KMC BAC-7303 Installation Guide

Add to My manuals
20 Pages

advertisement

KMC BAC-7303 Installation Guide | Manualzz

Installation and Operation Guide

BAC-7303 and BAC-7303C

Advanced Applications Controller for Fan Coil Unit Applications

Section 1

About the BAC-7303

Specifications ........................................................................................................................ 3

Accessories ............................................................................................................................ 6

Safety considerations .......................................................................................................... 7

Section 2

Installing the controller

Mounting .............................................................................................................................. 9

Connecting inputs ............................................................................................................... 9

Connecting outputs ........................................................................................................... 10

Connecting to a NetSensor ............................................................................................... 11

Connecting to an MS/TP network .................................................................................. 11

Connecting power ............................................................................................................. 13

Programming ..................................................................................................................... 14

Section 3

Operating the controller

Operation ............................................................................................................................ 15

Controls and Indicators .................................................................................................... 15

Restoring factory settings ................................................................................................. 18

Revision F 905-019-59F

KMC Controls

Important notices

Disclaimer

©2013, KMC Controls, Inc.

WinControl XL Plus, NetSensor, and the KMC logo are registered trademarks of

KMC Controls, Inc.

BACstage and TotalControl are trademarks of KMC Controls, Inc.

MS/TP automatic MAC addressing is protected under United States Patent

Number 7,987,257.

All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language in any form by any means without the written permission of KMC Controls, Inc.

Printed in U.S.A.

The material in this manual is for information purposes only. The contents and the product it describes are subject to change without notice. KMC Controls, Inc. makes no representations or warranties with respect to this manual. In no event shall KMC

Controls, Inc. be liable for any damages, direct or incidental, arising out of or related to the use of this manual.

KMC Controls

P.O. Box 497

19476 Industrial Drive

New Paris, IN 46553

U.S.A.

TEL: 1.574.831.5250

FAX: 1.574.831.5252

E-mail: [email protected]

2 Revision F

BAC-7303 FCU Controller

SECTION 1

About the BAC-7303

This section provides a general description of the KMC Controls

BAC-7303 controller. It also introduces safety information. Review this material before installing or operating the controller.

Specifications

Revision F

The BAC-7303 is a native BACnet, fully programmable controller designed for fan coil units. Use this versatile controller in stand-alone environments or networked to other BACnet devices. As part of a complete facilities management system, the BAC-

7303 controller provides precise monitoring and control of connected points.

BACnet MS/TP compliant

Automatically assigns the MAC address and the device instance

Triac outputs for fan control, two-stage heating or two-stage cooling

Supplied with programming sequences for fan coil units

Easy to install, simple to configure, and intuitive to program

Controls room temperature, humidity, fans, monitors refrigeration, lighting, and other building automation functions.

Inputs

Universal inputs

Key features

Pull–up resistors

Connector

Conversion

Pulse Counting

Input range

4

Software selectable as analog, binary or accumulator objects. Accumulators limited to three in one controller.

Standard units of measure.

NetSensor compatible

Overvoltage input protection

Switch select none or 10k

.

Removable screw terminal block, wire size

14–22 AWG

10–bit analog–to–digital conversion

Up to 16 Hz

0–5 volts DC

Outputs, Universal

Key features

Connector

Output voltage

Output current

2

Output short protection

Programmable as an analog or binary object.

Standard units of measure

Removable screw terminal block

Wire size 14-22 AWG

0–10 volts DC analog

0–12 volts DC binary output range

100 mA per output

3

About the BAC-7303

Specifications

4

KMC Controls

Outputs, Single-stage triac 1

Key features

Connector

Optically isolated triac output.

Programmable a binary object.

Removable screw terminal block

Wire size 14-22 AWG

Output range Maximum switching 30 volts AC at 1 ampere

Outputs, Dual-stage triac

Key features

Connector

Output range

1

Two optically isolated triac outputs.

Programmable as binary object.

Removable screw terminal block

Wire size 14-22 AWG

Maximum switching 30 volts AC at 1 ampere

Communications

BACnet MS/TP

NetSensor

EIA–485 operating at rates up to 76.8 kilobaud.

Automatic baud detection.

Automatically assigns MAC addresses and device instance numbers.

Removable screw terminal block.

Wire size 14–22 AWG

Compatible with models KMD-1161, KMD-1162,

KMD-1181 and KMD-1183, Connects through RJ–12 connector.

Programmable features

Control Basic

PID loop objects

Value objects

Time keeping

10 program areas

4 loop objects

40 analog and 40 binary

Real time clock with power backup for 72 hours

(BAC-7303-C only)

See PIC statement for supported BACnet objects

Schedules

Schedule objects

Calendar objects

Trend objects

8

3

8 objects each of which holds 256 samples

Alarms and events

Intrinsic reporting Supported for input, output, value, accumulator, trend and loop objects.

Notification class objects 8

Memory Programs and program parameters are stored in nonvolatile memory.

Auto restart on power failure

Revision F

BAC-7303 FCU Controller About the BAC-7303

Specifications

Application programs

Regulatory

Environmental limits

Operating

Shipping

Humidity

Installation

Supply voltage

Weight

Case material

Models

BAC-7303C

BAC-7303

KMC Controls supplies the BAC-7303 controllers with programming sequences for fan coil units:

Proportional fan control

Proportional chilled water valve

1 or 2 stage heat

Optional humidity control

UL 916 Energy Management Equipment

FCC Class A, Part 15, Subpart B

BACnet Testing Laboratory listed

SASO PCP Registration KSA R-103263

32 to 120° F (0 to 49° C)

–40 to 140° F (–40 to 60° C)

0–95% relative humidity (non-condensing)

24 volts   AC   (–15%,   +20%),   50 ‐ 60   Hz,   8   VA   minimum,   15   VA   maximum   load,   Class   2   only,   non ‐ supervised   (all   circuits,   including   supply   voltage,   are   power   limited   circuits)

8.2 ounces (112 grams)

Flame retardant green and black plastic

BACnet FCU controller with real-time clock

BACnet FCU controller without real-time clock

Revision F 5

About the BAC-7303

Accessories

Dimensions

E

A

Accessories

C

B

Table 1-1 BAC-7303 Dimensions

A

4.36 in.

B

6.79 in.

C

1.42 in.

111 mm 172 mm 36 mm

D

4.00 in.

E

6.00 in.

102 mm 152 mm

Power transformer

XEE-6111-40

XEE-6112-40

Single-hub 120 volt transformer

Dual-hub 120 volt transformer

D

KMC Controls

6 Revision F

BAC-7303 FCU Controller About the BAC-7303

Safety considerations

Safety considerations

KMC Controls assumes the responsibility for providing you a safe product and safety guidelines during its use. Safety means protection to all individuals who install, operate, and service the equipment as well as protection of the equipment itself. To promote safety, we use hazard alert labeling in this manual. Follow the associated guidelines to avoid hazards.

Danger

Danger represents the most severe hazard alert. Bodily harm or death will occur if danger guidelines are not followed.

Warning

Warning represents hazards that could result in severe injury or death.

Caution

Caution indicates potential personal injury or equipment or property damage if instructions are not followed.

Note

Notes provide additional information that is important.

Detail

Provides programing tips and shortcuts that may save time.

Revision F 7

About the BAC-7303

Safety considerations

KMC Controls

8 Revision F

BAC-7303 FCU Controller

SECTION 2

Installing the controller

This section provides a brief overview of the BAC-7303 and the

BAC-7303C Direct Digital Controllers. Review this material before you attempt to install the controller.

Mounting

Mount the controller inside of a metal enclosure. KMC Controls recommends using a UL-approved Enclosed Energy Management Equipment Panel such as a KMC model HCO–1034, HCO–1035 or HCO–1036. Insert #6 hardware through the four mounting holes on the top and bottom of the controller to securely fasten it to a flat

surface. See Dimensions on page 6 for mounting hole locations and dimensions. To

maintain RF emission specifications, use either shielded connecting cables or enclose all cables in conduit.

Connecting inputs

The BAC-7303 controller has four universal inputs. Each input can be configured to receive either analog or digital signals. By using the optional pull-up resistors, either passive or active devices may be connected to the inputs.

Note

KMC supplied Control Basic programs assign input 1 (I1) to the space temperature sensor input. If the KMC programs are not in used or are modified, input 1 is available for other use. Inputs 2 and 3 are not assigned by

KMC programs and are available as needed.

Pull–up resistors

For passive input signals, such as thermistors or switch contacts, use a pull-up resistor. For KMC thermistors and most other applications set the switch to the On

position. See Illustration 2-1 for the pull-up switch location.

BAC-7303 cover removed.

1

Off On

Illustration 2-1 Pull-up resistors and input terminals

Revision F 9

Installing the controller

Connecting outputs

Connecting outputs

10

KMC Controls

4–20 mA inputs

To use a 4–20 current loop input, connect a 250 ohm resistor from an input to ground. The resistor will convert the current input to a voltage which can be read by the controller analog-to-digital converter. Set the pull-up switch to the Off position.

Ground terminals

Input ground terminals are located next to the input terminals. Up to two wires, size

14 – 22 AWG, can be clamped into each ground terminal. If more than two wires must be joined at a common point, use an external terminal strip to accommodate the additional wires.

Pulse inputs

Connect pulse inputs under the following conditions:

If the pulse input is a passive input such as switch contacts, then place the input pull-up in the On position.

If the pulse is an active voltage (up to a maximum of +5 volts DC ), then place the input pull-up jumper in the Off position.

The BAC-7303 includes one single-stage triac, one-dual stage triac and two universal outputs. All triacs are rated for 30 volt, 1 ampere loads, switch on zero crossing and are optically isolated.

Triac 1 output and return

Triac 2a, 2b outputs and return

Universal outputs 3, 4 and ground

Illustration 2-2 Output terminals

Caution

When connecting loads to triacs, use only the terminal marked RTN associated with each triac for the 24-volt circuit.

Output 1 This output a single triac is designed to switch a 24-volt AC fan motor starter circuit.

Output 2 Typically programmed with a PID loop object to control two-stage heating. Triac 2A turns on when the programmed output is above 40% and turns off below 30%. Triac 2B turns on when the programmed output is above 80% and turns off below 70%.

Revision F

BAC-7303 FCU Controller Installing the controller

Connecting to a NetSensor

Outputs 3 and 4 These outputs are universal outputs that can be programmed as either analog or digital output objects.

Connecting to a

NetSensor

The Network RJ–12 connector provides a connection port to a compatible NetSensor

model. See NetSensor on page 4 . Connect the controller to a NetSensor with a KMC

Controls approved cable. The cable can be no longer than 75 feet. See the installation guide supplied with the NetSensor for complete NetSensor installation instructions.

75 feet Max.

Illustration 2-3 Connection to a NetSensor

Connecting to an

MS/TP network Connections and wiring

Use the following principles when connecting a controller to an MS/TP network:

Connect no more than 128 addressable BACnet devices to one MS/TP network. The devices can be any mix of controllers or routers.

To prevent network traffic bottlenecks, limit the MS/TP network size to 60 controllers.

Use 18 gauge, twisted pair, shielded cable with capacitance of no more than

50 picofarads per foot for all network wiring. Belden cable model #82760 meets the cable requirements.

Connect the A terminal in parallel with all other - terminals.

Connect the + B terminal in parallel with all other + terminals.

Connect the shields of the cable together at each controller. For KMC

BACnet controllers use the S terminal.

Connect the shield to an earth ground at one end only.

Use a KMD–5575 BACnet MS/TP repeater between every 32 MS/TP devices or if the cable length will exceed 4000 feet (1220 meters). Use no more than seven repeaters per MS/TP network.

Place a KMD–5567 surge surpressor in the cable where it exits a building.

Revision F 11

Installing the controller

Connecting to an MS/TP network

KMC Controls

See Application Note AN0404A, Planning BACnet Networks for addional information about installing controllers.

-A

+B

S

-A

+B

S

-A

+B

S

-A

+B

S

Illustration 2-4 MS/TP network wiring

Note

The BAC-7303 EIA–485 terminals are labeled -A , +B and S . The S terminal is provided as a connecting point for the shield. The terminal is not connected to the ground of the controller. When connecting to controllers from other manufacturers, verify the shield connection is not connected to ground.

End of line termination switches

The controllers on the physical ends of the EIA-485 wiring segment must have endof-line termination installed for proper network operation. Set the end-of-line termination to On using the EOL switches.

Set end-of-line termination to

On in these controllers only.

Illustration 2-5 End of line termination

12 Revision F

BAC-7303 FCU Controller Installing the controller

Connecting power

Illustration 2-6 shows the position of the BAC-7303 end-of-line switches associated

with the EIA–485 inputs.

Network connector

Off On

EOL switches

Connected

Disconnected

Network disconnect switch

1

Illustration 2-6 Location of EOL switch

Connecting power

The controllers require an external, 24 volt, AC power source. Use the following guidelines when choosing and wiring transformers.

Use a KMC Controls Class–2 transformer of the appropriate size to supply power to the controllers. KMC Controls recommends powering Power only one controller from each transformer.

When installing a controller in a system with other controllers, you may power multiple controllers with a single transformer as long as the total power drawn from the transformer does not exceed its rating and phasing is correct.

If several controllers are mounted in the same cabinet, you can share a transformer between them provided the transformer does not exceed 100 VA or other regulatory requirements.

◆ Do not run 24 volt, AC power from within an enclosure to external controllers.

Connect the 24 volt AC power supply to the power terminal block on the lower right side of the controller near the power jumper. Connect the ground side of the transformer to the – or GND terminal and the AC phase to the ~ (phase) terminal.

Power is applied to the controller when the transformer is plugged in and the power jumper is in place.

Illustration 2-7 Power terminal and jumper

Revision F 13

Installing the controller

Programming

Programming

KMC Controls

Network configuration

For more information on installing, configuring, and programming HVAC system controllers, see the following documents available on the KMC Controls web site:

BACstage User’s Guide to Installation and Getting Started (902-019-62)

BAC-5000 Reference Guide (902019-63)

TotalControl Reference Guide

Application Note AN0404A Planning BACnet Networks .

MS/TP Automatic MAC Addressing Installation Instructions

Supplied applications programming

Refer to the KMC Digital Applications Manual for information on using the applications programs included with the controller.

14 Revision F

BAC-7303 FCU Controller

SECTION 3

Operating the controller

This section provides a brief overview of the BAC-7303 and the

BAC-7303C Direct Digital Controllers. Review this material before you attempt to install the controller.

Operation

Once configured, programmed and powered up, the controller requires very little user intervention.

Controls and

Indicators

The following topics describe the controls and indicators found on the controller.

Additional information for automatic addressing functions are described in the guide MS/TP Automatic MAC Addressing Installation Instructions that is available from the KMC Controls web site.

Connected

Disconnected

Network disconnect switch

Restart button

Revision F

Isolation bulbs

Ready status LED

Com status LED

Power jumper

1

Illustration 3-1 Controls and indicators

Network disconnect switch

The network disconnect switch is located on the left side of the controller. Use this switch to enable or disable the MS/TP network connection. When the switch is ON the controller can communicate on the network; when it is OFF, the controller is isolated from the network.

Alternately, you may remove the isolation bulbs to isolate the controller from the network.

15

Operating the controller

Controls and Indicators

KMC Controls

Ready LED

The green Ready LED indicates the state of the controller. This includes automatic addressing functions that are fully described in the guide MS/TP Addressing For

BACnet Controllers.

Power up During controller initialization, the Ready LED is continuously illuminated for 5 to 20 seconds. Once initialization is complete, the Ready LED begins flashing to indicate normal operation.

Normal operation During normal operation, the Ready LED flashes a repeating pattern of one second on and then one second off.

Restart button acknowledge The restart button includes several functions for automatic addressing that are acknowledged with the Ready LED. When the restart button is pressed, the Ready LED illuminates continuously until either of the following take place:

• The restart button is released.

• The restart button time-out period is reached and a restart operation is complete. Restart button operations are listed in the following table.

Table 3-1 Ready LED patterns for restart button operations

Controller state LED pattern

The controller is set as an automatic addressing anchor. The MAC in the controller is set to 3

The controller has sent the automatic addressing lock command to the network

No restart operation

A rapid repeating pattern of a short flash followed by a short pause.

Two short flashes followed by a long pause. The pattern repeats until the restart button is released.

Ready LED remains unlit until the restart button is released.

Communications (Com) LED

The yellow Communications LED indicates how the controller is communicating with other controllers on the network.

Sole master Repeating pattern of a long flash and a short pause that repeats once a second. It indicates that the controller has either generated the token or is a sole MS/

TP master and has yet to establish communications with other MS/TP devices.

Token passing A short flash each time the token is passed. The frequency of the flash is an indication of how often the device receives the token.

16 Revision F

BAC-7303 FCU Controller Operating the controller

Controls and Indicators

Nomad patterns There are three Com LED patterns that indicate that the controller is an automatic addressing nomad controller that is receiving valid MS/TP traffic.

Table 3-2 Automatic addressing nomad patterns

Controller state

Lost nomad

Wandering nomad

Assigned nomad

LED pattern

A long flash

A long flash followed by three short flashes

Three short flashes followed by a long pause.

Error conditions for the LEDs

The two network isolation bulbs, located next to the network switch, serve three functions:

Removing the bulbs opens the EIA-485 circuit and isolates the controller from the network.

If one or both bulbs are lit, it indicates the network is improperly phased. This means that the ground potential of the controller is not the same as other controllers on the network.

If the voltage or current on the network exceeds safe levels, the bulbs operate as fuses and may protect the controller from damage.

Revision F 17

Operating the controller

Restoring factory settings

KMC Controls

R estoring factory settings

If the controller appears to be operating incorrectly, or is not responding to commands, you may need to reset or restart the controller.

To perform a reset or restart, locate the red restart push-button and then—in order—use one of the following procedures.

1. A warm start is the option least disruptive to the network and should be tried first.

2. If problems persist, then try a cold start.

3. If the problems continues, restoring the controller to factory settings may be required.

Caution

Read all of the information in this section before proceeding!

Note

Momentarily pushing the red reset button while the controller remains powered will have no effect on the controller.

Performing a warm start

A warm start changes the controller as follows:

Restarts the controller’s Control Basic programs.

Leaves object values, configuration, and programming intact.

Caution

In the unlikely event that the checksum test in RAM fails during the warm start, the controller will automatically perform a cold start. During a cold start, controller outputs may abruptly turn connected equipment on and off. To prevent equipment damage, turn connected equipment off or temporarily remove the output terminal blocks from the controller before performing a warm start.

Do either of the following to perform a warm start:

Reinitialize the controller with either BACstage or TotalControl Design Studio a

BACnet operator workstation .

Remove the power jumper for a few seconds and then replace it.

Performing a cold start

Performing a cold start changes the controller as follows:

Restarts the controller programs.

Returns all object states to their initial factory settings until the controller programs update them.

Leaves configuration and programming intact.

18 Revision F

BAC-7303 FCU Controller Operating the controller

Restoring factory settings

Caution

Returning object values to their relinquished defaults during a cold start may abruptly turn connected equipment on or off. To prevent equipment damage, turn connected equipment off or temporarily remove the output terminal blocks from the controller before performing a warm start.

To perform a cold start:

1. While the controller is powered, press and hold the restart button.

2. Remove the power jumper.

3. Release the red button before replacing the power jumper.

Note

A cold start performed by this method is the same as performing a cold start with BACstage or from TotalControl Design Studio.

Restoring to factory settings

Restoring a controller to factory settings changes the controller as follows:

Removes all programming.

Removes all configuration settings.

Restores the controller to factory default settings.

Caution

Resetting the controller erases all configuration and programming. After resetting to factory settings, you must configure and program the controller to establish normal communications and operation.

To reset the controller to factory settings.

1. If possible, use BACstage or TotalControl Design Studio to backup the controller.

2. Remove the power jumper.

3. Press and hold the red restart button.

4. Replace the power jumper while continuing to hold the restart button.

5. Restore configuration and programming with BACstage or TotalControl

Design Studio.

Revision F 19

Operating the controller

Restoring factory settings

KMC Controls

20 Revision F

advertisement

Related manuals