Easystat EA906S User manual
Add to my manuals
30 Pages
Easystat EA906S is a 6KVA Standard model UPS system that provides reliable power protection for your critical equipment. It features an intelligent LCD display that provides real-time information about the UPS status, input and output voltage, load level, and battery capacity. The EA906S also includes advanced power management features such as AVR (Automatic Voltage Regulation), which protects your equipment from voltage fluctuations, and EPO (Emergency Power Off), which allows for safe shutdown in the event of an emergency. With its compact design and long battery backup time, the Easystat EA906S is the ideal UPS system for protecting your valuable electronics.
advertisement
1
2
1. Safety instructions
1.1 UPS safety instructions
●Before applying the UPS system, Please read through all safety information and operating instructions carefully. It’s recommended to save this manual properly for future reading.
●Do not install the UPS system near the water or in moist environments.
●Do not install the UPS system where it would be exposed to direct sunlight or near the heater.
●Place the UPS staying away from the wall for some distances, ensure enough space on each side of UPS, do not block ventilation holes in the UPS housing. Install it by following the instructions in the manual.
●Please do not open the UPS case as you will, there is a high risk of electric shocks inside.
●Do not connect to the equipment like hair dryer or electric heater, to ensure the safety for the UPS.
●Do not use liquid extinguisher if there is a fire, a dry powder extinguisher is recommended.
Attention:
UPS has high voltage inside, for personal safety, please do not repair by yourself. If any questions, please contact local service center or dealer.
1.2 Battery safety instructions
●Battery life cycle will be shortened as environment temperature rise. Replacing battery periodically can help to keep UPS in normal state and assure backup time required.
●Battery replacement should be done by authorized technician. If you want to replace the battery cable, please purchase it from our local service center or distributors to avoid fever and lighter which can cause fire from inadequate power capacity.
●Batteries may cause electric shocks and have a high short-circuit current, for human being safety, please follow the specifications as below when replace the batteries:
A. Remove wristwatches, rings and other metal objects
B. Use only tools with insulated grips and handles
C. Wear insulated shoes and gloves
D. Do not put the metal tools or parts on the battery
E. Before disconnecting the terminals on battery, please cut off all the loads to battery first.
●Do not dispose of the batteries with fire so as to avoid explosion.
●Don’t open the battery, electrolyte inside will do harm to eyes and skin. Please use plenty of clean water to wash if touching and go to see a doctor.
●Do not connect the positive pole and negative pole directly, otherwise it cause electric shocks or will be on fire.
●The battery circuit is not isolated from the input voltage, high voltage may occur between the battery terminals and ground, before touching, please verify no voltage is present.
2. Features
2.1 Unpacking inspection
●Open the UPS package, please check the enclosed accessories including user manual, RS232 communication cable, USB cable and CD-ROM.
●Check the UPS if anything damaged in transport. If find something damaged or parts missing, do not power on, please turn to the carrier and dealer.
●To determine whether this UPS is the model you want to buy. Check the model name showed both on the front panel and rear panel of UPS to confirm.
3
Model
EA906S
EA906H
EA9010S
EA9010H
EA9015H
EA9020H
Type
6KVA Standard model
6KVA Long backup model
10KVA Standard model
10KVA Long backup model
15KVA Long backup model
20KVA Long backup model
Note:
Please save the packaging box and packaging materials for future transport use. As a heavy product, please transit the UPS with care.
2.2 UPS rear panel view
USB
Parallel
Port
Intelligent
Slot
PARALLEL PORT
INTELLIGENT SLOT
USB
RS232
EPO
Parallel
Port
Intelligent
Slot
BAT_NTC
Fan
INPUT BREAKER
ON
Input
Breaker
OFF
WARNING
HIGH LEAKAGE CURRENT
EARTH CONNECTION ESSENTIAL
BEFORE CONNECTING SUPPLY
Input
Breaker
ON
INPUT BREAKER
OFF
WARNING
HIGH LEAKAGE CURRENT
EARTH CONNECTION ESSENTIAL
BEFORE CONNECTING SUPPLY
DO NOT OPEN EXCEPT
QUALIFIED TECHNICIAN
Manual
Bypass
Switch
Terminal
Block
Terminal
Block
USB
BAT_NTC
BAT_NTC
RS232
EPO
Fan
DO NOT OPEN EXCEPT
QUALIFIED TECHNICIAN
Manual
Bypass
Switch
RS232
EPO
Parallel
Port
PARALLEL PORT
INTELLIGENT SLOT
Intellengent
Slot
Fan
Input
Breaker
Battery
Breaker
BAT_NTC
BAT_NTC
INPUT
BREAKER
ON
BATTERY
BREAKER
ON
WARNING
HIGH LEAKAGE CURRENT
EARTH CONNECTION ESSENTIAL
BEFORE CONNECTING SUPPLY
DO NOT OPEN EXCEPT
QUALIFIED TECHNICIAN
Manual
Bypass
Switch
Terminal
Block
Ext.Battery
a. 6KVA &10KVA Long back up b. 15KVA &20KVA Long back up c .6KVA & 10KVA Standard type
Note: Due to the technology upgrading and development, goods and diagrams might have some differences.
4
3. Installation instructions
3.1 Attention items of installation
●The UPS installation environment must be with good ventilation, away from water, flammable gases and corrosive entities.
●Do not lie down the UPS against the wall so that front and side panel air intake hole, rear panel air outtake hole will be unobstructed.
●The peripheral environment temperature around the UPS should be within 0 ℃ ~ 40 ℃.
● If dismantling the machine at low temperatures, there may be condensation droplets, users can not install or operate it before UPS completely got dry both inside and outside, otherwise there will be danger of electric shocks.
● Place the UPS near the mains socket so that can cut off AC mains without any delay at any emergent case.
●Make sure the load connect to the UPS is off when users connect the load to UPS, and then turn on the load one by one later.
●Please connect the UPS with the socket which is over-current protected. Do not connect the UPS with the socket which rated current is less than the Maximum input current of the UPS.
●All the power socket should be configured with earthing device for safety.
●UPS could be electrified or powered no matter the input power cable is tied or not, even when the UPS is off.
The only way to cut off the output is switching off the UPS and disconnecting the mains power supply.
●For all standard type UPS, it is advised to charge the battery over 8 hours before used. Once the AC mains power energizes the UPS, it will automatically charge the battery. Without prior charging, UPS output remains as usual but with shorter back-up time than normal.
●When connected to motor, display equipment, laser printer etc, UPS power selection should be based on the startup power of the load which is usually twice as rated power.
●When wiring, please ensure input cables and output cables are connected firmly.
●If install a leakage current protective switch, please install it on output cable.
●For EA900II 6-20K Series UPS, before installing, prepare wires for terminal block of the UPS based on the following tables.
Wiring spec
Model Three-phase
Input
Single-phase
Input
Output Battery
Non-isolated
Neutral
Ground
6KVA S 6mm2 6mm2 6mm2 6mm2 6mm2 6mm2
6KVA H
10KVA S
10KVA H
15KVA H
6mm2
10mm2
10mm2
16mm2
6mm2
10mm2
10mm2
16mm2
6mm2
10mm2
10mm2
16mm2
6mm2
10mm2
10mm2
16mm2
6mm2
10mm2
10mm2
16mm2
6mm2
10mm2
10mm2
16mm2
20KVA H 20mm2 20mm2 20mm2 20mm2 20mm2 20mm2
Note: When connecting, please make sure to connect input cables and output cables with terminals firmly.
When the input is three-phase, if the UPS is working on Bypass mode, the total current goes through phase R, so the line widths of phase R must be the same as output. When the input is single-phase, before doing input connection, users have to use two short wires to connect R&S and S&T.
3.2 Output connection
Output connection is configured with terminal blocks. Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid the hazards of electric shock or fire.
5
Note: Do not use the wall receptacle as the input power source for the UPS, which rated current is less than the UPS’s maximum input current. Otherwise the receptacle may be burned and destroyed.
INPUT
INPUT
L
OUTPUT
N
++
BATTERY
--
A B C N
L
OUTPUT
N
A B C N a. 6KVA &10KVA Long back up terminal blocks b. 6KVA &10KVA Standard type terminal blocks
A B
INPUT
C N
++
BATTERY
--
L
OUTPUT
N c. 15KVA &20KVA terminal blocks
3.3 Parallel system of 6-20K UPS installation
Only 6-20K UPS and containing parallel ports can do parallel operation, other types is not supported.
N+X parallel structure is the most reliable power supply structure at present, N stands for the minimum number of UPS for the load, X stands for the number of redundant UPS,X absolutely means how many UPS could be malfunctioning at the same time and the parallel UPS system is still steady. The larger X is, the system is more reliable. N+X is the best method for high reliability. Just install a little more simple accessories, at most 8 UPS could work together to form a flexible parallel system.
This structure of power supply system increases the power safety and reliability. For example, two single
UPS make up a parallel system to load averagely, when one is malfunctioning, another one can take all the load independently. It allows isolation repairs for malfunctioning UPS, and according to users own different requirements, every single UPS could install manual maintenance bypass switch.
3.3.1 Parallel system installation
The function of parallel operation is an optional function of UPS, users can purchase parallel function parts
(including parallel card and parallel wire) and contact service personnel to install. At most 8 UPS work together by using parallel wires to form a flexible parallel system. Each UPS should be equipped individual battery pack.
>Parallel system installation requirement:
●Install parallel wire, users need to purchase a specific parallel wire from our company, it’s not recommended to use other type parallel wires. There are 2m length and 5m length to be chosen.
●Prepare wires for terminal block of the UPS based on the wiring spec table above in attention items.
●Each UPS input wiring please comply with the requirements of single UPS wiring.
●Every UPS is recommended to connect together to one common utility power terminal block.
●The output cables of each UPS are recommended to connect together on a common terminal block, then output to the load.
●Each UPS should be equipped individual battery pack.
●Wiring installation for parallel UPS system please refer to the wiring diagrams are given below, switches of
6KVA should withstand more than 50A/250VAC, and switches of 10KVA should withstand more than
6
80A/250VAC, and switches of 15KVA should withstand more than 100A/250VAC, and switches of 20KVA should withstand more than125A/250VAC.
●Output wiring length requirements: when the distance between the load and each UPS is less than 20 meters, the length difference of cables to the load should be less than 20%; when the distance between the load and each UPS is more than 20 meters, the length difference of cables to the load should be less than
10%.
>Installation procedure:
① Install parallel wires. Two UPS to form an UPS parallel system , in order to ensure the reliability of the parallel system, there is only one way to wire two UPS, use two parallel wires to connect two UPS like the diagram showing below, connection looks like a circle. If three or more than three UPS are needed, the connection is similar, you can refer to the diagram as below. How many UPS unit, how many parallel wires you need.
INPUT BREAKER
OFF
WARNING
HIGH LEAKAGE CURRENT
EARTH CONNECTION ESSENTIAL
BEFORE CONNECTING SUPPLY
DO NOT OPEN EXCEPT
QUALIFIED TECHNICIAN
INPUT BREAKER
OFF
WARNING
HIGH LEAKAGE CURRENT
EARTH CONNECTION ESSENTIAL
BEFORE CONNECTING SUPPLY
DO NOT OPEN EXCEPT
QUALIFIED TECHNICIAN
Parallel system of two UPS wiring
INPUT BREAKER
ON OFF
WARNING
HIGH LEAKAGE CURRENT
EARTH CONNECTION ESSENTIAL
BEFORE CONNECTING SUPPLY
DO NOT OPEN EXCEPT
QUALIFIED TECHNICIAN
INPUT BREAKER
ON
OFF
WARNING
HIGH LEAKAGE CURRENT
EARTH CONNECTION ESSENTIAL
BEFORE CONNECTING SUPPLY
DO NOT OPEN EXCEPT
QUALIFIED TECHNICIAN
INPUT BREAKER
ON OFF
WARNING
HIGH LEAKAGE CURRENT
EARTH CONNECTION ESSENTIAL
DO NOT OPEN EXCEPT
QUALIFIED TECHNICIAN
Parallel system of three UPS wiring
Caution: For three UPS parallel system or more than three unites system type, please remove the short pin CN3 on the parallel card as following pictures, Only keep the first unit and the last unit shot pin(CN3) connected and remove the rest ones. Open the UPS cover, find the parallel card, it’s installed on the rear panel. Take off the short pin CN3, then screw the cover back. It’s advisable to contact to local dealer to operate, if you have to operate by yourself, please be sure that you have cut off all the electrical connection, be careful the electric shocks from the UPS inside.
7
Parallel Card
Parallel Card
6KVA &10KVA Parallel Card 15KVA &20KVA Parallel Card
Short Pin
②Connect output cables of all UPS together to a common terminal block.
③Connect input cables of all UPS together to one common utility power terminal block.
Ut i l i t y power suppl y
I nput common t er mi nal bl ock
Out put common t er mi nal bl ock
Load
Load Load Load
Parallel UPS system view
. . .
8
R S T
N L
N
BAT+ BAT-
R S
T N L
N
BAT+ BAT-
R S T N L N
INPUT
BAT+ BAT-
BAT1
OUTPUT
BAT2
Wiring diagram for two UPS parallel system
R S T
N L
N
BAT+ BAT-
R S T
N L
N
BAT+ BAT-
INPUT BAT1 BAT2
OUTPUT
BAT3
Wiring diagram for thee UPS parallel system
④ If the UPS is the standard type, each UPS has batteries inside already. If the UPS is the long-run type, each UPS should be equipped a individual battery pack.
⑤ After installation, check all the wiring carefully, be sure to confirm correct, then can operate the system.
3.3.2 Parallel system operation and maintenance
General operation of parallel system, please refer to the operation instruction of single UPS. Before starting the system, need to set up different ID for each UPS, specific settings please refer to the instruction of ID setting which is given in single UPS panel function setting.
>Turn on the parallel system
● Start the system with mains power: After inputting the mains power,turn on any one UPS of system, others will start by themself at same time. All UPS will enter into Line mode.
●Start the system without mains power: Make sure the battery pack is connected well and the breaker is in
“ON” position. There are two ways to start the UPS parallel system without utility power supply:
A: Press the key on each UPS, make each LCD of each UPS light up, then turn on any one UPS of system, others will start by themself at same time. All UPS will enter into BAT mode.
B: Turn on UPS one by one.
>Turn off the parallel system
Hold on the OFF KEY of any one UPS of system for more than 4 seconds, it would turn off the whole parallel system. Hold on the OFF KEY of any one UPS of system for more than 1 second(less than 4 seconds), it would turn off single UPS you choose, of course if you need to turn on it again or turn on any other single
UPS of the system, just press ON KEY of that UPS to start it.
>Parallel system maintenance
●Parallel system maintenance please follow the maintenance of single UPS.
9
●If one UPS of parallel system is malfunctioning, first of all, turn off the malfunctioning UPS, then cut off the input power to the faulty UPS and disconnect the output of faulty UPS to the parallel system, make sure that there is no electrical connection with malfunctioning UPS, after all of those, it’s safe to do operation.
3.4 External battery connection procedure for long back up type
●For different UPS type, users are instructed to configure different battery voltage as below sheet. More or less units are forbidden, or else something abnormal or faulty will appear.
Type
6KVA
10KVA
15KVA
20KVA
Battery Quantity
(unit)
16/20
16/20
16/20
16/20
Battery Voltage
(volt)
192V/240V
192V/240V
192V/240V
192V/240V
Note: there are two battery pack options for UPS, 16 units and 20 units. Users can choose the different battery pack voltage in accordance with different requirements. The default units of batteries to UPS is 16, and users can not connect 16 batteries to UPS if the UPS should be connected 20 units. Please strictly follow the procedure of batteries connection, or will get electric shocks.
1. Set the battery switch at ‘OFF’ position, then install batteries in series.
2. Connecting the cables to batteries firstly, or you may get electric shocks if you connect the cables to UPS firstly. You’d better connect the red cable to battery positive pole ‘+’, black to negative pole ‘-’, so that it would be much easier to distinguish.
3. Select proper cables to connect the batteries and UPS is very important, and there should be a switch connected between the battery pack and UPS.
4. Finally, without any load, set on the battery switch which is connected between the UPS and the battery pack, so that UPS can get connected to batteries, then switch in the mains power, after doing all of those, the batteries will be charged by the UPS automatically.
To UPS terminal blocks
Positive
Negative
Battery
Breaker
16/20PCS
+
BAT
-
+
BAT
-
+
BAT
-
+
BAT
-
3.5 Network functions
3.5.1 Communication port
Users could monitor the UPS system through the communication port such as standard RS232 port and
10
standard USB port with computer. With a communication wire to connect UPS and computer, could simply achieve UPS management.
☆RS232 port:
Foot
Explanation
1 empty
2 3 4 5 6 7 send receive empty ground empty empty
8 empty
9 empty
☆USB port:
Foot
Explanation
1
+5V
2 date+
3 date-
4
GND
3.5.2 EPO port
EPO is short for Emergency Power Off, EPO port is on rear panel of UPS, it’s green, in some emergent cases, users could cut off the output of UPS immediately by operating EPO port. Wiring diagram as below:
Normally, pin1 and pin2 are connected so that the machine can be working normally. When some emergencies happen, and when users do have to cut off the output, just need to disconnect the connection between pin1 and pin2, or there is a anther useful simple way is pulling it out.
3.5.3 Intelligent card (option)
This series High frequency online UPS supply a intelligent slot on rear panel, it’s for SNMP card, dry contact and USB card, users could insert any type intelligent card from those three into it to monitor and manager the
UPS. You don’t have to turn off the UPS when you install the intelligent card. Procedure as following:
●Fist of all, remove the intelligent slot cover;
●Then insert the intelligent card(SNMP card, dry contact or USB card);
●Last, screw the intelligent card back.
> SNMP card (option)
SNMP card on UPS is compatible with the most software, hardware and network operating system, it is a network management of UPS, with this function, UPS can login on internet , which can supply information of
UPS status and input power, and even possible to control UPS via net management system.
> Dry contact card (option)
11
Insert the dry contact card into the intelligent slot, it’s another type function of intelligent monitoring.
Foot Definition
PIN1
PIN2
ON:UPS is malfunctioning
ON:Alarm(system failure)
PIN3
PIN4
Ground
Remote shutdown
PIN5
PIN6
PIN7
PIN8
Common
ON:Bypass mode
ON:Battery low
ON:Inverter mode;
OFF:Bypass mode
PIN9
ON:No AC power in
> RS485 card (option)
RS485 card is also designed for this series UPS, A(+) and B(-) on the right are the output of RS485.
All above, for more information, please contact to the local dealer.
3.6 Maintenance switch (option)
UPS with maintenance switch(option) can be maintained online. Open the maintenance bypass switch cover you can see a maintenance switch if the UPS has this function.
When you need to maintain or repair the UPS online, follow the procedure as below:
●Open the maintenance bypass switch cover, UPS will transfer to BYPASS mode automatically;
●Set the switch at “BYPASS” position;
●Now you can maintain or repair the UPS;
●After finishing the maintenance operation, set the switch back to “UPS” position, and put the cover back.
Complete all the steps above, you are done the maintenance.
3.7 Battery pack selecting
There are two options of battery group quantity for users to choose, 16 units and 20 units. The default quantity is 16 units, but this series UPS are also allowed to connect with 20 units batteries. When users want to apply 20 units batteries group for this series UPS, need to open the UPS case and find the control board and the charger, then operate the short pins on control board and charger board.
12
Short pin
Short pin
Control board Charger board
Battery group Operation
16 units batteries
A. Remove the short pin(J16) off the control board;
B. Insert the short pin(middle of CN7) of the charger board.
20 units batteries
A. Remove the short pin(middle of CN7) of the charger board;
B. Insert the short pin(J16) of the control board.
Note: for long-run type UPS, there are two chargers, users have to operate two charger board.
4. Panel function and operation
The operation is simple, operators only need to read the manual and follow the operation instructions listed in this manual without any special training.
4.1 Keys function
※ ON K E Y (
+ )
Press and hold the two keys for more than half a second to turn on the UPS.
※ OFF K E Y (
+ )
Press and hold the two keys for more than half a second to turn off the UPS.
※ TEST/MUTE K E Y (
+ )
13
Press and hold the two keys for more than 1 second in Line mode or ECO mode or CUCF mode: UPS runs the self-test function.
Press and hold the two keys for more than 1 second in battery mode: UPS runs the mute function.
※ INQUIR ING K E Y (
, )
Non-function setting mode:
Press and hold or for more than half a second (less than 2 seconds): display the items orderly.
Press and hold for more than 2 seconds: Circularly and orderly display the items every 2 seconds, when press and hold the key for some time again, it will turn to output status.
Function setting mode:
Press and hold the key or for more than half a second (less than 2 seconds): Select the set option.
※ FUNCTION SETTING KEY
Non-function setting mode:
Press and hold the key for more than 2 seconds: Function setting interface.
Function setting mode:
Press and hold the key for more than half a second (less than 2 seconds): Enter the function setting option.
Press and hold the key for more than 2 seconds: exit from this function setting interface.
4.2 LED Function
Number LED Explanation
①
②
③
Inverter LED
Battery LED
Bypass LED
Inverter green LED is on: UPS is normally powered by Line mode or ECO mode or BAT mode.
Battery yellow LED is on: Battery mode.
Bypass yellow LED is on: Bypass mode or ECO mode, etc.
④
Warning LED Warning red LED is on: UPS fault. For example: Overload beyond the allowed time, inverter fault, BUS fault, over temperature fault, etc
PS: LED display detail in different mode is listed at the back.
4.3 LCD display function
LCD displays as following figure.
14
Icon display area
Digital display area
Working mode display area
※ Ico n d isp lay area:
A. The top diagram is for load and battery capacity indication, each grid of which represents 25%. When UPS is over load, the load light will blink the same as the battery light blink when the capacity of battery get low or battery disconnected.
B. The fan icon is for fan working indication; when fan normally runs, the icon will display rotation; if the fan is not connected or faulty, the icon blinks;
C. Press the mute button under the battery mode, buzzer icon will blink; it will disappear in other cases.
D. Fault icon will be on when UPS is in fault mode, otherwise it will not.
※ Dig ital d isp lay area:
A. Under none setting mode, it will display UPS output information when UPS normally runs in AC mode; other information like input, battery, load and temperature will be showed after pressing the inquiring key; Fault code will be told in fault mode.
B. Under setting mode, users could adjust different output voltage, activate ECO mode, activate CUCF mode, select an ID number and so on by operating function setting key and inquiring keys.
※ Mode display area:
A. This area will display the power capacity of the machine after starting the UPS within 20 seconds.
B. After over 20 seconds, this area will display the working mode of the machine. Such as STDBY(standby
Mode), BYPASS(Bypass Mode), LINE(AC Mode), BAT(Battery Mode), BATT(Battery Self Test Mode ),
ECO(Economic mode), SHUTDN(Shutdown mode), CUCF(Constant Voltage and Constant Frequency
Mode).
4.4 Single UPS turn On/Off operation
4.4.1 Turn on operation
> Turn on the UPS on line mode
①Once mains power is plugged in, the UPS will charge the battery, at the m oment, LCD shows that the output voltage is 0, which means UPS has no output as default condition. If it is expected to have output of bypass, you can set the BPS “ON” by LCD setting menu.
② Press and hold the ON key for more than half a second to start the UPS, then it will start the inverter.
③Once started, the UPS will perform a self-test function, and LED will light and go off circularly and orderly.
15
When self-test finishes, it will come to online mode, the corresponding LED lights, UPS is working in line mode.
> Turn on the UPS by DC without mains power
①W hen m ain power is disconnected, press and hold the ON key for more than half a second to start UPS.
②The operation of UPS in the process of start is almost the sam e as that when m ains power is on. After the self-test finishes, the corresponding LED lights and UPS are working in battery mode.
4.4.2 Turn off operation
> Turn off the UPS in line mode
①Press and hold the OFF key for more than half a second to turn off the UPS and inverter.
②After UPS shutting down, LE D goes out and there is no output. If output is needed, you can set BPS “ON” on LCD setting menu.
> Turn off the UPS in DC mode without mains power
①Press and hold the OFF key for more than half a second to turn off the UPS.
②W hen turning off the UPS, it will do self-test first. LED lights go out circularly and orderly until there is no display on the panel.
4.5 Single UPS self-test/mute test operation
① W hen UPS is in LINE Mode, press and hold the self-test/mute key for more than 1 second, LED light will go off circularly and orderly. UPS comes to self-test mode and tests its status. It will exit automatically after finishing test.
② W hen UPS is in BAT Mode, press and hold the self-test/mute key for more than 1 second, the buzzer stops beeping. If you press and hold the self-test/mute key for one more second, it will restart to beep again.
4.6 Single UPS panel function setting
UPS has setting function. It can run the setting in any mode. After setting, it will become effective at once when meets some standards. The set information can be saved only when the battery connected and normally turning off the UPS.
4.6.1 ECO mode setting
① E nter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, press and hold the inquiring key ( , ) for more than half a second(less than 2 seconds), select the function setting, choose output voltage setting interface, at the moment, the letters
“ECO” will flash.
② E nter the ECO setting interface. Press and hold the function setting key for more than half a second(less than 2 seconds), then come to setting interface of ECO, at this time, the letters “ECO” will not flash any more. The “ON” (or OFF) will flash. Press and hold the inquiring key ( , ) for more than half a second (less than 2 seconds) to determine whether the ECO function is used or not. If used, the corresponding word is “ON”, if not, the word is “OFF”. It can be determined by yourself.
③ Confirm the ECO selecting interface. After selecting ON or OFF, press and hold the function setting key for more than half a second (less than 2 seconds). Now, the ECO setting function is completed and the “ON” or “OFF” will light without flash.
16
④ E xit from the setting interface. Press and hold function setting key the setting interface and return to main interface. for more than 2 seconds, exit from
4.6.2 Input methods setting
① E nter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, press and hold the inquiring key ( , ) for more than half a second(less than 2 seconds), select the function setting, choose output voltage setting interface, at the moment, the letters
“IPP” will flash.
② E nter the IPP setting interface. Press and hold the function setting key for more than half a second(less than 2 seconds), then come to setting interface of IPP, at this time, the letters “IPP” will not flash any more, the numerical value next to the IPP will flash. Press and hold the inquiring key ( , ) for more than half a second (less than 2 seconds) to select the numerical value. There are two Input methods, the value
‘1’ means single phase input, the value ‘3’ means three phase input. The default input method is single phase.
③ Confirm the IPP selecting interface. After selecting input m ethod, press and hold the function setting key for more than half a second (less than 2 seconds). Now, the IPP setting function is completed and the value next to IPP will light without flash.
④ E xit from the setting interface. Press and hold function setting key the setting interface and return to main interface. for more than 2 seconds, exit from
4.6
.3 Output voltage setting
① E nter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, press and hold the inquiring key ( , ) for more than half a second(less than 2 seconds), select the function setting, choose output voltage setting interface, at the moment, the letters
“OPU” will flash.
17
② E nter the output voltage setting interface. Press and hold the function setting key
for more than half a second(less than 2 seconds), then come to setting interface of output voltage OPU, at this time, the letters
“OPU” will not flash any more. The numerical value next to the OPU will flash. Press and hold the inquiring key ( , ) for more than half a second (less than 2 seconds), select the numerical value in accordance with “OPU” function. The provided voltages are 208V, 220V, 230V, 240V, you can choose anyone by yourself (The default value is 220V).
③ Confirm the output voltage setting interface. After selecting num erical value, press and hold the function setting for more than half a second (less than 2 seconds). Now, the OPU setting function is completed and the numerical value will light without flash.
④ E xit from the setting interface. Press and hold function setting key for more than half a second (less than 2 seconds), exit from the setting interface and return to main interface.
4.6.4 Low battery voltage shutdown point setting
① Enter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, Press and hold the inquiring key ( , ) for more than half a second(less than 2 seconds), select the function setting, choose battery voltage setting interface, at the moment, the letters “bat” will flash.
② Enter the battery voltage selecting interface. Press and hold the function setting key for more than half a second(less than 2 seconds), then come to setting interface of battery voltage, this time, the numerical value will flash. Press and hold the inquiring key ( , ) for more than half a second (less than 2 seconds), select the numerical value in accordance with “battery” function. The provided voltages are 10V,
10.2V, 10.5V, numbers stand for the voltage of each battery, you can choose anyone by yourself (The default is 10V), anyone has been chosen, under BAT mode, UPS will shutdown when its battery voltage achieve the voltage you chose.
③ Confirm the battery voltage selecting interface. After selecting numerical value, press and hold the function setting , for more than half a second (less than 2 seconds). Now, the battery setting function is completed and the numerical value will light without flash.
④ E xit from the setting interface. Press and hold function setting key for more than half a second (less than 2 seconds), exit from the setting interface and return to main interface.
18
4.6.5 Frequency converter mode setting
① CUCF mode only can be set in STDBY mode. In STDBY mode, enter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, Press and hold the inquiring key ( , ) for more than half a second(less than 2 seconds), select the function setting, choose battery voltage setting interface, at the moment, the letters “CF” will flash.
② E nter the CF setting interface. Press and hold the function setting key for more than half a second(less than 2 seconds), then come to setting interface of CF, at this time, the letters “CF” will not flash any more.
The “ON” (or OFF) will flash. Press and hold the inquiring key ( , ) for more than half a second (less than 2 seconds) to determine whether the CF function is used or not. If used, the corresponding word is
“ON”, if not, the word is “OFF”. It can be determined by yourself.
③ Confirm the CF selecting interface. After selecting ON or OFF, press and hold the function setting key for more than half a second (less than 2 seconds). Now, the CF setting function is completed and the “ON” or “OFF” will light without flash.
④ E xit from the setting interface. Press and hold function setting key for more than 2 seconds, exit from the setting interface and return to main interface.
⑤After setting CF at “ON”, UPS would be back in STDBY Mode. The default value of CF is OFF.
4.6.6 Output frequency setting in CUCF mode
①Output frequency only can be set when CUCF mode is ON.
②In STDBY m ode, enter the setting interface. Press and hold the function setting key seconds, then come to setting interface, Press and hold the inquiring key ( , for more than 2
) for more than half a second(less than 2 seconds), select the function setting, choose battery voltage setting interface, at the moment, the letters “OPF” will flash.
③ E nter the OPF setting interface. Press and hold the function setting key for more than half a second(less than 2 seconds), then come to setting interface of OPF, at this time, the letters “OPF” will not flash any more. The “OFF” (or 50HZ, 60HZ) will flash. Press and hold the inquiring key ( , ) for
19
more than half a second (less than 2 seconds) to determine whether the CF function is used or not. If used, select 50HZ or 60HZ according to you. It is determined by yourself, the default value is 50HZ.
④ Confirm the OPF selecting interface. After selecting 50HZ or 60HZ, press and hold the function setting key for more than half a second (less than 2 seconds). Now, the OPF setting function is completed and the “50HZ” or “60HZ” will light without flash.
⑤E xit from the setting interface. Press and hold function setting key for more than 2 seconds, exit from the setting interface and return to main interface.
4.6.7 ID setting
① E nter the setting interface. Press and hold the function setting key for more than 2 seconds, then come to setting interface, press and hold the inquiring key ( , ) for more than half a second(less than 2 seconds), select the function setting, choose output voltage setting interface, at the moment, the letters “Id” will flash.
② E nter the output voltage setting interface. Press and hold the function setting key
for more than half a second(less than 2 seconds), then come to setting interface of ID, at this time, the letters “Id” will not flash any more. The numerical value next to the “Id” will flash. Press and hold the inquiring key ( , ) for more than half a second (less than 2 seconds), select the numerical value. The provided ID numbers are 1,
2, 3, 4, 5, 6, 7, 8, you can choose anyone by yourself (The default value is 1).
③ Confirm the output voltage setting interface. After selecting num erical value, press and hold the function setting for more than half a second (less than 2 seconds). Now, the ID setting function is completed and the numerical value will light without flash.
④ E xit from the setting interface. Press and hold function setting key for more than half a second (less than 2 seconds), exit from the setting interface and return to main interface.
Note: ID only can be set before doing parallel operation.
4.7 Parameters inquiring operation
20
Press and hold the inquiring key or for more than half a second(less than 2 seconds) to inquire about items. The inquired items include input, battery, output, load and temperature. The displayed items on LCD screen are showed as following:
Output:Display the output voltage and output frequency of the UPS. As the following graphic shows, the output voltage is 220V, the output frequency is 50Hz.
Load: Display the numerical value of the active power (WATT) and apparent power (VA) of the load. For example, as the following graphics shows: the WATT of the load is 9KW, VA is 10KVA (when disconnect load, it is a normal phenomenon to show a small numerical value of WATT and VA).
Temperature: Display the maximum temperature of the components in the UPS. As the following graphics shows: the maximum temperature is 40℃.
Input: Display the voltage and frequency of the input. As the following graphics shows: the input voltage is
220V, input frequency is 50Hz.
21
Battery: Display the voltage and capacity of the battery (determined by type). As the following graphics shows: the battery voltage is 192V, the capacity of battery is 100% (the capacity of battery is approximately reckoned according to the battery voltage).
Press and hold the inquiring key for more than 2 seconds, LCD begins to display the items circularly and orderly which transfer to another every 2 seconds. Press and hold the key for some time again within 30s, it will return to output status.
5. Working mode introduction
5.1 Bypass mode
LED indications on front panel in bypass mode are as following:
Bypass yellow LED is on, the buzzer beeps once every 2 minutes. The warning red LED is on when beeping, what LCD displays depending on the exact load and battery capacity.
Turn to bypass mode under the following two conditions:
① Turn off the UPS line mode while start the bypass output.
② Overload in line mode.
Note: When UPS is working in bypass mode, it has no back up function.
5.2 Line mode
LED indications on front panel in line mode or CUCF mode are as following: The inverter green LED is on.
When input AC mains correspond to the working conditions, UPS will work in line mode.
5.3 Battery mode
LED indications on front panel in battery mode are as following: both the inverter green LED and battery yellow LED is on, the buzzer beeps once every 4 seconds. The warning red LED will be on while beeping.
When the mains power is low or unstable, UPS will turn to battery mode at once.
5.4 ECO mode
LED indications on front panel in ECO mode are as following: both the inverter green LED and bypass yellow
LED are on.
22
When the input mains meets the input range of the ECO mode and the ECO function is on, the UPS will works in ECO mode. If input AC mains exceed the range of ECO several times within one minute but stays in inverter input range, UPS will work in AC inverting mode automatically.
Note: On ECO mode, when the UPS switches to Inverter mode (including Line mode and BAT mode) from
ECO mode, 15ms interrupt probably be happened.
5.5 Fault mode
LED indications on front panel in Fault mode are as following: warning red LED is on and LCD display fault code and related icon.
Fault mode (LCD interface on which the fault code display)
When UPS has faulted. The warning LED is on and the buzzer beeps. UPS will turn to fault mode. UPS cuts off the output and LCD display fault codes. At the moment, you can press the mute key to make the buzzer stop beeping temporarily to wait for maintenance. You can also press the OFF key to shut down the UPS when confirmed that there is no serious fault.
6. The warning code list of the LED light and display panel
Appendix 1: The table of the fault code
Fault code
0、1、2、3、4
5、6、7、8、9
10、11、12、13、14
15、16、17、18、19
20、21、22、23、24
25、26、27、28、29
30、31、32、33、34
35、36、37、38、39
40、41、42、43、44
45、46、47、48、49
50、51、52、53、54
55、56、57、58、59
Fault type
Bus high
Bus low
Bus unbalance
Bus soft start fail
Inverter soft start fail
Inverter high
Inverter low
Bus discharge fail
Over heat
OP(inverter) shorted
Overload
Negative output power
Bypass output
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Note
23
60、61、62、63、64
65、66、67、68、69
75、76、77、78、79
80、81、82、83、84
85、86、87、88、89
90、91、92、93、94
95、96、97、98、99
100、101、102、103、104
Shutdown fault
BUS shorted
Communication fault
Relay fault
AC input SCR fault
CAN fault
ID conflict
Incompatible type
Appendix 2: Table for working status
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No unused
S/N Working status
LED on Front panel
Normal Battery Bypass Fault
1 Inverter mode (mains power)
Mains power voltage
●
Mains power high/low voltage protection, switch to battery mode
2 Battery mode
Battery voltage - normal
Warning for abnormal voltage of battery
3 Bypass mode
Mains power –
●
●
● normal
(under
●
●
★
●
★
★
★
★
Alarm beep
N
One beep / 4 sec
One beep / 4 sec
One beep / sec
One beep / 2 mins
Note
Bypass
)
Mains power – high voltage warning
(under Bypass)
Mains power – low voltage warning
(under Bypass)
4 Warning for battery disconnected
Bypass mode
Inverter mode
Power on / Switch on
●
5 Output overload protection
●
●
●
★
★
★
★
One beep / 4 sec
One beep / 4 sec
One beep / 4 sec
One beep / 4 sec
6 beeps
24
6
Warning for mains power overload
Protect operation for mains power mode overload
Warning for battery overload
Protect operation for battery mode overload
Warning for bypass mode overload
7
Fans fault(fan icon
)
●
●
●
▲
●
●
▲
●
●
▲
★
●
★
●
★
★
2 beeps / sec
Long beep
2 beeps / sec
Long beep
One beep / 2 sec
One beep / 2 sec
8 Faults mode
●
Long beep
● LED indicator lights long time
★ LED indicator flicker
▲ LED indicator status depends on other conditions
Note: End user need to provide below information when require to maintain the UPS.
UPS Model No. & Serial No.
Date of fault occurrence.
Fault detail (LED status, noise, AC power situation, load capacity, for long back up type, battery capacity configuration is also necessary.)
7. Trouble shooting
When the system runs in failure mode, the LCD will show as below:
Fault icon
Fault code
Explicit Troubleshoot Introduction Sheet
Trouble indication
Fault LED on, audible buzzer
Persistently alarm, the fault code is 00-14
Failure point
Bus bar voltage fault
Solution
Please test the bus bar voltage or contact the supplier.
25
Fault LED on, audible buzzer persistently alarm, the fault code is15-24
Soft start fault
Fault LED on, audible buzzer persistently alarm, the fault code is
25-39
Inverter voltage fault
Please check the soft start up circuit, especially the soft start resistance or contact the supplier directly.
Please contact the supplier.
Fault LED on, audible buzzer persistently alarm, the fault code is
40-44
Fault LED on, audible buzzer
Persistently alarm, the fault code is 45-49
Over temperature inside
Output short-circuited
Please make sure the UPS didn’t get overload, and the fan vent was not obstructed, as well as the indoor temperature is not high.
Leave alone the UPS 10 minutes for cooling, and restart it. If failure remains, please contact the supplier.
Turn of the UPS and disconnect all the load, make sure there no any fault or internal short circuit of the load.
And then restart the UPS, if failure still, please contact the supplier.
Fault LED on, audible buzzer persistently alarm, the fault code is
50-54
Fault LED on, audible buzzer
Persistently alarm, fan icon in the
LCD flickers
Over load
Fan fault
Pressing time too short
Please check the load level and disconnect the noncritical devices, recount the total capacity of your load and reduce the load to the UPS.
Please check whether the load device has fault or not.
Fault LED on, audible buzzer persistently alarm, the fault code is
55-59
Fault LED on, audible buzzer persistently alarm, the fault code is
60-64
Fault LED on, audible buzzer persistently alarm, the fault code is
65-69
Negative output power Please contact the supplier.
Power fault
BUS short-circuited
Please Check whether the input & output power normal or not, contact the supplier if it is abnormal.
Please contact the supplier.
Please check whether the fans connect well, is the fan plugged and is the fan broken? If all above condition is OK, please contact the supplier.
Please press the power key more than 2 seconds to start the UPS.
UPS fail to start when operate
“On” key
The input connection is not ready or
UPS internal battery disconnect
UPS internal system fault
Please connect the input well, if the battery voltage is too low, please disconnect the input and start the UPS with no-load.
Please contact the supplier.
26
Back up time become short
Battery undercharge
UPS overload
Battery maturing, capacity descend
Please keep the UPS battery recharging more than 3 hours
Please check the load level and disconnect the noncritical devices,
Please change new battery, contact your supplier to get the new battery and spare parts.
Please reset the circuit breaker by manual.
UPS doesn’t have any power go through even main power on
UPS input breaker disconnects
Input fuse broken or input method is inconsistent with the
IPP setting
Please check the fuse and IPP setting, and contact the supplier.
Attention: When the output is short-circuited, the action of the protection of the UPS will show up. Before turning off the UPS, please make sure to disconnect the entire load and cut off the AC mains power supply, otherwise will make the AC input short-circuit.
Appendix 1: EMC Level
The series product is designed to meet the below standard.
EMS
IEC61000-4-2(ESD)
IEC61000-4-3(RS)
IEC61000-4-4(EFT)
IEC61000-4-5(Surge)
EMI
GB9254-1998/IEC 62040-2
Level 4
Level 3
Level 4
Level 4
Class B
Appendix 2: Symbol instructions:
Symbols and significations
Symbol Significations
Caution
Danger! High Voltage!
Turn on
Turn off
Standby or Shutdown
AC
DC
Symbol Significations
Protect grounding
Alarm cancel
Overload
Battery inspection
Repeat
Display screen repeat key
Battery
Appendix 3: Specification Sheet
27
MODEL
Capacity
INPUT
Rated Voltage
Voltage Range
Frequency
Power Factor
BYPASS
Voltage Range
Frequency
OUTPUT
Voltage
Voltage Regulation
Frequency
Waveform
Crest Factor
Harmonic Distortion
Transfer Time
Overload Capability
EFFICIENCY
AC Mode
Battery Mode
ECO Mode
BATTERY
DC Voltage
Inbuilt Battery of Standard
Model
Charge
Current
Standard Model
Long Time Model
Typical Recharge Time
ALARM
Utility Failure
Battery Low
Overload
UPS Fault
ENVIRONMENT
Humidity
Noise Level
EA906II EA9010II EA9015II EA9020II
6KVA/5.4KW 10KVA/9KW 15KVA/13.5KW 20KVA/18KW
3/1: 360V/365V/380V/400V/415VAC;
1/1: 208V/210V/220V/230V/240VAC.
(Set up by LCD display)
3/1: Half load (190-520)±5VAC, Full load (277-520)±5VAC;
1/1: Half load (110-300)±5VAC, Full load (160-300)±5VAC.
40-70Hz±0.5% (Auto sensing)
3/1: ≥0.95;
1/1: ≥0.99.
160V-Rated output voltage+32V
50/60Hz±5Hz
208V/210V/220V/230V/240Vac Setting available via LCD
±1%
Synchronized with utility on AC mode; 50/60±0.1Hz on battery mode
Pure sine wave
3:1
≤2%(Linear load); ≤5%(Non-linear load)
AC mode to battery mode: 0ms
Inverter mode to bypass mode: 0ms
105%-125%: Transfer to bypass after 3mins;
125%-150%: Transfer to bypass after 30s;
>150%: Transfer to bypass after 100ms
≥93%
≥92%
≥98%
192V/240VDC
16*7AH
1A
16*9AH
7A
8 hours recover to 90% capacity
Beep/4s
Beep/1s
Beep Twice/1s
Long Beep
NO
20~90% RH @ 0~40℃(non-condensing)
≤58dB (1m) ≤60dB (1m)
28
MANAGEMENT
Standard RS-232 and USB
Optional SNMP
PHYSICAL
Dimension(mm) W*D*H
Packing Dimension(mm)
W*D*H
Net Weight(kg)
Supports Windows 98/2000/2003/XP/Vista/2008/7/8
Power management from SNMP manager and web browser
262×580×455(H),
262×580×732(S)
262×580×628(H)
355×682×615(H),
359×687×822(S)
25.0(H),
73.0(S)
25.5(H),
74.0(S)
359×687×717(H)
38.5(H) 39.0(H)
Gross Weight(kg)
28.5(H),
82.5(S)
29.0(H),
83.5(S)
47.0(H) 47.5(H)
Derate capacity to 70% in CUCF mode and to 90% when the output voltage is adjusted to 208Vac.
3/1 means three phase input and single phase output mode, 1/1 means single phase input and single phase output mode.
S means standard model, H means long backup time model.
29
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Key Features
- 6KVA power capacity
- Standard model with long battery backup time
- Intelligent LCD display provides real-time information
- AVR protection against voltage fluctuations
- EPO for safe shutdown in emergencies
- Compact design for easy placement
- Easy-to-use controls and intuitive interface