Sloan Solis 8100 Series Flushometer Installation Instructions
Advertisement
Advertisement
Code No. 0816805
Rev. 7 (04/21)
INSTALLATION INSTRUCTIONS FOR RETROFIT AND COMPLETE VALVE
INSTALLATION FOR SLOAN SOLIS
®
, SOLAR POWERED, SINGLE FLUSH
WATER CLOSETS AND URINALS
RESS Series Retrofit Conversion Kit Models
RESS Sloan SOLIS ® Models are used to convert existing Flushometers to
Solar Powered, Sensor Activated.
8100 Series Complete Flushometer Models
8100 Series Sloan SOLIS ® valves are complete flushometers and ideal for new installations.
Sloan SOLIS ® Water Closet Models can be furnished for the following:
1.6 gpf/6.0 Lpf
3.5 gpf/13.2 Lpf
Sloan SOLIS ® Urinal Models can be furnished for the following:
1.0 gpf/3.8 Lpf
1.5 gpf/5.7 Lpf
For Low Consumption Bowls
For Water Saver Bowls
For Low Consumption Urinals
For older Siphon Jet Urinals
LIMITED WARRANTY
Unless otherwise noted, Sloan Valve Company warrants this product, manufactured and sold for commercial or industrial uses, to be free from defects in material and workmanship for a period of three (3) years (one (1) year for special finishes, SF faucets, PWT electronics and 30 days for PWT software) from date of first purchase. During this period, Sloan Valve
Company will, at its option, repair, replace, or refund the purchase price of any product which fails to conform with this warranty under normal use and service. This shall be the sole and exclusive remedy under this warranty. Products must be returned to Sloan Valve Company, at customer’s cost. No claims will be allowed for labor, transportation or other costs.
This warranty extends only to persons or organizations who purchase Sloan Valve Company’s products directly from Sloan Valve Company for purpose of resale. This warranty does not cover the life of the batteries.
THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. IN NO EVENT IS SLOAN VALVE COMPANY
RESPONSIBLE FOR ANY CONSEQUENTIAL DAMAGES OF ANY MEASURE WHATSOEVER.
PRIOR TO INSTALLING THE SLOAN SOLIS
®
FLUSHOMETER
Prior to installing the Sloan SOLIS ® flushometer, install the items listed below as illustrated in the rough-in diagram. (New installations only.)
• Closet or Urinal fixture
• Drain line
• Water supply line
IMPORTANT:
• INSTALL ALL PLUMBING IN ACCORDANCE WITH
APPLICABLE CODES AND REGULATIONS.
• WATER SUPPLY LINES MUST BE SIZED TO PROVIDE AN
ADEQUATE VOLUME OF WATER FOR EACH FIXTURE.
• WHEN INSTALLING A FLUSHOMETER, IT IS
IMPORTANT THAT THE FLUSH MODEL MATCHES THE
REQUIREMENTS OF THE PLUMBING FIXTURE.
• FLUSH ALL WATER LINES PRIOR TO MAKING
CONNECTIONS.
The Sloan SOLIS ® is designed to operate with 15 to 100 PSI (104 to 689 kPa) of water pressure. THE MINIMUM PRESSURE REQUIRED
TO THE VALVE IS DETERMINED BY THE TYPE OF FIXTURE
SELECTED.
Consult fixture manufacturer for pressure requirements.
Most Low Consumption water closets (1.6 gallon/6 liter) require a minimum flowing pressure of 25 psi (172 kPa).
TOOLS REQUIRED FOR INSTALLATION
• Slotted screwdriver to adjust control stop.
• Sloan A-50 Super-Wrench™, Sloan A-109 Plier Wrench or smooth jawed spud wrench for couplings.
• Trimpot adjustment screwdriver (supplied) to adjust range, if necessary.
• Strap wrench (supplied) to install Sloan SOLIS ® to valve body.
• 7/64” hex wrench (supplied) to secure Sloan SOLIS ® cover to base plate.
• 5/64” hex wrench to secure water Supply Flange.
VALVE ROUGH-IN
Typical Urinal Installation
Models 8180 & 8186
Reference for RESS-U Retrofit
‡
† For new installations, Sloan strongly recommends the use of our Model 8111 which has a shorter installation height.
Model 8115 & 8116 valves are designed for installations where the water supply is roughed-in 24” - 27” (610 mm - 686 mm) above the top of the water closet.
Model “X” “Y”
8111 † 11½” (292 mm) 16½” (419 mm)
8113 16” (406 mm) 21” (533 mm)
8115 ‡ 24” (610 mm) 29” (737 mm)
8116 ‡ 27” (686 mm) 32” (813 mm)
!!! IMPORTANT !!!
PROTECT THE CHROME OR SPECIAL
FINISH
OF FLUSHOMETERS — DO NOT USE
TOOTHED
TOOLS TO INSTALL OR SERVICE THESE
VALVES.
USE A SLOAN A-50 SUPER-WRENCH™,
SLOAN
A-109 PLIER WRENCH OR SMOOTH
JAWED SPUD WRENCH TO SECURE ALL
COUPLINGS.
ALSO SEE “CARE AND CLEANING”
SECTION.
2¼” (57 mm) MIN.
8180
1” I.P.S.
(25 mm DN)
SUPPLY
8186
¾” I.P.S.
(20 mm DN)
SUPPLY
11½”
(292 mm)
16½”
(419 mm)
C/L OF
FIXTURE
4¾”
(121 mm)
!!! IMPORTANT !!!
LAWS AND REGULATIONS PROHIBIT THE
USE OF HIGHER FLUSHING VOLUMES THAN
LISTED ON FIXTURE OR FLUSHOMETER.
!!! IMPORTANT !!!
THE STRAP WRENCH PROVIDED WITH THE SOLIS ® IS A
CONVENIENCE TOOL AND IS NOT TO BE USED TO REMOVE
OR INSTALL THE FLUSHOMETER COUPLINGS.USE STRAP
WRENCH ONLY TO INSTALL THE SOLIS ® LOCKING RING.
!!! IMPORTANT !!!
WITH THE EXCEPTION OF THE CONTROL STOP INLET, DO
NOT USE PIPE SEALANT OR PLUMBING GREASE ON ANY
VALVE COMPONENT OR COUPLING!
!!! IMPORTANT !!!
THIS PRODUCT CONTAINS MECHANICAL AND/OR
ELECTRICAL COMPONENTS THAT ARE SUBJECT TO
NORMAL WEAR. THESE COMPOENTS SHOULD BE CHECKED
ON A REGULAR BASIS AND REPLACED AS NEEDED TO
MAINTAIN THE VALVE’S PERFORMANCE.
FINISHED
WALL FINISHED
FLOOR
!!! IMPORTANT !!!
NEVER OPEN CONTROL STOP TO WHERE THE FLOW FROM
THE VALVE EXCEEDS THE FLOW CAPABILITY OF THE
FIXTURE. IN THE EVENT OF A VALVE FAILURE, THE FIXTURE
MUST BE ABLE TO ACCOMMODATE A CONTINUOUS FLOW
FROM THE VALVE.
Please take the time to read this manual to ensure proper product installation and longevity. Also, please visit our website to download our most recent documentation for this product.
If you have questions about how to install your Sloan flushometer, consult your local Sloan Representative or call
Sloan Technical Support Team at:
1-888-SLOAN-14 (1-888-756-2614)
ALTERNATIVE WATER CLOSET INSTALLATION
1” NPT
1½
(38 mm)
When installing the Sloan SOLIS ® Electronic Flushometer in an ADA compliant stall: Per ADA Guidelines (section
604.9.4) it is recommended that the grab bars be split or shifted to the wide side of the stall. For alternative installations, lower water supply rough-in to 10” (254 mm), or use the H-1018-A 1-1/2” offset adapter (not supplied) to lower the overall height. The Sloan H-1018-A 1” NPT x
1-1/2” offset adapter kit (sold separately) is designed to lower a SOLIS ® Flushometer 1-1/2” when the space above the top of the Flushometer conflicts with grab bar clearance. Mount the grab bar at the 36” (914 mm) maximum allowed height (top of grab bar at 36”).
32½”
(825 mm)
10”
(254 mm)
36”
(914 mm)
17”
(432 mm)
FIN. FLOOR
2
2
F
E
H
G
D
C
B
A
1 - FOR COMPLETE VALVE INSTALLATION, START HERE. FOR RESS
RETROFIT INSTALLATIONS, START AT STEP 6. INSTALL OPTIONAL
SWEAT SOLDER ADAPTER (ONLY IF YOUR SUPPLY PIPE DOES NOT
HAVE A MALE THREAD)
FINISHED WALL A
Measure from finished wall to C/L of Fixture Spud. Cut pipe 1¼”
(32 mm) shorter than this measurement. Chamfer O.D. and I.D. of water supply pipe.
B
Slide Threaded Adapter fully onto pipe.
WATER SUPPLY PIPE
1-1/4”
(32 mm)
C
Sweat solder the Adapter to pipe.
!!! IMPORTANT !!!
WITH THE EXCEPTION OF THE CONTROL STOP INLET,
DO NOT USE PIPE SEALANT OR PLUMBING GREASE ON
ANY VALVE COMPONENT OR COUPLING!
SWEAT
SOLDER
ADAPTER
C/L OF
FIXTURE
SPUD
2 - INSTALL COVER TUBE, WALL FLANGE AND CONTROL STOP TO SUPPLY PIPE
A
Measure from finished wall to first thread of adapter or threaded supply pipe (dimension
“X”). Cut cover tube to this length.
WATER
SUPPLY PIPE
“X” SWEAT
SOLDER ADAPTER
C
Thread control stop onto pipe. Tighten with a wrench.
SET SCREW
IRON PIPE NIPPLE OR
COPPER PIPE WITH SWEAT
SOLDER ADAPTER
COVER TUBE
COVER TUBE
B
Slide cover tube over pipe.
Slide wall flange over cover tube until against wall.
WALL
FLANGE
SUPPLY
FLANGE
D
Tighten set screw with a 5/64” hex wrench. DO NOT install vandal resistant stop cap at this time.
BAK-CHEK ®
CONTROL STOP
3 - FLUSH OUT SUPPLY LINE
A
Open Control Stop.
B
Turn on water supply to flush line of any debris or sediment.
C
Close control stop.
4 - INSTALL VACUUM BREAKER FLUSH CONNECTION
NOTE
If cutting Vacuum Breaker Tube to size, note that Critical Line (C/L) on
Vacuum Breaker must typically be 6” (152 mm) above fixture. Consult
Code for details.
MODELS
8110/8111,
8115, 8116
VACUUM
BREAKER
TUBE
A
Slide Spud Coupling, Nylon Slip Gasket, Rubber Gasket and Spud
Flange over Vacuum Breaker Tube.
B
Insert Tube into Fixture Spud.
C
Hand tighten Spud Coupling onto Fixture Spud.
SPUD COUPLING
NYLON SLIP
GASKET
RUBBER GASKET
SPUD FLANGE
3
MODEL 8180
VACUUM
BREAKER
TUBE
SPUD COUPLING
NYLON SLIP
GASKET
RUBBER GASKET
SPUD FLANGE
MODEL 8186
5 - INSTALL FLUSHOMETER
A
Lubricate tailpiece o-ring with water.
Insert adjustable tailpiece into control stop. Tighten tailpiece coupling by hand.
B
Align flushometer directly above the vacuum breaker flush connection by sliding the flushometer body IN or OUT as needed. Tighten vacuum breaker coupling by hand.
C
Align flushometer body and securely tighten first the tailpiece coupling (1), then the vacuum breaker coupling (2), and finally the spud coupling (3). Use a wrench to tighten these couplings in the order shown.
NOTE
Maximum adjustment of the Sloan Adjustable Tailpiece is ½” (13 mm)
IN or OUT from the standard 4¾” (121 mm) (centerline of Flushometer to centerline of Control Stop).
If roughing-in measurement exceeds 5¼” (133 mm), consult factory for longer tailpiece.
FLUSHOMETER
BODY
G-44 FRICTION RING
2 VACUUM
BREAKER
COUPLING
VACUUM BREAKER
FLUSH CONNECTION
3
SPUD
COUPLING
TAILPIECE COUPLING 1
O-RING
ADJUSTABLE
TAILPIECE
VACUUM
BREAKER
REPAIR KIT
CONTROL STOP
C/L
SUPPLY
C/L
FIXTURE
4-3/4”
(121 mm)
6 - WHEN RETROFITTING AN EXISTING VALVE, START HERE. REMOVE COMPENENTS
FROM EXISTING FLUSHOMETER (RESS RETROFIT INSTALLATIONS ONLY)
A
Remove control stop cap.
B
Turn off water supply at control stop. Push valve handle to relieve water pressure.
C
C
Remove outside and inside covers and old inside parts kit.
B
A
D
Remove old handle assembly and gasket.
E
Install chrome handle cap with gasket to handle opening on flushometer body. Tighten chrome handle cap securely.
NOTE: An extra H-553 tail o-ring is included in the event leakage occurs if the valve is repositioned during the installation of the new SOLIS ® . Use only as needed.
E
D
H-553
TAIL O-RING
RESS SERIES
INSTALLATIONS ONLY
7 - SLOAN SOLIS
®
FLUSH VOLUME (RESS RETROFIT INSTALLATIONS ONLY)
The flush volume of the Sloan SOLIS ® is controlled by the Regulator in the flex tube diaphragm Kit. Regulators are identified by color.
O-RING
REGULATOR
(MUST BE INSTALLED
PAST O-RING)
Note: Never use more water than needed. Low Consumption water closets and urinals will not function properly on excess water.
4
8 - ASSEMBLE FLEX TUBE DIAPHRAGM TO SOLIS ASSEMBLY
SLOAN SOLIS ®
ASSEMBLY
C
Push diaphragm securely against underside of
Sloan SOLIS ® Assembly.
Place entire Assembly onto the Valve Body.
O-RING
FLEX TUBE
DIAPHRAGM
B
Insert diaphragm into the base of the Sloan SOLIS ®
Assembly. O-ring must be fully inserted into the hole.
A
Make sure Flush
Volume Regulator is Installed Past
O-ring.
VALVE
BODY
To facilitate installation, wet the diaphragm assembly (on top or completely).
Note: Sensor Lens must face directly forward. Rotating the
Sensor to either side will decrease the Sensor’s ability to detect a target.
9 - TIGHTEN LOCKING RING
A
Thread Locking Ring onto Valve Body.
!!! IMPORTANT !!!
THE LOCKING RING MUST BE INSTALLED DOWN PAST
THE VALVE BODY THREADS BY AT LEAST ONE THREAD.
IF DIFFICULTY IS EXPERIENCED INSTALLING THE
LOCKING RING, TURN THE LOCKING RING BACK AND
FORTH, EACH TIME WORKING IT FURTHER DOWN THE
THREADS. THE LOCKING RING WILL ACT AS A THREAD
CHASER IN THE EVENT THERE HAS BEEN A BUILD-UP OF
MATTER ON THE THREADS OF THE OLD VALVE BODY.
B
Use Strap Wrench provided to tightly secure
Locking Ring. Both wrench and coupling ring must be dry.
If retrofitting the Sloan SOLIS ® onto a † Zurn valve body, a special Locking
Ring must be used (identified by a machined groove around the ring).
Order the Sloan SOLIS ® with the “Z” variation to receive the unit supplied with this Ring.
10 - REMOVE TAPE FROM SOLAR PANEL AND SENSOR WINDOW TO ACTIVATE
A
Remove the tape located over solar panel.
B
Remove the tape located over sensor window.
C
For the first ten (10) minutes of operation, a visible light flashes in the sensing window of the SOLIS ® flushometer when a user is detected.
!!! IMPORTANT !!!
The start-up routine will be 1 minute long and allows the sensors to adapt to the surrounding enviroment. It is VERY IMPORTANT that no non-permanent targets (i.e. persons, buckets, covers, etc) are present at this time. The start-up routine consists of a long (3 seconds) BLUE light ON, followed by slow BLUE light blinking in for 1 minute.
At the end of the routine the sensor will show ONE long (2 seconds) BLUE light ON for lithium battery or TWO long (2 seconds each) BLUE light ON pulses for alkaline to complete the routine. Only at this time can the non-permanent objects be present.
† Zurn® is a registered trademark of Zurco, Inc. Use of “Zurn” is for identification purposes only and does not imply affiliation, endorsement, or association between Sloan and Zurco, Inc.
5
11 - TEST SENSOR OPERATION
The Sloan SOLIS ® has a factory set sensing range:
Water Closet Models - 22” to 42” (559 mm to 1067 mm)
Urinal Models - 15” to 30” (381 mm to 762 mm)
THE FACTORY SETTING SHOULD BE SATISFACTORY
FOR MOST INSTALLATIONS. IF A RANGE ADJUSTMENT
IS REQUIRED, REFER TO THE RANGE ADJUSTMENT
INSTRUCTIONS.
A
Test Sensor with Cover in Place.
B
Stand in front of Sensor for sixteen (16) seconds C
Step away from Sensor and listen for “CLICK.”
12 - ADJUST CONTROL STOP AND INSTALL VANDAL RESISTANT STOP CAP
A
B
C
Open control Stop COUNTERCLOCKWISE ½ turn from closed position.
Activate flushometer by placing hand in front of Sloan SOLIS ®
Sensor Lens for ten
(10) seconds (or press override button) and then moving it away.
Adjust control stop after each flush until the rate of flow delivered properly cleanses the fixture.
!!! IMPORTANT !!!
SLOAN FLUSHOMETERS ARE ENGINEERED FOR QUIET
OPERATION. EXCESSIVE WATER FLOW CREATES NOISE,
WHILE TOO LITTLE WATER FLOW MAY NOT SATISFY THE
NEEDS OF THE FIXTURE. PROPER ADJUSTMENT IS MADE
WHEN PLUMBING FIXTURE IS CLEANSED AFTER EACH
FLUSH WITHOUT SPLASHING WATER OUT FROM THE LIP
AND A QUIET FLUSHING CYCLE IS ACHIEVED.
!!! IMPORTANT !!!
THE CONTROL STOP SHOULD NEVER BE OPENED TO THE
POINT WHERE THE FLOW FROM THE VALVE EXCEEDS
THE FLOW CAPABILITY OF THE FIXTURE. IN THE EVENT
OF A VALVE FAILURE, THE FIXTURE MUST BE ABLE TO
ACCOMMODATE A CONTINUOUS FLOW FROM THE VALVE.
D
Install control stop cap onto control stop. For RESS retrofit applications, reuse stop cap from existing valve. In complete valve installations, a new stop cap is provided. Follow the instructions packaged with the free spinning vanda resistant stop cap.
OPERATION
1. A continuous, INVISIBLE light beam is emitted from the Sloan SOLIS ® sensor.
2. As the user enters the beam’s effective range, 22 to 42 inches (559 mm to 1067 mm) for closet installations and 15 to 30 inches (381 mm to 762 mm) for urinal installations, the beam is reflected into the Scanner Window to activate the Output Circuit. Once activated, the Output Circuit continues in a “hold” mode for as long as the user remains within the effective range of the sensor. Once the user steps away, a full flush will automatically initiate.
3. When the user steps away, this initiates a full flush. The circuit automatically resets and is ready for the next user.
4. In addition to the above the Sloan SOLIS ® urinal incorporates a standard deferred flushing mode feature that accommodates the high volume usage seen in stadiums or similar high attendance facilities.
BATTERY REPLACEMENT
When required, replace batteries with four (4)
Alkaline AA-Size batteries.
Note: Water does not have to be turned off to replace batteries.
COVER
ASSEMBLY
SENSOR
MODULE Loosen the two (2) Screws on top of unit.
Remove the complete cover assembly. Lift the sensor module from its plate. Unplug the electrical connector from battery compartment cover. Loosen the retaining screw on battery compartment cover. Remove battery compartment cover and old batteries. Install four (4) fresh Alkaline AA-Size batteries exactly as illustrated.
PLATE
SENSOR
MODULE
CLOSET URINAL
RETAINING
SCREW
BATTERY
COMPARTMENT
COVER
ELECTRICAL CONNECTOR RECEPTACLE
Install battery compartment cover and secure with retaining screw. Make certain that battery compartment cover is fully compressed against gasket to provide a seal; DO NOT overtighten. Plug the electrical connector into the battery compartment cover. Reinstall the sensor module onto the Plate.
Reinstall the complete cover assembly onto the plate. Tighten the two (2) screws on top of the unit.
6
RANGE ADJUSTMENT (ADJUST ONLY IF NECESSARY)
The Sloan SOLIS
® has a factory set sensing range: Water Closet Models -
22” to 42” (559 mm to 1067 mm)Urinal Models - 15” to 30” (381 mm to 762 mm)
The factory setting should be satisfactory for most installations.
Note: Water DOES NOT have to be turned off to adjust range.
RANGE ADJUSTMENT PROCEDURE For the first ten (10) minutes of operation, a visible light flashes in the sensing Window of the Sloan SOLIS
® flushometer when a user is detected. This visible light feature can be reactivated after ten (10) minutes by opening and closing the battery compartment door. Check the range by stepping toward the unit until the light flashes, indicating the sensor’s maximum detection limit.
Always Determine the Sensing Range with Metal Cover and Lens
Window On Top of the Unit. To recalibrate the sensor, touch and hold the override button for 30 seconds, once the Blue LED blinks every second, and release.
Stand at desired distance, LED should blink once every 2 seconds for 30 seconds). The setting mode will run for one minute.
NOTE: For -BT models only, to automatically check battery strength, troubleshoot, diagnose and report flushometer issues with a wireless device, use the Sloan Connect
APP. The APP is available free-of-charge at the Apple iPhone APP store for iOS devices or the Google Play APP store for Android devices. For more information about the APP and its capabilities please visit Sloan.com.
CARE AND CLEANING
DO NOT use abrasive or chemical cleaners to clean flushometers as they may dull the luster and attack the chrome or special decorative finishes. Use ONLY soap and water, then wipe dry with clean cloth or towel.
While cleaning the bathroom tile, the flushometer should be protected from any splattering of cleaner. Acids and cleaning fluids can discolor or remove chrome plating.
TROUBLESHOOTING GUIDE
1. Sensor Flashes Continuously Only When User Steps Within Range.
A. Unit in Start-Up mode; no problem. This feature is active for the first ten (10) minutes of operation.
2. Valve Does Not Flush; Sensor Not Picking Up User.
A. Range too short; increase the range.
3. Valve Does Not Flush; Sensor Picking Up Opposite Wall or Surface, or Only
Flushes When Someone Walks By. Light Flashes Continuously for First 10
Minutes Even with No One in Front of the Sensor.
A. Range too long; shorten range.
4. Valve Does Not Flush Even After Adjustment.
A. Range Adjustment Potentiometer set at full “max” or full “min” setting. Re-adjust
Potentiometer away from full “max” or “min” setting.
B. Batteries completely used up; replace batteries.
C. Problem with Electronic Sensor Module; replace Electronic Sensor Module.Try swapping module with working unit to test module function.
D. Are there audible clicks from the solenoid?
NO : check for solenoid plugged into module; possibly solenoid stuck in closed position, replace solenoid.
YES : check solenoid for over-tightening, check to make sure locking ring was secured properly.
E. Module is working, and solenoid clicking, loosen and re-tighten locking ring; check diaphragm for perforations in diaphragm disc; replace.
5 . Unit Flashes 4 Quick Times When User Steps Within Range.
A. Batteries low; replace batteries.
NOTE: THE EBV-46-A BEAM DEFLECTOR IS NOT REQUIRED OR AVAILABLE
FOR THE SLOAN SOLIS®.
Note: Troubleshooting also applies to the Sloan SOLIS Urinals.
!!! IMPORTANT !!!
WHEN SERVICING SOLENOID, ROTATING LOCKING RING, SERVICING
DIAPHRAGM, SERVICING VACUUM BREAKER OR SPUD, TURN OFF WATER
SUPPLY AT STOP
!!! IMPORTANT !!!
LAWS AND REGULATIONS PROHIBIT THE
USE OF HIGHER FLUSHING VOLUMES THAN
LISTED ON FIXTURE OR FLUSHOMETER.
6. Valve Does Not Shut Off.
A. Bypass Orifice in Diaphragm is clogged with dirt or debris, or Bypass is clogged by an invisible gelatinous film due to “over-treated” water.
Remove flex tube diaphragm and wash under running water.
NOTE: SIZE OF ORIFICE IN THE BYPASS IS OF UTMOST IMPORTANCE FOR
THE PROPER METERING OF WATER BY THE VALVE. DO NOT ENLARGE
OR DAMAGE THIS ORIFICE. REPLACE FLEX TUBE DIAPHRAGM IF
CLEANING DOES NOT CORRECT THE PROBLEM.
B. Dirt or debris fouling stem or flex tube diaphragm. Remove flex tube diaphragm and wash under running water.
C. O-ring on stem of flex tube diaphragm is damaged or worn. Replace o-ring if necessary.
D. Problem with electronic sensor module; replace sensor module. Try swapping module with working unit to test module function
E. Are there audible clicks from the solenoid?
NO, possibly solenoid stuck open position, replace solenoid
YES, check solenoid properly screwed into inside cover, check to make sure locking ring was secured properly.
F. If module is working, and solenoid clicking, check diaphragm for perforations in diaphragm disc; replace
7. Not Enough Water to Fixture.
A. Wrong flush volume regulator installed in flex tube diaphragm kit.
Install the correct Regulator.
B. Wrong SOLIS
® model installed; i.e., 1.0 gpf urinal installed on 3.5 gpf closet fixture. Replace with proper Sloan SOLIS
® model.
C. Enlarged by-pass in diaphragm. Replace flex tube diaphragm.
D. Control Stop not adjusted properly. Readjust control stop.
E. Inadequate volume or pressure at supply. Increase water pressure or supply (flow) to valve. Consult factory for assistance.
8. Too Much Water to Fixture.
A. Wrong flush volume regulator installed in flex tube diaphragm Kit.
Install the correct regulator.
B. Control Stop not adjusted properly. Readjust Control Stop.
C. Wrong Sloan SOLIS
® model installed; i.e., 3.5 gpf Model installed on
1.0 or 1.5 gal. Urinal fixture. Replace with proper Sloan SOLIS
® model.
D. Dirt in Diaphragm Bypass. Clean under running water or replace Flex
Tube Diaphragm.
7
PARTS LIST
13
18A 18B 18C 18D
2
20A
19
3
4
20A 20B 20C
1
11
5
7
12
FLEX TUBE DIAPHRAGM ASSEMBLY
Sloan SOLIS ® valve models feature Sloan’s exclusive flex tube diaphragm for the ultimate in valve performance, reliability and chloramines resistance.
6
10
14
17
8
9
15
16
Item # Part # Description
Items Included with RESS Retrofit and Complete Sloan SOLIS ®
Valves
1 EBV-304-A Cover/Sensor/Assembly - Closet Solis Electronic Single
Button Flush
EBV-320-A
EBV-306-A
Cover/Sensor/Assembly (†Zurn) - Closet Solis Electronic
Single Button Flush
Cover/Sensor/Assembly - Urinal Solis Electronic
Single Button
EBV-321-A
2 EBV-309-A
3 EBV-14
Cover/Sensor/Assembly (†Zurn) - Urinal Solis Electronic
Single Button
Cover Assembly - Solis Electronic Single Button Flush
Locking Ring
EBV-30 Locking Ring - for †Zurn valves
4 EBV-312-A-C Sensor Assembly Solis - Water Closet
EBV-312-A-U Sensor Assembly Solis - Urinal
5 EBV-134 Cover Rest Plate
6 EBV-145-A Inside Cover Assembly (includes solenoid)
7 EBV-136-A Solenoid
8 † †
9 † †
Flex Tube Diaphragm Assembly
Flush Volume Regulator
10 EBV-1017-A Handle Cap
11 EBV-91 Range Adjustment Tool
12 EBV-22
13 EBV-137
Strap Wrench
7/64” Hex Wrench
FCC INFORMATION TO USERS
This equipment has been tested and found to comply with the limits for a class B digital devices, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmfull interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmul interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna
• Increase the separation between the equipment and receiver
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected
• Consult the dealer or an experienced radio/TV technician for help
Item # Part # Description
Items Included with Complete Sloan SOLIS ® Valves Only
14 H-633-AA 1” (25 mm) Sweat Solder Kit
H-636-AA
15 H-700-A
¾” (19 mm) Sweat Solder Kit
1” (25 mm) Bak-Chek ® Control Stop
16
17
H-700-A
H-1010-A
EBV-36-A
18A V-600-AA
¾” (19 mm) Bak-Chek ® Control Stop
Vandal Resistant Stop Cap
Valve Body
V-600-AA
1½” (38 mm) x 10½” (229 mm) Vacuum Breaker
(Model 8110/8111)
1½” (38 mm) x 15” (584 mm) Vacuum Breaker
(Model 8113)
V-600-AA
V-600-AA
18B V-600-A
18C V-600-AA
18D V-600-AA
19 F-109
20A F-5-AT
20B F-5-AU
20C F-5-AW
1½” (38 mm) x 23” (584 mm) Vacuum Breaker
(Model 8115)
1½” (38 mm) x 26” (660 mm) Vacuum Breaker
(Model 8116)
3” (76 mm) Vacuum Breaker Assembly
1¼” (32 mm) x 10½” (229 mm) Vacuum Breaker
(Model 8180)
¾” (19 mm) x 10½” (229 mm) Vacuum Breaker
(Model 8186)
1½” (38 mm) Elbow Flush Connection
1½” Spud Coupling Assembly (Water Closet Models)
1¼” Spud Coupling Assembly (Model 8180)
¾” Spud Coupling Assembly (Model 8186)
† † Flow volume varies with valve model and desired flush volume.
Manufactured in the U.S.A. by Sloan Valve Company under one or more of the following patents: U.S. Patents: D598,975; D599,436; 7,124,997. Other Patents
† Zurn® is a registered trademark of Zurco, Inc. Use of “Zurn” is for identification purposes only and does not imply affiliation, endorsement, or association between Sloan and Zurco, Inc.
Pending. BAK-CHEK ® , PARA-FLO ® , PERMEX ® , TURBO-FLO ® .
The information contained in this document is subject to change without notice.
SLOAN • 10500 SEYMOUR AVENUE • FRANKLIN PARK, IL 60131
Phone: 1-800-982-5839 or 1-847-671-4300 • Fax: 1-800-447-8329 or 1-847-671-4380 • sloan.com
© 2021 SLOAN VALVE COMPANY Code No. 0816805 – Rev. 7 (04/21)