Algas SDI TORREXX TX25 Operation & Maintenance Manual
Publicité
Publicité
...Innovative liquid vaporizing and gas mixing solutions
Vertical electric single core vaporizer
Operations & Maintenance
Manual
151 South Michigan Street, Seattle, Washington, USA 98108
Tel: +1-206-789-5410 Fax: +1-206-789-5414 Web: www.algas-sdi.com
FILE: MANUAL PN 52368 TORREXX REV 05-05-17
2017.05.0
5
13:47:41
-07'00'
WARNING
Read the OPERATION MANUAL before operating this equipment.
■ NOTE: Algas-SDI reserves the right to use alternate manufacturers’ components as vendor delivery applicability dictates. Vendors have supplied literature contained in the Operation Manual. Please check to be sure supplied data matches your configuration. Contact Algas-SDI if any questions exist.
■ This equipment uses LPG - a flammable fuel, handled under pressure. Inherent hazards exist and a thorough understanding of the equipment is required to allow safe operation and maintenance.
■ Allow only a TRAINED and FULLY QUALIFIED PERSON to service this equipment.
■ Any time a component must be replaced use the same type, model etc. DO NOT SUBSTITUTE! The consequence from such actions is unpredictable and may lead to dire consequences. When components are replaced with components not approved for use in our FM listed equipment, the FM listing becomes void for that unit.
WARRANTY
REGISTRATION
To register your new equipment: Visit Algas-SDI's web site at: www.algassdi.com, then click on the "Tech Support" button. Select online Registration or print out the Acrobat Warranty Registration.
OR
Fill out the Warranty Registration information on the last page of this manual.
Then make a photocopy and mail to the address shown at the bottom.
WARRANTY,
COPYRIGHTS
AND
APPROVALS
WARRANTY
Algas-SDI International, LLC (ASDI ) warrants that the equipment is free of defects in materials and workmanship under normal use and service. ASDI agrees to repair or replace, at our option, without charge f.o.b. factory, any part which has proven defective to the satisfaction of Algas-SDI International, LLC within one (1) year from the date of the original installation or within 18 months from the date of shipment, whichever is earlier. Equipment, which in the opinion of ASDI , has been damaged by improper installation or operation, or has been abused or tampered with in any way, will not be accepted for return under warranty.
Algas-SDI International, LLC will not accept back charges for work performed by others upon or in conjunction with ASDI equipment, unless prior authorization is given by means of an Algas-SDI International, LLC purchase order. Algas-SDI
International, LLC will not be liable by reason of shutdown, non-operation or increased expense of operation of other equipment, or any other loss or damage of any nature, whether direct or consequential, arising from any cause whatsoever.
Algas-SDI International, LLC makes NO other warranty of any kind, whatsoever expressed or implied; and all warranties of merchantability and fitness for a particular purpose are hereby disclaimed by Algas-SDI International, LLC and excluded from these terms of sale. No person has any authority to bind Algas-
SDI International, LLC to any representation or warranty other than this warranty.
COPYRIGHT
Copyright 2014 by Algas-SDI International, LLC, Seattle, Washington 98108.
All rights reserved. No part of this manual may be reproduced or copied in any form or by any means, photographic, electronic, or mechanical, without the prior express written consent from Algas-SDI International, LLC, Seattle, Washington,
USA.
APPROVALS
*Approvals depending on model
SYMBOLS
AND
CONVENTIONS
Special symbols are used to denote hazardous or important information. You should familiarize yourself with their meaning and take special notice of the indicated information.
Please read the following explanations thoroughly.
GENERAL
WARNING
OR
CAUTION
This symbol indicates hazards or unsafe practices, which can result in damage to the equipment or cause personal injury. Use care and follow the instructions given.
FLAMMABLE
GAS
HAZARD
This symbol indicates a potential hazard, which can result in severe personal injury or death. Use extreme care and follow the instructions given.
ELECTRICAL
DISCONNECT
REQUIRED
This symbol indicates a potentially dangerous situation, which can result in severe personal injury or death or damage to equipment.
Use great care and follow the instructions given.
ASDI
CONTACT
NUMBERS
If you have questions, need help with your equipment, or want information on other products, contact Algas-SDI at:
Telephone: 206.789.5410
Facsimile:
Email:
Internet:
206.789.5414 [email protected]
http://www.algas-sdi.com
TORREXX TABLE of CONTENTS
1. INTRODUCTION
DESCRIPTION
Figure 1 – TORREXX Dimensional Drawing (LPG Version)
TORREXX OPTIONS – INTRODUCTION
2. MAJOR COMPONENTS
DESCRIPTION
Figure 2 – Heating system
Figure 3 – Liquid Passage Prevention system
MAJOR COMPONENTS LIST
Figure 4 – TORREXX Major Components Drawing (LPG CONFIGURATION)
1-1
1-2
1-3
3. INSTALLATION
GENERAL
Figure 5 – Typical TORREXX Installation Drawing with Pump & Vapor Bypass
3-9
3-9
Figure 6 – Typical TORREXX Installation Drawing with Vapor Bypass and No Pump 3-10
Figure 7 – Typical TORREXX Installation Drawing with Economy Operation and
Vapor Bypass 3-10
Figure 8 – Typical TORREXX Installation Drawing for Manifolding 2 Vaporizers 3-11
Figure 9 – Typical TORREXX Installation Drawing for Manifolding 3 Vaporizers
LIQUID LINE
3-11
3-12
LIQUID PUMP
VAPOR LINE
SAFETY RELIEF VALVE
ELECTRICAL SERVICE
3-12
3-12
3-13
3-13
DETERMINING WIRE SIZE
Table 1 – Wire Length Chart (#4 AWG)
Table 2 – Wire Length Chart (#6 AWG)
Table 3 – Wire Length Chart (#8 AWG)
Table 4 – Wire Length Chart (#10 AWG)
Table 5 – Liquid Temperature vs. Tank Pressure Chart
Table 6 – LPG liquid line sizing chart (Minimum Pipe Size)
3-13
3-14
3-14
3-15
3-15
3-17
3-18
Table 7 – Equivalent Pipe Length of Various Valves and Fittings
(Length in Feet/Meters) 3-18
2-6
2-6
2-7
2-8
2-8
TORREXX TABLE of CONTENTS - Continued
4. OPERATION
GENERAL
OPERATING INSTRUCTIONS
STARTING THE VAPORIZER
STOPPING THE VAPORIZER
PURGING THE VAPORIZER
5. MAINTENANCE
GENERAL
INITIAL INSTALLATION AND OPERATION INSPECTIONS
ANNAUL MAINTENANCE REQUIREMENTS
CONTACTOR INSPECTION
Liqui-SAFE TM VALVE – PERFORMANCE CHECK (6 MONTHS)
Figure 10 – Steps to check the Liqui-SAFE TM valve operation
Liqui-SAFE TM VALVE – SERVICE INSTRUCTIONS
Figure 11A – STEP 1 – Be sure that the Liqui-SAFE TM valve is at the close position as shown
Figure 11B – STEP 2 – Unscrew reset button base and remove spring
Figure 11C – STEP 3 – Replace button post internal o-ring
Figure 11D – Full hook o-ring tool
Figure 11E – STEP 4 – Unscrew valve latch body
Figure 11F – STEP 5 – Replace valve body static o-ring
Figure 11G – STEP 6 – Replace valve seat and valve stem base o-rings
6. TROUBLESHOOTING
TROUBLESHOOTING TREES
FULL LOAD VOLTAGE CHECK
Figure 12 – Full load voltage check
FULL LOAD CURRENT CHECK
Figure 13 – Full Load Current Check
TORREXX ELECTRIC VAPORIZER DATA SHEET
HEATER CORE RESISTANCE
Figure 14 – Heater Core Resistance Wiring Connections
SOLENOID VALVE LEAK TEST
Figure 15 – Solenoid Valve Leak Test Components
TORREXX TABLE of CONTENTS - Continued
4-19
4-19
4-20
4-20
4-20
6-29
6-35
6-35
6-36
6-36
6-37
6-38
6-38
6-39
6-39
5-26
5-26
5-27
5-27
5-27
5-28
5-28
5-22
5-22
5-23
5-24
5-25
5-25
5-26
SOLENOID VALVE ELECTRICAL TEST
Figure 16 – Solenoid Valve Electrical Test
THERMOCOUPLE SENSOR REPLACEMENT
Figure 17 – TORREXX Box showing Thermocouple location
Figure 18 – Thermocouple Sensor with Bayonet Style Retainer
7. TORREXX OPTIONS
ECONOMY OPERATION
Figure 19 – TORREXX Economy valve installation
TORREXX ECONOMY VALVE MAINTENANCE
Figure 20A – STEP 1 – Unscrew the Inlet Housing from the Outlet Housing
Figure 20B – STEP 2 – Replace the two O-rings, apply excess o-ring grease.
7-43
7-43
7-44
7-44
7-44
Figure 20C – STEP 3 – Clean all o-ring contact surfaces and the bottom surface of the Outlet Housing. Apply excess o-ring grease 7-45
Figure 20D – STEP 4 – Clean all piston surfaces. Apply excess grease on o-rings 7-45
Figure 20E – STEP 5 – Make sure that the Pin Hole is clear and The Spring is
6-40
6-40
6-41
6-41
6-42 undamaged. Carefully reassemble all the parts. Apply lubrication grease on straight threads if necessary
MERCURY RELAY
TX REMOTE BOX
VALVE AND STRAINER PACKAGE
FILTAIRE – CONTAMINANT SEPARATOR
Figure 21 – Filtaire Operation
APPENDIX A – TECHNICAL INFORMATION
EC DECLARATION OF CONFORMITY
TORREXX LPG VAPORIZER DATA SHEET (FM)
TORREXX ELECTRIC VAPORIZER SPARE PARTS AND ACCESSORIES (FM)
Figure 23 – TORREXX ELECTRIC VAPORIZER MAJOR COMPONENTS AND
ACCESSORIES
TORREXX LPG VAPORIZER DATA SHEET (NEMKO)
TORREXX ELECTRIC VAPORIZER SPARE PARTS AND ACCESSORIES (NEMKO)
HEATER BUSSING DIAGRAMS
EQUIPMENT DRAWINGS
INSTALLATION DRAWINGS
TORREXX WIRING SCHEMATIC
REMOTE BOX WIRING SCHEMATICS
SOLENOID NOISE
ASCO SOLENOID VALVE USED BY ASDI
SOLENOID VALVE INSTLLATION AND MAINTENANCE INSTRUCTIONS
Warranty Registration – Refer to the nameplate on the unit to fill out the product registration.
Then photocopy and mail to address shown
7-47
7-46
7-46
7-46
7-46
7-46
INTRODUCTION
DESCRIPTION
1
The dimensional drawing (see page 1-2) identifies various components of the
Algas-SDI TORREXX vaporizer. Multiple resistance heating elements provide thermal energy to the finned aluminum heat exchanger. A solid state controller monitors the heat exchanger temperature and regulates the operating temperature to a predetermined set point. The controls consist of 2 individual Ktype thermocouple sensors with independent high temperature limits. One sensor monitors operating temperature and the other controls the liquid inlet solenoid valve. The liquid inlet solenoid valve does not open until a predetermined warm-up temperature is reached. The vaporizer reaches operating temperature in approximately 60 seconds from a cold start. The vaporized LPG rises into the vapor header and exits through the vapor outlet.
The Liqui-SAFE TM Valve is specially developed to prevent liquid from going downstream.
TORREXX Vaporizer can be configured for many applications.
Standard configuration for Class I, Division 1, Group D for use with propane and LPG applications, FM and cFM approvals.
Standard configuration for Zone I for use with propane and LPG, NEMKO &
CE mark.
Feedback configuration for Class I, Division 1, Group D for Propane and LPG for tank heater applications where adequate tank pressure must be maintained.
TORREXX TM vaporizer can be manifolded together for increased capacity on a single skid. Consult Algas-SDI for Configuration information.
TORREXX TM vaporizer can be packaged with an Algas-SDI mixing system on a single skid. Consult Algas-SDI for Configuration information.
For customizing the TORREXX TM vaporizer to your requirements consult
Algas-SDI for information.
1-1 ASDI Operations and Maintenance – TX Models – P/N: 52368
Figure 1 – TORREXX Dimensional Drawing (LPG Version)
(4) ½” DIA MOUNTING HOLES
MODEL TX25 TX50 TX100 TX160 TX240
A
41”
1040mm
47”
1190mm
52”
1320mm
TX320
59”
1500mm
PRESSURE
RELIEF
VALVE
Liqui-SAFE
VALVE
1” FNPT
VAPOR
OUTLET
INSULATION
JACKET
FLOAT
HEATER
ELEMENT
TEMPERATURE
CONTROL
SENSOR
CONTROL
HOUSING
ELECTRICAL
SERVICE
REQUIRED
1 1/2”FNPT
PRESSURE
GAUGE
INLET
SOLENOID
VALVE
ASDI Operations and Maintenance – TX Models – P/N: 52368 1-2
TORREXX
VAPORIZER
OPTIONS
1-3
Your TORREXX TM vaporizer may be equipped with one or several of the factory options. All the options can be integrated to your TORREXX TM vaporizer and are designed to enhance convenience for the end user.
Below is a brief introduction to the options available for the TORREXX TM vaporizer. See SECTION 8 of this manual or contact Algas-SDI for more information.
1) Valve and Strainer Package – Includes strainer with magnetic plug, inlet shut-off angle valve, hydrostatic relief valve, outlet shut-off ball valve and outlet pressure gauge. Ships loose. All items not shown below.
2) Pipe Away Adapter – Allows the user to pipe the relief valve away from the vaporizer. Fits relief valve P/N 34876. 1”FNPT pipe connection.
3) TORREXX Stand – Elevates TORREXX Vaporizer 1 foot off the ground for ease of control box access and removes the vaporizer from elements i.e. snow and mud. Hardware to mount TX to stand is included. Ships loose.
ASDI Operations and Maintenance – TX Models – P/N: 52368
4) Economy – Allows the customer to use propane storage tank vaporization when the storage tank can provide enough vaporization and pressure to satisfy the load requirements.
Control – Includes remote start/stop capability and a status light indicating the vaporizer is ready for operation (solenoid valve open). IP65
(NEMA 4) enclosure.
6) Drain valve kit – Enables the user to drain the oils, heavy ends, and other impurities that can collect over time in the vaporizer heat exchanger. Kit available factory or field installed.
7) Stabilaire Pump Package – Consult factory
8) Contaminant Separator (Filtaire) – The Algas-SDI Filtaire TM is a filtering device design to trap heavy hydrocarbons commonly present in LPG gas vapor. It also traps other materials, which may be in gas due to storage conditions and internal condition of the equipment.
9) Balancing orifice – When manifolding two or more vaporizer together a balancing orifice must be used.
ASDI Operations and Maintenance – TX Models – P/N: 52368 1-4
SAFETY
CAUTION
Propane Odor can fade.
CAUTION
Vaporizer may be hot after or during use.
CAUTION
Allow only a TRAINED and FULLY QUALIFIED PERSON to service this equipment.
1-5 ASDI Operations and Maintenance – TX Models – P/N: 52368
MAJOR
COMPONENTS
2
Your New TORREXX TM vaporizer is designed to be reliable and user friendly.
Several features allow you to quickly determine the status of your vaporizer.
There are two basic control systems within a TORREXX TM :
1) Heating system – Figure 3
2) Liquid Passage Prevention system – Figure 4
Figure 2 – Heating system
SELF REGULATING HEATER SYSTEM
NO START/STOP SWITCHES
ENGAGES AUTOMATICALLY
JUST APPLY POWER TO TURN THE
VAPORIZER ON
TEMPERATURE ACTIVATED
CIRCUIT OPENS AT 55ºC OR
131ºF WITH SOLENOID VALVE
TO ENSURE AUTOMATIC
RESTART AFTER POWER
INTERRUPTION
TEMPERATURE CONTROLLER
DETECTS HEAT EXCHANGER
TEMPERATURE VIA A DUAL K
TYPE THERMOCOUPLE
HEAVY DUTY
CONTACTOR
TX100 SHOWN (CE CONFIGURATION) WITH NO OPTIONS
ASDI Operations and Maintenance – TX Models – P/N: 52368 2-6
Figure 3 – Liquid Passage Prevention system
RED FLAG INDICATES STATUS
VALVE IS TRIPPED WHEN FLAG
IS UP (AS SHOWN)
CLEAR PROTECTIVE BUTTON KEEPS
DEBRIS, WATER OR ICE FROM
IMPEDING PROPER OPERATION
VALVE IS IN OPERATING
POSITION WHEN FLAG IS
DOWN (AS SHOWN)
FLOAT BALL ACTIVATED
MANUAL RESET Liqui-SAFE
VALVE DETECTS AND
PREVENTS LIQUID FROM
PASSING TROUGH
THE Liqui-SAFE VALVE CAN
BE MANUALLY TRIPPED TO
VERIFY CLOSING INTEGRITY
FLOAT BALL
TX100 SHOWN (FM/cFM CONFIGURATION) WITH NO OPTIONS
2-7 ASDI Operations and Maintenance – TX Models – P/N: 52368
Figure 4 – TORREXX Major Components Drawing (LPG CONFIGURATION)
1) Liquid Inlet Solenoid Valve
2) Valve, Gauge and Strainer kit components (Optional)
3) Mercury Relay kit (Optional)
4) Temperature Controller Board
5) Economy Valve (Optional)
6) Liqui-SAFE TM Valve with manual reset
7) Insulation Jacket
8) Contactor
ASDI Operations and Maintenance – TX Models – P/N: 52368 2-8
INSTALLATION
WARNING
3
The equipment described in this manual is designed to operate with
LP-gas, a flammable fuel under pressure. The nature of the application involves inherent hazards that could result in injury.
ONLY a trained and fully qualified person should service this equipment.
NOTE
Prior to installing your new TORREXX vaporizer, check all relevant codes and standards that apply in your local area to ensure compliance!
CAUTION
To prevent ignition of hazardous atmospheres:
NOTE
Keep flameproof enclosure cover tight, torque to 26.6 Nm (19.6 ft. lbs.) while in service and disconnect power before installing or removing unit from service.
Installer must install a terminal box (connection facility).
Metal Terminal Box (M32)
EEx d II A Gb, (ATEX certified or equivalent) - marking for
Europe;
Metal Terminal Box (1”):
Class I, Division 1, Group D (UL listed or equivalent) - for US and Canada.
WARNING
Potential electrostatic charging hazard. Clean insulation with a damp cloth.
CAUTION
Connect only metal electrical conduit or armored cable to the vaporizer sealing fitting.
3-9 ASDI Operations and Maintenance – TX Models – P/N: 52368
GENERAL
Install the ASDI TORREXX vaporizer on a level firm base at least 6” above grade and secure it through the four ½” holes. Protect the equipment against damage by moving vehicles by use of an appropriate barrier. Consult state, provincial, insurance carriers, and local authorities for installation requirements. Clean all foreign material from all pipelines prior to making final connections. All joints require a pipe sealant approved for LPG, depending on type of service. Test for leaks using an inert gas, such as compressed carbon dioxide or nitrogen, at 1½ times the working pressure or as required by applicable codes. Check all connections using an appropriate leak detection solution or device. Even very small leaks are unacceptable. Eliminate all leaks prior to operation.
Install in accordance with applicable codes and local regulations as required.
Explosion proof seal off must carry the same approvals as the vaporizer in order to maintain the approval of the overall installation.
Figure 5 - Typical TORREXX Installation Drawing with Pump & Vapor Bypass
NOTES
1.
2.
3.
LIQUID PIPING LOSSES BETWEEN VAPORIZER AND THE TANK
MUST NOT EXCEED HYDROSTATIC HEAD WHEN THE PUMP IS
SHUT OFF.
INSTALL VAPORIZER 1 ST STAGE REGULATOR UPSTREAM OF
THE TANK VAPOR PRESSSURE CONNECTION POINT.
SET 1 ST STAGE VAPORIZER REULATOR 2-4 PSIG HIGHER THAN
4.
TANK VAPOR PRESSURE REGULATOR SET-POINT.
NO CHECK VALVES IN LIQUID LINE. LIQUID MUST BE ABLE TO
FLOW IN BOTH DIRECTIONS.
TANK VAPOR
PRESSURE
REGULATOR*
*BY OTHERS
VAPOR BY-PASS LINE ISOLATION
VALVE*
ISOLATION
VALVE*
VAPORIZER REGULATOR*
PRESSURE GAUGE*
(VAPOR)
TO LOAD
OUTLET ISOLATION
VALVE”
STORAGE TANK
STRAINER WITH
MAGNET FOR IRON
PARTICLE PICK-UP*
SEAL OFF REQUIRED*
ELECTRIC SERVICE
REQUIRED*
LIQUID
OPTIONAL
ISOLATION VALVE
W/HYDROSTATIC
RELIEF*
Note: The vapor bypass line is not required except when you have the Economy
Operation option. In other installations, it is recommended because it will provide vapor from the tank to the load in case of vaporizer failure or power failure but it is not required. Vaporizer will operate properly without the bypass.
ASDI Operations and Maintenance – TX Models – P/N: 52368 3-10
Figure 6 - Typical TORREXX Installation Drawing with Vapor Bypass and No Pump
1.
NOTES
LIQUID PIPING LOSSES BETWEEN VAPORIZER AND THE TANK
2.
3.
MUST NOT EXCEED HYDROSTATIC HEAD WHEN THE PUMP IS
SHUT OFF.
INSTALL VAPORIZER 1 ST STAGE REGULATOR UPSTREAM OF
THE TANK VAPOR PRESSSURE CONNECTION POINT.
SET 1 ST STAGE VAPORIZER REULATOR 2-4 PSIG HIGHER THAN
TANK VAPOR PRESSURE REGULATOR SET-POINT.
4.
*BY OTHERS
NO CHECK VALVES IN LIQUID LINE. LIQUID MUST BE ABLE TO
FLOW IN BOTH DIRECTIONS.
VAPOR BY-PASS LINE
TANK VAPOR
PRESSURE
REGULATOR*
ISOLATION
VALVE*
OUTLET ISOLATION VALVE”
ISOLATION
VALVE*
STORAGE TANK
(VAPOR)
TO LOAD PRESSURE GAUGE*
VAPORIZER
REGULATOR*
STRAINER WITH
MAGNET FOR IRON
PARTICLE PICK-UP*
SEAL OFF REQUIRED*
ELECTRIC SERVICE
REQUIRED*
LIQUID
ISOLATION VALVE
W/HYDROSTATIC
RELIEF*
ISOLATION VALVE”
1.
2.
3.
Figure 7 - Typical TORREXX Installation Drawing with Economy Operation and Vapor Bypass
NOTES
LIQUID PIPING LOSSES BETWEEN VAPORIZER AND THE TANK
MUST NOT EXCEED HYDROSTATIC HEAD WHEN THE PUMP IS
SHUT OFF.
INSTALL VAPORIZER 1 ST STAGE REGULATOR UPSTREAM OF
THE TANK VAPOR PRESSSURE CONNECTION POINT.
SET 1 ST STAGE VAPORIZER REULATOR 2-4 PSIG HIGHER THAN
TANK VAPOR PRESSURE REGULATOR SET-POINT.
TANK VAPOR
PRESSURE
REGULATOR*
4.
*BY OTHERS
NO CHECK VALVES IN LIQUID LINE. LIQUID MUST BE ABLE TO
FLOW IN BOTH DIRECTIONS.
VAPOR BY-PASS LINE
ISOLATION
VALVE*
ISOLATION
VALVE*
OUTLET ISOLATION VALVE*
(VAPOR)
TO LOAD
PRESSURE GAUGE*
ASDI ECONOMY VALVE
SENSES UPSTREAM
PRESSURE (OPEN 30PSIG
CLOSED 60PSIG)
PRESSURE GAUGE*
STORAGE TANK
VAPORIZER
REGULATOR*
STRAINER WITH
MAGNET FOR IRON
PARTICLE PICK-UP*
SEAL OFF REQUIRED*
ELECTRIC SERVICE
REQUIRED*
ISOLATION VALVE
W/HYDROSTATIC
RELIEF*
LIQUID
ISOLATION VALVE”
Note: Economy option cannot be used on an installation that requires a pump.
3-11 ASDI Operations and Maintenance – TX Models – P/N: 52368
Figure 8 – Typical TORREXX Installation for manifolding 2 vaporizers.
BALL VALVE WITH BALANCING ORIFICE
Liqui-SAFE VALVE
OVERSIZED COMMON
HEADER
VAPOR OUT
TORREXX VAPORIZER
NOTE:
1. USE 1” UNION AND BALL
VALVE WITH BALANCING
ORIFICES ON ALL VAPORIZER
OUTLETS
2. ONLY SAME SIZE VAPORIZERS
SHALL BE MANIFOLDED
TOGETHER
LIQUID IN
Figure 9 – Typical TORREXX Installation for manifolding 3 vaporizers.
BALL VALVE WITH BALANCING ORIFICE
Liqui-SAFE VALVE
OVERSIZED COMMON
HEADER
VAPOR OUT
TORREXX VAPORIZER
NOTE: USE 1” UNION AND BALL
VALVE WITH BALANCING
ORIFICES ON ALL VAPORIZER
OUTLETS
2. ONLY SAME SIZE
VAPORIZERS SHALL BE
MANIFOLDED TOGETHER
LIQUID IN
LIQUID INLET STRAINER
W/MAGNET FOR IRON
PARTICLE PICK-UP
ASDI Operations and Maintenance – TX Models – P/N: 52368 3-12
3-13
LIQUID
LINE
LIQUID
PUMP
Size the liquid line from the storage tank to the vaporizer to supply the vaporizer at full capacity with a minimal pressure drop. A liquid linesizing chart is provided in Table 6. If liquid line is undersized this may limit vaporizer capacity at low loads due to inability to push liquid back to the tank. Install a liquid line strainer with magnet for iron particle pickup at the vaporizer inlet.
CAUTION
A liquid pump must be installed if the pressure drop in the liquid line between the vaporizer and the tank exceeds the hydrostatic liquid head in the storage tank. ONE FOOT OF LIQUID PROPANE
EQUALS .21 PSI! Liquid line frosting is a sure indication of too much pressure drop in the liquid line.
Is a Liquid Pump necessary? What are your vapor pressure requirements?
Pressure in the storage tank depends on temperature See Table 5. A good “rule of thumb” for determining when a Liquid Pump is necessary is this: If the storage pressure will not always exceed the required distribution pressure by 5 psig (0.35 kg/cm2), a pump is necessary. Install an ASDI STABILAIRE Liquid Pump in the liquid line close to the storage tank. To prevent cavitation, place the liquid strainer at least five feet upstream of the pump inlet. Typically a pump is not required unless a mixing system is used or temperature at the installation will be extremely low, causing the pressure to drop below the required process pressure. When using a pump, vaporizer capacity may decrease due to increase in boiling point of LPG. Increasing boiling point requires larger portion of heat exchanger area to be used for liquid heating instead for boiling and vaporization. Please consult ASDI when using a pump.
VAPOR
LINE
Install an appropriate regulator within 3 feet (1m) of the vapor outlet. Connect pipe from the outlet port of the regulator to the distribution system. Further reduction of downstream pressure requires a “Second Stage” regulator close to the consuming equipment. Properly sized piping and regulators will insure satisfactory service.
NOTE
For safety reasons both FIRST and SECOND stage regulators must be 250 psig (17.58 cm/kg 2 ) inlet pressure rated!
ASDI Operations and Maintenance – TX Models – P/N: 52368
SAFETY
RELIEF
VALVE
If the vaporizer is to be installed within an enclosure or building, VENT THE
SAFETY RELIEF VALVE OUTSIDE THE ENCLOSURE AND REDIRECT THE
DISCHARGE UPWARD. A pipe-away adapter must be used at the relief valve.
Always install a rain-cap or similar device to prevent water and other debris from entering the relief discharge. If water enters, it may freeze and prevent the relief valve from proper discharge, creating a potentially hazardous situation.
ELECTRICAL
SERVICE
The rating plate on the vaporizer and the data sheet provided with the manual provides your specific vaporizer’s electrical power requirements and the drawing numbers of the appropriate wiring diagrams and schematics. This unit is constructed to meet NFPA 70 Class I, Division 1, Group D requirements or ATEX
Zone I requirements (depending on model). All wiring to the unit, including the ground connection, must meet the applicable codes for the area in which it is being installed. Wire size and type must comply with the applicable codes for the area in which it is being installed. The Tables 1 through 4 list the recommended wire size for the different models. Those tables are to be used as guides only.
Provide a fused disconnect outside of the classified area. If it is not within sight of the vaporizer, the fused disconnect must have a locking device. Run wire within rigid conduit, and install a seal-off at the connection of the field conduit to the vaporizer. Use separate breaker for each vaporizer!
WIRE
SIZE
When selecting the type and size of wire used to install the TORREXX series electric vaporizers, please take into account the following environmental information:
■ Maximum enclosure surface temperature: 65º C (150ºF).
■ Maximum enclosure ambient temperature: 65º C (150ºF).
■ Maximum temperature allowed at contactor terminals: 90º C (195º F).
■ Current draw of vaporizer: Indicated on vaporizer rating plate and on the data sheet.
■ Contactor terminal lug wire size range: #2 - 10.
As the length of the wire run affects the overall wire size requirements, always refer to NFPA 70 (NEC) for proper wire selection. Several wire-sizing charts have been provided for determining the size of wire required due to load and length of wire.
When installing the wire it is important to have a good connection at the terminal lugs. Loose terminals may cause an excessive temperature rise at the terminal lugs, which can lead, to premature contactor failure, transformer failure, and/or overheating and possible destruction of the transformer. For this reason it is strongly recommended that the wire terminations be checked and re-tightened periodically to prevent excessive overheating at the terminals due to loose connections.
ASDI Operations and Maintenance – TX Models – P/N: 52368 3-14
Table 1 – Wire Length Chart [#4 AWG]
Table 2 – Wire Length Chart [#6 AWG]
3-15 ASDI Operations and Maintenance – TX Models – P/N: 52368
Table 3 – Wire Length Chart [#8 AWG]
Table 4 – Wire Length Chart [10 AWG]
ASDI Operations and Maintenance – TX Models – P/N: 52368 3-16
°C
37.4
40.2
42.9
45.7
48.4
51.2
53.9
56.7
59.4
-3.
-1.1
1.7
4.4
7.2
9.9
12.7
15.4
18.2
20.9
23.7
26.4
29.2
31.9
34.7
-41.7
-39.6
-36.9
-34.1
-31.4
-28.6
-25.9
-23.1
-20.4
-17.6
-14.9
-12.1
-9.35
-6.6
Table 5 – Liquid Temperature vs. Tank Pressure Chart
Propane
Liquid
Temperature
Tank Gauge
Pressure
°F
100
105
110
115
120
125
130
135
140
45
50
55
60
65
25
30
35
40
70
75
80
85
90
95
-43.73
-40
-35
-30
-25
-20
-15
-10
-5
0
5
10
15
20
PSI
173.6
186.1
199.2
213.0
227.4
242.5
258.2
274.7
291.9
46.2
51.7
57.6
63.8
70.5
77.5
84.9
92.8
101.2
109.9
119.3
129.1
139.7
150.2
161.6
0
1.4
3.4
5.6
8.0
10.7
13.6
16.7
20.0
23.6
27.6
31.7
36.2
41.1
1.2
2.9
4.8
6.9
9
11.3
13.8
16.5
19.3
22.4
25.8
29.2
32.7
36.7
41.0
46.6
50.3
55.3
60.5
66.1
72.1
78.2 kPa
1196.6
1283.1
1373.7
1468.6
1567.9
1671.9
1780.5
1893.9
2012.4
318.7
356.7
397.0
440.1
485.8
534.3
585.7
640.1
697.6
758.3
822.4
889.9
963.5
1035.7
1114.2
0
9.6
23.6
38.9
55.6
73.7
93.5
114.9
136.1
163.1
189.9
218.9
249.9
283.1
Butane
Tank Gauge
Pressure
PSI kPa
NOTE:
Below 30°F or -10°C,
Butane is a liquid at normal atmospheric pressure.
8.6
20.1
33.2
47.2
62.0
78.0
95.3
113.8
133.1
154.7
177.9
201.4
225.3
252.8
282.8
321.1
346.7
381.1
417.3
455.9
497.3
538.9
PSI
196.7
214.2
231.8
251.4
271.0
292.9
314.9
339.2
363.5
39.0
44.9
51.5
58.4
66.0
74.3
83.1
92.6
102.8
113.9
125.5
137.9
151.3
165.5
181.1
1.2
3.5
6.2
8.9
12.2
15.6
19.6
23.7
28.4
33.4
Ammonia
Tank Gauge
Pressure kPa
1356.2
1477.1
1597.9
1733.4
1868.9
2019.9
2171.0
2338.8
2506.5
268.9
309.3
355.1
402.8
455.3
511.9
572.9
638.6
709.1
784.5
865.2
951.4
1043.3
1141.3
1248.8
8.5
24.4
42.6
61.8
84.2
107.7
134.9
163.3
195.9
230.0
3-17 ASDI Operations and Maintenance – TX Models – P/N: 52368
Table 6 – LPG liquid line sizing chart (Minimum Pipe Size)
Capacity of units
Distance from storage to vaporizer - feet (meters)*
MMBTU
(Kcal)
1.146
(288,792)
2.292
(557,584)
4.584
(1,155,168)
7.280
(1,834,537)
10.920
(2,751,806)
14.665
(3,668,800)
Kg
25
50
100
160
240
320
LBS
(GPH)
55
(12.5)
110
(25)
220
(50)
352
(80)
530
(120)
530
(160)
25
(8)
½”
½”
½”
¾”
1”
1”
50
(15)
½”
½”
¾”
¾”
1”
1”
75
(23)
½”
½”
¾”
1”
100
(31)
½”
¾”
¾”
1”
150
(36)
½”
¾”
1”
1”
200
(61)
¾”
1”
1”
300
(92)
¾”
1”
1”
1¼‘ 1¼‘
400
(122)
¾”
1”
1¼‘
1¼‘
1¼‘ 1¼‘ 1¼‘ 1½ ” 1½ ” 1½ ”
1¼‘ 1¼‘ 1¼‘ 1½ ” 1½ ” 1½ ”
Table 7 – Equivalent Pipe Length of Various Valves and Fittings (Length in Feet/Meters)
½” ¾” 1” 1 ¼” 1 ½”
Size/Description
(1.27 cm) (1.91 cm) (2.54 cm) (3.18 cm) (3.81 cm)
Globe Valve 15.5/4.72 21/6.40 27/8.23 36/10.97 43/13.11
Gate Valve
Angle Valve
Elbow, 90
Elbow, 45
0.6/0.18 0.8/0.24
8/2.44 11/3.35
1.4/0.43 1.9/0.58
0.7/0.21 1/0.30
1/0.30
14/4.23
2.4/0.73
1.2/0.37
1.4/0.43
18/5.49
3.2/0.98
1.6/0.49
1.6/0.49
21/6.40
3.8/1.19
2/0.61
Elbow, 90 STR
Tee
2.3/0.70 3.1/0.94
2.7/0.82 3.7/1.13
4/1.22
4.8/1.46
5.3/1.62
6.4/1.95
6.3/1.92
7.5/2.29
ASDI Operations and Maintenance – TX Models – P/N: 52368 3-18
OPERATION
GENERAL
4
TORREXX Electric Vaporizer utilizes a finned cast aluminum heater core. The heater core contains multiple cast-in resistance heater elements. Multiple wiring configurations allow a variety of AC input voltages to suit local power supply requirements.
Liquid LPG enters the vaporizer through the Liquid Inlet Solenoid Valve at the base of the pressure vessel.
During operation, a K-type thermocouple temperature sensor and solid state control system maintain the core temperature at 165°F (74°C). As the temperature increases on start, the Liquid Inlet Solenoid Valve opens at 131°F
(55°C), liquid enters the vaporizer and comes in contact with the heater core.
Vaporization results as the liquid extracts energy (heat) from the heater core. As the heater core cools, the Temperature Sensor provides a signal to the control system to energize the heater power contactor, applying power to the heater elements.
OPERATING
INSTRUCTIONS
1) Complete the installation and leak test.
2) Check current and voltage to verify proper operation of the vaporizer.
3) This unit will not be damaged by operating the unit in a “dry” condition. It is not necessary to have liquid in the unit for testing or evaluation.
4) Normal operating temperature is 165°F (74°C). Use caution when working around vaporizer.
4-19 ASDI Operations and Maintenance – TX Models – P/N: 52368
STARTING
THE
VAPORIZER
CAUTION
Power wiring terminals may become loose during shipping. Prior to applying electrical power all power wiring terminals must be retightened. Recheck terminals and retighten as necessary during next service interval.
CAUTION
Do not start the vaporizer when both inlet and outlet isolation valves are closed. Pressure can build in the vaporizer during startup and blow the relief valve.
1) Close the outlet isolation valve.
2) Open all valves between the storage tank and the vaporizer to allow liquid flow to the vaporizer when the solenoid valve opens.
3) Apply power. A small “click” should be heard immediately afterwards. The vaporizer heater elements are now energized. It will take approximately 60 seconds for the vaporizer to reach operating temperature. After reaches the operating temperature, the Inlet Solenoid Valve will open automatically to allow LPG to enter. Wait approximately 2 minutes so that excess LPG is pushed back to the storage tank.
4) Carefully press the Button on top of the Liqui-SAFE TM valve all the way down and SLOWLY release it. A latch mechanism inside the Liqui-SAFE TM valve will keep the Red Flag at the down position, indicating the valve is open and in operating position.
5) TORREXX vaporizer is now ready to supply vapor. Slowly open the outlet isolation valve to pressurize the supply piping. Then, fully open the outlet isolation valve to allow vapor to flow to the load. Heater will cycle automatically to match the flow conditions.
STOPPING
THE
VAPORIZER
1) Close the outlet isolation valve.
2) Disconnect power.
PURGING
THE
VAPORIZER
Purging procedure should be followed anytime a vaporizer needs to be maintained, serviced, relocated or shut down for any other reason.
CAUTION
Prior to purging the vaporizer, ensure that there are no closed ball valves or back check valves restricting the flow of liquid to the tank.
1) Close the valve at the outlet of the vaporizer.
ASDI Operations and Maintenance – TX Models – P/N: 52368 4-20
2) If the vaporizer is not operating, start the vaporizer.
3) Allow at most 5 minutes for vaporizer to heat up and push most of the remaining liquid back into the tank. You should hear the contactor cycle off.
4) Close the tank liquid outlet valve.
5) Open the vaporizer outlet valve and flare or allow attached equipment to consume remaining gas in the line.
4-21 ASDI Operations and Maintenance – TX Models – P/N: 52368
MAINTENANCE
GENERAL
5
TORREXX vaporizer is designed for long term trouble free operation. Because of the nature of their use, and the severe duty they receive, it is important to provide scheduled maintenance. The maintenance schedule, type and frequency, provided in this manual is the minimum maintenance required for proper operation of the vaporizer. Ambient conditions surrounding the vaporizer installation and LPG quality may require a more frequent maintenance schedule.
A list of RECOMMENDED SPARE PARTS is located in the appendix section of this manual.
CAUTION
The equipment described in this manual is designed to operate with
LP gas, a flammable fuel under pressure. The nature of the application involves inherent hazards that could result in injury.
ONLY a trained and fully qualified person should service this equipment.
CAUTION
Before performing maintenance on the vaporizer,
Disconnect and lock out power to the vaporizer to prevent electric shock.
Be sure the LP-gas supply is shut off and the vaporizer is completely purged. Ensure ALL sources of ignition are extinguished within 25 feet of the work area.
Initial Installation & Operation Inspections:
Component
Inlet Strainer
Required 30-60 days after initial installation
Action Required
Electronic wiring and connections
Heat exchanger & drip legs
Inspect strainer and remove accumulated debris. Note: if debris accumulation is heavy check every 3-6 months.
Check primary terminal lug tension. Inspect electrical connections for loose wires and any indication of heat build-up.
Check all drip legs and vaporizer for heavy ends and oil build-ups. If present, first ensure there are no sources of ignition within 25 feet, then drain heavy ends.
NOTE: In areas where LPG quality is poor it may be necessary for the drip legs and heat exchanger to be checked for heavy ends more frequently (monthly or bimonthly depending on quality of LPG). Once it is verified that no significant quantity of heavy ends are accumulating during vaporizer operation, this maintenance can be performed on an annual basis.
ASDI Operations and Maintenance – TX Models – P/N: 52368 5-22
Annual Maintenance Requirements:
Component
Inlet strainer
Action Required
Remove plug and clean the screen. Replace screen if gaps or holes are present
Inlet solenoid valve in the screen. If oils or contaminants are present, it may be necessary to use a cleaner to remove them.
Change solenoid valve diaphragm and internal component using recommended repair kit for the inlet solenoid valve (see spare parts list for proper part number).
Refer to the maintenance and operation information for ASCO 2 way valves
Liqui-SAFE
Contactor
TM valve included in the Appendix section. Replace solenoid valve if the valve body is damaged. NOTE: Install kit if the valve makes unusual noise (chatter or buzzing) during normal operation.
Conduct performance check as described on page 5-25.
If valve does not pass leak test, replace all O-rings in the Liqui-SAFE TM valve provided in the repair kit.
If valve does not latch test, replace Liqui-SAFE TM parts list for proper part numbers). valve assembly. (see spare
Follow the contactor inspection schedule as described in the Contactor
Inspection section. Inspect the contactor for any discoloration, warping, melting, or pitting. These are indications of excessive heat or excessive wear. If these indicators exist, replace the contactor before returning the vaporizer to operation.
If contactor operation is noisy (humming), replace the contactor.
Relief Valve
Electronic wiring and connections
Heat exchanger & system drip legs
Visually check and replace in leaks are observed. Check for excessive corrosion and ensure the relief valve is covered with the appropriate rain cap to prevent rain and debris from entering the valve. Replace rain cap if not present or damaged. Relief valve should be replaced per the manufacturers’ recommended replacement date or if it relieves during normal operation.
Check primary terminal lug tension and visually inspect all electrical connections for corrosion, loose wires, heat build-up and/or charring. Tighten or replace if necessary.
Check the system drip legs and vaporizer for heavy ends and oil build-ups. If present, first ensure there are no sources of ignition within 25 feet, then drain heavy ends. NOTE: In areas where LPG quality is poor it may be necessary for the drip legs and heat exchanger to be checked for heavy ends more frequently
(monthly or bi-monthly depending on quality of LPG). Once it is verified that no significant quantity of heavy ends are accumulating during vaporizer operation, this maintenance can be performed on an annual basis.
5-23 ASDI Operations and Maintenance – TX Models – P/N: 52368
CONTACTOR
INSPECTION
WARNING
Contactor that powers the heaters produces sparks which may ignite any flammable vapors in the area when the control box cover is removed. If the cover must be removed, shut off the power, remove the cover and check very carefully for fumes, leaks, or any indication of flammable vapors in the atmosphere or in the control enclosure.
Do not re-apply power if fumes are present. They may ignite!
CAUTION
Keep a fire extinguisher available in the immediate vicinity before re-applying power when the control cover is removed.
TORREXX TM vaporizer utilizes an electro-mechanical contactor to switch power to the heating elements. Since contactors wear out in normal operation, it is prudent industry practice to inspect then on a preventive maintenance basis.
Manufacturers define a cycle life for contactors based upon operations at rated current. The cycle rate of the contactor in vaporizers varies due to liquid temperature/pressure, percent loading of the vaporizer, and installation specifics.
Vaporizer testing has demonstrated that cycle rates are greatest at around 50% of the vaporizer loading and least when vaporizers are energized in a standby mode.
We recommend the following inspection schedule for contactors:
5000 hours for vaporizers in service
30,000 hours for vaporizers in standby mode
Remove the incoming and outgoing wires and inspect the individual contacts for signs of excessive heat or wear. If blackening or pitting is present, the contactor should be replaced.
For vaporizers operating in a combination of service and standby modes, we are providing a simple formula to help determine when contactors should be inspected.
Contactor life factor (LF) can be defined as follows:
LF = X + Y _
When
5000 30000
X = hours of vaporizer operation mode
Y = hours of vaporizer in standby mode
If LF is 1 or greater, the contactor should be replaced.
This data is to be used only as a guide. It is not “fool-proof” as the environment your vaporizer operates in and its load may affect the contactor life span.
ASDI Operations and Maintenance – TX Models – P/N: 52368 5-24
Liqui
‐
SAFE
TM
valve
–
Performance
check
(Every
6
months)
I Latch operation. – While the valve is in the open position and the Red Flag is down, press Button and release QUICKLY. This will cause the valve to close and the Red Flag should pop up. Carefully press the Button again all the way down and release SLOWLY. The valve will stay open with red flag down.
II Leak detection. – Follow the instructions in “I” to manually open and close the valve. Perform leak tests in both conditions. If a leak is detected at the Valve
Body (Step 1) when the valve is open, replace the Valve Body O-ring (This can be performed in the field. See below.) If a leak is detected in Step 5 when the valve is closed (see Figure 11), follow the “Liqui-SAFE TM valve –
Service Instructions” and change all the o-rings. (This service should not be performed in the field.)
Figure 10 – Follow 1 to 7 below to check the Liqui-SAFE TM valve operation
2. PRESS AND RELEASE
QUICKLY TO CLOSE
1. CHECK FOR LEAKS
(AT THE GAP)
3. CHECK FOR LEAKS
(AT PIPE THREADS)
7. MAKE SURE VALVE FLAG
IS DOWN. VALE IS NOW IN
OPERATING POSITION
STEP 1
4. CHECK FOR LEAKS
(AT VALVE THREADS)
6. PRESS AND RELEASE
SLOWLY TO RE-OPEN
5. CHECK FOR LEAKS
(AT THE GAP)
STEP 2
5-25
STEP 3
WARNING
Extreme caution must be taken due to the potential of flammable vapors being exposed to the atmosphere creating an ignition. Do not operate any equipment that may create a spark from this point.
Do not open the explosion-proof enclosure.
ASDI Operations and Maintenance – TX Models – P/N: 52368
Liqui–SAFE
TM
Valve
–
Service
Instructions
There are four (4) o-rings in the Liqui-SAFE TM valve; the Button Post o-ring,
Valve Body o-ring, Valve Seat o-ring and Valve Stem Base o-ring. Follow the instructions below to service the Liqui-SAFE TM valve. Clean all the metal parts with WD-40. Re-assemble all the parts. Simulate the tripping action of the valve to ensure proper latch operation before re-installing in the vaporizer. The tripping force applied on the Extension Stem is between 0.2 lbf (0.89 N) and 0.5 lbf (2.22
N).
Figure 11A – STEP 1 – Be sure that the Liqui-SAFE TM valve is in the close position as shown
Figure 11B – STEP 2 – Unscrew reset button base and remove the spring
UNSCREW RESET
BUTTON BASE
REMOVE SPRING
ASDI Operations and Maintenance – TX Models – P/N: 52368 5-26
Figure 11C – STEP 3 – Replace button post internal o-ring
COMPRESS SUB-ASSEMBLY TO GAIN BEST ACESS TO
THE O-RING. REMOVE USING FULL HOOK O-RING TOOL
(SEE FIGURE 12D)
REPLACE O-RING. APPLY WHITE LITHIUM GREASE
PRIOR TO INSERTING BACK IN THE O-RING GROOVE.
Figure 11D – Full hook o-ring tool
Figure 11E – STEP 4 – Unscrew valve latch body
UNSCREW VALVE LATCH BODY
5-27
WARNING: BE SURE THAT THE VALVE IS IN THE
CLOSED POSITION BEFORE UNSCREWING
VALVE LATCH BODY. FAILING TO DO SO MAY
RESULT IN PERMANENTLY DAMAGING THE
LATCH!
ASDI Operations and Maintenance – TX Models – P/N: 52368
Figure 11F – STEP 5 – Replace valve body static o-ring
PULL VALVE STEM
GUIDE UP
Figure 11G – STEP 6 – Replace valve seat and valve stem base o-rings.
USE O-RING HOOK TOOL TO REMOVE O-RING
FROM O-RING GROOVE. SLIDE O-RING OVER
STEM GUIDE.
REPLACE O-RING. APPLY WHITE LITHIUM
GREASE PRIOR TO INSERTING BACK IN
THE O-RING GROOVE
USE O-RING HOOK TOOL TO REMOVE O-RINGS
FROM O-RING GROOVES.
REPLACE O-RING. APPLY WHITE LITHIUM
GREASE TO BOTH O-RINGS PRIOR TO
INSERTING BACK IN THE O-RING GROOVES
IMPORTANT:
Always perform a functional check and leak test (see Figure 11 ) of the re-assembled valve to ensure that it actuates per design and that valve seat o-ring seals properly against the valve body. A proper seal is present when the large valve seat o-ring shown in Figure 12G is sealing along the entire surface on the bottom face of the valve body.
Please note that on older versions of the valve (installed on vaporizers built before 8/11/2010) it was necessary to remove the driving magnet in order to access and replace the o-ring below the valve stem guide. When reassembling the old version of the valve after servicing o-rings, make sure that super glue is applied to the inside of the magnet holder and that magnet is firmly pressed in until it bottoms out. Allow sufficient time for glue to dry.
ASDI Operations and Maintenance – TX Models – P/N: 52368 5-28
TROUBLESHOOTING
General
Follow
the
troubleshooting
guide
below
to
identify
the
problem:
6
YES
NO FLOW OUT OF THE VAPORIZER
IS Liqui-SAFE
VALVE
TRIPPED?
NO
SEE TROUBLESHOOTING TREE 1A SEE TROUBLESHOOTING TREE 2A
6-29 ASDI Operations and Maintenance – TX Models – P/N: 52368
TREE # 1 A
Liqui-SAFE VALVE TRIPS
YES
PERFORM FULL LOAD CURRENT CHECK.
SEE PAGE 6-36
REMOVE LIQUI-SAFE VALVE. SEE PAGE
5-26 FOR SERVICE INSTRUCTIONS.
RE-INSTALL LIQUI-SAFE VALVE
YES
IS CURRENT
CHECK GOOD?
IS VAPORIZER WARM
AND UP TO
TEMPERATURE?
NO
SEE TROUBLESHOOTING
TREE 1B
NO
PERFORM FULL LOAD VOLTAGE CHECK.
SEE PAGE 6-35
YES
IS VOLTAGE
CHECK GOOD?
NO
YES
VAPORIZER CAPACITY
EXCEEDED.
REDUCE LOAD
RESTART
VAPORIZER.
DOES THE
VALVE TRIP?
NO
RESUME OPERATING
THE VAPORIZER
CHECK FOR OPEN FUSE
LINKS
FIX VOLTAGE ISSUE
AND RESTART
VAPORIZER
YES
REPLACE OPEN FUSE
LINKS.
CONTACT ASDI
FUSE LINKS
OPEN?
NO
CHECK FOR OPEN
HEATERS.
CONTACT ASDI
ASDI Operations and Maintenance – TX Models – P/N: 52368 6-30
YES
PERFORM SOLENOID VALVE
LEAK TEST (SEE PAGE 6-39).
REPAIR OR REPLACE
SOLENOID VALVE
PERFORM LEAK TEST
AGAIN TO ENSURE
ISSUE IS CORRECTED.
RESTART VAPORIZER
TREE # 1 B
Liqui-SAFE TM VALVE TRIPS
IS VAPORIZER POWER
OFF?
NO
SEE TROUBLESHOOTING TREE # 2A
6-31 ASDI Operations and Maintenance – TX Models – P/N: 52368
TREE # 2A
Liqui-SAFE VALVE DOES NOT TRIP
CHECK CONTROL BOARD LIGHT
RED GREEN
SEE TROUBLESHOOTING
TREE #2C
SEE TROUBLESHOOTING
TREE #2B
NO
NO LIGHT
CHECK
INCOMING
POWER
INCOMING
POWER OK?
CORRECT
INCOMING
POWER ISSUE
YES
CHECK
TRANSFORMER
WIRING
BAD WIRING
CONNECTIONS.
REPLACE OR REPAIR
ANY DAMAGED WIRING
YES
LOOSE
WIRING?
NO
CHECK
TRANSFORMER FUSE
YES
REPLACE FUSE AND
RESTART
VAPORIZER
BLOWN
FUSE?
YES
PROBLEM
FIXED?
NO
PROBLEM CAUSED BY
A BLOWN FUSE.
REPLACE TRANSFORMER
AND RESTART VAPORIZER.
NO
YES
ASDI Operations and Maintenance – TX Models – P/N: 52368
IS THE PROBLEM
FIXED?
NO
REPLACE
TEMPERATURE
CONTROLLER.
RESTART VAPORIZER
6-32
TREE # 2B
Liqui-SAFE VALVE DOES NOT TRIP
GREEN
YES
IS CONTACTOR
LATCHED?
NO
NO
SEE HEATER CORE
RESISTANCE ON
PAGE 6-37.
CHECK FUSE LINKS
NO
FUSE LINKS
OPEN?
YES
CHECK FOR LOOSE
WIRING
IS THERE A
LOOSE WIRE?
YES
TIGHTEN WIRES.
RESTART
VAPORIZER.
PRESS HI-LIMIT
BUTTON TO RESET
YES VAPORIZER
STARTS
WORKING?
NO
REPLACE OPEN
FUSE LINKS.
CONTACT ASDI
CHECK IF THERE
IS 24V AT THE
CONTACTOR
LEADING TO THE
TEMPERATURE
CONTROLLER
CHECK:
1. IF THERMOCOUPLE
CONNECTION IS LOOSE.
2. IF THERMOCOUPLE IS BAD
3. CHECK FOR SUFFICIENT
THERMAL GREASE IN THE
THERMOWELL
4. REMOVE DRAIN PLUG AND
CHECK FOR HEAVY ENDS
IF THE ABOVE ACTIONS DO
NOT FIX THE PROBLEM THEN
REPLACE TEMPERATURE
CONTROLLER BOARD.
NO 24V AT THE
CONTACTOR?
YES
REPLACE
CONTACTOR
6-33 ASDI Operations and Maintenance – TX Models – P/N: 52368
TREE # 2C
Liqui-SAFE VALVE DOES NOT TRIP
RED
NO IS THERMOCOUPLE
MOLEX LOOSE OR
DISCONNECTED?
YES
OPTIONAL
NO IS HIGH TEMP.
LIMIT
REACHED?
NO
IS FLOAT
SWITCH OR
PRESSURE
SWITCH
OPEN?
YES
REPLACE TEMP.
CONTROLLER.
RESTART
VAPORIZER
1. ASSESS SYSTEM
CAPACITY
2. PERFORM SOLENOID
VALVE LEAK TEST.
3. CHECK WIRING.
4. CHECK FUSE LINKS.
IF THE ABOVE ACTIONS
DO NOT FIX THE
PROBLEM CONTACT
ASDI.
YES
RECONNECT LOOSE OR
DISCONNECTED MOLEX
PRESS RED RESET BUTTON TO
RESTART VAPORIZER
IF THE ABOVE ACTIONS DO NOT
FIX THE PROBLEM THEN GO TO
THE NEXT STEP
PRESS RED RESET BUTTON TO
RESTART VAPORIZER.
IF PROBLEM REOCCURS THEN:
1. CHECK BOARD SETPOINT
2. CHECK FOR SUFFICIENT
THERMAL GREASE IN
THERMOWELL
3. CHECK THERMOCOUPLE
INSERTION DEPTH
4. REMOVE DRAIN PLUG AND
CHECK FOR HEAVY ENDS
IF THE ABOVE ACTIONS DO NOT
FIX THE PROBLEM THEN
CONTACT ASDI OR GO TO NEXT
STEP IF FLOAT OR PRESSURE
SWTITCH ARE INSTALLED.
ASDI Operations and Maintenance – TX Models – P/N: 52368 6-34
Full
Load
Voltage
Check
NOTE
Current flow depends on the applied voltage. Voltage lower than the specified voltage causes low current and may negatively affect operation. Make all measurements with the heater ON (Contactor closed).
WARNING
These tests include high voltage. Exercise great caution in making the following tests. Carelessness could result in severe injury or death. See additional warnings located at the beginning of this
Chapter.
FULL
LOAD
VOLTAGE
CHECK
Check heater voltage by measuring voltage at the contactor terminals. See Data sheet of your manual or rating plate on the vaporizer to determine the correct voltage reading of your vaporizer. Measure voltage between all connected poles of the contactor. The readings should be equal to +/- 3% of the value on the rating plate.
Figure 12 – Full load voltage check
POWER IN
MEASURE VOLTAGE
CONTROL BOARD
6-35
CONTACTOR
ASDI Operations and Maintenance – TX Models – P/N: 52368
Full
Load
Current
Check
NOTE
See fusible link detail below for typical fusible link installation.
WARNING
These tests include high voltage. Exercise great caution in making the following tests. Carelessness could result in severe injury or death. See additional warnings located at the beginning of this
Chapter.
Measure the current on each of the heater AC power input wires. See Data
Sheet or rating plate provided with your manual for the correct reading (line current) for your vaporizer. All wires should have readings equal to +/- 3% of the value listed on the rating plate.
Low current on all wires indicates low input voltage. Drastically different current readings may indicate a defective heater, defective wiring, or an open fusible link due to overheating. If a fusible link is open, contact the factory. Do not attempt to repair it.
Figure 13 – Full Load Current Check
FUSIBLE LINKS
POWER IN
MEASURE CURRENT
VIEW OF FUSIBLE
LINKS IN NORMAL
CONDITIONS
COPPER STRIP
POWER
INPUT
WIRING
VIEW OF FUSIBLE
LINKS IN OPEN
CONDITIONS
CONTROL
BOARD
AMP CLAMP
ASDI Operations and Maintenance – TX Models – P/N: 52368 6-36
TORREXX
Electric
Vaporizer
Data
Sheet
MODEL PHASE
VOLTAGE
(VAC)
TX240
TX320
TX320
TX320
TX320
TX320
TX 320
6-37
TX160
TX160
TX160
TX160
TX160
TX160
TX160
TX160
TX240
TX240
TX240
TX240
TX100
TX100
TX100
TX100
TX100
TX100
TX100
TX100
TX100
TX100
TX100
TX25
TX25
TX25
TX25
TX50
TX50
TX50
TX50
TX50
TX50
TX50
TX50
TX50
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
1
3
1
3
1
1
3
3
3
1
3
3
3
1
1
1
1
1
440
480
380
400
415
440
220
240
380
400
415
480
380
400
415
440
480
575
380
400
415
440
480
208
208
208
220
220
240
240
208
220
220
240
240
380
400
415
120
208
220
240
208
CURRENT
(A)
47.6
51.9
27.5
28.9
30.0
23.8
26.0
38.1
40.1
41.6
33.0
36.0
59.7
52.8
54.8
51.7
47.4
39.4
19.8
20.8
21.6
17.1
18.7
45.0
56.2
32.4
59.5
34.3
54.1
37.4
32.4
14.1
14.9
16.2
28.1
16.2
29.7
17.1
32.4
18.7
9.9
10.4
10.8
22.2
22.2
22.2
22.2
22.2
16.0
22.2
22.2
22.2
22.2
22.2
22.2
HEATER
RESISTANCE
(OHMS)
22.2
22.2
22.2
22.2
22.2
22.2
22.2
22.2
22.2
22.2
22.2
22.2
22.2
22.2
22.2
22.2
29.6
29.6
5.3
3.7
7.4
3.7
7.4
4.4
7.4
WIRE-TO-WIRE
RESISTANCE
(OHMS)
3.7
14.8
14.8
14.8
7.4
14.8
7.4
14.8
7.4
14.8
44.4
44.4
44.4
POWER
(kW)
13.0
14.4
15.5
13.1
15.5
16.2
11.7
11.7
13.1
13.1
13.0
15.5
5.8
6.5
6.5
7.8
7.8
6.5
7.2
7.8
3.9
2.9
3.3
3.9
5.8
16.0
16.0
16.0
16.0
16.0
16.0
16.0
11.5
11.5
11.5
11.5
5.3
5.3
16.0
16.0
16.0
21.3
21.3
11.5
11.5
11.5
15.4
18.1
21.5
18.1
20.0
21.5
18.1
21.5
25.1
27.8
29.9
25.1
11.5
8.8
8.8
8.8
8.8
8.8
15.4
7.4
8.8
8.8
9.8
11.7
29.9
39.3
36.6
39.3
39.4
39.4
16.9 16.9 39.2
ASDI Operations and Maintenance – TX Models – P/N: 52368
Heater
Core
Resistance
NOTE
Refer to the Bussing diagram in Appendix A for wire to wire resistance for your vaporizer.
CAUTION
Turn off electrical power at the disconnect before proceeding.
Carefully slide out the control panel for access to the heater wire connections on the contactor. Measure the resistance across each pair of wires. An incorrect resistance reading indicates a faulty heater element, a wiring problem, or an open fusible link.
Figure 14 – Heater Core Resistance Wiring Connections
READ WIRE TO WIRE RESISTANCE.
SEE HEATER WIRING DIAGRAM
ASDI Operations and Maintenance – TX Models – P/N: 52368 6-38
Solenoid
Valve
Leak
Test
1) Shut off the outlet isolation valve. The inlet isolation valve should be open. Start the vaporizer and allow it to heat up until the heaters shut off.
This allows any accumulated liquid in the vaporizer to be forced back toward the supply tank.
2) Disconnect the vaporizer by shutting off the power at the disconnect.
Shut off the inlet isolation valve. Cautiously bleed off any LPG pressure in the vaporizer and outlet supply piping. When the pressure reaches no pressure in the vaporizer, remove and then reinstall pressure gauge and verify 0 pressure.
3) Turn on the inlet isolation valve. The solenoid valve is closed and you should not have any pressure build up in the vaporizer. If pressure increases, the solenoid valve is leaking and needs to be repaired or replaced.
Figure 15 – Solenoid Valve Leak Test Components
VAPOR DISCHARGE OUTLET
ISOLATION VALVE
VAPOR
PRESSURE
GAUGE
FIRST STAGE
REGULATOR
VAPOR OUT
SOLENOID VALVE
STRAINER
LIQUID INLET
ISOLATION VALVE
LIQUID IN
6-39 ASDI Operations and Maintenance – TX Models – P/N: 52368
Solenoid
Valve
Electrical
Test
NOTE
A multimeter is required for the following test.
CAUTION
Turn off electrical power at the disconnect before performing this procedure.
Open the electrical housing at the vaporizer base. Disconnect the 2-PIN Molex plug connector and measure resistance between the pins. You should measure approximately 3 ohms. If not, replace the solenoid coil.
Figure 16 – Solenoid Valve Electrical Test
RESISTANCE SHOULD BE
APPROXIMATELY 3 OHMS
1. DISCONNECT
SOLENOID MOLEX
FROM MAIN HARNESS
2. MEASURE
RESISTANCE
3. RECONNECT WHEN
FINISHED
ASDI Operations and Maintenance – TX Models – P/N: 52368 6-40
Thermocouple
Sensor
Replacement
CAUTION
Always disconnect power to vaporizer before servicing.
1) Shut off power at the disconnect.
2) Remove the control box lid.
3) Disconnect the main power wires attached to the contactor and the wires going to the heaters.
4) Slide the circuit panel half way out of the control box.
5) Disconnect the yellow and red thermocouple wires from control board.
6) The thermocouple can now be removed from the center of the core (see
Figure 18 and 19). Two types of locking collars have been used on the sensors.
Figure 17 – TORREXX Box showing Thermocouple location
THERMOCOUPLE WIRES
6-41 ASDI Operations and Maintenance – TX Models – P/N: 52368
FIGURE 18 – Thermocouple Sensor with Bayonet Style Retainer
1) To remove a sensor fitted with the bayonet style retainer, push gently on the retainer while turning to the left. When the retainer is disengaged, pull out the old temperature sensor.
2) Use a short, flat-blade screwdriver to remove the adapter.
3) Install the new spring tab retainer using an appropriately sized open end wrench (1/2” or 13mm).
4) Install the new sensor by applying a small amount of heat transfer grease to the sensor tube and re-inserting in the unit. Squeeze the spring tab while inserting the sensor. Push firmly until the sensor is fully engaged. There should be at least ½” of sheath remaining.
5) When connecting new thermocouple wires back to the control board ensure that the yellow wires are connected to the yellow terminals and red wires to the red terminals. Do not over tighten terminal screws!
Connect the main power wires back to the contactor and re-install the control box lid. Torque lid bolts to 19.5 ft-lb. Failure to properly torque lid bolts may compromise explosion proof enclosure rating and may lead to water entering the enclosure.
6) Restart vaporizer and check operation.
ASDI Operations and Maintenance – TX Models – P/N: 52368 6-42
TORREXX
OPTIONS
TANK VAPOR
PRESSURE
REGULATOR*
ISOLATION
VALVE*
7
Economy
Operation
The Economy Option minimizes the electric power required to meet your vapor demand by shutting off the outlet of the vaporizer when the natural vaporization rate of the storage tank is able to supply enough vapor to meet the demand. A pressure sensing valve is specially developed to sense the upstream pressure. The valve opens when the tank pressure falls below 30PSIG, and closes at 60PSIG. The pressure sensing valve is a mechanical device and it operates independently to the electrical controls.
The Economy Option will NOT function if a pump is used.
The pressure set-point of the TORREXX Economy Valve is nonadjustable.
The Economy is normally a factory-installed option. However, a separate Economy valve can be purchased as an add-on in the field.
For the Economy Valve field installation kit, use ASDI PN: 41051.
Make sure that the Economy Valve is correctly installed. Verify the flow direction on the Rating Plate.
Figure 19 – TORREXX Economy valve installation
1.
2.
3.
NOTES
LIQUID PIPING LOSSES BETWEEN THE VAPORIZER AND THE
TANK MUST NOT EXCEED THE HYDROSTATIC HEAD WHEN THE
PUMP IS SHUT OFF
INSTALL VAPORIZER 1 ST STAGE REGULATOR UPSTREAM OF
THE TANK VAPOR PRESSSURE CONNECTION POINT.
SET 1 ST STAGE VAPORIZER REULATOR 2-4 PSIG HIGHER THAN
4.
*BY OTHERS
TANK VAPOR PRESSURE REGULATOR SET-POINT.
NO CHECK VALVES IN LIQUID LINE. LIQUID MUST BE ABLE TO
FLOW IN BOTH DIRECTIONS.
VAPOR BY-PASS LINE
OUTLET ISOLATION VALVE* ISOLATION
VALVE*
(VAPOR)
TO LOAD
PRESSURE GAUGE*
ASDI ECONOMY VALVE
SENSES UPSTREAM
PRESSURE (OPEN 30PSIG
CLOSED 60PSIG)
PRESSURE GAUGE*
STORAGE TANK
VAPORIZER
REGULATOR*
STRAINER WITH
MAGNET FOR IRON
PARTICLE PICK-UP*
SEAL OFF REQUIRED*
ELECTRIC SERVICE
REQUIRED*
ISOLATION VALVE
W/HYDROSTATIC
RELIEF*
LIQUID
ISOLATION VALVE”
Note: Economy option cannot be used on an installation that requires a pump.
7-43 ASDI Operations and Maintenance – TX Models – P/N: 52368
TORREXX
Economy
Valve
Maintenance
TORREXX Economy Valve operates by sensing the pressure of the Vaporizer and Storage Tank. The Economy
Valve consists of a moving piston which opens and closes the valve’s outlet. The movement of the piston is driven by the pressure force balance between two different sized o-rings and a spring.
Follow the instructions below and perform maintenance on the Economy Valve:
Figure 20A – STEP 1 – Unscrew the Inlet Housing from the Outlet Housing.
Figure 20B – STEP 2 – Replace the two O-rings (ASDI PN 39012 and 39014). Apply excess lithium o-ring grease.
39012
ASDI Operations and Maintenance – TX Models – P/N: 52368 7-44
7-45
Figure 20C – STEP 3 – Clean all o-ring contact surfaces and the bottom surface of the Outlet Housing.
Apply excess lithium o-ring grease.
Figure 20D – STEP 4 – Clean all piston surfaces. Apply excess lithium grease on o-rings.
Figure 20E – STEP 5 – Make sure that the Pin Hole is clear and the spring is undamaged. Carefully reassemble all the parts. Apply lubrication grease on the straight threads if necessary.*
ASDI Operations and Maintenance – TX Models – P/N: 52368
* - The threads between the Inlet Housing and the Outlet Housing are straight threads and are designed to be hand tightened. Gas will NOT leak through these threads because of the seals from the two o-rings. However, the
Inlet Housing MUST be screwed all the way down for the Valve to accurately function at the set pressure. DO
NOT apply sealing agent or Teflon tape on these threads.
Refer to the table below for any replacement parts in the TORREXX Economy Valve.
QUANTITY ASDI PART NO.
1
1
1
1
1
1
1
2
5001-5023
5001-5025
5001-5024
39012
39014
39038
5001-5026
60204
DESCRIPTION
INLET HOUSING
OUTLET HOUSING
VALVE PISTON
VALVE O-RING (LARGE)
VALVE O-RING (SMALL)
VALVE SPRING
VALVE RATING PLATE
RIVET
Mercury
Relay
The life of the vaporizer can be further extended by using a Mercury Relay. Compared to a “dry” contactor, a
Mercury Relay reduces the wear and tear each time the heater cycles. A larger explosion-proof enclosure is also used which improves access to the electrical controls.
Mercury Relay is standard on TX240 and TX320 vaporizers in most markets. It is suitable for Class I Division 1
Group D locations and is only available in the NEC configuration. Please contact ASDI if you want to implement this option on TX 160 or want to find out if Mercury Relay option can be used in your market.
The Mercury Relay Option can be integrated with all the other TORREXX options (i.e. Economy, Remote, etc.) In addition, customized options such as external lamps/indicators, on/off switches are also available. Please consult
ASDI for details.
TX
Remote
Box
Includes remote start/stop capability and a status light indicating the vaporizer is ready for operation (solenoid valve open). Connection between the box and the vaporizer is established trough the wire harness found on the inside the vaporizer explosion proof enclosure. Remote box is intended for indoor or outdoor installation in general purpose location.
FIGURE 21 – Remote START/STOP box
ASDI Operations and Maintenance – TX Models – P/N: 52368 7-46
Valve
and
Strainer
Package
For TX25 to TX320
For TX19AA to TX240AA
ASDI PN: 36922 ¾” NPT inlet, 1” NPT outlet
ASDI PN: 36925
Filtaire
–
Contaminant
Separator
The Filtaire is a filtering device designed to trap heavy hydrocarbons commonly present in LPG vapor. It also traps other materials, which may be in the gas due to storage conditions and internal condition of the equipment.
Impurities are collected in the system and periodically removed through the system blow down drain. Residual heavy end hydrocarbons with boiling points higher than pure LPG are trapped by the filter and fall to the bottom for removal.
A complete Filtaire system consists of inlet and outlet connections, a blow-down drain (5), a pressure gauge (4), a vent which is normally plugged (6), and a bypass valve system for cleaning (1, 2, and 3). The bypass valves enable the system to continue operating when the Filtaire is removed for cleaning.
FIGURE 22 – Filtaire Operation
Leak Test
1. Close outlet valve.
2. Slowly open inlet valve and allow pressure to equalize in the vaporizer.
3. Apply a small amount of soap/water solution to ALL pipe connections.
4. Check for any leaks by observing new bubble formation in the soap/water solution.
Repair any leaks before continuing.
7-47 ASDI Operations and Maintenance – TX Models – P/N: 52368
APPENDIX A
TECHNICAL
INFORMATION
TORREXX Vertical Electric Vaporizer Data Sheet
LPG Systems
Refer to Nameplate on unit for the model and voltage information then look up specific information on the tables below.
General Specifications: Applies to all units
Electrical: 50 – 60 Hz, NEMA 4, 1 Phase units are 2 wire, 3 Phase units are 3 wire
Starting Temperature: 55 Deg. C 131 Deg. F
Operating Temperature: 71-79 Deg. C 160-175 Deg. F
High Temperature Limit: 171 Deg. C 340 Deg. F
Connections: ¾” FNPT – Inlet; 1” FNPT – Outlet
1” FNPT, Conduit Seal-Off by others Conduits:
Type of Service: Propane Vaporization
ASME Pressure Vessel: 250 PSIG MAWP @ 250ºF
-20ºF MDMT @ 250 PSIG
Heat Exchanger Area: 2.9 ft 2 / 0.269 m 2 TX25, TX50 and TX100
Dry Weight:
4.3 ft
5.4 ft
7.1 ft
2
2
2
/ 0.399 m
/ 0.503 m
/ 0.660 m
2
2
2
128 lbs / 58.1 kg
TX160
TX240
TX320
TX25, TX50 and TX100
145 lbs* / 65.8 kg*
155 lbs* / 70.3 kg*
TX160
TX240
173 lbs* / 78.5 kg* TX320
* - Add 50 lbs / 22.7 kg if vaporizer if the Mercury Relay option is installed.
Wiring:
Other:
Meets NFPA Pamphlet 70 requirements for Class I Division 1 Group D
Meets NFPA Pamphlet 58 requirements for electric vaporizers and may be installed per indirect fired vaporizers limitations.
“TORREXX” is a trademark of Algas-SDI International LLC.
TORREXX VERTICAL ELECTRIC VAPORIZER DATA SHEET FOR LPG SYSTEMS
MODEL PHASE VOLTAGE
TX160
TX160
TX160
TX160
TX160
TX160
TX160
TX240
TX240
TX240
TX-50
TX100
TX100
TX100
TX100
TX100
TX100
TX100
TX100
TX160
TX240
TX240
TX320
TX320
TX320
TX320
TX320
TX320
TX-25
TX-25
TX-25
TX-25
TX-50
TX-50
TX-50
TX100
TX100
TX100
TX-50
TX-50
TX-50
TX-50
TX-50
1
1
3
3
3
3
3
1
1
1
1
1
1
1
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
220
240
208
220
240
380
400
120
208
220
240
208
220
240
208
415
208
220
240
380
400
415
440
480
415
440
480
380
400
415
440
480
575
208
220
240
380
400
415
440
480
380
400
EQUIPMENT
DRAWING
ELECTRICAL
DRAWING
BUSSING
DIAGRAM
5001 - 6001 5001-7008 0620 - 7007
5001 - 6001 5001-7008 0620 - 7003
5001 - 6001 5001-7008 0620 - 7003
5001 - 6001 5001-7008 0620 - 7003
5001 - 6001 5001-7008 0620 - 7004
5001 - 6001 5001-7008 0620 - 7004
5001 - 6001 5001-7008 0620 - 7004
5001 - 6001 5001-7008 0620 - 7007
5001 - 6001 5001-7008 0620 - 7007
5001 - 6001 5001-7008 0620 - 7008
5001 - 6001 5001-7008 0620 - 7005
5001 - 6001 5001-7008 0620 - 7005
5001 - 6001 5001-7008 0620 - 7005
5001 - 6001 5001-7008 0620 - 7028
5001 - 6001 5001-7008 0620 - 7028
5001 - 6001 5001-7008 0620 - 7028
5001 - 6001 5001-7008 0620 - 7009
5001 - 6001 5001-7008 0620 - 7009
5001 - 6001 5001-7008 0620 - 7009
5001 - 6001 5001-7008 0620 - 7010
5001 - 6001 5001-7008 0620 - 7010
5001 - 6001 5001-7008 0620 - 7010
5001 - 6001 5001-7008 0620 - 7011
5001 - 6001 5001-7008 0620 - 7011
5001 - 6001 5001-7008 0620 - 7009
5001 - 6001 5001-7008 0620 - 7009
5001 - 6001 5001-7008 0620 - 7012
5001 - 6001 5001-7008 0620 - 7010
5001 - 6001 5001-7008 0620 - 7010
5001 - 6001 5001-7008 0620 - 7010
5001 - 6001 5001-7008 0620 - 7011
5001 - 6001 5001-7008 0620 - 7011
5001 - 6001 5001-7008 0620 - 7010
5001 - 6001 5001-7008 0620 - 7010
5001 - 6001 5001-7008 0620 - 7010
5001 - 6001 5001-7008 0620 - 7011
5001 - 6001 5001-7008 0620 - 7011
5001 - 6001 5001-7008 0620 - 7010
5001 - 6001 5001-7008 0620 - 7010
5001 - 6001 5001-7008 0620 - 7010
5001 - 6001 5001-7008 0620 - 7011
5001 - 6001 5001-7008 0620 - 7011
5001 - 6001 5001-7008 0620 - 7010
11
12
13
14
8
9
10
15
16
17
18
19
4
5
6
7
1
2
3
20
21
22
23
24
REFERENCE
KEY
10
11
12
6
7
8
9
1
2
3
4
5
13
14
15
16
17
18
19
20
21
22
23
24
REFERENCE
KEY
TORREXX Electric Vaporizer Spare Parts and Accessories
SPARE PARTS
TEMPERATURE CONTROL BOARD
TRANSFORMER
CONTACTOR
THERMOCOUPLE
Liqui-SAFE VALVE
PRESSURE RELIEF VALVE
RAIN CAP
FUSIBLE LINK
INLET SOLENOID
FUSE KIT
ECONOMY VALVE FIELD INSTALL KIT
MERCURY RELAY CONTACTOR
TRANSFORMER (MERCURY RELAY)
WIRE HARNESS (MERCURY RELAY)
PIPE AWAY ADAPTOR
VALVE, GAUGE AND STRAINER KIT
DRAIN ASSEMBLY
STAND
WIRE HARNESS (MAIN)
CORROSION INHIBITING TAPE
INLET SOLENOID KIT
Liqui-SAFE VALVE O-RING KIT
REMOTE START/STOP BOX
BALANCING ORIFICE
SPARE PARTS
TEMPERATURE CONTROL BOARD
TRANSFORMER
CONTACTOR
THERMOCOUPLE
Liqui-SAFE VALVE
PRESSURE RELIEF VALVE
RAIN CAP
FUSIBLE LINK
INLET SOLENOID
FUSE KIT
ECONOMY VALVE FIELD INSTALL KIT
MERCURY RELAY CONTACTOR
TRANSFORMER (MERCURY RELAY)
WIRE HARNESS (MERCURY RELAY)
PIPE AWAY ADAPTOR
VALVE, GAUGE AND STRAINER KIT
DRAIN ASSEMBLY
STAND
WIRE HARNESS (MAIN)
CORROSION INHIBITING TAPE
INLET SOLENOID KIT
Liqui-SAFE VALVE O-RING KIT
REMOTE START/STOP BOX
BALANCING ORIFICE
TX100
380V
400V
415V
53889
52607-01
53630
5001-4027-01
5001-3003
34876
35379
33139
36111
52222
41051
N/A
N/A
N/A
34877
36922
5010-3003
20437
53820
60806
40287
40421
41067
64004
TX25
120V
53889
52605-01
53630
5001-4027-01
5001-3003
34876
35379
33139
36111
52222
41051
N/A
N/A
N/A
34877
36922
5010-3003
20437
53820
60806
40287
40421
41067
64004
TX100
440V
480V
53889
52608-01
53630
5001-4027-01
5001-3003
34876
35379
33139
36111
52222
41051
N/A
N/A
N/A
34877
36922
5010-3003
20437
53820
60806
40287
40421
41067
64004
TX25
208V
220V
240V
53889
52606-01
53630
5001-4027-01
5001-3003
34876
35379
33139
36111
52222
41051
N/A
N/A
N/A
34877
36922
5010-3003
20437
53820
60806
40287
40421
41067
64004
TX160
208V
220V
240V
53889
52606-01
53630
5001-4027-02
5001-3003
34876
35379
33139
36111
52222
41051
N/A
N/A
N/A
34877
36922
5010-3003
20437
53820
60806
40287
40421
41067
64004
TX50
208V
220V
240V
53889
52606-01
53630
5001-4027-01
5001-3003
34876
35379
33139
36111
52222
41051
N/A
N/A
N/A
34877
36922
5010-3003
20437
53820
60806
40287
40421
41067
64004
TX50
380V
400V
415V
53889
52607-01
53630
5001-4027-01
5001-3003
34876
35379
33139
36111
52222
41051
N/A
N/A
N/A
34877
36922
5010-3003
20437
53820
60806
40287
40421
41067
64004
TX160
380V
400V
415V
53899
52607-01
53630
5001-4027-02
5001-3003
34876
35379
33139
36111
52222
41051
N/A
N/A
N/A
34877
36922
5010-3003
20437
53820
60806
40287
40421
41067
64004
TX100
208V
220V
240V
53889
52606-01
53630
5001-4027-01
5001-3003
34876
35379
33139
36111
52222
41051
N/A
N/A
N/A
34877
36922
5010-3003
20437
53820
60806
40287
40421
41067
64004
TX160
440V
480V
53889
52608-01
53630
5001-4027-02
5001-3003
34876
35379
33139
36111
52222
41051
N/A
N/A
N/A
34877
36922
5010-3003
20437
53820
60806
40287
40421
41067
64004
6
REFERENCE
KEY
12
13
14
15
9
10
11
16
17
18
19
5
6
7
8
1
2
3
4
20
21
22
23
SPARE PARTS
TEMPERATURE CONTROL BOARD
TRANSFORMER
CONTACTOR
THERMOCOUPLE
Liqui-SAFE VALVE
PRESSURE RELIEF VALVE
RAIN CAP
FUSIBLE LINK
INLET SOLENOID
FUSE KIT
ECONOMY VALVE FIELD INSTALL KIT
MERCURY RELAY CONTACTOR
TRANSFORMER (MERCURY RELAY)
WIRE HARNESS (MERCURY RELAY)
PIPE AWAY ADAPTOR
VALVE, GAUGE AND STRAINER KIT
DRAIN ASSEMBLY
STAND
WIRE HARNESS (MAIN)
CORROSION INHIBITING TAPE
INLET SOLENOID KIT
Liqui-SAFE VALVE O-RING KIT
REMOTE START/STOP BOX
TX240
380V
400V
415V
53889
52607-01
53630
5001-4027-03
5001-3003
34876
35379
33139
36111
52222
41051
53324
52607-01
53823
34877
36922
5010-3003
20437
53820
60806
40287
40421
41067
TX240
440V
480V
53889
52608-01
53630
5001-4027-03
5001-3003
34876
35379
33139
36111
52222
41051
53324
52608-01
53823
34877
36922
5010-3003
20437
53820
60806
40287
40421
41067
24 BALANCING ORIFICE 64004 64004
FIGURE 22 – TORREXX electric vaporizer major components and accessories
7
5
8
TX320
380V
400V
415V
53889
52607-01
53630
5001-4027-04
5001-3003
34876
35379
33139
36111
52222
41051
53324
52607-01
53823
34877
36922
5010-3003
20437
53820
60806
40287
40421
41067
64004
4
TX320
440V
480V
575V
53889
52608-01
53630
5001-4027-04
5001-3003
34876
35379
33139
36111
52222
41051
53324
52608-01
53823
34877
36922
5010-3003
20437
53820
60806
40287
40421
41067
64004
20
3
2
1
19
TORREXX Vertical Electric Vaporizer Data Sheet
NEMKO LPG Systems
Refer to Nameplate on unit for the model and voltage information then look up specific information on the tables below.
General Specifications: Applies to all units
Electrical: 50 – 60 Hz, NEMA 4, 1 Phase units are 2 wire, 3 Phase units are 3 wire
Starting Temperature: 55 Deg. C 131 Deg. F
Operating Temperature: 71-79 Deg. C 160-175 Deg. F
High Temperature Limit: 171 Deg. C 340 Deg. F
Connections: ¾” FNPT – Inlet; 1” FNPT – Outlet
Conduits:
Type of Service:
1” FNPT, Conduit Seal-Off by others
Propane Vaporization
ASME Pressure Vessel: 250 PSIG MAWP @ 250ºF
-20ºF MDMT @ 250 PSIG
Heat Exchanger Area: 2.9 ft 2 / 0.269 m 2 TX25, TX50 and TX100
4.3 ft 2 / 0.399 m 2 TX160
5.4 ft 2 / 0.503 m 2 TX240
7.1 ft 2 / 0.660 m 2 TX320
Dry Weight: 128 lbs / 58.1 kg
145 lbs / 65.8 kg
TX25, TX50 and TX100
TX160
155 lbs / 70.3 kg
173 lbs / 78.5 kg
TX240
TX320
Hazardous Area Rating: NEMKO 04 ATEX 1026X Ex d IIB T3
TO AVOID POTENTIAL ELECTROSTATIC CHARGING HAZARD, ALWAYS USE A DAMP CLOTH FOR
CLEANING THE INSULATION JACKET. AVOID DRY RUBBING OF THE INSULATION JACKET.
2460
0496
“TORREXX” is a trademark of Algas-SDI International LLC.
TORREXX VERTICAL ELECTRIC VAPORIZER DATA SHEET FOR LPG SYSTEMS
(NEMKO)
MODEL PHASE VOLTAGE
TX-50
TX-50
TX-50
TX100
TX100
TX100
TX100
TX100
TX160
TX-25
TX-25
TX-50
TX-50
TX100
TX100
TX-50
TX-50
TX160
TX160
TX160
TX160
TX240
TX240
TX240
TX320
TX320
TX320
3
3
3
3
3
3
3
3
3
3
1
1
1
1
1
1
3
3
3
3
3
3
3
3
3
3
3
240
380
400
415
220
240
380
400
415
220
220
240
220
240
220
240
220
240
380
400
415
380
400
415
380
400
415
EQUIPMENT
DRAWING
ELECTRICAL
DRAWING
BUSSING
DIAGRAM
5001 - 6003 5001-7008 0620 - 7003
5001 - 6003 5001-7008 0620 - 7003
5001 - 6003 5001-7008 0620 - 7004
5001 - 6003 5001-7008 0620 - 7004
5001 - 6003 5001-7008 0620 - 7007
5001 - 6003 5001-7008 0620 - 7008
5001 - 6003 5001-7008 0620 - 7005
5001 - 6003 5001-7008 0620 - 7005
5001 - 6003 5001-7008 0620 - 7028
5001 - 6003 5001-7008 0620 - 7028
5001 - 6003 5001-7008 0620 - 7028
5001 - 6003 5001-7008 0620 - 7009
5001 - 6003 5001-7008 0620 - 7009
5001 - 6003 5001-7008 0620 - 7010
5001 - 6003 5001-7008 0620 - 7010
5001 - 6003 5001-7008 0620 - 7010
5001 - 6003 5001-7008 0620 - 7009
5001 - 6003 5001-7008 0620 - 7012
5001 - 6003 5001-7008 0620 - 7010
5001 - 6003 5001-7008 0620 - 7010
5001 - 6003 5001-7008 0620 - 7010
5001 - 6003 5001-7008 0620 - 7010
5001 - 6003 5001-7008 0620 - 7010
5001 - 6003 5001-7008 0620 - 7010
5001 - 6003 5001-7008 0620 - 7010
5001 - 6003 5001-7008 0620 - 7010
5001 - 6003 5001-7008 0620 - 7010
TORREXX Electric Vaporizer Spare Parts and Accessories (NEMKO)
10
11
12
6
7
8
9
13
14
15
16
1
2
3
4
5
17
18
19
20
21
REFERENCE
KEY
10
11
12
6
7
8
9
13
14
15
16
1
2
3
4
5
17
18
19
20
21
REFERENCE
KEY
SPARE PARTS
TEMPERATURE CONTROL BOARD
TRANSFORMER
CONTACTOR
THERMOCOUPLE
Liqui-SAFE VALVE
PRESSURE RELIEF VALVE
RAIN CAP
FUSIBLE LINK
INLET SOLENOID
FUSE KIT
ECONOMY VALVE FIELD INSTALL KIT
PIPE AWAY ADAPTOR
VALVE, GAUGE AND STRAINER KIT
DRAIN ASSEMBLY
STAND
WIRE HARNESS (MAIN)
CORROSION INHIBITING TAPE
INLET SOLENOID KIT
Liqui-SAFE VALVE O-RING KIT
REMOTE START/STOP BOX
BALANCING ORIFICE
SPARE PARTS
TEMPERATURE CONTROL BOARD
TRANSFORMER
CONTACTOR
THERMOCOUPLE
Liqui-SAFE VALVE
PRESSURE RELIEF VALVE
RAIN CAP
FUSIBLE LINK
INLET SOLENOID
FUSE KIT
ECONOMY VALVE FIELD INSTALL KIT
PIPE AWAY ADAPTOR
VALVE, GAUGE AND STRAINER KIT
DRAIN ASSEMBLY
STAND
WIRE HARNESS (MAIN)
CORROSION INHIBITING TAPE
INLET SOLENOID KIT
Liqui-SAFE VALVE O-RING KIT
REMOTE START/STOP BOX
BALANCING ORIFICE
TX100
380V
400V
415V
53889
52607-01
53630
5001-4027-01
5001-3003
34876
35379
33139
33418
52222
41051
34877
36922
5010-3003
20437
53820
60806
40249
40421
41067
64004
TX25
120V
53889
52605-01
53630
5001-4027-01
5001-3003
34876
35379
33139
33418
52222
41051
34877
36922
5010-3003
20437
53820
60806
40249
40421
41067
64004
TX100
440V
480V
53889
52608-01
53630
5001-4027-01
5001-3003
34876
35379
33139
33418
52222
41051
34877
36922
5010-3003
20437
53820
60806
40249
40421
41067
64004
TX25
208V
220V
240V
53889
52606-01
53630
5001-4027-01
5001-3003
34876
35379
33139
33418
52222
41051
34877
36922
5010-3003
20437
53820
60806
40249
40421
41067
64004
TX160
208V
220V
240V
53889
52606-01
53630
5001-4027-02
5001-3003
34876
35379
33139
33418
52222
41051
34877
36922
5010-3003
20437
53820
60806
40249
40421
41067
64004
TX50
208V
220V
240V
53889
52606-01
53630
5001-4027-01
5001-3003
34876
35379
33139
33418
52222
41051
34877
36922
5010-3003
20437
53820
60806
40249
40421
41067
64004
TX50
380V
400V
415V
53889
52607-01
53630
5001-4027-01
5001-3003
34876
35379
33139
33418
52222
41051
34877
36922
5010-3003
20437
53820
60806
40249
40421
41067
64004
TX160
380V
400V
415V
539889
52607-01
53630
5001-4027-02
5001-3003
34876
35379
33139
33418
52222
41051
34877
36922
5010-3003
20437
53820
60806
40249
40421
41067
64004
TX160
440V
480V
53889
52608-01
53630
5001-4027-02
5001-3003
34876
35379
33139
33418
52222
41051
34877
36922
5010-3003
20437
53820
60806
40249
40421
41067
64004
TX100
208V
220V
240V
53889
52606-01
53630
5001-4027-01
5001-3003
34876
35379
33139
33418
52222
41051
34877
36922
5010-3003
20437
53820
60806
40249
40421
41067
64004
REFERENCE
KEY
10
11
12
13
14
15
16
5
6
7
8
9
1
2
3
4
17
18
19
20
21
SPARE PARTS
TEMPERATURE CONTROL BOARD
TRANSFORMER
CONTACTOR
THERMOCOUPLE
Liqui-SAFE VALVE
PRESSURE RELIEF VALVE
RAIN CAP
FUSIBLE LINK
INLET SOLENOID
FUSE KIT
ECONOMY VALVE FIELD INSTALL KIT
PIPE AWAY ADAPTOR
VALVE, GAUGE AND STRAINER KIT
DRAIN ASSEMBLY
STAND
WIRE HARNESS (MAIN)
CORROSION INHIBITING TAPE
INLET SOLENOID KIT
Liqui-SAFE VALVE O-RING KIT
REMOTE START/STOP BOX
BALANCING ORIFICE
TX240
380V
400V
415V
53889
52607-01
53630
5001-4027-03
5001-3003
34876
35379
33139
36111
52222
41051
34877
36922
5010-3003
20437
53820
60806
40249
40421
41067
64004
TX240
440V
480V
53889
52608-01
53630
5001-4027-03
5001-3003
34876
35379
33139
36111
52222
41051
34877
36922
5010-3003
20437
53820
60806
40249
40421
41067
64004
TX320
380V
400V
415V
53889
52607-01
53630
5001-4027-04
5001-3003
34876
35379
33139
36111
52222
41051
34877
36922
5010-3003
20437
53820
60806
40249
40421
41067
64004
TX320
440V
480V
575V
53889
52608-01
53630
5001-4027-04
5001-3003
34876
35379
33139
36111
52222
41051
34877
36922
5010-3003
20437
53820
60806
40249
40421
41067
64004
PRESSURE GAUGE
RATING PLATE
HEATING ELEMENT
.XX .XXX
(4) 1/2" DIA MOUNTING HOLES CONTROL BOX MOUNTING CLAMP
6" 152
Liqui-SAFE VALVE
INSULATION JACKET
MERCURY RELAY CONTROL BOX
3/4" FNPT LIQUID INLET VALVE
CONTROL HOUSING COVER
10 GA WIRE MESH OR DEFORMED REBAR
1 8
THIRD ANGLE PROJECTION
DO NOT SCALE DRAWING
3 4
1 4
1" FNPT VAPOR OUTLET
TX240 52" [1320] TX320 59" [1500]
3 PHASE ELECTRICAL SERVICE (BY OTHERS) 1-1/4" FNPT (THREAD PROTECTOR INSTALLED FOR SHIPPING) FACTORY INSTALLED CONDUIT WITH SEAL OFF
1 4
TX240 56 3/4" [1313] TX320 63 3/4" [1619]
NOTES: 1. ALL DIMMENSIONS ARE IN INCHES [mm]. 2. FM AND FMc APPROVED FOR USE IN CLASS 1 DIVISION 1 GROUP D AREAS. 3. EXPLOSION PROOF CONTROL BOX MEETS NEMA 4 REQUIREMENTS. 4. VAPORIZER PRESSURE VESSEL RATED AT 250 PSIG [17.6 KG/CM 7. SUITABLE FOR INDOOR/OUTDOOR INSTALLATION. 8. VAPORIZER TO BE SECURED THROUGH THE FOUR MOUNTING HOLES ON ABOVE GROUND, LEVEL, SOLID, NON-COMBUSTIBLE BASE. 9. AVOID DRY RUBBING OF THE INSULATION JACKET TO PREVENT ELECTROSTATIC CHARGING HAZARD. ALWAYS USE DAMP CLOTH FOR CLEANING. 10. ECONOMY VALVE OPTION AVAILABLE UPON REQUEST. 11. APROXIMATE SHIPPING WEIGHT: TX240 (205lbs.) TX320 (223lbs.)
SET-POINT. 3.
.XXX .XX
ASCO Valve used by Algas-SDI
SOLENOID NOISE
Solenoid valves emit a sound when operated. When energized, they emit a clicking sound. Also, accompanying the operation of most AC valves, is AC hum.
Whether or not AC hum is objectionable actually depends on the requirements and opinion of the user. Normal AC hum is the result of the constantly reversing magnetic field produced by alternating current. The constantly reversing magnetic field can cause vibrations in the solenoid parts.
1. Solenoid noise due to damage solenoid parts such as bent solenoid base assembly, stretched return springs, loose parts, etc.
Solution: Inspect valve internals and exterior. Replaced damaged
parts.
2. Solenoid noise due to foreign matter between the core and plug-nut. When foreign matter is trapped between the core and plug-nut, the core assembly will rock back and forth at 60 hertz. Eventually, the core and plug-nut face will be distorted, at which time the noise can continue even though the foreign material may have been flushed or removed from the valve.
Solution: Replace damaged parts entirely, clean and reassemble.
3. Solenoid noise due to damaged coil. On rare occasions, a severe voltage spike or over voltage can potentially short a small portion of the coil winding.
This shorting can cause solenoid noise and coil overheating. However, it would normally lead to rapid coil burnout. The solenoid parts, however, could be damaged enough that the noise would continue even after the coil was replaced due to the deformation produced during the peening process.
4. Missing solenoid parts can severely weaken the magnetic circuit. This can produce a solenoid noise condition. As discussed above, it will probably also result in coil burn-out.
Solution: Replace damaged parts, replace lost parts, clean and re-
assemble.
In general, when a noise condition has been encountered, the source of the problem should be determined and eliminated. The valve should then be thoroughly inspected to insure that it is yet repairable. Most times, simple installation of a spare parts kit and a solenoid base sub assembly can restore a valve to like new condition. The restored and reinstalled solenoid valve should be tested to insure proper operation, and a voltage check should be made at the solenoid valve while the valve is energized. In addition, a current reading can be obtained and compared with catalog specifications to verify normal solenoid and coil operation.
Note: The coil may have been damaged due to excessive current draw of at damaged shading coil within the solenoid valve. A partial rebuilding of a valve damaged by a noise condition can prove useless as the noise condition would continue. The entire valve should be dismantled and inspected and cleaned. All parts supplied in a spare parts kit should be installed. Further, and additional solenoid parts damaged by a noise condition such as a solenoid base sub assembly, should be replaced. Examine valve seating, pistons and the valve body to verify that they have not been damaged. Damage to major portions of the valve may make repairing the valve uneconomical.
Should a noise condition be encountered, immediate action may prevent any damage to the solenoid valve itself.
SOLENOID NOISE
Solenoid valves emit a sound when operated. When energized, they emit a clicking sound. Also, accompanying the operation of most AC valves, is AC hum.
Whether or not AC hum is objectionable actually depends on the requirements and opinion of the user. Normal AC hum is the result of the constantly reversing magnetic field produced by alternating current. The constantly reversing magnetic field can cause vibrations in the solenoid parts.
1. Solenoid noise due to damage solenoid parts such as bent solenoid base assembly, stretched return springs, loose parts, etc.
Solution: Inspect valve internals and exterior. Replaced damaged
parts.
2. Solenoid noise due to foreign matter between the core and plug-nut. When foreign matter is trapped between the core and plug-nut, the core assembly will rock back and forth at 60 hertz. Eventually, the core and plug-nut face will be distorted, at which time the noise can continue even though the foreign material may have been flushed or removed from the valve.
Solution: Replace damaged parts entirely, clean and reassemble.
3. Solenoid noise due to damaged coil. On rare occasions, a severe voltage spike or over voltage can potentially short a small portion of the coil winding.
This shorting can cause solenoid noise and coil overheating. However, it would normally lead to rapid coil burnout. The solenoid parts, however, could be damaged enough that the noise would continue even after the coil was replaced due to the deformation produced during the peening process.
4. Missing solenoid parts can severely weaken the magnetic circuit. This can produce a solenoid noise condition. As discussed above, it will probably also result in coil burn-out.
Solution: Replace damaged parts, replace lost parts, clean and re-
assemble.
In general, when a noise condition has been encountered, the source of the problem should be determined and eliminated. The valve should then be thoroughly inspected to insure that it is yet repairable. Most times, simple installation of a spare parts kit and a solenoid base sub assembly can restore a valve to like new condition. The restored and reinstalled solenoid valve should be tested to insure proper operation, and a voltage check should be made at the solenoid valve while the valve is energized. In addition, a current reading can be obtained and compared with catalog specifications to verify normal solenoid and coil operation.
Note: The coil may have been damaged due to excessive current draw of at damaged shading coil within the solenoid valve. A partial rebuilding of a valve damaged by a noise condition can prove useless as the noise condition would continue. The entire valve should be dismantled and inspected and cleaned. All parts supplied in a spare parts kit should be installed. Further, and additional solenoid parts damaged by a noise condition such as a solenoid base sub assembly, should be replaced. Examine valve seating, pistons and the valve body to verify that they have not been damaged. Damage to major portions of the valve may make repairing the valve uneconomical.
Should a noise condition be encountered, immediate action may prevent any damage to the solenoid valve itself.
ASCO Valve used by Algas-SDI
Installation & Maintenance Instructions
SERIES
8003G
8202G
OPEN-FRAME, GENERAL PURPOSE, WATERTIGHT/EXPLOSIONPROOF SOLENOIDS
Form No.V6584R8
Ċ SERVICE NOTICE Ċ
ASCO solenoid valves with design change letter G" or H" in the catalog number (ex. 8210G 1) have an epoxy encapsulated ASCO Red Hat II solenoid. This solenoid replaces some of the solenoids with metal enclosures and open-frame constructions. Follow these installation and maintenance instructions if your valve or operator uses this solenoid.
See separate instructions for basic valve.
INSTALLATION
Check nameplate for correct catalog number, service, and wattage. Check front of solenoid for voltage and frequency.
WARNING: Electrical hazard from the accessibility of live parts. To prevent the possibility of death,Ăserious injury or property damage, install the open - frame solenoid in an enclosure.
DESCRIPTION
Catalog numbers 8003G and 8202G are epoxy encapsulated pull-type solenoids. The green solenoid with lead wires and 1/2 Ăconduit connection is designed to meet Enclosure Type 1-General Purpose, Type 2-Dripproof,
Types 3 and 3S-Raintight, and Types 4 and 4X-Watertight. The black solenoid on catalog numbers prefixed EF" or EV" is designed to meet
Enclosure Types 3 and 3S-Raintight, Types 4 and 4X-Watertight, Types 6 and 6P-Submersible, Type 7 (A, B, C & D) Explosionproof Class I, Division
1 Groups A, B, C, & D and Type 9 (E, F, & G)-Dust-Ignitionproof Class II,
Division 1 Groups E, F & G. The Class II, Groups F & G Dust Locations designation is not applicable for solenoids or solenoid valves used for steam service or when a class H" solenoid is used. See Temperature Limitations section for solenoid identification and nameplate/retainer for service. When installed just as a solenoid and not attached to an ASCO valve, the core has a 0.250-28 UNF-2B tapped hole, 0.38 or 0.63 minimum full thread.
NOTE: Catalog number prefix EV" denotes stainless steel construction.
Catalog numbers 8202G1, 8202G3, 8202G5 and 8202G7 are epoxy encapsulated push-type, reverse-acting solenoids having the same enclosure types as previously stated for Catalog numbers 8003G1 and
8003G2.
Series 8003G and 8202G solenoids are available in:
Open-Frame Construction: The green solenoid may be supplied with
1/4 spade, screw or DIN terminals. (Refer to Figure 4)
Panel Mounted Construction: These solenoids are specifically designed to be panel mounted by the customer through a panel having a .062 to .093
maximum wall thickness. Refer to Figure 1 and section on Installation of
Panel Mounted Solenoid.
Optional Features For Type 1 - General Purpose
Construction Only
Junction Box: This junction box construction meets Enclosure Types
2,3,3S,4, and 4X. Only solenoids with 1/4 spade or screw terminals may have a junction box. The junction box provides a 1/2 conduit connection, grounding and spade or screw terminal connections within the junction box (See Figure 5).
DIN Plug Connector Kit No.K236034: Ă Use this kit only for solenoids with
DIN terminals. The DIN plug connector kit provides a two pole with grounding contact DIN Type 43650 construction (See Figure 6).
OPERATION
Series 8003G - When the solenoid is energized, the core is drawn into the solenoid base sub-assembly. IMPORTANT: When the solenoid is de-energized, the initial return force for the core, whether developed by spring, pressure, or weight, must exert a minimum force to overcome residual magnetism created by the solenoid. Minimum return force for AC construction is 11 ounces, and 5 ounces for DC construction.
Series 8202G - When the solenoid is energized, the disc holder assembly seats against the orifice. When the solenoid is de-energized , the disc holder assembly returns.
IMPORTANT: Initial return force for the disc or disc holder assembly, whether developed by spring, pressure, or weight, must exert a minimum force to overcome residual magnetism created by the solenoid. Minimum return force is 1 pound, 5 ounces.
MM All Rights Reserved.
F OR B LACK E NCLOSURE T YPES 7 AND 9 O NLY
CAUTION: To prevent fire or explosion, do not install solenoid and/or valve where ignition temperature of hazardous atmosphere is less than 165 C. On valves used for steam service or when a class
H" solenoid is used, do not install in hazardous atmosphere where ignition temperature is less than 180 C. See nameplate/retainer for service.
NOTE: These solenoids have an internal non-resetable thermal fuse to limit solenoid temperature in the event that extraordinary conditions occur which could cause excessive temperatures. These conditions include high input voltage, a jammed core, excessive ambient temperature or a shorted solenoid, etc. This unique feature is a standard feature only in solenoids with black explosionproof/dust-ignitionproof enclosures (Types 7 & 9).
CAUTION: To protect the solenoid valve or operator, install a strainer or filter, suitable for the service involved in the inlet side as close to the valve or operator as possible. Clean periodically depending on service conditions. See ASCO Series 8600, 8601, and
8602 for strainers.
Temperature Limitations
For maximum valve ambient temperatures, refer to chart. The temperature limitations listed, only indicate maximum application temperatures for field wiring rated at 90 C. Check catalog number prefix and watt rating on nameplate to determine maximum ambient temperature. See valve installation and maintenance instructions for maximum fluid temperature.
NOTE: For steam service, refer to Wiring section, Junction Box for temperature rating of supply wires.
Temperature Limitations For Series 8003G or 8202G Solenoids for use on Valves Rated at 10.1, 11.6, 17.1, or 22.6 Watts
Watt
Rating
Catalog
Number Coil Prefix
Class of
Insulation
Maximum
Ambient Temp.
10.1 & 17.1
10.1 & 17.1
None, FB, KF, KP
SC, SD, SF, & SP,
HB, HT, KB, KH,
SS, ST, SU,
F
H
125
140
F (51.7
F (60
C)
C)
11.6 & 22.6
11.6 & 22.6
None, FB,KF, KP,
SC, SD, SF, & SP.
HP, HT, KB, KH,
SS, ST, SU, & SV
F
H
104
104
F (40
F (40
C)
C)
Minimum ambient temperature -40 F (-40 C).
Positioning
This solenoid is designed to perform properly when mounted in any position.
However, for optimum life and performance, the solenoid should be mounted vertically and upright to reduce the possibility of foreign matter accumulating in the solenoid base sub-assembly area.
Wiring
Wiring must comply with local codes and the National Electrical Code. All solenoids supplied with lead wires are provided with a grounding wire which is green or green with yellow stripes and a 1/2 conduit connection. To
Printed in U.S.A.
50 Hanover Road, Florham Park, New Jersey 07932 www.ascovalve.com
Page 1 of 4
facilitate wiring, the solenoid may be rotated 360 . For the watertight and explosionproof solenoid, electrical fittings must be approved for use in the approved hazardous locations.
CAUTION: Cryogenic Applications - Solenoid lead wire insulation should not be subjected to cryogenic temperatures.
Adequate lead wire protection and routing must be provided.
Additional Wiring Instructions For Optional Features:
Open-Frame solenoid with 1/4 spade terminals.
For solenoids supplied with screw terminal connections use #12-18 AWG stranded copper wire rated at 90 C or greater. Torque terminal block screws to 10 ± 2 in-lbs [1,0 ± 1,2 Nm]. A tapped hole is provided in the solenoid for grounding, use a #10-32 machine screw. Torque grounding screw to 15 - 20 in-lbs [1,7 - 2,3 Nm]. On solenoids with screw terminals, the socket head screw holding the terminal block to the solenoid is the grounding screw.
Torque the screw to 15 - 20 in-lbs [1,7 - 2,3 Nm] with a 5/32 hex key wrench.
Junction Box
The junction box is used with spade or screw terminal solenoids only and is provided with a grounding screw and a 1/2 conduit connection. Connect
#12-18 AWG standard copper wire only to the screw terminals. Within the junction box use field wire that is rated 90 C or greater for connections. For steam service use 105 C rated wire up to 50 psi or use 125 C rated wire above
50 psi. After electrical hookup, replace cover gasket, cover, and screws.
Tighten screws evenly in a crisscross manner.
DIN Plug Connector Kit No.K236034
1. The open-frame solenoid is provided with DIN terminals to accommodate the plug connector kit.
2. Remove center screw from plug connector. Using a small screwdriver, pry terminal block from connector cover.
3. Use #12-18 AWG stranded copper wire rated at 90 C or greater for connections. Strip wire leads back approximately 1/4 f or installation in socket terminals. The use of wire-end sleeves is also recommended for these socket terminals. Maximum length of wire-end sleeves to be approximately 1/4 .ĂTinning of the ends of the lead wires is not recommended.
4. Thread wire through gland nut, gland gasket, washer and connector cover.
NOTE: Connector housing may be rotated in 90 increments from position shown for alternate positioning of cable entry.
5. Check DIN connector terminal block for electrical markings. Then make electrical hookup to terminal block according to markings on it. Snap terminal block into connector cover and install center screw.
6. Position connector gasket on solenoid and install plug connector. Torque center screw to 5 ± 1 in-lbs [0,6 ± 1,1 Nm].
NOTE: Alternating current (AC) and direct current (DC) solenoids are built differently. To convert from one to the other, it may be necessary to change the complete solenoid including the core and solenoid base sub-assembly, not just the solenoid. Consult ASCO.
Installation of Solenoid
Solenoids may be assembled as a complete unit. Tightening is accomplished by means of a hex flange at the base of the solenoid.
Installation of Panel Mounted Solenoid (See Figure 1)
1. Disassemble solenoid following instruction under Solenoid Replacement then proceed .
2. Install solenoid base sub-assembly through customer panel.
3. Position spring washer on opposite side of panel over solenoid base sub-assembly.
4. Replace solenoid, nameplate/retainer and red cap.
5. Make electrical hookup, see Wiring section.
Solenoid Temperature
Standard solenoids are designed for continuous duty service. When the solenoid is energized for a long period, the solenoid becomes hot and can be touched by hand only for an instant. This is a safe operating temperature.
MAINTENANCE
WARNING: To prevent the possibility of death, serious injury or property damage, turn off electrical power, depressurize solenoid operator and/or valve, and vent fluid to a safe area before servicing.
Page 2 of 4
Cleaning
All solenoid operators and valves should be cleaned periodically. The time between cleaning will vary depending on medium and service conditions. In general, if the voltage to the solenoid is correct, sluggish valve operation, excessive noise or leakage will indicate that cleaning is required. Clean strainer or filter when cleaning the valve.
Preventive Maintenance
Keep the medium flowing through the solenoid operator or valve as free from dirt and foreign material as possible.
While in service, the solenoid operator or valve should be operated at least once a month to insure proper opening and closing.
Depending on the medium and service conditions, periodic inspection of internal valve parts for damage or excessive wear is recommended.
Thoroughly clean all parts. Replace any worn or damaged parts.
Causes of Improper Operation
Faulty Control Circuit: Check the electrical system by energizing the solenoid. A metallic click signifies that the solenoid is operating. Absence of the click indicates loss of power supply. Check for loose or blown fuses, open-circuited or grounded solenoid, broken lead wires or splice connections.
Burned-Out Solenoid: Check for open-circuited solenoid. Replace if necessary. Check supply voltage; it must be the same as specified on nameplate/retainer and marked on the solenoid. Check ambient temperature and check that the core is not jammed.
Low Voltage: Check voltage across the solenoid leads. Voltage must be at least 85% of rated voltage.
Solenoid Replacement
1. Disconnect conduit, coil leads, and grounding wire.
NOTE: Any optional parts attached to the old solenoid must be reinstalled on the new solenoid. For 3-way construction, piping or tubing must be removed from pipe adapter.
2. Disassemble solenoids with optional features as follows:
Spade or Screw Terminals
Remove terminal connections, grounding screw, grounding wire, and terminal block (screw terminal type only).
NOTE: For screw terminals, the socket head screw holding the terminal block serves as a grounding screw.
Junction Box
Remove conduit and socket head screw (use 5/32 hex key wrench) from center of junction box. Disconnect junction box from solenoid.
DIN Plug Connector
Remove center screw from DIN plug connector. Disconnect DIN plug connector from adapter. Remove socket head screw (use 5/32 hex key wrench), DIN terminal adapter, and gasket from solenoid.
3. Snap off red cap from top of solenoid base sub-assembly. For 3-way construction with pipe adapter (Figure 3), remove pipe adapter, nameplate and solenoid. Omit steps 4 and 5.
4. Push down on solenoid. Then using a suitable screwdriver, insert blade between solenoid and nameplate/retainer. Pry up slightly and push to remove.
NOTE: Series 8202G solenoids have a spacer between the nameplate/ retainer and solenoid.
5. Remove solenoid from solenoid base sub-assembly.
6. Reassemble in reverse order of disassembly. Use exploded views for identification and placement of parts.
7. Torque pipe adapter to 90 inch-pounds maximum [10,2 Nm maximum].
Then make up piping or tubing to pipe adapter on solenoid.
Disassembly and Reassembly of Solenoids
1. Remove solenoid, see Solenoid Replacement .
2. Remove spring washer from solenoid base sub-assembly. For 3-way construction, remove plugnut gasket.
3. Unscrew solenoid base sub-assembly from valve body.
4. Remove internal solenoid parts for cleaning or replacement. Use exploded views for identification and placement of parts.
5. If the solenoid is part of a valve, refer to basic valve installation and maintenance instructions for further disassembly.
6. Torque solenoid base sub-assembly and adapter to 175±25 in-lbs
[19,8±2,8 Nm].
ORDERING INFORMATION FOR ASCO SOLENOIDS
When Ordering Solenoids for ASCO Solenoid Operators or Valves, order the number stamped on the solenoid. Also specify voltage and frequency.
Form No.V6584R8
50 Hanover Road, Florham Park, New Jersey 07932 www.ascovalve.com
Part Name solenoid base sub-assembly & adapter pipe adapter
Remove red cap and
Then pry here to lift nameplate/retainer and push to remove.
Torque Chart
Torque Value Inch-Pounds
175 ± 25
90 maximum solenoid with 1/2 NPT
.062 to .093 maximum thickness of panel for mounting red cap nameplate/ retainer grounding wire green or green with yellow stripes finger washer
0.69 diameter mounting hole
Torque Value Newton-Meters
19,8 ± 2,8
10,2 maximum
Remove red cap and
Then pry here to lift nameplate/retainer and push to remove.
core
(AC) core
(DC)
Tapped hole in core
0.250-28 UNF-2B
0.63 minimum full thread (AC)
0.38 minimum full thread (DC) red cap nameplate/ retainer spacer solenoid base sub-assembly
0.9375-26 UNS -2A
Panel Mount thread
Figure 1. Series 8003G solenoids
Remove red cap and
Then pry here to lift nameplate/retainer and push to remove.
solenoid with 1/2 NPT grounding wire green or green with yellow stripes spring washer
Side View collar to face valve body
Alternate
Construction finger washer pipe adapter plugnut gasket
Without
Adapter
Form No.V6584R8
bonnet washer core(small end up) solenoid base gasket plugnut assembly retainer gasket retainer stem disc disc spring adapter gasket disc holder assembly disc holder spring
Figure 2. Series 8202G solenoids adapter
With
Adapter
Air Only Construction
Vent to Atmosphere
Figure 3. 3-Way Construction
Page 3 of 4
50 Hanover Road, Florham Park, New Jersey 07932 www.ascovalve.com
Part Name terminal block screws socket head screw center screw
Open-Frame Solenoid with 1/4 Spade Terminals
See torque chart above tapped hole for
#10-32 grounding screw
(not included)
Junction Box Solenoid with 1/4 Spade Terminals or Screw Terminals
Torque Chart
Torque Value in Inch-Pounds
10 ± 2
15 - 20
5 ± 1
Open-Frame Solenoid with Screw Terminals.
Socket head screw is used for grounding.
Torque Value in Newton-Meters
1,1 ± 0,2
1,7 - 2,3
0,6 ± 0,1
Open-Frame Solenoid with DIN Terminals Indicates parts supplied in Termination Module
Kit No. K256104 screw terminal adapter gasket
DIN terminal adapter block screw socket head grounding screw
(5/32 hex key wrench)
Figure 4. Open-frame solenoids socket head screw
(5/32 hex key wrench) cover screw cover cover gasket
See torque chart above grounding screw and cup washer
Note: junction box gasket
Junction box with screw terminals shown. With screw terminal block removed, remaining parts comprise the junction box for spade terminal construction.
junction box with
1/2 conduit connection and grounding terminal
Figure 5. Junction box (optional feature) socket head screw
(5/32 hex key wrench)
Open-Frame Solenoid with DIN Terminal
Plug Conector
Indicates that these parts are included in DIN plug connector Kit No. K236034
See torque chart above gasket
DIN terminal adapter connector gasket gland nut gland gasket
Notes:
1. Connector cover may be rotated in 90 increments from position shown for alternate position of cable entry.
2. Refer to markings on DIN connector for proper electrical connections.
socket head screw
(5/32 hex key wrench)
DIN connector terminal block
(see note 2) connector cover
(see note 1) washer center screw
Page 4 of 4
Figure 6. DIN plug connector kit No. K236034 (optional feature)
Form No.V6584R8
50 Hanover Road, Florham Park, New Jersey 07932 www.ascovalve.com
Florham Park, New Jersey 07932
Tel. (973) 966-2000
Fax (973) 966 2628
Aiken, South Carolina 29801
Tel. (803) 641-9200
Fax (803) 641-9290
SCIENTIFIC
50 Hanover Road
Florham Park, New Jersey 07932
Tel. (973) 236-6160
Fax (973) 966 6461
MMIl All Rights Reserved.
Printed in U.S.A. Form No. V6950R5
50 Hanover Road, Florham Park, New Jersey 07932 www.ascovalve.com
Page 1 of 2
ASCOMATICA S.A. de C.V.
Bosques de Duraznos No. 65-1003A
Fraccionamiento Bosques de las Lomas
Delegacion Miguel Hildago
Mexico, D.F. CP11700
Tel: (52)-55-5596-7741
Fax: (52)-55-5596-7719
ASCO Valve Canada
P.O. Box 160 (Airport Road)
Fax: (519)758-5540
ASCOTECH S.A. de C.V.
Circuito Del Progreso No.27
Mexicali, B.C. Mexico
Tel: (011)-52-686-559-8500
Fax: (011)-52-686-559-8548
MMIl All Rights Reserved.
50 Hanover Road, Florham Park, New Jersey 07932 www.ascovalve.com
Printed in U.S.A.
Form No. 6950R5
Page 2 of 2
Innovative Liquid Vaporizing and Gas Mixing Solutions
WARRANTY REGISTRATION
Type of Equipment:
ASDI Sales Order #:
Purchased By:
Serial Number:
Order Date:
To help us give you better service, please fill out this warranty registration form and return it to
ASDI to register your purchase and for follow up on the performance of ASDI equipment.
We are dedicated to producing a quality product and if a problem occurs,
ASDI wants to know about it.
Please help us with a small amount of information about your company and how the equipment will be used. When contacting ASDI, please have the type of equipment and the serial number handy so we can give you accurate information. If you have had any kind of problem with this equipment, or you have any comments, please attach a separate sheet to this form. Keep a copy for your records.
End Customer/Company Name:
Address:
City:
State:
Tel:
Fax:
Zip:
Name of individual to contact for follow up information:
Title:
Usage - Circle one:
Other:
Base Load Standby System Peak Shaving
In what application is the equipment being used?
When was the equipment put in service?
Note: If you have more than one piece of ASDI equipment, fill out one warranty sheet and staple the others to it, ASDI will do the rest.
151 South Michigan Street,
Seattle, Washington, 98108, USA
Tel: 206.789..5410
Fax: 206.789.5414
E-mail: [email protected]
Internet: www.algas-sdi.com
Algas-SDI International, LLC
151 South Michigan Street
Seattle, Washington 98108
USA
Ph.: 1.206.789.5410
Fax.: 1.206.789.5414 www.algas-sdi.com