Datakom DKM-409 Manual
Add to my manuals
36 Pages
Datakom DKM-409 is a versatile device for measuring and analyzing various AC parameters in 3-phase distribution panels, offering features like harmonic distortion display, oscilloscope waveform display, user-configurable display screens, and Modbus RTU communication. Its isolated RS-485 port enables safe data transfer to automation systems, while the voltage and current inputs can be used for both 230/400V and 120/208V systems.
advertisement
[email protected] http://www.datakom.com.tr
Tel: +90-216 466 84 60
Fax: +90-216 364 65 65
DKM-409 NETWORK ANALYSER
WITH HARMONIC MEASUREMENT AND SCOPEMETER
INTRODUCTION FEATURES
The DKM-409 is a precision instrument designed for displaying various AC parameters in 3-phase distribution panels.
Thanks to its isolated RS-485 Modbus RTU communication port, the device is free from ground potential difference issues and measured parameters are safely transferred to factory and building automation systems.
The power supply of the unit is isolated, thus the same device can be used in both
230/400V and 120/208V systems.
The graphic screen allows display of waveforms and harmonic analysis graphs.
Various display screens can be scrolled automatically. The user configurable screen where any measured parameter set can be displayed, transforms the unit to a custom designed measurement panel.
True RMS measurements
Harmonic distortion display ( 31 harmonics)
Oscilloscope, waveform display
Max demand display
User configurable display screen
Fully isolated RS-485 serial port
MODBUS-RTU communication
2 configurable relay outputs
Energy pulse output capability
Optically isolated, configurable digital inputs
Switched dual active-reactive power counters
Independent mains/generator energy metering
Configurable user counters
Voltage transformer ratio for MV applications
Password protected front panel programming
High visibility, 128x64 pixels graphic LCD
Reduced panel depth
Wide operating temperature range
Sealed front panel (IP54)
Plug-in connection system
J38D01 - 1 -
SAFETY NOTICE
Failure to follow below instructions will result in death or serious injury
• Electrical equipment should be installed only by qualified specialist. No responsibility is assured by the manufacturer or any of its subsidiaries for any consequences resulting from the non-compliance to these instructions.
• Check the unit for cracks and damages due to transportation. Do not install damaged equipment.
• Do not open the unit. There is no serviceable parts inside.
• Fuses must be connected to the power supply and phase voltage inputs, in close proximity of the unit.
• Fuses must be of fast type (FF) with a maximum rating of
6A.
• Disconnect all power before working on equipment.
• When the unit is connected to the network do not touch terminals.
• Short circuit terminals of unused current transformers.
• Any electrical parameter applied to the device must be in the range specified in the user manual.
• Do not try to clean the device with solvent or the like.
Only clean with a dry cloth.
•
•
Verify correct terminal connections before applying power.
Only for front panel mounting.
J38D01 - 2 -
TABLE OF CONTENTS
Section
1. INSTALLATION
1.1. FRONT / REAR PANELS
1.2. MECHANICAL INSTALLATION
1.3. ELECTRICAL INSTALLATION
1.4. CONNECTION DIAGRAM FOR 230/400V NETWORK
1.5. CONNECTION DIAGRAM FOR 120/208V NETWORK
2. PUSHBUTTON FUNCTIONS
3. DISPLAY NAVIGATION
4. DISPLAY SCREEN
4.1. DISPLAY SCREEN DETAILS
4.2. PHASE SEQUENCE DISPLAY
5. DISPLAY SYMBOLS
6. SETTING AUTO-SCROLL MODE
7. RESETTING VISUAL WARNINGS
8. DEVICE CONFIGURATION
8.1. INTRODUCTION
8.2. ADJUSTING THE LCD CONTRAST
8.3. LANGUAGE SELECTION
8.4. CURRENT TRANSFORMER RATIO
8.5. VOLTAGE TRANSFORMER RATIO
8.6. MODBUS ADDRESS
8.7. CHANGING THE PASSWORD
8.8. MODIFYING THE SERIAL NUMBER
8.9. USER DISPLAY PAGE CONFIGURATION
8.10. CONFIGURING AN ITEM’S LOW OR HIGH LIMIT
8.11. INPUT CONFIGURATION
8.12. RELAY CONFIGURATION
8.13. RESETTING A COUNTER
8.14. RESETTING DEMAND VALUES
8.15. OVERCURRENT DETECTOR CONFIGURATION
8.16. PHASE SEQUENCE FAILURE
8.17. RESETTING LOW/HIGH LIMITS
8.18. RETURN TO FACTORY SETTINGS
8.19. CALIBRATION
9. MODBUS COMMUNICATIONS
9.1. DESCRIPTION
9.2. MODBUS REGISTERS
9.3. WARNING REGISTERS
10. TECHNICAL SPECIFICATIONS
J38D01 - 3 -
1. INSTALLATION
Before installation:
• Read the user manual carefully, determine the correct connection diagram.
• Remove all connectors and mounting brackets from the unit, then pass the unit through the mounting opening.
• Put mounting brackets and tighten. Do not tighten too much, this can brake the enclosure.
• Make electrical connections with plugs removed from sockets, then place plugs to their sockets.
• Note that the power supply terminal is separated from measurement terminals.
Below conditions may damage the device:
• Incorrect connections.
• Incorrect power supply voltage.
• Voltage at measuring terminals beyond specified range.
• Current at measuring terminals beyond specified range.
• Connecting or removing data terminals when the unit is powered-up.
• Overload or short circuit at relay outputs
• Voltage applied to digital inputs over specified range.
• High voltage applied to communication port.
Below conditions may cause abnormal operation:
• Power supply voltage below minimum acceptable level.
• Power supply frequency out of specified limits
• Phase order of voltage inputs not correct.
• Current transformers not matching related phases.
• Current transformer polarity incorrect.
J38D01 - 4 -
1.1 FRONT / REAR PANELS
1.2 MECHANICAL INSTALLATION
Panel Cutout Required Panel Depth
J38D01 - 5 -
1.3 ELECTRICAL INSTALLATION
Do not install the unit close to high electromagnetic noise emitting devices like contactors, high current busbars, switchmode power supplies and the like.
Although the unit is protected against electromagnetic disturbance, excessive disturbance can affect the operation, measurement precision and data communication quality.
• ALWAYS remove plug connectors when inserting wires with a screwdriver.
• Fuses must be connected to the power supply and phase voltage inputs, in close proximity of the unit.
• Fuses must be of fast type (FF) with a maximum rating of 6A.
• Use cables of appropriate temperature range.
• Use adequate cable section, at least 0.75mm
2
(AWG18).
• For current transformer inputs, use at least 1.5mm
2
section (AWG15) cable.
• The current transformer cable length should not exceed 1.5 meters. If longer cable is used, increase the cable section proportionally.
• Follow national rules for electrical installation.
• Current transformers must have 5A output.
• For the RS-485 connection, use appropriate shielded twisted wire cable.
Communication quality will depend highly on the cable used.
J38D01 - 6 -
1.4 CONNECTION DIAGRAM FOR 230/400V NETWORK
J38D01 - 7 -
1.5 CONNECTION DIAGRAM FOR 120/208V NETWORK
J38D01 - 8 -
2. PUSHBUTTON FUNCTIONS
Three buttons on the front panel provide access to configuration and measurement screens.
BUTTON FUNCTION
Previous screen or
Decrease related value (configuration mode)
Next screen or
Increase related value (configuration mode)
Changes voltage and current channels for
• scopemeter display
• harmonic display
• digital harmonic display
Available channels: U12-U23-U31- V1-V2-V3- I1-I2-I3
HELD PRESSED FOR 3 SEC: enable/disable auto-scroll function
HELD PRESSED TOGETHER FOR 3 SEC:
• Clears visual warning condition if any.
• If no warning condition, enters configuration mode.
J38D01 - 9 -
3. DISPLAY NAVIGATION
J38D01 - 10 -
4. DISPLAY SCREEN
4.1
DISPLAY SCREEN DETAILS
Display 1
DATAKOM LOGO
Software version
Display 4
I1 (A)
I2 (A)
I3 (A)
U1-2 (V)
Display 7
Total active power (kW)
Total reactive power (kVAr)
Power factor
Total active energy (kWh)
Display 10
I1 (A) demand value
I2 (A) demand value
I3 (A) demand value
P (kW) demand value
Display 13
Time Display Screen
Channel time curve
Channel frequency
Channel value (V/A)
Display 16
User configurable screen
Default values are:
USR1 USR4 – User counters
Display 2
U1-2 (V)
U2-3 (V)
U3-1 (V)
Frequency (Hz)
Display 5
P1 Active power (kW)
P2 Active power (kW)
P3 Active power (kW)
Total Active Power
Display 8
Total active power (kW)
Total reactive power (kVAr)
Power factor
Total reactive energy (kVArh)
Display 11
USR1 – User counter 1
USR2 – User counter 2
USR3 – User counter 3
USR4 – User counter 4
Display 14
Harmonic Display Screen
Channel harmonic bars
Channel frequency
Channel value (V/A)
Display 3
V1-N (V)
V2-N (V)
V3-N (V)
Frequency (Hz)
Display 6
Q1Reactive power(kVAr)
Q2Reactive power(kVAr)
Q3Reactive power(kVAr)
Total Reactive Power
Display 9
Total apparent power (kVA)
Total active power (kW)
Total reactive power (kVAr)
Power factor
Display 12
CT x VT ratio
Transmission speed (bps)
Modbus address
Instrument serial number
Display 15
Channel Harmonic List
(1-31 %)
J38D01 - 11 -
4.2
PHASE SEQUENCE DISPLAY
The unit checks continuously the sequence of AC phase voltages.
If voltages are in the correct sequence, below symbol appears on voltage display pages, namely pages 2 and 3
If voltages are in wrong order, the symbol disappears.
The effect of phase sequence failure is configurable. It can be a visual warning, a relay output or nothing.
To learn more about the phase sequence failure output, please review the section PHASE
SEQUENCE FAILURE in the CONFIGURATION menu.
J38D01 - 12 -
5. DISPLAY SYMBOLS
SYMBOL DESCRIPTION
Q2
Q3
∑ Q
S1
S2
S3
∑ S
Cos1
Cos2
Cos3
∑ Cos
Pc1
Pc2
Qc1
Qc2
I1mx
I1
I2
I3
P1
P2
P3
∑ P
Q1 ver
U12
U23
U31
FRQ
V1
V2
V3
Software version
Phase 1 to phase 2 AC RMS voltage value
Phase 2 to phase 3 AC RMS voltage value
Phase 3 to phase 1 AC RMS voltage value
Frequency value
Phase 1 to Neutral AC RMS voltage value
Phase 2 to Neutral AC RMS voltage value
Phase 3 to Neutral AC RMS voltage value
Phase 1 AC RMS current value
Phase 2 AC RMS current value
Phase 3 AC RMS current value
Phase 1 active power (kW) value
Phase 2 active power (kW) value
Phase 3 active power (kW) value
Total active power (kW) value
Phase 1 reactive power (kVAr) value
Phase 2 reactive power (kVAr) value
Phase 3 reactive power (kVAr) value
Total reactive power (kVAr) value
Phase 1 apparent power (kVA) value
Phase 2 apparent power (kVA) value
Phase 3 apparent power (kVA) value
Total apparent power (kVA) value
Phase 1 power factor
Phase 2 power factor
Phase 3 power factor
Power factor
Active power counter 1 (kWh)
Active power counter 2 (kWh)
Reactive power counter 1 (kVArh)
Reactive power counter 2 (kVArh)
Phase 1 maximum apparent current value
I2mx
I3mx
Pmax
USR1
USR2
USR3
USR4
Phase 2 maximum apparent current value
Phase 3 maximum apparent current value
Total active power maximum value
User counter 1
User counter 2
User counter 3
User counter 4
VTxIT
BAUD
Current Transformer Ratio x Voltage Transformer Ratio
Transmission speed (bps)
MODBUS Modbus node address
SERIAL Instrument serial number
I
C
H1-H31
Power factor is inductive
Power factor is capacitive
Harmonic values
J38D01 - 13 -
6. SETTING AUTO-SCROLL MODE
The unit offers the possibility of automatically scanning of all display screens.
In order to enable auto-scroll function hold the SET button pressed for 3 seconds.
In order to disable auto-scroll function hold the SET button pressed for 3 seconds.
When the auto-scroll is enabled, the unit will switch to the next screen every 5 seconds.
7. RESETTING VISUAL WARNINGS
In order to reset visual warnings, hold both MENU buttons pressed for 3 seconds.
If no fault conditions exists this will enable the configuration menu.
J38D01 - 14 -
8. DEVICE CONFIGURATION
8.1 INTRODUCTION
In order to offer the maximum flexibility to the user, the unit has several configurable parameters.
• Device configurations
LCD Contrast
Language selection
Modbus node address
User display screen configuration
• Input/Output Configurations
Reference value setting
Input Configurations
Relay Configurations
• Line Configurations
Clearing Counters
Resetting demand values
Overcurrent configuration
Setting the current transformer ratio
Setting the voltage transformer ratio
Input calibration
• Return to factory settings
In order to enable the configuration menu, hold both MENU buttons pressed for 3 seconds.
When the configuration mode is entered, the password entry screen will be displayed.
A 4 digit password must be entered using buttons.
The factory default password is “9876” . Each digit is adjusted with MENU buttons and the next digit is selected with SET button.
When the configuration mode is entered, a list of available configuration topics will be displayed as in the below screen.
In order to exit the configuration menu, hold both MENU buttons pressed for 3 seconds.
If no button is pressed, the unit will automatically close the configuration menu after 30 seconds.
Navigation on the list is made with and buttons. Selected configuration topic is shown in reverse video (black on white). In order to enter inside a configuration topic, please press button.
J38D01 - 15 -
8.2 ADJUSTING THE LCD CONTRAST
Select “ LCD CONTRAST ” on “ CONFIGURATION
MENU ”. Change the contrast value with and
until best visibility is obtained and then press
to save new LCD contrast value and return back to “ CONFIGURATION MENU ”.
.
8.3 LANGUAGE SELECTION
Select “ LANGUAGE ” on “ CONFIGURATION
MENU ”. Change language with and until the desired language is selected and then press to save the new language and return to
“ CONFIGURATION MENU ” again.
8.4 CURRENT TRANSFORMER RATIO
For the correct current measurement, the current transformer ratio has to be set properly.
The secondary of the current transformer is always supposed to be 5 Amps. Only the primary value is set.
Select “ CRNT TRF RATIO ” on “ CONFIGURATION
MENU ”.
Then adjust the current transformer ratio with and buttons until required value then press
button to save the new current transformer ratio and return to “ CONFIGURATION MENU ”.
J38D01 - 16 -
8.5 VOLTAGE TRANSFORMER RATIO
If a voltage transformer is used, then its ratio needs to be set to the unit.
The voltage transformer ratio is defined as primary voltage / secondary voltage. The secondary is always supposed 1.0. Thus only the primary is programmed.
Select “ VOLT TRF RATIO ” on “ CONFIGURATION
MENU ”.
Adjust the voltage transformer ratio with and
buttons until required value then press button to save new voltage transformer ratio and return to “ CONFIGURATION MENU ”.
8.6 MODBUS ADDRESS
Select “ MODBUS ADDRESS ” on
“ CONFIGURATION MENU ”. Change the modbus node address with and until the desired address is displayed and then press to save the new modbus node address and return to “ CONFIGURATION MENU ” again.
8.7 CHANGING THE PASSWORD
Select “ CHANGE PASSWORD ” on
“ CONFIGURATION MENU ”.
Write new password with MENU buttons. Every depression of digit.
button will switch to the next
Long press (3 sec) to save the new password and return to “ CONFIGURATION
MENU ” again.
J38D01 - 17 -
8.8 MODIFYING THE SERIAL NUMBER
The unit holds a user definable 16 characters serial number.
Every character can take values between 0-9 and
A-Z.
The default value of serial number is
“0000000000000000”.
Select “ SERIAL NUMBER ” on “ CONFIGURATION
MENU ”. Write new serial number with MENU buttons. Every depression of switch to the next character.
button will
Long press (3 sec) to save new serial number and return to “ CONFIGURATION MENU ” again.
8.9 USER DISPLAY PAGE CONFIGURATION
The unit offers a user-configurable screen (display page 16) through “ USER MENU ” topic.
There are 2 sizes of characters that can be selected (5x7 and 10x14 pixels).
Select the character size with and , and then press to select item menu.
Select an item to display on “ SELECT AN ITEM ” menu, then press .
This will return to character type selection menu for the next displayed item.
As long as the screen setting continues, the current status the user display page is constantly displayed.
The display configuration will resume when there is no place to show another item.
The user can terminate anytime by long pressing
(3 sec) the button.
J38D01 - 18 -
8.10 CONFIGURING AN ITEM’S LOW OR HIGH LIMIT
Select “ REFERENCE CNFG ” on
“ CONFIGURATION MENU ”. Select low limit
(minimum acceptable value) or high limit
(maximum acceptable value) of the item to configure then press .
Then select the item to configure on the list and press again.
After selection of the item, the limit value should be entered. Especially for power or user counters, large values may be needed. Thus the user must select the multiplier first (‘x1’,’x100’ or ‘x1000’).
For example; ‘x10’ means “ multiply set value by
10 ”. Then the user will enter a smaller value.
The format of the value is “000000.0” and can be between 0.0 and 999999.9
J38D01 - 19 -
After entering the limit value of the item, the action to be taken when the condition occurs has to be selected.
LOCK means that, once the condition occurs, it will persist until manually reset by the user.
Otherwise the condition will reset automatically when the event causing the condition goes off.
The user can select between actions to be taken when the condition occurs.
” VISUAL WARNING ” means there is no output function, but a message is displayed on the screen.
The unit has 2 internal relays and each one has four input registers referred as “ VALUE-1 ”,
“ VALUE-2 ”, “ VALUE-3 ”, and “ VALUE-4 ”.
The condition may be directed to any relay’s
VALUE registers.
VALUE registers will be used in relay configuration.
The “ RELAY CONFIGURATION ” chapter will describe in detail the use of VALUE registers.
J38D01 - 20 -
2.11 INPUT CONFIGURATION
The unit has two configurable inputs.
Level transitions from high to low (NC=normally closed contact) and low to high (NO=normally open contact) may be programmed independently.
There are various functions that can be assigned for each input. Some of these actions can be clearing a counter, selecting between counters, clearing fault conditions, assigning the input to relay input registers.
• Clear Counter: Sets the selected counter to zero.
• Increment Counter: Increments the selected counter by 1.
• Select Counter: The unit has 2 sets of active and reactive power counters additionally to 4 user counters.
Active/Reactive 1 counters are default selections and incremented with consumed power. As there may be more than one power source (like gensets) and these sources supply power on different occasions, the user may want to measure consumed powers from different sources with separate counters. If an input is assigned as “SELECT COUNTER”,
“kW/kVAr 1&2”, then the unit will increment the first counter set when there is no signal at the input, and it will increment the second set when the signal is present. In the same way, user counters can be switched with input signal.
• Clear Alarm: Resets selected alarm.
• Clear All Alarms: Resets all alarms.
• Relay Value: Write input status to relay
VALUE register.
J38D01 - 21 -
2.12 RELAY CONFIGURATION
The unit has 2 relay outputs with configurable functions.
Relays can be configured as kW or kVAr tick outputs, sending 1 pulse per kW (or kVAr).
Each relay has 4 input value registers.
Relays can operate depending on a logical function of their input value registers.
There are several available logical functions:
• Relay = VALUE 1: The relay output will follow the VALUE 1 register.
When the value is TRUE then the relay contact will close.
• Relay = NOT VALUE 1: The relay output will be the opposite of the
VALUE 1 register. When the value is
FALSE then the relay contact will close.
• Relay = VALUE 1 OR VALUE 2: If at least one of value registers is TRUE then the relay contact will close.
Otherwise it will open.
• Relay=VALUE 1 AND VALUE 2: If both value registers are TRUE then the relay contact will close. Otherwise it will open.
• Relay = VALUE 1 NOR VALUE 2: If at least one of value registers is TRUE then the relay contact will open. Otherwise it will close.
• Relay = VALUE 1 NAND VALUE 2: If both value registers are TRUE then the relay contact will open. Otherwise it will close.
• Relay = V1 OR V2 OR V3 OR V4: If at least one of value registers is TRUE then the relay contact will close. Otherwise it will open.
• Relay = V1 NOR V2 NOR V3 NOR V4: If at least one of value registers is TRUE then the relay contact will open.
Otherwise it will close.
• Relay = VALUE 1 OR (NOT VALUE 2):
If VALUE 1 is true or VALUE 2 is false then the relay contact will close.
Otherwise it will open.
• Relay = VALUE 1 AND (NOT VALUE
2): If VALUE 1 is true and VALUE 2 is false then the relay contact will close.
Otherwise it will open.
• Relay = VALUE 1 NOR (NOT VALUE
2): If VALUE 1 is true or VALUE 2 is false then the relay contact will open.
Otherwise it will close.
• Relay = VALUE 1 NAND (NOT VALUE
2): If VALUE 1 is true and VALUE 2 is false then the relay contact will open.
Otherwise it will close.
J38D01 - 22 -
A “delay before response can be set for relays.
The screen below will be displayed after first two steps. Set the required delay time here.
2.13 RESETTING A COUNTER
The unit offers 2 sets of active and reactive power counters together with 4 user counters. Counters can be reset via the configuration menu whenever required.
Select “ CLEAR COUNTERS ” on
“ CONFIGURATION MENU ”. From the list select the counter required to be reset.
A confirmation screen will appear. Selecting “ YES ” option on this screen will reset the counter and return to “ CONFIGURATION MENU ”.
Counter value cannot be restored.
2.14 RESETTING DEMAND VALUES
The unit always stores the maximum values of both current inputs (I1-I2-I3) and the total active power ( ∑ P).
These values are visualized on Display page 10.
The user can reset these values and restart the monitoring via “ DEMAND RESET ” menu.
Select “ DEMAND RESET ” on “ CONFIGURATION
MENU ”. Then select “YES” and press reset demand values and return to the
“ CONFIGURATION MENU ” .
to
J38D01 - 23 -
2.15 OVERCURRENT DETECTOR CONFIGURATION
The “OVERCURRENT” function is used in order to generate a protection relay output when any of the phase currents exceeds the preset value for “TIMEOUT” duration.
The response time depends on the overcurrent rate as shown on below graph.
4A
OVERCURRENT AREA
3A
2A
PERMITTED AREA
A
A: Over current value
T: Timeout value
The fastest detection time is 500 milliseconds.
The overcurrent function will be assigned to a relay output.
When overcurrent function is assigned to a relay, then other configurations for that relay is discarded.
J38D01 - 24 -
2.16 PHASE SEQUENCE FAILURE
The unit checks continuously the sequence of AC phase voltages.
If voltages are in the correct sequence, below symbol appears on voltage display pages, namely pages 2 and 3.
If voltages are in wrong order, the symbol disappears.
The effect of phase sequence failure is configurable. It can be:
• assigned to a relay’s value register
• a visual warning
• nothing (no effect) .
Select “ PHASE SEQUENCE ” on
“ CONFIGURATION MENU ”. Select action to take then press .
Note that PHASE SEQUENCE FAILURE may be combined with other conditions using VALUE registers. (see section RELAY CONFIGURATION )
2.17 RESETTING LOW/HIGH LIMITS
It is possible to clear every items low and high limit configurations.
For this select “ RESET ALL REFS ” on
“ CONFIGURATION MENU ”. Select “YES” and then press to clear all reference configurations and return to “ CONFIGURATION
MENU ”.
J38D01 - 25 -
2.18 RETURN TO FACTORY SETTINGS
It is possible to reset the unit to factory settings, before starting a new configuration process.
For this select “ RETURN FACTORY ” on
“ CONFIGURATION MENU ”.
Then select “YES” and press to reset the unit to factory configuration and return to
“ CONFIGURATION MENU ”.
2.19 CALIBRATION
Calibration can be modified only with a special password.
The unit is factory calibrated but it is possible to recalibrate it in order to obtain equal display values on different measuring instruments.
Select “ CALIBRATION ” on “ CONFIGURATION
MENU ”. Then select channel with and , and then press .
Then adjust the coefficient until required measured value is displayed on the bottom right of the screen then press to save the new calibration coefficient and return “ CONFIGURATION MENU ”.
CHANNEL
MEASUREMENT
J38D01 - 26 -
9. MODBUS COMMUNICATIONS
9.1 DESCRIPTION
The unit offers serial data communication port allowing it to be integrated in automation systems.
The serial port is of RS-485 MODBUS-RTU standard. It is fully isolated from power supply and measurement terminals for failure-free operation under harsh industrial conditions.
The MODBUS properties of the unit are:
-Data transfer mode: RTU
-Serial data: 9600 bps, 8 bit data, no parity, 1 bit stop
-Supported functions:
-Function 3 (Read multiple registers)
-Function 6 (Write single register)
-The answer to an incoming message is sent with a minimum of 4.3ms delay after message reception.
Each register consists of 2 bytes (16 bits). Larger data structure contain multiple registers.
Detailed description about the MODBUS protocol is found in the document “ Modicon
Modbus Protocol Reference Guide” .
This document may be downloaded at: www.modbus.org/docs/PI_MBUS_300.pdf
Data Reading
The function 03 (read multiple registers) will be used for data reading. The MODBUS master will send a query. The answer will be one of the below:
-A response containing the requested data
-An exceptional response indicating a read error.
The maximum number of registers read in one message is 123. If more registers are requested, the unit will send only the first 123 registers.
The query message specifies the starting register and quantity of registers to be read. The message structure is below:
Byte Description
0 Controller address
1
2
3
Function code
Starting address high
Starting address low
Value
1 to 253
3
See below the description of available registers
4
5
6
7
Number of registers high
Number of registers low
CRC low byte
CRC high byte always 0 max 7Bh (123 decimal)
See below for the checksum calculation
Here is the sequence to read 16 registers starting from address 20h (32 decimal):
01 03 00 20 00 10 45 CC (each byte is expressed as 2 hexadecimal characters)
The checksum value in the above message may be used for the verification of checksum calculation algorithm.
J38D01 - 27 -
2
3
4
5
6
7
Byte
0
1
4
5
6
....
L+1
L+2
1
2
3
The normal response will be:
Byte
0
Description
Controller address
Function code
Data lenght in bytes (L)
High byte of 1st register
Low byte of 1st register
High byte of 2nd register
Low byte of 2nd register
High byte of the last register
Low byte of the last register
Value same as in the query
3 number of registers * 2
L+3
L+4
CRC low byte
CRC high byte
The exceptional response will be:
Byte
0
1
2
3
Description
Controller address
Function code
Exception code
CRC low byte
See below for the checksum calculation
Value same as in the query
131 (function code + 128)
2 (illegal address)
See below for the checksum calculation
4 CRC high byte
Data Writing
The function 06 (write single register) is used for data writing. Only one register can be written at a time.
The MODBUS master will send a query containing data to be written. The answer will be one of the below:
-A normal response confirming successful write,
-An exceptional response indicating a write error.
Only some of the available registers are authorized to be written. An attempt to write a write protected register will result to the exceptional response.
The query message specifies the register address and data. The message structure is below:
Description
Controller address
Function code
Register address high
Register address low
Data high byte
Data low byte
CRC low byte
CRC high byte
Value
1 to 253
6
See below the description of available registers
See below for the checksum calculation
J38D01 - 28 -
Here is the sequence to write the value 0010h to the register 40h (64 decimal):
01 06 00 40 00 10 89 D2 (each byte is expressed as 2 hexadecimal characters)
The checksum value in the above message may be used for the verification of checksum calculation algorithm
The normal response will be the same as the query:
Byte Description Value
0
1
2
3
4
Controller address
Function code
Register address high
Register address low
Data high byte
1 to 253
6
See below the description of available registers
5
6
Data low byte
CRC low byte
7 CRC high byte
The exceptional response will be:
Byte Description
0 Controller address
1
2
Function code
Exception code
3
4
CRC low byte
CRC high byte
See below for the checksum calculation
Value same as in the query
134 (function code + 128)
2 (illegal address) or
10 (write protection)
See below for the checksum calculation
CRC calculation
Here is a procedure for generating a CRC:
1) Load a 16–bit register with FFFF hex (all 1’s). Call this the CRC register.
2) Exclusive OR the first 8–bit byte of the message (the function code byte) with the low– order byte of the 16–bit CRC register, putting the result in the CRC register.
3) Shift the CRC register one bit to the right (toward the LSB), zero–filling the MSB. Extract and examine the LSB. The LSB is the least significant bit of the CRC before the shift operation.
4) If the LSB is 1: Exclusive OR the CRC register with the polynomial value A001 hex.
5) Repeat Steps 3 and 4 until 8 shifts have been performed. Thus, a complete 8–bit byte will be processed.
6) Repeat Steps 2 through 5 for the next 8–bit byte of the message. Continue doing this until all bytes have been processed.
7) The final contents of the CRC register is the CRC value.
8) Place the CRC into the message such that the low byte is transmitted first. The algorithm should give the correct CRC for below messages:
01 03 00 20 00 10 45 CC
01 06 00 40 00 10 89 D2
J38D01 - 29 -
Error codes
Only 3 error codes are used:
01: illegal function code
02: illegal address
10: write protection (attempt to write a read_only register)
Data types
Each register consists of 16 bits (2 bytes)
If the data type is a byte, only the low byte will contain valid data. High byte is don’t care.
For data type longer than 16 bits, consecutive registers are used. The least significant register comes first.
Register definitions
Write single register is only used for changing channel to calculate harmonics. Thus only register 1 is writable.
9.2 MODBUS REGISTERS
ADDRE
SS
40001
NAME
Channel
DESCRIPTION
Channel for harmonic calculation
LENGTH R/W TYPE X
16 BIT R/W unsigned word 1
40002 1. Harmonic 1. harmonic of selected channel (%) 16 BIT R-O unsigned word 0.01
40003 3. Harmonic 3. harmonic of selected channel (%) 16 BIT R-O unsigned word 0.01
40004 5. Harmonic 5. harmonic of selected channel (%) 16 BIT R-O unsigned word 0.01
40005 7. Harmonic 7. harmonic of selected channel (%) 16 BIT R-O unsigned word 0.01
40006 9. Harmonic 9. harmonic of selected channel (%) 16 BIT R-O unsigned word 0.01
40007 11. Harmonic 11. harmonic of selected channel (%) 16 BIT R-O unsigned word 0.01
40008 13. Harmonic 13. harmonic of selected channel (%) 16 BIT R-O unsigned word 0.01
40009 15. Harmonic 15. harmonic of selected channel (%) 16 BIT R-O unsigned word 0.01
40010 17. Harmonic 17. harmonic of selected channel (%) 16 BIT R-O unsigned word 0.01
40011 19. Harmonic 19. harmonic of selected channel (%) 16 BIT R-O unsigned word 0.01
40012 21. Harmonic 21. harmonic of selected channel (%) 16 BIT R-O unsigned word 0.01
40013 23. Harmonic 23. harmonic of selected channel (%) 16 BIT R-O unsigned word 0.01
40014 25. Harmonic 25. harmonic of selected channel (%) 16 BIT R-O unsigned word 0.01
40015 27. Harmonic 27. harmonic of selected channel (%) 16 BIT R-O unsigned word 0.01
40016 29. Harmonic 29. harmonic of selected channel (%) 16 BIT R-O unsigned word 0.01
40017 31. Harmonic 31. harmonic of selected channel (%) 16 BIT R-O unsigned word 0.01
40018 Warnings [1] Warnings Register 1 (See Warnings) 16 BIT R-O unsigned word 1
40019 Warnings [2] Warnings Register 1 (See Warnings) 16 BIT R-O unsigned word 1
40020 Warnings [3] Warnings Register 1 (See Warnings) 16 BIT R-O unsigned word 1
40021 Warnings [4] Warnings Register 1 (See Warnings) 16 BIT R-O unsigned word 1
40022 Warnings [5] Warnings Register 1 (See Warnings) 16 BIT R-O unsigned word 1
J38D01 - 30 -
40046
40047
40048
40049
40050
40051
40052
40053
40038
40039
40040
40041
40042
40043
40044
40045
40030
40031
40032
40033
40034
40035
40036
40037
ADDRE
SS
40023
40024
40025
40026
40027
40028
40029
40054
40055
40056
40057
40058
40059
NAME
V1 RMS
V2 RMS
V3 RMS
I1 RMS
I2 RMS
I3 RMS
V12 RMS
V23 RMS
V31 RMS
S1 Apparent
Power
S2 Apparent
Power
S3 Apparent
Power
∑ S Apparent
Power
P1 Active
Power
Q1 Reactive
Power
P2 Active
Power
Q2 Reactive
Power
P3 Active
Power
Q3 Reactive
Power
DESCRIPTION
V1 phase to neutral voltage AC RMS value
V2 phase to neutral voltage AC RMS value
V3 phase to neutral voltage AC RMS value
I1 current AC RMS value
I2 current AC RMS value
I3 current AC RMS value
U12 phase to phase voltage AC RMS value
U23 phase to phase voltage AC RMS value
U31 phase to phase voltage AC RMS value
Phase 1 apparent power (kVA)
Phase 2 apparent power (kVA)
Phase 3 apparent power (kVA)
Total apparent power (kVA)
Phase 1 active power (kW)
Phase 1 reactive power (kW)
Phase 2 active power (kW)
Phase 2 reactive power (kW)
Phase 3 active power (kW)
Phase 3 reactive power (kW)
LENGTH R/W TYPE
32 BIT
32 BIT
32 BIT
32 BIT
32 BIT
32 BIT
32 BIT
R-O unsigned long
R-O unsigned long
R-O unsigned long
R-O unsigned long
0.1
0.1
0.1
0.1
32 BIT R-O unsigned long 0.1
32 BIT
32 BIT
32 BIT
32 BIT
32 BIT
32 BIT
32 BIT
32 BIT
32 BIT
32 BIT
32 BIT
R-O unsigned long
R-O unsigned long
R-O unsigned long
R-O unsigned long
R-O unsigned long
R-O unsigned long
R-O unsigned long
R-O unsigned long
R-O signed long
R-O signed long
R-O signed long
R-O signed long
R-O signed long
R-O signed long
X
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
J38D01 - 31 -
ADDRE
SS
40060
40061
40062
40063
40064
NAME
∑ P Active
Power
∑ Q Reactive
Power
DESCRIPTION
Total active power (kW)
Total reactive power (kW)
LENGTH R/W TYPE
32 BIT
32 BIT
R-O signed long
R-O signed long
X
0.1
0.1
40065
40066
40067
40068
Cos
Cos
Cos
∑ ф ф ф
Cos
1
2
3 ф
Phase 1 power factor
Phase 2 power factor
Phase 3 power factor
Total power factor
16 BIT
16 BIT
16 BIT
16 BIT
R-O signed word
R-O signed word
R-O signed word
R-O signed word
0.00
1
0.00
1
0.00
1
0.00
1
16 BIT R-O unsigned word 0.01 40069 Frequency
40070
40071
40072 kW Counter 1 Active power counter 1 kVAr Counter
1
Frequency
Reactive power counter 1
40073
40074 kW Counter 2 Active power counter 2
40075
40076
40077 kVAr Counter
2
Reactive power counter 2
40078
40079
40080
User Counter
1
User Counter
2
User Counter 1
User Counter 2
40081
40082
40083
40084
40085
User Counter
3
User Counter
4
User Counter 3
User Counter 4
40086
40087
40088
40089
40090
40091
THD
I1 MAX
I2 MAX
Total harmonic distortion of the selected channel
Phase L1, max current in a month’s period.
I3 MAX
Phase L1, max current in a month’s period.
Phase L1, max current in a month’s period.
40092
40093
40094
P MAX
32 BIT
32 BIT
32 BIT
32 BIT
32 BIT
32 BIT
32 BIT
32 BIT
16 BIT
32 BIT
32 BIT
32 BIT
Max active power in a month’s period. 32 BIT
R-O unsigned long
R-O unsigned long
R-O unsigned long
R-O unsigned long
R-O unsigned long
R-O unsigned long
R-O unsigned long
R-O unsigned long
R-O signed word
R-O unsigned long
R-O unsigned long
R-O unsigned long
R-O unsigned long
0.1
0.1
0.1
0.1
1
1
1
1
0.01
0.1
0.1
0.1
0.1
J38D01 - 32 -
9.3 WARNING REGISTERS
MODBUS warnings register section contains 5 x 16 bit registers, 80 bits in total.
First 40 bits indicate values below set limit, last 40 bits indicate values above set limits.
ADDRESS
REG.
BIT
40018 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
ADDRESS
REG.
BIT
40019 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
5
6
7
8
9
10
11
12
13
14
15
2
3
4
TOTAL
BIT
0
1
TOTAL
BIT
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
DESCRIPTION
V1 RMS value below the set value
V2 RMS value below the set value
V3 RMS value below the set value
I1 RMS value below the set value
I2 RMS value below the set value
I3 RMS value below the set value
U12 RMS value below the set value
U23 RMS value below the set value
U31 RMS value below the set value
Phase 1 active power below the set value
Phase 2 active power below the set value
Phase 3 active power below the set value
Phase 1 reactive power below the set value
Phase 2 reactive power below the set value
Phase 3 reactive power below the set value
Phase 1 apparent power below the set value
DESCRIPTION
Phase 2 apparent power below the set value
Phase 3 apparent power below the set value
Total active power below the set value
Total reactive power below the set value
Total apparent power below the set value
Phase 1 power factor below the set value
Phase 2 power factor below the set value
Phase 3 power factor below the set value
Total power factor below the set value
Frequency below the set value
Active power counter 1 below the set value
Reactive power counter 1 below the set value
Active power counter 2 below the set value
Reactive power counter 2 below the set value
User counter 1 below the set value
User counter 2 below the set value
J38D01 - 33 -
ADDRESS
REG.
BIT
40020 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
ADDRESS
REG.
BIT
40021 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
44
45
46
47
39
40
41
42
43
TOTAL
BIT
32
33
34
35
36
37
38
DESCRIPTION
User counter 3 below the set value
User counter 4 below the set value
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
V1 RMS value above the set value
V2 RMS value above the set value
V3 RMS value above the set value
I1 RMS value above the set value
I2 RMS value above the set value
I3 RMS value above the set value
U12 RMS value above the set value
U23 RMS value above the set value
59
60
61
62
63
53
54
55
56
57
58
TOTAL
BIT
48
49
50
51
52
DESCRIPTION
U31 RMS value above the set value
Phase 1 active power above the set value
Phase 2 active power above the set value
Phase 3 active power above the set value
Phase 1 reactive power above the set value
Phase 2 reactive power above the set value
Phase 3 reactive power above the set value
Phase 1 apparent power above the set value
Phase 2 apparent power above the set value
Phase 3 apparent power above the set value
Total active power above the set value
Total reactive power above the set value
Total apparent power above the set value
Phase 1 power factor above the set value
Phase 2 power factor above the set value
Phase 3 power factor above the set value
J38D01 - 34 -
ADDRESS
REG.
BIT
40022 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
76
77
78
79
71
72
73
74
75
TOTAL
BIT
64
65
66
67
68
69
70
DESCRIPTION
Total power factor above the set value
Frequency above the set value
Active power counter 1 above the set value
Reactive power counter 1 above the set value
Active power counter 2 above the set value
Reactive power counter 2 above the set value
User counter 1 above the set value
User counter 2 above the set value
User counter 3 above the set value
User counter 4 above the set value
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
J38D01 - 35 -
10. TECHNICAL SPECIFICATIONS
Power Supply Input: 170 - 275VAC, 50 - 60Hz nominal (± 10%)
Different AC supply voltages available.
Measurement Input Range:
Voltage inputs: 10 - 300 V AC (L-N)
20 - 520 V AC (L-L)
Current inputs: 0.2 – 5.5 A AC
Frequency:
Accuracy:
30 - 100 Hz
Voltage:
Current:
Frequency:
Power(kW,kVAr):
0.5%+1digit
0.5%+1 digit
0.5%+1 digit
1.0%+2digit
Power factor:
Measurement Range:
2.0%+2digit
CT range: 5 / 5A to 5000 / 5A
VT range: kW range:
1.0
/ 1 to 5000.0
/ 1
1.0 kW to 50.0 MW
Power Consumption: < 4 VA
Voltage burden:
Current burden:
Relay Outputs:
Digital Inputs:
< 0.1VA per phase
< 1VA per phase
5A @ 250VAC
Active level: 5 to 30V-DC or AC
Min pulse duration: 250ms.
Isolation:
Serial Port:
1000V AC, 1 minute
Signal level: RS-485
Communication: Modbus RTU
Data Rate:
Isolation:
Serial port cable:
9600 bauds, no parity, 1 bit stop.
500V AC, 1minute
2 wires twisted, shielded cable. Max 60pF/meter
Operating Temperature: -20°C to +70°C (-4 to +158 ° F).
Maximum humidity: 95% non-condensing.
Degree of Protection: IP 54 (Front Panel) , IP 30 (Back panel)
Enclosure:
Installation:
Dimensions:
Non-flammable, ROHS compliant, ABS/PC (UL94-V0)
Flush mounting with rear retaining brackets
Panel Cutout:
Weight:
102x102x53mm (WxHxD)
92x92mm
350 gr
EU Directives Conformity:
2006/95/EC (low voltage)
2004/108/EC (EMC)
PACKAGING INFORMATION
Pieces per Package:
Package Size:
Package Weight:
Norms of reference:
EN 61010 (safety requirements)
EN 61326 (EMC requirements)
12 pieces
280 x 170 x 215mm (LxWxH)
4.4 kg
J38D01 - 36 -
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement