Sound-insulated inline centrifugal fans
Use
Supply and extract ventilation systems installed in premises with high requirements to the noise level.
Suitable for limited mounting space.
Compatible with ∅ 100 up to 315 mm round air ducts.
Air flow: up to
Power: from
2150
597
72 W
m³/h
l/s
Noise level: from 33 dBA
Design
Galvanized steel casing internally filled with 30 mm thermal- and soundinsulating layer made of non-flammable foamed polyurethane.
The connection spigots are equipped with rubber seals.
Fixing brackets for easy mounting.
Motor
Two-pole external rotor asynchronous motor with centrifugal impeller and backward curved blades.
The motor is installed on specially designed vibration-damping mounts to absorb vibration and noise.
Equipped with ball bearings for longer service life.
Integrated thermal protection with automatic restart.
Dynamically balanced impeller.
Speed control
Smooth speed control with an external thyristor controller or step speed control with an external auto transformer (both available upon separate order).
Mounting
Fixed to wall or ceiling with a fixing bracket supplied as a standard.
Flexible air ducts are fixed on the fan spigots with clamps.
Power is supplied through an external terminal box.
Modifications and options
max: high-powered motor.
G1: speed controller, temperature controller with external temperature sensor (cable length 4 m), power cable with mains plug.
GI1: speed controller, temperature controller with integrated temperature sensor and power cable with mains plug.
The G1 and GI1 modifications enable automatic speed control depending on indoor temperature. The optimal ventilation solution for premises requiring permanent temperature control as greenhouses, orangeries, etc.
W1: power cable with mains plug.
Designation key
Series
Iso-B
Spigot diameter [mm]
100; 125; 150; 160; 200; 250; 315
Accessories
Silencers Filter boxes
Motor modifications max: high-powered motor
Options
G1: speed controller, temperature controller with external temperature sensor, power cable with mains plug
GI1: speed controller, temperature controller with integrated temperature sensor and power cable mains plug
W1: power cable with mains plug
Electric heaters Water heaters
Backdraft air dampers
Air dampers Speed controllers Timers/Sensors
108
SD KFBK / KFBT EKH WKH VRV VK / VKA CDT E1.8
TE(TI) / HSE(HSI) /
LSE(LSI) / IRSE(IRSI) blaubergventilatoren.de
blaubergventilatoren.de
Overall dimensions
[mm]
Type
Iso-B 100
Iso-B 125
Iso-B 150
Iso-B 160
Iso-B 200
Iso-B 200 max
Iso-B 250
Iso-B 315
∅ D
199
199
249
314
99
124
149
159
B
432
432
432
502
322
322
352
352
B1
368
368
368
438
280
280
310
310
H
287
287
287
397
192
192
212
212
L
588
588
588
648
447
447
477
477
L1
506
506
506
566
380
380
410
410
L2
480
480
480
540
350
350
380
380
Weight [kg]
10.0
12.0
12.5
15.5
5.4
5.4
6.4
6.4
INDUSTRIAL VENTILATION | 2021 109
2021 | INDUSTRIAL VENTILATION
Technical data
Parameters
Voltage [V]
Frequency [Hz]
Power [W]
Current [A]
Maximum air flow [m³/h (l/s)]
RPM [min⁻¹]
Sound pressure at 3 m [dBA]
Transported air temperature [°C]
SEC class
IP rating
Motor IP rating
ErP
Iso-B 100
1 ~ 230
50
73
0.32
240 (67)
2560
33
-25…+55
C
IPX4
IP44
2018
60
77
0.34
255 (71)
2690
34
Iso-B 125
1 ~ 230
50
73
0.32
330 (92)
2590
35
-25…+55
C
IPX4
IP44
2018
60
77
0.34
345 (96)
2700
36
Iso-B 150
50
72
0.32
420 (117)
2600
36
1 ~ 230
60
76
0.33
435 (121)
2720
37
-25…+55
C
IPX4
IP44
2018
Iso-B 160
50
75
0.33
420 (117)
2690
36
1 ~ 230
60
76
0.33
435 (121)
2720
37
-25…+55
C
IPX4
IP44
2018
ISO-B 100
Sound power level,
A-weighted
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
59
68
40
400
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
53
49
27
57
50
29
54
53
32
52
56
31
51
66
34
54
63
29
51
56
29
47
54
20
350
300
250
200
150
100
50
0
0
80
75
70
65
60
0
50 Hz
60 Hz
50 100
50 100
150
150
200 250
Air flow [m³/h]
200 250
ISO-B 150
Sound power level,
A-weighted
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
62
66
41
49
43
26
50
44
30
58
59
35
56
55
34
54
62
34
55
60
30
52
55
26
50
53
25
400
350
300
250
200
150
100
50 50 Hz
60 Hz
0
80
75
70
65
60
0 50 100 150 200 250 300 350 400 450
Air flow [m³/h]
0 50 100 150 200 250 300 350 400 450
ISO-B 125
Sound power level,
A-weighted
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
400
64
65
38
51
50
29
51
49
32
54
59
33
56
55
33
54
61
33
55
61
31
53
58
28
51
51
25
350
300
250
200
150
100
50
0
0
80
75
70
65
60
0
50 Hz
60 Hz
50 100 150 200 250 300 350
Air flow [m³/h]
50 100 150 200 250 300 350
ISO-B 160
Sound power level,
A-weighted
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
62
68
41
50
48
28
51
47
26
60
57
32
56
60
33
52
67
36
55
63
34
54
59
25
51
56
23
400
350
300
250
200
150
100
50
80
75
70
65
60
0
0 50 100 150 200 250 300 350 400 450
Air flow [m³/h]
0
50 Hz
60 Hz
50 100 150 200 250 300 350 400 450
110 blaubergventilatoren.de
blaubergventilatoren.de
Parameters
Voltage [V]
Frequency [Hz]
Power [W]
Current [A]
Maximum air flow [m³/h (l/s)]
RPM [min⁻¹]
Sound pressure at 3 m [dBA]
Transported air temperature [°C]
SEC class
IP rating
Motor IP rating
ErP
Iso-B 200
50
103
0.45
730 (203)
1 ~ 230
60
122
0.53
750 (208)
2550
38
-25…+50
2740
39
-25…+45
B
IPX4
IP44
2018
Iso-B 200 max
50
195
0.85
950 (264)
1 ~ 230
60
232
1.02
960 (267)
2570
41
-25…+45
2690
42
-25…+45
B
IPX4
IP44
2018
Iso-B 250
1 ~ 230
50
198
0.87
1300 (361)
60
238
1.04
1315 (365)
2420
41
-25…+50
2730
43
-25…+45
–
IPX4
IP44
–
Iso-B 315
1 ~ 230
50
322
1.4
2150 (597)
60
367
1.6
2150 (597)
2670
43
-25…+45
2850
44
-25…+45
–
IPX4
IP44
–
ISO-B 200
Sound power level,
A-weighted
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
450
400
52
67
43
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
37
49
33
38
46
35
45
55
33
45
64
38
39
59
25
39
60
31
36
53
25
26
41
25
350
300
250
200
150
100
50 50 Hz
60 Hz
0
0 100 200 300 400 500 600 700 800
Air flow [m³/h]
120
110
100
90
0 100 200 300 400 500 600 700 800
ISO-B 250
Sound power level,
A-weighted
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
59
74
46
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
44
51
33
45
51
36
54
62
41
51
70
42
47
67
30
45
64
26
45
61
23
38
55
27
600
500
400
300
200
100
0
0
250
230
210
190
170
150
0
50 Hz
60 Hz
200 400 600 800 1000 1200 1400
Air flow [m³/h]
200 400 600 800 1000 1200 1400
ISO-B 200 MAX
Sound power level,
A-weighted
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
53
70
45
41
48
29
43
49
32
53
57
37
51
68
40
47
65
27
44
63
29
44
58
26
36
51
27
500
400
300
200
100
50 Hz
60 Hz
0
230
210
190
170
150
0 100 200 300 400 500 600 700 800 900 1000
ISO-B 315
Sound power level,
A-weighted
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
59
75
48
45
52
41
47
51
41
56
59
44
47
68
43
48
68
36
50
65
28
44
62
32
40
54
29
700
600
500
400
300
200
100
0
0
380
320
260
0
50 Hz
60 Hz
500 1000 1500 2000
Air flow [m³/h]
500 1000 1500 2000
INDUSTRIAL VENTILATION | 2021 111
Descarcă
Publicitate