advertisement
Allen-Bradley
Bulletin 1203
Remote I/O
Communications
Module
Catalog Numbers
1203-GD1
1203-GK1
1336-GM1
Getting
Started
Manual
Important User
Information
Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.
The illustrations shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the
Application, Installation, and Maintenance of Solid-State Control
(available from your local Allen-Bradley office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or in part, without written permission of Allen-Bradley
Company, Inc., is prohibited.
Throughout this manual we use notes to make you aware of safety considerations:
!
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage or economic loss.
Attention statements help you to:
• identify a hazard
• avoid the hazard
• recognize the consequences
Important: Identifies information that is critical for successful application and understanding of the product.
PLC, PLC–2, PLC–3, and PLC–5 are registered trademarks of Allen–Bradley Company, Inc.
PLC–2/30, PLC–5/10, PLC–5/15, PLC–5/25, PLC–5/30, PLC–5/40, PLC–5/40L, PLC–5/60L, and PLC–5/250 are trademarks of Allen–Bradley Company, Inc.
SCANport is a registered trademark of Allen–Bradley Company, Inc.
SLC 500, SLC–5/02, and PLC–5/15 are registered trademarks of Allen–Bradley Company, Inc.
DH+ is a registered trademark of Allen–Bradley Company, Inc.
Summary of Changes
Summary of Changes
We would like to call your attention to the following changes to the
1203-5.1 manual which have occurred since the previous version published in April, 1996. All references to page, table, and figure numbers refer to the December publication. Page, table, and figure numbers in the July, 1997 publication may not match the page, table, and figure number references mentioned here due to omissions or inclusions and, likewise, text and graphics shifting somewhat from page to page.
•
Page 1–1 was updated to include the 1336 IMPACT and 1397 drives.
•
Figure 1.1 was changed to reflect a change in LED colors.
•
Figure 1.2 was changed to reflect a change in LED colors.
•
Figure 4.1 was changed to reflect a change in LED colors.
•
Table 4.A was changed to reflect a change in LED colors.
•
Table 5.A was changed to identify the column headings more clearly.
Publication 1203–5.1 – July, 1997
soc–ii Summary of Changes
Publication 1203–5.1 – July, 1997
Overview
Installation
Configuration and
Interfacing
Table of Contents
Preface
Who Should Use this Manual?
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Purpose of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Firmware Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PLC Product Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terms and Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Common Techniques Used in this Manual
Allen–Bradley Support
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Local Product Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Product Assistance . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 1
Chapter Objectives
Adapter Description
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SCANport Device Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuration Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Datalinks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 2
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting the Module Configuration Switches
Switch SW3
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Switch SW2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Switch SW1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting the Remote I/O Module . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the Remote I/O Cable . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the Termination Resistor
Connecting the SCANport Link
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
1305 Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1336 PLUS (7.5 – 500HP) and 1336 FORCE
SMP 3
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SMC Dialog Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 3
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Programmable Controller Data Table Use . . . . . . . . . . . . . . . . . . .
Data Transfer Through the Communications Module . . . . . . . . . . . .
ii
Troubleshooting
Specifications
Chapter 4
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 5
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Product Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Programmable Controller Compatibility . . . . . . . . . . . . . . . . . . . . .
Publication 1203–5.1 – July, 1997
Preface
Preface
Who Should Use this
Manual?
Purpose of this Manual
Read this preface to familiarize yourself with the rest of the manual.
This preface covers the following topics:
• who should use this manual
• the purpose of this manual
• safety precautions
• firmware support
• product compatibility
• terms and abbreviations
• conventions used in this manual
•
Allen–Bradley support
Use this manual if you are responsible for designing, installing, programming, or troubleshooting control systems that use the
Bulletin 1203 remote I/O communications module. You must have previous experience with and a basic understanding of electrical terminology, configuration procedures, required equipment, and safety precautions.
To efficiently use this communications module, you must be able to program and operate an Allen-Bradley programmable controller. In particular, you must be familiar with remote I/O concepts and configuration and be able to program block transfer instructions.
This manual provides you with the information you need to apply the remote I/O communications module that is available for products that include the SCANport t
communications port. This manual describes the procedures for installing, configuring, and troubleshooting the remote I/O communications module. Block transfer instructions are explained in a separate software programming manual.
For information on specific product features, refer to the product manual.
Important: Read this manual in its entirety before installing, operating, servicing, or initializing the remote I/O communications module.
Publication 1203–5.1 –– July, 1997
P–2 Preface
Safety Precautions
Contents of this Manual
This manual contains the following information:
Chapter:
Preface
Title:
1
2
3
4
5
Overview
Installation
Configuration and
Interfacing
Troubleshooting
Specifications
Contents:
Describes the purpose, background, and scope of this manual as well as an overview of this product.
Provides an overview of the adapter features, configuration information, and diagnostic information.
Provides the procedures you need to mount the Bulletin
1203 remote I/O communications module, connect the power, and configure the switches, as well as providing cabling and hardware information.
Provides information such as addressing, information transfer, and sample programs.
Provides information about the LED indications and fault descriptions.
Provides the environmental, electrical, and communications specifications.
Please read the following safety precautions carefully.
!
ATTENTION: Only personnel familiar with
SCANport devices and the associated machinery should plan or implement the installation, start-up, configuration, and subsequent maintenance of this remote I/O communications module. Failure to comply may result in personal injury and/or equipment damage.
Firmware Support
!
ATTENTION: This module contains ESD
(Electrostatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing, or repairing this assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, reference
Allen-Bradley Publication 8000-4.5.2, Guarding
against Electrostatic Damage, or any other applicable
ESD protection handbook.
This manual supports communication module firmware versions
1.xx and 2.xx (the xx designator may vary). Features that work with specific firmware versions will be denoted as such.
Publication 1203–5.1 –– July, 1997
Preface P–3
PLC Product Compatibility
"
This adapter is designed to be used with the following Allen-Bradley programmable controllers:
•
PLC-2/30
with SD2 (communications module version 1.02 or later)
•
PLC-3
•
SLC 500 t with 1747-SN scanner
•
PLC-5/10 t
, PLC-5/15 t
, PLC-5/25 t
family
•
PLC-5/30 t
, PLC-5/40 t
, PLC-5/40L t
, PLC-5/60 t
,
PLC-5/60L t family, PLC-5/80 t
•
PLC5/250 t
•
PLC
scanner modules and subscanners.
This adapter was tested with the current revision level of the PLC processors listed. Earlier versions of the processors may not be compatible.
Terms and Abbreviations
The following terms and abbreviations are specific to this product.
For a complete listing of Allen–Bradley terminology, refer to the
Allen–Bradley Industrial Automation Glossary.
In this manual, we refer to the:
• remote I/O communications module as communications module
• variable frequency ac drive (1305, 1336 FORCE, or 1336 PLUS) as the drive or SCANport device
•
The programmable logic controller as the programmable controller
•
Allen–Bradley remote input/output network as remote I/O
• earth ground as Gnd
Common Techniques Used in this Manual
"
The following conventions are used throughout this manual:
•
Bulleted lists provide information, not procedural steps.
•
Numbered lists provide sequential steps or hierarchical information.
•
Italic type is used for emphasis and chapter names.
We also use this convention to call attention to helpful information.
Publication 1203–5.1 –– July, 1997
P–4 Preface
Allen–Bradley Support
Allen–Bradley offers support services worldwide, with over 75
Sales/Support Offices, 512 authorized Distributors and 260 authorized Systems Integrators located throughout the United States alone, plus Allen–Bradley representatives in every major country in the world.
Local Product Support
Contact your local Allen–Bradley representative for:
• sales and order support
• product technical training
• warranty support
• support service agreements
Technical Product Assistance
If you need to contact Allen–Bradley for technical assistance, please review the information in the Troubleshooting chapter first. If you are still having problems, then call your local Allen–Bradley representative.
Publication 1203–5.1 –– July, 1997
Chapter Objectives
Adapter Description
SCANport Device
Compatibility
Chapter
1
Overview
Chapter 1 covers the following information:
• a description of the communications module
•
SCANport device compatibility
• configuration switches
• datalinks
• safety precautions
The remote I/O communications module is an optional interface device designed to provide a direct, digital link between an
Allen-Bradley programmable controller and any device that uses the
SCANport t
communication port. The current list of products that use the SCANport communications interface includes: 1305, 1336
PLUS, 1336 FORCE, 1336 IMPACT, 1397, and SMP3 and SMC
Dialog Plus. The board connects to these products through the
SCANport peripheral interface.
The adapter is available in both Open style (Figure 1.1) and Enclosed
(Figure 1.2) type configurations. The Open style module mounts inside certain drives, depending on drive size (refer to Table 1.A).
You can use the Enclosed module with any compatible SCANport device that is mounted outside the drive package.
Table 1.A Remote I/O Configurations
Designation Enclosure Power Supply Source
Open Style Open PC board Supplied by drive
Enclosed IP30
24V ac/dc separately supplied or
120/240V ac separately supplied
Used With
1336 PLUS
➀
1336 FORCE
➁
1305
1336 PLUS
1336 FORCE
SMP3
SMC Dialog Plus
Other SCANport products
➀
7.5 hp and higher sizes only
➁
7.5 hp and higher sizes with standard adapter board only
The remote I/O communications module does not support version
1.xx (the .xx designator may vary) of the 1305 drive. If you try to use the remote I/O communications module with a version 1.xx
1305, the remote I/O communications module will continually reset itself, resulting in the red adapter fault status LED and the amber
SCANport status LED both flashing simultaneously indicating an error condition. Firmware revision 2.xx or higher on the 1305 is required to support remote I/O communications and block transfer.
Publication 1203–5.1 –– July, 1997
1–2 Overview
Adapter Health
(Green)
SCANport Status
(Green)
Figure 1.1
Open Style Communications Module
Block Transfer Enable
Logic Command / Status Enable
Analog Reference / Feedback Enable
Datalink A-D enable
Truncate last datalink
Adapter Fault
Status (Red)
Starting Quarter
Baud Rate
Rack Fault
Hold Last State
Last Rack
Rack Address
8 SW3 1 8 SW2 1 8 SW1 1
Remote I/O Active
(Green)
J4
Front View
Remote I/O Status
(Green)
Remote I/O Connector
Publication 1203–5.1 –– July, 1997
Overview 1–3
Figure 1.2
Enclosed Style Communications Module
SCANport
Communication
Cable Connector
. . .
Connect
Power Supply Here
Front View
Switch SW3
– Block Transfer Enable
– Logic Command/
Status Enable
– Analog Reference/
Feedback Enable
– Datalink A-D enable
– Truncate last datalink
Switch SW1
– Rack Address
8 SW3 1 8 SW2 1 8 SW1 1
Remote I/O
Connector
Remote I/O Status (Green)
Remote I/O Active (Green)
Adapter Health (Green)
SCANport Status (Green)
Adapter Fault Status (Red)
Switch SW2
– Starting Quarter
– Baud Rate
– Rack Fault
– Hold Last State
– Starting Quarter
Bottom View
Publication 1203–5.1 –– July, 1997
1–4 Overview
Figure 1.3
Typical Programmable Controller/SCANport Device Interconnection
PLC
.
..
Open Style
RIO
Adapter
1336 PLUS
.
1305*
Micro
Drive
SCANport
Communications
Module
Remote I/O Link
Panel View Operator Terminal
ÁÁÁ
ÁÁÁ
ÀÀ
ÀÀ
Communications
Module
Communications
Module
SMC Dialog Plus
SMP 3
SCANport
Other Remote I/O Devices
*NOTE: Refer to Page 1–1 for compatibility requirements of SCANport devices
Publication 1203–5.1 –– July, 1997
Configuration Switches
Overview 1–5
The remote I/O communications module contains three DIP switches
SW1, SW2, and SW3 (Figure 1.1 and Figure 1.2). Switches are set
On or Off as detailed in Figure 1.4. For a detailed explanation of switch configuration, refer to Chapter 2, Installation.
Figure 1.4
Configuration Switch
OPEN
8 7 6 5 4 3 2 1
Rocker Switch
Open
Side View of Typical Switches
Slide Switch
Open
Open (Off)
Open Open
Closed (On)
Switch Designation as shown in this manual
OFF (OPEN)
ON
Datalinks
Datalinks are a SCANport mechanism for transferring additional information between a programmable controller and a SCANport device. Each datalink switch on the adapter reserves two words of the programmable controller I/O image table. The 1305, 1336
PLUS, and 1336 FORCE drives support this mechanism. For additional details, refer to Chapter 3, Configuration and Interfacing.
Publication 1203–5.1 –– July, 1997
1–6 Overview
Safety Precautions
Please read the following safety precautions.
!
ATTENTION: This board contains ESD
(Electrostatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing, or repairing this assembly. Component damage may result if you do not follow ESD control procedures. If you are not familiar with static control procedures, refer to Allen-Bradley publication 8000-4.5.2, Guarding Against Electrostatic
Damage, or any other applicable ESD Protection
Handbook.
!
ATTENTION: Servicing or configuring the RIO boards on drives larger than 3hp involves opening the
1336 drive cabinet which creates the potential to come in contact with other drive components. Energized industrial control equipment can be hazardous. Severe injury or death can result from electrical shock, burn, or unintended actuation of controlled equipment.
Recommended practice is to disconnect and lock out all control equipment from power sources, and allow stored energy in any capacitors to dissipate. If you must work near energized equipment, you must follow the safety related work practices of NFPA 70E,
Electrical Safety Requirements for Employee
Workplaces.
Publication 1203–5.1 –– July, 1997
Chapter Objectives
Setting the Module
Configuration Switches
Chapter
2
Installation
Chapter 2 provides information to help you:
• set the module configuration switches
• mount the remote I/O module
• connect the remote I/O cable
• connect the termination resistor
• connect the SCANport link
• connect the power supply
Read this chapter completely before you attempt to install or configure your remote I/O communications module. Double check all connections and option selections before you apply power.
Important: Switch selections take effect only on power–up. If you change selections after power is applied, cycle the power to use the new settings.
This publication describes switches as being either on or off. If the switch assembly has the word OPEN printed on it, the word OPEN corresponds to OFF (O).
When you change the adapter board configurations, keep in mind the addressing conventions of the type of processor that you are using. In all cases, each remote I/O device must have a unique address that the processor can recognize.
Important: This adapter is not compatible with complementary I/O configurations because the adapter uses both output and input image words for proper drive control.
!
ATTENTION: When you make changes to the switch settings, use a blunt, pointed instrument such as a ball point pen. Do not use a pencil because the lead
(graphite) of the pencil may damage the switch assembly.
ATTENTION: Failure to check connections and switch settings for compatibility with your application when configuring the communications module, could result in personal injury and/or equipment damage due to unintended or undesirable operation of the drive or process equipment.
Publication 1203–5.1 –– July, 1997
2–2 Installation
Switch SW3
"
Set switch SW3 first. The settings on this switch determine how the
SCANport device uses the data contained in the programmable controller I/O image table. SW3 also establishes the minimum rack size that this communications module requires.
The switches are labeled in the same orientation as they appear on the board.
Table 2.A, SW3 Image Table Map, and Figure 2.2, SW3 Flowchart, are included to help you set the DIP switches properly. It may also be helpful to color in the final switch settings in Figure 2.1 as a visual record of your SW3 settings. Chapter 3 contains several examples of how to fill in the worksheet and set these DIP switches.
Figure 2.1
Configuration Switch SW3 Settings
Open Style
Enclosed Style
J1
SW3
OPEN
8 7 6 5 4 3 2 1
Off (Open)
On
Truncate
➀➁
Last Datalink
Datalink D
Transfers
Datalink C
Transfers
Datalink B
Transfers
Off Off Off Off
Datalink A
Transfers
Off
Reference/
Feedback
Off
Logic
Command/Status
Block
Transfer
Off Not
Enabled
Off
On On On On On On On
➀
IMPORTANT: Only available on communications modules with version 1.02 or later firmware.
➁
All datalinks are two words, the truncate function will delete the last datalink word. (If “Datalink B” is the last used,
“Data in B2” and “Data Out B2” will be truncated.)
Enabled On
Publication 1203–5.1 –– July, 1997
Installation
Table 2.A
SW3 Image Table Map
RESERVED FOR:
Output Image Input Image
Minimum
R i
Rack Size
➀ G p
2–3
➀
Use this to select settings for switch SW2, switches 1 and 2
How to use Table 2.A:
1. Use Figure 2.2 to set DIP switch SW3 and fill out Table 2.A.
2. Use minimum rack size shown in Table 2.A to set DIP switch
SW2-1 and SW2-2.
Figure 2.2
SW3 Flowchart
Step 1. Block Transfer
Will block transfer or block transfer RIO pass thru be used?
NO
YES
1. Write “Block Transfer” in word 0 of both the input and the output image
2. Set SW 3-1 to on
Step 2. Logic Command
Will the SCANport device be controlled by (Start/Stop etc.) or will the Logic Status by monitored by the PLC?
YES
NO
1. Write “Logic Cmd” in the output image and “Logic
Status” in the input image of the next available word
2. Set SW3-2 to on
Step 3. Reference/Feedback
Will a reference or feedback be provided
from/to the programmable controller?
YES
1. Write “Reference” in the output image and
“Feedback” in the input image of the next available word
2. Set SW3-3 to on
NO
1. Set SW3-1 to off
2. Move to step 2
NOTE: For detailed information on block transfer messages refer to the 1203-5.0 Reference Manual.
1. Set SW3-2 to off
2. Move to step 3
1. Set SW3-3 to off
2. Move to step 4
Publication 1203–5.1 –– July, 1997
2–4 Installation
Figure 2.2
SW3 Flowchart continued
Step 4. Datalink A Transfer
Will Datalink Group A be used?
YES
1. Write “Datalink A” in the output and input image of the next two available words
2. Set SW3-4 to on
NO
Step 5. Datalink B Transfer
Will Datalink Group B be used?
YES
1. Write “Datalink B“ in the output and input image of the next two available words
2. Set SW3-5 to on
Step 6. Datalink C Transfer
Will Datalink Group C be used?
YES
1. Write “Datalink C” in the output and input image of the next two available words
2. Set SW3-6 to on
Step 7. Datalink D Transfer
Will Datalink Group D be used?
YES
1. Write “Datalink D” in the output and input image of the next two available words
2. Set SW3-7 to on
Step 8. Truncate Last Datalink
Will the last Datalink be one word
(truncate last Datalink) ?
YES
1. Cross out the last word of the last Datalink group used in the output and input image table
2. Set SW3-8 to on
NO
NO
NO
NO
Step 9. Calculate minimum rack size
Refer to Table 2.A on page page 2–3.
1.
Record the minimum rack size in Table 2.A on page 2–3.
2.
Use the minimum rack size to set Dip switches SW2-1 and SW2-2.
1. Set SW3-4 to off
2. Move to step 5
1. Set SW3-5 to off
2. Move to step 6
1. Set SW3-6 to off
2. Move to step 7
1. Set SW3-7 to off
2. Move to step 8
1. Set SW3-8 to off
2. Move to step 9
Publication 1203–5.1 –– July, 1997
Installation 2–5
"
Switch SW2
Switch SW2 determines Rack Size, Last State, Rack Fault, and Bit
Rate Selections as shown in Figure 2.3.
The switches are labeled in the same orientation as they appear on the board.
Figure 2.3
Configuration Switch SW2 Settings
J1
Open Style
SW2
OPEN
8 7 6 5 4 3 2 1
Enclosed Style
OFF (OPEN)
ON
RIO Baud Rate Reset/
Program/
Test
➂ ➄
Communications
Loss
➅
Hold
Last
State
➄ ➅
Last
Rack
Setting
➃
Starting Module Group ➁
57.6
kbps
115.2
kbps
230.4
kbps
Off
Off
On
Off
On
Off
➀
If this switch is set to No Fault, the setting of the Hold Last State switch determines the data sent to the SCANport device when the
PLC is in Reset/Program/Test.
Fault
Drive
On
Fault on
Comm
Loss
On
Off
No
Fault
➀
Off
No
Fault
Zero
Image on PLC
Fault
On
Run at
Last State
Off
Last
Rack On
0
On
Off
On
Not–
Last
Rack
Off
2
On
Off
4
On
➄
Refer to Figure 2.4.
➅
Refer to Figure 2.5
and Figure 2.6.
Off Off
6
➁
The setting of this switch is determined by the amount of discrete I/O that will be passed between the PLC and the drive.
Refer to Table 2.A for more information.
➂
This switch is active on
Firmware Version 2.xx
modules only. It is not used by modules containing Firmware
Version 1.xx.
➃
Set this switch on the last module used for a given rack address. It does not electrically terminate the RIO link.
Publication 1203–5.1 –– July, 1997
2–6 Installation
Communications loss
Off
Hold last state
Off
Send the last command to the drive
Figure 2.4
PLC Switched to Program
On
Fault drive in program set
Off
Hold last state
Off
Send command on to the drive
On
Figure 2.5
SCANport Cable Unplugged
On
Communications loss
Off
Hold last state
Off
Send the last image of the drive status to the PLC
On
Figure 2.6
RIO Cable Disconnected
On
On
Generate a drive communications loss fault
Send a 0 command to the drive
Stop responding to the PLC.
The PLC generates a rack fault
Send a value of 0 to the
PLC for the drive status
Generate a drive communications loss fault
Send zero images to the drive.
Publication 1203–5.1 –– July, 1997
Installation 2–7
"
Switch SW1
Switch SW1 controls starting quarter and rack address options as shown in Figure 2–7.
Note: When using a PLC-2 family processor, you need to offset the value of the rack number by one. The PLC-2 cannot have a remote
I/O rack numbered zero. Therefore, add a value of one to the Rack
No value in Table 2.B when writing your PLC code.
Figure 2.7
Configuration Switch SW1 Settings
J1
Open Style
SW1
OPEN
8 7 6 5 4 3 2 1
Not Used
Rack Addressing (See Table 2.B.)
Enclosed Style
Off (Open)
On
Publication 1203–5.1 –– July, 1997
2–8 Installation
Rack No.
22
23
24
25
26
15
16
17
20
21
06
07
10
11
12
13
14
00
01
02
03
04
05
27
30
31
32
33
34
35
36
37
Table 2.B
Switch SW1 Settings
SW1-8 through SW1-1 DIP Switch Definitions, Rack Address
SW1-3
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
SW1-4
Off
Off
Off
Off
Off
On
On
On
Off
Off
On
On
On
On
On
On
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
SW1-5
On
On
On
On
On
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
Off
On
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
SW1-6
On
Off
Off
Off
Off
On
On
Off
On
On
On
On
On
On
On
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
On
On
Off
Off
Off
SW1-8
On
Off
On
Off
On
On
Off
On
Off
Off
On
Off
On
Off
On
Off
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
SW1-7
Off
Off
On
On
Off
On
Off
Off
On
On
On
On
Off
Off
On
On
On
Off
Off
Off
On
On
Off
Off
On
On
Off
Off
On
On
Off
Off
SW1-2 SW1-1 not used not used not used not used not used not used not used not used not used not used not used not used not used not used not used not used not used not used not used not used not used not used not used not used not used not used not used not used not used not used not used not used
Publication 1203–5.1 –– July, 1997
Mounting the Remote I/O
Module
Installation 2–9
The remote I/O communications module can be provided in three mounting configurations:
•
Open Style board factory installed in a drive (not available for all drives)
•
Open Style board as a separate kit
•
Enclosed style for panel mount or DIN rail mount
This section provides mounting information for the Enclosed style and the Open style kit.
Figure 2.8
Open Style Communications Module Mounting Location (1336 Plus
7.5–500HP)
1336 PLUS Main Control Board
Open Communications Module
Mounts Here
J1
Mounting Screws & Standoffs Qty 4
U44
J3
Memory
Module
SCANport 6
Human Interface
Module
U50 U54 U56
J4
L OPTION
J7
J9
TB1
TB2
"
Install the board with the component side facing you.
Publication 1203–5.1 –– July, 1997
2–10 Installation
Figure 2.9
Open Style Communications Module Mounting Location (1336
FORCE Drive)
1336 FORCE Main Control Board
Open Communications Module
Mounts Here
J1
1336 FORCE Standard Adapter Board
J4
SCANport 6
L OPTION
Mounting Screws & Standoffs Qty 4
TB2
"
Install the board with the component side facing you.
Publication 1203–5.1 –– July, 1997
Side View
123 mm
(4.8)
Installation
Figure 2.10
Enclosed Style Communications Module Dimensions
2–11
Back View
ÉÉ
ÉÉ
DIN RAIL
ÉÉ
ÉÉ
ÉÉ
ÍÍÍÍ
ÍÍÍÍ 70 mm
(2.7)
ÍÍÍÍ
ÍÍÍÍ
ÍÍÍÍ
ÉÉÉÉ
ÉÉÉÉ
DIN
RAIL
ÉÉÉÉ
ÉÉÉÉ
ÉÉÉÉ
ÉÉÉÉ
ÉÉÉÉ
Top View
44 mm
(1.75)
DIN RAI L
ÉÉÉÉ ÉÉÉÉ
ÉÉÉÉ
ÉÉÉÉ
ÉÉÉÉ 76 mm
(3.0)
ÉÉÉÉ
ÉÉÉÉ
ÉÉÉÉ
Front View
45 mm
(1.8)
DIN rail mounting
clip
25 mm
(1)
ÉÉÉÉ
ÉÉÉÉ
DIN
RAIL
ÉÉÉÉ
ÉÉÉÉ
ÉÉÉÉ
45mm
(1.8)
25 mm
(1)
Note: The enclosure requires clearance at the top and bottom for proper cooling. Additional space will be required if access to DIP switches is desired without having to remove the device.
All dimensions in millimeters and (inches)
Publication 1203–5.1 –– July, 1997
2–12 Installation
Connecting the Remote I/O
Cable
Blue
Shield
ÉÉÉ
Clear
1
SH
2
REM
I/O
You must connect remote I/O communications module cables as shown in the example in Figure 2.11. Refer to Table 2.C for cable guidelines.
Figure 2.11
Remote I/O Module Interconnections
PLC
..
.
Enclosed
Communication Module
J4
2
SH
Clear
Shield
ÉÉÉ 1 Blue
1336 Plus
Open Style
Communication
Module
.
Blue
Shield
ÉÉÉ
Clear
J4
1
SH
2
Publication 1203–5.1 –– July, 1997
Installation 2–13
Twinaxial cable used for remote I/O (RIO) and Data Highway+
(DH+ TM ) communications represents a communications transmission line in which certain characteristics exist. The following are some general guidelines that must be adhered to in order to obtain the best results.
Cable Type – Only 1770-CD Belden #9463 is approved for RIO and
DH+ installations. All other cable types or manufacturers, no matter how similar, are untested. Using other cable types is strictly at your own risk.
Important: The transmission rate determines the maximum cable length.
Table 2.C
Twinaxial Cable Guidelines
Remote I/O link communications rate
57.6 kbps
115.2 kbps
230.4 kbps
Cable length cannot exceed:
3,048 m (10,000 ft)
1,524 m (5,000 ft)
762 m (2,500 ft)
Connections – Connect all three conductors, blue, clear, and shield, at each wiring point. No additional ground connections should be made to the shield.
Important: DO NOT use star type connections. Only two cables may be connected at any wiring point on a series connection application.
OK
"
These are general rules and certain deviations may be warranted because diverse installation and environmental concerns could change the requirements.
Publication 1203–5.1 –– July, 1997
2–14 Installation
Connecting the
Termination Resistor
You must terminate both ends of a remote I/O link to ensure proper operation. This termination is required only at the ends of the physical cable. Each remote I/O network should have exactly two termination resistors installed. Use Table 2.D and Figure 2.12 and
Figure 2.13 to determine the proper termination for your particular link. Termination resistor R3 is located on the board, and the J2 jumper selects this resistor.
Table 2.D
Termination Resistor Requirements
If this device is an end device of a remote I/O link:
Programmable controller
Open style, single point remote I/O adapter
Enclosed style single point remote I/O adapter
Terminate the link by:
Refer to the manual for your model processor.
Set jumper J2 in position 1–2 for termination and 2–3 for no termination as shown in Figure 2.12. The jumper enables a 150 ohm resistor as the terminator resistor.
Connect a terminator resistor between the remote I/O terminals labeled 1 and 2 as shown in Figure 2.13.
Use either a 150 Ohm or an 82 Ohm terminator.
•
You must use an 82 Ohm resistor if the remote I/O link is operating at 230.4 kbps (terminator must be connected at both the scanner and the adapter).
•
You should use an 82 Ohm resistor if the remote I/O link is operating at 57.6 kbps or 115.2 kbps unless one of the devices on the link is listed in Table 2.E. If you are using a device listed in Table 2.E, then you must use a 150 Ohm terminator.
Important: The following products (Table 2.E) cannot be on a link using 82-Ohm termination resistors.
Table 2.E
Unsupported Remote I/O Link Devices
Device Type
Scanners
Adapters
Miscellaneous
Catalog Number
1771-SN
1772-SD, -SD2
1775-SR
1775-S4A, -S4B
6008-SQH1, -SQH2
1771-AS
1772-ASB
1771-DCM
1771-AF
Series
All
All
A
All
All
Publication 1203–5.1 –– July, 1997
Installation
Figure 2.12
Terminating a Remote I/O Link Using the Module Mounted Resistor
2–15
Blue
Shield
ÉÉ
Clear
J4
1
SH
2
J5
J2
3 2 1
T1
Not Last Rack
(Factory Default)
Last Rack,
Termination
Resistor Inserted
Enables 150 ohm
Termination Resistor
3 2 1
3 2 1
Enclosed
Remote I/O Module
Figure 2.13
Terminating a Remote I/O Link Using an External Resistor
To
Another Remote I/O
Link Device
Clear
Shield
Remote I/O Module
2
Sh
1
I50 Ohm or
82 Ohm
1 watt,
±
10%
Publication 1203–5.1 –– July, 1997
2–16
Connecting the SCANport
Link
Installation
SCANport cables are available in either Male–to– Male or
Male–to–Female configuration. You can connect cables of up to 10 meters (33 feet) from the master to the SCANport device (A in
Figure 2.14). If you use a port expander as shown in Figure 2.14, subtract the cable length from the master to the port expander from the cable length used to connect the device to the expander (B1+ C = maximum 10 meters).
A
Optional
Male–Female
Cable
1305 Drive
An Allen-Bradley SCANport link cable is used to make the connection between the communications module and the drive
(Figure 2.14).
Figure 2.14
SCANport connection on Remote I/O
1305 Drive
Port 1
Port 2
C
B1
Port Expander
2 3 4 5
Optional
Male–Male Cable
B2
Human Interface Module
Remote I/O
Communication Module
Remote I/O
Communication Module
Important: The maximum cable distance between any two master devices cannot exceed 10 meters (33 feet) of cable. For example, B1 + C = maximum of 10 meters or B1 + B2
= maximum of 10 meters.
1336 PLUS (7.5 – 500HP) and 1336 FORCE
Refer to the product manual for connection information. On larger horsepower 1336 PLUS and 1336 FORCE drives with an open remote I/O module mounted in the drive, you do not need a separate
SCANport cable connection.
Publication 1203–5.1 –– July, 1997
Installation 2–17
SMP 3
An Allen-Bradley SCANport cable is used to connect the communications adapter and an SMP 3. See the cable requirements on page 2–16 for details on cable length.
Figure 2.15
SCANport connection on Remote I/O
RESET
SCANport
Remote
Reset
SMP 3 Enclosed
Adapter
AB0538A
SMC Dialog Plus
An Allen-Bradley Bulletin 1202 SCANport cable is required to connect the communications adapter and the SMC Dialog Plus controller.
Figure 2.16
SCANport connection on Remote I/O
Allen-Bradley SMC Dialog Plus
ESC SEL
SMC Dialog Plus
Enclosed
Adapter
SCANport
AB0537A
Publication 1203–5.1 –– July, 1997
2–18 Installation
Connecting the Power
Supply
The Enclosed remote I/O is powered from a separate 24V dc or
115V ac power supply (Figure 2.17). With the open style remote I/O board mounted in the drive, no separate power supply connections are required.
Figure 2.17
Typical Power Supply Connection
115/230V
Typical Connection
115V AC Hi
115V AC Low
GND
L
N
G
Enclosed Remote I/O
Communication Module
24V DC
Typical Connection
24V DC +
Power
Supply –
+
–
G
GND
Enclosed Remote I/O
Communication Module
Publication 1203–5.1 –– July, 1997
Chapter Objectives
Programmable Controller
Data Table Use
Chapter
3
Configuration and Interfacing
Chapter 3 provides information on how the remote I/O communications module and a programmable controller communicate. The following topics are covered:
• programmable controller data table use
• data transfer through the adapter
Important: Block transfer messaging is covered in a separate publication.
!
ATTENTION: When you configure a system for the first time, disconnect the motor from the machine or process during the initial testing.
The remote I/O communications module allows a SCANport device to look and act like a remote I/O chassis when connected to a programmable controller. Data contained in the input/output image table is transferred between the programmable controller by the remote I/O scanner, the same as with any remote I/O chassis. You control the location and amount of data transferred by setting the rack address and starting quarter/rack size DIP switches on the remote I/O communication module.
Figure 3.1 shows a typical example of data transfer between a programmable controller, the remote I/O communications module, and a 1336 PLUS drive. This same concept works for all SCANport devices. In this example, assume that you have set the DIP switches for rack address 2, a rack size of 1/4 (or greater if larger amounts of data are to be transferred), and has enabled (Set) the Logic
Command/Status switch.
Data placed in the output image table area for rack address 2 is transferred to the remote I/O communications module every rack scan. The communications module then transfers the data to the 1336
PLUS drive as Logic Command. Logic status data is transferred from the drive to the remote I/O communications module and then passed to the programmable controller during a rack scan.
!
ATTENTION: The RIO to SCANport conversion is asynchronous. Any data sent to the adapter for transfer to the drive must be maintained until the drive has received the data.
Publication 1203–5.1 –– July, 1997
3–2
Enabled
Running
Cmd Direction
Actual
Direction
Accelerating
Decelerating
Alarm
Faulted
At Speed
Local
Local
Local
Ref Select
Ref Select
Ref Select
Ref Select
00
01
02
03
04
05
06
07
10
11
12
13
14
15
16
17
00
01
05
06
07
10
02
03
04
11
12
13
14
15
16
17
Stop
Start
Jog
Clear Faults
Direction
Direction
Local
Mop Increment
Accel Time
Accel Time
Decel Time
Decel Time
Ref Select
Ref Select
Ref Select
MOP Decrement
Configuration and Interfacing
Figure 3.1
Typical Example of Data Transfer Through the Communications Module
Programmable Controller
I/O Image Table
Rack 2
Output Image
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Word 6
Word 7
Remote I/O
Communications
Module
1336 PLUS
Drive
Rack 2
Input Image
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Word 6
Word 7
Remote I/O
Logic Command/
Status Enabled
SCANport
Logic Command
Logic Status
"
This is a typical example of data transfer from a PLC to a 1336
PLUS drive. Refer to the manual provided with your
SCANport–compatible product for actual Control and Status words.
Important: The communications module does not scale the data that is transferred. If data in the programmable controller is manipulated in units other than device units, the data must first be converted before being sent to the device. Consequently, all scaling of the data must be done in the PLC. Refer to the appropriate SCANport device manual for details on device units.
Publication 1203–5.1 –– July, 1997
Data Transfer Through the
Communications Module
Configuration and Interfacing 3–3
DIP switch SW3 determines how the data contained in the programmable controller I/O image table is used in the drive (Figure
3.2). The first three switches (1 through 3) select the basic control features. Switches 4 through 7 support additional capability to transfer selected parameter information between the drive and the programmable controller. Products that have this capability have a group of parameters for adapter I/O. These parameters are identified as “Data In” and “Data Out” parameters. Each datalink switch on the adapter consumes two words (unless truncated using SW3–8) in both the input and output image table of the programmable controller.
The following are the rules for using datalink switches:
1. Normally, each datalink switch reserves two words in both the input and output image tables of the programmable controller.
The starting module group/rack size switch (SW2, 1-2) on the adapter must be set to support this.
2. The truncate last datalink switch truncates the last datalink to one word in the input and output image table, instead of two. You can use this to minimize the required rack size consumed by a communications module.
3. Each set of datalink parameters in the drive can only be used by one remote I/O communications module. If more than one module is connected to a single SCANport link, the switch settings must not conflict.
4. Parameter setting in the drive determine the data passed through the datalink mechanism. Refer to the “Adapter I/O” group in the drive manual for details.
Table 3.A
Datalink Switch SW3 Settings
SW3 switch: State:
DatalinkA
SW3–4
On
Off
Datalink B
SW3–5
Datalink C
SW3–6
Datalink D
SW3–7
Truncate
Last Datalink
SW3–8
On
Off
On
Off
On
Off
On
Off
Input and output parameter assignments in the drive:
Reserves Data In/Out A for this adapter
Data In/Out A not used by this adapter
Reserves Data In/Out B for this adapter
Data In/Out B not used by this adapter
Reserves Data In/Out C for this adapter
Data In/Out C not used by this adapter
Reserves Data In/Out D for this adapter
Data In/Out D not used by this adapter
Truncates the last datalink to one word
No truncation performed
Publication 1203–5.1 –– July, 1997
3–4
Programmable
Controller
I/O Image Table
Output Image
Blk Transfer
Logic Command
Reference
WORD 3
WORD 4
WORD 5
WORD 6
WORD 7
Configuration and Interfacing
Figure 3.2
Typical Programmable Controller Configuration Using Datalink A
Remote I/O
Communications
Module
Drive
Datalink A
Parameters
Data In A1
Data In A2
Data Out A1
Data Out A2
Input Image
Blk Transfer
Logic Status
Feedback
WORD 3
WORD 4
WORD 5
WORD 6
WORD 7
NOTE: This configuration requires a minimum rack size of 3 /
4
rack.
SW3
SW3
Block Transfer On
Logic Command On
Reference/Feedback On
Datalink A On
Datalink B Off
Datalink C Off
Datalink D Off
Truncate last Datalink Off
AB0504B
Publication 1203–5.1 –– July, 1997
Programmable Controller
I/O Image Table
Output Image
Logic Command
Reference
WORD 2
WORD 3
WORD 4
WORD 5
WORD 6
WORD 7
Input Image
Logic Status
Feedback
WORD 2
WORD 3
WORD 4
WORD 5
WORD 6
WORD 7
NOTE: This configuration requires a minimum rack size of
3
/
4
rack.
Configuration and Interfacing
Figure 3.3
Typical Programmable Controller Configuration for 1305 and 1336
PLUS/FORCE without Block Transfer
Remote I/O
Communications
Module
1336 PLUS/FORCE
Controller
Datalink A
Datalink C
Parameters
Data In A1
Data In A2
Data In B1
Data In B2
Data In C1
Data In C2
Data In D1
Data In D2
SW3
Datalink A
Datalink C
Data Out A1
Data Out A2
Data Out B1
Data Out B2
Data Out C1
Data Out C2
Data Out D1
Data Out D2
SW3
Block Transfer Off
Logic Cmd/Sts On
Reference/Feedback On
Datalink A On
Datalink B Off
Datalink C On
Datalink D Off
Truncate Last Datalink Off
AB0505A
3–5
Publication 1203–5.1 –– July, 1997
3–6 Configuration and Interfacing
Figure 3.4
Typical Programmable Controller Configuration for 1305 and 1336
PLUS/FORCE with Block Transfer
Remote I/O
Communications
Module
1336 PLUS/FORCE
Controller
Programmable Controller
I/O Image Table
Output Image
Block Transfer
Logic Command
Reference
WORD 3
WORD 4
WORD 5
WORD 6
WORD 7
Datalink A
Datalink B*
Parameters
Data In A1 Data
In A2
Data In B1
Data In B2
Input Image
Block Transfer
Logic Status
Feedback
WORD 3
WORD 4
WORD 5
WORD 6
WORD 7
*NOTE: Datalink B has been truncated on a
1/4 rack boundary. Only the first word of Datalink B is transferred. This configuration requires a minimum rack size of 3/4 rack.
SW3
Datalink A
Datalink B*
SW3
Data Out A1
Data Out A2
Data Out B1
Data Out B2
Block Transfer On
Logic Cmd/Sts On
Reference/Feedback On
Datalink A On
Datalink B On
Datalink C Off
Datalink D Off
Truncate Last Datalink On
AB0506A
Publication 1203–5.1 –– July, 1997
Programmable
Controller I/O
Image Table
Output Image
Logic Command
WORD 1 REF
WORD 2
WORD 3
WORD 4
WORD 5
WORD 6
WORD 7
Input Image
Logic Status
Feedback
WORD 2
WORD 3
WORD 4
WORD 5
WORD 6
WORD 7
*NOTE: While the reference is sent via the SCANport to the SMP3, the reference is ignored by the SMP3.
SW3
Configuration and Interfacing
Figure 3.5
Typical Programmable Controller Configuration for SMP3
SMP3 Remote I/O
Communications
Module
SW3
Block Transfer Off
Logic Cmd/Sts On
Feedback On
Datalink A Off
Datalink B Off
Datalink C Off
Datalink D Off
Truncate Last Datalink Off
AB0507A
3–7
Publication 1203–5.1 –– July, 1997
3–8 Configuration and Interfacing
Programmable
Controller I/O
Image Table
Output Image
Logic Command
Figure 3.6
Typical Programmable Controller Configuration for SMC Dialog Plus without
Block Transfer
SMC Dialog Plus Remote I/O
Communications
Module
Input Image
Logic Status
Feedback
➀
SW3
➀
Current Phase A
SW3
Block Transfer Off
Logic Cmd/Sts On
Reference/Feedback Off
Datalink A Off
Datalink B Off
Datalink C Off
Datalink D Off
Truncate Last Datalink Off
AB0507A
Publication 1203–5.1 –– July, 1997
Programmable
Controller I/O
Image Table
Output Image
Block Transfer
Logic Command
Configuration and Interfacing
Figure 3.7
Typical Programmable Controller Configuration for SMC Dialog Plus with
Block Transfer
SMC Dialog Plus Remote I/O
Communications
Module
3–9
Input Image
Block Transfer
Logic Status
Feedback
➀
SW3
➀
Current Phase A
SW3
Block Transfer On
Logic Cmd/Sts On
Reference/Feedback Off
Datalink A Off
Datalink B Off
Datalink C Off
Datalink D Off
Truncate Last Datalink Off
AB0536A
Publication 1203–5.1 –– July, 1997
3–10 Configuration and Interfacing
Figure 3.8
SLC 5/02 TM Controller Example
Example Information:
PLC Type –
Drive Type –
Drive Rack Address –
Rack Size –
Starting Module Group –
SLC 5/02
1336 PLUS
2
1/2 Rack Minimum
0
Block Transfer Off
Logic Cmd/Sts On
Reference/Fdbk On
Datalink A On
Datalink B Off
Datalink C Off
Datalink D Off
Truncate Last Datalink Off
PLC
WORD
0
1
2
3
PLC Image Table Map
OUTPUT
IMAGE
Logic Cmd
Reference
Datalink A
Datalink A
INPUT
IMAGE
Logic Sts
Feedback
Datalink A
Datalink A
When the Machine Start PushButton is pressed, the PLC sends a START command to the drive. The drive will start if no STOP command is being sent by the PLC or any other control device. (Start button is a normally open contact in this example.)
Machine
START
Pushbutton
I : 1.8
0
Drive
START
Command
0 : 1.16
1
When the Machine Stop Pushbutton is pressed, the PLC sends a STOP command to the drive. (Stop button is normally closed contact in this example).
Machine
STOP
Button
I : 1.8
Drive
STOP
Command
0 : 1.16
0
1
Drive Stop
Command
0 : 1.16
Drive Running
Bit
I : 1.16
0 1
This rung transfers a frequency command from the PLC data table to the drive. A range of 0 to 32767 is equivalent to Zero to Maximum Frequency. (In this example, the drive’s Frequency Select parameters are set to receive a frequency reference from the RIO Adapter.)
MOV
Drive Frequency
Command
MOVE
Source
Dest
N7 : 0
16000
0: 1.17
16000
AB0508A
Publication 1203–5.1 –– July, 1997
Configuration and Interfacing 3–11
SLC 5/02 Example continued
When the Machine JOG Pushbutton is pressed, the PLC will send a JOG command to the drive. (Jog button is a normally open contact in this example.)
Machine
JOG
Pushbutton
I : 1.8
Drive
JOG
Command
0 : 1.16
2 2
When the Machine Clear Faults Pushbutton is pressed, the PLC sends a Clear Faults command to the drive. (Clear Faults button is a momentary normally open contact in this example.)
Machine Clear
Faults
Pushbutton
I : 1.8
Drive
Clear Faults
Command
0 : 1.16
3 3
When the Drive is running, the PLC will receive a Drive Running Status Bit.
Drive
Running
Status Bit
I : 1.16
1
Machine
Running
Indicator
0 : 1.8
1
When the drive is faulted, the PLC will receive a Drive Faulted Status Bit.
Drive
Faulted
Status Bit
I : 1.16
7
This rung moves a value from the PLC data table into the drive parameter specified by the Data In A1 parameter of the drive.
Machine
Faulted
Indicator
0 : 1.8
7
MOV
MOVE
Source
Dest
Drive Data In A1
(Data to Drive)
N7 : 1
500
0: 1.18
0
END OF FILE
Publication 1203–5.1 –– July, 1997
3–12 Configuration and Interfacing
Figure 3.9
PLC 5/15 Controller Example
Example Information:
PLC Type –
Drive Type –
Drive Rack Address –
Rack Size –
Starting Module Group –
PLC 5/15
1336 PLUS
2
1/2 Rack Minimum
0
Block Transfer Off
Logic Cmd/Sts On
Reference/Fdbk On
Datalink A On
Datalink B Off
Datalink C Off
Datalink D Off
Truncate Last Datalink Off
PLC
WORD
0
1
2
3
PLC Image Table Map
OUTPUT
IMAGE
Logic Cmd
Reference
Datalink A
Datalink A
INPUT
IMAGE
Logic Sts
Feedback
Datalink A
Datalink A
When the Machine Start Pushbutton is pressed, the PLC sends a START command to the drive. The drive will start if no STOP command is being sent to the PLC or any other control device. (Start button is a normally open contact in this example.)
Machine
START
Pushbutton
I : 000
00
Drive
START
Command
0 : 020
01
When the Machine Stop Pushbutton is pressed, the PLC sends a STOP command to the drive. (Stop button is normally closed contact in this example).
Machine
STOP
Button
I : 000
Drive
STOP
Command
0 : 020
00
01
Drive Stop
Command
0 : 020
Drive Running
Bit
I : 020
00 01
This rung transfers a frequency command from the PLC data table to the drive. A range of 0 to 32767 is equivalent to Zero to Maximum Frequency. (In this example, the drive’s Frequency Select parameters are set to receive a frequency reference from the RIO Adapter.)
Drive Frequency
Command
MOV
MOVE
Source
Dest
N7 : 0
16000
0: 021
16000
Publication 1203–5.1 –– July, 1997
Configuration and Interfacing 3–13
PLC 5/15 Example continued
When the Machine JOG Pushbutton is pressed, the PLC will send a JOG command to the drive. The drive will start and run at the programmed Jog
Frequency if no STOP command is being sent by the PLC or other control device. (Jog button is a normally open contact in this example.)
Machine
JOG
Pushbutton
I : 000
Drive
JOG
Command
0 : 020
02 02
When the Machine Clear Faults Pushbutton is pressed, the PLC sends a Clear Faults command to the drive. (Clear Faults button is a momentary normally open contact in this example.)
Machine Clear
Faults
Pushbutton
I : 000
Drive
Clear Faults
Command
0 : 020
03 03
When the Drive is running, the PLC will receive a Drive Running Status Bit.
Drive
Running
Status Bit
I : 020
01
Machine
Running
Indicator
0 : 000
00
When the drive is faulted, the PLC will receive a Drive Faulted Status Bit.
Drive
Faulted
Status Bit
I : 020
07
This rung moves a value from the PLC data table into the drive parameter specified by the Data In A1 parameter of the drive.
Machine
Faulted
Indicator
0 : 000
01
MOV
MOVE
Source
Dest
Drive Data In A1
(Data to Drive)
N7 : 1
500
0: 022
500
END OF FILE
Publication 1203–5.1 –– July, 1997
3–14 Configuration and Interfacing
This Page Intentionally Left Blank.
Publication 1203–5.1 –– July, 1997
Chapter
4
Troubleshooting
Chapter Objectives
Chapter 4 provides information to help you troubleshoot your remote
I/O system using the LED indicators on the front of the device
(Figure 4.1). The remote I/O module is a non-serviceable device that should be returned to Allen-Bradley for replacement when a major fault exists that is attributable to the remote I/O communications module itself.
SCANport Status
(Green)
Figure 4.1
LED Locations
Adapter Fault Status
(Red) Front View
Open Version
SW3 SW2
Adapter Health
(Green)
SW1
J1
J3
Remote I/O
Active (Green)
J4
J2
Remote I/O
Status (Green)
Refer to Table 4.A for details on LED operation.
Front View
Enclosed Version
...
Remote I/O
Status (Green)
Remote I/O
Active (Green)
Adapter Health
(Green)
SCANport Status
(Green)
Adapter Fault
Status (Red)
Publication 1203–5.1 –– July, 1997
4–2 Troubleshooting
Troubleshooting Table
Table 4.A
General Indications
Indicator
Adapter Fault Status
SCANport Status
Adapter Health
Remote I/O Active
Color
Red (Steady)
Red (Blinking)
Red (Off)
Green (Steady)
Green (Off)
Green (Blinking)
Green (Steady)
Green (Off)
Green (Steady)
Green (Off)
Probably cause
Unrecoverable fault
Recoverable fault
Normal operation
Normal operation
No SCANport communication
When blinking in tandem with red fault status, a device incompatibility exists
Normal operation
Internal adapter fault
Normal operation
No data transfer from PLC/SLC
Recommended action
Replace the adapter.
Check configuration switch setting, check for SCANport cable connection.
None
SCANport is active.
Check SCANport cables, device, cycle power.
Check compatibility of drive on page 1–1 of this manual.
None.
Cycle power.
None.
Remote I/O offline, make certain the PLC is in Run Mode, check rack address, check wiring and processor.
Remote I/O Status Green (Steady)
Green (Blinking)
Green (Blinking)
Normal Operation None.
PLC is in Reset/Program/Test Mode None.
PLC has more rack space allocated than is being used
Do a PLC auto configuration.
Green (Off) No communication with processor
Check wiring to processor. Check adapter configuration in processor.
Adapter Fault Status Red (Blinking) and Configuration switch setting incorrect Check configuration switch settings.
and Adapter Health Green (Steady) Remote I/O and/or SCANport cable not wired or connected properly
Check SCANport and remote I/O cable connections.
Publication 1203–5.1 –– July, 1997
Chapter
5
Specifications
Chapter Objectives
Chapter 5 provides you with background information and specifications that you may need to install, repair, or apply your remote I/O communications module.
Product Specifications
Environmental
Operating temperature
Storage temperature
Relative humidity
Electrical
Input voltage
Input frequency
Input current
SCANport load
Communications
Drive side
PLC side
Baud rates
Rack size
Dimensions
Enclosure type
Package size
Table 5.A
General Indications
Open Style
(1336–GM1)
Enclosed Style –– 115V ac
(1203–GD1)
0–50
°
C (32–122
°
F)
–40–85
°
C (–40–158
°
F)
0–95%, non–condensing
0–50
°
C (32–122
°
F)
–40–85
°
C (–40–158
°
F)
0–95%, non–condensing
Supplied by drive
NA
NA
60 mA
Open (IP00)
Not applicable
85–264V ac, 1 ph
45–63 Hz
35 mA maximum
60 mA
SCANport peripheral interface
Allen Bradley remote I/O
57.6K, 115.2K, or 230.4K
1/4, 1/2, 3/4, or full
NEMA 1 (IP30)
45mm x 76mm (1.8 x 3.0 in)
Enclosed Style –– 24V dc
(1203–GK1)
0–50
°
C (32–122
°
F)
–40–85
°
C (–40–158
°
F)
0–95%, non–condensing
24V dc,
±
10%
NA
0.4 amps maximum
60 mA
NEMA 1 (IP30)
45mm x 76mm (1.8 x 3.0 in)
Publication 1203–5.1 –– July, 1997
5–2 Specifications
Programmable Controller
Compatibility
"
This communications module is designed to be used with the following Allen-Bradley programmable controllers:
•
PLC-2/30
with SD2 (communications module version 1.02 or later)
•
PLC-3
•
SLC500 TM with 1747-SN scanner
•
PLC 5/10
TM
, 5/15
TM
, 5/25
TM
family
•
PLC 5/30
TM
, 5/40
TM
, 5/40L
TM
, 5/60
TM
, 5/60L
TM
family and
PLC-5/80
TM
•
PLC 5/250
TM
•
PLC
scanner modules and subscanners.
Note: This adapter was tested with the current revision level of the
PLC processors listed. Earlier versions of the processors may not be compatible.
Publication 1203–5.1 –– July, 1997
We Want Our Manuals to be the Best!
You can help! Our manuals must meet the needs of you, the user. This is your opportunity to make sure they do just that.
By filling out this form you can help us provide the most useful, thorough, and accurate manuals available. Please take a few minutes to tell us what you think - then mail this form or FAX it.
FAX: your local Allen-Bradley Sales Office or 414/512-8579
PUBLICATION NAME ________________________________________________________________________________________________
PUBLICATION NUMBER, DATE AND PART NUMBER (IF PRESENT) _________________________________________________________
✔
CHECK THE FUNCTION THAT MOST CLEARLY DESCRIBES YOUR JOB.
❏ SUGGEST/RESPONSIBLE FOR THE PURCHASE OF EQUIPMENT
❏ DESIGN/IMPLEMENT ELECTRICAL SYSTEMS
❏ SUPERVISE FLOOR OPERATIONS
❏ MAINTAIN/OPERATE PROGRAMMABLE MACHINERY
❏ TRAIN/EDUCATE MACHINE USERS
✔ WHAT LEVEL OF EXPERIENCE DO YOU HAVE WITH EACH OF THE FOLLOWING PRODUCTS?
PROGRAMMABLE CONTROL
AC/DC DRIVES
PERSONAL COMPUTERS
NC/CNC CONTROLS
DATA COMMUNICATIONS/LAN
NONE
❏
❏
❏
❏
❏
LITTLE
❏
❏
❏
❏
❏
MODERATE
❏
❏
❏
❏
❏
EXTENSIVE
❏
❏
❏
❏
❏
✔
RATE THE OVERALL QUALITY OF THIS MANUAL BY CIRCLING YOUR RESPONSE BELOW. (1) = POOR (5) = EXCELLENT
HELPFULNESS OF INDEX/TABLE OF CONTENTS
CLARITY
EASE OF USE
ACCURACY AND COMPLETENESS
QUALITY COMPARED TO OTHER COMPANIES’ MANUALS
QUALITY COMPARED TO OTHER ALLEN-BRADLEY MANUALS
1
1
1
1
1
1
2
2
2
2
2
2
3
3
3
3
3
3
4
4
4
4
4
4
5
5
5
5
5
5
✔
WHAT DID YOU LIKE MOST ABOUT THIS MANUAL?
✔
WHAT DID YOU LIKE LEAST ABOUT THIS MANUAL?
✔
PLEASE LIST ANY ERRORS YOU FOUND IN THIS MANUAL (REFERENCE PAGE, TABLE, OR FIGURE NUMBERS).
✔
DO YOU HAVE ANY ADDITIONAL COMMENTS?
✔ COMPLETE THE FOLLOWING.
NAME
__________________________________________________________________________
COMPANY
____________________________________________________________________________
TITLE _________________________________________________ DEPARTMENT_______________________________________________
STREET _______________________________________________ CITY _______________________ STATE ______ ZIP
___________________
TELEPHONE ___________________________________________ DATE ______________________________________________________
FOLD HERE
FOLD HERE
BUSINESS REPLY MAIL
FIRST CLASS PERMIT NO. 413 MEQUON, WI
POSTAGE WILL BE PAID BY ADDRESSEE
ALLEN-BRADLEY
Attn: Marketing Communications
P.O. Box 760
Mequon, WI 53092-9907
NO POSTAGE
NECESSARY
IF MAILED
IN THE
UNITED STATES
Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world’s leading technology companies.
Worldwide representation.
Argentina
•
Australia
•
Austria
•
Bahrain
•
Belgium
•
Brazil
•
Bulgaria
•
Canada
•
Chile
•
China, PRC
•
Colombia
•
Costa Rica
•
Croatia
•
Cyprus
•
Czech Republic
•
Denmark
•
Ecuador
•
Egypt
•
El Salvador
•
Finland
•
France
•
Germany
•
Greece
•
Guatemala
•
Honduras
•
Hong Kong
•
Hungary
•
Iceland
•
India
•
Indonesia
•
Ireland
•
Israel
•
Italy
•
Jamaica
•
Japan
•
Jordan
•
Korea
•
Kuwait
•
Lebanon
•
Malaysia
•
Mexico
•
Netherlands
•
New Zealand
•
Norway
•
Pakistan
•
Peru
•
Philippines
•
Poland
•
Portugal
•
Puerto Rico
•
Qatar
•
Romania
•
Russia–CIS
•
Saudi Arabia
•
Singapore
•
Slovakia
•
Slovenia
•
South Africa, Republic
•
Spain
•
Sweden
•
Switzerland
•
Taiwan
•
Thailand
•
Turkey
•
United Arab Emirates
•
United Kingdom
•
United States
•
Uruguay
•
Venezuela
•
Yugoslavia
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication 1203-5.1 – July 1997
Supersedes Publication 1203-5.1 – April 1995
PN74001-002-01(F)
Copyright 1997 Allen-Bradley Company, Inc. Printed in USA
advertisement
Related manuals
advertisement
Table of contents
- 5 Overview
- 5 Installation
- 5 Configuration and Interfacing
- 6 Troubleshooting
- 6 Specifications
- 7 Who Should Use this Manual?
- 7 Purpose of this Manual
- 8 Safety Precautions
- 8 Firmware Support
- 9 PLC Product Compatibility
- 9 Terms and Abbreviations
- 9 Common Techniques Used in this Manual
- 10 Allen–Bradley Support
- 11 Chapter Objectives
- 11 Adapter Description
- 11 SCANport Device Compatibility
- 15 Configuration Switches
- 15 Datalinks
- 16 Safety Precautions
- 17 Chapter Objectives
- 17 Setting the Module Configuration Switches
- 25 Mounting the Remote I/O Module
- 28 Connecting the Remote I/O Cable
- 30 Connecting the Termination Resistor
- 32 Connecting the SCANport Link
- 34 Connecting the Power Supply
- 35 Chapter Objectives
- 35 Data Table Use
- 37 Data Transfer Through the Communications Module
- 49 Chapter Objectives
- 50 Troubleshooting Table
- 51 Chapter Objectives
- 51 Product Specifications
- 52 Programmable Controller Compatibility