advertisement
Technical Data Manual
for model numbers and pricing: see price list
VITOLIGNO 300-C
Product may not be exactly as shown
Vitoligno 300-C, 32 and 48
Wood pellet floor mounted boiler, with Ecotronic weather-compensated, digital boiler and heating circuit control unit
Heating input: 44 MBH to 193 MBH
13 kW to 57 kW
5790 981 - 01 05/2017
H
Please file in service binder.
2
Introduction
Product Description
Vitoligno 300-C Technical Data
Benefits at a glance
Fully automatic compact pellet boiler.
Efficiency: up to 85%.
Innovative combustion technology for lowest dust
Low fuel consumption through high efficiency,
modulating operation and weather-compensated control.
Automatic combustion chamber ash removal through
a stainless steel finned grate ensures high operational
reliability and long cleaning intervals.
Automatic ash removal compresses the ash into the
ash box - mobile ash box only needs to be emptied
once or twice a year depending on the amount of consumed.
High operational reliability provided by rotary lock valve,
for 100% burn-back protection.
Low power consumption – automatic ignition with
ceramic heating element.
Ecotronic control unit with plain text user prompts
and automatic function monitoring, plus buffer tank
charging control and solar function.
Extensive accessories for pellet supply and storage
Software update function via SD card
Web-enabled via Vitoconnect (accessory) for operation
and service using Viessmann apps.
Lambda probe, boiler water temperature sensor and flue gas temperature sensor for combustion control are integral to the boiler. Outdoor temperature sensor and temperature sensor for DHW tank are included with the boiler body.
Low temperature protection package
The low temperature protection package is required to protect the boiler from temperatures below the dew point.
Accessories (specific to the system)
Heating system with heating water buffer tank. If using heating water buffer tanks, the buffer temperature sensor set must be ordered separately.
Heating system with heating circuit with mixing valve
An extension kit (accessories) is required for each heating circuit with mixing valve.
DHW heating by a solar thermal system
For DHW heating by the solar thermal system, the temperature sensors for the solar circuit (collector temperature sensor and tank temperature sensor) have to be ordered separately.
Delivered condition
Boiler body (in shipping crate) with:
Fitted thermal insulation mats
Combustion chamber door
Ash door
Automatic ignition
Variable speed flue gas fan
Automatic ash removal and mobile ash box
Cleaning accessories
Ecotronic boiler control unit with user prompts
Vitoligno 300-C Technical Data
Product Description
(continued)
Introduction
Legend
A Integral suction turbine
B Pellet hopper (version with vacuum system only)
C Variable speed flue gas fan for modulating operation
D Automatic heat exchanger cleaning
E Ecotronic control unit with user prompts
F Self-cleaning rotary finned grate made from stainless
steel
G Combustion chamber made from high temperature- ceramics
H Rotary lock valve for 100% burn-back protection
K Automatic ash removal with mobile ash box
The Vitoligno 300-C is a fully automatic wood pellet boiler. The boiler has an efficiency of up to 85% when converting pellets into heat.
The wood pellet boiler offers a wide spectrum of applications – from low energy houses to buildings with a higher heat demand.
Modulation of 1:3 leads to low consumption and clean combustion under partial load conditions. A ceramic ignition unit consumes little power, whilst innovative combustion technology featuring dual combustion control with lambda probe and flue gas temperature sensor keeps dust values low.
The Vitoligno 300-C offers versatile and flexible supply system options for almost any application. Pellets are supplied to the boiler either via a flexible screw conveyor or a vacuum system. Thanks to its compact design, it is suitable for installation in rooms with low ceiling heights. Versions with pellet supply via a vacuum system are supplied with a pellet hopper with integral suction turbine and capacity for one-day operation. The wood pellet boiler is convenient to use and is partially automated. The automated features include ignition, heat exchanger cleaning, the selfcleaning rotary finned grate and fully automatic compaction of ash. The mobile ash box only needs emptying once or twice a year. Thanks to the sealed ash box, ash removal is also clean and stress-free.
Operating the boiler is easy with the weathercompensated digital Ecotronic control unit. The integral
Ecotronic controls up to four heating circuits with mixing valve. The Ecotronic controls boilers with pellet supply, heating circuits and the tank temperature.
The clear display, with graphic capability and multiple line plain text user prompts, provides intuitive operation and easy adjustment of all relevant parameters.
In combination with a solar thermal system, current solar data is also shown on the display.
The Vitotrol 350-C (optional accessory) control unit extension enables the wood pellet boiler to be operated from the living space as well. With the 5 in. (125 mm) color touchscreen display in 16:9 format, operation couldn’t be easier. The Vitotrol 350-C enables remote control of the boiler with all relevant adjustment options and display of all relevant information about the boiler and the heating water buffer tank. Optionally, the Vitotrol 350-C can be used not only as a remote controller but also as a cascade controller. Up to four boilers can be connected in a cascade. Additionally, one oil/gas boiler can be enabled via the lead boiler.
The most important control circuits of the cascade system can be displayed and operated.
3
Introduction
Principles of Pellet Combustion
Vitoligno 300-C Technical Data
What are wood pellets?
Wood pellets are made from 100 percent natural wood remnants. This raw material is waste matter created by the wood industry in large volumes through planing or sawing.
Wood remnants are compressed under high pressure and formed into pellets, i.e. pressed into a cylindrical shape.
The raw material is stored and transported under completely dry conditions. System users should also ensure completely dry storage conditions. This is the only way to guarantee optimum and effective combustion.
Requirement
Diameter
Length
Bulk density in delivered condition
Net calorific value in the delivered condition
Water content in delivered condition
Fines content in the delivered condition
Mechanical strength in the delivered condition
Ash content, free from water
Ash softening temperature
This value is only binding for pellets certified to CANPlus.
It indicates the temperature at which the wood ash is deformed and can therefore cause fusions in the combustion chamber.
Chlorine content, free from water
Sulphur content, free from water
Nitrogen content, free from water
Pellet requirements
It is recommended that the pellets used complies with the requirements of the Pellet Fuel Institute (PFI - Standard or
PFI - Premium) and/or CANPlus grade A1 and/or CAN/CSA
- ISO 17225 Part 2 Standard.
PFI -
Standard lb/cuft
(kg/m³)
MBH/lb (MJ/kg)
MBH/lb (kWh/kg) m-% m-% m-%
%
°F
(°C) in.
(mm) in.
(mm)
0.230 - 0.285
(5.84 - 7.25)
A maximum of 1% may be longer than
1.5 in.
(38 mm)
38-48
(608-769)
--
--
≤ 10
≤ 1
≥ 95
--
--
CAN plus-A1 Specification as per
CAN/CSA
ISO 17225-2
Grade A1
0.236 ± 0.039
(6 ± 1)
A maximum of 1% may be longer than
1.7 in. (40 mm), but no longer than
1.77 in. (45 mm)
D06
0.125 to 1.575
(3.15 to 40)
37-47
(600 to 750)
≥ 6.9 ( ≥ 16.5)
(BD600)
Q16.5
≥ 7.1 ( ≥ 4.6) Q4.6
≥ 10 M10
≤ 1
≤ 97.5
F1.0
DU 97.5
≤ 0.7
≤ 2200
( ≤ 1200)
A0.7
--
-m-% m-% m-%
≤ 300 ppm
--
--
≤
≤
0.02
0.04
≤ 0.3
C10.2
S0.04
N0.03
m-% = percentage by mass
Pellet Quality Characteristics
High quality pellets:
Smooth shiny surface
Uniform length
Low proportion of dust
Sink in water
Low quality pellets:
Cracked rough surface
Widely varying length
High proportion of dust
Float in water
Types of Pellet Delivery
4
Pellets are sold in sacks, in bulk on pallets and loose.
In their loose form, pellets are transported by silo tanker and pumped into the storage room via a hose system.
Careful handling of pellets ensures a low proportion of dust, perfect fuel charging and a constant boiler heating output.
Note: For boilers equipped with the vacuum system, the pellet hopper inside the boiler has a capacity of approx. 3.5 cu. ft (100 L). This corresponds to approx. 143 lbs. (65 Kg) of pellets.
Vitoligno 300-C Technical Data
Specification
Boiler model 300-C
Input
Output
MBH
(Kw)
MBH
(Kw)
Efficiency
– At full load
– At partial load
Heat exchanger surface area
Supply temperature
Fixed High Limit (FHL)
Adjustable high limit range
Max. operating pressure at 230°F (110°C)
Power Supply
ft 2 (m
%
%
2 )
°F (°C)
°F (°C) psi
(bar)
Voltage
Phase
Hz
Amperage
Overall dimensions
Total length h
Total width b (boiler)
Total width d (boiler with pellet hopper)
Total width c (boiler with connection unit for the flexible screw conveyor)
Height a (boiler)
Total height m
Total weight
– Boiler incl. thermal insulation and pellet hopper
– Boiler incl. thermal insulation and connection unit for flexible
screw conveyor
Pellet hopper capacity (with vacuum system)
Volume of ash box
Boiler water content
Boiler connections
Boiler supply
Boiler return
Safety connection
Drain
Flue gas
Average temperature (gross)
– At upper heating output
– At partial load (33% of upper heating output)
Mass flow rate
– At upper heating output
– At partial load (33% of upper heating output)
CO
2
content in the flue gas
– At the upper rated heating output
– At partial load (33% of upper heating output)
Flue outlet
Required draught (at full load)
Max. permiss. draught *1
*1 Install a barometric damper in the chimney (see page 23).
in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) lb. (kg) lb. (kg) cu ft. (L) cu ft. (L)
USG (L)
NPT
NPT
NPT
NPT
°F (°C)
°F (°C) lb/h (kg/h) lb/h (kg/h)
%
%
7 in.
7
(mm)
“w.c. (Pa)
“w.c. (Pa)
32
44-129
(13-38)
37.4-109.6
(11-32)
85
85
30.9 (2.87)
230 (110)
203 (95)
45
(3)
240
1
60
20
48 d (1224)
30 d (765)
52 b (1332)
50 (1244)
60 f (1538)
61 b (1560)
1433 (650)
1356 (615)
3.5 (101)
2.3 (65)
47.5 (180)
1 b “
1 b “
1 b “ c “
266 (130)
176 (80)
231 (105)
53 (24)
13
11
6
(150)
0.02 (5)
0.06 (15)
Introduction
48
64-193
(19-57)
54.4-164
(16-48)
85
85
30.9 (2.87)
230 (110)
203 (95)
45
(3)
240
1
60
20
48 d (1224)
30 d (765)
52 b (1332)
50 (1244)
60 f (1538)
61 b (1560)
1433 (650)
1356 (615)
3.5 (101)
2.3 (65)
47.5 (180)
1 b “
1 b “
1 b “ c “
275 (135)
176 (80)
273 (124)
64 (29)
13
11
6
(150)
0.02 (5)
0.06 (15)
5
Introduction
Dimensions
Vitoligno 300-C Technical Data
6
Legend
A Version with pellet hopper
(pellet supply via vacuum system)
B Version with connection unit
(for pellet supply via flexible screw conveyor)
AGA Flue outlet 6 in. (150 mm)
E Drain c in. NPT
KR Boiler return 1 b in. NPT
KV Boiler supply 1 b in. NPT
SA Safety header 1 b in. NPT
Boiler model 300-C a*
32 to 48 in. (mm) 60 f (1539) b in. (mm) 30 d (765) c (total width of version
with pellet supply via
flexible screw conveyor) d (total width of version
with pellet supply via
vacuum system) e in. (mm) 49 (1244) in. (mm) 52 b (1332) f* g* h in. (mm) 36 a (920) in. (mm) 19 d (487) in. (mm) 58 d (1478) in. (mm) 48 d (1224) l k* in. (mm) 31 d (792) in. (mm) 19 a (488) m* (height with SA connection) in. (mm) 61 b (1560)
* includes adjustable feet height set to 1 a in. (30 mm)
Vitoligno 300-C Technical Data
Clearances
Minimum clearances for version with pellet supply via vacuum system
Introduction
Note: The specified wall clearances are required for installation and maintenance work.
Recommended minimum service clearances
For typical Vitoligno 300-C series boiler installations,
Viessmann recommends installing the boiler with the service clearances shown in the illustrations. b c
Minimum clearances vacuum system a in. (mm) d in. (mm) in. (mm) in. (mm) g h e f in. (mm) in. (mm) in. (mm) in. (mm)
Minimum room height in. (mm)
30 (765)
36 (920)
35 b (900)
31 b (800)
16 (400)
20 (500)
4 (100)
22 b (570)
79 (2000)
Legend
A Boiler
B Pellet hopper
Minimum clearances for version with pellet supply via flexible screw conveyor
Recommended minimum service clearances
For typical Vitoligno 300-C series boiler installations,
Viessmann recommends installing the boiler with the service clearances shown in the illustrations. b c
Minimum clearances flexible screw conveyor a in. (mm) 30 (765) d in. (mm) in. (mm) in. (mm)
26/35
36 (920) b
31
* (670/900 b (800)
* ) e f in. (mm) in. (mm)
Minimum room height in. (mm)
16 (400)
20 (500)
79 (2000)
* Dimension c, when the flexible screw conveyor
is routed to the back parallel to the boiler.
Legend
A Boiler
B Connection unit for pellet supply with flexible screw conveyor (can be pivoted 90° to the front or back)
Clearance to combustibles
Boiler model 300-C
Top
Sides (left and right)
Front
Rear
Floor
32
0
0
0
48
0
0
0
0 0 noncombustible noncombustible
7
8
Introduction
Clearances
Legend
A Pellet discharge or connector at the pellet silo
B Hose with screw conveyor
*
Legend
A Pellet discharge or connector at the pellet silo
B Hose with screw conveyor
Vitoligno 300-C Technical Data
Flexible screw conveyor
Specification
The boiler supply with flexible screw conveyor can either be connected to the room discharge with screw conveyor supply system or to a pellet silo.
The rotary adjuster at the pellet silo or at the room discharge, as well as the drive unit of the flexible screw conveyor on the boiler, can be fitted in different positions.
Further details regarding positioning:
Dimension a
Dimension b (hose length) in.
(mm) in.
(mm) min. 67
(min. 1700) min. 55
(min. 1390)
* Note: Observe the minimum bending radius of the flexible screw conveyor.
Intended use
The appliance is intended solely for installation and operation in sealed unvented heating systems. It is only designed for heating up heating water that is of potable water quality.
Intended use presupposes that a fixed installation in conjunction with permissible, system-specific components has been carried out.
Commercial or industrial usage for a purpose other than heating the building or DHW shall be deemed inappropriate.
Any usage beyond this must be approved by the manufacturer in each individual case.
Incorrect usage or operation of the appliance (e.g. the appliance being opened by the system user) is prohibited and will result in an exclusion of liability.
Incorrect usage also occurs if the components in the heating system are modified from their intended use
(e.g. if the flue gas and ventilation air paths are sealed).
Connection unit, feed screw conveyor with drive unit, flexible screw conveyor (can be pivoted 90°)
Vitoligno 300-C Technical Data
Pressure Drop
Introduction
Legend
A Boiler model Vitoligno 300-C, 32 and 48 kW
The Vitoligno 300-C is only suitable for fully pumped hot water heating systems.
Boiler model 300-C
32 USGPM
48 USGPM
(m
(m 3
3 /h)
/h))
∆ T = 20 ° F (10 K)
Flow rate
11.0 (2.5)
16.4 (3.7)
Note: This boiler does not require a flow switch.
∆ T = 30 ° F (15 K)
Flow rate
7.3 (1.7)
10.9 (2.5)
∆ T = 40 ° F (20 K)
Flow rate
5.5 (1.2)
8.2 (1.9)
9
10
Control
Ecotronic Control Unit
Vitoligno 300-C Technical Data
Ecotronic Specification
Weather-compensated digital boiler and heating circuit control unit for controlling three heating circuits with mixing valve, two heating circuits with mixing valve plus DHW heating or one heating circuit with mixing valve, one DHW heating and one solar circuit. An additional, fourth heating circuit with mixing valve can be connected via the KM-BUS.
With separately adjustable periods, heating curves,
set temperature values and heating programs.
With tank temperature controller
With intelligent buffer management
With integral diagnostic system and additional functions
With commissioning assistant. An extension
(accessories) is required for each heating circuit with
Design and functions (Modular design)
The Ecotronic boiler control unit is a decentralized microprocessor system. To control the boiler system, the Ecotronic comprises three PCBs integrated into the boiler (PCB for boiler controller, heating circuit PCB and boiler-specific auxiliary PCB) and the programming unit with display integrated into the boiler. A sensor tank management is part of the standard Ecotronic version.
Functions
Continuously regulating air dampers optimize the heat-
up and burnout process.
Lambda probe enables efficient combustion control,
minimum emission levels and maximum efficiency.
Control of the return temperature raising facility.
Supporting auxiliary and service functions.
Enabling a second heat generator.
Activation of tank priority control if required.
Control of automatic changeover device (accessory)
Available languages:
English, German Danish, Estonian, French, Italian,
Croatian, Latvian, Lithuanian, Dutch, Norwegian,
Polish, Romanian, Russian, Swedish, Serbian,
Slovakian, Slovenian, Spanish, Czech, Hungarian
To reduce the heat-up output, the reduced room temperature is raised when outdoor temperatures are low.
To shorten the heat-up time after a setback phase the supply temperature is raised for a limited time.
Ecotronic specification
Rated voltage................240VAC
Rated frequency..............60 Hz
Rated current..................20 FLA
Vitoligno 300-C Technical Data
Ecotronic Control Unit
(continued)
Control
Overview of connection options
Key
HC Heating circuit
SOL Solar circuit
FRC Flow rate control
To Ecotronic (HKK PCB)
1 heating circuit
2 heating circuit
3 heating circuit
4 heating circuit
1 heating circuit and DHW
2 heating circuit and DHW
3 heating circuit and DHW
4 heating circuit and DHW
Only DHW
1 heating circuit and solar
2 heating circuit and solar
3 heating circuit and solar
4 heating circuit and solar
1 heating circuit, solar and DHW
2 heating circuit, solar and DHW
3 heating circuit, solar and DHW
4 heating circuit, solar and DHW
Solar and DHW only
Solar only
HC1
HC1
HC1
--
--
HC1
HC1
HC1
--
HC1
HC1
--
--
--
(CP)
HC2
HC2
DHW+(CP)
(CP)
DHW+(CP)
(CP)
HC2
HC2
HC2
DHW+(CP)
(CP)
DHW+(CP)
HC2
HC2
HC2
DHW+(CP)
DHW+(CP)
(CP)
(CP)
(CP)
HC2
(CP)
(CP)
HC2
(CP)
(CP)
HC2
(CP)
DHW+(CP)
(CP)
DHW+(CP)
(CP)
(CP)
DHW+(CP)
(CP)
(CP)
DHW+(CP)
HC2
(CP)
DHW+(CP)
DHW+(CP)
HC2
DHW+(CP)
DHW+(CP)
(CP)
(CP)
HC1
HC1
HC1
--
HC1
HC1
HC1
HC1
--
HC1
HC1
--
--
HC1
--
HC1
--
HC1
HC1
HC1
HC1
HC1
--
HC1
HC1
--
--
HC1
HC1
HC1
HC1
--
--
Connection group
A1
HC1
--
HC1
--
HC1
HC1
HC1
HC1
--
HC1
HC1
HC1
HC1
HC1
A2
(CP)
(CP)
HC2
(CP)
(CP)
HC2
HC2
(CP)
(CP)
HC2
HC2
(CP)
DHW+(CP)
DHW+(CP)
(CP)
Key
DHW heating
(CP) DHW recirculation pump, optional
SOL
SOL
SOL
SOL
SOL
SOL
SOL
SOL
SOL
SOL
SOL
SOL
SOL
SOL
SOL
SOL
SOL
SOL
SOL
SOL
SOL
SOL
SOL
--
--
--
SOL
SOL
SOL
SOL
SOL
--
DHW+(CP)
(CP)
--
--
--
--
HC3
DHW+(CP)
(CP)
--
--
--
HC3
(CP)
DHW+(CP)
--
--
HC3
(CP)
--
--
--
--
A3
--
--
(CP)
--
--
HC3
(CP)
--
DHW+FRC
HC2
HC2
HC1
HC1
DHW+FRC
HC3
HC3
HC2
HC2
HC1
HC4
HC3
HC3
HC2
--
DHW+FRC
--
HC1
--
HC2
--
--
HC1
HC2
HC3
HC2
--
DHW+FRC
HC1
HC1
DHW+FRC
HC2
HC2
HC1
HC1
HC3
HC2
HC2
HC1
HC4
HC2
--
DHW+FRC
--
To “extension module for heating circuit with mixing valve” (KM-BUS subscriber)
Rotary selector setting
1
--
HC1
--
HC1
HC2
--
HC3
HC2
HC1
HC4
HC3
HC2
--
DHW+FRC
HC1
HC1
--
--
3
--
--
--
--
--
--
--
5
--
--
HC3
--
--
HC4
--
--
--
--
--
--
--
--
--
DHW+FRC
--
--
--
--
--
--
HC2
--
--
HC3
HC2
HC4
HC3
--
--
--
DHW+FRC
--
--
DHW+FRC
HC2
HC2
DHW+FRC
HC3
HC3
HC2
HC4
HC3
--
--
--
HC2
--
--
--
HC3
HC2
--
HC4
HC3
--
--
--
DHW+FRC
--
--
--
DHW+FRC
HC2
HC2
--
--
DHW+FRC
HC3
HC3
HC2
DHW+FRC
HC4
HC4
HC3
--
--
--
HC3
--
DHW+FRC
--
HC4
--
--
--
--
--
--
--
--
--
HC3
--
HC4
--
--
--
--
--
--
--
DHW+FRC
--
--
DHW+FRC
--
HC3
DHW+FRC
HC4
--
--
--
11
12
Control
Ecotronic Accessories
Vitoligno 300-C Technical Data
Vitotrol 200-A
KM-BUS subscriber
Displays:
– Room temperature
– Outdoor temperature
– Operating condition
Settings:
– Set room temperature for standard mode (normal room
The set room temperature for reduced mode (reduced room temperature) is set at the control unit.
– Operating program
Party and economy mode can be enabled via keys
Integral room temperature sensor for room temperature hook-up (only for one heating circuit with mixing valve)
Installation location:
Weather-compensated mode:
Installation anywhere in the building
Room temperature hook-up:
The integral room temperature sensor captures the actual room temperature and effects any necessary correction of the supply temperature.
The captured room temperature depends on the site:
– Main living room on an internal wall opposite radiators
– Not on shelves or in recesses
– Never in the immediate vicinity of doors or close
to heat sources
(e.g. direct sun, fireplace, etc.).
Connection:
2-core lead 18 AWG, length max. 164 ft. (50 m)
(even if connecting several remote control units)
Never route sensor or communication cables near
120/240VAC line voltage wiring.
LV plug as standard delivery
Notes:
If the Vitotrol 200-A is to be used for room temperature hook-up, site the device in a main
living
room.
Connect maximum 3 Vitotrol 200-A units to
the control unit.
Specification
Power supply Via KM-BUS
Power consumption 0.2 W
Permissible ambient temperature
Operation
Storage and transport
32 to 104°F (0 to +40°C)
-4 to 149°F (-20 to +65°C)
Vitoligno 300-C Technical Data
Ecotronic Accessories
(continued)
Control
Specification
Power supply
Power consumption
Permissible ambient temperature
Operation
Storage and transport
Via KM-BUS
0.5 W
32 to 104°F (0 to +40°C)
-4 to 149°F (-20 to +65°C)
Notes:
If the Vitotrol 300-A is to be used for room
temperature hook-up, site the device in a main
room.
If the Vitotrol 300-A cannot be installed in a suitable
location for capturing the room temperature, order
a room temperature sensor as well.
Connect no more than one Vitotrol 300-A to the
Vitotrol 300-A
KM-BUS subscriber.
Displays:
– Room temperature
– Outdoor temperature
– Operating program
– Operating condition
– Heat-up condition of the heating water buffer
tank, ash box full, recharge fuel and heat-up
(depending on boiler type).
Settings:
– Set room temperature for standard mode (normal
room temperature) and reduced mode (reduced
– Set DHW temperature
– Operating program, switching times for heating
circuits, plus further settings via plain text menu
on the display
Party and economy mode can be enabled via the menu
Integrated room temperature sensor for room
Installation location:
Weather-compensated mode:
Installation anywhere in the building.
Room temperature hook-up:
The integral room temperature sensor captures the actual room temperature and effects any necessary correction of the supply temperature.
Connection:
2-core lead 18 AWG, length max. 164 ft. (50 m)
(even if connecting several remote control units).
Never route sensor or communication cables near
120/240VAC line voltage wiring.
LV plug as standard delivery
Room temperature sensor
Separate room temperature sensor as supplement to the
Vitotrol 300A; to be used if the Vitotrol 300A cannot be installed inside the main living room or in a suitable position for temperature capture and adjustment.
Installation in the main living room on an internal wall opposite radiators.
Never install inside shelving units, in recesses, or immediately by a door or heat source (e.g. direct sun, fireplace, etc.).
Connect the room temperature sensor to the Vitotrol
300A.
Connection:
2-core lead with a cross-section of min AWG 18 (copper)
Max. lead length from the remote control: 99 ft. (30 m)
Never route sensor or communication cables near
120/240VAC line voltage wiring.
Specification
Sensor type
Permissible ambient temperature
Operation
Storage and transport
Viessmann NTC 10 k Ω at
77°F (25°C)
32 to 104°F (0 to +40°C)
-4 to 149°F (-20 to +65°C)
13
14
Control
Ecotronic Accessories
(continued)
Standard delivery:
Programming unit with 5 in. (125 mm) touchscreen
Wall socket for wall mounting
Installation materials for wall mounting
Connection:
CAN BUS data cable
Type of cable: LiYCY 2 x 2 x AWG 20 (min)
Shielded cable
A data cable is needed for each additional controller module. If a data cable of more than 33 ft. (10 m) is required, this may also be provided on site by the electrician.
The total length of all CAN BUS cables must not exceed
1000 ft. (300 m).
Vitoligno 300-C Technical Data
Vitotrol 350-C
CAN BUS subscriber
Remote control and cascade controller with control unit extension (CAN BUS subscriber). Optional use as remote control or cascade controller. With 5 in. (125 mm) color touchscreen for wall mounting.
Room controller with control unit extension:
Display of all information pertinent to the boiler
Charge indicator for the heating water buffer tank
Modbus TCP
Cascade controller with control unit extension:
Cascade of up to 4 solid fuel boilers and enabling of additional boilers as peak load boilers (oil/gas boilers)
All control circuits are displayed and operated on the
boiler
Charge indicator for the heating water buffer tank
Modbus TCP
Vitoligno 300-C Technical Data
Ecotronic Accessories
(continued)
Vitotrol 350-C connection options
Boiler, Vitotrol 350-C and controller modules connected in parallel
Control
Legend
A Boiler
B Vitotrol 350-C
C Mixing valve extension module
The Vitotrol 350-C cascade controller enables:
Display of all relevant information for each boiler in the cascade
Control of up to 4 Vitoligno 300-C boilers
Control of an external heat generator
(e.g. oil/gas boiler) via the lead boiler
Control of the boilers according to priority
Charge indicator for the heating water buffer tank
Legend
A Vitotrol 350-C
B Vitoligno 300-C boiler (lead boiler)
C Peak load boiler (e.g. oil/gas boiler)
D Vitoligno 300-C boiler (lag)
E Vitoligno 300-C boiler (lag)
15
Control
Ecotronic Accessories
(continued)
Vitoligno 300-C Technical Data
Heating circuit
Weather-compensated heating circuit control unit with digital time switch for setback mode according to individual day and seven-day program, with pump control unit, frost protection function, eco mode and limited supply temperature.
16
Legend
A Strap-on temperature sensor (PT 1000)
B Pump
C Mixing valve
Tank heating with flow control
If the temperature at the tank temperature sensor falls below the set value, the circulation pump for tank heating starts and the DHW tank is heated.
The flow rate of the heating water is controlled via the return temperature (flow control). This results in optimum stratification of the buffer tank with sustained high temperature at the tank flow. The heating periods
(individual day and seven-day program) can be adjusted via the integrated time switch.
PT1000 immersion temperature sensor with connecting
lead Ø a in., 78 in. (Ø 6 mm, 2 m long)
Strap-on temperature sensor PT1000
Note: The standard delivery does not include items
A and B .
Legend
A Pump
B Control valve
C Strap-on temperature sensor (PT1000)
D Immersion temperature sensor (PT1000)
Vitoligno 300-C Technical Data
Ecotronic Accessories
(continued)
Control
Sensors for use with Ecotronic control
Buffer tank temperature sensor set
3 buffer temperature sensors for operation with a heating water buffer tank.
With R½ x 11 in. (280 mm) sensor wells.
With connecting lead, for capturing temperatures in the heating water buffer tank.
5 buffer temperature sensors for operation with a heating water buffer tank.
With R½ x 11 in. (280 mm) sensor wells.
With connecting lead, for capturing temperatures in the heating water buffer tank.
On-site extension of the connecting lead:
2-core lead, length up to 198 ft. (60 m) of AWG 18
(copper) minimum.
Never route sensor or communication cables near
120/240VAC line voltage wiring.
Specification
Lead length
Sensor type
198 in. (5 m), fully wired
Viessmann PT1000
Permissible ambient temperature
Operation
Storage and transport
32 to 194°F (0 to +90°C)
-4 to 158°F (-20 to +70°C)
Solar collector temperature sensor
Immersion temperature sensor as collector temperature sensor with connecting lead for installation in the solar collector.
On-site extension of the connecting lead:
2-core lead, length up to 198 ft. (60 m) of AWG 18
minimum.
Never route sensor or communication cables near
120/240VAC line voltage wiring.
Specification
Lead length
Sensor type
198 in. (5 m), fully wired
Viessmann PT1000
Permissible ambient temperature
Operation
Storage and transport
-4 to 356°F (0 to +90°C)
-4 to 158°F (-20 to +70°C)
17
18
Control
Ecotronic Accessories
(continued)
Vitoligno 300-C Technical Data
Sensors for use with Ecotronic control (continued)
DHW tank temperature sensor (supplied)
Immersion temperature sensor as DHW tank temperature sensor with connecting lead.
In systems with DHW tanks from Viessmann, the tank temperature sensor is installed directly into the sensor well of the threaded elbow in the heating water solar return.
On-site extension of the connecting lead:
2-core lead, length up to 198 ft. (60 m) of AWG 18
minimum.
Never route sensor or communication cables near
120/240VAC line voltage wiring.
Specification
Lead length
Sensor type
198 in. (5 m), fully wired
Viessmann PT1000
Permissible ambient temperature
Operation
Storage and transport
32 to 194°F (0 to +90°C)
-4 to 158°F (-20 to +70°C)
Strap on temperature sensor
Specification
Lead length
Sensor type
198 in. (5 m), fully wired
Viessmann PT1000
Permissible ambient temperature
Operation 23 to 122°F
(–5 to +50°C) to
Storage and transport 23 to 158°F
(–13 to +70°C) to
Vitoligno 300-C Technical Data
Ecotronic Accessories
(continued)
Control
Mixing valve extension module
Three heating circuits with mixing valve, two heating circuits with mixing valve plus DHW heating or one heating circuit with mixing valve, one DHW heating and one solar circuit can be connected to the Ecotronic.
An additional, fourth heating circuit with mixing valve can be connected via the KMBUS.
Note: List of different connection options to the HKK PCB
of the Ecotronic and KM-BUS: See chapter
“Ecotronic control unit, overview of connection
options” (refer to page 11).
Mixing Valve Extension Module
Rated voltage
Rated frequency
Rated current
Power consumption
Max. ambient temp.
O peration:
120VAC
60 Hz
2A
4 W
32 to 104ºF (0 to 40ºC)
Storing or transporting:
Relay output for heating circuit pump:
Actuator torque:
Required runtime of the mixing valve motor for
90° ∢
-4 to+149ºF (-20 to+65ºC)
2 A, 120VAC
2.2 ft.lb (3 Nm)
120 sec.
Mixing valve motor kit
The mixing valve actuator is mounted directly on the
Viessmann ¾ to 2½” mixing valve.
The mixing valve actuator is a motor-driven control unit.
The rotational direction is reversible.
Specification
Rated voltage
Rated frequency
Power consumption
120VAC
60 Hz
4 W max.
Permissible ambient temperature
Operation 32°F to 104°F (0º C to 40°C)
Storage and transport -4°F to 149°F (-20°C to 65°C)
19
20
Control
Ecotronic Accessories
(continued)
Vitoligno 300-C Technical Data
Sensors for use with mixing valve extension module
Supply temperature sensor
Strap-on (included with mixing valve motor kit, see page 18)
Specification
Lead length 19 ft. (5.8 m), fully wired
Sensor type Viessmann NTC 10 k Ω at 77°F (25°C)
Permissible ambient temperature
Operation
Storage and transport
32 to 248°F (0 to +120°C)
-4 to 158°F (–20 to +70°C)
Immersion temperature sensor
To capture a temperature in a sensor well.
Specification
Lead length 19 ft. (5.8 m), fully wired
Sensor type Viessmann NTC 10 k Ω at 77°F
(25°C)
Permissible ambient temperature
Operation
Storage and transport
32 to 194°F (0 to +90°C)
-4 to 158°F (-20 to +70°C)
KM BUS distributor
For the connection of 2 to 9 devices to the control unit
KM BUS.
Specification
Lead length 10 ft. (3.0 m), fully wired
Permissible ambient temperature
Operation
Storage and transport
32°F to 104°F (0º C to 40°C)
-4°F to 149°F (-20°C to 65°C)
Vitoligno 300-C Technical Data
Accessories for Pellet Storage Room and Pellet Supply
Accessories
Pellet supply hose and return air hose
Only for pellet supply via vacuum system.
Only required if the length of 49 ft. (15 m) supplied with the room discharge system is insufficient or if the fuel is stored in a pellet silo.
7
2 in. (
7
50 mm), roll with 49 ft. (15 m).
With 6 broad clips.
Observe the maximum hose length of 99 ft. (30 m).
The pellet supply hose must be made from a single piece max. 49 ft. (15 m).
Broad clip
2 pieces,
7
2 in. (
7
50 mm)
For pellet supply hose and return air hose.
As adaptor at the pellet hopper, suction turbine, pellet silo or room discharge screw conveyor.
Fire protection collar
Only for pellet supply via vacuum system.
2 pieces
7
2 in. (
7
50 mm).
For pellet supply hose and return air hose.
For routing through an additional room.
Z bracket
2 pieces, 40 in. (1 m) long.
For storage room door or access hatches.
Pellet deflector shield
40 in. x 48 in. (1.0 x 1.2 m) long, plastic.
Flexible screw conveyor
118 in. (3 m) long.
157 in. (4 m) long.
For pellet supply from a pellet silo to the boiler.
Flexible screw conveyor (hose with screw conveyor),
can be trimmed.
2 hose clips.
21
22
Design
Additional Information
Water quality
Treatment for boiler feed water should be considered in areas with known problems, such as where a high mineral content and hardness exist. In areas where freezing might occur, it recommended that an antifreeze be added to the system water for protection against freezing. Please adhere to the specifications given by the antifreeze manufacturer. Do not use automotive silicatebased antifreeze. Please observe that an antifreeze/water mixture may require a back flow preventer within the automatic water feed and influence components such as diaphragm expansion tanks, radiation, etc. A 40% antifreeze content will provide freeze-up protection to
-10°F (-23°C). Do not exceed 50% antifreeze mix ratio and do not use antifreeze other than specifically made for hot water heating systems.
Total output (MBH) Total Hardness (ppm as ca CO
3
)
> 1 Total 680 200
> 680 to 255 150
The pH value of the heating water should be between 8.2 and 9.5
Vitoligno 300-C Technical Data
Oxygen diffusion barrier under floor tubing
The boiler warranty does not cover pressure vessel failure resulting from corrosion caused by the use of underfloor plastic tubing without an oxygen diffusion barrier.
Such systems without oxygen diffusion barrier must have the tubing separated from the boiler with a heat exchanger. Viessmann always recommends the use of underfloor plastic tubing with an oxygen diffusion barrier.
Boiler start-up
Vitoligno 300-C boilers does not require start-up by
Viessmann.
Sound attenuation
Please consult a professional engineer who is specialized in noise attenuation for advice.
The burner/boiler systems, circulation pumps and other auxiliary equipment used in heating systems generate noise.
This noise is transferred from the boiler room via floorboards, ceiling and walls to neighboring rooms and via the flue gas system as well as the ventilation air and exhaust air apertures into other rooms and into the open, where they may cause a nuisance.
To avoid this from happening, additional protective measures may be required which should be considered at the design stage.
Subsequent measures to reduce noise nuisance frequently require extensive effort and expenditure.
Frost protection
An antifreeze additive suitable for heating systems can be added to the fill water. The antifreeze manufacturer must verify its suitability, since otherwise damage to gaskets and diaphragms can occur as well as noise during heating operation. Viessmann accepts no liability for any resulting damage or consequential losses.
Vitoligno 300-C Technical Data
Venting Information
Design
Boiler vent connection
It is the responsibility of the vent manufacturer to provide the boiler vent adaptor. Dimensions of the flue outlet of the boiler are shown in the illustration and in the chart below.
Flue outlet dimensions a in. (mm) b in. (mm) c in. (mm) d in. (mm) e degrees
5.8 (147.1)
6.0 (153.4)
1.9 (47.1)
3.6 (92.5)
4.0
Connection on the flue gas side
Chimney
A chimney compliant with regulations relevant to the rated boiler heating output is required for efficient boiler operation. In Canada refer to CSA B365 (latest edition).
In the US refer to NFPA-211 (latest edition).
Note that in the lower output range of the boiler, flue gas temperatures below 194°F (90°C) may be generated.
Therefore connect the boiler to a moisture-resistant chimney.
If the boiler is to be connected to a chimney that is not moisture resistant, carry out a chimney calculation or request a chimney assessment.
Single acting barometric draft regulator
* The barometric draft regulator must be the same diameter
opening as the chimney for which the vent is sized.
For example, a 6 in. (150 mm) chimney would require a
6 in. (150 mm) barometric draft regulator. Do not size the barometric draft regulator to the breeching outlet of the boiler, unless the chimney is also intended to be of that diameter.
For room sealed operation and a draught > 0.02 “w.c.
(> 0.15 mbar), a barometric draft regulator approved for room sealed operation must be used.
Vitoligno 300-C, barometric draft regulator in the chimney.
IMPORTANT
* The flue size outlet on the boiler does not automatically determine the horizontal breeching, or the actual chimney diameter.
The chimney size must be designed for the actual boiler model and its respective input.
23
24
Design
Venting Information
(continued)
Vitoligno 300-C Technical Data
Flue gas connection
Install the flue pipe rising to the chimney (with 45º
possible).
Never push the flue pipe too far into the chimney.
Ensure the full flue gas path (incl. cleaning port)
gas-tight.
Never insert the flue pipe into the brickwork of the chimney. Instead, connect using a flexible flue pipe adaptor. Provide a cleaning port.
Acoustic transmission may arise from the flue gas
fan, which can lead to excessive noise. We recommend making the connection to the chimney with a flexible flue pipe adaptor.
Max. flue pipe length: 118 in. (3 m)
Provide the flue pipe with thermal insulation of at least
1 a in. (30 mm) thickness.
The use of a boiler flue connection with condensate trap is recommended because of the low flue gas temperatures in partial load operation.
The installation of this unit shall be in accordance with local codes. In the absence of local codes use:
- In Canada, CSA B365 installation code for solid fuel
burning appliances and equipment (latest edition).
- In USA, NFPA-211 standards for chimneys fire places,
vents and/or solid fuel burning appliances (latest edition).
Legend
A Boiler flue connection with condensate trap (for
B
H
K
Diagram of boiler with wall clearance
Flexible flue pipe inlet
C – F Possible installation location for the barometric
damper
G Flue pipe cross-section
Chimney cross-section
Thermal insulation
Explanation of possible installation locations:
C Very good control, venting effect limited by long flue pipe or small cross-section ratio flue: chimney; select this installation location only in extreme circumstances.
D Very good venting effect, good control; select this installation location only in extreme
circumstances.
E Very good venting effect, good control; retrofit only in case of masonry chimneys. In case of multi layered construction, installation only by qualified contractor; installation location E is
preferred .
F Limited control and venting. Due to the low soot levels, we recommend this installation for solid fuel boilers and lined chimneys.
Venting requirements
This boiler needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation air. Inadequate supply of combustion air can cause poisonous flue gases to enter living space which can cause severe personal injury or loss of life.
This boiler must be properly vented. Use a vent material certified for use with solid-fuel fired equipment.
This boiler’s venting system must be listed to ULC S-629
(Canada) or UL 103HT (USA) – Standard for Solid and liquid Fuel Chimneys. Use current revision of codes.
This boiler shall be connected to: a) a masonry chimney conforming to local regulations or,
in the absence of such regulations, to the requirements
of the National Building Code
or...
b) a certified factory-built chimney.
A flue pipe serving this boiler shall be constructed of steel or other suitable material with a melting point of not less than 2000°F (1100°C). Galvanized steel shall not be used.
Vitoligno 300-C Technical Data
Buffer Information
Design
Engineering information for systems with heating water buffer tank
Benefits for systems with heating water buffer tank.
Using a heating water buffer tank provides substantial benefits for the operation of a wood pellet boiler. As the boiler supplies heat to the heating circuits and the heating water buffer tank, the minimum boiler runtime of 30 minutes required for clean combustion is reached. After the boiler shuts down, any heat demand in the heating circuits will first be met from the heating water buffer tank before the boiler starts again. For system examples, refer to the Installation and Service Instructions.
Insufficient runtimes of the boiler can cause the following problems:
Formation of tar due to boiler temperatures being too low.
Impaired or prevented function of the lambda probe, the combustion grate and other boiler components due to contamination and condensate.
Increased power consumption due to multiple ignitions.
Reduced service life of the boiler due to frequent starts and stops. Under the following conditions, the wood pellet boiler must never be operated without a heating water buffer tank:
- When individual room control is installed.
- When the heat demand is significantly lower
than the rated boiler heating output. In these
buildings, a large proportion of the operating time
is under the lowest modulation level of the boiler.
- When the heating system is run with very small
heating loads in spring/autumn or e.g. only the
bathroom is heated.
- When an unusually high DHW demand or high DHW
peaks have to be met (e.g. hotels, large multi
occupancy blocks, showers in sports centres).
A wood pellet boiler requires 30 minutes to reach its
maximum heat output from standby. This period has
to be bridged with a heating water buffer tank.
- When air heating systems or even only individual
heater fans are started without lead time for the
boiler.
- When a solar thermal system is incorporated
into a low temperature heating system.
- When it is not possible to guarantee the minimum
runtime of 30 minutes in all operating situations.
Design/engineering information
The sizing of the heating water buffer tank determines the convenience provided by the pellet heating system.
The heating water buffer tank ensures rapid heating in the morning and adequate heat transfer under all operating conditions and extends the boiler standstill periods. As long as funding, standards and laws do not require a larger capacity heating water buffer tank, the following values can be used for sizing:
Vitoligno 300-C (model 32): 2.3 USG/MBH (30 L/kW) rated heating output.
Examples:
109.2 MBH x 2.3 USG/MBH = 253.3 USG
(32 kW x 30 L/kW = 960 L)
(minimum buffer tank volume)
25
Design
Pellet Storage and Pellet Supply Information
Vitoligno 300-C Technical Data
Information regarding the bulk delivery of pellets by truck
26
Legend
A Return air connector
B Fill connector
C Pellet storage room
Pellets are delivered by pellet delivery truck when bought in bulk. The size of the delivery tanker must be taken into consideration when planning access.
Access could therefore be affected by weight and/or height restrictions, narrow or steep access routes, tight bends or a lack of turning space.
Pellet storage rooms should, where possible, be located alongside an external wall to leave the fill hoses as short as possible. Because of fluctuating air volumes, handling with fill hoses in excess of 99 ft. (30 m) becomes difficult.
Contact your pellet supplier for access to delivery requirements.
Vitoligno 300-C Technical Data
Pellet Storage and Pellet Supply Information
(continued)
Design
Fuel consumption and storage room design
Building heat load
MBH (kW)
10.2 (3)
17.0 (5)
23.7 (8)
34.1 (10)
41.0 (12)
51.2 (15)
68.2 (20)
* Annual consumption
US ton
(metric ton)
1.3 (1.2)
2.2 (2.0)
3.5 (3.2)
4.3 (3.9)
5.2 (4.7)
6.5 (5.9)
8.6 (7.8)
85.3 (25) 10.8 (9.8)
119.4 (35) 15.1 (13.7)
153.5 (45) 19.4 (17.6)
170.6 (50) 21.5 (19.5)
204.7 (60) 25.9 (23.5)
238.9 (70) 30.3 (27.5)
273.0 (80) 34.2 (31)
307.0 (90) 38.6 (35)
341.2 (100) 43.0 (39)
Volume for annual demand cu ft. (m³)
Storage room without a sloping floor cu ft. (m³)
63.6 (1.8)
106.0 (3.0)
169.5 (4.8)
212.0 (6.0)
254.2 (7.2)
317.8 (9.0)
423.8 (12)
529.7 (15)
741.6 (21)
953.5 (27)
1059.4 (30)
1271.3 (36)
1483.2 (42)
1695.1 (48)
1907.0 (54)
2118.9 (60)
* Fuel consumption will vary depending on climate and
length of the heating season.
Fuel storage in the pellet storage room
Sizing the pellet storage room
The storage room should ideally be rectangular and large enough to accommodate a year’s supply of fuel. This reduces the number of deliveries.
The size of the storage room depends on the heat load of the building which in turn is subject to the building’s heat demand. The floor area should not be less than 7 x 10 ft.
(2 x 3 m).
Calculating the annual pellet demand
The volume of the annual pellet demand subject to the building heat load can be calculated with the following rule of thumb:
Volume for annual demand = building heat load in
MBH x 6.2 ft 3 /MBH (kW x factor 0.6 m 3 /kW)
1. For storage rooms without sloping floor, the volume
for the annual demand corresponds to the volume of
the storage room:
Storage room volume without sloping floor volume =
volume for annual demand
2. For storage rooms with sloping floors, the unused
space has to be taken into account, to ensure the
volume is sufficient for the annual demand.
The sloping floor causes approximately 1/3 of the
volume to be lost:
Storage room volume with sloping floor = 1.5 x
volume for annual demand
Conversion of storage room volume to pellet quantity:
Pellet quantity in lb = storage room volume in ft 3 x 40.6 lb/ft 3
(Pellet quantity in t = storage room volume in m 3 x 0.65 t/m 3 )
Sample calculation for pellet storage room with sloping floor
Heat load of the building: 41 MBH (12 kW)
Calculation of volume for annual demand:
41 MBH x 6.2 ft 3 /MBH = 254.2 cu ft.
(12 kW x 0.6 (m 3 /kW) = 7.2 m 3 )
Calculation of annual pellet demand:
254.2 x 40.6 lb/ft 3 = 10320.5 lb
(7.2 x 0.65 t/m 3 = 4.7 metric tons)
Calculation of storage room volume with sloping floor:
1.5 x 254.2 cu ft = 381.3 cu ft.
(1.5 x 7.2 m 3 = 10.8 m 3 )
Calculation of floor area of storage room with a room height of 7.6 ft. (2.3 m):
381.3 cu ft/7.6 ft = 50.2 ft 2 (10.8 m 3 /2.3 m = 4.7 m 2 )
A minimum floor area of 7 x 10 ft (2 x 3 m) is adequate to store a year’s supply of fuel.
Calculation of stored energy:
Annual pellet demand in kg x net calorific value of the pellets in 10320.5 lb x 7.1 MBH/lb = 73275 MBH
(kWh/kg 4700 kg x 4.6 kWh/kg = 21,620 kWh)
Legend
A Fill connector
B Return air connector
C Clear space
D Sloping floor
E Empty space
F Viessmann discharge system
G Available volume = h of the room
27
28
Design
Pellet Storage and Pellet Supply Information
(continued)
Vitoligno 300-C Technical Data
Wood pellet storage must be installed observing local regulations in addition to National Codes (in the absent of such codes use CSA B365 Installation Code for Solid Fuel
Appliances and Burner Equipment.
The General requirements of the pellet storage room and required system components are…
When storage facilities for wood are required, the wood
should be kept at least 1.5 m (5 ft) from then heating
appliance.
The space around the wood-burning appliance should
be kept clean and free of litter and wood residues.
Requirement for storing particulate fuels (including wood pellets);
Storage facilities for particulate fuels inside buildings,
other than those that form an integral part of the should
(a) effectively isolate any insects, vapors, and airborne
contaminants associated with the fuel from contact
with, and transmission to, other parts of the building;
(b) be partitioned from the remainder of the building by
a 0.5 h fire separation;
(c) be constructed of materials that provide sufficient
structural strength and are resistant to decay;
(d) not be located over a sewer or drain opening or at
the low point of the floor;
(e) have a smoke detector or smoke alarm located at
ceiling level within 3 m (10 ft) of the opening of the
storage
(f) be provided with a means of removing moisture,
limiting excess temperatures, and venting air to the and
(g) be located such that no access opening is closer
than 1.5 m (5 ft) to the appliance.
Electrical devices such as switches and motors should
be located outside the storage facility, and electric
wiring and lighting required in the storage facility should
be suitable for Class 2, Division 2, Group F locations,
as specified in the Canadian Electrical Code, Part I.
Openings for access should be provided with doors that
(a) are gasketed; and
(b) have a secure, child-proof mechanism.
Every pipe or duct intended to operate at temperatures
greater than or equal to 195°F (90°C) should be located
such that fuel cannot be stored in contact with it.
Where fuel is to be drawn automatically from the
storage facility by conveyors or screw augers, means
should be provided to prevent burnback in the fuel
supply
train.
Where fuel is to be pneumatically forced into the
storage facility, provision should be made to
(a) prevent the pressurization of the storage facility;
(b) provide an electric ground connection for the fuel
supply chute or hose to prevent the buildup of a
static electrical charge; and
(c) provide for dust control during the loading process.
A suitable fire extinguisher should be provided and be
Fire separation must be built in accordance with;
For Canada) NBCC (National Building Code of Canada)
most recent edition, as well as any other province,
territory, local codes and/or regulations
For USA) IBC (International Building Code) most recent
edition, as well as any other state, local codes and/or
regulations.
Information regarding the pellet storage room
The pellet storage room must be designed to allow easy cleaning. To ensure a permanent interruption free fuel supply to the boiler, the fuel store must be cleaned regularly. This includes carefully removing fines in the fuel store. After two to three deliveries, the fuel store should be cleaned prior to the next pellet delivery. Over time, pellet dust accumulates in the lower part of the fuel store and can cause faults in the fuel supply.
Wood pellets of inferior quality with an increased percentage of fines cause increased accumulations of dust in the storage room. However, fines are also produced by the mechanical stresses that wood pellets are subjected to during transport and injection (injection pressure, installations, etc.) into the storage room. pellets certified to CANPlus Grade A1 or PFI (Standard or Premium Grade) ensures proper pellet quality, through strict wood pellet requirements.
This involves monitoring the entire value chain from production to delivery. Manufacturers and suppliers of high quality wood pellets can be found at www.pelletfuel.
org,www.pellet.org.
Vitoligno 300-C Technical Data
Pellet Storage and Pellet Supply Information
(continued)
Legend
A Protective boards at the entrance to the storage room
B Discharge area, screw conveyor system
C Deflector
D Discharge to flexible screw conveyor or to vacuum
system
E Min./max. length of discharge area
F Max. storage room length
G Return air connector
H Fill connector
K Slanted panel for balancing storage room length / extraction area length
Design
Wood pellet storage
Guidelines regarding wood pellet storage;
The pellet storage room must be dry, as pellets will
swell up markedly if exposed to moisture. This leads to
substantial difficulties in supplying pellets to the boiler.
The pellet storage room must be of solid, dust-tight
construction, as loading pellets into the room creates
dust and the pellets will exert high pressure on the walls.
The pellet storage room or the installation room for
prefabricated stores must be vented. Vents should not
be positioned directly below windows or supply air
apertures. Vents should be closed during filling, so that
the vacuum fan can create a slight negative pressure in
the storage room.
Doors or access hatches into the pellet storage room
must open outwards and must be dust-tight (with an gasket).
Fit protective boards on the inside of the door opening,
so that pellets do not press against the door.
There should be no electrical installations inside the
pellet storage room. Essential electrical installations
must be of explosion-proof type, in accordance with
Avoid the installation of water pipes inside the storage
room because of condensation and the risk of burst
pipes.
Pellet storage rooms should be equipped with a fill
connector and a return air connector G (see page
31) with a Storz coupling, type A, Ø 4 in. (Ø 100 mm)
(fire hose connector), with extension pipes leading into
the pellet storage room. Pipes should be metal,
connected to the brickwork and grounded.
Fit a deflector C opposite the fill connector to protect
the pellets and the brickwork.
The pellet storage room must be free from foreign
bodies (small stones, wood particles, etc.).
The supply hoses and return air hoses for the vacuum
system must be grounded, must not be routed outside
and should be protected against temperatures in excess
of 140°F (60°C).
The wall outlet for the room discharge should be sealed
from the storage room side with fireproof material (e.g.
plastered).
The pellet storage room must be inaccessible to
children. The wood pellet boiler should be shut down
approximately one hour before the storage room is
filled. The storage room should be sufficiently vented
before anyone enters.
29
30
Design
Pellet Storage and Pellet Supply Information
(continued)
Vitoligno 300-C Technical Data
Room discharge with screw conveyor system
The screw conveyor system may be up to 252 in. (6.4 m) long. The available depth of the storage room can be extended to up to 272 in. (6.9 m) by installing a third sloping floor between the screw conveyor terminal module and the storage room wall.
Legend
A Sloping floor
B Discharge screw conveyor
C Mounting panel
Vitoligno 300-C Technical Data
Pellet Storage and Pellet Supply Information
(continued)
Connector spacing ≥ 19 f in. ( ≥ 500) mm
Legend
A Fill connector
B Return air connector
Connector spacing <19 f in. (<500)
Legend
A Fill connector
B Return air connector
Design
Fill connector and return air connector
Arrange the connectors so that no overpressure can develop in the pellet storage room during the filling process.
Keep the return air connector unrestricted, even when the maximum filling level in the storage room has been reached
(see page 27). The connectors should be located as high as possible inside the pellet storage room to enable it to be filled to the maximum.
The fill connectors should be at least 8 in. (20 cm) below the ceiling to prevent pellets hitting the ceiling
(fit protective boards if the ceiling is plastered). Choose a position for the connectors on the narrow side of the storage room. Pellets are blown approx. 158 in. to 196 in.
(4 m to 5 m) with straight fill connectors.
Where a 90° bend fitting is located before the entry into the storage room, fit a straight pipe of at least 40 in. (1 m) length on the other side to protrude into the storage room.
This enables the pellets to reach the required filling velocity and therefore the required fill width.
Grounding
Ground all connectors to prevent static electricity building up during the filling process. Generally the connection of each pipe element to the equipotential bonding of the building is recommended. At the very least, connect each pipe element securely to the brickwork, either by setting the pipe into the brickwork (without thermal insulation) or by means of pipe clips set into the brickwork.
Connector length and location
The length of the fill connector depends on the distance to the return air connector. Connector spacing of <20 in.
(< 500 mm) may occur if both connectors are set into a cellar window.
If connectors are to be located on the long side of the storage room, we recommend alternating the filling between both connectors, which ensures more efficient filling of the storage room. In any case, both connectors must be grounded. Install a deflector opposite both connectors.
Alternating filling
Legend
A Deflector
B Fill and return air connectors
31
Design
Pellet Storage and Pellet Supply Information
(continued)
Vitoligno 300-C Technical Data
Internal pellet storage room
If the fill and return air connectors are to be routed through an adjacent room, clad them with a material compliant with 1.5 hr fire separation (rock wool or similar). Ground each extension pipe using pipe clips.
Plastic pipes should not be used as extension pipes.
Legend
A Connector
B Fire-resistant cladding
C Extension pipe
D Pipe clip
Connector installation options
Setting into brickwork
The connector is set into the outlet with mortar without thermal insulation.
32
Legend
A Fill connector
B Wall outlet Ø 6 in. (Ø 150 mm) (on-site) for
fill
Wall installation with screws
The connector is secured to the outside wall with screws and grounded with a pipe clip.
Legend
A Fill connector
B Screws
C Pipe clip for grounding
D Wall outlet Ø 4 in. (Ø 110 mm) (on-site) for
Vitoligno 300-C Technical Data
Pellet Storage and Pellet Supply Information
(continued)
Design
Window installation with screws
A plate is set into the window opening. The connector is fitted through the plate, secured with screws and grounded with a pipe clip.
Legend
A Fill connector
B Screws
C Pipe clip for grounding
D Outlet Ø 4 in. (Ø 110 mm) (on-site) for
fill A
E Window opening
Installation in the light well
Wall installation and installation in the window opening are both possible.
The reduced fill and return air connectors are each pushed into a 45º bend, which in turn is located in an extension pipe pushed through the wall or the window opening.
Legend
A Fill connector
B Pipe clip for grounding
C Extension pipe
D Wall outlet Ø 4 in. (Ø 110 mm) (on-site)
or
Outlet
E 45 º bend
4
Storing fuel in a pellet silo
Benefits:
Flexible installation location
Quick, easy installation
Completely dustproof
Discharge system freely accessible for maintenance work
Fuel extraction via suction system or flexible auger
Sizing the pellet silo
Where possible, size the pellet silo so that enough pellets can be stored to cover the annual fuel demand.
Note: formula sizing can be found on page 28.
Pellet silo (adjustable height)
As textile/metal combination, delivered in parts.
Standard delivery:
Powder coated steel frame
Horizontal filler neck
Pellet silo made from UV protected fabric
Installation material
Filling system with retainer, Storz-A couplings, caps clamps
Discharge unit to be ordered separately (starting on page 34).
33
Design
Pellet Storage and Pellet Supply Information
(continued)
Vitoligno 300-C Technical Data
34
Pellet silos
Mode
2.2
3.1
3.9
5.9
7.3
Dimensions a in. (mm) b in. (mm)
65 (1650)
77 (1950)
88 (2230)
100 (2540)
119 (3010)
Max. tonnage (at bulk density)
Mode
85 (2150)
85 (2150)
85 (2150)
99 (2500)
99 (2500)
Assembled height (steel frame)
in. (mm)
Ceiling height
65 (1650)
65 (1650)
65 (1650)
79 (2000)
79 (2000)
Room height min. 77 in. (1.8 m)
Room height min. 85 in. (2.15 m)
Room height min. 99 in. (2.5 m)
2.2 ton (metric ton)
1.9 (1.7)
2.5 (2.2)
--
3.1
ton (metric ton)
2.5 (2.3)
3.4 (3.1)
--
3.9
ton (metric ton)
3.2 (2.9)
4.3 (3.9)
--
5.9
ton (metric ton)
--
5.1 (4.6)
6.5 (5.9)
in. (mm)
77-85 (1800-2150)
77-85 (1800-2150)
85-99 (2150-2500)
85-99 (2150-2500)
85-99 (2150-2500)
7.3
ton (metric ton)
--
5.8 (5.3)
8.0 (7.3)
Legend
A
B
C
E
F
G
Return air connector
Fill connector
Deflector
D Vitoligno 300-C
Connection unit, flexible screw conveyor
Flexible screw conveyor
Discharge screw conveyor
On-site requirements of the installation room
For storage room requirements, see page 26. The pellet silo can be installed in any suitable load bearing room such as a basement. The variable container height enables an optimum utilisation of the available space. For installation purposes, the installation room needs to be 4 in. (100 mm) wider than the pellet silo. There must be no pointed or sharp objects inside the installation room, otherwise the fabric of the pellet silo can be damaged. The fabric must not come into contact with damp walls, must not rub against walls or be exposed to direct sunlight.
Installation outdoors requires a weather-proof enclosure.
The load-bearing capacity of the substrate must be assured in accordance with the details in the following diagrams.
Particularly with “floating” concrete (unfinished concrete
+ insulation layer + slab), there is a risk that they may not meet the specified requirements. Secure the pellet silo to its support surface.
Pellet supply from the pellet storage room to the boiler pellet supply via flexible screw conveyor — room discharge with screw conveyor system.
If the pellet storage room is located very close to the boiler installation room. The pellets can be conveyed directly to the rotary lock valve via a flexible screw conveyor. A pellet hopper at the boiler is then not required.
Vitoligno 300-C Technical Data
Pellet Storage and Pellet Supply Information
(continued)
Design
Depth 71 in. (1.8 m) A
Depth 90 b in. (2.3 m) B
Depth 114 a ft. (2.9 m) C
Depth 134 in. (3.4 m) D
Complete system for room discharge with screw conveyor system:
Flexible screw conveyor, 118 or 157 in. (3 or 4 m)
long.
Screw conveyor system for different room depths
and connection to a flexible screw conveyor.
Comprising:
– 1 wall module screw conveyor system 25 a in. (0.64 m) long 1
– 1 screw conveyor terminal module 44 in. (1.14 m) long 4
– 3 mounting brackets 5
– 1 flexible screw conveyor 6
Comprising:
– 1 wall module screw conveyor system 25 a in. (0.64 m) long 1
– 1 screw conveyor module 19 f in. (0.5 m) long 2
– 1 screw conveyor terminal module 44 in. (1.14 m) long 4
– 4 mounting brackets 5
– 1 flexible screw conveyor 6
Comprising:
– 1 wall module screw conveyor system 25 a in. (0.64 m) long 1
– 1 screw conveyor module 44 in. (1.14 m) long 3
– 1 screw conveyor terminal module 44 in. (1.14 m) long 4
– 4 mounting brackets 5
– 1 flexible screw conveyor 6
Comprising:
– 1 wall module screw conveyor system 25 a in. (0.64 m) long 1
– 1 screw conveyor module 19 f in. (0.5 m) long 2
– 1 screw conveyor module 44 in. (1.14 m) long 3
– 1 screw conveyor terminal module 44 in. (1.14 m) long 4
– 5 mounting brackets 5
– 1 flexible screw conveyor 6
35
Design
Pellet Storage and Pellet Supply Information
(continued)
Vitoligno 300-C Technical Data
Depth 161 b in. (4.1 m)
Depth 205 in. (5.2 m)
Depth 252 in. (6.4 m)
(max. room depth)
F
G
E Comprising:
– 1 wall module screw conveyor system 25 a in. (0.64 m) long 1
– 2 screw conveyor module 44 in. (1.14 m) long 3
– 1 screw conveyor terminal module 44 in. (1.14 m) long 4
– 5 mounting brackets 5
– 1 flexible screw conveyor 6
Comprising:
– 1 wall module screw conveyor system 25 a in. (0.64 m) long 1
– 3 screw conveyor module 44 in. (1.14 m) long 3
– 1 screw conveyor terminal module 44 in. (1.14 m) long 4
– 6 mounting brackets 5
– 1 flexible screw conveyor 6
Comprising:
– 1 wall module screw conveyor system 25 a in. (0.64 m) long 1
– 4 screw conveyor module 44 in. (1.14 m) long 3
– 1 screw conveyor terminal module 44 in. (1.14 m) long 4
– 7 mounting brackets 5
– 1 flexible screw conveyor 6
Note: Clearance for installation (depth) at least 4 in.
(100) mm between the screw conveyor system and the wall.
Wall duct for screw conveyor discharge from the pellet store
36
Legend
A Pellet sensor
B Room discharge adaptor, part of the standard delivery of Vitoligno 300-C for flexible screw
conveyor
Vitoligno 300-C Technical Data
Pellet Storage and Pellet Supply Information
(continued)
Legend
A Return air connector
B Fill connector
C Deflector
D Pressure hose
E Vacuum hose
F Vitoligno 300-C with pellet hopper
G Discharge screw conveyor
Design
Pellet supply via vacuum system / room discharge with screw conveyor system
Can be used if the pellet storage room is not immediately adjacent to the installation room. Pellets can be transported up to a distance of 49 ft. (15 m) and to a height differential of 197 in. (5 m). The flexible positioning of the vacuum supply system enables installations even in tight spaces.
To determine the required hose length, calculate
the distance between the pellet hopper connector
and the pellet discharge point from the pellet
storage room or the pellet silo.
Use the shortest path from the storage room to the
boiler. Route hoses so that they cannot be stepped on.
Never kink the hoses; the smallest bending radius
should be 12 in. (300 mm).
Hoses should be routed as straight and level as
possible. If hoses are routed up and down several
times, some pellets will not be transported from the
lower lying areas.
Hoses must be grounded to prevent static electricity
building up during pellet handling.
The pellet supply hose should be made from one
piece, whilst the return air hose can be made up of
several pieces. The connection piece should be made
of metal to ensure continuous grounding.
Never expose the hoses to temperatures above 140ºF
(60ºC), i.e. never route them near heating pipes or flue
pipes that are not thermally insulated.
Never route outdoors (risk of becoming brittle due to
Complete system for room discharge with vacuum system:
Pellet supply hose and return air hose 7 2 in. (50 mm),
Max. supply hose length: 49 ft. (15 m)
Max. length supply hose plus return air hose: 99 ft. (30 m)
The supply hose must be made from a single piece.
Screw conveyor system for different room depths and
connection to a vacuum system.
37
Design
Pellet Storage and Pellet Supply Information
(continued)
Vitoligno 300-C Technical Data
Depth 71 in. (1.8 m)
Depth 90 b
Depth 114
Depth 161
in. (2.3 m) a b
B
in. (2.9 m)
Depth 134 in. (3.4 m) D
in. (4.1 m)
Depth 205 in. (5.2 m)
Depth 252 in. (6.4 m)
(max. room depth)
A
F
G
C
E
Comprising:
– 1 pellet supply and return air hose 50 ft. (15 m) long 1
– 1 wall module vacuum system 25 a in. (0.64 m) long 2
– 1 screw conveyor terminal module 44 in. (1.14 m) long 5
Comprising:
– 1 pellet supply and return air hose 50 ft. (15 m) long 1
– 1 wall module vacuum system 25 a in. (0.64 m) long 2
– 1 screw conveyor module 19 f in. (0.5 m) long 3
– 1 screw conveyor terminal module 44 in. (1.14 m) long 5
Comprising:
– 1 pellet supply and return air hose 50 ft. (15 m) long 1
– 1 wall module vacuum system 25 a in. (0.64 m) long 2
– 1 screw conveyor module 44 in. (1.14 m) long 4
– 1 screw conveyor terminal module 44 in. (1.14 m) long 5
Comprising:
– 1 pellet supply and return air hose 50 ft. (15 m) long 1
– 1 wall module vacuum system 25 a in. (0.64 m) long 2
– 1 screw conveyor module 19 f in. (0.5 m) long 3
– 1 screw conveyor module 44 in. (1.14 m) long 4
– 1 screw conveyor terminal module 44 in. (1.14 m) long 5
Comprising:
– 1 pellet supply and return air hose 50 ft. (15 m) long 1
– 1 wall module vacuum system 25 a in. (0.64 m) long 2
– 2 screw conveyor module 44 in. (1.14 m) long 4
– 1 screw conveyor terminal module 44 in. (1.14 m) long 5
Comprising:
– 1 pellet supply and return air hose 50 ft. (15 m) long 1
– 1 wall module vacuum system 25 a in. (0.64 m) long 2
– 3 screw conveyor module 44 in. (1.14 m) long 4
– 1 screw conveyor terminal module 44 in. (1.14 m) long 5
Comprising:
– 1 pellet supply and return air hose 50 ft. (15 m) long 1
– 1 wall module vacuum system 25 a in. (0.64 m) long 2
– 3 screw conveyor module 44 in. (1.14 m) long 4
– 1 screw conveyor terminal module 44 in. (1.14 m) long 5
Wall duct for screw conveyor discharge from the pellet store
Note: Clearance for installation (depth) at least 4 in.
(100 mm) between the screw conveyor system and the wall.
38
Legend
A Pellet sensor
B Pellet hose connector
Vitoligno 300-C Technical Data
Pellet Storage and Pellet Supply Information
(continued)
Design
Pellet supply from the pellet silo to the boiler :
Pellet supply by flexible screw conveyor (screw conveyor
+ pellet silo)
If the pellet silo is located very close to the boiler installation room.
The pellets can be charged directly to the rotary lock valve via a flexible screw conveyor.
A pellet hopper at the boiler is then not required.
Legend
A Return air connector
B Fill connector
C Pellet silo
D Flexible screw conveyor with connection to the pellet silo
E Connection unit, flexible screw conveyor
F Vitoligno 300-C
Pellet supply by vacuum system
(vacuum system + pellet silo)
Can be used if the pellet silo is not immediately adjacent to the installation room. Pellets can be transported up to a distance of 49 ft. (15 m) and to a height differential of
197 in. (5 m).
Legend
A Pellet silo
B Return air connector
C Fill connector
D Pressure hose
E Vacuum hose
E Vitoligno 300-C
G Vacuum hose
H Pressure hose
39
Scan for digital copy of this document
Vitoligno 300-C Technical Data
Printed on environmentally friendly (recycled and recyclable) paper.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project