Sound-insulated inline fans
Use
Hot and highly polluted air extract up to
+120 °C in high resistance condition.
Kitchen placement extract systems (combi ned with grease filters).
Ventilation for baking halls.
Welding gas extract.
The fans is available for round air ducts
∅ 150, 160, 200, 250, 315, 355, 400, 450 mm.
Air flow: up to
Power: from
8138
2261
180
m³/h
l/s
W
Noise level: from 41 dBA
Design
Galvanized steel casing internally filled with 50 mm thermal- and sound-insulating layer made of non-flammable mineral wool.
The fan casing is installed on a supporting mounting frame with integrated vibration isolators.
The swivel motor-impeller block is attached to the swivel door which facilitates the fan servicing.
Motor
Single- or three-speed motor.
Galvanized steel impeller.
Equipped with ball bearings for longer service life.
Dynamically balanced impeller.
F class motor winding insulation and IP54 ingress protection rating.
Operation and speed control
Smooth or step-up speed control with an auto transformer or frequency inverter (both available upon separate order).
Mounting
Compatible with round air ducts. The spigot diameter matches the standard air duct sizes.
Mounting to the wall with the mounting angle bracket UM Iso-K . Available upon separate order.
External terminal box on the motor for connection to power mains.
Iso-K 150 4E
Iso-K 150 4D
Iso-K 160 4E
Iso-K 160 4D
Iso-K 200 4E
Iso-K 200 4D
Iso-K 250 4E
Iso-K 250 4D
Iso-K 315 4E
Iso-K 315 4D
Iso-K 315 2E
Iso-K 315 2D
Iso-K 355 4E
Iso-K 355 4D
Iso-K 355 2E
Iso-K 355 2D
Iso-K 400 4E
Iso-K 400 4D
Iso-K 400 6E
Iso-K 400 6D
Iso-K 450 4E
Iso-K 450 4D
Iso-K 450 6E
Iso-K 450 6D
Overall dimensions
[mm]
Type ∅ D B B1 H H1 L L1 L2 L3 L4
Weight
[kg]
150 410 330 540 365 525 500 470 475 205 17
150 410 330 540 365 525 500 470 475 205 17
160 410 330 540 365 525 500 470 475 205 17
160 410 330 540 365 525 500 470 475 205 17
200 485 365 600 425 625 600 570 515 235 25
200 485 365 600 425 625 600 570 515 235 25
250 575 435 665 505 700 675 645 620 285 40
250 575 435 665 505 700 675 645 620 285 40
315 690 550 708 600 715 700 650 612 327 53
315 690 550 708 600 715 700 650 612 327 52
315 690 550 708 600 715 700 650 672 327 61
315 690 550 708 600 715 700 650 672 327 60
355 740 600 764 655 727 700 650 637 352 60
355 740 600 764 655 727 700 650 637 352 59
355 740 600 764 655 727 700 650 637 352 68
355 740 600 764 655 727 700 650 637 352 65
400 906 700 900 790 908 900 850 747 402 92
400 906 700 900 790 908 900 850 747 402 92
400 906 700 900 790 908 900 850 687 402 87
400 906 700 900 790 908 900 850 687 402 87
450 996 750 980 870 925 900 850 782 437 109
450 996 750 980 870 925 900 850 782 437 109
450 996 750 980 870 925 900 850 739 437 105
450 996 750 980 870 925 900 850 739 437 105
Designation key
Series
Iso-K
Spigot diameter [mm]
150; 160; 200; 250; 315;
355; 400; 450
Accessories
Backdraft air dampers
Fixing brackets
Motor
Number of poles Phase
2; 4; 6
Sleeves
E: single-phase
D: three-phase
Flexible connectors
150
VRV UM Iso-K V Iso-K EVA blaubergventilatoren.de
blaubergventilatoren.de
Technical data
Parameters
Voltage [V]
Frequency [Hz]
Power [W]
Current [A]
Maximum air flow [m³/h (l/s)]
RPM [min⁻¹]
Sound pressure at 3 m [dBA]
Transported air temperature [°C]
IP rating
Motor IP rating
Iso-K 150 4E /
Iso-K 160 4E
1 ~ 230
50
180
1.7
700 (194)
1450
41
-20…+120
IP54
IP54
Iso-K 150 4D /
Iso-K 160 4D
3 ~ 400
50
180
0.6
730 (203)
1455
41
-20…+120
IP54
IP54
Iso-K 200 4E
1 ~ 230
50
550
3.0
1600 (444)
1475
45
-20…+120
IP54
IP54
Iso-K 200 4D
3 ~ 400
50
750
2.0
1650 (458)
1465
45
-20…+120
IP54
IP54
Iso-K 250 4E
1 ~ 230
50
1500
11.0
3400 (945)
1500
51
-20…+120
IP54
IP54
Iso-K 250 4D
3 ~ 400
50
1500
3.4
3500 (972)
1470
51
-20…+120
IP54
IP54
ISO-K 150 4E / ISO-K 160 4E, ISO-K 150 4D / ISO-K 160 4D
Sound power level,
A-weighted
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
76
77
57
68
73
51
70
77
56
72
79
57
62
70
50
59
66
49
63
67
48
57
60
40
61
53
33
220
200
180
160
140
120
100
80
60
40
20
0
0 100 200 300 400 500 600 700 800
Air flow [m³/h]
ISO-K 200 4E, ISO-K 200 4D
Sound power level,
A-weighted
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
79
82
59
71
78
53
75
78
60
75
81
58
66
74
54
62
68
50
65
69
51
58
64
42
64
56
36
200
150
100
50
0
0
350
300
250
500
Iso-K 200 4D
Iso-K 200 4E
1000 1500 2000
Air flow [m³/h]
ISO-K 250 4E, ISO-K 250 4D
Sound power level,
A-weighted
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
82
85
63
75
79
55
79
80
63
80
82
61
71
79
57
65
71
53
68
70
53
63
65
45
65
61
41
600
500
400
300
200
100
0
0 1000
Iso-K 250 4D
Iso-K 250 4E
2000 3000 4000
Air flow [m³/h]
INDUSTRIAL VENTILATION | 2022 151
2022 | INDUSTRIAL VENTILATION
Parameters
Voltage [V]
Frequency [Hz]
Power [W]
Current [A]
Maximum air flow [m³/h (l/s)]
RPM [min⁻¹]
Sound pressure at 3 m [dBA]
Max. transported air temperature [°C]
IP rating
Motor IP rating
Iso-K 315 4E
1 ~ 230
50
304
1.84
1970 (547)
1475
46
60
383
1.72
2310 (642)
1750
47
-20…+120
IP54
IP54
Iso-K 315 4D
3 ~ 400
50
184
0.70
2040 (567)
1488
46
60
206
0.70
2355 (654)
1776
48
-20…+120
IP54
IP54
Iso-K 315 2E Iso-K 315 2D
1 ~ 230 3 ~ 400
50
1531
60
2816
50
1225
60
2011
7.35
11.92
2.80
3.40
4695 (1304) 5345 (1485) 4710 (1308) 5290 (1470)
3125
53
3384
55
3025
52
3328
54
-20…+120
IP54
IP54
-20…+120
IP54
IP54
ISO-K 315 4E
Sound power level,
A-weighted
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
85
87
67
66 69 83 78 79
66 71 84 79 81
45 49 63 58 59
78 73
79 74
58 53
64
66
44
65 75
67 77
46 56
700
0
600
500
400
300
200
100
0
0
Air flow [l/s]
100 200 300 400 500 600
50 Hz
60 Hz
500 1000 1500 2000
Air flow [m³/h]
Air flow [l/s]
100 200 300 400 500 600
440
0
400
360
320
280
240
0 500 1000 1500 2000
Air flow [m³/h]
ISO-K 315 2E
Sound power level,
A-weighted
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
92
94
74
59 65 82 90 84
61 67 84 92 86
40 46 63 71 65
83 81
85 83
64 62
74
76
55
72 82
74 84
53 63
2000
1800
1600
1400
1200
1000
800
600
400
200
0
Air flow [l/s]
0 200 400 600 800 1000 1200 1400
0
50 Hz
60 Hz
1000 2000 3000 4000 5000
Air flow [m³/h]
Air flow [l/s]
0 200 400 600 800 1000 1200 1400
2800
2400
2000
1600
1200
0 1000 2000 3000 4000 5000
Air flow [m³/h]
ISO-K 315 4D
Sound power level,
A-weighted
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
85
87
67
64 83 79 75 71 69
77 85 80 77 72 70
51 65 60 56 51 49
64 59
66 61
44 39
65 75
67 77
46 56
700
0
600
500
400
300
200
100
0
0
Air flow [l/s]
100 200 300 400 500 600
50 Hz
60 Hz
500 1000 1500 2000
Air flow [m³/h]
Air flow [l/s]
100 200 300 400 500 600
240
220
200
180
160
140
120
0
0 500 1000 1500 2000
Air flow [m³/h]
ISO-K 315 2D
Sound power level,
A-weighted
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
90
92
72
58 64 80 89 82 81
60 66 82 91 84 83
39 45 62 70 64 63
79 72
81 74
61 54
70 80
72 82
52 62
2000
1800
1600
1400
1200
1000
800
600
400
200
0
Air flow [l/s]
0 200 400 600 800 1000 1200 1400
0
50 Hz
60 Hz
1000 2000 3000 4000 5000
Air flow [m³/h]
2300
2100
1900
1700
1500
1300
1100
900
Air flow [l/s]
0 200 400 600 800 1000 1200 1400
0 1000 2000 3000 4000 5000
Air flow [m³/h]
152 blaubergventilatoren.de
blaubergventilatoren.de
Parameters
Voltage [V]
Frequency [Hz]
Power [W]
Current [A]
Maximum air flow [m³/h (l/s)]
RPM [min⁻¹]
Sound pressure at 3 m [dBA]
Max. transported air temperature [°C]
IP rating
Motor IP rating
Iso-K 355 4E
1 ~ 230
50
393
2.11
3545 (985)
1517
50
-20…+120
IP54
IP54
60
525
2.34
3860 (1072)
1705
52
Iso-K 355 4D
3 ~ 400
50
405
0.87
3155 (876)
1379
49
-20…+120
IP54
IP54
60
580
1.25
3270 (908)
1578
50
Iso-K 355 2E
1 ~ 230
50
2621
12.66
6570 (1825)
2890
54
-20…+120
IP54
IP54
Iso-K 355 2D
3 ~ 400
50
3145
6.12
6185 (1718)
2652
54
-20…+120
IP54
IP54
ISO-K 355 4E
Sound power level,
A-weighted
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
89
91
71
74 76 86 81 83
72 78 88 83 84
50 57 67 62 63
81 75
83 77
62 55
68
69
48
69 79
71 81
50 60
0
800
700
600
500
400
300
200
100
0
0
200 400
Air flow [l/s]
600 800 1000
50 Hz
60 Hz
1000
400
2000 3000 4000
Air flow [m³/h]
Air flow [l/s]
800 1000
580
530
480
430
380
330
280
0
0 200 600
1000 2000 3000 4000
Air flow [m³/h]
ISO-K 355 2E
Sound power level,
A-weighted
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
92
94
74
59 66 80 90 85
65 68 83 92 86
39 46 62 72 66
83 81
84 82
65 63
73
76
56
72 82
74 84
54 64
2000
1800
1600
1400
1200
1000
800
600
400
200
0
0 400 800 1200
Air flow [l/s]
1600
0 1000 2000 3000 4000 5000 6000 7000
Air flow [m³/h]
2800
2700
2600
2500
2400
2300
2200
2100
0 400 800 1200
Air flow [l/s]
1600
0 1000 2000 3000 4000 5000 6000 7000
Air flow [m³/h]
ISO-K 355 4D
Sound power level,
A-weighted
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
88
90
70
67 87 82 78 74
80 88 84 80 75
54 68 63 59 54
71
73
51
67 62
68 64
46 41
68 78
70 80
49 59
700
0
600
500
400
300
200
100
0
0
200 400 600
Air flow [l/s]
800 1000
0
630
580
530
480
430
380
330
280
0
50 Hz
60 Hz
1000
200 400
2000
600
3000 3500
Air flow [m³/h]
Air flow [l/s]
800 1000
1000 2000 3000
Air flow [m³/h]
ISO-K 355 2D
Sound power level,
A-weighted
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
92
94
74
59 65 82 90 84
61 67 84 92 86
40 47 64 72 66
83
85
65
81 74
83 76
63 55
72 82
74 84
54 64
2000
1800
1600
1400
1200
1000
800
0 400 800 1200
Air flow [l/s]
1600
600
400
200
0
0 1000 2000 3000 4000 5000 6000 7000
Air flow [m³/h]
3300
0
3200
3100
400 800 1200
Air flow [l/s]
1600
3000
2900
2800
2700
0 1000 2000 3000 4000 5000 6000 7000
Air flow [m³/h]
INDUSTRIAL VENTILATION | 2022 153
2022 | INDUSTRIAL VENTILATION
Parameters
Voltage [V]
Frequency [Hz]
Power [W]
Current [A]
Maximum air flow [m³/h (l/s)]
RPM [min⁻¹]
Sound pressure at 3 m [dBA]
Max. transported air temperature [°C]
IP rating
Motor IP rating
Iso-K 400 4E
1 ~ 230
50
1048
5.00
5392 (1498)
1440
54
-20…+120
IP54
IP54
Iso-K 400 4D
3 ~ 400
50
785
2.25
5098 (1416)
1470
53
-20…+120
IP54
IP54
Iso-K 400 6E
1 ~ 230
50
362
1.71
2915 (810)
930
48
-20…+120
IP54
IP54
Iso-K 400 6D
3 ~ 400
50
357
0.92
2966 (824)
948
47
-20…+120
IP54
IP54
ISO-K 400 4E
Sound power level,
A-weighted
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
86
88
74
64 79 80 77 78
69 68 83 82 81
53 67 68 69 66
77 72
77 72
61 58
67
67
53
65 75
67 77
54 64
ISO-K 400 6E
Sound power level,
A-weighted
Air flow [l/s]
0 200 400 600 800 1000 1200 1400
900
800
700
600
500
400
300
200
100
0
1100
0 1000 2000 3000 4000 5000
Air flow [m³/h]
Air flow [l/s]
0 200 400 600 800 1000 1200 1400
1000
900
800
700
0 1000 2000 3000 4000 5000
Air flow [m³/h]
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
92
94
74
59 65 82 90 84
61 67 84 92 86
40 46 63 71 65
83 81
85 83
64 62
74
76
55
72 82
74 84
53 63
350
0
300
250
200
150
200 400 600
Air flow [l/s]
800 1000
100
50
400
380
0
360
340
320
0
0 500 1000 1500 2000 2500 3000 3500
Air flow [m³/h]
200 400 600
Air flow [l/s]
800 1000
300
0 500 1000 1500 2000 2500 3000 3500
Air flow [m³/h]
ISO-K 400 4D
Sound power level,
A-weighted
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
85
86
73
63 79 80 77 78 77
67 66 82 81 80 76
53 66 67 68 65 60
71 66
70 65
58 53
65 75
66 76
53 63
ISO-K 400 6D
Sound power level,
A-weighted
Air flow [l/s]
0 200 400 600 800 1000 1200 1400
900
800
700
600
500
400
300
200
100
0
800
700
600
500
400
300
0
0 1000 2000 3000 4000 5000
Air flow [m³/h]
Air flow [l/s]
0 200 400 600 800 1000 1200 1400
1000 2000 3000 4000 5000
Air flow [m³/h]
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
77
80
68
47 58 71 72 69 70
59 62 72 74 74 72
48 49 60 62 62 60
69 65
68 63
55 52
57 67
59 69
47 57
350
300
0
250
200
150
100
50
200 400 600
Air flow [l/s]
800 1000
0
390
0 500 1000 1500 2000 2500 3000 3500
Air flow [m³/h]
0 200 400 600
Air flow [l/s]
800 1000
350
310
270
230
0 500 1000 1500 2000 2500 3000 3500
Air flow [m³/h]
154 blaubergventilatoren.de
blaubergventilatoren.de
Parameters
Voltage [V]
Frequency [Hz]
Power [W]
Current [A]
Maximum air flow [m³/h (l/s)]
RPM [min⁻¹]
Sound pressure at 3 m [dBA]
Max. transported air temperature [°C]
IP rating
Motor IP rating
Iso-K 450 4E
1 ~ 230
50
1570
7.25
8138 (2261)
1470
57
-20…+120
IP54
IP54
Iso-K 450 4D
3 ~ 400
50
1350
2.81
7840 (2178)
1450
56
-20…+120
IP54
IP54
Iso-K 450 6E
1 ~ 230
50
594
2.85
5299 (1472)
970
50
-20…+120
IP54
IP54
Iso-K 450 6D
3 ~ 400
50
454
1.33
4991 (1386)
920
49
-20…+120
IP54
IP54
ISO-K 450 4E
Sound power level,
A-weighted
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
90
92
77
67 83 84 81 82
72 71 87 86 85
56 70 71 72 69
81 75
81 75
64 61
70
70
56
69 79
71 81
57 67
1000
900
800
700
600
500
400
300
200
100
0
0
0
200 600
2000
Air flow [l/s]
1000 1400 1800 2200
4000 6000 8000
Air flow [m³/h]
Air flow [l/s]
1000 1400 1800 2200 0 200
1500
1300
1100
900
700
0
600
2000 4000 6000 8000
Air flow [m³/h]
ISO-K 450 6E
Sound power level,
A-weighted
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
81
84
71
49 61 74 76 73
62 65 76 78 78
50 52 63 65 66
74 73
76 72
63 58
68
67
55
61 71
63 73
50 60
500
450
400
350
300
250
200
150
100
50
0
Air flow [l/s]
0 200 400 600 800 1000 1200 1400
0 1000 2000 3000 4000 5000
Air flow [m³/h]
Air flow [l/s]
0 200 400 600 800 1000 1200 1400
600
550
500
450
400
350
0 1000 2000 3000 4000 5000
Air flow [m³/h]
ISO-K 450 4D
Sound power level,
A-weighted
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
89
91
77
66 83 84 81 82
71 70 87 86 85
55 70 71 72 69
81
81
63
74 69
74 69
60 55
69 79
71 81
56 66
ISO-K 450 6D
Sound power level,
A-weighted
1000
900
800
700
600
500
400
300
200
100
0
Air flow [l/s]
0 200 600 1000 1400 1800 2200
0 2000 4000 6000 8000
Air flow [m³/h]
1400
1200
Air flow [l/s]
0 200 600 1000 1400 1800 2200
1000
800
600
400
0 2000 4000 6000 8000
Air flow [m³/h]
L wA
to inlet [dBA]
L wA
to outlet [dBA]
L wA
to environment [dBA]
Total
Octave frequency bands [Hz]
63 125 250 500 1000 2000 4000 8000
LpA
3 m
LpA
1 m
80
82
70
48 60 73 75 71
61 64 75 76 76
49 51 62 64 65
72
75
62
71 67
70 65
57 54
59 69
62 72
49 59
Air flow [l/s]
0 200 400 600 800 1000 1200 1400
450
400
350
300
250
200
150
100
50
0
500
450
400
350
300
250
200
0
0 1000 2000 3000 4000 5000
Air flow [m³/h]
Air flow [l/s]
0 200 400 600 800 1000 1200 1400
1000 2000 3000 4000 5000
Air flow [m³/h]
INDUSTRIAL VENTILATION | 2022 155
ಡೌನ್ಲೋಡ್ ಮಾಡಿ
ಜಾಹಿರಾತು