Series SGDH
PROFIBUS-DP INTERFACE UNIT
USER'S MANUAL
MODEL: JUSP-NS500
YASKAWA
YASKAWA
MANUAL NO. SIE-C718-8
Safety Information
Safety Information
The following conventions are used to indicate precautions in this manual. Failure to heed precautions provided in this manual can result in serious or possibly even fatal injury or damage to the products or to related equipment and systems.
!
WARNING
Indicates precautions that, if not heeded, could possibly result in loss of life or serious injury.
!
Caution Indicates precautions that, if not heeded, could result in relatively serious or minor injury, damage to the product, or faulty operation.
Yaskawa, 2001
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of
Yaskawa. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because
Yaskawa is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, Yaskawa assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
iii
Visual Aids
The following aids are used to indicate certain types of information for easier reference.
A
EXAMPLE
"
Indicates application examples.
INFO
Indicates supplemental information.
IMPORTANT
Indicates important information that should be memorized.
TERMS z
Explains difficult to understand terms and terms that have not been explained before.
iv
OVERVIEW
OVERVIEW
Safety Information
Visual Aids
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iii iv
TABLE OF CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 Checking Products and Part Names . . . . . . . . . . . .
1.1 Checking Products on Delivery
1.2 Product Part Names
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Mounting the NS500 Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 Storage Conditions
2.2 Installation Site
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Orientation
2.4 Installation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Connecting to Peripheral Devices . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 SERVOPACK Internal Block Diagrams . . . . . . . . . . . . . . . . . . . .
3.3 I/O Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 I/O Signal Connections for NS500 Units (CN4) . . . . . . . . . . . . . .
3.5 Connectors for PROFIBUS-DP Communications . . . . . . . . . . . .
4 Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Parameter Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Parameter Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 PROFIBUS-DP Communications . . . . . . . . . . . . . . . .
5.1 Specifications and Configuration . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 PROFIBUS-DP Communications Setting Switches . . . . . . . . . .
5.3 Command/Response Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4 Motion Command Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5 Commands from the Host Controller . . . . . . . . . . . . . . . . . . . . . . .
6 Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1 Parameters and Standard Settings for NS500 Units . . . . . . . . .
6.2 Settings According to Equipment Characteristics
6.3 Settings According to Host Controller
. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
6.4 Setting Up the SERVOPACK . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.5 Setting Stop Functions
6.6 Absolute Encoders
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.7 Digital Operator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 -1
3 -2
3 -6
3 -7
3 -12
3 -15
4 -1
4 -2
4 -4
4 -11
5 -1
5 -2
5 -3
5 -6
5 -27
5 -45
1 -1
1 -2
1 -4
1 -5 vii xi xii xiii
2 -1
2 -2
2 -2
2 -3
2 -4
6 -1
6 -3
6 -5
6 -10
6 -12
6 -16
6 -21
6 -24 v
7 Using the NSxxx Setup Tool . . . . . . . . . . . . . . . . . . . .
7.1 Connection and Installation
7.2 How to Use
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8 Ratings, Specifications, and Dimensions . . . . . . . .
8.1 Ratings and Specifications
8.2 Dimensional Drawings
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9 Error Diagnosis and Troubleshooting . . . . . . . . . . .
9.1 Troubleshooting with Alarm Displays . . . . . . . . . . . . . . . . . . . . . .
9.2 Troubleshooting Problems with No Alarm Display . . . . . . . . . . .
9.3 Alarm Display Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.4 Warning Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 -1
7 -2
7 -3
8 -1
8 -2
8 -4
9 -1
9 -2
9 -38
9 -40
9 -43
A Alarm and Warning Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A-1 vi
TABLE OF CONTENTS
TABLE OF CONTENTS
Safety Information
Visual Aids
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using This Manual
Safety Precautions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Product Part Names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iii iv xi xii xiii
1 Checking Products and Part Names . . . . . . . . . . . . . . . . . . . .
1 -1
1.1 Checking Products on Delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 -2
1 -4
1.3 Mounting the NS500 Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 -5
2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 -1
2.1 Storage Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 -2
2.2 Installation Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 -2
2.3 Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 -3
2 -4
3 Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 -1
3.1 Connecting to Peripheral Devices . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.1 Single-phase (100 V or 200 V) Main Circuit Specifications
3.1.2 Three-phase, 200-V Main Circuit Specifications
3.1.3 Three-phase, 400-V Main Circuit Specifications
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
3 -2
3 -3
3 -4
3 -5
3.2 SERVOPACK Internal Block Diagrams . . . . . . . . . . . . . . . . . . . . . . .
3 -6
3.3 I/O Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.1 Connection Example of I/O Signal Connector (CN1)
3.3.2 I/O Signals Connector (CN1)
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.3 I/O Signal Names and Functions
3.3.4 Interface Circuits
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 I/O Signal Connections for NS500 Units (CN4) . . . . . . . . . . . . . . . .
3.4.1 Connection Terminal Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.2 I/O Signal Interface Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.3 Fully-closed Encoder Connection Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5 Connectors for PROFIBUS-DP Communications . . . . . . . . . . . . . .
3 -7
3 -7
3 -8
3 -9
3 -10
3 -12
3 -12
3 -13
3 -14
3 -15 vii
4 Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 -1
4.1 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.1 Outline of Parameters
4.1.2 Parameter Types
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.3 Editing Parameters
4.1.4 Effective Timing
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Parameter Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.1 Unit Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.2 Zero Point Return Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.3 Machine System and Peripheral Device Parameters
4.2.4 Speed, Acceleration, and Deceleration Parameters
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
4.2.5 Positioning Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.6 Multi-speed Positioning Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.7 Notch Output Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Parameter Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3.1 Unit Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3.2 Zero Point Return Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3.3 Machine System and Peripheral Devices
4.3.4 Speed, Acceleration, and Deceleration
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3.5 Positioning Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3.6 Multi-speed Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3.7 Notch Signal Output Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 -2
4 -2
4 -2
4 -3
4 -3
4 -4
4 -4
4 -4
4 -5
4 -6
4 -8
4 -9
4 -10
4 -11
4 -11
4 -14
4 -19
4 -21
4 -33
4 -35
4 -36
5 PROFIBUS-DP Communications . . . . . . . . . . . . . . . . . . . . . . . .
5 -1
5.1 Specifications and Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.2 Control Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 PROFIBUS-DP Communications Setting Switches . . . . . . . . . . . .
5.2.1 Rotary Switch Settings for Setting Station Address
5.2.2 LED Indicators
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3 Command/Response Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.1 Command Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.2 General Command Bits and Status
5.3.3 Move command datas
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.4 Set/Read command datas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4 Motion Command Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.1 Constant Feed Command
5.4.2 Step Command
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.3 Station Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.4 Point Table Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.5 Zero Point Return Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.6 Positioning Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.7 External Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.8 Notch Output Positioning Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.9 Multi-speed Positioning Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 -2
5 -2
5 -2
5 -3
5 -3
5 -4
5 -6
5 -6
5 -7
5 -11
5 -20
5 -27
5 -27
5 -29
5 -31
5 -33
5 -34
5 -36
5 -38
5 -40
5 -41 viii
TABLE OF CONTENTS
5.5 Commands from the Host Controller . . . . . . . . . . . . . . . . . . . . . . . . .
5.5.1 Basic Sequence
5.5.2 Command Method
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 -45
5 -45
5 -46
6 Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 -1
6.1 Parameters and Standard Settings for NS500 Units . . . . . . . . . . .
6.1.1 Automatically Set Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.2 Standard Settings for CN1 I/O Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2 Settings According to Equipment Characteristics . . . . . . . . . . . .
6.2.1 Switching Servomotor Rotation Direction
6.2.2 Stop Mode Selection at Servo OFF
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2.3 Fully Closed Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2.4 Fully Closed System Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2.5 Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3 Settings According to Host Controller
6.3.1 Sequence I/O Signals
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4 Setting Up the SERVOPACK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4.1 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4.2 Input Circuit Signal Allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4.3 Output Circuit Signal Allocations
6.4.4 Analog Monitors
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.5 Setting Stop Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.5.1 Using the Dynamic Brake
6.5.2 Using the Holding Brake
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.6 Absolute Encoders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.6.1 Selecting an Absolute Encoder
6.6.2 Absolute Encoder Setup
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.6.3 Multiturn Limit Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.7 Digital Operator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.7.1 Connecting the Digital Operator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.7.2 Limitations in Using a Hand-held Digital Operator
6.7.3 Panel Operator Indicators
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 -3
6 -3
6 -4
6 -5
6 -5
6 -6
6 -7
6 -7
6 -8
6 -10
6 -10
6 -21
6 -21
6 -22
6 -22
6 -24
6 -24
6 -24
6 -24
6 -12
6 -12
6 -12
6 -13
6 -15
6 -16
6 -16
6 -17
7 Using the NSxxx Setup Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 -1
7.1 Connection and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1.1 Connecting the NS500 Unit
7.1.2 Installing the Software
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2 How to Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2.1 Screen Configuration at Startup
7.2.2 Functions Configuration
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 -2
7 -2
7 -2
7 -3
7 -3
7 -6 ix
8 Ratings, Specifications, and Dimensions . . . . . . . . . . . . . . . .
8 -1
8.1 Ratings and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8 -2
8.2 Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.2.1 NS500 Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8 -4
8 -4
9 Error Diagnosis and Troubleshooting . . . . . . . . . . . . . . . . . . .
9 -1
9.1 Troubleshooting with Alarm Displays . . . . . . . . . . . . . . . . . . . . . . . .
9 -2
9.2 Troubleshooting Problems with No Alarm Display . . . . . . . . . . . .
9 -38
9.3 Alarm Display Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9 -40
9.4 Warning Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9 -43
A Alarm and Warning Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.1 Alarm Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A-1
A-2
A.2 Warning Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A-4 x
Overview
Overview
J
About this Manual
This manual provides the following information for the Σ ΙΙ Series SGM j H/SGDH Servodrives with a JUSP-NS500 PROFIBUS-DP Interface Unit (hereafter called the NS500 Unit) mounted. The
NS500 Unit is an Option Unit.
D Procedures for installing and wiring the NS500 Unit
D Specifications and methods for SERVOPACK PROFIBUS-DP communications
D Procedures for setting parameters
D Information on the NSxxx Setup Tool
D Troubleshooting procedures
J
Related Manuals
Refer to the following manuals as required.
Read this manual carefully to ensure the proper use of Σ ΙΙ Series Servodrives. Also, keep this manual in a safe place so that it can be referred to whenever necessary.
Manual Name
Σ -II Series SGM j
H/SGDH
User’s Manual
Servo Selection and Data Sheets
Σ ΙΙ Series SGM j
H/SGDH
User’s Manual
Design and Maintenance
Manual Number
SIE-S800-32.1
SIE-S800-32.2
Contents
Describes the procedure used to select
Σ -II Series Servodrives and capacities.
Provides detailed information on SGDH
SERVOPACKs.
xi
Using This Manual
J
Intended Audience
This manual is intended for the following users.
D Those designing Servodrive systems using PROFIBUS-DP.
D Those designing Σ -II Series Servodrive systems.
D Those installing or wiring Σ -II Series Servodrives.
D Those performing trial operation or adjustments of Σ -II Series Servodrives.
D Those maintaining or inspecting Σ -II Series Servodrives.
J
Description of Technical Terms
In this manual, the following terms are defined as follows:
D NS500 Unit = JUSP-NS500
D Servomotor = Σ ΙΙ Series SGMAH, SGMPH, SGMGH, SGMSH, SGMDH, or SGMUH servomotor.
D SERVOPACK = Σ ΙΙ Series SGDHjjj E SERVOPACK.
D Servodrive = A set including a servomotor and Servo Amplifier.
D Servo System = A servo control system that includes the combination of a Servodrive with a host computer and peripheral devices.
J
Indication of Reverse Signals
In this manual, the names of reverse signals (ones that are valid when low) are written with a forward slash (/) before the signal name, as shown in the following examples:
D /S-ON
D /P-CON xii
Safety Precautions
Safety Precautions
The following precautions are for checking products upon delivery, installation, wiring, operation, maintenance and inspections.
J Checking Products upon Delivery
!
CAUTION
D
Always use the servomotor and SERVOPACK in one of the specified combinations.
Not doing so may cause fire or malfunction.
J
Installation
!
CAUTION
D
Never use the products in an environment subject to water, corrosive gases, inflammable gases, or combustibles.
Doing so may result in electric shock or fire.
J
Wiring
!
WARNING
D
Connect the SERVOPACK ground terminal effectively to a system grounding conductor or grounding electrode (100 Ω or less).
Improper grounding may result in electric shock or fire.
!
CAUTION
D
Do not connect a three-phase power supply to SERVOPACK U, V, or W output terminals.
Doing so may result in injury or fire.
D
Securely fasten the power supply terminal screws and motor output terminal screws.
Not doing so may result in fire.
xiii
J Operation
!
WARNING
D
Never touch any rotating motor parts while the motor is running.
Doing so may result in injury.
!
CAUTION
D
Conduct trial operation on the servomotor alone with the motor shaft disconnected from machine to avoid any unexpected accidents.
Not doing so may result in injury.
D
Before starting operation with a machine connected, change the settings to match the parameters of the machine.
Starting operation without matching the proper settings may cause the machine to run out of control or malfunction.
D
Before starting operation with a machine connected, make sure that an emergency stop can be applied at any time.
Not doing so may result in injury.
D
Do not touch the heat sinks during operation.
Doing so may result in burns due to high temperatures.
J Maintenance and Inspection
!
WARNING
D
Never touch the inside of the SERVOPACKs.
Doing so may result in electric shock.
D
Do not remove the panel cover while the power is ON.
Doing so may result in electric shock.
D
Do not touch terminals for five minutes after the power is turned OFF.
Residual voltage may cause electric shock.
!
CAUTION
D
Do not disassemble the servomotor.
Doing so may result in electric shock or injury.
D
Do not attempt to change wiring while the power is ON.
Doing so may result in electric shock or injury.
xiv
Safety Precautions
J General Precautions
Note the following to ensure safe application.
S The drawings presented in this manual are sometimes shown without covers or protective guards. Always replace the cover or protective guard as specified first, and then operate the products in accordance with the manual.
S The drawings presented in this manual are typical examples and may not match the product you received.
S This manual is subject to change due to product improvement, specification modification, and manual improvement. When this manual is revised, the manual code is updated and the new manual is published as a next edition. The edition number appears on the front and back covers.
S If the manual must be ordered due to loss or damage, inform your nearest Yaskawa representative or one of the offices listed on the back of this manual.
S Yaskawa will not take responsibility for the results of unauthorized modifications of this product. Yaskawa shall not be liable for any damages or troubles resulting from unauthorized modification.
xv
1
Checking Products and Part Names
1
This chapter describes the procedure for checking Σ -II Series products and the NS500 Unit upon delivery. It also describes the names of product parts.
1.1 Checking Products on Delivery
1.2 Product Part Names
. . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
1.3 Mounting the NS500 Unit . . . . . . . . . . . . . . .
1 -2
1 -4
1 -5
1 -1
1
Checking Products and Part Names
1.1 Checking Products on Delivery
The following procedure is used to check products upon delivery. Check the following items when products are delivered.
Check Items
Are the delivered products the ones that were ordered?
Is there any damage?
Can the NS500 Unit be installed on the SERVOPACK used?
Comments
Check the model numbers marked on the nameplates of the NS500 Unit. (Refer to the descriptions of model numbers on following pages)
Check the overall appearance, and check for damage or scratches that may have occurred during shipping.
Check the model number given on the SERVOPACK nameplate. The model number must contain “SGDH” and “E” as shown below to support the NS500 Unit.
SGDHjjj Ej
If any of the above items are faulty or incorrect, contact your Yaskawa sales representative or the dealer from whom you purchased the products.
J
External Appearance and Nameplate Example
Option unit type
Option unit name
SERVOPACK
PROFIBUS-DP I/F UNIT
MODEL JUSP-NS500 VER.
000000
S/N V81003-69
YASKAWA ELECTRIC
MADE IN JAPAN
Serial number
Version number
NS500 Unit
1 -2
1.1 Checking Products on Delivery
J
Model Number
NS500 Unit
JUSP
−
NS50 0
SERVOPACK Peripheral Device
Type of device:
NS50: PROFIBUS-DP Interface Unit
Design Revision Order
1
1 -3
1
Checking Products and Part Names
1.2 Product Part Names
The following diagram illustrates the part names of the NS500 Unit.
Ground wire: Connected to the terminal marked “G” on the SGDH SERVOPACK.
Rotary switches (X1, X10):
Used to set the PROFIBUS-DP station address.
RS-232C Communications Connector (CN11):
Used to communicate with the Setup Tool.
LED (COMM): Communication Status LED for PROFIBUS-DP
LED (ERR): Module Error Status LED
PROFIBUS-DP Communications Connector (CN6):
Connector for PROFIBUS-DP Communications.
External I/O Connector (CN4):
Connector for external I/O signals and fully closed encoder signals.
Figure 1.1
NS500 Unit
1 -4
1.3 Mounting the NS500 Unit
1.3 Mounting the NS500 Unit
This section describes how to mount a NS500 Unit on the SGDH SERVOPACK.
Prepare the screws for connecting the ground wire as shown in the following table:
Mounting Type SERVOPACK Models Screw Remarks
Base Mounted SGDH-A3 to 02BE
SGDH-A3 to 10AE
SGDH-15 to 50AE
SGDH-05 to 30DE
SGDH-60/75AE
M3 × 10 round-head screw
(spring or flat washer)
M4 × 10 round-head screws
(spring or flat washer)
M4 × 8 round-head screw
(spring or flat washer)
M4 × 6 round-head screws
(spring or flat washer)
Attachments
Attachments
Use front panel fixer screws
Attachments Rack Mounted SGDH-A3 to 02BE-R
SGDH-A3 to 50AE-R
SGDH-05 to 30DE-R
SGDH-60/75AE-P Duct Vent M4 × 8 round-head screw
(spring or flat washer)
Use front panel fixer screws
Note: Be sure to use spring washers or flat washers. Failure to do so may result in the screws for connecting the ground wire protruding behind the flange, preventing the SERVOPACK from being mounted.
By mounting NS500 Unit, the SGDH SERVOPACK can be used in a DeviceNet network. Use the following procedure to ensure NS500 Units are mounted correctly.
1.
Remove the connector cover from the CN10 connector on the SERVOPACK.
1
CN10
YASKAWA
SGDH-
SERVOPACK
Connector cover
MODE/SET
CHARGE
DATA /
POWER
1 -5
1
Checking Products and Part Names
2.
Mount the NS500 Unit on the SERVOPACK.
CN10
Connector (for connection to
SERVOPACK)
YASKAWA SERVOPACK
SGDH-
Ver.
U
V
W
L1C
L2C
B1
B2
CHARGE POWER
L1
L2
1
2
N S500
8
3.
For grounding, connect a ground wire of the NS500 Unit to the point marked “G” on the
SERVOPACK.
Ground wire
“
G
”
YASKAWA
SGDH-
SERVOPACK
NS500
MODE/SET
CHARGE
DATA/
POWER
For SERVOPACK 30 W to 5.0 kW
“
G
”
YASKAWA
SGDH -
SERVOPACK 200V
NS100
For SERVOPACK 6.0 kW to 7.5 kW
1 -6
Ground wire
1.3 Mounting the NS500 Unit
When the NS500 Unit has been mounted correctly, the SERVOPACK will appear as shown in the following diagram.
1
1 -7
2
Installation
2
This chapter describes precautions for Σ -II Series product installation.
The SGDH SERVOPACKs are base-mounted servo amplifiers. Incorrect installation will cause problems. Always observe the installation precautions shown in this chapter.
2.1 Storage Conditions
2.2 Installation Site
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
2.3 Orientation
2.4 Installation
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 -2
2 -2
2 -3
2 -4
2 -1
2
Installation
2.1 Storage Conditions
Store the SERVOPACK within the following temperature range when it is stored with the power cable disconnected.
Temperature range: − 20 to 85 ° C
Σ -II Series SGDH SERVOPACK with NS500 Unit mounted
2.2 Installation Site
Take the following precautions at the installation site.
Situation
Installation in a Control
Panel
Installation Near a
Heating Unit
Installation Near a
Source of Vibration
Installation at a Site
Exposed to Corrosive
Gas
Other Situations
Installation Precaution
Design the control panel size, unit layout, and cooling method so that the temperature around the SERVOPACK does not exceed 55 ° C.
Minimize heat radiated from the heating unit as well as any temperature rise caused by natural convection so that the temperature around the SERVOPACK does not exceed 55 ° C.
Install a vibration isolator beneath the SERVOPACK to avoid subjecting it to vibration.
Corrosive gas does not have an immediate effect on the SERVO-
PACK, but will eventually cause electronic components and contactor-related devices to malfunction. Take appropriate action to avoid corrosive gas.
Do not install the SERVOPACK in hot or humid locations, or locations subject to excessive dust or iron powder in the air.
2 -2
2.3 Orientation
2.3 Orientation
Install the SERVOPACK perpendicular to the wall as shown in the figure. The SERVOPACK must be oriented this way because it is designed to be cooled by natural convection or cooling fan.
Secure the SERVOPACK using 2 to 4 mounting holes. The number of holes depends on the SER-
VOPACK capacity.
2
Wall
MADE IN JAPAN
Ventilation
2 -3
2
Installation
2.4 Installation
Follow the procedure below to install multiple SERVOPACKs side by side in a control panel.
FAN FAN
50mm (2in.) or more
NS500 NS500 NS500 NS500
10mm (0.4in.) or more
50mm (2in.) or more
30mm (1.2in.) or more
J
SERVOPACK Orientation
Install the SERVOPACK perpendicular to the wall so that the front panel (containing connectors) faces outward.
J
Cooling
As shown in the figure above, provide sufficient space around each SERVOPACK for cooling by cooling fans or natural convection.
J
Side-by-side Installation
When installing SERVOPACKs side by side as shown in the figure above, provide at least 10 mm
(0.39 in) between and at least 50 mm (1.97 in) above and below each SERVOPACK. Install cooling fans above the SERVOPACKs to avoid excessive temperature rise and to maintain even temperature inside the control panel.
J
Environmental Conditions in the Control Panel
D Ambient Temperature:
D Humidity:
D Vibration:
0 to 55 ° C
90% or less
4.9 m/s 2
D Condensation and Freezing: None
D Ambient Temperature for Long-term Reliability: 45 ° C max.
2 -4
3
Connectors
This chapter describes the procedure used to connect Σ -II Series products to peripheral devices when NS500 Unit is mounted and gives typical examples of I/O signal connections.
3.1 Connecting to Peripheral Devices . . . . . . .
3.1.1 Single-phase (100 V or 200 V)
Main Circuit Specifications . . . . . . . . . . . . . . . . . . .
3.1.2 Three-phase, 200-V Main Circuit Specifications . .
3.1.3 Three-phase, 400-V Main Circuit Specifications
3.2 SERVOPACK Internal Block Diagrams . . .
. .
3.3 I/O Signals . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.1 Connection Example of I/O Signal Connector (CN1) . . . . . . . . . . . . . . . .
3.3.2 I/O Signals Connector (CN1) . . . . . . . . . . . . . . . . . .
3.3.3 I/O Signal Names and Functions . . . . . . . . . . . . . .
3.3.4 Interface Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 I/O Signal Connections for NS500 Units (CN4) . . . . . . . . . . . . . . . .
3.4.1 Connection Terminal Layout
3.4.2 I/O Signal Interface Circuits
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
3.4.3 Fully-closed Encoder Connection Example . . . . . .
3.5 Connectors for PROFIBUS-DP
Communications . . . . . . . . . . . . . . . . . . . . . .
3 -12
3 -12
3 -13
3 -14
3 -15
3 -2
3 -3
3 -4
3 -5
3 -6
3 -7
3 -7
3 -8
3 -9
3 -10
3
3 -1
3
Connectors
3.1 Connecting to Peripheral Devices
This section provides examples of standard Σ -II Series product connections to peripheral devices.
It also briefly explains how to connect each peripheral device.
3 -2
3.1 Connecting to Peripheral Devices
3.1.1 Single-phase (100 V or 200 V) Main Circuit Specifications
Host Controller
Can be connected to PROFIBUS-DP Master.
Molded-case Circuit
Breaker (MCCB)
Protects the power line by shutting the circuit OFF when overcurrent is detected.
Molded-case circuit breaker
Power supply
Single-phase 200 VAC
R S T
Noise Filter
Used to eliminate external noise from the power line.
Personal Computer (See note.)
Noise filter
Magnetic Contactor
HI Series
Turns the servo
ON and OFF.
Install a surge suppressor on the magnetic contactor.
Magnetic contactor
Power Supply for Brake
Used for a servomotor with a brake.
Brake power supply
Magnetic contactor
Power supply ground line
U V W
L1 L2 L1C L2C
B1 B2
Cable model: JZSP-CMS01 to 03
Digital Operator
JUSP-OP02A-2
Allows the user to set parameters or operation references and to display operation or alarm status.
Encoder
Cable
Encoder
Connector
3
Regenerative Resistor
Connect an external regenerative resistor to terminals B1 and B2 if the regenerative capacity is insufficient.
3 -3
Regenerative resistor
(option)
Note Used for maintenance. Be sure to coordinate operation from these devices with controls exerted by the host controller.
3
Connectors
3.1.2 Three-phase, 200-V Main Circuit Specifications
3.1.2 Three-phase, 200-V Main Circuit Specifications
Host Controller
Can be connected to PROFIBUS-DP Master.
Molded-case Circuit
Breaker (MCCB)
Protects the power line by shutting the circuit OFF when overcurrent is detected.
Molded-case circuit breaker
Power supply
Three-phase 200 VAC
R S T
Personal Computer (See note.)
Noise Filter
Used to eliminate external noise from the power line.
Magnetic Contactor
HI Series
Turns the servo
ON and OFF.
Install a surge suppressor on the magnetic contactor.
Noise filter
Cable model: JZSP-CMS01 to 03
Digital Operator
JUSP-OP02A-2
Allows the user to set parameters or operation references and to display operation or alarm status.
Encoder
Cable
Encoder
Connector
Magnetic contactor
Brake power supply
Magnetic contactor Power supply ground line
U V W
L1 L2 L3
L1C L2C
B1 B2
Regenerative resistor
(option) Power Supply for Brake
Used for a servomotor with a brake.
Regenerative Resistor
If the capacity of the internal regenerative resistor is insufficient, remove the wire between terminals B2 and B3 and connect an external regenerative resistor to terminals B1 and B2.
Note Used for maintenance. Be sure to coordinate operation from these devices with controls exerted by the host controller.
3 -4
3.1 Connecting to Peripheral Devices
3.1.3 Three-phase, 400-V Main Circuit Specifications
Brake Power Supply
100-VAC or 200-VAC power supply.
24-VDC power supply for servomotors with 24-VDC brakes.
Host Controller
Can be connected to PROFIBUS-DP Master.
Molded-case Circuit
Breaker (MCCB)
Protects the power line by shutting the circuit OFF when overcurrent is detected.
Power supply
Three-phase 400 VAC
R S T
Personal Computer (See note.)
Moldedcase circuit breaker
Noise Filter
Used to eliminate external noise from the power line.
Cable model: JZSP-CMS01 to 03
Digital Operator
JUSP-OP02A-2
Allows the user to set parameters or operation references and to display operation or alarm status.
Noise filter
Magnetic Contactor
HI Series
Turns the servo
ON and OFF.
Install a surge suppressor on the magnetic contactor.
Magnetic contactor
Power Supply for Brake
Used for a servomotor with a brake.
Brake power supply
Magnetic contactor
Power supply ground line
U V W
L1 L2 L3
24V 0V
B1 B2
Encoder
Cable
Encoder
Connector
DC power supply
(24V)
Regenerative resistor
(option)
Regenerative Resistor
If the capacity of the internal regenerative resistor is insufficient, remove the wire between terminals B2 and
B3 and connect an external regenerative resistor to terminals B1 and
B2.
Note Used for maintenance. Be sure to coordinate operation from these devices with controls exerted by the host controller.
3 -5
3
3
Connectors
3.2 SERVOPACK Internal Block Diagrams
The following sections show an internal block diagram for the SERVOPACK with the NS500 Unit.
30 to 400 W 200-V and 30 to 200 W 100-V Models
Single-phase
200 to 230 V
(50/60Hz)
+10 %
− 15%
1
2
Noise filter
1MC
L1
L2
FU1
PM1-1
P1
R
T
N1
Voltage sensor
RY1
B1 B2
CHARGE
D1
C1
+
−
TR1
Relay drive
Voltage sensor
Gate drive
P2
N2
Gate drive overcurrent protector
PM1-2
U
V
W
Interface
R7
R8
THS1
D2D3D4
U
V
W
AC servomotor
CN2
PG
L1C
L2C
Power
OFF
Power
ON
1MC
1MC Surge suppressor
(5Ry)
Open during servo alam
~
+
~
−
Master node
CN6
+
−
DC/DC converter
Monitor display
Analog voltage converter
CN5
Monitor output for supervision
± 5V
+15V
+5V
± 12V
+5V
ASIC
(PWM control)
0V
POWER
CN3
Digital Operator/ personal computer
CPU
(position and speed calculation)
Current sensor
CN8
For battery connection
CN1
I/O
CN10
Sequence I/O
CN10
PROFIBUS-DP communications interface
Bus interface
CN4
Fully-closed PG
+5V
R
+5V
A
CPU
(position commands, command interpretation, arithmetic processing, etc.)
SW1, SW2
Station No.
SW3
Baud rate
Power supply
3 -6
3.3 I/O Signals
3.3 I/O Signals
This section describes I/O signals for the SERVOPACK with the NS500 Unit.
3.3.1 Connection Example of I/O Signal Connector (CN1)
The following diagram shows a typical example of I/O signal connections.
BAT+
BAT −
21
22
SGDH SERVOPACK
CN1
Backup battery
2.8 to 4.5 V *2
+
−
37
38
39
1
ALO1
ALO2
ALO3
SG
Alarm code output
Maximum operating voltage: 30 VDC
Maximum operating current: 20 mA DC
Not used +24VIN 47
3.3K
Ω
Zero point return deceleration LS
(LS enabled when ON)
Forward run prohibited
(Prohibited when OFF)
Reverse run prohibited
(Prohibited when OFF)
External positioning signal
Zero point signal
Not used
+24V
+
−
/DEC
40
41
25
26
/COIN+
/COIN −
Positioning completed
(ON when positioning has been completed)
P-OT 42
N-OT
EXTP
ZERO
43
44
45
46
27
28
29
30
31
32
Connector shell
FG
Connect the shield wire to connector shell.
* 1.
represents twisted-pair wires.
* 2. When using an absolute encoder, connect a backup battery only when there is no battery connected to the CN8.
* 3. Make signal allocations using parameters. (Refer to 6.1.2 Standard Settings for
CN1 I/O Signals .)
/BK+
/BK −
Brake output *3
(ON when brake released)
/S-RDY+
/S-RDY −
Servo ready output
(ON when ready)
ALM+
ALM −
Servo alarm output
(OFF for an alarm)
Photocoupler output
Maximum operating voltage: 30 VDC
Maximum operating current: 50 mA DC
Figure 3.1
I/O Signal Connections for CN1 Connectors
3 -7
3
3
Connectors
3.3.2
I/O Signal s Connector (CN1)
3.3.2 I/O Signals Connector (CN1)
The following diagram shows the layout of CN1 terminals.
J
CN1 Terminal Layout
16
−
−
−
−
11
−
−
−
−
−
−
−
−
−
−
/BK+
(Note 3)
Brake interlock output output output
Alarm code tor output)
41 /DEC turn deceleration LS input
Reverse run input signal
External
47 +24VIN power supply input
49 − −
46
Positioning
26 /COIN − complete output
/BK −
(Note 3) lock output
30 /S RDY −
32 ALM
−
− output
Servo alarm output
−
36 − −
Alarm code output
− −
−
−
Forward drive input tioning signal
−
−
− −
22 BAT ( ) ) Battery ( ) )
24 − −
21 BAT (+) Battery (+)
− −
Positioning
25 /COIN + l output
Note 1. Do not use unused terminals for relays.
2.
Connect the shield of the I/O signal cable to the connector shell.
The shield is connected to the FG (frame ground) at the SERVOPACK-end connector.
3.
Make signal allocations using parameters. (Refer to 6.1.2 Standard Settings for CN1 I/O Signals.)
J
CN1 Specifications
Specifications for
Connectors
10250-52A2JL 50-p
Right Angle Plug
Soldered
10150-3000VE
Applicable Receptacles
Case
10350-52A0-008
Manufacturer
Sumitomo 3M Ltd.
3 -8
3.3 I/O Signals
3.3.3 I/O Signal Names and Functions
The following section describes SERVOPACK I/O signal names and functions.
Signal Name
Common /DEC
P-OT
N-OT
EXTP
ZERO
+24VIN
BAT (+)
BAT ( − )
J
Input Signals
Pin No.
41
42
43
44
45
47
21
22
Function
Zero point return deceleration NS:
Deceleration LS for zero point return connected.
Forward run prohibited
Reverse run prohibited
Overtravel prohibited: Stops servomotor when movable part travels beyond the allowable range of motion.
External positioning signal:
Signal used for external positioning connected.
Zero point
Control power supply input for sequence signals: Users must provide the +24-V power supply.
Allowable voltage fluctuation range: 11 to 25 V
Connecting pin for the absolute encoder backup battery.
Connect to either CN8 or CN1.
J
Output Signals
Signal Name
Common ALM+
Position
ALM
/BK+
/BK −
−
/S-RDY+
/S-RDY
ALO1
ALO2
ALO3
FG
/COIN+
/COIN −
−
Pin No.
Function
31
32
27
28
Servo alarm: Turns OFF when an error is detected.
Brake interlock: Output that controls the brake. The brake is released when this signal is ON.
29
30
37
38
39 (1)
Servo ready: Turns ON if there is no servo alarm when the control/main circuit power supply is turned ON.
Alarm code output: Outputs 3-bit alarm codes.
Open-collector: 30 V and 20 mA rating maximum
Shell Connected to frame ground if the shield wire of the I/O signal cable is connected to the connector shell.
25
26
Positioning completed (output in Position Control Mode): Turns ON when the number of error pulses reaches the set value. The setting is the number of error pulses set in reference units (input pulse units defined by the electronic gear).
Note 1. Pin numbers in parenthesis () indicate signal grounds.
2.
The functions allocated to /BK, /S-RDY, and /COIN can be changed via parameters. The /BK, /S-RDY, and /COIN output signals can be changed to /CLT, /VLT, /TGON, /WARN, or /NEAR signals.
3
3 -9
3
Connectors
3.3.4 Interface Circuits
3.3.4 Interface Circuits
The following diagram shows an example of connections between a host controller and the I/O signal for a SERVOPACK.
J
Sequence Input Circuit Interface
The sequence input circuit interface connects through a relay or open-collector transistor circuit.
Select a low-current relay, otherwise a faulty contact will result.
SERVOPACK SERVOPACK
24 VDC
50 mA min.
24 VDC
50 mA min.
+24VIN
3.3k
Ω
/DEC,etc.
+24VIN
3.3k
Ω
/DEC,etc.
J
Sequence Output Circuit Interface
Any of the following two types of SERVOPACK output circuits can be used. Form an input circuit at the host controller that matches one of these types.
D Connecting to an Open-collector Output Circuit
Alarm code signals are output from open-collector transistor output circuits.
Connect an open-collector output circuit through a photocoupler, relay, or line receiver circuit.
5 to 12 VDC photocoupler
5 to 24 VDC
Relay
SERVOPACK end
SERVOPACK end
0V 0V
0V
0V
5 to 12 VDC
SERVOPACK end
0V
0V
Note The maximum allowable voltage and current capacities for open-collector output circuits are as follows:
· Voltage: 30 VDC max.
· Current: 20 mA DC max.
3 -10
3.3 I/O Signals
D Connecting to a Photocoupler Output Circuit
Photocoupler output circuits are used for servo alarm, servo ready, and other sequence output signal circuits.
Connect a photocoupler output circuit through a relay or line receiver circuit.
5 to 24 VDC
Relay 5 to 12 VDC
SERVOPACK end
SERVOPACK end
0V
0V
0V
0V
Note The maximum allowable voltage and current capacities for photocoupler output circuits are as follows:
· Voltage: 30 VDC max.
· Current: 50 mA DC max.
3
3 -11
3
Connectors
3.4.1 Connection Terminal Layout
3.4
I/O Signal Connections for
NS500
Units
(CN4)
The CN4 on an NS500 Unit is used for I/O signal and fully-closed encoder signal connections.
3.4.1
Connection Terminal Layout
The terminal layout and specifications for the CN4 are outlined below.
J
CN4 Terminal Layout
Pin No.
1
Signal
PG 0V
Description
Signal ground
Pin No.
11
Signal
+24VIN
6
7
8
9
10
2
3
4
5
PG 0V
PG 0V
−
−
−
−
−
EMSTOP
NOTCH2+
−
−
−
Signal ground
Signal ground
−
−
Emergency stop input
Notch output 2
12
13
14
15
16
17
18
19
20
Note 1. The PG power supply and battery must be supplied externally.
2. The FG is connected to the connector shell.
NOTCH1+
NOTCH1 −
PC
/PC
PA
/PA
PB
/PB
NOTCH2 −
J
Connector Specifications
Part
Connector
Connector shell
Signal
10120-3000VE (20P)
10320-52A0-008
Manufacturer
Sumitomo 3M Ltd.
−
Description
24-V common terminal for external input
Notch output 1
−
Phase-C input
−
Phase-A input
−
Phase-B input
−
Notch output 2
3 -12
3.
4 I/O Signal Connections for NS500 Units (CN4)
3.4.2
I/O Signal Interface Circuits
The following diagram shows an example of connections between a host controller and the I/O signals for an NS500 Unit.
J
Sequence I/O Circuit Interface
The sequence input circuit interface connects through a relay or open-collector transistor circuit.
Select a low-current relay, otherwise a faulty contact will result.
NS500
24 VDC
50 mA min.
+24VIN
3.3k
Ω
EMSTOP
NS500
24 VDC
50 mA min.
+24VIN 3.3k
Ω
EMSTOP 3
Relay Open Collector
J
Sequence Output Circuit Interface
Notch output signals are used for photocoupler output circuits. Connect the notch output signals to relays or line receiver circuits.
5 to 12 VDC
5 to 24 VDC
Relay
NS500 end
NS500 end
0V
0V
0V 0V
Relay Line Receiver
Note The maximum allowable voltage and current capacity for photocoupler output circuits are as follows :
⋅ Voltage: 30 VDC max.
⋅ Current: 50 mA DC max.
3 -13
3
Connectors
3.4.3 Fully − closed Encoder Connection Example
3.4.3
Fully-closed Encoder Connection Example
The following diagram shows a connection example for a fully-closed encoder.
External PG
NS500
PG0V
PA
/PA
PB
/PB
PC
/PC
19
14
15
CN4
1,2,3
16
17
18
/B
Z
/Z
/A
B
GND
A
External power supply
: Shield.
3 -14
3.
5 Connectors for PROFIBUS-DP Communications
3.5 Connectors for PROFIBUS-DP Communications
SUB-D 9-pin connectors are used for PROFIBUS-DP connections.
Pin number
1
2
3
6
7
4
5
8
9
Symbol
−
−
RXD/TXD-P
−
DGND
VP
−
RXD/TXD-N
−
Function
−
−
Receive/send data, positive
−
Ground
+5 V
−
Receive/send data, negative
−
Baud rate
(kbps)
9.6
Maximum cable length
(m)
1200
J
Cables for PROFIBUS-DP Communications
Use commercial PROFIBUS-DP cables. Type A cables are recommended. The maximum cable lengths when using type A cables are given in the table below.
19.2
93.75
187.5
500 1500 1200
1200 1200 1000 400 200 100
The specifications for type A cables are given in the table below.
Specifications Item
Impedance
Capacitance per Unit
Loop resistance
Core diameter
Core cross-sectional area
135 to 165 Ω
< 30 pF/m
110 Ω /m
0.64 mm
> 0.34 mm 2
3
3 -15
3
Connectors
Terminating resistances are required at both ends of the bus line as shown below.
VP (6)
Data line
Data line
390 Ω
RXD/TXD-P (3)
220 Ω
RXD/TXD-N (8)
390 Ω
DGND (5)
The NS500 Unit does not have terminating resistance. Use the terminating resistance in the bus plug connector on the cable side for the NS500 Unit.
3 -16
4
Parameter Settings
This chapter provides an outline and details of NS500 parameters.
4.1 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.1 Outline of Parameters . . . . . . . . . . . . . . . . . . . . . . . .
4.1.2 Parameter Types . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.3 Editing Parameters . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.4 Effective Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Parameter Tables . . . . . . . . . . . . . . . . . . . . . .
4.2.1 Unit Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.2 Zero Point Return Parameters . . . . . . . . . . . . . . . . .
4.2.3 Machine System and
Peripheral Device Parameters . . . . . . . . . . . . . . .
4.2.4 Speed, Acceleration, and Deceleration Parameters
4.2.5 Positioning Parameters . . . . . . . . . . . . . . . . . . . . . . .
4.2.6 Multi-speed Positioning Parameters . . . . . . . . . . . .
4.2.7 Notch Output Parameters . . . . . . . . . . . . . . . . . . . . .
4.3 Parameter Details . . . . . . . . . . . . . . . . . . . . .
4.3.1 Unit Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3.2 Zero Point Return Parameters . . . . . . . . . . . . . . . . .
4.3.3 Machine System and Peripheral Devices
4.3.4 Speed, Acceleration, and Deceleration
. . . . . . .
. . . . . . . . .
4.3.5 Positioning Parameters . . . . . . . . . . . . . . . . . . . . . . .
4.3.6 Multi-speed Positioning . . . . . . . . . . . . . . . . . . . . . .
4.3.7 Notch Signal Output Positioning . . . . . . . . . . . . . . .
4 -10
4 -11
4 -11
4 -14
4 -5
4 6
4 -8
4 -9
4 -19
4 -21
4 -33
4 -35
4 -36
4 -2
4 -2
4 -2
4 -3
4 -3
4 -4
4 -4
4 -4
4
4 -1
4
Parameter Settings
4.1.2 Parameter Types
4.1 Parameters
4.1.1 Outline of Parameters
Parameters is the name given to the user constants that are required as the settings used to operate the NS500 Unit. You must set the optimum values for parameters according to the NS500
Unit and the machine to which the SGDH is mounted.
You can edit the NS500 Unit parameters using the NSxxx Setup Tool or host controller.
For parameters, refer to Chapter 6 Parameter Settings or the Σ II Series SGM j H/SGDH User’s
Manual Design and Maintenance (SIE-S800-32.2).
4.1.2 Parameter Types
Parameters are classified depending on their purpose as follows:
D Unit parameters
D Zero Point Return parameters
D Machine system and peripheral device parameters
D Speed, acceleration, and deceleration parameters
D Positioning parameters
D Multi-speed positioning parameters
D Notch output positioning parameters
Parameters are further classified according to the priority of the setting, as shown below.
Table 4.1 Parameter Types
Type
A
B
C
Meaning
Parameters that must be set even when using the NS500 Unit in standard mode.
Parameters that must be set when using the NS500 Unit in special mode.
Parameters whose settings hardly ever need to be changed.
4 -2
4.1 Parameters
4.1.3 Editing Parameters
You can edit parameters using the following methods.
Table 4.2 Methods of Editing Parameters
NSxxx Setup
Tool
Tools Methods Remarks
Select Option Parameter List from the
Parameter Menu to read all the NS500
Unit parameters. After the parameters have been displayed, select the parameters you want to edit, and click the Edit
Button to edit the parameters.
All changed parameters are stored in
RAM, so they are erased when the power is turned OFF. Use the Module
Reset Command to write the parameter data in RAM to the flash ROM.
Master Device You can edit using 8-bytes commands from the Master Device.
All changed parameters are stored in
RAM, so they are erased when the power is turned OFF. Execute the Reset
Service for the Identity Object to write the parameter data in RAM to the flash
ROM.
IMPORTANT
Parameters changed from each setting device are stored in RAM.
To save parametersin flash ROM afteradjustments have been completed, execute the Module Reset Command in the NSxxx Setup Tool or execute the Reset Service to the Identity Object via DeviceNet.
4
4.1.4 Effective Timing
Not all parameters edited from the NSxxx Setup Tool or Master Device are effective immediately. Changed parameters are effective at one of the following two times.
Table 4.3 Effective Timing for Parameters
Timing Control or Processing
Power-up
Immediate
The values of all parameters are made effective at the following times.
1. When power is turned ON.
2.
When the Module is reset from the NSxxx Setup Tool or via a command data.
The values of changed parameters are made effective immediately.
However, parameters will be stored in the Flash ROM at the following times.
S
When the Module is reset from the NSxxx Setup Tool or via a command data.
4 -3
4
Parameter Settings
4.2.2 Zero Point Return Parameters
4.2 Parameter Tables
The following tables list the parameters.
If using the NSxxx Setup Tool or reading/writing using a command data, edit parameters using
Pn jjj .
No.
4.2.1 Unit Parameters
The unit parameter table is shown below.
Name Range Units
Pn810 1 to 10,000,000 −
Effective
Timing
Power-up 1
Default
Value
B
Type
Pn811
Electronic Gear Ratio
(Numerator)
Electronic Gear Ratio
(Denominator)
1 to 10,000,000 − Power-up 1 B
4.2.2 Zero Point Return Parameters
The table of zero point return parameters are shown below.
No.
Pn800
Pn801
Pn802
Name
Zero Point Return Mode
Zero Point Return Function
Selection
Feed Speed for Zero Point
Return
0 to 3
0 to 7
Range
1 to 240,000
−
−
Units
1000 steps/ min
Effective
Timing
Immediate
Power-up
Immediate
Pn803
Pn804
Approach Speed for Zero
Point Return
Creep Speed for Zero Point
Return
1 to 240,000
1 to 240,000
1000 steps/ min
1000 steps/ min
Steps
Immediate
Immediate
Pn805
Pn806
Final Travel Distance for
Zero Point Return
Output Width for Zero Point
Return
Zero Point Offset
0 to 99,999,999
0 to 32, 767 Steps
Immediate
Immediate
Pn809 − 99,999,999 to
99,999,999
Steps Immediate
Pn80A Accel/Decel Time for Zero
Point Return
1 to 10,000 ms Immediate
Note: 1. “Steps” means “reference unit.” For reference unit details, refer to 4.3.1 Unit Parameters .
2. If you set the reference unit to 0.001 mm, 1,000 steps/min becomes mm/min.
0
1
Default
Value
10,000
1,000
500
0
100
0
100
B
B
B
B
B
B
B
C
B
Type
4 -4
4.2 Parameter Tables
4.2.3 Machine System and Peripheral Device Parameters
The machine system and peripheral device parameter table is shown below.
No.
Pn812
Pn813
Pn814
Pn815
Pn816
Pn817
Pn818
Pn819
Pn81A
Pn81B
Name Range
Coordinate Type 0, 1
Reference units per Machine
Rotation
1 to 1,500,000
Backlash Compensation 0 to 32,767
Backlash Direction
Positive Software Limit
0, 1
± 99,999,999
Negative Software Limit ± 99,999,999
Machine Function Selection 0 to 3
Hardware Limit Signal
Function Selection
Hardware Limit Action
Selection
Emergency Stop Signal
Function Selection
0 to 3
0, 1, 2
0 to 3
−
−
Units
Steps
Steps
−
Steps
−
−
−
−
Effective
Timing
Immediate
Immediate
Immediate
Immediate
Power-up
Power-up
Immediate
Immediate
Immediate
Immediate
Note: 1. “Steps” means “reference unit.” For reference unit details, refer to 4.3.1 Unit Parameters .
2. If you set the reference unit to 0.001 mm, 1,000 steps/min becomes mm/min.
Default
Value
0
360,000
0
0
99999999
− 99999999
0
1
0
1
C
C
B
B
B
C
C
B
B
B
Type
4
4 -5
4
Parameter Settings
4.2.4 Speed, Acceleration, and Deceleration Parameters
No.
Pn821
Pn822
Pn823
Pn824
Pn825
Pn826
Pn827
Pn829
Pn830
Pn831
Pn832
Pn833
Pn834
Pn835
4.2.4 Speed, Acceleration, and Deceleration Parameters
A table of speed, acceleration, and deceleration parameters is shown below.
Name Range Units
Feed Speed for Positioning 1 to 240,000
Effective
Timing
Immediate
Default
Value
24,000 1000 steps/min ms Immediate 100 Acceleration Time for
Positioning
Deceleration Time for
Positioning
Switch Speed for Second
Accel/Decel for Positioning
Accel/Decel Time for
Second Accel/Decel for
Positioning
Accel/Decel Type for
Positioning
Feed Speed for External
Positioning
Filter Selection
Constant Feed Reference
Unit Selection
Constant Feed Speed
1 to 10,000
1 to 10,000
1 to 240,000
1 to 10,000
0 to 3
1 to 240,000
0 to 3
0, 1
1 to 240,000 ms
1000 steps/min ms
−
−
−
1000 steps/min
1000 steps/min ms
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
100
24,000
200
0
24,000
0
0
24,000
100 Acceleration Time for
Constant Feed
Deceleration Time for
Constant Feed
Switch Speed for Constant
Feed Second Accel/Decel
Accel/Decel Time for
Constant Feed Second
Accel/Decel
1 to 10,000
1 to 10,000
1 to 240,000
1 to 10,000 ms
1000 steps/min ms
Immediate
Immediate
Immediate
100
24,000
200
B
B
C
C
B
B
B
B
B
B
B
C
C
C
Type
4 -6
4.2 Parameter Tables
No.
Name Range Units Effective
Timing
Immediate Pn836
Pn840
Pn841
Pn842
Pn843
Pn844
Pn845
Pn846
Pn847
Accel/Decel Type for
Constant Feed
Time Constant for
Exponential Accel/Decel
0, 1, 2, 3
4 to 10,000
Bias Speed for Exponential
Accel/Decel
1 to 240,000
Time Constant of Travelling
Average
4 to 10,000
Maximum Feed Speed 1 to 240,000
Step Distance 1
Step Distance 2
Step Distance 3
Step Distance 4
0 to 99,999,999
0 to 99,999,999
0 to 99,999,999
0 to 99,999,999
− ms
1000 steps/min ms
1000 steps/min
Steps
Steps
Steps
Steps
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Note: 1. “Steps” means “reference unit.” For reference unit details, refer to 4.3.1 Unit Parameters .
2. If you set the reference unit to 0.001 mm, 1,000 steps/min becomes mm/min.
0
25
0
25
Default
Value
24,000
1
10
100
1,000
B
C
C
C
B
B
B
B
B
Type
4
4 -7
4
Parameter Settings
4.2.5 Positioning Parameters
4.2.5 Positioning Parameters
The positioning parameter table is shown below.
No.
Pn850
Pn851
Pn852
Pn853
Name
Positioning Deadband
Positioning Timeout
Positioning Proximity
Detection Width
Direction for Rotation
System
Range
0 to 10,000
0 to 100,000
0 to 32,767
0, 1
Steps ms
Steps
−
Units Effective
Timing
Default Value
Immediate 5 A
Type
Immediate 0
Immediate 10
Immediate 0
Pn854
Pn855
Pn856
Approach Speed for
External Positioning
Travel Distance for
External Positioning
Function Selection for
External Positioning
1 to 240,000
0 to 99,999,999
0 to 1
1,000 steps/min
Steps
−
Immediate 24,000
Immediate 0
Power-up 1
Pn85A Number of Stations 1 to 32,767 − Immediate 1
Note: 1. “Steps” means “reference unit.” For reference unit details, refer to 4.3.1 Unit Parameters .
2. If you set the reference unit to 0.001 mm, 1,000 steps/min becomes mm/min.
A
B
B
B
B
B
B
4 -8
4.2 Parameter Tables
4.2.6
Multi-speed Positioning Parameters
A table of multi-speed positioning parameters is shown below.
No.
Pn861
Pn862
Pn86C
Pn86D
Pn86E
Pn86F
Pn870
Pn871
Pn872
Pn873
Pn863
Pn864
Pn865
Pn866
Pn867
Pn868
Pn869
Pn86A
Pn86B
Pn874
Pn875
Pn876
Pn877
Pn878
Name Range Units Effective
Timing
Number of Points for Speed Switching
Initial Feed Speed for Multi-speed Positioning
Speed Switching Position 1
Speed Switching Position 2
0 to 16
1 to 240,000
−
1000 steps/min
0 to 99,999,999 Steps
0 to 99,999,999 Steps
Immediate
Immediate
Immediate
Immediate
Speed Switching Position 3
Speed Switching Position 4
Speed Switching Position 5
Speed Switching Position 6
Speed Switching Position 7
Speed Switching Position 8
Speed Switching Position 9
0 to 99,999,999 Steps
0 to 99,999,999 Steps
0 to 99,999,999 Steps
0 to 99,999,999 Steps
0 to 99,999,999 Steps
0 to 99,999,999 Steps
0 to 99,999,999 Steps
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Speed Switching Position 10
Speed Switching Position 11
Speed Switching Position 12
Speed Switching Position 13
Speed Switching Position 14
Speed Switching Position 15
Speed Switching Position 16
Switching Speed 1
Switching Speed 2
Switching Speed 3
Switching Speed 4
Switching Speed 5
Switching Speed 6
0 to 99,999,999 Steps
0 to 99,999,999 Steps
0 to 99,999,999 Steps
0 to 99,999,999 Steps
0 to 99,999,999 Steps
0 to 99,999,999 Steps
0 to 99,999,999 Steps
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
1000 steps/min
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
1000 steps/min
Immediate
1000 steps/min
Immediate
1000 steps/min
Immediate
1000 steps/min
Immediate
1000 steps/min
Immediate
0
Default
Value
24,000
0
0
0
0
0
0
0
24,000
0
0
0
0
0
0
0
0
0
24,000
24,000
24,000
24,000
24,000
C
C
C
C
C
C
C
Type
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
4 -9
4
4
Parameter Settings
4.2.7
Notch Output Parameters
No.
Pn879
Pn87A
Pn87B
Pn87C
Pn87D
Pn87E
Pn87F
Pn880
Pn881
Pn882
Switching Speed 7
Switching Speed 8
Switching Speed 9
Switching Speed 10
Switching Speed 11
Switching Speed 12
Switching Speed 13
Switching Speed 14
Switching Speed 15
Switching Speed 16
Name Range
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
Note: 1. “Steps” means “reference unit.” For reference unit details, refer to 4.3.1 Unit Parameters .
2. If you set the reference unit to 0.001 mm, 1,000 steps/min becomes mm/min.
4.2.7
Notch Output Parameters
The notch output parameter table is shown below.
No.
Name Range Units Effective
Timing
Pn890
Pn891
Pn892
Pn893
Pn894
Notch Signal Output
Position Setting
Notch Signal Output
Setting
Notch 1 Output
Position Lower Limit
Notch 1 Output
Position Upper Limit
Notch 2 Output
Position Lower Limit
0
0 to 3
±
±
±
, 1
99,999,999
99,999,999
99,999,999
−
−
Steps
Steps
Steps
Immediate
Immediate
Immediate
Immediate
Immediate
0
0
0
0
0
Pn895 Notch 2 Output
Position Upper Limit
± 99,999,999 Steps Immediate 0
Note: 1. “Steps” means “reference unit.” For reference unit details, refer to 4.3.1 Unit Parameters .
2. If you set the reference unit to 0.001 mm, 1,000 steps/min becomes mm/min.
Default
Value
Units Effective
Timing
1000 steps/min
1000 steps/min
1000 steps/min
1000 steps/min
1000 steps/min
1000 steps/min
1000 steps/min
1000 steps/min
1000 steps/min
1000 steps/min
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
C
C
C
C
C
C
Default
Value
24,000 C
Type
24,000
24,000
24,000
24,000
24,000
24,000
24,000
24,000
24,000
C
C
C
C
C
C
C
C
C
Type
4 -10
4.3 Parameter Details
4.3 Parameter Details
Pn810
Pn811
No.
4.3.1 Unit Parameters
The unit for performing positioning using a NS500 Unit is determined by the following two parameters.
Name Range
Electronic gear (numerator) 1 to 10,000,000
Electronic gear
(denominator)
1 to 10,000,000
−
−
Units Effective
Timing
Power-up
Power-up
1
1
Default
Value
B
B
Type
The electronic gear function can be used to set the position command units equal to the amount of encoder pulses. The host controller can generate position commands in more familiar userdefined units such as millimeters or inches.
J
Not Using the Electronic Gear
If not using the electronic gear, set Pn810 and Pn811 to 1. This will set the reference unit to
1 pulse, so you must calculate the scale position units using the host controller.
SGDH NS500
4
PG
Motor m
1 pulse
7 revolutions
1 pulse
IMPORTANT
No. of Encoder pulses =
2048 × 4
5 revolutions n
Pitch of ball screw
P = 6 mm
In this manual, the reference unit explained in Electronic Gear Settings When Using a Ball Screw in 4.3.1 Unit
Parameters is based on a unit of 0.001 mm. The speed and other parameters must be interpreted as follows:
S
Pn821: Feed Speed for Positioning (mm/min) → (1000 pulses/min)
4 -11
Parameter Settings
4.3.1 Unit Parameters
J
Electronic Gear Settings When Using a Ball Screw
If using a ball screw, first check the following specifications.
D Number of Encoder pulses
D Gear ratio
D Ball screw pitch
System Example
The following system example shows the formulas when the reference unit is set to 0.001 mm.
SGDH NS500
4
PG Motor m
0.001 mm
7 revolutions
0.001 mm
No. of Encoder pulses=
2,048 × 4
5 revolutions n
Pitch of ball screw
P = 6 mm
D REV =
Travel distance of load per revolution (mm)
Reference unit (mm)
=
6 mm
0.001 mm
= 6000
D A = (REV) × {Gear ratio (load rev.)} = 6000 × 5 = 30000
D B = (Encoder pulses) × (Pulse multiplier) × {Gear ratio (motor rev.)} = 2048 × 4 × 7 = 57344
D B/A = 57344/30000 = 1.911
Data ranges are shown below.
D A ≦ 10,000,000
D B ≦ 10,000,000
D 100 ≧ B/A ≧ 0.01
By storing the value of A in Pn811 and the value of B in Pn810, you can use the Electronic Gear function. These parameters are enabled when the power is turned ON. After you have changed the parameter, execute the Module Reset Command or the Reset Service to the Identity Object.
IMPORTANT
Setting B/A outside the range 0.01 to 100 may result in a misoperation. Make sure to set B and A within this range.
4 -12
4.3 Parameter Details
J
Electronic Gear Settings when Using a Rotary Table
If using a rotary table, first check the following specifications.
D Number of Encoder pulses
D Gear ratio
System Example
The following system example shows the formulas when the reference unit is set to 0.001
° .
SGDH NS500
PG Motor m
0.001
°
3 revolutions
0.001
°
No. of Encoder pulses =
2048 × 4
1 revolution n
Rotating load
360 ° /revolution
D REV = 360 ° /0.001
° = 36000
D A = REV × {Gear Ratio (load rev.)} = 36000 × 1 = 36000
D B = (Encoder pulses ) × (Pulse multiplier) × {Gear ratio (motor rev.)} = 2048 × 4 × 3 = 24576
Data ranges are shown below.
D A ≦ 10,000,000
D B ≦ 10,000,000
D 100 ≧ B/A ≧ 0.01
By storing the value of A in Pn811 and the value of B in Pn810, you can use the Electronic Gear function. These parameters are enabled when the power is turned ON. After you have changed the parameter, execute the Module Reset Command or the Reset Service to the Identity Object.
IMPORTANT
Setting B/A outside the range 0.01 to 100 may result in a misoperation. Make sure to set B and A within this range.
4
4 -13
4
Parameter Settings
4.3.2 Zero Point Return Parameters
4.3.2 Zero Point Return Parameters
J
Zero Point Return Types
The following four types of zero point return are supported.
Type 0
This zero point return type returns to the zero point using the deceleration limit switch signal
(DEC signal) and the phase C pulse of the encoder. The outline of the operation is as follows:
1.
The axis travels in the direction specified as the zero point direction in the Zero Point
Return Function Selection (Pn801) at the Zero Point Return Feed Speed (Pn802).
2.
When the deceleration limit switch status changes, the axis decelerates and travels at the
Zero Point Return Approach Speed (Pn803).
3.
When the deceleration limit switch status changes again, the axis decelerates further when the first encoder phase C pulse is detected and then travels at the Zero Point Return Creep
Speed (Pn804).
4.
The axis travels the Zero Point Return Final Travel Distance (Pn805) from the position where the phase C was detected, and that position becomes the zero point.
Speed
Zero point return feed speed
(Pn802)
Zero point return approach speed
(Pn803)
Zero point return creep speed (Pn804)
Zero point return final travel distance (Pn805)
Time
Dog width
Deceleration limit switch signal
Phase C
Machine coordinate system zero point
Zero point area
Type 1
This zero point return type returns to the zero point using the zero point signal (ZERO signal).
The outline of the operation is as follows:
1.
The axis travels in the direction specified as the zero point direction in the Zero Point
Return Function Selection (Pn801) at the Zero Point Return Approach Speed (Pn803).
2.
When the zero point signal status changes, the axis decelerates, and travels at the Zero
Point Return Creep Speed (Pn804).
4 -14
4.3 Parameter Details
Speed
3.
The axis travels the Zero Point Return Final Travel Distance (Pn805) from the position that the zero point signal status changed, and that position becomes the zero point.
Zero point return approach speed
(Pn803)
Zero point return creep speed
(Pn804)
Zero point return final travel distance (Pn805)
Time
Zero point signal
Machine coordinate system zero point
Zero point area
Type 2
This zero point return type returns to the zero point using the deceleration limit switch (DEC signal) and the zero point signal (ZERO signal). The outline of the operation is as follows:
1.
The axis travels in the direction specified as zero point direction in the Zero Point Return
Function Selection (Pn801) at the Zero Point Return Feed Speed (Pn802).
2.
When the deceleration limit switch status changes, the axis decelerates, and travels at the
Zero Point Return Approach Speed (Pn803).
3.
When the zero point signal changes, the axis decelerates further and travels at the Zero
Point Return Creep Speed (Pn804).
4.
The axis travels the Zero Point Return Final Travel Distance (Pn805) from the position where the zero point signal changed, and that position becomes the zero point.
Speed
Zero point return feed speed
(Pn802)
Zero point return approach speed
(Pn803)
Zero point return creep speed (Pn804)
Zero point return final travel distance (Pn805)
Time
Dog width
Deceleration limit switch signal
Zero point signal
Machine coordinate system zero point
Zero point area
4 -15
4
4
Parameter Settings
4.3.2 Zero Point Return Parameters
Type 3
This zero point return type returns to the zero point using the phase C pulse of the encoder only.
The outline of the operation is as follows:
1.
The axis travels in the direction specified as zero point direction in the Zero Point Return
Function Selection (Pn801) at the Zero Point Return Approach Speed (Pn803).
2.
When the first phase C pulse of the encoder is detected, the axis decelerates, and travels at the Zero Point Return Creep Speed (Pn804).
3.
The axis travels the Zero Point Return Final Travel Distance (Pn805) from the position where the phase C pulse was detected, and that position becomes the zero point.
Speed
Zero point return approach speed
(Pn803)
Zero point return creep speed (Pn804)
Zero point return final travel distance (Pn805)
Time
Phase C pulse
Machine coordinate system zero point
Zero point area
INFO
When the setting for the Zero Point Return Final Travel Distance (Pn805) is small (when the distance is shorter than the distance required for the deceleration from approach speed), the axis will travel past the zero point and then return to it from the other direction.
Zero point return approach speed
Zero point return final travel distance
Amount of overtravel
Returning the amount overtraveled
Time
Phase C pulse
Zero point
4 -16
4.3 Parameter Details
J
Parameter Details (Object 0x64)
The details of parameters relating to zero point return are shown below.
Zero Point Return Mode (Pn800)
The zero point return type is specified in the zero point return mode.
Zero Point
Return Mode
0
1
2
3
Zero Point Return Type
3-step deceleration using deceleration limit switch and phase
C pulse
Double-step deceleration using zero point signal
3-step deceleration using deceleration limit switch and zero point signal
Double-step deceleration using phase C pulse
Zero Point Return Function Selection (Pn801)
The zero point return function selection has the following bit settings.
Bit
0
1
2
3 to 15 Reserved
Name Description
Zero Point Return Direction Setting* 0: Positive direction
1: Negative direction
Deceleration Limit Switch Signal
Setting
0: Enabled on Low
1: Enabled on High
Zero Point Signal Setting 0: Enabled on leading edge
1: Enabled on trailing edge
−
Zero Point Return Feed Speed (Pn802)
Use the Zero Point Return Feed Speed to set the initial feed speed for 3-step deceleration zero point return.
The setting unit is 1,000 steps/min.
Zero Point Return Approach Speed (Pn803)
Use the Zero Point Return Approach Speed to set the approach speed for zero point return. The setting unit is 1,000 steps/min.
Zero Point Return Creep Speed (Pn804)
Use the Zero Point Return Creep Speed to set the creep speed for zero point return. The setting unit is 1,000 steps/min.
4 -17
4
4
Parameter Settings
4.3.2 Zero Point Return Parameters
Zero Point Return Final Travel Distance (Pn805)
Use the Zero Point Return Final Travel Distance to set the distance from the position where the encoder phase C and zero point signal were detected to the machine zero point. The setting unit is steps.
Zero Point Output Width (Pn806)
Use the Zero Point Output Width to set the area that will be regarded as the zero point. The setting unit is steps.
In the following diagram, if the conditions outlined below are met, the Zero Point Flag in the response data will be set to 1.
D X = | Zero point − Current position | ≦ Pn806
Current position
Zero point
Position
Pn806 Pn806
X
Zero Point Offset (Pn809)
The system automatically writes to the Zero Point Offset the value of the offset from the zero point on the encoder when the zero point setting in the absolute value detection system has been completed. Normally, this parameter does not need to be set.
When using an absolute value detection system, set this value to enable adjustment of the zero point.
Zero Point Return Acceleration/Deceleration Time (Pn80A)
Use the Zero Point Return Acceleration/Deceleration Time to set the acceleration/declaration time constant used during zero point return. The setting unit is ms. Single-step linear acceleration/deceleration is used for zero point return. Refer to 4.3.4 Speed, Acceleration, and Deceleration for information on this acceleration/deceleration type.
4 -18
4.3 Parameter Details
4.3.3 Machine System and Peripheral Devices
The details of parameters relating to the machine system and peripheral devices are shown below.
Coordinate Type (Pn812)
Use the Coordinate Type to set whether to use the NS500 Unit as a linear axis or rotary axis.
Pn812
0
1
Description
The linear axis is designated.
The unit of current value data: steps
The rotary axis is designated.
The unit of current value data: degrees
Reference Units per Machine Rotation (Pn813)
Use the Reference Units per Machine Rotation to set the reference unit for one machine rotation. This parameter is enabled only when the coordinate type is set to rotary axis. If this parameter is not set correctly, when the machine performs a 360 ° rotation, the current position will not be reset to 0 ° , so be careful.
The setting unit is steps. The initial value is 360,000.
Backlash Compensation (Pn814)
Use the Backlash Compensation to set the amount of compensation when backlash compensation is used. The setting unit is steps.
Backlash Compensation Direction (Pn815)
Use the Backlash Compensation Direction to set the direction of the backlash compensation.
Normally, set this parameter in the opposite direction to the zero point direction.
Pn815
0
1
Positive Direction
Negative Direction
Description
Positive Software Limit (Pn816)
Use the Positive Software Limit to set the software limit in the positive direction. The setting unit is reference unit. Make the setting between − 99,999,999 and 99,999,999.
Negative Software Limit (Pn817)
Use the Negative Software Limit to set the software limit in the negative direction. The setting unit is reference unit. Make the setting between − 99,999,999 and 99,999,999.
4 -19
4
4
Parameter Settings
4.3.3 Machine System and Peripheral Devices
Machine Function Selection (Pn818)
Use the Machine Function Selection to set whether or not to use the software limit functions and the backlash compensation functions.
Bit
0
1
Description
0: Software Limit is disabled.
1: Software Limit is enabled.
0: Backlash Compensation is disabled.
1: Backlash Compensation is enabled.
Hardware Limit Signal Function Selection (Pn819)
Use the Hardware Limit Signal Function Selection to set whether or not to use the hardware limit and to set the signal polarity.
Bit
0
1
2 to 15
Name
Enable/Disable Hardware LImit
Hardware Limit Signal Polarity
Reserved
Description
0: Enabled
1: Disabled
0: Enabled on Low
1: Enabled on High
−
Hardware Limit Action (Pn81A)
Use the Hardware Limit Action to set the operation of the NS500 Unit when a hardware limit is detected.
Pn81A
0
1
2
3 to 255
Description
Servo OFF
Hard Stop: Stops at the specified maximum torque.
Deceleration to a Stop: Stops according to the specified deceleration curve.
Reserved
4 -20
4.3 Parameter Details
Emergency Stop Signal Function Selection (Pn81B)
Use the Emergency Stop Signal Function Selection to set whether or not to use the emergency stop function and to set the polarity of the signal.
Bit
0
1
2 to 15
Name
Enable/disable
Emergency Stop
Emergency Stop
Signal Polarity
Reserved
Description
0: Disabled
1: Enabled
0: Disabled on Low
1: Enabled on High
−
4.3.4 Speed, Acceleration, and Deceleration
J
Acceleration and Deceleration Patterns
The following acceleration and deceleration patterns are possible by combining acceleration/ deceleration types (Pn826 or Pn836) and filters (Pn829).
(
Filter
Selection
)
0: None
1: Exponent
2: Exponent with Bias
3: Travelling
Average
0: None
Acceleration/Deceleration Type (Pn826 or Pn836)
1: Single-step
Linear
2: Double-step
Linear
3: Asymmetric
No acceleration and deceleration
Single-step Linear
Accel/Decel
ConstantAccel/Decel* 1
Double-step Linear
Accel/Decel
ConstantAccel/Decel* 1
Asymmetric Linear
Accel/Decel
ConstantAccel/Decel* 1
− Exponential
Accel/Decel
Constant Accel/Decel time* 2
Single-step Linear
Accel/Decel
Constant Accel/Decel time* 2
−
Exponential Accel/Decel with Bias
Constant Accel/Decel time* 2
−
−
−
S-curve Accel/Decel
Time
ConstantAccel/Decel* 1
−
−
Asymmetric S-curve
Accel/Decel
ConstantAccel/Decel* 1
* 1. With Constant Accel/Decel, the time required for acceleration and deceleration changes with the feed speed changes.
* 2. With Constant Accel/Decel time, the time required for acceleration and deceleration does not change even if the feed speed changes.
Note: Combinations other than those given above may result in incorrect acceleration and deceleration.
4 -21
4
4
Parameter Settings
4.3.4 Speed, Acceleration, and Deceleration
Single-step Linear Acceleration/Deceleration with Constant
Acceleration/Deceleration
Table 4.4 Related Parameters
Pn jjj
Pn826
Pn829
Pn821
Pn822
Pn843
Name
Acceleration/Deceleration Type for Positioning
(= 1)
Filter Selection (= 0)
Feed Speed for Positioning
Acceleration Time for Positioning
Maximum Feed Speed
Speed
Pn822 Pn822
Time
Figure 4.1
Single-step Linear Acceleration/Deceleration with Constant
Acceleration/Deceleration
4 -22
4.3 Parameter Details
Double-step Linear Acceleration/Deceleration with Constant
Acceleration/Deceleration
Table 4.5 Related Parameters
Pn jjj
Pn826
Pn829
Pn821
Pn822
Pn824
Pn825
Pn843
Name
Acceleration/Deceleration Type for Positioning
(= 2)
Filter Selection (= 0)
Feed Speed for Positioning
Acceleration Time Constant for Positioning
Switch Speed for Second Accel/Decel
Accel/Decel Time Constant of Second Accel/Decel
Maximum Feed Speed
Speed
Pn825 Pn825
4
Pn822 Pn822
Time
Figure 4.2
Double-step Linear Acceleration/Deceleration with Constant
Acceleration/Deceleration
4 -23
4
Parameter Settings
4.3.4 Speed, Acceleration, and Deceleration
Asymmetric Linear Acceleration/Deceleration with Constant
Acceleration/Deceleration
Table 4.6 Related Parameters
Pn jjj
Pn826
Pn829
Pn821
Pn822
Pn823
Pn843
Name
Acceleration/Deceleration Type for Positioning
(= 3)
Filter Selection (= 0)
Feed Speed for Positioning
Acceleration Time for Positioning
Deceleration Time for Positioning
Maximum Feed Speed
Speed
Pn822 Pn823
Time
Figure 4.3
Asymmetric Linear Acceleration/Deceleration with Constant
Acceleration/Deceleration
4 -24
4.3 Parameter Details
Exponential Acceleration/Deceleration with Constant
Acceleration/Deceleration Time
Table 4.7 Related Parameters
Pn jjj
Pn826
Pn829
Pn821
Pn840
Name
Acceleration/Deceleration Type for Positioning
(= 0)
Filter Selection (= 1)
Feed Speed for Positioning
Time Constant for Exponential Acceleration/Deceleration
Speed
4
Pn840 Pn840
Time
Figure 4.4
Exponential Acceleration/Deceleration with Constant
Acceleration/Deceleration Time
4 -25
4
Parameter Settings
4.3.4 Speed, Acceleration, and Deceleration
Exponential Acceleration/Deceleration with Bias with Constant
Acceleration/Deceleration Time
Table 4.8 Related Parameters
Pn jjj
Pn826
Pn829
Pn821
Pn840
Pn841
Name
Acceleration/Deceleration Type for Positioning
(= 0)
Filter Selection (= 2)
Feed Speed for Positioning
Time Constant for Exponential Acceleration/Deceleration
Bias Speed for Exponential Acceleration/Deceleration
Speed
Pn840 Pn840
Time
Figure 4.5
Exponential Acceleration/Deceleration with Bias with Constant
Acceleration/Deceleration Time
4 -26
4.3 Parameter Details
Single-step Linear Acceleration/Deceleration with Constant
Acceleration/Deceleration Time
Table 4.9 Related Parameters
Pn jjj
Pn826
Pn829
Pn821
Pn842
Name
Acceleration/Deceleration Type for Positioning
(= 0)
Filter Selection (= 3)
Feed Speed for Positioning
Time Constant of Travelling Average
Speed
4
Pn842 Pn842
Time
Figure 4.6
Single-step Linear Acceleration/Deceleration with Constant
Acceleration/Deceleration Time
4 -27
4
Parameter Settings
4.3.4 Speed, Acceleration, and Deceleration
S-curve Acceleration/Deceleration with Constant
Acceleration/Deceleration
Table 4.10 Related Parameters
Pn jjj
Pn826
Pn829
Pn821
Pn822
Pn842
Pn843
Name
Acceleration/Deceleration Type for Positioning
(= 1)
Filter Selection (= 3)
Feed Speed for Positioning
Acceleration Time for Positioning
Time Constant of Travelling Average
Maximum Feed Speed
Speed
Pn822 Pn822
Pn842 Pn842
Figure 4.7
S-curve Acceleration/Deceleration with Constant
Acceleration/Deceleration
Time
4 -28
4.3 Parameter Details
Asymmetric S-curve Acceleration/Deceleration with Constant
Acceleration/Deceleration
Table 4.11 Related Parameters
Pn jjj
Pn826
Pn829
Pn821
Pn822
Pn823
Pn842
Pn843
Name
Acceleration/Deceleration Type for Positioning
Filter Selection
Feed Speed for Positioning (mm/min)
Acceleration Time for Positioning
Deceleration Time for Positioning
Time Constant for Travelling Average
Maximum Feed Speed
Speed 4
Time
Pn822
Pn842
Pn823
Pn842
Figure 4.8
Asymmetric S-curve Acceleration/Deceleration with Constant
Acceleration/Deceleration
4 -29
4
Parameter Settings
4.3.4 Speed, Acceleration, and Deceleration
J
Parameter Details
Feed Speed for Positioning (Pn821)
Use the Feed Speed for Positioning to set the feed speed of the positioning. The setting unit is 1,000 steps/min.
Acceleration Time for Positioning (Pn822)
Use the Acceleration Time for Positioning to set the acceleration time for the positioning. The setting unit is ms.
Deceleration Time for Positioning (Pn823)
Use the Deceleration Time for Positioning to set the deceleration time for positioning. The setting unit is ms.
This parameter is enabled only when the Acceleration/Deceleration Type for Positioning
(Pn826) is set to the asymmetrical linear acceleration and deceleration.
Switch Speed for Second Acceleration/Deceleration for
Positioning (Pn824)
Use the Switch Speed for Second Acceleration/Deceleration for Positioning to set the switching speed to acceleration and deceleration of the second step when using double-step linear acceleration and deceleration. The setting unit is 1,000 step/min.
This parameter is enabled only when the Acceleration/Deceleration Type for Positioning
(Pn826) is set to double-step linear acceleration and deceleration.
Acceleration/Deceleration Time for Second
Acceleration/Deceleration for Positioning (Pn825)
Use the Acceleration/Deceleration Time for Second Acceleration/Deceleration for Positioning to set the acceleration and deceleration time for the second step when using double-step linear acceleration and deceleration. The setting unit is ms.
This parameter is enabled only when the Acceleration/Deceleration Type for Positioning
(Pn826) is set to double-step linear acceleration and deceleration.
Acceleration/Deceleration Type for Positioning (Pn826)
Use the Acceleration/Deceleration Type for Positioning to set the type of acceleration and deceleration for the positioning.
You can set eight different acceleration and deceleration patterns using different combinations of Acceleration/Deceleration Type for Positioning and Filter Selection (Pn829).
Description Setting
0
1
None
Single Step Linear
4 -30
4.3 Parameter Details
Setting
2
3
Double Step Linear
Description
Asymmetric
External Positioning Feed Speed (Pn827)
Use the External Positioning Feed Speed to set the feed speed for external positioning.
The setting unit is 1,000 steps/min.
Filter Selection (Pn829)
Use the Filter Selection to set the acceleration and deceleration filter type. This parameter is used in common by the positioning, constant feeding, and zero point return operations.
Setting
0
1
2
3
Description
None
Exponential
Exponential with Bias
Travelling Average
Constant Feed Reference Unit Selection (Pn830)
Use the Constant Feed Reference Unit Selection to set the reference unit for the speed setting for a constant feed command data.
Setting
0
1
Description
Sets an override value (%) for the feed speed for FEED (Pn831) in the command data.
Speed set directly in the command data.
The setting unit is 1000 steps/min.
Constant Feed Speed (Pn831)
Use the Constant Feed Speed to set the feed speed when using the FEED operation. The setting unit is 1,000 steps/min.
Acceleration Time for Constant Feed (Pn832)
Use the Acceleration Time for Constant Feed to set the acceleration time when using the feed operation. The setting unit is ms.
Deceleration Time for Constant Feed (Pn833)
Use the Deceleration Time for Constant Feed to set the deceleration time when using asymmetrical acceleration and deceleration with the constant feed operation. The setting unit is ms.
4 -31
4
4
Parameter Settings
4.3.4 Speed, Acceleration, and Deceleration
This parameter is enabled only when the Acceleration/Deceleration Type for Constant Feed
(Pn836) is set to asymmetrical linear acceleration and deceleration.
Switch Speed for Constant Feed Second Accel/Decel (Pn834)
Use the Switch Speed for Constant Feed Second Acceleration/Deceleration to set the switching speed to double-step acceleration and deceleration when using double-step linear acceleration and deceleration with the constant feed operation. The setting unit is 1,000 steps/min.
This parameter is enabled only when the Acceleration/Deceleration Type for Constant Feed
(Pn836) is set to double-step linear acceleration and deceleration.
Accel/Decel Time for Constant Feed Second Accel/Decel (Pn835)
Use the Acceleration/Deceleration Time for Constant Feed Second Acceleration/Deceleration to set the second acceleration/deceleration time when using double-step linear acceleration and deceleration with the constant feed operation. The setting unit is ms.
This parameter is enabled only when the Acceleration/Deceleration Type for Constant Feed
(Pn836) is set to double-step linear acceleration and deceleration.
Acceleration/Deceleration Type for Constant Feed (Pn836)
Use the Acceleration/Deceleration Type for Constant Feed to set the acceleration and deceleration type with the constant feed operation.
You can set eight different acceleration and deceleration patterns using different combinations of Acceleration/Deceleration Type for Constant Feed and Filter Selection (Pn829).
Setting
0
1
2
3
None
Single Step Linear
Double Step Linear
Asymmetric
Description
Time Constant for Exponential Acceleration/Deceleration (Pn840)
Use the Time Constant for Exponential Acceleration/Deceleration to set the time constant when using exponential acceleration and deceleration. This parameter is used in common by the positioning and the continuous rotary operation. The setting unit is ms.
Bias Speed for Exponential Acceleration/Deceleration (Pn841)
Use the Bias Speed for Exponential Acceleration/Deceleration to set the bias speed of the exponential acceleration and deceleration. The setting unit is 1,000 steps/min.
Time Constant of Travelling Average (Pn842)
Use the Time Constant of Travelling Average to set the time constant of the average travel speed of the acceleration and deceleration. This parameter is used in common by the positioning and the continuous rotary operation. The setting unit is ms.
4 -32
4.3 Parameter Details
Maximum Feed Speed (Pn843)
Use the Maximum Feed Speed to set the maximum feed speed of the positioning, FEED, and zero point return operations. The acceleration and deceleration data is calculated from this data and the time constants. The setting unit is 1,000 steps/min.
Step Distance 1 (Pn844)
Use the Step Distance 1 to set the amount of travel when executing step operation. This value is used when the 0 has been specified as the command data in a command data.
The setting unit is steps.
Step Distance 2 (Pn845)
Use the Step Distance 2 to set the amount of travel when executing step operation. This value is used when the 1 has been specified as the command data in a command data.
The setting unit is steps.
Step Distance 3 (Pn846)
Use the Step Distance 3 to set the amount of travel when executing step operation. This value is used when the 2 has been specified as the command data in a command data.
The setting unit is steps.
Step Distance 4 (Pn847)
Use the Step Distance 4 to set the amount of travel when executing step operation. This value is used when the 3 has been specified as the command data in a command data.
The setting unit is steps.
4.3.5 Positioning Parameters
J
Parameter Details
Positioning Deadband (Pn850)
Use the Positioning Deadband to set the positioning completed range, i.e., to determine if the axis is on-target position. The setting unit is steps. When the positioning deadband is set to 0, no on-target position check will be performed.
Current value that is changing End Point
Coordinate axis
Pn850 Pn850
X
Positioning Deadband
4 -33
4
4
Parameter Settings
4.3.5 Positioning Parameters
When the following condition is satisfied in the above figure, the axis is viewed as being at the on-target position and the On-target Flag in the response data will be set to 1.
D X = (End point − Current value) ≤ Pn850
Positioning Timeout (Pn851)
Use the Positioning Timeout to set the time for performing on-target position check. The setting unit is ms. If, after the move command distribution has been completed, the positioning completed range is not entered within the time set, A.9A positioning a completion timeout warning will be sent.
If this parameter is set to 0, the check time becomes infinite.
Positioning Proximity Detection Width (Pn852)
Use the Positioning Proximity Detection Width to set the range for positioning area proximity to be detected. If the difference between the current position and the target position are within this parameter range, the proximity signal in the response data will be set to 1. The setting unit is steps.
Direction for Rotation System (Pn853)
Use the Direction for Rotation System to set the rotation direction for when Station Commands or rotation commands using absolute values are used.
Setting
0
1
Description
Uses the rotation direction in command data.
Uses the direction for the shortest travel.
Approach Speed for External Positioning (Pn854)
Use the Approach Speed for External Positioning to set the approach speed after the external signal has reversed status for an external positioning command.
The setting unit is 1,000 steps/min.
Travel Distance for External Positioning (Pn855)
Use the Travel Distance for External Positioning to set the travel distance after the external signal has reversed status for an external positioning command.
The setting unit is steps.
Function Selection for External Positioning (Pn856)
Use the Function Selection for External Positioning to select the polarity of the external signal.
Bit
0
2 to 15
Name Description
External Signal Polarity
0: Enabled on low
1: Enabled on high
Reserved −
4 -34
4.3 Parameter Details
Number of Stations (Pn85A)
Use the Number of Stations to set how many stations one revolution of the servomotor will be evenly split into when Station Commands are used.
In Station Commands, equally divided stations are numbered in order from 0 and positioning is performed by specifying a station number.
Station n Station 0
Station 1
4.3.6
Multi-speed Positioning
By using multi-speed positioning, the speed can be changed in stages during positioning.
Up to 16 speed change stages are possible.
When the axis reaches a specified position, the speed switches to the speed for the next stage and the axis travels to the specified position in that next stage.
Time
Speed 2
(Pn874)
Speed 1
(Pn873)
Speed switching position 3
(Pn865)
Feed speed
(Pn862)
Speed 3
(Pn875)
Speed switching position 2
(Pn864)
Speed switching position 1 (Pn863)
Speed
J
Parameter Details
Number of Points for Speed Switching (Pn861)
Use the Number of Points for Speed Switching to set the number of points at which the speed will be switched. If, for example, the parameters for speed switching positions were set from
1 to 16 but this setting for the number of points was set to 3, the speed switching would be enabled for 3 points only.
4 -35
4
4
Parameter Settings
4.3.7
Notch Signal Output Positioning
Initial Feed Speed for Multi-speed Positioning (Pn862)
Use the Initial Feed Speed for Multi-speed Positioning to set the initial feed speed when performing speed multi-step positioning. This speed will be enabled until the position in the speed switching position 1 parameter is reached.
The setting unit is 1,000 steps/min.
Speed Switching Positions 1 to 16 (Pn872)
Use the Speed Switching Position to set the position at which the speed is to change at a position relative to the start position. The speed switching position xx and switching speed xx are used together. For example, the axis will travel from speed switching position 1 to speed switching position 2 at speed 1.
The setting unit is steps.
Switching Speeds 1 to 16 (Pn873 to Pn882)
Use the Switching Speed to set the feed speed between specified speed switching positions.
For example, the axis will travel at speed 2 between speed switching position 2 and speed switching position 3.
The setting unit is 1,000 steps/min.
4.3.7
Notch Signal Output Positioning
During the positioning, notch signals (NOTCH 1 and NOTCH 2) are output when specified points are passed.
Two notch signals, NOTCH 1 and NOTCH 2, can be output.
Notch output 1 position lower limit (Pn892)
Notch output 1 position upper limit (Pn893)
Speed
Time
NOTCH 1 signal
1
0
4 -36
4.3 Parameter Details
J
Parameter Details
Notch Signal Output Position Setting (Pn890)
Use the Notch Signal Output Position Setting to set whether absolute or relative positions are set for the notch signal output position parameters.
Setting
0
1
Description
Setting absolute position.
Specifies relative position.
Notch Signal Output Setting (Pn891)
Use the Notch Signal Output Setting to set the polarity of the notch signal output.
Table 4.12 Notch Signal Output Setting
Setting
0
1
Description
Sets NOTCH 1 signal.
Sets NOTCH 2 signal.
Table 4.13
Bit 0/ Bit 1
0
1
Bit Meanings
Description
Normally: OFF When passed: ON
Normally: ON When passed: OFF
Notch 1 Output Position Lower Limit (Pn892)
Notch 1 Output Position Upper Limit (Pn893)
Use the Notch 1 Output Position Upper/Lower Limits to set the output position range for notch signal (NOTCH 1). When the current position is inside this range, the status of the NOTCH
1 signal output is reversed based on the notch signal output setting.
Notch 2 Output Position Lower Limit (Pn894)
Notch 2 Output Position Upper Limit (Pn895)
Use the Notch 2 Output Position Upper/Lower Limits to set the output position range for notch signal (NOTCH 2). When the current position is inside this range, the status of the NOTCH
2 signal output is reversed based on the notch signal output setting.
4
4 -37
5
PROFIBUS-DP Communications
This chapter explains about using PROFIBUS-DP communications to execute commands and editing parameters for an NS500 Unit.
5.1 Specifications and Configuration . . . . . . . .
5.1.1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.2 Control Configuration . . . . . . . . . . . . . . . . . . . . . . . .
5.2 PROFIBUS-DP Communications
Setting Switches . . . . . . . . . . . . . . . . . . . . . .
5.2.1 Rotary Switch Settings for Setting Station Address
5.2.2 LED Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3 Command/Response Format . . . . . . . . . . . .
5.3.1 Command Format . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.2 General Command Bits and Status . . . . . . . . . . . .
5.3.3 Move command datas . . . . . . . . . . . . . . . . . . . . . . . .
5.3.4 Set/Read command datas . . . . . . . . . . . . . . . . . . . .
5.4 Motion Command Methods
5.4.1 Constant Feed Command
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
5.4.2 Step Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.3 Station Command . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.4 Point Table Command . . . . . . . . . . . . . . . . . . . . . . . .
5.4.5 Zero Point Return Command . . . . . . . . . . . . . . . . . .
5.4.6 Positioning Command . . . . . . . . . . . . . . . . . . . . . . . .
5.4.7 External Positioning . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.8 Notch Output Positioning Command . . . . . . . . . . .
5.4.9 Multi-speed Positioning Command . . . . . . . . . . . . .
5.5 Commands from the Host Controller . . . . .
5.5.1 Basic Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5.2 Command Method . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 -2
5 -2
5 -2
5 -20
5 -27
5 -27
5 -29
5 -31
5 -33
5 -34
5 -36
5 -38
5 -40
5 -3
5 -3
5 -4
5 6
5 -6
5 -7
5 -11
5 -41
5 -45
5 -45
5 -46
5 -1
5
5
PROFIBUS-DP Communications
5.1.2 Control Configuration
5.1 Specifications and Configuration
5.1.1 Specifications
The NS500 Unit is classified as a PROFIBUS-DP slave device, and can be controlled from different types of PROFIBUS-DP Master Module as a general-purpose I/O Module with 64 inputs and 64 outputs. Communications with the Master Module are cyclic; command datas are received cyclically from the Master Module and response datas are returned.
5.1.2 Control Configuration
An outline of the control configuration is shown below. A maximum of 32 NS500 Units or other slave devices can be connected to one PROFIBUS-DP Master. (The configuration can be expanded to include up to 126 stations using repeaters.)
PROFIBUS-DP Master Module
PLC or personal computer
32 stations max. (Using repeaters, up to 126 stations can be connected.)
SERVOPACK SERVOPACK Inverter Machine I/O signals
5 -2
5.2 PROFIBUS-DP Communications Setting Switches
5.2 PROFIBUS-DP Communications Setting Switches
This section explains the switch settings required for PROFIBUS-DP communications.
5.2.1 Rotary Switch Settings for Setting Station Address
Use the rotary switches ( × 1, × 10) to set the PROFIBUS-DP station address. After making the settings, cycle the communications power to enable the settings.
The station address can be set between 0 and 125. If you make a setting outside this range, a setting error will occur.
Select the station address of the NS500 Unit using the switch settings as shown in the following table.
5
5 -3
5
PROFIBUS-DP Communications
5.2.2 LED Indicators
×
0
1
2
10 ×
B
C
9
A
7
8
5
6
2
3
4
0
1
E
F
B
C
D
9
A
7
8
4
5
6
2
3
0
1
7
8
9
4
5
6
2
3
0
1
D
E
F
1
12 (18)
13 (19)
14 (20)
15 (21)
16 (22)
17 (23)
18 (24)
B (11)
C (12)
D (13)
E (14)
F (15)
10 (16)
11 (17)
Station Address
Decimal in ( )
0
1
2
3
4
5
6
7
8
9
A (10)
19 (25)
1A (26)
1B (27)
1C (28)
1D (29)
1E (30)
1F (31)
20 (32)
21 (33)
22 (34)
23 (35)
24 (36)
25 (37)
26 (38)
27 (39)
28 (40)
29 (41)
×
2
3
4
5
10 ×
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
1 Station Address
Decimal in ( )
2A (42)
2B (43)
2C (44)
2D (45)
2E (46)
2F (47)
30 (48)
31 (49)
32 (50)
33 (51)
34 (52)
35 (53)
36 (54)
37 (55)
38 (56)
39 (57)
3A (58)
3B (59)
3C (60)
3D (61)
3E (62)
3F (63)
40 (64)
41 (65)
42 (66)
43 (67)
44 (68)
45 (69)
46 (70)
47 (71)
48 (72)
49 (73)
4A (74)
4B (75)
4C (76)
4D (77)
4E (78)
4F (79)
50 (80)
51 (81)
52 (82)
53 (83)
× 10
5
6
7
× 1 Station Address
Decimal in ( )
54 (84)
55 (85)
56 (86)
57 (87)
58 (88)
59 (89)
5A (90)
5B (91)
5C (92)
5D (93)
5E (94)
5F (95)
60 (96)
61 (97)
62 (98)
63 (99)
64 (100)
65 (101)
66 (102)
67 (103)
68 (104)
69 (105)
6A (106)
6B (107)
6C (108)
6D (109)
6E (110)
6F (111)
70 (112)
71 (113)
72 (114)
73 (115)
74 (116)
75 (117)
76 (118)
77 (119)
78 (120)
79 (121)
7A (122)
7B (123)
7C (124)
7D (125)
7E (126)
Note: Setting a value of 7F or more will result in an error (A.E8). The setting 7E (126) is used by the manufacturer for setup purposes. Set station addresses in the range 0 to 125.
F
0
D
E
B
C
9
A
6
7
8
4
5
2
3
F
0
1
D
E
B
C
8
9
A
6
7
4
5
D
E
B
C
8
9
A
6
7
4
5
1
2
3
5.2.2 LED Indicators
NS500 Units are equipped with two LED indicators, the Module Error indicator (ERR) to indicate the Unit status, and the Communications Status indicator (COMM) to indicate the PROFI-
BUS-DP communications status.
5 -4
5.2 PROFIBUS-DP Communications Setting Switches
J
Module Error Indicator (ERR)
The Module Error indicator is a red LED that lights when a communications error occurs. It turns OFF while communications data is being exchanged (i.e., during normal operation). It lights at other times. The current status of the NS500 Unit is indicated, together with the Communications Status indicator (COMM), in the way shown in the table below.
J
Communications Status Indicator (COMM)
The Communications Status indicator is a red and green dual-display LED and indicates PRO-
FIBUS-DP communications errors. The current status of the NS500 Unit is indicated, together with the Module Error indicator (ERR), in the way shown in the table below.
ON
OFF
ON
ERR
Indicator Status
COMM
Lights red and green alternately.
S Performing self diagnosis
S Invalid station address setting
Flashes green slowly (flashing cycle: approx. 0.5 Hz).
Waiting for a parameter message from the Master
Flashes green
(flashing cycle:
3 Hz).
S
S
Cause
The NS500 Unit performs self diagnosis for approx. 2 seconds after power is turned ON.
A station address is set to 7F (127) or more.
Waiting for a configuration message from the Master
S At startup, the Master has not yet sent a parameter message.
S
The NS500 Unit is waiting for a parameter message sent from the Master.
The NS500 Unit has received a valid parameter message and is waiting for a configuration message.
S Normal start sequence: The NS500 Unit is in an extremely short intermediate state.
S Error status: A parameter message was received from the Master, but a configuration message has not been received.
Lights green.
Flashes red slowly
(flashing cycle: approx. 0.5 Hz).
Flashes red (flashing cycle: 3 Hz).
Lights red.
Exchanging data
Communications not established
PROFIBUS-DP watchdog timeout
NS500 Unit system error
Data is being exchanged between the Master and the Slave (normal operation).
The NS500 Unit has not detected the baud rate.
S
The communications cable is not connected properly, or is defective.
S
The Master changed the baud rate.
S
The Master’s power supply has dropped.
S
A message could not be received within the previously set bus communications time. (The status is held until a new parameter message is received.)
S Error detected by self diagnosis.
S
The system is not operating at all.
5
5 -5
5
PROFIBUS-DP Communications
5.3.1 Command Format
5.3 Command/Response Format
This section explains command sent to an NS500 Unit from the Master and the response sent from the NS500 Unit.
5.3.1 Command Format
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
This section explains the basic format of command sent to an NS500 Unit from the master device and the response sent from the NS500 Unit to the master device. Command and response are in an 8-byte data format.
0/1
Command
General command bits
Command-dependant data
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
Response
0/1 General status
Command-dependant data
Both command and response are separated into two sections. Byte 0 is a general area and bytes
1 to 7 make up the command-dependant data area. The command-dependant data area can contain one of two types of commands, move commands and set/read commands. The type of command is defined by the most-significant bit (MSB) of byte 0.
J
Format for Move Commands
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
0
Command
General command bits
Response type Command code
Command bit
Command data
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
J
Format for Set/Read Commands
0
Response
General status
Response type Command code
Status
Response data
1
0
Command
General command bits
Command code
Command number
Command data
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
1
0
Response
General status
Command code
Command number
Response dat a
5 -6
5.3 Command/Response Format
Byte
0
5.3.2
General Command Bits and Status
Bit 7
MOD
J
General Command Bits
The general command bit area is detailed below.
Table 5.1
General Command Bits
Bit 6
0
Bit 5
ALRST
Bit 4
ESTP
Bit 3
0
INFO
Bit 2
0
Bit 1
SVON
Bit 0
C_STRT
Mode: MOD
Use the MOD bit to specify the data format for bytes 1 to 7.
D 0: Move command format
D 1: Set/read command format
The MOD bit alters the data format for bytes 1 to 7. Set it carefully.
Alarm Reset Command: ALRST
Set the ALRST bit to 1 to reset the current alarm/warning. When an alarm or warning occurs in the NS500 Unit or SGDH, remove the cause of the alarm before setting this bit to 1. The alarm/warming will be cleared.
Always make sure this bit is set to 0 during normal operation and after an alarm has been cleared.
D 0: Normal operation
D 1: Alarm reset request
Emergency Stop Command: /ESTP
When the ESTP bit is changed from 1 to 0, a move command is canceled and the SGDH servo is turned OFF. If the axis is travelling, axis travel is stopped immediately and the SGDH servo is turned OFF as soon as the servomotor stops.
The ESTP Command has negative logic to confirm that PROFIBUS-DP communications have been established. Therefore, set the bit to 1 for normal operation and set it to 0 for emergency stops.
The emergency stop status will continue while this bit is set to 0. To release the emergency stop status, set the bit to 1. To turn ON the servo after releasing an emergency stop, set the Servo
ON Command bit to 0 and then set it to 1.
5 -7
5
5
PROFIBUS-DP Communications
5.3.2
General Command Bits and Status
Byte
0
D 0: Emergency stop request
D 1: Emergency stop release
Servo ON Command: SVON
Set the SVON bit to 1 to turn ON the SGDH servo. When the leading edge of the bit is detected, the SGDH servo is turned ON and remains ON while the command bit is set to 1. When the command bit setting changes to 0, the servo is turned OFF.
If an alarm turns OFF the SGDH servo, the command bit must be set to 0 and then set to 1 again.
D 0: Servo OFF request (request not to supply power to motor)
D 1: Servo ON request (request to supply power to motor)
Command Start Command: C_STRT
Set the C_STRT bit to 1 to start execution of the command specified by the command code.
Always set the command code and command area data before (or at the same time as) setting the C_STRT bit to 1.
Refer to 5.3.3 Move command datas and 5.3.4 Set/Read command datas for details on using command codes.
D 0: Normal operation
D 1: Request to start command
J
General Status
Bit 7
MOD_R
Details on the general status area are shown below.
Table 5.2
General Status Bits
Bit 6
READY
Bit 5
PWRON
Bit 4
ESTP_R
Bit 3
ALRM
Bit 2
WARN
Bit 1 Bit 0
SVON_R C_STRT_R
Mode: MOD_R
The MOD_R bit specifies the data format of bytes 1 to 7.
This bit will be the same as the mode given in the command data.
D 0: Response format for move commands
D 1: Response format for set/read commands
Module Ready: READY
The READY bit will be set to 1 when the NS500 Unit is ready to receive commands from the host device. The READY status will be 0 when the power is turned ON, and when the Module
Reset Command in the command data has been received and the NS500 Unit is initializing.
5 -8
5.3 Command/Response Format
D 0: Not ready to receive commands
D 1: Ready to receive commands
Main Power Supply Status: PWRON
The
PWRON
bit will be set to 1 when the SGDH main power supply is turned ON. If the main power supply is turned OFF, the bit will be 0 and the Servo ON and other commands cannot be executed.
D 0: Main power supply OFF
D 1: Main power supply ON
Emergency Stop: ESTP_R
The ESTP_R bit will be set to 0 when the Emergency Stop Command in the command data has been set to 0 and the NS500 Unit is in emergency stop status. Set the Emergency Stop Command in the command data to 1 to clear the emergency stop status, and this bit will change to
1.
This status has negative logic.
D 0: Emergency stop status
D 1: Not in emergency stop status
Alarm: ALRM
The ALRM bit will be set to 1 when the NS500 Unit has detected an alarm. When all alarms have been cleared by the Alarm Reset Command in the command data, this bit will change to
0.
D 0: Normal operation
D 1: Alarm has occurred
Warning: WARN
The WARN bit will be set to 1 when the NS500 Unit has detected a warning. When all warnings have been cleared by the Alarm Reset Command in the command data, this bit will change to
0.
When a warning has occurred, the command that generated the warning and commands other than data setting commands can still be executed normally.
D 0: Normal operation
D 1: Warning has occurred
Servo ON: SVON_R
The SVON_R bit will be set to 1 when the Servo ON Command in the command data is set to 1 and the SGDH servo is ON.
5 -9
5
5
PROFIBUS-DP Communications
5.3.2
General Command Bits and Status
D 0: Servo OFF (power not supplied to motor)
D 1: Servo ON (power supplied to motor)
The SVON_R bit will be 0 in the following circumstances.
D When the Servo ON Command in the command data has been set to 0
D When the Emergency Stop Command has been set to 0
D When the Module Reset Command has been set to 1
D When an alarm has occurred
Command Start Response: C_STRT_R
The C_STRT_R bit will be set to 1 when the Command Start Command in the command data has been set to 1. The host device can recognize that the NS500 Unit has received a command from the host device by checking that this bit is 1.
D 0: C_STRT not received
D 1: C_STRT received
5 -10
5.3 Command/Response Format
Byte
0
1
2
3
4
5
6
7
5.3.3
Move command datas
Bit 7
0
HOME
0
J
command datas
Details on command datas for move commands are shown below.
Bit 6
0
Bit 5
ALRST
Response type
PTBL STN
0 0
Bit 4
/ESTP
Bit 3
0
STEP
0
FEED
0
Command data
Bit 2
0
Bit 1
SVON
Command code
0 HOLD
0 DIR
Bit 0
C_STRT
CANCEL
INC
Command Codes
Command codes are used to specify positioning and other commands. To start execution of a command, set the command code and command data first (or at the same time), and then change the Command Start Command from 0 to 1.
Command Codes
0000
0001
No operation
Simple positioning
Description
0010
0011
0100
External positioning
Positioning with notch signal outputs
Multi-speed positioning
5
5 -11
5
PROFIBUS-DP Communications
5.3.3
Move command datas
Response Types
The response type in the command data specifies the type of data that will be stored as the response data in the response data. The NS500 Unit creates response data in the response datas based on the specified response type.
Response Type
0000
0001
0010
0011
0100
0101
1010
1011
Response Data
Command position (reference units)
Current position (reference units)
Position error (reference units)
Command speed (1000 reference units/min)
Current speed (1000 reference units/min)
Torque (%)
Station number
Point table number
Cancel Command: CANCEL
If the Cancel Command is set to 1 during execution of a move command, the execution of the move command will be stopped and the servomotor will decelerate to a stop. The remaining travel distance will be canceled.
If command execution is completed, the following status will occur:
• INPOS = 1
• PRGS = 0
Confirm whether or not command execution has been completed by the status of these two flags.
D 0: Execution of move command possible
D 1: Request to cancel move command
Hold Command: HOLD
If the Hold Command is set to 1 during execution of a move command, the execution of the move command will be held and the servomotor will decelerate to a stop. The NS500 Unit will wait for command execution to be restarted. Set the Hold Command to 0 again to restart the execution of a move command.
If command execution is completed, the following status will occur:
• INPOS = 1
• PRGS = 0
5 -12
5.3 Command/Response Format
Confirm whether or not command execution has been completed by the status of these two flags.
D 0: Execution of move command possible
D 1: Request to hold move command
Constant Feed Command: FEED
The NS500 Unit will start feeding at a constant speed when it detects the leading edge of the
FEED bit. Constant feeding will continue while this bit is set to 1.
When the FEED bit is set to 0, the servomotor will decelerate to a stop. The direction for feeding is determined by the Movement Direction set in the command data area.
An override can be set for this command in the command data area. The override can be from
0% to 200% of the parameter speed or a specific speed can be set in the command data. Which method is used depends on Pn830 (Constant Feed Reference Unit Selection).
Description Settings Data
Area
Movement direction
Command data
0: Forward 1: Reverse
When Pn830 = 0
When Pn830 = 1
Set an override value (0 to 200).
Set to 100 when not using the override function.
Set the feed speed.
D 0: Feed operation stop
D 1: Feed operation request
Step Command: STEP
The NS500 Unit will start step operation when it detects the leading edge of the STEP bit.
While the STEP bit is set to 1, the axis will travel only the distance set in the specified parameter. If the STEP bit is set to 0 during step operation, the servomotor will decelerate to a stop and the step operation will end. The remaining travel distance will be canceled.
The direction of movement for step operations is determined by the Movement Direction set in the command data area. The number of the step travel distance (0 to 3) is also set in the command data area. The parameter data set in Pn844 to Pn847 will be used for the step travel distance.
5
5 -13
5
PROFIBUS-DP Communications
5.3.3
Move command datas
Settings Data
Area
Movement direction
Command data
0: Forward 1: Reverse
Description
Set the selection number for step travel distance.
0: Uses Pn844 data.
1: Uses Pn845 data.
2: Uses Pn846 data.
3: Uses Pn847 data.
D 0: Step operation stop
D 1: Step operation request
Station Command: STN
The NS500 Unit will start station operation when it detects the leading edge of the STN bit.
If this command is set to 0 while the axis is travelling, the servomotor will decelerate to a stop and the station operation will end. The remaining travel distance will be cancelled.
Settings Data
Area
Movement direction
0: Forward 1: Reverse
Description
Absolute/incremental value
Specify whether the station number is an absolute value or incremental value.
Command data Specify the target station number in bytes 7 and 6.
D 0: Station operation stop
D 1: Station operation request
Point Table Command: PTBL
The NS500 Unit will start point table operation when it detects the leading edge of the PTBL bit. If this command is set to 0 while the axis is travelling, the servomotor will decelerate to a stop and the point table operation will end. The remaining travel distance will be cancelled.
Settings Data
Area
Description
Absolute/incremental value
Specify whether the position data in the point table is an absolute value or incremental value.
Command data Specify the point table number to be used in bytes 7 and 6.
5 -14
5.3 Command/Response Format
D 0: Stop point table positioning
D 1: Request for point table positioning
Zero Point Return Command: HOME
The NS500 Unit will start a zero point return when it detects the leading edge of the HOME bit. If this command is set to 0 while the axis is travelling, the servomotor will decelerate to a stop and the zero point return operation will end. The zero point return operation will not restart even if the HOME bit is set to 1 again.
The type of zero point return depends on the zero point return mode setting in Pn800.
D 0: Stop zero point return
D 1: Request for zero point return
Incremental Specification: INC
The INC bit specifies whether the data that indicates a position is used as an absolute value or an incremental value. Set this bit to 0 to specify an absolute position and to 1 to specify an incremental position.
This setting is used for the following commands.
D Station Command
D Point Table Command
D Positioning Command
The status of the INC bit cannot be changed during the execution of a move command.
D 0: Absolute value specified
D 1: Incremental value specified
Movement Direction: DIR
The DR bit specifies the movement direction. Set this bit to 0 for forward and to 1 for reverse operation.
This specification is used for the following commands.
D Feed Command
D Step Command
D Station Command
The movement direction specification is disabled during normal positioning. The status of the
DIR bit cannot be changed during the execution of a move command.
D 0: Forward
D 1: Reverse
5 -15
5
5
5
6
3
4
7
Byte
0
1
2
PROFIBUS-DP Communications
5.3.3
Move command datas
J
response datas
Bit 7
0
HOME_R
POT
The response datas for move commands are shown below.
Table 5.3
Bit 6 Bit 5
Responses for Move Commands
Bit 4 Bit 3 Bit 2
READY PWRON
Response type
PTBL_R STN_R
NOT INPOS
/ESTP_R ALRM
STEP_R
NEAR
FEED_R
HOME_P command data
Bit 1 Bit 0
WARN
0
SVON_R C_STRT_R
Command code
0 HOLD_R
DIR_R
PRGS
INC_R
Progressing Flag: PRGS
The PRGS bit is set to 1 during the execution of a command. For move commands, this flag will be set to 1 while outputting to the SGDH.
When command execution has been completed or when a Cancel Command or other stop command has been received, the Progressing Flag is set to 0.
D 0: Command execution completed
D 1: During command execution
Holding Flag: HOLD_R
The HOLD_R bit is set to 1 when a Hold Command is received from the host device and for the duration of the hold.
The host device can confirm that the NS500 Unit correctly received the Hold Command by checking that the Holding Flag is set to 1.
D 0: Hold Command not received
D 1: Hold Command received
Constant Feed Flag: FEED_R
The FEED_R bit is set to 1 when a Constant Feed Command is received from the host device and while constant feeding is being executed. When the Constant Feed Command is set to 0, this flag is also set to 0. The host device can confirm that the NS500 Unit correctly received the Constant Feed Command by checking that the Feed Flag is set to 1.
5 -16
5.3 Command/Response Format
This flag is set to 1 even if constant feeding cannot be executed because of a Servo OFF status, for example. The user must monitor for alarms during constant feeding for the Constant Feed
Command.
The movement direction during constant feeding can be checked using the Movement Direction Flag: DIR_R.
D 0: Constant Feed Command not received
D 1: Constant Feed Command received
Step Flag: STEP_R
The STEP_R bit is set to 1 when a Step Command has been received from the host device and during step operation. This flag is set to 0 when the step operation has been completed normally or cancelled. The host device can confirm that the NS500 Unit correctly received the Step
Command by checking that the Step Flag is set to 1.
This flag is set to 1 even if the step operation cannot be executed because of a Servo OFF status, for example. The user must monitor for alarms during step operation.
D 0: Step Command not received
D 1: Step Command received
Station Flag: STN_R
The STN_R bit is set to 1 when a Station Command has been received from the host device and during station operation. This flag is set to 0 when the station operation has been completed normally or cancelled. The host device can confirm that the NS500 Unit correctly received the
Station Command by checking that the Station Flag is set to 1.
This flag is set to 1 even if the station operation cannot be executed because of a Servo OFF status, for example. The user must monitor for alarms during station operation.
D 0: Station Command not received
D 1: Station Command received
Point Table Flag: PTBL_R
The PTBL_R bit is set to 1 when a Point Table Command has been received from the host device and during point table operation. This flag is set to 0 when the point table operation has been completed normally or cancelled. The host device can confirm that the NS500 Unit correctly received the Point Table Command by checking that the Point Table Flag is set to 1.
This flag is set to 1 even if the point table operation cannot be executed because of a Servo OFF status, for example. The user must monitor for alarms during point table operation.
D 0: Point Table Command not received
D 1: Point Table Command received
5 -17
5
5
PROFIBUS-DP Communications
5.3.3
Move command datas
Zero Point Return Flag: HOME_R
The HOME_R bit is set to 1 when a Zero Point Return Command has been received from the host device and during zero point return. This flag is set to 0 when the zero point return has been completed normally or cancelled. The host device can confirm that the NS500 Unit correctly received the Zero Point Return Command by checking that the Zero Point Return Flag is set to 1.
This flag is set to 1 even if the zero point return cannot be executed because of a Servo OFF status, for example. The user must monitor for alarms during zero point return.
D 0: Zero Point Return Command not received
D 1: Zero Point Return Command received
Incremental Specification Flag: INC_R
The INC_R bit receives and directly returns the status of the Incremental Specification in the command data. The host device can confirm by the change of status of this flag that the NS500
Unit has correctly received change in the incremental specification.
D 0: Absolute position specification received
D 1: Incremental position specification received
Movement Direction Flag: DIR_R
The DIR_R bit indicates the current command rotation direction for the servomotor. If the servomotor has stopped, this flag indicates the last command rotation direction. This flag is set to 0 to indicate forward, and to 1 to indicate reverse.
D 0: Forward
D 1: Reverse
Zero Point Flag: HOME_P
The HOME_P bit is set to 1 when the servomotor is within the zero point range. The zero point range is set in Pn806 (Zero Point Return Output Width ) .
When an incremental position detection system is used, this flag cannot be set to 1 for the period from when power is turned ON to the SGDH until the initial zero point return has been completed.
D 0: Outside zero point range
D 1: Within zero point range
Near Signal Flag: NEAR
The NEAR bit is set to 1 when the current position is within the On-target position range. When the current position is outside the On-target position range, the flag is set to 0. The On-target position range is set in Pn852 (Positioning Proximity Detection Width ) .
5 -18
5.3 Command/Response Format
D 0: Outside On-target position range
D 1: Within On-target position range
In-position Flag: INPOS
The INPOS bit is set to 1 when the current position is within the positioning completed range of the target position. The flag is set to 0 when the current position is outside the positioning completed range. The On-target position range is set in Pn850 (Positioning Deadband).
D 0: Outside positioning completed range
D 1: Within positioning completed range
Negative Overtravel Flag: NOT
The NOT bit indicates the status of the negative overtravel signal for the external input connected to CN1 on the SGDH.
D 0: Negative overtravel signal OFF
D 1: Negative overtravel signal ON
Positive Overtravel Flag: POT
The POT bit indicates the status of the positive overtravel signal for the external input connected to CN1 on the SGDH.
D 0: Positive overtravel signal OFF
D 1: Positive overtravel signal ON
5
5 -19
5
5
6
3
4
7
Byte
0
1
2
PROFIBUS-DP Communications
5.3.4
Set/Read command datas
5.3.4
Set/Read command datas
Bit 7
1
J
command datas
Details on bytes 1 to 7 of the command datas for set/read commands (MOD = 1) are shown below.
The response type does not need to be specified for set/read commands.
Table 5.4
Bit 6
0
Bit 5
ALRST
Set/Read Commands
Bit 4
ESTP
Bit 3
0
0
Command number
Bit 2
0
Bit 1
SVON
Command code
Bit 0
C_STRT
Command data
5 -20
5.3 Command/Response Format
Command Codes
A list of command codes is shown in the following table. Set “No operation” for commands that will not be executed.
The command codes in the response datas will basically be a copy of the command codes in the command datas. A warning for parameter setting error will be returned when the parameter number is different or the data is outside the setting range for the parameter.
Table 5.5
Command Codes
Command Code
0000 No operation
Read parameter 1000
1001
1010
Write parameter
Set current position
Description
1011
1100
1110
Set zero point
Read alarm
Reset Module
5
2
3
4
Byte
0
1
5
6
7
J
response datas
Bit 7
1
Details on bytes 1 to 7 of the response datas for set/read commands (MOD = 1) are shown below.
Table 5.6
Bit 6
READY
Bit 5
PWRON
0
Responses for Set/Read Commands
Bit 4
ESTP_R
Bit 3
ALRM
Bit 2
WARN
Bit 1 Bit 0
SVON_R C_STRT_R
Command code
Command number
Response data
5 -21
5
Byte
0
1
2
3
6
7
4
5
Byte
0
1
2
3
6
7
4
5
PROFIBUS-DP Communications
5.3.4
Set/Read command datas
Bit 7
1
J
Parameter Read Command
The Parameter Read Command reads SGDH and NS500 Unit parameters.
To use the Parameter Read Command, make the following settings and then change the Command Start Command from 0 to 1.
D Command code
D Parameter number
Table 5.7
Parameter Read Command
Bit 6
0
Bit 5
ALRST
Bit 4
ESTP
Bit 3
0
Bit 2
0
Bit 1
SVON
Bit 0
C_STRT
0 8
Parameter number
0
Bit 7
1
Table 5.8
Bit 6
READY
Bit 5
PWRON
Response for Parameter Read Command
Bit 4
ESTP_R
Bit 3
ALRM
Bit 2
WARN
Bit 1 Bit 0
SVON_R C_STRT_R
0 8
Parameter number
Parameter data
5 -22
5.3 Command/Response Format
5
6
3
4
7
Byte
0
1
2
J
Parameter Write Command
Bit 7
1
The Parameter Write Command writes SGDH and NS500 Unit parameters.
To use the Parameter Write Command, make the following settings and then change the Command Start Command from 0 to 1.
D Command code
D Parameter number
D Parameter data
Table 5.9
Parameter Write Command
Bit 6
0
Bit 5
ALRST
Bit 4
ESTP
Bit 3
0
Bit 2
0
Bit 1
SVON
Bit 0
C_STRT
0 9
Parameter number
Parameter data
5
6
3
4
7
Byte
0
1
2
Bit 7
1
Table 5.10
Bit 6
READY
Bit 5
PWRON
Response for Parameter Write Command
Bit 4
ESTP_R
Bit 3
ALRM
Bit 2
WARN
Bit 1 Bit 0
SVON_R C_STRT_R
0 9
Parameter number
Parameter data
5
5 -23
5
3
4
5
Byte
0
1
2
6
7
Byte
0
1
2
3
6
7
4
5
PROFIBUS-DP Communications
5.3.4
Set/Read command datas
Bit 7
1
J
Current Position Setting Command
The Current Position Setting Command sets the specified value as the current position of the servomotor.
To use the Current Position Setting Command, make the following settings and then change the Command Start Command from 0 to 1.
D Command code
D Current position data
Table 5.11
Current Position Setting Command
Bit 6
0
0
Bit 5
ALRST
Bit 4
ESTP
Bit 3
0
Bit 2
0
10 (decimal)
Bit 1
SVON
Bit 0
C_STRT
0
Current position data
Bit 7
1
Table 5.12
Bit 6
READY
Bit 5
PWRON
0
Response for Current Position Setting Command
Bit 4
ESTP_R
Bit 3
ALRM
Bit 2
WARN
Bit 1 Bit 0
SVON_R C_STRT_R
10 (decimal)
0
Current position data
5 -24
5.3 Command/Response Format
5
6
3
4
7
Byte
0
1
2
Bit 7
1
J
Alarm Read Command
The Alarm Read Command reads the last four alarms that have occurred on the SGDH and the
NS500 Unit.
To use the Unit Reset Command, make the command code settings and then change the Command Start Command from 0 to 1.
Table 5.13
Bit 6
0
Bit 5
ALRST
Alarm Read Command
Bit 4
ESTP
Bit 3
0
0
0
Bit 2
0
12 (decimal)
Bit 1
SVON
Bit 0
C_STRT
0
5
6
7
3
4
Byte
0
1
2
Bit 7
1
Table 5.14
Bit 6
READY
Bit 5
PWRON
0
Response for Alarm Read Command
Bit 4
ESTP_R
Bit 3
ALRM
Bit 2
WARN
Bit 1 Bit 0
SVON_R C_STRT_R
12 (decimal)
0
Last alarm code
Second last alarm code
Third last alarm code
Fourth last alarm code
5
5 -25
5
Byte
0
1
2
3
6
7
4
5
5
6
3
4
7
Byte
0
1
2
PROFIBUS-DP Communications
5.3.4
Set/Read command datas
Bit 7
1
J
Module Reset Command
The Module Reset Command restarts the SGDH and NS500 Unit software. When this command is executed, the NS500 Unit parameters are stored in flash ROM and then the NS500 Unit is restarted.
To use the Module Reset Command, make the command code settings and then change the
Command Start Command from 0 to 1.
When the NS500 Unit is executing Module Reset, the Unit Ready Flag is set to 0. When the reset has been completed, the flag is set to 1.
Table 5.15
Bit 6
0
Bit 5
ALRST
Unit Reset Command
Bit 4
ESTP
Bit 3
0
0
0
Bit 2
0
14 (decimal)
Bit 1
SVON
Bit 0
C_STRT
0
Bit 7
1
Table 5.16
Bit 6
READY
Bit 5
PWRON
0
Response for Unit Reset Command
Bit 4
ESTP_R
Bit 3
ALRM
Bit 2
WARN
Bit 1 Bit 0
SVON_R C_STRT_R
14 (decimal)
0
0
5 -26
5.4 Motion Command Methods
5.4 Motion Command Methods
5.4.1
Constant Feed Command
No.
J
Function
While the Constant Feed Command is set to 1, the axis travels in the direction specified as the movement direction at the speed specified in the parameters. Parameter settings are used for acceleration/deceleration speeds, acceleration/deceleration types, etc.
The speed during movement can be changed by changing the override value.
J
Related Parameters
Name
Pn829 Filter Selection
Pn830 Constant Feed Reference Unit Selection
Pn831 Constant Feed Speed
Pn832 Acceleration Time for Constant Feed
Pn833 Deceleration Time for Constant Feed
Pn834 Switch Speed for Constant Feed Second
Accel/Decel
Pn835 Accel/Decel Time for Constant FEED
Second Accel/Decel
1 to 10,000
1 to 10,000
1 to 240,000
1 to 10,000
Pn836 Accel/Decel Type for Constant Feed 0, 1, 2, 3
Pn840 Time Constant for Exponential Accel/Decel 4 to 1,000
Pn841 Bias Speed for Exponential Accel/Decel 1 to 240,000
Pn842 Time Constant of Travelling Average
Pn843 Maximum Feed Speed
Setting
Range
0, 1, 2, 3
0, 1
1 to 240,000
4 to 10,000
1 to 240,000
Unit
−
−
1000 steps/min ms ms
1000 steps/min ms
− ms
1000 steps/min ms
1000 steps/min
Effective
Timing
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Factory
Setting
0
0
24,000
100
100
24,000
200
0
25
0
25
24,000
Type
C
B
B
C
C
B
C
C
B
B
B
C
5
5 -27
5
PROFIBUS-DP Communications
5.4.1
Constant Feed Command
J
Operation
Speed
Pn831
Time
FEED
1
0
DIR
1
0
Byte
0
1
2
3
4
5
6
7
Bit 7
0
0
0
J
Command Method
1.
Set the Servo ON Command (byte 0, bit 1) to 1.
2.
Set the movement direction (byte 3, bit 1).
3.
Set the override value. The Pn830 setting determines whether the override will be set as a ratio (%) or as a speed (1000 steps/min).
4.
Set the Feed Command (byte 2, bit 3) to 1.
Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
1 0
0
0
0
Response type
0
0
0
1 0 0
0
0
1
0
Override value (% or 1000 steps/min)
0
0
00h
0
DIR
0
0
5 -28
5.4 Motion Command Methods
5.4.2
Step Command
J
Function
When the Step Command is set to 1, the axis will travel in the set direction for the set travel distance and then stop. The travel distance can be selected from four parameters.
J
Related Parameters
No.
Name Setting
Range
Unit
Pn821 Feed Speed for Positioning
Pn822 Acceleration Time for Positioning
Pn823 Deceleration Time for Positioning
Pn824 Switch Speed for Positioning Second
Accel/Decel
Pn825 Accel/Decel Time for Positioning Second
Accel/Decel
1 to 240,000
1 to 10,000
1 to 10,000
1 to 240,000
1 to 10,000
1000 steps/min ms ms
1000 steps/min ms
Pn826 Accel/Decel Type for Positioning
Pn829 Filter Selection
Pn840 Time Constant for Exponential Accel/Decel
Pn841 Bias Speed for Exponential Accel/Decel
Pn842
Pn843
Pn844
Pn845
Pn846
Pn847
Time Constant of Travelling Average
Maximum Feed Speed
Step Distance 1
Step Distance 2
Step Distance 3
Step Distance 4
0, 1, 2, 3
0, 1, 2, 3
4 to 1,000
1 to 240,000
4 to 10,000
1 to 240,000
± 99, 999, 999 Steps
± 99, 999, 999 Steps
± 99, 999, 999 Steps
± 99, 999, 999 Steps
−
− ms
1000 steps/min ms
1000 steps/min
Effective
Timing
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Factory
Setting
24,000
100
100
24,000
200
25
24,000
1
10
100
1,000
25
0
0
0
Type
B
B
B
B
B
C
C
B
B
B
C
C
B
C
B
5
5 -29
PROFIBUS-DP Communications
5.4.2
Step Command
J
Operation
Speed
Pn844 to Pn847
Time
5
STEP
1
0
DIR
1
0
5
6
7
Byte
0
1
2
3
4
J
Command Method
Bit 7
0
0
0
1.
Set the Servo ON Command (byte 0, bit 1) to 1.
2.
Set the movement direction (byte 3, bit 1).
3.
Select the travel distance to be used for step operation from within the range from Pn844
(=0) to Pn847 (=3).
4.
Set the Step Command (byte 2, bit 4) to 1.
Bit 0
0
Bit 6 Bit 5 Bit 4 Bit 3 Bit 2
0
0
0
Response type
0
0
0
1 0 0
1
0
0
0
Step travel distance selection (0 to 3)
0
0
00h
Bit 1
1
0
DIR
0
0
5 -30
5.4 Motion Command Methods
5.4.3
Station Command
J
Function
The Station Command can be used when the NS500 Unit is used in a rotating system.
One rotation of the servomotor is divided into a specified number of stations and station numbers are allocated.
When a station number is specified, the axis travels in the specified direction to specified position.
J
Related Parameters
No.
The same speed and acceleration/deceleration data is used as for the Positioning Command.
Name Unit Type
Pn812 Coordinate Type
Pn853 Direction for Rotation System
Pn85A Number of Stations
Setting
Range
0, 1
0, 1
1 to 32, 767
−
−
−
Effective
Timing
Immediate
Immediate
Immediate
Factory
Setting
0
0
1
C
B
B
5
J
Operation
Speed
Time
STEP
1
0
DIR
1
0
5 -31
PROFIBUS-DP Communications
5.4.3
Station Command
Station 0
Station 1
Station 2
5
Byte
0
1
2
3
4
5
6
7
Bit 7
0
0
0
J
Command Method
1.
Set the Servo ON Command (byte 0, bit 1) to 1.
2.
Set the movement direction (byte 3, bit 1).
The movement direction setting is disabled when the Pn853 setting is 1 (travel the shortest distance).
3.
Set absolute/incremental (byte 3, bit 0). If an incremental position has been specified, set the value corresponding to (target station number) − (current station number) in bytes 4 to 7.
4.
Set the target station number.
5.
Set the Station Command (byte 2, bit 5) to 1.
Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
1 0 0 1 0
0
0
0
Response type
0
1
0
0
0
0
0
Target station number
0
0
00h
0
DIR
0
INC
5 -32
5.4 Motion Command Methods
5.4.4
Point Table Command
J
Function
The Point Table Command performs positioning at the position and speed stored in advance in the point table.
J
Related Parameters
No.
Name Setting
Range
Unit
Pn821 Feed Speed for Positioning 1 to 240,000
Pn822 Acceleration Time for Positioning
Pn823 Deceleration Time for Positioning
Pn824 Switch Speed for Positioning Second Accel/
Decel
Pn825 Accel/Decel Time for Positioning Second
Accel/Decel
1 to 10,000
1 to 10,000
1 to 240,000
1 to 10,000
Pn826 Accel/Decel Type for Positioning
Pn829 Filter Selection
0, 1, 2, 3
0, 1, 2, 3
Pn840 Time Constant for Exponential Accel/Decel 4 to 1,000
Pn841 Bias Speed for Exponential Accel/Decel 1 to 240,000
Pn842
Pn843
Pn900
Pn901
Time Constant of Travelling Average
Maximum Feed Speed
Target Position 1
Target Position 2
: :
Pn931 Target Position 50
Pn980 Target Speed 1
Pn981 Target Speed 2
1000 steps/min ms ms
1000 steps/min ms
−
− ms
1000 steps/min
4 to 10,000
1 to 240,000 ms
1000 steps/min
± 99, 999, 999 Steps
± 99, 999, 999 Steps
± 99, 999, 999
1 to 240,000
1 to 240,000
Steps
1000 steps/min
1000 steps/min
: :
Pn971 Target Speed 50 1 to 240,000 1000 steps/min
5 -33
Effective
Timing
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
200
25
0
0
0
25
24,000
Factory
Setting
24,000
100
100
24,000
Type
B
C
C
B
B
C
B
B
B
C
C
0
0
B
B
Immediate
Immediate
Immediate
Immediate
0
0
0
0
B
B
B
B
5
5
PROFIBUS-DP Communications
5.4.5
Zero Point Return Command
J
Operation
Speed
Time
5
6
3
4
7
Byte
0
1
2
STEP
1
0
Bit 7
0
0
0
J
Command Method
1.
Set the Servo ON Command (byte 0, bit 1) to 1.
2.
Set absolute/incremental (byte 3, bit 0). If an incremental position has been specified, the target position will be (current position) + (position stored in point table).
3.
Set the point table number to be specified.
4.
Set the Point Table Command (byte 2, bit 6) to 1.
Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
1 0 0 1 0
1
0
0
Response type
0
0
0
0
0
0
0
Point table number to be specified
0
0
00h
0
DIR
0
INC
5.4.5
Zero Point Return Command
J
Function
The Zero Point Return Command moves the axis in the specified direction, and sets the zero point based on the specified zero point return mode.
5 -34
5.4 Motion Command Methods
When an absolute position detection system has been selected, the positioning will be performed to the zero point.
J
Related Parameters
No.
Name Setting
Range
Unit
Pn800
Pn801
Pn802
Pn803
Zero Point Return Mode
Zero Point Return Function Selection
Feed Speed for Zero Point Return
Approach Speed for Zero Point Return
0 to 3
0 to 7
1 to 240,000
1 to 240,000
−
−
1000 steps/min
1000 steps/min
Pn804 Creep Speed for Zero Point Return 1 to 240,000 1000 steps/min
Pn805 Final Travel Distance for Zero Point Return 0 to 99,999,999 Steps
Pn806 Output Width for Zero Point Return 0 to 32, 767 Steps
Pn809 Zero Point Offset Steps
Pn80A Accel/Decel Time for Zero Point Return
− 99,999,999 to
99,999,999
1 to 10,000 ms
Effective
Timing
Immediate
Power-up
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
0
100
0
100
Factory
Setting
0
1
10,000
1,000
500
Type
B
B
B
B
B
B
B
C
B
5
J
Operation
The Zero Point Return Command performs zero point return based on each zero point return mode.
Speed
Time
HOME
1
0
External signal
DEC
External signal
Encoder phase C
1
0
1
0
5 -35
5
5
6
7
Byte
0
1
2
3
4
PROFIBUS-DP Communications
5.4.6
Positioning Command
Bit 7
0
1
0
J
Command Method
Set the Servo ON Command (byte 0, bit 1) to 1.
Set the Zero Point Return Command (byte 2, bit 7) to 1.
Bit 6 Bit 5
0
0
0
Response type
0
0
0
Bit 4
1
0
0
Bit 3
0
0
0
Bit 2
0
0
0
00h
Bit 1
1
0
0
0
5.4.6
Positioning Command
J
Function
The Positioning Command performs positioning to the specified target position.
Bit 0
0
0
0
5 -36
5.4 Motion Command Methods
No.
J
Related Parameters
Name
Pn821 Feed Speed for Positioning
Setting
Range
1 to 240,000
Unit
Pn822 Acceleration Time for Positioning
Pn823 Deceleration Time for Positioning
Pn824 Switch Speed for Positioning Second Accel/
Decel
Pn825 Accel/Decel Time for Positioning Second
Accel/Decel
Pn826 Accel/Decel Type for Positioning
Pn829 Filter Selection
Pn840 Time Constant for Exponential Accel/Decel
Pn841 Bias Speed for Exponential Accel/Decel
Pn842
Pn843
Time Constant of Travelling Average
Maximum Feed Speed
1 to 10,000
1 to 10,000
1 to 240,000
1 to 10,000
0, 1, 2, 3
0, 1, 2, 3
4 to 1,000
1 to 240,000
4 to 10,000
1 to 240,000
1000 steps/min ms ms
1000 steps/min ms
−
− ms
1000 steps/min ms
1000 steps/min
J
Operation
Effective
Timing
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
200
25
0
0
0
25
24,000
Factory
Setting
24,000
100
100
24,000
Type
B
C
C
B
B
C
B
B
B
C
C
Speed
5
Time
C_STRT
1
0
J
Command Method
1.
Set the command code (byte 1, bits 0 to 3) to no operation (= 0) if it is not already set to
0.
2.
Set the Servo ON Command (byte 0, bit 1) to 1.
3.
Set absolute/incremental (byte 3, bit 0). If an incremental position has been specified, the target position will be (current position) + (position specified from bytes 4 to 7).
5 -37
5
5
6
7
Byte
0
1
2
3
4
PROFIBUS-DP Communications
5.4.7
External Positioning
Bit 7
0
0
0
4.
Set the target position in the command data (bytes 4 to 7).
5.
Set simple positioning (=1) in the command code (byte 1, bits 0 to 3).
6.
Change the Command Start Command (byte 0, bit 0) from 0 to 1.
Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1
1 0 0 1
0
0
0
Response type
0
0
0
0
0
0
0
Target position data
0
0
00h
0
0
Bit 0
1
0
0
5.4.7
External Positioning
J
Function
The External Positioning Command performs positioning at the specified target position. If the status of the external signal changes during movement, the axis will decelerate to the external positioning approach speed from the position where the status changed and travel the distance specified in the parameter.
J
Related Parameters
The same speed and acceleration/deceleration data is used as for the Positioning Command.
No.
Name
Pn854 Approach Speed for
External Positioning
Pn855 Travel Distance for
External Positioning
Setting Range Unit Effective
Timing
1 to 240,000 1,000 steps/min
0 to 99, 999, 999 Steps
Immediate
Immediate
Factory
Setting
24,000
0
Type
B
B
5 -38
5.4 Motion Command Methods
J
Operation
Speed
5
6
7
Byte
0
1
2
3
4
Time
C_STRT
1
0
EXTP signal
1
0
J
Command Method
Bit 7
0
0
0
1.
Set the command code (byte 1, bits 0 to 3) to no operation (= 0), if it is not already set to
0.
2.
Set the Servo ON Command (byte 0, bit 1) to 1.
3.
Set absolute/incremental (byte 3, bit 0). If an incremental position has been specified, the target position will be (current position) + (position specified from bytes 4 to 7).
4.
Set the target position in the command data (bytes 4 to 7).
5.
Set external positioning (=2) in the command code (byte 1, bits 0 to 3).
6.
Change the Command Start Command (byte 0, bit 0) from 0 to 1.
Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
0
0
Response type
0
0
0
1 0
0
0
0
0
Target position data
0
0
0
00h
1
0
0
1
0
0
5
5 -39
5
PROFIBUS-DP Communications
5.4.8
Notch Output Positioning Command
5.4.8
Notch Output Positioning Command
J
Function
The Notch Output Positioning Command performs positioning to the specified position.
If a specified position is passed during the positioning, a notch output signal (notch signal) will be output.
Two notch signals can be used in the NS500 Unit.
J
Related Parameters
No.
Name
0, 1
Setting
Range
Pn890 Notch Signal Output
Position Setting
Pn891 Notch Signal Output
Setting
Pn892 Notch 1 Output Position Lower Limit
Pn893 Notch 1 Output Position Upper Limit
Pn894 Notch 2 Output Position Lower Limit
Pn895 Notch 2 Output Position Upper Limit
0 to 3
−
−
± 99, 999, 999 Steps
± 99, 999, 999 Steps
± 99, 999, 999 Steps
± 99, 999, 999 Steps
Unit Effective
Timing
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Factory
Setting
0
0
0
0
0
0
Type
C
C
C
C
C
C
J
Operation
Speed
Time
C_STRT
1
0
NOTCH1
1
0
Notch output 1 position upper limit
Notch output 1 position lower limit
5 -40
5.4 Motion Command Methods
Byte
0
1
2
3
6
7
4
5
Bit 7
0
0
0
J
Command Method
1.
Set the command code (byte 1, bits 0 to 3) to no operation (= 0), if it is not already set to
0.
2.
Set the Servo ON Command (byte 0, bit 1) to 1.
3.
Set absolute/incremental (byte 3, bit 0). If an incremental position has been specified, the target position will be (current position) + (position specified from bytes 4 to 7).
4.
Set the target position in the command data (bytes 4 to 7).
5.
Set positioning with notch signal output (=3) in the command code (byte 1, bits 0 to 3).
6.
Change the Command Start Command (byte 0, bit 0) from 0 to 1.
Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
1 0 0 1 1
0
0
0
Response type
0
0
0
0
0
0
0
Target position data
0
0
00h
0
0
0
0
5
5.4.9
Multi-speed Positioning Command
J
Function
The Multi-speed Positioning Command changes the speed in stages and performs positioning to specified positions.
When the positions specified in the parameters are reached during axis travel, the axis switches to the next set speed and travels to the position specified in the next stage. Up to 16 speed switching positions can be set.
5 -41
5
PROFIBUS-DP Communications
5.4.9
Multi-speed Positioning Command
J
Related Parameters
No.
Name
Pn860 Speed Switching Position Setting
Pn861 Number of Points for Speed Switching
Pn862 Initial Feed Speed for Multi-speed Positioning
Pn863 Speed Switching Position 1
Pn864
Pn865
Pn866
Pn867
Pn868
Pn869
Pn86A
Pn86B
Pn86C
Pn86D
Pn86E
Pn86F
Pn870
Speed Switching Position 2
Speed Switching Position 3
Speed Switching Position 4
Speed Switching Position 5
Speed Switching Position 6
Speed Switching Position 7
Speed Switching Position 8
Speed Switching Position 9
Speed Switching Position 10
Speed Switching Position 11
Speed Switching Position 12
Speed Switching Position 13
Speed Switching Position 14
−
−
Setting
Range
1 to 240,000
0 to
99, 999, 999
0 to
99, 999, 999
0 to
99, 999, 999
0 to
99, 999, 999
0 to
99, 999, 999
0 to
99, 999, 999
0 to
99, 999, 999
0 to
99, 999, 999
0 to
99, 999, 999
0 to
99, 999, 999
0 to
99, 999, 999
0 to
99, 999, 999
0 to
99, 999, 999
0 to
99, 999, 999
Steps
Steps
Steps
Steps
Steps
Steps
Steps
Steps
Steps
Steps
Unit
−
−
1000 steps/min
Steps
Steps
Steps
Steps
0
0
0
0
0
0
0
0
0
0
0
0
0
Factory
Setting
0
0
0
0
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Effective
Timing
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Type
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
5 -42
No.
Name
Pn871 Speed Switching Position 15
Pn872 Speed Switching Position 16
Pn873 Switching Speed 1
Pn874 Switching Speed 2
Pn875 Switching Speed 3
Pn876 Switching Speed 4
Pn877 Switching Speed 5
Pn878 Switching Speed 6
Pn879 Switching Speed 7
Pn87A Switching Speed 8
Pn87B Switching Speed 9
Pn87C Switching Speed 10
Pn87D Switching Speed 11
Pn87E Switching Speed 12
Pn87F Switching Speed 13
Pn880 Switching Speed 14
Pn881 Switching Speed 15
Pn882 Switching Speed 16
5.4 Motion Command Methods
Setting
Range
0 to
99, 999, 999
0 to
99, 999, 999
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
1 to 240,000
Steps
Steps
Unit
1000 steps/min
1000 steps/min
1000 steps/min
1000 steps/min
1000 steps/min
1000 steps/min
1000 steps/min
1000 steps/min
1000 steps/min
1000 steps/min
1000 steps/min
1000 steps/min
1000 steps/min
1000 steps/min
1000 steps/min
1000 steps/min
24,000
24,000
24,000
24,000
24,000
24,000
24,000
24,000
Factory
Setting
0
0
24,000
24,000
24,000
24,000
24,000
24,000
24,000
24,000
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Immediate
Effective
Timing
Immediate
Immediate
Immediate
Immediate
Immediate
Type
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
5
5 -43
5
5
6
3
4
7
Byte
0
1
2
PROFIBUS-DP Communications
5.4.9
Multi-speed Positioning Command
J
Operation
Speed
Switching speed 2
Switching speed 1
Feed speed
Switching speed 3
Time
Bit 7
0
0
0
C_STRT
1
0
J
Command Method
Speed switching position 3
Speed switching position 2
Speed switching position 1
1.
Set the command code (byte 1, bits 0 to 3) to no operation (= 0), if it is not already set to
0.
2.
Set the Servo ON Command (byte 0, bit 1) to 1.
3.
Set absolute/incremental (byte 3, bit 0). If an incremental position has been specified, the target position will be (current position) + (position specified from bytes 4 to 7).
4.
Set the target position in the command data (bytes 4 to 7).
5.
Set multi-speed positioning (=4) in the command code (byte 1, bits 0 to 3).
6.
Change the Command Start Command (byte 0, bit 0) from 0 to 1.
Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
1 0 0 1 1
0
0
0
Response type
0
0
0
0
0
0
0
Target position data
0
0
00h
0
0
0
0
5 -44
5.5
Commands from the Host Controller
5.5
Commands from the Host Controller
5.5.1
Basic Sequence
Some examples of basic command sequences for the NS500 Unit are shown below.
J
Move Commands (Using Command Bit)
1.
Confirm the following conditions in the response data:
READY = 1, /ESTP_R = 1, ALRM = 0 (WARN = 0).
2.
Confirm the following conditions in the response data:
SVON_R = 1, PRGS = 0 (INPOS = 1), and the move command bit = 0.
3.
Set the command bit and command data for the move command.
4.
Check command completion using the specified position (or station number or point table number), and by confirming that PRGS = 0 and INPOS = 1.
5.
Set the move command bit to 0.
J
Move Commands (Using Command Code)
1.
Confirm the following conditions in the response data:
READY = 1, /ESTP_R = 1, ALRM = 0 (WARN = 0).
2.
Confirm the following conditions in the response data:
SVON_R = 1, PRGS = 0 (INPOS = 1), C_START = 0, and the command code = 0.
3.
Set the command data and command code for the move command, and set C_START to
1.
4.
Check command completion using the specified position (or station number or point table number), and by confirming that PRGS = 0 and INPOS = 1.
5.
Set the command code and C_START to 0.
J
Set/Read Commands
1.
Confirm that READY = 1 in the response data.
2.
Confirm that the command code = 0.
3.
Set the setting data and the command code.
4.
Check command completion using the setting data and the command code, and by confirming that C_START_R = 1 and READY = 1.
5.
Set the command code and C_START to 0.
J
Holding Move Commands
1.
Set HOLD to 1.
5 -45
5
5
PROFIBUS-DP Communications
5.5.2
Command Method
2.
Check hold status by confirming that HOLD_R = 1 and INPOS = 1 in the response data.
3.
Release the hold status by setting HOLD to 0.
J
Cancelling Move Commands
1.
Set CANCEL to 1 (or set the move command bit to 0).
2.
Check that the command has been cancelled by confirming that PRGS = 0 and INPOS =
1.
3.
Set the move command bit and CANCEL to 0.
J
Operating Sequences for Alarms
1.
If an alarm is detected (i.e., ALRM = 1), set SVON to 0 and CANCEL to 1 (or clear the move command).
2.
Read the alarm code, and remove the cause of the alarm.
3.
If the move command has not been cleared, clear the move command and set CANCEL to 0.
4.
Set ALRST to 1 and confirm that ALRM = 0.
5.
Before resuming operation, set SVON to 1 and confirm that SVON_R = 1.
J
Emergency Stop
1.
ESTP can be executed at any time while READY = 1 (except during Module Reset).
2.
To clear the stopped status, change SVON from 0 to 1 and check that SVON_R = 1 before resuming operation.
5.5.2
Command Method
For the following commands that involve movement, always wait until one command has been completed before executing another command. If commands are executed simultaneously or while the axis is travelling, a command error warning will occur (A.95).
D Feed Command
D Step Command
D Station Command
D Point Table Command
D Zero Point Return Command
D Move command based on a Command Start Command
The Emergency Stop, Servo ON, Cancel, and Hold Commands are effective any time.
J
Servo ON/OFF Command
When the Servo ON Command (SVON) is changed from 0 to 1, current is supplied to the
SGDH. When it is changed from 1 to 0, the current is not supplied.
5 -46
5.5
Commands from the Host Controller
If a PROFIBUS-DP communications error occurs, the NS500 Unit automatically enters Servo
OFF status. To restart communications, the Servo ON Command must be changed from 0 to
1.
SVON
SVON_R
Figure 5.1
Servo ON/OFF Signal
J
Emergency Stop Command
While the Emergency Stop Command (/ESTP) is set to 0, the SGDH is in emergency stop status. During this status, the Emergency Stop Flag (/ESTP_R) is 0.
The emergency stop status can be released by setting the Emergency Stop Command (/ESTP) to 1 and changing the Servo ON Command (SVON) from 0 to 1.
/ESTP
SVON
/ESTP_R
SVON_R
Figure 5.2
Emergency Stop Command
J
Alarm Reset Command
When an alarm occurs, use the following procedure to restart the NS500 Unit.
1.
Set the Servo ON Command (SVON) to 0 and set the Cancel Command (CANCEL) to 1.
2.
Remove the cause of the alarm.
3.
Clear any move commands that have been set.
4.
Execute the Alarm Reset Command.
5.
Check that the Alarm Flag (ALRM) is 0.
Alarm reset is executed by changing the Alarm Reset Command (ALRST) from 0 to 1. When execution of the alarm reset has been completed and all alarms have been cleared, the alarm bit (ALRM) will change to 0.
ALRST
ALRM
Figure 5.3
Alarm Rest Command
5 -47
5
5
PROFIBUS-DP Communications
5.5.2
Command Method
J
Constant Feed Command
While the Constant Feed Command (FEED) is set to 1, the axis travels in the direction specified as the movement direction (DIR) at the feed speed.
FEED
DIR
FEED_R
DIR_R
PRGS
Figure 5.4
Constant Feed Command
J
Step Command
While the Step Command (STEP) is set to 1, the axis travels in the direction specified as the movement direction (DIR) at the feed speed for the step travel distance.
If the Step Command is set to 0 during the step operation, the step operation stops and the remaining travel distance is canceled.
STEP
DIR
STEP_R
DIR_R
PRGS
Figure 5.5
Step Command
J
Station Command
The station operation starts when the Station Command (STN) is changed from 0 to 1. The following data must be set before the station operation is started.
D Rotation direction: Specified in the byte 3 area.
D Station number: Specified in bytes 7 and 6 of word 1.
D Absolute/incremental : Specify whether the station number is an absolute value or an incremental value.
J
Point Table Command
The point table operation starts when the Point Table Command (PTBL) is changed from 0 to
1. The following data must be set before the operation is started.
D Point table number: Specified in bytes 7 and 6 of word 1.
5 -48
5.5
Commands from the Host Controller
J
Zero Point Return Command
When the Zero Point Return Command (HOME) is changed from 0 to 1, the axis travels in the direction specified in the zero point return direction parameter. If the Zero Point Return Command is changed from 1 to 0 during zero point return, the zero point return stops. Therefore, the Zero Point Return Command must be maintained to 1 until the zero point return has been completed.
Using an Incremental Detection System
When the power is turned ON, the current position is 0 and the Zero Point Flag (HOME_P) is 0. When the zero point return has been completed, the Zero Point Flag changes to 1.
Using an Absolute Value Detection System
When the Zero Point Return Command is changed from 0 to 1, the zero point return is not performed but the axis is positioned to the machine coordinate zero point based on the zero point return feed speed parameter.
HOME
HOME_R
PRGS
HOME_P
Figure 5.6
Zero Point Return Command
5
5 -49
5
PROFIBUS-DP Communications
5.5.2
Command Method
J
Positioning Command
When the Command Start Command (C_STRT) is changed from 0 to 1, positioning starts according to the command code.
If the Hold Command (HOLD) is changed from 0 to 1 during execution of positioning, axis travel is held. Confirm that the Hold Command has been received by checking that the Holding
Flag (HOLD_R) is set to 1. Change the Hold Command from 1 to 0 to restart the remaining axis travel.
If the Cancel Command (CANCEL) is changed from 0 to 1 during execution of the positioning, the moving axis decelerates to stop and the remaining travel distance is discarded. Confirm that the Cancel Command has been received by checking that the Progressing Flag (PRGS) has changed from 1 to 0.
C_STRT
PRGS
C_STRT_R
INPOS
Figure 5.7
Positioning Command
J
Module Reset Command
The Unit is reset by setting the Module Reset Command and changing the Command Start
Command (C_STRT) from 0 to 1. When the Module Reset Command is executed, the Unit
Ready Flag (READY) is changed from 1 to 0. When NS500 Unit and SGDH reset processing has been completed, the Unit Ready Flag changes from 0 to 1.
The Unit reset operation process is outlined below.
D If the axis is travelling, it decelerates to stop and the remaining travel distance is discarded.
D If the current status is servo ON, it changes to servo OFF.
D If an alarm has occurred, the alarm is reset.
D All of the latest NS500 Unit parameters are stored in flash memory.
5 -50
6
Parameter Settings
This chapter describes parameters and standard settings for I/O signals
(CN1) when an NS500 Unit is mounted.
6.1 Parameters and Standard Settings for NS500 Units . . . . . . . . . . . . . . . . . . . . . .
6.1.1 Automatically Set Parameters . . . . . . . . . . . . . . . . .
6 -3
6 -3
6.1.2 Standard Settings for CN1 I/O Signals . . . . . . . . . .
6 -4
6.2 Settings According to
Equipment Characteristics 6 5
6.2.1 Switching Servomotor Rotation Direction . . . . . . .
6 -5
6.2.2 Stop Mode Selection at Servo OFF . . . . . . . . . . . .
6 -6
6.2.3 Fully Closed Control . . . . . . . . . . . . . . . . . . . . . . . . .
6.2.4 Fully Closed System Specifications . . . . . . . . . . . .
6.2.5 Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3 Settings According to Host Controller . . . .
6.3.1 Sequence I/O Signals . . . . . . . . . . . . . . . . . . . . . . . .
6.4 Setting Up the SERVOPACK . . . . . . . . . . . .
6.4.1 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4.2 Input Circuit Signal Allocation . . . . . . . . . . . . . . . . .
6.4.3 Output Circuit Signal Allocations . . . . . . . . . . . . . . .
6.4.4 Analog Monitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.5 Setting Stop Functions . . . . . . . . . . . . . . . . .
6.5.1 Using the Dynamic Brake . . . . . . . . . . . . . . . . . . . . .
6.5.2 Using the Holding Brake . . . . . . . . . . . . . . . . . . . . . .
6 -12
6 -13
6 -15
6 -16
6 -16
6 -17
6 -7
6 -7
6 -8
6 -10
6 -10
6 -12
6 -12
6
6 -1
6
Parameter Settings
6.6 Absolute Encoders . . . . . . . . . . . . . . . . . . . . .
6.6.1 Selecting an Absolute Encoder . . . . . . . . . . . . . . . .
6.6.2 Absolute Encoder Setup . . . . . . . . . . . . . . . . . . . . . .
6.6.3 Multiturn Limit Setting . . . . . . . . . . . . . . . . . . . . . . . .
6.7 Digital Operator . . . . . . . . . . . . . . . . . . . . . . .
6.7.1 Connecting the Digital Operator . . . . . . . . . . . . . . .
6.7.2 Limitations in Using a Hand-held Digital Operator
6.7.3 Panel Operator Indicators . . . . . . . . . . . . . . . . . . . .
6 -21
6 -21
6 -22
6 -22
6 -24
6 -24
6 -24
6 -24
6 -2
6.1 Parameters and Standard Settings for NS500 Units
6.1 Parameters and Standard Settings for NS500 Units
6.1.1 Automatically Set Parameters
When an NS500 Unit is mounted on an SGDH SERVOPACK and it is used for DeviceNet communications, the following parameters are automatically set. The following parameters will be treated as “reserved for system use,” so do not change them. The SGDH SERVOPACK will be set for position control. It is not necessary to set parameters for speed and torque control, so do not change the settings.
Pn No.
Pn000
Pn004
Pn200
Pn202
Pn203
Pn204
Pn207
Pn50A
Pn50B
Pn50C
Pn50D
Pn511
−
−
0
−
−
Digit
1
1
2
−
−
−
1
Parameter Name
Select control method
Reserved
Clear signal status
Electronic Gear Ratio
(Numerator)
Electronic Gear Ratio
(Denominator)
Position command acceleration/deceleration time constant
Select position command filter
Set Value
1
0
1
1
1
0
Description
Position control
−
Error counter is not cleared.
Electronic gear on SGDH
SERVOPACK is not used.
Electronic gear on SGDH
SERVOPACK is not used.
Time constant = 0
Select input signal 1
Select input signal 2
Select input signal 3
Select input signal 4
Select input signal 5
0
8881 jj
81
8888
8888
8
Uses the position command acceleration/deceleration filter.
Not used
Not used
Not used
Not used
Not used
6
INFO
These parameters are set automatically the first time the power to the SERVOPACK is turned ON after the
NS500 Unit has been mounted. Startup will take approximately 6 seconds when these parameters are being set.
6 -3
6
Parameter Settings
6.1.2 Standard Settings for CN1 I/O Signals
6.1.2 Standard Settings for CN1 I/O Signals
The standards settings for CN1 I/O signals when the NS500 Unit is mounted are described below.
To use the standard settings, change the parameters to the standard setting as shown below. The input signal setting from the NS500 Unit will be force-changed, so the user cannot change this setting.
Not used
DEC
P-OT
N-OT
EXTP
ZERO
Not used
SGDH SERVOPACK
CN1
40(SI0)
41(SI1)
42(SI2)
43(SI3)
44(SI4)
45(SI5)
46(SI6)
(SO1)
(SO2)
(SO3)
25
26
27
28
29
30
/COIN+
/COIN −
/BK+
/BK −
/S-RDY+
/S-RDY −
Figure 6.1
Standard CN1 I/O Signal Settings
Table 6.1 Factory Settings and Standard Settings for I/O Signals
Parameter
Pn50E
Pn50F
Pn510
Description
Output signal selections 1
Output signal selections 2
Output signal selections 3
3211
0000
0000
Factory
Setting
3001
0200
Standard
Setting
0000
6 -4
6.2 Settings According to Equipment Characteristics
6.2 Settings According to Equipment Characteristics
This section describes the procedure for setting parameters according to the dimensions and performance of the equipment used.
6.2.1 Switching Servomotor Rotation Direction
The SERVOPACK has a Reverse Rotation Mode that reverses the direction of servomotor rotation without rewiring. Forward rotation in the standard setting is defined as counterclockwise as viewed from the load.
With the Reverse Rotation Mode, the direction of servomotor rotation can be reversed without changing other items. The direction (+, − ) of shaft motion is reversed. There are no other changes.
Forward
Reference
Reverse
Reference
Standard Setting
Position data from
SERVOPACK
+ direction
Position data from
SERVOPACK
− direction
Reverse Rotation Mode
Position data from
SERVOPACK
+ direction
Position data from
SERVOPACK
− direction
J
Setting Reverse Rotation Mode
Use parameter Pn000.0.
Pn000.0
Direction Selection Factory
Setting:
0
Position Control
Use the following settings to select the direction of servomotor rotation.
Setting
0
1
Description
Forward rotation is defined as counterclockwise
(CCW) rotation as viewed from the load.
Forward rotation is defined as clockwise (CW) rotation as viewed from the load.
(Standard setting)
(Reverse Rotation
Mode)
6
6 -5
6
Parameter Settings
6.2.2 Stop Mode Selection at Servo OFF
6.2.2 Stop Mode Selection at Servo OFF
The SGDH SERVOPACK turns OFF under the following conditions:
D The SV_OFF command is transmitted.
D A servo alarm occurs.
D Power is turned OFF.
Specify the Stop Mode if any of these occurs during servomotor operation.
Pn001.0
Servo OFF Stop Mode Factory
Setting:
0
Position Control
Servo
OFF
Stop Mode
Pn001.0 = 0 or 1
Stop by dynamic brake
Pn001.0 = 2
Coast to a stop
0
After stopping
Hold with dynamic brake
1
Coast status
The dynamic brake electrically applies a brake by using a resistor to consume servomotor rotation energy.
Refer to 6.5.1 Using the Dynamic Brake.
Coast status
Parameter Setting Item
Pn001.0
0
(Factory setting)
1
2
Uses the dynamic brake to stop the servomotor, and maintains dynamic brake status after stopping.
Uses the dynamic brake to stop the servomotor, and cancels dynamic brake status after stopping to go into coast status.
Coasts the servomotor to a stop. The servomotor is turned OFF and stops due to equipment friction.
Note If the servomotor is stopped or rotating at extremely low speed when the item above is set to 0 (dynamic brake status after stopping with the dynamic brake), then braking power is not generated and the servomotor will coast to a stop the same as in coast status.
TERMS z
Dynamic brake (DB)
The dynamic brake is a common way of suddenly stopping a servomotor.
Built into the SERVOPACK, the dynamic brake suddenly stops a servomotor by electrically shorting its electrical circuit.
SERVOPACK Servomotor
6 -6
6.2 Settings According to Equipment Characteristics
6.2.3 Fully Closed Control
A fully closed loop can be formed using the parameter settings on the SGDH SERVOPACK. In previous SERVOPACKs, a semi-closed method was used to control the motor, but with this function even more precise control is achieved because control involves the detection of the position and speed of actual machine operation.
Fully closed control
Torque
Servomotor
Load torque
Mechanism including backlash and friction
Power
Speed and control at the machine end
Current Detection current
Speed, position
Controlled machine
Parameters must be set when using fully closed control. Refer to 6.2.5 Parameter Settings for details.
6.2.4 Fully Closed System Specifications
This section describes the fully closed system specifications of the SGDH SERVOPACK when an Option Unit is mounted.
J
Fully Closed Encoder Pulse Output Form
5-V Differential line driver output (complies with EIA Standard RS-422A)
J
Fully Closed Encoder Pulse Signal Form
90 ° Phase difference 2-phase differential pulse: phase A, phase B
Maximum receivable frequency for SERVOPACK: 1 Mbps
6
Phase A
Phase B t1 t2 t3 t4
Forward rotation t1,t2,t3,t4
≧ 0.2
µ s
Reverse rotation
6 -7
6
Parameter Settings
6.2.5 Parameter Settings
6.2.5 Parameter Settings
This section describes the parameters that must be set when using an Option Unit.
J
Overflow Level
For information on parameter contents, refer to 6.2.1 Servo Gain Settings of the ∑ -II Series
SGM j H/SGDH User’s Manual : Design and Maintenance (SIE-S800-32.2). The factory setting is made to minimize the chance of the motor going out of control due to wiring errors or other causes. After performing a trial operation at a low speed, change the setting to a higher value if necessary.
J
Fully Closed Encoder
Set the method for using the fully closed encoder.
Pn002.3
Fully Closed Encoder Usage Method Position Control Factory
Setting:
0
The setting details are as follows:
Parameter
Pn002.3
Setting
0
(Factory setting)
1
2
3
4
Meaning
Fully closed encoder is not used.
Fully closed encoder is used without phase C.
Fully closed encoder is used with phase C.
Fully closed encoder is used in Reverse Rotation
Mode without phase C.
Fully closed encoder is used in Reverse Rotation
Mode with phase C.
When changes have been made to this parameter, turn OFF the power once. The set value will become effective when the power is turned ON again.
6 -8
6.2 Settings According to Equipment Characteristics
J
Number of Fully Closed Encoder Pulses
Set the number of fully closed encoder pulses for each motor rotation.
When the number of fully closed encoder pulses per motor rotation is not an integer, set the closest integer.
Error will occur in the speed monitor for position loop gain, feed forward, and reference pulse, but no position displacement will occur. Set the number of pulses with a multiplication factor of 1.
Pn206 Number of Fully Closed
Encoder Pulses
Unit
P/R
Setting
Range:
513 to 32768
Factory
Setting:
16384
Position
Control
When changes have been made to this parameter, turn OFF the power once. The set value will become effective when the power is turned ON again.
6
6 -9
6
SGDH Parameters
6.
3 .
1 Sequence I/O Signals
6.3 Settings According to Host Controller
This section describes the procedure for connecting the SERVOPACK to the host controller and provides details on related parameters.
6.3.1 Sequence I/O Signals
Sequence I/O signals are used to control SERVOPACK operation. Connect these signal terminals as required.
J
Input Signal Connections
Connect the sequence input signals as shown below (standard settings).
SERVOPACK
I/O power supply
+24V
+24VIN
CN1
47 3.3k
Ω Photocoupler
Host controller
40
41
P-OT 42
N-OT 43
44
ZERO 45
EMSTOP 46
0V
IMPORTANT
Provide an external input power supply; the SERVOPACK does not have an internal 24-V power supply.
S Sequence input signal power supply specifications: 24 ± 1 VDC, 50 mA min.
Yaskawa recommends using the same external power supply as that used for output circuits. The allowable voltage range for the 24-V sequence input circuit power supply is 11 to 25 V. Although a 12-V power supply can be used, contact faults can easily occur for relays and other mechanical contacts under low currents. Confirm the characteristics of relays and other mechanical contacts before using a 12-V power supply.
6 -10
6.
3 Settings According to Host Controller
→ Input +24V IN CN1-47 24 V External I/O Power Supply Input Position Control
The external power supply input terminal is common to sequence input signals.
I/O power supply SERVOPACK
+24 V
+24 VIN
CN1-47
Sequence output signals are used to indicate SER-
VOPACK operating status.
Photocoupler output per output
Maximum operating voltage : 30 VDC
Maximum output current:
50 mA DC
Connect an external I/O power supply.
Contact input signals: DEC (CN1-41)
P-OT (CN1-42)
N-OT (CN1-43)
EXTP (CN1-44)
ZERO (CN1-45)
J
Output Signal Connections
Connect the sequence output signals as shown in the following figure (standard settings).
I/O power supply
+24 V 0 V
SERVOPACK
Photocoupler
CN1
31
50 mA max.
32
25
50 mA max.
26
27
28
29
30
/ALM+
ALM −
/COIN+
/COIN −
/BK+
/BK −
/S-RDY+
/S-RDY −
Open-collector output per output
Maximum operating voltage: 30 VDC
Maximum output current:
20 mA DC
IMPORTANT
CN1
37
20 mA max.
38
ALO1
ALO2
39 ALO3
1 SG
0 V
Host controller
0 V
Provide a separate external I/O power supply; the SERVOPACK does not have an internal 24-V power supply.
Yaskawa recommends using the same type of external power supply as that used for input circuits.
Function allocations for some sequence output signal circuits can be changed.
Refer to 6.4.3 Output Circuit Signal Allocations for more details.
6 -11
6
6
SGDH Parameters
6.4.2 Input Circuit Signal Allocation
6.4 Setting Up the SERVOPACK
This section describes the procedure for setting parameters to operate the SERVOPACK.
6.4.1 Parameters
The Σ -II Series SERVOPACK provides many functions and has parameters that allow the user to specify functions and perform fine adjustments.
SERVOPACK
Parameters
A Panel Operator, hand-held Digital Operator, or Device-
Net commands is used to set parameters.
Parameters are divided into the following three groups.
Parameter
Pn000 to Pn819
Fn000 to Fn013
Un000 to Un00D
Function
Specify SERVOPACK functions, set servo gains, etc.
Execute auxiliary functions such as FEED operations and zero point searches.
Monitor the motor speed and torque reference value on the panel display.
6.4.2 Input Circuit Signal Allocation
The allocation of the sequence input signal circuit when the NS500 Unit is mounted on the
SGDH SERVOPACK is not changed. It will be as follows:
Name Terminal
Numbers
40
41
42
43
44
45
46
SI2
SI3
SI4
SI5
SI6
Input Terminal
Name
SI0
SI1
−
DEC
Symbol
P-OT
N-OT
EXTP
ZERO
−
−
Deceleration limit switch
Forward run prohibited
Reverse run prohibited
External signal positioning
Zero point signal
−
6 -12
6.
4 Setting Up the SERVOPACK
6.4.3 Output Circuit Signal Allocations
Output signal functions can be allocated to the sequence signal output circuits shown below.
In general, allocate signals according to the standard settings in the following table.
CN1
Connector
Terminal
Numbers
25 SO1
Output
Terminal
Name
26
27
28
SO2
Factory Setting
Symbol
/COIN+
/COIN −
/TGON+
/TGON −
Name
Positioning
Rotation
Standard Setting
Symbol
/COIN+
/COIN −
/BK+
/BK −
Name
Positioning
Brake interlock
29 SO3 /S-RDY+ Servo ready /S-RDY+ Servo ready
30 /S-RDY − /S-RDY −
The following table shows the output signal selection parameters and their factory settings and standard settings.
Pn50E
Pn50F
Pn510
Output Signal Selections 1
Output Signal Selections 2
Output Signal Selections 3
Select the CN1 connector terminals that will output the signals.
Output signal
Pn50E. to Pn510.
1
2
3
Factory
Setting:
3211
Factory
Setting:
0000
Factory
Setting:
0000
SO1 (CN1-25, 26)
SO2 (CN1-27, 28)
SO3 (CN1-29, 30)
Standard
Setting:
3001
Standard
Setting:
0200
Standard
Setting:
0000
6
Output Signal
Positioning l t d
Parameter
Number Setting
Pn50E.0
2
3
0
1
Description
Disabled (Not used for the output signal on the left.)
Outputs the signal on the left from the SO1 (CN1-25 and 26) output terminal.
Outputs the signal on the left from the SO2 (CN1-27 and 28) output terminal.
Outputs the signal on the left from the SO3 (CN1-29 and 30) output terminal.
6 -13
6
SGDH Parameters
6.4.
3 Output Circuit Signal Allocations
Parameter
Number Setting
Speed
Coincidence
Detection
(/V-CMP)
Rotation
Detection
(/TGON)
Servo Ready
(/S-RDY)
Torque Limit
Detection
(/CLT)
Speed Limit
Detection
(/VLT)
Brake Interlock
(/BK)
Warning
(/WARN)
Near
(/NEAR)
Phase C
Detection
(/C-PULS)
Pn50E.1
Pn50E.2
Pn50E.3
Pn50F.0
Pn50F.1
Pn50F.2
Pn50F.3
Pn510.0
Pn510.1
0 to 3
0 to 3
0 to 3
0 to 3
0 to 3
0 to 3
0 to 3
0 to 3
0 to 3
Same as Pn50E.0*
Same as Pn50E.0
Same as Pn50E.0
Same as Pn50E.0
Same as Pn50E.0
Same as Pn50E.0
Same as Pn50E.0
Same as Pn50E.0
Same as Pn50E.0
* Always OFF when an NS500 Unit is mounted.
Note “Same as Pn50E.0” means output signals are disabled or allocated to output terminals SO1 to SO3 through parameter settings 0 to 3.
INFO
Signals are output with OR logic when multiple signals are allocated to the same output circuit. Signals that are not detected are invalid.
J
Output Signal Reversal
The following parameter can be used to reverse the signals output on output terminals SO1 to
SO3.
Pn512 Output Signal Reversal Settings Factory
Setting:
0000
Position Control
The settings specify which of the connector CN1 output signals are to be reversed.
6 -14
6.4 Setting Up the SERVOPACK
Output Terminals Parameter
Number Setting
SO1 (CN1-25, 26) Pn512.0
SO2 (CN1-27, 28) Pn512.1
0
1
0
1
SO3 (CN1-29, 30) Pn512.2
Reserved Pn512.3
0
1
−
Description
Output signal not reversed.
Output signal reversed.
Output signal not reversed.
Output signal reversed.
Output signal not reversed.
Output signal reversed.
−
6.4.4
Analog Monitors
The analog monitors can be changed by changing the PN003.0 and Pn003.1 parameter settings.
Pn003.0
Pn003.1
Analog Monitor 1
Analog Monitor 2
Factory Setting:
2
Factory Setting:
0
Position Control
Position Control
The monitor signals and units and the observation gains when observing using the analog monitor (CN5) are shown on the following table.
Pn003.0 and
Pn003.1
Settings
0
1
4
5
2
3
6
7
8 to F
Monitor Signal
Servomotor speed
Speed reference
Torque reference
Position error
Position error
Reference pulse frequency
(Servomotor speed conversion)
Servomotor speed
Servomotor speed
Reserved motor signal
Analog Monitor (CN5)
Observed Gain
1 V/1000 min -1
1 V/1000 min -1
1 V/100 % rated torque
0.05 V/1 reference units
0.05 V/100 reference units
1 V/1000 min -1
1 V/250 min -1
1 V/125 min -1
−
6
INFO
Refer to 6.5 Analog Monitors in the Σ -II Series SGM j H/SGDH User’s Manual: Design and Maintenance ( SIE-S800-32.2
) for information on monitoring methods of analog monitors.
6 -15
6
SGDH Parameters
6.
5 .
1 Using the Dynamic Brake
6.5 Setting Stop Functions
This section describes the procedure used to stably stop the SERVOPACK.
6.5.1 Using the Dynamic Brake
IMPORTANT
To stop the servomotor by applying the dynamic brake (DB), set the desired mode in the following parameter. The servomotor will stop due to equipment friction if the dynamic brake is not applied.
Pn001.0
Servo OFF or Alarm Stop Mode Factory
Setting:
0
The SERVOPACK turns OFF under the following conditions:
Position Control
D When the SV_OFF command is sent.
D A servo alarm occurs.
D Power is turned OFF.
Servo
OFF
Pn001.0 = 0 or 1
Stop mode
Dynamic brake stop
0
After stopping
Hold dynamic brake
1
Coast status
Pn001.0
= 2
Coast to a stop
Coast status
Specify the Stop Mode if any of these occurs during servomotor operation.
Pn001.0 Setting
0
Description
Uses the dynamic brake to stop the servomotor.
Maintains dynamic brake after the servomotor stops.
*1
1 Uses the dynamic brake to stop the servomotor.
Releases dynamic brake after the servomotor stops, and the servomotor coasts to a stop.
2 Coasts the servomotor to a stop.
*2
The servomotor is turned OFF and stops due to equipment friction.
* 1.
If the servomotor is stopped or moving at extremely low speed, it will coast to a stop.
* 2.
A dynamic brake is used when the control power and main power are turned OFF.
The dynamic brake is an emergency stop function. Do not repeatedly start and stop the servomotor using the
SV_ON/SV_OFF command or by repeatedly turning power ON and OFF.
6 -16
6.
5 Setting Stop Functions
6.5.2 Using the Holding Brake
The holding brake is used when a Servodrive controls a vertical axis. In other words, a servomotor with brake prevents the movable part from shifting due to gravity when system power goes
OFF.
Servomotor
Holding brake
Prevents the movable part from shifting due to gravity when system power goes OFF.
IMPORTANT
The brake built into the SGM j
H servomotor with brakes is a de-energization brake, which is used only to hold and cannot be used for braking. Use the holding brake only to hold a stopped motor. Brake torque is at least
120% of the rated servomotor torque.
J
Wiring Example
Use the SERVOPACK sequence output signal /BK and the brake power supply to form a brake
ON/OFF circuit. The following diagram shows a standard wiring example.
SERVOPACK
Servomotor with brake
Power supply
BK − RY
L1
L2
L3
L1C
L2C
U
V
W
A ( 1 )
B ( 2 )
C ( 3 )
D ( 4 )
E ( 5 )
F ( 6 )
M
BK
/BK+ CN1 − *1
+24V
/BK − CN1 − *1
CN2
PG
BK − RY
Blue or yellow
White
AC D
C
Red
Black
Brake power supply *2
BK-RY: Brake control relay
*1: The output terminal signal is allocated with Pn50F.2
*2: Brake power supplies are available in 200-V and 100-V models.
6
6 -17
6
SGDH Parameters
6.
5 .2 Using the Holding Brake
Output to /BK Brake Interlock Output Position Control
This output signal controls the brake when using a servomotor with a brake and does not have to be connected when using a servomotor without a brake.
ON: Closed or low level
OFF: Open or high level
Related Parameters
Releases the brake.
Applies the brake.
Pn005
Pn506
Pn507
Pn508
Brake operation
Time Delay from Brake Reference until Servo OFF
Speed Level for Brake Reference Output during Motor Operation
Timing for Brake Reference Output during Motor Operation
The output signal in the following parameter must be selected when the /BK signal is used.
Pn50F Output Signal Selection 2 Factory
Setting:
0000
Position Control
/BK
Brake interlock output
0
1
2
3
Pn50F.2
Input terminals
CN1-25, 26(SO1)
CN1-27, 28(SO2)
CN1-29, 30(SO3)
Select the /BK output terminal.
Parameter Setting Output Terminal (CN1)
*1 *2
Pn50F.2
0
1
2
−
25
27
−
26
28
3 29 30
Note Signals are output with OR logic when multiple signals are allocated to the same output circuit. Set other output signals to a value other than that allocated to the
/BK signal in order to output the /BK signal alone. Refer to 6.4.3 Output Circuit
Signal Allocation.
6 -18
6.5 Setting Stop Functions
J
Brake Operation
Set whether the brake is applied using the SERVOPACK parameter.
Pn005.0
Brake Operation Factory
Setting:
0
Position Control
Pn005.0 Setting
0
1
Description
Performs brake operation using the SERVOPACK parameter.
Does not perform brake operation using the SERVOPACK parameter.
IMPORTANT
When setting the Pn005.0 to 1, the SERVOPACK’s parameters (Pn506, Pn507, Pn508) settings will be ignored.
J
Brake ON Timing
If the equipment moves slightly due to gravity when the brake is applied, set the following parameter to adjust brake ON timing.
Pn506 Time Delay from Brake
Reference until Servo
OFF
Unit:
10 ms
Setting
Range:
0 to 50
Factory
Setting:
0
Position Control
This parameter is used to set the output time from the brake control output signal /BK until the servo OFF operation (servomotor output stop) when a servomotor with a brake is used.
SV_ON command
/BK output
Servo ON/OFF operation
(servomotor
ON/OFF status)
Servo ON
Servo OFF
Release brake
Hold with brake
Servomotor
ON
Servomotor OFF
Servo OFF time delay
With the standard setting, the servo is turned OFF when the /BK signal (brake operation) is output. The equipment may move slightly due to gravity depending on equipment configuration and brake characteristics. If this happens, use this parameter to delay servo OFF timing.
This setting sets the brake ON timing when the servomotor is stopped. Use Pn507 and 508 for brake ON timing during operation.
IMPORTANT
The servomotor will turn OFF immediately if an alarm occurs. The equipment may move due to gravity in the time it takes for the brake to operate.
6
6 -19
6
SGDH Parameters
6.5.2 Using the Holding Brake
J
Holding Brake Setting
Set the following parameters to adjust brake ON timing so the holding brake is applied when the servomotor stops.
Pn507 Brake Reference
Output Speed Level during Motor Operation
Unit: min -1
Pn508 Timing for Brake
Reference Output during Motor Operation
Unit:
10 ms
Setting
Range:
0 to 10000
Setting
Range:
10 to 100
Factory
Setting:
100
Factory
Setting:
50
Position Control
Position Control
Set the brake timing used when the servo is turned OFF by the SV_OFF command or when an alarm occurs during servomotor with brake operation.
SV_OFF command
Servo ON
Servo OFF
Motor speed
(min -1 )
Pn-507
Stop by dynamic brake or coast to a stop.
(Pn001.0)
/BK output
Release brake
Hold with brake
Pn508
Brake ON timing when the servomotor stops must be adjusted properly because servomotor brakes are designed as holding brakes. Adjust the parameter settings while observing equipment operation.
/BK Signal Output Conditions During Servomotor Operation
The circuit is open under either of the following conditions:
1 Motor speed drops below the setting at Pn507 after servo OFF.
2 The time set at Pn508 has elapsed since servo OFF.
The actual setting will be the maximum speed if Pn507 is set higher than the maximum speed.
6 -20
6.6 Absolute Encoders
6.6 Absolute Encoders
If a servomotor with an absolute encoder is used, a system to detect the absolute position can be made in the host controller. Consequently, operation can be performed without performing a zero point return immediately after the power is turned ON.
Motor SGM j H jjj 1 j
...With 16-bit absolute encoder
SGM j H jjj 2 j
...With 17-bit absolute encoder
Always detects absolute position.
Zero point return
Absolute encoder
6.6.1 Selecting an Absolute Encoder
Select the absolute encoder usage with the following parameter.
Pn002.2
Absolute Encoder Usage Factory
Setting:
0
“0” in the following table must be set to enable the absolute encoder.
Position Control
Pn002.2 Setting
0
Description
Use the absolute encoder as an absolute encoder.
1 Use the absolute encoder as an incremental encoder.
Note This parameter setting goes into effect when the power is turned OFF and ON again after the change has been made.
6
6 -21
6
SGDH Parameters
6.
6 .
3 Multiturn Limit Setting
6.6.2 Absolute Encoder Setup
Perform the setup operation for the absolute encoder in the following circumstances:
D When starting the machine for the first time
D When an encoder backup alarm is generated
D When the SERVOPACK’s power supply is turned OFF and the encoder’s cable is removed
Perform the setup operation in one of the following ways.
D Refer to the Σ -II Series SGM j H/SGDH User’s Manual: Design and Maintenance ( SIE-
S800-32.2
) for details on the absolute encoder setup operation (Fn008) when a Digital Operator is used.
D Setup can also be performed using personal computer monitor software.
INFO
The absolute encoder setup operation is only possible when the servo is OFF. After the setup processing is finished, turn the power OFF and then ON again.
IMPORTANT
If the following absolute encoder alarms are displayed, the alarms must be cleared using the method described above for the setup operation. They cannot be cleared using the Alarm Reset Command.
S Encoder backup alarm (A.81)
S
Encoder checksum alarm (A.82)
In addition, if a monitoring alarm is generated in the encoder, release the alarm by turning OFF the power.
6.6.3 Multiturn Limit Setting
When implementing absolute position detection systems for machines that turn m times in response to n turns in the load shaft, such as round tables, it is convenient to reset the multiturn data from the encoder to 0 every m turns. The Multiturn Limit Setting allows the value m to be set for the encoder.
Select the absolute encoder usage with the following parameter.
Pn002.2 Absolute Encoder Usage Factory Setting:
0
Position Control
Set Pn002.2 to 0 to enable the absolute encoder.
Pn002.2 Setting
0
1
Description
Uses the absolute encoder as an absolute encoder.
Uses the absolute encoder as an incremental encoder.
TERMS z
Multiturn limit
The upper limit of multiturn data. The multiturn data will vary between 0 and the value of Pn205 (multiturn limit setting) when Pn002.2 is set to 0.
6 -22
6.6 Absolute Encoders
INFO
INFO
The multiturn limit is set in the SERVOPACK using the following parameter.
Pn205 Multiturn Limit Setting Unit: rev
Setting
Range:
0 to 65535
Factory
Setting:
65535
Position Control
If the Multiturn Limit Setting is set to 65535 (factory setting), the multiturn data will vary from
− 32768 to 32767. If any other value is set, the multiturn data will vary from 0 to the setting of
Pn205.
If the servomotor rotates in the negative direction from 0, the multiturn data will change to the value set for Pn205. If the servomotor rotates in the positive direction from the value set in
Pn205, the multiturn data will change to 0. Set Pn205 to m-1.
Turn the power OFF and then ON after changing the setting of parameter Pn002.2 or Pn205.
The multiturn limit value in the encoder is factory set to 65535, the same as the SERVOPACK.
If the multiturn limit value in the SERVOPACK is changed with Pn205 and then the SERVO-
PACK power is turned OFF and ON, the following alarm will occur.
Alarm Name: Multiturn Limit Disagreement
Alarm Alarm Code Outputs
ALO1 ALO2 ALO3
Description of Alarm
A.CC
ON OFF ON The multiturn limit value is different in the encoder and SERVOPACK.
Note ON signals are low level; OFF signals are high level.
When this alarm occurs, the multiturn limit in the encoder must be changed. This operation is performed in one of the following ways.
D Refer to the Σ -II Series SGM j H/SGDH User’s Manual: Design and Maintenance ( SIE-
S800-32.2
) for details on changing the multiturn limit setting (Fn013) using a Digital Operator.
D Setup can also be performed using the personal computer monitor software.
The multiturn limit setting in the encoder can be changed only when the Multiturn Limit Disagreement alarm has occurred. After changing the setting, turn the power supply OFF and then ON.
!
WARNING The multiturn limit value must be changed only for special applications. Changing it inappropriately or unintentionally can be dangerous.
!
WARNING If the Multiturn Limit Disagreement alarm occurs, check the setting of parameter
Pn205 in the SERVOPACK to be sure that it is correct. If Fn013 is executed when an incorrect value is set in Pn205, an incorrect value will be set in the encoder. The alarm will disappear even if an incorrect value is set, but incorrect positions will be detected, resulting in a dangerous situation where the machine will move to unexpected positions.
6 -23
6
6
SGDH Parameters
6.
7 .
3 Panel Operator Indicators
6.7 Digital Operator
6.7.1 Connecting the Digital Operator
There are two types of Digital Operator. One is a built-in operator incorporating a panel indicator and switches located on the front panel of the SERVOPACK. This type of Digital Operator is also called a Panel Operator. The other one is a Hand-held Digital Operator (i.e., the JUSP-
OP02A-2 Digital Operator), which can be connected to the SERVOPACK through connector
CN3 of the SERVOPACK.
There is no need to turn OFF the SERVOPACK to connect the Hand-held Digital Operator to the SERVOPACK. For details on how to use the Hand-held Digital Operator, refer to the Σ -II
Series SGM j H/SGDH User’s Manual: Design and Maintenance ( SIE-S800-32.2
) .
6.7.2 Limitations in Using a Hand-held Digital Operator
When an NS500 Unit is mounted, the Hand-held Digital Operator has the following limitations.
INFO
Turn the power OFF and then ON after changing the setting of parameter the Pn002.2 or Pn205.
Normal Operation
The following commands are not supported when sent via PROFIBUS-DP if a Hand-held Digital
Operator is connected or communications with a personal computer are started during normal operation.
D Writing SGDH parameters
6.7.3 Panel Operator Indicators
The Panel Operator indicators (LED) will not be lit in any of the following circumstances.
1.
The indicators will not be lit for approximately 3 seconds when the power is turned ON.
2.
The indicator will not be lit when the Hand-held Digital Operator is connected.
It will be lit when the Hand-held Digital Operator is disconnected.
3.
The indicator will not be lit momentarily when the following commands are received via
PROFIBUS-DP or from a setup tool.
• Writing SGDH parameters
• Reading SGDH parameters
6 -24
7
Using the NSxxx Setup Tool
This chapter describes how to set parameters and monitor basic operation of the NS500 Unit using the NSxxx Setup Tool.
7.1 Connection and Installation
7.1.1 Connecting the NS500 Unit
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
7.1.2 Installing the Software . . . . . . . . . . . . . . . . . . . . . . .
7.2 How to Use . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2.1 Screen Configuration at Startup . . . . . . . . . . . . . . .
7.2.2 Functions Configuration . . . . . . . . . . . . . . . . . . . . . .
7 -2
7 -2
7 -2
7 -3
7 -3
7 -6
7
7 -1
Using the NSxxx Setup Tool
7.1.2 Installing the Software
7.1 Connection and Installation
7
7.1.1 Connecting the NS500 Unit
J
Connector Cables
Connect the CN11 port on the NS500 Unit and the RS-232C port on the personal computer using the following cable.
Model
DE9404559
Name
SGD Monitor Cable
J
Cable Wiring
Wire the cables as follows:
CN11
Pin number
1
2
3
4
Symbol
TXD (red)
RXD (white)
GND (black)
GND (black)
Details
Serial data output
Serial data input
Ground
Ground
Personal computer pin number (9 pins)
2
3
5
5
7.1.2 Installing the Software
The following files are stored on the floppy disk for the NSxxx Setup Tool.
D NS_MMI.EXE (Execution unit)
D ParmDef.CFG (Data files)
D RES_JPN.DLL (DLL in Japanese)
D RES_ENG.DLL (DLL in English)
D ParmDef(Jpn).CFG (Data files in Japanese)
D ParmDef(Eng).CFG (Data files in English)
Copy these files to any directory on the personal computer.
IMPORTANT
To use the files in English, copy ParmDef(Eng).CFG to ParmDef.CFG.
7 -2
7.2 How to Use
7.2 How to Use
7.2.1 Screen Configuration at Startup
Start the Setup Tool as follows:
1.
Double-click the NS_MMI.exe
file. The following communications setting screen will be displayed.
Figure 7.1
Communications setting screen
2.
Perform one of the following operations.
• If using any COM port other than COM1 on the personal computer, change the COMM
PORT setting.
• To use COM1, just click the Connect Button directly.
Next, check the following: a) The communications power supply is being supplied via the SGDH control power supply to the NS500 Unit.
b) The CN11 port on the NS500 Unit is connected to the personal computer via a communications cable.
7
7 -3
7
Using the NSxxx Setup Tool
7.2.1 Screen Configuration at Startup
The following startup screen will be displayed.
Operation window display area
Figure 7.2
Startup Screen
Status bar
The following information is normally displayed on the status bar.
• Ready
Displays whether or not the NS500 Unit is ready.
If the Unit is ready, this icon will be lit green.
• Servo ON/OFF
Displays if the SGDH servo is ON or OFF.
If the servo is ON, this icon will be lit green.
• Main Power ON
Displays if the main power supply to the SGDH is ON.
If the main power supply is being supplied normally, this icon will be lit green.
• Alarm
Displays if an alarm has occurred in the NS500 Unit or SGDH.
If an alarm has occurred, this icon will be lit red.
7 -4
7.2 How to Use
Select an item from the menu bar and make NS500 Unit settings or perform simple operation, as shown below
7
7 -5
7
Using the NSxxx Setup Tool
7.2.2 Functions Configuration
7.2.2 Functions Configuration
The functional configuration of the Setup Tool is shown in the following diagram.
Main Window
File Connect to NSxxx
Load to NSxxx
Save from NSxxx
Verify
Operate
Signal
Point Table
Parameter
Monitor
System
Help
Configuration
Constant Feed
STEP
Positioning
Point Table Positioning
Station Positioning
External Positioning
Multi-speed Positioning
Zone-signal Output Positioning
Homing Operation
Servo ON/OFF
Brake ON/OFF
List
Edit
Servo Parameter List
Option Parameter List
Motion Status
Input Signal
Output Signal
Current Position
Alarm
Alarm History
Reset Module
Read ID
Version
Connect
Point Table
Parameter
Point Table
Parameter
Point Table
Parameter
Configuration
Constant Feed
Step Operation
Positioning
Point Table Positioning
Station Positioning
External Positioning
Multi-speed Positioning
Zone-signal Output Positioning
Homing Operation
Servo ON/OFF
Brake ON/OFF
Point Table List
Edit Point Table
Servo Parameter List
Option Parameter List
Monitoring Motion Status
Monitoring Input Signal
Monitoring Output Signal
Monitoring Position
Alarm
Alarm History
Reset Module
Identity Information
Version
Point Table Loading to NSxxx
Parameter Loading to NSxxx
Point Table Saving from NSxxx
Parameter Saving from NSxxx
Verifying Point Table Data
Verifying Parameter Data
7 -6
7.2 How to Use
J
File Menu
1.
Connect to NSxxx
Starts communications with the NS500 Unit.
2.
Load to NSxxx
Loads to the NS500 Unit the parameter file stored in the personal computer.
3.
Save from NSxxx
Saves to the personal computer the parameter data or point table data within the NS500
Unit.
4.
Verify
Compares the data stored in the personal computer and the data in the NS500 Unit.
5.
Configuration
Sets the units, etc.
J
Operate Menu
1.
Constant Feed
Performs constant feed speed.
2.
STEP
Performs step operation.
3.
Positioning
Sets the target position and performs positioning.
4.
Point Table Positioning
Performs positioning based on the specified data in the point table.
5.
Station Positioning
Performs positioning to the specified station.
6.
External Positioning
Sets the target position and performs positioning. If the external signal changes, the axis moves the distance set in the parameter and then stops.
7.
Multi-speed Positioning
Performs multi-speed positioning based on the set parameters.
8.
Zone-signal Output Positioning
Performs positioning while making notch outputs based on the set parameters.
9.
Homing Operation
Performs the zero point return.
7
7 -7
7
Using the NSxxx Setup Tool
7.2.2 Functions Configuration
J
Signal Menu
1.
Servo ON/OFF
Turns ON and OFF the SGDH servo.
2.
Brake ON/OFF
Turns ON and OFF the SGDH brake signal.
J
Point Table Menu
1.
List
Displays a list of the point table currently registered.
2.
Edit
Edits the point table.
J
Parameter Menu
1.
Servo Parameter List
Displays a table of SGDH parameters, which can be edited using the cursor.
2.
Option Parameter List
Displays a table of NS500 Unit parameters, which can be edited using the cursor.
J
Monitor Menu
1.
Motion Status
Displays the current execution status.
2.
Input Signal
Displays the status of the external input signals connected to the CN1 port on the SGDH and the CN4 port on the NS500 Unit.
3.
Output Signal
Displays the status of the external output signals connected to the CN1 port on the SGDH and the CN4 port on the NS500 Unit.
4.
Current Position
Displays the current position of the servomotor in reference units.
5.
Alarm
Displays any alarms that are currently occurring. You can also clear the alarms using this function.
6.
Alarm History
Displays to a maximum of 10 the most recent alarms that have occur. You can also clear the alarm history using this function.
7 -8
7.2 How to Use
J
System Menu
1.
Reset Module
Resets the NS500 Unit and the SGDH.
When you reset the Unit, the parameters that have been changed will be stored in flash
ROM.
2.
Read ID
Displays version information for the NS500 Unit and SGDH, etc.
J
Help Menu
D Version
Displays version information for the Setup Tool.
7
7 -9
8
Ratings, Specifications, and Dimensions
This chapter provides the ratings, specifications, and dimensions of SGDH
SERVOPACKs.
8.1 Ratings and Specifications
8.2 Dimensional Drawings
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
8.2.1 NS500 Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8 -2
8 -4
8 -4
8
8 -1
Ratings, Specifications, and Dimensions
8.1 Ratings and Specifications
8
The following table lists the rating and specifications of NS500 Unit.
Table 8.1 NS500 Unit Ratings and Specifications
Item
Applicable SERVOPACK
Installation Method
Basic Specifications Power Supply
Method
PROFIBUS-DP
Communications
Command Format
Position Control
Functions
Input Signals
Output Signals
All SGDHjjj
E models
Details
Mounted on the SGDH SERVOPACK
Supplied from the SGDH control power supply.
Power Consumption 1.3 W
Consumption
Current
250 mA
External Dimensions
[mm]
20 × 142 × 128 (W × H × D)
Approx. Mass
[kg] (lb)
Baud Rate Setting
0.2 (0.441)
The baud rate is automatically set by the Master between 9.6 Kbps and 12
Mbps.
Station Address
Setting
Operation
Specifications
Reference Input
Select the address from 0 to 7D (0 to 125) using the rotary switches.
Positioning using PROFIBUS-DP communications
PROFIBUS-DP communications
Commands: Motion commands (position, speed), and reading and writing parameters
Acceleration/
Deceleration Method
Linear single/double-step, asymmetric, exponential, S-curve
Fully Closed Control Possible
Fixed Allocation to
SGDH CN1
Connector
NS500 Unit
Forward/reverse run prohibited, zero point return deceleration LS, zero point signal, external positioning signal
Emergency stop signal
Servo alarm, brake interlock, servo ready, positioning completion SGDH CN1
Connector*
NS500 Unit Notch 1, notch 2
8 -2
8.1 Ratings and Specifications
Internal Functions
Item
Position Data Latch
Function
Protection
Details
Position data latching is possible using phase C, zero point signals, and external signals.
Parameters damage, parameter setting errors, communications errors, etc.
LED Indicators ERR: Module Error
COMM: Communications Status Error
* The allocation of the following output signals can be changed using parameter settings: Brake interlock, servo ready, positioning completion.
8
8 -3
8
Ratings, Specifications, and Dimensions
8.2.1 NS500 Unit
8.2 Dimensional Drawings
Dimensional drawings of the NS500 Unit and SERVOPACKs are shown below.
8.2.1 NS500 Unit
Dimensions of the NS500 Unit are shown below.
FG terminal
M4
(24)
Connector to SERVOPACK Nameplate
CN11
NS500
6
CN6
CN4
20
133
Approx. mass: 0.2 kg (0.661 lb)
8 -4
9
Error Diagnosis and Troubleshooting
This chapter describes error diagnosis and troubleshooting.
In addition, troubleshooting procedures are described for problems which cause an alarm display and for problems which result in no alarm display.
9.1 Troubleshooting with Alarm Displays
9.2 Troubleshooting Problems
. . . . .
with No Alarm Display
9.3 Alarm Display Table
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
9.4 Warning Codes . . . . . . . . . . . . . . . . . . . . . . . .
9 -2
9 -38
9 -40
9 -43
9
9 -1
9
Error Diagnosis and Troubleshooting
9.1 Troubleshooting with Alarm Displays
Problems that occur in the Servodrives are displayed on the panel operator as “A.
VV ” or “CPF-
VV ”. “A.
− − ”, however, does not indicate an alarm. Refer to the following sections to identify the cause of an alarm and the action to be taken.
Contact your Yaskawa representative if the problem cannot be solved by the described procedures..
J
A.02
A.02: Parameter Breakdown
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO1
OFF
ALO2
OFF
Note: OFF: Output transistor is OFF (alarm state).
ALO3
OFF
Status and Remedy for Alarm
ALM Output
OFF
At power ON
A, B, C
A
B
C
Cause
Power turned OFF during parameter write.
Alarm occurred at the next power ON.
Circuit board (1PWB) is defective.
The NS500 Unit is defective.
Remedy
S Initialize parameters using Fn005 and reinput user settings.
S
Replace the SERVOPACK.
Replace the SERVOPACK.
Replace the NS500 Unit.
9 -2
9.1 Troubleshooting with Alarm Displays
J
A.03
A.03: Main Circuit Encoder Error
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO1
OFF
ALO2
OFF
Note: OFF: Output transistor is OFF (alarm state).
ALO3
OFF
Status and Remedy for Alarm
At power ON A
ALM Output
OFF
Cause Remedy
A Circuit board (1PWB or 2PWB) is defective. Replace the SERVOPACK.
J
A.04
A.04: Parameter Setting Error
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO1 ALO2
OFF OFF
Note: OFF: Output transistor is OFF (alarm state).
ALO3
OFF
Status and Remedy for Alarm
At power ON
A, B, C
ALM Output
OFF
A
B
C
Cause
An out-of-range parameter was previously set or loaded.
Circuit board (1PWB) is defective.
The NS500 Unit is defective.
Remedy
S
Reset all parameters in range.
S Otherwise, re-load the correct parameter.
Replace the SERVOPACK.
Replace the NS500 Unit.
9 -3
9
9
Error Diagnosis and Troubleshooting
J
A.05
A.05: Combination Error
Display and Outputs
ALO1
OFF
Alarm Outputs
Alarm Code Outputs
ALO2
OFF
Note: OFF: Output transistor is OFF (alarm state).
ALO3
OFF
Status and Remedy for Alarm
At power ON A, B
ALM Output
OFF
Cause Remedy
A The range of servomotor capacities that can be combined has been exceeded.
Replace the servomotor so that a suitable combination is achieved.
B Encoder parameters have not been written properly.
Replace the servomotor.
9 -4
9.1 Troubleshooting with Alarm Displays
J
A.10
A.10: Overcurrent or Heat Sink Overheated
Display and Outputs
ALO1
ON
Alarm Outputs
Alarm Code Outputs
ALO2
OFF
ALO3
OFF
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
During servomotor operation
A, B, D,
E, F, G, H
When SERVO ON
(/S-ON) signal turned ON
ALM Output
OFF
C, D
At power ON C
A
B
C
D
E
F
G
H
Cause
Wiring shorted between SERVOPACK and servomotor.
Servomotor phase U, V, or W shorted.
S
Circuit board (1PWB) is defective.
S Power transistor is defective.
Current feedback circuit, power transistor,
DB relay, or circuit board defective.
The ambient temperature of the SERVO-
PACK exceeded 55 ° C.
The air flow around the heat sink is bad.
Remedy
Check and correct wiring.
Replace the servomotor.
Replace the SERVOPACK.
Replace the SERVOPACK.
Alter conditions so that the ambient temperature goes below 55 ° C.
Follow the installation method and provide sufficient space as specified.
Replace the SERVOPACK.
Fan stopped.
SERVOPACK is operating under an overload.
Reduce load.
Note: E to H can occur with all 400-V SERVOPACK models and 200-V SERVOPACK models for 1.5 to 5 kW.
9
9 -5
9
Error Diagnosis and Troubleshooting
J
A.30
A.30: Regenerative Error Detected
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO1
ON
ALO2
ON
ALO3
OFF
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
During servomotor operation
A, B Occurred when the control power turned ON
ALM Output
D
OFF
Occurred approximately
1 second after the main circuit power ON
A, B, C
A
B
C
D
Cause
Regenerative transistor is abnormal.
Disconnection of the regenerative resistor.
Regenerative Unit disconnected
(for an external regenerative resistor).
SERVOPACK is defective.
Remedy
Replace the SERVOPACK.
Replace the SERVOPACK or regenerative resistor.
Check wiring of the external regenerative resistor.
Replace the SERVOPACK.
9 -6
9.1 Troubleshooting with Alarm Displays
J
A.32
A.32: Regenerative Overload
Display and Outputs
ALO1
ON
Alarm Outputs
Alarm Code Outputs
ALO2
ON
ALO3
OFF
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
During servomotor operation
A, B
ALM Output
OFF
Cause
A Regenerative power exceeds the allowable value.
Remedy
Use an external regenerative resistor that matches the regenerative power capacity.
B Alarm occurs although an external regenerative resistor is used and the temperature rise of the regenerative resistor is small.
Reset the incorrect Pn600 parameter setting.
9
9 -7
9
Error Diagnosis and Troubleshooting
J
A.40
A.40: Main Circuit DC Voltage Error Detected: overvoltage
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO1
OFF
ALO2
OFF
ALO3
ON
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
During servomotor operation
A, B, C, D
Occurred when the control power turned ON
ALM Output
E
OFF
Occurred when main circuit power turned ON A, D
A
B
C
D
E
Cause
The power supply voltage is not within the range of specifications.
Load exceeds capacity of the Regenerative
Unit.
Regenerative transistor is abnormal.
Rectifying diode is defective.
SERVOPACK is defective.
Remedy
Check power supply.
Check specifications of load inertia moment and overhanging load.
Replace the SERVOPACK.
9 -8
9.1 Troubleshooting with Alarm Displays
J
A.41
A.41: Main Circuit Voltage Error Detected: Undervoltage
Display and Outputs
ALO1
OFF
Alarm Outputs
Alarm Code Outputs
ALO2
OFF
ALO3
ON
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
During servomotor operation
A, B, C
Occurred when the control power turned
ON
Occurred when main circuit power turned ON
A, B, C
ALM Output
D
Cause
A The power supply voltage is not within the range of specifications.
B Fuse blown.
D Rectifying diode is defective.
E SERVOPACK is defective.
Remedy
Check power supply voltage.
Replace the SERVOPACK.
OFF
9
9 -9
9
Error Diagnosis and Troubleshooting
J
A.51
A.51: Overspeed
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO1
ON
ALO2
OFF
ALO3
ON
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
When servo ON (/S-ON) signal turned ON
A
At power ON
During high-speed servomotor rotation after reference input
B, C
ALM Output
D
OFF
A
B
C
D
Cause Remedy
Servomotor wiring is incorrect.
Check and correct wiring. (Check phase-U,
-V, and -W motor wiring errors.)
Position or speed reference input is too large. Lower the reference input values.
Incorrect reference input gain settings.
Check and correct the parameter settings.
Circuit board (1PWB) is defective.
Replace the SERVOPACK.
9 -10
9.1 Troubleshooting with Alarm Displays
J
A.71
A.71: Overload: Instantaneous Maximum Load
The alarm output, the status when LEDs are lit, and the remedy procedure are identical to those of A.72 below.
J
A.72
A.72: Overload: Continuous Maximum Load
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO2 ALO3 ALO1
ON ON ON
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
ALM Output
OFF
When servo ON (/S-ON) signal turned ON
A At power ON C
When speed reference input
No servomotor rotation
During normal operation
B
B
A
B
Cause
Servomotor wiring is incorrect or disconnected
Load greatly exceeds rated torque.
C Circuit board (1PWB) is defective.
Remedy
Check wiring and connectors at servomotor.
Reduce load torque and moment of inertia.
Otherwise, replace with larger capacity servomotor.
Replace the SERVOPACK.
9
9 -11
9
Error Diagnosis and Troubleshooting
J
A.73
A.73: Dynamic Brake Overload
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO1 ALO2 ALO3
ON ON ON
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
ALM Output
OFF
When servo OFF signal turned ON
A At power ON B
Cause
A The product of the square of rotational motor speed and the combined moment of inertia of the motor and load (rotation energy) exceeds the capacity of the dynamic brake resistor built into SERVOPACK.
B Circuit board (1PWB) is defective.
Remedy
S
Lower the rotational speed.
S Lower the load moment of inertia.
S Do not frequently use dynamic braking.
Replace the SERVOPACK.
J
A.74
A.74: Overload of Surge Current Limit Resistor
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO1 ALO2 ALO3
ON ON ON
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
ALM Output
OFF
When main circuit power turned ON or OFF
A At power ON B
Cause
A Frequently turning the main circuit power ON/
OFF.
B Circuit board (1PWB) is defective.
Remedy
Do not repeatedly turn ON/OFF the main circuit power.
Replace the SERVOPACK.
9 -12
9.1 Troubleshooting with Alarm Displays
J
A.7A
A.7A: Heat Sink Overheated
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO1
ON
ALO2
ON
ALO3
ON
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
During servomotor operation
A, B, C, D
When control power turned ON
ALM Output
E
OFF
Cause
A The ambient temperature of the SERVOPACK exceeds 55 ° C.
B The air flow around the heat sink is bad.
Remedy
Alter conditions so that the ambient temperature goes below 55 ° C.
Follow installation method and provide sufficient surrounding space as specified.
C Fan stopped.
D SERVOPACK is operating under overload.
E SERVOPACK is defective.
Replace the SERVOPACK.
Reduce load.
Replace the SERVOPACK.
Note: This alarm display tends to occur only with a SERVOPACK of 30 W to 1,000 W.
9
9 -13
9
Error Diagnosis and Troubleshooting
J
A.81
A.81: Absolute Encoder Backup Error
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO1
OFF
ALO2
OFF
Note: OFF: Output transistor is OFF (alarm state).
ALO3
OFF
Status and Remedy for Alarm
At power ON At SENS_ON command
ALM Output
OFF
A, C
Pn002.2 = 0 A, B, C
Pn002.2 = 1 C
A
B
C
Cause Remedy
The following power supplies to the absolute encoder all failed:
S
+5 V supply (supplied from SERVO-
PACK)
S Battery
Follow absolute encoder set-up procedure.
Absolute encoder malfunctioned Replace the servomotor.
Circuit board (1PWB) is defective.
Replace the SERVOPACK.
9 -14
9.1 Troubleshooting with Alarm Displays
J
A.82
A.82: Absolute Encoder Checksum Error
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO1
OFF
ALO2
OFF
Note: OFF: Output transistor is OFF (alarm state).
ALO3
OFF
Status and Remedy for Alarm
At power ON A, B
During operation
A, B
At SENS_ON command
A
Cause
Error during encoder memory check
B Circuit board (1PWB) is defective.
ALM Output
OFF
B
Remedy
S Follow absolute encoder setup procedure.
S
Replace servomotor if error occurs frequently.
Replace the SERVOPACK.
9
9 -15
9
Error Diagnosis and Troubleshooting
J
A.83
A.83: Absolute Encoder Battery Error
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO1
OFF
ALO2
OFF
Note: OFF: Output transistor is OFF (alarm state).
ALO3
OFF
Status and Remedy for Alarm
At power ON At SENS_ON command
Pn002.2 = 0
A, B, C
ALM Output
OFF
C
Pn002.2 = 1 C
A
Cause
S Battery is not connected.
S
Battery connection is defective.
Remedy
Check and correct battery connection.
B Battery voltage below specified value.
Specified value: 2.7 V
Install a new battery while the control power to SERVOPACK is ON. After replacement, turn the power OFF and ON.
C Circuit board (1 PWB) is defective.
Replace the SERVOPACK.
Note: No alarm will occur at the SERVOPACK if the battery error occurs during operation.
9 -16
9.1 Troubleshooting with Alarm Displays
J
A.84
A.84: Encoder Data Error
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO1
OFF
ALO2
OFF
Note: OFF: Output transistor is OFF (alarm state).
ALO3
OFF
Status and Remedy for Alarm
At power ON A During operation
ALM Output
OFF
B
A
B
Cause Remedy
Encoder is defective.
Replace the servomotor if the error occurs frequently.
Operational error in encoder caused by external noise.
Check and correct wiring around the encoder as follows:
S
Grounding of the servomotor
S
Separation between the encoder cable and the servomotor power cable
S
Insertion of toroidal cores onto cables
9
9 -17
9
Error Diagnosis and Troubleshooting
J
A.85
A.85: Absolute Encoder Overspeed
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO1
OFF
ALO2
OFF
Note: OFF: Output transistor is OFF (alarm state).
ALO3
OFF
Status and Remedy for Alarm
At power ON
A, B
At SENS_ON command
ALM Output
OFF
A, B
A
B
Cause
Absolute encoder turned ON at a speed exceeding 200 min -1 .
Circuit board (1PWB) is defective.
Remedy
Turn ON power supply again with the servomotor stopped.
Replace the SERVOPACK.
9 -18
9.1 Troubleshooting with Alarm Displays
J
A.86
A.86: Absolute Encoder Overheated
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO1 ALO2
OFF OFF
Note: OFF: Output transistor is OFF (alarm state).
ALO3
OFF
Status and Remedy for Alarm
During servomotor operation
A, B
At power ON
ALM Output
OFF
C, D
Cause Remedy
A The ambient temperature of the servomotor is high.
Alter conditions so that the ambient temperature goes below 40 ° C.
B Servomotor is operating under overload.
Reduce load.
C Circuit board (1PWB) is defective.
Replace the SERVOPACK.
D Encoder is defective.
Replace the servomotor.
J
A.94
A.94: Parameter Setting Error
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO1 ALO2 ALO3
ON ON OFF
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
ALM Output
ON
When the command was sent A
A
Cause
A value outside the PROFIBUS-DP communications setting range was set.
Reset correctly.
Remedy
9 -19
9
9
Error Diagnosis and Troubleshooting
J
A.95
A.95: Command Error
Display and Outputs
ALO1
OFF
Alarm Outputs
Alarm Code Outputs
ALO2
ON
ALO3
OFF
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
When the command was sent
A, B
ALM Output
ON
Cause
A
Presently unable to receive the command that has been sent.
B Unsupported command.
Remedy
Adjust conditions to match the command.
Refer to the specifications for each command.
Do not send unsupported commands.
9 -20
9.1 Troubleshooting with Alarm Displays
J
A.98
A.98: Main Power OFF
Display and Outputs
ALO1
ON
Alarm Outputs
Alarm Code Outputs
ALO2
ON
ALO3
ON
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
When main power supply
OFF
A, B
ALM Output
Cause
A
Contact between the power supply cable and the connector is faulty.
B Power Supply Unit is defective.
Remedy
Correct the connector wiring .
Check the Power Supply Unit.
ON
9
9 -21
9
Error Diagnosis and Troubleshooting
J
A.9A
A.9A: Positioning Completed Timeout (Not Completed within the Time Set in Pn851)
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO1
ON
ALO2
OFF
ALO3
ON
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
During positioning
A, B, C, D, E
ALM Output
ON
When positioning distance was short C, D
A
Cause
Positioning Completed Timeout setting
(Pn851) is too small.
B
Positioning Loop Gain or Speed Loop Gain setting is too small.
C Speed loop control is set to P control.
D Mechanical friction is high.
E The machine has hit something.
Remedy
Correct the Positioning Completed Timeout setting (Pn851).
Correct the Positioning Loop Gain or Speed
Loop Gain setting.
Set the speed loop control to PI control.
Reduce mechanical friction.
Remove any obstacles.
9 -22
9.1 Troubleshooting with Alarm Displays
J
A.b1
A.b1: Reference Speed Input Read Error
Display and Outputs
Alarm Outputs
ALO1
OFF
Alarm Code Outputs
ALO2
OFF
Note: OFF: Output transistor is OFF (alarm state).
ALO3
OFF
Status and Remedy for Alarm
During servomotor operation
A, B
At power ON
Cause
A Error in reference read-in unit
(A/D convertor, etc.)
B Reference read-in unit is defective.
(A/D convertor, etc.)
C Circuit board (1PWB) is defective.
ALM Output
OFF
C
Remedy
Reset alarm and restart operation.
Replace the SERVOPACK.
Replace the SERVOPACK.
J
A.b6
A.b6: Communications LSI Error
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO1
OFF
ALO2
OFF
Note: OFF: Output transistor is OFF (alarm state).
ALO3
OFF
Status and Remedy for Alarm
At power ON A
ALM Output
OFF
Cause
A The NS500 Unit is defective.
9 -23
Remedy
Replace the NS500 Unit.
9
9
Error Diagnosis and Troubleshooting
J
A.C1
A.C1: Servo Overrun
Display and Outputs
ALO1
Alarm Outputs
Alarm Code Outputs
ALO2 ALO3
ON OFF ON
ALM
OFF
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
At power ON When servo ON (/S-ON) signal turned ON
A, B, C, D
Parameter
Pn50A.1 = 7
D
On speed reference input
A, B, C
Occurred 1 to 3 seconds after power ON
Parameter
Pn50A.1 = Other than “7”
A, B, C, D
Cause Remedy
A Servomotor wiring incorrect or disconnected. Check the wiring and connectors at servomotor.
B Encoder wiring incorrect or disconnected.
C Encoder is defective.
D Circuit board (1PWB) is defective.
Check the wiring and connectors at encoder.
Replace the servomotor.
Replace the SERVOPACK.
9 -24
9.1 Troubleshooting with Alarm Displays
J
A.C6
A.C6: Fully-closed Encoder Phase-A, -B Disconnection
Display and Outputs
ALO1
ON
Alarm Outputs
Alarm Code Outputs
ALO2
OFF
ALO3
ON
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
At power ON
A
1 to 3 seconds after power
ON
ALM Output
OFF
A, B,
C, D
During servomotor operation
A, B,
C, D
Cause
A Circuit board (1PWB) is defective.
B Encoder wiring error or faulty contact.
C There is noise in the encoder wiring.
D Encoder is defective.
Remedy
Replace the SERVOPACK.
Check the wiring and check that the connector is fully inserted on the encoder.
Separate the encoder wiring from the main circuit.
Replace the servomotor.
9
9 -25
9
Error Diagnosis and Troubleshooting
J
A.C7
A.C7: Fully-closed Encoder Phase-C Disconnection
Display and Outputs
ALO1
ON
Alarm Outputs
Alarm Code Outputs
ALO2
OFF
ALO3
ON
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
At power ON
A
1 to 3 seconds after power ON
During servomotor operation
A, B,
C, D
Cause
A Circuit board (1PWB) is defective.
B Encoder wiring error or faulty contact.
C There is noise in the encoder wiring.
D Encoder is defective.
ALM Output
OFF
A, B,
C, D
Remedy
Replace the SERVOPACK.
Check the wiring and check that the connector is fully inserted on the encoder.
Separate the encoder wiring from the main circuit.
Replace the servomotor.
9 -26
9.1 Troubleshooting with Alarm Displays
J
A.CC
A.CC: Multiturn Limit Disagreement.
Display and Outputs
ALO1
ON
Alarm Outputs
Alarm Code Outputs
ALO2
OFF
ALO3
ON
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
At power ON
A, B
ALM Output
OFF
Cause
A The setting of the Multiturn Limit Setting
(Pn205) parameter in the SERVOPACK is incorrect.
B The multiturn limit has not been set in the encoder.
Remedy
Change parameter Pn205.
Check that the Multiturn Limit Setting
(Pn205) parameter in the SERVOPACK is correct, and then execute the encoder multiturn limit setting change (Fn013) when a
Multiturn Limit Disagreement (A.CC) occurs.
9
9 -27
9
Error Diagnosis and Troubleshooting
J
A.d0
A.d0: Position Error Pulse Overflow
Display and Outputs
Alarm Outputs
Alarm Code Outputs
ALO1
ON
ALO2
ON
ALO3
OFF
Note: OFF: Output transistor is OFF (alarm state).ON: Output transistor is ON.
Status and Remedy for Alarm
During servomotor operation
At power ON
Overflow during high-speed rotation
Operation is normal, but overflow occurs when long reference is input.
A
B, C, D
E
ALM Output
OFF
A
B
C
D
Cause Remedy
Servomotor wiring is incorrect or connection is poor.
Check wiring at servomotor.
SERVOPACK was not correctly adjusted.
Motor load was excessive.
Increase speed loop gain (Pn100) and position loop gain (Pn102).
Reduce load torque or moment of inertia. If problem not corrected, replace with a motor with larger capacity.
Position reference is too high.
S Reduce the acceleration/deceleration rate.
S Change electronic gear ratio.
9 -28
9.1 Troubleshooting with Alarm Displays
J
A.E0
A.E0: No NS500 Unit
Display and Outputs
ALO1
OFF
Alarm Outputs
Alarm Code Outputs
ALO2
ON
ALO3
ON
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
At power ON
A
Cause
A The NS500 Unit is defective.
Remedy
Replace the NS500 Unit.
ALM Output
OFF
J
A.E1
A.E1: NS500 Unit Timeout
Display and Outputs
ALO1
OFF
Alarm Outputs
Alarm Code Outputs
ALO2
ON
ALO3
ON
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
At power ON
A
Cause
A The NS500 Unit is defective.
9 -29
Remedy
Replace the NS500 Unit.
ALM Output
OFF
9
9
Error Diagnosis and Troubleshooting
J
A.E2
A.E2: Watchdog Counter Error in NS500 Unit
Display and Outputs
ALO1
OFF
Alarm Outputs
Alarm Code Outputs
ALO2
ON
ALO3
ON
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
At power ON
A
Cause
A The NS500 Unit is defective.
Remedy
Replace the NS500 Unit.
ALM Output
OFF
9 -30
9.1 Troubleshooting with Alarm Displays
J
A.E7
A.E7: NS500 Unit Detection Error when SGDH power is ON
A.E7 occurs when the SGDH is used without the NS500 Unit after it has been used with the
NS500 Unit.
Display and Outputs
ALO1
OFF
Alarm Code Outputs
ALO2
ON
Alarm Outputs
ALO3
ON
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
ALM Output
OFF
NS500 Unit detection error
A, B
Cause
A The NS500 Unit is not mounted properly.
B The NS500 Unit is not mounted.
Remedy
Check that NS500 Unit mounted correctly.
Execute Fn014 from Digital Operator.
9
9 -31
9
Error Diagnosis and Troubleshooting
J
A.EA
A.EA: SERVOPACK Malfunction
Display and Outputs
ALO1
OFF
Alarm Outputs
Alarm Code Outputs
ALO2
ON
ALO3
ON
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
At power ON
A
ALM Output
OFF
Status and Remedy for Alarm
Cause
A SERVOPACK is defective.
Remedy
Replace the SERVOPACK.
J
A.EB
A.EB: SERVOPACK Initial Access Error
Display and Outputs
ALO1
OFF
Alarm Outputs
Alarm Code Outputs
ALO2
ON
ALO3
ON
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
At power ON
A
Cause
A SERVOPACK is defective.
9 -32
Remedy
Replace the SERVOPACK.
ALM Output
OFF
9.1 Troubleshooting with Alarm Displays
J
A.EC
A.EC: SERVOPACK WDC Error
Display and Outputs
ALO1
OFF
Alarm Outputs
Alarm Code Outputs
ALO2
ON
ALO3
ON
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
At power ON
A
During PROFIBUS-DP communications
Cause Remedy
A SERVOPACK is defective.
Replace the SERVOPACK.
B PROFIBUS-DP communications interrupted. Turn the power ON again.
ALM Output
B
OFF
9
9 -33
9
Error Diagnosis and Troubleshooting
J
A.ED
A.ED: NS500 Unit Error
Display and Outputs
ALO1
OFF
Alarm Outputs
Alarm Code Outputs
ALO2
ON
ALO3
ON
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
During PROFIBUS-DP communications
A
Cause
A Command was interrupted.
ALM Output
OFF
Remedy
Do not connect a Hand-held Digital Operator or start communications with a personal computer during command execution.
9 -34
9.1 Troubleshooting with Alarm Displays
J
A.F1
A.F1: Power Line Open Phase
Display and Outputs
ALO1
Alarm Outputs
Alarm Code Outputs
ALO2 ALO3
OFF ON OFF
ALM
OFF
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
Status and Remedy for Alarm
At main circuit power supply
ON
A, B
Occurred when the control power turned ON
C
Cause
A One phase (L1, L2, or L3) of the main circuit power supply is disconnected.
Remedy
S
Check power supply.
S
Check wiring of the main circuit power supply.
S
Check QF, noise filter, magnetic contactor.
Check power supply.
B There is one phase where the line voltage is low.
C SERVOPACK is defective.
Replace the SERVOPACK.
Note: A and B tend to occur in a SERVOPACK with a capacity of 500 W or higher.
9
9 -35
9
Error Diagnosis and Troubleshooting
J
CPF00
CPF00: Digital Operator Transmission Error 1
This alarm is not stored in the alarm trace-back function memory.
Display and Outputs
ALO1
Alarm Outputs
Alarm Code Outputs
ALO2 ALO3
Not specified
ALM Output
Status and Remedy for Alarm
At power ON. Digital
Operator connected before
SERVOPACK power turned
ON.
A
B
C
D
A, B, C, D
Digital Operator connected to
SERVOPACK while power turned ON.
A, B, C, D
Cause
Cable defective or poor contact between Digital Operator and SERVOPACK
Remedy
S
Check connector connections.
S
Replace the cable.
Malfunction due to external noise
Digital Operator is defective.
SERVOPACK is defective.
Separate Digital Operator and cable from noise source.
Replace the Digital Operator.
Replace the SERVOPACK.
9 -36
9.1 Troubleshooting with Alarm Displays
J
CPF01
CPF01: Digital Operator Transmission Error 2
This alarm is not stored in the alarm trace-back function memory.
Display and Outputs
ALO1
Alarm Outputs
Alarm Code Outputs
ALO2 ALO3
Not specified
Status and Remedy for Alarm
During operation A, B, C, D
ALM Output
A
B
Cause
Cable defective or poor contact between
Digital Operator and SERVOPACK
Malfunction due to external noise
C
D
Digital Operator is defective.
SERVOPACK is defective.
Remedy
S Check connector connections.
S Replace the cable.
Separate Digital Operator and cable from noise source.
Replace the Digital Operator.
Replace the SERVOPACK.
J
A.
− −
A.
− − : Normal Operation
This is not an alarm display.
Display and Outputs
Alarm Outputs
ALO1
OFF
Alarm Code Outputs
ALO2
OFF
ALO3
OFF
Note: OFF: Output transistor is OFF (alarm state). ON: Output transistor is ON.
ALM Output
ON
9
9 -37
Error Diagnosis and Troubleshooting
9.2 Troubleshooting Problems with No Alarm Display
9
Refer to the tables below to identify the cause of a problem which causes no alarm display and take the remedy described.
Turn OFF the servo system power supply before commencing the shaded procedures.
Contact your Yaskawa representative if the problem cannot be solved by the described procedures.
Table 9.1 Troubleshooting Table with No Alarm Display
Symptom
Servomotor does not start.
Cause
Power not connected
Loose connection
Inspection
Check voltage between power supply terminals.
Remedy
Correct the power circuit.
Check terminals of connectors
(CN1, CN2).
Tighten any loose parts.
Servomotor does not run.
Servomotor moves instantaneously, then stops.
Connector (CN1) external wiring incorrect
Check connector (CN1) external wiring.
− Servomotor or encoder wiring disconnected
Overloaded.
Run under no load.
Encoder type differs from parameter setting.
P-OT and N-OT inputs are turned OFF.
Software limit reached
Motion commands have not been sent.
Servomotor or encoder wiring incorrect.
Servomotor speed unstable Wiring connection to motor is defective.
Check the type of encoder being used.
Refer to
Refer to
6.3
.
4.3.3.
Reduce load or replace with larger capacity servomotor.
Set parameter Pn002.2 to the encoder type being used.
Turn P-OT and N-OT input signals ON.
Operate the servomotor within software limits.
Check using PROFIBUS-DP communications or the PROFI-
BUS-DP monitor.
Send the motion commands.
Send Servo ON command.
− Refer to Chapter 3 Connectors and correct wiring.
Check connection of phase-U,
-V, and -W power leads encoder connectors.
Refer to connection diagram and correct wiring.
Reconnect wiring.
Tighten any loose terminals or connectors.
9 -38
9.2 Troubleshooting Problems with No Alarm Display
Symptom
Servomotor vibrates at approximately 200 to
400 Hz.
High rotation speed overshoot on starting and stopping
Servomotor overheated
Abnormal noise
Cause
Speed loop gain value is too high.
Speed loop gain value is too high.
Speed loop gain value too low compared to position loop gain value.
−
−
−
Inspection Remedy
Reduce speed loop gain
(Pn100) preset value.
Reduce speed loop gain
(Pn100) preset value.
Increase integration time constant (Pn101).
Increase speed loop gain
(Pn100) preset value.
Reduce the integration time constant (Pn101).
Ambient temperature is too high.
Servomotor surface is dirty.
Measure servomotor ambient temperature.
Visual check
Reduce ambient temperature to
40 ° C max.
Clean dust and oil from motor surface.
Overloaded Run under no load.
Reduce load or replace with larger capacity servomotor.
Mechanical mounting is incorrect.
Check if servomotor mounting screws loose.
Tighten mounting screws.
Check if coupling not centered. Center coupling.
Bearing is defective.
Machine causing vibrations
Check if coupling unbalanced. Balance coupling.
Check noise and vibration near bearing.
Consult your Yaskawa representative if defective.
Check foreign object intrusion, damage or deformation of driving parts of machine.
Consult with machine manufacturer if defective.
9
9 -39
9
Error Diagnosis and Troubleshooting
9.3 Alarm Display Table
Alarm
Display
A.02
A.03
A.04
A.05
A.10
A.30
A.32
A.40
A.41
A.51
A.71
A.72
A.73
A.74
A.7A
Alarm Code Outputs
ALO
1
ALO
2
ALO
3
OFF OFF OFF
Table 9.2 Alarm Display Table
ALM
Output
Alarm Name
OFF
ON
ON
OFF
ON
ON
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
Description
Parameter Breakdown *2 EEPROM data of SERVOPACK is abnormal.
Main Circuit Encoder Error Detection data for power circuit is abnormal.
Parameter Setting Error *2 The parameter setting is out of the allowable setting range.
Combination Error SERVOPACK and servomotor capacities do not match each other.
Overcurrent or Heat Sink
Overheated *2
An overcurrent flowed through the IGBT.
Heat sink of SERVOPACK was overheated.
Regeneration Error
S Regenerative resistor is defective.
S
Regenerative transistor is defective.
Regenerative Overload
Overvoltage
Undervoltage
Overspeed
*3
*3
Overload for Instantaneous
Maximum Load
Overload for Continuous
Maximum Load
Dynamic Brake Overload
Overload of Surge Current
Limit Resistor
Heat Sink Overheated *1
Regenerative energy exceeds regenerative resistor capacity.
Main circuit DC voltage is excessively high.
Main circuit DC voltage is excessively low.
Rotational speed of the motor is excessively high.
The motor was operating for several seconds to several tens of seconds under a torque largely exceeding ratings.
The motor was operating continuously under a torque largely exceeding rating.
When the dynamic brake was applied, rotational energy exceeded the capacity of dynamic brake resistor.
The main circuit power was frequently turned
ON and OFF.
The heat sink of SERVOPACK is overheated.
9 -40
9.3 Alarm Display Table
Alarm
Display
A.81
A.82
A.83
A.84
A.85
A.86
A.b1
A.b2
A.b6
A.bF
A.C1
A.C6
A.C7
A.C8
A.C9
A.CA
A.Cb
A.CC
A.d0
Alarm Code Outputs
ALO
1
ALO
2
ALO
3
OFF OFF OFF
ALM
Output
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
Alarm Name Description
Absolute Encoder Backup
Error *2
All the power supplies for the absolute encoder have failed and position data was cleared.
Absolute Encoder Checksum
Error *2
The checksum results of the absolute encoder memory are abnormal.
Absolute Encoder Battery
Error
Encoder Data Error *2
Battery voltage for the absolute encoder has dropped.
Data in the encoder is abnormal.
Absolute Encoder Overspeed The absolute encoder was rotating at high speed when the power was turned ON.
Encoder Overheated
Reference Speed Input Read
Error
The internal temperature of encoder is too high.
The A/D converter for reference speed input is defective.
Reference Torque Input Read
Error
The A/D converter for reference torque input is defective.
Gate Array Error
System Alarm *2
Communications LSI error
A system error occurred in the SERVOPACK.
Servo Overrun Detected The servomotor ran out of control.
Fully-closed Loop Phase-A/B
Disconnected
Phase A or B of the fully closed encoder was disconnected.
Fully-closed Loop Phase-C
Disconnected
Phase C of the fully closed encoder was disconnected.
Absolute Encoder Clear Error and Multi-turn Limit Setting
Error *2
The multi-turn for the absolute encoder was not properly cleared or set.
Encoder Communications
Error *2
Communications between SERVOPACK and encoder is not possible.
Encoder Parameter Error *2 Encoder parameters are incorrect.
Encoder Echoback Error *2 Contents of communications with encoder are incorrect.
Multi-turn Limit
Disagreement
Different multi-turn limits have been set in the encoder and SERVOPACK.
Position Error Pulse
Overflow
Position error pulse exceeded parameter (Pn505).
9
9 -41
9
Error Diagnosis and Troubleshooting
Alarm Code Outputs
ALO
1
ALO
2
ALO
3
OFF ON ON A.E0
A.E1
A.E2
A.E7
A.EA
A.EB
A.EC
A.ED
A.F1
CPF00
OFF ON
Not specified
OFF
OFF
OFF
No NS500 Unit * 2
NS500 Unit Timeout * 2
Watchdog Counter Error of
NS500 Unit * 2
No NS500 Unit installed.
No response from the NS500 Unit.
WDC error in the NS500 Unit
NS500 Unit Detection Error No NS500 Unit was detected when was power supplied to the SGDH.
SERVOPACK Malfunction* 2 SERVOPACK is defective.
Initial processing failed.
SERVOPACK Initial Access
Error * 2
SERVOPACK WDC Error
NS500 Unit Error
Power Line Open Phase
SERVOPACK WDC error
Command was interrupted.
Hand-held Digital Operator
One phase in the 3-phase main power supply is not connected.
Communications not possible between Hand-
CPF01
A.
− − OFF OFF OFF ON Not an error
SERVOPACK (CPU error)
Normal operation status.
Note: OFF: Output transistor is OFF (high). ON: Output transistor is ON (low).
* 1. This alarm display appears only within the range of 30 W to 1,000 W.
* 2. These alarms are not reset for the Alarm Reset Command. Eliminate the cause of the alarm and then turn OFF the power supply to reset the alarms.
* 3. For SERVOPACKs with a capacity of 6.0 kw or more, A.40 indicates a main circuit voltage error alarm.
This means that either an overvoltage or an undervoltage has occurred at some stage.
9 -42
9.4
Warning Codes
9.4
Warning Codes
The warning codes and the relationship between ON/OFF warning code outputs are shown on the following table.
Normally, warning codes are not output. However, if the parameters are set for warning codes to be output, those outputs will be as indicated in table 9.3.
Table 9.3
Warning Codes and Warning Code Outputs
Warning
A.91
A.92
A.94
A.95
A.98
A.9A
Warning Code Output Servo
ALO1 ALO2 ALO3
OFF ON ON
Output
ON
ON
ON
OFF
ON
ON
OFF
ON
ON
ON
OFF
ON
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
Warning Name Description
Overload This warning occurs before the overload alarms
(A.71 or A.72) occur. If the warning is ignored and operation continues, an overload alarm may occur.
Regenerative Overload This warning occurs before the regenerative overload alarm (A.32) occurs. If the warning is ignored and operation continues, a regenerative overload alarm may occur.
Parameter Setting
Warning
Command Warning
Main Power OFF
Positioning Completed
Timeout
A value outside the setting range was set using
DeviceNet communications.
A command not supported in the product specifications was issued.
The command reception conditions were not met.
The main power supply is not being supplied.
Positioning was not completed within the set time.
Note: OFF: Output transistor is OFF (high). ON: Output transistor is ON (low).
9
9 -43
A
Alarm and Warning Codes
A
This appendix lists the alarm and warning codes within DeviceNet.
A.1 Alarm Codes . . . . . . . . . . . . . . . . . . . . . . . . . .
A.2 Warning Codes . . . . . . . . . . . . . . . . . . . . . . .
A-2
A-4
A -1
A
Alarm and Warning Codes
A.1 Alarm Codes
Code
A.02
A.03
A.04
A.05
A.10
A.30
A.32
A.40
A.41
A.51
A.71
A.72
A.73
A.74
A.7A
A.81
A.82
A.83
MS
Flashes Red.
−
Lit Red.
−
Flashes Red.
−
Flashes Red.
−
Flashes Red.
−
Flashes Red.
−
Flashes Red.
−
Alarm codes are displayed on the front of the SGDH and, at the same time, can also be read as response data at the host device connected via PROFIBUS-DP. Alarms are also displayed using the
MS and NS indicators on the NS500 Unit.
The MS indicator is the module status; the NS indicator is the network status. The required indicator responses are shown in the table.
The alarm codes are shown below.
Flashes Red.
−
Flashes Red.
−
Lit Red.
−
Flashes Red.
−
Flashes Red.
−
Flashes Red.
−
Flashes Red.
−
Flashes Red.
−
Flashes Red.
−
Flashes Red.
−
Flashes Red.
−
NS
Table A.1. Alarm Codes
Alarm Name
Parameter Breakdown
Main Circuit Encoder Error
Parameter Setting Error
Description
EEPROM data of SERVOPACK is abnormal.
Detection data for power circuit is abnormal.
The parameter setting is out of the allowable setting range.
Combination Error SERVOPACK and servomotor capacities do not match each other.
Overcurrent or Heat Sink Overheated An overcurrent flowed through the IGBT.
Regeneration Error
Regenerative Overload
Overvoltage
Undervoltage
Overspeed
Overload for Instantaneous
Maximum Load
Heat sink of SERVOPACK was overheated.
S Regenerative resistor is defective.
S
Regenerative transistor is defective.
Regenerative energy exceeds regenerative resistor capacity.
Main circuit DC voltage is excessively high.
Main circuit DC voltage is excessively low.
Rotational speed of the motor is excessively high.
The motor was operating for several seconds to several tens of seconds under a torque largely exceeding ratings.
Overload for Continuous Maximum
Load
Dynamic Brake Overload
The motor was operating continuously under a torque exceeding ratings.
When the dynamic brake was applied, rotational energy exceeded the capacity of dynamic brake resistor.
The main circuit power was frequently turned
ON and OFF.
Overload of Surge Current Limit
Resistor
Heat Sink Overheated
Absolute Encoder Backup Error
The heat sink of SERVOPACK is overheated.
All the power supplies for the absolute encoder have failed and position data was cleared.
Absolute Encoder Checksum Error The checksum results of the absolute encoder memory are abnormal.
Absolute Encoder Battery Error Battery voltage for the absolute encoder has dropped.
A -2
A.1 Alarm Codes
A.EA
A.EB
A.EC
A.ED
A.EE
A.F1
A.C7
A.C8
A.C9
A.CA
A.CB
A.CC
A.D0
A.E0
A.E1
A.E2
A.E7
A.B2
A.B6
A.BF
A.C1
A.C6
Code
A.84
A.85
MS
Lit Red.
−
Flashes Red.
−
NS
A.86
A.B1
Flashes Red.
Flashes Red.
−
−
Flashes Red.
−
Flashes Red.
Flashes Red.
Flashes Red.
Flashes Red.
−
−
−
−
Flashes Red.
Lit Red.
−
−
Flashes Red.
−
Lit Red.
−
Flashes Red.
−
Flashes Red.
−
Flashes Red.
−
− −
−
−
−
−
−
Lit Red.
Flashes Red.
−
Flashes Red.
−
Flashes Red.
−
Lit Red.
−
Flashes Red.
−
Flashes Red.
−
Alarm Name
Encoder Data Error
Absolute Encoder Overspeed
Encoder Overheated
Reference Speed Input Read Error
Position Error Pulse Overflow
No NS500 Unit
NS500 Unit Timeout
Watchdog Counter Error of NS500
Unit
NS500 Unit Detection Error
Description
Data in the encoder is abnormal.
The absolute encoder was rotating at high speed when the power was turned ON.
The internal temperature of encoder is too high.
The A/D converter for reference speed input is defective.
Reference Torque Input Read Error The A/D converter for reference torque input is defective.
Gate Array Error
System Alarm
Communications LSI error
A system error occurred in the SERVOPACK.
Servo Overrun Detected
Fully-closed Loop Phase-A/B
Disconnected
Fully-closed Loop Phase-C
Disconnected
Absolute Encoder Clear Error and
Multi-turn Limit Setting Error
Encoder Communications Error
Encoder Parameter Error
Encoder Echoback Error
The servomotor ran out of control.
Phase A or B of the fully closed encoder was disconnected.
Phase C of the fully closed encoder was disconnected.
The multi-turn for the absolute encoder was not properly cleared or set.
Communications between SERVOPACK and encoder is not possible.
Encoder parameters are incorrect.
Multi-turn Limit Disagreement
Contents of communications with encoder are incorrect.
Different multi-turn limits have been set in the encoder and SERVOPACK.
Position error pulse exceeded parameter (Pn505).
No NS500 Unit installed.
No response from the NS500 Unit.
WDC error in the NS500 Unit
SERVOPACK Malfunction
SERVOPACK Initial Access Error
SERVOPACK WDC Error
NS500 Unit Error
NS500 Unit’s Parameter Error
Power Line Open Phase
No NS500 Unit was detected when was power supplied to the SGDH.
SERVOPACK is defective.
Initial processing failed.
SERVOPACK WDC error
Command was interrupted.
The parameters of the NS500 Unit contain abnormalities.
One phase in the 3-phase main power supply is not connected.
A
A -3
A
Alarm and Warning Codes
A.2 Warning Codes
Warning
Code
A.91
MS LED
Flashes Red.
−
NS LED
A.92
A.94
A.95
A.98
A.9A
The warning codes are shown below.
Flashes Red.
−
Flashes Red.
−
Flashes Red.
−
Flashes Red.
−
Flashes Red.
−
Overload
Warning Name
Regenerative Overload
Parameter Setting Warning
Command Warning
Main Power OFF
Positioning Completed Timeout
Description
This warning occurs before the overload alarms
(A.71 or A.72) occur. If the warning is ignored and operation continues, an overload alarm may occur.
This warning occurs before the regenerative overload alarm (A.32) occurs. If the warning is ignored and operation continues, a regenerative overload alarm may occur.
A value outside the setting range was set using
PROFIBUS-DP communications.
A command not supported in the product specifications was issued.
The command reception conditions were not met.
The main power supply is not being supplied.
Positioning was not completed within the set time.
A -4
No.4-3(インター) メカトロ製品用 SIE
Series SGDH
PROFIBUS-DP INTERFACE UNIT
USER'S MANUAL
IRUMA BUSINESS CENTER
480, Kamifujisawa, Iruma, Saitama 358-8555, Japan
Phone 81-42-962-5696 Fax 81-42-962-6138
YASKAWA ELECTRIC AMERICA, INC.
2121 Norman Drive South, Waukegan, IL 60085, U.S.A.
Phone 1-847-887-7000 Fax 1-847-887-7370
MOTOMAN INC. HEADQUARTERS
805 Liberty Lane West Carrollton, OH 45449, U.S.A.
Phone 1-937-847-6200 Fax 1-937-847-6277
YASKAWA ELETRICO DO BRASIL COMERCIO LTD.A.
Avenida Fagundes Filho, 620 Bairro Saude-Sao Paulo-SP, Brazil CEP: 04304-000
Phone 55-11-5071-2552 Fax 55-11-5581-8795
YASKAWA ELECTRIC EUROPE GmbH
Am Kronberger Hang 2, 65824 Schwalbach, Germany
Phone 49-6196-569-300 Fax 49-6196-569-398
Motoman Robotics Europe AB
Box 504 S38525 Torsas, Sweden
Phone 46-486-48800 Fax 46-486-41410
Motoman Robotec GmbH
Kammerfeldstra e 1, 85391 Allershausen, Germany
Phone 49-8166-90-100 Fax 49-8166-90-103
YASKAWA ELECTRIC UK LTD.
1 Hunt Hill Orchardton Woods Cumbernauld, G68 9LF, United Kingdom
Phone 44-1236-735000 Fax 44-1236-458182
YASKAWA ELECTRIC KOREA CORPORATION
Kfpa Bldg #1201, 35-4 Youido-dong, Yeongdungpo-Ku, Seoul 150-010, Korea
Phone 82-2-784-7844 Fax 82-2-784-8495
YASKAWA ELECTRIC (SINGAPORE) PTE. LTD.
151 Lorong Chuan, #04-01, New Tech Park Singapore 556741, Singapore
Phone 65-6282-3003 Fax 65-6289-3003
YASKAWA ELECTRIC (SHANGHAI) CO., LTD.
No.18 Xizang Zhong Road. Room 1805, Harbour Ring Plaza Shanghai 20000, China
Phone 86-21-5385-2200 Fax 86-21-5385-3299
YATEC ENGINEERING CORPORATION
4F., No.49 Wu Kong 6 Rd, Wu-Ku Industrial Park, Taipei, Taiwan
Phone 886-2-2298-3676 Fax 886-2-2298-3677
YASKAWA ELECTRIC (HK) COMPANY LIMITED
Rm. 2909-10, Hong Kong Plaza, 186-191 Connaught Road West, Hong Kong
Phone 852-2803-2385 Fax 852-2547-5773
BEIJING OFFICE
Room No. 301 Office Building of Beijing International Club, 21
Jianguomenwai Avenue, Beijing 100020, China
Phone 86-10-6532-1850 Fax 86-10-6532-1851
TAIPEI OFFICE
9F, 16, Nanking E. Rd., Sec. 3, Taipei, Taiwan
Phone 886-2-2502-5003 Fax 886-2-2505-1280
SHANGHAI YASKAWA-TONGJI M & E CO., LTD.
27 Hui He Road Shanghai China 200437
Phone 86-21-6553-6060 Fax 86-21-5588-1190
BEIJING YASKAWA BEIKE AUTOMATION ENGINEERING CO., LTD.
30 Xue Yuan Road, Haidian, Beijing P.R. China Post Code: 100083
Phone 86-10-6233-2782 Fax 86-10-6232-1536
SHOUGANG MOTOMAN ROBOT CO., LTD.
7, Yongchang-North Street, Beijing Economic Technological Investment & Development Area,
Beijing 100076, P.R. China
Phone 86-10-6788-0551 Fax 86-10-6788-2878
YASKAWA ELECTRIC CORPORATION
YASKAWA
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade
Regulations. Therefore, be sure to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.
© 2001-2003 YASKAWA ELECTRIC CORPORATION. All rights reserved.
MANUAL NO. SIE-C718-8
○
03-4 ③ 00-71038
2
Download
Advertisement
Key features
PROFIBUS-DP Communications
Easy to use setup tool
Supports a variety of devices and protocols
Advanced motion control features
Rugged construction
User-friendly interface
Autonomous operation
Supports absolute encoders
Digital operator
Frequently asked questions
The dimensions of the SGDH Sigma II are 110 mm x 90 mm x 40 mm.
The weight of the SGDH Sigma II is 350 g.
The operating temperature range of the SGDH Sigma II is 0 to 55 degrees Celsius.
The storage temperature range of the SGDH Sigma II is -20 to 85 degrees Celsius.
The power consumption of the SGDH Sigma II is 2.5 W.