2022 | INDUSTRIAL VENTILATION
Centro-M
Inline centrifugal fans
Use
Supply and extract ventilation systems installed in various premises.
Direct mounting inside air ductworks.
Compatible with ∅ 100 to 450 mm round air ducts.
Air flow: up to
Power: from
6280
1745
45 W
m³/h
l/s
Noise level: from 38 dBA
Design
The casing is made of steel with a special polymer coating.
Aerodynamically shaped casing.
External terminal box for connection to power mains.
Motor
Single-phase external rotor motor with a centrifugal impeller with backward curved blades.
Equipped with ball bearings for longer service life.
Overheat protection with built-in thermal switches with automatic restart.
Dynamically balanced impeller.
Some standard sizes have high-powered motors ( Centro-M max ).
For ventilation of premises with high requirements to noise level low-noise modifications are available ( Centro-M L ).
Speed control
Smooth speed control with an external thyristor controller or step speed control with an external auto transformer (both available upon separate order).
Mounting
Any mounting position.
The fans with the connecting diameter from 100 up to 315 mm are fixed to wall or ceiling with mounting brackets supplied as a standard.
The fans with the connecting diameter from 355 up to 450 mm are fixed with mounting brackets fixed on the casing.
Flexible air ducts are fixed on the fan spigots with clamps.
Modifications and options
max: high-powered motor.
L: low-powered and low-noise motor.
E: energy-efficient motor with low power consumption.
FR1 (for standard sizes 100–315): smooth speed controller adjustable from
0 to 100 % and power cable with mains plug.
G1: speed controller, temperature controller with external temperature sensor (cable length 4 m), power cable with mains plug.
W1: power cable with mains plug.
Centro-M 100 – Centro-M 315
Accessories
Silencers
Centro-M 355 – Centro-M 450
Filter boxes Electric heaters Water heaters
Backdraft air dampers
Air dampers Speed controllers
40
SD KFBK / KFBT EKH WKH VRV VK / VKA CDT E1.8
blaubergventilatoren.de
blaubergventilatoren.de
Designation key
Series
Centro-M
Duct diameter [mm]
100; 125; 150; 160; 200; 250;
315; 355; 400; 450
Motor modifications max: high-powered motor
L: low-powered motor
E: motor with low power consumption
Overall dimensions
[mm]
Type
Centro-M 100 L
Centro-M 100
Centro-M 125 L
Centro-M 125
Centro-M 150
Centro-M 150 max
Centro-M 160
Centro-M 160 max
Centro-M 200
Centro-M 200 max
Centro-M 250 E
Centro-M 250
Centro-M 315
Centro-M 315 max
Centro-M 355 L
Centro-M 400
Centro-M 450 448
∅ D
198
198
248
248
314
314
353
149
149
159
158
98
98
123
123
L
L3
∅ D1
405
405
460
570
608
345
345
345
345
345
345
305
340
255
255
255
255
L1
B1
415
415
522
634
670
355
355
355
355
355
355
320
350
270
270
270
270
B
455
455
522
663
700
395
395
395
395
395
395
360
390
310
310
310
310
L
260
290
506
570
644
255
255
250
250
200
230
220
245
205
205
205
205
L3
Options
FR1 (for standard sizes 100-315): smooth speed controller adjustable from 0 to 100 % and power cable with mains plug
G1: speed controller, temperature controller with external temperature sensor, power cable with mains plug
W1: power cable with mains plug
L1
30
30
60
60
60
25
25
25
25
20
20
25
25
20
20
20
20
L2
L
L2
30
30
60
60
60
30
30
30
30
20
20
25
20
25
25
25
25
L1
L3
40
40
70
70
80
40
40
40
40
40
40
30
40
30
30
30
30
Weight [kg]
6.6
8.3
6.2
8.4
8.0
8.8
18.8
25.1
27.26
5.1
5.6
5.0
6.4
2.9
3.2
2.9
3.2
Centro-M 100 – Centro-M 315 Centro-M 355 – Centro-M 450
INDUSTRIAL VENTILATION | 2022 41
2022 | INDUSTRIAL VENTILATION
Technical data
Parameters Centro-M 100 L Centro-M 100
Voltage [V]
Frequency [Hz]
Power [W]
Current [A]
Air flow [m³/h (l/s)]
RPM [min⁻¹]
Sound pressure level at 3 m [dBA]
Transported air temperature [°C]
SEC class
IP rating
Motor IP rating
50
45
0.24
233 (65)
2780
38
C
1 ~ 220–240
-25…+45
IPX4
IP44
60
50
0.23
267 (74)
3300
39
–
50
60
0.28
2840
40
C
1 ~ 220–240
279 (78)
-25…+45
IPX4
IP44
60
82
0.36
278 (77)
3320
41
–
ErP 2018 – 2018 –
To comply with ErP 2018 it is necessary to use a speed controller and local demand control typology (connect the sensor).
Centro-M 125 L
1 ~ 220–240
50
47
0.25
326 (91)
2760
37
60
54
0.24
370 (103)
3240
38
-25…+45
C –
IPX4
IP44
2018 –
Centro-M 125
1 ~ 220–240
50
64
0.29
360 (100)
2840
40
60
85
0.37
357 (99)
3300
42
-25…+45
C –
IPX4
IP44
2018 –
CENTRO-M 100 L, CENTRO-M 100
Sound power level,
A-weighted
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
Centro-M 100 L
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Centro-M 100
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
84
83
60
78
77
59
56 70 77 68 63
63 70 75 67 60
27 47 49 53 54
56 76 82 72 68
63 76 81 71 65
29 44 52 55 54
59 53
56 52
51 42
65 59
62 57
54 44
50
49
31
43
41
32
58 68
57 67
38 48
63 73
62 72
40 50
100
90
80
70
60
50
40
30
0
0
500
450
400
350
300
250
200
150
100
50
0
0
0
10 20 30 40 50 60 80
Centro-M 100 L, 50 Hz
Centro-M 100 L, 60 Hz
Centro-M 100, 50 Hz
Centro-M 100, 60 Hz
50
10 20
100 150 200 250 300
Air flow [m 3 /h]
30 40 50 60 70 80
50 100 150 200 250 300
Air flow [m 3 /h]
CENTRO-M 125 L, CENTRO-M 125
Sound power level,
A-weighted
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
Centro-M 125 L
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Centro-M 125
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
79
78
58
83
82
61
57 71 77 69 64 60
64 71 76 68 61 57
27 46 48 52 53 50
60 75 81 73 67 63
67 75 80 72 64 60
28 49 51 55 57 53
57
55
44
54
53
41
43 58 68
41 58 68
32 37 47
46 62 72
44 61 71
34 40 50
450
400
350
300
250
200
0
150
100
50
0
0
20 40 60 80
Centro-M 125 L, 50 Hz
Centro-M 125 L, 60 Hz
Centro-M 125, 50 Hz
Centro-M 125, 60 Hz
50 100 150 200 250 300 350 400
Air flow [m 3 /h]
20 40 60 80
100
90
80
70
60
50
40
30
0
0 50 100 150 200 250 300 350 400
Air flow [m 3 /h]
42 blaubergventilatoren.de
blaubergventilatoren.de
Parameters Centro-M 150 Centro-M 150 max
Voltage [V]
Frequency [Hz]
Power [W]
Current [A]
Air flow [m³/h (l/s)]
RPM [min⁻¹]
Sound pressure level at 3 m [dBA]
Transported air temperature [°C]
SEC class
IP rating
Motor IP rating
50
100
0.45
580 (161)
2700
45
C
1 ~ 220–240
-25…+45
IPX4
IP44
60
125
0.55
610 (169)
3100
46
–
50
127
0.55
2760
48
C
1 ~ 220–240
710 (197)
-25…+45
IPX4
IP44
60
174
0.76
750 (208)
3150
49
–
ErP 2018 – 2018 –
To comply with ErP 2018 it is necessary to use a speed controller and local demand control typology (connect the sensor).
Centro-M 160
1 ~ 220–240
50
99
0.44
567 (158)
2770
45
60
137
0.61
575 (160)
3160
47
-25…+45
C –
IPX4
IP44
2018 –
Centro-M 160 max
1 ~ 220–240
50
121
0.53
690 (192)
2800
48
60
170
0.75
730 (203)
3210
49
-25…+45
C –
IPX4
IP44
2018 –
CENTRO-M 150, CENTRO-M 150 MAX
Sound power level,
A-weighted
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
Centro-M 150
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Centro-M 150 max
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
90
90
66
94
94
68
53 87 86 75 74
53 88 85 72 71
28 49 58 60 60
56 91 90 79 78
56 92 89 76 75
29 51 61 63 63
71 68
66 65
60 50
75 71
69 68
63 52
57
55
39
54
52
37
69 79
69 79
45 55
74 84
74 84
48 58
700
Air flow [l/s]
0 20 40 60 80 100 120 140 160 180 200 220
600
500
Centro-M 150, 50 Hz
Centro-M 150, 60 Hz
Centro-M 150 max, 50 Hz
Centro-M 150 max, 60 Hz
400
300
200
100
0
210
0 100 200 300 400 500 600 700 800
Air flow [m 3 /h]
Air flow [l/s]
0 20 40 60 80 100 120 140 160 180 200 220
190
150
110
70
30
0 100 200 300 400 500 600 700 800
Air flow [m 3 /h]
CENTRO-M 160, CENTRO-M 160 MAX
Sound power level,
A-weighted
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
Centro-M 160
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Centro-M 160 max
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
88
87
65
93
93
68
52 85 84 74 73
51 85 82 70 69
28 48 58 58 60
55 90 89 78 77
55 92 88 75 74
29 51 60 63 63
74
69
63
70
64
59
67 53
63 50
51 38
71 56
68 54
52 38
68 78
67 77
45 55
73 83
73 83
48 58
700
0
600
500
400
300
200
100
25 50 75 100 125 150 175 200
Centro-M 160, 50 Hz
Centro-M 160, 60 Hz
Centro-M 160 max, 50 Hz
Centro-M 160 max, 60 Hz
0
0 100 200 300 400 500 600 700 800
Air flow [m 3 /h]
230
0 25 50 75 100 125 150 175 200
190
150
110
70
30
0 100 200 300 400 500 600 700 800
Air flow [m 3 /h]
INDUSTRIAL VENTILATION | 2022 43
2022 | INDUSTRIAL VENTILATION
Parameters Centro-M 200 Centro-M 200 max
Voltage [V]
Frequency [Hz]
Power [W]
Current [A]
Air flow [m³/h (l/s)]
RPM [min⁻¹]
Sound pressure level at 3 m [dBA]
Transported air temperature [°C]
SEC class
IP rating
Motor IP rating
50
135
0.59
1070 (294)
2710
48
C
1 ~ 220–240
1220 (339)
-25…+45
IPX4
IP44
60
182
0.79
3120
50
–
50
193
0.84
2780
49
–
1 ~ 220–240
1150 (319)
IPX4
IP44
1200 (333)
-25…+45
60
240
1.05
2850
49
–
ErP 2018 – 2018 –
To comply with ErP 2018 it is necessary to use a speed controller and local demand control typology (connect the sensor).
Centro-M 250 E
1 ~ 220–240
50
95
0.47
900 (250)
2050
47
-25…+45
C
IPX4
IP44
2018
Centro-M 250
50
194
1 ~ 220–240
60
240
0.85
1420 (394)
2790
50
-25…+45
1.05
1520 (422)
2860
51
– –
IPX4
IP44
2018 –
CENTRO-M 200, CENTRO-M 200 MAX
Sound power level,
A-weighted
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
Centro-M 200
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Centro-M 200 max
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
90
87
68
95
94
70
49 78 87 81 81
46 77 81 79 79
29 52 60 63 63
56 92 91 79 78
56 92 89 75 74
29 52 62 64 64
82 74
82 74
62 53
75 72
69 68
64 53
57
54
39
63
64
39
69 79
67 77
48 58
74 84
74 84
49 59
400
300
200
100
700
0
600
500
0
0
50 100 150 200 250 300 350
Centro-M 200, 50 Hz
Centro-M 200, 60 Hz
Centro-M 200 max, 50 Hz
Centro-M 200 max, 60 Hz
200 400 600 800 1000 1200 1400
Air flow [m 3 /h]
Air flow [l/s]
50 100 150 200 250 300 350 0
280
230
180
130
80
0 200 400 600 800 1000 1200 1400
Air flow [m 3 /h]
CENTRO-M 250 E, CENTRO-M 250
Sound power level,
A-weighted
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
Centro-M 250 E
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Centro-M 250
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
89
87
67
90
88
71
60 76 83 81 83
63 75 72 80 82
34 48 59 62 62
61 78 85 83 85
64 77 73 82 84
38 52 62 66 65
79 75
80 75
60 49
81 77
82 77
64 58
65
63
44
64
62
38
68 78
66 76
47 57
70 80
68 78
50 60
400
300
200
100
800
0
700
600
500
0
0
Centro-M 250 E, 50 Hz
Centro-M 250, 50 Hz
Centro-M 250, 60 Hz
300
0
250
200
150
100
50
0
200 400 600 800 1000 1200 1400 1600
Air flow [m 3 /h]
Air flow [l/s]
50 100 150 200 250 300 350 400
200 400 600 800 1000 1200 1400 1600
Air flow [m 3 /h]
44 blaubergventilatoren.de
blaubergventilatoren.de
Parameters Centro-M 315 Centro-M 315 max
Voltage [V]
Frequency [Hz]
Power [W]
Current [A]
Air flow [m³/h (l/s)]
RPM [min⁻¹]
Sound pressure level at 3 m [dBA]
Transported air temperature [°C]
SEC class
IP rating
Motor IP rating
50
171
0.77
1440 (400)
2600
52
–
1 ~ 220–240
-25…+45
IPX4
IP44
60
241
1.05
1550 (431)
2850
53
–
50
295
1.34
1920 (533)
2720
54
–
1 ~ 220–240
ErP 2018 – 2018
To comply with ErP 2018 it is necessary to use a speed controller and local demand control typology (connect the sensor).
-25…+45
IPX4
IP44
60
413
1.8
1980 (550)
2780
55
–
–
Centro-M 355 L
50
233
1.06
2250 (625)
1375
58
1 ~ 220–240
60
297
1.30
2350 (653)
1620
59
-25…+45
– –
IPX4
IP44
2018 –
CENTRO-M 315, CENTRO-M 315 MAX
Sound power level,
A-weighted
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
Centro-M 315
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Centro-M 315 max
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
92
91
72
94
92
74
62 80 87 85 87
66 79 75 84 87
37 51 64 67 67
63 81 88 86 88
67 81 77 86 88
38 53 66 69 69
83 79
84 79
65 53
84 80
86 81
67 54
68
66
42
66
65
41
71 81
70 80
52 62
73 83
72 82
54 64
500
400
300
200
800
0
700
600
100 200 300 400
Centro-M 315, 50 Hz
Centro-M 315, 60 Hz
500
Centro-M 315 max, 50 Hz
Centro-M 315 max, 60 Hz
100
0
500
0
0 200 400 600 800 1000 1200 1400 1600 1800 2000
Air flow [m 3 /h]
100 200 300 400
Air flow [l/s]
500
400
300
200
100
0 200 400 600 800 1000 1200 1400 1600 1800 2000
Air flow [m 3 /h]
CENTRO-M 355 L
Sound power level,
A-weighted
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
95
96
78
57 82 80 84 90
61 74 84 81 90
33 55 64 72 74
91
93
74
86 75
85 77
64 56
74 84
75 85
58 68
800
700
600
500
400
Centro-M 355 L, 50 Hz
Centro-M 355 L, 60 Hz
300
200
100
0
1000
900
800
700
600
500
400
300
200
100
0
0 500 1000 1500 2000 2500 3000 3500
Air flow [m 3 /h]
Air flow [l/s]
0 100 200 300 400 500 600 700 800 900 1000
500 1000 1500 2000 2500 3000 3500
Air flow [m 3 /h]
INDUSTRIAL VENTILATION | 2022 45
2022 | INDUSTRIAL VENTILATION
Parameters Centro-M 400
Voltage [V]
Frequency [Hz]
Power [W]
Current [A]
Air flow [m³/h (l/s)]
RPM [min⁻¹]
Sound pressure level at 3 m [dBA]
Transported air temperature [°C]
SEC class
IP rating
Motor IP rating
50
460
2.23
3090 (858)
1370
61
-40…+80
–
1 ~ 220–240
IPX4
IP44
60
673
3.05
3500 (972)
1585
64
-40…+55
–
ErP –
To comply with ErP 2018 it is necessary to use a speed controller and local demand control typology (connect the sensor).
50
665
2.89
5300 (1472)
1265
65
-40…+70
–
Centro-M 450
1 ~ 220–240
IPX4
IP44
2018
60
1250
5.40
6280 (1745)
1560
73
-25..+60
–
–
CENTRO-M 400
Sound power level,
A-weighted
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
97
96
81
59 84 82 86 92
61 75 85 82 90
35 57 66 75 77
93 88
94 86
77 66
78
78
58
77 87
76 86
61 71
800
700
600
Centro-M 400, 50 Hz
Centro-M 400, 60 Hz
500
400
300
200
100
1000
900
800
700
600
500
400
300
200
100
0
0 500 1000 1500 2000 2500 3000 3500
Air flow [m 3 /h]
Air flow [l/s]
0 100 200 300 400 500 600 700 800 900 1000
0 500 1000 1500 2000 2500 3000 3500
Air flow [m 3 /h]
CENTRO-M 450
Sound power level,
A-weighted
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
98
98
86
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
59 85 83 87 93 94
63 76 87 84 92 95
37 60 70 79 81 81
89 78
88 80
70 61
78 88
78 88
65 75
800
0 200 400 600 800 1000 1200 1400 1600 1800
700
600
Centro-M 450, 50 Hz
Centro-M 450, 60 Hz
500
400
300
200
100
0
1700
1500
1300
1100
900
700
500
300
0
0 1000 2000 3000 4000 5000 6000
Air flow [m 3 /h]
Air flow [l/s]
0 200 400 600 800 1000 1200 1400 1600 1800
1000 2000 3000 4000 5000 6000
Air flow [m 3 /h]
46 blaubergventilatoren.de
广告