Pro-face KPM(T) 5012KPM(T), 5015KPM(T) Flat Panel Industrial Monitor User Manual
Below you will find brief information for KPM(T) 5012KPM(T), KPM(T) 5015KPM(T). These monitors offer a robust design, including a resistive membrane touch screen, an integral pointing device, and an integral full alphanumeric keypad. They are rated for use in Class I & II Division 2 Hazardous Locations, making them suitable for industrial environments.
Advertisement
Advertisement
KPM(T) Monitor Series
Flat Panel Industrial Monitors
User Manual for the
5012KPM(T) and
5015KPM(T) models
Printed in the United States of America
KPM(T) Series Flat Panel Industrial Monitor
Revision Description
A
B
C
D
Manual Released
TIR caution added
Clarified front panel frame, glass and overlay in Tables 1-1 & 1-2
Name change, correct where applicable with document
Revision
Date
03/04
06/04
08/04
04/07
Part Number 143448(D)
Trademark Information
Xycom and Xycom Automation are trademarks of Xycom Automation, L.L.C.
Xycom Automation, L.L.C. now is referred to as Pro-face through a D.B.A. The Pro-face name and logo will replace the Xycom name and logo on all documents where possible.
Pro-face is a trademark of Digital Electronics Corporation.
Brand or product names are trademarks or registered trademarks of their respective owners. Intel and
Pentium are registered trademarks and Celeron is a trademark of Intel Corporation. Windows, Windows NT, and Windows XP are registered trademarks of Microsoft Corporation in the U.S. and in other countries.
Copyright Information
This document is copyrighted by Xycom Automation, L.L.C. (Xycom) and shall not be reproduced or copied without expressed written authorization from Xycom Automation, L.L.C.
The information contained within this document is subject to change without notice. Pro-face does not guarantee the accuracy of the information.
United States FCC Part 15, Subpart B, Class A EMI Compliance Statement:
NOTE:
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at the user’s expense.
For European Users – WARNING:
This is a Class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
INSTALLATION – Electromagnetic Compatibility WARNING:
The connection of non-shielded equipment interface cables to this equipment will invalidate FCC
EMI and European Union EMC compliance and may result in electromagnetic interference and/or susceptibility levels which are in violation of regulations applying to the legal operation of this device. It is the responsibility of the system integrator and/or user to apply the following directions relating to installation and configuration:
All interface cables must include shielded cables. Braid/foil type shields are recommended.
Communication cable connectors must be metal, ideally zinc die-cast backshell types, and provide 360-degree protection about the interface wires. The cable shield braid must be terminated directly to the metal connector shell; ground drain wires alone are not adequate.
Protective measures for power and interface cables as described within this manual must be applied. Do not leave cables connected to unused interfaces or disconnected at one end.
Changes or modifications to this device not expressly approved by the manufacturer could void the user’s authority to operate the equipment..
143448(D)
Table of Contents
CHAPTER 1 – INTRODUCTION ...................................................................................................................................1
P
RODUCT
O
VERVIEW
....................................................................................................................................................1
S
TANDARD
F
EATURES
...................................................................................................................................................1
Front Panel Controls ..............................................................................................................................................2
Back Panel.............................................................................................................................................................5
U
NPACKING THE
U
NIT
....................................................................................................................................................7
Q
UICK
S
TARTUP
...........................................................................................................................................................8
CHAPTER 2 – INSTALLATION.....................................................................................................................................9
I
NSTALLATION
O
VERVIEW
...............................................................................................................................................9
S
YSTEM
C
UTOUT
D
IMENSIONS
.....................................................................................................................................11
5012KPM(T).........................................................................................................................................................11
5015KPM(T).........................................................................................................................................................12
P
OWER
M
ANAGEMENT
.................................................................................................................................................13
System Power......................................................................................................................................................13
Excessive Heat ....................................................................................................................................................14
Electrical Noise ....................................................................................................................................................14
Line Voltage Variation ..........................................................................................................................................15
General Compatibility Issues ...............................................................................................................................15
XVME C
OMPATIBILITY
I
SSUES
.....................................................................................................................................16
U
SING A
T
OUCH
S
CREEN
.............................................................................................................................................16
C
USTOM
L
OGO
...........................................................................................................................................................17
C
REATING
C
USTOM
K
EYPAD
I
NSERTS
...........................................................................................................................17
H
AZARDOUS
L
OCATIONS
I
NSTALLATION
.........................................................................................................................23
Safety Agency Approval.......................................................................................................................................24
Definitions ............................................................................................................................................................25
Class I Locations..................................................................................................................................................25
Class II Locations.................................................................................................................................................25
Division 1 Locations .............................................................................................................................................25
Division 2 Locations .............................................................................................................................................26
Groups .................................................................................................................................................................26
Enclosures ...........................................................................................................................................................27
Power Switch .......................................................................................................................................................27
Cable Connections...............................................................................................................................................28
Hazardous Locations Control Drawing.................................................................................................................29
Operation and Maintenance.................................................................................................................................30
CHAPTER 3 – MONITOR SETTINGS .........................................................................................................................31
O
N
S
CREEN
D
ISPLAY
(OSD) S
WITCH
...........................................................................................................................31
M
ODE AND
I
MAGE
A
DJUSTMENT
...................................................................................................................................31
OSD Functions.....................................................................................................................................................32
Reset Factory Default Settings.............................................................................................................................34
A
NALOG
RGB I
NTERFACE
S
PECIFICATIONS
...................................................................................................................34
G
RAPHIC
M
ODES
........................................................................................................................................................35
CHAPTER 4 – OPERATOR INPUT.............................................................................................................................36
I
NSTALLING THE
T
OUCH
S
CREEN
D
RIVER
......................................................................................................................36
C
ALIBRATING THE
T
OUCH
S
CREEN
................................................................................................................................37
U
SING A
P
OINTING
D
EVICE WITH A
T
OUCH
S
CREEN FOR
DOS .........................................................................................37
CHAPTER 5 – KEYPAD UTILITY PROGRAM............................................................................................................38
L
OADING THE
K
EYPAD
U
TILITY
.....................................................................................................................................38
U
SING THE
K
EYPAD
U
TILITY
.........................................................................................................................................38
S
TARTUP
....................................................................................................................................................................39
M
AIN
M
ENU
................................................................................................................................................................39
Exit.......................................................................................................................................................................40
i
143448 (D)
Files Menu ...........................................................................................................................................................40
Macros Menu .......................................................................................................................................................41
Upload Menu........................................................................................................................................................43
Download Menu ...................................................................................................................................................43
Utilities Menu........................................................................................................................................................44
U
TILITY
B
ATCH
M
ODE
..................................................................................................................................................44
K
EYPAD
S
CAN
C
ODES
.................................................................................................................................................45
CHAPTER 6 – MAINTENANCE ..................................................................................................................................48
G
ENERAL
P
REVENTIVE
M
AINTENANCE
...........................................................................................................................48
Fuse Replacement...............................................................................................................................................48
T
ROUBLESHOOTING
.....................................................................................................................................................48
Before Contacting Technical Support...................................................................................................................48
P
RODUCT
R
EPAIR
P
ROGRAM
.......................................................................................................................................49
KPM(T) S
ERIES
F
RONT
P
ANEL
F
RAME
.........................................................................................................................50
Chemicals Compatible with Frame.......................................................................................................................50
Front Panel Overlay .............................................................................................................................................51
Chemicals Compatible with Overlay.....................................................................................................................51
Compatible Cleaning Agents for Overlay .............................................................................................................51
Chemicals Not Compatible with Overlay ..............................................................................................................51
APPENDIX A – TECHNICAL SPECIFICATIONS........................................................................................................52
H
ARDWARE
S
PECIFICATIONS
........................................................................................................................................52
E
NVIRONMENTAL
S
PECIFICATIONS
................................................................................................................................53
APPENDIX B – PINOUTS ...........................................................................................................................................54
VGA I
NPUT
C
ONNECTOR
.............................................................................................................................................54
S
ERIAL
I
NTERFACE
......................................................................................................................................................54
Touch Screen RS-232 Output Connector ............................................................................................................55
USB I
NPUT
/O
UTPUT
C
ONNECTOR
................................................................................................................................55
ii 143448 (D)
Chapter 1 – Introduction
Product Overview
Pro-face/X ycom industrial flat panel monitors offer state-of-the-art performance and features while meeting the rigorous requirements of the plant floor. Pro-face/
Xycom’s
5012KPM(T) and 5015KPM(T) high-resolution flat panel displays reflect the latest technology and are contained within a rugged housing with a resistive membrane touch screen, an integral pointing device, and an integral full alphanumeric keypad.
The 5012KPM(T) and 5015KPM(T) are UL508 listed, CE compliant and UL listed for use in Class I & II Division 2 Hazardous Locations.
The front panel is sealed to NEMA TYPE 4/4x/12 (UL 50) standards and is protected by an impact-resistant shield. UL listed for Hazardous Locations: Class I, Division 2,
Groups A, B, C; Class II, Division 2, Groups F and G (pending).
Standard Features
The KPM(T) monitor comes with the following standard features:
••••
••••
••••
Rear IBM® PS/2 keyboard port and mouse port
Front PS/2 keyboard/mouse port and front USB port
Diagnostic LEDs
– Power
– Input
••••
••••
••••
••••
••••
••••
••••
••••
••••
••••
Analog RGB video interface
Analog resistive touch screen with RS-232 interface
Die-cast aluminum front bezel
Shallow mounting depths – 2.32”on 5012KPM(T) and 2.17” on
5015KPM(T)
100-240V AC or optional 24V DC input power
Front panels meet NEMA 4/4X/12 and IP65 specifications when panel mounted
UL Listed for use in Class I and Class II, Division 2 Hazardous Locations,
Groups A, B, C, D, F, and G
UL 508 Listed
40 relegendable function keys (74 with the F/A function)
Numeric, PC control, and alpha keypads
Integrated mouse
••••
1
143448 (D)
KPM(T) Series Flat Panel Industrial Monitor Chapter 1 – Introduction
The 5012KPM(T) has a 12.1" TFT SVGA color LCD, which supports resolutions up to 800x600 @75Hz. The 5015KPM(T) has a 15” TFT XGA, which supports resolutions up to 1024x768 @ 75Hz.
The figures and tables on the next several pages illustrate the internal and external components of the front and back panels to help you locate the features of the
KPM(T) monitors.
Figure 1-1 shows the front panel controls for the KPM(T) monitors. Table 1-1 outlines the front panel control functions.
Figure 1-1. 5012KPM(T)& 5015KPM(T) Front Panel Controls
The 5012KPM(T) and 5015KPM(T) feature function keys on either side of the flat panel display (PF1-PF20), function keys below the display (F1-F20), a numeric keypad, window keys, a curser control keypad, power LED, input LED, industrial
2 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor Chapter 1 – Introduction
mouse/keyboard and USB ports. All keypad keys are reprogrammable
1
F/A key, and all function keys are relegendable
2
, except the
. See Chapter 5 for more details.
Caution
Leaving your TFT LCD display on constantly can result in temporary image retention
(TIR). TIR can be avoided by using a screen saver, enabling the idle/doze timeout feature, or by turning off the display when it is not in use.
Feature
Front Panel
Diagnostic LEDs
Table 1-1. 5012KPM(T) & 5015KPM(T) Front Panel Controls Functions
Description
The front panel has four components: a display; strengthened glass covering the display; a frame in which the display and the glass are mounted; and the polyester overlay attached to both the glass and the frame.
The 5012KPM(T) has a 12.1" TFT LCD flat panel. The 5015KPM(T) has a
15" TFT LCD flat panel.
The strengthened glass covering the display is intended to withstand normal operating conditions. In the event of damage to the glass, the overlay will protect the user from any glass shards.
For more information abut the frame or the overlay, see Chapter 6 –
Maintenance.
Following is a description of the diagnostic LEDs and their meanings:
Power GREEN when the system has power.
Disk LED is not active on the 5012KPM(T) and 5015KPM(T).
COM LED is not active on the 5012KPM(T) and 5015KPM(T).
Input GREEN when the unit has a touch screen (LED gets brighter when a touch input is detected) or a key is pressed.
Fault LED is not active on the 5012KPM(T) and 5015KPM(T).
Brightness Control These buttons adjust the brightness of the backlights. The right button increases the brightness and the left button decreases the brightness.
Port Access The 5012KPM(T) and 5015KPM(T) feature front panel access to a PS/2 keyboard/mouse port and a USB 1.1 or 2.0 port (depending on capabilities of the host).
These front access connections on the 5012KPM(T) and 5015KPM(T) are nonincendive circuits and may be used safely in Class I Division 2,
Groups A, B, C, & D and in Class II Division 2, Groups F & G applications in which the peripheral electrical characteristics comply with the Hazardous Locations Control Drawing on page 29.
1
All keypad keys can be programmed to perform any function necessary.
2
You are able to create your own, custom keypad inserts to reflect any reprogramming you may have done.
3 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor Chapter 1 – Introduction
Feature
74-Key Keypad
Table 1-1. 5012KPM(T) & 5015KPM(T) Front Panel Controls Functions
Description
The 5012KPM(T) and 5015KPM(T) keypads feature:
•
Alpha, numeric and control keys
•
40 relegendable function keys
•
All keys reprogrammable (except the F/A key)
Integrated Mouse The 5012KPM(T) & 5015KPM(T) feature a 2-button integrated mouse.
See Chapter 5, Keypad Utility Program, for detailed instructions on programming the keypad. See Chapter 2, Installation, for detailed instructions on creating custom keypad inserts.
4 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor Chapter 1 – Introduction
Figure 1-2 shows a view of the KPM(T) monitor back panel. Figure 1-3 shows the bottom edge of the back panel, where the connectors are located.
Figure 1-2. 5012KPM(T) & 5015KPM(T) Back Panel, straight view
Figure 1-3. 5012KPM(T) & 5015KPM(T) Back Panel, bottom view
The back panel contains the OSD controls, the power connector, a video input connector, a pass-thru USB port (B-style connector), the serial touchscreen output connector, and the local and host ports for an external mouse and keyboard. The input range for the power supply is 100-240 VAC, 50-60 HZ, or 18-32 VDC.
Appendix A contains more information about the power connector pinouts.
5 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor Chapter 1 – Introduction
Table 1-2. 5012KPM(T) & 5015KPM(T) Back Panel Functions
No.* Feature
1
2
3
OSD controls
Mouse Local
Mouse Host
Description
Used to access, navigate and execute the OSD menu. The controls include the selector switch, and
Menu, Select, Increase and Decrease buttons
Used to plug in external mouse
Used to send both external mouse and integrated mouse signals to the computer (host), whether the optional external mouse is plugged into the local port on the back of the monitor or into the port on the front of the monitor
Used to plug in external keyboard 4 Keyboard Local
5
6
7
Keyboard Host
Touch Out RS-232
Pass-Thru USB**
Used to send the external keyboard and integrated keypad signals to the computer (host), whether the optional external keyboard is plugged into the local port on the back of the monitor or into the port on the front of the monitor
Used to send touch screen output to the computer
(host)
Used only as a pass thru port for USB signals to and from the host
8 Video In (VGA) Used to receive video input signal from computer
(host) VGA port.
9 AC Input (DC option) 100-240 VAC auto-ranging (18-30 VDC on DC models)
* See diagrams on previous page.
** USB devices plugged directly into this connector will not function.
The OSD controls are explained further in Chapter 3, Monitor Settings.
There must be an external cable connecting the “mouse host” port to the host computer for the integrated mouse to work. An external mouse can be plugged into either the front port or the “mouse local” port on the back of the KPM(T) monitor. If you are using an external mouse, there must be a cable going from the “mouse host” port to the host computer.
There must be an external cable connecting the “keyboard host” port to the host computer for the integrated keypad to work. An external keyboard can be plugged into either the front port or the “keyboard local” port on the back of the KPM(T) monitor. If you are using an external keyboard, there must be a cable going from the
“keyboard host” port to the host computer.
A Y cable may be used to connect both an external keyboard and an external mouse to the front port.
Caution
Do not connect either a mouse or keyboard cable from the PS/2 host port to the PS/2 local port. Damage can occur to either the host computer or the KPM(T) monitor.
6 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor Chapter 1 – Introduction
The Touch Out RS-232 is used when the touch screen option is utilized. A cable in this port sends the signals from the touch screen to the computer.
There is a USB port on the front of the monitor that can be used at any time. This is a pass-through only; there is no local USB activity on your KPM(T) monitor. To make your device work, you must have a cable going out to the computer from the USB port on the back of the monitor.
Caution
The USB cable that is used to connect the USB device cannot be more than 5 meters in length from the host computer, or the device will not work correctly. Pro-face ships a
3M USB cable with the 5012KPM(T) monitors and 5015KPM(T) monitors.
As a basic part of the initial setup of your KPM(T) monitor, you will connect a cable to both the AC port and the Video In port. The cable from the computer to the Video
In port provides the signal connection for the monitor. An RS-232 cable sends touch screen signals to the computer. A PS/2 cable connected to the ‘host keyboard’ port sends keypad (or an optional external keyboard) signals to the computer. A PS/2 cable connected to the ‘host mouse’ port sends integral mouse (or an optional external mouse) signals to the computer.
Unpacking the Unit
When you remove the KPM(T) monitor from its shipping box, verify that you have the parts listed below. Save the box and inner wrapping in case you need to reship the unit.
••••
••••
5012KPM(T) or 5015KPM(T) monitor
Documentation kit, which includes
•
10-32 hex nuts (12)
•
Analog RGB Cable (10 ft.)
•
RS-232C Cable (10 ft.)
•
Two PS/2 cables (10 ft.)
•
USB Cable (3 m)
•
Documentation and Support Library CD-ROM, which contains this manual and all drivers required by this unit
7 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor Chapter 1 – Introduction
Quick Startup
This section gives you the steps to get the system up and running without explaining the capabilities and options.
Warning
Remove power from the unit and disconnect the power cord before making any adjustments to the inside or outside of the monitor.
Warning
For Hazardous Locations installation, review Hazardous Locations
Installation in Chapter 2 before startup.
To prepare the system for use, perform the following steps.
1. Attach optional keyboard to the keyboard port.
2. Attach optional mouse to the mouse port.
3. Attach other optional equipment following the instructions in Chapter 2.
4. Attach the power cord from the power receptacle to a properly grounded 100-240
VAC, 50-60 Hz, or an optional 18-30 VDC power source. (See System Power in
Chapter 2 for more information.)
5. Turn on power to the KPM(T) monitor (via an outlet power switch if applicable).
Then turn on power to the host computer. The system will boot up into the operating system.
6. If the unit is equipped with a touch screen, install drivers on the host computer via the floppy, the CD-ROM, or the network, as applicable.
8 143448 (D)
Chapter 2 – Installation
This chapter offers detailed installation instructions and outlines the options for the
5012KPM(T) & 5015KPM(T). It also includes the guidelines for preparing your unit for installation and use.
Installation Overview
Warning
For Hazardous Locations installation, review the Hazardous Locations
Installation section in this chapter before startup.
The rugged design of the KPM(T) monitors allows the unit to be installed in most industrial environments. The system is generally placed in a NEMA 4/4X/12 enclosure to protect against contaminants such as dust, and moisture. Metal enclosures also help minimize the effects of electromagnetic radiation that nearby equipment can generate. Class II Hazardous Locations always require a Type 12
(dust-proof) minimum enclosure rating.
Read the following sections carefully to be sure that you are complying with all the safety requirements.
1. Select a NEMA rated enclosure and place the unit within the enclosure to allow easy access to the system ports (see other sections in this chapter and Appendix
A).
•
To assure a NEMA 4 seal, choose an approved enclosure that has a 14-gauge
(0.075 in/1.9 mm thick steel or 0.125 in/3.2 mm thick aluminum) front face.
•
Be sure to account for the unit’s depth when choosing the depth of the enclosure.
2. Create a cutout in the enclosure (see Figure 2-1 and Figure 2-2 in System Cutout
Dimensions).
•
Be sure to place the unit at a comfortable working level
•
Make sure the area around the cutout is clean and free from metal burrs
3. Mount the unit in an upright position and properly secure the unit into the panel.
•
Tighten the fourteen #10 nuts to 25 inch-pounds (2.8 Newton-meters / 28Kgf cm).
4. Attach one end of the power cord to the power receptacle on the unit and the other end to a properly grounded 100-240 VAC, 50-60 Hz outlet, or optional 18-
30 VDC power source.
9
143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 2 – Installation
5. Turn on power to the KPM(T) monitor, and then to the host computer. The system will boot up the installed operating system.
6. Install the application software via a floppy drive, CD-ROM, or the network.
Additional aspects to take into account when mounting your KPM(T) monitor:
••••
••••
••••
••••
••••
••••
••••
••••
••••
••••
Consider locations of accessories such as AC power outlets and lighting
(interior lighting and windows) for installation and maintenance convenience
Prevent condensation by installing a thermostat-controlled heater or air conditioner
To allow for maximum cooling, avoid obstructing the airflow
Place any fans or blowers close to the heat generating devices. If using a fan, make sure that outside air is not brought into the enclosure unless a fabric or other reliable filter is used. This filtration prevents conductive particles and other harmful contaminants from entering the enclosure.
Do not select a location near equipment that generates excessive electromagnetic interference (EMI) or radio frequency interface (RFI).
Examples of these types of equipment are: high power welding machines; induction heating equipment; and large motor starters.
Place incoming power line devices (such as isolation or constant voltage transformers, local power disconnects, and surge suppressers) away from the system. The proper location of incoming line devices keeps power wire runs as short as possible and minimizes electrical noise transmitted to the unit.
Make sure the location does not exceed the unit’s shock, vibration, and temperature specifications
Install the unit in the rack or panel in such a way as to ensure that it does not cause a hazard from uneven mechanical loading
Incorporate a readily-accessible disconnect device in the fixed wiring on permanently connected equipment
Avoid circuit overloading of the supply circuit
10 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 2 – Installation
System Cutout Dimensions
Figure 2-1 shows the cutout dimensions for the 5012KPM(T). Figure 2-2 shows the cutout dimensions for the 5015KPM(T).
5012KPM(T)
Figure 2-1. 5012KPM(T) system cutout dimensions (inches [mm])
11 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 2 – Installation
5015KPM(T)
Figure 2-2. 5015KPM(T) system cutout dimensions (inches [mm])
12 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 2 – Installation
Power Management
The monitor is based on the VESA DPMS and the DVI DMPM standards. To activate the monitor's Power Management function, both the video card and the computer must conform to the VESA DPMS standard and the DVI DMPM standard.
It is a good practice to use isolation transformers on the incoming AC power line to the system. An isolation transformer is especially desirable in cases in which heavy equipment is likely to introduce noise onto the AC line. The isolation transformer can also serve as a step-down transformer to reduce the incoming line voltage to a desired level. The transformer should have a sufficient power rating (units of volt-amperes) to supply the load adequately.
Proper grounding is essential to all safe electrical installations. Refer to the relevant federal, state/provincial, and local electric codes, which provide data such as the size and types of conductors, color codes and connections necessary for safe grounding of electrical components. The code specifies that a grounding path must be permanent
(no solder), continuous, and able to safely conduct the ground-fault current in the system with minimal impedance (minimum wire required is 18 AWG, 1 mm).
Observe the following practices:
• Separate the power and ground (P. E., or Protective Earth) cable from signal cables at the point of entry to the enclosure. To minimize the ground wire length within the enclosure, locate the ground reference point near the point of entry for the plant power supply.
• All electrical racks or chassis and machine elements should be Earth Grounded in installations where high levels of electrical noise can be expected. The rack/chassis should be grounded with a ground rod or attached to a nearby Earth structure such as a steel support beam. Connect each different apparatus to a single Earth Ground point in a "star" configuration with low impedance cable.
Scrape away paint and other nonconductive material from the area where a chassis makes contact with the enclosure.
The following figures diagram the power input terminal blocks for the KPM(T) monitors.
100-240 VAC
Power Input Terminal Block
Number
1
2
Function
AC Line Input
AC Neutral Input
3
Protective Earth
Ground
Figure 2-3 100-240 VAC Power Input Terminal Block
13 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 2 – Installation
18-30 VDC
Power Input Terminal Block
Number
1
2
Function
+ DC Line Input
– DC Return Input
3
Protective Earth
Ground
Figure 2-4. 18-30 VDC Power Input Terminal Block
Caution
Use 18 AWG (1mm) wire or greater for the monitor power cable
Isolate the AC main circuit line, I/O signal lines, and power cord. Do not bind or group them together.
To keep the temperature in range, the cooling air at the base of the system must not exceed the maximum temperature specification (see Environmental Specifications in
Appendix A). Allocate proper spacing between internal components installed in the enclosure. When the air temperature is higher than the specified maximum in the enclosure, use a fan or air conditioner to lower the temperature.
Electrical noise is seldom responsible for damaging components, unless extremely high energy or high voltage levels are present. However, noise can cause temporary malfunctions that can result in hazardous machine operation in certain applications.
Noise may be present only at certain times, may appear at widely spread intervals, or in some cases, may exist continuously.
Noise commonly enters through input, output, and power supply lines, and may also be coupled through the capacitance between these lines and the noise signal carrier lines. This usually results from the presence of high voltage or long, close-spaced conductors. When control lines are closely spaced with lines carrying large currents, the coupling of magnetic fields can also occur. Use shielded cables to help minimize noise. Potential noise generators include switching components, relays, solenoids, motors, and motor starters.
Refer to the relevant Federal, State/Provincial, and local electric codes, which provide data such as the size and types of conductors, color codes and connections necessary for safe grounding of electrical components. It is recommended that high- and low-voltage cabling be separated and dressed apart. In particular, AC cables and switch wiring should not be in the same conduit with all communication cables.
14 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 2 – Installation
The power supply section of the unit is built to sustain the specified line fluctuations and still allow the system to function within its operating margin. As long as the incoming voltage is adequate, the power supply provides all the logic voltages necessary to support the monitor unit.
Unusual AC line variations may cause undesirable system shutdowns. As a first step to reduce line variations, correct any possible feed problems in the distribution system. If this correction does not solve the problem, use a constant voltage transformer. The constant voltage transformer stabilizes the input voltage to the systems by compensating for voltage changes at the primary in order to maintain a steady voltage at the secondary. When using a constant voltage transformer, check that the power rating is sufficient to supply the unit.
!
Listed below are general compatibility issues that apply to the 5012KPM(T) and
5015KPM(T):
••••
••••
••••
••••
••••
The KPM(T) monitor must be powered up before the host computer is powered up so that the host can determine if a keyboard and mouse are connected. If the KPM(T) monitor is not powered up first, the host will determine that there is no mouse or keyboard available.
Once the complete system is up and running, the KPM(T) monitor can be power cycled at any time without affecting the host. It is the initial power up of the host that requires the power up sequence.
If an operating system is loaded on the host computer, the KPM(T) monitor should not be used as the host mouse or keyboard during the loading of the operating system. Instead, a mouse and keyboard can plug directly into the host for the loading of an operating system. The KPM(T) monitor can be used for the monitor only during the loading of the operating system.
The IBM specification for PS/2 ports defines both a Type I and Type II interface. The KPM(T) monitor is a Type II interface. Pro-face has determined that not all PS/2 compatible devices are Type II compatible. The user can try any standard PS/2 device, but Pro-face only guarantees the approved list.
Non-standard devices should not be used with the KPM(T) monitor. If a device does not meet the standard PS/2 definition, and does not use the standard PS/2 driver that comes with the operating system, it will not work reliably with the KPM(T) monitor. For example, if a device requires its own separate driver it probably will not work because it was written to expect that the device would be plugged directly into the computer’s host port. In the case of the KPM(T) monitor, this is not true.
Table 2-1. Known compatible and incompatible devices
Compatible
Microsoft®PS/2 Mouse
Logitech® Mouse
Incompatible
Dell® Mouse
••••
Daisy-chaining two or more KPM(T) monitors is not supported.
15 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 2 – Installation
••••
••••
••••
Special functions, such as Capslock and Numlock, cannot be part of a programmed keypad macro sequence.
Hot unplug of a full-travel keyboard or mouse from the KPM(T) monitor is not supported.
Using the Pro-face/Xycom models 33XX/34XX as a host is not supported.
Note
Maximum total USB cable length between the host and the USB device cannot exceed
5M. Example: 3M USB cable from the host computer to the KPM(T) monitor and a 2M
USB cable from the front of the KPM(T) monitor to the USB device.
XVME Compatibility Issues
Listed below are XVME compatibility issues that apply to the 5012KPM(T) and
5015KPM(T):
••••
••••
If you are going to connect a KPM(T) monitor to a Pro-face/Xycom XVME-660 or
XVME-661 processor board, the CPU module must have BIOS revision 1.3
(or higher). The Pro-face/Xycom BIOS revision number will appear at the top of the screen briefly during system boot-up. If you do not see the Pro-face/Xycom
BIOS revision number for the CPU module, enable the Boot Time Diagnostic
Screen in the Advanced menu of the BIOS setup (see the XVME-660 or
XVME-661 manual for more details). Older Pro-face/Xycom processor boards
(i.e. XVME-654, XVME-655, and older) have not been validated to work with the 5012KPM(T) or the 5015KPM(T).
Using the XVME-653, 656, 658 or 659 as a host is not supported.
To get a copy of the new BIOS revision, call Pro-face technical support at
734-944-0482, or email [email protected]
Using a Touch Screen
Pro-face/Xycom
’s touch screen complies with environmental specifications and maintains a NEMA 4 seal when panel mounted. The touch screen controller emulates a Microsoft PS/2 mouse. For more information about your touch screen, see Chapter
4, Operator Input.
16 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 2 – Installation
Custom Logo
You have the option to place a custom label on your unit. Refer to Figure 2-5 for the dimensions and recommended requirements for a customized label. Once a customized label is procured, place the new label over the “Pro-face/Xycom" label.
0.81 [20.57]
0.06 [1.52
(4 Places)
Your Logo On
Entire Surface
2.25 [57.15]
NOTE: All dimensions are in inches [mm]
Recommended material: 0.007 [0.176] thick polyester with 3M #468 adhesive on far side.
Figure 2-5. Logo Label Dimensions
Creating Custom Keypad Inserts
You can customize your keypad with keypad inserts to match the function keys that you program. Refer to Figure 2-6 and Figure 2-7 for insert dimensions for the
5012KPM(T). Refer to Figure 2-8 and Figure 2-9 for insert dimensions for the
5015KPM(T). Refer to Figure 2-10 for a keypad insert installation diagram.
17 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 2 – Installation
5012KPM(T) Keypad Inserts
The following figures show the dimensions for the 5012KPM(T) keypad inserts.
Figure 2-6. 5012KPM(T) Keypad Inserts with Dimensions (PF1 – PF10)
Note : The PF11-PF20 insert has the same dimensions
18 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 2 – Installation
Figure 2-7. 5012KPM(T) Keypad Insert with Dimensions (F1 - F20)
19 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 2 – Installation
5015KPM(T) Keypad Inserts
The following figures show the dimensions for the 5015KPM(T) keypad inserts.
Figure 2-8. 5015KPM(T) Keypad Inserts with Dimensions (PF1 – PF10)
Note : The PF11-PF20 insert has the same dimensions
20 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 2 – Installation
Figure 2-9. 5015KPM(T) Keypad Insert with Dimensions (F1 - F20)
21 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 2 – Installation
Keypad Installation Diagram
The following figure shows how to insert the custom keypads you have created.
Figure 2-10. Rear View of KPM(T)Monitor Bezel, with Keypad Insertion Points Marked
22 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 2 – Installation
Hazardous Locations Installation
Pro-face
designed the KPM(T) monitors to meet the requirements of
Class I and II, Division 2 Hazardous Locations applications. Division 2 locations are those locations that are normally non-hazardous, but could become hazardous due to accidents that may expose the area to flammable vapors, gases or combustible dusts.
These systems have been designed as non-incendiary devices. They are not intrinsically safe and should never be operated within a Division 1 (normally hazardous) location when installed as described here. Nor should any peripheral interface device attached to these systems be located within Division 1 locations unless approved and/or certified diode barriers are placed in series with each individual signal and DC power line. Any such installations are beyond the bounds of
Pro-face design intent. Pro-face accepts no responsibility for installations of this equipment or any devices attached to this equipment in Division 1 locations.
Note
When additional cards are added, it is the customer’s responsibility to ensure that the cards chosen meet operating conditions for Class I and II, Division 2 Hazardous
Locations
.
Additions and/or modifications without express consent from UL and/or
Pro-face
will void Hazardous Locations compliance.
It is the responsibility of the customer to ensure that the product is properly rated for the location. If the intended location does not presently have a Class, Division, and
Group rating, then users should consult the appropriate authorities having jurisdiction in order to determine the correct rating for that hazardous location.
In accordance with Federal, State/Provincial, and local regulations, all Hazardous
Locations installations should be inspected by the appropriate authority having jurisdiction prior to use. Only technically qualified personnel should install, service, and inspect these systems.
Warning
In order to maintain a safe condition, do not use an external keyboard or mouse when the unit is operating in a hazardous environment.
23 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 2 – Installation
" # #
The Pro-face systems have the following approvals:
••••
••••
Underwriters Laboratories Inc., UL 1604 Standard for Safety. Electrical equipment for use in Class I and Class II, Division 2, and Class III hazardous
(classified) locations (UL Listed, File E180970)
Underwriters Laboratories Inc., UL 508, “Industrial Control Equipment”
(UL Listed, File E107636)
••••
••••
Canadian Standard Association, Specification C22.2 No. 213-M1987. Nonincendiary electrical equipment for use in Class I, Division 2 Hazardous
Locations (cUL Listed, File E180970)
Canadian Standards Association, Specification C22.2 No. 142, Process
Control Equipment (cUL Listed, File E107636)
Warning
Suitable for use in Class I, Division 2, Groups A, B, C, and D, and Class II, Division 2,
Groups F and G Hazardous Locations or non-hazardous locations only.
Warning – Explosion Hazard
Substitution of components may impair suitability for Class I, Class II, Division 2.
Avertissement – Risque d’Explosion
La substitution de composants peut rendre ce materiel inacceptable pour les emplamements de classe I, II, Division 2.
Warning – Explosion Hazard
Do not disconnect equipment unless the power has been switched off or the area is known to be non-hazardous.
Avertissement – Risque d’Explosion
Avant de deconnecter l’equipment, coupler le courant ou s’assurer que l’emplacement est designe non dangereux.
24 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 2 – Installation
Warning – Explosion Hazard
When in Hazardous Locations, turn off power before replacing or wiring modules.
Avertissement – Risque d’Explosion
Dans les situations hasardees, couper la courant avant de remplacer ou de cabler les modules.
$ "
$
The following Class and Division explanations are derived from Article 500
(Sections 5 and 6) of the United States National Fire Protection Agency National
Electric Code (NFPA 70, 1990). The definitions are not complete and are included here only for a general description for those not familiar with generic Hazardous
Locations' requirements.
Persons responsible for the installation of this equipment in Hazardous Locations are responsible for ensuring that all relevant codes and regulations related to location rating, enclosure, and wiring are met.
Class I locations are those in which flammable gases or vapors are, or may be, present in the air in quantities sufficient to produce explosive or ignitable mixtures.
Class II locations are those that are or may become hazardous because of the presence of combustible dust.
%
A Division 1 location is one in which flammable or ignitable gasses, vapors, or combustible dusts and particles can exist due the following conditions:
••••
Normal operating conditions;
••••
••••
Because of repair, maintenance conditions, leakage, or mechanical failure or abnormal operation of machinery or equipment; or
Combustible dusts of an electrically conductive nature may be present in hazardous quantities.
Note
Pro-face
systems are not suitable for installation within Division 1 locations.
25 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 2 – Installation
Note
Electrical equipment cannot be installed in Division 1 locations unless they are intrinsically safe, installed inside approved explosion-proof enclosures, or installed inside approved purged and pressurized enclosures.
$ &
Division 2 locations are listed below:
••••
Class I volatile flammable liquids or flammable gasses are handled, processed, or used, but confined within closed containers or closed systems from which they can escape only in cases of accidental rupture or breakdown of such enclosures or systems, or in case of abnormal operation of equipment.
••••
••••
••••
Ignitable concentrations of Class I vapors or gasses are normally prevented by positive mechanical ventilation, but which may become hazardous due to mechanical failure of those ventilation systems.
Location is adjacent to a Division 1 location.
Class II combustible dust is not normally in the air in quantities sufficient to produce explosive or ignitable mixtures. Dust accumulations are normally insufficient to interfere with normal operation of electrical equipment or other apparatus. Combustible dust may be in suspension in the air as a result of the following: malfunctioning of handling or processing equipment; combustible dust accumulations on, or in the vicinity of electrical equipment; may be ignitable by abnormal operation or failure of electrical equipment.
!
All electrical equipment that is approved for use in Hazardous Locations must include a group rating. Various flammable and combustible substances are divided into these groups as a function of their individual maximum experimental safe gap
(MESG), explosion pressure, and ignition temperature.
Component temperatures and the potential for spark based upon voltage, current, and circuit characteristics, within electrical equipment, will determine what the equipment group rating will be. A device approved for installation within Class I,
Group A locations may also be used in Groups B, C, or D.
Note
Approved Class I equipment may not be suitable for Class II installations. Class I includes Groups A, B, C, and D. Class II includes Groups F and G.
26 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 2 – Installation
!
The systems are designed for installation within a clean and dry enclosure for both ordinary and Hazardous Locations. The front panel meets the requirements of UL and
CSA Type 4, 4X, and 12 enclosures. The enclosure used for Class I Hazardous
Locations should have a minimum rating of Type 12 (NEMA 12, IP 5X). However,
Type 4 (IP 6X) enclosures are strongly recommended.
Panel flatness and rigidity are important if a proper panel seal is to be maintained. If non-metal type enclosures, such as plastic or fiberglass, are to be used, install a rigid metal stiffener behind the front panel. Failure to do so may result in an inadequate panel seal due to flexure of the front panel material between the stud mounts. Tighten the nuts on the mounting studs to 25 inch-pounds.
The requirements for enclosure fittings, conduit, and wiring vary according to the specific rating of the location and the type of flammable or combustible material involved. Those requirements are beyond the scope of this document and it is the responsibility of the customer to ensure that the installation is compliant with codes and regulations that apply to their specific location. Refer to NFPA 70, Article 500 for specific regulations in the United States.
'
The KPM(T) monitors do not have a power switch. The amount of input power required by these systems classifies a power switch as an incendiary device because the voltage and current across the make/break device are capable of creating a spark.
Hazardous locations’ regulations require that a power switch rated for ordinary locations may be used if it is located in an area specified as non-hazardous. However, limits in cable length between the workstation and the power switch may apply.
Otherwise the switch must be compliant with Class I, Division 1 requirements
(intrinsically safe). These switches are built in a manner that prevents the possibility of a spark when contacts are made or broken.
Use suitable UL listed and/or CSA Certified Class I, Division 1 switches in
Hazardous Locations. These switches are available from a wide number of sources. It is the responsibility of the customer to ensure that the power switch selected for their installation has the correct Hazardous Locations rating for the location in which it is installed.
27 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 2 – Installation
Division 2 Hazardous Locations’ regulations require that all cable connections be provided with adequate strain relief and positive interlock. Front panel keyboard/mouse and USB ports may be used in Hazardous Locations with appropriate ratings if their electrical load characteristics comply with the Control
Drawing on 29.
All communication cables should include a chassis ground shield. This shield should include both copper braid and aluminum foil. The D-sub style connector housing should be a metal conductive type (e.g., molded zinc) and the ground shield braid should be well terminated directly to the connector housing. Do not use a shield drain wire.
The outer diameter of the cable must be suited to the inner diameter of the cable connector strain relief in order to ensure that a reliable degree of strain relief is maintained.
Warning
Never connect or disconnect the communication cables while power is applied at either end of the cable. This may result in an incendiary spark and permanent damage to the workstation communication components may occur.
Note
This warning does not apply to the front panel keyboard and USB interface connectors.
These connections are nonincendive circuits. Please refer to the Hazardous Locations control drawing on page 29.
28 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 2 – Installation
( ) !
$
Warning
The following control drawing applies to front panel ports only.
Class I, Division 2, Groups A, B, C and D, and Class II, Division 2, Groups F and G
Hazardous (Classified) Locations
Pro-face
/
Xycom
Model
5012KPM(T) or
5015KPM(T)
Front Panel USB and
PS/2 Ports
(see note 1)
Nonincendive Field
Wiring Apparatus
Notes:
1. Nonincendive Circuit Parameters:
USB Port (Pins 1 to 4) PS/2 Port (Pins 3 to 4)
V oc
= 5 VDC
I sc
= 3.3 A
C a
= 10 uF
V oc
= 5 VDC
I sc
= 3.3 A
C a
= 10 uF
L a
= 16 uH L a
= 4 uH
2. Selected nonincendive Field Wiring Apparatus shall satisfy the following:
Nonincendive Field Wiring Apparatus
Pro-face/X
ycom Models 5012KPM(T) and 5015KPM(T)
V max
I max
≥
≥
V oc
I sc
C i
+ C cable
≤ C a
L i
+ L cable
≤ L a
3. If the electrical parameters of the cable are unknown, the following values may be used:
Capacitance – 60 pF/ft
Inductive – 0.20 uH/ft
4. Nonincendive Field Wiring must be installed in accordance with Article 501.4(B)(3) of the
National Electrical Code ANSI/NFPA 70.
29 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 2 – Installation
* )+
The KPM(T) monitors have been designed for compliance with relevant spark ignition tests. However, please note that the workstation front panel contrast adjustment tactile switches and keyboard connector are the only make/break components intended to be exercised by the operator in the course of normal operation.
Warning
In order to maintain a safe condition, never use an external keyboard or mouse connected to side ports when the unit is operating in the presence of a hazardous environment. Use of the front panel USB/keyboard ports is safe only if the control drawing criteria is satisfied as indicated on the control drawing on page 29, and if the device is approved for use in the classified
Hazardous Location.
With respect to Hazardous Location installations, always observe the following rules:
1. Always install the workstations within an enclosure suitable for the specific application. General-purpose enclosures may be acceptable for Class I applications but are never acceptable for Class II applications. Type 4 (IP 65) enclosures are recommended even when not required by regulations.
2. If present, keep enclosure doors or openings closed at all times, to avoid the accumulation of foreign matter inside the workstation.
3. Never subject the unit to any installation or service procedures unless power has been removed and the area is known to be non-hazardous. This includes the installation or removal of power cables, communication cables, or removal of the rear cover of the unit.
4. Only technically qualified service personnel should perform all installation and service. These workstations are designed to require no service in the course of normal operation by an operator.
30 143448 (D)
Chapter 3 – Monitor Settings
On Screen Display (OSD) Switch
The OSD Select switch is located on the back panel and offers two choices: OFF or
ON. The OSD keys can be locked-out by setting the OSD switch to OFF, or unlocked by setting the OSD switch to ON. Setting this switch to the OFF position will help prevent accidental changes to the settings. The OSD switch is next to the Menu,
Select and Increase/Decrease buttons (see Figure 3-1).
Caution
Touch data is transmitted to host computer while OSD menu is displayed.
Mode and Image Adjustment
Not all video controllers produce exactly the same video output levels or the same timing. The KPM(T) monitors use onscreen configuration menus to make setup and adjustment easy. The menus are selected and the menu items are adjusted using the buttons located on the back panel of the monitor (see Figure 3-1). You need only tap the buttons to activate each one. Table 3-1 outlines the functions of these controls.
Controls
Figure 3-1. Back Panel Control Buttons
Table 3-1. Back Panel Control Button Functions
Function
!
!
"
" $
#
With the OSD enabled, use the back panel control buttons to navigate through the adjustment menus and make adjustments. Press MENU to view the onscreen OSD
31
143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 3 – Monitor Settings
Functions menu. Use INC or DEC to highlight one of the adjustment menus, and
SELECT to access it. The adjustment menus are explained in Figure 3-2.
Note
The OSD will time out if you do not complete a task within a specified time period.
The default setting is 15 seconds, but you can change the setting in the OSD Timeout submenu, under Miscellaneous.
* $ !
Figure 3-2.OSD Functions menu
Press MENU to select the highlighted adjustment menu; the first adjustment option in the menu will be highlighted. Use INC or DEC to select a submenu, and then press
SELECT to access the submenu. Use INC or DEC to adjust the value of the highlighted option. Press SELECT to save the changes or MENU to cancel. Repeat the instructions above for selecting another adjustment menu. Press MENU again to exit the OSD adjustment menus.
32 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 3 – Monitor Settings
Note
To adjust the brightness of the backlights on the monitor, use the or
keys on the monitor’s keypad, not the brightness adjustment submenu in the OSD.
The Brightness and Contrast menus allow you to change the display on your flat panel monitor. Once the unit is mounted in a rack, however, the back panel controls will be less accessible. The Brightness control features on the front panel should be used instead.
Figures 3-3 through 3-7 show the adjustment options in the submenus for the color menu, the RGB menu, the position menu, the image menu, and the miscellaneous menu.
Note
In the following tables, the INC button is referred to as “+“, and the DEC button is referred to as “-“.
The color submenu offers three options: Auto Balance; RGB; and Color temperature.
Figure 3-3 outlines the functions of these choices.
Figure 3-3. Color submenu
The RGB submenu allows you to adjust the Red, Green and Blue on the monitor.
Figure 3-4 explains how these options work.
Figure 3-4. RGB submenu
The Position submenu offers three options as well: Image Horizontal Position; Image
Vertical Position; and Auto Center. Figure 3-5 explains these options.
33 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 3 – Monitor Settings
Figure 3-5. Position submenu
Figure 3-6 shows the three options available in the Image submenu: Phase;
Horizontal size; and Auto phase
Figure 3-6. Image submenu
Figure 3-7 explains the three options available in the Miscellaneous submenu: Load
Default; OSD Timeout; OSD position.
Figure 3-7. Miscellaneous submenu
, $ "!
To reset the factory default settings on your monitor, follow these steps.
1. Navigate to the Miscellaneous menu and highlight Load Default.
2. Press SELECT to enter submenu, which will ask you to choose yes or no.
3. Press the INC key to highlight yes, and press SELECT to enable your choice.
4. The default settings will be loaded as the submenu is exited.
Analog RGB Interface Specifications
Listed below are the Analog RGB Interface specifications.
• Based on VESA standard, separate analog RGB
• 0.7Vp-p positive true typically
• Input range: 0.5 to 1.0Vp-p typical with terminal resistance of 75Ω
• H sync signal input: TTL level, negative true or positive true
• V sync signal input: TTL level, negative true or positive true
34 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 3 – Monitor Settings
Graphic Modes
The following table lists the supported graphic modes for the KMP(T) monitors.
Table 3-2. Supported Video Modes
NOTE
All video modes are non-interlaced.
If the monitor is receiving timing signals that are not compatible, [OUT OF TIMING] will appear. Follow your computer’s instruction manual to set the timing so that it is compatible with the monitor.
If the monitor is not receiving any signal, [NO SIGNAL] will appear.
35 143448 (D)
Chapter 4 – Operator Input
Installing the Touch Screen Driver
In order to use the touch screen on your KPMT monitor, you must install the proper driver on the computer hooked to your monitor.
For computers running Windows® 98, NT, 2000, or XP, you will be installing the driver
.
This driver can be found in the
“Drivers\Touchscreen” folder on the Documentation and Support Library CD that shipped with your monitor. The default setting is serial mode.
1. Create a folder named “Touch” on your desktop or in the root directory of your C: drive, and unzip the files into the folder.
2. Click on the file “setup.exe” and follow the directions. Pro-face suggests that you accept all of the defaults.
3. Calibrate the touchscreen, following the directions in the next section.
Caution
When using MS-DOS®, the mouse driver must be loaded before the touch screen driver if both a mouse and touch screen are to be supported.
For computers running MS-DOS®, you will be installing the driver,
. This driver can be found in the “Drivers\Touchscreen” folder on the Documentation and Support Library CD that shipped with your monitor.
1. Create a directory named “Touch” in the root directory of your C:\ drive and unzip the files into the folder.
2. Run the file “install.exe” in the TB458 subdirectory and follow the directions. Pro-face suggests that you accept all of the defaults.
3. Copy all of the batchfile utilities from the Batch Files subdirectory to C:\
4. Add the command
5. Re-boot your system.
to your autoexec.bat file.
6. Calibrate the touchscreen, following the directions in the next section.
Caution
It is recommended that you keep all default setting when installing the driver.
The touch screen drivers are located on the Document and Support Library CD, which is shipped with you unit. Drivers can also be downloaded from http://www.profaceamerica.com
.
36
143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 5 – Keypad Utility Program
Calibrating the Touch Screen
You need to calibrate the touch screen in the following cases:
•
The cursor does not follow the movement of your finger or pen.
•
You adjust the size of the video image or change the video mode.
For computers running Windows® 98, NT, 2000, or XP: Before calibrating your touch screen, Pro-face strongly recommends altering the following default settings in the calibration program.
1. Go to START/PROGRAMS/UPDD/SETTINGS
2. Click on the Calibration tab.
3. Set the Calibration points to 25.
4. Set the Margin Percentage to 1.
Note
If the Margin Percentage is set to 0, the calibration may not be correct at the edges of the screen, causing the cursor to jump unexpectedly.
5. Click on the Settings tab.
6. Set the Averaging to 0.
7. Click Apply.
You are now ready to calibrate your touch screen. Follow the instructions found in the following applet to calibrate the touch screen:
START/PROGRAMS/UPDD/CALIBRATE
Note
The touch screen and controller is a matched pair calibrated at the factory. If touch screen and controllers are interchanged calibration may be needed.
For computers running MS-DOS®, the touch screen drivers must be loaded before you can calibrate. After the drivers are loaded, switch to C:\Touch, and run
TBCAL.EXE to calibrate the touch screen:
1. Enter the "H" command for hard calibrate
2. Touch the cross hairs as directed by the calibrate utility
3. Save the settings
4. Exit the calibrate utility with the "X" command
37 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 5 – Keypad Utility Program
Chapter 5 – Keypad Utility Program
The keypad utility program allows users to redefine any or all of the keypad keys on the unit with new scan codes, using utility software. You must use an external fullstroke PC/AT keyboard to access the utility. This chapter explains how to load the keypad utility, and details how the program’s pull-down menus work. Also included in this chapter are the default keypad scan codes.
Note
Your external full-stroke PC/AT keyboard cannot be redefined by running the keypad utility.
Note
The keypad switch arrays are disabled while the keypad utility is running.
Loading the Keypad Utility
Note
Pro-face/X ycom’s keypad utility will only run under DOS 3.2 or better.
The
keypad utility will not run in a Windows environment.
The keypad utility is on the “Documentation & Support Library” CD that shipped with your computer. You will find the self-extracting zip file, Keypad Utility 1.1
142606-001.exe, in the folder:
DRIVERS\Keypad Software\Keypad Utility 1.1 142606-001
If your computer is running DOS (revision 3.2 or better), create a subdirectory on your hard drive for the files, and extract the files on the disk into that subdirectory.
To run the utility, go to the subdirectory and type kp3util at the DOS prompt.
If your computer is not running DOS, you will need to extract the files onto a
DOS-bootable diskette. The diskette is then inserted into the floppy drive. You will need to reboot your computer for the computer to access the program. To run the utility, type kp3util at the DOS prompt.
Using the Keypad Utility
The keypad utility uses a menu bar and pull-down menu system. All menu bars are displayed across the top of the screen. “Proface/Xycom KP3 Utility” and the current menu titles are shown at the bottom of the screen (see Figure 5-1).
38 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 5 – Keypad Utility Program
Startup
A full-stroke keyboard is needed to enter keystrokes while recording a new key macro, editing an existing macro, or entering utility commands. You can redefine all keys on the keypads, except the F/A (Function/Alpha) key. While the utility is running, the keypads are disabled.
Dialog boxes appear for user prompts, and to display error and user advice messages.
Any keys used specifically in each menu are shown at the bottom of each screen (see
Figure 5-1).
Two keys allow you to exit the menus:
• ESC moves to the previous menu or out of the utility from the Main Menu
• F1 returns to the current menu headings in some of the menus where
Exit
can be chosen to exit this menu
To begin using the keypad utility, type kp3util at the prompt (for the floppy drive when no DOS is available, or the subdirectory you created earlier). The program will bring up the main menu. Open the def3612.pkm file in the main menu to program the keypad. (This file contains the default keypad settings for the KPM(T) monitors.)
Changes to the default file should be saved to a new file with the pkm extension. If you do not open a file, the macros pull-down menu will not be available.
Note
If you make any changes to your keypad and want to set it back to the default settings, open the pkm file for your unit (e.g., def3612.PKM for 5015KPM) from the File/Open menu, and then download it from the download menu.
Caution
Do not save any changes to the default files.
Main Menu
Figure 5-1 shows the Main Menu screen. The functions of the pull-down menus are described in the following sections.
Note
Exit and Download do not have pull-down menus.
Note
Use
F
1 to access the menu bar options in the
kp3util
program.
39 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 5 – Keypad Utility Program
Exit Files
Open
Close
Save
Save As
Delete
Exit
Macros
Function Keys
Alpha Keys
Upload
KP Ctl. Version
Exit
Download Utilities
Factory Default
Exit
<Company Name>
KP3 Utility: MAIN L-Arrow, R-Arrow, Enter
Figure 5-1. Main Menu, showing first-level pull-down menus
Exit closes any open files and exits the utility.
ESC can also be used for this purpose.
ESC
works for exiting the other menus as well.
+ !
When you choose Files, a pull-down menu will display the following choices: Open,
Close, Save, Save As, Delete, and Exit. The following table describes these menu commands.
Table 5-1. Files Menu
Command Description
Open Opens a file that contains a macro set for the keypad and loads the contents into memory. Any macro set in memory is overwritten. Once loaded, the macro set is available to edit, view, teach, or download to the keyboard controller.
Close Clears the macro set from memory and closes the file from which the set came.
Save
Save As
Delete
Exit
Copies the macro set from memory back into its original file. The original file contents are overwritten.
Creates a new file under the specified name and copies the macro set from memory into it. For example, to define different sets of codes, save each set under a different name and download the one you wish to use.
Deletes a file.
Returns to the Main Menu.
You can save files containing keypad macro sets (a macro for each key) on disk, and then load them into memory to view, edit, teach, or download to the keyboard controller. Some of these files may be included in the utility package for use in reconfiguring the keypads for different software packages, and as templates for defining completely new keypad macro sets.
40 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 5 – Keypad Utility Program
+ + !
Note
You must have a macro file in memory before the Macros Menu is available. To load a macro file, select the File/Open menu.
When you select Macros, a keypad type pull-down menu is available. This pull-down menu provides the following choices: Function Keys, Alpha Keys, and Exit. Table
5-2 explains the commands in the Macros Keypad Type menu.
Table 5-2. Macros Keypad Type Menu
Command Description
Function Keys Selects the function keys on the keypad to view, edit, or teach.
Alpha Keys Selects the alpha keys on the keypad to view, edit, or teach.
Exit Returns to the main menu.
After choosing which keys you want to work with (Function or Alpha), another pulldown menu becomes available. This macros edit menu displays the following choices: Exit, View, Teach, and Edit. Table 5-3 explains the commands in the
Macros Edit menu.
Table 5-3. Macros Edit Menu
Command Description
Exit Returns to the Main Menu.
View Lets you view, but not edit, the macro for the selected key. When View is chosen, the Exit option is displayed on the menu bar and a graphic representation of the chosen keypad is shown. To return to the Macros
Menu, select Exit from the View Menu.
To select a key to view, use the arrow keys to position the cursor on the desired key and press
ENTER
. The macro is displayed as two lines: ASCII and code. The ASCII line displays each keycode as the keys it represents on the full-stroke keyboard. Special labels are used for certain keys (e.g.,
Spc for space bar, UAr for up arrow, and bk for the break code prefix). The code line is displayed in either Hex or decimal. There is a one-to-one correspondence between the ASCII and code lines.
While viewing the macro, the menu bar displays two options: Exit and
Hex/Decimal. To access the menu bar, use
F
1. Exit returns to the View
Menu; Hex/Decimal toggles between displaying the macro in hex or decimal format. When Hex is chosen, the keycodes are displayed as hexadecimal value scan codes. When Decimal is chosen, the keycodes are displayed as the decimal equivalent of the hex codes.
For example, the macro
abc
would be displayed as 1C F0 1C 32 F0 32 21
F0 21 in hex, and 28 240 28 50 240 50 33 240 33 in decimal.
41 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 5 – Keypad Utility Program
Table 5-3. Macros Edit Menu
Command Description
Teach Allows you to record up to 105 keystrokes in a macro. When Teach is selected, a graphic representation of the keypad currently in memory displays. Menu bar choices are Exit, ASCII, and Click OFF. To access the menu bar, use
F
1.
As usual, Exit returns you to the Macros menu. ASCII specifies the format to display the keystrokes as they are entered. ASCII is the default setting.
The Click OFF choice is not supported.
To select a key to define, use the arrow keys to position the cursor on the desired key and press
ENTER
. After you select a key, the utility records every keystroke made on the external full-stroke keyboard. The keystrokes are saved in a macro assigned to the chosen key. As the keystrokes are entered, they are displayed using the chosen format.
ESC stops recording and returns you to the Teach Menu, so you cannot record the
ESC key. However,
ESC can be included in a macro by using the editor.
Changes made to the macros in the Teach Menu are not programmed until you select Download.
Edit
Edit/Cut
Displays a graphic representation of the keypad in memory and a menu bar displaying Exit and Click OFF. Exit returns to the Macros menu. Click
OFF is not supported.
To select a key to edit, use the arrow keys to position the cursor on the desired key and press
ENTER
. In edit mode, the macro is displayed as two lines. The top line displays the macro in either hex or decimal format, and is the line in which the editing takes place. The bottom line displays the macro in ASCII format; this line is not user configurable. The bottom line keeps track of which part of the macro being edited, and is updated by the utility as editing takes place. The insert, delete, and cursor control keys on the full-stroke keyboard are active for editing.
When a key is selected from the Edit Macro option, the menu bar displays the following choices: Exit, Cut, Copy, Paste, Codes, Hex, and I/O
(Insert/Overtype). The macro for the chosen key is also displayed. To access the menu bar, use
F
1. Use the Insert key on your full-stroke external keyboard to toggle between insert and overtype mode.
Cut deletes a sequence of scan codes from the macro. To select a section to cut:
1. Place the cursor on the first character to cut.
2. Press
F
1 (to access the menu bar choices) and select
CUT
.
3. Press
ENTER
. Cut should still be highlighted, but the cursor will appear on the Edit line. Move the cursor on the last character to cut and press
ENTER
.
The last character of every macro is the end of the macro (EOM) and cannot be deleted.
42 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 5 – Keypad Utility Program
Table 5-4. Macros Edit Menu
Command Description
Edit/Copy Copy duplicates a sequence of scan codes from the macro into memory.
To select the section to copy:
1. Place the cursor on the first character to copy. Press
F
1 and select
Copy.
2. Press
ENTER
. Copy should still be highlighted, but the cursor will appear on the Edit line.
3. Move the cursor to the last character to copy and press
ENTER
.
The copied item does not appear on the screen until you select Paste.
Edit/Paste Paste inserts a sequence of scan codes (which were saved in memory using Copy) into the macro. To paste a sequence of scan codes that were previously copied, position the cursor where you want the text to appear and then press
F
1. Select Paste and then press
ENTER
.
Codes displays a table of keys and their scan codes in Hex. See the
Codes section in this chapter for a complete code listing.
Hex/Decimal toggles between displaying the scan codes in Hex and
Decimal formats.
I/O allows the user to insert text or type over text in the code(s). Use the
Insert key on your full-stroke external keyboard to toggle between insert and overtype mode.
-
$
Note
The 5012KPMT and 5015KPMT do not support the programming of special functions such as caps lock, Number lock, or scroll lock.
)+ !
Use the Upload Menu to access the keypad version. As illustrated in Table 5-5, the choices in this menu are Keypad Version and Exit.
Table 5-5. Upload Menu
Command Description
Keypad
Version
Exit
Commands the keyboard controller to send its firmware revision number.
Returns to the Main Menu.
)+ !
Note
Download contains no options. If you select Download, any macro set previously programmed is overwritten.
43 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 5 – Keypad Utility Program
Caution
The macros set in memory should be saved before downloading. If the set is not saved, all changes will be lost.
Download should be used only after all the keypad keys have been programmed and saved to a *.pkm file. Selecting Download prior to saving changes will result in a loss of all keypad macro programming.
When you select Download, the program creates a download file called download.dld and loads the keypad controller’s non-volatile memory with the new macros, which become the new key definitions for the keypad. After the download is complete, the system will prompt the user to cycle power.
+ !
When the Utilities menu is selected, two choices are displayed: Factory Default, and
Exit. Table 5-6 explains these choices.
Table 5-6. Utilities Menu
Command Description
Factory Default Reprograms the keypad macros to the factory default settings. After completion, the system will need to be power cycled.
Exit Returns to the Main Menu.
Utility Batch Mode
The Utility Batch Mode can be used to reprogram keypads on multiple units with the same customized keypad macros. This feature is useful because it allows you to do the reprogramming without having to enter the full keypad utility for each individual unit. After you have programmed the first keypad macros, you will need to create a
DOS-bootable diskette to run the Utility Batch Mode.
You will need to extract files from the Documentation and Support Library CD-ROM to for the diskette. The necessary files can be found in the folder,
DRIVERS\Keypad Software\Keypad Utility 1.1 142606-001
Save the following files from the CD-ROM to the root directory on your DOSbootable diskette:
••••
••••
••••
••••
••••
••••
••••
H8flash.exe
KP3util.exe
H8fload.mot
*.pkm codes.pkm symbols.pkm download.dld
44 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 5 – Keypad Utility Program
Then, insert the diskette into the unit you want to reprogram and reboot it. At the
DOS prompt, type the kp3util *.pkm to run the reprogramming function. This utility can be used on as many units as necessary.
Note
The
*.pkm
file is the macro file you saved in the earlier step. The * indicates the name you selected for the file.
Note
The
download.dld
file was created after the last keypad programming process.
This includes both new programming and reprogramming the keypad to the factory default settings.
Keypad Scan Codes
The utility’s default keypad keycodes are listed in the following table.
Table 5-7. Default Keypad Keycodes
F/A Key LED Off (Function Mode) F/A Key LED On (Alpha Mode) 5012KPM(T)
5015KPM(T)
Description of Key
PF1 / A
PF10 / J
F1 / K
F2 / L
F3 / M
F4 / N
F5 / O
F6 / P
F7 / Q
PF2 / B
PF3 / C
PF4 / D
PF5 / E
PF6 / F
PF7 / G
PF8 / H
PF9 / I
F8 / R
F9 / S
F10 / T
F11 / U
F12 / V
Make
Codes
14 05
0C
03
0B
83
14 09
05
06
04
14 06
14 04
14 0C
14 03
14 0B
14 83
14 0A
14 01
0A
01
09
12 05
12 06
Keyboard
Equivalent
F21
F4
F5
F6
F7
F30
F1
F2
F3
F8
F9
F10
F11
F12
F22
F23
F24
F25
F26
F27
F28
F29
Break Codes
F0 05 F0 14
F0 06 F0 14
F0 04 F0 14
F0 0C F0 14
F0 03 F0 14
F0 0B F0 14
F0 83 F0 14
F0 0A F0 14
F0 01 F0 14
F0 09 F0 14
F0 05
F0 06
F0 04
F0 0C
F0 03
F0 0B
F0 83
F0 0A
F0 01
F0 09
F0 05 F0 12
F0 06 F0 12
Make
Codes
1C
31
44
4D
15
3B
42
4B
3A
2D
1B
2C
3C
2A
2B
34
33
43
32
21
23
24
N
O
P
Q
J
K
L
M
R
S
T
U
V
F
G
H
I
B
C
D
E
Keyboard
Equivalent
A
Break Codes
F0 1C
F0 32
F0 21
F0 23
F0 24
F0 2B
F0 34
F0 33
F0 43
F0 3B
F0 42
F0 4B
F0 3A
F0 31
F0 44
F0 4D
F0 15
F0 2D
F0 1B
F0 2C
F0 3C
F0 2A
45 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 5 – Keypad Utility Program
5012KPM(T)
5015KPM(T)
Description of Key
F13 / W
F14 / X
F15 / Y
F16 / Z
F17 / :
F18 / /
F19 / \
F20 / *
PF11 / (
PF12 / )
PF13 / ?
PF14 / ^
PF15 / %
PF16 / $
PF17 / @
PF18 / <
PF19 / >
PF20 / ~
CTRL
SHIFT
ESC
ALT
TAB
DEL
F/A
SPACE
BACKSPACE
9
.
7
8
3
4
5
6
1
2
0
=
PgUp up arr
F/A Key LED Off (Function Mode)
Keyboard
Equivalent
F31
F32
F33
F34
F35
F36
F37
F38
F39
F40
CTRL
1
SHIFT
1
ESC
ALT
1
F13
F14
F15
F16
F17
F18
F19
F20
TAB
DEL
SPACE
BACKSPACE
9
.
7
8
3
4
5
6
1
2
0
=
PgUp up arr
Make
Codes
Table 5-7. Default Keypad Keycodes
Break Codes
F/A Key LED On (Alpha Mode)
Keyboard
Equivalent
11 05
11 06
11 04
11 0C
11 03
11 0B
11 83
11 0A
12 04
12 0C
12 03
12 0B
12 83
12 0A
12 01
12 09
11 01
11 09
14
12
76
F0 04 F0 12
F0 0C F0 12
F0 03 F0 12
F0 0B F0 12
F0 83 F0 12
F0 0A F0 12
F0 01 F0 12
F0 09 F0 12
F0 05 F0 11
F0 06 F0 11
F0 04 F0 11
F0 0C F0 11
F0 03 F0 11
F0 0B F0 11
F0 83 F0 11
F0 0A F0 11
F0 01 F0 11
F0 09 F0 11
F0 14
F0 12
F0 76
26
25
2E
36
29
66
16
1E
11
0D
F0 11
F0 0D
ALT
TAB
E0 12 E0 71 E0 F0 71 E0 F0 12 DEL
F0 29
F0 66
F0 16
F0 1E
SPACE
BACKSPACE
F0 26
F0 25
F0 2E
F0 36
3
4
5
6
1
2
3D
3E
46
49
F0 3D
F0 3E
F0 46
F0 49
9
.
7
8
45
55
F0 45
F0 55
0
=
E0 12 E0 7D E0 F0 7D E0 F0 12 PgUp
E0 12 E0 75 E0 F0 75 E0 F0 12 up arr
%
$
@
<
?
^
(
)
:
/
\
*
W
X
Y
Z
>
~
CTRL
SHIFT
ESC
Make
Codes
Break Codes
12 46
12 45
12 4A
12 36
12 2E
12 25
12 1E
12 41
1D
22
35
1A
12 4C
4A
5D
12 3E
12 49
12 0E
14
12
76
3D
3E
46
49
26
25
2E
36
29
66
16
1E
11
0D
F0 11
F0 0D
E0 12 E0 71 E0 F0 71 E0 F0 12
F0 29
F0 66
F0 16
F0 1E
F0 26
F0 25
F0 2E
F0 36
F0 3D
F0 3E
F0 46
F0 49
45
55
F0 45
F0 55
E0 12 E0 7D E0 F0 7D E0 F0 12
E0 12 E0 75 E0 F0 75 E0 F0 12
F0 1D
F0 22
F0 35
F0 1A
F0 12 F0 4C
F0 4A
F0 5D
F0 12 F0 3E
F0 12 F0 46
F0 12 F0 45
F0 12 F0 4A
F0 12 F0 36
F0 12 F0 2E
F0 12 F0 25
F0 12 F0 1E
F0 12 F0 41
F0 12 F0 49
F0 12 F0 0E
F0 14
F0 12
F0 76
46 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Chapter 5 – Keypad Utility Program
5012KPM(T)
5015KPM(T)
Description of Key
+ left arr
HOME right arr
PgDn down arr
-
ENTER
END
Left Start
Explorer
Table 5-7. Default Keypad Keycodes
F/A Key LED Off (Function Mode) F/A Key LED On (Alpha Mode)
Keyboard
Equivalent
+
2 left arr
HOME right arr
PgDn down arr
-
2
ENTER
1
END
Mouse click
(windows start menu)
Mouse click
(windows pop-up menu)
Make
Codes
Break Codes Keyboard
Equivalent
79 F0 79 +
E0 12 E0 6B E0 F0 6B E0 F0 12 left arr
E0 12 E0 6C E0 F0 6C E0 F0 12 HOME
E0 12 E0 74 E0 F0 74 E0 F0 12 right arr
E0 12 E0 7A E0 F0 7A E0 F0 12 PgDn
E0 12 E0 72 E0 F0 72 E0 F0 12 down arr
7B
5A
F0 7B
F0 5A
-
ENTER
E0 12 E0 69 E0 F0 69 E0 F0 12 END
E0 12 E0 1F E0 F0 1F E0 F0 12
E0 12 E0 2F E0 F0 2F E0 F0 12
Make
Codes
Break Codes
79 F0 79
E0 12 E0 6B E0 F0 6B E0 F0 12
E0 12 E0 6C E0 F0 6C E0 F0 12
E0 12 E0 74 E0 F0 74 E0 F0 12
E0 12 E0 7A E0 F0 7A E0 F0 12
E0 12 E0 72 E0 F0 72 E0 F0 12
7B
5A
F0 7B
F0 5A
E0 12 E0 69 E0 F0 69 E0 F0 12
E0 12 E0 1F E0 F0 1F E0 F0 12
E0 12 E0 2F E0 F0 2F E0 F0 12
1
: Use the keyboard buttons located on the left side of the keyboard, i.e. the buttons normally used with the alpha keys
2
: Use the keyboard buttons located on the right side of the keyboard, i.e. the buttons normally used with the numeric keys
Additional notes:
• F11-F20 = SHIFT F1-F10
• F21-F30 = CTRL F1-F10
• F31-F40 = ALT F1-F10
• END, LEFT START, and EXPLORE keys are available.
47 143448 (D)
Chapter 6 – Maintenance
The KPM(T) monitors are designed to withstand the harsh environment of the factory floor. Routine maintenance can help keep your system in good operating condition.
Preventive maintenance consists of several basic procedures that will greatly reduce the chance of system malfunction. Schedule preventive maintenance along with the regular equipment maintenance to minimize down time.
General Preventive Maintenance
Here are some preventive measures you can take:
••••
Clean the monitor screen using a non-residue cleaner such as a mild window cleaning solution or CRT screen cleaner. Take care not to scratch the screen face.
••••
••••
Base your maintenance schedule on the type of environment the system is in
(i.e., if the area is dusty, you should schedule maintenance more often than if it is a dry, clean area).
Check the connections to I/O modules, especially in environments where vibration could loosen the connections. Check to see that all plugs, sockets, terminal strips, and module connections are solid.
••••
••••
Remove unnecessary articles, such as drawings or manuals, from the unit.
They can obstruct airflow and create hot spots, which cause the system to malfunction.
Do not place noise-generating equipment near the KPM(T) monitor.
!
,
The KPM(T) monitor has no accessible fuse. Return the unit to the factory for fuse replacement.
Troubleshooting
Pro-face
Technical Support offers a variety of support options to answer any questions about Pro-face products and their implementation. You may call Technical Support directly at 734-944-0482, or via email at [email protected]
.
" . ' !
Before contacting Technical Support, refer to the relevant chapter(s) in your documentation for a possible solution to any problem you may have with your system.
48
143448 (D)
KPM(T) Series Flat Panel Industrial Monitor Chapter 6 – Maintenance
If you find it necessary to contact Technical Support for assistance, please have the following information at hand:
1. Serial number and model number.
2. The operating system type and version (i.e., Microsoft Windows NT version
4.0 used on host computer).
3. Exact wording of system error messages encountered.
4. Any relevant output listing from the Microsoft Diagnostic utility (MSD) or other diagnostic applications.
5. Details of attempts made to rectify the problem(s) and results.
6. The log number assigned from Pro-face Technical Support if this is an ongoing problem.
7. The name of the Technical Support Engineer with whom you last spoke, if known.
Product Repair Program
Pro-face ’s Product Repair & Customization Department (PR&C) restores equipment to normal operating condition and implements engineering changes that enhance operating specifications. Pro-face tests products returned to Pro-face with the standard Pro-face test diagnostics.
Follow the steps below to prepare the unit for shipment:
1. Obtain a Return Merchandise Authorization (RMA) number for your unit by calling your nearest Pro-face Repair Department or Xycom Automation, LLC. at 734-429-4971.
2. Please have the following information:
••••
Company name, shipping and billing address
••••
••••
••••
••••
Type of service desired: product repair or product exchange
Product model number, part number, quantity, serial number(s), and warranty status
Failure mode and failure systems
Purchase order number or repair order number
3. Make sure the front panel assembly is properly attached to the unit.
4. Attach failure information to the unit to speed processing.
5. Place the unit securely in its original packaging or an equivalent heavy-duty box.
6. Mark the RMA number on your purchase order and on the outside of the box.
7. Send the unit to the address given when you receive your RMA number.
49 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor Chapter 6 – Maintenance
KPM(T) Monitors Front Panel Frame
The 5012KPM(T) and 5015KPM(T) front panel frames are made of powder-coated aluminum. The key ingredients are pure polyester, TEPIC-G, titanium oxide, barium sulfate, leveling agent, and carbon black.
' '
Table 6-1 should be used only as a guide. Specific testing should be conducted to verify that the unit’s finish would meet the demands of extreme environments.
CHEMICAL
Acetic, 10%
Acetic, Glacial
Benzene Sulfonic, 10%
Benzoic
Boric
Butyric, 100%
Chloracetic, 10%
Chromic, 5%
Citric, 10%
Fatty Acids
Fluosilicic
Formic, 90%
Hydrobromic, 20%
Hydrochloric, 20%
Hydrocyanic
Hydrofluoric, 20%
Hypochlorous, 5%
Lactic, 5%
Maleic, 25%
Nitric, 5%
Nitric, 30%
Oleic
Oxalic
Phosphoric
Picric
Stearic
Sulfuric, 50%
Sulfuric, 80%
Tannic
Table 6-1. KPM(T) Monitors Front Panel Frame Chemical Compatibility
H C CHEMICAL H C CHEMICAL H C
Ammonium Hydroxide P P Alcohols E E
Calcium Hydroxide P
Potassium Hydroxide P
P
P
Aluminum Sulfate E
Ammonium Chloride* E
Copper Chloride* E
Iron Chloride* E
E
E
E
E
Nickel Chloride* E
Zinc Chloride* E
Barium Sulfide
E
E
E E
Aliphatic Hydrocarbons G
Aromatic Hydrocarbons G
Sodium Hydroxide P P Chlorinated Hydrocarbons P N
Ketones F P
Ethers F
Esters F
Gasoline E
Carbon Tetrachloride G
Aniline P
Benzene F
Formaldehyde, 37% G
G
F
P
P
E
G
P
P
G
Sodium Bicarbonate
Sodium Carbonate
Sodium Sulfide
Trisodium Phosphate
Calcium Chloride* E
Magnesium Chloride* E
Potassium Chloride* E
E
E
E
G
E
F
F
F
E
E
E
Phenol, 5% G
Mineral Oils E
Vegetable Oils E
Chlorobenzene G
F
E
E
F
Sodium Chloride* E E
' ( )
(
%
+ (
50 143448 (D)
KPM(T) Series Flat Panel Industrial Monitor Chapter 6 – Maintenance
*
The KPM(T) monitor front panel polyester overlay may be adversely affected by combinations of chemical environments, temperature, and stress. For this reason, material that may come in contact with the KPM(T) monitor should be carefully evaluated under end-use conditions for compatibility.
' '*
The KPM(T) monitor front panel overlay withstands more than 24 hours of exposure to the chemicals listed in Table 6-2 without visible change.
Ethanol
Cyclohexanol
Glycol
Isopropanol
Glycerine
Methanol
Acetone
Methyl ethyl ketone
Dioxan
Table 6-2. Front Panel Overlay Chemical Compatibility
Ammonia <2%
Caustic soda <2%
Alkalicarbonate
Bichromate
Potassium ferrocyanide/ferricyanide
Acetaldehyde
Aliphatic hydrocarbons
Petrol
Toluene
Xylene
Benzene
Formic acid <50%
Acetic acid <50%
Phosphoric acid <30%
Hydrochloric acid <10%
Nitric acid <10%
Sulphuric acid <10%
Cutting oil
Diesel oil
Linseed oil
Paraffin oil
Blown castor oil
Silicone oil
Turpentine substitute
Fluorochlorohydrocarbons
Perchloroethylene
1.1.1. Trichloroethane
Trichloroethylene
Ethylacetate
Diethyl ether
Sodium hypochlorite <20%
Hydrogen peroxide <25%
Potassium carbonate
Washing powders
Fabric conditioner
# " *
The following list contains known cleaning agents and household products that are compatible with the KPM(T) monitor front panel overlay. If you want to use a cleaning agent that is not listed below, contact the appropriate manufacturer for compatibility.
Jet Dry®
Fantastic®
Wisk®
Ariel®
Persil®
Windex®
Downey®
Vim®
Vortex®
Domestos®
Lenor®
Formula 409®
' '*
The following chemicals and household products are known to be non-compatible with the KPM(T) monitor front panel overlay:
Concentrated mineral acids Benzyl alcohol
Concentrated caustic solution Methylene chloride
High pressure steam over 212ºF(100ºC)
Tomato juice
Lemon juice
Tomato ketchup
51 143448 (D)
Appendix A – Technical Specifications
Hardware Specifications
Characteristic
Mechanical
Height
Width
Depth
Weight
Electrical
AC Power
DC Power
Front Panel
Agency
Approvals
Regulatory
Compliance
Table A - 1 lists the hardware specifications for the KPM(T) monitors.
Table A - 1. 5012KPM(T) & 5015KPM(T) Hardware Specifications
Specification
5012KPM(T)
Front Panel 12.22 in [310.388 mm]
5015KPM(T)
Front Panel 13.97 in [354.84 mm]
Front Panel 19 in [482.6 mm] overall 3.32 in [84.328 mm] behind front panel 2.32 in [59.93 mm] front panel protrusion 1.00 in [25.4 mm]
Front Panel 19 in [482.6 mm] overall 3.17 in [80.52 mm] behind front panel 2.17 [55.12 mm] front panel protrusion 1.00 in [25.4 mm]
18.85 lbs [8.55 kg] 16.15 lbs [7.33 kg]
100-240 V AC, 1A maximum, 50/60 Hz
18-32 V DC
NEMA 4/4X/12 and IP65
UL 508 (Listed) Industrial Control Equipment
UL 1604 (Listed) Electrical equipment for use in Class I and Class II, Division 2 and
Class III Hazardous (classified) locations cUL CSA C22.2, No. 142 (Listed) Process Control Equipment cUL CSA C22.2, No. 213 (Listed) Non-incendiary electrical equipment for use in Class I,
Division 2 Hazardous Locations
CE
EMI EN55022, Class A
IMMUNITY EN 61000-6-2
SAFETY EN 60950
HARMONICS EN 61000-3-2
FLICKER EN 61000-3-3
FCC
47 CFR, Part 15, Class A
Industry Canada
ICES-003, Class A
52
143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Appendix A – Technical Specifications
Environmental Specifications
Table A - 2 lists the environmental specifications for the KPM(T) monitors.
Table A - 2. 5012KPM(T) & 5015KPM(T) Environmental Specifications
Characteristic
Temperature
Specification
Humidity
Operating
Non-operating
Operating
Non-operating
0° to 50° C (32° to 122° F)
-20° to 60° C (-4° to 140° F)
20% to 80% RH, non-condensing
20% to 80% RH, non-condensing
Altitude*
Operating
Non-operating
Vibration 5-2000 Hz
Operating
Non-operating
Sea level to 10,000 feet (3,048 m)
Sea level to 40,000 feet (12,192 m)
0.006” (0.15 mm) peak to peak displacement
1.0g maximum acceleration
0.015” (0.38 mm) peak to peak displacement
2.5g maximum acceleration
Shock
Operating 15g peak acceleration, 11 msec duration, ½ sine wave
Non-operating 30g peak acceleration, 11 msec duration, ½ sine wave
* Consistent with internal component specifications
53 143448 (D)
Appendix B – Pinouts
This appendix provides the pinouts for the VGA input, RS232 output, and USB output connectors.
NC indicates No Connection.
VGA Input Connector
The following table lists the signal definitions for the VGA DB-15 connector.
Table B - 1. VGA Input Connector Pinout
D-Shell (Female)
1
2
3
6
7
4
5
8
9
10
11
12
13
14
15
Signal Name
Red
Green
Blue
GND-Digital
GND-Red return
GND-Green return
GND-Blue return
DDC 5V
GND-Digital
DDC SDA
Hsync
Vsync
DDC SCL
Serial Interface
RS-232C
Data Transmission Speed: 9600 bps
Data Length: 8 bits
Stop Bit: 1 bit
Parity: None
54
143448 (D)
KPM(T) Series Flat Panel Industrial Monitor
Appendix B - Pinouts
. ! ' , /&0&*! !
The following table lists the connections for the D-sub 9-pin female RS-232 Output
Connector. (Set screw: Inch type [4-40 UNC])
Table B - 2. Serial Signal Input Connector Pinout
Number Signal Name Function
1 NC No Connection
4
5
2
3
SD
RD
DTR*
GND
Send Data
Receive Data
Terminal Ready
Signal Ground
6 NC No Connection
7
8
RTS*
NC
Request Send
No Connection
9 NC No Connection
* RTS and DTR are connected together inside the KPM(T) monitors.
Note
The KMP(T) monitor has been configured to use a straight through cable to connect the monitor to the PC.
USB Input/Output Connector
The following table lists the descriptions of the 4-pin USB input/output connector.
Table B - 3. Touch Screen USB Output Pinout
Pin
1
2
3
4
*
Description
5VFUSE
USB–
USB+
GND
* +5V is not provided on the rear host USB connector.
Note
The front panel USB connector serves only as a “pass-through” connector and connects directly to the rear panel USB connector.
55
143448 (D)
INDEX
Access keyboard port, 3
Adjustment mode and image, 30
Back panel, 4
Cable Connections, 26
Chemicals compatible with frame, 48 compatible with overlay, 49 not compatible with overlay, 49
Class I locations, 24
Class II locations, 24
Compatibility issues
XVME, 15
Connector touch screen RS-232 output, 53 touch screen USB output, 53
VGA input, 52
Control drawing hazardous locations, 28
Definitions class and division, 24
Display, 3
Division 1 locations, 24
Division 2 locations, 25
Driver touch scre ens, 35
Electrical noise, 13
Enclosures, 25
Features standard, 1
Front panel controls, 2
Functions
OSD, 31
Fuse replacement, 46
Graphic modes, 34
Groups, 25
Heat excessive, 13
Installation hazardous locations, 22 overview, 8
Keyboard port, 3
Keypad inserts custom, 16
Keypad Inserts, 17, 19
Keypad keycodes
56 default, 43
Keypad utility
Batch Mode, 42
Download menu, 41
Exit menu, 38
Files menu, 38 loading, 36
Macros Keypad Type Menu, 38
Main menu, 37
Upload menu, 41 using, 36
Keypad Utility Program, 36
LEDs, 3
Line voltage variation, 14
Logo custom, 16
Maintenance general, 46
Monitor, 3
On Screen Display switch, 30
PKIM utility
Utilities menu, 42
Power system, 12
Power management, 12
Power Switch, 26
Preparing the system, 8, 13
Preventive maintenance general, 46
Product Repair Program, 47
Returning the unit, 47
Specifications environmental, 51 hardware, 50
System maintenance, 29 operation, 29
System cutout dimensions, 9
Touch screens calibrating, 35 driver, 35 using, 15 using a mouse, 35 using a pointing device, 35
Troubleshooting, 46 using the Keypad Utility, 36
Variation line voltage, 14
XVME, 15
143448 (D)
Xycom Automation, LLC
734-429-4971
Fax: 734-429-1010
http://www.profaceamerica.com
Canada Sales: 905-607-3400
Northern Europe Sales: +44-1604-790-767
Southern Europe Sales: +39-011-770-53-11
143448 (D)
Download
Advertisement
Key features
Rugged design
Resistive membrane touch screen
Integral pointing device
Integral full alphanumeric keypad
UL Listed for Class I & II Division 2 Hazardous Locations
100-240V AC or 24V DC input power
NEMA 4/4X/12 front panel
Shallow mounting depth
40 relegendable function keys
Reprogrammable keypad keys
Frequently asked questions
The monitors have an auto-ranging AC input of 100-240 VAC, 50-60 Hz, or an optional 18-30 VDC input.
The monitors are specified for a wide range of temperatures, humidity, and shock levels. Refer to Appendix A for detailed environmental specifications.
The touch screen driver can be installed from the provided CD-ROM, floppy disk, or network.