1.0

Connecting OpenGN to

FleX-Net™ FX-4000

i

!

Attention: Before you begin, follow the instructions in LT-1113 “OpenGN

Administrator’s Guide” to install OpenGN and configure the computer running OpenGN and the OpenGN Gateway.

Note: These instructions should be completed by someone familiar with configuring

FleX-Net™ FX-4000. See LT-894MP, the FleXNet™ FX-4000 Installation and

Operations Manual.

You need:

• Mircom’s MGC-CONFIG-KIT4

• Registered CodeMeter key for FleX-Net™ FX-4000

• FleX-Net™ FX-4000 firmware version 1.2.4

• MGC-4000 Configurator version 1.6 or higher

• Ethernet cable (maximum 300’)

• OpenGN version 3.7

• OpenGN Gateway version 3.7

• OpenGN license key

1.1

Overview

To connect OpenGN to FleX-Net™ FX-4000, you must:

1. Connect the OpenGN Gateway to FleX-Net™ FX-4000

2. Configure FleX-Net™ FX-4000

3. Export the Job File

4. Import the Job File into OpenGN

5. Configure the OpenGN Gateway

6. Verify the Connection in the OpenGN Gateway

Follow the instructions below to complete these steps.

LT-6703 Rev 0 1

Connecting OpenGN to FleX-Net™ FX-4000

1.2

Connect the OpenGN Gateway to FleX-Net™ FX-4000

To connect the OpenGN Gateway to a FleX-Net™ FX-4000 Fire Alarm Control Panel through

Ethernet:

1. Open the Fire Alarm Control Panel enclosure.

2. Open the Fire Alarm Control Panel chassis to access the FleX-Net™ FX-4000 main board.

3. Connect the Ethernet cable to the Ethernet port (P7) on the main board.

Ethernet Port

2

Figure 1 FleX-Net™ FX-4000 Main Board Ethernet Port (P7) Location

4. Connect the other end of the Ethernet cable to the network that the computer is connected to.

1.3

Configure FleX-Net™ FX-4000

The FleX-Net™ FX-4000 node that is connected to OpenGN must be configured so that it can communicate with the FleX-Net™ FX-4000 network.

1. Insert your CodeMeter key into the computer.

The CodeMeter icon in the Windows system tray (in the lower right-hand corner of the screen) turns blue.

Figure 2 Connected CodeMeter Key

If the CodeMeter key is not inserted, the icon is gray.

Figure 3 Disconnected CodeMeter Key

LT-6703 Rev 0

Connecting OpenGN to FleX-Net™ FX-4000

2. Use the MGC-CONFIG-KIT4 to connect the computer to the FleX-Net™ FX-4000 node.

Follow the instructions in LT-6230 available on mircom.com

.

3. Start the Configurator.

The Configurator prompts you for your PIN.

4. Type your 4 digit PIN.

Figure 4 Security Key Logon

The Configurator opens.

5. Click Panel > Connect .

6. Open the job for the installation of FleX-Net™ FX-4000 that will connect to OpenGN.

7. Click Job > New Version , and type a comment to describe the new version, for instance

OpenGN .

The left side of the Configurator window lists the job as a tree.

8. Select the node that is connected to OpenGN.

The Network Node Info window appears on the right.

LT-6703 Rev 0

Figure 5 Network Node Details

3

Connecting OpenGN to FleX-Net™ FX-4000

9. Type the static IP address, subnet mask, and gateway for the node. If you need assistance, contact your network administrator.

10. Select Supervise Ethernet Connection . If this option is selected, then FleX-Net™

FX-4000 reports a trouble when the Ethernet cable is disconnected.

11. Select Enable under Graphics Workstation . This option allows FleX-Net™ FX-4000 to communicate with the OpenGN Gateway.

12. Select Supervise Connection under Graphics Workstation . If this is selected,

FleX-Net™ FX-4000 reports a loss of connection with OpenGN as a trouble on the annunciators.

Do steps 10, 11 and 12 only on the node that is connected to OpenGN.

4

Figure 6 Network Settings

13. Click Job > Send Job . Send the job to the node that OpenGN will be connected to.

LT-6703 Rev 0

Connecting OpenGN to FleX-Net™ FX-4000

1.4

Export the Job File

To export the job file from a FleX-Net™ FX-4000 panel

1. Start the Configurator.

2. Click Job > Export Job .

The Export current job to a file window appears.

Figure 7 Export current job to a file

3. In the Save as type menu, click OpenGN Phase III (*.xml) , and then click Save .

1.5

Import the Job File into OpenGN

1. Transfer the job file you generated in section 1.4 to the computer that OpenGN is running on.

2. Insert the OpenGN CodeMeter license key in the computer.

3. Double-click the Open Graphic Navigator icon.

The Login window appears.

Figure 8 Login Window

LT-6703 Rev 0 5

Connecting OpenGN to FleX-Net™ FX-4000

4. Select the user from the Login menu.

5. Type the password.

6. Click OK .

The OpenGN Main Display window appears.

7. Click the Config button from the Main Display window.

8. Click Yes to confirm that you want to enter the configuration section.

The Configuration window appears.

9. Click the Settings button in the lower right-hand corner of the Configuration window.

The Main Program Settings window appears.

6 i

Figure 9 Panel Settings

10. Click Browse in the Panel Configuration section, and then navigate to the XML file.

11. Select Auto-associate default icons if you want to associate the object icons with the existing system icon images.

Note: If you are importing a new version of a previously imported job file, uncheck

Auto-associate default icons . Otherwise, any custom icon settings you have made will be erased.

12. Click Import XML .

13. Click Yes .

14. Restart OpenGN.

LT-6703 Rev 0

Connecting OpenGN to FleX-Net™ FX-4000

1.6

Configure the OpenGN Gateway

1. Double-click the Open Graphic Navigator Gateway icon.

Figure 10 OpenGN Gateway

2. Click the Select Interface pulldown menu and select the interface that you are connecting with. If you are using an Ethernet cable, select Local Area Connection .

3. Click the + button.

The Adapter Configuration window appears.

LT-6703 Rev 0

Figure 11 Adapter Configuration Window

7

Connecting OpenGN to FleX-Net™ FX-4000

4. Provide the following information:

Type

Connection

String

FleX-Net™ FX-4000 Series

Type the IP address of the panel that the OpenGN Gateway is connected to, then a colon, then 14000 .

See section 3 on page 14 for instructions on how to get this information from the FleX-Net™ FX-4000 panel.

For example, if the IP address of the panel is 192.168.1.10, then type:

192.168.1.10:14000

5. Click the green button beside Destination, and then provide the following information:

Destination IP The IP address of the OpenGN computer. If the OpenGN Gateway and

OpenGN are on the same computer, use 127.0.0.1.

1209 Destination Port

Store and Forward

Events

Reserved for future use.

8

Figure 12 Destination

6. Click OK .

The Destination appears in the Destination field on the left.

7. Under Command Connection , provide the following information:

Incoming

Command IP

Port

The IP address of the computer that the OpenGN Gateway is on. If the

OpenGN Gateway and OpenGN are on the same computer, use

127.0.0.1.

1309 . This must be a different port than the port listed above.

Figure 13 Command Connection

LT-6703 Rev 0

Connecting OpenGN to FleX-Net™ FX-4000

8. Click Auto Start Adapter When OpenGN Gateway Starts if you want the OpenGN

Gateway to connect automatically with these settings when it starts.

9. Click Save at the bottom of the Adapter Configuration window.

10. In the Windows taskbar, right-click the OpenGN Gateway icon, and then select Close window .

Figure 14 Close OpenGN Gateway

11. Double-click the Open Graphic Navigator Gateway icon.

1.7

Verify the Connection in the OpenGN Gateway

1. If the OpenGN Gateway is not running, double-click the Open Graphic Navigator

Gateway icon.

2. Select the adapter that you created earlier.

3. Click the green arrow icon:

When OpenGN is connected, the adapter in the Adapter List is green.

LT-6703 Rev 0

Figure 15 OpenGN Gateway with One Connection

9

10

Connecting OpenGN to FleX-Net™ FX-4000

4. Double-click the adapter to view its details.

When OpenGN Gateway is connected, the icon beside Connection String is green, and the Destination is green.

Figure 16 The OpenGN Gateway Showing a Connection

LT-6703 Rev 0

Connecting OpenGN to FleX-Net™ FX-4000

2.0

Updating the Job File for

FleX-Net™ FX-4000

If the job on the Fire Alarm Control Panel changes, you must export the job file from the

Configurator, and then import it into OpenGN again.

2.1

Exporting the Job File from the Configurator

In this step, you export the job file from the Configurator. In the next step you import it into

OpenGN.

To export the job file

1. Start the Configurator.

2. Click Job > Export Job .

The Export current job to a file window appears.

Figure 17 Export current job to a file

3. In the Save as type menu, click OpenGN Phase III (*.xml) , and then click Save .

LT-6703 Rev 0 11

12

Connecting OpenGN to FleX-Net™ FX-4000

2.2

Importing the Job File into OpenGN

After you have exported the job file, you must import it into OpenGN.

To import the job file

1. Transfer the job file you just saved to the computer that OpenGN is running on.

2. Insert the OpenGN CodeMeter license key in the computer.

3. Start OpenGN.

The Login window appears.

Figure 18 Login Window

4. Select the user from the Login menu.

5. Type the password.

6. Click OK .

The OpenGN Main Display window appears.

7. Click the Config button from the Main Display window. Click Yes to confirm that you want to enter the configuration section.

The Configuration window appears.

8. Click the Settings button in the lower right-hand corner of the Configuration window.

The Main Program Settings window appears.

9. Click the Panel Settings tab.

The Panel Settings window appears.

LT-6703 Rev 0

LT-6703 Rev 0

Connecting OpenGN to FleX-Net™ FX-4000

10. Click Browse in the Panel Configuration section, and then navigate to the job file.

11. Click Import XML .

12. If the job already exists, a window appears asking you if you want to update the stored version of the job with the one you are importing.

13. Click Yes .

Figure 19 Update Job Confirmation Box

A message appears saying that the import was successful.

14. Click Close .

13

Connecting OpenGN to FleX-Net™ FX-4000

3.0

Getting Configuration

Information from FleX-Net™

FX-4000

To get configuration information from the FACP

1. On the main display of any node or on an annunciator for any node in the system, press the MENU button.

2. Use the arrow buttons to scroll to Config Info , and then press ENTER.

The display shows the ESDNo (ESD number) and TechNo (technician number).

3. Press the down arrow button to see the Build Time (the date and time when the firmware on the CPU was built).

4. Press the down arrow button to see the IP information for this node (the IP address, the subnet mask, and the default gateway).

14 LT-6703 Rev 0

$BOBEB

*OUFSDIBOHF8BZ

7BVHIBO0/-,8

5FM

'BY

64"

8JUNFS*OEVTUSJBM&TUBUFT

/JBHBSB'BMMT/:

5FM

ª .($ 2

1SJOUFEJO$BOBEB

4VCKFDUUPDIBOHFXJUIPVUQSJPSOPUJDF

IUUQXXXNJSDPNHSPVQDPNPQFOHO

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement