Power+™ Trip Unit Rating Plugs
Power Breake I} Circuit Breakers
Function
Power+™ Trip Units are designed with UL-listed
interchangeable Rating Plugs. These Rating Plugs
change the per-unit (1X) continuous-current rating of
the breaker. A circuit breaker equipped with a suitable
Trip Unit and Rating Plug has a long-time trip
current equal to the ampere rating marked on the
Rating Plug times the LT setting on the Trip Unit.
For example, a breaker frame with a 1600 A sensor,
an 800 A Rating Plug, and a long-time pickup switch
setting of 1.0 has an 800 A continuous-current (long-
time) rating.
Several Rating Plugs are available for each sensor
rating and each Rating Plug is keyed for a particular
sensor rating.
The catalog number structure for the available Rating
Plugs for Power Break II insulated-case circuit breakers
is listed in Table 1. See DEH-049, Power+™ Trip Units
User’s Guide, for a complete listing of all Rating Plug
catalog numbers.
UL Label
The UL label is mounted on the side of the Rating
Plug and is not visible when the Rating Plug is
installed. The label lists the circuit breaker frames that
will accept that Rating Plug.
TR 20€
Code | Description | Function
2 200 A
4 400 A
8 800 A
10 1000 A
16 1600 А Sensor
20 2000 A
2 2500 A
SD 3000 А
40 4000 A
poc] PB || [__Breaker M-—
<none> | No Ground Fault
GF Ground Fault
Ground Fault
Front Label
The front label, shown in Figure 1, is visible when the
Rating Plug is installed. The items listed are:
Sensor Rating (S) The ampere rating of the
corresponding breaker frame.
The Rating Plug continuous
current in amperes.
The test-jack receptacle is used
with the Test Kit, catalog
number TVRMS2, for
overcurrent and ground-fault
functional testing.
Follows the format TRppCqqqq,
as shown in Table 1.
Rating Plug Amps (X)
Test
Catalog Number
Cat TRIOCIONBF
4000 À
Х = 1006 д |
$ = 1000 А лоте ЗВ
24 BG
Ground Fit Pinus Gesund Faut Delay
Figure 1. Rating Plug with ground-fault function.
dl
000 GF
В Code | Description | Function
100 100 À
150 150 À
200 200 À
225 225 À
250 250 A
300 300 A
400 400 À
500 500 A
600 600 À
700 700 À
800 800 À Rating
1000 1000 A
1100 1100 А
1200 1200 A
1600 1600 А
2000 2000 A |
2500 2500 A
3000 3000 A
3200 3200 A
3600 3600 A |
40C0 4900 A
Table 7. Rating Plug catalog number structure