Swegon CLASS UNIT TAC5 CLASS UNIT - Instructions
Reklama
Reklama
CLASS UNIT
Operation and maintenance instructions
Applicable to program versions TAC5
2 Operation and maintenance instructio ns – CLASS UNIT TAC5
CLASS UNIT
Table of content
1.0
Safety precautions
2.0
Product Overview
3.0
Wiring Overview
4.0
Functions
5
.0
Commissioning
6.0
Preventive maintenance
7.0
Troubleshooting
8
.0
Parameters/Commissioning Sheet
9.0
CE Declaration
Operation and maintenance instruction s – CLASS UNIT TAC5
3
Symbols and abbreviations
PX
WARNING
Must be connected by a qualified
Electrician.
Warning! Hazardous voltage.
PLATE HEAT
EXCHANGER
Electronic boards contains ESD sensitive components.
Wear antistatic wrist strap connected to protective earth before to manipulate them.
In alternative, discharge by touching the unit, handle boards at corners only and use antistatic gloves.
Air from outdoor to the AHU (OA)
Air from the AHU to the building (SA)
Air from the building to the AHU (ETA)
Air from the AHU to outdoor (EHA)
KW
HEATING COIL
(ELECTRICAL)
4 Operation and maintenance instructio ns – CLASS UNIT TAC5
1.0 Safety precautions
Danger/Warning/Caution
• All staff concerned shall acquaint themselves with these instructions before beginning any work on the unit. Any damages to the unit or its components caused by improper handling or misuse by the purchaser or the installer cannot be considered subject to guarantee if these instructions have not been followed correctly.
• Make sure that the power supply to the unit is disconnected before performing any maintenance or electrical work!
•
All electrical connections must be carried out by an authorized installer and in accordance with local rules and controls.
• Although the mains supply to the unit has been disconnected there is still risk for injury due to rotating parts that have not come to a complete standstill.
• Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is used. Use protective clothing.
• Unit should always be operated with closed doors and panels.
•
If the unit is installed in a cold place make sure that all joints are covered with insulation and are well taped.
• Duct connections/duct ends should be covered during storage and installation, in order to avoid condensation inside of the unit.
• Check that there are no foreign objects in unit, ducting system or functional sections.
• The unit is packed to prevent damage of the external and internal parts of the unit, dust and moisture penetration. If the unit is not to be installed immediately, it should be stored in a clean, dry area.
If stored externally, it should be adequately protected from the weather influence.
Operation and maintenance instruction s – CLASS UNIT TAC5
5
2.0 Product Overview
COMPONENTS CLASS UNIT
6
1.
Centralized wiring box of the CB4 TAC5 DG circuit
(factory pre-wired)
2.
Supply fan
3.
Exhaust fan
4.
Air/Air heat exchanger ( + modulating 100% by-pass)
5.
Drain pan
6.
GF-ePM10 50% filter at fresh air inlet
7.
GF-ePM10 50% filter on exhaust air
8.
Access panels
9. Air inlet damper
10.
Internal postheating electric coil (KWout)
Operation and maintenance instructio ns – CLASS UNIT TAC5
AIR VOLUME AND DIMENSIONS
SIZE
CLASS UNIT 1000
AIR VOLUME
1050 m³/h 291 l/s
Operation and maintenance instruction s – CLASS UNIT TAC5
7
3.0 Wiring Overview
MAIN CONTROL BOARD TAC DG - CID025000
CT = output to inlet damper CT actuator(prewired)
BYPASS = output to bypass actuator (prewired)
AL1 = ALARM OUTPUT (230V/5A)
B- / A+ / GND / +12V = connection to HMI TACtouch
K1 : Airflow MODE = m³/h K1
Demand/Pressure control
Torque MODE
= START/STOP
= %torque K1
K2 : Airflow control
Demand/Pressure control
Torque control
K3 : Airflow control
= m³/h K2
= 0-10V INPUT
= %torque K2
= m³/h K3
Demand/Pressure control
Torque control
= % ON K3 or 0-10 V INPUT
= %torque K3
T1 = from outdoors T° sensor (prewired)
T2 = from indoors T° sensor (prewired)
T3 = to outdoors T° sensor (prewired)
T5 = supply T° sensor for KWout coil (prewired)
8
IN1 = Master selection
IN2 = dPa (pressostat digital input)
IN3 = Fire alarm input
IN4 = Bypass open / Stop heat recovery
IN5 = Real time clock auto/manu
IN6 = ON/OFF post heating (IBA/KWout)
IN7 = ON/OFF SUPPLY if fire alarm
IN8 = ON/OFF EXHAUST if fire alarm
IN9 = BOOST Airflow
IN12 = PWM input bypass position
OUT1 = 0-10V OUTPUT (airflow / pressure)
OUT2 = 0-10V OUTPUT (airflow / pressure)
OUT5 = 24VDC / 1A
O.R.1
O.R.2
(output relay 1 - SAT3)
(output relay 2 - SAT3)
= PRESSURE ALARM
= FAN ON
O.R.3
(output relay 3 - SAT3)
O.R.4
(output relay 4 - SAT3)
= HEATING DEMAND OUTPUT
= BYPASS STATUS
KWout = output for KWout capacity control (prewired)
Operation and maintenance instructio ns – CLASS UNIT TAC5
3.1 CIRCUIT BOARD SAT 3 - CID372005
The SAT3 circuit board is used for extra functions for which inputs and outputs are not included as standard in the control unit of the air handling unit. All outputs are normally open (N.O.). Maximal load: 230VAC – 4A.
The circuit board SAT3 allows for signalling of the following by means of a potential-free contact:
• Fan status - O.R. 1
• Differential pressure alarm -
• Heating demand -
• Bypass status -
O.R. 2
O.R.3
O.R.4
Installation
SAT3 must be plugged onto the control board circuit
(see fig.1).
Attention: The SAT3 must be plugged in before the circuit is powered. SAT must be plugged in correctly, wrong positioning can damage both circuits permanently.
Fig. 1
Operation and maintenance instruction s – CLASS UNIT TAC5
9
3.2 INTERNAL WIRING DIAGRAM CLASS UNIT
10 Operation and maintenance instructio ns – CLASS UNIT TAC5
4.0 Functions
4.1 OPERATING MODE
There are five main operating modes. The operating mode determines how the airflow or the fan torque is modulated. The default operating mode is Airflow control. Exceptions if Constant Torque mode has been selected in the product setup menu, in his cases it is the fan torque that will be controlled and modulated.
In all the operating modes, the supply fan(s) will operate as per the assigned mode and parameters. The exhaust fan(s) will operate according to the chosen percentage of the supply fan (%EXH/SUP ratio). The five main operating modes are:
• 1 - Airflow control:
Flow control involves operating the air handling unit to keep the pre-set airflow constant. The speed of the
fans is automatically regulated to provide correct airflow even if the filters begin to become clogged, air
terminals are blocked, etc. Airflow control mode is advantageous, since the airflow always is exactly as it was
from the beginning. It should however be noted that everything that increases the pressure drop in the
ventilation system, such as blocking of air terminals and dust accumulating in filters, causes the fans to run at
a higher speed. This results in higher power consumption and may also cause discomfort in the form of noise.
There are three airflow setpoints to be configured by the user (m³h K1, m³h K2, m³h K3).
• 2 - Torque control:
3 torque setpoints to be configured by the user (%TQ K1, %TQ K2, %TQ K3). The setpoint is configured
in % of the maximal torque. The torque control allows to vary the fan speed automatically, to
provide a variable airflow for demand controlled systems (DCV). This allows for demand controlled fan operation
or fan optimisation by a BMS system, mostly used in multi zone systems. This operation mode can partially
replace the constant pressure control when a duct pressure sensor hasn’t been installed.
• 3 - Demand control 0-10V:
The airflow is controlled by a 0-10 V signal. The control signal is connected to terminals K2&GND. The assigned
supply airflow is set as a percentage of a linear 0-10 V signal. The user defines the link with 4 parameters: Vmin,
Vmax, m³h Vmin and m³h Vmax, applied to the following diagram. The demand control mode is also
available for modulating fan torque instead of airflow (relevant for backwards fans units without Kit CA).
The principle is identical to the demand control mode operation with the difference that Vmin and Vmax are
connected to a %TQ instead of m³/h.
A CO2 sensor option is available for selection when ordering. Once this option is selected, the sensors are
prewired and pre-configured to be ready for use.
• 4 - MODE OFF :
This stops the AHU
Operation and maintenance instruction s – CLASS UNIT TAC5
11
4.2 TEMPERATURE CONTROL
There are several options available on CLASS UNIT units to ensure a comfortable temperature. The options are controlled either via supply or extract air temperature.
Supply Air Temperature
Supply temperature control is the default setting. This involves keeping a constant supply air temperature without consideration to the load in the premises. The supply air temperature is measured on sensor T5.
Extract Air Temperature
The default temperature control can be changed to Extract temperature control via the advanced setup.
The extract air temperature is measured on sensor T2. Extract air control involves keeping a constant temperature in the extract air duct (premises), by controlling the supply air temperature. This provides a uniform temperature in the premises regardless of the load. The internal sensor T2 can be replaced with the optional external room temperature sensor (CID370042).
Temperature sensor positioning :
12 Operation and maintenance instructio ns – CLASS UNIT TAC5
4.3 CHANGE OVER FUNCTION
4 PIPE AUTOMATIC CHANGE OVER
The TAC controller allows for the control of reversible coil or both cooling and heating coil. The coils are equipped with their motorised 3-way valves. The offset between the measured temperature (supply air or extract air, to be configured) and the setpoint will determine if heating or cooling is automatically activated. When the unit is equipped with reversible coil or with both a cooling and a heating coil, only one setpoint has to be configured: Comfort temperature. The neutral band prevents the cooling and heating systems from counteracting each other. The neutral band is added to the comfort setpoint for the activation of the cooling function. The neutral bands has to be configured in the advanced setup.
Operation and maintenance instruction s – CLASS UNIT TAC5
13
4.4 FROST PROTECTION
PLATE HEAT EXCHANGER
There are three strategies to protect the plate heat exchanger from freezing :
• 1 - Reduced supply air flow :
The heat exchanger is supplied with a frost protection sensor on the exhaust air (T3). If the exhaust air
temperature (T3) is >1°C and <+5°C :
• In airflow control mode and demand control, the supply air flow will modulate between 100% and 33% the
• In pressure control mode, the supply air pressure will modulate between 100% and 50% (AFlow) of the setpoint
(AFn)
If the exhaust air temperature (T3) is <1°C, the supply air fans will stop until the exhaust air temperature (T3) is
>2°C for 5 minutes.
• 2 - Modulating bypass :
The modulating bypass is controlled by the exhaust temperature sensor (T3). If:
• Exhaust temperature (T3) >+1°C: bypass closed or controlled by free cooling function
• Exhaust temperature (T3) ≤ +1°C: bypass will modulate for the exhaust temperature (T3) to exceed +1°C.
The corresponding supply air temperature will drop due to a lower airflow through the heat exchanger
These Settings can be configured in ADVANCED SETUP
4.5 TIME SCHEDULE
The controller allows 6 time slots (channels) to be configured. For each day of the week, the operation mode can be either AUTO (operate according to time slots) or OFF.
For each time slot select :
• In airflow control mode: the airflow by selecting m³h K1 / m³h K2 / m³h K3 / OFF (stop)
• In torque control mode: the torque by selecting %TQ K1 / %TQ K2 / %TQ K3 / OFF (stop)
• In demand control mode :
• with only one 0-10 V signal (default) or with 2 signals to control the
supply airflow: the link LS (percentage of the nominal link, cfr m³/h Vmin
and m³/h Vmax in setup OR cfr %TQ Vmin and %TQ Vmax in setup) and
the rate of the exhaust airflow by the supply airflow.
• with one 0-10 V signal for supply and one 0-10 V signal for exhaust (via
advanced setup): one link LS (percentage of the nominal link) for supply
and one for exhaust.
• In pressure control mode :
• Constant pressure on supply or exhaust: the pressure setpoint (percentage of the
nominal setpoint) and the rate of the exhaust airflow by the supply airflow.
• Constant pressure on supply and exhaust: one pressure setpoint (percentage of the
nominal setpoint) for supply and one for exhaust.
14 Operation and maintenance instructio ns – CLASS UNIT TAC5
5.0 Commissioning
As a human machine interface (HMI), several options are available. The HMI will enable access to the control parameters in the integrated controller. The HMI as such does not contain any programming and therefor is not mandatory.
The possible HMIs are:
TACtouch touchscreen - CID372096
This 4.3” touchscreen display is used when there is a need for a graphical HMI. The Touchscreen touchscreen is a complete graphic monitoring system where the screens are designed to be intuitive and complete, ensuring a userfriendly experience.
Position switch (COM4) - CID010007
The most basic interface to control a CLASS UNIT air handling unit is the 4 position swich. This swith will allow to control the unit to its three configured airflow (low, medium and high) and as a fourth position, the unit is switched off.
Operation and maintenance instruction s – CLASS UNIT TAC5
15
16
5.1 COMMISSIONING WITH TACtouch INTERFACE
The hand-held terminal consists of a 4.3” touch screen with a 1,5 metre long cable for connection to the air handling unit's control circuit board.
If the hand-held terminal is not used for 20 minutes, it switches over to the sleep mode.
The Touchscreen controller can be used outdoors, but it must be kept at a weatherproof place.
Data:
Operating temperature:
Maximum length of the cable:
Protection
Dimensions [mm]:
Power consumption:
0... + 50°C
>100 metres
96,8x148,8x14,5
120mA
IMAGE MANAGEMENT
Start-up image
At the first start up, the basic setup menu will be activated automatically. See section 6.1.3
BASIC SETUP
LANGUAGE
UNIT
AIRFLOW REGULATION
TEMPERATURE
FIRE ALARM
Home Screen. See Section 6.1.1.
By default, the home screen will be shown if no other menu is opened by the user or if selected in the main menu.
N.B.! The appearance of the image varies depending on the type of air handling unit and functions selected.
Main menu. See Section 6.1.2.
The main menu is presented as a rotary menu. After pressing the “menu”-button at the bottom left corner of the Home Screen, the rotary menu will be shown.
Operation and maintenance instructio ns – CLASS UNIT TAC5
5.1.1 HOME SCREEN
The home screen displays the current key data for the air handling unit and is shown is normally displayed if no other menu has been selected or if selected from the main menu. The touch screen switches to the sleep mode after 20 minutes. To leave the sleep mode, press on the touchscreen.
On the main screen, the fields are:
• Current operation mode
The operation modes are: STOP, Heating, Cooling, Post ventilation, Freecooling, Frost protection.
Current operation status
• Current date and time
• Active alarms
This fields shows the number of current alarms. By clicking on this field, more detailed information about the different alarms is available
• Menu
Accessing the main menu, see section 6.1.2
Main menu button
• Flow Chart
The flow chart is not editable by the user, the configuration of the activated options and functions is done throught the product setup (menu). A code and a special training are desired for access to this menu. The appearence of the image varies depending on the type of air handling unit and its selected functions and/or options. Flow chart symbols:
Number of current alarms
Bypass (closed/open)
Electrical heating coil
Motorised damper
(open/closed/opening)
Operation and maintenance instruction s – CLASS UNIT TAC5
17
18
5.1.2 MAIN MENU
The main menu consists of a rotary menu with 7 icons.
Control
The control menu will allow for the user to change basic parameters and operation status of the unit.
The unit can be switched on/off
The fan speed can be selected; three manual speeds + one auto speed
Post heating, post cooling and free cooling setpoints can be changed.
Alarm
Alarms are displayed on the main screen of the HMI. Active alarms can be viewed in this menu. All the alarms can be reset.
A fault can be traced by examining the function or functional component indicated in the alarm text. More information about the individual alarms, see section 7.0
If the fault cannot be immediately remidied:
Consider whether the air handling unit can continue to operate until the fault has been remedied.
Time schedule
The built-in timer enables you to control the AHU’s operating mode/time. Certain other oversteering functions such as external timer, communication, etc. affect the preset operating modes. The controller allows 6 time slots (channels) to be configured.
Time and date
The current date and time can be set and adjusted if needed. The timer automatically takes leap years into consideration. The system is preset for automatic changeover between summer time/winter time according to EU Standard.
Time schedule
Times and days can be set when the air handling unit is to run in the high speed mode, medium speed mode, low speed mode or be switched off. For each day (Monday -
Sunday), six different time slots can be configured. The time slots are subsequent.
Seasonal management
The seasonal management menu allows for the deactivation of heating coils, cooling coils and bypass freecooling function based upon a year calendar. In between the programmed interval, the selected function is OFF.
Operation and maintenance instructio ns – CLASS UNIT TAC5
Basic Setup
The basic setup menu will guide the user through the most critical settings of the air handling unit. This setup procedure is described in detail, section 6.1.3
Readings
The operating status and the Settings can be read. Used for performance checks and for generally checking Settings, settings, power consumption, etc. No Settings can be altered in this menu group.
Maintenance
Configuration of service related settings. A maintenance warning interval can be configured as wel as the filter clogging alarm.
Advanced setup
A code and a special training are desired for access to this menu.
BASIC SETUP
LANGUAGE
UNITS
AIRFLOW REGULATION
TEMPERATURE
FIRE ALARM
Operation and maintenance instruction s – CLASS UNIT TAC5
19
20
5.1.3 BASIC SETUP
When the air handling unit is started up for the first time, the commissioning menu is automatically displayed. At the very end of the commissioning (menu) the commissioning of the unit has to be confirmed by the service technician. Once the commissioning has been confirmed, the commissioning menu will not be displayed as first menu any more. The commissioning menu, however, will remain accessible through the advanced setup . See
Section 6.1.4.
Language
The language desired can be set here. The language setting can be changed at any time in the basic setup menu.
Setting
Language
Settings range
Languages as displayed
Factory setting
English
Units
The desired unit can be set here. The unit setting can be changed at any time in the basic setup menu.
Setting
Unit
Settings range m³/h l/s
Factory setting m³/h
Airflow regulation
The desired control mode can be set here. The setting can be changed at any time in the basic setup menu. Depending on the selected function, flows can be set as (l/s, m³/h), pressure
(Pa), input signal strenght (%) or torque (%). For both “Airflow control” and “Torque control”, three setpoints are available: Low, medium and high.
Setting
Operating mode
Settings range
OFF
Airflow
Demand control
Pressure
Torque
Factory setting
Airflow
BASIC SETUP
BASIC SETUP
LANGUAGE
UNITS
AIRFLOW REGULATION
TEMPERATURE
FIRE ALARM
BASIC SETUP
LANGUAGE
UNITS
AIRFLOW REGULATION
TEMPERATURE
FIRE ALARM
BASIC SETUP
LANGUAGE
UNITS
AIRFLOW REGULATION
TEMPERATURE
FIRE ALARM
Operation and maintenance instructio ns – CLASS UNIT TAC5
Constant airflow
Flow control involves operating the air handling unit to keep the preset airflow constant. The speed of the fans is automatically regulated to provide correct airflow even if the filters become clogged, diffusers are blocked, etc. The exhaust air fan is controlled as a slave. A ratio between exhaust and supply pressure can be configured in order to create over, under or balanced pressure. For units with backward fans, constant airflow can only be selected if the “constant air kit” has been ordered as an option. The desired setpoint is preset in (l/s, m³/h).
Setting
Airflow K1/K2/K3
Ratio exhaust/supply
Range
0...max
5...999%
Factory setting
100%
Enable pressure alarm No
Yes
DP Supply/Exhaust for pressure alarm
Yes
25...999Pa
200Pa
Initialisation airflow (l/s, m³/h)
Pressure alarm initialisation
No
Yes
Yes
Torque control
The constant torque operating mode allows to vary the fan speed automatically, to provide a variable airflow for demand controlled systems. This operating mode can partially replace the constant pressure control when a duct pressure sensor hasn’t been installed. The exhaust air fan is controlled as a slave. A ratio between exhaust and supply pressure can be configured in order to create over, under or balanced pressure. The desired setpoint is preset in %. The Torque control mode can be deactivated in the advanced setup.
Setting
Airflow K1/K2/K3
Range
0...100%
Ratio exhaust/supply 5...999%
Factory setting
100%
Demand control
The airflow desired is regulated in response to 0-10 V input signals from an external sensor, such as a carbon dioxide or a humidity sensor. The function can be configured with a positive or a negative logic. A ratio between exhaust and supply pressure can be configured in order to create over, under or balanced pressure. The desired setpoint is preset in (l/s, m³/h). The “sleep factor” is a lower operating rate for the unit (due to e.g. low occupancy) that will be activated by speed “III “
Setting Range Factory setting
Vmin
Vmax m³/h ~Vmin
0...10V
0...10V
(l/s, m³/h)
1,0V
10,0V m³/h ~Vmax
Ratio exhaust/supply
(l/s, m³/h)
5...999%
Sleep factor on K3
DP Supply/Exhaust for pressure alarm
10...100%
Enable pressure alarm No
Yes
10...999Pa
Initialisation airflow (l/s, m³/h)
Pressure alarm initialisation
No
Yes
100%
100%
Yes
200Pa
Yes
Constant pressure
The airflow automatically varies to provide constant pressure in the ducting. The duct pressure is measured by an external in-duct pressure sensor which is connected to the control unit’s BUS communication or the an analogue 0...10V input. The function can be configured on supply air, extract air or supply and extract air. The first two configurations will have the second set of fans be controlled as a slave. A ratio between exhaust and supply pressure can be configured in order to create over, under or balanced pressure. The initialisation will allow for an automatic calculated pressure setpoint, determined by the nominal airflow. The “sleep factor” is a lower operating rate for the unit (due to e.g. low occupancy) that will be activated by speed “III “
Setting Range Factory setting
Supply Control Supply
Exhaust
Supply+Exhaust
Ratio exhaust/supply 5...999%
Sleep factor on K3 10...100%
Pressure initialisation Via Airflow
Via Pressure
Start reference initialisation
Yes
No
100%
100%
Airflow
Yes
Operation and maintenance instruction s – CLASS UNIT TAC5
21
22
Temperature
The temperature control can be configured as a supply air control or an extract air control. By default, this function is configured as a supply air temperature control. Changes to this configuration are done in the advanced setup; see
Section 6.1.4
Setting
T° heating
T° Cooling
T° Freecooling
Settings range
0...45°C
0...99°C
0...99°C
Factory setting
20,0°C
24,0°C
15°C
Fire Alarm
An external fire detection system is used to control the air handling unit in case of emergency. The fire alarm function is activated by means of digital input
IN3.
Setting
Input
Supply airflow
Extract airflow
Settings range
Normally open
Normally closed
0...max
0...max
Factory setting
Normally closed
BASIC SETUP
LANGUAGE
UNITS
AIRFLOW REGULATION
TEMPERATURE
FIRE ALARM
BASIC SETUP
LANGUAGE
UNITS
AIRFLOW REGULATION
TEMPERATURE
FIRE ALARM
Periodic maintenance
Built-in timer for maintenance warning; if the maintenance interval is exceeded, a maintenance reminder will be displayed.
Setting Settings range
3 monthly warning Yes
No
12 monthly warning Yes
No
Factory setting
No
No
Commissioning completed
When the commissioning has been successfull and this is confirmed in this menu, the commissionig menu will not be activated automatically anymore.
Setting
Confirmation of successfull commissioning
Settings range
Yes
No
Factory setting
No
BASIC SETUP
UNITS
AIRFLOW REGULATION
TEMPERATURE
FIRE ALARM
PERIODIC MAINTENANCE
BASIC SETUP
AIRFLOW REGULATION
TEMPERATURE
FIRE ALARM
PERIODIC MAINTENANCE
COMMISSIONING COMPLETED
Operation and maintenance instructio ns – CLASS UNIT TAC5
5.1.4 ADVANCED SETUP
N.B.! The appearance and content of this menu varies depending on the type of air handling unit and functions and/or options selected. A code and a special training are needed to access this menu.
Attention: The settings range for most of the functions is defined for maximal flexibility. The factory setting is the advised setting, deviating from this setting requires carefull consideration.
Stop fan with 0...10V
Function only availalbe if “demand control” function has been selected in basic setup. With this function, the fans can be stopped if the 0...10V control signal is below or above a specified setpoint. The control signal is connected to the analogue input K2.
Setting
Stop if <Vlow
Vlow
Stop if >Vhigh
Vhigh
Settings range
No
Yes
0...10V
No
Yes
0...10V
Second 0...10V control signal
Factory setting
Yes
0,8V
Yes
10,0V
Function only availalbe if “demand control” function has been selected in basic setup. With this function, a separate 0...10V control signal for the extract air can be activated. The control signal is connected to the analogue input K3.
Setting
0...10V on K3?
Control
Settings range
No
Yes
Exhaust
Supply
Factory setting
No
Exhaust
Pressure control
Function only availalbe if “pressure control” function has been selected in basic setup. The reaction speed of the fans for the balancing of the constant pressure system can be modified. A higher Setting will result in a faster reaction speed; a lower Setting will result in a slowerreaction speed.
The system can be defined as a negative or a positive logic. A negative logic airflow drops when analogue signal on K2 is > than the setpoint.
Setting Settings range
Reaction speed 0...10
Logic Positive
Negative
Factory setting
10
Negative
ADVANCED SETUP
ADVANCED SETUP
STOP FAN WITH 0...10V
2ND 0...10 CONTROL SIGNAL
CONSTANT PRESSURE
SOFT STOP
START TORQUE
ADVANCED SETUP
STOP FAN WITH 0...10V
2ND 0...10 CONTROL SIGNAL
CONSTANT PRESSURE
SOFT STOP
START TORQUE
ADVANCED SETUP
STOP FAN WITH 0...10V
2ND 0...10 CONTROL SIGNAL
CONSTANT PRESSURE
SOFT STOP
START TORQUE
Operation and maintenance instruction s – CLASS UNIT TAC5
23
24
Stop fan when pressure alarm
Possibility to stop the fans automatically in case of a pressure alarm.
Setting
Stop fans
Settings range
No
Yes
Factory setting
No
Start torque
Possibility to change the fans’s starting torque.
Setting
Start Torque
Settings range
0...100%
Deactivate softstop
Factory setting
2%
With this function, the “OFF” function is deactivated.
Setting
Softstop
Settings range
Yes
No
Factory setting
No
Temperature
In this menu advanced temperature control parameters can be modified.
Supply air involves keeping a constant supply air temperature without consideration to the load in the premises.
Extract air involves keeping a constant temperature in the extract air duct (premises), by modulating the supply air temperature.
The reaction speed of capacity control signal can be modified.
A higher Setting will result in a smoother control; a lower Setting will result in a faster reaction speed. but also greater risc of oscillations.
Setting
Supply or Extract temperature control?
Reaction speed
Supply air, min
Settings range
Supply
Extract
1...10
0...20°C
Supply air, max 16...50°C
Stop fan if T°Supply <5°C No
Yes
Factory setting
Supply
1
15,0°C
28,0°C
No
ADVANCED SETUP
2ND 0...10 CONTROL SIGNAL
CONSTANT PRESSURE
STOP FAN
START TORQUE
DEACTIVATE SOFTSTOP
ADVANCED SETUP
CONSTANT PRESSURE
STOP FAN
START TORQUE
DEACTIVATE SOFTSTOP
TEMPERTURE
ADVANCED SETUP
CONSTANT PRESSURE
DEACTIVATE SOFTSTOP
TEMPERATURE
BOOST
POST VENTILATION
Operation and maintenance instructio ns – CLASS UNIT TAC5
Boost
The boost mode can be used to force the supply and extract airflow to a higher setpoint, when specific conditions are met.
The boost mode can be activated with a contact connected to the digital input IN9 or by an analogue 0...10V control signal connected to input K3. The boost setpoint is preset in (l/s, m³/h).
Setting
Supply / Extract airflow
Boost activation on
RH on / off
Vmin/max RH on K3
RH ~Vmin/max
Settings range
0...max
Contact
RH
0...100%
0...10V
0...100%
Factory setting
Contact
60% / 40%
2,0V / 9,5V
2% / 95%
Post ventilation
The post ventilation function is used to keep the fans running during a specified laps of time. This function is activated automatically when an electrical heating coil is activated.
Setting
Activation
Time
Settings range
No
Yes
Factory setting
No
0...9999sec 90sec
ADVANCED SETUP
DEACTIVATE SOFTSTOP
TEMPERATURE
BOOST
POST VENTILATION
EXTERNAL COILS
ADVANCED SETUP
TEMPERATURE
BOOST
POST VENTILATION
INTERNAL COILS
EXTERNAL COILS
Operation and maintenance instruction s – CLASS UNIT TAC5
25
Internal coils
Electrical postheating coil
The electrical postheating coil is installed and configured in factory. The electrical postheating coil will always have its separate power supply and main switch. The capacity of the coil will be controlled proportionally in order to keep a temperature as defined by the selected operating mode.
Setting
Control mode
Settings range
Exhaust
Supply
Setpoint -9,9...99,9°C
PID - Proportional Band 0...100
PID - Integral
PID - Derivate
0...100
0...100
Factory setting
Supply
21,0°C
5
30
11
Water postheating coil
The water postheating coil is installed and configured in factory. The 3-way valve is not installed and will have to be installed and wired on site. The capacity of the coil will be controlled proportionally in order to keep a temperature as defined by the selected operating mode.
The output O.R.3 on the optional “SAT3” output relay, is activated whenever heating is desired.
Setting
Control mode
Setpoint
Reaction Speed
Settings range
Exhaust
Supply
-9,9...99,9°C
1...10
Factory setting
Supply
21,0°C
5
Frost protection
Frost protection plate heat exchangers
In environments where the extract air can occasionally be humid, the defrosting function can be activated to protect the heat exchanger from frosting. There are four strategies: down control of the supply air volume, modulating by-pass control, modulation of capacity of a preheating coil, differential pressure measurement (cold climate option). If non of these measures are effective, the air handling unit can be stopped by limting the minimal supply air temperature. When the Frost protection cycle is active, it will be indicated on the HMI. The configurable temperatures are exhaust temperatures.
26
Setting
T° Low
T° High
Stop supply airflow
Frost protection cycle active
Frost protection alarm
Settings range
1...3°C
1...5°C
No
Yes
Factory setting
+1,0°C
+5,0°C
Yes
ADVANCED SETUP
BOOST
POST VENTILATION
INTERNAL COILS
EXTERNAL COILS
INTERNAL COILS
Operation and maintenance instructio ns – CLASS UNIT TAC5
0-10V output
The controller has as a standard feature two configurable analogue 0...10V outputs. The outputs represent the actual airflow (or torque) or the actual pressure delivered by one of the selected fans.
Setting
Output 1
Output 2
Settings range
Flow Fan 1
Pressure Fan 1
Flow Fan 2
Pressure Fan 2
Flow Fan 3
Pressure Fan 3
Flow Fan 4
Pressure Fan 4
Torque Fan 1
Torque Fan 2
Torque Fan 3
Torque Fan 4
Flow Fan 1
Pressure Fan 1
Flow Fan 2
Pressure Fan 2
Flow Fan 3
Pressure Fan 3
Flow Fan 4
Pressure Fan 4
Torque Fan 1
Torque Fan 2
Torque Fan 3
Torque Fan 4
Factory setting
Flow Fan 1
Pressure Fan 1
Modbus configuration
The MODBUS RTU communication requires an additional satellite circuit (CID050043) which is used as communication interface. The communication protocol used is
MODBUS RTU, RS485.
Setting
Adress
Baudrate
Parity
Settings range
1...247
1200
4800
9600
19200
No
Yes
Factory setting
1
9600
No
LAN configuration
The MODBUS TCP/IP communication requires an additional satellite circuit (CID025072) which is used as communication interface. The communication protocol used is Modbus TCP/IP on Ethernet network over twisted pair
10 BASE T/100Base-TX IEEE 802.3.
Setting Settings range
Factory setting
Manual IP configuration DHCP
Manual
IP adress
Netmask
Gatway
192.167.1.1
255.255.255.0
0.0.0.0
Operating time
For maintenance purposes, operating timers can be activated. If the “service alarm time” or the “Stop fan” timers are triggered, the according alarm will be shown and the unit will switch to “OFF”-mode.
Setting
Reset timer
Settings range
No
Yes
Factory setting
No
Fan run time activation No
Yes
Display time No
Yes
Service alarm time
Stop fan
No
No
0...999999h
0h
0...999999h
0h
Operation and maintenance instruction s – CLASS UNIT TAC5
27
6.0 Preventive maintenance
Attention : before handling and/or opening the access panels it is compulsory to shut down the unit. Do not isolate the power supply whilst the unit is running. If KWin and\or KWout are installed, then isolate the corresponding power supplies.
Regular maintenance is essential to guarantee good operation of the air handling unit and a long service life. The maintenance frequency will depend on the application and on the actual environment conditions but the following are general guidelines:
6.1 ONCE THE UNIT OPERATES IN NORMAL CONDITION
Replace the filters with a kit of replacement filters.
6.2 EVERY 3 MONTHS
- Check for any alarms indicated on the control device. In case of an alarm refer to troubleshooting section.
- Check the state of filter clogging. The control device allows a pre-defined ‘filter alarm’ threshold to be set.
Replace filters if necessary. Filters that are too clogged can generate the following problems:
- Insufficient ventilation
- Excessive increase of fan rotation speed
- Excessive sound levels
- Excessive power consumption (power consumption will increase exponentially to an increase
in pressure drop, for a constant airflow)
- Unfiltered air passing through the heat exchanger (risk of clogging) and into ventilated rooms.
The list of replacement filter kits for each unit can be downloaded from our website.
- To locate the filter, refer to schemas on point 2.0.
- Inspection and cleaning of the inside of the unit:
• Vacuum clean any accumulations of dust in the unit.
• Inspect and gently vacuum clean the heat exchanger if necessary. Use a brush to protect the fins.
• Clean any condensation stains
• Clean any accumulations in the drain pan.
28 Operation and maintenance instructio ns – CLASS UNIT TAC5
6.3 EVERY 12 MONTHS
1.
Fan maintenance:
Check again whether the power supply is shut down and fans are not running.
Inspect and clean the fan impellers to remove any dirt deposits, be careful not to alter the impeller balance
(do not remove balancing clips). Check the impeller to make sure that it is not out of balance. Clean or brush off the
fan motor. It can also be cleaned by carefully wiping it with a damp cloth that has been dipped in a solution of water and
detergent. Clean the fan space, if needed. Remove the fans if necessary.
2.
Check seals on the unit:
Ensure that the side access panels are fully closed and that the seals are intact. Replace if necessary.
Operation and maintenance instruction s – CLASS UNIT TAC5
29
7.0 Troubleshooting
The TAC control board generates and reports 18 types of alarms.
The alarms are subdivided into auto resetting and non-auto resetting alarms. For the latter, a reset will be necessary once the problem has been resolved.
For each type of alarm, a full text description will be displayed on the user interface depending on the alarm type:
- Activation of contact relay (NC or NO contact)- AL 1
- Activation of SAT3 OR1 in case of pressure alarm, provided that the optional module SAT 3 is installed on the control board.
- “Alarm”, “Pa” and “AF” activated LED’s on control board
- Alarm on user interface.
- Alarm communication with networking modules provided that an optional communication module
(Modbus RTU, MODBUS TCP/IP, and KNX) is installed on the TAC control board.
7.1 TYPE 1: ALARM INDICATING A FAN FAILURE
- Conditions:
- Causes:
• Failure of fan Fx. This problem is usually caused by the fan motor.
If not, the failure may be caused by an internal cable (control or power) or by the TAC circuit.
- Effects:
B.11
B.12
B.13
B.14
AL1 relay
Alarm
O.R.1
/
Displayed on HMI TACtouch
Text displayed
Fan 1 failure
Fan 2 failure
Fan 3 failure
Fan 4 failure
TAC control board
LED ALARM
ON
Auto reset: yes
LED AF
/
LED ALARM
RED
LED Pa
Fans stopped
/
30 Operation and maintenance instructio ns – CLASS UNIT TAC5
7.2 TYPE 2: ALARM ON THE PRESSURE VARIATION
- Conditions:
• Mode airflow control or demand control. Unit must have forward fans or backward fans with kit CA.
• External pressostat connected on IN2 input
- Causes:
• Pressure alarm setup in airflow control or demand control mode
• External pressostat connected on IN2 input has triggered
- Effects:
P.10
P.20
S.40
Displayed on HMI TACtouch
Text displayed
Pressure alarm - Supply air
Pressure alarm - Extract air
Pressure alarm from Pressure Switch*
LED ALARM LED Pa
/ RED
AL1 relay
/
O.R.1
Closed
TAC control board
LED ALARM
ON
Auto reset: yes
* unless the status has been changed in advanced setup
LED AF
/
Fans
Run*
Operation and maintenance instruction s – CLASS UNIT TAC5
31
7.3 TYPE 3: ALARM REPORT DURING REFERENCE PRESSURE INITIALIZATION
- Conditions:
• Mode Airflow control or Demand control: during the initialization of the pressure alarm. In this case, the unit must have
forward fans or backward fans with kit CA.
• Mode Pressure control: during the initialization of the pressure reference via airflow
- Causes:
The reference pressure (Paref) cannot be identified and the fans are stopped. 4 possibilities:
1.
Actual airflow < requested airflow: The requested working point is ‘too high’ (too high pressure loss)
for the maximal available pressure at the requested airflow for this fan.
2.
Actual airflow > requested airflow: the nominal airflow requested to initialize the pressure alarm
cannot be reached because the lower limit of the fan’s operating zone has been reached.
3.
Very unstable pressure (pumping).
4.
Assigned airflow not reached after 3 minutes.
If this occurs during initializing an alarm pressure, there are 2 options:
1.
No action is taken: the control will operate without a pressure alarm.
2.
Corrective action is taken (change the working point to one located in the working
zone of the fan, by reducing the pressure system, modifying the nominal airflow…) and restart the setup operation.
If this occurs during initializing of the assignment pressure in pressure control mode: Corrective action must be taken
(change the working point to one located in the working zone of the fan, by reducing the pressure system,
modifying the nominal airflow …) and restart the setup operation.
- Effects:
P.20
P.21
P.22
P.23
P.24
P.25
P.26
P.27
Displayed on HMI TACtouch
Text displayed
Initialisation of the reference pressure - Unstable supply air pressure
Initialisation of the reference pressure - Unstable extract air pressure
Initialisation of the reference pressure - Supply air flow too low
Initialisation of the reference pressure - Extract air flow too low
Initialisation of the reference pressure - Supply air flow not reached
Initialisation of the reference pressure - Extract air flow not reached
Initialisation of the reference pressure - Supply air flow too high - Min. limit of the motor
Initialisation of the reference pressure - Extract air flow too high - Min. limit of the motor
LED ALARM LED Pa
RED /
AL1 relay
ALARM
O.R.1
/
TAC control board
LED ALARM
ON
Auto reset: no
LED AF
/
Fans
Stopped
32 Operation and maintenance instructio ns – CLASS UNIT TAC5
7.4 TYPE 4: ALARM INDICATING THE SYSTEM CANNOT FULFIL THE SETPOINT
- Conditions:
- Causes:
S.11
S.12
S.13
S.14
S.20
S.21
S.22
S.23
S.24
S.25
S.34
S.35
- Effects:
Displayed on HMI TACtouch
Text displayed
“Constant Pressure” fan 1 - Measured pressure too high - Minimum air flow reached
“Constant Pressure” fan 1 - Measured pressure too low - Maximum air flow reached
“Constant Pressure” fan 3 - Measured pressure too high - Minimum air flow reached
“Constant Pressure” fan 3 - Measured pressure too low - Maximum air flow reached
“Demand control” fan 1 - Air flow too low - Reduce the pressure on this fan
“Demand control” fan 1 - Air flow too high - Minimum limit of the motor reached
“Demand control” fan 2 - Air flow too low - Reduce the pressure on this fan
“Demand control” fan 2 - Air flow too high - Minimum limit of the motor reached
“Demand control” fan 3 - Air flow too low - Reduce the pressure on this fan
“Demand control” fan 3 - Air flow too high - Minimum limit of the motor reached
“Constant Air Flow” fan 3 - Air flow too low - Reduce the pressure on this fan
“Constant Air Flow” fan 3 - Air flow too high - Minimum limit of the motor reached
AL1 relay
/
O.R.1
/
TAC control board
LED ALARM
ON
Auto reset: yes
LED AF
/
LED ALARM LED Pa
RED
Fans
/
/
7.5 TYPE 5: ALARM INDICATING A DATA FAILURE IN THE CONTROL CIRCUIT
- Conditions:
- Causes:
• Crucial data from the circuit board has been lost
- Effects:
Displayed on HMI TACtouch
Text displayed LED ALARM
D.10
D.20
Programme Error
Data Error
RED
AL1 relay O.R.1
TAC control board
LED ALARM LED AF
Alarm status / ON
Auto reset: no
/
- Solutions:
• Try a TOTAL RESET of the data using the advanced setup. If still not resolved, order a new circuit board.
LED Pa
Fans
Stopped
/
Operation and maintenance instruction s – CLASS UNIT TAC5
33
7.6 TYPE 6: FIRE ALARM
- Conditions:
• Fire alarm input must be connected to a fire detection system
- Causes:
Activation of fire alarm input, IN3, connected to a fire detection system.
IN3 can be configured to work as NO open contact by default or as NC if configured so in the advanced setup.
- Effects:
Displayed on HMI TACtouch
Text displayed
F.10
F.11
FIRE ALARM
End of the fire alarm
LED ALARM
RED
LED Pa
/
AL1 relay
Alarm status
O.R.1
/
TAC control board
LED ALARM
ON
Auto reset: no
LED AF
/
* The fans are stopped by default in the event of a fire alarm but, via the advanced setup, it is possible to configure a fixed airflow for supply (contact IN7 needs to be closed) and for exhaust
(contact IN8 needs to be closed).
Fans
*
34 Operation and maintenance instructio ns – CLASS UNIT TAC5
7.7 TYPE 7: MAINTENANCE ALARM
- Conditions:
• the running hours feature must be enabled in advanced setup
- Causes:
• SERVICE ALARM: the fan operating time (in hours) has exceeded the configurable threshold
• STOP FAN: the fan operating time (in hours) has exceeded the configurable threshold. This alarm stops the fans
- Effects:
Displayed on HMI TACtouch
Text displayed LED ALARM LED Pa
M.10
M.11
M.21
M.22
Maintenance 3 months
Maintenance 6 months
Operating hours
Operating hours - AHU off
RED /
AL1 relay
Alarm status
O.R.1
/
TAC control boards
LED ALARM
ON
LED AF
/
Reset via “fan run time” (TACtouch) or “alarm menu” (App)
Fans
Stopped if SERVICE STOP
FAN *
* unless the status has been changed in advanced setup
7.8 TYPE 8: ALARM INDICATING A COMMUNICATION BREAKDOWN
BETWEEN THE TAC CIRCUIT AND THE HMI
- Conditions:
• User interface is connected
- Causes:
• Communications failure between the TAC circuit and the HMI
- Effects:
CB COM ERROR
Text displayed
Displayed on HMI TACtouch
LED ALARM
Red
LED Pa
/
AL1 relay
Alarm status
O.R.1
/
TAC control board
LED ALARM
/
Auto reset: yes
LED AF
/
Fans
/
Operation and maintenance instruction s – CLASS UNIT TAC5
35
7.9 TYPE 9: ALARM INDICATING A T° SENSOR T1/T2/T3 FAILURE
T.10
T.11
T.20
T.21
T.30
T.31
- Conditions:
- Causes:
One or more of the T° sensors T1/T2/T3 connected to the TAC circuit and mounted on heat exchanger is
defect or not connected. These sensors are needed for the bypass control and the anti-frost procedure.
- Effects:
Displayed on HMI TACtouch
Text displayed LED ALARM
Sensor T1 disconnected
Sensor T1 short circuit
Sensor T2 disconnected
Sensor T2 short circuit
Sensor T3 disconnected
Sensor T3 short circuit
RED
AL1 relay
Alarm status
O.R.1
/
TAC control board
LED ALARM
ON
Manual reset mandatory.
LED AF
/
LED Pa
Fans
Stopped
/
7.10 TYPE 10: ALARM INDICATING FAILURE ON T° SENSOR T4
- Conditions:
• Only with internal water heating coil (IBA) option
- Causes:
• T° sensor T4 located on the coil and connected to the TAC circuit is defective (open or short circuit) or not connected.
This is used to prevent frosting of the internal heating coil. In this case, as a safety measure, the 3-way valve is
opened and the circulator contact is closed.
- Effects:
Displayed on HMI TACtouch
Text displayed LED ALARM LED Pa
T.40
T.41
Sensor T4 disconnected
Sensor T4 short circuit
RED /
AL1 relay
Alarm status
O.R.1
/
TAC control board
LED ALARM
ON
Manual reset mandatory.
* unless the status has been changed in advanced setup
LED AF
/
Fans
/
36 Operation and maintenance instructio ns – CLASS UNIT TAC5
7.11 TYPE 10 BIS: DRAIN PUMP ALARM
- Conditions:
• Only for CLASS UNIT LP
- Causes:
The level of condensate is higher than a set Setting (approx. 1.5 cm).
It can also be activated if the pump is not present or defective
- Effects:
Displayed on HMI TACtouch
Text displayed
R.10
Condensate tray full
LED ALARM
RED
LED Pa
/
AL1 relay O.R.1
TAC control board
LED ALARM LED AF
Alarm status / ON /
When activated, the supply and exhaust fans are stopped. This alarm is automatically reset when the water level in the drain pan is lower than the setpoint, and the fans restart automatically.
Fans
Stopped if SERVICE STOP
FAN
7.12 TYPE 11: ALARM INDICATING FAILURE ON T° SENSOR T5
- Conditions:
• Only with post-heating, post-cooling or free cooling with heat wheel or modulating bypass option
- Causes:
• T° sensor T5 located in the supply duct and connected to the TAC circuit is open, or short-circuited. This sensor is used
to regulate the post-heating or post-cooling function in the case of comfort T° control on T5 or to control the high
and low thresholds to limit the supply air temperature in the case of comfort T° control on T2.
- Effects:
Displayed on HMI TACtouch
Text displayed LED ALARM LED Pa
T.50
T.51
Sensor T5 disconnected
Sensor T5 short circuit
RED /
AL1 relay
Alarm status
O.R.1
/
TAC control board
LED ALARM
ON
Manual reset mandatory.
LED AF
/
Fans
/
Operation and maintenance instruction s – CLASS UNIT TAC5
37
7.13 TYPE 12: ALARM INDICATING THAT THE COMFORT T° IS TOO LOW RELATIVE TO SETPOINT T°
- Conditions:
• Only with post-heating option
- Causes:
• The comfort T° setpoint cannot be reached (actual T° lower than setpoint during 15 minutes, or 30 minutes
if comfort on T2 instead of T5, while post heating is at maximum.)
- Effects:
S.50
Displayed on HMI TACtouch
Text displayed
Post-heating - T° of the supply air too low
LED ALARM
RED
LED Pa
/
AL1 relay
/
O.R.1
/
TAC control board
LED ALARM
ON
Auto reset: yes
LED AF
/
Fans
/
7.14 TYPE 13: ALARM INDICATING HEAT EXCHANGER FROST PROTECTION ALERT
- Conditions:
• Only with post-heating option
- Causes:
Frost protection is only selected with electrical pre-heating coil (KWin) or water preheating coil (BAin) or modulating bypass.
With KWin or BAin option: In certain air T° conditions as measured on the exhaust airflow after heat recovery, indicating
that the internal electrical KWin coil or external hydraulic coil (BAin) has reached its limit, the TAC control can take
over to guarantee the anti-frost function.
If T° < assignment T°-1,5°C for more than 5 minutes: supply and exhaust airflow reduction of 33% if airflow control or
demand control and of 25%
if pressure control mode, for 15 minutes.
- Effects:
Displayed on HMI TACtouch
A.10
Anti-freeze - Reduced air flows
Text displayed LED ALARM
RED
LED Pa
/
AL1 relay
/
O.R.1
/
TAC control board
LED ALARM
ON
Auto reset: yes
LED AF
ON
Fans
/
38 Operation and maintenance instructio ns – CLASS UNIT TAC5
7.15 TYPE 14: ALARM INDICATING FROST PROTECTION ALERT – FANS STOPPED T°
- Conditions:
• Frost protection is only selected for units with electrical preheating (KWin) or water preheating (BAin) or if modulating
bypass
- Causes:
• With KWin or BAin option: in certain air T° conditions as measured on the exhaust airflow after the heat recovery,
indicating that the internal electrical KWin coil or external hydraulic coil (BAin) has reached its limit, the TAC
control can take over to guarantee the anti-frost function.
If T° < -5°C during 5 minutes, fans are stopped.
• With modulating bypass in frost protection (« A-FREEZE » or « AF+FREECOOL » in the advanced setup),
this alarm indicates that the extracted air temperature at the exchanger output (T3 sensor) has not exceeded 1°C
during 15 minutes after that the bypass has been opened at 100%.
- Effects:
Displayed on HMI TACtouch
Text displayed LED ALARM LED Pa
A.11
Anti-freeze - Fans stopped RED /
AL1 relay
Alarm status
O.R.1
/
TAC control board
LED ALARM
ON
Manual reset mandatory.
LED AF
Blinking
7.17 TYPE 15 BIS: ALARM INDICATING THAT THE COMFORT T° IS TOO HIGH
RELATIVE TO SETPOINT T°
- Conditions:
• Only with post cooling option
- Causes:
The comfort T° setpoint cannot be reached (actual T° lower than setpoint during 15 minutes, or 30 minutes
if comfort on T2 instead of T5, while post cooling is at maximum).
- Effects:
Fans
Stopped
S.60
Displayed on HMI TACtouch
Text displayed
Post-cooling - T° of the supply air too high
LED ALARM
RED
LED Pa
/
AL1 relay
/
O.R.1 relay of SAT3
/
TAC control board
LED ALARM
ON
Auto reset: yes
LED AF
/
Fans
/
Operation and maintenance instruction s – CLASS UNIT TAC5
39
7.18 TYPE 16: ALARM INDICATING THAT THE SUPPLY T° IS TOO LOW
- Conditions:
• Only with post heating or cooling option
- Causes:
• This alarm indicates that the supply temperature (T5) is lower than 5°C. The fans are stopped for 1 minute.
The alarm is configurable through the advanced setup and is disabled by default.
- Effects:
S.50
S.60
Displayed on HMI TACtouch
Text displayed
Post-heating - T° of the supply air too low
Supply air T° too low - Fan stopped
LED ALARM
RED
AL1 relay
Alarm Status
O.R.1
/
TAC control board
LED ALARM
ON
Manual reset mandatory.
LED AF
/
Fans
Stopped
LED Pa
/
7.19 TYPE 17: ALARM INDICATING HYDRAULIC COILS FROST PROTECTION ALERT
- Conditions:
• Only with internal hydraulic post heating coil (IBA), or external heating coil (EBA)
- Causes:
• Indicates that the anti-frost protection temperature of the hydraulic coil is lower than 4°C (configurable through
advanced setup, it is important to reduce this Setting for BAin coil if an antifreeze is in the fluid). The 3-way valve is
automatically opened at 100% for 15 minutes and the heating demand contact is closed (output SAT3 O.R.3). If the
AHU is running, the alarm is sent after 2 minutes for a preheating coil and immediately for the others; if the AHU is not
running, the alarm is sent after 5 minutes.
- Effects:
Displayed on HMI TACtouch
LED ALARM LED Pa
A.40
A.41
A.42
A.43
Text displayed
Anti-freeze protection of the internal post-heater (IBA)
Anti-freeze protection of the waterborne post-heater (EBA+)
Anti-freeze protection of the waterborne post-cooler (EBA-)
Anti-freeze protection of the waterborne reversible coil (EBA+-)
Red /
AL1 relay
Alarm Status
O.R.1
/
TAC control board
LED ALARM
ON
Manual reset mandatory.
LED AF
/
Fans
Stopped
40 Operation and maintenance instructio ns – CLASS UNIT TAC5
7.20 TYPE 18: ALARM INDICATING AN INCORRECT POSITION OF THE MODULATING
BYPASS RELATIVE TO THE ORDERED POSITION
- Conditions:
• units with modulating bypass
- Causes:
• This alarm indicates that the modulating bypass has not reached the ordered position within 10 seconds.
The most common reason for this is a damaged position sensor on the bypass actuator, and this must be replaced.
Other reasons may be that the control board output is damaged, implying the replacement of the board, or a
mechanical blocking verified by a visual inspection of the bypass
- Effects:
B.20
Displayed on HMI TACtouch
Text displayed
Position of the modulating bypass incorrect
LED ALARM
RED
LED Pa
/
AL1 relay
Alarm Status
O.R.1
/
TAC control board
LED ALARM
ON
Manual reset mandatory.
LED AF
/
Fans
Stopped
7.21 TYPE 19: ALARM INDICATING THAT THE HOURS LIMIT FOR THE MAINTENANCE OF
THE FILTERS HAS BEEN REACHED
- Conditions:
• The basic setup parameter “Filters Resets” must be >0
- Causes:
• Alarm indicating that the hours limit for the maintenance of the filters has been reached
- Effects:
Text displayed
FILTERS ALARM
Displayed on HMI TACtouch
LED ALARM
Red
LED Pa
/
AL1 relay
/
O.R.1
/
TAC control board
LED ALARM
ON
Auto reset: via dedicated reset
LED AF
/
Fans
/
Operation and maintenance instruction s – CLASS UNIT TAC5
41
7.22 TYPE 20: ALARM INDICATING THAT THE DEFROST PROCESS IS ACTIVE
- Conditions:
• Unit with counter flow heat exchanger
- Causes:
• The ice forming inside of the plate heat exchanger is genrating a pressure drop that is to high for the current airflow.
This detection requires a Modbus pressure sensor placed on the heat exchanger and that the modulation
of the fans speed is based on the airflow and not on torque
• When the previous detection is not available, the supply T° is checked and if it falls below 11°C, it is considered
that is due to the ice that reduces the heat exchanger efficiency
- Effects:
A.20
Defrost
Displayed on HMI TACtouch
Text displayed LED ALARM
RED
LED Pa
/
AL1 relay
/
O.R.1
/
TAC control board
LED ALARM
ON
Auto reset: yes
7.23 REC TABLE
In the control board the “REC type” is used to define the type unit. When replacing the control board, the REC type needs to be configured in the product setup menu. The product setup menu is used to enable specific features or to modify factory settings. This must be done by an accredited technician. A code and special training is mandatory to access this menu group. The table below is valid for controllers generation TAC.
RANGE
CLASS UNIT
SIZE
Unique
TAC DG
884229
LED AF
ON
Fans
Supply stopped
42 Operation and maintenance instructio ns – CLASS UNIT TAC5
8
.0 Parameters/Commissioning Sheet
Please enter all settings specific to your installation in this table. Please keep this document at hand when there is a need to contact us to report a problem.
8.1 MAIN PARAMETERS AFTER COMMISSIONING
CLASS UNIT mo-
1
del:
2
Operating mode:
O Constant Airflow
O Demand control
3
4
5
6
Constant Airflow:
Constant Torque:
Demand control:
Constant pressure:
7
Ratio exhaust / supply:
K1 =
K2 =
K3 =
K1 =
K2 =
K3 =
Vmin =
Vmax = m³h / %TQ Vmin = m³h / %TQ Vmax =
% on K3 =
Assignment Pa =
% on K3 =
8
If KWin option:
T° KWin =
O Constant Torque
O Constant pressure
O [m³/h] O [l/s]
O [m³/h] O [l/s]
O [m³/h] O [l/s]
% Torque
V
V
% Torque
% Torque
%
%
O [m³/h] O [l/s]
O [m³/h] O [l/s]
%
O [V] O [Pa]
°C
9
KWout
T° KWout = °C
Operation and maintenance instruction s – CLASS UNIT TAC5
43
8.2 TRACK CHANGES
Enter details when the Setting of a parameter has been changed (use only one row per parameter):
Parameter Name
Setting before change
Setting of change #1
Date of change #1
Setting of change #2
Date of change #2
44 Operation and maintenance instructio ns – CLASS UNIT TAC5
EC DECLARATION OF CONFORMITY
Manufacturer (and where appropriate his authorized representative):
Company: Swegon Operations Belgium
Address: Parc-industriel de Sauvenière 102 Chaussée de Tirlemont
B5030 Gembloux
Hereby declares that:
Following product range(s): GLOBAL PX (TOP) / GLOBAL RX (TOP) / GLOBAL LP (OUT)/
CLASS UNIT / MURAL
Complies with the requirements of Machinery Directive 2006/42/EC (LVD included)
Complies also with applicable requirements of the following EC directives:
2014/30/EU EMC
2009/125/EC
2011/65/EU
Ecodesign (Regulation nr 1253/2014 – LOT 6)
RoHS 2 (including amendment 2015/863/EU – RoHS 3)
Authorized to compile the technical file:
Name: Nicolas Pary
Address: Parc-industriel de Sauvenière 102 Chaussée de Tirlemont
B5030 Gembloux
Signature:
Place and date:
Signature: Name:
Position:
Gembloux 2021-05-17
Jean-Yves Renard
R&D Director
Operation and maintenance instruction s – CLASS UNIT TAC5
45
46 Operation and maintenance instructio ns – CLASS UNIT TAC5
Version: 20220414
We reserve the right for changes.