Duran Electronica DURTOX-X Installation & User Manual

Add to My manuals
12 Pages

advertisement

Duran Electronica DURTOX-X Installation & User Manual | Manualzz

DURTOX-X

ELECTROCHEMICAL DETECTORS FOR TOXIC GASES AND O

2

Installation & User Manual

Certificate nº FS82426

© 2010 DURAN ELECTRONICA S.L. - All rights reserved · www.duranelectronica.com

I-manDURTOX-v01

TABLE OF CONTENTS

6

7

4.

5.

1.

2.

3.

8

9

10 page

DURTOX-X. Electrochemical technology detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

RELAY OUTPUT MODULE (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

ADDRESSING RS485C DETECTORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

OPTICAL INDICATORS (internal LEDs): signals and functioning . . . . . . . . . . . . . . . . . . 7

TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

TECHNICAL CHARACTERISTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

INFORMATION ABOUT ATEX MARKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

GUARANTEE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

EC DECLARATION OF CONFORMITY.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

I-manDURTOX-v0 1

3

1. DURTOX-X. Electrochemical technology detectors

DURTOX-X is an exproof detector using electrochemical technology for the detection of toxic gases and O

2

.

Available gases Installation height Area covered

Carbon monoxide CO

Hydrogen sulfide H

2

S

Ammonia NH

3

Nitrogen dioxide NO

2

Oxygen O

2

Standard range*

0-300ppm*

0-100ppm / 0-200ppm*

0-100ppm*/0-1000ppm/0-5000ppm

0-20ppm*

0-25% vol*

1,50 to 2m from floor

1m from floor

30cm from ceiling

1m from floor

1,70 to 2m from floor

300 m 2

150 m 2

75 m 2

200 m 2

200 m 2

* Ranges available with RS485C detectors compatible with EUROSONDELCO / SIEMENS CC62P

Communication formats

• RS485C addressable, 4 wire connection, compatible with EUROSONDELCO and SIEMENS

CC62P control panels. Up to 16 detectors can be connected in parallel on the same loop.

• 4-20mA , 3 wire connection, compatible with any standard system provided with this type of input.

Applications

DURTOX-X exproof detectors have been designed for environments in which the formation of explosive atmospheres due to gases or vapours is probable, and assure a high level of protection.

(Group of apparatus II – ATEX Directive Category 2)

Special features

• Provided with a 12bit microprocessor allowing total control over the sensor status..

• Thermal compensation that allows a correct response from each of the electrochemical sensors when faced with temperature variations, except for DURTOX-X O2, which due to its systems does not require such a feature.

• Self testing hardware.

• Digital filter based on variable samplings of the sensor average values

• Auto-Zero automatic adjustment This special feature monitors zero value in relation to sensor response and electronics. The following protocol is used for this: Every 30 minutes an automatic test is performed, if drift is +/- than 2% of the full scale, it will readjust itself to zero, otherwise it will be shown as a readout.

• Other features accessible with factory based methodology allow us to check on the sensor remaining useful life, date of manufacture, date of last calibration and serial number.

2. RELAY OUTPUT MODULE (optional)

The optional relay output for the RS485 models of DURTOX-X is programmed with the following default values:

Activated, instantaneous –no delay-

Alarm: 50ppm for CO, 10ppm for H

2

S, 25ppm for NH

3

, 5ppm for NO

2

, <18% for O

2

4 © 2010 DURAN ELECTRONICA S.L.

All rights reserved · www.duranelectronica.com

3. CONNECTIONS

IMPORTANT – Instructions regarding cable glands for ATEX detectors:

The user must ensure the cable is well anchored. The minimum torque setting applicable to the cap is 20 Nm.. Check cable entry tightness after any maintenance operation: If cable has moved, tighten up the cap again. If tightening isn’t possible, send the detector back to factory for cable gland replacement.

DURTOX-X with RS485C communication:

I-manDURTOX-v0 1

5

DURTOX-X with 4-20mA communication :

IMPORTANT:

If the system where detectors are to be connected does not have 4-20mA inputs, but 0-5 or

0-10V DC tension inputs, a resistance must be connected between negative (-) and signal (s), on the receptor device. Resistance value will depend on the detector power tension in accordance to the following table:

6 © 2010 DURAN ELECTRONICA S.L.

All rights reserved · www.duranelectronica.com

Detector Tension

Between 10V and 18V DC

Between 18V and 30V DC

Load Resistance

250 Ω 1%

500 Ω 1%

Tension Range (4-20mA)

From 1V to 5V DC

From 2V to 10V DC

4. ADDRESSING RS485 DETECTORS

Before connecting DURTOX-X detectors to EUROSONDELCO or SIEMENS CC62P , they must be addressed. If more than one detector is connected to the same loop, assign a number to each of them according to table 1.

Table 1- NUMBERING DETECTORS USING SW1 (addressing)

Detector nr.

01

02

03

04

05

06

11

12

13

14

15

16

07

08

09

10

On

Off

On

Off

On

Off

On

Off

On

Off

1

On

Off

On

Off

On

Off

Off

Off

On

On

Off

Off

Off

Off

On

On

2

On

On

Off

Off

On

On

On

On

Off

Off

Off

Off

Off

Off

On

On

3

On

On

On

On

Off

Off

Off

Off

Off

Off

Off

Off

On

On

Off

Off

4

On

On

On

On

On

On

5. OPTICAL INDICATORS (internal LEDs): signals and functioning

RS485C models – installed in vertical module -

• Fast intermittent: during initialization and recognition of the loop by the module line.

• Periodic intermittent: normal functioning. Time between blinking, in seconds, will correspond with the assigned number of the detector (1 to 16).

• 6-blink burst: Line failure. A-B communication cable is cut.

• 1 second cadence: failure or short circuit in the A-B communication lines. More than 5 minutes have passed without the detector being able to communicate with the module line.

4-20mA models –installed in main module-

• LD1: indicates the detector operational status.

• LD2: this LED will turn on in case of any internal failure in the detector as well as to indicate a positive or negative scale overflow.

I-manDURTOX-v0 1

7

6. TEST

Once connected, DURTOX-X begins to count a 60 second sensor stabilization time. During this time the 4-20mA model will have a tension output of only 1,9mA, later increasing to 4mA.

Do not open these detectors while powered. Adjustments or calibrations of the installation are not allowed. Due to the technology applied, these operations can only be carried out at the factory.

Perform a check-up test at least once a year using gas tester containers with the right composition for each gas.

Using any other means could poison or destroy the sensor and, therefore, the guarantee would be invalidated.

All detectors manufactured by DURAN ELECTRONICA are factory calibrated with the appropriate target gas.

Therefore, manipulation is neither required nor advisable once installed.

7. TECHNICAL CHARACTERISTICS

Technology

Power

Maximum consumption

Useful life

Accuracy

Repeatability

Initialization stabilization delay when connecting

- all versions -

12bit Microprocessor and electrochemical sensors

10 to 30V DC (4-20mA)/10 to 15V (RS485C)

43mA to 12V DC

± 2 years in air, 4 years CO

± 5% bottom of scale

± 5% bottom of scale

Approx. 5 minutes

T90 response time

Temperature and humidity ranges

Working atmospheric pressure

Air velocity

Maintenance periods

Explosive atmosphere code

Housing material

Stopping plug material

Cable gland material and cable diameter

Adaptor material & syntherized filter

Cable type (RS485)

Cable type (4-20mA)

Maximum installation distance

Dimensions (mm) & weight (gr)

CO & NH3 ≤ 30s

H2S ≤ 20s

O2 ≤ 15s

-10ºC to +50ºC

20-90% Hr

90-110 KPa

<0.1-0.5m/s

Annual - recommended -

II 2G Ex d IIC T6 Gb

Aluminium & Epoxy paint

Type PLG

Natural brass & Santoprene 6-10mm 2

Stainless steel.

4 wire shielded (power 2 x 1,5 + A and B communications

2 x 0,25 twisted pair)

3 X 1,5mm Ø shielded, recommended minimum

1000m (RS485C) & 350m (4-20mA)

162 x 150 x 90 / 1.392

8 © 2010 DURAN ELECTRONICA S.L.

All rights reserved · www.duranelectronica.com

8. INFORMATION ABOUT ATEX MARKING

0163

EC marking in conformity with Directive 94 / 9 / EC (ATEX).

(the number 0163 corresponds to the Notified Body,

Laboratorio Oficial J. M. Madariaga)

II 2 G Ex d IIC T6 Gb

Group II apparatus, Category 2G (explosive atmosphere caused by gases

and vapours) In conformity with protection mode “d” - flameproof enclosures

LOM 10ATEX2076 EC Type Examination Certificate

9. GUARANTEE

DURTOX-X detectors are guaranteed against any manufacturing defect for a 1 year period after the acquisition of

the equipment. If, during this period of time, any anomaly was detected, please inform your provider or installer.

Guarantee covers the full repair of the equipment which DURAN ELECTRONICA Technical Department considers

to be defective, with the purpose of bringing them back to their normal use. This warranty will be valid as long

as the equipment has been installed by a competent person, and always following the specifications contained in

this manual. Negligent installation or use will exempt DURAN ELECTRONICA from any responsibility from

damages caused to objects and/or people, and from the fulfillment of the terms of this warranty. In case of improper

handling, or not respecting the conditions, characteristics and observations described in this manual, DURAN

ELECTRONICA WILL NOT HOLD ITSELF RESPONSIBLE FOR DAMAGES CAUSED BY IMPROPER USE OF THIS PRODUCT.

Guarantee does not include: installations, periodic tests and maintenance, damages caused by inadequate handling,

inappropriate use, negligence, overload, inadequate power or equipment abandonment, tension deviations,

defective installations and all other external causes, repairs or amendments made by personnel not authorized by

DURAN ELECTRONICA and transportation costs of the equipments.

DURAN ELECTRONICA reserves the right to carry out improvements or to include modifications the equipment

without prior notice.

I-manDURTOX-v0 1

9

10. DECLARATION OF CONFORMITY

Víctor Manuel Andrés González, Managing Director of:

DURAN ELECTRÓNICA, S. L.

Tomás Bretón, 50 - 28045 MADRID (Spain)

Declares the conformity of gas detector model DURTOX-X in accordance with the contains of the following European

Parliament and Council directives:

2004/108/EC Electromagnetic compatibility

94/9/EC Equipment and protective systems intended for use in potentially explosive atmospheres conformity assumed by compliance with the following standards:

EN 60079-0:2009

EN 60079-1:2007

Year of affixing the regulatory (Ex d IIC T6 Gb) marking: 2010

EC Type examination certificate number LOM 10ATEX2076

Product Quality Assurance Notification number: LOM 08ATEX9073

Issued by notified body number 0163: Laboratorio Oficial J. M. Madariaga (LOM)

C/ Alenza, 1 – 28003 MADRID (Spain), that authorizes to affix the legal marking.

0163 II 2 G

The LOM 10ATEX2076 certificate does not cover that indicated in the paragraph 2, Article I of the 94/9/EC directive related to safety, controlling and regulating devices, nor the Essential Health and Safety Requeriments indicated in the paragraphs 1.5.5, 1.5.6 and 1.5.7 of the Annex II of the Directive 94/9/EC related to devices with a measuring function.

In witness whereof and for such purposes as may arise

ENTIDAD DURAN

ELECTRONICA SL

- CIF B80418965 -

NOMBRE ANDRES

GONZALEZ

VICTOR MANUEL

- NIF 05244956J

Firmado digitalmente por

ENTIDAD DURAN ELECTRONICA

SL - CIF B80418965 - NOMBRE

ANDRES GONZALEZ VICTOR

MANUEL - NIF 05244956J

Nombre de reconocimiento

(DN): c=ES, o=FNMT, ou=FNMT

Clase 2 CA, ou=703015196, cn=ENTIDAD DURAN

ELECTRONICA SL - CIF

B80418965 - NOMBRE ANDRES

GONZALEZ VICTOR MANUEL -

NIF 05244956J

Fecha: 2010.10.25 12:31:23

+02'00'

10 © 2010 DURAN ELECTRONICA S.L.

All rights reserved · www.duranelectronica.com

I-manDURTOX-v0 1

11

Certificate nº FS82426 c/ Tomás Bretón, 50

28045 MADRID, Spain

Phone: +34 91 528 93 75

Fax +34 91 527 58 19 [email protected]

www.duranelectronica.com

I-manDURTOX-v01

advertisement

Related manuals

Frequently Answers and Questions

What type of gases is the DURTOX-X used to detect?
It is used to detect toxic gases and oxygen (O2).
How many detectors can be connected to the same loop?
Up to 16 detectors can be connected in parallel on the same loop.
What is the maximum distance the detector can be installed from the control panel?
The maximum installation distance is 1000m (RS485C) & 350m (4-20mA).
How often should the detector be tested?
At least once a year.
Is the detector user-serviceable?
No, adjustments or calibrations of the installation are not allowed. These operations can only be carried out at the factory.
What is the warranty period for the detector?
DURTOX-X detectors are guaranteed against any manufacturing defect for a 1 year period after the acquisition of the equipment.