Fema S40-T User manual
Add to my manuals
12 Pages
Fema S40-T is a compact and versatile panel meter designed for accurate temperature measurement and display. It supports a wide range of temperature sensors, including Pt100 RTDs and various types of thermocouples. The device offers user-selectable temperature units (°C or °F), configurable alarms with hysteresis and delays, and memory functions for maximum and minimum readings. Additionally, it provides options for signal retransmission and control via add-on modules, making it a suitable solution for industrial temperature monitoring and control applications.
advertisement
Panel Meters
Series S40
Panel meter 72x36mm size
Model S40-T for Pt100 / RTD
Thermocouples
Panel meter for Pt100/RTD (2 and 3 wires), and thermocouples J, K, T, E, S,
R, N, C, L and X with temperature display in degrees celsius (ºC) or fahrenheit
(ºF). Selectable Pt100/RTD resolution at 1º or 0.1º, and manual offset available.
Thermocouple measure with internal CJC selectable (enabled or disabled).
Selectable behavior in case of sensor break (‘to_high’ or ‘to_low’). Reduced housing 72x36mm DIN standard. Display in 4 digits and negative sign. Maximum and minimum display memory, steps, alarms with single or double setpoints, 5 levels of brightness, ... Universal AC and DC power modules and up to 2 modules for signal retransmission and control.
USER’S MANUAL
(2264R00)
User’s Manual S40-T
Meter S40-T
Panel meter 72x36mm size for Pt100/RTD and Thermocouples
Panel meter for temperature signals, accepts Pt100/RTD with
2 and 3 wires, and thermocouples J, K, T, E, S, R, N, C, L and
X. Temperature display in degrees celsius (ºC) or fahrenheit
(ºF). Thermocouple cold junction compensation selectable.
Manual offset selectable. Selectable behavior for alarms in case of sensor break (‘to_high’ or ‘to_low’).
Power options with universal AC and DC ranges, and space for two additional control and/or signal retransmission modules.
Standard IP54 front protection, with optional upgrade to IP65 protection.
Instrument with small 72x36mm standard DIN size. Resolution 4 digits and negative sign.
Connections via plug-in screw terminals and configuration via three front push-buttons. For application on industrial environments.
Management for up to 4 alarms with 1 or 2 setpoints each alarm, with hysteresis and delays. Provides memory for maximum and minimum, display on selectable steps, password and selectable levels of brightness.
Order Reference
S40 -
Model
T -
Power
H
-H
(85-265 Vac/dc)
-L
(11-60 Vdc and 24/48 Vac)
-
Option1
---
-R1
(1 relay)
-AO
(Analogue Output)
-
(empty)
-
Option2
---
-R1
(1 relay)
-AO
(Analogue Output)
-
(empty)
-
Others
---
-65
(IP65)
-
(empty)
Precautions on installation
Risk of electrical shock. Instrument terminals can be connected to dangerous voltage.
Instrument protected with double isolation. No earth connection required.
Instrument is in conformity with CE rules and regulations. See
“CE Declaration of Conformity” further in this document.
This instrument has been designed and verified according to the 61010-1
CE security regulation, and is designed for applications on industrial environments. See the “CE Declaration of Conformity” further in this document for information on the category of measure and the degree of pollution levels that apply.
Installation of this instrument must be performed by qualified personnel only. This manual contains the appropriate information for the installation.
Using the instrument in ways not specified by the manufacturer may lead to a reduction on the specified protection level. Disconnect the instrument from power before starting any maintenance and / or installation action.
The instrument does not have a general switch and will start operation as soon as power is connected. The instrument does not have protection fuse, the fuse must be added during installation.
The instrument is designed to be panel mounted. An appropriate ventilation of the instrument must be assured. Do not expose the instrument to excess of humidity. Maintain clean by using a humid rag and do NOT use abrasive products such as alcohols, solvents, etc.
General recommendations for electrical installations apply, and for proper functionality we recommend : if possible, install the instrument far from electrical noise or magnetic field generators such as power relays, electrical motors, speed variators, ... If possible, do not install along the same conduits power cables (power, motor controllers, electrovalves, ...) together with signal and/or control cables.
Before proceeding to the power connection, verify that the voltage level available matches the power levels indicated in the label on the instrument.
In case of fire, disconnect the instrument from the power line, fire alarm according to local rules, disconnect the air conditioning, attack fire with carbonic snow, never with water.
FEMA ELECTRÓNICA - Page 2
User’s Manual S40-T
Logo
Alarms
Front View
Rear View
Option1 Option2
User’s Manual S40-T
Input signal connections - Pt100/RTD
Measure can be selected for 2 or 3 wire systems.
1 2 3 4 5
Select input Pt100 2Wires in the menu. Terminal 2 can be left unconnected.
Button
LE
Button
UP
Button
SQ
Units
RTD/Pt100
2 wires
1 2 3 4 5
Select input Pt100 3Wires in the menu
RTD/Pt100
3 wires
Input signal connections - Thermocouple
To configure, select the appropriate thermocouple type in the configuration menu.
1 2 3 4 5
Signal
+
-
Thermocouple
Power
Power Connections
6 7 8 9 0
~
+
~
-
Earth connection - Although a terminal is offered for earth connection, the connection is optional. The instrument does not need this connection for correct functioning nor for compliance with the security regulations.
Fuse - To comply with security regulation 61010-1, add to the power line a protection fuse acting as disconnection element, easily accessible to the operator and identified as a protection device.
Power “H” fuse 250mA time-lag
Power “L” fuse 400mA time-lag
FEMA ELECTRÓNICA - Page 3
User’s Manual S40-T
Technical Data
Digits 4
Type
Height
Display maximum
Display minimum
Decimal point
Overrange
Underrange
7 segments, red
14 mm
9999
-1999 selectable 8.8.8.8.
9999 flashing
-1999 flashing
Technical Data (cont.)
Power
Power “H”
Power “L”
85 to 265 Vac/dc
11 to 60 Vdc and 24/48Vac
Consumption <4W
Isolation 3500Veff for power “H”
2000Veff for power “L” all levels tested for 60 seconds
Signals accepted
Temperature scale
Display units
Thermocouple data
Thermocouples accepted J, K, T, E, S, R, N, C, L, X
(Thermocouple X is a linear 10uV/ºC signal)
Resolution 1º
Ranges
Max. error at 25ºC
Offset drift
Span drift*
CJC
CJC accuracy
CJC thermal drift
On sensor break
Acquisitions
Pt100/RTD and Thermocouples
ITS90
ºC or ºF, selectable see table 3 see table 3 see table 3 see table 3
*Note - span drift includes also the offset drift
automatic (“On”/“Off” selectable)
<1.0ºC
<0.04º/ºC
“to_high” or “to_low”, selectable
3 acquisitions / second
Pt100/RTD data
Sensors accepted
Resolution
Ranges
Alpha
Max. error at 25ºC
Offset drift
Span drift *
2 or 3 wire, selectable
1º or 0.1º, selectable
see table 3
Alpha385 or Alpha390, selectable see table 3 see table 3 see table 3
*Note - span drift includes also the offset drift
Cable compensation up to 14 Ohm
Compensation accuracy <0.02ºC / Ohm
Acquisitions 4 acquisitions / second
Configuration
Functions available
Steps
Memory of maximum
Memory of minimum
Password
Double setpoints
Brightness control
3 frontal push buttons yes, configurable yes yes yes, configurable yes yes, 5 levels
Options maximum 2
Mechanical
Mounting panel
Connections
Weight
Housing materials
Front size
Panel cut-out
Deep from panel plug-in screw terminals
<150 grams
ABS, polycarbonate, vergaflex
72x36mm
69x32.5mm
98mm (including terminal)
Protection
Temperature Operation 0 to 50ºC
Temperature Storage –20 to +70ºC
Warm-up 15 minutes
Type Range ºC
Pt100/RTD
800 / -200 ºC
Thermocouple J
1200 / -200 ºC
Thermocouple K
1372 / -200 ºC
Thermocouple T
400 / -200 ºC
Thermocouple E
1000 / -200 ºC
Thermocouple S
1768 / -50 ºC
Thermocouple R
1600 / -50 ºC
Max. error at 25ºC*
<0.2ºC
<2ºC
<2ºC
<2ºC
<2ºC
<4ºC
<4ºC
Range ºF
1562 / -328 ºF
2192 / -328 ºF
2372 / -328 ºF
752 / -328 ºF
1832 / -328 ºF
2282 / -58 ºF
2912 / -58 ºF
Thermocouple N
1300 / -200 ºC
Thermocouple C
2320 / 0 ºC
Thermocouple L
900 / -200 ºC
Thermocouple X
4000 / -200 ºC
<2ºC
<2ºC
<2ºC
<2ºC
2372 / -328 ºF
4192 / 32 ºF
1652 / -328 ºF
7232 / -328 ºF
Table 3 - Thermocouple and PT100/RTD specifications
IP54 standard
IP65 optional (Front sealed. Opening the front breaks the seal)
Offset drift
0.05º/ºC
0.05º/ºC
0.05º/ºC
0.02º/ºC
0.05º/ºC
0.20º/ºC
0.20º/ºC
0.05º/ºC
0.02º/ºC
0.05º/ºC
0.02º/ºC
Span drift*
*includes offset drift
0.10º/ºC
0.20º/ºC
0.20º/ºC
0.02º/ºC
0.20º/ºC
0.20º/ºC
0.20º/ºC
0.20º/ºC
0.02º/ºC
0.20º/ºC
0.02º/ºC
FEMA ELECTRÓNICA - Page 4
User’s Manual S40-T User’s Manual S40-T
Mechanical Dimensions (mm) Information Menu
36
72
32,5
Panel cut-out
69
18 80 8
Operating the Information Menu
To enter the “Information Menu” press the SQ button. The
“Information Menu” allows to visualize information and does not allow to modify the configuration of the instrument. It is not affected by the “PASSWord” function. During operation with the “Information Menu”, alarms remain “frozen” and are kept on-hold. Leaving the “Information Menu” returns to the measuring state of the instrument, without restart.
Information Menu Tree - See page 5.
Rollback - After 30 seconds without interaction from the operator, the instrument leaves the “Information Menu”.
Button SQ - Selects the visible option.
Button UP - Moves vertically along the available menu options.
Button LE - Leaves selected menu or leaves the “Informa-
tion Menu”.
Information Menu Description
Configuration (Conf) - Information on the configured input sensor and the degrees selected.
Maximum (MAX) - Value of the maximum display.
Minimum (MIn) - Value of the minimum display.
AlarmX (ALX) - Configuration of alarm X. The sequence of information shows if the alarm is being managed (“On/Off”), the alarm type (“Max/Min”), the setpoint, the hysteresis value, the activation delay and the value of setpoint2 (“Off” or the setpoint2 value).
OptionX (OptX) - Type of module installed. If there is no module shows “nonE”.
Configuration
Sensor type
ºC or ºF
Memory of maximum
Maximum
Memory of minimum
Minimum
Alarm1
Option1
Option2
“On / Off”
“Max” / “Min”
Setpoint
Counts
Hysteresis
Delay
Setpoint2
See menu for Alarm1
See menu for Alarm1
See menu for Alarm1
Option installed
Option installed
Seconds
Second setpoint
FEMA ELECTRÓNICA - Page 5
User’s Manual S40-T
Operating the Configuration Menu
To enter the “Configuration Menu” press the SQ button. The
“Configuration Menu” allows to change the configuration of the instrument. Access to the “Configuration Menu” can be password protected with the function “PASSWord”. During operation with the “Configuration Menu” the alarms remain
“frozen” and are kept on-hold. When leaving the “Configura-
tion Menu” the instrument performs a restart, and new configuration is applied. During the restart of the instrument a short alarm deactivation is performed.
Configuration Menu Tree - See page 6 and 7.
Description of Configuration Menu functions - See page
8 and 9.
Rollback - After 30 seconds without interaction from the operator, the instrument leaves the “Configuration Menu”, discarding all changes.
Button SQ - Moves horizontally on the menu. Allows selection of the current option displayed. During a value selection menu (for example a setpoint value) validates the value on display.
Button UP - Moves vertically on the menu. Displays the available menu options. During a value selection menu (for example a setpoint value) increases digit value from 0 to 1,
2, 3, 4, 5, 6, 7, 8, 9.
Button LE - Leaves the current menu. Pressing LE several times will leave all menus and leave the “Configuration Menu” tree. During a value selection menu (for example a setpoint value) allows to select each digit for modification with the
UP button.
Reset - Leaving the “Configuration Menu” forces a restart of the instrument, even in case of no changes in configuration.
Input
Temp. Config,
Configuration Menu
Pt100/RTD 2 wires
Pt100/RTD 3 wires
Thermocouple J
Thermocouple K
Thermocouple T
Thermocouple E
Thermocouple S
Thermocouple R
Thermocouple N
Thermocouple C
Thermocouple L
Thermocouple X
Degrees
Pt100/RTD res..
Offset
Celsius
Fahrenheit
1º Resolution
0.1º Resolution
Offset counts to add
Thermoc. CJC
On break
Reading to high
Reading to low
Alpha
FEMA ELECTRÓNICA - Page 6
User’s Manual S40-T
Alarms
Alarm1
Active = On
Inactive = Off
Max=Maximum
Min= Minimum
Setpoint
Hysteresis
Delay
Setpoint2
See menu for Alarm1
See menu for Alarm1
See menu for Alarm1
Display
Steps
Maximum
Minimum
User’s Manual S40-T
Configuration Menu
Tools
Alarm management
Password
Factory Default
Alarm as max.
Alarm as min.
Version
Brightness
Counts
Seconds
Second setpoint
Configuration for Option1
Option1
Option2
Configuration for Option2
Select password
Counts for step
Memory of maxim.
Reset of maxim.
Memory of minim.
Reset of minim.
Default factory configuration
Sensor Pt100 2Wire
Degrees ºC
Resolution 0.1º
Offset 0
On Break To high
Alpha 385
Alarms 1,2,3 and 4
Active
Type
Setpoint
Hysteresis
Delay
Setpoint2
Display
Off (not managed) maximum
1000
0 counts
0.0 seconds
Off
Steps Off
Memory of maximum -9999
Memory of minimum 9999
Tools
Password
Brightness
Off
3
FEMA ELECTRÓNICA - Page 7
Resets to factory default values
Firmware version
Minimum brightness
Default brightness
Maximum brightness
User’s Manual S40-T
Input Menu
The input menu selects the input signal range. Options available are Pt100/RTD 2 or 3 wires, and thermocouples J, K, T,
E, S, R, N, C, L and X.
Note - Thermocouple X is a linear signal at 10uV/ºC.
Hysteresis (hySt) - Value from “0” to “9999”. Points of hysteresis. The hysteresis applies on the deactivation of the alarm.
Delay (dEL) - Value from “0.0” to “99.9” seconds. Delay to be applied to the relay activation and deactivation. Relays are activated and deactivated X seconds after the activation / deactivation of the alarm. The delay affects only to the relays.
The delay does not affect to the front leds.
Temperature Configuration Menu
The temperature configuration menu sets the function parameters for Pt100/RTD and thermocouple sensors.
Degrees (dEG) - Value “ºC/ºF”. Select the temperature to be displayed in celsius or fahrenheit degrees.
Setpoint2 (SEt2) - Value from “-1999” to “9999”. Second setpoint. The second setpoint allows for the creation of activation windows. If the alarm is configured as maximum with setpoint 1000 and setpoint2 is configured at 1500, the alarm will be activated between 1000 and 1500 and the alarm will be deactivated when display is <1000 and >1500. Setpoint2 is affected on the same way as the setpoint with hysteresis and delays.
Pt100/RTD resolution (P.rES) - Value “1º/0.1º”. Resolution for the Pt100/RTD. Select to display with degree or tenth of degree resolution.
Display Menu
Functions on this menu allow for configuration of the visualization.
Offset (oFFS) - Value from “-1999” to “9999” counts. Offset to be added to the reading. Both for Pt100/RTD and thermocouples.
Thermocouple Cold Junction Compensation (t.cJc) - Value “On/Off”. Select “On” for automatic CJC compensation in the instrument. Select “Off” to disable the CJC compensation.
Steps (StEP) - Display changes on predefined steps. Values are 1, 2, 5, 10, 20 and 50. The display is made in steps of X counts. For example, select a step of 20 will make the display to change in steps of 20 (1420, 1440, 1460, ...).
On break (on.bk) - Value “to_h/to_l”. Select “To L” to make the reading go to minimum, in case of probe broken. Select
“To H” to make the reading go to maximum in case of probe broken.
AlarmX Menu
Maximum (MAX) - Memory of maximum display. Indicates the maximum value of display since the last reset of the memory. Memory is reset on the following cases : manual reset from the Configuration Menu (Maximum), change on the input signal (Input), modification on the scaling (Scaling), change on the decimal point (dP), modification of the linearization segments, or instrument power-down.
Alpha (ALPh) - Value “385/390”. Select “385” or “390” according to your PT100/RTD sensor.
The instrument manages up to 4 alarms. Each alarm is controlled by the condition “display higher (or lower) than the configured setpoint”. The front leds are controlled by the activation / deactivation of the related alarm. The relays installed on Option1 and/or Option2 are controlled by Alarm1 and Alarm2.
Minimum (MIn) - Memory of minimum display. Indicates the minimum value of display since the last reset of the memory.
Memory is reset on the following cases : manual reset from the Configuration Menu (minimum), change on the input signal (Input), modification on the scaling (Scaling), change on the decimal point (dP), modification of the linearization segments, or instrument power-down.
Active (Act) - Value “On/Off”. Defines if the instrument has to manage this alarm or not. Select “Off” for alarm not managed.
Type (tyPE) - Value “Max/Min”. Defines the behavior of the alarm as maximum or minimum alarm. The alarms configured as maximum are activated when the display value is equal or higher than the setpoint. The alarms configured as maximum are deactivated when the display is lower than the setpoint. The alarms configured as minimum have the inverse behavior.
Setpoint (SEt) - Value from “9999” to “-1999”. Alarm set point.
FEMA ELECTRÓNICA - Page 8
User’s Manual S40-T User’s Manual S40-T
Tools Menu
Password (Pass) - Select a number to act as password. This password will be requested when entering the Configuration
Menu. To deactivate the password select “Off”.
Factory Settings (Fact) - Factory default configuration. Select “yES” to activate the factory default configuration.
Version (Ver) - Firmware version installed.
Light (Ligh) - Luminosity. Select between 5 predefined levels of luminosity.
Options Menu
Menu options OPT1 and OPT2 give access to the configuration menus of the installed options. The menu depends on the installed option. If there is no option installed the instrument shows “nonE”.
Messages and errors
When the instrument detects that the displayed value does not correspond to the input value, the display will flash and alternate with a message.
“ h.udr” Hardware underrange. The thermocouple signal is lower than minimum readable signal (-30mV).
“ h.oVr” Hardware overrange. The thermocouple signal is higher than maximum readable signal (80mV).
“ d.udr” Display underrange. The Pt100/RTD is shortcircuited.
“ hoLd” The instrument is showing the value present when the hold function was activated. Hold function is active.
“ Min” The instrument displays the minimum displayed value in memory. The minimum visualization is active.
“ MAX” The instrument displays the maximum displayed value in memory. The maximum visualization is active.
“ brk” The instrument displays “brk” with either “9999” or
“-9999” when : 1) resistance measured is higher than 390
Ohms (higher than 850ºC for PT100/RTD measure), or 2) in case the third wire ohm is higher than 15 Ohm, or 3) thermocouple measure is open circuit.
Err.1
Password incorrect.
Err.2
The instrument has detected an installed option but was unable to communicate.
T H
I S
S
E C
T I
O
N
B L
A N
K
FEMA ELECTRÓNICA - Page 9
User’s Manual S40-T
Option R1 - 1 relay
Relay type
Maximum current
Voltage
Instalable in
Connections for Option1
3 contacts (Com, NC, NO)
8A (resistive load)
250 Vac continuously
Option1 and/or Option2
Connections for Option2
A B C D E F G H I J
K L M N O P Q R
NC
NO
Common
Warranty
NC
NO
Common
Accessing the instrument
You may need to access the inside of the instrument to insert additional options. Use a flat screwdriver to unlock the upper clips marked with “A”. Then unlock the lower clips marked with “B” and move out the front filter. Let the inside of the instrument slide out of the housing.
To reinsert the instrument make sure that all modules are correctly connected to the pins on the display module. Place all the set into the housing, assuring that the modules correctly fit into the internal guiding slides of the housing. Once introduced, place again the front filter by clipping first the upper clips “A” and then the lower clips “B”.
Important - If your instrument was delivered with the IP65 front seal option, accessing the inside of the instrument will permanently break the IP65 seal on the areas of clips “A” and “B”.
A
All instruments are warranted against all manufacturing defects for a period of 24 MONTHS from the shipment date.
This warranty does not apply in case of misuse, accident or manipulation by non-authorized personnel. In case of malfunction get in contact with your local provider to arrange for repair. Within the warranty period and after examination by the manufacturer, the unit will be repaired or substituted when found to be defective. The scope of this warranty is limited to the repair cost of the instrument, not being the manufacturer eligible for responsibility on additional damages or costs. .
B
CE Declaration of Conformity
Manufacturer FEMA ELECTRÓNICA, S.A.
Altimira 14 - Pol. Ind. Santiga
E08210 - Barberà del Vallès
BARCELONA - SPAIN www.fema.es - [email protected]
Immunity rules
61000-6-2
61000-4-2
Generic rules of immunity
By contact ±4KV - Criteria B
On air ±8KV - Criteria B
Products - S40-T
Security rules 61010-1
Equipment “Fixed”
“Permanently connected”
Pollution degree 1 and 2 (without condensation)
Isolation Double
61000-4-3 Criteria A
61000-4-4 On AC power lines: ±2KV - Criteria B
On DC power lines: ±2KV - Criteria B
On signal lines : ±1KV - Criteria B The manufacturer declares that the instruments indicated comply with the directives and rules indicated below.
Directive of electromagnetic compatibility 2004/108/CEE
Directive of low voltage 73/23/CEE
61000-4-5 Between AC power lines ±1KV - Criteria B
Between DC power lines ±0.5KV - Criteria B
61000-4-6 Criteria A
61000-4-8 30A/m at 50Hz - Criteria A
61000-4-11 0% 1 cycle Criteria A
40% 10 cycle Criteria B
70% 25 cycle Criteria B
0% 250 cycle Criteria B
Emission rules
61000-6-4 Generic rule of emission
Barberà del Vallès November 2011
Daniel Juncà - Quality Manager
FEMA ELECTRÓNICA - Page 10
User’s Manual S40-T User’s Manual S40-T
T H
I S
P
A G
E
B L
A N
K
FEMA ELECTRÓNICA - Page 11
other products
Panel Meters
Standard 96x48mm
Panel Meters
Small 72x36mm
Panel Meters
Miniature 48x24mm
Large Displays
60&100mm digit
Signal Converters
& Isolators
Panel Meters
Standard 96x48mm
www.fema.es
ELECTRONIC INSTRUMENTATION FOR INDUSTRY
FEMA ELECTRÓNICA, S.A.
Altimira 14 - Pol. Ind. Santiga
E08210 Barberà del Vallès
BARCELONA - SPAIN
Tel. (+34) 93.729.6004 - www.fema.es
Fax (+34) 93.729.6003 - [email protected]