Intermatic T174 T170 Series 40 Amp 24-Hour Mechanical Time Switch Instructions
Add to my manuals1 Pages
Intermatic T174 is a 24-hour dial time switch with a "Skipper" feature, allowing you to automate lighting, motors, and other electrical devices based on time of day and day of the week. It supports a variety of loads, including resistive, inductive, tungsten, electronic ballasts, and motors, with a maximum load of 40 amps per pole for resistive loads and 16 amps for electronic ballasts. The switch features a manual lever for overriding automatic operation and a skipping mechanism for selecting the days of the week when the switch should operate.
advertisement
MODEL: T174
24 HOUR DIAL TIME SWITCH
WITH “SKIPPER
®
”
LR3730
TYPE 1 INDOOR USE ONLY
DOUBLE POLE SINGLE THROW (DPST)
40 A RESISTIVE, PER POLE 120 - 480 VAC; 40 A INDUCTIVE,
TUNGSTEN OR 1000 VA PILOT DUTY PER POLE 120 - 277 VAC;
2 HP (24 FLA) - 120 VAC; 5 HP (28 FLA) - 240 VAC
16 A ELECTRONIC BALLAST, 277 VAC
UL
HOLOGRAM
LABEL
WARNING Risk of Fire or Electric Shock
• Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
• Installation and/or wiring must be in accordance with national and local electrical code requirements.
• Use wires rated at least 90°C - COPPER conductors ONLY.
• Replace plastic insulator covering terminals before powering ON.
• KEEP DOOR CLOSED AT ALL TIMES when not servicing.
AVERTISSEMENT Risque d’incendie ou de choc électrique
• Utiliser des fils classés 90 °C minimum - Conducteurs en CUIVRE UNIQUEMENT.
NOTICE
• Rotate timer dial clockwise only.
• Do not move the clock hands on the timer. Moving the clock hands can damage the timer.
CLOCK MOTOR: 208-277 VAC, 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER
REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
POINTER
TIME
DIAL
OFF
TRIPPER
MANUAL
LEVER
ON/CUTOUT
TRIPPER
DAY
ARROW
SKIPPER
WHEEL
SKIPPING
SCREW
WIRING DIAGRAM
240V 2 WIRE
AND GROUND
240V
SUPPLY
GR
LINE 1
LINE 2
A 1 2 3 4
GROUND
CLOCK
MOTOR
TO
LOAD(S)
277/480 VOLT CONNECT MOTOR LEADS TO TERMINALS “A”
AND 1 AND SUPPLY NEUTRAL TO TERMINAL “A”.
WIRING INSTRUCTIONS: Remove 1/2 inch of insulation from wire ends. Tighten terminal screws firmly
(2-18 in-lbs). Use solid or stranded COPPER conductors only. May use two wires of the same size and type.
MINIMUM
COPPER
WIRE SIZE
(AWG)
MAX.
LOAD
(AMP)
MIN.
INSUL-
ATION
TEMP(°C)
75°C INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE
120 V.
240 V.
208 V.
3 PHASE
240 V.
PRESSURE PLATE
TERMINAL SCREW
14
12
10
8
15
20
30
40
90
90
90
90
1/2
1
-
2
2
2 1/2
3
5
N/A N/A
MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE
PROGRAMMING INSTRUCTIONS
1.
TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-DIAL , pointing to time (AM or PM) when ON and OFF operations are desired, tighten tripper screws firmly.
For additional tripper pairs on CLOCK-DIAL order 156T1948A.
2. Pull CLOCK-DIAL outward. Turn in either direction and align the exact time-of-day on the CLOCK-DIAL (the time now, when switch is being put into operation) to the pointer.
DO NOT MOVE POINTER.
3.
TO SKIP OPERATION(S) ON SELECTED DAY(S): Insert SKIPPING SCREW(S) in SKIPPER
WHEEL for day(s) automatic operation(s) is/are NOT required. Tighten screws firmly. Move
MANUAL LEVER to “OFF” and rotate SKIPPER WHEEL to locate correct day-of-week opposite DAY ARROW--”YESTERDAY” if ON/CUTOUT TRIPPER has not yet advanced wheel “TODAY” if it has.
OPERATING INSTRUCTIONS
• TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER below CLOCK-DIAL left or right as indicated by arrows. This will not effect next operation.
CAUTION: TO AVOID SLOW SWITCH ACTION FAILURE, DO NOT OPERATE
SWITCH MANUALLY NOR PLACE A TRIPPER 4 HOURS PRIOR TO
ON/CUTOUT TRIPPER SWITCHING.
IN CASE OF POWER FAILURE, programming instructions.
reset CLOCK-DIAL to proper time-of-day. See