Below you will find brief information for Programmable Controller SYSMAC CPM2A. The CPM2A Programmable Controllers feature a variety of functions in a compact unit, including synchronized pulse control, interrupt inputs, pulse outputs, analog settings, and a clock function. The CPM2A CPU Unit can handle a broad range of machine control applications, so it is ideal for use as a built-in control unit in equipment.
Advertisement
Advertisement
Cat.No. W352–E1–3
SYSMAC
CPM2A
Programmable Controllers
OPERATION MANUAL
CPM2A Programmable Controllers
Operation Manual
Revised December 1999
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to property.
!
DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
!
WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
!
Caution Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury, or property damage.
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means
“word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PC” means Programmable Controller and is not used as an abbreviation for anything else.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of information.
Note Indicates information of particular interest for efficient and convenient operation of the product.
1, 2, 3...
1.
Indicates lists of one sort or another, such as procedures, checklists, etc.
OMRON, 1999
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
v
TABLE OF CONTENTS
PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Application Precautions
6 EC Directives
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1 CPM2A Features and Functions
1-2 Basic System Configurations
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3 Structure and Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4 Functions Listed by Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-5 Comparison with the CPM1A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-6 Preparation for Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 2
Unit Specifications and Components . . . . . . . . . . . . . . . .
2-1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 Unit Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 3
Installation and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1 Design Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Selecting an Installation Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3 Installing the CPM2A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4 Wiring and Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 4
Using Programming Devices . . . . . . . . . . . . . . . . . . . . . . .
4-1 SYSMAC-CPT Support Software
4-2 SYSMAC Support Software (SSS)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3 Using a Programming Console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4 Programming Console Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5 Programming Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 5
Test Runs and Error Processing . . . . . . . . . . . . . . . . . . . .
5-1 Initial System Checks and Test Run Procedure
5-2 Self-diagnostic Functions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3 Programming Console Operation Errors
5-4 Programming Errors
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-5 Troubleshooting Flowcharts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-6 Maintenance Inspections
5-7 Battery Replacement
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 6
Expansion Memory Unit . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2 Specifications and Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3 Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
131
132
133
136
136
137
145
146
149
150
151
152
43
44
44
46
49 xi xii xii xii xiii xiii xv
27
28
35
83
84
92
95
101
124
1
10
16
2
8
18
24 vii
viii
TABLE OF CONTENTS
Appendices
A Standard Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
159
163
171
175
About this Manual:
The CPM2A is a compact, high-speed Programmable Controller (PC) designed for control operations in systems requiring from 10 to 120 I/O points per PC. There are two manuals describing the setup and operation of the CPM2A: The CPM2A Operation Manual (this manual) and the CPM1/CPM1A/CPM2A/
CPM2C/SRM1(-V2) Programming Manual (W353). (The CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2)
Programming Manual is referred to as simply the Programming Manual in this manual.)
This manual describes the system configuration and installation of the CPM2A and provides a basic explanation of operating procedures for the Programming Consoles. It also introduces the capabilities of the SYSMAC Support Software (SSS) and SYSMAC-CPT Support Software. Read this manual first to acquaint yourself with the CPM2A.
The Programming Manual (W353) provides detailed descriptions of the CPM2A’s programming functions. The SYSMAC Support Software Operation Manuals: Basics and C-series PCs (W247 and W248) provide descriptions of SSS operations for the CPM2A and other SYSMAC C-series PCs. The SYSMAC-
CPT Support Software Quick Start Guide (W332) and User Manual (W333) provide descriptions of ladder diagram operations in the Windows environment. The WS02-CXPC1-E CX-Programmer User Manual
(W361) and the CX-Server User Manual (W362) provide details of operations for the WS02-CXPC1-E
CX-Programmer.
Please read this manual carefully and be sure you understand the information provided before attempting to install and operate the CPM2A.
Section 1 gives a brief overview of the steps involved in developing of a CPM2A System, describes the possible system configurations, and describes the CPM2A’s special features and functions.
Section 2 provides the technical specifications of the Units that go together to create a CPM2A PC and describes the main components of the Units.
Section 3 describes how to install and wire a CPM2A PC.
Section 4 describes SYSMAC and SYSMAC-CPT Support Software capabilities, how to connect the Programming Console, and how to perform the various programming operations.
Section 5 describes how to perform a test run and how to diagnose and correct the hardware and software errors that can occur during PC operation.
Section 6 describes how to use the CPM1-EMU01-V1 Expansion Memory Unit. Follow the handling precautions and procedures to properly use the Unit.
Appendix A provides tables of CPM2A Units and related products.
Appendix B provides the dimensions of CPM2A Units.
!
WARNING Failure to read and understand the information provided in this manual may result in personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given.
ix
PRECAUTIONS
This section provides general precautions for using the Programmable Controller (PC) and related devices.
The information contained in this section is important for the safe and reliable application of the Programmable Controller. You must read this section and understand the information contained before attempting to set up or operate a
PC system.
1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii xii xii xiii xiii xv xi
Safety Precautions
1
2
3
Intended Audience
This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent).
•
Personnel in charge of installing FA systems.
•
Personnel in charge of designing FA systems.
•
Personnel in charge of managing FA systems and facilities.
General Precautions
The user must operate the product according to the performance specifications described in the operation manuals.
Before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems, machines, and equipment that may have a serious influence on lives and property if used improperly, consult your OMRON representative.
Make sure that the ratings and performance characteristics of the product are sufficient for the systems, machines, and equipment, and be sure to provide the systems, machines, and equipment with double safety mechanisms.
This manual provides information for programming and operating the Unit. Be sure to read this manual before attempting to use the Unit and keep this manual close at hand for reference during operation.
!
WARNING It is extremely important that a PC and all PC Units be used for the specified purpose and under the specified conditions, especially in applications that can directly or indirectly affect human life. You must consult with your OMRON representative before applying a PC System to the above-mentioned applications.
3 Safety Precautions
!
WARNING Do not attempt to take any Unit apart while the power is being supplied. Doing so may result in electric shock.
!
WARNING Do not touch any of the terminals or terminal blocks while the power is being supplied. Doing so may result in electric shock.
!
WARNING Do not attempt to disassemble, repair, or modify any Units. Any attempt to do so may result in malfunction, fire, or electric shock.
!
WARNING Provide safety measures in external circuits (i.e., not in the Programmable
Controller), including the following items, in order to ensure safety in the system if an abnormality occurs due to malfunction of the PC or another external factor affecting the PC operation. Not doing so may result in serious accidents.
•
Emergency stop circuits, interlock circuits, limit circuits, and similar safety measures must be provided in external control circuits.
•
The PC will turn OFF all outputs when its self-diagnosis function detects any error or when a severe failure alarm (FALS) instruction is executed. As a countermeasure for such errors, external safety measures must be provided to ensure safety in the system.
xii
Application Precautions
4
5
5
•
The PC outputs may remain ON or OFF due to deposition or burning of the output relays or destruction of the output transistors. As a countermeasure for such problems, external safety measures must be provided to ensure safety in the system.
•
When the 24-VDC output (service power supply to the PC) is overloaded or short-circuited, the voltage may drop and result in the outputs being turned
OFF. As a countermeasure for such problems, external safety measures must be provided to ensure safety in the system.
!
WARNING When transferring programs to other nodes, or when making changes to I/O memory, confirm the safety of the destination node before transfer. Not doing so may result in injury.
!
Caution Execute online edit only after confirming that no adverse effects will be caused by extending the cycle time. Otherwise, the input signals may not be readable.
!
Caution Tighten the screws on the terminal block of the AC Power Supply Unit to the torque specified in the operation manual. The loose screws may result in burning or malfunction.
Operating Environment Precautions
!
Caution Do not operate the control system in the following places:
•
Locations subject to direct sunlight.
•
Locations subject to temperatures or humidity outside the range specified in the specifications.
•
Locations subject to condensation as the result of severe changes in temperature.
•
Locations subject to corrosive or flammable gases.
•
Locations subject to dust (especially iron dust) or salts.
•
Locations subject to exposure to water, oil, or chemicals.
•
Locations subject to shock or vibration.
!
Caution Take appropriate and sufficient countermeasures when installing systems in the following locations:
•
Locations subject to static electricity or other forms of noise.
•
Locations subject to strong electromagnetic fields.
•
Locations subject to possible exposure to radioactivity.
•
Locations close to power supplies.
!
Caution The operating environment of the PC System can have a large effect on the longevity and reliability of the system. Improper operating environments can lead to malfunction, failure, and other unforeseeable problems with the PC System. Be sure that the operating environment is within the specified conditions at installation and remains within the specified conditions during the life of the system.
Application Precautions
Observe the following precautions when using the PC System.
!
WARNING Always heed these precautions. Failure to abide by the following precautions could lead to serious or possibly fatal injury.
•
Always connect to a ground such that the grounding resistance does not exceed 100
Ω
when installing the Units. Not connecting to the correct ground may result in electric shock.
xiii
Application Precautions 5
•
Always turn OFF the power supply to the PC before attempting any of the following. Not turning OFF the power supply may result in malfunction or electric shock.
•
Mounting or dismounting I/O Units, CPU Units, Memory Cassettes, or any other Units.
•
Assembling the Units.
•
Setting DIP switches or rotary switches.
•
Connecting or wiring the cables.
•
Connecting or disconnecting the connectors.
!
Caution Failure to abide by the following precautions could lead to faulty operation of the
PC or the system, or could damage the PC or PC Units. Always heed these precautions.
•
Fail-safe measures must be taken by the customer to ensure safety in the event of incorrect, missing, or abnormal signals caused by broken signal lines, momentary power interruptions, or other causes.
•
Construct a control circuit so that power supply for the I/O circuits does not come ON before power supply for the Unit. If power supply for the I/O circuits comes ON before power supply for the Unit, normal operation may be temporarily interrupted.
•
If the operating mode is changed from RUN or MONITOR mode to PROGRAM mode, with the IOM Hold Bit ON, the output will hold the most recent status. In such a case, ensure that the external load does not exceed specifications. (If operation is stopped because of an operation error (including FALS instructions), the values in the internal memory of the CPU Unit will be saved, but the outputs will all turn OFF.)
•
Always use the power supply voltage specified in the operation manuals. An incorrect voltage may result in malfunction or burning.
•
Take appropriate measures to ensure that the specified power with the rated voltage and frequency is supplied. Be particularly careful in places where the power supply is unstable. An incorrect power supply may result in malfunction.
•
Install external breakers and take other safety measures against short-circuiting in external wiring. Insufficient safety measures against short-circuiting may result in burning.
•
Do not apply voltages to the input terminals in excess of the rated input voltage.
Excess voltages may result in burning.
•
Do not apply voltages or connect loads to the output terminals in excess of the maximum switching capacity. Excess voltage or loads may result in burning.
•
Disconnect the functional ground terminal when performing withstand voltage tests. Not disconnecting the functional ground terminal may result in burning.
•
Install the Unit properly as specified in the operation manual. Improper installation of the Unit may result in malfunction.
•
Be sure that all the mounting screws, terminal screws, and cable connector screws are tightened to the torque specified in the relevant manuals. Incorrect tightening torque may result in malfunction.
•
Be sure to leave the labels attached at the time of shipment on the CPM1 or
CPM2A when wiring in order to prevent wiring cuttings from entering the Unit.
•
Remove the label after the completion of wiring to ensure proper heat dissipation. Leaving the label attached may result in malfunction.
•
Be sure to perform wiring in accordance with the relevant operation manual.
Incorrect wiring may result in burning.
•
Use crimp terminals for wiring. Do not connect bare stranded wires directly to terminals. Connection of bare stranded wires may result in burning.
xiv
EC Directives 6
•
Double-check all the wiring before turning ON the power supply. Incorrect wiring may result in burning.
•
Be sure that the terminal blocks, Memory Units, expansion cables, and other items with locking devices are properly locked into place. Improper locking may result in malfunction.
•
Be sure that terminal blocks and connectors are connected in the specified direction with the correct polarity. Not doing so may result in malfunction.
•
Check the user program for proper execution before actually running it on the
Unit. Not checking the program may result in an unexpected operation.
•
Confirm that no adverse effect will occur in the system before attempting any of the following. Not doing so may result in an unexpected operation.
•
Changing the operating mode of the PC.
•
Force-setting/force-resetting any bit in memory.
•
Changing the present value of any word or any set value in memory.
•
Resume operation only after transferring to the new CPU Unit the contents of the DM and HR Areas required for resuming operation. Not doing so may result in an unexpected operation.
•
Do not pull on the cables or bend the cables beyond their natural limit. Doing either of these may break the cables.
•
Do not place objects on top of the cables. Doing so may break the cables.
•
Under no circumstances should batteries be short-circuited between positive
(+) and negative (–) terminals, charged, disassembled, heated, or thrown into fire.
•
When replacing parts, be sure to confirm that the rating of a new part is correct.
Not doing so may result in malfunction or burning.
•
Before touching the Unit, be sure to first touch a grounded metallic object in order to discharge any static build-up. Not doing so may result in malfunction or damage.
•
Do not touch the expansion I/O connecting cable while the power is being supplied in order to prevent any malfunction due to static electricity.
•
When using a thermocouple-input type Temperature Sensor Unit, observe the following precautions:
•
Do not remove the cold junction compensator attached at the time of delivery. If the cold junction compensator is removed the Unit will not be able to measure temperatures correctly.
•
Each of the input circuits is calibrated with the cold junction compensator attached to the Unit. If the Unit is used with the cold junction compensator from other Units, the Unit will not be able to measure temperatures correctly.
•
Do not touch the cold junction compensator. Doing so may result in incorrect temperature measurement.
6 EC Directives
6-1 Applicable Directives
•
EMC Directives
•
Low Voltage Directive
6-2 Concepts
EMC Directives
OMRON devices that comply with EC Directives also conform to the related xv
EC Directives 6
EMC standards so that they can be more easily built into other devices or the overall machine. The actual products have been checked for conformity to EMC standards (see the following note). Whether the products conform to the standards in the system used by the customer, however, must be checked by the customer.
EMC-related performance of the OMRON devices that comply with EC Directives will vary depending on the configuration, wiring, and other conditions of the equipment or control panel on which the OMRON devices are installed. The customer must, therefore, perform the final check to confirm that devices and the overall machine conform to EMC standards.
Note Applicable EMC (Electromagnetic Compatibility) standards are as follows:
EMS (Electromagnetic Susceptibility): EN61131-2
EMI (Electromagnetic Interference): EN50081-2
(Radiated emission: 10-m regulations)
Low Voltage Directive
Always ensure that devices operating at voltages of 50 to 1,000 VAC and 75 to
1,500 VDC meet the required safety standards for the PC (EN61131-2).
6-3 Conformance to EC Directives
The CPM2A PCs comply with EC Directives. To ensure that the machine or device in which the CPM2A PC is used complies with EC directives, the PC must be installed as follows:
1, 2, 3...
1. The CPM2A PC must be installed within a control panel.
2. Reinforced insulation or double insulation must be used for the DC power supplies used for the communications and I/O power supplies.
3. CPM2A PCs complying with EC Directives also conform to the Common
Emission Standard (EN50081-2). Radiated emission characteristics (10-m regulations) may vary depending on the configuration of the control panel used, other devices connected to the control panel, wiring, and other conditions. You must therefore confirm that the overall machine or equipment complies with EC Directives.
6-4 Relay Output Noise Reduction Methods
The CPM2A PCs conform to the Common Emission Standards (EN50081-2) of the EMC Directives. However, the noise generated when the PC is switched ON or OFF using the relay output may not satisfy these standards. In such a case, a noise filter must be connected to the load side or other appropriate countermeasures must be provided external to the PC.
Countermeasures taken to satisfy the standards vary depending on the devices on the load side, wiring, configuration of machines, etc. Following are examples of countermeasures for reducing the generated noise.
Countermeasures
(Refer to EN50081-2 for more details.)
Countermeasures are not required if the frequency of load switching for the whole system with the PC included is less than 5 times per minute.
Countermeasures are required if the frequency of load switching for the whole system with the PC included is 5 times or more per minute.
xvi
EC Directives 6
Countermeasure Examples
When switching an inductive load, connect a surge protector, diodes, etc., in parallel with the load or contact as shown below.
Circuit
CR method
Power supply
Diode method
Power supply
Varistor method
Power supply
Current
AC DC
Characteristic
Yes Yes If the load is a relay or solenoid, there is a time lag between the moment the circuit is opened and the moment the load is reset.
If the supply voltage is 24 to 48 V, insert the surge protector in parallel with the load. If the supply voltage is
100 to 200 V, insert the surge protector between the contacts.
No Yes The diode connected in parallel with the load changes energy accumulated by the coil into a current, which then flows into the coil so that the current will be converted into Joule heat by the resistance of the inductive load.
This time lag, between the moment the circuit is opened and the moment the load is reset, caused by this method is longer than that caused by the CR method.
Yes Yes The varistor method prevents the imposition of high voltage between the contacts by using the constant voltage characteristic of the varistor. There is time lag between the moment the circuit is opened and the moment the load is reset.
If the supply voltage is 24 to 48 V, insert the varistor in parallel with the load. If the supply voltage is 100 to
200 V, insert the varistor between the contacts.
Required element
The capacitance of the capacitor must be 1 to 0.5
µ
F per contact current of
1 A and resistance of the resistor must be 0.5 to 1
Ω
per contact voltage of
1 V. These values, however, vary with the load and the characteristics of the relay. Decide these values from experiments, and take into consideration that the capacitance suppresses spark discharge when the contacts are separated and the resistance limits the current that flows into the load when the circuit is closed again.
The dielectric strength of the capacitor must be 200 to 300 V. If the circuit is an AC circuit, use a capacitor with no polarity.
The reversed dielectric strength value of the diode must be at least 10 times as large as the circuit voltage value.
The forward current of the diode must be the same as or larger than the load current.
The reversed dielectric strength value of the diode may be two to three times larger than the supply voltage if the surge protector is applied to electronic circuits with low circuit voltages.
--xvii
EC Directives 6
6-5 CPM1A-MAD01 Conformance to EMC Directives
Immunity testing conditions when using the current I/O of the CPM1A-MAD01 are as follows.
•
Total accuracy: +10%/-1%
•
Insert the following core in each line as shown below.
Recommended core: 2643-002402
Manufacturer: Fair Rite Products Corp.
xviii
SECTION 1
Introduction
This section describes the CPM2A’s special features and functions, shows the possible system configurations, and outlines the steps required before operation. Read this section first when using the CPM2A for the first time.
Refer to the CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2) Programming Manual (W353) for details on programming operation.
1-1 CPM2A Features and Functions
1-1-1 CPM2A Features
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1-2 Overview of CPM2A Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2 Basic System Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-1 Stand-alone CPU Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-2 CPU Unit, Expansion Units, and Expansion I/O Units . . . . . . . . . . . . . . . . . . . . .
1-3 Structure and Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3-1 CPU Unit Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3-2 Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3-3 Operating Mode at Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3-4 PC Operation at Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3-5 Cyclic Operation and Interrupts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4 Functions Listed by Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-5 Comparison with the CPM1A
1-6 Preparation for Operation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12
13
16
10
10
11
11
18
24
8
8
8
2
2
7
1
CPM2A Features and Functions Section 1-1
1-1 CPM2A Features and Functions
1-1-1 CPM2A Features
The CPM2A PCs incorporate a variety of features in a compact Unit, including synchronized pulse control, interrupt inputs, pulse outputs, analog settings, and a clock function. Also, the CPM2A CPU Unit is a stand-alone Unit that can handle a broad range of machine control applications, so it is ideal for use as a builtin control unit in equipment.
The full complement of communications functions provide communications with personal computers, other OMRON PCs, and OMRON Programmable Terminals. These communications capabilities allow the user to design a low-cost distributed production system.
The CPU Unit contains 20, 30, 40, or 60 I/O points and Expansion I/O Units can be added to provide a total I/O capacity of up to 120 I/O points. Analog I/O
Units, Temperature Sensor Units, and CompoBus/S
I/O Link Units can also be connected.
Peripheral Port
Programming Devices are compatible with other models of OMRON PCs. This port can also be used for Host Link or no-protocol communications.
Basic Functions
CPU Unit Variations
Expansion I/O Units
Analog I/O Units
Temperature Sensor
Units
RS-232C Port
This port can be used for a Host Link, no-protocol, 1:1 PC Link, or 1:1 NT Link communications.
The CPM2A PCs are one-piece PCs with 20, 30, 40, or 60 built-in I/O terminals.
There are 3 types of outputs available (relay outputs, sinking transistor outputs, and sourcing transistor outputs) and 2 types of power supplies available
(100/240 VAC or 24 VDC).
Up to 3 Expansion I/O Units can be connected to the CPU Unit to increase the
PC’s I/O capacity to a maximum of 120 I/O points. There are 3 types of Expansion I/O Units available: a 20-point I/O Unit, an 8-point Input Unit, and an 8-point
Output Unit. The maximum I/O capacity of 120 I/O points is achieved by connecting three 20-point I/O Units to a CPU Unit with 60 built-in I/O terminals.
Up to 3 Analog I/O Units can be connected to provide analog inputs and outputs.
Each Unit provides 2 analog inputs and 1 analog output, so a maximum of 6 analog inputs and 3 analog outputs can be achieved by connecting 3 Analog I/O
Units. (Time-proportional control can be performed by combining the analog I/O points with the PID(––) and PWM(––) instructions.)
•
The analog input range can be set to 0 to 10 VDC, 1 to 5 VDC, or 4 to 20 mA with a resolution of 1/256. (The open-circuit detection function can be used with the 1 to 5 VDC and 4 to 20 mA settings.)
•
The analog output range can be set to 0 to 10 VDC, –10 to 10 VDC, or 4 to
20 mA with a resolution of 1/256.
A Temperature Sensor Unit can be connected to provide up to 6 inputs for temperature input from sensors, such as thermocouples or platinum resistance
2
CPM2A Features and Functions
CompoBus/S I/O Link
Units
Section 1-1 thermometers. The PID(––) instruction can be used with a Temperature Sensor
Unit for easy temperature monitoring.
CompoBus/S I/O Link Units can be connected to make the CPM2A a Slave Device in a CompoBus/S Network. The I/O Link Unit has 8 input bits (internal) and
8 output bits (internal).
The CompoBus/S Network provides distributed CPU control based on a “PC + compact PC” configuration, which is an improvement on the earlier distributed
I/O control based on a “PC + remote I/O” configuration. The distributed CPU control makes equipment modular, so designs can be standardized, special needs can be addressed, and modules can be replaced easily in the event of a breakdown.
Master PC
CompoBus/S Master Unit
(or SRM1 CompoBus/S Master Control Unit)
CPM2A (Slave) CompoBus/S I/O Link Unit
CompoBus/S
Distributed CPU control
Share Programming
Devices
The same Programming Devices, such as Programming Consoles and Support
Software, can be used for the C200H, C200HS, C200HX/HG/HE, CQM1,
CPM1, CPM1A, CPM2C, and SRM1 (-V2) PCs, so existing ladder program resources can be used effectively.
Built-in Motor Control Capability
Synchronized Pulse
Control
(Transistor Outputs Only)
Synchronized pulse control provides an easy way to synchronize the operation of a peripheral piece of equipment with the main equipment. The output pulse frequency can be controlled as some multiple of the input pulse frequency, allowing the speed of a peripheral piece of equipment (such as a supply conveyor) to be synchronized with the speed of the main piece of equipment.
CPM2A
Encoder Motor driver Motor
High-speed Counters and
Interrupts
Easy Position Control with Pulse Outputs
(Transistor Outputs Only)
Pulses are output as a fixed multiple of the input frequency.
The CPM2A has a total of five high-speed counter inputs. The one high-speed counter input has a response frequency of 20 kHz/5 kHz and the four interrupt inputs (in counter mode) have a response frequency of 2 kHz.
The high-speed counter can be used in any one of the four input modes: differential phase mode (5 kHz), pulse plus direction input mode (20 kHz), up/down pulse mode (20 kHz), or increment mode (20 kHz). Interrupts can be triggered when the count matches a set value or falls within a specified range.
The interrupt inputs (counter mode) can be used for incrementing counters or decrementing counters (2 kHz) and trigger an interrupt (executing the interrupt program) when the count matches the target value.
CPM2A PCs with transistor outputs have two outputs that can produce 10 Hz to
10 kHz pulses (single-phase outputs).
When used as single-phase pulse outputs, there can be two outputs with a frequency range of 10 Hz to 10 kHz with a fixed duty ratio or 0.1 to 999.9 Hz with a variable duty ratio (0 to 100% duty ratio).
3
CPM2A Features and Functions Section 1-1
When used as pulse plus direction or up/down pulse outputs, there can be just one output with a frequency range of 10 Hz to 10 kHz.
High-speed Input Capabilities for Machine Control
High-speed Interrupt
Input Function
There are four inputs used for interrupt inputs (shared with quick-response inputs and interrupt inputs in counter mode) with a minimum input signal width of
50
µ s and response time of 0.3 ms. When an interrupt input goes ON, the main program is stopped and the interrupt program is executed.
Quick-response Input
Function
Stabilizing Input Filter
Function
There are four inputs used for quick-response inputs (shared with interrupt inputs and interrupt inputs in counter mode) that can reliably read input signals with a signal width as short as 50
µ s.
The input time constant for all inputs can be set to 1 ms, 2 ms, 3 ms, 5 ms,
10 ms, 20 ms, 40 ms, or 80 ms. The effects of chattering and external noise can be reduced by increasing the input time constant.
Other Functions
Interval Timer Interrupts
Analog Settings
Calendar/Clock
Long-term Timer
Analog PID Control
The interval timer can be set between 0.5 and 319,968 ms and can be set to generate just one interrupt (one-shot mode) or periodic interrupts (scheduled interrupt mode).
There are two controls on the CPU Unit that can be turned to change the analog settings (0 to 200 BCD) in IR 250 and IR 251. These controls can be used to easily change or fine-tune machine settings such as a conveyor belt’s pause time or feed rate.
The built-in clock (accuracy within 1 minute/month) can be read from the program to show the current year, month, day, day of the week, and time. The clock can be set from a Programming Device (such as a Programming Console) or the time can be adjusted by rounding up or down to the nearest minute.
TIML(––) is a long-term timer that accommodates set values up to 99,990 seconds (27 hours, 46 minutes, 30 seconds). When combined with the SECONDS
TO HOURS conversion instruction (HMS(––)), the long-term timer provides an easy way to control equipment scheduling.
The PID(––) instruction can be used with an Analog I/O Unit to control analog
I/O.
Complete Communications Capabilities
Host Link A Host Link connection can be made through the PC’s RS-232C port or Peripheral port. A personal computer or Programmable Terminal connected in Host
4
CPM2A Features and Functions Section 1-1
Link mode can be used for operations such as reading/writing data in the PC’s
I/O memory or reading/changing the PC’s operating mode.
1:1 Host Link Communications 1:N Host Link Communications
B500-AL004
Link Adapter
CPM1-CIF01
NT-AL001
CPM2A
(RS-232C port connection)
CPM2A (Peripheral port connection*)
*An RS-232C Adapter is needed to connect to the Peripheral port.
RS-232C/RS-422A Adapter
(Up to 32 PCs can be connected.)
No-protocol
Communications
Inputting data from a bar code reader
Bar code reader
The TXD(48) and RXD(47) instructions can be used in no-protocol mode to exchange data with standard serial devices. For example, data can be received from a bar code reader or transmitted to a serial printer. The serial devices can be connected to the RS-232C port or Peripheral port.
Outputting data to a serial printer
Serial printer
High-speed 1:1 NT Link
Communications
CPM2A
(RS-232C port connection*)
*An RS-232C Adapter is needed to connect to the Peripheral port.
CPM2A
(RS-232C port connection*)
In a 1:1 NT Link, an OMRON Programmable Terminal (PT) can be connected directly to the CPM2A. The PT must be connected to the RS-232C port; it cannot be connected to the Peripheral port.
OMRON PT
One-to-one PC Link
CPM2A
(RS-232C port connection)
A CPM2A can be linked directly to another CPM2A, CQM1, CPM1, CPM1A,
CPM2C, SRM1(-V2), or a C200HS or C200HX/HG/HE PC. The 1:1 PC Link al-
5
CPM2A Features and Functions Section 1-1 lows automatic data link connections. The PC must be connected through the
RS-232C port; it cannot be connected through the Peripheral port.
Expansion Memory Unit
CPM2A
(RS-232C port connection)
CPM2A
(RS-232C port connection)
The CPM1-EMU01-V1 Expansion Memory Unit is a program loader for smallsize or micro PLCs. Using the CPM1-EMU01-V1, simple on-site transfer of user programs and data memory is possible with PLCs.
Uploading
Downloading
SYSMAC
EEPROM
6
CPM2A Features and Functions Section 1-1
1-1-2 Overview of CPM2A Functions
Main function
Interrupts
High-speed counters
Quick-response input
Analog settings
Input time constant
Calendar/Clock
Expansion Unit functions
Variations/Details
Interrupt inputs
4 inputs, see note 1.
Response time: 0.3 ms
Interval timer interrupts
1 input
Set value: 0.5 to 319,968 ms
Precision: 0.1 ms
High-speed counter
1 input, see note 2.
Differential phase mode (5 kHz)
Pulse plus direction input mode (20 kHz)
Up/down input mode (20 kHz)
Increment mode (20 kHz)
Scheduled interrupts
One-shot interrupt
No interrupt
Count-check interrupt
(An interrupt can be generated when the count equals the set value or the count lies within a preset range.)
Pulse outputs
Interrupt inputs (counter mode)
4 inputs, see note 1.
No interrupt
Incrementing counter (2 kHz)
Decrementing counter (2 kHz)
Count-up interrupt
2 outputs:
Single-phase pulse output without acceleration/deceleration (See note 3.)
10 Hz to 10 kHz
2 outputs:
Variable duty ratio pulse output (See note 3.)
0.1 to 999.9 Hz, duty ratio 0 to 100%
1 output:
Pulse output with trapezoidal acceleration/deceleration (See note 3.)
Pulse plus direction output, up/down pulse output, 10 Hz to 10 kHz
Synchronized pulse control 1 point, see notes 2 and 3.
Input frequency range: 10 to 500 Hz, 20 Hz to 1 kHz, or 300 Hz to 20 kHz
Output frequency range: 10 Hz to 10 kHz
4 inputs, see note 1.
Minimum input signal width: 50
µ s
2 controls (setting ranges: 0 to 200 BCD)
Determines the input time constant for all inputs. (Settings: 1, 2, 3, 5, 10, 20, 40, or 80 ms)
Shows the current year, month, day of the week, day of the month, hour, minute, and second.
Analog I/O Unit functions (CPM1A-MAD01)
Two analog inputs: input range 0 to 10 V, 1 to 5 V, or 4 to 20 mA
One analog output: output range 0 to 10 V, –10 to 10 V, or 4 to 20 mA
Temperature Sensor Unit functions
Thermocouple input (CPM1A-TS001/002; 2/4 input points):
K: –200 ° to 1,300 ° C (–300 ° to 2,300 ° F)
0.0
°
to 500.0
°
C (0.0
°
to 900.0
°
F)
J: –100 ° to 850 ° C (–100 ° to 1,500 ° F)
0.0
°
to 400.0
°
C (0.0
°
to 750.0
°
F)
Platinum resistance thermometer input (CPM1A-TS101/102; 2/4 input points):
Pt100: –200.0
°
to 650.0
°
C (–300.0
°
to 1,200.0
°
F)
JPt100: –200.0
°
to 650.0
°
C (–300.0
°
to 1,200.0
°
F)
CompoBus/S Slave functions (CPM1A-SRT21)
Exchanges 8 input bits and 8 output bits of data with the Master Unit.
Note 1. These four inputs are shared by interrupt inputs, interrupt inputs in counter mode, and quick-response inputs, but each input can be used for only one purpose.
7
Basic System Configurations Section 1-2
2. This input is shared by the high-speed counter and synchronized pulse control functions.
3. This output is shared by the pulse output and synchronized pulse control functions. These functions can be used with transistor outputs only.
1-2 Basic System Configurations
1-2-1 Stand-alone CPU Unit
CPU Unit with 20/30 I/O Points CPU Unit with 40 I/O Points CPU Unit with 60 I/O Points
Number of I/O points
20 I/O points
(12 inputs and 8 outputs)
30 I/O points
(18 inputs and 12 outputs)
40 I/O points
(24 inputs and 16 outputs)
60 I/O points
(36 inputs and 24 outputs)
Power supply
100 to 240 VAC 24 VDC
24 VDC 24 VDC
24 VDC
24 VDC
100 to 240 VAC 24 VDC
24 VDC 24 VDC
24 VDC
24 VDC
100 to 240 VAC 24 VDC
24 VDC 24 VDC
24 VDC
24 VDC
100 to 240 VAC 24 VDC
24 VDC 24 VDC
24 VDC
24 VDC
Inputs Outputs
Relay
Relay
Sinking Transistor
Sourcing Transistor
Relay
Relay
Sinking Transistor
Sourcing Transistor
Relay
Relay
Sinking Transistor
Sourcing Transistor
Relay
Relay
Sinking Transistor
Sourcing Transistor
Model
CPM2A-20CDR-A
CPM2A-20CDR-D
CPM2A-20CDT-D
CPM2A-20CDT1-D
CPM2A-30CDR-A
CPM2A-30CDR-D
CPM2A-30CDT-D
CPM2A-30CDT1-D
CPM2A-40CDR-A
CPM2A-40CDR-D
CPM2A-40CDT-D
CPM2A-40CDT1-D
CPM2A-60CDR-A
CPM2A-60CDR-D
CPM2A-60CDT-D
CPM2A-60CDT1-D
1-2-2 CPU Unit, Expansion Units, and Expansion I/O Units
Up to 3 Expansion Units or Expansion I/O Units can be connected to the expansion connector with expansion I/O connecting cables. (Only one Expansion Unit or Expansion I/O Unit can be connected if an NT-AL001 Adapter is connected to the RS-232C port because the CPU Unit’s 5-VDC power supply is limited.)
There are four types of Units available: Expansion I/O Units, an Analog I/O Unit,
Temperature Sensor Units, and a CompoBus/S I/O Link Unit.
Expansion connector
Expansion I/O Unit or Expansion Unit
(Analog I/O Unit, Temperature Sensor
Unit, or CompoBus/S I/O Link Unit)
Expansion I/O connecting cable
8
Basic System Configurations Section 1-2
A PC with 120 I/O points (the maximum) can be assembled by connecting three
Expansion I/O Units to a CPU Unit with 60 I/O points.
CPM2A-60CDR-A
(36 inputs, 24 outputs)
×
1 Unit +
CPM1A-20EDR1
(12 inputs, 8 outputs)
×
3 Units = 72 inputs, 48 outputs
A PC with 6 analog inputs and 3 analog outputs (the maximum) can be assembled by connecting three Analog I/O Units. (Only one Analog I/O Unit can be connected if an NT-AL001 Adapter is connected to the CPU Unit’s RS-232C port.)
A PC with up to 6 temperature inputs for input from thermocouples or platinum resistance thermometers can be assembled by connecting Temperature Sensor
Units.
CompoBus/S I/O Link Units (Slave Units) can be connected to a CPU Unit. I/O data (8 inputs and 8 outputs) is transferred between the CPU Unit and the area allocated to the CompoBus/S Slave. (The I/O data exchanged with the Slave is internal data; there are no external input or output terminals.)
Note 1. Different types of Expansion I/O Units or Expansion Units can be connected at the same time. For example, an Expansion I/O Unit, an Analog I/O Unit, and a CompoBus/S I/O Link Unit can be connected to the CPU Unit.
2. When an NT-AL001 Adapter is connected to the RS-232C port, only one Expansion Unit or Expansion I/O Unit can be connected to the CPU Unit because of power supply limitations.
Expansion I/O Units
20-point I/O Unit 8-point Input Unit 8-point Output Unit
Unit
Expansion 20 I/O
I/O Units points
12 inputs
8 outputs
8 inputs
8 outputs
Max. number of Units
Inputs
3 Units max.
24 VDC
(See note.)
24 VDC
24 VDC
Outputs
Relays
Sinking transistors
Sourcing transistors
Model
CPM1A-20EDR1
CPM1A-20EDT
CPM1A-20EDT1
24 VDC
---
---
---
---
Relays
Sinking Transistors
Sourcing Transistors
CPM1A-8ED
CPM1A-8ER
CPM1A-8ET
CPM1A-8ET1
Note Only one Expansion I/O Unit can be connected if an NT-AL001 Adapter is connected to the CPU Unit’s RS-232C port.
Expansion Units
Analog I/O Unit Temperature Sensor Unit CompoBus/S I/O Link Unit
9
Structure and Operation Section 1-3
Unit
Analog I/O Unit
2 analog inputs (2 words)
1 analog output (1 word)
Temperature
Sensor Unit
Thermocouple inputs
Platinum resistance thermometer inputs
CompoBus/S I/O Link Unit
8 inputs and 8 outputs
Max. number of Units
3 Units max.
(See note.)
Inputs
2 analog inputs
Outputs
1 analog output
Model
CPM1A-MAD01
3 Units max.
(See note.)
1 Unit max.
(See note.)
3 Units max.
(See note.)
1 Unit max.
(See note.)
3 Units max.
(See note.)
2 inputs (K, J)
4 inputs (K, J)
2 inputs (Pt100, JPt100)
4 inputs (Pt100, JPt100)
8 bits
(Inputs from the Master.)
---
8 bits
(Outputs to the Master.)
CPM1A-TS001
CPM1A-TS002
CPM1A-TS101
CPM1A-TS102
CPM1A-SRT21
Note Only one Expansion Unit can be connected if an NT-AL001 Adapter is connected to the CPU Unit’s RS-232C port.
1-3 Structure and Operation
1-3-1 CPU Unit Structure
The following diagram shows the internal structure of the CPU Unit.
External input devices
I/O memory
Program
PC Setup
Settings
External output devices
I/O Memory
Program
Peripheral port
Settings
Communications processing
Settings
Communications switch
RS-232C port
The program reads and writes data in this memory area during execution. Part of the I/O memory contains the bits that reflect the status of the PC’s inputs and outputs. Parts of the I/O memory are cleared when the power is turned ON and other parts are retained.
Note Refer to Section 3 Memory Areas in the Programming Manual (W353) for more details on I/O memory.
This is the program written by the user. The CPM2A executes the program cyclically. (Refer to 1-3-5 Cyclic Operation and Interrupts for details.)
The program can be divided broadly into two parts: the “main program” that is executed cyclically and the “interrupt programs” that are executed only when the corresponding interrupt is generated.
10
Structure and Operation Section 1-3
PC Setup The PC Setup contains various startup and operating parameters. The PC Setup parameters can be changed from a Programming Device only; they cannot be changed from the program.
Some parameters are accessed only when PC’s power supply is turned on and others are accessed regularly while the power is on. It will be necessary to turn the power off and then on again to enable a new setting if the parameter is accessed only when the power is turned on.
Note Refer to Section 1 PC Setup in the Programming Manual (W353) for more details.
Communications Switch The Communications Switch determines whether the peripheral port and
RS-232C port operate with the standard communications settings or the communications settings in the PC Setup.
1-3-2 Operating Modes
CPM2A CPU Units have 3 operating modes: PROGRAM, MONITOR, and RUN.
PROGRAM Mode
MONITOR Mode
RUN Mode
The program cannot be executed in PROGRAM mode. This mode is used to perform the following operations in preparation for program execution
•
Changing initial/operating parameters such as those in the PC Setup
•
Writing, transferring, or checking the program
•
Checking wiring by force-setting and force-resetting I/O bits
The program is executed in MONITOR mode and the following operations can be performed from a Programming Device. In general, MONITOR mode is used to debug the program, test operation, and make adjustments.
•
Online editing
•
Monitoring I/O memory during operation
•
Force-setting/force-resetting I/O bits, changing set values, and changing present values during operation
The program is executed at normal speed in RUN mode. Operations such as online editing, force-setting/force-resetting I/O bits, and changing set values/ present values cannot be performed in RUN mode, but the status of I/O bits can be monitored.
1-3-3 Operating Mode at Startup
The operating mode of the CPM2A when the power is turned on depends upon the PC Setup settings and the Programming Console’s mode switch setting if a
Programming Console is connected.
PC Setup setting
Word Bits Setting
DM6600 08 to 15 00
00 to 07
01
02
00
01
02
Programming Console connected
Programming Console not connected
Startup mode determined by the mode switch setting.
Startup mode is RUN mode. (See note.)
Startup mode is the same as the operating mode before power was interrupted.
Startup mode is determined by bits 00 to 07.
PROGRAM mode
MONITOR mode
RUN mode
Note The default setting is 00. With this default setting, the startup operating mode is determined by the Programming Console’s mode switch setting if a Programming Console is connected to the Peripheral port. If a Programming Console is not connected, the PC will automatically enter RUN mode.
11
Structure and Operation Section 1-3
1-3-4 PC Operation at Startup
Time Required for
Initialization
The time required for startup initialization depends on several factors, such as the operating conditions (including power supply voltage, system configuration, and ambient temperature) and the program contents.
Power OFF Operation
Minimum Power Supply Voltage
The PC will stop and all outputs will be turned OFF if the power supply voltage falls below 85% of the rated value.
Momentary Power Interruption
A power interruption will not be detected and CPU Unit operation will continue if the power interruption lasts less than 10 ms for an AC power supply or 2 ms for a
DC power supply.
A power interruption may or may not be detected for power interruptions somewhat longer than 10 ms for an AC power supply or 2 ms for a DC power supply.
When a power interruption is detected, the CPU Unit will stop operating and all outputs will be turned OFF.
Automatic Reset
Operation will restart automatically when the power supply voltage is restored to more than 85% of the rated voltage.
Timing Chart of Power OFF Operation
The power interruption detection time is the time required for a power interruption to be detected after the power supply voltage drops below 85% of the rated value.
1, 2, 3...
1. Minimum power interruption detection time
Power interruptions that are shorter than 10 ms (AC power supply) or 2 ms
(DC power supply) will not be detected.
2. Undetermined additional time
Power interruptions only slightly longer than the minimum power interruption time may not be detected.
85% of rated voltage
Detection of power interruption
1. Minimum time 2. Additional time
Program execution Executing Stopped
CPU reset signal
CPU Unit operation will continue if voltage is restored in this region.
CPU Unit operation may continue if voltage is restored in this region.
Note If the power supply voltage fluctuates around 85% of the PC’s rated voltage, PC operation may stop and restart repeatedly. When repeated stopping and starting will cause problems with the controlled system, set up a protective circuit such as a circuit that shuts off the power supply to sensitive equipment until the power supply voltage returns to the rated value.
12
Structure and Operation Section 1-3
1-3-5 Cyclic Operation and Interrupts
Basic CPU Operation Initialization processing is performed when the power is turned on. If there are no initialization errors, the overseeing processes, program execution, I/O refreshing, and communications port servicing are performed repeatedly (cyclically).
Startup initialization
S
Check hardware.
S
Check memory.
S
Read data from flash memory (program, read-only DM data, and PC Setup settings).
Overseeing processes
S
Check for battery error.
S
Preset the watch (maximum) cycle time.
S
Check program memory.
S
Refresh bits for expansion functions.
Program execution
Cycle time calculation
S
Execute the program.
(Refer to the Programming Manual (W353) for details on cycle time and I/O response times.)
S
Wait for minimum cycle time if a minimum cycle time has been set in the PC Setup
(DM 6619).
S
Calculate cycle time.
I/O refreshing
S Read input data from input bits.
S Write output data to output bits.
RS-232C port servicing
Peripheral port servicing
S
Perform RS-232C port communications processing. (Can be changed in DM 6616.)
S Perform Peripheral port communications processing. (Can be changed in DM 6617.)
The cycle time can be read from a Programming Device.
AR 14 contains the maximum cycle time and AR 15 contains the present cycle time in multiples of 0.1 ms.
13
Structure and Operation Section 1-3
Program Execution in
Cyclic Operation
The cycle time will vary slightly depending on the processing being performed in each cycle, so the calculated cycle time will not always match the actual cycle time.
The following diagram shows the cyclic operation of the CPM2A when the program is being executed normally.
Normally, the results of program execution are transferred to I/O memory just after program execution (during I/O refreshing), but IORF(97) can be used to refresh a specified range of I/O words during program execution. The specified range of I/O words will be refreshed when IORF(97) is executed.
The cycle time is the sum of the time required for program execution, I/O refreshing, and communications port servicing.
A minimum cycle time (1 to 9,999 ms) can be set in the PC Setup (DM 6619).
When a minimum cycle time has been set, CPU operation is paused after program execution until the minimum cycle time is reached. CPU operation will not be paused if the actual cycle time is longer than the minimum cycle time set in
DM 6619.
Note A fatal error will occur and PC operation will stop if a maximum cycle time has been set in the PC Setup (DM 6618) and the actual cycle time exceeds that setting.
The default settings for RS-232C port servicing and Peripheral port servicing are
5% of the cycle time, but these settings can be changed (between 1% and 99%) in the PC Setup. The RS-232C port’s setting is in DM 6616 and the Peripheral port’s setting is in DM 6617.
Refer to Section 7 PC Operations and Processing Time in the Programming
Manual (W353) for more details and precautions on the cycle time.
Overseeing processes
Main program
Cycle time
I/O refreshing
RS-232C port servicing
Peripheral port servicing
If a minimum cycle time has been set in DM 6619, CPU operation is paused until the minimum cycle time is reached.
The servicing time can be set in DM 6616.
The servicing time can be set in DM 6617.
14
Structure and Operation
Interrupt Program
Execution
Section 1-3
When an interrupt is generated during execution of the main program, main program execution is interrupted immediately and the interrupt program is executed. The following diagram shows the cyclic operation of the CPM2A when an interrupt program is executed.
Normally, the results of interrupt program execution are transferred to I/O memory just after program execution (during I/O refreshing), but IORF(97) can be used to refresh a specified range of I/O words during execution of the interrupt program. The specified range of I/O words will be refreshed when IORF(97) is executed.
The normal cycle time is extended by the time required for execution of the interrupt program.
Refer to Section 7 PC Operations and Processing Time in the Programming
Manual (W353) for more details and precautions on the cycle time.
Overseeing processes
Main program
Interrupt generated.
Interrupt program
Cycle time
I/O refreshing
RS-232C port servicing
Peripheral port servicing
!
Caution Although IORF(97) can be used in interrupt subroutines, you must be careful of the interval between IORF(97) executions. If IORF(97) is executed too frequently, a fatal system error may occur (FALS 9F), stopping operation. The interval between executions of IORF(97) should be at least 1.3 ms + total execution time of the interrupt subroutine.
Immediate Refreshing IORF(97) can be executed in the program to refresh a specified range of I/O words. The specified I/O words will be refreshed when IORF(97) is executed.
IORF(97) can be used to refresh I/O from the main program or the interrupt program.
15
Functions Listed by Usage Section 1-4
When IORF(97) is used, the cycle time is extended by the time required to refresh the specified I/O words.
Cycle time
Overseeing processes
Main program
IORF(97) executed.
Immediate refreshing
I/O refreshing
I/O refreshing
RS-232C port servicing
Peripheral port servicing
1-4 Functions Listed by Usage
Machine Control Functions
Usage Function
Receive high-speed count inputs
Max. count frequency of 2 kHz
(single-phase) length or position with an encoder).
Max. count frequency of 5 kHz (differential phase) or 20 kHz (single-phase)
Generate a pulse output based on a multiple of an input pulse to synchronize control of a peripheral process with the main process.
The multiple for the peripheral process (such as tool feed rate) can be changed during operation by calculating the multiple from another input value (such as an encoder) in the peripheral process.
This method can be used to change the process for different products or models without stopping the equipment.
Use interrupt input (counter mode) to read the present value without interrupts.
Use high-speed counter to read the present value without interrupts.
Pulse synchronization
Refer to
W353
16
Functions Listed by Usage Section 1-4
Usage Function
Multiply the input pulse frequency from a high-speed counter by a fixed multiple, convert that value to an analog value, and output as an analog output.
(For example, synchronizing the speed of a supply conveyor with the rotational position of the main piece of equipment (such as a label inserter) measured by an analog input.)
Reliably receive input pulses with an ON-time shorter than the cycle time (such as inputs from a photomicrosensor).
Interrupt functions Execute a special process very quickly when an input goes ON.
(For example, operating a cutter when an interrupt input is received from a Proximity
Switch or Photoelectric Switch.)
Count input ON pulses and execute a special process very quickly when the count reaches the preset value.
(For example, stopping the supply feed when a preset number of workpieces have passed through the system.)
Execute a special process at a preset count value.
(For example, cutting material very precisely at a given length.)
Execute a special process when the count is within a preset range.
(For example, sorting material very quickly when it is within a given length range.)
Execute a special process when a timer times out.
(For example, stopping a conveyor at very precise time (independent of the cycle time) after the workpiece is detected.)
Repeat a special process at regular intervals.
(For example, the speed of a sheet feeder can be monitored by measuring the input signal from an encoder at regular intervals and calculating the speed.)
Perform simple positioning by outputting pulses to a motor driver that accepts pulse-train inputs.
Use a variable duty-ratio output to perform time-allocated temperature control.
Easily set and fine-tune settings such as the low-speed feed rate when a conveyor is temporarily stopped.
Receive an analog input and output an analog output.
Pulse synchronization and analog output function
Quick-response input function
Interrupt input (interrupt input mode)
Interrupt input (counter mode)
High-speed counter interrupt generated when the count matches the set value.
High-speed counter interrupt generated when the count is within the set range.
Interval timer interrupt
(One-shot mode)
Interval timer interrupt
(Scheduled interrupt mode)
Pulse output function
Analog input + Variable duty-ratio output pulse function (PWM(––))
Analog controls
Receive temperature sensor input directly at the PC.
Reduce required wiring, space, and PC load by controlling equipment with a few low-capacity PCs dispersed near the equipment rather than a single, large, centralized PC.
(Create a remote I/O link with a CompoBus/S Master and CompoBus/S
Slaves.)
Analog I/O Unit
(Connect the Analog I/O Unit to the
CPU Unit.)
Temperature Sensor Unit
(Connect the Temperature Sensor
Unit to the CPU Unit.)
CompoBus/S I/O Link Unit
(Connect the CompoBus/S I/O Link
Unit to the CPU Unit.)
Refer to
W353
17
Comparison with the CPM1A Section 1-5
Basic Functions
Usage Function
Set a minimum (fixed) cycle time in the PC Setup.
Set a maximum (watch) cycle time in the PC Setup.
Refer to
W353 Set the cycle time to a fixed interval.
Stop PC operation when the cycle time exceeds a maximum setting.
Keep all outputs ON when PC operation stops.
Retain the contents of I/O memory when starting operation.
Retain the contents of I/O memory when the PC is turned on.
Turn ON the IOM Hold Bit (SR 25212).
Turn ON the IOM Hold Bit (SR 25212).
Eliminate effects from chattering and external noise.
Turn ON the IOM Hold Bit (SR 25212) and set the PC
Setup (DM 6601) so that the status of the IOM Hold Bit is maintained at startup.
Set a longer input time constant in the PC Setup.
Maintenance Functions
Usage Function Refer to
W353 Record data with time-stamp.
Establish user-defined errors for desired input conditions. (Fatal and non-fatal errors can be defined.)
Read the number of power interruptions.
Set the startup operating mode.
Clock/calendar function
FAL(06) defines non-fatal errors. (PC operation continues.)
FALS(07) defines fatal errors. (PC operation stops.)
The number of power interruptions is stored in AR 23.
Set the startup operating mode in the PC Setup
(DM 6600).
Communications Functions
Usage Function
Read/write I/O memory data and change the operating mode from a host computer.
Connect to a serial device such as a bar code reader or serial printer.
Make a high-speed connection with an OMRON
Programmable Terminal.
Make a PC-PC data link connection with another
CPM2A, or a CPM1, CPM1A, CPM2C, SRM1, CQM1,
C200HS, or C200HX/HG/HE PC.
Connect a Programming Console.
Host Link communications (Set the communications mode to Host Link in the PC Setup.)
No-protocol communications (Set the communications mode to no-protocol in the PC Setup.)
1:1 NT Link (Set the communications mode to 1:1 NT
Link in the PC Setup.)
1:1 PC Link (Set the communications mode to 1:1 PC
Link in the PC Setup.)
Connect a personal computer running SYSMAC
Support Software (SSS) or SYSMAC-CPT Support
Software.
Monitor equipment with a Programmable Terminal and program the PC with a Programming Device.
Connect the Programming Console to the Peripheral port. (The CPU Unit’s Communications Switch setting has no effect on this connection.)
The computer can be connected to the Peripheral port or RS-232C port.
(The Host Link settings in the PC Setup are used when the switch is OFF; the standard Host Link communications settings are used when the CPU
Unit’s Communications Switch is ON.)
The RS-232C port and Peripheral port can be used simultaneously.
Refer to
W353
Page
98
Page
89
W353
Page
98
1-5 Comparison with the CPM1A
Instruction set
Instruction execution times
Program capacity
Item
Basic instructions
Special instructions
Basic instructions
Special instructions
CPM2A CPM1A
14 Same as CPM2A.
105 instructions, 185 variations 79 instructions, 139 variations
LD: 0.64
µ s
MOV(21): 7.8
µ s
LD: 1.72
µ s
MOV(21): 16.3
µ s
4,096 words 2,048 words
18
Comparison with the CPM1A Section 1-5
Item
Maximum number Stand-alone CPU Unit of I/O points
CPU Unit with Expansion I/O
Units
Expansion Units and Expansion I/O
Units
I/O memory
Interval timer
Quick-response inputs
Maximum number of Units
Available models
Input bits
Output bits
Work bits
SR (Special Relay) area
TR (Temporary Relay) area
HR (Holding Relay) area
AR (Auxiliary Relay) area
LR (Link Relay) area
Timer/Counter area
DM (Data
Memory) area
Read/write area
Read-only area
PC Setup
Memory backup Program area, read-only DM area (including PC Setup)
Read/write DM area, HR area,
AR area, and counters
Interrupt inputs (interrupt input mode)
Interrupt inputs
(counter mode)
Counter mode
Counter upper limit
SR 244 to SR 247
Method(s) to read counter PV
Method to change counter PV
One-shot mode
Scheduled interrupt mode
Setting the quick-response function
INT(89) (Mask)
INT(89) (Read mask)
INT(89) (Clear)
Minimum pulse width
CPM2A
30, 40, or 60 points
90, 100, or 120 points max.
CPM1A
10, 20, 30, or 40 points
90 or 100 points max.
A maximum of 3 Units can be connected to any of the CPU
Units.
(If the CPM1A-TS002/102 is connected, the maximum is 2.)
Expansion I/O Units,
Analog I/O Unit, Temperature
Sensor Units, and
CompoBus/S I/O Link Unit
IR 00000 to IR 00915
IR 01000 to IR 01915
928 bits:
IR 02000 to IR 04915,
IR 20000 to IR 22715
448 bits:
SR 22800 to SR 25515
8 bits: TR0 to TR7
320 bits:
HR 0000 to HR 1915
384 bits:
AR 0000 to AR 2315
256 bits:
LR 0000 to LR 1515
256 bits:
TIM/CNT 0 to TIM/CNT 256
2,048 words
(DM 0000 to DM 2047)
456 words
(DM 6144 to DM 6599)
56 words
(DM 6600 to DM 6655)
Flash memory backup
A maximum of 3 Units can be connected to the 30-point and
40-point CPU Units.
Same as CPM2A.
Same as CPM2A.
Same as CPM2A.
512 bits:
IR 20000 to IR 23115
384 bits:
SR 23200 to SR 25515
Same as CPM2A.
Same as CPM2A.
256 bits:
AR 0000 to AR 1515
Same as CPM2A.
128 bits:
TIM/CNT 0 to TIM/CNT 127
1,024 words
(DM 0000 to DM 1023)
Same as CPM2A.
Same as CPM2A.
Same as CPM2A.
Internal battery backup
(5-year lifetime, replaceable)
4
Incrementing counter
Decrementing counter
2 kHz
Contains counter PV.
Read SR 244 to SR 247.
Execute PRV(62).
(Counter PV)
Execute INI(61).
Yes
Yes
PC Setup
Not supported (ignored)
Reads mask status.
Not supported (ignored)
50
µ s min.
Capacitor backup
(20-day backup at 25
°
C)
Same as CPM2A.
Decrementing counter
1 kHz
Contains counter PV–1.
Read SR 244 to SR 247.
(Counter PV – 1)
Not supported.
Yes
Yes
PC Setup and INT(89)
(Unmask interrupt input.)
Supported.
Reads result of mask setting.
Supported.
200
µ s min.
19
Comparison with the CPM1A Section 1-5
High-speed counter
Item
Count mode
Max. counter frequency
Counter PV range
Check when registering target value match table
Method used to reference the target value match interrupt table
Reading range-comparison results
Reading status
CPM2A
Differential-phase (up/down) mode
Pulse plus direction mode
Up/down pulse mode
Increment mode
5 kHz in differential-phase
(up/down) mode
20 kHz in pulse plus direction mode, up/down pulse mode, and increment mode
–8,388,608 to 8,388,607 in differential-phase (up/down) mode, pulse plus direction mode, and up/down pulse mode
0 to 16,777,215 in increment mode
Same direction, same SV not possible
Comparison of all values in the table, regardless of order of appearance in table
Check AR 1100 to AR 1107 or execute PRV(62).
Check AR 1108 (comparison in progress), check AR 1109
(high-speed counter PV overflow/underflow), or execute PRV(62).
CPM1A
Differential-phase (up/down) mode
Increment mode
2.5 kHz in differential-phase
(up/down) mode,
5 kHz in increment mode
–32,768 to 32,767 in differential-phase (up/down) mode
0 to 65,535 in increment mode
Same direction, same SV possible
Comparison in order of appearance in table
Check AR 1100 to AR 1107.
---
Not supported.
Not supported.
Pulse synchronization
Pulse output control
Supported.
Trapezoidal acceleration/ deceleration
PWM(––) output
Number of simultaneous pulse outputs
Maximum frequency
Minimum frequency
Supported with ACC(––). The initial frequency can be set.
Supported.
2 max.
10 kHz max.
10 Hz
Pulse output quantity
Direction control
Positioning to absolute positions Supported.
Bit status while pulses are being output
No effect
Reading PV
–16,777,215 to 16,777,215
Supported.
Resetting PV
Status outputs
Read SR 228 through SR 231 or execute PRV(62).
Supported.
Accelerating/decelerating
PV overflow/underflow
Pulse quantity set
Pulse output completed
Pulse output status
Analog controls
Clock function
Analog I/O
Words containing time info.
2
Internal
AR 17 to AR 21
Analog I/O Units can be connected.
Not supported.
1 max.
2 kHz max.
20 Hz
0 to 16,777,215
Not supported.
Not supported.
Turned ON/OFF by pulse output
Not supported.
Not supported.
Pulse output status
2
None
---
Same as CPM2A.
20
Comparison with the CPM1A
Temperature monitoring
Item
CompoBus/S communications
Communications switch
Battery
Communications
(in CPU Unit)
Battery
Battery replacement
Life expectancy/backup time
Battery error detection
Peripheral port
Input time constant
RS-232C port
Section 1-5
CPM2A
The CPU Unit can receive temperature sensor input from either thermocouples or platinum resistance thermometers.
A CompoBus/S I/O Link Unit can be connected to provide
CompoBus/S Slave functions.
This switch determines whether communications are governed by the standard settings or PC Setup settings.
Lithium
Possible
5-year lifetime at 25
°
C
Supported.
Programming Console
(auto-detect)
Peripheral bus (auto-detect)
Host Link (with Slave-initiated communications)
No-protocol
Host Link
No-protocol
1:1 PC LInk
1:1 NT Link
Can be set to 1, 2, 3, 5, 10, 20,
40, or 80 ms. (Default: 10 ms)
CPM1A
Same as CPM2A.
Same as CPM2A.
None
None (capacitor backup only)
---
20-day backup at 25
°
C
---
Programming Console
(auto-detect)
Peripheral bus (auto-detect)
Host Link
1:1 PC LInk
1:1 NT Link
None
Can be set to 1, 2, 4, 8, 16, 32,
64, or 128 ms. (Default: 8 ms)
21
Comparison with the CPM1A
Differences in Instruction Sets
Instructions added to the CPM2A
Mnemonic
TXD(48)
RXD(47)
SCL(66)
TRANSMIT
RECEIVE
SCALING
Name
SCL2(––) SIGNED BINARY TO BCD SCALING
SCL3(––) BCD TO SIGNED BINARY SCALING
SRCH(––) DATA SEARCH
MAX(––) FIND MAXIMUM
MIN(––) FIND MINIMUM
SUM(––)
FCS(––)
HEX(––)
AVG(––)
SUM CALCULATION
FCS CALCULATE
ASCII-TO-HEXADECIMAL
AVERAGE VALUE
PWM(––) PULSE WITH VARIABLE DUTY RATIO
PID(––) PID CONTROL
ZCP(––) AREA RANGE COMPARE
ZCPL(––) DOUBLE AREA RANGE COMPARE
NEG(––)
ACC(––)
2’S COMPLEMENT
ACCELERATION CONTROL
STUP(––) CHANGE RS-232C SETUP
SYNC(––) SYNCHRONIZED PULSE CONTROL
BINL(58) DOUBLE BCD TO DOUBLE BINARY
BCDL(59) DOUBLE BINARY TO DOUBLE BCD
TMHH(––) VERY HIGH-SPEED TIMER
TIML(––)
SEC(––)
HMS(––)
LONG TIMER
HOURS-TO-SECONDS
SECONDS-TO-HOURS
Section 1-5
Instructions with Changed Specifications
Mnemonic
INI(61)
PRV(62)
CTBL(63)
PULS(65)
INT(89)
Name
MODE CONTROL
HIGH-SPEED
COUNTER PV READ
COMPARISON TABLE
LOAD
SET PULSES
INTERRUPT CONTROL
CPM2A
Supports the interrupt input (counter mode) PV change operation.
Supports the pulse output PV change operation.
Supports the pulse synchronization control stop operation.
Supports the interrupt input (counter mode) PV read operation.
Supports the pulse output PV read operation.
The count is compared with all of the target values in the target value comparison table.
Supports absolute pulse specification, but the coordinate system must be set to absolute coordinates.
Supports a count-up interrupt for incrementing counters.
CPM1A
Does not support these operations.
Does not support these operations.
The count is compared with each target value in the order that they appear in the target value comparison table.
Does not support absolute pulse specification.
Does not support this interrupt function.
22
Comparison with the CPM1A Section 1-5
!
Caution Before using a CPM1A program containing one or more of the instructions in the table above, check the program to be sure that it will operate properly and edit the program if necessary. The CPM2A may not operate properly if a CPM1A program with these instructions is transferred and executed unchanged.
Added Function Code
Allocations
The following three instructions are allocated function codes that were not used in the CPM1A.
Instruction
RXD(47)
TXD(48)
SCL(66)
CPM2A
RECEIVE
TRANSMIT
SCALING
CPM1A
Not allocated. (NOP(00))
Differences in I/O Memory
SR Area Differences The following table shows differences in the SR area. (PV is the abbreviation for present value.)
Pulse output 0 PV
Function
Pulse output 1 PV
Pulse output 0 PV Reset Bit
Pulse output 1 PV Reset Bit
RS-232C Port Reset Bit
Battery Error Flag
Changing RS-232C Port Setup Flag
CPM2A
SR 228 to SR 229
SR 230 to SR 231
SR 25204
SR 25205
SR 25209
SR 25308
SR 25312
CPM1A
Not supported.
AR Area Differences
DM Area Differences
The following table shows differences in the AR area.
Function
Clock/calendar data
RS-232C Communications Error Code
RS-232C Error Flag
RS-232C Transmission Enabled Flag
RS-232C Reception Completed Flag
RS-232C Reception Overflow Flag
CPM2A
AR 17 to AR 21
AR 0800 to AR 0803
AR 0804
AR 0805
AR 0806
AR 0807
Peripheral Port Reception Completed Flag
Peripheral Port Reception Overflow Flag
RS-232C Reception Counter
High-speed Counter Comparison Flag
AR 0814
AR 0815
AR 09
AR 1108
High-speed Counter Overflow/Underflow Flag AR 1109
Pulse Output 0 Condition
Pulse Output 0 PV Overflow/Underflow Flag
Pulse Output 0 Pulse Quantity Set Flag
Pulse Output 0 Output Completed Flag
Pulse Output 1 PV Overflow/Underflow Flag
Pulse Output 1 Pulse Quantity Set Flag
Pulse Output 1 Output Completed Flag
Pulse Output 1 Output Status
Power OFF Counter
AR 1111
AR 1112
AR 1113
AR 1114
AR 1212
AR 1213
AR 1214
AR 1215
AR 23 (See note.)
CPM1A
Not supported.
AR 10
Note CPM1A programs that use AR 10 (the Power OFF Counter) cannot be used in the CPM2A without editing the program. In the CPM2A, the Power OFF Counter is in AR 23.
The following table shows differences in the DM area other than the PC Setup.
23
Preparation for Operation Section 1-6
Function
Error Log Area
CPM2A CPM1A
DM 2000 to DM 2021 DM 1000 to DM 1021
Note CPM1A programs that use the Error Log Area cannot be used in the CPM2A without editing the program to change the location of the Error Log Area.
The following table shows differences in the PC Setup.
Function
RS-232C Port Servicing Time Setting
RS-232C Port Servicing Time Enable
Pulse Output 0 Coordinate System
Pulse Output 1 Coordinate System
RS-232C Communications Settings Selector
CPM2A CPM1A
DM 6616 bits 00 to 07 Not
DM 6616 bits 08 to 15 supported
DM 6629 bits 00 to 03
DM 6629 bits 04 to 07
DM 6645 bits 00 to 03
RS-232C Port CTS Control Settings
RS-232C Port Link Words for 1:1 PC Link
RS-232C Port Communications Mode
RS-232C Port Baud Rate
RS-232C Port Frame Format
RS-232C Port Transmission Delay
DM 6645 bits 04 to 07
DM 6645 bits 08 to 11
DM 6645 bits 12 to 15
DM 6646 bits 00 to 07
DM 6646 bits 08 to 15
DM 6647
RS-232C Port Host Link Node Number DM 6648 bits 00 to 07
RS-232C Port No-protocol Start Code Enable DM 6648 bits 08 to 11
RS-232C Port No-protocol End Code Enable DM 6648 bits 12 to 15
RS-232C Port No-protocol Start Code Setting DM 6649 bits 00 to 07
RS-232C Port No-protocol End Code Setting or Number of Bytes Received
DM 6649 bits 08 to 15
Peripheral Port No-protocol Start Code Enable DM 6653 bits 08 to 11
Peripheral Port No-protocol End Code Enable DM 6653 bits 12 to 15
Peripheral Port No-protocol Start Code Setting DM 6654 bits 00 to 07
Peripheral Port No-protocol End Code Setting or Number of Bytes Received
Battery Error Detect Setting
DM 6654 bits 08 to 15
DM 6655 bits 12 to 15
1-6 Preparation for Operation
Follow the steps listed below when setting up a CPM2A system.
1, 2, 3...
1. System Design
•
Select a CPM2A CPU Unit, Expansion Units and Expansion I/O Units with the specifications required in the controlled system.
•
Design external fail-safe circuits such as interlock circuits and limit circuits.
Refer to 2-1 Specifications and 3-1 Design Precautions for details.
2. Installation
•
Install the CPU Unit. (Surface-mount or DIN-track installation)
•
Install the Expansion Unit(s) and Expansion I/O Unit(s).
Refer to 3-3 Installing the CPM2A and 3-4 Wiring and Connections for details.
3. Wiring
•
Wire the power supply and I/O devices.
•
Connect communications devices if necessary.
•
Connect the Programming Console.
Refer to 3-4 Wiring and Connections for details.
4. Initial Settings
•
Turn OFF the CPU Unit’s Communications Switch, if necessary.
(When this switch is OFF, communications with devices other than the
Programming Console are governed by the settings in the PC Setup.)
24
Preparation for Operation Section 1-6
•
Connect the Programming Console, set the mode switch to PROGRAM mode, and turn ON the PC.
•
Check the CPU Unit’s LED indicators and the Programming Console’s display.
•
Clear the PC’s memory. (All Clear)
•
Make PC Setup settings.
Refer to 3-3 Installing the CPM2A for details.
5. Create Ladder Program
•
Create a ladder program to control the system.
Refer to the Programming Manual for details.
6. Write Ladder Program in PC
•
Write the ladder program in the PC with the Programming Console or transfer the program to the PC from the Support Software.
Refer to Section 4 Using Programming Devices, to the SYSMAC Support
Software Operation Manuals and to the CPT User Manual for details.
7. Test Run
•
Check I/O wiring in PROGRAM mode.
•
Check and debug program execution in MONITOR mode.
Refer to Section 5 Test Runs and Error Processing for details.
25
SECTION 2
Unit Specifications and Components
This section provides the technical specifications of the Units that go together to create a CPM2A PC and describes the main components of the Units.
2-1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-1 General Specifications of CPU Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-2 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-3 I/O Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 Unit Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-1 CPU Unit Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-2 Expansion I/O Unit Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-3 Analog I/O Unit Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-4 Temperature Sensor Unit Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-5 CompoBus/S I/O Link Unit Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
28
28
29
31
35
35
38
39
39
41
27
Specifications Section 2-1
2-1 Specifications
2-1-1 General Specifications of CPU Units
Item CPU Units with
20 I/O points
24 VDC
CPU Units with
30 I/O points
100 to 240 VAC, 50/60 Hz
CPU Units with
40 I/O points
CPU Units with
60 I/O points
Supply voltage AC power
DC power
Operating voltage range
AC power
DC power
85 to 264 VAC
20.4 to 26.4 VDC
60 VA max.
Power consumption
AC power
Inrush current
DC power
AC power
20 W max.
60 A max.
DC power 20 A max.
External power Supply voltage 24 VDC supply
Output
(AC power capacity
300 mA: Use for input devices only. Cannot be used to drive outputs.
supplies only)
(When the external power supply provides an overcurrent or is short circuited, the external power supply voltage will drop and PC operation will stop.)
Insulation resistance 20 M Ω min. (at 500 VDC) between the external AC terminals and protective earth terminals
Dielectric strength 2,300 VAC 50/60 Hz for 1 min between the external AC and protective earth terminals, leakage current: 10 mA max.
Noise immunity
Vibration resistance
Shock resistance
Ambient temperature
Humidity
Conforms to IEC6100-4-4; 2 kV (power lines)
10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s 2 in X, Y, and Z directions for 80 minutes each
(Time coefficient; 8 minutes
×
coefficient factor 10 = total time 80 minutes)
147 m/s 2 three times each in X, Y, and Z directions
Operating: 0
°
to 55
°
C
Storage: –20
°
to 75
°
C
10% to 90% (with no condensation)
Atmosphere
Terminal screw size
Power interrupt time
Must be free from corrosive gas
M3
AC power supply: 10 ms min.
DC power supply: 2 ms min.
(A power interruption occurs if power falls below 85% of the rated voltage for longer than the power interrupt time.)
CPU Unit weight
AC power
DC power
Expansion I/O Unit weight
Expansion Unit weight
650 g max.
550 g max.
700 g max.
600 g max.
Units with 20 I/O points: 300 g max.
Units with 8 output points: 250 g max.
Units with 8 input points: 200 g max.
Analog I/O Units: 150 g max.
Temperature Sensor Units: 250 g max.
CompoBus/S I/O Link Units: 200 g max.
800 g max.
700 g max.
1,000 g max.
900 g max.
28
Specifications Section 2-1
2-1-2 Characteristics
Item
Control method
I/O control method
Programming language
Instruction length
Instructions
Execution time
Specification
Stored program method
Cyclic scan with direct output (Immediate refreshing can be performed with IORF(97).)
Ladder diagram
1 step per instruction, 1 to 5 words per instruction
Basic instructions: 14
Special instructions: 105 instructions, 185 variations
Basic instructions: 0.64 µ s (LD instruction)
Special instructions: 7.8
µ s (MOV instruction)
4,096 words
20 points
80 points max.
30 points
90 points max.
40 points
100 points max.
60 points
120 points max.
Program capacity
Max. I/O CPU Unit only capacity
With Expansion
I/O Units
Input bits
Output bits
Work bits
Special bits (SR area)
Temporary bits (TR area)
Holding bits (HR area)
Auxiliary bits (AR area)
Link bits (LR area)
Timers/Counters
Data memory
IR 00000 to IR 00915 (Words not used for input bits can be used for work bits.)
IR 01000 to IR 01915 (Words not used for output bits can be used for work bits.)
928 bits: IR 02000 to IR 04915 and IR 20000 to IR 22715
448 bits: SR 22800 to SR 25515
8 bits (TR0 to TR7)
320 bits: HR 0000 to HR 1915 (Words HR 00 to HR 19)
384 bits: AR 0000 to AR 2315 (Words AR 00 to AR 23)
256 bits: LR 0000 to LR 1515 (Words LR 00 to LR 15)
256 timers/counters (TIM/CNT 000 to TIM/CNT 255)
1-ms timers: TMHH(––)
10-ms timers: TIMH(15)
100-ms timers: TIM
1-s/10-s timers: TIML(––)
Decrementing counters: CNT
Reversible counters: CNTR(12)
Read/Write: 2,048 words (DM 0000 to DM 2047)*
Read-only: 456 words (DM 6144 to DM 6599)
PC Setup: 56 words (DM 6600 to DM 6655)
Interrupt processing
Interval timer interrupts
High-speed counter
Interrupt Inputs
(Counter mode)
Quick-response inputs
Analog controls
*The Error Log is contained in DM 2000 to DM 2021.
External interrupts: 4
(Shared by the external interrupt inputs (counter mode) and the quick-response inputs.)
1 (Scheduled Interrupt Mode or Single Interrupt Mode)
One high-speed counter: 20 kHz single-phase or 5 kHz two-phase (linear count method)
Counter interrupt: 1 (set value comparison or set-value range comparison)
Four inputs (Shared by the external interrupt inputs (counter mode) and the quick-response inputs.)
Pulse output
Counter interrupts: 4 (Shared by the external interrupt inputs and quick-response inputs.)
Two points with no acceleration/deceleration, 10 Hz to 10 kHz each, and no direction control.
One point with trapezoid acceleration/deceleration, 10 Hz to 10 kHz, and direction control.
Two points with variable duty-ratio outputs.
(Pulse outputs can be used with transistor outputs only, they cannot be used with relay outputs.)
Synchronized pulse control One point:
A pulse output can be created by combining the high-speed counter with pulse outputs and multiplying the frequency of the input pulses from the high-speed counter by a fixed factor.
(This output is possible with transistor outputs only, it cannot be used with relay outputs.)
Four points (Min. input pulse width: 50
µ s max.)
2 controls, setting range: 0 to 200
29
Specifications Section 2-1
Item Specification
Input time constant
(ON response time =
OFF response time)
Can be set for all input points.
(1 ms, 2 ms, 3 ms, 5 ms, 10 ms, 20 ms, 40 ms, or 80 ms)
Clock function Shows the year, month, day of the week, day, hour, minute, and second.
(Backed up by the battery.)
Communications functions Built-in peripheral port:
Supports Host Link, peripheral bus, no-protocol, or Programming Console connections.
Functions provided by
Expansion Units
Built-in RS-232C port:
Supports Host Link, no-protocol, 1:1 Slave Unit Link, 1:1 Master Unit Link, or 1:1 NT Link connections.
Analog I/O Unit: Provides 2 analog inputs and 1 analog output.
Memory protection
(See notes 1 and 2.)
Memory backup
(See notes 1 and 2.)
Temperature Sensor Unit: Provides up to 6 thermocouple or platinum resistance thermometer inputs.
CompoBus/S I/O Link Unit: Provides 8 inputs and 8 outputs as a CompoBus/S Slave.
HR area, AR area, program contents, read/write DM area contents, and counter values maintained during power interruptions.
Flash memory:
Program, read-only DM area, and PC Setup
Self-diagnostic functions
Program checks
Battery backup:
The read/write DM area, HR area, AR area, and counter values are backed up by a battery. (Battery life is approximately 5 years at 25
°
C.)
CPU Unit failure (watchdog timer), I/O bus error, battery error, and memory failure
No END instruction, programming errors (checked when operation is started)
Note 1. The DM area, HR area, AR area, and counter values are backed up by the
CPU Unit’s built-in battery. If the battery is discharged, the contents of these areas will be lost and the data values will revert to the defaults.
2. The contents of the program area, read-only DM area (DM 6144 to
DM 6599), and PC Setup (DM 6600 to DM 6655) are stored in flash memory. The contents of these areas will be read from flash memory the next time the power is turned ON, even if the backup battery is discharged.
When data has been changed in any of these areas, write the new values to flash memory by switching the CPM2A to MONITOR or RUN mode, or by turning the power OFF and then ON again.
30
Specifications
2-1-3 I/O Specifications
CPU Unit Input Specifications
Item
Input voltage
Input impedance
Input current
Inputs
All
IN00007 and up
24 VDC +10% /
–15%
IN00000 to IN00001 2.7 k Ω
IN00002 to IN00006 3.9 k
Ω
4.7 k
Ω
IN00000 to IN00001 8 mA typical
IN00002 to IN00006 6 mA typical
IN00007 and up 5 mA typical
ON voltage/current IN00000 to IN00001 17 VDC min., 5 mA
IN00002 and up
OFF voltage/current All
ON delay All
OFF delay All
Circuit configuration IN00000 to IN00001
Specification
14.4 VDC min., 3 mA
5.0 VDC max., 1 mA
1 to 80 ms max. Default: 10 ms (See note.)
1 to 80 ms max. Default: 10 ms (See note.)
IN
Input LED
0.01
µ
F
IN
Internal circuits
COM
2.7 k Ω 680
Ω
Section 2-1
IN00002 to IN00006
IN
IN
COM
3.9 k
Ω
750
Ω
Input LED
Internal circuits
IN00007 and up
IN
IN
COM
4.7 k
Ω
750 Ω
Input LED
Internal circuits
Note The input time constant can be set to 1, 2, 3, 5, 10, 20, 40, or 80 ms in the PC
Setup.
High-speed Counter Inputs
Inputs IN00000 through IN00002 can be used as high-speed counter inputs, as shown in the following table. The maximum count frequency is 5 kHz in differential phase mode and 20 kHz in the other modes.
Input Function
Differential phase mode
IN00000 A-phase pulse input
Pulse plus direction input mode
Pulse input
Up/down input mode
Increment pulse input
Increment mode
Increment pulse input
IN00001 B-phase pulse input Direction input Decrement pulse input Normal input
IN00002 Z-phase pulse input or hardware reset input
(IN00002 can be used as a normal input when it is not used as a high-speed counter input.)
31
Specifications Section 2-1
The minimum pulse widths for inputs IN00000 (A-phase input) and IN00001 (Bphase input) are as follows:
Pulse plus direction input mode, Up/down input mode, Increment mode
50
µ s min.
Phase A
Phase B
12.5
µ s min.
12.5
µ s min.
Differential phase mode
100
µ s min.
T
1
T
2
T
3
T
4
T
1
T
2
T
3
T
4
: 12.5
µ s min.
The minimum pulse width for input IN00002 (Z-phase input) is as follows:
50
µ s min.
Phase Z
500
µ s min.
Interrupt Inputs
Inputs IN00003 through IN00006 can be used as interrupt inputs (interrupt input mode or counter mode) and quick-response inputs. The minimum pulse width for these inputs is 50
µ s.
Expansion I/O Unit Input Specifications
Item
Input voltage
Input impedance
Input current
ON voltage
OFF voltage
ON delay
OFF delay
Circuit configuration
Specification
24 VDC
+10%
/
–15%
4.7 k
Ω
5 mA typical
14.4 VDC min.
5.0 VDC max.
1 to 80 ms max. Default: 10 ms (See note.)
1 to 80 ms max. Default: 10 ms (See note.)
IN
Input LED
IN
COM
4.7 k
Ω
750 Ω
Internal circuits
Note The input time constant can be set to 1, 2, 3, 5, 10, 20, 40, or 80 ms in the PC
Setup.
!
Caution Do not apply voltage in excess of the rated voltage to the input terminal. It may result in damage to the product or fire.
32
Specifications
CPU Unit and Expansion I/O Unit Output Specifications
Relay Outputs
Item
Max. switching capacity
Min. switching capacity
Service life of relay
(See note.)
ON delay
OFF delay
Circuit configuration
20CDRj
30CDRj
2 A, 250 VAC (cos
φ
= 1)
2 A, 24 VDC
(4 A/common)
10 mA, 5 VDC
Electrical:
Specification
40CDRj
60CDRj 8ER
150,000 operations (24-VDC resistive load)
100,000 operations (240-VAC inductive load, cos
φ
= 4)
20,000,000 operations Mechanical:
15 ms max.
15 ms max.
Output LED
Section 2-1
20EDR1
Life (x 10 4 )
Internal circuits
Maximum
250 VAC: 2 A
24 VDC: 2 A
Note The service life of relay output contacts shown in the table assumes the worst conditions. The following graph shows the results of OMRON’s service life tests at a switching rate of 1,800 times/hour.
120 VAC, resistive load
24 VDC,
τ
= 7 ms
120 VAC, cos
φ
= 0.4
240 VAC, cos
φ
= 0.4
24 VDC/240 VAC, resistive load
Contact current (A)
Switching rate: 1,800 times/hour
33
Specifications Section 2-1
Transistor Outputs (Sinking or Sourcing)
Item
Max.
switching capacity
Specification
20CDT-D
20CDT1-D
30CDT-D
30CDT1-D
40CDT-D
40CDT1-D
60CDT-D
60CDT1-D
OUT01000 and OUT01001: 4.5 to 30 VDC, 0.2 A/output (See note 1.)
OUT01002 and up:
0.8 A/common
1.6 A/Unit
(See note 2.)
4.5 to 30 VDC, 0.3 A/output
0.8 A/common
2.4 A/Unit
(See note 2.)
0.8 A/common
3.2 A/Unit
(See note 2.)
0.8 A/common
4.8 A/Unit
(See note 2.)
0.1 mA max.
8ET
8ET1
0.9 A/common
1.8 A/Unit
(See note 2.)
Leakage current
Residual voltage
ON delay
OFF delay
Fuse
1.5 V max.
OUT01000 and OUT01001: 20
µ s max.
OUT01002 and up: 0.1 ms max.
OUT01000 and OUT01001: 40
µ s max. for 4.5 to 26.4 V, 10 to 100 mA
0.1 ms max. for 4.5 to 30 V, 10 to 200 mA
OUT01002 and up: 1 ms max.
1 fuse/output (cannot be replaced by user)
20EDT
20EDT1
24 VDC
+10%
/
–5%
,
0.3 A/output
0.9 A/common
1.8 A/Unit
0.1 ms max.
1 ms max.
(24 VDC
+10%
/
–5%
,
5 to 300 mA)
1 fuse/common
(cannot be replaced by user)
Circuit configura tion
Sinking Outputs
Output LED
OUT
Sourcing Outputs
Output LED
Internal circuits
OUT
24 VDC
COM (–)
Internal circuits
COM (+)
OUT
24 VDC
OUT
Note 1. When using OUT01000 or OUT01001 as a pulse output, connect a dummy resistor as required to bring the load current between 0.01 and 0.1 A. If the load current is below 0.1 A, the ON-to-OFF response time will be shorter and high-speed pulses (source-type transistor outputs) will not be output. If the load current is above 0.1 A, the transistor will generate more heat and components may be damaged.
2. The total for OUT01000 to OUT 01003 must be 0.8 A maximum. If the ambient temperature is maintained below 50
°
C, however, up to 0.9 A/common can be used.
!
Caution Do not apply voltage in excess of the maximum switching capacity to an output terminal. It may result in damage to the product or fire.
34
Unit Components
2-2 Unit Components
2-2-1 CPU Unit Components
CPU Units with 20 or 30 I/O Terminals
2. Functional ground terminal
(AC power supplies only)
1. Power supply input terminals 5. Input terminals
3. Protective ground terminal
Section 2-2
10. Analog controls
11. Peripheral Port
7. PC Status Indicators
14. Battery compartment
4. External Power supply terminals
(AC power supplies only)
CPU Units with 40 I/O Terminals
6. Output terminals
8. Input indicators
(0CH only for
20-point CPU Units)
12. RS-232C port
15. Expansion connector cover
13. Communications
Switch
9. Output indicators
(10CH only for
20-point CPU Units)
CPU Units with 60 I/O Terminals
35
Unit Components
Section 2-2
CPU Unit Component Descriptions
1, 2, 3...
1. Power Supply Input Terminals
Connect the power supply (100 to 240 VAC or 24 VDC) to these terminals.
2. Functional Ground Terminal ( )
Be sure to ground this terminal (AC-type PCs only) to enhance immunity to noise and reduce the risk of electric shock.
3. Protective Ground Terminal ( )
Be sure to ground this terminal to reduce the risk of electric shock.
4. External Power Supply Terminals
CPM2A PCs are equipped with these 24-VDC power output terminals to supply power to input devices. (AC-type PCs only.)
5. Input Terminals
Connects the CPU Unit to external input devices.
6. Output Terminals
Connects the CPU Unit to external output devices.
7. PC Status Indicators
These indicators show the operating status of the PC, as shown in the following table.
Indicator
PWR
(green)
Status
ON
Meaning
Power is being supplied to the PC.
RUN
(green)
OFF
ON
Power isn’t being supplied to the PC.
The PC is operating in RUN or MONITOR mode.
COMM
(yellow)
OFF The PC is in PROGRAM mode or a fatal error has occurred.
Flashing Data is being transferred via the Peripheral port or
RS-232C port.
OFF Data isn’t being transferred via the Peripheral port or RS-232C port.
ERR/ALARM ON
(red)
Flashing
A fatal error has occurred. (PC operation stops.)
A non-fatal error has occurred. (PC operation continues.)
OFF Indicates normal operation.
8. Input Indicators
The input indicators are lit when the corresponding input terminal is ON. The indicators are lit during I/O refreshing.
When a fatal error occurs, the input indicators change as follows:
Fatal error
CPU Unit error, I/O bus error, or too many I/O Units
Memory error or FALS (fatal system) error
Turn OFF.
Input indicators
The indicators will change with the status of the input signal, but input status will not be updated in memory.
Note a) When interrupt inputs are used in interrupt input mode, the indicator may not light even when the interrupt condition is met if the input is not ON long enough.
b) When high-speed counters are used, the input indicator may not light if the input pulse is too fast.
9. Output Indicators
The output indicators are lit when the corresponding output terminal is ON.
The indicators are lit during I/O refreshing. When pulse outputs are being used, the indicator will remain lit continuously while the pulses are being output.
36
Unit Components
Section 2-2
10. Analog Controls
Turn these controls to change the analog settings (0 to 200) in IR 250 and
IR 251.
11. Peripheral Port
Connects the PC to a Programming Device (including Programming
Consoles), host computer, or standard external device.
12. RS-232C Port
Connects the PC to a Programming Device (excluding Programming
Consoles), host computer, Programmable Terminal, or standard external device.
RS-232C Port Pin Allocation
FG
SD
1
2
RD 3
RTS 4
CTS 5
6
7
8
9
DCD
DSR
DTR
SG
(Factory-set to OFF)
13. Communications Switch
This switch selects whether the Peripheral port and RS-232C port will use the communications settings in the PC Setup or the standard settings.
OFF
ON
The Peripheral port and RS-232C port operate according to the communications settings in the PC Setup, except for a Programming
Console connected to the Peripheral port.
The Peripheral port and RS-232C port operate according to the standard communications settings, except for Programming Consoles connected to the Peripheral port.
Note This switch’s setting has no effect on communications with a Programming Console connected to the Peripheral port. It affects the
RS-232C port.
14. Battery
This battery backs up memory in the CPU Unit and is connected when the
Unit is shipped.
15. Expansion Connector
Connects the PC’s CPU Unit to an Expansion I/O Unit or Expansion Unit
(Analog I/O Unit, Temperature Sensor Unit, or CompoBus/S I/O Link Unit).
Up to 3 Expansion Units or Expansion I/O Units can be connected to a CPU
Unit.
Note If an NT-AL001 is connected to the CPM2A’s RS-232C port, only one
Expansion Unit or Expansion I/O Unit can be connected to the CPU
Unit because the NT-AL001 draws its 5-VDC power from the CPU
Unit.
37
Unit Components
2-2-2 Expansion I/O Unit Components
Expansion I/O Unit with 20 I/O Terminals
Section 2-2
5. Expansion I/O connecting cable
1. Input terminals
3. Input indicators
6. Expansion connector
4. Output indicators
2. Output terminals
Expansion I/O Unit with 8 Input Terminals
04 05 06 07
1. Input terminals
3. Input indicators
6. Expansion connector
5. Expansion I/O connecting cable
1. Input terminals
Expansion I/O Unit with 8 Output Terminals
04 05 06 07
2. Output terminals
4. Output indicators
6. Expansion connector
2. Output terminals
5. Expansion I/O connecting cable
1, 2, 3...
1. Input Terminals
Connects the CPU Unit to external input devices.
2. Output Terminals
Connects the CPU Unit to external output devices.
3. Input Indicators
The input indicators are lit when the corresponding input terminal is ON.
4. Output Indicators
The output indicators are lit when the corresponding output terminal is ON.
5. Expansion I/O Connecting Cable
Connects the Expansion I/O Unit to the expansion connector on the PC’s
CPU Unit, an Expansion Unit, or another Expansion I/O Unit.
38
Unit Components
Section 2-2
!
Caution Do not touch the expansion I/O connecting cable while the power is being supplied in order to prevent any malfunction due to static electricity.
6. Expansion Connector
Connects to another Expansion I/O Unit or an Expansion Unit (Analog I/O
Unit, Temperature Sensor Unit, or CompoBus/S I/O Link Unit). Up to 3 Expansion Units or Expansion I/O Units can be connected to a CPU Unit.
2-2-3 Analog I/O Unit Components
2. Expansion I/O connecting cable
3. Expansion connector
1. Analog I/O terminals
1, 2, 3...
1. Analog I/O Terminals
Connects the Unit to analog input devices and analog output devices.
2. Expansion I/O Connecting Cable
Connects the Analog I/O Unit to the expansion connector on the PC’s CPU
Unit, an Expansion I/O Unit, or another Expansion Unit. The cable is connected to the Analog I/O Unit and cannot be removed.
!
Caution Do not touch the expansion I/O connecting cable while the power is being supplied in order to prevent any malfunction due to static electricity.
3. Expansion Connector
Connects to an Expansion I/O Unit or another Expansion Unit (Analog I/O
Unit, Temperature Sensor Unit, or CompoBus/S I/O Link Unit). Up to 3 Expansion Units or Expansion I/O Units can be connected to a CPU Unit.
2-2-4 Temperature Sensor Unit Components
2. DIP switch 3. Rotary switch
5. Expansion connector
4. Expansion I/O connecting cable 1. Temperature input terminals
1, 2, 3...
1. Temperature Input Terminals
Connect to a thermocouple or a platinum resistance thermometer.
39
Unit Components
Section 2-2
2. DIP Switch
Sets the temperature unit (
°
C or
°
F), and the number of decimal places used.
ON
1 2
Number of decimal places used
OFF: Normal (0 or 1); ON: 2
Temperature unit
OFF:
°
C; ON:
°
F
3. Rotary Switch
Sets the temperature range. Set the range in accordance with the specifications of the temperature sensor used.
40
CPM1A-TS001/002
1
2
Set value
0
3
4 to F
K
J
---
Thermocouple Range (
°
C)
–200 to 1,300
0.0 to 500.0
–100 to 850
0.0 to 400.0
Setting not possible
Range (
°
F)
–300 to 2,300
0.0 to 900.0
–100 to 1,500
0.0 to 750.0
CPM1A-TS101/102
0
1
Set value Platinum resistance thermometer
Pt100
JPt100
2 to F ---
Range (
°
C)
–200.0 to 650.0
–200.0 to 650.0
Setting not possible
Range (
°
F)
–300.0 to 1,200.0
–300.0 to 1,200.0
4. Expansion I/O Connecting Cable
Connects the Temperature Sensor Unit to the expansion connector on the
PC’s CPU Unit, an Expansion I/O Unit, or another Expansion Unit. The cable is connected to the Temperature Sensor Unit and cannot be removed.
!
Caution Do not touch the expansion I/O connecting cable while the power is being supplied in order to prevent any malfunction due to static electricity.
5. Expansion Connector
Connects to an additional Expansion I/O Unit or another Expansion Unit.
Unit Components
2-2-5 CompoBus/S I/O Link Unit Components
Section 2-2
2. DIP switch
3. LED indicators
5. Expansion connector
1. CompoBus/S terminals 4. Expansion I/O connecting cable
NODE ADDRESS
ON
1, 2, 3...
1. CompoBus/S Terminals
Include the CompoBus/S communications data high/low terminal, communications power supply +/– terminals, and NC terminals. Power is supplied to the Unit internally, so the power supply terminals can be used as relay terminals.
2. DIP Switch
The DIP switch sets the Unit’s node address, sets the communications mode, and determines whether or not the outputs will be cleared in the event of a communications error.
SW1
Pin(s)
1 to 4
(labeled
1, 2, 4, and 8)
DR
HOLD
Function
These pins set the Unit’s node address using the DIP switch pins as binary digits. (1 = ON)
0: 0000
4: 0100
8: 1000
12: 1100
1: 0001
5: 0101
9: 1001
13: 1101
2: 0010
6: 0110
10: 1010
14: 1110
ON: Long-distance Communications Mode
OFF: High-speed Communications Mode
(See note.)
3: 0011
7: 0111
11: 1011
15: 1111
ON: Retain outputs when a communications error occurs.
OFF: Clear outputs when a communications error occurs.
Note The Long-distance Communications Mode can be used only when connected to one of the following Master Units: C200HW-SRM21-V1, CQM1-SRM21-V1, or
SRM1-C0 j -V2.
3. LED Indicators
These indicators show the status of CompoBus/S communications.
Indicator
COMM
(yellow)
Status
ON
OFF
ON
Meaning
Communications in progress.
Communications error or stopped.
A communications error has occurred.
ERR
(red)
OFF Indicates normal or no communications.
4. Expansion I/O Connecting Cable
Connects the CompoBus/S I/O Link Unit to the expansion connector on the
PC’s CPU Unit, an Expansion I/O Unit, or another Expansion Unit.
!
Caution Do not touch the expansion I/O connecting cable while the power is being supplied in order to prevent any malfunction due to static electricity.
5. Expansion Connector
Connects to an Expansion I/O Unit or another Expansion Unit (Analog I/O
Unit, Temperature Sensor Unit, or CompoBus/S I/O Link Unit). Up to 3 Expansion Units or Expansion I/O Units can be connected to a CPU Unit.
41
SECTION 3
Installation and Wiring
This section provides information on installing and wiring a CPM2A PC. Be sure to follow the directions and precautions in this section when installing the CPM2A in a panel or cabinet, wiring the power supply, or wiring I/O.
3-1 Design Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1-1 Power Supply Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1-2 Power Supply Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1-3 Interlock and Limit Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Selecting an Installation Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2-1 Installation Site Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2-2 Panel/Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3 Installing the CPM2A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3-1 CPM2A Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3-2 CPM2A Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3-3 Connecting an Expansion Unit or Expansion I/O Unit . . . . . . . . . . . . . . . . . . . . .
3-4 Wiring and Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-1 General Precautions for Wiring
3-4-2 Removing the Terminal Block
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-3 Ground Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-4 Power Supply Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-5 Input Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-6 Output Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-7 Programming Device Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-8 Host Link Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-9 No-Protocol Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-10 OMRON PT Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-11 One-to-one PC Link Connections
3-4-12 CompoBus/S I/O Link Connections
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
49
49
50
51
46
46
48
44
45
45
46
44
44
44
44
77
80
80
52
54
62
76
81
81
43
Selecting an Installation Site
Section 3-2
3-1 Design Precautions
Observe the following precautions when designing a system incorporating a
CPM2A PC.
3-1-1 Power Supply Wiring
Separate the power supply wiring from the control system, CPM2A system, and
DC I/O system wiring. Separate the control circuits that supply power to the main
Unit from the main circuits using dedicated circuit protectors and fuses.
3-1-2 Power Supply Voltage
!
Caution Use the power supply voltages indicated in Section 2 Unit Specifications and
Components. Failure to adhere to the specifications may result in fire.
If the power supply voltage falls below 85% of the rated voltage, the CPM2A will stop and all outputs will be turned OFF. If low voltage affects the equipment, etc., provide a protection circuit which shuts off the output until the supply voltage returns to the rated value.
In places where power supply conditions are poor, take steps to ensure that power is supplied at the rated voltage. Be sure to adhere to safety precautions, such as providing breakers to prevent short circuits in external wiring.
When conducting any of the following operations, turn OFF the power to the PC.
Electrocution, product damage and malfunction may result.
•
Connecting or disconnecting Expansion Units, Expansion I/O Units, and CPU
Units.
•
Assembling Units
•
Connecting cables and wiring.
3-1-3 Interlock and Limit Circuits
!
WARNING Emergency stop circuits, interlock circuits, limit circuits, and similar safety measures must be provided in external control circuits (i.e., not in the
Programmable Controller) to ensure safety in the system if an abnormality occurs due to malfunction of the PC or another external factor affecting the PC operation. Not providing proper safety measures may result in serious accidents.
The following diagram shows an example of an interlock circuit.
Interlock Circuit
01005
MC1
CPM2A MC2
Motor forward
01006
MC1
MC2
Motor reverse
In the interlock circuit above, MC1 and MC2 can’t be ON at the same time even if
CPM2A outputs 01005 and 01006 are both ON (an incorrect PC operation).
3-2 Selecting an Installation Site
The CPM2A is resistant to harsh conditions and highly reliable, but installing the
PC in a favorable site will maximize its reliability and operating lifetime.
44
Selecting an Installation Site
Section 3-2
!
Caution Be sure to install the CPM2A correctly, as outlined in this manual. Failure to do so may result in Unit malfunction.
3-2-1 Installation Site Conditions
Note Do not install the CPM2A under any of the following conditions.
•
Locations subject to direct sunlight.
•
Locations subject to a temperature below 0
°
C or over 55
°
C.
•
Locations subject to a humidity below 10% or over 90%.
•
Locations subject to condensation as the result of severe changes in temperature.
•
Locations subject to corrosive or flammable gases.
•
Locations subject to dust (especially iron dust) or salts.
•
Locations subject to shock or vibration.
•
Locations subject to exposure to water, oil, or chemicals.
Be sure that the conditions at the installation site conform to the CPM2A’s general specifications. Refer to 2-1-1 General Specifications for details.
Note Provide proper shielding when installing in the following locations:
•
Locations subject to static electricity or other sources of noise.
•
Locations subject to strong electromagnetic fields.
•
Locations subject to possible exposure to radiation.
•
Locations near to power supply lines.
3-2-2 Panel/Cabinet Installation
Overheating
Consider PC operation, maintenance, and surrounding conditions when installing the CPM2A in a panel or cabinet.
The operating temperature range for the CPM2A is 0 _ C to 55 _ C. Be sure that there is adequate ventilation for cooling.
•
Allow enough space for air circulation.
•
Do not install the CPM2A above equipment that generates a large amount of heat, such as heaters, transformers, or large resistors.
•
Install a cooling fan or system when the ambient temperature exceeds 55 _ C.
Control panel
Fan
Electrical Noise
CPM2A
Air vent
Power lines and high-voltage equipment can cause electrical noise in the PC.
•
Do not install the CPM2A in a panel or cabinet with high-voltage equipment.
•
Allow at least 200 mm between the CPM2A and nearby power lines.
200 mm min.
CPM2A
200 mm min.
45
Installing the CPM2A Section 3-3
Accessibility Ensure that the CPM2A can be accessed for normal operation and maintenance.
•
Provide a clear path to the CPM2A for operation and maintenance. High-voltage equipment or power lines could be dangerous if they are in the way during routine operations.
•
The PC will be easiest to access if the panel or cabinet is installed about 3 to 5 feet above the floor.
3-3 Installing the CPM2A
This section describes how to install the CPM2A and connect Expansion Units and Expansion I/O Units. Refer to Appendix B for diagrams showing the dimensions of the Units.
3-3-1 CPM2A Orientation
The CPM2A must be installed in the position shown below to ensure adequate cooling.
Correct
Do not install the CPM2A in either of the following positions.
Incorrect Incorrect
3-3-2 CPM2A Installation
The CPM2A can be installed on a horizontal surface or on a DIN track.
Surface Installation Use the following pattern when installing a CPM2A CPU Unit, Expansion Unit, or
Expansion I/O Unit on a vertical surface. (Use M4 dia. x 15 screws.)
Four M4 holes
100 mm
Unit
A 8 mm
The width (A) between the mounting holes depends on the Unit.
Unit
CPU Unit with 20/30 I/O terminals
CPU Unit with 40 I/O terminals
Width (A)
(tolerance:
±
0.2 mm)
120 mm
140 mm
46
Installing the CPM2A
DIN Track Installation
Section 3-3
Unit
CPU Unit with 60 I/O terminals
Expansion I/O Unit with 20 I/O terminals
Expansion I/O Unit with 8 input terminals
Expansion I/O Unit with 8 output terminals
Analog I/O Unit
CompoBus/S I/O Link Unit
RS-232C Adapter
RS-422 Adapter
Temperature Sensor Unit
Width (A)
(tolerance:
±
0.2 mm)
185 mm
76 mm
56 mm
56 mm
56 mm
56 mm
21 mm
21 mm
76 mm
Allow 10 to 15 mm between the Units when installing an Expansion Unit, Expansion I/O Unit, or Communications Adapter next to the CPU Unit.
21 mm
81 mm CPU Unit
100 mm
Communications
Adapter
10 to
15 mm
10 to
15 mm
Expansion Unit or Expansion I/O
Unit
The CPM2A can be installed on a 35-mm DIN Track.
DIN Track
PFP-100N (1 m)
PFP-50N (50 cm)
PFP-100N2 (1 m)
End Plates
(PFP-M)
Installation
Lower the CPM2A so that the notch on the back of the PC catches the top of the
DIN Track. Push the PC forward until the lock snaps into place.
47
Installing the CPM2A Section 3-3
Removal
Pry the lock down with a flat-blade screwdriver and pivot the PC upward to remove it.
Screwdriver
3-3-3 Connecting an Expansion Unit or Expansion I/O Unit
Up to 3 Expansion Units or Expansion I/O Units can be connected to a CPM2A
CPU Unit. Use the following procedure when connecting an Expansion Unit or
Expansion I/O Unit.
1, 2, 3...
1. Remove the cover from the CPU Unit’s or the Expansion I/O Unit’s expansion connector. Use a flat-blade screwdriver to remove the cover from the
Expansion I/O Connector.
Expansion connector cover
2. Insert the Expansion I/O Unit’s connecting cable into the CPU Unit’s or the
Expansion I/O Unit’s expansion connector.
48
Wiring and Connections Section 3-4
3. Replace the cover on the CPU Unit’s or the Expansion I/O Unit’s expansion connector.
3-4 Wiring and Connections
This section provides basic information on wiring the Power Supply Unit, Expansion Units, and Expansion I/O Units, and on connecting Programming Devices.
3-4-1 General Precautions for Wiring
!
Caution Leave the protective label in place while wiring. The Unit may malfunction if strands of wire get inside the Unit. After completing wiring be sure to remove the label to avoid overheating.
Protective label
I/O Line Noise Do not run CPM2A I/O lines in the same duct or conduit as power lines.
Hanging Ducts
Leave at least 300 mm between the power cables and the I/O or control wiring, as shown in the following diagram.
CPM2A I/O lines
Control cables and
CPM2A power lines
Power cables
300 mm min.
300 mm min.
49
Wiring and Connections Section 3-4
Floor Ducts
Leave at least 200 mm between the wiring and the top of the duct, as shown in the following diagram.
CPM2A I/O lines
Control cables and
CPM2A power lines Power cables
Metal plate (iron)
200 mm min.
Conduits
Separate the CPM2A I/O lines, power and control lines, and power cables, as shown in the following diagram.
CPM2A I/O lines
Control cables and
CPM2A power lines Power cables
3-4-2 Removing the Terminal Block
The terminal block on the CPM2A CPU Unit can be removed. Use the following procedure.
The terminal blocks on the Expansion Units and Expansion I/O Units cannot be removed.
1, 2, 3...
1. Loosen the black screws at the ends of the terminal block as shown in the following diagram.
Black screws
Black screws
50
Wiring and Connections
2. Lift the terminal block off the CPU Unit.
Section 3-4
3-4-3 Ground Wiring
Grounding Be sure to ground the earth terminal to less than 100
Ω
in order to protect against electric shock and incorrect operation from electrical noise. Be sure to use a wire of at least 1.25 mm
2
for grounding.
!
WARNING During installation, be sure to ground to 100
Ω max.
Ground to 100
Ω
or less
AC power supply unit
Ground to 100
Ω
or less
DC power supply unit
Note Always disconnect the functional earth terminal before conducting a withstand voltage test.
Crimp Terminals
!
Caution Always use crimp terminals for the CPM2A’s ground lines or use solid wire
(instead of a stranded wire). Do not connect bare stranded wires directly to terminals. Stray wire strands can short-circuit and cause a fire.
Use M3 crimp terminals and tighten the terminal screws to a torque of 0.5 N S m.
Fork terminal Ring terminal
6.2 mm max.
6.2 mm max.
The recommended wire size for solid wires is 0.4 to 1.2 mm (AWG26 to AWG18).
51
Wiring and Connections Section 3-4
3-4-4 Power Supply Wiring
100- to 240-VAC Power
Supply
Wire a separate circuit for the CPM2A’s power supply circuit so that there isn’t a voltage drop from the inrush current that flows when other equipment is turned on.
When several CPM2A PCs are being used, it is recommended to wire the PCs on separate circuits to prevent a voltage drop from the inrush current or incorrect operation of the circuit breaker.
Use twisted power supply wires to prevent noise from the power supply lines.
Adding a 1:1 isolating transformer reduces electrical noise even further.
Considering the possibility of voltage drops and the allowable current, be sure to use thick power lines.
Twist the wires. The cross-sectional area of each wire must be 1.25 mm 2 min.
Isolating transformer
AC power supply
Breaker
Note 1. Before connecting the power supply, make sure that the CPU Unit requires an AC power supply and not a DC power supply. The CPU Unit’s internal circuitry will be damaged if AC power is mistakenly supplied to a CPU Unit that requires a DC power supply.
2. The power supply input terminals are at the top of the CPU Unit; the terminals at the bottom of the CPU Unit output 24-VDC power for external devices. The CPU Unit’s internal circuitry will be damaged if AC power is mistakenly supplied to a CPU Unit’s power supply output terminals.
!
Caution Tighten the terminal block screws of the AC Power Supply to the torque of
0.5 N S m. Loose screws may result in fire or malfunction.
Crimp Terminals
!
Caution Always use crimp terminals for the CPM2A’s power lines. Do not connect bare stranded wires directly to terminals. Stray wire strands can short-circuit and cause a fire.
Use M3 crimp terminals and tighten the terminal screws to a torque of 0.5 N S m.
Connect a ring terminal to each terminal screw.
Ring terminal
6.2 mm max.
52
Wiring and Connections
24-VDC Power Supply Use a DC power supply with sufficient capacity and low ripple.
24 VDC
Section 3-4
Note 1. Do not perform a dielectric test on the DC power supply terminals on the
CPU Unit. The test might damage the PC’s internal components.
2. When equipment must conform to the EC Directives (Low-voltage Directives), use a power supply with double insulation or reinforced insulation.
Crimp Terminals
!
Caution Always use crimp terminals for the CPM2A’s power lines or use solid wire
(instead of a stranded wire). Do not connect bare stranded wires directly to terminals. Stray wire strands can short-circuit and cause a fire.
Use M3 crimp terminals and tighten the terminal screws to a torque of 0.5 N
S
m.
Fork terminal Ring terminal
6.2 mm max.
6.2 mm max.
The recommended wire size for solid wires is 0.4 to 1.2 mm (AWG26 to AWG18).
53
Wiring and Connections Section 3-4
3-4-5 Input Wiring
Wire the inputs to the CPM2A’s CPU Unit and Expansion I/O Units as shown in the following diagrams. Use crimp terminals or solid wires (not stranded wire) to connect to the PC. The power supply output terminals can be used with CPU
Units with AC power supplies.
Note When equipment must conform to the EC Directives (Low-voltage Directives), use a power supply with double insulation or reinforced insulation.
Input Configuration The following diagrams show the input configurations.
Note Refer to Section 3 Memory Areas in the Programming Manual (W353) for details on the allocation of input bits in CPM2A PCs.
CPM2A-20CDRj , CPM2A-20CDT-D, and CPM2A-20CDT1-D
Terminals 00 through 11 of “0CH” correspond to bits IR 00000 through IR 00011.
24 VDC
Input devices
24 VDC
CPM2A-30CDRj , CPM2A-30CDT-D, and CPM2A-30CDT1-D
Terminals 00 through 11 of “0CH” correspond to bits IR 00000 through IR 00011, terminals 00 through 05 of “1CH” correspond to bits IR 00100 through IR 00105.
Input devices
54
Wiring and Connections Section 3-4
CPM2A-40CDRj , CPM2A-40CDT-D, and CPM2A-40CDT1-D
Terminals 00 through 11 of “0CH” correspond to bits IR 00000 through IR 00011, terminals 00 through 11 of “1CH” correspond to bits IR 00100 through IR 00111.
24 VDC
Input devices
55
Wiring and Connections Section 3-4
CPM2A-60CDRj , CPM2A-60CDT-D, and CPM2A-60CDT1-D
Terminals 00 through 11 of “0CH” correspond to bits IR 00000 through IR 00011, terminals 00 through 11 of “1CH” correspond to bits IR 00100 through IR 00111, terminals 00 through 11 of “2CH” correspond to bits IR 00200 through IR 00211.
Input devices
56
24 VDC
Wiring and Connections Section 3-4
CPM1A-20EDR1, CPM1A-20EDT, and CPM1A-20EDT1
Terminals 00 through 11 of “mCH” correspond to bits 00 through 11 of word IR m.
24 VDC
Input devices
CPM1A-8ED
Terminals 00 through 07 of “mCH” correspond to bits 00 through 07 of word IR m.
24 VDC
Input devices
04
05
06
07
Note Although the commons are connected internally, they must all be wired.
57
Wiring and Connections
Input Wiring Example
Section 3-4
A CPU Unit with an AC power supply is shown. CPU Units with DC power supplies don’t have power supply outputs.
Input devices
External power supply output:
300 mA at 24 VDC for CPU Units with 20, 30, 40, or 60 I/O points
(CPU Units with a AC power supply input only.)
!
WARNING When the 24-VDC output (service power supply to the PC) is overloaded or short-circuited, the voltage may drop and result in the outputs being turned OFF.
External safety measures must be provided to ensure safety in the system. Not providing proper safety measures may result in serious accidents.
58
Wiring and Connections
Input Devices
Device
Relay output
Section 3-4
The following table shows how to connect various input devices.
Circuit diagram
5 mA/12 mA
IN
COM (+)
CPM2A
NPN open collector
Sensor power supply
NPN current output
Output
5 mA/12 mA
0 V
IN
COM (+)
CPM2A
Use the same power supply for the input and sensor.
Constant current circuit
Output
5 mA/12 mA
0 V
+
IN
COM (+)
CPM2A
PNP current output
Sensor power supply
5 mA/12 mA
Output
0 V
IN
COM (–)
CPM2A
Voltage output
Output
0 V
COM (+)
IN CPM2A
Sensor power supply
Note Do not use the following wiring with voltage-output devices:
Output
0 V
Sensor power supply
Incorrect Wiring
CPM2A IN
COM(+)
59
Wiring and Connections Section 3-4
High-speed Counter Inputs
Differential Phase Mode
(Count frequency: 5 kHz)
Using IR 00000 to IR 00002 as High-speed Counter Inputs
In these examples, Encoders with an external 24-VDC open-collector output are connected.
CPM2A
Pulse Plus Direction Input Mode
(Count frequency: 20 kHz)
CPM2A
Encoder 00000 A-phase input
Encoder 00000 Pulse input
00001 B-phase input
Sensor or switch
00002 Z-phase input
Sensor or switch
00001 Direction input
00002 Reset input
Sensor
24 VDC
Up/Down Mode
(Count frequency: 20 kHz)
COM
CPM2A
00000 CW input*
00001 CCW input*
Sensor
Sensor or switch 00002 Reset input
COM
24 VDC
Increment Mode
(Count frequency: 20 kHz)
CPM2A
Encoder
00000 Pulse input
00001 Normal input
00002 Normal input
PC Setup Settings
COM COM
24 VDC 24 VDC
Note *CW is clockwise and CCW is counter-clockwise.
Using IR 00003 to IR 00006 as Interrupt Inputs (Counter Mode)
In these examples, an Encoder with an external 24-VDC open-collector output is connected.
Increment or decrement
(Count frequency: 2 kHz)
CPM2A
Input (00003 to 00006)
Encoder
COM
24 VDC
The input bits shown in the following tables can operate as normal inputs or they can be assigned special functions in the PC Setup.
Special functions for input bits IR 00000 through IR 00002 are set in DM 6642:
Bit address
PC Setup setting (DM 6642 bits 08 to15)
00
IR 00000 Used as normal inputs.
IR 00001
01
Used as high-speed counter inputs.
Used as inputs for synchronized pulse control.
02, 03, or 04
IR 00002 Used as a normal input.
60
Wiring and Connections Section 3-4
Special functions for input bits IR 00003 through IR 00006 are set in DM 6628:
Bit Bits in address DM 6628
PC Setup setting (in DM 6628)
0
IR 00003 00 to 03 Used as normal
IR 00004 04 to 07 inputs.
1
Used as interrupt inputs (including counter mode).
Used as
2 quick-response inputs.
IR 00005 08 to 11
IR 00006 12 to 15
High-speed Counter Input Connection Examples
Differential Phase Mode
(Count frequency: 5 kHz)
E6B2-CWZ6C
Encoder
(NPN open-collector output)
Black
White
CPM2A
00000 A-phase input
00001 B-phase input
Pulse Plus Direction Input mode
(Count frequency: 20 kHz)
CPM2A
E6A2-CS5C
Encoder 00000 Pulse input
00001 Direction input
Orange
Brown
Blue
24 VDC
00002 Z-phase input
COM
Sensor or switch
Sensor or switch
Sensor power
24 VDC
00002 Reset input
COM
Leakage Current A leakage current can cause false inputs when using 2-wire sensors (proximity switches or photoelectric switches) or limit switches with LEDs. False inputs won’t occur if the leakage current is less than 1.0 mA (2.5 mA for IN00000 to
IN00002). If the leakage current exceeds these values, insert a bleeder resistor in the circuit to reduce the input impedance, as shown in the following diagram.
Input power supply
Bleeder resistor
2-wire sensor, etc.
I: Device’s leakage current (mA)
R: Bleeder resistance (k
Ω
)
W: Bleeder resistor’s power rating (W)
R CPM2A
I
L
E
C
C
C
: CPM2A’s input impedance (k
Ω
)
: CPM2A’s input current (mA)
: CPM2A’s OFF voltage (V) = 5.0 V
R
+
L
C
I L
C
5.0
–5.0
k
W max.
W
+
2.3
R
W min.
The equations above were derived from the following equations:
I
R
Input voltage (24)
Input Current (I
C
)
R
)
Input voltage (24)
Input Current (I
C
) x
OFF voltage (E
C
: 5.0)
W y
Input voltage (24)
R
Input voltage (24) tolerance (4)
Refer to 2-1-3 I/O Specifications for details on the values L
C
, I
C
, and E
C
.
The input impedance, input current, and OFF voltage may vary depending on the input being used. (IN00000 through IN00002 have different values.)
Inductive Loads When connecting an inductive load to an input, connect a diode in parallel with the load. The diode should satisfy the following requirements:
1, 2, 3...
1. Peak reverse-breakdown voltage must be at least 3 times the load voltage.
61
Wiring and Connections
2. Average rectified current must be 1 A.
Diode
IN
CPM2A
COM
Section 3-4
Crimp Terminals
!
Caution Always use crimp terminals for the CPM2A’s I/O lines or use solid wire (instead of a stranded wire). Do not connect bare stranded wires directly to terminals.
Stray wire strands can short-circuit and cause a fire.
Use M3 crimp terminals and tighten the terminal screws to a torque of 0.5 N
S
m.
6.2 mm max.
Fork terminal
6.2 mm max.
Ring terminal
The recommended wire size for solid wires is 0.4 to 1.2 mm (AWG26 to AWG18).
3-4-6 Output Wiring
Relay Output Wiring
Wire the outputs to the CPM2A’s CPU Unit and Expansion I/O Units as shown in the following diagrams. Use crimp terminals or solid wires (not stranded wire) to connect to the PC. The power supply output terminals can be used with a CPU
Unit with an AC power supply.
•
Always use single wire or attach crimp terminals if a stranded wire is used.
•
Don’t exceed the output capacity or the maximum common current. Refer to
2-1-3 I/O Specifications for details.
Item
Output capacity
Relay outputs Transistor outputs, sinking or sourcing
2 A (250 VAC or 24 VDC) 01000 and 01001: 200 mA (30 VDC)
01002 and higher: 300 mA (30 VDC)
Max. common capacity 4 A/common 0.8 A/common
Note Refer to Section 3 Memory Areas in the Programming Manual (W353) for details on the allocation of output bits in CPM2A PCs.
!
WARNING The PC outputs may remain ON or OFF due to deposition or burning of the output relays or destruction of the output transistors. External safety measures must be provided to ensure safety in the system. Not providing proper safety measures may result in serious accidents.
62
Wiring and Connections
Output Configurations
Section 3-4
CPM2A-20CDRj
Terminals 00 through 07 of “10CH” correspond to IR 01000 through IR 01007.
250 VAC/
24 VDC
250 VAC/
24 VDC
250 VAC/
24 VDC
250 VAC/
24 VDC
CPM2A-30CDRj
Terminals 00 through 07 of “10CH” correspond to IR 01000 through IR 01007.
Terminals 00 through 03 of “11CH” correspond to IR 01100 through IR 01103.
250 VAC/
24 VDC
250 VAC/
24 VDC
250 VAC/
24 VDC
250 VAC/
24 VDC
250 VAC/
24 VDC
CPM2A-40CDRj
Terminals 00 through 07 of “10CH” correspond to IR 01000 through IR 01007.
Terminals 00 through 07 of “11CH” correspond to IR 01100 through IR 01107.
250 VAC/
24 VDC
250 VAC/
24 VDC
250 VAC/
24 VDC
250 VAC/
24 VDC
250 VAC/
24 VDC
250 VAC/
24 VDC
63
Wiring and Connections Section 3-4
CPM2A-60CDRj
Terminals 00 through 07 of “10CH” correspond to IR 01000 through IR 01007.
Terminals 00 through 07 of “11CH” correspond to IR 01100 through IR 01107.
Terminals 00 through 07 of “12CH” correspond to IR 01200 through IR 01207.
Load
Load
Load
250 VAC/
24 VDC
Load
Load
Load
Load
Load
250 VAC/
24 VDC
Load
Load
Load
250 VAC/
24 VDC
Load
Load
Load
Load
Load
250 VAC/
24 VDC
Load
Load
Load
250 VAC/
24 VDC
Load
Load
Load
Load
250 VAC/
24 VDC
250 VAC/
24 VDC
Load
250 VAC/
24 VDC
64
Wiring and Connections Section 3-4
CPM1A-20EDR1
Terminals 00 through 07 of “1nCH” correspond to bits 00 through 07 of word
IR 1n.
250 VAC/
24 VDC
250 VAC/
24 VDC
250 VAC/
24 VDC
250 VAC/
24 VDC
CPM1A-8ER
Terminals 00 through 07 of “1nCH” correspond to bits 00 through 07 of word
IR 1n.
250 VAC/
24 VDC
250 VAC/
24 VDC
04
05
06
07
65
Wiring and Connections Section 3-4
Transistor Output Wiring (Sinking)
Wire the outputs to the CPM2A’s CPU Unit and Expansion I/O Units as shown in the following diagrams.
•
Always use single wire or attach crimp terminals if a stranded wire is used.
•
Don’t exceed the output capacity or the maximum common current. Refer to
2-1-3 I/O Specifications for details.
Item
Output capacity
Specification
OUT01000 and OUT01001: 200 mA (30 VDC)
OUT01002 and up: 300 mA (30 VDC)
Max. common capacity 0.8 A/common
Note Refer to Section 3 Memory Areas in the Programming Manual (W353) for details on the allocation of output bits in CPM2A PCs.
!
Caution Double-check the polarity of the power supply for the load before turning it ON. If the polarity is reversed, the load may malfunction or internal components may be damaged.
Output Configurations
CPM2A-20CDT-D
Terminals 00 through 07 of “10CH” correspond to IR 01000 through IR 01007.
66
4.5 to
30 VDC
4.5 to
30 VDC
4.5 to
30 VDC
4.5 to 30 VDC
CPM2A-30CDT-D
Terminals 00 through 07 of “10CH” correspond to IR 01000 through IR 01007.
Terminals 00 through 03 of “11CH” correspond to IR 01100 through IR 01103.
4.5 to
30 VDC
4.5 to
30 VDC
4.5 to
30 VDC
4.5 to 30 VDC 4.5 to 30 VDC
Wiring and Connections Section 3-4
CPM2A-40CDT-D
Terminals 00 through 07 of “10CH” correspond to IR 01000 through IR 01007.
Terminals 00 through 07 of “11CH” correspond to IR 01100 through IR 01107.
4.5 to
30 VDC
4.5 to
30 VDC
4.5 to
30 VDC
4.5 to 30 VDC 4.5 to 30 VDC 4.5 to 30 VDC
67
Wiring and Connections Section 3-4
CPM2A-60CDT-D
Terminals 00 through 07 of “10CH” correspond to IR 01000 through IR 01007.
Terminals 00 through 07 of “11CH” correspond to IR 01100 through IR 01107.
Terminals 00 through 07 of “12CH” correspond to IR 01200 through IR 01207.
Load
Load
Load
4.5 to 30 VDC
Load
Load
Load
Load
Load
4.5 to 30 VDC
Load
Load
Load
4.5 to 30 VDC
Load
Load
Load
Load
Load
4.5 to 30 VDC
Load
Load
Load
4.5 to 30 VDC
Load
Load
Load
4.5 to 30 VDC
Load
4.5 to 30 VDC
Load
4.5 to 30 VDC
68
Wiring and Connections Section 3-4
CPM1A-20EDT
Terminals 00 through 07 of “1nCH” correspond to bits 00 through 07 of word
IR 1n.
24 VDC +10%/–15%
CPM1A-8ET
Terminals 00 through 07 of “1nCH” correspond to bits 00 through 07 of word
IR 1n.
4.5 to 30 VDC
4.5 to 30 VDC
04
05
06
07
69
Wiring and Connections Section 3-4
Transistor Output Wiring (Sourcing)
Wire the outputs to the CPM2A’s CPU Unit and Expansion I/O Units as shown in the following diagrams.
•
Always use single wire or attach crimp terminals if a stranded wire is used.
•
Don’t exceed the output capacity or the maximum common current. Refer to
2-1-3 I/O Specifications for details.
Item Specification
Output capacity OUT01000 and OUT01001: 200 mA (30 VDC)
OUT01002 and up: 300 mA (30 VDC)
Max. common capacity 0.8 A/common
Note Refer to Section 3 Memory Areas in the Programming Manual (W353) for details on the allocation of output bits in CPM2A PCs.
!
Caution Double-check the polarity of the power supply for the load before turning it ON. If the polarity is reversed, the load may malfunction or internal components may be damaged.
Output Configurations
CPM2A-20CDT1-D
Terminals 00 through 07 of “10CH” correspond to IR 01000 through IR 01007.
4.5 to
30 VDC
4.5 to
30 VDC
4.5 to
30 VDC
4.5 to 30 VDC
CPM2A-30CDT1-D
Terminals 00 through 07 of “10CH” correspond to IR 01000 through IR 01007.
Terminals 00 through 03 of “11CH” correspond to IR 01100 through IR 01103.
4.5 to
30 VDC
4.5 to
30 VDC
4.5 to
30 VDC
4.5 to 30 VDC 4.5 to 30 VDC
70
Wiring and Connections Section 3-4
CPM2A-40CDT1-D
Terminals 00 through 07 of “10CH” correspond to IR 01000 through IR 01007.
Terminals 00 through 07 of “11CH” correspond to IR 01100 through IR 01107.
4.5 to
30 VDC
4.5 to
30 VDC
4.5 to
30 VDC
4.5 to 30 VDC 4.5 to 30 VDC 4.5 to 30 VDC
71
Wiring and Connections Section 3-4
CPM2A-60CDT1-D
Terminals 00 through 07 of “10CH” correspond to IR 01000 through IR 01007.
Terminals 00 through 07 of “11CH” correspond to IR 01100 through IR 01107.
Terminals 00 through 07 of “12CH” correspond to IR 01200 through IR 01207.
Load
Load
Load
4.5 to 30 VDC
Load
Load
Load
Load
Load
4.5 to 30 VDC
Load
Load
Load
4.5 to 30 VDC
Load
Load
Load
Load
Load
4.5 to 30 VDC
Load
Load
Load
4.5 to 30 VDC
Load
Load
Load 4.5 to 30 VDC
Load
4.5 to 30 VDC
Load
4.5 to 30 VDC
72
Wiring and Connections Section 3-4
CPM1A-20EDT1
Terminals 00 through 07 of “1nCH” correspond to bits 00 through 07 of word
IR 1n.
24 VDC +10%/–15%
CPM1A-8ET1
Terminals 00 through 07 of “1nCH” correspond to bits 00 through 07 of word
IR 1n.
4.5 to 30 VDC
4.5 to 30 VDC
04
05
06
07
73
Wiring and Connections Section 3-4
Using Pulse Outputs The following diagrams show example applications of sink-type transistor outputs using output bits IR 01000 and IR 01001. Use the PULS(65), SPED(––),
ACC(––), PWM(––), and SYNC(––) instructions to produce pulse outputs (rather than normal outputs) from output bits IR 01000 and IR 01001.
Single-phase pulse output
(Fixed duty ratio)
CPM2A
Motor driver
Single-phase pulse output
(Variable duty ratio)
CPM2A
Relay
Pulse output 0: 01000 Pulse output 0: 01000
COM COM
Motor driver Relay
Pulse output 1: 01001 Pulse output 1: 01001
COM COM
Pulse plus direction output
CPM2A
Pulse output 0: 01000
COM
Direction output: 01001
COM
Motor driver
Increment pulse output
CPM2A
Motor driver
CW input
CW* pulse output: 01000
COM
Direction input
CCW input CCW* pulse output: 01001
COM
Note *CW is clockwise and CCW is counter-clockwise.
Output Wiring Precautions Observe the following precautions to protect the PC’s internal components.
Output Short Protection
The output or internal circuitry might be damaged when the load connected to an output is short-circuited, so it is recommended to install a protective fuse in each output circuit.
74
Wiring and Connections Section 3-4
Inductive Loads
When connecting an inductive load to an input, connect a surge protector or diode in parallel with the load.
The surge protector’s components should have the following ratings:
Relay Output
OUT
CPM2A
COM
Surge protector
Relay Output
Transistor Output
(Sinking)
CPM2A
OUT
COM
Diode
Relay Output
Transistor Output
(Sourcing)
CPM2A
OUT
COM
Diode
The diode should satisfy the following requirements:
Peak reverse-breakdown voltage must be at least 3 times the load voltage.
Average rectified current must be 1 A.
Inrush Current Considerations
When switching a load with a high inrush current in the CPM2A relay output or transistor output model, such as an incandescent lamp, suppress the inrush current as shown below.
Countermeasure 1
OUT OUT
Countermeasure 2
R
R
COM COM
Providing a dark current of approx. one-third of the rated value through an incandescent lamp
Providing a limiting resistor
Fuse Insertion
The CPM2A with transistor output may burn if the load is short-circuited, therefore, insert a protective fuse in series to the load.
Crimp Terminals
!
Caution Always use crimp terminals for the CPM2A’s I/O lines or use solid wire (instead of a stranded wire). Do not connect bare stranded wires directly to terminals.
Stray wire strands can short-circuit and cause a fire.
Use M3 crimp terminals and tighten the terminal screws to a torque of 0.5 N S m.
Fork terminal Ring terminal
6.2 mm max.
6.2 mm max.
The recommended wire size for solid wires is 0.4 to 1.2 mm (AWG26 to AWG18).
75
Wiring and Connections Section 3-4
3-4-7 Programming Device Connections
The CPM2A CPU Unit can be connected to a Programming Console or a host computer running SYSMAC Support Software (SSS) or SYSMAC-CPT Support
Software.
Programming Console The CPM2A CPU Unit can be connected to a C200H-PRO27-E Programming
Console with a standard C200H-CN222 (2 m) or C200H-CN422 (4 m) Connecting Cable. The CPM2A CPU Unit can be also connected to a CQM1-PRO01-E.
A 2-m Connecting Cable is attached to the CQM1-PRO01-E.
CQM1-PRO01-E Connection
CPM2A CPU Unit
C200H-PRO27-E Connection
CPM2A CPU Unit
CQM1-PRO01-E
Support Software
Peripheral port
C200H-PRO27-E
Peripheral port
Connecting Cable
C200H-CN222 (2 m)
C200H-CN422 (4 m)
Connect the Programming Console to the CPU Unit’s Peripheral port; a Programming Console cannot be connected to the RS-232C port. The PC will automatically communicate with the Programming Console in Programming Console mode, regardless of the communications method selected on the CPU
Unit’s Communications Switch.
An IBM-compatible personal computer running the SSS or SYSMAC-CPT Support Software can be connected to the CPU Unit’s Peripheral port or RS-232C port. The Peripheral port can operate in Peripheral bus mode or Host Link mode.
The RS-232C port operates in Host Link mode only.
The setting on the CPU Unit’s Communications Switch determines whether the
RS-232C port will operate with the communications settings in the PC Setup or the standard settings, as shown in the following table.
Switch setting
ON
OFF
Communications settings
Peripheral port RS-232C port
Standard settings (The standard settings and PC Setup default settings are Host Link communications at 9,600 bps with 1 start bit, 7-bit data, 2 stop bits, and even parity.)
PC Setup settings in DM 6650 and
DM 6651
PC Setup settings in DM 6645 and
DM 6646
Connect to the Peripheral port when connecting to the PC’s Peripheral bus. The communications mode will be Host Link communications, but the CPM2A will automatically switch to Peripheral bus communications if Peripheral bus has been selected in the Support Software.
76
Wiring and Connections Section 3-4
Using a CQM1-CIF02
CQM1-CIF02
Peripheral Port Connection
A personal computer can be connected to the CPU Unit’s Peripheral port with a
CQM1-CIF01 or CPM1-CIF01 RS-232C Adapter.
CPM2A
Using a CPM1-CIF01
CPM2A
CPM1-CIF01
IBM PC/AT or compatible computer
Peripheral port
IBM PC/AT or compatible computer
Peripheral port
XW2Zj
00S
RS-232C Port Connection
A personal computer can be connected to the CPU Unit’s RS-232C port with an
XW2Zj 00S or XW2Zj 00S-V Connecting Cable.
Using an XW2Zj
00S Cable
CPM2A
Using an XW2Zj
00S-V Cable
CPM2A
XW2Zj
00S XW2Zj
00S-V
IBM PC/AT or compatible computer
RS-232C port
IBM PC/AT or compatible computer
RS-232C port
Note The XW2Zj
00S cables have a D-Sub 25-pin connector and the
XW2Zj 00S-V cables have a D-Sub 9-pin connector.
Support Software
Name
SYSMAC Support
Software
SYSMAC-CPT
Support Software
Model number Comments
C500-ZL3AT1-E For IBM PC/AT or compatible computers
(1.44 MB 3.5-inch floppy disks)
WS01-CPTB1-E For IBM PC/AT or compatible computers
(1.44 MB 3.5-inch floppy disks or CD-ROM)
Cables and Adapters
CPM2A port Cable length Model number
Peripheral 3.3 m CQM1-CIF01
3.3 m +
0.15 m
CPM1-CIF01 +
XW2Z-S001
RS-232C 2 m
5 m
XW2Z-200S
XW2Z-500S
2 m
5 m
Comments
For a 25-pin computer serial port
For a 25-pin computer serial port
XW2Z-200S-V For a 9-pin computer serial port
XW2Z-500S-V
3-4-8 Host Link Connections
Host Link is a command/response communications system in which commands are transmitted from the host computer and corresponding responses are returned from the destination PCs. Host Link commands can be used to read/ write data in PC data areas and read/write PC settings.
One-to-one Host Link
Connection
The CPM2A CPU Unit can be connected to an IBM PC/AT or compatible computer or a Programmable Terminal through the CPU Unit’s Peripheral port or
RS-232C port, as shown in the following diagrams.
77
Wiring and Connections Section 3-4
Peripheral Port Connection
Connect to the CPU Unit’s Peripheral port with a CQM1-CIF01 or CPM1-CIF01
RS-232C Adapter.
Using a CQM1-CIF jj
CQM1-CIF02
CPM2A
Using a CPM1-CIF01
CPM2A
CPM1-CIF01
IBM PC/AT or compatible computer
Peripheral port
IBM PC/AT or compatible computer
Peripheral port
XW2Zj
00S
IBM PC/AT or compatible computer
RS-232C Port Connection
Connect to the CPU Unit’s RS-232C port with an XW2Zj
00S or
XW2Zj
00S-V Connecting Cable.
Using an XW2Zj
00S Cable
CPM2A
XW2Zj
00S
RS-232C port
Using an XW2Zj
00S-V Cable
CPM2A
XW2Zj
00S-V
IBM PC/AT or compatible computer
RS-232C port
Note The XW2Zj 00S cables have a D-Sub 25-pin connector and the
XW2Zj 00S-V cables have a D-Sub 9-pin connector.
Cables and Adapters
CPM2A port Cable length Model number
Peripheral
RS-232C
3.3 m
3.3 m +
0.15 m
2 m
5 m
2 m
5 m
CQM1-CIF02
CPM1-CIF01 +
XW2Z-S001
Comments
For a 25-pin computer serial port
XW2Z-200S
XW2Z-500S
For a 25-pin computer serial port
XW2Z-200S-V For a 9-pin computer serial port
XW2Z-500S-V
Communications Settings
Set the CPU Unit’s Communications Switch to ON when using the standard communications settings 1 . Set the switch to OFF to use the settings in the PC
Setup.
Note The standard settings are: Host Link, 9,600 bps, 7-bit data, 1 start bit, 2 stop bits, and even parity. Refer to Section 1 PC Setup in the Programming Manual
(W353) for details on settings.
78
Wiring and Connections
One-to-N Host Link
Connection
Section 3-4
Up to 32 OMRON PCs, including CPM2A PCs, can be controlled from a host computer. The following diagrams show separate RS-232C port and Peripheral port configurations, but both ports can be used simultaneously.
RS-232C Port Connection
XW2Zj 00S
RS-232C cable
IBM PC/AT or compatible computer
CPM2A
B500-AL004 or NT-AL001 (for +5 V)
(See note 1.)
RS-422A/485 (Total length: 500 m max.)
NT-AL001
RS-232C 2
NT-AL001
RS-232C 2
CPM2A
RS-232C port
CPM2A
RS-232C port
NT-AL001
RS-232C 2
RS-232C port
Up to 32 PCs
Peripheral Port Connection
IBM PC/AT or compatible computer
XW2Zj 00S
RS-232C cable
CPM2A
B500-AL004 or NT-AL001 (for +5 V)
(See note 1.)
RS-422A/485 (Total length: 500 m max.)
CPM1-CIF11
CPM2A
CPM1-CIF11
CPM2A
CPM1-CIF11
Peripheral port Peripheral port
Up to 32 PCs
Peripheral port
Note 1. The NT-AL001 must be supplied externally with 5 VDC.
When an NT-AL001 is connected to a CPM2A PC, pin 6 of the CPM2A’s
RS-232C port supplies +5 VDC and an external power supply is not necessary. When the NT-AL001 is connected to a host computer, it is necessary to supply 5 VDC from an external power supply.
If an NT-AL001 is connected to the CPM2A’s RS-232C port, only one Expansion Unit or Expansion I/O Unit can be connected to the CPU Unit because the NT-AL001 draws its 5-VDC power from the CPU Unit.
2. Use an XW2Z-070T-1 (0.7 m) or XW2Z-200T-1 (2 m) cable to connect the
NT-AL001 to the CPM2A’s RS-232C port.
Cables and Adapters
Name
Link
Adapter
RS-422
Adapter
Function
RS-232C/RS-422 conversion
For host computer connection
(Can be connected to the CPM2A.)
For CPM2A connection
(Can be connected to a host computer, but requires an external
5-VDC power supply.)
Model number
B500-AL004
NT-AL001
79
Wiring and Connections Section 3-4
3-4-9 No-Protocol Communications
The TXD(48) and RXD(47) instructions can be used in no-protocol mode to exchange data with standard serial devices. For example, data can be received from a bar code reader or transmitted to a serial printer. The serial devices can be connected to the RS-232C port or Peripheral port, as shown in the following diagrams.
CPM2A CPU Unit
RS-232C devices
S
Bar code reader
S
Serial printer
S
Other serial device
RS-232C port
CPM1-CIF11
RS-232C Adapter
CPM2A CPU Unit
RS-232C devices
S Bar code reader
S
Serial printer
S Other serial device
Peripheral port
Note Set the CPU Unit’s Communications Switch to OFF to use the settings in the PC
Setup and set the communications mode to no-protocol mode for the port being used. Refer to Section 1 PC Setup in the Programming Manual (W353) for details on settings.
3-4-10 OMRON PT Connections
In a 1:1 NT Link, a CPM2A can be connected directly to a Programmable Terminal. The Programmable Terminal must be connected to the RS-232C port; it cannot be connected to the Peripheral port.
OMRON Programmable Terminal CPM2A CPU Unit
RS-232C Cable
(such as the OMRON
XW2Z-200T (2 m) or
XW2Z-500T (5 m))
RS-232C port
Note Set the CPU Unit’s Communications Switch to OFF to use the settings in the PC
Setup and set the communications mode to a 1:1 NT Link for the RS-232C port.
Refer to Section 1 PC Setup in the Programming Manual (W353) for details on settings.
80
Wiring and Connections Section 3-4
3-4-11 One-to-one PC Link Connections
A CPM2A can be linked to another CPM2A, a CQM1, CPM1, CPM1A, CPM2C,
SRM1 or a C200HS or C200HX/HE/HG PC. The PC must be connected through the RS-232C port; it cannot be connected through the Peripheral port.
In a 1:1 PC connection, one PC is specified as the Master in its PC Setup and the other as the Slave in its PC Setup.
CPM2A CPU Unit CPM2A CPU Unit
1:1 PC
Link
Master
1:1 PC
Link
Slave
RS-232C port RS-232C port
RS-232C Cable
(such as the OMRON
XW2Z-200T (2 m) or
XW2Z-500T (5 m))
OMRON PC (CQM1, CPM1,
CPM1A, CPM2C, SRM1(-V2),
C200HS, or C200HX/HE/HG)
OMRON PC (CQM1, CPM1,
CPM1A, CPM2C, SRM1(-V2),
C200HS, or C200HX/HE/HG)
Note Set the CPU Unit’s Communications Switch to OFF to use the settings in the PC
Setup and set the RS-232C port communications mode to 1:1 PC Link Master in one PC and 1:1 PC Link Slave in the other PC. Refer to Section 1 PC Setup in the
Programming Manual (W353) for details on settings.
3-4-12 CompoBus/S I/O Link Connections
A CompoBus/S I/O Link can be used to create an I/O link (remote I/O) of 8 input points and 8 output points with a CompoBus/S Master Unit or SRM1 PC. The connection is made through a CompoBus/S I/O Link Unit.
From the standpoint of the CPM2A CPU Unit, the area allocated to the Compo-
Bus/S I/O Link Unit can be treated just like the area allocated to an Expansion I/O
Unit. The difference is that the bits are not actual I/O points, but I/O bits in the
Master Unit.
CompoBus/S Master Unit (or SRM1 PC)
C200HX/HG/HE PC
CPM2A CPU Unit CompoBus/S I/O Link Unit
(Slave)
Cables
Use special flat cable or VCTF cable to connect the nodes in the CompoBus/S
81
Wiring and Connections Section 3-4
I/O Link. (Special flat cables and VCTF cables cannot be combined in the same system.)
Name
Flat cable
VCTF cable
Specifications
4-core flat cable, 0.75 mm
2
2-core x 0.75 mm 2
82
SECTION 4
Using Programming Devices
This section outlines the operations possible with the SYSMAC-CPT, SYSMAC Support Software (SSS) and the Programming Consoles. Actual SYSMAC-CPT operating procedures are provided in the SYSMAC-CPT User Manual. Actual SSS operating procedures are provided in the SSS Operation Manuals: Basics and C-series PCs. Operations for the
WS02-CXPC1-E CX-Programmer are provided in the WS02-CXPC1-E CX-Programmer User Manual (W361) and the CX-Server User Manual (W362).
Refer to 3-4-7 Programming Device Connections and 4-3-3 Connecting the Programming Console for details on connecting a
Programming Console or personal computer to the CPM2A.
4-1 SYSMAC-CPT Support Software
4-1-1 Introduction
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1-2 Limitations and Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1-3 Using the SYSMAC-CPT Support Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 SYSMAC Support Software (SSS)
4-2-1 Introduction
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-2 Limitations and Precautions
4-3 Using a Programming Console
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3-1 Compatible Programming Consoles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3-2 Changing the CPM2A’s Mode with the Mode Switch . . . . . . . . . . . . . . . . . . . . . .
4-3-3 Connecting the Programming Console
4-3-4 Preparation for Operation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3-5 Entering the Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4 Programming Console Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-2 Clearing Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-3 Reading/Clearing Error Messages
4-4-4 Buzzer Operation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-5 Assigning Expansion Instruction Function Codes . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-6 Setting and Reading a Program Memory Address and Monitoring I/O Bit Status
4-4-7 Entering or Editing Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-8 Instruction Search
4-4-9 Bit Operand Search
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-10 Inserting and Deleting Instructions
4-4-11 Checking the Program
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-12 Bit, Digit, Word Monitor
4-4-13 Differentiation Monitor
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-14 Binary Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-15 Three-Word Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-16 Signed Decimal Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-17 Unsigned Decimal Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-18 Three-Word Data Modification
4-4-19 Changing Timer, Counter SV
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-20 Hexadecimal, BCD Data Modification
4-4-21 Binary Data Modification
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-22 Signed Decimal Data Modification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-23 Unsigned Decimal Data Modification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-24 Force Set, Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-25 Clear Force Set/Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-26 Hex-ASCII Display Change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-27 Displaying the Cycle Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-28 Reading and Setting the Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5 Programming Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5-1 Preparatory Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5-2 Example Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5-3 Programming Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5-4 Checking the Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5-5 Test Run in MONITOR Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
122
122
123
123
124
124
125
126
129
129
116
117
118
119
119
120
121
111
113
114
115
115
116
105
105
108
109
110
111
99
101
101
102
103
103
104
92
95
95
97
98
99
84
84
84
86
92
92
83
SYSMAC-CPT Support Software Section 4-1
4-1 SYSMAC-CPT Support Software
4-1-1 Introduction
The SYSMAC-CPT Support Software is a complete programming and control package. It provides not only programming capabilities, but also advanced debugging, monitoring, and program/data management. The software is compatible with Windows 3.1, Windows 95, Windows 98, and Windows NT 3.5/4.0.
Any version of the SYSMAC-CPT Support Software can be used to program
CPM2A PCs with the limitations described later in this section. For further information and actual operating procedures, please refer to the SYSMAC-CPT
Support Software Quick Start Guide (W332) and User Manual (W333).
Refer to 3-4-7 Programming Device Connections for details on connecting a personal computer to the CPM2A.
4-1-2 Limitations and Precautions
When programming a CPM2A PC with the SYSMAC-CPT Support Software, set the PC model to “CQM1” and the CPU model to “CPU43.” There are some software limitations because of differences between the CPM2A and CQM1-CPU43
CPUs.
Program Input and
Program Check
CQM1 data areas are larger than the corresponding CPM2A data areas, so the data area addresses that don’t actually exist in the CPM2A or instructions not supported by the CPM2A can be input and won’t be detected in the program check. Be sure that the word and bit addresses are within the specified ranges and that all instructions are supported.
If a program contains a data area address that exceeds the range of a CPM2A data area, a memory error will be generated when the program is executed and the Memory Area Specification Error Flag (AR 1308) will be turned ON.
Data area
Input words
Output words
Work words and dedicated words
SR area
CQM1 range
IR 000 to IR 011
IR 100 to IR 111
IR 012 to IR 099
CPM2A range
IR 000 to IR 009
IR 010 to IR 019
IR 020 to IR 049/IR 200 to IR 227
(IR 050 to IR 199 cannot be used.)
SR 228 to SR 255 SR 244 to SR 255
HR area
AR area
HR 00 to HR 99
AR 00 to AR 27
HR 00 to HR 19
(HR 20 to HR 99 cannot be used.)
AR 00 to AR 23
(AR 24 to AR 27 cannot be used.)
LR area LR 00 to LR 63 LR 00 to LR 15
(LR 16 to LR 63 cannot be used.)
Timer/Counter area
DM area
Read/write
TIM/CNT 000 to 511 TIM/CNT 000 to 255
(TIM/CNT 256 to 511 cannot be used.)
DM 0000 to DM 6143 DM 0000 to DM 1999,
DM 2022 to DM 2047
(DM 2048 to DM 6143 cannot be used.)
Read-only DM 6144 to DM 6568 DM 6144 to DM 6599
Error Log DM 6569 to DM 6599 DM 2000 to DM 2021
PC Setup DM 6600 to DM 6655 DM 6600 to DM 6655
Monitoring, Online
Editing, and Set Values
Available Program
Memory
An error message will be displayed and the values will not be accepted if a data area address that exceeds the range of a CPM2A data area is entered for monitoring, an instruction operand, or a timer/counter SV.
The program capacity of the CQM1 (7,200 words) is greater than that of the
CPM2A (4,096 words), and so the display will show more free space than is actually available. Be sure to keep the actual program capacity in mind while programming.
84
SYSMAC-CPT Support Software
Program Transfer
Expansion Instructions
Error Log
PC Setup
Section 4-1
When the program is transferred from the PC to the CPT with the default function code assignments, FUN18, FUN19, FUN87, and FUN88 will be displayed as
TKY, MCMP, DSW, and 7SEG. The instructions, however, will be transferred correctly.
An error will occur if any instructions not supported by the CPT are transferred from the CPM2A.
When the program is transferred from the CPT to the PC, TKY, MCMP, DSW, and 7SEG will be displayed on the CPT, but will not be executed in the CPU Unit.
They will be treated as NOP.
If expansion instructions are transferred to the PC with DM 6602 is set to the “default settings” or if instructions not supported by the CPM2A are transferred to the PC, a message saying that expansion instructions cannot be written because DIP switch pin 4 is OFF will be displayed. Change the setting of DM 6602 to enable user settings to use expansion instructions.
It will not be possible to transfer the program if the function codes assigned to expansion instructions (18 instructions) have been changed from their default settings. A message to turn ON the DIP switch of the PC and execute again will be displayed. Change the function code assignments to the CQM1 defaults shown in the following table before programming.
67
68
69
87
63
64
65
66
88
89
47
48
60
61
62
Function code Default CPM2A Assignments Default CQM1 Assignments
17 ASFT ASFT
18
19
---
---
TKY
MCMP
RXD
TXD
CMPL
INI
PRV
RXD
TXD
CMPL
INI
PRV
CTBL
SPED
PULS
SCL
BCNT
BCMP
STIM
---
---
INT
CTBL
SPED
PULS
SCL
BCNT
BCMP
STIM
DSW
7SEG
INT
There are four CPM2A instructions (STUP(––), SYNC(––), TIML(––), and
TMHH(––)) that are not supported by the CQM1 and cannot be used. If one of these instructions is used in the program, an error will occur when the program is transferred from the PC to the computer.
The input word for the frequency for PWM must be between IR 000 and IR 049, or between IR 200 and IR 252.
If a CQM1 instruction that is not supported by the CPM2A is used in the program, an error will occur when the program is transferred from the computer to the PC.
The error log cannot be displayed. If data has been written to DM 6569 to
DM 6599, however, this data will be incorrectly displayed as the error log. Do not use the information that is displayed.
Some of the CPM2A’s PC Setup settings are different from those in the CQM1, so not all settings can be made from the menus. These settings have to be made by writing data directly to the word containing the setting.
85
SYSMAC-CPT Support Software Section 4-1
4-1-3 Using the SYSMAC-CPT Support Software
This section shows how to perform basic SYSMAC-CPT Support Software operations with the CPM2A PC. (The software is operating in a Windows 95 environment in these examples.)
Starting the Software The SYSMAC-CPT Support Software is a Windows 3.1/Windows 95 application. Refer to the SYSMAC-CPT Support Software User Manual (W333) for details on computer requirements and the software installation procedure.
1, 2, 3...
1. Select “Programs (P)” from the Start Menu, “SYSMAC-CPT,” and then
“SYSMAC-CPT” to start the software.
2. Read the notes provided in the startup messages and click “OK.”
3. The SYSMAC-CPT Support Software will start.
86
Note To exit from the SYSMAC-CPT Support Software, select “File (F)” from the menu bar and “Exit (X)” from the File menu.
SYSMAC-CPT Support Software Section 4-1
Creating a New Project Follow this procedure when using SYSMAC-CPT Support Software for the first time or creating a new project. Specify the PC model and CPU version of the PC being used.
1, 2, 3...
1. Select “File (F)” from the menu bar and “New (N)” from the File menu.
2. Input the name of the new project, set the PC model to “CQM1,” set the CPU version to “CPU43,” and click “OK.” a) Input the project name.
d) Click OK.
b) Set the PC model to CQM1.
c) Set the PC model to CQM1.
3. The new project’s ladder diagram will be displayed.
87
SYSMAC-CPT Support Software
Writing and Editing the
Ladder Program
Section 4-1
The SYSMAC-CPT Support Software can display programs in ladder-diagram format or mnemonic format. To switch the display/editing format, select
“View (V)” from the menu bar, “Program editor (P),” and then “Ladder (L)” or
“Mnemonic (M).”
Ladder-diagram format Mnemonic format
Transferring the Program There are three steps involved in transferring the program.
•
Connect the CPM2A with the computer in which the SYSMAC-CPT Support
Software has been installed.
•
Switch the SYSMAC-CPT Support Software to online operation.
•
Transfer the program.
88
SYSMAC-CPT Support Software Section 4-1
Connecting the CPM2A with the Computer
Securely insert the computer Connecting Cable to the CPM2A’s peripheral port and then turn on the CPM2A’s power supply.
IBM PC/AT or compatible personal computer
CPM2A CPU Unit
Connecting Cable
S
CQM1-CIF01
( 25-pin D-Sub Connector)
S
CQM1-CIF02
(9 -pin D-Sub Connector)
Operating Modes
If power is turned ON to the CPM2A without anything connected to the peripheral port, the CPM2A will start operation in RUN mode. If operation starts in RUN mode when power is turned ON even though a Connecting Cable is correctly connected to the peripheral port, check the settings in the PC Setup in the
CPM2A.
The CMP2A has three operating modes: PROGRAM, MONITOR, and RUN.
When the CPT is offline, the CPM2A will operate in PROGRAM mode. When the
CPT is online, the CPM2A operating mode can be controlled from the CPT.
PROGRAM Mode
The CPM2A program isn’t executed in PROGRAM mode. Use PROGRAM mode to create and edit the program, clear memory, or check the program for errors.
MONITOR Mode
The CPM2A program is executed in MONITOR mode and I/O is processed just as it is in RUN mode. Use MONITOR mode to test system operations, such as monitoring CPM2A operating status, force-setting and resetting I/O bits, changing the SV/PV of timers and counters, changing word data, and online editing.
RUN Mode
This is the CPM2A’s normal operating mode. The CPM2A’s operating status can be monitored from a Programming Device, but bits can’t be force-set/force-reset and the SV/PV of timers and counters can’t be changed.
89
SYSMAC-CPT Support Software Section 4-1
Switching to Online Operation
The SYSMAC-CPT Support Software must make an online connection in order to communicate with the CPM2A, transfer the program, or change the CPM2A’s operating mode.
1, 2, 3...
1. Select “Online (O)” from the menu bar and “Go online (G)” from the Online menu.
90
2. A confirmation message will be displayed. Click “OK” to go online.
Cancel
3. The ladder-diagram display will change to indicate the online connection.
Changes to “Program,” showing the PC’s operating mode.
SYSMAC-CPT Support Software Section 4-1
Transferring the Program
Use the following procedure to transfer a program to the PC.
Before attempting to transfer the program, make sure that the SYSMAC-CPT
Support Software is online and that the CPM2A is in PROGRAM mode. The program cannot be transferred unless the PC is in PROGRAM mode.
1, 2, 3...
1. Check that the PC is in PROGRAM mode, select “Online (O)” from the menu bar, and “Transfer (Computer
→
PC (T))” from the Online menu.
M ake sure that the CPM2A is in PROGRAM mode before attempting to transfer the program.
2. Select “Program” and click “Transfer (Computer
→
PC)” to begin transfer the program.
a) Select “Program.” b) Click to begin the program transfer.
Checking Operation in MONITOR Mode
Use the following procedure to switch the CPM2A to MONITOR mode.
1, 2, 3...
1. Make sure that the SYSMAC-CPT Support Software is online. Select “Online (O)” from the menu bar, select “Mode (M),” and then “MONITOR (M).”
2. A confirmation message will be displayed. Click “OK” to switch to MONITOR mode.
Cancel
91
SYSMAC Support Software (SSS) Section 4-2
Starting Operation in RUN Mode
Use the following procedure to switch the CPM2A to RUN mode.
1, 2, 3...
1. Make sure that the SYSMAC-CPT Support Software is online. Select “Online (O)” from the menu bar, select “Mode (M),” and then “RUN (R).”
2. A confirmation message will be displayed. Click “OK” to switch to RUN mode.
Cancel
4-2 SYSMAC Support Software (SSS)
4-2-1 Introduction
The SSS is a complete programming and control package designed for C-series and CVM1 PCs. It provides not only programming capabilities, but also advanced debugging, monitoring, and program/data management. For further information and actual operating procedures, please refer to the SYSMAC Sup-
port Software Operation Manuals: Basics and C-series.
CPM2A programming can be performed with any version of the SSS.
Refer to 3-4-7 Programming Device Connections for details on connecting a personal computer to the CPM2A.
4-2-2 Limitations and Precautions
When programming a CPM2A PC with the SSS, set the PC model to “CQM1.”
There are some software limitations because of differences between the
CPM2A and CQM1 CPUs.
CQM1
A: CVM1-CPU21
K: CQM1
Program Input and
Program Check
CQM1 data areas are larger than the corresponding CPM2A data areas, so the data area addresses that don’t actually exist in the CPM2A or instructions not supported by the CPM2A can be input and won’t be detected in the program check. Be sure that the word and bit addresses are within the specified ranges and that all instructions are supported.
92
SYSMAC Support Software (SSS) Section 4-2
If a program contains a data area address that exceeds the range of a CPM2A data area, a memory error will be generated when the program is executed and the Memory Area Specification Error Flag (AR 1308) will be turned ON.
Data area
Input words
Output words
Work words
CQM1 range
IR 000 to IR 011
IR 100 to IR 111
IR 012 to IR 099
CPM2A range
IR 000 to IR 009
IR 010 to IR 019
IR 020 to IR 049/IR 200 to IR 227
(IR 050 to IR 199 cannot be used.)
SR 228 to SR 255 SR area SR 244 to SR 255
HR area
AR area
HR 00 to HR 99
AR 00 to AR 27
HR 00 to HR 19
(HR 20 to HR 99 cannot be used.)
AR 00 to AR 23
(AR 24 to AR 27 cannot be used.)
LR area LR 00 to LR 63 LR 00 to LR 15
(LR 16 to LR 63 cannot be used.)
Timer/Counter area
DM area
Read/write
TIM/CNT 000 to 511 TIM/CNT 000 to 255
(TIM/CNT 256 to 511 cannot be used.)
DM 0000 to DM 6143 DM 0000 to DM 1999,
DM 2022 to DM 2047
(DM 2048 to DM 6143 cannot be used.)
Read-only DM 6144 to DM 6568 DM 6144 to DM 6599
Error Log DM 6569 to DM 6599 DM 2000 to DM 2021
PC Setup DM 6600 to DM 6655 DM 6600 to DM 6655
Monitoring, Online
Editing, and Set Values
Transferring and
Verifying DM Area Data
Available Program
Memory
Program Transfer
An error message will be displayed and the values will not be accepted if a data area address that exceeds the range of a CPM2A data area is entered for monitoring, time charts, an instruction operand, or a timer/counter SV.
DM Area addresses not supported by the CPM2A cannot be transferred or monitored. DM 1024 to DM 6143 are not checked for DM Area verification.
Since the program capacity of the CQM1 (7,200 words) is greater than that of the
CPM2A (4,096 words), the display will show more free space than is actually available. Be sure to keep the actual program capacity in mind while programming.
When the program is transferred from the PC to the SSS with the default function code assignments, FUN18, FUN19, FUN87, and FUN88 will be displayed as
TKY, MCMP, DSW, and 7SEG. The instructions, however, will be transferred correctly.
“???” will be displayed if any instructions not supported by the SSS are transferred from the CPM2A. Mnemonics will be displayed, however, if any have been defined for the specified function code.
When the program is transferred from the SSS to the PC, TKY, MCMP, DSW, and 7SEG will be displayed on the SSS, but will not be executed in the CPU Unit.
They will be treated as NOP.
If expansion instructions are transferred to the PC with DM 6602 is set to the “default settings,” a message saying that expansion instructions cannot be written because DIP switch pin 4 is OFF will be displayed. Change the setting of
DM 6602 to enable user settings to use expansion instructions. If instructions not supported by the CPM2A are transferred to the PC, a message saying to set expansion instructions will be displayed, and transfer will not be possible.
93
SYSMAC Support Software (SSS) Section 4-2
Expansion Instructions It will not be possible to transfer the program if the function codes assigned to expansion instructions have been changed from their default settings. A message to turn ON the DIP switch of the PC and execute again will be displayed.
Change the function code assignments to the CQM1 defaults shown in the following table before programming.
66
67
68
62
63
64
65
69
87
88
89
47
48
60
61
Function code Default CPM2A Assignments Default CQM1 Assignments
17 ASFT ASFT
18
19
---
---
TKY
MCMP
RXD
TXD
CMPL
INI
RXD
TXD
CMPL
INI
PRV
CTBL
SPED
PULS
SCL
BCNT
BCMP
STIM
---
---
INT
PRV
CTBL
SPED
PULS
SCL
BCNT
BCMP
STIM
DSW
7SEG
INT
If a CQM1 instruction that is not supported by the CPM2A is used in the program, an error will occur when the program is transferred from the computer to the PC.
There are four CPM2A instructions (STUP(––), SYNC(––), TIML(––), and
TMHH(––)) that are not supported by the CQM1. These instructions can be used by transferring the expansion instructions from the CPM2A to the SSS. This procedure is outlined below.
1, 2, 3...
1. Select “Transfer Instr” from the “Utility” menu.
PC Setup
94
2. Confirm the transfer by pressing “Y” when the confirmation pop-up is displayed.
3. The “Utility” menu will be displayed again when the transfer is completed.
Since some of the CPM2A’s PC Setup settings are different from those in the
CQM1, not all settings can be made from the menus. These settings have to be made by writing data directly to the word containing the setting.
Using a Programming Console Section 4-3
4-3 Using a Programming Console
This section provides information on connecting and using a Programming Console. Refer to 5-3 Programming Console Operation Errors for details on errors that might occur during Programming Console operations.
4-3-1 Compatible Programming Consoles
There are two Programming Consoles that can be used with the CPM2A: The
CQM1-PRO01-E and the C200H-PRO27-E. The key functions for these Programming Consoles are identical.
Press and hold the Shift Key to input a letter shown in the upper-left corner of the key or the upper function of a key that has two functions. For example, the
CQM1-PRO01-E’s AR/HR Key can specify either the AR or HR Area; press and release the Shift Key and then press the AR/HR Key to specify the AR Area.
CQM1-PRO01-E
Attached Connecting
Cable (2 m)
LCD display
Mode switch
Operation keys
C200H-PRO27-E
LCD display
Mode switch
Operation keys
Cassette recorded jack
(Cannot be used with the CPM2A).
Connecting Cables
C200H-CN222 (2 m)
C200H-CN422 (4 m)
95
Using a Programming Console
Different Keys
Section 4-3
The following keys are labeled differently on the CQM1-PRO01-E and the
C200H-PRO27-E, but the operation of the keys in each pair is identical.
C200H-PRO27-E Keys CQM1-PRO01-E Keys
AR
HR
HR
SET
PLAY
SET
RESET
REC
RESET
Note To specify the AR area, use SHIFT and HR Keys for the C200H-PRO27-E and use SHIFT and AR/HR Keys for the CQM1-PRO01-E.
A shift symbol will be displayed in the upper-right corner of the screen when the
Shift Key is pressed. The shift input can be cleared by pressing the Shift Key again.
SHIFT
^ Shift input symbol
Mode Switch
Contrast Control
The mode switch controls the CPM2A’s operating mode. The key can be removed when the switch is set to RUN or MONITOR but it cannot be removed when the switch is set to PROGRAM.
The display contrast can be adjusted with the control on the right side of the Programming Console.
Contrast control
Buzzer Volume The C200H-PRO27-E’s buzzer volume can be adjusted with the lever on the right side of the Programming Console. The CQM1-PRO01-E’s buzzer volume cannot be adjusted.
Low volume
High volume
C200H-PRO27-E
Note The buzzer volume can be turned on and off with a key operation. See 4-4-4
Buzzer Operation for details.
96
Using a Programming Console Section 4-3
4-3-2 Changing the CPM2A’s Mode with the Mode Switch
Once the Programming Console has been connected, its mode switch can be used to change the CPM2A’s operating mode. The mode display (<PRO-
GRAM>, <MONITOR>, or <RUN>) will appear on the Programming Console screen.
•
No key operations can be performed while the mode display is displayed on the Programming Console screen. Press CLR to clear the display so that key operations can be performed.
•
If the SHIFT Key is pressed while the mode switch is turned, the original display will remain on the Programming Console’s screen and the mode display won’t appear.
•
The CPM2A will enter RUN mode automatically if a Programming Console isn’t connected when the CPM2A is turned on.
MONITOR
RUN PROGRAM
MONITOR
RUN PROGRAM
MONITOR
RUN PROGRAM
Mode display
<PROGRAM> BZ <MONITOR> BZ <RUN> BZ
CLR
Operation
Initial display
00000
Operation
SHIFT CLR
Operating Modes
PROGRAM Mode
The CPM2A program isn’t executed in PROGRAM mode. Use PROGRAM mode to create and edit the program, clear memory, or check the program for errors.
MONITOR Mode
The CPM2A program is executed in MONITOR mode and I/O is processed just as it is in RUN mode. Use MONITOR mode to test system operations, such as monitoring CPM2A operating status, force-setting and resetting I/O bits, changing the SV/PV of timers and counters, changing word data, and online editing.
RUN Mode
This is the CPM2A’s normal operating mode. The CPM2A’s operating status can be monitored from a Programming Device, but bits can’t be force-set/force-reset and the SV/PV of timers and counters can’t be changed.
!
Caution Check the system thoroughly before changing the operating mode of the PC to prevent any accidents that might occur when the program is first started.
!
Caution Never change the mode while pressing any of the keys.
97
Using a Programming Console Section 4-3
Startup Operating Mode The operating mode of the CPM2A when the power is turned ON depends upon the PC Setup setting in DM 6600 and the Programming Console’s mode switch setting if the Programming Console is connected.
PC Setup setting
(DM 6600)
0000
0100
0200
0201
0202
Programming
Console connected
The startup mode determined by the mode switch setting.
Programming Console not connected
RUN mode if no Programming Device is connected. PROGRAM mode if another Programming Device is connected.
The startup mode is the same as the operating mode before power was interrupted.
PROGRAM mode
MONITOR mode
RUN mode
Note The default setting is 0000. If a Programming Console is not connected, the PC will automatically enter RUN mode. Be sure that it is safe for the PC to operate before turning on the PC without a Programming Console connected.
4-3-3 Connecting the Programming Console
Connect the Programming Console’s connecting cable to the CPM2A’s peripheral port, as shown below.
Panel Installation The C200H-PRO27-E Programming Console can be installed in a control panel as shown in the following diagram. (The C200H-ATT01 Mounting Bracket is sold separately.)
Mounting hole dimensions
(DIN43700 standards) Mounting Bracket
Two screws
186
+1.1
–0
Panel thickness: 1.0 to 3.2 mm 92
+0.8
–0
98
Using a Programming Console Section 4-3
Allow at least 80 mm for the cable connector above the Programming Console.
37
15
At least 80 mm is required.
Either connector may be used.
About 70 mm is required.
4-3-4 Preparation for Operation
This section describes the procedures required to begin Programming Console operation when using the Programming Console for the first time.
!
Caution Always confirm that the Programming Console is in PROGRAM mode when turning ON the PC with a Programming Console connected unless another mode is desired for a specific purpose. If the Programming Console is in RUN mode when PC power is turned ON, any program in Program Memory will be executed, possibly causing a PC-controlled system to begin operation.
The following sequence of operations must be performed before beginning initial program input.
1, 2, 3...
1. Be sure that the PC is OFF.
2. Connect the Programming Console to the CPU Unit’s peripheral port. See
4-3-3 Connecting the Programming Console for details.
(The CPU Unit’s Communications Switch setting has no effect on communications with the Programming Console.)
3. Set the mode switch to PROGRAM mode.
4. Turn ON the PC.
5. Enter the password. See 4-3-5 Entering the Password for details.
6. Clear (All Clear) the PC’s memory. See 4-4-2 Clearing Memory for details.
7. Read and clear all errors and messages. See 4-4-3 Reading/Clearing Error
Messages for details.
8. Start programming.
4-3-5 Entering the Password
To gain access to the PC’s programming functions, you must first enter the password. The password prevents unauthorized access to the program.
The PC prompts you for a password when PC power is turned on or, if PC power is already on, after the Programming Console has been connected to the PC. To gain access to the system when the “Password!” message appears, press CLR and then MONTR. Then press CLR to clear the display.
99
Using a Programming Console Section 4-3
If the Programming Console is connected to the PC when PC power is already on, the first display below will indicate the mode the PC was in before the Programming Console was connected. Ensure that the PC is in PROGRAM mode
before you enter the password. When the password is entered, the PC will shift to the mode set on the mode switch, causing PC operation to begin if the mode is set to RUN or MONITOR. The mode can be changed to RUN or MON-
ITOR with the mode switch after entering the password.
<PROGRAM>
PASSWORD!
<PROGRAM> BZ
Indicates the mode set by the mode selector switch.
100
Programming Console Operations
4-4 Programming Console Operations
Section 4-4
4-4-1 Overview
The following table lists the programming and monitoring operations that can be performed from a Programming Console. Refer to the rest of this section for details on operational procedures.
Name
Clearing memory
Reading/clearing error messages
Buzzer operation
Function
Clears all or part of the Program Memory and any data areas that are not read-only, as well as the contents of the Programming Console’s memory.
Displays and clears error messages and displays MESSAGE instruction messages.
Turns on and off the buzzer that sounds when Programming Console keys are pressed.
Reads or changes the function codes assigned to expansion instructions Assigning expansion instruction function codes
Setting a program memory address
Reading a program memory address
Instruction search
Sets the specified program memory address when reading, writing, inserting and deleting programs.
Reads the contents of the Program Memory. Displays the status of the currently displayed bit in PROGRAM and MONITOR modes.
Finds occurrences of the specified instruction in the program.
Bit operand search
Inserting and deleting instructions
Finds occurrences of the specified operand bit in the program.
Inserts or deletes instructions from the program.
Entering or editing programs Overwrites the contents of the current Program Memory to either input a program for the first time or to change a program that already exists.
Checking the program Checks for programming errors and displays the program address and error when errors are found.
Bit, digit, word monitor
Multiple address monitor
Monitors the status of up to 16 bits and words, although only 3 can be shown on the display at one time.
Monitors the status of up to 6 bits and words simultaneously.
Differentiation monitor
Binary monitor
3-word monitor
Signed decimal monitor
Unsigned decimal data modification
Monitors the up or down differentiation status of a particular bit.
Monitors the ON/OFF status of any word’s 16 bits.
Monitors the status of three consecutive words.
Converts the contents of the specified word from signed hexadecimal
(two’s complement format) to signed decimal for display.
Converts hexadecimal data in a word to unsigned decimal for display.
Unsigned decimal monitor
3-word data modification Changes the contents of one or more of the 3 consecutive words displayed in the 3-Word Monitor operation.
Changing timer, counter SV 1 Changes the SV of a timer or counter.
Changing timer, counter SV 2 Makes fine adjustment changes to the SV of the timer or counter.
Changes the BCD or hexadecimal value of a word being monitored.
Hexadecimal, BCD data modification
Binary data modification
Signed decimal data modification
Changes the status of a word’s bits when the word is being monitored.
Changes the decimal value of a word being monitored as signed decimal data, within a range of –32,768 to 32,767. The contents of the specified word are converted automatically to signed hexadecimal (two’s complement format.)
Changes the decimal value of a word being monitored as unsigned decimal data, within a range of 0 to 65,535. A change into hexadecimal data is made automatically.
Force set/reset
Clear force set/reset
Hex-ASCII display change
Forces bits ON (force set) or OFF (force reset.)
Restores the status of all bits which have been force set of reset.
Converts word data displays back and forth between 4-digit hexadecimal data and ASCII.
Page
102
103
103
104
105
105
108
109
110
105
111
111
113
113
114
115
115
116
116
117
118
118
119
119
120
121
122
122
101
Programming Console Operations Section 4-4
Name Function
Displaying the cycle time Displays the current average cycle time (scan time.)
Reading and setting the clock Reads or sets the internal clock.
Page
123
123
4-4-2 Clearing Memory
This operation is used to clear all or part of the Program Memory and data areas, as well as the contents of the Programming Console’s memory. This operation is possible in PROGRAM mode only.
No
RUN
No
MONITOR
OK
PROGRAM
All Clear
Before beginning to program for the first time or when installing a new program, clear all areas.
The following procedure is used to clear memory completely, including the program, all data areas, counter PVs, Data Memory, and the PC Setup (DM 6600 to
DM 6655).
1, 2, 3...
1. Bring up the initial display by pressing the CLR Key repeatedly.
2. Press the SET, NOT, and then the RESET Key to begin the operation.
SET NOT RESET
00000MEMORY CLR?
HR CNT DM
3. Press the MONTR Key to clear memory completely.
MONTR
00000MEMORY CLR
END HR CNT DM
!
Caution The PC Setup (DM 6600 through DM 6655) will be cleared when this operation is performed.
Partial Clear It is possible to retain the data in specified areas or part of the Program Memory.
To retain the data in the HR, TC, or DM Areas, press the appropriate key after pressing SET, NOT, and RESET. Any data area that still appears on the display will be cleared when the MONTR Key is pressed.
The HR Key is used to specify both the AR and HR Areas, the CNT Key is used to specify the entire timer/counter area, and the DM Key is used to specify the DM
Area.
It is also possible to retain a portion of the Program Memory from the first memory address to a specified address. After designating the data areas to be retained, specify the first Program Memory address to be cleared. For example, input 030 to leave addresses 000 to 029 untouched, but to clear addresses from 030 to the end of Program Memory.
As an example, follow the procedure below to retain the timer/counter area and
Program Memory addresses 000 through 122:
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the SET, NOT, and then the RESET Key to begin the operation.
3. Press the CNT Key to remove the timer/counter area from the data areas shown on the display. (Counter PVs will not be cleared.)
CNT
00000MEMORY CLR?
HR DM
4. Press 123 to specify 123 as the starting program address.
B
1
C
2
D
3
00123MEMORY CLR?
HR DM
102
Programming Console Operations Section 4-4
5. Press the MONTR Key to clear the specified regions of memory.
MONTR
00000MEMORY CLR
END HR DM
4-4-3 Reading/Clearing Error Messages
This operation is used to display and clear error messages. It is possible to display and clear non-fatal errors and MESSAGE instruction messages in any mode, but fatal errors can be cleared in PROGRAM mode only.
OK
RUN
OK
MONITOR
OK
PROGRAM
Key Sequence
Before inputting a new program, any error messages recorded in memory should be cleared. It is assumed here that the causes of any of the errors for which error messages appear have already been taken care of. If the buzzer sounds when an attempt is made to clear an error message, eliminate the cause of the error, and then clear the error message. (Refer to Section 5 Test
Runs and Error Processing for troubleshooting information.)
Follow the procedure below to display and clear messages.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the FUN and then the MONTR Key to begin the operation. If there are no messages, the following display will appear:
ERR/MSG CHK OK
FUN MONTR
If there are messages, the most serious message will be displayed when the
MONTR Key is pressed. Pressing MONTR again will clear the present message and display the next most serious error message. Continue pressing
MONTR until all messages have been cleared. These are some examples of error messages:
A memory error:
MEMORY ERR
MONTR
A system error:
MONTR
SYS FAIL FAL01
A message (displayed with MSG(46)):
MATERIAL USED UP
MONTR
All messages cleared:
MONTR
ERR/MSG CHK OK
4-4-4 Buzzer Operation
This operation is used to turn on and off the buzzer that sounds when Programming Console keys are pressed. This buzzer will also sound whenever an error occurs during PC operation. Buzzer operation for errors is not affected by this setting.
This operation is possible in any mode.
OK
RUN
OK
MONITOR
OK
PROGRAM
103
Programming Console Operations
Key Sequence
Section 4-4
Follow the procedure below to turn the key-input buzzer on and off.
1, 2, 3...
1. Press the CLR, SHIFT, and then the CLR Key to bring up the mode display.
In this case the PC is in PROGRAM mode and the buzzer is ON.
<MONITOR> BZ
CLR SHIFT CLR
2. Press the SHIFT and then the 1 Key to turn off the buzzer.
SHIFT
B
1
<MONITOR>
The buzzer will not sound when “BZ” is not displayed.
3. Press the SHIFT and then the 1 Key again to turn the buzzer back ON.
<MONITOR> BZ
SHIFT
B
1
4-4-5 Assigning Expansion Instruction Function Codes
This operation is used to display or change the expansion instructions assigned to expansion instruction function codes. The assignments can be displayed in any mode, but can be changed in PROGRAM mode only.
Operation
Read assignment OK
Change assignment No
RUN
OK
No
MONITOR
OK
PROGRAM
OK
Assign expansion instruction function codes before inputting the program.
The CPM2A will not operate properly if expansion instructions aren’t assigned correctly. An expansion instruction can be assigned to one function code only.
The PC Setup must be set for user-defined expansion instruction assignments. Set bits 8 to 11 of DM 6602 to 1 and turn the PC’s power off and then on again to enable the new setting.
There is a table on page 85 showing the default function code assignments in the CPM2A.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the EXT Key to display the assignment for the first function code (17).
EXT
INST TBL READ
FUN017:ASFT
3. Press the Up and Down Arrow Keys to scroll through the expansion instruction function codes.
↓
CHG
INST TBL READ
FUN018:FUN
4. Press the CHG Key to assign a different expansion instruction to the selected function code.
INST TBL CHG?
FUN018:FUN ~????
5. Press the Up and Down Arrow Keys to scroll through the expansion instructions that can be assigned to the selected function code.
↓
INST TBL CHG?
FUN018:FUN ~HEX
104
Programming Console Operations Section 4-4
6. Press the WRITE Key to assign the displayed instruction to the function code.
WRITE
INST TBL READ
FUN018:HEX
4-4-6 Setting and Reading a Program Memory Address and Monitoring
I/O Bit Status
This operation is used to display the specified program memory address and is possible in any mode. In the RUN or MONITOR mode, the I/O bit status of bits in the program will be displayed.
OK
RUN
OK
MONITOR
OK
PROGRAM
When inputting a program for the first time, it is generally written to Program
Memory starting from address 000. Because this address appears when the display is cleared, it is not necessary to specify it.
When inputting a program starting from other than 000 or to read or modify a program that already exists in memory, the desired address must be designated.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the desired address. It is not necessary to input leading zeroes.
C
2
A
0
A
0
00200
3. Press the Down Arrow Key.
↓
00200READ OFF
LD 00000
In the RUN or MONITOR mode, ON/OFF status of the bit will be displayed.
Pressing the MONTR Key will change to the I/O monitor display. Bits can be force-set or force-reset from the I/O monitor display. Press the CLR Key to return to I/O bit status monitoring of the initial address.
Note The ON/OFF status of any displayed bit will be shown if the PC is in
RUN or MONITOR mode.
4. Press the Up and Down Arrow Keys to scroll through the program.
↓
00201READ ON
AND 00001
↑
00200READ OFF
LD 00000
4-4-7 Entering or Editing Programs
This operation is used enter or edit programs. It is possible in PROGRAM mode only.
No
RUN
No
MONITOR
OK
PROGRAM
The same procedure is used to either input a program for the first time or to change a program that already exists. In either case, the current contents of
Program Memory is overwritten.
105
Programming Console Operations Section 4-4
The program shown in the following diagram will be entered to demonstrate this operation.
00002
TIM 000
#0123
12.3 s
Address Instruction
00200
00201
LD
TIM
MOV(021)
#0100
LR 10
00202 MOV(021)
00203 ADB(050)
ADB(050)
#0100
#FFF6
DM 0000
IR
Operands
00002
000
#0123
LR
#0100
10
#0100
#FFF6
DM 0000
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Specify the address where the program will begin.
3. Input the address where the program will begin and press the Down Arrow
Key. It is not necessary to input leading zeroes.
C
2
A
0
A
0
↓
00200READ
NOP (000)
4. Input the first instruction and operand.
LD
C
2
WRITE
00200
LD 00002
5. Press the WRITE Key to write the instruction to Program Memory. The next program address will be displayed.
00201READ
NOP (000)
If a mistake was made inputting the instruction, press the Up Arrow Key to return to the previous program address and input the instruction again. The mistaken instruction will be overwritten
To specify the Completion Flag for a timer or counter, press the LD, AND,
OR, or NOT Key followed by the TIM or CNT Key, and then input the timer/ counter number last.
6. Input the second instruction and operand. (In this case it isn’t necessary to enter the timer number, because it’s 000.) Press the WRITE Key to write the instruction to Program Memory.
TIM Timer number WRITE
00201 TIM DATA
#0000
7. Input the second operand (123 to specify 12.3 seconds) and press the
WRITE Key. The next program address will be displayed.
B
1
C
2
D
3 WRITE
00202READ
NOP (000)
If a mistake was made inputting the operand, press the Up Arrow Key to return to display the mistaken operand and input the operand again.
Note a) Counters are input in the same basic way as timers except the
CNT Key is pressed instead of the TIM Key.
b) Timer and counter SVs are input in BCD, so it isn’t necessary to press the CONT/# Key.
106
Programming Console Operations Section 4-4
8. Input the third instruction and its operands. First input the instruction by pressing the FUN Key and then the function code (21 in this case).
FUN
C
2
B
1
00202
MOV (021)
To input the differentiated version of an instruction, press the NOT Key after the function code (FUN 2 1 NOT). The “@” symbol will be displayed next to differentiated instructions. Press the NOT Key again to change back the instruction back to a non-differentiated instruction. The “@” symbol will disappear.
To change an instruction after it has been entered, simply scroll through the program until the desired instruction is displayed and press the NOT Key.
The “@” symbol should be displayed next to the instruction.
9. Press the WRITE Key to write the instruction to Program Memory. The input display for the first operand will be displayed.
WRITE
00202 MOV DATA A
000
•
Writing Hexadecimal, BCD Constant
10. Input the first operand.
The operands of MOV (21) are normally word addresses, but a constant can be input by pressing the CONT/# Key first. When the CONT/# Key is pressed, the display will change to “#0000,” indicating that a constant can be entered.
CONT
#
B
1
A
0
A
0
WRITE
00202 MOV DATA A
#0100
Press the WRITE Key to write the instruction to Program Memory. The input display for the second operand will appear.
00202 MOV DATA B
000
Note The operands of MOV(21) can be word addresses, so the CONT/#
Key must be pressed to input a constant.
•
Writing a Word Address
11. Input the second operand.
*EM
LR
B
1
A
0
00202 MOV DATA B
LR 10
Press the WRITE Key to write the instruction to Program Memory. The next program address will be displayed.
WRITE
00203READ
NOP (000)
Note When the default display value is “000”, a word address can be input immediately without pressing the Shift and CH/# Keys.
12. Input the next instruction.
FUN
F
5
A
0
00203
ADB (050)
Press the WRITE Key to write the instruction to Program Memory.
WRITE
00203 ADB DATA A
000
•
Writing an Unsigned Decimal Number
107
Programming Console Operations Section 4-4
13. The first operand is input as an unsigned integer.
CONT
#
SHIFT TR NOT
00203 ADB DATA A
#00000
Input the value of the operand from 0 to 65535.
C
2
F
5 6
00203 ADB DATA A
#00256
Note If an erroneous input is made, press the CLR Key to restore the status prior to the input. Then enter the correct input.
14. Restore the hexadecimal display.
SHIFT TR
00203 ADB DATA A
#0100
Note If an input is made outside of the permissible range, a buzzer will sound and the hexadecimal display will not be displayed.
WRITE
00203 ADB DATA B
000
15. The second operand is input as a signed integer.
CONT
#
SHIFT TR
00203 ADB DATA B
#+00000
Input the value of the operand from –32,768 to 32,767. Use the SET Key to input a positive number, and use the RESET Key to input a negative number.
RESET
B
1
A
0
00203 ADB DATA B
#Ć00010
Note If an erroneous input is made, press the CLR Key to restore the status prior to the input. Then enter the correct input.
16. Restore the hexadecimal display.
SHIFT TR
00203 ADB DATA B
#FFF6
WRITE
00203 ADB DATA C
000
•
Writing a Word Address (DM 0000)
17. Input the final operand and then press the WRITE Key. (It isn’t necessary to input leading zeroes.)
EM
DM
WRITE
00203 ADB DATA C
DM 0000
00204READ
NOP (000)
4-4-8 Instruction Search
This operation is used to find occurrences of the specified instruction in the program and is possible in any mode.
OK
RUN
OK
MONITOR
OK
PROGRAM
The ON/OFF status of any displayed bit will be shown if the PC is in RUN or
MONITOR mode.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
108
Programming Console Operations Section 4-4
OUT
2. Input the address from which the search will begin and press the Down
Arrow Key. It is not necessary to input leading zeroes.
B
1
A
0
A
0
↓
00100READ
TIM 001
3. Input the instruction to be found and press the SRCH Key. In this case, the search is for OUT 01000.
In this case, the next OUT 01000 instruction is at address 200, as shown below.
B
1
A
0
A
0
A
0 SRCH
00200SRCH
OUT 01000
4. Press the Down Arrow Key to display the instruction’s operands or press the
SRCH Key to search for the next occurrence of the instruction.
5. The search will continue until an END instruction or the end of Program
Memory is reached. In this case, an END instruction was reached at address 397.
Indicates the address of END instruction.
SRCH
00397SRCH
END (001)00.4KW
Indicates the amount used by the user program in units of 0.1 Kwords.
4-4-9 Bit Operand Search
This operation is used to find occurrences of the specified operand bit in the program and is possible in any mode.
OK
RUN
OK
MONITOR
OK
PROGRAM
The ON/OFF status of any displayed bit will be shown if the PC is in RUN or
MONITOR mode.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the operand address. It is not necessary to input leading zeroes.
SHIFT
CONT
#
F
5
00000CONT SRCH
LD 00005
3. Press the SRCH Key to begin the search.
SRCH
00123CONT SRCH
LD 00005
4. Press the SRCH Key to search for the next occurrence of the operand bit.
SRCH
00255CONT SRCH
AND NOT 00005
5. The search will continue until an END instruction or the end of Program
Memory is reached. In this case, an END instruction was reached.
Indicates the address of END instruction.
SRCH
00397CONT SRCH
END (001)00.4KW
Indicates the amount used by the user program in units of 0.1 Kwords.
109
Programming Console Operations Section 4-4
4-4-10 Inserting and Deleting Instructions
This operation is used to insert or delete instructions from the program. It is possible in PROGRAM mode only.
No
RUN
No
MONITOR
OK
PROGRAM
To demonstrate this operation, an IR 00105 NO condition will be inserted at program address 00206 and an IR 00103 NO condition deleted from address
00205, as shown in the following diagram.
Original Program
Address Instruction Operands
00100 00101 00103 00104
01000
00201 00102
Delete
00105
Insert
END(01)
Delete
00205
00206
00207
00208
AND
AND NOT
OUT
END(01)
00103
00104
01000
-
Insert
Insertion
Deletion
Follow the procedure below to insert the IR 00105 NO condition at address
00206.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the address where the NO condition will be inserted and press the
Down Arrow Key. It is not necessary to input leading zeroes.
C
2
A
0 6
↓
00206READ
AND NOT 00104
3. Input the new instruction and press the INS Key.
AND
B
1
A
0
F
5 INS
00206INSERT?
AND 00105
4. Press the Down Arrow Key to insert the new instruction.
↓
00207INSERT END
AND NOT 00104
Note For instructions that require more operands (such as set values), input the operands and then press the WRITE Key.
Follow the procedure below to delete the IR 00103 NO condition at address
00205.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the address where the NO condition will be deleted and press the
Down Arrow Key. It is not necessary to input leading zeroes.
C
2
A
0
F
5
↓
00205READ
AND 00103
3. Press the DEL Key.
DEL
00205DELETE?
AND 00103
4. Press the Up Arrow Key to delete the specified instruction.
If the instruction has more operands, the operands will be deleted automatically with the instruction.
↑
00205 DELETE END
AND 00105
110
Programming Console Operations Section 4-4
After completing the insertion and deletion procedures, use the Up and Down
Arrow Keys to scroll through the program and verify that it has been changed correctly, as shown in the following diagram.
Corrected Program
00100 00101 00105 00104
Address Instruction Operands
01000
00201 00102
END(01)
00205
00206
00207
00208
AND
AND NOT
OUT
END(01)
00105
00104
01000
-
4-4-11 Checking the Program
This operation checks for programming errors and displays the program address and error when errors are found. It is possible in PROGRAM mode only.
No
RUN
No
MONITOR
OK
PROGRAM
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the SRCH Key. An input prompt will appear requesting the desired check level.
SRCH
00000PROG CHK
CHK LBL (0Ć2)?
3. Input the desired check level (0, 1, or 2). The program check will begin when the check level is input, and the first error found will be displayed.
A
0
00178CIRCUIT ERR
OUT 00200
Note Refer to 5-4 Programming Errors for details on check levels and the errors that may be detected when the program is checked.
4. Press the SRCH Key to continue the search. The next error will be displayed. Continue pressing the SRCH Key to continue the search.
The search will continue until an END instruction or the end of Program
Memory is reached. A display like this will appear if the end of Program
Memory is reached:
SRCH
00300NO END INST
END
A display like this will appear if an END instruction is reached:
SRCH
00310PROG CHK
END (001)00.3KW
No more errors exist if the END instruction is displayed.
If errors are displayed, edit the program to correct the errors and check the program again. Continue checking the program by pressing the SRCH Key again until all errors have been corrected.
4-4-12 Bit, Digit, Word Monitor
This operation is used to monitor the status of up to 16 bits and words, although only 3 can be shown on the display at any one time. Operation is possible in any mode.
111
Programming Console Operations Section 4-4
OK
RUN
OK
MONITOR
OK
PROGRAM
Program Read then Monitor When a program address is being displayed, the status of the bit or word in that address can be monitored by pressing the MONTR Key.
Bit Monitor
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the desired program address and press the Down Arrow Key.
C
2
A
0
A
0
↓
00200READ
TIM 000
3. Press the MONTR Key to begin monitoring.
MONTR
T000
1234
If the status of a bit is being monitored, that bit’s status can be changed using the Force Set/Reset operation. Refer to 4-4-24 Force Set, Reset for details.
If the status of a word is being monitored, that word’s value can be changed using the Hexadecimal/BCD Data Modification operation. Refer to 4-3-19
Hexadecimal, BCD Data Modification, 4-3-20 Binary Data Modification,
4-3-21 Signed Decimal Data Modification, and 4-3-22 Unsigned Decimal
Data Modification for details.
4. Press the CLR Key to end monitoring.
CLR
00200
TIM 000
Follow the procedure below to monitor the status of a particular bit.
Word Monitor
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the bit address of the desired bit and press the MONTR Key.
SHIFT
CONT
#
B
1 MONTR
00001
^ ON
The Up or Down Arrow Key can be pressed to display the status of the previous or next bit.
The displayed bit’s status can be changed using the Force Set/Reset operation. Refer to 4-4-24 Force Set, Reset for details.
3. Press the CLR Key to end monitoring.
CLR
00000
CONT 00001
Follow the procedure below to monitor the status of a particular word.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the word address of the desired word.
SHIFT
CH
*DM
*EM
LR
B
1
00000
CHANNEL LR 01
3. Press the MONTR Key to begin monitoring.
MONTR
cL01
FFFF
The Up or Down Arrow Key can be pressed to display the status of the previous or next word.
The displayed word’s status can be changed using the Hexadecimal/BCD
Data Modification operation. Refer to Refer to 4 3-19 Hexadecimal, BCD
Data Modification, 4-3-20 Binary Data Modification, 4-3-21 Singed Decimal
112
Programming Console Operations Section 4-4
Multiple Address
Monitoring
Data Modification, and 4-3-22 Unsigned Decimal Data Modification for details.
4. Press the CLR Key to end monitoring.
CLR
00000
CHANNEL LR 01
Note The operating mode can be changed without altering the current monitor display by holding down the SHIFT Key and then changing the operating mode.
The status of up to six bits and words can be monitored simultaneously, although only three can be shown on the display at any one time.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the address of the first bit or word and press the MONTR Key.
TIM MONTR
T000
0100
3. Repeat step 2 up to 6 times to display the next addresses to be monitored.
SHIFT
CONT
#
B
1 MONTR
EM
DM
MONTR
00001 T000
^ OFF 0100
D000000001 T000
0000^ OFF 0100
If 4 or more bits and words are being monitored, the bits and words that do not appear on the display can be displayed by pressing the MONTR Key. If the MONTR Key is pressed alone, the display will shift to the right.
If more than six bits and words are input, monitoring of the bit or word input first will be canceled.
4. Press the CLR Key to stop monitoring the leftmost bit or word and clear it from the display.
CLR
00001 T000
^ OFF 0100
5. Press the SHIFT and CLR Keys to end monitoring altogether.
SHIFT CLR
00000
CONT 00001
Note Press the SHIFT Key, CLR Key, and then CLR Key again to return to the initial
Programming Console display with the multiple address monitoring state unchanged. Press the SHIFT Key and then the MONTR Key from the initial display to return to the multiple address monitoring state. The monitoring states can be retained for 6 bits and words.
The operating mode can be changed without altering the current monitor display by holding down the SHIFT Key and then changing the operating mode.
4-4-13 Differentiation Monitor
This operation is used to monitor the up or down differentiation status of a particular bit. When detected, the up or down differentiation will be displayed and the buzzer will sound. It is possible in any mode.
OK
RUN
OK
MONITOR
OK
PROGRAM
1, 2, 3...
1. Monitor the status of the desired bit according to the procedure described in
4-4-12 Bit, Digit, Word Monitor. If 2 or more bits are being monitored, the desired bit should be leftmost on the display.
113
Programming Console Operations Section 4-4
In this case the differentiation status of LR 00 will be monitored.
L000000001H0000
^ OFF^ OFF^ OFF
2. To specify up-differentiation monitoring, press the SHIFT and then the Up
Arrow Key. The symbols “U@” will appear.
SHIFT
↑
L000000001H0000
U@OFF^ OFF^ OFF
Indicates waiting for the bit to turn ON.
To specify down-differentiation monitoring, press the SHIFT and then the
Down Arrow Key. The symbols “D@” will appear.
SHIFT
↓
L000000001H0000
D@OFF^ OFF^ OFF
3. The buzzer will sound when the specified bit goes from off to on (for up-differentiation) or from on to off (for down-differentiation).
L000000001H0000
^ ON^ OFF^ OFF
Note The buzzer will not sound if it has been turned off.
4. Press the CLR Key to end differentiation monitoring and return to the normal monitoring display.
CLR
L000000001H0000
^ OFF^ OFF^ OFF
4-4-14 Binary Monitor
This operation is used to monitor the ON/OFF status of any word’s 16 bits. It is possible in any mode.
OK
RUN
OK
MONITOR
OK
PROGRAM
1, 2, 3...
1. Monitor the status of the desired word according to the procedure described in 4-4-12 Bit, Digit, Word Monitor. The desired word should be leftmost on the display if 2 or more words are being monitored.
c010
0000
(Word monitor)
2. Press the SHIFT and then the MONTR Key to begin binary monitoring. The
ON/OFF status of the selected word’s 16 bits will be shown along the bottom of the display. A 1 indicates a bit is on, and a 0 indicates it is off.
SHIFT MONTR
c010 MONTR
0000000000000000
Bit 15 Bit 00
The status of force-set bits is indicated by “S,” and the status of a force-reset bits is indicated by “R,” as shown below.
c010 MONTR
000S0000000R0000
Force-set bit Force-reset bit
Note a) The status of displayed bits can be changed at this point. Refer to
4-4-21 Binary Data Modification for details.
114
Programming Console Operations Section 4-4 b) The Up or Down Arrow Key can be pressed to display the status of the previous or next word’s bits.
3. Press the CLR Key to end binary monitoring and return to the normal monitoring display.
CLR
c010
0000
4-4-15 Three-Word Monitor
This operation is used to monitor the status of three consecutive words. It is possible in any mode.
OK
RUN
OK
MONITOR
OK
PROGRAM
1, 2, 3...
1. Monitor the status of the first of the three words according to the procedure described in 4-4-12 Bit, Digit, Word Monitor.
If 2 or more words are being monitored, the desired first word should be leftmost on the display.
c200
89AB
(Word monitor)
2. Press the EXT Key to begin 3-word monitoring. The status of the selected word and the next two words will be displayed, as shown below. In this case,
DM 0000 was selected.
EXT
c202 c201 c200
0123 4567 89AB
The Up and Down Arrow Keys can be used to shift one address up or down.
The status of the displayed words can be changed at this point. Refer to
4-4-18 Three-word Data Modification.
The display can be changed to display ASCII text, which is useful when three consecutive words containing an ASCII message are displayed. Refer to 4-4-26 Hex-ASCII Display Change.
3. Press the CLR Key to end 3-word monitoring and return to the normal monitoring display. The rightmost word on the 3-word monitor display will be monitored.
CLR
c200
89AB
Note The operating mode can be changed without altering the current monitor display by holding down the SHIFT Key and then changing the operating mode.
4-4-16 Signed Decimal Monitor
This operation converts the contents of the specified word from signed hexadecimal (two’s complement format) to signed decimal for display. The operation can be executed while using I/O monitoring, multiple address monitoring or 3-word monitoring.
OK
RUN
OK
MONITOR
OK
PROGRAM
1, 2, 3...
1. Monitor the word that is to be used for decimal monitor with sign. During multiple address monitoring, the leftmost word will be converted.
(Multiple address monitor)
c200 cL0020000
FFF0 0000^ OFF
115
Programming Console Operations Section 4-4
2. Press the SHIFT+TR Keys to display the leftmost word as signed decimal.
SHIFT TR
c200
Ć00016
At this point, the contents of the displayed word can be changed with a signed-decimal input. Refer to 4-4-22 Signed Decimal Data Modification.
3. Press the CLR Key or the SHIFT+TR Keys to end the unsigned decimal display and return to normal monitoring.
CLR
c200 cL0020000
FFF0 0000^ OFF
4-4-17 Unsigned Decimal Monitor
This operation is used to convert hexadecimal data in a word to unsigned decimal for display. The operation can be executed while using I/O monitoring, multiple address monitoring or 3-word monitoring.
OK
RUN
OK
MONITOR
OK
PROGRAM
1, 2, 3...
1. Monitor the word that is to be used for decimal monitor without sign. During multiple address monitoring, the leftmost word will be converted.
Multiple address monitoring
c200 cL0020000
FFF0 0000^ OFF
2. Press the SHIFT+TR+NOT Keys to display the leftmost word as unsigned decimal.
SHIFT TR NOT
c200
65520
At this point, the contents of the displayed word can be changed with an unsigned-decimal input. Refer to 4-4-23 Unsigned Decimal Data Modification.
3. Press the CLR Key or the SHIFT+TR Keys to end the unsigned decimal display and return to normal monitoring.
CLR
c200 cL0020000
FFF0 0000^ OFF
4-4-18 Three-Word Data Modification
This operation is used to change the contents of one or more of the 3 consecutive words displayed in the Three-Word Monitor operation. It is possible in MONITOR or PROGRAM mode only.
No
RUN
OK
MONITOR
OK
PROGRAM
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Unit, Expansion Units, or Expansion I/O Units may operate unexpectedly.
1, 2, 3...
1. Monitor the status of the desired words according to the procedure described 4-4-15 Three-Word Monitor.
(Three-word monitor)
D0002D0001D0000
0123 4567 89AB
116
Programming Console Operations Section 4-4
2. Press the CHG Key to begin 3-word data modification. The cursor will appear next to the contents of the leftmost word.
CHG
D0002 3CH CHG?
00123 4567 89AB
3. Input the new value for the leftmost word on the display and press the CHG
Key if more changes will be made.
(Input the new value and press the WRITE Key to write the changes in memory if no more changes will be made.)
B
1 CHG
D0002 3CH CHG?
0001 4567 89AB
4. Input the new value for the middle word on the display and press the CHG
Key if the rightmost word will be changed. Input the new value and press the
WRITE Key to write the changes in memory if the rightmost word will not be changed. (In this case, it will not.)
C
2
D
3
E
4 WRITE
D0002D0001D0000
0001 0234 89AB
Note If the CLR Key is pressed before the WRITE Key, the operation will be cancelled and the 3-word monitor display will return without any changes in data memory.
4-4-19 Changing Timer, Counter SV
There are two operations that can be used to change the SV of a timer or counter. They are possible in MONITOR or PROGRAM mode only. In MON-
ITOR mode, the SV can be changed while the program is being executed.
No
RUN
OK
MONITOR
OK
PROGRAM
The timer or counter SV can be changed either by inputting a new value or by incrementing or decrementing the current SV.
Inputting a New SV
Constant
This operation can be used to input a new SV constant, as well as to change an
SV from a constant to a word address designation and vice versa. The following examples show how to input a new SV constant and how to change the SV from a constant to an address.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Display the desired timer or counter.
TIM
B
1 SRCH
00201SRCH
TIM 001
3. Press the Down Arrow Key and then the CHG Key.
↓
CHG
00201DATA?
T001 #0134 #????
4. At this point a new SV constant can be input or the SV constant can be changed to a word address designation a) To input a new SV constant, input the constant and press the WRITE
Key.
B
1
C
2
E
4 WRITE
00201 TIM DATA
#0124
SHIFT b) To change to a word address designation, input the word address and press the WRITE Key.
CH
*DM
AR
HR
B
1
A
0 WRITE
00201 TIM DATA
HR 10
117
Programming Console Operations Section 4-4
Incrementing and
Decrementing a Constant
This operation can be used to increment and decrement an SV constant. It is possible only when the SV has been entered as a constant.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Display the desired timer or counter.
TIM SRCH
00201SRCH
TIM 000
3. Press the Down Arrow, CHG, and then the EXT Key.
↓
CHG EXT
00201DATA ? U/D
T000 #0123 #0123
The constant on the left is the old SV and the constant on the right will become the new SV constant in step 5.
4. Press the Up and Down Arrow Keys to increment and decrement the constant on the right. (In this case the SV is incremented once.)
↓
00201DATA ? U/D
T000 #0123 #0124
5. Press the CLR Key twice to change the timer’s SV to the new value.
CLR CLR
00201 TIM DATA
#0124
4-4-20 Hexadecimal, BCD Data Modification
This operation is used to change the BCD or hexadecimal value of a word being monitored using the procedure described in 4-4-12 Bit, Digit, Word
Monitor. It is possible in MONITOR or PROGRAM mode only.
No
RUN
OK
MONITOR
OK
PROGRAM
Words SR 253 to SR 255 cannot be changed.
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Unit, Expansion Units, or Expansion I/O Units may operate unexpectedly.
1, 2, 3...
1. Monitor the status of the desired word according to the procedure described in 4-4-12 Bit, Digit, Word Monitor. If two or more words are being monitored, the desired word should be leftmost on the display.
D0000
0119
(Word monitor)
2. Press the CHG Key to begin hexadecimal, BCD data modification.
CHG
PRES VAL?
D0000 0119 ????
3. Input the new PV and press the WRITE Key to change the PV.
The operation will end and the normal monitoring display will return when the WRITE Key is pressed.
C
2
A
0
A
0 WRITE
D0000
0200
118
Programming Console Operations Section 4-4
4-4-21 Binary Data Modification
This operation is used to change the status of a word’s bits when the word is monitored using the procedure described in 4-4-14 Binary Monitor. It is possible in MONITOR or PROGRAM mode only.
No
RUN
OK
MONITOR
OK
PROGRAM
Bits SR 25300 to SR 25507 and timer/counter flags cannot be changed.
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Unit, Expansion Units, or Expansion I/O Units may operate unexpectedly.
1, 2, 3...
1. Monitor the status of the desired word according to the procedure described
4-4-14 Binary Monitor.
(BInary monitor)
c010 MONTR
1000010101010101
Bit 15
2. Press the CHG Key to begin binary data modification.
Bit 00
CHG
c010 CHG?
1000010101010101
A flashing cursor will appear over bit 15. The cursor indicates which bit can be changed.
3. Three sets of keys are used to move the cursor and change bit status: a) Use the Up and Down Arrow Keys to move the cursor to the left and right.
↓ ↓
c010 CHG?
1000010101010101 b) Use the 1 and 0 Keys to change a bit’s status to on or off. The cursor will move one bit to the right after one of these keys is pressed.
B
1
c010 CHG?
1010010101010101 c) Use the SHIFT+SET and SHIFT+RESET Keys to force-set or force-reset a bit’s status. The cursor will move one bit to the right after one of these keys is pressed. The NOT Key will clear force-set or force-reset status.
Note Bits in the DM Area cannot be force-set or force-reset.
4. Press the WRITE Key to write the changes in memory and return to the binary monitor.
WRITE
c010 MONTR
1010010101010101
4-4-22 Signed Decimal Data Modification
This operation is used to change the decimal value of a word being monitored as signed decimal data, within a range of –32,768 to 32,767. The contents of the specified word are converted automatically to signed hexadecimal (two’s complement format).
119
Programming Console Operations Section 4-4
Words SR 253 to SR 255 cannot be changed.
No
RUN
OK
MONITOR
OK
PROGRAM
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Unit, Expansion Units, or Expansion I/O Units may operate unexpectedly.
1, 2, 3...
1. Monitor (signed decimal) the status of the word for which the present value is to be changed.
D0200
Ć00016
(Signed decimal monitor)
2. Press the CHG Key to begin decimal data modification.
CHG
PRES VAL?
D0200Ć00016
3. Input the new PV and press the WRITE Key to change the PV. The operation will end and the signed-decimal monitoring display will return when the
WRITE Key is pressed.
The PV can be set within a range of –32,768 and 32,767. Use the SET Key to input a positive number, and use the RESET Key to input a negative number.
RESET
D
3
C
2 7 6 8 WRITE
D0200
Ć32768
If an erroneous input has been made, press the CLR Key to restore the status prior to the input. Then enter the correct input.
The buzzer will sound if a value outside the specified range is input, allowing no writing.
4-4-23 Unsigned Decimal Data Modification
This operation is used to change the decimal value of a word being monitored as unsigned decimal data, within a range of 0 to 65,535. A change into hexadecimal data is made automatically.
Words SR 253 to SR 255 cannot be changed.
No
RUN
OK
MONITOR
OK
PROGRAM
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Unit, Expansion Units, or Expansion I/O Units may operate unexpectedly.
1, 2, 3...
1. Monitor (unsigned decimal) the status of the word for which the present value is to be changed.
c200
65520
(Unsigned decimal monitor)
2. Press the CHG Key to begin decimal data modification.
120
Programming Console Operations Section 4-4
CHG
PRES VAL?
c200 65520
3. Input the new PV and press the WRITE Key to change the PV. The operation will end and the decimal-without-sign monitoring display will return when the
WRITE Key is pressed.
D
3
The PV can be set within a range of 0 to 65,535.
C
2 7 6 8 WRITE
c200
32768
If an erroneous input has been made, press the CLR Key to restore the status prior to the input. Then enter the correct input.
The buzzer will sound if a value outside the specified range is input, allowing no writing.
4-4-24 Force Set, Reset
This operation is used to force bits ON (force set) or OFF (force reset) and is useful when debugging the program or checking output wiring. It is possible in MONITOR or PROGRAM mode only.
No
RUN
OK
MONITOR
OK
PROGRAM
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Unit, Expansion Units, or Expansion I/O Units may operate unexpectedly.
1, 2, 3...
1. Monitor the status of the desired bit according to the procedure described in
4-4-12 Bit, Digit, Word Monitor. If two or more words are being monitored, the desired bit should be leftmost on the display.
0000020000
^ OFF^ ON
(Multiple address monitor)
2. Press the SET Key to force the bit ON or press the RESET Key to force the bit OFF.
SET
0000020000
ON^ ON
The cursor in the lower left corner of the display indicates that the force set/ reset is in progress. Bit status will remain ON or OFF only as long as the key is held down; the original status will return one cycle after the key is released.
3. Press the SHIFT and SET Keys or SHIFT and RESET Keys to maintain the status of the bit after the key is released. In this case, the force-set status is indicated by an “S” and the force-reset status is indicated by an “R.”
To return the bit to its original status, press the NOT Key or perform the Clear
Force Set/Reset operation. Refer to 4-4-25 Clear Force Set/Reset for details.
Forced status will also be cleared in the following cases: a) When the PC’s operating mode is changed (although the forced status will not be cleared when the mode is changed from PROGRAM to MON-
ITOR if SR 25211 is ON) b) When the PC stops because a fatal error occurred
121
Programming Console Operations Section 4-4 c) When the PC stops because of a power interruption d) When the Clear Force Set/Reset Operation is performed
4-4-25 Clear Force Set/Reset
This operation is used to restore the status of all bits which have been force set or reset. It is possible in MONITOR or PROGRAM mode only.
No
RUN
OK
MONITOR
OK
PROGRAM
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Unit, Expansion Units, or Expansion I/O Units may operate unexpectedly.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the SET and then the RESET Key. A confirmation message will appear.
00000FORCE RELE?
SET
RESET
Note If you mistakenly press the wrong key, press CLR and start again from the beginning.
3. Press the NOT Key to clear the force-set/reset status of bits in all data areas.
NOT
00000FORCE RELE
END
4-4-26 Hex-ASCII Display Change
This operation is used to convert word data displays back and forth between
4-digit hexadecimal data and ASCII. It is possible in any mode.
The displayed PV of the timer or counter cannot be changed.
OK
RUN
OK
MONITOR
OK
PROGRAM
1, 2, 3...
1. Monitor the status of the desired word(s) according to the procedure described in 4-4-12 Bit, Digit, Word Monitor. While the multiple addresses are being monitored, the leftmost word is subject to change.
(Multiple address monitor)
D0000D0001
4142 3031
2. Press the TR Key to switch to ASCII display. The display will toggle between hexadecimal and ASCII displays each time the TR Key is pressed.
TR
TR
D0000 D0001
"AB" 3031
D0000D0001
4142 3031
Note 1. A message contained in three words can be displayed by using ASCII display in combination with the Three-word monitor operation.
2. The Hexadecimal, BCD Data Modification Operation can be used while displaying ASCII data. Input values in 4-digit hexadecimal.
122
Programming Console Operations Section 4-4
4-4-27 Displaying the Cycle Time
This operation is used to display the current average cycle time (scan time).
It is possible only in RUN or MONITOR mode while the program is being executed.
OK
RUN
OK
MONITOR
No
PROGRAM
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the MONTR Key to display the cycle time.
MONTR
00000SCAN TIME
012.1MS
“MS” in the display indicates the unit “ms” for the cycle time.
There might be differences in displayed values when the MONTR Key is pressed repeatedly. These differences are caused by changing execution conditions.
4-4-28 Reading and Setting the Clock
This operation is used to read or set the CPU’s clock. The clock can be read in any mode, but can be set in MONITOR or PROGRAM mode only.
Operation
Read clock
Set clock
OK
No
RUN
OK
OK
MONITOR
OK
PROGRAM
OK
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the FUN Key, SHIFT Key, and then the MONTR Key to display the date and time.
FUN SHIFT MONTR
TIM 99Ć02Ć22
11:04:32 MON(1)
3. Press the CHG Key to change the date and/or time.
CHG
TIM CHG?99Ć02Ć22
11:04:32 MON(1)
The digit that can be changed will flash. If necessary, input a new value with the Up and Down Arrow Keys or Numeric Keys. Press the CHG Key to move the cursor to the next digit. The following table shows the setting ranges for each value.
Year Month Day Hour Minute Second Day-of-week
00 to 99 01 to 12 01 to 31 00 to 23 00 to 59 00 to 59 0 to 6
(SUN to SAT)
4. Press the WRITE Key to write the new value.
WRITE
INST TBL READ
FUN018:HEX
Press the CLR Key to return to the initial display.
123
Programming Example Section 4-5
4-5 Programming Example
This section demonstrates all of the steps needed to write a program with the
Programming Console.
4-5-1 Preparatory Operations
Use the following procedure when writing a program to the CPM2A for the first time.
1, 2, 3...
1. Set the Programming Console’s mode switch to PROGRAM mode and turn on the CPM2A’s power supply. The password input display will appear on the Programming Console.
MONITOR
RUN PROGRAM
<PROGRAM>
PASSWORD!
2. Enter the password by pressing the CLR and then the MONTR Key.
CLR MONTR
<PROGRAM> BZ
3. Clear the CPM2A’s memory by pressing the CLR, SET, NOT, RESET, and then the MONTR Key. Press the CLR Key several times if memory errors are displayed.
00000
CLR
SET NOT RESET
00000MEMORY CLR?
HR CNT DM
MONTR
00000MEMORY CLR
END HR CNT DM
4. Display and clear error messages by pressing the CLR, FUN, and then the
MONTR Key. Continue pressing the MONTR Key until all error messages have been cleared.
00000
CLR
FUN
00000
FUN (0??)
MONTR
ERR/MSG CHK OK
5. Press the CLR Key to bring up the initial programming display (program address 00000). The new program can be written at this point.
00000
CLR
!
Caution Check the system thoroughly before starting or stopping the CPM2A to prevent any accidents that might occur when the program is first started.
124
Programming Example
4-5-2 Example Program
The following ladder program will be used to demonstrate how to write a program with the Programming Console. This program makes output IR 01000 flicker ON/OFF (one second ON, one second OFF) ten times after input
IR 00000 is turned ON.
Start input
00000 C000
20000 Self-holding bit
00000
20000
00004
20000 T002
TIM 001
#0010
1-second timer
00007
20000 T002
TIM 002
#0020
2-second timer
20000 T001
00010
20000
Count input
CP
R
CNT 000
#0010
10-count counter
Reset input
00014
20000 T001
Section 4-5
01000
Flicker output (10 counts)
ON
OFF
END(01)
1
S
00017
The mnemonic list for the example program is shown in the following table. The steps required to enter this program from a Programming Console are described in 4-5-3 Programming Procedures.
Address Instruction Data Programming example procedures in 4-5-3
Programming Procedures
(1) Self-holding bit 00000
00001
00002
00003
00004
00005
00006
00007
00008
00009
00010
00011
00012
00013
00014
00015
00016
00017
LD
OR
AND NOT
OUT
LD
AND NOT
TIM
LD
AND NOT
TIM
LD
AND
LD NOT
CNT
LD
AND NOT
OUT
END (01)
C
T
#
T
#
T
#
T
002
002
0020
20000
001
20000
000
0010
20000
001
01000
---
00000
20000
000
20000
20000
002
001
0010
20000
(2) 1-second timer
(3) 2-second timer
(4) 10-count counter
(5) Flicker output (10 counts)
(6) END(01) instruction
125
Programming Example Section 4-5
4-5-3 Programming Procedures
The example program will be written to the CPM2A according to the mnemonic list in 4-5-2 Example Program. The procedure is performed beginning with the initial display. (Clear the memory before entering a new program.)
Note If an error occurs while inputting the program, refer to 5-3 Programming Console
Operation Errors for details on correcting the error. Refer to the relevant Support
Software Operation Manual for details on errors that appear when operating the
SSS or SYSMAC-CPT Support Software.
(1) Inputting the Self-holding Bit
1, 2, 3...
1. Input the normally open condition IR 00000.
(It isn’t necessary to input leading zeroes.)
OR
OUT
LD
WRITE
00000
LD 00000
00001READ
NOP (000)
2. Input the OR condition IR 20000.
C
2
A
0
A
0
A
0
A
0
WRITE
00001
OR 20000
00002READ
NOP (000)
3. Input the normally closed AND condition C000.
(It isn’t necessary to input leading zeroes.)
AND
NOT CNT
00002
AND NOT CNT 000
WRITE
00003READ
NOP (000)
4. Input the OUT instruction IR 20000.
C
2
A
0
A
0
A
0
A
0
WRITE
00003
OUT 20000
00004READ
NOP (000)
(2) Inputting the One-second Timer
1, 2, 3...
1. Input the normally open condition IR 20000.
LD
C
2
A
0
A
0
A
0
A
0
00004
LD 20000
WRITE
00005READ
NOP (000)
2. Input the normally closed AND condition T002.
(It isn’t necessary to input leading zeroes.)
AND
NOT TIM
C
2
WRITE
00005
AND NOT TIM 002
00006READ
NOP (000)
126
Programming Example Section 4-5
3. Input the 1-second timer T001.
TIM
B
1
00006
TIM 001
WRITE
00006 TIM DATA
#0000
4. Input the SV for T001 (#0010 = 1.0 s).
B
1
A
0
WRITE
00006 TIM DATA
#0010
00007READ
NOP (000)
The following key operations are used to input the 2-second timer.
(3) Inputting the
Two-second Timer
1, 2, 3...
1. Input the normally open condition IR 20000.
LD C
2
A
0
A
0
A
0
A
0
00007
LD 20000
WRITE
00008READ
NOP (000)
2. Input the normally closed AND condition T002.
(It isn’t necessary to input leading zeroes.)
AND
NOT TIM
TIM
C
2
C
2
00008
AND NOT TIM 002
WRITE
00009READ
NOP (000)
3. Input the 2-second timer T002.
00009
TIM 002
WRITE
00009 TIM DATA
#0000
4. Input the SV for T002 (#0020 = 2.0 s).
C
2
A
0
WRITE
00009 TIM DATA
#0020
00010READ
NOP (000)
(4) Inputting the 10-count
Counter
The following key operations are used to input the 10-count counter.
1, 2, 3...
1. Input the normally open condition IR 20000.
LD
C
2
A
0
A
0
A
0
A
0
00010
LD 20000
WRITE
00011READ
NOP (000)
2. Input the normally open AND condition T001.
(It isn’t necessary to input leading zeroes.)
AND
TIM
B
1
WRITE
00011
AND TIM 001
00012READ
NOP (000)
127
Programming Example Section 4-5
LD
NOT
3. Input the normally closed condition IR 20000.
C
2
A
0
A
0
A
0
A
0
00012
LD NOT 20000
WRITE
00013READ
NOP (000)
4. Input the counter 000.
CNT
A
0
00013
CNT 000
WRITE
00013 CNT DATA
#0000
5. Input the SV for counter 000 (#0010 = 10 counts).
B
1
A
0
WRITE
00013 CNT DATA
#0010
00014READ
NOP (000)
(5) Inputting the Flicker Output
1, 2, 3...
1. Input the normally open condition IR 20000.
LD C
2
A
0
A
0
A
0
A
0
000014
LD 20000
WRITE
00015READ
NOP (000)
2. Input the normally closed AND condition T001.
(It isn’t necessary to input leading zeroes.)
AND
NOT TIM
B
1
00015
AND NOT TIM 001
WRITE
00016READ
NOP (000)
3. Input the OUT instruction IR 01000.
(It isn’t necessary to input leading zeroes.)
OUT
B
1
A
0
A
0
A
0
WRITE
00016
OUT 01000
00017READ
NOP (000)
(6) Inputting the END(001)
Instruction
Input END(01). (The display shows three digits in the function code, but only the last two digits are input for CPM2A PCs.)
A
0
FUN
B
1
WRITE
00017
FUN (0??)
00017
END (001)
00018READ
NOP (000)
128
Programming Example Section 4-5
4-5-4 Checking the Program
Check the program syntax in PROGRAM mode to make sure that the program has been input correctly.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
00000
CLR
2. Press the SRCH Key. An input prompt will appear requesting the desired check level.
SRCH
00000PROG CHK
CHK LBL (0Ć2)?
3. Input the desired check level (0, 1, or 2). The program check will begin when the check level is input, and the first error found will be displayed. If no errors are found, the following display will appear.
A
0
00017PROG CHK
END (001)00.1KW
Note Refer to 5-4 Programming Errors for details on check levels and the programming errors that may be displayed during a program check.
4. Press the SRCH Key to continue the search. The next error will be displayed. Continue pressing the SRCH Key to continue the search.
The search will continue until an END(01) instruction or the end of Program
Memory is reached.
If errors are displayed, edit the program to correct the errors and check the program again. Continue checking the program until all errors have been corrected.
4-5-5 Test Run in MONITOR Mode
Switch the CPM2A in MONITOR mode and check the operation of the program.
1, 2, 3...
1. Set the Programming Console’s mode switch to MONITOR mode.
RUN
MONITOR
PROGRAM
<MONITOR> BZ
2. Press the CLR Key to bring up the initial display.
00000
CLR
3. Force-set the start input bit (IR 00000) from the Programming Console to start the program.
LD
00000
LD 00000
MONTR
00000
^ OFF
SET
00000
ON
The cursor in the lower left corner of the display indicates that the force set is in progress. The bit will remain ON as long as the Set Key is held down.
4. The output indicator for output IR 01000 will flash ten times if the program is operating correctly. The indicator should go OFF after ten one-second flashes.
There is a mistake in the program if the output indicator doesn’t flash. In this case, check the program and force set/reset bits to check operation.
129
SECTION 5
Test Runs and Error Processing
This section describes procedures for test runs of CPM2A operation, self-diagnosis functions, and error processing to identify and correct the hardware and software errors that can occur during PC operation.
5-1 Initial System Checks and Test Run Procedure
5-1-1 Initial System Checks
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1-2 Flash Memory Precautions
5-1-3 CPM2A Test Run Procedure
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2 Self-diagnostic Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2-1 Identifying Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2-2 User-defined Errors
5-2-3 Non-fatal Errors
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2-4 Fatal Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2-5 Communications Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3 Programming Console Operation Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4 Programming Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-5 Troubleshooting Flowcharts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-6 Maintenance Inspections
5-7 Battery Replacement
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
133
134
134
135
135
136
136
137
145
146
132
132
132
132
133
131
Initial System Checks and Test Run Procedure Section 5-1
5-1 Initial System Checks and Test Run Procedure
5-1-1 Initial System Checks
Check the following items after setting up and wiring the CPM2A, but before performing a test run.
Item
Power supply and
I/O connections
Points to check
Is the wiring correct?
Are the terminals securely tightened?
Are there any shorts between crimp terminals or wires?
Refer to 3-4 Wiring and Connections for details.
Connecting cables Are the cables all connected correctly and locked?
Protective label
Refer to 3-4 Wiring and Connections for details.
Has the protective label been removed?
Note 1. Always clear memory before beginning to program the CPM2A. Although memory is cleared before the CPU Unit is shipped, the contents of the DM,
HR, AR, and counter areas may change in transit. See 4-4-2 Clearing
Memory for details on the All Clear operation.
2. See 1-3-3 Operating Mode at Startup to determine what mode the CPM2A will enter when the power is turned on.
5-1-2 Flash Memory Precautions
Observe the following precautions to protect the flash memory and ensure proper operation.
1, 2, 3...
1. If changes are made in the read-only DM area (DM 6144 through DM 6599) or PC Setup (DM 6600 through DM 6655), the PC’s operating mode must be changed to write the new contents to flash memory. If backup battery is changed before the changes are written to flash memory, the changes will be lost.
The changes can be saved by switching the CPM2A to RUN or MONITOR mode or turning the CPM2A off and then on again.
2. When contents of the program, read-only DM (DM 6144 through DM 6599), or PC Setup (DM 6600 through DM 6655) have been changed, startup processing will take up to 1,200 ms longer than usual. Be sure to take this onetime startup delay into account if it may affect operations.
3. If one of the following three operations is performed in MONITOR or RUN mode, the CPM2A’s cycle time will be extended by up to 1,200 ms and interrupts will be disabled while the program or PC Setup is being overwritten.
•
Program changes with the online edit operation
•
Changes to the read-only DM area (DM 6144 through DM 6599)
•
Changes to the PC Setup (DM 6600 through DM 6655)
A “SCAN TIME OVER” error won’t occur during these operations. Be sure to take this delay in the CPM2A’s I/O response times into account when performing online editing.
5-1-3 CPM2A Test Run Procedure
1, 2, 3...
1. Power Supply Application a) Check the CPM2A’s power supply voltage and terminal connections.
b) Check the I/O devices’ power supply voltage and terminal connections.
c) Turn on the power supply and check that the “PWR” indicator lights.
d) Use a Programming Device to set the CPM2A to PROGRAM mode.
132
Self-diagnostic Functions Section 5-2
2. I/O Wiring Checks a) With the CPM2A in PROGRAM mode, check the output wiring by turning on the output bits with the force set and force reset operations.
Refer to 4-4-24 Force Set, Reset for details.
b) Check the input wiring with the CPM2A’s input indicators or a Programming Device’s monitor operations.
3. Test Run a) Use a Programming Device to set the CPM2A to RUN or MONITOR mode and check that the “RUN” indicator lights.
b) Check the sequence of operation with the force set/reset operations, etc.
4. Debugging
Correct any programming errors that are detected.
5. Saving the Program a) Use a Programming Device to write the program to a backup floppy disk.
b) Print out a hard copy of the program with a printer.
Note Refer to Section 4 Using Programming Devices for details on the Support Software and Programming Console operations.
5-2 Self-diagnostic Functions
The CPM2A is equipped with a variety of self-diagnostic functions to help identify and correct errors and reduce down time.
5-2-1 Identifying Errors
An error can be identified by the error message displayed on a Programming
Device, error flags in the AR and SR areas, and the error code output to SR 253.
Fatal and Non-fatal
Errors
Error Messages
Error Flags
PC errors are divided into 2 categories based on the severity of the errors. The status of the ERR/ALM indicator (lit or flashing) shows which type of error has occurred.
ERR/ALM Lit (Fatal Error)
Fatal errors are serious errors which stop CPM2A operation. There are two ways to restart operation:
•
Turn the PC off and then on again.
•
Use a Programming Device to switch the PC to PROGRAM mode, and read/ clear the error.
ERR/ALM Flashing (Non-fatal Error)
Non-fatal errors are less serious errors which don’t stop CPM2A operation.
When an error is detected, a corresponding error message will be displayed on the Programming Console or other Programming Device connected to the PC.
When a hardware error is detected, the corresponding error flag in the AR or SR area will be turned ON.
Error Code When an error is detected, a specific 2-digit hexadecimal error code is output to
SR 25300 to SR 25307. The error code and time of occurrence are also output to the Error Log Area (DM 2000 to DM 2021).
!
WARNING The PC will turn OFF all outputs when its self-diagnosis function detects any error or when a severe failure alarm (FALS) instruction is executed. External safety measures must be provided to ensure safety in the system. Not providing proper safety measures may result in serious accidents.
133
Self-diagnostic Functions Section 5-2
5-2-2 User-defined Errors
There are three instructions that can be used to define errors or messages.
FAL(06) causes a non-fatal error, FAL(07) causes a fatal error, and MSG(46) sends a message to the Programming Console or host computer connected to the PC.
FAILURE ALARM – FAL(06) FAL(06) is an instruction that causes a non-fatal error. The following will occur when an FAL(06) instruction is executed:
1, 2, 3...
1. The ERR/ALM indicator on the CPU Unit will flash. PC operation will continue.
2. The instruction’s 2-digit BCD FAL number (01 to 99) will be written to
SR 25300 to SR 25307.
The FAL numbers can be set arbitrarily to indicate particular conditions, but the same number should not be used as both an FAL number and an FALS number.
To clear an FAL error, correct the cause of the error and then execute FAL 00 or use a Programming Device to clear the error.
SEVERE FAILURE ALARM –
FALS(07)
FALS(07) is an instruction that causes a fatal error. The following will occur when an FALS(07) instruction is executed:
1, 2, 3...
1. Program execution will be stopped and all outputs will be turned OFF.
2. The ERR/ALM indicator on the CPU Unit will be lit.
3. The instruction’s 2-digit BCD FALS number (01 to 99) will be written to
SR 25300 to SR 25307.
The FALS numbers can be set arbitrarily to indicate particular conditions, but the same number should not be used as both an FAL number and an FALS number.
To clear an FALS error, use a Programming Device to switch the PC to PRO-
GRAM Mode, correct the cause of the error, and then clear the error.
MESSAGE – MSG(46) MSG(46) is used to display a message on a Programming Device connected to the CPM2A. The message, which can be up to 16 characters long, is displayed when the instruction’s execution condition is ON.
5-2-3 Non-fatal Errors
PC operation and program execution will continue after one or more of these errors have occurred. Although PC operation will continue, the cause of the error should be corrected and the error cleared as soon as possible.
When one of these errors occurs, the POWER and RUN indicators will remain lit and the ERR/ALM indicator will flash.
Message
SYS FAIL FAL**
(** is 01 to 99 or 9B.)
FAL No.
Meaning and appropriate response
01 to 99 An FAL(06) instruction has been executed in the program. Check the FAL number to determine conditions that would cause execution, correct the cause, and clear the error.
9B An error has been detected in the PC Setup. Check flags AR 1300 to AR 1302, and correct as directed.
AR 1300 ON: An incorrect setting was detected in the PC Setup (DM 6600 to
DM 6614) when power was turned on. Correct the settings in PROGRAM Mode and turn on the power again.
AR 1301 ON: An incorrect setting was detected in the PC Setup (DM 6615 to
DM 6644) when switching to RUN or MONITOR mode. Correct the settings in
PROGRAM Mode and switch to RUN or MONITOR mode again.
AR 1302 ON: An incorrect setting was detected in the PC Setup (DM 6645 to
DM 6655) during operation. Correct the settings and clear the error.
134
Self-diagnostic Functions Section 5-2
Message FAL No.
SCAN TIME OVER F8
Battery error
(no message)
F7
Meaning and appropriate response
The cycle time has exceeded 100 ms. (SR 25309 will be ON.)
This indicates that the program cycle time is longer than recommended. Reduce cycle time if possible. (The CPM2A can be set so that this error won’t be detected.)
If the voltage of the CPM2A-BAT01 backup battery is below the minimum level, the
ERR/ALM indicator will flash and SR 25308 will be turned ON.
Replace the battery. (See 5-7 Battery Replacement for details.)
5-2-4 Fatal Errors
PC operation and program execution will stop and all outputs from the PC will be turned OFF when any of these errors have occurred. CPM2A operation can’t be restarted until the PC is turned off and then on again or a Programming Device is used to switch the PC to PROGRAM mode and clear the fatal error.
All CPU Unit indicators will be OFF for the power interruption error. For all other fatal operating errors, the POWER and ERR/ALM indicators will be lit. The RUN indicator will be OFF.
Message
Power interruption
(no message)
MEMORY ERR
NO END INST
I/O BUS ERR
I/O UNIT OVER
SYS FAIL FALS**
(** is 01 to 99 or 9F.)
FALS
No.
None
Meaning and appropriate response
F1
Power has been interrupted for more than 10 ms (2 ms for DC power types.)
Check power supply voltage and power lines. Try to power-up again.
AR 1308 ON: There is a non-existent bit or word address in the user program. Check the program and correct errors.
AR 1309 ON: An error has occurred in flash memory. Replace the CPU Unit.
AR 1310 ON: A checksum error has occurred in read-only DM (DM 6144 to DM 6599).
Check and correct the settings in the read-only DM area.
AR 1311 ON: A checksum error has occurred in the PC Setup. Initialize the PC Setup and input the settings again.
AR 1312 ON: A checksum error has occurred in the program. Check the program and correct any errors detected.
AR 1313 ON: A checksum error has occurred in the expansion instructions data and all function codes have been set the their default values. Reset the expansion instructions.
F0
AR 1314 ON: Data was not maintained in an area specified for holding. Clear the error, check the data in the areas specified for holding, and try again.
END(01) is not written in the program. Write END(01) at the end of the program.
C0
E1 Too many Expansion Units or Expansion I/O Units have been connected. Check the
Unit configuration.
01 to 99 A FALS(07) instruction has been executed in the program. Check the FALS number to determine the conditions that caused execution, correct the cause, and clear the error.
9F
An error has occurred during data transfer between the CPU Unit and an Expansion
Unit or an Expansion I/O Unit. Check the Unit’s connecting cable.
The cycle time has exceeded the Maximum (Watch) Cycle Time setting (DM 6618).
Check the cycle time and adjust the Maximum Cycle Time setting if necessary.
5-2-5 Communications Errors
The COMM indicator will be turned OFF and AR 0812 will be turned ON if an error occurs in communications through the peripheral port or AR 0804 will be turned ON if an error occurs in communications through the RS-232C port.
Check the connecting cables and restart.
There are no error messages or error codes generated by this error and the
ERR/ALM indicator is not affected.
135
Programming Errors Section 5-4
5-3 Programming Console Operation Errors
The following error messages may appear when performing operations on the
Programming Console. Correct the error as indicated and continue operation.
Message Meaning and appropriate response
REPL ROM An attempt was made to write to write-protected memory. Set bits
00 to 03 of DM 6602 to “0.”
PROG OVER The instruction at the last address in memory is not NOP(00). Erase all unnecessary instructions after END(01).
ADDR OVER An address was set that is larger than the highest memory address in Program Memory. Input a smaller address.
SETDATA
ERR
FALS 00 has been input, and “00” cannot be input. Reinput the data.
I/O NO. ERR A data area address has been designated that exceeds the limit of the data area, e.g., an address is too large. Confirm the requirements for the instruction and re-enter the address.
Note Refer to the relevant Support Software Operation Manual for details on errors that may appear when operating the SSS or SYSMAC-CPT Support Software.
5-4 Programming Errors
These errors in program syntax will be detected when the program is checked using the Program Check operation.
Three levels of program checking are available. The desired level must be designated to indicate the type of errors that are to be detected. The following table provides the error types, displays, and explanations of all syntax errors. Check level 0 checks for type A, B, and C errors; check level 1, for type A and B errors; and check level 2, for type A errors only.
Type
A
Message
?????
Meaning and appropriate response
The program has been damaged, creating a non-existent function code. Re-enter the program.
CIRCUIT ERR The number of LD instructions (LD or LD NOT) does not match the number of logic block instructions (OR LD or
AND LD).Check your program.
OPERAND
ERR
A constant entered for the instruction is not within defined values. Change the constant so that it lies within the proper range.
NO END
INSTR
LOCN ERR
There is no END(01) in the program. Write END(01) at the end of the program.
An instruction is in the wrong place in the program. Check instruction requirements and correct the program.
JME UNDEFD A JME(05) instruction is missing for a JMP(04) instruction.
Correct the jump number or insert the proper JME(05) instruction.
DUPL The same jump number or subroutine number has been used twice. Correct the program so that the same number is only used once for each.
SBN UNDEFD An SBN(92) has not been programmed with the same subroutine number as an SBS(91) instruction in the program. Correct the program.
STEP ERR STEP(08) with a section number and STEP(08) without a section number have been used incorrectly. Check
STEP(08) programming requirements and correct the program.
136
Troubleshooting Flowcharts Section 5-5
Type
B
C
Message Meaning and appropriate response
IL-ILC ERR IL(02) and ILC(03) are not used in pairs. Check the program before processing.
JMP-JME ERR JMP(04) and JME(05) are not used in pairs. Check the program before processing.
SBN-RET ERR RET(93) has not been used properly or the relationship between SBN(92) and RET(93) is not correct. Correct the program.
COIL DUPL The same bit is being controlled (i.e., turned ON and/or
OFF) by more than one instruction (e.g., OUT, OUT NOT,
DIFU(13), DIFD(14), KEEP(11), SFT(10)). This error occurs when the same number is used for the timer and counter instructions. Although this is allowed for certain instructions, check instruction requirements to confirm that the program is correct or rewrite the program so that each bit is controlled by only one instruction.
JMP UNDEFD JME(05) has been used with no JMP(04) with the same jump number. Add a JMP(04) with the same number or delete the JME(05) that is not being used.
SBS UNDEFD A subroutine exists that is not called by SBS(91). Program a subroutine call in the proper place, or delete the subroutine if it is not required.
5-5 Troubleshooting Flowcharts
Use the following flowcharts to troubleshoot errors that occur during operation.
Main Check
Error
PWR indicator lit?
Yes
No
Check power supply. (See page 138.)
RUN indicator lit?
Yes
No
Operation stopped. Check for fatal errors.
(See page 139.)
ERR/ALM indicator flashing?
Not lit
Flashing
Is I/O sequence normal?
Yes
No
Operating environment normal?
No
Yes
Replace the CPU
Unit.
Check for non-fatal errors. (See page 140.)
Check I/O. (See page 141.)
Check operating environment. (See page 143.)
137
Troubleshooting Flowcharts
Power Supply Check
Section 5-5
PWR indicator not lit.
Is power being supplied?
Yes
No
No
Connect power supply.
Is PWR indicator lit?
Yes
Is voltage adequate?
No
Yes
No
Set supply voltage within acceptable limits.
Is PWR indicator lit?
Yes
Are there any loose terminal screws or broken wires?
No
Yes
No
Tighten screws or replace wires.
Is PWR indicator lit?
Yes
Has the external power supply shorted or overloaded?
No
Yes
No
Correct the short circuit or limit the connected load to the specification range.
Is PWR indicator lit?
Yes
Replace the CPU
Unit.
End
138
Troubleshooting Flowcharts
Fatal Error Check
RUN indicator not lit.
No
Is the ERR/ALM indicator lit?
Yes
Determine the cause of the error with a
Programming Device.
Section
Yes
Is PC mode displayed on Programming
Device?
No
Is PC mode displayed on
Programming Device?
Yes
No
Turn the power supply OFF, and then ON again.
Is a fatal error displayed?
No
Switch to RUN or
MONITOR mode.
Yes
Identify the error, eliminate its cause, and clear the error.
Follow the Memory Error
Check flowchart if a memory error has occurred.
5-5
Is the RUN indicator lit?
Yes
End
No
Replace the CPU
Unit.
139
Troubleshooting Flowcharts
Non-fatal Error Check
Section 5-5
ERR/ALM indicator flashing.
Determine the cause of the error with a Programming Device.
Is a non-fatal error indicated?
No
Yes
Identify the error, eliminate its cause, and clear the error.
Is the ERR/ALM indicator flashing?
Not lit
Flashing
End
Replace the CPU
Unit.
140
Troubleshooting Flowcharts
I/O Check
Section 5-5
The I/O check flowchart is based on the following ladder diagram section.
(LS1)
00002
(LS2)
00003
01003
01003
SOL1
SOL1 malfunction.
Malfunction of SOL1
Is the
IR 01003 output indicator operating normally?
No
Yes
Check the voltage at the
IR 01003 terminals.
Wire correctly.
Operation OK?
Yes
No
No
Is output wiring correct?
Yes
Is the external power supply shorted or overloaded?
No
Yes
Disconnect the external wires and check the conductivity of each wire.
Correct the short circuit or limit the connected load to the specified range.
Monitor the ON/OFF status of IR 01003 with a Programming
Device.
Operation OK?
Yes
No
A
To next page
Yes
Operation OK?
No
Check output device
SOL1.
Replace the CPU Unit,
Expansion Unit, or
Expansion I/O Unit with the problem.
141
Troubleshooting Flowcharts
A
From previous page
Are the IR 00002 and IR 00003 input indicators operating normally?
Yes
Check the voltage at the IR 00002 and
IR 00003 terminals.
Section
Check the voltage at the IR 00002 and
IR 00003 terminals.
Operation OK?
No
Yes
No
Yes
Check operation by using a dummy input signal to turn the input ON and OFF.
Operation OK?
No
Yes
Is input wiring correct?
No
Wire correctly.
Yes
Tighten the terminal screws
Are the terminal screws loose?
No
No
Operation OK?
Yes
Replace the CPU Unit,
Expansion Unit, or
Expansion I/O Unit.
Check input devices
LS1 and LS2.
Return to “start.”
Replace the CPU Unit,
Expansion Unit, or
Expansion I/O Unit.
5-5
142
Troubleshooting Flowcharts
Environmental Conditions Check
Section 5-5
Environmental conditions check
Is the ambient temperature below 55
°
C?
Yes
No
Consider using a fan or cooler.
Is the ambient temperature above
0
°
C?
Yes
No Consider using a heater.
Is the ambient humidity between 10% and
85%?
Yes
No
Is noise being controlled?
Yes
Consider using an air conditioner.
No
Install surge protectors or other noisereducing equipment at noise sources.
Is the installation environment okay?
End.
Yes
No
Consider constructing an instrument panel or cabinet.
143
Troubleshooting Flowcharts
Memory Error Check
Memory error occurred.
AR 1309 ON?
No
Yes Replace the CPU
Unit.
AR 1314 ON?
No
Yes Check/correct backed-up data and clear error.
Section
AR 1308 ON?
No
Yes
Check the program, correct any errors, and clear the error.
No
AR 1310 to
AR 1312 ON?
No
Yes
Turned ON during startup?
No
Yes
Check the error indicated by the flag that is ON, correct settings as required, and write data to the flash memory.
Check the external environment.
End
5-5
144
Maintenance Inspections Section 5-6
5-6 Maintenance Inspections
In order for your SYSMAC system to operate in optimum condition, be sure to carry out daily or periodical inspections.
Inspection Items The main system components of a SYSMAC system are semiconductors, and it contains few components with limited lifetimes. Poor environmental conditions, however, can lead to deterioration of the electrical components, making regular maintenance necessary.
The standard period for maintenance checks is 6 months to 1 year, but more frequent checks are required if the PC is operated in more demanding conditions.
If the criteria are not met, adjust to within the specified ranges.
Inspection items Details
Power supply Determine whether the voltage fluctuation at the power supply terminals is within specifications.
Environmental conditions
I/O power supply
Installation status
Is the ambient temperature inside the panel appropriate?
Is the ambient humidity inside the panel appropriate?
Has dirt or dust collected?
Is the voltage fluctuation measured at the
I/O terminals within the standard range?
Are all units securely installed?
Are all connection cables and connectors inserted completely and locked?
Are any of the external wiring screws loose?
Are any of the external wiring cables frayed?
Product service life Contact output relay
Criteria
Within the voltage variation range (see note)
0 to 55
_
C
10% to 85% RH with no condensation
None
Each I/O terminal must conform to the specifications
Nothing is loose
Nothing is loose
Nothing is loose
No external abnormalities
Tester
Remarks
Thermometer
Hygrometer
Visual inspection
Tester
Phillips screwdriver
Visual inspection
Phillips screwdriver
Visual inspection
---
Battery (CPM2A-BAT01)
Electrical:
Resistance load:
300,000 operations
Inductive load:
100,000 operations
Mechanical:
10,000,000 operations
5 years ---
Required Tools
Note Power supply voltage variation range.
Power supply
100 to 240 VAC
24 VDC
Allowable voltage fluctuation range
85 to 264 VAC
20.4 to 26.4 VDC
Standard Tools (Required)
•
Screwdrivers (Phillips and flat-blade)
•
Voltage tester or digital voltage meter
•
Industrial alcohol and a cotton cloth
Measurement Devices (May be Needed)
•
Synchroscope
•
Cathode-ray oscilloscope
•
Thermometer, hygrometer
Note Do not attempt to disassemble, repair, or modify the PC in any way.
145
Battery Replacement Section 5-7
5-7 Battery Replacement
If power has not been supplied to the PC for an extended period of time, turn ON the power supply for at least 5 minutes before replacing the battery.
Turn OFF the power supply to the PC before replacing the battery.
Use the procedure below when replacing the battery. This procedure must be completed within 5 minutes.
1, 2, 3...
1. Remove the battery cover with a flat-blade screwdriver.
b) Remove battery cover.
a) Open terminal cover.
2. Remove the battery.
3. Disconnect the battery connector.
146
Battery Replacement
4. Check the replacement battery’s connector.
Section 5-7
5. Check the alignment of the connector tab and fully insert the connector.
6. Insert the battery into the compartment, making sure that the cord on the battery is facing the connector on the right side inside the compartment.
7. Close the battery cover.
147
SECTION 6
Expansion Memory Unit
This section describes how to use the CPM1-EMU01-V1 Expansion Memory Unit. Follow the handling precautions and procedures to properly use the Unit.
6-1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1-1 Memory Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1-2 Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2 Specifications and Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-2 Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3 Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3-1 Mounting/Removing EEPROM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3-2 PC Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3-3 Uploading Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3-4 Downloading Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
151
152
152
153
154
155
150
150
150
151
151
149
Overview
6-1 Overview
Section 6-1
The CPM1-EMU01-V1 Expansion Memory Unit is a program loader for smallsize or micro PCs. Using the CPM1-EMU01-V1, simple on-site transfer of user programs and data memory between PCs is possible.
Uploading
Downloading
SYSMAC
CPM1, CPM1A, CPM2A, CPM2C,
CQM1, CQM1H, SRM1(-V2)
EEPROM
Expansion Memory Unit
Note The “PLC” in the “DOWNLOAD TO PLC” Button indicates PCs (Programmable
Controllers).
6-1-1 Memory Areas
The memory areas that are uploaded or downloaded vary with the button used as shown in the following table.
Button UPLOAD + DM UPLOAD
Ladder program and expansion instructions
DM 6144 to 6655
Read from PC to
EEPROM.
Read from PC to
EEPROM.
Not affected.
DOWNLOAD TO
PLC
All contents of
EEPROM written to PC.
Note For details on program size, DM area, and the availability of expansion instructions, refer to the relevant PC manual.
6-1-2 Precautions
•
Do not attempt to use the CPM1-EMU01-V1 for any applications other than those described here. Doing so may result in malfunction.
•
Do not attempt to upload or download data between different types of PC. Doing so may result in malfunction.
•
Do not download when the PC is in RUN or MONITOR mode. If downloading is performed when the PC is running, it will automatically switch to PROGRAM mode and operation will stop.
•
Do not attempt to disassemble, repair, or modify the CPM1-EMU01-V1. Any attempt to do so may result in malfunction, fire, or electric shock.
•
After downloading has been completed, be sure to confirm the user program, data, and expansion instruction information. Not doing so may result in faulty operation.
150
Specifications and Nomenclature Section 6-2
•
Before touching the EEPROM or the CPM1-EMU01-V1, first touch a grounded metallic object to discharge any static build-up. Not doing so may result in malfunction or damage.
6-2 Specifications and Nomenclature
6-2-1 Specifications
Item
Supported PCs
Read/Write memory areas
Connector
Communications setting
EEPROM (See note 1.)
Current consumption
Dimensions
Weight
Specifications
CPM1, CPM1A, CPM2A, CPM2C, SRM1 (-V2),
CQM1, CQM1H
User program: 15.2 Kwords max.
Data memory: DM 6144 to DM 6655
(Read-only DM and PC Setup)
Expansion instructions: 18 instructions
Connector compatible with CPM1, CPM1A, CPM2A,
SRM1 (-V2), and CQM1 PCs.
For CPM2C and CQM1H PCs, connect via
CS1W-CN114 or CPM2C-CN111 Connecting Cable.
1 start bit, 7 data bits, even parity, 2 stop bits,
9,600 bps
256-Kbit EEPROM
ATMEL: AT28C256
OMRON: EEROM-JD
129 mA max.
Main body (not including cables or connectors):
57
×
92
×
38 mm (W
×
H
×
D)
200 g max. (not including EEPROM)
Note 1. The EEPROM must be purchased separately.
2. For general specifications, refer to the relevant PC manual.
6-2-2 Nomenclature
Peripheral Port
Connector
Lock Lever
Indicator
UPLOAD + DM Button
EEPROM Socket
DOWNLOAD to PLC Button
UPLOAD Button
Lock Lever
For mounting and removing EEPROM.
DOWNLOAD TO PLC Button
Writes all EEPROM data (ladder programs, data memory etc.) to the PC.
UPLOAD + DM Button
Reads PC user program and contents of
DM 6144 to DM 6655 to EEPROM.
UPLOAD Button
Reads only PC user program to EEPROM.
Note The “PLC” in the “DOWNLOAD TO PLC” Button indicates PCs (Programmable
Controllers).
151
Handling Section 6-3
LED Indicator
CONNECT
(green)
OFF
ON
Blinking
ON
OFF
OFF
ERR (red)
OFF
OFF
OFF
Blinking
ON
Blinking
Meaning
Not connected to PC (power supply OFF).
Connected to a recognized PC.
Uploading/downloading data.
Host link communications error, retry by user.
PC model and EEPROM data not compatible.
One of the following errors has occurred:
An unrecognized PC is connected.
An EEPROM error (EEPROM not present, EEPROM defect, or no program to download) or checksum error.
6-3 Handling
6-3-1 Mounting/Removing EEPROM
!
Caution Do not mount or remove the EEPROM with the CPM1-EMU01-V1 connected to the PC. Doing so may damage the EEPROM.
Mounting EEPROM
1, 2, 3...
1. Lift up the lock lever.
2. Straighten the pins on the EEPROM, line up with the socket and lower into the socket, as shown in the following diagram. If the EEPROM is loose, place it in the center of the socket.
Lift up the lock lever.
EEPROM
Insert the EEPROM.
3. Gently hold down the EEPROM and pull down the lock lever.
Pull down the lock lever.
152
Handling
Removing EEPROM Lift up the lock lever and detach the EEPROM.
6-3-2 PC Connections
Section 6-3
!
Caution Mount the EEPROM to the CPM1-EMU01-V1 before connecting the
CPM1-EMU01-V1 to the PC.
!
Caution Do not disconnect the CPM1-EMU01-V1 from the PC when the indicator is blinking green.
CPM1, CPM1A, CPM2A,
CQM1, and SRM1 (-V2)
PCs
When connecting to the CPM1, CPM1A, CPM2A, CQM1 or SRM1 (-V2),insert the connector into the peripheral port making sure that the connector is oriented correctly.
•
Insert the connector until it securely locks into place.
•
Connections are not possible to the RS-232C port or any other port.
Connection to CPM2A
CPM2C and CQM1H PCs
Peripheral Port
Communications
Settings
When connecting to the CPM2C or CQM1H, connect to the peripheral port via the CPM2C-CN111 or CS1W-CN114 Connecting Cable. Also, set the pins on the CPU Unit’s DIP switch as follows:
CPM2C
CQM1H
Pin 1: ON (see note)
Pin 2: ON
Pin 5: ON (see note)
Pin 7: ON
Note If pin 1 on the CPM2C or pin 5 on the CQM1H is OFF, connection is still possible if the peripheral port is set to the defaults.
The peripheral port must be set to the default communications settings shown below.
Start bit: 1
Data bits: 7
Stop bits: 2
Parity: Even
Baud rate: 9,600 bps
153
Handling
Disconnecting
Section 6-3
Press the levers on the top and bottom of the connector inwards to unlock the connector and pull out as shown in the following diagram.
Note Do not attempt to remove the connector by pulling the cable.
6-3-3 Uploading Programs
Ladder programs and the contents of data memory can be uploaded to the
EEPROM using the following procedure. The buttons used will determine whether the contents of data memory are uploaded or not.
Expansion Memory Unit
SYSMAC PC
Indicator
UPLOAD+DM Button UPLOAD Button
Button
Ladder program and expansion instructions
DM6144 to 6655
UPLOAD + DM
Read from PC to
EEPROM.
UPLOAD
Read from PC to
EEPROM.
Not affected.
Note Use a Phillips screwdriver or other tool with a diameter of 3.0 mm max. and a blade length of 10 mm min. to press the upload button.
3.0 dia. max.
10 mm min.
Uploading is possible even if the PC is in RUN or MONITOR mode.
154
Handling
Operation Procedure
Section
Start
Mount the EEPROM to the
CPM1-EMU01-V1.
Connect the CPM1-EMU01-V1 to the
PC’s peripheral port.
After 2 or 3 s, check if the indicator is lit green.
No
Yes
Select the memory area to be uploaded.
See the note on the right.
Mount the EEPROM to the CPM1-EMU01-V1 before connecting to the PC.
Check the orientation of the connector before connecting the CPM1-EMU01-V1.
Note If the indicator is not lit at all, lit red or blinks red, uploading will not be possible. In this case, check the following items.
•
Is the connector properly connected?
•
Is the EEPROM properly mounted?
•
Are the EEPROM specifications correct?
•
Are the peripheral port communications settings correct?
Upload both the ladder program and DM 6144 to
DM 6655.
Upload only the ladder program.
6-3
Press the UPLOAD+DM
Button.
Press the UPLOAD Button.
Check if the indicator is blinking green
(indicating that uploading has started).
No
Yes
Check if the indicator is lit green (indicating that uploading has been successfully completed).
See the note above.
See the note above.
No
Yes
Remove the Expansion Memory Unit from the PC.
End
6-3-4 Downloading Programs
Ladder programs and the contents of data memory can be downloaded from the
EEPROM to the PC using the procedure given below. When downloading, note the following points.
155
Handling Section 6-3
!
Caution If the PC is in RUN or MONITOR mode when downloading is started, it will automatically switch to PROGRAM mode and operation will stop. Confirm that no adverse effects will occur to the system before downloading. Not doing so may result in unexpected operation.
Note 1. If the PC is in RUN or MONITOR mode, switch the PC mode to PROGRAM mode.
2. Confirm that the program or other data to be downloaded to the PC is compatible with the PC before downloading.
3. For the CQM1 or CQM1H, when downloading programs that use user-assigned function codes for expansion instructions, be sure that pin 4 on the
CPU Unit’s DIP switch is ON. If these programs are downloaded while the pin is OFF, the assignments for the expansion instructions will return to their default settings.
4. After downloading has been completed, be sure to confirm the user program, data, and expansion instructions.
5. When the DOWNLOAD TO PLC Button is pressed, all EEPROM data (ladder programs, data memory etc.) is written to the PC.
Expansion Memory Unit
Indicator
SYSMAC PC
DOWNLOAD TO PLC Button
156
Handling
Operation Procedure
Start
Section
Mount the EEPROM to the
CPM1-EMU01-V1.
Mount the EEPROM to the
CPM1-EMU01-V1 before downloading.
Change the mode of the PC to PRO-
GRAM mode.
Confirm the safety of the system.
Connect the CPM1-EMU01-V1 to the
PC’s peripheral port.
Confirm the orientation of the connector before connecting the CPM1-EMU01-V1.
After 2 or 3 s, check if the indicator is lit green.
No
Yes
Press the DOWNLOAD TO PLC Button.
See the note on the right.
Check if the indicator is blinking green (indicating that downloading has started).
See the note above.
No
Yes
Check if the indicator is lit green
(indicating that downloading has been successfully completed).
No
Yes
Remove the Expansion Memory Unit from the PC.
See the note above.
Note If the indicator is not lit at all, lit red or blinks red, downloading will not be possible. In this case, check the following items.
•
Is the connector properly connected?
•
Is the EEPROM properly mounted?
•
Are the EEPROM specifications correct?
•
Are the peripheral port communications settings correct?
6-3
Check the program.
End
Before actual operation, check the contents of the ladder program and the DM area, as well as the expansion instruction settings.
157
Appendix A
Standard Models
CPU Units
Description
CPU Units with 20 I/O points
CPU Units with 30 I/O points
CPU Units with 40 I/O points
CPU Units with 60 I/O points
Input points
12 points
18 points
24 points
36 points
Output points
8 points
12 points
16 points
24 points
Power supply
AC
DC
AC
DC
AC
DC
AC
DC
Relay outputs
Model number
---
Transistor outputs
Sinking Sourcing
--CPM2A-
20CDR-A
CPM2A-
20CDR-D
CPM2A-
30CDR-A
CPM2A-
30CDR-D
CPM2A-
40CDR-A
CPM2A-
40CDR-D
CPM2A-
60CDR-A
CPM2A-
60CDR-D
CPM2A-
20CDT-D
---
CPM2A-
30CDT-D
---
CPM2A-
40CDT-D
---
CPM2A-
60CDT-D
CPM2A-
20CDT1-D
---
CPM2A-
30CDT1-D
---
CPM2A-
40CDT1-D
---
CPM2A-
60CDT1-D
Expansion I/O Units
Description
Expansion I/O Unit with 20 I/O points
Input Output points points
12 points
Model number
Relay output Transistor output
Sinking Sourcing
8 points CPM1A-20EDR1 CPM1A-20EDT CPM1A-20EDT1
Expansion I/O Unit with 8 input points 8 points --CPM1A-8ED (no outputs)
Expansion I/O Unit with 8 output points --8 points CPM1A-8ER CPM1A-8ET CPM1A-8ET1
159
Standard Models
Expansion Units
Analog I/O Unit
Description
Analog I/O Unit
Specifications
2 analog inputs and 1 analog output
Appendix A
Model number
CPM1A-MAD01
Temperature Sensor Units
Description
Temperature Sensor Unit
Specifications
2 thermocouple inputs: K, J
4 thermocouple inputs: K, J
2 platinum resistance thermometer inputs:
Pt100 (100
Ω
), JPt100 (100
Ω
)
4 platinum resistance thermometer inputs:
Pt100 (100
Ω
), JPt100 (100
Ω
)
Model number
CPM1A-TS001
CPM1A-TS002
CPM1A-TS101
CPM1A-TS102
CompoBus/S I/O Link Unit
Description
CompoBus/S I/O Link Unit
Specifications
Operates as a CompoBus/S Slave and provides 8 inputs and 8 outputs to the CPM1A or CPM2A PC.
Model number
CPM1A-SRT21
Adapters and Connecting Cables (1:1 Connection)
CPM2A port Name
Peripheral RS-232C
Appearance Model number
CQM1-CIF01
Comments Cable length
For a 25-pin computer serial port 3.3 m
CQM1-CIF02
CPM1-CIF01 (+
XW2Zj 00S)
For a 9-pin computer serial port 3.3 m
For a 25-pin computer serial port 3.3 m (+ j m)
RS-232C RS-232C
Cable
XW2Z-200S
XW2Z-500S
XW2Z-200S-V
XW2Z-500S-V
For a 25-pin computer serial port 2 m
For a 9-pin computer serial port
5 m
2 m
5 m
160
Standard Models Appendix A
Adapters and Connecting Cables (1:N Connections)
Name
RS-422 Adapter
Link Adapter
Appearance Model number
NT-AL001
B500-AL004
Specifications
Use for CPM2A RS-232C port to RS-422A conversion.
Requires a 5-VDC, 150 mA power supply which is supplied through the CPM2A connection.
(Can also be connected to a personal computer, but this connection requires an external 5-VDC power supply.)
Use for personal computer RS-232C port to RS-422A.
(Can also be connected to a CPM2A.)
RS-422 Adapter CPM1-CIF11 Use for CPM2A peripheral port to RS-422A conversion.
RS-232C Cables
(For use with the
NT-AL001.)
XW2Z-070T-1 Use for CPM2A RS-232C port to NT-AL001 connection.
(70-cm cable)
XW2Z-070T-1 Use for CPM2A RS-232C port to NT-AL001 connection.
(2-m cable)
161
Standard Models
Peripheral Devices
Name
Programming Console
Appearance
Appendix A
Model Number
CQM1-PRO01-E
Specifications
2-m Connecting Cable attached
CX-Programmer
SYSMAC Support Software
SYSMAC-CPT
Connecting Cable
Expansion Memory Unit
EEPROM
C200H-PRO27-E Hand-held, w/backlight; requires a
C200H-CN222 or C200H-CN422
Connecting Cable, see below.
C200H-CN222
C200H-CN422
WS02-CXPC1-E
Connects the
C200H-PRO27-E to a peripheral port.
2-m cable
4-m cable
For MS-Windows 95/98 (CD-ROM)
C500-ZL3AT1-E 3.5”, 2HD for IBM PC/AT compatible
WS01-CPTB1-E For IBM PC/AT or compatible computers
(3.5” disks (2HD) and CDROM)
C200H-CN222
C200H-CN422
CPM1-EMU01-V1
Connects C200H Programming Console to
Peripheral Port (2 m)
Connects C200H Programming Console to
Peripheral Port (4 m)
Uploads the ladder program and DM 6144 to DM 6655 from the PC to the EEPROM and downloads the ladder program and
DM 6144 to DM 6655 from the EEPROM to the PC.
EEROM-JD 256 K bit
Maintenance Accessories
Name
Backup Battery
Appearance Model Number
CPM2A-BAT01 ---
Specifications
162
Appendix B
Dimensions
All dimensions are in millimeters.
CPM2A-20CD
j
-
j
CPU Units
Four, 4.5 dia.
CPU Units with DC Power CPU Units with AC Power
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
CPM2A-30CD
j
-
j
CPU Units
Four, 4.5 dia.
CPU Units with DC Power CPU Units with AC Power
163
Dimensions
CPM2A-40CD
j
-
j
CPU Units
Appendix B
Four, 4.5 dia.
CPU Units with DC Power CPU Units with AC Power
CPM2A-60CD
j
-
j
CPU Units
Four, 4.5 dia.
CPU Units with DC Power CPU Units with AC Power
164
Dimensions
CPM1A-20ED
j
Expansion I/O Units
Appendix B
CPM1A-8
jjj
Expansion I/O Units
Four, 4.5 dia.
CPM1A-MAD01 Analog I/O Unit
Four, 4.5 dia.
Four, 4.5 dia.
165
Dimensions
CPM1A-TS
jjj
Temperature Sensor Units
Appendix B
76
±
0.2
Four, 4.5 dia.
CPM1A-SRT21 CompoBus/S I/O Link Unit
Four, 4.5 dia.
166
Dimensions
CPM1-CIF01 (RS-232C Adapter)
Appendix B
167
Dimensions
CPM1-CIF11 (RS-422 Adapter)
Appendix B
168
Dimensions
Dimensions with Programming Devices Attached
CPU Units with DC Power
Approx. 95
CPU Units with AC Power
Approx. 130
Appendix B
CPM1-CIF01 RS-232C Adapter
Approx. 120
169
Numbers
1:1 communications, 77
1:N communications, 79
A
Analog I/O Unit, standard model, 160 analog volume controls, location, 37 arc killer, examples, xvii
ASCII, converting displays, Programming Console, 122 atmosphere, 28
B battery, replacing, 146 binary data, modifying, Programming Console, 119 bit status, force-set/reset, Programming Console, 121 bits, searching, Programming Console, 109 buzzer operation, Programming Console, 103
C cabinet installation, precautions, 45
Programming Console installation, 98 cables, available models, 160 characteristics, 29 check levels, program checks, 136 checking, program syntax, Programming Console, 111 circuit configuration inputs, 31 outputs, relay, 33 clearing, memory areas, Programming Console, 102 clock, reading and setting the clock, 123 communication errors, 135 communications capabilities, 18 overview, 4
CompoBus/S I/O Link, 81
CompoBus/S I/O Unit, standard model, 160 components
Analog I/O Unit, 39
CompoBus/S I/O Link Unit, 41
CPU Unit, 35
Expansion I/O Unit, 38
Temperature Sensor Unit, 39
Index
computer, connecting, 77 conduit installation, 50 counters changing SV, Programming Console, 117 example of inputting, 127
CPM1A, function comparison, 18
CPU Units available models, 8, 159 cyclic operation, 13 internal structure, 10 standard models, 159 cycle time, displaying, Programming Console, 123 cyclic operation, 13
D data, modifying, Programming Console, 116–117, 118, 119,
120 data link, 5, 81 date. See clock decimal data with sign. See signed decimal data decimal data without sign. See unsigned decimal data dielectric strength, 28 differentiated instructions, entering, 107 dimensions, 163
DIN Track installation, 47 displays converting between hex and ASCII, Programming Console,
122 cycle time, Programming Console, 123 downloading, programs, 155 duct installation, 49
E
EC Directives, precautions, xv
EEPROM mounting/removing, 152 specifications, 151 electrical noise, preventing, 45, 49
ERR/ALM indicator flashing, 134 lit, 135 errors communications, 135 error processing, 131 fatal, 135 identifying, 133 non-fatal, 134
171
programming, 136
Programming Console operations, 136 reading/clearing messages, Programming Console, 103 user-defined errors, 134
Expansion I/O Units available models, 9, 159 components, 38 connection, 48 standard models, 159 expansion instructions, reading and changing function code assignments, 104
Expansion Memory Unit, 149 connections, 153
Expansion Units available models, 9, 160 connection, 48
Index
PC status indicators, 36 inductive loads, 61, 75 initialization, time required, 12 input devices, connecting, 59 input specifications, 31, 32 inputs, wiring, 54 configuration, 54 inrush current, suppressing, 75 inspections, 145 installation, 46 site, selecting, 44 instructions inserting and deleting, Programming Console, 110 searching, Programming Console, 108 insulation resistance, 28 interlocks, 44 interrupt program execution, in cyclic operation, 15
F
FAL numbers, 134
FAL(06), 134
FALS numbers, 135
FALS(07), 134 false inputs, 61 fatal errors, troubleshooting, 139 features, 2 flash memory, precautions, 132 flicker output, example, 128 force-set/reset clearing, Programming Console, 122
Programming Console, 121 function codes, reading and changing expansion instruction assignments, 104 functions, 7 grounding, 36, 51 hexadecimal data, converting displays, Programming Console,
122
Host Link, connections, 77
I
G–H
I/O capacity, 29
I/O errors, troubleshooting, 141
I/O line noise, preventing, 49 indicators
CompoBus/S LED indicators, 41 flashing ERR/ALM indicator, 134 lit ERR/ALM indicator, 135
L–M leakage current, 61 limit switches, preventing false inputs, 61 machine control functions, list, 16 maintenance, 145 memory backup, 30
Expansion Memory Unit, 149 protection, 30 memory areas clearing, Programming Console, 102 partial clear, 102 uploading/downloading, 150 messages, reading/clearing, 103 mode, changing the PC mode, 97 model numbers, 159 modes, operating modes, 11 modifying binary data, Programming Console, 119 data, Programming Console, 116 hexadecimal/BCD data, Programming Console, 118 signed decimal data, Programming Console, 119
SV, Programming Console, 117 unsigned decimal data, Programming Console, 120
MONITOR mode description, 89, 97 example test run, 129 monitoring
3-word monitor, Programming Console, 115 binary monitor, Programming Console, 114–115 differentiation monitor, Programming Console, 113–114 signed decimal monitor, Programming Console, 115–116 status, Programming Console, 111 unsigned decimal monitor, Programming Console, 116 motor control, capabilities, 3
MSG(46), 134
172
N no-protocol communications, 80 noise, preventing electrical noise, 45, 49 noise immunity, 28 non-fatal errors, troubleshooting, 140
NPN current output, connecting, 59
NPN open collector, connecting, 59
NT Link, connections, 80
O operating conditions, troubleshooting, 143 operating modes, 11 operating mode at startup, 11 operation, preparations, 99 output short protection, 74 output specifications relay output, 33 transistor output, sink type, 34 output wiring configuration, 63, 66, 70 relay output, 62 transistor output sink type, 66 source type, 70
P panel, Programming Console installation, 98 panel installation, precautions, 45 password, entering on Programming Console, 99
PC mode, changing, 97
PC Status, indicators, 36
Peripheral Devices, 162 available models, 162 photoelectric switches, preventing false inputs, 61
PNP current output, connecting, 59 position control, 3 power, consumption, 28 power cables, 49 power interruption, detection, 12 power supply capacity, 28 interrupt time, 28 precautions, 44 troubleshooting, 138, 144 wiring, 52 precautions design precautions, 44
Index general, xi uploading/downloading, 150 program, programming example, 124 program capacity, 29 program execution, in cyclic operation, 14 program memory, setting address and reading content, Programming Console, 105
PROGRAM mode, description, 89, 97 programming checking the program, 129 checks for syntax, Programming Console, 111 errors, 136 inserting and deleting instructions, Programming Console,
110–111 preparation for, 124 searching, Programming Console, 108–109 setting and reading a memory address, Programming Console, 105
Programming Console connecting, 76, 98 keys, 95 models, 95 operations, 101
Programming Devices connecting, 76 using, 83 programming example, 124 programs checking, check levels, 136 downloading, 155 entering and editing, Programming Console, 105 uploading, 154 proximity switches, preventing false inputs, 61 pulse control, 3 pulse outputs, 3 wiring, 74
Q–R quick-response inputs, 4 relay outputs, connecting, 59
RUN mode, description, 89, 97
S search instruction, Programming Console, 108–109 operands, Programming Console, 109 self-diagnosis functions, 30 self-holding bit, example, 126 self-diagnostic functions, 133 serial communications, 80 shock resistance, 28 signed decimal data
173
modifying, Programming Console, 119 monitoring, 115–116 specifications characteristics, 29
Expansion Memory Unit, 151 general specifications, 28 input specifications, 31, 32 output specifications relay output, 33 transistor output, sink type, 34
SSS, 92 status, monitoring, Programming Console, 111
Support Software, 76, 84
SV, modifying, Programming Console, 117 syntax, checking the program, Programming Console, 111
SYSMAC Support Software, 76
See also SSS precautions, 92
SYSMAC-CPT Support Software, 76, 84 precautions, 84 system, checks, 132 system configuration, 8
T temperature, operating, storage, 28
Temperature Sensor Units precautions, xv standard models, 160 temperature, ambient, 28 terminal block, removing, 50
Index terminals, screw size, 28 test run example, 129 procedure, 132 time. See clock timers changing SV, Programming Console, 117 example of inputting, 127 troubleshooting, 137 fatal errors, 139
I/O errors, 141 non-fatal errors, 140 operating conditions, 143 power supply, 138, 144
U–W unsigned decimal data modifying, Programming Console, 120 monitoring, 116 uploading, programs, 154 vibration resistance, 28 voltage operating voltage range, 28 supply voltage, 28 voltage output, connecting, 59 weight
CPU Unit, 28
Expansion I/O Unit, 28
Expansion Unit, 28 wiring, 49 power supply, 52
174
Revision History
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
Cat. No. W352-E1-3
Revision code
The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version.
Revision code
1
2
3
Date
April 1999 Original production
Revised content
September 1999 Information relating to 20-point CPU Units added throughout the manual.
Information relating to the CPM1-EMU01-V1 Expansion Memory Unit added throughout the manual.
December 1999 Information relating to Temperature Sensor Units added throughout the manual.
175
Download
Advertisement
Key features
Compact and high-speed
Synchronized pulse control
Interrupt inputs and pulse outputs
Analog settings and clock function
Expansion I/O Units (up to 120 I/O points)
Analog I/O Units
Temperature Sensor Units
CompoBus/S I/O Link Units
Host Link and other communications functions
Frequently asked questions
The CPM2A offers compact size, high speed, synchronized pulse control, interrupt inputs, pulse outputs, analog settings, and a clock function. It also allows for expansion up to 120 I/O points with expansion I/O units, analog I/O, temperature sensors, and CompoBus/S support.
The CPM2A CPU Unit comes in variations with 20, 30, 40, or 60 built-in I/O terminals.
Yes, the CPM2A supports analog I/O Units which can provide up to 6 analog inputs and 3 analog outputs. The PID instruction can be used with these units for PID control.
The CPM2A provides Host Link capability through both its RS-232C port and Peripheral port. This allows communication with personal computers and Programmable Terminals for data exchange and system control.