Lennox EL195 Gas Furnace Installation Manual

Add to My manuals
56 Pages

advertisement

Lennox EL195 Gas Furnace Installation Manual | Manualzz

E 2011 Lennox Industries Inc.

Dallas, Texas, USA

INSTALLATION

INSTRUCTIONS

EL195UH

ELITE ® SERIES GAS FURNACE

UPFLOW / HORIZONTAL AIR DISCHARGE

506596−01

03/2011

Supersedes 02/2011

Litho U.S.A.

THIS MANUAL MUST BE LEFT WITH THE

HOMEOWNER FOR FUTURE REFERENCE

This is a safety alert symbol and should never be ignored.

When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death.

CAUTION

As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.

AIR FLOW

UPFLOW

HORIZONTAL LEFT HORIZONTAL RIGHT

WARNING

Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.

Unit Dimensions

Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Use of Furnace as a Construction Heater . . . . . . . . . . .

General

Table of Contents

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

EL195UH Parts Arrangement

EL195UH Gas Furnace

. . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . .

Shipping and Packing List . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Combustion, Dilution, Ventilation Air . . . . . . . . . . . . . . .

2

3

4

4

4

5

6

6

Setting Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Duct System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

13

13

Pipe and Fittings Specifications

Joint Cementing Procedure

. . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . .

13

15

Venting Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Vent Piping Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . .

16

17

Gas Piping

Electrical

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

34

37

Unit Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Gas Pressure Measurement

Proper Combustion

. . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

40

42

42

High Altitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Other Unit Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . .

42

44

Blower Motor Performance

Service

. . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

45

47

Planned Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Integrated Control Diagnostic Codes . . . . . . . . . . . . . . .

49

49

Troubleshooting

Repair Parts List

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Start Up Checklist

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

50

53

54

03/11

*2P0311*

Page 1

506596−01

*P506596-01*

EL195UH Unit Dimensions − inches (mm)

1 NOTE − 60C size units that require air volumes

1800 cfm or over (850 L/s) must have one of the following

1. Single side return air with transition, to accommodate

20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter. Required to maintain proper air velocity.

2. Single side return air with optional Return Air Base

3. Bottom return air.

4. Return air from both sides.

5. Bottom and one side return air.

See Blower Performancetables for additional information.

2 Optional External Side Return Air Filter Kit is not for use with the optional Return Air Base.

3/4

(19)

A

B 9/16 (14)

1 − 7/8 (48)

3 − 1/4

(83)

D

COMBUSTION

AIR INTAKE

2 OPTIONAL

SIDE RETURN

AIR FILTER KIT

(Either Side)

1 − 1/2 (38)

Front Panel

EXHAUST AIR

OUTLET

SUPPLY AIR

OPENING

23 − 3/4

(603)

25

(635)

TOP VIEW

27 − 3/4

(705)

19 − 7/16

(494)

9/16

(14)

2 OPTIONAL

SIDE RETURN

AIR FILTER KIT

(Either Side)

33

(838)

6 − 9/16 (167)

Left

9 (229)

Right

12 − 5/8 (321)

(Either Side)

ELECTRICAL

INLET

(Either Side)

14 − 3/4

(375)

16

(406)

AIR FLOW

C

1 Bottom Return

Air Opening

FRONT VIEW

Model No.

EL195UH045P24B

EL195UH045P36B

EL195UH070P36B

EL195UH070P48B

EL195UH090P36C

EL195UH090P48C

EL195UH090P60C

EL195UH110P48C

EL195UH110P60C

EL195UH135P60D

3/4

(19)

5/8

(16) in.

A mm

17 − 1/2

21

24 − 1/2

446

533

622 in.

B mm

16 − 3/8

19 − 7/8

23 − 3/8

3 − 1/4

(83)

416

505

594

2 (51)

(Either Side)

GAS PIPING INLET

(Either Side)

CONDENSATE

TRAP CONNECTION

(Either Side)

6 − 1/2 (165)

(Either Side)

23

(584)

1 Side Return

Air Opening

(Either Side) in.

C mm

1

23 − 1/2

(597)

Bottom Return

Air Opening

SIDE VIEW

D in.

mm

16 406

19 − 1/2 495

23 584

7 − 5/8

9 − 3/8

11 − 1/8

14

(356)

1 − 15/16 (49)

194

238

283

1 − 1/2

(38)

Page 2

EL195UH Parts Arrangement

GAS VALVE

EL195UH PARTS IDENTIFICATION

BURNER BOX

ASSEMBLY

FLEXIBLE NO−HUB

EXHAUST COLLAR

TOP CAP

DuralokPlus TM

HEAT EXCHANGER

ASSEMBLY

COMBUSTION AIR

INDUCER

PRIMARY LIMIT

BAG ASSEMBLIES

(shipping location)

OUTER

COLD END

ACCESS

PANEL

HEADER BOX

COMBUSTION

AIR PRESSURE

SWITCH

BLOWER

ASSEMBLY

CONTROL BOX

(includes integrated ignition control, transformer and interlock switch)

FIGURE 1

Page 3

EL195UH Gas Furnace

The EL195UH Category IV gas furnace is shipped ready for installation in the upflow or horizontal position. The furnace is shipped with the bottom panel in place. The bottom panel must be removed if the unit is to be installed in horizontal or upflow applications with bottom return air.

The EL195UH can be installed as either a Direct Vent or a Non−Direct Vent gas central furnace.

The furnace is equipped for installation in natural gas applications. A conversion kit (ordered separately) is required for use in propane/LP gas applications.

NOTE − In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors. In

Non−Direct Vent installations, combustion air is taken from indoors and flue gases are discharged outdoors. See figure

2 for applications involving roof termination.

DIRECT VENT INSTALLATION

COMBUSTION

AIR INTAKE

OUTSIDE OF

HOUSE

EXHAUST

OUTLET

NON−DIRECT VENT

INSTALLATION

EXHAUST

OUTLET

EL195UH EL195UH

COMBUSTION

AIR INTAKE INSIDE

OF HOUSE

FIGURE 2

Shipping and Packing List

Package 1 of 1 contains

1 − Assembled EL195UH unit

1 − Bag assembly containing the following:

3 − Wire nuts

1 − Snap bushing

1 − Snap plug

1 − Wire tie

1 − Condensate trap

1 − Condensate trap cap

1 − Condensate trap clamp

1 − 2" diameter debris screen

Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.

The following items may also be ordered separately:

1 − Thermostat

1 − LP/Propane changeover kit

1 − Return air base kit

1 − Horizontal suspension kit

1 − High altitude pressure switch

Safety Information

WARNING

Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.

CAUTION

As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.

DANGER

Danger of explosion.

There are circumstances in which odorant used with

LP/propane gas can lose its scent. In case of a leak,

LP/propane gas will settle close to the floor and may be difficult to smell. An LP/propane leak detector should be installed in all LP applications.

Use only the type of gas approved for use with this furnace.

Refer to unit nameplate.

EL195UH units are CSA International certified to ANSI

Z21.47 and CSA 2.3 standards.

Building Codes

In the USA, installation of gas furnaces must conform with local building codes. In the absence of local codes, units must be installed according to the current National Fuel Gas Code

(ANSI-Z223.1/NFPA 54). The National Fuel Gas Code is available from the following address:

American National Standards Institute, Inc.

11 West 42nd Street

New York, NY 10036

In Canada, installation must conform with current National

Standard of Canada CSA-B149 Natural Gas and Propane

Installation Codes, local plumbing or waste water codes and other applicable local codes.

In order to ensure proper unit operation in non−direct vent applications, combustion and ventilation air supply must be provided according to the current National Fuel Gas Code or CSA-B149 standard.

Page 4

Installation Locations

This furnace is CSA International certified for installation clearances to combustible material as listed on the unit

nameplate and in the table in figure 10. Accessibility and ser-

vice clearances must take precedence over fire protection clearances.

NOTE − For installation on combustible floors, the furnace shall not be installed directly on carpeting, tile, or other combustible material other than wood flooring.

For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 18 inches (457 mm) above the floor. The furnace must be located or protected to avoid physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a hazardous atmosphere, the furnace must be installed according to recommended good practice requirements and current National Fuel Gas Code or CSA B149 standards.

NOTE − Furnace must be adjusted to obtain a temperature rise within the range specified on the unit nameplate. Failure to do so may cause erratic limit operation and premature heat exchanger failure.

This EL195UH furnace must be installed so that its electrical components are protected from water.

Installed in Combination with a Cooling Coil

When this furnace is used with cooling coils (figure 3), it shall

be installed in parallel with, or on the upstream side of, cooling coils to avoid condensation in the heating compartment.

With a parallel flow arrangement, a damper (or other means to control the flow of air) must adequately prevent chilled air from entering the furnace. If the damper is manually operated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full HEAT or

COOL setting.

When installed, this furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Electric

Code, ANSI/NFPA No. 70. The National Electric Code

(ANSI/NFPA No. 70) is available from the following address:

National Fire Protection Association

1 Battery March Park

Quincy, MA 02269

In Canada, all electrical wiring and grounding for the unit must be installed according to the current regulations of the

Canadian Electrical Code Part I (CSA Standard C22.1) and/or local codes.

Heating Unit Installed Parallel to Air Handler Unit

Dampers

(open during heating operation only)

Gas Unit

AIR FLOW

Air Handler Unit

Dampers

(open during cooling operation only)

AIR FLOW

Heating Unit Installed Upstream of Cooling Coil

AIR FLOW

Gas Unit

AIR FLOW

Cooling Coil

FIGURE 3

NOTE − This furnace is designed for a minimum continuous return air temperature of 60°F (16°C) or an intermittent operation down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air temperature must not exceed 85°F (29°C) dry bulb.

The EL195UH furnace may be installed in alcoves, closets, attics, basements, garages, crawl spaces and utility rooms in the upflow or horizontal position.

This furnace design has not been CSA certified for installation in mobile homes, recreational vehicles, or outdoors.

Use of Furnace as Construction Heater

Lennox does not recommend the use of EL195UH units as a construction heater during any phase of construction.

Very low return air temperatures, harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit.

EL195UH units may be used for heating of buildings or structures under construction, if the following conditions are met:

D The vent system must be permanently installed per these installation instructions.

D A room thermostat must control the furnace. The use of fixed jumpers that will provide continuous heating is not allowed.

D The return air duct must be provided and sealed to the furnace.

D Return air temperature range between 60°F (16°C) and

80°F (27°C) must be maintained.

Page 5

D Air filters must be installed in the system and must be maintained during construction.

D Air filters must be replaced upon construction completion.

D The input rate and temperature rise must be set per the furnace rating plate.

D One hundred percent (100%) outdoor air must be provided for combustion air requirements during construction. Temporary ducting may supply outdoor air to the furnace. Do not connect duct directly to the furnace.

Size the temporary duct following these instructions in section for Combustion, Dilution and Ventilation Air in a confined space with air from outside.

D The furnace heat exchanger, components, duct system, air filters and evaporator coils must be thoroughly cleaned following final construction clean−up.

D All furnace operating conditions (including ignition, input rate, temperature rise and venting) must be verified according to these installation instructions.

General

These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.

In addition to the requirements outlined previously, the following general recommendations must be considered when installing a EL195UH furnace:

Place the furnace as close to the center of the air distribution system as possible. The furnace should also be located close to the vent termination point.

When the furnace is installed in non−direct vent applications, do not install the furnace where drafts might blow directly into it. This could cause improper combustion and unsafe operation.

When the furnace is installed in non−direct vent applications, do not block the furnace combustion air opening with clothing, boxes, doors, etc. Air is needed for proper combustion and safe unit operation.

When the furnace is installed in an attic or other insulated space, keep insulation away from the furnace.

• When the furnace is installed in an unconditioned space, consider provisions required to prevent freezing of condensate drain system.

CAUTION

EL195UH unit should not be installed in areas normally subject to freezing temperatures.

WARNING

Product contains fiberglass wool.

Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)

Fiberglass wool may also cause respiratory, skin, and eye irritation.

To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.

Lennox Industries Inc.

P.O. Box 799900

Dallas, TX 75379−9900

WARNING

Insufficient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rusting and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following substances in the combustion air supply:

Permanent wave solutions

Chlorinated waxes and cleaners

Chlorine base swimming pool chemicals

Water softening chemicals

De−icing salts or chemicals

Carbon tetrachloride

Halogen type refrigerants

Cleaning solvents (such as perchloroethylene)

Printing inks, paint removers, varnishes, etc.

Hydrochloric acid

Cements and glues

Antistatic fabric softeners for clothes dryers

Masonry acid washing materials

Combustion, Dilution & Ventilation Air

If the EL195UH is installed as a Non−Direct Vent Furnace, follow the guidelines in this section.

NOTE − In Non−Direct Vent installations, combustion air is taken from indoors and flue gases are discharged out− doors.

In the past, there was no problem in bringing in sufficient outdoor air for combustion. Infiltration provided all the air that was needed. In today’s homes, tight construction practices make it necessary to bring in air from outside for combustion. Take into account that exhaust fans, appliance vents, chimneys, and fireplaces force additional air that could be used for combustion out of the house.

Unless outside air is brought into the house for combus-

Page 6

tion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a downdraft can occur in the furnace vent pipe or chimney. As a result, combustion gases enter the living space creating a potentially dangerous situation.

In the absence of local codes concerning air for combus− tion and ventilation, use the guidelines and procedures in this section to install EL195UH furnaces to ensure efficient and safe operation. You must consider combustion air needs and requirements for exhaust vents and gas piping. A portion of this information has been reprinted with permission from the National Fuel Gas Code (ANSI−

Z223.1/NFPA 54). This reprinted material is not the complete and official position of the ANSI on the referenced subject, which is represented only by the standard in its entirety.

In Canada, refer to the CSA B149 installation codes.

CAUTION

Do not install the furnace in a corrosive or contaminated atmosphere. Meet all combustion and ventilation air requirements, as well as all local codes.

All gas-fired appliances require air for the combustion process. If sufficient combustion air is not available, the furnace or other appliance will operate inefficiently and unsafely. Enough air must be provided to meet the needs of all fuel−burning appliances and appliances such as exhaust fans which force air out of the house. When fireplaces, exhaust fans, or clothes dryers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a downdraft. Insufficient air causes incomplete combustion which can result in carbon monoxide.

In addition to providing combustion air, fresh outdoor air dilutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace components.

The requirements for providing air for combustion and ventilation depend largely on whether the furnace is installed in an unconfined or a confined space.

Unconfined Space

An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.42 m

3

) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space.

This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be unconfined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures in the Air from Outside section.

Confined Space

A confined space is an area with a volume less than 50 cubic feet (1.42 m

3

) per 1,000 Btu (.29 kW) per hour of the com− bined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.

When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room.

Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space either from inside the building or from outside.

Air from Inside

If the confined space that houses the furnace adjoins a space categorized as unconfined, air can be brought in by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (645 mm 2 ) per 1,000 Btu (.29 kW) per hour of total input rating of all gas−fired equipment in the confined space. Each opening must be at least 100 square inches

(64516 mm 2 ). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12

inches (305 mm) of the bottom. See figure 4.

EQUIPMENT IN CONFINED SPACE − ALL AIR FROM INSIDE

ROOF TERMINATED

EXHAUST PIPE

SIDE WALL

TERMINATED

EXHAUST PIPE

(ALTERNATE

LOCATION)

EL195UH

OPENINGS

(To Adjacent

Unconfined

Space)

NOTE − Each opening shall have a free area of at least one square inch per 1,000 Btu (645mm 2 per .29kW) per hour of the total input rating of all equipment in the enclosure, but not less than 100 square inches

(64516mm.

2).

FIGURE 4

Page 7

Air from Outside

If air from outside is brought in for combustion and ventilation, the confined space shall be provided with two permanent openings. One opening shall be within 12" (305mm) of the top of the enclosure and one within 12" (305mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch per 4,000 Btu (645mm 2 per 1.17kW) per hour of total input rating of all equipment in the enclosure. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 Btu (645mm

2 per .59kW) per total input rating of all equipment in the en-

closure (See figure 5).

EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE

(Inlet Air from Crawl Space and Outlet Air to Ventilated Attic)

VENTILATION LOUVERS

(Each end of attic)

ROOF TERMINATED

EXHAUST PIPE

When ducts are used, they shall be of the same cross−sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protective covering is not known for calculating the size opening required, it may be assumed that wood louvers will have

20 to 25 percent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.

EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE

(All Air Through Ventilated Attic)

ROOF TERMINATED

EXHAUST PIPE

OUTLET

AIR

VENTILATION LOUVERS

(Each end of attic)

SIDE WALL

TERMINATED

EXHAUST PIPE

(ALTERNATE

LOCATION)

FURNACE

INLET

AIR

OUTLET

AIR

VENTILATION

LOUVERS

(For unheated crawl space)

NOTE −The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm 2 per 1.17kW) per hour of the total input rating of all equipment in the enclosure.

FIGURE 5

If air from outside is brought in for combustion and ventilation, the confined space must have two permanent openings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches

(305 mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (645 mm 2 ) per 4,000

Btu (1.17 kW) per hour of total input rating of all equipment

in the enclosure. See figures 5 and 6. When communicat-

ing with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (645 mm 2 ) per 2,000 Btu (.56 kW) per total input rating of all equipment in the enclosure. See

figure 7.

SIDE WALL

TERMINATED

EXHAUST PIPE

(ALTERNATE

LOCATION)

FURNACE

INLET AIR

(Ends 12" above bottom)

NOTE −The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm 2 per 1.17kW) per hour of the total input rating of all equipment in the enclosure.

FIGURE 6

EQUIPMENT IN CONFINED SPACE −

ALL AIR FROM OUTSIDE

ROOF TERMINATED

EXHAUST PIPE

FURNACE

OUTLET AIR

SIDE WALL

TERMINATED

EXHAUST PIPE

(ALTERNATE

LOCATION)

INLET AIR

NOTE −Each air duct opening shall have a free area of at least one square inch per 2,000 Btu (645mm 2 per .59kW) per hour of the total input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings communicate directly with the outdoors, each opening shall have a free area of at least 1 square inch per 4,000 Btu (645mm 2 per 1.17kW) per hour of the total input rating of all other equipment in the enclosure.

FIGURE 7

Page 8

Shipping Bolt Removal

Units with 1/2 hp blower motor are equipped with three flexible legs and one rigid leg. The rigid leg is equipped with a shipping bolt and a flat white plastic washer (rather than the rubber mounting grommet used with a flexible mounting

leg). See figure 8.

The bolt and washer must be removed before the furnace is placed into operation.

After the bolt and washer have been removed, the rigid leg will not touch the blower housing.

EL195UH090P48C

EL195UH110P48C with 1/2 HP Blower Motor

RIGID LEG

(Remove shipping bolt and washer)

FIGURE 8

Installation − Setting Equipment

WARNING

Do not connect the return air duct to the back of the furnace. Doing so will adversely affect the operation of the safety control devices, which could result in personal injury or death.

WARNING

Blower access panel must be securely in place when blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.

Upflow Applications

The EL195UH gas furnace can be installed as shipped

in the upflow position. Refer to figure 10 for clearances.

Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, condensate trap and drain connections, and installation and service clearances [24 inches (610 mm) at unit front]. The unit must be level from side to side. The unit may be positioned from level to ½" toward the front. See

figure 9.

Allow for clearances to combustible materials as indicated on the unit nameplate.

SETTING EQUIPMENT

UPFLOW APPLICATION

AIR FLOW

FRONT VIEW

UNIT

FRONT

AIR FLOW

SIDE VIEW

HORIZONTAL APPLICATION

1/2" max.

UNIT

FRONT

SIDE VIEW

UNIT

FRONT

AIR FLOW

1/2" max.

END VIEW

FRONT VIEW

Unit must be level side−to−side. Unit may be positioned from level to 1/2" toward the front to aid in draining.

FIGURE 9

Page 9

WARNING

Improper installation of the furnace can result in personal injury or death. Combustion and flue products must never be allowed to enter the return air system or air in the living space. Use sheet metal screws and joint tape to seal return air system to furnace.

In platform installations with furnace return, the furnace should be sealed airtight to the return air plenum. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Allow absolutely no sagging, cracks, gaps, etc.

For no reason should return and supply air duct systems ever be connected to or from other heating devices such as a fireplace or stove, etc. Fire, explosion, carbon monoxide poisoning, personal injury and/or property damage could result.

Installation Clearances

Top

Return Air Guidelines

Return air can be brought in through the bottom or either side of the furnace installed in an upflow application. If the furnace is installed on a platform with bottom return, make an airtight seal between the bottom of the furnace and the platform to ensure that the furnace operates properly and safely. The furnace is equipped with a removable bottom panel to facilitate installation.

Markings are provided on both sides of the furnace cabinet for installations that require side return air. Cut the furnace cabinet at the maximum dimensions shown on page 2.

Refer to Engineering Handbook for additional information.

EL195UH applications which include side return air and a condensate trap installed on the same side of the cabinet (trap can be installed remotely within 5 ft.) require either a return air base or field−fabricated transition to accommodate an optional IAQ accessory taller

than 14.5". See figure 11.

Left Side Right Side

Side Return Air

(with transition and filter)

20" X 25" X 1"

(508mm X635mm X 25mm)

1−1/2 in.

Air Filter Bottom (Floor)

Top/Plenum

*Front

Back

Sides

Vent

1 in. (25 mm)

0

0

0 †

0

Floor 0 ‡

*Front clearance in alcove installation must be 24 in. (610 mm).

Maintain a minimum of 24 in. (610 mm) for front service access.

† Allow proper clearances to accommodate condensate trap.

‡ For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.

FIGURE 10

Return

Air

Plenum

Transition

FIGURE 11

Page 10

FURNACE

FRONT

Optional Return Air Base

(Upflow Applications Only)

AIR FLOW

INDOOR AIR

QUALITY

CABINET

(PCO, Filter

Cabinet, etc.)

IF BASE

IS USED

WITHOUT

IAQ CABINET,

A SINGLE

RETURN AIR

PLENUM

MUST

COVER BOTH

UNIT AND

RETURN

AIR BASE

OPENINGS

3 − 1/4

(83)

1 23 (584)

Overall

(Maximum)

1 Unit side return air

Opening

1 Minimum

11 (279)

2 Maximum

14 (356)

1 22 − 7/16

(570)

Overall

(Maximum)

7 − 1/4

(184)

5 − 5/8

(143)

SIDE RETURN

AIR OPENINGS

(Either Side)

17 − 1/2 (446) B Width (50W98)

21 (533) C Width (50W99)

24 − 1/2 (622) D Width (51W00)

FRONT VIEW

OPTIONAL

RETURN

AIR BASE

23

(584)

26 − 7/8

(683)

SIDE VIEW

3/4

(19)

NOTE− Optional side return air filter kits are not for use with return air base.

1 Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.

Minimum unit side return air opening dimensions for units requiring 1800 cfm of air and over (W x H): 23 x 11 in. (584 x 279 mm).

2

The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.

Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air opening. The size of the opening must not extend beyond the markings on the furnace cabinet.

To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.

Removing the Bottom Panel

FIGURE 12

Removing the Bottom Panel

Remove the two screws that secure the bottom cap to the furnace. Pivot the bottom cap down to release the bottom panel. Once the bottom panel has been removed, reinstall

the bottom cap. See figure 13.

Horizontal Applications

WARNING

Do not install the furnace on its front or back.

See figure 14.

Screw

Bottom Cap

Bottom Panel

Front Back

FIGURE 13

FIGURE 14

Page 11

The EL195UH furnace can be installed in horizontal applications with either right− or left−hand air discharge.

Refer to figure 15 for clearances in horizontal applications.

Horizontal Application

Installation Clearances

Right−Hand Discharge

Left End Right End

Air

Flow

Air

Flow

Bottom (Floor)**

Left−Hand Discharge

Top

Left End Right End

NOTE − Heavy−gauge sheet metal straps may be used to suspend the unit from roof rafters or ceiling joists. When straps are used to suspend the unit in this way, support must be provided for both the ends. The straps must not interfere with the plenum or exhaust piping installation.

Cooling coils and supply and return air plenums must be supported separately.

TYPICAL HORIZONTAL APPLICATION

Metal Strap

(typical)

Internal Brace

(provided with kit)

Bracket

(typical)

Air

Flow

Air

Flow

Bottom (Floor)**

Top

Front*

Back

Ends

Vent

Floor

0

0

0

0

0

0 ‡

*Front clearance in alcove installation must be 24 in. (610 mm).

Maintain a minimum of 24 in. (610 mm) for front service access.

**An 8" service clearance must be maintained below the unit to provide for servicing of the condensate trap.

‡ For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.

FIGURE 15

Suspended Installation of Horizontal Unit

This furnace may be installed in either an attic or a crawlspace. Either suspend the furnace from roof rafters or

floor joists, as shown in figure 16, or install the furnace on a

platform, as shown in figure 17. A horizontal suspension

kit (51W10) may be ordered from Lennox or use equivalent.

FIGURE 16

Air

Flow the horizontal suspension kit in a crawlspace, it must be elevated enough to avoid water damage, accommodate drain trap and to allow the evaporator coil to drain.

Platform Installation of Horizontal Unit

1 − Select location for unit keeping in mind service and

other necessary clearances. See figure 15.

2 − Construct a raised wooden frame and cover frame with a plywood sheet. If unit is installed above finished space, fabricate an auxiliary drain pan to be installed

under unit. Set unit in drain pan as shown in figure 17.

Leave 8 inches for service clearance below unit for condensate trap.

3 − Provide a service platform in front of unit. When installing the unit in a crawl space, a proper support platform may be created using cement blocks.

4 − Route auxiliary drain line so that water draining from this outlet will be easily noticed by the homeowner.

Page 12

5 − If necessary, run the condensate line into a condensate pump to meet drain line slope requirements. The pump must be rated for use with condensing furnaces.

Protect the condensate discharge line from the pump to the outside to avoid freezing.

6 − Continue with exhaust, condensate and intake piping installation according to instructions.

INTAKE PIPE

EXHAUST PIPE

*GAS

CONNECTOR

*Gas connector may be used for Canadian installation if acceptable by local authority having jurisdiction.

RAISED

PLATFORM

SERVICE PLATFORM

FIGURE 17

Return Air −− Horizontal Applications

Return air may be brought in only through the end of a furnace installed in the horizontal position. The furnace is equipped with a removable bottom panel to facilitate

installation. See figure 13.

Filters

This unit is not equipped with a filter or rack. A field−provided high velocity rated filter is required for the unit to oper-

ate properly. Table 1 lists recommended filter sizes.

A filter must be in place whenever the unit is operating.

TABLE 1

Furnace

Cabinet Width

17−1/2"

21"

24−1/2"

Side Return

16 X 25 X 1 (1)

16 X 25 X 1 (1)

16 X 25 X 1 (2)

Filter Size

Bottom Return

16 X 25 X 1 (1)

20 X 25 X 1 (1)

24 X 25 X 1 (1)

Duct System

Use industry-approved standards to size and install the supply and return air duct system. Refer to ACCA Manual

D. This will result in a quiet and low-static system that has uniform air distribution.

NOTE − This furnace is not certified for operation in heating mode (indoor blower operating at selected heating speed) with an external static pressure which exceeds 0.5 inches w.c. Operation at these conditions may result in improper limit operation.

Supply Air Plenum

If the furnace is installed without a cooling coil, a removable access panel should be installed in the supply air duct. The access panel should be large enough to permit inspection of the heat exchanger. The furnace access panel must always be in place when the furnace is operating and it must not allow leaks.

Return Air Plenum

NOTE − Return air must not be drawn from a room where this furnace, or any other gas−fueled appliance

(i.e., water heater), or carbon monoxide−producing device (i.e., wood fireplace) is installed.

When return air is drawn from a room, a negative pressure is created in the room. If a gas appliance is operating in a room with negative pressure, the flue products can be pulled back down the vent pipe and into the room. This reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas. This raw gas or toxic fumes might then be distributed throughout the house by the furnace duct system.

Return air can be brought in through the bottom or either side of the furnace. If a furnace with bottom return air is installed on a platform, make an airtight seal between the bottom of the furnace and the platform to ensure that the unit operates properly and safely. Use fiberglass sealing strips, caulking, or equivalent sealing method between the plenum and the furnace cabinet to ensure a tight seal. If a filter is installed, size the return air duct to fit the filter frame.

Pipe & Fittings Specifications

All pipe, fittings, primer and solvent cement must conform with American National Standard Institute and the American Society for Testing and Materials (ANSI/ASTM) standards. The solvent shall be free flowing and contain no lumps, undissolved particles or any foreign matter that adversely affects the joint strength or chemical resistance of the cement. The cement shall show no gelation, stratification, or separation that cannot be removed by stirring. Re-

fer to the table 2 below for approved piping and fitting ma-

terials.

Page 13

CAUTION

Solvent cements for plastic pipe are flammable liquids and should be kept away from all sources of ignition. Do not use excessive amounts of solvent cement when making joints. Good ventilation should be maintained to reduce fire hazard and to minimize breathing of solvent vapors. Avoid contact of cement with skin and eyes.

TABLE 2

PIPING AND FITTINGS SPECIFICATIONS

Schedule 40 PVC (Pipe)

Schedule 40 PVC (Cellular Core Pipe)

Schedule 40 PVC (Fittings)

D1785

F891

D2466

Schedule 40 CPVC (Pipe)

Schedule 40 CPVC (Fittings)

SDR−21 PVC or SDR−26 PVC (Pipe)

SDR−21 CPVC or SDR−26 CPVC (Pipe)

Schedule 40 ABS Cellular Core DWV (Pipe)

Schedule 40 ABS (Pipe)

Schedule 40 ABS (Fittings)

ABS−DWV (Drain Waste & Vent)

(Pipe & Fittings)

PVC−DWV (Drain Waste & Vent)

Pipe & Fittings)

F441

F438

D2241

F442

F628

D1527

D2468

D2661

D2665

PRIMER & SOLVENT CEMENT

ASTM

SPECIFICATION

PVC & CPVC Primer

PVC Solvent Cement

CPVC Solvent Cement

ABS Solvent Cement

PVC/CPVC/ABS All Purpose Cement For

Fittings & Pipe of the same material

ABS to PVC or CPVC Transition Solvent

Cement

CANADA PIPE & FITTING & SOLVENT

CEMENT

PVC & CPVC Pipe and Fittings

PVC & CPVC Solvent Cement

ABS to PVC or CPVC Transition Cement

F656

D2564

F493

D2235

D2564, D2235, F493

D3138

MARKING

ULCS636

IMPORTANT

EL195UH exhaust and intake connections are made of PVC. Use PVC primer and solvent cement when using PVC vent pipe. When using ABS vent pipe, use transitional solvent cement to make connections to the PVC fittings in the unit.

Use PVC primer and solvent cement or ABS solvent cement

meeting ASTM specifications, refer to Table 2. As an alter-

nate, use all purpose cement, to bond ABS, PVC, or CPVC pipe when using fittings and pipe made of the same materials. Use transition solvent cement when bonding ABS to either PVC or CPVC.

Low temperature solvent cement is recommended during cooler weather. Metal or plastic strapping may be used for vent pipe hangers. Uniformly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean inside socket surface of fitting and male end of pipe to depth of fitting socket.

Canadian Applications Only − Pipe, fittings, primer and solvent cement used to vent (exhaust) this appliance must be certified to ULC S636 and supplied by a single manufacturer as part of an approved vent (exhaust) system. In addition, the first three feet of vent pipe from the furnace flue collar must be accessible for inspection.

Page 14

EL195

UNIT

VENT

PIPE

DIA.

(in.)

2

Outdoor

Exhaust

Accelerator

(Dia. X

Length)

1−1/2" X 12"

YES

TABLE 3

OUTDOOR TERMINATION KITS USAGE

STANDARD

Outdoor

Exhaust

Accelerator

(Dia. X

Length)

2" Wall Plate

Kit

3" Wall Plate

Kit

2" Wall

Ring Kit

Flush-

Mount

Kit

2" X 12"

22G44 or 30G28

44J40 or 81J20

15F74 51W11**

YES YES* YES YES

71M80 or

44W92

YES

CONCENTRIC

1−1/2"

Concentric

Kit

2"

Concentric

Kit

3"

Concentric

Kit

69M29 or

44W92

60L46 or 44W93

045 2−1/2

3

2

YES

YES

YES

YES

YES

YES

YES*

YES*

YES*

YES

YES

YES

YES

YES

YES

YES

YES

YES

2−1/2 YES YES YES* YES YES YES 070

090

110

3

2

2−1/2

3

2

2−1/2

3

YES

YES

YES

YES

YES

YES

YES

YES YES*

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

135 3 YES YES YES YES

*Requires field−provided and installed 1−1/2" exhaust accelerator.

** Kit 51W11 is provided with a 1−1/2" accelerator which must be used for all EL195UH−045, −070 and −090 installations.

Termination kits 44W92, 44W93, 30G28 and 81J20 approved for use in Canadian installations to meet CSAB149.

The 44W92 concentric kit is provided with a 1−1/2" accelerator which must be installed on the exhaust outlet when this kit is used with theEL195UH045P24B and

EL195UH070P36B furnaces.

4 − Test fit joint and mark depth of fitting on outside of pipe.

Joint Cementing Procedure

All cementing of joints should be done according to the specifications outlined in ASTM D 2855.

5 − Uniformly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean inside socket surface of fitting and male end of pipe to depth of fitting socket.

DANGER

DANGER OF EXPLOSION!

Fumes from PVC glue may ignite during system check. Allow fumes to dissipate for at least 5 minutes before placing unit into operation.

NOTE − Time is critical at this stage. Do not allow primer to dry before applying cement.

6 − Promptly apply solvent cement to end of pipe and inside socket surface of fitting. Cement should be applied lightly but uniformly to inside of socket. Take care to keep excess cement out of socket. Apply second coat to end of pipe.

1 − Measure and cut vent pipe to desired length.

2 − Debur and chamfer end of pipe, removing any ridges or rough edges. If end is not chamfered, edge of pipe may remove cement from fitting socket and result in a leaking joint.

NOTE − Check the inside of vent pipe thoroughly for any obstruction that may alter furnace operation.

3 − Clean and dry surfaces to be joined.

7 − Immediately after applying last coat of cement to pipe, and while both inside socket surface and end of pipe are wet with cement, forcefully insert end of pipe into socket until it bottoms out. Turn PVC pipe 1/4 turn during assembly (but not after pipe is fully inserted) to distribute cement evenly. DO NOT turn ABS or cellular core pipe.

Page 15

NOTE − Assembly should be completed within 20 seconds after last application of cement. Hammer blows should not be used when inserting pipe.

8 − After assembly, wipe excess cement from pipe at end of fitting socket. A properly made joint will show a bead around its entire perimeter. Any gaps may indicate an improper assembly due to insufficient solvent.

9 − Handle joints carefully until completely set.

Venting Practices

CHIMNEY

OR GAS

VENT

(Check sizing for water heater only)

FURNACE

(Replaced by EL195)

REPLACING FURNACE THAT

WAS PART OF A COMMON

VENT SYSTEM

WATER

HEATER

OPENINGS

(To Adjacent

Room)

Piping Suspension Guidelines

SCHEDULE 40

PVC − 5’ all other pipe* − 3’

* See table 2 for allowable pipe.

NOTE − Isolate piping at the point where it exits the outside wall or roof in order to prevent transmission of vibration to the structure.

Wall Thickness Guidelines

24" maximum

3/4" minimum inside

Wall outside

If an EL195UH furnace replaces a furnace which was commonly vented with another gas appliance, the size of the existing vent pipe for that gas appliance must be checked. Without the heat of the original furnace flue products, the existing vent pipe is probably oversized for the single water heater or other appliance. The vent should be checked for proper draw with the remaining appliance.

FIGURE 19 insulation

(if required)

FIGURE 18

1 − In areas where piping penetrates joists or interior walls, hole must be large enough to allow clearance on all sides of pipe through center of hole using a hanger.

2 − When furnace is installed in a residence where unit is shut down for an extended period of time, such as a vacation home, make provisions for draining condensate collection trap and lines.

Exhaust Piping (Figures 22 and 23)

Route piping to outside of structure. Continue with installation following instructions given in piping termination section.

CAUTION

Do not discharge exhaust into an existing stack or stack that also serves another gas appliance. If vertical discharge through an existing unused stack is required, insert PVC pipe inside the stack until the end is even with the top or outlet end of the metal stack.

CAUTION

The exhaust vent pipe operates under positive pressure and must be completely sealed to prevent leakage of combustion products into the living space.

Page 16

Vent Piping Guidelines

The EL195UH can be installed as either a Non−Direct

Vent or a Direct Vent gas central furnace.

NOTE − In Non-Direct Vent installations, combustion air is taken from indoors and flue gases are discharged outdoors.

In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors.

Intake and exhaust pipe sizing −− Size pipe according to

tables 4 and 5

. Table 4 lists the

minimum vent pipe lengths permitted. Table

5

lists the maximum pipe lengths permitted.

Regardless of the diameter of pipe used, the standard roof and wall terminations described in section Exhaust Piping

Terminations should be used. Exhaust vent termination pipe is sized to optimize the velocity of the exhaust gas as

it exits the termination. Refer to table 6.

In some applications which permit the use of several different sizes of vent pipe, a combination vent pipe may be used. Contact Lennox’ Application Department for assistance in sizing vent pipe in these applications.

NOTE − The exhaust collar on all models is sized to accommodate 2" Schedule 40 vent pipe. In horizontal applications, any transition to exhaust pipe larger than 2" must be made in vertical runs of the pipe. Therefore a 2" elbow must be added before the pipe is transitioned to any size larger than 2". This elbow must be added to the elbow count used to determine acceptable vent lengths.

Contact the Application Department for more information concerning sizing of vent systems which include multiple pipe sizes.

Exhaust Pipe

12" Min.

12" max of straight pipe

Use the following steps to correctly size vent pipe diameter.

1

Furnace capacity?

2

Which termination?

3

4

Which needs most elbows?

How many?

5

Desired pipe size?

045, 070,

090, 110 or 135 btuh

Standard or

Concentric?

See table 3

Intake or exhaust

2", 2 1/2",

3" or 4"

6

What is the altitude?

Horizontal Application

NOTE − All horizontal runs of exhaust pipe must slope back toward unit. A minimum of 1/4" (6mm) drop for each 12" (305mm) of horizontal run is mandatory for drainage.

NOTE − Exhaust pipe MUST be glued to furnace exhaust fittings.

NOTE − Exhaust piping should be checked carefully to make sure there are no sags or low spots.

EL195UH

MODEL

FIGURE 20

TABLE 4

MINIMUM VENT PIPE LENGTHS

MIN. VENT LENGTH*

045, 070, 090, 110, 135

15 ft. or

5 ft. plus 2 elbows or

10 ft. plus 1 elbow

*Any approved termination may be added to the minimum length listed.

7

Use table 5 to find max intake or exhaust pipe length.

FIGURE 21

IMPORTANT

Do not use screens or perforated metal in exhaust or intake terminations. Doing so will cause freeze−ups and may block the terminations.

Page 17

TABLE 5

Maximum Allowable Intake or Exhaust Vent Length in Feet

*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.

Number Of

90° Elbows

Used

8

9

6

7

10

3

4

1

2

5

Number Of

90° Elbows

Used

6

7

4

5

8

1

2

3

9

10

71

66

61

045

81

76

56

51

46

41

36

66

61

56

51

46

045

81

76

71

41

36

51

46

41

36

31

070

66

61

56

26

21

2" Pipe

Model

090

44

39

34

29

24

19

14 n/a

56

51

46

070

66

61

41

36

31

26

21

2" Pipe

Model

090

44

39

34

29

24

19

14 n/a

110

24

19

14 n/a

Standard Termination at Elevation 0 − 4500 ft

135 045 070

2−1/2" Pipe

Model

090 110 135

115

110

105

100

95

115

110

105

100

95

93

88

83

78

73

58

53

48

43

38 n/a n/a

90

85

80

75

90

85

80

75

68

63

58

53

33

28

23

18

110

70 70 48 13

Standard Termination Elevation 4500 − 10,000 ft

135 045 070

2−1/2" Pipe

Model

090 110 135

115

110

105

115

110

105

93

88

83

58

53

48 n/a n/a

100

95

90

85

80

75

70

100

95

90

85

80

75

70

78

73

68

63

58

53

48

43

38

33

28

23

18

13 n/a

070

137

132

127

122

117

112

107

102

97

92

045

138

133

128

123

118

113

108

103

98

93

122

117

112

107

102

070

137

132

127

97

92

123

118

113

108

103

045

138

133

128

98

93

103

98

93

88

83

78

73

3" Pipe

Model

090

118

113

108

3" Pipe

Model

090

118

113

108

103

98

93

88

83

78

73

135

114

109

104

99

94

89

84

79

74

69

110

118

113

108

103

98

93

88

83

78

73

99

94

89

84

79

135

114

109

104

74

69

103

98

93

88

83

110

118

113

108

78

73

Page 18

TABLE 5 Continued

Maximum Allowable Intake or Exhaust Vent Length in Feet

*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.

Number Of

90° Elbows

Used

6

7

4

5

8

1

2

3

9

10

Number Of

90° Elbows

Used

5

6

3

4

7

1

2

8

9

10

070

43

38

33

28

23

58

53

48

18

13

045

58

53

48

43

38

73

68

63

33

28

23

18

13

38

33

28

070

58

53

48

43

38

33

28

53

48

43

045

73

68

63

58

2" Pipe

Model

090

27

22

17

12

42

37

32 n/a

2" Pipe

Model

090

42

37

32

27

22

17

12 n/a

Concentric Termination at Elevation 0 − 4500 ft

2−1/2" Pipe

110 135 045 070

Model

090 110 135

22

17

12 n/a n/a

90

85

80

75

70

105

100

95

105

100

95

90

85

80

75

70

89

84

79

74

69

64

59

54

54

49

44

39

34

29

24

19 n/a

65

60

65

60

49

44

14 n/a

Concentric Termination Elevation 4501 − 10,000 ft

2−1/2" Pipe

Model

110 n/a

135 n/a

70

65

60

85

80

75

045

105

100

95

90

70

65

60

85

80

75

070

105

100

95

90

54

49

44

69

64

59

090

89

84

79

74

19

14 n/a

34

29

24

110

54

49

44

39

135 n/a

045

121

116

111

106

101

96

91

86

81

76

101

96

91

86

81

76

045

121

116

111

106

070

121

116

111

106

101

96

91

86

81

76

3" Pipe

Model

090

99

94

89

84

79

114

109

104

74

69

101

96

91

86

81

76

070

121

116

111

106

3" Pipe

Model

79

74

69

94

89

84

090

114

109

104

99

135

90

85

80

75

70

105

100

95

65

60

110

99

94

89

84

79

114

109

104

74

69

70

65

60

85

80

75

135

105

100

95

90

79

74

69

94

89

84

110

114

109

104

99

Page 19

TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN UPFLOW DIRECT OR

NON−DIRECT VENT APPLICATIONS

EXHAUST INTAKE EXHAUST INTAKE

2”

2” or

2”

3”

2” 2”

3”

TRANSITION

*2” *2”

TRANSITION

DO NOT transition from smaller to larger pipe in horizontal runs of exhaust pipe .

2”

* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.

FIGURE 22

TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN HORIZONTAL DIRECT OR NON−DIRECT VENT

APPLICATIONS (RIGHT HAND DISCHARGE SHOWN)

EXHAUST

12" max.

2”

2”

2” or

2”

2”

2”

2”

2” or

2”

2”

*2”

45°

MAX

SIDE VIEW

45°

MAX

INTAKE

3”

EXHAUST

*2"

*2"

TRANSITION

3”

DO NOT transition from smaller to larger pipe in horizontal runs of exhaust pipe .

*2"

*2"

INTAKE

* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.

FIGURE 23

Page 20

Intake Piping

The EL195UH furnace may be installed in either direct vent or non−direct vent applications. In non−direct vent applications, when intake air will be drawn into the furnace from the surrounding space, the indoor air quality must be considered and guidelines listed in Combustion, Dilution and Ventilation Air section must be followed.

Follow the next two steps when installing the unit in Direct

Vent applications, where combustion air is taken from outdoors and flue gases are discharged outdoors. The provided air intake screen must not be used in direct vent applications (outdoors).

1 − Use transition solvent cement or a sheet metal screw to secure the intake pipe to the inlet air connector.

2 − Route piping to outside of structure. Continue with installation following instructions given in general guidelines for piping terminations and intake and exhaust piping terminations for direct vent sections. Refer to table

5

for pipe sizes.

TYPICAL AIR INTAKE PIPE CONNECTIONS

UPFLOW NON − DIRECT

VENT APPLICATIONS

INTAKE

DEBRIS

SCREEN

(Provided)

TYPICAL AIR INTAKE PIPE CONNECTIONS

HORIZONTAL NON − DIRECT VENT APPLICATIONS

(Horizontal Right − Hand Air Discharge Application Shown)

PVC pipe coupling

OR

INTAKE

DEBRIS

SCREEN

(Provided)

NOTE − Debris screen may be positioned straight out

(preferred) or with an elbow rotated to face down.

FIGURE 25

Follow the next two steps when installing the unit in Non-

Direct Vent applications where combustion air is taken from indoors and flue gases are discharged outdoors .

1 − Use field−provided materials and the factory−provided air intake screen to route the intake piping as shown in

figure 24 or 25. Maintain a minimum clearance of 3"

(76mm) around the air intake opening. The air intake opening (with the protective screen) should always be directed forward or to either side in the upflow position, and either straight out or downward in the horizontal position.

The air intake piping must not terminate too close to the flooring or a platform. Ensure that the intake air inlet will not be obstructed by loose insulation or other items that may clog the debris screen.

2 − Use a sheet metal screw to secure the intake pipe to the connector, if desired.

NOTE − Debris screen and elbow may be rotated, so that screen may be positioned to face forward or to either side.

FIGURE 24

Page 21

General Guidelines for Vent Terminations

In Non-Direct Vent applications, combustion air is taken from indoors and the flue gases are discharged to the outdoors. The EL195UH is then classified as a non-direct vent, Category IV gas furnace.

In Direct Vent applications, combustion air is taken from outdoors and the flue gases are discharged to the outdoors. The EL195UH is then classified as a direct vent,

Category IV gas furnace.

In both Non-Direct Vent and Direct Vent applications, the vent termination is limited by local building codes. In the absence of local codes, refer to the current National Fuel

Gas Code ANSI Z223−1/NFPA 54 in U.S.A., and current

CSA−B149 Natural Gas and Propane Installation Codes in

Canada for details.

Position termination according to location given in figure 26

or 27. In addition, position termination so it is free from any

obstructions and 12" above the average snow accumulation.

At vent termination, care must be taken to maintain protective coatings over building materials (prolonged exposure to exhaust condensate can destroy protective coatings). It is recommended that the exhaust outlet not be located within 6 feet (1.8m) of a condensing unit because the condensate can damage the painted coating.

NOTE − If winter design temperature is below 32°F (0°C), exhaust piping should be insulated with 1/2" (13mm), Armaflex or equivalent when run through unheated space.

Do not leave any surface area of exhaust pipe open to outside air; exterior exhaust pipe should be insulated with

1/2" (13mm) Armaflex or equivalent. In extreme cold climate areas, 3/4" (19mm) Armaflex or equivalent may be necessary. Insulation on outside runs of exhaust pipe must be painted or wrapped to protect insulation from deterioration. Exhaust pipe insulation may not be necessary in some specific applications.

NOTE − During extremely cold temperatures, below approximately 20°F (6.7°C), units with long runs of vent pipe through unconditioned space, even when insulated, may form ice in the exhaust termination that prevents the unit from operating properly. Longer run times of at least 5 minutes will alleviate most icing problems. Also, a heating cable may be installed on exhaust piping and termination to prevent freeze−ups. Heating cable installation kit is available from Lennox. See Condensate Piping section for part numbers.

IMPORTANT

Do not use screens or perforated metal in exhaust terminations. Doing so will cause freeze−ups and may block the terminations.

IMPORTANT

For Canadian Installations Only:

In accordance to CSA International B149 installation codes, the minimum allowed distance between the combustion air intake inlet and the exhaust outlet of other appliances shall not be less than 12 inches

(305mm).

Page 22

D

E

VENT TERMINATION CLEARANCES

FOR NON−DIRECT VENT INSTALLATIONS IN THE USA AND CANADA

INSIDE CORNER

DETAIL

G

H

A

B

L

F

C

Fixed

Closed

Operable

B

Operable

B

Fixed

Closed

I

M

B

K

J

A

B

A =

B =

VENT TERMINAL

Clearance above grade, veranda, porch, deck or balcony

Clearance to window or door that may be opened

AIR SUPPLY INLET

US Installations 1

12 inches (305mm) or 12 in. 305mm) above average snow accumulation.

AREA WHERE TERMINAL

IS NOT PERMITTED

Canadian Installations 2

12 inches (305mm) or 12 in. 305mm) above average snow accumulation.

4 feet (1.2 m) below or to side of opening;

1 foot (30 cm) above opening

* 12"

6 inches (152mm) for appliances <10,000

Btuh (3kw), 12 inches (305mm) for appliances > 10,000 Btuh (3kw) and

<100,000 Btuh (30kw), 36 inches (.9m) for appliances > 100,000 Btuh (30kw)

* 12"

C = Clearance to permanently closed window

D =

E =

F =

G =

H =

I =

J =

Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (mm) from the center line of the terminal

Clearance to unventilated soffit

Clearance to outside corner

Clearance to inside corner

Clearance to each side of center line extended above meter / regulator assembly

Clearance to service regulator vent outlet

Clearance to non−mechanical air supply inlet to building or the combustion air inlet to any other appliance

*

* Equal to or greater than soffit depth.

* Equal to or greater than soffit depth.

* No minimum to outside corner

*

3 feet (.9m) within a height 15 feet (4.5m) above the meter / regulator assembly

* 3 feet (.9m)

4 feet (1.2 m) below or to side of opening;

1 foot (30 cm) above opening

3 feet (.9m) above if within 10 feet

(3m) horizontally

7 feet (2.1m)

* Equal to or greater than soffit depth.

* Equal to or greater than soffit depth.

* No minimum to outside corner

*

3 feet (.9m) within a height 15 feet (4.5m) above the meter / regulator assembly

3 feet (.9m)

6 inches (152mm) for appliances <10,000

Btuh (3kw), 12 inches (305mm) for appliances > 10,000 Btuh (3kw) and

<100,000 Btuh (30kw), 36 inches (.9m) for appliances > 100,000 Btuh (30kw)

6 feet (1.8m) K =

L =

Clearance to mechanical air supply inlet

Clearance above paved sidewalk or paved driveway located on public property

7 feet (2.1m)

M = Clearance under veranda, porch, deck or balcony

*12 inches (305mm)

1

In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code

2 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code

12 inches (305mm)

*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearance will be in accordance with local installation codes and the requirements of the gas supplier and these installation instructions."

A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.

Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Lennox recommends avoiding this location if possible.

FIGURE 26

Page 23

VENT TERMINATION CLEARANCES

FOR DIRECT VENT INSTALLATIONS IN THE USA AND CANADA

INSIDE CORNER

DETAIL

G

H

A

D

E

B

L

F

C

Fixed

Closed

Operable

B

Operable

B

Fixed

Closed

I

M

B

K

J

A

B

A =

B =

VENT TERMINAL

Clearance above grade, veranda, porch, deck or balcony

Clearance to window or door that may be opened

AIR SUPPLY INLET

US Installations 1

12 inches (305mm) or 12 in. 305mm) above average snow accumulation.

AREA WHERE TERMINAL

IS NOT PERMITTED

Canadian Installations 2

12 inches (305mm) or 12 in. 305mm) above average snow accumulation.

6 inches (152mm) for appliances <10,000

Btuh (3kw), 9 inches (mm) for appliances

> 10,000 Btuh (3kw) and <50,000 Btuh

(15 kw), 12 inches (305mm) for appliances > 50,000 Btuh (15kw)

* 12"

6 inches (152mm) for appliances <10,000

Btuh (3kw), 12 inches (305mm) for appliances > 10,000 Btuh (3kw) and

<100,000 Btuh (30kw), 36 inches (.9m) for appliances > 100,000 Btuh (30kw)

* 12" C = Clearance to permanently closed window

D =

E =

F =

Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (mm) from the center line of the terminal

Clearance to unventilated soffit

Clearance to outside corner

* Equal to or greater than soffit depth

* Equal to or greater than soffit depth

* No minimum to outside corner

*

* Equal to or greater than soffit depth

* Equal to or greater than soffit depth

* No minimum to outside corner

G =

H =

I =

J =

Clearance to inside corner

Clearance to each side of center line extended above meter / regulator assembly

Clearance to service regulator vent outlet

Clearance to non−mechanical air supply inlet to building or the combustion air inlet to any other appliance

3 feet (.9m) within a height 15 feet (4.5m) above the meter / regulator assembly

* 3 feet (.9m)

6 inches (152mm) for appliances <10,000

Btuh (3kw), 9 inches (mm) for appliances

> 10,000 Btuh (3kw) and <50,000 Btuh

(15 kw), 12 inches (305mm) for appliances > 50,000 Btuh (15kw)

3 feet (.9m) above if within 10 feet

(3m) horizontally

*

3 feet (.9m) within a height 15 feet (4.5m) above the meter / regulator assembly

3 feet (.9m)

6 inches (152mm) for appliances <10,000

Btuh (3kw), 12 inches (305mm) for appliances > 10,000 Btuh (3kw) and

<100,000 Btuh (30kw), 36 inches (.9m) for appliances > 100,000 Btuh (30kw)

6 feet (1.8m) K =

L =

Clearance to mechanical air supply inlet

Clearance above paved sidewalk or paved driveway located on public property

* 7 feet (2.1m)

7 feet (2.1m)

M = Clearance under veranda, porch, deck or balcony

*12 inches (305mm)

1

In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code

2 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code

12 inches (305mm)

*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearance will be in accordance with local installation codes and the requirements of the gas supplier and these installation instructions."

A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.

Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Lennox recommends avoiding this location if possible.

FIGURE 27

Page 24

Details of Intake and Exhaust Piping Terminations for

Direct Vent Installations

NOTE − In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged to outdoors.

NOTE − Flue gas may be slightly acidic and may adversely affect some building materials. If any vent termination is used and the flue gasses may impinge on the building material, a corrosion−resistant shield (minimum 24 inches square) should be used to protect the wall surface. If the optional tee is used, the protective shield is recommended.

The shield should be constructed using wood, plastic, sheet metal or other suitable material. All seams, joints, cracks, etc. in the affected area should be sealed using an

appropriate sealant. See figure 29.

Intake and exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof

is preferred. Figures 28 through 40 show typical termina-

tions.

1 − Exhaust and intake exits must be in same pressure zone. Do not exit one through the roof and one on the side. Also, do not exit the intake on one side and the exhaust on another side of the house or structure.

2 − Intake and exhaust pipes should be placed as close together as possible at termination end (refer to illustrations). Maximum separation is 3" (76mm) on roof terminations and 6" (152mm) on side wall terminations.

3 − On roof terminations, the intake piping should terminate straight down using two 90° elbows (See figure

28).

4 − Exhaust piping must terminate straight out or up as shown. A reducer may be required on the exhaust piping at the point where it exits the structure to improve the velocity of exhaust away from the intake piping.

See table 6.

3"(76mm) MAX.

Inches(mm) SIZE TERMINATION

PIPE PER TABLE 6.

8" (203mm) MIN

12" (305mm) ABOVE

AVERAGE SNOW

ACCUMULATION

UNCONDITIONED

ATTIC SPACE

1/2" (13mm) FOAM

INSULATION IN

UNCONDITIONED

SPACE

TABLE 6

EXHAUST PIPE TERMINATION SIZE REDUCTION

EL195UH

MODEL

Exhaust Pipe Size

Termination

Pipe Size

*045 and 070

*090

110

135

2" (51mm), 2−1/2" (64mm),

3" (76mm)

3" (76mm)

1−1/2" (38mm)

2" (51mm)

2" (51mm)

2" (51mm)

*EL195UH−045, −070 and −090 units with the flush mount termination must use the 1−1/2"accelerator supplied with the kit.

NOTE − Care must be taken to avoid recirculation of exhaust back into intake pipe.

5 − On field−supplied terminations for side wall exit, exhaust piping may extend a maximum of 12 inches

(305mm) for 2" PVC and 20 inches (508mm) for 3"

(76mm) PVC beyond the outside wall. Intake piping

should be as short as possible. See figures 30 and 31.

6 − On field−supplied terminations, a minimum distance between the end of the exhaust pipe and the end of the intake pipe without a termination elbow is 8" and a minimum distance of 6" with a termination elbow. See

figures 30 and 31.

7 − If intake and exhaust piping must be run up a side wall to position above snow accumulation or other obstructions, piping must be supported every 24"

(610mm) as shown in figures 30 and 31. In addition,

close coupled wall termination kits must be extended

for use in this application. See figures 38 and 39.

When exhaust and intake piping must be run up an outside wall, the exhaust piping must be terminated

with pipe sized per table 6.The intake piping may be

equipped with a 90° elbow turndown. Using turndown will add 5 feet (1.5m) to the equivalent length of the pipe.

8 − A multiple furnace installation may use a group of up to four terminations assembled together horizontally, as

shown in figure 35.

3" (76mm) OR

2" (51mm) PVC

PROVIDE SUPPORT

FOR INTAKE AND

EXHAUST LINES

DIRECT VENT ROOF TERMINATION KIT

(15F75 or 44J41)

FIGURE 28

Page 25

B

B

D

D

Intake

C

3

C

1

A

Exhaust

Front View of

Intake and Exhaust

2

A

Intake Exhaust

D

TABLE 7

2" (51mm)

Vent Pipe

3" (76mm)

Vent Pipe

2

B

A

E

C

1

12"

A − Clearance above grade or average snow accumulation

B −Horizontal

separation between

intake and exhaust

C −Minimum from end of exhaust to inlet of intake

D −Exhaust pipe length

E −Wall support distance from top of each pipe

(intake/exhaust)

12" (508MM) Min.

6" (152MM) Min.

24" (610 MM) Max

9" (227MM) Min.

12" (305MM) Min.

16" (405 MM) Max.

6" (152MM) Max.

12" (508MM) Min.

6" (152MM) Min.

24" (610 MM) Max

9" (227MM) Min.

12" (305MM) Min.

20" (508MM) Max.

6" (152MM) Max.

NOTE − See unit installation instructions for proper exhaust pipe termination size reduction.

1 The exhaust termination tee should be connected to the 2" or 3" PVC flue pipe as shown in the illustration. Do not use an accelerator in applications that include an exhaust termination tee. The accelerator is not required.

2 As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent termination is used and flue gases will impinge on the building materials, a corrosion−resistant shield (24 inches square) should be used to protect the wall surface. If optional tee is used, the protective shield is recommended. The shield should be constructed using wood, sheet metal or other suitable material. All seams, joints, cracks, etc. in affected area, should be sealed using an appropriate sealant.

3 Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust away from adjacent property. The exhaust must never be directed toward the combustion air inlet.

FIGURE 29

Page 26

FIELD−SUPPLIED WALL TERMINATION OR

(15F74) WALL RING TERMINATION KIT

NOTE − FIELD−PROVIDED

REDUCER MAY BE

REQUIRED TO ADAPT

LARGER VENT PIPE SIZE

TO TERMINATION

D

1/2" (13mm) ARMAFLEX

INSULATION IN UN-

CONDITIONED SPACE

SIZE TERMINATION

PER TABLE 6

C

A

B

STRAIGHT

APPPLICATION

1/2" (13mm) ARMAFLEX INSULATION

IN UNCONDITIONED SPACE

D

* WALL

SUPPORT

E

B

A

C

EXTENDED

APPLICATION

See venting table

5

for maximum venting lengths with this arrangement.

* Use wall support every 24" (610 mm). Use two wall supports if extension is greater than 24" (610 mm) but less than 48" (1219 mm).

NOTE − One wall support must be 6" (152 mm) from top of each pipe

(intake and exhaust)

A −Minimum clearance above grade or average snow accumulation

B −Maximum horizontal

separation between

intake and exhaust

C −Minimum from end of exhaust to inlet of intake

D −Maximum exhaust pipe length

E −Maximum wall support distance from top of each pipe (intake/exhaust)

2" (51mm)

Vent Pipe

12" (508MM)

6" (152MM)

8" (203MM)

12" (305MM)

6" (152MM)

3" (76mm)

Vent Pipe

12" (508MM)

6" (152MM)

8" (203MM)

20" (508MM)

6" (152MM)

FIGURE 30

FIELD−SUPPLIED WALL TERMINATION OR

(15F74) WALL RING TERMINATION KIT

With INTAKE ELBOW

NOTE − FIELD−PROVIDED

REDUCER MAY BE

REQUIRED TO ADAPT

LARGER VENT PIPE SIZE

TO TERMINATION

1/2" (13mm) ARMAFLEX

INSULATION IN UN-

CONDITIONED SPACE

SIZE TERMINATION

PER TABLE 6

D

C

A

B

STRAIGHT

APPPLICATION

1/2" (13mm) ARMAFLEX INSULATION

IN UNCONDITIONED SPACE

D

* WALL

SUPPORT

E

C

B

A

EXTENDED

APPLICATION

See venting table 5 for maximum venting lengths with this

arrangement.

* Use wall support every 24" (610 mm). Use two wall supports if extension is greater than 24" (610 mm) but less than 48" (1219 mm).

NOTE − One wall support must be 6" (152 mm) from top of each pipe

(intake and exhaust)

2" (51mm)

Vent Pipe

3" (76mm)

Vent Pipe

A −Minimum clearance above grade or average snow accumulation

B −Maximum horizontal

separation between

intake and exhaust

C −Minimum from end of exhaust to inlet of intake

D −Maximum exhaust pipe length

E −Maximum wall support distance from top of each pipe (intake/exhaust)

12" (508MM)

6" (152MM)

6" (152MM)

12" (305MM)

6" (152MM)

12" (508MM)

6" (152MM)

6" (152MM)

20" (508MM)

6" (152MM)

FIGURE 31

Page 27

2" EXTENSION FOR 2" PVC

PIPE1" EXTENSION FOR 3"

PVC PIPE

4’’

FURNACE

EXHAUST

PIPE

FURNACE

INTAKE

PIPE

GLUE EXHAUST

END FLUSH INTO

TERMINATION

FLAT

SIDE 1−1/2" ACCELERATOR

( all −45, −070 and −090 units)

FLUSH−MOUNT SIDE WALL TERMINATION

51W11

FIGURE 32

EXHAUST

VENT

INTAKE

AIR

Inches (mm)

5"

(127mm)

18" MAX.

(457mm)

12"

(305mm)

5−1/2"

(140mm)

Front View

EXHAUST VENT

INTAKE

AIR

12" (305mm) Min.

above grade or average snow accumulation.

EXHAUST

VENT

12” (305mm)

Minimum

Above Average

Snow

Accumulation

INTAKE

AIR

1 1/2" (38mm) accelerator provided on 71M80 & 44W92 kits for EL195UH045P24B,

070P24B & 070P36B

FLASHING

(Not Furnished) optional intake elbow

Side View

OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT

INSTALLATION OF DIRECT VENT WALL TERMINATION KIT

(22G44, 44J40, 30G28 or 81J20)

FIGURE 35

Front View

INTAKE

AIR

EXHAUST VENT

SIZE

TERMINATION

PIPE PER

TABLE 6.

Top View

1/2" (13mm) Foam Insulation

in Unconditioned Space

FIELD−

PROVIDED

REDUCER MAY

BE REQUIRED

TO ADAPT

LARGER VENT

PIPE SIZE TO

TERMINATION

EXHAUST VENT

INTAKE AIR

6 (152mm) MIN.

CLAMP

SHEET METAL STRAP

(Clamp and sheet metal strap must be field installed to support the weight of the termination kit.)

FIELD−PROVIDED

REDUCER MAY BE REQUIRED

TO ADAPT LARGER VENT

PIPE SIZE TO TERMINATION

DIRECT VENT CONCENTRIC ROOFTOP TERMINATION

71M80, 69M29 or 60L46 (US)

44W92 or 44W93 (Canada)

FIGURE 33

FIELD−PROVIDED

REDUCER MAY BE REQUIRED

TO ADAPT LARGER VENT

PIPE SIZE TO TERMINATION

OUTSIDE

WALL

EXHAUST

VENT

INTAKE

AIR

CLAMP

(Not Furnished)

12" (305mm) Min.

above grade or average snow accumulation.

GRADE

DIRECT VENT CONCENTRIC WALL TERMINATION

71M80, 69M29 or 60L46 (US)

44W92 or 44W93 (Canada)

FIGURE 34

1−1/2" (38mm) accelerator provided on 71M80 & 44W92 kits for EL195UH045P24B,

070P24B & 070P36B

INTAKE

AIR

EXHAUST

VENT

OUTSIDE WALL

DIRECT VENT WALL TERMINATION KIT

(30G28 or 81J20)

FIGURE 36

Front View EXHAUST VENT

SIZE

TERMINATION

PIPE PER

TABLE 6.

INTAKE

AIR

1/2" (13mm) Foam Insulation

in Unconditioned Space

FIELD−

PROVIDED

REDUCER MAY

BE REQUIRED

TO ADAPT

LARGER VENT

PIPE SIZE TO

TERMINATION

Top View

EXHAUST VENT

INTAKE AIR

8" (206mm) MIN.

OUTSIDE WALL

DIRECT VENT WALL TERMINATION KIT

(22G44 or 44J40)

FIGURE 37

Page 28

WALL TERMINATION KITS (CLOSE − COUPLE)

EXTENDED VENT FOR GRADE CLEARANCE

2 inch (51 mm) 22G44 (US)

3 inch (76 mm) 44J40 (US)

If intake and exhaust pipe is less than 12 in. (305 mm) above snow accumulation or other obstructions, field − fabricated piping must be installed.

FIELD−PROVIDED

REDUCER MAY BE REQUIRED TO ADAPT

LARGER VENT PIPE SIZE TO TERMINATION

WALL SUPPORT*

8” (203 mm) Min. for 2” (51 mm) & 3” (76 mm) DIA. pipe between the end of the exhaust pipe and intake pipe

12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust

20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust

12”

(305 mm)

6” (152 mm)

Maximum

EXHAUST

AIR

1/2” (13 mm)

FOAM INSULATION

(Field − Furnished)

INTAKE

AIR

INTAKE

AIR EXHAUST

AIR

5” (127 mm)

8” (203 mm) Min.

12” (305 mm) Minimum

Above Grade or Average

Snow Accumulation

GRADE

ÉÉÉÉÉÉÉÉÉÉÉÉ

12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust

ÉÉÉÉÉÉÉÉÉÉÉÉ 20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust

5 − 1/2”

(140 mm)

12” (305 mm) Minimum

Above Grade or Average

Snow Accumulation

ÉÉÉÉÉÉÉÉÉÉÉÉ

GRADE

*Use wall support every 24" (610). Use two supports if

ÉÉÉÉÉÉÉÉÉÉÉÉ extension is greater than 24" but less than 48".

FIGURE 38

WALL TERMINATION KITS (CLOSE − COUPLE)

EXTENDED VENT FOR GRADE CLEARANCE

2 inch (51 mm) 30G28 (WTK Canada)

3 inch (76 mm) 81J20 (WTK Canada)

See Installation Instructions for additional information.

If intake and exhaust pipe is less than 12 in. (305 mm) above snow accumulation or other obstructions, field − fabricated piping must be installed.

WALL SUPPORT*

6” (152 mm)

Maximum

INTAKE

AIR

FIELD−PROVIDED

REDUCER MAY BE REQUIRED TO ADAPT

LARGER VENT PIPE SIZE TO TERMINATION

12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust

20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust

12”

(305 mm)

EXHAUST

AIR

1/2” (13 mm)

FOAM INSULATION

(Field − Furnished)

6” (152 mm)

Minimum

INTAKE

AIR EXHAUST

AIR

5” (127 mm)

6” (152 mm)

Minimum

12” (305 mm) Minimum

Above Grade or Average

Snow Accumulation

GRADE

5 − 1/2”

(140 mm)

12” (305 mm) Minimum

Above Grade or Average

Snow Accumulation

GRADE

ÉÉÉÉÉÉÉÉÉÉÉÉ

12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust

20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust

ÉÉÉÉÉÉÉÉÉÉÉÉ

*Use wall support every 24" (610). Use two supports if extension is greater than 24" but less than 48".

FIGURE 39

Page 29

EL195UH DIRECT VENT APPLICATION

USING EXISTING CHIMNEY

3"−8"

(76mm−203mm)

STRAIGHT−CUT OR

ANGLE−CUT IN DIRECTION

OF ROOF SLOPE *

8" − 12"

(203mm − 305mm)

Minimum 12" (305MM) above chimney top plate or average snow accumulation

INTAKE PIPE

INSULATION (optional)

SHEET

METAL TOP

PLATE

INSULATE

TO FORM

SEAL

EXHAUST VENT

1/2" (13mm)

WEATHERPROOF

INSULATION

SHOULDER OF FITTINGS

PROVIDE SUPPORT

OF PIPE ON TOP PLATE

ALTERNATE

INTAKE PIPE

3" − 8"

(76mm−

203mm)

EXTERIOR

PORTION OF

CHIMNEY

*SIZE TERMINATION

PIPE PER TABLE 6.

NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If vertical discharge through an existing unused chimney or stack is required, insert piping inside chimney until the pipe open end is above top of chimney and terminate as illustrated. In any exterior portion of chimney, the exhaust vent must be insulated.

FIGURE 40

Details of Exhaust Piping Terminations for Non-Direct

Vent Applications

Exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is pre-

ferred. Figures 41 through 44 show typical terminations.

1 − Exhaust piping must terminate straight out or up as shown. The termination pipe must be sized as listed in

table 6.The specified pipe size ensures proper veloc-

ity required to move the exhaust gases away from the building.

2 − On field supplied terminations for side wall exit, exhaust piping may extend a maximum of 12 inches

(305mm) for 2" PVC and 20 inches (508mm) for 3"

(76mm) PVC beyond the outside wall. See figure 42.

SIZE TERMINATION

PIPE PER TABLE 6.

12" (305mm)

ABOVE AVE.

SNOW

ACCUMULATION

1/2" (13mm) FOAM

INSULATION

1/2" (13mm) ARMAFLEX

INSULATION IN

UNCONDITIONED SPACE

FIELD−PROVIDED

REDUCER MAY

BE REQUIRED TO

ADAPT LARGER

VENT PIPE SIZE

TO TERMINATION

SIZE TERMINATION

PIPE PER TABLE 6.

12" (305mm) MAX. for 2" (51mm)

20" (508mm) MAX. for 3" (76mm)

1/2" (13mm)

ARMAFLEX

INSULATION

PVC REDUCER

12" MIN.

(305mm)

Above Grade or average snow accumulation

NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION OR

(15F74) WALL TERMINATION KIT

FIGURE 42

3 − If exhaust piping must be run up a side wall to position above snow accumulation or other obstructions, piping must be supported every 24 inches (610mm) as

shown in figure 43. When exhaust piping must be run

up an outside wall, any reduction in exhaust pipe size must be done after the final elbow.

12" (305mm) MAX. for 2" (51mm)

20" (508mm) MAX. for 3" (76mm)

UNCONDITIONED

SPACE

6" (152mm)

Max

*WALL SUPPORT

OUTSIDE WALL

FIELD−PROVIDED

REDUCER MAY BE

REQUIRED TO

ADAPT LARGER

VENT PIPE SIZE TO

TERMINATION

SIZE TER-

MINATION

PIPE PER

TABLE 6.

12" (305mm)

ABOVE GRADE OR

AVERAGE SNOW

ACCUMULATION

1/2" (13mm) FOAM

INSULATION IN

UNCONDITIONED

SPACE

1/2" (13mm) FOAM

INSULATION

NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION

EXTENDED OR (15F74) WALL TERMINATION VENT PIPE

EXTENDED

*Use wall support every 24" (610). Use two supports if extension is greater than 24" but less than 48".

FIGURE 43

3" (76mm) OR

2" (51mm) PVC

PROVIDE SUPPORT

FOR EXHAUST LINES

UNCONDITIONED

ATTIC SPACE

NON−DIRECT VENT ROOF TERMINATION KIT

(15F75 or 44J41)

FIGURE 41

Page 30

EL195UH NON−DIRECT VENT APPLICATION

USING EXISTING CHIMNEY

SIZE TERMINATION

PIPE PER TABLE 6.

STRAIGHT−CUT OR

ANGLE−CUT IN DIRECTION

OF ROOF SLOPE

Minimum 12" (305MM) above chimney top plate or average snow accumulation

SHEET

METAL TOP

PLATE

EXHAUST VENT

1/2" (13mm)

WEATHERPROOF

INSULATION

SHOULDER OF FITTINGS

PROVIDE SUPPORT

OF PIPE ON TOP PLATE

INSULATE

TO FORM

SEAL

EXTERIOR

PORTION OF

CHIMNEY

CONDENSATE TRAP AND PLUG LOCATIONS

(Unit shown in upflow position)

Trap

(same on right side)

1−1/2 in.

Plug

(same on left side)

NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If vertical discharge through an existing unused chimney or stack is required, insert piping inside chimney until the pipe open end is above top of chimney and terminate as illustrated. In any exterior portion of chimney, the exhaust vent must be insulated.

FIGURE 44

Condensate Piping

This unit is designed for either right- or left-side exit of condensate piping in upflow applications. In horizontal applications, the condensate trap must extend below the unit. An

8" service clearance is required for the condensate trap.

Refer to figure 45 for condensate trap locations. Figure 49

shows trap assembly using 1/2" PVC or 3/4" PVC.

NOTE − If necessary the condensate trap may be installed up to 5´ away from the furnace. Use PVC pipe to connect trap to furnace condensate outlet. Piping from furnace must slope down a minimum of 1/4" per ft. toward trap.

1 − Determine which side condensate piping will exit the unit, location of trap, field−provided fittings and length of

PVC pipe required to reach available drain.

2 − Remove plug (figure 45) from the cold end header box

at the appropriate location on the side of the unit. Install field−provided 1/2 NPT male fitting into cold end header box. Use Teflon tape or appropriate pipe dope.

3 − Install the cap over the clean out opening at the base of

the trap. Secure with clamp. See figure 49.

NOTE − In upflow applications where side return air filter is installed on same side as the condensate trap, filter rack must be installed beyond condensate trap or trap must be re−located to avoid interference.

FIGURE 45

4 − Install drain trap using appropriate PVC fittings, glue all joints. Glue the provided drain trap as shown in fig-

ure 49. Route the condensate line to an open drain.

Condensate line must maintain a 1/4" downward slope from the furnace to the drain.

NOTE − Vinyl tubing may be used for condensate drain.

Tubing must be 1−1/4" OD X 1" ID and should be attached to the drain on the trap using a hose clamp.

CAUTION

Do not use copper tubing or existing copper condensate lines for drain line.

5 − If unit will be started immediately upon completion of installation, prime trap per procedure outlined in Unit

Start−Up section.

Condensate line must slope downward away from the trap to drain. If drain level is above condensate trap, condensate pump must be used. Condensate drain line should be routed within the conditioned space to avoid freezing of condensate and blockage of drain line. If this is not possible, a heat cable kit may be used

Page 31

on the condensate trap and line. Heating cable kit is available from Lennox in various lengths; 6 ft. (1.8m) − kit no. 26K68; 24 ft. (7.3m) − kit no. 26K69; and 50 ft.

(15.2m) − kit no. 26K70.

CONDENSATE TRAP LOCATIONS

(Unit shown in upflow position with remote trap)

Field Provided Vent

Min. 1" Above Condensate

Drain Connection

1" Min.

*5’ max.

PVC Pipe Only

Trap Can Be Installed a

Maximum 5’ From Furnace

CAUTION

A separate drain line must be run to the drain from the condensate trap to ensure proper drainage and pressure switch operation. DO NOT connect the condensate trap drain into the drain line from the evaporator coil.

EL195UH with Evaporator Coil

Condensate trap and evaporator coil must be drained separately as shown.

To Drain

*Piping from furnace must slope down a minimum of 1/4" per ft. toward trap.

FIGURE 46

CONDENSATE TRAP LOCATIONS

(Unit shown in horizontal right − hand discharge position)

FIGURE 47

Field−Provided Vent

Must Not Interfere With

Service To The Unit to drain

4−1/2"

Min.

5’ max.

*PVC Pipe Only

*Piping from furnace must slope down a minimum of 1/4" per ft. toward trap.

FIGURE 48

Page 32

TRAP / DRAIN ASSEMBLY USING 1/2" PVC OR 3/4" PVC

OPTIONAL Condensate Drain Connection

Adapter 1/2 inch slip X

1/2 inch mpt (Not Furnished)

Adapter 1/2 inch slip X

1/2 inch mpt (Not Furnished)

90 ° Street Elbow

1/2 inch PVC

(Not Furnished)

1 (25) Minimum

Vent

5 Feet

Maximum

Condensate Drain

Connection In Unit

Condensate Drain

Connection In Unit

90 ° Elbow 1/2 inch PVC

(Not Furnished)

OPTIONAL Drain Piping

Drain Assembly for 1/2 inch Drain Pipe

1/2 inch PVC Pipe

(Not Furnished)

1/2 inch PVC Pipe

(Not Furnished)

Coupling 1/2 inch slip X slip

(Not Furnished)

To

Drain

90 ° Street Elbow

1/2 inch PVC

(Furnished)

To

Drain

1/2 inch PVC Pipe

(Not Furnished)

90 ° Elbow

1/2 inch PVC

(Not Furnished)

Drain Assembly for 3/4 inch Drain Pipe

Drain Trap

Assembly

(Furnished)

Drain Trap

Clean Out

To

Drain

90 ° Elbow

3/4 inch PVC

(Not Furnished)

90 ° Elbow

3/4 inch PVC

(Not Furnished)

To

Drain

Coupling 3/4 inch slip X slip

(Not Furnished)

Drain Trap Assembly

(Furnished)

Drain Trap Assembly with 1/2 inch Piping

1 inch (25mm) Minimum Above Top of

Condensate Drain Connection In Unit

Vent

Drain Trap Assembly with 3/4 inch Piping

1 inch (25mm) Minimum Above Top of

Condensate Drain Connection In Unit

Vent

7

(178)

Condensate Drain

Connection In Unit

Condensate Drain

Connection In Unit

To

Drain

To

Drain

FIGURE 49

Page 33

Gas Piping

Gas supply piping should not allow more than 0.5"W.C. drop in pressure between gas meter and unit. Supply gas pipe must not be smaller than unit gas connection.

CAUTION

If a flexible gas connector is required or allowed by the authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet. The flexible connector can then be added between the black iron pipe and the gas supply line.

WARNING

Do not exceed 600 in−lbs (50 ft−lbs) torque when attaching the gas piping to the gas valve.

1 − Gas piping may be routed into the unit through either the left- or right-hand side. Supply piping enters into the gas valve from the side of the valve as shown in

figure 51. Move Bellows grommet to side which gas

line enters. Ensure opposite gas line hole is plugged with supplied plug.

2 − When connecting gas supply, factors such as length of run, number of fittings and furnace rating must be con-

sidered to avoid excessive pressure drop. Table 8 lists

recommended pipe sizes for typical applications.

NOTE − Use two wrenches when connecting gas piping to avoid transferring torque to the manifold.

3 − Gas piping must not run in or through air ducts, clothes chutes, chimneys or gas vents, dumb waiters or elevator shafts. Center gas line through piping hole. Gas

line should not touch side of unit. See figures 51 and

52.

4 − Piping should be sloped 1/4 inch per 15 feet (6mm per

5.6m) upward toward the gas meter from the furnace.

The piping must be supported at proper intervals, every 8 to 10 feet (2.44 to 3.05m), using suitable hangers or straps. Install a drip leg in vertical pipe runs to serve as a trap for sediment or condensate.

5 − A 1/8" N.P.T. plugged tap or pressure post is located on the gas valve to facilitate test gauge connection.

See figure 59.

6 − In some localities, codes may require installation of a manual main shut-off valve and union (furnished by installer) external to the unit. Union must be of the ground joint type.

IMPORTANT

Compounds used on threaded joints of gas piping must be resistant to the actions of liquified petroleum gases.

Leak Check

After gas piping is completed, carefully check all piping connections (factory− and field−installed) for gas leaks. Use a leak detecting solution or other preferred means.

Never use an open flame to test for gas leaks. Check all connections using a commercially available soap solution made specifically for leak detection.

The furnace must be isolated from the gas supply system by closing its individual manual shut-off valve during any pressure testing of the gas supply system at pressures greater than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).

MANUAL MAIN SHUT−OFF

VALVE WILL NOT HOLD

NORMAL TEST PRESSURE

1/8" N.P.T.

PLUGGED TAP

CAP

FURNACE

ISOLATE

GAS VALVE

FIGURE 50

IMPORTANT

When testing pressure of gas lines, gas valve must

be disconnected and isolated. See figure 50. Gas

valves can be damaged if subjected to pressures greater than 1/2 psig (3.48 kPa).

WARNING

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result in serious injury, death, or property damage.

Never use an open flame to test for gas leaks. Check all connections using a commercially available soap solution made specifically for leak detection. Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly after leak test has been completed.

Page 34

Left Side Piping

(Standard)

MANUAL

MAIN SHUT−OFF

VALVE

GROUND

JOINT

UNION

Plug Plug

Right Side Piping

(Alternate)

Bellows Grommet

MANUAL

MAIN SHUT−OFF

VALVE

GROUND

JOINT

UNION

DRIP LEG

DRIP LEG

Gas Valve

Bellows Grommet

FIELD

PROVIDED

AND INSTALLED

NOTE − BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET

FIGURE 51

Gas Valve

MANUAL

MAIN SHUT−OFF

VALVE

Horizontal Applications

Possible Gas Piping Configurations

MANUAL

MAIN SHUT−OFF

VALVE Horizontal Application

Left−Side Air Discharge

GROUND

JOINT

UNION

DRIP LEG

Bellows Grommet

GROUND

JOINT

UNION

DRIP LEG

Bellows Grommet

Gas Valve

Horizontal Application

Right−Side Air Discharge

Gas Valve

MANUAL

MAIN SHUT−OFF

VALVE

GROUND

JOINT

UNION

DRIP LEG

Plug

FIELD

PROVIDED

AND INSTALLED

Bellows Grommet

NOTE − BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET

FIGURE 52

Page 35

Nominal

Iron Pipe Size

−Inches(mm)

1/2

(12.7)

3/4

(19.05)

1

(25.4)

1−1/4

(31.75)

1−1/2

(38.1)

2

(50.8)

2−1/2

(63.5)

3

(76.2)

4

(101.6)

Internal

Diameter

−Inches(mm)

.622

(17.799)

.824

(20.930)

1.049

(26.645)

1.380

(35.052)

1.610

(40.894)

2.067

(52.502)

2.469

(67.713)

3.068

(77.927)

4.026

(102.260)

10

(3.048)

175

(4.96)

360

(10.19)

680

(19.25)

1400

(39.64)

2100

(59.46)

3950

(111.85)

6300

(178.39)

11000

(311.48)

23000

(651.27)

TABLE 8

GAS PIPE CAPACITY − FT 3 /HR (kL/HR)

20

(6.096)

120

(3.40)

250

(7.08)

465

(13.17)

950

(26.90)

460

(41.34)

2750

(77.87)

4350

(123.17)

7700

(218.03)

15800

(447.39)

30

(9.144)

97

(2.75)

200

(5.66)

375

(10.62)

770

(21.80)

1180

(33.41)

2200

(62.30)

3520

(99.67)

6250

(176.98)

12800

(362.44)

40

(12.192)

82

(2.32)

Length of Pipe−Feet(m)

50

(15.240)

73

(2.07)

60

(18.288)

66

(1.87)

70

(21.336)

61

(1.73)

170

(4.81)

320

(9.06)

660

(18.69)

990

(28.03)

1900

(53.80)

3000

(84.95)

5300

(150.07)

10900

(308.64)

151

(4.28)

285

(8.07)

580

(16.42)

900

(25.48)

1680

(47.57)

2650

(75.04)

4750

(134.50)

9700

(274.67)

138

(3.91)

260

(7.36)

530

(15.01)

810

(22.94)

1520

(43.04)

2400

(67.96)

4300

(121.76)

8800

(249.18)

125

(3.54)

240

(6.80)

490

(13.87)

750

(21.24)

1400

(39.64)

2250

(63.71)

3900

(110.43)

8100

(229.36)

NOTE − Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specific gravity gas.

80

(24.384)

57

(1.61)

118

(3.34)

220

(6.23)

460

(13.03)

690

(19.54)

1300

(36.81)

2050

(58.05)

3700

(104.77)

7500

(212.37)

Removal of the Furnace from Common Vent

In the event that an existing furnace is removed from a venting system commonly run with separate gas appliances, the venting system is likely to be too large to properly vent the remaining attached appliances.

Conduct the following test while each appliance is operating and the other appliances (which are not operating) remain connected to the common venting system. If the venting system has been installed improperly, you must correct the system as indicated in the general venting requirements section.

WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.

The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:

1 − Seal any unused openings in the common venting system.

2 − Inspect the venting system for proper size and horizontal pitch. Determine that there is no blockage, restriction, leakage, corrosion, or other deficiencies which could cause an unsafe condition.

90

(27.432)

53

(1.50)

110

(3.11)

205

(5.80)

430

(12.18)

650

(18.41)

1220

(34.55)

1950

(55.22)

3450

(97.69)

7200

(203.88)

100

(30.480)

50

(1.42)

103

(2.92)

195

(5.52)

400

(11.33)

620

(17.56)

1150

(32.56)

1850

(52.38)

3250

(92.03)

6700

(189.72)

3 − Close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.

4 − Follow the lighting instructions. Turn on the appliance that is being inspected. Adjust the thermostat so that the appliance operates continuously.

5 − After the main burner has operated for 5 minutes, test for leaks of flue gases at the draft hood relief opening.

Use the flame of a match or candle.

6 − After determining that each appliance connected to the common venting system is venting properly, (step 3) return all doors, widows, exhaust fans, fireplace dampers, and any other gas−burning appliances to their previous mode of operation.

7 − If a venting problem is found during any of the preceding tests, the common venting system must be modified to correct the problem.

Resize the common venting system to the minimum vent pipe size determined by using the appropriate tables in Appendix G. (These are in the current standards of the National Fuel Gas Code ANSI Z223.1.

Page 36

Electrical

ELECTROSTATIC DISCHARGE (ESD)

Precautions and Procedures

CAUTION

Electrostatic discharge can affect electronic components. Take precautions to neutralize electrostatic charge by touching your hand and tools to metal prior to handling the control.

INTERIOR MAKE−UP BOX INSTALLATION

Left side

MAKE−UP

BOX

FIGURE 53

INTERIOR MAKE−UP BOX INSTALLATION

MAKE−UP

BOX remove and relocate plug to unused opening on left side

Right Side

FIGURE 54

The unit is equipped with a field make−up box. The make− up box may be moved to the right side of the furnace to facilitate installation. Seal unused openings on left side with plugs removed from right side. Secure the excess wire to the existing harness to protect it from damage.

Refer to figure 56 for field wiring and figure 57 for schematic

wiring diagram and troubleshooting.

The power supply wiring must meet Class I restrictions.

Protected by either a fuse or circuit breaker, select circuit protection and wire size according to unit nameplate.

NOTE − Unit nameplate states maximum current draw.

Maximum Over−Current Protection allowed is 15 AMP.

Holes are on both sides of the furnace cabinet to facilitate wiring.

Install a separate (properly sized) disconnect switch near the furnace so that power can be turned off for servicing.

Before connecting the thermostat check to make sure the wires will be long enough for servicing at a later date. Make sure that thermostat wire is long enough to facilitate future removal of blower for service.

Complete the wiring connections to the equipment. Use the provided unit wiring diagram and the field wiring diagram

shown in figure 56. Use 18−gauge wire or larger that is suit-

able for Class II rating for thermostat connections.

Electrically ground the unit according to local codes or, in the absence of local codes, according to the current National Electric Code (ANSI/NFPA No. 70) for the USA and current Canadian Electric Code part 1 (CSA standard

C22.1) for Canada. A green ground wire is provided in the field make−up box.

NOTE − The EL195UH furnace contains electronic components that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.

Accessory Terminals

One line voltage EAC" 1/4" spade terminal is provided on

the furnace integrated control. See figure 58 for integrated

control configuration. This terminal is energized when the indoor blower is operating. Any accessory rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. If an accessory rated at greater than one amp is connected to this terminal, it is necessary to use an external relay.

One line voltage HUM" 1/4" spade terminal is provided on

the furnace integrated control. See figure 58 for integrated

control configuration. This terminal is energized in the heating mode when the combustion air inducer is operating. Any humidifier rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. If a humidifier rated at greater than one amp is connected to this terminal, it is necessary to use an external relay relay.

Page 37

One 24V "H" 1/4" spade terminal is provided on the furnace

integrated control. See figure 58 for integrated control con-

figuration. The terminal is energized in the heating mode when the combustion air inducer is operating and the pressure switch is closed. Any humidifier rated up to 0.5 amp can be connected to this terminal with the ground leg of the circuit connected to ground or the "C" terminal.

EL195UH and CONDENSING UNIT

THERMOSTAT DESIGNATIONS

(Refer to specific thermostat and outdoor unit.)

Thermostat Furnace Condensing

Unit

POWER

*CONDENSING

UNIT

R R

HEAT

W1 W

COOLING

CONDENSING

UNIT

Y Y

INDOOR BLOWER

G G

C

COMMON

C

CONDENSING

UNIT COMMON

*NOTE − R" REQUIRED ON SOME OUTDOOR UNITS

FIGURE 55

Install the room thermostat according to the instruc-

tions provided with the thermostat. See figure 55 for

thermostat designations. If the furnace is being matched with a heat pump, refer to the FM21 installation instruction or appropriate dual fuel thermostat instructions.

Indoor Blower Speeds

1 − When the thermostat is set to FAN ON," the indoor blower will run continuously on the fan speed when there is no cooling or heating demand.

2 − When the EL195UH is running in the heating mode, the indoor blower will run on the heating speed.

3 − When there is a cooling demand, the indoor blower will run on the cooling speed.

Generator Use − Voltage Requirements

The following requirements must be kept in mind when specifying a generator for use with this equipment:

D The furnace requires 120 volts + 10% (Range: 108 volts to 132 volts).

D

The furnace operates at 60 Hz + 5% (Range: 57 Hz to

63 Hz).

D

The furnace integrated control requires both polarity and proper ground. Both polarity and proper grounding should be checked before attempting to operate the furnace on either permanent or temporary power.

D

Generator should have a wave form distortion of less than 5% THD (total harmonic distortion).

TYPICAL EL195UH FIELD WIRING DIAGRAM

IGNITOR

*R

*NOTE − R" REQUIRED ON SOME OUTDOOR

UNITS

FIGURE 56

Page 38

TYPICAL EL195UH WIRING DIAGRAM

FIGURE 57

Page 39

INTEGRATED CONTROL

(Automatic Hot Surface Ignition System)

HUM

LINE

XFMR

EAC

COOL

HEAT

PARK

FLAME

FAN

HUM

TERMINAL DESIGNATIONS

Humidifier (120VAC)

Input (120VAC)

Transformer (120VAC)

Indoor Air Quality Accessories (120VAC)

Blower − Cooling Speed (120VAC)

Blower − Heating Speed (120VAC)

Dead terminals to park alternate speed taps

Flame sensor

Continuous blower

Humidifier (24VAC)

Red LED Recall

Blower off delay jumper

FIGURE 58

Unit Start−Up

FOR YOUR SAFETY READ BEFORE OPERATING

WARNING

Do not use this furnace if any part has been underwater. A flood−damaged furnace is extremely dangerous. Attempts to use the furnace can result in fire or explosion. Immediately call a qualified service technician to inspect the furnace and to replace all gas controls, control system parts, and electrical parts that have been wet or to replace the furnace, if deemed necessary.

WARNING

Danger of explosion. Can cause injury or product or property damage. Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical supply.

CAUTION

Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch.

BEFORE LIGHTING the unit, smell all around the furnace area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

The gas valve on the EL195UH is equipped with a gas control switch (lever). Use only your hand to move switch. Never use tools. If the the switch will not move by hand, do not try to repair it. Force or attempted repair may result in a fire or explosion.

Placing the furnace into operation:

EL195UH units are equipped with an automatic hot surface ignition system. Do not attempt to manually light burners on this furnace. Each time the thermostat calls for heat, the burners will automatically light. The ignitor does not get hot when there is no call for heat on these units.

Page 40

Priming Condensate Trap

The condensate trap should be primed with water prior to start−up to ensure proper condensate drainage. Either pour 10 fl. oz. (300 ml) of water into the trap, or follow these steps to prime the trap:

1 − Follow the lighting instructions to place the unit into operation.

2 − Set the thermostat to initiate a heating demand.

3 − Allow the burners to fire for approximately 3 minutes.

4 − Adjust the thermostat to deactivate the heating demand.

5 − Wait for the combustion air inducer to stop. Set the thermostat to initiate a heating demand and again allow the burners to fire for approximately 3 minutes.

6 − Adjust the thermostat to deactivate the heating demand and wait for the combustion air inducer to stop.

At this point, the trap should be primed with sufficient water to ensure proper condensate drain operation.

WARNING

If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or death.

Gas Valve Operation (Figure 59)

1 − STOP ! Read the safety information at the beginning of this section.

2 − Set the thermostat to the lowest setting.

3 − Turn off all electrical power to the unit.

4 − This furnace is equipped with an ignition device which automatically lights the burners. Do not try to light the burners by hand.

5 − Remove the access panel.

6 − Move gas valve switch to OFF.

See figure 59.

7 − Wait five minutes to clear out any gas. If you then smell gas, STOP! Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you do not smell gas go to next step.

8 − Move gas valve switch to ON.

See figure 59.

MANIFOLD PRESSURE

ADJUSTMENT SCREW

(under barbed fitting)

MANIFOLD

PRESSURE

OUTLET

PORT

INLET

PRESSURE

PORT

GAS VALVE SHOWN IN ON POSITION

FIGURE 59

9 − Replace the access panel.

10− Turn on all electrical power to to the unit.

11− Set the thermostat to desired setting.

NOTE − When unit is initially started, steps 1 through 11 may need to be repeated to purge air from gas line.

12− If the appliance will not operate, follow the instructions

Turning Off Gas to Unit" and call your service technician or gas supplier.

Turning Off Gas to Unit

1 − Set the thermostat to the lowest setting.

2 − Turn off all electrical power to the unit if service is to be performed.

3 − Remove the access panel.

4 − Move gas valve switch to OFF.

5 − Replace the access panel.

Failure To Operate

If the unit fails to operate, check the following:

1 − Is the thermostat calling for heat?

2 − Are access panels securely in place?

3 − Is the main disconnect switch closed?

4 − Is there a blown fuse or tripped breaker?

5 − Is the filter dirty or plugged? Dirty or plugged filters will cause the limit control to shut the unit off.

6 − Is gas turned on at the meter?

7 − Is the manual main shut-off valve open?

8 − Is the internal manual shut-off valve open?

9 − Is the unit ignition system in lockout? If the unit locks out again, inspect the unit for blockages.

Heating Sequence Of Operation

1 − When thermostat calls for heat, combustion air inducer starts.

2 − Combustion air pressure switch proves blower operation. Switch is factory set and requires no adjustment.

3 − After a 15−second prepurge, the hot surface ignitor energizes.

4 − After a 20−second ignitor warm−up period, the gas valve solenoid opens. A 4−second trial for ignition period begins."

5 − Gas is ignited, flame sensor proves the flame, and the combustion process continues.

6 − If flame is not detected after first ignition trial, the ignition control will repeat steps 3 and 4 four more times before locking out the gas valve (WATCHGUARD" flame failure mode). The ignition control will then automatically repeat steps 1 through 6 after 60 minutes.

To interrupt the 60−minute WATCHGUARD" period, move thermostat from Heat" to OFF" then back to

Heat". Heating sequence then restarts at step 1.

Page 41

Gas Pressure Adjustment

Gas Flow (Approximate)

EL195

Unit

−045

−070

−090

−110

−135

TABLE 9

GAS METER CLOCKING CHART

Seconds for One Revolution

Natural LP

1 cu ft

Dial

2 cu ft

Dial

1 cu ft

Dial

2 cu ft

DIAL

80

55

41

33

27

160

110

82

66

54

200

136

102

82

68

Natural−1000 btu/cu ft LP−2500 btu/cu ft

400

272

204

164

136

Furnace should operate at least 5 minutes before checking gas flow. Determine time in seconds for two revolutions of gas through the meter. (Two revolutions assures a more accurate time.) Divide by two and compare to time

in table 9 below. If manifold pressure matches table 10

and rate is incorrect, check gas orifices for proper size and restriction. Remove temporary gas meter if installed.

NOTE − To obtain accurate reading, shut off all other gas appliances connected to meter.

Supply Pressure Measurement

When testing supply gas pressure, use the 1/8" N.P.T.

plugged tap or pressure post located on the gas valve to

facilitate test gauge connection. See figure 59. Check gas

line pressure with unit firing at maximum rate. Low pressure may result in erratic operation or underfire. High pressure can result in permanent damage to gas valve or overfire.

On multiple unit installations, each unit should be checked separately, with and without units operating. Supply pres-

sure must fall within range listed in table 10.

Manifold Pressure Measurement

1 − Remove the threaded plug from the outlet side of the gas valve and install a field−provided barbed fitting.

Connect to a manometer to measure manifold pressure.

2 − Start unit and allow 5 minutes for unit to reach steady state.

3 − While waiting for the unit to stabilize, observe the flame. Flame should be stable and should not lift from burner. Natural gas should burn blue.

4 − After allowing unit to stabilize for 5 minutes, record manifold pressure and compare to value given in table

10.

NOTE − Shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to remove barbed fitting and replace threaded plug.

TABLE 10

Supply Line and Manifold Pressure (inches w.c.)

Unit Fuel

Manifold

Pressure

Line Pressure

All

All

Nat

LP/Propane

3.5

10.0

4.5 − 10.5

11.0 − 13.0

Proper Combustion

Furnace should operate minimum 15 minutes with correct manifold pressure and gas flow rate before checking combustion. Take combustion sample beyond the flue outlet and compare to the tables below.

TABLE 11

EL195

Unit

CO

2

%

For Nat

CO

2

%

For LP

−045

−070

−090

−110

7.2 − 8.2

8.6 − 9.6

−135

The maximum carbon monoxide reading should not exceed 50 ppm.

High Altitude Information

NOTE − In Canada, certification for installations at elevations over 4500 feet (1372 m) is the jurisdiction of local authorities.

Units installed at altitude of 4501 − 10,000 feet (1373 to

3048m) may require a pressure switch change which can

be ordered separately. Table 12 lists conversion kit and

pressure switch requirements at varying altitudes.

The combustion air pressure switch is factory−set and requires no adjustment.

Page 42

EL195

Unit

−045

−070

−090

−110

−135

TABLE 12

LP/Propane Conversion Kit and Pressure Switch Requirements at Varying Altitudes

Natural to

LP/Propane

0 − 7500 ft

(0 − 2286m)

High Altitude

Natural Burner

Orifice Kit

7501 − 10,000 ft

(2286 − 3038m)

High Altitude

LP/Propane Burner

Orifice Kit

7501 − 10,000 ft

(2286 − 3038m)

High Altitude Pressure Switch

*69W73 73W37 *68W68

4501 − 7500 ft

(1373 − 2286m)

No Change

77W43

77W42

77W43

77W42

7501 −10,000 ft

(2286 − 3048m)

74W90

73W22

73W22

73W22

73W22

* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit.

Pressure switch is factory set. No adjustment necessary. All models use the factory−installed pressure switch from 0−4500 feet (0−1370 m).

Testing for Proper Venting and Sufficient Combustion Air for Non−Direct Vent Applications

WARNING

CARBON MONOXIDE POISONING HAZARD!

Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.

The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation.

After the EL195UH gas furnace has been started, the following test should be conducted to ensure proper venting and sufficient combustion air has been provided to the

EL195UH as well as to other gas-fired appliances which are separately vented.

If a EL195UH furnace replaces a Category I furnace which was commonly vented with another gas appliance, the size of the existing vent pipe for that gas appliance must be checked. Without the heat of the original furnace flue products, the existing vent pipe is probably oversized for the single water heater or other appliance. The vent should be checked for proper draw with the remaining appliance.

The test should be conducted while all appliances (both in operation and those not in operation) are connected to the venting system being tested. If the venting system has been installed improperly, or if provisions have not been made for sufficient amounts of combustion air, corrections must be made as outlined in the previous section.

1 − Seal any unused openings in the venting system.

2 − Visually inspect the venting system for proper size and horizontal pitch. Determine there is no blockage or restriction, leakage, corrosion, or other deficiencies which could cause an unsafe condition.

3 − To the extent that it is practical, close all building doors and windows and all doors between the space in which the appliances connected to the venting system are located and other spaces of the building.

4 − Close fireplace dampers.

5 − Turn on clothes dryers and any appliances not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan.

6 − Follow the lighting instruction to place the appliance being inspected into operation. Adjust thermostat so appliance will operate continuously.

7 − Use the flame of match or candle to test for spillage of flue gases at the draft hood relief opening after 5 minutes of main burner operation.

8 − If improper venting is observed during any of the above tests, the venting system must be corrected or sufficient combustion/make-up air must be provided.

The venting system should be re-sized to approach the minimum size as determined by using the appropriate tables in appendix G in the current standards of the National Fuel Gas Code ANSI−Z223.1/NPFA 54 in the U.S.A., and the appropriate Natural Gas and

Propane appliances venting sizing tables in the current standard of the CSA−B149 Natural Gas and Propane Installation Codes in Canada.

9 − After determining that each appliance remaining connected to the common venting system properly vents when tested as indicated in step 3, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous condition of use.

Page 43

Other Unit Adjustments

NOTE − See troubleshooting flow charts if any safety switches are found to be open.

Primary Limit .

The primary limit is located on the heating compartment vestibule panel. This limit is factory set and requires no adjustment.

Flame Rollout Switches (Two)

These manually reset switches are located on the front of the burner box.

Pressure Switch

The pressure switch is located in the heating compartment on the cold end header box. This switch checks for proper combustion air inducer operation before allowing ignition trial. The switch is factory−set and must not be adjusted.

Temperature Rise

After the furnace has been started and supply and return air temperatures have been allowed to stabilize, check the temperature rise. If necessary, adjust the blower speed to maintain the temperature rise within the range shown on the unit nameplate. Increase the blower speed to decrease the temperature. Decrease the blower speed to increase the temperature rise. Failure to adjust the temperature rise may cause erratic limit operation.

Fan Control

Fan On Delay

The heat fan on time of 30 seconds is not adjustable. The cool fan on delay is 2 seconds and not adjustable.

Fan Off Delay

The heat fan off delay (amount of time that the blower operates after the heat demand has been satisfied) may be adjusted by changing the jumper position across the five pins on the integrated control. The unit is shipped with a factory fan off setting of 90 seconds. The fan off delay affects comfort and is adjustable to satisfy individual applications. Adjust the fan off delay to achieve a supply air temperature between 90° and 110°F at the moment that the blower is de−energized. Longer off delay settings provide lower return air temperatures; shorter settings provide higher re-

turn air temperatures. See figure 60.

The cool fan off delay (amount of time that the blower operates after the cool demand has been satisfied) is 45 seconds and not adjustable.

Thermostat Heat Anticipation

Set the heat anticipator setting (if adjustable) according to the amp draw listed on the wiring diagram that is attached to the unit.

Electrical

1 − Check all wiring for loose connections.

2 − Check for the correct voltage at the furnace (furnace operating). Correct voltage is 120VAC + 10%

3 − Check amp−draw on the blower motor with blower access panel in place.

Motor Nameplate__________Actual__________

HEAT FAN-OFF TIME IN SECONDS

NO JUMPER

To adjust fan−off timing, reposition jumper across pins to achieve desired setting.

60 Second off Time

90 Second off Time

120 Second off Time

180 Second off Time

FIGURE 60

Blower Speeds

Follow the steps below to change the blower speeds.

1 − Turn off electrical power to furnace.

2 − Remove blower access panel.

3 − Disconnect existing speed tap at integrated control speed terminal.

NOTE − Termination of any unused motor leads must be insulated.

4 − Place unused blower speed tap on integrated control

PARK" terminal or insulate.

5 − Refer to blower speed selection chart on unit wiring diagram for desired heating or cooling speed. See Blower performance data beginning on the next page.

6 − Connect selected speed tap at integrated control speed terminal.

7 − Resecure blower access panel.

8 − Turn on electrical power to furnace.

9 − Recheck temperature rise.

Electronic Ignition

The integrated control has an added feature of an internal

Watchguard control. The feature serves as an automatic reset device for integrated control lockout caused by ignition failure. This type of lockout is usually due to low gas line pressure. After one hour of continuous thermostat demand for heat, the Watchguard will break and remake thermostat demand to the furnace and automatically reset the integrated control to begin the ignition sequence.

Exhaust and Air Intake Pipe

1 − Check exhaust and air intake connections for tightness and to make sure there is no blockage.

2 − Is pressure switch closed? Obstructed exhaust pipe will cause unit to shut off at pressure switch. Check termination for blockages.

3 − Obstructed pipe or termination may cause rollout switches to open. Reset manual flame rollout switches on burner box assembly if necessary.

Page 44

BLOWER DATA

EL195UH045P24B PERFORMANCE (Less Filter)

External

Static

Pressure in. w.g.

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

Air Volume / Watts at Various Blower Speeds

High

Medium-

High

Medium-

Low

Low cfm Watts cfm Watts cfm Watts cfm Watts

1140 455 920 365 765 295 710 265

1135 445 900 360 765 290 690 255

1125 430 895 350 755 285 680 255

1090 415 870 340 725 280 660 250

1065 405 870 325 715 270 635 245

1020 390 825 315 675 260 605 235

945 365 780 300 640 250 555 225

910 350 740 295 585 240 505 220

790 325 670 275 510 225 455 205

735 310 575 255 460 220 390 195

EL195UH045P36B PERFORMANCE (Less Filter)

External

Static

Pressure in. w.g.

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

Air Volume / Watts at Various Blower Speeds

High

Medium-

High

Medium-

Low

Low cfm Watts cfm Watts cfm Watts cfm Watts

1605 700 1370 590 1160 475 1010 400

1600 680 1355 565 1155 465 1015 390

1550 645 1330 540 1150 445 1000 380

1480 620 1295 520 1140 430 975 365

1425 590 1280 490 1105 415 975 345

1355 565 1190 460 1085 395 940 335

1320 545 1165 435 1030 380 900 315

1225 500 1110 425 980 355 855 310

1135 480 1050 395 920 330 780 280

1025 445 950 360 795 295 700 255

EL195UH070P36B PERFORMANCE (Less Filter)

External

Static

Pressure in. w.g.

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

Air Volume / Watts at Various Blower Speeds

High

Medium-

High

Medium-

Low

Low cfm Watts cfm Watts cfm Watts cfm Watts

1585 685 1340 585 1095 480 880 380

1560 665 1320 565 1085 470 885 375

1515 630 1300 540 1080 460 880 370

1465 590 1275 520 1065 440 890 360

1410 570 1235 490 1050 420 875 350

1345 540 1195 470 1020 400 840 335

1275 510 1140 440 975 365 830 315

1195 485 1090 410 930 355 780 290

1105 460 995 380 850 325 730 275

985 420 890 345 770 300 650 255

EL195UH070P48B PERFORMANCE (Less Filter)

External

Static

Pressure in. w.g.

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

Air Volume / Watts at Various Blower Speeds

High

Medium-

High

Medium-

Low

Low cfm Watts cfm Watts cfm Watts cfm Watts

2015 1005 1950 840 1870 730 1675 630

1930 985 1915 830 1805 720 1650 615

1880 965 1840 805 1760 695 1620 600

1815 945 1775 790 1700 675 1560 580

1740 925 1700 770 1630 655 1515 565

1680 895 1625 750 1545 635 1455 545

1575 880 1555 720 1485 620 1380 530

1500 860 1450 700 1380 600 1310 515

1400 825 1380 680 1315 580 1230 495

1290 805 1270 655 1235 560 1145 480

EL195UH090P36C PERFORMANCE (Less Filter)

External

Static

Pressure in. w.g.

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

Air Volume / Watts at Various Blower Speeds

High

Medium-

High

Medium-

Low

Low cfm Watts cfm Watts cfm Watts cfm Watts

1630 715 1345 590 1090 475 885 385

1615 700 1320 580 1070 465 890 380

1580 675 1305 570 1070 455 890 370

1525 620 1295 535 1060 435 890 360

1480 615 1275 515 1055 430 885 350

1415 565 1220 485 1030 410 860 330

1350 535 1175 450 1005 390 835 310

1260 505 1115 415 955 360 785 290

1190 480 1010 380 880 325 740 285

1060 435 930 360 795 295 655 250

EL195UH090P48C PERFORMANCE (Less Filter)

External

Static

Pressure in. w.g.

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

Air Volume / Watts at Various Blower Speeds

High

Medium-

High

Medium-

Low

Low cfm Watts cfm Watts cfm Watts cfm Watts

2140 880 1895 780 1590 645 1350 550

2110 850 1880 760 1585 635 1360 545

2060 810 1835 725 1580 620 1360 520

1990 765 1805 690 1550 585 1365 495

1925 750 1755 655 1510 545 1330 470

1830 700 1680 610 1455 525 1285 450

1720 645 1610 575 1390 480 1230 415

1600 615 1525 535 1300 465 1165 390

1455 560 1410 495 1195 430 1035 365

1300 515 1305 465 1100 390 900 320

EL195UH110P48C PERFORMANCE (Less Filter)

External

Static

Pressure in. w.g.

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

Air Volume / Watts at Various Blower Speeds

High

Medium-

High

Medium-

Low

Low cfm Watts cfm Watts cfm Watts cfm Watts

2000 910 1675 765 1360 635 1185 525

1980 895 1650 745 1370 610 1180 505

1935 855 1600 710 1400 590 1170 485

1875 830 1560 680 1370 570 1160 490

1800 785 1490 655 1325 545 1120 455

1725 720 1400 610 1295 515 1080 435

1630 685 1335 585 1185 480 1030 410

1530 665 1290 525 1100 435 940 385

1410 610 1190 485 985 400 790 365

1245 560 1000 430 925 380 715 315

Page 45

BLOWER DATA

EL195UH090P60C PERFORMANCE (Less Filter)

Air Volume / Watts at Different Blower Speeds

External

Static

Pressure in. w.g.

0.00

0.10

Bottom Return Air, Side Return Air with Optional Return

Air Base, Return Air from Both Sides or Return Air from

Bottom and One Side.

High Medium-High Medium-Low Low

Single Side Return Air − Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. air filter in order to maintain proper air velocity.

High Medium-High Medium-Low Low cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts

2445 1290 2235 1000 1875 840 1495 660 2445 1355 2180 1020 1785 850 1400 665

2430 1270 2220 985 1860 830 1500 650 2425 1335 2160 1010 1775 840 1405 655

0.20

0.30

0.40

0.50

0.60

0.70

0.80

2370 1260 2170

2290 1220 2110

2200 1190 2055

960

935

900

1875

1855

1835

805

785

765

1515

1545

1560

645

640

625

2390 1310 2135

2305 1270 2080

2230 1240 2015

985

960

925

1790

1805

1775

825

805

780

1435

1455

1460

645

640

630

2095 1155 1970 865 1785 735 1520 610 2150 1215 1965 900 1745 755 1460 620

2010 1145 1920 850 1725 715 1495 600 2055 1170 1890 865 1695 730 1440 605

1960 1120 1835 815 1655 690 1455 575 1955 1145 1805 840 1640 705 1415 590

1845 1080 1720 785 1570 665 1390 550 1825 1095 1705 815 1565 675 1360 565

0.90

1725 1040 1620 755 1490 645 1305 530 1715 1065 1590 775 1470 645 1290 540

EL195UH110P60C PERFORMANCE (Less Filter)

Air Volume / Watts at Different Blower Speeds

External

Static

Pressure in. w.g.

0.00

0.10

Bottom Return Air, Side Return Air with Optional Return

Air Base, Return Air from Both Sides or Return Air from

Bottom and One Side.

High Medium-High Medium-Low Low

Single Side Return Air − Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. air filter in order to maintain proper air velocity.

High Medium-High Medium-Low Low cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts

2485 1515 2090 1070 1835 865 1380 660 2400 1475 2100 1075 1755 870 1320 655

2460 1475 2075 1040 1810 835 1390 650 2370 1440 2090 1060 1735 850 1330 645

0.20

0.30

0.40

0.50

0.60

0.70

2405 1445 2040

2335 1375 1990

995

980

1790

1760

820

790

1405

1460

650

635

2320 1405 2060 1050

2235 1350 2040 1030

1720

1725

835

825

1340

1350

650

645

2215 1355 1935 940 1740 775 1410 630 2165 1330 1975 970 1700 815 1330 632

2185 1310 1865 895 1680 750 1410 625 2040 1290 1920 945 1700 790 1325 620

2060 1270 1805 870 1630 720 1405 610 1960 1260 1845 910 1635 770 1340 620

1945 1235 1700 840 1605 700 1380 590 1865 1215 1750 890 1575 730 1295 600

0.80

0.90

1845 1210 1605 810 1505 670 1305 570 1715 1175 1590 840 1505 710 1280 590

1730 1150 1570 790 1470 660 1250 540 1630 1135 1490 685 1460 685 1235 565

EL195UH135P60D PERFORMANCE (Less Filter)

Air Volume / Watts at Different Blower Speeds

External

Static

Pressure in. w.g.

0.00

0.10

Bottom Return Air, Side Return Air with Optional Return

Air Base, Return Air from Both Sides or Return Air from

Bottom and One Side.

High Medium-High Medium-Low Low

Single Side Return Air − Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in. air filter in order to maintain proper air velocity.

High Medium-High Medium-Low Low cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts

2595 1515 2245 2015 1780 890 1365 700 2540 1500 2185 1095 1715 880 1350 700

2570 1490 2235 1095 1765 875 1370 665 2525 1480 2165 1085 1725 870 1335 675

0.20

0.30

0.40

0.50

0.60

0.70

2440 1465 2135 1075 1745

2340 1405 2075 1060 1755

2255 1370 1995 1005 1680

865

845

825

1395

1365

1370

660

660

660

2440 1445 2120 1090

2345 1400 2060 1060

2220 1345 1955 1015

1725

1715

1685

865

850

820

1345

1345

1370

675

670

660

2095 1320 1915 960 1650 805 1335 650 2100 1310 1895 985 1620 805 1320 650

1995 1270 1840 935 1595 775 1320 630 2005 1285 1780 945 1605 790 1285 635

1900 1225 1755 905 1540 755 1270 615 1845 1235 1700 910 1510 740 1225 610

0.80

0.90

1740 1180 1650 875 1430 725 1190 590 1745 1185 1645 880 1450 720 1175 595

1580 1140 1535 840 1350 695 1145 570 1655 1160 1545 840 1380 705 1135 575

Page 46

Service

WARNING

ELECTRICAL SHOCK, FIRE,

OR EXPLOSION HAZARD.

Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage.

Improper servicing could result in dangerous operation, serious injury, death, or property damage.

Before servicing, disconnect all electrical power to furnace.

When servicing controls, label all wires prior to disconnecting. Take care to reconnect wires correctly.

Verify proper operation after servicing.

At the beginning of each heating season, system should be checked as follows by a qualified service technician:

Blower

Check the blower wheel for debris and clean if necessary.

The blower motors are prelubricated for extended bearing life. No further lubrication is needed.

WARNING

The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.

Filters

All air filters are installed external to the unit. Filters should be inspected monthly. Clean or replace the filters when

necessary to ensure proper furnace operation. Table 1

lists recommended filter sizes.

Exhaust and air intake pipes

Check the exhaust and air intake pipes and all connections for tightness and to make sure there is no blockage.

NOTE − After any heavy snow, ice or frozen fog event the furnace vent pipes may become restricted. Always check the vent system and remove any snow or ice that may be obstructing the plastic intake or exhaust pipes.

Electrical

1 − Check all wiring for loose connections.

2 − Check for the correct voltage at the furnace (furnace operating).

3 − Check amp−draw on the blower motor.

Motor Nameplate__________Actual__________

Winterizing and Condensate Trap Care

1 − Turn off power to the furnace.

2 − Have a shallow pan ready to empty condensate water.

3 − Remove the clean out cap from the condensate trap and empty water. Inspect the trap then reinstall the clean out cap.

Cleaning Heat Exchanger

If cleaning the heat exchanger becomes necessary, follow the below procedures and refer to figure 1 when disassembling unit. Use papers or protective covering in front of furnace while removing heat exchanger assembly.

1 − Turn off electrical and gas supplies to the furnace.

2 − Remove the furnace access panels.

3 − Disconnect the 2 wires from the gas valve.

4 − Remove gas supply line connected to gas valve. Remove the burner box cover (if equipped) and remove gas valve/manifold assembly.

5 − Remove sensor wire from sensor. Disconnect 2-pin plug from the ignitor.

6 − Disconnect wires from flame roll−out switches.

7 − Disconnect combustion air intake pipe. It may be necessary to cut the existing pipe to remove burner box assembly.

8 − Remove four burner box screws at the vestibule panel and remove burner box. Set burner box assembly aside.

NOTE − If necessary, clean burners at this time. Follow procedures outlined in Burner Cleaning section.

9 − Loosen the clamps to the flexible exhaust coupling.

10 − Disconnect condensate drain line from the cold end header box.

11 − Disconnect condensate drain tubing from flue collar.

Remove screws that secures the flue collar into place.

Remove flue collar. It may be necessary to cut the exiting exhaust pipe for removal of the fitting.

12 − Mark and disconnect all combustion air pressure tubing from cold end header collector box.

13 − Mark and remove wires from pressure switch assembly. Remove the assembly. Keep tubing attached to pressure switches.

14 − Disconnect the plug from the combustion air inducer.

Remove two screws which secure combustion air inducer to collector box. Remove combustion air inducer assembly. Remove ground wire from vest panel.

15 − Disconnect the condensate drain line.

16 − Remove cold end header box.

17 − Remove electrical junction box from the side of the furnace.

18 − Mark and disconnect any remaining wiring to heating compartment components. Disengage strain relief bushing and pull wiring and bushing through the hole in the blower deck.

19 − Remove the primary limit from the vestibule panel.

20 − Remove two screws from the front cabinet flange at the blower deck. Spread cabinet sides slightly to allow clearance for removal of heat exchanger.

Page 47

21 − Remove screws along vestibule sides and bottom which secure vestibule panel and heat exchanger assembly to cabinet. Remove two screws from blower rail which secure bottom heat exchanger flange. Remove heat exchanger from furnace cabinet.

22 − Back wash heat exchanger with soapy water solution or steam.

If steam is used it must be below 275°F

(135°C) .

23 − Thoroughly rinse and drain the heat exchanger. Soap solutions can be corrosive. Take care to rinse entire assembly.

24 − Reinstall heat exchanger into cabinet making sure that the clamshells of the heat exchanger assembly is engaged properly into the support bracket on the blower deck. Remove the indoor blower to view this area through the blower opening.

25 − Re-secure the supporting screws along the vestibule sides and bottom to the cabinet.

26 − Reinstall cabinet screws on front flange at blower deck.

27 − Reinstall the primary limit on the vestibule panel.

28 − Route heating component wiring through hole in blower deck and reinsert strain relief bushing.

29 − Reinstall electrical junction box.

30 − Reinstall the cold end header box.

31 − Reinstall the combustion air inducer. Reconnect the plug to the wire harness.

32 − Reinstall pressure switches and reconnect pressure switch wiring.

33 − Carefully connect combustion air pressure switch tubing from pressure switches to proper ports on cold end header collector box.

34 − Reconnect condensate drain line to the cold end header box.

35 − Use securing screws to reinstall flue collar to the top cap on the furnace. Reconnect exhaust piping and exhaust drain tubing.

36 − Replace flexible exhaust adapter on combustion air inducer and flue collar. Secure using two existing hose clamps.

37 − Reinstall burner box assembly in vestibule area. Secure burner box assembly to vestibule panel using four existing screws. Make sure burners line up in center of burner ports

38 − Reconnect flame roll−out switch wires.

39 − Reconnect sensor wire and reconnect 2−pin plug from ignitor.

40 − Reinstall gas valve manifold assembly. Reconnect gas supply line to gas valve.

41 − Reconnect the combustion air intake pipe.

42 − Reinstall burner box cover.

43 − Reconnect wires to gas valve.

44 − Replace the blower compartment access panel.

45 − Reconnect gas supply piping. Turn on power and gas supply to unit.

46− Follow lighting instructions on unit nameplate to light and operate furnace for 5 minutes to ensure the furnace is operating properly.

47− Check all piping connections, factory and field, for gas leaks. Use a leak detecting solution or other preferred means.

48− Replace heating compartment access panel.

CAUTION

Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly after leak test has been completed. Do not use matches, candles, flame or other sources of ignition to check for gas leaks.

Cleaning the Burner Assembly (if needed)

1 − Turn off electrical and gas power supplies to furnace.

Remove upper and lower furnace access panels.

2 − Disconnect the wires from the gas valve.

3 − Remove the burner box cover (if equipped).

4 − Disconnect the gas supply line from the gas valve. Remove gas valve/manifold assembly.

5 − Mark and disconnect sensor wire from the sensor. Disconnect wires from flame rollout switches.

6 − Disconnect combustion air intake pipe. It may be necessary to cut the existing pipe to remove burner box assembly.

7 − Remove four screws which secure burner box assembly to vest panel. Remove burner box from the unit.

8 − Use the soft brush attachment on a vacuum cleaner to gently clean the face of the burners. Visually inspect the inside of the burners and crossovers for any blockage caused by foreign matter. Remove any blockage.

9 − Reinstall the burner box assembly using the existing four screws. Make sure that the burners line up in the center of the burner ports.

10 − Reconnect the sensor wire and reconnect the 2−pin plug to the ignitor wiring harness. Reconnect wires to flame rollout switches.

11 − Reinstall the gas valve manifold assembly. Reconnect the gas supply line to the gas valve. Reinstall the burner box cover.

12 − Reconnect wires to gas valve.

13 − Replace the blower compartment access panel.

14 − Refer to instruction on verifying gas and electrical connections when re−establishing supplies.

15 − Follow lighting instructions to light and operate furnace for 5 minutes to ensure that heat exchanger is clean and dry and that furnace is operating properly.

16 − Replace heating compartment access panel.

Page 48

Planned Service

A service technician should check the following items during an annual inspection. Power to the unit must be shut off for safety.

Fresh air grilles and louvers (on the unit and in the room where the furnace is installed) − Must be open and unobstructed to provide combustion air.

Burners − Must be inspected for rust, dirt, or signs of water.

Vent pipe − Must be inspected for signs of water, cracked, damaged or sagging pipe, or disconnected joints.

Unit appearance − Must be inspected for rust, dirt, signs of water, burnt or damaged wires, or components.

Blower access door − Must be properly in place and provide a seal between the return air and the room where the furnace is installed.

Ignition Control Board Diagnostic Codes

RED LED

Flash Code

Off

Heartbeat 1

3

4

1

2

5

6

7

11

12

13

8

9

10

Note 1

Note

Note

Return air duct − Must be properly attached and provide an air seal to the unit.

Operating performance − Unit must be observed during operation to monitor proper performance of the unit and the vent system.

Combustion gases − Flue products must be analyzed and compared to the unit specifications.

Problems detected during the inspection may make it necessary to temporarily shut down the furnace until the items can be repaired or replaced.

Instruct the homeowners to pay attention to their furnace.

Situations can arise between annual furnace inspections that may result in unsafe operation. For instance, items innocently stored next to the furnace may obstruct the combustion air supply. This could cause incomplete combustion and the production of carbon monoxide gas.

Diagnostic Codes / Status of Furnace

No power to control or board fault detected

Control powered − displayed during all modes of operation if no errors are detected

Reverse Line Voltage Polarity

Improper Earth Ground

Burner failed to light, or lost flame during heat demand

Low Flame Signal − check flame sensor

Watchguard − burner failed to light, exceeded maximum number of retries or recycles.

Ignitor Circuit Failure − not available on this control

Primary or Secondary Limit Open or Watchguard Mode − Limit Switch Open longer than 3 minutes

Rollout Switch Open

Pressure Switch failed to close or opened during heat demand

Watchguard − Pressure Switch opened 5 times during one heat demand

Pressure Switch stuck closed prior to activation of combustion air inducer

Flame Sensed without gas valve energized

Low Line Voltage

Notes

A "Heartbeat" is indicated by a "Slow Flash" − 1 sec on 1 sec off, repeating

Error codes are indicated by a "Rapid Flash" − the LED flashes X times at 1/2 sec on 1/2 sec off, remains off for 3 sec, then repeats

Last 10 error codes are stored in memory − To recall, press and release button, most recent will be displayed first, LED off for 3 sec, then next error code is displayed, etc. To clear error codes, depress and hold button longer than 5 seconds.

Page 49

Troubleshooting: Heating Sequence of Operation

HEATING SEQUENCE OF OPERATION

ABNORMAL HEATING MODE

NORMAL HEATING MODE

POWER ON

CONTROL SELF−CHECK OKAY?

NO

GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.

INDOOR BLOWER DELAY OFF.

LED SLOW FLASH

(RESET CONTROL BY TURNING MAIN POWER OFF.)

YES

IS POLARITY CORRECT?

YES

IS THERE A PROPER GROUND?

YES

NO

NO

LED FLASHES CODE 1 − POLARITY REVERSED.

LED FLASHES CODE 2 − IMPROPER GROUND.

NO

IS VOLTAGE

ABOVE 70 VOLTS?

LED FLASHES CODE 13 − LOW LINE VOLTAGE.

CONTROL WILL NOT RESPOND TO A CALL FOR

HEATING UNTIL VOLTAGE RISES ABOVE 75 VOLTS.

YES

ROLLOUT SWITCH CLOSED?

YES

NO

LED FLASHES CODE 8 − ROLLOUT SWITCH OPEN.

GAS VALVE OFF. COMBUSTION AIR INDUCER ON.

INDOOR BLOWER ON.

SEQUENCE HOLDS UNTIL ROLLOUT SWITCH CLOSES

AND POWER IS RESET OR T’STAT IS INTERRUPTED

FOR MINIMUM OF 1 SECOND.

NO

LED FLASHES CODE 12 − FLAME SENSED

WITHOUT GAS VALVE ENERGIZED.

GAS VALVE OFF. COMBUSTION AIR INDUCER ON.

INDOOR BLOWER ON HEATING SPEED.

NO

BURNER OFF?

( Flame sensed without gas valve energized )

YES

NORMAL OPERATION:

LED SLOW FLASH

YES

THERMOSTAT CALLS FOR HEAT:

LED SLOW FLASH

YES

PRIMARY LIMIT SWITCH. CLOSED?

YES

IS COMBUSTION AIR

PRESSURE SWITCH OPEN?

YES

IS COMBUSTION AIR INDUCER

ENERGIZED?

YES

HAS COMBUSTION AIR PRESSURE

SWITCH CLOSED IN 2.5 MINUTES?

YES

CONTINUED NEXT PAGE

NO

NO

LED FLASHES CODE 7 − PRIMARY LMIT

OPEN. COMBUSTION AIR INDUCER

OFF.INDOOR BLOWER ON

LED FLASHES CODE 11 − PRESSURE

SWITCH CLOSED.

GAS VALVE OFF COMBUSTION AIR

INDUCER OFF. INDOOR BLOWER

OFF WITH DELAY.

(Sequence holds until pressure switch opens or thermostat resets control.)

NO

LED FLASHES CODE 9 − PRESSURE SWITCH FAILED

TO CLOSE OR OPENED DURING HEAT DEMAND.

PRESSURE SWITCH IS IN WATCHGUARD MODE. GAS

VALVE OFF. COMBUSTION AIR INDUCER OFF.

INDOOR BLOWER OFF WITH DELAY. IS 5-MINUTE

RESET PERIOD COMPLETE?

YES

Page 50

Troubleshooting: Heating Sequence of Operation (Continued)

HEATING SEQUENCE CONTINUED

NORMAL HEATING MODE ABNORMAL HEATING MODE

15-SECOND COMBUSTION AIR INDUCER PREPURGE

INITIATED BY CLOSED PRESSURE SWITCH.

YES

NO

IGNITOR WARM-UP −− 20 SECONDS.

YES

4-SECOND TRIAL FOR IGNITION.

GAS VALVE OPENS. IGNITOR ENERGIZED FOR

FIRST 3 SECONDS OF THE TRIAL.

YES

FLAME STABILIZATION PERIOD.

4 SECONDS

IS VOLTAGE ABOVE 70 VOLTS?

YES

NO

LED FLASHES CODE 13 −

LOW LINE VOLTAGE.

ONCE VOLTAGE IS ABOVE

75 VOLTS, HEATING

SEQUENCE RESTARTS.

NO

GAS VALVE OFF. COMBUSTION AIR INDUCER ON.

INDOOR BLOWER OFF.

HAS CONTROL FAILED TO SENSE FLAME FOR

FIVE CONSECUTIVE TRIES DURING A SINGLE

HEAT DEMAND?

NO

YES

FLAME RECTIFICATION CURRENT

CHECK. CAN FLAME BE PROVEN WITHIN

4 SECONDS AFTER GAS VALVE OPENS?

(0.5 microamps)

YES

LED SIGNAL WATCHGUARD FAILURE CODE

WATCHGUARD MODE. GAS VALVE OFF.

COMBUSTION AIR INDUCER OFF.

INDOOR BLOWER OFF WITH DELAY

IS 60-MINUTE RESET PERIOD COMPLETE?

YES

FLAME PRESENT?

NO

HAS CONTROL RESET IGNITION

SEQUENCE FOUR TIMES?

NO

YES

YES

FLAME SIGNAL 1.5 MICROAMPS OR GREATER?

YES

INDOOR BLOWER ON

AFTER 30−SECOND DELAY

YES

PRIMARY LIMIT SWITCH CLOSED?

YES

ROLLOUT SWITCH CLOSED?

YES

COMBUSTION AIR PRESSURE

SWITCH CLOSED?

YES

NO

LED FLASHES CODE 4 − LOW FLAME

SIGNAL.

(Does not affect operation of control)

NO

LED FLASHES CODE 7 − PRIMARY LIMIT OPEN

GAS VALVE DE−ENERGIZED.

COMBUSTION AIR INDUCER DE−ENERGIZED.

INDOOR BLOWER ON UNTIL SWITCH CLOSES.

LIMIT SWITCH CLOSED?

YES

YES

HAS PRIMARY LIMIT RESET

TIME EXCEEDED 3 MINUTES?

LED FLASHES CODE

7 − PRIMARY LIMIT

OPEN. GAS VALVE,

COMB. AIR INDUCER

AND INDOOR BLOW-

ER OFF. LEDs SIG-

NAL LIMIT SWITCH

OPEN UNTIL MAIN

POWER IS

INTERRUPTED OR

T’STAT IS CYCLED

OFF/ON FOR 1 SEC.

MINIMUM. 60−MINUTE

WATCHGUARD PE-

RIOD STARTS AT

TIME LIMIT CLOSES.

IS 60−MIN. PERIOD

COMPLETE?

NO

NO

LED FLASHES CODE 8 − ROLLOT SWITCH OPEN.

GAS VALVE POWER OFF. COMBUSTION AIR INDUCER POWER

ON. INDOOR BLOWER ON SEQUENCE HOLDS UNTIL ROLLOUT

SWITCH IS RESET AND MAIN POWER IS INTERRUPTED OR

THERMOSTAT IS CYCLED OFF/ON FOR 1 SEC. MINIMUM.

NO

THERMOSTAT DEMAND SATISFIED.

YES

LED SLOW FLASH.

YES

COMB. AIR INDUCER CONTINUES 5-SECOND

POST PURGE AFTER T’STAT DEMAND IS SATISFIED.

INDOOR AIR BLOWER COMPLETES SELECTED OFF"

DELAY BEFORE SHUTTING OFF.

HAS PRESSURE SWITCH OPENED 5 TIMES

IN THE SAME HEAT DEMAND?

NO YES

GAS VALVE DE−ENERGIZED. COMBUSTION AIR

INDUCER ON. INDOOR BLOWER OFF WITH

DELAY. HAS CAB PRESSURE SWITCH CLOSED

WITHIN 2.5 MINUTES?

NO

5-MINUTE PRESSURE SWITCH

WATCHGUARD MODE.

YES

LED FLASHES

CODE 10

1 HR PRESSURE

SWITCH

WATCHGUARD

MODE

Page 51

Troubleshooting: Cooling Sequence of Operation

COOLING SEQUENCE OF OPERATION

NORMAL COOLING MODE

POWER ON

ABNORMAL COOLING MODE

IGNITION CONTROL MAIN POWER ON.

CONTROL SELF DIAGNOSTIC CHECK.

IS CONTROL OPERATING NORMALLY?

YES

IS THERE A PROPER GROUND?

YES

IS POLARITY CORRECT?

YES

IS VOLTAGE

ABOVE 70 VOLTS?

YES

NO

ROLLOUT SWITCH MONITORED CONTINUOUSLY.

IS ROLLOUT SWITCH CLOSED?

YES

NO

GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.

INDOOR BLOWER OFF WITH NORMAL DELAY.

SIGNAL CIRCUIT BOARD FAILURE AT LED.

INTERRUPT MAIN POWER TO RESET CONTROL.

NO

NO

LED FLASHES CODE 2 IMPROPER GROUND

CONTROL WILL CONTINUE TO CALL FOR COOLING

IN THIS CONDITION.

LED FLASHES CODE 1 POLARITY REVERSED

CONTROL WILL CONTINUE TO CALL FOR COOLING IN

THIS CONDITION.

NO

LED FLASHES CODE 13 LOW VOLTAGE. CONTROL

WILL CONTINUE TO CALL FOR COOLING

IN THIS CONDITION.

LED FLASHES CODE 8 ROLLOUT SWITCH OPEN. GAS

VALVE OFF. COMBUSTION AIR INDUCER ON. INDOOR

BLOWER ON. SEQUENCE HOLDS UNTIL ROLLOUT SWITCH

CLOSES AND MAIN POWER IS INTERRUPTED OR

THERMOSTAT IS CYCLED OFF/ON FOR 1 SEC. MINIMUM.

LED: SLOW FLASH RATE REMAINS UNCHANGED

THROUGHOUT COOLING CYCLE.

THERMOSTAT CALLS FOR COOLING.

COMPRESSOR CONTACTOR AND SYSTEM FAN

ENERGIZED WITH 2-SECOND DELAY

(COOLING SPEED). EAC TERM. ENERGIZED.

THERMOSTAT OPENS.

COMPRESSOR OFF.

SYSTEM FAN AND EAC TERM. OFF

WITH 45-SECOND DELAY.

Page 52

Troubleshooting: Continuous Fan Sequence of Operation

CONTINUOUS FAN SEQUENCE OF OPERATION

LED: SLOW FLASH RATE REMAINS

UNCHANGED THROUGHOUT SEQUENCE.

MANUAL FAN SELECTION MADE AT THERMOSTAT.

CONTROL (G) ENERGIZES SYSTEM FAN AT FAN

SPEED. EAC TERMINAL IS ENERGIZED.

THERMOSTAT CALLS FOR HEAT (W).

NO YES

THERMOSTAT CALLS FOR COOLING.

YES

SYSTEM FAN SWITCHED TO COOL SPEED.

EAC TERM. REMAINS ON.

NO

SYSTEM FAN CONTINUES FAN SPEED WITHOUT

INTERRUPTION. EAC TERMINAL REMAIN ON.

HUM TERMINAL IS ENERGIZED WITH COMBUSTION

AIR BLOWER.

THERMOSTAT OPENS.

MANUAL FAN SELECTION MADE AT THERMOSTAT.

CONTROL (G) ENERGIZES SYSTEM FAN AT FAN

SPEED. EAC TERM. ENERGIZED.

SYSTEM FAN SWITCHES TO HEAT SPEAD AFTER 30

SECOND DELAY. EAC AND HUM TERMINAL REMAIN ON.

THERMOSTAT OPENS.

HUM. TERMINAL OFF AFTER POST PURGE

BY COMBUSTION AIR BLOWER. SYTEM FAN

SWITCHES TO FAN SPEED AFTER BLOWER

OFF DELAY. EAC CONTINUES WITHOUT

INTERRUPTION.

Repair Parts List

The following repair parts are available through Lennox dealers. When ordering parts, include the complete furnace model number listed on the CSA nameplate −− Example: EL195UH045P24B−01. All service must be performed by a licensed professional installer (or equivalent), service agency, or gas supplier.

Cabinet Parts

Outer access panel

Blower access panel

Top Cap

Control Panel Parts

Transformer

Integrated control board

Door interlock switch

Blower Parts

Blower wheel

Motor

Motor mounting frame

Motor capacitor

Blower housing cutoff plate

Heating Parts

Flame Sensor

Heat exchanger assembly

Gas manifold

Combustion air inducer

Gas valve

Main burner cluster

Main burner orifices

Pressure switch

Ignitor

Primary limit control

Flame rollout switches

Page 53

Start−Up & Performance Check List

UNIT SET UP

Furnace:

Model Number_______________

Serial Number_________________

2

2

Line Voltage

4

1 GAS SUPPLY

Natural Gas LP Propane Gas

Piping Connections Tight

Leak Tested

Supply Line Pressure W.C.________

SUPPLY

AIR

1

Gas Supply Pressure

1

3

Flter

RETURN AIR

3

DUCT SYSTEM

SUPPLY AIR DUCT

Sealed

Insulated (if necessary)

2 INTAKE / EXHAUST PIPE

All Joints Primed and Glued

Terminations Installed Properly

Horizontal Pipes Sloped (if applicable)

Condensate Trap Primed / Line Sloped

Pipes Supported

Heat Cable Installed and Operable (if applicable)

RETURN DUCT

Sealed

Filter Installed and Clean

4

Grilles Unobstructed

VOLTAGE CHECK

Supply Voltage _____

Electrical Connections Tight

Page 54

1

HEATING MODE

GAS MANIFOLD PRESSURE W.C._____

UNIT OPERATION

3

COOLING MODE

INDOOR BLOWER AMPS______

2 COMBUSTION SAMPLE CO

2

%

______

CO PPM_______

3

INDOOR BLOWER AMPS______

4

TEMPERATURE RISE

Supply Duct Temperature ________

Return Duct Temperature _ _____

Temperature Rise = ________

5

TOTAL EXTERNAL STATIC

Supply External Static _______

Return External Static + ______

Total External Static = _______

6

CONDENSATE LINE

Leak Free

7 VENT PIPE

Leak Free

Combustion CO

2

4

TEMPERATURE DROP

Return Duct Temperature _________

Supply Duct Temperature _ _______

Temperature Drop = _________

5 TOTAL EXTERNAL STATIC (dry coil)

Supply External Static _______

Return External Static + ______

Total External Static = _______

8 DRAIN LINE

Leak Free

9

THERMOSTAT

Adjusted and Programmed

Explained Operation to Owner

2

7

SUPPLY

AIR

Thermostat

9

Blower Motor Amps

3

6

8

Gas Manifold Pressure

1

Temperatures

4

Duct Static

5

RETURN AIR

Contractor’s: Name_________________________Telephone_____________Checklist Completed____________________

Job Address_____−________________________________Technician’s Name___________________________________

Page 55

Requirements for Commonwealth of Massachusetts

Modifications to NFPA−54, Chapter 10

Revise NFPA−54 section 10.8.3 to add the following requirements:

For all side wall, horizontally vented, gas−fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above the finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

1 − INSTALLATION OF CARBON MONOXIDE DETEC-

TORS. At the time of installation of the side wall, horizontally vented, gas−fueled equipment, the installing plumber or gasfitter shall observe that a hard−wired carbon monoxide detector with an alarm and battery backup is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery−operated or hard−wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall, horizontally vented, gas−fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard−wired carbon monoxide detectors.

a − In the event that the side wall, horizontally vented, gas−fueled equipment is installed in a crawl space or an attic, the hard−wired carbon monoxide detector with alarm and battery back−up may be installed on the next adjacent floor level.

b − In the event that the requirements of this subdivision cannot be met at the time of completion of installation, the owner shall have a period of thirty

(30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery−operated carbon monoxide detector with an alarm shall be installed.

2 − APPROVED CARBON MONOXIDE DETECTORS.

Each carbon monoxide detector as required in accordance with the above provisions shall comply with

NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

3 − SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented, gas−fueled heating appliance or equipment. The sign shall read, in print size no less than one−half (1/2) inch in size, GAS VENT DIRECT-

LY BELOW. KEEP CLEAR OF ALL OBSTRUC-

TIONS."

4 − INSPECTION. The state or local gas inspector of the side wall, horizontally vented, gas−fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.

EXEMPTIONS: The following equipment is exempt from 24 CMR 5.08(2)(a) 1 through 4:

1 − The equipment listed in Chapter 10 entitled Equipment Not Required to Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and

2 − Product Approved side wall, horizontally vented, gas− fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS −

GAS EQUIPMENT VENTING SYSTEM PROVIDED.

When the manufacturer of Product Approved side wall, horizontally vented, gas−fueled equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1 − Detailed instructions for the installation of the venting system design or the venting system components: and

2 − A complete parts list for the venting system design or venting system.

MANUFACTURER REQUIREMENTS −

GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.

When the manufacturer of Product Approved side wall, horizontally vented, gas−fueled equipment does not provide the parts for venting the flue gases, but identifies special venting systems," the following requirements shall be satisfied by the manufacturer:

1 − The referenced special venting system" instructions shall be included with the appliance or equipment installation instructions; and

2 The special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product

Approved side wall, horizontally vented, gas−fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

Page 56

advertisement

Related manuals

Download PDF

advertisement