Panel Meters

Series S40

Panel meter 72x36mm size

Model S40-T for Pt100 / RTD

Thermocouples

Panel meter for Pt100/RTD (2 and 3 wires), and thermocouples J, K, T, E, S,

R, N, C, L and X with temperature display in degrees celsius (ºC) or fahrenheit

(ºF). Selectable Pt100/RTD resolution at 1º or 0.1º, and manual offset available.

Thermocouple measure with internal CJC selectable (enabled or disabled).

Selectable behavior in case of sensor break (‘to_high’ or ‘to_low’). Reduced housing 72x36mm DIN standard. Display in 4 digits and negative sign. Maximum and minimum display memory, steps, alarms with single or double setpoints, 5 levels of brightness, ... Universal AC and DC power modules and up to 2 modules for signal retransmission and control.

USER’S MANUAL

(2264R00)

User’s Manual S40-T

Meter S40-T

Panel meter 72x36mm size for Pt100/RTD and Thermocouples

Panel meter for temperature signals, accepts Pt100/RTD with

2 and 3 wires, and thermocouples J, K, T, E, S, R, N, C, L and

X. Temperature display in degrees celsius (ºC) or fahrenheit

(ºF). Thermocouple cold junction compensation selectable.

Manual offset selectable. Selectable behavior for alarms in case of sensor break (‘to_high’ or ‘to_low’).

Power options with universal AC and DC ranges, and space for two additional control and/or signal retransmission modules.

Standard IP54 front protection, with optional upgrade to IP65 protection.

Instrument with small 72x36mm standard DIN size. Resolution 4 digits and negative sign.

Connections via plug-in screw terminals and configuration via three front push-buttons. For application on industrial environments.

Management for up to 4 alarms with 1 or 2 setpoints each alarm, with hysteresis and delays. Provides memory for maximum and minimum, display on selectable steps, password and selectable levels of brightness.

Order Reference

S40 -

Model

T -

Power

H

-H

(85-265 Vac/dc)

-L

(11-60 Vdc and 24/48 Vac)

-

Option1

---

-R1

(1 relay)

-AO

(Analogue Output)

-

(empty)

-

Option2

---

-R1

(1 relay)

-AO

(Analogue Output)

-

(empty)

-

Others

---

-65

(IP65)

-

(empty)

Precautions on installation

Risk of electrical shock. Instrument terminals can be connected to dangerous voltage.

Instrument protected with double isolation. No earth connection required.

Instrument is in conformity with CE rules and regulations. See

“CE Declaration of Conformity” further in this document.

This instrument has been designed and verified according to the 61010-1

CE security regulation, and is designed for applications on industrial environments. See the “CE Declaration of Conformity” further in this document for information on the category of measure and the degree of pollution levels that apply.

Installation of this instrument must be performed by qualified personnel only. This manual contains the appropriate information for the installation.

Using the instrument in ways not specified by the manufacturer may lead to a reduction on the specified protection level. Disconnect the instrument from power before starting any maintenance and / or installation action.

The instrument does not have a general switch and will start operation as soon as power is connected. The instrument does not have protection fuse, the fuse must be added during installation.

The instrument is designed to be panel mounted. An appropriate ventilation of the instrument must be assured. Do not expose the instrument to excess of humidity. Maintain clean by using a humid rag and do NOT use abrasive products such as alcohols, solvents, etc.

General recommendations for electrical installations apply, and for proper functionality we recommend : if possible, install the instrument far from electrical noise or magnetic field generators such as power relays, electrical motors, speed variators, ... If possible, do not install along the same conduits power cables (power, motor controllers, electrovalves, ...) together with signal and/or control cables.

Before proceeding to the power connection, verify that the voltage level available matches the power levels indicated in the label on the instrument.

In case of fire, disconnect the instrument from the power line, fire alarm according to local rules, disconnect the air conditioning, attack fire with carbonic snow, never with water.

FEMA ELECTRÓNICA - Page 2

User’s Manual S40-T

Logo

Alarms

Front View

Rear View

Option1 Option2

User’s Manual S40-T

Input signal connections - Pt100/RTD

Measure can be selected for 2 or 3 wire systems.

1 2 3 4 5

Select input Pt100 2Wires in the menu. Terminal 2 can be left unconnected.

Button

LE

Button

UP

Button

SQ

Units

RTD/Pt100

2 wires

1 2 3 4 5

Select input Pt100 3Wires in the menu

RTD/Pt100

3 wires

Input signal connections - Thermocouple

To configure, select the appropriate thermocouple type in the configuration menu.

1 2 3 4 5

Signal

+

-

Thermocouple

Power

Power Connections

6 7 8 9 0

~

+

~

-

Earth connection - Although a terminal is offered for earth connection, the connection is optional. The instrument does not need this connection for correct functioning nor for compliance with the security regulations.

Fuse - To comply with security regulation 61010-1, add to the power line a protection fuse acting as disconnection element, easily accessible to the operator and identified as a protection device.

Power “H” fuse 250mA time-lag

Power “L” fuse 400mA time-lag

FEMA ELECTRÓNICA - Page 3

User’s Manual S40-T

Technical Data

Digits 4

Type

Height

Display maximum

Display minimum

Decimal point

Overrange

Underrange

7 segments, red

14 mm

9999

-1999 selectable 8.8.8.8.

9999 flashing

-1999 flashing

Technical Data (cont.)

Power

Power “H”

Power “L”

85 to 265 Vac/dc

11 to 60 Vdc and 24/48Vac

Consumption <4W

Isolation 3500Veff for power “H”

2000Veff for power “L” all levels tested for 60 seconds

Signals accepted

Temperature scale

Display units

Thermocouple data

Thermocouples accepted J, K, T, E, S, R, N, C, L, X

(Thermocouple X is a linear 10uV/ºC signal)

Resolution 1º

Ranges

Max. error at 25ºC

Offset drift

Span drift*

CJC

CJC accuracy

CJC thermal drift

On sensor break

Acquisitions

Pt100/RTD and Thermocouples

ITS90

ºC or ºF, selectable see table 3 see table 3 see table 3 see table 3

*Note - span drift includes also the offset drift

automatic (“On”/“Off” selectable)

<1.0ºC

<0.04º/ºC

“to_high” or “to_low”, selectable

3 acquisitions / second

Pt100/RTD data

Sensors accepted

Resolution

Ranges

Alpha

Max. error at 25ºC

Offset drift

Span drift *

2 or 3 wire, selectable

1º or 0.1º, selectable

see table 3

Alpha385 or Alpha390, selectable see table 3 see table 3 see table 3

*Note - span drift includes also the offset drift

Cable compensation up to 14 Ohm

Compensation accuracy <0.02ºC / Ohm

Acquisitions 4 acquisitions / second

Configuration

Functions available

Steps

Memory of maximum

Memory of minimum

Password

Double setpoints

Brightness control

3 frontal push buttons yes, configurable yes yes yes, configurable yes yes, 5 levels

Options maximum 2

Mechanical

Mounting panel

Connections

Weight

Housing materials

Front size

Panel cut-out

Deep from panel plug-in screw terminals

<150 grams

ABS, polycarbonate, vergaflex

72x36mm

69x32.5mm

98mm (including terminal)

Protection

Temperature Operation 0 to 50ºC

Temperature Storage –20 to +70ºC

Warm-up 15 minutes

Type Range ºC

Pt100/RTD

800 / -200 ºC

Thermocouple J

1200 / -200 ºC

Thermocouple K

1372 / -200 ºC

Thermocouple T

400 / -200 ºC

Thermocouple E

1000 / -200 ºC

Thermocouple S

1768 / -50 ºC

Thermocouple R

1600 / -50 ºC

Max. error at 25ºC*

<0.2ºC

<2ºC

<2ºC

<2ºC

<2ºC

<4ºC

<4ºC

Range ºF

1562 / -328 ºF

2192 / -328 ºF

2372 / -328 ºF

752 / -328 ºF

1832 / -328 ºF

2282 / -58 ºF

2912 / -58 ºF

Thermocouple N

1300 / -200 ºC

Thermocouple C

2320 / 0 ºC

Thermocouple L

900 / -200 ºC

Thermocouple X

4000 / -200 ºC

<2ºC

<2ºC

<2ºC

<2ºC

2372 / -328 ºF

4192 / 32 ºF

1652 / -328 ºF

7232 / -328 ºF

Table 3 - Thermocouple and PT100/RTD specifications

IP54 standard

IP65 optional (Front sealed. Opening the front breaks the seal)

Offset drift

0.05º/ºC

0.05º/ºC

0.05º/ºC

0.02º/ºC

0.05º/ºC

0.20º/ºC

0.20º/ºC

0.05º/ºC

0.02º/ºC

0.05º/ºC

0.02º/ºC

Span drift*

*includes offset drift

0.10º/ºC

0.20º/ºC

0.20º/ºC

0.02º/ºC

0.20º/ºC

0.20º/ºC

0.20º/ºC

0.20º/ºC

0.02º/ºC

0.20º/ºC

0.02º/ºC

FEMA ELECTRÓNICA - Page 4

User’s Manual S40-T User’s Manual S40-T

Mechanical Dimensions (mm) Information Menu

36

72

32,5

Panel cut-out

69

18 80 8

Operating the Information Menu

To enter the “Information Menu” press the SQ button. The

“Information Menu” allows to visualize information and does not allow to modify the configuration of the instrument. It is not affected by the “PASSWord” function. During operation with the “Information Menu”, alarms remain “frozen” and are kept on-hold. Leaving the “Information Menu” returns to the measuring state of the instrument, without restart.

Information Menu Tree - See page 5.

Rollback - After 30 seconds without interaction from the operator, the instrument leaves the “Information Menu”.

Button SQ - Selects the visible option.

Button UP - Moves vertically along the available menu options.

Button LE - Leaves selected menu or leaves the “Informa-

tion Menu”.

Information Menu Description

Configuration (Conf) - Information on the configured input sensor and the degrees selected.

Maximum (MAX) - Value of the maximum display.

Minimum (MIn) - Value of the minimum display.

AlarmX (ALX) - Configuration of alarm X. The sequence of information shows if the alarm is being managed (“On/Off”), the alarm type (“Max/Min”), the setpoint, the hysteresis value, the activation delay and the value of setpoint2 (“Off” or the setpoint2 value).

OptionX (OptX) - Type of module installed. If there is no module shows “nonE”.

Configuration

Sensor type

ºC or ºF

Memory of maximum

Maximum

Memory of minimum

Minimum

Alarm1

Option1

Option2

“On / Off”

“Max” / “Min”

Setpoint

Counts

Hysteresis

Delay

Setpoint2

See menu for Alarm1

See menu for Alarm1

See menu for Alarm1

Option installed

Option installed

Seconds

Second setpoint

FEMA ELECTRÓNICA - Page 5

User’s Manual S40-T

Operating the Configuration Menu

To enter the “Configuration Menu” press the SQ button. The

“Configuration Menu” allows to change the configuration of the instrument. Access to the “Configuration Menu” can be password protected with the function “PASSWord”. During operation with the “Configuration Menu” the alarms remain

“frozen” and are kept on-hold. When leaving the “Configura-

tion Menu” the instrument performs a restart, and new configuration is applied. During the restart of the instrument a short alarm deactivation is performed.

Configuration Menu Tree - See page 6 and 7.

Description of Configuration Menu functions - See page

8 and 9.

Rollback - After 30 seconds without interaction from the operator, the instrument leaves the “Configuration Menu”, discarding all changes.

Button SQ - Moves horizontally on the menu. Allows selection of the current option displayed. During a value selection menu (for example a setpoint value) validates the value on display.

Button UP - Moves vertically on the menu. Displays the available menu options. During a value selection menu (for example a setpoint value) increases digit value from 0 to 1,

2, 3, 4, 5, 6, 7, 8, 9.

Button LE - Leaves the current menu. Pressing LE several times will leave all menus and leave the “Configuration Menu” tree. During a value selection menu (for example a setpoint value) allows to select each digit for modification with the

UP button.

Reset - Leaving the “Configuration Menu” forces a restart of the instrument, even in case of no changes in configuration.

Input

Temp. Config,

Configuration Menu

Pt100/RTD 2 wires

Pt100/RTD 3 wires

Thermocouple J

Thermocouple K

Thermocouple T

Thermocouple E

Thermocouple S

Thermocouple R

Thermocouple N

Thermocouple C

Thermocouple L

Thermocouple X

Degrees

Pt100/RTD res..

Offset

Celsius

Fahrenheit

1º Resolution

0.1º Resolution

Offset counts to add

Thermoc. CJC

On break

Reading to high

Reading to low

Alpha

FEMA ELECTRÓNICA - Page 6

User’s Manual S40-T

Alarms

Alarm1

Active = On

Inactive = Off

Max=Maximum

Min= Minimum

Setpoint

Hysteresis

Delay

Setpoint2

See menu for Alarm1

See menu for Alarm1

See menu for Alarm1

Display

Steps

Maximum

Minimum

User’s Manual S40-T

Configuration Menu

Tools

Alarm management

Password

Factory Default

Alarm as max.

Alarm as min.

Version

Brightness

Counts

Seconds

Second setpoint

Configuration for Option1

Option1

Option2

Configuration for Option2

Select password

Counts for step

Memory of maxim.

Reset of maxim.

Memory of minim.

Reset of minim.

Default factory configuration

Sensor Pt100 2Wire

Degrees ºC

Resolution 0.1º

Offset 0

On Break To high

Alpha 385

Alarms 1,2,3 and 4

Active

Type

Setpoint

Hysteresis

Delay

Setpoint2

Display

Off (not managed) maximum

1000

0 counts

0.0 seconds

Off

Steps Off

Memory of maximum -9999

Memory of minimum 9999

Tools

Password

Brightness

Off

3

FEMA ELECTRÓNICA - Page 7

Resets to factory default values

Firmware version

Minimum brightness

Default brightness

Maximum brightness

User’s Manual S40-T

Input Menu

The input menu selects the input signal range. Options available are Pt100/RTD 2 or 3 wires, and thermocouples J, K, T,

E, S, R, N, C, L and X.

Note - Thermocouple X is a linear signal at 10uV/ºC.

Hysteresis (hySt) - Value from “0” to “9999”. Points of hysteresis. The hysteresis applies on the deactivation of the alarm.

Delay (dEL) - Value from “0.0” to “99.9” seconds. Delay to be applied to the relay activation and deactivation. Relays are activated and deactivated X seconds after the activation / deactivation of the alarm. The delay affects only to the relays.

The delay does not affect to the front leds.

Temperature Configuration Menu

The temperature configuration menu sets the function parameters for Pt100/RTD and thermocouple sensors.

Degrees (dEG) - Value “ºC/ºF”. Select the temperature to be displayed in celsius or fahrenheit degrees.

Setpoint2 (SEt2) - Value from “-1999” to “9999”. Second setpoint. The second setpoint allows for the creation of activation windows. If the alarm is configured as maximum with setpoint 1000 and setpoint2 is configured at 1500, the alarm will be activated between 1000 and 1500 and the alarm will be deactivated when display is <1000 and >1500. Setpoint2 is affected on the same way as the setpoint with hysteresis and delays.

Pt100/RTD resolution (P.rES) - Value “1º/0.1º”. Resolution for the Pt100/RTD. Select to display with degree or tenth of degree resolution.

Display Menu

Functions on this menu allow for configuration of the visualization.

Offset (oFFS) - Value from “-1999” to “9999” counts. Offset to be added to the reading. Both for Pt100/RTD and thermocouples.

Thermocouple Cold Junction Compensation (t.cJc) - Value “On/Off”. Select “On” for automatic CJC compensation in the instrument. Select “Off” to disable the CJC compensation.

Steps (StEP) - Display changes on predefined steps. Values are 1, 2, 5, 10, 20 and 50. The display is made in steps of X counts. For example, select a step of 20 will make the display to change in steps of 20 (1420, 1440, 1460, ...).

On break (on.bk) - Value “to_h/to_l”. Select “To L” to make the reading go to minimum, in case of probe broken. Select

“To H” to make the reading go to maximum in case of probe broken.

AlarmX Menu

Maximum (MAX) - Memory of maximum display. Indicates the maximum value of display since the last reset of the memory. Memory is reset on the following cases : manual reset from the Configuration Menu (Maximum), change on the input signal (Input), modification on the scaling (Scaling), change on the decimal point (dP), modification of the linearization segments, or instrument power-down.

Alpha (ALPh) - Value “385/390”. Select “385” or “390” according to your PT100/RTD sensor.

The instrument manages up to 4 alarms. Each alarm is controlled by the condition “display higher (or lower) than the configured setpoint”. The front leds are controlled by the activation / deactivation of the related alarm. The relays installed on Option1 and/or Option2 are controlled by Alarm1 and Alarm2.

Minimum (MIn) - Memory of minimum display. Indicates the minimum value of display since the last reset of the memory.

Memory is reset on the following cases : manual reset from the Configuration Menu (minimum), change on the input signal (Input), modification on the scaling (Scaling), change on the decimal point (dP), modification of the linearization segments, or instrument power-down.

Active (Act) - Value “On/Off”. Defines if the instrument has to manage this alarm or not. Select “Off” for alarm not managed.

Type (tyPE) - Value “Max/Min”. Defines the behavior of the alarm as maximum or minimum alarm. The alarms configured as maximum are activated when the display value is equal or higher than the setpoint. The alarms configured as maximum are deactivated when the display is lower than the setpoint. The alarms configured as minimum have the inverse behavior.

Setpoint (SEt) - Value from “9999” to “-1999”. Alarm set point.

FEMA ELECTRÓNICA - Page 8

User’s Manual S40-T User’s Manual S40-T

Tools Menu

Password (Pass) - Select a number to act as password. This password will be requested when entering the Configuration

Menu. To deactivate the password select “Off”.

Factory Settings (Fact) - Factory default configuration. Select “yES” to activate the factory default configuration.

Version (Ver) - Firmware version installed.

Light (Ligh) - Luminosity. Select between 5 predefined levels of luminosity.

Options Menu

Menu options OPT1 and OPT2 give access to the configuration menus of the installed options. The menu depends on the installed option. If there is no option installed the instrument shows “nonE”.

Messages and errors

When the instrument detects that the displayed value does not correspond to the input value, the display will flash and alternate with a message.

h.udr” Hardware underrange. The thermocouple signal is lower than minimum readable signal (-30mV).

h.oVr” Hardware overrange. The thermocouple signal is higher than maximum readable signal (80mV).

d.udr” Display underrange. The Pt100/RTD is shortcircuited.

hoLd” The instrument is showing the value present when the hold function was activated. Hold function is active.

Min” The instrument displays the minimum displayed value in memory. The minimum visualization is active.

MAX” The instrument displays the maximum displayed value in memory. The maximum visualization is active.

brk” The instrument displays “brk” with either “9999” or

“-9999” when : 1) resistance measured is higher than 390

Ohms (higher than 850ºC for PT100/RTD measure), or 2) in case the third wire ohm is higher than 15 Ohm, or 3) thermocouple measure is open circuit.

Err.1

Password incorrect.

Err.2

The instrument has detected an installed option but was unable to communicate.

T H

I S

S

E C

T I

O

N

B L

A N

K

FEMA ELECTRÓNICA - Page 9

User’s Manual S40-T

Option R1 - 1 relay

Relay type

Maximum current

Voltage

Instalable in

Connections for Option1

3 contacts (Com, NC, NO)

8A (resistive load)

250 Vac continuously

Option1 and/or Option2

Connections for Option2

A B C D E F G H I J

K L M N O P Q R

NC

NO

Common

Warranty

NC

NO

Common

Accessing the instrument

You may need to access the inside of the instrument to insert additional options. Use a flat screwdriver to unlock the upper clips marked with “A”. Then unlock the lower clips marked with “B” and move out the front filter. Let the inside of the instrument slide out of the housing.

To reinsert the instrument make sure that all modules are correctly connected to the pins on the display module. Place all the set into the housing, assuring that the modules correctly fit into the internal guiding slides of the housing. Once introduced, place again the front filter by clipping first the upper clips “A” and then the lower clips “B”.

Important - If your instrument was delivered with the IP65 front seal option, accessing the inside of the instrument will permanently break the IP65 seal on the areas of clips “A” and “B”.

A

All instruments are warranted against all manufacturing defects for a period of 24 MONTHS from the shipment date.

This warranty does not apply in case of misuse, accident or manipulation by non-authorized personnel. In case of malfunction get in contact with your local provider to arrange for repair. Within the warranty period and after examination by the manufacturer, the unit will be repaired or substituted when found to be defective. The scope of this warranty is limited to the repair cost of the instrument, not being the manufacturer eligible for responsibility on additional damages or costs. .

B

CE Declaration of Conformity

Manufacturer FEMA ELECTRÓNICA, S.A.

Altimira 14 - Pol. Ind. Santiga

E08210 - Barberà del Vallès

BARCELONA - SPAIN www.fema.es - [email protected]

Immunity rules

61000-6-2

61000-4-2

Generic rules of immunity

By contact ±4KV - Criteria B

On air ±8KV - Criteria B

Products - S40-T

Security rules 61010-1

Equipment “Fixed”

“Permanently connected”

Pollution degree 1 and 2 (without condensation)

Isolation Double

61000-4-3 Criteria A

61000-4-4 On AC power lines: ±2KV - Criteria B

On DC power lines: ±2KV - Criteria B

On signal lines : ±1KV - Criteria B The manufacturer declares that the instruments indicated comply with the directives and rules indicated below.

Directive of electromagnetic compatibility 2004/108/CEE

Directive of low voltage 73/23/CEE

61000-4-5 Between AC power lines ±1KV - Criteria B

Between DC power lines ±0.5KV - Criteria B

61000-4-6 Criteria A

61000-4-8 30A/m at 50Hz - Criteria A

61000-4-11 0% 1 cycle Criteria A

40% 10 cycle Criteria B

70% 25 cycle Criteria B

0% 250 cycle Criteria B

Emission rules

61000-6-4 Generic rule of emission

Barberà del Vallès November 2011

Daniel Juncà - Quality Manager

FEMA ELECTRÓNICA - Page 10

User’s Manual S40-T User’s Manual S40-T

T H

I S

P

A G

E

B L

A N

K

FEMA ELECTRÓNICA - Page 11

other products

Panel Meters

Standard 96x48mm

Panel Meters

Small 72x36mm

Panel Meters

Miniature 48x24mm

Large Displays

60&100mm digit

Signal Converters

& Isolators

Panel Meters

Standard 96x48mm

www.fema.es

ELECTRONIC INSTRUMENTATION FOR INDUSTRY

FEMA ELECTRÓNICA, S.A.

Altimira 14 - Pol. Ind. Santiga

E08210 Barberà del Vallès

BARCELONA - SPAIN

Tel. (+34) 93.729.6004 - www.fema.es

Fax (+34) 93.729.6003 - [email protected]