Electronic Automation Pvt MPR-E1 V2.0 Instruction Manual

Add to My manuals
2 Pages

advertisement

Electronic Automation Pvt MPR-E1 V2.0 Instruction Manual | Manualzz

Instruction Manual

Safety Precautions

Read and follow all the safety precautions and instructions before installing and working with the equipment.

MPR-E1 V2.0

Motor Protection Relay

EAPL

Introduction

Self powered device, Displays 3 Phase voltage, current and frequency during healthy condition.

Monitors and control Phase failure, Phase unbalance, Phase Reversal, over voltage, under voltage, over current, under current, over frequency, under frequency and Earth Leakage in 3 Phase 4 wire system.

PARAMETERS

IN VOLTAGE,

CURRENT AND

FREQUENCY

R-V

Y-V

B-V

RY-V

YB-V

BR-V

R-A

Y-A

Box Accessories

B-A

Hz

One (1) MPR-E1 V2.0 Monitoring Device

One (1) Instruction Manual

One (1) RC Filter

!

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

• Apply appropriate personal protective equipment(PPE) and follow safety work practices

• Only qualified electrical workers should install this equipment. Such work should be performed only after reading this entire set of instructions.

• If the equipment is not used in the manner specified by the manufacturer, the protection provided by the equipment may be impaired.

• NEVER work alone.

• Turn OFF all power supplying the monitoring device and the equipment in which it is installed before working on it.

• The successful operation of this equipment depends upon proper handling, installation and operation. Neglecting fundamental installation requirements may lead to personal injury as well as damage to electrical equipment or other property.

• NEVER bypass external fusing.

• NEVER apply the voltages at Program Lock and Auto Reset terminals.

• Before performing Dielectric or Megger testing on any equipment in which the monitoring device is installed, disconnect all the input and output wires to the monitoring device. High voltage testing may damage electronic components contained in the monitoring device.

• The monitoring device should be installed in a suitable electrical enclosure.

Failure to follow these instructions will result in death or serious injury.

• EAPL is not responsible for any consequential damages arising out of use of our products, though the technology is cautiously chosen and implemented like any other well designed good electric device.

Installation

Connecting cable recommendations

Insulation rating Current rating

Note: All Dimensions are in mm.

Front Panel

Rear View

Wiring

1. Top Display Window

2. Bottom Display Window

3. MENU/ ENTER/

HOLD/SCROLL Button

4. MANUAL/ESC Button

5. INC Button

6. DEC Button

7. RLY

Voltage circuit >600 VAC > 0.1A

Current circuit >600 VAC >7.5A/2.5mm

2 /

14AWG minimum

Tools and Fasteners

Kindly use star – type screw driver for tightening the screws.

NOTE:

Installation should include a disconnecting device, like switch or circuit breaker, with clear ON/OFF markings, to turn-off the auxiliary supply (control power).The disconnecting device should be within the reach of the equipment and the operator .

Dimension

1,2,3,4 - R ,Y,B,N

5 , 6 - CBCT

8 - Com

9,10 - S1, S2 (R phase)

11, 12 - S1, S2 (Y phase)

13, 14 - S1, S2 (B phase)

15, 16 - NO, NC

Page 1 of 2

CREATED ON: June 21, 2016

System Type : Star/Wye

OD RE NN 610002 REV 02/21-06-16

Keys and Operation

MENU/ENTER/HOLD/SCROLL Key

RUN Mode : Used to select scroll/hold the

parameters.

PROGRAM MODE : Used to enter into program

mode.

: used to select next parameters.

INC Key

PROGRAM Mode : Used to increase the values.

DEC Key

PROGRAM Mode : Used to decrease the values.

MANUAL/ESC Key

RUN Mode : When fault recovery happens this key shall be used to Load ON/OFF manually.

PROGRAM Mode : It is used to view the previous parameters.

RUN Mode

1. On power application, relay will be in NC condition for

approximately 10sec.

2. During healthy condition, all the voltage parameters shall be

displayed with instantaneous values. Relay and relay LED will

3. During fault condition, type of fault shall be displayed with

Relay OFF or ON Status depending on Rly ’y’ or Rly ‘n’ setting.

Auto mode

4. Once the fault is recovered, unit automatically comes back

to parameter display mode as mentioned in point – 2.

Manual mode

5. Once the fault is recovered, manual key to be pressed to

bring back display mode as mentioned in point – 2.

6. If faults are rectified before set trip delay timings of relay,

display will continue to show fault status. Relay status remain

unaltered. Press Manual key to show the parameter display.

Press MENU/ENTER key for 3Seconds to HOLD/SCROLL display.

When fault occurs unit display’s the following:

Parameters

OVER VOLTAGE

UNDER VOLTAGE

OVER CURRENT

UNDER CURRENT

OVER FREQUENCY

UNDER FREQUENCY

EARTH LEAKAGE

PHASE UNBALANCE

PHASE REVERSE

R PHASE FAIL

Y PHASE FAIL

B PHASE FAIL

Top display

Err

Err

Err

Err

Err

Err

Err

Phs

Phs

FAIL

FAIL

FAIL

Bottom display

OUOL

UUOL

OCrt

UCrt

O-HZ

U-HZ

ELr

UbAL rEU

P-r

P-y

P-b

2

3

4

5

6

7

Phase Unbalance Condition

To set unbalance condition for 20%.

Set 20 in unit (PUbL=20 as shown in the table).

If RY=350V, YB=450V, BY=319V in the load.

Fault is created in the unit, upper displays shows “Phs” and

lower shows “UbAL”.

Calculations are as follows

Set nVOL=415V, PUbL=20% in the unit.

Vry=350V, Vyb=450V, Vbr=319V, Vavg= 373V

Vry -Vavg=23V, Vyb -Vavg=77V, Vb-Vavg=54V

Phase unbalance= (Maximum deviation / Vavg) * 100

= (77/373)*100= 20 %

PROGRAM Mode

To enter program mode press INC & DEC key simultaneously for 4sec.

Programming

Parameters

Range

Factory setting

1 “nUOL” 415

9

10

11

12

13

14

15

16

17

18

“OUOL”

“UUOL”

“CT-P”

“nCrt”

“OCrt”

“UCrt”

“ PUbl”

“O-Hz”

“U-Hz”

“ELr”

“IrdY”

“ tdOU”

“ tdUU”

“ tdOC”

“ tdUC”

“tdUb” bYPS

Nominal voltages: 415V

Over Voltage. Range: 5 to 100V

Under voltage. Range: 5 to 100V

CT Primary. Range: 5 to 2500A

Nominal Current. Range: 0.5-500A

Over Current. Range: 105-800%

Under Current. Range: 20-95%

Phase Unbalance. Range: P 1-20%

Over frequency. Range: 2 to 5Hz

Under frequency. Range: 2 to 5Hz

Earth leakage current. Range: 1 to 8A

Inrush delay. Range: 1-60sec

Trip delay Over Voltage. Range: 1- 250sec

Trip delay Under Voltage. Range: 1 - 250sec

Trip delay Over Current. Range: 1 - 250sec

Trip delay Under Current. Range: 1 - 250sec

Trip delay Unbalance. Range: 1 – 250sec

“OUL Y/n” Bypass Over Voltage n

030

030

005

005.0

120

20

20

05

05

1

01

005

005

005

005

005

19 bYPS

“UUL Y/n” Bypass Under Voltage n

20

21

22

23 bYPS

“OCt Y/n” bYPS “UCt Y/n” bYPS

“UBL Y/n” bYPS “OHz Y/n”

Bypass Over Current

Bypass Under Current

Bypass Phase Unbalance

Bypass Over Frequency n n n n

24 bYPS “UHz Y/n”

Bypass Under Frequency n

25 CntL rLY ‘n’ rLY ‘Y’

Relay & Status LED OFF in healthy condition

Relay & Status LED ON in healthy condition y

26 “Auto” rst ‘Y’ rst ‘n’

Auto reset enable

Auto reset disable

(Manual mode)

“Y”

“n”

CREATED ON: June 21, 2016

Technical Specification

Function

Phase Unbalance, Phase

Reversal, Phase Failure, Under and Over Voltage, Under and

Over Current, Under and Over

Frequency, Earth Leakage

Monitor and Control.

System Input

Input Voltage

Input Current

Input Frequency

Control output

Power Consumption

415V AC(3Ph-4W)

Current input (AR,AY,AB) Ib=5A

50 Hz, ± 10%

1c/o rated for 10A @

250VAC/28VDC resistive load

5VA/ 1W

Accuracy

Voltage

Current

Frequency

Trip Time

Earth leakage current

± 4V of display value

± 5% of Ib ± 1 digit (Ib = 5A)

± 2% of FS ± 1 digit

± 1% of set delay ± 2 sec

± 500mA of setting accuracy.

General

Minimum sensing current 0.5A

Maximum sensing current

5A(Above 5A> Ext.CT can be used)

Earth leakage Trip time delay 5 sec Earth leakage

Phase Failure trip time delay

Phase reverse trip time delay

Frequency trip time delay

Recovery Time

< 5 sec

Instantaneous

Instantaneous

2 sec Min

Power On Delay

Mode of Operation

Core Balance Current

Transformer type

CBCT Size Internal Diameter

Climatic

Ambient Temperature

10 sec Max

Auto/ Manual

Toroidal core

100mm

Operation: -10 ° C to +55 ° C

Storage : -25 ° C to +80 ° C

MAX 85% RH @ 40 ° C Humidity

Disposition

Once the product life is over, you may send back the

unit to EAPL for disposition