Viessmann Versatronik 300 Cascade Control Versatronik Controls & Gateway Technical information
Below you will find brief information for Versatronik 300 704083, Versatronik 300 704092. These cascade controls are engineered to stage Viessmann LON-enabled boilers. They offer features like outdoor reset functionality, interlock for system enable/disable, and auxiliary heat demand input. The BACnetIP model (704092) allows for integration with BACnet Building Management Systems. Proper installation and configuration are vital for optimal operation.
Advertisement
Advertisement
Versatronik
®
300
Cascade Control
704083 w/o BACnetIP
704092 with BACnetIP
Applicable Controls
Vitotronic 100, GC1/GC1B
Vitotronic 300, GW2
Vitotronic 300, GW5B
Vitotronic 200, HO1/HC1
Vitodens 200 B2HA
Technical, Installation and Configuration Information
Cautionary Statement
The information presented in this document is only to be used by those familiar with its application and use.
IMPORTANT
Read and save these instructions for future reference
About these instructions
!
Take note of all symbols and notations intended to draw attention to potential hazards or important product information. These include “WARNING”, “CAUTION” and “IMPORTANT”. See below.
!
WARNING
Indicates an imminently hazardous situation which, if not avoided, could result in death, serious injury or substantial product/property damage.
Warnings draw your attention to the presence of potential hazards or important product information.
!
CAUTION
Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product/property damage.
Cautions draw your attention to the presence of potential hazards or important product information
CAUTION
Static sensitive components may be damaged by improper handling or work within the control. Ensure all possible measures are taken to eliminate build-up of static electricity.
IMPORTANT
Helpful hints for installation, operation or maintenance which pertains to the product.
Trademark Information
Viessmann® and Vitotronic® are trademarks of Viessmann Werke
GmbH & Co KG registered in the
United States and other countries.
Please visit: www.viessmann.ca www.viessmann.us
Echelon®, LON®,
LONWORKS®, i.LON®, LNS®,
LONMARK®, Neuron®, and the
LonUsers logo are trademarks of Echelon Corporation registered in the United States and other countries.
Please visit: www.echelon.com
BACnet® is a registered trademark of the American
Society of Heating,
Refrigerating and Air-
Conditioning Engineers, Inc.,
1791 Tullie Circle NE, Atlanta,
GA 30329.
For more information please visit: www.bacnet.org
www.ashrea.org
2
Important Regulatory and Installation Requirements
Codes
The installation of this unit must be in accordance with local codes.
All electrical wiring is to be done in accordance with the latest edition of CSA C22,1 Part 1 and/ or local codes. In the U.S. use the National Electrical Code
ANSI/NFPA 70.
The installing contractor must comply with the Standard of
Controls and Safety Devices for
Automatically fired Boilers, ANSI/
ASME CSD-1 where required by the authority having jurisdiction.
Working on the equipment
The installation, adjustment, service and maintenance of this unit must be done by a licensed professional heating contractor or persons who are qualified and experienced in the installation, service, and maintenance of similar products. There are no user serviceable parts on this control.
Power supply
Install power supply in accordance with the regulation of the authorities having jurisdiction or in absence of such requirements, in accordance with
National Codes.
Please carefully read this manual prior to attempting installation.
Any warranty is null and void if these instructions are not followed.
The completeness and functionality of field supplied electrical controls and components must be verified by those installing the device
!
WARNING
More than one live circuit. See wiring diagram in this manual.
Turn off power supply to control and damper/blower before servicing. Contact with live electrical components can result in serious injury or death
Purpose of Device and Operation
The Versatronik 300 Cascade control is designed to stage
Viessmann LON enabled boilers and boiler controls via a CAT5 wire connection LON communication.
3
Versatronik 300
This page is intentionally left blank
4
Control Installation
Control Information
Section 2
Section 2.0
Information Page
What’s in the box?
Mounting Versatronik 300 control
6
7
Outdoor Sensor connection (if required)
Common Supply Temperature Sensor Immersion
Return Temperature Sensor Immersion
Interlock for system enable/disable
8
9
9
10
AUX Heat Demand Input
AUX 0-10VDC Input BMS Common Supply Set Point
Communication Connections Vitotronic 100, GC1 and GC1B
Communication Connections Vitotronic 300, GW5B
Communication Connections Vitodens 200, WB2B w/HC1 control
Communication Connections Vitodens 200, WB2B W/HO1 control
Communication Connections Vitodens B2HA
Communications End of Line Resistor
Communications BACnet Unit 704092 only
Configuration of BACnet IP Settings
Configuration of BACnet Device Settings
BACnet Data Points Overview
Combustion Air Functions
120VAC Output Connections (Pump, AUX output, Fault)
120VAC Power Supply Connection
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
Installation
What’s in the box?
Un-boxing the Control
In the box, you will find the following:
Qty. Description
2 Immersion Sensor LLH Supply/Return 10K
1 Outdoor Temperature Sensor 5K
1 Versatronik 300 Manual
1 Spare fuse Sub-miniature T160mA
Part Number
211059
211062
394031
255071
255017
213018
6
Installation
Mounting Versatronik 300 Control
2
4
1
3
1
Mounting Steps
1. Mount Versatronik 300 in a convenient location near the connected boiler controls control.
Remove cover by loosening the two screws on either side of base to release the cover.
2. Fasten base to wall using field-supplied screws/fasteners.
3. Remove knockout and installed wire strain relief or box connector. Removal of remaining knockouts is required to make further connections.
4. Once all of the 120VAC and low voltage connections are complete and verified, reinstall the cover from Step 1.
7
!
WARNING
When extending wire there is the possibility of exposure to electromagnetic interference. Avoid running wires beside or near high voltage 120/240
VAC conductors. If proximity to high voltage conductors cannot be avoided, use stranded, twisted pair of shield design wire. Ensure that only one end of the shielding is grounded.
Outdoor Temperature Sensor Connections (If Required)
2
3
1
Wiring Steps
1. Install outdoor temperature sensor on outside of structure.
2. Connect field supplied wiring to terminals inside of sensor. Ensure wiring is run through strain relief at bottom of sensor housing.
Reinstall sensor cover onto sensor backing.
3. Run field supplied wiring between sensor and
Versatronik 300 control.
4. Connect wires to the S1 wire terminals inside of the control.
Note:
In applications which are not outdoor reset based, it is not necessary to install the sensor.
Activation of the sensor only occurs when outdoor reset is enabled in the set up menu.
4
Important
The outdoor temperature sensor should be mounted 2 to 2.5 metres above ground level on the north or north-west facing wall of the building. In the case of multi-storey buildings, it should be mounted in the upper half of the second storey. Make sure that the sensor is not located over windows, doors and air vents, nor immediately beneath a balcony or guttering. Do not paint over the outdoor temperature sensor housing.
8
!
WARNING
When extending wire there is the possibility of exposure to electromagnetic interference. Avoid running wires beside or near high voltage 120/240
VAC conductors. If proximity to high voltage conductors cannot be avoided, use stranded, twisted pair of shield design wire. Ensure that only one end of the shielding is grounded.
Supply & Return Temperature Sensor (Immersion)
3
1
2
Installation Instruction
The immersion sensor supplied with the control is designed to be used with an immersion well.
Should it be necessary to be used as a strap-on sensor, ensure the sensor is tight against the pipe. Where possible, conductive paste can be used along with a metal strap for fastening.
Avoid using wire ties as the plastic will become brittle and loosen.
Once securely fastened, cover with pipe insulation.
1. Ensure that sensor is pushed completely into temperature well.
2. Use temperature well clip to ensure that sensor remains securely in place.
3. Alternate method of securing sensor to pipe should there be no immersion temperature well.
4. Wire the sensor to the S2 terminals inside of the Versatronik 300 control.
5
4
Return Temperature Sensor (Optional)
Installing a return temperature sensor will allow the temperature differential to be seen by the user. There is no control logic associated with the extra sensor.
5. Connect leads of sensor to terminal connections at S3 input.
Securely mount onto pipe or install in correct immersion sensor well like that of the supply temperature sensor.
9
!
WARNING
When extending wire there is the possibility of exposure to electromagnetic interference. Avoid running wires beside or near high voltage 120/240
VAC conductors. If proximity to high voltage conductors cannot be avoided, use stranded, twisted pair of shield design wire. Ensure that only one end of the shielding is grounded.
INT Interlock for Boiler Disable
BMS
or mechanical control
R
1
2
3
4
Installation Instruction
The boiler interlock is designed for any potentialfree, dry contact to be connected to the INT terminals. The operational intent of this input is the boiler plant will be shut down when the
Versatronik 300 does not sense a contact closure.
1. Control signal from BMS system or mechanical device control such as damper or blower motor.
2. Control relay (field supplied) of either AC or
DC control voltage to relay coil. Contact closure necessary for operation of boiler plant.
3. Low voltage wiring to Versatronik 300 control.
4. Connect to terminals of the INT terminal block.
!
WARNING
When extending wire there is the possibility of exposure to electromagnetic interference. Avoid running wires beside or near high voltage 120/240
VAC conductors. If proximity to high voltage conductors cannot be avoided, use stranded, twisted pair of shield design wire. Ensure that only one end of the shielding is grounded.
10
Coding Requirement
If this function is used, it must be turned on in the Specifications menu selection of the control.
Press and hold ENTER button for 5 seconds.
Press arrow up to Specifications main menu option.
Locate Interlock menu selection and press ENTER button to “Enable”.
Press ESC to escape from menu
If successfully programmed, a C1 error will be present indicating an open contact and fault output will be ON.
The alarm function can be disabled as a way to simply enable/disable the boiler plant. In circumstances where an alarm is not required, ensure that the alarming is turned off. Refer to the menu page with applicable instructions.
AUX Heat Demand Input
BMS
or mechanical control
R
3
4
2
1
!
WARNING
When extending wire there is the possibility of exposure to electromagnetic interference. Avoid running wires beside or near high voltage 120/240
VAC conductors. If proximity to high voltage conductors cannot be avoided, use stranded, twisted pair of shield design wire. Ensure that only one end of the shielding is grounded.
Installation Instruction
The heat demand is designed for any potentialfree, dry contact to be connected to the AUX terminals. The function of this input allows a heat demand to be provided to the control thereby causing a fixed set point temperature. This demand can be used in conjunction with the
Outdoor reset or without as a constant enable/ disable function.
The fixed temperature setpoint is adjustable in the Specifications menu selection.
1. Control signal from BMS system or mechanical device control. .
2. Control relay (field supplied) of either AC or
DC control voltage to relay coil. Contact closure for heat demand.
3. Low voltage wiring to Versatronik 300 control.
4. Connect to terminals of the AUX terminal block.
Coding Requirement
The external demand is the default function of the Versatronik 300 control.
To modify the set point temperature when a demand contact closure is present, access the programming by pressing the ENTER button for 5 seconds.
Press the arrow up until Specifications appears and press ENTER button.
Press the arrow up until DMD SetP is viewed and press ENTER to modify the value. Arrow up or down to increase/decrease and press enter to select desired value.
Press ESC to exit from programming. Return to screen showing Set Point Temperature. The value presently displayed should equal the programmed value of the set point demand. As well, an A should be present indicating the “AUX” demand.
11
AUX 0-10VDC Input (Option)
BMS or 0-10VDC
Device Control
Output
— +
— +
3
4
2
1
Installation Instruction
The 0-10VDC input is to allow a BMS controlled set point for the common supply. The signal is connected to the AUX terminals. The function of this input must be changed from the factory default of DEMAND to the 0-10VDC setting. This input can be used in conjunction with the
Outdoor Reset function, but the control will operate to the higher of the two set points.
1. Control signal from BMS system or mechanical device control. . connections from BMS or 0-10VDC device control output signal
3. Low voltage wiring to Versatronik 300 control.
4. Connect to terminals of the AUX terminal block. Left terminal is — and the right terminal is the + input.
!
WARNING
When extending wire there is the possibility of exposure to electromagnetic interference. Avoid running wires beside or near high voltage 120/240
VAC conductors. If proximity to high voltage conductors cannot be avoided, use stranded, twisted pair of shield design wire. Ensure that only one end of the shielding is grounded.
Coding
Selection of the 0-10VDC input is set in the
Specification menu selection. Press the ENTER button for 5 seconds.
Press the arrow up until Specifications appears and press ENTER button.
Press the arrow up until AUX Mode is viewed in the screen. Pressing the ENTER button will allow you to set the 0-10VDC mode. Once this is viewed in the screen, press the ESC button to exit.
Press ESC to exit from programming. Return to screen showing Set Point Temperature. The present 0-10VDC signal should appear at the setpoint value. As well, an A should be present indicating the “AUX” demand.
NOTE:
The scaling of the range of 2V to 10V equates to a 20C/68F to 100C/212F set point.
12
Communications-Vitotronic 100, GC1 and GC1B
Communication connections—Vitotronic 100, GC1 and GC1B
1
2
6
Connection Overview
The communication between the Versatronik
300 control and Viessmann Vitotronic 100, GC1 is a CAT5E cable with RJ45 ends, non cross over type connection. This cable can made up on site or ordered from Viessmann.
The cable is plugged into the Versatronik 300 and daisy chained from control to control.
1. Plug connection into the J1 receptacle on the PCB in the upper right hand corner of the PCB.
2. CAT5e cable connecting the boiler control
LON communication boards.
Boiler Control Programming Considerations
Refer to manual specific to boiler control.
Ensure necessary LON communication card installed.
The GC1 coding considerations:
Address 01 set to 01 for single boiler operation.
Boiler set point [ tr ] turned down to a value of
20C/68F. Should not be left at the factory default of 75C.
Ensure that burner load settings are made correctly. Addresses 08, 09 and 0A will influence how the Versatronik 300 will see the modulation rates from the boilers.
If boiler pumps are being used, address 4d must be set to a value of 2.
LON Settings:
Boiler control LON settings must be made from the factory values. Address 77 is the individual boiler LON addressing. The Versatronik 300 understands addressing from 1 to 16. Ensure that there are no boiler controls programmed with duplicate LON address values.
Minimum Boiler Functions:
The minimum boiler functions are handled by the boiler control. The boiler temperature may need to be satisfied before the actual boiler turns off after disabling by the Versatronik 300.
13
Communications-Vitotronic 300, GW5B
Communication connections—Vitotronic 300, GW5B
1
2
6
14
Connection Overview
The communication between the Versatronik
300 control and Viessmann Vitotronic 300,
GW5B is a CAT5E cable with RJ45 ends, non cross over type connection. This cable can made up on site or ordered from Viessmann.
The cable is plugged into the Versatronik 300 and daisy chained from control to control.
1. Plug connection into the J1 receptacle on the PCB in the upper right hand corner of the PCB.
2. CAT5e cable connecting the boiler control
LON communication boards.
Boiler Control Programming Considerations
Refer to Viessmann manual specific to boiler control. Ensure necessary LON communication card installed.
The Vitotronic 300, GW5B coding considerations: The boiler must be set to single boiler mode, not multi-boiler cascade control.
The outdoor sensor can be mounted inside of the control.
Ensure that burner load settings are made correctly. Addresses 08, 09 and 0A will influence how the Versatronik 300 will see the modulation rates from the boilers.
If boiler pumps are used, address 4d will need to be set to a value of 2.
LON Settings:
Boiler control LON settings must be made from the factory values. Address 77 is the individual boiler LON addressing. The Versatronik 300 understands addressing from 1 to 16. Ensure that there are no boiler controls programmed with duplicate LON values.
Minimum Boiler Functions:
The minimum boiler functions are handled by the boiler control. The boiler temperature may need to be satisfied before the actual boiler turns off after disabling by the Versatronik 300.
Typically this can be approximately 149F/65C.
Communications-Vitodens 200 w/HC1 Control
Communication connections—Vitodens 200, WB2B with Vitotronic 100, HC1 control
1
2
Connection Overview
The communication between the Versatronik
300 control and Viessmann Vitodens is a CAT5e cable with RJ45 ends, non cross over type connection. This cable can made up on site or ordered from Viessmann.
The cable is plugged into the Versatronik 300 and daisy chained from control to control.
1. Plug connection into the J1 receptacle on the PCB in the upper right hand corner of the PCB.
2. CAT5e cable connecting the boiler control
LON communication boards.
LON
LON
15
Boiler Control Programming Considerations
Refer to manual specific to boiler control.
Ensure necessary LON communication card installed.
IMPORTANT
Coding 00: 00 (Vitodens WB2B Only) Note: this coding cannot be directly set to 0. The way to do this is to temporarily change coding 01 to 2
(multi-boiler). A click can be heard. Change
01:02 back to 01:01. Address 34 must be changed to a value of 23 as well.
The Vitodens boiler pump will remain running unless this is performed correctly.
Boiler set point [ tr ] turned down to a value of
20C/68F. Should not be left at the factory default of 75C.
LON Settings:
Boiler control LON settings must be made from the factory values. Address 77 is the individual boiler LON addressing. The Versatronik 300 understands addressing from 1 to 16. Ensure that there are no boiler controls programmed with duplicate addresses.
Start at LON address 1 and sequentially increase for all of the controls. Address 76:1,
78:1, 79:0, 98:1
Communications-Vitodens 200 w/HO1 Control
Communication connections—Vitodens 200, WB2B with Vitotronic 200, H01 control
1
LON
LON
2
Connection Overview
The communication between the Versatronik 300 control and Viessmann Vitodens is a CAT5e cable with RJ45 ends, non crossover type connection.
This cable can made up on site or ordered from
Viessmann.
The cable is plugged into the Versatronik 300 and daisy chained from control to control.
1. Plug connection into the J1 receptacle on the
PCB in the upper right hand corner of the
PCB.
2. CAT5e cable connecting the boiler control
LON communication boards.
Boiler Control Programming Considerations
IMPORTANT CONSIDERATIONS
When communicating to a Vitodens WB2B boiler with Vitotronic 200, HO1 control, the outdoor temperature sensor will need to be connected. It can be located inside of boiler housing. An outdoor temperature sensor fault will always appear if it is not connected. An alternate installation method is to use a resistor to simulate an outdoor temperature greater than 68F/20C.
The Sun and Moon settings should be adjusted so that the boiler is always in warm weather shutdown mode. A setting of 10C/50F for each is typical.
Address 34 must be changed to a value of 16 as well.
For some systems that have small DHW production demands, it is still possible to use the boiler to satisfy tank demands. The priority settings may need to be changed based on desired functionality.
LON Settings:
Boiler control LON settings must be made from the factory values. Address 77 is the individual boiler
LON addressing. The Versatronik 300 understands addressing from 1 to 16. Ensure that there are no boiler controls programmed with duplicate addresses. Start at LON address 1 and sequentially increase for all of the controls. Address 76:1, 78:1,
79:0, 98:1
16
Communications-Vitodens B2HA with Black GUI
Communication connections—Vitodens 200, B2HA with new GUI
1
LON
2
Connection Overview
The communication between the Versatronik 300 control and Viessmann Vitodens is a CAT5e cable with RJ45 ends, non crossover type connection.
This cable can made up on site or ordered from
Viessmann.
The cable is plugged into the Versatronik 300 and daisy chained from control to control.
1. Plug connection into the J1 receptacle on the
PCB in the upper right hand corner of the
PCB.
2. CAT5e cable connecting the boiler control
LON communication boards.
Boiler Control Programming Considerations
IMPORTANT CONSIDERATIONS
When communicating to a Vitodens B2HA boiler, the outdoor temperature sensor will need to be connected. It can be located inside of boiler housing. An outdoor temperature sensor fault will always appear if it is not connected. An alternate installation method is to use a resistor to simulate an outdoor temperature greater than 68F/20C. A
10Kohm resistor (Brown Black Orange) will set an outdoor temperature of approximately 77F or 25C
The Sun and Moon settings should be adjusted so that the boiler is always in warm weather shutdown mode. A setting of 10C/50F for each is typical.
Boiler coding and LON Settings:
Boiler control LON settings must be made from the factory values. Address 77 is the individual boiler
LON addressing. The Versatronik 300 understands addressing from 1 to 16. Ensure that there are no boiler controls programmed with duplicate addresses. Start at LON address 1 and sequentially increase for all of the controls.
Boiler Coding Addresses:
30:0, 3F:2, 76:1, 78:1, 79:0, 98:1,
LON
17
Communications-End of Line Resistor
End of Line Resistor Installation
Connection Overview
An end of line resistor has been provided with the Versatronik 300 control. This is to be installed into the last boiler within the communications network.
The end of line resistor is has an RJ45 plug which will allow it to be inserted into the LON communication board
1. The control for the Vitodens 200 boiler will need to be tilted forward to expose the area which the end of line resistor is installed.
2. The LON communication card of the GC1 control is under the front display of the boiler control. Loosen the three screws across the bottom of the control housing and tilt the control face upwards. Locate empty socket and plug in end of line resistor.
LON
LON
1
18
2
Communications-BACnet: Applicable to Unit 704092 only
BACnet Communications
BACnet BMS Connection
RJ45 Plug
Connection Overview
1. Connect Ethernet cable with RJ45 end, for
BACnet communications into the communication port closest to the middle of the Versatronik 300 control.
1
Integration Overview
Refer to following pages regarding the Configuration of the BACnet IP settings and the device settings
19
Configuration of BACnet: Applicable to Unit 704092 only
Configuring BACnet/IP Settings
Connect your computer DIRECTLY to the BACnet port of the Versatronik 300 device. With no other devices attached (an isolated network). Either set your computer’s network connection to automatic
IP Address (DHCP), or set your computer’s IP address to 192.168.88.90 (subnet mask
255.255.255.0)
Restart the Versatronik 300 by cycling the power off and then on again.
Open a browser window and insert the following
URL: http://192.168.88.89/admin
The default user name / password is "admin" and
"admin" (without the quotes). This can be renamed in the Change Password screen. At this point you will see the Configuration pages.
Versatronik 300
IMPORTANT: Make sure that you remember any changes made here.
20
Configuration of BACnet Continued: Applicable to Unit 704092 only
BACnet Device Settings
You can now reconfigure these settings according to your network requirements. Make sure that you press SAVE on every screen where you make changes. The new setting will not take effect until the Activate Configuration screen has been confirmed. These configuration pages can now be accessed through both the 192.168.88.89
Address, as well as the one you have selected.
The BACnet Device Settings screen looks like this:
Versatronik 300
NOTE: The Device ID must be unique on the entire BACnet internetwork.
The Restore Defaults and Change Password screens are very simplistic. When you select
Activate Configuration, it will ask you if you want to SAVE your settings. This will then store your new settings and reboot automatically.
You can now join the Versatronik 300 to the rest of your network, provided you have not specified a duplicate IP Address. Any Computer on the network should now be able to access these configuration screens.
21
BACnet Data Points Overview: Applicable to Unit 704092 only
Analogue Inputs
Values which can be read from the Versatronik 300
Point
AI1
Point Description
Fault Code (See Appendix A)
AI4
AI6
AI101– AI116
AI201-AI216
AI301-AI316
AI401-AI416
AI501-AI516
Return Temperature (Only applicable if sensor installed)
AUX Input (Demand or 0-10VDC signal) The set point temperature will be shown whether it be a demand signal or 0-10VDC signal
Boiler Sequence 01 to 16
Boiler 01-16 Fault Code
Boiler 01-16 Temperature
Boiler 01-16 Set Point Temperature
Boiler 01-16 Modulation %
C/F
Unit
C/F
C/F
C/F
C/F
C/F
Analogue Outputs
Values which can be written to the Versatronik 300
Point Point Description
AO1 Slope
AO2 Shift
AO4 Supply Temperature Setpoint
Binary Inputs
Status which can be read from the Versatronik 300
Point Point Description
BI1 Interlock
Binary Outputs
Status which can be written to the Versatronik 300
Point
BO1
Point Description
Units (False=Metric; True=Imperial)
Unit
Unit
True/False
Unit
True/False
True/False
True/False
22
Outputs-Combustion Air Function
Combustion Air Demand
BMS
or mechanical control feedback
1
R
2
6
4
3
3
R
Field Supplied
Relay for
Combustion Air
Demand
Connection Overview
1. Signal from BMS or mechanical device as a status of combustion/exhaust air blower or damper.
2. Field supplied relay.
3. Interconnection to the Versatronik 300 control onto the INT input. Only dry contact status input to the control.
4. Combustion/Exhaust air blower/damper demand signal based on when the control requests the first boiler to fire.
6. Field supplied relay to provide dry contact to BMS or other device for demand.
!
Notice
The Versatronik 300 control may provide a demand to the boiler system for operation, resulting in the operation of the exhaust/damper device without boilers actually operating. If the boiler temperature is above its actual operational set point, the boiler may not fire, even though a call for heat from the
Versatronik 300 is present.
5
Sequence of Operation
1. Versatronik 300 senses drop in common supply temperature below the setpoint, provides set point demand to first boiler and AUX output turns ON.
2. The AUX output triggers demand for combustion/exhaust air operation.
3. Versatronik 300 waits for input signal from
BMS or combustion/exhaust system before allowing boilers to receive heat demand.
4. If the combustion air input signal is not sensed in 60 minutes, the control will provide a fault output. This time delay value can be altered from factory value.
!
CAUTION
It is possible for the boilers to be demanded ON with the override function and not provide demand signal to the combustion air system in Vitodens systems.
23
Outputs-120VAC
Output connections for 120VAC
1
2
R
120VAC coil Relay dry contact output
Connection Overview
The Versatronik has three 120VAC outputs for its various functions:
1. The common supply pump is connected to the control at the output marked PUMP.
This is a 120VAC output rated at 5FLA. If a larger amperage pump is necessary to be controlled a field supplied motor started should be used, which can be controlled by the pump output.
2. A field supplied 120VAC relay can be trigged from the AUX output for one of two functions:
External demand of alternate heating sources based on the time/temperature operation of the AUX connection.
Alternate function of combustion air demand to external system. Output active when demand present to the boiler plant.
This is a 120VAC, 3FLA output.
3. The fault output connection can be connected to various 120VAC loads at a
3FLA maximum. A relay can also be used to control an alternate load.
3
24
Input-120VAC
Input connections for 120VAC
Connection Overview
The Versatronik 300 control come complete with a power cord. Once all of the low voltage and output connections are complete, the unit can be plugged into a standard 120VAC wall outlet.
The power supply outlet should not be switch or controlled by a low water cut off.
The control is rated for 120VAC, 10A.
Depending on the load of the pump, it may be necessary to have a dedicated 120VAC source.
25
Configuration of Gateway Overview
Configuration Information
Section 3.0
Information Page
Overview of user interface elements and keys 27
General temperature status and review information 28
Menu structure
Operational overview
Configuration overview
Specifications information
Start up checks
29
30
32
33
34
What to expect
Cascade Overview
Outdoor reset function and operation
34
35
37
Control Operation
Overview of User Interface Elements
Esc
Versatronik ® 300
ST: 77c
SP: 30cR
1
Overview
The Versatronik 300 user interface is comprised of two elements, the screen display and the function buttons.
1. Screen displays information using two lines with multiple characters.
2. Buttons are used to view information, perform relay tests, change set points and perform coding changes.
Buttons:
Esc, Arrow Up, Arrow Down and Enter
Letter Set Point
L Low Limit
H High Limit
2
IMPORTANT
Screen Information
The system information that can be viewed at the screen has been maximized to provide the greatest amount of detail with the least number of characters. On the SP (Set Point line) a letter is shown beside the set point temperature. This value is representative of where the set point is coming from. The table below shows this.
Navigation
Movement within the various screens is accomplished with the Arrow Up and Arrow Down buttons.
Esc
To exit from a selected screen or menu press the ESC button. This button can be pressed to return back to the ST
(supply temperature) screen.
The ENTER button is used to access various menu options, adjust set points and access coding level.
Coding Level Accessing
Press and hold the ENTER button for 5 seconds.
Esc
To exit the coding level, press the ESC button.
A Auxiliary Input (Demand/0-10V)
? No calculation source (start up)
27
Control Operation
General Temperature/Status Review
Versatronik ® 300
ST:
SP:
77c
30c
1 1
Main Screen Information
Control navigation is accomplished by using the user buttons mounted on the front of the control.
With the UP arrow and DOWN arrow you may scroll down trough main display screens.
1. Press UP or DOWN arrows to move temperature/status information.
Shows on the display
ST - Supply Temperature
SP – Setpoint Temperature
Screen Display
ST:: 77c
SP:: 30c
OT – Outdoor Temperature
RT – Return Temperature OT: 76c
RT: 75c
B1 – Boiler Status 1 (LON address)
Status On or Off (control feedback)
Temperature
Fault Info (00 no fault present)
B1: OFF
43c: F00
Depending on the number of boilers in system will dictate the number of boiler status screens. The control will display the number of boilers it is programmed for.
See Note Below
B16 –Boiler Status 16 (LON address)
Status On or Off (control feedback)
Temperature
Fault Info (00 no fault present)
Boiler Sequence
It is possible to view the current sequence of the boilers. Sequentially, the boilers can be viewed in order of operation.
This display shows the first boiler is boiler number 4 based on LON addressing 77
B16:
43c:
BLR
OFF
F00
SEQ
SEQ 1 4
NOTE:
While in the individual boiler status information screen, pressing the ENTER button will display the boiler set point value and modulation value. Press the ESC button to exit this screen
SP: 54
MOD: 100%
28
Menu Structure
Access the control menu by pressing and holding the enter button. Navigation is achieved by pressing the up or down arrow keys. Pressing the enter button on a setting will allow you to “Edit” the value. Press enter to allow the new value to take effect. Press the escape button to exit.
Press and hold 5 sec
Main Screen
ST: Supply Temp
SP: Set Point Temp
OT: Outdoor Temp
RT: Return Temp
Boiler 1 Status On/Off
Temp C/F Fault Code
Boiler 16
Status On/Off
Temp C/F Fault Code
Boiler Sequence
SEQ 1 1
Boiler Sequence
SEQ 16 16
Movement within menu selection
Menu
Software
Relay Test
Sensor Test
Outdoor Reset
Boiler Config
Specifications
Factory Reset
Specifications
Celsius or Fahrenheit selection
High Limit (95C/203F default) (75C/167F to 100C
Low Limit (5C/41F)
PMP Delay (60 to 1 mins and Always ON)
AUX Input Mode (Demand/0-10V)
Demand Set Point (20C/68F to 100C/212F)
AUX Mode (external heat/combustion air function)
AUX Wait Time (1 to 99 mins) (Ex-heat mode)
AUX Min Run Time (1 to 99 mins) (Ex-heat mode)
AUX Error Delta T (1 to 30C) (Ex-heat)
Interlock Enable/Disable (Disabled factory)
Interlock Alarm Yes/No (only Interlock mode)
Return Temp Sensor (Enable)
LON Address
Factory Reset
No/Yes
Software Version
Software VX
Relay Test
Relay Test Off/On
Pump Off/On
AUX Off/On
Fault Off/On
Sensor Test
S1 (Outdoor temperature)
S2 (Supply temperature)
S3 (Return temperature)
INT (Interlock)
AUX (Input)
Outdoor Reset
Enable/Disable
Slope (0.2 to 3.5)
Shift (-15K to 35K)
WWSD (5C/41F to 30C/86F)
Boiler Config
Number of boilers (1 to 16)
Rotation Hours (1 to 99)
Boiler Staging Delay (min)
Minimum Boiler Mod (1 to 99%)
Maximum Boiler Mod (1 to 99%)
Stage On (5C/41F to 30C/86F)
Stage Off (5C/41F to 30C/86F)
Always run lead boiler pump
All Boilers (Yes/No)
Boiler 1 LON Address
Boiler 1 Group (Lead/Lag)
Boiler 1 ECO lock enabled (Yes/No)
Boiler 1 ECO Lock Temp
Boiler 16 LON Address
Boiler 16 Eco Lock (Yes/No)
29
Operational Overview
Logical Operational Output Information
Pump Output
System pump runs if outdoor temperature is below WWSD (minimum run time). Should the control not be programmed for outdoor reset operation, when the common supply set point is greater than 0C/32F, the common supply pump will operate.
The pump output has a factory set delay time of
10 minutes when there is no set point being calculated. If it is necessary to have the supply pump run continuously, it is possible to program so that it does not shut down.
Boiler Cascading
An additional boiler will be called if any of the following are true:
The common supply/LLH temperature is more than 5C (adjustable) below the setpoint
The average modulation for all active boilers exceeds the maximum average modulation
(adjustable)
A boiler will be taken off line if any of the following are true:
The common supply/LLH temperature is more than 5 (this setting is adjustable) above the setpoint.
The average modulation for all active boilers drops below the minimum average modulation
(this setting is adjustable)
Boilers will be brought on/off-line no faster than one boiler every 2 minutes under normal circumstances.
Boilers will be brought on in the following sequence:
All boilers not listed below
Eco-lock
Boilers reporting a fault
Boilers to which do not appear to be
communicating
If all non-Eco lock boilers are online or faulted
AND the set point can’t be met, turn on the AUX output.
AUX Output-Heat Demand
If all boilers are online (or faulted) and setpoint can’t be met; turn on AUX Output. The AUX
Output is function of not being able to be within the set differential for a set period time. Once the
AUX Output is energized, it will be on for the set minimum amount of time until the set differential temperature is achieved.
AUX will switch on when all non-faulted, non-eco lock boilers are running and the common supply temperature drops below the setpoint. It must drop to or below the differential specified in the setup menu. It must have been below this temperature for at least the amount of time specified in the configuration menu
Once running, it will run until the minimum amount of time specified in the setup menu has elapsed and either of the following conditions are met:
The common supply temperature is satisfied
Either of the non-faulted, non-eco lock boilers stages off
AUX Output-Combustion Air Function
The AUX output can be alternately programmed for a combustion air device function. When there is a call for heat, the AUX Output will turn on. This output can be used to demand some device such as a damper or blower rated for 120VAC.
A proving signal is then sensed by the INT input as a confirmation that the combustion air system is functional and then will allow the boiler plant to continue operation. This signal can only be in the form of a dry contact.
As part of the combustion air function, there is an
AUX Wait timer function that if the proving signal has not been sensed by the control in 60 minutes
(adjustable) an alarm will be triggered.
30
Operational Overview
Logical Operational Output Information Continued
INT Input
When the interlock mode is enabled through the set up menu and the INT contact is closed, the boiler plant will be allowed to operate. Should the
INT contact open for whatever reason, the boiler plant will shut down via communications and a C1 failure code will be present in the display of the control. As soon as the contact is again closed, the fault will clear and the boiler plant will again to stage on the boilers.
An alarm function is also possible which is set in coding. Should the control sense that the INT is open, the Fault output will turn on. As soon as the
INT input is sensed, the fault will clear automatically.
Boiler Rotation
Boilers will rotate on the hours programmed into the control. Rotation will take place on the set accumulated time when the common supply set point is satisfied.
31
Operational Overview
Configuration Information
Boiler Configuration
Number of boilers (1 to 16)
Detail
The number of boilers which the Versatronik 300 communicates with should be set here.
Rotation Hours (1 to 99)
Boiler Staging Delay (min)
Minimum Boiler Mod (1 to 99%)
Maximum Boiler Mod (1 to 99%)
Stage ON (5C/41F to 30C/86F)
Maximum boiler modulation setting allows the cascade control to only bring on another boiler should a currently running boiler exceeds this value. This is dependent on system operating temperatures
The Stage ON function is based on when another boiler is forced ON if the current boiler load is not sufficiently satisfying the common supply temperature. Should the common supply actual temperature drop below the set point plus this value, a boiler will be brought on.
Stage Down (5C/41F to 30C/86F) As the common supply set point is satisfied by this amount, boilers will start to be staged off in conjunction with a 2 minute delay
Always run lead boiler pump
Boiler minimum modulation setting has a factory value of 30%. This value is the factory default.
All Boilers (Yes/No)
By default, the lead boiler pump will always operate. By selecting the alternate function, the lead boiler pump will turn off if there is no boiler call for heat.
This setting allows the control to bring on all boilers, including ECO Lock boilers to achieve the common supply set point.
Boiler 1 LON Address
The rotation hours from when the boilers rotate lead boiler is set here. The boilers will rotate as long as the common supply/LLH set point is satisfied
A boiler staging delay can be adjusted here to provide sufficient time before bringing on another boiler. This allows the boilers to be able to satisfy the current load requirements.
Boiler 1 Group (Lead/Lag)
Boiler 1 Eco Lock (Yes/No)
Boiler 1 ECO Lock Temperature
Boiler 2-16 LON Address
Boiler LON address. This is based on the value programmed in at address 77 for all LON based boilers. Ensure that there are no boilers which have address 77 duplicated.
It is possible to select a “lead” group of boilers which are all of the boilers which are to function before the “lag” boilers. The boilers in both the lead and lag will rotate. The lag boiler group should never operate before the lead group.
It is possible to put a boiler into ECO lock mode which is a function of the current outdoor temperature. As the outdoor temperature drops below the ECO Lock setting, the boiler will be allowed to be part of the cascade function of the Versatronik 300 control.
The programmed outdoor temperature at which the ECO lock boiler is enabled to function as part of the cascaded boilers
Boiler LON address for boilers 2-16
Boiler 2-16 Group (Lead/Lag)
Boiler 2-16 Eco Lock (Yes/No)
Selection of boilers whether they are part of the “lead” boiler group or the “lag” boiler group.
ECO Lock function for boilers 2-16
Boiler 2-16 ECO Lock Temperature The programmed outdoor temperature at which the ECO lock boiler is enabled to function as part of the cascaded boilers for boilers 2-16
32
Operational Overview
Specifications Information
Specifications
Celsius or Fahrenheit selection
High Limit (95C/203F)
Low Limit (5C/41F)
Detail
Selection of Celsius or Fahrenheit temperature display
Electronic high limit of control limiting the calculation of common supply set point
Electronic minimum set point of common supply
AUX Input Mode (Demand/0-10V)
Demand Set Point (20C/68F to 100C/212F)
Selection of either demand set point or 0-10VDC input
Set point temperature of demand function
AUX Mode (external heat/combustion air function)
AUX Wait Time (1 to 99 mins) (Ex-heat mode)
Selection of external AUX heat demand output based on time temperature relationship of the common supply set point and actual temperature OR combustion air device function with status input into the INT input
External AUX heat demand output function
AUX Min Run Time (1 to 99 mins) (Ex-heat mode)
AUX Error Delta T (1 to 30C) (Ex-heat)
External AUX heat demand output function minimum run time when activated.
External AUX heat demand output function temperature
Interlock Enable/Disable
Interlock Alarm Yes/No (only Interlock mode)
Return Temp Sensor (Enable)
Interlock Enable/Disable selection can operate as system control On/Off
Interlock alarm only when enabled
Return temperature sensor
LON Address LON address of Versatronik 300 control
33
Control Commissioning
Start Up Information
Step Description
1 Mount unit on surface with field supplied hardware
2
3
Connect required sensors
Outdoor sensor (If required)
Supply/LLH
Return
Low Voltage External Connections (If required)
Demand
0-10VDC
4 120VAC Connections
AUX output (heat demand or combustion air) output
Outdoor Reset Menu
Enable/Disable
Slope/Shift/WWSD
Configuration
Number
Boiler LON addresses for number of programmed boilers
Control addresses specific to control pages
Specifications
AUX mode selection (demand or 0-10VDC)
Demand set point if necessary
Interlock
Return Temperature sensor (enable/disable)
What to expect during operation
Observations
A set-point temperature will be show on the screen display of the control.
This set point temperature is function of either outdoor reset, demand input, BACnet or 0-10VDC
The set point temperature will have a R for reset or a A for AUX
If the boilers are able to function, the control will provide a setpoint to the boiler control.
The boiler should fire based on the temperature demand
The setpoint that is being sent to the boilers can be viewed in the main menu
The setpoint can also be viewed at the boiler control too in the diagnosis mode
Boiler modulation is a function of the boiler not the Versatronik 300 control
Boiler cascading is a function of modulation settings, temperature and time delays.
34
Cascade Function
Cascade Overview
Cascade On/Modulation
Maximum Burner Mod
Stage On
Settings
Stage Off
Setting
Setpoint
Cascade Off/Modulation
Minimum Burner Mod
Stage Off
Settings
Stage On
Setting
LLH/Common Supply
Temperature
Overview Description
The boiler cascading operation of the Versatronik
300 control is based on time/temperature/ modulation functions. The digital communications between the boiler controls and the 300 provide information regarding the current percentage of burner modulation. The 300 control uses the burner modulation to be able to bring on another boiler should the % setting be exceeded. Because of this logic, it is possible to have a larger number of boilers on at a lower firing rate. The opposite of this is also true. By programming a higher % value, it is also possible to have the boilers function at a greater modulation level.
Burner modulation is a function of the boilers and not controlled by the Versatronik 300 control. As the individual boiler temperature set point is being satisfied, the boilers themselves will modulate down.
Cascading Sample Graph
The above picture shows a typical cascading ON and OFF of boilers to achieve the set point demand from either outdoor reset, heat demand or 0-10VDC input.
As the actual common supply or LLH temperature drops below the set point, a call for heat will be provided to the lead boiler. This call for heat takes place approximately 2C below the set point. The set point, which can be seen on the screen of the
Versatronik 300 control, is provided to the boiler.
The boiler control will process this signal and based on the current boiler water temperature, will decided to fire the burner or not. Since the pump will be on and the actual boiler water temperature will decrease, the burner will fire.
Burner modulation will take place as a function of the internal PID operations of the control. The enabling of another boiler is a function of the
Maximum Boiler Modulation % setting and the
Stage On setting, which is a temperature setting.
If the Maximum Boiler Modulation % is exceeded, the next boiler will be provided the set point and again it is responsible for its own modulation to achieve boiler set point.
The operation of the boilers and the modulation is a function of the flows through the boiler and internal PID functions. Should the common supply temperature drop because of extra loading, the
Stage On setting may be exceeded which will force another boiler on as a way to ensure that the common supply set point is achieved.
As the common supply starts coming up in temperature as a result of the boiler operation and modulation, the boilers themselves will start to modulate down. Based on the number of currently running boilers and the Minimum Boiler Modulation setting, the boilers may start to be staged off. As well, it is possible that the
Continued on Next Page
35
Cascade Function
Cascade Overview Continued
Cascade On/Modulation
Maximum Burner Mod
Stage On
Settings
Stage Off
Setting
Setpoint
Cascade Off/Modulation
Minimum Burner Mod
Stage Off
Settings
Stage On
Setting
LLH/Common Supply
Temperature boilers themselves have modulated down and turned off but still have a call for heat in the form of a boiler temperature set point.
Depending on the current operation of the system, the Versatronik 300 control looks at the Minimum
Burner Modulation of the active boilers. Should the average modulation of the currently active boilers be equal to or less than this setting, a boiler will be staged off in conjunction with a 2 minute delay.
Cascade Adjustment Strategies
Pure Modulation Staging
Cascade operation as a function of burner/boiler loading, increase the Stage On value so as to not force boilers on earlier as a function of temperature. This may be upwards to a value of
10C/18F or 15C/27F. Adjust the Maximum Burner
Modulation setting to a value where the next boiler should be brought on. Each successive boiler will come on at the Max Modulation value.
To have the boilers stage off earlier, set the
Minimum Burner Modulation to a value higher than the default value of 30%.
Temperature Dependant
By either leaving the Stage On value at its factory default setting or lowering it to a smaller value, successive boilers will be brought on quicker. Each boiler will modulate again to achieve the boiler temperature set point.
36
Outdoor Rest Function
Operational Information
Menu
Software
Relay Test
Sensor Test
Outdoor Reset
Boiler Config
Specifications
Factory Reset
Outdoor Reset
Enable/Disable
Slope (0.2 to 3.5)
Shift (-15K to 35K)
WWSD (5C to 30C)
Operation Instruction
With the outdoor reset function enabled, it is possible to make a slope, shift and WWSD function adjustment.
Press and hold the ENTER button for approximately 5 seconds. Navigate the main menu with the arrow up or down key to select the Outdoor reset menu.
There are three settings for outdoor reset adjustment: Slope, Shift and WWSD (warm weather shutdown). Select the value to be changed by pressing the ENTER button. The word
EDIT will appear in the screen and press the arrow up or down to program a new value. Press the ENTER button to accept the new value and the ESC button will exit to the main menu.
The table below shows various slope settings at a
WWSD of 20C/68F.
C F
30 30
20 20
68
20
59
15
50
10
41
5
32
0
‐
°C
-5
‐
4
‐
7
‐
1
5
‐
1
‐
1
-4
‐
1
-13 -22 -31 -40
‐
2
‐
2
‐
2
‐
3
‐
3
‐
3
-10 -15 -20 -25 -30 -35 -40
‐
4
F
C
Outdoor Temperature
37
1.2
1
0.8
0.6
0.4
3.6
3
2.4
2
1.6
Diagnosis and Technical Information
Technical Information
Section 3.0
Information Page
Fault Codes 39
Outdoor temperature sensor information 44
Supply/Return temperature sensor information
Versatronik 300 Technical information
45
46
38
Fault Codes
Appendix A—Fault Codes
Error codes for Viessmann control units based on controls/equipment installed
Fault Code (hex) Fault Code (Dec) Description
5D
5E
5F
60
58
59
5A
5C
54
55
56
57
4d
50
51
52
45
48
49
4C
38
40
41
44
19
20
28
30
0
0F
10
18
85
86
87
88
89
8C
8D
81
82
83
84
68
70
78
80
93
94
95
96
88
89
90
92
84
85
86
87
77
80
81
82
69
72
73
76
56
64
65
68
25
32
40
48
0
15
16
24
133
134
135
136
137
140
141
104
112
120
128
129
130
131
132
System without fault
Perform maintenance check-up
Short circuit, outdoor temperature sensor
Open circuit, outdoor temperature sensor
Communication External Outdoor temperature sensor
Short circuit, supply temperature sensor HC1/system
Open circuit, supply temperature sensor HC1/system
Short circuit, boiler water temperature sensor
Open circuit, boiler water temperature sensor
Short circuit, supply temperature sensor heating circuit 2
Short circuit, return temperature sensor heating circuit 2
Short circuit, supply temperature sensor heating circuit 3
Short circuit, return temperature sensor heating circuit 3
Open circuit, supply temperature sensor heating circuit 2
Open circuit, return temperature sensor heating circuit 2
Open circuit, supply temperature sensor heating circuit 3
Open circuit, return temperature sensor heating circuit 3
Short circuit, DHW tank temperature sensor
Short circuit, DHW tank temperature sensor 2
Short circuit, Buffer tank sensor 9
Error Boiler 5
Error Boiler 6
Error Boiler 7
Error Boiler 8
Open circuit, DHW tank temperature sensor 5A
Open circuit, DHW tank temperature sensor 2
Open circuit, Buffer tank
Failure boiler 5
Failure boiler 6
Failure boiler 7
Failure boiler 8
Short circuit, return temperature sensor 17A
Open circuit, return temperature sensor 17A
Short circuit, supply/return temperature sensor 17B
Open circuit, supply/return temperature sensor 17B
Short circuit, burner control, boiler temperature limit sensor
Sensor differential (drift), burner control, boiler temperature limit sensor
Short circuit, burner control, flue gas temperature limit sensor
Sensor differential (drift), burner control, flue gas temperature limit sensor
Error boiler 1
Error boiler 2
Error boiler 3
Error boiler 4
Open circuit, burner control, boiler temperature limit sensor
Open circuit, burner control, flue gas temperature limit sensor
Failure boiler 1
Failure boiler 2
39
Fault Codes Continued
Appendix A—Fault Codes Continued
Error codes for Viessmann control units based on controls/equipment installed
Fault Code (hex) Fault Code (Dec) Description b1 b4 b5 b6
AD
AE
AF b0
A7
AA
AB
AC
A1
A2
A3
A4
99
9A
9B
9C
9E
9F
A0
92
93
94
98
8E
8F
90
91 bC bD bE bF b7 b8 b9 bA
C1
C2
C3
173
174
175
176
177
180
181
182
161
162
163
164
167
170
171
172
153
154
155
156
158
159
160
142
143
144
145
146
147
148
152
183
184
185
186
188
186
190
191
193
194
195
Failure boiler 3
Failure boiler 4
Short circuit, Solarmodule sensor 3 (SM1 Sensor 7)
Short circuit, Solarmodule sensor 4 (SM1 Sensor 10)
Short circuit Solar: collector temperature sensor
Short circuit Solar: collector return temperature sensor
Short circuit Solar: collector DHW tank temperature sensor
Open circuit, Solarmodule sensor 3 (SM1 Sensor 7)
Open circuit, Solarmodule sensor 4 (SM1 Sensor 10)
Open circuit Solar: collector temperature sensor
Open circuit Solar: collector return temperature sensor
Open circuit Solar: DHW tank temperature sensor
Solarmodule Delta-T Monitoring Failure Solar control
Solar: general fault message
Fault/Failure module 2: safety device input 1
Fault/Failure module 2: safety device input 2
Fault/Failure module 2: safety device input 3
Fault/Failure module 2: safety device input 4
Fault/Failure module 2: External
Fault control unit wireless clock module
Configuration failure TSA Function
Configuration failure heat exchanger setting
Configuration failure return temperature control
Configruation failure isolation valve control
Internal fault mixing valve
Internal fault mixing valve
Short circuit, flue gas temperature sensor
Communication fault, programming unit (internal)
Internal fault
Internal fault
Internal fault, invalid hardware recognition
Internal fault, boiler protection coding card
Open circuit, flue gas temperature sensor
Failure plausibility test
Fault, mixing valve module (KM-BUS)
Fault, Vitotrol heating circuit 1 (KM-BUS)
Fault, Vitotrol heating circuit 2 (KM-BUS)
Fault, Vitotrol heating circuit 3 (KM-BUS)
Copatibility failure LON Module
External fault indication, boiler (Low Water Cut Off)
Communication fault solar control unit (KM-BUS)
Communication failure AM1 Module
40
Fault Codes Continued
Appendix A—Fault Codes Continued
Error codes for Viessmann control units based on controls/equipment installed
221
222
223
224
225
226
227
228
212
213
214
215
216
218
219
220
203
204
205
206
207
209
210
211
196
197
198
199
200
201
202
229
230
236
237
238
239
240
241
242
243
244
Fault Code (hex) Fault Code (Dec) Description
E1
E2
E3
E4 dd dE dF
E0 d8 dA db dC d4 d5 d6 d7
CF d1 d2 d3
Cb
CC
Cd
CE
C4
C5
C6
C7
C8
C9
CA
EE
EF
F0
F1
E5
E6
EC
ED
F2
F3
F4
Communication failure 0-10V Module
Fault, speed controlled pump heating circuit 1 (KM-BUS)
Fault, speed controlled pump heating circuit 2 (KM-BUS)
Fault module, External failure
Fault, water level control input 1
Fault, maximum pressure input 2
Fault, minimum pressure/maximum pressure 2 input 3
Fault, maximum pressure 2 input 4
Reserved, external periphery
Communication fault, Vitocom 100/300 (KM-BUS)
Communication fault, fault indicator module (KM-BUS)
Communication fault: wrong LON module
Burner fault, boiler
Communications failure fault module 2
Communications failure EA1 Module
Fixed high limit fault, boiler
Cascade: boiler is not responding
External fault 1, plug-in adaptor
External fault 2, plug-in adaptor
External fault 3, plug-in adaptor
Short circuit, room temperature sensor heating circuit 1
Short circuit, room temperature sensor heating circuit 2
Short circuit, room temperature sensor heating circuit 3
Open circuit, room temperature sensor heating circuit 1
Open circuit, room temperature sensor heating circuit 2
Open circuit, room temperature sensor heating circuit 3
Fault, external participant/device connected to LON
Gas valve 1/gas pressure monitoring 1
Gas valve 2/gas pressure monitoring 2
Error safety chain
Fault 24volt power supply voltage
Internal fault combustion control unit
Flue gas/air supply system blocked
Fault safety relay
Fault ignition relay
Internal error in feedback from gas safety valves
Internal error in feedback from gas safety valves
Communication fault combustion control unit KM-BUS
Flue gas temperature limit has tripped
Boiler temperature limit has tripped
Flame signal is present at burner start or incorrect coding card
Flame signal is not present (number of other faults possible)
41
Fault Codes Continued
Appendix A—Fault Codes Continued
Error codes for Viessmann control units based on controls/equipment installed
Fault Code (hex) Fault Code (Dec) Description
F9
FA
FC
FD
F5
F6
F7
F8
FE
FF
245
246
247
248
249
250
252
253
254
255
Air pressure switch not open for burner start
Gas pressure switch not open for burner start
Air pressure sensor short circuit or offset value outside of tolerances
Fuel valve closure delayed
Blower speed too low at burner start
Blower speed too high at burner start
Control of modulation valve defective
Fault combustion control unit
Coding plug defective or wrong EMV error
Internal fault
42
Additional Alarm/Fault Information
The Versatronik 300 show fault codes in hexadecimal format to conserve screen space on the user interface.
In which base-format this fault can be displayed depends on your BMS software.
This example shows how to display this fault code in hexadecimal, and Text format in
Niagara AX.
To display in hex, you can use the KitControl -
> Util “Numeric Bit And” object’s mask input.
To display the equivalent fault text value, you can use the KitControl -> Conversion
“Numeric To Enum” object and type out the enum range for all Viessmann error codes.
These values can now be displayed on a px webpage by pointing a Bound Label to the appropriate slot values.
43
Outdoor Temperature Technical Information k in e nc ta is es
100
80
60
40
20
10
8
6
4
-15
5
-5 0
23 32
Temperature
10
50
20
68
30 ºC
86 ºF
Temperature Resistive Table
Temperature 5Kohm NTC
-60°C
-50°C
-76°F
-58°F
698961
333908
40°C
50°C
60°C
70°C
80°C
90°C
100°C
110°C
120°C
-40°C
-30°C
-20°C
-10°C
0°C
10°C
20°C
25°C
30°C
-40°F
-22°F
-4°F
14°F
32°F
50°F
68°F
77°F
86°F
104°F
122°F
140°F
158°F
176°F
194°F
212°F
230°F
248°F
2662
1801
1244
876
628
458
339
255
194
167835
88340
48487
27648
16325
9952
6247
5000
4028
44
Technical Information
Technical data: Supply and Return Temperature Sensor
Temperature Resistive Table
20
10
8
6
4
2
1
0.8
0.6
0.4
10
50
30
86
50
122
70
158
Temperature
90
194
110
230
C
F
0C 32F
5C 41F
10C 50F
15C 59F
20C 68F
25C 77F
30C 86F
35C 95F
40C 104F
45C 113F
50C 122F
55C 131F
60C 140F
65C 149F
70C 158F
75C 167F
80C 176F
85C 185F
90C 194F
95C 203F
100C 212F
105C 221F
110C 230F
115C 239F
120C 248F
125C 257F
32,650
25,394
19,903
15,714
12,493
10,000
8,056
6,530
5,325
4,367
3,601
2,985
2,487
2,082
1,752
1,480
1,256
1,070
916
787
678
587
510
444
388
341
45
Technical Information—120VAC
3
4 5
10
6
F2 T160mA
2
9 8 7
PCB Identifiers
1 120VAC Power Supply Connections
2 Fuse (low voltage) 100mA Time Delay
1
4 BMS Communications BACnet
5 LON Communication to boilers
6 Display and keyboard
7 120VAC Fault Output 3FLA
8 120VAC AUX Output 3FLA
9 120VAC Pump Output 3FLA
10 Fuse Pump Outputs 10A
Specifications
Voltage Requirements 120VAC
Fuse Rating (low V) 160mA Time Delay
Power 4VA
Fuse Rating (pump) 10A 250VAC
Dimensions:
Width 167mm/6.5in
Height 206mm/8in
Depth 42mm/1.62in
Clearance:
100mm Left & Right side to loosen cover screws
46
CAUTION
Static sensitive components may be damaged by improper handling or work within the control. Ensure all possible measures are taken to eliminate build-up of static electricity.
Page is left intentionally blank
47
KWE Technologies Group
750 McMurray Road
Waterloo, Ontario, Canada
N2V 2G5
Tel: (519) 747-5042
Fax: (519) 747-4448 www.kwe-tech.com [email protected]
48
Download
Advertisement
Key features
Stages Viessmann LON-enabled boilers
Supports outdoor reset functionality
Offers interlock for system enable/disable
Includes auxiliary heat demand input
BACnetIP model available for BMS integration
Monitors supply and return temperatures
Frequently asked questions
It is designed to stage Viessmann LON enabled boilers and boiler controls via a CAT5 wire connection LON communication.
The Versatronik 300 is compatible with Vitotronic 100 GC1/GC1B, Vitotronic 300 GW2, Vitotronic 300 GW5B, Vitotronic 200 HO1/HC1 and Vitodens 200 B2HA.
The boiler interlock is designed for any potential-free, dry contact to be connected to the INT terminals. The operational intent of this input is the boiler plant will be shut down when the Versatronik 300 does not sense a contact closure.
The control will provide a fault output. This time delay value can be altered from factory value.