TrueAlert ES Addressable US/Weather Proof Ceiling Mount Speaker Notification Appliances

Installation Instructions

Cautions, warnings, and regulatory information

Important: When the notification appliance emits light or sound, it indicates the possibility of an emergency situation that requires immediate attention of all occupants.

SAFETY: Always install, maintain, and test notification appliances within their specifications. Failure to follow all safety precautions and instructions may result in loss of life and property due to non-functioning notification appliances. Some notification appliances use high voltage. To avoid electrical hazards and avoid damage to appliances, make sure that the electrical power for the Notification Appliance

Circuit is disconnected at the control panel before installing, repairing, or internally adjusting any notification appliances. Even with electrical power removed, some notification appliances (such as visible strobes) store a high voltage charge. The high voltage can cause injury resulting in death from electrical shock. DO NOT TOUCH EXPOSED CIRCUITRY.

LOCATION REFERENCE: Location and quantity of appliances required must conform to the applicable local standards and guidelines

(the National Fire Alarm and Signaling Code (NFPA 72); ULC Standard CAN/ULC-S524, Installation of Fire Alarm Systems; the appropriate model building codes, etc.) and specific requirements of the Local Authority Having Jurisdiction (AHJ). These notification appliances are not intended for installation within hazardous locations as defined by the National Electrical Code (NEC) or NFPA.

UL listed TrueAlert ES indoor product identification reference

Table 1: Product Identification Reference

Type

Figure 1: Ceiling

Mount

Speaker/

Visible(S/V) with cover

Cover colors

• Red

• White

• Red

• White

Models

Components:

A49SVH-APPLC-O

A49SVH-APPLC-O

Components:

A49SO-APPLC-O

A49SO-APPLC-O-BA

Covers:

A49SVC-CRALT-O

A49SVC-CRFIRE-O

A49SVC-CRS-O

A49SVC-CRBC-O

A49SVC-CWBC-O

A49SVC-CWFIRE-O

A49SVC-CRFEU-O

A49SVC-CRBF-O

A49SVC-CWALT-O

A49SVC-CWBA-O

A49SVC-CRBA-O

A49SVC-CWS-O

A49SVC-CWBF-O

A49SVC-CWFEU-O

A49SVC-CK-O

A49SOC-CRS-O

A49SOC-CWFIRE-O

A49SOC-CWS-O

A49SOC-CK-O

Back boxes:

A49WPBB-SVCR

A49WPBB-SVCW

Back boxes:

A49WPBB-SOCR

A49WPBB-SOCW

Operation

These appliances provide an audible (SO) or audible/visible (S/

V) warning of an alarm condition when activated from the control panel of a compatible UL/ULC

Listed, Autocall Fire Alarm

System. Consult Autocall Fire

Alarm panel documentation for compatibility information. The speakers can be turned ON/OFF individually under compatible panel control.

Covers:

A49SOC-CW-O

A49SOC-CR-O

A49SOC-CWALT-O

A49SOC-CRALT-O

A49SOC-CRFIRE-O

Figure 2: Ceiling

MountS peaker

Only (SO) with cover

Kit contents:

Not included:

Appliance x1, with 1.25 inch thread forming screws (#8-16 thread) x 4.

Order a back box to mount the appliance assembly to the ceiling. Order a cover separately for each appliance.

Note: For information about TrueAlert ES appliance testing consult TrueAlert ES Addressable Appliances Troubleshooting (579-1049AC).

Strobe operation levels

The A49 S/V appliances have multiple strobe intensity levels. Levels W135, W110, and W185 are rated for UL outdoor private mode applications. Level

110 is rated for UL indoor and uncontrolled wet Public Mode applications.

579-1241AC Rev A

*05791241ACA*

TrueAlert ES Addressable US/Weather Proof Ceiling Mount Speaker Notification Appliances Installation

Instructions

Mounting instructions

1.

Select the mounting location and install the back box using screws suitable for the mounting surface.

2.

Connect the building wires to the terminals at the back of the appliance, see the wiring section.

3.

Secure the appliance to the back box using the provided hardware.

4.

Set the appliance settings. See

Setting the address DIP switch

.

5.

Attach the cover to the appliance. For the A49SO, align the cover mounting tab with the tab in the backbox, and carefully place the cover onto the unit. For the A49SVH, align the cover mounting tab with the strobe dome, and carefully place the cover over the unit.

6.

Press the cover until it snaps into place.

Weather proof back box Weather proof back box

Cover

SO Appliance

Cover

S/V Appliance

Screws #8-16 x 1.25 inch Screws #8-16 x 1.25 inch

Figure 3: Mounting instructions

Wiring instructions

Warning: Make sure that all power is disconnected before starting the installation.

1.

At the back box, connect the building wiring to the CKT + and CKT - terminals on the appliance.

2.

To ensure proper continuity, use a torque wrench to tighten the terminal block screws to 12-15 inch-pounds.

3.

Ensure that the correct polarity is maintained for each strobe unit.

4.

SLC wiring must be twisted pair (TWP). CKT Terminals accept 2 Wires: 12-18 American wire gauge (AWG) TWP .

Important: Strip the lead insulation to 7/16 inch maximum.

page 2 579-1241AC Rev A

TrueAlert ES Addressable US/Weather Proof Ceiling Mount Speaker Notification Appliances Installation

Instructions

Terminal 2: ‘NAC-’

Terminal 1: ‘NAC+’

Terminal 3: ‘Audio+’

Terminal 4: ‘Audio-’

S/V, S/O S/V, S/O S/V, S/O

Class A Wiring (See Notes)

From Compatible SLC

Controller (See Notes)

From Amplifier

Audio +

Audio -

Audio -

Audio +

SLC -

1

CKT

2

SLC +

3

CKT

4

Audio Audio +

SLC -

1

CKT

2

SLC +

3

CKT

4

Audio Audio +

SLC -

1

CKT

2

SLC +

3

CKT

4

Audio Audio +

Audio -

Audio +

To Next Appliance or Compatible SLC

Controller

(See Notes)

(T-tapping example)

S/V Appliance Back Side

S/V, S/O S/V, S/O S/V, S/O S/V, S/O

Terminal 2: ‘NAC-’

Terminal 1: ‘NAC+’

Terminal 3: ‘Audio+’

Terminal 4: ‘Audio-’

Class B Wiring (See Notes)

From Compatible SLC

Controller (See Notes)

From Amplifier

Audio +

Audio -

Audio -

Audio +

1 2

CKT

3 4

SLC -

SLC +

Audio -

Audio +

1 2

CKT

3 4

Audio -

Audio +

SLC -

SLC +

1 2

CKT

3 4 1

SLC -

SLC +

Audio -

Audio +

2

CKT

3 4

SO Appliance Back Side

Figure 4: Wiring instructions

Wiring notes:

1.

Assign a maximum of 127 active appliances to a circuit. Assign a maximum of 12 active strobe appliances to a powered circuit. The maximum wire resistance between appliances is 25 ohms. Refer to the Field Wiring Diagrams of the driving compatible fire alarm control panel for further instructions.

2.

Notification appliances are rated using an individual module label.

3.

Maintain the correct polarity on the terminal connections.

4.

Terminals 1 through 6 each accommodate two wires, one wire going in and one wire going out to the next appliance.

5.

These appliances are rated to the operating voltage limits of 23-30 VDC. The appliance can fail to operate as intended, and can cause permanent damage to this equipment if it operates outside of these limits.

6.

Only operate the TrueAlert IDNAC S/V and SO using a compatible power supply and amplifier.

7.

T-tapping is not permitted for Class A wiring.

8.

TrueAlert SLC wiring connections are supervised and power-limited.

Setting the address DIP switch

Each addressable TrueAlert IDNAC notification appliance has a unique address that is set using an eight-position DIP switch (ADDR1).

Assign up to 127 unique addresses an signaling line circuit (SLC), however, the total appliance loading available may be less due to appliance current requirements.

To set the address complete the following steps:

1.

Unclip the cover from the appliance by inserting a slotted screwdriver, or a similar sized object into the opening at either end of the cover.

See Figure 5.

2.

Use a non-metallic stylus, or the equivalent to set the switches.

3.

Record the set address.

4.

DIP switch position 8 determines whether this appliance is viewed by the system as an 'ALARM' (OFF) or 'ALERT' (ON) type of appliance.

Confirm the setting for the appliance at this address with the FACP system configuration documentation.

page 3 579-1241AC Rev A

TrueAlert ES Addressable US/Weather Proof Ceiling Mount Speaker Notification Appliances Installation

Instructions

To Access Switches:

ALARM/

ALERT

DIP SWITCHES 5 THROUGH 7

000 100 010 110 001

68

69

70

64

65

66

67

75

76

77

78

79

71

72

73

74

101

91

92

93

94

95

87

88

89

90

84

85

86

80

81

82

83

011

100

101

102

103

96

97

98

99

108

109

110

111

104

105

106

107

111

116

117

118

119

112

113

114

115

124

125

126

127

120

121

122

123

SO Appliance

S/V Appliance

Figure 5: Setting the DIP switch address

Setting the strobe candela setting

1.

The jumpers are factory set to FACP. Use this setting when programming the candela setting at the 4100ES FACP. The candela setting is visible through the slot on the side of the appliance.

2.

For manual selection, remove the cover and slide the candela flag to the required setting:

W75, W110, W185, 110 candela, or FACP.

The candela setting is visible through the slot on the side of the appliance.

Note: To avoid a programming mismatch trouble, an authorized service personnel must program one of the four candela outputs for each appliance.

To set the candela through the Programmer, set it to FACP. For additional information refer to the 4100ES Programmer’s Manual (574-849AC).

page 4 579-1241AC Rev A

TrueAlert ES Addressable US/Weather Proof Ceiling Mount Speaker Notification Appliances Installation

Instructions

Audio circuit configuration for S/V and SO appliances

Move the wire harness position to the correct terminal post for audio circuit voltage and power tap selection. See Figure 6 and Table 4.

The jumper at P2, on the speaker transformer drive board at the rear of the unit, is factory set to 1-2 for a 25V-1/4W output. For a 70V- 2W output, set

the jumper to 2-3, see Figure 6. Use the default setting, 1-2, for all other speaker tap settings.

Audio Circuit Configuration Speaker transformer drive board at the rear of the unit

110

W185

W135

W110

L1

P2

1

J2

Figure 6: Setting the strobe and appliance configuration

Appliance specifications

Table 2: Environmental specifications

Specifications

Rated DC Control/Strobe Voltage Range

UL/ULC temperature rating -

W110 CD/W135 CD/W185 CD

UL/ULC temperature rating for indoor and uncontrolled wet Public Mode - 110 CD

FM temperature rating

UL/ULC humidity range

Details

SPECIAL APPLICATION 23-30 VDC

-40 °F to 151 °F (-40 °C to 66 °C)

0 °F to 120 °F (0 °C to 49 °C)

-40 °F to 120°F (-40 °C to 50 °C)

95 %, non-condensing at 60 °F (60 °C)

Connections Terminal for 18 AWG to 12 AWG (0.82 mm

2

to 3.31 mm

2

)

CAUTION: The appliance covers and backboxes are available in red and white. Do not paint or otherwise alter the factory finishes in any way.

Table 3: Maximum RMS operating current

A49SVH-APPLC-O

Candela

W110

W135

Speaker Only

Current

308 mA

335 mA

Candela

W185

110

SO

Current

398 mA

305 mA

15 mA

Specifications

Input voltage

Power taps using Jumper J1

Frequency response Fire Alarm

Table 4: Speaker Specifications

Details

25 VRMS or 70.7 VRMS -

Speakers are for connection to compatible fire alarm audio circuits.

1/4 W, 1/2 W, 1 W and 2 W

400 Hz to 4000 Hz

Table 5: Vertical and horizontal light dispersion ratings (ceiling to walls and floors)

±5

±10

±15

±20

±25

Percent of rated light output at 110 candela setting (room temperature)

Vertical dispersion Horizontal dispersion

Y-Plane Angle

0

UL Req Output

100 %

Typical Output

327 %

X-Plane Angle

0

UL Req Output

100 %

90 %

90 %

90 %

90 %

90 %

293 %

281 %

197 %

168 %

142 %

±5

±10

±15

±20

±25

90 %

90 %

90 %

90 %

90 %

Typical Output

343 %

160 %

175 %

129 %

145 %

165 % page 5 579-1241AC Rev A

Table 5: Vertical and horizontal light dispersion ratings (ceiling to walls and floors)

±75

±80

±85

±90

±55

±60

±65

±70

±35

±40

±45

±50

Percent of rated light output at 110 candela setting (room temperature)

Vertical dispersion Horizontal dispersion

Y-Plane Angle

±30

UL Req Output

75 %

Typical Output

143 %

X-Plane Angle

±30

UL Req Output

75 %

75 %

75 %

75 %

55 %

155 %

156 %

134 %

115 %

±35

±40

±45

±50

75 %

75 %

75 %

55 %

45 %

40 %

35 %

35 %

30 %

30 %

25 %

25 %

104 %

103 %

98 %

87 %

90 %

96 %

96 %

83 %

±55

±60

±65

±70

±75

±80

±85

±90

45 %

40 %

35 %

35 %

30 %

30 %

25 %

25 %

Typical Output

152 %

144 %

139 %

129 %

129 %

123 %

111 %

120 %

103 %

75 %

83 %

70 %

47 %

Table 6: TrueAlert Addressable Ceiling Mount S/V and SO Units- speaker switch setting and output ratings (25 V or 70 V audio)

-

25 V

70.7 V

1

2

1

2

1/4

1/2

Tap Settings in

Watts

1/4

1/2

UL reverberant at 10 ft

80

83

86

88

78

82

85

88

ULC anechoic at 3 m

82

85*

88*

90*

80

84

87*

90*

Note:

• Reverberant dBA measurements are a minimum UL rating based on sound level measurements made in ULs reverberant test chamber.

• Anechoic dBA measurements are a minimum ULC rating based on sound pressure level measurements made in ULCs anechoic test chamber.

• The sound pressure level decreases by 3dB at an angular displacement of 37° from the line perpendicular to the speaker’s center. The SPL decreases by 6 dB at an angle of 55° from that line.

*Only marked settings may be used for ULC fire alarm applications.

Angle

W75 CD at 77°F (25°C)

W110 CD at 77°F (25°C)

W185 CD at 77°F (25°C)

Table 7: Private mode Candela (CD) rating for W110 CD/ W135 CD/ W185 CD

Straight out from unit

320

360

420

Vertical above/below unit

45°

110

140

146

90°

93

103

126

Left/right horizontal

45°

134

145

173

90°

57

63

76

© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice. Additional listings may be applicable, contact your local Autocall product supplier for the latest status. Listings and approvals under Tyco Fire & Security GmbH, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National

Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA).

579-1241AC Rev A