Type B Gas Vent - 3” to 12” Diameter

Installation Instructions

Installation Instructions

Type B Gas Vent

-

3" to 12" Diameter

Please read and understand the requirements before proceeding.

Hart & Cooley Type B gas vent pipe and fittings are

Underwriters Laboratories-tested and listed to

Standard 441 for use with listed gas-fired appliances that have been certified for use with Type B gas vent. B-Vent is intended for neutral or negative draft applications. It is designed for vertical installations

(including laterals) but may be used for horizontal applications with a draft-inducing fan located such that all indoor portions of the vent are under negative pressure.

The materials in this B-Vent have been selected to provide maximum resistance to corrosion and heat; however

,

their use with temperatures exceeding

550° F or in highly corrosive atmospheres, such as chlorinated hydrocarbons (i.e., refrigerants, drycleaning fluids, degreasers, paint removers, etc.), may substantially reduce their life expectancy

.

These installation instructions will enable the installer to make a safe and proper installation of the vent. Compliance with these instructions will ensure an installation that mee ts the requirements of all

National Building Codes and the National Fuel Gas

Code, NFPA 54 and NFPA 211. Hart & Cooley Type

B gas vents are listed under the follow-up service of Underwriters Laboratories, Inc.

Unit heaters

Duct furnaces

Attic furnaces

Floor furnaces

Water heaters

The following appliances must be connected to chimneys.

• All incinerators in domestic applications

• All appliances that may be converted readily t o the use of solid or liquid fuels

• Combination gas/oil-burning appliances

• Unlisted appliances

Room (space) heaters

Central warm-air furnaces

Hot-water boilers

Steam boilers

CAUTION

Hart & Cooley Type B vents are not to be used with appliances burning solid or liquid fuels.

Gas appliances that must be connected to chimneys

CAUTION

Flue gas temperatures must never exceed

550° F in any Hart & Cooley gas vent system.

Gas appliances that may be connected to Type

B gas vents

General instructions

• The vent should always be sized for the sea-level name plate input rating of appliances in accordance with the procedures set forth in the

Gas Vent Capacity Tables ,

which appear in the

Gas vent chimney sizing & application guide or in NFPA 54.

Type B gas vents may be used to vent gas appliances listed for use with Type B gas vent.

These vents shall be installed in accordance with our listing as detailed in these installation instructions. The type of appliances that may be vented with these vents include:

• Provide for adequate air supply for combustion air and draft-hood dilution air. Refer to NFPA 54 or the application guide for recommended arrangements and proper size of air supply openings.

• Use only parts and fittings listed in the catalog to ensure an approved vent.

1

Type B Gas Vent - 3” to 12” Diameter

Installation Instructions

• Portions of g as vents that may pass through accessible spaces must be enclosed to prevent personal contact with and possible damage to the vent. The enclosure also may have to meet fireresistance rating provisions. See all local and national codes that may apply

.

• Unenclosed outside vents below the roofline are prohibited.

• No damper or other restriction is permitted in a gas vent.

gure 1

• Single-wall connectors and stovepipes may be used with Hart & Cooley Type B vent with the following considerations: The use of single-wall materials cause higher heat loss from the flue products, which in turn reduce the draft and may cause condensation to occur

.

(A) Since the heat loss from single-wall pipe is double that from Hart & Cooley pipe, be sure to use the capacity table for single-wall connector

.

(B) Observe the local requirements for clearance to combustibles for single-wall pipe.

This distance is 6" to 9" in most areas.

(C) Do not run single-wall connectors through unheated spaces, partitions, or in concealed areas.

Figure 1

Vent Size

3RP

4RP

“A” Square

5-1/2 inches

Step-by-step installation procedure

Assembly of the vent

5RP

6RP

7RP

6-1/2 inches

7-1/2 inches

8-1/2 inches

10-1/2 inches

8RP 11-1/2 inches

Firestop Support

Table 1

The Firestop Support (FSP) serves as both a firestop as well as a support. Each support is designed to support up to 20 feet of vent pipe when installed as follows:

1. It is recommended that the Vent Pipe be supported at least every other floor. The distance between must not, in any case, exceed 20 feet.

2. Frame in an opening providing proper clearance to Type B Gas Vent. See Figure 1 and Table 1.

2

3. Secure Firestop Support (FSP) as shown in

Figure 2. Install strapping (minimum 3/4”, 28gauge) through all four slots in collar, and nail as shown or nail at all four slots as shown in Figure

3 and Figure 4 .

Type B Gas Vent - 3” to 12” Diameter

Installation Instructions

NAIL STRAPPING

IN PLACE

(FOUR PLACES)

Figure 2

4. Pass Type B Gas Vent through opening in Firestop Support (FSP)

.

5. Install Support Bracket as shown in Figure 1 .

Clamp bracket securely to pipe section, using the pair of bolts and nuts provided. Insert the included screws through the holes in the Support Bracket and into the pipe

.

For installations with multiple supports

,

an adjustable length section of Type B Gas Vent should be installed between each pair of locations where a

Firestop Support is used

.

See Figure 5. This provides relief for thermal expansion. The adjustable length section should be positioned directly under the Vent Pipe section that is being supported.

NAIL THROUGH

SLOTS

(FOUR PLACES)

NOTE: When installed with the entire vent in a vertical position as shown in Figure 5, the bottom end of the adjustable length sections should not be secured with the screws provided

.

This will allow movement to compensate for expansion

.

See section titled

Adjustable Length Sections on Page 4.

Figure 3

FIRESTOP SUPPORT

ADJUSTABLE

LENGTH SECTION

20 FEET

MAXIMUM

NAIL THROUGH

SLOTS

(FOUR PLACES) FIRESTOP SUPPORT

ADJUSTABLE

LENGTH SECTION

20 FEET

MAXIMUM

Figure 4

FIRESTOP SUPPORT

ADJUSTABLE

LENGTH SECTION

APPLIANCE

DRAFTHOOD

Figure 5

3

Type B Gas Vent - 3” to 12” Diameter

Installation Instructions

Round Support Plates

The Round Support Plate (RSP) is designed for use with 9- inch diameter and larger Type B Gas Vent.

Each support is designed to support up to 3

0

feet of

Vent Pipe when installed as follows

.

1. It is recommended that the Vent Pipe be supported at least every other floor

.

The distance between supports must not, in any case, exceed 30 feet

.

2. The circular cutout in the Round Support Plate is designed to engage the recess in the female end of the Vent Pipe. See Figure 6 .

5. For installations with multiple supports

,

an

Adjustable Length Section of Type B Gas Vent should be installed be-tween each pair of locations where a support is used. See Figure 5

.

This allow s the location of the pipe recess to be in the proper position at each opening where a support is to be used. The Adjustable Length Section also provides relief for liner thermal expansion

.

The

Adjustable Length Section should be positioned directly under the Vent Pipe Section that is being supported

.

RECESS

Figure 6

3. Surround the Vent Pipe with the two identical

Support Plate halves

.

See Figure 7 . Engage the plate edges in the pipe recess as described in

Step 2 . Use two pair of bolts and nuts to hold the plate halves together. (Four predrilled tabs are provided for this purpose.)

Adjustable Length Sections

Adjustable Length sections of Type B Gas Vent are available to allow for installation where fixed

length sections do not produce the desired dimensions

.

The Adjustable Length sections use a clamping method consisting of a screw and tabs to draw the outer wall tightly around the mating section Type B

Gas Vent.

Adjustable Length Sections may also be used to compensate for linear thermal expansion between two fixed points in the vent system. An example of this is shown in Figure 5 . In these examples

, the fastening devices are not used. This allows for expansion between two fixed supports or between a fixed support and the appliance. Note that the fastening means should be left loose only if the Vent and the Adjustable Length Sections are installed vertically. I f the Adjustable Length Sections are used in a position other than vertical

,

such as between offsets, the fastening means should be used

.

Finally

,

when joining an Adjustable Length Section to another section of Type B Gas Vent, make sure that there is a minimum overlap of one inch.

Assembly of the vent

Figure 7

4 . Mounting holes are provided around the perimeter of the Round Support Plate. Use appropriate fasteners to secure the Support Plate halves to the opening between floors. (Round

Support Plates should be attached to the TOP of the opening only.)

4

Appliances to be vented should be placed a s close as possible to the point where the vent is to run vertically up through the building.

Install the support assembly (RSA). A support assembly is recommended for all installations for the following reasons.

Type B Gas Vent - 3” to 12” Diameter

Installation Instructions

(A)It allows installation of the vent system prior to installation of appliances.

(B)It allows disconnection of the appliance for service at any time without disturbing or temporarily supporting the vent.

(C)It provides the required firestop as well as support.

(D)It is UL-listed.

Figure 8 shows the installation of an

RSA support assembly.

Figure 8

Figure 9

The support assembly shall be inst alled in the following manner. Frame an opening between standard 2" joists, either on 16" or 32" centers, depending on vent dimension, with headers of the same dimension lumber as the joists ( Figure 9 ) or on the wall studs with 2x4’s as in Figure 10 . The opening must be square and level on the bottom side. Place the support plate up into the opening with flanges tight against the underside o f the framing. Nail in place with two 8d nails on each side through the holes provided.

Installation of vent pipe in the RSA support

Place a supporting collar in the groove at the bottom end of any standard pipe just above the locking ring. Tighten the screw so that the collar is firmly clamped into position in the groove. The pipe is now assembled properly to fit into the support plate. ( See Figure 11 .) This pipe assembly will rest on the upper side of the support plate and provide the REQUIRED 1-INCH

CLEARANCE FROM COMBUSTIBLES. The pipe will protrude below the support for connecting additional pipe from the vent to the appliance. A maximum of 60 feet of vent can be installed above the support before resupport is required.

Figure 11

Figure 9 shows an RSA vent support installation in floor or ceiling joists or rafters of a flat roof.

Figure 10 •

Place an RDH draft hood connector on the outlet or the draft hood of the appliance. The aluminum portion of the draft hood connector should be fastened to the appliance collar with sheet metal screws. The extending aluminum portion can be readily shaped by hand to fit oval collars.

Figure 10 shows an RSA vent support using a wall bracket

(by others)

Install vertical vent pipe and fittings.

5

Type B Gas Vent - 3” to 12” Diameter

Installation Instructions

Installation for Optional Model RGS Firestop/

Gripper Support

• At the desired location, cut a square or circular hole in the floor at a minimum of 2½ inches larger than the nominal pipe size, but not greater than 4 inches larger. See chart below. This will provide the required 1-INCH CLEARANCE FROM COM-

BUSTIBLES .

Table 2

Nominal Pipe Size

Nominal Hole Size

Maximum Hole Size

Support Hole Dimensions

(inches)

3 3 3 3

51/2

7

51/2

7

51/2

7

51/2

7

Place the support over the hole with the ring down.

Use an 8-penny nail or self-drilling sheet metal screw in each corner at least 3/8 of an inch from the edge.

Pipe should be inserted from below

.

A maximum of 30 feet of pipe may be installed above the support before resupport is required. ( See Figure

12 .)

Assembling joints

See Figures 13, 14, and 15

Use gloves when handling vent parts.

To assemble joints of pipe and fittings, first make sure that the lock ring is moved upward sufficiently to clear the formed tabs. Check the tabs to see that they are projecting slightly outward from the pipe so that the upper section will slide down over the top end of the lower section to which it is being joined. Look for the word “UP” with the arrow pointing in the direction of flue-gas flow

.

Slide the top pipe or fitting down over the upper end of the lower pipe until the projections on the tabs line up with the groove in the lower pipe.

The joint will naturally come to a stop at this point if it is placed firmly down over the lower section.

Using the thumbs and fingers, press the tabs into position, and slide the lock ring down to lock the tabs in place.

If for some reason it is necessary to uncouple a joint, this may be easily done by sliding up the lock ring and moving the top section slightly to loosen the tabs. The section can then be lifted off.

Figure 13

6

Figure 12

Figure 14 Figure 15

(A) Whenever possible, a vertical vent should be used. This is done by simply using straight sections of pipe from the dra ft hood connector out through the roof. Where this is not possible, a vent connector using B-vent is used to run laterally from th e draft hood to the base

Type B Gas Vent - 3” to 12” Diameter

Installation Instructions of the vertical vent. The horizontal length of this vent connector should not exceed 1½ feet for each inch of connector diameter. If it is necessary for B-vent connector to pass through a partition, an RWT thimble may be used, or the wall framed to allow 1-INCH CLEARANCE and an RPC collar used on each side of the partition. When a vent connector is used, it should have as much vertical rise as possible BEFORE the horizontal run. Vent connectors attached directly to side outlet draft hoods, shuch as floor furnaces, shall be

DO NOT USE SCREWS

IN B-VENT UNLESS

LINING A MASONRY pitched upward at least 1/4 inch per foot. The lateral run of vent connectors attached to top

CHIMNEY. SCREWS

ARE NOT NECESSARY

AND CAUSE NOISE.

outlet draft hoods may be either horizontal or pitched upward.

using metal straps, and again maintaining the

MINIMUM CLEARANCE OF 1 INCH from combustibles. ( See Figure 9 .

)

CAUTION

Laterals in common vents are limited to

1½ feet for each inch of vent diameter

.

(E) Laterals must be supported at 5-foot maximum intervals. Where vertical vents are spaced by firestops between floors, they need only be supported at the bottom.

For Caps see

Figure 20 and Table 3

For

(B) The necessary straight lengths of pipe should be connected to the elbow

,

tee, or the draft hood connector

,

and all joints should be securely locked together as indicated above.

(C) Floors, ceilings, a nd other combustible construction should be cut away or framed a s necessary to provide a MINIMUM OF 1-INCH

CLEARANCE from the surface of the vent pipe.

Metal straps should be used to maintain the vent pipe in position to ensure that the 1-INCH

CLEARANCE to combustibles is maintained after the walls are closed. ( See Figure 16 .) DO

NOT SCREW INTO THE VENT

.

CAUTION

Do not allow the offset pipe to put pressure on the elbow. Use pipe strap for support.

Figure 16

Framing to prevent contact with building insulation

• In many instances, vents pass through ceilings that are insulated. I n these cases, it is necessary to frame around the opening cut in the ceiling for passage of the vent pipe so that building insulation or other combustible material will not come in contact with the surface of the vent. This framing should, of course, be arranged to PROVIDE 1-INCH MINIMUM

CLEARANCE from the surface of the vent.

( See Figure 16 ).

(D) Whenever possible, the vent should be continued straight out through the roof. If it is necessary to make offsets in the attic space, the lateral run should be sloped upward as sharply as possible, using elbows to minimize resistance. The lateral run should be supported

• Occasionally Type B vent connectors must pass through partitions that are insulated. The simplest means of preventing contact with the insulation in these cases is to use an RWT wall thimble.

7

Type B Gas Vent - 3” to 12” Diameter

Installation Instructions

8

Fire-stopping

In single-story, slab-floor houses having an attic space, a firestop must be provided where the vent p a s s e s through the ceiling, unless a support is used there.

The ceiling should be cut away from the opening frame to PROVIDE

Figure 17

1-INCH MINIMUM CLEARANCE from the vent pipe. A firestop consisting of a noncombustible material, such as 1/4-thick ceramic board or 26gauge galvanized sheet metal, should be cut to fit the pipe and the framed opening. The firestop should be fastened to the top of the jois ts and framing members to eliminate any pock ets in which combustible debris might collet. An RPC pipe collar may be used on the underside of the ceiling to finsh off the opening. ( See Figure 17 .)

Four-inch round vent (4RPX) may be used in a 2” x 6” stud wall. The proper clearance in a 2” x 6” wall is provided by the spacer on the pipe and by the 4RFS firestop spacer. All other uses of a 4” pipe require the normal 1-INCH CLEARANCE TO COMBUSTIBLES.

Four-inch round vent (4RP) must main tain

1-INCH CLEARANCE T O COMBUSTIBLES.

In single-story buildings with an attic space and with the gas appliance located in a basement or crawl sp ace, firestops must be provided where the vent p asses through both the floor and the ceiling .

This can be done by cutting away and framing the floor and ceiling construction and installing firestops of noncombustible material as shown in Figure 17 ) . All combustible construction should be cut away sufficiently to PROVIDE

THE MINIMUM CLEARANCE OF 1 INCH FROM THE

VENT PIPE SURFACE.

In multi-story buildings, a firestop must be provided at every point where the vent p asses through a floor or ceiling. These firestops may be provided as indicated in the paragraph above.

Figure 18

Terminations using a flashing and a cap

Gas Venting Systems use a termination cap and may terminate in accordance with Table 3 and

Figure 20.

3" - 8" TOP INSTALLATION

Round tops (for pipe sizes 3"

Fig. 22-A

-

8") have a spring clip which engages and locks automatically when the top is pushed into the upper end of the pipe. (See

.) The top will also fit any single wall metal pipe having full nominal inch dimensions is required). To attach securely

,

.

(Never use single wall metal pipe where Type B Gas Vent

bend a one inch length of the pipe upper end inward about 1/8"

.

The spring clip will lock under this bent edge. (See Figure 22-B.

) To remove the top from any pipe

,

pull up evenly on the opposite sides of the skirt of the top.

Type B Gas Vent - 3” to 12” Diameter

Installation Instructions

A cap or chimney housing offers resistance to the entrance of rain, snow and debris, as well as birds, and will minimize the effect of wind on the vent.

It will protect the vent from down drafts caused by wind.

However , no vent cap, cowl or top can overcome the adverse effect of a region of high static pressure around the vent terminal nor the effect of an interior region of low pressure.

- Reference: American Gas Association Research Bulletin 68

Figure 19

Models RHW and RM caps

,

sizes 3" through 12", are listed for installation on gas vents terminating so that the lowest discharge opening shall be no closer than the minimum height shown i n Table 3 and Figure 20 . These minimum heights may be used, provided that the vent is not less than 8 feet from any vertical wall. FOR A VENT CLOSER THAN

8 FEET

,

THE VENT TERMINATION MUST BE

RAISED UNTIL 2 FEET HIGHER THAN THE

STRUCTURE.

Offsets in the attic space should be used to minimize the amount of vent pipe that must be exposed above the roof in order to comply with the above. No gas vent should be terminated less than 5 feet in vertical height above the highest connected appliance draft hood outlet.

• If a vent extends more than 5 feet above the roof, it should be guyed with 3 wires or braced with

2 pieces of rigid conduit

CAUTION

Where heavy snowfall occurs, the cap should be installed to a height above the average snow depth.

Regions of high static pressure around the vent terminal can be avoided by following the general rule for the vent termination given previously. Low or negative interior pressures in the building may be caused by (1) failure to provide combustion air

,

(2) excessive use of exhaust fans, and (3) tight construction resulting in the lack of infiltration air.

Vented clothes dryers and fireplaces also will remove large amounts of air from the interior

, tending to produce a low interior pressure.

WHERE THE VENT PASSES THROUGH THE

ROOF, the roof sheathing should be cut away sufficiently to PROVIDE A MINIMUM OF 1-INCH

CLEARANCE from the vent pipe. The vent pipe should be run up to a point where the top end is at least a foot or so above the roof.

An RF roof flashing should be placed down over the upper end of the pipe, and adjusted so the base place of the flashing fits tightly against the roof with the vent pipe held in a position, MAINTAINING THE

1-INCH CLEARANCE FROM COMBUSTIBLE

CONSTRUCTION . The flashing may be sealed to the roof. The RS storm collar must be placed immediately above the roof flashing. The storm collar must be sealed with roof cement or RTV silicone to seal the joint between the storm collar and the vent pipe. The storm collar provides protection against the entrance of any moisture into the flashing.

(See Figure 16 .)

9

Type B Gas Vent - 3” to 12” Diameter

Installation Instructions

Painting the exposed vent surfaces above the roof will result in longer vent life. A good grade of paint designed for use on galvanized steel should be used. RHW and RM caps push straight down and snap onto the pipe. To remove, pull straight up and rock slightly.

In those cases where the posting of such a notice is required, a label shall be placed as follows.

(A) Where a vertical vent is used, the label shall be placed on the ceiling near the point where the vent passes through the ceiling.

(B) If the vent is horizontal, the label shall be placed on the wall near the point where the vent passes through the wall, on the side of the partition on which the appliance is located.

Figure 20

Outside vents

Roof Pitch

Flat 6/12

Over 6/12 to 7/12

Over 7/12 to 8/12

Over 8/12 to 9/12

Over 9/12 to 10/12

Over 10/12 to 11/12

Over 11/12 to 12/12

Over 12/12 to 14/12

Over 14

.

12 to 16/12

Over 16/12 to 18/12

Over 18/12 to 20/12

Over 20/12 to 21/12

Minimum He ight from Roof to Low e s t

Discharge Opening

,

Ft

.

1

.0

1

.

25

1

.

5

2

.0

2

.

5

3

.

25

4

.0

5

.0

6

.0

7

.0

7

.

5

8

.0

Table 3

Notice concerning limitation of Hart & Cooley pipe used with gas appliances

Gas vent systems should be plainly and permanently labeled:

This gas vent is for appliances that burn gas only. Do not connect to incinerators or solid or liquid fuel-burning appliances. Inspect the vent prior to each heating season to confirm an unrestricted vent .

The authority having jurisdiction shall determine whether the particular locality constitutes an area where such notice must be posted.

Occasionally it is necessary to vent an appliance through an exterior wall and up along the out side wall to a point above the roof, as shown in

18 .

Figure

In this case, an R DH draft hood connector and/or short length of RP pipe is used to connect the appliance to an RT tee, which is capped off on the bottom and supported. T he vertical vent is then erected from the tee, using straight lengths of RP pipe. These lengths of pipe should be securely locked together and positioned with RWB wall brackets to MAINTAIN 1-INCH MINIMUM CLEAR-

ANCE TO COMBUSTIBLE CONSTRUCTION AT

ALL POINTS. The vent may be carried through the roof overhang using an RF flashing and RS storm collar, and terminated with a cap. The vent then shall be enclosed below the overhang.

Lining a masonry chimney

An unlined masonry chimney is not permitted to be used to vent gas appliances. Hart & Cooley Type

B gas vent or chimney liner system may be used to line a masonry chimney. These instructions are for Type B vent.

Lining an unused masonry chimney should be done only by a qualified contractor. Contact local building or fire officials about restrictions and inst allation inspection in your area.

10

Type B Gas Vent - 3” to 12” Diameter

Installation Instructions

The chimney liner size must not be less than that specified in the appliance manufacturer’s instructions or smaller at any point than the connected appliance flue outlet size. Zero airspace clearance between the vent and the chimney interior surface is permitted.

The masonry chimney may also have a zero airspace clearance (direct contact with) combustibles and the chimney exterior surface. This is permitted with nominal 4"-width brick. A masonry chimney must have a clear passageway

,

sound construction, and be clean before proceeding. Inspect the chimney for cracked brick and mortar

,

missing pieces or holes, and repair as necessary. To prevent corrosion to the

B-vent, thoroughly clean the chimney of any residual debris, creosote, or soot that may coat the inside passageway. The passageway must be at least large enough to accommodate the proper size B-vent for the appliance(s).

If there is space remaining in the chimney outside the liner

,

this space shall not be used to vent another appliance unless another liner is used. Minimum and maximum heights and sizing for B-vent are in the National Fuel Gas Code. The chimney termination must meet the requirements of NFPA 211.

Installation

A tee (RT with a tee cap, RTC) should be used at the lowest point of the liner

.

A welded angle iron frame (by o t h e r s ) mortared into the chimney walls should be used with the s u p p o r t assembly

.

(See

Figure 21

Figure 21 .) Through-bolt the support assembly into the frame with 1/4-20 nuts and botls (by others) in all holes. Place the supporting collar in the groove at the bottom of the tee just above the locking ring. (See Figure 8 .) Tighten the screw so that the collar is firmly clamped into position in the groove. The tee is ready to fit into the support plate.

• Sixty feet of pipe may be supported by the RSA support. If more than 60 feet is required, another support assembly may be used. An adjustable length (RPA) should be used just below the resupport to make up for odd dimensions between supports and to provide for expansion, if necessary

.

• If pipe assemblies are lowered into place from above, sheet metal screws should be used to hold the lock bands in place.

• Terminate the vent with a tall cone flashing (RTF), storm collar (RS), and appropriate diameter cap.

Maintenance and inspection

Gas is a clean-burning fuel that typically does not require maintenance of appliance vent system.

However

,

the liner must be inspected at least once a year by a qualified inspector or installer at the same time that the appliance is being inspected and serviced. The cap snaps off for visual inspection of the outlet area. Connector pipe should be removed to examine the inlet at the base of the chimney.

Look for loose joints, debris, condensate or corrosion, and clean or repair as required.

Combined vents

For detailed instructions for combining two or more appliances into a common vent, see the

Gas Vent

Capacity Tables section in the application guide.

Whenever possible, vents should be run directly from collar of the appliance vertically out through the roof in the most direct method available.

In those cases where it is necessary or desirable to combine the vent connectors of several gas-fired appliances into a common vent, the vent connector from each individual appliance should be arranged to have as great a vertical rise as possible before starting the lateral run to the common vent. If a combined vent cannot be used because of limitations in the connector rise or total vent height,

Figure 22 alternatives such as those illustrated ( Figure 22 ) may be used to secure greater rise or greater total vent height. TYPE B GAS VENT CONNECTOR must be used for Figure 22B .

11

Type B Gas Vent - 3” to 12” Diameter

Installation Instructions

Hart & Cooley vent into Other

THESE INSTRUCTIONS SHOULD

REMAIN AVAILABLE TO THE

HOMEOWNER AT ALL TIMES.

Installation instructions for Hart & Cooley

UL-listed Type B gas vent adapters

The following table specifies the UL-listed adapters to be used when changing between Hart & Cooley and B-vent manufactured by others.

Insert “Other” female end’s inner and outer inside RRA’s inner and oute r. Slide together minimum of 1 inch to seat inner. Tighten the screw. (See Figure 24 .)

Figure 24

Other

Manufacturer

Selkirk LLC

Metal Fab, Inc.

American Metal

Products, Inc.

General Products

Company, Inc.

Simpson

Dura-Vent

Pipe

Diameter

3"

-

6"

7"

-

8"

3" 6"

7" 8"

3" 6"

7" 8"

3"

-

6"

7"

-

8"

3" 6"

7" 8"

Table 4

Other into

Hart & Cooley

RA or RPS

RA

RA or RPS

RA

RA or RPS

RA

RAA

RAA

RAA

RAA

Hart & Cooley

Vent into

RAA

RAA

RAA

RAA

RAA

Other into Hart & Cooley vent

Assemble the female end of the a d a p t e r over the

Figure 23 male end of the other listed B-Vent. Fully seat the adapter or provide a minimum of 1-inch overlap. Tighten the screw in the slips provided. (See Figure 23.

)

©2015 Hart & Cooley, Inc. All rights reserved Form No. 150952

12

12/15/2015 Printed in U.S.A.