616_38H_7_0.book 72 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
Flowchart D: PG Encoder Offset Auto-Tuning
The flowchart below covers Rotational and Stationary Auto-Tuning procedures used to automatically set up the PG encoder offset. PG encoder Offset Tuning should be performed when the PG encoder offset (T2-17) is unknown, when a
PG encoder offset value has been set but problems with the speed feedback occur, or when the PG encoder is replaced.
START
YEA_comm on
Set the motor and PG encoder data manually or perform motor data Auto-tuning.
No
Has all motor and PG encoder data been set correctly?
Yes
Set terminals H1-HC and H2-HC if Safe Disable function is used.
Set the Baseblock input (H1 = 8/9) if used.
Close the motor contactor(s).
Select Initial Magnet Pole Search Parameter Auto-Tuning T2-01 = 3.
Press the Up key until “Tuning Ready” is displayed.
<1>
Press the Run key on the digital operator and wait until
Auto-Tuning is finished.
No - “Er-22” <2>
Rotational PG Encoder Offset Auto-Tuning necessary
Tuning
Successful?
Yes
(Stationary PG Encoder Offset
Auto-Tuning possible)
Absolute PG encoder necessary for driving the motor.
Change the PG option card and use an absolute PG Encoder
(EnDat, ...).
Absolute PG encoder used?
Yes
(EnDat, ...)
No
(PG-X3, Incremental
PG encoder used)
Uncouple motor and the mechanical system of the elevator (remove ropes).
Select Stationary Encoder Offset Auto-Tuning
T2-01 = 4.
Press the Up key until “Tuning Ready” is displayed.
<1>
Press the Run key on the digital operator and wait until Auto-Tuning is finished.
Select Rotational PG Encoder Offset
Auto-Tuning T2-01 = 10.
Press the Up key until “Tuning Ready” is displayed.
<1>
Tuning
Successful?
No
Yes
Refer to
Auto-Tuning Fault Detection on page 140
.
Remove the Fault/Alarm source and repeat Auto Tuning.
Release the brake.
Press the Run key on the digital operator and wait until Auto-Tuning is finished.
Apply the brake.
Tuning
Successful?
Yes
No
Refer to
Auto-Tuning Fault Detection on page 140
.
Remove the Fault/Alarm source and repeat Auto Tuning.
Open the motor contactor.
Open the Baseblock input (H1 = 8/9) if used.
Open terminals H1-HC and H2-HC if used during the normal sequence.
Recouple the motor (ropes) to the load if decoupled for tuning.
FINISH
<1> If an LED operator is used, the display shows “
<2> If an LED operator is used, the display shows “ ”.
”.
Figure 37 PG Encoder Offset Auto-Tuning
72 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 73 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
Types of Auto-Tuning
The drive offers different types of Auto-Tuning for induction motors and permanent magnet motors. The type of
Auto-Tuning used differs further based on the control mode and other operating conditions. Refer to the tables below to select the type of Auto-Tuning that bests suits the application. Directions for performing Auto-Tuning are listed in
Start-Up Flowcharts on page 66 .
Note: The drive will only show Auto-Tuning parameters that are valid for the control mode that has been set in A1-02. If the control mode is for an induction motor, the Auto-Tuning parameters for PM motors will not be available. If the control mode is for a PM motor, the Auto-Tuning parameters for induction motors will not be available. Inertia Tuning and ASR Gain Tuning parameters and setting options will be visible only when the drive is set for operation with CLV or CLV/PM.
Auto-Tuning for Induction Motors
Table 24 Types of Auto-Tuning for Induction Motors
Type Setting Requirements and Benefits
Control Mode (A1-02)
V/f (0) OLV (2) CLV (3)
Rotational
Auto-Tuning
Stationary
Auto-Tuning 1
Stationary
Auto-Tuning for
Line-to-Line
Resistance
Stationary
Auto-Tuning 2
T1-01 = 0
T1-01 = 1
T1-01 = 2
T1-01 = 4
• Rotational Auto-Tuning gives the most accurate results, and is recommended if possible.
• Motor must run freely or with light load (<30%), i.e. ropes have to be removed.
• A motor test report listing motor data is not available.
• Automatically calculates motor parameters needed for vector control.
• Use if ropes cannot be removed. Note that the accuracy is less then with
Rotational Auto-Tuning.
• Used for V/f Control or in vector control modes when the drive was previously set up properly and now the motor cable has changed.
• Used in V/f control if drive and motor capacities differ.
• Should not be used for any vector control modes unless the motor cable has changed.
• A motor test report is available. Once the no-load current and the rated slip have been entered, the drive calculates and sets all other motor-related parameters.
• Use if ropes cannot be removed and if slip and no-load current data are available.
No
No
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Auto-Tuning for Permanent Magnet Motors
Automatically sets the V/f pattern and motor parameters E1 , E5 , and some F1 parameters for speed feedback detection.
Table 25 Types of Auto-Tuning for Permanent Magnet Motors
Type
Motor Data Input
Stationary Auto-Tuning
Stationary Stator
Resistance Auto-Tuning
Rotational Back EMF
Constant Auto-Tuning
Setting
T2-01 = 0
T2-01 = 1
T2-01 = 2
T2-01 = 11
Requirements and Benefits
• Use if a motor test report is available.
• Input motor data from the motor test report. Convert data into the correct unit before inputting data if necessary.
• Motor does not rotate during Auto-Tuning.
• Use if a motor test report is not available.
• Input motor data from the motor name plate. Make sure to convert data into the correct units. The drive automatically calculates the motor data.
• Tunes stator resistance only.
• Should be performed if the motor cabling has changed.
• Use if a motor test is not available.
• Tunes the Motor Induction Voltage only.
• Should be performed after Motor data are set and the encoder offset is adjusted.
• The motor must be uncoupled from the mechanical system (remove ropes).
Auto-Tuning of PG-E3
Encoder Characteristics
T2-01 = 12 Perform this Auto-Tuning to obtain accurate position data from the motor rotor for driving a PM motor.
<1> Available in drive software versions PRG: 7017 or later.
Auto-Tuning of PG-E3 encoder characteristics requires a PG-E3 option with software version 1102 or later. To identify the PG-E3 software version, refer to the PG-E3 labeling on the option, in the field designated “C/N” (S + four digit number).
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 73
TOEP_C710616_38H_7_0.book 74 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Input Value
Input
Paramet er
Unit
Control Mode
Motor Rated Power
Motor Rated Voltage
A1-02
T2-04
T2-05
Motor Rated Current
Number of Motor Poles
T2-06
T2-08
Motor Rated Speed T2-09
Stator 1 Phase Resistance T2-10
T2-11
T2-12 d-Axis Inductance q-Axis Inductance
Induced Voltage
Constant Unit Selection
Voltage Constant
PG Number of Pulses per
Revolution
T2-13
T2-14
T2-16
– kW
V
A
N/A r/min
Ω mH mH
N/A
Yes
Yes
Z Pulse Offset
Speed Reference for
Auto-Tuning of PG-E3
Encoder
Characteristics
Rotation Direction for
Auto-Tuning of PG-E3
Encoder
Characteristics
T2-17
T2-18
T2-19
N/A deg
(mech.) r/min
N/A
Yes
Yes
N/A
N/A
<1> Available in drive software versions PRG: 7017 or later.
<2> Depends on T2-13 setting.
Table 26 Auto-Tuning Input Data
7
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
0
Motor
Paramet er
Settings
1
Stationar y
2
Stationar y
Stator
Resistan ce
7
Yes
Yes
Yes
Yes
Yes
N/A
N/A
N/A
7
N/A
N/A
Yes
N/A
N/A
N/A
N/A
N/A
Tuning Type (T2-01)
3
Initial
Magnet
Pole
Search
Paramete rs
Auto-Tuni ng
7
4
Encoder
Offset
Stationar y
Auto-Tuni ng
10
Encoder
Offset
Rotationa l
Auto-Tuni ng
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
7
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
7
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
11
Back
EMF
Constant
12
Auto-
Tuning of
PG-E3
Encoder
Characteristics
7
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
7
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Yes
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Yes
Yes
Properly set the motor and PG encoder data before performing PG Encoder Offset Tuning.
Table 27 Types of Auto-Tuning for PG Encoder Offset
Type
Initial Magnet Pole Search
Parameters Auto-Tuning
Stationary PG Encoder
Offset
Auto-Tuning
Rotational PG Encoder
Offset
Auto-Tuning
Setting
T2-01 = 3
T2-01 = 4
Requirements and Benefits
• Should be performed after motor Auto-Tuning in order to determine the PG encoder tuning method.
• Attempts to detect the motor rotor position, determines whether PG encoder offset can be tuned using
Stationary Encoder Offset Tuning and sets parameters needed for Initial Magnet Pole Search (n8-36, n8-37).
• When using the Rescue Operation mode, perform this tuning to let the drive automatically set the parameters needed for Initial Magnet Pole Search with power supply from a battery or UPS (n8-81, n8-82).
• Must be performed when using an incremental PG encoder.
Important: If this tuning fails when using a PG-X3 card with an incremental PG encoder the motor cannot be driven using an incremental PG encoder. Change the PG encoder to an absolute PG encoder.
• Tunes the PG encoder offset without rotating the motor.
• If the PG encoder offset cannot be tuned properly by this method, try Rotating PG Encoder Offset
Tuning.
T2-01 = 10
• Tunes the PG encoder offset while rotating the motor.
• Motor and mechanical system must be uncoupled (ropes must be removed from traction sheave).
74 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 75 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Auto-Tuning of PG-E3 Encoder Characteristics
This feature optimizes the drive settings for the characteristics of the PG-E3 speed-control option card for the ERN1387 encoder (manufactured by HEIDENHAIN) while rotating the motor. Perform Auto-Tuning to obtain accurate position data from the motor rotor for driving a PM motor. This type of Auto-Tuning automatically sets the characteristics of the
PG-E3 option card for the ERN1387 encoder in parameters F1-66 to F1-81 (Encoder Adjust 1 to 16).
Note: 1.
The motor rotates during execution of Auto-Tuning of PG-E3 encoder characteristics. Before starting, refer to the drive technical manual.
2.
Auto-Tuning of PG-E3 encoder characteristics adjusts the unique characteristics of the ERN1387 encoder connected to the drive by using a PG-E3 option card. This type of tuning should be performed when setting up the drive or after replacing the encoder or drive.
The signal lines between the PG-E3 option card and the ERN1387 encoder must be connected between the R+ and R- terminals while this type of tuning is performed.
3.
The setting values of parameters F1-66 to F1-81 are reset to factory default values when A1-03 is set to 2220. The setting values of parameters F1-66 to F1-81 are modified at completion of Auto-Tuning of PG-E3 encoder characteristics.
■
Auto-Tuning Interruption and Fault Codes
If tuning results are abnormal or the STOP key is pressed before completion, Auto-Tuning will be interrupted and a fault code will appear on the digital operator.
Figure 34
DIGITAL OPERATOR JVOP-180
ALM
DRV FOUT
DRV Rdy
Tune Proceeding
X.XX Hz/ X.XXA
FWD
DIGITAL OPERATOR JVOP-180
- MODE DRV
ALM
Er-03
STOP key
FWD RESET YEA_ common
During Auto-Tuning Auto-Tuning Aborted
Figure 38 Auto-Tuning Aborted Display
■
Auto-Tuning Operation Example
The following example demonstrates Rotational Auto-Tuning when using OLV (A1-02 = 2).
Selecting the Type of Auto-Tuning
Step
1.
Turn on the power to the drive. The initial display appears.
Display/Result
- MODE DRV Rdy
Speed Ref (OPR)
U1-01= 0.00%
U1-02= 0.00%
U1-03= 0.00A
RSEQ
LREF
FWD FWD/REV
2.
Press or until the Auto-Tuning display appears.
- MODE PRG
Auto-Tuning
AUTO
HELP FWD DATA
3.
Press
4.
Press
to begin setting parameters.
to select the value for T1-01.
- A.TUNE PRG
Tuning Mode
T101 = 0 ∗
0
∗
Standard Tuning
ESC FWD DATA
- A.TUNE PRG
Tuning Mode
T1-01= 0 ∗
0
∗
Standard Tuning
“0”
FWD
4
5.
Save the setting by pressing .
Entry Accepted
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 75
TOEP_C710616_38H_7_0.book 76 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Step
6.
The display automatically returns to the display shown in Step 3.
Display/Result
- A.TUNE PRG
Tuning Mode
T101 = 0 ∗ 0 ∗
Standard Tuning
ESC FWD DATA
Enter Data from the Motor Nameplate
After selecting the type of Auto-Tuning, enter the data required from the motor nameplate.
Note: These instructions continue from Step 6 in “Selecting the Type of Auto-Tuning”.
Step
1.
Press to access the motor output power parameter T1-02.
2.
Press to view the default setting.
3.
Press
F1 left data in kW.
,
F2 right
, , and to enter the motor power nameplate
Display/Result
- A.TUNE PRG
Mtr Rated Power
T102 = 3.70kW
(0.00 ~ 650.00)
“3.70kW”
ESC FWD DATA
- A.TUNE PRG
Mtr Rated Power
T1-02= 0 03.70kW
(0.00 ~ 650.00)
“3.70kW”
FWD
- A.TUNE PRG
Mtr Rated Power
T1-02= 004.0
0 kW
(0.00 ~ 650.00)
“3.70kW”
FWD
4.
Press to save the setting.
Entry Accepted
5.
The display automatically returns to the display in Step 1.
- A.TUNE PRG
Mtr Rated Power
T102 = 4.00kW
(0.00 ~ 650.00)
“3.70kW”
ESC FWD DATA
- A.TUNE PRG
Mtr Rated Power
T102 = 4.00kW
(0.00 ~ 650.00)
“3.70kW”
ESC FWD DATA
6.
Repeat Steps 1 through 5 to set the following parameters:
• T1-03, Motor Rated Voltage
• T1-04, Motor Rated Current
• T1-05, Motor Base Frequency
• T1-06, Number of Motor Poles
• T1-07, Motor Base Speed
- A.TUNE PRG
Rated Speed
T107 = 1450RPM
(0 ~ 24000)
“1450RPM”
ESC FWD DATA
Starting Auto-Tuning
WARNING!
Sudden Movement Hazard. The drive and motor may start unexpectedly during Auto-Tuning, which could result in death or serious injury. Ensure the areas surrounding the drive, motor and load are clear before proceeding with Auto-Tuning.
WARNING!
Electrical Shock Hazard. High voltage will be supplied to the motor when Stationary Auto-Tuning is performed even with the motor stopped, which could result in death or serious injury. Do not touch the motor until Auto-Tuning has been completed.
WARNING!
When performing Rotational Auto-Tuning for motor data or PG encoder offset, always uncouple the motor from the mechanical system (remove ropes from traction sheave). Performing Rotational Auto-Tuning with the mechanical system connected to the motor can cause hazardous situations, injury to personnel and damage to the equipment.
NOTICE: Rotational Auto-Tuning will not function properly if a holding brake is applied on the load. Ensure the motor can freely spin before beginning Auto-Tuning. Failure to comply could result in improper operation of the drive.
Enter the required information from the motor nameplate. Press to proceed to the Auto-Tuning start display.
Note: These instructions continue from Step 6 in “Enter Data from the Motor Nameplate”.
76 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 77 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
1.
Step
After entering the data listed on the motor nameplate, press to confirm.
Display/Result
- A.TUNE DRV
Auto-Tuning
0.00 Hz/ 0.00A
Tuning Ready ?
Press RUN key
ESC FWD
2.
Press to activate Auto-Tuning. The drive begins by injecting current into the motor for about 1 min, and then starts to rotate the motor.
Note: The first digit on the display indicates which motor is undergoing Auto-Tuning
(motor 1 or motor 2). The second digit indicates the type of Auto-Tuning being performed.
- A.TUNE DRV Rdy
Tune Proceeding
X.XX Hz/ X.XXA
FWD
3.
Auto-Tuning finishes in approximately one to two minutes.
- MODE DRV
End
Tune Successful
FWD RESET
■
Parameter Settings during Induction Motor Auto-Tuning: T1
The T1 parameters are used to set the Auto-Tuning input data for induction motor tuning.
Note: For motors operating in the field weakening range, first perform the Auto-Tuning with the base data. After Auto-Tuning is complete, change E1-04, Maximum Output Frequency, to the desired value.
T1-01: Auto-Tuning Mode Selection
Sets the type of Auto-Tuning to be used.
Refer to Auto-Tuning for Induction Motors on page 73 for details on the
different types of Auto-Tuning.
Setting Range
2 (V/f)
0 to 2, 4 (OLV, CLV)
Default
2 (V/f)
1 (OLV, CLV)
No.
T1-01
Parameter Name
Auto-Tuning Mode Selection
Setting 0: Rotational Auto-Tuning
Setting 1: Stationary Auto-Tuning 1
Setting 2: Stationary Auto-Tuning for Line-to-Line Resistance
Setting 4: Stationary Auto-Tuning 2
T1-02: Motor Rated Power
Sets the motor rated power according to the motor nameplate value.
No.
T1-02
Parameter Name
Motor Rated Power
Setting Range
0.00 to 650.00 kW
Default
Determined by o2-04
T1-03: Motor Rated Voltage
Sets the motor rated voltage according to the motor nameplate value. Enter the motor voltage at base speed here if the motor is operating above base speed.
Enter the voltage needed to operate the motor under no-load conditions at rated speed to T1-03 for better control precision around rated speed when using a vector control mode. The no-load voltage can usually be found in the motor test report available from the manufacturer. If the motor test report is not available, enter approximately 90% of the rated voltage printed on the motor nameplate. This may increase the output current and reduce the overload margin.
4
No.
T1-03
Parameter Name
Motor Rated Voltage
Setting Range
0.0 to 255.5 V
Default
<1> Values shown are specific to 200 V class drives. Double value for 400 V class drives. Multiply value by 2.875 for 600 V class drives.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 77
TOEP_C710616_38H_7_0.book 78 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
T1-04: Motor Rated Current
Sets the motor rated current according to the motor nameplate value. Set the motor rated current between 50% and 100% of the drive rated current for optimal performance in OLV or CLV. Enter the current at the motor base speed.
No.
T1-04
Parameter Name
Motor Rated Current
Setting Range
10 to 200% of drive rated current
Default
Depending on o2-04
T1-05: Motor Base Frequency
Sets the motor rated frequency according to the motor nameplate value. If a motor with an extended speed range is used or if the motor is used in the field weakening area, enter the maximum frequency to E1-04 (E3-04 for motor 2) after
Auto-Tuning is complete.
No.
T1-05
Parameter Name
Motor Base Frequency
T1-06: Number of Motor Poles
Sets the number of motor poles according to the motor nameplate value.
Setting Range
0.0 to 200.0 Hz
Default
60.0 Hz
No.
T1-06
Parameter Name
Number of Motor Poles
Setting Range
2 to 48
Default
4
T1-07: Motor Base Speed
Sets the motor rated speed according to the motor nameplate value. If a motor with an extended speed range is used or if the motor is used in the field weakening area, enter the speed at base frequency to T1-07.
No.
T1-07
Parameter Name
Motor Base Speed
Setting Range
0 to 24000 r/min
T1-08: PG Number of Pulses Per Revolution
Sets the number of pulses from the PG encoder. Set the actual number of pulses for one full motor rotation.
Default
1750 r/min
No.
T1-08
Parameter Name
PG Number of Pulses Per Revolution
Setting Range
0 to 60000 ppr
Default
1024 ppr
Note: T1-08 will only be displayed in CLV.
T1-09: Motor No-Load Current
Sets the no-load current for the motor. The default setting displayed is no-load current automatically calculated from the output power set in T1-02 and the motor rated current set to T1-04. Enter the data listed on the motor test report. Leave this data at the default setting if the motor test report is not available.
No.
T1-09
Parameter Name
Motor No-Load Current
Setting Range
0 to [T1-04] A
(Max: 0 to 2999.9)
Default
–
<1> The value will have two decimal places (0.01 A) in the drive models 2 0008 to 2 0033,4 0005 to 4 0018 and 5 0003 to 5 0013 (refer to
Table 57 ), and one decimal place (0.1 A) in the drive models 2
0047 to 2 0415, 4 0024 to 4 0605 and 5 0017 to
5 0200.
78 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 79 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
T1-10: Motor Rated Slip
Sets the rated slip for the motor.
The default setting displayed is the motor rated slip for a Yaskawa motor calculated from the output power set in T1-02.
Enter the data listed on the motor test report.
No.
T1-10
Parameter Name
Motor Rated Slip
Setting Range
0.00 to 20.00 Hz
Default
–
■
Parameter Settings during PM Motor Auto-Tuning: T2
The T2 parameters are used to set the Auto-Tuning input data for PM motor tuning.
T2-01: PM Auto-Tuning Mode Selection
details on different types of Auto-Tuning.
No.
T2-01
Parameter Name
PM Auto-Tuning Mode Selection
Setting Range
0 to 4, 10 to 12
Default
0
<1> Setting 12 is available in drive software versions PRG: 7017 or later.
Auto-Tuning of PG-E3 encoder characteristics requires a PG-E3 option with software version 1102 or later. To identify the PG-E3 software version, refer to the PG-E3 labeling on the option, in the field designated “C/N” (S + four digit number).
Setting 0: Motor Data Input
Setting 1: PM Stationary Auto-Tuning
Setting 2: PM Stationary Stator Resistance Auto-Tuning
Setting 3: Initial Magnet Pole Search Parameters Auto-Tuning
Setting 4: Stationary PG Encoder Offset Auto-Tuning
Setting 10: Rotational PG Encoder Offset Auto-Tuning
Setting 11: Rotational Back EMF Constant Auto-Tuning
Setting 12: Auto-Tuning of PG-E3 Encoder Characteristics
T2-04: PM Motor Rated Power
Specifies the PM motor rated power in kilowatts.
No.
T2-04
T2-05: PM Motor Rated Voltage
Sets the PM motor rated voltage.
Parameter Name
PM Motor Rated Power
Setting Range
0.00 to 650.00 kW
Default
Depending on o2-04
No.
T2-05
Parameter Name
PM Motor Rated Voltage
Setting Range
0.0 to 255.0 V
Default
<1> Values shown are specific to 200 V class drives. Double value for 400 V class drives. Multiply value by 2.875 for 600 V class drives.
T2-06: PM Motor Rated Current
Enter the PM motor rated current in amps.
No.
T2-06
Parameter Name
PM Motor Rated Current
Setting Range
10% to 200% of the drive rated current
Default
Depending on o2-04
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 79
TOEP_C710616_38H_7_0.book 80 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
T2-08: Number of PM Motor Poles
Enter the number of motor poles.
No.
T2-08
Parameter Name
Number of PM Motor Poles
<1> When PG-E3 option connected: Max setting = 48
T2-09: PM Motor Base Speed
Enter the motor rated speed in r/min.
Note: T2-09 will be displayed when in CLV/PM.
No.
T2-09
Parameter Name
PM Motor Base Speed
T2-10: PM Motor Stator Resistance
Enter the motor stator resistance per motor phase.
No.
T2-10
Parameter Name
PM Motor Stator Resistance
T2-11: PM Motor d-Axis Inductance
Enter the d axis inductance per motor phase.
No.
T2-11
Parameter Name
PM Motor d-Axis Inductance
T2-12: PM Motor q-Axis Inductance
Enter the q axis inductance per motor phase.
Setting Range
2 to 120
Setting Range
0 to 24000 r/min
Setting Range
0.000 to 65.000
Ω
Setting Range
0.00 to 600.00 mH
Default
6
Default
150 r/min
Default
–
Default
–
No.
T2-12
Parameter Name
PM Motor q-Axis Inductance
T2-13: Induced Voltage Constant Unit Selection
Selects the units used for setting the induced voltage coefficient.
Setting Range
0.00 to 600.00 mH
Default
–
No.
T2-13
Parameter Name
Induced Voltage Constant Unit Selection
Setting Range
0, 1
Default
1
Setting 0: mV (r/min)
Setting 1: mV (rad/sec)
Note: If T2-13 is set to 0, then the drive will use E5-24 (Motor Induction Voltage Constant 2), and will automatically set E5-09 (Motor
Induction Voltage Constant 1) to 0.0. If T2-13 is set to 1, then the drive will use E5-09 and will automatically set E5-24 to 0.0.
T2-14: PM Motor Induced Voltage Constant
Enter the motor induced voltage constant.
No.
T2-14
Parameter Name
PM Motor Induced Voltage Constant
Setting Range
0.0 to 2000.0
Default
Depending on T2-02
80 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 81 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
T2-16: PG Number of Pulses Per Revolution for PM Motor Tuning
Enter the number of pulses from the PG encoder per motor rotation.
No.
T2-16
Parameter Name
Encoder Resolution (Pulses Per Revolution)
Setting Range
1 to 15000 ppr
Default
1024 ppr
T2-17: PG Encoder Z-pulse Offset
Sets the offset between the rotor magnet axis and the PG encoder zero position. If the PG encoder offset value is unknown or if the PG encoder is replaced, perform PG Encoder Offset Auto-Tuning.
No.
T2-17
Parameter Name
PG Encoder Z-pulse Offset
Setting Range
-180.0 to 180.0 deg
T2-18: Speed Reference for Auto-Tuning of PG-E3 Encoder Characteristics
Note: Available in drive software PRG: 7017 or later.
Sets the speed reference for execution of Auto-Tuning of PG-E3 encoder characteristics (T2-01 = 12).
Default
0.0 deg
No.
T2-18
Parameter Name
Speed Reference for Auto-Tuning of PG-E3 Encoder Characteristics
Setting Range
1 to 30 r/min
Default
10 r/min
T2-19: Rotation Direction for Auto-Tuning of PG-E3 Encoder Characteristics
Note: Available in drive software PRG: 7017 or later.
Sets the direction of motor rotation for execution of Auto-Tuning of PG-E3 encoder characteristics (T2-01 = 12).
No.
T2-19
Parameter Name
Rotation Direction for Auto-Tuning of PG-E3 Encoder Characteristic
Setting 0: Forward (Up)
Setting 1: Reverse (Down)
Setting Range
0, 1
Default
0
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 81
4
TOEP_C710616_38H_7_0.book 82 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
◆
Setup Procedure for Elevator Applications
■
Up and Down Commands and Speed Reference Selection
WARNING!
Sudden Movement Hazard. Remove the Up/Down Command before resetting alarms and faults. Failure to comply can result in death or serious injury.
WARNING!
Sudden Movement Hazard. Verify drive parameter b1-03 Stopping Method is set to 0:Ramp to Stop before starting the drive. Failure to comply may cause the elevator to free-fall when the Up/Down command is removed.
WARNING!
Sudden Movement Hazard. The drive is capable of running the motor at high speed. Verify the maximum drive output frequency before starting the drive. Failure to comply may cause injury or death due to inadvertent high speed operation.
WARNING!
Sudden Movement Hazard. Use the Initial Pole Search Status Signal (H2 = 61) to interlock the brake to ensure the brake is not released before the Initial Magnetic Pole Search is completed. Failure to comply may cause inadvertent elevator movement resulting in serious injury.
NOTICE: Always turn off the RUN command before changing the setting of parameters d1-18 (Speed Reference Selection Mode), b1-01 (Speed Reference Selection), or H1 (Multi-Function Digital Inputs). If the RUN command is on when changing any of these settings, the motor may unexpectedly start running, and could result in injury.
Speed Reference Selection
Parameter b1-01 determines the source of the speed reference.
b1-01
0 (default)
1
2
3
Reference source
Digital operator keypad
Serial Communication
Speed reference input
Set the speed references in the d1 parameters and use digital inputs to switch between different reference values.
Apply the speed reference signal to terminal A1 or A2.
Serial Communications using the RS422/485 port
Communications option card
<1> If source of the speed reference is assigned to the control terminals (b1-01 = 1), then d1-18 will automatically be set to 0 (so that the drive uses multi-speed references d1-01 to d1-08).
<2> If the speed reference selection in d1-18 is set so that either the high speed reference has priority (d1-18 = 1), or so that the leveling speed has priority (d1-18 = 2), then the drive will look to the multi-function input terminals for the speed reference.
Up/Down Command Source Selection
The input source for the Up and Down command can be selected using parameter b1-02.
b1-02
0
1 (default)
2
3
Up/Down source
Operator keypad
Digital inputs
Serial Communication
Option Board
Up/Down command input
RUN and STOP keys on the operator
Terminal S1: Run in the Up direction
Terminal S2: Run in the Down direction
Serial Communications using the RS422/485 port
Communications option card
Travel Start and Stop
Travel Start
To start the elevator in the up or down direction, the following conditions must be fulfilled:
• A speed reference greater than zero must be provided.
• The Safe Disable signals at terminals H1 and H2 must both be closed (drive output enabled).
• If a multi-function digital input is programmed for Baseblock (H1 = 8 or 9), this input must be set so the drive is not in a baseblock condition.
• An Up or Down Signal must be set at the source specified in b1-02.
• If a multifunction input is programmed for output contactor feedback (H1 = 56), then the output contactor must be closed.
82 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 83 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Travel Stop
The drive stops under the following conditions:
• The Up or Down command is removed.
• d1-18 is set to 1 or 2 and the Up/Down or Leveling Speed signal (H1 = 53) is removed.
• d1-18 is set to 3 and all speed inputs are removed.
• A fault occurs. The stopping method depends on the specific fault that occurred, in combination with certain parameter settings.
• The Safe Disable inputs are opened or a Base Block signal is input. In this case, the brake is applied immediately and the drive output shuts off.
■
Speed Selection Using Digital Inputs (b1-01 = 0)
Set parameter b1-01 = 0 to enable the speed selection using the drive digital inputs. Use parameter d1-18 to determine different travel speeds selected by the digital inputs.
NOTICE: Always turn off the RUN command before changing the setting of parameters d1-18 (Speed Reference Selection Mode), b1-01 (Speed Reference Selection), or H1 (Multi-Function Digital Inputs). If the RUN command is on when changing any of these settings, the motor may unexpectedly start running, and could result in injury.
d1-18
0 (default)
1
2
3
Speed Selection
Multi-speed inputs 1, Speed references are set in d1-01 to d1-08
Separate speed inputs, Speed references are set in d1-19 to d1-24 and d1-26, Higher speed has priority
Separate speed inputs, Speed references are set in d1-19 to d1-24 and d1-26, Leveling speed has priority
Multi speed inputs 2, Speed references are set in d1-02 to d1-08, Stop if no speed selection input is enabled
Multi-Speed Inputs 1, 2 (d1-18 = 0 or 3)
Speed Selection
When d1-18 = 0 or 3, multi-function digital inputs are preset as shown below.
Terminal
S5
S6
S7
Parameter Number
H1-05
H1-06
H1-07
Set Value
3
4
5
Details
Multi-Speed Reference 1
Multi-Speed Reference 2
Multi-Speed Reference 3
Different speed reference settings can be selected by combining the three digital inputs as shown in the table below.
Note: Parameters d1-19 through d1-26 are displayed only if d1-18 is set to 1 or 2.
Multi-Speed
Reference 1
0
1
0
1
0
1
1
0
0 = Off, 1 = On
Digital Inputs
Multi-Speed
Reference 2
0
0
1
0
1
1
1
0
Multi-Speed
Reference 3
0
0
0
1
1
1
0
1
Selected Speed d1-18 = 0 d1-18 = 3
Speed reference 1 (d1-01) Stop
Speed reference 2 (d1-02 or terminal A1, A2 input value if H3-02 or H3-10 is set to
2)
Speed reference 3 (d1-03 or terminal A1, A2 input value if H3-02 or H3-10 is set to
3)
Speed reference 4 (d1-04)
Speed reference 5 (d1-05)
Speed reference 6 (d1-06)
Speed reference 7 (d1-07)
Speed reference 8 (d1-08)
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 83
TOEP_C710616_38H_7_0.book 84 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Setting d1-18 = 0
Up to eight speed references can be set using parameters d1-01 to d1-08. The drive starts with an Up or Down command, and stops when the Up or Down command is removed. When d1-18 = 0, parameters d1-19 through d1-23 will not be displayed.
Setting d1-18 = 3
Allows seven speed references to be set using parameters d1-02 to d1-08. The drive starts with an Up or Down command, and stops either when all three input terminals that set the speed reference are released, or when the Up/Down command is released. When d1-18 = 0, parameters d1-19 through d1-23 will not be displayed.
Separate Speed Inputs (d1-18 = 1 or 2)
Six different speed settings (defined in the parameters d1-19 to d1-24 and d1-26) can be set and selected using four digital inputs.
Speed Selection
When d1-18 = 1 or 2, multi-function digital inputs are preset as shown below.
Terminal
S3
S5
S6
Parameter Number
H1-03
H1-05
H1-06
Set Value
50
51
53
Nominal speed (d1-19)
Intermediate speed
Leveling speed (d1-26)
Details
Different speed settings can be selected depending on the assignment of the speed selection digital inputs (H1 ) as shown in the table below.
Note: Parameters d1-19 through d1-26 are displayed only if d1-18 is set to 1 or 2.
Selected Speed
Nominal Speed (d1-19)
Intermediate Speed 1 (d1-20)
Intermediate Speed 2 (d1-21)
Intermediate Speed 3 (d1-22)
Releveling Speed (d1-23)
Leveling Speed (d1-26)
Zero Speed
Leveling and Nominal Speed assigned
(H1 = 50 and H1 = 53)
50 51 52 53
0
0
1
0
1
0
0
0
1
1
1
0
0
0
0
0
1
1
1
0
0
A
A
A
1
A
A
0
Leveling speed not assigned
(H1 ≠ 53)
50 51 52
0
0
1
0
1
0
N/A
0
1
1
1
0
0
N/A
0
0
1
0
1
1
N/A
0 = Off, 1 = On, A = 0 when d1-18 = 2 and no influence when d1-18 = 1, B = no influence, N/A = Not available
N/A
1
0
B
N/A
Nominal Speed not assigned
(H1 ≠ 50)
51 52 53
0
1
0
0
0
0
N/A
1
1
B
N/A
N/A
0
0
B
N/A
Higher Speed has Priority and the Leveling Speed Input is Assigned (d1-18 = 1 and H1 = 53) (Default)
The higher speed has priority over the leveling speed. The leveling signal is disregarded as long as any other speed selection input is active. The drive decelerates to the leveling speed (d1-26) when the selected speed reference signal is removed.
DC Injection/
Position lock
Speed
Safe disable (terminals H1/H2 on) and Baseblock off (H1 = 8/9)
Up/Down Command
Leveling speed
Selected speed (other than leveling)
DC Injection/
Position lock
Input is set No effect
84 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 85 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Higher Speed Priority is Selected and the Leveling Speed Input is Not Assigned (d1-18 = 1 and H1 ≠ 53)
The drive decelerates to the leveling speed (d1-26) when the selected speed reference signal is removed.
If no speed reference is selected at start, the drive will trigger an “FrL” fault. Set parameter S6-15 to 0 to disable Speed
Reference Missing (FrL) detection. With this setting the drive starts using leveling speed if no other speed reference is selected.
DC Injection/
Position lock
DC Injection/
Position lock
Speed
Safe disable (terminals H1/H2 on) and Baseblock off (H1 = 8/9)
Up/Down Command
Selected speed (other than leveling)
Input is set
Leveling Speed has Priority and the Leveling Speed Input is Assigned (d1-18 = 2, H1 = 53)
The leveling signal has priority over other speed references. The drive decelerates to the leveling speed (d1-26) when the leveling speed selection input is activated. The drive stops when either the leveling input or the Up/Down command is released.
DC Injection/
Position lock
DC Injection/
Position lock
Speed
Safe disable (terminals H1/H2 on) and Baseblock off (H1 = 8/9)
Up/Down Command
Leveling speed
Leveling speed has priority
Selected speed (other than leveling)
Input is set No effect
Leveling Speed Priority is Selected and the Nominal Speed Input is Not Assigned (d1-18 = 2, H1 ≠ 50)
The drive runs at nominal speed (d1-19) when no speed selection input is set. When the leveling speed signal is set, the drive decelerates to the leveling speed. The leveling speed signal has priority over all other speed signals.
NOTICE: Equipment Hazard. This function may not work properly if a broken wire connection to the drive I/O causes improper elevator speed selection. Properly tighten wire connections at the drive terminals before enabling this function.
DC Injection/ position lock
DC Injection/ position lock
Speed
Safe disable (terminals H1/H2 on) and Baseblock off (H1 = 8/9)
Up/Down Command
Leveling speed
Input is set
■
Multi-Function Terminal Setup
Multi-Function Digital Input (Terminals S3 to S8)
The H1 parameters assign functions to digital input terminals S3 to S8 digital input terminal functions, refer to
Multi-Function Digital Inputs on page 183
.
Multi-Function Digital Outputs
The H2 parameters assign functions to digital output terminals M1-M2, M3-M4, M5-M6, P1-C1, and P2-PC digital input terminal functions, refer to
H2: Multi-Function Digital Outputs on page 185 .
Multi-Function Analog Inputs
The H3 parameters assign functions to analog input terminals A1 and A2 analog input functions, refer to
Multi-Function Analog Inputs on page 187
.
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 85
TOEP_C710616_38H_7_0.book 86 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Multi-Function Analog Outputs
The H4 parameters assign functions to analog output terminals FM and AM. Select the function for these terminals by
.
■
Accel/Decel Ramp and Jerk Settings
Acceleration and deceleration ramps are set using the C1 parameters. Use the C2 parameters to adjust the jerk at the start of acceleration or deceleration.
Figure 39 explains how accel/decel ride and jerk settings can be used to adjust the ride profile.
Figure 35
C2-02
(Jerk at
Accel End)
C2-01
(Jerk at
Accel Start)
C1-01
(Accel Ramp 1)
C2-03
(Jerk at
Decel Start)
C2-04
(Jerk at
Decel End) C2-05 (Jerk Below Leveling Speed) d1-26 (Leveling Speed)
C1-02
(Decel Ramp 1)
Figure 39 Accel/Decel Ramp and the Jerk Function
Units used to set the acceleration and deceleration ramp as well as the Jerk function change with the setting of parameter o1-03.
■
Elevator Emergency Stop
Start condition for Elevator Emergency Coast to Stop
An emergency coast to stop is performed when the Up or Down command is cleared and all of the following conditions are met.
• Parameter b1-03 (Stopping Method Selection) is set to 4.
• Parameter d1-18 (Speed Reference Selection Mode) is set to 0 or 3.
• Parameter b1-01 (Speed Reference Selection) is set to 1.
• The Up/Down command is cleared and U1-05 (Speed Feedback) is equal to or greater than S1-26 (Emergency Stop
Start Level).
Elevator Emergency Stop Timing Chart
A timing chart for Elevator Emergency Coast to Stop and normal Ramp to Stop appears in
Figure 36
Selected Speed
Speed
DC Injection Braking/
Position Lock at Start
S1-26
Emergency Stop
Start Level
S1-11
(Output Contactor Open
Delay Time)
Coast to Stop
Up/Down Command
Safe disable (terminals H1/H2 on) or Baseblock off (H1 = 8/9)
H2 = 51 (Output Cont. Contr.)
H2 = 50 (Brake Control)
Enabled
Figure 40 With Up/Down command cleared and U1-05 ≥ S1-26
86 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 87 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Figure 37
Speed
DC Injection Braking/
Position Lock at Start
Up/Down Command
Safe disable (terminals H1/H2 on) or Baseblock off (H1 = 8/9)
H2 = 51 (Output Cont. Contr.)
H2 = 50 (Brake Control)
Selected Speed
S1-26
Emergency Stop
Start Level
S1-05
(DC Injection/Position
Lock Time at stop)
DC Injection/
Position Lock at Stop
S1-07
(Brake Close
Delay Time)
S1-11
(Output Contactor Open
Delay Time)
Enabled
Figure 41 With Up/Down command cleared and U1-05 < S1-26
■
Inspection Operation
Start Condition in Inspection Operation
NOTICE: Always turn off the RUN command before changing the setting of parameters d1-18 (Speed Reference Selection Mode), b1-01 (Speed Reference Selection), or H1 (Multi-Function Digital Inputs). If the RUN command is on when changing any of these settings, the motor may unexpectedly start running, and could result in injury.
Inspection operation is performed when an Up or Down signal is input while one of the following conditions is true:
• Parameter d1-18 is set to 0 or 3 and the selected speed is higher than d1-28 but lower than d1-29.
• Parameter d1-18 is set to 1 or 2 and a digital input programmed for Inspection Operation Speed (H1 = 54) is enabled.
Inspection Operation uses the same acceleration characteristics and brake sequence at start as normal operation.
The carrier frequency is set to 2 kHz during Inspection Operation, but can be changed using parameter C6-21.
Stop Condition in Inspection Operation
To stop the drive during Inspection Operation, either remove the Up or Down command or reset the input terminal for
Inspection Operation.
A deceleration ramp can be set for Inspection Operation using parameter C1-15.
• If C1-15 = 0.00, the drive immediately applies the brake, shuts off the drive output, and opens the motor contactor, i.e., the multi-function output terminals set for “Brake Control” (H2 = 50) and “Output Contactor Control” (H2 =
51) are cleared.
• If C1-15 > 0.00, the drive decelerates to stop at the rate set to C1-15, then applies the brake, shuts the output off, and opens the motor contactor.
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 87
TOEP_C710616_38H_7_0.book 88 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Inspection Operation Timing Chart
A timing chart for Inspection Operation appears in
.
Inspection Operation without Decel Ramp (C1-15 = 0) Inspection Operation with Decel Ramp (C1-15 > 0)
■
Speed
Safe disable (terminals H1/H2 on) and Baseblock off (H1 = 8/9)
H1 = 54 (Inspection Operation)
H2-
Up/Down command
= 51 (Output Cont. Contr.)
H2 = 50 (Brake Control)
Inspection Operation
Speed
DC Injection Braking/
Position Lock at start
<1>
Speed
Safe disable (terminals H1/H2 on) and Baseblock off (H1 = 8/9)
H1 = 54 (Inspection Operation)
H2-
Up/Down command
= 51 (Output Cont. Contr.)
H2 = 50 (Brake Control)
Inspection Operation
Speed
DC Injection Braking/
Position Lock at start
C1-15
<1>
Enabled
<1> The drive stops if either the Up/Down command or Inspection Operation signals are removed.
Figure 42 Inspection Operation Sequence
Brake Sequence
WARNING!
Sudden Movement Hazard. Rapid deceleration may cause the drive to fault on an overvoltage condition, resulting in death or serious injury due to an uncontrolled motor state. Be sure to set an acceptable deceleration time in parameter C1-09, Fast Stop
Ramp, when using the fast-stop feature.
NOTICE: Always turn off the RUN command before changing the setting of parameters d1-18 (Speed Reference Selection Mode), b1-01 (Speed Reference Selection), or H1 (Multi-Function Digital Inputs). If the RUN command is on when changing any of these settings, the motor may unexpectedly start running, and could result in injury.
The drive supports two types of brake sequences, one with torque compensation at start using an analog input terminal
(H3 = 14) and the other without torque compensation at start.
Brake Sequence without Torque Compensation
To configure the brake sequence operation without torque compensation, do not set any analog input terminals for
“Torque compensation” (H3 = 14).
Figure 38
S1-10
(Up/Down Command
Delay Time)
Speed
S1-04
(DC Injection/
PositionLock
Time at Start)
DC Injection Braking/
Position Lock at Start
S1-06
(Brake
Release
Delay
Time)
Selected Speed
S1-11
(Output Contactor
Open Delay Time)
Up/Down Command
Safe disable (terminals H1/H2 on) and Baseblock off (H1 = 8/9)
Output Contactor Control
(H2= 51)
Motor Contactor Response
(H1 = 56)
Brake Control (H2 = 50) d1-26
(Leveling Speed)
S1-05
(DC Injection
Braking/Position
Lock Time at stop)
DC Injection/
Position Lock at Stop
S1-07
(Brake
Close
Delay
Time) t1 t2 t3 t4 t5 t6 t7 t8 t9
Enabled
Figure 43 Brake Sequence without Torque Compensation at Start
88 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 89 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
is divided into time zones.
explains the sequence in each time zone.
Time Zone t1 t2 t3 t4 t5 t6 t7 t8 t9
Table 28 Time Zones for Brake Sequence without Torque Compensation at Start
Description
Up or Down command is issued.
Safe Disable terminals H1-HC and H2-HC must be set and Baseblock must be disabled (digital inputs set to H1 = 8/9).
Speed reference must be selected by multi-function input terminals.
Output contactor control signal is set (H2 = 51) by the drive.
Drive waits for the “Motor Contactor Feedback” signal (H1 = 56) to be issued. If the motor contactor feedback is not received within t1, or if the feedback signal is on before the contactor control command has been issued, an SE1 fault is triggered.
If the motor contactor feedback signal is not used, then the drive waits for the operation start delay time set in S1-10 to pass, then proceeds to the next step.
After the delay time set in S1-10 has passed, the drive outputs current to the motor.
DC Injection Braking or Position Lock begins.
After the brake release delay time set in S1-06 has passed, the drive sets the “Brake Control” output (H2 = 50) in order to release the brake.
DC Injection Braking or Position Lock will continue until: the time S1-04 has elapsed, or the time S1-06 has elapsed if S1-06 > S1-04 (this setting should be avoided since the motor could be driven against the applied brake).
The drive accelerates up to the selected speed. The speed is kept constant until the leveling speed is selected.
Leveling speed is selected. The drive decelerates to the leveling speed and maintains that speed until the Up or Down command is removed.
The Up or Down signal is cleared. The drive decelerates to zero speed.
The motor speed reaches the zero speed level (S1-01).
DC Injection Braking or Position Lock is then executed for the time set in S1-05.
After the delay time to close the brake set in S1-07 has passed, the drive clears the “Brake Control” output (H2 = 50). The brake applies.
The drive continues DC Injection or Position Lock until the time S1-05 has passed. When S1-05 has passed the drive output is shut off.
After the delay for the magnetic contactor set in S1-11 has passed, the drive resets the output terminal set for “Output Contactor
Control” (H2 = 51).
The Safe Disable Inputs can be cleared and Baseblock can be enabled.
Brake Sequence Using Torque Compensation
If a load measuring device is installed in the elevator, an analog input can be used to input a torque compensation value to the drive. This function requires one of the closed loop control modes (CLV or CLV/PM). To use torque compensation, one of the analog input terminals must be configured to provide the torque compensation signal (H3 = 14).
is a timing chart for a brake sequence using torque compensation.
Figure 39
S1-10
(Up/Down Command
Delay Time)
S1-04
(DC Injection/
Position Lock
Time at Start)
Position Lock
Selected Speed
S1-11
(Output Contactor
Open Delay Time)
Speed
Latch value from analog input
Torque Compensation at Start
300%Torque
S3-14 (Torque
Compensation
Diminish Speed)
Torque Compensation
Fades Out with S3-15 at S3-14.
d1-26
(Leveling Speed)
S1-05
(DC Injection
Braking/
Position Lock at stop)
Position Lock
S1-07
(Brake
Close
Delay
Time)
S3-10 (Starting
Torque Compensation
Increase Time)
Up/Down Command
Safe disable (terminals H1/H2 on) and Baseblock off (H1 = 8/9)
Output Contactor Control
(H2 = 51)
Motor Contactor Response
(H1 = 56)
Brake Control (H2 = 50) t1 t2 t3 t4 t5 t6 t7 t8 t9
Enabled
Figure 44 Brake Sequence Using Torque Compensation at Start
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 89
TOEP_C710616_38H_7_0.book 90 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
is divided into time zones. Table 29 explains the sequence in each time zone.
Table 29 Time Zones for Brake Sequence Using Torque Compensation at Start
Time Zone t1 t2 t3 t4 t5 t6 t7 t8 t9
Description
Up or Down command is issued.
Safe Disable terminals H1-HC and H2-HC must be set and Baseblock must be disabled (digital inputs set to H1 = 8/9).
Speed reference must be selected by multi-function input terminals.
Output contactor control signal is set (H2 = 51) by the drive.
Drive waits for the “Motor Contactor Feedback” signal (H1 = 56) to be issued. If the motor contactor feedback is not received within t1, or if the feedback signal is on before the contactor control command has been issued, an SE1 fault is triggered.
If the motor contactor feedback signal is not used, then the drive waits for the operation start delay time set in S1-10 to pass, then proceeds to the next step.
The drive reads the torque value from the analog input (load cell).
After the delay time set in S1-10 has passed, the drive outputs current to the motor. Position Lock begins.
The torque value from the analog input is latched and internal torque compensation value is increased from zero to the latched value using the time constant set in S3-10.
After the internal torque compensation level reaches the latched value, the drive sets the “Brake Control” output (H2 = 50) in order to release the brake.
The brake is released and the drive executes Position Lock until the time set in S1-04 has passed.
The drive accelerates up to the selected speed.
After the torque compensation diminish speed level (S3-14) is reached during acceleration, the internal torque compensation value is reduced in accordance with the time constant set in S3-10.
Leveling speed is selected. The drive decelerates to the leveling speed and maintains that speed until the Up or Down command is removed.
The Up or Down signal is cleared. The drive decelerates to zero speed.
The motor speed reaches the zero speed level (S1-01).
DC Injection Braking or Position Lock is then executed for the time set in S1-05.
After the delay time to close the brake set in S1-07 has passed, the drive clears the “Brake Control” output (H2 = 50). The brake applies.
The drive continues DC Injection or Position Lock until the time S1-05 has passed. When S1-05 has passed the drive output is shut off.
After the delay for the magnetic contactor set in S1-11 has passed, the drive resets the output terminal set for “Output Contactor
Control” (H2 = 51).
The Safe Disable Inputs can be cleared and Baseblock can be enabled.
Adjusting the Torque Compensation at Start
CAUTION!
Set all motor-related parameters (the E parameters) and perform a test run before fine-tuning the torque compensation at start. Adjusting the torque compensation prematurely may result in faulty performance.
To use torque compensation at start, apply at least 50% of the maximum weight to the elevator car and set the drive according to the Load Condition 2 procedure below. If using a voltage signal to the analog input terminals as a load sensor, then that input signal will determine the rate of torque compensation applied according to S3-27 and S3-28.
Before the torque compensation function can be used, the analog input scaling must be adjusted to the load sensor output.
This can be done by bringing the elevator into two different load conditions and teaching the corresponding analog input value and torque reference value to the drive.
Note: 1.
This torque compensation requires a closed loop control mode (CLV, CLV/PM).
2.
The torque compensation value is limited to 120%.
90 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 91 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Set an analog input terminal for torque compensation (H3 = 14) and proceed with the steps below.
Procedure for Load Condition 1 (S3-27, S3-29)
1.
Make sure the drive is wired properly. For instructions, refer to
Standard Connection Diagram on page 25 .
2.
Set the speed reference to 0%.
3.
Apply no weight to the elevator car.
4.
Note the value of the analog input monitor for the load signal input is connected to (U1-13 for terminal A1, U1-14 for terminal A2).
5.
Provide an elevator Up or Down command, using Inspection Operation or normal operation mode. The car should be held in place when the brake releases.
6.
Note the drives internal torque reference monitor U1-09.
7.
Stop the drive.
8.
Set the value noted in step 4 to parameter S3-29. Set the value noted in step 6 to parameter S3-27.
Procedure for Load Condition 2 (S3-28, S3-30)
1.
Set the speed reference to 0%.
2.
Apply load to the car has much as possible (at least 50% of the maximum weight).
3.
Note the value of the analog input monitor for the load signal input connected to (U1-13 for terminal A1, U1-14 for terminal A2).
4.
Provide an elevator Up or Down command, using Inspection Operation or normal operation mode. The car should be held in place when the brake releases.
5.
Note the drives internal torque reference monitor U1-09.
6.
Stop the drive.
7.
Set the value noted in step 3 to parameter S3-30. Set the value noted in step 5 to parameter S3-28.
shows the Torque Compensation at Start settings with parameters S3-27 to S3-30.
The solid line in
Figure 45 indicates the torque compensation at start when the elevator moves up or down.
Figure 40
Torque Compensation Value
S3-28
(Torque Compensation
Value with Load Condition 2)
During Load Condition 2
S3-29
(Analog Input from
Load Sensor with Load
Condition 1)
0
S3-27
(Torque Compensation Value with Load Condition 1)
During Load Condition 1
S3-30
Analog Input Voltage (V)
(Analog input from Load Sensor with Load Condition 2)
Figure 45 Torque Compensation at start for the Elevator in Up and Down Direction
Note: PRG: 7015 or earlier will apply a limit at 0 V torque compensation input value.
PRG: 7016 or later have no torque compensation limit when adding negative voltage to analog input voltage (see
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 91
TOEP_C710616_38H_7_0.book 92 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
After setting load conditions 1 and 2, perform a trial run. If required, parameter S3-12 can be set up to add a bias to the load sensor input when riding in a Down direction (default: 0.0%, same torque compensation characteristics in up and
S3-30.
Figure 41
S3-28
(Torque Compensation
Value with Load Condition 2)
Torque Compensation at Start for the Elevator in the Down Direction
0
S3-29
(Analog Input from Load Sensor with Load
Condition 1)
During Load Condition 2
Torque Compensation at Start for the Elevator in the Up Direction
S3-12 (Starting Torque
Compensation Bias during Lowering)
S3-30
(Analog input
Analog Input Voltage (V) from Load Sensor with Load Condition 2)
S3-27
(Torque Compensation Value with Load Condition 1)
During Load Condition 1
Figure 46 Torque Compensation at start for the Elevator in Up and Down Direction
92 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 93 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
◆
S: Elevator Parameters
This section describes various functions and faults needed to operate an elevator application: braking sequence, slip compensation, optimal adjustments at start and stop, Rescue Operation, and elevator-related faults.
■
S1-01: Zero Speed Level at Stop
Determines the speed to begin applying DC Injection (or Position Lock) when the drive is ramping to stop (b1-03 = 0).
Set as a percentage of the maximum output frequency (E1-04).
No.
S1-01
Parameter Name
Zero Speed Level at Stop
Setting Range
0.000 to 9.999%
Default
Determined by A1-02
The function set by S1-01 changes depending on the control mode:
• V/f Control or OLV Control (A1-02 = 0, 2)
For these control modes, parameter S1-01 sets the starting speed for DC Injection Braking at stop. Once the output speed falls below the setting of S1-01, the amount of DC Injection Braking current set in S1-03 is injected into the motor for the time set in parameter S1-05.
• CLV Control or CLV/PM Control (A1-02 = 3, 7)
For these control modes, parameter S1-01 sets the starting speed for Position Lock at stop. Once the motor speed falls below the setting of S1-01, Position Lock is enabled for the time set in parameter S1-05.
■
S1-02: DC Injection Current at Start
Determines the amount of current to use for DC Injection at start. Set as a percentage of the drive rated current.
No.
S1-02
Parameter Name
DC Injection Current at Start
Setting Range
0 to 100%
Default
50%
■
S1-03: DC Injection Current at Stop
Determines the amount of current to use for DC Injection at stop. Set as a percentage of the drive rated current. When using OLV Control, the DC injection current is determined by multiplying S1-03 by S3-25 or S3-26.
No.
S1-03
Parameter Name
DC Injection Current at Stop
Setting Range
0 to 100%
Default
50%
■
S1-04: DC Injection / Position Lock Time at Start
Determines how long the drive should perform DC Injection at start. In CLV and CLV/PM, S1-04 determines how long
Position Lock should be performed. During this time, the drive allows motor flux to develop, which is essential for applying torque quickly once the brake is released. A setting of 0.00 disables S1-04.
No.
S1-04
Parameter Name
DC Injection / Position Lock Time at Start
Setting Range
0.00 to 10.00 s
Default
0.40 s
■
S1-05: DC Injection / Position Lock Time at Stop
Determines how long the drive should perform DC Injection at stop. In CLV and CLV/PM, S1-05 determines how long
Position Lock should be performed. A setting of 0.00 disables S1-05.
4
No.
S1-05
Parameter Name
DC Injection / Position Lock Time at Stop
Setting Range
0.00 to 10.00 s
Default
0.60 s
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 93
TOEP_C710616_38H_7_0.book 94 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
S1-06: Brake Release Delay Time
Determines the time that must pass after an Up/Down command is entered before the output terminal set for “Brake control” (H2 = 50) is triggered.
Adjusting this delay time can help when there is not enough time to develop the appropriate amount of motor flux. Be sure to also increase the time S1-04 when setting S1-06 to relatively long delay time.
No.
S1-06
Parameter Name
Brake Release Delay Time
Setting Range
0.00 to 10.00 s
Default
0.20 s
■
S1-07: Brake Close Delay Time
Determines the time that must pass after zero speed is reached before the output terminal set for "Brake control"
(H2 = 50) is released.
No.
S1-07
Parameter Name
Brake Close Delay Time
Setting Range
0.00 to [S1-05]
Default
0.10 s
■
S1-10: Run Command Delay Time
Sets the time the drive waits after receiving an Up/Down command before starting operation. The time set should give the motor contactor enough time to close.
No.
S1-10
Parameter Name
Run Command Delay Time
Setting Range
0.00 to 1.00 s
Default
0.10 s
■
S1-11: Output Contactor Open Delay Time
Determines the time that must pass for an output terminal set for “Output contactor control” (H2 = 51) to be released after the drive has stopped and drive output has been shut off.
No.
S1-11
Parameter Name
Output Contactor Open Delay Time
Setting Range
0.00 to 1.00 s
Default
0.10 s
■
S1-12: Motor Contactor Control During Auto-Tuning Selection
Note: Available in drive software PRG: 7016 or later.
Determines the state of the output contactor control command (H2 = 51) during Auto-Tuning. The contactor closes as soon as the Enter key is pressed in the Auto-Tuning start menu.
No.
S1-12
Parameter Name
Motor Contactor Control during Auto-Tuning
<1> Setting 2 is available in drive software versions PRG: 7017 or later.
<2> The setting is 0 or 1 for software version PRG: 7016.
Setting Range
Default
0
Setting 0: Disabled
Setting 1: Enabled
Setting 2: Enabled during Auto-Tuning and HBB
WARNING!
Sudden Movement Hazard. Use parameter S1-12 to enable/disable automatic switching of the Motor Contactor Control output signal during Auto-Tuning. When using setting S1-12 = 1 or 2, ensure that the multi-function output terminals are properly wired and in the correct state before setting parameter S1-12. Failure to comply could result in damage to the drive, serious injury or death.
94 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 95 ページ 2015年11月11日 水曜日 午後7時40分
No.
S1-26
Parameter Name
Emergency Stop Start Level
■
S2-01: Motor Rated Speed
Sets the rated speed of the motor.
4 Start-Up Programming & Operation
■
S1-26: Emergency Stop Start Level
Note: Available in drive software PRG: 7017 or later.
Sets the Emergency Stop Start Level as a percentage of the Maximum Output Frequency. This setting is available when the control mode is set to Closed Loop Vector Control (A1-02 = 3) or Closed Loop Vector Control for PM Motors (A1-02
= 7) and the stopping method is set to Elevator Emergency Stop (b1-03 = 4).
The drive coasts to a stop after the Up/Down command is cleared and when the value of U1-05 (Speed Feedback) is equal to or greater than the value of S1-26 (Emergency Stop Start Level).
The drive ramps to a stop after the Up/Down command is cleared and when the value of U1-05 (Speed Feedback) is lower than the value of S1-26 (Emergency Stop Start Level).
Setting Range
0.0 to 100.0%
Default
10.0%
No.
S2-01
Parameter Name
Motor Rated Speed
Setting Range
300 to 1800 rpm
Default
1380 rpm
■
S2-02/S2-03: Slip Compensation Gain in Motoring Mode / Regenerative Mode
Slip compensation for leveling speed can be set separately for motoring and regenerative states to help improve the accuracy of leveling.
No.
S2-02
S2-03
Parameter Name
Slip Compensation Gain in Motoring Mode
Slip Compensation Gain in Regenerative Mode
■
S2-05: Slip Compensation Torque Detection Delay Time
Sets a delay time before detecting torque for slip compensation.
Setting Range
0.0 to 5.0
0.0 to 5.0
Default
0.7
1.0
No.
S2-05
Parameter Name
Slip Compensation Torque Detection Delay Time
Setting Range
0 to 10000 ms
■
S2-06: Slip Compensation Torque Detection Filter Time Constant
Sets the filter time constant applied to the torque signal used for the slip compensation value calculation.
Default
1000 ms
No.
S2-06
Parameter Name
Slip Compensation Torque Detection Filter Time Constant
Setting Range
0 to 2000 ms
Default
500 ms
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 95
TOEP_C710616_38H_7_0.book 96 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
S3-01 / S3-02: Position Lock Gain at Start 1 / 2
Sets gain levels 1 and 2 for the Position Lock at start function. Position Lock at start adjusts the internal torque reference value depending on the position deviation to hold the car in place when the brake is released. S3-01 sets the gain used to adjust the speed reference During Position Lock. S3-02 sets gain to adjust the internal torque reference directly
(Anti-Rollback function).
Increase S3-01 and S3-02 if there is a problem with rollback when the brake is released. Decrease S3-01 and S3-02 if motor oscillation occurs during Position Lock.
No.
S3-01
S3-02
Parameter Name
Position Lock Gain at Start 1
Position Lock Gain at Start 2 (Anti-Rollback Gain)
Setting Range
0 to 100
0.00 to 100.00
Default
5
0.00
Note: 1.
Check the C5 parameters to make sure the speed control loop settings are correct before making any adjustments to the Position
Lock gain.
2.
Sometimes a fault may occur with detecting the direction of motor rotation (dv4) when using Closed Loop Vector for PM motors. To correct this, either increase the settings of S3-01 and S3-02, or increase the number of pulses needed to trigger dv4 (F1-19).
■
S3-03: Position Lock Gain at Stop
Sets the gain used by the Position Lock control loop at stop to hold the car in place while the brake is applied.
Setting S3-03 to a high value will increase the ability of the drive to hold the car in place. Setting S3-03 too high can cause motor oscillation and car vibration.
No.
S3-03
Parameter Name
Position Lock Gain at Stop
Setting Range
0 to 100
Default
5
Note: 1.
Check the C5 parameters to make sure the speed control loop settings are correct before making any adjustments to the Position
Lock gain.
2.
Faults may occur when detecting the direction of motor rotation (dv4) when using CLV/PM. To correct this, either increase the settings of S3-01 and S3-02, or increase the number of pulses required to trigger dv4 (F1-19).
■
S3-04: Position Lock Bandwidth
Determines the bandwidth around the locked position to enable a digital output set for H2 = 33 (within position lock bandwidth). The output will be triggered when the car moves from the Position Lock start point to plus or minus the number of pulses set to S3-04.
No.
S3-04
Parameter Name
Position Lock Bandwidth
Setting Range
0 to 16383
Default
10
■
S3-10: Starting Torque Compensation Increase Time
Sets a time constant for the torque reference to reach 300%. Enabled by setting an analog input terminal for torque compensation (H3 = 14).
No.
S3-10
Parameter Name
Starting Torque Compensation Increase Time
■
S3-12: Starting Torque Compensation Bias in Down Direction
Adds a bias to torque compensation in the Down direction.
Refer to
Adjusting the Torque Compensation at Start on page 90 for details.
Setting Range
0 to 5000 ms
Default
500 ms
No.
S3-12
Parameter Name
Starting Torque Compensation Bias in Down Direction
Setting Range
–40.0 to 40.0%
Default
0.00%
96 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 97 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
S3-14: Torque Compensation Diminish Speed
Sets the speed level for torque compensation to diminish during the time determined by S3-15. Set as a percentage of the maximum output frequency (E1-04). A setting of 0.0% disables this function.
No.
S3-14
Parameter Name
Torque Compensation Diminish Speed
Setting Range
0.0 to 200.0%
■
S3-15: Torque Compensation Diminish Time
Sets the time for torque compensation to diminish when motor speed reaches the level set in S3-14.
Default
0.0%
No.
S3-15
Parameter Name
Torque Compensation Diminish Time
Setting Range
0 to 5000 ms
Default
1000 ms
■
S3-16: Torque Limit Reduction Time
After Position Lock at stop, S3-16 determines the length of time to reduce the torque limit rate =
Torque 300%
S3-16
Setting Range
0 to 10000 ms
Default
100 ms
No.
S3-16
Parameter Name
Torque Limit Reduction Time
■
S3-20: Dwell 2 Speed Reference
Sets the speed reference for the Dwell 2 function.
Note: Setting this parameter to 0.00 disables the Dwell 2 function.
No.
S3-20
Parameter Name
Dwell 2 Speed Reference
Setting Range
0.00 to 100.00%
Default
0.00%
Figure 42
Run Command
ON
C1-01
SFS output
Motor speed
C1-07
C2-01
S3-21
S3-20
Figure 47 Dwell Speed Reference at Start
■
S3-21: Dwell 2 End Speed
The Dwell 2 function will end when the drive reaches this speed. A setting of 0.00 will disable the acceleration rate switch that occurs at the end of Dwell 2.
4
No.
S3-21
Parameter Name
Dwell 2 End Speed
Setting Range
0.00 to 100.00%
Default
0.00%
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 97
TOEP_C710616_38H_7_0.book 98 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
S3-25: DC Injection Gain in Regenerative Operation
In OLV Control, S3-25 sets a gain level for DC Injection at stop (S1-03) for when the regenerative load reaches 100%. At that time, the current applied during DC Injection at stop is determined as S1-03 × S3-25.
No.
S3-25
Parameter Name
DC Injection Gain in Regenerative Operation
Setting Range
0 to 400%
Default
100%
■
S3-26: DC Injection Gain in Motoring Operation
In OLV Control, S3-26 sets a gain level for DC Injection at stop (S1-03) when the motoring load reaches 100%. At that time, the current applied during DC Injection at stop is determined as S1-03 × S3-26.
No.
S3-26
Parameter Name
DC Injection Gain in Motoring Operation
Setting Range
0 to 400%
Default
20%
■
S3-27: Torque Compensation Value with Load Condition 1
Adjusts the analog signal from a load sensor for torque compensation. Refer to
Adjusting the Torque Compensation at
No.
S3-27
Parameter Name
Torque Compensation Value with Load Condition 1
Setting Range
-100.0 to 100.0%
Default
-50.0%
■
S3-28: Torque Compensation Value with Load Condition 2
Adjusts the analog signal from a load sensor for torque compensation. Refer to
Adjusting the Torque Compensation at
No.
S3-28
Parameter Name
Torque Compensation Value with Load Condition 2
Setting Range
-100.0 to 100.0%
Default
50.0%
■
S3-29: Analog Input from Load Sensor with Load Condition 1
Adjusts the analog signal from a load sensor for torque compensation. Refer to
Adjusting the Torque Compensation at
No.
S3-29
Parameter Name
Analog Input from Load Sensor with Load Condition 1
Setting Range
-100.0 to 100.0%
Default
0.0%
■
S3-30: Analog Input from Load Sensor with Load Condition 2
Adjusts the analog signal from a load sensor for torque compensation. Refer to
Adjusting the Torque Compensation at
No.
S3-30
Parameter Name
Analog Input from Load Sensor with Load Condition 2
Setting Range
-100.0 to 100.0%
Default
100.0%
■
S3-34: Anti-Rollback Torque Bias 1
Sets an intermediary value for the torque bias used for Anti-Rollback when Position Lock at start is performed. This setting rarely needs to be changed.
No.
S3-34
Parameter Name
Anti-Rollback Torque Bias 1
Setting Range
0.0 to 100.0%
Default
0.0%
98 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 99 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
S3-35: Anti-Rollback Torque Bias 2
Sets a maximum value for the torque bias used for Anti-Rollback when Position Lock at start is performed. This setting rarely needs to be changed.
No.
S3-35
Parameter Name
Anti-Rollback Torque Bias 2
Setting Range
0.0 to 100.0%
Default
0.0%
■
S3-37: Position Deviation Level to Apply Anti-Rollback Torque Bias 1
Sets the position deviation level to activate at Anti-Rollback Torque Bias 1 (S3-34). This setting rarely needs to be changed.
No.
S3-37
Parameter Name
Position Deviation Level to Apply Anti-Rollback Torque Bias 1
Setting Range
0 to 32767
Default
0
■
S3-38: Position Deviation Level to Apply Anti-Rollback Torque Bias 2
Determines the position deviation level when the drive should switch from the Anti-Rollback torque bias set in S3-34 to the torque bias set in S3-35. This setting rarely needs to be changed.
No.
S3-38
Parameter Name
Position Deviation Level to Apply Anti-Rollback Torque Bias 2
Setting Range
0 to 32767
Default
0
■
S3-39: Anti-Rollback Integral Gain
Determines the drive responsiveness for Anti-Rollback during Position Lock.
Increasing the value set to S3-39 may help if there is still too much deviation from the Position Lock start position after
Position Lock gain 1 and gain 2 have already been adjusted. Lower S3-39 if oscillation occurs. This parameter rarely needs to be changed.
No.
S3-39
Parameter Name
Anti-Rollback Integral Gain
■
S3-40: Anti-Rollback Movement Detection
Sets the amount of speed feedback signal pulses to detect a movement of the rotor.
Setting Range
-30.00 to 30.00
Default
0.00
No.
S3-40
Parameter Name
Anti-Rollback Movement Detection
Setting Range
0 to 100 pulses
Default
1 pulse
■
S3-41: Position Lock Gain at Start 2 Reduction
Sets a reduction factor for the Position Lock Gain at Start 2 (Anti Rollback Gain) set in parameter S3-02.
If the motor rotation (i.e., car movement) is below the movement detection level set to S3-40, the drive will reduce the
Anti-Rollback gain according to the gain reduction level set in S3-41.
No.
S3-41
Parameter Name
Position Lock Gain at Start 2 Reduction
Setting Range
0.00 to 1.00
0.50
Default
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 99
TOEP_C710616_38H_7_0.book 100 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
S4-01: Light Load Direction Search Selection
Enables and disables the Light Load Direction Search.
No.
S4-01
Parameter Name
Light Load Direction Search Selection
Setting 0: Disabled
Setting 1: Enabled
Setting 2: Enabled for motor 1 only
■
S4-02: Light Load Direction Search Method
Determines the method used to perform Light Load Direction Search.
Setting Range
0 to 2
No.
S4-02
Parameter Name
Light Load Direction Search Method
Setting 0: Output current
Setting 1: Detect direction of regeneration
■
S4-03: Light Load Direction Search Time
Sets the time to perform Light Load Direction Search.
No.
S4-03
Parameter Name
Light Load Direction Search Time
■
S4-04: Light Load Direction Search Speed Reference
Sets the speed reference to use during Light Load Direction Search.
No.
S4-04
Parameter Name
Light Load Direction Search Speed Reference
■
S4-05: Rescue Operation Torque Limit
Sets the torque limit used during Rescue Operation.
Setting Range
0 or 1
Setting Range
0.0 to 5.0 s
Setting Range
0.00 to 20.00%
No.
S4-05
Parameter Name
Rescue Operation Torque Limit
Setting Range
0 to 300%
■
S4-06: Rescue Operation Power Supply Selection
Specifies the type of backup power supply the drive should switch to when the power goes out.
No.
S4-06
Parameter Name
Rescue Operation Power Supply Selection
Setting 0: Battery
Setting 1: UPS (single-phase)
Setting 2: UPS (three-phase)
Setting Range
0 to 2
Default
0
Default
1
Default
1.0 s
Default
Determined by A-02
Default
100%
Default
0
100 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 101 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
S4-07: UPS Power
Sets the capacity of the UPS.
No.
S4-07
Parameter Name
UPS Power
Setting Range
0.0 to 100.0 kVA
Default
0.0 kVA
■
S4-08: UPS Operation Speed Limit Selection
Determines how a speed limit should be applied to the Rescue Operation speed (S4-15) when operating from a UPS. The drive calculates the appropriate speed limit based on the UPS capacity set in S4-07. This speed limit helps prevent voltage saturation and motor stall during Rescue Operation.
No.
S4-08
Parameter Name
UPS Operation Speed Limit Selection
Setting 0: Disabled
Setting 1: Enabled until Light Load Direction Search is complete
Setting 2: Enabled until stop
■
S4-12: DC Bus Voltage during Rescue Operation
Sets the DC bus voltage during Rescue Operation.
Setting Range
0 to 2
Default
2
No.
S4-12
Parameter Name
DC Bus Voltage during Rescue Operation
Setting Range
0 to 1150 V
Default
0 V
■
S4-13: Rescue Operation Power Supply Deterioration Detection Level
Determines at which level of backup power supply deterioration a PF5 fault is triggered. The following conditions will trigger PF5:
• During Rescue Operation, DC bus voltage < [S4-12 × (S4-13 – 10%)]
• 100 ms after Rescue Operation has been triggered, the DC bus voltage does not rise above S4-12 × S4-13 before the motor starts
No.
S4-13
Parameter Name
Rescue Operation Power Supply Deterioration Detection Level
■
S4-15: Speed Reference Selection at Rescue Operation
Note: Available in drive software PRG: 7016 or later.
Selects the speed reference used for Rescue Operation.
Setting Range
10 to 100%
Default
80%
No.
S4-15
Parameter Name
Speed Reference Selection for Rescue Operation
Setting Range
0, 1
Setting 0: The setting of parameter d1-25 is used as speed reference for Rescue Operation
Setting 1: The speed selected by digital inputs is used as speed reference
Default
0
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 101
TOEP_C710616_38H_7_0.book 102 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
Short Floor Function
Short Floor automatically adjusts the speed in order to reduce the leveling time if leveling speed was activated before the selected speed was reached. Short Floor is enabled setting S5-01 = 1. The drive calculates the distance to decelerate from rated speed to the leveling speed, then controls the stop so that the stopping time is shortened. In
below, area S indicates the distance for a stop from nominal speed.
Figure 43
Speed d1-19 (nominal speed)
S nominal speed × 0.4
d1-26 (leveling speed) <1>
0 t
Figure 48 Speed During Normal Operation
<1> The drive will recognize the speed reference that is lower than the Leveling Speed Detection Level (d1-28) as the leveling speed if the speed priority is set for multi-step speed reference (d1-18 = 0 or 3).
Advance Short Floor
Advanced Short Floor minimizes the operation time to arrive at a designated floor. It uses the leveling speed once the leveling speed command is entered via one of the multi-function inputs (H1 = 53). Advance Short Floor calculates optimal speed based on the Short Floor Minimum Constant Speed Time (S5-03) and the currently selected deceleration rate.
102 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 103 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
explains the Short Floor and Advance Short Floor functions.
Table 30 Short Floor Operation Example
Leveling
Speed Input
Timing
Short Floor Advanced Short Floor
Constant speed operation at rated speed
(normal stop sequence)
0
Time d1-26
(Leveling Speed)
H1 = 53
(Leveling Speed) <1>
(The speed is 40% of the nominal speed or more.)
Operating speed d1-19
(Nominal Speed)
0
Time
40% of nominal speed d1-26
(Leveling Speed)
H1 = 53
(Leveling Speed )
<1>
ON(close)
ON(close)
H1-
(The speed is over Optimum Speed.)
Operating speed
= 53
0
( Leveling Speed ) <1>
ON (close)
During acceleration
Operating speed d1-19
(Nominal Speed)
(The speed is optimal speed or less.)
Operating speed
S5-03
(The speed is less than 40% of the nominal speed.)
Operating speed d1-19
(Nominal Speed)
40% of nominal speed
0 d1-26
(Leveling Speed)
Time
H1 = 53
(Leveling Speed) <1>
ON(close)
0
H1 = 53
(Leveling Speed ) <1>
ON (close) d1-19
(Nominal Speed)
Optimal Speed
Time d1-26
(Leveling Speed) d1-19
(Nominal Speed)
Optimal Speed
Time d1-26
(Leveling Speed)
Constant speed operation at less than the rated speed
(The speed is 40% of the nominal speed or more.)
Operating speed
0 d1-19
(Nominal Speed)
40% of nominal speed d1-26
(Leveling Speed)
Time
H1 = 53
(Leveling Speed) <1>
ON(close)
(The speed is less than 40% of the nominal speed.)
Operating speed d1-19
(Nominal Speed)
Not Available.
0
40% of nominal speed d1-26
(Leveling Speed)
Time
H1 = 53
( Leveling Speed ) <1>
ON(close)
Before start Operates at the leveling speed.
<1> The drive will recognize the speed reference that is lower than the Leveling Speed Detection Level (d1-28) as the leveling speed if the speed priority is set for multi-step speed reference (d1-18 = 0 or 3).
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 103
TOEP_C710616_38H_7_0.book 104 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
S5-01: Short Floor Operation Selection
Enables and disables the Short Floor function.
Note: 1.
The Short Floor and Advanced Short Floor functions cannot be used during Rescue Operation.
2.
Do not use Short Floor or Advanced Short Floor when the analog input terminals are configured to supply the speed reference.
3.
The drive will accelerate or decelerate to the specified speed reference at the specified Accel/Decel rate if the speed priority is set for multi-step speed reference (d1-18 = 0 or 3) and the leveling speed reference is selected during Short Floor or Advanced Short Floor.
No.
S5-01
Parameter Name
Short Floor Operation Selection
Setting Range
0 to 2
Default
0
Setting 0: Disabled
Setting 1: Enabled (Short Floor Operation)
Setting 2: Enabled (Advanced Short Floor Operation)
■
S5-02: Nominal Speed for Short Floor Calculation
Determines the rated speed used to calculate the distance for the Short Floor function when speed priority is set for
Multi-step Speed Reference (d1-18 = 0 or 3).
No.
S5-02
Parameter Name
Nominal Speed for Short Floor Calculation
Setting Range
0.0 to 100.0%
Default
0.0%
■
S5-03: Short Floor Minimum Constant Speed Time
Sets the minimum time of the constant speed operation when the Advanced Short Floor function is enabled (S5-01 = 2).
No.
S5-03
Parameter Name
Short Floor Minimum Constant Speed Time
Setting Range
0 to 2.0 s
Default
0.0 s
■
S5-04: Distance Calculation Acceleration Time Gain
Sets the gain used to adjust the jerk at acceleration for an optimum speed calculation when Short Floor Operation
Selection (S5-01) is set to 2.
• Increase the gain level set to S5-04 and S5-05 if the leveling time is too short or if the optimum speed calculated by the drive is too fast.
• Decrease the gain level set to S5-04 and S5-05 if the leveling time is too long or if the optimum speed calculated by the drive is too slow.
No.
S5-04
Parameter Name
Distance Calculation Acceleration Time Gain
Setting Range
50.0 to 200.0%
Default
150.0%
Note: Setting S5-04 too low may trigger an overrun due to faster optimum speeds and shortened leveling times. Avoid setting this gain less than 100%.
■
S5-05: Distance Calculation Deceleration Time Gain
Sets the gain used to adjust the jerk at deceleration and optimum speed calculation when Short Floor Operation Selection
(S5-01) is set to 2.
• Increase the gain level set to S5-04 and S5-05 if the leveling time is too short or if the optimum speed calculated by the drive is too fast.
• Decrease the gain level set to S5-04 and S5-05 if the leveling time is too long or if the optimum speed calculated by the drive is too slow.
No.
S5-05
Parameter Name
Distance Calculation Deceleration Time Gain
Setting Range
50.0 to 200.0%
Default
150.0%
Note: Setting S5-05 too low may trigger an overrun due to faster optimum speeds and shortened leveling times. Avoid setting this gain less than 100%.
104 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 105 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
Leveling Distance Control
Leveling Distance Control uses the accel/decel rate, jerk settings, and stopping distance to automatically calculate a speed sequence and arrive at the designated floor with increased accuracy. Two types of Leveling Distance Control are available that allow the user to select the Stopping Method (S5-10).
WARNING!
Inadvertent Movement Hazard. The elevator will not stop at the designated location and an overrun will occur which may cause injury to personnel if parameters o1-20, S5-11, and S5-12 are set incorrectly. Before using Leveling Distance Control, make sure that parameters for Traction Sheave Diameter (o1-20), Deceleration Distance (S5-11) and the Stop Distance (S5-12) are set to the correct units.
Note: Leveling Distance Control should be used only for elevators with a constant stopping distance. Do not use Leveling Distance
Control in elevators where the stopping distance changes frequently.
The following functions are disabled when Leveling Distance Control is selected:
• Switching between deceleration times
• Droop Control (b7 parameters)
• Shoot Floor, Advanced Short Floor (S5-01 = 1, 2)
Leveling Distance Control is disabled when any one of the following functions are selected:
• Analog frequency reference
• Rescue Operation
• Inspection Operation
• During Motor 2 selection
Direct Landing
Direct Landing (S5-10 = 1) is activated at the start of deceleration, and brings the elevator car to the designated floor without the use of the leveling speed.
Direct Landing disables Leveling Distance Control, and uses a speed reference calculated by multiplying E1-04 times
S5-13. If a Stop distance correction command (H1 = 5C) is triggered during Direct Landing, then the drive will switch to the stop distance set in S5-12 for the remaining distance. Direct Landing will end once data from the encoder indicates that the stopping distance is 0.
illustrates a Direct Landing Operation example.
Table 31 Conditions for Direct Landing
Speed Priority
Multi-step speed sequence
(d1-18 = 0, 3)
High speed reference has priority
(d1-18 = 1)
Leveling speed reference has priority
(d1-18 = 2)
Direct Landing Start Conditions
Speed reference ≥ E1-04 × S5-13 and the Up/Down command is not active or the speed reference is
0.
The Up/Down command is not active, the speed reference is 0, or the leveling speed reference has been selected by one of the multi-function input terminals (H1 ).
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 105
TOEP_C710616_38H_7_0.book 106 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Run Command
(Forward [Up] / Reverse [Down])
H1 = 5C
(Stop Distance Correction)
H2 = 51
( Output Contactor Control )
H1 = 56
( Motor Contactor Feedback )
ON
ON
ON
OFF
OFF
Output Contactor Open
Delay Time (S1-11)
Run Command Delay Time (S1-10)
Brake Release Delay Time
( S1-06 )
ON
OFF
H2 = 50 (Brake Control )
Operation
Speed
Brake Close
Delay Time
(S1-07)
Zero Speed at Start
S1 <1>
Zero Speed at Stop
S2
<1>
Time
<1> Area S1 is the deceleration distance (S5-11) from the start of deceleration to stop. Area S2 is the stopping distance (S5-12) from the point at which the stopping distance compensation signal is entered to when the car arrives at the designated floor.
Figure 49 Direct Landing Operation Example
Leveling Distance Control
Leveling Distance Control (S5-10 = 2) uses the leveling speed reference for the remaining distance to arrive at the designated floor. Leveling Distance Control is activated when the conditions listed in
are met.
Table 32 Leveling Distance Control Operation
Speed Priority Selection
Multi-step speed sequence
(d1-18 = 0, 3)
High speed reference has priority
(d1-18 = 1)
Multi-step speed sequence
(d1-18 = 2)
Multi-Function Input Terminal Settings Leveling Distance Control Start Conditions
–
The Up/Down command is not active or the speed reference is 0.
Leveling speed reference is selected
(H1 = 53).
The Up/Down command is not active, or all input terminals set for
H1 = 50 to 53 are open.
Leveling speed reference is not selected
(H1 ≠ 53).
Up/Down command is not active.
Rated speed reference is selected
(H1 = 50).
The Up/Down command is not active, or all input terminals set for
H1 = 50 to 53 are open.
Rated speed reference is not selected
(H1 ≠ 50).
Up/Down command is not active.
106 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 107 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Run Command
(Forward [Up] / Reverse [Down])
H2 = 53 (Not Zero Speed )
H2 = 51
(Output Contactor Control )
H1 = 56
(Motor Contactor Feedback )
ON
OFF
Run Command Delay Time (S1-10)
Brake Release Delay Time
( S1-06 )
ON
ON
ON
ON
OFF
OFF
Output Contactor Open
Delay Time (S1-11)
OFF
H2 = 50 (Brake Control )
Operation
Speed
Brake Close
Delay Time
( S1-07 )
Zero Speed at Stop
Zero Speed at Start
S
<1>
Time
<1> Area S is the stopping distance (S5-12) from the point at which leveling operation is complete to when the car arrives at the designated floor.
Figure 50 Operation Sequence Example for Leveling Distance Control
■
S5-10: Stopping Method Selection
Selects the stopping method.
No.
S5-10
Parameter Name
Stopping Method Selection
Setting Range
0 to 2
Default
0
Setting 0: Disable
Setting 1: Direct Landing
Setting 2: Leveling Distance Control
■
S5-11: Deceleration Distance
for details.
No.
S5-11
Parameter Name
Deceleration Distance
Setting Range
0 to 32767 mm
Default
0 mm
<1> The setting range becomes 0.00 to 650.00 inches when the length units are set for inches (o1-12 = 1).
■
S5-12: Stop Distance
Distance Control on page 106 for details.
No.
S5-12
Parameter Name
Stop Distance
Setting Range
0 to 10000 mm
<1> The setting range becomes 0.00 to 393.00 inches when the length units are set for inches (o1-12 = 1).
Default
0 mm
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 107
TOEP_C710616_38H_7_0.book 108 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
S5-13: Direct Landing Minimum Speed Level
Sets the speed level for the start of Direct Landing. Direct Landing is disabled if the starting speed for Direct Landing is less than the maximum output speed multiplied by this parameter (E1-04 × S5-13).
No.
S5-13
Parameter Name
Direct Landing Minimum Speed Level
Setting Range
0 to 100%
Default
20%
■
S6-01: Motor Contactor Response Error (SE1) Detection/Reset Selection
Determines when the drive should detect a motor contactor response error (SE1). SE1 is triggered if there is no response from the motor contactor within the time set in S6-10 after the contactor control output has been set.
No.
S6-01
Parameter Name
Motor Contactor Response Error (SE1) Detection/Reset Selection
Setting Range
0 to 2
Default
0
Setting 0: Detect during stop, SE1 must be manually reset
Setting 1: Detect during stop, SE1 can be automatically reset
Setting 2: No SE1 detection
■
S6-02: Starting Current Error (SE2) Detection Delay Time
Sets a delay time for starting current error (SE2). SE2 is detected when the drive output current is below 25% after the
Up/Down command has been entered and the brake release time and the time set to S6-02 have both passed. The brake control command will not be issued (brake stays applied).
No.
S6-02
Parameter Name
Starting Current Error (SE2) Detection Delay Time
Setting Range
0.00 to [S1-04 – S1-06]
Default
200 ms
■
S6-03: SE2 Detect Current Level
Note: Available in drive software PRG: 7017 or later.
Sets the level of current applied to the motor when the Brake Control command is activated, as a percentage of the Motor
No-load Current (E2-03). A Starting Current Error (SE2) occurs when the drive’s output current is less than the value in
S6-03 after both the Brake Release Delay Time (S1-06) and the SE2 Detection Delay Time (S6-02) have passed after a
RUN command.
No.
S6-03
Parameter Name
SE2 Detect Current Level
Setting Range
0 to 100%
Default
25%
■
S6-04: Output Current Error (SE3) Detection Delay Time
Sets a delay time for detecting an output current fault (SE3). SE3 is detected when the drive output current drops below
25% after the brake has released.
No.
S6-04
Parameter Name
Output Current Error (SE3) Detection Delay Time
Setting Range
0 to 5000 ms
Default
200 ms
■
S6-05: Brake Response Error (SE4) Detection Time
Sets a delay time for detecting a brake response error (SE4). SE4 is detected when an output terminal set for “Brake release” (H2 = 50) and an input terminal set for “Brake feedback” (H1 = 79) do not match for the time set to
S6-05.
No.
S6-05
Parameter Name
Brake Response Error (SE4) Detection Time
Setting Range
0 to 10000 ms
Default
500 ms
108 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 109 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
S6-10: Overacceleration Detection Level
If the elevator car accelerates at an abnormal rate, the drive triggers an overacceleration fault (dv6) and the motor coasts to stop. Parameter S6-10 determines the acceleration rate that triggers the dv6 fault. A setting of 0.0 m/s 2 disables overacceleration detection.
No.
S6-10
Parameter Name
Overacceleration Detection Level
Setting Range
0.0 to 20.0 m/s 2
Default
1.5 m/s
<1> Default setting is determined by parameter o1-03. If o1-03 is set to 0 through 5, the default is 1.5 m/s2. If o1-03 is set to 6, the default is 5.0 ft/ s 2 (setting range: 0.0 to 50.0 ft/s 2 ).
■
S6-11: Overacceleration Detection Time
Sets the time that the acceleration must exceed the overacceleration detection level before as fault is triggered.
No.
S6-11
Parameter Name
Overacceleration Detection Time
■
S6-12: Overacceleration Detection Selection
Determines the conditions for detecting an overacceleration situation.
Setting Range
0 to 5000 ms
Default
50 ms
No.
S6-12
Parameter Name
Overacceleration Detection Selection
Setting 0: Always enabled
Setting 1: During run only
■
S6-15: Speed Reference Loss Detection
Enabled or disables detection for missing speed reference (FrL).
Setting Range
0 or 1
Default
0
No.
S6-15
Parameter Name
Speed Reference Loss Detection
Setting Range
0 or 1
Default
1
Setting 0: Disabled
Setting 1: Enabled
■
S6-16: Restart after Baseblock Selection
Allows the drive to restart the motor after returning to normal operation from Baseblock state (H1 = 8/9) or from
Safe Torque-Off state (Safe Disable inputs H1 and H2 enabled) while the Up/Down command is still active.
No.
S6-16
Parameter Name
Restart after Baseblock Selection
Setting Range
0 or 1
Default
0
Setting 0: No restart after Baseblock or Safe Torque-Off
Do not restart the motor when leaving the Baseblock or Safe Torque-Off state even if an Up/Down command is still active.
Setting 1: Restart after Baseblock or Safe Torque-Off
Restart when the Up/Down command is still active while the Baseblock or Safe Torque-Off state is left. To use this function with the Safe Disable function, parameter L8-88 must be set to 1.
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 109
TOEP_C710616_38H_7_0.book 110 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
Rescue Operation
In the event of a power outage, Rescue Operation allows the elevator to travel to the nearest floor by switching to a backup battery or UPS (Uninterruptable Power Supply) for power.
An input terminal set for Rescue Operation (H1 = 55) can be used to initiate Rescue Operation. During Rescue
Operation, the drive uses the speed reference set in S4-15 to travel to the nearest floor.
NOTICE: Equipment Hazard. Do not use the Rescue Operation feature for extended periods. Failure to comply may result in drive heat sink overtemperature alarms (oH).
NOTICE: When changing parameters while the drive is supplied from the rescue operation power supply, wait at least 5 s after entering parameters before switching off the power supply. Instantly switching off the power can cause parameter settings corruption that can only be resolved by initializing the drive. This may cause erroneous drive performance.
NOTICE: Always turn off the RUN command before changing the setting of parameters d1-18 (Speed Reference Selection Mode), b1-01 (Speed Reference Selection), or H1 (Multi-Function Digital Inputs). If the RUN command is on when changing any of these settings, the motor may unexpectedly start running, and could result in injury.
Drive Power Supply for Rescue Operation
There are various methods of supplying power to the drive for rescue operation. Independent of the chosen method, the voltage in the DC bus of the drive and the voltage supplied to the drive control circuit must meet the specifications provided in
.
The DC bus voltage can either be supplied by a battery connected to the DC bus terminals of the drive or by a UPS connected to drive terminals L1 and L2. The control circuit voltage can be supplied directly from the drives DC bus (no external wiring required), from an external battery (connection to CN19), or by using an optional 24 Vdc control power backup unit.
When using a single-phase AC power supply for rescue operation such as a single-phase UPS, the ripple in the DC bus voltage will be higher than with a three-phase or battery supply. Make sure that the DC bus voltage never falls below the
minimum value listed in Table 33 .
When using a PM motor with an incremental PG encoder and a PG-X3 option card, always perform Initial Magnet Pole
Search Parameters Auto-Tuning (T2-01 = 3) with the normal power supply connected. The tuning function will prepare the drive for Rescue Operation by automatically setting certain parameters. If the tuning ends with an “End8” to “End10” fault, then rescue operation will require a battery or UPS that supplies the drive DC bus with at least 280 Vdc for 200 V class drives, 560 Vdc for 400 V class drives, and 700 Vdc for 600 V class drives. Alternatively utilize to an absolute PG encoder and a PG-E3 or PG-F3 option card.
If the DC bus voltage is low, the overload protection level (oL2 fault detection level) will be reduced due to the low speed run and the drive overload (oL2) will be triggered. If oL2 is detected, select the battery or UPS so that the output speed is equal to or greater than 6 Hz.
The upper speed limit during rescue operation can be monitored by U4-40.
110 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 111 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Motor Type
Induction Motor
Permanent Magnet
Motor
Table 33 Power Supply Ratings for Rescue Operation
Speed Feedback
Without PG Encoder or
Incremental PG Encoder with
PG-B3 or PG-X3 option card
Incremental PG Encoder with
PG-X3 option card
“End8” to “End10” error occurs during Initial Magnet Pole Search
Auto-Tuning.
Incremental PG Encoder with
PG-X3 option card
No error occurs during Initial
Magnet Pole Search Auto-Tuning.
Absolute PG Encoder with PG-F3 or PG-E3 option card
DC Bus Voltage
200 V class drives: 48 to 340
Vdc
400 V class drives: 48 to 680
Vdc
600 V class drives: 48 to 850
Vdc
200 V class drives: 280 to 340
Vdc
400 V class drives: 560 to 680
Vdc
600 V class drives: 700 to 850
Vdc
200 V class drives: 72 to 340
Vdc
400 V class drives: 144 to 680
Vdc
600 V class drives: 207 to 850
Vdc
200 V class drives: 48 to 340
Vdc
400 V class drives: 48 to 680
Vdc
600 V class drives: 48 to 850
Vdc
Control Circuit Voltage
When supplied from a battery or the drive DC bus:
200 V class drives: 250 to 340 Vdc
400 V class drives: 280 to 680 V (recommended:
500 to 680 Vdc)
600 V class drives: 280 to 850 V (recommended:
720 to 850 Vdc)
When supplied via a 24 Vdc control power backup unit:
200 V, 400 V and 600 V class drives: 24 Vdc
Parameter Setup
Adjust drive parameters as described below when using Rescue Operation.
• Select the type of Rescue Operation power supply for the drives main circuit in parameter S4-06.
• When using a UPS, set the UPS power value to parameter S4-07. Use parameter S4-08 to decide if the Rescue
Operation speed shall be limited automatically depending on the UPS power.
• If deterioration of the battery or UPS shall be detected, also set up parameters S4-12 and S4-13. Measure the DC bus voltage during operation using the rescue power supply and set the measured value to parameter S4-12. Set the deterioration detection level to parameter S4-13.
• Set parameters S4-01 to S4-04 if light load direction search shall be automatically performed when Rescue Operation is started.
Wiring Examples
Switching the main power supply to a battery or UPS requires magnetic contactors that must be controlled by an external controller. Wiring methods and the sequence used for the magnetic contactors depend on the application. This instruction manual describes the following configurations:
• A single-phase, 230 V UPS is used as backup power supply for a 200 V, 400 V or 600 V class drive.
• Two separate batteries for the main power and control power supplies. Main power battery voltage is below 250 Vdc for
200 V class drives, 500 Vdc for 400 V class drives, or 720 Vdc for 600 V class drives.
• Two separate batteries. One is used for the main power supply, a second battery supplies the controller via an optional
24 V Backup Power Supply Unit.
• A single battery with minimum 250 Vdc for 200 V class drives, 500 Vdc for 400 V class drives, or 720 Vdc for 600 V class drives is used for the main and control power supply.
Select the configuration that matches your application. Follow the corresponding instructions for wiring and drive settings. For configurations not covered in the list above, contact your Yaskawa representative or our sales office directly for consultation.
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 111
TOEP_C710616_38H_7_0.book 112 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
WARNING!
Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Never remove or install option cards or attempt to replace the cooling fan while the drive is switched on. Make sure that the drive and all devices connected to the drive have been shut off prior to performing and type of maintenance or wiring. After shutting off the power, wait for at least the amount of time specified on the drive before touching any components or perform wiring. The internal capacitor remains charged even after the power supply is turned off.
NOTICE: Be sure to thoroughly read the instructions for wiring and magnetic contactor sequence described in this section before setting up the drive for Rescue Operation. Failure to follow these instructions can damage the drive.
NOTICE: Refrain from using Rescue Operation for extend periods of time. Rescue Operation uses a low DC bus voltage, which can cause the cooling fan to shut off temporarily during Rescue Operation. Continuing to operate under these conditions can trigger an overheat fault and damage the drive.
NOTICE: Install the inrush current suppression circuit outside the drive if the DC bus battery voltage is lower than 190 Vdc for 200 V.
NOTICE: Install the inrush current suppression circuit outside the drive if the DC bus battery voltage is lower than 190 Vdc for 200 V class drives of models CIMR-LU2 0215 to 2 0415, 380 Vdc for 400 V class drives of models CIMR-LU4 0150 to 4 0605, and 500
Vdc for 600 V class drives of models CIMR-LU5 0099 to 5 0200. Failure to comply will cause the soft-charge bypass relay to remain open and result in damage to the drive.
Using a Single-Phase, 230 Vac UPS (Uninterruptable Power Supply)
Follow the instructions when using a single-phase 230 V UPS for Rescue Operation. A 230 V UPS can be used for 200 V,
400 V and 600 V class drives.
Wiring
Refer to
for a wiring diagram.
Figure 44
Elevator control system
L1000A
Magnetic
Contactor A B2
N UPS sine wave
230 Vac single-phase
L1
L2
L3
Magnetic
Contactor B
+1
+2
R/L1
S/L2
T/L3
-
Power supply
Control circuit
CN19
1
U/T1
V/T2
W/T3
H1غغ = 55
(Rescue Operation)
4
S3 to S8
SC
Magnetic Contactor Sequence
Magnetic Contactor B
Magnetic Contactor A
H1غغ = 55
(Rescue Operation)
Figure 51 Using a Single-Phase 230 V UPS
112 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 113 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Operation Sequence
Starting Rescue Operation
1.
Open contactor B.
2.
Set the input terminal programmed for Rescue Operation (H1 = 55).
3.
Close contactor A.
4.
Set the Up/Down command.
Ending Rescue Operation
1.
After the car has stopped open contactor A.
2.
Clear the input terminal set for Rescue Operation (H1 = 55).
3.
Close contactor B to return to operation with normal power supply.
Application Precautions
The drive may fault on a control power supply fault (Uv2) if the UPS can’t provide enough voltage, or if the Light Load
Direction Search is not set properly. If this problem occurs, take the following corrective actions:
Corrective Action:
• Use a separate battery for the controller power supply.
• Use a battery with a voltage higher than 250 Vdc for 200 V class drives, 500 Vdc for 400 V class drives, or 720 Vdc for
600 V class drives and connect it to the control power supply input (CN19). Alternatively use a 24 Vdc battery and an optional 24 V Backup Power Supply Unit.
• Enable Light Load Direction Search (S4-01 = 1).
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 113
4
TOEP_C710616_38H_7_0.book 114 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Using Separate Batteries for DC Bus and Control Power Supply, DC Bus Battery under 250 Vdc (500 Vdc, 720
Vdc)
Follow these instructions when using separate batteries for Rescue Operation with the battery for the DC bus having a lower voltage than 250 Vdc for 200 V class drives, 500 Vdc for 400 V class drives, or 720 Vdc for 600 V class drives.
Follow the wiring diagram shown in
. When connecting the battery for the control power supply to the L1000A, use the 1.1 m cable packaged with the product. The connector cover must first be removed in order to
Wiring for CIMR-LU2 0008 to 2 0180, 4 0005 to 4 0112, and 5 0003 to 5 0077
Figure 45
YEA_common
L1000A
B2
Battery for DC bus
200 V Class: 48 to 250 Vdc
400 V Class: 48 to 500 Vdc
600 V Class: 48 to 720 Vdc
B1
Magnetic Contactor A
+1
DC bus power supply
L1
L2
L3
Magnetic Contactor B
+2
R/L1
S/L2
T/L3
-
U/T1
V/T2
W/T3
CN19
1
Power supply
Control circuit
Magnetic Contactor C
Battery for control circuit
200 V Class: 250 to 340 Vdc
400 V Class: 500 to 680 Vdc
600 V Class: 720 to 850 Vdc
H1غغ = 55
(Rescue Operation)
4
S3 to S8
SC
Magnetic Contactor Sequence
Magnetic Contactor B
5 s
Magnetic Contactor A
0.5 s
Magnetic Contactor C
H1غغ = 55
(Rescue Operation)
Figure 52 Wiring Two Batteries for DC Bus and Control Power Supply
(DC Bus Battery is less than 250 Vdc (500 Vdc, 720 Vdc))
Operation Sequence
Starting Rescue Operation
1.
Open contactor B and wait at least 5 seconds.
2.
Set the input terminal programmed for Rescue Operation (H1 = 55).
3.
Close contactors A and C.
4.
Set the Up/Down command.
Ending Rescue Operation
1.
After the car has stopped, open contactors A and C.
2.
Clear the input terminal set for Rescue Operation (H1 = 55).
3.
Wait at least 0.5 s and then close contactor B to return to operation with normal power supply.
114 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 115 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Wiring for CIMR-LU2 0215 to 2 0415, 4 0150 to 4 0605, and 5 0099 to 5 0200
• Voltage Lower Than 48 to 190 Vdc for 200 V Class Drives, 48 to 380 Vdc for 400 V Class Drives, and 48 to 500 Vdc for 600 V Class Drives
Figure 46
Inrush current suppression circuit <1>
Inrush current suppression resistor L1000A
(A)
+3
Battery for DC bus
200 V Class: 48 to 190 Vdc
400 V Class: 48 to 380 Vdc
600 V Class: 48 to 500 Vdc
(D)
+1
DC bus power supply
L1
L2
L3
(B)
R/L1
S/L2
T/L3
Relay
+
Current sensor
U/T1
V/T2
W/T3
-
YEA_common
Battery for control circuit
200 V Class: 250 to 340 Vdc
400 V Class: 500 to 680 Vdc
600 V Class: 720 to 850 Vdc
(C) CN19
Power supply board
Control board
OPE
H1 = 55
(Rescue Operation)
S3 to S12
SC
Magnetic Contactor Sequence
After the DC bus voltage falls lower than the battery voltage
Magnetic Contactor B
0.5 s
Magnetic Contactor A
Magnetic Contactor C
Magnetic Contactor D
H1 = 55
(Rescue Operation)
After the DC bus voltage is charged to the battery voltage
Figure 53 Voltage Lower Than 48 to 190 Vdc for 200 V Class Drives, 48 to 380 Vdc for 400 V Class Drives, and 48 to 500 Vdc for 600 V Class Drives
<1> Install the inrush current suppression circuit outside the drive if the DC bus battery voltage is lower than 190 Vdc for 200 V class drives and 380 Vdc for 400 V class drives. Failure to comply will cause the soft-charge bypass relay to remain open and result in damage to the drive.
Refer to the following table to install the inrush current suppression circuit for battery.
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 115
TOEP_C710616_38H_7_0.book 116 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Table 34 Installation of the Inrush Current Suppression Circuit for Battery
Voltage
200 V
400 V
575 V
Drive Model
CIMR-LU
2 0215
2 0283
2 0346
2 0415
4 0150
4 0180
4 0216
4 0260
4 0304
4 0370
4 0450
4 0605
5 0099
5 0130
5 0172
5 0200
Resistor
1.0 Ω , 80 W
1.0 Ω , 80 W
1.0 Ω , 80 W
1.0 Ω , 80 W
1.0 Ω , 120 W
1.0 Ω , 220 W
1.0 Ω , 220 W
1.0 Ω , 220 W
1.0 Ω , 220 W
1.0 Ω , 500 W
2.0 Ω , 1000 W
2.0 Ω , 1000 W
2.0 Ω , 220 W
2.0 Ω , 220 W
2.0 Ω , 440 W
2.0 Ω , 440 W
Relay
<1> Select the appropriate relay referring to the following calculation even if the battery voltage or main power current is applied.
Load current of battery (A) =
Motor rated power (kW) × Operation frequency when running battery (Hz) × 2 × 1000
Battery voltage (Vdc) × 0.6 (Motor efficiency) × Motor rated frequency (Hz)
YEA_common
116 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 117 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
• Voltage Lower Than 190 to 340 Vdc for 200 V Class Drives, 380 to 680 Vdc for 400 V Class Drives, and 500 to 850
Vdc for 600 V Class Drives
Figure 47
L1000A
DC bus power supply
200 V Class: 190 to 340 Vdc
400 V Class: 380 to 680 Vdc
600 V Class: 500 to 850 Vdc
(A)
+3
+1
DC bus power supply
L1
L2
L3
(B)
R/L1
S/L2
T/L3
-
Relay
+
Current sensor
U/T1
V/T2
W/T3
YEA_common
Battery for control circuit
200 V Class: 250 to 340 Vdc
400 V Class: 500 to 680 Vdc
600 V Class: 720 to 850 Vdc
(C) CN19
Power supply board
Control board
OPE
H1 = 55
(Rescue Operation)
S3 to S12
SC
Magnetic Contactor Sequence
Magnetic Contactor B
After the DC bus voltage falls lower than the battery voltage
0.5 s
Magnetic Contactor A
Magnetic Contactor C
H1 = 55
(Rescue Operation)
Figure 54 Voltage Lower Than 190 to 340 Vdc for 200 V Class Drives, 380 to 680 Vdc for 400 V Class Drives, and 500 to 850 Vdc for 600 V Class Drives
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 117
TOEP_C710616_38H_7_0.book 118 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Using a Battery for the DC Bus and 24 V Power Supply Unit Option for the Control Circuit
Follow the instructions when using a 24 V Power Supply Unit option for the control circuit and a battery for the main circuit. The main circuit battery voltage must be higher than 48 Vdc for 200 V, 400 V, and 600 V class drives.
Yaskawa offers a 24 V Power Supply Option for the control circuit that is useful in applications unable to connect to a
backup battery greater than 250 V. Wiring instructions can be found in Figure 55 to
. For a more detailed explanation of the 24 V Power Supply Option, refer to the manual provided with the option.
Wiring for CIMR-LU2 0008 to 2 0180, 4 0005 to 4 0112, and 5 0003 to 5 0077
Figure 48
L1000A
YEA_common
B2
B1
Magnetic Contactor A
Battery for DC bus
200 V Class: 48 to 340 Vdc
400 V Class: 48 to 680 Vdc
600 V Class: 48 to 850 Vdc
DC bus power supply
L1
L2
L3
Magnetic Contactor B
+1
+2
R/L1
S/L2
T/L3
-
Battery for control circuit
24 Vdc
Magnetic Contactor C
24 V
Power
Supply
Unit
CN19
1
4
Power supply
Control circuit
U/T1
V/T2
W/T3
H1غغ = 55
(Rescue Operation)
S3 to S8
SC
Magnetic Contactor Sequence
Magnetic Contactor B
5 s
Magnetic Contactor A
0.5 s
Magnetic Contactor C
H1غغ = 55
(Rescue Operation)
Figure 55 Using a Battery for the DC Bus and 24 V Power Supply Unit Option for the Control Circuit
Operation Sequence
Starting Rescued Operation
1.
Open contactor B and wait at least 5 seconds.
2.
Set the input terminal programmed for Rescue Operation (H1 = 55).
3.
Close contactors A and C.
4.
Set the Up/Down command.
Ending Rescue Operation
1.
After the car has stopped, open contactors A and C.
2.
Clear the input terminal set for Rescue Operation (H1 = 55).
3.
Wait at least 0.5 s and then close contactor B to return to operation with normal power supply.
118 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 119 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Wiring for CIMR-LU2 0215 to 2 0415, 4 0150 to 4 0605, and 5 0099 to 5 0200
• Voltage Lower Than 48 to 190 Vdc for 200 V Class Drives, 48 to 380 Vdc for 400 V Class Drives, and 48 to 500 Vdc for 600 V Class Drives
Figure 49
Inrush current suppression circuit <1>
Inrush current suppression resistor L1000A
(A)
+3
Battery for DC bus
200 V Class: 48 to 190 Vdc
400 V Class: 48 to 380 Vdc
600 V Class: 48 to 500 Vdc
(D)
+1
DC bus power supply
L1
L2
L3
(B)
R/L1
S/L2
T/L3
Relay
+
Current sensor
U/T1
V/T2
W/T3
-
YEA_common
Battery for control circuit
24 Vdc
Magnetic Contactor C
24 V
Power
Supply
Unit
H1 = 55
(Rescue Operation)
CN19
S3 to S12
SC
Power supply board
Control board
OPE
Magnetic Contactor Sequence
After the DC bus voltage falls lower than the battery voltage
Magnetic Contactor B
0.5 s
Magnetic Contactor A
Magnetic Contactor C
Magnetic Contactor D
H1 = 55
(Rescue Operation)
After the DC bus voltage is charged to the battery voltage
Figure 56 Using a Battery for the DC Bus and 24 V Power Supply Unit Option for the Control Circuit
(CIMR-LU2 0215 to 2 0415, 4 0150 to 4 0605, and 5 0099 to 5 0200)
<1> Install the inrush current suppression circuit outside the drive if the DC bus battery voltage is lower than 190 Vdc for 200 V class drives and 380 Vdc for 400 V class drives. Failure to comply will cause the soft-charge bypass relay to remain open and result in damage to the drive.
for the installation of the inrush current suppression circuit for battery.
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 119
TOEP_C710616_38H_7_0.book 120 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
• Voltage Lower Than 190 to 250 Vdc for 200 V Class Drives, 380 to 500 Vdc for 400 V Class Drives, and 500 to 720
Vdc for 600 V Class Drives
Figure 50
L1000A
DC bus power supply
200 V Class: 190 to 250 Vdc
400 V Class: 380 to 500 Vdc
600 V Class: 500 to 720 Vdc
(A)
+3
+1
DC bus power supply
L1
L2
L3
(B)
R/L1
S/L2
T/L3
-
Relay
+
Current sensor
U/T1
V/T2
W/T3
YEA_common
CN19
Power supply board
Control board
OPE
Battery for control circuit
24 Vdc
Magnetic Contactor C
24 V
Power
Supply
Unit
H1 = 55
(Rescue Operation)
S3 to S12
SC
Magnetic Contactor Sequence
Magnetic Contactor B
After the DC bus voltage falls lower than the battery voltage
0.5 s
Magnetic Contactor A
Magnetic Contactor C
H1 = 55
(Rescue Operation)
Figure 57 Voltage Lower Than 190 to 250 Vdc for 200 V Class Drives, 380 to 500 Vdc for 400 V Class Drives, and 500 to 720 Vdc for 600 V Class Drives
120 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 121 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Using a Single Battery with Minimum 250 Vdc (500 Vdc, 720 Vdc)
Follow the instructions when using one battery to supply both, main circuit and controller. The battery voltage must be at least 250 Vdc for 200 V class drives, 500 Vdc for 400 V class drives, or 720 Vdc for 600 V class drives.
Wiring
Following the wiring diagram show in Figure 58
.
Figure 51
L1000A
YEA_common
B2
B1
Magnetic Contactor A
Battery for DC bus
200 V Class: 250 to 340 Vdc
400 V Class: 500 to 680 Vdc
600 V Class: 720 to 850 Vdc
DC bus power supply
L1
L2
L3
Magnetic Contactor B
R/L1
S/L2
T/L3
-
H1غغ = 55
(Rescue Operation)
CN19
1
4
S3 to S8
SC
Power supply
Magnetic Contactor Sequence
Magnetic Contactor B
Control circuit
Magnetic Contactor A
H1غغ = 55
(Rescue Operation)
Figure 58 Using a Backup Battery With Minimum 250 Vdc (500 Vdc, 720 Vdc)
Operation Sequence
Starting Rescue Operation
1.
Open contactor B.
2.
Set the input terminal programmed for Rescue Operation (H1 = 55).
3.
Close contactor A.
4.
Set the Up/Down command.
Ending Rescue Operation
1.
After the car has stopped, open contactor A.
2.
Clear the input terminal set for Rescue Operation (H1 = 55).
3.
Close contactor B to return to operation with normal power supply.
U/T1
V/T2
W/T3
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 121
TOEP_C710616_38H_7_0.book 122 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Connecting the Drive and Battery
Use the 1.1 m cable packaged with the drive to connect the battery. Remove the connector covering port CN19 before connecting the cable to CN19.
Information on battery power ratings can be found in Table 33 .
Note: The connector port location and angle vary by drive model.
DANGER!
Switch off the power supply before wiring and connecting the battery cable. Failure to comply will lead to death or serious injury from electric shock.
Battery Connections for CIMR-LU2 0008 to 2 0075, CIMR-LU4 0005 to 4 0039, and CIMR-LU5 0003 to
5 0027
1.
Insert the tip of a screwdriver into the opening on the edge of the CN19 connector cover. Slide the cover off the
drive as indicated in Figure 59 .
NOTICE: A straight-edge screwdriver should be inserted into the opening provided on the connector cover at the proper angle.
Attempting to insert the screwdriver blade at a different angle could damage the drive.
Figure 52
Press inwards on the tab and slide the connector cover in the direction indicated by the arrow.
Figure 59 Removing the Connector Cover
2.
Connect the cable provided to the CN19 port.
NOTICE: Be sure that the connector fastens at the correct angle to the drive port. The incorrect angle could damage the battery, cable, or connector.
Figure 53
Port CN19
122
Press in on the connector clip to plug in the cable.
Figure 60 Connecting the Cable
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 123 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Figure 54
3.
Use a pair of diagonal cutters to cut an opening in the connector cover that allows the cable to pass through. The cable should pass through the connector cover with the cover fastened to the drive.
Cut an opening to allow the battery cable to pass through.
Figure 61 Reattaching the Connector Cover (1)
4.
Slide the connector cover back into place as shown in
NOTICE: Make sure the cable does not get pinched between the drive and the connector cover, as this could damage the cable.
Figure 55
Figure 56
Figure 62 Reattaching the Connector Cover (2)
Connect to battery.
Figure 63 Drive and Battery Connection Complete
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 123
TOEP_C710616_38H_7_0.book 124 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Models CIMR-LU2 0085 to 2 0415, CIMR-LU4 0045 to 4 0370, 5 0003 to 5 0200, and 5 0032 to 5 0200
1.
Use a Phillips screwdriver to loosen the screw holding the CN19 connector cover in place.
Figure 57
Screw
Connector cover
Figure 58
Phillips screwdriver
Figure 64 Removing the CN19 Connector Cover
2.
Slide the CN19 connector cover from the drive as shown in
.
Figure 59
Figure 65 Sliding the CN19 Connector Cover
3.
Insert a straight-edge screwdriver into the opening as shown in Figure 66
, then remove the CN19 connector cover by sliding it as shown in
124
Figure 66 Removing the CN19 Connector Cover
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 125 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
4.
Connect the cable to the CN19 connector port on the drive.
Note: The connector port location and angle vary by drive model.
NOTICE: Be sure that the connector fastens at the correct angle to the CN19 connector port. The incorrect angle could damage the battery, cable, or connector.
Figure 60
Port CN19
Battery cable
Figure 61
Figure 67 Connecting the Cable
5.
The cable should pass through the connector cover with the cover fastened to the drive.
Figure 68 Reattaching the CN19 Connector Cover
6.
Slide the CN19 connector cover back into place as shown in Figure 69
.
NOTICE: Make sure the cable does not get pinched between the drive and the CN19 connector cover, as this could damage the cable.
Figure 62
Downward Leftward
4
Figure 69 Sliding the CN19 Connector Cover into Place
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 125
TOEP_C710616_38H_7_0.book 126 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
7.
Use a Phillips screwdriver to fasten the screw that holds the CN19 connector cover in place.
NOTICE: Use the screw provided to fasten the connector cover into place. Using a different screw may damage the internal drive components.
Figure 63
Figure 64
Figure 70 Reattaching the CN19 Connector Cover
Connect to battery
Figure 71 Drive and Battery CN19 Connection Complete
Models CIMR-LU4A0450 and 0605
1.
Use a Phillips screwdriver to remove the drive covers.
Figure 65
A
B
C
A – Front cover 1
B – Front cover 2
C – Terminal cover
Figure 72 Removing the Connector Cover
126 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 127 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
Figure 66
2.
Connect the cable provided to the CN19 port.
Note: Be sure that the connector fastens at the correct angle to the drive port. The incorrect angle could damage the battery, cable, or connector.
Port CN19
Figure 67
Figure 73 Connecting the Cable
3.
Reinstall the drive covers to their original locations.
A
B
C
A – Front cover 1
B – Front cover 2
C – Terminal cover
Figure 74 Reinstalling the Covers to the Drive
Rescue Operation Torque Limit
The Torque Limit During Rescue Operation is set in parameter S4-05. After Rescue Operation is complete, the drive utilizes to the torque limits set in the L7 parameters.
Light Load Direction Search Function
Light Load Direction Search can be used to automatically perform Rescue Operation in the direction with the lower load.
It can help to minimize the amount of power required by the backup power supply required for Rescue Operation. Light
Load Direction Search can be set so that it is automatically performed when Rescue Operation is started. To enable Light
Load Direction Search set parameter S4-01 = 1.
When Light Load Direction Search is enabled the drive first runs in the up and then in the down direction, each for the time set to S4-03. It then compares the load condition of both operations and travels to the next floor using the lighter load condition direction. The speed reference used for Light Load Direction Search can be set in parameter S4-04.
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 127
TOEP_C710616_38H_7_0.book 128 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
• When the lightest load direction is up, the drive stops after Light Load Direction Search and then accelerates upwards to the Rescue Operation speed set in parameter S4-15. The output terminals set for “Light Load Direction” (H2 = 54) and “Light Load Direction detection status” (H2 = 55) will close.
Figure 68
H1غغ = 55
(Rescue Operation)
Off (open) On (closed)
Up/Down command
Off (open) On (closed)
Speed agree torque calculations
Up command (internal)
Up Up
Down command (internal) Down
Elevator moves in the direction of the light load
H2 = 55
㧔 Light Load Direction Search status 㧕
Off (open) On (closed)
H2 = 54
㧔 Light load direction 㧕
Off (open) On (closed)
Figure 75 Light Load Direction Detection (Up)
• When the lightest direction is down, then after Light Load Direction Detection is finished the drive immediately accelerates to the Rescue Operation speed set in S4-15 without stopping. An output terminal set for “Light load direction” (H2 = 54) will stay open, and an output terminal set for “Light Load Direction detection status”
(H2 = 55) will close.
Figure 69
H1غغ = 55
(Rescue Operation)
Off (open) On (closed)
Up/Down command
Off (open) On (closed)
Speed agree torque calculations
Up command (internal)
Up
Down command (internal) Down
H2 = 55
㧔 Light Load Direction Search status 㧕
H2 = 54
㧔 Light load direction 㧕
Off (open)
Off (open)
Figure 76 Light Load Direction Detection (Down)
Elevator moves in the direction of the light load
On (closed)
128 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 129 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
◆
Setup Troubleshooting and Possible Solutions
This section describes troubleshooting problems that do not trip an alarm or fault.
Symptom
Cannot Change Parameter Settings
Motor Does Not Rotate Properly after Pressing RUN Button or after Entering External Up/Down Command
Motor Does Not Rotate
Motor Rotates in the Opposite Direction from the Up/Down
Command
Motor Gets Too Hot
Drive Does Not Allow Selection of Rotational Auto-Tuning
Encoder Offset (E5-11) Set During Auto-Tuning (Rotational or Stationary) Consistently Differs by 30 Degrees or More
Noise From Drive or Output Lines When the Drive is Powered On
The Safety Controller Does Not Recognize Safe Disable Monitor Output Signals (Terminals DM+ and DM-)
■
Cannot Change Parameter Settings
Cause
The drive is running the motor (i.e., the Up/Down command is present).
The Access Level is set to restrict access to parameter settings.
The operator is not in the Parameter Setup Mode.
The wrong password was entered.
Undervoltage was detected.
Possible Solutions
• Stop the drive and switch over to the Programming Mode.
• Most parameters cannot be edited during run.
Set the Access Level to allow parameters to be edited (A1-01 = 2).
• Verify the digital operator mode, Drive or Programming mode?
• Switch to the Programming Mode. Refer to
The Drive and Programming Modes on page 63
.
• If the password entered to A1-04 does not match the password saved to A1-05, then drive settings cannot be changed.
• Reset the password.
If the password is unknown:
• Scroll to A1-04. Press
STOP
and press at the same time. Parameter A1-05 will appear.
• Set a new password to parameter A1-05.
• Check the drive main input voltage by looking at the DC bus voltage (U1-07).
• Check all main circuit wiring.
Page
4
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 129
TOEP_C710616_38H_7_0.book 130 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
Motor Does Not Rotate Properly after Pressing RUN Button or after Entering External Up/
Down Command
Motor Does Not Rotate
Cause
The drive is not in the Drive Mode.
Possible Solutions
• Check if the DRV on the digital operator is displayed.
• Enter the Drive Mode. Refer to The Drive and Programming Modes on page 63 .
Stop the drive and check if the correct frequency reference source is selected. If the digital operator is the source, the LO/RE button LED must be on. If the source is REMOTE, it must be off.
Take the following steps to solve the problem:
The pushed.
button is enabled (o2-01=1) and was
Auto-Tuning has just completed.
A Fast Stop was executed and is not reset.
Settings are incorrect for the source that provides the Up/Down command.
There is faulty wiring in the control circuit terminals.
The speed reference source setting is incorrect.
The settings for the analog speed reference are incorrect.
Selection for the sink/source mode and the internal/ external power supply is incorrect.
Speed reference is too low.
• Push the button.
• o2-01 is set to 0 by default, i.e. the LO/RE button is disabled.
• When Auto-Tuning completes, the drive is switched back to the Programming Mode. The
Up/Down command will not be accepted unless the drive is in the Drive Mode.
• Use the digital operator to enter the Drive Mode. Refer to The Drive and Programming
.
Reset the Fast Stop command.
Check parameter b1-02 (Up/Down Command Selection).
Set b1-02 so that it corresponds with the correct Up/Down command source.
0: Digital operator
1: Control circuit terminal (default setting)
2: MEMOBUS/Modbus communications
3: Option card
• Check the wiring for the control terminal.
• Correct wiring mistakes.
• Check the input terminal status monitor (U1-10).
Check parameter b1-01 (Speed Reference Selection).
Set b1-01 to the correct source of the speed reference.
0: Digital operator
1: Control circuit terminal (default setting)
2: MEMOBUS/Modbus communications
3: Option card
Check the settings (signal level, function, bias, gain) for the analog input that supplies the speed reference.
Check the position of the jumper and setting for S3.
Refer to Control I/O Configuration on page 54
.
• Check the speed reference monitor (U1-01).
• Increase the speed reference above the minimum output speed (E1-09).
• Make sure speed references are set properly and the speed selection works properly. If using an analog signal make sure the input signal is present at the time the Up/Down command is issued.
The brake does not release or motor contactor is not closed.
Check the brake and motor contactor sequence.
The
STOP
button is enabled (o2-02 = 1) and was • When the pressed when the drive was started from a
REMOTE source.
STOP
button is pressed, the drive will decelerate to stop.
• Switch off the Up/Down command and then re-enter a new Up/Down command.
• o2-02 is set to 0 by default, i.e. the Stop button is disabled.
Motor Rotates in the Opposite Direction from the Up/Down Command
Cause
Phase wiring between the drive and motor is incorrect.
Drive control circuit terminals for the Up and Down commands are switched.
Possible Solutions
Check the motor wiring. Perform the steps described in
Motor Rotation Direction Setup on page 69
and
.
• Check the control circuit wiring.
• Correct any fault wiring.
130 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 131 ページ 2015年11月11日 水曜日 午後7時40分
4 Start-Up Programming & Operation
■
Motor is Too Hot
The load is too heavy.
Insufficient voltage insulation between motor phases.
Cause
The air around the motor is too hot.
The drive is operating in a vector control mode but
Auto-Tuning has not yet been performed.
The motor fan has stopped or is clogged.
Possible Solutions
If the load is too heavy for the motor, the motor will overheat as it exceeds its rated torque value for an extended period of time.
Keep in mind that the motor also has a short-term overload rating in addition to the possible solutions provided below:
• Reduce the load.
• Lower the acceleration and deceleration ramps. (Increase the acceleration time and deceleration time.)
• Check the values set for the motor protection (L1-01, L1-02) as well as the motor rated current (E2-01).
• Increase motor capacity.
• Check the ambient temperature.
• Cool the area until it is within the specified temperature range.
• Perform Auto-Tuning.
• Calculate the motor value and reset the motor parameters.
• Change the motor control method to V/f Control (A1-02 = 0).
When the motor cable is long, high voltage surges occur between the motor coils and drive switching.
Normally, surges can reach up to three times the drive input power supply voltage.
• Use a motor with a voltage tolerance higher than the max voltage surge.
• Install an AC reactor on the output side of the drive. Make sure the output reactor can handle frequencies in the range of the drive carrier frequency.
Check the motor fan.
■
Drive Does Not Allow Selection the Desired Auto-Tuning Mode
Cause
The desired Auto-Tuning mode is not available for the selected control mode.
Possible Solutions
• Check if the desired tuning mode is available for the selected control mode.
• Change the motor control method by setting A1-02.
■
Encoder Offset (E5-11) Set During Auto-Tuning (Rotational or Stationary) Consistently
Differs by 30 Degrees or More
Cause
PG-E3 option detected excess position error with the ERN1387 encoder.
Possible Solutions
Perform Auto-Tuning of PG-E3 encoder characteristics (T2-01 = 12).
■
Electrical Noise From Drive or Output Lines When the Drive is Operating
Cause
PWM switching in the drive generates excessive noise.
Possible Solutions
• Lower the carrier frequency (C6-03).
• Install a noise filter on the input side of drive input power.
• Install a noise filter on the output side of the drive.
• Place the wiring inside a metal conduit to shield it from switching noise.
• Ground the drive and motor properly.
• Separate the main circuit wiring and the control lines.
• Make sure wires and the motor have been properly grounded.
■
The Safety Controller Does Not Recognize Safe Disable Monitor Output Signals (Terminals
DM+ and DM-)
4
Cause
There is faulty wiring in the Safe Disable monitor output terminals.
Possible Solutions
• Check the wiring and logic for the Safe Disable monitor output terminal.
• Correct wiring mistakes.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 131
TOEP_C710616_38H_7_0.book 132 ページ 2015年11月11日 水曜日 午後7時40分
5 Troubleshooting
5 Troubleshooting
◆
Fault Detection
■
Fault Displays, Causes, and Possible Solutions
Faults are detected for drive protection, and cause the drive to stop while triggering the fault output terminal
MA-MB-MC. Remove the cause of the fault and manually clear the fault before attempting to run the drive again.
Table 35 Detailed Fault Displays, Causes, and Possible Solutions
Digital Operator Display boL bUS
CE
CF
CoF
Fault Name
Braking Transistor Overload
The braking transistor has reached its overload level.
Option Communication Error
• The connection was lost after establishing initial communication.
• Only detected when the Up/Down command speed reference is assigned to an option card.
MEMOBUS/Modbus Communication Error
Communication data was not received for the amount of time set in parameter, H5-09
Communication Fault Detection Time.
Control Fault
The torque limit was reached continuously for three seconds or longer while ramping to stop in OLV
Control.
Current Offset Fault
The current sensor is damaged or there was residual induction current in the motor (e.g., during sudden deceleration or when coasting) when the drive attempted to start the motor.
or
CPF00 or CPF01 Control Circuit Error
CPF02
CPF03
CPF06
A/D Conversion Error
An A/D conversion error or control circuit error occurred.
Control Board Connection Error
Connection error between the control board and the drive
EEPROM Memory Data Error
An error in the data saved to EEPROM
to
to
CPF07
CPF08
,
CPF11 to CPF14,
CPF16 to CPF21
Terminal Board Connection Error
Control Circuit Error
to
CPF22
CPF23
CPF24
CPF25
CPF26 to CPF34
CPF35
Hybrid IC Failure
Control Board Connection Error
Connection error between the control board and the drive
Drive Unit Signal Fault
The drive capacity cannot be detected correctly (drive capacity is checked when the drive is powered up).
Terminal Board not Connected
Control Circuit Error
CPU error
A/D Conversion Error
An A/D conversion error or control circuit error occurred.
132 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 133 ページ 2015年11月11日 水曜日 午後7時40分
Digital Operator Display dEv dv1 dv2 dv3
EF0
EF3
EF4
EF5
EF6
EF7
EF8
Err
FrL
GF
LF
LF2 oC dv6 dv7 dv8 dv4
5 Troubleshooting
Fault Name
Speed Deviation (for Control Mode with Encoder)
The deviation between the speed reference and speed feedback is greater than the setting in F1-10 for longer than the time set to F1-11.
Encoder Z Pulse Fault
The motor turned one full rotation without the Z Pulse being detected.
Z Pulse Noise Fault Detection
The Z pulse is out of phase by more than 5 degrees for the number of times specified in parameter
F1-17.
Inversion Detection
The torque reference and acceleration are in opposite directions and the speed reference and actual motor speed differ by over 30% for the number of times set to F1-18.
Inversion Prevention Detection
Pulses indicate that the motor is rotating in the opposite direction of the speed reference. Set the number of pulses to trigger inverse detection to F1-19.
Note: Set F1-19 to 0 to disable inverse detection in applications where the motor may rotate in the opposite direction of the speed reference.
Overacceleration Detection
The acceleration of the elevator car exceeds the overacceleration detection level (S6-10)
Rotor Polarity Detection Timeover
Unable to detect the magnetic poles within the designated time.
PM Rotor Position Estimation Error
An invalid value resulted from Initial Pole Search.
Note: Reset the fault and try Initial Pole Search again.
Option Card External Fault
An external fault condition is present.
External Fault (input terminal S3)
External fault at multi-function input terminal S3.
External Fault (input terminal S4)
External fault at multi-function input terminal S4.
External Fault (input terminal S5)
External fault at multi-function input terminal S5.
External Fault (input terminal S6)
External fault at multi-function input terminal S6.
External Fault (input terminal S7)
External fault at multi-function input terminal S7
External Fault (input terminal S8)
External fault at multi-function input terminal S8
EEPROM Write Error
Data cannot be written to the EEPROM.
Speed Reference Missing
Parameter d1-18 is set to 3, leveling speed detection is not assigned to a digital input (H1 ≠ 53) and no speed was selected while an Up or Down command was entered.
Ground Fault
A current short to ground exceeded 50% of rated current on the output side of the drive.
Output Phase Loss
• Phase loss on the output side of the drive.
• Setting L8-07 to 1 or 2 enables Phase Loss Detection.
Output Current Imbalance (detected when L8-29 = 1)
One or more of the phases in the output current is lost.
Overcurrent
Drive sensors have detected an output current greater than the specified overcurrent level.
5
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 133
TOEP_C710616_38H_7_0.book 134 ページ 2015年11月11日 水曜日 午後7時40分
5 Troubleshooting
,
,
to
to
Digital Operator Display
to
to
to
to oFA00
Fault Name
Option Card Connection Error at Option Connector CN5-A, Option Card Fault at Option Connector
CN5-A
Option compatibility error
Option Card Fault at Option Connector CN5-A
Option not properly connected oFA01 oFA05, oFA06 oFA10, oFA11 oFA12 to oFA17 oFA30 to oFA43 oFb00
Option card error occurred at option port CN5-A oFb01
Option Card Fault at Option Port CN5-B
Option compatibility error
Option Card Fault at Option Port CN5-B
Option not properly connected
Option Card Fault at Option Port CN5-B
Same type of option card already connected oFb02 oFb03 to oFb11 oFb12 to oFb17 oFC00
Option card error occurred at Option Port CN5-B oFC01 oFC02
Option Card Connection Error at Option Port CN5-C
Option compatibility error
Option Card Fault at Option Port CN5-C
Option not properly connected
Option Card Fault at Option Port CN5-C
A maximum of two PG option boards can be used simultaneously. Remove the PG option board installed into option port CN5-A.
oFC03 to oFC11 oFC12 to oFC17 oFC50 oFC51 oFC52 oFC53 oFC54 oH oH1 oH3 oH4
Option card error occurred at option port CN5-C
Encoder Option AD Conversion Error
Error with the A/D conversion level (VCC level), or A/D conversion timed out.
Encoder Option Analog Circuit Error
Incorrect signal level (+2.5 V signal)
Encoder Communication Timeout
Signal encoder timed out waiting to receive data
Encoder Communication Data Error
Serial encoder CRC checksum error
Encoder Error
Alarm reading EnDat absolute position data from encoder
(OR flag from EnDat error for overvoltage, undervoltage, etc.)
Heatsink Overheat
The temperature of the heatsink exceeded the overheat pre-alarm level set to L8-02. Default value for L8-02 is determined by drive capacity (o2-04).
Heatsink Overheat
The temperature of the heatsink exceeded the drive overheat level. The overheat level is determined by drive capacity (o2-04).
Motor Overheat Alarm (PTC thermistor input)
• The motor overheat signal to analog input terminal A1 or A2 exceeded the alarm detection level.
• Detection requires multi-function analog input H3-02 or H3-10 be set to “E”.
Motor Overheat Fault (PTC thermistor input)
• The motor overheat signal to analog input terminal A1 or A2 exceeded the fault detection level.
• Detection requires that multi-function analog input H3-02 or H3-10 = “E”.
134 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 135 ページ 2015年11月11日 水曜日 午後7時40分
Digital Operator Display oL1 oL2 oL3 oL4
oPr oS ov rF rr
SC
SCF
SE1
PF
PF5
PGo
PGoH
SE2
SE3
SE4
SvE
5 Troubleshooting
Fault Name
Motor Overload
The electronic motor overload protection tripped.
Drive Overload
The thermal sensor of the drive triggered overload protection.
Overtorque Detection 1
The current has exceeded the value set for torque detection (L6-02) for longer than the allowable time (L6-03).
Overtorque Detection 2
The current has exceeded the value set for Overtorque Detection 2 (L6-05) for longer than the allowable time (L6-06).
External Digital Operator Connection Fault
• The external operator has been disconnected from the drive.
Note:
An oPr fault will occur when all of the following conditions are true:
Output is interrupted when the operator is disconnected (o2-06 = 1).
The Up/Down command is assigned to the operator (b1-02 = 0 and LOCAL has been selected).
Overspeed
The motor speed feedback exceeded the F1-08 setting.
DC Bus Overvoltage
Voltage in the DC bus has exceeded the overvoltage detection level.
• For 200 V class: approximately 410 V
• For 400 V class: approximately 820 V
• For 600 V class: approximately 1040 V
Input Phase Loss
Drive input power has an open phase or has a large imbalance of voltage between phases. Detected when L8-05 = 1, 2, 3 (enabled).
Rescue Operation Power Supply Deterioration Error
Encoder Disconnected (for Control Mode with Encoder)
No encoder pulses are received for longer than the time set to F1-14.
Encoder Disconnected (detected when using an encoder)
Encoder cable is not connected properly.
Braking Resistor Fault
The resistance of the braking resistor being used is too low.
Dynamic Braking Transistor Fault
The built-in dynamic braking transistor failed.
IGBT Short Circuit
Short Circuit or Ground Fault is detected
Safety Circuit Fault
Safety Circuit Fault is detected.
Motor Contactor Response Error
Motor contactor does not respond within the time set to S1-10 (Run Command Delay Time).
Starting Current Error
The output current was lower than 25% of the motor no-load current at start.
Output Current Error
The output current was lower than 25% of the motor no-load current during operation.
Brake Feedback Error
The input terminal set for “Brake feedback” (H1 = 79) or “Brake feedback 2” (H1 = 5B) did not respond within the SE4 error time set to S6-05 after an output terminal set for “Brake release” (H2 = 50) closed.
Position Lock Error
Position deviation during Position Lock.
5
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 135
TOEP_C710616_38H_7_0.book 136 ページ 2015年11月11日 水曜日 午後7時40分
5 Troubleshooting
Digital Operator Display
STo
UL3
UL4
Uv1
Uv2
Uv3 voF
Fault Name
Motor Pull Out or Step Out Detection
Motor pull out or step out has occurred. Motor has exceeded its pull out torque.
Undertorque Detection 1
The current has fallen below the minimum value set for torque detection (L6-02) for longer than the allowable time (L6-03).
Undertorque Detection 2
The current has fallen below the minimum value set for torque detection (L6-05) for longer than the allowable time (L6-06).
DC Bus Undervoltage
One of the following conditions occurred while the drive was running:
• Voltage in the DC bus fell below the undervoltage detection level (L2-05)
• For 200 V class: approximately 190 V
• For 400 V class: approximately 380 V (350 V when E1-01 is less than 400)
• For 600 V class: approximately 500 V
Control Power Supply Voltage Fault
Voltage is too low for the control drive input power.
Soft-Charge Bypass Circuit Fault
The soft-charge bypass circuit failed.
Output Voltage Detection Error
Problem detected with the voltage on the output side of the drive.
<1> Displayed as will show or
or when occurring at drive power up. When one of the faults occurs after successfully starting the drive, the display
.
<2> Displayed only for models in compliance with IEC/EN 61508 SIL3 Safety Integrity Level 3.
◆
Alarm Detection
■
Alarm Codes, Causes, and Possible Solutions
Alarms are drive protection functions that do not necessarily cause the drive to stop. Once the cause of an alarm is removed, the drive will return to the same status as before the alarm occurred.
When an alarm has been triggered, the ALM light on the digital operator display blinks and the alarm code display flashes. If a multi-function output is set for an alarm (H2 = 10), that output terminal will be triggered for certain alarms.
Note: If a multi-function output is set to close when an alarm occurs (H2 = 10), it will also close when maintenance periods are reached, triggering alarms LT-1 through LT-4 (triggered only if H2 = 2F).
Table 36 Alarm Codes, Causes, and Possible Solutions
Digital Operator Display
AEr bb boL bUS
CALL
CE
CrST
Minor Fault Name
Communication Option Node ID Setting Error (CANopen)
Option card node address is outside the acceptable setting range.
Baseblock
Drive output interrupted as indicated by an external baseblock signal.
Braking Transistor Overload
The braking transistor in the drive has been overloaded.
Option Communication Error
• After initial communication was established, the connection was lost.
• Assign a Up/Down command or speed reference to the option card.
Serial Communication Stand By
Communication has not yet been established.
MEMOBUS/Modbus Communication Error
Control data was not received correctly for two seconds.
Cannot Reset
136 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 137 ページ 2015年11月11日 水曜日 午後7時40分
Digital Operator Display dEv
EF
EF0
EF3
EF4
EF5
EF6
EF7
EF8
Hbb
HbbF
HCA
LT-1
LT-2
LT-3
LT-4 oH oH3 oL3 oL4 oS
5 Troubleshooting
Minor Fault Name
Speed Deviation (when using a PG option card)
The deviation between the speed reference and speed feedback is greater than the setting in F1-10 for longer than the time in F1-11.
Up/Down Command Error
Both forward run and reverse run closed simultaneously for over 0.5 s.
Option Card External Fault
An external fault condition is present.
External fault (input terminal S3)
External fault at multi-function input terminal S3.
External fault (input terminal S4)
External fault at multi-function input terminal S4.
External fault (input terminal S5)
External fault at multi-function input terminal S5.
External fault (input terminal S6)
External fault at multi-function input terminal S6.
External fault (input terminal S7)
External fault at multi-function input terminal S7.
External fault (input terminal S8)
External fault at multi-function input terminal S8.
Safe Disable Circuit Fault Signal (H1-HC, H2-HC) Release
Both Safe Disable Input channels are open.
Safe Disable Circuit Fault Signal (H1-HC, H2-HC) Release
One Safe Disable channel is open while the other one is closed.
High Current Alarm
Drive current exceeded overcurrent warning level (150% of the rated current).
Cooling Fan Maintenance Time
The cooling fan has reached its expected maintenance period and may need to be replaced.
Note: An alarm output (H2 = 10) will only be triggered if H2 = 2F.
Capacitor Maintenance Time
The main circuit and control circuit capacitors are nearing the end of their expected performance life.
Note: An alarm output (H2 = 10) will only be triggered if H2 = 2F.
Soft Charge Bypass Relay Maintenance Time
The DC bus soft charge relay is nearing the end of its expected performance life.
Note: An alarm output (H2 = 10) will only be triggered if H2 = 2F.
IGBT Maintenance Time (90%)
IGBTs have reached 90% of their expected performance life.
Note: An alarm output (H2 = 10) will only be triggered if H2 = 2F.
Heatsink Overheat
The temperature of the heatsink exceeded the overheat pre-alarm level set to L8-02 (90-100 ° C). Default value for L8-02 is determined by drive capacity (o2-04).
Motor Overheat Alarm (PTC thermistor input)
• The motor overheat signal to analog input terminal A1 or A2 exceeded the alarm detection level.
• Detection requires multi-function analog input H3-02 or H3-10 be set to “E”.
Overtorque Detection 1
Drive output current (or torque in OLV, CLV, CLV/PM) was greater than L6-02 for longer than the time set in L6-03.
Overtorque Detection 2
Drive output current (or torque in OLV, CLV, CLV/PM) was greater than L6-05 for longer than the time set in L6-06.
Overspeed (for Control Mode with Encoder)
The motor speed feedback exceeded the F1-08 setting.
5
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 137
TOEP_C710616_38H_7_0.book 138 ページ 2015年11月11日 水曜日 午後7時40分
5 Troubleshooting
Digital Operator Display ov
PASS
PGo
PGoH
SE
TrPC
UL3
UL4
Uv voF
Minor Fault Name
DC Bus Overvoltage
The DC bus voltage exceeded the trip point.
For 200 V class: approximately 410 V
For 400 V class: approximately 820 V
For 600 V class drives: approximately 1040 V
MEMOBUS/Modbus Communication Test Mode Complete
Encoder Disconnected (for Control Mode with Encoder)
Detected when no encoder signal is received for a time longer than setting in F1-14.
Encoder Disconnected (detected when using an encoder)
Encoder cable has become disconnected.
MEMOBUS/Modbus Self Test Failed
IGBT Maintenance Time (90%)
IGBTs have reached 90% of their expected performance life.
Note: This alarm will not trigger a multi-function output terminal that is set for alarm output (H2 =
10).
Undertorque Detection 1
Drive output current (or torque in OLV, CLV, CLV/PM) less than L6-02 for longer than L6-03 time.
Undertorque Detection 2
Drive output current (or torque in OLV, CLV, CLV/PM) less than L6-05 for longer than L6-06 time.
Undervoltage
One of the following conditions was true when the drive was stopped and a Up/Down command was entered:
• DC bus voltage dropped below the level specified in L2-05.
• Contactor to suppress inrush current in the drive was opened.
• Low voltage in the control drive input power. This alarm outputs only if L2-01 is not 0 and DC bus voltage is under L2-05.
Output Voltage Detection Error
There is a problem with the output voltage.
<1> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN 61800-5-2, ISO/EN
13849 Cat. 3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
138 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 139 ページ 2015年11月11日 水曜日 午後7時40分
5 Troubleshooting
◆
Operator Programming Errors
■
oPE Codes, Causes, and Possible Solutions
An Operator Programming Error (oPE) occurs when a contradictory parameter is set or an individual parameter is set to an inappropriate value.
The drive will not operate until the parameter or parameters causing the problem are set correctly. An oPE, however, does
action. When an oPE appears on the operator display, press the ENTER button to view U1-18 and see which parameter is causing the oPE.
Table 37 oPE Codes, Causes, and Possible Solutions
Digital Operator Display oPE01 oPE02 oPE03 oPE04
Error Name
Drive Capacity Setting Fault
Drive capacity and the value set to o2-04 do not match.
Parameter Range Setting Error
Use U1-18 to find parameters set outside the range.
Multi-function Digital Input Selection Error
A contradictory setting is assigned to multi-function contact inputs H1-03 to H1-08.
Terminal Board Mismatch Error oPE05 oPE06 oPE07 oPE08 oPE10 oPE16 oPE18 oPE20 oPE21
Reference Source Selection Error
Control Mode Selection Error
Correct the setting for the control method.
Multi-function Analog Input Selection Error
A contradictory setting is assigned to multi-function analog inputs H3-02 and H3-10.
Parameter Selection Error
A function has been set that cannot be used in the motor control method selected.
V/f Pattern Setting Error
The following setting errors have occurred where:
E1-04 is greater than or equal to E1-06, E1-06 is greater than or equal to E1-07, E1-07 is greater than or equal to E1-09, or E1-09 is greater than or equal to E1-11.
Energy Savings Constants Error
Parameter Setting Error, Online Tuning Parameter Setting Error
• The input from load cell with load condition 1 (S3-29) is set to the same value as load condition 2
(S3-30).
• DWELL 2 related parameters are not set correctly.
• Parameters that control Online Tuning are not set correctly.
PG-F3 Setting Error
The encoder signal frequency is too high.
Elevator Parameter Setting Fault
Elevator parameters are not set correctly.
5
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 139
TOEP_C710616_38H_7_0.book 140 ページ 2015年11月11日 水曜日 午後7時40分
5 Troubleshooting
◆
Auto-Tuning Fault Detection
Auto-Tuning faults in this section are displayed on the digital operator and will cause the motor to coast to a stop.
Auto-Tuning faults do not trigger a multi-function digital output set for fault or alarm output.
An End error on the digital operator display indicates Auto-Tuning has successfully completed with discrepancies in the calculations. Check the cause of the End error using the tables in this section and perform Auto-Tuning again after fixing the cause.
The drive may be used in the application if no cause can be identified despite the existence of an End error.
An Er error indicates that Auto-Tuning has not completed successfully. Check for the cause of the error using the tables in this section, and perform Auto-Tuning again after fixing the cause.
■
Auto-Tuning Codes, Causes, and Possible Solutions
Table 38 Auto-Tuning Codes, Causes, and Possible Solutions
Digital Operator Display
End1
End2
End3
End4
End5
End6
End7
End8
End9
End10
Er-01
Error Name
Excessive V/f Setting (detected only during Rotational Auto-Tuning, and displayed after Auto-Tuning is complete)
Motor Iron-Core Saturation Coefficient (detected only during Rotational Auto-Tuning and displayed after Auto-Tuning is complete)
Rated Current Setting Alarm (displayed after Auto-Tuning is complete)
Adjusted Slip Calculation Error
Resistance Tuning Error
Leakage Inductance Alarm
No-Load Current Alarm
Rescue Operation Speed Warning
Rescue Operation Rotor Pole Position Search Warning
Rescue Operation Rotor Polarity Detection Warning
Motor Data Error
Er-02
Er-03
Er-04
Alarm
STOP Button Input
Line-to-Line Resistance Error
Er-05
Er-08
Er-09
Er-10
Er-11
Er-12
Er-13
Er-18
Er-19
Er-20
Er-21
Er-22
Er-23
Er-24
No-Load Current Error
Rated Slip Error
Acceleration Error
Motor Direction Error
Motor Speed Fault
Current Detection Error
Leakage Inductance Error
Induction Voltage Error
Inductance Error
Stator Resistance Error
Z Pulse Correction Error
Initial Rotor Pole Search Error
Non-rotating Encoder Offset Tuning Warning
Auto-Tuning Error for PG-E3 Encoder Characteristics
140 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 141 ページ 2015年11月11日 水曜日 午後7時40分
5 Troubleshooting
◆
Copy Function Related Displays
■
Tasks, Errors, and Troubleshooting
The table below lists the messages and errors that may appear when using the Copy function.
When executing the tasks offered by the Copy function, the operator will indicate the task being performed. When an error occurs, a code appears on the operator to indicate the error. Note that errors related to the Copy function do not trigger a multi-function output terminal that has been set up to close when a fault or alarm occurs. To clear an error, simply press any key on the operator and the error display will disappear.
lists the corrective action that can be taken when an error occurs.
Note: 1.
Whenever using the copy function, the drive should be fully stopped.
2.
The drive will not accept an Up/Down command while the Copy function is being executed.
3.
Parameters can only be saved to a drive when the voltage class, capacity, control mode, and software version match.
Table 39 Copy Function Task and Error Displays
Digital Operator Display
CoPy
CPEr
CPyE
CSEr dFPS
ECE
ECS
EdE
EiF ndAT rdEr rEAd vAEr vFyE vrFy
End
EPE
ErE
EvE iFEr
Task
Writing Parameter Settings (flashing)
Control Mode Mismatch
Error Writing Data
Copy Unit Error
Drive Model Mismatch
Copy Error
Checksum Error
Write Impossible
Write Data Error
Task Complete
ID Mismatch
Data Error
Verify Error
Communication Error
Model, Voltage Class, Capacity Mismatch
Error Reading Data
Reading Parameter Settings (flashing)
Voltage Class, Capacity Mismatch
Parameter settings in the drive and those saved to the copy function are not the same
Comparing Parameter Settings (flashing)
5
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 141
TOEP_C710616_38H_7_0.book 142 ページ 2015年11月11日 水曜日 午後7時40分
5 Troubleshooting
■
Fault Reset Methods
When a fault occurs, the cause of the fault must be removed and the drive must be restarted. The table below lists the different ways to restart the drive.
After the Fault Occurs Procedure
Fix the cause of the fault, restart the drive, and reset the fault
Press on the digital operator when error code is displayed.
Resetting via Fault Reset Digital
Input S4
Close then open the fault signal digital input via terminal S4. S4 is set for “Fault Reset” as default (H1-04 = 14).
YEA_
RESET
DIGITAL OPERATOR JVOP-180 ALARM
- MODE DRV oC
Overcurrent
FWD RESET
F1
ESC
F2
LO
RE
RESET
RUN
ENTER
STOP
Drive
Fault Reset Switch
S4 Fault Reset Digital Input
SC Digital Input Common
2
ON
If the above methods do not reset the fault, turn off the drive main power supply.
Reapply power after the digital operator display is out.
1 OFF
Note: If the Up/Down command is present, the drive will disregard any attempts to reset the fault. Remove the Up/Down command before attempting to clear a fault situation.
142 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 143 ページ 2015年11月11日 水曜日 午後7時40分
6 Periodic Inspection & Maintenance
6 Periodic Inspection & Maintenance
◆
Inspection
Power electronics have limited life and may exhibit changes in characteristics or performance deterioration after years of use under normal conditions. To help avoid such problems, it is important to perform preventive maintenance and periodic inspection on the drive.
Drives contain a variety of power electronics such as power transistors, semiconductors, capacitors, resistors, fans, and relays. The electronics in the drive serve a critical role in maintaining proper motor control.
Follow the inspection lists provided in this chapter as a part of a regular maintenance program.
Note: The drive will require more frequent inspection if it is placed in harsh environments, such as:
• High ambient temperatures
• Frequent starting and stopping
• Fluctuations in the AC supply or load
• Excessive vibrations or shock loading
• Dust, metal dust, salt, sulfuric acid, chlorine atmospheres
• Poor storage conditions.
Perform the first equipment inspection one to two years after installation.
■
Recommended Daily Inspection
outlines the recommended daily inspection for Yaskawa drives. Check the following items on a daily basis to avoid premature deterioration in performance or product failure. Copy this checklist and mark the “Checked” column after each inspection.
Table 40 General Recommended Daily Inspection Checklist
Inspection Category
Motor
Cooling
Environment
Load
Power Supply Voltage
Inspect for abnormal oscillation or noise coming from the motor.
Inspect drive cooling fan and circulation fan operation.
Inspection Points
Inspect for abnormal heat generated from the drive or motor and visible discoloration.
Corrective Action
• Check the load coupling.
• Measure motor vibration.
• Tighten all loose components.
Check for excessive load.
• Excessive load.
• Loose connections.
• Dirty heatsink or motor.
• Ambient temperature.
Check for the following:
• Clogged or dirty fan.
• Correct fan operation parameter setting.
Verify the drive environment complies with the specifications listed in
Installation Environment on page 17 .
The drive output current should not be higher than the motor or drive rating for an extended period of time.
Check main power supply and control voltages.
Eliminate the source of contaminants or correct poor environment.
Check for the following:
• Excessive load.
• Correct motor parameter settings.
• Correct the voltage or power supply to within nameplate specifications.
• Verify all main circuit phases.
Checked
6
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 143
TOEP_C710616_38H_7_0.book 144 ページ 2015年11月11日 水曜日 午後7時40分
6 Periodic Inspection & Maintenance
■
Recommended Periodic Inspection
should generally be performed once a year, the drive may require more frequent inspection in harsh environments or with rigorous use. Operating and environmental conditions, along with experience in each application, will determine the actual inspection frequency for each installation. Periodic inspection will help to avoid premature deterioration in performance or product failure. Copy this checklist and mark the “Checked” column after each inspection.
Periodic Inspection
WARNING!
Electrical Shock Hazard. Do not inspect, connect, or disconnect any wiring while the power is on. Failure to comply can result in serious personal injury. Before servicing the drive, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. After shutting off the power, wait for at least the amount of time specified on the drive before touching any components.
Table 41 Periodic Inspection Checklist
Inspection Area
General
Conductors and
Wiring
Terminals
Relays and
Contactors
Braking Resistors
Electrolytic
Capacitor
Diode, IGBT (Power
Transistor)
Operation Check
General
Inspect for dirt, foreign particles, or dust collection on components.
Inspection Points
Main Circuit Periodic Inspection
• Inspect equipment for discoloration from overheating or deterioration.
• Inspect for damaged or deformed parts.
Corrective Action
• Replace damaged components as required.
• The drive has few serviceable parts and may require complete drive replacement.
• Inspect enclosure door seal if used.
• Remove foreign particles and dust by sucking them out with a vacuum cleaner to avoid touching parts.
• Replace components if cleaning is not possible.
• Inspect wiring and connections for discoloration, damage, or heat stress.
• Inspect wire insulation and shielding for wear.
Inspect terminals for stripped, damaged, or loose connections.
• Inspect contactors and relays for excessive noise during operation.
• Inspect coils for signs of overheating such as melted or cracked insulation.
Inspect for discoloration of heat stress on or around resistors.
Repair or replace damaged wiring.
Tighten loose screws and replace damaged screws or terminals.
• Check coil voltage for overvoltage or undervoltage conditions.
• Replace damaged removable relays contactors or circuit board.
• Minor discoloration may be acceptable.
• Check for loose connections if discoloration exists.
• Inspect for leaking, discoloration, or cracks.
• Check if the cap has come off, for any swelling, or if the sides have burst open.
The drive has few serviceable parts and may require complete drive replacement.
Inspect for dust or other foreign material collected on the surface.
Remove foreign particles and dust by sucking them out with a vacuum cleaner to avoid touching parts.
Motor Periodic Inspection
Check for increased vibration or abnormal noise.
Stop the motor and contact qualified maintenance personnel as required.
Control Circuit Periodic Inspection
• Inspect terminals for stripped, damaged, or loose connections.
• Make sure all terminals have been properly tightened.
• Tighten loose screws and replace damaged screws or terminals.
• If terminals are integral to a circuit board, then board or drive replacement may be required.
Checked
144 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 145 ページ 2015年11月11日 水曜日 午後7時40分
6 Periodic Inspection & Maintenance
Inspection Area
Circuit Boards
Inspection Points Corrective Action
Check for any odor, discoloration, and rust. Make sure connections are properly fastened and that no dust or oil mist has accumulated on the surface of the board.
• Fix any loose connections.
• If an antistatic cloth or vacuum plunger cannot be used, replace the board.
• Do not use any solvents to clean the board.
• Remove foreign particles and dust by sucking them out with a vacuum cleaner to avoid touching parts.
• The drive has few serviceable parts and may require complete drive replacement.
Cooling System Periodic Inspection
Checked
Cooling Fan,
Circulation Fan,
Control Board
Cooling Fan
• Check for abnormal oscillation or unusual noise.
• Check for damaged or missing fan blades.
Clean or replace the fan.
Heatsink
Air Duct
Digital Operator
Inspect for dust or other foreign material collected on the surface.
Remove foreign particles and dust by sucking them out with a vacuum cleaner to avoid touching parts.
Inspect air intake and exhaust openings. They must be free from obstruction and properly installed.
• Visually inspect the area.
• Clear obstructions and clean air duct as required.
Display Periodic Inspection
• Make sure data appears on the operator properly.
• Inspect for dust or other foreign material that may have collected on surrounding components.
• Contact a Yaskawa representative if there is any trouble with the display or keypad.
• Clean the digital operator.
◆
Periodic Maintenance
The drive has Maintenance Monitors that keep track of component wear. This feature provides advance maintenance warning and eliminates the need to shut down the entire system for unexpected problems. The drive allows the user to check predicted maintenance periods for the components listed below.
• Cooling Fan, Circulation Fan, Control Board Cooling Fan
• Electrolytic Capacitors
• Inrush Prevention Circuit
• IGBTs
For replacement parts, contact the distributor where the drive was purchased or contact Yaskawa directly.
■
Replacement Parts
contains the estimated performance life of components that require replacement during the life of the drive. Only use Yaskawa replacement parts for the appropriate drive model and revision.
Table 42 Estimated Performance Life
Component
Cooling Fan, Circulation Fan
Electrolytic Capacitors
Estimated Performance Life
10 years
<1> The drive has few serviceable parts and may require complete drive replacement.
NOTICE: Estimated performance life based on specific usage conditions. These conditions are provided for the purpose of replacing parts to maintain performance. Some parts may require more frequent replacement due to poor environments or rigorous use. Usage conditions for estimated performance life:
Ambient temperature: Yearly average of 40 ° C (104 ° F) (IP00 enclosure)
Load factor: 80% maximum
Operation time: 24 hours a day
6
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 145
TOEP_C710616_38H_7_0.book 146 ページ 2015年11月11日 水曜日 午後7時40分
6 Periodic Inspection & Maintenance
Performance Life Monitors Maintenance Monitors
The drive calculates the maintenance period for components that may require replacement during the life of the drive. A percentage of the maintenance period is displayed on the digital operator by viewing the appropriate monitor parameter.
When the maintenance period reaches 100%, there is increased risk that the drive may malfunction. Yaskawa recommends checking the maintenance period regularly to ensure maximum performance life.
Refer to Recommended Periodic Inspection on page 144 for more details.
Table 43 Performance Life Monitors Used for Component Replacement
Parameter
U4-03
U4-04
U4-05
U4-06
U4-07 IGBT
Component
Cooling Fan, Circulation Fan,
Control Board Cooling Fan
DC Bus Capacitors
Inrush (pre-charge) Relay
Contents
Displays the accumulated operation time of the fan, from 0 to 99999 hours. This value is automatically reset to 0 once it reaches 99999.
Displays the accumulated fan operation time as a percentage of the specified maintenance period.
Displays the accumulated time the capacitors are used as a percentage of the specified maintenance period.
Displays the number of times the drive is powered up as a percentage of the performance life of the inrush circuit.
Displays the percentage of the maintenance period reached by the IGBTs.
Alarm Outputs for Maintenance Monitors
An output can be set up to inform the user when a specific components has neared its expected performance life.
When one of multi-function digital output terminals has been assigned the maintenance monitor function (H2 = 2F), the terminal will close when the cooling fan, DC bus capacitors, or DC bus pre-charge relay reach 90% of the expected performance life, or when the IGBTs have reached 50% of their expected performance life. Additionally the digital
Table 44 Maintenance Alarms
Alarm Display
LED Operator LCD Operator
Function Corrective Action
LT-1
LT-2
LT-3
LT-4
TrPC
The cooling fans have reached 90% of their designated lifetime.
The DC bus capacitors have reached 90% of their designated lifetime.
The DC bus charge circuit has reached 90% of its designated lifetime.
The IGBTs have reached 50% of their designated lifetime.
The IGBTs have reached 90% of their designated lifetime.
Replace the cooling fan.
Replace the drive.
Replace the drive.
Check the load, carrier frequency, and output frequency.
Replace the drive.
<1> This alarm message will be output only if the Maintenance Monitor function is assigned to one of the digital outputs (H2 = 2F). The alarm will also trigger a digital output that is programmed for alarm indication (H2 = 10).
<2> This alarm message will always be output, even if the Maintenance Monitor function is not assigned to any of the digital outputs (H2 =
2F). The alarm will also trigger a digital output that is programmed for alarm indication (H2 = 10).
Related Drive Parameters
Use parameters o4-03, o4-05, o4-07, and o4-09 to reset a Maintenance Monitor to zero after replacing a specific component.
Refer to Parameter Table on page 166
for details on parameter settings.
NOTICE: If these parameters are not reset after the corresponding parts have been replaced, the Maintenance Monitor function will continue to count down the performance life from the value that was reached with the old part. If the Maintenance Monitor is not reset, the drive will not have the correct value of the performance life for the new component.
146 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 147 ページ 2015年11月11日 水曜日 午後7時40分
6 Periodic Inspection & Maintenance
◆
Drive Replacement
■
Serviceable Parts
The drive contains some serviceable parts. The following parts can be replaced over the life span of the drive:
• Terminal board I/O PCBs
• Cooling fan(s)
• Front cover
Replace the drive if the main power circuitry is damaged. Contact your local Yaskawa representative before replacing parts if the drive is still under warranty. Yaskawa reserves the right to replace or repair the drive according to Yaskawa warranty policy.
■
Terminal Board
CAUTION!
Crush Hazard. Carrying the drive by the front cover may cause the main body of the drive to fall, resulting in minor or moderate injury. Always hold the case when carrying the drive.
NOTICE: Correctly set parameter o2-04 when replacing the control terminal board. Failure to comply may result in drive damage due to lack of protective functions and poor drive performance.
The drive has a modular I/O terminal block that facilitates quick drive replacement. The terminal board contains on-board memory that stores all drive parameter settings and allows the parameters to be saved and transferred to the replacement drive. To transfer the terminal board, disconnect the terminal board from the damaged drive then reconnect it to the replacement drive. Once transferred, there is no need to manually reprogram the replacement drive.
Figure 70
Note: If the damaged drive and the new replacement drive are have different capacities, the data stored in the control terminal board cannot be transferred to the new drive and an oPE01 error will appear on the display. The control terminal board can still be used, but parameter setting from the old drive cannot be transferred. The replacement drive must be initialized and manually programmed.
YEA_com mon
A E
B
C D
A – Removable terminal board
B – Charge LED
C – Bottom cover
D – Bottom cover screws
E – Control terminal board locking screws
Figure 77 Terminal Board
6
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 147
TOEP_C710616_38H_7_0.book 148 ページ 2015年11月11日 水曜日 午後7時40分
6 Periodic Inspection & Maintenance
■
Replacing the Drive
WARNING!
Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply can result in serious personal injury. Before servicing the drive, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. After shutting off the power, wait for at least the amount of time specified on the drive before touching any components.
WARNING!
Electrical Shock Hazard. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in serious injury. Installation, maintenance, inspection and servicing must be performed only by authorized personnel familiar with installation, adjustment and maintenance of AC drives.
NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
The following procedure explains how to replace a drive. This section provides instructions for drive replacement only.
To install option cards or other types of options, refer to the specific manuals for those options.
NOTICE: When transferring a braking transistor, braking resistor, or other type of option from a damaged drive to a new replacement drive, make sure they are working properly before reconnecting them to the new drive. Replace broken options to prevent immediate break down of the replacement drive.
Figure 71
1.
Remove the terminal cover. Refer to
Terminal Cover on page 29 for details.
Note: The shape of the terminal covers and the numbers of the screws differ depending on the drive models.
YEA_ comm on
Figure 72
Figure 78 Drive Replacement: Removing the Terminal Cover
2.
Loosen the screws holding the terminal board in place. Remove the screw securing the bottom cover and remove the bottom cover from the drive.
YEA_com mon
Figure 79 Drive Replacement: Removing the Control Terminal Board
148 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 149 ページ 2015年11月11日 水曜日 午後7時40分
6 Periodic Inspection & Maintenance
Figure 73
3.
Slide the terminal board as illustrated by the arrows to remove it from the drive along with the bottom cover.
YEA_ comm on
Figure 80 Drive Replacement: Remove the Control Terminal Board
Figure 74
YEA_c ommon
Figure 81 Drive Replacement: Removable Control Terminal Board
Disconnected from the Drive
4.
Disconnect all option cards and options. Make sure they are intact before reusing them.
5.
Replace the drive and wire the main circuit.
Installing the Drive
1.
screw to fasten the terminal block into place.
Figure 75
YEA_ comm on
Figure 82 Drive Replacement: Installing the Control Terminal Board
2.
Reconnect all options to the new drive in the same way they were installed in the old drive. Connect option boards to the same option ports in the new drive that were used in the old drive.
3.
Put the terminal cover back into its original place.
4.
After powering on the drive, all parameter settings are transferred from the terminal board to the drive memory. If an oPE04 error occurs, load the parameter settings saved on the terminal board to the new drive by setting parameter A1-03 to 5550. Reset the Maintenance Monitor function timers by setting parameters o4-01 through o4-12 to 0, and parameter o4-13 to 1.
6
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 149
TOEP_C710616_38H_7_0.book 150 ページ 2015年11月11日 水曜日 午後7時40分
7 Option Card Installation
7 Option Card Installation
This section provides instructions on installing the option cards listed in
.
◆
Prior to Installing the Option
Prior to installing the option, wire the drive, make the necessary connections to the drive terminals, and verify that the
drive functions normally. Refer to the Table 45 for information on wiring and connecting the drive.
those option cards.
Table 45 Option Card Installation
Option Card
PG-B3, PG-X3
, PG-E3
DO-A3, AO-A3
Connector
CN5-C
CN5-C
CN5-A, B, C
CN5-A
Number of Cards Possible
2
1
1
1
<1> If two PG option cards are connected, use both CN5-B and CN5-C. If only one PG option card is connected to the drive, use the CN5-C connector.
<2> These option cards are not available for the application with Motor 2 Selection.
<3> When DI-A3 is to be used as monitors, the card can be connected to any of CN5-A, CN5-B or CN5-C. The input status of DI-A3 can then be viewed using U1-17.
Figure 83 shows an exploded view of the drive with the option and related components for reference.
Figure 76
A
B
C
L
K
J
I
D
E
F
H
G
YEA_common
A – Insertion point for CN5
B – Option card
C – Included screws
D – Front cover
E – Digital operator
F – Terminal cover
G – Removable tabs for wire routing
H – Ground wire
I – Drive grounding terminal (FE)
J – Connector CN5-A
K – Connector CN5-B
L – Connector CN5-C
Figure 83 Installing an Option Card
150 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 151 ページ 2015年11月11日 水曜日 午後7時40分
7 Option Card Installation
◆
Installing the Option
Refer to the instructions below to install the option.
DANGER!
Electrical Shock Hazard. Disconnect all power to the drive and wait at least the amount of time specified on the drive front cover safety label. After all indicators are off, measure the DC bus voltage to confirm safe level, and check for unsafe voltages before servicing to prevent electric shock. The internal capacitor remains charged even after the power supply is turned off.
WARNING!
Electrical Shock Hazard. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in death or serious injury. Maintenance, inspection, and replacement of parts must be performed only by authorized personnel familiar with installation, adjustment and maintenance of AC drives and Option Cards.
NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling the option, drive, and circuit boards. Failure to comply may result in ESD damage to circuitry.
NOTICE: Damage to Equipment. Tighten all terminal screws to the specified tightening torque. Failure to comply may cause the application to operate incorrectly or damage the drive.
1.
Shut off power to the drive, wait the appropriate amount of time for voltage to dissipate, then remove the digital
operator (E) and front covers (D, F). Refer to Digital Operator and Front Cover on page 31 .
Figure 77
YEA_common
D
E
F
Figure 78
Figure 84 Remove the Front Covers and Digital Operator
2.
Insert the option card (B) into the CN5-A (J), CN5-B (K) or CN5-C (L) connectors located on the drive and fasten it into place using one of the included screws (C).
YEA_common
A
B
C
L
K
J
Figure 85 Insert the Option Card
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 151
7
TOEP_C710616_38H_7_0.book 152 ページ 2015年11月11日 水曜日 午後7時40分
7 Option Card Installation
Figure 79
3.
Connect one end of the ground wire (H) to the ground terminal (I) using one of the remaining screws (C). Connect the other end of the ground wire (H) to the remaining ground terminal and installation hole on the option (B) using the last remaining provided screw (C).
YEA_common
B
C
I
H
Figure 86 Connect the Ground Wire
Note: 1.
The option package includes two ground wires. Use the longer wire when plugging the option into connector CN5-C on the drive side.
Use the shorter wire when plugging the option into connector CN5-B. Refer to the option card instruction manual for more information.
2.
There are two screw holes on the drive for use as ground terminals (I). When connecting three options, two ground wires will need to share the same drive ground terminal.
4.
Prepare and connect the wire ends as shown in Figure 87 and Figure 88 .
precaution to ensure that each wire is properly connected and wire insulation is not accidentally pinched into electrical terminals.
WARNING!
Fire Hazard. Tighten all terminal screws according to the specified tightening torque. Loose electrical connections could result in death or serious injury by fire due to overheating electrical connections. Tightening screws beyond the specified tightening torque may result in erroneous operation, damage to the terminal block, or cause a fire.
NOTICE: Heat shrink tubing or electrical tape may be required to ensure that cable shielding does not contact other wiring. Insufficient insulation may cause a short circuit and damage the option or drive.
Figure 80
Shield Insulation
PG option terminal PG at motor
B 3
FE/SD
Ground Terminal
Shield sheath
(Insulate with electrical tape or shrink tubing)
Figure 87 Preparing Ends of Shielded Cable
Figure 81
Screwdriver blade size
YEA_common Preparing wire ends:
Pull back the shielding and lightly twist the end with fingers, keeping the ends from fraying.
about 5.5 mm (0.22 in.)
When not using crimped insulated sleeves
Blade depth of
0.4 mm (0.015 in.) or less
Blade width of
2.5 mm (0.1 in.) or less
Loosen the screws and insert the wire into the opening on the terminal block.
Shielded cable
(do not solder ends)
Figure 88 Preparing and Connecting Cable Wiring
Option terminal block
152 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 153 ページ 2015年11月11日 水曜日 午後7時40分
7 Option Card Installation
5.
Figure 93 for wiring instructions.
Refer to Terminal Functions on page 154 for a detailed description of the option terminal functions.
■
Connecting PG-B3 Option
Parameter Settings and Connections for Different Encoder Types
• Connecting a Single-Pulse Encoder
When using a single-pulse encoder in V/f with PG control mode, connect the pulse output from the PG to the option and set drive parameter F1-21 to 0.
• Connecting a Two-Pulse Encoder
When using a two-pulse encoder, connect the A and B pulse outputs on the PG to the option and set F1-21 to 1.
When using a two-pulse encoder in Closed Loop Vector control mode, connect pulse outputs A and B from the encoder to the corresponding terminals on the option.
• Connecting a Two-Pulse Encoder with Z Marker Pulse
When using a two-pulse encoder with Z marker pulse, connect the A, B, and Z pulse outputs to the corresponding terminals on the option.
Control Method
No. of Encoders
Single Pulse (A)
Two Pulse (AB Quadrature)
Two Pulse with Marker (ABZ)
V/f with PG
1 (CN5-C)
F1-21 = 0
2 (CN5-B)
F1-37 = 0
F1-21 = 1
F1-21 = 1
F1-37 = 1
F1-37 = 1
Closed Loop Vector
1 (CN5-C)
N/A
2 (CN5-B)
N/A
No setting required
No setting required
No setting required
No setting required
Connection Diagram of PG-B3
for a detailed description of the option board terminal functions.
Refer to Wire Gauges and Tightening Torques on page 155 for information on making cables.
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
YASKAWA
Drive
M
FE
CN5
PG B3
Option
NC
TB1
A+
A
B+
B
Z+
Z
SD
FE
3
4
5
6
E
TB2
IP
IG
1
2
AO
IG
BO
IG
ZO
IG
PG
A pulse monitor signal
B pulse monitor signal
Z pulse monitor signal
Ground wire
Twisted-pair shielded line
Main circuit terminal
Control circuit terminal
B 3
<1> Ground the shield on the PG side and the drive side. If noise problems arise in the PG signal, remove the shield ground from one end of the signal line or remove the shield ground connection on both ends.
Figure 89 PG-B3 Option and Encoder Connection Diagram
Note: The PG-B3 Option reads a maximum input frequency from the PG encoder of 50 kHz. Be sure to select an PG encoder with an output pulse frequency of maximum 50 kHz when operating at maximum speed.
7
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 153
TOEP_C710616_38H_7_0.book 154 ページ 2015年11月11日 水曜日 午後7時40分
7 Option Card Installation
Take the following steps to prevent erroneous operation caused by noise interference:
• Use shielded wire for the PG encoder signal lines.
• Limit the length of all motor output power cables to less than 100 m. Limit the length of open-collector output lines to less than 50 m.
• Use separate conduit or cable tray dividers to separate option control wiring, main circuit input power wiring, and motor output power cables.
Interface Circuit
• Complementary Output
Figure 82
Vcc PG Encoder
PG-B3
470
Ω
12 V
330 Ω
IP
A+,B+,Z+
A-,B-,Z-
330
Ω
IG
A,B,Z
0 V
0 V
AO,BO,ZO
Monitor Signals
IG
Figure 90 Complementary Outputs for the Interface Circuit
• Open-Collector Outputs
Figure 83
PG B3
470
Ω
12 V
330
Ω
IP
A+,B+,Z+
A ,B ,Z
330 Ω
IG
AO,BO,ZO
IG
Vcc
PG Encoder
A,B,Z
0 V
Monitor Signals
Figure 91 Open-Collector Outputs for the Interface Circuit
Terminal Functions
Table 46 Option Terminal Functions
Terminal
Block
Terminal Function Description
TB1
TB2
TB1
TB2
A+
A–
B+
B–
Z+
Z–
SD
FE
IP
IG
AO
BO
ZO
IG
A+ pulse signal input
A– pulse signal input
B+ pulse signal input
B– pulse signal input
Z+ pulse signal input
Z– pulse signal input
NC pin (open)
Ground
PG power supply
PG power supply common
A pulse monitor signal
B pulse monitor signal
Z pulse monitor signal
Monitor signal common
• Pulse signal inputs from the PG.
• Signal inputs from complementary and open-collector outputs
• Signal level
H level: 8 to 12 V
L level: 2.0 V or less
For use when cables shields should not be grounded
Used for grounding shielded lines
• Output voltage: 12.0 V ± 5%
• Outputs the monitor signal for the A, B, and Z pulses from the PG speed control card
• For open collector outputs from the option
• Max voltage: 24 V
• Max current: 30 mA
<1> A separate UL Listed class 2 power supply is necessary when the PG requires more than 200 mA to operate.
154 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 155 ページ 2015年11月11日 水曜日 午後7時40分
7 Option Card Installation
Wire Gauges and Tightening Torques
Wire gauge and torque specifications are listed in
. For simpler and more reliable wiring, use crimp ferrules on the wire ends. Refer to the option manuals for the wire size and torque specifications of other options.
A+, A–, B+,
B–, Z+, Z–,
FE, IP, IG
AO, IG, BO,
IG, ZO, IG
M2
Table 47 Wire Gauges and Tightening Torques
Tightening
Torque
N m
(lb.in.)
0.22 to 0.25
(1.95 to 2.21)
Bare Cable
Applicable
Gauges mm 2
Recomm.
Gauge mm 2
0.75
(18 AWG)
Stranded wire:
0.25 to 1.0
(24 to 17 AWG)
Solid wire:
0.25 to 1.5
(24 to 16 AWG)
Crimp Terminals
Applicable
Gauges mm 2
Recomm.
Gauge mm 2
0.5
(20 AWG)
0.25 to 0.5
(24 to 20 AWG)
Wire Type
Shielded twisted pair, etc.
Shielded cable, etc.
Crimp Terminals
Yaskawa recommends using CRIMPFOX 6 by Phoenix Contact or equivalent crimp terminals with the specifications listed in
for wiring to ensure proper connections.
Note: Properly trim wire ends so loose wire ends do not extend from the crimp terminals.
Table 48 Crimp Terminal Sizes
–
Wire Gauge mm 2
Phoenix Contact Model
L mm (in) d1
6 mm
(0.24 in.)
L d2
0.25 (24 AWG)
0.34 (22 AWG)
0.5 (20 AWG)
AI 0.25 - 6YE
AI 0.25 - 6BU
AI 0.34 - 6TQ
AI 0.5 - 6WH
10.5 (13/32)
10.5 (13/32)
12 (15/32) d1 mm (in)
0.8 (1/32)
0.8 (1/32)
1.1 (3/64) d2 mm (in)
2 (5/64)
2 (5/64)
2.5 (3/32)
PG Encoder Cables for PG-B3 Option
Yaskawa recommends using a LMA B-S185Y (complementary output) for cables running between the PG-B3
Option and the PG as show in
.
For instructions on wiring the terminal block, refer to
Figure 84
TB1
A+ A- B+ B- Z+ ZSD FE
TB2
IP IG AO IG BO IG ZO IG
3 4 5 6 E 1 2
TA1
PG encoder side
B
C
A
H
D
G
E
F
L
( Pin )
Figure 92 Wiring PG Encoder Cable
B 3
7
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 155
TOEP_C710616_38H_7_0.book 156 ページ 2015年11月11日 水曜日 午後7時40分
7 Option Card Installation
Option Terminal
IP
IG
A+
A–
B+
B–
FE
Table 49 Connecting the PG Encoder Cable Specification
6
E
4
5
Wire
1
2
3
PG Encoder Cable
Color
Blue
White
Yellow
White
Green
White
N/A (shield)
F
D
G
A
C
H
B
Table 50 PG Encoder Cable Types
Type
W5010
W5030
Length
50 m (164 ft.)
100 m (328 ft.)
Pin
Length
10 m (32 ft.)
30 m (98 ft.)
Type
W5050
W5100
■
Connecting PG-X3 Option
Parameter Settings and Connections for Different Encoder Types
• Connecting a Single-Pulse Encoder
When using a single-pulse encoder in V/f with PG control mode, connect the pulse output from the PG to the option and set drive parameter F1-21 to 0.
• Connecting a Two-Pulse Encoder
When using a two-pulse encoder, connect the A and B pulse outputs on the PG to the option and set F1-21 to 1.
When using a two-pulse encoder in Closed Loop Vector control mode, connect pulse outputs A and B from the encoder to the corresponding terminals on the option.
• Connecting a Two-Pulse Encoder with Z Marker Pulse
When using a two-pulse encoder with Z marker pulse, connect the A, B, and Z pulse outputs to the corresponding terminals on the option.
When using a two-pulse encoder in CLV/PM control mode, connect pulse outputs A and B from the encoder to the corresponding terminals on the option.
Control Method
No. of Encoders
Single Pulse (A)
Two Pulse (AB Quadrature)
Two Pulse with Marker (ABZ)
V/f with PG
1 (CN5-C) 2 (CN5-B)
F1-21 = 0
F1-21 = 1
F1-21 = 1
F1-37 = 0
F1-37 = 1
F1-37 = 1
Closed Loop Vector
1 (CN5-C) 2 (CN5-B)
N/A
No setting required
No setting required
N/A
No setting required
No setting required
156 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 157 ページ 2015年11月11日 水曜日 午後7時40分
7 Option Card Installation
Connection Diagram of PG-X3
for a detailed description of the option board terminal functions.
The positioning of jumper CN3 selects the PG encoder power supply voltage (5.5 V or 12 V). Select the voltage level for the PG encoder connected to the option and motor. If the wrong voltage is selected, the PG encoder may not operate properly or may become damaged as a result.
Refer to Setting the PG Encoder Power Supply Voltage on page 158 for details.
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
YASKAWA
Drive
PG X3
Option
NC
TB1
A+
A
B+
B
Z+
Z
SD
FE
M
PG
FE
CN5-B or
CN5-C
IP12
IP5
IG
CN3
TB2
IP
IG
SG b z+ z a+ a b+
A pulse monitor signal
B pulse monitor signal
Z pulse monitor signal
Ground wire twisted-pair shielded line
X3 main circuit terminal control circuit terminal
<1> Ground the shield on the PG side and the drive side. If noise problems arise in the PG signal, remove the shield ground from one end of the signal line or remove the shield ground connection on both ends.
Figure 93 PG-X3 Option and PG Encoder Connection Diagram
Note: The PG-X3 Option reads a maximum input frequency from the PG of 300 kHz. Be sure to select a PG with an output pulse frequency of maximum 300 kHz when operating at maximum speed.
Take the following steps to prevent erroneous operation caused by noise interference:
• Use shielded wire for the PG encoder signal lines.
• Use separate conduit or cable tray dividers to separate option control wiring, main circuit input power wiring, and motor output power cables.
Interface Circuit
Figure 85
PG Encoder
A,B,Z
PG X3
26LS32 level
A+,B+,Z+
600
Ω
A ,B ,Z a+,b+,z+ a ,b ,z
26LS31 level
SG
A,B,Z 26LS31 level
Monitor Signals
Figure 94 Interface Circuit (PG-X3)
7
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 157
TOEP_C710616_38H_7_0.book 158 ページ 2015年11月11日 水曜日 午後7時40分
7 Option Card Installation
Terminal Functions
TB1
Terminal Block
TB2
TB1
TB2
SG a+ a– b+ b– z+ z–
Table 51 Option Terminal Functions
Terminal
A+
A–
B+
B–
Z+
Z–
Function
A+ pulse signal input
A– pulse signal input
B+ pulse signal input
B– pulse signal input
Z+ pulse signal input
Z– pulse signal input
Description
• Inputs for the A channel, B channel, and Z pulses from the
PG encoder
• Signal level matches RS-422
SD
FE
IP
NC pin (open)
Open connection connectors for use when cable shields should not be grounded
Used as the shield ground termination point.
IG
Ground
PG encoder power supply
PG encoder power supply common
Monitor signal common
A+ pulse monitor signal
A- pulse monitor signal
B+ pulse monitor signal
B- pulse monitor signal
Z+ pulse monitor signal
Z- pulse monitor signal
• Output voltage: 12.0 V ± 5% or 5.5 V ± 5%
• Max. output current: 200 mA
• Output signal for monitoring A channel, B channel, and Z pulses from the PG encoder
• Signal level matches RS-422
<1> A separate UL Listed class 2 power supply is necessary when the PG requires more than 200 mA to operate.
Setting the PG Encoder Power Supply Voltage
For the PG-X3 Option, set the voltage for the PG encoder power supply using jumper CN3 located on the option.
NOTICE: The positioning of jumper CN3 selects the PG encoder power supply voltage (5.5 V or 12 V). Select the voltage level for the
PG encoder connected to the option and motor. If the wrong voltage is selected, the PG encoder may not operate properly or may become damaged as a result.
Voltage Level
Table 52 Setting the PG Encoder Power Supply Voltage (IP) with Jumper CN3
5.5 V ± 5% (default) 12.0 V ± 5%
5.5 V 12 V
CN3
Jumper CN3
5.5 V 12 V
CN3
Wire Gauges and Tightening Torques
the wire ends. Refer to the option manuals for the wire size and torque specifications of other options.
A+, A–, B+,
B–, Z+, Z–,
SD, FE, IP, IG a+, a–, b+, b–, z+, z–, SG
M2
Table 53 Wire Gauges and Tightening Torques
Tightening
Torque
N m
(lb.in.)
0.22 to 0.25
(1.95 to 2.21)
Bare Cable
Applicable
Gauges mm 2
0.75
(18 AWG)
Recomm.
Gauge mm 2
Stranded wire:
0.25 to 1.0
(24 to 17 AWG)
Solid wire:
0.25 to 1.5
(24 to 16 AWG)
Crimp Terminals
Applicable
Gauges mm 2
Recomm.
Gauge mm 2
0.5
(20 AWG)
0.25 to 0.5
(24 to 20 AWG)
Wire Type
Shielded twisted pair, etc.
Shielded cable, etc.
158 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 159 ページ 2015年11月11日 水曜日 午後7時40分
7 Option Card Installation
Crimp Terminals
Yaskawa recommends using CRIMPFOX 6 by Phoenix Contact or equivalent crimp terminals with the specifications listed in
for wiring to ensure proper connections.
Note: Properly trim wire ends so loose wire ends do not extend from the crimp terminals.
Table 54 Crimp Terminal Sizes
Wire Gauge mm 2
Phoenix Contact Model
L mm (in) d1
6 mm
(0.24 in.)
L d2
0.25 (24 AWG)
0.34 (22 AWG)
0.5 (20 AWG)
AI 0.25 - 6YE
AI 0.25 - 6BU
AI 0.34 - 6TQ
AI 0.5 - 6WH
10.5 (13/32)
10.5 (13/32)
12 (15/32) d1 mm (in)
0.8 (1/32)
0.8 (1/32)
1.1 (3/64) d2 mm (in)
2 (5/64)
2 (5/64)
2.5 (3/32)
6.
Route the option wiring.
Depending on the drive model, some drives may require routing the wiring through the side of the front cover to the outside. For drive models CIMR-LU2 0008 through 2 0033, 4 0005 through 4 0018, and 5 0003 through 5 0010, cut out the perforated openings on the left side of the drive front cover as shown in
and leave no sharp edges to damage wiring.
Route the wiring inside the enclosure as shown in Figure 95
-B for drive models CIMR-LU2 0047 through
2 0415, 4 0024 through 4 0605, and 5 0013 through 5 0200 that do not require routing through the front cover.
Figure 86
B
A
A – Route wires through the openings provided on the left side of the front cover.
(CIMR-LU2 0008 through 2 0033,
4 0005 through 4 0018, and
5 0003 through 5 0010)
B – Use the open space provided inside the drive to route option wiring.
(CIMR-LU2 0047 through 2 0415,
4 0024 through 4 0605, and
5 0013 through 5 0200)
<1> The drive will not meet IP20/NEMA 1, UL Type 1 requirements if wiring is exposed outside the enclosure.
Figure 95 Wire Routing Examples
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 159
7
TOEP_C710616_38H_7_0.book 160 ページ 2015年11月11日 水曜日 午後7時40分
7 Option Card Installation
Figure 87
7.
Replace and secure the front covers of the drive (D, F) and replace the digital operator (E).
YEA_common
D
E
F
Figure 96 Replace the Front Covers and Digital Operator
Note: Take proper precautions when wiring the option so that the front covers will easily fit back onto the drive. Make sure cables are not pinched between the front covers and the drive when replacing the covers.
Figure 88
8.
For the PG-B3 and PG-X3 Option, set drive parameters
A1: Initialization Parameters on page 166
and
Speed Control Card on page 179
for proper motor rotation.
With a two-pulse or three-pulse PG encoder, the leading pulse determines the motor rotation direction. A PG encoder signal with leading A pulse is considered to be rotating forward (counter-clockwise when viewing rotation from motor load side).
A pulse
The A pulse leads, followed by the B pulse displaced at 90 degrees
B pulse
Figure 89
Time →
Figure 97 Displacement of A and B Pulses
9.
After connecting the PG encoder outputs to the option, apply power to the drive and manually rotate the motor and check the rotation direction by viewing monitor U1-05 on the digital operator.
Reverse motor rotation is indicated by a negative value for U1-05; forward motor rotation is indicated by a positive value.
If monitor U1-05 indicates that the forward direction is opposite of what is intended, set F1-05 to 1, or reverse the
two A pulse wires with the two B pulse wires on option terminal TB1 as shown in Figure 98 .
B 3
A+ A- B+ B- Z+ ZA+ A- B+ B- Z+ Z-
3 4 5 6 5 6 3 4
Figure 98 A Channel and B Channel Wire Switching
10.
If switching the wires is inconvenient, set drive parameter F1-05 to 1 to switch the direction of how the option reads pulses from the PG encoder output.
Please note that when the drive is initialized using A1-03 =1110, 2220, 3330, the value for F1-05 will reset to factory default and the parameter will need to be adjusted again to switch the direction.
160 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 161 ページ 2015年11月11日 水曜日 午後7時40分
A Specifications
A Specifications
◆
Three-Phase 200 V Class Drives
Table 55 Power Ratings (Three-Phase 200 V Class)
Item
CIMR-LU2
Maximum Applicable Motor Capacity
(HP)
Rated Voltage
Rated Frequency
Input Allowable Voltage Fluctuation
Allowable Frequency
Fluctuation
Input Power (kVA)
Output
000
8 0011
2 3
001
4
4
001
8
3.7
(5)
002
5
7.5
003
3
10
004
7
15
Specification
006
0
20
007
5
25
008
5 0115
30 40
014
5
50
018
0
60
021
5
75
028
3
034
6
041
5
100 125 150
7.5
11 15.6 18.9 28 37 52 68 80 82 111 136 164 200 271 324 394
Three-phase 200 to 240 Vac 50/60 Hz/270 to 340 Vdc
-15 to 10%
±5%
Rated Output Current (A)
Overload Tolerance
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Speed (Hz)
4.1
5.8
7.8
9.5 14 18 27 36 44 37 51 62 75 91 124 148 180
3 4.2
5.3
6.7
9.5
12.6
17.9
23 29 32 44 55 69 82 108 132 158
<5> <5> <5> <5> <5> <5> <5> <5> <5> <5> <5> <6> <6> <6> <6> <6> <6>
8
11
14
17.5
25
33
47
60
75
85
115
145
180
215
283
346
415
150% of rated output current for 60 s
User adjustable between 2 and 15 kHz
User adjustable between 2 and 10 kHz
Three-phase 200 to 240 V (proportional to input voltage)
200 Hz (user-set)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and power supply impedance.
<3> DC is not available for UL standards.
<4> Rated motor capacity is calculated with a rated output voltage of 220 V.
<5> Carrier frequency can be set up to 8 kHz while keeping this current rating. Higher carrier frequency settings require derating.
<6> Carrier frequency can be set up to 5 kHz while keeping this current rating. Higher carrier frequency settings require derating.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 161
A
TOEP_C710616_38H_7_0.book 162 ページ 2015年11月11日 水曜日 午後7時40分
A Specifications
◆
Three-Phase 400 V Class Drives
Table 56 Power Ratings (Three-Phase 400 V Class)
Item
CIMR-LU4
Maximum Applicable Motor Capacity
(HP)
Rated Voltage
Rated Frequency
Input
Allowable Voltage
Fluctuation
Allowable Frequency
Fluctuation
Output
Input Power (kVA)
Rated Output Capacity
(kVA)
Rated Output Current
(A)
Overload Tolerance
Carrier Frequency
Maximum Output
Voltage (V)
Maximum Output Speed
(Hz)
Specification
0005 0006 0007 0009 0015 0018 0024 0031 0039 0045 0060
2
3.6
4.1
3.5
3.5
3
5.1
5.8
4.1
4.1
5
8.3
Three-phase 380 to 480 Vac 50/60 Hz 510 to 680 Vdc
9.5
6.3
6.3
7.5
12
10
16
-15 to 10%
±
15
23
5%
20
31
14
9.8
9.8
18
12
12
26
17
17
35
22
22
150% of rated output current for 60 s
User adjustable between 2 and 15 kHz
Three-phase 380 to 480 V (proportional to input voltage)
200 Hz (user-adjustable)
25
38
43
27
27
25-30
44
25-30
43
40
58
46.6 39.3 53.0
30
39
34
45
48
60
Maximum Applicable Motor Capacity
Input
Output
Item
CIMR-LU4
(HP)
Specification
0075 0091 0112 0150 0180 0216 0260 0304 0370 0450 0605
50-60 50-60 75 100 125-150 150 200 250 300 350
400-450
-
500
71 86 105 142 170 207 248 300 346 410 584
Rated Voltage
Rated Frequency
Allowable Voltage
Fluctuation
Allowable Frequency
Fluctuation
Input Power (kVA)
Rated Output Capacity
(kVA)
Rated Output Current
(A)
Overload Tolerance
Carrier Frequency
Three-phase 380 to 480 Vac 50/60 Hz 510 to 680 Vdc
-15 to 10%
± 5%
64.9 78.6 96.0 129.9 155
57 69 85 114 137
75
91
112
150
180
189
165
216
227
198
260
274
232
304
150% of rated output current for 60 s
User adjustable between 2 and 15 kHz
User adjustable between 2 and 10 kHz
316
282
370
375
343
450
534
461
605
User-adjustable between
2 and 5 kHz
Maximum Output
Voltage (V)
Maximum Output Speed
(Hz)
Three-phase 380 to 480 V (proportional to input voltage)
200 Hz (user-adjustable) 400 Hz (user-adjustable)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring conditions, and power supply impedance.
<3> DC is not available for UL standards.
162 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 163 ページ 2015年11月11日 水曜日 午後7時40分
A Specifications
<4> Rated motor capacity is calculated with a rated output voltage of 440 V.
<5> Carrier frequency can be set up to 8 kHz while keeping this current rating. Higher carrier frequency settings require derating.
<6> Carrier frequency can be set up to 5 kHz while keeping this current rating. Higher carrier frequency settings require derating.
<7> Carrier frequency can be set up to 2 kHz while keeping this current derating. Higher carrier frequency settings require derating.
◆
Three-Phase 600 V Class Drives
Table 57 Power Ratings (Three-Phase 600 V Class)
Item
CIMR-LU5A
Maximum Applicable
Motor Capacity
Input Current
(A)
Input
Rated Voltage
Rated
Frequency
Allowable
Voltage
Fluctuation
Allowable
Frequency
Fluctuation
Input Power
(kVA)
Rated Output
Capacity
(kVA)
Rated Output
Current (A)
Overload
Tolerance
Specification
0003 0004 0006 0010 0013 0017 0022 0027 0032 0041 0052 0062 0077 0099 0130 0172 0200
2
3.6
4.1
3.5
3.5
3
5.1
5.8
4.1
4.1
5
8.3
9.5
6.3
6.3
7.5
12
14
9.8
9.8
10
16
18
12
12.5
15
23
26
17
17
20
31
Three-phase 500 to 600 Vac 50/60 Hz
35
22
22
25
38
-10 (-15) to 10%
43
27
27
25-30
±
33
5%
38
32
32
40
44
50
41
41
50-60 50-60
54
62
52
52
150% of rated output current for 60 s
66
75
62
62
75
80
91
77
77
100
108
123
99
99
125
129
147
129
130
150
158
181
171
172
250
228
261
199
200
Outpu t
Carrier
Frequency
User adjustable between
2 and 15 kHz
User adjustable between
2 and 10 kHz
User adjustab le between
2 and 8 kHz
User adjustable between
2 and 3 kHz
Maximum
Output
Voltage (V)
Maximum
Output Speed
(Hz)
Three-phase 500 to 600 Vac (proportional to input voltage)
200 Hz (user-adjustable)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 575 V.
<4> Carrier frequency can be set up to 3 kHz while keeping this current derating. Higher carrier frequency settings require derating.
<5> Carrier frequency can be set up to 8 kHz while keeping this current derating. Higher carrier frequency settings require derating.
<6> Carrier frequency can be set up to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 163
A
TOEP_C710616_38H_7_0.book 164 ページ 2015年11月11日 水曜日 午後7時40分
A Specifications
◆
Drive Specifications
Note: 1.
Perform rotational Auto-Tuning to obtain the performance specifications given below.
2.
For optimum performance life of the drive, install the drive in an environment that meets the required specifications.
Control
Characterist ics
Protection
Functions
Item
Frequency Accuracy
(Temperature Fluctuation)
Frequency Setting Resolution
Specification
Control Method
The following control methods can be set using drive parameters:
• V/f Control (V/f)
• Open Loop Vector Control (OLV)
• Closed Loop Vector Control (CLV)
• Closed Loop Vector Control for PM (CLV/PM)
Frequency Control Range 0.01 to 200 Hz
Digital input: within ±0.01% of the max output speed [-10 to 40°C (14 to 104°F)]
Analog input: within ±0.1% of the max output speed [25 ±10°C (77 ±18°F)]
Digital inputs: 0.01 Hz
Analog inputs: 1/2048 of the maximum output speed setting (11 bit plus sign)
Output Speed Resolution 0.001 Hz
Frequency Setting Signal
Main speed frequency reference: DC -10 to +10 V (20 k Ω ), DC 0 to +10 V (20 k Ω ), 4 to 20 mA
(250 Ω ), 0 to 20 mA (250 Ω )
V/f: 150% at 3 Hz
OLV: 200% at 0.3 Hz
CLV, CLV/PM: 200% at 0 r/min
Speed Control Range
Speed Response
Torque Limit
V/f: 1:40
OLV: 1:200
CLV, CLV/PM: 1:1500
OLV: ± 0.2% [25 ±10°C (77 ±18°F)]
CLV: ± 0.02% [25 ±10°C (77 ±18°F)]
OLV: 10 Hz [25 ±10°C (77 ±18°F)]
CLV: 100 Hz
CLV/PM: 100 Hz
Parameters setting allow separate limits in four quadrants (available in OLV, CLV, CLV/PM)
Accel/Decel Ramp
Braking Transistor
V/f Characteristics
Main Control Functions
0.0 to 6000.0 s (4 selectable combinations of independent acceleration and deceleration settings, unit changeable to m/s 2 or ft/s 2 )
Models CIMR-LU2 0008 to 2 0115, 4 0005 to 4 0060, and 5 0003 to 5 0041 have a built-in braking transistor.
Freely programmable
Inertia Compensation, Position Lock at Start and Stop/Anti-Rollback Function, Overtorque/
Undertorque Detection, Torque Limit, Speed Reference, Accel/decel Switch, 5 Zone Jerk Settings,
Auto-Tuning (Stationary and Rotational Motor/Encoder Offset Tuning), Dwell, Cooling Fan on/off
Switch, Slip Compensation, Torque Compensation, DC Injection Braking at Start and Stop,
MEMOBUS/Modbus Comm. (RS-422/485 max, 115.2 kbps), Fault Reset, Removable Terminal
Block with Parameter Backup Function, Online Tuning, High Frequency Injection, Short Floor,
Rescue Operation (Light Load Direction Search Function), Inspection Run, Brake Sequence, Speed related parameters with elevator units display, etc.
Electronic thermal overload relay Motor Protection
Momentary Overcurrent
Protection
Overload Protection
Drive stops when output current exceeds 200% of rated output current
Overvoltage Protection
Undervoltage Protection
Drive stops after 60 s at 150% of rated output current
200 V class: Stops when DC bus voltage exceeds approx. 410 V
400 V class: Stops when DC bus voltage exceeds approx. 820 V
600 V class: Stops when DC bus voltage exceeds approx. 1040 V
200 V class: Stops when DC bus voltage falls below approx. 190 V
400 V class: Stops when DC bus voltage falls below approx. 380 V
600 V class: Stops when DC bus voltage falls below approx. 500 V
Heatsink Overheat Protection Thermistor
Stall Prevention Stall Prevention is available during acceleration, and during run.
Ground Protection
DC Bus Charge LED
Electronic circuit protection
Remains lit until DC bus voltage falls below 50 V
164 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 165 ページ 2015年11月11日 水曜日 午後7時40分
A Specifications
Environmen t
Item
Area of Use
Ambient Temperature
Humidity
Storage Temperature
Altitude
Vibration/Shock
Standards
Protection Design
Specification
Indoors
IP00 enclosure with top protective cover: [-10 to 40°C (14 to 104°F)]
IP00 enclosure: [-10 to 50°C (14 to 122 ° F)]
95 RH% or less (no condensation)
[-20 to 60°C (-4 to 140 ° F)] (short-term temperature during transportation)
Up to 1000 meters (3280 ft.) without derating, up to 3000 meters (9842 ft.) with output current and voltage derating
10 to 20 Hz: 9.8 m/s 2
20 to 55 Hz: 5.9 m/s 2 (CIMR-LU2 0008 to 2 0180, 4 0005 to 4 0150, and 5 0003 to
5 0077) or 2.0 m/s 2 (CIMR-LU2 0215 to 2 0415, 4 0180 to 4 0260, and 5 0099 to
5 0200)
• UL Underwriters Laboratories Inc:
UL508C Power Conversion Equipment
• IEC/EN 61800-3, IEC/EN 61800-5-1
• ISO International Organization for Standardization:
ISO/EN 13849-1 Cat. 3 PLd Safety of machinery - Safety-related parts of control systems (models
CIMR-L A )
ISO/EN 13849-1 Cat. 3 PLe Safety of machinery - Safety-related parts of control systems (models
CIMR-L F )
• IEC International Electrotechnical Commission:
IEC/EN 61508 SIL2 Functional safety of electrical/electronic/programmable electronic safety-related systems safety integrity level 2 (models CIMR-L A )
IEC/EN 61508 SIL3 Functional safety of electrical/electronic/programmable electronic safety-related systems safety integrity level 3 (models CIMR-L F )
• CSA Canadian Standards Association International
:
2411-02 Elevator Equipment - Enclosed Elevator-and Escalator Electrical Equipment
3211-06 Industrial Control Equipment - Motor Controllers - Miscellaneous
C22.2 No.04-04 Bonding and Grounding of Electrical Equipment
C22.2 No.14-05 Industrial Control Equipment
B44.1/ASME-A17.5-2004 Safety Code for Elevators and Escalator Electrical Equipment used by
CSA to evaluate the L1000 to Class 2411 (Elevator Equipment)
• ANSI/ASME American Society of Mechanical Engineers/American National Standards Institute:
ANSI/ASME A17.1-2007/B44-04 Safety Code for Elevators and Escalators, Dumbwaiters,
Moving Walks, Material Lifts, and Dumbwaiters with Automatic Transfer Devices using IEC/EN
12016:2004 immunity requirements.
ANSI/ASME-A17.5-2004/CSA B44.1 - Elevator and Escalator Electrical Equipment, used by
CSA to evaluate the L1000 to Class 2411 (Elevator Equipment)
IP00 enclosure with top protective cover, IP00
<1> The accuracy of these values depends on motor characteristics, ambient conditions, and drive settings. Specifications may vary with different motors and with changing motor temperature. Contact Yaskawa for consultation.
<2> For drives with B or earlier as the design revision order, 50 Hz is required. The design revision order and software version are printed on the
nameplate affixed to the side of the drive. Refer to Model Number on page 16
for details.
<3> Overload protection may be triggered when operating with 150% of the rated output current if the output speed is less than 6 Hz.
<4> Ground protection cannot be provided when the impedance of the ground fault path is too low, or when the drive is powered up while a ground fault is present at the output.
<5> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN 61800-5-2, ISO/EN
13849 Cat. 3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
■
Altitude Derating
The drive standard ratings are valid for an installation altitude up to 3000 m (9842 ft.). If the altitude exceeds 1000 m
(3280 ft.). both the drive rated voltage and the rated output current must be derated for 1% per 100 m (328 ft.). The maximum altitude is 3000 m (9842 ft.).
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 165
A
TOEP_C710616_38H_7_0.book 166 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
B Parameter Table
◆
A: Initialization Parameters
The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.
: Indicates that the parameter setting can be changed while the drive is operating the motor
Motor 2: Refers the second motor when the drive is operating two motors (use input terminals to switch between motors).
■
A1: Initialization Parameters
Setting No.
A1-00
A1-01
A1-02
A1-03
Name
Language Selection
Access Level Selection
Control Method Selection
Initialize Parameters
Description
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
7: Chinese
8: Czech
9: Russian
10: Turkish
11: Polish
12: Greek
Note: 1.
Language selection settings 8 to 12 can be selected from an LCD operator with version (REV) F or later. The version number of the LCD operator's PRG software is shown on the back of the digital operator.
2.
Language selection settings 8 to 12 are available in drive software PRG: 7017 or later.
0: View and set A1-01 and A1-04. U parameters can also be viewed.
1: User Parameters (access to a set of parameters selected by the user, A2-01 to
A2-32)
2: Advanced Access (access to view and set all parameters)
0: V/f Control
2: Open Loop Vector Control
3: Closed Loop Vector Control
7: Closed Loop Vector Control for PM Motors
0: No initialization
1110: User Initialize (parameter values must be stored using parameter o2-03)
2220: 2-wire initialization
5550: oPE04 error reset
A1-04 Password
A1-05 Password Setting
When the value set into A1-04 does not match the value set into A1-05, parameters
A1-01 through A1-03, and A2-01 through A2-33 cannot be changed.
Default: 0
Min: 0
Max: 12
Default: 2
Min: 0
Max: 2
Default: 2
Min: 0
Max: 7
Default: 0
Min: 0
Max: 5550
Default: 0000
Min: 0000
Max: 9999
<1> Parameter setting value is not reset to the default value when the drive is initialized.
166 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 167 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
A2: User Parameters
No.
Name Description
A2-01 to
A2-32
A2-33
User Parameters 1 to 32
Parameters that were recently edited are listed here. The user can also select parameters to appear here for quick access.
User Parameter Automatic
Selection
0: Parameters A2-01 through A2-32 are reserved for the user to create a list of User
Parameters.
1: Save history of recently viewed parameters. Recently edited parameters will be saved to A2-17 through A2-32 for quick access.
<5> Default setting is determined by the control mode (A1-02).
Setting
Min: A1-00
Max: S6-16
Default: 1
Min: 0
Max: 1
◆
b: Application
Application parameters configure the source of the Up/Down command, timer functions, the Dwell function, the Droop
Control function, Energy Savings, and a variety of other application-related settings.
■
b1: Operation Mode Selection
No.
b1-01 Speed Reference Selection b1-02 b1-03 b1-06 b1-08
Name
Up/Down Command
Selection
Stopping Method Selection
Digital Input Reading
Up/Down Command
Selection while in
Programming Mode
Description
0: Digital operator
1: Analog input terminals
2: MEMOBUS/Modbus communications
3: Option card
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option card
0: Ramp to stop
1: Coast to stop
4: Elevator Emergency Stop
Note: Setting 4 is available in the control mode CLV or CLV/PM for drives with software versions PRG: 7017 or later. The setting is 0 or 1 for software version PRG:
7016.
0: Input status is read once and processed immediately (for quick response).
1: Input is read twice and processed only if the status is the same in both readings
(robust against noisy signals).
0: Up/Down command not accepted while in the Programming Mode.
1: Up/Down command accepted while in the Programming Mode.
2: Prohibit entering Programming Mode during run.
b1-14 Phase Order Selection
0: U-V-W
1: U-W-V
Setting
Default: 0
Min: 0
Max: 3
Default: 1
Min: 0
Max: 3
Default: 0
Min: 0
Max: 4
Default: 1
Min: 0
Max: 1
Default: 0
Min: 0
Max: 2
Default: 0
Min: 0
Max: 1
■
b2: Magnetic Flux Compensation
No.
b2-08
Name
Magnetic Flux
Compensation Value
Description
Sets the magnetic flux compensation as a percentage of the no-load current value
(E2-03).
Setting
Default: 0%
Min: 0%
Max: 1000%
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 167
B
TOEP_C710616_38H_7_0.book 168 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
b4: Delay Timers
No.
b4-01 b4-02
Timer Function On-Delay
Time
Name
Timer Function Off-Delay
Time
Description
Used to set the on-delay and off-delay times for a digital timer output (H2 = 12).
The output is triggered by a digital input programmed to H1 = 18).
Setting
Default: 0.0 s
Min: 0.0 s
Max: 3000.0 s
Default: 0.0 s
Min: 0.0 s
Max: 3000.0 s
■
b6: Dwell Function
No.
Name b6-01 Dwell Speed at Start b6-02 Dwell Time at Start b6-03 Dwell Speed at Stop b6-04 Dwell Time at Stop
Description
Parameters b6-01 and b6-02 set the speed to hold and the time to maintain that speed at start.
Parameters b6-03 and b6-04 set the speed to hold and the time to maintain that speed at stop.
Setting
Default: 0.0%
Min: 0.0%
Max: 100.0%
Default: 0.0 s
Min: 0.0 s
Max: 10.0 s
Default: 0.0%
Min: 0.0%
Max: 100.0%
Default: 0.0 s
Min: 0.0 s
Max: 10.0 s
■
b7: Droop Control
No.
b7-01
Name
Droop Control Gain b7-02
Description
Sets the speed reduction gain applied at a torque reference of 100%. Set as a percentage of motor base speed.
Droop Control Delay Time Used to adjust the responsiveness of Droop Control.
Setting
Default: 0.0%
Min: 0.0%
Max: 100.0%
Default: 0.05 s
Min: 0.03 s
Max: 2.00 s
■
b8: Energy Saving
No.
b8-01
Name
Energy Saving Control
Selection b8-16 b8-17
Energy Saving Control
Constant (Ki)
Energy Saving Control
Constant (Kt)
0: Disabled
1: Enabled
Description
Enter the Energy Saving value (Ki) as specified on the motor name plate. (for IPM motors only)
Enter the Energy Saving value (Kt) as specified on the motor name plate. (for IPM motors only)
Setting
Default: 0
Min: 0
Max: 1
Default: 0.10
Min: 0.00
Max: 2.00
Default: 1.00
Min: 0.00
Max: 2.00
168 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 169 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
◆
C: Tuning
C parameters are used to adjust the acceleration and deceleration ramps, jerk settings, slip compensation, torque compensation, and carrier frequency selections.
■
C1: Acceleration and Deceleration Ramps
No.
C1-01
Name
Acceleration Ramp 1
Description
Sets the ramp to accelerate from 0 to maximum speed.
Setting
C1-02
Deceleration Ramp 1 Sets the ramp to decelerate from maximum speed to 0.
C1-03
Acceleration Ramp 2 Sets the ramp to accelerate from 0 to maximum speed.
C1-04
C1-05
Deceleration Ramp 2
Acceleration Ramp 3
(Motor 2 Accel Time 1)
Sets the ramp to decelerate from maximum speed to 0.
Sets the ramp to accelerate from 0 to maximum speed.
Default: 1.50
Min: 0.00 s
Max: 600.00
C1-06
Deceleration Ramp 3
(Motor 2 Decel Time 1)
Sets the ramp to decelerate from maximum speed to 0.
C1-07
Acceleration Ramp 4
(Motor 2 Accel Time 2)
Sets the ramp to accelerate from 0 to maximum speed.
C1-08
Deceleration Ramp 4
(Motor 2 Decel Time 2)
Sets the ramp to decelerate from maximum speed to 0.
C1-09 Fast Stop Ramp Sets the ramp for the Fast Stop function.
C1-10
C1-11
Accel/Decel Setting
Resolution
Accel/Decel Switching
Speed
Inspection Deceleration
Ramp
0: 0.01 s unit
1: 0.1 s unit
Sets the speed to switch between accel/decel ramp settings.
C1-12 Motor 2 Acceleration Time
Sets the acceleration time for motor 2.
Note: Parameter C1-12 determines the acceleration time for motor 2 as long as d1-27 is not set to 0.00 Hz.
C1-13
C1-15
Motor 2 Acceleration Time Sets the deceleration time for motor 2.
Sets the deceleration ramp used for inspection run.
Default: 0
Min: 0
Max: 1
Default: 0.0%
Min: 0.0%
Max: 100.0%
Default: 1.0 s
Min: 0.0 s
Max: 600.0 s
Default: 1.0 s
Min: 0.0 s
Max: 600.0 s
Default: 0.00 s
Min: 0.00 s
Max: 2.00 s
<6> Setting ranges and defaults vary by the setting units determined by parameter o1-03.
Refer to
Defaults and Setting Ranges by Display Unit Selection (o1-03) on page 215
.
<8> Setting range value is dependent on parameter C1-10, Accel/Decel Setting Resolution. When C1-10 = 0 (units of 0.01 seconds), the setting range becomes 0.00 to 600.00 seconds.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 169
B
TOEP_C710616_38H_7_0.book 170 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
C2: Jerk Settings
No.
C2-01
C2-02
C2-03
C2-04
C2-05
Name
Jerk at Accel Start
Jerk at Accel End
Jerk at Decel Start
Jerk at Decel End
Five different jerk values can be set. They are automatically applied as shown in the figure below.
Up/Down command
Output speed
Description
C2-01
ON
C2-02
OFF
C2-03
C2-04
C2-05
C2-05
Time
Jerk below Leveling Speed Sets the jerk used when the speed reference is lower than the leveling speed setting.
Setting
Min: 0.00 s
Min: 0.00 s
Min: 0.00 s
Min: 0.00 s
Min: 0.00 s
<6> Setting ranges and defaults vary by the setting units determined by parameter o1-03.
Refer to
Defaults and Setting Ranges by Display Unit Selection (o1-03) on page 215 .
■
C3: Slip Compensation
No.
C3-01
C3-02
C3-03
C3-04
C3-05
Name
Slip Compensation Gain
Slip Compensation
Primary Delay Time
Slip Compensation Limit
Slip Compensation
Selection during
Regeneration
Output Voltage Limit
Operation Selection
Description
Sets the gain for the motor slip compensation function.
Adjusts the slip compensation function delay time.
Sets an upper limit for the slip compensation function as a percentage of motor rated slip for motor 1 (E2-02).
0: Disabled.
1: Enabled above 6 Hz.
2: Enabled whenever slip compensation is possible.
0: Disabled.
1: Enabled. Automatically decreases motor flux when output voltage saturation is reached.
Note: Available control modes for parameter C3-05 vary by drive model: Models
CIMR-LU2 0008 to 2 0415, 4 0005 to 4 0605, and 5 0003 to 5 0200:
Available when A1-02 = 2, 3
Setting
Default: 1.0
Min: 0.0
Max: 2.5
Default: 2000 ms
Min: 0 ms
Max: 10000 ms
Default: 200%
Min: 0%
Max: 250%
Default: 0
Min: 0
Max: 2
Default:
Min: 0
Max: 1
<5> Default setting is determined by the control mode (A1-02).
170 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 171 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
C4: Torque Compensation
No.
C4-01
C4-02
C4-03
C4-04
C4-05
Name
Torque Compensation
Gain
Torque Compensation
Primary Delay Time
Torque Compensation at
Forward Start
Torque Compensation at
Reverse Start
Torque Compensation
Time Constant
Description
Sets the gain for the automatic torque (voltage) boost function and helps to produce better starting torque.
Sets the torque compensation filter time.
Sets torque compensation at forward start as a percentage of motor torque.
Sets torque compensation at reverse start as a percentage of motor torque.
Sets the time constant for torque compensation at forward start and reverse start
(C4-03 and C4-04).
Setting
Default: 1.00
Min: 0.00
Max: 2.50
Min: 0 ms
Max: 60000 ms
Default: 0.0%
Min: 0.0%
Max: 200.0%
Default: 0.0%
Min: -200.0%
Max: 0.0%
Default: 10 ms
Min: 0 ms
Max: 200 ms
<5> Default setting is determined by the control mode (A1-02).
■
C5: Speed Control Loop Settings
No.
C5-01
C5-02
C5-03
C5-04
C5-06
C5-07
C5-08
C5-13
C5-14
C5-16
C5-17
Constant
Name
Speed Control Loop
Proportional Gain 1
Speed Control Loop
Integral Time 1
Speed Control Loop
Proportional Gain 2
Speed Control Loop
Integral Time 2
Speed Control Loop
Primary Delay Time
Speed Control Settings
Switching Speed
Speed Control Loop
Integral Limit
Speed Control Loop
Proportional Gain 3
Speed Control Loop
Integral Time 3
Speed Control Loop Delay
Time during Position Lock
Motor Inertia
Sets the filter time constant for the time from the speed loop to the torque command output.
Sets a delay to the torque command output from speed control loop during Position
Lock.
Sets the motor inertia.
Description
Sets the proportional gain 1 of the speed control loop.
Sets the integral time 1 of the speed control loop.
Sets the proportional gain 2 of the speed control loop.
Sets the integral time 2 of the speed control loop.
Sets the speed for switching between proportional gain 1, 2, 3 and integral time 1, 2,
3.
Sets the speed control loop integral upper limit as a percentage of rated torque.
Sets the proportional gain 3 of the speed control loop.
Sets the integral time 3 of the speed control loop.
Setting
Min: 0.00
Max: 300.00
Min: 0.000 s
Max: 10.000 s
Min: 0.00
Max: 300.00
Default: 0.500 s
Min: 0.000 s
Max: 10.000 s
Default: 0.004 s
Min: 0.000 s
Max: 0.500 s
Min: 0.0%
Max: 100.0%
Default: 400%
Min: 0%
Max: 400%
Min: 0.00
Max: 300.00
Min: 0.000 s
Max: 10.000 s
Default: 0.000 s
Min: 0.000 s
Max: 0.500 s
Min: 0.0001 kgm 2
Max: 600.00 kgm 2
B
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 171
TOEP_C710616_38H_7_0.book 172 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
No.
C5-18
C5-19
C5-20
C5-50
Name
Load Inertia Ratio
Speed Control Loop
Proportional Gain Time during Position Lock
Speed Control Loop
Integral Time during
Position Lock
Set Vibrational Frequency
Filter
Description
Sets the ratio between the motor and load inertia.
Sets the Speed Control Loop Proportional gain used during Position Lock.
Sets the Speed Control Loop Integral time used during Position Lock.
Setting
Default: 1.0
Min: 0.0
Max: 6000.0
Min: 0.00
Max: 300.00
Default:0.100 s
Min: 0.000 s
Max: 10.000 s
Sets the mechanical vibration filter frequency in units of 1 Hz.
Note: Set C5-50 to 0 (Hz) to disable the filter. The frequencies from 1 to 19 Hz cannot be set. Test equipment may be required to determine the mechanical resonance frequency. Setting C5-50 to an improper frequency will result in ineffective filtering of the effects of mechanical resonance.
Default: 0 Hz
Min: 20 Hz
Max: 1000 Hz
<4> Default setting value varies by the drive model (o2-04).
<5> Default setting is determined by the control mode (A1-02).
<45> Available in drive software versions PRG: 7200 or later.
■
C6: Carrier Frequency
No.
C6-03
Name
Carrier Frequency Sets the carrier frequency.
Description
C6-06
C6-09
PWM Method
Carrier Frequency during
Rotational Auto-Tuning
Selects PWM modulation method.
0: 2-phase/3-phase conversion
1: 2-phase modulation
2: 3-phase modulation
0: Carrier Frequency = 5 kHz
1: Setting value for C6-03
C6-21
C6-23
C6-31
Inspection Operation
Carrier Frequency
Carrier Frequency during
Initial Motor Pole Search
Carrier Frequency during
Rescue Operation
Sets the carrier frequency during Inspection Run.
0: Setting value for C6-03
1: Carrier Frequency = 2 kHz
Sets the carrier frequency when estimating the initial polarity.
0: Carrier Frequency = 2 kHz
1: Setting value for C6-03
Sets the carrier frequency during Rescue Operation.
0: C6-03 setting
1: 2 kHz
<4> Default setting value varies by the drive model (o2-04).
<39> Available in drive software versions PRG: 7016 or later.
Setting
Default:
Min: 1.0 kHz
Max: 15.0 kHz
Default: 0
Min: 0
Max: 2
Default: 0
Min: 0
Max: 1
Default: 1
Min: 0
Max: 1
Default: 0
Min: 0
Max: 1
Default: 0
Min: 0
Max: 1
172 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 173 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
◆
d: Speed References
Speed Reference parameters are used to set the various speed reference values during operation.
■
d1: Speed Reference
No.
d1-01
Name Description
Speed Reference 1 d1-02
Speed Reference 2 d1-03
Speed Reference 3 d1-04
Speed Reference 4 d1-05
Sets the Speed reference for the drive when d1-18 is set to 0 or 3. Setting units are determined by parameter o1-03.
Speed Reference 5 d1-06
Speed Reference 6 d1-07
Speed Reference 7 d1-08 d1-18 d1-19 d1-20 d1-21 d1-22 d1-23 d1-24
Setting
Min: 0.00%
Max: 100.00%
Speed Reference 8
Speed Reference Selection
Mode
Sets the mode of speed reference selection by digital inputs.
0: Use multi-speed references (d1-01 to d1-08)
1: High speed reference has priority (d1-19 to d1-23, d1-26)
2: Leveling speed reference has priority (d1-19 to d1-23, d1-26)
3: Use multi-speed references d1-02 to d1-08, no speed selection stops the drive.
Drive will stop when all input terminals programmed for speed references (H1 =
3, 4, 5) are open.
Default: 0
Min: 0
Max: 3
Nominal Speed
Intermediate Speed 1
Intermediate Speed 2
Intermediate Speed 3
Releveling Speed
Inspection Operation
Speed
Sets the nominal speed reference when d1-18 = 1 or 2.
Sets intermediate speed reference 1 when d1-18 = 1 or 2.
Sets intermediate speed reference 2 when d1-18 = 1 or 2.
Sets intermediate speed reference 3 when d1-18 = 1 or 3.
Sets speed reference for releveling when d1-18 = 1 or 2.
Sets speed reference when inspection operation is enabled.
Default:
Min: 0.00%
Max: 100.00%
Min: 0.00%
Max: 100.00%
Min: 0.00%
Max: 100.00%
Min: 0.00%
Max: 100.00%
Min: 0.00%
Max: 100.00%
Default:
Min: 0.00%
Max: 100.00%
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 173
B
TOEP_C710616_38H_7_0.book 174 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
No.
d1-25 d1-26 d1-27
Name
Rescue Operation Speed
Leveling Speed
Motor 2 Speed Reference
Description
Sets the speed reference during inspection operation.
Sets leveling speed reference when d1-18 = 1 or 2.
Setting
Default:
10.00%
Min: 0.00%
Default: 8.00%
Min: 0.00%
Sets the speed reference for motor 2.
Note:
1. If set to 0.00, the drive will control motor 1 instead.
2. When using motor 2, be sure that the accel/decel times are set in parameters C1-12 and C1-13.
Default: 0.00 Hz
Min: 0.00 Hz
Max: 200.00 Hz d1-28 d1-29
Leveling Speed Detection
Level
Inspection Speed Detection
Level
Used when d1-18 = 0 or 3. If the speed reference selected is lower than d1-28, then the drive uses the leveling speed as the speed reference.
Used when d1-18 = 0 or 3. If the speed reference selected is higher than d1-28 but lower or equal to d1-29, then the drive uses inspection speed as the speed reference.
Default: 0.0%
Min: 0.0%
Max: 100.0%
Default: 0.0%
Min: 0.0%
Max: 100.0%
<6> Setting ranges and defaults vary by the setting units determined by parameter o1-03.
Refer to
Defaults and Setting Ranges by Display Unit Selection (o1-03) on page 215 .
■
d6: Field Forcing
No.
Name d6-03 Field Forcing Selection d6-06 Field Forcing Limit
0: Disabled
1: Enabled
Description
Sets the upper limit of the excitation current command during magnetic field forcing.
A setting of 100% is equal to motor no-load current. Disabled only during DC
Injection Braking.
Setting
Default: 0
Min: 0
Max: 1
Default: 400%
Min: 100%
Max: 400%
174 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 175 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
◆
E: Motor Parameters
■
E1: V/f Pattern
No.
E1-01
E1-03
E1-04
E1-05
E1-06
E1-07
E1-08
E1-09
E1-10
E1-11
E1-12
E1-13
Maximum Output
Frequency
Minimum Output
Frequency
Name
Input Voltage Setting
V/f Pattern Selection
Maximum Voltage
Base Frequency
Middle Output Frequency
Middle Output Frequency
Voltage
Minimum Output
Frequency Voltage
Middle Output Frequency
2
Middle Output Frequency
Voltage 2
Base Voltage
Description
This parameter must be set to the power supply voltage.
WARNING!
Electrical Shock Hazard. Drive input voltage (not motor voltage) must be set in E1-01 for the protective features of the drive to function properly. Failure to do so may result in equipment damage and/or death or personal injury.
Setting
Default: 230 V
Min: 155 V
Max: 255 V
F: Custom V/f, E1-04 through E1-13 settings define the V/f pattern
To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. Ensure that the five frequencies are set according to these rules:
E1-09 ≤ E1-07 < E1-06 ≤ Ε1−11 ≤ E1-04
Note that if E1-11 = 0, then both E1-11 and E1-12 are disabled, and the above conditions do not apply.
Output Voltage (V)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09 E1-07 E1-06 E1-11 E1-04
Frequency (Hz)
Note: Some parameters may not be available depending on the control mode.
• E1-07, E1-08 and E-10 are available only in the V/f control and Open Loop Vector control modes.
• E1-11, E1-12 and E-13 are available only in the V/f control and Closed Loop
Vector control modes.
Default: F
Min: –
Max: F
Max: 200.0 Hz
Default: 230.0
V
Min: 0.0 V
Min: 0.0 Hz
Max: 200.0 Hz
Default: 3.0 Hz
Min: 0.0 Hz
Max: 200.0 Hz
Min: 0.0 V
Min: 0.0 Hz
Max: 200.0 Hz
Min: 0.0 V
Default: 0.0 Hz
Min: 0.0 Hz
Max: 120.0 Hz
Min: 0.0 V
Min: 0.0 V
<2> Default setting is dependent on the control mode (A1-02) and the drive model (o2-04).
<5> Default setting is determined by the control mode (A1-02).
<9> Values shown here are for 200 V class drives. The default is 400 V when using a 400 V class drive. Multiply value by 2.875 for 600 V class drives.
<11> Parameter is ignored when E1-11 and E1-12 are set to 0.0.
<13> When E1-13 (Base Voltage) is set to 0.0, output voltage is controlled with E1-05 (Maximum Voltage) = E1-13. When Auto-Tuning is performed, E1-05 and E1-13 are automatically set to the same value.
<23> Setting range depends on the type of motor being used. CLV allows a setting range of 10.0 to 200.0 Hz, while CLV/PM allows a setting range of 4.0 to 200.0 Hz.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 175
B
TOEP_C710616_38H_7_0.book 176 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
E2: Motor Parameters
No.
E2-01
E2-02
E2-03
E2-04
E2-05
E2-06
E2-07
E2-08
E2-09
E2-10
E2-11
Name
Motor Rated Current
Motor Rated Slip
Motor No-Load Current
Number of Motor Poles
Motor Line-to-Line
Resistance
Motor Leakage Inductance
Motor Iron-Core
Saturation Coefficient 1
Motor Iron-Core
Saturation Coefficient 2
Motor Mechanical Loss
Motor Iron Loss for Torque
Compensation
Motor Rated Power
Sets the motor nameplate full load current in Amps. Automatically set during
Auto-Tuning.
Sets the motor iron saturation coefficient at 50% of magnetic flux. Automatically set during Auto-Tuning.
Sets the motor iron saturation coefficient at 75% of magnetic flux. Automatically set during Auto-Tuning.
Sets the motor iron loss.
Description
Sets the motor rated slip. Automatically set during Auto-Tuning.
Sets the no-load current for the motor. Automatically set during Auto-Tuning.
Sets the number of motor poles. Automatically set during Auto-Tuning.
Sets the phase-to-phase motor resistance. Automatically set during Auto-Tuning.
Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage. Automatically set during Auto-Tuning.
Sets the motor mechanical loss as a percentage of motor rated power (kW).
Sets the motor rated power in kilowatts (1 HP = 0.746 kW). Automatically set during
Auto-Tuning.
Setting
Default:
Min: 10% of drive rated current
Max: 200% of drive rated
Default:
Min: 0.00 Hz
Max: 20.00 Hz
Default:
Min: 0 A
Max: E2-01
Default: 4
Min: 2
Max: 48
Default:
Min: 0.000 Ω
Max: 65.000 Ω
Default:
Min: 0.0%
Max: 40.0%
Default: 0.50
Min: 0.00
Max: 0.50
Default: 0.75
Min: E2-07
Max: 0.75
Default: 0.0%
Min: 0.0%
Max: 10.0%
Default:
Min: 0 W
Max: 65535 W
Default:
Min: 0.00 kW
Max: 650.00 kW
<4> Default setting value varies by the drive model (o2-04).
<10> The display resolution depends on the rated output power of the drive. Models CIMR-LU2 0008 to 2 0033, 4 0005 to 4 0018, and
5 0003 to 5 0013 display values in 0.01 A units, while models CIMR-LU2 0047 to 2 0415, 4 0024 to 4 0605, and 5 0017 to 5 0200 display values in 0.1 A units.
176 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 177 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
E3: V/f Pattern for Motor 2
These parameters are hidden when a PM motor control mode has been selected for motor 1 (A1-02 = 7).
No.
E3-04
E3-05
E3-06
E3-07
E3-08
E3-09
E3-10
Frequency
Frequency
Name
Motor 2 Maximum Output
Frequency
Motor 2 Maximum Voltage
Motor 2 Base Frequency
These parameters are only applicable when E1-03 is set to F.
To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the four frequencies are set according to these rules or an oPE10 fault will occur:
E3-09 ≤ E3-07 < E3-06 ≤ E3-04
Motor 2 Mid Output
Motor 2 Mid Output
Frequency Voltage
Motor 2 Minimum Output
Motor 2 Minimum Output
Frequency Voltage
Description
Output Voltage (V)
E3-05
E3-08
E3-10
E3-09 E3-07
Frequency (Hz)
E3-04
Setting
Default: 60.0 Hz
Min: 10.0 Hz
Max: 200.0 Hz
Default: 230.0
V
Min: 0.0 V
Default: 60.0 Hz
Min: 0.0 Hz
Max: 200.0 Hz
Default: 3.0 Hz
Min: 0.0 Hz
Max: 200.0 Hz
Min: 0.0 V
Default: 1.5 Hz
Min: 0.0 Hz
Max: 200.0 Hz
Min: 0.0 V
<4> Default setting value is dependent on the drive model (o2-04).
<9> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. Multiply value by 2.875 for 600 V class drives.
<31> Available in drive software versions PRG: 7012 or later.
■
E4: Motor 2 Parameters
These parameters are hidden when a PM motor control mode has been selected for motor 1 (A1-02 = 7).
No.
E4-01
E4-02
E4-03
E4-04
E4-05
E4-06
Name
Motor 2 Rated Current
Motor 2 Rated Slip
Motor 2 Rated No-Load
Current
Motor 2 Motor Poles
Motor 2 Line-to-Line
Resistance
Motor 2 Leakage
Inductance
Description
Sets the full load current for motor 2. Automatically set during Auto-Tuning.
Sets the rated slip for motor 2. Automatically set during Auto-Tuning.
Sets the no-load current for motor 2. Automatically set during Auto-Tuning.
Sets the number of poles of motor 2. Automatically set during Auto-Tuning.
Sets the phase-to-phase resistance for motor 2. Automatically set during Auto-Tuning.
Sets the voltage drop for motor 2 due to motor leakage inductance as a percentage of rated voltage. Automatically set during Auto-Tuning.
Setting
Min: 10% of drive rated current
Max: 200% of drive rated current
Min: 0.00 Hz
Min: 20.00 Hz
Min: 0 A
Min: [E4-01]
Default: 4
Min: 2
Max: 48
Min: 0.000
Ω
Max: 65.000 Ω
Min: 0.0%
Max: 40.0%
B
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 177
TOEP_C710616_38H_7_0.book 178 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
<4> Default setting value is dependent on the drive model (o2-04).
<10> The display resolution depends on the rated output power of the drive. Models CIMR-LU2 0008 to 2 0033, 4 0005 to 4 0018, and
5 0003 to 5 0013 display values in 0.01 A units, while models CIMR-LU2 0047 to 2 0415, 4 0024 to 4 0605, and 5 0017 to 5 0200 display values in 0.1 A units.
■
E5: PM Motor Settings
No.
E5-02
E5-03
E5-04
E5-05
E5-06
E5-07
E5-09
E5-11
E5-24
Name
Motor Rated Power
Motor Rated Current
Number of Motor Poles
Motor Stator Resistance
(Single Phase)
Motor d-Axis Inductance
Motor q-Axis Inductance
Motor Induction Voltage
Constant 1
Encoder Offset
Motor Induction Voltage
Constant 2
Sets the rated capacity of the motor.
Sets the motor rated current.
Sets the number of motor poles.
Description
Sets the stator resistance (1 phase value).
Sets the d-axis inductance.
Sets the q-axis inductance.
Sets the induced phase peak voltage in units of 0.1 mV (rad/s) [electrical angle].
When setting this parameter, E5-24 should be set to 0.0.
Sets the offset between the rotor magnetic axis and the encoder zero position. Set during Encoder Offset Tuning.
Sets the induced phase-to-phase rms voltage in units of 0.1 mV/(r/min) [mechanical angle].
When setting this parameter, E5-09 should be set to 0.0.
Setting
Default:
Min: 0.10 kW
Max: 650.00 kW
Default:
Min: 10% of drive rated current
Max: 200% of drive rated
Default: 12
Min: 2
Default:
Min: 0.000 Ω
Max: 65.000 Ω
Default:
Min: 0.00 mH
Max: 600.00 mH
Default:
Min: 0.00 mH
Max: 600.00 mH
Default:
Min: 0.0 mV/(rad/ s)
Max:
6500.0 mV/(rad/s)
Default: 0.0 deg
Min: -180 deg
Max: 180 deg
Default:
0.0 mV/(r/min)
Min:
0.0 mV/(r/min)
Max:
6500.0 mV/(r/ min)
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<4> Default setting value is determined by the drive model (o2-04).
<10> The display resolution depends on the rated output power of the drive. Models CIMR-LU2 0008 to 2 0033, 4 0005 to 4 0018, and
5 0003 to 5 0013 display values in 0.01 A units, while models CIMR-LU2 0047 to 2 0415, 4 0024 to 4 0605, and 5 0017 to 5 0200 display values in 0.1 A units.
<43> When PG-E3 option connected: Max setting = 48
178 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 179 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
◆
F: Option Settings
F parameters are used to program the drive for Encoder and PG feedback from the motor and to function with option cards.
■
F1: PG Speed Control Card
No.
F1-01
Name
Encoder 1 Resolution
Description
Sets the encoder resolution (number of pulses per revolution)
Setting
Min: 1 ppr
Max: 60000 ppr
F1-02
F1-03
F1-04
Operation Selection at PG
Open Circuit (PGo)
Operation Selection at
Overspeed (oS)
Operation Selection at
Deviation
0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.
0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.
0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.
Default: 1
Min: 0
Max: 3
Default: 1
Min: 0
Max: 3
Default: 3
Min: 0
Max: 3
F1-05
F1-06
F1-08
F1-09
F1-10
F1-11
F1-14
F1-18
F1-19
F1-20
Encoder 1 Rotation
Direction Selection
Overspeed Detection Level Sets the overspeed detection level as a percentage of the maximum output frequency.
Overspeed Detection
Delay Time
Excessive Speed Deviation
Detection Level
Excessive Speed Deviation
Detection Delay Time
PG Open-Circuit Detection
Time dv3 Detection Selection dv4 Detection Selection
PG Option Card
Disconnect Detection 1
0: A phase leads B in the up direction
1: B phase leads A in the up direction
Sets the time in seconds for an overspeed situation to trigger a fault (oS).
Sets the speed deviation detection level as a percentage of the maximum output frequency.
Sets the time in seconds for a speed deviation situation to trigger a fault (dEv).
Sets the time required to trigger a PG Open fault (PGo).
0: Disabled n: Sets the number of dv3 situations that may be detected before triggering an actual dv3 fault.
0: Disabled n: Number of pulses that the A and B pulse are reversed that triggers dv4 detection.
0: Disabled
1: Enabled
Min: 0
Max: 1
PG 1 Pulse Monitor Output
Division Ratio
Sets the division ratio for the pulse monitor used of the PG option card installed to connector CN5-C. By setting “xyz”, the division ratio becomes = [(1 + x) / yz]. If only using the A pulse for one track input, then the input ratio will be 1:1, regardless of what F1-06 is set to.
Default: 1
Min: 1
Max: 132
Default: 115%
Min: 0%
Max: 120%
Default: 0.0 s
Min: 0.0 s
Max: 2.0 s
Default: 10%
Min: 0%
Max: 50%
Default: 0.5 s
Min: 0.0 s
Max: 10.0 s
Default: 2.0 s
Min: 0.0 s
Max: 10.0 s
Default: 10
Min: 0
Max: 10
Default: 128
Min: 0
Max: 5000
Default: 1
Min: 0
Max: 1
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 179
B
TOEP_C710616_38H_7_0.book 180 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
No.
F1-29
F1-50
F1-51
Name dEv Detection Condition
Selection
Encoder Selection
PGoH Detection Level
Description
Selects when DEV is active.
0: After speed reference, soft starter output and motor speed have matched once.
1: After speed reference and soft starter output have matched once.
2: Always during Run
Selects the encoder connected the PG-F3 option.
0: EnDat 2.1/01, 2.2/01 Serial Communication + Sin/Cos
1: EnDat 2.2/22 Serial Communication
2: HIPERFACE
Sets the level for detecting PG Hardware Fault (PGoH). Available when F1-20 = 1
Setting
Default: 2
Min: 0
Max: 2
Default: 0
Min: 0
Max: 2
Default: 80%
Min: 1%
Max: 100%
F1-52
F1-63
Communication Speed of
Serial Encoder Selection
PG-E3 R Track Selection
Selects the communication speed between the PG-F3 option and serial encoder.
0: 1M bps/9600 bps
1: 500k bps/19200 bps
2: 1M bps/38400 bps
3: 1M bps/38400 bps
0: Disabled
1: Enabled
F1-66 to
F1-81
(B9AH to
BA9H)
Encoder Adjust 1 to 16
Sets encoder offsets 1 to 16 for the PG-E3 option card. These parameters are automatically set by the execution of Auto-Tuning of PG-E3 encoder characteristics.
Default: 0
Min: 0
Max: 3
Default: 0
Min: 0
Max: 1
Default: 0
Min: 0
Max: FFFF
<5> Default setting is determined by the control mode (A1-02).
<34> Setting range is 1 to 15000 ppr when the drive is set for CLV/PM.
<39> Available in drive software versions PRG: 7016 or later.
<44> Available in drive software versions PRG: 7017 or later.
■
F3: Digital Input Card (DI-A3)
No.
F3-01
F3-03
Name
DI-A3 Option Card Input
Selection
DI-A3 Option Card Data
Length Selection
Description
0: BCD, 1% units
1: BCD, 0.1% units
2: BCD, 0.01% units
3: BCD, 1 Hz units
4: BCD, 0.1 Hz units
5: BCD, 0.01 Hz units
6: BCD customized setting (5 digit), 0.02 Hz units
7: Binary input
The unit and the setting range are determined by F3-03.
F3-03 = 0: 255/100% (-255 to +255)
F3-03 = 1: 40961/100% (-4095 to +4095)
F3-03 = 2: 30000/100% (-33000 to +33000)
When the digital operator units are set to be displayed in Hertz or user-set units (o1-03
= 2 or 3), the units for F3-01 are determined by parameter o1-03.
0: 8 bit
1: 12 bit
2: 16 bit
Setting
Default: 0
Min: 0
Max: 7
Default: 2
Min: 0
Max: 2
180 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 181 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
F4: Analog Monitor Card (AO-A3)
No.
F4-01
F4-02
F4-03
F4-04
F4-05
F4-06
F4-07
F4-08
Terminal V1 Function
Selection
Terminal V2 Function
Selection
Name
Terminal V1 Gain
Terminal V2 Gain
Terminal V1 Bias
Terminal V2 Bias
Terminal V1 Signal Level
Selection
Terminal V2 Signal Level
Selection
Description
Sets the monitor signal for output from terminal V1. Set this parameter to the last three digits of the desired U monitor. Some U parameters are available only in certain control modes.
Sets the gain for voltage output via terminal V1.
Sets the monitor signal for output from terminal V2. Set this parameter to the last three digits of the desired U monitor. Some U parameters are available only in certain control modes.
Sets the gain for voltage output via terminal V2.
Sets the amount of bias added to the voltage output via terminal V1.
Sets the amount of bias added to the voltage output via terminal V2.
0: 0 to 10 V
1: -10 to 10 V
Setting
Default: 102
Min: 000
Max: 999
Default: 100.0%
Min: -999.9%
Max: 999.9%
Default: 103
Min: 000
Max: 999
Default: 50.0%
Min: -999.9%
Max: 999.9%
Default: 0.0%
Min: -999.9%
Max: 999.9%
Default: 0.0%
Min: -999.9%
Max: 999.9%
Default: 1
Min: 0
Max: 1
Default: 1
Min: 0
Max: 1
■
F5: Digital Output Card (DO-A3)
No.
F5-01
F5-02
F5-03
F5-04
F5-05
F5-06
F5-07
F5-08
F5-09
Name
Terminal P1-C1 Output
Selection
Terminal P2-C2 Output
Selection
Terminal P3-C3 Output
Selection
Terminal P4-C4 Output
Selection
Terminal P5-C5 Output
Selection
Terminal P6-C6 Output
Selection
Terminal M1-M2 Output
Selection
Terminal M3-M4 Output
Selection
DO-A3 Output Mode
Selection
Description
Sets the function for contact output terminals M1-M2, M3-M4, and photocoupler output terminals P1 through P6.
0: Output terminals are each assigned separate output functions.
1: Binary code output
2: Use output terminal functions selected by parameters F5-01 through F5-08.
Default: 37
Min: 0
Max: 161
Default: F
Min: 0
Max: 161
Default: F
Min: 0
Max: 161
Default: 0
Min: 0
Max: 2
Setting
Default: 0
Min: 0
Max: 161
Default: 1
Min: 0
Max: 161
Default: 2
Min: 0
Max: 161
Default: 4
Min: 0
Max: 161
Default: 6
Min: 0
Max: 161
B
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 181
TOEP_C710616_38H_7_0.book 182 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
F6: Communication Option Card
For more details on a specific option card, refer to the instruction manual for the option card.
No.
F6-01
Name
Operation Selection after
Communications Error
Description
0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.
Setting
Default: 1
Min: 0
Max: 3
F6-02
External Fault from
Communication Option
Detection Selection
0: Always detected
1: Detection during run only
Default: 0
Min: 0
Max: 1
F6-03
F6-04
F6-06
F6-08
F6-35 bUS Error Detection Time Sets the delay time for error detection if a bus error occurs.
Torque Limit Selection from Communications
Option
Reset Communication
Parameter
CANopen Node ID
0: Disabled. Torque limit from option card disabled.
1: Enabled. Torque limit from option card enabled.
Sets the node address.
Default: 2.0 s
Min: 0.0 s
Max: 5.0 s
Default: 0
Min: 0
Max: 1
0: Communication-related parameters (F6 ) are not reset when the drive is initialized using A1-03.
1: Reset all communication-related parameters (F6 ) when the drive is initialized using
A1-03.
Default: 0
Min: 0
Max: 1
Default: 0
Min: 0
Max: 126
F6-36
External Fault from
Communication Option
Operation Selection
CANopen Communication
Speed
0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.
0: Auto-detection
1: 10 kbps
2: 20 kbps
3: 50 kbps
4: 125 kbps
5: 250 kbps
6: 500 kbps
7: 800 kbps
8: 1 Mbps
Default: 1
Min: 0
Max: 3
Default: 6
Min: 0
Max: 8
<1> Parameter setting value is not reset to the default value when the drive is initialized.
182 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 183 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
◆
H: Multi-Function Terminals
H parameters assign functions to the multi-function input and output terminals.
■
H1: Multi-Function Digital Inputs
No.
H1-03
H1-04
H1-05
H1-06
H1-07
H1-08
Terminal S3 Function
Selection
Name
Terminal S4 Function
Selection
Terminal S5 Function
Selection
Terminal S6 Function
Selection
Terminal S7 Function
Selection
Terminal S8 Function
Selection
Description
Assigns a function to the multi-function digital inputs.
Refer to page
for a description of setting values.
Note: Unused terminals should be set to F.
Setting
Min: 3
Max: 79
Min: 3
Max: 79
Min: 3
Max: 79
Min: 3
Max: 79
Min: 3
Max: 79
Default: F
Min: 3
Max: 79
<19> With the speed reference priority d1-18 is set to 0 or 3, the default settings for parameters H1-03 to H1-07 governing input terminals S3 to S7 are: 24, 14, 3, 4, and 5 respectively. When d1-18 is set to 1 or 2, the default settings for H1-03 to H1-07 become 50, 54, 51, 53, and F respectively.
H1
Setting
3
4
5
Function
Multi-Step Speed Reference 1
Multi-Step Speed Reference 2
Multi-Step Speed Reference 3
6
7
8
9
F
14
15
16
17
18
Jog reference selection
Accel/decel Ramp Selection 1
Baseblock Command (N.O.)
Baseblock Command (N.C.)
Not Used (Through Mode)
Fault Reset
Fast Stop (N.O.)
Motor 2 Selection
Fast Stop (N.C.)
Timer Function Input
H1 Multi-Function Digital Input Settings
Description
When input terminals are set to Multi-Step Speed References 1 through 3, switching combinations of those terminals will create a multi-step speed sequence using the speed references set in d1-01 through d1-08.
Closed: Jog frequency reference (d1-17) selected.
The Jog frequency can be used when the speed reference selection is not assigned to input terminals
(b1-01 ≠ 1) and the speed reference priority is set to use the multi-step speed reference (d1-18 = 0 or
3).
Used to switch between accel/decel ramp 1 (set in C1-01, C1-02) and accel/decel ramp 2 (set in
C1-03, C1-04).
When combined with another input terminal set for “Accel/Decel ramp 2” (H1 = 1A), the drive can also switch between accel/decel ramp 3 (set in C1-05, C1-06) and accel/decel ramp 4 (set in
C1-07, C1-08).
Closed: No drive output
Open: No drive output
Select this setting when the terminal is not used or when using the terminal in the pass-through mode. The terminal does not trigger a drive function but can be used as digital input for the controller the drive is connected to.
Closed: Resets faults if the cause is cleared and the Up/Down command is removed.
Closed: Decelerates to stop at the Fast Stop ramp set to C1-09.
Open: Motor 1(E1 , E3 )
Closed: Motor 2 (E2 , E4 )
Open: Decelerates to stop at the Fast Stop ramp set to C1-09.
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction with the timer function output (H2 = 12).
B
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 183
TOEP_C710616_38H_7_0.book 184 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
H1 Multi-Function Digital Input Settings
H1
Setting
Function Description
1A
20 to 2F
50
51
52
53
54
55
Accel/decel Ramp Selection 2
External Fault
Nominal Speed
Intermediate Speed
Releveling Speed
Leveling Speed
Inspection Operation
Rescue Operation
Used in conjunction with an input terminal set for “Accel/decel ramp selection 1” (H1 = 7), and allows the drive to switch between accel/decel ramp 3 and 4.
20: N.O., Always detected, ramp to stop
21: N.C., Always detected, ramp to stop
22: N.O., During run, ramp to stop
23: N.C., During run, ramp to stop
24: N.O., Always detected, coast to stop
25: N.C., Always detected, coast to stop
26: N.O., During run, coast to stop
27: N.C., During run, coast to stop
28: N.O., Always detected, Fast Stop
29: N.C., Always detected, Fast Stop
2A: N.O., During run, Fast Stop
2B: N.C., During run, Fast Stop
2C: N.O., Always detected, alarm only (continue running)
2D: N.C., Always detected, alarm only (continue running)
2E: N.O., During run, alarm only (continue running)
2F: N.C., During run, alarm only (continue running)
Closed: Activates the nominal speed (d1-19).
Closed: Activates the Intermediate Speed (d1-20).
Closed: Activates the Releveling Speed (d1-23).
Closed: Activates the Leveling Speed (d1-26).
Closed: Activates Inspection operation using the speed set in d1-24.
Closed: Activates rescue operation.
56 Motor Contactor Feedback
Open: Motor contactor open
Closed: Motor contactor closed (N.O.)
Closed: Uses the leveling speed as the maximum speed when going up.
57 High Speed Limit (Up)
58
5A
5B
High Speed Limit (Down)
Motor Contactor Feedback 2
Brake Feedback 2
Closed: Uses the leveling speed as the maximum speed when going down.
Open: Motor contactor closed (N.C.)
Closed: Motor contactor open
Open: Brake open (N.C.)
Closed: Brake closed
Closed: Initiate Direct Landing (S5-10 = 1) 5C Floor Sensor
67
79
Communications Test Mode
Brake Feedback
Tests the MEMOBUS/Modbus RS-485/422 interface. Displays “PASS” if the test completes successfully.
Open: Brake closed
Closed: Brake open (N.O.)
<44> Available in drive software versions PRG: 7017 or later.
184 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 185 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
H2: Multi-Function Digital Outputs
No.
H2-01
H2-02
H2-03
H2-04
H2-05
Name
Terminals M1-M2
Function Selection (relay)
Terminals M3-M4
Function Selection (relay)
Terminals M5-M6
Function Selection (relay)
Terminal P1-C1 Function
Selection (photocoupler)
Terminal P2-C2 Function
Selection (photocoupler)
Description
Refer to H2 Multi-Function Digital Output Settings on page 185
for a description of setting values.
Setting
Default: 50
Min: 0
Max: 161
Default: 51
Min: 0
Max: 161
Default: 6
Min: 0
Max: 161
Default: 37
Min: 0
Max: 161
Default: F
Min: 0
Max: 161
4
5
6
7
8
2
3
9
11
12
13
14
15
16
18
1A
1B
A
B
E
F
10
H2
Setting
0
1
Function
H2 Multi-Function Digital Output Settings
Description
During Run
Zero Speed
Speed Agree 1
User-set Speed Agree 1
Speed Detection 1
Speed Detection 2
Drive Ready (READY)
DC Bus Undervoltage
During Baseblock (N.O.)
Speed Reference Source
Up/Down Command Source
Closed: An Up/Down command is active or voltage is output.
Open: Output speed is greater than the value of E1-09 (Minimum Output Frequency) or S1-01 (Zero
Speed Level at Stop).
Closed: Output frequency is less than or equal to the value of E1-09 (Minimum Output Frequency) or
S1-01 (Zero Speed Level at Stop).
Closed: Output speed equals the speed reference (plus or minus the hysteresis set to L4-02).
Closed: Output speed and speed reference equal L4-01 (plus or minus the hysteresis set to L4-02).
Closed: Output speed is less than or equal to the value in L4-01 with hysteresis determined by L4-02.
Closed: Output speed is greater than or equal to the value in L4-01 with hysteresis determined by L4-02.
Closed: Power up is complete and the drive is ready to accept an Up/Down command.
Closed: DC bus voltage is below the Uv trip level set in L2-05.
Closed: Drive has entered the baseblock state (no output voltage).
Open: The speed reference is supplied by an external reference (set in b1-01).
Closed: Digital operator supplies the speed reference.
Open: The Up/Down command is supplied by an external reference (set in b1-02).
Closed: Digital operator supplies the Up/Down command.
Closed: An overtorque or undertorque situation has been detected.
Torque Detection 1
Fault Closed: Fault occurred. (excluding CPF00 and CPF01)
Not used (Through Mode) Set this value when the terminal is not used or when using the terminal in the pass-through mode.
Minor Fault
Fault Reset Command
Active
Timer Output
Closed: An alarm has been triggered, or the IGBTs have reached 90% of their expected life span.
Closed: The drive has received a reset command from the multi-function input terminals or from serial network, or the digital operator’s RESET key has been pressed.
Closed: Timer output.
Speed Agree 2
User-set Speed Agree 2
Speed Detection 3
Speed Detection 4
Closed: When drive output frequency equals the speed reference ±L4-04.
Closed: When the drive output speed is equal to the value in L4-03 ±L4-04.
Closed: When the drive output speed is less than or equal to the value in L4-03 ±L4-04.
Closed: When the output speed is greater than or equal to the value in L4-03 ±L4-04.
Torque Detection 2
During Down Direction
Closed: Overtorque or undertorque has been detected.
Closed: Drive is running in the down direction.
During Baseblock 2 (N.C.) Open: Drive has entered the baseblock state (no output voltage).
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 185
B
TOEP_C710616_38H_7_0.book 186 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
H2 Multi-Function Digital Output Settings
H2
Setting
Function Description
1C
1D
1E
1F
20
Motor 2 Selection
During Regeneration
Reset Enabled
Motor Overload Alarm
(oL1)
Drive Overheat Pre-alarm
(oH)
Open: Motor 1 is selected
Closed: Motor 2 is selected
Closed: Motor is operated in regenerative mode.
Closed: An automatic reset is performed
Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers this alarm.
Closed: Heatsink temperature exceeds the parameter L8-02 value.
2F Maintenance Period
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay may require maintenance.
Closed: When the torque limit has been reached.
30
33
During Torque Limit
Within Position Lock
Bandwidth
Closed: Position deviation is within the Position Lock Bandwidth.
37
47
During Frequency Output
Input Phase Loss
Open: No frequency output from drive when stopped with baseblock, stopped with DC injection braking during initial excitation, or stopped with short circuit braking.
Closed: Drive is outputting a frequency.
Closed: Input phase loss has occurred
Open: Normal operation (no phase loss detected)
4E
50
51
52
53
54
55
58
5C
Braking Transistor Fault (rr)
Brake Control
Output Contactor Control
Closed: The built-in dynamic braking transistor failed.
Note: This function is not available in models CIMR-LU2 0145 to 2 0415, 4 0075 to 4 0216, or
5 0052 to 5 0200.
Close: Release brake
Open: Apply brake
Closed: Close output contactor
Door Zone Reached
Not Zero Speed
Light Load Direction
Closed: Indicates that the door zone has been reached.
Closed: Speed is greater than the zero speed level set to S1-01
Open: Operating at zero speed level
Closed: Light load direction is up
Open: Light load direction is down
Closed: Ready for Light Load Direction Search
Open: Light Load Detection in progress
Light Load Direction
Detection Status
Safe Disable Status
Motor Current Monitor
Closed: Safe Disable terminals H1-HC and H2-HC are open, drive is in a baseblock state
Open: Safe Disable terminals H1-HC and H2-HC are closed (normal operation)
Open: Output current is greater than the value of L8-99.
Closed: Output current is less than or equal to the value of L8-99.
Internal Cooling Fan Alarm Closed: Internal cooling fan alarm
60
61
100 to 161
Motor Pole Search Status
Function 0 to 61 with Inverse
Output
Closed: Motor pole search successful
Inverts the output switching of the multi-function output functions.
Sets the last two digits of 1 to reverse the output signal of that specific function.
<44> Available in drive software versions PRG: 7017 or later.
186 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 187 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
H3: Multi-Function Analog Inputs
No.
H3-01
H3-02
H3-03
H3-04
H3-09
H3-10
H3-11
H3-12
H3-13
H3-16
H3-17
Name
Terminal A1 Signal Level
Selection
Terminal A1 Function
Selection
0: 0 to 10 V
1: -10 to 10 V
Terminal A1 Gain Setting Sets the level of the input value selected in H3-02 when 10 V is input at terminal A1.
Terminal A1 Bias Setting
Sets the function of terminal A1.
Description
Sets the level of the input value selected in H3-02 when 0 V is input at terminal A1.
Setting
Default: 0
Min: 0
Max: 1
Default: 0
Min: 0
Max: 1F
Default: 100.0%
Min: -999.9%
Max: 999.9%
Default: 0.0%
Min: -999.9%
Max: 999.9%
Terminal A2 Signal Level
Selection
0: 0 to 10 V
1: -10 to 10 V
Note: Use DIP switch S1 to set input terminal A2 for a current or a voltage input signal.
Default: 0
Min: 0
Max: 0
Terminal A2 Function
Selection
Terminal A2 Gain Setting
Terminal A2 Bias Setting
Analog Input Filter Time
Constant
Offset for Terminal A1
Offset for Terminal A2
Sets the function of terminal A2.
Sets the level of the input value selected in H3-10 when 10 V is input at terminal A2.
Sets the level of the input value selected in H3-10 when 0 V is input at terminal A2.
Sets a primary delay filter time constant for terminals A1 and A2. Used for noise filtering.
Applies an offset to analog input A1. Can be used for zero adjustment of the analog input.
Applies an offset to analog input A2. Can be used for zero adjustment of the analog input.
Default: 0
Min: 0
Max: 1F
Default: 100.0%
Min: -999.9%
Max: 999.9%
Default: 0.0%
Min: -999.9%
Max: 999.9%
Default: 0.03 s
Min: 0.00 s
Max: 2.00 s
Default: 0
Min: -500
Max: 500
Default: 0
Min: -500
Max: 500
Setting
0
H3 Multi-Function Analog Input Settings (H3-02 and H3-10)
Function
Speed Reference Bias
(value added to input signal when multiple analog terminals supply the speed reference)
Description (For when output is 100%)
E1-04 (maximum output frequency)
2
3
Auxiliary Speed Reference 1
(used as a second speed reference)
Auxiliary Speed Reference 2
(used as third speed reference)
E1-04 (maximum output frequency)
E1-04 (maximum output frequency)
E
14
Motor Temperature (PTC thermistor input)
Torque Compensation (load cell input) oH3 Alarm detection level: 1.18 V oH4 Fault detection level: 2.293 V
10 V = Motor rated torque
1F Not used (Through Mode)
Sets this value when the terminal is not used or when using the terminal in the pass-through mode .
<44> Available in drive software versions PRG: 7017 or later.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 187
B
TOEP_C710616_38H_7_0.book 188 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
H4: Analog Outputs
No.
H4-01
H4-02
H4-03
H4-04
H4-05
H4-06
H4-07
H4-08
Selection
Selection
Name
Terminal FM Monitor
Selection
Terminal FM Gain
Terminal FM Bias
Terminal AM Monitor
Terminal AM Gain
Terminal AM Bias
Terminal FM Signal Level
Terminal AM Signal Level
Selection
Selects the data to be output through multi-function analog output terminal FM.
Set the desired monitor parameter to the digits available in U . For example, enter “103” for U1-03.
Sets the signal level at terminal FM that is equal to 100% of the selected monitor value.
Description
Sets the bias value added to the terminal FM output signal.
Selects the data to be output through multi-function analog output terminal AM.
Set the desired monitor parameter to the digits available in U . For example, enter “103” for U1-03.
Sets the signal level at terminal AM that is equal to 100% of the selected monitor value.
Sets the bias value added to the terminal AM output signal.
0: 0 to 10 V
1: -10 to 10 V
0: 0 to 10 V
1: -10 to 10 V
Setting
Default: 102
Min: 000
Max: 999
Default: 100.0%
Min: -999.9%
Max: 999.9%
Default: 0.0%
Min: -999.9%
Max: 999.9%
Default: 103
Min: 000
Max: 999
Default: 50.0%
Min: -999.9%
Max: 999.9%
Default: 0.0%
Min: -999.9%
Max: 999.9%
Default: 0
Min: 0
Max: 1
Default: 0
Min: 0
Max: 1
188 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 189 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
H5: MEMOBUS/Modbus Serial Communication
Note: The settings for MEMOBUS/Modbus communications become effective when the drive is restarted.
No.
H5-01
Name
Drive Node Address
Description
Selects drive station node number (address) for MEMOBUS/Modbus terminals R+,
R-, S+, S-. Cycle power for the setting to take effect.
Setting
Default: 1
Min: 0
Max: FF
H5-02
H5-03
H5-04
Communication Speed
Selection
Communication Parity
Selection
Stopping Method After
Communication Error (CE)
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Cycle power for the setting to take effect.
0: No parity
1: Even parity
2: Odd parity
Cycle power for the setting to take effect.
0: Ramp to stop
1: Coast to stop
2: Fast Stop
3: Alarm only
Default: 3
Min: 0
Max: 8
Default: 0
Min: 0
Max: 2
Default: 3
Min: 0
Max: 3
H5-05
H5-06
H5-07
H5-09
H5-10
H5-11
Communication Fault
Detection Selection
0: Disabled
1: Enabled. If communication is lost for more than two seconds, a CE fault will occur.
Drive Transmit Wait Time Sets the wait time between receiving and sending data.
RTS Control Selection
Communication Fault
Detection Time
Unit Selection for
MEMOBUS/Modbus
Register 0025H
Communications ENTER
Function Selection
0: Disabled. RTS is always on.
1: Enabled. RTS turns on only when sending.
Sets the time required to detect a communications error. Adjustment may be needed when networking several drives.
0: 0.1 V units
1: 1 V units
0: Drive requires an Enter command before accepting any changes to parameter settings.
1: Parameter changes are activated immediately without the Enter command.
Default: 1
Min: 0
Max: 1
Default: 5 ms
Min: 5 ms
Max: 65 ms
Default: 1
Min: 0
Max: 1
Default: 2.0 s
Min: 0.0 s
Max: 10.0 s
Default: 0
Min: 0
Max: 1
Default: 0
Min: 0
Max: 1
<14> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 189
B
TOEP_C710616_38H_7_0.book 190 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
◆
L: Protection Functions
L parameters provide protection to the drive and motor, including control during momentary power loss, Stall Prevention, frequency detection, fault reset, overtorque detection, torque limits, and other types of hardware protection.
■
L1: Motor Protection
No.
L1-01
L1-02
L1-03
L1-04
L1-05
L1-13
Name
Motor Overload Protection
Selection
Description
0: Disabled
1: General purpose motor (standard fan cooled)
2: Drive dedicated motor with a speed range of 1:10
3: Vector motor with a speed range of 1:100
5: PM motor with constant torque characteristics
The drive may not be able to provide protection when multiple motors are used, even if overload is enabled in L1-01. Set L1-01 to 0 and install separate thermal relay to each motor.
Setting
Default:
Min: 0
Max: 5
Motor Overload Protection
Time
Sets the motor thermal overload protection (oL1) time.
Default: 1.0 min
Min: 0.1 min
Max: 5.0 min
Motor Overheat Alarm
Operation Selection (PTC thermistor input)
Motor Overheat Fault
Operation Selection (PTC thermistor input)
Motor Temperature Input
Filter Time (PTC thermistor input)
Continuous Electrothermal
Operation Selection
Sets operation when the motor temperature analog input (H3-02 or H3-10 = E) exceeds the oH3 alarm level.
0: Ramp to stop
1: Coast to stop
2: Emergency Stop (Fast Stop) (decelerate to stop using the deceleration time in
C1-09)
3: Alarm only (“oH3” will flash)
Sets stopping method when the motor temperature analog input (H3-02 or H3-10 = E) exceeds the oH4 fault level.
0: Ramp to stop
1: Coast to stop
2: Emergency Stop (Fast Stop) (decelerate to stop using the deceleration time in
C1-09)
Default: 3
Min: 0
Max: 3
Default: 1
Min: 0
Max: 2
Adjusts the filter for the motor temperature analog input (H3-02 or H3-10 = E).
0: Disabled
1: Enabled
Default: 0.20 s
Min: 0.00 s
Max: 10.00 s
Default: 1
Min: 0
Max: 1
<5> Default setting is determined by the control mode (A1-02).
<44> Available in drive software versions PRG: 7017 or later.
■
L2: Undervoltage Detection
No.
L2-05
Name
Undervoltage Detection
Level (Uv)
Description
Sets the DC bus undervoltage trip level.
Setting
Min: 150 Vdc
<9> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. Multiply value by 2.875 for 600 V class drives.
<15> Default setting value is dependent on the setting for the input voltage (E1-01).
190 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 191 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
L3: Stall Prevention
No.
L3-01
L3-02
L3-05
L3-06
Name
Stall Prevention Selection during Acceleration
Description
0: Disabled.
1: General purpose. Acceleration is paused as long as the current is above the L3-02 setting.
2: Intelligent. Accelerate in the shortest possible time without exceeding the L3-02 level.
Setting
Default: 1
Min: 0
Max: 2
Stall Prevention Level during Acceleration
Used when L3-01 = 1 or 2. 100% is equal to the drive rated current.
Stall Prevention Selection during Run
0: Disabled. Drive runs at a set frequency. A heavy load may cause speed loss.
1: Decel time 1. Uses the deceleration ramp set to C1-02 while Stall Prevention is performed.
2: Decel time 2. Uses the deceleration ramp set to C1-04 while Stall Prevention is performed.
Min: 0%
Default: 1
Min: 0
Max: 2
Stall Prevention Level during Run
Enabled when L3-05 is set to 1 or 2. 100% is equal to the drive rated current.
Min: 30%
<16> The setting value is dependent on the setting for the carrier frequency reduction (L8-38).
■
L4: Speed Detection
No.
L4-01
L4-02
L4-03
L4-04
L4-05
L4-06
L4-07
L4-13
Name
Speed Agreement
Detection Level
Speed Agreement
Detection Width
Speed Agreement
Detection Level (+/-)
Speed Agreement
Detection Width (+/-)
Speed Reference Loss
Detection Selection
Speed Reference at
Reference Loss
Speed Agree Detection
Selection
Door Zone Level
0: Stop. Drive stops when the speed reference is lost.
1: Run. Drive runs at a reduced speed when the speed reference is lost.
Sets the percentage of the speed reference that the drive should run with when the speed reference is lost.
0: No detection during baseblock.
1: Detection always enabled.
Description
L4-01 sets the speed detection level for digital output functions H2-
L4-02 sets the hysteresis or allowable margin for speed detection.
= 3, 4, 5.
L4-03 sets the speed detection level for digital output functions H2 = 13, 14, 15,
16.
L4-04 sets the hysteresis or allowable margin for speed detection.
Sets the door zone speed level. The “door zone” multi-function digital output is closed when the speed falls below this level.
Setting
Default: 0.0%
Min: 0.0%
Max: 100.0%
Default: 4.0%
Min: 0.0%
Max: 40.0%
Default: 0.0%
Min: -100.0%
Max: 100.0%
Default: 4.0%
Min: 0.0%
Max: 40.0%
Default: 0
Min: 0
Max: 1
Default: 80%
Min: 0.0%
Max: 100.0%
Default: 0
Min: 0
Max: 1
Default: 0.0%
Min: 0.0%
Max: 100.0%
<44> Available in drive software versions PRG: 7017 or later.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 191
B
TOEP_C710616_38H_7_0.book 192 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
L5: Automatic Fault Reset
No.
L5-01
L5-02
L5-06
Name
Number of Auto Reset
Attempts
Fault Output Operation during Auto Reset
Description
Sets the number of times the drive may attempt to reset after the following faults occur: GF, LF, oC, ov, rr, oH1, oL1, oL2, oL3, oL4, UL3, UL4.
0: Fault output not active.
1: Fault output active during reset attempt.
Undervoltage Fault Reset
Selection
0: Same as L5-01 condition
1: Always automatically reset UV1
Setting
Default: 0
Min: 0
Max: 10
Default: 0
Min: 0
Max: 1
Default: 0
Min: 0
Max: 1
■
L6: Torque Detection
No.
L6-01
L6-02
Name
Torque Detection Selection
1
Description
0: Disabled
1: oL3 detection only active during speed agree, operation continues after detection
2: oL3 detection always active during run, operation continues after detection
3: oL3 detection only active during speed agree, output shuts down on an oL3 fault
4: oL3 detection always active during run, output shuts down on an oL3 fault
5: UL3 detection only active during speed agree, operation continues after detection
6: UL3 detection always active during run, operation continues after detection
7: UL3 detection only active during speed agree, output shuts down on an oL3 fault
8: UL3 detection always active during run, output shuts down on an oL3 fault
Setting
Default: 0
Min: 0
Max: 8
Torque Detection Level 1 Sets the overtorque and undertorque detection level.
Default: 150%
Min: 0%
Max: 300%
Default: 0.1 s
Min: 0.0 s
Max: 10.0 s
L6-03
L6-04
Torque Detection Time 1
Sets the time an overtorque or undertorque condition must exist to trigger torque detection 1.
Torque Detection Selection
2
0: Disabled
1: oL4 detection only active during speed agree, operation continues after detection
2: oL4 detection always active during run, operation continues after detection
3: oL4 detection only active during speed agree, output shuts down on an oL4 fault
4: oL4 detection always active during run, output shuts down on an oL4 fault
5: UL4 detection only active during speed agree, operation continues after detection
6: UL4 detection always active during run, operation continues after detection
7: UL4 detection only active during speed agree, output shuts down on an oL4 fault
8: UL4 detection always active during run, output shuts down on an oL4 fault
Default: 0
Min: 0
Max: 8
L6-05
L6-06
Torque Detection Level 2
Torque Detection Time 2
Sets the overtorque and undertorque detection level.
Sets the time an overtorque or undertorque condition must exist to trigger torque detection 2.
Default: 150%
Min: 0%
Max: 300%
Default: 0.1 s
Min: 0.0 s
Max: 10.0 s
192 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 193 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
L7: Torque Limit
No. Name
L7-01 Forward Torque Limit
L7-02 Reverse Torque Limit
L7-03
L7-04
L7-16
Forward Regenerative
Torque Limit
Reverse Regenerative
Torque Limit
Torque Limit Process at
Start
Sets the torque limit value as a percentage of the motor rated torque. Four individual quadrants can be set.
0: Disabled
1: Enabled
REV
Description
Output Torque
L7-04
Regeneration
Positive Torque
L7-01
Motor r/min
FWD
Regeneration
L7-02
L7-03
Negative Torque
Setting
Default: 200%
Min: 0%
Max: 300%
Default: 200%
Min: 0%
Max: 300%
Default: 200%
Min: 0%
Max: 300%
Default: 200%
Min: 0%
Max: 300%
Default: 1
Min: 0
Max: 1
■
L8: Drive Protection
No.
L8-02
L8-03
L8-05
L8-06
L8-07
L8-09
L8-10
Name
Overheat Alarm Level
An overheat alarm will occur if the heatsink temperature exceeds the level set in
L8-02.
Description Setting
Min: 50 ° C
Max: 150 ° C
Overheat Pre-Alarm
Operation Selection
Input Phase Loss
Protection Selection
Input Phase Loss Detection
Level
Output Phase Loss
Protection Selection
0: Ramp to stop. A fault is triggered.
1: Coast to stop. A fault is triggered.
2: Fast Stop. Decelerate to stop using the deceleration ramp in C1-09. A fault is triggered.
3: Continue operation. An alarm is triggered.
Selects the detection of input current phase loss, power supply voltage imbalance, or main circuit electrolytic capacitor deterioration.
0: Disabled
1: Enabled always
2: Enabled during operation
3: Enabled during constant speed
Setting 1 cannot be selected for 600 V class drive models and models
CIMR-L F that are in compliance with IEC/EN 61508 SIL3 Safety Integrity
Level 3.
When ripple is observed in the DC bus, expansion of the input bias is calculated and becomes the input phase if the difference between the max and minimum values of the ripple are greater than L8-06.
Detection Level = 100% = Voltage class × (determines
0: Disabled
1: Enabled (triggered by a single phase loss)
2: Enabled (triggered when two phases are lost)
3: Fault at phase loss at start or when two phases lost mid-operation
Note: Setting 3 is available in the control mode V/f or OLV for drives with software versions PRG: 7200 or later.
Output Ground Fault
Detection Selection
Heatsink Cooling Fan
Operation Selection
Default: 3
Min: 0
Max: 3
Min: 0
Max: 3
Default: 0
Min: 0
Max: 3
Min: 0.0%
Max: 50.0%
0: Disabled
1: Enabled
Default: 1
Min: 0
Max: 1
0: Run with timer (Fan operates only during run and for L8-11 seconds after stop.)
1: Run always (Cooling fan operates whenever the drive is powered up.)
2: Temperature controlled (Cooling fan operated depending on the temperature of the drives heatsink.)
Default: 0
Min: 0
Max: 2
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 193
B
TOEP_C710616_38H_7_0.book 194 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
No.
L8-11
L8-12
L8-15
L8-27
L8-29
L8-35
L8-38
L8-39
L8-55
L8-62
L8-77
L8-88
L8-89
L8-99
Setting
Selection
Name
Heatsink Cooling Fan Off
Delay Time
Ambient Temperature oL2 (drive overload)
Characteristics Selection at
Low Speeds
Overcurrent Detection
Gain
Current Unbalance
Detection (LF2)
Installation Selection
Oscillation Suppression
Safe Disable Operation
Mode
Current Monitoring
Current Monitoring Level
0: No oL2 level reduction below 6 Hz.
1: oL2 level is reduced linearly below 6 Hz. It is halved at 0 Hz.
Sets the gain for overcurrent detection as a percentage of the motor rated current.
Overcurrent is detected using the drive’s overcurrent level or the value set to L8-27, whichever is lower.
0: IP00 enclosure drive
Description
Sets a delay time to shut off the cooling fan after the Up/Down command is removed when L8-10 = 0.
Enter the ambient temperature. This value adjusts the oL2 detection level.
0: Disabled
1: Enabled
2: IP00 enclosure drive with top protective cover
Used to suppress speed oscillations that occur with an unloaded motor and that have the same frequency as the output frequency.
0: Mode 0
1: Mode 1
Enables or disables the Current Monitoring function.
0: Disabled
1: Enabled
Sets the current monitoring level as a percentage of the drive’s rated current. Sets the level of current used for L8-89 and H2 = 5C.
Setting
Default: 60 s
Min: 0 s
Max: 300 s
Default: 40 ° C
Min: -10 ° C
Max: 50 ° C
Default: 1
Min: 0
Max: 1
Default: 300.0%
Min: 0.0%
Max: 300.0%
Default: 1
Min: 0
Max: 1
Default:
Min: 0
Max: 2
Automatic Torque Boost
Selection
Reduced Carrier
Frequency
Internal Braking Transistor
Protection
Operation Selection at
Input Phase Loss
Torque Boost increases the output current limit while decreasing the carrier frequency when the output current exceeds a certain value.
0: Disabled
3: Enabled
Default: 0
Min: 0
Max: 3
Sets the reduced carrier frequency used by the Torque Boost function.
0: Disabled. L8-55 should be disabled when using a regen converter or an optional braking unit.
1: Protection enabled.
Sets stopping method when a Input phase loss fault (PF) occurs. See parameter L8-05.
0: Ramp to Stop - Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to Stop
2: Fast Stop - Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only - Drive continues operation.
Default: 3.0 kHz
Min: 1.0 kHz
Max: 15.0 kHz
Default: 1
Min: 0
Max: 1
Default: 1
Min: 0
Max: 3
Default: 0
Min: -100
Max: 100
Default: 1
Min: 0
Max: 1
Default: 0
Min: 0
Max: 1
Default: 10.0%
Min: 0.0%
Max: 50.0%
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<4> Default setting is determined by the drive model (o2-04).
<44> Available in drive software versions PRG: 7017 or later.
<48> The default is 2 for 600 V class drive models and models CIMR-L F that are in compliance with IEC/EN 61508 SIL3 Safety Integrity
Level 3.
194 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 195 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
◆
n: Advanced Performance Set-Up
The n parameters are used to adjust more advanced performance characteristics such as speed feedback detection, Online
Tuning for motor line-to-line resistance, and PM motor control tuning.
■
n1: Hunting Prevention
No. n1-08
Name
Leakage Current Vibration
Control Selection
0: Method 1
1: Method 2
Description Setting
Default: 0
Min: 0
Max: 1
<45> Available in drive software versions PRG: 7200 or later.
■
n2: Speed Feedback Detection Control (AFR) Tuning
No. n2-01 n2-02 n2-03
Name
Speed Feedback Detection
Control (AFR) Gain
Description
Sets the internal speed feedback detection control gain in the automatic frequency regulator (AFR).
If hunting occurs, increase the set value. If response is low, decrease the set value.
Speed Feedback Detection
Control (AFR) Time
Constant 1
Speed Feedback Detection
Control (AFR) Time
Constant 2
Sets the time constant used for speed feedback detection control (AFR).
Sets the AFR time constant to be used during regen.
■
n5: Inertia Compensation
Setting
Default: 1.00
Min: 0.00
Max: 10.00
Default: 50 ms
Min: 0 ms
Max: 2000 ms
Default: 750 ms
Min: 0 ms
Max: 2000 ms
No. n5-01 n5-02
Selection
Name
Inertia Compensation
Motor Acceleration Time n5-03 Inertia Compensation Gain n5-07 n5-08
Speed Feedback
Compensation Selection
Speed Feedback
Compensation Gain (P)
0: Disabled
1: Enabled
Sets the time required to accelerate the motor at 100% torque from 0 to the nominal speed.
0: Disabled
1: Enabled
2: Test Mode
Description
Sets the ratio between motor and load inertia. Lower this setting if overshoot occurs at the end of acceleration.
Sets the proportional gain for the Speed Feedback Compensation.
Setting
Default: 0
Min: 0
Max: 1
Min: 0.001 s
Max: 10.000 s
Default: 1.00
Min: 0.00
Max: 100.00
Default: 1
Min: 0
Max: 2
Default: 12.00
Min: 0.00
Max: 300.00
<4> Default setting value is dependent on the drive model (o2-04).
■
n6: Online Tuning
No. Name n6-01 Online Tuning Selection n6-05 Online Tuning Gain
Description
0: Disabled
1: Line-to-line resistance tuning
2: Voltage correction.
Decrease this setting for motors with a relatively large rotor time constant.
If overload occurs, increase this setting slowly in increments of 0.1.
Setting
Default: 2
Min: 0
Max: 2
Default: 1.0
Min: 0.1
Max: 50.0
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 195
B
TOEP_C710616_38H_7_0.book 196 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
n8: PM Motor Control Tuning
No. n8-01 n8-02 n8-29 n8-30 n8-32 n8-33 n8-35 n8-36 n8-37 n8-62 n8-81 n8-82 n8-84 n8-86 q-Axis Current Control
Gain during Normal
Operation q-Axis Current Control
Integral Time during
Normal Operation d-Axis Current Control
Gain during Normal
Operation d-Axis Current Control
Integral Time during
Normal Operation
High Frequency Injection
Level
High Frequency Injection during Rescue Operation
High Frequency Injection
Amplitude during Rescue
Operation
Name
Initial Polarity Estimation
Current
Pole Attraction Current
Initial Rotor Position
Detection Selection
High Frequency Injection
Amplitude
Output Voltage Limit
Polarity Detection Current
Magnet Pole Search Error
Detection Selection
Description
Sets the current used for initial rotor position estimation as a percentage of the motor rated current (E5-03). If the motor nameplate lists an “Si” value, that value should be entered here.
Sets the current during initial polar attraction as a percentage of the motor rated current. Enter a high value when attempting to increase starting torque.
Sets the q axis proportional gain for the normal control range.
Sets the q axis integral time for the normal control range.
Sets the d axis proportional gain for the normal control range.
Sets the d axis integral time for the normal control range.
1: High frequency injection
2: Pulse injection
Sets the frequency in Hz for the superimposed signal used for superimposed harmonics.
Sets the amplitude for superimposed harmonics according to the voltage class of the motor. Adjust this value when there is too much or too little current as a result of the settings assigned to motor parameters.
Prevents output voltage saturation. Should be set just below the voltage provided by the input power supply.
Sets the frequency used for Polar Detection Method 1 during Rescue Operation.
Sets the amplitude for High Frequency Injection during Rescue Operation as a percentage of the voltage (200 V or 400 V).
Sets the current level (E5-03) as a percentage for detecting polarity during Initial
Polarity Estimation.
0: Disabled
1: Enabled
Default: 1
Min: 1
Max: 2
Default: 500 Hz
Min: 25 Hz
Max: 1000 Hz
Default: 20.0%
Min: 0.0%
Max: 99.9%
Default: 200.0
V
Min: 0.0 V
Max: 230.0 V
Default: 90 Hz
Min: 25 Hz
Max: 1000 Hz
Default: 15.0%
Min: 0.1%
Max: 99.9%
Default: 100%
Min: 0%
Max: 150%
Default: 0
Min: 0
Max: 1
Setting
Default: 50%
Min: 0%
Max: 100%
Default: 80%
Min: 0%
Max: 150%
Default: 1000 rad/ s
Min: 0 rad/s
Max: 2000 rad/s
Default: 10.0 ms
Min: 0.0 ms
Max: 100.0 ms
Default: 1000 rad/ s
Min: 0 rad/s
Max: 2000 rad/s
Default: 10.0 ms
Min: 0.0 ms
Max: 100.0 ms
<9> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. Multiply value by 2.875 for 600 V class drives.
■
n9: Current Detection Adjustments
No. n9-60
Name
A/D Conversion Start
Delay
Description
Sets a delay time for starting the current signal A/D conversion. This value seldom needs to be changed.
Setting
Default:
Min: 0.0 μ s
Max: 40.0 μ s
<4> Default setting is determined by the drive model (o2-04).
196 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 197 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
◆
o: Operator Related Parameters
The o parameters set up the digital operator displays.
■
o1: Digital Operator Display Selection
No. o1-01 o1-02 o1-03 o1-04 o1-05 o1-06
o1-07
o1-08
o1-10 o1-11 o1-12 o1-20
Selection
Name
Drive Mode Unit Monitor
Selection
User Monitor Selection after Power Up
Digital Operator Display
Unit Selection
V/f Pattern Setting Units
LCD Contrast Control
User Monitor Selection
Mode
Second Line Monitor
Selection
Third Line Monitor
User-Set Display Units
Maximum Value
User-Set Display Units
Decimal Display
Length Units
Description
Switches the display after the power has been turned on. When using an LED operator, pressing the up arrow key will display the following data: frequency reference → rotational direction → output frequency → output current → output voltage → U1 .
(This is done by entering the 1 part of U1 . Certain monitors are not available in some control modes.) o1-02 selects the information that is displayed when the power is turned on.
1: Speed reference (U1-01)
2: Direction
3: Output speed (U1-02)
4: Output current (U1-03)
5: User-selected monitor (set by o1-01)
Sets the units the drive should use to display the frequency reference and motor speed monitors.
0: 0.01 Hz
1: 0.01% (100% = E1-04)
2: r/min (calculated using the number of motor poles setting in E2-04, E4-04, or
E5-04)
3: User-selected units (set by o1-10 and o1-11)
4: Elevator units 1 (speed in m/s, accel/decel rate and jerk in s)
5: Elevator units 2 (speed in m/s, accel/decel rate in m/s 2 , jerk in m/s 3 )
6: Elevator units 3 (speed in ft/min, accel/decel rate in ft/s 2 , jerk in ft/s 3 )
Setting
Default: 106
(Monitor U1-06)
Min: 105
Max: 699
Default: 1
Min: 1
Max: 5
Default: 1
Min: 0
0: Hz
1: r/min
Sets the brightness of the LCD operator (option).
0: 3 Monitor Sequential (Displays the next 2 sequential monitors)
1: 3 Monitor Selectable (o1-07 and o1-08 selected monitor is displayed)
Selects the monitor displayed on the second line.
Selects the monitor displayed on the third line.
These settings define the display values when o1-03 is set to 3. o1-10 sets the display value that is equal to the maximum output frequency.
o1-11 sets the position of the decimal position.
0: Millimeter unit
1: Inch unit
Traction Sheave Diameter Sets the traction sheave diameter for display unit calculations.
Min: 0
Max: 1
Default: 3
Min: 0
Max: 5
Default: 0
Min: 0
Max: 1
Default: 102
Min: 101
Max: 699
Default: 103
Min: 101
Max: 699
Min: 1
Max: 60000
Min: 0
Max: 3
Default: 0
Min: 0
Max: 1
Default: 400 mm
Min: 100 mm
Max: 2000 mm
B
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 197
TOEP_C710616_38H_7_0.book 198 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
No. Name Description Setting o1-21 Roping Ratio
Sets the roping ratio.
1: 1:1
2: 1:2
3: 1:3
4: 1:4
Default: 2
Min: 1
Max: 4 o1-22 Mechanical Gear Ratio o1-23
HBB Non Display Select
Sets the ratio of the gear installed for display unit calculations.
Shows or hides the HBB command on the digital operator while the safety signal is being input.
0: Shows HBB
1: Hide HBB
Default:
Min: 0.10
Default: 0
Min: 0
Max: 1
<5> Default setting is determined by the control mode (A1-02).
<20> This parameter appears when the drive displays user-set units (o1-03 = 3).
<21> The control mode determines the selections available. In V/f Control, only settings 1 through 3 are permitted.
<38> Default setting and setting range changes when inches are selected for the length units (o1-12 = 1). The setting range becomes 3.70 to 78.00 inches, and the default becomes 15.70 inches.
<44> Available in drive software versions PRG: 7017 or later.
<45> Available in drive software versions PRG: 7200 or later.
<46> The setting range changes depending on drive software versions.
PRG: 7017 or earlier: 0.10 to 50.00
PRG: 7200 or later: 0.10 to 100.00
■
o2: Digital Operator Keypad Functions
No. o2-01 o2-02 o2-03 o2-04
LO/RE Key Function
Selection
Value
Name
STOP Key Function
Selection
User Parameter Default
Drive Model Selection
0: Disabled
1: Enabled. LO/RE key switches between LOCAL and REMOTE operation.
0: Disabled. STOP key is disabled in REMOTE operation.
1: Enabled. STOP key is always enabled.
0: No change.
Description
1: Set defaults. Saves parameter settings as default values for a User Initialization.
2: Clear all. Clears the default settings that have been saved for a User Initialization.
Enter the drive model. Setting required only if installing a new control board.
o2-05
Speed Reference Setting
Method Selection
0: ENTER key must be pressed to enter a speed reference.
1: ENTER key is not required. The speed reference can be adjusted using the up and down arrow keys only.
o2-06
Operation Selection when
Digital Operator is
Disconnected o2-09 Reserved
0: The drive continues operating if the digital operator is disconnected.
1: A fault is triggered (oPr) and the motor coasts to stop.
–
Setting
Default: 0
Min: 0
Max: 1
Default: 0
Min: 0
Max: 1
Default: 0
Min: 0
Max: 2
Default:
Determined by drive capacity
Min: –
Max: –
Default: 0
Min: 0
Max: 1
Default: 0
Min: 0
Max: 1
–
<1> Parameter setting value is not reset to the default value when the drive is initialized.
198 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 199 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
o3: Copy Function
No. Name o3-01 Copy Function Selection o3-02 Copy Allowed Selection
Description
0: Copy select
1: INV → OP READ (Read parameters from the drive, saving them onto the digital operator.)
2: OP → INV WRITE (Copy parameters from the digital operator, writing them to the drive.)
3: OP ↔ INV VERIFY (Verify parameter settings on the drive to check if they match the data saved on the operator.)
To read the drive’s parameter settings into the digital operator, set o3-02 to 1 (to allow reading).
Selects whether the read operation (o3-01 = 1) is enabled or disabled.
0: Read operation prohibited
1: Read operation allowed
Setting
Default: 0
Min: 0
Max: 3
Default: 0
Min: 0
Max: 1
■
o4: Maintenance Monitor Settings
No. o4-01 o4-02 o4-03 o4-05 o4-07 o4-15
o4-16
Setting o4-09 IGBT Maintenance Setting o4-11
Maintenance Monitoring
Selection
Name
Cumulative Operation
Time Setting
Cumulative Operation
Time Selection
Cooling Fan Operation
Time Setting
Capacitor Maintenance
DC bus Pre-charge Relay
Maintenance Setting
U2, U3 Initialization o4-12 kWh Monitor Initialization o4-13
Number of Travels
Counter Reset
Maintenance Alarm
Snooze Period
Sets the value of the Maintenance Monitor for the soft charge bypass relay. See U4-06 to check when the bypass relay may need to be replaced.
Sets the value of the Maintenance Monitor for the IGBTs. See U4-07 to check when the IGBTs may need to be replaced.
Description
Sets the value for the cumulative operation time of the drive in units of 10 h.
0: Logs power-on time
1: Logs operation time when the drive output is active (output operation time).
Sets the value of the fan operation time monitor U4-03 in units of 10 h.
Sets the value of the Maintenance Monitor for the capacitors. See U4-05 to check when the capacitors may need to be replaced.
0: U2 and U3 monitor data is not reset when the drive is initialized (A1-03).
1: Resets the data for the U2 and U3 monitors. Once o4-11 is set to 1 and the ENTER key is pressed, fault data is erased and the display returns to 0.
0: U4-10 and U4-11 monitor data is not reset when the drive is initialized (A1-03).
1: Resets the kWh counter. The monitors U4-10 and U4-11 will display “0” after they are initialized. Once o4-12 is set to 1 and the ENTER key is pressed, kWh data is erased and the display returns to 0.
0: Keep the number of travels counter value. The counter is not reset when the drive is initialized (A1-03).
1: Resets the number 0 travels counter. The monitor U4-24/25 will show 0. Once o4-13 is set to 1 and the ENTER key is pressed, the counter value is erased and the display returns to 0.
After a maintenance alarm output has been triggered, o4-15 determines the level that will trigger the next alarm for the same component. The same alarm will be triggered by the detection level that triggered the original alarm plus the level set in o4-15.
Selects the Maintenance Monitor using bits 0 to 3.
0: LT1 (cooling fan)
1: LT2 (DC bus capacitors)
2: LT3 (soft-charge bypass relay)
3: LT4 (IGBTs have passed 90% of the their life expectancy)
Default: 0
Min: 0
Max: 1
Default: 0
Min: 0
Max: 1
Default: 2%
Min: 0%
Max: 20%
Default: 1000
Min: 0000
Max: 1111
Setting
Default: 0
Min: 0
Max: 9999
Default: 0
Min: 0
Max: 1
Default: 0 h
Min: 0 h
Max: 9999 h
Default: 0%
Min: 0%
Max: 150%
Default: 0%
Min: 0%
Max: 150%
Default: 0%
Min: 0%
Max: 150%
Default: 0
Min: 0
Max: 1
<1> Parameter setting value is not reset to the default value during drive initialization (A1-03).
B
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 199
TOEP_C710616_38H_7_0.book 200 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
◆
S: Elevator Parameters
This section describes various functions and faults needed to operate an elevator application: braking sequence, slip compensation for elevators, start/stop optimization, Rescue Operation, and elevator-related faults.
■
S1: Brake Sequence
No.
S1-01
S1-02
S1-03
S1-04
S1-05
S1-12
S1-26
DC Injection Current at
Stop
DC Injection/Position
Lock Time at Stop
Output Contactor Open
Delay Time
Emergency Stop Start
Level
Name
Zero Speed Level at Stop
S1-06 Brake Release Delay Time
S1-07
S1-10
S1-11
DC Injection Current at
Start
DC Injection/Position
Lock Time at Start
Brake Close Delay Time
Run Command Delay
Time
Motor Contactor Control
During Auto-Tuning
Determines the speed to begin applying DC Injection (or Position Lock) when the drive is ramping to stop (b1-03 = 0). Set as a percentage of the maximum output frequency (E1-04).
Determines how long the drive should perform DC Injection at start. In CLV and
CLV/PM, S1-04 determines how long Position Lock should be performed. A setting of 0.00 disables S1-04.
Determines how long the drive should perform DC Injection at stop. In CLV and
CLV/PM, S1-05 determines how long Position Lock should be performed. A setting of 0.00 disables S1-05.
Determines the delay time between the start of DC injection/Position Lock and setting the brake control command (H2 = 50) in order to release the brake at the beginning of the ride.
Determines the delay time between reaching Zero Speed (S1-01) and resetting the brake control command (H2 = 50) in order to apply the brake at the end of the ride.
Description
Determines the amount of current to use for DC Injection at start. Set as a percentage of the drive rated current.
Determines the amount of current to use for DC Injection at stop. Set as a percentage of the drive rated current.
Sets the time that must pass after the Up/Down command is entered until the drive internal Run command is set and the ride is started.
Determines the delay time between shutting off the output of the drive and resetting the contactor control command (H2 = 51) in order to release the motor contactor after a ride has finished.
Determines the state of the output contactor control command (H2 = 51) during
Auto-Tuning.
0: Disabled
1: Enabled
2: Enabled during Auto-Tuning and HBB
Note: Setting 2 is available in the control mode CLV or CLV/PM for drives with software versions PRG: 7017 or later. The setting is 0 or 1 for software version PRG:
7016.
Default: 0
Min: 0
Max: 2
Setting
Default:
Min: 0.000%
Max: 9.999%
Default: 50%
Min: 0%
Max: 100%
Default: 50%
Min: 0%
Max: 100%
Default: 0.40 s
Min: 0.00 s
Max: 10.00 s
Default: 0.60 s
Min: 0.00 s
Max: 10.00 s
Default: 0.20 s
Min: 0.00 s
Max: 10.00 s
Default: 0.10 s
Min: 0.00 s
Max: [ S1-05 ]
Default: 0.10 s
Min: 0.00 s
Max: 1.00 s
Default: 0.10 s
Min: 0.00 s
Max: 1.00 s
Sets the Emergency Stop Start Level as a percentage of the Maximum Output
Frequency.
Default: 10.0%
Min: 0.0%
Max: 100.0%
<5> Default setting is determined by the control mode (A1-02).
<39> Available in drive software versions PRG: 7016 or later.
<44> Available in drive software versions PRG: 7017 or later.
200 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 201 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
S2: Slip Compensation for Elevators
No.
S2-01
S2-02
S2-03
S2-05
S2-06
Name
Motor Rated Speed
Slip Compensation Gain in
Motoring Mode
Slip Compensation Gain in
Regenerative Mode
Slip Compensation Torque
Detection Delay Time
Sets the motor rated speed.
Description
Slip compensation for leveling speed can be set separately for motoring and regenerative states. This can help improve the accuracy of leveling.
Sets a delay time before detecting torque for slip compensation.
Slip Compensation Torque
Detection Filter Time
Constant
Sets the filter time constant applied to the torque signal used for the slip compensation value calculation.
Setting
Default: 1380 rpm
Min: 300 rpm
Max: 1800 rpm
Default: 0.7
Min: 0.0
Max: 5.0
Default: 1.0
Min: 0.0
Max: 5.0
Default: 1000 ms
Min: 0 ms
Max: 10000 ms
Default: 500 ms
Min: 0 ms
Max: 2000 ms
■
S3: Start/Stop Optimization
No.
S3-01
S3-02
S3-03
S3-04
S3-10
S3-12
S3-14
S3-15
S3-16
S3-20
S3-21
Starting Torque
Compensation Increase
Time
Starting Torque
Compensation Bias in
Down Direction
Torque Limit Reduction
Time
Name
Position Lock Gain at Start
1
Position Lock Gain at Start
2
(Anti Rollback Gain)
Position Lock Gain at Stop
Position Lock Bandwidth
Torque Compensation
Diminish Speed
Torque Compensation
Diminish Time
Dwell 2 Speed Reference
Dwell 2 End Speed
Sets gain levels 1 and 2 for the Position Lock function. Position Lock at start attempts to keep the car position when opening the brake in order to avoid roll back.
Adds a bias to torque compensation value from the load cell when moving in the down direction.
Sets the speed level for torque compensation to diminish during the time determined by S3-15. Sets as a percentage of the maximum output frequency (E1-04). A setting of 0.0% disables this function.
Sets the time for torque compensation to diminish once motor speed reaches the level set in S3-14.
Description
Sets the Position Lock gain at stop. Position Lock at stop keeps the car in position until the brake has been applied entirely.
Determines the bandwidth around the stop position in which a digital output programmed for “Within Position Lock Bandwidth” (H2 = 33) is closed.
Sets a time constant for the torque reference to reach 300%. Enabled by setting an analog input terminal for torque compensation (H3 = 14).
Setting
Default: 5
Min: 0
Max: 100
Default: 0.00
Min: 0.00
Max: 100.00
Default: 5
Min: 0
Max: 100
Default: 10
Min: 0
Max: 16383
Default: 500 ms
Min: 0 ms
Max: 5000 ms
Default: 0
Min: -40.0%
Max: 40.0%
Default: 0.0%
Min: 0.0%
Max: 200.0%
Default: 1000 ms
Min: 0 ms
Max: 5000 ms
Determines the reduction rate used bring the internal torque reference value down to zero after Position Lock at Stop has finished.
Rate = Torque 300%
S3-16
Default: 100 ms
Min: 0 ms
Max: 10000 ms
Sets the speed reference for the Dwell 2 function.
Note: A setting of 0.00 essentially disables the Dwell 2 function.
The Dwell 2 function will end when the drive reaches this speed.
Note: A setting of 0.00 will disable the acceleration rate switch that occurs at the end of Dwell 2.
Default: 0.00%
Min: 0.00%
Max: 100.00%
Default: 0.00%
Min: 0.00%
Max: 100.00%
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 201
B
TOEP_C710616_38H_7_0.book 202 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
No.
S3-25
S3-26
S3-27
S3-28
S3-29
S3-30
S3-34
S3-35
S3-37
S3-38
S3-39
S3-40
S3-41
Name
DC Injection Gain in
Regenerative Operation
DC Injection Gain in
Motoring Operation
Description
Sets the gain level applied to the DC injection current at stop (S1-03) for when the load is 100% regenerative. The current applied during DC Injection at stop is determined as S1-03 × S3-25.
Sets the gain level applied to the DC injection current at stop (S1-03) for when the load is 100% motoring. The current applied during DC Injection at stop is determined as S1-03 × S3-26.
Torque Compensation
Value with Load Condition
1
Torque Compensation
Value with Load Condition
2
Used for starting torque compensation utilizing a load cell signal. Sets the torque compensation value for load condition 1.
Used for starting torque compensation utilizing a load cell signal. Sets the torque compensation value for load condition 2.
Analog Input from Load
Cell with Load Condition 1
Analog Input from Load
Cell with Load Condition 2
Used for starting torque compensation utilizing a load cell signal. Sets the analog signal level from the load cell for load condition 1.
Used for starting torque compensation utilizing a load cell signal. Sets the analog signal level from the load cell for load condition 2.
Anti-Rollback Torque Bias
1
Sets the Anti-Rollback Bias applied at small position deviations during Position Lock at start.
Anti-Rollback Torque Bias
2
Position Deviation Level to
Apply ARB Torque Bias 1
Position Deviation Level to
Apply ARB Torque Bias 2
Anti-Rollback Integral
Gain
Anti-Rollback Movement
Detection
Position Lock Gain at Start
2 Reduction
Sets the Anti-Rollback Bias applied at large position deviations during Position Lock at start.
Sets the position deviation level to active at Anti-Rollback Torque Bias 1 (S3-34).
Determines the position deviation level for when the drive should switch from the torque bias set in S3-34 to the torque bias set in S3-35.
Determines the drive’s responsiveness for Anti-Rollback during Position Lock.
Sets the amount of pulses for movement detection during Anti-Rollback.
Sets a reduction factor for the Position Lock Gain at Start 2 (Anti-Rollback Gain) set in parameter S3-02.
Setting
Default: 100%
Min: 0%
Max: 400%
Default: 20%
Min: 0%
Max: 400%
Default: -50%
Min: -100%
Max: 100%
Default: 50%
Min: -100%
Max: 100%
Default: 0.0%
Min: -100%
Max: 100%
Default: 100.0%
Min: -100.0%
Max: 100%
Default: 0.0%
Min: 0.0%
Max: 100.0%
Default: 0.0%
Min: 0.0%
Max: 100.0%
Default: 0
Min: 0
Max: 32767
Default: 0
Min: 0
Max: 32767
Default: 0.00
Min: -30.00
Max: 30.00
Default: 1 pulse
Min: 0 pulse
Max: 100 pulses
Default: 0.50
Min: 0.00
Max: 1.00
■
S4: Rescue Operation
No.
S4-01
S4-02
S4-03
S4-04
Name
Light Load Direction
Search Selection
Light Load Direction
Search Method
Light Load Direction
Search Time
Light Load Direction
Search Speed Reference
Description
0: Disabled
1: Enabled
2: Enabled for Motor 1 only
Determines how the drive detects the light load direction.
0: Output Current
1: Regenerative direction detection
Sets the time to perform Light Load Direction Search.
Sets the speed reference to use during Light Load Direction Search.
Setting
Default: 0
Min: 0
Max: 2
Default: 1
Min: 0
Max: 1
Default: 1.0 s
Min: 0.0 s
Max: 5.0 s
Default:
Min: 0.00%
Max: 20.00%
202 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 203 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
No.
S4-05
S4-06
Name
Rescue Operation Torque
Limit
Description
Sets the torque limit used during Rescue Operation.
Rescue Operation Power
Supply Selection
0: Battery
1: UPS (single-phase)
2: UPS (3-phase)
S4-07 UPS Power Sets the capacity of the UPS.
Setting
Default: 100%
Min: 0%
Max: 300%
Default: 0
Min: 0
Max: 2
Default: 0.0 kVA
Min: 0.0 kVA
Max: 100.0 kVA
S4-08
S4-12
S4-13
S4-15
UPS Operation Speed
Limit Selection
Determines how a speed limit should be applied to the Rescue Operation speed
(S4-15) when operating from a UPS.
0: Disabled
1: Enabled until Light Load Direction Search is complete
2: Enabled until stop
DC Bus Voltage during
Rescue Operation
Sets the DC bus voltage during Rescue Operation.
Rescue Operation Power
Supply Deterioration
Detection Level
Determines at which level of backup power supply deterioration a PF5 fault is triggered.
Speed Reference Selection for Rescue Operation
Selects the speed reference used for Rescue Operation.
Default: 2
Min: 0
Max: 2
Default: 0 V
Min: 0 V
Max: 1150 V
Default: 80%
Min: 10%
Max: 100%
Default: 0
Min: 0
Max: 1
<5> Default setting is determined by the control mode (A1-02).
<39> Available in drive software versions PRG: 7016 or later.
■
S5: Short Floor Operation
No.
S5-01
S5-02
S5-03
S5-04
S5-05
Selection
Name
Short Floor Operation
Nominal Speed for Short
Floor Calculation
Short Floor Minimum
Constant Speed Time
Distance Calculation
Acceleration Time Gain
Distance Calculation
Deceleration Time Gain
S5-10 Stopping Method Selection
S5-11
S5-12
Deceleration Distance
Stop Distance
0: Disabled
1: Enabled (Short Floor)
2: Enabled (Advance Short Floor)
When d1-18 (Speed Priority Selection) is set to 0 or 3, S5-02 determines the rated speed used during Short Floor.
0: Disabled
1: Direct Landing
2: Leveling Distance Control
Description
Sets the minimum operation time when the Advanced Short Floor function is enabled
(S5-01 = 2).
Set for acceleration jerk compensation in Distance Calculation.
Set for deceleration jerk compensation in Distance Calculation.
Sets the deceleration distance when Stop Distance Control is enabled.
Sets the stopping distance when Stop Distance Control is enabled.
Setting
Default: 0
Min: 0
Max: 2
Default: 0.0%
Min: 0.0%
Max: 100.0%
Default: 0.0 s
Min: 0.0 s
Max: 2.0 s
Default: 150.0%
Min: 50.0%
Max: 200.0%
Default: 150.0%
Min: 50.0%
Max: 200.0%
Default: 0
Min: 0
Max: 2
Default: 0 mm
Min: 0 mm
Max: 32767 mm
Default: 0 mm
Min: 0 mm
Max: 10000 mm
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 203
B
TOEP_C710616_38H_7_0.book 204 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
No.
S5-13
Name
Direct Landing Minimum
Speed Level
Description
Sets the speed level for the start of Direct Landing.
Direct Landing is essentially disabled if the starting speed for Direct Landing is less than the maximum output speed multiplied by this parameter (E1-04 × S5-13).
<36> When the length units are set for inches (o1-12 = 1), the setting range becomes 0.00 to 650.00 inches.
<37> When the length units are set for inches (o1-12 = 1), the setting range becomes 0.00 to 393.00 inches.
■
S6: Error Detection
Setting
Default: 20%
Min: 0%
Max: 100%
No.
S6-01
S6-02
S6-03
S6-04
S6-05
S6-10
S6-11
S6-12
S6-15
S6-16
Time
Name
Motor Contactor Response
Error (SE1) Detection/
Reset Selection
Starting Current Error
(SE2) Detection Delay
SE2 Detect Current Level
Output Current Error (SE3)
Detection Delay Time
Brake Response Error
(SE4) Detection Time
Description
0: Detect during stop, SE1 must be manually reset
1: Detect during stop, SE1 can be automatically reset
2: No SE1 detection
Sets a delay time for detecting SE2.
Sets the level of current applied to the motor when the Brake Control command is activated, as a percentage of the Motor No-load Current (E2-03).
Sets a delay time for detecting SE4.
Overacceleration Detection
Level
If the elevator car accelerates at an abnormal rate, the drive triggers an overspeed fault
(dv6) and has the motor coast to stop. Parameter S6-10 determines the acceleration rate that triggers a fault.
Overacceleration Detection
Time
Overacceleration Detection
Selection
Speed Reference Loss
Detection
Restart after Baseblock
Selection
Sets a delay time for detecting SE3.
Sets a primary delay for detecting overacceleration.
0: Always enabled
1: During run only
Enabled or disables detection for speed reference missing (FrL).
0: Disabled
1: Enabled
0: No restart after Baseblock/Safe Torque-Off
1: Restart after Baseblock/Safe Torque-Off
Setting
Default: 0
Min: 0
Max: 2
Default: 200 ms
Min: 0.00 ms
Max:
[S1-04]-[S1-06]
Default: 25%
Min: 0%
Max: 100%
Default: 200 ms
Min: 0 ms
Max: 5000 ms
Default: 500 ms
Min: 0 ms
Max: 10000 ms
Min: 0.0 m/s 2
Max: 20.0 m/s
Default: 50 ms
Min: 0 ms
Max: 5000 ms
Default: 0
Min: 0
Max: 1
Default: 1
Min: 0
Max: 1
Default: 0
Min: 0
Max: 1
<7> Default setting value is determined by the digital operator display unit selection (o1-03). The default is normally 1.5 m/s2, but when o1-03 = 6, the default becomes 5.0 ft/s 2 (Setting Range: 0.0 to 50.0 ft/s 2 ).
<44> Available in drive software versions PRG: 7017 or later.
204 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 205 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
◆
T: Motor Tuning
Enter data into the following parameters to tune the motor and drive for optimal performance.
■
T1: Induction Motor Auto-Tuning
No.
T1-01
T1-02
T1-03
T1-04
T1-05
T1-06
T1-07
T1-08
T1-09
T1-10
Selection
Name
Auto-Tuning Mode
Motor Rated Power
Motor Rated Voltage
Motor Rated Current
Motor Base Frequency
Number of Motor Poles
Motor Base Speed
Encoder Resolution (pulses per revolution)
0: Rotational Auto-Tuning
1: Stationary Auto-Tuning 1
2: Stationary Auto-Tuning for Line-to-Line Resistance
4: Stationary Auto-Tuning 2
Sets the motor rated power as specified on the motor nameplate.
Note: Use the following formula to convert horsepower into kilowatts: kW = HP ×
0.746.
Set the number of pulses per revolution for the PG being used (pulse generator or encoder).
Description
Sets the motor rated voltage as specified on the motor nameplate.
Sets the motor rated current as specified on the motor nameplate.
Sets the rated frequency of the motor as specified on the motor nameplate.
Sets the number of motor poles as specified on the motor nameplate.
Sets the rated speed of the motor as specified on the motor nameplate.
Motor No-Load Current
(Stationary Auto-Tuning 1 and 2)
Motor Rated Slip
(Stationary Auto-Tuning 2)
Sets the no-load current for the motor.
After setting the motor capacity to T1-02 and the motor rated current to T1-04, this parameter will automatically display the no-load current for a standard 4 pole
Yaskawa motor. Enter the no-load current as indicated on the motor test report.
Sets the motor rated slip.
After setting the motor capacity to T1-02, this parameter will automatically display the motor slip for a standard 4 pole Yaskawa motor. Enter the motor slip as indicated on the motor test report.
Setting
Min: 0
Min: 0.00 kW
Max: 650.00 kW
Default: 200.0
V
Min: 0.0 V
Min: 10% of drive rated current
Max: 200% of drive rated
Default: 50.0 Hz
Min: 0.0 Hz
Max: 200.0 Hz
Default: 4
Min: 2
Max: 48
Default: 1450 r/ min
Min: 0 r/min
Max: 24000 r/min
Default: 1024 ppr
Min: 0 ppr
Max: 60000 ppr
Default: –
Min: 0 A
Max: Up to
T1-04
Default: –
Min: 0.00 Hz
Max: 20.00 Hz
<4> Default setting value varies by the drive model (o2-04).
<5> Default setting is determined by the control mode (A1-02).
<9> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. Multiply value by 2.875 for 600 V class drives.
<10> The display resolution depends on the rated output power of the drive. Models CIMR-LU2 0008 to 2 0033, 4 0005 to 4 0018, and
5 0003 to 5 0013 display values in 0.01 A units, while models CIMR-LU2 0047 to 2 0415, 4 0024 to 4 0605, and 5 0017 to 5 0200 display values in 0.1 A units.
<18> The variety of Auto-Tuning methods depends on the control mode setting. V/f Control allows T1-01 to be set to 2 or 3, while vector control modes (OLV and CLV) allow T1-01 to be set to 0 through 4.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 205
B
TOEP_C710616_38H_7_0.book 206 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
T2: PM Motor Auto-Tuning
No.
T2-01
T2-04
T2-05
T2-06
T2-08
T2-09
T2-10
T2-11
T2-12
T2-13
T2-14
T2-16
T2-17
T2-18
Constant
Name
Motor Auto-Tuning Mode
Selection
Motor Rated Power
Motor Rated Voltage
Motor Rated Current
Number of Motor Poles
Motor Base Speed
Single Phase Stator
Resistance
Motor d-Axis Inductance
Motor q-Axis Inductance
Induced Voltage Constant
Unit Selection
Motor Induced Voltage
Encoder Resolution
Encoder Offset
Speed Reference for
Auto-Tuning of PG-E3
Encoder Characteristics
Description
0: Motor Data input
1: Stationary Auto-Tuning
2: Stationary stator resistance Auto-Tuning
3: Initial magnet pole search parameters Auto-Tuning
4: Encoder offset stationary Auto-Tuning
10: Encoder offset rotational Auto-Tuning
11: Rotational back EMF constant Auto-Tuning
12: Auto-Tuning of PG-E3 encoder characteristics
Setting 12 is available in drive software versions PRG: 7017 or later.
Auto-Tuning of PG-E3 encoder characteristics requires a PG-E3 option with software version 1102 or later. To identify the PG-E3 software version, refer to the PG-E3 labeling on the option, in the field designated “C/N” (S + four digit number).
Setting
Default: 0
Min: 0
Max: 12
Sets the motor rated power as indicated on the motor nameplate.
Enter the motor rated voltage as indicated on the motor nameplate.
Enter the motor rated current as indicated on the motor nameplate.
Enter the number of motor poles for the motor as indicated on the motor nameplate.
Enter the base speed for the motor as indicated on the motor nameplate.
Enter the 1-phase resistance of the stator winding.
Enter the d-axis inductance for the motor as indicated on the motor nameplate.
Enter the q-axis inductance for the motor as indicated on the motor nameplate.
0: mV/(r/min). E5-09 will automatically be set to 0.0, and E5-24 will be used.
1: mV/(rad/sec). E5-24 will automatically be set to 0.0, and E5-09 will be used.
Enter the induced voltage coefficient for the motor as indicated on the motor nameplate.
Sets the number of pulses per revolution for the PG being used (pulse generator or encoder).
Sets the offset between encoder offset and the rotor magnetic axis.
Sets the speed reference for execution of Auto-Tuning of PG-E3 encoder characteristics (T2-01 = 12).
Default:
Min: 0.00 kW
Max: 650.00 kW
Default: 200.0
V
Min: 0.0 V
Max: 255.0 V
Default:
Min: 10% of drive rated current
Max: 200% of drive rated
Default: 6
Min: 2
Default: 150 r/min
Min: 0 r/min
Max: 24000 r/min
Default: –
Min: 0.000 Ω
Max: 65.000 Ω
Default: –
Min: 0.00 mH
Max: 600.00 mH
Default: –
Min: 0.00 mH
Max: 600.00 mH
Default: 1
Min: 0
Max: 1
Default: –
Min: 0.0
Default: 1024 ppr
Min: 1 ppr
Max: 15000 ppr
Default: 0.0 deg
Min: -180.0 deg
Max: 180.0 deg
Default: 10 r/min
Min: 1 r/min
Max: 30 r/min
206 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 207 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
No.
T2-19
Name
Rotation Direction for
Auto-Tuning of PG-E3
Encoder Characteristics
Description
Sets the direction of motor rotation for execution of Auto-Tuning of PG-E3 encoder characteristics (T2-01 = 12).
0: Forward (Up)
1: Reverse (Down)
Setting
Default: 0
Min: 0
Max: 1
<4> Default setting value varies by the drive model (o2-04).
<9> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. Multiply value by 2.875 for 600 V class drives.
<10> The display resolution depends on the rated output power of the drive. Models CIMR-LU2 0008 to 2 0033, 4 0005 to 4 0018, and
5 0003 to 5 0013 display values in 0.01 A units, while models CIMR-LU2 0047 to 2 0415, 4 0024 to 4 0605, and 5 0017 to 5 0200 display values in 0.1 A units.
<30> Setting units are determined by the induced voltage constant unit selection for PM motors set to T2-13.
<43> When PG-E3 option connected: Max setting = 48
<44> Available in drive software versions PRG: 7017 or later.
◆
U: Monitors
Monitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.
■
U1: Operation Status Monitors
No. Name
U1-01 Speed Reference
U1-02 Output Speed
U1-03 Output Current
Monitors the speed reference.
Displays the output speed.
Description
Analog Output
Level
10 V: Max frequency
(-10 to +10 V)
10 V: Max frequency
(-10 to +10 V)
10 V: Drive rated current
Unit
0.01%
0.01%
U1-04 Control Method
Displays the output current.
0: V/f Control
2: Open Loop Vector Control
3: Closed Loop Vector Control
7: Closed Loop Vector Control for PM
No signal output available
–
U1-05 Speed Feedback
U1-06
Output Voltage
Reference
U1-07 DC Bus Voltage
U1-08 Output Power
U1-09 Torque Reference
Displays the motor speed feedback.
Displays the output voltage.
Displays the DC bus voltage.
Displays the output power (this value is calculated internally).
Monitors the internal torque reference.
10 V: Max
Frequency
(-10 to +10 V)
10 V: Drive rated power
(kW)
(-10 to +10 V)
0.01%
10 V: 200
Vrms
0.1 Vac
10 V: 400 V
1 Vdc
10 V: Motor rated torque
(-10 to +10 V)
0.1%
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 207
B
TOEP_C710616_38H_7_0.book 208 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
No. Name
U1-10 Input Terminal Status
Displays the input terminal status.
Description
U1 - 10= 00000000
YEA_co mmon
1 Digital input 1
(terminal S1 enabled)
1 Digital input 2
(terminal S2 enabled)
1
1
Digital input 3
(terminal S3 enabled)
Digital input 4
(terminal S4 enabled)
1
1
1
1
Digital input 5
(terminal S5 enabled)
Digital input 6
(terminal S6 enabled)
Digital input 7
(terminal S7 enabled)
Digital input 8
(terminal S8 enabled)
Displays the output terminal status.
U1-11 Output Terminal Status
YEA_co mmon
U1 - 11= 00000000
1
Multi-Function
Digital Output
(terminal M1-M2)
1 Multi-Function
Digital Output
(terminal M3-M4)
1 Multi-Function
Digital Output
(terminal M5-M6)
1 Multi-Function
Digital Output
(terminal P1-C1)
1 Multi-Function
Digital Output
(terminal P2-C2)
Not Used
1 Fault Relay
(terminal MA-MC closed
MA-MC open)
Displays the drive operation status.
U1-12 Drive Status
U1-13
U1-14
U1-16
U1-17
YEAco mmon
U1 - 12= 00000000
1
1
1
1
During run
During zero-speed
During down direction
During fault reset signal input
1
During speed agree
1
1
Drive ready
During alarm detection
1
During fault detection
Terminal A1 Input
Voltage
Terminal A2 Input
Voltage
Displays the voltage input to terminal A1.
Displays the voltage input to terminal A2.
Output Speed after Soft
Start
Displays output speed with ramp time and jerk settings. Units determined by o1-03.
DI-A3 Option Card
Input Status
Displays the reference value input from the DI-A3 option card.
Display will appear in hexadecimal as determined by the digital card input selection in F3-01.
3FFFF: Set (1 bit) + sign (1 bit) + 16 bit
Analog Output
Level
Unit
No signal output available
–
No signal output available
–
No signal output available
–
10 V: 100%
(-10 to +10 V)
10 V: 100%
(-10 to +10 V)
10 V: Max frequency
(-10 to +10 V)
No signal output available
0.1%
0.1%
0.01%
–
208 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 209 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
No. Name
U1-18 oPE Fault Parameter
Description
Displays the parameter number that caused the oPE02 or oPE08 (Operation error).
Analog Output
Level
No signal output available
Displays the contents of a MEMOBUS/Modbus error.
Unit
–
U1-19
MEMOBUS/Modbus
Error Code
U1 - 19= 00000000
YEAcom mon
1
CRC Error
1
0
Data Length Error
Not Used
1
1
Parity Error
Overrun Error
1
1
0
Framing Error
Timed Out
Not Used
U1-25
Software Number
(Flash)
FLASH ID
U1-26 Software No. (ROM) ROM ID
No signal output available
–
No signal output available
No signal output available
–
–
<9> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. Multiply value by 2.875 for 600 V class drives.
<10> The display resolution depends on the rated output power of the drive. Models CIMR-LU2 0008 to 2 0033, 4 0005 to 4 0018, and
5 0003 to 5 0013 display values in 0.01 A units, while models CIMR-LU2 0047 to 2 0415, 4 0024 to 4 0605, and 5 0017 to 5 0200 display values in 0.1 A units.
<12> The display resolution depends on the rated output power of the drive. Models CIMR-LU2 0008 to 2 0033, 4 0005 to 4 0018, and
5 0003 to 5 0013 display values in 0.01 kW units, while models CIMR-LU2 0047 to 2 0415, 4 0024 to 4 0605, and 5 0017 to
5 0200 display values in 0.1 kW units.
<29> Setting units are determined by the digital operator display unit selection (o1-03). When o1-03 = 0, the value is set in Hertz. When o1-03 = 4 or
5, the value is displayed in m/s. When o1-03 = 6, the value is displayed in ft/min.
<40> When checking the values of U1-03, U2-05 and U4-13 with the digital operator they are displayed in units of amperes, but when they are checked using MEMOBUS communications, the monitor value in MEMOBUS communications is: displayed numeric value / 8192 × drive’s rated current (A), from the condition “8192 (maximum value) = drive’s rated current (A)”.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 209
B
TOEP_C710616_38H_7_0.book 210 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
U2: Fault Trace
No.
U2-01
U2-02
U2-03
U2-04
U2-05
U2-06
U2-07
U2-08
U2-09
U2-10
U2-11
U2-12
U2-13
U2-14
U2-15
U2-16
U2-17
U2-20
U2-21
U2-22
Name
Current Fault
Previous Fault
Speed Reference at
Previous Fault
Output Speed at
Previous Fault
Output Current at
Previous Fault
Motor Speed at
Previous Fault
Output Voltage at
Previous Fault
DC Bus Voltage at
Previous Fault
Output Power at
Previous Fault
Torque Reference at
Previous Fault
Input Terminal Status at
Previous Fault
Output Terminal Status at Previous Fault
Drive Operation Status at Previous Fault
Cumulative Operation
Time at Previous Fault
Soft Starter Output at
Previous Fault
Motor q-Axis Current at
Previous Fault
Motor d-Axis Current at
Previous Fault
Heatsink Temperature at Previous Fault
Peak Hold Current during Fault
Peak Hold Frequency during Fault
Displays the current fault.
Displays the previous fault.
Displays the operation status of the drive at the previous fault. Displayed as in
U1-12.
Displays the output frequency when the peak current displayed in U2-21 occurred.
Description
Displays the speed reference at the previous fault.
Displays the output speed at the previous fault.
Displays the output current at the previous fault.
Displays the motor speed at the previous fault.
Displays the output voltage at the previous fault.
Displays the DC bus voltage at the previous fault.
Displays the output power at the previous fault.
Displays the torque reference at the previous fault.
Displays the input terminal status at the previous fault. Displayed as in U1-10.
Displays the output status at the previous fault. Displayed as in U1-11.
Displays the cumulative operation time at the previous fault.
Displays the run speed after a soft start when a previous fault occurred. Displayed as in U1-16.
Displays the q-axis current for the motor at the previous fault. Displayed as in
U6-01.
Displays the d-axis current for the motor at the previous fault. Displayed as in
U6-02.
Displays the temperature of the heatsink when the most recent fault occurred.
Displayed as in U4-08.
Displays the peak current that occurred just prior to the previous fault.
Analog Output
Level
No signal output available
No signal output available
No signal output available
Unit
–
–
0.01%
No signal output available
No signal output available
0.01%
No signal output available
No signal output available
0.01%
0.1 Vac
No signal output available
No signal output available
1 Vdc
0.1 kW
No signal output available
No signal output available
0.1%
–
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
–
–
1 h
0.01%
0.1%
No signal output available
No signal output available
0.1%
1 ° C
No signal output available
0.01 A
No signal output available
0.01 Hz
<10> The display resolution depends on the rated output power of the drive. Models CIMR-LU2 0008 to 2 0033, 4 0005 to 4 0018, and
5 0003 to 5 0013 display values in 0.01 A units, while models CIMR-LU2 0047 to 2 0415, 4 0024 to 4 0605, and 5 0017 to 5 0200 display values in 0.1 A units.
<29> Setting units are determined by the digital operator display unit selection (o1-03). When o1-03 = 0, the value is set in Hertz. When o1-03 = 4 or
5, the value is displayed in m/s. When o1-03 = 6, the value is displayed in ft/min.
<40> When checking the values of U1-03, U2-05 and U4-13 with the digital operator they are displayed in units of amperes, but when they are checked using MEMOBUS communications, the monitor value in MEMOBUS communications is: displayed numeric value / 8192 × drive’s rated current (A), from the condition “8192 (maximum value) = drive’s rated current (A)”.
210 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 211 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
U3: Fault History
No.
U3-01 to
U3-04
U3-05 to
U3-10
U3-11 to
U3-14
U3-15 to
U3-20
Name Description
First to 4th Most Recent
Fault
Displays the first to the fourth most recent faults.
5th to 10th Most Recent
Fault
Displays the fifth to the tenth most recent faults.
After ten faults have occurred in the drive, data for the oldest fault is deleted. The most recent fault appears in U3-01, with the next most recent fault appearing in
U3-02. The data is moved to the next monitor parameter every time a fault occurs.
Cumulative Operation
Time at 1st to 4th Most
Recent Fault
Cumulative Operation
Time at 5th to 10th
Most Recent Fault
Displays the cumulative operation time when the first to the fourth most recent faults occurred.
Displays the cumulative operation time when the fifth to the tenth most recent faults occurred.
Analog Output
Level
No signal output available
No signal output available
No signal output available
No signal output available
Unit
–
–
1 h
1 h
■
U4: Maintenance Monitors
No. Name Description
Analog Output
Level
U4-01
U4-03
U4-04
U4-05
U4-06
U4-07
Cumulative Operation
Time
Cooling Fan Operation
Time
Cooling Fan
Maintenance
Capacitor Maintenance
Soft Charge Bypass
Relay Maintenance
IGBT Maintenance
Displays the cumulative operation time of the drive. The value for the cumulative operation time counter can be reset in parameter o4-01. Use parameter o4-02 to determine if the operation time should start as soon as the power is switched on or only while the Up/Down command is present. The maximum number displayed is
99999, after which the value is reset to 0.
Displays the cumulative operation time of the cooling fan. The default value for the fan operation time is reset in parameter o4-03. This value will reset to 0 and start counting again after reaching 99999.
Displays main cooling fan usage time in as a percentage of its expected performance life. Parameter o4-03 can be used to reset this monitor. The fan should be replaced when this monitor reaches 90%.
Displays main circuit capacitor usage time in as a percentage of their expected performance life. The capacitors should be replaced when this monitor reaches
90%. Parameter o4-05 can be used to reset this monitor.
Displays the soft charge bypass relay maintenance time as a percentage of its estimated performance life. The soft charge relay should be replaced when this monitor reaches 90%. Parameter o4-07 can be used to reset this monitor.
Displays IGBT usage time as a percentage of the expected performance life. The
IGBTs should be replaced when this monitor reaches 90%. Parameter o4-09 can be used to reset this monitor.
U4-08 Heatsink Temperature Displays the heatsink temperature.
U4-09 LED Check Lights all segments of the LED to verify that the display is working properly.
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
10 V: 100 ° C
No signal output available
Unit
1 h
1 h
1%
1%
1%
1%
1 °
–
C
U4-10
U4-11 kWh, Lower 4 Digits kWh, Upper 5 Digits
Monitors the drive output power. The value is shown as a 9 digit number displayed across two monitor parameters, U4-10 and U4-11.
Example:
12345678.9 kWh is displayed as:
U4-10: 678.9 kWh
U4-11: 12345 MWh
No signal output available
No signal output available
1 kWh
1 MWh
U4-13
U4-14
U4-16
Peak Hold Current
Peak Hold Output
Frequency
Motor Overload
Estimate (oL1)
Displays the highest current value that occurred during a ride.
Displays the output frequency when the current value shown in U4-13 occurred.
Shows the value of the motor overload detection accumulator. 100% is equal to the oL1 detection level.
No signal output available
0.01 A
No signal output available
0.01 Hz
10 V: 100% 0.1%
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 211
B
TOEP_C710616_38H_7_0.book 212 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
U4-23
U4-24
U4-25
U4-26
U4-27
U4-28
No.
U4-17
U4-18
U4-19
U4-20
U4-21
U4-22
U4-29
U4-30
Name Description
Analog Output
Level
Unit
Drive Overload
Calculations (oL2)
Speed Reference
Selection Results
Displays the level of the drive overload detection (oL2). A value of 100% is equal to the oL2 detection level.
Displays the source for the speed reference as XY-nn.
X: indicates which reference is used:
1 = Reference 1 (b1-01)
Y-nn: indicates the reference source
0-01 = Digital operator
1-01 = Analog (terminal A1)
1-02 = Analog (terminal A2)
2-02 to 8 = Digital Inputs (d1-02 to 8)
3-01 = MEMOBUS/Modbus communications
4-01 = Communication option card
Speed Reference from
MEMOBUS/Modbus
Comm.
Speed Reference From
Option Card
Displays the speed reference provided by MEMOBUS/Modbus (decimal).
Displays the speed reference input by an option card (decimal).
Up/Down Command
Source Selection
Displays the source for the Up/Down command as XY-nn.
X: Indicates which Up/Down command source is used:
1 = Reference 1 (b1-02)
Y: Input power supply data
0 = Digital operator
1 = External terminals
3 = MEMOBUS/Modbus communications
4 = Communication option card nn: Up/Down command limit status data
00: No limit status.
01: Up/Down command was left on when stopped in the PRG mode
02: Up/Down command was left on when switching from LOCAL to REMOTE operation
03: Waiting for soft charge bypass contactor after power up (Uv or Uv1 flashes after 10 s)
04: Waiting for “Up/Down Command Prohibited” time period to end
05: Fast Stop (multi-function input, operator)
07: During baseblock while coast to stop with timer
08: Speed reference is below minimal reference during baseblock
09: Waiting for Enter command
MEMOBUS/Modbus
Communications
Reference
Communication Option
Card Reference
Number of Travels
(Lower 4 digit)
Number of Travels
(Higher 4 digit)
Max. Current during
Acceleration
Max. Current during
Deceleration
Max. Current during
Constant Speed
Max. Current during
Leveling Speed
Slip Compensation
Value
Displays the drive control data set by MEMOBUS/Modbus communications register no. 0001H as a four-digit hexadecimal number.
Displays drive control data set by an option card as a four-digit hexadecimal number.
Displays the lower four digits for the number of trips the drive has made.
Displays the upper four digits for the number of trips the drive has made.
Shows the maximum current that occurred during acceleration.
Shows the maximum current that occurred during deceleration.
Shows the maximum current that occurred during ride at top speed.
Shows the maximum current that occurred during ride at leveling speed.
Shows the slip compensation value.
10 V = 100%
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
0.1%
–
0.01%
0.01%
–
–
–
1 time
1 time
0.1 A
0.1 A
0.1 A
0.1 A
0.01%
212 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 213 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
No. Name Description
U4-31 Car Acceleration Rate Shows the car acceleration rate.
U4-40
Speed Reference Limit at Rescue Operation
Displays the speed limit for Rescue Operation based on how much power the backup battery or UPS has. Displays 0% when Rescue Operation is not being performed.
Analog Output
Level
Unit
No signal output available
0.01 m/ s 2
No signal output available
1%
U4-42
U4-43
U4-44
Remaining Distance Displays the remaining distance according to the stopping method selected.
Minimum Deceleration
Distance
Minimum Stop
Distance
Displays the Minimum Deceleration Distance calculated by E1-04.
Displays the Minimum Stop Distance calculated by d1-26.
10 V:
S5-10 = 1: S5-11
S5-10 = 2: S5-12
No signal output available
No signal output available
1 mm
1 mm
1 mm
<29> Setting units are determined by the digital operator display unit selection (o1-03). When o1-03 = 0, the value is set in Hertz. When o1-03 = 4 or
5, the value is displayed in m/s. When o1-03 = 6, the value is displayed in ft/min.
<35> o1-12 (Length Units) determines the units. When o1-12 is set to 0, the unit is millimeters. When o1-12 is set to 1, the unit is inch.
<40> When checking the values of U1-03, U2-05 and U4-13 with the digital operator they are displayed in units of amperes, but when they are checked using MEMOBUS communications, the monitor value in MEMOBUS communications is: displayed numeric value / 8192 × drive’s rated current (A), from the condition “8192 (maximum value) = drive’s rated current (A)”.
<41> The MEMOBUS communications data is in 10 h units. If data in 1 h units are also required, refer to register number 0099H.
<42> The MEMOBUS communications data is in 10 h units. If data in 1 h units are also required, refer to register number 009BH.
Note: Fault trace (i.e., the fault history) is not maintained when CPF00, CPF01, CPF06, CPF24, oFA00, oFb00, oFC00, Uv1, Uv2, or
Uv3 occur.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 213
B
TOEP_C710616_38H_7_0.book 214 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table
■
U6: Control Monitors
No.
U6-01
U6-02
U6-03
U6-04
U6-05
U6-06
U6-07
U6-08
U6-13
U6-18
U6-22
U6-25
U6-26
U6-56
U6-80 to U6-99
Input
Output
Name
Motor Secondary
Current (Iq)
Motor Excitation
Current (Id)
Speed Control Loop
Speed Control Loop
Output Voltage
Reference (Vq)
Output Voltage
Reference (Vd) q-Axis Current
Controller Output d-Axis Current
Controller Output
Flux Position Detection
(sensor)
Speed Detection PG1
Counter
Displays the value of the motor secondary current (Iq). Motor rated secondary current is 100%.
Displays the value calculated for the motor excitation current (Id). Motor rated secondary current is 100%.
Description
Displays the input and output values of the speed control loop.
Output voltage reference (Vq) for the q-axis.
Output voltage reference (Vd) for the d-axis.
Displays the output value for current control relative to motor secondary current
(q-axis).
Displays the output value for current control relative to motor secondary current
(d-axis).
Monitors the value of the flux position detection (sensor).
Monitors the number of pulses for speed detection (PG1).
Analog Output
Level
10 V: Motor secondary rated current
(-10 to +10 V)
10 V: Motor secondary rated current
(-10 to +10 V)
10 V: Max frequency
(-10 to +10 V)
10 V: Motor secondary rated current
(-10 to +10 V)
10 V: 200
(-10 to +10 V)
10 V: 200
(-10 to +10 V)
10 V: 200
(-10 to +10 V)
10 V: 200
(-10 to +10 V)
10 V: 180 deg
-10 V: -180 deg
Unit
0.1%
0.1%
0.01%
0.1 Vac
0.1 Vac
0.1%
0.1%
0.1 deg
10 V: 65536 1 pulse
Position Lock
Deviation Counter
Feedback Control
Output
Inertia Compensation
Output
Speed Feedback
Compensation Output
Displays how far the rotor has moved from its last position in PG pulses
(multiplied by 4).
Output monitor for the speed control loop.
Output monitor for Inertia Compensation.
Displays observed speed when n5-07 = 1 or 2.
Option Monitor 1 to 20 Monitors reserved to display data from option cards.
10 V: No. of pulses per revolution
(-10 to +10 V)
10 V: Motor secondary rated current
(-10 to +10 V)
10 V: Motor secondary rated current
(-10 to +10 V)
10 V: Max output frequency
No signal output available
1 pulse
0.01%
0.01%
0.01%
–
<9> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. Multiply value by 2.875 for 600 V class drives.
214 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 215 ページ 2015年11月11日 水曜日 午後7時40分
B Parameter Table d1-01 d1-02 d1-03 d1-04 d1-05 d1-06
C2-01
C2-02
C2-03
C2-04
C2-05
C1-11 d1-07 d1-08 d1-19 d1-20 d1-21 d1-22 d1-23 d1-24 d1-25 d1-26
C1-01
C1-02
C1-03
C1-04
C1-05
C1-06
C1-07
C1-08
C1-09
C1-15
◆
Defaults and Setting Ranges by Display Unit Selection (o1-03)
shows parameters, default settings, and setting ranges that change according to parameter o1-03, Display Unit
Selection.
Table 58 Defaults and Setting Ranges by Display Unit Selection (o1-03)
No.
Name
0
(0.01 Hz) o1-03 (Digital Operator Display Unit Selection)
1
(0.01%)
2
(r/min)
3
(User-set)
4
(Elevator units 1)
5
(Elevator units 2)
6
(Elevator units 3)
Default
Acceleration Ramp 1
Deceleration Ramp 1
Acceleration Ramp 2
Deceleration Ramp 2
Acceleration Ramp 3
Deceleration Ramp 3
Acceleration Ramp 4
Deceleration Ramp 4
Fast Stop Time
Inspection Run Deceleration
Ramp
Jerk at Accel Start
Jerk at Accel End
Jerk at Decel Start
Jerk at Decel End
Jerk below leveling speed
Accel/Decel Switching Speed
Speed Reference 1
Speed Reference 2
Speed Reference 3
Speed Reference 4
Speed Reference 5
Speed Reference 6
Speed Reference 7
Speed Reference 8
Nominal Speed
Intermediate Speed 1
Intermediate Speed 2
Intermediate Speed 3
Releveling Speed
Inspection Operation Speed
Rescue Operation Speed
Leveling Speed
0.00 to
[E1-04] Hz
0.00 to
100.00%
0.00 to 600.00 s
0.00 to 10.00 s
r/min
User define 0.00 to
m/s m/s
2
3
0.00 to ft/s ft/s
0.00 to
2
3 ft/min
1.50 s
0.00 s
0.50 s
0.0%
0.00%
100.0%
0.00%
50.00%
10.00%
8.00%
<1> Automatically calculated according to the values set to o1-20, o1-21, o1-22, and E2 /E5 parameters.
<2> Automatically calculated according to the values set to the E2 /E5 parameters.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 215
B
TOEP_C710616_38H_7_0.book 216 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
C Standards Compliance
◆
European Standards
Figure 90
Figure 99 CE Mark
The CE mark indicates that a product is in compliance with applicable European Directives for safety and environmental regulations. It is required for engaging in business and commerce in Europe.
The applicable European Directives for this product are as follows. We declared the CE marking based on the harmonized standards in the following table.
Applicable European Directive
Low Voltage Directive (2006/95/EC)
EMC Directive (2004/108/EC)
Machinery Directive (2006/42/EC)
Applicable Harmonized Standards
IEC/EN 61800-5-1: 2007
EN 61800-3: 2004/A1: 2012
IEC 61800-3: 2004/A1: 2011
IEC/EN 62061: 2005 (SILCL3)
<1> These standards are in compliance for models CIMR-L F only.
The user(s) is solely responsible for ensuring that the end products used with this drive comply with all applicable
European directives and with other national regulations (if required).
Note: 600 V class drives (models 5 ) are not compliant with European Standards.
■
CE Low Voltage Directive Compliance
This drive has been tested according to European standard IEC/EN 61800-5-1, and it fully complies with the Low Voltage
Directive.
To comply with the Low Voltage Directive, be sure to meet the following conditions when combining this drive with other devices:
Area of Use
Do not use drives in areas with pollution higher than degree 2 and overvoltage category 3 in accordance with IEC/EN
664.
216 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 217 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
2 0075
2 0085
2 0115
2 0145
2 0180
2 0215
2 0283
2 0346
2 0415
2 0008
2 0011
2 0014
2 0018
2 0025
2 0033
2 0047
2 0060
4 0060
4 0075
4 0091
4 0112
4 0150
4 0180
4 0216
4 0260
4 0304
4 0370
4 0450
4 0605
4 0005
4 0006
4 0007
4 0009
4 0015
4 0018
4 0024
4 0031
4 0039
4 0045
Factory Recommended Branch Circuit Protection
Table 59 Recommended Input Fuse Selection
Drive Model
CIMR-LU
5 0003
5 0004
5 0006
25
30
40
60
60
75
100
125
150
200
250
300
350
400-450-500
Nominal
Output Power
HP
AC Drive Input
Amps
7.5
10
15
20
25
30
40
50
3
5
2
3
60
75
100
125
150
7.5
11
15.6
18.9
28
37
52
68
80
82
111
136
164
200
271
324
394
MCCB Rating
Amps
L1000
Time Delay
Fuse Rating
Amps
Three-Phase 200 V Class
15
20
12
17.5
25
35
50
60
100
125
150
150
200
250
300
400
500
600
700
25
30
40
60
90
110
125
125
175
225
250
350
450
500
600
Three-Phase 400 V Class
5
5
3
3
7.5
10
15
20
4.4
6
8.2
10.4
15
20
29
39
15
15
15
20
30
40
50
75
7
10
12
17.5
25
35
50
60
2
3
5
47
43
58
71
86
105
142
170
207
248
346
410
465
657
3.6
5.1
8.3
225
250
350
400
600
800
75
75
100
125
150
175
900
1200
800
Three-Phase 600 V Class
15
15
15
6.25
8
12
225
250
350
400
600
700
75
75
100
110
150
175
Non-time
Delay Fuse
Rating Amps
10
15
20
225
225
250
350
450
600
800
900
1100
75
100
150
200
20
30
40
50
125
125
150
200
250
300
12
17.5
20
30
40
60
80
110
400
500
600
700
Bussmann
Semi-conductor Fuse
Rating
(Fuse Ampere)
FWH-70B (70)
FWH-70B (70)
FWH-90B (90)
FWH-90B (90)
FWH-100B (100)
FWH-200B (200)
FWH-200B (200)
FWH-200B (200)
FWH-300A (300)
FWH-300A (300)
FWH-350A (350)
FWH-400A (400)
FWH-400A (400)
FWH-600A (600)
FWH-700A (700)
FWH-800A (800)
FWH-1000A (1000)
FWH-70B (70)
FWH-70B (70)
FWH-90B (90)
FWH-90B (90)
FWH-80B (80)
FWH-100B (100)
FWH-125B (125)
FWH-200B (200)
FWH-250A (250)
FWH-250A (250)
FWH-250A (250)
FWH-250A (250)
FWH-250A (250)
FWH-350A (350)
FWH-400A (400)
FWH-500A (500)
FWH-600A (600)
FWH-700A (700)
FWH-800A (800)
FWH-800A (800)
FWH-1000A (1000)
FWH-1200A (1200)
FWP-50B (50)
FWP-60B (60)
FWP-60B (60)
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 217 C
TOEP_C710616_38H_7_0.book 218 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
Drive Model
CIMR-LU
5
5
5
5
5
5
5
5
5
5
5
5
5
5
Nominal
Output Power
HP
AC Drive Input
Amps
MCCB Rating
Amps
<1>
50-60
75
100
125
150
200
7.5
10
15
20
25
25-30
40
50-60
66
80
108
129
158
228
38
33
44
54
12
16
23
31
125
150
175
250
300
400
75
60
75
100
20
30
40
60
L1000
Time Delay
Fuse Rating
Amps
<2>
110
125
175
225
250
350
60
50
75
90
20
25
40
50
Non-time
Delay Fuse
Rating Amps
<3>
175
225
300
350
400
600
100
90
125
150
35
45
60
90
Bussmann
Semi-conductor Fuse
Rating
(Fuse Ampere)
<4>
FWP-70B (70)
FWP-100B (100)
FWP-100B (100)
FWP-125A (125)
FWP-125A (125)
FWP-175A (175)
FWP-175A (175)
FWP-250A (250)
FWP-250A (250)
FWP-250A (250)
FWP-350A (350)
FWP-350A (350)
FWP-600A (600)
FWP-600A (600)
<1> Maximum MCCB Rating is 15 A, or 200% of drive input current rating, whichever is larger. MCCB voltage rating must be 600 VAC or greater.
<2> Maximum Time Delay fuse is 175% of drive input current rating. This covers any Class CC, J or T class fuse.
<3> Maximum Non-time Delay fuse is 300% of drive input current rating. This covers any CC, J or T class fuse.
<4> When using semiconductor fuses, Bussmann FWH and FWP are required for UL compliance. Select FWH for 240 V and 480 V models and
FWP fuses for 600 V models.
<5> Class L fuse is also approved for this rating.
<6> 600 V class drives are not compliant with European Standards.
Grounding
The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded systems, contact your Yaskawa representative for instructions.
CE Standards Compliance for DC Power Supply Input
To meet CE standards, the following fuses should be installed. For details, refer to Figure 100 .
Figure 91
DC power supply
(converter)
Fuse
+
_
+1
_
U/ T1
V/ T2
W/ T3
M
Drive
YEC_common
Fuse
+1
_
Drive
U/ T1
V/ T2
W/ T3
M
Figure 100 Example of DC Power Supply Input (two L1000A drives connected in series)
Note: 1.
When connecting multiple drives together, make sure that each drive has its own fuse. If any one fuse blows, all fuses should be replaced.
2.
For an AC power supply, refer to Standard Connection Diagram on page 25
.
3.
The recommended fuses and fuse holders are made by Fuji Electric.
218 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 219 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
2 0008
2 0011
2 0014
2 0018
2 0025
2 0033
2 0047
2 0060
2 0075
2 0085
2 0115
2 0145
2 0180
2 0215
2 0283
2 0346
2 0415
Drive Model
CIMR-LU
Type
CR2LS-50
CR2LS-75
CR2LS-100
CR2L-125
CR2L-150
CR2L-175
CR2L-225
CR2L-260
CR2L-300
CR2L-350
CR2L-400
CR2L-450
CR2L-600
CS5F-800
CS5F-1200
Table 60 Fuses and Fuse Holders
DC Power Supply Input
Fuse
Rated
Short-circu it Breaking
Current
(kA)
Qty.
Fuse Holder
Type Qty.
200 V Class
Drive Model
CIMR-LU
Type
100
200
2
2
2
CM-1A
CM-2A
1
1
4 0005
4 0006
4 0007
4 0009
4 0015
4 0018
4 0024
4 0031
4 0039
4 0045
4 0060
4 0075
4 0091
4 0112
4 0150
4 0180
4 0216
4 0260
4 0304
4 0370
4 0450
4 0605
CR6L-50
CR6L-75
CR6L-100
CR6L-150
CR6L-200
CR6L-250
CR6L-300
CR6L-350
CR6L-400
CS5F-600
CS5F-800
CS5F-1200
CS5F-1500
Fuse
Rated
Short-circu it Breaking
Current
(kA)
Qty.
Fuse Holder
Type Qty.
400 V Class
100
200
200
2
2
2
2
CMS-4
CMS-5
2
2
<1> DC is not available for UL standards.
<2> Manufacturer does not recommend a specific fuse holder for this fuse. Contact Yaskawa or your nearest sales representative on fuse dimensions.
Guarding Against Harmful Materials
When installing IP00 enclosure drives, use an enclosure that prevents foreign material from entering the drive from above or below.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 219 C
TOEP_C710616_38H_7_0.book 220 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
■
EMC Guidelines Compliance
This drive is tested according to European standards IEC/EN 61800-3: 2004, and complies with the European standards
IEC/EN 12015 (requires an optional AC reactor) and IEC/EN 12016.
Note: Make sure the protective earthing conductor complies with technical standards and local safety regulations. Because the leakage current exceeds 3.5 mA when an EMC filter is installed, IEC/EN 61800-5-1 states that either the power supply must be automatically disconnected in case of discontinuity of the protective earthing conductor or a protective earthing conductor with a cross-section of at least 10 mm 2 (Cu) or 16 mm 2 (Al) must be used.
EMC Filter Installation
The following conditions must be met to ensure continued compliance with European standards IEC/EN 12015 and IEC/
EN 12016.
Refer to EMC Filters on page 222 for EMC filter selection.
Installation Method
Verify the following installation conditions to ensure that other devices and machinery used in combination with this drive also comply with EMC guidelines.
1.
Install an EMC noise filter to the input side specified by Yaskawa for compliance with European standards.
2.
Place the drive and EMC noise filter in the same enclosure.
3.
Use braided shield cable for the drive and motor wiring, or run the wiring through a metal conduit.
4.
Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.
Figure 92
B
A D C
U/T1
V/T2
W/T3
U
V
W
M
E
A – Drive
B – 10 m max cable length between drive and motor
C – Motor
D – Metal conduit
E – Ground wire should be as short as possible.
Figure 101 Installation Method
5.
Make sure the protective earthing conductor complies with technical standards and local safety regulations.
WARNING!
Electrical Shock Hazard. Because the leakage current exceeds 3.5 mA in models CIMR-L 4A0370 and larger, IEC/EN
61800-5-1 states that either the power supply must be automatically disconnected in case of discontinuity of the protective earthing conductor or a protective earthing conductor with a cross-section of at least 10 mm 2 (Cu) or 16 mm 2 (Al) must be used. Failure to comply may result in death or serious injury.
Figure 93
A
220
A – Braided shield cable
B – Metal panel
C B
C – Cable clamp (conductive)
Figure 102 Ground Area
6.
Connect an AC reactor or a DC link choke to minimize harmonic distortion.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 221 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
Three-Phase 200 V / 400 V Class
Figure 94
L3
L2
L1
Make sure the ground wire is grounded
PE
Enclosure panel
Metal plate
Grounding surface
(remove any paint or sealant)
YEA_common
E
EMC noise filter
Drive
Grounding surface
(remove any paint or sealant)
Ground plate
(scrape off any visible paint)
Cable clamp Motor cable (braided shield cable, max. 10 m)
Ground the cable shield
Motor
Figure 103 EMC Filter and Drive Installation for CE Compliance (Three-Phase 200 V / 400 V Class)
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 221 C
TOEP_C710616_38H_7_0.book 222 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
4 0005
4 0006
4 0007
4 0009
4 0015
4 0018
4 0024
4 0031
4 0039
4 0045
4 0060
4 0075
4 0091
4 0112
4 0150
4 0180
4 0216
4 0260
4 0304
4 0370
4 0450
4 0605
EMC Filters
Install the drive with the EMC filters below to comply with the IEC/EN 61800-3 and IEC/EN 12015 requirements.
Note: If the Safe Disable function of the drive is part of the safety concept of a machine or installation and used for a safe stop according to EN 60204-1, stop category 0, use these filters recommended by Yaskawa. For all other EMC filters, additional measurements must be performed to prove EMC compatibility. This also applies when using the safe disable function in one motor contactor installations as described in
Safe Disable Input Function on page 237 .
Table 61 IEC/EN 61800-3 Filters
Model
CIMR-LU Type
Filter Data (Manufacturer: Schaffner)
Rated Current
(A)
Weight
(lb)
Dimensions
[W x D x H]
(in)
Three-Phase 200 V Class
Y x X
(in)
Figur e
2 0008
2 0011
2 0014
2 0018
2 0025
2 0033
2 0047
2 0060
2 0075
2 0185
2 0115
2 0145
2 0180
2 0215
2 0283
2 0346
2 0415
FS5972-18-07
FS5972-35-07
FS5972-60-07
FS5972-100-35
FS5972-170-40
FS5972-250-37
FS5972-410-99
FS5972-600-99
18
35
60 8.8
100 7.5
170 13.2
250 25.8
410
600
2.9
4.6
23.1
24.3
5.6 × 1.8 × 13.0
8.1 × 2.0 × 14.0
5.1
× 9.5 × 24.0
10.2 × 4.5 × 15.2
10.2 × 5.3 × 15.2
4.5 × 12.3
6.9 × 13.2
8.1 × 15.4
2.6 × 10.0
4.0 × 14.4
3.5 × 19.6
9.3 × 4.7
9.3 × 4.7
1
2
3
Three-Phase 400 V Class
FS5972-10-07
FS5972-18-07
FS5972-35-07
FS5972-60-07
FS5972-100-35
FS5972-170-35
FS5972-250-37
FS5972-410-99
FS5972-600-99
FS5972-800-99
10
18
35
60
100
170
250
410
600
800
2.6
2.9
4.6
8.8
16.5
10.4
25.8
23.1
24.3
69.4
5.6 × 13.0 × 1.8
5.6 × 1.8 × 13.0
8.1 × 2.0 × 14.0
9.3 × 2.6 × 16.1
3.5 × 5.9 × 13.0
4.7 × 6.7 × 17.8
5.1
× 9.5 × 24.0
10.2 × 4.5 × 15.2
10.2 × 5.3 × 15.2
11.8 × 28.2 × 6.3
4.5 × 12.3
4.5 × 12.3
6.9 × 13.2
8.0 × 15.4
2.6 × 10.0
4.0 × 14.4
3.5 × 19.6
9.3 × 4.7
9.3 × 4.7
10.8 × 8.3
1
2
3
222 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 223 ページ 2015年11月11日 水曜日 午後7時40分
Figure 95
W
Y
.
.
.
Filter Side (LINE)
D
LINE
LOAD
Figure 1
Drive Side (LOAD)
Filter Side (LINE)
W
Y
L1
L1
PE
L2
LINE
L2
LINE
L3
L3
Recommended torque: 26 - 30Nm / PE: 15 - 17Nm
ZSN FS5972-250-37
ZSN 3x480/275V 50/60Hz
250A@45°C 25/100/21
C Standards Compliance
Filter Side (LINE)
D
ZSN High leakage current,
ZSN first connect to earth!
LOAD
L1' L2'
L1'
LOAD
L2' L3'
Recommended torque: 26 - 30Nm / PE: 15 - 17Nm
PE
L3'
Drive Side (LOAD)
Figure 2
D
L3
L3 L2
LINE
L2
LINE
L1
L1
L3'
L3' L2'
LOAD
L2'
LOAD
L1'
L1'
Y
W
Drive Side (LOAD)
Figure 3
Figure 104 EMC Filter Dimensions
AC Reactors for IEC/EN 12015 Compliance
Contact Yaskawa for information about reactors.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 223 C
TOEP_C710616_38H_7_0.book 224 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
◆
UL and CSA Standards
■
UL Standards Compliance
The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product testing and evaluation, and determined that their stringent standards for product safety have been met. For a product to receive
UL certification, all components inside that product must also receive UL certification.
Figure 96
Figure 105 UL/cUL Mark
This drive is tested in accordance with UL standard UL508C and complies with UL requirements. To ensure continued compliance when using this drive in combination with other equipment, meet the following conditions:
Installation Area
Do not install the drive to an area greater than pollution degree 2 (UL standard).
Ambient Temperature
IP00 enclosure with top protective cover: -10 to +40 ° C (14 to 104 ° F)
IP00 enclosure: -10 to +50 ° C (14 to 122 ° F)
Main Circuit Terminal Wiring
Yaskawa recommends using closed-loop crimp terminals on all drive models. UL/cUL approval requires the use of UL
Listed closed-loop crimp terminals when wiring the drive main circuit terminals on models CIMR-LU2 0085 through
2 0415, 4 0045 through 4 0605, and 5 0032 to 5 0200. Use only the tools recommended by the terminal manufacturer for crimping.
The wire gauges listed in Table 62 and
are Yaskawa recommendations. Refer to local codes for proper wire gauge selections.
Table 62 Wire Gauge and Torque Specifications (Three-Phase 200 V Class)
Model
CIMR-LU
2 0008
2 0011
2 0014
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
Recommended
Gauge
AWG, kcmil
14
14
–
–
10
12
14
–
–
10
–
–
10
10
10
Applicable Gauge
AWG, kcmil
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
12 to 10
14 to 10
14 to 10
14 to 10
14 to 10
Screw
Size
M4
M4
M4
Tightening Torque
N m (lb.in.)
1.2 to 1.5
(10.6 to 13.3)
1.2 to 1.5
(10.6 to 13.3)
1.2 to 1.5
(10.6 to 13.3)
224 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
Model
CIMR-LU
2
2
0018
0025
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
2
2
0033
0047
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
2 0060
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
2 0075
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
2 0085
2 0115
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
B1, B2
TOEP_C710616_38H_7_0.book 225 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
Applicable Gauge
AWG, kcmil
12 to 10
12 to 10
12 to 10
14 to 10
12 to 10
10 to 6
10 to 6
10 to 6
14 to 10
10 to 8
8 to 6
8 to 6
6
12 to 10
10 to 8
6 to 4
6 to 4
6 to 4
10 to 6
8 to 6
4 to 3
4 to 3
4 to 3
8 to 6
6 to 4
3 to 2
3 to 2
3 to 2
6
6 to 4
3 to 1/0
3 to 1/0
2 to 1/0
6 to 1/0
6 to 4
1 to 2/0
1 to 2/0
1/0 to 3/0
4 to 2/0
4
6
3
3
–
–
6
2
2
–
–
6
6
2/0
2/0
–
–
1/0
1/0
–
–
4
Recommended
Gauge
AWG, kcmil
10
10
–
–
–
–
8
8
–
–
6
8
4
4
–
–
Screw
Size
Tightening Torque
N m (lb.in.)
M4
M4
M5
M4
M5
M6
M5
M6
M8
M5
M6
M8
M5
M6
M8
M10
M8
1.2 to 1.5
(10.6 to 13.3)
2.1 to 2.3
(18.6 to 20.4)
2.0 to 2.5
(17.7 to 22.1)
2.1 to 2.3
(18.6 to 20.4)
2.0 to 2.5
(17.7 to 22.1)
5.4 to 6.0
(47.8 to 53.1)
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
(47.8 to 53.1)
9.9 to 11.0
(87.6 to 97.4)
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
(47.8 to 53.1)
9.9 to 11.0
(87.6 to 97.4)
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
(47.8 to 53.1)
9 to 11
(79.7 to 97.4)
18 to 23
(159 to 204)
9 to 11
(79.7 to 97.4)
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 225 C
TOEP_C710616_38H_7_0.book 226 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
CIMR-LU
2
2
Model
0145
0180
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
Terminal
Recommended
Gauge
AWG, kcmil
4/0
4/0
–
–
4
1/0 × 2P
1/0 × 2P
–
–
4
3/0 × 2P
3/0 × 2P
–
–
Applicable Gauge
AWG, kcmil
2/0 to 4/0
3/0 to 4/0
1 to 4/0
1/0 to 4/0
4 to 2
1/0 to 2/0
1/0 to 2/0
1 to 4/0
1/0 to 4/0
4 to 1/0
3/0 to 300
3/0 to 300
3/0 to 300
2 to 300
Screw
Size
M10
M10
Tightening Torque
N m (lb.in.)
18 to 23
(159 to 204)
9 to 11
(79.7 to 97.4)
18 to 23
(159 to 204)
9 to 11
(79.7 to 97.4)
2 0215
2 0283
2 0346
2 0415
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
3
4/0 × 2P
3/0 × 2P
–
–
2
250 × 2P
4/0 × 2P
–
–
1
350 × 2P
300 × 2P
–
–
1
3 to 300
3/0 to 300
3/0 to 300
3/0 to 300
3/0 to 300
2 to 300
4/0 to 600
4/0 to 600
250 to 600
3/0 to 600
1 to 350
250 to 600
300 to 600
300 to 600
3/0 to 600
1 to 350
M12
M10
M12
M12
M10
M12
M12
M10
M12
M12
M10
M12
32 to 40
(283 to 354)
18 to 23
(159 to 204)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
18 to 23
(159 to 204)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
18 to 23
(159 to 204)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
18 to 23
(159 to 204)
32 to 40
(283 to 354)
<2> Drive models CIMR-LU2 0085 to 2 0415 require the use of closed-loop crimp terminals for UL/cUL compliance. Use only the tools recommended by the terminal manufacturer for crimping.
Note: Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a continuous maximum allowable temperature of 75 ° C (167 ° F) 600 V UL approved vinyl sheathed insulation. Ambient temperature should not exceed
40 ° C (104 ° F).
226 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 227 ページ 2015年11月11日 水曜日 午後7時40分
Model
CIMR-LU
4 0005
4 0006
4 0007
4 0009
4 0015
4 0018
4 0024
4 0031
4 0039
4 0045
C Standards Compliance
Table 63 Wire Gauge and Torque Specifications (Three-Phase 400 V Class)
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
Recommended
Gauge
AWG, kcmil
14
14
–
–
10
–
–
10
10
–
–
12
14
10
Applicable Gauge
AWG, kcmil
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
12 to 6
12 to 6
12 to 6
12 to 10
Screw
Size
M4
M4
M4
Tightening Torque
N m (lb.in.)
1.2 to 1.5
(10.6 to 13.3)
1.2 to 1.5
(10.6 to 13.3)
2.1 to 2.3
(18.6 to 20.4)
10 14 to 10 M5
2.0 to 2.5
(17.7 to 22.1)
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
–
–
10
10
10 to 6
10 to 6
12 to 6
12 to 10
M4
2.1 to 2.3
(18.6 to 20.4)
10 12 to 10 M5
2.0 to 2.5
(17.7 to 22.1)
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
8
8
–
8 to 6
10 to 6
10 to 6
M5
3.6 to 4.0
(31.8 to 35.4)
B1, B2 – 10 to 8 M5
M6
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
(47.8 to 53.1)
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
8
6
8
–
10 to 8
8 to 6
8 to 6
6
M5
3.6 to 4.0
(31.8 to 35.4)
B1, B2 –
6
10 to 8
10 to 6
M5
M6
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
(47.8 to 53.1)
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
6
6
–
6 to 4
6 to 4
6 to 4
M6
5.4 to 6.0
(47.8 to 53.1)
B1, B2 – 10 to 8 M5
M6
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
(47.8 to 53.1)
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
B1, B2
6
4
4
–
–
6
8 to 6
6 to 4
6 to 4
6 to 1
8 to 4
8 to 6
M8
9 to 11
(79.7 to 97.4)
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 227 C
TOEP_C710616_38H_7_0.book 228 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
Model
CIMR-LU
4 0060
4 0075
4 0091
4 0112
4 0150
4 0180
4 0216
4 0260
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
4 0304
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
–
4
300
300
–
–
3/0
2/0
–
–
4
4/0
4/0
–
Recommended
Gauge
AWG, kcmil
3
3
–
–
6
1/0
1
–
–
4
–
–
2
2
4
4
400
400
–
–
2
500
500
–
–
2
4/0 × 2P
4/0 × 2P
–
–
1
Applicable Gauge
AWG, kcmil
1/0 to 4/0
4 to 2
2 to 300
2 to 300
1 to 250
3 to 3/0
4 to 300
1 to 600
1/0 to 600
3/0 to 600
1 to 325
2 to 350
2/0 to 600
2/0 to 600
3/0 to 600
2 to 1/0
2 to 1/0
3 to 1/0
4 to 1/0
6 to 4
1/0 to 4/0
1/0 to 4/0
1/0 to 4/0
3 to 4/0
4
3/0 to 4/0
3/0 to 4/0
1 to 4/0
4 to 3
4 to 3
4 to 1
6 to 3
6
3 to 1/0
3 to 1/0
3 to 1/0
6 to 1/0
6 to 4
1 to 325
2 to 350
3/0 to 600
3/0 to 600
4/0 to 600
3/0 to 600
1 to 350
Screw
Size
M8
M8
M8
M10
M10
M10
M10
M10
M12
M12
M10
M12
M12
Tightening Torque
N m (lb.in.)
9 to 11
(79.7 to 97.4)
9 to 11
(79.7 to 97.4)
9 to 11
(79.7 to 97.4)
18 to 23
(159 to 204)
18 to 23
(159 to 204)
18 to 23
(159 to 204)
18 to 23
(159 to 204)
32 to 40
(283 to 354)
18 to 23
(159 to 204)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
18 to 23
(159 to 204)
32 to 40
(283 to 354)
228 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 229 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
Model
CIMR-LU
4 0370
4 0450
4 0605
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
Recommended
Gauge
AWG, kcmil
300 × 2P
300 × 2P
–
–
1
3/0 × 4P
4/0 × 4P
–
–
1/0
300 × 4P
300 × 4P
–
–
2/0
Applicable Gauge
AWG, kcmil
4/0 to 300
4/0 to 300
3/0 to 300
3/0 to 300
1 to 3/0
3/0 to 300
3/0 to 300
1/0 to 300
1/0 to 300
1/0 to 300
4/0 to 300
4/0 to 300
1/0 to 300
1/0 to 300
2/0 to 300
Screw
Size
M12
M12
M12
Tightening Torque
N m (lb.in.)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
<1> Drive models CIMR-LU4 0045 to 4 0260 require the use of closed-loop crimp terminals for UL/cUL compliance. Use only the tools recommended by the terminal manufacturer for crimping.
<2> When an EMC filter is installed, take additional measures to comply with IEC/EN 61800-5-1. Refer to
EMC Filter Installation on page 220
for details.
Note: Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a continuous maximum allowable temperature of 7 5° C (167 ° F) 600 V UL approved vinyl sheathed insulation. Ambient temperature should not exceed
40 ° C (104 ° F).
Table 64 Wire Gauge and Torque Specifications (Three-Phase 600 V Class)
Model
CIMR-LU
5 0003
5 0004
5 0006
5 00010
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
Recomm. Gauge
AWG, kcmil
14
14
–
14
–
–
–
10
14
10
10
14
–
–
Wire Range
AWG, kcmil
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
12 to 10
14 to 6
14 to 6
14 to 6
14 to 10
Screw
Size
M4
M4
M4
Tightening Torque
N m (lb.in.)
1.2 to 1.5
(10.6 to 13.3)
1.2 to 1.5
(10.6 to 13.3)
2.1 to 2.3
(18.6 to 20.4)
8 12 to 8 M5
2.0 to 2.5
(17.7 to 22.1)
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
10
10
–
10 to 6
10 to 6
10 to 6 M5
3.6 to 4.0
(31.8 to 35.4)
5 0013
B1, B2 –
8
10 to 8
12 to 8 M6
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
(47.8 to 53.1)
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 229 C
TOEP_C710616_38H_7_0.book 230 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
Model
CIMR-LU
5 0017
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
5 0022
5 0027
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
B1, B2
5 0032
5 0041
5 0052
5 0062
5 0077
5 0099
5 0130
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
+3
Wire Range
AWG, kcmil
10 to 6
10 to 6
10 to 6
10 to 8
10 to 8
6 to 4
6 to 4
6 to 4
10 to 8
10 to 6
6 to 4/0
4
10 to 4/0
10 to 4/0
3 to 4/0
6 to 4/0
4
10 to 4/0
10 to 4/0
2 to 4/0
4 to 4/0
4
1 to 300
1 to 300
2/0 to 3/0
1 to 1/0
4 to 300
2/0 to 300
2/0 to 300
3/0 to 4/0
1/0 to 2/0
4 to 300
10 to 3
10 to 3
6 to 1
12 to 3
6
10 to 3
10 to 3
6 to 1
8 to 3
6
10 to 4/0
10 to 4/0
4 to 4/0
Recomm. Gauge
AWG, kcmil
8
10
–
–
8
6
6
–
–
6
2/0
2/0
–
–
3
–
4
1
–
3/0
3/0
–
–
3
–
4
3
–
1/0
–
4
3
4
–
6
4
6
–
–
–
6
4
6
6
–
Screw
Size
M5
M6
M6
M5
M6
Tightening Torque
N m (lb.in.)
3.6 to 4.0
(31.8 to 35.4)
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
(47.8 to 53.1)
5.4 to 6.0
(47.8 to 53.1)
2.7 to 3.0
(23.9 to 26.6)
5.4 to 6.0
(47.8 to 53.1)
M8
9 to 11
(79.7 to 97.4)
M8
M10
M10
M10
M10
M10
9 to 11
(79.7 to 97.4)
18 to 23
(159 to 204)
18 to 23
(159 to 204)
18 to 23
(159 to 204)
18 to 23
(159 to 204)
18 to 23
(159 to 204)
230 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 231 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
Model
CIMR-LU
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
Recomm. Gauge
AWG, kcmil
300
250
–
Wire Range
AWG, kcmil
2/0 to 600
2/0 to 600
2/0 to 400
Screw
Size
M12
Tightening Torque
N m (lb.in.)
32 to 40
(283 to 354)
5 0172
+3 –
1
2/0 to 250
1 to 350
M10
M12
18 to 23
(159 to 204)
32 to 40
(283 to 354)
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
400
350
–
2/0 to 600
2/0 to 600
2/0 to 500
M12
32 to 40
(283 to 354)
5 0200
+3 –
1
250 to 300
1 to 350
M10
M12
Closed-Loop Crimp Terminal Recommendations
Yaskawa recommends using closed-loop crimp terminals on all drive models. UL approval requires the use of UL Listed crimp terminals when wiring the drive main circuit terminals on Models CIMR- LU2 0085 to 2 0415, 4 0045 to
4 0605, and 5 0032 to 5 0200. Use only crimping tools as specified by the crimp terminal manufacturer. Yaskawa recommends crimp terminals made by JST and Tokyo DIP (or equivalent) for the insulation cap.
matches the wire gauges and terminal screw sizes with Yaskawa - recommended crimp terminals, tools, and insulation caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire gauge and screw size for your drive model. Place orders with a Yaskawa representatives the Yaskawa sales department.
Table 65 Closed-Loop Crimp Terminal Size
18 to 23
(159 to 204)
32 to 40
(283 to 354)
Wire Gauge
14 AWG
12 / 10 AWG
8 AWG
6 AWG
4 AWG
3/2/1 AWG
1/0 AWG
1/0 AWG × 2P
2/0 AWG
2/0 AWG × 2P
1 AWG × 2P
2 AWG × 2P
3/0 AWG
3/0 AWG × 2P
4/0 AWG
Terminal
Screws
M8
M6
M8
M8
M10
M8
M10
M5
M4
M5
M6
M4
M4
M5
M4
M10
M10
M10
M10
M12
M10
Crimp Terminal
Model Number
R2-4
R5.5-4
R5.5-5
8-4
R8-5
14-NK4
R14-5
R14-6
R14-8
R22-6
R22-8
R38-8
R38-10
R60-8
R60-10
70-10
38-L10
80-10
80-L10
80-L12
R100-10
Tool
Machine No.
YA-4
YA-4
YA-4
YA-4
YA-4
YA-4
Die Jaw
AD-900
AD-900
AD-900
AD-901
AD-901
AD-902
YA-4
YA-5
YA-5
YA-5
YA-5
AD-902
AD-952
AD-952
AD-953
AD-953
YA-5
YA-5
YA-5
AD-954
AD-954
AD-955
YF-1, YET-300-1 TD-321, TD-311
YF-1, YET-300-1 TD-323, TD-312
YF-1, YET-150-1 TD-224, TD-212
YF-1, YET-300-1 TD-323, TD-312
YF-1, YET-150-1 TD-227, TD-214
YF-1, YET-300-1 TD-323, TD-312
YF-1, YET-300-1
YF-1, YET-150-1
TD-324, TD-312
TD-228, TD-214
Insulation Cap
Model No.
TP-003
TP-005
TP-005
TP-008
TP-008
TP-014
TP-014
TP-014
TP-014
TP-022
TP-022
TP-038
TP-038
TP-060
TP-060
TP-080
TP-038
TP-080
TP-080
TP-080
TP-100
Code
100-054-028
100-054-029
100-054-030
100-054-031
100-054-032
100-054-033
100-054-034
100-051-261
100-054-035
100-051-262
100-051-263
100-051-264
100-061-114
100-051-265
100-051-266
100-054-036
100-051-556
100-051-267
100-051-557
100-051-558
100-051-269
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 231 C
TOEP_C710616_38H_7_0.book 232 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
Wire Gauge
4/0 AWG × 2P
250 / 300 kcmil
250 kcmil × 2P
300 kcmil × 2P
350 kcmil
400 kcmil
350 kcmil × 2P
400 kcmil × 2P
500 kcmil
600 / 650 kcmil
500 kcmil × 2P
600 kcmil × 2P
Terminal
Screws
M10
M12
M10
M12
M10
M12
M10
M10
M12
M12
M10
M12
Crimp Terminal
Model Number
100-L10
100-L12
R150-10
R150-12
150-L10
150-L12
180-10
200-10
180-L12
200-L12
325-10
325-12
Tool
Machine No.
Die Jaw
YF-1, YET-150-1 TD-228, TD-214
YF-1, YET-300-1
YF-1. YET-150-1
YF-1, YET-300-1
YF-1, YET-150-1
YF-1, YET-300-1
YF-1, YET-300-1
YF-1, YET-300-1
YF-1, YET-300-1
YF-1, YET-300-1
YF-1, YET-300-1
YF-1, YET-300-1
TD-324, TD-312
TD-229, TD-215
TD-325, TD-313
TD-229, TD-215
TD-325, TD-313
TD-326, TD-313
TD-327, TD-314
TD-326, TD-313
TD-327, TD-314
TD-328, TD-315
TD-328, TD-315
Insulation Cap
Model No.
TP-100
TP-100
TP-150
TP-150
TP-150
TP-150
TP-200
TP-200
TP-200
TP-200
TP-325
TP-325
Code
<1>
100-051-559
100-051-560
100-051-272
100-051-273
100-051-561
100-051-562
100-066-687
100-051-563
100-066-688
100-051-564
100-051-565
100-051-277
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the user should order two sets of [100-051-272].
Example 2: Models with 4/0 AWG × 2P for both input and output require two sets for input terminals and two sets for output terminals, so the user should order four sets of [100-051-560].
Note: Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable temperature of 75° C (167 ° F) 600 Vac UL-approved vinyl-sheathed insulation.
232 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 233 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
■
Installing Input Fuses
NOTICE: If a fuse is blown or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of the peripheral devices to identify the cause. Contact Yaskawa before restarting the drive or the peripheral devices if the cause cannot be identified.
Factory Recommended Branch Circuit Protection
Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with
UL508C. Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in
.
Table 66 Factory Recommended L1000A AC Drive Branch Circuit Protection
Drive Model
CIMR-LU
2 0415
4 0005
4 0006
4 0009
4 0015
4 0018
4 0024
4 0031
4 0039
4 0045
4 0060
4 0075
4 0091
4 0112
4 0150
4 0180
4 0216
4 0304
4 0370
2 0008
2 0011
2 0018
2 0025
2 0033
2 0047
2 0060
2 0075
2 0085
2 0115
2 0145
2 0180
2 0215
2 0283
2 0346
Nominal
Output Power
HP
3
3
5
7.5 - 10
10
15
20
25 - 30
30
40
60
60
75
100
125 - 150
150
250
300
25
30
40
50
60
75
100
125
7.5
10
15
20
2
3
5
150
L1000A in Heavy Duty Mode (C6-01 = 0)
AC Drive Input
Amps
MCCB Rating
Amps
Time Delay Fuse
Non-time Delay
Fuse Rating
Amps
Bussmann
Semiconductor
Fuse Rating
(Fuse
80
82
111
136
164
200
271
324
7.5
11
18.9
28
37
52
68
Three-Phase 200 V Class
15
20
35
50
60
100
125
150
150
200
250
300
400
500
600
394 700
12
17.5
30
40
60
90
110
125
125
175
225
250
350
450
500
600
20
30
50
75
100
150
200
225
225
250
350
450
600
800
900
FWH-70B (70)
FWH-70B (70)
FWH-90B(90)
FWH-100B (100)
FWH-200B (200)
FWH-200B (200)
FWH-200B (200)
FWH-300A (300)
FWH-300A (300)
FWH-350A (350)
FWH-400A (400)
FWH-400A (400)
FWH-600A (600)
FWH-700A (700)
FWH-800A (800)
FWH-1000A
(1000)
29
39
47
43
58
71
4.4
6
10.4
15
20
86
105
142
170
207
300
346
Three-Phase 400 V Class
15
15
20
30
40
50
75
75
75
100
125
150
175
225
250
350
500
600
7
10
17.5
25
35
50
60
75
75
100
110
150
175
225
250
350
500
600
12
17.5
30
40
60
80
110
125
125
150
200
250
300
400
500
600
800
FWH-70B (70)
FWH-70B (70)
FWH-90B (90)
FWH-80B (80)
FWH-100B (100)
FWH-125B (125)
FWH-200B (200)
FWH-250A (250)
FWH-250A (250)
FWH-250A (250)
FWH-250A (250)
FWH-250A (250)
FWH-350A (350)
FWH-400A (400)
FWH-500A (500)
FWH-600A (600)
FWH-800A (800)
FWH-800A (800)
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 233 C
TOEP_C710616_38H_7_0.book 234 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
L1000A in Heavy Duty Mode (C6-01 = 0)
Drive Model
CIMR-LU
4
4
0450
0605
Nominal
Output Power
HP
350
400 - 500
AC Drive Input
Amps
410
584
MCCB Rating
Amps
700
1000
<1>
Time Delay Fuse
Rating Amps
700
<2>
Non-time Delay
Fuse Rating
Amps
1200
1600
<3>
Bussmann
Semiconductor
Fuse Rating
(Fuse
Ampere)
<4>
FWH-1000A
(1000)
FWH-1200A
(1200)
5 0003
5 0004
5 0006
5 0010
5 0013
5 0017
5 0022
5 0027
5 0032
5 0041
5 0052
5 0062
5 0077
5 0099
5 0130
5 0172
5 0200
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
200
3.6
5.1
8.3
12
16
23
31
38
33
44
54
66
80
108
129
158
228
Three-Phase 600 V Class
15
15
15
20
30
40
60
75
60
75
100
125
150
175
250
300
400
6.25
8
12
20
25
40
50
60
50
75
90
110
125
175
225
250
350
10
15
20
35
45
60
90
100
90
125
150
175
225
300
350
400
600
FWP-50B (50)
FWP-60B (60)
FWP-60B (60)
FWP-70B (70)
FWP-100B (100)
FWP-100B (100)
FWP-125A (125)
FWP-125A (125)
FWP-175A (175)
FWP-175A (175)
FWP-250A (250)
FWP-250A (250)
FWP-250A (250)
FWP-350A (350)
FWP-350A (350)
FWP-600A (600)
FWP-600A (600)
<1> Maximum MCCB Rating is 15 A, or 200% of drive input current rating, whichever is larger. MCCB voltage rating must be 600 Vac or greater.
<2> Maximum Time Delay fuse is 175% of drive input current rating. This covers any Class CC, J or T class fuse.
<3> Maximum Non-time Delay fuse is 300% of drive input current rating. This covers any CC, J or T class fuse.
<4> Class L fuse is also approved for this rating.
Low Voltage Wiring for Control Circuit Terminals
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. If external power supply used, it shall be UL Listed Class 2 power source only or equivalent. Refer to NEC Article 725 Class 1,
Class 2, and Class 3 Remote-Control, Signaling, and Power Limited Circuits for requirements concerning class 1 circuit conductors and class 2 power supplies.
Table 67 Control Circuit Terminal Power Supply
Input / Output
Open Collector Outputs
Digital inputs
Analog inputs / outputs
Terminal Signal
P1, C1, P2, C2, DM+, DM-
S1-S8, SN, SC, SP, HC, H1, H2
+V, -V, A1, A2, AC, AM, FM
Power Supply Specifications
Requires class 2 power supply
Use the internal LVLC power supply of the drive. Use class 2 for external power supply.
Drive Short Circuit Rating
This drive is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes,
600 Vac maximum (Up to 240 V in 200 V class drives, up to 480 V for 400 V class drives), when protected by Bussmann
Type FWH fuses as specified in Table 59 .
234 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 235 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
■
CSA Standards Compliance
CSA for Industrial Control Equipment
The L1000 is CSA certified as Industrial Control Equipment Class 3211.
Specifically, the L1000 is certified to: CAN/CSA C22.2 No.04-04 and CAN/CSA C22.2 No.14-05.
Figure 97
Figure 106 CSA Mark
CSA for Elevator Equipment
The L1000 is tested and complies with CSA B44.1-04/ASME A17.5-2004 standard. This standard is used by CSA to evaluate the L1000 to Class 2411 (Elevator Equipment).
Figure 98
CSA B44.1 /
ASME A17.5
Figure 107 CSA B44.1-04/ASME A17.5-2004 Mark
■
Drive Motor Overload Protection
Set parameter E2-01/E5-03 (motor rated current) to the appropriate value to enable motor overload protection. The internal motor overload protection is UL Listed and in accordance with the NEC and CEC.
E2-01/E5-03: Motor Rated Current (IM Motor/PM Motor)
Setting Range: Model Dependent
Default Setting: Model Dependent
Parameter E2-01/E5-03 (motor rated current) protects the motor if parameter L1-01 is not set to 0 (default is 1, enabling protection for standard induction motors).
If Auto-Tuning has been performed successfully, the motor data entered to T1-04/T2-04 is automatically written into parameter E2-01/E5-03. If Auto-Tuning has not been performed, manually enter the correct motor rated current to parameter E2-01/E5-03.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 235 C
TOEP_C710616_38H_7_0.book 236 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
L1-01: Motor Overload Protection Selection
The drive has an electronic overload protection function (oL1) based on time, output current, and output speed, which protects the motor from overheating. The electronic thermal overload function is UL-recognized, so it does not require an external thermal relay for single motor operation.
This parameter selects the motor overload curve used according to the type of motor applied.
Table 68 Overload Protection Settings
Setting
0
1
2
3
5
6
Disabled
Standard fan-cooled motor (default)
Drive duty motor with a speed range of
1:10
Vector motor with a speed range of 1:100
Permanent Magnet motor with constant torque
Standard fan cooled motor (50 Hz)
Description
Disabled the internal motor overload protection of the drive.
Selects protection characteristics for a standard self cooled motor with limited cooling capabilities when running below the rated speed. The motor overload detection level (oL1) is automatically reduced when running below the motor rated speed.
Selects protection characteristics for a motor with self-cooling capability within a speed range of 10:1. The motor overload detection level (oL1) is automatically reduced when running below 1/10 of the motor rated speed.
Selects protection characteristics for a motor capable of cooling itself at any speed — including zero speed (externally cooled motor). The motor overload detection level (oL1) is constant over the entire speed range.
Selects protection characteristics for a constant torque PM motor. The motor overload detection level (oL1) is constant over the whole speed range.
Selects protection characteristics for a standard self cooled motor with limited cooling capabilities when running below the rated speed. The motor overload detection level (oL1) is automatically reduces when running below the motor rated speed.
When connecting the drive to more than one motor for simultaneous operation, disable the electronic overload protection
(L1-01 = 0) and wire each motor with its own motor thermal overload relay.
Enable the motor overload protection (L1-01 = 1 to 3, 5) when connecting the drive to a single motor, unless another motor overload preventing device is installed. The drive electronic thermal overload function causes an oL1 fault, which shuts off the output of the drive and prevents additional overheating of the motor. The motor temperature is continually calculated while the drive is powered up.
L1-02: Motor Overload Protection Time
Setting Range: 0.1 to 5.0 min
Factory Default: 1.0 min
Parameter L1-02 determines how long the motor is allowed to operate before the oL1 fault occurs when the drive is running at 60 Hz and at 150% of the full load amp rating (E2-01/E5-03) of the motor. Adjusting the value of L1-02 can shift the set of oL1 curves up the y axis of the diagram below, but will not change the shape of the curves.
Figure 99
Operation time (minutes)
10
7
3
1
Cold start
(Characteristics when an overload occurs at a complete stop)
0.4
0.1
0 100 150 200
Hot start
(Characteristics when an overload occurs during continuous operation at 100%)
Motor current (%)
E2-01 = 100% motor current
Figure 108 Protection Operation Time for General Purpose Motors at the Rated Output Frequency
236 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 237 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
L1-03 Motor Overload Alarm Operation Selection
Setting
0
1
2
3
Ramp to Stop
Coast to Stop
Fast-Stop
Alarm Only (default setting)
L1-04 Motor Overload Fault Operation Selection
Setting
0
1
2
Ramp to Stop
Coast to Stop (default setting)
Fast-Stop
Description
Description
◆
Safe Disable Input Function
This section explains the Safe Disable function and how to use it in an elevator installation. Contact Yaskawa if more information is required.
■
Safety Standards
The TUV mark indicates compliance with safety standards.
Figure 100
Figure 109 TUV mark
Standard Models (CIMR-L A )
Table 69 Safety Standards and Applicable Harmonized Standards for CIMR-L A
Safety Standards
Functional Safety
Safety of Machinery
EMC
Applicable Harmonized Standards
IEC/EN 61508 series (SIL2)
IEC/EN 61800-5-2 (SIL2)
ISO/EN ISO 13849-1/AC: 2009 (PL d (Cat.3))
EN 61800-3: 2004/A1: 2012
IEC 61800-3: 2004/A1: 2011
Models in Compliance with IEC/EN 61508 SIL3 (CIMR-L F )
Table 70 Safety Standards and Applicable Harmonized Standards for CIMR-L F
Safety Standards
Functional Safety
Safety of Machinery
EMC
Applicable Harmonized Standards
IEC/EN 61508 series: 2010 (SIL3)
IEC/EN 62061: 2005 (SILCL3)
IEC/EN 61800-5-2: 2007 (SIL3)
ISO/EN ISO 13849-1/AC: 2009 (PL e (Cat.3))
IEC/EN 61326-3-1: 2008 (EMC-related)
The Safe Disable function is in compliance with these standards.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 237 C
TOEP_C710616_38H_7_0.book 238 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
■
Specifications
The Safe Disable inputs provide a stop function in compliance with “Safe Torque Off” as defined in the IEC/EN
61800-5-2. Safe Disable inputs have been designed to meet the requirements of the ISO/EN 13849-1 and IEC/EN 61508.
A Safe Disable Status Monitor for error detection in the safety circuit is also provided.
Table 71 Specifications for Safe Disable Function
Inputs / Outputs
Response Time from Input Open to Drive Output
Stop
Response Time from Input Open of H1 and H2
Terminals to EDM
• Inputs: 2
Safe Disable inputs H1, H2
Signal ON level: 18 to 28 Vdc
Signal OFF level: -4 to 4 Vdc
• Outputs: 1
Safe Disable Monitor output EDM (DM+, DM-)
CIMR-L A : less than 1 ms
CIMR-L F : less than 3 ms
CIMR-L A : less than 1 ms
CIMR-L F : less than 4 ms
Failure Probability
Demand Rate Low
Demand Rate High or
Continuous
Performance Level
HFT (Hardware Fault Tolerance)
Classification of Subsystem
CIMR-L A : PFD = 5.15E
-5
CIMR-L F : PFD = 8.14E
-6
CIMR-L A : PFH = 1.2E
-9
CIMR-L F : PFH = 1.96E
-9
The Safe Disable inputs satisfy the following requirements (DC from EDM considered).
CIMR-L A : Performance Level (PL) d according to ISO/EN 13849-1
CIMR-L F : Performance Level (PL) e according to ISO/EN 13849-1
N = 1
Type B
<1> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN 61800-5-2, ISO/EN
13849 Cat.3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
■
Precautions
Note: Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN
61800-5-2, ISO/EN 13849 Cat. 3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
DANGER!
Sudden Movement Hazard. Improper use of the Safe Disable function will result in serious injury or death. Make sure the entire system or machinery uses the Safe Disable function in compliance with safety requirements. When implementing the Safe
Disable function into the safety system of a machine, a thorough risk assessment and validation for the whole system must be carried out to ensure it complies with relevant safety norms (e.g., ISO/EN 13849, IEC/EN 61508, IEC/EN 62061).
DANGER!
Sudden Movement Hazard. When using a PM motor, even if the drive output is shut off by the Safe Disable function, a break down of two output transistors can cause current to flow through the motor winding, resulting in a rotor movement for a maximum angle of 180 degrees (electrically). Ensure this condition will not affect the safety of the application when using the Safe Disable function. Failure to comply will result in death or serious injury.
DANGER!
Electrical Shock Hazard. The Safe Disable function can switch off the drive output, but does not cut the drive power supply and cannot electrically isolate the drive output from the input. Always shut off the drive power supply when performing maintenance or installations on the drive input side as well as the drive output side. Failure to comply will result in death or serious injury.
WARNING!
Sudden Movement Hazard. If the motor is subjected to an external force, use a mechanical brake that meets the safety requirements of entire system or machinery to stop the machine connected to the load. The motor will move when an external gravitational force in the vertical axis is applied even if the Safety Disable function is in operation. Failure to comply may result in serious injury or death.
WARNING!
Sudden Movement Hazard. Connect the Safe Disable inputs to the devices in compliance with safety requirements. Failure to comply will result in death or serious injury.
WARNING!
Sudden Movement Hazard. When using the Safe Disable inputs, make sure to remove the wire links between terminals
H1, H2, and HC that were installed prior to shipment. Failing to do so will keep the Safe Disable circuit from operating properly and can cause injury or even death.
WARNING!
All safety features (including Safe Disable) should be inspected daily and periodically. If the system is not operating normally, there is a risk of serious personal injury.
WARNING!
Only a qualified technician with a thorough understanding of the drive, the instruction manual, and safety standards should be permitted to wire, inspect, and maintain the Safe Disable input. Failure to comply may result in serious injury or death.
238 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 239 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
WARNING!
Sudden Movement Hazard. The logic of terminals DM+/DM- is inverted between drive models CIMR-L A and
CIMR-L F . Check all wiring to ensure that the sequence is correct after installing the drive and connecting any other devices.
Improper wiring connections could result in death or serious injury.
NOTICE: From the moment terminal inputs H1 and H2 have opened, it takes up to 1 ms for the drive output of models CIMR-L A to shut off completely, or up to 3 ms for the drive output of models CIMR-L F to shut off completely. The sequence set up to trigger terminals H1 and H2 should confirm that both terminals remain open for at least 1 ms in order to properly interrupt the drive output of models CIMR-L A , or for at least 3 ms in order to properly interrupt the drive output of models CIMR-L F . This may result in the Safe Disable Input not activating.
NOTICE: The Safe Disable Monitor (output terminals DM+ and DM-) should not be used for any other purpose than to monitor the Safe
Disable status or to discover a malfunction in the Safe Disable inputs. The monitor output is not considered a safe output.
NOTICE:
■
Using the Safe Disable Function
Note: Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN
61800-5-2, ISO/EN 13849 Cat. 3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
The Safe Disable inputs offer a stop function in compliance with “Safe Torque Off,” as defined in IEC/EN 61800-5-2.
Safe Disable inputs have been designed to meet the requirements in
A Safe Disable Status Monitor for error detection in the safety circuit is also provided.
Safe Disable Circuit
Note: Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN
61800-5-2, ISO/EN 13849 Cat.3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
The Safe Disable circuit consists of two independent input channels that can block the output transistors (terminals H1 and H2). The input can either use the drive internal power supply or an external power supply. Use jumper S3 on the terminal board to select between Sink or Source mode with either internal or external power supply.
A photocoupler output is available to monitor the status of the Safe Disable terminals DM+ and DM-.
for signal specifications when using this output.
Additionally a Safe Disable monitor function can be assigned to one of the digital outputs (H2 = 58).
Figure 101
Main Power
24 Vdc
Safety Relay or PLC with safety functionality
HC
Control
Circuit
Feedback
Safety
Outputs
H1
Jumper S3
Setting:
SOURCE
Gate Block 1
N
Power Module P
H2
DM+
DM-
Drive
>=1
Gate Block 2
Figure 110 Safe Disable Function Wiring Example (Source Mode)
M
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 239 C
TOEP_C710616_38H_7_0.book 240 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
Disabling and Enabling the Drive Output (“Safe Torque Off”)
Note: Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN
61800-5-2, ISO/EN 13849 Cat.3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
Figure 111 illustrates a Safe Disable input operation example.
Figure 102
Motor coasts to stop
Output
Frequency
Drive is ready for operation
Up/Down Command Run Stop
H1, H2 Input ON (Safe Disable off) OFF (Safe Disable activated)
Drive Output Normal operation Safe Torque-Off Baseblock (Not Safe!)
Figure 111 Safe Disable Operation
Entering the “Safe Torque Off” State
Note: Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN
61800-5-2, ISO/EN 13849 Cat.3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
Whenever either one Safe Disable input or both inputs open, the motor torque is shut off by switching off the drive output.
If the motor was running before the Safe Disable inputs opened, it will coast to stop, regardless of the stopping method set in parameter b1-03.
Notice that the “Safe Torque Off” state can only be achieved using the Safe Disable function. Removing the Up/Down command stops the drive and shuts the output off (baseblock), but does not create a “Safe Torque Off” status.
Note: To avoid an uncontrolled stop during normal operation, make sure that the Safe Disable inputs are opened first when the motor has completely stopped.
Returning to Normal Operation after Safe Disable
Note: Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN
61800-5-2, ISO/EN 13849 Cat.3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
The Safe Torque-Off state can be left by simply closing both Safe-Disable inputs.
If the Up/Down command is issued before the Safe-Disable inputs are closed, then the drive operation depends on the setting of parameter L8-88.
• If L8-88 is set to 0, the Up/Down command needs to be cycled in order to start the motor.
• If L8-88 is set to 1 (default), the drive will start the motor immediately when the Safe Torque-Off mode is left, i.e., the
Safe Disable inputs are enabled.
Additionally when L8-88 is set to 1, then parameter S6-16 (Restart after Baseblock Selection) can be used to determine how the drive behaves when the Safe-Disable inputs are opened and closed while the Up/Down command is kept active.
When S6-16 is set to 0, the drive will not restart (default) and the Up/Down command needs to be cycled. When S6-16 is set to 1, then the drive will restart as soon as the Safe-Disable inputs are closed.
240 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 241 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
Safe Disable Monitor Output Function and Digital Operator Display
Note: Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN
61800-5-2, ISO/EN 13849 Cat. 3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
The table below explains the drive output and Safe Disable monitor state depending on the Safe Disable inputs.
Table 72 Drive Output and Safe Disable Monitor State depending on the Safe Disable Inputs
Drive Model
Safe Disable Input
Input 1,
H1-HC
Input 2,
H2-HC
Safe Disable
Monitor,
EDM (DM+, DM-)
Safe Disable
Monitor,
H2 = 58
Drive Output
Digital Operator
Display
CIMR-L A
CIMR-L F
Off
On
Of f
On
Off
On
Of f
On
Off
Off
On
On
Off
Off
On
On
Off
On
On
On
On
Off
Off
Off
On
On
On
Off
On
On
On
Off
Safely disabled, “Safe Torque
Off”
Safely disabled, “Safe Torque
Off”
Safely disabled, “Safe Torque
Off”
Baseblock, ready for operation
Safely disabled, “Safe Torque
Off”
Safely disabled, “Safe Torque
Off”
Safely disabled, “Safe Torque
Off”
Baseblock, ready for operation
Hbb (flashes)
HbbF (flashes)
HbbF (flashes)
Normal display
Hbb (flashes)
HbbF (flashes)
HbbF (flashes)
Normal display
Safe Disable Status Monitor
Note: Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN
61800-5-2, ISO/EN 13849 Cat. 3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
With the Safe Disable monitor output (terminals DM+ and DM-), the drive provides a safety status feedback signal. This signal should be read by the device that controls the Safe Disable inputs (PLC or a safety relay) in order to prohibit leaving the “Safe Torque Off” status in case the safety circuit malfunctions. Refer to the instruction manual of the safety device for details on this function.
Digital Operator Display
Note: Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN
61800-5-2, ISO/EN 13849 Cat. 3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
In contrast to terminals DM+/DM-, the safe disable monitor function that can be programmed for a digital output
(H2 = 58) is a software function and can be used for EN81-1 conform one contactor solutions but not as an EDM signal according to IEC/EN 61800-5-2.
When both Safe Disable inputs are open, “Hbb” will flash in the digital operator display.
Should only one of the Safe Disable channels be on while the other is off, " HbbF " will flash in the display to indicate that there is a problem in the safety circuit or in the drive. This display should not appear under normal conditions if the Safe
possible errors.
If a fault in the safety circuit of the drive is detected, “SCF” will be displayed in the LCD operator. This indicates damage to the drive. Refer to
Fault Displays, Causes, and Possible Solutions on page 132 for details.
Validating Safe Disable Function
When you start-up, replace parts or conduct maintenance, you must always perform the following validation test on the safe disable inputs after completing the wiring. (Check results should be maintained as a record of tests performed.)
• When the H1 and H2 signals turn OFF, confirm that “Hbb” is displayed on the LCD operator, and that the motor is not in operation.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 241 C
TOEP_C710616_38H_7_0.book 242 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
If the ON/OFF status of the signals do not coincide with the display, the following must be considered: an error in the external device, disconnection of the external wiring, short circuit in the external wiring, or a failure in the drive. Find the cause and correct the problem.
• In normal operation, confirm the EDM signal by referring to Table 72 .
◆
EN81-1/20 Conform Circuit with one Motor Contactor
The safe disable circuit can be utilized to install the drive models CIMR-L in an elevator system using only one motor contactor instead of two. In such a system the following guidelines must be followed to comply with EN81-1 or
EN81-20:
• The circuit must be designed so that the inputs H1 and H2 are opened and the drive output shuts off when the safety chain is interrupted.
• A drive digital output must be programmed as Safe Disable feedback (H2 = 58). This feedback signal must be implemented in the contactor supervision circuit of the controller that prevents a restart in case of a fault in the Safe
Disable circuit or the motor contactor.
• All contactors and wiring must be selected and installed in compliance with EN81-1 or EN81-20.
• The safe disable inputs H1 and H2 must be used to enable/disable the drive. The input logic must be set to Source
The figure below shows a wiring example.
Safety Chain
Circuit
Elevator Controller
Contactor Close
Command
Contactor Check
(Restart Permission)
K01
24 Vdc
K1
Drive
Yaskawa
CIMR-L
H1 H2
Speed selection; ...
Safe Disable Monitor
(H2 = 58)
K2
242
M
Note: 1.
The drive output will immediately shut off when either of the inputs H1 or H2 is opened. In this case the brake should apply immediately in order to prevent uncontrolled movement of the elevator.
2.
Terminals H1 or H2 must be closed prior to setting the Up/Down command.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
TOEP_C710616_38H_7_0.book 243 ページ 2015年11月11日 水曜日 午後7時40分
C Standards Compliance
◆
EN81-20 Conform Circuit with No Motor Contactor
The safe disable circuit can be utilized to install the drive models CIMR-L F in an elevator system with no motor contactor. In such a system, the following guidelines must be followed to comply with EN81-20:
• The circuit must be designed so that the inputs H1 or H2 are opened and the drive output shuts off when the safety chain is interrupted.
• The safe disable inputs H1 and H2 must be used to enable/disable the drive. The input logic must be set to Source
Mode. Refer to Sinking/Sourcing Mode Selection for Safe Disable Inputs on page 55
for details on setting jumper S3.
The figure below shows a wiring example.
Safety Chain
Circuit
Elevator Controller
Drive Ready
Command Status Monitor
K01
24 Vdc
K1
K2
Drive
Yaskawa
CIMR-L F
H2 H1 HC Up/Down;
Speed selection; ...
Safe Disable Monitor
(H2 = 58)
M
Note: 1.
The drive output will immediately shut off when either of the inputs H1 or H2 is opened. In this case the brake should apply immediately in order to prevent uncontrolled movement of the elevator.
2.
Terminals H1 or H2 must be closed prior to setting the Up/Down command.
3.
A drive digital output must be programmed as Safe Disable feedback (H2 = 58). This feedback signal can be implemented in the contactor supervision circuit of the controller that monitors a fault in the Safe Disable circuit.
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 243 C
TOEP_C710616_38H_7_0.book 244 ページ 2015年11月11日 水曜日 午後7時40分
Revision History
The revision dates and the numbers of the revised manuals appear on the bottom of the back cover.
MANUAL NO. TOEP C710616 38B <1>
Published in Japan September 2010
Revision number
Date of publication
Date of
Publication
November 2015
June 2014
December 2013
August 2012
February 2012
March 2011
September 2010
March 2010
Revision
Number
<7>
<6>
<5>
<4>
<3>
<2>
<1>
−
Section Revised Content
Front cover Revision: Format
All Revision: Reviewed and corrected entire documentation.
Appendix C
Addition: EN81-20 conform circuit with no motor contactor
Revision: EN81-1/20 conform circuit with one motor contactor
Back cover Revision: Address, format
All Addition: Models CIMR-L F in compliance with IEC/EN 61508 SIL3 Safety
Integrity Level 3
Revision: Reviewed and corrected entire documentation
All Addition: Larger drive capacities added along with corresponding data
Three-phase 400 V: CIMR-LU4A0304 to 4A0605
Three-phase 600 V: CIMR-LU5A0003 to 5A0200
Revision: Review and corrected entire documentation.
Upgraded the software version to PRG: 7017 and PRG: S7200.
Back cover Revision: Address
All Addition: Smaller drive capacities added along with corresponding data
Three-phase 200 V: CIMR-LU2A0008 to 2A0014
Three-phase 400 V: CIMR-LU4A0005 to 4A0007
Back cover Revision: Address
All Revision: Reviewed and corrected entire documentation
Back cover Revision: Address
Front cover Revision: Format
Preface &
General
Safety,
Chapter 2 to
5, Appendix
B and C
Revision: Reviewed and corrected entire documentation
Chapter 7 Revision: Option card installation procedure
Back cover Revision: Address, format
All Revision: Reviewed and corrected entire documentation
Chapter 7 Addition: Option Card Installation
Back Cover Revision: Address
− First Edition
244 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
英文 No.5-5 (レター) YAI向けインバータ製品用 新ロゴ
YASKAWA AC Drive-L1000A
AC Drive for Elevator Applications
Quick Start Guide
YASKAWA AMERICA, INC.
2121, Norman Drive South, Waukegan, IL 60085, U.S.A.
Phone: 1-800-YASKAWA (927-5292) or 1-847-887-7000 Fax: 1-847-887-7310 http://www.yaskawa.com
DRIVE CENTER (INVERTER PLANT)
2-13-1, Nishimiyaichi, Yukuhashi, Fukuoka, 824-8511, Japan
Phone: 81-930-25-3844 Fax: 81-930-25-4369 http://www.yaskawa.co.jp
YASKAWA ELECTRIC CORPORATION
New Pier Takeshiba South Tower, 1-16-1, Kaigan, Minatoku, Tokyo, 105-6891, Japan
Phone: 81-3-5402-4502 Fax: 81-3-5402-4580 http://www.yaskawa.co.jp
YASKAWA ELÉTRICO DO BRASIL LTDA.
777, Avenida Piraporinha, Diadema, São Paulo, 09950-000, Brasil
Phone: 55-11-3585-1100 Fax: 55-11-3585-1187 http://www.yaskawa.com.br
YASKAWA EUROPE GmbH
185, Hauptstra β e, Eschborn, 65760, Germany
Phone: 49-6196-569-300 Fax: 49-6196-569-398 http://www.yaskawa.eu.com
YASKAWA ELECTRIC KOREA CORPORATION
9F, Kyobo Securities Bldg., 26-4, Yeouido-dong, Yeongdeungpo-gu, Seoul, 150-737, Korea
Phone: 82-2-784-7844 Fax: 82-2-784-8495 http://www.yaskawa.co.kr
YASKAWA ELECTRIC (SINGAPORE) PTE. LTD.
151, Lorong Chuan, #04-02A, New Tech Park, 556741, Singapore
Phone: 65-6282-3003 Fax: 65-6289-3003 http://www.yaskawa.com.sg
YASKAWA ELECTRIC (THAILAND) CO., LTD.
59, 1st-5th Floor, Flourish Building, Soi Ratchadapisek 18 , Ratchadapisek Road, Huaykwang, Bangkok, 10310, Thailand
Phone: 66-2-017-0099 Fax: 66-2-017-0799 http://www.yaskawa.co.th
YASKAWA ELECTRIC (CHINA) CO., LTD.
22F, One Corporate Avenue, No.222, Hubin Road, Shanghai, 200021, China
Phone: 86-21-5385-2200 Fax: 86-21-5385-3299 http://www.yaskawa.com.cn
YASKAWA ELECTRIC (CHINA) CO., LTD. BEIJING OFFICE
Room 1011, Tower W3 Oriental Plaza, No. 1, East Chang An Ave.,
Dong Cheng District, Beijing, 100738, China
Phone: 86-10-8518-4086 Fax: 86-10-8518-4082
YASKAWA ELECTRIC TAIWAN CORPORATION
9F, 16, Nanking E. Rd., Sec. 3, Taipei, 104, Taiwan
Phone: 886-2-2502-5003 Fax: 886-2-2505-1280
YASKAWA INDIA PRIVATE LIMITED
#17/A, Electronics City, Hosur Road, Bangalore, 560 100 (Karnataka), India
Phone: 91-80-4244-1900 Fax: 91-80-4244-1901 http://www.yaskawaindia.in
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations.
Therefore, be sure to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.
© 2010-2015 YASKAWA ELECTRIC CORPORATION