Notifier IRX-751CTEM Data Sheet

Add to My manuals
3 Pages

advertisement

Notifier IRX-751CTEM Data Sheet | Manualzz

SMART

4

Multi-Criteria Fire Sensor

Data Sheet

Fires take many forms, from a slow smouldering fire that produces large amounts of smoke and Carbon Monoxide but little heat through to alcohol fires that produce high temperatures very quickly without any evidence of smoke. The SMART 4 has a sophisticated ‘brain’ capable of intelligently combining the data from the four sensing elements to provide a fast response to real fires while remaining extremely resilient to false alarm incidents.

Using a combination of Carbon Monoxide, Heat, Optical smoke sensing and Infrared flame sensing elements enables SMART 4 to detect the broadest range of fire conditions providing the earliest warning.

Features

• Unique, true four sensor Multi-criteria detector

• Fully integrated Infra Red sensor to support the fire alarm decision

• CO gas sensing for fastest response to slow developing and smouldering fires

• Highest possible immunity to unwanted alarms

• Automatic drift compensation of smoke sensor and CO cell

• Twin LED indicators providing 360° visibility

• Wide temperature range

• Built in test switch

• Stable communication with high noise immunity

How the SMART

4

works

The SMART 4 is configured so that it normally operates at a high immunity level, changing to become very sensitive to fires when fire characteristics are sensed. In this way transient nuisances are monitored and ignored, reducing the false alarm rate.

SMART 4 dynamically adjusts the detection profile of the device in response to the input from the sensors, enabling it to be re-characterised on the fly as the ambient conditions change.

Based upon the sensor signals, sensor thresholds, sensor gain, time delays, combination, sampling rates, averaging rates are dynamically adjusted. And, if any sensor fails the sensitivity of the remaining sensors are adjusted to compensate and a fault condition is indicated.

The IR light sensor helps the detector recognise specific situations such as welding and makes adjustments rapidly in order to further reduce the potential for false alarms. The thermal detection function fuses thermistor technology with a software corrected linear temperature response. In areas where the normal daytime activities are likely to create unwanted alarms, the detector can be programmed to operate on a “Heat only” mode, automatically reverting to multi sensor operation during the unoccupied period. The SMART 4 is thus able to offer exceptional false alarm immunity and excellent fire detection.

This document is not intended to be used for installation purposes. Every care has been taken in the preparation of this document but no liability can be accepted for the use of the information therein. Design features may be changed or amended without prior notice.

For more information, contact:

NOTIFIER. Charles Avenue, Burgess Hill, West Sussex, RH15 9UF. United Kingdom

Phone: +44 (0) 1444 230 300 Fax: +44 (0) 1444 230 888

Page 1 of 3 - 990-125_0314

ISO9001

Design, Manufacture and

Supply to Quality Manage ment Systems Certified to

ISO9001:1994 www.notifierfiresystems.co.uk

SMART

4

Multi-Criteria Fire Sensor - IRX-751CTEM

The SMART 4 combines 4 separate sensing elements to act as a single unit. CO sensing (using EC technology) for monitoring CO products from a smouldering fire, IR sensing for measuring ambient light levels and flame signatures, optical smoke detection and heat detection.

SMART 4 dynamically adjusts the detection profile of the device in response to the input from the sensors. It normally operates at a high immunity level, changing to become very sensitive to fires when fire characteristics are sensed. In this way transient nuisances are monitored and ignored, delivering exceptional false alarm immunity and excellent fire detection.

Where specific threats of false alarm have been identified, one of 6 sensitivity levels can be chosen directly from the fire alarm control panel in order to further tailor the detectors performance to its environment.

Specifications

IRX-751CTEM

Mechanical Specification

• Height: 66mm installed in B501 base

• Diameter: 102mm installed in B501 base

• Weight:

• Max Wire Gauge for

Terminals:

• Colour:

• Material:

176g (inc base)

2.5mm

2

White

Bayblend FR110

66 mm*

102 mm

* Note: the delay counter starts when the smoke level exceeds approximately 0.75%/ft.

† Do not install detectors in locations where normal ambient temperature exceeds 50°C

The IRX-751CTEM SMART 4 contains an electro-chemical CO sensor which has an expected lifetime from date of manufacture of 6 years and the remainder of the components are made to last over 10 years. Test your fire detection system at least biannually. Clean and take care of your smoke sensors regularly. Taking care of the fire detection system you have installed will significantly reduce your product liability risks.

Page 2 of 3 - 990-125_0314

Electrical Specification

• Operating Voltage Range: 15 to 32Vdc

• Max. Standby Current: 220μA @ 24Vdc (no communications)

• Max. Alarm Current: 7mA @ 24 Vdc

• Remote Output Voltage: 22.5Vdc @ 24Vdc

• Remote Output Current: 10.8mA @ 24Vdc

• Additional loop resistance

using the B501AP: typ 20mohm (max 30 mohm)

Environmental Specifications

• Temperature Range: -20°C to +55°C †

• Humidity: 15 to 90% relative humidity (non-condensing)

Range

• IR Limits

• CO Limits

0-450 uW/cm2

0-500 PPM

Sensitivity and Nuisance Immunity Settings

The product provides 6 levels of sensitivity, detailed below:

Level 1 Low false alarm resistance, high photoelectric only sensitivity

1%/ft of smoke or greater than 45 ppm of CO.

No delays from processed photo output.

Level 2 Medium false alarm resistance, medium photoelectric only sensitivity

2%/ft of smoke. No delays from processed photo output.

Level 3

Level 4

Level 5

Standard false alarm resistance, low photoelectric only sensitivity

3%/ft of smoke. No delays from processed photo output.

High false alarm resistance, low photoelectric only sensitivity

3%/ft of smoke.

Maximum of 10 minutes delay from processed photo output.

*

Very high false alarm resistance, low photoelectric only sensitivity

4%/ft of smoke.

Maximum of 10 minutes delay from processed photo output.

*

Level 6 Heat only alarm. Class A1R

If the heat level on either thermistor exceeds 60°C or rate of rise limits.

The panel threshold should be chosen according to the specific environment:

Ultra-clean applications use Level 1 for pre alarm or alarm

Clean applications use Level 1 for pre alarm and levels 2 & 3 for alarm

Moderate environments use Level 1,2 or 3 for pre alarm and Level 4 for alarm

Harsh environments use Level 2 or 3 for pre alarm and Levels 5-6 for alarm www.notifierfiresystems.co.uk

Product Range at a Glance

OPAL Optical smoke detector

OPAL Heat detector, fixed 58ºC

OPAL Heat detector (A1R), rate of rise + fixed 58ºC

OPAL Heat detector, fixed 78ºC

OPAL SMART 2 Optical smoke & heat detector

OPAL SMART 3 Optical smoke & heat detector with infra-red flame sensing

SMART 4 sensor

Infrared, Carbon Monoxide, Optical, Thermal Multi

Analogue sensor base with SEMS screw connections for isolated and non-isolated detectors and address identification label

Wet Base shroud for use with standard bases to allow condensation run off and rear seal. Conduit entry only.

Isolator Colour

 Ivory

 n/a n/a n/a n/a

Ivory

White

White

Ivory

White

Ivory

White

Ivory

White

Ivory

White

Ivory

White

Ivory

White

Ivory

White

Part Number

NFX-OPT-IV

NFXI-OPT

NFX-TFIX58-IV

NFXI-TFIX58

NFX-TDIFF-IV

NFXI-TDIFF

NFX-TFIX78-IV

NFXI-TFIX78

NFX-SMT2-IV

NFXI-SMT2

NFX-SMT3-IV

NFXI-SMT3

IRX-751CTEM-IV

IRX-751CTEM-W

B501AP

B501AP-IV

WB-1AP

WB-1AP-IV

Page 3 of 3 - 990-125_0314