advertisement
1
GEH 5 3 6 9 Installation Instruction s
MicroVersaTrip RMS-9 Programmer
For Circuit Breakers 15D-4000 Amps; 240, 480 and 600 Vac
INTRODUCTION
MicroVersaTrip® RMS-9 programmer is the General
Electric state-of-the-art solid state overcurrent protection programmer for industrial circuit breakers.
The MicroVersaTrip® RMS-9 programmer includes a digital microprocessor for direct rms sensing of sinusoidal or harmonic power distribution currents.
The MicroVersaTrip® RMS-9 programmer is factory installed in the frame. Breaker ampere ratings may be upgraded in the field by changing rating plug on the front of the MicroVersaTrip® RMS-9 programmer.
The current sensors and flux shifters used for the
MicroVersaTrip® RMS-9 programmers are identical to the ones used for the MicroVersaTrip® programmer.
The MicroVersaTrip® RMS-9 programmer is provided with circuit breakers with the following frame designations:
"J" Molded Case Circuit Breakers: T JH,T JL
"K" Molded Case Circuit Breakers: TKH,TKL
Power Break Circuit Breakers: TP_SS,
THP_ss,
Tc_ss,
THC_SS,
AK/AKR Circuit Breakers and conversion kits:
AKR-30, AKR-30S
AKRU-30, AKR-30H,
AKR-50, AKRT-50
AKR-75, AKR-100,
AK-25, AKS-50
AK-75, AK-100
TRIPPING FUNCTIONS
General Description
1. Current Setting-standard
2. Long Time Delay_standard
3. Long Time Pickup Light-standard (Mounted in
Rating Plug)
4. Short Time Pickup--optional (Cat. No. Suffix "S")
5. Short Time Delay-optional (Cat. No. Suffix "S")
6. Instantaneous Pickup--optional in AKR breakers, standard for other breakers, Standard
Instantaneous (Cat. No. Suffix "I"), Adjustable
High Range Instantaneous (Cat. No. Suffix "H")
7. Ground Fault Pickup--optional (Cat. No. Suffix
9. Triple Selective Trip with Fixed High Range
Instantaneous-optional in AKR-30S Breakers
(Cat. No. Suffix "K")
10. Fault Trip Targets-optional Overload and Short
Circuit (Cat. No. Suffix "T1 ") Overload, Short
Circuit and Ground Fault (Cat. No. Suffix "T2")
11. Zone Selective Interlock-optional, Ground Fault
Only (Cat. No. Suffix "21 "), Ground Fault and
Short Time (Cat. No. Suffix "22")
12. Switchable OFF Instantaneous/Ground Fault optional for AK/AKR only. Pickup functions can be deleted by turning switch to OFF position (Cat.
No. Suffix X). Breakers with this programmer option are not UL Listed.
RATING PLUG
The MicroVersaTrip® RMS-9 trip units are designed for use with UL listed field interchangeable rating plugs. These rating plugs serve the function of chang ing the per unit (1 X) rating of a breaker, or in other words, changing the ampere rating. Several rating plugs exist for a particular sensor. The maximum value of a rating plug is equal to the sensor rating(S).
Each rating plug is keyed for a particular sensor. An
Epic or MicroVersaTrip® RMS-9 circuit breaker frame, when shipped from the factory, is configured to accept only the specific rating plugs keyed to that particular sensor.
The long time, timing light and test jack are housed within the rating plug.
2
DETAILED DESCRIPTION
1. CURRENT SETTING
Current Setting "C", is the current value the breaker will carry indefinitely without tripping.
The value of the current is determined by the product of current setUng and the ampere rating on the rating plug, "X".
Settings are .5X, .6X, .7X, .8X, .85X, .9X, .95X
and 1.0X for J/K and Power Break® circuit break ers. For AKR low voltage circuit breakers, set tings are .5X, .6X, 7X, .8X, .9X, .95X, 1.0X and
1.1X.
2. LONG TIME PICKUP AND DELA V
The Long Time pickup is fixed at 110% of the cur rent setting for J/K and Power Break circuit break ers and at 100% of current setting for AKR low voltage circuit breakers.
The Long Time delay trip bands provide the func tion of withstanding temporary overloads such as motor starting, welding or other overcurrent con ditions without interrupting service.
The purpose of the time delay bands is to provide further degrees of coordination and selectivity within a system. The delay bands provide in creasing times to trip at any fixed overload cur rent. The bands are marked as follows:
Continuous Current
Ratings
150-4000 Amps
Band 1
Band 2
Band 3
Band 4
Typical Time Delay at 600% of Device Setting
(nominal time delay)
3 seconds
6 seconds
12 seconds
25 seconds
3. LONG TIME PICKUP LIGHT
Whenever the current reaches 105% of the cur rent setting for J/K and Power Break circuit breakers, and 95% for AKA low voltage power circuit breakers, the Long Time pickup LED will flash to indicate the approach of the full load condition. When the breaker load current is over the pickup threshold, the LED will be on continuously (110% of current setting for J/K and Power Break, and 100% for AKA breakers.)
4. SHORT TIME PICKUP
The primary function of the Short Time pickup is to allow the breaker to carry a high level of current for a short period of time. This feature provides a further degree of selectivity within a system.
The Short Time pickup settings are the follow ing multiplies of current setting:
1.5C, 2C, 2.5C, 3C, 4C, SC, 7C and 9C
5. SHORT TIME DELA V
The adjustable Short Time delay provides fur ther coordination between "upstream" and
"downstream" breakers which have the same short time pickup setting.
The l 2 t IN/OUT section provides further selectivity by placing the 1 2 t section of the short time region in or out. When the switch selection is OUT, the constant time delay bands dictate the short time trip characteristics. When the switch is in the IN position, depending on the magnitude of the fault current, the trip time will be on the 1 2 t section of the curve or the constant time delay section if the fault magnitude is high enough.
These six selections are available for the short time delay function (delay shown at
600% of current settings with pickup set at
SC or lower
1. 1 2 t IN minimum delay, .5 seconds on l 2 t slope
2. l 2 t IN intermediate delay, .5 seconds on l 2 t slope
3. 1 2 t IN maximum delay, .5 seconds on
1 2 t slope
4. 1 2 t OUT maximum delay, .42 seconds
5. 1 2 t OUT intermediate delay, .26 seconds
6. l 2 t OUT minimum delay, .13 seconds
9. INSTANTANEOUS PICKUP
The instantaneous setting provides immediate
(no intentional time delay) interruption of severe overloads, thereby minimizing damage to system equipment. There are three variations possible: a.
NO INSTANTANEOUS
This is available in AKR breakers only.
b. ADJUSTABLE INSTANTANEOUS
The following variations are possible for the different MicroVersaTrip® RMS-9 units. There are several combinations possible depending on the rating of the breaker and whether short time has been selected or not. The combina tions are:
• 1.SX, 2X, 3X, SX, 7X, 9X, 1 OX, 13X, 1 SX
• 1.5X, 2X, 3X, SX, 7X, 9X, 1 OX, 13X
• 1.5X, 2X, 3X, SX, 7X, 9X, 1 OX
• 1.5X, 2X, 3X, 5X, 7X, 9X
• 1.5X, 2X, 3X, 5X, 7X, 9X, 1 OX, 13X, 15X,
OFF (AKR Only)
• 1.5X, 2X, 3X, 5X, 7X, 9X, 1 OX, OFF (AKR
Only)
• 1.SX, 2X, 3X, 5X, 7X, 9X, OFF (AKR Only) c. HIGH RANGE INSTANTANEOUS
High range instantaneous provides protection and coordination at levels up to the full short time rating of the circuit breaker. High range instantaneous is adjustable from 40% to 100% of the short time rating in four steps of 20% each. Available on Power Break® and AKR breakers only.
3
10. GROUND FAULT PICKUP
Settings are adjustable with no setting exceeding
1200 Amps to comply with National Electrical
Code, Section 230-95.
These settings are the following multiples of Sen sor Ampere Rating (S):
• 150-2000 Amps-.2S, .25S, .3S, .35S, .4S,
.45S, .5S, .6S
• 2500A & 3000 Amps-.2S, .22S, .24S,
.26S, .28, .30S, .34S, .37S
• 4000 Amps-.2S, .22S, .24S, .26S, .28S,
.3S
11. GROUND FAULT DELAY
The adjustable ground fault delay provides further coordination between "upstream" and "down stream" breakers which have the same ground fault pickup setting.
The 1 2 t IN/OUT section provides further selectivi ty by placing the 1 2 t section of the ground fault region in or out. When the switch selection is
OUT, the constant ground fault delay bands dic tate the ground fault trip characteristics. When the switch is in the IN position, depending on the magnitude of the ground fault current, the ground fault trip will be on the 1 2 t section of the curve or the constant ground fault delay section if the fault magnitude is high enough.
These six selections are availale for the ground fault delay function. (nominal delay shown at
200% of pickup setting):
1. 1 2 t IN minimum delay, .5 seconds on 1 2 t slope
2. 1 2 t IN intermediate delay, .5 seconds on
1 2 t slope
3. 1 2 t IN maximum delay, .5 seconds on l 2 t slope
4. 1 2 t OUT maximum delay, .42 seconds
5. 1 2 t OUT intermediate delay, .26 seconds
6. 1 2 t OUT minimum delay, .13 seconds
12. FAULY TRIP TARGETS
The mechanical pop-out fault targets identify the type of overcurrent fault (overload, short circuit or ground fault) responsible for tripping the breaker.
The target has to be reset manually by pressing it back into the programmer.
13. ZONE SELECTIVE INTERLOCK
The Zone Selective Interlock system allows the breaker sensing the fault to trip immediately.
Zone Selective Interlock is available in two ver sions: a) Ground Fault Only "21" or b) Short
Time and Ground Fault "22". One or more Zone
Selective Interlock Modules, Cat. No.
TIM1(120Vac input) or TIM2(125Vdc input) must be used with the Zone Interlock option. Refer to
Instructions GEK-64467A for connection details.
Whenever the downstream breaker goes into
Ground Fault Pickup for "21" (and/or Short Time
Pickup for "22") and the fault current magnitude is in the region where the constant time delay bands are in effect, a signal is sent to the up stream breaker, through the zone interlock module.
When the Zone Selective Interlock signal is re ceived, the upstream breaker's delay band is changed from minimum to the one selected by the switch setting for 21 . For a breaker with the
22 option, both ground fault and short time bands are changed from the minimum to the switch setting.
Note that a programmer with the zone interlock option will time out on the minimum delay band for Ground Fault for 21 (and Short Time for 22) in the absence of a signal from a downstream inter lock module. The switch settings are relevant only when a Zone Input signal is received.
MOUNTING NEUTRAL CURRENT SENSORS
(required on a 4-wire system if the programmer has the ground fault protection system
If the load circuit does not include a neutral (for example: 3-phase, 3-wire), the neutral sensor ter minals on the circuit breaker should be left open and neutral sensor not used. (Do not "short" terminals)
When a neutral is included in the load circuit, neutral sensor line and load markings must be re spected when making bus or cable connections.
The polarity of connecting wires from secondary of neutral sensor to circuit breaker must also be respected: white to white, black to black.
The neutral sensor can only be used with a breaker whose sensor rating(S) matches the neutral sensor ampere rating or tap setting.
WIRING
Connect wiring from sensor to breaker black to black and white to white using twisted pair #14 AWG mini mum, Belden 8640,61 or 8470,71 or equal.
TESTING MICROVERSATRIP® RMS-9
PROGRAMMER
Cat. No. TVRMS is a portable, hand-held, battery powered, test kit providing RMS-9 programmer self tests and functional trip/no trip tests. Interface is via a plug on the front of the programmer and tests can be conducted with breaker in service. Kit uses six rechargeable NICAD or standard alkaline "D" cells supplied by customer. Kit can also be powered by 120-volts ac source. Testing of a MicroVersa
Trip® RMS-9 equipped circuit breaker may also be accomplished using primary current from a high cur rent, low voltage test set.
4 When high current testing a breaker with ground fault option, one of several methods must be employed to insure that a ground fault trip does not preempt a long-time or short-time trip:
A. Single-pole testing
(1) Plug TVRMS test kit into programmer and follow menu driven instructions for high current testing (this will temporarily defeat the ground fault function). Or,
(2) For breakers rated 2000A maximum - use a value of test current less than 90 per cent of the ground fault pickup setting, but greater than 110 percent of the long time or short-time pickup. (In most cases this will require a low current set ting or short-time pickup, and a high ground fault pickup setting.)
B. Test with two-poles in series
Connect high current source (leads L 1 and
L2) to line side of breaker and jumper load terminals as shown in Figure 1.
C. Note that test kit Cat. No. TVRMS can always be used when using primary injection (high current test set) to temporarily defeat the ground fault function.
CAUTION:
When high current testing a breaker with ground fault option, ground fault defeat cable Cat. No. TVTGD9 must NOT be used. Only MicroVersa Trip® RMS-9 test kit Cat. No. TVRMS may be used to temporarily defeat the ground fault function. Programmer damage may result if these cautions are not followed.
GROUND FAULT PROTECTION
SCHEMES
MicroVersaTrip® RMS-9 programmers used on AKR
Low Voltage Power Circuit Breakers, Power Break
Insulated Case Circuit Breakers, and Molded Case
Circuit Breakers are self-powered. The integral ground fault function (suffix "G") provided vectorially sums the phase currents and neutral current, if pres ent, as shown in Figure 1. In the absence of ground fault currents the vector sum of the phase and neutral currents, I
G sum, I
G
, is zero. With a ground fault, the vector corresponds to the ground fault current.
MUL Tl-SOURCE SYSTEMS
Multi-souce systems with grounded neutral inter-ties such as secondary selective and spot networks re quire special ground fault circuitry.
In the circuit shown in Figure 2, the neutral sensor secondary windings, in addition to being connected to their respective breaker, are interconnected with each other in a loop circuit. With this arrangement, the circuit is not responsive to normal neutral loading, but is responsive to ground fault current regardless of its return path to the source supplying ground fault current. Each breaker should have an auxiliary "A" contact connected as shown. The aux iliary contact "A" condition is similar to the breaker.
When the breaker is open, "A" is open. When the breaker is closed, "A" is closed.
One breaker must always be open so its neutral sensors will be disconnected from its associated breaker to provide the driving force to assure that the current flows around the sensor loop circuit.
G, N A B C
Figure 1
Figure 2
TRIP
FUNCTION
Figure 3
These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation operation or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser's purposes, the matter should be referred to ABB Company.
—
ABB Inc.
305 Gregson Drive
Cary, NC 27511. electrification.us.abb.com
—
GE is a trademark of GE. Manufactured by ABB Inc. under license from GE.
—
We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB Inc. does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.
We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB Inc.
Copyright© 2019 ABB
All rights reserved
advertisement
Related manuals
advertisement