CommScope ADCP-90-326 User Manual
CommScope ADCP-90-326 is a Fiber Management Tray-D (FMT-D) that provides a rack-mount and front-access solution for organizing and managing fiber optic cables. It offers various configurations, including termination and storage, bulk slack storage, and termination and splice, making it suitable for a wide range of applications. The FMT-D features adjustable recess configurations, allowing for customized installation to meet specific requirements. It includes sliding adapter packs for easy access to connectors, tie lances for securing fibers, and edge protectors to prevent cable damage.
Publicitate
Publicitate
ADCP-90-326 • Rev B • November 2020 www.commscope.com
Fiber Management Tray-D (FMT-D
)
User
Manual
20250-A
Fiber Management Tray
Content Page
Related Publications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
(continued)
ADCP-90-326 Rev B Page 1
© 2020, CommScope Inc.
ADCP-90-326 • Rev B • November 2020
Content Page
6.4Termination and Storage FMT Configuration15
6.4.1
12-Position Termination and Storage Tray, Universal Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
INTRODUCTION
This manual describes the CommScope Fiber Management Tray-D (FMT-D) and provides all information required to install and use this product.
The FMT is a fiber optic tray that provides a variety of rack-mount and functional options. All options are covered in this manual to the extent of relevance when the FMT is installed and used.
Revision History
ISSUE DATE
Issue 1 11/2001
Issue 2 04/2003
Issue 3 06/2004
REASON FOR CHANGE
Original.
Revised to reflect changes in product design.
Add attenuator information.
Issue 4 06/2005 New spring lock and mounting brackets. Update cable routing.
Rev B November 2020 Changed to CommScope format.
Trademark Information
CommScope (logo) and CommScope are trademarks of CommScope, Inc.
Page 2
© 2020, CommScope Inc.
ADCP-90-326 • Rev B • November 2020
ADMONISHMENTS
Important safety admonishments are used in this manual to warn of possible hazards to persons or equipment. The admonishments — in the form of Dangers, Warnings, and Cautions — must be followed at all times. These warnings are flagged by use of a triangular alert icon (shown below), and are listed in descending order of severity of injury or damage and likelihood of occurrence.
.
Danger: Danger is used to indicate the presence of a hazard that will cause severe personal injury, death, or substantial property damage if the hazard is not avoided.
Warning: Warning is used to indicate the presence of a hazard that can cause severe personal injury, death, or substantial property damage if the hazard is not avoided.
Caution: Caution is used to indicate the presence of a hazard that will or can cause minor personal injury or property damage if the hazard is not avoided.
GENERAL SAFETY PRECAUTIONS
Danger: Infrared radiation is invisible and can seriously damage the retina of the eye. Do not look into the ends of any optical fiber. Do not look directly into the optical adapters of the adapter packs. Exposure to invisible laser radiation may result. An optical power meter should be used to verify active fibers. A protective cap or hood MUST be immediately placed over any radiating adapter or optical fiber connector to avoid the potential of dangerous amounts of radiation exposure. This practice also prevents dirt particles from entering the adapter or connector .
1 PRODUCT DESCRIPTION
The CommScope Fiber Management Tray (FMT) is a rack-mount, front-access fiber optic tray available in a variety configurations. Some of these are noted below:
• 12- or 16-position termination and storage (universal storage);
• 24-position termination and storage (left or right storage);
• 12-position termination and splice (left or right splice entry);
• 32-, 48-, or 60-cable bulk slack storage (capacity dependent on cable diameter).
Rack-mount and recess options include:
• EIA or WECO, reversible 19- or 23-inch (48.26 or 58.42 cm) mounting brackets installed for 5-inch recess;
• ETSI, 20.28-inch (51.5 cm) with 40 mm recess.
Customer adjustable recess configurations include:
• EIA 19-inch (48.26 cm) with 40 mm recess;
• EIA or WECO, 19 or 23-inch (48.26 or 58.42 cm) FMT offer 2.2-inch (5.59 cm), 3.1-inch
(7.9 cm), 5-inch (12.7 cm), or 6.5-inch (16.5 cm) recess;
Page 3
© 2020, CommScope Inc.
ADCP-90-326 • Rev B • November 2020
shows one of the FMT configurations, the 12-position termination and storage tray.
Some of the features common to all FMT configurations are displayed.
LOCK OPEN
LATCH
LEFT REAR
RADIUS LIMITERS
SLIDING
ADAPTER
PACKS
RIGHT REAR
RADIUS LIMITERS
TIE LANCES
(EACH SIDE)
20198-A
RELEASE
TAB
MOUNTING
BRACKET
(2 PLACES)
STORAGE
RADIUS
LIMITERS
SLIDING RADIUS
LIMITER (2 PLACES)
EDGE
PROTECTORS
(4 EACH SIDE)
RELEASE
TAB
Figure 1. FMT Features (12-Position Termination and Storage Tray, Universal Entry, Shown)
The features shown include the following (from bottom left clockwise):
• Edge Protectors —Protect cables from sharp angles at bend points.
• Release Tabs —Allows the FMT tray to open.
• Lock Open Latch —Allows the technician to lock open the FMT while working in the tray.
• Rear Radius Limiters (Left and Right) —Maintain a protective, minimum-bend radius for cables routed into panel.
• Tie Lances —Provide anchor points for securing fibers.
• Storage Radius Limiters —Provide service loop storage for cable terminated in panel.
• Mounting Brackets —Adapt the tray for the different mounting options. Brackets may by mounted in several recess locations based on customer needs.
• Sliding Radius Limiter —Provides protective entry point for cables. Radius limiter slides backward when tray is pulled out and forward when tray is closed.
Page 4
© 2020, CommScope Inc.
ADCP-90-326 • Rev B • November 2020
• Sliding Adapters Packs —Each with two adapters, provide easy access for connecting cables and cleaning connectors. Product offerings for adapters/connectors include most industry-standard multimode and singlemode types.
shows a closed tray with the sliding radius limiter in a closed position. Also shown is the optional lock.
202 8 2-A
LOCK
(OPTIONAL)
MOUNTING BRACKET
(ONE EACH S IDE)
S LIDING RADIU S
LIMITER
(ONE EACH S IDE)
Figure 2. FMT Features (Closed Tray Shown)
2 SPECIFICATIONS
Table 1 lists specifications for the Fiber Management Tray.
Figure 3 shows the FMT dimensions
for rack type, rack width, and recess options.
Table 1. Fiber Management Tray Specifications
ITEM
Dimensions (H × W × D)
Approximate Weight
Configuration Options and Capacity
DESCRIPTION
See
on
.
7.9 lbs. (3.98 Kg)
Termination/storage (12, 16, or 24 terminations)
Bulk storage
3 mm O.D. cable: 32 cables, length 1.7 m (66 in.) each
2 mm O.D. cable: 48 cables, length 3.4 m each (132 in.)
1.7 mm O.D. cable: 60 cables, length 3.9 m (154 in.) each
Termination and splice (12 splices)
Page 5
© 2020, CommScope Inc.
ADCP-90-326 • Rev B • November 2020
19-INCH FMT
17.21 IN.
(43.7 CM)
11.05 IN.
(28.05 CM)
RECESS OPTIONS
40 mm 1.535 IN.
3.9 CM
2.2-INCH 3.07 IN.
7.8 CM
5-INCH
6.5-INCH
5.0 IN.
6.5 IN.
12.7 CM
16.5 CM
TOP VIEW
1.71 IN.
(4.34 CM)
FRONT VIEW
RACK TYPE OPTIONS
ETSI
WECO
EIA
0.98 IN.
1.0 IN.
1.25 IN
2.5 CM
2.5 CM
3.25 CM
Figure 3. FMT Dimensions
RACK WIDTH OPTIONS
ETSI
19-INCH EIA/WECO
23-INCH EIA/WECO
20.28 IN.
18.31 IN.
22.32 IN
51.5 CM
46.5 CM
56.7 CM
20199-A
3 UNPACKING THE PRODUCT
Unpack and inspect the Fiber Management Tray as follows:
1. Inspect the exterior of the shipping container for evidence of rough handling that may have damaged the contents of the container.
2. Unpack the FMT and check for possible damage.
Page 6
© 2020, CommScope Inc.
ADCP-90-326 • Rev B • November 2020
3. If damage is detected or if parts are missing, file a claim with the commercial carrier and then notify CommScope Customer Service. Save damaged carton for inspection by the carrier.
4. Refer to
Section 8 Customer Information and Assistance
for repair, replacement, and warranty information.
5. Save the shipping container for use if equipment requires shipment at a future date.
4 MOUNTING THE FMT ON THE RACK
For all mounting options, the FMT uses two mounting brackets, one on either side, with two
mounting holes in each bracket (see Figure 4
). Determine what recess is required and adjust mounting brackets for the required recess. Secure tray to rack using the screws (provided).
Note: In some configurations, the same screw is used for both the mounting bracket (top
hole) and the vertical cable guide (see Section 5 Installing Vertical Cable Guides ).
20200-A
MOUNTING
HOLES
Figure 4. FMT Mounting Holes
5 INSTALLING VERTICAL CABLE GUIDES
Optional vertical cable guides (VCGs) may be installed with FMTs when space permits. Table 2
summarizes possible uses of VCGs for various combinations of rack width and recess.
Table 2. Possible Uses of VGCs
RACK WIDTH
19 inches
(48.26 cm)
VERTICAL CABLE
GUIDE
VCGs not advised
23 inches
(58.42 cm)
RECESS
40 mm (1.54 inch)
2.2-inch (5.59 cm)
3.1-inch (7.9 cm)
5-inch (12.7 cm)
6.5-inch (16.5 cm)
40 mm (1.54 inch)
2.2-inch (5.59 cm)
3.1-inch (7.9 cm)
5-inch (12.7 cm)
6.5-inch (16.5 cm)
1. If the rack width is 19 inches (48.26 cm) or ETSI (20.28 inches, 51.5 cm) and:
Page 7
© 2020, CommScope Inc.
ADCP-90-326 • Rev B • November 2020 a. Recess is 40 mm (1.54 inch) or 2.2-inch (5.59 cm), use of VCGs is not advised. b. Recess is 3.1-inch (7.9 cm), 5-inch (12.7 cm), or 6.5-inch (16.5 cm), mount the VCGs on the rack narrow flange using the same screw and hole position as used for the top
mounting screw on the panel mounting bracket. Refer to Figure 5 .
20201-A
VERTICAL
CABLE GUIDE
MOUNTING
BRACKET
Figure 5. Installing VCGs (19-Inch Rack Mount)
2. If the rack width is 23 inches (58.42 cm), mount the VCGs on the rack narrow flange using the same screw and hole position as used for the top mounting screw on the panel mounting bracket. Refer to
.
Page 8
© 2020, CommScope Inc.
ADCP-90-326 • Rev B • November 2020
20202-A
VERTICAL
CABLE GUIDE
MOUNTING
BRACKET
Figure 6. Installing VCGs (23-Inch Rack Mount)
6 INSTALLING AND ROUTING CABLES
Danger: Infrared radiation is invisible and can seriously damage the retina of the eye. Do not look into the ends of any optical fiber. Do not look directly into the optical adapters of the adapter packs. Exposure to invisible laser radiation may result. An optical power meter should be used to verify active fibers. A protective cap or hood MUST be immediately placed over any radiating adapter or optical fiber connector to avoid the potential of dangerous amounts of radiation exposure. This practice also prevents dirt particles from entering the adapter or connector .
Caution: Placing a load in excess of 5 pounds (2.3 kg) onto an open tray will result in misalignment or damage to the tray.
6.1
Routing and Securing Cables
The FMT may be configured to provide termination and storage, storage only, or termination and splice functions. For each configuration, the fiber optic cables or patch cords are routed to the FMT, installed within the sliding tray, and secured.
All cables enter the FMT through one of the two sliding entry points, located on the left and right sides of the FMT. When properly installed, the slack loop that forms when the FMT is closed is taken up within the FMT by movement of the sliding radius limiter.
Page 9
© 2020, CommScope Inc.
ADCP-90-326 • Rev B • November 2020
and Figure 8 show typical cable routing. Prior to routing cables, review the installation
procedure corresponding to the configuration (provided in Subsection 6.3
Then use the following guidelines for routing and installing the cables or patch cords:
1. Open the tray fully, the lock open latch will lock the tray in the open position (see
).
2. Route the cables to the FMT. The cables may be routed from either overhead or under the floor and to the left or right side of the FMT depending on configuration requirements.
3. Secure the cable on the rack using a cable clamp such as shown in Figure 7 and
.
Note: Install the cable clamp kit following the instructions provided in the installation drawing shipped with the kit. Ribbon blocking kits are available from CommScope in a variety of sizes to match any ribbon cable type.
4. Route the cables into the FMT through the specified sliding radius limiter(s).
5. Route and connect the cables within the FMT as required by the configuration. Refer to the installation procedure that corresponds to the FMT configuration.
6. Adjust the cables within the FMT until all excess slack is removed or stored.
7. Secure the cables to the back of the FMT at the rear tie-off point (see Figure 7
Note that a tie-off point is provided on both the left and right side.
8. Use the kurly locks provided to bundle fibers together between the sliding radius limiter and the rear radius limiter as needed.
9. Adjust the cable position with the cable clamp as required to remove excess slack.
10. Release the lock open latch and close the tray (see Subsection 7.4
).
Page 10
© 2020, CommScope Inc.
CABLE CLAMP
AND MOUNTING
BRACKET
ADCP-90-326 • Rev B • November 2020
TIE
LANCE
DETAIL OF
CABLE TIE-OFF
POINT
CABLE CLAMP
AND MOUNTING
BRACKET
PLACE OPTIONAL
ATTENUATOR ON THIS
SIDE OF SLIDING
ADAPTER PACK
ROUTE CABLE
INTO FMT
THROUGH SLIDING
RADIUS LIMITER
20203-A
Figure 7. Routing and Securing Cable - Typical Configuration for IFC Stranded Cable
Page 11
© 2020, CommScope Inc.
ADCP-90-326 • Rev B • November 2020
CABLE CLAMP
AND MOUNTING
BRACKET
RIBBON
BLOCKING
KIT
RIBBON
CABLE
DETAIL OF
CABLE TIE-OFF
POINT
TIE
LANCE
CABLE CLAMP
AND MOUNTING
BRACKET
RIBBON
BLOCKING
KIT
PLACE OPTIONAL
ATTENUATOR ON THI S
S IDE OF S LIDING
ADAPTER PACK
ROUTE PROTECTIVE
TUBING INTO FMT
THROUGH S LIDING
RADIU S LIMITER
20277-A
Figure 8. Routing and Securing Cable - Typical Configuration for Ribbon Cable
6.2
Attenuators
Attenuators decrease the optical power in a fiber by a specific or adjustable amount. Once the desired level of attenuation is determined, fixed attenuators may be inserted in the fiber optic line to deliver a precise output. Optional attenuators are installed on tab side of the sliding
Page 12
© 2020, CommScope Inc.
1 1
ADCP-90-326 • Rev B • November 2020
6.3
Termination Only FMT Configuration
Cables routed into the FMT for termination only will typically be pre-terminated individual cables of 2 mm or 3 mm diameter. Refer to the following instructions.
6.3.1
24-Position Termination Only Tray, Universal Entry
Route and install the cables as shown in Figure 9 . Place kurly locks at locations indicated.
ROUTE FIBER S ALONG THE
S OLID ARROW ON INDICATED
PATH, THEN FOLLOW THE
APPROPRIATE DOTTED LINE.
KURLY
LOCK
KURLY
LOCK
2 2
2
2
3
2
2
3
20 3 40-A
1 FROM BOTH S IDE S ROUTE THE FIR S T 10 FIBER S DIRECTLY INTO THE
BACK 10 ADAPTER S .
2 FROM BOTH S IDE S ROUTE THE NEXT 12 FIBER S AROUND THE EDGE
PROTECTOR S (2 FIBER S PER EDGE PROTECTOR) AND INTO THE NEXT
12 ADAPTER S .
3 FROM BOTH S IDE S ROUTE THE LA S T 2 FIBER S AROUND THE FRONT EDGE
PROTECTOR S (2 FIBER S PER EDGE PROTECTOR) AND INTO THE FRONT
2 ADAPTER S .
Figure 9. Cable Routing for 24-Position Termination Only Tray, Universal Entry
Page 13
© 2020, CommScope Inc.
ADCP-90-326 • Rev B • November 2020
KURLY
LOCK
6.3.2
32-Position Termination Only Tray, Universal Entry
Route and install the cables as shown in Figure 10 . Place kurly locks at locations indicated.
ROUTE FIBER S ALONG THE
S OLID ARROW ON INDICATED
PATH, THEN FOLLOW THE
APPROPRIATE DOTTED LINE.
7 3
KURLY
LOCK
6 2
8
8
8
8
4
4
4
4
1 5
1 ROUTE THE FIR S T 2 FIBER S THROUGH THE S LIDING RADIU S LIMITER, AROUND THE RIGHT REAR
RADIU S LIMITER, AND AROUND THE FRONT RIGHT CORNER OF THE ADAPTER S (EDGE PROTECTOR).
CONTINUE ROUTING FIBER S ACRO SS THE FRONT OF THE TRAY AROUND THE EDGE PROTECTOR S
TO THE 2 ADAPTER S ON THE LEFT S IDE.
2 ROUTE THE NEXT 2 FIBER S THROUGH THE S LIDING RADIU S LIMITER, AROUND THE RIGHT REAR
RADIU S LIMITER TO THE 2 ADAPTER S ON THE RIGHT S IDE.
3 ROUTE THE NEXT 8 FIBER S THROUGH THE S LIDING RADIU S LIMITER, AROUND THE RIGHT REAR
RADIU S LIMITER TO THE TOP 8 ADAPTER S ON THE RIGHT S IDE.
4 ROUTE THE NEXT 16 FIBER S THROUGH THE S LIDING RADIU S LIMITER, AROUND THE RIGHT REAR
RADIU S LIMITER TO THE EDGE PROTECTOR S . ROUTE 4 FIBER S AROUND EACH EDGE PROTECTOR
TO 4 ADAPTER S ON THE RIGHT S IDE.
5 ROUTE THE FIR S T 2 FIBER S THROUGH THE S LIDING RADIU S LIMITER, AROUND THE LEFT REAR
RADIU S LIMITER, AND AROUND THE FRONT LEFT CORNER OF THE ADAPTER S (EDGE PROTECTOR).
CONTINUE ROUTING FIBER S ACRO SS THE FRONT OF THE TRAY AROUND THE EDGE PROTECTOR S
TO THE 2 ADAPTER S ON THE RIGHT S IDE.
6 ROUTE THE NEXT 2 FIBER S THROUGH THE S LIDING RADIU S LIMITER, AROUND THE LEFT REAR
RADIU S LIMITER TO THE 2 ADAPTER S ON THE LEFT S IDE.
7 ROUTE THE NEXT 8 FIBER S THROUGH THE S LIDING RADIU S LIMITER, AROUND THE LEFT REAR
RADIU S LIMITER TO THE TOP 8 ADAPTER S ON THE LEFT S IDE.
8 ROUTE THE NEXT 16 FIBER S THROUGH THE S LIDING RADIU S LIMITER, AROUND THE LEFT REAR
RADIU S LIMITER TO THE EDGE PROTECTOR S . ROUTE 4 FIBER S AROUND EACH EDGE PROTECTOR
TO 4 ADAPTER S ON THE LEFT S IDE.
20 3 41-A
Figure 10. Cable Routing for 32-Position Termination Only Tray, Universal
Page 14
© 2020, CommScope Inc.
ADCP-90-326 • Rev B • November 2020
6.4
Termination and Storage FMT Configuration
Cables routed into the FMT for termination and storage will typically be pre-terminated individual cables of 2 mm or 3 mm outside diameter. For instructions on routing the cables within the tray, select from the subsections below based on the tray configuration being installed.
6.4.1
12-Position Termination and Storage Tray, Universal Storage
Route and install the cables as shown in Figure 11
. Place kurly locks at locations indicated.
ROUTE FIBER S ALONG THE
S OLID ARROW ON INDICATED
PATH, THEN FOLLOW THE
APPROPRIATE DOTTED LINE.
KURLY
LOCK
KURLY
LOCK
3
2
1
3
2
1
S TORAGE
S POOL
S TORAGE
S POOL
202 83 -A
1 ROUTE THE FIR S T 4 FIBER S THROUGH THE RIGHT S LIDING RADIU S LIMITER, AROUND THE
RIGHT REAR RADIU S LIMITER, AND AROUND THE 2 FAR RIGHT RADIU S LIMITER S . WRAP
FIBER S COUNTER CLOCKWI S E AROUND THE RIGHT FRONT S TORAGE S POOL S AND ROUTE
TO THE FRONT 4 ADAPTER S ON THE RIGHT S IDE. WIND S LACK CABLE AROUND S TORAGE
S POOL S IN THE DIRECTION S HOWN.
2 ROUTE THE NEXT 4 FIBER S THROUGH THE RIGHT S LIDING RADIU S LIMITER, AROUND THE
RIGHT REAR RADIU S LIMITER, AND AROUND THE 2 FAR RIGHT RADIU S LIMITER S . WRAP
FIBER S COUNTER CLOCKWI S E AROUND THE RIGHT FRONT S TORAGE S POOL S AND ROUTE
AROUND THE S INGLE RADIU S LIMITER TO THE NEXT 4 ADAPTER S ON THE RIGHT S IDE. WIND
S LACK CABLE AROUND S TORAGE S POOL S IN THE DIRECTION S HOWN.
3 ROUTE THE LA S T 4 FIBER S THROUGH THE RIGHT S LIDING RADIU S LIMITER, AROUND THE
RIGHT REAR RADIU S LIMITER, AND AROUND THE 2 FAR RIGHT RADIU S LIMITER S . WRAP
FIBER S COUNTER CLOCKWI S E AROUND THE RIGHT FRONT S TORAGE S POOL S AND ROUTE
AROUND THE S INGLE RADIU S LIMITER TO THE LA S T 4 ADAPTER S ON THE RIGHT S IDE. WIND
S LACK CABLE AROUND S TORAGE S POOL S IN THE DIRECTION S HOWN.
4 REPEAT THE PROCE SS FOR THE LEFT S IDE, WRAPING THE FIBER S CLOCKWI S E AROUND
THE S TORAGE S POOL S .
Figure 11. Cable Routing for 12-Position Termination and Storage Tray, Universal Storage
Page 15
© 2020, CommScope Inc.
ADCP-90-326 • Rev B • November 2020
6.4.2
16-Position Termination and Storage Tray, Universal Storage
Route and install the cables as shown in Figure 12 . Place kurly locks at locations indicated.
ROUTE FIBER S ALONG THE
S OLID ARROW ON INDICATED
PATH, THEN FOLLOW THE
APPROPRIATE DOTTED LINE.
KURLY
LOCK
KURLY
LOCK
2
1
4
3
2
1
4
3
S TORAGE
S POOL
S TORAGE
S POOL
20 3 42-A
1 ROUTE THE FIR S T 4 FIBER S THROUGH THE RIGHT S LIDING RADIU S LIMITER, AROUND THE
RIGHT REAR RADIU S LIMITER, AND AROUND THE 2 FAR RIGHT RADIU S LIMITER S . WRAP
FIBER S COUNTER CLOCKWI S E AROUND THE RIGHT FRONT S TORAGE S POOL S AND ROUTE
TO THE FRONT 4 ADAPTER S ON THE RIGHT S IDE. WIND S LACK CABLE AROUND S TORAGE
S POOL S IN THE DIRECTION S HOWN.
2 ROUTE THE NEXT 4 FIBER S THROUGH THE RIGHT S LIDING RADIU S LIMITER, AROUND THE
RIGHT REAR RADIU S LIMITER, AND AROUND THE 2 FAR RIGHT RADIU S LIMITER S . WRAP
FIBER S COUNTER CLOCKWI S E AROUND THE RIGHT FRONT S TORAGE S POOL S AND ROUTE
AROUND THE S INGLE RADIU S LIMITER TO THE NEXT 4 ADAPTER S ON THE RIGHT S IDE. WIND
S LACK CABLE AROUND S TORAGE S POOL S IN THE DIRECTION S HOWN.
3 ROUTE THE NEXT 4 FIBER S THROUGH THE RIGHT S LIDING RADIU S LIMITER, AROUND THE
RIGHT REAR RADIU S LIMITER, AND AROUND THE 2 FAR RIGHT RADIU S LIMITER S . WRAP
FIBER S COUNTER CLOCKWI S E AROUND THE RIGHT FRONT S TORAGE S POOL S AND ROUTE
AROUND THE S INGLE RADIU S LIMITER TO THE NEXT 4 ADAPTER S ON THE RIGHT S IDE. WIND
S LACK CABLE AROUND S TORAGE S POOL S IN THE DIRECTION S HOWN.
4 ROUTE THE LA S T 4 FIBER S THROUGH THE RIGHT S LIDING RADIU S LIMITER, AROUND THE
RIGHT REAR RADIU S LIMITER, AND AROUND THE 2 FAR RIGHT RADIU S LIMITER S . WRAP
FIBER S COUNTER CLOCKWI S E AROUND THE RIGHT FRONT S TORAGE S POOL S AND ROUTE
AROUND THE S INGLE RADIU S LIMITER TO THE LA S T 4 ADAPTER S ON THE RIGHT S IDE. WIND
S LACK CABLE AROUND S TORAGE S POOL S IN THE DIRECTION S HOWN.
5 REPEAT THE PROCE SS FOR THE LEFT S IDE, WRAPING THE FIBER S CLOCKWI S E AROUND
THE S TORAGE S POOL S .
Figure 12. Cable Routing for 16-Position Termination and Storage Tray, Universal Storage
Page 16
© 2020, CommScope Inc.
ADCP-90-326 • Rev B • November 2020
6.4.3
24-Position Termination and Storage Tray, Left/Right Storage
Route and install the cables as shown in
. The figure shows a left-storage configuration with sliding adapter packs. For a right-entry storage, the routing is a mirror image of what is shown. Routing is the same for trays with bulkhead plate adapters (route left storage as shown below; route right storage as mirror image). Place kurly locks at locations indicated.
S ECURE FIBER TO
HOLE IN FAN OUT
WITH WAXED LACING
ROUTE FIBER S ALONG THE
S OLID ARROW ON INDICATED
PATH, THEN FOLLOW THE
APPROPRIATE DOTTED LINE.
3
KURLY
LOCK
4
2
1
5
KURLY
LOCK S
S TORAGE
S POOL
6
20 3 74-A
LOOP FIBER TWICE
AROUND S POOL
1 ON THE RIGHT S IDE ROUTE THE FIR S T 8 FIBER S THROUGH THE S LIDING RADIU S
LIMITER, AROUND THE RIGHT REAR RADIU S LIMITER S TO THE FRONT 8 ADAPTER S .
2 ON THE RIGHT S IDE ROUTE THE NEXT 8 FIBER S THROUGH THE S LIDING RADIU S
LIMITER, AROUND THE RIGHT REAR RADIU S LIMITER S TO THE NEXT 8 ADAPTER S .
3 ON THE RIGHT S IDE ROUTE THE LA S T 8 FIBER S THROUGH THE S LIDING RADIU S
LIMITER, AROUND THE RIGHT REAR RADIU S LIMITER S TO THE BACK 8 ADAPTER S .
4 ON THE LEFT S IDE ROUTE THE FIR S T EIGHT FIBER S THROUGH THE S LIDING RADIU S
LIMITER, AROUND THE LEFT REAR RADIU S LIMITER S , AROUND THE S TORAGE S POOL
TO THE BACK 8 ADAPTER S . WIND S LACK CABLE AROUND S TORAGE S POOL IN THE
DIRECTION S HOWN.
5 ON THE LEFT S IDE ROUTE THE NEXT EIGHT FIBER S THROUGH THE S LIDING RADIU S
LIMITER, AROUND THE LEFT REAR RADIU S LIMITER S , AROUND THE S TORAGE S POOL
TO THE NEXT 8 ADAPTER S . WIND S LACK CABLE AROUND S TORAGE S POOL IN THE
DIRECTION S HOWN.
6 ON THE LEFT S IDE ROUTE THE LA S T EIGHT FIBER S THROUGH THE S LIDING RADIU S
LIMITER, AROUND THE LEFT REAR RADIU S LIMITER S , AROUND THE S TORAGE S POOL
TO THE FRONT 8 ADAPTER S . WIND S LACK CABLE AROUND S TORAGE S POOL IN THE
DIRECTION S HOWN.
Figure 13. Cable Routing for 24-Position Termination and Storage Tray, Left Storage
Page 17
© 2020, CommScope Inc.
ADCP-90-326 • Rev B • November 2020
6.5
Bulk Storage Only FMT Configuration
Note: The number and length of cables that can be stored in a bulk storage tray depends on the cable dimension (refer to
Route and install the cables as shown in Figure 14 . Place kurly locks at locations indicated.
KURLY
LOCK
KURLY
LOCK
Figure 14. Cable Routing for Bulk Storage Tray
20 3 4 3 -A
Page 18
© 2020, CommScope Inc.
ADCP-90-326 • Rev B • November 2020
6.6
12-Position Termination and Splice Tray
Note: Splicing instructions are not included. For splicing instructions, follow local practice.
Termination and splice trays provide 12 termination and splice positions. Install the cables for a
12-position termination and splice tray as follows:
1. Break out the cable corresponding to the dimensions provided in Figure 15 .
2. Route the cables into the tray as shown in
, and perform the splices outside the tray at an adjacent work area, as shown. Perform the splices following local practice.
Refer to pigtail installation drawing (provided with FMT) for pigtail connection scheme.
3. Loop the cables three times around the radius limiters as shown in Figure 17 .
Note:
Tie off the cable at the tie off point shown in Figure 17 , using a one-inch section of
soft wall jacket per the breakout dimensions shown in Figure 15 .
900 MICRON
JACKETED
FIBERS
SECTION OF
SOFT WALL
JACKET
SOFT WALL
PIGTAIL BUNDLE
16967-A
48 IN. (121.9 CM) 1 IN. (2.5 CM)
133 IN. (337.8 CM)
Figure 15. 12-Position Termination and Splice Tray Breakout Dimensions
4. Carefully position the tray within the splice area as shown in Figure 18 . Make certain that
the pre-terminated and customer fiber bundles are properly routed around the appropriate radius limiters as they enter the FMT (see
5. Use the kurly locks provided to bundle fibers together as needed. Place kurly locks at
locations indicated in Figure 19 .
6. Verify that the completed tray looks as shown (see Figure 19
).
Page 19
© 2020, CommScope Inc.
ADCP-90-326 • Rev B • November 2020
TIE OFF
CU S TOMER
FIBER BUNDLE
TO S LIDING
ADAPTER PACK S
PRE-TERMINATED
FIBER BUNDLE
CU S TOMER
FIBER BUNDLE
S PLICE
TRAY
20 3 44-A
Figure 16. Cable Routing for 12-Position Termination and Splice Tray, Step 2
Page 20
© 2020, CommScope Inc.
TIE OFF
ADCP-90-326 • Rev B • November 2020
CU S TOMER
FIBER BUNDLE
LOOP
THREE
TIME S
TO S LIDING
ADAPTER PACK S
PRE-TERMINATED
FIBER BUNDLE
TIE OFF
POINT
PRE-TERMINATED
FIBER
CU S TOMER
FIBER BUNDLE
TIE OFF
POINT
CU S TOMER
FIBER
S PLICE
TRAY
CU S TOMER
FIBER
PRE-TERMINATED
FIBER
20 3 45-A
Figure 17. Cable Routing for 12-Position Termination and Splice Tray, Step 3
Page 21
© 2020, CommScope Inc.
ADCP-90-326 • Rev B • November 2020
TIE OFF
CU S TOMER
FIBER BUNDLE
TO S LIDING
ADAPTER PACK S
20 3 46-A
Figure 18. Cable Routing for 12 Termination and Splice Tray, Step 4
TIE OFF
CU S TOMER
PATCHCORD S
20205-A
Figure 19. Completed Cable Routing for 12-Position Termination and Splice Tray
Page 22
© 2020, CommScope Inc.
CU S TOMER
FIBER BUNDLE
KURLY
LOCK
( 3 PLACE S )
ADCP-90-326 • Rev B • November 2020
7 OPERATION
The term “operation” refers to procedures performed on an ongoing basis after the FMT is installed. The only FMT trays that require operation are those having a termination function.
Patch cords may be installed in such trays for use in connecting or testing equipment. When routing patch cords, refer to the routing diagrams provided in
Section 6 Installing and Routing
Cables . For instructions on accessing adapters, refer to the following instructions.
7.1
Opening Tray
Caution: Placing a load in excess of 5 pounds (2.3 kg) onto an open tray will result in misalignment or damage to the tray.
To open the FMT tray, slide the release tabs inward with both hands and pull the drawer straight
out as far as it goes. The latch locks the tray in the open position as shown in Figure 20
.
PRESS TO
RELEASE
RELEASE
TAB
Figure 20. Tray Locked in Open Position
RELEASE
TAB
20204-A
Page 23
© 2020, CommScope Inc.
ADCP-90-326 • Rev B • November 2020
7.2
Accessing Sliding Adapter Packs
Danger: Infrared radiation is invisible and can seriously damage the retina of the eye. Do not look into the ends of any optical fiber. Do not look directly into the optical adapters of the adapter packs. Exposure to invisible laser radiation may result. An optical power meter should be used to verify active fibers. A protective cap or hood MUST be immediately placed over any radiating adapter or optical fiber connector to avoid the potential of radiation exposure. This practice also prevents dirt particles from entering the adapter or connector .
Note: Always inspect connectors and adapters when connecting connectors to adapters.
For cleaning procedures, refer to ADCP-90-139.
To access a sliding adapter pack ( Figure 21 ):
1. Route the patch cord into the tray as shown in the appropriate diagram in Section 6
.
2. Lift up the release tab and slide up the adapter pack.
18541-A
Figure 21. Removing Dust Cap From Sliding Adapter
3. Pull the dust cap straight out.
4. Connect the patch cord connector to the adapter.
5. Slide down the adapter back to its home position.
6. Close the tray.
Page 24
© 2020, CommScope Inc.
ADCP-90-326 • Rev B • November 2020
7.3
Accessing Bulkhead Plate Adapters
Danger: Infrared radiation is invisible and can seriously damage the retina of the eye. Do not look into the ends of any optical fiber. Do not look directly into the optical adapters of the adapter packs. Exposure to invisible laser radiation may result. An optical power meter should be used to verify active fibers. A protective cap or hood MUST be immediately placed over any radiating adapter or optical fiber connector to avoid the potential of radiation exposure. This practice also prevents dirt particles from entering the adapter or connector .
Note: Always inspect connectors and adapters when connecting connectors to adapters.
For cleaning procedures, refer to ADCP-90-139.
Use the following procedure to connect a patch cord to an FMT having bulkhead plate adapters:
1. Route the patch cord into the tray as shown in the appropriate diagram in Section 6
.
2. Pull the dust cap straight out.
3. Connect the patch cord connector to the adapter.
4. Close the tray.
7.4
Closing the Tray
Close the tray using the following procedure:
1. If closing a tray with sliding adapter pack, fully lower and seat all adapter packs.
2. Assure that all cables and fibers are properly secured and located below the top surface of the tray.
3. Assure that all unused adapters are covered with dust caps.
4. Release the lock open latch (“unlocked position” shown in Figure 20 on page 23 ).
5. Slowly close tray, observing that no fiber kinks or microbends occur as a result of fiber routing.
Page 25
ADCP-90-326 • Rev B • November 2020
8 CUSTOMER INFORMATION AND ASSISTANCE
For general product information, visit our website: http://www.commscope.com
For technical assistance, contact the CommScope Support Center using the following URL: http://www.commscope.com/SupportCenter
For information on patents, go to http://www.cs-pat
Page 26
© 2020, CommScope Inc.