Smartgen CMM365-2G is a cloud monitoring communication module that enables real-time monitoring of generator set status and searching of running records via mobile app or PC. It connects to the generator controller via RS485 or LINK port and transmits data via GPRS wireless network to the cloud server. The module also supports SMS functions for controlling the generator and sending alarm messages. With wide power supply range and easy installation, CMM365-2G is an ideal solution for remote monitoring of generators.
advertisement
CMM365-2G
CLOUD MONITORING COMMUNICATION MODULE
USER MANUAL
SMARTGEN (ZHENGZHOU) TECHNOLOGY CO., LTD.
CMM365-2G Cloud Monitoring Communication Module User Manual
CONTENT
CMM365-2G Cloud Monitoring Communication Module 2017-07-31 Version 1.1 Page 2 of 19
CMM365-2G Cloud Monitoring Communication Module User Manual
Chinese trademark
English trademark
SmartGen — make your generator smart
SmartGen Technology Co., Ltd.
No.28 Jinsuo Road
Zhengzhou
Henan Province
P. R. China
Tel: 0086-371-67988888/67981888
0086-371-67991553/67992951
0086-371-67981000(overseas)
Fax: 0086-371-67992952
Web: http://www.smartgen.com.cn
http://www.smartgen.cn
Email: [email protected]
All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder.
Applications for the copyright holder’s written permission to reproduce any part of this publication should be addressed to Smartgen Technology at the address above.
Any reference to trademarked product names used within this publication is owned by their respective companies.
SmartGen Technology reserves the right to change the contents of this document without prior notice.
Software Version
Date
2016-11-14
Version
1.0
2017-07-31 1.1
Original release.
Note
Modified the wire connection on the mask, and changed rated pictures.
CMM365-2G Cloud Monitoring Communication Module 2017-07-31 Version 1.1 Page 3 of 19
CMM365-2G Cloud Monitoring Communication Module User Manual
1 OVERVIEW
CMM366-2G Cloud Monitoring Communication Module is GPRS wireless network communication protocol switch module which can achieve genset (with SCI) connect to Internet. The module gains genset data via RS485 port, USB port, or LINK port of genset controller modules of international first-class brands including SmartGen, DeepSea, ComAp, etc. Then the module transmits the data to corresponding cloud server via GPRS wireless network for achieving user’s real-time monitoring to running status and searching of running records via APP (IOS or Android) and PC terminal devices.
CMM366-2G module has already integrated protocols of mainstream genset control module. It not only can achieve genset monitoring but also can insert some digital alarm input/output signal to achieve monitoring of generator room entrance guard, guard against theft and fire facilities.
This module has master and slave RS485 ports, in which master RS485 port connects with genset controllers and slave RS485 port connects with dynamic environment monitoring system.
2 PERFORMANCE AND CHARACTERISTICS
1) Connect to cloud server via GPRS wireless network , one to one monitoring;
2) With two kinds of ports for communication with genset control module: RS485 and LINK; can monitor great majority genset control modules of international first-class brands;
3) Widely power supply: DC (8~35)V, can direct use genset build-in battery;
4) With ARM-based 32-bit SCM, high integration of hardware and strong programming ability;
5) Include with GPS locate function to achieve gain location information and locate genset;
6) Take JSON network data communication protocol, upload real-time data variation and take compression algorithm to vastly reduce network flow at the same time;
7) Users can set up history data upload rest to upload monitoring data to server (history data can be analyzed);
8) When alarm occurs it can upload data to server immediately;
9) 2 auxiliary digital input ports which can receive external alarm signal;
10) 1 auxiliary relay output ports which can output various of alarm signal;
11) Master and slave RS485 ports; master RS485 port connects with genset controllers and slave
RS485 port connects with dynamic environment monitoring system.
12) With SMS functions to control genset. All the alarm signals of genset can be sent to 5 preset telephone numbers as short massages, and users also can check genset status via SMS function.(only suit for HGM7000 series and HGM9000series controllers of SartGen)
13) Power and multiple communication status indicators on front panel that working status is clear at a glance;
14) Lamp test function;
15) Parameter adjust function: users can adjust parameters via USB port;
16) Take standard π-type 35mm guide-rail installation or screw-fixed installation that the module can be installed in the genset control box;
17) Modular design, self extinguishing ABS plastic shell, light weight, compact structure with easy installation.
CMM365-2G Cloud Monitoring Communication Module 2016-11-14 Version 1.0 Page 4 of 19
3 SPECIFICATION
CMM365-2G Cloud Monitoring Communication Module User Manual
Items
Operating Voltage
Power Consumption
Auxiliary Input
Auxiliary Output
Master RS485
Slave RS485
LINK
USB Device
GPRS Port
Case Dimensions
Working Conditions
Storage Condition
Weight
Contents
DC 8.0V~35.0V, continuous power supply.
Standby: ≤2W
Working: ≤5W
Volt Free Digital Input
1A DC30V Volt free output
Non seclusion type
Seclusion type
SmartGen exclusive port
B-type USB mother port
Standard SMB port (female), SMB port (male) for antenna.
73mmx105mmx35mm
Temperature: (-25 ~ +70)°C Humidity: (20 ~ 93)%RH
Temperature: (-25 ~ +70)°C
0.15kg
CMM365-2G Cloud Monitoring Communication Module 2016-11-14 Version 1.0 Page 5 of 19
CMM365-2G Cloud Monitoring Communication Module User Manual
4 PANEL AND TERMINAL DESCRIPTION
4.1 PANEL INDICATOR AND BUTTONS
Icon Note
GreenLED Light: Power supply and cloud server connection normal indicator;
RedLED Light: Common alarm indicator; POWER
ALARM(Red)
RS485
MASTER(Red)
RS485 SLAVE(Red)
GPRS(Red)
LINK(Red)
RedLED Blink when without inserting SIM card.
Normally Light: Common alarm indicator
Normally Extinguish:RS485 disabled
Normally Light: Communication fail
Blink: Communication normal
Normally Extinguish: Not communication
Blink: Communication normal
Extinguish: CMM365-2G login with server unsuccessfully
Light: Login with server successfully
Blink: Real-time communication normal
Normally Extinguish: Disabled
Normally Light: Communication fail
Blink: Communication normal
Lamp test/Rest:
Press this button for 1s, all the LEDs are illuminated; press for 10s, reset the module to default and all the LEDs blink for 3 times.
Note: After reset the module, set up the parameters via PC software is recommended. Please operate cautiously.
CMM365-2G Cloud Monitoring Communication Module 2016-11-14 Version 1.0 Page 6 of 19
CMM365-2G Cloud Monitoring Communication Module User Manual
4.2 GPRS
Connect GPRS antenna to cloud monitoring module port.
4.3 MASTER RS485
Achieving genset data information via RS485 port connects to Genset control module’s RS485 port.
Add 120Ω terminal resistance is recommended if fail to communicate. Shielding wire one end connects to SCR and the other one hang in the air.
RS485 Connection Diagram is as follows,
4.4 SLAVE RS485
Connect to RS485 port of dynamic environment monitoring system via slave RS485 port, then dynamic environment system will achieve genset data monitoring function.
CMM365-2G Cloud Monitoring Communication Module 2016-11-14 Version 1.0 Page 7 of 19
CMM365-2G Cloud Monitoring Communication Module User Manual
4.5 LINK
Achieving genset data information via LINK port connects to Genset control module’s LINK port.
RS485 Connection Diagram is as follows,
4.6 USB DEVICE
Set up all the parameters and view CMM365-2G ID&Login password by CMM365 USB port connecting with PC USB port.
USB and PC connection diagram is follows,
CMM365-2G Cloud Monitoring Communication Module 2016-11-14 Version 1.0 Page 8 of 19
No.
1
2
6
7
8
9
10
11
12
13
3
4
5
CMM365-2G Cloud Monitoring Communication Module User Manual
4.7 TERMINAL
B-
B+
Function Cable Size
1.0mm
2
1.0mm
1.0mm
1.0mm
2
2
2
Note
Connected with negative of starter battery.
Connected with positive of starter battery. 3A fuse is recommended.
Active when connect to B-.
Active when connect to B-.
Aux. Input 1
Aux. Input 2
SCR
RS485 B(-)
RS485 A(+)
SCR
Normally
Open
Aux. Output Common
Normally
Close
RS485 B(-)
RS485 A(+) MASTER
SLAVE
1.0mm
2
1.0mm
1.0mm
2
2
0.5mm
2
0.5mm
2
0.5mm
2
0.5mm
2
0.5mm
2
0.5mm
2
Normally open outputs, rated 1A DC30V
Impedancerecommended, its single-end earthed.
Impedance-
120Ω shielding wire is
120Ω shielding wire is recommended, its single-end earthed.
CMM365-2G Cloud Monitoring Communication Module 2016-11-14 Version 1.0 Page 9 of 19
CMM365-2G Cloud Monitoring Communication Module User Manual
5 PROGRAMMABLE PARAMETERS
5.1 CONTENTS AND SCOPES OF PARAMETERS
Form1
No.
Gateway
Items Parameters Defaults Description
1
GSM
4
5
6
7
8
Website
2 URL
3 Server Port
4 Password
1 GSM Enabled
2 GPRS Password
3 Message Center
PIN Enabled
APN
SMS Enabled
SMS Warning
Phone Number Set
(0-65535)
(0-65535)
(0-65535)
(0-65535)
(0-1)
Reserved
Reserved
(0-1)
(0-65535)
(0-1)
(0-1)
Max. 20 bits cm.smartgen.com.cn
81
123456
20 Chinese characters, letters or numbers
40 characters
16 characters
1
0
40characters
0:Disabled; 1:Enabled
0:Disabled; 1:Enabled
0
0
Area code needed to be added before the phone number.
E.g. China 8613666666666
Cloud Server
1
Auto Gain Comm.
Port
2 ID
(0-1)
(1-254)
1
1
0:Disabled; 1:Enabled
Module ID
3
4
5
Communication Port
Baud Rate
Location Info
6 Longitude
7 Latitude
8
9
10
11
12
13
Altitude
Type
Name
Debug Staff Name
Telephone
Installation Time
(0-4)
(0-2)
(0-1)
2
0
0
0:Disabled;
1:LINK;
2:RS485;
3:RS232;
4:USB
0:9600bit/s;
1:19200bit/s
2: 115200bit/s
0: Disabled
1: Manual input location info
(-180-180)°
(-90-90)°
0.000000
0.000000
(-9999.9-9999.9) 100.0
Location and elevation of genset control module.
HGM6110 Detailed to See: Form4
(0-65535)
Module Names(20 Chinese characters, letters or numbers)
20 Chinese characters, letters or numbers
20 Chinese characters, letters or numbers
20 Chinese characters, letters or numbers
CMM365-2G Cloud Monitoring Communication Module 2016-11-14 Version 1.0 Page 10 of 19
CMM365-2G Cloud Monitoring Communication Module User Manual
14 History Data Rest (0-3600)s
15 Time Zone
Live Data Upload
16
Interval
Module Configuration Info
(-12-12)
(1-20)s
0
8
5
History data upload rest.
Note: No upload when it is 0s
Time Zone
Interval time of uploading real time data.
1
2
3
4
5 Rated Freq
6 Rated Current
7
8
9
10
11
12
Type
Rated Speed
AC Supply
Rated Volt
Rated Power
(0-5)
(0-6000)r/min
(0-3)
(30-30000)V
(10-600)Hz
(5-6000)A
(0-6000)kW
Custom Description 1 (0-65535)
Custom Description 2 (0-65535)
Custom Description 3 (0-65535)
Custom Description 4 (0-65535)
Custom Description 5 (0-65535)
0
0:AMF module
1:Single-unit self-starting module
2: Single-single parallel module
3:Mains-genset parallel module
4:Mains-bus parallel module
5:Bus-bus parallel module
Note: The parameter will auto change according to genset type.
Rated Speed
0:3P4W;1:3P3W;2:2P3W;3:1P2W 。
Rated Volt
1500
0
230
50
500
276
Rated Freq
Rated Current
Rated Power
Custom Description (20 Chinese characters, letters or numbers)
Custom Description (20 Chinese characters, letters or numbers)
Custom Description (20 Chinese characters, letters or numbers)
Custom Description (20 Chinese characters, letters or numbers)
Custom Description (20 Chinese characters, letters or numbers)
Digital Input
Digital Input 1
1 Setting
2 Type
(0-9)
(0-1)
0
0
Default: Not used
0:Active when close
1:Active when open
Action delay 3 Delay
Digital Input 2
3 Setting
(0-20.0) 0.0
4 Type
(0-9)
(0-1)
1
0
Default: Lamp test
0:Active when close
1:Active when open
Action delay 5 Delay
Digital Output
(0-20.0) 0.0
1 Setting (0-14) 0
Default: Not used
CMM365-2G Cloud Monitoring Communication Module 2016-11-14 Version 1.0 Page 11 of 19
CMM365-2G Cloud Monitoring Communication Module User Manual
Form2
No.
0 Not Used
1 Lamp Test
Item
Not used.
Description
All the indicators are illuminated when input is active.
2 Remote Control Inhibited Cloud start/stop control is prohibited when input is active.
3 Access Alarm Input
4 Fire Alarm Input
Access alarm is uploaded to server when input is active.
Fire alarm is uploaded to server when input is active.
5 Alarm Input
6 Reserved
7 Reserved
8 Reserved
9 Factory Test Mode
External alarm is uploaded to server when input is active.
It is only used for factory hardware port test when active.
Form3
No.
0 Not used
Item
1 Digital Input 1 Active
2 Digital Input 2 Active
3 RS485 Comm. Fail
4 Network Comm. Fail
5 LINK Comm. Fail
6 RS232 Comm. Fail
7 Common Alarm
8 Remote Control
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
Form4
Manufacturers
SmartGen
Type
HGM6110
HGM6120
HGM7x10
HGM7x20
HGM410
HGM420
HGM9120
HGM9210
HGM9220
HGM9310
Description
Output port won’t output when this item is selected.
Output when auxiliary input 1 is active.
Output when auxiliary input 2 is active.
RS485 communication fails.
Network communication fails.
LINK communication fails.
RS232 communication fails.
Output when there is an alarm.
When remote control command is sent via cloud server, output delay fixed as 20s.
Note
Single-unit self-starting module
AMF module
Single-unit self-starting module
AMF module
Single-unit self-starting module
AMF module
AMF module
Single-unit self-starting module
AMF module
Single-unit self-starting module
CMM365-2G Cloud Monitoring Communication Module 2016-11-14 Version 1.0 Page 12 of 19
DeepSea
ComAp
Harsen
CMM365-2G Cloud Monitoring Communication Module User Manual
HGM9320
HGM9410
HGM9420
HGM9510
HGM9520
HGM9530
HGM9540
HGM9560
HGM9580
HGM9610
HGM9620
ZX9320
HSC940
TC1.0
TC2.0
TC3.0
DSE7110MKII
DSE7120MKII
DSE7210
DSE7220
DSE7310
DSE7320
DSE7410
DSE7420
DSE7450
DSE8610
DSE8620
MRS10
Ⅱ
MRS16
Ⅱ
AMF25
Ⅱ
IGNT
GU620A
GU621A
GU630A
GU631A
GU620A-00
GU621A-00
GU630A-00
GU631A-00
GU320A
GU320B
AMF module
Single-unit self-starting module
AMF module
Single-single parallel module
Mains-genset parallel module
Single-single parallel module
Mains-genset parallel module
Mains-bus parallel module
Bus-bus parallel module
Single-unit self-starting module
AMF module
AMF module
Single-unit self-starting module
AMF module
AMF module
Single-unit self-starting module
Single-unit self-starting module
AMF module
Single-unit self-starting module
AMF module
Single-unit self-starting module
AMF module
Single-unit self-starting module
AMF module
Single-unit self-starting module
Single-single parallel module
Mains-single parallel module
Single-unit self-starting module
Single-unit self-starting module
AMF module
Single-single parallel module
Single-unit self-starting module
AMF module
Single-unit self-starting module
AMF module
Single-unit self-starting module
AMF module
Single-unit self-starting module
AMF module
Single-unit self-starting module
Single-unit self-starting module
CMM365-2G Cloud Monitoring Communication Module 2016-11-14 Version 1.0 Page 13 of 19
CMM365-2G Cloud Monitoring Communication Module User Manual
5.2 PC CONFIGURATION INTERFACE
The USB port of CMM366-3G communication module connects PC port to configure the parameters.
Gateway Configuration
Cloud Server Configuration
Module Monitoring Interface
CMM365-2G Cloud Monitoring Communication Module 2016-11-14 Version 1.0 Page 14 of 19
CMM365-2G Cloud Monitoring Communication Module User Manual
6 SMS FUNCTION AND REMOTE CONTROL
6.1 SMS SHORT MESSAGE ALARM
When controller detects alarm, it will send short message to phone automatically.
NOTE: SMS short message alarm function only suit for SmartGen HGM7000 series and HGM9000 series controllers.
NOTE: All alarms about shutdown, trip and stop and trip will be sent to the pre-set phone. Warnings are sent to the phone according to the pre-set.
6.2 GSM SHORT MESSAGE REMOTE CONTROL
Users send order message to the module, then controller will make actions according to this SMS order and pass back corresponding operations information. Controllers only execute the orders by pre-set.
SMS Orders List :
No. SMS Orders Pass Back Information Description
When genset is
GENSET ALARM
SYSTEM IN STOP MODE
GENSET AT REST stopping alarm
At rest status in stop mode
1
SMS
GENSET
SYSTEM IN MANUAL MODE
GENSET AT REST
SYSTEM IN TEST MODE
GENSET AT REST
SYSTEM IN AUTO MODE
GENSET AT REST
SYSTEM IN STOP MODE
GENSET IS RUNNING
At rest manual mode
At rest status in test mode
At rest status in auto mode
Running stop mode status status in in status of genset
SYSTEM IN MANUAL MODE
GENSET IS RUNNING
SYSTEM IN TEST MODE
GENSET IS RUNNING
SYSTEM IN AUTO MODE
GENSET IS RUNNING
Running manual mode
Running status in test mode
Running auto mode status status in in
2 SMS START
GENSET ALARM
STOP MODE NOT START
SMS START OK
Generator is shutdown alarm or trip alarm
Cannot start in stop mode
Start in manual/test
Start genset mode
AUTO MODE NOT START
Cannot start in auto mode
3
4
5
SMS STOP
MODE
SMS MANUAL
MODE
SMS TEST
MODE
SMS STOP OK
SMS MANUAL MODE OK
SMS TEST MODE OK
Set as stop mode
Set as manual mode
Set as test mode
CMM365-2G Cloud Monitoring Communication Module 2016-11-14 Version 1.0 Page 15 of 19
CMM365-2G Cloud Monitoring Communication Module User Manual
6
7
SMS AUTO
MODE
SMS AUTO MODE OK
SMS DETAIL
Pass back information can be set via controller software.
Set as auto mode
Gets details information of genset.
NOTE: When sending orders, users need to follow SMS orders in above form and all the letters must be capital.
NOTE: Pass back information from SMS DETAIL including: working mode, mains voltage, generator voltage, load current, mains frequency, generator frequency, active power, apparent power, power factor, battery voltage, D+ voltage, water temperature, oil pressure, oil level, engine speed, total running time, genset status, and alarm status.
7 SYSTEM DIAGRAM
One set CMM366-3G module connects with one genset monitor module. It can be connected via RS485 port, LINK port.
MM365-2G System Diagram
CMM365-2G Cloud Monitoring Communication Module 2016-11-14 Version 1.0 Page 16 of 19
CMM365-2G Cloud Monitoring Communication Module User Manual
8 CASE DIMENSION AND INSTALLATION
2 ways for installation: 35mm guide rail in box or screw (M4) installation as below:
CMM365-2G Case Dimension
CMM365-2G Guide Rail Installation
CMM365-2G Screw Installation
CMM365-2G Cloud Monitoring Communication Module 2016-11-14 Version 1.0 Page 17 of 19
9 FAULT FINDING
CMM365-2G Cloud Monitoring Communication Module User Manual
Symptoms
Controller no response with power.
Possible Solutions
Check power voltage;
Check controller connection wirings.
RS485
Abnormal
Check SIM card is inserted or not;
GPRS Indicator Not Light
Check GPRS antenna is connected or not.
Check connections;
Communication Check RS485 port is enabled or not;
Check settings of genset ID and baud rate are correct or not.
Check RS485’s connections of A and B is reverse connect or not.
LINK
Abnormal
Communication
Check connections;
Check LINK port is enabled or not;
Check settings of genset ID and baud rate are correct or not.
CMM365-2G Cloud Monitoring Communication Module 2016-11-14 Version 1.0 Page 18 of 19
4
5
CMM365-2G Cloud Monitoring Communication Module User Manual
10 ENCLOSE: PACKING LIST
1
No.
2
3
Name
CMM365-2G
Osculum Type GSM
Antenna
120Ω
Resistance
Certification
Matched
User Manual
Number
1
1
4
1
1
Remark
_________________________________
CMM365-2G Cloud Monitoring Communication Module 2016-11-14 Version 1.0 Page 19 of 19