advertisement
Gasmaster
M07624
Issue 6
July 2008
Installation,
Operation and
Maintenance
Manual
The equipment described in this manual may have mains voltages applied to it.
Ensure correct safety procedures are adopted before working on the equipment.
The equipment described in this manual is designed for the detection of flammable and/or toxic gases. Detectors may be sited in hazardous areas. Ensure local safety procedures are adopted before carrying out any maintenance or calibration work.
The equipment described in this manual may be connected to remote alarms and/ or shutdown systems. Ensure that local operating procedures are adopted before carrying out any maintenance or calibration work.
This product has been tested and found to comply with the European Directive 89/336/EEC and the EMC requirements of EN50270. It also complies with the
Council Directive 73/23/EEC relating to electrical safety and the Low Voltage Directive. It conforms to the CE
Marking Directive 93/68/EEC.
MODEL
GASMASTER
Passed inspection by
Date
Tested for electrical safety by
Date
R
C22.2 No.152
Caution : Read & understand manual before operating. Mount outside hazardous area.
See manual for relay contact ratings.
2 Blacklands Way, Abingdon Business Park,
Abingdon, Oxon, OX14 1DY, England
Telephone: 01235 557700 Fax 01235 557749 www.crowcon.com
The Canadian Standards Authority (CSA) have only assessed the combustible gas portion of this instrument for performance.
Crowcon Detection Instruments Ltd
2 Blacklands Way, Abingdon
OX14 1DY UK
Tel. +44 (0)1235 557700
Fax. +44 (0)1235 557749 www.crowcon.com
Email: [email protected]
© Copyright Crowcon Detection Instruments Ltd 2008
All rights are reserved. No part of the document may be photocopied, reproduced, or translated to another language without the prior written consent of Crowcon
Detection Instruments Ltd.
Publication number: M07624
Sixth edition: July 2008
GasMaster Contents
Contents
I. Introduction . . . . . . . . . . . . . . . . . . . . . 1
1.1 About Gasmaster . . . . . . . . . . . . . 1
1.2 About this manual. . . . . . . . . . . . . 1
1.3 Instructions for use in marine applications . . . . . . . . . . . . . . . . . . 2
II. Installation . . . . . . . . . . . . . . . . . . . . . . 3
Please read this first. . . . . . . . . . . . . . . . 3
2.1 Before installation . . . . . . . . . . . . . 4
2.2 General . . . . . . . . . . . . . . . . . . . . . 4
2.3 Mounting . . . . . . . . . . . . . . . . . . . 5
2.4 Cabling requirements . . . . . . . . . . 5
2.5 Installing gas and fire detectors . . . 6
2.6 Installing output devices . . . . . . . . 6
2.7 Connecting mains power . . . . . . . 6
2.8 Connecting input devices . . . . . . . 7
2.9 Connecting output devices . . . . . 11
2.10 Applying power. . . . . . . . . . . . . . 13
2.11 Battery back-up times . . . . . . . . . 13
2.12 Commissioning . . . . . . . . . . . . . . 14
III. Operation . . . . . . . . . . . . . . . . . . . . . . 16
3.1 Gasmaster Operator Panel. . . . . . 16
3.2 Gasmaster start up sequence . . . 18
3.3 How to adjust display contrast . . 18
3.4 How to display Instrument serial number and system identity . . . . 18
3.5 Using the menu system . . . . . . . . 19
3.6 Inhibiting channels . . . . . . . . . . . 19
3.7 Using the Control Panel in
Supervisor Mode . . . . . . . . . . . . . 20
3.8 In the event of an alarm . . . . . . . 21
3.9 In the event of a fault . . . . . . . . . 21
3.10 System Configuration . . . . . . . . . 21
Menu system overview . . . . . . . . . . . . . . . 23
Faults menu
. . . . . . . . . . . . . . . . . . . . . . . . 23
Warnings menu
. . . . . . . . . . . . . . . . . . . . . 25
View menu
. . . . . . . . . . . . . . . . . . . . . . . . . . 26
Actions menu
. . . . . . . . . . . . . . . . . . . . . .27
Supervisor menu . . . . . . . . . . . . . . . . .
28
IV. Maintenance . . . . . . . . . . . . . . . . . . . . 34
4.1 Functional Testing . . . . . . . . . . . . 34
4.2 System Inhibit . . . . . . . . . . . . . . . 34
4.3 Detector Calibration . . . . . . . . . . 35
4.4 Changing Batteries . . . . . . . . . . . 35
4.5 Module Replacement . . . . . . . . . 35
4.6 Event logging . . . . . . . . . . . . . . . 35
4.7 Service card. . . . . . . . . . . . . . . . . 35
4.8 Cleaning . . . . . . . . . . . . . . . . . . . 35
Appendix A: Specifications . . . . . . . . . . . . 36
Appendix B: Spare Parts and Accessories . 37
Appendix C: Display characters . . . . . . . . . 38
Warranty Statement . . . . . . . . . . . . . . . . . 39
Regional addresses . . . . . . . . . . . . . . . . . . 40
GasMaster Introducton
I. Introduction
1.1 About Gasmaster
Gasmaster is a gas and fire control panel, designed to monitor remote gas and fire detectors. Gasmaster can also monitor flame detectors as well as Crowcon's ESU product. The status of each input is displayed on a large, clear LCD display, and alarms or faults are indicated by clear
LEDs and an integral sounder.
Relay outputs are provided for alarms and faults, as well as dedicated outputs for audible visual alarms. An RS-485 Modbus output is provided for two-wire transfer of all data to industry-standard control systems.
Gasmaster logs all alarm and fault events so that they can be investigated at a later stage using
Gasmaster PC software.
There are two versions of Gasmaster:
Gasmaster 1 - single channel unit for one gas detector, fire zone or ESU sampling device.
.
Gasmaster 4 - four channel unit for one to four gas detectors, fire zones or ESU sampling devices.
Gasmaster 1 is identifiable from Gasmaster 4 by having only a single channel display (see figure
3.2, page 16) and a de-populated terminal PCB. All operating functions are identical to Gasmater 4.
Gasmaster is designed for simple operation, and all day-to-day functions can be performed from the front panel. Please refer to section 3 for details on display operation.
1.2 About this manual
The manual is divided into sections which detail procedures for installing, operating and maintaining Gasmaster. Gasmaster is a safety system and it is essential that all instructions are correctly followed.
Details of the types of device that can be connected to Gasmaster are shown in section 2, along with typical connection diagrams. Section
3 provides instructions for day-to-day operation of Gasmaster as well as detailed information on system configuration.
Warning
Regular maintenance of any safety system is essential, and failure to maintain the system according to these instructions could result in failures which could lead to harm to plant and/or personnel or even death. Details of the requirements for Gasmaster systems are provided in section 4.
There are separate appendices for systems specification and spare parts identification.
Introducton GasMaster
1.3 Instructions for use in marine applications
This section applies only to the following products:
C011058 Gasmaster 1 single channel unit.
Marine approved.
C011060 Gasmaster 1 with Communications
Port. Marine approved.
C011057 Gasmaster 4 one to four channel unit. Marine approved.
C011059 Gasmaster 4 with Communications
Port. Marine approved
Additional Cabling Requirement for Marine
Applications
In order to meet Marine EMC requirements the following installation instructions should be followed for all cables entering/leaving the enclosure. After installing the gland and cable into the enclosure each core of the cable should loop round a ferrite ring as shown in the diagram below.
3 ferrite beads will be initially supplied for single channel units.
6 ferrite beads will be initially supplied for
4-channel units.
If additional cables require installation, please contact Crowcon sales in order to purchase more ferrite beads, quoting E01773 as the part number reference.
Usage of these ferrites is a requirement for Marine certification.
&ERRITE
#ROWCON0ART.UMBER
%
SUPPLIED
7IRES
#ABLE'LAND
FERRITEBEADSWILLBEINITIALLYSUPPLIEDFORSINGLECHANNELUNITS
FERRITEBEADSWILLBEINITIALLYSUPPLIEDFOR CHANNELUNITS
!TMINIMUMTHEFOLLOWINGCABLESREQUIRET HISAPPLICATION-AINS0OWER
#HANNEL)NPUTAND!UDIBLE6ISUAL!LARM
GasMaster Installaton
II. Installation
Please read this first
Before commencing the installation and commisioning of your Gasmaster system, please read through the following information which will guide you through the whole process.
The installation instructions contained in this section are for a pre-configured
Gasmaster
.
For instructions on installing and commissioning gas and fire detectors, please follow the user manual instructions supplied with the detectors.
Alternatively contact Crowcon for advice.
To complete the installation of your Gasmaster system you will need to use the Operator panel and Menu. Full instructions can be found in section
III
. Operation, you are advised to familiarise yourself with the operator buttons on the front panel and the menu structure, see page 21. Some configuration steps may require you to enter
Supervisor mode. Crowcon advises that personnel familiar with installing and commisioning gas and fire detection systems carry out this part.
If you have purchased a Gasmaster 1
Please follow the instructions in this section but ignore the reference to additional channels.
If you have purchased a non-configured
Gasmaster 4
Please follow the installation instructions for a pre-configured Gasmaster 4. Additional information on setting-up your Gasmaster system can be found in section III
.
Operation.
Step-by-step instructions
The installation and commissioning of your
Gasmaster system is presented in easy to follow instructions. A summary table of contents detailing a typical sequence of installation steps is shown below. Depending on your configuration some or part of each step may be omitted.
Warning:
Gasmaster is not certified for use in hazardous areas, but may be connected to detectors and/or alarm devices which are installed in a hazardous area. Instructions for field devices must be closely observed when installing a Gasmaster system.
2.1 Before installation
2.2 General
2.3 Mounting
2.4 Cabling requirements
2.5 Installing gas and fire detectors
2.6 Installing output devices
2.7 Connecting mains power
2.8 Connecting input devices
2.8.1 Two wire devices
2.8.2 Three wire devices
2.8.3 Heat/smoke detectors
2.8.4 Environmental Sampling Unit
(ESU)
2.8.5 Flame detectors
2.8.6 Remote inhibit and accept/ reset inputs
2.9 Connecting output devices
2.9.1 Audible visual alarms
2.9.2 Common relay connections
2.9.3 Channel relay connections
2.9.4 Analogue outputs
2.9.5 RS485 communications
2.10 Applying power
2.11 Battery back-up time/
power calculations
2.12 Commissioning
2.12.1 Zero adjustment and calibration
2.12.2 Testing fire channels
2.12.3 Testing ESU channels
Installaton GasMaster
2.1 Before installation
Before carrying out any installation work, ensure that local regulations and site procedures are followed. Further advice is available from Crowcon if required.
Gasmaster is intended for use in non hazardous areas. Gas and fire detectors may be mounted in potentially flammable atmospheres using appropriate barrier devices where necessary. Check the equipment to be installed is suitable for the area classification. Please refer to instrument installation manuals for information on location.
Crowcon recommends the installation of
Gasmaster be carried out by people with experience of installing electrical equipment in potentially hazardous areas.
2.2 General
This section describes how to get started with a
Gasmaster
or
Gasmaster
system that has been pre-configured for the detectors supplied. Figures
2.1, 2.2 and 2.5 show the internal structure of
Gasmaster.
See the
Specfcaton and Inspecton Certfcate
provided with your system for full details of its configuration.
Figure 2.1 shows the internal arrangement of a
Gasmaster system. The front cover
is removed by unscrewing the four screws
and carefully disconnecting the two-pole sounder connector from the display PCB
. The front cover should then be placed in a safe location. With the front cover removed the chassis plate
is accessible which supports the display PCB
and batteries
. Below the chassis plate is the terminal PCB
which contains all the input and output terminals and power terminals. The display PCB
is connected to the terminal PCB
via a 50-way ribbon connector, and is hinged on the left side so that it can be moved to provide access to the detector input terminals. Most terminals are accessible once the display PCB is moved and the batteries
are removed, however if necessary the chassis plate can be removed for easier terminal access by carefully disconnecting the display PCB ribbon connector from the terminal PCB and unscrewing the four fixings
. Care should be taken when
Display
PCB
Display
PCB ribbon
Front cover
Batteries
Chassis plate
Gland knock outs
Optional comms port
Terminal PCB
Figure 2.1 Exploded view of Gasmaster re-fitting the display PCB so as not to damage the connector or ribbon cable.
Six punched cable gland knock-outs are provided on the top and bottom of the enclosure. The knock-outs are suitable for M20, fi"NPT or PG13.5 cable glands. To remove Knock-outs, tap around the edge of the recessed flange using a small hammer and a screwdriver. The knocks outs should then come away from the enclosure. Knock-outs should be removed prior to mounting Gasmaster and great care must be taken to avoid damaging internal components.
Power supply
Gasmaster comes fitted with an auto-ranging power supply suitable for 100-240 V ac 50-60 Hz operation. This provides a nominal 24 V dc supply with a maximum power of 60 W. Alternatively
Gasmaster can be powered from an external 24 V dc supply, a maximum 60 W supply is required.
Gasmaster must never be connected to ac and dc supplies at the same time.
GasMaster Installaton
The Gasmaster power supply contains no user replaceable fuses.
Short crcut protecton
Each detector input is short-circuit protected.
Self-resetting ‘polyfuses’ are fitted to the 24 V power supply which will cut power in the event of a cabling fault, and automatically reset when the fault is corrected. Detectors with a maximum consumption of 500 mA may be connected.
Crcut breaker
If the equipment is permanently connected to a mains supply then a dedicated circuit breaker must be included in the installation, to comply with EN 61010-1. The circuit breaker must be close to Gasmaster, in easy reach of the operator.
It must be marked as the disconnecting device for the Gasmaster system, and the ON and OFF positions must be clearly marked.
The circuit breaker must comply with the relevant requirements of IEC60947-1 and IEC60947-3.
The protective earth must not be disconnected even when the breaker is activated.
sounder connector from the display PCB. The cover should be placed in a secure location. It is recommended that Gasmaster is positioned by hand in the desired location, and a pencil used to mark the mounting hole positions.
Gasmaster should be removed before drilling the mounting holes.
278
120
110
77
5
Batteries
Battery connection diagram
Figure 2.2 Gasmaster chassis plate with display
PCB board and batteries.
2.3 Mounting
All Gasmaster systems should be installed in a safe area. Consider location, cabling and earthing requirements.
Figure 2.3 provides a dimensional view of
Gasmaster. To access the mounting points, first remove the front cover by unscrewing the fixings labelled
in figure 2.1. Carefully remove the
Mounting holes
Figure 2.3 Dimensional view of Gasmaster with mounting holes shown
2.4 Cabling requirements
Cabling to Gasmaster and detectors must be in accordance with the recognised standards of the appropriate authority in the country concerned, and must meet the electrical requirements of the detector.
Explosion-proof (Exd) devices
Crowcon recommends the use of steel wire armoured (SWA) cable. Suitable explosionproof glands must be used.
Intrinsically Safe (I.S.) devices
Crowcon recommends the use of twisted pair cable with overall screen and sheath. Suitable weatherproof glands must be used. I.S. devices must be used with a suitable Zener Barrier or Galvanic Isolator when used in a hazardous area.
Fire detectors,
Crowcon recommends the use of twisted-pair cable, screened with an overall protective sheath that is fireproof, for example, Pirelli
FP200 or similar. A 1K8 end-of-line resistor must be fitted to the last detector on each conventional smoke or heat detector loop.
Installaton GasMaster
Alternative cabling techniques, such as steel conduit, may be acceptable provided that appropriate standards are met.
The minimum acceptable supply voltage measured at the detector and the maximum current drawn by that detector is different for each device. Please refer to the relevant Installation,
Operating and Maintenance Instructions provided with each detector to calculate the maximum cable distances allowed for different cable types.
The maximum cable distance allowed is dependent upon the installation, for example, whether
Zener Barriers or Galvanic Isolators are required
(for I.S. devices) or not.
When calculating maximum cable distances for detectors, assume a minimum supply of 19 V and a sense resistance of 98
Ω (
39
Ω
for convential fire channels).
Table 1: Typical cable characteristics c.s.a
(mm2)*
Resistance (
Ω
per km)
Cable Loop
0.5 (20)
1.0 (17)
39.0
18.1
78.0
36.2
1.5 (15)
2.5 (13)
12.1
8.0
24.2
16.0
*Approximate c.s.a. in awg given in brackets.
Cable lengths should be calculated according to the equations defined in the detector instructions sheet and the cable and Gasmaster characteristics specified above.
There are a number of suitable ways of terminating cables and glands to Gasmaster dependant on the cable and gland type:
– Steel wire-armoured (SWA) cable and glands with electrical termination of the armour to the enclosure via the gland.
– Screened cable with the screen terminated inside the enclosure via a metal tag attached to the gland.
– Screened cable using an EMC gland where the screen is terminated to the enclosure via the gland.
– For detectors, 4-20 mA outputs and RS-
485 terminations: screened cable where the screen is connected to the SCR terminal on the appropriate terminal strip.
2.5 Installing gas and fire detectors
Install gas and fire detectors as per instrument installation manuals, paying attention to location and cabling requirements. For ESU devices please refer to installation manual provided.
2.6 Installing output devices
Gasmaster can drive 24 V dc audible visual alarms directly via the Audible Visual drive terminals on the terminal PCB. Relays are provided for switching additional outputs, and 24 V dc 200 mA auxiliary supplies are available adjacent to each block of relay terminals for switching low power devices. Section 2.9 provides detailed information on connections to output devices.
2.7 Connecting mains power
Connect the external power supply using the two part screw terminals, refer to figures 2.4 and 2.5.
Gasmaster must be earthed either at the power connector earth terminal (see Figure 2.4) or using the stud on top of the enclosure.
Live Neutral Earth
E N L
L N E
FIRE
SINK
SRCE
CH1
CH2
FIRE
SINK
SRCE
Figure 2.4 Mains connection terminals on terminal PCB
GasMaster
MAINS
INPUT
CHANNEL
INPUT
TERMINALS
COMMON
RELAY TERMINALS
Installaton
DISPLAY
PCB
CONNECTOR
CHANNEL
RELAY
TERMINALS
LINK TO
CHASSIS
ON NON
I.S.SYSTEM
ONLY
LINK TO
CHASSIS
ON I.S.
SYSTEM
ONLY
EXTERNAL
24 V DC
INPUT
ANALOGUE
OUTPUT
TERMINALS
Figure 2.5 Terminal PCB layout
RS-485 MODBUS
COMMUNICATIONS
TERMINALS
AUDIBLE VISUAL
ALARM TERMINALS
REMOTE INHIBIT AND
ACCEPT/RESET INPUTS
2.8 Connecting input devices
Gasmaster provides connectivity to a range of gas and fire detectors using two part connectors with screw terminals. Each channel input can accept 4-
20 mA or conventional fire loop.
Note: Gasmaster
has one channel only. Ths channel can be used to detect one gas detector, fre zone or ESU.
Details of hardware configurations and link settings can be found in section 2.8.1 to 2.8.6.
4-20 mA Inputs
Gasmaster provides analogue 4-20 mA inputs with a sensor supply voltage of 19 to 28 V dc and measures the signal across a 98
Ω
sense resistor.
Inputs can be gas detectors or flame detectors in 4-20 mA 2-wire sink, or 3-wire sink or source configurations. Gasmaster will track inputs from 3 to 21.5 mA at which point an 'over-range' fault will be indicated. Connection details are shown in section 2.8.1 and 2.8.2.
Conventonal fre detectors
A loop of up to 20 conventional smoke/heat detectors (for example Apollo series 60 devices) can be connected to each Gasmaster input channel. A fire loop can also comprise switched devices such as manual alarm call points or flame detectors, and devices can be mixed on the
Installaton GasMaster
same loop provided electrical characteristics are compatible and fire regulations allow. Switched devices require a 470
Ω
series resistor. Each fire loop must be terminated with a 1K8 end-of-line resistor, which is monitored to provide indication of open circuit or short circuit faults. Connection details are shown in section 2.8.3.
Environmental Sampling Unit (ESU)
Each Gasmaster input can monitor a Crowcon
Environmental Sampling Unit (ESU), which enables detection of flammable or toxic gases over a wide area using a sample draw technique. It is essential that the sampling device on the ESU is operating correctly, and Gasmaster provides this monitoring function to ensure a sample is being drawn. Gasmaster provides a 2-wire 24
V dc supply to the sampling device. Separate
Gasmaster input channels are required to monitor the gas detector or detectors fitted to the ESU.
Connection details are shown in section 2.8.4.
mV bridge pellistor detectors
Some flammable gas detectors manufactured by Crowcon provide a mV bridge signal rather than a 4-20 mA signal. Typical examples are high operating temperature detectors and detectors which will be mounted in inaccessible areas.
An Accessory Box is available to enable these type of detectors to be connected to Gasmaster.
The Accessory Box contains 1 to 4 PCB's which convert the mV bridge signal from each detector to a 4-20 mA signal that can be monitored by Gasmaster. mV bridge detector cables will be terminated at the Accessory Box, which has a connector that simply plugs-in to Gasmaster.
Accessory Box details are shown in Appendix B.
Please contact Crowcon for specific wiring details for Crowcon detectors
2.8.1 Two wire devices
Figure 2.6 shows a typical wiring configuration for a 2 wire current sink detector. Set the detector type link for the appropriate channel to
SINK
and the protection link to short 1&2, refer to figure 2.5.
Detector Type Link
FIRE
SINK
SRCE
Protection Link
3 2 1
Detector
–
+
SCR
0V
SIG
PWR
Figure 2.6 Connections for 2 wire detector
Figures 2.7 and 2.8 show typical wiring configurations for a 2 wire sink I.S.detector with Zener barrier or Galvanic Isolator. Set the link for the appropriate channel as shown in each diagram.
2.8.2 Three wire devices
Figure 2.9 shows a typical wiring configuration for a 3 wire detector. Set the link for the appropriate channel to
SINK
for a current sink detector, or
SRCE
for a current source detector, the protection link should short 1&2, refer to figure 2.5.
–
SIG
+
FIRE
SINK
SRCE
Detector Type Link
OR
FIRE
SINK
SRCE
Protection Link
3 2 1
SCR
0V
SIG
PWR
Figure 2.9 Connections for 3 wire detector
2.8.3 Heat/smoke detectors
Conventional fire detectors for safe area use should be setup according to figure 2.10 and
2.11. Conventional fire detectors for hazardous area use should be setup according to figure
2.12.
Figure 2.11 shows connections for manual alarm call points.
GasMaster
HAZARDOUS AREA
Gas Detector
+
-
4-20mA Current Sink
Installaton
SAFE AREA
Z722
I.S. Earth
P&F Z722 Zener Barrier
Crowcon Part Number: C03335
Detector Type Link
FIRE
SINK
SRCE
Protection Link
3 2 1
SCR
0V
SIG
PWR
Figure 2.7 Typical connections for 2 wire I.S. detector with Zener barrier. Set channel link to SINK (see figure 2.5) and configuration to DET4-20 SINK (see Menu System Overview section, page 21 and 29.
HAZARDOUS AREA SAFE AREA
Detector Type Link
FIRE
SINK
SRCE
Protection Link
3 2 1
Detector
–
+
1
2
11
12
MTL
5041
13
14
–
+
20-35 V dc supply
SCR
0V
SIG
PWR
Detector
–
+
3
1
7
8
12
11
Pepperl & Fuchs
KFD2-CR-Ex1.30200
–
+
20-35 V dc supply
SCR
0V
SIG
PWR
Figure 2.8 Typical connections for 2 wire I.S. detector with Galvanic Isolator. Set channel link to SRCE (see figure 2.5) and configuration to DET4-20 SRCE (see Menu System Overview section, page 21 and 29.
Installaton GasMaster
L2
Fire detector
L2
Detector Type Link Protection Link
3 2 1
SCR
0V
SIG
PWR
2.8.5 Flame detectors
Figure 2.14 shows a typical wiring configuration for a 4-20 mA 3 wire Flame detector. Set the detector type link appropriate for the type of flame detector, refer to figure 2.5.
Do not set link to FIRE.
Figure 2.10 Connections for smoke/heat detector
1K8
Manual alarm call points
470R 470R
Detector Type Link Protection Link
3 2 1
SCR
0V
SIG
PWR
4-20 mA
Flame detector
FIRE
SINK
SRCE
Detector Type Link
OR
FIRE
SINK
SRCE
Protection Link
3 2 1
–
SIG
+
SCR
0V
SIG
PWR
Figure 2.14 Connections for 4-20 mA 3 wire
Flame detector
Figure 2.11 Connections for manual alarm call points
2.8.4 Environmental Sampling Unit
(ESU)
Figure 2.13 shows the wiring configuration for monitoring the ESU sampling device. Gas detectors fitted to the ESU should be cabled separately to the appropriate input channels on the
Gasmaster or other control panel. For connections, details are shown on the instructions provided with the ESU.
2.8.6 Remote inhibit and accept/reset inputs
Gasmaster has inputs for the connection of remote switches to inhibit alarm outputs or accept and reset alarms. Inputs are activated when pulled down to 0 V, the open circuit voltage is 5 V dc.
Warning
Crowcon strongly recommends that remote inhibit switches be key operated only, and that access to the key should be restricted to authorised personnel. A Gasmaster system that has been inhibited without other safety precautions being in place may not provide the protection for which it was designed. Steps should be taken to ensure that all appropriate personnel are aware when a Gasmaster system is inhibited.
Detector Type Link
FIRE
SINK
SRCE
Protection Link
3 2 1
ESU sampling device terminal box
–
S
+
SCR
0V
SIG
PWR
Figure 2.13 Connections for ESU sampling device
HAZARDOUS AREA
1K8
L1
L2
L1
L2
Smoke or Heat Detectors
SAFE AREA
Detector Type Link Protection Link
3 2 1
Figure 2.12 Connections for conventional fire detectors for hazardous area
Z722
SCR
0V
SIG
PWR
I.S. Earth
P&F Z722 Zener Barrier
Crowcon Part Number: C03335
0
GasMaster Installaton
Remote ACCEPT/RESET
Close the contact momentarily to accept alarms and cancel audible alarms. Close the contact again when the hazard is cleared to reset alarms.
Remote INHIBIT
Closing the contact will inhibit alarms on all input channels. Channels will remain inhibited until the contact is opened; the Gasmaster will then return to its original state (any channels that have been set to inhibit using the Supervisor menu will remain inhibited). Figure 2.15 shows wiring configurations for remote inputs.
Crowcon recommends screened cables for connecting remote switches. The screen should be terminated at the appropriate ‘SCR’ terminal.
Remote Accept/Reset Global Inhibit
0V
INH
A/R
0V
0V
INH
A/R
0V
Figure 2.15 Connections for remote inhibit/ accept/reset inputs
2.9 Connecting output devices
WARNING:
After accounting for internal power consumption, the maximum power available for input and output devices is 48 W
2.9.1 Audible visual alarms
Figure 2.16 shows a typical wiring configuration for 24 V dc audible visual alarms. The Audible
Visual drive output from Gasmaster is capable of providing up to 650 mA, which equates to two general purpose audible visual alarm devices.
Two separate sounder outputs are provided to activate on level 1 and level 2 alarms respectively
(terminal AV2 becomes active on alarm level 1,
AV3 becomes active on alarm level 2). Figure 2.16 shows connections to an audible visual alarm device that can produce different tones for level
1 and 2 alarms. If a single tone device is used, connections to the sounder should be made to terminals AV2 and 0 V only. Terminal AV1 is intended to drive a visual alarm and activates on a level 1 alarm.
2.9.2 Common relay connections
Double-Pole-Change-Over (DPCO) relays with contact rating of 250 V ac 8 A (non-inductive),
5 A (inductive) are provided for Alarm 1, Alarm 2 and Fault. Each relay can be set in its non-active state as energised (
Fal safe
) or de-energised. It is common practice to set the Fault relay as
Fal Safe
so in the event of power loss, the fault relay will change state. See figure 2.5 for Common Relay terminal location and figure 2.17 for contact definitions. Terminals are fitted adjacent to all relay blocks to provide 24 V dc 200 mA supplies for switching low power devices.
AUDIBLE
VISUAL
BEACON
-
+
SOUNDER
0V S1 S2
AV3
AV2
AV1
0V
Loop all connections to a second audible visual alarm if required.
Figure 2.16 Connections for AV drive
Common Alarm and Fault relay configurations can be set using the User Control Panel and Menu System.
See section
III
. Operation on page 14 for details.
NO
C
Contacts shown de-energised
(non-inverted)
NC
NC
C
Contacts shown energised
(inverted)
NO
Figure 2.17 Gasmaster contacts for all relays are identified on the terminal PCB.
Installaton GasMaster
2.9.3 Channel relay connections
Gasmaster 4 provides Double-Pole-Change-Over
(DPCO) relays for each channel. The relays provide a contact rating of 250 V ac 8 A (non-inductive),
5 A (inductive) for Alarm 1 and Alarm 2. Each relay can be set in its non-active state as energised
(
Fal safe
) or de-energised. Refer to figure 2.5 for location of Channel Relay terminals and figure
2.17 for contact definitions. Terminals are fitted adjacent to all relay blocks to provide 24 V dc
200 mA supplies for switching low power devices.
Channel Alarm thresholds and configurations can be set using the User Control Panel and Menu
System. See section
III.
Operation on page 14 for details.
Fire Channels
Conventional fire channels will activate both Alarm
1 and Alarm 2 relays on the affected channel in the event of an alarm. The Common Alarm 2 relay only will activate. 4-20 mA flame detectors will activate two levels of alarm as per a gas detector.
ESU Channels
If the ESU sampling device slows significantly causing reduced sample flow the Alarm 1 relay for that channel will activate. If the sampling device stops the Alarm 2 relay will activate. The
Common Alarm relays
will not
activate if the sampling device slows or stops. If the cable to the sampling device is open or short-circuited the
Common Fault relay will activate.
2.9.4 Analogue outputs
Gasmaster provides an analogue output for each channel which can be set as either 4-20 mA or
1-5 V dc by fitting a link (see Figure 2.18). These signals can be used to drive PLC/DCS/SCADA systems or remote displays. 4-20 mA outputs are current source (resolution 0.1 mA) and can drive a maximum load of 700
Ω
, 1-5 V outputs require a minimum load of 50 K
Ω
.
Analogue outputs will function in the following way:
-0 mA gas detectors:
the output will track the input from 3 to 21.5 mA, the signal will drop to
0 mA if the input rises above 21.5 mA to signal a fault. A sensor signal that is greater than 110% of range is designated by Gasmaster as a fault condition. The signal will be set to 2 mA to indicate when a channel is inhibited, and 0 mA when a channel is in fault.
Fre channels:
a signal of between 4 and 12 mA indicates a 'no-fire' condition, 12-20 mA indicates a fire, 0mA indicates a fault (open or short circuit). A 2 mA signal indicates that a channel is inhibited.
ESU channels:
a signal of between 4 and 12 mA indicates the sampling device is operating correctly, 12-20 mA indicates a sampling device failure,
0 mA indicates a fault (open or short circuit). A
2 mA signal indicates that a channel is inhibited.
0V
SIG
SCR
0V
SIG
SCR
0V
SIG
SCR
0V
SIG
SCR
LK7
Link: 1-5V
No Link: 4-20mA
LK8
Link: 1-5V
No Link: 4-20mA
LK9
Link: 1-5V
No Link: 4-20mA
LK10
Link: 1-5V
No Link: 4-20mA
Figure 2.18 Gasmaster analogue output connection terminals
2.9.5 RS-485 communications
Gasmaster can provide alarm and system information to PLC/DCS/SCADA systems via a two-wire link using the Modbus RTU protocol (9600 baud,
8 data bits, no parity, 1 or 2 stop bits). Up to 16
Gasmaster systems can be 'multi-dropped' on a single two-wire link with a maximum cable length of 1 Km, two-core twisted pair cable is recommended. Single Gasmaster systems that are to communicate via the RS-485 link should have the
RS TERM
link made, which connects a terminating resistor. For multi-dropped systems the
RS TERM
link should be removed from all
Gasmasters except the last unit on the line.
A Modbus specification document is available from Crowcon on request.
GasMaster Installaton
The RS-485 terminals on Gasmaster systems ordered with the optional local communications connector will be used for terminating the connector leads. These leads must be removed if a remote RS-485 serial link is required.
485A
485B
SCR
LK2
RS485
TERM
Figure 2.19 Gasmaster RS-485 terminals
2.10 Applying power
Before applying power ensure that any control or shutdown systems to which the
Gasmaster is connected are inhibited.
Once all field cables have been installed, the batteries can be connected as per the diagram attached to the chassis plate. (Refer to section
4.4.) Gasmaster will not power up until an external power supply is applied.
Apply power to Gasmaster from either the AC or
24 V dc external supplies. Outputs are inhibited for a preset time after power-up, and the system will perform a start up sequence testing alarm indicators and the internal sounder. If after a settling period faults are reported, check the sensor connections again or refer to Faults Menu on page 20.
When power is applied the green Power LED will illuminate and flash every 5 seconds to indicate that the system is operational.
If the external supply fails, Gasmaster will continue to operate from its internal batteries and the Power LED will flash every second. Depending on configuration, Gasmaster will display either a
Warning (Warning LED lights and the sounder will beep every 5 seconds) or a fault (the Fault LED and sounder will activate, and the fault relay will change state).
Gasmaster should display all channels being monitored. Allow sensors to settle before commencing calibration, refer to sensor instructions supplied with detectors for recommended settling times.
Note:
your Gasmaster is supplied pre-configured, refer to the
Specfcaton and Inspecton
Certfcate
provided with your system. If no channels are configured, Gasmaster will display the following screen:
No detectors!
Please configure
To configure your system go to page 25.
2.11 Battery back-up times
Gasmaster is fitted with 1.2 Ah batteries to provide continued operation in the event of a power loss. Examples of typical back-up times are provided below for a system in a non-alarm state, relays set as de-energised and with the 4-20mA outputs unused (system current consumption without detectors is approximately 50mA):
Gasmaster 1 with a toxic gas detector (2-wire): 21 hours
Gasmaster 1 with an oxygen detector (2-wire): 16 hours
Gasmaster 1 with a pellistor flammable gas detector: 9.5 hours
Gasmaster 1 with an Infrared gas detector: 2.5 hours
Gasmaster 4 with four toxic gas detectors (2-wire): 10 hours
Gasmaster 4 with four oxygen detectors (2-wire): 4 hours
Gasmaster 4 with four pellistor flammable gas detectors:
2 hours
Gasmaster 4 with four Infrared gas detectors: 25 minutes
Gasmaster incorporates protection to prevent the internal batteries being damaged by being deeply discharged. When operating from internal batteries, Gasmaster will display a "Warning
- battery low" fault message when the battery voltage drops to 22 V. When the voltage drops to approximately 20 V, the batteries will be automatically disconnected. The batteries will only be re-connected when the external power supply is re-instated, and will take approximately 18 hours to fully re-charge.
Installaton
Note:
The internal batteries may not be charged efficiently when Gasmaster is powered from an external dc supply, and therefore the back-up function may not work if the external supply fails
Please contact Crowcon for further advice.
2.12 Commissioning
Note:
it is strongly recommended that persons intending to commission a Gasmaster system first read and understand the Operating instructions provided in section
III.
Operation.
When all field devices have been connected and powered-up, commissioning can commence. Gas detectors should be calibrated according to their instructions, fire detectors should be tested using appropriate tools.
Alarms should be simulated and actions noted to ensure that the system operates as intended. All warning devices should be checked, and interfaces with auxiliary equipment should also be verified. The test and View menu's are provided for this purpose (see page 23 and 26).
2.12.1 Zero adjustment and calibration
Calibration must be carried out separately on individual gas detectors on Gasmaster. Follow calibration instructions supplied with each detector. Ensure at all times the local legislation and codes of practice are complied with.
Allow detectors to stabilise for at least one hour before commencing calibration. Refer to detector manual for more information.
Gasmaster provides Zero and Calibration Wizards to enable you to carry out calibration easily. These are accessed through the Operator Display Panel and Menu System. Section
III.
Operation provides detailed information on the menu structure and operator buttons.
Zero adjustment
1. From the normal operating display, press the
Continue
button to enter the menu system.
2. Use the
Up
and
Down
buttons as necessary to select
Supervisor
and press
Continue
.
GasMaster
3. You will be asked to enter a
password
, press
Continue
.
The default password is ZZZ (uppercase), use the
Up
and
Down
buttons to enter the first character of the password.
Note:
Double click the
Up
or
Down
button to move to the top or bottom of the alphabet list. To enter numbers or lower case characters, continue pressing the
Up
or
Down
button.
When you have selected the correct character, press
Continue
, the cursor will move to the next character position.
Continue entering the rest of the password. When you have finished press the
Continue
button twice.
(See 3.7 in section
III.
Operation for details of entering text strings).
4. The Zero Wizard offers temporary Inhibit but you may wish to Inhibit all channels during the calibration process.
How to set global inhibit:
From the
Supervisor
menu, scroll down to
Inhibit
and press
Continue
. Select
All
and press
Continue
. Use the
Up
or
Down
button to set inhibit to
INHIBIT=ON
, press
Continue
to accept. Use the
Back
button to return to the
Supervisor
menu. The Inhibit icons will appear on the channel display.
How to set channel inhibit:
Channel inhibit can be selected from the
Inhibit
menu or within the
Zero
or
Calibrate
menu. Follow the instructions provided above, selecting the
Channel
#n
(where n represents the channel number) in place of
All
.
5. From the
Supervisor
menu, use the
Up
and
Down
buttons to select
Zero
by pressing the
Continue
button.
6.
Select the channel to apply zero. Press the
Continue
button to step through the Zero Wizard.
7. Press
Continue
when
‘…Only continue if in clean air!…’
is displayed, ensure the detector has been
GasMaster Installaton
correctly zeroed first (i.e. 4 mA)
Press
Continue
to apply
Zero now
.
Gasmaster will display zero is successful or
‘Pass’
when
‘Fail’
if the detector zero is out of range.
8. Use the
Continue
button to Zero other channels or
Back
button to the
Supervisor
menu to continue calibration.
Calibration
1. Follow points 1 to 3 above in Zero adjustment to enter
Supervisor
mode.
2. Before you commence calibration, ensure the channels are inhibited prior to applying gas. Channels can be inhibited globally or individually.
Follow the instructions given in step 4 in
Zero Adjustment.
3. From
Supervisor
menu, scroll down and select
Calibrate
.
4. Select the channel to calibrate. Press the
Continue
button to step through the
Calibrate Wizard. Ensure the channels are inhibited prior to applying gas.
5. The next wizard screen displays the default calibration gas concentration as
50% of range. If necessary this calibration figure must be adjusted to match the concentration of the calibration gas used.
Adjust the value using the
Up
and
Down
buttons as necessary and press
Continue
.
6. When "Apply Gas" is displayed, apply gas to the detector and press
Continue
, allow readings to settle.
7. Press
Continue
when the reading on the appropriate channel is stable, and the detector has been calibrated according to its instructions.
Gasmaster will display
‘Pass’
when successful or
‘Fail’
signal is out of range.
if the detector
8. Calibration is complete when
‘Purge’
is displayed, remove the gas from the detector.
Use the
Continue
button to calibrate another channel or
Back
button to exit
Supervisor
mode and return to the main display.
9. Ensure that all channel inhibits are removed after calibration is complete.
2.12.2 Testing fire channels
To test
smoke detectors,
inhibit the relevant FIRE channel and use a smoke test aerosol to test each detector on a loop in turn. The channel display will indicate FirE when the detector activates.
Each detector on a loop should be reset before testing the next to ensure that all detectors activate the alarm.
Heat detectors
can be tested with a heat-gun using the same method as described above.
Flame detectors
can either provide a signal using contacts, or a 4-20 mA signal.
A contact type detector will be connected as a conventional fire loop using 470
Ω
series resistors and a 1K8 end of line resistor and will only indicate FIRE or FAULT. A 4-20 mA detector will be connected directly as a 4-20 input, and may have various alarm levels to indicate UV or IR activation
(please refer to the instructions supplied with the device for details). Flame detectors require a UV or
IR torch (depending on detector type) to simulate alarms. Inhibit the relevant channel, shine the torch at the detector and check that FirE is shown on the Gasmaster display. For 4-20 mA detectors, also check that the appropriate alarm level is displayed.
2.12.3 Testing ESU channels
To test a channel monitoring an ESU sampling device, inhibit the channel and manually slow the device, check that Alarm Level 1 is activated.
Manually stop the device and check that Alarm
Level 2 is activated. If the alarms do not activate the thresholds may need changing, refer to section
3.10 for details on how to change alarm levels.
When commissioning is complete ensure that the system is left fully functional with no faults present and no channels inhibited.
Operaton GasMaster
III. Operation
Every Gasmaster system is pre-configured by
Crowcon, please refer to the
Specfcaton and
Inspecton Certfcate
provided with the product for configuration details. This section describes the operation of pre-configured units, and includes procedures for altering settings.
3.1 Gasmaster Operator Panel
The Operator Panel allows you to communicate with Gasmaster. Use it to monitor the status of all attached field devices, determine system settings and configuration of field devices. Figure
3.1 shows the Operator Panel and typical display under normal, non-alarm monitoring conditions.
Fault LED
Accept/
Reset
Up
Down
Power LED
#1=CH4
#3=O2
#2=H2S
#4=Fire
1
Alarm LED
Warning LED
M essage and channel reminder display area
Back
Continue
00 LEL
2
Channel display area
3
00 V/V
PPM
Channel number
4
#1=CH4
#3=H2S
In the event of an alarm, this message area will display the channels in alarm and their location.
See section 3.8 for more information on alarm conditions.
ALARM:
Boiler room
#2=O2
#4=FIRE
#1=CH4
If more then one channel is in alarm, the alarm message will cycle through all messages.
In the case of a fault (or warning), brief details of the fault will be displayed. See section 3.9 for more information on fault conditions. Detailed fault and warning messages can be found in section 3.10.
FAULT: =30
Chan #3 over range..
Figure 3.1 Operator Display Panel and buttons
Gasmaster Display
The User display provides continuous readings for up to 4 field devices plus a display area for user messages and channel number summary.
Gasmaster 1 provides display for one field device plus the message area.
Message display area
In normal, non-alarm condition, the message area displays the channel numbers and detector types, e.g. CH4 refers to methane detector, see following example.
The # symbol represents the channel number (i.e.
#1 is channel 1).
Note:
User messages longer then sixteen characters are displayed as scrolling text.
If fault and alarm conditions are present at the same time, alarm messages take priority.
Channel display area
Gasmaster 4 has a large clear display which shows all gas levels simultaneously. Gasmaster 1 has a display for one gas level only, see figure 3.2. The image below shows details of the channel display area and icons that are used on Gasmaster.
GasMaster Operaton
Fault
Warning
Alarms
Gas reading
#1=CH4
1
2
00 LEL
Channel number
00
00
PPB
PPM
LEL
V/V
Units
Figure 3.2 User display Gasmaster 1
Display panel LEDs
The LEDs on the Gasmaster Display Panel indicate the following:
Yellow Fault LED:
Lights when any detector or system fault is detected (see page 23 for a list of fault messages). The fault LED operates with the common fault relay, and can be set as latched or non-latched dependant on the system configuration.
Yellow Warnng LED:
Lights when a warning condition is present
(see page 25 for a list of warning messages).
The warning LED will automatically reset when the cause is cleared.
Green Power LED:
Is normally on when power is present, and will switch off briefly once every five seconds to indicate that the system is operational. The
LED will flash on and off every second when
Gasmaster is operating from its batteries due to power failure.
Red Alarm Bar:
Will flash when an alarm from any channel is triggered, and will remain in a steady 'on' state when the accept/reset button is pressed. The LED bar will flash again if a new alarm is triggered.
Operator Panel Buttons
Use the five operator buttons to respond to alarm conditions, examine the status of system settings, and configure Gasmaster.
ACCEPT/RESET
Press the
Accept/Reset
button to mute the internal sounder and external alarms.
When alarm or fault conditions have cleared, press
Accept/Reset
again to reset the system.
Double-click the
Accept/Reset
button to exit the menu system and return to message display.
UP and DOWN
Use the
Up
and
Down
buttons to scroll through menu items.
Press and hold the
Up
or
Down
button to move quickly through the menu items.
Double-click the
Up
or
Down
button to move directly to the top or bottom of the alpha-numeric characters when configuring text or entering the Supervisor password
In
Supervisor
Mode (see section 3.7), use the
Up
and
Down
buttons to change values or settings.
In normal, non-alarm conditions, press and hold the
Up
and
Down
buttons to adjust the message display area brightness.
CONTINUE
Use the
Continue
button to display available menus. The menu system can be accessed during normal channel monitoring, alarm or fault condition. Gasmaster has four standard menus plus one advanced menu. See figure 3.4 on page
24 for an overview of Gasmaster’s Menu
System. The standard and advanced menus are as follows:
Operaton GasMaster
Faults
.
Lists the fault conditions present
Warnings
.
Lists the warning conditions present
View
.
View current status of relays, outputs, detector inputs, power supply and configuration
Action
.
Perform routine operations: tests of control panel or audio visual alarms
Supervisor
.
Perform password protected supervisor functions: inhibit channels, calibration, testing and configuration
Use the
Continue
button and the
Up
and
Down
buttons, to navigate through the menu system. Use the
Continue
button to select and action menu items, submenus and wizard menus.
During editing and configuration of
Gasmaster, use the
Continue
button to accept changes made to settings.
BACK
Use the
Back
button to exit the menu system or cancel actions. Double-click the
Back
button to cancel text edits or return to the main menu.
3.2 Gasmaster start up sequence
At power up during Gasmaster installation, or when Gasmaster is restarted, Gasmaster will initialise the system by performing a self-test. The start up sequence is shown below:
Display and AV test
GASMASTERII
= Software version number
...Gas detection you
#1=CH4
#3=H2S
scrolling text
#2=O2
#4=FIRE
3.3 How to adjust display contrast
To edit the display contrast press and hold the
Up
button to increase contrast, and
Down
to decrease contrast. The contrast level will be displayed.
Menu contrast
=
+++++......
The menu display contrast is altered independently from the channel display area. Press the
Continue
button whilst still in the Menu
Contrast screen, use the
Up
or
Down
button to choose Menu Display or Channel Display.
Press
Continue
to select. Adjust the display contrast as described above. Press the
Back
button to finish.
3.4 How to display Instrument serial number and system identity
The system identity and instrument serial number can be displayed during normal channel monitoring, alarm or fault conditions.
To display the system identity and instrument serial number, press and hold the
Back
button.
GasMaster Operaton
First the Local Service telephone number is displayed followed by the customer identity display.
After 10 seconds the serial number will automatically be displayed on the next screen (for approximately 4 seconds).
The
Continue
button can be used to advance to the next screen. Use the
Back
button to return to the previous screen. The display will return to the normal operating display when finished.
3.5 Using the menu system
To enter the menu system press the
Continue
button. The menu system can be accessed during normal channel monitoring, alarm or fault condition. The message area will display the following screen:
MENU:
Faults
Note:
if the menu system has been accessed previously, the menu item displayed will be the last actioned menu item. For example, if you were using Supervisor mode the last time, the menu display will show this:
MENU:
Supervisor
Use the
Up
and
Down
buttons to scroll through the menu list. To exit the menu press and hold the
Accept/Reset
button or press
Back
button as many times as necessary.
Menu display
The top line of the message area displays the current menu level. Some menu levels have submenus and wizards that guide you through configuration. The lower line displays the menu item, value or setting.
Use the
Up
and
Down
buttons to scroll through the menu list, press
Continue
to select the menu item.
Refer to figure 3.4 on page 24 for an overview of the menu system.
Menu wizards
Wizards are an extension of the menu system to guide the user through a process such as calibration. A wizard menu will consist of selections, user prompts and display status conditions during the process.
The
Back
button can be used to return to the previous screen or abort the wizard. The
Down
and
Up
buttons are used to alter a selection.
The
Continue
button accepts the current selection and continues to the next step of the wizard.
Wizards are available for
Zero
and
Calbraton
menus in
Supervisor
menu.
3.6 Inhibiting channels
Inputs can be temporarily inhibited so as not to cause alarms. This may be necessary when calibrating detectors, or when operations are carried out close to a sensor which may trigger an alarm
(for example, soldering near a smoke detector).
Input channels can be inhibited individually or all at once. The 'inhibit' option is available in the
Supervisor Menu, see the Menu System Overview on page 23 for details on how to access this function.
When inhibited Gasmaster will:
Display the 'inhibit' symbol on the channel display for each affected channel.
Illuminate the yellow 'Warning' LED.
In the event of an alarm on an inhibited channel,
Gasmaster will:
Illuminate the Alarm symbol on the channel display for the affected channel.
Illuminate the red alarm LED bar.
Display the alarm text message for the affected channel.
Gasmaster
will not:
Operate any relays associated with the affected channel.
Drive external audible visual alarms.
Activate the internal sounder.
Operaton GasMaster
If it is necessary to permanently disable a channel, enter Supervisor Mode and set the relevant detector Type to Unused (see page 21 section 3.10).
The channel display will then blank, and the power supply will be removed from the detector.
Warning
Crowcon strongly recommends that remote inhibit switches be key operated only, and that access to the key should be restricted to authorised personnel. A Gasmaster system that has been inhibited without other safety precautions being in place may not provide the protection for which it was designed.
Steps should be taken to ensure that all appropriate personnel are aware when a
Gasmaster system is inhibited.
3.7 Using the Control Panel in
Supervisor Mode
Supervisor mode provides all the functions required for trained personnel to perform system installation and configuration of field devices. This area is a password protected to prevent mis-use or accidental changes.
From the operator panel, you can select menu items and associated values to configure relays and field devices. All the menu items are explained in section 3.10, page 21.
You can modify settings by:
Selecting values from a list
Editing numeric values
Editing text strings
How to enter Supervisor mode
1. Press the
Continue
button to enter the menu system.
2. Use the
Up
and
Down
buttons as necessary to select
Supervisor
and press
Continue
.
3. You will be asked to enter a password, press
Continue
. Use the
Up
and
Down
buttons to enter the first character of the password. The default password is ZZZ.
Note:
Double click the
Up
or
Down
button to move to the top or bottom of the alphabet list. To enter numbers or lower case characters, continue pressing the
Up
or
Down
button.
For convenience, after the first character has been entered, the next character will start from the same point in the alpha-numeric list. To enter ‘ZZZ’ use the
Up
and
Down
buttons to enter the first letter, then simply press
Down
then
Continue
,
Down
then
Continue
.
When you have selected the correct character, press
Continue
, the cursor will move to the next character position.
Continue entering the rest of the password. When you have finished press the
Continue
button twice.
Note:
When the Supervisor mode is active the
Warning LED on the control panel will illuminate
How to select values from a list
1. With the menu item selected use the
Up
and
Down
buttons to scroll through the available list items. When the value you require is displayed press the
Continue
button.
For example, when configuring the Units of a channel, the possible settings are: none, FIRE, PPB, PPM, %LEL and %VOL, as you scroll through the list the unit symbol will appear on the display.
Press
Continue
to make a selection.
The menu screen will return to the next menu item in the list.
How to edit values of parameters
1. With the menu item selected press the
Continue
button. Use the
Up
and
Down
buttons to change the parameter value. Press
Continue
to accept new value.
The menu screen will return to the next menu item in the list.
How to edit text string values
1. With the menu item selected press the
Continue
button. A flashing cursor will appear below the first character of
0
GasMaster Operaton
the text string, you are now in edit mode. Use the
Up
and
Down
buttons to scroll through the character values. See
Appendix D for more information
Note:
Double click the
Up
or
Down
button to move to the top or bottom of the alphabet list. To enter numbers or lower case characters, continue pressing the
Up
or
Down
button.
When you have selected the correct character, press
Continue
, the cursor will move to the next character position.
Note
: The next character will start from the last one selected.
If you are editing a current text string, press
Continue
to accept a character you wish to keep.
To delete characters press the
Back
button, all characters will be deleted to the right of the cursor.
If a text string is deleted in error, double-click the
Back
button to exit the menu item. The original text string will be retained.
Continue entering the rest of the text string. To finish press the
Continue
button once more.
3.8 In the event of an alarm
In the event of an alarm the message display area will display the channel in alarm and the detectors location (if this information has been pre-set in the configuration), the Alarm LED will flash, the internal sounder and any dedicated audible visual alarms will activate, and any external alarm apparatus connected through the channel relays will operate. If more then one channel goes into alarm, the display will cycle through the channels in alarm. Channel display area in the Figure 3.3 shows channel #2=CH4 (methane) in alarm condition. The gas reading will cycle back and forth between the channel type and the gas reading.
Gas detectors
The channel or channels in alarm will display an alarm symbol and flash alternately with the type of the detector in the channel display. Gasmaster provides low and high alarm levels, these levels are user configurable and can be set as rising or falling.
Fre detectors
Fire detectors in alarm will display
FIRE
in the channel display. There is only one level of alarm for fire channels.
Envronmental samplng Unts (ESU)
ESU sampling devices that have slowed or stopped will display ESU. Level 1 means slow, level 2 means stopped
To mute the sounder
Press the
Accept/Reset
button on the operator panel (or remote Accept/Reset switch if fitted).
The Alarm LED will stop flashing, but remain lit.
The channel display will show the gas reading.
When alarm conditions have cleared, press the
Accept/Reset
button to clear any latched alarms.
2
00
LEL
Figure 3.3 Example system in alarm
3.9 In the event of a fault
In the event of a fault the fault LED will illuminate and the internal sounder will activate. The message area will display
FAULT
: and fault ID number. The fault description will appear in the lower portion of the message area, messages longer then 16 characters will be scrolled across the screen.
Pressing Accept/Reset will clear the fault message from the display. To display a list of all faults present, use the faults menu.
A list of faults can be found in the menu system overview on page 24.
3.10 System Configuration
Your Gasmaster system is supplied pre-configured, however, you may wish to configure relay
Operaton
and alarm settings to suit your requirements or adjust detector values, carry out calibration and other confidence checks. Your Gasmaster system can be configured using the Operator Panel and
Menu System. You will find details of the menu structure and configuration options over the next few pages, refer to figure 3.4 for an overview of the menu structure.
To edit your systems configuration you must enter the Supervisor mode which is password protected to prevent miss-use or accidental change. (Refer to section 3.7 for details on entering Supervisor mode.)
For more information on testing your Gasmaster system, please go to the Maintenance section on page 34.
Gasmaster PC software is available which enables full system configuration from a PC. An optional communications port is required if Gasmaster PC is to be used, contact Crowcon for details.
3.10.2 Re-configuring a channel
Your Gasmaster system is supplied pre-configured, but you may require to re-configure when a detector is changed or a new detector is added.
This section provides details on configuring channels, refer to page 31 ‘Channels #1 to #4’ from the Supervisor configuration menu.
3.10.3 Limitations
If Gasmaster is used in a manner not specified in this manual, the protection provided may be impaired.
GasMaster
GasMaster Menu system overvew
Menu system overview
Over the next few pages you will find a detailed description of the menu system. Use figure 3.4 as an overall guide to locate menu items.
Gasmaster has five standard menus: Faults, Warnings,
View, Actions and Supervisor. Only the Supervisor menu allows you to configure Gasmaster.
This section contains tables that list the menu items for each menu and the available values.
Faults menu
(lists faults present on the system)
See 3.7 'Using the Control Panel in Supervisor
Mode’ on page 20 for instructions on how to alter settings.
Note:
The display only shows two lines of information at a time. Use the
Up
and
Down
buttons to see additional menu items or values.
Use
Continue
to select choices and
Back
to exit menu.
Menu Item Values
(as shown on display)
Description Fault codes
No faults
Faults
(end of list)
Measurement system failure!
Warning - Battery low
Relay power supply fail
Main supply fail
NVM hardware fail
Loaded default settings
No faults are present
Fatal fault, contact Crowcon. 1 or 2
Input supply has failed and internal 4 battery supply has dropped to 22 volts.
Power rail to the relays has failed and 5 relays will no longer operate. Contact
Crowcon
Main supply has failed and the system 6 is running on batteries
Fatal fault, contact Crowcon.
System has returned to standard configuration settings. Re-configure using the Supervisor menu.
7
8
Common relay fail
Chan #1 relay fail
ESU #1 stalled!
ESU #1 slow!
Chan #1 over range
Coil fault detected. Contact Crowcon 9, 10, 11
Channel relay coil fault detected.
Contact Crowcon.*
12 to 19
ESU sampling device has stopped.*
ESU sampling device has slowed.*
20 to 23
24 to 27
Chan #1 under range
Detector input signal is over 21.5 mA. 28 to 31
Investigate cause at detector taking necessary precautions as high gas levels may be present.*
Detector input signal is under 3 mA. 32 to 35
Check detector.* If the 'Interpret
2 mA' command is set to Warning or Inhibit in the channel configuration, this fault message will display when the input signal drops below 1mA.
* #1 denotes the channel number and therefore may read #2, #3 or #4 on Gasmaster.
The fault codes are numbered to relate to a particular channel where appropriate (e.g. fault code 19 means there is a fault on Channel 4 Level 2 alarm relay).
Menu system overvew GasMaster
Press
CONTINUE
Faults
Warnings
View
Action
Supervisor
Faults Menu
Lst of faults present
Warnings
Menu
Lst of warnngs present
View:
Relay com stat
Alarm L1 common
Alarm L2 common
Fault common
View:
Configuration
System
Language
AV drive
Relay common
Channels 1 to 4*
View:
Relay chan stat
Alarm L1
(Channels 1 to 4)*
Alarm L2
(Channels 1 to 4)*
View:
Configuration:
Relays common
Alarm L1 common
Alarm L2 common
Common Fault
Note:
* Menu items are hidden for unused channels
† Visible only for 4-20 mA
Sink/SRC
‡ Visible only for Fire conv type
^Not present for Alarm 2
View:
Configuration:
Channels 1 to 4*
Type
Name
Location
Units†
Range†
Zero suppression†
Interpret 2 mA†
Stab time
Fire reset time‡
Alarm 1
Alarm 2
(
See Supervsor confguraton)
Figure 3.4 Overview of Gasmaster Menu system
View Menu
Relay com stat
Relay chan stat
Output status
Input status
Supply status
Configuration
Action Menu
Display contrast
Control panel
Audio visual
All Supervisor Menu options are password protected, see page 20 for details of this menu section.
Supervisor:
Test
Relays common
Channels 1 to 4*
Supervisor:
Configuration:
Relay common
Alarm L1 common
Alarm L2 common
Common Fault
Supervisor:
Configuration:
Channels #1 to 4*
Alarm 1 & Alarm 2
Direction
On threshold
Off threshold^
Relay type
Relay drive
Indication^
Supervisor
Menu
Password
Inhibit
Zero
Calibrate
Test
Configure
Supervisor:
Configuration
System
Language
AV drive
Relay common
Channels 1 to 4*
Supervisor:
Configuration:
Channels #1 to 4*
Type
Name
Location
Units†
Range†
Zero suppression†
Interpret 2 mA†
Stab time
Fire reset time‡
Alarm 1
Alarm 2
GasMaster Menu system overvew
Warnings menu
(lists .warnings .present .on .the .system)
Menu Item Values
(as shown on display)
Description Codes
No warnings (end of list)
Warnings
Supervisor mode
No warnings are present.
System configurations may be changed.
Global inhibit All input channels are inhibited.
Testing audio visual alarm Audible visual outputs will be driven.
Service/calibration due Service or calibration interval has expired.
Common relay forced
Main Supply Fail
1
2
3
4
Common alarm or fault relays are being forced 5, 6, 7 to their 'alarm' state.
Main supply has failed and the system is running on batteries
8
Detector #1 stabilising
Detector #1 input low
Detector is currently in its stabilisation or reset 9, 17, 25, 33 period*, (see page 30).
Detector input signal is between 1 and 3 mA.* 10, 18, 26, 3
Only applies when the 'Interpret 2 mA' command is set to Warning in the channel configuration.
Detector #1 initiated inhibit
A 2 mA inhibit signal has been received from a 11, 19, 27, 35 detector.* Only applies when the 'Interpret
2 mA' command is set to Inhibit in the channel configuration.
Chan #1 inhibited Input channel is in an inhibit state* . 12, 20, 28, 36
Chan #1 input simulated Channel input is being forced in Test mode.* 13, 21, 29, 37
14, 28, 30, 38 Chan #1 output forced
Chan #1 relay forced
Channel analogue output is being forced in
Test mode.*
Channel alarm relay is being forced in
Test mode.*
* #1 denotes the channel number and therefore may read #2, #3 or #4 on Gasmaster.
15, 16, 23, 24
31, 32, 39, 40
Menu system overvew GasMaster
View menu
(shows .system .status .and .configuration, .but .does .not .allow .changes .to .be .made .)
Menu Item Values
(as shown on display)
Description
Relay com stat
Alarm L1 common
Values = No alarm
In alarm
Alarm L2 common
Values = No alarm
In alarm
Fault common
Values = No alarm
In alarm
Relay chan stat
Alarm L1 #1
Values = No alarm
In alarm
Alarm L2 #1
Values = No alarm
In alarm
L1 = Level 1.
L2 = Level 2
The 'values' show the current state of each relay
(relays may be normally energised or de-energised dependant on configuration):
'No alarm' means the relay is in its normal state.
'In alarm' means the relay is in its alarm or fault state.
#1 refers to the input channel, use the Down button to scroll to channels #2, #3, #4 if appropriate.
L1 = Level 1.
L2 = Level 2 (use the down key to view level 2).
The 'values' show the current state of each relay
(relays may be normally energised or de-energised dependant on configuration):
'No alarm' means the relay is in its normal state.
'In alarm' means the relay is in its alarm state.
Output status
Output #1
Values = 0.0 to 25.5 mA
#1 refers to the input channel, use the Down button to scroll to channels #2, #3, #4 if appropriate.
The 'values' show the current analogue output level for a channel.
Input status
Input #1
Values = 0.0 to 66.7 mA,
#1 refers to the input channel, use the Down button to scroll to channels #2, #3, #4 if appropriate.
The 'values' show the current signal input level for a channel.
Supply status
Supply
Value = 19.8 to 40 V
Configuration
See table
Supervisor menu
:
Indicates the DC supply level from either the internal
PSU or an external DC supply.
* #1 denotes the channel number and therefore may read #2, #3 or #4 on Gasmaster.
GasMaster Menu system overvew
Actions menu
(allows .basic .tests .and .adjustments .)
Menu Item Values
(as shown on display)
Description
Audio visual
Audio Visual:
Test alarm?
Values = Testing beacon
Testing alarm L1
Testing alarm L2
Test complete
Control panel
Control Panel:
Start test?
Test complete
Display contrast
Display:
Values = Menu contrast
Channel contrast
Drives Audible Visual alarm terminals to test external audible visual alarms
Beacon output becomes active for 3 seconds, followed by;
Sounder level 1 output becomes active for 3 seconds, followed by; followed by;
Sounder level 2 output becomes active for 3 seconds,
Outputs de-activate and display returns to the Audio
Visual menu
Press Continue to test LCD display, LED's and internal sounder for 3 seconds. Display returns to Control
Panel menu
Alters the message display area contrast
Use the Up and Down buttons to adjust the contrast of the LCD
Menu system overvew GasMaster
.
Supervisor menu
(allows .system .tests .to .be .performed, .and .configurations .to .be .changed . .A .pass .
.
word .is .required .to .enter .this .mode, .see .section .3 .7 .for .details .)
Menu Item Values
(as shown on display)
Inhibit
Zero
Calibrate
All
Values = Inhibit off
Inhibit on
Channels #1, #2, #3, #4
Values = Inhibit off
Inhibit on
Zero Wizard
Select channel
Values = #1=name
#2=name
#3=name
#4=name
Select channel Inhibit
Values = Inhibit on
Inhibit off
User confrmaton
Only continue if in clean air!
Result
Values = Pass
Fail
Calibration Wizard
Select channel
Values = #1=name
#2=name
#3=name
#4=name
Cal #1 level
Values = 25% - 100% of range
Description
Inhibits all input channels when selected.
Only whilst in Supervisor mode used for calibration and test
Allows individual channels to be inhibited.
NB: Inhibit persists on exit from Supervisor mode
Use Down button to select the required channel to zero, then follow wizard instructions.
Inhibit option will not be displayed if channels have already been set to inhibit using the menu shown above.
Reminds the user to check that the detector has been zeroed and is currently not seeing gas.
Channel has correctly zeroed
Input signal was out of acceptable range, re-zero the detector and check that its output current is 4 mA.
Use Down button to select the required channel to calibrate, then follow wizard instructions.
Select channel Inhibit
Values = Inhibit on
Inhibit off
User acton
Apply gas
User confrmaton
Continue when reading is
stable
Refers to the calibration gas concentration
Calibration is only possible with a gas concentration that is at least 25% of the full range of the sensor.
Use the UP and Down buttons to enter the concentration of the calibration gas (e.g. 50% LEL,10 ppm etc.).
Gasmaster will store the gas value entered so that it does not need to be adjusted next time the sensor is calibrated.
Inhibit option will not be displayed if channels have already been set to inhibit using the Inhibit menu.
Apply gas and calibrate the detector.
Press Continue when the detector has been calibrated and is providing the correct output signal.
GasMaster Menu system overvew
Supervisor menu
.
(allows .system .tests .to .be .performed, .and .configurations .to .be .changed . .A .pass .
.word .is .required .to .enter .this .mode, .see .section .3 .7 .for .details .)
Menu Item Values
(as shown on display)
Calibrate Calibration Wizard cont.
Result
Value = Pass
Fail
User acton
Purge gas
Test Relay common
Use to simulate inputs and outputs for testing and commissioning purposes.
Relay alarm L1
Alarm L1 common
Values = No alarm
In alarm
Relay alarm L2
Alarm L2 common
Values = No alarm
In alarm
Fault
Fault common
Values = No fault
In fault
Channel #1, #2, #3, #4
Sim Input #1
Values = 0.0 - 25.5 mA
0.0 - 66.7 mA
for fire detectors
Force output #1
Values = 0.0 - 25.5 mA
Description
Channel has correctly calibrated.
Input signal was out of acceptable range, re-calibrate the detector and check that its output current is proportional to the gas level
Reminds the user to remove the calibration gas and re-expose the detector to clean air.
Forces common level 1, 2 or Fault relays.
L1 = Level 1.
L2 = Level 2
The 'values' show the current state of each relay
(relays may be normally energised or de-energised dependant on configuration):
'No alarm' or ‘No fault’ means the relay is in its normal state.
'In alarm' or ‘In fault’ means the relay is in its alarm or fault state.
Use the Up and Down buttons to change the relay state, press Back to exit, the relay will return to its normal state
Use the Up and Down buttons to select the desired channel. The channel warning symbol
will show.
Channel alarm relays can be tested as described above.
When selected, displays the input signal level for the selected channel (e.g. 4.1 mA).
The channel warning symbol
will show.
Use the Up and Down buttons to force the input to the required level. The reading on the channel display will change accordingly and alarms will activate at the preset points.
Use the Accept/Reset button to silence alarms if necessary. Press Back to exit, the input will return to its normal state.
When selected, displays the analogue output signal level for the selected channel (e.g. 4.1 mA).
The channel warning symbol
will show.
Use the Up and Down buttons to force the output to the required level.
No alarms will be activated on Gasmaster. Use to test remote displays.
Press Back to exit, the input will return to its normal state.
Menu system overvew GasMaster
Supervisor menu
.
(allows .system .tests .to .be .performed, .and .configurations .to .be .changed . .A .pass .
.word .is .required .to .enter .this .mode, .see .section .3 .7 .for .details .)
Menu Item Values
(as shown on display)
Relay alarm L1
Values = No alarm
In alarm
Relay alarm L2
Values = No alarm
In alarm
Configure
Select from config sub menus
Use to change below system settings
System
ModBus addr
Values = 1 to 254
Serial comms
Values = 9600, 8, N, 1
9600, 8, N, 2
Identity
Values = 16 character string
Description
Forces level 1, 2 relays for the selected channel.
The channel warning symbol
will show.
Contact orientation will depend on whether the relay is configured as normally energised or de-energised.
Press Back to exit, the relay will return to its normal state.
Required for RS-485 digital communications only, any address in the range can be chosen. If multiple units are connected on an addressable loop to a
'Master' controller, each Gasmaster must have a different address.
Describes the required RS-485 communications parameters; Gasmaster is factory set to 2 stop bit.
Language
AV drive
Mains Fail
Values = AS WARNING
AS FAULT
Language
Values = English (UK) configurable
Beacon type
Values = Latched
Non-latched
Sounder type
Values = Latched
Non-latched
Latch-accept
Allows a system name to be entered which will be shown on the Gasmaster display when the appropriate mode is selected (see section 3.4). Use the Up and Down buttons to enter required alpha-numeric characters and press Continue to accept.
Determines whether a main supply fail is treated as a fault or a warning
The default display language is English. A second language may be available depending on system configuration.
Determines the operation of beacons connected to the 'AV1 Drive' terminal.
Latched
means that in an alarm state, the beacon will continue flashing when the Accept/Reset button is pressed, and will only stop flashing when the alarm is cleared and the Accept/Reset button is pressed again.
Non-latched
means that the beacon will continue flashing when the Accept/Reset button is pressed, but stop automatically when non-latching alarms have reset.
Determines the operation of sounders connected to the 'AV2/3 Drive' terminals.
Latched
means that in an alarm state, the sounder will continue to operate when the Accept/Reset but ton is pressed, and will only stop sounding when the alarm is cleared and the Accept/Reset button is pressed again.
0
GasMaster Menu system overvew
Supervisor menu
.
(allows .system .tests .to .be .performed, .and .configurations .to .be .changed . .A .pass .
.word .is .required .to .enter .this .mode, .see .section .3 .7 .for .details .)
Menu Item Values
(as shown on display)
AV drive cont.
Relay common
Alarm L1 common
Type
Alarm 1 type
Values = Latched
Non-latched
Latch-accept
Drive
Alarm 1 drive
Values = De-energised
Energised
Description
Non-latched
means that the sounder will continue to operate when the Accept/Reset button is pressed, but will silence automatically when the alarm has cleared.
Latch-accept
means that in an alarm condition the sounder will silence when the Accept/Reset button is pressed.
Determines the operation of the common alarm and fault relays.
L1 = Level 1.
L2 = Level 2
Latched
means that in an alarm state, the relay will stay active when the Accept/Reset button is pressed, and will only reset when the alarm or fault has cleared and the Accept/Reset button is pressed again.
Non-latched
means that the relay will stay active when the Accept/Reset button is pressed, but will reset automatically when the alarm has cleared.
Latch-accept
means that in an alarm or fault condition the relay will reset when the Accept/Reset button is pressed.
De-energised
means that the relay coil is not energised in a non-alarm state (normally de-energised).
Energised
means that the relay coil is energised in a non-alarm state (normally energised or 'fail-safe')
Alarm L2 common
Type
Alarm 2 type
Values = Latched
Non-latched
Latch-accept
Drive
Alarm 2 drive
Values = De-energised
Energised
Fault common
Type
Fault type
Values = Latched
Non-latched
Drive
Fault drive
Values = De-energised
Energised
Channels #1 to #4
Press the Up and Down
Config Channel
#1 buttons to cycle through configuration for channels #2,
#3 and #4.
Type
Values = Unused
DET 4-20 SRCE
DET 4-20 SINK
FIRE 4-20 SRCE
Sets the input type for each channel, links on the terminal PCB must also be set to the appropriate positions (see section 2.8 for details).
No detector connected
4-20mA current source gas detector
4-20mA current sink gas detector
4-20mA current source flame detector
Menu system overvew GasMaster
Supervisor menu
.
(allows .system .tests .to .be .performed, .and .configurations .to .be .changed . .A .pass .
.word .is .required .to .enter .this .mode, .see .section .3 .7 .for .details .)
Menu Item Values
(as shown on display)
Description
Channels #
1 to #4 Cont.
FIRE 4-20 SINK
FIRE CONV
ESU
Name
Values = 4 character string
Location
Values = 32 character string
*Options will be shown for
4-20 mA input channels only
Units*
Values = None
%LEL
PPB
PPM
%VOL
FIRE
Range*
Values = 0 to 9999.9
*Options will be shown for
4-20 mA input channels only
Zero suppression (ZFS)*
Values = Enabled
Disabled
Interpret 2mA*
Values = Fault
Warning
Inhibit
Stab time
Values = 0 to 120 seconds
Fire reset time**
Values = 0 to 30 seconds
Alarm L1 #1, #2, #3, #4
See submenu below
4-20mA current sink flame detector
Conventional smoke/heat or call points
ESU sampling device
Detector name (e.g. CH4 for methane, O2 for oxygen, FIRE for smoke/heat detectors)
Optional. Detector location or tag, will be shown on the message display if an alarm occurs
(e.g. Boiler Room).
E.g. for an ESU channel
For flammable channels
Very low range toxic gas detectors
General toxic gas detectors
Oxygen or other high volume gases
Flame or conventional smoke/heat detectors.
Detector range (e.g. 100 for a flammable detector).
Applies suppression to the first 3% of scale to prevent small deviations from zero being displayed.
If the Level 1 alarm for a channel is set below 8% of full scale, the level of suppression is reduced.
Some gas detectors produce a 2 mA signal to indicate a certain state.
This option determines how Gasmaster interprets a signal between 1 and 3 mA.
Inhibits the input for preset time after Gasmaster is powered-up to prevent false alarms while the sensor is settling.
Time for which power is removed from smoke/heat detectors when the Accept/Reset button is pressed.
** Opton wll be shown for conventonal fre channels only
GasMaster Menu system overvew
Supervisor menu
.
(allows .system .tests .to .be .performed, .and .configurations .to .be .changed . .A .pass .
.word .is .required .to .enter .this .mode, .see .section .3 .7 .for .details .)
Menu Item Values
(as shown on display)
Description
Config channel
Submenu:
Alarm L1 #1
Direction
Values = Rising
Level 1 alarm relay
Falling configuration for each channel
Press the Up and Down buttons to cycle through configuration for channels
#2,#3,#4
On threshold
Values = 0.1 to Range
(full scale)
Off threshold
Values = 0.1 to L1 On threshold
(rising alarms)
L1 threshold to full scale - 0.1 (Falling alarms
Rising alarms required where there is normally no gas.
Falling alarms required where gas should normally be present (e.g. oxygen).
Level at which the relay will activate.
Level at which the Level 1 relay will reset. Allows hysteresis for applications such as ventilation control where the fan should continue to run until the gas reaches a low level.
Relay type
Values = Latched
Non-latched
Latch accept
Latched
means that in an alarm state, the relay will stay active when the Accept/Reset button is pressed, and will only reset when the alarm or fault has cleared and the Accept/Reset key is pressed again.
Relay drive
Values = De-energised
Energised
Non-latched
means that the relay will stay active when the Accept/Reset key is pressed, but will reset automatically when the alarm has cleared.
Indication
Values = Visible
Hidden
Latch-accept
the relay will reset when the Accept/Reset button is pressed.
De-energised
gised in a non-alarm state (normally de-energised).
Energised
means that in an alarm condition
means that the relay coil is not enerin a non-alarm state (normally energised or
'fail-safe')
Visible
means that the relay coil is energised
means that an alarm will trigger the alarm
LED bar, internal sounder, external audible visual alarms, and display the alarm message.
Hidden
means that an alarm will only cause the alarm icon in the channel display to show. No other audible or visual alarms will activate (used for ventilation control applications)
A similar menu is available for Level 2 alarm relays, with the exception that the 'Off Threshold' and
'Indication' options are not available.
Alarm L2 #1*
Direction
Threshold
Relay type
Relay drive
* #1 denotes the channel number and therefore may read #2, #3 or #4 on Gasmaster.
Mantenance GasMaster
IV. Maintenance
It is essential that any safety system such as Gasmaster is routinely checked. Crowcon offer service contracts to ensure that this equipment is fully operational at all times.
As a minimum, Crowcon recommend that systems are calibrated and tested on a sixmonthly basis. Sensors should be changed as advised in the detector manual.
Note:
a ‘calibration due’ warning message may be flagged six months after the last service*. The warning LED
will light and the message will be shown in the Warnings Menu (see page 22). This message can be reset using Gasmaster PC, which also allows the period after which the message is displayed to be adjusted.
*Or when the system was last powered-up.
4.1 Functional Testing
Gasmaster allows you to test relays, force inputs into alarm state, and force analogue outputs to verify the correct operation of the Gasmaster system and its interfaces with external equipment.
These functions are available in the
Supervsor
menu under
Test
.
Please note that using this function will activate the appropriate relays, audible visual alarm drives and analogue outputs. Ensure necessary precautions are taken prior to using test functions.
The options available in Test can be found in section 3.10, page 26, along with a description of each function.
4.2 System Inhibit
Inputs can be temporarily inhibited so as not to cause alarms. This may be necessary when calibrating detectors, or when operations are carried out close to a sensor which may trigger an alarm
(for example soldering near a smoke detector).
Input channels can be inhibited individually or all at once. The 'inhibit' option is available in the
Supervsor
menu, see section 3.6 on page 17 and the Menu System Overview on page 20 in the
Operaton
chapter for details of this function.
If it is necessary to permanently disable a channel, enter Supervisor mode and set the relevant detector Type to Unused (see page 29). The channel display will be no longer shown, and the power supply will be removed from the detector.
Warning
Crowcon strongly recommends that remote inhibit switches be key operated only, and that access to the key should be restricted to authorised personnel. A Gasmaster system that has been inhibited without other safety precautions being in place may not provide the protection for which it was designed. Steps should be taken to ensure that all appropriate personnel are aware when a Gasmaster system is inhibited.
How to perform Inhibit
1. From the normal operating display, press the
Continue
button to enter the menu system.
2. Use the
Up
and
Down
buttons as necessary to select
Supervisor
and press
Continue
.
3. Enter the password (the default password is ZZZ), press
Continue
.
See section 3.7 in Operation for details on entering
Supervsor mode
.
4. How to set global inhibit:
From the
Supervisor
menu, scroll down to Inhibit and press
Continue
. Select
All and press
Continue
. Use the
Up
or
Down
button to set inhibit to
INHIBIT ON, press
Continue
to accept. Use the
Back
button to return to the
Supervisor
menu. The Inhibit icons will appear on the channel display.
How to set channel inhibit:
Channel inhibit can be selected from the
Inhibit
menu or within the
Zero
or
Calibrate
menu. Follow the instructions provided above, selecting the
Channel
#n
(where n represents the channel number) in place of
All
.
Ensure all inhibits are removed when maintenance activities are complete.
GasMaster Mantenance
4.3 Detector Calibration
Crowcon recommends that you check detectors routinely to ensure correct calibration and operation.
Gas detectors require recalibration at least every 3 to 6 months. Fire detectors should be tested with the same frequency. Site procedures may require more frequent testing. See section 2.12.1 page
12 for calibration instructions.
For detailed instructions on the routine functional testing of detectors, please refer to the relevant
Installation, Operating and Maintenance Instructions provided with each detector.
4.4 Changing Batteries
During routine servicing, it is recommended that the power be isolated form Gasmaster temporarily to ensure that the back-up batteries are operational. Crowcon recommend that batteries are changed every two years, and replaced as a pair.
Replacement batteries should be Yuasa UCEL
Y1.2-12, 12 v 1.2 Ah C20 lead-acid type cells.
A 10 A fuse is fitted to the batteries, for replacement part number see Spare Parts and Accessories section.
Batteries
Battery connection diagram
Warning
When replacing batteries, care should be taken to ensure cables are re-fitted as shown on the battery connection diagram. Incorrect fitment of battery cables may result in a fire and/or harm to personnel.
4.5 Module Replacement
In the unlikely event of a Gasmaster component failure, Crowcon recommend that repair should not be undertaken by anyone other than Crowcon approved personnel. Please contact Crowcon for details of your nearest service centre.
4.6 Event logging
Gasmaster records alarms, faults and display panel button activities in an Event Log. A maximum of 300 events are logged, after which data is over-written on a first-in-first-out basis. This function provides a record of all system activities which can be uploaded using Gasmaster PC software at any time.
The event log is held in RAM (volatile memory), so in the event of a complete power failure all data will be lost.
4.7 Service card
A card is fitted to the inside of the front cover for logging service activity. It is recommended that this card be filled in with the dates of services, and details of any parts replaced.
4.8 Cleaning
If required, the outside of the Gasmaster case can be cleaned by gently wiping with a damp cloth using a mild soap solution only.
Figure 4.1 Battery replacement
Batteries should be checked regularly on units operating over 40ºC.
Appendx A: Specfcatons
Appendix A: Specifications
Size
Weight
Enclosure material
Ingress protection
Power
Battery back-up
Operating temperature
Humidity
Input:
Gas
Fire
Environmental
Remote inhibit
Remote reset
Sampling Unit control
Outputs:
Relays
Audible/visual alarm drive
Analogue
Digital communications
Communications port
Event logging1
Panel indication
Approvals
Gasmaster 1
288h x 278w x 110d (mm)
4.5 kg
Back-box: Painted steel
Front cover: fire-retardant ABS plastic.
IP54
100-240 V ac 50-60 Hz 1.3 A or
20-30 V dc, 60 W max.
1.2 Ah batteries fitted internally
-10ºC to + 50ºC (14 to 122ºF).
0 to 95% RH non-condensing
One 2 or 3 wire 4-20 mA gas detector (sink or source). Adaptor for mV bridge type detectors available.
Maximum detector current 500 mA.
One loop of up to 20 conventional smoke/heat detectors or manual call points, or one flame detector (4-20 mA or digital contact signal).
For use with one Crowcon ESU sampling device.
Via normally open contact.
Via normally open contact.
Low alarm, High alarm, Fault.
DPCO contacts rated at
250 V ac, 30 V dc 8 A (non-inductive load), 5 A (inductive load).
24 V dc 650 mA maximum drive (typically 2 devices max.)
4-20 mA (current source, max. loop resistance 700
Ω
) or
1-5 V dc (min. load 50 K
Ω
).
RS-485 Modbus RTU
9600 Baud
8 Data bits
No parity
2 Stop bits
Optional 3-way connector for PC configuration and event log upload
Time-stamped log of up to 300 alarm, fault or system intervention activities.
LCD back-lit display shows gas level (in ppb, ppm, % volume or % LEL units), and scrolling alphanumeric status indication.
LEDs for Alarm, Fault, Power and
Warning status indication.
Integral 85 dB sounder.
EN 50270 (EMC), EN 61010-1 (Low voltage directive)
CSA standards C22.2 NO.152 and
C22.2 No. 142
Gasmaster 4
288h x 278w x 110d (mm)
4.5 kg
Back-box: Painted steel
Front cover: fire-retardant ABS plastic.
IP54
100-240 V ac 50-60 Hz 1.3 A or
20-30 V dc, 60 W max.
1.2 Ah batteries fitted internally
-10ºC to + 50ºC (14 to 122ºF).
0 to 95% RH non-condensing
One to four 2 or 3 wire 4-20 mA gas detectors (sink or source). Adaptor for mV bridge type detectors available.
Maximum detector current 500 mA.
One to four loops of up to 20 conventional smoke/heat detectors or manual call points, or one to four flame detectors (4-20 mA or digital contact signal).
For use with one Crowcon ESU sampling device.
Via normally open contact.
Via normally open contact.
Low alarm and High alarm per channel plus Common Low, High and
Fault.
DPCO contacts rated at 250 V ac, 30 V dc 8 A (non-inductive load), 5 A (inductive load).
24 V dc 650 mA maximum drive (typically 2 devices max.)
4-20 mA for each channel (current source, max. loop resistance 700
Ω
) or 1-5 V dc (min. load 50 K
Ω
).
RS-485 Modbus TRU
9600 Baud
8 Data bits
No parity
2 Stop bits
Optional 3-way connector for PC configuration and event log upload
Time-stamped log of up to 300 alarm, fault or system intervention activities.
LCD back-lit display shows gas level
(in ppb, ppm, % volume or % LEL units) for all channels, and scrolling alphanumeric status indication. LEDs for Alarm, Fault, Power and Warning status indication
Integral 85 dB sounder.
EN 50270 (EMC), EN 61010-1 (Low voltage directive)
CSA standards C22.2 NO.152 and
C22.2 No. 142
1Event log access requires Gasmaster PC software and communication port. Event log data is held in non-volatile memory, data will be lost in the event of a complete sys tem power failure.
GasMaster
GasMaster Appendx B: Spare parts and Accessores
Appendix B: Spare Parts and Accessories
Part No.
E01875
E07534
M05897
M07624
S012016
S011713/2
S011714/2
E07109
S011746
S011723
M04683
M05891
M05906
M05892
M05893
C01929
E07635
C01919
C01920
C01921
C01922
E07636
S011750
S011555
M01861/2
Description
12V 1.2Ah battery
Battery fuse assembly
Service card
Installation, Operation and maintenance manual
Display PCB
Gasmaster 4 terminal PCB
Gasmaster 1 terminal PCB
Insulated Jumper links
Power supply assembly
Sounder assembly
Sounder seal
Gasmaster 4 display label
Gasmaster 1 display label
Domed Crowcon label
Domed Gasmaster label
Communications Kit
Communications port
Accessory Enclosure
Accessory Enclosure
Accessory Enclosure
Accessory Enclosure
Accessory enclosure connector
Front cover assembly for Gasmaster 1
Front cover assembly for Gasmaster 4
Comment
2 required
Assembly with fuse, fuse holder and loom
Replacement service cards, minimum quantity 10
For all Gasmaster models
No links supplied, use links from old PCB
No links supplied, use links from old PCB
Spare links for PCB's, minimum order quantity 10
Complete with wiring looms
Complete with wiring loom
For front cover
For front cover
For front cover of all models
For front cover of Gasmaster 1 and 4
Includes Gasmaster PC software, connection lead and
RS485/232 converter.
3-pin connector for fitment to Gasmaster to enable interface with the Communications Kit. Comes complete with wiring loom for connection to the RS-485 terminals.
For connecting
one
mV bridge type flammable gas detector to Gasmaster 1 or 4. Comes with the connector for Gasmaster.
For connecting
two
mV bridge type flammable gas detectors to Gasmaster 4. Comes with the connector for
Gasmaster.
For connecting
three
mV bridge type flammable gas detectors to Gasmaster 4. Comes with the connector for
Gasmaster.
For connecting
four
mV bridge type flammable gas detectors to Gasmaster 4. Comes with the connector for
Gasmaster.
Connector for fitment to Gasmaster to enable an
Accessory Enclosure to be connected. Comes complete with wiring loom.
Complete with labels, sounder and seals
Complete with labels, sounder and seals
Flush mounting brackets For mounting Gasmaster into a panel.
Appendx C: Dsplay characters GasMaster
Appendix C: Display characters
Message display area characters
When editing strings of text for passwords, detector location or system identity, the following characters are available:
Group1: <space> !
Group2: # $ % &
Group3: * + , - . /
Group4: 0 1 2 3 4 5 6 7 8 9
Group5: : ;
Group6: ? @
Group7: A B C D E F G H I J K L M N
O P Q R S T U V W X Y Z
Group8: _
Group9: a b c d e f g h i j k l m n o p q r s t u v w z y z
Use the Up and Down buttons as described in section 3.7 to select the required characters.
For some string types the available characters may be restricted, only the applicable characters will be shown. For example the detector name (e.g. gas type) is restricted to groups 4 and 7 (numerals and upper case) only: single clicking or holding the Up button will advance forward through the available groups of characters:
A B C D ... X Y Z 0 1 2 ... 7 8 9 A B C
... etc single clicking or holding the Down button will advance backwards through the available groups of characters:
Z Y X W ... C B A 9 8 7 ... 2 1 0 Z Y X ... etc double clicking the Up button will jump forwards to the end of the current group then on to the start of the following one etc: Z 0 9 A Z ...
double clicking the Down button will jump backwards to the start of the current group then on to the end of the following one etc: A 9 0 Z A ...
6
7
8
9
4
5
2
3
0
1
Channel display characters
NB:
The following characters represent those which can be shown on the channel display area to represent detector types.
The following characters cannot be closely represented: K, M, V, W, X
Q
R
S = 5
T
M
N
K
L
O
P
I
J
E
F
G = 9
H
C
D
A
B
W
X
U
V
Y
Z = 2 dash underscore
?
blank
b5 b6 b0
.dp
b7 b1 b3 b2 b4
Thank you for reading this data sheet.
For pricing or for further information, please contact us at our UK Office, using the details below.
UK Office
Keison Products,
P.O. Box 2124, Chelmsford, Essex, CM1 3UP, England.
Tel: +44 (0)
330 088 0560
Fax: +44 (0)1245
808399
Email: [email protected]
Please note - Product designs and specifications are subject to change without notice. The user is responsible for determining the suitability of this product.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 5 I. Introduction
- 5 1.1 About Gasmaster
- 5 1.2 About this manual
- 6 applications
- 7 II. Installation
- 7 Please read this first
- 8 2.1 Before installation
- 8 2.2 General
- 9 2.3 Mounting
- 9 2.4 Cabling requirements
- 10 2.5 Installing gas and fire detectors
- 10 2.6 Installing output devices
- 10 2.7 Connecting mains power
- 11 2.8 Connecting input devices
- 15 2.9 Connecting output devices
- 17 2.10 Applying power
- 17 2.11 Battery back-up times
- 18 2.12 Commissioning
- 20 III. Operation
- 20 3.1 Gasmaster Operator Panel
- 22 3.2 Gasmaster start up sequence
- 22 3.3 How to adjust display contrast
- 22 number and system identity
- 23 3.5 Using the menu system
- 23 3.6 Inhibiting channels
- 24 Supervisor Mode
- 25 3.8 In the event of an alarm
- 25 3.9 In the event of a fault
- 25 3.10 System Configuration
- 27 Menu system overview
- 38 IV. Maintenance
- 38 4.1 Functional Testing
- 38 4.2 System Inhibit
- 39 4.3 Detector Calibration
- 39 4.4 Changing Batteries
- 39 4.5 Module Replacement
- 39 4.6 Event logging
- 39 4.7 Service card
- 39 4.8 Cleaning
- 40 Appendix A: Specifications
- 42 Appendix C: Display characters
- 43 Warranty Statement
- 44 Regional addresses