Potter Electric 1119611 IntelliGen™ 1/2 in. FNPT Brass and Steel Nitrogen Generator Installation Manual

Add to My manuals
49 Pages

advertisement

Potter Electric 1119611 IntelliGen™ 1/2 in. FNPT Brass and Steel Nitrogen Generator Installation Manual | Manualzz

INS-500/1000

Nitrogen Generators

Installation, Operation, and

St. Louis, MO

800-325-3936 www.pottersignal.com

Manual #5403645 - F

09/19

INS-500 & INS-1000 • 5403645 • REV F • 09/19

WARRANTY INFORMATION

GENERAL PROVISIONS & LIMITATIONS

Potter Electric Signal Company, LLC (the “Company”) warrants to each original purchaser (“Purchaser”) of its new products from the

Company or its Authorized Distributor that such products are, at the time of delivery to the Purchaser, made with good materials and workmanship. No warranty is made with respect to:

1. Any product, which has been repaired or altered in such a way, in the Companies judgment, as to affect the product adversely.

2. Any product, which has, in the Companies judgment been subjected to negligence, accident, improper storage, improper installation or application.

3. Any product, which has not been operated or maintained in accordance with the recommendations of the Company.

4. Components or accessories manufactured, warranted and serviced by others.

5. Any reconditioned or prior owned product.

Claims for items described in 4 above should be submitted directly to the manufacturer.

WARRANTY PERIOD

The Company’s obligation under this Warranty is limited to repair or, at its option, replacing during normal business hours at the designated facility of the Company, any part that in its judgment proved not to be as warranted within the applicable Warranty Period as follows.

COMPONENTS

All non-consumable components are warranted for 12 months from the date of purchase. Consumable are not covered under warranty. The unit must have been installed by either a factory authorized distributor or agent in accordance with the factory recommendations taking into account all other local site conditions not originally noted to the factory. The unit must be operated and maintained in accordance with the

Factory recommendations and original design conditions. Failure to provide such proof of the above may void warranty.

LABOR TRANSPORTATION & INSPECTION

The Company will repair or replace any product or part thereof which in the Companies judgment is proved to be not as warranted. Labor costs are not covered under warranty.

All costs of transportation of product, labor or parts claimed not to be as warranted and, of repaired or replaced parts to or from factory shall be borne by purchaser. The Company may require the return of any part claimed not to be as warranted to one of its facilities as designated by the Company, transportation prepaid by Purchaser, to establish a claim under this warranty.

Replacement parts provided under the terms of the warranty are warranted for the remainder of the Warranty Period of the product upon which installed to the same extent as if such parts were original components.

DISCLAIMER

THE FOREGOING WARRANTY IS EXCLUSIVE AND IT IS EXPRESSLY AGREED THAT, EXCEPT AS TO TITLE, THE

COMPANY MAKES NO OTHER WARRANTIES, EXPRESSED OR IMPLIED OR STATUTORY, INCLUDING ANY IMPLIED

WARRANTY OR MERCHANTABILITY.

THE REMEDY PROVIDED UNDER THIS WARRANTY SHALL BE THE SOLE, EXCLUSIVE AND ONLY REMEDY AVAILABLE

TO THE PURCHASER AND IN NO CASE SHALL THE COMPANY BE SUBJECT TO ANY OTHER OBLIGATIONS OR

LIABILITIES. UNDER NO CIRCUMSTANCES SHALL THE COMPANY BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL OR

CONSEQUENTIAL DAMAGES, EXPENSES, LOSSES OR DELAYS HOWSOEVER CAUSED.

No statement, representation, agreement, or understanding, oral or written, made by any agent, distributor, representative or employee of the Company which is not contained in this Warranty will be binding upon the company unless made in writing and executed by an officer of the Company.

This warranty shall not be effective as to any claim which is not presented within 30 days after the date upon which the product is claimed not to have been as warranted. Any action for breach of this warranty must be commenced within one year after the date upon which the cause of action occurred.

Any adjustment made pursuant to this warranty shall not be construed as an admission by the Company that any product was not as warranted.

PROMPT DISPOSITION

The Company will make a good faith effort for prompt correction or other adjustment with respect to any product, which proves to be defective within the warranty period. Before returning any product, write or call the distributor, agent or authorized company from which the product was purchased, describing defect and giving date and number of original invoice, as well as proof of Factory supplied consumable and proof of scheduled maintenance. Title and risk of loss pass to buyer upon delivery to the common carrier.

PRODUCT SUITABILITY

Many States, Localities and Countries have codes and regulations governing sales, construction, installation, and/or use of products for certain purposes, which may vary from those in neighboring areas. While Potter attempts to assure that its products comply with such codes, it cannot guarantee compliance, and cannot be responsible for how the product is installed or used. Before purchase and use of a product, please review the product application, and national and local codes and regulations, and be sure that the product, installation, and use will comply with them.

Potter Electric Signal Company, LLC

St. Louis, MO • (866) 956-0988

2

INS-500 & INS-1000 • 5403645 • REV F • 09/19

C

ontents

Safety Guidelines .........................................................................................................................................................................4

Important Notice to Users ...................................................................................................................................................4

Unpacking ...........................................................................................................................................................................4

General Safety Information .................................................................................................................................................4

System Overview .........................................................................................................................................................................6

Key Terms ...........................................................................................................................................................................6

IntelliGen ™ Controller ........................................................................................................................................................6

INS-500/1000 Exterior View .......................................................................................................................................................7

INS-500/1000 Interior View ........................................................................................................................................................8

IntelliGen ™ Display ....................................................................................................................................................................9

Installation of the Nitrogen Generator .........................................................................................................................................10

Wiring of the Nitrogen Generator ................................................................................................................................................12

Nitrogen Generator Operation .....................................................................................................................................................14

Nitrogen Functionality Test ........................................................................................................................................................16

Filling the Sprinkler System and Purging ....................................................................................................................................17

Purging with IntelliPurge ® Nitrogen Purge Valve (INS-PV) .......................................................................................................18

Purging with Potter Nitrogen Purge Valve (NGP-SPV) ..............................................................................................................19

IntelliView

IntelliPurge

®

Dashboard Connectivity .........................................................................................................................................20

Wiring and Networking ..........................................................................................................................................21

Maintenance and Part Replacements ...........................................................................................................................................23

Standard Maintenance (Every 1,000 Compressor Operating Hours) ..........................................................................................24

Compressor Air Intake Filters .............................................................................................................................................25

Air Tank Blow-down Strainer .............................................................................................................................................25

Filter Elements ....................................................................................................................................................................26

Resetting Maintenance Alert and Checking for Leaks .......................................................................................................28

Air Compressor Replacement ......................................................................................................................................................29

Nitrogen Membrane Replacement ...............................................................................................................................................29

Maintenance Alerts and Actions ..................................................................................................................................................30

Trouble Alerts and Probable Causes ............................................................................................................................................31

Troubleshooting ...........................................................................................................................................................................33

Leak on Sprinkler System or Nitrogen Generator ..............................................................................................................33

Nitrogen Flow Rate and Nitrogen Purity Test ....................................................................................................................33

Normal Operating Parameters of the INS-500/1000 ...................................................................................................................34

Nitrogen Generator Leak Detection System ................................................................................................................................35

To Change the Leak Rate Warning Set Point ........................................................................................................................36

To Change Sprinkler System Size ........................................................................................................................................36

INS-500/1000 Dimensional Drawings .........................................................................................................................................37

INS-500/1000 Piping Instrumentation Diagram ..........................................................................................................................38

Wiring Diagrams ..........................................................................................................................................................................39

INS-500/1000 Single Phase 115VAC .................................................................................................................................39

INS-500/1000 Single Phase 230VAC .................................................................................................................................40

INS-500/1000 Three Phase 230VAC ..................................................................................................................................41

INS-500/1000 Three Phase 460VAC ..................................................................................................................................42

Menu Trees...................................................................................................................................................................................43

Menu Tree 1 ........................................................................................................................................................................43

Menu Tree 2 ........................................................................................................................................................................44

Menu Tree 3 ........................................................................................................................................................................45

Menu Tree 4 ........................................................................................................................................................................46

Menu Tree 5 ........................................................................................................................................................................47

Menu Tree 6 ........................................................................................................................................................................48

Menu Tree 7 ........................................................................................................................................................................49

3

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Safety Guidelines

This manual contains safety information that is important to know and understand. This information is provided for the safety of installers, operators, and users of the Potter

Nitrogen Generator as well as equipment. To help recognize this information, observe the following symbols.

D

Danger indicates an imminently hazardous situation which, if not avoided, WILL result in death or serious injury.

Warning indicates a potentially hazardous situation which, if not avoided, COULD result in death or serious injury.

CAUTION

Caution indicates a potentially hazardous situation which, if not avoided, MAY result in minor or moderate injury

Notice indicates important information, that if not followed may cause damage to equipment or property.

Important Notice to Users

The Installation, Operation, and Instruction Manual supplied with each unit must be read thoroughly and completely understood before installation and operation of the Potter IntelliGen ™ Nitrogen Generator. All appropriate safety standards for handling of gases as determined by local or national laws and regulations should be followed at all times.

Unpacking

After unpacking unit, carefully inspect all parts and equipment for any damage that may have occurred during transit. Make sure to tighten fittings, bolts, etc. before putting unit into service.

Do not operate if damage occurred during shipping, handling, or use. Contact Potter immediately.

General Safety Information

Important: Read all of the safety information in this manual before operating this equipment. Use of the equipment in a manner not specified within this manual may impair the protection provided by the generator and could result in an unplanned release of pressure, which may cause serious injury or damage. Only competent personnel, who have been trained, qualified, and approved by Potter Electric Signal Company should perform commissioning, servicing, and repair procedures.

When handling, installing, or operating this equipment, personnel must employ safe engineering practices and observe all related local regulations, health, and safety procedures, and legal requirements for safety. Ensure that the equipment is depressurized and electrically isolated, before carrying out any of the scheduled maintenance instructions specified in this manual.

4

INS-500 & INS-1000 • 5403645 • REV F • 09/19

The warnings in this manual cover most known potential hazards, but by definition cannot be all-inclusive. If the user employs an operating procedure, item of equipment, or a method of working that is not specifically recommended by Potter Electric Signal

Company, the user must ensure that the equipment will not be damaged or become hazardous to persons or property.

Nitrogen is not a poisonous gas. However, in a concentrated form, there is a risk of asphyxiation. The generator produces a flow of nitrogen and oxygen enriched air which quickly disperses in the atmosphere. However, do not directly inhale the output gas from the outlet pipe.

The generator is classified as non-hazardous for transportation purposes and as non-flammable for fire regulations. This equipment is for indoor use only. Do not operate outdoors.

Operation of the nitrogen membrane separator above the rated design pressure may be hazardous. Do not connect it to compressed air sources that can exceed its maximum rated pressure without installing appropriate pressure controls and safety relief devices in the compressed air supply line.

Specific procedure must be developed for maintenance of the equipment on which the membrane separator is located. Appropriate labels must be continuously displayed in all areas where personnel might be exposed to a nitrogen atmosphere under normal or upset condition.

Do not attempt to disassemble the nitrogen membrane separator. Equipment damage may occur and cause the system to function incorrectly.

5

INS-500 & INS-1000 • 5403645 • REV F • 09/19

System Overview

Potter IntelliGen ™ Nitrogen Generators are specifically designed to provide clean, dry, high purity nitrogen for use in fire protection sprinkler systems. The generator is a fully assembled package ready to be connected to a new or existing fire sprinkler system using a factory pre-engineered air compressor. These easy-to-use systems include all air filtration equipment and controls required to keep the generator operating at peak efficiency.

The Potter IntelliGen ™ Nitrogen Series operates using membrane technology. The smaller oxygen and water vapor molecules can pass through (permeate) the membrane quickly. The larger nitrogen molecules are less likely to diffuse through the separator tubes; therefore, they continue downstream to the separator outlet. The permeated molecules are discharged to the atmosphere through a vent in the separator housing.

Key Terms

Bypass Mode – Most nitrogen generators cannot produce enough nitrogen to completely fill the sprinkler system in 30 minutes required by NFPA 13. Therefore, they contain valves that allow the nitrogen membrane to be bypassed so the system can be filled with compressed air. The valve setting that bypasses the nitrogen membrane is called Bypass Mode.

Nitrogen Generating Mode – The valve setting that allows the air to flow through the nitrogen membrane and create nitrogen is called Nitrogen Generating Mode.

Purging – Purging is defined as the removal of oxygen from the sprinkler system via a purge valve. The purge valve allows some gas to escape from the system which requires the nitrogen generator to supply nitrogen to maintain system pressure. This process therefore increases the nitrogen concentration within the system piping over time.

IntelliGen

Controller

The IntelliGen ™ of the IntelliGen

Nitrogen Generator Series is the only line of intelligent nitrogen generators for fire sprinkler systems. At the heart

™ units, is the IntelliGen ™ Controller. The IntelliGen to ensure the unit is performing optimally. The IntelliGen ™

™ Controller monitors every aspect of the nitrogen generator

Controller monitors pressure, runtime, power, connectivity and operational mode. Using this information and proprietary algorithms, the IntelliGen ™ Controller can determine if the unit needs to be in Bypass Mode or Nitrogen Generating Mode. No need to manually change ball valve configurations or worry if the unit is producing nitrogen. Also, by monitoring the generator activity the controller can indicate the development of sprinkler system leaks, user interaction, and even if maintenance to the generator is required. Combined with the IntelliPurge

Valve, the IntelliGen ™

® Nitrogen Purge

Nitrogen Generator is the only system that can truly monitor and protect a sprinkler system.

See Menu Tree Diagram on page 43 for more information on programming.

The INS-500 and the INS-1000 are FM approved per FM 1035 "Nitrogen Generators".

• The INS-500 has a Bypass Fill Capacity of 500 gallons at 40 PSI and a Total System Capacity of 1,850 gallons

• The INS-1000 has a Bypass Fill Capacity of 1,000 gallons at 40 PSI and a Total System Capacity of 3,400 gallons

Part Number

1119607

1119608

1119611

1119612

1119613

Model

INS-500, 115VAC 1PH 60 HZ

INS-500, 230VAC 1PH 60 HZ

INS-1000, 230VAC 1PH 60 HZ

INS-1000, 230VAC 3PH 60 HZ

INS-1000, 460VAC 3PH 60 HZ

Description

IntelliGen ™ Nitrogen System-500, 115VAC Single Phase

IntelliGen ™ Nitrogen System-500, 230VAC Single Phase

IntelliGen ™ Nitrogen System-1000, 230VAC Single Phase

IntelliGen ™ Nitrogen System-1000, 230VAC Three Phase

IntelliGen ™ Nitrogen System-1000, 460VAC Three Phase

6

INS-500/1000 Exterior View

Fig. 1

1

INS-500 & INS-1000 • 5403645 • REV F • 09/19

2

3

4

9

8

5

6

7

11

10

12

13

14

15

1. Upper Cabinet Latches (Qty. 2)

2. IntelliGen

Display

3. Air Compressor Power Switch

4. Nitrogen Tank

5. Nitrogen Tank Gauge

6. 12" Flex Hose to Fire Sprinkler System (1/2"

MNPT)

7. N

2

Tank Outlet Valve (V03)

8. N

2

Tank Inlet Valve (V02)

9. Air Tank

10. Air Tank Gauge

11. Air Tank Outlet Valve (V01)

12. Blow-Down Solenoid (AD01)

13. Valve With Strainer

14. 3/8" Drain Tube (10' Supplied)

15. Ø9/16" Mounting Hole (Qty. 4)

7

INS-500/1000 Interior View

Fig. 2

INS-500 & INS-1000 • 5403645 • REV F • 09/19

4 5 6

3

2

1

20

19

22

21

18

1. Nitrogen Membrane (M01)

2. Flow Control Valve (FCV01)

3. Back Pressure Regulator (PRV02)

4. Instrument Air Solenoids

5. Membrane Outlet N

2

Solenoid (XV02)

6. IntelliGen

Controller

7. Owner Supplied Power Connection

8. PLINK Connection

9. BMS Connection

10. Pressure Transducer (PI01)

11. Nitrogen Sample Port (SP)

7

8

9

10

11

12

13

14

15

16

17

8

12. N

2

Bleed Valve (V04)

13. Bypass Solenoid Valve (XV03)

14. Coalescing Filter 5µm (F01)

15. Coalescing Filter 1µm (F02)

16. Coalescing Filter .01µm (F03)

17. Activated Carbon Filter with Drain Valve (F04)

18. Cooling Fan (CF01)

19. Excess Air Regulator (PRV01)

20. Membrane Inlet Air Solenoid (XV01)

21. Instrument Air Filter (F05)

22. Instrument Air Regulator (PRV03)

INS-500 & INS-1000 • 5403645 • REV F • 09/19

IntelliGen

Display:

The IntelliGen ™ Display is the interface to the IntelliGen ™ Nitrogen Generator. This display shows the generator’s history, parameters, and troubles; as well as devices networked to the unit.

Fig. 3

POWER

SILENCED

BYPASS

SILENCE CLEAR

PURGING

MAINTENANCE

TROUBLE

1 2

4 5

7 8

MAINT PURGE

ENTER 0

3

6

9

ESC

IntelliGen

Display LED Light Indications:

POWER – The green POWER LED indicates if the IntelliGen ™ Nitrogen Generator has power.

SILENCED – The amber SILENCED LED indicates the Trouble Horn on the IntelliGen ™ Nitrogen Generator is silenced.

BYPASS – The amber BYPASS LED indicates if the IntelliGen ™ indicator is off, the unit is in Nitrogen Generating Mode.

Nitrogen Generator is in Bypass Mode. If the Bypass LED

PURGING – The amber PURGING LED indicates the IntelliGen ™ Nitrogen Generator detects that a networked INS-PV is in a purge process.

MAINTENANCE – The amber MAINTENANCE LED indicates the IntelliGen ™ Nitrogen Generator needs maintenance.

TROUBLE – The red TROUBLE LED indicates the IntelliGen ™ Nitrogen Generator has a trouble condition.

IntelliGen

Display Button Indications:

SILENCE – The "SILENCE" button will silence the Trouble Horn on the IntelliGen ™ Nitrogen Generator.

CLEAR – The "CLEAR" button will clear all Troubles.

MAINT – The "MAINT" button will display the Maintenance Menu.

PURGE – The "PURGE" button will bring up the Purge Menu on the IntelliGen ™ Display.

9

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Installation of the Nitrogen Generator

1. On arrival, do a full inspection by checking all packages and crates in the shipment for damage.

2. If damage is found, sign for the damage or refuse the shipment. Contact the carrier immediately and file a shipping damage claim with the carrier.

3. Check to ensure all components are contained and no visible damage has occurred during shipping.

• Nitrogen Cabinet

• IntelliGen ™ Display

• Air Tank

• Nitrogen Tank

• Air Compressor

4. Each nitrogen generator requires a minimum of one Nitrogen Air Maintenance Device (NAMD) and one Nitrogen Purge

Valve per sprinkler system. Check to see these components have arrived.

• Nitrogen Air Maintenance Device (one per riser) (NAMD #1119660)

• Nitrogen Purge Valve (NGP-SPV #1119784) or (INS-PV #1119478)

• Portable Nitrogen Analyzer (one per job) (PNA #1119504)

5. Find a location for the nitrogen generator to be installed meeting these requirements:

• Dry, clean and well-ventilated

• Dimensions 54” X 42” X 32” (H x W x D)

• Ambient temperatures above 50º F at all times

• Access to front for service

• Conveniently located near fire sprinkler system connections

• Conveniently located near a drain

• Near a dedicated electrical circuit with an electrical disconnect switch

6. Mount the skid base to the floor using (4) 3/8” bolts. See Fig. 4.

Fig. 4

7. To plumb the nitrogen generator to the fire sprinkler system first, install the supplied 12" flexible hose to the N installation practices. See Fig. 5.

2

Tank Outlet

Valve (V03). Plumb the 1/2" NPT piping to the sprinkler system Nitrogen Air Maintenance Device using standard accepted

Fig. 5

1/2" MNPT to Fire

Sprinkler System

Supplied Flexible Hose

10

INS-500 & INS-1000 • 5403645 • REV F • 09/19

8. Pipe the provided 10' of the 3/8” drain tubing to the floor drain in the sprinkler room. Do not pipe the drain tubing upward.

Ensure drain tubing is restrained. See Fig. 6.

Fig. 6

Pipe to Floor Drain

9. Each riser requires a minimum of ONE Nitrogen Purge Valve to be installed prior to implementing the Nitrogen Purging

Procedure. For installation instructions, refer to Model NGP-SPV Bulletin (#5401520) or Model INS-PV Manual

(#5401532) supplied with each purge valve. See Fig. 7 for NGP-SPV installation diagram. See Fig. 8 for INS-PV installation diagram.

Fig. 7

11 1 /

4

"

PIPE FROM SPRINKLER SYSTEM

NGP-SPV

7"

1/2" NPT TEE CONNECTION AND CLOSE NIPPLE

(SUPPLIED BY SPRINKLER CONTRACTOR)

7 1 /

4

"

PURGE ORIFICE (N

2

SAMPLING PORT)

PIPE PLUG (INSTALL AFTER

PURGE COMPLETE)

REMOVE PLUG WHEN SAMPLING

N

2

LEVELS AND PURGING

UNION - POSITION VENT / ORIFICE

APPROPRIATELY

PURGE BALL VALVE

SHOWN IN NON - PURGE POSITION

INSPECTOR'S TEST VALVE

Fig. 8

PIPE FROM SPRINKLER SYSTEM

7 1/8"

VENT

DWG. #0400-13

20 1/2"

ORIFICE

UNION

INTELLIPURGE

INS-PV

7 1/4"

PURGE BALL VALVE, SHOWN

IN CLOSED (NON-PURGE) POSITION

INSPECTORS TEST VALVE

Installing the purge valve upside down will not allow the system to purge. Also, ensure that there is NO water in the pipe to the purge valve.

11

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Wiring of the Nitrogen Generator

All wiring should be performed by a licensed electrician and conform to NEC and all applicable local standards.

1. Run a dedicated electrical circuit with an electrical disconnect switch to sprinkler room.

2. To wire the INS-500 or INS-1000, open the front panel at the top of the nitrogen cabinet to access wiring terminal blocks. Use the 1/2" or 3/4" knockouts on back of cabinet for electrical conduit. See Fig. 9.

Fig. 9

Wiring Terminal

Block

(120V shown)

Knockouts

(Bottom knockout is hidden in drawing)

3. Depending on the voltage of the model (115V, 230V, 460V-Single or Three phase) follow the wiring diagram in this manual on page 39, or use the wiring diagram on the inside of the nitrogen generator cabinet door.

CAUTION

For Three Phase motors, ensure the air compressor turns in the correct direction labeled on the air compressor.

4. For internet connectivity (see the IntelliView ™ section on page 20 for more details), wire a CAT-5 Ethernet cable using a 1/2" knockout on the back of the cabinet to the Ethernet Port on the IntelliGen ™ Controller. See Fig. 10.

Fig. 10

12

Ethernet Port

INS-500 & INS-1000 • 5403645 • REV F • 09/19

5. Using the other 1/2" knockout on the back of the cabinet, wire the IntelliPurge ® Nitrogen Purge Valve to the IntelliGen ™

Controller using 3 wire cable (22-24 AWG stranded recommended). See the IntelliPurge ® Section on page 21 for more details. Connect the PLINK to the terminal blocks next to the controller. See Fig. 11.

Fig. 11

6. Using the same 1/2" knockout on the back of the cabinet, a form C relay is available to wire any BMS (Building Management

System) to the BMS terminal blocks. See Fig. 12.

Fig. 12

13

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Nitrogen Generator Operation

Initial Set Up:

1. Before beginning, make sure the water supply to the sprinkler system is turned off.

2. Make sure all piping connections have been made in accordance with the installation instructions.

3. Ensure the Air Compressor Power Switch located on the right side of the cabinet is in the "OFF" position.

4. Close the Nitrogen Air Maintenance Device. If multiple Nitrogen Air Maintenance Devices are used, ensure all valves are in closed position.

5. Close the N

2

Tank Outlet Valve (V03) on the nitrogen tank. See Fig. 13.

Fig. 13

To Fire Sprinkler System

V03

6. Turn power ON to the nitrogen generator using the contractor installed "Electrical Disconnect" switch.

7. The IntelliGen ™ Display will turn on, indicating power with a green LED labeled "POWER".

Note: There will be a short delay as the IntelliGen ™ Display turns on and the system boots up.

8. The amber LED labeled "BYPASS" will activate if the pressure is less than 55 PSI in the nitrogen tank.

14

INS-500 & INS-1000 • 5403645 • REV F • 09/19

9. Turn power ON to the air compressor using the switch labeled “Air Compressor Power” on the right side of the cabinet. See

Fig. 14.

Fig. 14

10. The air compressor will begin running and the pressure in the air tank and nitrogen tank will begin to rise. Start recording the time it takes until the compressor turns off.

11. When the nitrogen tank pressure reaches approximately 80 PSI the valves inside the cabinet will close.

12. When the air tank pressure reaches approximately 105 PSI the air compressor will turn off.

13. If the nitrogen generator is isolated from the sprinkler system:

• The air compressor of the INS-500 should take no longer than 8 minutes to pressurize both tanks and turn off.

• The air compressor of the INS-1000 should take no longer than 6 minutes to pressurize both tanks and turn off.

If the air compressor is not turning off, or it is taking longer than expected, go to the Troubleshooting section in this manual on page 33.

14. When the two tanks are pressurized, the amber LED labeled "BYPASS" on the IntelliGen ™ on the IntelliGen ™

Display will turn off and "Mode"

Display will change to "N2 Mode". This indicates that the unit is now in Nitrogen Generating Mode.

15. Check all piping connections for leaks as pre-plumbed fittings may have loosened during shipment. Any pressure drop on the tanks during this time could indicate a leak.

15

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Nitrogen Functionality Test:

1. To ensure the nitrogen generator is operating correctly and that the correct nitrogen purity is being produced, a functional test must be performed.

2. On the inside of the nitrogen cabinet locate the blue N

2

Bleed Valve (V04). See Fig 15.

Fig. 15

V04

3. Slightly open the blue N

2

Bleed Valve and begin relieving the pressure from the nitrogen tank.

4. Quickly close the blue N

2

Bleed Valve when you see the red instrument air solenoid lights turn on. This will happen at approximately 60 PSI as shown on the IntelliGen ™ display. See Fig 16.

Fig. 16

Note: If the pressure in the nitrogen tank drops below 55 PSI, the IntelliGen ™ Nitrogen Generator will return to

Bypass Mode. Close the valve and wait for the nitrogen generator to refill the tanks and the unit to return to Nitrogen

Generating Mode before trying again.

5. Immediately begin timing to see how long it takes to reach approximately 80 PSI in the nitrogen tank while the nitrogen generator is in Nitrogen Generating Mode.

6. If the nitrogen generator is isolated from the sprinkler system: a. The INS-500 should take no longer than 8 minutes to pressurize the nitrogen tank to 80 PSI.

b. The INS-1000 should take no longer than 4 minutes to pressurize the nitrogen tank to 80 PSI.

7. During this time, connect the Portable Nitrogen Analyzer to the Nitrogen Sample Port (SP) to measure the purity of the exiting gas. The analyzer should read 98.0% or greater. This may take a few minutes.

8. When the nitrogen generator reaches approximately 80 PSI in the nitrogen tank, the red instrument air solenoid lights will turn off. The air compressor will continue to run until the air tank pressure reaches approximately 105 PSI.

16

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Filling the Sprinkler System and Purging:

1. To fill the sprinkler system, open the N

2

Tank Outlet Valve (V03) on the nitrogen tank and open the bypass valve on the

Nitrogen Air Maintenance Device. See Fig. 17.

Fig. 17 V03

2. The pressure in the nitrogen tank and the air tank will decrease rapidly, causing the nitrogen generator to switch to Bypass

Mode.

3. The amber LED labeled "BYPASS" will turn on and the "Mode" on the IntelliGen ™ Display will turn to "Bypass Mode". This indicates that the nitrogen generator is filling the system with air to meet the NFPA required 30 minute fill time.

4. The air compressor will also turn on.

5. Allow the fire sprinkler system to reach the desired pressure. This should take 30 minutes or less.

6. As soon as sprinkler system supervisory pressure is reached, put the sprinkler system back into service by placing the

Nitrogen Air Maintenance Device in the maintenance position (refer to the Nitrogen Air Maintenance Device manual for proper operation).

Fill only one fire sprinkler system at time. Doing multiple systems at once could lead to longer compressor runtimes and possible damage to equipment. Allow air compressor to cool before beginning again.

7. When the sprinkler system(s) are completely filled, the nitrogen generator will repressurize the air tank and nitrogen tank to capacity. The air compressor will turn off and the unit will automatically return to Nitrogen Generating Mode.

Note: The amber LED labeled "BYPASS" should be off and the "Mode" on the IntelliGen ™ Display will display "N2 Mode".

8. Reset the Leak Rate by pressing the "MAINT" button on the IntelliGen ™ Display Keypad. Enter "0000" for passcode.

9. Move the cursor to "Excess N2 Demand" and press "ENTER".

10. Press "ENTER" on the keypad to clear maintenance alert and reset Leak Rate (LR).

11. You will receive confirmation that the alert has been cleared.

12. Press "ESC" to return to the main screen.

17

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Purging with IntelliPurge

®

Nitrogen Purge Valve (INS-PV):

Fig. 18

Slotted Cam Latch

S2 Toggle Switch

S1 Toggle Switch

N

2

Level % Display

Power LED

Purge LED

Trouble LED

Purge Time Display

Purge Exhaust Port

1. See Manual #5401532 for full details on installing, programming, purging and wiring of the INS-PV.

2. Go to the end of the sprinkler system(s) where the INS-PV(s) is installed. Each riser should have one INS-PV.

3. Check to ensure power is connected to the INS-PV. The green Power LED will be ON.

4. Open the ball valve on the INS-PV.

5. Ensure the INS-PV is installed properly. Installing the valve upside down will cause the unit to not purge. Any trapped water in the piping will also cause the unit to not purge.

6. To check that the INS-PV is allowing air/nitrogen flow, toggle the “MANUAL PURGE” switch ON. This will open the solenoid valves inside the unit.

7. If the sprinkler system is pressurized, listen for flow out of the Purge Exhaust Port on the bottom of the unit. You may also use your fingers to feel for flow. If no flow is present, there is a blockage such as a shut ball valve, water in the pipe, or a clogged orifice upstream.

8. If the INS-PV unit is not connected to a nitrogen generator or an INS-RA, toggle the “START PURGE” switch to start the

Purge Process.

9. Once the Purge Process has started, the yellow Purge LED indicator will begin blinking.

10. The Purge Time Display will display the max number of purge days, which is the maximum amount of time the unit is allowed to purge before indicating a trouble.

11. The N2 Level display will blink indicating that it is taking an initial nitrogen level reading. After five minutes the N2 Level display should read ambient nitrogen levels, between 78-81%.

12. The INS-PV is now purging. The oxygenated air is escaping out of the Purge Exhaust Port.

13. If an IntelliPurge ® Nitrogen Purge Valve (INS-PV) is connected to a nitrogen generator or an INS-PV, the S1 toggle switch will be DISABLED.

14. Return to the nitrogen generator.

15. If an INS-PV is connect to the nitrogen generator, press the “PURGE” button on the IntelliGen ™ Display keypad.

16. Follow all prompts.

17. Once the system reaches 98% the INS-PV automatically closes and your system is purged.

18

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Purging with Potter Nitrogen Purge Valve (NGP-SPV):

Fig. 19

1. See Bulletin #5401520 for full details on installing and purging of the NGP-SPV.

2. Go to the end of the sprinkler system(s) where the NGP-SPV(s) is installed. Each riser should have one NGP-SPV purge valve.

3. Open the ball valve on the NGP-SPV.

4. Ensure the NGP-SPV is installed properly. Installing the valve upside down will cause the unit not to purge. Any trapped water in the piping will also cause the unit not to purge.

5. Unscrew the 1/2" pipe plug located at the end of the NGP-SPV.

6. Check to ensure flow is coming out the purge valve.

7. If the sprinkler system is pressurized, listen for flow. You may also use your fingers to feel for flow. If no flow is present, there is a blockage such as a shut ball valve, water in the pipe, or a clogged orifice upstream.

8. Wait approximately 14 days before returning to the job site and checking the exiting gas with the Portable Nitrogen Analyzer.

9. Check the nitrogen purity to ensure the exiting gas is 98% or greater.

10. If the gas is 98% purity or greater close the ball valve and screw the plug back in. The system is purged.

11. If the nitrogen purity is 85% or greater, wait another 7 days before returning to the site and rechecking. Some larger systems may have longer purge times.

12. If the nitrogen purity is around 80% it indicates that there is a blockage in the sprinkler system piping, the ball valve is closed on the purge valve or that your nitrogen generator is in Bypass Mode.

19

INS-500 & INS-1000 • 5403645 • REV F • 09/19

IntelliView

Dashboard Internet Connectivity

Potter's IntelliGen ™ Controller is designed to provide you with live status updates of your nitrogen generator. The IntelliGen ™

Nitrogen Generator needs to be wired using a CAT-5 Ethernet cable. The Ethernet port is located on the bottom left of the

IntelliGen ™ Controller. When the unit is wired and powered on, data will be accessible at www.PotterIntelliView.com.

Register your nitrogen generator, visit www.PotterIntelliView.com.

1. Log In or Register New User.

2. If you are a new user you will be required to enter your name, company information, and a valid e-mail address.

3. You will receive an e-mail confirmation with an account verification link.

4. Once logged in, click the "Register Generator" button on the Dashboard Overview page.

5. Enter the unit’s MAC ID Number and the Serial Number which can be found on the IntelliGen ™

See Fig. 20.

Controller inside the cabinet.

Fig. 20

Serial Number

MAC ID

6. Add a name for the generator and the building where the generator is located.

7. A window will appear indicating that you have successfully added the nitrogen generator. Click save.

8. The page will refresh with information on the new nitrogen generator.

9. For more information on the Potter IntelliView ™ Dashboard, watch a tutorial at www.potterintelliview.com

.

20

INS-500 & INS-1000 • 5403645 • REV F • 09/19

IntelliPurge

®

Wiring and Networking

1. The PLINK network is Potter’s propriety networking connection. It is a RS-485 network for serial communication between the Nitrogen Generator (INS Series) and its Purge Valves (INS-PV).

2. PLINK requires 3 signal lines to allow communication to and from the Nitrogen Generator and the Purge Valves.

• PL-A

• PL-B

• PL-G

Recommended wire is an unshielded 24 AWG stranded CAT5 equivalent or higher rated network cable.

Fig. 21

PL-A is the blue wire

PL-B is the white/blue wire

PL-G is the orange wire

The other 5 wires are not needed in this application

3. We recommend the unused conductors from the network cable be pulled back and taped against the outer jacket for possible future use.

4. Maximum number of INS-PV devices networked to an IntelliGen Series Nitrogen Generator is 26. The maximum wire length for the network when using the recommended wire is 4000 Ft. Contact technical support for further assistance if a longer wire length is required.

5. The PLINK network works as a Master and Slave network. The INS generator is defined as the Master.

PLINK Wiring Schematic

Fig. 22

Nitrogen

Generator

PL-A (Blue Wire)

PLINK IN

PL-A

INS-PV 2

PLINK OUT

PL-A

PL-A (Blue Wire)

PL-B (White/Blue) PL-B (White/Blue)

PL-B PL-B

PL-G (Orange) PL-G (Orange)

PL-G PL-G

The first INS-PV in the network when connected to the nitrogen generator should be addressed INS-PV-2. The last INS-PV in the network must be addressed as INS-PV-27. If Only ONE INS-PV is networked to the generator it must be addressed as INS-PV-27

21

INS-500 & INS-1000 • 5403645 • REV F • 09/19

1. The INS-PV requires 35 watts of 24V AC/DC power. This must be supplied by a dedicated power supply. An optional

120V (40VA) transformer may have been supplied.

PLINK Wiring Diagram

Fig. 23

PL-G

PL-B

PL-A

PL-G

PL-A

PL-B

To Next

Device

INS-PV 2 INS-PV 3

NOTES:

• Wiring from the INS Series Nitrogen Generator to the INS-PVs is low voltage.

• Do not route INS-PV wiring into the high voltage wire ways.

• Do not run INS-PV communication or power wiring parallel to any high voltage wiring or conduit. Keep as much space from high voltage wiring as possible. Only cross high voltage wiring with INS-PV wiring at right angles.

• Do not coil or store excess cable in the INS-PV Cabinet. Doing so may cause communication errors or faulty readings.

• Use the knockouts below the INS IntelliGen Nitrogen Generator control board to exit the nitrogen cabinet. Keep excess wire to a minimum.

2. Each INS-PV device comes with a Building Management System (BMS) connection that is a NC or NO contact. This can be wired back to a Building Management System or Fire Panel. If connected to a fire panel it should be wired as a Trouble.

22

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Maintenance and Part Replacements

Potter IntelliGen ™ Nitrogen Generators are designed to provide maintenance alerts that ensure the long life of the nitrogen generator. These alerts also ensure that the unit runs at peak efficiency. The IntelliGen ™ Nitrogen Generator has an internal maintenance timer that monitors how long the unit has been operating since it has been serviced. Normal scheduled maintenance should be done every 1,000 compressor operating hours, or during the annual inspection of the unit, whichever comes first.

When the system needs maintenance, the amber maintenance light on the IntelliGen compressor operating hours, the nitrogen generator will show a trouble condition.

™ Display will turn on. If connected to the internet, you will receive an e-mail notification as well. If maintenance on the nitrogen generator is not done within 250

To reset the maintenance timer and get the maintenance alert to reset, go to the IntelliGen ™ Display.

1. Press "MAINT" on the IntelliGen ™ Display keypad.

2. Enter passcode "0000".

3. Select “Std. Maintenance” and press "ENTER".

4. The menu will then display the count down hour log on the Maintenance Timer. Press "ENTER" on the keypad to clear

Maintenance Timer. Press "ENTER" to confirm.

5. The amber Maintenance LED will turn off.

CAUTION

All pressure must be relieved from the entire nitrogen generator system BEFORE servicing. To avoid system damage and/or personal injury, the nitrogen generator should be isolated from the sprinkler system and the generator system fully depressurized before any maintenance or service is performed. All maintenance and troubleshooting activities for the Potter

Nitrogen Generator should be performed by qualified personnel using reasonable care. Before servicing, isolate all risers by closing all Nitrogen Air Maintenance Device valves and relieving all system pressure from the Potter Nitrogen Generator.

Failure to do so could result in serious injury or death. Ensure power is turned off at the electrical disconnect.

Scheduled Maintenance - 1,000 Compressor Operating Hours:

• Replace the activated carbon and coalescing filter elements.

• Clean the air tank blow-down strainer screen.

• Clean or replace the air compressor intake filter elements.

Annual Inspection:

• Check for unusual noise or vibration.

• Clean all external parts of the compressor and motor.

• Manually test safety relief valves.

• Inspect system for leaks.

• Tighten fittings, nuts and screws as required.

• Check the pressure settings.

• Check the nitrogen purity using Portable Nitrogen Analyzer. It should be 98.0% or greater.

Maintenance and Replacement Parts:

Part Number

0090206

1119504

1119589

1119590

1119662

1119599

1119600

1119625

1119805

Description

KIT-FILTER ELEMENT REPLACEMENT INS-500/1000

PORTABLE NITROGEN ANALYZER

MEMBRANE SEPARATOR-INS 500

MEMBRANE SEPARATOR-INS 1000/1500

FILTER-GAST 1HP/2HP COMPRESSOR INTAKE ELEMENT (1 PER CYLINDER=2 REQD F/INS-500, 4 REQD F/INS-1000)

COMPRESSOR-2 HP, 230VAC 1PH 60HZ (INS-1000)

COMPRESSOR-2 HP, 230VAC/460VAC 3PH 60HZ (INS-1000)

COMPRESSOR-1 HP, 115VAC/230VAC 1PH 60HZ (INS-500)

PRESSURE SWITCH-INS

23

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Standard Maintenance (Every 1,000 Compressor Operating Hours)

Tools Needed:

• 13/16” wrench • Potter Filter Elements Kit (#0090206)

• Channel Lock • Potter Air Intake Elements Kit (#1119662)

• Rag

Drain all pressure from the nitrogen generator before proceeding and turn off power to unit at the contractor installed electrical disconnect.

1. Power off the air compressor using the Air Compressor Power Switch located on the right side of the cabinet.

2. Power off the nitrogen generator using the customer installed electrical disconnect.

3. Isolate the nitrogen generator from the sprinkler system by closing the N

2 tank. See Fig. 24.

Fig. 24

Tank Outlet Valve (V03) located on the nitrogen

V03

To Fire Sprinkler

System

4. Open the blue N

2

Bleed Valve (V04) located near the Nitrogen Sample Port (SP) and begin draining pressure from the nitrogen tank. See Fig. 25.

Fig. 25

V04

5. Open the black handled valve located on the Activated Carbon Filter (F04) and begin draining pressure from the air tank. See

Fig. 26.

Fig. 26

24

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Compressor Air Intake Filters:

6. When the pressure has been drained from the nitrogen generator clean or replace the air intake filter elements.

7. Go to the air compressor located on the top of the nitrogen tank. Locate the black filter enclosures. There will be two (2) on the INS-500 and four (4) on the INS-1000. See Fig. 27.

Fig. 27

8. Twist filter cover CCW to access filter. See Fig. 28.

Fig. 28

Air Intake

Element

9. Replace the air intake element.

10. Return the air intake element to the enclosure and reattach cover. Repeat for all air intake filters.

Air Tank Blow-Down Strainer Screen:

11. Locate the inline blow-down strainer on the bottom right side of the air tank. Using a channel lock loosen the strainer screen cap. See Fig. 29.

Fig. 29

25

INS-500 & INS-1000 • 5403645 • REV F • 09/19

12. Remove the screen and clean all debris. Wipe the inside of the strainer with a rag.

13. Reinstall the screen into the strainer.

14. Retighten the strainer screen cap.

Filter Elements:

15. Locate the four (4) filters on the inside of the nitrogen generator cabinet. See Fig. 30.

Fig. 30

F04 F03 F02 F01

16. Disconnect the drain tubes from the filter bowl by pushing up on the plastic releasing collar and pulling down on the tube.

See Fig. 31.

Fig. 31

Releasing Collar

26

INS-500 & INS-1000 • 5403645 • REV F • 09/19

17. Using a 13/16” wrench loosen the filter bowl from the filter body. See Fig. 32.

Fig. 32

CAREFULLY

WRENCH HERE

ONLY

DO NOT PLACE

WRENCH HERE

CAUTION

It is extremely important that you only unscrew the drain bowl from the filter body. The float adjustments at the bottom must remain in auto. Manual (man) will cause the floats to remain open and air to leak. If you accidently loosen the float adjustment, simply retighten with your hand. See Fig. 33.

Fig. 33 man

18. After the filter bowl is separated from the filter body, remove the filter element by gently pulling down. See Fig. 34.

Fig. 34 Filter Body

Filter Element auto

Filter Bowl

19. Replace the filter element with the correct filter element from the replacement kit (#0090206). See Fig. 35: a. The filter body (#5230003) all the way to the right is the 5 micron filter which has a GREEN element (#5230012).

b. The filter body (#5230004) second from the right is the 1 micron filter which has a RED element (#5230013).

c. The filter body (#5230005) third from the right is the 0.01 micron filter which has a BLUE element (#5230014).

d. The filter body (#5230006) on the far left is the activated carbon filter which has a BLACK element (#5230015).

Note: This filter bowl is not connected to the drain and has a black handled valve.

Fig. 35

RED (b)

GREEN (a)

BLACK (d)

BLUE (c)

27

INS-500 & INS-1000 • 5403645 • REV F • 09/19

20. Remove old O-rings and replace with the O-rings in the filter element kit.

21. Clear filter bowls of debris.

22. Screw the filter bowl back into the filter body. Use a 13/16” wrench to tighten the correct wrenching flats. Be careful to not over tighten or you may crack the filter body. Repeat for all filters.

23. Close the black handled ball valve on the Activated Carbon Filter (F04) and the blue N

2

Bleed Valve (V04).

Resetting Maintenance Alert and Checking for Leaks:

24. Turn power on to the unit using the electrical disconnect.

25. To reset the maintenance timer and get the maintenance alert or maintenance trouble to reset, go to the IntelliGen ™ Display.

26. Press "MAINT" on the IntelliGen ™ Display keypad.

27. Enter passcode "0000"

28. Select “Std. Maintenance” press "ENTER".

29. The menu will display maintenance timer countdown hours.

30. To reset the maintenance timer press "ENTER". Press "ENTER" again to confirm.

31. The maintenance light on the IntelliGen ™ Display will turn off and the maintenance timer has been reset.

32. Turn power back on to the air compressor using the Air Compressor Switch located on the right of the cabinet. The amber

"BYPASS" LED will be ON since there is no pressure in the tanks.

33. If the nitrogen generator is isolated from the sprinkler system: a. The air compressor of the INS-500 should take no longer than 8 minutes to pressurize the two tanks and turn off.

b. The air compressor of the INS-1000 should take no longer than 6 minutes to pressurize the two tanks and turn off.

34. The amber "BYPASS" LED should turn off.

35. If the air compressor is not turning off or it is taking longer than expected, it could indicate a leak.

36. Allow the system to hold pressure for several minutes. Check all piping connections for leaks. Any drop in pressure on the nitrogen tank or air tank during this time could indicate a leak.

37. If there is a drop in pressure, soap all filters and blow-down strainer.

28

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Air Compressor Replacement

1. Isolate the nitrogen generator from the sprinkler system and relieve pressure.

2. Disconnect the power to the nitrogen generator using lockout-tagout procedure.

3. Disconnect wires in junction box on the air compressor.

4. Loosen flex hose and fittings on compressor discharge.

5. Remove flex hose from compressor discharge.

6. Remove conduit fittings from junction box.

7. Remove bolts holding compressor to tank.

8. Install new air compressor. Torque bolts to 20 ft/lbs.

9. Verify wiring in motor junction box corresponds to the input voltage.

10. Turn power back on to the generator. If Three Phase model, verify correct rotation.

11. Check for leaks.

Nitrogen Membrane Replacement

1. Isolate the nitrogen generator from the sprinkler system and relieve pressure.

2. Disconnect the power to the nitrogen generator using lockout-tagout procedure.

3. Remove the top tube to the nitrogen membrane.

4. Remove the bottom tube to the nitrogen membrane.

5. Loosen the clamps holding the nitrogen membrane in place.

6. Remove push to connect fittings on old membrane and reinstall on new membrane.

7. Replace the old nitrogen membrane with the new nitrogen membrane. Check to ensure inlet and outlet on the membrane are in correct orientation.

8. Tighten the clamps down.

9. Reattach both the top and bottom tube to the nitrogen membrane.

10. Turn on power to the nitrogen generator.

11. Retest nitrogen purity.

29

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Maintenance Alerts and Actions

A maintenance alert is noncritical to the operation of the nitrogen generator. The maintenance light will turn on and a maintenance alert will appear on the IntelliGen ™ Display and IntelliView ™ website, and an e-mail will also be sent. The Trouble Horn will not sound and the BMS will not trip. Maintenance alerts can be cleared by performing maintenance on the issue then going into the

"Maintenance Menu" and clearing the appropriate alert.

Maintenance Alert #1 - Standard Maintenance

Issue: Maintenance Timer expired after 1,000 hours and the nitrogen generator needs maintenance.

Action:

1. Within 250 compressor operating hours, complete standard maintenance following the procedure in this manual.

2. Reset Maintenance Alert #1 by going into the Maintenance Menu on the display and following the procedure on page 23.

Maintenance Alert #2 - Excess Nitrogen Demand (Sprinkler System Leak Rate Excessive)

Issue: Sprinkler system leak rate is greater than Leak Rate Warning Set Point. You have one week to address this before it turns into a trouble alert.

Action:

1. Leak check nitrogen generator and sprinkler system. Repair leaks if found.

2. Adjust Leak Rate Warning Set Point. See page 36 for details.

Note: Increased leak rates can cause excessive maintenance and damage to equipment.

3. Reset the Maintenance Alert #2 by going into the Maintenance Menu on the display.

30

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Trouble Alerts and Probable Causes

A trouble alert is a critical alert to the operation of the nitrogen generator. The trouble light will turn on and a trouble alert will be created on the IntelliGen ™ Display and IntelliView ™ website, an e-mail will also be sent. The Trouble Horn will sound and the BMS will trip. Trouble Alerts can be cleared by fixing the issue and pressing “CLEAR” on the display keypad, and entering passcode "0000".

Trouble Alert #1 - Nitrogen Generator in Bypass Mode for 2 hours

Issue: Bypass Solenoid Valve continuously ON for 2 hours.

Probable Cause:

1. Air compressor power is turned off.

2. Air Tank Outlet Valve (V01) is closed.

3. Filling multiple sprinkler systems at one time.

4. Leak on nitrogen generator air tank or sprinkler system.

5. Blockage in pathway from air tank to nitrogen tank.

Trouble Alert #2 - Air Compressor is Continuously Running

Issue: Air tank pressure switch continuously ON for 90 minutes.

Probable Cause:

1. Filling multiple sprinkler systems at one time.

2. Major leak on nitrogen generator (air side).

a. Air Tank Blow-Down (AD01) stuck open.

b. Float valve on filters stuck open.

3. Leak on sprinkler system.

4. Pressure Switch (PS01) needs to be adjusted or replaced.

5. Air compressor not building adequate pressure.

6. Compressor unloader valve located on Pressure Switch (PS01) is stuck open.

Trouble Alert #3 - Excessive Air Compressor Cycling

Issue: Air tank pressure switch turns ON 10 times in 1 hours.

Probable Cause:

1. Leak on nitrogen generator air tank. Check valve sticking open could cause the leak.

2. Float valve on filters could be stuck open.

3. Excess Air Regulator (PRV01) closed.

4. Pressure Switch (PS01) needs to be adjusted or replaced.

5. Filter elements need to be replaced.

6. Membrane Inlet Air Solenoid (XV01) is stuck open.

Trouble Alert #4 - Excessive Membrane Runtime

Issue: Membrane Inlet Air Solenoid (XV01) and Membrane Outlet N

2

Solenoid (XV02) continuously ON for 30 minutes.

Probable Cause:

1. Leak on nitrogen generator or sprinkler system.

2. Air Compressor Power is turned off.

3. Air Tank Outlet Valve (V01) closed.

4. Membrane Inlet Air Solenoid (XV01) and/or Membrane Outlet N

2

Solenoid (XV02) are blocked, or closed.

5. Instrument Air Regulator (PRV03) is less than 60 PSI.

6. Blockage in pathway from air tank to nitrogen tank.

31

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Trouble Alert #5 - Excessive Membrane Cycling

Issue: Nitrogen valves turn ON 16 (INS-500) or 24 (INS-1000) times in 4 hours.

Probable Cause:

1. Leak on sprinkler system.

2. Leak on nitrogen tank.

3. Pressure settings need to be adjusted or pressure transducer replaced.

4. Membrane Outlet N

2

Solenoid (XV02) is stuck open.

Trouble Alert #6 - Nitrogen Generator Cannot Keep Up While in Nitrogen Generating Mode

Issue: Bypass Solenoid cycles 16 times over 4 hours.

Probable Cause:

1. Filling multiple sprinkler systems.

2. Performing functionality testing on the nitrogen generator.

3. Leak on nitrogen generator or sprinkler system.

Trouble Alert #7 - Excess Nitrogen Demand (Sprinkler System Leak Rate Excessive)

Issue: Sprinkler system leak rate is greater than Leak Rate Warning Set Point and has not been acknowledged for a week.

Probable Cause:

1. Leak on sprinkler system.

2. Leak on nitrogen tank.

3. Leak Rate Warning Set Point not appropriate for application.

Trouble Alert #8 - Max. Temperature Limit Reached

Issue: Internal cabinet temperature reached max. limit.

Probable Cause:

1. Cooling fan failure.

Trouble Alert #9 - Maintenance

Issue: Compressor Maintenance Timer expires when maintenance request has not been reset in 250 hours.

Probable Cause:

1. Standard maintenance was not completed.

2. Maintenance timer not reset.

Trouble Alert #10 - Hardware Failure Detected

Issue: IntelliGen ™ Controller failure detected.

Probable Cause:

1. Short circuit on output wiring.

Trouble Alert #11 - PLINK Connection Error

Issue: Devices cannot communicate.

Probable Cause:

1. Wiring not correct.

2. Power failure.

32

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Trouble Alert #12 - PLINK Device Trouble

Issue: One or more PLINK devices are reporting trouble.

Probable Cause:

1. An INS-PV connected to the generator has an error.

2. See INS-PV Manual #5401532.

Troubleshooting

Leak on Sprinkler System or Nitrogen Generator

1. View the Leak Rate (LR) by exiting to the main menu of the IntelliGen ™ Display. It will be displayed as LR: # PSI/24HR.

2. If the Leak Rate (LR) is greater than 6 PSI/24HR; there is an excessive leak.

3. Isolate the nitrogen generator from the sprinkler system using the N

2

Tank Outlet Valve (V03).

4. Allow the nitrogen generator to fill the nitrogen and air tanks.

5. Once the air compressor turns off allow the nitrogen generator to sit for 30 minutes.

6. If pressure drops in the air tank or nitrogen tank that indicates there is a leak on the nitrogen generator.

7. Soap all fittings and tighten fittings that are leaking. Avoid electronics.

8. If pressure does not drop, this indicates the leak is outside of the nitrogen generator. Check all piping downstream of the N

2

Tank Outlet Valve (V03). Fix leaks as needed.

9. Clear the trouble using the “CLEAR” button on the IntelliGen ™ Display and enter passcode "0000".

Testing Nitrogen Flow Rate and Nitrogen Purity

1. Isolate the nitrogen generator from the sprinkler system using the N

2 nitrogen generator to fill the air tank and nitrogen tank.

Tank Outlet Valve (V03) on the nitrogen tank. Allow the

2. When the nitrogen tank pressure reaches approximately 80 PSI the red instrument air solenoid lights located inside the cabinet should turn off.

3. To ensure the nitrogen generator is operating correctly and that the correct nitrogen purity is being produced a functional test must be performed.

4. On the inside of the nitrogen cabinet, locate the blue N

2

Bleed Valve (V04) near the Nitrogen Sample Port (SP).

5. Slightly open the blue N

2

Bleed Valve (V04) and begin draining the pressure out of the nitrogen tank.

6. Quickly close the blue N

2 approximately 60 PSI.

Bleed Valve (V04) when you see the red instrument air solenoid lights turn on. This will happen at

Note: If the pressure in the nitrogen tank drops below 55 PSI the nitrogen generator will return to Bypass Mode. Wait for the nitrogen generator to refill the tanks and the unit to return to Nitrogen Generating Mode before trying again.

7. Begin timing to see how long it takes to reach approximately 80 PSI in the nitrogen tank.

8. If the nitrogen generator is isolated from the sprinkler system: a. The INS-500 should take no longer than 8 minutes to pressurize the nitrogen tank to 80 PSI.

b. The INS-1000 should take no longer than 4 minutes to pressurize the nitrogen tank to 80 PSI.

9. During this time, connect the Portable Nitrogen Analyzer to the Nitrogen Sample Port (SP) to measure the purity of the exiting gas. The analyzer should read 98.0% or greater. This may take a few minutes.

10. When the nitrogen generator reaches approximately 80 psi in the nitrogen tank, the red instrument air solenoid lights will turn off. The air compressor will continue to run until the air tank pressure reaches approximately 105 PSI.

11. Allow the nitrogen generator to sit for 30 minutes.

12. If pressure drops in either tank this indicates there is a leak in the nitrogen generator. Soap all pre-plumbed fittings and tighten any fittings that are leaking. Avoid electronics.

13. If the pressure does not drop, this indicates the leak is outside of the nitrogen generator. Check sprinkler system for leaks.

33

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Normal Operating Parameters of the INS-500 and the INS-1000

The Potter IntelliGen ™ Nitrogen Generators use a two tank system design to deliver high purity nitrogen to the fire protection system. The pressure switch on the air tank controls the air compressor by turning it on and off at the desired pressure set points.

A pressure transducer on the nitrogen tank controls the pneumatic valves on the inside of the cabinet. Whenever the nitrogen tank requires nitrogen, the pneumatic valves open allowing air to flow from the air tank. When the nitrogen tank reaches the desired set point the pneumatic valves close.

• Periodic running of the air compressor is expected (typically less than 24 times a day).

INS-500 INS-1000 Recorded Parameter

Air Compressor

OFF Pressure*

105 PSI 105 PSI

Air Compressor

ON Pressure*

85 PSI 85 PSI

Nitrogen Tank

OFF Pressure*

80 PSI 80 PSI

Nitrogen Tank

ON Pressure*

60 PSI

Max time interval to build pressure from 60 PSI to 80

PSI in nitrogen tank in Nitrogen

Generating Mode

8 minutes

* Pressures are approximated and can vary ±3 PSI.

60 PSI

4 minutes

34

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Nitrogen Generator Leak Detection System

Each Potter IntelliGen ™ Nitrogen Generator comes with an integrated Leak Detection System. The Leak Detection System uses pressure decays to calculate the actual pressure loss in 24 hours, or the Leak Rate of the sprinkler system.

This Leak Rate is displayed on the IntelliGen ™ Display as “LR # PSI/24HR”. # is the number in PSI that is calculated.

Increases in the Leak Rate can cause excessive demand on the nitrogen generator. Excessive demand causes increased runtimes on the unit. Increased runtimes increase the frequency of maintenance and repairs. In some cases, excessive Leak Rates can cause catastrophic failures.

The Leak Detection System is designed as a rolling average over 1 week to ensure the presence of an actual leak. To reset the LR number, reset the Maintenance Alert #2 under maintenance on the IntelliGen ™ display.

All Potter IntelliGen ™ Nitrogen Systems are designed to run approximately 1,000 operating hours in a typical year.

This translates to a maximum pressure loss of 6 PSI in 24 hours. This is the default Leak Rate Warning Set Point. If the actual

Leak Rate of the sprinkler system is greater than that value, a maintenance alert or a trouble will display on the nitrogen generator.

The Leak Rate Warning Set Point in the Potter IntelliGen ™ Nitrogen Generator is a user adjustable set point for when a maintenance or trouble alert is activated. It will give a preemptive warning that the system Leak Rates have increased above the acceptable level.

This Leak Rate Warning Set Point can be set from 1 PSI up to 36 PSI per 24 hours.

• NFPA 13 allows a leak rate of 1.5 PSI loss per 24 hours for new systems.

• NFPA 25 allows a leak rate of 36 PSI loss per 24 hours for existing systems.

Increases in Leak Rates will cause more maintenance and possible failures.

Example: At a 6 PSI loss per 24 hour leak rate, the unit will run approximately 1,000 hours per year. At a 36 PSI loss per 24 hour leak rate, the unit will run approximately 6,000 hours per year. That means, at a 6 PSI leak rate, the air compressor will be operating 11% of the year, compared to a 36 PSI leak rate, where the air compressor will be operating 70% of the year.

35

INS-500 & INS-1000 • 5403645 • REV F • 09/19

To Change the Leak Rate Warning Set Point:

1. Press "ENTER" on the IntelliGen ™ Display keypad.

2. Select "Settings" using the keypad.

3. Enter passcode "0000".

4. Select "Leak Rate". Press "ENTER".

5. Press "ENTER" to choose settings.

6. Select "Leak Rate Warning". Press "ENTER".

7. Using the directional arrows, adjust the leak rate limit number "--" PSI per 24 hours.

a. NFPA allows 1.5 PSI per 24 hours on new systems.

b. Potter Nitrogen Generators are designed for 6 PSI per 24 hours.

8. Press "ENTER" to confirm.

9. Press "ENTER" to acknowledge warning.

10. Press "ENTER" to accept change.

11. Press "ESC" to return to main menu.

The Leak Rate is also calculated based on the size of the sprinkler system the nitrogen generator is protecting. The INS-500 is factory set at 1,850 gallons (max) and the INS-1000 is factory set at 3,400 gallons (max). This can be adjusted lower if the units are servicing smaller systems.

To Change the Sprinkler System Size:

1. Press "ENTER" on the IntelliGen ™ Display keypad.

2. Select "Settings" using the keypad. Press "ENTER".

3. Enter passcode "0000".

4. Select "Leak Rate". Press "ENTER".

5. Press "ENTER" to choose settings.

6. Select "Sprinkler Capacity". Press "ENTER".

7. Using the numeric pad, enter the total system volume size in gallons.

8. Press "ENTER".

9. Press "ESC" to return to main menu.

36

INS-500 & INS-1000 • 5403645 • REV F • 09/19

INS-500/1000 Dimensional Drawings

DRAIN CONNECTION

37

INS-500 & INS-1000 • 5403645 • REV F • 09/19

38

XV03 FC

XV01 FC

INS-500 & INS-1000 • 5403645 • REV F • 09/19

B

A

-

+

A

B

+

-

G22

AWG22

AWG22

AWG22

N

AW

RED

BLACK

GREE

WHITE

AWG12

AWG12

G12 AW WHITE

AWG12

N GREE

N GREE

BLACK

AWG12

AWG12

G12 AW BLUE

N GREE

BLACK

F1

SB 0A 250VAC2

GND

GND

L

N

AWG12 BLACK

AWG18

BLACK

AWG18

RED

AWG12

AWG12

AWG12

G12

G12

G12

AW

D AW

AW

AWG12 RED

WHITE

WHITE

BLUE

ORANGE

BLACK

BLACK

AWG12

BLACK TB1

A1

A2

O

5L3

13N

3L2

1L1

AWG12

O

2T1

4T2

6T3

14N

BROWN

AWG18

AWG18

C

NC

NO

N

AWG18

BLACK

GREE

RED

1

2

3

BMS-

BMS-

BMS-

PL-A

PL-B

PL-G

AWG22

G22

G18 AW

AWG18

AWG22

AWG22

AW

N

BLACK

BLACK

WHITE

WHITE

GREE

RED

6

5

4

3

2

1

AWG18

G18

AWG18

AWG18

G18 AW

G18 AW

LOW

BLUE

BROWN

GREY

YEL

ORANGE

AW WHITE

5

4

6

3

2

1

AWG12

G12 AW

AWG12

AWG12

WHITE

BLACK

ORANGE

RED

PL-G

PL-B

PL-A

BMS-C

BMS-NC

BMS-NO

RED

BLACK

RED

BLACK

BLACK

RK

BLUE

BROWN

BLUE

BROWN

8

7

9

6

5

2

1

4

3

10

BLK/wMA

2

3

1

K

RED

WHITE

BLAC

R MOTO

GND

LINE R

LE ENAB

SWITCH

MOTO LINE

AWG12

AWG12

G12 AW

N

WHITE

BLACK

GREE

39

INS-500 & INS-1000 • 5403645 • REV F • 09/19

B

A

-

+

+

-

A

B

G22

AWG22

AWG22

AWG22

N

AW

RED

BLACK

GREE

WHITE

AWG12

AWG12

AWG12

AWG12

N GREE

N GREE

BLACK

RED

F2

F1

E3 NOT

E3 NOT SEE

SEE

L1

GND

GND

L2

AWG12

AWG12 N GREE

G12 AW BLUE

BLACK

AWG12

AWG12 RED

BLACK

AWG18

BLACK

AWG18

RED

AWG12

AWG12

AWG12

AWG12

AWG12

G12 AW

AWG12

AWG12

RED

RED

BLUE

BROWN

ORANGE

BLACK

BLACK

BLACK TB1

A1

A2

O 13N

3L2

1L1

5L3

AWG12

O

6T3

14N

4T2

2T1

BROWN

AWG18

AWG18

AWG18

BLACK

N

S-NO

S-NC

GREE

RED

3

2

1

S-C

PL-

PL-

PL-

BM

BM

BM

A

B

G

AWG22

G22

G18 AW

AWG18

AWG22

AWG22

AW

N

BLACK

BLACK

WHITE

WHITE

GREE

RED

4

3

2

1

6

5

AWG18

G18

G18 AW

G18

AWG18

AW

AWG18

LOW

BLUE

BROWN

GREY

YEL

ORANGE

AW WHITE

5

4

6

3

2

1

AWG12

AWG12

AWG12

AWG12 RED

ORANGE

BLACK

BROWN

PL-G

PL-B

PL-A

BMS-C

BMS-NC

BMS-NO

RK

E BLU

BROWN

BLUE

BLACK

RED

BLACK

RED

BLACK

BROWN

7

6

8

9

4

3

5

2

1

10

BLK/wMA

2

1

3 K

RED

BLAC

WHITE

R MOTO

GND

LINE R

LE ENAB

SWITCH

MOTO LINE

AWG12

AWG12

AWG12

N

RED

BLACK

GREE

40

INS-500 & INS-1000 • 5403645 • REV F • 09/19

B

A

-

+

A

B

+

-

G22

AWG22

AWG22

AWG22

N

AW

RED

BLACK

GREE

WHITE

AWG12

AWG12

AWG12

G12 AW E BLU

BLACK

AWG12

N

N GREE

GREE

RED

F1

F2

F3

AWG12

AWG12 N

G12 AW E BLU

GREE

BLACK

AWG12

AWG12

AWG12

AWG12

AWG12

AWG12

G12

G12

AW

AW

E

E

BLU

BLU

ORANGE

BLACK

BLACK

RED

RED

BLACK TB1

A1

A2

O

5L3

13N

3L2

1L1

SB

GND

GND

L2

L1

L3

SB

SB

0A

0A

0A C2

250VAC2

250VAC2

250VA

G12 AW BLUE

AWG12 BLACK

AWG12 RED

AWG12

O

4T2

6T3

14N

2T1

BROWN

AWG18

BLACK

AWG18

RED

AWG18

AWG18

C

NC

NO

N

AWG18

BLACK

GREE

RED

1

2

3

BMS-

BMS-

BMS-

PL-A

PL-B

PL-G

AWG18

AWG22

AWG22

G18

G22

AWG22

AW

BLACK

BLACK

AW

N

WHITE

WHITE

GREE

RED

6

5

4

3

2

1

AWG18

G18

AWG18

AWG18

G18 AW

G18 AW

LOW

BLUE

BROWN

GREY

YEL

ORANGE

AW WHITE

5

4

6

3

2

1

INTELLIGEN CO

PL-B

PL-A

PL-G

BMS-C

BMS-NC

BMS-NO

E

RED

BLACK

BLACK

RED

RK

BLACK

BLU

BROWN

BLUE

BROWN

8

7

6

5

4

3

2

1

9

10

BLK/wMA

2

3

1

K

RED

WHITE

BLAC

G12 AW

AWG12

BLUE

AWG12 BLACK

ORANGE

AWG12 RED

R MOTO

GND

LINE R

LE ENAB

SWITCH

MOTO LINE

AWG12

G12 AW

AWG12

AWG12

N

RED

BLUE

BLACK

GREE

41

A

B

+

INS-500 & INS-1000 • 5403645 • REV F • 09/19

5

4

3

6

2

1

3

2

1

5

4

3

6

1

2

8

7

9

6

5

3

2

1

4

10

2

3

1

42

Menu Trees

1. Menu Tree 1

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Title Screen

Model Number

Status: ## Mode: ##

N2 Tank: ## Leak Rate (LR): ##

1) System Status 2) View History 3) Maintenance 4) Purge 5) Settings

Menu Tree 2 Menu Tree 3 User PW

Menu Tree 4

User PW User PW

Menu Tree 5 Menu Tree 7

43

2. Menu Tree 2

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Main Menu

1) System Status

Screen

1) Generator Status

Compressor: Total Run Time: ## Average Cycle Time: ##

Press [ENTER] for Viewable Parameters

Viewable Parameters

1) Trouble Status

2) Maintenance Status

3) Compressor Run Time

4) Membrane Run Time

2) Purge Status

Device Number: ## N2 Level: ## Days Remaining: ##

Purge Mode: ## Purge Status: ##

Press [ENTER] for Viewable Parameters

Viewable Parameters

1) Trouble Status

2) Sensor Status

Trouble Status

Error Code

Description

List for only troubled units

Maintenance Status

Maintenance Code

Description

List for only troubled units

Compressor or Membrane Runtime

Average On Time: ## Average Cycle Time: ##

State: ON/OFF

Total Membrane Cycles: ##

Trouble Status

Device Number: ## Error Code: ##

Error Description: ##

List for only troubled units

Sensor Status

Device Address: ##

Sensor Status: ##

Listed for all units

44

3. Menu Tree 3

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Main Menu

2) View History

History

1) Generator History

2) INS-PV History

Generator

History:

Scrollable list of all history from

N2 generator

INS-PV History:

Scrollable list of connected

INS-PV devices

INS-PV:

Scrollable list of all history from

INS-PV devices

45

4. Menu Tree 4

1) Standard

Nitrogen

Maintenance

Maintenance Timer: ##

Reset Maintenance Timer

[ENTER]

Reset Maintenance Timer

Press Enter to Clear Maintenance Alert

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Main Menu

3) Maintenance

2) Excessive

Nitrogen Demand

Excessive Nitrogen Demand:

Clear Maintenance Alert [ENTER]

46

5. Menu Tree 5

1) Start Purge

Purge Start

1) All Devices

2) Specify INS-PV

INS-500 & INS-1000 • 5403645 • REV F • 09/19

Main Menu

4) Purge

2) Cancel Purge

Cancel Purge

1) All Units

2) Specify INS-PV

3) Settings

Settings

1) Purge Settings

2) Manual Purge

3) Refresh N2 Lvl %

Purge Settings

1) All Units

2) Specify INS-PV

3) Purge Scheduling

4) Reset Defaults

Manual Purge

1) All Units

2) Specify INS-PV

Refresh N2 %

1) All Units

2) Specify INS-PV

Menu Tree 6

47

INS-500 & INS-1000 • 5403645 • REV F • 09/19

6. Menu Tree 6

1) Purge Settings

Purge Settings

1) Set All Units

2) Set Individual INS-PV

3) Purge Scheduling

4) Restore Factory Default

Restore Factory Default

1) All Units

2) Individual INS-PV

Set All Units

1) Perfect Purge

2) IntelliDry

3) Single Shot

Set Individual INS-PV

N2 Level: ##.#%

Mode:

Fault: ## Days

Press Enter to Edit Parameters

Perfect Purge

1) 14 days

2) 21 days

3) 30 days

IntelliDry

1) 14 days

2) 21 days

3) 30 days

IntelliDry

Dryness

1) Low Dry

2) Medium Dry

3) Heavy Dry

Single Shot

Operation

1) 14 days open, then close

2) 21 days open, then close

3) 30 days open, then close

4) Indefinitely open

Perfect Purge

1) 14 days

2) 21 days

3) 30 days

Pressing Enter -> Gives Warning Message that the Device will cancel existing purge cycles on affected devices before saving parameters

Esc -> Exit without saving parameters

Set INS-PV-1

1) Perfect Purge

2) IntelliDry

3) Single Shot

IntelliDry

1) 14 days

2) 21 days

3) 30 days

IntelliDry

Dryness

1) Low Dry

2) Medium Dry

3) Heavy Dry

Single Shot

Operation

1) 14 days open, then close

2) 21 days open, then close

3) 30 days open, then close

4) Indefinitely open

Purge Scheduling Settings

1) Number of Allowable

Purge Valves (Only used by Master)

Maximum number of INS-PV purging at one time: 05

Press Enter to Edit

Parameter

48

INS-500 & INS-1000 • 5403645 • REV F • 09/19

7. Menu Tree 7

Main Menu 5) Settings

Network

1) View IP Settings

2) Learn Network

View IP Settings

Host Name: ##

MAC ID: ##

Subnet Mask: ##

IP Address: ##

Speed: ##

Default Gateway: ##

DNS_Server: ##

Date/Time

1) Set Date/Time

2) Sync Date/Time

Learn Network

Searches for New Devices on the Network

1) Network

2) Date/Time

3) Leak Rate

4) Blow Down

5) BMS Test

6) Admin.

Leak Rate Screen

Leak Rate: ##

Leak Rate Warning Set Point: ##

Press [ENTER] to Edit

Parameters

Air Tank Blow Down

1) Change Settings

2) Test Blow Down

1) Set Leak Rate

Warning Set Point

2) Set Total Sprinkler

System Capacity

BMS Test

BMS Relay Test

Relay will Energize for 30 Seconds

Admin

Firmware

Version

Number

Set Leak Rate Warning Set Point Screen

### PSI per 24 hours

Set Total Sprinkler System Capacity

Volume: #### Gallons

Change Settings

Set Air Tank Blow

Down Limits

Test Blow Down

Activates Air Blow

Down for 2 seconds

49