TrueAlert ES Addressable US/Weather Proof Ceiling Mount Speaker Notification Appliances
Installation Instructions
Cautions, warnings, and regulatory information
Important: When the notification appliance emits light or sound, it indicates the possibility of an emergency situation that requires immediate attention of all occupants.
SAFETY: Always install, maintain, and test notification appliances within their specifications. Failure to follow all safety precautions and instructions may result in loss of life and property due to non-functioning notification appliances. Some notification appliances use high voltage. To avoid electrical hazards and avoid damage to appliances, make sure that the electrical power for the Notification Appliance
Circuit is disconnected at the control panel before installing, repairing, or internally adjusting any notification appliances. Even with electrical power removed, some notification appliances (such as visible strobes) store a high voltage charge. The high voltage can cause injury resulting in death from electrical shock. DO NOT TOUCH EXPOSED CIRCUITRY.
LOCATION REFERENCE: Location and quantity of appliances required must conform to the applicable local standards and guidelines
(the National Fire Alarm and Signaling Code (NFPA 72); ULC Standard CAN/ULC-S524, Installation of Fire Alarm Systems; the appropriate model building codes, etc.) and specific requirements of the Local Authority Having Jurisdiction (AHJ). These notification appliances are not intended for installation within hazardous locations as defined by the National Electrical Code (NEC) or NFPA.
UL listed TrueAlert ES indoor product identification reference
Table 1: Product Identification Reference
Type
Figure 1: Ceiling
Mount
Speaker/
Visible(S/V) with cover
Cover colors
• Red
• White
• Red
• White
Models
Components:
A49SVH-APPLC-O
A49SVH-APPLC-O
Components:
A49SO-APPLC-O
A49SO-APPLC-O-BA
Covers:
A49SVC-CRALT-O
A49SVC-CRFIRE-O
A49SVC-CRS-O
A49SVC-CRBC-O
A49SVC-CWBC-O
A49SVC-CWFIRE-O
A49SVC-CRFEU-O
A49SVC-CRBF-O
A49SVC-CWALT-O
A49SVC-CWBA-O
A49SVC-CRBA-O
A49SVC-CWS-O
A49SVC-CWBF-O
A49SVC-CWFEU-O
A49SVC-CK-O
A49SOC-CRS-O
A49SOC-CWFIRE-O
A49SOC-CWS-O
A49SOC-CK-O
Back boxes:
A49WPBB-SVCR
A49WPBB-SVCW
Back boxes:
A49WPBB-SOCR
A49WPBB-SOCW
Operation
These appliances provide an audible (SO) or audible/visible (S/
V) warning of an alarm condition when activated from the control panel of a compatible UL/ULC
Listed, Autocall Fire Alarm
System. Consult Autocall Fire
Alarm panel documentation for compatibility information. The speakers can be turned ON/OFF individually under compatible panel control.
Covers:
A49SOC-CW-O
A49SOC-CR-O
A49SOC-CWALT-O
A49SOC-CRALT-O
A49SOC-CRFIRE-O
Figure 2: Ceiling
MountS peaker
Only (SO) with cover
Kit contents:
Not included:
Appliance x1, with 1.25 inch thread forming screws (#8-16 thread) x 4.
Order a back box to mount the appliance assembly to the ceiling. Order a cover separately for each appliance.
Note: For information about TrueAlert ES appliance testing consult TrueAlert ES Addressable Appliances Troubleshooting (579-1049AC).
Strobe operation levels
The A49 S/V appliances have multiple strobe intensity levels. Levels W135, W110, and W185 are rated for UL outdoor private mode applications. Level
110 is rated for UL indoor and uncontrolled wet Public Mode applications.
579-1241AC Rev A
*05791241ACA*
TrueAlert ES Addressable US/Weather Proof Ceiling Mount Speaker Notification Appliances Installation
Instructions
Mounting instructions
1.
Select the mounting location and install the back box using screws suitable for the mounting surface.
2.
Connect the building wires to the terminals at the back of the appliance, see the wiring section.
3.
Secure the appliance to the back box using the provided hardware.
4.
Set the appliance settings. See
Setting the address DIP switch
.
5.
Attach the cover to the appliance. For the A49SO, align the cover mounting tab with the tab in the backbox, and carefully place the cover onto the unit. For the A49SVH, align the cover mounting tab with the strobe dome, and carefully place the cover over the unit.
6.
Press the cover until it snaps into place.
Weather proof back box Weather proof back box
Cover
SO Appliance
Cover
S/V Appliance
Screws #8-16 x 1.25 inch Screws #8-16 x 1.25 inch
Figure 3: Mounting instructions
Wiring instructions
Warning: Make sure that all power is disconnected before starting the installation.
1.
At the back box, connect the building wiring to the CKT + and CKT - terminals on the appliance.
2.
To ensure proper continuity, use a torque wrench to tighten the terminal block screws to 12-15 inch-pounds.
3.
Ensure that the correct polarity is maintained for each strobe unit.
4.
SLC wiring must be twisted pair (TWP). CKT Terminals accept 2 Wires: 12-18 American wire gauge (AWG) TWP .
Important: Strip the lead insulation to 7/16 inch maximum.
page 2 579-1241AC Rev A
TrueAlert ES Addressable US/Weather Proof Ceiling Mount Speaker Notification Appliances Installation
Instructions
Terminal 2: ‘NAC-’
Terminal 1: ‘NAC+’
Terminal 3: ‘Audio+’
Terminal 4: ‘Audio-’
S/V, S/O S/V, S/O S/V, S/O
Class A Wiring (See Notes)
From Compatible SLC
Controller (See Notes)
From Amplifier
Audio +
Audio -
Audio -
Audio +
SLC -
1
CKT
2
SLC +
3
CKT
4
Audio Audio +
SLC -
1
CKT
2
SLC +
3
CKT
4
Audio Audio +
SLC -
1
CKT
2
SLC +
3
CKT
4
Audio Audio +
Audio -
Audio +
To Next Appliance or Compatible SLC
Controller
(See Notes)
(T-tapping example)
S/V Appliance Back Side
S/V, S/O S/V, S/O S/V, S/O S/V, S/O
Terminal 2: ‘NAC-’
Terminal 1: ‘NAC+’
Terminal 3: ‘Audio+’
Terminal 4: ‘Audio-’
Class B Wiring (See Notes)
From Compatible SLC
Controller (See Notes)
From Amplifier
Audio +
Audio -
Audio -
Audio +
1 2
CKT
3 4
SLC -
SLC +
Audio -
Audio +
1 2
CKT
3 4
Audio -
Audio +
SLC -
SLC +
1 2
CKT
3 4 1
SLC -
SLC +
Audio -
Audio +
2
CKT
3 4
SO Appliance Back Side
Figure 4: Wiring instructions
Wiring notes:
1.
Assign a maximum of 127 active appliances to a circuit. Assign a maximum of 12 active strobe appliances to a powered circuit. The maximum wire resistance between appliances is 25 ohms. Refer to the Field Wiring Diagrams of the driving compatible fire alarm control panel for further instructions.
2.
Notification appliances are rated using an individual module label.
3.
Maintain the correct polarity on the terminal connections.
4.
Terminals 1 through 6 each accommodate two wires, one wire going in and one wire going out to the next appliance.
5.
These appliances are rated to the operating voltage limits of 23-30 VDC. The appliance can fail to operate as intended, and can cause permanent damage to this equipment if it operates outside of these limits.
6.
Only operate the TrueAlert IDNAC S/V and SO using a compatible power supply and amplifier.
7.
T-tapping is not permitted for Class A wiring.
8.
TrueAlert SLC wiring connections are supervised and power-limited.
Setting the address DIP switch
Each addressable TrueAlert IDNAC notification appliance has a unique address that is set using an eight-position DIP switch (ADDR1).
Assign up to 127 unique addresses an signaling line circuit (SLC), however, the total appliance loading available may be less due to appliance current requirements.
To set the address complete the following steps:
1.
Unclip the cover from the appliance by inserting a slotted screwdriver, or a similar sized object into the opening at either end of the cover.
2.
Use a non-metallic stylus, or the equivalent to set the switches.
3.
Record the set address.
4.
DIP switch position 8 determines whether this appliance is viewed by the system as an 'ALARM' (OFF) or 'ALERT' (ON) type of appliance.
Confirm the setting for the appliance at this address with the FACP system configuration documentation.
page 3 579-1241AC Rev A
TrueAlert ES Addressable US/Weather Proof Ceiling Mount Speaker Notification Appliances Installation
Instructions
To Access Switches:
ALARM/
ALERT
DIP SWITCHES 5 THROUGH 7
000 100 010 110 001
68
69
70
64
65
66
67
75
76
77
78
79
71
72
73
74
101
91
92
93
94
95
87
88
89
90
84
85
86
80
81
82
83
011
100
101
102
103
96
97
98
99
108
109
110
111
104
105
106
107
111
116
117
118
119
112
113
114
115
124
125
126
127
120
121
122
123
SO Appliance
S/V Appliance
Figure 5: Setting the DIP switch address
Setting the strobe candela setting
1.
The jumpers are factory set to FACP. Use this setting when programming the candela setting at the 4100ES FACP. The candela setting is visible through the slot on the side of the appliance.
2.
For manual selection, remove the cover and slide the candela flag to the required setting:
W75, W110, W185, 110 candela, or FACP.
The candela setting is visible through the slot on the side of the appliance.
Note: To avoid a programming mismatch trouble, an authorized service personnel must program one of the four candela outputs for each appliance.
To set the candela through the Programmer, set it to FACP. For additional information refer to the 4100ES Programmer’s Manual (574-849AC).
page 4 579-1241AC Rev A
TrueAlert ES Addressable US/Weather Proof Ceiling Mount Speaker Notification Appliances Installation
Instructions
Audio circuit configuration for S/V and SO appliances
The jumper at P2, on the speaker transformer drive board at the rear of the unit, is factory set to 1-2 for a 25V-1/4W output. For a 70V- 2W output, set
the jumper to 2-3, see Figure 6. Use the default setting, 1-2, for all other speaker tap settings.
Audio Circuit Configuration Speaker transformer drive board at the rear of the unit
110
W185
W135
W110
L1
P2
1
J2
Figure 6: Setting the strobe and appliance configuration
Appliance specifications
Table 2: Environmental specifications
Specifications
Rated DC Control/Strobe Voltage Range
UL/ULC temperature rating -
W110 CD/W135 CD/W185 CD
UL/ULC temperature rating for indoor and uncontrolled wet Public Mode - 110 CD
FM temperature rating
UL/ULC humidity range
Details
SPECIAL APPLICATION 23-30 VDC
-40 °F to 151 °F (-40 °C to 66 °C)
0 °F to 120 °F (0 °C to 49 °C)
-40 °F to 120°F (-40 °C to 50 °C)
95 %, non-condensing at 60 °F (60 °C)
Connections Terminal for 18 AWG to 12 AWG (0.82 mm
2
to 3.31 mm
2
)
CAUTION: The appliance covers and backboxes are available in red and white. Do not paint or otherwise alter the factory finishes in any way.
Table 3: Maximum RMS operating current
A49SVH-APPLC-O
Candela
W110
W135
Speaker Only
Current
308 mA
335 mA
Candela
W185
110
SO
Current
398 mA
305 mA
15 mA
Specifications
Input voltage
Power taps using Jumper J1
Frequency response Fire Alarm
Table 4: Speaker Specifications
Details
25 VRMS or 70.7 VRMS -
Speakers are for connection to compatible fire alarm audio circuits.
1/4 W, 1/2 W, 1 W and 2 W
400 Hz to 4000 Hz
Table 5: Vertical and horizontal light dispersion ratings (ceiling to walls and floors)
±5
±10
±15
±20
±25
Percent of rated light output at 110 candela setting (room temperature)
Vertical dispersion Horizontal dispersion
Y-Plane Angle
0
UL Req Output
100 %
Typical Output
327 %
X-Plane Angle
0
UL Req Output
100 %
90 %
90 %
90 %
90 %
90 %
293 %
281 %
197 %
168 %
142 %
±5
±10
±15
±20
±25
90 %
90 %
90 %
90 %
90 %
Typical Output
343 %
160 %
175 %
129 %
145 %
165 % page 5 579-1241AC Rev A
Table 5: Vertical and horizontal light dispersion ratings (ceiling to walls and floors)
±75
±80
±85
±90
±55
±60
±65
±70
±35
±40
±45
±50
Percent of rated light output at 110 candela setting (room temperature)
Vertical dispersion Horizontal dispersion
Y-Plane Angle
±30
UL Req Output
75 %
Typical Output
143 %
X-Plane Angle
±30
UL Req Output
75 %
75 %
75 %
75 %
55 %
155 %
156 %
134 %
115 %
±35
±40
±45
±50
75 %
75 %
75 %
55 %
45 %
40 %
35 %
35 %
30 %
30 %
25 %
25 %
104 %
103 %
98 %
87 %
90 %
96 %
96 %
83 %
±55
±60
±65
±70
±75
±80
±85
±90
45 %
40 %
35 %
35 %
30 %
30 %
25 %
25 %
Typical Output
152 %
144 %
139 %
129 %
129 %
123 %
111 %
120 %
103 %
75 %
83 %
70 %
47 %
Table 6: TrueAlert Addressable Ceiling Mount S/V and SO Units- speaker switch setting and output ratings (25 V or 70 V audio)
-
25 V
70.7 V
1
2
1
2
1/4
1/2
Tap Settings in
Watts
1/4
1/2
UL reverberant at 10 ft
80
83
86
88
78
82
85
88
ULC anechoic at 3 m
82
85*
88*
90*
80
84
87*
90*
Note:
• Reverberant dBA measurements are a minimum UL rating based on sound level measurements made in ULs reverberant test chamber.
• Anechoic dBA measurements are a minimum ULC rating based on sound pressure level measurements made in ULCs anechoic test chamber.
• The sound pressure level decreases by 3dB at an angular displacement of 37° from the line perpendicular to the speaker’s center. The SPL decreases by 6 dB at an angle of 55° from that line.
*Only marked settings may be used for ULC fire alarm applications.
Angle
W75 CD at 77°F (25°C)
W110 CD at 77°F (25°C)
W185 CD at 77°F (25°C)
Table 7: Private mode Candela (CD) rating for W110 CD/ W135 CD/ W185 CD
Straight out from unit
0°
320
360
420
Vertical above/below unit
45°
110
140
146
90°
93
103
126
Left/right horizontal
45°
134
145
173
90°
57
63
76
© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice. Additional listings may be applicable, contact your local Autocall product supplier for the latest status. Listings and approvals under Tyco Fire & Security GmbH, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National
Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA).
579-1241AC Rev A
advertisement
Related manuals
advertisement
Table of contents
- 1 Cautions, warnings, and regulatory information
- 1 UL listed TrueAlert ES indoor product identification reference
- 1 Strobe operation levels
- 2 Mounting instructions
- 2 Wiring instructions
- 3 Wiring notes:
- 3 Setting the address DIP switch
- 4 Setting the strobe candela setting
- 5 Audio circuit configuration for S/V and SO appliances
- 5 Appliance specifications