Omron CIMR-E7Z4090 User manual
Pubblicità
Pubblicità
Manual No.
TOE-S616-56.1-0
3-OY
VARISPEED E7
Variable Torque Frequency Inverter
USER’S MANUAL
Table of Content
1
2
Safety Precautions and Instructions for Use........................................ VIII
Registered Trademarks......................................................................... XV
Handling Inverters .................................................................. 1-1
Exterior and Mounting Dimensions ..............................................................1-9
Checking and Controlling the Installation Site ...........................................1-13
Installation Orientation and Space .............................................................1-15
Accessing the Inverter Terminals ..............................................................1-16
Removing the Terminal Cover (IP00 and NEMA 1 / IP20 Inverters) ........................... 1-16
Removing/Attaching the Digital Operator and Front Cover .......................1-18
Wiring....................................................................................... 2-1
I
II
3
4
5
Installing and Wiring Option Cards ............................................................ 2-38
Digital Operator and Modes....................................................3-1
Trial Operation .........................................................................4-1
Setting the Power Supply Voltage Jumper
User Parameters ......................................................................5-1
Digital Operation Display Functions and Levels .......................................... 5-3
6
Setting Values that Change with the V/f Pattern Selection (E1-03) ............................. 5-46
Parameter Settings by Function............................................ 6-1
Selecting the Stopping Method when a Stop Command is Input ................................. 6-11
Acceleration and Deceleration Characteristics ..........................................6-15
Preventing the Motor from Stalling During Acceleration
Adjusting Frequency References ..............................................................6-21
Jump Frequency Function (Operation Avoiding Resonance) ...................................... 6-23
(Frequency Reference Limit Function) ......................................................6-24
Improved Operating Performance .............................................................6-27
III
IV
Continuing Operation at Constant Speed When Frequency Reference Is Lost .......... 6-44
Restarting Operation After Transient Fault (Auto Restart Function) ........................... 6-45
Stopping Acceleration and Deceleration
Raising and Lowering Frequency References Using
Switching Operation Source to Communication Option Card ..................................... 6-60
Switching Operation Source to MEMOBUS communication ....................................... 6-60
Jog Frequency Operation without Forward and Reverse Commands (FJOG/RJOG) 6-62
7
8
9
Troubleshooting ..................................................................... 7-1
Protective and Diagnostic Functions ...........................................................7-2
If the Motor Operates at Higher Speed than the Frequency Reference ...................... 7-17
If the Earth Leakage Breaker Operates when a RUN Command is Input ................... 7-19
If OV (Overvoltage) or OC (Overcurrent) is Detected
If Output Frequency Does Not Rise to Frequency Reference ..................................... 7-20
Maintenance and Inspection.................................................. 8-1
Specifications ......................................................................... 9-1
10 Appendix ............................................................................... 10-1
Power Transmission Mechanism (Speed Reducers, Belts and Chains) ..................... 10-5
V
VI
Warnings
CAUTION
Cables must not be connected or disconnected, nor signal tests carried out, while the power is switched on.
The Varispeed E7 DC bus capacitor remains charged even after the power has been switched off. To avoid an electric shock hazard, disconnect the frequency inverter from the mains before carrying out maintenance. Then wait for at least 5 minutes after all LEDs have gone out.
Do not perform a withstand voltage test on any part of the Varispeed. The frequency inverter contains semiconductors, which are not designed for such high voltages.
Do not remove the digital operator while the mains supply is switched on. The printed circuit board must also not be touched while the inverter is connected to the power.
Never connect general LC/RC interference suppression filters, capacitors or overvoltage protection devices to the inverter input or output.
To avoid unnecessary overcurrent faults, etc. being displayed, the signaling contacts of any contactor or switch fitted between inverter and motor must be integrated into the inverter control logic
(e.g. baseblock).
This is absolutely imperative!
This manual must be read thoroughly before connecting and operating the inverter. All safety precautions and instructions for use must be followed.
The inverter may must be operated with the appropriate line filters, following the installation instructions in this manual and with all covers closed and terminals covered.
Only then will adequate protection be provided. Please do not connect or operate any equipment with visible damage or missing parts. The operating company is responsible for any injuries or equipment damage resulting from failure to heed the warnings in this manual.
VII
VIII
Safety Precautions and Instructions for Use
General
Please read these safety precautions and instructions for use thoroughly before installing and operating this inverter. Also read all of the warning signs on the inverter and ensure they are never damaged or removed.
Live and hot inverter components may be accessible during operation. Removal of housing components, the digital operator or terminal covers runs the risk of serious injuries or damage in the event of incorrect installation or operation. The fact that frequency inverters control rotating mechanical machine components can give rise to other dangers.
The instructions in this manual must be followed. Installation, operation and maintenance may only be carried out by qualified personnel. For the purposes of the safety precautions, qualified personnel are defined as individuals who are familiar with the installation, starting, operation and maintenance of frequency inverters and have the proper qualifications for this work. Safe operation of these units is only possible if they are used properly for their intended purpose.
The DC bus capacitors can remain live for about 5 minutes after the inverter is disconnected from the power.
It is therefore necessary to wait for this time before opening its covers. All of the main circuit terminals may still carry dangerous voltages.
Children and other unauthorized persons must not be allowed access to these inverters.
Keep these Safety Precautions and Instructions for Use readily accessible and supply them to all persons with any form of access to the inverters.
Intended Use
Frequency inverters are intended for installation in electrical systems or machinery.
Their installation in machinery and systems must conform to the following product standards of the Low Voltage Directive:
EN 50178, 1997-10, Equipping of Power Systems with Electronic Devices
EN 60204-1, 1997-12Machine Safety and Equipping with Electrical Devices
Part 1: General Requirements (IEC 60204-1:1997)/
Please note: Includes Corrigendum of September 1998
EN 61010-1, A2, 1995Safety Requirements for Information Technology Equipment
(IEC 950, 1991 + A1, 1992 + A2, 1993 + A3, 1995 + A4, 1996, modified)
CE marking is carried out to EN 50178, using the line filters specified in this manual and following the appropriate installation instructions.
Transportation and storage
The instructions for transportation, storage and proper handling must be followed in accordance with the technical data.
Installation
Install and cool the inverters as specified in the documentation. The cooling air must flow in the specified direction. The inverter may therefore only be operated in the specified position (e.g. upright). Maintain the specified clearances. Protect the inverters against impermissible loads. Components must not be bent nor insulation clearances changed. To avoid damage being caused by static electricity, do not touch any electronic components or contacts.
Electrical Connection
Carry out any work on live equipment in compliance with the national safety and accident prevention regulations. Carry out electrical installation in compliance with the relevant regulations. In particular, follow the installation instructions ensuring electromagnetic compatibility (EMC), e.g. shielding, grounding, filter arrangement and laying of cables. This also applies to equipment with the CE mark. It is the responsibility of the manufacturer of the system or machine to ensure conformity with EMC limits.
Your supplier or Omron Yaskawa Motion Control representative must be contacted when using leakage current circuit breaker in conjunction with frequency inverters.
In certain systems it may be necessary to use additional monitoring and safety devices in compliance with the relevant safety and accident prevention regulations. The frequency inverter hardware must not be modified.
Notes
The Varispeed E7 frequency inverters are certified to CE, UL, and cUL except the IP54 version which is certified to CE only.
IX
X
EMC Compatibility
Introduction
This manual was compiled to help system manufacturers using OMRON YASKAWA Motion Control
(OYMC) frequency inverters design and install electrical switch gear. It also describes the measures necessary to comply with the EMC Directive. The manual's installation and wiring instructions must therefore be followed.
Our products are tested by authorized bodies using the standards listed below.
Product standard: EN 61800-3:1996
EN 61800-3; A11:2000
Measures to Ensure Conformity of OYMC Frequency inverters to the EMC Directive
OYMC frequency inverters do not necessarily have to be installed in a switch cabinet.
It is not possible to give detailed instructions for all of the possible types of installation. This manual therefore has to be limited to general guidelines.
All electrical equipment produces radio and line-borne interference at various frequencies. The cables pass this on to the environment like an aerial.
Connecting an item of electrical equipment (e.g. drive) to a supply without a line filter can therefore allow HF or LF interference to get into the mains.
The basic countermeasures are isolation of the wiring of control and power components, proper grounding and shielding of cables.
A large contact area is necessary for low-impedance grounding of HF interference. The use of grounding straps instead of cables is therefore definitely advisable.
Moreover, cable shields must be connected with purpose-made ground clips.
Laying Cables
Measures Against Line-Borne Interference:
Line filter and frequency inverter must be mounted on the same metal plate. Mount the two components as close to each other as possible, with cables kept as short as possible.
Use a power cable with well-grounded shield. For motor cables up to 50 meters in length use shielded cables.
Arrange all grounds so as to maximize the area of the end of the lead in contact with the ground terminal (e.g.
metal plate).
Shielded Cable:
– Use a cable with braided shield.
– Ground the maximum possible area of the shield. It is advisable to ground the shield by connecting the cable to the ground plate with metal clips (see following figure).
Ground clip Ground plate
The grounding surfaces must be highly conductive bare metal. Remove any coats of varnish and paint.
– Ground the cable shields at both ends.
– Ground the motor of the machine.
Further informations can be found in the document EZZ006543 which can be ordered at Omron Yaskawa
Motion Control.
XI
XII
Line Filters
The IP54 version is already equipped with a internal EMC filter. For the IP00 and NEMA 1 / IP20 versions of the Varispeed E7 the recommended line filters are as follows:
Recommended Line Filters for Varispeed E7 (IP00 and NEMA 1 / IP20)
Inverter Model
Varispeed E7
(IP00/20)
CIMR-E7Z40P4
Model
Line Filter
EN
55011 Class
Current
(A)
Weight
(kg)
Dimensions
W x D x H
CIMR-E7Z40P7
3G3RV-PFI3010-SE 10 1.1
141 x 46 x 330
CIMR-E7Z41P5
CIMR-E7Z42P2
CIMR-E7Z43P7
3G3RV-PFI3018-SE
B, 25 m
*1
18 1.3
141 x 46 x 330 CIMR-E7Z44P0
CIMR-E7Z45P5
CIMR-E7Z47P5
3G3RV-PFI3035-SE 35 2.1
206 x 50 x 355
CIMR-E7Z4011
CIMR-E7Z4015
CIMR-E7Z4018
3G3RV-PFI3060-SE 60 4.0
236 x 65 x 408
CIMR-E7Z4022
CIMR-E7Z4030
CIMR-E7Z4037
CIMR-E7Z4045
CIMR-E7Z4055
CIMR-E7Z4075
CIMR-E7Z4090
CIMR-E7Z4110
3G3RV-PFI3070-SE
3G3RV-PFI3130-SE
3G3RV-PFI3170-SE
3G3RV-PFI3200-SE
A, 100 m
70
130
170
250
3.4
4.7
6.0
11
80 x 185 x 329
90 x 180 x 366
120 x 170 x 451
130 x 240 x 610
CIMR-E7Z4132
CIMR-E7Z4160
CIMR-E7Z4185
3G3RV-PFI3400-SE 400 18.5
300 x 160 x 610
3G3RV-PFI3600-SE 600 11,0 260 x 135 x 386
CIMR-E7Z4220
CIMR-E7Z4300
*1.
Class A, 100 m
3G3RV-PFI3800-SE 800 31.0
300 x 160 x 716
Permissible emission of power drive systems for commercial and light environment (EN61800-3, A11)
(general availability, 1st environment)
Inverter Model
Varispeed E7
(IP00/20)
Type
EN
55011
Class
Line Filters
Current
(A)
CIMR-E7Z20P4
CIMR-E7Z20P7
CIMR-E7Z21P5
CIMR-E7Z22P2
CIMR-E7Z23P7
CIMR-E7Z25P5
CIMR-E7Z27P5
CIMR-E7Z2011
3G3RV-PFI3010-SE
3G3RV-PFI3018-SE
3G3RV-PFI2035-SE
3G3RV-PFI2060-SE
B, 25 m
*1
CIMR-E7Z2015
CIMR-E7Z2018
CIMR-E7Z2022
CIMR-E7Z2030
3G3RV-PFI2100-SE
3G3RV-PFI2130-SE
CIMR-E7Z2037
CIMR-E7Z2045
3G3RV-PFI2160-SE
3G3RV-PFI2200-SE A, 100 m
CIMR-E7Z2055
CIMR-E7Z2075
3G3RV-PFI3400-SE
CIMR-E7Z2090
CIMR-E7Z2110 3G3RV-PFI3600-SE
*1.
Class A, 100 ambient temperature: 45°C max
10
18
35
60
100
130
160
200
400
600
Weight
(kg)
1.1
1.3
1.4
3
4.9
4.3
6.0
11.0
18.5
11.0
Dimensions
W x D x H
141 x 45 x 330
141 x 46 x 330
141 x 46 x 330
206 x 60 x 355
236 x 80 x 408
90 x 180 x 366
120 x 170 x 451
130 x 240 x 610
300 x 160 x 564
260 x 135 x 386
EMC Specifications of Varispeed E7 (IP54)
The Varispeed E7 IP54 is already equipped with an internal EMC filter. The Varispeed E7 IP54 complies with
EN55011 class A with a motor cable length up to 25m.
For the wiring methods to comply with the EMC regulations for the Varispeed E7 (IP54) refer to page
XIII
XIV
Installation inverters and EMC filters
PE
L1 L3
L2
Ground Bonds
( remove any paint )
PE
Line
Filter
Load
Inverter
PE
L1 L3
L2
U
V
W
PE
Cable Length as short as possible
Metal Plate
Ground Bonds
( remove any paint )
M
3~
Motor cable screened
Registered Trademarks
The following registered trademarks are used in this manual.
•
DeviceNet is a registered trademark of the ODVA (Open DeviceNet Vendors Association, Inc.).
•
InterBus is a registered trademark of Phoenix Contact Co.
•
ControlNet is a registered trademark of ControlNet International, Ltd.
•
LONworks is a registered trademark of the Echelon.
•
Metasys is a registered trademark of Johnson Controls Inc.
•
CANopen is a registered trademark of CAN in Automation e.V.
XV
XVI
1
Handling Inverters
This chapter describes the checks required upon receiving or installing an Inverter.
Varispeed E7 Introduction..................................................1-2
Confirmations upon Delivery..............................................1-4
Exterior and Mounting Dimensions ....................................1-9
Checking and Controlling the Installation Site .................1-13
Installation Orientation and Space ...................................1-15
Accessing the Inverter Terminals.....................................1-16
Removing/Attaching the Digital Operator and Front Cover1-18
1-2
Varispeed E7 Introduction
Varispeed E7 Applications
The Varispeed E7 is ideal for the following applications.
•
Fan, blower and pump applications with variable torque characteristics.
Settings must be adjusted to the application for optimum operation. Refer to
.
Varispeed E7 Models
The Varispeed E7 Series includes Inverters in two voltage class es: 200 V and 400 V. The maximum motor capacities vary from 0.55 to 300 kW. The inverter is available in protection classes IP00, IP20 and IP54 according to the following table:
Table 1.1 Varispeed E7 Models
Voltage Class
200 V class
22
30
37
45
7.5
11
15
18.5
Maximum
Motor
Capacity kW
0.55
0.75
1.5
2.2
3.7
5.5
55
75
90
110
Varispeed E7
Output
Capacity kVA
1.2
1.6
2.7
3.7
5.7
8.8
32
44
55
69
12
17
22
27
82
110
130
160
Basic Model Number
CIMR-E7Z20P4
CIMR-E7Z20P7
CIMR-E7Z21P5
CIMR-E7Z22P2
CIMR-E7Z23P7
CIMR-E7Z25P5
CIMR-E7Z27P5
CIMR-E7Z2011
CIMR-E7Z2015
CIMR-E7Z2018
CIMR-E7Z2022
CIMR-E7Z2030
CIMR-E7Z2037
CIMR-E7Z2045
CIMR-E7Z2055
CIMR-E7Z2075
CIMR-E7Z2090
CIMR-E7Z2110
Specifications
(Always specify through the protective structure when ordering.)
IEC IP00
CIMR-E7Z
NEMA 1 (IEC IP20)
CIMR-E7Z
IEC IP54
CIMR-E7Z
20P41 -
20P71 -
Remove the top and bottom covers from the IP20 model.
21P51
22P21
23P71
25P51
-
-
-
-
27P51
20111
20151
20181 -
-
-
-
20220
20300
20370
20450
20550
20750
20900
21100
20221
20301
20371
20451
20551
20751
-
-
-
-
-
-
-
-
-
-
Varispeed E7 Introduction
Voltage Class
400 V class
18.5
22
30
37
5.5
7.5
11
15
Maximum
Motor
Capacity kW
0.55
0.75
1.5
2.2
3.7
4.0
110
132
160
185
45
55
75
90
220
300
Varispeed E7
Output
Capacity kVA
1.4
1.6
2.8
4.0
5.8
6.6
30
34
46
57
9.5
13
18
24
160
200
230
280
69
85
110
140
390
510
Basic Model Number
CIMR-E7Z40P4
CIMR-E7Z40P7
CIMR-E7Z41P5
CIMR-E7Z42P2
CIMR-E7Z43P7
CIMR-E7Z44P0
CIMR-E7Z45P5
CIMR-E7Z47P5
CIMR-E7Z4011
CIMR-E7Z4015
CIMR-E7Z4018
CIMR-E7Z4022
CIMR-E7Z4030
CIMR-E7Z4037
CIMR-E7Z4045
CIMR-E7Z4055
CIMR-E7Z4075
CIMR-E7Z4090
CIMR-E7Z4110
CIMR-E7Z4132
CIMR-E7Z4160
CIMR-E7Z4185
CIMR-E7Z4220
CIMR-E7Z4300
Specifications
(Always specify through the protective structure when ordering.)
IEC IP00
CIMR-E7Z
NEMA 1 (IEC IP20)
CIMR-E7Z
IEC IP54
CIMR-E7Z
40P41 -
40P71 -
Remove the top and bottom covers from the IP20 model.
41P51
42P21
43P71
44P01
-
-
-
-
45P51
47P51
40111
40151
-
47P52
40112
40152
40220
40300
40370
40450
40550
40750
40900
40181
40221
40301
40371
40451
40551
40751
40901
40182
40222
40302
40372
40452
40552
-
-
41100
41320
41600
41850
42200
43000
41101
41321
41601
-
-
-
-
-
-
-
-
-
1-3
1-4
Confirmations upon Delivery
Checks
Check the following items as soon as the Inverter is delivered.
Table 1.2 Checks upon delivery
Item Method
Has the correct Inverter model been delivered?
Check the model number on the nameplate on the side of the Inverter.
Is the Inverter damaged in any way?
Are any screws or other components loose?
Inspect the entire exterior of the Inverter to see if there are any scratches or other damage resulting from shipping.
Use a screwdriver or other tools to check for tightness.
Additionally check that following parts are delivered in the package with the IP54 inverter:
Table 1.3 Additional Deliveries with IP54 Inverters
Part Name
Cable Gland (for Input)
Cable Gland (for Motor Output)
Cable Gland (for Control)
Cable Gland (for Fieldbus)
Door Key
Blind Plug (Control Cable Entry)
Blind Plug (Fieldbus Cable Entry)
1
1
1
1
Qty.
1
1
1
If any irregularities in the above items are found, contact the agency from which the Inverter was purchased or your Omron Yaskawa Motion Control representative immediately.
Nameplate Information
There is a nameplate attached to the side of each Inverter. The nameplate shows the model number, specifications, lot number, serial number, and other information on the Inverter.
Example Nameplate
The following nameplate is an example for a standard European Inverter: 3-phase, 400 VAC, 0.55 kW,
NEMA 1 / IP20 standards
Inverter model
Input specifications
Output specifications
Lot number
Serial number
MODEL: CIMR-E7Z40P4
SPEC: 40P41A
OUTPUT: AC3PH 0-480V 0-200Hz 1.8A 1.4kVA
Inverter specifications
Mass
Software Number
Fig 1.1 Nameplate Example
Confirmations upon Delivery
Inverter Model Numbers
The model number of the Inverter on the nameplate indicates the specification, voltage class, and maximum motor capacity of the Inverter in alphanumeric codes.
CIMR – E7Z40 P4
Inverter
Varispeed E7
European Spec.
Max. Motor Power
0P4 0.55 kW
0P7
to
0.75 kW
to
300 300 kW
Voltage Class
2 200 V
4 400 V
Fig 1.2 Inverter Model Numbers
Inverter Specifications
The Inverter specifications (“SPEC”) on the nameplate indicate the voltage class, maximum motor capacity, the protective structure, and the revision of the Inverter in alphanumeric codes.
40P41A
Voltage Class
2 200 V
4 400 V
Max. Motor Power
0P4
0P7
to
300
0.55 kW
0.75 kW
to
300 kW
Revision
Protection
0
1
2
IP00
IP20
IP54
Fig 1.3 Inverter Specifications
Inverter Software Version
The Inverter software version can be read out from the monitor parameter U1-14. The parameter shows the last four digits of the software number (e.g. display is “3021” for the software version VSE103021).
IMPORTANT
This manual describes the functionality of the inverter software version VSE103021.
Older software versions do not support all described functions. Check the software versions before starting to work with this manual.
1-5
1-6
Component Names
Inverters of 18.5 kW or Less
The external appearance and component names of the Inverter are shown in
, the terminal arrangement in
Top cover
Front cover
Digital Operator
Mounting hole
Diecast case
Terminal cover
Nameplate
Bottom protective cover
Fig 1.4 NEMA 1 Inverter Appearance (18.5 kW or Less)
IMPORTANT
The top cover is a protection against foreign bodies (screws, metal scrap from drilling etc.), which could fall into the inverter during the installation in the cabinet.
Remove the top cover when the installation is finished!
E(G)
SN SC
S1
SP
S2 S3
A1 A2
S4
+V
S5
AC
S6 S7
-V MP AC
FM AC
RP
AM IG
R+
S+
R-
S-
M5 M6
M3
MA
M4
MB MC
M1 M2 E(G)
Control Circuit Terminals
Main Circuit Terminals
NOT USED
Charge Indicator
Fig 1.5 Terminal Arrangement (18.5 kW or less)
Ground Terminal
Confirmations upon Delivery
Inverters of 22 kW or More
The external appearance and component names of the Inverter are shown in
Mounting holes
Inverter cover
Cooling fan
Front cover
Digital Operator
Nameplate
Terminal cover
Fig 1.6 Inverter Appearance (22 kW or More)
E(G)
SN
S1
SC
S2
SP
S3
A1
S4
A2
S5
+V AC
S6 S7
-V MP
FM
AC
AC
RP R+
AM IG
R-
S+ S-
M5 M6
M3
MA
M4
MB
M1
MC
M2 E(G)
Control Circuit Terminals
Carge Indicator
Main Circuit Terminals
Ground Terminals
Fig 1.7 Terminal Arrangement (22kW or More)
1-7
1-8
Protection Class IP54
The external appearance and component names of the Inverter are shown in
Inverter enclosure
Digital Operator
Door Locks
Nameplate
Door
Mounting Holes
Cable Entry Plate
Fig 1.8 IP54 Inverter Appearance
Exterior and Mounting Dimensions
Exterior and Mounting Dimensions
IP00 Inverters
W1
4-d
W1
4-d t1
W D1
D 3
200 V/400 V Class Inverters of 0.55 to 18.5 kW
W1
Max.10
W
Max.10
5
200 V Class Inverters of 22 or 110 kW
400 V Class Inverters of 22 to 160 kW
Ø
W2
D t1
D1
W3
W1
W
15
400 V Class Inverters of 185 to 300 kW
5
Fig 1.9 Exterior Diagrams of IP00 Inverters
D
D1 t1
1-9
1-10
NEMA 1 / IP20 Inverters
W1
4-d
W1
4-d t1
W
3
200 V/400 V Class Inverters of 0.55 to 18.5 kW
D1
D
Max.10
W
Max.10
Grommet
5
200 V Class Inverters of 22 to 75 kW
400 V Class Inverters of 22 to 160 kW
Fig 1.10 Exterior Diagrams of NEMA 1 / IP20 Inverters
IP54 Inverters
W D
2 - lifting holes
W1
4-d
D t1
D1 t1
Fig 1.11 Exterior Diagrams of IP54 Inverters
Exterior and Mounting Dimensions
Table 1.4 Inverter Dimensions (mm) and Masses (kg) from 0.4 to 160 kW, IP00 and NEMA 1 / IP20
Voltage
Class
Max.
Applicable
Motor
Output
[kW]
200 V
(3phase)
0.55
0.75
1.5
W H
Protection Class IP00
D W1 H1 H2 D1 t1
0.75
1.5
157 39
140 280 126 266 7
2.2
3.7
177 59
5.5
7.5
11
15
200 300 197 186 285 7.5
65.5
240 350 207 216 335 8
18.5
22 250 400
258
195 385
78
7.5
100
30 275 450 220 435
100 37 298
375 600
328
250 575
45
55
450 725 348 325 700
75
90 500 850 358 370 820
12.5
15
110 575 885 378 445 855
0.55
157
130
140
39
5
2.3
3.2
4.5
Appr ox.
Mass
3
4
Dimensions (mm)
W H
140 280
6 300
7
200
310
350
11 240
380
21 254 535
24 279 615
57
380 809
63
D W1 H0 H1 H2 H3 D1 t1
157
177
197 186 300 285
207 216 350 335
258
298
328
Protection Class NEMA 1 / IP20
126 280 266
195 400 385
220 450 435
250 600 575
7
8
7.5
0
10
0
30
135
165
209
12.5
86
453 1027 348 325 725 700 302
87
108 504 1243 358 370 850 820 15 390
39
59
65.5
78
100
100
130
5
2.3
3.2
4.5
Appr ox.
Mass
Moun ting
Holes d*
Caloric Value
(W)
Exter nal
Internal
Total
Heat
Generation
Cooling
Metho d
20 39 59
3
27 42 69
50 50 100
Natural
M5
70 59 129
112 74 186
4
6
7
164 84 248
219 113 332
374 170 544
429 183 612
11 M6
24
501 211 712
586 274 860
Fan
27
62
865 352 1217
1015 411 1426
68
94
95
114
M10
1266 505 1771
1588 619 2207
150
3 157
---
39 3
2019 838 2857
M12
2437 997 3434
2733 1242 3975
14 39 53
17 41 58
36 48 84
Natural
140 280 126 266 7 5 140 280 126 266 266 7 5 M5 2.2
3.7
4.0
5.5
177 59 4 177
0
59 4
59 56 115
80 68 148
91 70 161
127 82 209
400 V
(3phase)
7.5
11
15
18.5
200 300 197 186 285
240 350 207 216 335
8 65.5
78
22
30
37
45
279 450 258 220 435
7.5
100
325 550 283 260 535 105
55
75
90
110
450 725 348 325 700 12.5
130
500 850 358 370 820 15
132
160 575 916 378 445 855 45.8 140
2.3
3.2
4.5
6
10
21
36 329
88
89
102
200 300 197 186 300 285
240 350 207 216 350 335
279 535 258 220 450 435
635
715
283 260 550 535
8
7.5
85
165
453 1027 348 325 725 700 12.5 302
65.5
78
100
105
130
504 1243 358 370 850 820 15 393
120
160 579 1324 378 445 916 855 46 408 140
2.3
3.2
4.5
6
10
24
M6
193 114 307
252 158 410
326 172 498
426 208 634
466 259 725
678 317 995
784 360 1144
901 415 1316
Fan
40
96
97
122
130
170
1203 495 1698
M10
1399 575 1974
1614 671 2285
2097 853 2950
M12 2388 1002 3390
2791 1147 3938
Table 1.5 Inverter Dimensions (mm) and Masses (kg) of 400V Class Inverters of 185 kW to 300 kW, IP00
Voltage
Class
Max.
Applicable Motor
Output
[kW]
185
400V
(3-phase)
220
300
W H D W1
Dimensions (mm)
Protection Class IP00
W2 W3 H1 H2 D1 t1
710 1305 413 540 240 270 1270 15 125.5
4.5
916 1475 413 730 365 365 1440 15 125.5
4.5
Approx.
Mass
Mounting
Holes d
260
External
Caloric Value (W)
Internal
Total
Heat
Generation
3237 1372 4609
280
405
M12 3740
5838
1537
2320
5277
8158
Cooling
Method
Fan
1-11
1-12
Table 1.6 Inverter Dimensions (mm) and Masses (kg) of 400V class inverters 7.5 to 55 kW, IP54
Dimensions (mm)
Voltage
Class
Max.
Applicable Motor
Output
[kW]
400V
(3-phase)
22
30
37
45
55
7.5
11
15
18.5
W
350
410
580
H
600
650
750
D
240
260
300
330
W1
260
270
410
H1
576
620
714
H2
9
12
11 t1
2.5
2.5
2.5
Approx.
Mass
25
30
43
71
Mounting
Holes d
∅ 10
M8
Total
Heat
Generation
302
423
∅ 12
M10
531
655
754
989
∅ 14
M10
1145
1317
1701
Cooling
Method
Fan
Checking and Controlling the Installation Site
Checking and Controlling the Installation Site
Install the Inverter in the installation site described below and maintain optimum conditions.
Installation Site
Install the Inverter under the following conditions in a pollution degree 2 environment.
Type
Protection Class IP20 and IP54
Protection Class IP00
Ambient Operating Temperature
-10 to + 40
°C
-10 to + 45
°C
Humidity
95% RH or less (no condensation)
95% RH or less (no condensation)
Protection covers are attached to the top and bottom of the NEMA 1 and IP00 Inverters. Be sure to remove the top cover before operating a 200 or 400 V Class Inverter with an output of 18.5 kW or less inside a panel.
•
Observe the following precautions when mounting the Inverter.
•
Install the Inverter in a clean location which is free from oil mist and dust. It can be installed in a totally enclosed panel that is completely shielded from floating dust.
•
When installing or operating the Inverter, always take special care so that metal powder, oil, water, or other foreign matter does enter the Inverter.
•
Do not install the Inverter on combustible material, such as wood.
•
Install the Inverter in a location free from radioactive materials and combustible materials.
•
Install the Inverter in a location free from harmful gasses and liquids.
•
Install the Inverter in a location without excessive oscillation.
•
Install the Inverter in a location free from chlorides.
•
Install the Inverter in a location without in direct sunlight.
•
The IP54 Inverters provide protection from non-conductive dust and splashing water from all directions.
Install the Inverter indoors in a heated and controlled environment to avoid condensation inside the
Inverter.
•
Keep any water or dust outside of the IP54 Inverter when wiring.
Controlling the Ambient Temperature
To enhance the reliability of operation, the Inverter should be installed in an environment free from extreme temperature increases. If the IP00 or NEMA 1 Inverter is installed in an enclosed environment, such as a box, use a cooling fan or air conditioner to maintain the internal air temperature below 45
°C.
When the IP54 Inverter is installed in a environment with low temperatures or when the Inverter remains switched off for a long time, condensation may occur inside the Inverter. In that case additional heaters may effectively prevent condensation inside the inverter.
Protecting the IP00 or NEMA 1 Inverter from Foreign Matter
Place a cover over the Inverter during installation to shield it from metal power produced by drilling.
Always remove the cover from the Inverter after completing installation. Otherwise, ventilation will be reduced, causing the Inverter to overheat.
1-13
1-14
Additional Installation Precautions for the IP54 Inverters
•
Ensure that the door locks are closed before carrying the Inverter. Always hold the case when carrying the
Inverter, do not carry it holding the door or the cable glands. If the door locks are open or the Inverter is held by the door (or cable glands) when carrying the main body of the Inverter may fall, possibly resulting injury.
•
Pay attention not to damage the cable glands when lifting. Otherwise the equipment may be damaged by ingress of water or dust.
Keeping the IP54 protection
•
Mount the blind plugs attached for option and control entry if these terminals are not connected
•
Pay attention not to damage the cable glands during the installation
Installation Orientation and Space
Installation Orientation and Space
Install the Inverter vertically so as not to reduce the cooling effect. When installing the Inverter, always provide the following installation space to allow normal heat dissipation.
A
B
Air
50mm min.
30mm min.
30mm min.
Horizontal Space
120mm min.
Vertical Space
Air
200V class inverter, 0.55 to 90 kW
400V class inverter, 0.55 to 132 kW
200V class inverter, 110 kW
400V class inverter, 160 to 220 kW
400V class inverter, 300 kW
A B
50 mm 120 mm
120 mm 120 mm
300 mm 300 mm
Fig 1.12 Inverter Installation Orientation and Space
IMPORTANT
1. The same space is required horizontally and vertically for Inverters of all protection classes, either
IP00, NEMA 1 / IP20 and IP54 Inverters.
2. Always remove the top cover after installing a 200 or 400 V Class Inverter with an output of 18.5 kW or less in a panel.
3. Always provide enough space for suspension eye bolts and the main circuit lines when installing a
200 or 400 V Class Inverter with an output of 22 kW or more in a panel.
4. When IP54 Inverters are installed side by side provide a distance of 60mm or more between the
Inverters
1-15
1-16
Accessing the Inverter Terminals
Removing the Terminal Cover (IP00 and NEMA 1 / IP20 Inverters)
Inverters of 18.5 kW or Less
Loosen the screw at the bottom of the terminal cover, press in on the sides of the terminal cover in the directions of arrows 1, and then lift up on the terminal in the direction of arrow 2.
1
2
1
Fig 1.13 Removing the Terminal Cover (Model CIMR-E7Z25P51 Shown Above)
Inverters of 22 kW or More
Loosen the screws on the left and right at the top of the terminal cover, pull out the terminal cover in the direction of arrow 1 and then lift up on the terminal in the direction of arrow 2.
2
1
Fig 1.14 Removing the Terminal Cover (Model CIMR-E7Z20220 Shown Above)
Attaching the Terminal Cover
When wiring the terminal block has been completed, attach the terminal cover by reversing the removal procedure.
For Inverters with an output of 18.5 kW or less, insert the tab on the top of the terminal cover into the groove on the Inverter and press in on the bottom of the terminal cover until it clicks into place.
Accessing the Inverter Terminals
Opening the Door (IP54 Inverters)
Unlock the door locks with the provided key by pushing and rotating it 90 degrees in the directions of arrow 1 and open the door in the direction of arrow 2.
When opening the door, always take special care so that powder, oil, water or other foreign materials do not enter the Inverter.
1
2
OPEN
CLOSE
1
Fig 1.15 Opening the door on a IP54 inverter
IMPORTANT
Max. permitted door opening angle is approx. 135 degrees.
Opening the door over 135 degrees may damage the door hinges.
If the inverter is put into horizontal orientation for wiring or maintenance, the door should be supported and operation should be finished quickly to avoid stress to the door hinges.
Closing the Door (IP54 Inverters)
Close and lock the door tightly by reversing the opening procedure.
1-17
1-18
Removing/Attaching the Digital Operator and
Front Cover
The digital operator can only be removed on Inverters in protection class IP00 and NEMA 1 / IP20
Inverters of 18.5 kW or Less
To attach optional cards or change the terminal board, remove the Digital Operator and front cover in addition to the terminal cover. Always remove the Digital Operator from the front cover before removing the front cover itself.
The removal and attachment procedures are described below.
Removing the Digital Operator
Press the lever on the side of the Digital Operator in the direction of arrow 1 to unlock the Digital Operator and lift the Digital Operator in the direction of arrow 2 to remove the Digital Operator as shown in the following illustration.
2
1
Fig 1.16 Removing the Digital Operator (Model CIMR-E7Z45P5 Shown Above)
Removing/Attaching the Digital Operator and Front Cover
Removing the Front Cover
Press the left and right sides of the front cover in the directions of arrows 1 and lift the bottom of the cover in the direction of arrow 2 to remove the front cover as shown in the following illustration.
1
2
Fig 1.17 Removing the Front Cover (Model CIMR-E7Z45P5 Shown Above)
Mounting the Front Cover
After wiring the terminals, mount the front cover to the Inverter by performing the steps to remove the front cover in reverse order.
1. Do not mount the front cover with the Digital Operator attached to the front cover; otherwise, Digital
Operator may malfunction due to imperfect contact.
1. Insert the tab of the upper part of the front cover into the groove of the Inverter and press the lower part of the front cover onto the Inverter until the front cover snaps shut.
Mounting the Digital Operator
After attaching the terminal cover, mount the Digital Operator onto the Inverter using the following procedure.
1. Hook the Digital Operator at A (two locations) on the front cover in the direction of arrow 1 as shown in the following illustration.
1. Press the Digital Operator in the direction of arrow 2 until it snaps in place at B (two locations).
A
B
Fig 1.18 Mounting the Digital Operator
1-19
1-20
IMPORTANT
1. Do not remove or attach the Digital Operator or mount or remove the front cover using methods other than those described above, otherwise the Inverter may break or malfunction due to imperfect contact.
2. Never attach the front cover to the Inverter with the Digital Operator attached to the front cover. Imperfect contact can result.
Always attach the front cover to the Inverter by itself first, and then attach the Digital Operator to the front cover.
Inverters of 22 kW or More
For inverters with an output of 22 kW or more, remove the terminal cover and then use the following procedures to remove the Digital Operator and front cover.
Removing the Digital Operator
Use the same procedure as for Inverters with an output of 18.5 kW or less.
Removing the Front Cover
Lift up at the location label 1 at the top of the control circuit terminal card in the direction of arrow 2.
2
1
Fig 1.19 Removing the Front Cover (Model CIMR-E7Z2022 Shown Above)
Attaching the Front Cover
After completing required work, such as mounting an optional card or setting the terminal card, attach the front cover by reversing the procedure to remove it.
1. Confirm that the Digital Operator is not mounted on the front cover. Contact faults can occur if the cover is attached while the Digital Operator is mounted to it.
2. Insert the tab on the top of the front cover into the slot on the Inverter and press in on the cover until it clicks into place on the Inverter.
Attaching the Digital Operator
Use the same procedure as for Inverters with an output of 18.5 kW or less.
2
Wiring
This chapter describes wiring terminals, main circuit terminal connections, main circuit terminal
wiring specifications, control circuit terminals, and control circuit wiring specifications.
Connection Diagrams ........................................................2-2
Terminal Block Configuration .............................................2-5
Wiring Main Circuit Terminals ............................................2-7
Wiring Control Circuit Terminals ......................................2-27
Wiring Check....................................................................2-37
Installing and Wiring Option Cards ..................................2-38
2-2
Connection Diagrams
The connection diagrams of the Inverters are shown in
When using the Digital Operator, the motor can be operated by wiring only the main circuits.
DC reactor to improve input power factor (optional)
U X
Short-circuit bar
1
Fuse
Main contactor
1 2
Varispeed E7
Motor
3-phase power supply
L1
L2
380 to 480 V
50/60 Hz
L3
PE
Line
Filter
R/L1
S/L2
T/L3
CIMR-
E7Z47P51
U/T1
V/T2
W/T3
M
2
MA
MB
MC
Fault contact output
250 VAC, 1 A max.
30 VDC, 1 A max.
Multi-function digital inputs
[Factory settings]
Forward Run/Stop
Reverse Run/Stop
External fault
Fault reset
Multi-step speed setting 1
Multi-step speed setting 2
Jog frequency selection
S1
S5
S6
S7
SN
SC
SP
S2
S3
S4
24V
E(G)
Shield terminal
M1
M2
M3
M4
Contact output 1
[Default: During run]
Contact output 2
[Default: Zero speed]
Shield terminal
E(G)
3
Multi-function digital output
250 VAC, 1 A max.
30 VDC, 1 A max.
2k Ω
Adjustment
3
1
2
0 to 10V
4 to 20mA
P
2k
Ω
P
+V
Analog input power supply
+15 V, 20 mA
A1
Analog input 1: Master frequency reference
A2
AC
Multi-function analog input 1:
[Default: Frequency Bias
4 to 20 mA (250 )]
-V
0V
Analog input power supply
-15 V, 20 mA
FM
AM
AC
Adjustment,
20 k
Ω
+
FM
-
Multi-function analog output 1
(0 to 10 V, 2 mA)
[Default: Output frequency , 0 to 10 V]
Adjustment,
20 k
Ω
+
AM
-
Multi-function analog output 2
(0 to 10 V, 2 mA)
[Default: Output power, 0 to 10 V]
Input Option Cards
Terminating resistance
MEMOBUS communication
RS-485/422
P
P
R+
R-
S+
S-
IG
Shielded wires P
Twisted-pair shielded wires
Fig 2.1 Connection Diagram of IP20 Inverters (Model CIMR-E7Z47P51 Shown Above)
Connection Diagrams
3-phase power supply
380 to 480 V
50/60 Hz
L1
L2
L3
PE
Fuse
Multi-function digital inputs
[Factory settings]
Forward Run/Stop
Reverse Run/Stop
External fault
Fault reset
Multi-step speed setting 1
Multi-step speed setting 2
Jog frequency selection
Main contactor
DC reactor to improve input power factor (optional)
U X
Short-circuit bar
R/L1
S/L2
T/L3
1 2
Varispeed E7
CIMR-E7Z47P52
U/T1
V/T2
W/T3
2kΩ
Adjustment
3
2
0 to 10V
1
4 to 20mA
P
2k
Ω
P
1
Motor
M
S1
S2
S3
S4
S5
S6
S7
SN
SC
SP
24V
E(G)
Shield terminal
2
MA
MB
MC
Fault contact output
250 VAC, 1 A max.
30 VDC, 1 A max.
M1
M2
M3
M4
Contact output 1
[Default: During run]
Contact output 2
[Default: Zero speed]
Multi-function digital output
250 VAC, 1 A max.
30 VDC, 1 A max.
+V
Analog input power supply
+15 V, 20 mA
A1
Analog input 1: Master frequency reference
0 to 10 V (20 k )
A2
AC
Multi-function analog input 1:
[Default: Frequency Bias
4 to 20 mA (250 )]
-V
0V
Analog input power supply
-15 V, 20 mA
Shield terminal
E(G)
3
FM
AM
AC
Adjustment,
20 k
Ω
+
FM
-
Multi-function analog output 1
(0 to 10 V, 2 mA)
[Default: Output frequency, 0 to 10 V]
Adjustment,
20 k
Ω
+
AM
-
Multi-function analog output 2
(0 to 10 V, 2 mA)
[Default: Output power, 0 to 10 V]
Input Option Cards
MEMOBUS communication
RS-485/422
P
P
R+
R-
S+
S-
IG
Terminating resistance
Shielded wires
P
Twisted-pair shielded wires
Fig 2.2 Connection Diagram of IP54 Inverters (Model CIMR-E7Z47P52 Shown Above)
2-3
2-4
Circuit Descriptions
Refer to the numbers indicated in
.
1
These circuits are hazardous and are separated from accessible surfaces by protective separation.
2
These circuits are separated from all other circuits by protective separation consisting of double and reinforced insulation. These circuits may be interconnected with SELV (or equivalent) or non-
SELV
*
circuits, but not both.
3
Inverter supplied by four-wire-system source (neutral grounded)
These circuits are SELV
*
circuits and are separated from all other circuits by protective separation consisting of double and reinforced insulation. These circuits may only be interconnected with other SELV
*
(or equivalent) circuits.
Inverter supplied by three-wire-system source (ungrounded or corner grounded)
These circuits are not separated from hazardous circuits by protective separation, but only with basic insulation. These circuits must not be interconnected with any circuits which are accessible, unless they are isolated from accessible circuits by supplemental insulation.
* SELV (Safety Extra Low Voltage) circuits have no direct connection to the primary power and are supplied by a transformer or equivalent isolating device. The circuits are designed and protected, so that, under normal and fault condition, its voltage does not exceed a safe value. (See IEC 61010)
1. Control circuit terminals are arranged as shown below.
IMPORTANT
2. The output current capability of the +V terminal is 20 mA.
3. Main circuit terminals are indicated with double circles and control circuit terminals are indicated with single circles.
4. The wiring of the digital inputs S1 to S7 is shown for the connection of relay contacts or NPN transistors (0V common and sinking mode). This is the default setting.
For the connection of PNP transistors or for using a 24V external power supply, refer to
page 2-33, Sinking/Sourcing Mode
.
5. The master speed frequency reference can be input either at terminal A1 or at terminal A2 by changing the setting of parameter H3-13. The default setting is terminal A2.
6. DC reactors to improve the input power factor are built into 200 V Class Inverters from 22 up to 110 kW and 400
V Class Inverters from 22 up to 300 kW. A DC reactor is an option only for Inverters of 18.5 kW or less. Remove the short circuit bar when connecting a DC reactor.
Terminal Block Configuration
Terminal Block Configuration
The terminal arrangements are shown in
.
E(G)
SN SC
S1 S2
SP A1
S3 S4
A2
S5
+V AC
S6 S7
-V
F
M
M
P AC
AC
A
M
RP
IG
R+
S+
R-
S-
M5 M6
M3
MA
M4
MB
M1
M
C
M2
E(G
)
Control Circuit Terminals
Main Circuit Terminals
NOT USED
Charge Indicator
Ground Terminal
Fig 2.3 Terminal Arrangement (200V / 400V Class Inverter of 0.4 kW)
E(G)
SN SC
S1
SP
S2
A1
S3
A2
S4
+V AC
S5 S6 S7
-V MP
FM
AC
AC
RP
AM IG
R+
S+
R-
S-
M5
M3
M6
M4
MA MB
M1
MC
M2 E(G)
Control Circuit Terminals
Carge Indicator
Main Circuit Terminals
Ground Terminals
Fig 2.4 Terminal Arrangement (200V / 400V Class Inverter of 22 kW or more)
2-5
2-6
Control Terminals
Output Terminals
NOT USED
R/L1 S/L2 T/L3
+1 +2 U/T1
MOTOR
V/T2 W/T3
CAUTION Terminal tightening torque;
Refer to manual for connections.
Use 75°C Cu wires or equivalent.
M5:2.5N.m
M6:4.0-5.0N.m
NPJU30012-1-1
Input Terminals
Ground Terminals
Fig 2.5 Terminal Arrangement (IP54 Inverter of 18.5kW)
Control Terminals
Shielding Clamp for Control Cables
Input Terminals
R/L1 S/L2 S/L3
Output Terminals
Ground Terminals
Fig 2.6 Terminal Arrangement (IP54 Inverter of 37kW)
Shielding Clamp for Motor Cables
Wiring Main Circuit Terminals
Wiring Main Circuit Terminals
Applicable Wire Sizes and Crimp Terminals
Select the appropriate wires and crimp terminals from the following tables.
Table 2.1 200 V Class Wire Sizes
Inverter
Model
CIMR-
Terminal Symbol
Terminal
Screws
Tightening
Torque
(N•m)
Possible
Wire Sizes mm
2
(AWG)
Recommended
Wire Size mm
2
(AWG)
E7Z20P4
U/T1, V/T2, W/T3
M4 1.2 to 1.5
1.5 to 4
(14 to 10)
2.5
(14)
Wire Type
E7Z20P7
U/T1, V/T2, W/T3
E7Z21P5
U/T1, V/T2, W/T3
M4 1.2 to 1.5
1.5 to 4
(14 to 10)
M4 1.2 to 1.5
1.5 to 4
(14 to 10)
2.5
(14)
2.5
(14)
E7Z22P2
E7Z23P7
E7Z25P5
U/T1, V/T2, W/T3
U/T1, V/T2, W/T3
U/T1, V/T2, W/T3
M4 1.2 to 1.5
1.5 to 4
(14 to 10)
M4 1.2 to 1.5
4
(12 to 10)
M4 1.2 to 1.5
6
(10)
E7Z27P5
U/T1, V/T2, W/T3
E7Z2011
U/T1, V/T2, W/T3
E7Z2015
R/L1, S/L2, T/L3, , 1, 2, U/T1, V/
T2, W/T3
B1, B2
E7Z2018
R/L1, S/L2, T/L3, , 1, 2, U/T1, V/
T2, W/T3
B1, B2
E7Z2022
E7Z2030
R/L1, S/L2, T/L3, , 1, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31
3
R/L1, S/L2, T/L3, , 1 U/T1,
V/T2, W/T3, R1/L11, S1/L21, T1/L31
3
M5 2.5
10
(8 to 6)
M5 2.5
4.0 to 5.0
2.5
4.0 to 5.0
9.0 to 10.0
2.5
4.0 to 5.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
M6
M8
M8
M6
M8
M8
M5
M6
M8
M6
M5
M6
16
(6 to 4)
25
(4 to 2)
10
(8 to 6)
25
(4)
25 to 35
(3 to 2)
10
(8 to 6)
25
(4)
25 to 35
(3 to 1)
10 to 16
(8 to 4)
25 to 35
(4 to 2)
50
(1 to 1/0)
10 to 16
(8 to 4)
25 to 35
(4 to 2)
10
(8)
16
(6)
-
25
(4)
50
(1)
-
25
(4)
-
25
(4)
25
(3)
25
(4)
-
25
(4)
25
(3)
2
(14)
4
(12)
6
(10)
Power cables, e.g., 600 V vinyl power cables
2-7
2-8
Table 2.1 200 V Class Wire Sizes
Inverter
Model
CIMR-
E7Z2037
E7Z2045
E7Z2055
E7Z2075
E7Z2090
E7Z2110
R/L1, S/L2, T/L3,
V/T2, W/T3, R1/L11, S1/L21, T1/L31
3 r/l1,
R/L1, S/L2, T/L3,
V/T2, W/T3, R1/L11, S1/L21, T1/L31
3 r/l1,
R/L1, S/L2, T/L3,
3 r/l1,
1
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31
3 r/l1,
R/L1, S/L2, T/L3,
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31
R/L1, S/L2, T/L3,
,
,
,
,
,
1 U/T1,
1 U/T1,
1
1
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31
3 r/l1,
3
Δ/l2
Δ/l2
Δ/l2
Δ/l2
Δ/l2 r/l1,
Δ/l2
Terminal Symbol
R/L1, S/L2, T/L3, , 1
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31
Terminal
Screws
M10
M8
M10
M4
M10
M8
M10
M4
M12
M10
M8
M10
M4
M12
M10
M8
M10
M4
M12
M8
M12
M4
M12
M8
M12
M4
Tightening
Torque
(N•m)
17.6 to 22.5
8.8 to 10.8
17.6 to 22.5
1.3 to 1.4
17.6 to 22.5
8.8 to 10.8
17.6 to 22.5
1.3 to 1.4
31.4 to 39.2
17.6 to 22.5
8.8 to 10.8
17.6 to 22.5
1.3 to 1.4
31.4 to 39.2
17.6 to 22.5
8.8 to 10.8
17.6 to 22.5
1.3 to 1.4
31.4 to 39.2
8.8 to 10.8
31.4 to 39.2
1.3 to 1.4
31.4 to 39.2
8.8 to 10.8
31.4 to 39.2
1.3 to 1.4
The wire thickness is set for copper wires at 75
°C.The wire thickness is set for copper wires at 75°
Possible
Wire Sizes mm
2
(AWG)
Recommended
Wire Size mm
2
(AWG)
70
(2/0)
70 to 95
(2/0 to 4/0)
6 to 16
(10 to 4)
35 to 70
(2 to 2/0)
0.5 to 4
(20 to 10)
95
(3/0 to 4/0)
95 to 122
(3/0 to 250)
95
(3/0 to 4/0)
6 to 70
(10 to 2/0)
95 to 185
(3/0 to 400)
0.5 to 4
(20 to 10)
150 to 185
(250 to 400)
95 to 150
(4/0 to 300)
6 to 70
(10 to 2/0)
70 to 150
(2/0 to 300)
0.5 to 4
(20 to 10)
6 to 16
(10 to 4)
50 to 70
(1 to 2/0)
0.5 to 4
(20 to 10)
50 to 95
(1/0 to 4/0)
90
(4/0)
6 to 70
(10 to 2/0)
35 to 95
(3 to 4/0)
0.5 to 4
(20 to 10)
–
35
(2)
1.5
(16)
95
(3/0)
240 to 300
(350 to 600)
150 to 300
(300 to 600)
6 to 70
(10 to 2/0)
150
(300)
0.5 to 4
(20 to 10)
Wire Type
–
50
(1)
1.5
(16)
50
× 2P
(1/0
× 2P)
90
(4/0)
–
50
(1/0)
1.5
(16)
95
× 2P
(3/0
× 2P)
95
× 2P
(3/0
× 2P)
–
95
(3/0)
1.5
(16)
150
× 2P
(250
× 2P)
95
× 2P
(4/0
× 2P)
–
70
× 2P
(2/0
× 2P)
1.5
(16)
240
× 2P, or
50
× 4P
(350
× 2P, or
1/0
× 2P)
150
× 2P, or
50
× 4P
(300
× 2P, or
1/0
× 4P)
–
150
× 2P
(300
× 2P)
1.5
(16)
Power cables, e.g., 600 V vinyl power cables
Wiring Main Circuit Terminals
Inverter
Model
CIMR-
E7Z40P4
Table 2.2 400 V Class Wire Sizes, NEMA 1/ IP20 and IP00 Inverters
Terminal Symbol
Terminal
Screws
Tightening
Torque
(N•m)
Possible
Wire Sizes mm
2
(AWG)
Recommended
Wire Size mm
2
(AWG)
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3
M4 1.2 to 1.5
1.5 to 4
(14 to 10)
2.5
(14)
Wire Type
E7Z40P7
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3
M4 1.2 to 1.5
1.5 to 4
(14 to 10)
2.5
(14)
E7Z41P5
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3
M4 1.2 to 1.5
1.5 to 4
(14 to 10)
2.5
(14)
E7Z42P2
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3 M4 1.2 to 1.5
1.5 to 4
(14 to 10)
E7Z43P7
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3
E7Z44P0
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3
E7Z45P5
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3
E7Z47P5
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3
E7Z4011
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3
E7Z4015
R/L1, S/L2, T/L3, , 1, 2, B1, B2,
U/T1, V/T2, W/T3
E7Z4018
R/L1, S/L2, T/L3, , 1, 2, U/T1, V/
T2, W/T3
B1, B2
E7Z4022
R/L1, S/L2, T/L3, , 1, 3, U/T1, V/
T2, W/T3, R1/L11, S1/L21, T1/L31
E7Z4030
R/L1, S/L2, T/L3, , 1, 3, U/T1, V/
T2, W/T3, R1/L11, S1/L21, T1/L31
M4
M4
M4
M4
M5
1.2 to 1.5
1.2 to 1.5
1.2 to 1.5
1.2 to 1.5
2.5
M6
M8
M6
M8
M5
M5
(M6)
M6
M5
M6
2.5
2.5
(4.0 to 5.0)
4.0 to 5.0
2.5
4.0 to 5.0
4.0 to 5.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
2.5 to 4
(14 to 10)
2.5 to 4
(14 to 10)
4
(12 to 10)
2.5 to 4
(14 to 10)
6
(10)
4
(12 to 10)
6 to 10
(10 to 6)
10
(8 to 6)
6 to 10
(10 to 6)
10 to 35
(8 to 2)
10
(8)
10 to 16
(8 to 4)
16
(6 to 4)
16 to 25
(6 to 2)
25
(4)
25 to 35
(4 to 2)
2.5
(14)
10
(8)
10
(8)
10
(8)
10
(8)
6
(10)
4
(12)
10
(8)
6
(10)
16
(6)
16
(6)
25
(4)
25
(4)
4
(12)
2.5
(14)
4
(12)
2.5
(14)
4
(12)
2.5
(14)
6
(10)
Power cables, e.g., 600 V vinyl power cables
2-9
2-10
Inverter
Model
CIMR-
E7Z4037
E7Z4045
E7Z4055
E7Z4075
E7Z4090
E7Z4110
E7Z4132
R/L1, S/L2, T/L3, , 1, U/T1, V/T2, W/
T3, R1/L11, S1/L21, T1/L31
3
R/L1, S/L2, T/L3, , 1, U/T1, V/T2, W/
T3, R1/L11, S1/L21, T1/L31
3
R/L1, S/L2, T/L3, , 1, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31
3
3
R/L1, S/L2, T/L3, , 1
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31
3
3
Table 2.2 400 V Class Wire Sizes, NEMA 1/ IP20 and IP00 Inverters
Terminal Symbol
R/L1, S/L2, T/L3, , 1
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31
3 r/l1,
Δ200/ l2
200,
Δ400/ l2
400
R/L1, S/L2, T/L3, , 1
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31 r/l1,
Δ200/ l2
200,
Δ400/ l2
400 r/l1,
Δ200/ l2
200,
Δ400/ l2
400
R/L1, S/L2, T/L3, , 1
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31 r/l1,
Δ200/ l2
200,
Δ400/ l2
400
Terminal
Screws
M8
M6
M8
M8
M6
M8
M8
M6
M8
M10
M10
M8
M10
M4
M10
M10
M8
M10
M4
M10
M8
M12
M4
M10
M8
M12
M4
Tightening
Torque
(N•m)
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
31.4 to 39.2
17.6 to 22.5
8.8 to 10.8
31.4 to 39.2
1.3 to 1.4
31.4 to 39.2
17.6 to 22.5
8.8 to 10.8
31.4 to 39.2
1.3 to 1.4
31.4 to 39.2
8.8 to 10.8
31.4 to 39.2
1.3 to 1.4
31.4 to 39.2
8.8 to 10.8
31.4 to 39.2
1.3 to 1.4
Possible
Wire Sizes mm
2
(AWG)
Recommended
Wire Size mm
2
(AWG)
35
(2)
25 to 50
(4 to 1/0)
10 to 16
(8 to 4)
25 to 35
(4 to 2)
35 to 50
(2 to 1/0)
10 to 16
(8 to 4)
25 to 35
(4 to 2)
50
(1 to 1/0)
10 to 16
(8 to 4)
25 to 35
(4 to 2)
70 to 95
(2/0 to 4/0)
50 to 100
(1/0 to 4/0)
6 to 16
(10 to 4)
35 to 70
(2 to 2/0)
0.5 to 4
(20 to 10)
95
(3/0 to 4/0)
95
(3/0 to 4/0)
10 to 16
(8 to 4)
50 to 95
(1 to 4/0)
0.5 to 4
(20 to 10)
50 to 95
(1/0 to 4/0)
10 to 70
(8 to 2/0)
70 to 150
(2/0 to 300)
0.5 to 4
(20 to 10)
95
(3/0 to 4/0)
75 to 95
(2/0 to 4/0)
10 to 70
(8 to 2/0)
95 to 150
(4/0 to 300)
0.5 to 4
(20 to 10)
50
25
(4)
35
(2)
-
25
(4)
50
(1)
25
(4)
70
(2/0)
50
(1/0)
-
35
(2)
1.5
(16)
95
(4/0)
95
(4/0)
50
(1)
1.5
(16)
× 2P
(1/0
-
-
-
× 2P)
-
70
(2/0)
1.5
(16)
95
× 2P
(3/0
× 2P)
75
× 2P
(2/0
× 2P)
-
95
(4/0)
1.5
(16)
Wire Type
Power cables, e.g., 600 V vinyl power cables
Wiring Main Circuit Terminals
Inverter
Model
CIMR-
E7Z4160
E7Z4185
E7Z4220
E7Z4300
R/L1, S/L2, T/L3, , 1
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31
3 r/l1,
Δ200/ l2
200,
Δ400/ l2
400
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L33
3 r/l1,
Δ200/ l2
200,
Δ400/ l2
400
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L33
3 r/l1,
Δ200/ l2
200,
Δ400/ l2
400
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3
3
Table 2.2 400 V Class Wire Sizes, NEMA 1/ IP20 and IP00 Inverters
Terminal Symbol r/l1,
Δ200/ l2
200,
Δ400/ l2
400
Terminal
Screws
M12
M8
M12
M4
M16
M4
M16
M4
M16
M4
Tightening
Torque
(N•m)
31.4 to 39.2
8.8 to 10.8
31.4 to 39.2
1.3 to 1.4
78.4 to 98
1.3 to 1.4
78.4 to 98
1.3 to 1.4
78.4 to 98
1.3 to 1.4
Possible
Wire Sizes mm
2
(AWG)
95 to 185
(4/0 to 400)
95 to 185
(3/0 to 400)
10 to 70
(8 to 2/0)
50 to 150
(1/0 to 300)
0.5 to 4
(20 to 10)
Recommended
Wire Size mm
2
(AWG)
95
× 2P
(4/0
× 2P)
95
× 2P
(3/0
× 2P)
95 to 300
(4/0 to 600)
0.5 to 4
(20 to 10)
95 to 300
(4/0 to 600)
0.5 to 4
(20 to 10)
95 to 300
(4/0 to 600)
0.5 to 4
(20 to 10)
-
50
× 2P
(1/0
× 2P)
1.5
(16)
150
× 2P
(300
× 2P)
120
× 2P
(250
× 2P)
300
× 2P
(600
× 2P)
–
95
× 2P
(3/0
× 2P
1.5
(16)
240
× 2P
(500
× 2P)
240
× 2P
(400
× 2P)
120
× 4P
(250
× 4P)
–
120
× 2P
(250
× 2P)
1.5
(16)
120
× 4P
(250
× 4P)
120
× 4P
(4/0
× 4P)
240
× 4P
(400
× 4P)
–
120
× 2P
(250
× 2P
1.5
(16)
Wire Type
Power cables, e.g., 600 V vinyl power cables
2-11
2-12
Inverter Model
CIMR-
E7Z47P52
E7Z40112
E7Z40152
E7Z40182
E7Z40222
E7Z40302
E7Z40372
E7Z40452
E7Z40552
Table 2.3 400 V Class Wire Sizes, IP54 Inverters
Terminal Symbol
INPUT (R/L1, S/L2, T/L3, )
OUTPUT (U/T1, V/T2, W/T3, )
INPUT (R/L1, S/L2, T/L3, )
OUTPUT (U/T1, V/T2, W/T3, )
INPUT (R/L1, S/L2, T/L3, )
U/T1, V/T2, W/T3
OUTPUT
( )
INPUT (R/L1, S/L2, T/L3, )
OUTPUT (U/T1, V/T2, W/T3, )
INPUT (R/L1, S/L2, T/L3, )
(U/T1, V/T2, W/T3)
OUTPUT
( )
INPUT (R/L1, S/L2, T/L3, )
(U/T1, V/T2, W/T3)
OUTPUT
( )
INPUT (R/L1, S/L2, T/L3, )
(U/T1, V/T2, W/T3)
OUTPUT
( )
INPUT (R/L1, S/L2, T/L3, )
(U/T1, V/T2, W/T3)
OUTPUT
( )
INPUT (R/L1, S/L2, T/L3, )
(U/T1, V/T2, W/T3)
OUTPUT
( )
M5
M5
M5
M5
M6
M5
M4
M4
M5
M5
M5
M6
M6
M6
M6
M8
M8
M8
M8
M8
M8
M8
M8
M8
M6
M8
M8
M8
M8
M6
M6
M6
M8
Terminal
Screws
4.0 to 5.0
4.0 to 5.0
4.0 to 5.0
9.0 to 10.0
4.0 to 5.0
9.0 to 10.0
9.0 to 10.0
9.0 to 10.0
9.0 to 10.0
9.0 to 10.0
9.0 to 10.0
9.0 to 10.0
9.0 to 10.0
9.0 to 10.0
9.0 to 10.0
9.0 to 10.0
9.0 to 10.0
Tightening
Torque
(N•m)
2.5
1.8
Recommended
Wire Size mm
2
(AWG)
6
Cable Gland size
Possible
Clamping Cable
Diam.
(mm)
Minimum
Diam Over
Braid Shield
(mm)
M32 (Plastic) 11 to 21 -
6 M32 (Metal) 11 to 21 9.0
1.8
2.5
6
10
-
M32 (Plastic) 11 to 21
-
-
2.5
2.5
2.5
2.5
4.0 to 5.0
10
10
10
10
M32 (Metal)
-
M32 (Metal)
11 to 21
-
M32 (Plastic) 11 to 21
11 to 21
9.0
-
-
9.0
2.5
2.5
4.0 to 5.0
4.0 to 5.0
4.0 to 5.0
4.0 to 5.0
9.0 to 10.0
10
10
10
10
16
16
-
M32 (Plastic) 11 to 21
M32 (Metal) 11 to 21
-
M40 (Plastic) 19 to 28
M40 (Metal) 19 to 28
9.0
-
-
-
-
15.0
16
25
25
25
35
35
35
35
35
35
50
50
50
-
M40 (Plastic) 19 to 28
M40 (Metal)
-
19 to 28
-
M50 (Plastic) 19 to 28
M50 (Metal)
-
M50 (Plastic) 19 to 28
M50 (Metal)
-
M50 (Metal)
-
19 to 28
-
19 to 28
-
M50 (Plastic) 19 to 28
19 to 28
-
-
-
15.0
-
-
-
-
-
-
-
-
-
-
Table 2.4 Recommended Wire Types for IP54 Inverters
INPUT
OUTPUT
(-), (+1)
4-core Power Cable
*1
4-core shielded Power Cable
e.g. 600V Vinyl Power Cable
*1. 4-core power cables or 4-core shielded power cables are available e.g. Lappkabel (Ölflex) or Pirelli
Wiring Main Circuit Terminals
Table 2.5 Tightening Torques for Cable Gland
Cable Gland Size
M16
M20
M25
M32
M40
M50
Tightening Torque (Nm)
Plastic Metal
3.0
6.0
10.0
12.0
8.0
10.0
13.0
15.0
12.0
18.0
18.0
20.0
IMPORTANT
Determine the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage.
Line voltage drop is calculated as follows:
Line voltage drop (V) = 3 x wire resistance (W/km) x wire length (m) x current (A) x 10
-3
2-13
2-14
Recommended Crimp Terminals
Table 2.6 Recommended Crimp Terminals
Wire Cross Section
(mm²)
0.5-1.0
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
240
Terminal Screws
300
*1. not applicable for E7Z2011
M4
M5
M6
M8
M4
M4
M4
M4
M5
M6
M8
M5
M12
M10
M12
M16
M10
M12
M8
M10
M6
M8
M10
M8
M6
M8
M6
M8
M12
M16
M12
M16
M12
M16
M16
107 R/12
108 R/10
108 R/12
108 R/16
109 R/12
109 R/16
110 R/12
110 R/16
105 R/6
105 R/8
105 R/10
106 R/8
106 R/10
106 R/12
107 R/8
107 R/10
112 R/12
112 R/16
113 R/16
101 R/8
102 R/5
102 R/6
102 R/8
103 R/5
*1
103 R/6
103 R/8
104 R/6
104 R/8 a
620/4
630/4
630/4
650/4
650/4
101 R/5
101 R/6
Recommended Crimp Terminals
Klauke y b
1620/4
1620/4
1630/4
1650/4
1650/4
1650/5
1650/6
1650/8
1652/5
1652/6
1652/8
1653/5
1656/10
1656/12
1657/8
1657/10
1657/12
1658/10
1658/12
1658/16
1653/6
1653/8
1654/6
1654/8
1655/6
1655/8
1655/10
1656/8
1659/12
1659/16
1660/12
1660/16
1662/12
1662/16
-
JST
GS4-1
GS4-1
GS4-2.5
GS4-6
GS4-6
GS5-6
GS6-6
GS8-6
GS5-10
GS6-10
GS8-10
GS5-16
GS10-50
GS12-50
GS8-70
GS10-70
GS12-70
GS10-95
GS12-95
GS16-95
GS6-16
GS8-16
GS6-25
GS8-25
GS6-35
GS8-35
GS10-35
GS8-50
GS12-120
GS16-120
GS12-150
GS16-150
GS12-240
GS16-240
-
Wiring Main Circuit Terminals
Main Circuit Terminal Functions
Main circuit terminal functions are summarized according to terminal symbols in
nals correctly for the desired purposes.
Table 2.7 Main Circuit Terminal Functions
Purpose
Main circuit power input
Inverter outputs
DC bus terminals
DC reactor connection
Terminal Symbol
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3
1,
1, 2
Model: CIMR-E7Z
200 V Class
20P4 to 2110
2022 to 2110
20P4 to 2110
20P4 to 2110
20P4 to 2018
400 V Class
40P4 to 4300
4022 to 4300
40P4 to 4300
40P4 to 4300
40P4 to 4018
Braking Unit connection
3,
2022 to 2110 4022 to 4300
Ground 20P4 to 2110 40P4 to 4300
2-15
2-16
Main Circuit Configurations
The main circuit configurations of the Inverter are shown in
Table 2.8 Inverter Main Circuit Configurations (IP00, NEMA 1/IP20 Inverters)
200 V Class 400 V Class
CIMR-E7Z20P4 to 2018
B1 B2
CIMR-E7Z40P4 to 4018
B1 B2
+
1
+
R
2
S
T
-
U
V
W
+
1
+
2
R
S
T
-
Power
Supply
Control
Circuit
Power
Supply
Control
Circuit
CIMR-E7Z2022 to 2030
+
3
CIMR-E7Z4022 to 4055
+
3
+
1
R
S
T
R1
S1
T1
-
U
V
W
+
1
R
S
T
R1
S1
T1
-
Power
Supply
Control
Circuit
Power
Supply
Control
Circuit
CIMR-E7Z4075 to 4300
+ 3
CIMR-E7Z2037 to 2110
+ 3
+ 1
R/L1
S/L2
T/L3
R1/L11
S1/L21
T1/L31
r/l
1 s 200/l
2
200
U/T1
V/T2
W/T3
+ 1
R/L1
S/L2
T/L3
R1/L11
S1/L21
T1/L31
r/l
1 s 200/l
2
200 s 400/l
2
400
Power
Supply
Control
Circuit
Note: Consult your Omron Yaskawa Motion Control representative before using 12-phase rectification.
400/200
Power
Supply
Control
Circuit
U
V
W
U
V
W
U/T1
V/T2
W/T3
Wiring Main Circuit Terminals
Table 2.9 Main Circuit Configurations (IP54 Inverters)
400 V class
CIMR-E7Z47P52 to 40182
1
2
R/L1
S/L2
T/L3
EMC filter
U/T1
V/T2
W/T3
Power supply
Control circuits
1
R/L1
S/L2
T/L3
EMC
Filter
CIMR-E7Z40222 to 40552
3
Power
Supply
Control
Circuits
U/T1
V/T2
W/T3
2-17
2-18
Standard Connection Diagrams
Standard Inverter (NEMA 1 / IP20) connection diagrams are shown in
. These are the same for both
200 V Class and 400 V Class Inverters.
shows the standard Inverter connection diagrams for the IP54
Inverters. The connections depend on the Inverter capacity.
CIMR-E7Z20P4 to 2018 and 40P4 to 4018
CIMR-E7Z2022, 2030 and 4022 to 4055
Braking
Resistor (optional)
CDBR Braking
Unit (optional)
Braking
Resistor (optional)
CDBR Braking
Unit (optional)
3 Phase 200VAC or
400VAC
-
R/L1
S/L2
T/L3
+ 1
U/T1
V/T2
W/T3
DC reactor
(optional)
+ 2
M
3 Phase 200VAC or
400VAC
+ 1
R/L1
S/L2
T/L3
R1/L11
S1/L21
T1/L31
+ 3 -
U/T1
V/T2
W/T3
M
Be sure to remove the short-circuit bar before connecting the DC reactor.
The DC reactor is built in.
CIMR-E7Z2037 to 2110
3 Phase 200VAC or
400VAC
+ 1
R/L1
S/L2
T/L3
+ 3
R1/L11
S1/L21
T1/L31 r / l1
/ l2
-
U/T1
V/T2
W/T3
Braking
Resistor (optional)
CDBR Braking
Unit (optional)
M
CIMR-E7Z4075 to 4300
3 Phase 200VAC or
400VAC
+ 1
R/L1
S/L2
T/L3
+ 3
R1/L11
S1/L21
T1/L31 r / l1
200 / l
2
200
400 / l
2
400
-
U/T1
V/T2
W/T3
Braking
Resistor (optional)
CDBR Braking
Unit (optional)
M
Control power is supplied internally from the DC bus at all inverter models.
Fig 2.7 Main Circuit Terminal Connections for NEMA 1 / IP20 Inverters
Wiring Main Circuit Terminals
CIMR-E7Z47P72 to 4055
Braking
Resistor (optional)
CDBR Braking
Unit (optional)
+ 1
DC reactor
(optional)
+ 2
-
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
3 Phase 400VAC
M
Be sure to remove the short-circuit bar before connecting the DC reactor.
Fig 2.8 Main Circuit Terminal Connections for IP54 Inverters
2-19
2-20
Wiring the Main Circuits
This section describes wiring connections for the main circuit inputs and outputs.
Wiring Main Circuit Inputs
Observe the following precautions for the main circuit power supply input.
4110
4132
4160
4185
4220
4300
4022
4030
4037
4045
4055
4075
4090
40P4
40P7
41P5
42P2
43P7
44P0
45P5
47P5
4011
4015
4018
Installing Fuses
To protect the inverter, it is recommended to use semiconductor fuses like they are shown in the table below.
Table 2.10 Input Fuses
20P4
20P7
21P5
22P2
23P7
25P5
27P5
2011
2015
2018
2022
2030
2037
2045
2055
2075
2090
2110
Inverter Type
Rated Inverter
Output
Current (A)
3.2
4.1
7.0
9.6
15
23
31
45
58
71
85
115
145
180
215
283
346
415
Voltage (V)
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
Fuse Selection
Current (A)
40
60
80
100
130
150
10
10
15
20
30
180
240
300
350
450
550
600
I
2 t (A
2 s)
12~25
12~25
23~55
34~98
82~220
220~610
290~1300
450~5000
1200~7200
1800~7200
870~16200
1500~23000
2100~19000
2700~55000
4000~55000
7100~64000
11000~64000
13000~83000
Selection Example (Ferraz)
Model Rating
I
2 t (A
2 s)
A60Q12-2
A60Q12-2
A60Q15-2
A60Q20-2
A60Q30-2
A50P50-4
A50P80-4
A50P80-4
A50P125-4
A50P150-4
A50P150-4
A50P200-4
A50P250-4
A50P300-4
A50P350-4
A50P450-4
A50P600-4
A50P600-4
600V / 12A
600V / 12A
600V / 15A
600V / 20A
600V / 30A
500V / 50A
500V / 80A
500V / 80A
500V / 125A
500V / 150A
500V / 150A
500V / 200A
500V/ 250A
500V / 300A
500V / 350A
500V / 450A
500V / 600A
500V / 600A
250
640
640
1600
2200
2200
17
17
26
41
132
4000
6200
9000
12000
20000
36000
36000
216
260
304
370
506
675
45
60
75
91
112
150
180
7.6
8.7
12.5
17
24
31
39
1.8
2.1
3.7
5.3
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
350
400
450
600
700
900
80
100
125
150
150
250
300
30
50
60
70
15
20
25
5
5
10
10
6~55
6~55
10~55
18~55
34~72
50~570
100~570
100~640
150~1300
400~1800
700~4100
A60Q10-2
A60Q10-2
A60Q12-2
A60Q15-2
A60Q20-2
A60Q30-2
A60Q30-2
A60Q30-2
A70P50-4
A70P70-4
A70P80-4
240~5800
500~5800
750~5800
920~13000
1500~13000
3000~55000
3800~55000
A70P80-4
A70P100-4
A70P125-4
A70P150-4
A70P200-4
A70P250-4
A70P300-4
5400~23000 A70P350-4
7900~64000 A70P400-4
14000~250000 A70P450-4
20000~250000 A70P600-4
34000~400000 A70P700-4
52000~920000 A70P900-4
600V / 10A
600V / 10A
600V / 12A
600V / 15A
600V / 20A
600V / 30A
600V / 30A
600V / 30A
700V / 50A
700V / 70A
700V / 80A
700V / 80A
700V / 100A
700V / 125A
700V / 150A
700V / 200A
700V / 250A
700V / 300A
700V / 350A
700V / 400A
700V / 450A
700V / 600A
700V / 700A
700V / 900A
770
1200
1900
2700
4800
7500
11000
15000
19000
24000
43000
59000
97000
41
132
132
132
300
590
770
10
10
17
26
Wiring Main Circuit Terminals
Installing a Moulded-case Circuit Breaker
When connecting the power input terminals (R/L2, S/L2, and T/L3) to the power supply using a moulded-case circuit breaker (MCCB) observe that the circuit breaker is suitable for the Inverter.
•
Choose an MCCB with a capacity of 1.5 to 2 times of the inverter's rated current.
•
For the MCCB's time characteristics, be sure to consider the inverter's overload protection (one minute at
150% of the rated output current).
Installing an Earth Leakage Breaker
Inverter outputs use high-speed switching, so high-frequency leakage current is generated. If an earth leakage breaker should be used, select a breaker that detects only the leakage current which is in the frequency range that is hazardous to humans but not high-frequency leakage currents.
•
For a special-purpose earth leakage breaker for Inverters, choose a ground fault interrupter with a sensitivity amperage of at least 30 mA per Inverter.
•
When using a general earth leakage breaker, choose one with a sensitivity amperage of 200 mA or more per Inverter and with an operating time of 0.1 s or more.
Installing a Magnetic Contactor
If the power supply for the main circuit is to be shut off by a control circuit, a magnetic contactor can be used.
The following things should be considered:
•
The Inverter can be started and stopped by opening and closing the magnetic contactor on the primary side.
Frequently opening and closing the magnetic contactor, however, may cause the Inverter to break down.
Do not exceed one power up per hour.
•
When the Inverter is operated with the Digital Operator, automatic operation cannot be performed after recovery from a power interruption.
Connecting Input Power Supply to the Terminal Block
Input power supply can be connected to any terminal R, S or T on the terminal block; the phase sequence of input power supply is irrelevant to the output phase sequence.
Installing an Input AC Reactor
If the Inverter is connected to a large-capacity power transformer (600 kW or more) or a phase advancing capacitor is switched nearby, an excessive peak current may flow through the input power circuit, causing the inverter unit to break down.
To prevent this, install an optional AC Reactor on the input side of the Inverter or a DC reactor to the DC reactor connection terminals.
This also improves the power factor on the power supply side.
Installing a Surge Absorber
Always use a surge absorber or diode for inductive loads near the Inverter. These inductive loads include magnetic contactors, electromagnetic relays, solenoid valves, solenoids, and magnetic brakes.
2-21
2-22
Wiring the Output Side of Main Circuit
Observe the following precautions when wiring the main output circuits.
Connecting the Inverter and Motor
Connect output terminals U/T1, V/T2, and W/T3 respective to the motor lead wires U, V, and W.
Check that the motor rotates forward with the forward run command. Switch over any two of the output terminals to each other and reconnect if the motor rotates in reverse with the forward run command.
Never Connect a Power Supply to Output Terminals
Never connect a power supply to output terminals U/T1, V/T2, and W/T3. If voltage is applied to the output terminals, the internal circuits of the Inverter will be damaged.
Never Short or Ground Output Terminals
If the output terminals are touched with bare hands or the output wires come into contact with the Inverter casing, an electric shock or grounding may occur. This is extremely hazardous. Do not short the output wires.
Do Not Use a Phase Advancing Capacitor
Never connect a phase advancing capacitor to an output circuit. The high-frequency components of the
Inverter output may overheat and be damaged and may cause other parts to burn.
Using a Magnetic Contactor
Check the control sequence to make sure, that the magnetic contactor (MC) between the Inverter and motor is not turned ON or OFF during inverter operation. If the MC is turned ON while the Inverter is operating, a large inrush current will be created and the inverter’s overcurrent protection may operate. If the MC is turned
OFF while the Inverter is operating a large induced voltage may occur and damage the inverter output parts.
Installing a Thermal Overload Relay Contact for Motor Protection
This Inverter has an electronic thermal protection function to protect the motor from overheating. If, however, more than one motor is operated with one Inverter or a multi-polar motor is used, always install a thermal relay (THR) between the Inverter and the motor and set L1-01 to 0 (no motor protection). The control circuit should be designed so that the contacts of the thermal overload relay turn OFF the magnetic contactor on the main circuit inputs.
Cable Length between Inverter and Motor
If the cable between the Inverter and the motor is long, the high-frequency leakage current will increase, causing the Inverter output current to increase as well. This may affect peripheral devices. To prevent this, adjust the carrier frequency (set in C6-02) as shown in
. (For details, refer to
Table 2.11 Cable Length between Inverter and Motor
Cable length
Carrier frequency
50 m max.
15 kHz max.
100 m max.
10 kHz max.
More than 100 m
5 kHz max.
Wiring Main Circuit Terminals
Ground Wiring
Observe the following precautions when wiring the ground line.
•
Always use the ground terminal of the 200 V Inverter with a ground resistance of less than 100
Ω and that of the 400 V Inverter with a ground resistance of less than 10
Ω.
•
Do not share the ground wire with other devices, such as welding machines or power tools.
•
Always use a ground wire that complies with technical standards on electrical equipment and minimize the length of the ground wire.
Leakage current flows through the Inverter. Therefore, if the distance between the ground electrode and the ground terminal is too long, potential on the ground terminal of the Inverter will become unstable.
•
When using more than one Inverter, be careful not to loop the ground wire.
OK
NO
Fig 2.9 Ground Wiring
Connecting a Braking Unit (CDBR) and a Braking Resistor Unit (LKEB)
Connect a Braking Unit and a Braking Resistor Unit to the Inverter as shown in the
.
The Braking Resistor Unit will not work if L3-04 is set to 1 (i.e., if stall prevention is enabled for deceleration). Hence the deceleration time may be longer than the set time (C1-02/04).
To prevent the braking unit/braking resistor unit from overheating, design the control circuit to turn OFF the
inverter output using the thermal overload relay of the Unit as shown in
CDBR
Braking Unit
Braking Resistor
+ 3
+
+ 3
Inverter
Thermal
Overload
Relay Contact
-
- 0
Thermal Overload
Relay Contact
Fig 2.10 Connecting the Braking Resistor Unit and Braking Unit
2-23
2-24
Connecting Braking Units in Parallel
When connecting two or more Braking Units in parallel, use the wiring and jumper settings like shown in
. There is a jumper for selecting whether each Braking Unit is to be a master or slave. Select “Master” for the first Braking Unit only, and select “Slave” for all other Braking Units (i.e., from the second Unit onwards).
Thermal overload relay contact Thermal overload relay contact Thermal overload relay contact
Braking
Resistor
Unit
Braking
Resistor
Unit
Braking
Resistor
Unit
Inverter
Braking Unit #2 Braking Unit #3
Braking Unit #1
Thermal overload relay contact Thermal overload relay contact
Fig 2.11 Connecting Braking Units in Parallel
Thermal overload relay contact
Wiring the Power Cables of IP54 Inverters
Special attention has to be paid for wiring the motor cables of the IP54 inverters. The smaller capacities feature an EMC cable gland which is used to earth the motor cable shield easily.
Installing the Metal (EMC) Cable Gland on IP54 Inverters 7.5 to 30kW
1. With the Standard Contacting:
Make a round cut into the outer sheath, with a length of appr. 14mm from the end of the sheath but do not remove the sheath.
Guide the cable through the gland. appr. 15 mm
Pull off the cut-off outer sheath, remove some part of the shield and pull the cable back until the shield has proper contact to the springs of the cable gland.
Wiring Main Circuit Terminals
Close the cable gland.
2. With thin wires and without an inner sheath
Make a round cut into the sheath, with a length of appr. 15 to 20mm and remove it.
Pull back the braided shield over the outer sheath, the inner shield should be kept for easier guiding through the gland.
Guide the cable through the gland until the shield has proper contact to the springs of the cable gland and close the cable gland. appr. 15 to 20 mm
Note:
To ensure conformity to EMC regulations the shielded cable has to be locked tightly by the metal cable gland.
Confirm the cable length and the terminal specifications before fitting the metal cable gland.
2-25
Special Considerations for IP54 Inverters of 22 and 30kW capacity
Install the shielded output cable as shown in the
.
Remove the braided shield on the output cable entirely from the entry hole to the terminal end to avoid short circuit to the input terminals or the filter.
Remove the braided shield entirely from the entry hole to the terminal end.
Input Cable
Output Cable
(Shielded Cable)
Fig 2.12 Motor Cable Installation for IP54 Inverters of 22 and 30kW
Installing the Motor Cable at IP54 Inverters of 37 to 55kW capacity
Install the shielded output cable as shown in the figure below. Remove the outer sheath and clamp the braided shield by the earth clamp.
2-26
Earth Plate
Remove the outer sheath and clamp the braided shield by the earth clamp
.
Earth Clamp Output Cable
Fig 2.13 Motor Cable Installation for IP54 Inverters of 37 to 55kW
Wiring Control Circuit Terminals
Wiring Control Circuit Terminals
Wire Sizes
For remote operation using analog signals, keep the control line length between the Analog Operator or operation signals and the Inverter to 50 m or less, and separate the lines from main power lines or other control circuits to reduce induction from peripheral devices.
When setting frequencies from an external frequency source (and not from a Digital Operator), use shielded twisted-pair wires and ground the shield for the largest area of contact between shield and ground.
Terminal numbers and wire sizes are shown in
.
Table 2.12 Terminal Numbers and Wire Sizes (Same for all models)
Terminals
Terminal
Screws
Tightening Torque
(N•m)
Possible
Wire
Sizes mm
2
(AWG)
Recommended
Wire Size mm
2
(AWG)
IP54 Inverters Only
Cable
Gland
Size
Possible
Clamping
Cable
Diam.
(mm)
FM, AC, AM, SC, SP,
SN, A1, A2, +V, -V,
S1, S2, S3, S4,
S5, S6, S7
MA, MB, MC, M1,
M2, M3, M4,
R+, R-, S+, S-, IG
Phoenix type
0.5 to 0.6
Single wire
*1
:
0.14 to 2.5
Stranded wire:
0.14 to 1.5
(26 to 14)
0.75
(18)
M25
*2
9 to 17
Wire Type
• Shielded, twistedpair wire
*3
• Shielded, polyethylene-covered, vinyl sheath cable
E (G) M3.5
0.8 to 1.0
0.5 to 2
(20 to 14)
1.25
(12)
-
*1. We recommend using cable-end sleeves on signal lines to simplify wiring and to improve reliability.
*2. Refer to
for tightening torques for the cable glands.
*3. Use shielded twisted-pair cables to input an external frequency reference.
2-27
Cable-End Sleeves for Signal Lines
Models and sizes of straight solderless terminals are shown in the following table.
Table 2.13 Straight Solderless Terminal Sizes
Wire Size mm
2
(AWG)
0.25 (24)
0.5 (20)
0.75 (18)
1.25 (16)
2 (14)
Model
AI 0.25 - 8YE
AI 0.5 - 8WH
AI 0.75 - 8GY
AI 1.5 - 8BK
AI 2.5 - 8BU d1
0.8
1.1
1.3
1.8
2.3
d2
2
2.5
2.8
3.4
4.2
L
12.5
14
14
14
14
Manufacturer
Phoenix Contact
2-28
Fig 2.14 Cable-End Sleeve Size
Wiring Method
Use the following procedure to connect wires to the terminal block.
1. Loosen the terminal screws with a thin-slot screwdriver.
2. Insert the wires from underneath the terminal block.
3. Tighten the terminal screws firmly
Screwdriver
Blade of screwdriver
Control circuit terminal block
Strip the end for
7 mm if no cableend sleeve is used.
Wires
Solderless terminal or wire without soldering
3.5 mm max.
Blade thickness: 0.6 mm max.
Fig 2.15 Connecting Wires to Terminal Block
Wiring Control Circuit Terminals
Earthing the Control Cable Shield in IP54 Inverters
For a appropriate shielding earth clamps have been mounted in the IP54 inverters.
show where the earth clamps can be found.
Control Terminal
Cable Mounting Base
Earth Clamp
Fig 2.16 Earth Clamp of IP54 Inverters with 7.5 to 18.5kW capacity
Control
Terminal
Earth Clamp
Cable Tie
(optional)
Earth Clamp
Cable
Mounting
Base
Control Cable
Fig 2.17 Earth clamp of IP54 Inverters with 22 to 55kW
Cable Gland
2-29
2-30
Use the following procedure to clamp and shield the control cables in the IP54 Inverters.
Loosen both mounting screws for the earth clamp
Insert the shielded cable for control between earth clamp and cable mounting base
Tighten the screws alternately until screws are fixed to the end.
Wiring Control Circuit Terminals
Control Circuit Terminal Functions
The functions of the control circuit terminals are shown in
.
Table 2.14 Control Circuit Terminals with Default Settings
Type No.
Signal Name
S1 Forward run/stop command
S2 Reverse run/stop command
S3
External fault input
*1
S4
S5
S6
S7
SC Digital input common
SN Digital Input Neutral
SP
MA
MB
MC
Multi-step speed reference 1
(Master/auxiliary switch)
Multi-step speed reference 2
+V 15 V power output
A1 Frequency reference
Fault output signal
Digital Input Power Supply
A2 Auxiliary Frequency Reference
-V -15 V power output
AC Analog reference common
E(G)
Shield wire, optional ground line connection point
M1
M2
M3
During run
(1NO contact)
M4
Zero speed
(1NO contact)
Function
Forward run when ON; stopped when OFF.
Reverse run when ON; stopped when OFF.
Fault when ON.
Reset when ON
Auxiliary frequency reference when ON.
Multi-step speed 2 when
ON.
Jog frequency when ON.
–
–
Functions are selected by setting H1-01 to
H1-05.
+24VDC power supply for digital inputs
15 V power supply for analog references
0 to +10 V/100%
Auxiliary analog frequency reference;
4 to 20 mA (250
Ω)
Function is selected by setting H3-09.
-15 V power supply for analog references
–
–
Closed during Run
CLOSED when output frequency at zero level
(b2-01) or below
24 VDC, 8 mA
Photocoupler isolation
–
–
24 VDC, 250 mA max.
*2
15 V (Max. curr.: 20mA)
0 to +10 V (20 k
Ω)
4 to 20 mA (250
Ω)
0 V to +10 V (20k
Ω)
0 to 20 mA (250
Ω)
–
–
Signal Level
Function selected by H2-01 and
H2-02
Relay contacts
Contact capacity:
1 A max. at 250 VAC
1 A max. at 30 VDC
*3
CLOSED across MA and MC during faults
OPEN across MB and MC during faults
FM
AC
AM
Output frequency
Analog common
Inverter output power
Analog output frequency signal;
0 to 10 V; 10V=FMAX
–
Analog output power signal;
0 to 10V; 10V=max. appl. motor capacity
Function selected by H4-01
Function selected by H4-04
0 to +10 V max. ±5%
2 mA max.
2-31
2-32
Type
Table 2.14 Control Circuit Terminals with Default Settings
No.
Signal Name
R+
MEMOBUS communications
Rinput
S+
MEMOBUS communications
Soutput
IG Signal common –
Function
For 2-wire RS-485, short R+ and S+ as well as R- and S-.
Signal Level
Differential input, PHC isolation
Differential input, PHC isolation
–
*1. The default settings are given for terminals S3 to S7. For a 3-wire sequence, the default settings are a 3-wire sequence for S5, multi-step speed setting
1 for S6 and multi-step speed setting 2 for S7.
*2. Do not use this power supply for supplying any external equipment.
*3. When driving a reactive load, such as a relay coil with DC power supply, always insert a flywheel diode as shown in
Flywheel diode
External power:
30 VDC max.
Coil
1 A max.
The rating of the flywheel diode must be at least as high as the circuit voltage.
Fig 2.18 Flywheel Diode Connection
Switch S1 - Standard Terminal Board
The Switch S1 can be used to terminate the internal RS422/485 port and for selecting the input signal type for analog input A2. See
Off
S1
On
V I
RS422/485 Port Termination Resistance
Analog Input A2 Current/Voltage Signal Selection
Fig 2.19 Standard terminal board - Switch S1 function
The settings of switch S1 is shown in the following table.
Name
S1-1
Function
RS-485 and RS-422 terminating resistance
S1-2 Input method for analog input A2
Setting
OFF: No terminating resistance
ON: Terminating resistance of 110
Ω
V: 0 to 10 V (internal resistance: 20 k
Ω)
I: 4 to 20 mA (internal resistance: 250
Ω)
Wiring Control Circuit Terminals
Switch S1 and Jumper CN15 - Optional Terminal Board
An optional terminal board which supports switching the signal type of the analog outputs FM and AM between voltage and current is available.The switch over can be performed using jumper CN15. The switch
S1 has the same function like on the standard terminal board. See
for details.
Ch1
Ch2
CN15
I V
Off
S1
On
Analog Output FM Current/Voltage Signal Selection
Analog Output AM Current/Voltage Signal Selection
RS422/485 Port Termination Resistance
Analog Input A2 Current/Voltage Signal Selection
V I
Fig 2.20 Optional terminal board - Switch S1 and jumper CN15 function
The settings of switch S1 and jumper CN15 are described in the following table.
Name
S1-1
S1-2
CN15-
CH1
CN15-
CH2
RS-485 and RS-422 terminating resistance
Function
Input method for analog input A2
Multifunction analog output FM voltage/ current switch
Setting
OFF: No terminating resistance
ON: Terminating resistance of 110
Ω
V: 0 to 10 V (internal resistance: 20 k
Ω)
I: 4 to 20 mA (internal resistance: 250
Ω)
I: Current output
V: Voltage output
Multifunction analog output AM voltage/ current switch
I: Current output
V: Voltage output
Sinking/Sourcing Mode
The input terminal logic can be switched between sinking mode (0-V common, NPN) and sourcing mode
(+24V common, PNP) by using the terminals SN, SC, and SP. An external power supply is also supported, providing more freedom in signal input methods.
Table 2.15 Sinking / Sourcing Mode and Input Signals
Internal Power Source - Sinking Mode (NPN) External Power Source - Sinking Mode (NPN)
External +24V
2-33
2-34
Table 2.15 Sinking / Sourcing Mode and Input Signals
Internal Power Source - Sourcing Mode (PNP) External Power Source - Sourcing Mode (PNP)
External +24V
Wiring Control Circuit Terminals
Control Circuit Terminal Connections
Connections to Inverter control circuit terminals are shown in
Multi-function digital inputs
[Factory settings]
Forward Run/Stop
Reverse Run/Stop
External fault
Fault reset
Multi-step speed setting 1
Multi-step speed setting 2
Jog frequency selection
≈
Varispeed E7
CIMR-E7Z47P5
S1
S2
S3
S4
S5
S6
S7
SN
SC
SP
24V
E(G)
Shield terminal
Shield terminal
E(G)
MA
MB
MC
≈
Fault contact output
250 VAC, 1 A max.
30 VDC, 1 A max.
M1
M2
M3
M4
Contact output 1
[Default: During run]
Contact output 2
[Default: Zero speed]
Multi-function digital output
250 VAC, 1 A max.
30 VDC, 1 A max.
2kΩ
Adjustment
3
1
2
0 to 10V
4 to 20mA
P
2k
Ω
P
MEMOBUS communication
RS-485/422
P
P
+V
Analog input power supply
+15 V, 20 mA
A1
Analog input 1: Master frequency reference
S+
S-
IG
A2
AC
Multi-function analog input 1:
[Default: Frequency Bias
4 to 20 mA (250 )]
-V
0V
Analog input power supply
-15 V, 20 mA
Terminating resistance
R+
R-
FM
AM
AC
Adjustment,
20 k
Ω
+
FM
-
Multi-function analog output 1
(0 to 10 V, 2 mA)
[Default: Output frequency, 0 to 10 V]
Adjustment,
20 k Ω
+
AM
-
Multi-function analog output 2
(0 to 10 V, 2 mA)
[Default: Output current, 0 to 10 V]
Shielded wires P
Twisted-pair shielded wires
Fig 2.21 Control Circuit Terminal Connections
2-35
2-36
Control Circuit Wiring Precautions
Observe the following precautions when wiring control circuits.
•
Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, U/T1, V/T2, W/T3,
, 1, 2, and 3) and other high-power lines.
•
Separate wiring for control circuit terminals MA, MB, MC, M1, M2, M3, and M4 (relay outputs) from wiring to other control circuit terminals.
•
If using an optional external power supply, it shall be a UL Listed Class 2 power supply source.
•
Use twisted-pair or shielded twisted-pair cables for control circuits to prevent operating faults.
•
Ground the cable shields so as to maximize the contact area of the shield and ground.
•
Cable shields have to be grounded on both cable ends.
Wiring Check
Wiring Check
Checks
Check all wiring after wiring has been completed. Do not perform continuity check on control circuits. Perform the following checks on the wiring.
•
Is all wiring correct?
•
Have no wire clippings, screws, or other foreign material been left?
•
Are all screws tight?
•
Are any wire ends contacting other terminals?
CAUTION
• Ensure that the door locks are closed and the cable glands are tightened after wiring. Otherwise the equipment may be damaged by the ingress of water or dust.
• Keep any water or dust outside of the Inverter when wiring. Otherwise the equipment may be damaged by the ingress of water or dust.
• Use the proper cable gland for each cable. Otherwise the equipment may be damaged by the ingress of water or dust.
• Mount the blind plugs attached for option and control card entry if these terminals are not connected.
This will keep IP54 protection for the inverter. Otherwise the equipment may be damaged by the ingress of water or dust.
WARNING
• Be sure to ground the grounding terminal. Moreover be sure to ground the shield of motor cable on the motor side. Otherwise an electric shock can occur.
2-37
2-38
Installing and Wiring Option Cards
Option Card Models
Option cards for field bus communications can be mounted in the Inverter like shown in
lists the type of Option Cards and their specifications.
Table 2.16 Option Cards
Card
Communication cards
PLC Option Card
Model
3G3RV-PDRT2
SI-P1
SI-R1
SI-S1
SI-J
3G3RV-P10ST8-E
3G3RV-P10ST8-DRT-E
Specifications
Intelligent DeviceNet option card
Option card for Profibus-DP fieldbus
Option card for InterBus-S fieldbus
Option card for CANopen fieldbus
Option card for LONworks
PLC option card
PLC option card with DeviceNet communications port (Slave)
Installation in IP00 and NEMA 1 / IP20 Inverters
Before mounting an Option Card, remove the terminal cover and be sure that the charge indicator inside the
Inverter does not glow anymore. After that remove the Digital Operator, front cover and the option clip. Then mount the Option Card.
Preventing Option Card Connectors from Rising
After installing the Option Card insert the Option Clip to prevent the side with the connector from rising. The
Option Clip can be easily removed before installing the card by holding onto the protruding portion of the Clip and pulling it out.
CN2
C Option Card connector
C Option Card mounting spacer
C Option Card
Option Clip
(To prevent raising of
C Option Card)
Fig 2.22 Mounting Option Cards
Installing and Wiring Option Cards
Installation in IP54 Inverters
Before mounting an Option Card, open the inverter door and be sure that the charge indicator inside the
Inverter does not glow anymore. After that remove the option clip and mount the Option Card like with the
IP00 or NEMA 1 Inverter.
Cable Gland Size for Option Cards
Refer to the terminal specification in each option card’s manual..
Table 2.17 Cable Gland Size for Option Cards
Cable Gland Size
Possible Clamping
Cable Diameter (mm)
Wire Type
M16
*1
4.5 to 7
• Shielded twisted-pair wire
• Shielded, PVC multi-core cable
(e.g. Lappkabel Ölflex)
*1. Refer to
for tightening torques for the cable glands.
Wiring Method for Option Cards
For the wiring refer to
below.
Option Card
Cable Tie
(optional)
Option Cable
Cable Mounting Base
Earth Clamp
Fig 2.23 Option Card Wiring for Inverters with 22 to 55kW
2-39
2-40
3
Digital Operator and
Modes
This chapter describes Digital Operator displays and functions, and provides an overview of operating modes and switching between modes.
Digital Operator..................................................................3-2
Modes ................................................................................3-5
3-2
Digital Operator
This section describes the displays and functions of the Digital Operator.
Digital Operator Display
The key names and functions of the Digital Operator for the IP00 and NEMA 1 / IP20 inverters are described below. This operator is referred to as “LED Digital Operator” or JVOP-161-OY
Drive Mode Indicators
FWD: Lights up when a forward run command is input.
REV: Lights up when a reverse run command is input.
SEQ: Lights up when the run command from the control circuit terminal is enabled.
REF: Lights up when the frequency reference from control circuit terminals A1 and A2 is enabled.
ALARM: Lights up when an error or alarm has occurred.
Data Display
Displays monitor data, parameter numbers, and settings.
Mode Display
DRIVE: Lights up in Drive Mode.
QUICK: Lights up in Quick Programming Mode.
ADV: Lights up in Advanced Programming Mode.
VERIFY:Lights up in Verify Mode.
A. TUNE:Lights up in Autotuning Mode.
Keys
Execute operations such as setting user parameters, monitoring, jogging, and autotuning.
Fig 3.1 LED Digital Operator Component Names and Functions
Digital Operator
The IP54 Inverter is equipped with a different type of digital operator, the LCD Digital Operator or JVOP-
160-OY. This Operator features a clear text display with 5 lines while the key names and functions are the same, see
. This operator is also available as an option for IP00 and NEMA 1 / IP20 Inverters.
Drive Mode Indicators
FWD: Lights up when a forward run command is input.
REV: Lights up when a reverse run command is input.
SEQ: Lights up when the run command from the control circuit terminal is enabled.
REF: Lights up when the frequency reference from control circuit terminals A1 and A2 is enabled.
ALARM: Lights up when an error or alarm has occurred.
Data Display
Displays monitor data, parameter numbers, and settings.
Keys
Execute operations such as setting user parameters, monitoring, jogging, and autotuning.
Fig 3.2 LCD Digital Operator Component Names and Functions
Digital Operator Keys
The names and functions of the Digital Operator Keys are described in
Table 3.1 Key Functions
Key Name
LOCAL/REMOTE Key
Function
Switches between operation via the Digital Operator (LOCAL) and the settings in b1-01 and b1-02 (REMOTE).
This key can be enabled or disabled by setting parameter o2-01.
MENU Key Selects the modes.
ESC Key
JOG Key
FWD/REV Key
Shift/RESET Key
Returns to the status before the DATA/ENTER Key was pressed.
Enables jog operation when the Inverter is being operated from the
Digital Operator.
Selects the rotation direction of the motor when the Inverter is being operated from the Digital Operator.
Sets the active digit when programming user parameters.
Also acts as the Reset key when a fault has occurred.
3-3
3-4
Key Name
Increment Key
Decrement Key
Table 3.1 Key Functions
Function
Selects user parameter numbers and increments parameter settings.
Used to move to the next item or data.
Selects user parameter numbers and decrements parameter settings.
Used to move to the previous item or data.
DATA/ENTER Key Enters menus and parameters and validates parameter settings.
RUN Key
Starts operation when the Inverter is being controlled by the Digital
Operator (LOCAL Mode).
STOP Key
Stops Inverter operation (LOCAL and REMOTE Mode).
This key can be enabled or disabled when operating from a source different tan the operator by setting parameter o2-02.
Except in diagrams, Keys are referred to the Key names listed in the above table.
There are indicators on the upper left of the RUN and STOP keys on the Digital Operator. These indicators will light and flash to indicate the operating status.
The RUN key indicator will flash and the STOP key indicator will light while a DC current is injected in the motor. The relationship between the indicators on the RUN and STOP keys and the Inverter status is shown in
Output
Frequency
RUN command
Frequency
Reference
RUN
STOP
Lit up
Blinking
Not lit up
Fig 3.3 RUN and STOP Indicators
Modes
Modes
This section describes the Inverter's modes and switching between modes.
Inverter Modes
The Inverter's user parameters and monitoring functions are organized in groups called modes that make it easier to read and set user parameters. The Inverter is equipped with 5 modes.
The 5 modes and their primary functions are shown in the
Drive mode
Mode
Quick programming mode
Advanced programming mode
Verify mode
Autotuning mode
Table 3.2 Modes
Primary function(s)
The Inverter can be run in this mode.
Use this mode for monitoring values such as frequency references or output current, displaying fault information and the fault history.
Use this mode to read and set the basic user parameters to operate the Inverter.
Use this mode to reference and set all user parameters.
Use this mode to read/set user parameters that have been changed from their factory-set values.
Use this mode when running a motor with unknown motor parameters. During
Autotuning the line-to-line resistance is measured and set automatically.
3-5
3-6
Switching Modes
The mode selection display will appear when the MENU key is pressed from any other operator display. Press the MENU key to switch between the different modes.
When the DATA/ENTER key is pressed the monitor display is entered. Depending on the entered menu the monitor data or parameters are displayed.
Example Operations with LED Digital Operator
shows the mode transition appearance with the LED digital operator.
Mode Selection Display Monitor Display Setting Display
MENU
Power ON
Drive Mode
ESC
(Operation possible)
MENU
Quick Programming Mode
ESC
ESC
MENU
Advanced Programming Mode
ESC ESC
MENU
Verify Mode
ESC
MENU
Autotuning Mode
ESC
ESC
Lit Up Blinking Not lit up
Fig 3.4 Mode Transitions with LED Digital Operator
Example Operations with LCD Digital Operator
shows the mode transition appearance with the LCD digital operator.
Display at Startup
-DRIVE-
Frequency Ref
Rdy
U1 01 =60.00Hz
U1-02= 60.00Hz
U1-03= 10.05A
Mode Selection
Display
MENU
Monitor Display Setting Display
ESC
-DRIVE-
Monitor
U1
-01
Rdy
= 0.00Hz
U1-02= 0.00Hz
U1-03= 0.00A
RESET
-DRIVE-
Frequency Ref
Rdy
U1 01 = 0.00Hz
U1-02= 0.00Hz
U1-03= 0.00A
ESC
ESC
-DRIVE-
Frequency Ref
Rdy
0
~
-DRIVE-
** Main Menu **
Operation
MENU
-QUICK-
** Main Menu **
Quick Setting
MENU
-ADV-
** Main Menu **
Programming
MENU
-VERIFY-
** Main Menu **
Modified Consts
MENU
-A.TUNE-
** Main Menu **
Auto-Tuning
ESC
-QUICK-
Select Language
A1-00= 0
English
*0*
ESC
-ADV-
Initialization
A1
- 00= 0
Select Language
RESET
-ADV-
Select Language
A1 00 = 0
*0*
English
"0"
ESC ESC
-ADV-
Select Language
A1-00=
English
"0"
0
*0*
ESC
-VERIFY-
None Modified
ESC
-A.TUNE-
Mtr. Rated Power
T102 = 0.40kW
(0.00 ~ 650.00)
"0.40 kW"
ESC
ESC
-QUICK-
Select Language
A1-00=
English
"0"
0
*0*
-A.TUNE-
Mtr. Rated Power
(0.00 ~ 650.00)
"0.40kW"
Fig 3.5 Mode Transitions with LCD Digital Operator
Modes
3-7
3-8
Drive Mode
The Inverter can be operated in the Drive Mode. Monitor parameters, fault information and the fault history parameters can be displayed.
When b1-01 (Reference selection is set to 0, the frequency reference can be changed from the frequency setting display. Use the Increment, Decrement and Shift/RESET keys to change it. The set value will be accepted when the DATA/ENTER key has been pressed.
Example Operations with LED Digital Operator
shows mode transition examples with the LED digital operator.
Mode Selection Display Monitor Parameter Display Frequency Setting Display
Drive Mode
MENU
Power ON
Frequency reference
Frequency Reference
Frequency reference setting/ display unit 01-03
Frequency Reference Setting /
Display unit set by 01-03
ESC
Output frequency
Output Frequency
ESC
ESC
Output current
Output Current
ESC
Monitor setting for o1-01
Monitor setting set by o1-01
ESC
Status Monitor
Status Monitor
RESET
Frequency reference
Frequency Reference
ESC
Fan operating time
PI Feedback 2
ESC
ESC
ESC
ESC
Fault Trace
Fault Trace
RESET
Current error
Current error
ESC
Operating time at error
Operating time at error
ESC
ESC
ESC
ESC
RESET
1st previous error
Previous error
ESC
Operating time at 4th latest error
ESC
ESC
ESC
Fig 3.6 Operations in Drive Mode with LED Digital Operator
Modes
Example Operations with LCD Operator
shows mode transition examples with the LCD digital operator.
Display at Startup
-DRIVE-
Frequency Ref
Rdy
U1 01 =60.00Hz
U1-02= 60.00Hz
U1-03= 10.05A
Mode Selection
Display
MENU
-DRIVE-
** Main Menu **
Operation
MENU
-QUICK-
** Main Menu **
Quick Setting
MENU
-ADV-
** Main Menu **
Programming
MENU
-VERIFY-
** Main Menu **
Modified Consts
ESC
Monitor Display
Frequency Setting Display
A B
-DRIVERdy
Monitor
U1 - 01=60.00Hz
U1-02= 60.00Hz
U1-03= 10.05A
1 2
RESET
ESC
-DRIVE-
Frequency Ref
Rdy
U1 01 =60.00Hz
U1-02= 60.00Hz
U1-03= 10.05A
-DRIVERdy
Monitor
U1
- 02
=60.00Hz
U1-03= 10.05A
U1-06= 203.5VAC
RESET
-DRIVE-
Output Freq
Rdy
U1 -
02 =60.00Hz
U1-03= 10.05A
U1-06= 203.5VAC
ESC
-DRIVE-
Frequency Ref
Rdy
0
(0.00 60.00)
"0.00Hz"
ESC
The Frequency Setting
Display will not be displayed when an frequency reference source different than the digital operator is used.
-DRIVERdy
Monitor
U1 - 53 =13.17%
U1-01= 60.00Hz
U1-02= 60.00Hz
-DRIVE-
Fault Trace
U2 - 01= None
U2-02= OC
U2-03= 60.00Hz
Rdy
RESET
-DRIVE-
PI Feedback 2
Rdy
U1 - 53 =13.17%
U1-01= 60.00Hz
U1-02= 60.00Hz
ESC
1
3
2
4
RESET
-DRIVE-
Current Fault
U2 01 = None
U2-02= OC
U2-03= 60.00Hz
Rdy
ESC
MENU
-A.TUNE-
** Main Menu **
Auto-Tuning
-DRIVE-
Fault Trace
U2 - 02= OC
U2-03= 60.00Hz
U2-04= 60.00Hz
Rdy
-DRIVE-
Fault History
U3 - 01 = OC
U3-02= OV
U3-03= OH
Rdy
RESET
-DRIVE-
Last Fault
U2 02 = OC
U2-03= 60.00Hz
U2-04= 60.00Hz
Rdy
ESC
3
5
4
6
Rdy
RESET
U3 01 = OC
U3-02= OV
U3-03= OH
ESC
ESC
ESC
U2 - 02= OC
Over Current
Rdy
U3 - 01= OC
Over Current
Rdy
-DRIVE-
Fault History
U3 - 02 = OV
U3-03= OH
U3-04= UV
Rdy
RESET
ESC
-DRIVE-
Fault History
U3 -
02 = OV
U3-03= OH
U3-04= UV
Rdy
5 6
A B
ESC
U3 - 02= OV
DC Bus Overvolt
Rdy
Fig 3.7 Operations in Drive Mode with LCD Digital Operator
IMPORTANT
To run the Inverter after viewing/changing parameters press the MENU key and the DATA/ENTER key in sequence to enter the Drive mode. A Run command is not accepted as long as the Inverter in any other display.
To enable Run commands from other sources during programming set parameter b1-08 to “1”.
Quick Programming Mode
In Quick Programming Mode, the basic parameters required for Inverter trial operation can be monitored and set.
The parameters can be changed in the setting displays. Use the Increment, Decrement and Shift/RESET keys to change the settings. The setting will be saved and the display will return to the monitor display when the
DATA/Enter key is pressed.
for details on the parameters displayed in Quick Programming Mode.
3-9
Example Operations with LED Digital Operator
shows example operations in Quick Programming Mode with the LED Digital Operator.
Mode Selection Display Monitor Display
MENU
Quick Programming Mode Reference Source
ESC
ESC
RUN Command Source
ESC
ESC
3-10
ESC
Motor Rated Current
ESC
Fig 3.8 Operations in Quick Programming Mode with LED Digital Operators
Example Operations with LCD Operator
shows example operations in Quick Programming Mode using the LCD Digital Operator.
MENU
-DRIVE-
** Main Menu **
Operation
MENU
-QUICK-
** Main Menu **
Quick Setting
MENU
-ADV-
** Main Menu **
Programming
MENU
-VERIFY-
** Main Menu **
Modified Consts
MENU
-A.TUNE-
** Main Menu **
Auto-Tuning
ESC
A
B
-QUICK-
Reference Source b1-01= 1
*1*
Terminals
"1"
-QUICK-
Run Source b1-02= 1
*1*
Terminals
"1"
ESC
ESC
-QUICK-
Reference Source b1-01=
Terminals
"1"
*1*
-QUICK-
Run Source b1-02=
Terminals
"1"
*1*
-QUICK-
Motor Rated FLA
E2-01= 1.90A
(0.32 ~ 6.40)
"1.90A"
A
B
ESC
-QUICK-
Motor Rated FLA
E2-01= 0 01.90A
(0.32 ~ 6.40)
"1.90A"
Fig 3.9 Operations in Quick Programming Mode with LCD Digital Operators
Modes
Advanced Programming Mode
In Advanced Programming Mode all parameters can be monitored and set.
The parameters can be changed from the setting display. Use the Increment, Decrement, and Shift/RESET keys to change the settings. The setting will be saved and the display will return to the monitor display when the DATA/Enter key is pressed.
for details on the parameters.
Example Operations with LED Digital Operator
shows example operations in Advanced Programming Mode with the LED Digital Operator.
Mode Selection Display
MENU
Function Selection Display
Monitor Display
Setting Display
ESC
Initialize Mode: A1-xx
RESET
ESC
Language Selection
Access Level
ESC
ESC
ESC
Initialize
ESC
ESC
ESC
PI Control: b5-xx
RESET
PI Control Mode Selection
ESC
Proportional Gain
ESC
ESC
ESC
PI Unit Selection
ESC
ESC
ESC
Copy Function: o3-xx
RESET
Copy Function Selection
ESC
Read Permission Selection
ESC
ESC
ESC
Fig 3.10 Operations in Advanced Programming Mode with LED Digital Operator
3-11
3-12
Example Operations with LCD Digital Operator
shows example operations in Advanced Programming Mode using the LCD Digital Operator.
Mode Selection Display Monitor Display Setting Display
1 2
-ADV-
** Main Menu **
Programming
A B
ESC
-ADV-
Initialization
A1
- 00= 0
Select Language
RESET
-ADV-
Select Language
A1
- 00 = 0
English
"0"
*0*
ESC
ESC
-ADV-
Select Language
A1
- 01 = 0
English
"0"
*0*
MENU
-VERIFY-
** Main Menu **
Modified Consts
-ADV-
Initialization
A1
- 03= 0
Init Parameters
ESC
-ADV-
Init Parameters
A1
- 03 = 0
No Initialize
"0"
*0*
MENU
-A.TUNE-
** Main Menu **
Auto-Tuning
MENU
-DRIVE-
** Main Menu **
Operation
MENU
-QUICK-
** Main Menu **
Quick Setting
-ADV-
PI Control b5
- 01= 0
PI Mode
-ADV-
PI Control b5 - 29= 1.00
PI Fb SqRt Gain
A B
RESET
-ADV-
Init Parameters
A1
- 03 = 0
No Initialize
"0"
*0*
ESC
1 2
3
4
RESET
-ADV-
PI Mode b5
- 01 = 0
Disabled
"0"
*0*
ESC
RESET
-ADV-
PI Fb SqRt Gain b5
- 29 = 1.00
(0.00 2.00)
"1.00"
ESC
3 4
ESC
-ADV-
PI Mode b5
- 01 = 0
Disabled
"0"
*0*
ESC
-ADV-
PI Fb SqRt Gain b5 29 = 1 .00
(0.00 2.00)
"1.00"
MENU
Fig 3.11 Operations in Advanced Programming Mode with LCD Digital Operator
Modes
9
10
11
Setting User Parameters using the LED Digital Operator
Below in
the procedure to change C1-01 (Acceleration Time 1) from 10 sec. to 20 sec. is shown using the LED Digital Operator
.
Table 3.3 Setting User Parameters in Advanced Programming Mode using the LED Digital Operator
Step
No.
Digital Operator Display Description
1 Power supply turned ON.
2
Press the MENU key to enter the Mode Selection Display.
3
Press the MENU key to scroll through the
Mode Selection Display.
4
5
6
7
8
Press the DATA/ENTER key to access the
Monitor Display in Advanced Programming
Mode.
Press the Increment or Decrement key until
C1-01 (Acceleration Time 1) is displayed.
Press the DATA/ENTER key to access the setting display. The setting can be changed now.
Press the Shift/RESET key to move the flashing digit to the right.
Press the Decrement key to change the value to
20.00sec.
Press the DATA/ENTER key to validate the new setting. “End” is displayed for 1 sec., then the new parameter setting for 0.5 sec.
The display returns to the Monitor Display.
3-13
3-14
Setting User Parameters using the LCD Digital Operator
the procedure to change C1-01 (Acceleration Time 1) from 10 sec. to 20 sec. is shown
using the LCD Digital Operator.
Table 3.4 Setting User Parameters in Advanced Programming Mode using the LCD Digital Operator
Step
No.
Digital Operator Display Description
1
-DRIVE-
Frequency Ref
Rdy
U1 01 =50.00Hz
U1-02= 0.00Hz
U1-03= 0.00A
Display after power supply has been turned ON.
2
-DRIVE-
** Main Menu **
Operation
Press the MENU key to enter the mode selection display.
3
-QUICK-
** Main Menu **
Quick Setting
Press the MENU key to scroll to the position of the advanced programming Menu.
4
-ADV-
** Main Menu **
Programming
5
-ADV-
Initialization
A1
0
Select Language
6
-ADV-
Accel/Decel
10.0sec
Accel Time 1
7
8
9
10
-ADV-
Accel/Decel
0 010.0sec
(0.0~6000.0)
10.0sec
-ADV-
Accel/Decel
0 0 10.0sec
(0.0~6000.0)
10.0sec
-ADV-
Accel/Decel
00 1 0.0sec
(0.0~6000.0)
10.0sec
-ADV-
Accel/Decel
00 2 0.0sec
(0.0~6000.0)
10.0sec
11
-ADV-
Entry Accepted
Press the DATA/ENTER key to access the monitor display.
Press the Increment or Decrement key until C1-
01 (Acceleration Time 1) is displayed.
Press the DATA/ENTER key to access setting display. The setting can be changed now.
Press the Shift/RESET key to move the flashing digit to the right.
Press the Decrement key to change the value to
20.00 s.
Press the DATA/ENTER key to validate the new setting.
-ADV-
Accel/Decel
C1 01 = 20.0sec
(0.0~6000.0)
10.0sec
“Entry Accepted” is displayed for appr. 1.0 sec. after the data setting has been confirmed with the DATA/ENTER key. The display returns to the C1-01 monitor display.
Modes
Verify Mode
Verify mode is used to display any parameters that have been changed from their default settings, either by programming or autotuning. If no parameter setting has been changed the display will show “NONE” with the
LED operator or “None Modified” with the LCD operator.
In Verify Mode the same procedures as in the programming modes can be used to change parameter settings.
Example Operations with LED Digital Operator
shows an example of operations in the Verify Mode. In that example following parameters have been changed from their default settings: Reference Selection (b1-01), Acceleration Time 1 (c1-01), Input Voltage
Setting (E1-01) and Motor Rated Current (E2-01).
Mode Selection Display Monitor Display Setting Display
MENU
Verify Mode
ESC
Frequency Reference Selection
ESC
Frequency Reference Selection
Acceleration Time 1
Acceleration Time 1
ESC ESC
Input Voltage Setting
Input Voltage Setting
ESC ESC
Motor Rated Current
Motor Rated Current
ESC ESC
Fig 3.12 Operations in Verify Mode with LED Digital Operator
3-15
3-16
Example Operations with LCD Digital Operator
shows an example of operations in the Verify Mode using the LCD Digital Operator. The same parameters have been modified like in
Mode Selection Display Monitor Display
Setting Display
MENU
-ADV-
** Main Menu **
Programming
MENU
-VERIFY-
** Main Menu **
Modified Consts
MENU
-A.TUNE-
** Main Menu **
Auto-Tuning
MENU
-DRIVE-
** Main Menu **
Operation
MENU
-QUICK-
** Main Menu **
Quick Setting
MENU
ESC
A B
-VERIFY-
Reference Source b1 - 01 = 0
*0*
Operator
"1"
-VERIFY-
Accel Time 1
C1 01 = 20.0sec
(0.0 6000.0sec)
"10.0sec"
-VERIFY-
Input Voltage
E1 - 01 = 380VAC
(310 510)
"400VAC"
-VERIFY-
Motor Rated FLA
E2
01 = 2.00A
(0.32 6.40)
"1.90A"
A B
ESC
ESC
ESC
ESC
-VERIFY-
Reference Source b1
- 01 = 0
Terminals
"1"
*0*
-VERIFY-
Accel Time 1
C1 0 020.0sec
(0.0 6000.0sec)
"10.0sec"
E1 01 = 3 8 0VAC
(310 510)
"400VAC"
-VERIFY-
Motor Rated FLA
E2 01 = 0 02.00A
(0.32 6.40)
"1.90A"
Fig 3.13 Operations in Verify Mode with LCD Digital Operator
Modes
Autotuning Mode
Autotuning automatically measures and sets the motor line-to-line resistance parameter including the motor cable in order to compensate the voltage drop and to achieve the best performance.
Example Operations with LED Digital Operator
Set the motor rated output power (in kW) and the motor rated current, specified on the motor nameplate and then press the RUN key. The motor is automatically run and the line-to-line resistance is measured.
shows an example for an Autotuning procedure.
Mode Selection Display Autotuning Monitor Display
MENU
Setting Display
Autotuning Motor Output Power Motor Output Power
ESC
ESC
Motor Rated Current Motor Rated Current
ESC
ESC
Autotuning Start
RUN
Autotuning
STOP
Stop Command Input
Autotuning Completed
Fig 3.14 Operation in Autotuning Mode with LED Digital Operator
3-17
3-18
Example Operations with LCD Digital Operator
shows an example for an Autotuning procedure with LCD Digital Operator
Mode Selection Display
Autotuning
Monitor Display
Setting Display
-A.TUNE-
** Main Menu **
Auto-Tuning
ESC
-A. TUNE-
Mtr Rated Power
T1
- 02 = 0.40
kW
(0.00~650.00)
"0.40kW"
ESC
-A. TUNE-
Mtr Rated Power
T1 - 02 = 0 00.40
kW
(0.00~650.00)
"0.40kW"
MENU
-DRIVE-
** Main Menu **
Operation
MENU
-QUICK-
** Main Menu **
Quick Setting
-A. TUNE-
Rated Current
T1
- 04 = 1.90
(0.32~6.40)
A
"1.90A"
ESC
-A. TUNE-
Rated Current
T1
- 04 = 0 01.90
A
(0.32~6.40)
"1.90A"
MENU
-ADV-
** Main Menu **
Programming
-A. TUNE-
Auto-Tuning
0Hz/ 0.00A
Tuning Ready ?
Press RUN key
Rdy
RUN
ESC
-A. TUNE-
Auto-Tuning
0Hz/ 0.38A
Rdy
START > > > GOAL
STOP
-A. TUNE-
Tune Aborted
STOP key
-A. TUNE-
Tune Successful
0Hz/ 0.00A
MENU
-VERIFY-
** Main Menu **
Modified Consts
MENU
Fig 3.15 Operation in Autotuning Mode with LCD Digital Operator
IMPORTANT
If a fault occurs during autotuning, refer to
.
4
Trial Operation
This chapter describes the procedures for trial operation of the Inverter and provides an example of trial operation.
Trial Operation Procedure..................................................4-2
Trial Operation ...................................................................4-3
Adjustment Suggestions ..................................................4-11
4-2
Trial Operation Procedure
Perform trial operation according to the following flowchart.
START
Installation
Wiring
Set power supply voltage jumper.
*1
Turn ON power.
*1: Set the jumper for 400V class Inverters
of 75kW and more
Confirm status.
Basic settings
(Quick programming mode)
Set E1-03.
V/f default: 400V/50Hz
Motor cable over
50 m or heavy load possibly causing motor to stall or overload?
NO
YES
Non-rotating autotuning for line-to-line resistance
Application settings
(Advanced programming mode)
No-load operation
Loaded operation
Optimum adjustments and parameter settings
Check/record parameters.
END
Fig 4.1 Trial Operation Flowchart
Trial Operation
Trial Operation
The procedure for the trial operation is described in order in this section.
Application Confirmation
First, confirm the application before using the Inverter. It is designed for:
•
Fan, blower, pump
Setting the Power Supply Voltage Jumper
(400 V Class Inverters of 75 kW or Higher)
The power supply voltage jumper must be set for 400 V Class Inverters of 75 kW or higher. Insert the jumper into the voltage connector nearest to the actual power supply voltage.
The jumper is factory-set to 440 V when shipped. If the power supply voltage is not 440 V, use the following procedure to change the setting.
1. Turn OFF the power supply and wait for at least 5 minutes.
2. Confirm that the CHARGE indicator has gone out.
3. Remove the terminal cover.
4. Insert the jumper at the position for the voltage supplied to the Inverter (see
).
5. Return the terminal cover to its original position.
Connector
Jumper (factory-set position)
200 V class power supply
400V class power supply
Power supply input terminals
CHARGE indicator
Fig 4.2 Power Supply Voltage Setting
Power ON
Confirm all of the following items and then turn ON the power supply.
•
Check that the power supply is of the correct voltage.
•
200 V class: 3-phase 200 to 240 VDC, 50/60 Hz
•
400 V class: 3-phase 380 to 480 VDC, 50/60 Hz
•
Make sure that the motor output terminals (U, V, W) and the motor are connected correctly.
•
Make sure that the Inverter control circuit terminal and the control device are wired correctly.
•
Set all Inverter control circuit terminals to OFF.
•
Make sure that the motor is not connected to the mechanical system (no-load status) if possible.
4-3
4-4
Checking the Display Status
After normal power up without any faults the operator display will show the following depending on the operator.
Display with LED Digital Operator
After normal power up without any faults the operator display will show the following:
Display for normal operation
The frequency reference monitor is displayed in the data display section.
When a fault has occurred, the details of the fault will be displayed instead of the above display. In that case, refer to
. The following display is an example of a display for faulty operation.
Display for fault operation
The display will differ depending on the type of fault.
A low voltage alarm is shown at left.
Display with LCD Digital Operator
After normal power up without any faults the operator display will show the following:
Display for normal operation
-DRIVE-
Frequency Ref
Rdy
U1 01 =50.00Hz
U1-02= 0.00Hz
U1-03= 0.00A
The frequency reference monitor is displayed in the data display section.
When a fault has occurred, the details of the fault will be displayed instead of the above display. In that case, refer to
. The following display is an example of a display for faulty operation.
Display for fault operation
-DRIVE-
UV
Main Power Loss
The display will differ depending on the type of fault.
A low voltage alarm is shown at left.
Trial Operation
Basic Settings
Before starting the Inverter ensure that it is initialized, i.e. all parameters are set to their factory defaults.
Therefor set parameter A1-03 to 2220 for 2-wire initialization or to 3330 for 3-wire initialization. Refer to
for details about 2-wire and 3-wire initialization.
Refer to
Chapter 3, Digital Operator and Modes
for Digital Operator operating procedures. Find a list of the
Quick Programming Parameters on
page 5-4, User Parameters Available in Quick Programming Mode
and details of the parameters in
Chapter 6, Parameter Settings by Function
Table 4.1 Basic Parameter Settings
: Must be set. : Set as required.
Class
Parameter
Number b1-01 b1-02 b1-03
C1-01
C1-02
Name Description
Setting
Range
Reference selection
Deceleration time 1
Sets the frequency reference input method.
0: Digital Operator
1: Control circuit terminal
(analog input)
2: MEMOBUS communications
3: Option Card
Operation method selection
Sets the run command input method.
0: Digital Operator
1: Control circuit terminal (digital input)
2: MEMOBUS communications
3: Option Card
Stopping method selection
Acceleration time 1
Selects stopping method when stop command is sent.
0: Deceleration to stop
1: Coast to stop
2: DC braking stop
3: Coast to stop with timer
Sets the acceleration time in seconds for the output frequency to climb from 0% to
100%.
Sets the deceleration time in seconds for the output frequency to fall from 100% to
0%.
0 to 3
0 to 3
0 to 3
0.0 to 6000.0
0.0 to 6000.0
d1-01 to d1-04 and d1-17
Frequency references 1 to 4 and jog frequency reference
Sets the required speed references for multi-step speed operation or jogging.
Factory
Setting
1
1
0
10.0 s
10.0 s
0 to 200.00 Hz d1-01 to d1-04: 0.00
Hz d1-17: 6.00
Hz
Page
E1-01
Input voltage setting
Sets the Inverter's nominal input voltage in volts.
155 to
255 V
*1
200 V
E2-01
L1-01
Motor rated current
Sets the motor rated current.
Motor protection selection
Used to enable or disable the motor overload protection function.
0: Disabled
1: Protection for general purpose motor
(fan cooled)
2: Protection for inverter motor (externally cooled motor)
3: Vector motor protection
0.32 to 6.40
*2
0 to 3
1.90 A
*3
1
4-5
4-6
Table 4.1 Basic Parameter Settings
: Must be set. : Set as required.
Class
Parameter
Number
Name Description
Setting
Range
Factory
Setting
Page
L3-02
Stall prevention selection during acceleration
Sets the stall prevention level (current limit) during acceleration as a percentage of the Inverter rated current.
0 to 200% 120%
L3-04
Stall prevention selection during deceleration
If using the dynamic brake option (Braking Resistor Units and Braking Units), be sure to set parameter L3-04 to 0 (disabled).
0 to 2
*1. Values for 200 V class Inverters are shown. For a 400 V class Inverter the values have to be doubled.
*2. The setting range is 10% to 200% of the Inverter rated output current. The value for a 200 V class Inverter of 0.4 kW is given.
*3. The factory setting depends on the Inverter capacity. The value for a 200 V class Inverter of 0.4 kW is given
1
Trial Operation
Selecting the V/f pattern
•
Set either one of the fixed patterns (0 to E) in E1-03 (V/f Pattern Selection) or set F in E1-03 to specify a user-set pattern as required for the motor and load characteristics in E1-04 to E1-13 in advanced programming mode.
Table 4.1 Selecting the V/f Pattern
Motor V/f Selection
E1-03 = 0
General purpose motor at 50 Hz
E1-03 = F (default)(Parameters E1-04 to E-13 are changeable and preset for 50 Hz)
General pupoase motor at 60 Hz E1-03 = 1
•
It is recommended to perform non-rotating autotuning for the line-to-line resistance if the motor cable is 50 m or longer for the actual installation or the load is heavy enough to produce stalling.
Autotuning
Autotuning for Line-to-Line Resistance
Autotuning can be used to improve the performance when very long motor cables are used or when motor and inverter have different power ratings.
To perform autotuning set T1-02 (Motor rated power) and T1-04 (Motor rated current) and then press the
RUN key on the Digital Operator. The Inverter will supply power to the motor for approximately 20 seconds and the line-to-line resistance (stator windings and cable resistance) will be measured automatically.
IMPORTANT
Power will be supplied to the motor during autotuning but the motor will not turn. Do not touch the motor until autotuning has been completed.
Parameter Settings for Autotuning
The following parameters must be set for autotuning.
Parameter
Number
Name Display
T1-02
Motor output power
Set the output power of the motor in Kilowatts.
T1-04
Motor rated current
Set the rated current of the motor in Amps.
Setting Range
Factory Setting
10% to 200% of
Inverter rated output
10% to 200% of
Inverter rated current
Same as
Inverter rated output
Same as general-purpose motor with same capacity as Inverter
4-7
4-8
Digital Operator Displays during Autotuning using LED Digital Operator
The following displays will appear on the LED Digital Operator during autotuning.
Table 4.2 LED Digital Operator Displays during Autotuning
Digital Operator Display
Motor rated power and current: T1-02 and T1-04
Description
When the Autotuning Mode is entered parameters T1-
02 and T1-04 have to entered.
Autotuning start display: TUn12
Autotuning in progress Stop command input
The autotuning start display will appear when the parameter settings have been completed. The
A.TUNE and DRIVE indicators will be lit.
Autotuning will start when the RUN Key is pressed from the autotuning start display.
If the STOP Key is pressed or a measurement error occurs during autotuning an error message will be display and autotuning will be stopped.
Autotuning completed
END will be displayed after approximately 20 seconds, indicating that autotuning has been completed.
Digital Operator Displays during Autotuning using LCD Digital Operator
The following displays will appear on the LCD Digital Operator during autotuning.
Table 4.3 LCD Digital Operator Displays during Autotuning
Digital Operator Display
Motor rated power and current: T1-02 and T1-04
-A. TUNE-
Mtr Rated Power
T1
- 02 = 0.40
kW
(0.00~650.00)
"0.40kW"
Description
When the Autotuning Mode is entered parameters T1-
02 and T1-04 have to entered.
Autotuning start display
-A. TUNE-
Auto-Tuning
0Hz/ 0.00A
Tuning Ready ?
Press RUN key
Rdy
Autotuning
-A. TUNE-
Auto-Tuning
0Hz/ 0.38A
Rdy
START > > > GOAL
Autotuning completed
-A. TUNE-
Tune Successful
0Hz/ 0.00A
The autotuning start display will appear when the parameter settings have been completed. Autotuning will start when the RUN Key is pressed from the autotuning start display.
Stop command input
-A. TUNE-
Tune Aborted
STOP key
If the STOP Key is pressed or a measurement error occurs during autotuning an error message will be display and autotuning will be stopped.
“Tune Successful” will be displayed after approximately 20 seconds, indicating that autotuning has been completed.
Trial Operation
Application Settings
User parameters can be set as required in advanced programming mode. All the parameters that can be set in quick programming mode can also be displayed and set in advanced programming mode.
Setting Examples
The following are examples of settings for applications.
•
To prevent the machine from being operated in reverse, set b1-04 to 1 to disable reverse operation or to 3 for output phase rotation and reverse disabled.
•
To increase the speed of a 50 Hz motor by 10%, set E1-04 to 55.0 Hz.
•
To use a 0 to 10 V analog signal for a 50 Hz motor for variable-speed operation between 0 and 45 Hz (0% to 90% speed), set H3-02 to 90.0%.
•
To limit the speed range between 20% and 80% set d2-01 to 80.0% and set d2-02 to 20.0%.
No-load Operation
This section describes trial operation in which the motor is in no-load state, that means the machine is not connected to the motor. To avoid failures caused due to the wiring of the control circuit it’s recommended to use the LOCAL mode. Press the LOCAL/REMOTE key on the Digital Operator to change to LOCAL mode (the
SEQ and REF indicators on the Digital Operator should be OFF).
Always confirm safety around the motor and machine before starting Inverter operation from the Digital
Operator. Confirm that the motor works normally and that no errors are displayed at the Inverter. For applications, at which the machine can be driven in one direction only, check the motor rotation direction.
Operation with Jog frequency reference (d1-17, default: 6.00 Hz) can be started and stopped by pressing and releasing the JOG key on the Digital Operator. If the external control circuit prevents operation from the Digital Operator, confirm that emergency stop circuits and machine safety mechanisms are functioning, and then start operation in REMOTE mode (i.e., with a signal from the control signal terminal).
NOTE
Both, a RUN command (forward or reverse) and a frequency reference (or multi-step speed command) must be provided to start Inverter operation.
Loaded Operation
Connecting the Load
•
After confirming that the motor has stopped completely, connect the mechanical system.
•
Be sure to tighten all the screws when connecting the motor shaft to the mechanical system.
Operation using the Digital Operator
•
Use the Digital Operator to start operation in LOCAL mode in the same way as in no-load operation.
•
For the case that a fault occurs during operation, make sure that the STOP key on the Digital Operator is easily accessible.
•
At first, set the frequency reference to a low speed, e.g. to one tenth of the nominal operating speed.
4-9
4-10
Checking Operating Status
•
Having checked that the operating direction is correct and that the machine is operating smoothly at slow speed, increase the frequency reference.
•
After changing the frequency reference or the rotation direction, check that there is no oscillation or abnormal sound from the motor. Check the monitor display to ensure that U1-03 (Output Current) is not too high.
•
page 4-11, Adjustment Suggestions
if hunting, vibration, or other problems originated by the control system occur.
Check and Recording User Parameters
Use verify mode to check user parameters that have been changed for trial operation and record them in a user parameter table.
Any user parameters that have been changed by autotuning will also be displayed in verify mode.
If required, the copy function (parameters o3-01 and o3-02 displayed in advanced programming mode) can be used to copy the changed settings from the inverter to a recording area in the Digital Operator. If changed settings are saved in the Digital Operator, they can be easily copied back to the Inverter to speed up system recovery if the inverter has to be replaced for any reason.
The following functions can also be used to manage user parameters.
•
Recording user parameters
•
Setting access levels for user parameters
•
Setting a password
Recording User Parameters (o2-03)
If o2-03 is set to 1 after completing trial operation, the settings of user parameters will be saved in a separate memory area in the inverter. When the Inverter settings have been changed for any reason, the user parameters can be initialized to the settings saved in the separate memory area by setting A1-03 (Initialize) to 1110.
User Parameter Access Levels (A1-01)
A1-01 can be set to 0 (monitoring-only) to prevent user parameters from being changed. A1-01 can also be set to 1 (User-specified Parameters) to display only parameters required by the machine or application in a programming mode. These parameters can be determined by setting the A2 parameters.
Password (A1-04 and A1-05)
When the access level is set to monitoring-only (A1-01 = 0), a password can be set so that user parameters will be displayed only when the correct password has been input.
Adjustment Suggestions
Adjustment Suggestions
If hunting, vibration or other problems occur during trial operation, adjust the parameters listed in the following table according to the control method. This table lists the most commonly used user parameters only.
Table 4.4 Useful Parameters in case of Problems during Trial Operation
Name (Parameter
Number)
Performance
Hunting-prevention gain (N1-02)
Controlling hunting and vibration in middlerange speeds
(20 to 80% FMAX)
Carrier frequency selec-
• Reducing motor magnetic noise tion
(C6-02)
• Controlling hunting and vibration at low
Torque compensation delay time constant
(C4-02)
Torque compensation gain (C4-01) speeds
• Increasing torque and speed response
• Controlling hunting and vibration
• Improving torque at low speeds (10 Hz or lower)
• Controlling hunting and vibration
Middle output frequency voltage
(E1-08)
Minimum output frequency voltage
(E1-10)
• Improving torque at low speeds
• Controlling shock at startup
Factory Setting
1.00
Depends on capacity
Depends on capacity
1.00
Depends on capacity and voltage
Recommended
Setting
0.50 to 2.00
0.4 kHz to default
200 to 1000 ms
0.50 to 1.50
Default to
“Default + 3 to 5
V”
*1
*1. The setting is given for 200 V Class Inverters. Double the voltage for 400 V Class Inverters.
Adjustment Method
• Reduce the setting if torque is insufficient for heavy loads.
• Increase the setting if hunting or vibration occurs for light loads.
• Increase the setting if motor magnetic noise is high.
• Reduce the setting if hunting or vibration occurs at low to middle-range speeds.
• Reduce the setting if torque or speed response is slow.
• Increase the setting if hunting or vibration occurs.
• Increase the setting in small steps of 0.05 if torque is insufficient at low speeds.
• Reduce the setting if hunting or vibration occurs for light loads.
• Increase the setting in small steps of 1 or 2 V if torque is insufficient at low speeds
• Reduce the setting if shock at startup is large.
The following user parameters will also affect the control system indirectly.
Table 4.5 Parameters influencing performance indirectly
Name (Parameter Number)
Acceleration/deceleration times
(C1-01 to C1-09)
S-curve characteristics (C2-01 and C2-02)
Jump frequencies (d3-01 to d3-04)
Analog input filter time constant (H3-12)
Stall prevention (L3-01 to L3-06)
Application
Adjust torque during acceleration and deceleration.
Used to prevent speed shock at start or stop of the acceleration.
Used to avoid resonance points during constant speed.
Used to prevent fluctuations in analog input signals caused by noise.
Used to prevent OV (overvoltage error) and motor stalling for heavy loads or rapid acceleration/deceleration. Stall prevention is enabled by default and the setting normally has not to be changed. When using an optional braking resistor unit and braking unit, however, disable stall prevention during deceleration by setting L3-04 to 0.
4-11
4-12
5
User Parameters
This chapter describes all user parameters that can be set in the Inverter.
User Parameter Descriptions .............................................5-2
Digital Operation Display Functions and Levels ................5-3
User Parameter Tables......................................................5-6
5-2
User Parameter Descriptions
This section describes the contents of the user parameter tables.
Description of User Parameter Tables
User parameter tables are structured as shown below. Here b1-01 (Frequency Reference Selection) is used as an example.
Parameter
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
Access
Level
MEMO-
BUS Register
Page b1-01
Reference selection
Sets the frequency reference input method.
0: Digital Operator
1: Control circuit terminal (analog input)
2: MEMOBUS communications
3: Option Card
0 to 3 1 No Q 180H –
• Parameter Number:
• Name:
• Description:
• Setting Range:
• Factory Setting:
• Change during Operation:
• Access Level:
• MEMOBUS Register:
• Page:
The number of the user parameter.
The name of the user parameter.
Details on the function or settings of the user parameter.
The setting range for the user parameter.
The default setting of the user parameter.
Indicates whether the parameter can be changed while the Inverter is in operation or not.
Yes: Changes are possible during operation.
No: Changes are not possible during operation.
Indicates the parameter access level in which the parameter can be changed or monitored.
Q: Quick programming mode and advanced programming mode.
A: Advanced programming mode only.
The register number used for MEMOBUS communications.
Reference page for more detailed information about the parameter.
Digital Operation Display Functions and Levels
Digital Operation Display Functions and Levels
The following figure shows the Digital Operator display hierarchy for the Inverter.
MENU Drive Mode
Inverter can be operated and its status can be displayed.
Quick Programming Mode
Minimum parameters required for operation can be monitored or set.
Advanced Programming Mode
All parameters can be monitored or set.
Verify Mode
Parameters changed from the default settings can be monitored or set.
Autotuning Mode
Automatically measures the line-to-line resistance.
Function
Status Monitor Parameters
Fault Trace
Fault History
Initialize Mode
User-specified Setting Mode
Operation Mode Selections
DC Injection Braking
Speed Search
Timer Function
PI Control
Energy Saving
Acceleration/Deceleration
S-curve Acceleration
Torque Compensation
Carrier Frequency
Preset Reference
Reference Limits
Jump Frequencies
Reference Frequency Hold
V/f Pattern
Motor Setup
Communications Option Card
Multi-function Digital Inputs
Multi-function Digital Outputs
Multi-function Analog Inputs
Multi-function Analog Outputs
MEMOBUS Communications
Motor Overload
Power Loss Ride through
Stall Prevention
Reference Detection
Fault Restart
Load Detection
Hardware Protection
Hunting Prevention Function
High Slip Braking
Monitor Select
Multi-function Selections
Copy Function
Motor Autotuning
No.
U1
U2
U3
L5
L6
L8 n1
L1
L2
L3
L4 n3 o1 o2 o3
H2
H3
H4
H5
E1
E2
F6
H1 d1 d2 d3 d4
C1
C2
C4
C6 b3 b4 b5 b8
A1
A2 b1 b2
T
Page
5-3
5-4
User Parameters Available in Quick Programming Mode
Commonly needed parameters for start-up of the Inverter can be monitored and set in the Quick Programming
Mode. Those parameters are listed in the following tables. All user parameters, including the Quick Programming Parameters can be found in the Advanced Programming Mode as well.
Quick Programming Parameters that are Always Available
Following table shows the parameter that are always available in Quick Programming Mode.
Parameter Number b1-01 b1-02 b1-03 b5-01
C1-01
C1-02 d2-01 d2-02
Name Description
Setting
Range
Factory
Setting
Change during
Operation
Reference source selection
Sets the frequency reference input method.
0: Digital Operator
1: Control circuit terminal (analog input)
2: MEMOBUS communications
3: Option Card
RUN command source selection
Sets the run command input method
0: Digital Operator
1: Control circuit terminal (digital multifunction inputs)
2: MEMOBUS communications
3: Option Card
Stopping method selection
Acceleration time 1
Select stopping method when stop command is input.
0: Deceleration to stop
1: Coast to stop
2: DC braking stop (Stops faster than coast to stop, without regenerative operation.)
3: Coast to stop with timer (Run commands are disregarded during deceleration time.)
PI control mode selection
0: Disabled
1: Enabled
3: PI control enabled (frequency reference + PI output)
When PI controller is enabled additional parameters are available in Quick Programming Mode and default values are changed, refer to the following table.
Sets the acceleration time to accelerate from 0 Hz to the maximum output frequency.
0 to 3
0 to 3
0 to 3
0, 1, 3
0.0 to
6000.0
Deceleration time 1
Frequency reference upper limit
Frequency reference lower limit
Sets the deceleration time to decelerate from the maximum output frequency to
0 Hz.
Sets the frequency reference upper limit as a percentage of the max. output frequency.
Sets the frequency reference lower limit as a percentage of the maximum output frequency.
0.0 to
110.0
0.0 to
110.0
1
1
0
0
10.0 sec.
100.0% No
0.0%
No
No
No
No
Yes
Yes
No
Access
Level
MEMO-
BUS
Register
Q
Q
Q
A
Q
Q
A
A
180H
181H
182H
1A5H
200H
201H
289H
28AH
Digital Operation Display Functions and Levels
Parameter Number
E1-01
E2-01
Name Description
Setting
Range
Factory
Setting
Change during
Operation
Access
Level
MEMO-
BUS
Register
Input voltage setting
Sets the inverter input voltage. This set value will be the basis for the protection functions.
155 to
255
*1
200 V
Motor rated current
Sets the motor rated current in Amps.
This set value becomes the base value for motor protection and torque limit. It is an input data for autotuning.
0.32 to
6.40
*2
1.90 A
*3
No
No
Q
Q
300H
30EH
*1. These are values for a 200 V class Inverter. For 400 V class Inverters the value has to be doubled.
*2. The setting range is from 10% to 200% of the Inverter rated output current.
*3. The factory setting depends on the Inverter capacity (the value for a 200 V Class Inverter for 0.4 kW is given).
Quick Programming Parameters that are Available with Enabled PI Controller
Following list shows the parameters that are available additionally in Quick Programming Mode whenever the
PI controller is enabled. The default settings are also set automatically to settings commonly used with the PI controller.
Parameter Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
H3-08
H3-09
H3-13
Analog input
A2 signal level selection
Analog input
A2 function selection
Terminal A1/
A2 switching
Selects the signal level input at multifunction analog input A2.
0: 0 to +10V (11 bit input)
2: 4 to 20mA (9 bit input)
3: 0 to 20mA (9 bit input)
Selects the multi-function analog input function for terminal A2. Refer to the
of the settings range.
Selects on which terminal the main frequency reference can be input.
0: Use analog input 1 on terminal A1 for main frequency reference.
1: Use analog input 2 on terminal A2 for main frequency reference.
0, 2, 3
0 to 1F
B
*2
0, 1
2
0 b5-31 PI unit selection
Selects the units for the PI controller values (b5-19, U1-24, U1-38).
explanation of the setting range b5-02
Proportional (P) gain
Sets the proportional gain of the PI controller. P control is not performed when set to 0.00
b5-03 Integral (I) time
Sets the integral time of the PI controller.
I control is not performed when set to 0.0.
0 to 11
0.00 to
25.00
0.0 to
360.0
0
1.00
No
No
No
No
Yes
1.0 sec.
Yes
Access
Level
MEMO-
BUS
Register
Q
*1
Q
Q
Q
Q
Q
417H
418H
41CH
1EDH
1A6H
1A7H
*1. Parameter is only moved into Quick Programming Mode when PI controller is enabled, otherwise the parameter is only available in Advanced
Programming Mode.
*2. Setting switched to “B” (PI feedback) only when PI controller is enabled, otherwise default setting is “2” (Auxiliary Reference)
5-5
5-6
User Parameter Tables
Setup Settings: A
Initialize Mode: A1
Parameter
Number
Name Description
A1-00
Language selection for Digital
Operator display
Used to select the language displayed on the LCD or HOA Digital
Operator only.
0: English
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
This parameter is not changed by the initialize operation.
A1-01
Parameter access level
Used to set the parameter access level (set/read.)
0: Monitoring only (Monitoring drive mode and setting A1-01 and A1-04.)
1: Used to select user parameter
(Only parameters set in A2-01 to A2-32 can be read and set.)
2: Advanced
(Parameters can be read and set in both, quick programming mode (Q) and advanced programming (A) mode.)
A1-03 Initialize
A1-04 Password
A1-05 Password setting
Used to initialize the parameters using the specified method.
0: No initializing
1110:Initializes using the user parameters that have been stored before using o2-03 parameter
2220:Initializes using a two-wire sequence. (Initializes to the factory setting.)
3330:Initializes using a three-wire sequence.
Password input when a password has been set in A1-05.
This function write-protects parameters of the initialize mode.
If the password is changed, A1-01 to A1-03 and A2-01 to A2-32 parameters can only be changed after inputting the right password.
Used to set a four digit number as the password.
Usually this parameter is not displayed. When the password (A1-
04) is displayed, hold down the
RESET key and press the Menu key and A1-05 will be displayed.
Setting
Range
0 to 6
0 to 2
0 to
3330
0 to
9999
0 to
9999
Factory
Setting
Change during
Operation
Access
Level
0
2
0
0
0
Yes
Yes
No
No
No
A
A
A
A
A
MEMO-
BUS
Register
100H
103H
Page
–
101H
–
104H
105H
User Parameter Tables
User-set Parameters: A2
Parameter
Number
Name
A2-01 to
A2-32
User-set parameters
Description
Setting
Range
Factory
Setting
Change during
Operation
Access
Level
MEMO-
BUS
Register
Used to select the function for each of the user specified parameters.
User parameters are the only accessible parameters if Parameter
Access Level is set to user parameters (A1-01=1) b1-01 to o3-02
– No A
106H to
125H
Page
5-7
5-8
Application Parameters: b
Operation Mode Selections: b1
Parameter
Number
Name Description b1-01 b1-02 b1-03 b1-04 b1-07 b1-08
Reference source selection
Sets the frequency reference input method.
0: Digital Operator
1: Control circuit terminal (analog inputs)
2: Serial communications (RS
422/485)
3: Option Card (connected on
CN2)
RUN command source selection
Sets the run command input method.
0: Digital Operator
1: Control circuit terminal (digital multifunction inputs)
2: Serial communications (RS
422/485)
3: Option Card (connceted on
CN2)
Stopping method selection
Selects the stopping method when the Run signal is removed
0: Deceleration to stop
1: Coast to stop
2: DC injection to stop
3: Coast to stop with timer (New
Run commands are disregarded while coasting.)
Prohibition of reverse operation
Operation selection after switching to remote mode
Run command selection in programming modes
0: Reverse enabled
1: Reverse disabled
2: Output Phase Rotation (both rotational directions are enabled)
3: Output Phase Rotation with
Reverse disabled.
Selects if the Inverter accepts a
Run command that is already set when the Inverter is switched to
Remote Mode.
0: Preset Run signals are disregarded.
(Run signal has to be cycled once to become active)
1: Preset Run signals become effective immediately after switching to the Remote mode.
Selects if a Run signal will be accepted when the Inverter is in any Programming Mode.
0: Run signal is disregarded.
1: Run signal is accepted (Disabled for b1-02 = 0).
Setting
Range
0 to 3
0 to 3
0 to 3
0 to 3
0 or 1
0 or 1
Factory
Setting
Change during
Operation
Access
Level
1
1
0
0
0
0
No
No
No
No
No
No
Q
Q
Q
A
A
A
MEMO-
BUS
Register
180H
181H
Page
182H
183H
186H
187H
–
–
User Parameter Tables
Parameter
Number
Name Description
Setting
Range b1-11 b1-12 b1-13
RUN delay
Sets the delay time for the execution of the Run signal. During the delay the Digital Operator display will show “ddLY”
HAND frequency reference source selection
*1
Sets the source of frequency reference for HAND operation.
0: Digital Operator
1: Control Circuit Terminal (analog input)
HAND/AUTO switching during
Selects if the Inverter will permit switching between HAND and
AUTO Modes while running.
0: Disabled
1: Enabled b1-14 b1-15
Emergency override speed
Emergency override reference selection
0 to
600
0 or 1
0 or 1
Sets the frequency reference used in emergency override mode when b1-15=0.
Selects the emergency override reference source.
0: Use b1-14 as frequency reference
1: Use AUTO as frequency reference
0.00 to
200.0
0 or 1
Factory
Setting
Change during
Operation
Access
Level
0 sec.
0
0
0.00
Hz
0
No
No
No
No
No
A
A
A
A
A
*1. This parameter is effective only, when the HOA operator JVOP-162 is used.
MEMO-
BUS
Register
1DFH
1E0H
61DH
61AH
61BH
Page
–
DC Injection Braking: b2
Parameter
Number b2-01 b2-02 b2-03 b2-04
Name
DC injection braking start frequency
DC injection braking current
DC injection braking time at start
DC injection braking time at stop
Description
Setting
Range
Factory
Setting
Change during
Operation
Access
Level
Used to set the frequency at which
DC injection braking starts in units of Hz when b1-03 is set to 0 (deceleration to stop).
If b2-01 < E1-09 (Min. output freq.) then DC injection begins at
E1-09.
Sets the DC injection braking current as a percentage of the Inverter rated current.
Sets the time DC injection braking is performed before the Inverter starts to accelerate the motor.
Used to stop a coasting motor before restarting it.
A set value of 0 sec. disables DC injection braking at start.
Sets the time DC injection braking is performed after finished deceleration.
Used to prevent coasting at the end of deceleration.
A set value of 0 sec. disables DC injection braking at stop
0.0 to
10.0
0 to
100
0.00
to
10.00
0.00
to
10.00
0.5 Hz
50%
0.00 sec.
0.50 sec.
No
No
No
No
A
A
A
A
MEMO-
BUS
Register
18AH
18BH
18CH
Page
189H
5-9
5-10
Parameter
Number b2-09
Motor preheat current 1 b2-10
Name
Motor preheat current 2
Description
Setting
Range
Factory
Setting
Change during
Operation
Sets the motor preheat current level in % of the Inverter rated current.
Motor preheat is enabled by an digital input.
Sets the motor preheat current level
2 in % of the Inverter rated current.
Motor preheat 2 is enabled by an digital input.
0 to
100
0%
0 to 10 5%
No
No
Access
Level
A
A
MEMO-
BUS
Register
1E1H
61CH
Page
Speed Search: b3
Parameter
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
Access
Level
MEMO-
BUS
Register
Page
Enables/disables the speed search function and sets the speed search method.
0:Disabled, speed calculation
1: Enabled, speed calculation
2: Disabled, current detection
3: Enabled, current detection b3-01
Speed search selection (current detection or speed calculation)
Speed Calculation:
When the search is started, the motor speed is calculated and acceleration/deceleration is performed from the calculated speed to the specified frequency (motor direction is also searched).
0 to 3 2 No A 191H
b3-02 b3-03
Current Detection:
The speed search is started from the frequency when power was momentarily lost and the maximum frequency, and the speed is detected at the search current level.
Speed search operating current
(current detection)
Speed search deceleration time
(current detection)
Sets the speed search operation current as a percentage, taking the
Inverter rated current as 100%.
Usually not necessary to set. When restarting is not possible with the factory settings, reduce the value.
Sets the output frequency deceleration time during speed search in 1second units.
Sets the time for deceleration from the maximum output frequency to the minimum output frequency.
b3-05
Speed search wait time (current detection or speed calculation)
When a speed search is performed after recovering from a momentary power loss, the search operation is delayed for the time set here.
If e.g. a contactor is used at the output side of the inverter set this parameter to the contactor delay time or more.
0 to
200
0.1 to
10.0
2.0 sec.
No
0.0 to
20.0
120%
0.2 sec.
No
No
A
A
A
192H
193H
195H
User Parameter Tables
Parameter
Number
Name b3-14
Bi-directional speed search selection
Description
Disables or enables the bi-directional capabilities of the speed search function.
0: Disabled
1: Enabled
Setting
Range
Factory
Setting
Change during
Operation
Access
Level
MEMO-
BUS
Register
Page
0 or 1 1 No A 19EH
Timer Function: b4
Parameter
Number
Name b4-01
Timer function
ON-delay time b4-02
Timer function
OFF-delay time
Description
Setting
Range
Factory
Setting
Change during
Operation
Sets the timer function output ONdelay time (dead time) for the timer function input.
Enabled when the timer function is set in H1 and H2.
0.0 to
3000.0
Sets the timer function output
OFF-delay time (dead band) for the timer function input.
Enabled when a timer function is set in H1 and H2-
0.0 to
3000.0
0.0 sec.
No
0.0 sec.
No
Access
Level
A
A
MEMO-
BUS
Register
1A3H
1A4H
Page
PI Control: b5
Parameter
Number b5-01 b5-02 b5-03 b5-04 b5-06 b5-07 b5-08
PI control mode selection
Proportional (P) gain
PI delay time constant b5-09
PI output characteristics selection b5-10
Name
Integral (I) time
Integral (I) limit
PI limit
PI offset
PI output gain
Description
Setting
Range
Factory
Setting
Change during
Operation
0: Disabled
1: Enabled
3: PI control enabled (frequency reference + PI output)
Sets the proportional gain of the PI controller. P control is not performed when set 0.00.
Sets the integral time of the PI controller. I control is not performed when set to 0.0 sec.
0.00
to
25.00
0.0 to
360.0
Sets the I control limit as a percentage of the maximum output frequency.
Sets the limit after PI control as a percentage of the maximum output frequency.
Sets the offset after PI control as a percentage of the maximum output frequency.
Sets the time constant for low pass filter of the PI control output.
Usually not necessary to set.
Selects forward/reverse direction for PI output.
0: PI output is forward.
1: PI output is reversed.
0.0 to
100.0
0.0 to
100.0
-100.0
to
+100.0
0.00 to
10.00
0 or 1
100.0% Yes
100.0% Yes
0.0%
0.00 sec.
0
Yes
Yes
No
Sets output gain.
0, 1, 3
0.0 to
25.0
0
1.00
1.0 sec.
1.0
No
Yes
Yes
No
Access
Level
A
Q
A
*1
A
A
A
A
A
A
MEMO-
BUS
Register
Page
1A5H
1A6H
1A7H
1A8H
1AAH
1ABH
1ACH
1ADH
1AEH
5-11
5-12
Parameter
Number
Name Description b5-11 b5-12 b5-13 b5-14 b5-15 b5-16 b5-17 b5-18
PI reverse output selection
Selection of PI feedback signal loss detection
PI feedback loss detection level
0: Limit to 0 when PI output is negative.
1: Reverses when PI output is negative.
Limit to 0 is also active when reverse operation disabled is selected by b1-04.
0: No detection of PI feedback loss.
1: Detection of PI feedback loss.
Operation continues during detection, the fault relay is not operated.
2: Detection of PI feedback loss.
The motor coasts to stop at detection, and the fault relay operates.
Sets the PI feedback loss detection level as percentage using the maximum output frequency as 100%.
PI feedback loss detection time
Sleep function operation level
Sleep operation delay time
Accel/decel time for PI reference
Sets the PI feedback loss detection time.
Sets the sleep function start level as a frequency.
Sets the delay time until the sleep function starts.
Sets the accel/decel time for the PI
Softstarter (SFS).
PI Setpoint Selection
0: Disabled
1: Enabled
Setting
Range
0 or 1
0 to 2
0 to
100
0 to 1
Factory
Setting
Change during
Operation
Access
Level
0
0
0%
0
No
No
No
0.0 to
25.5
0.0 to
200.0
0.0 to
25.5
0.0 to
25.5
1.0 sec.
No
0.0 Hz No
0.0 sec.
No
0.0 sec.
No
No
A
A
A
A
A
A
A
A b5-19 PI Setpoint PI target value
0.00 to
100.00
%
0 Yes A b5-20
PI Setpoint Scaling
Sets the unit for b5-19, U1-38 and
U1-24
0: 0.01 Hz
1: 0.01% (the maximum output frequency E1-04 is taken as
100%.
2 – 39: rpm, set value is equal to motor poles
40 – 39999: User desired display
0 to
39999
1 No A
MEMO-
BUS
Register
1AFH
1B0H
1B1H
1B2H
1B3H
1B4H
1B5H
1DCH
1DDH
1E2H
Page
Sets the display value for 100 %.
Sets the number of decimal digits.
b5-21
Sleep Function
Selection
Sets the operation method of the PI sleep function
0: PI Setpoint
1: SFS Input
2: Snooze
0 to 2 1 No A 1E3H
User Parameter Tables
Parameter
Number
Name Description
Setting
Range b5-22 b5-23
Snooze Level
Snooze Delay
Time b5-24 Wake-Up Level b5-25 Setpoint Boost
Sets the frequency level at which the snooze operation starts as percentage of the max. output frequency.
Sets a delay timer for the snooze function
Sets the feedback level at which the inverter wakes up from snooze operation.
Sets the PI setpoint boost when the snooze mode is activated. If it is reached once the output will be switched off. The value is set as percentage of the PI setpoint.
Sets the maximum time the boost operation is performed.
b5-26
Maximum Boost
Time b5-27 b5-28
Snooze feedback
PI Feedback
Square Root
Operation
PI Snooze function will only be activated when the feedback value is above this parameter setting.
The value is set as percentage of the PI setpoint.
Enables or disables the square root operation for the PI feedback value.
0: Disabled
1: Enabled b5-29
PI Feedback
Square Root Gain
Sets the gain for the feedback when square root operation is enabled.
b5-30
PI Output Monitor Square Root b5-31
PI unit selection
*2
Selects whether the PI output monitor is shown as square root value or not.
0: Disable
1: Enable
Selects the units for the PI controller values (b5-19, U1-24, U1-38).
the explanation of the setting range.
0 to
100
0 to
3600
0 to
100
0 to
100
0 to
3600
0 to
100
0 or 1
0 to
2.00
0 or 1
0 to 11
Factory
Setting
Change during
Operation
Access
Level
0%
0 sec.
0%
0%
0 sec.
60%
0
1.00
0
0
Yes
No
No
No
No
No
No
No
No
No
A
A
A
A
A
A
A
A
A
A
MEMO-
BUS
Register
Page
1E4H
1E5H
1E6H
1E7H
1E8H
1E9H
1EAH
1EBH
1ECH
1EDH
*1. Parameter is moved into Quick Programming Mode when PI controller is enabled, otherwise the parameter is available only in Advanced Programming Mode.
*2. Parameter function is only valid if a Digital Operator with LCD clear text display is used (LCD or HOA Digital Operator)
b5-31 Settings
Setting
Value
0
1
4
5
2
3
6
7
Function
WC: Inch of water column
PSI: lb/square inch
GPM: Gallons per minute
F: Degree Fahrenheit
CFM: Cubic feet per minute
CMH: Cubic meter per hour
LPH: Liters per hour
LPS: Liters per second
Displayed Unit
WC
PSI
GPM
F
CFM
CMH
LPH
LPS
5-13
5-14
Setting
Value
8
9
10
11
Function
Bar: Bar
Pa: Pascal
C: Degree Celsius
Mtr: Meters
Displayed Unit
Bar
Pa
C
Mtr
Energy Saving: b8
Parameter
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation b8-01 b8-04
Energy-saving mode selection
Energy-saving coefficient
Enables or disables the energy-saving function.
0: Disable
1: Enable
Sets the energy-saving coefficient.
Adjust the value in 5% steps until the output power becomes minimal.
0 or 1
0.0 to
655.00
b8-05
Power detection filter time constant
Sets the time constant for output power detection.
b8-06
Search operation voltage limiter
Sets the limit value of the voltage control range during search operation.
Set to 0 to disable the search operation. 100% is the motor rated voltage.
0 to
2000
0 to
100
0
*1
20msec No
0%
No
No
No
Access
Level
A
A
A
A
*1. The factory setting depends on the Inverter capacity.
MEMO-
BUS
Register
Page
1CCH
1CFH
1D0H
1D1H
User Parameter Tables
Tuning Parameters: C
Acceleration/Deceleration: C1
Parameter
Number
Name Description
Setting
Range
C1-01
C1-02
C1-03
C1-04
C1-09
Acceleration time 1
Deceleration time 1
Acceleration time 2
Deceleration time 2
Emergency stop time
C1-11
Accel/decel time switching frequency
Sets the acceleration time to accelerate from 0 Hz to the maximum output frequency.
Sets the deceleration time to decelerate from the maximum output frequency to 0 Hz.
Sets the acceleration time when the multi-function input “accel/decel time 1” is set to ON.
Sets the deceleration time when the multi-function input “accel/decel time 1” is set to ON.
0.0 to
6000.0
Sets the deceleration time when the multi-function input “Emergency
(fast) Stop” is set to ON.
Sets the frequency for automatic acceleration/deceleration switching.
If the output frequency is below the set frequency: Accel/decel time 2
If the output frequency is above the set frequency: Accel/decel time 1
The multi-function input “accel/ decel time 1” has priority.
0.0 to
200.0
Factory
Setting
Change during
Operation
Access
Level
MEMO-
BUS Register
10.0 sec.
Yes
Yes
Yes
Yes
No
0.0 Hz No
Q
Q
A
A
A
A
200H
201H
202H
203H
208H
20AH
Page
S-Curve Acceleration/Deceleration: C2
Parameter
Number
Name Description
C2-01
S-curve characteristic time at acceleration start
When the S-curve characteristic time is set, the accel time will increase by only half of the S-curve characteristic times at start and end.
Run command
ON
OFF
Output frequency
C2-02
Setting
Range
Factory
Setting
Change during
Operation
Access
Level
0.20
sec.
No A
C2-01
Time
0.00 to
2.50
MEMO-
BUS
Register
Page
20BH
C2-02
S-curve characteristic time at acceleration end
T accel
=
C2-01
C1-01
2
+ +
2
The S-Curve characteristic times at start and end of deceleration are fixed to 0.2 sec. and can not be changed.
0.20
sec.
No A 20CH
5-15
5-16
Torque Compensation: C4
Parameter
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
C4-01
C4-02
Torque compensation gain
Torque compensation delay time constant
Sets the torque compensation gain.
Usually setting is not necessary.
Adjust under the following circumstances:
• When the motor cable is long increase the set value.
• When the motor capacity is smaller than the Inverter capacity (Max. applicable motor capacity), increase the set values.
• When the motor speed is oscillating, decrease the set values.
Adjust the torque compensation gain so that at minimum speed the output current does not exceed the
Inverter rated output current.
The torque compensation delay time is set in ms units.
Usually setting is not necessary.
Adjust under the following circumstances:
• When the motor is oscillating, increase the set values.
• When the responsiveness of the motor is low, decrease the set values.
0.00 to
2.50
0 to
10000
1.00
Yes
200 ms No
Access
Level
A
A
MEMO-
BUS
Register
215H
216H
Page
User Parameter Tables
Carrier Frequency: C6
Parameter
Number
Name
C6-01
Normal duty selection
C6-02
Carrier frequency selection
Description
1: Normal Duty 1
2: Normal Duty 2
Selects the carrier frequency.
Select F to enable detailed settings using parameters C6-03 to C6-05.
Setting
Range
Factory
Setting
Change during
Operation
Access
Level
1 or 2 1 No A
MEMO-
BUS
Register
223H
Page
0 to F
6
*1
No A 224H
C6-03
Carrier frequency upper limit
Sets the carrier frequency upper limit and lower limit in kHz units.
The carrier frequency gain is set as follows:
2.0 to
15.0
*2 *3
15.0 kHz
C6-04
Carrier frequency lower limit
C6-05
Carrier frequency proportional gain
Carrier frequency
Output frequency x (C6-05) x K
Output frequency
(Max. output frequency)
K is a coefficient that depends on the setting of C6-03.
C6-03
≥ 10.0 kHz: K = 3
10.0 kHz > C6-03
≥ 5.0 kHz: K = 2
5.0 kHz > C6-03: K = 1
0.4 to
15.0
00 to
99
15.0 kHz
00
No
No
No
A 225H
A
A
226H
227H
*1. The factory setting depends on the Inverter capacity and the protection class.
*2. The setting range depends on the Inverter capacity.
*3. This parameter can only be set when C6-02 is set to F.
5-17
5-18
Reference Parameters: d
Preset Reference: d1
Parameter
Number
Name d1-01
Frequency reference 1 d1-02
Frequency reference 2 d1-03
Frequency reference 3 d1-04
Frequency reference 4 d1-17
Jog frequency reference
Description
Sets the frequency reference.
Setting
Range
Factory
Setting
Change during
Operation
0.00
Hz
Yes
Access
Level
A
Sets the frequency reference when multi-step speed command 1 is ON for a multi-function input.
Sets the frequency reference when multi-step speed command 2 is ON for a multi-function input.
Sets the frequency reference when multi-step speed commands 1 and
2 are ON for multi-function inputs.
Sets the frequency reference when the jog frequency reference selection, FJOG command, or RJOG command is ON.
0 to
FMAX
0.00
Hz
0.00
Hz
0.00
Hz
6.00
Hz
Yes
Yes
Yes
Yes
A
A
A
A
MEMO-
BUS
Register
280H
281H
282H
283H
292H
Note:The unit is set in o1-03 (frequency units of reference setting and monitor, default: 0.01 Hz).
Page
Reference Limits: d2
Parameter
Number
Name Description d2-01 d2-02
Frequency reference upper limit
Frequency reference lower limit d2-03
Master speed reference lower limit
Sets the frequency reference upper limit as a percentage of the max. output frequency.
Sets the frequency reference lower limit as a percentage of the maximum output frequency.
Sets the master speed reference lower limit as a percentage of the max. output frequency.
Setting
Range
Factory
Setting
Change during
Operation
Access
Level
0.0 to
110.0
0.0 to
110.0
0.0 to
110.0
100.0%
0.0%
0.0%
No
No
No
Q
Q
A
MEMO-
BUS
Register
289H
28AH
293H
Page
Note:The PI Sleep Function is also available and can be used without enabled PI controller. It can be used to let the inverter switch off automatically when a minimum output frequency (set in b5-15) has been output for a time longer than b5-16. Refer also to page
User Parameter Tables
Jump Frequencies: d3
Parameter
Number
Name Description d3-01 Jump frequency 1 d3-02 Jump frequency 2 d3-03 Jump frequency 3
Sets the jump (resonance) frequencies in Hz.
The function is disabled when the jump frequency is set to 0 Hz.
Always ensure the following setting order: d3-01
≥ d3-02 ≥ d3-03
Operation in the jump frequency range is prohibited but during acceleration and deceleration, the speed changes smoothly without jumping over the set frequencies d3-04
Jump frequency width
Sets the jump frequency bandwidth in Hz.
The jump frequency range will be the jump frequency ± d3-04.
Setting
Range
0.0 to
200.0
0.0 to
20.0
Factory
Setting
Change during
Operation
Access
Level
0.0 Hz No
0.0 Hz No
0.0 Hz No
1.0 Hz No
A
A
A
A
MEMO-
BUS
Register
Page
294H
295H
296H
297H
Reference Frequency Hold: d4
Parameter
Number
Name d4-01
Frequency reference hold function selection d4-02
Trim Control
Level
Description
Setting
Range
Factory
Setting
Change during
Operation
Access
Level
Sets whether or not frequency reference value on hold will be recorded.
0: Disabled (when operation is stopped or the power is turned on again the frequency reference is set to 0.)
1: Enabled (when operation is stopped or the power is turned on again the inverter starts at the previous hold frequency.)
This function is available when the multi-function inputs “Accel/Decel
Ramp Hold” or “UP/DOWN” commands are set.
Sets the frequency to be added to or subtracted from the analog frequency reference as a percentage of the max. output frequency.
Enabled when the Trim control increase command or Trim control decrease command is set for a multi-function input.
0 or 1
0 to
100
0
10%
No
No
A
A
MEMO-
BUS
Register
298H
Page
299H
5-19
5-20
Motor Parameters: E
V/f Pattern: E1
Parameter
Number
E1-03
V/f pattern selection
Name
E1-01
Input voltage setting
Description
Sets the Inverter input voltage.
This setting is used as a reference value for protection functions.
Setting
Range
Factory
Setting
Change during
Operation
155 to
255
*1
200 V
No
0 to E: Select from the 15 preset
F: patterns.
Custom user-set pattern
(Applicable for setting of E1-
04 to E1-10.)
FF: Custom user-set pattern without voltage and frequency limits
0 to F,
FF
F No
E1-04
Max. output frequency
(FMAX)
Output Voltage (V)
0.0 to
200.0
50.0
Hz
No
E1-05
Max. output voltage (VMAX)
0.0 to
255.0
200.0
V
No
Access
Level
Q
A
A
A
MEMO-
BUS
Register
300H
Page
302H
303H
304H
E1-06
Base frequency
(FA)
E1-07
E1-08
E1-09
Mid. output frequency (FB)
Mid. output frequency voltage
(VB)
Min. output frequency (FMIN)
E1-10
Min. output frequency voltage
(VMIN)
Frequency (Hz)
0.0 to
200.0
50.0
Hz
To set V/f characteristics in a straight line, set the same values for E1-07 and
E1-09. In this case, the setting for E1-
08 will be disregarded.
Always ensure that the four frequencies are set in the following manner:
E1-04 (FMAX)
≥ E1-06 (FA) > E1-07
(FB)
≥ E1-09 (FMIN)
0.0 to
15.0 V
0.0 to
200.0
0.0 to
255.0
1.2 Hz
9.0 V
No
No
No
E1-11
Mid. output frequency 2
E1-12
Mid. output frequency voltage 2
Set only to fine-adjust V/f for the output range. Normally, this setting is not required.
0.0 to
200.0
0.0 to
255.0
0.0 Hz
*2
0.0 V
No
0.0 to
200.0
2.5 Hz No
No
No
E1-13
Base voltage
(VBASE)
Sets the output voltage of the base frequency (E1-06).
0.0 to
255.0
0.0 V
No
A
A
A
A
A
A
A
A
305H
306H
307H
308H
309H
30AH
30BH
30CH
*1. Values for 200 V class Inverters are shown. For a 400 V class Inverter the values have to be doubled.
*2. Parameters E1-11 and E1-12 are disabled when set to 0.0
User Parameter Tables
Motor Setup: E2
Parameter
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
E2-01
E2-03
E2-05
Motor rated current
Sets the motor rated current.
This set value will become the reference value for motor protection and torque limits.
This parameter is an input data for autotuning.
Motor no-load current
Motor line-to-line resistance
Sets the motor no-load current.
This parameter is automatically set during autotuning.
Sets the motor phase-to-phase resistance in
Ω units.
This parameter is automatically set during autotuning.
0.32 to
6.40
*1
0.00 to
1.89
*3
0.000
to
65.000
1.90 A
*2
1.2 A
9.842
Ω
No
No
No
Access
Level
Q
A
A
*1. The setting range is 10% to 200% of the Inverter rated output current. The value for a 200 V class Inverter of 0.4 kW is given.
*2. The factory setting depends on the Inverter capacity. The value for a 200 V class Inverter of 0.4 kW is given
*3. The setting range is 0.00 A to (E2-01 - 0.01 A).
MEMO-
BUS
Register
30EH
Page
310H
312H
5-21
5-22
Option Parameters: F
Communications Option Cards: F6
Parameter
Number
Name Description
F6-01
F6-02
F6-03
F6-05
Operation selection after communications error
Set the stopping method for communications errors.
0: Deceleration to stop using the deceleration time in C1-02
1: Coast to stop
2: Emergency stop using the deceleration time in C1-09
3: Continue operation
Option card external fault detection selection
0: Always detected
1: Detected only during operation
Option card external fault stopping method
Current scaling via communication option card
0: Deceleration to stop using the deceleration time in C1-02
1: Coast to stop
2: Emergency stop using the deceleration time in C1-09
3: Continue operation
Sets the unit of the current monitor
0: Ampere
1: 100% 8192
Setting
Range
Factory
Setting
Change during
Operation
Access
Level
MEMO-
BUS
Register
0 to 3
0 or 1
0 to 3
0 or 1
1
0
1
0
No
No
No
No
A
A
A
A
3A2H
3A3H
3A4H
3A6H
Page
–
–
–
–
User Parameter Tables
Terminal Function Parameters: H
Multi-function Digital Inputs: H1
Parameter
Number
Name Description
H1-01
Terminal S3 function selection
Multi-function digital input 1
H1-02
Terminal S4 function selection
Multi-function digital input 2
H1-03
Terminal S5 function selection
Multi-function digital input 3
H1-04
Terminal S6 function selection
Multi-function digital input 4
H1-05
Terminal S7 function selection
Multi-function digital input 5
Setting
Range
Factory
Setting
Change during
Operation
Access
Level
MEMO-
BUS
Register
0 to 82
0 to 82
0 to 82
0 to 82
0 to 82
*1. The values in parentheses indicate initial values when initialized in 3-wire-sequence.
24
14
3 (0)
4 (3)
6 (4)
*1
No
No
No
No
No
A
A
A
A
A
400H
401H
402H
403H
404H
Page
–
–
–
–
–
13
14
15
17
F
10
11
12
A
C
8
9
4
6
7
Multi-function Digital Input Functions
Setting
Value
0
1
2
3
18
19
1B
1C
1D
1E
Function
3-wire sequence (Forward/Reverse Run command)
Local/Remote selection (ON: Operator, OFF: Parameter b1-01/b1-02 setting)
Operation Source Option Card/Inverter selection (ON: Parameter b1-01/b1-02 setting)
Multi-step speed reference 1
When H3-09 is set to 2, this function is combined with the master/auxiliary speed switch.
Multi-step speed reference 2
Jog frequency command (higher priority than multi-step speed reference)
Acceleration/Deceleration time selection 1
External baseblock NO (NO contact: Baseblock at ON)
External baseblock NC (NC contact: Baseblock at OFF)
Acceleration/deceleration ramp hold (ON: Acceleration/deceleration stopped, frequency is hold)
Multi-function analog input A2 enable (ON: Enable)
Terminal not used
UP command (Always set with the DOWN command)
DOWN command (Always set with the UP command)
FJOG command (ON: Forward run at jog frequency d1-17)
RJOG command (ON: Reverse run at jog frequency d1-17)
Fault reset (Reset when turned ON)
Emergency stop (NO: Deceleration to stop with deceleration time set in C1-09 when ON.)
Emergency stop (NC: Deceleration to stop with deceleration time set in C1-09 when OFF)
Timer function input
(times are set in b4-01 and b4-02 and the timer function outputs are set in H2.)
PI control disable (ON: PI control disabled)
Parameters write enable
(ON: All parameters can be set. OFF: All parameters are write protected.)
Trim control increase (ON: d4-02 frequency is added to analog frequency reference.)
Trim control decrease (ON: d4-02 frequency is subtracted from analog frequency reference.)
Analog frequency reference sample/hold (ON: reference is sampled and hold)
–
Page
5-23
5-24
Setting
Value
20 to 2F
30
6B
6C
6D*
6E*
67
68
69
6A
70
80
81
82
60
61
62
64
31
34
35
36
PI control integral hold (ON: integral is hold)
PI soft starter disable (ON: disabled)
PI input characteristics switch
Operation Source Option/Inverter selection 2 (ON: option card)
Motor preheat command 1 (ON: Performs motor preheat)
External speed search command 1 (ON: Speed search from maximum output frequency)
External speed search command 2 (ON: Speed search from set frequency)
External speed search command 3
Communications test mode
High Slip braking (HSB)
Jog Frequency 2
Drive enable (ON: Drive enabled)
Operation Source Communication/Inverter selection (ON: RS-422/485 port)
Operation Source Communication/Inverter selection 2 (ON: inverter settings)
AUTO mode selection (ON: AUTO mode active)
HAND mode selection (ON: HAND mode active)
Bypass Drive Enable (ON: Inverter enabled)
Function
External fault
Input mode: NO contact/NC contact, detection mode: normal/during operation
PI control integral reset
(ON: integral reset and hold as long as input is ON)
Motor Preheat 2 (ON: motor performs preheat 2)
Emergency Override Forward (ON: Inverter performs emergency override in forward direction)
Emergency Override Reverse (ON: Inverter performs emergency override in reverse direction)
* This setting is effective only, if the HOA operator JVOP-162 is used.
Multi-function Digital Outputs: H2
Parameter
Number
Name Description
H2-01
Terminal M1-M2 function selection
Multi-function digital output 1
H2-02
Terminal M3-M4 function selection
Multi-function digital output 2
Page
Setting
Range
Factory
Setting
Change during
Operation
Access
Level
MEMO-
BUS
Register
0 to 3D 0 No A 40BH
Page
–
0 to 3D 1 No A 40CH –
Multi-function Digital Output Functions
Setting
Value
0
1
2
3
4
5
Function
During run 1 (ON: run command is ON or voltage is being output)
Zero speed f ref
/f out
agree 1 (detection width L4-02 is used.) f ref
/f set
agree 1
(ON: Output frequency = ±L4-01, with detection width L4-02 used and during frequency agree)
Frequency detection 1
(ON: +L4-01
≥ output frequency ≥ -L4-01, detection width L4-02 used)
Frequency detection 2
(ON: Output frequency
≥ +L4-01 or output frequency ≤ -L4-01, detection width L4-02 used)
Page
User Parameter Tables
12
17
1A
1E
F
10
11
1F
20
38
39
3A
3B
3D
Setting
Value
6
A
B
C
7
8
9
E
Function
Inverter operation ready
READY: After start-up or no faults
During DC bus undervoltage (UV) detection
During baseblock (NO contact, ON: during baseblock)
Frequency reference source selection (ON: Frequency reference from Operator)
Run command source selection status (ON: Run command from Operator)
Load detection NO (NO contact, ON: overload/loss of load detected)
Loss of frequency reference (Effective when 1 is set for L4-05)
Fault (ON: Digital Operator communications error or fault other than CPF00 and CPF01 has occurred.)
Not used. (Set when the terminal is not used.)
Minor Fault (Alarm) (ON: Alarm displayed)
Fault reset command active
Timer function output
Load Detection NC (NC contact, OFF: overload/loss of load detected)
Reverse direction
Restart enabled (ON: Restart enabled)
During motor overload (OL1, including OH3) pre-alarm
(ON: 90% or more of the detection level)
OH pre-alarm (temperature reached L8-02)
Drive enabled
Drive waiting (start delay time b1-11 is active)
During OH and reduced Frequency
RUN command from option card/communications
Cooling fan fault (ON: internal cooling fan error)
Page
-
Analog Inputs: H3
Parameter Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
H3-02 Terminal A1 gain
Sets the frequency reference value when 10 V is input as a percentage of the maximum output frequency set in E1-04.
H3-03
H3-08
Terminal A1 bias
Sets the frequency reference value when 0 V is input as a percentage of the maximum output frequency set in E1-04.
Analog input A2 signal level selection
Selects the signal level input at multi-function analog input A2.
0: 0 to +10V (11 bit).
2: 4 to 20 mA (9-bit input).
3: 0 to 20 mA (9-bit input)
H3-09
Analog input A2 function selection.
0.0 to
1000.0
-100.0 to
+100.0
0, 2, 3
Selects the multi-function analog input function for terminal A2.
Refer to the table
for the explanation of the setting range.
0 to 1F
100.0% Yes
0.0%
2
2
*2
Yes
No
No
Access
Level
A
A
A
*1
A
MEMO-
BUS
Register
411H
Page
412H
417H
418H
5-25
5-26
Parameter Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
H3-10 Terminal A2 gain
Sets the value of the function signal when 10 V (20 mA) is input as a percentage of the maximum value.
H3-11
H3-12
H3-13
Terminal A2 bias
Analog input filter time constant
Terminal A1/A2 switching
Sets input filter time constant for the two analog input terminals
(A1 and A2).
Effective for noise suppression etc.
Selects on which terminal the main frequency reference can be input.
0: Use analog input 1 on terminal
A1 for main frequency reference.
1: Use analog input 2 on terminal
A2 for main frequency reference.
0.0 to
1000.0
Sets the value of the function signal when 0 V (0/4 mA) is input as a percentage of the maximum value.
-100.0
to
+100.0
0.00 to
2.00
0 or 1
100.0% Yes
0.0%
0.30
sec.
0
Yes
No
No
Access
Level
A
A
A
MEMO-
BUS
Register
419H
41AH
41BH
41CH
Page
*1. Parameter is also available in Quick Programming Mode when PI controller is enabled, otherwise parameter is only available in Advanced Programming Mode.
*2. Setting switched to “B” when PI controller is enabled
H3-09 Settings
Setting
Value
0
2
B
D
E
16
1F
Function
Frequency bias
Auxiliary frequency reference (is used as frequency reference 2)
PI feedback
Frequency Bias 2
Motor temperature input
PI differential input
Analog input not used.
Contents (100%)
Maximum output frequency
Maximum output frequency
Maximum output frequency
Maximum output frequency
–
Maximum output frequency
–
Page
–
User Parameter Tables
Multi-function Analog Outputs: H4
Parameter
Number
Name Description
Setting
Range
H4-01
H4-02
Terminal FM monitor selection
Terminal FM gain
Sets the number of the monitor item to be output (U1) at terminal FM.
Sets the analog output FM gain.
Sets the percentage of the monitor value that is equal to 10 V output at terminal FM.
Note that the maximum output voltage is 10 V.
H4-03 Terminal FM bias
H4-04
Terminal AM monitor selection
Sets the analog output FM bias.
Sets the percentage of the monitor item that is equal to 0 V output at terminal FM.
The maximum output from the terminal is 10 V.
Sets the number of the monitor item to be output (U1) at terminal FM.
1 to 53
0 to
1000.0
%
-110.0 to
+110.0
%
1 to 53
H4-05
Terminal AM gain
Sets the analog output AM gain.
Sets the percentage of the monitor value that is equal to 10V output at terminal AM.
Note that the maximum output voltage is 10V.
0 to
1000.0
%
H4-06
H4-07
Terminal AM bias
Sets the analog output AM bias.
Sets the percentage of the monitor item that is equal to 0 V output at terminal AM.
The maximum output from the terminal is 10 V.
Terminal FM signal level selection
Sets the signal output level for multi-function output 1 (terminal
FM)
0: 0 to +10 V output
2: 4 – 20 mA
*1
-110.0 to
+110.0
%
0 or 2
H4-08
Terminal AM signal level selection
Sets the signal output level for multi-function output 2 (terminal
AM)
0: 0 to +10 V output
0 or 2
Factory
Setting
Change during
Operation
Access
Level
2
100%
0.0%
8
0.0%
0
0
No
Yes
Yes
No
50.0% Yes
Yes
No
No
A
A
A
A
A
A
A
A
*1. An analog output signal of 4 - 20 mA requires an optional terminal board (ETC618121) for current output
MEMO-
BUS
Register
Page
41DH
41EH
41FH
420H
421H
422H
423H
424H
5-27
5-28
MEMOBUS Communications: H5
Parameter
Number
Name
H5-01 Station address
Description
Sets the Inverter's node address.
Setting
Range
Factory
Setting
Change during
Operation
Access
Level
0 to 20
*1
1F No A
MEMO-
BUS
Register
425H
Page
H5-02
Communications speed selection
Sets the baud rate for MEMOBUS communications.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
H5-03
H5-04
H5-05
Communications parity selection
Sets the parity for MEMOBUS communications.
0: No parity
1: Even parity
2: Odd parity
Stopping method after communications error
Sets the stopping method for communications errors.
0: Deceleration to stop using the deceleration time in C1-02
1: Coast to stop
2: Emergency stop using the deceleration time in C1-09
3: Continue operation
Communications error detection selection
Sets whether or not a communications time out is to be detected as a communications error.
0: Not detected
1: Detect
H5-06 Send wait time
H5-07
RTS control ON/
OFF
Sets the time the Inverter waits until a response is sent to the Master.
Enables or disables RTS control.
0: Disabled (RTS is always ON)
1: Enabled (RTS turns ON only when sending)
H5-08
Communication
Selection
Selects the Protocol for the Communication
0: Memobus
1: N2 (Metasys)
H5-09 CE detection time
Sets the time before CE error
(Communication error) is detected when MEMOBUS communication is used.
0 to 4
0 to 2
0 to 3
0 or 1
5 to 65 5 msec No
0 or 1
0, 1
0.0 to
10.0 sec
3
0
3
1
1
0
2.0 sec
No
No
No
No
No
No
No
*1. Set H5-01 to 0 to disable Inverter responses to MEMOBUS communications
A
A
A
A
A
A
A
A
426H
427H
428H
429H
42AH
42BH
434H
435H
User Parameter Tables
Protection Function Parameters: L
Motor Overload: L1
Parameter
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
L1-01
Motor protection selection
L1-02
Motor protection time constant
L1-03
L1-04
L1-05
Alarm operation selection during motor overheating
Motor overheating operation selection
Motor temperature input filter time constant
Sets whether the motor overload function is enabled or disabled at electric thermal overload relay.
0: Disabled
1: General-purpose motor protection (fan cooled motor)
2: Inverter motor protection
(externally cooled motor)
3:Vector motor protection
When several motors are connected to one Inverter, set to 0 and ensure that each motor is installed with a protection device.
Sets the electric thermal detection time in units of minutes.
Usually changing this setting is not necessary.
The factory setting is 150% overload for one minute.
When the motor's overload capability is known, also set the overload resistance protection time for when the motor is hot started.
Selects the operation when the input motor temperature (thermistor) input exceeds the alarm detection level (1.17 V) (H3-09 must be set to E).
0: Decelerate to stop
1: Coast to stop
2: Emergency stop using the deceleration time in C1-09.
3: Continue operation (oH3 on the
Operator display flashes).
0 or 3
0.1 to
5.0
0 to 3
Selects the operation when the motor temperature (thermistor) input exceeds the overheating detection level (2.34 V) (H3-09 must be set to E).
0: Decelerate to stop
1: Coast to stop
2: Emergency stop using the deceleration time in C1-09.
Sets the delay time constant for the motor temperature (thermistor) input (H3-09=E) in seconds.
0 to 2
0.00 to
10.00
1
3
1
0.20 sec.
No
1.0 min No
No
No
No
Access
Level
A
A
A
A
A
MEMO-
BUS
Register
Page
480H
481H
482H
483H
484H
5-29
5-30
Power Loss Ride Through: L2
Parameter
Number
Name Description
L2-01
L2-02
L2-03
Momentary power loss detection
Momentary power loss ride through time
Min. baseblock time
L2-04
Voltage recovery time
L2-05
Undervoltage detection level
0: Disabled (DC bus undervoltage
(UV1) detection)
1: Enabled (Restarted when the power returns within the time set in L2-02. When L2-02 is exceeded, DC bus undervoltage is detected.)
2: Enabled while CPU is operating. (Restarts when power returns during control operations. Does not detect DC bus undervoltage.)
Ride through time, when Momentary Power Loss Selection (L2-01) is set to 1.
Sets the Inverter's minimum baseblock time, when the Inverter is restarted after power loss ridethrough.
Set the time to approximately 0.7 times the motor time constant.
If an overcurrent or overvoltage occurs when starting a speed search or DC injection braking, increase the set values.
Sets the time required to return the
Inverter output voltage from 0V to normal voltage at the completion of a speed search.
Sets the main circuit undervoltage
(UV) detection level (main circuit
DC voltage).
Usually changing this setting is not necessary.
Setting
Range
0 to 2
0 to
25.5
0.1 to
5.0
0.0 to
5.0
150 to
210
Factory
Setting
Change during
Operation
Access
Level
0
0.1 sec.
*1
0.1 sec.
0.3 sec.
190
VDC
*2
No
No
No
No
No
A
A
A
A
A
*1. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
*2. These are values for a 200 V class Inverter. Values for a 400 V class Inverter are double
MEMO-
BUS
Register
487H
488H
Page
485H
486H
489H
User Parameter Tables
Stall Prevention: L3
Parameter
Number
Name Description
L3-01
L3-02
Stall prevention level during accel
L3-04
L3-05
L3-06
Stall prevention selection during accel
Stall prevention selection during decel
Stall prevention selection during running
Stall prevention level during running
0: Disabled (Acceleration as set.
With a heavy load, the motor may stall.)
1: Enabled (Acceleration stopped when L3-02 level is exceeded.
Acceleration starts again when the current has fallen below the stall prevention level).
2: Intelligent acceleration mode
(Using the L3-02 level as a basis, acceleration is automatically adjusted. Set acceleration time is disregarded.)
Effective when L3-01 is set to 1 or
2.
Set as a percentage of Inverter rated current.
Usually changing this setting is not necessary. Reduce the setting when the motor stalls.
0: Disabled (Deceleration as set. If deceleration time is too short, a
DC bus overvoltage may result.)
1: Enabled (Deceleration is stopped when the DC bus voltage exceeds the stall prevention level. Deceleration restarts when the voltage falls below the stall prevention level again.)
2: Intelligent deceleration mode
(Deceleration rate is automatically adjusted so that the
Inverter can decelerate in the shortest possible time. The set deceleration time is disregarded.)
When a braking option (Braking
Unit) is used, always set to 0.
0: Disabled (Runs as set. With a heavy load, the motor may stall.)
1: Deceleration using deceleration time 1 (C1-02.)
2: Deceleration using decelerationtime 2 (C1-04.)
Effective when L3-05 is 1 or 2.
Set as a percentage of the Inverter rated current.
Usually changing this setting is not necessary.
Reduce the setting when the motor stalls.
Setting
Range
0 to 2
0 to
200
0 to 2
0 to 2
30 to
200
Factory
Setting
Change during
Operation
Access
Level
1
120%
1
1
120%
No
No
No
No
No
A
A
A
A
A
MEMO-
BUS
Register
Page
48FH
490H
492H
493H
494H
5-31
5-32
Reference Detection: L4
Parameter
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
L4-01
Speed agreement detection level
Sets the detection level for the reference detection function.
Effective when a multi-function output is set to:
- 3 ("f out
= f set
agree"),
- 4 ("Frequency detection 1") or
- 5 ("Frequency detection 2").
L4-02
Speed agreement detection width
Sets the hysteresis for the reference detection function.
Effective when a multi-function output is set to:
- 2 ("f ref
= f out
agree"),
- 3 ("f out
= f set
agree"),
- 4 ("Frequency detection 1") or
- 5 ( "Frequency detection 2").
L4-05
L4-06
Operation when frequency reference is missing
0: Deceleration to Stop
1: Operation continues at the frequency set in parameter L4-06.
Frequency reference loss means that the frequency reference value drops over 90% in 400 ms.
Frequency reference value at frequency reference loss
Sets the frequency reference value as a percentage of the previous frequency reference, in case the frequency reference signal is lost.
0.0 to
200.0
0.0 to
20.0
0 or 1
0.0 to
100.0%
0.0 Hz
2.0 Hz
1
80%
No
No
No
No
Access
Level
A
A
A
A
MEMO-
BUS
Register
Page
499H
49AH
49DH
4C2H
Fault Restart: L5
Parameter
Number
Name Description
Setting
Range
L5-01
L5-02
Number of auto restart attempts
Auto restart operation selection
L5-03 Fault Retry time
Sets the number of auto restart attempts.
Automatically restarts after a fault and conducts a speed search from the run frequency.
Sets whether a fault relay is activated during fault restart.
0: No output (Fault relay is not activated.)
1: Output (Fault relay is activated.)
Sets the maximum time, the restart is tried.
0 to 10
0 or 1
0.5 to
180.0
Factory
Setting
Change during
Operation
Access
Level
0
0
10.0 sec
No
No
No
A
A
A
MEMO-
BUS
Register
Page
49EH
49FH
4A0H
User Parameter Tables
Load Detection: L6
Parameter
Number
Name
L6-01
Load detection selection
L6-02
L6-03
Load detection level
Load detection time
Description
Setting
Range
Factory
Setting
Change during
Operation
Access
Level
0: Load detection disabled.
1: Overload detection only at speed agree; operation continues (alarm).
2: Overload detection continuously during operation; operation continues (alarm).
3: Overload detection only at speed agree; coast to stop
(fault).
4: Overload detection continuously during operation; coast to stop (fault).
5: Loss of load detection only at speed agree; operation continues (alarm).
6: Loss of load detection continuously during operation; operation continues (alarm).
7: Loss of Load detection only at speed agree; coast to stop
(fault).
8: Loss of Load detection continuously during operation; coast to stop (fault).
Inverter rated current is set as
100%.
Sets the overload/loss of load detection time.
0 to 8
0 to
300
0.0 to
10.0
6
15%
10.0 sec.
No
No
No
A
A
A
MEMO-
BUS
Register
4A1H
4A2H
4A3H
Page
5-33
5-34
Hardware Protection: L8
Parameter
Number
Name Description
L8-02
L8-03
L8-06
Operation selection after overheat pre-alarm
L8-09
Ground fault protection selection
L8-10
L8-11
Overheat prealarm level
Input Phase Loss
Detection Level
Cooling Fan control selection
Cooling fan control delay time
Sets the detection temperature for the Inverter overheat detection prealarm in
°C.
Sets the operation for when the
Inverter overheat pre-alarm occurs.
0: Decelerate to stop using the deceleration time C1-02.
1: Coast to stop
2: Fast stop in fast-stop time
C1-09.
3: Continue operation (Monitor display only.)
4: OH-Alarm and output frequency reduction (L8-19)
A fault will be given in setting 0 to
2 and a alarm will be given in setting 3 and 4.
Allowed DC bus ripple before
Input Phase Loss is detected.
0: Disabled
1: Enabled
It is not recommended to use another setting than factory setting.
Sets the ON/OFF control for the cooling fan.
0: ON only when RUN command is on
1: ON whenever inverter is powered up
Set the time in seconds to delay turning OFF the cooling fan after the inverter STOP command is given.
L8-12
Ambient temperature
Set the ambient temperature.
L8-15
L8-18
L8-19
L8-32
OL2 characteristics selection at low speeds
Soft CLA selection
Frequency reference during OH pre-alarm
OH1 detection selection for fan failure
0: OL2 characteristics at low speeds disabled.
1: OL2 characteristics at low speeds enabled.
It is not recommended to use another setting than factory setting.
0: Disable
1: Enable
It is not recommended to use another setting than factory setting.
Sets the frequency reference when
OH pre-alarm is detected in percent of maximum frequency
Selects whether or not a failure of the internal fan leads to OH1.
0: Disabled
(FAN alarm is displayed)
1: Enabled (OH1 fault occurs)
Setting
Range
50 to
130
0 to 4
0.0 to
25.0%
0 or 1
0 or 1
0 to
300
45 to
60
0 or 1
0 or 1
0.0 to
100.0
0 or 1
Factory
Setting
Change during
Operation
Access
Level
95
°C *1
4
5%
1
0
300 sec.
45
1
1
°C
20.0%
1
No
No
No
No
No
No
No
No
No
No
No
A
A
A
A
A
A
A
A
A
A
A
MEMO-
BUS
Register
Page
4AEH
4AFH
4B2H
4B5H
4B6H
4B7H
4B8H
4BBH
4BEH
4BFH
4E2H
*1. The factory setting depends on the Inverter capacity and the protection class. The value for a 200 V Class Inverter of 0.4 kW in protection class IP00 or IP20 / NEMA 1 is given.
User Parameter Tables
Special Adjustments: n
Hunting Prevention Function: n1
Parameter
Number
Name Description n1-01
Hunting prevention function selection
0: Hunting prevention function disabled
1: Hunting prevention function enabled
Setting
Range
Factory
Setting
Change during
Operation
Access
Level
MEMO-
BUS
Register
Page
0 or 1 1 n1-02
Hunting prevention gain
Sets the hunting prevention gain.
0.00 to
2.50
1.00
No
No
A
A
580H
581H
High Slip Braking: n3
Parameter
Number
Name n3-01
High Slip braking deceleration frequency width n3-02
High Slip braking current limit
Description
Setting
Range
Factory
Setting
Change during
Operation
Sets the frequency width for deceleration during High Slip braking in percent of FMAX (E1-04).
1 to 20 5%
Sets the current limit for deceleration during High Slip braking in percent of the motor rated current.
The resulting limit must be 120% of the Inverter rated current or less.
100 to
200
150%
No
No n3-03
High Slip braking stop dwell time n3-04
High Slip braking OL7 time
Sets the dwell time for the output frequency for FMIN (1.5 Hz) after
High Slip Braking.
Sets the time until OL7 occurs if the output frequency does not change for any reason during High
Slip braking.
0.0 to
10.0
1.0 sec.
No
30 to
1200
40 sec.
No
Access
Level
A
A
A
A
MEMO-
BUS
Register
Page
588H
589H
58AH
58BH
5-35
5-36
Digital Operator Parameters: o
Monitor Select: o1
Parameter
Number o1-01
Monitor selection
*1 o1-02
Monitor selection after power up o1-03
Name
Digital operator display scaling
Description
Setting
Range
Factory
Setting
Change during
Operation
Access
Level
Sets the number of the 4th monitor item to be displayed in the Drive
Mode (U1).
(Only on LED Digital Operator.)
Sets the monitor item to be displayed when the power is turned on.
1: Frequency reference
2: Output frequency
3: Output current
4: The monitor item set for o1-01
Sets the units that will be set and displayed for the frequency reference and frequency monitor.
0: 0.01 Hz units
1: 0.01% units (Maximum output frequency is 100%)
2 to 39: rpm units (Set the motor poles.)
40 to 39999: User desired display
Set the desired values for setting and display for the max. output frequency.
6 to 53
1 to 4
0 to
39999
6
1
0
Yes
Yes
No
A
A
A
MEMO-
BUS
Register
500H
501H
502H
Page
o1-05 LCD-Focus o1-06
Monitor Mode
o1-07
2nd Monitor
Sets the value that is to be displayed at
100% excluding the decimal point.
Sets the number of decimal places.
Example: When the max. output value is 200.0, set 12000
Sets the brightness on the LCD
Digital Operator.
0: light
1:
2:
3: normal
4:
5: dark
0: Below the active monitor parameter the next 2 sequential monitors are displayed.
1: Below the active monitor the 2 monitors specified by o1-07 and o1-08 are locked
Selects the monitor that is displayed and locked in the second line of the operator display.
0 to 5
0 or 1
1 to 53
3
0
2
Yes
No
No
A
A
A
504H
517H
518H
–
–
–
User Parameter Tables
Parameter
Number
Name Description o1-08
3rd Monitor
Selection
o1-09
Frequency reference display unit selection
*2
Selects the monitor that is displayed and locked in the third line of the operator display.
Sets the unit display for the fre-
quency reference related monitors
when o1-03
Settings
for the setting range.
Setting
Range
Factory
Setting
Change during
Operation
Access
Level
1 to 53
0 to 11
3
0
No
No
A
A
*1. Parameter function is only valid if the LED Digital Operator is used.
*2. Parameter function is only valid if a Digital Operator with LCD clear text display is used (LCD or HOA Digital Operator).
MEMO-
BUS
Register
519H
Page
–
619H
o1-09 Settings
10
11
8
9
6
7
Setting
Value
0
1
4
5
2
3
Function
WC: Inch of water column
PSI: lb/square inch
GPM: Gallons per minute
F: Degree Fahrenheit
CFM: Cubic feet per minute
CMH: Cubic meter per hour
LPH: Liters per hour
LPS: Liters per second
Bar: Bar
Pa: Pascal
C: Degree Celsius
Mtr: Meters
Displayed Unit
WC
PSI
GPM
F
CFM
CMH
LPH
LPS
Bar
Pa
C
Mtr
5-37
5-38
Multi-function Selections: o2
Parameter
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation o2-01 o2-02 o2-03
LOCAL/
REMOTE key enable/disable
*1
Enables/disables the LOCAL/
REMOTE key
0: Disabled
1: Enabled (Switches between the
Digital Operator and the parameter settings b1-01, b1-02.)
STOP key during control circuit terminal opera-
Enables/disables the STOP key
0: Disabled (When the run command is issued from an external terminal, the Stop key is disabled.)
1: Enabled (Effective even during run.)
User parameter initial value
Clears or stores user initial values.
0: Stored/not set
1: Begins storing
(Records the set parameters as user initial values.)
2: Clearing memory (Clears all recorded user initial values)
When the set parameters are recorded as user initial values,
1110 can be set in A1-03 to recall them.
0 or 1
0 or 1
0 to 2
1
1
0 o2-04 o2-05 o2-06 o2-07 o2-08 o2-09 kVA selection
Frequency reference setting method selection
Operation selection when digital operator is disconnected
Cumulative operation time setting
Cumulative operation time selection
Initialize Mode
Do not set unless after replacing
for the setting values)
When the frequency reference is set on the Digital Operator frequency reference monitor, sets whether the Enter key is necessary or not.
0: Enter key needed
1: Enter key not needed
Sets the operation when the Digital
Operator is disconnected.
0: Disabled (Operation continues even if the Digital Operator is disconnected.)
1: Enabled (OPR is detected at
Digital Operator disconnection.
Inverter output is switched off, and fault relay is operated.)
Sets the cumulative operation time.
The operation time is accumulated form the set value.
0: Accumulated Inverter power on time
1: Accumulated Inverter run time.
2: Europe Spec.
5: PV-E Spec.
6: Chinese Spec.
0 to FF
0
*2
0 or 1
0 or 1
0 to
65535
0 or 1
2, 5, 6
0
0
0 hrs
1
2
No
No
No
No
No
No
No
No
No
Access
Level
A
A
A
A
A
A
A
A
A
MEMO-
BUS
Register
505H
506H
507H
508H
509H
50AH
50BH
50CH
50DH
Page
-
User Parameter Tables
Parameter
Number
Name Description o2-10 o2-12 o2-14 o2-15 o2-17
Fan operation time setting
Standard / IP54
Selection
Sets the initial value of the fan operation time.
The fan operation time is accumulated from the set value.
Fault trace initialize kWh monitor initialize
0: No change
1: Initialized. After setting ”1“ o2-
12 will return to ”0“
Resets the monitor parameters
U1-29 and U1-30 back to zero.
0: No change
1: Reset to zero
HAND Key function selection
*3
If set to 0 the HAND key on the
HOA Digital Operator is disabled and the Inverter will not enter the
HAND mode and start to run when the HAND key is pressed.
0: HAND key disabled
1: HAND key enabled
Selects whether the Inverter is in standard (IP00 or NEMA 1 / IP20) or IP54 protection class.
0: IP00 or NEMA 1 / IP20
1: IP54
Setting
Range
0 to
65535
0 or 1
0 or 1
0 or 1
0 or 1
Factory
Setting
Change during
Operation
Access
Level
0 hr.
0
0
0
*4
No
No
No
No
No
*1. This parameter is effective only when the LED or LCD Digital Operator is used.
*2. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
*3. This parameter is effective only when the HOA operator JVOP-162 is used.
*4. Factory setting depends on the protection class of the Inverter.
*5. The access level depends on the setting of o2-09: When o2-09 is set to “2” or “5” parameter o2-17 is accessable.
A
A
A
A
*5
MEMO-
BUS
Register
50EH
511H
512H
513H
51BH
Page
Copy Function: o3
Parameter
Number
Name Description o3-01
Copy function selection o3-02
Read permission selection
0: Normal operation
1: READ (Inverter to Operator)
2: COPY (Operator to Inverter)
3: Verify (compare)
0: READ prohibited
1: READ permitted
Setting
Range
Factory
Setting
Change during
Operation
Access
Level
MEMO-
BUS
Register
Page
0 to 3
0 or 1
0
0
No
No
A
A
515H
516H
5-39
5-40
Motor Autotuning: T
Parameter
Number
Name
T1-02
Motor output power
Description
Set the output power of the motor in Kilowatts.
Setting
Range
0.00 to
650.00
Factory
Setting
Change during
Operation
0.40 kW
*1
No
Access
Level
A
MEMO-
BUS
Register
702H
Page
T1-04
Motor rated current
Set the rated current of the motor in
Amps.
0.32 to
6.40
*2
1.90 A
No A 704H
*1. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
*2. The setting range is 10% to 200% of the Inverter rated output current. The value for a 200 V class Inverter of 0.4 kW is given.
User Parameter Tables
Monitor Parameters: U
Status Monitor Parameters: U1
Parameter
Number
Name
U1-01
Frequency reference
Description
Monitors/sets the frequency reference value.
*1
U1-02 Output frequency Monitors the output frequency.
Output Signal Level During Multi-
Function Analog Output
Min.
Unit
10 V: Max. frequency
10 V: Max. frequency
0.01
Hz
0.01
Hz
MEMO-
BUS
Register
40H
41H
U1-03 Output current Monitors the output current.
U1-06 Output voltage
Monitors the output voltage reference.
U1-07 DC bus voltage Monitors the DC bus voltage.
U1-08 Output power Monitors the output power.
10 V: Inverter rated output current
0.01
A
10 V: 200 VAC (400 VAC)
0.1
V
10 V: 400 VDC (800 VDC) 1 V
10 V: Inverter capacity
(max. applicable motor capacity)
0.1 kW
42H
45H
46H
47H
U1-10
Input terminal status
Shows input ON/OFF status.
1: FWD command
(S1) is ON
1: REV command
(S2) is ON
1: Multi input 1
(S3) is ON
1: Multi input 2
(S4) is ON
1: Multi input 3
(S5) is ON
1: Multi input 4
(S6) is ON
1: Multi input 5
(S7) is ON
(Cannot be output.) – 49H
U1-11
Output terminal status
Shows output ON/OFF status.
1: Multi-function digital output 1
(M1-M2) is ON
1: Multi-function digital output 2
(M3-M4) is ON
Not used
(Always 0).
1: Error output
(MA/MB-MC) is
ON
U1-12 Operation status
Inverter operating status.
1: Run
1: Zero speed
1: Reverse
1: Reset signal
input
1: Speed agree
1: Inverter ready
1: Minor fault
1: Major fault
(Cannot be output.)
(Cannot be output.)
– 4AH
– 4BH
5-41
5-42
Parameter
Number
Name Description
Output Signal Level During Multi-
Function Analog Output
U1-13
Cumulative operation time
Monitors the total operating time of the Inverter.
The initial value and the operating time/power ON time selection can be set in o2-07 and o2-08.
(Cannot be output.)
U1-14
Software No.
(flash memory)
(Manufacturer’s ID number) (Cannot be output.)
U1-15
U1-16
U1-18
U1-20
U1-24
U1-28
Terminal A1 input level
Terminal A2 input level
Motor secondary current (Iq)
Output frequency after softstarter (SFS output)
PI feedback value
*2
Software No.
(CPU)
Monitors the input level of analog input A1. A value of 100% equals
10V input.
10 V: 100%
Monitors the input level of analog input A2. A value of 100% equals
10V/20mA input.
10 V/20mA: 100%
Monitors the calculated value of the motor secondary current.
The motor rated current corresponds to 100%.
10 V:Motor rated current
Monitors the frequency reference after the soft starter.
This frequency value does not include compensations, such as
10 V: Max. frequency
Monitors the feedback value when PI control is used.
*3
10 V: 100% feedback value
(CPU software No.) (Cannot be output.)
U1-29 kWh display
U1-30 MWh display
Monitors the 4 lower digits, kWh display.
(Cannot be output.)
Monitors the 5 higher digits,
MWh display.
(Cannot be output.)
Min.
Unit
1 hr.
–
0.1% 4EH
0.1% 4FH
0.1% 51H
0.01
Hz
0.01
%
–
1 kWh
0.1
MW h
MEMO-
BUS
Register
4CH
4DH
53H
57H
5BH
5CH
5DH
U1-31 LED Test
U1-34
OPE fault parameter
For testing LEDs on operator. If this monitor is selected, all
LED’s light up (only on LED operator).
(Cannot be output.)
Shows the first parameter number when an OPE fault is detected.
(Cannot be output.)
–
–
3CH
61H
U1-36 PI input volume
U1-37 PI output volume
U1-38 PI setpoint
PI input volume
PI control output
10 V: 100% PI input
10 V: 100% PI output
10 V: 100% PI setpoint
0.01
%
0.01
%
0.01
%
63H
64H
65H
User Parameter Tables
Parameter
Number
Name
U1-39
MEMOBUS communications error code
Description
Shows MEMOBUS errors.
Output Signal Level During Multi-
Function Analog Output
Min.
Unit
MEMO-
BUS
Register
1: CRC error
1: Data length error
Not used
(always 0)
1: Parity error
1: Overrun error
1: Framing error
1: Timeout
Not used
(always 0)
(Cannot be output.) – 66H
U1-40
U1-51
U1-52
Cooling fan operating time
Monitors the total operating time of the cooling fan. The time can be set in o2-10.
(Cannot be output.)
Frequency reference at AUTO operation
Frequency reference at HAND operation
U1-53 PI feedback 2
Monitors the value of the frequency reference when AUTO operation is active.
Monitors the value of the frequency reference when HAND operation is active.
Monitors the feedback value of the PI fdbk2 input when Differential PI is selected (H3=6B)
10 V: Max. frequency
10 V: Max. frequency
10V: 100% feedback value
*1. The monitor parameter can be scaled in o1-03, the unit can be set in o1-09.
*2. The monitor parameters will be moved up to 2nd and 3rd position when the PI controller is enabled.
*3. The monitor parameter can be scaled in b5-20, the unit can be set in b5-31.
1 hr.
0.01
%
0.01
%
0.01
%
68H
72H
73H
74H
5-43
5-44
Fault Trace: U2
Parameter
Number
Name
U2-01 Current fault
Description
The content of the current fault.
Output Signal Level During
Multi-Function Analog Output
Min.
Unit
MEMO-
BUS
Register
– 80H
U2-02 Last fault The error content of the last fault.
U2-03
Reference frequency at fault
U2-04 Output frequency at fault
The reference frequency when the last fault occurred.
The output frequency when the last fault occurred.
U2-05 Output current at fault
U2-08 DC bus voltage at fault
The output current when the last fault occurred.
U2-07
Output voltage reference at fault
The output reference voltage when the last fault occurred.
The DC bus voltage when the last fault occurred.
U2-09 Output power at fault
The output power when the last fault occurred.
U2-11
U2-12
Input terminal status at fault
Output terminal status at fault
U2-13 Operation status at fault
The input terminal status when the last fault occurred.
The format is the same as for U1-10.
The output terminal status when the last fault occurred. The format is the same as for U1-11.
The operating status when the last fault occurred. The format is the same as for U1-12.
U2-14
Cumulative operation time at fault
The operating time when the last fault occurred.
Note: The following errors are not included in the error trace: CPF00, 01, 02, 03, UV1, and UV2.
(Cannot be output.)
– 81H
0.01
Hz
0.01
Hz
0.01
A
0.1
V
82H
83H
84H
86H
87H 1 V
0.1 kW
88H
–
–
–
1 hr.
8AH
8BH
8CH
8DH
User Parameter Tables
Fault History: U3
Parameter
Number
U3-01 Last fault
Name Description
U3-02 Second last fault
The error content of 1st last fault.
The error content of 2nd last fault.
The error content of 3rd last fault.
U3-03 Third last fault
U3-04 Fourth last fault The error content of 4th last fault.
U3-05
Cumulative operation time at fault
The total operating time when the
1st previous fault occurred.
U3-06
Accumulated time of second fault
U3-07
Accumulated time of third fault
U3-08
Accumulated time of fourth/oldest fault
The total operating time when the
2nd previous fault occurred.
The total operating time when the
3rd previous fault occurred.
The total operating time when the
4th previous fault occurred.
Output Signal Level During
Multi-Function Analog Output
(Cannot be output.)
Min.
Unit
–
MEMO-
BUS
Register
90H
–
–
–
1 hr.
1 hr.
1 hr.
1 hr.
91H
92H
93H
94H
95H
96H
U3-09
–
U3-14
Fifth last to tenth last fault
The error content of the 5th to
10th last fault
U3-15
–
U3-20
Accumulated time of fifth to tenth fault
Total generating time when 5th...
10th previous fault occurred
–
1hr
97H
804
805H
806H
807H
808H
809H
806H
80FH
810H
811H
812H
813H
Note:The following errors are not recorded in the error log: CPF00, 01, 02, 03, UV1, and UV2.
5-45
5-46
Setting Values that Change with the V/f Pattern Selection (E1-03)
200 V and 400 V Class Inverters of 0.4 to 1.5 kW
Parameter
Number
E1-03
E1-04
E1-05
*1
Unit Factory Setting
0 1 2 3 4 5 6 7 8 9 A B C D E F FF
Hz 50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
90.0
120.0
180.0
50.0
50.0
V 200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
E1-06
E1-07
Hz 50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
50.0
50.0
Hz 2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
2.5
2.5
E1-08
E1-09
E1-10
V 15.0
15.0
15.0
15.0
35.0
50.0
35.0
50.0
19.0
24.0
19.0
24.0
15.0
15.0
15.0
15.0
12.0
Hz
V
1.3
9.0
1.5
9.0
1.5
9.0
1.5
9.0
1.3
8.0
1.3
9.0
1.5
8.0
1.5
9.0
1.3
1.3
1.5
1.5
1.5
11.0
13.0
11.0
15.0
9.0
1.5
9.0
1.5
9.0
1.2
9.0
1.2
6.0
*1. These are values for a 200 V class Inverter. Values for a 400 V class Inverter are double
200 V and 400 V Class Inverters of 2.2 to 45 kW
Parameter
Number
E1-03
E1-04
E1-05
*1
Unit Factory Setting
0 1 2 3 4 5 6 7 8 9 A B C D E F FF
Hz 50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
90.0
120.0
180.0
50.0
50.0
V 200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
E1-06
E1-07
Hz 50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
50.0
50.0
Hz 2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
2.5
2.5
E1-08
E1-09
E1-10
V 14.0
14.0
14.0
14.0
35.0
50.0
35.0
50.0
18.0
23.0
18.0
23.0
14.0
14.0
14.0
14.0
15.0
Hz
V
1.3
7.0
1.5
7.0
1.5
7.0
1.5
7.0
1.3
6.0
1.3
7.0
1.5
6.0
1.5
7.0
1.3
9.0
1.3
1.5
11.0
9.0
1.5
1.5
13.0
7.0
1.5
7.0
1.5
7.0
1.2
7.0
1.2
9.0
*1. These are values for a 200 V class Inverter. Values for a 400 V class Inverter are double
200 V Class Inverters of 55 to 110 kW and 400 V Class Inverters of 55 to 300 kW
Parameter
Number
E1-03
E1-04
E1-05
*1
Unit Factory Setting
0 1 2 3 4 5 6 7 8 9 A B C D E F FF
Hz 50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
90.0
120.0
180.0
50.0
50.0
V 200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
E1-06
E1-07
Hz 50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
50.0
50.0
Hz 2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
2.5
2.5
E1-08
E1-09
E1-10
V 12.0
12.0
12.0
12.0
35.0
50.0
35.0
50.0
15.0
20.0
15.0
20.0
12.0
12.0
12.0
12.0
14.0
Hz
V
1.3
6.0
1.5
6.0
1.5
6.0
1.5
6.0
1.3
5.0
1.3
6.0
1.5
5.0
1.5
6.0
1.3
7.0
1.3
9.0
1.5
7.0
1.5
1.5
11.0
6.0
1.5
6.0
1.5
6.0
1.2
6.0
1.2
7.0
*1. These are values for a 200 V class Inverter. Values for a 400 V class Inverter are double
User Parameter Tables
Factory Settings that Change with the Inverter Capacity (o2-04)
200 V Class Inverters
Parameter
Number
– o2-04
Name
Inverter Capacity kVA selection b8-04 Energy-saving coefficient
C6-02
Carrier frequency selection
*1
Unit Factory Setting kW
–
0.4
0
0.75
1
1.5
2
2.2
3
3.7
4
5.5
5
7.5
6
11
7
15
8
– 288.20
223.70
169.40
156.80
122.90
94.75
72.69
70.44
63.13
Normal Duty 1 –
Normal Duty 2 –
6
4
6
4
6
4
6
3
6
4
6
6
6
6
6
3
6
4
E2-01
E2-03
Motor rated current
Motor no-load current
E2-05 Motor line-to-line resistance
L2-02
Momentary power loss ride through time
A
A
1.90
1.20
3.30
1.80
6.20
2.80
8.50
3.00
14.00
4.50
19.60
5.10
26.60
8.00
39.7
11.2
53.0
15.2
W 9.842
5.156
1.997
1.601
0.771
0.399
0.288
0.230
0.138
sec.
0.1
0.1
0.2
0.3
0.5
1.0
1.0
1.0
2.0
L2-03 Min. baseblock (BB) time
L2-04 Voltage recovery time
L8-02 Overheat pre-alarm level
L8-06 Input phase loss detection level sec.
sec.
°C
%
0.1
0.3
95
5.0
0.2
0.3
95
7.5
0.3
0.3
95
10.0
0.4
0.3
95
12.0
0.5
0.3
95
12.0
0.6
0.3
95
10.0
0.7
0.3
95
17.0
0.8
0.3
95
21.0
0.9
0.3
95
17.0
*1. The initial settings for C6-02 are as follows: 2: 5.0 kHz, 3: 8.0 kHz, 4: 10 kHz, 5: 12.5 kHz, and 6: 15 kHz. If the carrier frequency is set higher than the factory setting for Inverters with outputs of 30 kW or more, the Inverter rated current will need to be reduced.
Parameter
Number
– o2-04
Name
Inverter Capacity kVA selection b8-04 Energy-saving coefficient
C6-02
Carrier frequency selection
*1
Unit Factory Setting kW 18.5
– 9
–
22
A
30
B
37
C
45
D
55
E
75
F
90
10
110
11
57.87
51.79
46.27
38.16
35.78
31.35
23.10
23.10
23.10
Normal Duty 1 –
Normal Duty 2 –
6
4
6
4
6
4
6
3
6
4
6
6
6
6
6
3
6
4
E2-01
E2-03
Motor rated current
Motor no-load current
E2-05 Motor line-to-line resistance
L2-02
Momentary power loss ride through time
A
A
65.8
15.7
77.2
18.5
105.0
21.9
131.0
38.2
160.0
44.0
190.0
45.6
260.0
72.0
260.0
72.0
260.0
72.0
W 0.101
0.079
0.064
0.039
0.030
0.022
0.023
0.023
0.023
sec.
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
L2-03 Min. baseblock (BB) time
L2-04 Voltage recovery time
L8-02 Overheat pre-alarm level
L8-06 Input phase loss detection level sec.
sec.
°C
%
1.0
0.6
95
15.0
1.0
0.6
95
24.0
1.1
0.6
95
20.0
1.1
0.6
95
18.0
1.2
0.6
95
20.0
1.2
1.0
95
17.0
1.3
1.0
95
16.0
1.5
1.0
95
18.0
1.7
1.0
95
20.0
*1. The initial settings for C6-02 are as follows: 2: 5.0 kHz, 3: 8.0 kHz, 4: 10 kHz, 5: 12.5 kHz, and 6: 15 kHz. If the carrier frequency is set higher than the factory setting for Inverters with outputs of 30 kW or more, the Inverter rated current will need to be reduced.
5-47
5-48
400 V Class Inverters in Protection Class IP00 and NEMA 1 / IP20
Parameter
Number
– o2-04
Name
Inverter Capacity kVA selection b8-04 Energy-saving coefficient
C6-02
Carrier frequency selection
*1
E2-01 Motor rated current
E2-03 Motor no-load current
Normal
Duty 1
Normal
Duty 2
E2-05 Motor line-to-line resistance
L2-02
Momentary power loss ride through time
L2-03
Min. baseblock (BB) time
L2-04
Voltage recovery time
L8-02 Overheat pre-alarm level
L8-06 Input phase loss detection
Unit kW
–
0.75
21
1.5
22
2.2
23
Factory Setting
3.7
24
4.0
25
5.5
26
7.5
27
11
28
15
29
– 576.40 447.40 338.80 313.60 245.80 236.44 189.50 145.38 140.88 126.26
–
–
A
A sec.
sec.
sec.
0.3
°C
%
0.4
20
6
6
1.00
0.60
0.1
0.1
95
5.0
6
6
1.60
0.80
6
6
6
6
6
6
6
6
6
6
6
6
6
3
6
4
W 38.198 22.459 10.100
6.495
3.333
3.333
1.595
1.152
0.922
0.550
0.1
0.2
0.3
95
7.5
3.10
1.40
0.2
0.3
0.3
95
10.0
4.20
1.50
0.3
0.4
0.3
95
10.0
7.00
2.30
0.5
0.5
0.3
95
12.0
7.00
2.30
0.5
0.6
0.3
95
10.0
9.80
2.60
0.8
0.6
0.3
95
10.0
13.30
4.00
0.8
0.7
0.3
95
20.0
19.9
5.6
1.0
0.8
0.3
95
23.0
26.5
7.6
2.0
0.9
0.3
95
17.0
*1. The initial settings for C6-02 are as follows: 2: 5.0 kHz, 3: 8.0 kHz, 4: 10 kHz, 5: 12.5 kHz, and 6: 15 kHz. If the carrier frequency is set higher than the factory setting for Inverters with outputs of 30 kW or more, the Inverter rated current will need to be reduced.
Parameter Number
– o2-04
Name
Inverter Capacity kVA selection b8-04 Energy-saving coefficient
C6-02
Carrier frequency selection
*1
Normal
Duty 1
Normal
Duty 2
E2-01 Motor rated current
E2-03 Motor no-load current
E2-05 Motor line-to-line resistance
L2-02
Momentary power loss ride through time
L2-03 Min. baseblock (BB) time
L2-04 Voltage recovery time
L8-02 Overheat pre-alarm level
L8-06 Input phase loss detection
Unit kW
–
18.5
2A
22
2B
30
2C
37
2D
Factory Setting
45
2E
55
2F
75
30
90
31
110
32
132
33
– 115.74 103.58
92.54
76.32
71.56
67.20
46.20
41.22
36.23
33.18
–
–
A
A sec.
sec.
sec.
°C
%
6
4
32.9
7.8
6
4
4
3
4
3
4
3
4
2
3
2
3
3
3
2
2
2
W 0.403
0.316
0.269
0.155
0.122
0.088
0.092
0.056
0.046
0.035
2.0
1.0
0.6
95
17.0
38.6
9.2
2.0
1.0
0.6
95
20.0
52.3
10.9
2.0
1.1
0.6
95
20.0
65.6
19.1
2.0
1.1
0.6
95
20.0
79.7
22.0
2.0
1.2
0.6
95
20.0
95.0
24.0
2.0
1.2
1.0
100
20.0
130.0
36.0
2.0
1.3
1.0
95
20.0
156.0
40.0
2.0
1.5
1.0
110
16.0
190.0
49.0
2.0
1.7
1.0
110
16.0
223.0
58.0
2.0
1.7
1.0
110
16.0
*1. The initial settings for C6-02 are as follows: 2: 5.0 kHz, 3: 8.0 kHz, 4: 10 kHz, 5: 12.5 kHz, and 6: 15 kHz. If the carrier frequency is set higher than the factory setting for Inverters with outputs of 30 kW or more, the Inverter rated current will need to be reduced.
User Parameter Tables
Parameter Number
– o2-04
Name
Inverter Capacity kVA selection b8-04 Energy-saving coefficient
C6-02
Carrier frequency selection
*1
Normal Duty 1
Normal Duty 2
E2-01 Motor rated current
E2-03 Motor no-load current
A 270.0
310.0
370.0
500.0
A 70.0
81.0
96.0
130.0
E2-05 Motor line-to-line resistance W 0.029
0.025
0.020
0.014
L2-02 Momentary power loss ride through time sec.
2.0
2.0
2.0
2.0
L2-03
L2-04
L8-02
L8-06
Min. baseblock (BB) time
Voltage recovery time
Overheat pre-alarm level
Input phase loss detection level
Unit kW
–
–
–
– sec.
sec.
°C
%
1.8
1.0
108
14.0
Factory Setting
160
34
185
35
220
36
300
37
30.13
30.57
27.13
21.76
2
2
2
1
1
1
1
1
1.9
1.0
95
15.0
2.0
1.0
100
15.0
2.1
1.0
108
15.0
*1. The initial settings for C6-02 are as follows: 2: 5.0 kHz, 3: 8.0 kHz, 4: 10 kHz, 5: 12.5 kHz, and 6: 15 kHz. If the carrier frequency is set higher than the factory setting for Inverters with outputs of 30 kW or more, the Inverter rated current will need to be reduced.
400 V Class Inverters in Protection Class IP54
Parameter Number
– o2-04
Name
Inverter Capacity kVA selection b8-04 Energy-saving coefficient
C6-02
Carrier frequency selection
*1
E2-01 Motor rated current
E2-03 Motor no-load current
E2-05 Motor line-to-line resistance
L2-02
Momentary power loss ride through time
L2-03 Min. baseblock (BB) time
L2-04 Voltage recovery time
L8-02 Overheat pre-alarm level
L8-06 Input phase loss detection
Unit kW
–
7.5
67
11
68
15
69
18.5
6A
22
6B
30
6C
37
6D
45
6E
55
6F
–
145.38 140.88 126.26 115.74 103.58
92.54
76.32
71.56
67.20
– 2 2 2 2 2 2 2 2 2
A
13.30
19.9
26.5
32.9
38.6
52.3
65.6
79.7
95.0
A 4.00
5.6
7.6
7.8
9.2
10.9
19.1
22.0
24.0
W
1.152
0.922
0.550
0.403
0.316
0.269
0.155
0.122
0.088
sec.
0.8
1.0
2.0
2.0
Factory Setting
2.0
2.0
2.0
2.0
2.0
sec.
0.7
0.8
0.9
1.0
1.0
1.1
1.1
1.2
1.2
sec.
0.3
°C
90
0.3
95
0.3
95
0.6
98
0.6
87
0.6
87
0.6
85
0.6
86
1.0
86
%
20.0
23.0
17.0
17.0
20.0
20.0
20.0
20.0
20.0
*1. The initial settings for C6-02 are as follows: 2: 5.0 kHz, 3: 8.0 kHz, 4: 10 kHz, 5: 12.5 kHz, and 6: 15 kHz. If the carrier frequency is set higher than the factory setting for Inverters with outputs of 30 kW or more, the Inverter rated current will need to be reduced.
5-49
5-50
6
Parameter Settings by
Function
Carrier Frequency Selection ..............................................6-2
Frequency Reference ........................................................6-5
Run Command...................................................................6-9
Stopping Methods ............................................................6-11
Acceleration and Deceleration Characteristics ................6-15
Adjusting Frequency References.....................................6-21
Speed Limit (Frequency Reference Limit Function).........6-24
Frequency Detection........................................................6-25
Improved Operating Performance....................................6-27
Machine Protection ..........................................................6-29
Automatic Restart ............................................................6-38
Inverter Protection............................................................6-47
Input Terminal Functions .................................................6-52
Output Terminal Functions...............................................6-64
Monitor Parameters .........................................................6-67
Individual Functions .........................................................6-69
Digital Operator Functions .............................................6-110
Carrier Frequency Selection
Setting the Carrier Frequency
Using the following parameters the carrier frequency setting can be fitted to the applications requirements.
Related Parameters
Parameter
No.
Name
C6-01 Normal duty selection
C6-02 Carrier frequency selection
C6-03 Carrier frequency upper limit
C6-04 Carrier frequency lower limit
Setting
Range
1 or 2
0 to F
2.0 to
15.0
*2 *3
0.4 to
15.0
00 to 99
Factory
Setting
1
6
*1
15.0 kHz
15.0 kHz
00
Changes
During
Operation?
No
No
No
No
No
Access
Level
A
A
A
A
A C6-05 Carrier frequency proportional gain
*1. The factory setting depends on the Inverter capacity.
*2. The setting range depends on the Inverter capacity.
*3. This parameter can only be set when C6-02 is set to F.
Carrier Frequency, Current Derating and Overload Capability in Normal Duty 1 and 2
The Inverter overload capability depends among other things on the carrier frequency setting. If the carrier frequency setting is higher than the factory setting, the overload current capability must be reduced.
Further, Normal Duty 2 enables a higher continuous output current before the Inverter overload calculation is started.
Inverters in Protection Class IP00 and IP20 / NEMA 1 and Normal Duty 1
In Normal Duty 1 the default carrier frequency depends on the Inverter capacity. With the default setting the overload capability is 120% of the rated output current for 1 minute. If the carrier frequency is set to a higher value, the overload capability is reduced as shown in
.
200V Class 37 to 90kW
400V Class 75 to 110kW
200V Class 0.4 to 22kW
400V Class 0.4 to 22kW
120%
96%
90%
400V Class 132kW
400V Class 160kW
200V Class 30kW
400V Class 30 to 55kW
6-2
Carrier Freq.
0
5kHz 8kHz 10kHz 15kHz
Fig 6.1 Overload Capability depending on Carrier Frequency (IP00 and IP20 / NEMA 1) in Normal Duty 1
Carrier Frequency Selection
Inverters in Protection Class IP00 and IP20 / NEMA 1 and Normal Duty 2
In the Normal Duty 2 mode the maximum carrier frequency is decreased compared to the Normal Duty 1 mode but the short term overload capability is increased. No further increase of the carrier frequency is possi-
for the overload capability of both modes and to
page 5-47, Factory Settings that Change with the Inverter Capacity (o2-04)
for the carrier frequency default settings in Normal Duty 2
100
10
1
0.1
100 110 120 130 140 150 160
Overload Level [%]
Normal Duty 1
170
Normal Duty 2
180
Fig 6.2 Normal Duty 1 and 2 Inverter Overload Detection Curve
190 200
Inverters in Protection Class IP54
The default carrier frequency setting is 5kHz for all Inverters in protection class IP54. If the carrier frequency is set to a higher value than the factory setting, the overload capability is reduced as shown in
. For
IP54 Inverters the setting Heavy Duty 2 is not available.
120%
400V class 22 to 55kW (IP54)
96%
400V class 7.5kW to 18.5kW (IP54)
72%
5 kHz
10 kHz
15 kHz
Carrier Frequency
Fig 6.3 Overload Capability depending on Carrier Frequency (IP54)
6-3
6-4
Setting Precautions
Carrier Frequency Selection
When selecting the carrier frequency, observe the following precautions:
•
If the wiring distance between Inverter and motor is long: Set the carrier frequency low. (Use the following values as guidelines.
Wiring Length
C6-02 (carrier frequency) setting
50 m or less
0 to 6 (15 kHz)
100 m or less
0 to 4 (10 kHz)
Over 100 m
0 to 2 (5 kHz)
•
If speed and torque oscillate at low speeds: Decrease the carrier frequency.
•
If Inverter noise is affecting peripheral devices: Decrease the carrier frequency.
•
If leakage current from the Inverter is large: Decrease the carrier frequency.
•
If metallic noise from the motor is large: Increase the carrier frequency.
•
The carrier frequency can be set to vary depending on the output frequency as shown in the following diagram, by setting C6-03 (Carrier Frequency Upper Limit), C6-04 (Carrier Frequency Lower Limit), and
C6-05 (Carrier Frequency Proportional Gain).
Carrier Frequency
C6-03
C6-04
Output frequency x C6-05 x K
Output frequency
E1-04
Max. Output Frequency
Fig 6.4 Carrier Frequency Gain
* K is the coefficient determined by the set value in C6-03.
C6-03
≥ 10.0 kHz: K=3
10.0 kHz > C6-03
≥ 5.0 kHz: K=2
5.0 kHz > C6-03: K=1
•
To fix the carrier frequency to any desired value, set C6-03 and C6-04 to the same value, or set C6-05 to 0.
An OPE11 (Data setting error) will occur in the following cases:
•
If Carrier Frequency Proportional Gain (C6-05) > 6 and C6-03 < C6-04
•
If C6-02 is set from 7 to E.
Frequency Reference
Frequency Reference
This section explains how to input the frequency reference.
Selecting the Frequency Reference Source
Set parameter b1-01 to select the frequency reference source.
Related Parameters
Parameter
Number b1-01 Reference selection
Name
Setting
Range
0 to 3
Factory
Setting
1
Change during
Operation
No
Access
Level
Q
Input the Frequency Reference from the Digital Operator
When b1-01 is set to 0, the frequency reference can be input from the Digital Operator.
For details on setting the frequency reference, refer to
Chapter 3, Digital Operator and Modes
-DRIVE-
Frequency Ref
Rdy
~
"0.00Hz"
Fig 6.5 Frequency Setting Display with LED and LCD Digital Operator
Inputting the Frequency Reference Using Voltage (Analog Setting)
When b1-01 is set to 1, the frequency reference can be input from the control circuit terminal A1 (voltage input), or control circuit terminal A2 (voltage or current input).
Inputting Master Speed Frequency Reference Only
If inputting the master speed frequency reference only, input the voltage reference to control circuit terminal
A1.
Inverter
2 k
Ω
2 k
Ω
+V (Power supply: 15 V, 20 mA)
A1 (Master frequency reference)
A2 (Auxiliary frequency reference)
AC (Analog common)
Fig 6.6 Master Speed Frequency Reference Input
6-5
6-6
2-Step Switching: Master/Auxiliary
If 2-step switching between master and auxiliary speed frequencies is performed, input the master speed frequency reference to control circuit terminal A1, and input the auxiliary speed frequency reference to A2.
When terminal S3 (multi-step speed command 1) is OFF, terminal A1 input (master speed frequency reference) will be the Inverter frequency reference, and when terminal S3 is ON, terminal A2 input (auxiliary speed frequency reference) will be the Inverter frequency reference.
2 k
Ω
Master/
Auxiliary
2 k
Ω
2 k
Ω
0 to 10 V input
0 to 10 V input
Inverter
S3 Multi-step speed
command 1
SN Digital input neutral
+V (Power supply: 15 V,
20 mA)
A1 (Master frequency
reference)
A2 (Auxiliary frequency
reference)
AC (Analog common)
DIP switch S1
Fig 6.7 Master/Auxiliary Frequency Reference Input
Setting Precautions
When inputting a voltage signal to terminal A2, turn OFF pin 2 on DIP switch S1 to switch to voltage input
(factory setting is ON).
Inputting Frequency Reference Using Current
When b1-01 is set to 1, the frequency reference can be input from control circuit terminal A2. Input the current
(4 to 20 mA) in control circuit terminal A2.
When H3-09 (Multi-Function analog input terminal A2 function selection) is set to 0 (factory setting) the input on A2 is added to A1.
Inverter
4 to 20 mA
+V (Power supply: 15 V,
A1(Auxiliary frequency
A2(Master frequency
AC (Analog common)
DIP switch S1
Fig 6.8 Frequency Reference Using Current
Setting Precautions
•
When inputting a current signal to terminal A2, turn ON pin 2 on DIP switch S1 (factory setting: ON).
•
If using terminal A2 to input the master speed reference and terminal A1 to input the auxiliary frequency reference, set H3-13 (Terminal A1/A2 Switching) to 1.
Frequency Reference
Using Multi-Step Speed Operation
With Varispeed E7 series Inverters the speed can be changed in a maximum of 5 steps, using 4 multi-step frequency references and one jog frequency reference.
The following example of a multi-function input terminal function shows a 5-step operation using multi-step references 1 and 2 and jog frequency selection functions.
Related Parameters
To switch frequency references, set multi-step references 1 and 2 and the jog reference selection in the multifunction digital inputs.
Multi-function Digital Inputs (H1-01 to H1-04)
Terminal
Parameter
Number
Set Value
S5
S6
S7
H1-03
H1-04
H1-05
3
4
6
Details
Multi-step speed command 1 (Also used for master speed/auxiliary speed switching when multi-function analog input H3-09 is set to 2 (auxiliary frequency reference).)
Multi-step speed command 2
Jog frequency selection (given priority over multi-step speed command)
Combining Multi-Step Speed References and Multi-Function Digital Inputs
The frequency reference can be changed by combining the ON/OFF status of S4 to S6 (multi-function digital input terminals). The following table shows the possible combinations.
Speed
3
4
1
2
5
Terminal S5
Multi-step Speed
Command 1
OFF
ON
OFF
ON
–
Terminal S6
Multi-step Speed
Command 2
OFF
OFF
ON
ON
–
Terminal S7
Jog Frequency
Selection
OFF
OFF
OFF
OFF
ON
*1
Selected Frequency
Frequency reference 1, d1-01, master speed frequency
Frequency reference 2, d1-02, auxiliary frequency
Frequency reference 3, d1-03
Frequency reference 4, d1-04
Jog frequency d1-17
*1. Terminal S6's jog frequency selection is given priority over multi-step speed commands.
Setting Precautions
When setting analog inputs to step 1 and step 2, observe the following precautions.
•
When setting terminal A1's analog input to step 1 set b1-01 to 1, when setting d1-01 (Frequency Reference
1) to step 1 set b1-01 to 0.
•
When setting terminal A2's analog input to step 2 set H3-09 to 2 (auxiliary frequency reference). When setting d1-02 (Frequency Reference 2) to step 2 set H3-09 to 1F (do not use analog inputs).
6-7
6-8
Connection Example and Time Chart
The following diagram shows a time chart and control circuit terminal connection example during a 9-step operation.
Inverter
Forward/stop
Reverse/stop
Fault reset
Multi-step command 1
Multi-step command 2
Jog frequency
External fault
SN
Digital input neutral
Frequency reference
Fig 6.9 Control Circuit Terminal During 5-step Operation
Frequency reference 3
Frequency reference 2
Frequency reference 1
Frequency reference 4
Jog frequency
Forward/stop
Multi-step speed command 1
Multi-step speed command 2
OFF
OFF
Jog frequency selection
OFF
ON
ON
ON
OFF
ON
Fig 6.10 Multi-step speed command/Jog Frequency Selection Time Chart
Note:
•
The multifunction input setting “Jog Frequency 2” (69) can be used for jog frequency selection when a
3-wire control is used for the control circuit. If it is selected while the inverter is initialized to 2-wire control an OPE03 alarm will be displayed.
Run Command
Run Command
This section explains input methods for the run command.
Selecting the Run Command Source
Set parameter b1-02 to select the source for the run command.
Related Parameters
Parameter
Number
Name b1-02 Operation method selection
Setting
Range
0 to 3
Factory
Setting
1
Change during
Operation
No
Access
Level
Q
Performing Operations Using a Digital Operator
When b1-02 is set to 0, the Inverter can be operated using the Digital Operator keys (RUN, STOP, and FWD/
REV). For details on the Digital Operator, refer to
Chapter 3, Digital Operator and Modes
.
Performing Operations Using Control Circuit Terminals
When b1-02 is set to 1, Inverter operation can be performed using the control circuit terminals.
Performing Operations Using a 2-wire Control
The factory setting is set to a 2-wire control. When control circuit terminal S1 is set to ON, forward operation will be performed, and when S1 is turned OFF, the Inverter will stop. In the same way, when control circuit terminal S2 is set to ON, reverse operation will be performed, and when S2 is turned OFF, the Inverter will stop.
Inverter
Forward/Stop
Reverse/Stop
SN
Digital input neutral
Fig 6.11 2-Wire Control Wiring Example with Positive Logic
6-9
6-10
Performing Operations Using 3-Wire Control
When any parameter from H1-01 to H1-05 (multi-function digital input terminals S3 to S7) is set to 0, terminals S1 and S2 are used for a 3-wire control, and the multi-function input terminal that has been set to 0 works as a forward/reverse selection command terminal.
When the Inverter is initialized for 3-wire control with A1-03, multi-function input 3 becomes the input terminal for the forward/reverse run command.
Stop switch
(NC contact)
Operation switch
(NO contact)
Run command (operates when ON)
SN
Stop command (stopped when ON)
Forward/reverse command (multi-function input)
Digital input neutral
Fig 6.12 3-Wire Control Wiring Example
Run command
Stop command
Forward/reverse command
50 ms min.
Can be either ON or OFF
OFF
(stopped)
OFF (forward)
ON (reverse)
Motor speed
Stop Forward Reverse
Fig 6.13 Three-wire Control Time Chart
Stop Forward
NOTE
Use a control circuit that turns ON terminal S1 for 50 ms or longer for the run command. This will make the run command self-holding in the Inverter.
Stopping Methods
Stopping Methods
This section explains methods of stopping the Inverter.
Selecting the Stopping Method when a Stop Command is Input
There are four methods of stopping the Inverter when a stop command is input:
•
Deceleration to stop
•
Coast to stop
•
DC braking stop
•
Coast to stop with timer
Set parameter b1-03 to select the Inverter stopping method.
Related Parameters
Parameter
Number
Name b1-03 Stopping method selection b2-01
Zero speed level (DC injection braking starting frequency) b2-02 DC injection braking current b2-04 DC injection braking time at stop
Setting
Range
0 to 3
0.0 to
10.0
0 to
100
0.00
to
10.00
Factory
Setting
0
0.5 Hz
50%
0.50 sec.
Change during
Operation
No
No
No
No
Access
Level
Q
A
A
A
6-11
6-12
Deceleration to Stop
If the stop command is input (the run command is turned OFF) when b1-03 is set to 0, the motor decelerates to stop according to the deceleration time that has been set. (Factory setting: C1-02 (Deceleration Time 1)).
If the output frequency when decelerating to stop falls below b2-01, the DC injection brake will be applied using the DC current set in b2-02 for the time set in b2-04.
For deceleration time settings, refer to
page 6-15, Setting Acceleration and Deceleration Times
Run Command
ON OFF
Output
Frequency
Decelerates to stop using the active deceleration time
DC injection brake
DC injection brake time at stop (b2-04)
Fig 6.14 Deceleration to Stop
Coast to Stop
If the stop command is input (i.e., the run command is turned OFF) when b1-03 is set to 1, the Inverter output voltage is switched off. The motor coasts to stop.
Run command
ON OFF
Output frequency
Inverter output frequency interrupted
Fig 6.15 Coast to Stop
NOTE
After the stop command is input, run commands are ignored until the Minimum Baseblock Time
(L2-03) has elapsed.
DC Braking Stop
After the stop command is input and the minimum baseblock time (L2-03) has elapsed, DC injection will be applied to the motor. The applied DC injection current is programmed in parameter b2-02. The DC injection brake time depends on the set value of b2-04 and on the output frequency at the moment the stop command is input.If the output frequency was higher than 10% of the maximum output frequency (E1-04) the DC injection time is lengthened like shown in the figure below.
DC injection brake time
Run command
Output frequency
ON
OFF b2-04 x 10
Minimum baseblock time (L2-03)
Inverter output voltage interrupted
DC injection brake
DC injection brake time b2-04
10%
Fig 6.16 DC Injection Braking Stop
Output frequency at stop command input
100% (maximum output frequency
NOTE
Lengthen the Minimum Baseblock Time (L2-03) when an overcurrent (OC) occurs during stopping.
Stopping Methods
Coast to Stop with Timer
If the stop command is input (i.e., the run command is turned OFF) when b1-03 is set to 3, the Inverter output is switched off so that the motor coasts to stop. After the stop command is input, run commands are ignored until the time T has elapsed. The time T depends on the output frequency when the stop command is input and on the deceleration time.
Run command
Operation wait time T
Deceleration time
(e.g., C1-02)
Output frequency
Inverter output voltage interrupted
Operation wait time T
Minimum baseblock time (L2-03)
Minimum output frequency
Fig 6.17 Coast to Stop with Timer
Output frequency at stop command input
100% (Maximum output frequency)
Using the DC Injection Brake
Set parameter b2-03 to apply DC injection to the motor, before it starts to accelerate. Applying DC injection at start will stop the motor before starting if it was coasting through inertia or wind mill effect.
Set b2-03 to 0 to disable the DC injection brake at start.
Set parameter b2-04 to apply a DC injection brake to the motor at stopping. It prevents the motor from coasting when it would not be stopped completely using the normal deceleration. This can occur if the inertia is very high. The DC injection brake can be disabled by setting b2-04 to 0.
Set the DC injection brake current using b2-02.
Related Parameters
Parameter
Number
Name b2-01 DC injection braking starting frequency b2-02 DC injection braking current b2-03 DC injection braking time at start b2-04 DC injection braking time at stop
Setting
Range
0.0 to
10.0
Factory
Setting
0.5 Hz
0 to
100
0.00
to
10.00
0.00 to
10.0
50%
0.00 sec.
0.50 sec.
Change during
Operation
No
No
No
No
Access
Level
A
A
A
A
6-13
6-14
Using an Emergency Stop
Set a multi-function input terminal (H1-01 to H1-05) to 15 or 17 (emergency stop) to decelerate to stop using the deceleration time set in C1-09. If inputting the emergency stop with an NO contact, use setting 15, and if inputting the emergency stop with an NC contact, use setting 17.
After the emergency stop command has been input, operation cannot be restarted until the Inverter has stopped. To cancel the emergency stop, turn OFF the run command and emergency stop command.
Related parameters
Parameter
Number
C1-09 Emergency stop time
Name
Setting
Range
0.0 to
6000.0
Factory
Setting
10.0 sec.
Change during
Operation
No
Access
Level
A
Acceleration and Deceleration Characteristics
Acceleration and Deceleration Characteristics
This section explains the acceleration and deceleration characteristics of the Inverter.
Setting Acceleration and Deceleration Times
Acceleration time indicates the time to increase the output frequency from 0% to 100% of the maximum output frequency (E1-04). Deceleration time indicates the time to decrease the output frequency from 100% to
0% of (E1-04). The accel./decel. times 1 are used with the factory setting, the accel./decel. times 2 can be selected using a multifunction input.
Related Parameters
Parameter
Number
C1-01 Acceleration time 1
C1-02 Deceleration time 1
C1-03 Acceleration time 2
C1-04 Deceleration time 2
Name
C1-11 Acceleration/deceleration time switching frequency
C2-01 S-curve characteristic time at acceleration start
C2-02 S-curve characteristic time at acceleration end
Setting
Range
0.0 to
6000.0
Factory
Setting
10.0 sec.
Change during
Operation
Yes
Yes
Yes
Yes
0.0 to
200.0
0.0 Hz
0.00 to
2.50
0.20 sec.
No
No
0.00 to
2.50
0.20 sec.
No
Access
Level
A
A
Q
Q
A
A
A
Switching Acceleration and Deceleration Time Using Multi-Function Input Terminal
Commands
Two different acceleration times and deceleration times can be set. When one multi-function input terminal
(H1) is set to 7 (acceleration/deceleration time selection 1), the acceleration/deceleration time can even be switched during operation by changing the ON/OFF status of this terminal.
The following table shows the acceleration/deceleration time switching combinations.
Acceleration/Deceleration Time
Selection 1 Terminal
OFF
ON
Acceleration Time
C1-01
C1-03
Deceleration Time
C1-02
C1-04
Switching Acceleration and Deceleration Time Automatically
Use this setting when the acceleration/deceleration time should be switched automatically depending on the output frequency.
When the output frequency reaches the set value in C1-11, the Inverter switches the acceleration/deceleration time automatically as shown in the following diagram.
6-15
6-16
Set C1-11 to a value other than 0.0 Hz. If C1-11 is set to 0.0 Hz, the function will be disabled.
Output frequency
Acceleration/ deceleration time switching frequency
(C1-11)
C1-03 C1-01 C1-02 C1-04
When output frequency
≥ C1-11, acceleration and deceleration are performed using
Acceleration/deceleration Time 1 (C1-01, C1-02).
When output frequency < C1-11, acceleration and deceleration are performed using
Acceleration/deceleration Time 2 (C1-03, C1-04).
Fig 6.18 Acceleration/deceleration Time Switching Frequency
Entering S-curve Characteristics in the Acceleration and Deceleration Time
By performing acceleration and deceleration using an S-curve pattern, shock at start and stop of the machine can be reduced
Two S-curve characteristic times can be set: At acceleration start and at acceleration end. For deceleration start and end the S-curve times are fixed to 0.2 sec.
NOTE
When S-curve is set, calculate acceleration/deceleration time as follows:
Accel.Time
=
C2-01 +
2
C2-02
+ C1-01/03
Decel. Time = 0.2 sec + C1-02/04
Acceleration and Deceleration Characteristics
Setting Example
The S-curve characteristic when switching operation (forward/reverse) is shown in the following diagram.
Forward
Reverse
Output frequency
Fig 6.19 S-curve Characteristic during Operation Switching
Preventing the Motor from Stalling During Acceleration
(Stall Prevention During Acceleration Function)
The Stall Prevention During Acceleration function prevents the motor from stalling if a heavy load is applied to the motor, or sudden rapid acceleration is performed.
If L3-01 is set to 1 (enabled) and the Inverter output current reaches 85 % of the set value in L3-02, the acceleration rate will begin to slow down. When L3-02 is exceeded, the acceleration will stop.
If L3-01 is set to 2 (optimum adjustment), the motor accelerates so that the current is held at a level of 50 % of the inverter rated current. With this setting, the acceleration time setting is ignored.
Related Parameters
Parameter
Number
Name
L3-01 Stall prevention selection during acceleration
Setting
Range
0 to 2
Factory
Setting
1
Change during
Operation
No
Access
Level
A
L3-02 Stall prevention level during acceleration 0 to 200 120% No A
6-17
6-18
Time Chart
The following figure shows the frequency characteristics when L3-01 is set to 1.
Output current
Stall level during acceleration
L3-02
85% of
L3-02
Time
Output frequency
*1 *2 *3
*1 The acceleration rate is lowered
*2 The acceleration rate is stopped to reduce the output current
*3 The acceleration is restarted
Time
Fig 6.20 Time Chart for Stall Prevention During Acceleration
Setting Precautions
•
If the motor capacity is small compared to the Inverter capacity or if the inverter is operated using the factory settings and the motor stalls, lower the set value of L3-02.
•
If using the motor in the field weakening range, L3-02 will be automatically lowered to prevent stalling. It will be reduced to a fixed value of 50 % of the inverter rated current.
•
Set the parameters as a percentage taking the inverter rated current to be 100%.
Stall Prevention Level during Acceleration
L3-02
50% of inverter rated current
E1-06
Base Frequency (FA)
Output frequency
Fig 6.21 Stall Prevention Level and Limit During Acceleration
Acceleration and Deceleration Characteristics
Stall Prevention During Deceleration Function
This function automatically lengthens the deceleration time with respect to the DC-bus voltage to avoid overvoltage tripping.
Related Parameters
Parameter
Number
E1-01 Input voltage setting
Name
Setting
Range
155 to
255
*1
Factory
Setting
200
L3-04
Stall prevention selection during deceleration function selection
0 to 2 1
*1. Value for 200 V class Inverters are shown. For a 400 V class inverter the values have to be doubled.
Change during
Operation
No
No
Access
Level
Q
A
Setting the Stall Prevention Selection During Deceleration (L3-04)
There are four different settings selectable for L3-04.
L3-04=0: This setting disables the stall prevention function during deceleration. The motor will be decelerated using the time set in C1-02 (C1-04). If the load inertia is very high and an OV fault occurs during deceleration a braking option has to be used or the deceleration time has to be lengthened.
L3-04=1: This setting enables the stall prevention during deceleration. The inverter tries to decelerate within the set deceleration time. It also observes the DC bus voltage. If the DC bus voltage reaches the stall prevention level the deceleration is stopped and the output frequency is held. When the DC bus voltage falls below the stall prevention level the deceleration will be continued.
L3-04=2: This setting enables the stall prevention during deceleration. The deceleration time set as C1 is taken as reference. The function automatically tries to optimize the deceleration time by observing the DC bus voltage and shortening the deceleration time. The function does not lengthen the deceleration time, i.e. if C1-
is set too short OV may occur.
Setting Example
An example of stall prevention during deceleration when L3-04 is set to 1 is shown below.
Output frequency Deceleration time controlled to prevent overvoltage
Time
Deceleration time
(set value)
Fig 6.22 Stall Prevention During Deceleration Operation
6-19
6-20
Setting Precautions
•
The stall prevention level during deceleration differs depending on the inverter rated voltage and input voltage. Refer to the following table for details.
Inverter Rated/Input Voltage
200 V class
E1-01
≥ 400 V
400 V class
E1-01 < 400 V
Stall Prevention Level during Deceleration
380 VDC
760 VDC
660 VDC
•
When using a braking option, be sure to set parameter L3-04 to 0.
Adjusting Frequency References
Adjusting Frequency References
Adjusting Analog Frequency References
The analog reference values can be adjusted using the gain and bias functions for the analog inputs.
Related Parameters
Parameter
Number
H3-02
H3-03
H3-08
H3-09
H3-10
H3-11
H3-12
Name
Frequency reference terminal A1 input gain
Frequency reference terminal A1 input bias
Multi-function analog A2 signal level selection
Multi-function analog A2 function selection
Multi-function analog A2 input gain
Multi-function analog A2 input bias
Analog input filter time constant
Setting
Range
0.0 to
1000.0
-100.0
to +100.0
0, 2, 3
Factory
Setting
100.0%
0.0%
0 to 16
0.0 to
1000.0
-100.0
to +100.0
0.00 to
2.00
0 or 1
2
*1
0
100.0%
0.0%
0.30 sec.
0 H3-13 Terminal A1/A2 switching
*1. The setting is automatically switched to “B” when the PI controller is enabled
*2. Parameter is moved to Quick Programming Mode when PI controller is enabled.
Change during
Operation
Yes
Yes
No
No
Yes
Yes
No
No
Access
Level
A
A
A
*2
A
A
A
A
A
Adjusting Analog Frequency Reference Using Parameters
The frequency reference can be input from the control circuit terminals using analog voltage or current signals
(analog input A2 only).
The input signal levels can be selected using
•
H3-01 for the analog input A1
•
H3-08 for the analog input A2
Adjustments to the signals can be made using:
•
H3-02 (Gain) and H3-03 (Bias) if analog input A1 is selected to be the frequency reference input
•
H3-10 (Gain) and H3-11 (Bias) if analog input A2 is selected to be the frequency reference input
for adjusting the signal using the gain and bias functions.
Frequency reference Frequency reference
Terminal A1 input
Terminal A1 input voltage
0V (4 mA/0 mA)
Terminal A2 input
Fig 6.23 Terminals A1 and A2 Inputs
Terminal A2 input voltage (current)
6-21
6-22
Adjusting Frequency Bias Using an Analog Input
Frequency Bias (Setting: 0)
When parameter H3-09 is set to 0 (Frequency Bias), the frequency equivalent to the terminal A2 input voltage is added to the analog master frequency input at terminal A1 as a bias.
Frequency bias
Multi-function analog input terminal A2 input level
0V (4 mA/0 mA)
Fig 6.24 Frequency Bias Adjustment (Terminal A2 Input)
For example, if H3-02 is 100%, H3-03 is 0%, and terminal A2 is set to 1 V, the frequency reference when 0 V is input to A1 will be 10% of the maximum output frequency (E1-04).
Frequency reference
H3-02
10 %
Bias
0 V 10 V
Terminal A1 input voltage
Fig 6.25 Example Operation for Frequency Bias via Terminal A2
Frequency Bias 2 (Setting: D)
In contrary to the frequency bias function (H3-09=0) the frequency bias 2 function adds the analog bias value to any master frequency value, either from the analog input, MEMOBUS communication or option boards.
The bias value is not applied to multi-step speed references using the d1 parameters.
Setting Precautions
•
When the PI controller is enabled the function setting for analog input A2 is automatically switched to PI feedback.
•
If the Master Frequency Reference has to be input with a current signal (0/4 to 20 mA) the functionality of analog input A1 and A2 can be exchanged using parameter H3-13.
•
If the analog input A2 is used with a current signal ensure the proper setting of switch S1. Refer to
32, Switch S1 - Standard Terminal Board
.
•
In case a voltage reference signal is noisy a analog input filter time can be adjusted. By default a filter time of 0.3 sec. is set.
Adjusting Frequency References
Jump Frequency Function (Operation Avoiding Resonance)
•
This function allows the prohibition or “jumping” of certain frequencies within the Inverter’s output frequency range so that the motor can operate without resonant oscillations caused by some machine systems.
•
It can also be used for deadband control.
Related Parameters
Parameter
Number d3-01 Jump frequency 1 d3-02 Jump frequency 2 d3-03 Jump frequency 3
Name
Setting
Range
0.0 to
200.0
Factory
Setting
0.0 Hz
0.0 Hz
0.0 Hz
Change during
Operation
No
No
No d3-04 Jump frequency width
0.0 to
20.0
1.0 Hz No
The relationship between the output frequency and the jump frequency reference is as follows:
Output frequency
Access
Level
A
A
A
A
Frequency reference descending
Jump frequency width d3-04
Frequency reference ascending
Jump frequency width d3-04
Jump frequency width d3-04
Jump frequency reference
Jump frequency 3
(d3-03)
Jump frequency 2
(d3-02)
Jump
frequency 1
(d3-01)
Fig 6.26 Jump Frequency
Setting Precautions
•
Set the jump frequencies according to the following formula: d3-01
≥ d3-02 ≥ d3-03.
•
When parameters d3-01 to d3-03 are set to 0 Hz, the jump frequency function is disabled.
6-23
6-24
Speed Limit
(Frequency Reference Limit Function)
This section explains how to limit the motor speed.
Limiting Maximum Output Frequency
If the motor should not rotate above a given frequency, use parameter d2-01.
Set the upper limit value of the frequency reference as a percentage, taking E1-04 (Maximum Output Frequency) to be 100%.
Related Parameters
Parameter
Number
Name d2-01 Frequency reference upper limit
Setting
Range
0.0 to
110.0
Factory
Setting
100.0%
Change during
Operation
No
Access
Level
A
Limiting Minimum Frequency
If the motor should not rotate below a given frequency, use parameters d2-02 or d2-03.
There are two methods of limiting the minimum frequency, as follows:
•
Adjust the minimum level for all frequencies.
•
Adjust the minimum level for the master speed frequency (i.e., the lower levels of the jog frequency, multistep speed frequency, and auxiliary frequency will not be adjusted).
Related Parameters
Parameter
Number
Name d2-02 Frequency reference lower limit d2-03 Master speed reference lower limit
Setting
Range
0.0 to
110.0
0.0 to
110.0
Factory
Setting
0.0%
Change during
Operation
No
Access
Level
A
0.0% No A
Frequency Detection
Frequency Detection
Speed Agreement Function
There are four different types of frequency detection methods available. The digital multifunction outputs M1 to M4 can be programmed for this function and can be used to indicate a frequency detection or agreement to any external equipment.
Related Parameters
Parameter
Number
Name
L4-01 Speed agreement detection level
L4-02 Speed agreement detection width
Setting
Range
0.0 to
200.0
0.0 to
20.0
Factory
Setting
0.0 Hz
2.0 Hz
Change during
Operation
No
No
Access
Level
A
A
•
With L4-01 an absolute speed agreement level is set, i.e. a speed agreement is detected in both directions
(FWD and REV).
Multifunction Output Settings: H2-01 to H2-02
(M1 – M4 function selection)
The table below shows the necessary H2-01 and H2-02 parameter setting for each of the speed agreement functions.
Set Value
2
Function
3
4
5 f ref
= f out
Agree f out
= f set
Agree
Frequency detection 1
Frequency detection 2
6-25
6-26
Time Charts
The following table shows the time charts for each of the speed agreement functions.
Related parameter f ref
= f out
Agree
L4-01: Speed Agree Level
L4-02: Speed Agree Width
Freq. Ref.
f out
= f set
Agree
L4-02 f ref
= f out
Agree
Output
Frequency
Freq. Ref.
L4-02 f ref
= f out
Agree OFF
ON
(Multi-function output setting = 2) f out
= f set
Agree
(ON at the following conditions during frequency agree)
L4-02
L4-01
Output
Frequency
L4-01
L4-02
Frequency
Detection f out
= f ref
Agree 1
ON OFF
(Multi-function output setting = 3)
Frequency (FOUT) Detection 1
(L4-01 > | Output frequency |)
L4-02
L4-01
Output
Frequency
L4-01
L4-02
Freq. Detection 1
ON OFF
(Multi-function output setting = 4)
Frequency (FOUT) Detection 2
(L4-01 < | Output frequency |)
L4-02
L4-01
Output
Frequency
L4-01
L4-02
Freq. Detection 2 OFF ON
(Multi-function output setting = 5)
Improved Operating Performance
Improved Operating Performance
This section explains functions for improving motor operating efficiency.
Torque Compensation for Sufficient Torque at Start and Low-speed Operation
The torque compensation function detects a rising motor load, and increases the output torque.
The inverter calculates the motor primary loss voltage and adjusts the output voltage (V) to compensate insufficient torque at startup and during low-speed operation. The compensation voltage is calculated as follows:
Motor primary voltage loss
× parameter C4-01.
Related Parameters
Parameter
Number
Name
C4-01 Torque compensation gain
C4-02 Torque compensation delay time constant
Setting
Range
0.00 to
2.50
0 to
10000
Factory
Setting
Change during
Operation
1.00
200 msec
Yes
No
Access
Level
A
A
Adjusting Torque Compensation Gain (C4-01)
Normally, there is no need to change this setting.
Adjust the torque compensation gain under the following circumstances.
•
If the cable is very long, increase the set value.
•
If the motor capacity is smaller than the Inverter capacity (max. applicable motor capacity), increase the set value.
•
If the motor is vibrating, reduce the set value.
Adjust this parameter so that the output current during low-speed rotation does not exceed the Inverter rated output current range.
Adjusting the Torque Compensation Primary Delay Time Constant (C4-02)
Set the torque compensation function primary delay in milliseconds.
Normally, there is no need to change this setting. Adjust the parameter under the following circumstances:
•
If the motor is vibrating, increase the set value.
•
If the motor response is low, decrease the set value.
6-27
6-28
Hunting Prevention Function
The hunting prevention function suppresses hunting when the motor is operating with a light load.
If high response has the priority to vibration suppression this function should be disabled (n1-01 = 0).
Related Parameters
Parameter
Number
Name n1-01 Hunting prevention function selection n1-02 Hunting prevention gain
Setting
Range
0 or 1
0.00 to
2.50
Factory
Setting
1
1.00
Change during
Operation
No
No
Access
Level
A
A
Adjusting the Hunting Prevention Gain (n1-02)
Normally it is not necessary to change this setting. Adjust the value under the following circumstances:
•
If vibrations occur under light load condition increase the setting.
•
If the motor stalls reduce the setting.
Machine Protection
Machine Protection
Preventing Motor Stalling During Operation
Stall prevention during operation prevents the motor from stalling by automatically lowering the Inverter's output frequency when a transient overload occurs while the motor is operating at a constant speed.
If the Inverter output current continues to exceed the setting in parameter L3-06 for 100 ms or longer, the motor speed is reduced. Set whether to enable or disable the stall prevention using parameter L3-05. Set the according deceleration times using C1-02 (Deceleration time 1) or C1-04 (Deceleration Time 2).
If the Inverter output current reaches the set value in L3-06 – 2%, the motor will accelerate again to the set frequency.
Related Parameters
Parameter
Number
L3-05
Name
Stall prevention selection during running function selection
L3-06 Stall prevention level during running
Setting
Range
0 to 2
Factory
Setting
1
Change during
Operation
No
Access
Level
A
30 to 200 120% No A
6-29
6-30
Load Detection
If an excessive load is applied to the machinery (overload) or the load suddenly drops (loss of load), an alarm signal can be output via one of the output terminal M1-M2 or M3-M4.
To use the load detection function, set B or 17 (overload/loss of load detection NO/NC) in one of the parameter H2-01 and H2-02 (terminals M1-M2 and M3-M4 function selection).
The load detection level is set as a current level taking the inverter rated output current as 100%.
Related Parameters
Parameter
Number
Name
L6-01 Torque detection selection
L6-02 Torque detection level
L6-03 Torque detection time
Setting
Range
0 to 8
0 to 300
0.0 to
10.0
Factory
Setting
6
15%
10.0 sec.
Change during
Operation
No
No
No
Access
Level
A
A
A
Multi-function Output (H2-01 and H2-02)
Set Value
B
17
Function
Load detection NO
(NO contact: Overload or loss of load detected when output is ON)
Load detection NC
(NC contact: Overload or loss of load detected when output is OFF)
Machine Protection
L6-01 Set Value and Digital Operator Display
The relationship between alarms displayed on the Digital Operator when overload or loss of load is detected and the setting in L6-01 is shown in the following table.
Set
Value
0
Function
Operator
Overload/Undertorque Detection 1
–
Inverter condition
–
1
2
3
4
5
6
7
8
Load detection disabled
Overload detection only at speed agree, the operation is continued, a warning is output.
Overload detection continuously during operation, operation continues, a warning is output.
Overload detection only at speed agree, motor coasts to stop, Inverter is in fault condition.
Overload detection continuously during operation, motor coasts to stop, Inverter is in fault condition.
Loss of load detection only at speed agree, the operation is continued, a warning is output.
Loss of load detection continuously during operation, operation continues, a warning is output.
Loss of load detection only at speed agree, motor coasts to stop, Inverter is in fault condition.
Loss of load detection continuously during operation, motor coasts to stop, Inverter is in fault condition.
OL3 flashes
OL3 flashes
OL3 lights up
OL3 lights up
LL3 flashes
LL3 flashes
LL3 lights up
LL3 lights up
Alarm
Alarm
Fault
Fault
Alarm
Alarm
Fault
Fault
Setting Example
The following diagram shows the time chart for overload and loss of load detection.
•
Overload Detection
Motor current (output torque)
* Overload detection switch off bandwidth is approximately 10% of the Inverter rated output current.
L6-02
L6-03
L6-03
Load detection 1 NO
Fig 6.27 Example Operation for Overload Detection
6-31
6-32
•
Loss of Load Detection
Motor current (output torque)
L6-02
* Loss of Load detection switch off bandwidth is approximately 10% of the Inverter rated output current.
L6-03
L6-03
Load Detection NO
Fig 6.28 Example Operation for Loss of Load Detection
Machine Protection
Motor Overload Protection
The motor can be protected from overload using the Inverter's built-in electronic thermal overload relay function (I²t calculation).
Related Parameters
Parameter
Number
E2-01 Motor rated current
Name
Setting
Range
0.32 to
6.40
*1
Factory
Setting
1.90 A
*2
Change during
Operation
No
Access
Level
Q
L1-01
L1-02
Motor protection selection
Motor protection time constant
0 to 3
0.1 to
5.0
1
1.0 min
No
No
*1. The setting range is 10% to 200% of the Inverter rated output current. The value for a 200 V class Inverter of 0.4kW is given.
*2. The factory setting depends on the Inverter Capacity. The value for a 200 V class Inverter of 0.4 kW is given.
A
A
Multi-Function Outputs (H2-01 to H2-02)
Set Value
1F
Function
During motor overload (OL1, including OH3) pre-alarm (ON: 90% or more of the detection level)
Setting Motor Rated Current (E2-01)
Set the rated current value on the motor nameplate in parameters E2-01. This set value is the base current for the internal thermal overload calculation.
Setting Motor Overload Protection Characteristics (L1-01)
Set the overload protection function in L1-01 according to the application.
Set L1-01 to:
0: to disable the thermal motor protection function.
1: to enable the thermal motor protection for a fan cooled general purpose motor (self-cooled).
2: to enable the thermal motor protection for Inverter motors (forced or externally cooled)
3: to enable the thermal motor protection for a special vector motor (externally cooled).
Application Precautions
•
If a multi-function digital output is programmed to 1F the output will stay switched ON as long as the motor is overloaded. When the motor has been stopped to cool down the output will be switched OFF as soon as the Inverter’s I² t calculation falls below 90% of the detection level.
•
The multi-function digital output programmed to 1F will also switch OFF when the Inverter itself is in fault condition. The fault has to be reset manually.
6-33
6-34
Setting Motor Protection Operation Time (L1-02)
Set the motor protection operation time in L1-02.
The motor protection operation time is the time for that the motor can handle a 150% overload when it was running with the rated load before (i.e. operating temperature was reached before applying the 150% overload). Set the motor protection operation time in L1-02. The factory setting is 60 sec.
The following diagram shows an example of the characteristics of the electronic thermal protection operation time (L1-02 = 1.0 min., operation at 50 Hz, general-purpose motor characteristics, when L1-01 is set to 1)
Operating time (min.)
Cold start
Hot start
Motor current (%)
(E2-01 is set to 100%)
Fig 6.29 Motor Protection Operation Time
Setting Precautions
•
If multiple motors are connected to one inverter, set parameter L1-01 to 0 (disabled). To protect each of the motors, use a control circuit that switches off the inverter output when one of the motors overheats.
•
With applications where the power supply is often turned ON and OFF, there is a risk that the motor cannot be protected even if this parameter has been set to 1 (enabled), because the internally calculated thermal value will be reset after inverter power supply switch off.
•
For safe overload tripping, set the value in parameter L1-02 to a low setting.
•
When using a general-purpose motor (standard motor), the cooling ability will be lowered by f
1/4
(frequency). Consequently, a low output frequency may cause motor overload protection (OL1) to occur, even when the output current is below the rated current. If the motor is operated at the rated current at a low frequency, use a special motor which is externally cooled.
Setting the Motor Overload Pre-Alarm
To enable the Motor overload pre-alarm enable the motor overload protection function (i.e., L1-01 must be set to 1) and set H2-01 or H2-02 (multi-function output terminals M1-M2 and M3-M4 function selection) to 1F
(motor overload OL1 pre-alarm). If the electronic thermal value reaches minimum 90% of the overload detection level, the output terminal that has been set will be turned ON.
Application Precautions
With applications where the power supply is often turned ON and OFF, there is a risk that the motor cannot be protected even if this parameter has been set to 1 to 3, because the thermal value will be reset.
Machine Protection
Motor Overheat Protection Using PTC Thermistor Inputs
This function provides a motor overheating protection using a thermistor (PTC characteristic – Positive Temperature Coefficient) that is built into the windings of each motor phase.
Related Parameters
Parameter
Number
Name
L1-03 Alarm operation selection during motor overheating
Setting
Range
0 to 3
Factory
Setting
3
Change during
Operation
No
Access
Level
A
L1-04 Motor overheating operation selection
L1-05 Motor temperature input filter time constant
0 to 2 1
0.00 to
10.00
0.20 sec.
No
No
A
A
PTC Thermistor Characteristics
The following diagram shows the characteristics of the PTC thermistor temperature to the resistance value.
The shown resistance value is for one motor phase. Normally the 3 resistors (1 for each phase) are connected in series
Class F Class H
Resistance (Ohms)
Tr: Temperature threshold value
Temperature
Fig 6.30 PTC Thermistor Temperature-Resistance Value Characteristics
6-35
6-36
Operation during Motor Overheating
The operation when the motor overheats can be selected using the parameters L1-03 and L1-04. Set the motor temperature input filter time parameter in L1-05. If the motor overheats, the OH3 and OH4 error codes will be displayed on the Digital Operator.
Fault Codes If the Motor Overheats
Fault Code
OH3
OH4
Details
Inverter stops or continues to operate, according to the setting in L1-03.
Inverter stops according to the setting in L1-04. The fault relay is activated
By setting H3-09 (Multi-function Analog Input Terminal A2 Function Selection) to E (Motor temperature input) the motor temperature can be detected and OH3 respectively OH4 can be output if the motor overheats.
The terminal connections that are to be used are shown in
.
Inverter
Multi-function digital input
Multi-function digital output
Multi-function digital output
Branch resistance
18 k
Ω *1
Fault relay output
PTC thermistor
* 1. The resistance value of 18 k
Ω is only valid when a 3-phase PTC with the characteristic
shown on the previous page is used.
Fig 6.31 Terminal Connections for Motor Overheating Protection
Setting Precautions
Because this function uses a voltage signal to terminal A2, pin 2 of the DIP-switch S1 on the control terminal board has to be turned to OFF for A2 voltage input. The factory setting is ON (A2 current input). Refer to
Chapter 2, Switch S1 - Standard Terminal Board
.
For the same reason the parameter H3-08 (analog input terminal A2 signal level) has to be set to 0 (0-10V input).
Machine Protection
Limiting Motor Rotation Direction and Output Phase Rotation
If the motor reverse rotation is prohibited, a reverse run command will not be accepted, even if it is input. Use this setting for applications in which reverse motor rotation can cause problems (e.g., fans, pumps, etc.)
It is also possible to change the output phase order by changing b1-04 to 2 or 3. This much easier and faster than changing the wiring if the motor rotational direction is wrong.
Related Parameters
Parameter
Number
Name b1-04 Prohibition of reverse operation
Setting
Range
0 to 3
Factory
Setting
0
Change during
Operation
No
Access
Level
A
Settings
•
Setting 0: Both operation directions are enabled for the Inverter.
•
Setting 1: Reverse operation is not enabled, a reverse RUN command is disregarded.
•
Setting 2: Both operation directions are enabled, two output phases are exchanged
•
Setting 3: Reverse operation is not enabled, a reverse RUN command is disregarded. Additional two output phases are exchanged.
6-37
6-38
Automatic Restart
This section explains functions for continuing or automatically restarting Inverter operation after a momentary power loss.
Restarting Automatically After Momentary Power Loss
After a momentary power loss, the Inverter can be restarted automatically to continue motor operation.
To restart the Inverter after power is recovered, set L2-01 to 1 or 2.
If L2-01 is set to 1, the inverter will restart, when power is recovered within the time set in L2-02. If the power loss time exceeds the time set in L2-02, an UV1 fault (DC bus undervoltage) will be detected.
If L2-01 is set to 2, the inverter will restart, when the main power supply is recovered as long as the control power supply (i.e., power supply to the control circuit) is maintained. Consequently, alarm UV1 (DC bus undervoltage) will not be detected. Nevertheless, UV alarm is displayed.
Related Parameters
Parameter
Number
Name
L2-01 Momentary power loss detection
L2-02
L2-03
L2-04
L2-05
Momentary power loss ridethru time
Min. baseblock (BB) time
Voltage recovery time
Undervoltage (UV) detection level
Setting
Range
0 to 2
0 to 25.5
0.1 to 5.0
0.0 to
5.0
150 to
210
*2
Factory
Setting
0
0.1 sec.
*1
0.1 sec.
0.3 sec.
190 VDC
Change during
Operation
No
No
No
No
No
*1. The factory setting depends on the Inverter capacity. The value for a 200 V class Inverter of 0.4kW is given.
*2. Values for 200 V class Inverters are shown. For a 400 V class Inverter the values have to be doubled.
Access
Level
A
A
A
A
A
Setting Precautions
•
Fault output signals are not output during momentary power loss recovery.
•
To continue Inverter operation after power has been restored, ensure that the RUN command stays ON during the power loss
•
L2-04 sets an acceleration time for the output voltage (from 0 V to normal voltage). After the power supply has returned the output voltage will be increased to the set value using the time set in L2-04.
•
L2-05 sets the level at which UV is detected.
Automatic Restart
Speed Search
The speed search function finds the actual speed of a motor that is coasting and then starts smoothly from that speed. It is also activated after momentary power loss detection when L2-01 is set to 1 or 2.
Related Parameters
Parameter
Number
Name
Setting
Range
Factory
Setting b3-01
Speed search selection (current detection or speed calculation)
0 to 3 2 b3-02 b3-03 b3-05
Speed search wait time (current detection or speed calculation) b3-14 Bi-directional speed search selection
L2-03 Min. baseblock time
L2-04
Speed search operating current (current detection)
Speed search deceleration time (current detection)
Voltage recovery time
0 to
200
0.1 to
10.0
120%
2.0 sec.
0.0 to
20.0
0.0 to
5.0
0.2 sec.
0 or 1 1
0.1 to 5.0
0.1 sec.
0.3 sec.
*1
*1. The factory setting depends on the Inverter capacity. The value for a 200 V class Inverter of 0.4kW is given.
Change during
Operation
No
No
No
No
No
No
No
Access
Level
A
A
A
A
A
A
A
Multi-function Digital Inputs
Set Value
61
62
64
Function
External speed search command 1
OFF: Speed search disabled (Acceleration starts from FMIN)
ON: Speed calculation (Calculates the motor speed and starts search from the calculated speed)
Current detection (Starts speed search from maximum output frequency)
External speed search command 2
OFF: Speed search disabled (Acceleration starts from FMIN)
ON: Speed calculation (Calculates the motor speed and starts search from the calculated speed)
(Same operation as external speed search command 1)
Current detection: Starts speed search from set frequency
(reference frequency when speed search command was input).
External speed search command 3
OFF: Inverter is base blocked
ON: Inverter starts operation using speed search (same operation as speed search 2)
6-39
6-40
Setting Precautions
•
When both external search commands 1 and 2 are set for the multi-function digital terminals, an OPE03 alarm will occur.
•
If performing speed search using external search commands ensure that the RUN command and the external search command remain both ON.
•
If the Inverter output is equipped with a contactor, set the contactor operation delay time in the Speed
Search Wait Time (b3-05). The factory setting is 0.2 sec. If no contactor is used the setting can be reduced to 0 sec.
•
Parameter b3-02 (current detection level for search completion) is effective only when current detection speed search is selected. When the current falls below the detection level, the speed search is supposed to be completed, and the motor accelerates or decelerates to the set frequency.
•
Parameter b3-03 sets the time the output frequency is reduced during speed search until the actual motor speed is detected.
•
If an overcurrent (OC) is detected when using speed search, lengthen the Minimum Baseblock Time (L2-
03).
•
If speed search is only desired in the last known operation direction set b3-14 to 1.
Application Precautions for Speed Calculation Speed Search
•
Always perform non-rotating autotuning for line-to-line resistance before using speed searches based on calculated speeds.
•
If the cable length between the motor and Inverter is changed after autotuning has been performed, perform stationary autotuning for line-to-line resistance again.
Speed Search Selection
The speed search method can be selected using b3-01. If b3-01 is set to 0 the search method is speed calculation. It has to be activated by a multi-function input (H1 set to 61 or 62).
If b3-01 is set to 1, the search method is speed calculation too, but speed search is performed at every RUN command and has not to be activated by a multifunction input.
The same is valid for setting b3-01 to 2 or 3, only the search method is current detection and not speed calculation.
Search Name
Search Method
External Speed Search
Command
Application
Precautions
Speed Calculation
Calculates the motor speed at speed search start and accelerates or decelerates from the calculated speed to the set frequency. The direction of motor rotation is also detected.
With external speed search command 1and 2 the speed calculation is performed and the speed search started from the calculated speed.
Current Detection
Starts speed search from the last known frequency or the maximum output frequency. The output frequency is decreased until the output current falls below the speed search operating current.
External speed search command 1:
Starts speed search from the maximum output frequency.
External speed search command 2:
Starts speed search from the frequency reference set before the search command.
Cannot be used with multi-motor drives or with motors two or more sizes smaller than the
Inverter capacity.
The motor may accelerate suddenly with light loads.
Automatic Restart
Examples for Speed Calculation
Search at Startup
The time chart for when speed search at startup and speed search to multi-function input terminals is shown below.
Run command
OFF
ON
Deceleration time set in b3-03
Set frequency reference
Starts using calculated speed
Output frequency b3-02
Output current
0.7 to 1.0 s * Lower limit set using Speed Search Wait Time (b3-05)
Minimum baseblock time (L2-03) x 0.7*
Note: If the stopping method is set to coast to stop, and the run command turns ON in a short
time, the operation may be the same as the search in case 2.
Fig 6.32 Speed Search at Startup (Calculated Speed)
Speed Search after Short Baseblock (during Power Loss Recovery, etc.)
1. Loss Time shorter than the Minimum Baseblock Time (L2-03)
AC power supply
Output frequency
ON
OFF
Start using speed detected
Set frequency reference
Output current
10 ms
*1. After AC power supply recovery, motor waits for
the minimum Speed Search Wait Time (b3-05).
Minimum baseblock time (L2-03) x 0.75 *1
Fig 6.33 Speed Search after Baseblock (Calculated Speed: Loss Time Is Set in L2-03)
6-41
6-42
2. Loss Time longer than the Minimum Baseblock Time (L2-03)
AC power supply
Output frequency
ON
OFF Start using speed detected
Set frequency reference
Output current
10 ms
Minimum baseblock time
(L2-03)
Speed Search Wait Time
(b3-05)
Note: If the frequency immediately before the baseblock is low or the power supply break time is long,
operation may be the same as the search in case 1.
Fig 6.34 Speed Search after Baseblock (Calculated Speed: Loss Time > L2-03)
Examples for Current Detection
Speed Search at Startup
The time chart when speed search at startup or external speed search command is selected is shown below.
Run command
OFF
ON
Maximum output frequency or set frequency
Output frequency
Deceleration time set in b3-03
Set frequency reference b3-02
Output current
Minimum baseblock time*
(L2-03)
* Lower limit is set using Speed Search Time (b3-05).
Fig 6.35 Speed Search at Startup (Current Detection)
Speed Search after Short Baseblock (during Power Loss Recovery, etc.)
1. Loss time shorter than minimum baseblock time
AC power supply
Output frequency
ON
OFF
Output frequency before power loss
Deceleration time set in b3-03
Set frequency reference b3-02 speed search operating current
Output current
Minimum baseblock time (L2-03)*1
*2
*1 Baseblock time may be reduced by the output
frequency immediately before baseblock.
*2 After AC power supply recovery, motor waits for
the minimum Speed Search Wait Time (b2-03).
Fig 6.36 Speed Search After Baseblock (Current Detection: Loss Time < L2-03)
Automatic Restart
2. Loss time longer than minimum baseblock time
AC power supply
ON
OFF
Output frequency before power loss
Deceleration speed set in b3-03
Set frequency reference
Output frequency b3-02
Speed search operating time
Output current
Speed search wait time (b3-05)
Minimum baseblock time*
(L2-03)
Fig 6.37 Speed Search After Baseblock (Current Detection: Loss Time > L2-03)
6-43
6-44
Continuing Operation at Constant Speed When Frequency Reference Is
Lost
The frequency reference loss detection function can be used to continue operation at reduced speed using the set value in parameter L4-06 as frequency reference value. When using an analog input as frequency reference source, a frequency reference loss is detected, when the reference value drops more than 90% in 400 msec or less.
When parameter L4-05 is set to 1 the Inverter will continue operation at the percentage in L4-06 of the last active frequency reference.
An fault signal during frequency reference loss can be output if H2-01 or H2-02 (Terminal M1-M2/M3-M4 function selection) to C (Loss of frequency reference).
Related Parameters
Parameter
Number
Name
L4-05 Operation when frequency reference is missing
L4-06
Frequency reference value at frequency reference loss
Setting
Range
0 or 1
Factory
Setting
1
0 to 100% 80%
Change during
Operation
No
No
Access
Level
A
A
Multi-function Digital Outputs (H2-01 to H2-02)
Set Value
C Loss of frequency reference
Function
Automatic Restart
Restarting Operation After Transient Fault (Auto Restart Function)
If an Inverter fault occurs during operation, the Inverter will perform self-diagnosis. If no fault is detected, the
Inverter will automatically restart. This is called the auto restart function.
Related Parameters
Parameter
Number
Name
L5-01 Number of auto restart attempts
L5-02 Auto restart operation selection
L5-03 Fault Retry Time
Setting
Range
0 to 10
0 or 1
0.5 to
180.0
Factory
Setting
0
0
Change during
Operation
No
No
10.0 s No
Access
Level
A
A
A
Multi-function Digital Outputs (H2-01 to H2-02)
Set Value
1E Automatic restart enabled
Function
Application Precautions
•
The auto restart function can be applied to the following faults.
• OC (Overcurrent)
• GF (Ground fault)
• PUF (DC bus fuse blown)
• OV (Main circuit overvoltage)
• UV1 (DC Bus Undervoltage, Main Circuit MC Operation Failure)
*1
• PF (Main circuit voltage fault)
• OL1 (Motor overload)
• OL2 (Inverter overload)
• OH1 (Motor overheat)
• OL3 (Overload)
*1. When L2-01 is set to 1 or 2 (continue operation during momentary power loss)
If an fault that is not listed above occurs the Inverter will not restart automatically and remain in fault condition.
•
If the fault output should be operated during auto restart L5-02 has to be set to 1
•
The number of auto restarts is set in parameter L5-01. If a fault occurs the inverter performs the auto restart corresponding to
. The inverter tries to restart every 5 msec for the maximum time of L5-03. All retries performed during L5-03 are regarded as one restart attempt.
The internal counting of restart attempts is reset to 0 when the drive has run 10 minutes without fault.
6-45
6-46
Fault Occurrance
Fault Output
RUN Controller
Retry Function
Controller Base Block
Controller delay
5 msec
L2-03 L5-03 (max)
Total Base Block Time
Fig 6.38 Timing Chart for Auto Restart Function
Application Precautions
The number of auto restarts counter is reset under the following conditions:
•
After auto restart, normal operation has continued for 10 minutes.
•
After the protection operation has been performed and an fault reset has been input.
•
After the power supply is turned OFF, and then ON again.
Inverter Protection
Inverter Protection
Inverter Overheat Protection
The Inverter is protected against overheating using a thermistor that detects the heatsink temperature.
Related Parameters
Parameter
Number
Name
Setting
Range
L8-02 Overheat pre-alarm level 50 to 130
L8-03 Inverter overheat (OH) pre-alarm operation selection 0 to 4
L8-19 Frequency reference during OH pre-alarm
0.0 to
20.0%
Factory
Setting
95
°C
4
20.0%
Change during
Operation
No
No
No
Access
Level
A
A
A
Multi-function Digital Outputs (H2-01 to H2-02)
Set Value
20
Function
Inverter overheat pre-alarm (ON when overheat pre-alarm is active)
When the overheat temperature level is reached the inverter output is switched off.
To prevent a sudden and unexpected stop of the inverter due to an overtemperature, an overheating pre-alarm can be output. Parameter L8-02 selects the pre-alarm temperature level, parameter L8-03 selects the inverter reaction on the pre-alarm:
•
Setting 0: The Inverter decelerates to stop using deceleration time C1-02, OH fault is output.
•
Setting 1: The Inverter coasts to stop, OH fault is output.
•
Setting 2: The Inverter decelerates to stop using the emergency stop time C1-09, OH fault is output.
•
Setting 3: The Inverter will continue operation and only display an OH alarm on the operator display.
•
Setting 4: The Inverter will continue operation but reduce the output frequency order to reduce the load.
Parameter L8-19 defines the decrease in output frequency as a percentage of the maximum output frequency E1-04. An OH alarm is output.
6-47
6-48
Input Phase Loss Detection Level
For the Input Phase Loss Detection the drive monitors the DC bus ripple. The drive integrates this
ΔV value over 10 scans (appr. 10 seconds). If the integrated
ΔV value of any consecutive ten scan range is greater than the voltage determined by multiplying L8-06 times the drives rated OV Trip point (400 VDC/800 VDC), a PF fault will occur and the Drive will coast to stop.
Phase Loss Fault
Signal
DC Bus
Voltage
10 seconds t
L8-06
Fig 6.39 Input Phase Loss Detection
Related Parameters
Parameter
Number
L8-06
Name
Input Phase Loss Detection Level
Setting
Range
0.0 to
25.0%
Factory
Setting
5.0%
*1
*1. The factory setting depends on the Inverter capacity. The value for a 200 V class Inverter of 0.4 kW is given.
Change during
Operation
No
Access
Level
A
Ground Fault Protection
The ground fault protection function detects the earth leakage current by calculating the sum of the three output currents. Normally this sum should be 0. If the sum exceeds 50% of the Inverter rated current a GF fault is detected and the motor coasts to stop.
The ground fault protection can be disabled by setting L8-09 to 0. It is not recommended to disable the ground fault protection.
Related Parameters
Parameter
Number
Name
L8-09 Ground fault protection selection
Setting
Range
0 or 1
Factory
Setting
1
Change during
Operation
No
Access
Level
A
Inverter Protection
Cooling Fan Control
This function controls the fan that is mounted to the inverters heatsink.
Related Parameters
Parameter
Number
Name
L8-10 Cooling fan control selection
L8-11 Cooling fan control delay time
L8-32 OH1 detection selection for fan failure
Setting
Range
0 or 1
Factory
Setting
0
0 to 300 300 sec.
0 or 1 1
Change during
Operation
No
No
No
Access
Level
A
A
A
Multi-function Relay Outputs (H2-01 to H2-02)
Set Value
3D
Function
Cooling fan fault (ON: internal cooling fan fault)
Selecting the Cooling Fan Control
Using parameter L8-10 two modes can be selected:
0:The fan is ON only when the inverter output is ON, i.e. a voltage is output. This is the factory setting.
1:The fan is ON whenever the inverter power supply is switched ON.
If L8-10 is set to 0, the turn OFF delay time for the fan can be set in parameter L8-11. After switching OFF the
RUN command the inverter waits for this time before the cooling fan is switched. The factory setting is 300 sec.
Parameter L8-32 selects whether failure of the internal cooling fan will lead to an OH1 fault or not. The factory setting is 0. This disables the OH1 fault in case of fan failure and displays a FAN alarm instead. Setting 1 activates the OH1 fault also in case of a internal fan failure.
Application Precautions
When L8-32 is set to 0 and the internal fan fails the Inverter’s overload capability is automatically derated by
10%. The overload time at 100% of the Inverter rated current becomes 30 seconds and the overload time at
120% becomes 10 seconds.
IMPORTANT
If using L8-32 = 0 a multi-function output should be set to 10 (Alarm) or 3D (Cooling Fan Error) to indicate to peripheral equipment that the Inverter’s internal cooling fan has failed. Under this condition the
Inverter should be immediately stopped and serviced for fan replacement. If the Inverter continues to run in this state, its internal temperature will increase, resulting in a potential decrease of lifetime.
Setting the Ambient Temperature
The overload capability of the inverter depends on the ambient temperature. At ambient temperatures higher than 45°C (40°C for Inverters in protection class IP20 / NEMA1) the output current capacity is reduced, i.e.
the OL2 alarm level will be lowered. Refer to
for the output current derating.
6-49
6-50
Related Parameters
Parameter
Number
L8-12 Ambient temperature
Name
The ambient temperature must be set in parameter L8-12.
Setting
Range
45 to 60
Factory
Setting
45 °C
Change during
Operation
No
Access
Level
A
100
80
60
40
20
0
0
IP00
IP20
10 20 30
Temperature (°C)
40 50
Fig 6.40 Ambient Temperature Derating Curve
60
OL2 Characteristics at Low Speed
At output frequencies below 6 Hz the overload capability of the inverter is lower than at higher speeds, i.e. an
OL2 fault (inverter overload) may occur even if the current is below the normal OL2 current level (see
The special OL2 characteristics can be disabled by setting parameter L8-15 to 0. Generally is not recommended to disable that function as the Inverter lifetime might be shortened.
OL2 Detection Level
120% for 1 min.
60% for 1 min.
-6 Hz 0 Hz 6 Hz
Fig 6.41 OL2 Alarm Level at Low Frequencies
Output
Speed
Inverter Protection
Related Parameters
Parameter
Number
Name
L8-15 OL2 characteristics selection at low speeds
Setting
Range
0 or 1
Factory
Setting
1
Change during
Operation
No
Access
Level
A
Soft CLA Selection
Soft CLA (software current level A) is a current detection level for the output IGBT protection. It is only active during acceleration and lowers the output voltage quickly to reduce the current in order to protect the
IGBTs.
The Soft CLA function can be disabled by setting parameter L8-18 to 0. Generally it is absolutely not recommended to disable this function.
Related Parameters
Parameter
Number
L8-18 Soft CLA selection
Name
Setting
Range
0 or 1
Factory
Setting
1
Change during
Operation
No
Access
Level
A
6-51
6-52
Input Terminal Functions
Temporarily Switching Operation between Digital Operator and Control Circuit Terminals
The Inverter’s run command and frequency reference inputs can be switched between local (i.e., Digital Operator) and remote (input method set in b1-01 and b1-02).
If any parameter from H1-01 to H1-05 (terminal S3 to S7 function selection) has been set to 1 (local/remote selection), this input can be used to switch over between local and remote operation.
To set the frequency reference source and RUN command source to control circuit terminals, set b1-01 and b1-02 to 1.
Related Parameters
Parameter
Number
Name b1-01 Reference selection b1-02 RUN command source selection
Setting
Range
0 to 3
0 to 3
Factory
Setting
1
1
Change during
Operation
No
No
Access
Level
Q
Q
Multi-function Digital Inputs (H1-01 to H1-05)
Set Value
1
Function
Local/Remote selection (ON: Operator; OFF: Parameter b1-01/b1-02 setting)
NOTE
Local/remote switching can also be performed using the LOCAL/REMOTE key on the Digital Operator. When the local/remote selection has been set for one external terminal, the LOCAL/REMOTE key function on the Digital Operator will be disabled.
Input Terminal Functions
Blocking the Inverter Output (Baseblock Command)
Set 8 or 9 (Baseblock command NO/NC) in one of the parameters H1-01 to H1-05 (terminal S3 to S7 function selection) to perform baseblock commands and thereby to block the inverter output.
Clear the baseblock command to restart the operation using the speed search method set in b3-01 (speed search selection). Otherwise the Inverter may trip as it will start at the same frequency reference again.
Multi-function Digital Inputs (H1-01 to H1-05)
Set Value
8
9
Function
External baseblock NO (ON: Inverter is baseblocked)
External baseblock NC (OFF: Inverter is baseblocked)
Time Chart
The time chart when using a baseblock command is shown below.
Forward operation/Stop
Baseblock command
Frequency reference
Input
Cleared
Speed search
Output frequency
Coast to a stop
Fig 6.42 Baseblock Commands
IMPORTANT
When a contactor between inverter and motor is used, always perform a base block command before opening the contactor.
Multifunction Analog Input A2 Disable/Enable
If a digital input is programmed to setting C the analog input A2 can be enabled or disabled by switching the digital input.
Multi-function Digital Inputs (H1-01 to H1-05)
Set Value
C
Function
Multi-function analog input A2 enable (ON: A2 is enabled)
6-53
6-54
Drive Enable/Disable
If a digital input is programmed to setting 6A the Inverter can be enabled or disabled by switching the digital input
If the input is switched OFF while a RUN command is active the inverter will stop using the stopping method set in b1-03.
The Drive Enable/Disable signal has to be ON before the RUN command is activated.
Multi-function Digital Inputs (H1-01 to H1-05)
Set Value
6A Drive enable (ON: Inverter enabled)
Function
Bypass Drive Enable
If a digital input is programmed to setting 70 the Inverter will not execute a RUN command until this input is closed.
Unlike the setting 6A (Drive Enable/Disable) the RUN command does not need to be cycled after closing the input. The Inverter will start whenever the digital input is closed a RUN command is active with the activated acceleration time.
If a RUN command is active and the Bypass Drive Enable input is OFF the digital operator shows the alarm message “dnE”.
Multi-function Digital Inputs (H1-01 to H1-05)
Set Value
70
Function
Bypass Drive enable (ON: Inverter is enabled)
Stopping Acceleration and Deceleration (Acceleration/Deceleration
Ramp Hold)
•
If a digital input is programmed to setting A the Inverter will pause the acceleration or deceleration and hold the output frequency when the input is closed.
•
Acceleration/deceleration is restarted when the input is turned OFF.
•
The motor will be stopped if a stop command is input while the acceleration/deceleration ramp hold input is ON.
•
When parameter d4-01 (the frequency reference hold function selection) is set to 1, the held frequency will be stored in memory. This stored frequency will be retained as frequency reference even after a power loss and the motor will be restarted at this frequency when a run command is input again.
Related Parameters
Parameter
Number
Name d4-01 Frequency reference hold function selection
Setting
Range
0 or 1
Factory
Setting
0
Change during
Operation
No
Access
Level
A
Multi-function Digital Inputs (H1-01 to H1-05)
Set Value
A Accel./Decel. Ramp Hold
Function
Input Terminal Functions
Time Chart
The time chart when using Acceleration/Deceleration Ramp Hold commands is given below.
Power supply
OFF
Forward/Stop OFF ON OFF ON
OFF ON OFF ON
Acceleration/Deceleration
Ramp Hold
Frequency reference
Output frequency
Hold Hold
Fig 6.43 Acceleration/Deceleration Ramp Hold
Raising and Lowering Frequency References Using Digital Input Signals
(UP/DOWN)
The UP and DOWN commands raise and lower Inverter frequency references by turning ON and OFF a multifunction digital input terminal S3 to S7.
To use this function, set two of the parameters H1-01 to H1-05 (digital input terminal S3 to S7 function selection) to 10 (UP command) and 11 (DOWN command).
The table below shows the possible combinations of the UP and DOWN command and the corresponding operation.
Hold Operation
UP command
DOWN command
Acceleration Deceleration
ON OFF
OFF ON
ON
ON
OFF
OFF
The change of the output frequency depends on the acceleration and deceleration times. Be sure to set b1-02
(Run command selection) to 1 (Control circuit terminal).
Related Parameters
Parameter
Number
Name d2-01 Frequency reference upper limit d2-02 Frequency reference lower limit d2-03 Master speed reference lower limit d4-01 Frequency reference hold function selection
Setting
Range
0.0 to
110.0
0.0 to
110.0
0.0 to
110.0
0 or 1
Factory
Setting
100.0%
Change during
Operation
No
0.0%
0.0%
0
No
No
No
Access
Level
A
A
A
A
6-55
6-56
Multi-function Digital Inputs (H1-01 to H1-05)
Set Value
10
11
UP command
DOWN command
Function
Setting Precautions
An OPE03 alarm will occur if one of the following settings are programmed:
•
Only either the UP command or DOWN command has been set.
•
UP/DOWN commands and Acceleration/Deceleration Ramp Hold have been programmed to digital inputs at the same time.
Application Precautions
•
When the frequency reference is input by UP/DOWN commands the frequency is limited by the parameters d2-01 to d2-03 (Reference Limits, set in% of the maximum output frequency).
•
When the frequency reference is input by UP/DOWN commands the analog input A1 becomes the frequency reference lower limit. If a combination of the frequency reference from terminal A1 and the frequency reference lower limit is set in either parameter d2-02 or d2-03, the larger limit value will become the frequency reference lower limit.
•
If a frequency reference lower limit is set and the RUN command is activated the drive accelerates to the lower limit.
•
Multi-step operation is disabled when UP/DOWN commands are used.
•
When d4-01 (Frequency Reference Hold Function Selection) is set to 1, the last frequency reference value is stored even after the power supply is turned OFF. When the power supply is turned ON and the run command is input, the motor accelerates to the frequency reference that has been stored. To reset (i.e., to 0 Hz) the stored frequency reference, turn ON the UP or DOWN command before the power is switched on.
Input Terminal Functions
Connection Example and Time Chart
The time chart and settings example when the UP command is allocated to the multi-function Digital Input terminal S3, and the DOWN command is allocated to terminal S4, are shown below.
Parameter
H1-01
H1-02
Name
Multi-function input (terminal S3)
Multi-function input (terminal S4)
Set Value
10
11
0 to 10 V analog signal
Inverter
S1
Forward operation/Stop
S2
Reverse operation/Stop
S3
UP command
S4
DOWN command
SN
Digital input neutral
A1
Frequency reference lower limit
AC
Fig 6.44 Connection Example when UP/DOWN Commands Are Allocated
Output frequency
Upper limit
Accelerates to lower limit
Lower limit
Same frequency
Forward operation/stop
UP command
DOWN command
Reference frequency reset
Speed agree*
Power supply
* The speed agree signal turns ON when the motor is not accelerating/
decelerating while the RUN command is ON.
Fig 6.45 UP/DOWN Commands Time Chart
6-57
6-58
Trim Control Function
The trim control function increments or decrements the frequency reference from analog input by the value set in parameter d4-02 (Trim control level, set in% of maximum output frequency) using two digital inputs.
To use this function, set two of the parameters H1-01 to H1-05 (digital input S3 to S7 function selection) to 1C
(Trim Control Increase) and 1D (Trim Control Decrease).
Related Parameters
Parameter
Number d4-02 Trim control level
Name
Setting
Range
0 to 100
Factory
Setting
10%
Change during
Operation
No
Access
Level
A
Multi-function Digital Inputs (H1-01 to H1-05)
Set Value
1C
1D
Trim Control Increase
Trim Control Decrease
Function
Trim Control Increase/Decrease Command and Frequency Reference
The frequency references using Trim Control Increase/Decrease command ON/OFF operations are shown below.
Frequency Reference
Trim Control Increase
Trim Control Decrease
Set Frequency
Reference
+ d4-02
ON
OFF
Set Frequency
Reference
- d4-02
OFF
ON
ON
ON
HOLD
OFF
OFF
Setting Precautions
An OPE03 alarm will occur if only one of the trim control commands is programmed.
Application Precautions
•
Trim Control Increase/Decrease command is enabled when speed reference > 0 and the speed reference source is one of the analog input (A1 or A2).
•
When the (analog frequency reference value - d4-02) < 0, the frequency reference is set to 0.
Input Terminal Functions
Analog Frequency Reference Sample/Hold
If one of the parameters H1-01 to H1-05 (digital input terminal S3 to S7 function selection) is set to 1E (analog frequency reference sample/hold) the analog frequency reference will be sampled and held whenever the digital input remains ON for at least 100 miliseconds.
The analog value 100 ms after the command is turned ON is used as the frequency reference.
Sample/hold command
Analog input
Frequency reference
Fig 6.46 Sample/Hold Analog Frequency
Related Parameters
Multi-function Digital Inputs (H1-01 to H1-05)
Set Value
1E
Function
Analog frequency reference sample/hold (ON: Frequency reference sample/hold)
Setting Precautions
An OPE03 alarm will occur if the following functions are programmed to digital inputs additional to the analog frequency reference sample/hold function:
•
Acceleration/Deceleration Ramp Hold (setting A)
•
UP/DOWN (settings 10/11)
•
Trim Control Increase/Decrease (settings 1C/1D)
Application Precautions
•
When performing analog frequency reference sample/hold of, be sure to close the digital input for 100 msec or more. If the input is ON for less than 100 msec it will be ignored.
•
The frequency reference value that is held will be deleted when the power supply is turned OFF.
6-59
6-60
Switching Operation Source to Communication Option Card
The source of frequency reference and RUN command can be switched between a Communication option card and the sources selected in b1-01 and b1-02. Set one of the parameters H1-01 to H1-05 (digital input S3 to S7 function selection) to 2 or 36 to enable operation source switchover.
If a RUN command is active, the switchover will not be accepted.
Related Parameters
Multi-function Digital Inputs (H1-01 to H1-05)
Set Value
2
36
Function
Operation Source Option Card/Inverter selection (ON: Parameter b1-01/b1-02 setting)
Operation Source Option/Inverter selection 2 (ON: option card)
Setting Precautions
To use the operation source switching function make the following settings:
•
Set b1-01 (frequency reference source) to a value different from 3 (option card).
•
Set b1-02 (RUN command source) to a value different from 3 (option card).
•
Set one of the parameters H1-01 to H1-05 to 2 or 36.
Setting for one of
H1-01 to H1-05
Terminal
Status
Frequency Reference and Run Command Source
2
36
OFF
ON
OFF
ON
Communication option card
(Frequency reference and run command are input from communications option card)
Inverter
(Frequency reference and Run command source are set in b1-01 and b1-02)
Inverter
(Frequency reference and Run command source are set in b1-01 and b1-02)
Communication option card
(Frequency reference and run command are input from communications option card)
Switching Operation Source to MEMOBUS communication
The frequency reference and RUN command source can be switched between the MEMOBUS communication via RS-422/485 and the inverter settings in b1-01 and b1-02. Therefore set one of the parameters H1-01 to
H1-05 (digital inputs terminals S3 to S7 function selection) to 6B or 6C.
If a RUN command is active the switchover will not be accepted.
Related Parameters
Multi-function Digital Inputs (H1-01 to H1-05)
Set Value
6B
6C
Function
Operation source communication/Inverter selection (ON: RS-422/485 port active)
Operation source communication/Inverter selection 2 (ON: inverter settings active)
Input Terminal Functions
Setting precautions
To use the operation source switching function make the following settings:
•
Set b1-01 (Frequency reference source) to a value different from 2 (Memobus)
•
Set b1-02 (RUN command source) to a value different from 2 (Memobus)
•
Set one of the parameters H1-01 to H1-05 to 6B or 6C
Setting for one of
H1-01 to H1-05
Terminal
Status
OFF
6B
6C
ON
OFF
ON
Frequency Reference and Run Command Source
Inverter
(Frequency reference and Run command source are set in b1-01 and b1-02)
MEMOBUS communication
(Frequency reference and run command are input via Memobus, RS-422/485 port)
MEMOBUS communication
(Frequency reference and run command are input via Memobus, RS-422/485 port)
Inverter
(Frequency reference and Run command source are set in b1-01 and b1-02)
AUTO/HAND Mode Switching by Digital Input
If the HOA Digital Operator (optional available) is connected the Inverter can be switched to AUTO or
HAND mode with digital inputs.
If b1-13 (HAND/AUTO switching during run selection) is set to 1 this is also possible during run, otherwise the Inverter has to be stopped to enable the switchover. Depending on the setting of b1-13 the functionality of b1-12 (HAND frequency reference source selection) changes.
Related Parameters
Parameter
Number
Name b1-12 HAND frequency reference source selection b1-13 HAND/AUTO switching during run selection
Setting
Range
0 or 1
0 or 1
Factory
Setting
0
0
Change during
Operation
No
No
Access
Level
A
A
Multi-function Digital Inputs (H1-01 to H1-05)
Set Value
6D
6E
Function
AUTO mode selection (ON: AUTO mode active)
HAND mode selection (ON: HAND mode active)
Application Precautions
Following table shows the behavior of the Inverter depending on the setting of b1-12 and b1-13.
Setting of b1-12
Setting of b1-13
0
(Disabled)
HAND/AUTO Switching Behaviour
0
(Operator)
1
(Terminals)
1
(Enabled)
0
(Disabled)
1
(Enabled)
Inverter has to be stopped for HAND/AUTO switchover.
If started in HAND mode d1-01 becomes the active frequency reference.
Inverter can be switched over during run.
When switched to HAND mode the last AUTO frequency reference is used in
HAND mode and copied into d1-01.
Inverter has to be stopped for HAND/AUTO switchover.
If started in HAND mode the AUTO frequency reference is used.
Inverter can be switched over during run.
When switched to HAND mode d1-01 becomes the active frequency reference.
6-61
6-62
Setting Precautions
•
The status of the digital inputs programmed to AUTO mode selection or HAND mode selection will override any digital operator selections.
•
If a Digital Operator different from the HOA Digital Operator is connected to the Inverter the digital inputs
AUTO mode selection and HAND mode selection will be ignored.
•
An OPE3 alarm will occur when AUTO mode selection and HAND mode selection are assigned to 2 digital inputs simultaneously.
Jog Frequency Operation without Forward and Reverse Commands
(FJOG/RJOG)
The FJOG/RJOG function operates the inverter at the jog frequency. This function includes a RUN command, it does not need to be set additionally.
Related Parameters
Parameter
Number d1-17 Jog frequency reference
Name
Setting
Range
0 to
200.00
Factory
Setting
6.00 Hz
Change during
Operation
Yes
Access
Level
A
Multi-Function Digital Inputs (H1-01 to H1-05)
Set Value
12
13
Function
FJOG command (ON: Forward run at jog frequency d1-17)
RJOG command (ON: Reverse run at jog frequency d1-17)
Application Precautions
•
Jog frequencies using FJOG and RJOG commands will override any other frequency references.
•
When both FJOG command and RJOG commands are ON for 500 ms or longer at the same time, the
Inverter stops according to the setting in b1-03 (stopping method selection).
Input Terminal Functions
Stopping the Inverter on External Faults (External Fault Function)
Set
Value
2C
2D
2E
2F
28
29
2A
2B
24
25
26
27
20
21
22
23
The external fault function can activate the fault relay output and can stop the Inverter operation by a digital input. The Digital Operator will display EFx where x is the number of the digital input the fault signal is connected to.
To use the external fault function, set one of the values 20 to 2F in one of the parameters H1-01 to H1-05 (digital input terminal S3 to S7 function selection).
Select the value to be set in H1-01 to H1-05 from a combination of any of the following three conditions.
•
Signal logic from peripheral devices
•
External fault detection method
•
Operation during external fault detection
The following table shows the relationship between the combinations of conditions and the set value in H1-01 to H1-05.
Signal Logic
NO
Contact
NC
Contact
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Fault Detection Method
Continuous
Detection
Detection
During
Operation
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Operation During Fault Detection
Decelerate to Stop
(Fault)
Coast to
Stop
(Fault)
Fast Stop
(Fault)
Continue
Operation
(Warning)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
6-63
6-64
Output Terminal Functions
The digital multifunction outputs can be set for several functions using the H2-01 and H2-02 parameters (terminal M1 to M4 function selection). These functions are described in the following section.
Related Parameters
Parameter
Number
Name
H2-01 Terminal M1-M2 function selection
Setting
Range
0 to 3D
Factory
Setting
0
Change during
Operation
No
Access
Level
A
H2-02 Terminal M3-M4 function selection 0 to 3D 1 No A
During Run (Setting: 0) and During Run 2 (Setting: 37)
During Run (Setting: 0)
OFF
ON
The RUN command is OFF, the Inverter output is OFF
The RUN command is ON, the Inverter output is giving out a voltage.
During Run 2 (Setting: 37)
OFF
ON
The Inverter does not give out a frequency. (During baseblock, DC injection or stopped)
The Inverter gives out a frequency.
These outputs can be used to indicate the Inverter’s operating status.
Run command
Baseblock command
Output frequency
OFF
ON
OFF
ON
During run 1 output
During run 2 output
OFF ON
OFF
ON
Fig 6.47 Timing Chart for During Run and During Run 2 Output
Output Terminal Functions
Zero Speed (Setting: 1)
OFF
ON
The output frequency is higher than the zero speed level (DC injection braking start level, b2-01).
The output frequency is lower than the zero speed level (DC injection braking start level, b2-01).
Output frequency
Zero speed level (b2-01)
Zero-speed output
OFF ON
Fig 6.48 Timing Chart for Zero-speed
Inverter Operation Ready (Setting: 6)
If a multi-function digital output is programmed to 6 the output will be switched ON when the initialisation of the Inverter at startup has finished without any faults.
During DC Bus Undervoltage (Setting: 7)
If a multi-function digital output is programmed to 7 the output is switched ON as long as a DC bus undervoltage is detected.
During Baseblock (Setting: 8)
If a multi-function digital output is programmed to 8 the output is switched ON as long as the Inverter output is base blocked.
Frequency Reference Source Selection (Setting: 9)
If a multi-function digital output is programmed to 9 the output is ON when the Digital Operator is selected as frequency reference source. If any other frequency reference is selected the output is switched OFF.
Run Command Source Selection Status (Setting: A)
If a multi-function digital output is programmed to A the output is switched ON when the digital operator is selected as RUN command source. If any other RUN command source is selected output is switched OFF.
Fault (Setting: E)
If a multi-function digital output is programmed to E the output is switched ON when any fault different from
CPF00 and CPF01 occurs. The output is also not switched in alarm condition. (Refer to
for fault and alarm lists.)
Minor Fault (Alarm) (Setting: 10)
If a multi-function digital output is programmed to 10 the output is switched ON when the Inverter is in alarm
pp.).
6-65
6-66
Fault Reset Command Active (Setting: 11)
If a multi-function digital output is set to 11 the output is switched ON as long as a fault reset command is input at one of the digital inputs.
Reverse Direction (Setting: 1A)
If a multi-function digital output is programmed for this function the output is switched ON whenever the motor is rotating in reverse direction.
OH Pre-Alarm (Setting: 20)
The overheat fault function (OH) is designed to protect the Inverter from excessive temperature damage. Thermistors attached to the heatsink of the Inverter monitor the temperature and will make the Inverter trip if the temperature reaches 105 °C.
An OH pre-alarm digital output will be switched ON whenever the heatsink temperature reaches the level specified by parameter L8-02 (Overheat pre-alarm level). Parameter L8-03 (Operation selection after overheat pre-alarm) will determine the Inverter’s response to reaching the OH pre-alarm level (besides switching the configured digital output).
Drive Enabled (Setting: 38)
If a multi-function digital output is programmed to 38 the output is switched ON when the Inverter is enabled.
The Inverter can be enabled or disabled using a digital multifunction input (see also
).
Drive Waiting (Setting: 39)
The digital output will close during the time-out period between the input of a RUN command and the expiring of the delay time specified by b1-11.
During oH and Reduced Frequency (Setting: 3A)
If a multi-function digital output is programmed to 3A the output is switched ON when an Inverter overheat alarm has occurred and the motor is running at reduced speed according to parameter L8-19 (Frequency reference during OH pre-alarm). See also
.
RUN Command from Option Card/Communication Option (Setting: 3B)
If a multi-function digital output is programmed to 3B the output will be switched ON when the RUN command is input from the built-in communication (Memobus, N2) OR from a communication option card (SI-S1,
SI-N1, etc.). If both RUN commands are off the output will be switched OFF.
Cooling Fan Fault (Setting: 3D)
If a multi-function digital output is programmed to 3D the output will be swathed ON when the internal cooling fan is faulty. Whenever this output is switched ON the Inverter should be immediately stopped and serviced for internal fan replacement. If the Inverter continues to run in this state, its internal temperature will increase, resulting in a potential decrease of lifetime.
Monitor Parameters
Monitor Parameters
This section explains the analog monitor and pulse monitor parameters.
Using the Analog Monitor Parameters
Related Parameters
Parameter
Number
H4-02
H4-03
H4-04
H4-05
H4-06
H4-07
H4-08
Terminal FM gain
Terminal FM bias
Terminal AM gain
Terminal AM bias
Name
H4-01 Terminal FM monitor selection
Terminal AM monitor selection
Terminal FM signal level selection
Terminal AM signal level selection
Setting
Range
1 to 38
0 ~
1000.0%
-110.0 ~
+110.0%
1 to 53
0 ~
1000.0%
-110.0 ~
+110.0%
0 or 2
*1
0 or 2
Factory
Setting
2
100%
0.0%
8
50%
0.0%
0
0
Change during
Operation
No
Yes
Yes
No
Yes
Yes
No
No
*1. An analog output signal of 4-20 mA (setting 2) requires an optional terminal board (ETC618121) for current output.
A
A
A
A
A
A
Access
Level
A
A
Selecting Analog Monitor Items
Some of the Digital Operator monitor items (U1 [status monitors]) can be output at the multi-function analog output terminals FM-AC and AM-AC. Refer to
page 5-41, Monitor Parameters: U
, and set the parameter number of U1 group ( part of U1) for the parameters H4-01 respectively H4-04.
Adjusting the Analog Monitor Items
Adjust the output voltage for multi-function analog output terminals FM-AC and AM-AC using the gain and bias in H4-02, H4-03, H4-05, and H4-06.
The gain sets the analog output voltage value which is equal to 100% of the monitor item.
The bias sets the analog output voltage value which is equal to 0% of the monitor item.
Note that the maximum output voltage is 10V. A voltage higher than this value can not be output.
Selecting the Signal Level
Select the signal level for the analog outputs using parameters H4-07 and H4-08. The default setting is 0 to
10V. If a current output signal of 4 to 20mA should be used an optional terminal board (ETC618121) with additional analog current outputs is required.
6-67
6-68
Adjusting the Meter
The influence of the settings of gain and bias on the analog outputs is shown on three examples in
.
Output Voltage
Gain: 170%
Bias: 30%
10V
Gain: 100%
Bias: 0%
3V
0V
0%
Gain: 0%
Bias: 100%
100%
Monitor Item
(e.g. Output Frequency)
Fig 6.49 Monitor Output Adjustment
Individual Functions
Individual Functions
Using MEMOBUS Communications
The Varispeed E7 is equipped with a RS422/485 serial communication port using the MEMOBUS protocol
MEMOBUS Communication Configuration
MEMOBUS enables a master device (e.g. PLC) to communicate with up to 31 slave devices (e.g. Inverters).
Basically the slaves respond on messages sent from the master.
The master performs serial communications with only one slave at a time. Consequently, to every slave a address must be assigned.
PLC
Inverter Inverter Inverter
Fig 6.50 Example of Connections between PLC and Inverter
Communications Specifications
The MEMOBUS communications specifications are shown in the following table.
Item
Interface
Communications Cycle
Communications Parameters
Communications Protocol
Number of Connectable Units
Specifications
RS422, RS485
Asynchronous (Start-stop synchronization)
Baud rate: Select from 1,200, 2,400, 4,800, 9,600 and 19,200 bps.
Data length:
Parity:
Stop bits:
MEMOBUS
31 units max.
8 bits fixed
Select from even, odd or none.
1 bit selected
6-69
6-70
Communications Connection Terminal
The MEMOBUS communication uses the following terminals: S+, S-, R+, and R-. Enable the terminating resistance by turning ON pin 1 of switch S1 for the last Inverter (seen from the PLC) only.
-
RS-422A or
RS-485
O
F
F
S1
1
2
S1
Terminating resistance (1/2W, 110 Ohms)
Fig 6.51 Communications Connection Terminal
Terminating resistance
IMPORTANT
• Separate the communications cables from the main circuit cables and other wiring and power cables.
• Use shielded cables for the communications cables and use proper shielding clamps
• When using RS485 communication is used, connect S+ to R+, and S- to R-, on the Inverter exterior.
below.
Fig 6.52 Connections when RS485 Communication is used
Procedure for Communicating with the PLC
Use the following procedure to perform communications with the PLC.
1. Turn OFF the power supply and connect the communications cable between the PLC and the Inverter.
2. Turn ON the power supply.
3. Set the required communications parameters (H5-01 to H5-08) using the Digital Operator.
4. Turn OFF the power supply and check that the Digital Operator display has completely disappeared.
5. Turn ON the power supply once again.
6. Perform communications with the PLC.
IMPORTANT
It is absolutely necessary to cycle the input power once when any of the serial communication parameters (H5-01 to H5-09) has been changed.
Individual Functions
Related Parameters
Parameter
Number
Name b1-01 Reference source selection b1-02 RUN command Source Selection
H5-01 Station address
H5-02 Baud rate selection
H5-03 Communications parity selection
H5-04 Communications error detection selection
H5-05 Communications error detection selection
H5-06 Send wait time
H5-07 RTS control ON/OFF
H5-08 Communication Selection
H5-09 CE detection time
Setting
Range
0 to 3
0 to 3
0 to 20
*1
0 to 4
0 to 2
0 to 3
0 or 1
5 to 65 msec
0 or 1
0 or 1
0.0 to
10.0 sec.
Factory
Setting
1
1
1F
3
1
3
0
5 msec
1
0
2.0 sec.
Change during
Operation
No
No
No
No
No
No
No
No
No
No
No
Access
Level
Q
Q
A
A
A
A
A
A
A
A
A
*1. Set H5-01 to 0 to disable Inverter responses to MEMOBUS communication
MEMOBUS communications can perform the following operations regardless of the settings in b1-01 and b1-02.
•
Monitoring operation status of the inverter
•
Setting and reading parameters
•
Resetting faults
•
Inputting digital input commands. (an OR operation is performed between the commands from MEMO-
BUS communication and the signals input from multi-function digital input terminals S3 to S7.)
Setting RUN Command and Frequency Reference by MEMOBUS
If the RUN command or the frequency reference should be input directly by MEMOBUS communication parameter b1-01 respectively b1-02 have to be set to 3 (Serial communication)
MEMOBUS Communication settings
•
Parameter H5-02 selects the communication speed. Following speeds are possible: 1200 bps (setting 0),
2400 bps (setting 1), 4800 bps (setting 2), 9600 bps (setting 3, default) and 19200 bps (setting 4).
•
Parameter H5-03 selects the used parity between no parity (setting 0, default), even parity (setting 1) and odd parity (setting 2).
•
Parameter H5-04 selects the Inverter’s behaviour when a communication error (CE) has occurred and
H5-05 is set 1. Following settings are possible:
0: Deceleration to stop using deceleration time c1-02, CE fault.
1: Coast to stop, CE fault.
2: Emergency stop using the emergency stop time c1-09, CE fault.
3: Continue operation, CE alarm is displayed.
Parameter H5-05 selects whether communication error (CE) is detected or not. The default setting is 1, a time out from the master is detected after not receiving any message for the time set in H5-09.
•
Parameter H5-06 specifies the delay time the Inverter waits until it sends the response on the received message from the master.
•
Parameter H5-07 configures whether the Inverter will implement RTS (Request To Send) messaging all the time (H5-07=0) or only when sending (H5-07=1). It is recommended to set H5-07 to 0 when using
RS485 and to 1 when using RS422.
6-71
6-72
•
Beside MEMOBUS the drive is also capable of using Metasys N2 communications via the RS485/422 port. Setting parameter H5-08 to 0 activates MEMOBUS communication, setting 1 enables Metasys N2.
Note: A additional manual for the Metasys N2 protocol is available on request.
•
The setting of parameter H5-09 determines the length of time that serial communications must be lost before a CE fault occurs.
Setting Precautions
•
If the Inverter trips with CE faults with a communication speed setting of 19200 bps, lower the communication speed.
•
If the Inverter trips with CE faults with lower communication speed selections lengthen the send wait time in parameter H5-06
•
If the Inverter’s station address is set to 0 it will ignore all messages from the master.
Message Format
In MEMOBUS communication the master sends commands to the slave and the slave responds. The message format is configured for both sending and receiving as shown below and the length of data packets depends on the command (function) content.
Slave address
Function code
Data
Error check
The space between messages must meet the following conditions:
PLC to Inverter
Command message
Inverter to PLC
Response message
PLC to Inverter
Command message
Time
24 bits long
H5-06 setting
24 bits long
Fig 6.53 Message Spacing
5 ms min.
Slave Address
Set the address from 0 to 32. If set to 0, commands from the master will be received by all slaves. (Refer to
“Broadcast Data” on the following pages.)
Function Code
The function code specifies commands. The three function codes shown in the table below are available.
Command Message Response Message
Function Code
(Hexadecimal)
Function
Min. (Bytes) Max. (Bytes) Min. (Bytes) Max. (Bytes)
03H
08H
10H
Read memory register contents
Loopback test
Write multiple memory registers
8
8
11
8
8
41
7
8
8
37
8
8
Individual Functions
Data
Configure consecutive data by combining the memory register address (test code for a loopback address) and the data the register contains. The data length changes depending on the command details.
Error Check
Errors during communications are detected using CRC-16 (cyclic redundancy check, checksum method).
The result of the checksum calculation is stored in a data-word (16 bit), which starting value is FFFH. The value of this word is manipulated using Exclusive OR- and SHIFT operations together with the data package that should be sent (slave address, function code, data) and the fixed value A001H. At the end of the calculation the data-word contains the checksum value.
The checksum is calculated in the following way:
1. The starting value of the 16 Bit data-word, that is used for the calculation, has to be set to FFFFH.
2. An Exclusive OR operation has to be performed with the starting value and the slave address.
3. The result has to be shifted to the right until the overflow bit becomes 1.
4. When this bit becomes 1, an Exclusive OR operation with the result of step 3 and the fix value A001H has to be performed.
5. After 8 shift operations (every time when the overflow bit becomes 1, an Exclusive OR like in step 4 has to be done), perform an Exclusive OR operation with the result of the former operations and the next data package (8 bit function code). Again the result of this operation has to be shifted 8 times and if needed it has to be interconnected with the fix value A001H using an Exclusive OR operation.
6. The same steps have to be performed with the data, first with the higher byte and then with the lower byte until all data are proceeded.
7. The result of these operations is the checksum. It consists of a high and a low byte.
The following example clarifies the calculation method. It shows the calculation of a CRC-16 code with the slave address 02H (0000 0010) and the function code 03H (0000 0011). The resulting CRC-16 code is 40H for the lower and D1H for the higher byte. The example calculation in this example is not done completely (normally data would follow the function code).
6-73
6-74
Calculations
1111 1111 1111 1111
0000 0010
1111 1111 1111 1101
0111 1111 1111 1110
1010 0000 0000 0001
1101 1111 1111 1111
0110 1111 1111 1111
1010 0000 0000 0001
1100 1111 1111 1110
0110 0111 1111 1111
0011 0011 1111 1111
1010 0000 0000 0001
1001 0011 1111 1110
0100 1001 1111 1111
0010 0100 1111 1111
1010 0000 0000 0001
1000 0100 1111 1110
0100 0010 0111 1111
0010 0001 0011 1111
1010 0000 0000 0001
1000 0001 0011 1110
0000 0011
1000 0001 0011 1101
0100 0000 1001 1110
1010 0000 0000 0001
1110 0000 1001 1111
0111 0000 0100 1111
1010 0000 0000 0001
1101 0000 0100 1110
0110 1000 0010 0111
0011 0100 0001 0011
1010 0000 0000 0001
1001 0100 0001 0010
0100 1010 0000 1001
0010 0101 0000 0100
1010 0000 0000 0001
1000 0101 0000 0101
0100 0010 1000 0010
1010 0000 0000 0001
1110 0010 1000 0011
0111 0001 0100 0001
1010 0000 0000 0001
1101 0001 0100 0000
D1H 40H
Higher Lower
Byte Byte
Overflow
1
1
0
1
0
1
0
1
1
1
0
1
0
1
1
1
Description
Initial value
Address
ExOr Result
Shift 1
ExOr Result
Shift 2
ExOr Result
Shift 3
Shift 4
ExOr Result
Shift 5
Shift 6
ExOr Result
Shift 7
Shift 8
ExOr Result
Function Code
ExOr Result
Shift 1
ExOr Result
Shift 2
ExOr Result
Shift 3
Shift 4
ExOr Result
Shift 5
Shift 6
ExOr Result
Shift 7
ExOr Result
Shift 8
ExOr Result
CRC-16 Result
Individual Functions
MEMOBUS Message Example
An example of MEMOBUS command/response messages is given below.
Reading Inverter Memory Register Contents
The content of maximum 16 inverter memory registers can be readout at a time.
Among other things the command message must contain the start address of the first register that is to be read out and the quantity of registers that should be read out. The response message will contain the content of the first and the consecutive number of registers that has been set for the quantity.
The contents of the memory register are separated into higher 8 bits and lower 8 bits.
The following tables show message examples when reading status signals, fault details, data link status, and frequency references from the slave 2 Inverter.
Command Message
Slave Address
Function Code
Start
Address
Quantity
CRC-16
Higher
Lower
Higher
Lower
Higher
Lower
02H
03H
00H
20H
00H
04H
45H
F0H
Response Message
(During Normal Operation)
Slave Address
Function Code
02H
03H
Data quantity
1st storage register
Higher
Lower
Next storage register
Higher
Next storage register
Lower
Higher
Next storage register
Lower
Higher
Lower
Higher
CRC-16
Lower
08H
00H
65H
00H
00H
00H
00H
01H
F4H
AFH
82H
Response Message
(During Error)
Slave Address
Function Code
02H
83H
Error code
Higher
CRC-16
Lower
03H
F1H
31H
6-75
6-76
Loopback Test
The loopback test returns command messages directly as response messages without changing the contents to check the communications between the master and slave. A user-defined test code and data values can be set.
The following table shows a message example when performing a loopback test with the slave no. 1.
Command Message
Slave address
Function code
Test Code
Data
CRC-16
Higher
Lower
Higher
Lower
Higher
Lower
01H
08H
00H
00H
A5H
37H
DAH
8DH
Response Message
(During Normal Operation)
Slave address
Function code
01H
08H
Test Code
Data
CRC-16
Higher
Lower
Higher
Lower
Higher
Lower
00H
00H
A5H
37H
DAH
8DH
Response Message
(During Error)
Slave address
Function code
01H
89H
Error Code
Higher
CRC-16
Lower
01H
86H
50H
Writing to Multiple Inverter Memory Registers
The writing of inverter memory registers works similar to the reading process, i.e. the address of the first register that is to be written and the quantity of to be written registers must be set in the command message.
The to be written data must be consecutive, starting from the specified address in the command message. The data order must be higher 8 bits, then lower 8 bits. The data must be in memory register address order.
The following table shows an example of a message where a forward operation has been set with a frequency reference of 60.0 Hz for the inverter with the slave address 01H.
Command Message
Slave Address
Function Code
Start
Address
Higher
Lower
Higher
Quantity
Lower
No. of data
Lead data
Next data
CRC-16
Higher
Lower
Higher
Lower
Higher
Lower
00H
01H
02H
58H
63H
39H
01H
10H
00H
01H
00H
02H
04H
Response Message
(During Normal Operation)
Slave Address 01H
Function Code
Start
Address
Higher
Lower
Higher
Quantity
Lower
Higher
CRC-16
Lower
10H
00H
01H
00H
02H
10H
08H
Response Message
(During Error)
Slave Address 01H
Function Code
Error code
CRC-16
Higher
Lower
90H
02H
CDH
C1H
* No. of data = 2 x (quantity)
IMPORTANT
For the number of data value in the command message the double value of the data quantity must be used.
Individual Functions
Data Tables
The data tables are shown below. The types of data are as follows: Reference data, monitor data, and broadcast data.
Reference Data
The reference data table is shown below. These data can be read and written. They cannot be used for monitoring functions.
Register No.
0000H
0001H
Reserved
Run operation and input commands
Bit 0
Bit 1
Run/stop command
Forward/reverse operation
Bit 2
Bit 3
Bit 4
Bit 5
External fault
Fault reset
ComNet
ComCtrl
Contents
Bit 6
Bit 7
Bit 8
Bit 9
Multi-function input command 3
Multi-function input command 4
Multi-function input command 5
Multi-function input command 6
0006H
0007H
0008H
Bit A
Bits B to F
Multi-function input command 7
Not used
0002H Frequency reference (Set units using parameter o1-03)
0003H to 0005H Not used
PI target value
Analog output 1 setting (-11 V/-726 to 11 V/726)
→ 10V = 660
Analog output 2 setting (-11 V/-726 to 11 V/726)
→ 10V = 660
0009H
Multi-function digital output setting
Bit 0 Digital output 1 (Terminal M1-M2)
Bit 1
Bit 2
Digital output 2 (Terminal M3-M4)
Not used
Bits 3 to 5
Bit 6
Bit 7
Bits 8 to F
1: ON 0: OFF
1: ON 0: OFF
Not used
Set fault relay (terminal MA-MC) output using bit 7 1: ON 0: OFF
Fault relay (terminal MA-MC)
Not used
1: ON 0: OFF
000AH to 000EH Not used
Reference selection settings
Bit 0
Bit 1
Not used
Input PI target value
000FH
Bits 2 to B
C
D
E
F
Not used
Broadcast data terminal S5 input
Broadcast data terminal S6 input
Broadcast data terminal S7 input
Not used
1: Enabled 0: Disabled
1: Enabled 0: Disabled
1: Enabled 0: Disabled
1: Enabled 0: Disabled
Note: Write 0 to all unused bits. Also, do not write data to reserved registers.
6-77
6-78
Monitor Data
The following table shows the monitor data. Monitor data can only be read.
Register No.
0010H
0011H
0012H
0013H
0014H
Contents
Inverter status signal
Bit 0 During run
Bit 1
Bit 2
Zero speed
During reverse operation
Bit 3
Bit 4
Bit 5
Bit 6
Reset signal active
During speed agree
Inverter ready
Minor fault
Bit 7
Bits 8 to F
Operator status
Bit 0
Bit 1
Bit 2
Bit 3, 4
Bit 5 to F
Major fault
Not used
During OPE alarm
During fault
Operator in programming mode
00: JVOP-160 attached, 01: JVOP-161 attached, 11: PC connected
Not used
OPE Fault Number
Not used
Fault Content 1
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit A
Bit B
Bit C
Bit D
Bit E
Bit F
PUF, DC bus fuse blown
UV1
UV2
UV3
Not used
GF, Ground fault
OC, Over current
OV, DC bus over voltage
OH, Inverter heatsink overheat pre-alarm
OH1, Inverter heatsink overheat
OL1, Motor overload
OL2, Inverter overload
OL3, Overload detection
Not used
Not used
Not used
Register No.
0015H
0016H
0017H
0018H
Contents
Fault Content 2
Bit 0
Bit 1
Bit 2
EF3, External fault set on terminal S3
EF4, External fault set on terminal S4
EF5, External fault set on terminal S5
EF6, External fault set on terminal S6 Bit 3
Bit 4
Bit 5
Bit 6
EF7, External fault set on terminal S7
Not used
Not used
Not used Bit 7
Bit 8
Bit 9
Bit A
Not used
Not used
PF, Input phase loss
LF, Output open phase Bit B
Bit C
Bit D
Bit E
OH3, Motor overheat pre-alarm (PTC analog input)
OPR, Digital operator disconnected
ERR, EEPROM fault
OH4, Motor overheat (PTC analog input) Bit F
Fault Content 3
Bit 0
Bit 1
Bit 2/3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit A
CE, Memobus communications error
BUS, Bus option communications error
Not used
Not used
Not used
EF0, External fault from optional input card
FBL, PI feedback loss
LL3, Loss of Load detection
Not used
OL7, High Slip Braking overload
Bit B to F Not used
CPF Fault Content 1
Bit 0/1
Bit 2
Bit 3
Bit 4
Not used
CPF02
CPF03
Not used
Bit 5
Bit 6
CPF05
CPF06
Bit 7 to F Not used
CPF Fault Content 2
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4 to F
CPF20
CPF21
CPF22
CPF23
Not used
Individual Functions
6-79
6-80
Register No.
0019H
001AH
001BH
0020H
Contents
Bit 0
Bit 1
Bit 2 to F
Inverter status
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bits 8 to F
Alarm Content 2
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8 to A
Bit B
Bit C
Bit D
Bit E
Bit F
Alarm Content 3
Alarm Content 1
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit A
Bit B
Bit C
Bit D/E
Bit F
UV, DC bus undervoltage
OV, DC bus overvoltage
OH, Inverter heatsink overheat pre-alarm
OH2, Inverter overheat alarm input by a digital input
OL3, Overload detection 1
Not used
EF, Forward/Reverse input set at the same time
BB, Baseblock active
EF3, External alarm set on terminal S3
EF4, External alarm set on terminal S4
EF5, External alarm set on terminal S5
EF6, External alarm set on terminal S6
EF7, External alarm set on terminal S7
Not used
Not used
Not used
Not used
OPR, Digital operator disconnected
CE, Memobus communications error
BUS, Bus option communications error
CALL, Communications on standby
OL1, Motor overload
OL2, Inverter overload
Not used
FBL, PI feedback loss
CALL, Communications on standby
UL3, Loss of Load detection
Not used
Not used
Not used
OH3, Motor overheat pre-alarm
Not used
Forward operation
Reverse operation
Inverter startup complete
Fault
1: Completed 2: Not completed
1: Fault
Data setting error 1: Error
Multi-function digital output 1 (terminal M1 - M2) 1: ON 0: OFF
Multi-function digital output 2 (terminal M3 - M4) 1: ON 0: OFF
Not used
Not used
Individual Functions
Register No.
0021H
0022H
0023H
0024H
0025H
0026H
0027H
0028H
0029H
002AH
002BH
Contents
Fault details
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Overcurrent (OC), Ground fault (GF)
Main circuit overvoltage (OV)
Inverter overload (OL2)
Inverter overheat (OH1, OH2)
Not used
Fuse blown (PUF)
PI feedback lost (FbL)
External fault (EF, EFO) Bit 7
Bit 8
Bit 9
Bit A
Bit B
Bit C
Bit D
Bit E
Bit F
Data link status
Bit 0
Bit 1
Bit 2
Bit 3
Control board fault (CPF)
Motor overload (OL1) or Overload (OL3) detected
Not used
Main circuit undervoltage (UV) detected
Main circuit undervoltage (UV1), control power supply fault (UV2), inrush prevention circuit fault (UV3), power loss
Output phase loss (LF)
MEMOBUS communications error (CE)
Operator disconnected (OPR)
Writing data
Not used
Not used
Upper and lower limit errors
Data integrity error
Not used
Bit 4
Bits 5 to F
Frequency reference
Monitors U1-01
Output frequency Monitors U1-02
Output voltage Monitors U1-06
Output current Monitors U1-03
Output power Monitors U1-08
Not used
Not used
Not used
Control terminals input status
Bit 0
Bit 1
Bit 2
Bit 3
Input terminal S1
Input terminal S2
Multi-function input terminal S3
Multi-function input terminal S4
Bit 4
Bit 5
Bit 6
Bits 7 to F
Multi-function input terminal S5
Multi-function input terminal S6
Multi-function input terminal S7
Not used
1: ON 0: OFF
1: ON 0: OFF
1: ON 0: OFF
1: ON 0: OFF
1: ON 0: OFF
1: ON 0: OFF
1: ON 0: OFF
6-81
6-82
Register No.
002CH
Contents
Inverter status
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit A
Bit B
Bit C
Bit D
Bit E
Bit F
Operation
Zero speed
Frequency agree
User-defined speed agree
Frequency detection 1
Frequency detection 2
Inverter startup completed
Undervoltage detection
Baseblock
Frequency reference mode
Run command mode
Overload detection
Frequency reference lost
Restart enabled
1: During Operation
1: Zero speed
1: Agreement
1: Agreement
1: Output frequency
≤ L4-01
1: Output frequency
≥ L4-01
1: Startup completed
1: Detected
1: Inverter output baseblock
1: By communication option
1: By communication option
1: Detected
1: Lost
1: Restarting
Fault (including MEMOBUS communications time-out) 1:Fault occurred
MEMOBUS communications time-out
Multi-function digital output status
1: Timed out
002DH
Bit 0
Bit 1
Bit 2
Bits 3 to F
002EH - 0030H Not used
0031H DC bus voltage
0032H – 0037H Not used
Multi-function digital output 1 (terminal M1-M2) 1: ON 0: OFF
Multi-function digital output 2 (terminal M3-M4) 1: ON 0: OFF
Not used
Not used
0038H
0039H
PI feedback (max. output frequency = 100%; resolution 0.1%; without sign)
PI input (max. output frequency = 100%; resolution 0.1%; with sign)
003AH
003BH
003CH
003DH
003EH
PI output (max. output frequency = 100%; resolution 0.1%; with sign)
CPU software number
Flash software number
Communications error details
Bit 0
Bit 1
CRC error
Invalid data length
Bit 2
Bit 3
Bit 4
Bit 5
Not used
Parity error
Overrun error
Framing error
Bit 6
Bits 7 to F kVA setting
Time-out
Not used
Note: Communications error details are stored until an fault reset is input (can also be reset during operation).
Individual Functions
Broadcast Data
Using broadcast data a command can be given to all slaves at the same time. The message must be addressed to 00H. All slaves will receive the message, but will not respond.
The following table shows the broadcast data. Theses data can also be written.
Register
Address
Contents
0001H
0002H
Operation signal
Bit 0
Bit 1
Bits 2 and 3
Bit 4
Bit 5
Bits 6 to B
Bit C
Bit D
Bit E
Run command
Reverse operation command
Not used
External fault
Fault reset
Not used
Multi-function digital input terminal S5 input
Multi-function digital input terminal S6 input
Bit F
Frequency reference
Multi-function digital input terminal S7 input
Not used.
1: Operating 0: Stopped
1: Reverse 0: Forward
1: Fault
1: Reset command
Note: Bit signals not defined in the broadcast operation signals use local node data signals continuously.
Inverter Fault Codes
The content of a current fault and faults that have occurred earlier can be read out by Memobus using the Fault
Trace (U2) and the Fault History (U3) parameters. The fault codes are shown in the table below.
Fault
Code
01H
0FH
10H
11H
12H
0BH
0CH
0DH
0EH
07H
08H
09H
0AH
02H
03H
04H
06H
Fault Description
-
-
-
EF3
EF4
OH1
OL1
OL2
OL3
GF
OC
OV
OH
PUF
UV1
UV2
UV3
Fault
Code
13H
22H
25H
26H
27H
1EH
1FH
20H
21H
1AH
1BH
1CH
1DH
14H
15H
18H
19H
Fault Description
OH3
OPR
ERR
OH4
CE
BUS
CF
-
EF0
PF
LF
-
-
EF5
EF6
EF7
-
Fault
Code
28H
91H
92H
93H
94H
88H
89H
8AH
8BH
84H
85H
86H
87H
29H
2AH
2BH
83H
Fault Description
CPF06
CPF07
CPF08
CPF09
CPF10
CPF20
CPF21
CPF22
CPF23
FBL
UL3
-
OL7
CPF02
CPF03
CPF04
CPF05
for detailed fault descriptions and for corrective actions.
6-83
6-84
ENTER Command
When writing parameters to the Inverter from the master using MEMOBUS communications the parameters are temporarily stored in the parameter data area in the Inverter. To enable these parameters the ENTER command must be used.
There are two types of ENTER commands: ENTER commands that enable parameter data in RAM and
ENTER commands that write data into the EEPROM (non-volatile memory) in the Inverter at the same time as enabling the data in RAM.
The following table shows the registers used for ENTER commands. The ENTER command is enabled by writing 0 to register number 0900H or 0910H.
Register No.
0900H
0910H
Contents
Write parameter data to EEPROM, RAM is refreshed
Parameter data are not written to EEPROM, but refreshed in RAM only.
IMPORTANT
The maximum number of times it can be written to EEPROM is 100,000. Do not frequently execute
ENTER commands (0900H) that write into EEPROM.
The ENTER command registers are write-only. Consequently, if these registers are read out, the register address will become invalid (Error code: 02H).
Communications Error Codes
The following table shows MEMOBUS communications error codes.
Error Code
01H
02H
Contents
Function code error
A function code other than 03H, 08H, or 10H has been set by the master.
Invalid register number error
• The register address can not be accessed.
• With broadcast sending, a start address other than 0001H, or 0002H has been set.
03H
21H
22H
23H
24H
Invalid quantity error
• The quantity of registers being read or written is outside the range of 1 to 16.
• In write mode, the number of data in the message is not quantity of registers x 2.
Data setting error
• A upper limit or lower limit error has occurred in the control data or when writing parameters.
• When writing parameters, the parameter setting out of the setting range
Write mode error
• Attempting to write parameters to the Inverter during operation.
• Attempting to send an ENTER command during operation.
• Attempting to write parameters other than A1-00 to A1-05, E1-03, or o2-04 when warning alarm
CPF03 (defective EEPROM) has occurred.
• Attempting to write read-only data.
Writing during DC bus undervoltage (UV) error
• Writing parameters to the inverter during UV (DC bus undervoltage) alarm.
• Sending ENTER commands during UV (DC bus undervoltage) alarm.
Writing error during parameters processing.
Attempting to write parameters while other parameters in the Inverter are processed.
Individual Functions
Slave Not Responding
In the following cases, the slave will ignore the write function.
•
When a communications error (overrun, framing, parity, or CRC-16) is detected in the command message.
•
When the slave address in the command message and the slave address in the Inverter do not match.
•
When the gap between two blocks (8 bit) of a message exceeds 24 bits.
•
When the command message data length is invalid.
Application Precautions
IMPORTANT
If the slave address specified in the command message is 0, all slaves execute the write function, but do not return response messages to the master.
Self-Diagnosis
The Inverter has a built-in function for self-diagnosing of the serial communication interface circuits. This function uses the interconnected send/receive terminals and emulates messages.
To perform the self-diagnosis function use the following procedure.
1. Switch ON the Inverter power supply, and set 67 (communications test mode) in parameter H1-05 (Terminal S7 Function Selection).
2. Switch OFF the Inverter power supply.
3. Perform the wiring according to
4. Switch ON the terminating resistance. (Turn ON pin 1 on DIP switch 1.)
5. Switch ON the inverter power supply.
Fig 6.54 Communication Terminals Wiring for Self-Diagnosis
If the serial port is working correctly the Digital Operator displays “PASS” on the display.
If an error occurs, a “CE” (MEMOBUS communications error) alarm will be displayed on the Digital Operator, the fault digital output will be turned ON and the Inverter operation ready signal will be turned OFF.
6-85
6-86
Using the Timer Function
The digital input and output terminals can be used with a timer function: A digital output is switched ON with a set delay time after a digital input has been switched ON.
Related Parameters
Parameter
Number
Name Description b4-01 b4-02
Timer function ON-delay time
Set the timer function output ON delay time (dead time) for the timer function input in 1-second units.
Enabled when a timer function is set in H1and H2.
Timer function OFF-delay time
Set the timer function output OFF delay time (dead time) for the timer function input in 1-second units.
Enabled when the timer function is set in H1and H2.
Setting
Range
Factory
Setting
Change during
Operation
Access
Level
0.0 to
300.0
0.0 to
300.0
0.0 sec.
0.0 sec.
No
No
A
A
Multi-Function Digital Inputs (H1-01 to H1-05)
Set Value
18 Timer function input
Function
Multi-Function Digital Outputs (H2-01 to H2-02)
Set Value
12 Timer function output
Function
Setting Example
When the timer function input remains switched ON for a time longer than the setting in b4-01, the timer output function is turned ON. When the timer function input remains switched OFF for a time longer than the setting in b4-02, the timer output function is turned OFF. An example of timer function operation is given in the following diagram.
Timer function input
Timer function output
Fig 6.55 Timer Function Operation Example
Individual Functions
Using PI Control
PI control is a method of making the feedback value (detection value) match the set target value.
The characteristics of the PI control operations are given below.
P element
I element
The output of a P-element is proportional to the input (deviation). With using a P-element alone it is not possible to eliminate the deviation completely.
The output of an I-element is the time-integral of the input (deviation). With using a P-element and an
I-element together the deviation can be eliminated completely.
PID Control Operation
To understand the differences between the PI control operations P and I the output share of each operation is shown in the following diagram when the deviation (i.e., the difference between the target value and feedback value) is jumps to a certain value (step response).
Deviation
Time
PI control
Output of P- and
I-element
I control
P control
Time
Fig 6.56 PI Control Operation
PI Control Applications
The following table shows examples of PI control applications using the Inverter.
Application Control Details
Example of Sensor
Used
Pressure Control
Pressure information is fed back and constant pressure control is performed.
Flow Rate
Control
Temperature
Control
Flow rate information is fed back and the flow rate is controlled with high accuracy.
Temperature information is fed back and a temperature adjustment control using a fan can be performed.
Pressure sensor
Flow rate sensor
• Thermocouple
• Thermistor
6-87
6-88
Related Parameters
Parameter
Number b5-02 b5-03 b5-04 b5-06 b5-07 b5-08 b5-09 b5-10 b5-11 b5-14 b5-15 b5-16 b5-17 b5-18 b5-19 b5-20
Proportional (P) gain
Integral (I) time
Integral (I) limit
PI limit
PI offset
PI delay time constant
PI output gain
PI Setpoint Selection
PI Setpoint
PI Setpoint Scaling
Name b5-01 PI control mode selection
PI output characteristics selection
PI reverse output selection b5-12 Selection of PI feedback signal loss detection b5-13 PI feedback loss detection level
PI feedback loss detection time
Sleep function operation level
Sleep operation delay time
Accel/decel time for PI reference b5-21 Sleep Function Selection b5-22 Snooze Level b5-23 Snooze Delay Time b5-24 Wake-Up Level b5-25 Setpoint Boost b5-26 Maximum Boost Time b5-27 Snooze feedback b5-28 PI Feedback Square Root Operation b5-29 PI Feedback Square Root Gain b5-30 PI Output Monitor Square Root b5-31 PI unit selection
Setting
Range
0, 1, 3
0.00
to
25.00
0.0 to
360.0
0.0 to
100.0
0.0 to
100.0
-100.0
to
+100.0
0.00 to
10.00
0 or 1
0.0 to
25.0
0 or 1
0 to 2
0 to 100
0.0 to
25.5
0.0 to
200.0
0.0 to
25.5
0.0 to
25.5
Factory
Setting
0
1.00
1.0 sec.
100.0%
100.0%
0.0%
0.00 sec.
0
1.0
0
0
0%
1.0 sec.
0.0 Hz
0.0 sec.
0.0 sec.
0 to 1
0.00 to
100.00
0 to
39999
1 to 2
0
0%
1
1
0 to 100 0%
0 to 3600 0 sec.
0 to 100
0 to 100
0%
0%
0 to 3600 0 sec.
0 to 100 60%
0 or 1
0 to 2.00
0 or 1
0 to 11
0
1.00
0
0
Change during
Operation
No
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
Yes
No
No
Yes
No
No
No
No
No
No
No
No
No
Access
Level
A
A
A
*1
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
*1. Parameter is moved into Quick Programming Mode when PI controller is enabled, otherwise the parameter is available only in Advanced
Programming Mode
Individual Functions
Monitor Items (U1-
Parameter
Number
U1-24
)
Name
PI feedback value
U1-36
U1-37
U1-38
U1-53
PI input volume
PI output volume
PI setpoint
PI feedback 2
Multi-Function Analog Input (H3-09)
Set Value
B
C
16
PI feedback
PI target value
PI differential feedback
Output Signal Level at Analog Output
10 V: 100% feedback
10 V: 100% PI input
10 V: 100% PI output
10 V: 100% PI target
10 V: 100% PI feedback
Multi-Function Digital Inputs (H1-01 to H1-05)
Set Value
19
30
31
34
35
Function
PI control disable (ON: PI control disabled)
PI control integral reset (ON: integral reset and hold as long as input is ON)
PI control integral hold (ON: integral is hold)
PI soft starter disable (ON: disabled)
PI input characteristics switch
Function
Unit
0.01%
0.01%
0.01%
0.01%
0.01%
6-89
6-90
PI Control Methods
There are two PI control methods. Select the method by setting parameter b5-01.
Set Value
0
1
3
Control Method
PI control disabled
PI output becomes directly the Inverter output frequency.
PI output is added to the frequency reference as compensation value of the Inverter output frequency.
When the PI control is enabled (b5-01=1 or 3) further changes to other parameter settings occur automatically.
Following parameters change their Access Level to Quick Access Level:
Parameter Number
H3-08
Name
Analog input A2 signal level selection
H3-09
H3-13 b5-31 b5-02 b5-03
Analog input A2 function selection
Terminal A1/A2 switching
PI unit selection
Proportional (P) gain
Integral (I) time
Access Level
Q
Q
Q
Q
Q
Q
Following parameters change their Default Setting:
Parameter Number
H3-09
Name
Analog input A2 function selection
Default Setting
B
PI Input Methods
PI Target Value Input Methods
Normally, the frequency reference selected in b1-01 is the PI target value, the PI target value can also be set as shown in the following table.
PI Target Input Method Setting Conditions
MEMOBUS register 0006H
Parameter setting
Set MEMOBUS bit 1 in register address 000FH to 1 (enable/disable PI target value from communications) to be able to use register number 0006H as the PI target value.
If b5-18 is set to 1 the value in b5-19 becomes the PI target value.
NOTE
If the PI function is used the frequency reference value becomes the target value, which is set and shown in Hz on the operator. Nevertheless, internally the PI target value is used in percent. I.e. the following formula is used:
PI target value [%] = frequency reference [Hz] max. output frequency [Hz]
• 100%
Individual Functions
PI Feedback Input Methods
Select one of the following PI control feedback input methods
Input Method
Analog input A2
Analog input A1
(Differential Mode)
Setting Conditions
Set H3-09 (Analog Input A2 Function Selection) to B (PI feedback).
(Default when PI control is enabled)
Set H3-09 to 16. Analog input A1 becomes the feedback 1 input and the analog input
A2 becomes the feedback 2 input.
If H3-09 is set to 16, the PI differential mode is activated. Both analog inputs (A1 and A2) become feedback inputs and the difference between both (A1 - A2) becomes the feedback value for the PI controller. The monitor U1-24 becomes the feedback 1 monitor, U1-53 becomes the feedback 2 monitor.
In PI differential mode the PI target value can be set using parameter b5-07 (PI offset or PI differential setpoint).
PI Adjustment Examples
Suppressing Overshoot
If overshoot occurs, reduce Proportional gain (P), and increase integral time (I).
Response
Before adjustment
After adjustment
Time
Set a Rapidly Stabilizing Control Condition
To rapidly stabilize the control even if overshoot occurs, reduce integral time (I).
Response
Before adjustment
After adjustment
Time
Suppressing Long-cycle Vibration
If vibration occurs with a longer cycle than the integral time (I) set value, lengthen the integral time (I) to suppress the vibration.
Response
Before adjustment
After adjustment
Time
6-91
6-92
Suppressing Short Cycle Vibration
If short cycle vibration occurs reduce the proportional gain (P), or increase the PI delay time constant.
Response
Before adjustment
After adjustment
Time
Setting Precautions
•
Parameter b5-04 is used to prevent the calculated integral value from exceeding a specified amount and so from saturated control. Otherwise, when the load varies rapidly the Inverter response is delayed and the machine might be damaged or the motor may stall. In this case, reduce the set value to speed up Inverter response.
•
Parameter b5-06 is used to prevent the output value of the PI control calculation from exceeding a specified amount.
•
Parameter b5-07 is used to adjust the PI control offset. It is added to the PI output value. When differential
PI feedback is selected (H3-09=16) parameter b5-07 becomes the PI Setpoint it is added to the difference between both feedback values.
•
Set the filter time constant for the PI control output in b5-08 to prevent machinery resonance when machinery friction is great or rigidity is poor. In this case, set the constant to a higher value than the resonance frequency oscillation period. Increase this time constant to reduce Inverter responsiveness.
•
Parameter b5-09, the PI output polarity can be inverted. If now the PI target value increases the output frequency will be lowered. This function is usable e.g. for vacuum pumps.
•
Parameter b5-10 a gain can be applied to the PI control output. Enable this parameter to adjust the amount of compensation if the PI control output is added to the set frequency reference (b5-01 = 3).
•
Parameter b5-11 can be used to determine what happens to the inverter output when the PI control output is negative: Setting 0 will limit the PI control output to 0 while setting 1 will allow negative output values.
When b1-04 (Prohibition of Reverse Operation) is set to 1 or 3 (revers is disabled), however, the PI output is limited to 0.
•
Parameter b5-17 sets an accel./decel. ramp that raises/lowers the PI setpoint gradually (PI soft starter).
The normally used accel./decel. function (C1 parameters) is allocated after PI control so that, depending on the settings, resonance with the PI control and hunting in the machinery may occur. Using b5-17 this behaviour can be prevented.
The PI soft starter function can also be disabled or enabled using a digital input (H1 = 34).
PI Control Block
The following diagram shows the PI control block in the Inverter.
Individual Functions
Fig 6.57 PI Control Block Diagram
6-93
6-94
PI Feedback Loss Detection
When performing PI control be sure to use the PI feedback loss detection function. Otherwise, when the PI feedback gets lost, the Inverter output frequency may accelerate the motor to the maximum output frequency.
When b5-12 is set to 1 and the PI feedback value falls below the PI feedback loss detection level (b5-13) for a time longer than the PI feedback loss detection time (b5-14) a Fbl alarm (Feedback loss) will be displayed on the Digital Operator display and inverter operation is continued.
When the same happens and b5-12 is set to 2 a Fbl fault will be displayed on the display of the Digital Operator and the inverter operation will be stopped. The motor coasts to stop and the fault relay is operated.
The PI feedback loss function can be disabled by setting b5-12 to 0.
The time chart for PI feedback loss detection is shown below.
PI feedback value
Loss detection level
(b5-13)
Loss detection time
(b5-14)
No Fbl detection
Loss detection time’
(b5-14)
Fbl detection
Time
Fig 6.58 PI Feedback Loss Detection Time Chart
PI Sleep Function
The PI sleep function can be used in two different modes which depends on the setting of b5-21.
If b5-21 is set to 0, the frequency reference/PI target value is the input value for the sleep function. If b5-21 is set to 1, the output frequency before the softstarter (SFS input) is becomes the sleep function input value.
If this value falls below the sleep level b5-15 for a longer time than the sleep operation delay time b5-16, the inverter output will be stopped. If the value comes back to a value higher than b5-15 for a time longer than b5-
16, the inverter will resume operation. See also following timing chart.
PI output/SFS input
Sleep operation level b5-15
Sleep operation delay time
Sleep operation delay time
Internal run command
External run command
Operating
Operation Stopped
Run command has been input
Operation status output
Fig 6.59 PI Sleep Timing Chart
The functionality of the sleep function is also available with deactivated PI controller.
Individual Functions
PI Snooze Function
By setting b5-21 to 2 the PI snooze function can be enabled. This software observes the PI feedback value and the output frequency (Softstarter output) to switch the Inverter ON and OFF automatically as the system requires.
•
Snooze Activation
The inverter stops operation when the output frequency (Softstarter output) falls below the snooze level b5-22 for a time longer than the snooze delay time b5-23 and when the feedback value is above the snooze feedback value in b5-27. Before stopping the inverter finally, the PI setpoint can be boosted up to temporarily over-satisfy the load and thereby to avoid a short cycle ON and OFF switching of the inverter. The boost level is set in parameter b5-25 and it is set as percentage of the PI setpoint value, but the maximum time for boost operation is set in b5-26.
•
Wake up
The inverter resumes the normal PI operation when the PI feedback falls below the wake up level b5-24.
The normal acceleration ramp is used.
PI Setpoint
Setpoint Boost (b5-25) time
PI Setpoint + b5-25
PI Feedback
Snooze Feedback Level (b5-27)
Wake-Up Level (b5-24)
SFS Output Freq.
time
Snooze Level
(b5-22) t < b5-23
Snooze Delay
(b5-23) normal decel.
ramp
Normal PI operation Boost Snooze normal accel.
ramp time
Normal PI operation
Fig 6.60 PI Snooze Time Chart
NOTE
Using the parameter b5-21 either sleep operation or snooze operation can be enabled. It is impossible to enable both functions at the same time.
6-95
6-96
Square Root Feedback Operation
If parameter b5-28 is set to 1 the feedback value is converted into a value that equals the square root of the actual feedback. This can be used for example to control the flow rate when a pressure sensor is used to generate a feedback value. With parameter b5-29 the square root can be multiplied with a factor. Following formula applies: flow rate = gain (b5-29)
× pressure (head)
So linear connection between the PI target value and the feedback can be realized.
With parameter b5-30 also the feedback monitor can be switched to show a square root value of the actual feedback.
Scaling of PI Parameters and Monitors with Units
The PI parameter b5-19 and the monitor parameters U1-24 and U1-38 can be scaled using parameter b5-20.
Following setting can be applied:
0:
1:
0.01 Hz units (default setting
0.01% (Maximum output frequency is 100%)
2 to 39: rotation per minute (rpm) (Sets the motor poles)
40 to 39999: User desired display. Sets the maximum setting displayed using the setting rule in
Set the display at maximum frequency excluding the decimal point.
Set the number of digits displayed the decimal point.
Fig 6.61 PI Scaling Setting Rule
Example: When the max. PI value should be 200.0, set 12000: 2000 for the maximum display and 1 for the one digit behind the decimal point
Additional to the scaling also units can be displayed if a Digital Operator with LCD clear text display is used.
The units are defined by parameter b5-31 and following units are available:
9
10
7
8
11
Setting
Value
0
1
2
5
6
3
4
Function
WC: Inch of water column
PSI: lb/square inch
GPM: Gallons per minute
F: Degree Fahrenheit
CFM: Cubic feet per minute
CMH: Cubic meter per hour
LPH: Liters per hour
LPS: Liters per second
Bar: Bar
Pa: Pascal
C: Degree Celsius
Mtr: Meters
Displayed Unit
WC
PSI
GPM
F
CFM
CMH
LPH
LPS
Bar
Pa
C
Mtr
Individual Functions
Multifunction Digital Input Settings: H1-01 to H1-05 (Terminal S3 to S7)
PI Control Disable: 19
•
When a multi-function digital input is set for this function it can be used to disable the PI function by switching the input to ON.
•
The PI target value becomes the frequency reference value.
PI Control Integral Reset: 30
•
Using this function the integral value of the PI control can be reset by setting a multi-function digital input to ON.
•
It will remain at 0 as long as the input is ON.
PI Control Integral Hold: 31
•
Using this function the integral share value of the PI control can be hold by setting a multi-function digital input to ON. The value will be hold as long as the input is ON.
PI Soft Starter Disable: 34
•
To disable the PI soft starter temporarily switch ON the multi-function digital input.
PI Input Characteristic Switch: 35
•
Using this function the PI input characteristic can be inverted by switching the multi-function digital input
ON.
6-97
6-98
Energy-saving
When the Energy Saving Function is activated the output voltage is automatically lowered to run the motor at maximum efficiency.
Related Parameters
Parameter
Number
Name b8-01 Energy-saving mode selection b8-04 Energy-saving coefficient b8-05 Power detection filter time constant b8-06 Search operation voltage limiter
*1. The factory setting depends on the Inverter capacity
Setting
Range
Factory
Setting
0 or 1
0.0 to
655.00
0
*1
0 to 2000 20 msec
0 to 100 0%
Change
During
Operation
No
No
No
No
Access
Level
A
A
A
A
Adjusting Energy-saving Control
•
To enable the energy saving function, set b8-01 (Energy Saving Mode Selection) to 1. The default setting is 0 (disabled).
•
b8-04 (Energy-saving Coefficient) is preset assuming that motor and inverter capacity are the same. Adjust b8-04 in steps of 5 % until the output power reaches its minimum. The higher the energy-saving coefficient, the higher is the output voltage.
•
To improve the responsiveness when the load fluctuates reduce the power detection filter time constant b8-
05. If b8-05 is set too small the motor rotations may become unstable under light load conditions.
•
Motor efficiency varies due to temperature fluctuations and differences in motor characteristics. Consequently the motor efficiency has to be controlled. To have optimized efficiency, the search operation varies the output voltage. Parameter b8-06 (Search Operation Voltage Limiter) limits the range for the voltage search operation. For 200 V Class Inverters, a range of 100% is equal to 200 V and for 400 V Class Inverters a range of 100% is equal to 400 V. Set to 0 to disable the search operation voltage limiter.
Individual Functions
Setting Motor Parameters
Related Parameters
Parameter
Number
E2-01
E2-03
E2-05
Motor rated current
Motor no-load current
Name
Motor line-to-line resistance
Setting
Range
0.32 to
6.40
*1
0.00 to
1.89
*3
0.000
to
65.000
Factory
Setting
1.90 A
*2
9.842
Ω
Change during
Operation
No
No
No
*1. The setting range is 10% to 200% of the Inverter rated output current. The value for a 200 V class Inverter of 0.4 kW is given.
*2. The factory setting depends on the Inverter capacity. The value for a 200 V class Inverter of 0.4 kW is given
*3. The setting range is 0.00 A to (E1-01 - 0.01 A).
Access
Level
Q
A
A
Manual Setting of the Motor Parameter
Motor Rated Current Setting
Set E2-01 to the rated current value on the motor nameplate.
Motor No-Load Current Setting
Parameter E2-03 is measured automatically during motor line-to-line resistance auto-tuning. When auto-tuning can not be performed consult the motor manufacturer for the motor no-load current value.
Motor Line-to-Line Resistance Setting
Parameter E2-05 is measured automatically during motor line-to-line resistance autotuning. When auto-tuning can not be performed, consult the motor manufacturer for the line-to-line resistance value. Calculate the resistance from the line-to-line resistance value in the motor test report using the following formula and then make the setting accordingly.
•
•
•
E-type insulation: [Line-to line resistance (
Ω) at 75°C of test report] × 0.92 (Ω)
B-type insulation: [Line-to line resistance (
Ω) at 75°C of test repor]t × 0.92 (Ω)
F-type insulation: [Line-to line resistance (
Ω) at 115°C of test report] × 0.87 (Ω)
6-99
6-100
Setting the V/f Pattern
Using the E1 parameters the Inverter input voltage and the V/f pattern can be set as needed. It is not recommended to change the settings when the motor is used in open loop vector control mode.
Related Parameters
Parameter
Number
E1-01
E1-03
E1-04
E1-05
E1-06
E1-07
E1-08
E1-09
E1-10
E1-11
E1-12
E1-13
Input voltage setting
V/f pattern selection
Max. output frequency (FMAX)
Max. output voltage (VMAX)
Base frequency (FA)
Mid. output frequency (FB)
Mid. output frequency voltage (VB)
Min. output frequency (FMIN)
Min. output frequency voltage (VMIN)
Mid. output frequency 2
Mid. output frequency voltage 2
Base voltage (VBASE)
Name
Setting
Range
Factory
Setting
0.0 to
200.0
0.0 to
255.0
0.0 to
200.0
0.0 to
255.0
0.0 to
255.0
155 to
255
*1
0 to F, FF
0.0 to
200.0
0.0 to
255.0
0.0 to
200.0
0.0 to
200.0
0.0 to
255
F
0.0 V
50.0 Hz
50.0 Hz
2.5 Hz
15.0 V
1.2 Hz
0.0 Hz
*2
*1. Values for 200 V class Inverters are shown. For a 400 V class Inverter the values have to be doubled.
*2. Parameters E1-11 and E1-12 are disabled when set to 0.0
Change during
Operation
No
No
No
No
No
No
No
No
No
No
No
No
Access
Level
Q
A
A
A
A
A
A
A
A
A
A
A
Setting Inverter Input Voltage
Set the Inverter input voltage correctly in E1-01 so that it matches the power supply voltage. The set value becomes a reference value for the stall prevention during deceleration and the overvoltage level according to the table below.
Inverter
Voltage Class
Input Voltage
Setting E1-01
OV Level
Stall Prevention during Decel Level
200 V 200 V 410 VDC 377 VDC
O 400 V
720 VDC 662 VDC
400 V
P 400 V
820 VDC 754 VDC
Setting V/f Pattern
The V/f pattern can be selected using parameter E1-03. There are two methods of setting the V/f pattern:
Select one of the 15 preset pattern types (set value: 0 to E), or set a user-defined V/f pattern (set value: F).
The factory setting for E1-03 is F.
To select one of the existing patterns, refer to the following table.
Individual Functions
Characteristic
Variable torque characteristic
High Startup
Torque
*1
Application
Constant Torque
Characteristic
These patterns are used in general applications where the load torque is fixed, regardless of rotation speed, e.g. for linear transport systems.
These patterns are used for loads with torque proportional to the square or cube of the rotation speed, such as fans and pumps.
Select a high startup torque V/f pattern only in the following cases.
• The wiring distance between Inverter and motor is large (approx. 150 m min.)
• A large torque is required at startup
• An AC reactor is inserted in the Inverter input or output.
Set
Value
Specifications
0 (F) 50 Hz specifications
1
2
3
4
60 Hz specifications
60 Hz specifications, voltage saturation at
50 Hz
72 Hz specifications, voltage saturation at
60 Hz
50 Hz specifications, cubical torque characteristic
5
6
7
50 Hz specifications, quadratic torque characteristic
60 Hz specifications, cubical torque characteristic
60 Hz specifications, quadratic torque characteristic
8
50 Hz specifications, medium startup torque
9
A
50 Hz specifications, large startup torque
60 Hz specifications, medium startup torque
B 60 Hz specifications, large startup torque
Field Weakening
Operation
This pattern is used for frequencies of
60 Hz or higher. From the voltage saturation point on (in the field weakening area) the output voltage is fixed to the maximum output voltage.
C
D
E
90 Hz specifications, voltage saturation at
60 Hz
120 Hz specifications, voltage saturation at
60 Hz
180 Hz specifications, voltage saturation at
60 Hz
Without Limits
With this pattern the voltage and frequency values can be set to any desired value, without limitations.
FF
50 Hz specifications, without parameter limits.
*1. Usually sufficient starting torque is provided by the torque compensation function (automatic torque boost at low speed)
When one of these patterns is selected the values of parameters E1-04 to E1-10 are changed automatically.
There are three different sets of values for E1-04 to E1-10, depending on the Inverter capacity.
•
0.4 to 1.5 kW V/f pattern
•
2.2 to 45 kW V/f pattern
•
55 to 300 kW V/f pattern
The characteristics diagrams for each are shown in the following pages.
6-101
0.4 to 1.5 kW V/f Pattern
The diagrams show characteristics for a 200 V class Inverter. For a 400 V class Inverter, multiply all voltages with 2.
•
Constant Torque Characteristics (Set Value: 0 to 3)
Set Value 0 50 Hz Set Value 1 60 Hz Set Value 2 60 Hz Set Value 3 72 Hz
1.3 2.5
1.5
1.5 3
•
Variable Torque Characteristics (Set Value: 4 to 7)
Set Value 4 50 Hz Set Value 5 50 Hz Set Value 6
1.5 3
60 Hz Set Value 7 60 Hz
1.3
1.3
•
High startup torque (Set value 8: to B)
Set Value 8 50 Hz Set Value 9 50 Hz
1.5
Set Value A
1.5
60 Hz Set Value B 60 Hz
6-102
1.3 2.5
1.3 2.5
1.5
•
Field Weakening Operation (Set Value: C to E)
Set Value C 90 Hz Set Value D 120 Hz
1.5
Set Value E 180 Hz
1.5
1.5
1.5
Individual Functions
2.2 to 45 kW V/f Pattern
The diagrams show characteristics for a 200 V class Inverter. For a 400 V class Inverter, multiply all voltages with 2.
•
Constant Torque Characteristics (Set Value: 0 to 3)
Set Value 0 50 Hz Set Value 1 60 Hz Set Value 2 60 Hz Set Value 3 72 Hz
•
Variable Torque Characteristics (Set Value: 4 to 7)
Set Value 4 50 Hz Set Value 5 50 Hz Set Value 6 60 Hz Set Value 7 60 Hz
•
High Startup Torque (Set Value: 8 to B)
Set Value 8 50 Hz Set Value 9 50 Hz Set Value A 60 Hz Set Value B 60 Hz
•
Field Weakening Operation (Set Value: C to E)
Set Value C 90 Hz Set Value D 120 Hz Set Value E 180 Hz
6-103
6-104
55 to 300 kW V/f Pattern
The diagrams show characteristics for a 200 V class Inverter. For a 400 V class Inverter, multiply all voltages with 2.
•
Constant Torque Characteristics (Set Value: 0 to 3)
Set Value 0 50 Hz Set Value 1 60 Hz Set Value 2 60 Hz Set Value 3 72 Hz
•
Variable Torque Characteristics (Set Value: 4 to 7)
Set Value 4 50 Hz Set Value 5 50 Hz Set Value 6 60 Hz Set Value 7 60 Hz
•
High Startup Torque (Set Value: 8 to B)
Set Value 8 50 Hz Set Value 9 50 Hz Set Value A 60 Hz Set Value B 60 Hz
•
Field Weakening Operation (Set Value: C to E)
Set Value C 90 Hz Set Value D 120 Hz Set Value E 180 Hz
Individual Functions
NOTE
When E1-03 is set to F (User-defined V/f pattern) parameters E1-04 to E1-10 can be set. If E1-03 is set to anything other than F, parameters E1-04 to E1-13 can only be read. If the V/f characteristics are linear, set E1-07 and E1-09 to the same value. In this case, E1-08 will be ignored.
Output voltage (V)
Frequency (Hz)
Fig 6.62 User-Set V/f Pattern
Setting Precautions
When the setting is to user-defined V/f pattern, beware of the following points:
•
Parameters E1-11 and E1-12 are set to 0.0 by default in all V/f patterns. If E1-03 is set to F they can be set to obtain another point defining the V/f pattern.
•
Be sure to set the four frequencies as follows:
E1-04 (FMAX)
≥ E1-11 (FMID2) > E1-06 (FA) > E1-07 (FB) ≥ E1-09 (FMIN)
6-105
6-106
Motor Preheat Function
The motor preheat function can be used to prevent e.g. moisture inside the motor due to condensation. Two different current levels are available. The preheat currents can be set in parameters b2-09 and b2-10 as a percentage of the Inverter rated current. Both functions are enabled by digital inputs. If the Drive Enable (H1-
=6A) or Bypass Drive Enable (H1=70) function is used the motor preheat function 2 has to be used, the preheat function 2 can then also be activated without enabling the drive.
Related Parameters
Parameter
Number b2-09 Motor preheat current 1
Name
Setting
Range
0 to 100
Factory
Setting
0%
Change during
Operation
No
Access
Level
A b2-10 Motor preheat current 2 0 to 10 5% No A
Multi-function Digital Inputs (H1-01 to H1-05)
Function Set value
60
80
Motor preheat 1
Motor preheat 2
The time chart for motor preheat is shown below.
Motor preheat
RUN
Output frequency
E1-09 b2-01 b2-03
Output current b2-02 b2-09
Motor preheat
Fig 6.63 Motor Preheat Function 1 Time Chart b2-04
Motor preheat
Individual Functions
(Bypass)
Drive Enable
Motor preheat
RUN
Output frequency
E1-09 b2-01 b2-03 b2-04
Output current b2-02 b2-09
Motor preheat
Fig 6.64 Motor Preheat Function 2 Time Chart
Motor preheat
Setting Precautions
•
If the Motor Preheat command 1 and the Motor Preheat Command 2 are set simultaneously an OPE3 alarm will occur.
•
If Motor Preheat command 1 and Drive Enable or Bypass Drive Enable are set simultaneously an OPE3 alarm will occur. Motor Preheat 2 has to be used instead.
•
During motor preheat operation the Digital Operator display will show PRHT alarm.
6-107
6-108
Emergency Override Function
The emergency override function is used as a “smoke purge function. It will run the motor at the preset emergency override speed or at AUTO frequency reference in forward or reverse direction. See Fig for a timing chart.
Drive Enable*
Emergency Override
Run command
Emergency Override
Reference**
Output frequency
* Applies for Drive Enable (H1-xx=6A) or Bypass Drive Enable (H1-xx=70)
** Either b1-14 or AUTO reference, depending on b1-15 setting
Fig 6.65 Timing Chart for Emergency Override Function
Related Parameters
Parameter
Number
Name b1-14 Emergency override speed b1-15 Emergency override reference selection
Setting
Range
0 to
200.00
0 or 1
Factory
Setting
0.00 Hz
Change during
Operation
No
0 No
Access
Level
A
A
Multi-Function Digital Inputs (H1-01 to H1-05)
Set Value
81
82
Function
Emergency override forward (ON: Emergency override in forward direction)
Emergency override reverse (ON Emergency in override in reverse direction)
Setting and Application Precautions
•
An OPE3 alarm will occur when emergency override forward and emergency override reverse are programmed to digital inputs simultaneously.
•
During emergency override the Digital Operator display will show OVRD alarm.
•
When the HOA Digital Operator is used, the OFF key is disabled during Emergency Override if any of the multi-function inputs are programmed to Drive Enable (H1-xx=6A) or Bypass Drive Enable (H1-xx=70), in both HAND and AUTO Mode.
•
If a RUN or jog input is closed but the Drive Enable / Bypass Drive Enabled input is open, the Inverter will display a “DNE Drive not Enable” alarm and the STOP LED will blink. When the Emergency Override input is closed, the alarm display will change to “OVRD Emergcy Override”, the RUN LED will turn ON and the STOP LED will turn OFF again.
Individual Functions
High Slip Braking
The High Slip Braking function can shorten the deceleration times without using a braking option for emergency stops for example.
The function must be activated by a multifunction digital input.
Note the following:
•
The HSB function is not comparable with the normal deceleration function. It does not use a ramp function.
•
HSB should not be used at normal operation instead of a deceleration ramp.
Related Parameters
Parameter
Number
Name n3-01 High Slip braking deceleration frequency width n3-02 High Slip braking current limit n3-03 High Slip braking stop dwell time n3-04 High Slip braking OL7 time
Setting
Range
1 to 20
100 to
200
0.0 to
10.0
30 to
1200
Factory
Setting
5%
150%
1.0 sec.
40 sec.
Change during
Operation
No
No
No
No
Access
Level
A
A
A
A
Adjusting the HSB Deceleration Frequency Width (N3-01)
This parameter sets the step value (in percent of maximum output frequency) that is used for lowering the output frequency to achieve a large negative slip and thereby to brake the motor.
Normally no adjustments should be necessary. Increase the value if DC bus overvoltage faults occur.
Adjusting the HSB Current Limit (N3-02)
The setting of parameter N3-02 limits the output current while high slip braking is active. The current limit affects the achievable deceleration time. The parameter is set in percent of the motor rated current setting.
The lower the current limit the longer is the deceleration time.
Setting the HSB Dwell Time at Stop (N3-03)
At the end of a high slip braking the output frequency is held at the minimum output frequency for the time set in N3-03. Increase the time if the motor coasts after HSB.
Setting the HSB Overload Time (N3-04)
N3-04 sets the HSB overload time. If the output frequency does not change for any reason although an HSB command is given, an OL7 fault will be displayed and the fault relay will operate.
Activating High Slip Braking
If one of the multifunction inputs is set to “68” it can be used to activate the HSB function. The Inverter will brake the motor immediately after the HSB command was given. As the HSB function is activated by the positive edge of digital input signal HSB cannot be stopped, i.e. normal inverter operation cannot be resumed.
6-109
6-110
Digital Operator Functions
Setting Digital Operator Functions
Related Parameters
Parameter
Number o1-01 o1-02 o1-03
Monitor selection
*1
Name
Monitor selection after power up
Digital operator display scaling o1-09
Frequency reference display unit selection
*2 o2-01
LOCAL/REMOTE key enable/disable
*3 o2-02
STOP key during control circuit terminal operation
o2-03 User parameter initial value o2-05 Frequency reference setting method selection o2-06
Operation selection when digital operator is disconnected
Setting
Range
6 to 53
1 to 4
0 to
39999
0 to 11
0 or 1
0 or 1
0 to 2
0 or 1
0 or 1
Factory
Setting
6
Change during
Operation
Yes
1
0
0
1
1
0
0
0
Yes
No
No
No
No
No
No
No
Access
Level
A
A
A
A
A
A
A
A
A o2-07 o2-08 o2-09 o2-10
Cumulative operation time setting
Cumulative operation time selection
Initialize Mode
Fan operation time setting o2-12 Fault trace initialize o2-14 kWh monitor initialize o2-15
HAND Key function selection
*4
0 to
65535
0 or 1
1 to 5
0 to
65535
0 or 1
0 or 1
0 or 1
0 hrs
0
2
0 hr.
0
0
0
No
No
No
No
No
No
No
A
A
A
A
A
A
A
*1. This parameter is effective only when the LED Digital Operator is used.
*2. Parameter function is only valid if a Digital Operator with LCD clear text display is used (LCD or HOA Digital Operator).
*3. This parameter is effective only when the LED or LCD Digital Operator is used.
*4. This parameter is effective only when the HOA operator JVOP-162 is used
Monitor Selection (o1-01)
Using parameter o1-01 the third monitor item that is directly displayed in Drive Mode can be selected. This parameter is only effective when the LED Digital Operator is used.
Monitor Display when the Power Supply is Turned ON (o1-02)
Using parameter o1-02 the monitor item (U1supply is turned ON can be selected.
) that is displayed on the Digital Operator when the power
Digital Operator Functions
Changing Frequency Reference Scaling (o1-03)
The frequency monitors can be scaled using parameter o1-03. The scaling will be applied to following monitor items and parameters:
•
U1-01 (Frequency reference)
•
U1-02 (Output frequency)
•
U1-05 (Motor speed)
•
U1-20 (Output frequency after soft starter)
•
d1-01 to d1-04 and d1-17 (Frequency references)
The following scaling settings can be applied:
0: 0.01 Hz units (default setting
1:
2 to 39:
0.01% (Maximum output frequency is 100%) rotation per minute (rpm) (Sets the motor poles)
40 to 39999: User desired display. Sets the maximum setting displayed using the setting rule in
Set the display at maximum frequency excluding the decimal point.
Set the number of digits displayed the decimal point.
Fig 6.66 Frequency Scaling Setting Rule
Example: When the max. output frequency value should be 200.0, set 12000: 2000 for the maximum display and 1 for the one digit behind the decimal point
Changing Frequency Reference Display Units (o1-09)
Additional to the scaling also units can be displayed if a Digital Operator with LCD clear text display is used.
The units are defined by parameter o1-09 and following units are available:
10
11
8
9
6
7
Setting
Value
0
1
4
5
2
3
Function
WC: Inch of water column
PSI: lb/square inch
GPM: Gallons per minute
F: Degree Fahrenheit
CFM: Cubic feet per minute
CMH: Cubic meter per hour
LPH: Liters per hour
LPS: Liters per second
Bar: Bar
Pa: Pascal
C: Degree Celsius
Mtr: Meters
Displayed Unit
WC
PSI
GPM
F
CFM
CMH
LPH
LPS
Bar
Pa
C
Mtr
6-111
6-112
Disabling the LOCAL/REMOTE Key (o2-01)
Set o2-01 to 0 to disable the LOCAL/REMOTE Key on the LED or LCD Digital Operator.
If the key is disabled, it cannot be used anymore to switch over the frequency reference source or the RUN command source between Digital Operator and the settings in b1-01 and b1-02.
Disabling the STOP Key (o2-02)
This parameter is used to set whether the STOP key on the LED or LCD Digital Operator is active during remote control (b1-02
≠ 0) or not.
If o2-02 is set to 1 a STOP command from the operators STOP key will be accepted, the Inverter will stop according to the method set in parameter b1-03 (Stopping method). If o2-02 is set to 0 it will be disregarded.
Initializing Changed Parameter Values (o2-03)
The current Inverter parameter setting values can be saved as user-set parameter values. Therefore parameter o2-03 has to be set to 1.
To initialize the Inverter parameters using the user-set initial values in memory parameter A1-03 has to be set to 1110. To clear the user-set initial values in memory set o2-03 to 2.
Setting the Frequency Reference using the UP and DOWN Keys without Using the
Enter Key (o2-05)
This function is active when the frequency reference is input from any Digital Operator. When o2-05 is set to
1 and the frequency reference is input via any Digital Operator the reference can be incremented or decremented using the UP and DOWN keys directly, pressing the ENTER button is not necessary.
Operation Selection when the Digital Operator is Disconnected (o2-06)
Parameter o2-06 selects whether a fault is detected when the Digital Operator is disconnected from the
Inverter.
If o2-06 is set to 0 the operation is continued.
If o2-06 is set to 1 the output is switched off and the motor coasts to stop, the fault relay is operated and the
Digital Operator Display shows an OPR fault when reconnected.
Cumulative Operation Time (o2-07 and o2-08)
The Inverter counts its operation time cumulatively.
Using parameter o2-07 the cumulative operation time can be changed, e.g. after a replacement of the control board. If parameter o2-08 is set to 0 the inverter counts the time whenever the power supply is switched ON. If o2-08 is set to 1 the time when a RUN command is active is counted only. The factory setting is 1.
Cooling Fan Operation Time (o2-10)
This function counts the operating time of the inverter mounted fan cumulatively.
Using parameter o2-10 the counter can be reset, e.g. when the fan was replaced.
Fault Trace Initialize (o2-12)
This function can be used to initialize the fault trace by setting parameter o2-12 to 1. All previously stored faults are deleted.
Energy Monitor Initialize (o2-14)
This function can be used to initialize the energy monitor by setting parameter o2-14 to 1.
Digital Operator Functions
HAND Key Function Selection (o2-15)
With this parameter the HAND key can be enabled by setting parameter o2-15 to 1. The factory setting is 0,
HAND key disabled. The parameter is effective only, if the optional HOA Digital Operator is used.
Standard / IP54 Selection (o2-17)
This parameter selects whether the Inverter is of protection class IP00 / NEMA 1 / IP20 (setting 0) or IP54
(setting 1). Whenever an Inverter in protection IP54 class is used o2-17 has to be set to 1. This switches the carrier frequency and temperature limit parameters to appropriate values.
Copying Parameters
The Digital Operator can perform the following three functions using a built-in EEPROM
•
Store 1 Inverter parameter set in the Digital Operator (READ)
•
Write 1 Inverter parameter set from the Digital Operator to the Inverter (COPY)
•
Compare 1 Inverter parameter set stored in the Digital Operator with the Inverter parameters settings
(VERIFY)
Related Parameters
Parameter
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
Access
Level o3-01 Copy function selection o3-02 Read permitted selection
0: Normal operation
1: READ (Inverter to Operator)
2: COPY (Operator to Inverter)
3: Verify (compare)
0: READ prohibited
1: READ permitted
Refer to the following pages for the procedures for using the copy function.
0 to 3
0 or 1
0
0
No
No
A
A
6-113
6-114
Storing Inverter set values in the Digital Operator (READ)
To store Inverter set values in the Digital Operator use the following method.
Step
No.
Digital Operator Display
LED Digital Operator LCD/HOA Digital Operator
Explanation
1
-ADV-
** Main Menu **
Programming
Press the MENU key until the Advanced Programming Mode is reached.
2
3
4
5
6
-ADV-
Initialization
A1 - 00=1
Select Language
-ADV-
COPY Function o3 - 01=0
Copy Funtion Sel
-ADV-
Copy Function Sel o3-01= 0
COPY SELECT
*0*
-ADV-
Copy Function Sel o3-01= 1
*0*
INV OP READ
-ADV-
READ
INV OP READING
Press the DATA/ENTER key to enter the Function Selection Display in Advanced Programming Mode.
Scroll to parameter o3-01 (Copy Function
Selection) using the Increment key and Decrement key.
Press the DATA/ENTER key to enter the
Parameter Setting Display.
Change the set value to 1 using the Increment key.
Press the DATA/ENTER key. The READ function will start.
7
-ADV-
READ
READ COMPLETE
-ADV-
Copy Function Sel o3 01 =0
COPY SELECT
*0*
When the READ function is completed “End” respectively “Read Complete” is displayed on the Digital Operator for appr. 1 second. Then the display returns to the Monitor Display and parameter o1-03 is automatically reset to 0.
If a fault is displayed press any key to clear the fault display and return to the o3-01 display. Fault displays and their meanings are shown below.
Select READ Prohibited
This function prevents overwriting of the data that are stored in the EEPROM of the Digital Operator. When o3-02 is set to 0 and o3-01 is set to 1 to perform a write operation PrE will be displayed on the Digital Operator and the write operation will be stopped.
If it is safe to overwrite the parameter set stored in the Digital Operator set o3-02 to 1 and start the READ function again by setting o3-01 to 1.
Digital Operator Functions
Writing Parameter Set Values Stored in the Digital Operator to the Inverter (COPY)
To write parameter set values stored in the Digital Operator to the Inverter, use the following method.
Step
No.
Digital Operator Display
LED Digital Operator LCD/HOA Digital Operator
Explanation
1
-ADV-
** Main Menu **
Programming
Press the MENU key until the Advanced Programming Mode is reached.
2
3
4
5
6
-ADV-
Initialization
A1 - 00 = 1
Select Language
-ADV-
COPY Function o3 - 01 = 0
Copy Funtion Sel
-ADV-
Copy Function Sel o3-01= 0
*0*
COPY SELECT
-ADV-
Copy Function Sel o3-01= 2
*0*
OP INV WRITE
-ADV-
COPY
OP INV COPYING
Press the DATA/ENTER key to enter the Function Selection Display in Advanced Programming Mode.
Scroll to parameter o3-01 (Copy Function
Selection) using the Increment key and Decrement key.
Press the DATA/ENTER key to enter the
Parameter Setting Display.
Change the set value to 2 using the Increment key.
Press the DATA/ENTER key. The COPY function will start.
7
-ADV-
COPY
COPY COMPLETE
-ADV-
Copy Function Sel o3 01 =0
COPY SELECT
*0*
If the COPY function is completed “End” respectively “Copy Complete” is displayed on the Digital Operator. Then the display returns to the Monitor Display and parameter o1-03 is automatically reset to 0.
If a fault is displayed press any key to clear the fault display and return to the o3-01 display. Fault displays and their meanings are shown on the following page.
6-115
6-116
Comparing Inverter Parameters and Digital Operator Parameter Set Values (VERIFY)
To compare Inverter parameters and Digital Operator parameter set values, use the following method.
Step
No.
1
Digital Operator Display
LED Digital Operator LCD/HOA Digital Operator
-ADV-
** Main Menu **
Programming
Explanation
Press the MENU key until the Advanced Programming Mode is reached.
2
3
4
5
6
-ADV-
Initialization
A1 - 00 = 1
Select Language
-ADV-
COPY Function o3
- 01=0
Copy Funtion Sel
-ADV-
Copy Function Sel o3-01= 0
*0*
COPY SELECT
-ADV-
Copy Funtion Sel o3-01= 3
*0*
OP INV VERIFY
-ADV-
VERIFY
DATA VERIFYING
Press the DATA/ENTER key to enter the Function Selection Display in Advanced Programming Mode.
Scroll to Parameter o3-01 (Copy Function
Selection) using the Increment key and Decrement key.
Press the DATA/ENTER key to enter the
Parameter Setting Display.
Change the set value to 3 using the Increment key.
Press the DATA/ENTER key. The VERIFY function will start.
7
-ADV-
VERIFY
VERIFY COMPLETE
-ADV-
Copy Function Sel o3 01 = 0
COPY SELECT
*0*
When the VERIFY function is completed
“End” respectively “Verify Complete is displayed on the Digital Operator for appr. 1 second. Then the display returns to the Monitor
Display and parameter o1-03 is automatically reset to 0.
If an fault is displayed, press any key to cancel the fault display and return to the o3-01 display. Fault displays and their meanings are shown below. (Refer to
Chapter 7, Digital Operator Copy Function Faults
.)
Application Precautions
When using the copy function, check that the following settings are the same between the Inverter and the
Digital Operator.
•
Inverter product and type
•
Software number
•
Inverter capacity and voltage
Digital Operator Functions
Prohibiting Writing Parameters from the Digital Operator
If A1-01 is set to 0 only the parameters A1-01 and A1-04 are displayed and can be set, U1-
U3 are displayed.
, U2-
are displayed and can be set, U1-
and
, U2If A1-01 is set to 1 only the parameters A1-01, A1-04 and A2-
and U3 are displayed.
If A1-01 is set to 2 all parameters are displayed and can be set.
When the parameter write enable function is programmed to one of the multi-function digital inputs (H1-
=1B) all parameters are write protected as long as this digital input is switched OFF. The moment it is switched ON the parameters can be changed.
Related Parameters
Parameter
Number
A1-01 Parameter access level
Name
Setting
Range
0 to 2
Factory
Setting
2
Change during
Operation
Yes
Access
Level
A
Multi-Function Digital Inputs (H1-01 to H1-05)
Set Value
1B Parameters write enable
Function
Setting a Password
When a password is set in A1-05, and if the set values in A1-04 and A1-05 do not match, the settings of parameters A1-01 to A1-03, or A2-01 to A2-32 can not be modified.
The setting of all parameters except A1-00 can be prohibited by using the password function in combination with setting A1-01 to 0 (Monitor only): As long as A1-04 does not match A1-05 parameter A1-01 can not be changed.
To set a password parameter A1-05 has to be accessed in following way:
Scroll to A1-04, hold the Shift/RESET key pressed and press the MENU key additional. A1-05 will be displayed and the Setting Display can be entered.
Related Parameters
Parameter
Number
A1-01 Parameter access level
Name
A1-04 Password
A1-05 Password setting
Setting
Range
0 to 2
0 to
9999
0 to
9999
Factory
Setting
2
0
Change during
Operation
Yes
No
Access
Level
A
A
0 No A
6-117
6-118
Displaying User-set Parameters Only
The A2 parameters (user-set parameters) and A1-01 (parameter access level) can be used to establish a parameter set that contains only the most important parameters.
Set the of the parameters to which A2-01 to A2-32 should refer to and then set A1-01 to 1. In Advanced Programming Mode now only the parameters assigned to A2-01 to A2-32 are displayed and can be changed.
Related Parameters
Parameter
Number
A2-01 to
A2-32
User-set parameters
Name
Setting
Range b1-01 to o3-02
Factory
Setting
Change during
Operation
– No
Access
Level
A
7
Troubleshooting
This chapter describes the fault displays and countermeasure for Inverter and motor problems.
Protective and Diagnostic Functions..................................7-2
Troubleshooting ...............................................................7-15
7-2
Protective and Diagnostic Functions
This section describes the alarm functions of the Inverter. The alarm functions include fault detection, alarm detection, operation error detection, and autotuning error detection.
Fault Detection
When the Inverter detects a fault, the fault relay operates, and the Inverter output is switched OFF causing the motor to coast to stop. (The stopping method can be selected for some faults.) A fault code is displayed on the
Digital Operator.
When a fault has occurred, refer to the following table to identify the fault and to correct the causes.
Use one of the following methods to reset the fault before restarting the Inverter:
•
Set a multi-function digital input (H1-01 to H1-05) to 14 (Fault Reset) and switch the input ON.
•
Press the Shift/RESET key on the Digital Operator.
•
Turn the main circuit power supply OFF and then ON again.
•
To reset a fault it is necessary to witch OFF the RUN command.
Table 7.1 Fault Detection
Display
OC
Over Current
GF
Ground Fault
PUF
DC Bus Fuse Open
OV
DC Bus Overvolt
Overcurrent
The Inverter’s output current exceeded the overcurrent detection level.
Meaning
Ground Fault
The ground fault current at the
Inverter output exceeded approximately 50% of the Inverter rated output current and L8-09=1
(Ground fault detection enabled)
Probable Causes
Shorted Inverter output phase-tophase, shorted motor, locked rotor, load too heavy, accel/decel time too short, contactor on the
Inverter output has opened or closed, a special motor or a motor with a rated current larger than the Inverter’s output current is used.
Corrective Actions
• Remove the motor and run the Inverter without motor
• Check the motor for a phase to phase short.
• Check the Inverter for a phase to phase short at the output.
• Verify the accel/decel time settings
One Inverter output was shorted to ground and/or a DCCT is defective.
• Remove the motor and run the Inverter without motor.
• Check the motor for a phase to ground short.
• Check the output current with a clampmeter to verify the DCCT reading.
DC Bus Fuse Blown
The fuse in the main circuit is open.
Warning:
Never run the Inverter after replacing the DC bus fuse without checking for shorted components
Shorted Inverter output and/or damaged IGBTs
• Check the motor and motor cables for short circuits or insulation failures (phase to phase
• Replace the Inverter after correcting the cause.
DC Bus Overvoltage
The DC bus voltage has exceeded the overvoltage detection level.
for the OV detection level.
• The deceleration time is too short and the regenerative energy from the motor is too large.
• The power supply voltage is too high.
• Increase the deceleration time settings (C1-02/04/09) or connect a braking option.
• Check the power supply voltage and decrease the voltage to meet the
Inverter’s specification.
Protective and Diagnostic Functions
Display
UV1
DC Bus Undervolt
UV2
CTL PS Undervolt
UV3
MC Answerback
PF
Input Phase Loss
OH
Heatsink Overtemp
Table 7.1 Fault Detection
Meaning
DC Bus Undervoltage
The DC bus voltage is below the
Undervoltage Detection Level
(L2-05). The default settings are:
200 V class: 190 VDC
400V class: 380VDC
Main Circuit MC Operation
Failure
The MC stopped responding during Inverter operation. (Applicable Inverter Capacities
200 V class: 37 to 110 kW
400 V class: 75 to 300 kW)
Probable Causes Corrective Actions
• The voltage fluctuations of the power supply are too high.
• A momentary power loss has occurred.
• The terminal screws of the input power supply are loose.
• An open-phase error occurred at the input terminals.
• The acceleration time is set too short.
• A fault occurred in the inrush current prevention circuit.
• Check the input voltage.
• Check the wiring of the input terminals.
• Increase the accel time settings C1-01/03.
• In case of Main Circuit MC
Operation Failure replace the Inverter.
Control Power Supply
Undervoltage
Undervoltage of the control circuit while the Inverter was running.
An external load at the control terminals was pulling down the
Inverter’s power supplies or there was an internal short in the power/gate drive board.
• Remove all connections to the control terminals and cycle the power to the
Inverter.
• Replace the Inverter.
Inrush Current Prevention Circuit
Fault
An overheating of the charging resistor for the DC bus capacitors occurred.
The contactor of the inrush current prevention circuit is defective.
The MC of the charging circuit did not respond 10 sec. after the
MC ON signal has been output.
(Applicable Inverter Capacities:
200 V class: 37 to 110 kW
400 V class: 75 to 300 kW)
• Cycle the power to the
Inverter.
• Replace the Inverter
Main Circuit Voltage Fault
An unusual big ripple on the DC bus voltage has been detected.
Only detected when L8-05=1, the detection level is set by L8-06
• An open-phase occurred in the input power supply.
• A momentary power loss occurred.
• The wiring terminals for the input power supply are loose.
• The voltage fluctuations in the input power supply are too high.
• The voltage balance between the phases is bad.
• Tighten the input terminal screws
• Replace the Inverter
Heatsink Overheat
The temperature of the Inverter's cooling fin exceeded the setting in L8-02 while L8-03 = 0 to 2.
Inverter's Cooling Fan Stopped
• The ambient temperature is too high.
• There is a heat source nearby.
• The Inverter's cooling fan(s) stopped.
• The Inverter's internal cooling fan has stopped and L8-32=1
• Check for dirt build-up on the fans or heatsink.
• Install a cooling unit.
• Remove the heat source.
• Replace the cooling fan(s)
OH1
Heatsnk MAX Temp
Heatsink Overheat
The temperature of the Inverter’s heatsink exceeded 105 °C
Inverter’s Cooling Fan Stopped
• The ambient temperature is too high.
• There is a heat source nearby.
• The Inverter's cooling fan(s) stopped.
• The Inverter's internal cooling fan has stopped.and L8-32=1
• Check for dirt build-up on the fans or heatsink.
• Install a cooling unit.
• Remove the heat source.
• Replace the cooling fan(s)
7-3
7-4
Display
OH3
Motor Overheat 1
Table 7.1 Fault Detection
Meaning
Motor Overheat
Detected when the level at A2, programmed for motor temperature (thermistor input, H3-09=E), exceeds 1.17 V for the time L1-
05 and L1-03 = 0 to 2.
Probable Causes
Overheating of the motor has been measured by the motor thermistor.
Corrective Actions
• Check the cycle time and the size of the load.
• Check the accel/decel times
(C1).
• Check the V/f pattern
(E1)
OH4
Motor Overheat 4
Motor Overheat
Detected when the level at A2, programmed for motor temperature (thermistor input, H3-09=e), exceeds 2.34 V for the time L1-
05.
Overheating of the motor has been measured by the motor thermistor.
• Check the cycle time and the size of the load.
• Check the accel/decel times
(C1).
• Check the V/f pattern
(E1)
OL1
Motor Overload
OL2
Inv Overload
OL3
Overtorque Det 1
OL7
HSB OL
LL3
Loss of Load Det
FBL
Feedback Loss
Motor Overload
Detected when L1-01 = 1 to 3 and the Inverter’s output current exceeded the motor overload curve.
Refer to
for parameter settings.
• The load is too large. The acceleration time, deceleration time and cycle time are too short.
• The voltage settings of the V/f pattern is incorrect for the application
• The setting of the Motor Rated
Current (E2-01) is incorrect.
• Check the cycle time, the size of the load and the accel/decel time settings
(C1).
• Check the setting of the V/f pattern (E1).
• Check the setting of Motor
Rated Current (E2-01)
Inverter Overload
The internally calculated I²t value
(based on the Inverter rated current) has exceeded its detection level.
• The load is too large. The acceleration time, deceleration time and cycle time are too short.
• The voltage settings of the V/f pattern is incorrect for the application
• The capacity of the Inverter is too small
• Check the cycle time, the size of the load and the accel/decel time settings
(C1).
• Check the setting of the V/f pattern (E1).
• Check the setting of Motor
Rated Current (E2-01)
• Check if the Inverter rated current matches the motor rated current.
Overload Detection
Inverter’s output current exceeded L6-02 for longer then the time set in L6-03 and L6-
01=3 or 4.
Motor was overloaded
• Ensure the values in L6-02 and L6-03 are appropriate
• Check the application/ machine status to eliminate fault.
High Slip Braking OL
The output frequency stayed constant for longer than the time set in n3-04 during High Slip Braking.
The inertia of the load is too large.
• Make sure the load is an inertial load.
• If possible, reduce the load inertia
Loss of Load Detection
Inverter’s output current was below L6-02 for longer then the time set in L6-03 and
L6-01= 7 or 8.
Motor lost its load
• Make sure that the settings in L6-02 and L6-03 are appropriate.
• Check the mechanical system (mechanical connection of the load, e.g. belt).
PI Feedback Lost
This fault occurs when PI feedback loss detection is programmed to fault (b5-12
= 2) and the PI feedback fell below the PI
Feedback Loss Detection Level
(b5-13) for the PI Feedback Loss
Detection Time (b5-14)
PI feedback source (e.g. transducer, sensor, building automation signal) is not installed correctly or is not working
• Check the PI feedback signal source for correct operation.
• Check the wiring of the PI feedback signal.
Protective and Diagnostic Functions
Display
EF0
External Fault
Meaning
External fault input from Communications Option Card
(F6-03=1 to 2)
Table 7.1 Fault Detection
Probable Causes
An external fault condition was present, input from a communication option card.
Corrective Actions
• Check for an external fault condition
• Verify the parameters
• Verify communication signals
EF3
Ext Fault S3
External fault at terminal S3
EF4
Ext Fault S4
External fault at terminal S4
EF5
Ext Fault S5
External fault at terminal S5
An "external fault" was input from a multi-function input terminal (S3 to S7).
Remove the cause of the external fault.
EF6
Ext Fault S6
External fault at terminal S6
External fault at terminal S7
EF7
Ext Fault S7
OPR
Oper Disconnect
Digital Operator Connection
Fault
Detected when the Digital Operator is removed and if o2-06 = 1.
CE
Memobus Com Err
MEMOBUS Communication
Fault
Detected when control data was not received correctly for 2 seconds and H5-04=0 to 3 and H5-
05=1.
The Digital Operator has been disconnected from the Inverter.
Connection is broken and/or the master has stopped the communication.
• Check the connection to the
Digital Operator.
• Check the connections and all user-side software configurations.
BUS
Option Com Err
CPF00
COM-
ERR(OP&INV)
CPF01
COM-
ERR(OP&INV)
Option Communication Fault
After initial communication was established, the connection was lost.
Connection is broken and/or the master as stopped the communication.
Digital Operator Communication
Fault 1
Communication with the Digital
Operator could not be established within 5 seconds after the power was supplied to the Inverter.
• The Digital Operator's cable was not securely connected.
• Digital Operator is defective.
• Control board is defective
• Check the connections and al user-side software configurations.
• Disconnect the Digital
Operator and then connect it again.
• Replace the Inverter.
• Cycle the Inverter power supply.
• Replace the Inverter.
CPU External RAM Fault
Digital Operator Communication
Fault 2
After communication with the
Digital Operator was established the communication stopped for 2 seconds or more.
• The Digital Operator's cable was not securely connected.
• Digital Operator is defective.
• Control board is defective
• Disconnect the Digital
Operator and then connect it again.
• Replace the Inverter.
• Cycle the Inverter power supply.
• Replace the Inverter.
7-5
7-6
Display
CPF02
BB Circuit Err
Meaning
Table 7.1 Fault Detection
Probable Causes
Baseblock Circuit Fault
A baseblock circuit error occurred at power-up.
Gate array hardware failure at power-up.
CPF03
EEPROM Error
EEPROM Fault
Checksum is not valid.
Noise or spikes was on the control circuit input terminals or the control board is damaged.
Corrective Actions
CPF04
Internal A/D Err
CPU Internal A/D Converter
Fault
Noise or spikes was on the control circuit input terminals or the control board is damaged.
CPF05
External A/D Err
CPU External A/D Converter
Fault
CPF06
Option Error
Noise or spikes was on the control circuit input terminals or the control board is damaged.
Option Card Connection Error
• The Option Card is not connected properly.
• The Inverter or Option Card is faulty.
• Try to initialize the Inverter.
• Cycle the Inverter power.supply.
• Replace the Inverter.
ASIC Internal RAM Fault The control circuit is damaged.
CPF07
RAM-Err
Watchdog Timer Fault The control circuit is damaged.
CPF08
WAT-Err
CPU-ASIC Mutual Diagnosis
Fault
The control circuit is damaged.
CPF09
CPU-Err
ASIC Version Fault The control circuit is damaged.
CPF10
ASIC-Err
CPF20
Option A/D Error
Communications Option Card
A/D Converter Fault
• The Option Card is not connected properly.
• The Option Card's A/D converter is faulty.
• Turn off the power and reinstall the option board.
• Remove all inputs from the option board.
• Try to initialize the Inverter.
• Cycle the power to the
Inverter.
• Replace the Option Board.
• Replace the Inverter.
Protective and Diagnostic Functions
Display
CPF21
Option CPU Down
CPF22
Option Type Err
CPF23
Option DPRAM Err
Self-Diagnosis Fault of Option
Board
Option Board Interconnection
Fault
Meaning
Option Board Code Number
Fault
Table 7.1 Fault Detection
Probable Causes Corrective Actions
Noise or spikes was on the control circuit input terminals or the control board is damaged.
Unrecognizable option board is connected to the control board.
An option board was not correctly connected to the control board or an option board that was not made for the Inverter is attached to the control board.
• Turn off the power and reinstall the option board.
• Remove all inputs from the option board.
• Try to initialize the Inverter.
• Cycle the power to the
Inverter.
• Replace the Option Board.
• Replace the Inverter.
7-7
7-8
Alarm Detection
Alarms are detected as a type of Inverter protection function that do not operate the fault relay output. The system will automatically return to its original status when the cause of the alarm has been removed.
The Digital Operator display and the Alarm LED flashes and the alarm can be output at the multi-function outputs (H2-01 or H2-02). As long as the Inverter remains in Alarm status it can not be started and will not accept parameter changes.
When an alarm occurs, take appropriate countermeasures according to the table below.
Table 7.2 Alarm Content
Display
(flashing)
EF
External Fault
(flashing)
(flashing)
UV
DC Bus Undervolt
(flashing)
(flashing)
OV
DC Bus Overvolt
(flashing)
Meaning
Forward/Reverse Run Commands Input Together
Both the forward and the reverse run commands are input simultaneously for 500 msec or more.
This alarm will decelerate the motor stop
Probable Causes
The external forward and reverse command were input simultaneously.
Corrective Actions
Check external sequence logic, so only one input is received at a time.
DC Bus Undervoltage
The DC bus voltage is below the
Undervoltage Detection Level
(L2-05). The default settings are:
200 V class: 190 VDC
400 V class: 380 VDC
The MC of the inrush current prevention circuit opened.
The control power supply voltage was below the CUV level.
• The voltage fluctuations of the power supply are too high.
• A momentary power loss has occurred.
• The terminal screws of the input power supply are loose.
• An open-phase error occurred at the input terminals.
• The acceleration time is set too short.
• A fault occurred in the inrush current prevention circuit.
• An external load at the control terminals was pulling down the
Inverter’s power supplies or there was an internal short in the power/gate drive board.
• Check the input voltage.
• Check the wiring of the input terminals.
• In case of Main Circuit MC
Operation Failure replace the Inverter.
• Remove all connections to the control terminals and cycle the power to the
Inverter.
• Replace the Inverter.
DC Bus Overvoltage
The DC bus voltage exceeded the overvoltage detection level.
for the OV detection level.
OV Alarm is only detected when the drive is in a stopped condition
The power supply voltage is too high.
Check the power supply and decrease the voltage to meet the Inverter’s specifications
(flashing)
OH
Heatsnk Overtmp
(flashing)
Heatsink Overheat Alarm
The temperature of the Inverter's cooling fin exceeded the setting in L8-02 while L8-03 = 3
• The ambient temperature is too high.
• There is a heat source nearby.
• The Inverter cooling fan(s) has stopped.
• Check for dirt build-up on the fans or heatsink.
• Install a cooling unit.
• Remove the heat source.
(flashing)
OH3
Motor Overheat 1
(flashing)
Motor Overheat Alarm
Detected when the level at A2, programmed for motor temperature (thermistor input, H3-09=E), exceeds 1.17 V for the time L1-
05 and L1-03 = 3
Overheating of the motor has been measured by the motor thermistor.
• Check for dirt build-up on the fans or heatsink.
• Install a cooling unit.
• Remove the heat source.
Protective and Diagnostic Functions
Display
(flashing)
OL3
Overtorque Det.1
(flashing)
(flashing)
LL3
Loss of Load Det
(flashing)
EF0
Opt External Flt
(flashing)
Table 7.2 Alarm Content
Overload Detection
The Inverter’s output current exceeded L6-02 for longer than the time set in L6-03 and
L6-01 = 1 or 2.
External Fault Input from Communication Option Card (Alarm only)
(F6-03=3)
Meaning
Loss of Load Detection
Inverter’s output current was below L6-02 for longer then the time set in L6-03 and L6-01=5 or
6.
Probable Causes
Motor was overloaded
Motor lost its load
Corrective Actions
• Ensure that the values in
L6-02 and L6-03 are appropriate
• Check the application/ machine status to eliminate the fault.
• Make sure that the settings in L6-02 and L6-03 appropriate
• Check the application/ machine status to eliminate the alarm.
An external fault condition was present, input from a communication option card while F6-03 is set to Alarm only.
• Check for an external fault condition.
• Verify the parameter settings.
• Verify communication signals.
(flashing)
EF3
Ext Fault S3
(flashing)
External fault at terminal S3
(Alarm only)
(flashing)
EF4
Ext Fault S4
(flashing)
External fault at terminal S4
(Alarm only)
(flashing)
EF5
Ext Fault S5
(flashing)
External fault at terminal S5
(Alarm only)
An external fault was input from a multi-function digital input
(H1-01 to H1-05) that is programmed for external fault function that gives an alarm only and continues to run the motor.
Remove the cause of the external fault.
(flashing)
EF6
Ext Fault S6
(flashing)
External fault at terminal S6
(Alarm only)
(flashing)
EF7
Ext Fault S7
(flashing)
External fault at terminal S7
(Alarm only)
(flashing)
FBL
Feedback Loss
PI Feedback Lost
This alarm occurs when PI feedback loss detection is programmed to alarm (b5-12=1) and the PI feedback fell below the PI
Feedback Loss Detection Level
(b5-13) for the PI Feedback Loss
Detection (b5-14).
PI feedback source (e.g. transducer, sensor, building automation signal) is not installed correctly or is not working.
• Check the PI feedback signal source for correct operation.
• Check the wiring of the PI feedback signal.
7-9
7-10
Display Meaning
Table 7.2 Alarm Content
Probable Causes Corrective Actions
(flashing)
CE
MEMOBUS Com
Err
(flashing)
MEMOBUS Communications
Alarm
Detected when control data was not received correctly for 2 seconds and H5-04=4 and H5-05=1.
Connection is broken and/or the master has stopped the communication.
Check the connections and all user-side software configurations.
(flashing)
BUS
Option Com Err
(flashing)
Option Card Communications
Alarm
After initial communication was established, the connection was lost.
Connection is broken and/or the master has stopped the communication.
Check the connections and all user-side software configurations.
(flashing)
CALL
ComCall
(flashing)
DNE
Drive not Enable
(flashing)
(flashing)
Ext Run active
Cannot Reset
(flashing)
PRHT
Motor Preheating
(flashing)
Communication on Standby
Communication has not yet been established.
Connection was not made properly or user software was not configured to the proper baud rate or configuration (e.g. Parity)
Check the connections and all user-side software configurations.
Drive not Enabled
Detected when a multi-function digital input (H1-01 to H1-05) is programmed for 6A or 70.
The Inverter does not have the enable command when the RUN command is applied.
This alarm decelerates the motor.
• Enable command was lost while the Inverter was running.
• The RUN command was applied prior to the enable signal.
• Check the wiring and sequence of the external signals.
• Apply and maintain the enable command before applying the RUN signal
Detected when a RESET command is input while the RUN command is still active.
The RUN command has not been removed and a RESET command is input by digital input or by the
RESET button on the Digital
Operator.
Remove the RUN signal first and reset the fault.
Motor is preheating.
One of the digital inputs (H1-01 to H1-05) is programmed to 60 or
80 and the input is switched ON.
• Check the wiring and sequence of the external signals.
• Check the parameter settings.
(flashing)
OVRD
Emergcy Override
(flashing)
Emergency Override is active
On of the digital inputs (H1-01 to
H1-05) is programmed to 81 or
82 and the input is switched ON
• Check the wiring and sequence of the external signals.
• Check the parameter settings.
(flashing)
FAN
Cooling FAN Err
Internal Cooling Fan Alarm
The Inverter’s internal cooling fan failed while L8-32=0
The Inverter’ internal cooling fan failed or is blocked.
• Check the internal cooling and clean it in case it is dirty.
• Replace the cooling fan or the Inverter.
Protective and Diagnostic Functions
Operator Programming Errors
An Operator Programming Error (OPE) occurs when an inapplicable parameter is set or an individual parameter setting is inappropriate. The Inverter will not operate until the parameter is set correctly; however, no alarm or fault outputs will occur. If an OPE occurs, change the appropriate parameter by checking the cause shown in Table 7.3. When OPE error is displayed, press the ENTER key to display U1-34 (OPE Detected).
This monitor will display the parameter that is causing the OPE error.
Table 7.3 Operator Programming Errors
Display
OPE01 kVA Selection
Meaning
Inverter kVA Setting Error
Probable Causes
The control board was replaced and the kVA parameter (o2-04) is set incorrectly
Corrective Action
Enter the correct kVA setting (o2-04) by referring to the table “Factory settings that change with the Inverter kVA setting“on page 5-60.
OPE02
Limit
Parameter Setting Out of Range
Parameter setting was outside of the allowed range.
Verify the parameter settings.
OPE03
Terminal
OPE05
Sequence Select
Multi-function Input
Selection Error
RUN/Reference Command
Selection Error
The Reference Source Selection b1-01 and/or the RUN Source
Selection parameter b1-02 are set to 3 (option board) but no option board is installed.
One of the following errors has been made in the multi-function input (H1-
01 to H1-05) settings:
• Duplicate functions were selected.
• UP/DOWN command (setting 10 and 11) were not set simultaneously.
• The UP/DOWN commands (10 and 11) and Accel/decel ramp hold
(A) were set at the same time.
• More than one of the Speed Search inputs (61, 62, 64) were set simoultaneosly.
• External Baseblock NO (8) and
External Baseblock NC (9) were set at the same time.
• The UP/DOWN commands (10 and 11) were selected while PI
Control (b5-01) was enabled.
• The Emergency Stop Command
NO and NC were set at the same time.
• Motor Preheat (60) and Motor Preheat 2 (80) were set simultaneously.
• Emergency Override FWD (81) and Emergency Override REV (82) are set simultaneously.
Verify the parameter settings in H1-
Option board is not installed or is installed incorrectly
• Verify that the board is installed. Switch off the power supply and re-install the option board.
• Recheck the setting of b1-01 and b1-02.
7-11
7-12
Display
OPE09
PI Selection
OPE10
V/f Ptrn Setting
OPE11
CarrFrq/On-Delay
ERR
EEPROM R/W Err
Table 7.3 Operator Programming Errors
Meaning
PI Control Setup Error
V/f Parameter Setting Error
Probable Causes
The following settings have been made at the same time.
• b5-01 (PI Control Mode Selection) has been set to a value different from 0.
• b5-15 (PI Sleep Function Operation Level) has been set to a value different from 0.
• b1-03 (Stopping Method Selection) has been set to 2 or 3.
Corrective Action
Check the settings of parameters b5-01, b5-15 and b1-03
Parameters E1-04, E1-06, E1-07, E1-
09 and E1-11 do not satisfy the following conditions:
• E1-04 (FMAX)
≥ E1-11 (FMID2)
> E1-06 (FA) > E1-07 (FB) ≥ E1-
09 (FMIN)
• Check the parameter settings of E1-
• A frequency/voltage value might be set higher than the maximum frequency/voltage.
Carrier Frequency Parameter Setting Error
One of the following parameter setting errors exists:
• Carrier frequency Gain C6-05 > 6 and C6-03 (Carrier Frequency
Upper Limit) < C6-04 (Carrier Frequency Lower Limit)
• Upper/lower limit error in C6-03 and C6-04.
Check the parameter settings of C6-02 to C6-05.
EEPROM write error
The NV-RAM data do not match the EEPROM data
A verification error occurred when writing EEPROM.
• Cycle the Inverter power supply.
• Try to initialize the
Inverter.
Protective and Diagnostic Functions
Autotuning Faults
Auto-tuning faults are shown below. When the following faults are detected, the fault is displayed on the digital operator and the motor coasts to stop. No fault or alarm outputs will be operated.
Table 7.4 Autotuning Faults
Display
Er - 01
Fault
Meaning
Motor data fault
Probable causes
• There is an error in the data input for autotuning.
• There is an error in the relationship between the motor power and the motor rated current.
Corrective Actions
• Check the input data.
• Check the Inverter and motor capacity.
• Check the motor rated current setting.
Er - 02
Minor Fault
Alarm
An alarm is detected during autotuning.
• Check the input data.
• Check wiring and the machine.
• Check the load.
STOP key input
The STOP key was pressed to cancel autotuning.
-
Er - 03
STOP key
Er - 04
Resistance
Line-to-Line Resistance Fault
• Autotuning was not completed in the specified time.
• The autotuning result is outside the parameter setting range.
End - 3
Rated FLA Alm
Rated current setting alarm.
Displayed after autotuning is completed.
The rated current is set too high.
• Check the input data.
• Check motor wiring.
Check the motor rated current value.
Digital Operator Copy Function Faults
These faults can occur during the digital operator COPY function. When a fault occurs, the fault content is displayed on the operator. A fault does not activate the fault relay output or alarm output.
Table 7.5 Digital Operator Copy Function Faults
Function
Display Probable causes Corrective Actions
PRE
READ IMPOSSIBLE o3-01 was set to 1 to read parameters when the Digital Operator was write-protected (o3-02 = 0).
Set o3-02 to 1 to enable writing parameters into the Digital Operator’s memory.
Read
IFE
READ DATA ERROR
The data file read from the Inverter was of the wrong size indicating corrupted data.
• Retry the read command.
• Check the Digital Operator’s cable
• Replace the Digital Operator
RDE
DATA ERROR
An attempted wring of the Inverter data to the Digital Operator’s EEPROM failed.
• A low Inverter voltage has been detected.
• Retry the read command
• Replace the Digital Operator.
7-13
7-14
Function
Display
Table 7.5 Digital Operator Copy Function Faults
Probable causes Corrective Actions
Copy
CPE
ID UNMATCHED
The Inverter type or software number was different from the stored data in the digital operator
Use stored data of the same product (E7) and software number (U1-14) only.
VAE
INV. KVA UNMATCH
The capacity of the Inverter and the capacity of the stored data in the Digital
Operator are different.
Use stored data for the same Inverter capacity only (o2-04).
A parameter setting written to the
Inverter was different from the setting stored in the Digital Operator.
Retry the COPY function (o3-01 = 2)
CYE
COPY ERROR
CSE
SUM CHECK ERROR
Upon completion of the COPY function, the Inverter’s data checksum was different than the digital operator’s data checksum.
Retry the COPY function (o3-01 = 2)
Verify
VYE
VERIFY ERROR
The set value of the digital operator and the Inverter do not match
Retry the VERIFY function (o3-01 = 3)
Troubleshooting
Troubleshooting
Due to parameter setting errors, faulty wiring, and so on, the Inverter and motor may not operate as expected when the system is started up. If that occurs, use this section as a reference and perform the appropriate counter measures.
If the contents of the fault are displayed, refer to
Protective and Diagnostic Functions
If Parameters Cannot Be Set
The display does not change when the Increment and Decrement keys are pressed.
The following causes are possible.
The Inverter is operating (Drive Mode).
There are some parameters that cannot be set during operation. Turn off the RUN command and then make the settings.
Parameter write enable is input.
This occurs when "Parameters write enable" (set value: 1B) is set for a multi-function digital input (H1-01 to
H1-05). If the parameter write enable input is OFF, the parameters cannot be changed. Turn it ON and then set the parameters.
Passwords do not match. (Only when a password is set.)
If the parameter A1-04 (Password) and A1-05 (Password Setting) numbers are different, the parameters for the initialize mode cannot be changed. Reset the password.
If you cannot remember the password, display A1-05 (Password Setting) by pressing the Shift/RESET key and the MENU key simultaneously while in the A1-04 display. Then reset the password. (Input the reset password in parameter A1-04.)
OPE01 through OPE11 is displayed.
The set value for the parameter is wrong. Refer to
page 7-11, Operator Programming Errors
in this chapter and correct the setting.
CPF00 or CPF01 is displayed.
This is a Digital Operator communications error. The connection between the Digital Operator and the
Inverter may be faulty. Remove the Digital Operator and then re-connect it.
7-15
7-16
If the Motor Does Not Operate
The motor does not operate when the RUN key on the Digital Operator is pressed.
The following causes are possible.
The operation method setting is wrong.
If parameter b1-02 (RUN command source selection) is set to 1 (control circuit terminal), the motor will not operate when the RUN key is pressed. Either press the LOCAL/REMOTE key to switch to Digital Operator operation or set b1-02 to 0 (Digital Operator).
NOTE
The LOCAL/REMOTE key can be enabled or disabled by setting o2-01. It is enabled when the Drive
Mode is entered and o2-01 is set to 1.
The frequency reference is too low.
If the frequency reference is set below the frequency set in E1-09 (Minimum Output Frequency), the Inverter will not operate.
Raise the frequency reference to at least the minimum output frequency.
The motor does not operate when an external operation signal is input.
The following causes are possible.
The Inverter is not in Drive Mode.
If the Inverter is not in drive mode, it will remain in ready status and will not start. Press the MENU key make the DRIVE LED flash, and enter the drive mode by pressing the DATA/ENTER key. The DRIVE LED will light up when Drive Mode is entered.
The RUN command source selection is wrong.
If parameter b1-02 (reference selection) is set to 0 (Digital Operator), the motor will not operate when an external operation signal is input. Set b1-02 to 1 (control circuit terminal) and try again.
The motor will also not operate if the LOCAL/REMOTE key has been pressed to switch to Digital Operator operation. In that case press the LOCAL/REMOTE key again to return to the original setting.
NOTE
The LOCAL/REMOTE key can be enabled or disabled by setting o2-01. It is enabled when the drive mode is entered and o2-01 is set to 1.
3-wire control is enabled.
The input method for a 3-wire control is different than when operating by forward/stop and reverse/stop (2wire control). If a 3 wire control is selected, the motor will not operate when a wiring that is suitable for 2-wire control is used. When using a 3-wire control, refer to the wiring example and timing chart on
page 6-10, Performing Operations Using 3-Wire Control
and input the proper signals.
When using a 2-wire control, set the multi-function digital input (H1-01 through H1-05, terminals S3 to S7) to a value other than 0.
Troubleshooting
The frequency reference is too low.
If the frequency reference is set below the frequency set in E1-09 (Minimum Output Frequency), the Inverter will not operate. Raise the frequency reference to at least the minimum output frequency.
The motor stops during acceleration or when a load is connected.
The load may be too heavy. The Inverter has a stall prevention function and an automatic torque boost function (Torque Compensation), but the motor has a limited responsiveness which might be overloaded if acceleration is too rapid or if the load is too heavy. Lengthen the acceleration time or reduce the load. Also consider increasing the motor and/or Inverter capacity.
The motor rotates in one direction only.
Reverse run is disabled. If b1-04 (Prohibition of reverse operation) is set to 1 or 3(reverse run prohibited), the
Inverter will not accept reverse run commands. To use both forward and reverse operation, set b1-04 to 0 or 2.
If the Direction of the Motor Rotation is Reversed
If the motor rotates in the wrong direction, the motor output wiring may be incorrect. When the Inverter operates in the forward direction, the forward direction of the motor will depend on the manufacturer and the motor type, so be sure to check the motor specification
The direction of the motor rotation can be reversed by switching two wires among U, V, and W. If using an encoder, the polarity will also have to be switched. Also parameter b1-04 can be used to change the rotational direction.
If the Motor Does Not Put Out Torque or If Acceleration is Slow
The stall prevention level during acceleration is too low.
If the value set for L3-02 (Stall Prevention Level during Acceleration) is too low, the acceleration time will be very long. Check to be sure that the set value is suitable.
The stall prevention level during run is too low.
If the value set for L3-06 (Stall Prevention Level during Run) is too low, the speed may drop already at low output torque. Check to be sure that the set value is suitable.
If the Motor Operates at Higher Speed than the Frequency Reference
The analog frequency reference bias or gain setting is wrong.
The frequency reference bias or gain set in parameter H3-03 or H3-02 influence the frequency reference.
Check to be sure that these set values are suitable.
PI control is enabled.
If the PI control is enabled (b5-01 = 1 or 2), the Inverter output frequency will change to regulate the process variable to the desired set point. The PID can command a speed up to Maximum Output Frequency (E1-04) even though the reference is much lower.
7-17
7-18
A signal is being input to the multifunction analog input terminal A2.
When “0” (frequency bias) is set for parameter H3-09 (Analog Input A2 Function Selection) a frequency corresponding to the terminal A2 input voltage (current) is added to the frequency reference. Check to be sure that the set value and analog input value are suitable.
If Motor Deceleration is Slow
The deceleration time is long even when a braking option is connected.
The following causes are possible.
Stall prevention during deceleration enabled is set.
When a braking option is connected, set parameter L3-04 (Stall Prevention Selection during Deceleration) to 0
(disabled). When this parameter is set to 1 (enabled), the braking option will not work properly.
The deceleration time setting is too long.
Check the deceleration time setting (parameters C1-02 and C1-04).
Motor torque is insufficient.
If the parameters are correct and there is no overvoltage fault, maybe then the motor's power limit is reached.
Consider increasing the motor capacity.
If the Motor Overheats
The load is too heavy.
If the motor load is too heavy and the motor is used continuously with a torque that exceeds the motor's rated torque, the motor will overheat. Reduce the load amount by lowering the load. Also consider increasing the motor capacity.
The ambient temperature is too high.
The motor rating is determined within a particular ambient operating temperature range. The motor will burn out if it is run continuously at the rated torque in an environment in which the maximum ambient operating temperature is exceeded. Lower the motor's ambient temperature to be within its acceptable range.
Troubleshooting
If peripheral devices like PLCs or other are influenced by the starting or running inverter
If electrical noise is generated by Inverter perform the following countermeasures:
•
Change the Inverter's Carrier Frequency Selection (C6-02) to lower the carrier frequency. This will help to reduce the amount of transistor switching noise.
•
Install an Input Noise Filter at the Inverter's power input terminals.
•
Install an Output Noise Filter at the Inverter's motor terminals.
•
Use shielded cables or a conduit. Metal shields electrical noise.
•
Separate main circuit wiring from control circuit wiring.
If the Earth Leakage Breaker Operates when a RUN Command is Input
The Inverter’s output is pulse modulated, i.e. the output voltage consists of high frequency pulses (PWM).
This high frequency signal causes a certain amount of leakage current which may cause the earth leakage breaker to operate and cut off the power supply. Change to a ground fault interrupter with a high leakage detection level (i.e., a sensitivity current of 200 mA or higher, with an operating time of 0.1 s or more), or one that incorporates high frequencies countermeasures (i.e., one designed for use with Inverters). It will also help to some extent to lower the Inverter's Carrier Frequency Selection (C6-02). In addition, remember that the leakage current increases as the cable is lengthened.
If There is Mechanical Oscillation
The machinery is making unusual sounds.
There may be resonance between the mechanical system's natural frequency and the carrier frequency.
This is characterized by the motor running with no noise generation, but the machinery vibrates with a highpitched whine. To prevent this type of resonance, adjust the carrier frequency with parameters C6-02 to
C6-05.
There may be resonance between a mechanical system’s natural frequency and the output frequency of the Inverter.
To prevent this resonance frequency use the Jump Frequency Function in parameters d3, or have the driven motor and load balanced to reduce vibration.
Oscillation and hunting occur.
The torque compensation parameter settings may be incorrect for the machine. Adjust parameters C4-01
(Torque Compensation Gain) and C4-02 (Torque Compensation Delay Time). Decrease C4-01 carefully in steps of 0.05 and/or increase C4-02.
Furthermore the Hunting Prevention Gain (n1-02) can be increased if the problems occur in light load conditions and the Slip Compensation Delay Time (C3-02) can be decreased.
Oscillation and hunting occur with PI control.
If there is oscillation or hunting during PI control, check the oscillation cycle and individually adjust P and I parameters (refer to
7-19
7-20
If the Motor Rotates Even When Inverter Output is Stopped
If the motor coasts at low speed after a deceleration to stop has been executed, it means that the DC injection braking is not decelerating enough. Adjust the DC injection braking as follows:
•
Increase the parameter b2-02 (DC Injection Braking Current) setting.
•
Increase the parameter b2-04 (DC Injection Braking (initial excitation) Time at Stop) setting.
If OV (Overvoltage) or OC (Overcurrent) is Detected When a Fan is
Started, or a Fan Stalls
If a fan is windmilling (already rotating in an airstream) and the Inverter tries to start the motor from zero speed on OV (DC bus overvoltage) or OC (Overcurrent) might occur. This can be prevented by stopping the fan rotation using DC injection braking before starting the fan. Alternatively the speed search function can be used to catch the rotating motor.
If Output Frequency Does Not Rise to Frequency Reference
The frequency reference is within the jump frequency range.
When the jump frequency function is used, the output frequency does not change within the jump frequency range. Check to be sure that the Jump Frequency (d3-01 to d3-03) and Jump Frequency Width (d3-04) settings are suitable.
The frequency reference upper limit has been reached.
The output frequency upper limit is determined by the following formula:
Freq Ref Upper Limit = Max. Output Frequency (E1-04)
× Frequency Reference Upper Limit (d2-01) / 100
Check to be sure that the parameter E1-04 and d2-01 settings are suitable.
8
Maintenance and
Inspection
This chapter describes basic maintenance and inspection for the Inverter.
Maintenance and Inspection ..............................................8-2
8-2
Maintenance and Inspection
Periodic Inspection
Periodic Inspection for Inverters of Protection Class IP00 and NEMA 1/ IP20
Check the following items during periodic maintenance.
•
The motor should not vibrate or make unusual noises.
•
There should be no abnormal heat generation from the Inverter or motor.
•
The ambient temperature should be within the Inverter’s specifications.
•
The output current value shown in U1-03 should not be higher than the motor or the Inverter rated current for extended period of time.
•
The cooling fan in the Inverter should be operating normally.
Before attempting any maintenance checks, make sure that the three-phase power is disconnected. With power removed from the unit, the DC bus capacitors will stay charged for several minutes. The Charge LED in the
Inverter will glow red until the DC bus voltage is below 10VDC. To ensure that the DC bus is completely discharged, measure between the positive and negative bus with a DC voltmeter set to the highest scale. Be sure not to touch terminals immediately after the power has been turned off. Doing so can result in electric shock.
Table 8.1 General Inspection Items for Inverters of all Protection Classes
Item
External terminals
Mounting bolts
Connectors
Inspection
Are all screws and bolts tight?
Corrective Procedure
Tighten loose screws and bolts firmly.
Cooling fins
All PCBs
Input Diodes
Output Transistors
Power Modules
DC bus capacitors
Are connectors tight?
Reconnect the loose connectors.
Are the fins dirty or dusty?
Is there any conductive dirt or oil mist on the PCBs?
Is there any conductive dirt or oil mist on the modules or components?
Clean off any dirt and dust with an air gun using dry air at a pressure of 4 x 10
5
to 6 x 10
5
Pa
(4 to 6 bar, 55 to 85 psi).
Clean off any dirt and dust with an air gun using dry air at a pressure of 4 x 10
5
to 6 x 10
5
Pa
(4 to 6 bar, 55 to 85 psi).
Replace the boards if they cannot be made clean.
Clean off any dirt and dust with an air gun using dry air at a pressure of 4 x 10
5
to 6 x 10
5
Pa
(4 to 6 bar, 55 to 85 psi).
Are there any irregularities, such as discoloration or odor?
Replace the capacitor or Inverter.
Apply power to the Inverter and conduct the following inspection:
Item
Cooling Fan(s)
Inspection
Is there any abnormal noise or vibration, or has the total operating time exceeded
20,000 hours.
Check U1-40 for the elapsed cooling operation time.
Corrective Procedure
Replace Cooling Fan
Additional Information for Inverters in Protection Class IP54
After switching off the power supply wait at least for five minutes before beginning the inspection. Before opening the door ensure that the space around the Inverter is dry and clean. Water must not splash into the
Inverter box as it may destroy the Inverter and can result in electric shock.
Keep any water or dust outside of the Inverter box during the Inspection
Refer to the following table for additional inspection items for IP54 Inverters.
Maintenance and Inspection
Item
External terminals
Mounting bolts
Connectors
Cooling fins
Cooling Fan
All PCBs
Input Diodes
Output Transistors
Power Modules
DC bus capacitors
Cable Glands
Table 8.2 Inspection Items for IP54 Inverters
Inspection
Are all screws and bolts tight?
Corrective Procedure
Tighten loose screws and bolts firmly.
Are connectors tight?
Reconnect the loose connectors.
Are the fins dirty or dusty?
Are the cooling fans dirty or dusty
Is there any conductive dirt or oil mist on the PCBs?
Clean off any dirt and dust with an air gun using dry air at a pressure of 4 x 10
5
to 6 x 10
5
Pa
(4 to 6 bar, 55 to 85 psi).
7.5 to 18.5 kW:
External cooling fan is attached on the lower side in the wind tunnel.
Check the fan from the bottom and clean off any dirt in the same way as cleaning the cooling fin.
22 to 55 kW:
External cooling fan is attached on the upper side in the wind tunnel.
Check the fan from the top and clean off any dirt in the same way as cleaning the cooling fin.
Clean off any dirt and dust with an air gun using dry air at a pressure of 4 x 10
5
to 6 x 10
5
Pa
(4 to 6 bar, 55 to 85 psi).
Replace the boards if they cannot be made clean.
Is there any conductive dirt or oil mist on the modules or components?
Clean off any dirt and dust with an air gun using dry air at a pressure of 4 x 10
5
to 6 x 10
5
Pa
(4 to 6 bar, 55 to 85 psi).
Are there any irregularities, such as discoloration or odor?
Replace the capacitor or Inverter.
Are the cable glands tightened properly?
Tighten the cable glands and locknuts.
Apply power to the Inverter and conduct the following inspection:
Item
Cooling Fan(s)
Inspection
Is there any abnormal noise or vibration, or has the total operating time exceeded
20,000 hours.
Check U1-40 for the elapsed cooling operation time.
Corrective Procedure
Replace Cooling Fan
8-3
8-4
Periodic Maintenance of Parts
In order to keep the Inverter operating normally over a long period of time, and to prevent down time due to an unexpected failure, it is necessary to perform periodic inspections and replace parts according to their service life.
The data indicated in the following table is to be used as a general guideline only. Periodic inspection standards vary depending on the Inverter’s installation environment conditions and usage. The Inverter’s suggested maintenance periods are noted below.
Cooling fan(s)
Part
DC bus capacitor
Standard Replacement Period
2 to 3 years (20,000 hours)
5 years
–
Replacement Method
Replace with new part.
Replace with new part.
(Determine need by inspection.)
Determine need by inspection.
Soft charge contactor
DC bus fuse
Control power fuse
10 years Replace with new part.
PCB capacitors 5 years
Replace with new board.
(Determine need by inspection.)
Note:The standard replacement period is based on the following usage conditions:
Ambient temperature: Yearly average of 30
°C
Load factor: 80% max.
Operating rate: 12 hours max. per day
Maintenance and Inspection
Cooling Fan Replacement Outline
200 V and 400 V Class Inverters of 18.5 kW or Less
A cooling fan is attached to the bottom of the Inverter.
If the Inverter is installed using the mounting holes on the back of the Inverter, the cooling fan can be replaced without removing the Inverter from the installation panel.
Removing the Cooling Fan
1. Press in on the right and left sides of the fan cover in the direction of arrows 1 and when pull the fan out in the direction of arrow 2.
2. Pull out the cable connected to the fan from the fan cover and disconnect the cable.
3. Open the fan cover on the left and right sides and remove the fan cover from the fan.
1
Air flow direction
2
1
Fan cover
Fig 8.1 Cooling Fan Replacement (Inverters of 18.5 kW or Less)
Mounting the Cooling Fan
1. Attach the fan cover to the cooling fan. Be sure that the air flow direction is correct (see figure above).
2. Connect the cables securely and place the connector and cable into the fan cover.
3. Mount the fan cover on the Inverter. Be sure that the tabs on the sides of the fan cover click into place on the Inverter heatsink.
8-5
200 V and 400 V Class Inverters of 22 kW or More
A cooling fan is attached to the top panel inside the Inverter.
The cooling fan can be replaced without removing the Inverter from the installation panel.
Removing the Cooling Fan
1. Remove the terminal cover, Inverter cover, Digital Operator, and front cover from the Inverter.
2. Remove the controller bracket to which the cards are mounted. Remove all cables connected to the controler.
3. Remove the cooling fan power cable connector (CN26 and CN27) from the gate driver positioned at the back of the controller.
4. Remove the fan cover screws and pull out the fan cover from the Inverter.
5. Remove the cooling fan from the fan cover.
Mounting the Cooling Fan
After attaching a new cooling fan, use the above described procedure in reverse order to attach all of the components.
When attaching the cooling fan to the mounting bracket, be sure that the air flow direction faces the top of the
Inverter.
8-6
Controller bracket
Controller
Air flow direction
Fan cover
Connector
Gate driver
Fig 8.2 Cooling Fan Replacement (Inverters of 22 kW or More)
Maintenance and Inspection
Removing and Mounting the Control Circuit Terminal Card
Removing the Control Circuit Terminal Card
1. Remove the Digital Operator and front cover.
2. Remove the connecting line connectors connected to FE and NC on the control circuit terminal card.
3. Loosen the mounting screws (1) on the left and right sides of the control terminals until they are free. (It is not necessary to remove these screws completely. They are self-rising.)
4. Pull the terminal card out downwards (in direction 2).
Mounting the Control Circuit Terminal Card
Use the removal procedure in reverse order to mount the terminal card.
Confirm that the terminal circuit card and the controller card properly meet at connector CN5 before pressing into its plan.
The connector pins may be bent if the card is forced into place!
Removing and Mounting the
Control Circuit Terminal Card
1
NOTE
2
Fig 8.3 Removing the Control Circuit Terminal Card
Always confirm that the charge indicator does not light anymore before removing or mounting the control circuit terminal card.
8-7
8-8
9
Specifications
This chapter describes the basic specifications of the Inverter and specifications for options and peripheral devices.
Standard Inverter Specifications ........................................9-2
9-2
Standard Inverter Specifications
The standard Inverter specifications are listed by capacity in the following tables.
Specifications by Model
Specifications are given by model in the following tables.
200V Class
Model Number
CIMR-E7Z
Max. applicable motor output (kW)
*1
Rated output capacity
(kVA)
Rated output current
(A)
20P4 20P7 21P5 22P2 23P7 25P5 27P5 2011 2015 2018 2022 2030 2037 2045 2055 2075 2090 2110
0.55
1.2
3.2
0.75
1.6
4.1
1.5
2.7
7.0
2.2
3.7
9.6
3.7
5.7
15
5.5
8.8
23
7.5
12
31
11
17
45
15
22
58
18.5
27
71
22
32
85
30
44
115
37
55
145
45
69
180
55
82
215
75
110
283
90
130
346
110
160
415
Max. output voltage (V)
3-phase; 200, 220, 230, or 240 VAC
(Proportional to input voltage.)
Max. output frequency
(Hz)
Rated voltage (V)
Rated frequency (Hz)
Rated input current (A) 3.8
Allowable voltage fluctuation
4.9
8.4
11.5
18 24 37 52 68
200.0
3-phase, 200/208/220/230/240 VAC, 50/60 Hz
84
+ 10%, - 15%
94 120 160 198 237 317 381 457
Allowable frequency fluctuation
±5%
DC reactor
Measures for power supply harmonics
12-pulse rectification
Optional
Not possible
Built in
Possible
*2
*1. The maximum applicable motor output is given for a standard 4-pole Yaskawa motor. When selecting the actual motor and Inverter, be sure that the Inverter's rated current is applicable for the motor's rated current.
*2. A transformer with dual star-delta secondary is required on the power supply for 12-pulse rectification.
Standard Inverter Specifications
400 V Class Inverters in Protection Class IP00 and NEMA 1 / IP20
Model Number
CIMR-E7Z
Max. applicable motor output
Rated output capacity
(kVA)
Rated output current (A)
Max. output voltage (V)
Max. output frequency
(Hz)
40P4
0.55
1.4
1.8
40P7
0.75
1.6
2.1
41P5
1.5
2.8
42P2
2.2
4.0
43P7
3.7
5.8
44P0
4.0
6.6
4011
11
18
3.7
5.3
7.6
8.7
12.5
17 24
3-phase; 380, 400, 415, 440, 460, or 480 VAC (Proportional to input voltage.)
200.0
45P5
5.5
9.5
47P5
7.5
13
Rated voltage (V)
Rated frequency (Hz)
Rated input current (A)
Allowable voltage fluctuation
2.2
2.5
4.4
3-phase, 380, 400, 415, 440, 460 or 480 VAC, 50/60 Hz
6.4
9.0
10.4
+ 10%, - 15%
15 20 29
Allowable frequency fluctuation
±5%
4015
15
24
31
37
4018
18.5
30
39
47
DC reactor
Measures for power supply harmonics
12-phase rectification
Optional
Not possible
Model Number
CIMR-E7Z
Max. applicable motor output (kW)
*1
Rated output capacity
(kVA)
Rated output current (A)
Max. output voltage (V)
Max. output frequency
(Hz)
Max. voltage (V)
Rated frequency (Hz)
Rated input current (A)
Allowable voltage fluctuation
4022
22
34
45
50
Allowable frequency fluctuation
4030
30
4037
37
46
60
66 83
4045
45
4055
55
4075
75
4090
90
4110
110
4132
132
4160
160
4185
185
57 69 85 110 140 160 200 230 280
75 91 112 150 180 216 260 304
3-phase, 380, 400, 415, 440, 460, or 480 VAC (Proportional to input voltage.)
370
200.0
100
3-phase, 380, 400, 415, 440, 460, or 480 VAC, 50/60 Hz
120 165 198
+ 10%, - 15%
±5%
238 286 334 407
4220
220
4300
300
390
506
537
510
675
743
Measures for power supply harmonics
DC reactor
12-phase rectification
Built in
Possible
*2
*1. The maximum applicable motor output is given for a standard 4-pole Yaskawa standard motor. When selecting the actual motor and Inverter, be sure that the Inverter's rated current is higher than the motor's rated current.
*2. A transformer with dual star-delta secondary is required on the power supply for 12-pulse-rectification.
9-3
9-4
400 V Class Inverters in Protection Class IP54
Model Number
CIMR-E7Z
Max. applicable motor output
(kW)
*1
Rated output capacity
(kVA)
Rated output current (A)
Max. output voltage (V)
Max. output frequency
(Hz)
47P5
7.5
13
17
4011
11
18
4015
15
24
4018
18.5
30
4022
22
34
200.0
4030
30
46
4037
37
57
4045
45
69
24 31 39 45 60 75 91
3-phase; 380, 400, 415, 440, 460, or 480 VAC (Proportional to input voltage.)
Rated voltage (V)
Rated frequency (Hz)
Rated input current (A)
Allowable voltage fluctuation
20 29
3-phase, 380, 400, 415, 440, 460 or 480 VAC, 50/60 Hz
37 47 50
+ 10%, - 15%
66 83 100
Allowable frequency fluctuation
±5%
4055
55
85
112
120
DC reactor
Measures for power supply harmonics
12-phase rectification
Optional
Not possible
Built in
*1. The maximum applicable motor output is given for a standard 4-pole Yaskawa standard motor. When selecting the actual motor and Inverter, be sure that the Inverter's rated current is higher than the motor's rated current.
Standard Inverter Specifications
Common Specifications
The following specifications apply to both 200 V and 400 V Class Inverters.
Model Number
CIMR-E7Z
Specification
Control method
Speed control range
Speed control accuracy
Frequency control range
Frequency accuracy (temperature characteristics)
Frequency setting resolution
Sine wave PWM
V/f control
1:40
±3 (25
°C ± 10°C)
0.0to 200.0 Hz
Digital references: ± 0.01% (-10
°C to +40°C)
Analog references: ±0.1% (25
°C ±10°C)
Digital references: 0.01 Hz
Analog references: 0.025/50 Hz (11 bits plus sign)
Output frequency resolution
Frequency setting signal
Acceleration/Deceleration time
Braking torque
0.01 Hz
0 to +10V, 4 to 20 mA
0.01 to 6000.0 s (2 selectable combinations of independent acceleration and deceleration settings)
Approximately 20%
Main control functions
Motor protection
Instantaneous overcurrent protection
Fuse blown protection
Overload protection
*1
Restarting for momentary power loss, speed searches, overload detection, 5-speed control (maximum), acceleration/deceleration time changes, S-curve acceleration, 3-wire control, autotuning, cooling fan ON/OFF control, torque compensation, jump frequencies, upper and lower limits for frequency references, DC braking for starting and stopping, motor preheat function,
High Slip braking, PI control (with sleep/snooze function, scaling with units), energy-saving control, MEMOBUS communications (RS-485/422, 19.2 kbps maximum), emergency override, fault reset, and copy function.
Protection by electronic thermal overload relay.
Stops at approx. 200% of rated output current.
Stops for fuse blown.
120% of rated output current for 1 minute
Overvoltage protection
Undervoltage protection
200 Class Inverter: Stops when main-circuit DC voltage is above 410 V.
400 Class Inverter: Stops when main-circuit DC voltage is above 820 V.
200 Class Inverter: Stops when main-circuit DC voltage is below 190 V.
400 Class Inverter: Stops when main-circuit DC voltage is below 380 V.
Momentary power loss ride through
Cooling fin overheating
Stall prevention
By selecting the momentary power loss method, operation can be continued if power is restored within 2 s.
Grounding protection
Charge indicator
Protective structure
Ambient operating temperature
Protection by thermistor.
Stall prevention during acceleration, deceleration, or running.
Protection by electronic circuits.
Lights up when the main circuit DC voltage is approx. 50 V or more.
Enclosed wall-mounted type (NEMA 1): 18.5 kW or less (same for 200 V and 400 V class Inverters)
Open chassis type (IP00): 22 kW or more (same for 200 V and 400 V class Inverters)
-10
°C to 40°C (NEMA 1 / IP20 and IP54)
–10
°C to 45°C (IP00)
Ambient operating humidity
Storage temperature
95% max. (with no condensation)
Application site
Altitude
Vibration
- 20
°C to + 60°C (short-term temperature during transportation)
Indoor (no corrosive gas, dust, etc.)
1000 m max.
10 to 20 Hz, 9.8 m/s2 max.; 20 to 50 Hz, 2 m/s2 max
*1. Increase the Inverter capacity if loads exceeding these current values are expected.
9-5
9-6
10
Appendix
This chapter provides precautions for the Inverter, motor, and peripheral devices and also provides lists of parameters.
Inverter Application Precautions ......................................10-2
Motor Application Precautions .........................................10-4
User Parameters..............................................................10-6
10-2
Inverter Application Precautions
Selection
Observe the following precautions in selecting an Inverter.
Installing Reactors
A large peak current will flow in the power input circuit when the Inverter is connected to a large-capacity power transformer (600 kVA or higher) or when switching a compensating capacitor. Excessive peak current can destroy the rectifier section. To prevent this, install a DC or AC reactor (optional) to improve the power supply power factor.
DC reactors are built into Inverters of 22 and more.
If a thyristor converter, such as a DC drive, is connected in the same power supply system, connect a DC or
AC reactor regardless of the power supply conditions shown in the following diagram.
Power supply capacity (kVA)
DC or AC reactor
Required
DC or AC reactor
Not required
Inverter capacity (kVA)
Inverter Capacity
When connecting special motors or multiple motors in parallel to an Inverter, select the Inverter capacity so that the rated output current of the Inverter is minimum 1.1 times the sum of all the motor rated currents.
Initial Torque
The startup and acceleration characteristics of the motor are restricted by the overload current ratings of the
Inverter that is driving the motor. The torque characteristic generally is different from those when starting a motor on the power supply directly. If a large initial torque is required, select an Inverter one size bigger or increase the capacity of both, the motor and the Inverter.
Installation
Observe the following precautions when installing an Inverter.
Installation in Enclosures
Install the Inverter in a clean location where it is not subjected to oil mist, dust, and other contaminants, or install the Inverter in a completely enclosed panel. Provide cooling measures and sufficient panel space so that the temperature surrounding the Inverter does not exceed the allowable temperature. Do not install the Inverter on wood or other combustible materials.
Installation Direction
Mount the Inverter vertically to a wall or other vertical surface.
Inverter Application Precautions
Settings
Observe the following precautions when making settings for an Inverter.
Upper Limits
The maximum output frequency can be set up to 120Hz. Setting the output frequency too high can damage the machine. So pay attention to the mechanical system and observe required limits for the output frequency.
DC Injection Braking and Motor Preheat
If the DC injection braking current, the braking time or the motor preheat current or are set too high the motor can overheat what can damage the motor.
Acceleration/Deceleration Times
The motor's acceleration and deceleration times are determined by the torque generated by the motor, the load torque, and the load's inertial moment (GD
2
/4). If the stall prevention functions are activated during acceleration or deceleration, it might be necessary to increase the acceleration or deceleration time.
To reduce the acceleration or deceleration times, increase the capacity of the motor and Inverter.
Handling
Observe the following precautions when wiring or performing maintenance for an Inverter.
Wiring Check
The Inverter will be internally damaged if the power supply voltage is applied to output terminal U, V, or W.
Check wiring for any mistakes before supplying power. Check all wiring and control sequences carefully.
Magnetic Contactor Installation
If a magnetic contactor is installed in the power supply line, do not exceed one start every 30 minutes. Switching more often can damage the inrush current prevention circuit.
Maintenance and Inspections
After turning OFF the main circuit power supply it can take several minutes before the DC bus is discharged completely. The CHARGE LED, indicating if the DC bus is charged, glows above a voltage of 10VDC.
10-3
10-4
Motor Application Precautions
Using the Inverter for an Existing Standard Motor
Observe the following precautions when using an Inverter for an existing standard motor.
Low Speed Ranges
If a standard cooled motor is used at low speed the cooling effects are diminished. If the motor is used in constant torque applications in low speed area the motor may overheat. If full torque is required at low speed continuously an externally cooled motor must be used.
Installation Withstand Voltage
If the Inverter is used with an input voltage of 440 V or higher and long motor cables, voltage spikes at the motor terminals may occur which can damage the motor windings. Ensure that the motor insulation class is sufficient.
Acoustic Noise
The acoustic noise generated in the motor depends on the carrier frequency. The higher the setting, the less is the generated acoustic noise.
Motor Application Precautions
Using the Inverter for Special Motors
Observe the following precautions when using a special motor.
Pole-changing Motor
The rated input current of pole-changing motors differs from that of standard motors. Select an appropriate
Inverter according to the maximum current of the motor.
Submersible Motor
The rated input current of submersible motors is higher than that of standard motors. Therefore, always select an Inverter by checking its rated output current. When the distance between the motor and Inverter is long, use a motor cable with high cross section to prevent voltage drop and thereby motor torque reduction.
Explosion-proof Motor
When an explosion-proof motor is used, it must be subjected to an explosion-proof test in conjunction with the
Inverter. This is also applicable when an existing explosion-proof motor is to be operated with the Inverter.
Since the Inverter itself is, however, not explosion-proof always install it in a safe place.
Gearmotor
The speed range for continuous operation differs according to the lubrication method and motor manufacturer.
In particular, continuous operation of an oil-lubricated motor in the low speed range may result in damaging.
If the motor is to be operated at a speed higher than 50 Hz, consult the manufacturer.
Single-phase Motor
Do not use an Inverter for a single-phase motor. These motors are often equipped with phase-shift capacitors.
Any capacitor directly connected to the inverter output may damage the Inverter.
Power Transmission Mechanism (Speed Reducers, Belts and Chains)
If an oil-lubricated gearbox or speed reducer is used in the power transmission mechanism, oil lubrication will be affected when the motor operates only in the low speed range. The power transmission mechanism will be morey noisy and might experience problems with service life and durability if the motor is operated at low speeds continuously.
10-5
10-6
User Parameters
A complete parameter table with the factory default settings can be found in the following table. The factory settings are given for 200V class Inverter with 0.4 kW.
No.
Name
Factory
Setting
Setting
A1-00
Language selection for digital operator display
(LED/HOA Digital Operator)
A1-01 Parameter access level
A1-03 Initialize
A1-04 Password
A1-05 Password setting
A2-01 to
A2-32
User-set parameters b1-01 Reference source selection b1-02 RUN command source selection b1-03 Stopping method selection b1-04 Prohibition of reverse operation b1-07 Operation selection after switching to remote mode b1-08 Run command selection in programming modes b1-11 RUN delay b1-12 HAND frequency reference source selection b1-13 HAND/AUTO switching during run selection b1-14 Emergency override speed b1-15 Emergency override reference selection b2-01 DC injection braking starting frequency (Zero speed level) b2-02 DC injection braking current b2-03 DC injection braking time at start b2-04 DC injection braking time at stop b2-09 Motor preheat current b2-10 Motor preheat current 2 b3-01 Speed search selection b3-02 Speed search operating current b3-03 Speed search deceleration time b3-05 Speed search wait time b3-14 Bi-directional speed search selection b4-01 Timer function ON-delay time b4-02 Timer function OFF-delay time b5-01 PI control mode selection b5-02 Proportional (P) gain b5-03 Integral (I) time b5-04 Integral (I) limit b5-06 PI limit b5-07 PI offset b5-08 PI delay time constant b5-09 PI output characteristics selection
0
2
0
0
0
–
120%
2.0 sec.
0.2 sec.
1
0.0 sec.
0.0 sec.
0
1.00
1.0 sec.
100.0%
100.0%
0.0%
0.00 sec.
0
0
0
0.00 Hz
0
0.5 Hz
50%
0.00 sec.
0.50 sec.
1
1
0
0
0
0
0 sec.
0%
5%
2
No.
Name b5-10 PI output gain b5-11 PI reverse output selection b5-12 Selection of PI feedback loss detection b5-13 PI feedback loss detection level b5-14 PI feedback loss detection time b5-15 Sleep function operation level b5-16 Sleep operation delay time b5-17 Acceleration/deceleration time for PI reference b5-18 PI setpoint selection b5-19 PI setpoint b5-20 PI setpoint scaling b5-21 Sleep function selection b5-22 Snooze level b5-23 Snooze delay time b5-24 Wake-up level b5-25 Setpoint boost b5-26 Maximum boost time b5-27 Snooze feedback b5-28 PI feedback square root operation b5-29 PI feedback square root gain b5-30 PI output monitor square root b5-31 PI unit selecction b8-01 Energy-saving mode selection b8-04 Energy-saving coefficient b8-05 Power detection filter time constant b8-06 Search operation voltage limiter
C1-01 Acceleration time 1
C1-02 Deceleration time 1
C1-03 Acceleration time 2
C1-04 Deceleration time 2
C1-09 Emergency stop time
C1-11 Accel/decel time switching frequency
C2-01 S-curve characteristic time at acceleration start
C2-02 S-curve characteristic time at acceleration end
C4-01 Torque compensation gain
C4-02 Torque compensation time constant
C6-01 Normal duty selection
C6-02 Carrier frequency selection
C6-03 Carrier Frequency Upper Limit
C6-04 Carrier Frequency Lower Limit
C6-05 Carrier Freq. Proportional Gain
User Parameters
0%
10.0 sec.
10.0 sec.
10.0 sec.
10.0 sec.
10.0 sec.
0.0 Hz
0.20 sec.
0.20 sec.
1.00
0%
0 sec
60%
0
1.00
0
0
*1
0
288.20
*2
20 msec.
0.0 sec.
0
0.0%
1
1
0%
0 sec
0%
Factory
Setting
1.0
0
0
0%
1.0 sec.
0.0 Hz
0.0 sec.
200 msec.
1
6
*3
00
Setting
10-7
10-8
No.
Name d1-01 Frequency reference 1 d1-02 Frequency reference 2 d1-03 Frequency reference 3 d1-04 Frequency reference 4 d1-17 Jog frequency reference d2-01 Frequency reference upper limit d2-02 Frequency reference lower limit d2-03 Master speed reference lower limit d3-01 Jump frequency 1 d3-02 Jump frequency 2 d3-03 Jump frequency 3 d3-04 Jump frequency width d4-01 Frequency reference hold function selection d4-02 Trim control level
E1-01 Input voltage setting
E1-03 V/f pattern selection
E1-04 Max. output frequency
E1-05 Max. output voltage
E1-06 Base frequency
E1-07 Mid output frequency
E1-08 Mid. output frequency voltage
E1-09 Min. output frequency
E1-10 Min. output frequency voltage
E1-11 Mid. output frequency 2
E1-12 Mid. output frequency voltage 2
E1-13 Base voltage
E2-01 Motor rated current
E2-03 Motor no-load current
E2-05 Motor line-to-line resistance
F6-01 Operation selection after communications error
F6-02 Option card external fault detection selection
F6-03 Option card external fault stopping method
F6-05 Current scaling via communication option card
H1-01 Terminal S3 function selection
H1-02 Terminal S4 function selection
H1-03 Terminal S5 function selection
H1-04 Terminal S6 function selection
H1-05 Terminal S7 function selection
H2-01 Terminal M1-M2 function selection
H2-02 Terminal M3-M4 function selection
0.0 Hz
0.0 V
0.0 V
1.90 A
1.20 A
9.842
Ω
1
0
24
0
1
14
3 (0)
*5
0
1
0.0%
0.0 Hz
0.0 Hz
0.0 Hz
1.0 Hz
0
10%
200 V
*4
F
50.0 Hz
Factory
Setting
0.00 Hz
0.00 Hz
0.00 Hz
0.00 Hz
6.00 Hz
100.0%
0.0%
200.0 V
50.0 Hz
2.5 Hz
15.0 V
1.2 Hz
Setting
No.
Name
H3-02 Terminal A1 gain
H3-03 Terminal A1 bias
H3-08 Analog input A2 signal level selectoin
H3-09 Analog input A2 function selection
H3-10 Terminal A2 gain
H3-11 Terminal A2 bias
H3-12 Analog input filter time constant
H3-13 Terminal A1/A2 switching
H4-01 Terminal FM monitor selection
H4-02 Terminal FM gain
H4-03 Terminal FM bias
H4-04 Terminal AM monitor selection
H4-05 Terminal AM gain
H4-06 Terminal AM bias
H4-07 Terminal FM signal level selection
H4-08 Terminal AM signal level selection
H5-01 Station address
H5-02 Communications speed selection
H5-03 Communications parity selection
H5-04 Stopping method after communications error
H5-05 Communications error detection selection
H5-06 Send wait time
H5-07 RTS control ON/OFF
H5-08 Communications Selection
H5-09 CE detection time
L1-01 Motor protection selection
L1-02 Motor protection time constant
L1-03 Alarm operation selection during motor overheating
L1-04 Motor overheating operation selection
L1-05 Motor temperature input filter time constant
L2-01 Momentary power loss detection
L2-02 Momentary power loss ride through time
L2-03 Min. baseblock time
L2-04 Voltage recovery time
L2-05 Undervoltage detection level
L3-01 Stall prevention selection during acceleration
L3-02 Stall prevention level during acceleration
L3-04 Stall prevention selection during deceleration
L3-05 Stall prevention selection during running
L3-06 Stall prevention level during running
L4-01 Speed agreement detection level
User Parameters
1F
3
0
3
1
5 msec.
1
0
2.0 sec.
1
1.0 min
3
1
0.20 sec.
0
2
100%
0.0%
8
50%
0.0%
0
0
Factory
Setting
100.0%
0.0%
2
2
*6
100.0%
0.0%
0.30 sec.
0
0.1 sec.
0.3 sec
1
120%
1
1
120%
0.0 Hz
Setting
10-9
10-10
No.
Name
L4-02 Speed agreement detection width
L4-05 Operation when frequency reference is missing
L4-06 Frequency reference value at frequency reference loss
L5-01 Number of auto restart attempts
L5-02 Auto restart operation selection
L5-03 Fault Retry Time
L6-01 Load detection selection
L6-02 Load detection level
L6-03 Load detection time
L8-02 Overheat pre-alarm level
L8-03 Operation selection after overheat pre-alarm
L8-06 Input phase loss detection level
L8-09 Ground fault protection selection
L8-10 Cooling fan control selection
L8-11 Cooling fan control delay time
L8-12 Ambient temperature
L8-15 OL2 characteristics selection at low speeds
L8-18 Soft CLA selection
L8-19 Frequency reference during OH pre-alarm
L8-32 OH1 detection selection for fan failure n1-01 Hunting prevention function selection n1-02 Hunting prevention gain n3-01 High slip braking deceleration frequency width n3-02 High slip braking current limit n3-03 High slip braking stop dwell time n3-04 High slip braking OL7 time o1-01 Monitor selection o1-02 Monitor selection after power up o1-03 Digital operator display scaling o1-05 LCD Focus o1-06
Monitor mode Selection o1-07
2nd monitor selection o1-08
3rd monitor selection o1-09 Frequency reference display unit selection o2-01 LOCAL/REMOTE key enable/disable o2-02 STOP key during control circuit terminal operation o2-03 User parameter initial value o2-04 kVA selection o2-05 Frequency reference setting method selection o2-06 Operation selection when digital operator is disconnected o2-07 Cumulative operation time setting o2-08 Cumulative operation time selection o2-09 Initialize mode
2
3
1
0
0
1
0
0
0
0 hrs.
1
2
20.0%
1
1
1.00
5%
150%
1.0 sec.
40 sec.
1
0
300 sec.
45 °C
1
1
0
3
6
1
Factory
Setting
2.0 Hz
1
80%
0
0
10.0 sec.
6
15%
10.0 sec.
95 °C
4
0
Setting
User Parameters
No.
o2-10 Fan operation time setting o2-12 Fault trace initialize o2-14 kWh monitor initialize o2-15 HAND key function selection o2-17 Standard / IP54 Selection o3-01 Copy function selection o3-02 Read permission selection
T1-02 Motor output power
T1-04 Motor rated current
Name
Factory
Setting
0 hrs.
0
0
1
*7
0
0
0.40 kW
1.90 A
*1. Parameter function is only valid if a Digital Operator with LCD clear text display is used (LCD or HOA Digital Operator)
*2. The factory setting depends on the Inverter capacity.
*3. The factory setting depends on the Inverter capacity and the protection class.
*4. Values for 200 V class Inverters are shown. For a 400 V class Inverter the values have to be doubled.
*5. The values in parentheses indicate initial values when initialized in 3-wire-sequence.
*6. Setting switched to “B” when PI controller is enabled
*7. The setting depends on the protection class of the Inverter.
Setting
10-11
10-12