BLAUBERG Ventilatoren Tower-H, Tower-H 310 4E, Tower-V User Manual
जाहिरात
जाहिरात
Centrifugal roof fan
Tower-V
Tower-H
EN
USER’S MANUAL
www.blaubergventilatoren.de
tower-V/H
CONTENTS
This user’s manual is a main operating document intended for technical, maintenance, and operating staff.
The manual contains information about the purpose, technical details, operating principle, design, and installation of the Tower-V/H unit (-s) and all of its (their) modifications.
Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country.
The information in this user’s manual is correct at the time of the document’s preparation.
The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments.
No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means in any information search system or translated into any language in any form without the prior written permission of the Company.
SAFETY REQUIREMENTS
• Please read the user’s manual carefully prior to installing and operating the unit.
• All user’s manual requirements as well as the provisions of all the applicable local and national construction, electrical, and technical norms and standards must be observed when installing and operating the unit.
• The warnings contained in the user’s manual must be considered most seriously since they contain vital personal safety information.
• Failure to follow the rules and safety precautions noted in this user’s manual may result in an injury or unit damage.
• After a careful reading of the manual, keep it for the entire service life of the unit.
• While transferring the unit control, the user’s manual must be turned over to the receiving operator.
UNIT INSTALLATION AND OPERATION SAFETY PRECAUTIONS
• Disconnect the unit from power mains prior to any installation operations.
• Unpack the unit with care.
• The unit must be grounded!
• While installing the unit, follow the safety regulations specific to the use of electric tools.
2
tower-V/H
• Do not change the power cable length at your own discretion. Do not bend the power cable. Avoid damaging the power cable. Do not put any foreign objects on the power cable.
• Do not use damaged equipment or cables when connecting the unit to power mains.
• Do not touch the unit controls with wet hands. Do not carry out the installation and maintenance operations with wet hands.
• Do not allow children to operate the unit.
• Do not store any explosive or highly flammable substances in close proximity to the unit.
• Do not open the unit during operation.
• Do not block the air duct when the unit is switched on.
• Do not sit on the unit and avoid placing foreign objects on it.
www.blaubergventilatoren.de
• Do not lay the power cable of the unit in close proximity to heating equipment.
• Do not operate the unit outside the temperature range stated in the user’s manual. Do not operate the unit in aggressive or explosive environments.
• Do not wash the unit with water. Protect the electric parts of the unit against ingress of water.
• Disconnect the unit from power mains prior to any technical maintenance.
• When the unit generates unusual sounds, odour, or emits smoke, disconnect it from power supply and contact the Seller.
• Do not direct the air flow produced by the unit towards open flame or ignition sources.
• In case of continuous operation of the unit, periodically check the security of mounting.
• Use the unit only for its intended purpose.
THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE.
DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.
3
www.blaubergventilatoren.de
tower-V/H
PURPOSE
THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED
PHYSICAL, MENTAL, OR SENSORY CAPACITIES, OR THOSE WITHOUT
THE APPROPRIATE TRAINING.
THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED
PERSONNEL AFTER THE APPROPRIATE BRIEFING.
THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED
ACCESS BY UNATTENDED CHILDREN.
The TOWER-V/TOWER-H roof fans in metal casing are designed for ventilation systems in industrial premises as well as pools, apartment buildings, offices, hospitals, restaurants and other premises heated during the winter season.
The fan is mounted on the exhaust shaft of the air duct and is used only for exhaust ventilation.
DELIVERY SET
NAME
Fan
User’s manual
Packing box
NUMBER
1 pc.
1 pc.
1 pc.
DESIGNATION KEY
Designation example: TOWER-V 310 X X XX
Centrifugal roof fan
TOWER-V — with vertical air discharge
TOWER-H — with horizontal air discharge
Turbine standard size [mm]
200; 220; 225; 250; 280; 300; 310; 350; 355; 400; 450; 500
Number of motor poles
2, 4, 6
E — single-phase
D — three-phase
Options
CP — integrated pressure differential regulator
CF — integrated constant air flow regulator
S — built-in external switch
4
tower-V/H
The unit is rated as a Class I electrical appliance.
TOWER-V TOWER-H www.blaubergventilatoren.de
TECHNICAL DATA
D
438
438
438
438
438
438
213
213
285
285
285
285
438
D
438
438
438
438
438
213
213
285
285
285
285
438
438
Model
TOWER-H 220 2E
TOWER-H 225 2E
TOWER-H 250 2E
TOWER-H 280 2E
TOWER-H 310 4E
TOWER-H 310 4D
TOWER-H 355 4E
TOWER-H 355 4D
TOWER-H 400 4E
TOWER-H 450 4E
TOWER-H 400 4D
TOWER-H 450 4D
TOWER-H 500 6E
Model
TOWER-V 220 2E
TOWER-V 225 2E
TOWER-V 250 2E
TOWER-V 280 2E
TOWER-V 310 4E
TOWER-V 310 4D
TOWER-V 355 4E
TOWER-V 355 4D
TOWER-V 400 4E
TOWER-V 450 4E
TOWER-V 400 4D
TOWER-V 450 4D
TOWER-V 500 6E
Overall and connecting dimensions [mm]
H
420
454
420
454
454
275
275
275
275
330
330
420
420
L2
783
872
783
872
872
460
460
520
520
560
560
783
783
L1
450
535
450
535
535
245
245
330
330
330
330
450
450 d
12
12
12
12
12
12
10
10
10
10
10
10
12
Overall and connecting dimensions [mm]
H
325
348
400
323
400
465
228
228
265
265
300
300
348
L
598
598
668
598
668
668
338
338
425
425
438
438
598
L1
450
450
535
450
535
535
245
245
330
330
330
330
450
L
598
668
598
668
668
338
338
425
425
438
438
598
598
L2
550
550
640
550
640
640
338
338
365
365
400
400
550
Weight [kg]
15.6
21.0
22.7
22.0
22.7
26.6
6.9
7.1
10.1
10.2
10.2
10.2
15.6
Weight [kg]
27.5
30.0
27.5
30.0
33.8
8.9
9.6
12.0
12.7
17.8
17.8
22.0
22.0
5
www.blaubergventilatoren.de
tower-V/H
TOWER-V / TOWER-H
220 2E
Voltage [V]
Frequency [Hz]
1~ 220-240
50 60
Power [W] 85
Current [A] 0.38
111
0.44
Maximum air flow [m³/h] 700
RPM [min -1 ] 2700
Sound pressure level at 3 m distance
[dBA]
Maximum transported air temperature
[°C]
SEC class*
49
55
B
Ingress protection rating IPX4
815
2810
51
50
B
TOWER-V / TOWER-H
225 2E
1~ 220-240
50 60
135
0.6
142
0.65
900
2650
940
2830
49
55
B
IPX4
51
50
B
TOWER-V / TOWER-H
250 2E
1~ 220-240
50 60
155
0.7
265
1.15
1300
2600
1480
2640
65 70
50
-
IPX4
50
-
TOWER-V / TOWER-H
280 2E
1~ 220-240
50 60
225
1.0
348
1.51
1780
2700
1855
2790
66 69
50
-
IPX4
50
-
TOWER-V / TOWER-H
310 4E
Voltage [V]
Frequency [Hz]
1~ 220-240
50
Power [W] 120
60
183
Current [A] 0.54
Maximum air flow [m³/h] 1820
0.79
1880
RPM [min -1 ] 1370
Sound pressure level at 3 m distance
[dBA]
Maximum transported air temperature
[°C]
45
85
Ingress protection rating IPX4
1420
46
50
TOWER-V / TOWER-H
310 4D
3~ 400
50
110
60
172
0.32
1950
1400
0.32
2030
1480
TOWER-V / TOWER-H
355 4E
1~ 220-240
50 60
245 305
1.12
2800
1420
1.34
2920
1530
TOWER-V / TOWER-H
355 4D
3~ 400
50
170
60
235
0.52
2350
1400
0.5
2570
1600
53
65
IPX4
54
50
46
50
IPX4
49
50
53
70
IPX4
55
50
TOWER-V /
TOWER-H
400 4E
Voltage [V] 1~ 220-240
TOWER-V / TOWER-H
3~ 400 Δ
400 4D
TOWER-V /
TOWER-H
450 4E
3~ 400 Y 1~ 220-240
Frequency [Hz] 50 60 50 60 50 60
Power [W] 480 665 515 750 385 515
50
640
Current [A] 2.4
2.99
1.41
1.44
0.7
0.93
Maximum air flow [m³/h] 3400 3500 3950 4200 3800 3850
RPM [min -1 ] 1400 1480 1415 1610 1430 1420
Sound pressure level at 3 m distance
[dBA]
Maximum transported air temperature [°C]
Ingress protection rating
52
80
IPX4
53
50
59
-40
+60
IPX4
62
-40
+60
52
-40
+60
IPX4
53
-40
+40
3.1
3850
1350
53
50
IPX4
TOWER-V /
TOWER-H
450 4D
400 Y
50
470
0.82
4300
1430
53
50
IPX4
TOWER-V /
TOWER-H
500 6E
1~ 220-240
50
385
60
475
1.82
2.1
4700 5130
880 850
47
50
IPX4
49
40
6
tower-V/H www.blaubergventilatoren.de
MOUNTING AND SET-UP
BEFORE MOUNTING MAKE SURE THE CASING DOES NOT CONTAIN ANY FOREIGN
OBJECTS (E.G. FOIL, PAPER).
WHILE INSTALLING THE UNIT ENSURE CONVENIENT ACCESS FOR SUBSEQUENT
MAINTENANCE AND REPAIR.
• Fans are designed for horizontal mounting on a flat roof directly above an air duct or a ventilation shaft.
• In order to avoid ingress of water and snow into the ventilation duct, it is possible to install a fan on the mounting frame.
• The fan is connected to the ventilation duct by means of a counter flange, which is attached directly to the fan base.
• The fan base has holes for fixing bolts that attach the fan to a stationary even surface or to a mounting frame.
• A mounting frame, a counter flange and mounting bolts are not included in the delivery set and must be purchased separately.
TOWER-V
7
www.blaubergventilatoren.de
TOWER-H
3 tower-V/H
8
tower-V/H www.blaubergventilatoren.de
CONNECTION TO POWER MAINS
DISCONNECT THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
CONNECTION OF THE UNIT TO POWER MAINS IS ALLOWED BY A QUALIFIED
ELECTRICIAN WITH A WORK PERMIT FOR THE ELECTRIC UNITS UP TO 1000 V AFTER
CAREFUL READING OF THE PRESENT USER’S MANUAL. THE RATED ELECTRICAL
PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S LABEL.
• The unit is rated for connection to power mains with the parameters specified in the «Technical specifications» section, according to the wiring diagram. The connection must be made using durable, insulated and heat-resistant conductors (cables, wires).
• The actual wire cross section selection must be based on the maximum load current, maximum conductor temperature depending on the wire type, insulation, length and installation method.
• The external power input must be equipped with an automatic circuit breaker QF built into the stationary wiring to open the circuit in the event of overload or short-circuit. The position of the external automatic circuit breaker must ensure free access for quick power-off of the unit. The trip current of the automatic circuit breaker must exceed the maximum current consumption of the unit (refer to the
«Technical data» section or to the unit label). It is recommended to select the nominal current of the circuit breaker from the standard series, following the maximum current of the connected unit. The circuit breaker is not included in the delivery set and can be ordered separately.
Electrical connection is made on the terminal block located in the remote or integrated terminal box of the electric motor.
The terminal designations are shown on the label inside the fan casing.
ACCESS TO THE TERMINAL BLOCK TOWER-V
ACCESS TO THE TERMINAL BLOCK TOWER-H
9
www.blaubergventilatoren.de
Power supply parameters and examples of wiring diagrams depending on the unit model tower-V/H
TOWER-V/
TOWER-H 220 2E
TOWER-V/
TOWER-H 225 2E
TOWER-V/
TOWER-H 250 2E
TOWER-V/
TOWER-H 280 2E
TOWER-V/
TOWER-H 310 4E
TOWER-V/
TOWER-H 355 4E
L
~230 V
50 (60) Hz
N
PE
L
РЕ
N 3
4
X1
1
2
TOWER-V/
TOWER-H 310 4D
~400 V
50 (60) Hz
L1
L2
L3
PE
L1
L2
L3
РЕ
2
3
4
X1
1
10
TOWER-V/TOWER-H
400 4E
TOWER-V/TOWER-H
450 4E
TOWER-V/TOWER-H
500 6E
~230 V
50 (60) Hz
L
N
PE
TW1
TW2
L
РЕ
N
TW1
TW2
4
5
6
2
3
X1
1
TOWER-V/
TOWER-H 355 4E
TOWER-V/
TOWER-H 400 4D
TOWER-V/
TOWER-H 450 4D
L1
~400 V
50 (60) Hz
L2
L3
PE
L1
L2
L3
TW1
TW2
L1
L2
L3
РЕ
TW1
TW2
5
6
7
8
2
3
4
9
X1
1 U1
V1
W1
U2
V2
W2
PE
TW1
TW2
Model
TOWER-V/TOWER-H 220...250 2E
TOWER-V/TOWER-H 310 4E
TOWER-V/TOWER-H 280 2E
TOWER-V/TOWER-H 355 4E
TOWER-V/TOWER-H 400...450 4E
TOWER-V/TOWER-H 500 6E
TOWER-V/TOWER-H 310...450 4D
TOWER-V/TOWER-H 250...310 EC
TOWER-V/TOWER-H 355...450 EC
TOWER-V/TOWER-H 500...560 EC
Recommended rated current of the circuit breaker [A]
1
Recommended cable, nxS, where n is the number of wires, and S is the cross section in mm2
3x0.5
1.6
1
4
4
2.5
2
10
3x0.5
3x1.0
3x1.0
5x0.5
3x1.0
5x0.75
5x1.5
tower-V/H www.blaubergventilatoren.de
TECHNICAL MAINTENANCE
DISCONNECT THE UNIT FROM POWER MAINS BEFORE ANY MAINTENANCE
OPERATIONS!
• The technical maintenance includes periodic cleaning of the surfaces from accumulated dust and dirt.
• When carrying out fan maintenance, it is necessary to partially disassemble it in order to access contaminated parts of the fan.
• The impeller blades require thorough cleaning once in 6 months.
• Use a soft dry cloth, brush or compressed air to remove dust.
• Carry out wet cleaning using warm water and a mild household detergent.
• Protect the electric motor against liquid ingress.
• Do not immerse the unit in water!
• Do not use aggressive solvents, or sharp objects as they may damage the impeller.
TOWER-V
TOWER-H
11
www.blaubergventilatoren.de
tower-V/H
TROUBLESHOOTING
Problem
The fan does not start.
Noise, vibration.
Possible reasons
No power supply.
The fan impeller is soiled.
The fan or casing screw connection is loose.
Troubleshooting
Make sure the power supply line is connected correctly, otherwise troubleshoot a connection error.
Clean the impellers.
Tighten the screw connection of the casing against stop.
STORAGE AND TRANSPORTATION REGULATIONS
• Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range from +5 ˚С to +40 ˚С and relative humidity up to 70 %.
• Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
• Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
• Follow the handling requirements applicable for the particular type of cargo.
• The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
• Avoid sharp blows, scratches, or rough handling during loading and unloading.
• Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least
3-4 hours.
12
tower-V/H www.blaubergventilatoren.de
13
www.blaubergventilatoren.de
tower-V/H
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby declare that the product complies with the provisions of Electromagnetic Council Directive 2014/30/EU, Low Voltage Directive 2014/35/
EU and CE-marking Directive 93/68/EEC. This certificate is issued following test carried out on samples of the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date provided the user's observance of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation through the Manufacturer's fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component.
The warranty repair does not include:
• routine technical maintenance
• unit installation/dismantling
• unit setup
To benefit from warranty repair, the user must provide the unit, the user's manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases:
• User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
• Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user's manual.
• User’s failure to ensure timely technical maintenance of the unit.
• External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
• Redesign or engineering changes to the unit.
• Replacement and use of any assemblies, parts and components not approved by the manufacturer.
• Unit misuse.
• Violation of the unit installation regulations by the user.
• Violation of the unit control regulations by the user.
• Unit connection to power mains with a voltage different from the one stated in the user's manual.
• Unit breakdown due to voltage surges in power mains.
• Discretionary repair of the unit by the user.
• Unit repair by any persons without the manufacturer’s authorization.
• Expiration of the unit warranty period.
• Violation of the unit transportation regulations by the user.
• Violation of the unit storage regulations by the user.
• Wrongful actions against the unit committed by third parties.
• Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
• Missing seals if provided by the user’s manual.
• Failure to submit the user’s manual with the unit purchase date stamp.
• Missing payment paperwork certifying the unit purchase.
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND
TROUBLE-FREE OPERATION OF THE UNIT.
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON
PRESENTATION OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL
WITH THE PURCHASE DATE STAMP.
14
tower-V/H www.blaubergventilatoren.de
Unit Type
Model
Serial Number
Manufacture Date
Quality Inspector’s
Stamp
Centrifugal roof fan
CERTIFICATE OF ACCEPTANCE
TOWER-___________________________________
SELLER INFORMATION
Seller
Address
Phone Number
Purchase Date
This is to certify acceptance of the complete unit delivery with the user’s manual. The warranty terms are acknowledged and accepted.
Customer’s Signature
Seller’s Stamp
INSTALLATION CERTIFICATE
The TOWER-___________________________________ unit is installed pursuant to the requirements stated in the present user's manual.
Company name
Address
Phone Number
Installation
Technician’s Full Name
Installation Date: Signature:
The unit has been installed in accordance with the provisions of all the applicable local and national construction, electrical and technical codes and standards. The unit operates normally as intended by the manufacturer.
Signature:
Installation Stamp
WARRANTY CARD
Unit Type
Model
Serial Number
Manufacture Date
Purchase Date
Warranty Period
Seller
Centrifugal roof fan
TOWER-___________________________________
Seller’s Stamp
15
www.blaubergventilatoren.de
B204EN-01