- Home
- Home security & automation
- Carbon monoxide (CO) detectors
- Det-Tronics
- R8471H
- Instructions manual
advertisement
▼
Scroll to page 2
of
26
Instructions 95-8475 Combustible Gas Controller R8471H 1.1 5/07 95-8475 Table of Contents SECTION I - INSTALLATION AND STARTUP INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Sensor Location . . . . . . . . . . . . . . . . . . . . . . . . 1 General Wiring Requirements . . . . . . . . . . . . . . 2 Controller Wiring . . . . . . . . . . . . . . . . . . . . . . . . 2 Typical Application . . . . . . . . . . . . . . . . . . . . . . 5 Controller Programming . . . . . . . . . . . . . . . . . . 5 List of Illustrations Figure 1 Dimensions of Q4004 Mounting Rack . 3 Figure 2 Clip Positioning for Q4004 Mounting Racks . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Figure 3 Terminal Configuration for R8471H Combustible Gas Controller . . . . . . . . . 4 Figure 4 A Typical System with Relay Outputs and Non-Isolated Current Output . . . . . . . . 4 Figure 5 A Typical System with Relay Outputs and Isolated Current Output . . . . . . . . . . . . 5 Figure 6 CALIBRATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Calibration Procedure . . . . . . . . . . . . . . . . . . . . 9 Calibrating PointWatch . . . . . . . . . . . . . . . . . . 10 Calibrating the Controller . . . . . . . . . . . . . . . . . 11 Current Output Calibration . . . . . . . . . . . . . . . 11 Open Collector Output with Inductive Load and Transient Suppression Device . . . . . . . . . . . . . . . . . . . . . . . . . 5 Figure 7 R8471H Controller Wired to a PointWatch Detector . . . . . . . . . . . . . . 6 Figure 8 SECTION II - DESCRIPTION AND OPERATING CHARACTERISTICS FACEPLATE DESCRIPTION . . . . . . . . . . . . . . . . . 12 Programming Jumper Plugs and Switches . . . . . . . . . . . . . . . . . . . . . . . . 7 Figure 9 Controller Front Panel Figure 10 R8471H Controller Flow Chart . . . . . . 14 OUTPUTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Figure 11 Controller Dimensions in Inches (Centimeters) . . . . . . . . . . . . . . . . . . . 15 INSTALLATION CHECKLIST . . . . . . . . . . . . . . . . . 7 STARTUP PROCEDURE . . . . . . . . . . . . . . . . . . . . 8 SETPOINT ADJUSTMENT . . . . . . . . . . . . . . . . . . . 8 Setpoint Display Mode . . . . . . . . . . . . . . . . . . . 8 Setpoint Adjustment Procedure . . . . . . . . . . . . . 9 AUTOMATIC DIAGNOSTICS AND FAULT IDENTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . 13 Fault Record Sheet . . . . . . . . . . . . 12 . . . . . . . . . . . . . . 22 Recommended Test Form . . . . . . . . . 23 OPERATING MODES . . . . . . . . . . . . . . . . . . . . . . 13 Normal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Other Operating Modes . . . . . . . . . . . . . . . . . . 15 Table 1 Selectable Relay Options . . . . . . . . . . . 6 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 15 Table 2 System Status Codes . . . . . . . . . . . . . 10 Table 3 Troubleshooting Guide . . . . . . . . . . . . 16 SECTION III - SYSTEM MAINTENANCE TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . 15 ROUTINE MAINTENANCE . . . . . . . . . . . . . . . . . . 17 Manual Check of Output Devices . . . . . . . . . . 17 Checkout in Normal Mode . . . . . . . . . . . . . . . . 17 PointWatch Maintenance . . . . . . . . . . . . . . . . 17 DEVICE REPAIR AND RETURN . . . . . . . . . . . . . 17 ORDERING INFORMATION . . . . . . . . . . . . . . . . . 18 Mounting Racks . . . . . . . . . . . . . . . . . . . . . . . . 19 Gas Detector . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Calibration Kits . . . . . . . . . . . . . . . . . . . . . . . . 19 APPENDIX A - FACTORY MUTUAL RESEARCH CORPORATION (FMRC) APPROVAL DESCRIPTION APPENDIX B - CANADIAN STANDARDS ASSOCIATION (CSA) APPROVAL DESCRIPTION List of Tables INSTRUCTIONS Combustible Gas Controller R8471H IMPORTANT Be sure to read and understand the entire instruction manual before installing, operating or servicing the gas detection equipment. WARNING Do not open the PointWatch junction box with power applied unless it is verified that no combustible gases or vapors are present. A portable gas detection instrument should be used to ensure that the area is clear of any combustible gases. Calibration or maintenance should not be performed if there is any indication of the presence of combustible gas at the sensor. CAUTION The wiring instructions in this manual will provide safe and proper functioning of the device under normal conditions. However, local variations in wiring codes and regulations exist, and total compliance with these ordinances cannot be guaranteed. Be certain that all wiring complies with the IEC/NEC as well as all local ordinances. If in doubt, consult the local authority having jurisdiction before wiring the system. Section I Installation and Startup INSTALLATION SENSOR LOCATION Proper sensor positioning is essential to ensure maximum gas detection capability. Optimum sensor placement and density varies depending upon the conditions at the job site. The system designer and installer must examine the specific area to be protected and identify the most likely leak sources and gas accumulation areas to determine the best sensor locations. The following factors should be considered for every installation: 1.1 ©Detector Electronics Corporation 2007 1. What kind of gas is to be detected? If it is lighter than air (Acetylene, Hydrogen, Methane, etc.), place the sensor above the potential gas leak. Place it close to the floor for gases that are heavier than air (Benzene, Butane, Butylene, Propane, Hexane, Pentane, etc.) or for vapors resulting from flammable liquid spills. Careful analysis of both the vapor hazard and the application is required — first to determine the feasibility of detection and then to ensure that proper sensor locations are selected. 2. How rapidly will the gas diffuse into the air? Locate the sensor as close as practical to the anticipated source of a gas leak. 3. Ventilation characteristics of the immediate area must also be considered. Air movement can cause the gas to accumulate more heavily in one area than another. Smoke generator tests are useful in identifying typical air current patterns as well as “dead” air spots for both indoor and outdoor applications. The sensors should be placed where the most concentrated accumulation of gas is anticipated. 5/07 95-8475 4. The sensor should be located in an area where it is safe from potential sources of contamination. within the conduit system. Therefore, it is important to take proper precautions during installation to ensure that accumulated moisture will not cause damage to the components of the system. 5. The sensor should be pointed down to prevent the buildup of contaminants on the gas inlet. Conduit raceways should be inclined so that water will flow to low points for drainage and will not collect on conduit seals or inside enclosures. If this is not possible, install conduit drains above the seals to prevent the collection of water, or install a drain loop below the detector with a conduit drain at the lowest point of the loop. 6. The sensor must be accessible for testing and calibration. 7. Exposure to excessive heat or vibration can result in pre-mature failure of electronic devices and should be avoided if possible. Shield the sensor from intense sunlight to reduce solar heating. Conduit drains should be installed at water collection points to automatically drain accumulated moisture. Conduit breathers should be installed at upper locations to provide ventilation and allow water vapor to escape. At least one breather should be used with each drain. IMPORTANT All diffusion-based gas sensors must contact the target gas in order to provide an accurate gas measurement. This must always be remembered when selecting locations for gas sensor installation. When using steel wire armored or mineral-insulated copper-sheathed cable, select an approved gland with a watertight compression stage and an overall gland shroud for outdoor applications. A sealing washer must be fitted between the gland and the conduit/cable entry to ensure IP66 rating. For additional information on determining quantity and placement for sensors in a specific application, refer to Instrument Society of America (ISA) Transaction Volume 20, Number 2, titled “The Use of Combustible Detectors in Protecting Facilities from Flammable Hazards.” CONTROLLER WIRING GENERAL WIRING REQUIREMENTS Field Wiring Connector Wire Size and Type The controller is furnished with a field wiring connector backplate that incorporates pressure type screw terminals for connecting the external wiring and a circuit board edge connector for attaching to the controller. The use of a mounting rack is recommended for mounting the controller. The backplate is attached to the back of the rack to allow easy removal of the controller without disturbing the wiring. See Figures 1 and 2. In applications where the wiring cable is installed in conduit, the conduit must not be used for wiring to other electrical equipment. Three wire shielded cable is highly recommended for connecting the PointWatch to the controller. A foil shield is recommended. The maximum wiring distance between the PointWatch and controller is limited by the gauge of the wire being used. Refer to the PointWatch manual for specific information on maximum loop resistance. The controller is designed for installation in a nonhazardous area. Figure 3 shows the terminal configuration for the R8471H Controller. CONDUIT SEALS, DRAINS, AND BREATHERS Terminals 1 and 2 – 4 to 20 ma dc output. When installing the PointWatch in hazardous areas where explosion-proof equipment certification is required, explosion-proof conduit seals should be installed within 18 inches (46 cm) of the junction box to prevent the passage of vapors or flames through the conduit. Seals are recommended even if they are not required by local wiring codes. Non-Isolated Current Output If the 4 to 20 ma current loop is to be non-isolated, wire the system as shown in Figure 4. Note that terminal 2 is not used with a non-isolated current loop. Program the unit for a nonisolated current loop as described in the “Controller Conduit systems are never completely air-tight. As a result, significant amounts of condensation can form 1.1 2 95-8475 CONTROLLER POSITIONS FOR FLAME GAS 8 6 4 3 2 1 16 12 8 6 4 2 16 12 8 6 4 2 HT: DIM. (A) INCH MM DIM. (B) INCH MM DIM. (C) INCH MM DIM. (D) INCH MM DIM. (E) INCH MM WEIGHT LB KG 4U 4U 4U 4U 4U 4U 3U 3U 3U 3U 3U 3U 19.00 15.06 11.13 9.16 7.19 5.22 19.00 15.06 11.13 9.16 7.19 5.22 18.30 14.36 10.43 8.46 6.49 4.52 18.30 14.36 10.43 8.46 6.49 4.52 17.36 13.42 9.49 7.52 5.55 3.58 17.36 13.42 9.49 7.52 5.55 3.58 4.00 101.6 6.97 177.1 2.25 57.15 5.22 132.6 9.3 7.6 5.9 5.1 4.2 3.1 9.3 7.6 5.9 5.1 4.2 3.1 482.6 382.6 282.6 232.7 182.7 132.6 482.6 382.6 282.6 232.7 182.7 132.6 464.8 364.7 264.9 214.9 164.9 114.8 464.8 364.7 264.9 214.9 164.9 114.8 440.9 340.9 241.1 191.0 141.0 90.9 440.9 340.9 241.1 191.0 141.0 90.9 4.2 3.5 2.7 2.3 1.9 1.4 4.2 3.5 2.7 2.3 1.9 1.4 (A) (B) (C) 1.48 (37.59) (D) (E) ALL CONTROLLER CAGES REQUIRE A MINIMUM OF 10.12 INCHES (257.1 MM) DEPTH CLEARANCE B1475 Figure 1—Dimensions of the Q4004 Mounting Rack THE Q4004 CONTROLLER CAGE HAS BEEN MODIFIED TO ACCOMMODATE EITHER FIRE OR GAS CONTROLLERS OR ANY COMBINATION OF THE TWO. BY FOLLOWING THE INSTRUCTIONS BELOW, THE CAGE CAN BE SET UP TO ANY CONFIGURATION. 1 SET 2 GAP 3 2 1 FIRE CONTROLLERS ARE APPROX. TWO INCHES WIDE AND REQUIRE TWO GUIDE RAILS FOR INSERTION. PLACE THE RETAINING CLIP BETWEEN RAILS TO FORM SETS, LEAVE A GAP BETWEEN SETS. 2 TO INSERT A BLANK PANEL, PLACE A CLIP IN THE TOP BRACKET IN LINE WITH THE CLIP IN THE BOTTOM BRACKET. 3 GAS CONTROLLERS ARE APPROX. ONE INCH WIDE AND REQUIRE ONE RAIL FOR INSERTION. PLACE CLIPS IN LINE WITH GUIDE RAILS, CAGES WILL ACCEPT AS MANY GAS CONTROLLERS AS RAILS PROVIDED. SET A1476 Figure 2—Clip Positioning for Q4004 Mounting Racks 1.1 3 95-8475 – 1 + 2 an isolated current loop as described in the “Controller Programming” section of this manual. Note that this wiring scheme requires an external power source for the isolated current output. CURRENT OUTPUT CHASSIS GROUND 3 18 TO 32 VDC POWER + 4 – 5 POWER + 6 SIGNAL – 7 SENSOR EXTERNAL RESET 8 HIGH ALARM 9 HIGH ALARM / OC 10 AUX. ALARM 11 AUX. ALARM / OC 12 LOW ALARM 13 LOW ALARM / OC 14 FAULT 15 FAULT / OC 16 Terminal 3 – Chassis ground. Connect the cable shield to this terminal. NOTE If local wiring codes permit and if a ground fault monitoring system is not being used, the minus side of the dc power source can be connected to chassis (earth) ground. Alternatively, a 0.47 microfarad, 100 volt capacitor can be installed (terminal 5 to ground) for best immunity against electromagnetic interference. Terminal 4 – Connect to the positive (+) side of the 18 to 32 vdc power source. Terminal 5 – Connect to the negative (-) side of the dc power source. Terminal 6 – Make no connections to this terminal. Terminal 7 – 4 to 20 ma dc signal input from PointWatch. OC = OPEN COLLECTOR OUTPUT B1390 (BASE MODEL ONLY) Figure 3—Terminal Configuration for R8471H Combustible Gas Controller Programming” section of this manual. Isolated Current Output - If an isolated current loop is desired, wire the system as shown in Figure 5 and program the unit for R8471 CONTROLLER ISOLATED OUTPUT CURRENT LOOP 4-20 MA – 1 + 2 CHASSIS GROUND * DET-TRONICS JUNCTION BOX 3 18 TO 32VDC + + 4 SPARE 24 POWER GROUND POWER SENSOR – 5 + 6 – SIGNAL – VDC * 7 EXTERNAL RESET 8 HIGH ALARM 9 HIGH ALARM / OC 10 AUX. ALARM 11 AUX. ALARM / OC 12 LOW ALARM 13 LOW ALARM / OC 14 FAULT 15 FAULT / OC 16 CHASSIS CAL CAL 4 - 20 4 - 20 RET RET +24 +24 GREEN YELLOW WHITE BLACK RED POINTWATCH DETECTOR B1954 RESET HIGH ALARM AUXILIARY ALARM LOW ALARM FAULT *NO CONNECTION Figure 4—A Typical System with Relay Outputs and Non-Isolated Current Output 1.1 4 95-8475 R8471 CONTROLLER ISOLATED OUTPUT CURRENT LOOP 4-20 MA – 1 – + 2 + CHASSIS GROUND 24 VDC DET-TRONICS JUNCTION BOX 3 + 18 TO 32VDC + 4 POWER GROUND POWER SENSOR – 5 + 6 – SIGNAL – SPARE 24 VDC * 7 CHASSIS CAL CAL 4 - 20 4 - 20 RET RET +24 +24 8 EXTERNAL RESET 9 HIGH ALARM / OC 10 AUX. ALARM 11 AUX. ALARM / OC 12 LOW ALARM 13 LOW ALARM / OC 14 FAULT 15 FAULT / OC 16 POINTWATCH DETECTOR B1955 RESET HIGH ALARM GREEN YELLOW WHITE BLACK RED HIGH ALARM AUXILIARY ALARM LOW ALARM FAULT *NO CONNECTION Figure 5—A Typical System with Relay Outputs and Isolated Current Output Terminal 8 – damage. Figure 6 illustrates an inductive load with a diode used for transient suppression. A normally open momentary closure switch can be connected between this terminal and the negative (-) side of the power source for remote reset. Terminals 9 and 10 – TYPICAL APPLICATION Refer to Figure 7 for an illustration of an R8471H Controller wired to a PointWatch IR gas detector. High Alarm Output. Terminals 11 and 12 – Auxiliary Alarm Output. CONTROLLER PROGRAMMING Terminals 13 and 14 – Low Alarm Output. Refer to Figure 8 to determine the location of programming jumpers and switches. Table 1 shows the selectable options for each relay. Terminals 15 and 16 – Fault Output. NOTE All controller jumper plugs must be installed. The controller outputs will not function properly if a jumper plug is missing. Premium Controller – The relay outputs (terminals 9 to 16) are programmed for the desired operation using the procedure described in the “Controller Programming” section of this manual. Base Controller – Connections to open collector transistor outputs are made at terminals 10, 12, 14, and 16. Terminals 9, 11, 13, and 15 are not used. See Figure 6 for an example of a typical connection to an open collector transistor output. +32 VDC MAXIMUM 1N4004 TYPICAL OPEN COLLECTOR OUTPUT NOTE External equipment that can generate transients when switching (such as relays) must have a transient suppression device (diode) properly connected across the coil at the time of installation. This will safeguard the output transistors of the controller against possible 1.1 100K C1289 Figure 6—Open Collector Output with Inductive Load and Transient Suppression Device 5 95-8475 1 2 3 + 4 – 24 VDC POWER SUPPLY 5 MAGNETIC REED SWITCH FOR POINTWATCH CALIBRATION COMMAND 6 7 8 9 10 11 GREEN CAL CAL YELLOW SIG SIG RET RET BLACK + 24 + 24 RED 13 14 15 WHITE POINTWATCH SP. 12 16 17 B1956 NOTES: 1. REED SWITCH, LED, AND ALL INTERNAL CONNECTIONS ARE PROVIDED ON THE POINTWATCH JUNCTION BOX BASE CONNECTOR BOARD. 2. CONDUCT POINTWATCH CALIBRATION PROCEDURE BEFORE R8471 CONTROLLER CALIBRATION. 3. POINTWATCH CALIBRATION INITIATION WILL CAUSE R8471 FAULT CONDITION UNTIL POINTWATCH CALIBRATION PROCEDURE IS COMPLETED. 4. CONDUCT R8471 CALIBRATION PROCEDURE AFTER POINTWATCH CALIBRATION IS COMPLETED. 5. CABLE SHIELD WIRE IS TO BE CUT BACK AND TAPED OFF WITHIN POINTWATCH JUNCTION BOX. 6. CABLE SHIELD WIRE IS TO BE CONNECTED TO TERMINAL NO. 3 AT R8471 BACKPLATE, WHICH IS THE CONTROLLER EARTH GROUND CONNECTION. Figure 7—R8471H Controller Wired to a PointWatch Detector pins. For normally open operation, place the plug on the NO and center pins. For normally closed operation, place it on the NC and center pins. The pin groups are identified as follows: Normally Open/Closed Relays The four relays are individually programmed for either normally open or normally closed contacts. This is accomplished by placing a jumper plug on the appropriate pair of pins. Each relay has a set of three J2 – High Alarm J3 – Auxiliary Alarm J4 – Low Alarm J5 – Fault Table 1—Selectable Relay Options Relay Selectable Normally Open/Closed Selectable* Selectable* Normally Latch/ Energized/ Non-Latch De-Energized Low Y Y Y High Y Y N1 Auxiliary Y Y Y Fault Y N2 N3 Y = Yes Latching/Non-Latching Relays The Low and Auxiliary alarm relays are programmable as a group for latching or non-latching operation. The High alarm relay is always latching. Latching relay operation is programmed using rocker switch 1 at SW1 (SW1-1). For latching operation, place the switch in the closed position. For non-latching operation, place it in the open position. This switch is set at the factory for non-latching relay operation. 1Latching only N = No 2Normally Energized The controller is programmed at the factory for normally open relay contacts. 3No latching option *Relays selectable as a group. 1.1 6 95-8475 SW1-1 CLOSED = LATCHING OPEN = NON-LATCHING SW1-2 CLOSED = NORMALLY ENERGIZED OPEN = NORMALLY DE-ENERGIZED J1 INT = NON-ISOLATED EXT = ISOLATED HIGH ALARM AUXILIARY ALARM NORMALLY OPEN/CLOSED RELAY CONTACTS LOW ALARM FAULT A1392 Figure 8—Programming Jumper Plugs and Switches of system installation are complete and have been performed correctly. Normally Energized/De-Energized Relays The three alarm relays are programmable as a group for normally energized (fail-safe) or normally deenergized operation. This is accomplished by setting rocker switch 2 at SW1 (SW1-2). For normally energized alarm relays, place the switch in the closed position. For normally de-energized operation, place it in the open position. This switch is set at the factory for normally de-energized operation. 1. PointWatch detectors are installed following the instructions in the PointWatch manual. 2. Junction boxes are securely mounted and covers are tightly installed. 3. All cable shields are properly grounded. 4. Conduit seals have been installed at all junction box entries (if conduit is being used). The Fault relay is always normally energized, regardless of the setting of SW1-2. 5. PointWatch to controller wiring is correct. 4 to 20 ma Output 6. Power wiring to the controller is installed and power source is operational. Isolated or non-isolated operation of the 4 to 20 ma output is selected using a jumper plug at J1. For nonisolated operation, as illustrated in Figure 4, place the jumper plug in the INT (internal power source) position. Place the plug in the EXT position for an isolated circuit, as illustrated in Figure 5. The jumper is set at the factory for non-isolated operation. 7. External loads are properly connected to the controller. 8. Controller is programmed as desired. Record this information for future reference. INSTALLATION CHECKLIST 9. Controller is properly installed in the mounting enclosure. The following checklist is provided as a means of double checking the system to be sure that all phases 10. Proper ventilation is provided to prevent overheating of the controller. 1.1 7 95-8475 Proceed to System Startup, Setpoint Adjustment, and Calibration. The programmed calibration gas concentration in % LFL is also displayed and adjusted with the alarm setpoints. STARTUP PROCEDURE The adjustment range for the alarm setpoints and calibration gas concentration is as follows: 1. Output loads that are normally actuated by the gas detection system should be secured (remove power from all output devices) to prevent undesired activation. Low alarm High alarm Auxiliary alarm Calibration gas 2. Check all external wiring for proper connection. 5 to 50% LFL 10 to 60% LFL 3 to 90% LFL 30 to 90% LFL WARNING Calibration gas concentration must be set at 50% LFL when a PointWatch detector is used with the R8471H Controller. Other calibration gas settings may cause unreliable readings, which could result in a fire or explosion. 3. Before installing the controller in the mounting rack, inspect it to verify that it has not been physically damaged in shipment. Check the jumper plugs and rocker switches on the controller for proper programming, then slide the controller fully into the mounting enclosure. 4. Apply power to the system. The factory settings are: NOTE The controller has a power-up delay before beginning normal operation after power is applied to the system. During this time the outputs are inhibited, the FAULT LED is illuminated, and the current output indicates a fault condition. This delay allows time for the PointWatch output to stabilize before beginning normal operation. Low alarm: High alarm: Auxiliary alarm: Calibration gas: 20% LFL 50% LFL 50% LFL 50% LFL To check the present levels, use the “Setpoint Display Mode” described below. To change the values, use the “Setpoint Adjustment Procedure”. SETPOINT DISPLAY MODE 5. Put the controller in the Setpoint Display mode to determine the present alarm setpoints and calibration gas concentration. If changes are required, perform the Setpoint Adjustment procedure. 1. To enter the Setpoint Display mode, press and hold the Reset button until the Low LED begins to blink (approximately one second). Release the Reset button. The low alarm setpoint will be shown for two seconds on the digital display. 6. Perform the calibration procedure. This involves calibrating the PointWatch using the procedure described in the PointWatch manual, then calibrating the controller using the procedure described in the “Calibration” section of this manual. NOTE The Reset button should be released as soon as the controller has entered the Setpoint Display mode (after one second). If the button is still depressed at the end of the Setpoint Display mode (9 seconds), the controller will automatically enter the Calibrate mode. If the operator is not prepared to perform a calibration, a calibration fault will occur. Recycle power to the controller to exit the calibrate mode without affecting the calibration settings. 7. Check the 4 to 20 ma current loop for proper calibration and adjust as required. 8. After calibration is completed, restore the system output loads to ready condition. 2. At the end of the two second interval, the Low LED goes out, the High LED begins to blink, and the digital display shows the high alarm setpoint. SETPOINT ADJUSTMENT The R8471H Controller has independent Low, High, and Auxiliary alarm setpoints, with corresponding outputs. 1.1 3. Two seconds later the High LED goes out and the Auxiliary LED blinks. The digital display now shows the programmed auxiliary alarm setpoint. 8 95-8475 NOTE The alarm setpoints, calibration gas concentration, and calibration data are stored in non-volatile memory and are retained in the event of a power loss. However, if power is interrupted while performing the Setpoint Adjustment or Calibration procedure, the entire procedure must be repeated when power is restored. 4. Two seconds later the Auxiliary LED goes out and the CAL LED blinks. The digital display now shows the calibration gas concentration. This value should always be set at 50% LFL when a PointWatch detector is used with the R8471H. 5. After displaying the calibration gas concentration for two seconds, the controller automatically leaves the Setpoint Display mode and returns to the Normal operating mode. CALIBRATION 6. If adjustments to the setpoints are required, perform the Setpoint Adjustment procedure. When the setpoint levels are acceptable, record this information for future reference and perform the Calibration procedure. The PointWatch IR gas detector is calibrated at the factory for detection of methane gas. Recalibrating the device for detection of methane before placing it into operation is recommended, but not required. If the application involves detection of other gases and requires changing the PointWatch gas selection rotary switch, the PointWatch must be recalibrated to ensure accurate measurement. SETPOINT ADJUSTMENT PROCEDURE 1. Determine the required alarm setpoint levels. 2. Press and hold the Set button for one second, then release. The digital display indicates the present low alarm setpoint and the Low LED blinks. Press the Reset button to increase the reading or the Set button to decrease the reading. (Pushing and holding the button will cause the reading to change rapidly.) Infrared gas detectors generally do not require the same frequency of routine calibration as catalytic sensors, however, unusual gas types and applications may require special calibration considerations. Refer to the PointWatch instruction manual for additional information. CALIBRATION PROCEDURE 3. When no changes to the setpoint level have been made for 5 seconds, the Low LED goes out, the High LED blinks, and the digital display shows the high alarm setpoint. Press the appropriate button (detailed in step 2 above) to obtain the desired reading on the digital display. Calibration of the R8471H/PointWatch combustible gas detection system is a two step process — calibrate PointWatch, then calibrate the controller. NOTE The PointWatch unit must always be calibrated first. 4. When no changes to the setpoint level have been made for 5 seconds, the High LED goes out, the Auxiliary LED blinks, and the digital display shows the auxiliary alarm setpoint. Press the appropriate button to obtain the desired reading on the digital display. PointWatch Calibration. PointWatch calibration ensures a calibrated linear 4 to 20 ma input to the controller. PointWatch calibration is totally independent of the R8471H Controller calibration. The PointWatch calibration procedure can be performed by one person, with all adjustments made at the PointWatch. 5. When no changes have been made for 5 seconds, the Auxiliary LED goes out, the CAL LED blinks, and the digital display indicates the calibration gas concentration. This value should always be set at 50% LFL when a PointWatch detector is used with the R8471H. NOTE During the time that the PointWatch is in the calibrate mode, the R8471H indicates the status of the PointWatch calibration on its digital display (see Table 2). The controller cannot, however, put the PointWatch unit into the calibrate mode or control its calibration in any way. 6. When no changes have been made for 5 seconds, the controller automatically returns to the Normal operating mode. 7. Record the new values for future reference. Controller Calibration. This procedure calibrates the controller’s displays and 4 to 20 ma output. Controller 1.1 9 95-8475 Table 2—System Status Codes STATUS CONDITION F9X F91 F92 F93 F94 F95 F96 F97 F98 Initialization failure. (Subcodes are as follows.) EPROM sumcheck failure. Sensor failure during startup - current too high or too low. Watchdog timer failure. RAM failure. Internal 5 volt power supply failure during startup. External 24 volt power supply failure during startup. Controller type invalid. Error in data from RAM. Watch dog timer reset the controller. F70 External reset button has been activated for 15 seconds or longer. Self clearing when button is released. F60 External 24 vdc power input is not in the 18 to 32 vdc range. F50 Internal 5 volt power supply is not in the 4.75 to 5.25 volt range. F40 F41 F42 Sensor fault (after startup). Input is above 35 ma or below 0.5 ma. PointWatch unit has dirty optics. PointWatch calibration line fault. F30 Negative zero drift. Sensor input is -9% full scale or lower. F2X F20 F24 Calibration error. (Subcodes are as follows.) General calibration fault, or calibration aborted due to a higher priority fault. PointWatch calibration aborted. Time ran out while waiting for calibration gas to be applied to the sensor. Sensor input is too low. The sensor cannot generate enough offset to get an accurate calibration. Replace sensor. Possible wiring fault. Sensor is too sensitive for the controller to read 100% full scale. Replace sensor. Possible wiring fault. Zero gas level too high, or sensor zero input over limit. F10 Sensor sensitivity problem. CAL PointWatch in calibrate mode, doing Zero calibration. SPn PointWatch in calibrate mode, doing Span calibration. CC PointWatch in calibrate mode, successful calibration completed. F21 F22 F23 calibration typically requires two people, one at the controller and another at the PointWatch. All adjustments are made automatically by the controller. CALIBRATING POINTWATCH To calibrate the PointWatch unit, follow the calibration procedure described in the PointWatch instruction manual. The controller calibration procedure involves applying a zero and span gas to the PointWatch, while the controller calibrates its own display and current output to the linear 4 to 20 ma current input provided by the PointWatch. This procedure does not calibrate the PointWatch. 1.1 NOTE For best calibration results, allow the PointWatch detector to operate for at least an hour to ensure a stable output before performing calibration. 10 95-8475 6. When the microprocessor has completed the Span adjustments (30 seconds minimum), the digital display stops flashing. CALIBRATING THE CONTROLLER The R8471H Controller can be calibrated using either of two methods: 7. Remove the calibration gas. When the gas level falls below the lowest alarm setpoint, the controller automatically exits the Calibrate mode. Factory Default Calibration After the PointWatch has been calibrated, the operator can set the controller for factory programmed calibration default values. The procedure is performed after the initial PointWatch calibration and does not need to be repeated with each subsequent PointWatch recalibration. If the operator fails to complete the calibration procedure or if a successful calibration cannot be completed, a calibration fault (“F2X” status) will be generated and the controller will automatically revert back to the former calibration settings (after 10 minutes). The controller is set for the factory default calibration values as follows: CURRENT OUTPUT CALIBRATION The controller’s 4 to 20 milliampere output is calibrated at the factory, however, it can be recalibrated by performing the following procedure. 1. Press and hold the Reset button for approximately 9 seconds until the digital display begins flashing and the CAL LED is illuminated. Release the Reset button. 1. A dc current meter capable of measuring 4 to 20 milliamperes must be connected to the current loop output. This can be accomplished in one of the following ways: 2. Press the Set button. The FAULT LED comes on. 3. Press the Reset button. The controller returns to the normal operating mode (after a short time delay). — by disconnecting all loads and connecting a dc ammeter between the two 4 to 20 milliampere terminals, 4. The controller is now set for the factory default values. — by connecting a dc ammeter in series with the load, Field Calibration Procedure — by connecting a digital dc voltmeter across a known load resistance and calculating the current flow using the formula: 1. Be certain that the controller is programmed for a 50% LFL calibration gas mixture. (See “Setpoint Adjustment” section.) I = voltage/load resistance. 2. Be sure that only clean air (0% LFL) is present at the PointWatch. (The microprocessor begins taking Zero readings immediately upon entering the Calibrate mode.) If the possibility of background gases exists, the PointWatch can be purged with clean air to ensure accurate calibration. 2. Press and hold the Set button, then immediately press the Reset button. (The Reset button must be pressed within one second of pressing the Set button.) Release both buttons. The Low LED should flash slowly. The flashing Low LED indicates that the system is now generating a 4 ma output. 3. Place the controller in the calibrate mode by depressing and holding the Reset button until the CAL LED is illuminated and the digital display starts to flash (approximately 9 seconds). 3. Press the Reset (increase) or Set (decrease) button to obtain a 4 ma reading on the meter. (Pressing and holding the button will cause the output to change rapidly.) 4. When the Zero calculations are complete (30 seconds minimum), the digital display stops flashing. 4. When no adjustments have been made for 7 seconds, the controller automatically switches to a 20 ma output. This is indicated by a flashing High LED. Press the appropriate button to obtain a 20 ma reading. 5. Apply 50% LFL calibration gas to the PointWatch. The digital display starts to flash. 1.1 11 95-8475 5. When no adjustments have been made for 7 seconds, the controller generates the current output level for the calibrate mode. This is indicated by a flashing CAL LED. Press the appropriate button to obtain the desired current output level for the calibrate mode. DIGITAL DISPLAY ➀ ➂ 6. When no changes have been made for 7 seconds, the controller automatically returns to the Normal operating mode and saves the data in non-volatile memory. ➃ AUXILIARY LED ⑤ 7. Remove the meter from the system output. ➇ ➈ Section II Description and Operating Characteristics HIGH LED ➁ BAR GRAPH LOW LED RESET PUSHBUTTON SET PUSHBUTTON CAL LED ➅ FAULT LED ⑦ FACEPLATE DESCRIPTION The faceplate of the controller provides LEDs for identifying status conditions, a digital display and bar graph display for indicating the sensor input, and pushbuttons for programming, calibrating and resetting the system. See Figure 9 for the location of indicators and pushbuttons. 1. Digital Display - In the Normal mode, the digital display provides a continuous reading of the input from the PointWatch. An input signal less than 4 ma is displayed as a negative reading by the controller. An input signal greater than 20 ma is displayed as an over-range reading by the controller. A1384 Figure 9—Controller Front Panel 5. Low Alarm LED - Flashes in response to a sensor signal that exceeds the low setpoint. NOTE The alarm LEDs flash when the setpoint is exceeded and are on steady (until reset) when the gas level drops below the setpoint, whether the corresponding alarm output is latching or non-latching. In the event of a fault, the digital display identifies the nature of the fault using an alpha-numeric code. When the PointWatch unit is in the calibrate mode, the display tracks the calibration procedure. In other operating modes it shows the alarm setpoints and programmed calibration gas concentration. Since this display is always lit, it also functions as a power indicator. 6. Cal LED - Illuminated while the controller is in the calibrate mode. 2. Bar Graph Display - In the Normal mode, the 20 segment bar graph display provides a reading of sensor input in 5% LFL increments. NOTE In the Setpoint Display or Setpoint Adjust mode, a flashing alarm LED identifies the particular setpoint currently being indicated on the digital display. A flashing Cal LED indicates that the programmed calibration gas concentration (in % LFL) is currently being shown on the digital display. 3. High Alarm LED - Flashes in response to a sensor signal that exceeds the high setpoint. 4. Auxiliary Alarm LED - Flashes in response to a sensor signal that exceeds the auxiliary setpoint. 1.1 12 95-8475 — The Fault LED flashes. 7. Fault LED - Flashes upon detection of a system fault and is on steady during the power-up time delay. — The digital display identifies the nature of the fault using an alpha-numeric code. Refer to Table 2 for an interpretation of the codes. 8. Reset Pushbutton - Used for various system programming and calibration functions as well as for resetting the controller. — The normally energized Fault output is deenergized. — The dc current output drops to less than 1 ma. 9. Set Pushbutton - Used for various system programming and calibration functions. NOTE The fault code will be shown for about 2 seconds out of every 5 seconds. The gas concentration at the sensor will be displayed during the remaining time. If more than one fault should occur, the highest priority fault will be displayed. (Table 2 lists the faults in order of priority.) OUTPUTS The R8471H Controller is available in a Base version and a Premium version. The differences between the two models are the output configuration and programming options. An alarm condition will normally over-ride a fault condition unless the fault condition occurred first (except F10, F2X). However, faults that affect the actual function of the controller (F50, F60, F70, F9X) may impair the ability of the controller to maintain an alarm output. Base Model - The base controller is furnished with open collector transistor outputs (rated 100 milliamperes at 32 volts dc) for the Low alarm, High alarm, Auxiliary alarm, and Fault circuits. The normally de-energized alarm outputs are energized when their corresponding setpoints are exceeded. The fault output is normally energized and becomes deenergized upon detection of a system fault. All faults automatically reset except the F9X, F20, and F10 faults. After the fault condition has been corrected, the fault output automatically switches to the normal (energized) state, the dc current output returns to normal, and the Fault LED turns off. Clearing F9X faults requires removing operating power from the controller for approximately one second. Premium Model - The premium model is furnished with a set of four relays in place of the four solid state outputs. The relays have SPST contacts rated 5 amperes at 30 vdc or 250 vac. This model also includes a selectable isolated/nonisolated 4 to 20 ma dc current output for transmitting system information to other monitoring devices. The linear 4 to 20 ma output corresponds to levels from 0 to 100% LFL. If a system fault is detected, the output drops to less than 1.0 ma. The current output can be calibrated in the field to ensure maximum accuracy. (Refer to the “Calibration” section of this manual for details.) CAUTION The fault detection circuitry does not monitor the operation of external response equipment or the external wiring to these devices. It is important that these devices be checked periodically to ensure that they are operational. OPERATING MODES AUTOMATIC DIAGNOSTICS AND FAULT IDENTIFICATION The controller can operate in any of the following modes. See Figure 10. Operating modes other than Normal are selected by pressing the appropriate pushbutton(s) located on the controller front panel. The microprocessor based controller features selftesting circuitry that continuously checks for faulty sensor or open sensor wiring, low or high input voltage, and other problems that could prevent proper system response. When power is applied, the microprocessor automatically tests memory. In the Normal operating mode, it continuously monitors the input signal from the PointWatch to ensure proper functioning. In addition, a “watchdog” timer is maintained to ensure that the program is running correctly. If a fault should occur: 1.1 NORMAL In the Normal operating mode with no alarm condition: — Digital display is on and indicates the sensor input in % LFL. — Bar graph display reads the same as the digital display. 13 95-8475 POWER-UP RESET NORMAL BASIC RESET HOLD RESET < 0.5 SECOND RELEASE RESET RELEASE RESET RELEASE RESET TIME DELAY HOLD RESET FORCED RESET SETPOINT DISPLAY 9.0 SECONDS HOLD RESET CALIBRATE 1.0 SECOND 0.5 SECOND 1.0 SECOND SET RESET PUSHED WITH SET? NO YES SETPOINT ADJUST CURRENT CALIBRATE A1957 Figure 10—R8471H Controller Flow Chart In the Normal operating mode and a high alarm condition occurring: — All LEDs are off. — Alarm outputs are in their normal state (energized or de-energized as programmed). — Same as low or auxiliary alarm, but High LED is on and high alarm output is actuated. — Dc current output signal level corresponds to sensor input. When the signal decreases below the high alarm setpoint: — Fault output is energized. — The high alarm is always latching and unaffected by the latching/non-latching programming for the low and auxiliary alarms. High LED is on steady until reset. In the Normal operating mode with a low and/or auxiliary alarm condition occurring: — Digital display and bar graph display indicate the sensor input in % LFL. In the event of a system fault: — Low and/or Auxiliary LED flashes. — The normally energized Fault output is deenergized and the Fault LED is illuminated. — Low and/or Auxiliary alarm output changes state. — Dc current output signal level corresponds to sensor input. RESET — Fault output energized and LED off. The Reset mode is entered by pressing the Reset button located on the front panel of the controller. (See Figure 10.) When the signal decreases below the low or auxiliary setpoint: When the Reset button is momentarily depressed: — Digital display, bar graph display, and 4 to 20 ma output continue to track the sensor input. With no alarms or faults are occurring — all LEDs turn off and all outputs return to their normal condition (basic reset). — With latching operation programmed: No change to alarm outputs. — With non-latching operation programmed: Alarm outputs return to their normal state. If an alarm or fault condition exists — the basic reset will not reset the outputs. — Low and Auxiliary LEDs are on steady until reset. 1.1 14 95-8475 When the Reset button is held for 0.5 second: OPERATING RANGE— 0 to 100% LFL. If an alarm or fault condition exists — the LEDs turn off and the outputs return to their normal condition (forced reset). SOLID STATE OUTPUTS (Base model only)— Open collector transistors with a 100K resistor from the collector to emitter with the emitter grounded, rated 100 milliamperes at 32 volts dc maximum. NOTE If an alarm or fault condition exists, the controller will return to alarm or fault status when the reset button is released. RELAY CONTACTS (Premium model only)— Selectable normally open/normally closed contacts rated 5 amperes at 30 vdc/250 vac. See Table 1 for selectable relay options. Remote reset capability is also provided. (Remote reset performs a forced reset.) CURRENT OUTPUT (Premium model only)— 4 to 20 milliampere dc current, with a maximum loop resistance of 600 ohms at 24 vdc. User-selectable isolated or non-isolated signal reference from controller input power common return. NOTE The remote reset performs a reset function only. It cannot be used for entering other controller operating modes. DIMENSIONS— See Figure 11. OTHER OPERATING MODES Setpoint Display, Setpoint Adjustment, Calibration, and 4 to 20 ma Current Output Calibration modes are also executed by pressing buttons on the controller faceplate. Refer to the appropriate sections of this manual for details. SHIPPING WEIGHT (approximate)— 2.0 pounds (0.9 kilogram). 9.3 (23.6) ➛ ➛ ➛ ➛ ➛ 1.0 (2.5) SPECIFICATIONS OPERATING VOLTAGE— 24 vdc recommended. Operating range of 18 to 32 vdc. * 7.0 (17.8) Base model: 0.7 watt nominal, 1.3 watts maximum (25 ma nominal, 50 ma maximum at 24 vdc.) A1526 Premium model: 1.2 watts nominal, 3.5 watts maximum (50 ma nominal, 145 ma maximum at 24 vdc.) ➛ POWER CONSUMPTION (controller only, no transmitter or sensor included)— * 4U DIMENSIONS SHOWN, 3U HEIGHT IS 5.2 (13.3) Figure 11—Controller Dimensions in Inches (Centimeters) MAXIMUM SUPPLY VOLTAGE RIPPLE— Should not exceed 5 volts peak-to-peak. The sum of dcV plus ripple must be ≥18 vdc and ≤ 32 vdc. TEMPERATURE RANGE— Operating: +32°F to +140°F (0°C to +60°C) Storage: -49°F to +185°F (-45°C to +85°C). 1.1 15 95-8475 NOTE When replacing a controller, be sure that the jumper plugs and rocker switches of the replacement are the same as the original. Remove power before removing the device from the mounting cage or plugging in the replacement unit. SYSTEM APPROVAL— The R8471H Combustible Gas Controller, base and premium model in 3U and 4U height, has been tested and approved by FMA. It can be used with any FMA approved gas sensing device capable of generating a 4 to 20 ma input. FMA approval of the R8471H Combustible Gas Controller, however, does not include or imply approval of input devices such as sensors or transmitters, or devices connected to the controller outputs. To maintain FMA system approval, all equipment connected to the controller must be FMA approved. ROUTINE MAINTENANCE NOTE Ensure sensor hazardous (classified) location rating is applicable for the intended use. The gas detection system requires virtually no routine maintenance, except for periodic checks to assure proper system function and calibration. The frequency of these checks is determined by the requirements of the particular installation. The R8471H Combustible Gas Controller must be used only in non-hazardous locations. MANUAL CHECK OF OUTPUT DEVICES CENELEC: Fault detection circuitry continuously monitors for a sensor problem, excessive negative zero drift, wiring problems, and various other problems that could prevent proper response to a dangerous level of gas. It does not monitor external response equipment or the wiring to these devices. It is important that these devices be checked initially when the system is installed, as well as periodically during the ongoing maintenance program. CE Mark, EN 61779-4 Compliant. (Combustible gas performance). Refer to Appendix C. 0539 DEMKO 04 ATEX 134903X II (2) G. Special Conditions for Safe Use (“X”): Performance temperature rating 0°C to +60°C. The R8471H Combustible Gas Controller must be placed outside the Hazardous area. The R8471H Combustible Gas Controller must be used only in conjunction with stand-alone 4-20 mA CENELEC certified Combustible Gas Sensors. CHECKOUT IN NORMAL MODE The system must be checked periodically in the Normal mode to ensure that those items not checked by the controller diagnostic circuitry are functioning properly. CAUTION Be sure to secure all output devices that are actuated by the system to prevent unwanted activation of this equipment, and remember to place these same output devices back into service when the checkout is complete. Section III System Maintenance TROUBLESHOOTING Table 3 is intended to serve as an aid in locating the cause of a system malfunction. POINTWATCH MAINTENANCE Refer to the PointWatch instruction manual for information regarding maintenance or repairs to the PointWatch unit. NOTE Record all faults on the Fault Record Sheet supplied with this manual. It is recommended that power be removed prior to performing maintenance, repair or replacement. The R8471H Controller is not designed to be repaired in the field. If a problem should develop, first carefully check for proper wiring, programming and calibration. If it is determined that the problem is caused by a defect in the controller’s electronics, the device must be returned to the factory for repair. 1.1 A Recommended Test Form is supplied at the back of this manual for recording maintenance performed on the system. 16 95-8475 Table 3—Troubleshooting Guide Problem 1.1 Possible Cause No faceplate indicators illuminated. 1. Wiring to external power source. 2. Input power failure. FAULT LED on, digital display blank. 1. Power-up time delay (up to 5 minutes). 2. If condition continues after 5 minutes, repeat power-up. If problem continues, replace controller. F91 to F98 Status 1. Initialization failure. Repeat power-up. If successful, re-program and re-calibrate. If not, replace controller. F92 Status 1. Sensor failure (during startup) - current is over 35 ma or below 0.5 ma. F94 Status 1. RAM failure. Repeat power-up. If not successful, return to factory for repair. Do not press RESET button. If RESET is pressed, recalibrate and check setpoints. F96 Status 1. Input power problem (should be 18 to 32 volts). Check operation of power source and power wiring. F97 Status 1. Controller type invalid. Error in data from RAM. Repeat power-up. If not successful, return to factory for repair. Do not press RESET button. If RESET is pressed, recalibrate and check setpoints. F70 Status 1. External reset activated for over 15 seconds. Check external switch and wiring. F60 Status 1. Input power out of tolerance. Check operation of power source and power wiring. F50 Status 1. Internal power supply problem. Replace controller. F40 Status 1. Sensor output (after startup) is over 35 ma or below 0.5 ma. Check PointWatch wiring and calibration. 2. Faulty sensor. Replace and calibrate. F41 Status 1. PointWatch has dirty optics. Refer to PointWatch manual. F42 Status 1. PointWatch calibration line fault. F30 Status 1. Negative zero drift. Calibrate sensor. 2. Faulty sensor. Replace and calibrate. F20, F21 Status 1. Calibration error. Re-calibrate. F22, F23 Status 1. Sensor sensitivity out of tolerance. Calibrate PointWatch. If problem continues, replace sensor and calibrate. F24 Status 1. Wrong gas for zero calibration. 2. Background gas affecting the zero calibration. 3. Sensor zero input over limit, re-calibrate PointWatch. F10 Status 1. Sensor sensitivity problem. 17 95-8475 DEVICE REPAIR AND RETURN CALIBRATION KITS Prior to returning devices or components, contact the nearest local Detector Electronics office so that an RMI (Return Material Identification) number can be assigned. A written statement describing the malfunction must accompany the returned device or component to expedite finding the cause of the failure, thereby reducing the time and cost of the repair. Calibration Kit includes regulator, hose, calibration cup, and two cylinders of calibration gas. Available gases are: Pack the unit or component properly. Use sufficient packing material in addition to an anti-static bag or aluminum-backed cardboard as protection from electrostatic discharge. Replacement Parts for Calibration Kit Return all equipment transportation prepaid to the factory in Minneapolis. Replacement Cylinders Methane - 50% LFL Ethane - 50% LFL Ethylene - 50% LFL Propane - 50% LFL Regulator 3 foot hose Methane (50% LFL) Ethane (50% LFL) Ethylene (50% LFL) Propane (50% LFL) Air (0% LFL) ORDERING INFORMATION The PointWatch Detector must be ordered separately from the controller. When ordering please specify: For assistance in ordering a system to meet the needs of a specific application, please contact: R8471H Combustible Gas Controller Specify base or premium model, 3U or 4U height. Detector Electronics Corporation 6901 West 110th Street Minneapolis, Minnesota 55438 USA Operator: (952) 941-5665 or (800) 765-FIRE Customer Service: (952) 946-6491 Fax: (952) 829-8750 Web site: www.det-tronics.com E-mail: [email protected] MOUNTING RACKS A mounting rack is required for controller installation. 3U racks are slightly shorter in height than the 4U models, and are not rack-compatible with flame controllers. 4U racks can house gas or flame controllers in any combination. See Figures 1 and 2. Rack sizes are available to handle up to 8 flame controllers or up to 16 gas controllers. GAS DETECTOR • PointWatch Infrared Hydrocarbon Gas Detector • Junction box for PointWatch Detector 1.1 18 95-8475 APPENDIX A – FACTORY MUTUAL (FM) APPROVAL DESCRIPTION MODEL R8471H COMBUSTIBLE GAS CONTROLLER • Operating Temperature Limits 0°C to +60°C. • Storage Temperature Limits –45°C to +85°C. • Relative Humidity Range: 15 to 90% RH. • Combustible Gas Performance verified for 0 to 100% LFL methane-in-air atmospheres per FM 6310/6320. NOTES: • The Model R8471H Combustible Gas Controller must be connected to an FM Approved stand alone 4-20 mA combustible gas detection transmitter. The transmitter must be calibrated according to the manufacturer’s instructions and the controller must be calibrated using the procedure described in this manual. • FM Approval of the 4-20 mA input does not include or imply approval of the gas detection apparatus connected to the controller. In order to maintain FM Approval of the system, the 4-20 mA gas detection instruments connected to the input must also be FM Approved. 1.1 19 95-8475 APPENDIX B – CANADIAN STANDARDS ASSOCIATION (CSA) APPROVAL DESCRIPTION MODEL R8471H COMBUSTIBLE GAS CONTROLLER • Operating Temperature Limits 0°C to +60°C. • Storage Temperature Limits –45°C to +85°C. • Relative Humidity Range: 15 to 90% RH. • Combustible Gas Performance verified for 0 to 100% LFL methane-in-air atmospheres per CSA C22.2 #152. NOTES: • The Model R8471H Combustible Gas Controller must be connected to a CSA Certified stand alone 4-20 mA combustible gas detection transmitter. The transmitter must be calibrated according to the manufacturer’s instructions and the controller must be calibrated using the procedure described in this manual. • CSA Certification of the 4-20 mA input does not include or imply approval of the gas detection apparatus connected to the controller. In order to maintain CSA Certification of the system, the 4-20 mA gas detection instruments connected to the input must also be CSA Certified. 1.1 20 95-8475 10 20 30 40 50 60 70 80 90 100 8 8 8 10 20 30 40 50 60 70 80 90 100 8 8 8 21 10 20 30 40 50 60 70 80 90 100 8 8 8 R8471A 8 WITHOUT REFERENCE TO DEMKO. 1. DEMKO APPROVED DRAWING - NO MODIFICATIONS PERMITTED 2 4 2 R8471H CONTROLLER 4 CONTROLLER THE R8471A COMBUSTIBLE GAS CONTROLLER MUST BE USED ONLY IN CONJUNCTION WITH THE MODEL CGS COMBUSTIBLE GAS SENSOR. THE R8471H COMBUSTIBLE GAS CONTROLLER MUST BE USED ONLY IN CONJUNCTION WITH STAND-ALONE 4-20mA CENELEC CERTIFIED COMBUSTIBLE GAS SENSOR S. 2 DESIGN REFERENCE DRAWING 007736-001. 2 R8471A 4 CONTROLLER 3 SPECIAL CONDITIONS FOR SAFE USE ('X'): PERFORMANCE TEMP. RATING 0∞C TO +60∞C. THE R8471A AND R8471H COMBUSTIBLE GAS CONTROLLERS MUST BE PLACED OUTSIDE THE HAZARDOUS AREA. 4 CONFORMS TO EN 61779-4 (COMBUSTIBLE GAS PERFORMANCE CERTIFIED) 5 WARNING: ENSURE HAZARDOUS (CLASSIFIED) LOCATION RATING IS APPLICABLE FOR THE INTENDED USE. Ex %LEL SET FAULT RESET/CAL. L H Ex %LEL SET FAULT RESET/CAL. L H Ex %LEL SET FAULT RESET/CAL. L H II (2) G EN 61779-4 I I A B C DEMKO 04 ATEX 134903X 0539 ORDINARY LOCATIONS 7 7 6 6 SENSOR TERMINATION BOX, OPTIONAL (007006-001) SENSOR TERMINATION BOX, OPTIONAL (007006-001) HAZARDOUS LOCATIONS EEx d IIC T4-T6 DEMKO 02 ATEX 131324 T6(Tamb = -55∞C TO +60∞C) T5(Tamb = -55∞C TO +75∞C) T4(Tamb = -55∞C TO +125∞C) 5 IN NE A PO LI MN S, US A CAL/RESET ACCEPT SETUP MODEL U9500 %LFL EX INCREASE M DECREASE ALARM HI AUX LO XXXXX 3 4 3 4 4 4 CGS SERIES COMBUSTIBLE GAS SENSOR (006881-001) CGS SERIES COMBUSTIBLE GAS SENSOR (006881-001) HAZARDOUS LOCATIONS EEx d IIC T3, T5 DEMKO 02 ATEX 131323X T5(Tamb = -40∞C TO +75∞C) T3(Tamb = -55∞C TO +125∞C) Figure A-1 (Drawing 008940-001) 5 PIRTB TERMINATION BOX, OPTIONAL DEMKO 02 ATEX 131326 (007007-001) OR SENSOR TERMINATION BOX, OPTIONAL DEMKO 02 ATEX 131324 (007006-001) U9500A INFINITY TRANSMITTER DEMKO 02 ATEX 131327X (006956-001) P 505 COMBUSTIBLE GAS TRANSMITTER DEMKO 02 ATEX 131329X (006870-001) HAZARDOUS LOCATIONS EEx d IIC T5-T6 (SEE CERTIFICATE NUMBER BELOW) T6(Tamb = -55∞C TO +60∞C) T5(Tamb = -55∞C TO +75∞C) , R CO S IC ON TR EC EL OR 1.1 DE T E C T D 8 3 3 3 3 4 4 DWG NO DATE TITLE SHEET NO 2 DESCRIPTION 5 REV (0) ±.02 (0.0) ±.01 (0.00) ±.005 ANGLE ±1' ±(0.5) ±(0.25) ±(0.13) DATE DO NOT SCALE DRAWING SCALE NA 1 DETECTOR ELECTRONICS CORP. MINNEAPOLIS, MINNESOTA 55438 D SIZE 1 CADDS NAME: 008940-001 DRAWING NO. THIS DRAWING AND SPECIFICATION CONTAIN PROPRIETARY INFORMATION AND ANY REPRODUCTION DISCLOSURE OR USE THEREOF IS EXPRESSLY PROHIBITED WITHOUT THE WRITTEN PERMISSION OF DETECTOR ELECTRONICS CORPORATION. REMOVE ALL BURRS BREAK ALL EDGES AND SHARP CORNERS 0.0 0.00 0.000 UNLESS OTHERWISE SPECIFIED TOLERANCES ARE : DIMENSION TOLERANCE INCH (MM) INCH (MM) NEW RELEASE DWG, DESIGN REFERENCE R8471 SYSTEM "DEMKO" 1 OF 1 BILL OF MAT'L REQ. R8471 APP'D FIRST USED ON DATE APP'D DATE 11.5.04 DATE ECO NO. 7304 CDS CHECKED DRAWN REV A ATEX CERTIFIED 4-20mA STAND ALONE DEVICE OR ATEX SYSTEM CERTIFIED DEVICE HAZARDOUS LOCATION BASED ON DEVICE RATING SH 8940-01 APPROVED a A REV A B C D APPENDIX C – CE MARK 95-8475 Fault Record Sheet Date 1.1 Time Detector System Status Affected Operator Comments 22 95-8475 Recommended Test Form Detector Number 1.1 Detector Location Date Installed 23 Date Checked Date Calibrated Remarks 95-8475 Detector Electronics Corporation 6901 West 110th Street Minneapolis, MN 55438 USA X3301 Multispectrum IR Flame Detector PointWatch Eclipse® IR Combustible Gas Detector Eagle Quantum Premier® Safety System Eagle Logic Solver Safety System T: 952.941.5665 or 800.765.3473 F: 952.829.8750 W: http://www.det-tronics.com E: [email protected] Det-Tronics, the DET-TRONICS logo, Eagle Quantum Premier, and Eclipse are registered trademarks or trademarks of Detector Electronics Corporation in the United States, other countries, or both. Other company, product, or service names may be trademarks or service marks of others. © Copyright Detector Electronics Corporation 2007. All rights reserved.
advertisement
Related manuals
advertisement