ICP DAS USA GRP-520 User manual

Add to My manuals
75 Pages

advertisement

ICP DAS USA GRP-520 User manual | Manualzz

GRP-520 User Manual, V1.20, Aug. 2014

GRP-520 Series

3G Gateway

User Manual v1.20

High Quality, Industrial Data Acquisition, and Control Products

1

GRP-520 User Manual, V1.20, Feb. 2014

Warranty

All products manufactured by ICP DAS are warranted against defective materials for a period of one year from the date of delivery to the original purchaser.

Warning

ICP DAS assumes no liability for damages consequent to the use of this product. ICP DAS reserves the right to change this manual at any time without notice. The information furnished by ICP DAS is believed to be accurate and reliable. However, no responsibility is assumed by ICP DAS for its use, or for any infringements of patents or other rights of third parties resulting from its use. This is licensed under the terms of the GNU General Public License version 2.

Copyright

Copyright 2012 by ICP DAS CO., LTD. All rights reserved worldwide.

Trademark

The names used for identification only may be registered trademarks of their respective companies.

Version

1.00

1.10

1.20

Date

2013/03/20

2014/02/05

2014/08/05

Author

Malo

Malo

Malo

Description

Release version

Add new feature

Add new feature: RTU Client

2

GRP-520 User Manual, V1.20, Aug. 2014

Table of Contents

1.

Introduction ............................................................................................... 4

1.1 Features ............................................................................................................. 5

1.2 Applications ...................................................................................................... 5

2.

Hardware ................................................................................................... 8

2.1 Specifications ................................................................................................... 8

2.2 Appearance and pin assignments ...................................................................... 9

2.3 Dimensions ..................................................................................................... 10

2.4 LED indicators ................................................................................................ 11

2.5 Rotary Switch .................................................................................................. 12

2.6 Installing GRP-520 ......................................................................................... 13

3.

Web Utility .............................................................................................. 14

3.1 Login the Utility ............................................................................................. 14

3.2 Information ..................................................................................................... 15

3.3 Network .......................................................................................................... 18

3.4 System ............................................................................................................ 25

3.5 VxServer ......................................................................................................... 29

3.6 RTU Client ...................................................................................................... 31

4.

Example ................................................................................................... 38

4.1 3G Router Application .................................................................................... 38

4.2 Web Server and IP Camera Application ......................................................... 41

4.3 Remote I/O Control / Temperature Monitor ................................................... 46

4.4 Modbus/TCP to Modbus/RTU over 3G, and Card Reader Monitor ............... 51

4.5 RTU Client for Remote Control Application with RTU API.......................... 56

4.6 RTU Client for Remote Control Application with OPC DA Server. .............. 68

4.7 RTU Client for Remote Control Application with InduSoft........................... 71

4.8 Email or FTP report I/O logger file. ............................................................... 73

3

GRP-520 User Manual, V1.20, Aug. 2014

1. Introduction

The GRP-520 provided by ICP DAS is a 3G gateway for Ethernet or serial port. With optional GPS model, the GRP-520 can also be a GPS tracking system. It can be used in M2M application fields to transfer the remote I/O, Modbus data or video of the camera via 3G/2G.

Within the high performance CPU, the GRP-520 series can handle a large of data and are suit for the hard industrial environment. The GRP-520 series have 3G module, Ethernet interface, and optional GPS module.

4

GRP-520 User Manual, V1.20, Feb. 2014

1.1 Features

 Support Tri-band WCDMA 2100/1900/850 MHz and Quad-band GSM 850 / 900 / 1800 /

1900 MHz.

10/100 Base-TX compatible ethernet eontroller

COM port: COM1 (3-wire RS232), COM2 (RS-485), COM3 (3-wire RS232)

GPS : 32 channels with All-In-View tracking (option)

 Support Micro SD card.

 Provide 3G Router function.

 Support port mapping (port forward) function.

 Serial Port to 3G Gateway

 High reliability in harsh environments

 DIN-Rail mountable

1.2 Applications

 Signal Alarm Report System

 3G Router

 Home/Factory security

 Remote Video Monitor

 Energy Management

 Temperature Monitoring

5

Application 1: 3G Router

Application 2: Remote Video Monitor

GRP-520 User Manual, V1.20, Feb. 2014

Application 3: Remote Control (Serial Port to 3G gateway)

6

GRP-520 User Manual, V1.20, Feb. 2014

7

GRP-520 User Manual, V1.20, Feb. 2014

2. Hardware

2.1 Specifications

Item

System / Software

3G Gateway

GRP-520

Ethernet and Serial port (1x RS-232, 1x RS-485) to 3G

Embedded service Web Server, 3G router

System

CPU

SRAM

Flash

EEPROM

Expansion Flash Memory

ARM CPU (312MHz)

64 MB

64 MB

16 KB (Data Retention: 40 years; 1,000,000 erase/write cycles)

SD Card (Max. 32GB SDHC)

Expansion Disk

RTC(Real Time Clock)

USB disk (format : FAT32)

Provide seconds, minutes, hours, day of week/month, month and year

64-bit Hardware Serial Number Yes

Watchdog Timer Yes

LED Indicator

Rotary Switch

3 LEDs (SYS/PWR, F.W., 3G)

Yes (0~9)

GSM System

Frequency Band

GPRS connectivity

DATA GPRS

3G System

Frequency Band

GSM : 850/900/1800/1900 MHz

GPRS class 12/10; GPRS station class B

Downlink transfer: Max. 85.6 kbps; Uplink transfer: Max 42.8kbps

Data Transmission

WCDMA 2100/1900/850 MHz

WCDMA / HSDPA / HSUPA

Downlink transfer: Max. 7.2Mbps; Uplink transfer: Max 5.76Mbps

GPS System (option)

Support Channels

Protocol Support

Comm. Interface

32

NMEA 0183 version 3.01

Ethernet

COM1

COM2

COM3

Mechanism

RJ-45, 10/100 Base-TX

(Auto-negotiating, Auto MDI/MDI-X, LED indicators)

RS-232 (RxD, TxD and GND); Non-isolated(Console, Debug)

RS-485 (D2+, D2-); 3000 VDC isolated

RS-232 (RxD, TxD and GND); Non-isolated

Casing Plastic

Dimensions(W x L x H) 91 mm x 132 mm x 52 mm (W x L x H)

DIN-Rail Installation

Power

Protection

Frame Ground Protection

Required Supply Voltage

Power Consumption

Environment

Operation Temp.

Storage Temp.

Humidity

Power reverse polarity protection

ESD, Surge, EFT, Hi-Pot

+10 V

DC

~ +30 V

DC

4.8W ( 200 mA @ 24 V

DC

)

-25℃ to 75℃

-30℃ to 80℃

5~95% non-condensing

8

2.2 Appearance and pin assignments

GRP-520 User Manual, V1.20, Feb. 2014

COM Port & Power Input

Terminal No. Pin Assignment

COM1

COM2

COM3

Power

01

08

09

10

02

03

04

05

06

07

RxD1

TxD1

GND

D+

D-

RxD3

TxD3

DC.+VS

DC.GND

F.G.

9

2.3 Dimensions

GRP-520 User Manual, V1.20, Feb. 2014

10

GRP-520 User Manual, V1.20, Feb. 2014

2.4 LED indicators

There are three LED indicators to help users to judge the various conditions of GRP-520.

The description is as follows:

A. PWR(Green):Power LED to indicate whether the external power is input or not. The description is as follows:

The external power is active The external power is not active on off

B. OS(Red):OS LED indicates if the OS is normal or fail.

Normal

Heart beat (1 sec.)

Fail

Always ON or OFF

C. FW(Red):This LED indicates the status of VxServer firmware (Serial port to 3G).

Connected

500ms ON / 500ms OFF

Connecting

Blanking(4 sec)

Fail

Always ON or OFF

D. FW(Green):This LED indicates the status of RTU Client firmware.

Normal

500ms ON / 500ms OFF

Fail

Always ON or OFF

E. 3G (Red):The LED indicates the status of 3G module.

(the 3G module need about 60 seconds to register network usually)

Registered

800ms ON / 800ms OFF

3G/GPRS data transmit

200ms ON, 200ms OFF

Fail

Always ON or OFF

11

GRP-520 User Manual, V1.20, Feb. 2014

2.5 Rotary Switch

There are some functions of rotary switch. The description is as follows:

A. 0:Normal mode, default position.

B. 1 : Debug mode, this a engineering mode, we can communicate with the OS console.

C. 2 : OS Update with MicroSD card. 2G SD card is supported.

D. 4 : OS Update with Ethernet. It is used in the factory. Please don’t use it.

E. 8 : Factory default IP. If you set as 8, and then reset the device, its Ethernet IP will be

“192.168.255.1”. if you forgot your device IP, you can use this function to re-configure your device IP.

F. 9 : Factory default setting. If you forgot your password, you can follow the steps below:

(1) set rotary switch as 9

(2) and connect TxD3 and RxD3 together

(3) reset your device

(4) if the Red and Green FW Led blinking, it means restore as factory default setting successfully. Please turn rotary switch as 0.

12

GRP-520 User Manual, V1.20, Feb. 2014

2.6 Installing GRP-520

If users want to start GRP-520 normally, it needs to follow these steps to install the

GRP-520 below:

A. Install the antenna

B. Plug in the normal SIM card (Before apply the SIM card, confirm it is OK by mobile phone.)

C. Plug the Ethernet cable if you need it.

D. If you want to use the Micro SD card, please insert it into the slot.

E. Turn the rotary switch to 0 (normal mode). The COM1 will be the console in position 1

(debug mode), and the default username is “root”, default password is “root”.

F. Connect the DC.+VS and DC.GND to the power supply.

G. It is needed to wait about 20 ~ 30 seconds for OS booting. After finishing the process,

GRP-520 would be in normal operation mode and the OS LED would blank as heart beat per 1 sec.

H. It is needed to wait about 30 ~ 60 seconds to search the 3G/2G base and register to the

ISP. After finishing the process, the 3G LED would blank per 1 sec.

13

GRP-520 User Manual, V1.20, Feb. 2014

3.

Web Utility

You must configure GRP-520 from web utility before using.

3.1 Login the Utility

Please login before you use the web utility. The default username is “admin”, and the default password is “admin”

Default IP = “192.168.255.1”

Default Mask = “255.255.0.0”

Default Gateway = “192.168.0.1”

After login, the screenshot is showed as below:

14

3.2 Information

You can get the basic information of the device here.

3.2.1 Device Information

This page provides basic device information:

GRP-520 User Manual, V1.20, Feb. 2014

(1) Product Name: the Name of your product

(2) Serial Number: only one number of ICPDAS product

(3) OS Kernel Version: linux kernel version.

15

3.2.2 Network Information

This page provides basic network information:

GRP-520 User Manual, V1.20, Feb. 2014

(1) Ethernet: Ethernet information

.Mode: static IP or DHCP

.MAC address: a unique identifier assigned to network interfaces.

.IP Address: a computer's address under the Internet Protocol

.Mask: Mask will be provided from Gateway provider.

(2) 3G/GPRS Network information: the information will show out after dial up

.Status: “connected” mean the modem dial-up success.

.IP Address: the IP is provide by ISP provider.

.P-t-P: provide by ISP provider

.Mask: provide by ISP provider

(3) Modem information:

.PIN Code: the status of PIN Code. Please refer to below:

READY: PIN Code is ready.

SIM PIN: need PIN code of SIM card

SIM PUK: need PUK code of SIM card

SIM failure: Access SIM Card failure

16

GRP-520 User Manual, V1.20, Feb. 2014

.Register Status: Indicating GRP-520 connect to 3G base successful or not.

.Signal Quality: the 3G signal quality.

3.2.3 Storage Information

This page provides information about “Micro SD card”, “USB Disk”:

(1) USB Disk / SD card:

.Size: total size of storage

.used: the size is used

.Available: free space in the storage

.Path: the mount point in file system.

17

GRP-520 User Manual, V1.20, Feb. 2014

3.3 Network

The user can configure the Network functions here.

3.3.1 Ethernet

This page provides the basic settings of Ethernet:

(1) IP Address: IP of Ethernet.

(2) Mask: the Mask of the gateway.

(3) Gateway: IP of the gateway.

3.3.2 3G Configure

This page provides basic settings of 3G network:

(1) PIN Code: PIN Code are 4 character number provided by SIM Card provider

(2) Phone Number: usually fill it as “*99***1#” or “*99#”. The number is depended on

SIM Card provider

(3) APN: Access Point Name, please ask your SIM Card provider.

18

GRP-520 User Manual, V1.20, Feb. 2014

(4) User Name: the username for dial-up. Please ask your SIM Card provider.

(5) Password: the password for dial-up. Please ask your SIM Card provider.

(6) Auto-Dialing: Enable this function to dial-up to 3G network after power on.

3.3.3 3G/GPRS Reconnection

This function can keep the device always on 3G/GPRS network, but it will send the

IMCP signals to check 3G/GPRS network.

The default setting is “Disable” to prevent it from using extra packets.

PS. Some ISP upgrades their system cause GRP-520 difficult to dial-up in Taiwan.

Please enable this function to avoid this problem. When GRP-520 dial-up fails, it will try to solve this problem automatically. (It maybe take about 10 minutes, and this problem was solved in v1.1.1 and later).

(1) Server IP: the target IP or URL that you want to send signal (ping the target IP).

(2) Max. Retry: if the system retry time is over this number, it will reset 3G modem and dial-up to try again.

(3) Interval Time: the interval time between this retry and last.

(4) Timeout: the device will connect to 3G network for a period of 50 second (default value) after resetting the Modem, and then the system will start check the connection of 3G network.

(5) Enable Function: if you enable this function, it will run immediately.

(6) Alive: the firmware status. “true”(color green) means “alive”. “false”(color gray) means “not alive”..

19

3.3.4 DNS Server

The user can set DNS server IP here:

GRP-520 User Manual, V1.20, Feb. 2014

(1) Primary DNS Server: the device will use it to get DNS service first.

(2) Alternate DNS Server: if “Primary DNS Server” is invalid, the device will use

“Alternate DNS Server”.

3.3.5 DDNS Configure

DDNS is a method of updating, in real time, a Domain Name System (DNS) to point to a changing IP address on the Internet:

(1) Server: the address of DDNS service provider.

(2) Domain: The domains name you registered.

(3) Username: the username of DDNS service.

(4) Password: the password of DDNS service.

(5) Period: the period time (seconds) to update your address.

(6) Enable: Enable DDNS function.

20

GRP-520 User Manual, V1.20, Feb. 2014

3.3.6 DHCP Server

The Device could be a DHCP Server. The user can set the IP range for DHCP client.

(1) Subnet, Netmask, Lease-time: these items are read-only.

(2) Routers: the router IP. It usually is set as your device IP.

(3) Range: the IP range that DHCP server assign to DHCP client.

(4) Enable: Enable DHCP Server service.

* If your device need link to Internet via 3G/GPRS, please enable the “Routing rule” for

“DHCP Range” here. About “routing rule”, please refer next section

.

21

3.3.7 Routing

This page provides routing rule configuration.

GRP-520 User Manual, V1.20, Feb. 2014

(1) IP: IP address.

(2) Mask: the mask will effect how many IP this rule manages.

”24” = 255 IPs, “28” = 16 IPs, “32” = 1 IPs.

(3) Target: the target interface of the rule.

For example:

The Rule 0: This rule will push the socket packages from the address 192.168.27.0 ~

192.168.27.255 forward to “ppp0” (3G network).

The Rule 1: This rule will push the socket packages from the address 192.168.0.0 ~

192.168.0.15 forward to “ppp0” (3G network).

22

GRP-520 User Manual, V1.20, Feb. 2014

3.3.8 Port Mapping (Port Forward)

This page provides Port Mapping rule configuration.

(1) Type: the protocol type. There are “TCP” and “UDP”

(2) From: the interface that the socket comes from.

”ppp0” is 3G interface.

(3) Port: the port that the socket comes from.

(4) Target IP: the IP that the socket goes forward.

(5) Target Port: the Port of the “Target IP”.

For example:

The Rule 0: This rule will bind the socket from the “ppp0” and Port=”10080” with

192.168.0.10:80.

The Rule 1: This rule will bind the socket from the “ppp0” and Port=”10021” with

192.168.0.10:21.

23

GRP-520 User Manual, V1.20, Feb. 2014

3.3.9 Diagnostic

This page provides the tools to check the problem of the network.

(1) Ping Test: this tool will ping “Target IP”, and show result below.

(2) Traceroute: this tool will trace routing path to “Target IP”, and show the result below.

(3) Route Information:: this tool will show route setting below.

24

GRP-520 User Manual, V1.20, Feb. 2014

3.4 System

The user can configure “password”, “system parameter”, reboot the device and restore factory settings here.

3.4.1 Password

The user can change the password of the web utility here.

(1) Password: new password.

(2) Confirm: confirm the password again.

3.4.2 Reboot

The user can reboot the device here.

25

GRP-520 User Manual, V1.20, Feb. 2014

3.4.3 Reboot Timer

The user can use this function to reboot system automatically.

(1) Interval Time: Interval Time to reboot system.

(2) Enable: Enable Reboot Timer function.

3.4.4 Backup & Restore

The user can backup the device settings and restore it here.

(1) Backup: Press “Backup” button to backup settings into your PC.

(2) Restore: Press “Browse” button to select file, and then press “Restore” button to store your settings.

3.4.5 Restore Factory

The user can restore the device setting to factory default.

26

GRP-520 User Manual, V1.20, Feb. 2014

3.4.6 System Time

This page provide information about the time of the device.:

(1) Set Time: set the time of GRP-520 the same as your computer.

(2) NTP Server: device will connect to the NTP Server to synchronize time.

(3) Timezone: if you do not know your timezone, please click the link “check timezone” to find out.

(4) Enable NTP Function: if you enable it, GRP-520 will update time automatically.

3.4.7 System Service

This page indicates the status of system services.

(1) Process Name:

.pppd: this process will dial-up to 3G network.

.dhcpd: DHCP Server.

.ddns: ddns client process. It will auto update IP.

(2) Alive: the process status. “true”(color green) means “alive”. “false”(color gray) means

“not alive”.

27

(3) Start: click the button to start this process.

(4) Stop: click the button to stop this process.

GRP-520 User Manual, V1.20, Feb. 2014

28

3.5 VxServer

The user can configure VxServer firmware here.

3.5.1 VxServer

The user can configure VxServer firmware here.

GRP-520 User Manual, V1.20, Feb. 2014

(1) Server IP: Server IP or URL.

(2) Server Port: the port of the server.

(3) Heartbeat Time: if setting this value small, it is sensitive to detect network disconnected.

(4) Device ID: ID of the device. If you set it as “1”, you will find that “visual IP” is

“192.168.20.1” on the server side.

(5) Alias: an alias of device. Max. length is 8 characters.

29

GRP-520 User Manual, V1.20, Feb. 2014

(6) Time Interval: if the Time Interval between the two serial port data is more than this value, the data will be sliced into two network packet. And if there is no enough time interval, but data length is over 1000 bytes (default value), the data still be sliced into two network packet.

(7) Data Length: if serial port data length is over this value, the data will be sliced into two packets. Usually you just set this value as 1000 if you don’t need this function. (this value is limited by network protocol)

(8) Modbus TCP to RTU: Modbus/TCP to Modbus/RTU gateway function. Port1 is COM2 of GRP-520 (RS-485); Port2 is COM3 of GRP-520 (RS-232).

(9) Default Baudrate: this value is dependent on your Modbus RTU device. Please set this value is the same as your Modbus RTU device.

(10) Default Format: configuration of “Data bits”, “Parity” and “Stop bit”.

8, 7 mean 8 or 7bits of Data bits

N, O, E mean None, Odd, Even of Parity

1, 2 mean 1 or 2 bits of Stop bit

(11) Enable Function: Enable the firmware immediately.

(12) Alive: the firmware status. “true”(color green) means “alive”. “false”(color gray) means “not alive”.

30

GRP-520 User Manual, V1.20, Feb. 2014

3.6 RTU Client

The user can configure RTU Client function here. The RTU Client function will connect to

RTU Center , please refer GRP-520 website for more information.

3.6.1 RTU Client

The user can configure RTU Client firmware function here. There are three tabs:

(1)Main Info. (2)Modbus Number (3)FTP/Email

 Main Info. Tab:

(1) Server Address: Server IP or Domain Name.

(2) Server Port: the port of the server.

(3) Station ID: the ID for this device. (do not be the same with other RTU device)

(4) Data Update Period (sec.): set report time interval. GRP-520 will report all data to RTU

Center every interval time your setting.

(5) Heartbeat Period (sec.): set heartbeat time interval. 3G/GPRS connection will be terminate by ISP, this parameter can detect broken connection early. “Heartbeat

Period” must be smaller than “Data Update Period”.

31

GRP-520 User Manual, V1.20, Feb. 2014

(6) Baud Rate (RS-485 for Modbus/RTU): the baud rate of the COM2 (RS-485).

(7) Data bit: the data bit of COM2.

(8) Parity: the parity bit of COM2.

(9) Stop bit: the stop bit of COM2.

(10) Modbus Timeout (ms): the Timeout value of Modbus.

(11) Enable Function: enable the RTU Client function.

(12) Alive: the firmware status. “true”(color green) means “alive”. “false”(color gray) means “not alive”.

 Modbus Device: the interface for adding Modbus I/O device.

32

GRP-520 User Manual, V1.20, Feb. 2014

(1) Modbus Device Number: display the modbus device number here.

You can choose a model in the list, and then use the “Add” button to add a new modbus device.

(2) Device Name: the Name of the modbus device. This Name will be showed in RTU

Center.

(3) Device ID: the modbus ID.

(4) IP: the IP of modbus/TCP device. Keep it empty for Modbus/RTU device.

(5) Port: the Port number of modbus/TCP device.

(6) DI Number: the number of DI channel.

(7) DO Number: the number of DO channel.

(8) AI number: the number of AI channel.

(9) AO number: the number of AO channel.

(10) DI Address: the start address for reading DI value.

(11) DO Address: the start address for reading DO value.

(12) AI Address: the start address for reading AI value.

(13) AO Address: the start address for reading AO value.

33

GRP-520 User Manual, V1.20, Feb. 2014

 FTP / Email: this function will send back all I/O data log file automatically. The period time to send is depending on “Max. Time per Log File (hour)” parameter.

(1) Data Log Interval (sec.): the time interval to record I/O data to logger file. Set as “0” to disable all function in this tab .

(2) Max. Time per Log File (hour): the time interval to change log file and send log file via

Email or FTP. GRP-520 will change logger file before the file be over 3 MB, and move old logger file into “LOGFILE” folder, and send out the file at the same time.

If you enable FTP or Email function, GRP-520 will copy old logger file into

“FTP_UPLOAD” and “MAIL_UPLOAD” for sending out files.

If send FTP or Email logger file fails, GRP-520 will send files next time.

34

GRP-520 User Manual, V1.20, Feb. 2014

(3) FTP Server Address: FTP Server IP or Domain Name.

(4) FTP Port: the port of the FTP server.

(5) FTP Username: username for login

(6) FTP password: password for login

(7) Enable FTP Function: enable FTP report function.

(8) Email From: the email will be sent from this address.

(9) Email To: the email address that will receive logger file. Using “,” to separate each mail address

Example: for single receiver: [email protected] for multi-receiver: [email protected],[email protected]

(10) Email Server: the server address of the email server.

(11) Email Server Port: the server port of the email server. Usually it will be 25, 465, or

587.

(12) Email Username: the username of your email account.

(13) Email Password: the password of your email account.

(14) Enable Email Function: Enable email report function.

3.6.2 FTP Test

The user can test all configure for FTP here.

(1) FTP Server Address: FTP Server IP or Domain Name.

(2) FTP Port: the port of the FTP server.

(3) FTP Username: username for login

(4) FTP password: password for login

35

3.6.3 Email Test

The user can test all configure for Email here.

GRP-520 User Manual, V1.20, Feb. 2014

(1) Email From: the email will be sent from this address.

(2) Email To: the email address that will receive logger file. Using “,” to separate each mail address

Example: for single receiver: [email protected] for multi-receiver: [email protected],[email protected]

(3) Email Server: the server address of the email server.

(4) Email Server Port: the server port of the email server. Usually it will be 25, 465, or

587.

(5) Email Username: the username of your email account.

(6) Email Password: the password of your email account.

(7) “Test” button: Pressing this button, GRP-520 will send a test mail to the mail address in “Email To” field.

36

GRP-520 User Manual, V1.20, Feb. 2014

3.6.4 Modbus Test

The user can test all configure for Modbus here. There is the result message for testing ET-7026.

37

GRP-520 User Manual, V1.20, Feb. 2014

4.

Example

4.1 3G Router Application

This example shows the steps to share 3G network to 3 XPac8000.

(1) Please configure the Ethernet of XPac8000 as:

IP=192.168.0.10 ~ 12

Mask=”255.255.0.0” gateway = “192.168.27.51”.

(2) Set the Ethernet IP of GRP-520.

38

GRP-520 User Manual, V1.20, Feb. 2014

(3) Set Pin code of your SIM card, and Enable “Auto-Dialing” function.

Set “User Name” and “Password” if your SIM card need it.

Press “Modify” to save

(4) Enable “3G/GPRS Reconnection” function to keep your 3G/GPRS network always online

(usually, ISP will disconnect your connection once every 1~3 days).

Generally, you can set the Server IP as your server’s IP or google’s DNS server IP

(8.8.8.8). If you use MDVPN, please set the Server IP as your Server IP that doesn’t deny

ICMP service (Ping).

Press “Modify” after you finish all settings.

39

GRP-520 User Manual, V1.20, Feb. 2014

(5) Set routing rule to share 3G network. This setting will share 3G network to IP address from

192.168.0.0~192.168.0.255.

Press “Modify”

(6) Please reboot GRP-520 to enable settings. (you can reboot from the web or the power source)

40

GRP-520 User Manual, V1.20, Feb. 2014

4.2 Web Server and IP Camera Application

This example shows the steps to share 3G network to ET-7044 and IP camera.

(1) Please Set the Ethernet of ET-7044 and IP camera as:

IP=192.168.0.20 ~ 22

Mask=”255.255.0.0” gateway = “192.168.27.51”

(2) Set the IP of GRP-520 as below:

IP=”192.168.27.51”

Mask=”255.255.0.0”

41

GRP-520 User Manual, V1.20, Feb. 2014

(3) Set Pin code of your SIM card, and Enable “Auto-Dialing” function.

Set “User Name” and “Password” if your SIM card need it.

Press “Modify”

(4) Enable “3G/GPRS Reconnection” function to keep your 3G/GPRS network always online

(usually, ISP will disconnect your connection once every 1~3 days).

Generally, you can set the Server IP as your server’s IP or google’s DNS server IP

(8.8.8.8). If you use MDVPN, please set the Server IP as your Server IP that doesn’t deny

ICMP service (Ping).

Press “Modify” after you finish all settings.

42

GRP-520 User Manual, V1.20, Feb. 2014

(5) Set “DDNS” function. (Because the IP of 3G usually is not a fixed IP, we use DDNS to get a fixed domain name)

(6) Set “Port Mapping Rule” to let user access the device behind GRP-520 via the internet.

This setting will bind the port of 3G interface to “Target IP:Target Port”.

Port 12080 of 3G interface  192.168.0.20:80

Port 12180 of 3G interface  192.168.0.21:80

Port 12280 of 3G interface  192.168.0.22:80

(7) Please reboot GRP-520 to enable settings. (you can reboot from the web or the power source)

43

GRP-520 User Manual, V1.20, Feb. 2014

(8) Please type the IP address or domain name of GRP-520 in 3G network. You will look as below. (It maybe like “mygrp5k.no-ip.org:12080”.)

44

GRP-520 User Manual, V1.20, Feb. 2014

(9) If you want to see the IP Camera image from web browser, please type the IP address or domain name of GRP-520 in 3G network. (It maybe like “mygrp5k.no-ip.org:12180”.)

45

GRP-520 User Manual, V1.20, Feb. 2014

4.3 Remote I/O Control / Temperature Monitor

This example shows remote control application via “serial port to 3G gateway function”.

(1) Please connect your device (DL-100 or PLC) to serial port of GRP-520.:

(2) If you never use VxServer, please refer the link as below: http://m2m.icpdas.com/VxServer.html

you need download VxServer software and VxComm software, and install it on your control center.

(3) Set Pin code of your SIM card, and Enable “Auto-Dialing” function.

Set “User Name” and “Password” if your SIM card needs it.

Press “Modify”

46

GRP-520 User Manual, V1.20, Feb. 2014

(4) Enable “3G/GPRS Reconnection” function to keep your 3G/GPRS network always online

(usually, ISP will disconnect your connection once every 1~3 days).

Generally, you can set the Server IP as your server’s IP or google’s DNS server IP

(8.8.8.8). If you use MDVPN, please set the Server IP as your Server IP that doesn’t deny

ICMP service (Ping).

Press “Modify” after you finish all settings.

(5) Configure VxServer Function.

Set “Server IP” and “Server Port”, the default port number is “11000”.

Let other settings be default value.

Click “Enable Function” to enable VxServer function.

Press “Modify”, and GRP-520 will try to connect to server. if “Alive” field is not “True”(Green color), it mean VxServer function fail. Please check your settings again.

47

GRP-520 User Manual, V1.20, Feb. 2014

(6) Please reset your device and un-plug your Ethernet from GRP-520, it will dial-up in 60 seconds, and then it will connect to your control center.

48

GRP-520 User Manual, V1.20, Feb. 2014

(7) After GRP-520 connect to VxServer, please follow steps below:

(a) Press “Search Servers” button, you will get a device list.

(b) Click right button of the mouse on GRP-520

(c) Click “Add Server”.

(d) choose the virtual com port number, and click “OK”

49

GRP-520 User Manual, V1.20, Feb. 2014

(8) You will see virtual com port: COM11, COM12, but it can’t be opened.

Click “tool”/”Restart Driver” to restart VxComm driver.

Open com port to connect your device.

(In this case, COM11 is RS-485, COM12 is RS-232 of GRP-520.)

50

GRP-520 User Manual, V1.20, Feb. 2014

4.4 Modbus/TCP to Modbus/RTU over 3G, and Card Reader Monitor

This example shows Modbus/TCP to Modbus/RTU over 3G function”.

After steps below, please set “IP:Port” of Modbus/TCP program as “127.0.20.1:10001” on your control center (Port 10001 is RS485; Port 10002 is RS232)

(1) Please connect your device (M-7017 or PLC) to RS-485 of GRP-520.

Baudrate of Modbus device is 9600 bps, data format is 8N1 (Data bits, Parity, Stop bits).

Baudrate of Card Reader is 115200 bps

(2) If you never use VxServer, please refer the link as below: http://m2m.icpdas.com/VxServer.html

you need download VxServer software and VxComm software, and install it on your control center.

(3) Set Pin code of your SIM card, and Enable “Auto-Dialing” function.

Set “User Name” and “Password” if your SIM card needs it.

Press “Modify”

51

GRP-520 User Manual, V1.20, Feb. 2014

(4) Enable “3G/GPRS Reconnection” function to keep your 3G/GPRS network always online

(usually, ISP will disconnect your connection once every 1~3 days).

Generally, you can set the Server IP as your server’s IP or google’s DNS server IP

(8.8.8.8). If you use MDVPN, please set the Server IP as your Server IP that doesn’t deny

ICMP service (Ping).

Press “Modify” after you finish all settings.

(5) Configure VxServer Function.

Set “Server IP” and “Server Port”, the default port number is “11000”.

For Card Reader:

Please just set Port2 (RS-232) as default value.

For Modbus RTU device:

Please configure as below

Click “Enable Function” to enable VxServer function.

Press “Modify”, and GRP-520 will try to connect to server.

If “Alive” field is not “True”(Green color), it mean VxServer function fail. Please check your settings again.

52

53

GRP-520 User Manual, V1.20, Feb. 2014

GRP-520 User Manual, V1.20, Feb. 2014

(6) Please reset your device and un-plug your Ethernet from GRP-520, it will dial-up in 60 seconds, and then it will connect to your control center.

(7) After GRP-520 connect to VxServer, please follow steps below:

(a) Press “Search Servers” button, you will get a device list.

(b) Click right button of the mouse on GRP-520

(c) Click “Add Server”.

(d) choose the virtual com port number, and click “OK”

54

GRP-520 User Manual, V1.20, Feb. 2014

(8) You will see virtual com port: COM11, COM12, but it can’t be opened.

Click “tool”/”Restart Driver” to restart VxComm driver.

Open com port to connect your device.

(In this case, COM11 is RS-485, COM12 is RS-232 of GRP-520. Please don’t open

COM11, because it’s Modbus/TCP to Modbus/RTU mode)

55

GRP-520 User Manual, V1.20, Feb. 2014

4.5 RTU Client for Remote Control Application with RTU API.

This example shows how to use RTU API to collect and control remote Modbus/RTU and

Modbus/TCP I/O with RTU Client / Server.

There are ET-7017, M-7045, and a PLC in this system.

(1) Please connect your device (ET-7k or M-7k modules) to Ethernet or RS-485 of GRP-520.:

(2) If you never use RTU Center, please refer the link as below: http://m2m.icpdas.com/m2m_rtu.html

If you need OPC solution, please refer the link as below: http://m2m.icpdas.com/NAPOPC_M2M.html

If you need RTU library to develop your own software, please refer the link as below: http://m2m.icpdas.com/m2m_rtu_api.html

(3) Set Pin code of your SIM card, and Enable “Auto-Dialing” function.

Set “User Name” and “Password” if your SIM card needs it.

Press “Modify”

56

GRP-520 User Manual, V1.20, Feb. 2014

(4) Enable “3G/GPRS Reconnection” function to keep your 3G/GPRS network always online

(usually, ISP will disconnect your connection once every 1~3 days).

Generally, you can set the Server IP as your server’s IP or google’s DNS server IP

(8.8.8.8). If you use MDVPN, please set the Server IP as your Server IP that doesn’t deny

ICMP service (Ping).

Press “Modify” after you finish all settings.

57

GRP-520 User Manual, V1.20, Feb. 2014

(5) Add ET-7017 in “Modbus Device” tab. choose ET-7017 in the list, and then press “Add” button.

(6) The web will bring out all I/O number information as below. Please modify “Device Name”,

“Device ID”, “IP” and “Port” for your ET-7017.

(Device Name: an alias name of your device, you can modify as you need.)

Press “Modify” to add a device.

58

GRP-520 User Manual, V1.20, Feb. 2014

(7) Add M-7022 in “Modbus Device” tab. choose M-7022 in the list, and then press “Add” button. We will see the screenshot as below.

The web will bring out all I/O number information. Please modify “Device Name” and

“Device ID” for your M-7022. (Don’t modify “IP” and “Port” settings).

Press “Modify” to add a device.

59

GRP-520 User Manual, V1.20, Feb. 2014

(8) Add PLC in “Modbus Device” tab. (communication with RS-485) choose “Custom” in the list, and then press “Add” button. We will see the screenshot as below.

Here we set the “Device Name”, “Device ID”, “DI Number”, “AI Number” for the PLC.

Press “Modify” to add a device.

60

(9) Three devices we set as below:

GRP-520 User Manual, V1.20, Feb. 2014

(10) Please choose “Modbus Test” function, and press “Test” button to test our settings.

If the result is successful, the screenshot will be as below, and please follow next step.

If result is fail, the screenshot will be as below. Please check your settings or the wire connection.

61

GRP-520 User Manual, V1.20, Feb. 2014

(11) Configure “Main Info.” Tab.

 Set “Server Address” and “Server Port” of your server that running RTU Center.

 Set Station ID of this GRP-520, and don’t be the same with another RTU device.

 Set “Data Update Period” and “Heartbeat Period”. (0  disable)

 Configure the parameters of RS-485 for Modbus/RTU.

62

(12) Download RTU Center from: http://m2m.icpdas.com/m2m_rtu.html

and then extract “RTU Center”.

GRP-520 User Manual, V1.20, Feb. 2014

Or you can install NAPOPC.M2M DA Server, it contains RTU Center.

Please download install file from: http://m2m.icpdas.com/NAPOPC_M2M.html

(13) Execute RTU Center, and add a RTU device in RTU Center.

 Click “New Device” icon.

 Input the alias name of your GRP-520

 Choose module type as “GRP-520”

 Set Station ID as “1”, and then press “OK” button.

63

GRP-520 User Manual, V1.20, Feb. 2014

(14) GRP-520 will connect to RTU Center later, and screenshot as below.

64

GRP-520 User Manual, V1.20, Feb. 2014

(15) You can double click on “ET-7050” to bring out “Output control panel”, and press “DO1” to control remote DO.

(16) Download RTU API from RTU Center web page, and extract it. There are RTU API library and some demo for C#, VB.Net, VC6 as below.

65

GRP-520 User Manual, V1.20, Feb. 2014

(17) Copy pre-building demo into folder of RTU Center. (demo must be in the same folder with

RTU Center, because they use the same share memory in M2M_RTU.dll)

Here we copy two file “RTU_CS_demo.exe” and “M2M_RTU_NET.dll” from C# demo.

66

GRP-520 User Manual, V1.20, Feb. 2014

(18) Execute “RTU_CS_Demo.exe”.

 Press “Get Information” to get all stations information.

 Set “Station ID” as 1 (because we set Station ID as 1 in GRP-520)

 Press “(2)ReadData” button to read Local IO data. Because GRP-520 don’t have local

IO, we get the error code here

 Set “Modbus ID” as 1 and “Modbus Name” as “ET-7050”, and press “(3)ReadData” to get all IO data.

 Press “Write Dos (add 1)” button to control DO.

67

GRP-520 User Manual, V1.20, Feb. 2014

4.6 RTU Client for Remote Control Application with OPC DA Server.

(1) Please refer last section for setting of “RTU Client”, “RTU Center”.

(2) After install “NAPOPC.M2M DA Server”, please click the icon to launch NAPOPC.M2M

DA Server from right-bottom toolbar of desktop.

(3) Click “Search” to add all tags of GRP-520 automatically.

68

(4) You will get a tag list as below.

GRP-520 User Manual, V1.20, Feb. 2014

(5) You can double click on device node to modify device name.

69

GRP-520 User Manual, V1.20, Feb. 2014

(6) Now you can use OPC Client to read I/O data from NAPOPC.M2M DA Server.

Or you can client “Monitor” to monitor all I/O data.

70

GRP-520 User Manual, V1.20, Feb. 2014

4.7 RTU Client for Remote Control Application with InduSoft.

This example shows how to using SCADA “InduSoft” to control/monitor remote I/O with

GRP-520.

(1) About RTU Client, RTU Center and OPC Server, please refer last section.

(2) Right-click OPC DA 2.05 folder and insert a new worksheet.

(3) Choice OPC Server from Server Identifier, and Select NAPOPC.M2M Item from combo box

71

GRP-520 User Manual, V1.20, Feb. 2014

(4) Configure Tag Name and Item Column

 Fill in your tag.

 Double-click Item column and select the point from pop-up window.

72

GRP-520 User Manual, V1.20, Feb. 2014

4.8 Email or FTP report I/O logger file.

This example shows how to using GRP-520 to report I/O logger file periodically.

(1) About Modbus configure, please refer section 4.5

.

(2) Configure Email / FTP function in “Email/FTP” Tab. You must set “Data Log Interval” field more than 0, or log report function will be disabled . (include FTP and Email)

 Configure “Data Log Interval” to record IO data into csv file. (0  disable) filename format: GRP-520_StationID_YYYYMMDD_hhmmss.csv ex: GRP-520_13_20140806_172347.csv

 Configure “Max. Time per Log File” to indicate how long to change / send back log file.

If the file size is close 3MB, GRP-520 will create a new log file to recode I/O data and move old log file into “/RTU/LOGFILE/” in SD card.

 If you need FTP report function, please set all FTP parameters and set “Enable FTP

Function” as “Enable”. GRP-520 will send log file to FTP Sever when new log file is available.

 If you need Email report function, please set all Email parameters and set “Enable FTP

Function” as “Enable”. If you need 2 or more contact, please use comma “,” to separate each contact .

73

GRP-520 User Manual, V1.20, Feb. 2014

74

GRP-520 User Manual, V1.20, Feb. 2014

(3) Finally, please don’t forget enable firmware in “Main Info.” Tab. If you don’t need the firmware send data to RTU Center, you can set “Data Update Period” as 0.

75